Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 10:43:38
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1966.64 | 406.74 | 406.74 |
Net Site Energy | 1966.64 | 406.74 | 406.74 |
Total Source Energy | 3454.05 | 714.37 | 714.37 |
Net Source Energy | 3454.05 | 714.37 | 714.37 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1331.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 289.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 109.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 59.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 634.77 | 1331.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1331.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 10.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 289.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 109.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 58.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1331.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 10.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 289.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 109.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 59.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 19.98 | 275.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 131.28 | 275.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 19.98 | 275.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 131.28 | 275.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 634.766 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 634.766 | 100.00 |
Total On-Site and Utility Electric Sources | 634.766 | 100.00 |
Total Electricity End Uses | 634.766 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 69.83 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3060.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 96.62 |
Skylight-Roof Ratio [%] | 2.10 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.6485 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 12.8090 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 5.4896 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.7537 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.7537 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 8.6485 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 12.8090 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 5.4896 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.7537 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.7537 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.7537 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-JAN-08:09 | 18-DEC-17:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 312274.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27809.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4413.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1675.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 50998.53 | 312274.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 312274.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27809.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4413.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1675.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1443.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 31.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 916.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 346.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 186.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2010.30 | 1443.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 298.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 189.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 415.77 | 298.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 298.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 189.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 415.77 | 298.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.09 |
ZONE2 FINE STORAGE DIRECT AIR | 2.65 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 4.00 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 4.00 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 156864.42 |
PSZ-OFFICE HEATING COIL | 30332.20 |
PSZ-FINE STORAGE HEATING COIL | 98859.79 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 156864.43 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.00 | 1.00 | 1.09 |
PSZ-FINE STORAGE | 2.65 | 2.65 | 2.65 | 2.65 | 2.65 | 2.65 | 1.00 | 1.000000 | 2.65 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.09 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.65 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.09 | 1207.14 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.65 | 2834.90 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.09 | 1.09 | 1.09 | 1.09 | 19358.72 | 30332.20 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.65 | 2.65 | 2.65 | 2.65 | 59777.15 | 98859.79 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.09 | 0.545153 | 1.09 | 19358.72 | 9944.02 | 19358.72 | 0.800770 | 0.800770 |
PSZ-FINE STORAGE COOLING COIL | 2.65 | 1.32 | 2.65 | 59777.15 | 29679.50 | 59777.15 | 0.731730 | 0.731730 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 121 | 97 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 25.27 | 11 | 23 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 71.35 | 6 | 68 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 8.649 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 16.722 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 12.809 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.809 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 5.490 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.048 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2048.656 | 8.649 | 160.695 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2048.656 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 17848.242 | 12.809 | 594.941 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 17848.242 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 17593.267 | 5.490 | 254.975 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 17593.267 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1041 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.4317E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.4042E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 9.529 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 23.09 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 24.66 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
2 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
3 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
4 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
5 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
6 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
7 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
8 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
9 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
10 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
11 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
12 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
13 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
14 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
15 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
16 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.40943546E-08 | -0.48941433E-14 | 0.10002011E-14 | -0.40158259E-16 |
55 | 6 | 0.31272124E-05 | 0.19933103E-08 | 0.31973031E-02 | -0.26821658E-04 |
56 | 5 | -0.21335304E-03 | 0.11766416E-05 | -0.22414699 | 0.19598788E-02 |
57 | 4 | 0.48316011E-02 | 0.53476752E-04 | 4.8365802 | -0.45332602E-01 |
58 | 3 | -0.42187430E-01 | 0.42463702E-03 | -38.061149 | 0.39909293 |
59 | 2 | 0.14945981 | 0.70555311E-03 | 116.56127 | -1.4189736 |
60 | 1 | -0.21550367 | 0.21454475E-03 | -143.95282 | 2.0497880 |
61 | 0 | 0.10501452 | 0.52166033E-05 | 60.838472 | |
62 | 7 | -0.99354594E-08 | 0.85994744E-15 | -0.36446392E-14 | 0.33402613E-16 |
63 | 6 | 0.19007305E-05 | 0.85218543E-09 | 0.32020323E-02 | -0.26861330E-04 |
64 | 5 | -0.10257637E-03 | 0.49552608E-06 | -0.22441548 | 0.19622488E-02 |
65 | 4 | 0.21308868E-02 | 0.22341873E-04 | 4.8410464 | -0.45375540E-01 |
66 | 3 | -0.17974913E-01 | 0.17625076E-03 | -38.086349 | 0.39937154 |
67 | 2 | 0.62772635E-01 | 0.29099605E-03 | 116.61028 | -1.4196292 |
68 | 1 | -0.89915137E-01 | 0.87799409E-04 | -143.98166 | 2.0502620 |
69 | 0 | 0.43667207E-01 | 0.21083643E-05 | 60.838472 | |
70 | 7 | -0.10614037E-07 | 0.12466653E-14 | -0.85452615E-14 | 0.12855439E-15 |
71 | 6 | 0.18765462E-05 | 0.80237200E-09 | 0.32022472E-02 | -0.26863133E-04 |
72 | 5 | -0.98338504E-04 | 0.46542478E-06 | -0.22442766 | 0.19623563E-02 |
73 | 4 | 0.20165412E-02 | 0.20956150E-04 | 4.8412485 | -0.45377483E-01 |
74 | 3 | -0.16916006E-01 | 0.16514078E-03 | -38.087488 | 0.39938413 |
75 | 2 | 0.58934009E-01 | 0.27235831E-03 | 116.61249 | -1.4196588 |
76 | 1 | -0.84323034E-01 | 0.82076304E-04 | -143.98296 | 2.0502833 |
77 | 0 | 0.40927925E-01 | 0.19639094E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20666597E-14 | 0.96147816E-16 | 0.79647225E-12 | 0.11382549E-15 |
85 | 3 | -0.56581374E-04 | 0.28930881E-06 | -0.38972706E-03 | 0.15282143E-12 |
86 | 2 | 1.1494565 | 0.62914578E-02 | 1.7513786 | -0.74717338E-04 |
87 | 1 | -17.155584 | 0.16244765 | -7.1131205 | 0.33567575 |
88 | 0 | 16.278262 | 0.10333854 | 5.6342095 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.2921_SHGC_SOUTH_0.45 | 34 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.2921_SHGC_NORTH_0.45 | 35 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.2921_SHGC_EAST_0.45 | 36 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.2921_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.45 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.456 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.456 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30035 | 0.25772 | 0.25772 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30035 | 0.25772 | 0.25772 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE2 FINE STORAGE | 17 | 0 |
2 | ZONE3 BULK STORAGE | 48 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE2 FINE STORAGE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.099 | 0.453 | 0.451 |
2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.453 | 0.451 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1004E-004 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4241E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5750E-005 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6234E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3011E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1416E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1606E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3296E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0606E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.6571E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7055E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.0285E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8827E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2405E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.7779E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7507E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.3660E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9514E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6283E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1736E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.5193E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4580E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.0450E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2702E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6868E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.9037E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5190E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0944E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2191E-004 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.5568E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1123E-004 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8493E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6318E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8365E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5373E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.9698E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0784E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7114E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6368E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5142E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3322E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2406E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3167E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3220E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4619E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3247E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0789E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3753E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0520E-003 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6471E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2679E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1287E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5877E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6107E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8083E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4244E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7830E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0446E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9797E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1607E-004 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9531E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.5135E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2717E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6600E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6460E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8538E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5183E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1771E-004 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6733E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0172E-004 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.0410E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3591E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0590E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.4343E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8405E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4398E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1661E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9407E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8539E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8974E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2840E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1774E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4900E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2871E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1887E-003 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0589E-005 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5269E-003 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2321E-005 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9680E-004 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.4317E-005 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0187E-004 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9610E-005 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5477E-004 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2089E-005 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8936E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6268E-005 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.1863E-004 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.9383E-005 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.5724E-004 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1987E-005 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.9616E-004 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5102E-005 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1486E-004 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4139E-005 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6006E-004 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0958E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1233E-004 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1046E-003 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4200E-004 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.1649E-004 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8834E-004 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1726E-004 |
113 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2106E-004 |
114 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6473E-003 |
115 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0409E-004 |
116 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8780E-003 |
117 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0126E-004 |
118 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5969E-003 |
119 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3035E-004 |
120 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0060E-004 |
121 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8926E-005 |
122 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8072E-003 |
123 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2236E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7366E-003 |
125 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1340E-005 |
126 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8016E-003 |
127 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1002E-005 |
128 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.5996E-003 |
129 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.6270E-005 |
130 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6023E-004 |
131 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0237E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.9366E-004 |
133 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9688E-005 |
134 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2407E-003 |
135 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8473E-005 |
136 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4173E-003 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9104E-005 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0434E-005 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3346E-005 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9137E-005 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1903E-005 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4366E-005 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8839E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1433E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7223E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6658E-005 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6700E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9202E-005 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1975E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8159E-005 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7481E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7481E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0101E-005 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7427E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9203E-005 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7093E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1465E-005 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9578E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2851E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1028E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2022E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7832E-004 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5598E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0647E-004 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4068E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1241E-004 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8391E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8069E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0696E-005 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7642E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3970E-005 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6155E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3760E-005 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7287E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9183E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2479E-005 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3513E-005 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8047E-005 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3320E-005 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7828E-005 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4482E-005 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0146E-005 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2872E-005 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1031E-005 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3889E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5593E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1392E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8765E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5855E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7302E-005 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8375E-005 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1426E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1481E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8605E-004 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1575E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5095E-004 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2258E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7667E-004 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7197E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9091E-004 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4290E-004 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9080E-004 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0635E-004 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2779E-004 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5767E-004 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3417E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6610E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1295E-004 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3306E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.0376E-005 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5771E-004 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.1875E-005 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0257E-004 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8755E-005 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6601E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3004E-005 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4646E-005 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8178E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4117E-005 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7902E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6218E-005 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0334E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3995E-005 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1175E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0179E-003 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1786E-005 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1404E-003 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9310E-005 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0436E-003 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0467E-004 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8470E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2340E-005 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9347E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1309E-004 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5099E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3418E-004 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4018E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7963E-004 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8535E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7956E-004 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5268E-005 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8231E-005 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4371E-005 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7905E-005 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7537E-005 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0440E-005 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5177E-005 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1298E-005 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5317E-004 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3903E-003 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4615E-004 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5836E-003 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3667E-003 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4001E-004 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7659E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5144E-005 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8194E-005 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3964E-005 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7832E-005 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7787E-005 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0429E-005 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5974E-005 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1370E-005 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1039E-003 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2365E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0720E-003 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5672E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6929E-003 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1668E-004 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8124E-003 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1239E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6768E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3144E-004 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1090E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0611E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5459E-003 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7177E-004 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8158E-003 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8061E-004 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7067E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6161E-003 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5316E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5827E-003 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4814E-004 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4493E-003 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2117E-004 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9796E-003 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4286E-005 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8073E-005 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2991E-005 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7693E-005 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6745E-005 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0297E-005 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5964E-005 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1369E-005 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4973E-004 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2142E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2857E-004 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8185E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9672E-004 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3624E-003 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1995E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9232E-003 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6702E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.0882E-005 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7029E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2731E-005 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0294E-003 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0001E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7848E-003 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0987E-005 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4886E-004 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0824E-004 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4725E-004 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6636E-004 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5609E-004 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7575E-004 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7881E-003 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7534E-004 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0752E-004 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6057E-004 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0564E-005 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8904E-004 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1153E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9029E-004 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3831E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5273E-004 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9829E-004 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7421E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3957E-004 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4507E-004 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1706E-004 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0500E-004 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6954E-004 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7432E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6371E-005 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0075E-005 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6264E-005 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6858E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2960E-005 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8266E-005 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7466E-005 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1261E-005 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2947E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7886E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1700E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7508E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4890E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0078E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5155E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1296E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0894E-005 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4345E-004 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0420E-005 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1516E-004 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2028E-005 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1842E-004 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6327E-005 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8618E-004 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3003E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3895E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0486E-004 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8562E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0616E-004 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6011E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6234E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1106E-004 |
369 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1463E-005 |
370 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7661E-005 |
371 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0369E-005 |
372 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7300E-005 |
373 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2975E-005 |
374 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9822E-005 |
375 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3970E-005 |
376 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1172E-005 |
377 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9360E-004 |
378 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4428E-005 |
379 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3825E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7400E-005 |
381 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3486E-004 |
382 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0753E-005 |
383 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6891E-004 |
384 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1889E-005 |
385 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2765E-004 |
386 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9964E-005 |
387 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0372E-004 |
388 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4955E-005 |
389 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1005E-004 |
390 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9318E-005 |
391 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6225E-004 |
392 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2685E-005 |
393 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5071E-004 |
394 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0506E-005 |
395 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6095E-004 |
396 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9938E-005 |
397 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3758E-004 |
398 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1740E-005 |
399 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7132E-005 |
400 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6576E-005 |
401 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9537E-004 |
402 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1797E-005 |
403 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8113E-004 |
404 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9887E-005 |
405 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8077E-004 |
406 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5728E-005 |
407 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2073E-004 |
408 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1151E-005 |
409 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0599E-004 |
410 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7312E-005 |
411 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0866E-005 |
412 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5293E-005 |
413 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2190E-004 |
414 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9438E-005 |
415 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3811E-004 |
416 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9170E-005 |
417 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8956E-005 |
418 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4433E-005 |
419 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9618E-005 |
420 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2742E-005 |
421 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5783E-005 |
422 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5550E-005 |
423 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6264E-005 |
424 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6523E-005 |
425 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8023E-005 |
426 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1959E-005 |
427 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2821E-005 |
428 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0650E-005 |
429 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3241E-005 |
430 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2773E-005 |
431 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8821E-005 |
432 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4273E-005 |
433 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9091E-004 |
434 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1949E-005 |
435 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9148E-004 |
436 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0638E-005 |
437 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2624E-004 |
438 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4887E-005 |
439 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3980E-004 |
440 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9222E-005 |
441 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0694E-004 |
442 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8111E-005 |
443 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1782E-004 |
444 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8138E-005 |
445 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0997E-005 |
446 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8054E-005 |
447 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9165E-005 |
448 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4312E-005 |
449 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5618E-004 |
450 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0036E-005 |
451 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3692E-004 |
452 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7895E-005 |
453 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1991E-004 |
454 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3482E-005 |
455 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1951E-004 |
456 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1128E-005 |
457 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8755E-005 |
458 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1192E-005 |
459 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5118E-005 |
460 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0467E-005 |
461 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7991E-005 |
462 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3432E-005 |
463 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6274E-005 |
464 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3215E-005 |
465 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0623E-005 |
466 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9433E-005 |
467 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7641E-005 |
468 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8736E-005 |
469 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1021E-005 |
470 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1260E-005 |
471 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2499E-005 |
472 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2391E-005 |
473 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4594E-005 |
474 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1026E-005 |
475 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4379E-005 |
476 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0602E-005 |
477 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5057E-005 |
478 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2870E-005 |
479 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2635E-005 |
480 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2402E-005 |
481 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8405E-005 |
482 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0523E-005 |
483 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9318E-005 |
484 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0274E-005 |
485 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5670E-005 |
486 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2114E-005 |
487 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7239E-005 |
488 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1883E-005 |
489 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7316E-005 |
490 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0158E-005 |
491 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3485E-005 |
492 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9394E-005 |
493 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0559E-005 |
494 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2151E-005 |
495 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9925E-005 |
496 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2891E-005 |
497 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4189E-005 |
498 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0788E-005 |
499 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9966E-005 |
500 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0008E-005 |
501 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1767E-005 |
502 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2965E-005 |
503 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6196E-005 |
504 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3211E-005 |
505 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8814E-005 |
506 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1275E-005 |
507 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6798E-005 |
508 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0678E-005 |
509 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4536E-005 |
510 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3382E-005 |
511 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0083E-005 |
512 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2900E-005 |
513 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5450E-005 |
514 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8728E-005 |
515 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3338E-005 |
516 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8125E-005 |
517 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5183E-005 |
518 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0494E-005 |
519 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7154E-005 |
520 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1873E-005 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10582.18867 | 12698.62641 | 0.90859 | 1.09031 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 28.52933 | 1.27231E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 11759.60268 | 14111.52322 | 0.34454 | 0.41345 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -32.70000 | 1.83376E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 32984.27048 | 39581.12458 | 2.20777 | 2.64932 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 42469.30381 | 50963.16457 | 1.04782 | 1.25738 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -32.70000 | 1.83376E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 130720.36075 | 156864.43291 | 3.33277 | 3.99933 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15609.66 | 1.09031 | 1.09031 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 15459.65 | 0.41345 | 0.41345 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 46824.44 | 2.64932 | 2.64932 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 59404.74 | 1.25738 | 1.25738 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09031 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.64932 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.99933 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 3.99933 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 156864.42273 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 156864.43291 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09031 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09031 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09031 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09031 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.09031 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.09031 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.64932 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.64932 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.64932 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.64932 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.64932 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.64932 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.09031 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.64932 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.09031 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.09031 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1207.14172 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.09031 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.09031 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.09031 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.09031 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.09031 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54515 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.09031 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19358.72000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 9944.01940 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19358.72000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80077 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80077 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19358.72000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30332.20235 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 30332.20235 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.64932 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.64932 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2834.90147 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.64932 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.64932 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.64932 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.64932 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.64932 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.32466 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.64932 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 59777.15000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 29679.49964 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 59777.15000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73173 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73173 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 59777.15000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 98859.78603 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 98859.78603 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 18512.5 | 11.60 | 10.93 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 57718.8 | 11.83 | 11.15 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.5468952829 | 0.5281507895 | Pass | Pass | 1.0173007893 | 0.9130685874 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 1.0527380741 | 1.0146243403 | Pass | Pass | 0.6897725684 | 0.6433047101 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 7.0691193946E-005 | 1.4563944124E-004 | Pass | Pass | 2.2923225586E-002 | 1.9634420922E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7545.39 | 949.30 | 0.00 | 120.61 | 358.12 | 8973.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.102 | 0.104 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.043 | 0.043 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.165 | 0.168 | 1393.41 | 1368.14 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.040 | 0.040 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.165 | 0.168 | 3204.84 | 3133.49 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.2921_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.659 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.2921_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.659 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.2921_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.659 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.2921_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.659 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_17 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_16 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_15 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 114.28 | 3.860 | 0.455 | 0.451 | |||||||||||||||||
North Total or Average | 6.51 | 1.659 | 0.451 | 0.452 | |||||||||||||||||
Non-North Total or Average | 107.77 | 3.993 | 0.455 | 0.451 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_17 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_16 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_15 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 8.6485 | 236.88 | 2048.66 | LightsWired | LTG_SCH_OFFICE | 51.24 | 168.00 | 50.44 | 0.0000 | Y | 19.40 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 12.8090 | 1393.41 | 17848.24 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 45.84 | 0.0000 | Y | 153.59 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 5.4896 | 3204.84 | 17593.27 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 35.22 | 0.0000 | Y | 116.32 |
Interior Lighting Total | 7.7537 | 4835.13 | 37490.17 | 289.32 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17848.24 | 6603.85 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17848.24 | 6603.85 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17593.27 | 6509.51 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17593.27 | 6509.51 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6986.42 | AstronomicalClock | - | 83.52 | 83.52 | 109.53 | |
Exterior Lighting Total | 6986.42 | 109.53 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19358.72 | 15501.88 | 3856.84 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 59777.15 | 43740.73 | 16036.42 | 0.73 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 18512.5 | 11.60 | 10.93 | ||||
PSZ-FINE STORAGE COOLING COIL | 57718.8 | 11.83 | 11.15 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 156864.42 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 30332.20 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 98859.79 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 4.00 | 371.58 | 92.91 | 1.00 | 3.24 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.09 | 1207.14 | 1107.16 | 1.00 | 1.38 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.65 | 2834.90 | 1070.05 | 1.00 | 1.28 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10582.19 | 12698.63 | 53.61 | 0.909 | 1.090 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 23.90 | 23.90 | 0.00849 | 28.53 | 0.01272 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 32984.27 | 39581.12 | 28.41 | 2.208 | 2.649 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00891 | 30.10 | 0.01273 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 30.58 | 0.01279 | 29.98 | 0.01273 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11759.60 | 14111.52 | 59.57 | 0.345 | 0.413 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00771 | -32.70 | 0.00018 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 42469.30 | 50963.16 | 36.57 | 1.048 | 1.257 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00668 | -32.70 | 0.00018 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 130720.36 | 156864.43 | 48.95 | 3.333 | 3.999 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00565 | -32.70 | 0.00018 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.09 | 1.09 | 0.41 | 0.41 | 1.0903 | 1.0903 | 1.0903 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.65 | 2.65 | 1.26 | 1.26 | 2.6493 | 2.6493 | 2.6493 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 156864.423 | 156864.423 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 156864.42 | 156864.42 | 3.999329 | 10.00 | 7.45 | 0.00565334 | 43.33 | 21.64 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 10.00 | 0.00565334 | 71.2302 | 156864.43 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 19358.720 | 15501.882 | 1.090310 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 19358.72 | 16896.49 | 1.090310 | 25.30 | 16.73 | 0.00888905 | 12.00 | 10.89 | 0.00800000 | 28.86 | 0.01272368 | 20.77 | 9.3812 | 23.90 | 0.00849146 | 44.0726 | 10567.43 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 30332.202 | 30332.202 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 30332.20 | 30332.20 | 1.090306 | 16.01 | 11.55 | 0.00700841 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 9.3813 | 21.10 | 0.00771497 | 47.5266 | 11759.60 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 59777.150 | 43740.734 | 2.649320 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 59777.15 | 49387.46 | 2.649320 | 28.15 | 18.18 | 0.00951988 | 12.00 | 10.89 | 0.00800000 | 30.10 | 0.01272586 | 21.13 | 16.0310 | 26.70 | 0.00890780 | 39.1175 | 32984.27 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 98859.786 | 98859.786 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 98859.79 | 98859.79 | 2.649324 | 7.82 | 6.39 | 0.00563523 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 16.0309 | 15.55 | 0.00667607 | 58.3380 | 42469.30 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 156864.423 | 156864.423 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 3.999329 | 4.61492522 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 156864.42 | 156864.42 | 1.0000 | 4.61492522 | 3.999329 | 10.00 | 7.45 | 0.00565334 | 24288.5 | 43.33 | 21.64 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 156864.42 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 10.00 | 0.00565334 | 10.00 | 0.00565334 | 71.2302 | 156864.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19358.720 | 15501.882 | 1.090310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3643 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.090306 | 1.25813110 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | Sensible | 19358.72 | 16896.49 | 1.0000 | 1.25813581 | 1.090310 | 25.30 | 16.73 | 0.00888905 | 48075.2 | 12.00 | 10.89 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19358.72 | 28.86 | 0.01272368 | 20.77 | 0.10228463 | 9.3812 | 23.90 | 0.00849146 | 23.90 | 0.00849146 | 44.0726 | 10567.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30332.202 | 30332.202 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.090306 | 1.25813110 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 30332.20 | 30332.20 | 1.0000 | 1.25813110 | 1.090306 | 16.01 | 11.55 | 0.00700841 | 33821.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30332.20 | -32.70 | 0.00018338 | -32.70 | 0.10228463 | 9.3813 | 21.05 | 0.00771497 | 21.10 | 0.00771497 | 47.5266 | 11759.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 59777.150 | 43740.734 | 2.649320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.5370 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.649324 | 3.05712033 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 59777.15 | 49387.46 | 1.0000 | 3.05711620 | 2.649320 | 28.15 | 18.18 | 0.00951988 | 52592.4 | 12.00 | 10.89 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59777.15 | 30.10 | 0.01272586 | 21.13 | 0.42471127 | 16.0310 | 26.70 | 0.00890780 | 26.70 | 0.00890780 | 39.1175 | 32984.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 98859.786 | 98859.786 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.649324 | 3.05712033 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 98859.79 | 98859.79 | 1.0000 | 3.05712033 | 2.649324 | 7.82 | 6.39 | 0.00563523 | 22031.9 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 98859.79 | -32.70 | 0.00018338 | -32.70 | 0.42471127 | 16.0309 | 15.55 | 0.00667607 | 15.55 | 0.00667607 | 58.3380 | 42469.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.09 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.65 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2834.50 | 2746.50 | 2150.17 |
ZONE2 FINE STORAGE | 3206.33 | 3059.83 | 2688.17 |
ZONE3 BULK STORAGE | 3199.00 | 3336.00 | 2936.50 |
Facility | 3523.33 | 3438.00 | 3060.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 182.67 | 0.00 | 42.00 | 0.00 |
ZONE2 FINE STORAGE | 544.17 | 8.67 | 24.67 | 0.00 |
ZONE3 BULK STORAGE | 35.00 | 0.00 | 16.17 | 0.00 |
Facility | 700.17 | 8.67 | 69.83 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.733 | 0.447 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.623 | 0.246 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.152 | 0.000 | 0.080 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.29 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.04 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2635279.22 | 0.00 | 2635279.22 | 2325123.62 | 4960402.84 | 3225648.14 | 5713.84 | 2199.87 | 846.29 | 0.07 |
ZONE2 FINE STORAGE | 6659419.88 | 0.00 | 6659419.88 | 6606177.37 | 13265597.25 | 13393694.68 | 5703.51 | 2467.50 | 588.99 | 14.22 |
ZONE3 BULK STORAGE | 0.00 | 19687801.42 | 19687801.42 | 38498288.51 | 58186089.93 | 30805497.77 | 8242.43 | 55.67 | 461.91 | 4777.50 |
Total Facility | 9294699.11 | 19687801.42 | 28982500.52 | 47429589.50 | 76412090.02 | 47424840.58 | 8483.58 | 2655.33 | 1454.04 | 4778.28 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.2013 | 0.0000 | 0.2013 | 0.1239 | 0.3252 | 0.1023 | 589.91 | 2199.87 | 846.21 |
ZONE2 FINE STORAGE | 0.5024 | 0.0000 | 0.5024 | 0.2003 | 0.7027 | 0.4247 | 593.07 | 2467.50 | 575.43 |
ZONE3 BULK STORAGE | 0.0000 | 0.7760 | 0.7760 | 1.5030 | 2.2790 | 0.9768 | 3344.08 | 27.83 | 264.08 |
Total Facility | 0.7037 | 0.7760 | 1.4797 | 1.8272 | 3.3069 | 1.5038 | 3359.58 | 2627.50 | 1242.86 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3508986.48 | 0.00 | 3508986.48 | 3225648.14 | 5711.41 | 0.06 | 3048.54 | 0.07 |
PSZ-FINE STORAGE | 8867301.10 | 0.00 | 8867301.10 | 13393694.68 | 5698.56 | 0.17 | 3061.27 | 14.22 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2681 | 0.0000 | 0.2681 | 0.1023 | 587.48 | 0.06 | 3048.46 |
PSZ-FINE STORAGE | 0.6689 | 0.0000 | 0.6689 | 0.4247 | 588.28 | 0.17 | 3047.55 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2666.01 | 384.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2714.45 | 360.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2903 | 0.5237 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.7319 | 1.2719 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 69 | 69 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 444 |
Defaulted Fields | 429 |
Fields with Defaults | 1213 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 147 |
Autocalculatable Fields | 244 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 634.77 | 2265.47 | 16-APR-11:50 | 50998.53 | 09-JAN-08:10 |
Electricity:Building | 428.85 | 1782.47 | 26-FEB-11:40 | 41466.67 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 51.34 | 860.99 | 01-JAN-00:10 | 3141.26 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 428.61 | 1782.47 | 26-FEB-11:40 | 41466.67 | 02-JAN-09:10 |
InteriorLights:Electricity | 289.32 | 1208.72 | 26-FEB-11:40 | 31354.05 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 19.40 | 287.24 | 01-JAN-00:10 | 1228.76 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 289.32 | 1208.72 | 26-FEB-11:40 | 31354.05 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 289.32 | 1208.72 | 26-FEB-11:40 | 31354.05 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 19.40 | 287.24 | 01-JAN-00:10 | 1228.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 289.32 | 1208.72 | 26-FEB-11:40 | 31354.05 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 153.60 | 464.05 | 26-FEB-11:40 | 15171.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 153.60 | 464.05 | 26-FEB-11:40 | 15171.01 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 153.60 | 464.05 | 26-FEB-11:40 | 15171.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 223.91 | 457.42 | 15-JAN-11:30 | 23154.40 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 116.32 | 457.42 | 15-JAN-11:30 | 14954.28 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 116.32 | 457.42 | 15-JAN-11:30 | 14954.28 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 59.03 | 0.00 | 19-MAR-12:00 | 6347.34 | 29-JUN-15:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.25 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-16:50 |
Ventilation (simple):Fans:Electricity | 0.25 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-16:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.25 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-16:50 |
ElectricityPurchased:Facility | 634.77 | 2265.47 | 16-APR-11:50 | 50998.53 | 09-JAN-08:10 |
ElectricityPurchased:Plant | 634.77 | 2265.47 | 16-APR-11:50 | 50998.53 | 09-JAN-08:10 |
Cogeneration:ElectricityPurchased | 634.77 | 2265.47 | 16-APR-11:50 | 50998.53 | 09-JAN-08:10 |
General:Cogeneration:ElectricityPurchased | 634.77 | 2265.47 | 16-APR-11:50 | 50998.53 | 09-JAN-08:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 634.77 | 2265.47 | 16-APR-11:50 | 50998.53 | 09-JAN-08:10 |
ElectricityNet:Plant | 634.77 | 2265.47 | 16-APR-11:50 | 50998.53 | 09-JAN-08:10 |
Cogeneration:ElectricityNet | 634.77 | 2265.47 | 16-APR-11:50 | 50998.53 | 09-JAN-08:10 |
General:Cogeneration:ElectricityNet | 634.77 | 2265.47 | 16-APR-11:50 | 50998.53 | 09-JAN-08:10 |
Electricity:HVAC | 68.88 | 0.00 | 19-MAR-12:00 | 19922.03 | 29-JUN-16:00 |
General:Fans:Electricity | 58.79 | 0.00 | 19-MAR-12:00 | 4413.62 | 02-JAN-07:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 10.09 | 0.00 | 01-JAN-00:10 | 15879.99 | 29-JUN-16:00 |
General:Cooling:Electricity | 10.09 | 0.00 | 01-JAN-00:10 | 15879.99 | 29-JUN-16:00 |
ExteriorLights:Electricity | 109.53 | 0.00 | 01-JAN-08:20 | 6986.42 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 109.53 | 0.00 | 01-JAN-08:20 | 6986.42 | 01-JAN-00:10 |
Electricity:Plant | 27.50 | 483.00 | 03-JAN-23:20 | 3106.71 | 25-FEB-12:20 |
WaterSystems:Electricity | 27.50 | 483.00 | 03-JAN-23:20 | 3106.71 | 25-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 27.50 | 483.00 | 03-JAN-23:20 | 3106.71 | 25-FEB-12:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1331.87 | 0.00 | 12-MAR-12:00 | 312274.90 | 18-DEC-17:10 |
NaturalGas:HVAC | 1331.87 | 0.00 | 12-MAR-12:00 | 312274.90 | 18-DEC-17:10 |
Heating:NaturalGas | 1331.87 | 0.00 | 12-MAR-12:00 | 312274.90 | 18-DEC-17:10 |
General:Heating:NaturalGas | 1331.87 | 0.00 | 12-MAR-12:00 | 312274.90 | 18-DEC-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2106.69 | 0.00 | 19-MAR-12:00 | 468929.65 | 18-DEC-17:10 |
EnergyTransfer:Building | 1041.39 | 0.00 | 19-MAR-12:00 | 234425.04 | 04-JAN-08:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 77.60 | 0.00 | 01-JAN-00:40 | 31535.86 | 09-JAN-08:00 |
Heating:EnergyTransfer | 988.52 | 0.00 | 19-MAR-12:00 | 234425.04 | 04-JAN-08:00 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 59.12 | 0.00 | 01-JAN-00:40 | 31535.86 | 09-JAN-08:00 |
General:Heating:EnergyTransfer | 988.52 | 0.00 | 19-MAR-12:00 | 234425.04 | 04-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 59.12 | 0.00 | 01-JAN-00:40 | 31535.86 | 09-JAN-08:00 |
Cooling:EnergyTransfer | 52.87 | 0.00 | 01-JAN-00:10 | 32972.53 | 29-JUN-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 18.49 | 0.00 | 01-JAN-00:10 | 11167.11 | 29-JUN-16:10 |
General:Cooling:EnergyTransfer | 52.87 | 0.00 | 01-JAN-00:10 | 32972.53 | 29-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 18.49 | 0.00 | 01-JAN-00:10 | 11167.11 | 29-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 210.00 | 0.00 | 01-JAN-00:40 | 64462.26 | 12-FEB-22:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 175.62 | 0.00 | 01-JAN-00:40 | 64462.26 | 12-FEB-22:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 175.62 | 0.00 | 01-JAN-00:40 | 64462.26 | 12-FEB-22:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 34.38 | 0.00 | 01-JAN-00:10 | 29046.52 | 07-JUL-17:50 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 34.38 | 0.00 | 01-JAN-00:10 | 29046.52 | 07-JUL-17:50 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 753.79 | 0.00 | 13-JAN-14:00 | 158399.01 | 18-DEC-13:20 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 753.79 | 0.00 | 13-JAN-14:00 | 158399.01 | 18-DEC-13:20 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 753.79 | 0.00 | 13-JAN-14:00 | 158399.01 | 18-DEC-13:20 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1065.30 | 0.00 | 12-MAR-12:00 | 244563.08 | 18-DEC-17:10 |
HeatingCoils:EnergyTransfer | 1024.57 | 0.00 | 12-MAR-12:00 | 244563.08 | 18-DEC-17:10 |
CoolingCoils:EnergyTransfer | 40.73 | 0.00 | 01-JAN-00:10 | 58162.67 | 29-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 59.114 | -18.486 | 0.000 | 0.000 | 10.115 | 19.398 | 31.946 | 12.131 | 0.000 | 0.424 | 0.000 | 0.000 | -9.765 | 0.000 | -48.771 | -56.106 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 175.617 | -34.380 | 0.000 | 0.000 | 25.960 | 153.596 | 0.000 | 34.010 | 0.000 | 0.393 | 0.002 | 0.000 | -35.313 | 0.000 | -126.040 | -193.842 |
ZONE3 BULK STORAGE | 753.788 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 68.906 | 116.324 | 107.344 | 343.903 | 0.000 | 10.436 | 0.012 | 0.000 | -417.170 | 0.000 | -758.766 | -224.767 |
Total Facility | 753.788 | 0.000 | 234.731 | -52.866 | 0.000 | 0.000 | 104.981 | 289.319 | 139.290 | 390.045 | 0.000 | 11.253 | 0.014 | 0.000 | -462.248 | 0.000 | -933.577 | -474.715 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-JUN-07:02 | 0.00 | 0.00 | 0.00 | -22869.03 | 0.00 | 0.00 | 801.53 | 1228.76 | 1912.50 | 361.39 | 0.00 | 0.00 | 18830.92 | 0.00 | -0.00 | 0.00 | -266.08 | 0.00 |
ZONE2 FINE STORAGE | 07-JUL-17:11 | 0.00 | 0.00 | 0.00 | -61184.33 | 0.00 | 0.00 | 0.00 | 1564.70 | 0.00 | 2931.06 | 0.00 | 0.00 | 58543.44 | 0.00 | -0.00 | 0.00 | -1854.86 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-JUL-17:11 | 0.00 | 0.00 | 0.00 | -61184.33 | 0.00 | 0.00 | 0.00 | 2960.31 | 2623.78 | 48644.09 | 0.00 | 0.00 | 24427.12 | 0.00 | 0.00 | 0.00 | -17470.97 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 04-JAN-06:31 | 0.00 | 0.00 | 32763.20 | 0.00 | 0.00 | 0.00 | 155.67 | 367.04 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1142.15 | 0.00 | -5804.22 | -26913.29 |
ZONE2 FINE STORAGE | 05-JAN-06:41 | 0.00 | 0.00 | 103531.38 | 0.00 | 0.00 | 0.00 | 384.91 | 1784.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4002.92 | 0.00 | -11982.59 | -89715.61 |
ZONE3 BULK STORAGE | 18-DEC-13:20 | 158396.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8367.17 | 7576.83 | 8200.12 | 0.00 | 0.00 | 0.00 | 7858.04 | 0.00 | -11171.96 | 0.00 | -179226.74 | 0.00 |
Total Facility | 04-JAN-06:01 | 157244.29 | 0.00 | 129511.56 | 0.00 | 0.00 | 0.00 | 1474.92 | 3911.19 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -54130.90 | 0.00 | -174180.41 | -66454.42 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0903 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0903 | 0.0938 | 1.0000 | Not calculated | 0.1023 | 0.0938 | ||
PSZ-FINE STORAGE | 2.6493 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6493 | 0.1603 | 1.0000 | Not calculated | 0.4247 | 0.1603 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0903 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0903 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0938 | ||
PSZ-FINE STORAGE | 2.6493 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6493 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1603 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0903 | 1.0903 | 1.0903 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6493 | 2.6493 | 2.6493 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0903 | 1.0903 | 1.0903 | 1.0903 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6493 | 2.6493 | 2.6493 | 2.6493 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0903 | 1.0903 | 1.0903 | No | 0.1023 | 0.2474 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6493 | 2.6493 | 2.6493 | No | 0.4247 | 0.3378 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0903 | 1.0903 | 1.0903 | 1.0903 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6493 | 2.6493 | 2.6493 | 2.6493 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 69.83 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 69.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1331.87 | 312274.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 10.09 | 15879.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 289.32 | 31354.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 109.53 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.25 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 58.79 | 4413.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 27.50 | 3106.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 634.77 |
Natural Gas | 0.00 | 1331.87 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1966.64 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 59.84 |
Space Heating | 0.00 |
Space Cooling | 2.09 |
Fans (All) | 12.21 |
Service Water Heating | 5.69 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 131.28 |
Subtotal | 131.28 |
Natural Gas [MJ/m2] | |
Space Heating | 275.46 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 275.46 |
Subtotal | 275.46 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.71 |
Space Heating | 67.72 |
Space Cooling | 0.51 |
Fans (All) | 3.00 |
Service Water Heating | 1.40 |
Receptacle Equipment | 7.08 |
Miscellaneous | 5.57 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2672. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8211.17 | 548.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8017.50 | 742.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8156.00 | 591.00 | 13.00 | 0.00 | 0.00 |
Min | 8017.50 | 548.83 | 0.00 | 0.00 | 0.00 |
Max | 8211.17 | 742.50 | 13.00 | 0.00 | 0.00 |
Average | 8128.22 | 627.44 | 4.33 | 0.00 | 0.00 |
Sum | 24384.67 | 1882.33 | 13.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33017.67 | 9.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 69423.50 | 13295.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 172816.50 | 17771.17 | 605.33 | 0.00 | 0.00 |
Min | 33017.67 | 9.33 | 0.00 | 0.00 | 0.00 |
Max | 172816.50 | 17771.17 | 605.33 | 0.00 | 0.00 |
Average | 91752.56 | 10358.67 | 201.78 | 0.00 | 0.00 |
Sum | 275257.67 | 31076.00 | 605.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7877.67 | 882.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7511.50 | 1248.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7678.83 | 1076.50 | 4.67 | 0.00 | 0.00 |
Min | 7511.50 | 882.33 | 0.00 | 0.00 | 0.00 |
Max | 7877.67 | 1248.50 | 4.67 | 0.00 | 0.00 |
Average | 7689.33 | 1069.11 | 1.56 | 0.00 | 0.00 |
Sum | 23068.00 | 3207.33 | 4.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32254.17 | 772.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 67135.50 | 15583.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 163148.83 | 27777.00 | 267.17 | 0.00 | 0.00 |
Min | 32254.17 | 772.83 | 0.00 | 0.00 | 0.00 |
Max | 163148.83 | 27777.00 | 267.17 | 0.00 | 0.00 |
Average | 87512.83 | 14711.11 | 89.06 | 0.00 | 0.00 |
Sum | 262538.50 | 44133.33 | 267.17 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:38
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 27573.00 | 0.00 |
Sum | 0.00 | 191193.00 | 82719.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76808.13 | 384.04 | 21-JAN-08:07 | -22.1 | -22.3 | 0.492842E+09 | 603.25 | 11-JAN-15:20 | -22.1 | -22.3 |
February | 117996.92 | 589.98 | 11-FEB-08:07 | -15.5 | -15.9 | 0.453877E+09 | 603.25 | 01-FEB-11:30 | -15.5 | -15.9 |
March | 1061843.36 | 961.71 | 25-MAR-07:07 | -3.2 | -3.7 | 0.532879E+09 | 603.46 | 31-MAR-15:09 | 8.40 | 2.82 |
April | 62316912.06 | 1760.38 | 13-APR-07:07 | -1.8 | -3.5 | 0.510242E+09 | 768.97 | 12-APR-15:50 | -1.8 | -3.5 |
May | 0.180525E+10 | 19971.06 | 27-MAY-07:02 | 17.20 | 13.08 | 0.622955E+09 | 879.39 | 27-MAY-07:10 | 17.20 | 13.08 |
June | 0.400058E+10 | 22867.19 | 17-JUN-07:02 | 14.05 | 11.13 | 0.659181E+09 | 879.39 | 30-JUN-07:10 | 26.02 | 21.73 |
July | 0.554177E+10 | 22134.82 | 08-JUL-07:02 | 13.40 | 11.20 | 0.639023E+09 | 879.40 | 29-JUL-07:10 | 22.48 | 20.28 |
August | 0.493157E+10 | 20767.28 | 05-AUG-07:02 | 15.78 | 12.69 | 0.687961E+09 | 879.39 | 26-AUG-07:10 | 17.57 | 15.27 |
September | 0.195212E+10 | 21954.75 | 02-SEP-07:02 | 13.17 | 11.14 | 0.611125E+09 | 879.39 | 02-SEP-07:10 | 13.17 | 11.14 |
October | 0.188721E+09 | 2170.65 | 21-OCT-15:00 | 20.00 | 11.16 | 0.520772E+09 | 768.96 | 19-OCT-14:39 | 20.00 | 11.16 |
November | 2266170.12 | 1607.56 | 04-NOV-07:07 | -4.3 | -5.3 | 0.474848E+09 | 692.54 | 01-NOV-15:00 | -4.3 | -5.3 |
December | 4633.78 | 23.17 | 30-DEC-08:07 | -4.6 | -5.3 | 0.493296E+09 | 603.25 | 04-DEC-14:09 | -4.6 | -5.3 |
Annual Sum or Average | 0.184858E+11 | 0.669900E+10 | ||||||||
Minimum of Months | 4633.78 | 23.17 | -22.1 | -22.3 | 0.453877E+09 | 603.25 | -22.1 | -22.3 | ||
Maximum of Months | 0.554177E+10 | 22867.19 | 20.00 | 13.08 | 0.687961E+09 | 879.40 | 26.02 | 21.73 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186057E+09 | 6266.46 | 27-JAN-14:20 | -14.4 | -15.6 | 0.649026E+09 | 787.42 | 14-JAN-13:09 | -14.4 | -15.6 |
February | 0.618196E+09 | 7233.70 | 11-FEB-14:30 | -6.1 | -8.0 | 0.604243E+09 | 972.21 | 28-FEB-15:00 | 6.10 | 1.55 |
March | 0.165621E+10 | 7250.16 | 23-MAR-10:20 | -4.7 | -6.4 | 0.718014E+09 | 1113.16 | 31-MAR-15:09 | 8.40 | 2.82 |
April | 0.181334E+10 | 6388.55 | 04-APR-15:00 | -3.3 | -6.8 | 0.843641E+09 | 1670.56 | 22-APR-15:09 | 18.40 | 7.85 |
May | 0.200533E+10 | 43755.31 | 25-MAY-18:55 | 27.20 | 18.51 | 0.146308E+10 | 2258.02 | 23-MAY-15:00 | 27.20 | 18.51 |
June | 0.513244E+10 | 56714.12 | 17-JUN-17:23 | 23.90 | 13.28 | 0.180849E+10 | 2246.89 | 21-JUN-12:39 | 23.30 | 15.79 |
July | 0.982311E+10 | 61187.09 | 07-JUL-17:11 | 21.50 | 13.55 | 0.184525E+10 | 2246.92 | 26-JUL-15:09 | 23.30 | 14.94 |
August | 0.631941E+10 | 60137.94 | 05-AUG-17:51 | 22.20 | 14.12 | 0.195974E+10 | 2246.90 | 05-AUG-14:09 | 22.20 | 14.12 |
September | 0.262259E+10 | 49834.44 | 01-SEP-17:51 | 23.90 | 17.82 | 0.147948E+10 | 2246.88 | 01-SEP-10:09 | 23.90 | 17.82 |
October | 0.234497E+10 | 7272.69 | 25-OCT-07:15 | -3.1 | -3.3 | 0.911278E+09 | 1793.47 | 21-OCT-15:09 | -3.1 | -3.3 |
November | 0.160535E+10 | 6052.41 | 10-NOV-13:30 | -2.2 | -5.0 | 0.674437E+09 | 1301.84 | 01-NOV-15:09 | -2.2 | -5.0 |
December | 0.254266E+09 | 5991.74 | 30-DEC-11:00 | -3.7 | -4.3 | 0.649089E+09 | 787.42 | 04-DEC-14:39 | -3.7 | -4.3 |
Annual Sum or Average | 0.343813E+11 | 0.136058E+11 | ||||||||
Minimum of Months | 0.186057E+09 | 5991.74 | -14.4 | -15.6 | 0.604243E+09 | 787.42 | -14.4 | -15.6 | ||
Maximum of Months | 0.982311E+10 | 61187.09 | 27.20 | 18.51 | 0.195974E+10 | 2258.02 | 27.20 | 18.51 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.635795E+09 | 857.46 | 27-JAN-15:09 | -14.4 | -15.6 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -23.1 | -23.5 | 0.596279E+09 | 914.22 | 11-FEB-15:09 | -6.1 | -8.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 | -3.3 | 0.716803E+09 | 1102.84 | 23-MAR-14:20 | 0.20 | -4.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.38 | 0.890835E+09 | 1898.08 | 18-APR-14:09 | 17.33 | 10.22 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.4 | 0.210803E+10 | 4279.64 | 25-MAY-15:00 | 29.10 | 19.63 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.346663E+10 | 7746.39 | 29-JUN-15:00 | 35.00 | 24.72 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.57 | 0.452956E+10 | 6646.64 | 29-JUL-15:00 | 30.60 | 21.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.417697E+10 | 5896.97 | 08-AUG-15:00 | 30.60 | 22.99 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.258674E+10 | 5521.17 | 01-SEP-15:00 | 26.10 | 17.64 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.107926E+10 | 2257.32 | 02-OCT-13:39 | 10.37 | 9.55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 | 0.666521E+09 | 1441.08 | 01-NOV-14:50 | 18.22 | 13.41 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.640596E+09 | 805.31 | 02-DEC-15:30 | -17.9 | -18.6 |
Annual Sum or Average | 0.00 | 0.220940E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.596279E+09 | 805.31 | -17.9 | -18.6 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.452956E+10 | 7746.39 | 35.00 | 24.72 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139976E+11 | 32763.09 | 04-JAN-06:31 | -29.2 |
February | 0.105090E+11 | 32353.06 | 01-FEB-06:31 | -22.8 |
March | 0.878346E+10 | 31427.33 | 15-MAR-06:12 | -22.8 |
April | 0.361494E+10 | 30801.54 | 04-APR-06:02 | -9.2 |
May | 0.541500E+09 | 30387.21 | 01-MAY-06:02 | -3.5 |
June | 0.102236E+09 | 2992.16 | 02-JUN-07:03 | 10.18 |
July | 76584040.94 | 2045.02 | 24-JUL-06:05 | 18.68 |
August | 0.112645E+09 | 1880.60 | 25-AUG-06:15 | 9.80 |
September | 0.241094E+09 | 12310.05 | 28-SEP-06:03 | 6.70 |
October | 0.224735E+10 | 30602.32 | 30-OCT-06:02 | -9.4 |
November | 0.616918E+10 | 31088.99 | 29-NOV-06:42 | -19.2 |
December | 0.127195E+11 | 32389.02 | 20-DEC-06:31 | -29.0 |
Annual Sum or Average | 0.591151E+11 | |||
Minimum of Months | 76584040.94 | 1880.60 | -29.2 | |
Maximum of Months | 0.139976E+11 | 32763.09 | 18.68 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460801E+11 | 103531.32 | 05-JAN-06:41 | -32.3 |
February | 0.331408E+11 | 101753.40 | 13-FEB-19:22 | -22.8 |
March | 0.225764E+11 | 102709.84 | 15-MAR-05:01 | -22.2 |
April | 0.750819E+10 | 98608.27 | 02-APR-05:03 | -5.7 |
May | 0.649906E+09 | 52477.98 | 01-MAY-05:01 | -3.4 |
June | 0.254262E+09 | 2880.55 | 09-JUN-07:00 | 11.70 |
July | 81025663.05 | 2559.64 | 08-JUL-07:00 | 13.30 |
August | 0.161293E+09 | 2877.92 | 07-AUG-07:00 | 13.90 |
September | 0.214691E+09 | 2849.57 | 23-SEP-07:00 | 3.90 |
October | 0.325792E+10 | 73949.34 | 30-OCT-05:01 | -9.9 |
November | 0.182998E+11 | 101569.00 | 25-NOV-02:62 | -15.7 |
December | 0.433925E+11 | 102489.74 | 26-DEC-06:01 | -26.7 |
Annual Sum or Average | 0.175617E+12 | |||
Minimum of Months | 81025663.05 | 2559.64 | -32.3 | |
Maximum of Months | 0.460801E+11 | 103531.32 | 13.90 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206801E+12 | 158220.66 | 04-JAN-10:00 | -28.9 |
February | 0.152744E+12 | 158329.41 | 12-FEB-22:30 | -16.1 |
March | 0.955018E+11 | 127188.29 | 15-MAR-05:00 | -22.2 |
April | 0.245045E+11 | 77523.01 | 04-APR-18:54 | -7.2 |
May | 94880629.22 | 10619.65 | 01-MAY-04:00 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.263603E+10 | 36828.12 | 31-OCT-20:53 | -2.2 |
November | 0.758753E+11 | 107442.59 | 25-NOV-02:00 | -15.6 |
December | 0.195632E+12 | 158399.01 | 18-DEC-13:20 | -22.8 |
Annual Sum or Average | 0.753789E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.206801E+12 | 158399.01 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162246E+10 | 1228.76 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.147976E+10 | 1228.76 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.169071E+10 | 1228.76 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.159765E+10 | 1228.76 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.165659E+10 | 1228.76 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.163177E+10 | 1228.76 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.162246E+10 | 1228.76 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.169071E+10 | 1228.76 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.159765E+10 | 1228.76 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.162246E+10 | 1228.76 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.156352E+10 | 1228.76 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.162246E+10 | 1228.76 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.193982E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.147976E+10 | 1228.76 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.169071E+10 | 1228.76 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.155682E+11 | 15171.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.127828E+11 | 15171.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.140493E+11 | 15171.01 | 03-MAR-15:20 | 0.00 | 0.00 |
April | 0.122289E+11 | 15171.01 | 04-APR-08:09 | 0.00 | 0.00 |
May | 0.104003E+11 | 13386.18 | 01-MAY-07:10 | 0.00 | 0.00 |
June | 0.102532E+11 | 13386.18 | 09-JUN-07:10 | 0.00 | 0.00 |
July | 0.102408E+11 | 13386.18 | 08-JUL-07:10 | 0.00 | 0.00 |
August | 0.115869E+11 | 15171.01 | 15-AUG-08:09 | 0.00 | 0.00 |
September | 0.122398E+11 | 15171.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.139913E+11 | 15171.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.146162E+11 | 15171.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.156380E+11 | 15171.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.153596E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.102408E+11 | 13386.18 | 0.00 | 0.00 | |
Maximum of Months | 0.156380E+11 | 15171.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.132495E+11 | 14954.28 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.100881E+11 | 14954.28 | 01-FEB-15:50 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.101803E+11 | 13194.95 | 01-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.830390E+10 | 13194.95 | 01-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.721773E+10 | 10555.96 | 01-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.703702E+10 | 11265.56 | 09-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.692441E+10 | 10555.96 | 08-JUL-06:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.807477E+10 | 13194.95 | 28-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.879895E+10 | 13194.95 | 09-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.103178E+11 | 13194.95 | 02-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.124454E+11 | 14954.28 | 02-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.136865E+11 | 14954.28 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.116324E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.692441E+10 | 10555.96 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.136865E+11 | 14954.28 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883174E+10 |
February | 0.127628E+10 | 0.147976E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695909E+10 |
March | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587813E+10 |
April | 0.138726E+10 | 0.159765E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6118887.50 | 0.367052E+10 |
May | 0.144276E+10 | 0.165659E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58678111.76 | 0.183416E+10 |
June | 0.144276E+10 | 0.163177E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142034E+09 | 0.110896E+10 |
July | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140567E+09 | 0.862284E+09 |
August | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73661892.72 | 0.131093E+10 |
September | 0.138726E+10 | 0.159765E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3214300.34 | 0.212743E+10 |
October | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311504E+10 |
November | 0.133177E+10 | 0.156352E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490318E+10 |
December | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816971E+10 |
Annual Sum or Average | 0.168137E+11 | 0.193982E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424274E+09 | 0.487712E+11 |
Minimum of Months | 0.127628E+10 | 0.147976E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862284E+09 |
Maximum of Months | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142034E+09 | 0.883174E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.155682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217485E+11 |
February | 0.300332E+10 | 0.127828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181378E+11 |
March | 0.352563E+10 | 0.140493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128467E+11 |
April | 0.326447E+10 | 0.122289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51636537.12 | 0.956170E+10 |
May | 0.339505E+10 | 0.104003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31503979.69 | 0.499692E+10 |
June | 0.339505E+10 | 0.102532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159618E+09 | 0.365126E+10 |
July | 0.326447E+10 | 0.102408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118896E+09 | 0.296325E+10 |
August | 0.352563E+10 | 0.115869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31206351.82 | 0.416498E+10 |
September | 0.326447E+10 | 0.122398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600746E+10 |
October | 0.326447E+10 | 0.139913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678293E+10 |
November | 0.313390E+10 | 0.146162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131205E+11 |
December | 0.326447E+10 | 0.156380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220581E+11 |
Annual Sum or Average | 0.395654E+11 | 0.153596E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392860E+09 | 0.126040E+12 |
Minimum of Months | 0.300332E+10 | 0.102408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296325E+10 |
Maximum of Months | 0.352563E+10 | 0.156380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159618E+09 | 0.220581E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.132495E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102017E+12 |
February | 0.690763E+10 | 0.100881E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824608E+11 |
March | 0.810895E+10 | 0.101803E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 153009.63 | 0.551433E+11 |
April | 0.750829E+10 | 0.830390E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168844E+10 | 0.312769E+11 |
May | 0.780862E+10 | 0.721773E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276785E+10 | 0.147501E+11 |
June | 0.780862E+10 | 0.703702E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618570E+09 | 0.125603E+11 |
July | 0.750829E+10 | 0.692441E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60860593.94 | 0.178532E+11 |
August | 0.810895E+10 | 0.807477E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135423E+09 | 0.206424E+11 |
September | 0.750829E+10 | 0.879895E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93459615.17 | 0.251561E+11 |
October | 0.750829E+10 | 0.103178E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767563E+09 | 0.225350E+11 |
November | 0.720796E+10 | 0.124454E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268261E+09 | 0.501585E+11 |
December | 0.750829E+10 | 0.136865E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997257E+11 |
Annual Sum or Average | 0.910005E+11 | 0.116324E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640058E+10 | 0.534279E+12 |
Minimum of Months | 0.690763E+10 | 0.692441E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125603E+11 |
Maximum of Months | 0.810895E+10 | 0.136865E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276785E+10 | 0.102017E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1228.76 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 24626.17 | 04-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1228.76 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 23690.16 | 14-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1228.76 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 19855.46 | 15-MAR-06:20 |
April | 1680.92 | 01-APR-07:10 | 1228.76 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 422.59 | 23-APR-16:00 | 12836.70 | 04-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1228.76 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.96 | 25-MAY-16:10 | 8700.92 | 01-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 1228.76 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4428.76 | 29-JUN-16:10 | 4873.87 | 09-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1228.76 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2140.54 | 28-JUL-16:10 | 4919.91 | 27-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1228.76 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2757.72 | 08-AUG-16:10 | 5541.06 | 25-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 1228.76 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 712.21 | 01-SEP-16:10 | 7819.19 | 06-SEP-06:03 |
October | 1680.92 | 02-OCT-07:10 | 1228.76 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12547.46 | 30-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1228.76 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 16402.30 | 29-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1228.76 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 23651.06 | 20-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4873.87 | |||||
Maximum of Months | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4428.76 | 24626.17 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 15171.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 26759.88 | 04-JAN-16:10 |
February | 3955.50 | 01-FEB-08:09 | 15171.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 32643.51 | 12-FEB-23:00 |
March | 3955.50 | 01-MAR-08:09 | 15171.01 | 03-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 19931.53 | 14-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 15171.01 | 04-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3089.60 | 23-APR-16:00 | 16287.34 | 26-APR-15:10 |
May | 3955.50 | 01-MAY-07:10 | 13386.18 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1099.42 | 10-MAY-17:40 | 8916.45 | 20-MAY-06:20 |
June | 3955.50 | 01-JUN-07:10 | 13386.18 | 09-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4467.65 | 29-JUN-16:00 | 8779.90 | 09-JUN-08:00 |
July | 3955.50 | 01-JUL-07:10 | 13386.18 | 08-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3054.69 | 15-JUL-15:10 | 5894.70 | 08-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 15171.01 | 15-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2305.49 | 08-AUG-16:00 | 11080.36 | 17-AUG-15:05 |
September | 3955.50 | 01-SEP-07:10 | 15171.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 9227.57 | 20-SEP-06:20 |
October | 3955.50 | 02-OCT-07:10 | 15171.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 10713.64 | 31-OCT-17:00 |
November | 3955.50 | 01-NOV-07:10 | 15171.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 16086.57 | 22-NOV-01:35 |
December | 3955.50 | 01-DEC-08:09 | 15171.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 32861.76 | 18-DEC-16:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 13386.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5894.70 | ||||
Maximum of Months | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4467.65 | 32861.76 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 14954.28 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 155787.13 | 04-JAN-12:00 |
February | 9097.65 | 01-FEB-08:09 | 14954.28 | 01-FEB-15:50 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 121616.72 | 12-FEB-22:55 |
March | 9097.65 | 01-MAR-08:09 | 13194.95 | 01-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 192.33 | 26-MAR-16:00 | 77070.42 | 14-MAR-15:50 |
April | 9097.65 | 01-APR-07:10 | 13194.95 | 01-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31724.94 | 23-APR-16:00 | 53593.69 | 26-APR-15:00 |
May | 9097.65 | 01-MAY-07:10 | 10555.96 | 01-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20348.81 | 10-MAY-15:00 | 28033.21 | 20-MAY-07:10 |
June | 9097.65 | 01-JUN-07:10 | 11265.56 | 09-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11978.69 | 29-JUN-14:53 | 37856.54 | 09-JUN-09:00 |
July | 9097.65 | 01-JUL-07:10 | 10555.96 | 08-JUL-06:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6664.87 | 15-JUL-14:00 | 46414.61 | 03-JUL-10:55 |
August | 9097.65 | 01-AUG-07:10 | 13194.95 | 28-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5904.66 | 08-AUG-16:00 | 54600.19 | 17-AUG-14:00 |
September | 9097.65 | 01-SEP-07:10 | 13194.95 | 09-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4820.87 | 24-SEP-15:00 | 31730.32 | 20-SEP-07:10 |
October | 9097.65 | 02-OCT-07:10 | 13194.95 | 02-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18557.53 | 19-OCT-15:00 | 37518.71 | 05-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 14954.28 | 02-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9581.05 | 01-NOV-14:00 | 64879.42 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 14954.28 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 140365.42 | 18-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 10555.96 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28033.21 | |||||
Maximum of Months | 9097.65 | 14954.28 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 31724.94 | 155787.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 384.04 | 21-JAN-08:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.62 |
February | 589.98 | 11-FEB-08:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.09 |
March | 961.71 | 25-MAR-07:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.55 |
April | 1760.38 | 13-APR-07:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1941.11 |
May | 19971.06 | 27-MAY-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.50 |
June | 22867.19 | 17-JUN-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.08 |
July | 22134.82 | 08-JUL-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.12 |
August | 20767.28 | 05-AUG-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.66 |
September | 21954.75 | 02-SEP-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.87 |
October | 2170.65 | 21-OCT-15:00 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.04 |
November | 1607.56 | 04-NOV-07:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1355.92 |
December | 23.17 | 30-DEC-08:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1682.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23.17 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.87 | |
Maximum of Months | 22867.19 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1941.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6266.46 | 27-JAN-14:20 | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7233.70 | 11-FEB-14:30 | 3955.50 | 11428.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7250.16 | 23-MAR-10:20 | 3955.50 | 11428.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6388.55 | 04-APR-15:00 | 3955.50 | 11428.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3960.46 |
May | 43755.31 | 25-MAY-18:55 | 0.00 | 3569.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.58 | 0.00 |
June | 56714.12 | 17-JUN-17:23 | 0.00 | 4694.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.20 |
July | 61187.09 | 07-JUL-17:11 | 0.00 | 15646.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.86 |
August | 60137.94 | 05-AUG-17:51 | 0.00 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.80 |
September | 49834.44 | 01-SEP-17:51 | 0.00 | 16063.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.35 |
October | 7272.69 | 25-OCT-07:15 | 7911.00 | 26772.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6052.41 | 10-NOV-13:30 | 3955.50 | 13299.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3743.91 |
December | 5991.74 | 30-DEC-11:00 | 7911.00 | 26599.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2865.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5991.74 | 0.00 | 3569.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61187.09 | 7911.00 | 26772.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.58 | 3960.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 12315.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38081.41 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 10555.96 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60689.62 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 5277.98 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16084.62 |
April | 0.00 | 01-APR-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11249.75 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2663.74 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8756.86 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5721.24 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9479.88 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5258.10 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 1759.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6366.82 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11241.44 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 7037.31 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31457.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 1759.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2663.74 | |
Maximum of Months | 0.00 | 0.00 | 12315.29 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60689.62 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.626600E+11 | 50998.53 | 09-JAN-08:09 | 0.361330E+12 | 311673.52 | 04-JAN-17:30 |
February | 0.525128E+11 | 48514.52 | 03-FEB-15:00 | 0.264533E+12 | 292404.10 | 12-FEB-22:49 |
March | 0.562199E+11 | 46552.54 | 03-MAR-15:00 | 0.172441E+12 | 239419.34 | 15-MAR-05:10 |
April | 0.485141E+11 | 43643.23 | 01-APR-07:19 | 0.475204E+11 | 134735.98 | 04-APR-18:30 |
May | 0.453609E+11 | 42117.92 | 25-MAY-14:39 | 0.966870E+09 | 34288.08 | 01-MAY-03:49 |
June | 0.460152E+11 | 49143.83 | 30-JUN-07:10 | 1135476.15 | 1892.46 | 02-JUN-07:10 |
July | 0.477863E+11 | 45977.54 | 29-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.503256E+11 | 44726.76 | 31-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.492366E+11 | 44108.45 | 01-SEP-08:20 | 0.191923E+09 | 7298.81 | 28-SEP-06:10 |
October | 0.543259E+11 | 45729.06 | 30-OCT-08:09 | 0.114034E+11 | 70963.99 | 31-OCT-21:10 |
November | 0.583964E+11 | 50947.61 | 25-NOV-16:30 | 0.133827E+12 | 190276.26 | 25-NOV-02:09 |
December | 0.634120E+11 | 50954.82 | 30-DEC-16:00 | 0.339657E+12 | 312274.90 | 18-DEC-17:10 |
Annual Sum or Average | 0.634766E+12 | 0.133187E+13 | ||||
Minimum of Months | 0.453609E+11 | 42117.92 | 0.00 | 0.00 | ||
Maximum of Months | 0.634120E+11 | 50998.53 | 0.361330E+12 | 312274.90 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.304401E+11 | 0.120180E+11 | 0.115358E+11 | 0.00 | 0.626377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240227E+10 | 0.00 |
February | 0.243506E+11 | 0.987181E+10 | 0.105871E+11 | 0.00 | 0.549660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220663E+10 | 0.00 |
March | 0.259204E+11 | 0.959515E+10 | 0.123431E+11 | 0.00 | 0.586411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249714E+10 | 0.00 |
April | 0.221304E+11 | 0.794356E+10 | 0.114862E+11 | 0.00 | 0.461350E+10 | 0.00 | 0.00 | 30.38 | 0.00 | 0.00 | 0.00 | 0.234040E+10 | 0.00 |
May | 0.192746E+11 | 0.700039E+10 | 0.119357E+11 | 0.00 | 0.417537E+10 | 0.00 | 0.00 | 0.610670E+09 | 0.00 | 0.00 | 0.00 | 0.236410E+10 | 0.00 |
June | 0.189220E+11 | 0.612010E+10 | 0.118862E+11 | 0.00 | 0.431781E+10 | 0.00 | 0.00 | 0.251561E+10 | 0.00 | 0.00 | 0.00 | 0.225346E+10 | 0.00 |
July | 0.187877E+11 | 0.663151E+10 | 0.115358E+11 | 0.00 | 0.426399E+10 | 0.00 | 0.00 | 0.435034E+10 | 0.00 | 0.00 | 0.00 | 0.221695E+10 | 0.00 |
August | 0.213524E+11 | 0.766690E+10 | 0.123357E+11 | 0.00 | 0.436531E+10 | 0.00 | 0.00 | 0.235070E+10 | 0.00 | 0.00 | 0.00 | 0.225463E+10 | 0.00 |
September | 0.226364E+11 | 0.869809E+10 | 0.114788E+11 | 0.00 | 0.400445E+10 | 0.00 | 0.00 | 0.262956E+09 | 0.00 | 0.00 | 0.00 | 0.215590E+10 | 0.00 |
October | 0.259316E+11 | 0.103790E+11 | 0.115432E+11 | 0.00 | 0.422832E+10 | 0.00 | 0.00 | 791044.65 | 0.00 | 0.00 | 0.00 | 0.224299E+10 | 0.00 |
November | 0.286252E+11 | 0.112635E+11 | 0.110862E+11 | 0.00 | 0.520531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221618E+10 | 0.00 |
December | 0.309470E+11 | 0.123408E+11 | 0.115358E+11 | 0.00 | 0.623465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235374E+10 | 0.00 |
Annual Sum or Average | 0.289319E+12 | 0.109529E+12 | 0.139290E+12 | 0.00 | 0.590332E+11 | 0.00 | 0.00 | 0.100911E+11 | 0.00 | 0.00 | 0.00 | 0.275044E+11 | 0.00 |
Minimum of Months | 0.187877E+11 | 0.612010E+10 | 0.105871E+11 | 0.00 | 0.400445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215590E+10 | 0.00 |
Maximum of Months | 0.309470E+11 | 0.123408E+11 | 0.123431E+11 | 0.00 | 0.626377E+10 | 0.00 | 0.00 | 0.435034E+10 | 0.00 | 0.00 | 0.00 | 0.249714E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.361330E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.264533E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.172441E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.475204E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.966870E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1135476.15 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.191923E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.114034E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.133827E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.339657E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.133187E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.361330E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 31354.05 | 02-JAN-09:09 | 6986.42 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4413.62 | 02-JAN-07:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 31354.05 | 01-FEB-15:50 | 6986.42 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4413.62 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 29509.69 | 03-MAR-15:00 | 6986.42 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4413.62 | 01-MAR-07:19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27809.90 | 01-APR-07:10 | 6986.42 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4413.62 | 01-APR-06:19 | 0.00 | 0.00 | 01-APR-00:10 |
May | 24555.14 | 01-MAY-07:10 | 6986.42 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4042.04 | 01-MAY-06:40 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 25794.23 | 09-JUN-08:09 | 6986.42 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6347.34 | 29-JUN-15:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 24555.14 | 08-JUL-07:10 | 6986.42 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6347.34 | 21-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 27809.90 | 28-AUG-07:10 | 6986.42 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 4042.04 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 27809.90 | 09-SEP-07:10 | 6986.42 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 4042.04 | 01-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 29509.69 | 17-OCT-14:50 | 6986.42 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4413.62 | 12-OCT-06:19 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 31354.05 | 02-NOV-08:09 | 6986.42 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4413.62 | 03-NOV-06:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 31354.05 | 01-DEC-09:09 | 6986.42 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4413.62 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 24555.14 | 6986.42 | 10112.62 | 0.00 | 4042.04 | 0.00 | 0.00 | |||||
Maximum of Months | 31354.05 | 6986.42 | 10112.62 | 0.00 | 6347.34 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3073.14 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3106.71 | 25-FEB-12:20 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3102.62 | 06-MAR-12:30 | 0.00 |
April | 0.02 | 12-APR-15:50 | 0.00 | 0.00 | 0.00 | 3040.92 | 01-APR-11:39 | 0.00 |
May | 7837.78 | 25-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2871.59 | 03-MAY-11:39 | 0.00 |
June | 15879.99 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2654.58 | 01-JUN-11:30 | 0.00 |
July | 11666.43 | 15-JUL-15:09 | 0.00 | 0.00 | 0.00 | 2416.15 | 01-JUL-11:20 | 0.00 |
August | 11744.99 | 08-AUG-15:50 | 0.00 | 0.00 | 0.00 | 2227.92 | 01-AUG-11:00 | 0.00 |
September | 7897.93 | 01-SEP-15:30 | 0.00 | 0.00 | 0.00 | 2252.61 | 26-SEP-11:20 | 0.00 |
October | 185.92 | 19-OCT-14:00 | 0.00 | 0.00 | 0.00 | 2489.43 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2721.00 | 29-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2927.97 | 30-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2227.92 | 0.00 | ||
Maximum of Months | 15879.99 | 0.00 | 0.00 | 0.00 | 3106.71 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 50998.53 | 09-JAN-08:09 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 4413.62 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48514.52 | 03-FEB-15:00 | 31354.05 | 10112.62 | 0.00 | 0.00 | 4413.62 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 46552.54 | 03-MAR-15:00 | 29509.69 | 10112.62 | 0.00 | 0.00 | 4413.62 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43643.23 | 01-APR-07:19 | 27809.90 | 10112.62 | 0.00 | 0.00 | 4042.04 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42117.92 | 25-MAY-14:39 | 18390.06 | 10112.62 | 0.00 | 0.00 | 4042.04 | 0.00 | 0.00 | 7732.34 | 0.00 |
June | 49143.83 | 30-JUN-07:10 | 24555.14 | 10112.62 | 0.00 | 0.00 | 4042.04 | 0.00 | 0.00 | 8781.38 | 0.00 |
July | 45977.54 | 29-JUL-15:00 | 16371.08 | 10112.62 | 0.00 | 0.00 | 6347.34 | 0.00 | 0.00 | 11659.05 | 0.00 |
August | 44726.76 | 31-AUG-07:10 | 27809.90 | 10112.62 | 0.00 | 0.00 | 4042.04 | 0.00 | 0.00 | 1117.44 | 0.00 |
September | 44108.45 | 01-SEP-08:20 | 27665.32 | 10112.62 | 0.00 | 0.00 | 4042.04 | 0.00 | 0.00 | 609.09 | 0.00 |
October | 45729.06 | 30-OCT-08:09 | 29509.69 | 10112.62 | 0.00 | 0.00 | 4413.62 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 50947.61 | 25-NOV-16:30 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 4413.62 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 50954.82 | 30-DEC-16:00 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 4413.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 42117.92 | 16371.08 | 10112.62 | 0.00 | 0.00 | 4042.04 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50998.53 | 31354.05 | 10112.62 | 6986.42 | 0.00 | 6347.34 | 0.00 | 0.00 | 11659.05 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 311673.52 | 04-JAN-17:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 292404.10 | 12-FEB-22:49 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 239419.34 | 15-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 134735.98 | 04-APR-18:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 34288.08 | 01-MAY-03:49 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1892.46 | 02-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 7298.81 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 70963.99 | 31-OCT-21:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 190276.26 | 25-NOV-02:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 312274.90 | 18-DEC-17:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 312274.90 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 60.50 | 15.43 | 13.50 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
February | 39.83 | 15.27 | 7.00 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
March | 15.67 | 15.81 | 7.17 | 16.13 | 0.00 | 16.13 | 0.00 | 16.13 |
April | 3.50 | 16.38 | 2.67 | 16.57 | 0.00 | 16.57 | 0.00 | 16.57 |
May | 0.17 | 17.07 | 0.17 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 17.06 | 0.50 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
November | 5.83 | 15.94 | 3.17 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
December | 56.67 | 15.16 | 7.83 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
Annual Sum or Average | 182.67 | 15.38 | 42.00 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.50 | 17.07 | 13.50 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 114.50 | 13.93 | 4.33 | 13.92 | 0.00 | 13.92 | 0.00 | 13.92 |
February | 101.00 | 14.18 | 4.00 | 14.17 | 0.00 | 14.17 | 0.00 | 14.17 |
March | 91.00 | 14.51 | 5.50 | 14.51 | 0.00 | 14.51 | 0.00 | 14.51 |
April | 32.83 | 14.72 | 2.00 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
May | 0.83 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.38 | 0.00 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.38 | 0.00 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.00 | 27.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8.17 | 14.92 | 0.67 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
November | 81.33 | 14.57 | 4.00 | 14.57 | 0.00 | 14.57 | 0.00 | 14.57 |
December | 114.50 | 13.99 | 4.17 | 13.99 | 0.00 | 13.99 | 0.00 | 13.99 |
Annual Sum or Average | 544.17 | 14.24 | 24.67 | 14.24 | 8.67 | 14.44 | 0.00 | 14.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.50 | 14.98 | 5.50 | 14.98 | 5.50 | 27.38 | 0.00 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.00 | 8.55 | 11.33 | 8.39 | 0.00 | 8.39 | 0.00 | 8.39 |
February | 2.33 | 8.84 | 0.00 | 8.84 | 0.00 | 8.84 | 0.00 | 8.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.67 | 8.73 | 4.83 | 8.59 | 0.00 | 8.59 | 0.00 | 8.59 |
Annual Sum or Average | 35.00 | 8.63 | 16.17 | 8.47 | 0.00 | 8.47 | 0.00 | 8.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.00 | 8.84 | 11.33 | 8.84 | 0.00 | 8.84 | 0.00 | 8.84 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.66 | 300.00 | 20.66 | 300.00 | 20.66 |
February | 276.00 | 20.69 | 276.00 | 20.69 | 276.00 | 20.69 |
March | 324.00 | 20.70 | 324.00 | 20.70 | 324.00 | 20.70 |
April | 300.00 | 21.03 | 256.00 | 20.88 | 256.00 | 20.82 |
May | 227.00 | 22.53 | 105.00 | 22.38 | 57.00 | 22.09 |
June | 139.17 | 23.77 | 148.33 | 23.97 | 55.00 | 24.02 |
July | 38.83 | 24.61 | 298.50 | 24.24 | 38.83 | 24.28 |
August | 49.67 | 24.00 | 287.67 | 24.10 | 37.33 | 24.11 |
September | 203.83 | 22.87 | 58.50 | 22.94 | 25.50 | 22.86 |
October | 300.00 | 21.25 | 199.83 | 21.00 | 199.83 | 20.89 |
November | 288.00 | 20.74 | 280.67 | 20.72 | 280.67 | 20.72 |
December | 300.00 | 20.69 | 300.00 | 20.69 | 300.00 | 20.69 |
Annual Sum or Average | 2746.50 | 21.38 | 2834.50 | 21.53 | 2150.17 | 21.36 |
Minimum of Months | 38.83 | 20.66 | 58.50 | 20.66 | 25.50 | 20.66 |
Maximum of Months | 324.00 | 24.61 | 324.00 | 24.24 | 324.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.53 | 300.00 | 15.53 | 300.00 | 15.53 |
February | 276.00 | 15.61 | 276.00 | 15.61 | 276.00 | 15.61 |
March | 324.00 | 15.71 | 324.00 | 15.71 | 324.00 | 15.71 |
April | 300.00 | 17.51 | 282.33 | 17.37 | 282.33 | 17.33 |
May | 219.33 | 21.35 | 180.50 | 21.96 | 100.50 | 21.54 |
June | 163.83 | 25.39 | 240.83 | 25.92 | 110.00 | 26.05 |
July | 203.00 | 26.67 | 298.50 | 26.60 | 202.17 | 26.62 |
August | 183.33 | 26.48 | 306.50 | 26.43 | 173.67 | 26.49 |
September | 202.33 | 22.33 | 148.00 | 23.14 | 69.83 | 22.97 |
October | 300.00 | 18.22 | 261.67 | 17.96 | 261.67 | 17.87 |
November | 288.00 | 16.08 | 288.00 | 16.08 | 288.00 | 16.08 |
December | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
Annual Sum or Average | 3059.83 | 18.86 | 3206.33 | 19.24 | 2688.17 | 18.97 |
Minimum of Months | 163.83 | 15.53 | 148.00 | 15.53 | 69.83 | 15.53 |
Maximum of Months | 324.00 | 26.67 | 324.00 | 26.60 | 324.00 | 26.62 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 9.93 | 300.00 | 9.93 | 300.00 | 9.93 |
February | 276.00 | 10.03 | 276.00 | 10.03 | 276.00 | 10.03 |
March | 324.00 | 10.14 | 324.00 | 10.14 | 324.00 | 10.14 |
April | 300.00 | 11.64 | 300.00 | 11.64 | 300.00 | 11.64 |
May | 312.00 | 17.73 | 237.83 | 17.14 | 237.83 | 16.91 |
June | 278.67 | 22.98 | 152.00 | 23.44 | 128.83 | 23.57 |
July | 217.83 | 27.93 | 298.67 | 27.60 | 217.83 | 27.70 |
August | 160.17 | 25.19 | 257.83 | 25.58 | 111.17 | 25.75 |
September | 279.33 | 20.00 | 164.67 | 19.64 | 152.83 | 19.36 |
October | 300.00 | 12.88 | 300.00 | 12.88 | 300.00 | 12.88 |
November | 288.00 | 10.34 | 288.00 | 10.34 | 288.00 | 10.34 |
December | 300.00 | 9.97 | 300.00 | 9.97 | 300.00 | 9.97 |
Annual Sum or Average | 3336.00 | 14.99 | 3199.00 | 14.98 | 2936.50 | 14.69 |
Minimum of Months | 160.17 | 9.93 | 152.00 | 9.93 | 111.17 | 9.93 |
Maximum of Months | 324.00 | 27.93 | 324.00 | 27.60 | 324.00 | 27.70 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 118.42 | 30.38 | 0.83 | 118.42 | -0.0 | 0.00 | 0.00 | 12-APR-15:50 | 0.00 | 01-APR-00:10 | 0.09 | 12-APR-15:50 | 0.09 | 12-APR-15:50 | 0.00 | 01-APR-00:10 | 0.02 | 12-APR-15:50 | 0.00 | 01-APR-00:10 |
May | 0.148751E+10 | 0.371099E+09 | 85.15 | 0.130434E+10 | 0.183169E+09 | 0.00 | 1.00 | 26-MAY-07:02 | 0.00 | 01-MAY-00:10 | 20360.00 | 26-MAY-07:02 | 14789.61 | 27-MAY-07:02 | 6194.12 | 26-MAY-07:02 | 4412.87 | 26-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.428032E+10 | 0.105134E+10 | 182.73 | 0.331645E+10 | 0.963869E+09 | 0.00 | 1.00 | 10-JUN-07:03 | 0.00 | 01-JUN-00:10 | 23546.10 | 30-JUN-06:02 | 15180.38 | 17-JUN-07:02 | 10525.60 | 23-JUN-07:03 | 5046.55 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.682879E+10 | 0.164711E+10 | 232.42 | 0.508215E+10 | 0.174664E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 22998.22 | 23-JUL-16:21 | 16222.88 | 23-JUL-16:21 | 12270.27 | 05-JUL-07:02 | 5129.51 | 23-JUL-16:21 | 0.00 | 01-JUL-00:10 |
August | 0.480858E+10 | 0.115809E+10 | 206.77 | 0.348404E+10 | 0.132455E+10 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 21640.51 | 30-AUG-07:02 | 14383.86 | 05-AUG-07:02 | 11034.86 | 30-AUG-07:02 | 4634.59 | 30-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.614678E+09 | 0.150159E+09 | 62.44 | 0.524554E+09 | 90123907.40 | 0.00 | 1.00 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 | 18033.04 | 02-SEP-07:02 | 13270.58 | 02-SEP-07:02 | 8496.96 | 01-SEP-07:03 | 3935.64 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 3095543.87 | 791044.65 | 4.50 | 3095069.37 | 474.50 | 0.00 | 0.05 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 728.78 | 19-OCT-15:00 | 728.78 | 19-OCT-15:00 | 0.66 | 19-OCT-14:30 | 185.92 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.180230E+11 | 0.437859E+10 | 774.84 | 0.137146E+11 | 0.430835E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.682879E+10 | 0.164711E+10 | 232.42 | 0.508215E+10 | 0.174664E+10 | 0.00 | 1.00 | 0.00 | 23546.10 | 16222.88 | 12270.27 | 5129.51 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.901221E+09 | 0.239571E+09 | 29.38 | 0.772067E+09 | 0.129154E+09 | 0.00 | 1.00 | 25-MAY-18:55 | 0.00 | 01-MAY-00:10 | 63715.65 | 25-MAY-18:55 | 52301.39 | 25-MAY-18:55 | 11414.26 | 25-MAY-18:55 | 14707.91 | 25-MAY-18:55 | 0.00 | 01-MAY-00:10 |
June | 0.572059E+10 | 0.146427E+10 | 93.91 | 0.405755E+10 | 0.166304E+10 | 0.00 | 1.00 | 17-JUN-17:23 | 0.00 | 01-JUN-00:10 | 75257.64 | 30-JUN-01:45 | 57666.62 | 17-JUN-17:23 | 39957.24 | 30-JUN-01:45 | 16158.34 | 30-JUN-01:45 | 0.00 | 01-JUN-00:10 |
July | 0.108415E+11 | 0.270323E+10 | 183.23 | 0.761883E+10 | 0.322266E+10 | 0.00 | 1.00 | 01-JUL-17:12 | 0.00 | 01-JUL-00:10 | 74157.87 | 03-JUL-21:25 | 54235.54 | 07-JUL-17:45 | 39353.14 | 03-JUL-21:25 | 15931.27 | 23-JUL-10:05 | 0.00 | 01-JUL-00:10 |
August | 0.478804E+10 | 0.119261E+10 | 94.11 | 0.336041E+10 | 0.142764E+10 | 0.00 | 1.00 | 04-AUG-17:12 | 0.00 | 01-AUG-00:10 | 69544.55 | 08-AUG-19:15 | 55321.07 | 13-AUG-13:45 | 27335.40 | 09-AUG-19:25 | 15377.70 | 08-AUG-19:15 | 0.00 | 01-AUG-00:10 |
September | 0.454061E+09 | 0.112798E+09 | 9.69 | 0.342401E+09 | 0.111660E+09 | 0.00 | 1.00 | 01-SEP-17:11 | 0.00 | 01-SEP-00:10 | 64919.80 | 01-SEP-17:51 | 47623.20 | 01-SEP-17:11 | 17696.77 | 01-SEP-17:59 | 14296.29 | 01-SEP-17:11 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.227054E+11 | 0.571248E+10 | 410.32 | 0.161513E+11 | 0.655415E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.108415E+11 | 0.270323E+10 | 183.23 | 0.761883E+10 | 0.322266E+10 | 0.00 | 1.00 | 0.00 | 75257.64 | 57666.62 | 39957.24 | 16158.34 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.59 | 31.51 | 43.09 | 37.63 | 207.10 | 0.00 | 0.00 | 0.00 |
February | 120.51 | 55.11 | 65.40 | 89.99 | 161.23 | 0.00 | 0.00 | 0.00 |
March | 158.37 | 81.13 | 77.25 | 139.43 | 120.87 | 0.00 | 0.00 | 0.00 |
April | 201.75 | 102.06 | 99.69 | 211.27 | 70.71 | 0.00 | 0.00 | 0.00 |
May | 248.41 | 118.54 | 129.87 | 287.94 | 45.38 | 0.00 | 0.00 | 0.00 |
June | 239.42 | 103.48 | 135.94 | 285.34 | 36.59 | 0.00 | 0.00 | 0.00 |
July | 256.09 | 119.26 | 136.83 | 309.89 | 38.83 | 0.00 | 0.00 | 0.00 |
August | 209.73 | 94.90 | 114.83 | 247.49 | 44.29 | 0.00 | 0.00 | 0.00 |
September | 164.26 | 73.59 | 90.68 | 177.71 | 60.14 | 0.00 | 0.00 | 0.00 |
October | 104.03 | 41.80 | 62.23 | 96.84 | 75.63 | 0.00 | 0.00 | 0.00 |
November | 63.53 | 21.69 | 41.84 | 40.15 | 115.26 | 0.00 | 0.00 | 0.00 |
December | 56.13 | 19.58 | 36.55 | 21.55 | 199.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.28 | 71.99 | 86.29 | 162.52 | 97.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.13 | 19.58 | 36.55 | 21.55 | 36.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 256.09 | 119.26 | 136.83 | 309.89 | 207.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.59 | 31.51 | 43.09 | 37.63 | 207.10 | 0.00 | 0.00 | 0.00 |
February | 120.51 | 55.11 | 65.40 | 89.99 | 161.23 | 0.00 | 0.00 | 0.00 |
March | 158.37 | 81.13 | 77.25 | 139.43 | 120.87 | 0.00 | 0.00 | 0.00 |
April | 201.75 | 102.06 | 99.69 | 211.27 | 70.71 | 0.00 | 0.00 | 0.00 |
May | 248.41 | 118.54 | 129.87 | 287.94 | 45.38 | 0.00 | 0.00 | 0.00 |
June | 239.42 | 103.48 | 135.94 | 285.34 | 36.59 | 0.00 | 0.00 | 0.00 |
July | 256.09 | 119.26 | 136.83 | 309.89 | 38.83 | 0.00 | 0.00 | 0.00 |
August | 209.73 | 94.90 | 114.83 | 247.49 | 44.29 | 0.00 | 0.00 | 0.00 |
September | 164.26 | 73.59 | 90.68 | 177.71 | 60.14 | 0.00 | 0.00 | 0.00 |
October | 104.03 | 41.80 | 62.23 | 96.84 | 75.63 | 0.00 | 0.00 | 0.00 |
November | 63.53 | 21.69 | 41.84 | 40.15 | 115.26 | 0.00 | 0.00 | 0.00 |
December | 56.13 | 19.58 | 36.55 | 21.55 | 199.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.28 | 71.99 | 86.29 | 162.52 | 97.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.13 | 19.58 | 36.55 | 21.55 | 36.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 256.09 | 119.26 | 136.83 | 309.89 | 207.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 0.00 | 19.41 | 0.72 | 132.25 | 0.00 | 0.00 | 0.00 |
February | 29.82 | 0.00 | 29.82 | 5.08 | 100.94 | 0.00 | 0.00 | 0.00 |
March | 36.69 | 0.00 | 36.69 | 11.22 | 74.34 | 0.00 | 0.00 | 0.00 |
April | 48.21 | 0.48 | 47.73 | 32.32 | 41.29 | 0.00 | 0.00 | 0.00 |
May | 67.76 | 3.71 | 64.05 | 66.37 | 25.07 | 0.00 | 0.00 | 0.00 |
June | 75.56 | 8.36 | 67.20 | 82.97 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 72.10 | 6.17 | 65.93 | 79.48 | 21.46 | 0.00 | 0.00 | 0.00 |
August | 54.98 | 1.13 | 53.85 | 55.44 | 25.18 | 0.00 | 0.00 | 0.00 |
September | 42.72 | 0.03 | 42.69 | 34.44 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 29.63 | 0.00 | 29.63 | 16.32 | 45.37 | 0.00 | 0.00 | 0.00 |
November | 19.62 | 0.00 | 19.62 | 3.63 | 70.95 | 0.00 | 0.00 | 0.00 |
December | 16.45 | 0.00 | 16.45 | 0.20 | 126.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.81 | 1.66 | 41.15 | 32.51 | 59.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.45 | 0.00 | 16.45 | 0.20 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.56 | 8.36 | 67.20 | 82.97 | 132.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 0.00 | 19.41 | 0.71 | 132.25 | 0.00 | 0.00 | 0.00 |
February | 29.82 | 0.00 | 29.82 | 5.08 | 100.94 | 0.00 | 0.00 | 0.00 |
March | 36.69 | 0.00 | 36.69 | 11.22 | 74.34 | 0.00 | 0.00 | 0.00 |
April | 48.21 | 0.48 | 47.72 | 32.32 | 41.29 | 0.00 | 0.00 | 0.00 |
May | 67.76 | 3.71 | 64.05 | 66.37 | 25.07 | 0.00 | 0.00 | 0.00 |
June | 75.55 | 8.36 | 67.20 | 82.97 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 72.10 | 6.17 | 65.93 | 79.48 | 21.46 | 0.00 | 0.00 | 0.00 |
August | 54.98 | 1.13 | 53.85 | 55.44 | 25.18 | 0.00 | 0.00 | 0.00 |
September | 42.72 | 0.03 | 42.69 | 34.43 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 29.63 | 0.00 | 29.63 | 16.32 | 45.37 | 0.00 | 0.00 | 0.00 |
November | 19.62 | 0.00 | 19.62 | 3.63 | 70.95 | 0.00 | 0.00 | 0.00 |
December | 16.45 | 0.00 | 16.45 | 0.20 | 126.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.81 | 1.66 | 41.14 | 32.51 | 59.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.45 | 0.00 | 16.45 | 0.20 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.55 | 8.36 | 67.20 | 82.97 | 132.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_17
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_16
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_15
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 2.96 | 135.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 21.62 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 45.89 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 88.32 | 48.63 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 120.67 | 33.58 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 130.76 | 29.11 | 0.00 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 135.03 | 31.01 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 103.36 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 67.87 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 31.56 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 9.85 | 75.85 | 0.00 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 0.73 | 130.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 63.44 | 65.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 0.73 | 29.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 135.03 | 135.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 6.70 | 12.71 | 5.68 | 111.41 | 0.00 | 0.00 | 0.00 |
February | 34.42 | 15.74 | 18.68 | 28.04 | 86.00 | 0.00 | 0.00 | 0.00 |
March | 49.70 | 28.04 | 21.66 | 53.85 | 61.17 | 0.00 | 0.00 | 0.00 |
April | 72.60 | 45.69 | 26.91 | 99.31 | 35.03 | 0.33 | 0.00 | 0.00 |
May | 89.17 | 50.09 | 39.09 | 132.31 | 24.40 | 0.00 | 0.00 | 0.00 |
June | 94.16 | 54.27 | 39.88 | 137.68 | 24.05 | 7.50 | 0.00 | 0.00 |
July | 96.23 | 57.37 | 38.86 | 134.86 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 76.61 | 43.21 | 33.40 | 106.40 | 30.92 | 1.50 | 0.00 | 0.00 |
September | 55.57 | 28.71 | 26.85 | 73.26 | 34.92 | 3.17 | 0.00 | 0.00 |
October | 31.87 | 12.10 | 19.77 | 38.91 | 35.78 | 11.50 | 0.00 | 0.00 |
November | 19.01 | 5.76 | 13.25 | 15.06 | 55.88 | 12.50 | 0.00 | 0.00 |
December | 15.08 | 3.78 | 11.30 | 2.36 | 105.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.59 | 29.35 | 25.23 | 69.18 | 52.98 | 36.50 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 3.78 | 11.30 | 2.36 | 24.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.23 | 57.37 | 39.88 | 137.68 | 111.41 | 12.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.199794E+09 | 84389883.00 | 0.115404E+09 | 0.100786E+09 | 0.554689E+09 |
February | 0.291548E+09 | 0.133331E+09 | 0.158217E+09 | 0.217710E+09 | 0.390045E+09 |
March | 0.424186E+09 | 0.217289E+09 | 0.206898E+09 | 0.373458E+09 | 0.323733E+09 |
April | 0.522928E+09 | 0.264542E+09 | 0.258386E+09 | 0.547606E+09 | 0.183274E+09 |
May | 0.665338E+09 | 0.317502E+09 | 0.347836E+09 | 0.771222E+09 | 0.121553E+09 |
June | 0.620566E+09 | 0.268209E+09 | 0.352357E+09 | 0.739614E+09 | 94845068.78 |
July | 0.685903E+09 | 0.319413E+09 | 0.366490E+09 | 0.830019E+09 | 0.103993E+09 |
August | 0.561744E+09 | 0.254174E+09 | 0.307570E+09 | 0.662874E+09 | 0.118624E+09 |
September | 0.425772E+09 | 0.190738E+09 | 0.235033E+09 | 0.460624E+09 | 0.155887E+09 |
October | 0.278640E+09 | 0.111969E+09 | 0.166671E+09 | 0.259379E+09 | 0.202566E+09 |
November | 0.164664E+09 | 56212558.91 | 0.108451E+09 | 0.104070E+09 | 0.298766E+09 |
December | 0.150340E+09 | 52445171.42 | 97894864.64 | 57726233.48 | 0.534467E+09 |
Annual Sum or Average | 0.499142E+10 | 0.227021E+10 | 0.272121E+10 | 0.512509E+10 | 0.308244E+10 |
Minimum of Months | 0.150340E+09 | 52445171.42 | 97894864.64 | 57726233.48 | 94845068.78 |
Maximum of Months | 0.685903E+09 | 0.319413E+09 | 0.366490E+09 | 0.830019E+09 | 0.554689E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.199794E+09 | 84389883.00 | 0.115404E+09 | 0.100786E+09 | 0.554689E+09 |
February | 0.291548E+09 | 0.133331E+09 | 0.158217E+09 | 0.217710E+09 | 0.390045E+09 |
March | 0.424186E+09 | 0.217289E+09 | 0.206898E+09 | 0.373458E+09 | 0.323733E+09 |
April | 0.522928E+09 | 0.264542E+09 | 0.258386E+09 | 0.547606E+09 | 0.183274E+09 |
May | 0.665338E+09 | 0.317502E+09 | 0.347836E+09 | 0.771222E+09 | 0.121553E+09 |
June | 0.620566E+09 | 0.268209E+09 | 0.352357E+09 | 0.739614E+09 | 94845068.78 |
July | 0.685903E+09 | 0.319413E+09 | 0.366490E+09 | 0.830019E+09 | 0.103993E+09 |
August | 0.561744E+09 | 0.254174E+09 | 0.307570E+09 | 0.662874E+09 | 0.118624E+09 |
September | 0.425772E+09 | 0.190738E+09 | 0.235033E+09 | 0.460624E+09 | 0.155887E+09 |
October | 0.278640E+09 | 0.111969E+09 | 0.166671E+09 | 0.259379E+09 | 0.202566E+09 |
November | 0.164664E+09 | 56212558.91 | 0.108451E+09 | 0.104070E+09 | 0.298766E+09 |
December | 0.150340E+09 | 52445171.42 | 97894864.64 | 57726233.48 | 0.534467E+09 |
Annual Sum or Average | 0.499142E+10 | 0.227021E+10 | 0.272121E+10 | 0.512509E+10 | 0.308244E+10 |
Minimum of Months | 0.150340E+09 | 52445171.42 | 97894864.64 | 57726233.48 | 94845068.78 |
Maximum of Months | 0.685903E+09 | 0.319413E+09 | 0.366490E+09 | 0.830019E+09 | 0.554689E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51990863.87 | 0.00 | 51990863.87 | 1915280.24 | 0.354218E+09 |
February | 72133446.97 | 0.00 | 72133446.97 | 12285134.51 | 0.244192E+09 |
March | 98282822.99 | 7352.79 | 98275470.20 | 30043093.85 | 0.199100E+09 |
April | 0.124960E+09 | 1256703.87 | 0.123703E+09 | 83782611.99 | 0.107034E+09 |
May | 0.181487E+09 | 9924750.11 | 0.171562E+09 | 0.177764E+09 | 67147778.89 |
June | 0.195840E+09 | 21660897.00 | 0.174180E+09 | 0.215068E+09 | 52467387.81 |
July | 0.193117E+09 | 16529927.81 | 0.176587E+09 | 0.212876E+09 | 57467084.25 |
August | 0.147270E+09 | 3037828.54 | 0.144233E+09 | 0.148492E+09 | 67443638.82 |
September | 0.110730E+09 | 82776.70 | 0.110647E+09 | 89259380.67 | 92355386.57 |
October | 79364750.39 | 0.00 | 79364750.39 | 43709556.96 | 0.121518E+09 |
November | 50854377.39 | 0.00 | 50854377.39 | 9406287.60 | 0.183911E+09 |
December | 44050793.27 | 0.00 | 44050793.27 | 543569.35 | 0.337962E+09 |
Annual Sum or Average | 0.135008E+10 | 52500236.82 | 0.129758E+10 | 0.102515E+10 | 0.188482E+10 |
Minimum of Months | 44050793.27 | 0.00 | 44050793.27 | 543569.35 | 52467387.81 |
Maximum of Months | 0.195840E+09 | 21660897.00 | 0.176587E+09 | 0.215068E+09 | 0.354218E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51989147.24 | 0.00 | 51989147.24 | 1914934.01 | 0.354219E+09 |
February | 72131177.34 | 0.00 | 72131177.34 | 12283856.20 | 0.244193E+09 |
March | 98279861.15 | 7352.45 | 98272508.70 | 30040813.45 | 0.199101E+09 |
April | 0.124957E+09 | 1256644.97 | 0.123700E+09 | 83778900.24 | 0.107034E+09 |
May | 0.181481E+09 | 9924284.92 | 0.171557E+09 | 0.177758E+09 | 67147409.04 |
June | 0.195834E+09 | 21659881.72 | 0.174174E+09 | 0.215060E+09 | 52467152.90 |
July | 0.193111E+09 | 16529153.03 | 0.176582E+09 | 0.212869E+09 | 57466667.92 |
August | 0.147266E+09 | 3037686.16 | 0.144228E+09 | 0.148487E+09 | 67443326.55 |
September | 0.110726E+09 | 82772.82 | 0.110644E+09 | 89255505.25 | 92355171.78 |
October | 79362103.55 | 0.00 | 79362103.55 | 43706838.23 | 0.121518E+09 |
November | 50852644.70 | 0.00 | 50852644.70 | 9405310.16 | 0.183912E+09 |
December | 44049291.06 | 0.00 | 44049291.06 | 543433.68 | 0.337963E+09 |
Annual Sum or Average | 0.135004E+10 | 52497776.06 | 0.129754E+10 | 0.102510E+10 | 0.188482E+10 |
Minimum of Months | 44049291.06 | 0.00 | 44049291.06 | 543433.68 | 52467152.90 |
Maximum of Months | 0.195834E+09 | 21659881.72 | 0.176582E+09 | 0.215060E+09 | 0.354219E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_17
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_16
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_15
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 7922807.85 | 0.362672E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 52291795.33 | 0.255420E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.122903E+09 | 0.211152E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.228927E+09 | 0.126054E+09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.323212E+09 | 89943421.74 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.338921E+09 | 75466044.31 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361657E+09 | 83059801.77 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.276833E+09 | 89009574.29 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.175930E+09 | 0.106456E+09 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 84529286.05 | 0.132786E+09 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 25529207.47 | 0.196600E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 0.348587E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.200060E+10 | 0.207721E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 1943530.52 | 75466044.31 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361657E+09 | 0.362672E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C6
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5_C4
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8_C5
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51991182.76 | 17951615.77 | 34039566.99 | 15205200.32 | 0.298409E+09 |
February | 83271544.83 | 38069472.59 | 45202072.23 | 67827716.66 | 0.208061E+09 |
March | 0.133125E+09 | 75103927.54 | 58020665.16 | 0.144227E+09 | 0.163826E+09 |
April | 0.188167E+09 | 0.118420E+09 | 69747125.15 | 0.257404E+09 | 90788088.09 |
May | 0.238843E+09 | 0.134149E+09 | 0.104693E+09 | 0.354383E+09 | 65354362.85 |
June | 0.244056E+09 | 0.140677E+09 | 0.103379E+09 | 0.356872E+09 | 62350281.02 |
July | 0.257752E+09 | 0.153671E+09 | 0.104081E+09 | 0.361204E+09 | 86568112.09 |
August | 0.205199E+09 | 0.115741E+09 | 89457919.42 | 0.284989E+09 | 82811882.45 |
September | 0.144028E+09 | 74425566.32 | 69602249.19 | 0.189881E+09 | 90516874.15 |
October | 85353452.00 | 32402320.75 | 52951131.25 | 0.104210E+09 | 95836092.30 |
November | 49282632.67 | 14934974.26 | 34347658.41 | 39027157.89 | 0.144834E+09 |
December | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 0.281494E+09 |
Annual Sum or Average | 0.172147E+10 | 0.925671E+09 | 0.795799E+09 | 0.218154E+10 | 0.167085E+10 |
Minimum of Months | 40402290.80 | 10125104.91 | 30277185.89 | 6314978.95 | 62350281.02 |
Maximum of Months | 0.257752E+09 | 0.153671E+09 | 0.104693E+09 | 0.361204E+09 | 0.298409E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 59.84 | 661.84 | 188.01 | 63.02 | 125.00 | 0.00 | 0.00 |
February | 178.99 | 513.18 | 300.66 | 110.23 | 190.43 | 0.00 | 0.00 |
March | 295.09 | 384.20 | 390.13 | 162.26 | 227.88 | 0.00 | 0.00 |
April | 486.05 | 222.87 | 499.91 | 205.09 | 294.82 | 0.00 | 0.00 |
May | 705.94 | 138.23 | 632.33 | 244.49 | 387.84 | 0.00 | 0.00 |
June | 734.07 | 111.10 | 629.94 | 223.66 | 406.28 | 0.00 | 0.00 |
July | 776.12 | 117.94 | 656.37 | 250.85 | 405.52 | 0.00 | 0.00 |
August | 605.22 | 138.30 | 529.43 | 192.06 | 337.37 | 0.00 | 0.00 |
September | 423.26 | 190.51 | 413.97 | 147.24 | 266.73 | 0.00 | 0.00 |
October | 224.51 | 240.19 | 267.33 | 83.61 | 183.72 | 0.00 | 0.00 |
November | 82.27 | 367.15 | 166.29 | 43.37 | 122.92 | 0.00 | 0.00 |
December | 30.94 | 638.89 | 145.15 | 39.16 | 105.99 | 0.00 | 0.00 |
Annual Sum or Average | 384.68 | 309.66 | 402.17 | 147.31 | 254.87 | 0.00 | 0.00 |
Minimum of Months | 30.94 | 111.10 | 145.15 | 39.16 | 105.99 | 0.00 | 0.00 |
Maximum of Months | 776.12 | 661.84 | 656.37 | 250.85 | 406.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 50.29 | 2301.91 | 329.99 | 113.94 | 216.05 | 0.00 | 0.00 |
February | 367.46 | 1794.86 | 585.16 | 267.52 | 317.64 | 0.00 | 0.00 |
March | 780.07 | 1340.20 | 844.95 | 476.69 | 368.26 | 0.00 | 0.00 |
April | 1501.45 | 826.74 | 1234.12 | 776.67 | 457.45 | 0.00 | 0.00 |
May | 2051.45 | 570.88 | 1515.95 | 851.46 | 664.50 | 0.00 | 0.00 |
June | 2222.86 | 494.95 | 1600.68 | 922.65 | 678.03 | 0.00 | 0.00 |
July | 2295.46 | 527.19 | 1635.97 | 975.36 | 660.61 | 0.00 | 0.00 |
August | 1757.08 | 564.95 | 1302.41 | 734.62 | 567.80 | 0.00 | 0.00 |
September | 1153.86 | 698.21 | 944.63 | 488.13 | 456.50 | 0.00 | 0.00 |
October | 536.51 | 842.80 | 541.74 | 205.66 | 336.08 | 0.00 | 0.00 |
November | 167.44 | 1289.43 | 323.23 | 97.95 | 225.27 | 0.00 | 0.00 |
December | 12.34 | 2212.51 | 256.44 | 64.26 | 192.17 | 0.00 | 0.00 |
Annual Sum or Average | 1078.46 | 1119.75 | 927.99 | 499.00 | 428.99 | 0.00 | 0.00 |
Minimum of Months | 12.34 | 494.95 | 256.44 | 64.26 | 192.17 | 0.00 | 0.00 |
Maximum of Months | 2295.46 | 2301.91 | 1635.97 | 975.36 | 678.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1047.47 | 45917.56 | 931.74 | 321.71 | 610.03 | 0.00 | 0.00 |
February | 5097.63 | 34564.86 | 1652.21 | 755.35 | 896.87 | 0.00 | 0.00 |
March | 8383.43 | 22065.73 | 2385.75 | 1345.95 | 1039.80 | 0.00 | 0.00 |
April | 15824.96 | 8668.32 | 3484.57 | 2192.96 | 1291.61 | 0.00 | 0.00 |
May | 20901.01 | 3619.79 | 4280.34 | 2404.11 | 1876.22 | 0.00 | 0.00 |
June | 22567.92 | 3588.67 | 4519.56 | 2605.12 | 1914.43 | 0.00 | 0.00 |
July | 23995.71 | 4894.64 | 4619.22 | 2753.97 | 1865.25 | 0.00 | 0.00 |
August | 17638.91 | 4569.73 | 3677.40 | 2074.21 | 1603.19 | 0.00 | 0.00 |
September | 11412.71 | 5225.51 | 2667.18 | 1378.25 | 1288.93 | 0.00 | 0.00 |
October | 6015.78 | 6935.92 | 1529.63 | 580.69 | 948.95 | 0.00 | 0.00 |
November | 2460.81 | 17511.78 | 912.64 | 276.57 | 636.07 | 0.00 | 0.00 |
December | 441.29 | 43726.33 | 724.06 | 181.45 | 542.60 | 0.00 | 0.00 |
Annual Sum or Average | 11347.55 | 16715.79 | 2620.20 | 1408.94 | 1211.26 | 0.00 | 0.00 |
Minimum of Months | 441.29 | 3588.67 | 724.06 | 181.45 | 542.60 | 0.00 | 0.00 |
Maximum of Months | 23995.71 | 45917.56 | 4619.22 | 2753.97 | 1914.43 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160270E+09 | 0.177268E+10 | 0.503569E+09 | 0.168780E+09 | 0.334789E+09 | 0.00 | 0.00 |
February | 0.433010E+09 | 0.124149E+10 | 0.727361E+09 | 0.266662E+09 | 0.460699E+09 | 0.00 | 0.00 |
March | 0.790372E+09 | 0.102904E+10 | 0.104494E+10 | 0.434592E+09 | 0.610343E+09 | 0.00 | 0.00 |
April | 0.125984E+10 | 0.577682E+09 | 0.129577E+10 | 0.531597E+09 | 0.764175E+09 | 0.00 | 0.00 |
May | 0.189080E+10 | 0.370233E+09 | 0.169364E+10 | 0.654852E+09 | 0.103879E+10 | 0.00 | 0.00 |
June | 0.190271E+10 | 0.287982E+09 | 0.163281E+10 | 0.579739E+09 | 0.105307E+10 | 0.00 | 0.00 |
July | 0.207875E+10 | 0.315884E+09 | 0.175803E+10 | 0.671885E+09 | 0.108615E+10 | 0.00 | 0.00 |
August | 0.162102E+10 | 0.370425E+09 | 0.141802E+10 | 0.514423E+09 | 0.903601E+09 | 0.00 | 0.00 |
September | 0.109709E+10 | 0.493813E+09 | 0.107300E+10 | 0.381643E+09 | 0.691357E+09 | 0.00 | 0.00 |
October | 0.601337E+09 | 0.643330E+09 | 0.716006E+09 | 0.223937E+09 | 0.492069E+09 | 0.00 | 0.00 |
November | 0.213248E+09 | 0.951652E+09 | 0.431034E+09 | 0.112425E+09 | 0.318609E+09 | 0.00 | 0.00 |
December | 82877534.03 | 0.171120E+10 | 0.388780E+09 | 0.104890E+09 | 0.283890E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.121313E+11 | 0.976541E+10 | 0.126830E+11 | 0.464542E+10 | 0.803754E+10 | 0.00 | 0.00 |
Minimum of Months | 82877534.03 | 0.287982E+09 | 0.388780E+09 | 0.104890E+09 | 0.283890E+09 | 0.00 | 0.00 |
Maximum of Months | 0.207875E+10 | 0.177268E+10 | 0.175803E+10 | 0.671885E+09 | 0.108615E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.134688E+09 | 0.616543E+10 | 0.883850E+09 | 0.305177E+09 | 0.578673E+09 | 0.00 | 0.00 |
February | 0.888961E+09 | 0.434214E+10 | 0.141562E+10 | 0.647181E+09 | 0.768435E+09 | 0.00 | 0.00 |
March | 0.208934E+10 | 0.358958E+10 | 0.226312E+10 | 0.127677E+10 | 0.986351E+09 | 0.00 | 0.00 |
April | 0.389176E+10 | 0.214291E+10 | 0.319884E+10 | 0.201313E+10 | 0.118570E+10 | 0.00 | 0.00 |
May | 0.549460E+10 | 0.152904E+10 | 0.406033E+10 | 0.228054E+10 | 0.177979E+10 | 0.00 | 0.00 |
June | 0.576165E+10 | 0.128292E+10 | 0.414895E+10 | 0.239150E+10 | 0.175745E+10 | 0.00 | 0.00 |
July | 0.614817E+10 | 0.141202E+10 | 0.438179E+10 | 0.261241E+10 | 0.176938E+10 | 0.00 | 0.00 |
August | 0.470616E+10 | 0.151316E+10 | 0.348838E+10 | 0.196760E+10 | 0.152078E+10 | 0.00 | 0.00 |
September | 0.299080E+10 | 0.180975E+10 | 0.244847E+10 | 0.126523E+10 | 0.118324E+10 | 0.00 | 0.00 |
October | 0.143700E+10 | 0.225737E+10 | 0.145101E+10 | 0.550839E+09 | 0.900169E+09 | 0.00 | 0.00 |
November | 0.433997E+09 | 0.334221E+10 | 0.837805E+09 | 0.253895E+09 | 0.583910E+09 | 0.00 | 0.00 |
December | 33040018.88 | 0.592598E+10 | 0.686839E+09 | 0.172127E+09 | 0.514712E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.340102E+11 | 0.353125E+11 | 0.292650E+11 | 0.157364E+11 | 0.135286E+11 | 0.00 | 0.00 |
Minimum of Months | 33040018.88 | 0.128292E+10 | 0.686839E+09 | 0.172127E+09 | 0.514712E+09 | 0.00 | 0.00 |
Maximum of Months | 0.614817E+10 | 0.616543E+10 | 0.438179E+10 | 0.261241E+10 | 0.177979E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.280555E+10 | 0.122986E+12 | 0.249558E+10 | 0.861678E+09 | 0.163390E+10 | 0.00 | 0.00 |
February | 0.123322E+11 | 0.836193E+11 | 0.399703E+10 | 0.182733E+10 | 0.216970E+10 | 0.00 | 0.00 |
March | 0.224542E+11 | 0.591009E+11 | 0.638998E+10 | 0.360499E+10 | 0.278499E+10 | 0.00 | 0.00 |
April | 0.410183E+11 | 0.224683E+11 | 0.903201E+10 | 0.568414E+10 | 0.334786E+10 | 0.00 | 0.00 |
May | 0.559813E+11 | 0.969523E+10 | 0.114645E+11 | 0.643917E+10 | 0.502528E+10 | 0.00 | 0.00 |
June | 0.584960E+11 | 0.930183E+10 | 0.117147E+11 | 0.675248E+10 | 0.496221E+10 | 0.00 | 0.00 |
July | 0.642701E+11 | 0.131098E+11 | 0.123721E+11 | 0.737623E+10 | 0.499589E+10 | 0.00 | 0.00 |
August | 0.472441E+11 | 0.122396E+11 | 0.984955E+10 | 0.555557E+10 | 0.429398E+10 | 0.00 | 0.00 |
September | 0.295817E+11 | 0.135445E+11 | 0.691334E+10 | 0.357243E+10 | 0.334091E+10 | 0.00 | 0.00 |
October | 0.161127E+11 | 0.185772E+11 | 0.409697E+10 | 0.155531E+10 | 0.254165E+10 | 0.00 | 0.00 |
November | 0.637843E+10 | 0.453905E+11 | 0.236557E+10 | 0.716879E+09 | 0.164869E+10 | 0.00 | 0.00 |
December | 0.118194E+10 | 0.117117E+12 | 0.193931E+10 | 0.486005E+09 | 0.145330E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.357856E+12 | 0.527149E+12 | 0.826306E+11 | 0.444322E+11 | 0.381984E+11 | 0.00 | 0.00 |
Minimum of Months | 0.118194E+10 | 0.930183E+10 | 0.193931E+10 | 0.486005E+09 | 0.145330E+10 | 0.00 | 0.00 |
Maximum of Months | 0.642701E+11 | 0.122986E+12 | 0.123721E+11 | 0.737623E+10 | 0.502528E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.110855E+10 | -0.102007E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88486593.3 | 58.99 | 0.00 | 0.00 |
February | 0.103810E+10 | -958353784.0 | 0.00 | 0.00 | 672.00 | 0.00 | -79750214.3 | 59.00 | 0.00 | 0.00 |
March | 0.120349E+10 | -0.111573E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87756837.5 | 59.00 | 0.00 | 0.00 |
April | 0.108835E+10 | -0.100533E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -83013710.8 | 59.00 | 0.00 | 0.00 |
May | 0.107061E+10 | -993235885.8 | 0.00 | 0.00 | 744.00 | 0.00 | -77377675.0 | 58.99 | 0.00 | 0.00 |
June | 0.100166E+10 | -930602155.7 | 0.00 | 0.00 | 720.00 | 0.00 | -71056089.8 | 58.99 | 0.00 | 0.00 |
July | 0.922859E+09 | -852033627.2 | 0.00 | 0.00 | 744.00 | 0.00 | -70825423.3 | 59.00 | 0.00 | 0.00 |
August | 0.960778E+09 | -888789628.6 | 0.00 | 0.00 | 744.00 | 0.00 | -71988821.2 | 58.99 | 0.00 | 0.00 |
September | 0.903929E+09 | -830477372.6 | 0.00 | 0.00 | 720.00 | 0.00 | -73452088.3 | 58.99 | 0.00 | 0.00 |
October | 0.949197E+09 | -864899096.4 | 0.00 | 0.00 | 744.00 | 0.00 | -84297969.4 | 58.99 | 0.00 | 0.00 |
November | 0.964547E+09 | -879480090.6 | 0.00 | 0.00 | 720.00 | 0.00 | -85067290.9 | 58.99 | 0.00 | 0.00 |
December | 0.105994E+10 | -971527580.1 | 0.00 | 0.00 | 744.00 | 0.00 | -88415567.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.122720E+11 | -0.113105E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -961488281.1 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.903929E+09 | -0.111573E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88486593.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.120349E+10 | -830477372.6 | 0.00 | 0.00 | 744.00 | 0.00 | -70825423.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.88 | 0.51 | 24-JAN-11:00 | 119.41 | 0.00 | 0.00 | 0.00 | 91.53 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.78 | 0.26 | 17-FEB-11:00 | 154.23 | 0.00 | 0.00 | 11.50 | 744.09 | 0.00 | 0.00 | 28.33 |
March | 254.17 | 0.76 | 0.26 | 02-MAR-11:30 | 172.29 | 0.00 | 0.00 | 27.67 | 138.48 | 0.00 | 0.00 | 11.17 |
April | 296.33 | 0.73 | 0.26 | 01-APR-11:20 | 192.31 | 0.00 | 0.00 | 55.33 | 151.95 | 0.00 | 0.00 | 28.33 |
May | 437.50 | 0.65 | 0.26 | 02-MAY-10:00 | 249.70 | 0.00 | 0.00 | 148.17 | 187.01 | 0.00 | 0.00 | 80.50 |
June | 401.83 | 0.63 | 0.26 | 01-JUN-10:39 | 258.54 | 0.00 | 0.00 | 137.17 | 194.78 | 0.00 | 0.00 | 82.00 |
July | 409.17 | 0.63 | 0.26 | 01-JUL-09:50 | 260.95 | 0.00 | 0.00 | 134.33 | 199.02 | 0.00 | 0.00 | 85.00 |
August | 352.83 | 0.63 | 0.26 | 01-AUG-09:00 | 252.77 | 0.00 | 0.00 | 109.83 | 192.82 | 0.00 | 0.00 | 58.17 |
September | 344.17 | 0.71 | 0.26 | 02-SEP-11:39 | 201.57 | 0.00 | 0.00 | 62.50 | 154.31 | 0.00 | 0.00 | 12.33 |
October | 299.00 | 0.79 | 0.26 | 07-OCT-11:30 | 163.22 | 0.00 | 0.00 | 13.33 | 122.44 | 0.00 | 0.00 | 0.17 |
November | 255.50 | 0.86 | 0.51 | 18-NOV-13:09 | 121.62 | 0.00 | 0.00 | 0.00 | 144.70 | 0.00 | 0.00 | 10.33 |
December | 226.33 | 0.88 | 0.51 | 01-DEC-13:09 | 112.41 | 0.00 | 0.00 | 0.00 | 110.60 | 0.00 | 0.00 | 4.00 |
Annual Sum or Average | 3785.50 | 0.73 | 199.32 | 0.00 | 0.00 | 699.83 | 201.08 | 0.00 | 0.00 | 400.33 | ||
Minimum of Months | 226.33 | 0.63 | 0.26 | 112.41 | 0.00 | 0.00 | 0.00 | 91.53 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 437.50 | 0.88 | 0.51 | 260.95 | 0.00 | 0.00 | 148.17 | 744.09 | 0.00 | 0.00 | 85.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.69 | 0.26 | 15-JAN-11:30 | 139.30 | 13.92 | 0.00 | 55.50 | 113.89 | 14.57 | 0.00 | 17.00 |
February | 265.33 | 0.57 | 0.26 | 02-FEB-11:20 | 181.89 | 15.44 | 5.67 | 95.67 | 261.31 | 18.64 | 42.17 | 89.83 |
March | 254.17 | 0.53 | 0.26 | 02-MAR-10:39 | 876.35 | 17.80 | 44.33 | 159.00 | 777.82 | 19.22 | 60.17 | 126.67 |
April | 296.33 | 0.52 | 0.26 | 01-APR-10:39 | 904.27 | 17.70 | 59.50 | 216.83 | 581.17 | 17.06 | 58.83 | 160.17 |
May | 437.50 | 0.46 | 0.26 | 01-MAY-08:00 | 290.46 | 17.20 | 91.83 | 286.00 | 392.64 | 18.37 | 119.00 | 240.33 |
June | 401.83 | 0.45 | 0.26 | 01-JUN-07:40 | 305.47 | 17.53 | 101.17 | 291.33 | 1139.17 | 19.91 | 123.67 | 224.67 |
July | 409.17 | 0.44 | 0.26 | 01-JUL-07:40 | 308.89 | 17.76 | 111.67 | 299.83 | 713.30 | 19.50 | 129.33 | 241.67 |
August | 352.83 | 0.43 | 0.26 | 01-AUG-07:00 | 294.09 | 17.51 | 79.00 | 256.50 | 315.72 | 18.27 | 93.67 | 204.33 |
September | 344.17 | 0.50 | 0.26 | 01-SEP-10:39 | 233.54 | 16.31 | 41.50 | 192.17 | 919.45 | 17.00 | 61.83 | 151.83 |
October | 299.00 | 0.53 | 0.26 | 01-OCT-08:00 | 1074.32 | 15.19 | 3.50 | 143.17 | 979.71 | 19.73 | 71.67 | 123.17 |
November | 255.50 | 0.68 | 0.26 | 01-NOV-10:30 | 140.00 | 13.70 | 0.00 | 45.83 | 114.84 | 14.29 | 0.00 | 8.50 |
December | 226.33 | 0.71 | 0.26 | 04-DEC-10:39 | 129.38 | 13.38 | 0.00 | 25.00 | 105.85 | 13.98 | 0.00 | 3.00 |
Annual Sum or Average | 3785.50 | 0.52 | 401.40 | 16.36 | 538.17 | 2066.83 | 571.24 | 17.82 | 760.33 | 1591.17 | ||
Minimum of Months | 226.33 | 0.43 | 0.26 | 129.38 | 13.38 | 0.00 | 25.00 | 105.85 | 13.98 | 0.00 | 3.00 | |
Maximum of Months | 437.50 | 0.71 | 0.26 | 1074.32 | 17.80 | 111.67 | 299.83 | 1139.17 | 19.91 | 129.33 | 241.67 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167003E+11 | 30332.20 | 01-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123708E+11 | 30332.20 | 01-FEB-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103675E+11 | 30332.20 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398969E+10 | 30332.20 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.415103E+09 | 30332.20 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 749139.78 | 3745.70 | 02-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126901E+09 | 12039.10 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249292E+10 | 30332.20 | 04-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.711726E+10 | 30332.20 | 01-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151122E+11 | 30332.20 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.686934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167003E+11 | 30332.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.565027E+11 | 98859.79 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397490E+11 | 98859.79 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269943E+11 | 98859.79 | 01-MAR-20:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.783606E+10 | 98859.79 | 02-APR-01:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162640E+09 | 51731.66 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.305289E+10 | 73492.71 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203672E+11 | 98859.79 | 08-NOV-03:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.524442E+11 | 98859.79 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207109E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.565027E+11 | 98859.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.205814E+12 | 156864.42 | 03-JAN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151877E+12 | 156864.42 | 12-FEB-21:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.946277E+11 | 126816.71 | 15-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.241302E+11 | 77151.42 | 04-APR-18:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89640884.64 | 10248.05 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.250875E+10 | 36456.55 | 31-OCT-20:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.750810E+11 | 107071.02 | 25-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194641E+12 | 156864.42 | 16-DEC-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.748769E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205814E+12 | 156864.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 118.42 | 118.42 | 0.09 | 12-APR-15:50 | 0.09 | 0.00 |
May | 0.00 | 0.00 | 0.148751E+10 | 0.130434E+10 | 20360.00 | 26-MAY-07:02 | 14165.88 | 0.00 |
June | 0.00 | 0.00 | 0.428032E+10 | 0.331645E+10 | 23546.10 | 30-JUN-06:02 | 13607.86 | 0.00 |
July | 0.00 | 0.00 | 0.682879E+10 | 0.508215E+10 | 22998.22 | 23-JUL-16:21 | 16222.88 | 0.00 |
August | 0.00 | 0.00 | 0.480858E+10 | 0.348404E+10 | 21640.51 | 30-AUG-07:02 | 10605.64 | 0.00 |
September | 0.00 | 0.00 | 0.614678E+09 | 0.524554E+09 | 18033.04 | 02-SEP-07:02 | 13270.58 | 0.00 |
October | 0.00 | 0.00 | 3095543.87 | 3095069.37 | 728.78 | 19-OCT-15:00 | 728.78 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180230E+11 | 0.137146E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.682879E+10 | 0.508215E+10 | 23546.10 | 16222.88 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.901221E+09 | 0.772067E+09 | 63715.65 | 25-MAY-18:55 | 52301.39 | 0.00 |
June | 0.00 | 0.00 | 0.572059E+10 | 0.405755E+10 | 75257.64 | 30-JUN-01:45 | 35300.40 | 0.00 |
July | 0.00 | 0.00 | 0.108415E+11 | 0.761883E+10 | 74157.87 | 03-JUL-21:25 | 34804.73 | 0.00 |
August | 0.00 | 0.00 | 0.478804E+10 | 0.336041E+10 | 69544.55 | 08-AUG-19:15 | 42762.41 | 0.00 |
September | 0.00 | 0.00 | 0.454061E+09 | 0.342401E+09 | 64919.80 | 01-SEP-17:51 | 47259.56 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.227054E+11 | 0.161513E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108415E+11 | 0.761883E+10 | 75257.64 | 52301.39 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.986321E+09 | 0.08 | 371.58 | 01-JAN-00:01 | 0.08 |
February | 0.866152E+09 | 0.08 | 371.58 | 01-FEB-00:02 | 0.08 |
March | 0.872740E+09 | 0.07 | 371.58 | 01-MAR-00:03 | 0.08 |
April | 0.373549E+09 | 0.03 | 371.58 | 01-APR-00:10 | 0.08 |
May | 5239270.31 | 0.00 | 371.58 | 01-MAY-01:40 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.126560E+09 | 0.01 | 371.58 | 12-OCT-03:20 | 0.08 |
November | 0.793582E+09 | 0.07 | 371.58 | 01-NOV-00:10 | 0.08 |
December | 0.988104E+09 | 0.08 | 371.58 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.501225E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.988104E+09 | 0.08 | 371.58 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136739E+10 | 0.75 | 1207.14 | 12-JAN-17:20 | 0.95 |
February | 0.122292E+10 | 0.70 | 1207.14 | 01-FEB-13:30 | 0.95 |
March | 0.136162E+10 | 0.57 | 1207.14 | 01-MAR-11:00 | 0.95 |
April | 0.121584E+10 | 0.43 | 1207.14 | 01-APR-06:07 | 0.95 |
May | 0.124376E+10 | 0.36 | 1207.14 | 01-MAY-11:50 | 0.95 |
June | 0.124287E+10 | 0.37 | 1207.14 | 01-JUN-10:00 | 0.94 |
July | 0.119572E+10 | 0.35 | 1207.14 | 03-JUL-11:50 | 0.93 |
August | 0.129068E+10 | 0.37 | 1207.14 | 01-AUG-07:08 | 0.93 |
September | 0.119507E+10 | 0.36 | 1207.14 | 02-SEP-09:30 | 0.94 |
October | 0.119950E+10 | 0.36 | 1207.14 | 02-OCT-06:15 | 0.94 |
November | 0.119980E+10 | 0.51 | 1207.14 | 01-NOV-08:30 | 0.94 |
December | 0.136176E+10 | 0.72 | 1207.14 | 01-DEC-11:50 | 0.95 |
Annual Sum or Average | 0.150969E+11 | 0.49 | |||
Minimum of Months | 0.119507E+10 | 0.35 | 1207.14 | 0.93 | |
Maximum of Months | 0.136739E+10 | 0.75 | 1207.14 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.391006E+10 | 0.81 | 2834.90 | 02-JAN-09:00 | 0.92 |
February | 0.340753E+10 | 0.80 | 2834.90 | 01-FEB-12:10 | 0.92 |
March | 0.362975E+10 | 0.76 | 2834.90 | 01-MAR-07:40 | 0.92 |
April | 0.302411E+10 | 0.56 | 2834.90 | 01-APR-07:40 | 0.92 |
May | 0.292637E+10 | 0.36 | 2834.90 | 17-MAY-14:30 | 0.91 |
June | 0.296821E+10 | 0.38 | 2834.90 | 07-JUN-16:20 | 0.91 |
July | 0.292819E+10 | 0.37 | 2834.90 | 01-JUL-07:02 | 0.91 |
August | 0.307463E+10 | 0.37 | 2834.90 | 02-AUG-14:40 | 0.91 |
September | 0.280938E+10 | 0.35 | 2834.90 | 01-SEP-07:00 | 0.90 |
October | 0.290226E+10 | 0.48 | 2834.90 | 10-OCT-07:40 | 0.92 |
November | 0.321192E+10 | 0.75 | 2834.90 | 03-NOV-16:30 | 0.92 |
December | 0.388479E+10 | 0.81 | 2834.90 | 02-DEC-12:20 | 0.92 |
Annual Sum or Average | 0.386772E+11 | 0.56 | |||
Minimum of Months | 0.280938E+10 | 0.35 | 2834.90 | 0.90 | |
Maximum of Months | 0.391006E+10 | 0.81 | 2834.90 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.136739E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122292E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.136162E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.121584E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.161486E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.229421E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.284283E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.244876E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.134523E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.120029E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.119980E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.136176E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.194755E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.119980E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.284283E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.391006E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.340753E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.362975E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.302411E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.316594E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.443247E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.563142E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.426725E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.292217E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.290226E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.321192E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.388479E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.443897E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.290226E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.563142E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136739E+10 | 0.00 | 0.167003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122292E+10 | 0.00 | 0.123708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136162E+10 | 0.00 | 0.103675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121584E+10 | 118.42 | 0.398969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124376E+10 | 0.148751E+10 | 0.415103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124287E+10 | 0.428032E+10 | 749139.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119572E+10 | 0.682879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129068E+10 | 0.480858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119507E+10 | 0.614678E+09 | 0.126901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119950E+10 | 3095543.87 | 0.249292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119980E+10 | 0.00 | 0.711726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136176E+10 | 0.00 | 0.151122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150969E+11 | 0.180230E+11 | 0.686934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136739E+10 | 0.682879E+10 | 0.167003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.391006E+10 | 0.00 | 0.565027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340753E+10 | 0.00 | 0.397490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362975E+10 | 0.00 | 0.269943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.302411E+10 | 0.00 | 0.783606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.292637E+10 | 0.901221E+09 | 0.162640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.296821E+10 | 0.572059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.292819E+10 | 0.108415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.307463E+10 | 0.478804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.280938E+10 | 0.454061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.290226E+10 | 0.00 | 0.305289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321192E+10 | 0.00 | 0.203672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388479E+10 | 0.00 | 0.524442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386772E+11 | 0.227054E+11 | 0.207109E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.280938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.391006E+10 | 0.108415E+11 | 0.565027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121584E+10 | 0.00 | 0.00 | 0.00 | 30.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124376E+10 | 0.00 | 0.00 | 0.00 | 0.371099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124287E+10 | 0.00 | 0.00 | 0.00 | 0.105134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119572E+10 | 0.00 | 0.00 | 0.00 | 0.164711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129068E+10 | 0.00 | 0.00 | 0.00 | 0.115809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119507E+10 | 0.00 | 0.00 | 0.00 | 0.150159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119950E+10 | 0.00 | 0.00 | 0.00 | 791044.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150969E+11 | 0.00 | 0.00 | 0.00 | 0.437859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136739E+10 | 0.00 | 0.00 | 0.00 | 0.164711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.391006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.302411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.292637E+10 | 0.00 | 0.00 | 0.00 | 0.239571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.296821E+10 | 0.00 | 0.00 | 0.00 | 0.146427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.292819E+10 | 0.00 | 0.00 | 0.00 | 0.270323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.307463E+10 | 0.00 | 0.00 | 0.00 | 0.119261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.280938E+10 | 0.00 | 0.00 | 0.00 | 0.112798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.290226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386772E+11 | 0.00 | 0.00 | 0.00 | 0.571248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.280938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.391006E+10 | 0.00 | 0.00 | 0.00 | 0.270323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1097627.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421745E+10 | 0.00 | 0.00 | 0.12 |
February | 883736.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321745E+10 | 0.00 | 0.00 | 0.13 |
March | 7285344.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311587E+10 | 0.00 | 0.00 | 0.13 |
April | 0.429254E+09 | 0.00 | 0.00 | 19373.18 | 0.00 | 0.136908E+10 | 47264304.37 | 0.00 | 0.13 |
May | 0.455386E+09 | 53372346.57 | 0.00 | 1886191.29 | 0.00 | 0.108942E+09 | 0.128283E+10 | 0.00 | 0.35 |
June | 44630122.33 | 0.391646E+09 | 0.00 | 4246960.24 | 10381.64 | 260098.43 | 0.206601E+10 | 0.00 | 0.64 |
July | 5701195.11 | 0.696704E+09 | 0.00 | 4812580.66 | 0.00 | 0.00 | 0.152817E+10 | 0.00 | 0.58 |
August | 28361736.29 | 0.340177E+09 | 0.00 | 5449162.13 | 0.00 | 0.00 | 0.248659E+10 | 0.00 | 0.72 |
September | 0.462579E+09 | 13285330.38 | 0.00 | 2901541.10 | 0.00 | 37275532.09 | 0.234264E+10 | 0.00 | 0.44 |
October | 0.681048E+09 | 0.00 | 0.00 | 79932.97 | 0.00 | 0.100002E+10 | 0.143800E+09 | 0.00 | 0.15 |
November | 32671997.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228693E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390123E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.214890E+10 | 0.149518E+10 | 0.00 | 19395741.57 | 10381.64 | 0.192545E+11 | 0.989729E+10 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.681048E+09 | 0.696704E+09 | 0.00 | 5449162.13 | 10381.64 | 0.421745E+10 | 0.248659E+10 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134494E+11 | 0.00 | 0.00 | 0.17 |
February | 0.187994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881999E+10 | 0.00 | 0.00 | 0.17 |
March | 0.430670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559238E+10 | 0.00 | 0.00 | 0.19 |
April | 0.471588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773967E+09 | 0.00 | 0.00 | 0.18 |
May | 0.346355E+10 | 23017609.36 | 0.00 | 995340.91 | 0.00 | 0.00 | 0.753929E+09 | 0.00 | 0.24 |
June | 0.193981E+10 | 0.767275E+09 | 0.00 | 3477302.64 | 0.00 | 0.00 | 0.277356E+10 | 0.00 | 0.38 |
July | 0.341064E+09 | 0.105029E+10 | 0.00 | 8774844.47 | 0.00 | 0.00 | 0.508164E+10 | 0.00 | 0.55 |
August | 0.111309E+10 | 0.375231E+09 | 0.00 | 6981034.66 | 0.00 | 0.00 | 0.543662E+10 | 0.00 | 0.50 |
September | 0.429212E+10 | 1542793.16 | 0.00 | 1511512.60 | 0.00 | 0.00 | 0.129073E+10 | 0.00 | 0.23 |
October | 0.530695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114124E+09 | 0.00 | 0.00 | 0.17 |
November | 0.408291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301146E+10 | 0.00 | 0.00 | 0.17 |
December | 0.144788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118100E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.340443E+11 | 0.221736E+10 | 0.00 | 21740035.26 | 0.00 | 0.435713E+11 | 0.153365E+11 | 0.00 | 0.26 |
Minimum of Months | 0.341064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.530695E+10 | 0.105029E+10 | 0.00 | 8774844.47 | 0.00 | 0.134494E+11 | 0.543662E+10 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:38
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.244743E+12 | 0.176716E+12 | 0.00 | 0.188224E+11 | 0.823115E+11 |
February | 0.427081E+12 | 0.142968E+12 | 0.00 | 0.139183E+11 | 0.605371E+11 |
March | 0.648825E+12 | 0.981725E+11 | 0.00 | 0.130222E+11 | 0.404515E+11 |
April | 0.846729E+12 | 0.568536E+11 | 0.00 | 0.733547E+10 | 0.115645E+11 |
May | 0.102929E+13 | 0.263697E+11 | 0.00 | 0.599113E+10 | 0.329888E+10 |
June | 0.105738E+13 | 0.226518E+11 | 0.00 | 0.568505E+10 | 0.125169E+11 |
July | 0.109576E+13 | 0.329879E+11 | 0.00 | 0.523480E+10 | 0.220206E+11 |
August | 0.913406E+12 | 0.379229E+11 | 0.00 | 0.836919E+10 | 0.119473E+11 |
September | 0.655900E+12 | 0.475948E+11 | 0.00 | 0.841493E+10 | 0.139672E+10 |
October | 0.338711E+12 | 0.431807E+11 | 0.00 | 0.724603E+10 | 0.335271E+10 |
November | 0.143176E+12 | 0.903203E+11 | 0.00 | 0.941398E+10 | 0.312612E+11 |
December | 0.144397E+12 | 0.173564E+12 | 0.00 | 0.171591E+11 | 0.774593E+11 |
Annual Sum or Average | 0.754539E+13 | 0.949303E+12 | 0.00 | 0.120613E+12 | 0.358118E+12 |
Minimum of Months | 0.143176E+12 | 0.226518E+11 | 0.00 | 0.523480E+10 | 0.139672E+10 |
Maximum of Months | 0.109576E+13 | 0.176716E+12 | 0.00 | 0.188224E+11 | 0.823115E+11 |