Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 10:43:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 571.11 | 118.12 | 118.12 |
Net Site Energy | 571.11 | 118.12 | 118.12 |
Total Source Energy | 1805.69 | 373.45 | 373.45 |
Net Source Energy | 1805.69 | 373.45 | 373.45 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 230.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 109.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 51.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 569.66 | 1.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 230.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 109.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 51.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 230.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 109.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 51.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 18.53 | 0.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 117.82 | 0.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 18.53 | 0.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 117.82 | 0.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 569.662 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 569.662 | 100.00 |
Total On-Site and Utility Electric Sources | 569.662 | 100.00 |
Total Electricity End Uses | 569.662 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1951.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 96.62 |
Skylight-Roof Ratio [%] | 2.10 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.6485 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 12.8090 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 5.4896 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.7537 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.7537 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 8.6485 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 12.8090 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 5.4896 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.7537 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.7537 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.7537 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 05-DEC-16:40 | 03-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 17712.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 635.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27809.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4295.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1601.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 51441.93 | 17712.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 17712.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 635.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27809.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4295.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1601.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 41.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 731.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 347.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 164.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 78.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1804.12 | 1.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 373.13 | 0.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 373.13 | 0.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.10 |
ZONE2 FINE STORAGE DIRECT AIR | 2.88 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 39235.53 |
PSZ-OFFICE HEATING COIL | 26892.65 |
PSZ-FINE STORAGE HEATING COIL | 89430.95 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 31230.63 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.00 | 1.00 | 1.10 |
PSZ-FINE STORAGE | 2.88 | 2.88 | 2.88 | 2.88 | 2.88 | 2.88 | 1.00 | 1.00 | 2.88 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.10 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.88 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.10 | 1217.73 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.88 | 3078.26 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 1.10 | 18737.71 | 26892.65 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.88 | 2.88 | 2.88 | 2.88 | 58865.32 | 89430.95 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.10 | 0.549933 | 1.10 | 18737.71 | 9646.55 | 18737.71 | 0.800240 | 0.800240 |
PSZ-FINE STORAGE COOLING COIL | 2.88 | 1.44 | 2.88 | 58865.32 | 29190.86 | 58865.32 | 0.767420 | 0.767420 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 121 | 97 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 25.27 | 11 | 23 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 71.35 | 6 | 68 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 8.649 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 16.722 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 12.809 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.809 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 5.490 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.048 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2048.656 | 8.649 | 160.695 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2048.656 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 17848.242 | 12.809 | 594.941 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 17848.242 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 17593.267 | 5.490 | 254.975 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 17593.267 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2043 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2043 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
2 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
3 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
4 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
5 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
6 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
7 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
8 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
9 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
10 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
11 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
12 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
13 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
14 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
15 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
16 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.23941589E-14 | 0.16972320E-15 | 0.76147947E-12 | 0.12030052E-15 |
85 | 3 | -0.54770175E-04 | 0.40617527E-06 | -0.37802266E-03 | 0.14612398E-12 |
86 | 2 | 1.1283884 | 0.89444888E-02 | 1.7236739 | -0.72472748E-04 |
87 | 1 | -17.021073 | 0.23277257 | -7.1497137 | 0.33034766 |
88 | 0 | 16.283305 | 0.14884880 | 5.8169840 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4637_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 2.636 | 2.636 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.4637_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 2.636 | 2.636 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.4637_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 2.636 | 2.636 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.4637_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.636 | 2.636 | 1.000 | 0.251 | ||
5 | SKYLIGHT_U_0.9_SHGC_0.6 | 38 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.49037E-002 | 0.16139 | 0.61562 | 0.61562 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11941 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.49037E-002 | 0.16139 | 0.61562 | 0.61562 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11941 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.49037E-002 | 0.16139 | 0.61562 | 0.61562 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11941 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.49037E-002 | 0.16139 | 0.61562 | 0.61562 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11941 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE2 FINE STORAGE | 17 | 0 |
2 | ZONE3 BULK STORAGE | 48 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE2 FINE STORAGE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.867 | 0.602 | 0.602 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.602 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4082E-004 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2157E-003 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2543E-004 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3237E-003 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2356E-004 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3020E-003 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5846E-004 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1815E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5200E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4827E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1338E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3464E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4302E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.0916E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7678E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3854E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6084E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9289E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.7451E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2684E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1865E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1426E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2140E-003 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2647E-004 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4491E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1469E-004 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2408E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1834E-004 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1182E-004 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0581E-004 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8731E-004 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2827E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5321E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.6952E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4442E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9247E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0178E-004 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2733E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2313E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8071E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0908E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.7690E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1172E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9138E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1385E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6812E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4730E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6077E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3838E-003 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3957E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6339E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.6496E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5627E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9560E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8085E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6784E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9436E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1468E-004 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3297E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2024E-004 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9531E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0081E-004 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7041E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0147E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4708E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7177E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3336E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8656E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4905E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3339E-004 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3936E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9988E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9077E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.6038E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4113E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.0932E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0735E-003 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4729E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4816E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3509E-004 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1536E-003 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5955E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0673E-003 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7203E-004 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7071E-003 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2706E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0449E-003 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8210E-005 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3022E-003 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1187E-004 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3895E-003 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1701E-004 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5134E-003 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9245E-005 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2693E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9676E-005 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.6394E-004 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3179E-005 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.6370E-004 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.5637E-005 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2919E-004 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9089E-005 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9220E-004 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6633E-005 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1685E-004 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0829E-003 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6209E-004 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2747E-003 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9128E-004 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2824E-004 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2486E-004 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9544E-004 |
113 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5492E-004 |
114 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6852E-003 |
115 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3564E-004 |
116 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0966E-003 |
117 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3047E-004 |
118 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4323E-003 |
119 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7794E-004 |
120 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2088E-003 |
121 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0605E-004 |
122 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8119E-003 |
123 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8645E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7814E-003 |
125 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5497E-005 |
126 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.8257E-003 |
127 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1031E-004 |
128 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8081E-003 |
129 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0238E-004 |
130 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2618E-003 |
131 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.6044E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2057E-003 |
133 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4230E-005 |
134 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8302E-003 |
135 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0679E-004 |
136 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8985E-003 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3794E-005 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8776E-005 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7598E-005 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5910E-005 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6589E-005 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0076E-005 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6875E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7907E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4470E-005 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4272E-005 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2827E-005 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5163E-005 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8254E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1330E-005 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2505E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8790E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2225E-005 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8705E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1228E-005 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8530E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2305E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0188E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4518E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1894E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3172E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6523E-004 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8399E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7715E-004 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1218E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4075E-004 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3749E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9598E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2668E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8280E-004 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3419E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4730E-004 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0887E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3501E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7351E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9337E-005 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4767E-005 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9143E-005 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4280E-005 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9066E-005 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6038E-005 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0900E-005 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4547E-005 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1899E-005 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7720E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4417E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1362E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4318E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9859E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3276E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3727E-005 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6584E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8811E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2678E-003 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9540E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5290E-003 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8416E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5112E-004 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0577E-004 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5937E-004 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5244E-004 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9313E-004 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0019E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1009E-004 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8849E-004 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9044E-004 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2602E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5433E-004 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5782E-004 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2422E-005 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5053E-004 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0122E-005 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2957E-004 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8028E-005 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2589E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2626E-005 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6396E-005 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9366E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5528E-005 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9224E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7991E-005 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1109E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6146E-005 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2108E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3254E-003 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0932E-004 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4600E-003 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4179E-003 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2666E-004 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8579E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9146E-005 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6439E-003 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6713E-004 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8667E-003 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6987E-004 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5738E-003 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8559E-004 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8666E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7821E-004 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7572E-005 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9508E-005 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6304E-005 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9309E-005 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9402E-005 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1218E-005 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7819E-005 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2286E-005 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5014E-004 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7088E-003 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4726E-004 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1832E-003 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9746E-004 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2542E-003 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9087E-004 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0419E-003 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7899E-005 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9541E-005 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6332E-005 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9300E-005 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9562E-005 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1190E-005 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8944E-005 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2390E-005 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5408E-003 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1492E-004 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5027E-003 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0436E-004 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1714E-003 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3799E-004 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4247E-003 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2489E-004 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7230E-003 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3133E-004 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7208E-003 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8827E-004 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3561E-003 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8687E-004 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4293E-003 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8034E-004 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6098E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7489E-003 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4035E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8171E-003 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5650E-004 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5797E-003 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9999E-004 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9795E-003 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7231E-005 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9455E-005 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5562E-005 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9196E-005 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8282E-005 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1026E-005 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8931E-005 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2389E-005 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0590E-004 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2591E-003 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7971E-004 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0818E-003 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7016E-004 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6691E-003 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9835E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9047E-003 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7215E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0448E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4395E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2823E-005 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1906E-003 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1768E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3879E-003 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2454E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0345E-004 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8909E-004 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7800E-004 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3140E-004 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2622E-003 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3323E-004 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3923E-003 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7329E-004 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3718E-004 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3364E-004 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1776E-004 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5100E-004 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4938E-004 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6126E-004 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8859E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0100E-003 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5922E-004 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1874E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9342E-004 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8108E-004 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9619E-004 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3129E-004 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6556E-004 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7120E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4884E-005 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4773E-005 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3001E-005 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0683E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7520E-005 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9885E-005 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2484E-005 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6354E-005 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5779E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9263E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4216E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9013E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6147E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0766E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7788E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2283E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9647E-005 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7267E-004 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8171E-005 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4063E-004 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3056E-005 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4482E-004 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0459E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5301E-004 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5599E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1946E-004 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2836E-004 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0032E-004 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3467E-004 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0271E-004 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2096E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5176E-004 |
369 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3973E-005 |
370 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9000E-005 |
371 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2664E-005 |
372 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8780E-005 |
373 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3992E-005 |
374 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0469E-005 |
375 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6110E-005 |
376 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2103E-005 |
377 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5889E-004 |
378 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5307E-005 |
379 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9158E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5628E-005 |
381 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8131E-004 |
382 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5172E-005 |
383 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6472E-004 |
384 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8530E-005 |
385 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5691E-004 |
386 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7299E-005 |
387 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2861E-004 |
388 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0648E-005 |
389 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3166E-004 |
390 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1896E-005 |
391 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2084E-004 |
392 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2186E-005 |
393 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6000E-004 |
394 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2540E-005 |
395 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6088E-004 |
396 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1204E-005 |
397 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6893E-004 |
398 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4442E-005 |
399 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0569E-004 |
400 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9793E-005 |
401 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3667E-004 |
402 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5775E-005 |
403 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1333E-004 |
404 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3028E-005 |
405 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2398E-004 |
406 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8508E-005 |
407 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9939E-004 |
408 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6200E-005 |
409 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3641E-004 |
410 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1337E-005 |
411 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1608E-004 |
412 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8645E-005 |
413 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4042E-004 |
414 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1161E-005 |
415 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8831E-004 |
416 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3433E-005 |
417 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0320E-005 |
418 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7800E-005 |
419 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8218E-005 |
420 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5635E-005 |
421 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9978E-005 |
422 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6833E-005 |
423 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0450E-004 |
424 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9718E-005 |
425 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4311E-005 |
426 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4624E-005 |
427 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7787E-005 |
428 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3051E-005 |
429 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5532E-005 |
430 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3761E-005 |
431 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6851E-005 |
432 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6541E-005 |
433 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1661E-004 |
434 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5041E-005 |
435 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0762E-004 |
436 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2913E-005 |
437 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6991E-004 |
438 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7835E-005 |
439 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9059E-004 |
440 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3506E-005 |
441 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0935E-004 |
442 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9275E-005 |
443 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1254E-004 |
444 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8620E-005 |
445 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0201E-004 |
446 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0274E-005 |
447 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7326E-005 |
448 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6596E-005 |
449 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9723E-004 |
450 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4351E-005 |
451 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7006E-004 |
452 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1409E-005 |
453 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4865E-004 |
454 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5764E-005 |
455 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9776E-004 |
456 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6168E-005 |
457 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5665E-005 |
458 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3173E-005 |
459 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0120E-005 |
460 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2343E-005 |
461 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3463E-005 |
462 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4624E-005 |
463 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7130E-005 |
464 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5036E-005 |
465 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5660E-005 |
466 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1331E-005 |
467 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1707E-005 |
468 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0605E-005 |
469 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2831E-005 |
470 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2085E-005 |
471 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8078E-005 |
472 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3860E-005 |
473 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6903E-005 |
474 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2510E-005 |
475 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4870E-005 |
476 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2011E-005 |
477 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0041E-005 |
478 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4079E-005 |
479 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8268E-005 |
480 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3875E-005 |
481 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8972E-005 |
482 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1742E-005 |
483 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8279E-005 |
484 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1441E-005 |
485 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9339E-005 |
486 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3232E-005 |
487 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0724E-005 |
488 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3130E-005 |
489 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3956E-005 |
490 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2202E-005 |
491 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8683E-005 |
492 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1362E-005 |
493 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3302E-005 |
494 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3100E-005 |
495 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8376E-005 |
496 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4575E-005 |
497 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1764E-005 |
498 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2871E-005 |
499 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5754E-005 |
500 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1989E-005 |
501 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5885E-005 |
502 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4048E-005 |
503 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7023E-005 |
504 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5031E-005 |
505 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3576E-005 |
506 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3036E-005 |
507 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9656E-005 |
508 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2345E-005 |
509 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0371E-005 |
510 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4622E-005 |
511 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8596E-005 |
512 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4588E-005 |
513 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9047E-005 |
514 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0430E-005 |
515 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6390E-005 |
516 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9857E-005 |
517 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6442E-005 |
518 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1220E-005 |
519 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0605E-005 |
520 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3116E-005 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10933.53004 | 13120.23605 | 0.91655 | 1.09987 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 30.76600 | 8.23264E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7635.47322 | 9162.56786 | 0.21822 | 0.26186 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 3.80000 | 5.05843E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 36686.20526 | 44023.44631 | 2.39730 | 2.87675 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 16894.63606 | 20273.56327 | 0.40704 | 0.48845 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 3.80000 | 5.05843E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.23349E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 26025.52715 | 31230.63259 | 0.64795 | 0.97684 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16376.67 | 1.09987 | 1.09987 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7995.51 | 0.26186 | 0.26186 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 52535.17 | 2.87675 | 2.87675 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 20107.68 | 0.48845 | 0.48845 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09987 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.87675 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 39235.52798 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 31230.63259 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09987 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09987 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09987 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09987 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.09987 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.09987 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.87675 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.87675 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.87675 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.87675 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.87675 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.87675 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.09987 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.87675 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.09987 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.09987 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1217.72529 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.09987 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.09987 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.09987 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.09987 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.09987 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54993 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.09987 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18737.71000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 9646.55432 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18737.71000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80024 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80024 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18737.71000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26892.65389 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26892.65389 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.87675 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.87675 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3078.26322 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.87675 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.87675 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.87675 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.87675 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.87675 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.43838 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.87675 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 58865.32000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 29190.85775 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 58865.32000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76742 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76742 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 58865.32000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 89430.94535 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 89430.94535 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 17884.2 | 11.81 | 11.13 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 56631.3 | 11.68 | 11.00 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 2.5350530856E-002 | 1.9917237397E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 3.5328313442E-002 | 3.2038494254E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.2037902446E-002 | 2.1034270388E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7636.88 | 426.70 | 0.00 | 87.66 | 67.21 | 8218.50 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.55 | 0.199 | 0.204 | 1393.41 | 1368.14 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.55 | 0.199 | 0.204 | 3204.84 | 3133.49 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.4637_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.636 | 0.251 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.4637_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.636 | 0.251 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.4637_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.636 | 0.251 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.4637_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.636 | 0.251 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_17 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_16 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_15 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2_C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4_C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6_C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7_C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8_C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3_C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1_C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5_C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4_C5 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7_C5 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2_C5 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6_C5 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5_C5 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3_C5 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8_C5 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 114.28 | 4.726 | 0.547 | 0.548 | |||||||||||||||||
North Total or Average | 6.51 | 2.636 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 107.77 | 4.852 | 0.565 | 0.565 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_17 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_16 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_15 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 8.6485 | 236.88 | 2048.66 | LightsWired | LTG_SCH_OFFICE | 51.24 | 168.00 | 50.44 | 0.0000 | Y | 19.40 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 12.8090 | 1393.41 | 17848.24 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 35.67 | 0.0000 | Y | 119.52 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 5.4896 | 3204.84 | 17593.27 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 27.86 | 0.0000 | Y | 92.01 |
Interior Lighting Total | 7.7537 | 4835.13 | 37490.17 | 230.93 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17848.24 | 6603.85 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17848.24 | 6603.85 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17593.27 | 6509.51 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17593.27 | 6509.51 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6986.42 | AstronomicalClock | - | 83.75 | 83.75 | 109.84 | |
Exterior Lighting Total | 6986.42 | 109.84 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18737.71 | 14994.67 | 3743.04 | 0.80 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 58865.32 | 45174.42 | 13690.90 | 0.77 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 17884.2 | 11.81 | 11.13 | ||||
PSZ-FINE STORAGE COOLING COIL | 56631.3 | 11.68 | 11.00 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 39235.53 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26892.65 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 89430.95 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1217.73 | 1107.16 | 1.00 | 1.38 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.88 | 3078.26 | 1070.05 | 1.00 | 1.27 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10933.53 | 13120.24 | 55.39 | 0.917 | 1.100 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 23.90 | 23.90 | 0.00828 | 30.77 | 0.00823 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 36686.21 | 44023.45 | 31.59 | 2.397 | 2.877 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.70 | 26.70 | 0.00830 | 31.30 | 0.00823 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 0.00 | 31.69 | 0.00830 | 31.30 | 0.00823 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7635.47 | 9162.57 | 38.68 | 0.218 | 0.262 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00765 | 3.80 | 0.00506 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 16894.64 | 20273.56 | 14.55 | 0.407 | 0.488 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00652 | 3.80 | 0.00506 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 26025.53 | 31230.63 | 9.74 | 0.648 | 0.977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00579 | 3.80 | 0.00506 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.10 | 1.10 | 0.26 | 0.26 | 1.0999 | 1.0999 | 1.0999 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.88 | 2.88 | 0.49 | 0.49 | 2.8768 | 2.8768 | 2.8768 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 39235.528 | 39235.528 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 39235.53 | 39235.53 | 0.976836 | 10.00 | 7.80 | 0.00578796 | 43.33 | 21.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 10.00 | 0.00578796 | 74.6560 | 31230.63 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 18737.710 | 14994.665 | 1.099870 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 18737.71 | 17928.22 | 1.099870 | 25.46 | 16.52 | 0.00827190 | 12.00 | 11.09 | 0.00800000 | 30.86 | 0.00823278 | 18.30 | 9.2997 | 23.90 | 0.00827591 | 44.0036 | 10926.77 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26892.654 | 26892.654 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 26892.65 | 26892.65 | 1.099865 | 19.41 | 13.51 | 0.00740689 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 9.2997 | 21.10 | 0.00764768 | 48.2537 | 7635.47 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 58865.320 | 45174.424 | 2.876750 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 58865.32 | 56586.06 | 2.876750 | 28.27 | 17.49 | 0.00828712 | 12.00 | 11.09 | 0.00800000 | 31.30 | 0.00823349 | 18.45 | 14.7636 | 26.70 | 0.00829641 | 37.3439 | 36686.21 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 89430.945 | 89430.945 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 89430.95 | 89430.95 | 2.876754 | 13.82 | 10.10 | 0.00630044 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 14.7636 | 15.56 | 0.00651557 | 58.3138 | 16894.64 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39235.528 | 39235.528 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.15440386 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 39235.53 | 39235.53 | 1.0000 | 1.15440386 | 0.976836 | 10.00 | 7.80 | 0.00578796 | 24630.6 | 43.33 | 21.93 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39235.53 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 10.00 | 0.00578796 | 10.00 | 0.00578796 | 74.6560 | 31230.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18737.710 | 14994.665 | 1.099870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2170 | 1004.8586 | 1.1818 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.099865 | 1.29979714 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | Sensible | 18737.71 | 17928.22 | 1.0000 | 1.29980290 | 1.099870 | 25.46 | 16.52 | 0.00827190 | 46666.9 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18737.71 | 30.86 | 0.00823278 | 18.30 | 0.10228463 | 9.2997 | 23.90 | 0.00827591 | 23.90 | 0.00827591 | 44.0036 | 10926.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26892.654 | 26892.654 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.099865 | 1.29979714 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 26892.65 | 26892.65 | 1.0000 | 1.29979714 | 1.099865 | 19.41 | 13.51 | 0.00740689 | 38295.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26892.65 | 3.80 | 0.00505843 | 3.80 | 0.10228463 | 9.2997 | 21.01 | 0.00764768 | 21.10 | 0.00764768 | 48.2537 | 7635.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 58865.320 | 45174.424 | 2.876750 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2453 | 1004.8586 | 1.1818 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.876754 | 3.39968700 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 58865.32 | 56586.06 | 1.0000 | 3.39968177 | 2.876750 | 28.27 | 17.49 | 0.00828712 | 49563.6 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58865.32 | 31.30 | 0.00823349 | 18.45 | 0.42471127 | 14.7636 | 26.70 | 0.00829641 | 26.70 | 0.00829641 | 37.3439 | 36686.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89430.945 | 89430.945 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.876754 | 3.39968700 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 89430.95 | 89430.95 | 1.0000 | 3.39968700 | 2.876754 | 13.82 | 10.10 | 0.00630044 | 29807.4 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89430.95 | 3.80 | 0.00505843 | 3.80 | 0.42471127 | 14.7636 | 15.56 | 0.00651557 | 15.56 | 0.00651557 | 58.3138 | 16894.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.10 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.88 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1709.67 | 1777.67 | 240.17 |
ZONE2 FINE STORAGE | 2327.33 | 2239.17 | 1199.17 |
ZONE3 BULK STORAGE | 2423.33 | 2888.50 | 1823.33 |
Facility | 2994.50 | 3043.83 | 1951.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.17 | 0.00 | 0.17 | 0.00 |
ZONE2 FINE STORAGE | 0.83 | 4.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1.00 | 4.00 | 0.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.51 | 12.75 | 1010.76 | 1.473 | 0.468 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.37 | 30.00 | 2953.02 | 0.884 | 0.322 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.45 | 69.00 | 35277.63 | 0.000 | 0.146 | 0.000 | 0.058 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.51 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.37 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.45 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.51 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.37 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.45 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.32 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 5280126.70 | 0.00 | 5280126.70 | 2399885.91 | 7680012.61 | 3225648.14 | 5708.47 | 752.61 | 2298.91 | 0.00 |
ZONE2 FINE STORAGE | 9298943.22 | 0.00 | 9298943.22 | 7435190.39 | 16734133.61 | 13393694.68 | 5683.87 | 1889.24 | 1186.88 | 21.38 |
ZONE3 BULK STORAGE | 0.00 | 12132638.50 | 12132638.50 | 31836630.61 | 43969269.11 | 30805497.77 | 8685.57 | 6.67 | 67.76 | 4402.83 |
Total Facility | 14579069.92 | 12132638.50 | 26711708.42 | 41671706.92 | 68383415.33 | 47424840.58 | 8699.45 | 2062.68 | 2548.06 | 4403.93 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.4034 | 0.0000 | 0.4034 | 0.1286 | 0.5320 | 0.1023 | 584.47 | 752.61 | 2298.91 |
ZONE2 FINE STORAGE | 0.7009 | 0.0000 | 0.7009 | 0.2571 | 0.9581 | 0.4247 | 580.25 | 1889.16 | 1166.59 |
ZONE3 BULK STORAGE | 0.0000 | 0.5533 | 0.5533 | 1.3984 | 1.9517 | 0.9768 | 3573.12 | 5.33 | 57.55 |
Total Facility | 1.1043 | 0.5533 | 1.6576 | 1.7842 | 3.4418 | 1.5038 | 3575.45 | 2061.26 | 2517.56 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 7374229.22 | 0.00 | 7374229.22 | 3225648.14 | 5705.08 | 0.17 | 3054.75 | 0.00 |
PSZ-FINE STORAGE | 12986911.63 | 0.00 | 12986911.63 | 13393694.68 | 5673.76 | 0.33 | 3085.90 | 21.38 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.5634 | 0.0000 | 0.5634 | 0.1023 | 581.08 | 0.17 | 3054.75 |
PSZ-FINE STORAGE | 0.9789 | 0.0000 | 0.9789 | 0.4247 | 570.47 | 0.33 | 3065.19 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 1988.11 | 1074.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2377.27 | 725.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.7228 | 0.5694 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 1.0395 | 1.5350 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 69 | 69 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 444 |
Defaulted Fields | 429 |
Fields with Defaults | 1213 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 147 |
Autocalculatable Fields | 244 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 569.66 | 2265.47 | 01-JAN-12:00 | 51441.93 | 05-DEC-16:40 |
Electricity:Building | 370.34 | 1782.47 | 01-JAN-12:00 | 39622.31 | 02-JAN-16:00 |
Electricity:Zone:ZONE1 OFFICE | 51.34 | 860.99 | 01-JAN-00:10 | 3141.26 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 370.22 | 1782.47 | 01-JAN-12:00 | 39622.31 | 02-JAN-16:00 |
InteriorLights:Electricity | 230.93 | 1208.72 | 01-JAN-12:00 | 29509.69 | 02-JAN-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 19.40 | 287.24 | 01-JAN-00:10 | 1228.76 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 230.93 | 1208.72 | 01-JAN-12:00 | 29509.69 | 02-JAN-16:00 |
LightsWired:InteriorLights:Electricity | 230.93 | 1208.72 | 01-JAN-12:00 | 29509.69 | 02-JAN-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 19.40 | 287.24 | 01-JAN-00:10 | 1228.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 230.93 | 1208.72 | 01-JAN-12:00 | 29509.69 | 02-JAN-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 119.52 | 464.05 | 01-JAN-12:00 | 15171.01 | 02-JAN-16:00 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 119.52 | 464.05 | 01-JAN-12:00 | 15171.01 | 02-JAN-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 119.52 | 464.05 | 01-JAN-12:00 | 15171.01 | 02-JAN-16:00 |
Electricity:Zone:ZONE3 BULK STORAGE | 199.48 | 457.42 | 01-JAN-09:00 | 21395.07 | 02-JAN-16:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 92.01 | 457.42 | 01-JAN-09:00 | 13194.95 | 02-JAN-16:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 92.01 | 457.42 | 01-JAN-09:00 | 13194.95 | 02-JAN-16:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 51.93 | 0.00 | 01-JAN-00:10 | 6601.28 | 29-SEP-12:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.12 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-OCT-14:50 |
Ventilation (simple):Fans:Electricity | 0.12 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-OCT-14:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.12 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-OCT-14:50 |
ElectricityPurchased:Facility | 569.66 | 2265.47 | 01-JAN-12:00 | 51441.93 | 05-DEC-16:40 |
ElectricityPurchased:Plant | 569.66 | 2265.47 | 01-JAN-12:00 | 51441.93 | 05-DEC-16:40 |
Cogeneration:ElectricityPurchased | 569.66 | 2265.47 | 01-JAN-12:00 | 51441.93 | 05-DEC-16:40 |
General:Cogeneration:ElectricityPurchased | 569.66 | 2265.47 | 01-JAN-12:00 | 51441.93 | 05-DEC-16:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 569.66 | 2265.47 | 01-JAN-12:00 | 51441.93 | 05-DEC-16:40 |
ElectricityNet:Plant | 569.66 | 2265.47 | 01-JAN-12:00 | 51441.93 | 05-DEC-16:40 |
Cogeneration:ElectricityNet | 569.66 | 2265.47 | 01-JAN-12:00 | 51441.93 | 05-DEC-16:40 |
General:Cogeneration:ElectricityNet | 569.66 | 2265.47 | 01-JAN-12:00 | 51441.93 | 05-DEC-16:40 |
Electricity:HVAC | 64.79 | 0.00 | 01-JAN-00:10 | 16088.62 | 16-OCT-11:10 |
General:Fans:Electricity | 51.81 | 0.00 | 01-JAN-00:10 | 4295.99 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 12.99 | 0.00 | 01-JAN-00:10 | 11792.63 | 16-OCT-11:10 |
General:Cooling:Electricity | 12.99 | 0.00 | 01-JAN-00:10 | 11792.63 | 16-OCT-11:10 |
ExteriorLights:Electricity | 109.84 | 0.00 | 01-JAN-07:00 | 6986.42 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 109.84 | 0.00 | 01-JAN-07:00 | 6986.42 | 01-JAN-00:10 |
Electricity:Plant | 24.68 | 483.00 | 25-JUN-12:00 | 1799.14 | 07-FEB-12:40 |
WaterSystems:Electricity | 24.68 | 483.00 | 25-JUN-12:00 | 1799.14 | 07-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 24.68 | 483.00 | 25-JUN-12:00 | 1799.14 | 07-FEB-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1.45 | 0.00 | 01-JAN-00:10 | 17712.78 | 03-JAN-07:10 |
NaturalGas:HVAC | 1.45 | 0.00 | 01-JAN-00:10 | 17712.78 | 03-JAN-07:10 |
Heating:NaturalGas | 1.45 | 0.00 | 01-JAN-00:10 | 17712.78 | 03-JAN-07:10 |
General:Heating:NaturalGas | 1.45 | 0.00 | 01-JAN-00:10 | 17712.78 | 03-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 137.93 | 0.00 | 01-JAN-00:10 | 68145.65 | 29-SEP-15:10 |
EnergyTransfer:Building | 83.19 | 0.00 | 01-JAN-00:10 | 29814.49 | 29-SEP-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 38.25 | 0.00 | 01-JAN-00:10 | 12735.46 | 03-JAN-07:10 |
Heating:EnergyTransfer | 6.25 | 0.00 | 01-JAN-00:10 | 16515.69 | 03-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 2.49 | 0.00 | 01-JAN-00:10 | 12735.46 | 03-JAN-07:10 |
General:Heating:EnergyTransfer | 6.25 | 0.00 | 01-JAN-00:10 | 16515.69 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 2.49 | 0.00 | 01-JAN-00:10 | 12735.46 | 03-JAN-07:10 |
Cooling:EnergyTransfer | 76.94 | 0.00 | 01-JAN-00:10 | 29814.49 | 29-SEP-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 35.76 | 0.00 | 01-JAN-00:10 | 11184.79 | 16-OCT-11:10 |
General:Cooling:EnergyTransfer | 76.94 | 0.00 | 01-JAN-00:10 | 29814.49 | 29-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 35.76 | 0.00 | 01-JAN-00:10 | 11184.79 | 16-OCT-11:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 44.94 | 0.00 | 01-JAN-00:10 | 27818.21 | 04-JUL-17:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 3.77 | 0.00 | 01-JAN-00:10 | 7635.63 | 03-JAN-02:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 3.77 | 0.00 | 01-JAN-00:10 | 7635.63 | 03-JAN-02:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 41.17 | 0.00 | 01-JAN-00:10 | 27818.21 | 04-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 41.17 | 0.00 | 01-JAN-00:10 | 27818.21 | 04-JUL-17:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 54.74 | 0.00 | 01-JAN-00:10 | 40238.13 | 17-AUG-15:00 |
HeatingCoils:EnergyTransfer | 0.98 | 0.00 | 01-JAN-00:10 | 13166.45 | 03-JAN-07:10 |
CoolingCoils:EnergyTransfer | 53.76 | 0.00 | 01-JAN-00:10 | 40238.13 | 17-AUG-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 2.486 | -35.764 | 0.000 | 0.000 | 9.244 | 19.398 | 31.946 | 9.719 | 0.000 | 0.283 | 0.000 | 0.000 | -7.260 | 0.000 | -19.094 | -10.958 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 3.767 | -41.172 | 0.000 | 0.000 | 19.707 | 119.525 | 0.000 | 88.044 | 0.000 | 0.330 | 0.000 | 0.000 | -21.903 | 0.000 | -65.884 | -102.414 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 49.347 | 92.011 | 107.344 | 828.674 | 0.000 | 6.086 | 0.009 | 0.000 | -180.731 | 0.000 | -300.413 | -602.319 |
Total Facility | 0.000 | 0.000 | 6.253 | -76.937 | 0.000 | 0.000 | 78.299 | 230.934 | 139.290 | 926.437 | 0.000 | 6.700 | 0.009 | 0.000 | -209.894 | 0.000 | -385.391 | -715.691 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 29-APR-07:02 | 0.00 | 0.00 | 0.00 | -21590.62 | 0.00 | 0.00 | 801.54 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 17868.95 | 0.00 | -125.51 | 0.00 | -95.63 | 0.00 |
ZONE2 FINE STORAGE | 04-JUL-15:31 | 0.00 | 0.00 | 0.00 | -57615.42 | 0.00 | 0.00 | 0.00 | 684.18 | 0.00 | 7389.27 | 0.00 | 0.00 | 50715.27 | 0.00 | -0.00 | 0.00 | -1173.30 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-JUL-15:31 | 0.00 | 0.00 | 0.00 | -57615.42 | 0.00 | 0.00 | 0.00 | 1428.85 | 573.75 | 113456.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7828.82 | -50015.30 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 10-JAN-07:01 | 0.00 | 0.00 | 27111.56 | 0.00 | 0.00 | 0.00 | 266.70 | 670.24 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -511.62 | 0.00 | -6186.82 | -22306.30 |
ZONE2 FINE STORAGE | 02-JAN-07:02 | 0.00 | 0.00 | 18139.34 | 0.00 | 0.00 | 0.00 | 672.01 | 10708.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -523.42 | 0.00 | -2544.05 | -26452.82 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-JAN-07:02 | 0.00 | 0.00 | 45013.79 | 0.00 | 0.00 | 0.00 | 2466.08 | 21935.14 | 3006.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8790.52 | 0.00 | -15127.90 | -48502.88 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0999 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0999 | 0.0930 | 1.0000 | Not calculated | 0.1023 | 0.0930 | ||
PSZ-FINE STORAGE | 2.8768 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.8768 | 0.1476 | 1.0000 | Not calculated | 0.4247 | 0.1476 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0999 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0999 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0930 | ||
PSZ-FINE STORAGE | 2.8768 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.8768 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1476 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0999 | 1.0999 | 1.0999 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8768 | 2.8768 | 2.8768 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0999 | 1.0999 | 1.0999 | 1.0999 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8768 | 2.8768 | 2.8768 | 2.8768 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0999 | 1.0999 | 1.0999 | No | 0.1023 | 0.3906 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8768 | 2.8768 | 2.8768 | No | 0.4247 | 0.8695 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0999 | 1.0999 | 1.0999 | 1.0999 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8768 | 2.8768 | 2.8768 | 2.8768 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1.45 | 17712.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 12.99 | 11792.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 230.93 | 29509.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 109.84 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.12 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 51.81 | 4295.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.68 | 1799.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 569.66 |
Natural Gas | 0.00 | 1.45 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 571.11 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 47.76 |
Space Heating | 0.00 |
Space Cooling | 2.69 |
Fans (All) | 10.74 |
Service Water Heating | 5.11 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 117.82 |
Subtotal | 117.82 |
Natural Gas [MJ/m2] | |
Space Heating | 0.30 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.30 |
Subtotal | 0.30 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 40.44 |
Space Heating | 0.25 |
Space Cooling | 2.27 |
Fans (All) | 9.09 |
Service Water Heating | 4.32 |
Receptacle Equipment | 24.39 |
Miscellaneous | 19.23 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2672. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8287.00 | 473.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7445.67 | 1314.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6941.00 | 1819.00 | 0.00 | 0.00 | 0.00 |
Min | 6941.00 | 473.00 | 0.00 | 0.00 | 0.00 |
Max | 8287.00 | 1819.00 | 0.00 | 0.00 | 0.00 |
Average | 7557.89 | 1202.11 | 0.00 | 0.00 | 0.00 |
Sum | 22673.67 | 3606.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33023.17 | 3.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 54917.00 | 27802.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 140367.00 | 50826.00 | 0.00 | 0.00 | 0.00 |
Min | 33023.17 | 3.83 | 0.00 | 0.00 | 0.00 |
Max | 140367.00 | 50826.00 | 0.00 | 0.00 | 0.00 |
Average | 76102.39 | 26210.61 | 0.00 | 0.00 | 0.00 |
Sum | 228307.17 | 78631.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7314.83 | 1445.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 6240.00 | 2520.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6366.50 | 2393.50 | 0.00 | 0.00 | 0.00 |
Min | 6240.00 | 1445.17 | 0.00 | 0.00 | 0.00 |
Max | 7314.83 | 2520.00 | 0.00 | 0.00 | 0.00 |
Average | 6640.44 | 2119.56 | 0.00 | 0.00 | 0.00 |
Sum | 19921.33 | 6358.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32633.67 | 393.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 49453.00 | 33266.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 131235.50 | 59957.50 | 0.00 | 0.00 | 0.00 |
Min | 32633.67 | 393.33 | 0.00 | 0.00 | 0.00 |
Max | 131235.50 | 59957.50 | 0.00 | 0.00 | 0.00 |
Average | 71107.39 | 31205.61 | 0.00 | 0.00 | 0.00 |
Sum | 213322.17 | 93616.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 27573.00 | 0.00 |
Sum | 0.00 | 191193.00 | 82719.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108855E+10 | 5354.09 | 21-JAN-08:65 | 13.17 | 13.07 | 0.603445E+09 | 809.93 | 21-JAN-08:09 | 13.17 | 13.07 |
February | 0.807850E+09 | 3950.06 | 03-FEB-15:10 | 22.67 | 9.08 | 0.556577E+09 | 768.99 | 01-FEB-13:50 | 22.67 | 9.08 |
March | 0.962698E+09 | 4670.20 | 23-MAR-15:00 | 22.00 | 17.40 | 0.647576E+09 | 769.01 | 22-MAR-15:30 | 22.00 | 17.40 |
April | 0.255572E+10 | 21592.83 | 29-APR-07:02 | 14.33 | 11.79 | 0.627577E+09 | 879.39 | 29-APR-07:10 | 14.33 | 11.79 |
May | 0.304569E+10 | 21260.10 | 20-MAY-07:02 | 14.17 | 11.80 | 0.656732E+09 | 879.11 | 06-MAY-07:10 | 14.17 | 11.80 |
June | 0.430605E+10 | 19121.90 | 03-JUN-07:02 | 17.17 | 14.02 | 0.662028E+09 | 879.39 | 10-JUN-07:10 | 17.05 | 14.00 |
July | 0.551255E+10 | 18653.94 | 08-JUL-07:02 | 17.00 | 14.51 | 0.639462E+09 | 879.39 | 08-JUL-07:10 | 17.00 | 14.51 |
August | 0.575067E+10 | 17190.89 | 01-AUG-07:03 | 18.00 | 15.44 | 0.689992E+09 | 879.39 | 19-AUG-07:10 | 20.33 | 18.75 |
September | 0.452959E+10 | 20514.97 | 02-SEP-07:02 | 16.17 | 12.63 | 0.637481E+09 | 879.39 | 23-SEP-07:10 | 17.00 | 16.37 |
October | 0.410025E+10 | 20596.27 | 07-OCT-07:02 | 17.00 | 12.30 | 0.634827E+09 | 879.39 | 06-OCT-07:10 | 17.00 | 12.30 |
November | 0.171310E+10 | 5045.39 | 04-NOV-07:05 | 11.92 | 10.50 | 0.598275E+09 | 806.98 | 04-NOV-07:10 | 11.92 | 10.50 |
December | 0.139130E+10 | 5549.64 | 09-DEC-08:65 | 12.83 | 12.57 | 0.615425E+09 | 811.34 | 09-DEC-08:09 | 12.83 | 12.57 |
Annual Sum or Average | 0.357640E+11 | 0.756940E+10 | ||||||||
Minimum of Months | 0.807850E+09 | 3950.06 | 11.92 | 9.08 | 0.556577E+09 | 768.99 | 11.92 | 9.08 | ||
Maximum of Months | 0.575067E+10 | 21592.83 | 22.67 | 17.40 | 0.689992E+09 | 879.39 | 22.67 | 18.75 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.619439E+09 | 3773.20 | 12-JAN-09:00 | 8.00 | 8.00 | 0.139981E+10 | 2222.08 | 18-JAN-14:30 | 23.80 | 14.82 |
February | 0.561297E+09 | 2403.47 | 22-FEB-08:07 | 10.75 | 8.63 | 0.123970E+10 | 2212.45 | 03-FEB-15:30 | 10.75 | 8.63 |
March | 0.765831E+09 | 3498.86 | 29-MAR-15:00 | 8.00 | 6.48 | 0.143460E+10 | 2246.79 | 23-MAR-15:30 | 8.00 | 6.48 |
April | 0.155288E+10 | 51498.54 | 30-APR-14:15 | 23.67 | 16.60 | 0.165582E+10 | 2246.87 | 26-APR-14:30 | 23.67 | 16.60 |
May | 0.169850E+10 | 9720.92 | 03-MAY-15:00 | 22.00 | 15.39 | 0.176797E+10 | 2246.89 | 04-MAY-12:30 | 23.50 | 16.62 |
June | 0.461580E+10 | 54089.67 | 25-JUN-13:21 | 23.00 | 17.26 | 0.188139E+10 | 2246.90 | 24-JUN-12:00 | 23.00 | 17.26 |
July | 0.100973E+11 | 57619.03 | 04-JUL-15:31 | 21.00 | 15.98 | 0.185144E+10 | 2246.91 | 11-JUL-13:39 | 22.00 | 17.03 |
August | 0.979253E+10 | 53411.76 | 20-AUG-16:01 | 21.80 | 17.34 | 0.199858E+10 | 2246.91 | 01-AUG-13:00 | 21.80 | 17.34 |
September | 0.535270E+10 | 51714.83 | 30-SEP-17:12 | 25.00 | 17.45 | 0.183786E+10 | 2246.89 | 11-SEP-13:30 | 25.00 | 17.45 |
October | 0.462371E+10 | 51636.46 | 16-OCT-17:25 | 25.50 | 14.51 | 0.179973E+10 | 2246.90 | 18-OCT-14:30 | 22.00 | 18.09 |
November | 0.743425E+09 | 3628.42 | 01-NOV-08:15 | 12.67 | 11.74 | 0.150485E+10 | 2246.79 | 18-NOV-14:20 | 25.33 | 14.85 |
December | 0.749017E+09 | 3762.72 | 01-DEC-08:13 | 9.67 | 9.31 | 0.148646E+10 | 2246.79 | 05-DEC-15:20 | 24.33 | 12.97 |
Annual Sum or Average | 0.411724E+11 | 0.198582E+11 | ||||||||
Minimum of Months | 0.561297E+09 | 2403.47 | 8.00 | 6.48 | 0.123970E+10 | 2212.45 | 8.00 | 6.48 | ||
Maximum of Months | 0.100973E+11 | 57619.03 | 25.50 | 17.45 | 0.199858E+10 | 2246.91 | 25.33 | 18.09 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 | 0.234965E+10 | 3671.41 | 24-JAN-16:10 | 23.50 | 14.81 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 | 0.220756E+10 | 3761.84 | 03-FEB-15:09 | 22.67 | 9.08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.62 | 0.254120E+10 | 3966.37 | 23-MAR-14:39 | 22.33 | 17.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 | 0.309982E+10 | 4850.53 | 26-APR-14:09 | 25.50 | 16.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 | 0.356462E+10 | 5175.57 | 04-MAY-12:50 | 23.17 | 16.65 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 | 0.410057E+10 | 5893.83 | 30-JUN-15:30 | 22.85 | 17.86 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 | 0.480461E+10 | 6310.49 | 31-JUL-13:09 | 27.83 | 21.13 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 | 0.522226E+10 | 6309.07 | 19-AUG-14:20 | 26.67 | 19.73 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.83 | 0.428957E+10 | 7851.32 | 29-SEP-13:09 | 35.67 | 18.16 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 | 0.408813E+10 | 7430.29 | 16-OCT-12:00 | 34.10 | 16.81 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.07 | 0.279735E+10 | 4258.48 | 01-NOV-12:50 | 18.00 | 13.26 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 | 0.258766E+10 | 3893.68 | 05-DEC-15:30 | 24.00 | 12.83 |
Annual Sum or Average | 0.00 | 0.416530E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.63 | 5.44 | 0.220756E+10 | 3671.41 | 18.00 | 9.08 | ||
Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.522226E+10 | 7851.32 | 35.67 | 21.13 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.514453E+09 | 27111.90 | 10-JAN-07:01 | 4.67 |
February | 0.305003E+09 | 23117.40 | 28-FEB-07:03 | 11.33 |
March | 0.462237E+09 | 27099.53 | 30-MAR-06:01 | 5.58 |
April | 0.138658E+09 | 26295.51 | 01-APR-06:02 | 7.67 |
May | 0.125437E+09 | 2491.03 | 15-MAY-07:03 | 13.50 |
June | 0.104364E+09 | 1592.86 | 30-JUN-06:10 | 17.17 |
July | 86238585.72 | 1892.46 | 24-JUL-06:07 | 16.17 |
August | 0.100514E+09 | 1631.40 | 28-AUG-06:15 | 14.00 |
September | 95452829.80 | 1856.93 | 30-SEP-06:05 | 23.78 |
October | 94458939.31 | 1756.47 | 19-OCT-06:15 | 11.67 |
November | 0.168239E+09 | 8932.60 | 24-NOV-08:63 | 10.67 |
December | 0.291270E+09 | 24791.91 | 15-DEC-07:03 | 6.50 |
Annual Sum or Average | 0.248632E+10 | |||
Minimum of Months | 86238585.72 | 1592.86 | 4.67 | |
Maximum of Months | 0.514453E+09 | 27111.90 | 23.78 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.720617E+09 | 18139.32 | 02-JAN-07:02 | 11.00 |
February | 0.337670E+09 | 3322.87 | 27-FEB-08:00 | 9.00 |
March | 0.382453E+09 | 3111.72 | 28-MAR-07:00 | 11.00 |
April | 0.349090E+09 | 3128.11 | 21-APR-07:00 | 13.00 |
May | 0.241683E+09 | 3351.82 | 25-MAY-07:00 | 14.00 |
June | 0.173089E+09 | 3361.69 | 06-JUN-07:00 | 17.00 |
July | 66896293.86 | 2804.97 | 17-JUL-07:00 | 15.70 |
August | 84717382.24 | 2963.69 | 21-AUG-07:00 | 17.00 |
September | 0.184198E+09 | 3036.70 | 27-SEP-07:00 | 16.00 |
October | 0.193680E+09 | 3001.49 | 25-OCT-07:00 | 13.00 |
November | 0.397961E+09 | 3115.85 | 01-NOV-07:00 | 11.00 |
December | 0.634689E+09 | 3002.88 | 16-DEC-13:00 | 26.00 |
Annual Sum or Average | 0.376674E+10 | |||
Minimum of Months | 66896293.86 | 2804.97 | 9.00 | |
Maximum of Months | 0.720617E+09 | 18139.32 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162246E+10 | 1228.76 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.147976E+10 | 1228.76 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.169071E+10 | 1228.76 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.159765E+10 | 1228.76 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.165659E+10 | 1228.76 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.163177E+10 | 1228.76 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.162246E+10 | 1228.76 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.169071E+10 | 1228.76 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.159765E+10 | 1228.76 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.162246E+10 | 1228.76 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.156352E+10 | 1228.76 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.162246E+10 | 1228.76 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.193982E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.147976E+10 | 1228.76 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.169071E+10 | 1228.76 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.124068E+11 | 15171.01 | 02-JAN-15:00 | 0.00 | 0.00 |
February | 0.959358E+10 | 13386.18 | 01-FEB-08:09 | 0.00 | 0.00 |
March | 0.993184E+10 | 13386.18 | 01-MAR-16:00 | 0.00 | 0.00 |
April | 0.866377E+10 | 11735.22 | 01-APR-07:10 | 0.00 | 0.00 |
May | 0.828121E+10 | 11735.22 | 08-MAY-07:10 | 0.00 | 0.00 |
June | 0.824924E+10 | 11735.22 | 09-JUN-07:10 | 0.00 | 0.00 |
July | 0.836238E+10 | 11735.22 | 18-JUL-07:10 | 0.00 | 0.00 |
August | 0.910009E+10 | 11735.22 | 03-AUG-07:10 | 0.00 | 0.00 |
September | 0.933994E+10 | 13386.18 | 11-SEP-07:10 | 0.00 | 0.00 |
October | 0.113292E+11 | 15171.01 | 28-OCT-08:09 | 0.00 | 0.00 |
November | 0.113373E+11 | 15171.01 | 06-NOV-15:50 | 0.00 | 0.00 |
December | 0.129294E+11 | 15171.01 | 01-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119525E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.824924E+10 | 11735.22 | 0.00 | 0.00 | |
Maximum of Months | 0.129294E+11 | 15171.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.948324E+10 | 13194.95 | 02-JAN-16:10 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.750752E+10 | 13194.95 | 25-FEB-16:49 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.778373E+10 | 11567.57 | 01-MAR-16:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.667789E+10 | 10555.96 | 01-APR-06:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.651503E+10 | 7952.16 | 05-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.637493E+10 | 7952.16 | 06-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.639076E+10 | 7952.16 | 08-JUL-06:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.695767E+10 | 10555.96 | 21-AUG-06:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.714710E+10 | 10555.96 | 05-SEP-06:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.855811E+10 | 13194.95 | 28-OCT-15:00 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.875879E+10 | 13194.95 | 06-NOV-16:10 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.985643E+10 | 13194.95 | 01-DEC-16:10 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.920112E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.637493E+10 | 7952.16 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.985643E+10 | 13194.95 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4697072.94 | 0.182378E+10 |
February | 0.127628E+10 | 0.147976E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1589604.51 | 0.199027E+10 |
March | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43351.21 | 0.242423E+10 |
April | 0.138726E+10 | 0.159765E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5769721.55 | 0.164783E+10 |
May | 0.144276E+10 | 0.165659E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75138.08 | 0.187175E+10 |
June | 0.144276E+10 | 0.163177E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1374562.50 | 0.129889E+10 |
July | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39133805.27 | 0.925947E+09 |
August | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39676966.60 | 0.106534E+10 |
September | 0.138726E+10 | 0.159765E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62492569.38 | 0.111428E+10 |
October | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120732E+09 | 0.128193E+10 |
November | 0.133177E+10 | 0.156352E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2313096.41 | 0.182372E+10 |
December | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5522401.11 | 0.182599E+10 |
Annual Sum or Average | 0.168137E+11 | 0.193982E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283421E+09 | 0.190940E+11 |
Minimum of Months | 0.127628E+10 | 0.147976E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43351.21 | 0.925947E+09 |
Maximum of Months | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120732E+09 | 0.242423E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.124068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8837796.71 | 0.514392E+10 |
February | 0.300332E+10 | 0.959358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30865.54 | 0.628359E+10 |
March | 0.352563E+10 | 0.993184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729432E+10 |
April | 0.326447E+10 | 0.866377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4000314.33 | 0.582995E+10 |
May | 0.339505E+10 | 0.828121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709694E+10 |
June | 0.339505E+10 | 0.824924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498960E+10 |
July | 0.326447E+10 | 0.836238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6232833.98 | 0.385085E+10 |
August | 0.352563E+10 | 0.910009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3899824.85 | 0.448412E+10 |
September | 0.326447E+10 | 0.933994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84734676.40 | 0.414327E+10 |
October | 0.326447E+10 | 0.113292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213244E+09 | 0.523156E+10 |
November | 0.313390E+10 | 0.113373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7237769.04 | 0.579108E+10 |
December | 0.326447E+10 | 0.129294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1854766.46 | 0.574507E+10 |
Annual Sum or Average | 0.395654E+11 | 0.119525E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330073E+09 | 0.658843E+11 |
Minimum of Months | 0.300332E+10 | 0.824924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385085E+10 |
Maximum of Months | 0.352563E+10 | 0.129294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213244E+09 | 0.729432E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.948324E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657652E+09 | 0.134654E+11 |
February | 0.690763E+10 | 0.750752E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75590082.61 | 0.177734E+11 |
March | 0.810895E+10 | 0.778373E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143329E+09 | 0.212888E+11 |
April | 0.750829E+10 | 0.667789E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274520E+09 | 0.174063E+11 |
May | 0.780862E+10 | 0.651503E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235758E+11 |
June | 0.780862E+10 | 0.637493E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184404E+11 |
July | 0.750829E+10 | 0.639076E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199204E+11 |
August | 0.810895E+10 | 0.695767E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224675E+11 |
September | 0.750829E+10 | 0.714710E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212474E+09 | 0.172619E+11 |
October | 0.750829E+10 | 0.855811E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985457E+09 | 0.197122E+11 |
November | 0.720796E+10 | 0.875879E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265513E+09 | 0.178378E+11 |
December | 0.750829E+10 | 0.985643E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722181E+09 | 0.157125E+11 |
Annual Sum or Average | 0.910005E+11 | 0.920112E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333672E+10 | 0.224862E+12 |
Minimum of Months | 0.690763E+10 | 0.637493E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134654E+11 |
Maximum of Months | 0.810895E+10 | 0.985643E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985457E+09 | 0.235758E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1228.76 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 776.24 | 18-JAN-13:00 | 7197.64 | 09-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1228.76 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 673.65 | 01-FEB-12:10 | 5748.15 | 10-FEB-07:07 |
March | 1680.92 | 01-MAR-08:09 | 1228.76 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.03 | 11-MAR-14:00 | 6862.02 | 30-MAR-06:05 |
April | 1680.92 | 01-APR-07:10 | 1228.76 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 793.42 | 26-APR-11:10 | 5919.12 | 17-APR-16:03 |
May | 1680.92 | 01-MAY-07:10 | 1228.76 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.52 | 03-MAY-12:00 | 5388.19 | 12-MAY-16:03 |
June | 1680.92 | 01-JUN-07:10 | 1228.76 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.40 | 29-JUN-11:10 | 4078.03 | 05-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1228.76 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1564.43 | 19-JUL-12:00 | 4013.09 | 17-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1228.76 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1525.83 | 18-AUG-12:00 | 4187.89 | 28-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 1228.76 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4404.66 | 29-SEP-12:00 | 4197.68 | 20-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1228.76 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4937.78 | 16-OCT-11:10 | 5372.71 | 19-OCT-06:05 |
November | 1680.92 | 01-NOV-07:10 | 1228.76 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.80 | 19-NOV-13:00 | 5556.04 | 30-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1228.76 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 785.62 | 19-DEC-13:00 | 6312.52 | 13-DEC-07:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5.03 | 4013.09 | |||||
Maximum of Months | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4937.78 | 7197.64 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 15171.01 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.26 | 15-JAN-10:00 | 8280.32 | 27-JAN-05:00 |
February | 3955.50 | 01-FEB-08:09 | 13386.18 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.44 | 01-FEB-12:00 | 9718.46 | 25-FEB-16:05 |
March | 3955.50 | 01-MAR-08:09 | 13386.18 | 01-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 12799.65 | 28-MAR-15:05 |
April | 3955.50 | 01-APR-07:10 | 11735.22 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.34 | 30-APR-11:30 | 13492.31 | 17-APR-16:45 |
May | 3955.50 | 01-MAY-07:10 | 11735.22 | 08-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 12229.04 | 12-MAY-16:00 |
June | 3955.50 | 01-JUN-07:10 | 11735.22 | 09-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 7114.00 | 12-JUN-16:00 |
July | 3955.50 | 01-JUL-07:10 | 11735.22 | 18-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.56 | 31-JUL-13:00 | 7174.44 | 20-JUL-18:00 |
August | 3955.50 | 01-AUG-07:10 | 11735.22 | 03-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.25 | 17-AUG-14:00 | 5635.35 | 21-AUG-17:00 |
September | 3955.50 | 01-SEP-07:10 | 13386.18 | 11-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4049.48 | 29-SEP-15:10 | 6718.40 | 02-SEP-15:10 |
October | 3955.50 | 02-OCT-07:10 | 15171.01 | 28-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3907.88 | 14-OCT-15:10 | 8478.73 | 23-OCT-15:05 |
November | 3955.50 | 01-NOV-07:10 | 15171.01 | 06-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.12 | 19-NOV-13:00 | 8758.16 | 30-NOV-07:10 |
December | 3955.50 | 01-DEC-08:09 | 15171.01 | 01-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.08 | 25-DEC-12:00 | 9038.91 | 13-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 11735.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5635.35 | ||||
Maximum of Months | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4049.48 | 13492.31 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 13194.95 | 02-JAN-16:10 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9798.09 | 14-JAN-13:10 | 24916.97 | 27-JAN-05:00 |
February | 9097.65 | 01-FEB-08:09 | 13194.95 | 25-FEB-16:49 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7476.21 | 01-FEB-12:00 | 29486.92 | 25-FEB-13:05 |
March | 9097.65 | 01-MAR-08:09 | 11567.57 | 01-MAR-16:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6281.12 | 11-MAR-13:10 | 36382.36 | 28-MAR-08:00 |
April | 9097.65 | 01-APR-07:10 | 10555.96 | 01-APR-06:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9470.24 | 01-APR-12:10 | 37894.66 | 17-APR-16:00 |
May | 9097.65 | 01-MAY-07:10 | 7952.16 | 05-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 36637.14 | 12-MAY-16:00 |
June | 9097.65 | 01-JUN-07:10 | 7952.16 | 06-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 19904.24 | 12-JUN-16:00 |
July | 9097.65 | 01-JUL-07:10 | 7952.16 | 08-JUL-06:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 28009.50 | 20-JUL-09:00 |
August | 9097.65 | 01-AUG-07:10 | 10555.96 | 21-AUG-06:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 19991.96 | 22-AUG-16:00 |
September | 9097.65 | 01-SEP-07:10 | 10555.96 | 05-SEP-06:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13850.78 | 29-SEP-12:10 | 24646.33 | 02-SEP-15:00 |
October | 9097.65 | 02-OCT-07:10 | 13194.95 | 28-OCT-15:00 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22960.02 | 16-OCT-10:00 | 28422.86 | 07-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 13194.95 | 06-NOV-16:10 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6653.32 | 19-NOV-13:00 | 23866.50 | 01-NOV-08:00 |
December | 9097.65 | 01-DEC-08:09 | 13194.95 | 01-DEC-16:10 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15171.35 | 18-DEC-11:00 | 27766.89 | 12-DEC-13:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 7952.16 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19904.24 | |||||
Maximum of Months | 9097.65 | 13194.95 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 22960.02 | 37894.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5354.09 | 21-JAN-08:65 | 3361.84 | 2457.53 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 731.46 |
February | 3950.06 | 03-FEB-15:10 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.63 |
March | 4670.20 | 23-MAR-15:00 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.67 |
April | 21592.83 | 29-APR-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.63 |
May | 21260.10 | 20-MAY-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 694.99 |
June | 19121.90 | 03-JUN-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 880.45 |
July | 18653.94 | 08-JUL-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.85 |
August | 17190.89 | 01-AUG-07:03 | 6723.69 | 4915.05 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.31 |
September | 20514.97 | 02-SEP-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.01 |
October | 20596.27 | 07-OCT-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1166.31 |
November | 5045.39 | 04-NOV-07:05 | 3361.84 | 2457.53 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.85 |
December | 5549.64 | 09-DEC-08:65 | 3361.84 | 2457.53 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3950.06 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.63 | |
Maximum of Months | 21592.83 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1166.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3773.20 | 12-JAN-09:00 | 3955.50 | 10084.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2403.47 | 22-FEB-08:07 | 11866.50 | 35205.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1003.73 |
March | 3498.86 | 29-MAR-15:00 | 3955.50 | 3944.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1212.22 |
April | 51498.54 | 30-APR-14:15 | 0.00 | 928.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1010.35 |
May | 9720.92 | 03-MAY-15:00 | 3955.50 | 5815.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.56 |
June | 54089.67 | 25-JUN-13:21 | 0.00 | 4176.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2165.79 |
July | 57619.03 | 04-JUL-15:31 | 0.00 | 6841.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.30 |
August | 53411.76 | 20-AUG-16:01 | 0.00 | 8138.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2129.78 |
September | 51714.83 | 30-SEP-17:12 | 0.00 | 7139.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.62 |
October | 51636.46 | 16-OCT-17:25 | 0.00 | 3569.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.89 | 0.00 |
November | 3628.42 | 01-NOV-08:15 | 7911.00 | 22857.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3069.49 |
December | 3762.72 | 01-DEC-08:13 | 15822.00 | 40337.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2403.47 | 0.00 | 928.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57619.03 | 15822.00 | 40337.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.89 | 3069.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 1759.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9315.86 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8123.34 |
April | 0.00 | 01-APR-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11722.09 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7872.21 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6171.53 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4986.63 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7159.96 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7777.07 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 1759.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11841.90 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9203.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 1759.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11841.90 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.523555E+11 | 50807.93 | 13-JAN-16:00 | 0.574218E+09 | 17712.78 | 03-JAN-07:10 |
February | 0.442864E+11 | 43821.67 | 27-FEB-16:49 | 0.208269E+09 | 7937.99 | 10-FEB-07:10 |
March | 0.480561E+11 | 42339.30 | 10-MAR-16:00 | 0.417193E+09 | 15655.18 | 30-MAR-06:10 |
April | 0.434801E+11 | 37285.55 | 21-APR-15:50 | 16963657.94 | 6723.16 | 01-APR-06:10 |
May | 0.432837E+11 | 35684.62 | 08-MAY-07:10 | 845215.94 | 1408.69 | 15-MAY-07:10 |
June | 0.433361E+11 | 34541.03 | 09-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.456346E+11 | 38991.22 | 19-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.489244E+11 | 37185.99 | 19-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.463674E+11 | 47871.07 | 29-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.512683E+11 | 50020.23 | 17-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.492220E+11 | 50805.98 | 28-NOV-16:00 | 26787926.09 | 4831.91 | 24-NOV-08:09 |
December | 0.534470E+11 | 51441.93 | 05-DEC-16:40 | 0.204517E+09 | 9489.13 | 15-DEC-07:10 |
Annual Sum or Average | 0.569662E+12 | 0.144879E+10 | ||||
Minimum of Months | 0.432837E+11 | 34541.03 | 0.00 | 0.00 | ||
Maximum of Months | 0.534470E+11 | 51441.93 | 0.574218E+09 | 17712.78 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.235125E+11 | 0.108234E+11 | 0.115358E+11 | 0.00 | 0.425658E+10 | 0.00 | 0.00 | 0.111640E+09 | 0.00 | 0.00 | 0.00 | 0.211561E+10 | 0.00 |
February | 0.185809E+11 | 0.925142E+10 | 0.105871E+11 | 0.00 | 0.391279E+10 | 0.00 | 0.00 | 31601373.12 | 0.00 | 0.00 | 0.00 | 0.192262E+10 | 0.00 |
March | 0.194063E+11 | 0.948197E+10 | 0.123431E+11 | 0.00 | 0.459339E+10 | 0.00 | 0.00 | 68549043.50 | 0.00 | 0.00 | 0.00 | 0.216282E+10 | 0.00 |
April | 0.169393E+11 | 0.842981E+10 | 0.114862E+11 | 0.00 | 0.425580E+10 | 0.00 | 0.00 | 0.325903E+09 | 0.00 | 0.00 | 0.00 | 0.204308E+10 | 0.00 |
May | 0.164528E+11 | 0.804836E+10 | 0.119357E+11 | 0.00 | 0.442315E+10 | 0.00 | 0.00 | 0.327420E+09 | 0.00 | 0.00 | 0.00 | 0.209622E+10 | 0.00 |
June | 0.162559E+11 | 0.746150E+10 | 0.118862E+11 | 0.00 | 0.443830E+10 | 0.00 | 0.00 | 0.126359E+10 | 0.00 | 0.00 | 0.00 | 0.203058E+10 | 0.00 |
July | 0.163756E+11 | 0.785553E+10 | 0.115358E+11 | 0.00 | 0.439278E+10 | 0.00 | 0.00 | 0.343545E+10 | 0.00 | 0.00 | 0.00 | 0.203946E+10 | 0.00 |
August | 0.177485E+11 | 0.841305E+10 | 0.123357E+11 | 0.00 | 0.467546E+10 | 0.00 | 0.00 | 0.366312E+10 | 0.00 | 0.00 | 0.00 | 0.208866E+10 | 0.00 |
September | 0.180847E+11 | 0.885738E+10 | 0.114788E+11 | 0.00 | 0.434032E+10 | 0.00 | 0.00 | 0.160340E+10 | 0.00 | 0.00 | 0.00 | 0.200279E+10 | 0.00 |
October | 0.215097E+11 | 0.992631E+10 | 0.115432E+11 | 0.00 | 0.430170E+10 | 0.00 | 0.00 | 0.192284E+10 | 0.00 | 0.00 | 0.00 | 0.206454E+10 | 0.00 |
November | 0.216596E+11 | 0.102826E+11 | 0.110862E+11 | 0.00 | 0.408291E+10 | 0.00 | 0.00 | 95945746.96 | 0.00 | 0.00 | 0.00 | 0.201473E+10 | 0.00 |
December | 0.244083E+11 | 0.110078E+11 | 0.115358E+11 | 0.00 | 0.425303E+10 | 0.00 | 0.00 | 0.138339E+09 | 0.00 | 0.00 | 0.00 | 0.210373E+10 | 0.00 |
Annual Sum or Average | 0.230934E+12 | 0.109839E+12 | 0.139290E+12 | 0.00 | 0.519262E+11 | 0.00 | 0.00 | 0.129878E+11 | 0.00 | 0.00 | 0.00 | 0.246848E+11 | 0.00 |
Minimum of Months | 0.162559E+11 | 0.746150E+10 | 0.105871E+11 | 0.00 | 0.391279E+10 | 0.00 | 0.00 | 31601373.12 | 0.00 | 0.00 | 0.00 | 0.192262E+10 | 0.00 |
Maximum of Months | 0.244083E+11 | 0.110078E+11 | 0.123431E+11 | 0.00 | 0.467546E+10 | 0.00 | 0.00 | 0.366312E+10 | 0.00 | 0.00 | 0.00 | 0.216282E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.574218E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.208269E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.417193E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 16963657.94 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 845215.94 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 26787926.09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.204517E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144879E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.574218E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 29509.69 | 02-JAN-15:00 | 6986.42 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4295.99 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 27809.90 | 25-FEB-16:49 | 6986.42 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4295.99 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26182.52 | 01-MAR-16:00 | 6986.42 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4295.99 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 21935.14 | 01-APR-06:10 | 6986.42 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4295.99 | 12-APR-13:39 | 0.00 | 0.00 | 01-APR-00:10 |
May | 19649.42 | 08-MAY-07:10 | 6986.42 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4295.99 | 24-MAY-11:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 19649.42 | 09-JUN-07:10 | 6986.42 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 4295.99 | 26-JUN-14:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 19331.34 | 11-JUL-06:10 | 6986.42 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6601.28 | 31-JUL-12:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 21935.14 | 21-AUG-06:10 | 6986.42 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 5448.64 | 14-AUG-10:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 24555.14 | 18-SEP-07:10 | 6986.42 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6601.28 | 29-SEP-12:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27809.90 | 28-OCT-15:00 | 6986.42 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 6601.28 | 16-OCT-14:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 29509.69 | 06-NOV-15:50 | 6986.42 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4295.99 | 01-NOV-07:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 29509.69 | 02-DEC-15:50 | 6986.42 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4295.99 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 19331.34 | 6986.42 | 10112.62 | 0.00 | 4295.99 | 0.00 | 0.00 | |||||
Maximum of Months | 29509.69 | 6986.42 | 10112.62 | 0.00 | 6601.28 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 1272.97 | 24-JAN-15:30 | 0.00 | 0.00 | 0.00 | 1799.13 | 25-JAN-12:00 | 0.00 |
February | 1142.52 | 01-FEB-11:00 | 0.00 | 0.00 | 0.00 | 1799.14 | 07-FEB-12:39 | 0.00 |
March | 1440.78 | 23-MAR-13:00 | 0.00 | 0.00 | 0.00 | 1797.50 | 01-MAR-12:09 | 0.00 |
April | 6947.74 | 30-APR-11:30 | 0.00 | 0.00 | 0.00 | 1791.63 | 01-APR-11:09 | 0.00 |
May | 3392.19 | 04-MAY-12:09 | 0.00 | 0.00 | 0.00 | 1783.29 | 03-MAY-11:30 | 0.00 |
June | 7183.00 | 29-JUN-17:49 | 0.00 | 0.00 | 0.00 | 1775.48 | 01-JUN-11:20 | 0.00 |
July | 9367.43 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 1769.44 | 01-JUL-11:30 | 0.00 |
August | 9724.77 | 17-AUG-14:20 | 0.00 | 0.00 | 0.00 | 1768.54 | 31-AUG-11:09 | 0.00 |
September | 10985.85 | 29-SEP-11:00 | 0.00 | 0.00 | 0.00 | 1773.53 | 29-SEP-11:09 | 0.00 |
October | 11792.63 | 16-OCT-11:09 | 0.00 | 0.00 | 0.00 | 1782.04 | 31-OCT-11:30 | 0.00 |
November | 1752.00 | 18-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1790.15 | 30-NOV-12:00 | 0.00 |
December | 1368.98 | 05-DEC-14:00 | 0.00 | 0.00 | 0.00 | 1796.14 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1142.52 | 0.00 | 0.00 | 0.00 | 1768.54 | 0.00 | ||
Maximum of Months | 11792.63 | 0.00 | 0.00 | 0.00 | 1799.14 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 50807.93 | 13-JAN-16:00 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 4295.99 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43821.67 | 27-FEB-16:49 | 27809.90 | 10112.62 | 0.00 | 0.00 | 4295.99 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42339.30 | 10-MAR-16:00 | 26182.52 | 10112.62 | 0.00 | 0.00 | 4295.99 | 0.00 | 0.00 | 145.54 | 0.00 |
April | 37285.55 | 21-APR-15:50 | 21276.80 | 10112.62 | 0.00 | 0.00 | 4295.99 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35684.62 | 08-MAY-07:10 | 19649.42 | 10112.62 | 0.00 | 0.00 | 4295.99 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34541.03 | 09-JUN-07:10 | 19649.42 | 10112.62 | 0.00 | 0.00 | 4295.99 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 38991.22 | 19-JUL-15:00 | 14720.12 | 10112.62 | 0.00 | 0.00 | 4295.99 | 0.00 | 0.00 | 8266.85 | 0.00 |
August | 37185.99 | 19-AUG-07:10 | 19649.42 | 10112.62 | 0.00 | 0.00 | 4295.99 | 0.00 | 0.00 | 2252.04 | 0.00 |
September | 47871.07 | 29-SEP-15:00 | 19625.84 | 10112.62 | 0.00 | 0.00 | 6601.28 | 0.00 | 0.00 | 9934.12 | 0.00 |
October | 50020.23 | 17-OCT-15:00 | 26182.52 | 10112.62 | 0.00 | 0.00 | 4295.99 | 0.00 | 0.00 | 7830.87 | 0.00 |
November | 50805.98 | 28-NOV-16:00 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 4295.99 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 51441.93 | 05-DEC-16:40 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 4295.99 | 0.00 | 0.00 | 635.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 34541.03 | 14720.12 | 10112.62 | 0.00 | 0.00 | 4295.99 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51441.93 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 6601.28 | 0.00 | 0.00 | 9934.12 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 17712.78 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7937.99 | 10-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 15655.18 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 6723.16 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 1408.69 | 15-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 4831.91 | 24-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 9489.13 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 17712.78 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 17.18 | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 17.18 | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.18 | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.00 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.29 | 0.00 | 27.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.29 | 0.00 | 27.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.00 | 27.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.39 | 0.00 | 27.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 14.98 | 0.00 | 14.98 | 4.00 | 25.20 | 0.00 | 25.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 14.98 | 0.00 | 14.98 | 1.33 | 27.39 | 0.00 | 27.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 281.50 | 22.78 | 50.17 | 22.40 | 50.17 | 22.11 |
February | 270.00 | 22.84 | 32.83 | 22.54 | 32.83 | 22.29 |
March | 302.83 | 22.69 | 50.50 | 22.41 | 39.17 | 22.16 |
April | 137.83 | 23.19 | 87.17 | 23.40 | 4.67 | 23.33 |
May | 106.50 | 23.35 | 115.00 | 23.67 | 0.00 | 23.67 |
June | 19.83 | 23.52 | 255.00 | 24.04 | 0.67 | 24.04 |
July | 12.33 | 25.47 | 300.00 | 24.26 | 12.33 | 24.31 |
August | 28.00 | 25.06 | 324.00 | 24.24 | 28.00 | 24.30 |
September | 15.00 | 24.20 | 288.17 | 24.10 | 12.00 | 24.11 |
October | 80.50 | 23.79 | 157.83 | 23.99 | 17.33 | 24.06 |
November | 235.83 | 23.22 | 13.17 | 23.13 | 8.83 | 23.04 |
December | 287.50 | 23.09 | 35.83 | 22.79 | 34.17 | 22.54 |
Annual Sum or Average | 1777.67 | 23.07 | 1709.67 | 23.39 | 240.17 | 23.27 |
Minimum of Months | 12.33 | 22.69 | 13.17 | 22.40 | 0.00 | 22.11 |
Maximum of Months | 302.83 | 25.47 | 324.00 | 24.26 | 50.17 | 24.31 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 232.00 | 21.74 | 107.17 | 21.62 | 68.83 | 21.18 |
February | 239.17 | 21.78 | 70.50 | 21.50 | 58.00 | 21.17 |
March | 279.83 | 21.51 | 103.67 | 21.39 | 73.00 | 21.02 |
April | 100.17 | 23.20 | 190.00 | 24.87 | 18.67 | 24.85 |
May | 81.33 | 23.79 | 213.83 | 25.42 | 19.33 | 25.47 |
June | 132.67 | 26.43 | 294.17 | 26.37 | 121.83 | 26.44 |
July | 249.17 | 26.68 | 300.00 | 26.65 | 249.17 | 26.66 |
August | 273.33 | 26.66 | 324.00 | 26.62 | 273.33 | 26.63 |
September | 179.33 | 26.63 | 296.17 | 26.52 | 177.33 | 26.56 |
October | 110.83 | 25.64 | 254.17 | 26.22 | 79.33 | 26.29 |
November | 146.50 | 22.79 | 101.83 | 23.56 | 16.83 | 23.33 |
December | 214.83 | 22.47 | 71.83 | 22.35 | 43.50 | 21.99 |
Annual Sum or Average | 2239.17 | 24.01 | 2327.33 | 24.78 | 1199.17 | 24.83 |
Minimum of Months | 81.33 | 21.51 | 70.50 | 21.39 | 16.83 | 21.02 |
Maximum of Months | 279.83 | 26.68 | 324.00 | 26.65 | 273.33 | 26.66 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 19.32 | 202.50 | 18.96 | 202.50 | 18.80 |
February | 276.00 | 19.62 | 204.50 | 19.37 | 204.50 | 19.27 |
March | 324.00 | 19.40 | 238.67 | 19.12 | 238.67 | 19.01 |
April | 241.67 | 21.86 | 63.67 | 22.01 | 26.17 | 21.79 |
May | 174.00 | 22.72 | 86.50 | 23.51 | 1.33 | 23.50 |
June | 112.67 | 25.92 | 230.00 | 26.04 | 68.17 | 26.30 |
July | 282.00 | 28.34 | 300.00 | 28.29 | 282.00 | 28.30 |
August | 308.83 | 28.37 | 324.00 | 28.33 | 308.83 | 28.34 |
September | 150.33 | 27.28 | 296.17 | 26.83 | 150.00 | 26.95 |
October | 133.67 | 26.20 | 226.00 | 26.43 | 89.83 | 26.70 |
November | 285.33 | 21.66 | 59.17 | 21.35 | 59.17 | 21.12 |
December | 300.00 | 20.35 | 192.17 | 20.08 | 192.17 | 19.96 |
Annual Sum or Average | 2888.50 | 22.95 | 2423.33 | 23.43 | 1823.33 | 23.44 |
Minimum of Months | 112.67 | 19.32 | 59.17 | 18.96 | 1.33 | 18.80 |
Maximum of Months | 324.00 | 28.37 | 324.00 | 28.33 | 308.83 | 28.34 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.459807E+09 | 0.111640E+09 | 48.22 | 0.437720E+09 | 22087193.08 | 0.00 | 0.32 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 | 5314.67 | 24-JAN-15:30 | 5112.74 | 14-JAN-15:00 | 896.23 | 17-JAN-14:00 | 1272.97 | 24-JAN-15:30 | 0.00 | 01-JAN-00:10 |
February | 0.130156E+09 | 31601373.12 | 22.08 | 0.129388E+09 | 767902.84 | 0.00 | 0.29 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 4597.33 | 01-FEB-12:00 | 4597.33 | 01-FEB-12:00 | 279.16 | 01-FEB-13:40 | 1142.52 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 0.284732E+09 | 68549043.50 | 34.33 | 0.244358E+09 | 40374187.18 | 0.00 | 0.34 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 6147.51 | 23-MAR-14:00 | 4689.52 | 23-MAR-14:00 | 1699.01 | 23-MAR-15:00 | 1440.78 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.114627E+10 | 0.273901E+09 | 111.56 | 0.934823E+09 | 0.211452E+09 | 0.00 | 1.00 | 15-APR-07:02 | 0.00 | 01-APR-00:10 | 17798.45 | 15-APR-07:02 | 13700.40 | 29-APR-07:02 | 5699.85 | 15-APR-07:02 | 3774.31 | 15-APR-07:02 | 0.00 | 01-APR-00:10 |
May | 0.126327E+10 | 0.302021E+09 | 122.74 | 0.105389E+10 | 0.209381E+09 | 0.00 | 1.00 | 06-MAY-07:02 | 0.00 | 01-MAY-00:10 | 18869.38 | 06-MAY-07:02 | 13262.20 | 20-MAY-07:02 | 7603.67 | 06-MAY-07:02 | 3992.32 | 06-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.385421E+10 | 0.897827E+09 | 202.39 | 0.288710E+10 | 0.967113E+09 | 0.00 | 1.00 | 03-JUN-07:02 | 0.00 | 01-JUN-00:10 | 20112.27 | 30-JUN-07:02 | 14100.54 | 24-JUN-07:02 | 8448.24 | 30-JUN-07:02 | 4219.26 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.717393E+10 | 0.164724E+10 | 244.43 | 0.511605E+10 | 0.205788E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 20701.33 | 25-JUL-07:02 | 14130.26 | 10-JUL-07:03 | 10152.06 | 20-JUL-07:02 | 4317.50 | 25-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.786801E+10 | 0.180220E+10 | 262.33 | 0.550254E+10 | 0.236548E+10 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 21225.55 | 19-AUG-07:02 | 12833.54 | 30-AUG-07:03 | 10800.49 | 18-AUG-07:03 | 4400.00 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.426559E+10 | 0.101799E+10 | 206.17 | 0.318456E+10 | 0.108103E+10 | 0.00 | 1.00 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 | 21045.93 | 22-SEP-07:03 | 18613.84 | 30-SEP-06:03 | 10439.08 | 22-SEP-07:03 | 4372.25 | 22-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.409760E+10 | 0.992453E+09 | 204.45 | 0.341696E+10 | 0.680639E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 21179.05 | 05-OCT-07:02 | 17941.24 | 14-OCT-07:02 | 10165.71 | 05-OCT-07:04 | 4392.87 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.392885E+09 | 95248257.07 | 52.97 | 0.383775E+09 | 9109444.25 | 0.00 | 0.34 | 18-NOV-14:30 | 0.00 | 01-NOV-00:10 | 5676.13 | 18-NOV-14:40 | 5602.80 | 18-NOV-14:30 | 760.65 | 10-NOV-13:10 | 1366.27 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.569703E+09 | 0.138339E+09 | 75.72 | 0.566090E+09 | 3612762.40 | 0.00 | 0.35 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 5668.90 | 05-DEC-15:00 | 5668.90 | 05-DEC-15:00 | 558.73 | 07-DEC-14:00 | 1368.98 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.315062E+11 | 0.737900E+10 | 1587.40 | 0.238572E+11 | 0.764893E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.130156E+09 | 31601373.12 | 22.08 | 0.129388E+09 | 767902.84 | 0.00 | 0.29 | 0.00 | 4597.33 | 4597.33 | 279.16 | 1142.52 | 0.00 | |||||||
Maximum of Months | 0.786801E+10 | 0.180220E+10 | 262.33 | 0.550254E+10 | 0.236548E+10 | 0.00 | 1.00 | 0.00 | 21225.55 | 18613.84 | 10800.49 | 4400.00 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.207388E+09 | 52001873.13 | 8.42 | 0.185333E+09 | 22054697.85 | 0.00 | 1.00 | 30-APR-11:25 | 0.00 | 01-APR-00:10 | 62436.77 | 30-APR-12:55 | 56081.34 | 30-APR-11:25 | 9757.35 | 30-APR-12:55 | 13895.48 | 30-APR-11:25 | 0.00 | 01-APR-00:10 |
May | 98810101.27 | 25399422.98 | 11.83 | 87090384.50 | 11719716.77 | 0.00 | 0.12 | 03-MAY-13:00 | 0.00 | 01-MAY-00:10 | 6157.54 | 04-MAY-12:10 | 5818.25 | 03-MAY-13:00 | 887.75 | 04-MAY-12:10 | 1570.70 | 04-MAY-12:10 | 0.00 | 01-MAY-00:10 |
June | 0.148365E+10 | 0.365759E+09 | 66.47 | 0.105386E+10 | 0.429782E+09 | 0.00 | 1.00 | 18-JUN-12:05 | 0.00 | 01-JUN-00:10 | 65936.28 | 29-JUN-17:45 | 50280.74 | 25-JUN-12:25 | 24066.64 | 29-JUN-17:45 | 14365.99 | 29-JUN-17:45 | 0.00 | 01-JUN-00:10 |
July | 0.735226E+10 | 0.178821E+10 | 173.39 | 0.510657E+10 | 0.224570E+10 | 0.00 | 1.00 | 01-JUL-17:12 | 0.00 | 01-JUL-00:10 | 68284.25 | 18-JUL-17:11 | 49411.51 | 04-JUL-09:15 | 29901.66 | 29-JUL-17:12 | 14960.79 | 23-JUL-10:58 | 0.00 | 01-JUL-00:10 |
August | 0.758293E+10 | 0.186092E+10 | 191.80 | 0.513646E+10 | 0.244647E+10 | 0.00 | 1.00 | 03-AUG-17:12 | 0.00 | 01-AUG-00:10 | 67946.89 | 13-AUG-10:25 | 49027.88 | 19-AUG-17:11 | 29664.09 | 18-AUG-17:12 | 14956.48 | 06-AUG-12:45 | 0.00 | 01-AUG-00:10 |
September | 0.213289E+10 | 0.585412E+09 | 61.35 | 0.192826E+10 | 0.204624E+09 | 0.00 | 1.00 | 03-SEP-12:55 | 0.00 | 01-SEP-00:10 | 65370.29 | 10-SEP-14:01 | 53430.84 | 30-SEP-17:12 | 22592.59 | 10-SEP-12:15 | 14271.99 | 10-SEP-14:01 | 0.00 | 01-SEP-00:10 |
October | 0.339068E+10 | 0.930387E+09 | 90.28 | 0.317247E+10 | 0.218204E+09 | 0.00 | 1.00 | 01-OCT-10:55 | 0.00 | 01-OCT-00:10 | 68318.66 | 01-OCT-12:00 | 58165.60 | 16-OCT-17:25 | 25967.74 | 01-OCT-15:05 | 15096.92 | 01-OCT-12:00 | 0.00 | 01-OCT-00:10 |
November | 2583525.65 | 697489.88 | 1.50 | 2583525.65 | -0.0 | 0.00 | 0.03 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 | 1428.54 | 18-NOV-14:00 | 1428.54 | 18-NOV-14:00 | 0.00 | 18-NOV-13:50 | 385.73 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 82.53 | 21.90 | 0.17 | 82.53 | 0.00 | 0.00 | 0.00 | 05-DEC-15:10 | 0.00 | 01-DEC-00:10 | 0.14 | 05-DEC-15:10 | 0.14 | 05-DEC-15:10 | 0.00 | 01-DEC-00:10 | 0.04 | 05-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.222512E+11 | 0.560879E+10 | 605.21 | 0.166726E+11 | 0.557855E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.758293E+10 | 0.186092E+10 | 191.80 | 0.513646E+10 | 0.244647E+10 | 0.00 | 1.00 | 0.00 | 68318.66 | 58165.60 | 29901.66 | 15096.92 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.41 | 32.49 | 31.93 | 84.61 | 87.14 | 0.00 | 0.00 | 0.00 |
February | 76.77 | 35.42 | 41.35 | 96.04 | 77.70 | 0.00 | 0.00 | 0.00 |
March | 87.97 | 38.91 | 49.07 | 112.22 | 79.32 | 0.00 | 0.00 | 0.00 |
April | 121.11 | 62.93 | 58.18 | 167.50 | 73.63 | 0.00 | 0.00 | 0.00 |
May | 119.00 | 54.83 | 64.17 | 157.76 | 69.61 | 0.00 | 0.00 | 0.00 |
June | 126.35 | 63.19 | 63.16 | 175.09 | 58.89 | 0.00 | 0.00 | 0.00 |
July | 133.76 | 71.59 | 62.17 | 193.83 | 57.00 | 0.00 | 0.00 | 0.00 |
August | 125.30 | 67.83 | 57.47 | 184.93 | 58.93 | 0.00 | 0.00 | 0.00 |
September | 107.28 | 57.35 | 49.94 | 153.54 | 65.71 | 0.00 | 0.00 | 0.00 |
October | 82.11 | 44.85 | 37.26 | 120.62 | 71.01 | 0.00 | 0.00 | 0.00 |
November | 74.04 | 38.67 | 35.37 | 96.70 | 86.27 | 0.00 | 0.00 | 0.00 |
December | 65.28 | 34.91 | 30.37 | 85.72 | 92.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.70 | 50.31 | 48.39 | 135.90 | 73.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.41 | 32.49 | 30.37 | 84.61 | 57.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.76 | 71.59 | 64.17 | 193.83 | 92.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.41 | 32.49 | 31.93 | 84.61 | 87.14 | 0.00 | 0.00 | 0.00 |
February | 76.77 | 35.42 | 41.35 | 96.04 | 77.70 | 0.00 | 0.00 | 0.00 |
March | 87.97 | 38.91 | 49.07 | 112.22 | 79.32 | 0.00 | 0.00 | 0.00 |
April | 121.11 | 62.93 | 58.18 | 167.50 | 73.63 | 0.00 | 0.00 | 0.00 |
May | 119.00 | 54.83 | 64.17 | 157.76 | 69.61 | 0.00 | 0.00 | 0.00 |
June | 126.35 | 63.19 | 63.16 | 175.09 | 58.89 | 0.00 | 0.00 | 0.00 |
July | 133.76 | 71.59 | 62.17 | 193.83 | 57.00 | 0.00 | 0.00 | 0.00 |
August | 125.30 | 67.83 | 57.47 | 184.93 | 58.93 | 0.00 | 0.00 | 0.00 |
September | 107.28 | 57.35 | 49.94 | 153.54 | 65.71 | 0.00 | 0.00 | 0.00 |
October | 82.11 | 44.85 | 37.26 | 120.62 | 71.01 | 0.00 | 0.00 | 0.00 |
November | 74.04 | 38.67 | 35.37 | 96.70 | 86.27 | 0.00 | 0.00 | 0.00 |
December | 65.28 | 34.91 | 30.37 | 85.72 | 92.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.70 | 50.31 | 48.39 | 135.90 | 73.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.41 | 32.49 | 30.37 | 84.61 | 57.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.76 | 71.59 | 64.17 | 193.83 | 92.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.63 | 0.00 | 14.63 | 9.85 | 52.37 | 0.00 | 0.00 | 0.00 |
February | 18.36 | 0.00 | 18.36 | 11.87 | 46.93 | 0.00 | 0.00 | 0.00 |
March | 22.50 | 0.00 | 22.50 | 17.24 | 47.74 | 0.00 | 0.00 | 0.00 |
April | 25.99 | 0.15 | 25.84 | 20.82 | 43.52 | 0.00 | 0.00 | 0.00 |
May | 31.35 | 1.63 | 29.72 | 26.31 | 39.21 | 0.00 | 0.00 | 0.00 |
June | 33.15 | 3.20 | 29.95 | 32.26 | 33.15 | 0.00 | 0.00 | 0.00 |
July | 31.39 | 2.59 | 28.80 | 32.24 | 32.37 | 0.00 | 0.00 | 0.00 |
August | 26.20 | 0.61 | 25.59 | 26.10 | 34.08 | 0.00 | 0.00 | 0.00 |
September | 22.10 | 0.01 | 22.09 | 20.31 | 39.76 | 0.00 | 0.00 | 0.00 |
October | 17.52 | 0.00 | 17.52 | 18.06 | 42.58 | 0.00 | 0.00 | 0.00 |
November | 15.87 | 0.00 | 15.87 | 10.04 | 52.28 | 0.00 | 0.00 | 0.00 |
December | 13.62 | 0.00 | 13.62 | 8.10 | 55.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.74 | 0.69 | 22.06 | 19.48 | 43.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.62 | 0.00 | 13.62 | 8.10 | 32.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.15 | 3.20 | 29.95 | 32.26 | 55.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.63 | 0.00 | 14.63 | 9.85 | 52.37 | 0.00 | 0.00 | 0.00 |
February | 18.36 | 0.00 | 18.36 | 11.87 | 46.93 | 0.00 | 0.00 | 0.00 |
March | 22.50 | 0.00 | 22.50 | 17.24 | 47.74 | 0.00 | 0.00 | 0.00 |
April | 25.99 | 0.15 | 25.84 | 20.82 | 43.52 | 0.00 | 0.00 | 0.00 |
May | 31.35 | 1.63 | 29.72 | 26.31 | 39.21 | 0.00 | 0.00 | 0.00 |
June | 33.15 | 3.20 | 29.95 | 32.26 | 33.15 | 0.00 | 0.00 | 0.00 |
July | 31.39 | 2.59 | 28.80 | 32.24 | 32.37 | 0.00 | 0.00 | 0.00 |
August | 26.20 | 0.61 | 25.59 | 26.10 | 34.08 | 0.00 | 0.00 | 0.00 |
September | 22.10 | 0.01 | 22.09 | 20.31 | 39.76 | 0.00 | 0.00 | 0.00 |
October | 17.52 | 0.00 | 17.52 | 18.06 | 42.57 | 0.00 | 0.00 | 0.00 |
November | 15.87 | 0.00 | 15.87 | 10.04 | 52.27 | 0.00 | 0.00 | 0.00 |
December | 13.62 | 0.00 | 13.62 | 8.10 | 55.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.74 | 0.69 | 22.06 | 19.48 | 43.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.62 | 0.00 | 13.62 | 8.10 | 32.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.15 | 3.20 | 29.95 | 32.26 | 55.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_17
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_16
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_15
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 94.53 | 48.95 | 0.33 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 105.09 | 42.05 | 0.00 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 140.61 | 41.25 | 0.83 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 214.13 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 210.61 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 226.36 | 31.93 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 251.76 | 32.58 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.08 | 34.13 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 177.52 | 37.70 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 127.03 | 42.22 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 99.01 | 49.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 86.22 | 53.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 164.23 | 40.86 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 86.22 | 31.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 251.76 | 53.13 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 99.77 | 42.26 | 8.67 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 110.18 | 36.91 | 0.67 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 146.54 | 35.85 | 25.50 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 220.68 | 35.18 | 4.83 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 215.45 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 230.06 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 250.21 | 35.88 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 232.25 | 37.96 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 178.73 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 128.21 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.96 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 90.96 | 47.05 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 167.46 | 38.58 | 41.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 90.96 | 30.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 250.21 | 47.05 | 25.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172520E+09 | 87008483.01 | 85511893.36 | 0.226608E+09 | 0.233395E+09 |
February | 0.185716E+09 | 85688879.95 | 0.100027E+09 | 0.232351E+09 | 0.187983E+09 |
March | 0.235631E+09 | 0.104204E+09 | 0.131426E+09 | 0.300561E+09 | 0.212440E+09 |
April | 0.313911E+09 | 0.163121E+09 | 0.150790E+09 | 0.434167E+09 | 0.190845E+09 |
May | 0.318735E+09 | 0.146851E+09 | 0.171884E+09 | 0.422554E+09 | 0.186439E+09 |
June | 0.327495E+09 | 0.163791E+09 | 0.163703E+09 | 0.453835E+09 | 0.152647E+09 |
July | 0.358267E+09 | 0.191752E+09 | 0.166515E+09 | 0.519142E+09 | 0.152676E+09 |
August | 0.335603E+09 | 0.181687E+09 | 0.153916E+09 | 0.495324E+09 | 0.157844E+09 |
September | 0.278082E+09 | 0.148640E+09 | 0.129443E+09 | 0.397986E+09 | 0.170310E+09 |
October | 0.219931E+09 | 0.120139E+09 | 99791852.06 | 0.323062E+09 | 0.190191E+09 |
November | 0.191911E+09 | 0.100220E+09 | 91690786.11 | 0.250649E+09 | 0.223605E+09 |
December | 0.174848E+09 | 93503618.68 | 81344281.86 | 0.229588E+09 | 0.247107E+09 |
Annual Sum or Average | 0.311265E+10 | 0.158661E+10 | 0.152604E+10 | 0.428583E+10 | 0.230548E+10 |
Minimum of Months | 0.172520E+09 | 85688879.95 | 81344281.86 | 0.226608E+09 | 0.152647E+09 |
Maximum of Months | 0.358267E+09 | 0.191752E+09 | 0.171884E+09 | 0.519142E+09 | 0.247107E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172520E+09 | 87008483.01 | 85511893.36 | 0.226608E+09 | 0.233395E+09 |
February | 0.185716E+09 | 85688879.95 | 0.100027E+09 | 0.232351E+09 | 0.187983E+09 |
March | 0.235631E+09 | 0.104204E+09 | 0.131426E+09 | 0.300561E+09 | 0.212440E+09 |
April | 0.313911E+09 | 0.163121E+09 | 0.150790E+09 | 0.434167E+09 | 0.190845E+09 |
May | 0.318735E+09 | 0.146851E+09 | 0.171884E+09 | 0.422554E+09 | 0.186439E+09 |
June | 0.327495E+09 | 0.163791E+09 | 0.163703E+09 | 0.453835E+09 | 0.152647E+09 |
July | 0.358267E+09 | 0.191752E+09 | 0.166515E+09 | 0.519142E+09 | 0.152676E+09 |
August | 0.335603E+09 | 0.181687E+09 | 0.153916E+09 | 0.495324E+09 | 0.157844E+09 |
September | 0.278082E+09 | 0.148640E+09 | 0.129443E+09 | 0.397986E+09 | 0.170310E+09 |
October | 0.219931E+09 | 0.120139E+09 | 99791852.06 | 0.323062E+09 | 0.190191E+09 |
November | 0.191911E+09 | 0.100220E+09 | 91690786.11 | 0.250649E+09 | 0.223605E+09 |
December | 0.174848E+09 | 93503618.68 | 81344281.86 | 0.229588E+09 | 0.247107E+09 |
Annual Sum or Average | 0.311265E+10 | 0.158661E+10 | 0.152604E+10 | 0.428583E+10 | 0.230548E+10 |
Minimum of Months | 0.172520E+09 | 85688879.95 | 81344281.86 | 0.226608E+09 | 0.152647E+09 |
Maximum of Months | 0.358267E+09 | 0.191752E+09 | 0.171884E+09 | 0.519142E+09 | 0.247107E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39180440.36 | 0.00 | 39180440.36 | 26381787.54 | 0.140281E+09 |
February | 44422348.44 | 0.00 | 44422348.44 | 28712584.86 | 0.113529E+09 |
March | 60275496.02 | 1891.92 | 60273604.10 | 46183062.06 | 0.127872E+09 |
April | 67377058.44 | 401407.28 | 66975651.16 | 53970618.07 | 0.112792E+09 |
May | 83958900.97 | 4364064.65 | 79594836.32 | 70460568.55 | 0.105019E+09 |
June | 85915259.84 | 8287439.62 | 77627820.23 | 83625768.24 | 85912447.72 |
July | 84079046.43 | 6931707.61 | 77147338.82 | 86351194.43 | 86707419.64 |
August | 70175901.41 | 1637363.10 | 68538538.31 | 69913854.04 | 91275149.69 |
September | 57278866.92 | 20196.66 | 57258670.27 | 52644857.66 | 0.103062E+09 |
October | 46938181.22 | 0.00 | 46938181.22 | 48383975.55 | 0.114034E+09 |
November | 41128196.19 | 0.00 | 41128196.19 | 26014190.36 | 0.135497E+09 |
December | 36473657.13 | 0.00 | 36473657.13 | 21687552.95 | 0.149330E+09 |
Annual Sum or Average | 0.717203E+09 | 21644070.83 | 0.695559E+09 | 0.614330E+09 | 0.136531E+10 |
Minimum of Months | 36473657.13 | 0.00 | 36473657.13 | 21687552.95 | 85912447.72 |
Maximum of Months | 85915259.84 | 8287439.62 | 79594836.32 | 86351194.43 | 0.149330E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39179352.82 | 0.00 | 39179352.82 | 26380798.81 | 0.140280E+09 |
February | 44421026.75 | 0.00 | 44421026.75 | 28711147.12 | 0.113529E+09 |
March | 60273709.52 | 1891.83 | 60271817.69 | 46180863.91 | 0.127871E+09 |
April | 67375371.63 | 401388.47 | 66973983.16 | 53968868.53 | 0.112791E+09 |
May | 83956469.13 | 4363860.10 | 79592609.03 | 70457307.28 | 0.105019E+09 |
June | 85912769.02 | 8287051.17 | 77625717.85 | 83622248.10 | 85912221.15 |
July | 84076837.05 | 6931382.71 | 77145454.34 | 86348256.01 | 86707021.39 |
August | 70174221.71 | 1637286.35 | 68536935.35 | 69912047.12 | 91274744.90 |
September | 57277403.05 | 20195.71 | 57257207.34 | 52643233.88 | 0.103061E+09 |
October | 46936925.77 | 0.00 | 46936925.77 | 48382641.49 | 0.114033E+09 |
November | 41127040.51 | 0.00 | 41127040.51 | 26013090.85 | 0.135496E+09 |
December | 36472664.03 | 0.00 | 36472664.03 | 21686827.69 | 0.149329E+09 |
Annual Sum or Average | 0.717184E+09 | 21643056.35 | 0.695541E+09 | 0.614307E+09 | 0.136530E+10 |
Minimum of Months | 36472664.03 | 0.00 | 36472664.03 | 21686827.69 | 85912221.15 |
Maximum of Months | 85912769.02 | 8287051.17 | 79592609.03 | 86348256.01 | 0.149329E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_17
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_16
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_15
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.253195E+09 | 0.131114E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.254228E+09 | 0.101718E+09 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.376607E+09 | 0.110486E+09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.555030E+09 | 0.103488E+09 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.564095E+09 | 99771722.92 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.586720E+09 | 82761842.54 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.674301E+09 | 87249933.02 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.626963E+09 | 91405139.91 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.460134E+09 | 97726087.09 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.340246E+09 | 0.113076E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.256624E+09 | 0.127305E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.230935E+09 | 0.142303E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.517908E+10 | 0.128840E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.230935E+09 | 82761842.54 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.674301E+09 | 0.142303E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5_C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8_C5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.267233E+09 | 0.113187E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.266541E+09 | 89289574.59 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.392491E+09 | 96032513.09 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.572015E+09 | 91193459.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.577063E+09 | 93328436.00 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.596303E+09 | 78648034.24 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.670164E+09 | 96099078.10 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.622050E+09 | 0.101661E+09 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.463267E+09 | 99737796.15 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.343406E+09 | 0.114739E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.266876E+09 | 0.116742E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.243616E+09 | 0.126021E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.528102E+10 | 0.121668E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.243616E+09 | 78648034.24 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.670164E+09 | 0.126021E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 185.84 | 275.96 | 158.08 | 64.97 | 93.11 | 0.00 | 0.00 |
February | 212.73 | 246.17 | 190.26 | 70.84 | 119.42 | 0.00 | 0.00 |
March | 255.92 | 251.12 | 220.96 | 77.81 | 143.14 | 0.00 | 0.00 |
April | 374.52 | 232.16 | 294.20 | 126.17 | 168.03 | 0.00 | 0.00 |
May | 366.46 | 215.95 | 300.70 | 112.91 | 187.78 | 0.00 | 0.00 |
June | 412.78 | 182.15 | 318.99 | 132.78 | 186.21 | 0.00 | 0.00 |
July | 450.19 | 176.81 | 330.31 | 148.36 | 181.95 | 0.00 | 0.00 |
August | 420.80 | 184.75 | 303.00 | 136.89 | 166.11 | 0.00 | 0.00 |
September | 344.78 | 208.00 | 258.77 | 114.71 | 144.06 | 0.00 | 0.00 |
October | 274.93 | 224.74 | 199.27 | 89.71 | 109.56 | 0.00 | 0.00 |
November | 209.48 | 273.09 | 179.81 | 77.33 | 102.48 | 0.00 | 0.00 |
December | 184.00 | 292.39 | 157.80 | 69.82 | 87.98 | 0.00 | 0.00 |
Annual Sum or Average | 308.18 | 230.21 | 242.89 | 101.99 | 140.89 | 0.00 | 0.00 |
Minimum of Months | 184.00 | 176.81 | 157.80 | 64.97 | 87.98 | 0.00 | 0.00 |
Maximum of Months | 450.19 | 292.39 | 330.31 | 148.36 | 187.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1607.05 | 832.19 | 1342.51 | 886.05 | 456.46 | 0.00 | 0.00 |
February | 1786.49 | 714.78 | 1526.41 | 859.16 | 667.25 | 0.00 | 0.00 |
March | 2390.35 | 701.26 | 1973.03 | 1115.59 | 857.43 | 0.00 | 0.00 |
April | 3640.24 | 678.74 | 2947.63 | 2127.53 | 820.09 | 0.00 | 0.00 |
May | 3580.35 | 633.26 | 2941.06 | 1872.46 | 1068.60 | 0.00 | 0.00 |
June | 3848.09 | 542.81 | 3118.65 | 2128.37 | 990.27 | 0.00 | 0.00 |
July | 4279.84 | 553.78 | 3417.72 | 2543.72 | 874.00 | 0.00 | 0.00 |
August | 3979.38 | 580.16 | 3168.18 | 2414.92 | 753.26 | 0.00 | 0.00 |
September | 3017.85 | 640.95 | 2443.01 | 1728.45 | 714.56 | 0.00 | 0.00 |
October | 2159.57 | 717.70 | 1754.16 | 1210.10 | 544.06 | 0.00 | 0.00 |
November | 1683.10 | 834.95 | 1430.23 | 917.68 | 512.55 | 0.00 | 0.00 |
December | 1465.76 | 903.20 | 1252.70 | 853.91 | 398.79 | 0.00 | 0.00 |
Annual Sum or Average | 2791.87 | 694.54 | 2280.15 | 1558.68 | 721.47 | 0.00 | 0.00 |
Minimum of Months | 1465.76 | 542.81 | 1252.70 | 853.91 | 398.79 | 0.00 | 0.00 |
Maximum of Months | 4279.84 | 903.20 | 3417.72 | 2543.72 | 1068.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15556.19 | 6709.88 | 3790.62 | 2501.79 | 1288.83 | 0.00 | 0.00 |
February | 17412.97 | 5688.80 | 4309.86 | 2425.85 | 1884.01 | 0.00 | 0.00 |
March | 23578.86 | 5401.49 | 5570.90 | 3149.91 | 2420.99 | 0.00 | 0.00 |
April | 33686.84 | 5142.94 | 8322.71 | 6007.15 | 2315.55 | 0.00 | 0.00 |
May | 32098.23 | 5020.05 | 8304.18 | 5286.94 | 3017.24 | 0.00 | 0.00 |
June | 36582.28 | 4373.42 | 8805.59 | 6009.52 | 2796.07 | 0.00 | 0.00 |
July | 48255.73 | 5246.70 | 9650.03 | 7182.26 | 2467.77 | 0.00 | 0.00 |
August | 41365.58 | 5545.69 | 8945.45 | 6818.60 | 2126.86 | 0.00 | 0.00 |
September | 27195.58 | 5794.81 | 6897.91 | 4880.32 | 2017.58 | 0.00 | 0.00 |
October | 20610.41 | 6526.94 | 4952.93 | 3416.76 | 1536.17 | 0.00 | 0.00 |
November | 16123.94 | 6791.06 | 4038.29 | 2591.11 | 1447.19 | 0.00 | 0.00 |
December | 14320.29 | 7296.07 | 3537.05 | 2411.05 | 1126.00 | 0.00 | 0.00 |
Annual Sum or Average | 27300.18 | 5798.64 | 6438.08 | 4400.97 | 2037.11 | 0.00 | 0.00 |
Minimum of Months | 14320.29 | 4373.42 | 3537.05 | 2411.05 | 1126.00 | 0.00 | 0.00 |
Maximum of Months | 48255.73 | 7296.07 | 9650.03 | 7182.26 | 3017.24 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.497767E+09 | 0.739141E+09 | 0.423401E+09 | 0.174017E+09 | 0.249384E+09 | 0.00 | 0.00 |
February | 0.514628E+09 | 0.595526E+09 | 0.460275E+09 | 0.171378E+09 | 0.288898E+09 | 0.00 | 0.00 |
March | 0.685466E+09 | 0.672603E+09 | 0.591811E+09 | 0.208412E+09 | 0.383398E+09 | 0.00 | 0.00 |
April | 0.970766E+09 | 0.601765E+09 | 0.762575E+09 | 0.327045E+09 | 0.435530E+09 | 0.00 | 0.00 |
May | 0.981521E+09 | 0.578411E+09 | 0.805385E+09 | 0.302430E+09 | 0.502955E+09 | 0.00 | 0.00 |
June | 0.106993E+10 | 0.472133E+09 | 0.826817E+09 | 0.344157E+09 | 0.482660E+09 | 0.00 | 0.00 |
July | 0.120578E+10 | 0.473567E+09 | 0.884690E+09 | 0.397366E+09 | 0.487323E+09 | 0.00 | 0.00 |
August | 0.112707E+10 | 0.494832E+09 | 0.811556E+09 | 0.366648E+09 | 0.444908E+09 | 0.00 | 0.00 |
September | 0.893660E+09 | 0.539141E+09 | 0.670721E+09 | 0.297320E+09 | 0.373401E+09 | 0.00 | 0.00 |
October | 0.736382E+09 | 0.601941E+09 | 0.533737E+09 | 0.240278E+09 | 0.293459E+09 | 0.00 | 0.00 |
November | 0.542979E+09 | 0.707859E+09 | 0.466077E+09 | 0.200440E+09 | 0.265637E+09 | 0.00 | 0.00 |
December | 0.492817E+09 | 0.783140E+09 | 0.422642E+09 | 0.187007E+09 | 0.235635E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.971877E+10 | 0.726006E+10 | 0.765969E+10 | 0.321650E+10 | 0.444319E+10 | 0.00 | 0.00 |
Minimum of Months | 0.492817E+09 | 0.472133E+09 | 0.422642E+09 | 0.171378E+09 | 0.235635E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120578E+10 | 0.783140E+09 | 0.884690E+09 | 0.397366E+09 | 0.502955E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.430431E+10 | 0.222894E+10 | 0.359578E+10 | 0.237320E+10 | 0.122258E+10 | 0.00 | 0.00 |
February | 0.432187E+10 | 0.172921E+10 | 0.369269E+10 | 0.207847E+10 | 0.161422E+10 | 0.00 | 0.00 |
March | 0.640231E+10 | 0.187826E+10 | 0.528456E+10 | 0.298800E+10 | 0.229655E+10 | 0.00 | 0.00 |
April | 0.943550E+10 | 0.175929E+10 | 0.764024E+10 | 0.551457E+10 | 0.212568E+10 | 0.00 | 0.00 |
May | 0.958962E+10 | 0.169612E+10 | 0.787735E+10 | 0.501520E+10 | 0.286215E+10 | 0.00 | 0.00 |
June | 0.997425E+10 | 0.140695E+10 | 0.808353E+10 | 0.551674E+10 | 0.256679E+10 | 0.00 | 0.00 |
July | 0.114631E+11 | 0.148325E+10 | 0.915402E+10 | 0.681309E+10 | 0.234093E+10 | 0.00 | 0.00 |
August | 0.106584E+11 | 0.155389E+10 | 0.848566E+10 | 0.646812E+10 | 0.201754E+10 | 0.00 | 0.00 |
September | 0.782227E+10 | 0.166134E+10 | 0.633228E+10 | 0.448014E+10 | 0.185214E+10 | 0.00 | 0.00 |
October | 0.578419E+10 | 0.192229E+10 | 0.469835E+10 | 0.324114E+10 | 0.145721E+10 | 0.00 | 0.00 |
November | 0.436260E+10 | 0.216418E+10 | 0.370715E+10 | 0.237864E+10 | 0.132852E+10 | 0.00 | 0.00 |
December | 0.392589E+10 | 0.241914E+10 | 0.335524E+10 | 0.228712E+10 | 0.106812E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.880443E+11 | 0.219029E+11 | 0.719069E+11 | 0.491544E+11 | 0.227524E+11 | 0.00 | 0.00 |
Minimum of Months | 0.392589E+10 | 0.140695E+10 | 0.335524E+10 | 0.207847E+10 | 0.106812E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114631E+11 | 0.241914E+10 | 0.915402E+10 | 0.681309E+10 | 0.286215E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.416657E+11 | 0.179717E+11 | 0.101528E+11 | 0.670080E+10 | 0.345200E+10 | 0.00 | 0.00 |
February | 0.421254E+11 | 0.137623E+11 | 0.104264E+11 | 0.586862E+10 | 0.455780E+10 | 0.00 | 0.00 |
March | 0.631536E+11 | 0.144673E+11 | 0.149211E+11 | 0.843672E+10 | 0.648438E+10 | 0.00 | 0.00 |
April | 0.873163E+11 | 0.133305E+11 | 0.215725E+11 | 0.155705E+11 | 0.600191E+10 | 0.00 | 0.00 |
May | 0.859719E+11 | 0.134457E+11 | 0.222419E+11 | 0.141606E+11 | 0.808136E+10 | 0.00 | 0.00 |
June | 0.948213E+11 | 0.113359E+11 | 0.228241E+11 | 0.155767E+11 | 0.724741E+10 | 0.00 | 0.00 |
July | 0.129248E+12 | 0.140528E+11 | 0.258466E+11 | 0.192370E+11 | 0.660968E+10 | 0.00 | 0.00 |
August | 0.110794E+12 | 0.148536E+11 | 0.239595E+11 | 0.182629E+11 | 0.569658E+10 | 0.00 | 0.00 |
September | 0.704909E+11 | 0.150201E+11 | 0.178794E+11 | 0.126498E+11 | 0.522958E+10 | 0.00 | 0.00 |
October | 0.552029E+11 | 0.174818E+11 | 0.132659E+11 | 0.915145E+10 | 0.411448E+10 | 0.00 | 0.00 |
November | 0.417933E+11 | 0.176024E+11 | 0.104673E+11 | 0.671615E+10 | 0.375111E+10 | 0.00 | 0.00 |
December | 0.383555E+11 | 0.195418E+11 | 0.947363E+10 | 0.645776E+10 | 0.301587E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.860939E+12 | 0.182866E+12 | 0.203031E+12 | 0.138789E+12 | 0.642422E+11 | 0.00 | 0.00 |
Minimum of Months | 0.383555E+11 | 0.113359E+11 | 0.947363E+10 | 0.586862E+10 | 0.301587E+10 | 0.00 | 0.00 |
Maximum of Months | 0.129248E+12 | 0.195418E+11 | 0.258466E+11 | 0.192370E+11 | 0.808136E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.821923E+09 | -742375145.5 | 0.00 | 0.00 | 744.00 | 0.00 | -79547768.8 | 59.00 | 0.00 | 0.00 |
February | 0.754512E+09 | -682806982.2 | 0.00 | 0.00 | 672.00 | 0.00 | -71705139.0 | 58.99 | 0.00 | 0.00 |
March | 0.868645E+09 | -789290551.7 | 0.00 | 0.00 | 744.00 | 0.00 | -79354383.1 | 58.99 | 0.00 | 0.00 |
April | 0.791136E+09 | -718018458.8 | 0.00 | 0.00 | 720.00 | 0.00 | -73117242.4 | 59.00 | 0.00 | 0.00 |
May | 0.802358E+09 | -727622920.4 | 0.00 | 0.00 | 744.00 | 0.00 | -74735497.5 | 58.99 | 0.00 | 0.00 |
June | 0.778840E+09 | -708299663.7 | 0.00 | 0.00 | 720.00 | 0.00 | -70540041.6 | 58.99 | 0.00 | 0.00 |
July | 0.745571E+09 | -674424370.3 | 0.00 | 0.00 | 744.00 | 0.00 | -71146873.4 | 58.99 | 0.00 | 0.00 |
August | 0.795069E+09 | -723278154.0 | 0.00 | 0.00 | 744.00 | 0.00 | -71790377.7 | 58.99 | 0.00 | 0.00 |
September | 0.750716E+09 | -680581357.5 | 0.00 | 0.00 | 720.00 | 0.00 | -70135110.7 | 58.99 | 0.00 | 0.00 |
October | 0.770799E+09 | -697617664.2 | 0.00 | 0.00 | 744.00 | 0.00 | -73181654.3 | 58.99 | 0.00 | 0.00 |
November | 0.762269E+09 | -687592535.0 | 0.00 | 0.00 | 720.00 | 0.00 | -74676783.5 | 58.99 | 0.00 | 0.00 |
December | 0.810540E+09 | -732061845.8 | 0.00 | 0.00 | 744.00 | 0.00 | -78477859.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.945238E+10 | -0.856397E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -888408732.0 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.745571E+09 | -789290551.7 | 0.00 | 0.00 | 672.00 | 0.00 | -79547768.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.868645E+09 | -674424370.3 | 0.00 | 0.00 | 744.00 | 0.00 | -70135110.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.66 | 0.26 | 01-JAN-11:00 | 225.02 | 0.00 | 0.00 | 55.50 | 184.44 | 0.00 | 0.00 | 32.67 |
February | 279.67 | 0.56 | 0.26 | 01-FEB-11:09 | 294.83 | 0.00 | 0.00 | 115.00 | 1042.95 | 0.00 | 0.00 | 86.67 |
March | 338.17 | 0.51 | 0.26 | 01-MAR-11:39 | 1348.44 | 0.00 | 0.00 | 195.00 | 361.53 | 0.00 | 0.00 | 133.33 |
April | 358.33 | 0.50 | 0.26 | 01-APR-10:20 | 348.37 | 0.00 | 0.00 | 204.83 | 275.06 | 0.00 | 0.00 | 151.67 |
May | 393.83 | 0.48 | 0.26 | 01-MAY-09:39 | 415.04 | 0.00 | 0.00 | 252.67 | 2912.21 | 0.00 | 0.00 | 177.67 |
June | 381.00 | 0.49 | 0.26 | 01-JUN-09:39 | 2508.60 | 0.00 | 0.00 | 238.17 | 1068.53 | 0.00 | 0.00 | 160.50 |
July | 408.67 | 0.51 | 0.26 | 01-JUL-09:20 | 366.09 | 0.00 | 0.00 | 235.50 | 3537.69 | 0.00 | 0.00 | 162.67 |
August | 390.67 | 0.51 | 0.26 | 01-AUG-09:30 | 1073.11 | 0.00 | 0.00 | 234.50 | 1111.15 | 0.00 | 0.00 | 149.00 |
September | 328.83 | 0.51 | 0.26 | 01-SEP-10:20 | 329.27 | 0.00 | 0.00 | 175.33 | 260.95 | 0.00 | 0.00 | 115.50 |
October | 296.17 | 0.62 | 0.26 | 01-OCT-09:00 | 2151.03 | 0.00 | 0.00 | 113.50 | 206.71 | 0.00 | 0.00 | 56.83 |
November | 300.00 | 0.64 | 0.26 | 01-NOV-09:39 | 238.71 | 0.00 | 0.00 | 75.00 | 195.02 | 0.00 | 0.00 | 49.00 |
December | 297.00 | 0.70 | 0.26 | 01-DEC-10:39 | 196.20 | 0.00 | 0.00 | 39.17 | 162.22 | 0.00 | 0.00 | 19.33 |
Annual Sum or Average | 4065.67 | 0.55 | 809.85 | 0.00 | 0.00 | 1934.17 | 1046.37 | 0.00 | 0.00 | 1294.83 | ||
Minimum of Months | 279.67 | 0.48 | 0.26 | 196.20 | 0.00 | 0.00 | 39.17 | 162.22 | 0.00 | 0.00 | 19.33 | |
Maximum of Months | 408.67 | 0.70 | 0.26 | 2508.60 | 0.00 | 0.00 | 252.67 | 3537.69 | 0.00 | 0.00 | 177.67 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.45 | 0.26 | 01-JAN-08:00 | 270.71 | 18.09 | 50.83 | 198.83 | 222.87 | 18.93 | 69.50 | 157.33 |
February | 279.67 | 0.40 | 0.26 | 01-FEB-08:39 | 344.80 | 19.10 | 78.33 | 216.33 | 1300.19 | 19.92 | 96.33 | 182.00 |
March | 338.17 | 0.39 | 0.26 | 01-MAR-08:39 | 411.40 | 19.56 | 120.67 | 277.83 | 453.30 | 20.40 | 138.50 | 244.50 |
April | 358.33 | 0.36 | 0.26 | 01-APR-07:30 | 2242.20 | 20.80 | 129.17 | 303.50 | 351.68 | 20.67 | 134.17 | 260.00 |
May | 393.83 | 0.36 | 0.26 | 01-MAY-06:40 | 468.42 | 19.89 | 135.00 | 340.67 | 396.99 | 20.76 | 154.00 | 297.17 |
June | 381.00 | 0.36 | 0.26 | 01-JUN-06:40 | 445.86 | 19.42 | 112.83 | 333.33 | 374.74 | 20.30 | 131.33 | 290.17 |
July | 408.67 | 0.37 | 0.26 | 01-JUL-06:30 | 423.38 | 19.35 | 136.33 | 340.83 | 356.57 | 20.28 | 155.33 | 295.17 |
August | 390.67 | 0.37 | 0.26 | 01-AUG-07:10 | 2413.48 | 20.48 | 136.33 | 320.50 | 333.20 | 20.30 | 138.83 | 270.50 |
September | 328.83 | 0.37 | 0.26 | 01-SEP-06:00 | 390.28 | 19.03 | 87.17 | 275.00 | 323.66 | 19.92 | 105.00 | 234.00 |
October | 296.17 | 0.44 | 0.26 | 01-OCT-09:39 | 3609.62 | 19.55 | 84.33 | 223.50 | 1378.29 | 20.57 | 90.50 | 190.50 |
November | 300.00 | 0.45 | 0.26 | 01-NOV-07:49 | 284.09 | 17.75 | 64.33 | 203.17 | 233.46 | 18.58 | 88.33 | 164.50 |
December | 297.00 | 0.49 | 0.26 | 01-DEC-08:20 | 236.60 | 17.24 | 23.17 | 180.67 | 194.26 | 18.07 | 37.83 | 131.33 |
Annual Sum or Average | 4065.67 | 0.40 | 969.47 | 19.27 | 1158.50 | 3214.17 | 473.64 | 19.96 | 1339.67 | 2717.17 | ||
Minimum of Months | 279.67 | 0.36 | 0.26 | 236.60 | 17.24 | 23.17 | 180.67 | 194.26 | 18.07 | 37.83 | 131.33 | |
Maximum of Months | 408.67 | 0.49 | 0.26 | 3609.62 | 20.80 | 136.33 | 340.83 | 1378.29 | 20.76 | 155.33 | 297.17 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.325311E+09 | 26892.65 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140393E+09 | 23669.12 | 28-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.284235E+09 | 26892.65 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11897719.31 | 26892.65 | 01-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 554890.03 | 2774.45 | 15-MAY-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17872921.20 | 10152.89 | 24-NOV-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138123E+09 | 25329.79 | 15-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.918388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.325311E+09 | 26892.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 66091449.98 | 16151.77 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66091449.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 66091449.98 | 16151.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.459807E+09 | 0.437720E+09 | 5314.67 | 24-JAN-15:30 | 5076.26 | 0.00 |
February | 0.00 | 0.00 | 0.130156E+09 | 0.129388E+09 | 4597.33 | 01-FEB-12:00 | 4597.33 | 0.00 |
March | 0.00 | 0.00 | 0.284732E+09 | 0.244358E+09 | 6147.51 | 23-MAR-14:00 | 4689.52 | 0.00 |
April | 0.00 | 0.00 | 0.114627E+10 | 0.934823E+09 | 17798.45 | 15-APR-07:02 | 12098.60 | 0.00 |
May | 0.00 | 0.00 | 0.126327E+10 | 0.105389E+10 | 18869.38 | 06-MAY-07:02 | 11265.71 | 0.00 |
June | 0.00 | 0.00 | 0.385421E+10 | 0.288710E+10 | 20112.27 | 30-JUN-07:02 | 11664.03 | 0.00 |
July | 0.00 | 0.00 | 0.717393E+10 | 0.511605E+10 | 20701.33 | 25-JUL-07:02 | 11369.21 | 0.00 |
August | 0.00 | 0.00 | 0.786801E+10 | 0.550254E+10 | 21225.55 | 19-AUG-07:02 | 11245.09 | 0.00 |
September | 0.00 | 0.00 | 0.426559E+10 | 0.318456E+10 | 21045.93 | 22-SEP-07:03 | 10606.86 | 0.00 |
October | 0.00 | 0.00 | 0.409760E+10 | 0.341696E+10 | 21179.05 | 05-OCT-07:02 | 11038.49 | 0.00 |
November | 0.00 | 0.00 | 0.392885E+09 | 0.383775E+09 | 5676.13 | 18-NOV-14:40 | 5585.53 | 0.00 |
December | 0.00 | 0.00 | 0.569703E+09 | 0.566090E+09 | 5668.90 | 05-DEC-15:00 | 5668.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.315062E+11 | 0.238572E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.130156E+09 | 0.129388E+09 | 4597.33 | 4597.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.786801E+10 | 0.550254E+10 | 21225.55 | 12098.60 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.207388E+09 | 0.185333E+09 | 62436.77 | 30-APR-12:55 | 52679.42 | 0.00 |
May | 0.00 | 0.00 | 98810101.27 | 87090384.50 | 6157.54 | 04-MAY-12:10 | 5269.79 | 0.00 |
June | 0.00 | 0.00 | 0.148365E+10 | 0.105386E+10 | 65936.28 | 29-JUN-17:45 | 41869.64 | 0.00 |
July | 0.00 | 0.00 | 0.735226E+10 | 0.510657E+10 | 68284.25 | 18-JUL-17:11 | 42213.14 | 0.00 |
August | 0.00 | 0.00 | 0.758293E+10 | 0.513646E+10 | 67946.89 | 13-AUG-10:25 | 42968.09 | 0.00 |
September | 0.00 | 0.00 | 0.213289E+10 | 0.192826E+10 | 65370.29 | 10-SEP-14:01 | 44462.61 | 0.00 |
October | 0.00 | 0.00 | 0.339068E+10 | 0.317247E+10 | 68318.66 | 01-OCT-12:00 | 44120.18 | 0.00 |
November | 0.00 | 0.00 | 2583525.65 | 2583525.65 | 1428.54 | 18-NOV-14:00 | 1428.54 | 0.00 |
December | 0.00 | 0.00 | 82.53 | 82.53 | 0.14 | 05-DEC-15:10 | 0.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.222512E+11 | 0.166726E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.758293E+10 | 0.513646E+10 | 68318.66 | 52679.42 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.120644E+10 | 0.34 | 1217.73 | 23-JAN-07:10 | 0.92 |
February | 0.110910E+10 | 0.35 | 1217.73 | 01-FEB-08:50 | 0.92 |
March | 0.130211E+10 | 0.37 | 1217.73 | 10-MAR-09:50 | 0.92 |
April | 0.120555E+10 | 0.35 | 1217.73 | 01-APR-07:03 | 0.92 |
May | 0.125377E+10 | 0.35 | 1217.73 | 02-MAY-08:70 | 0.92 |
June | 0.125377E+10 | 0.36 | 1217.73 | 02-JUN-09:00 | 0.92 |
July | 0.120555E+10 | 0.34 | 1217.73 | 14-JUL-07:20 | 0.91 |
August | 0.130199E+10 | 0.36 | 1217.73 | 01-AUG-07:10 | 0.92 |
September | 0.120555E+10 | 0.35 | 1217.73 | 25-SEP-16:30 | 0.91 |
October | 0.120555E+10 | 0.34 | 1217.73 | 12-OCT-10:40 | 0.93 |
November | 0.115733E+10 | 0.34 | 1217.73 | 01-NOV-11:20 | 0.92 |
December | 0.120555E+10 | 0.34 | 1217.73 | 06-DEC-17:40 | 0.93 |
Annual Sum or Average | 0.146122E+11 | 0.35 | |||
Minimum of Months | 0.110910E+10 | 0.34 | 1217.73 | 0.91 | |
Maximum of Months | 0.130211E+10 | 0.37 | 1217.73 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.305015E+10 | 0.33 | 3078.26 | 03-JAN-07:02 | 0.89 |
February | 0.280368E+10 | 0.33 | 3078.26 | 01-FEB-07:05 | 0.89 |
March | 0.329128E+10 | 0.35 | 3078.26 | 01-MAR-07:02 | 0.89 |
April | 0.305025E+10 | 0.34 | 3078.26 | 12-APR-13:40 | 0.89 |
May | 0.316938E+10 | 0.34 | 3078.26 | 24-MAY-11:50 | 0.89 |
June | 0.318453E+10 | 0.35 | 3078.26 | 26-JUN-14:20 | 0.88 |
July | 0.317425E+10 | 0.35 | 3078.26 | 01-JUL-06:07 | 0.88 |
August | 0.336321E+10 | 0.37 | 3078.26 | 07-AUG-08:50 | 0.88 |
September | 0.306181E+10 | 0.34 | 3078.26 | 07-SEP-15:00 | 0.88 |
October | 0.307125E+10 | 0.34 | 3078.26 | 14-OCT-10:30 | 0.89 |
November | 0.292558E+10 | 0.33 | 3078.26 | 18-NOV-13:20 | 0.89 |
December | 0.304748E+10 | 0.33 | 3078.26 | 05-DEC-15:10 | 0.89 |
Annual Sum or Average | 0.371928E+11 | 0.34 | |||
Minimum of Months | 0.280368E+10 | 0.33 | 3078.26 | 0.88 | |
Maximum of Months | 0.336321E+10 | 0.37 | 3078.26 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.131808E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.114071E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.137066E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.147945E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.155579E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.215160E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.285279E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.310419E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.222353E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.219800E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.125257E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.134389E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.219912E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114071E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.310419E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.305015E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.280368E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.329128E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.310225E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.319478E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.355028E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.496246E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.522413E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.364722E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.400164E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.292628E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.304748E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.428016E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.280368E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.522413E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.120644E+10 | 0.459807E+09 | 0.325311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110910E+10 | 0.130156E+09 | 0.140393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130211E+10 | 0.284732E+09 | 0.284235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120555E+10 | 0.114627E+10 | 11897719.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125377E+10 | 0.126327E+10 | 554890.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125377E+10 | 0.385421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120555E+10 | 0.717393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130199E+10 | 0.786801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120555E+10 | 0.426559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120555E+10 | 0.409760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115733E+10 | 0.392885E+09 | 17872921.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120555E+10 | 0.569703E+09 | 0.138123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146122E+11 | 0.315062E+11 | 0.918388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110910E+10 | 0.130156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130211E+10 | 0.786801E+10 | 0.325311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.305015E+10 | 0.00 | 66091449.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.329128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.305025E+10 | 0.207388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.316938E+10 | 98810101.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.318453E+10 | 0.148365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.317425E+10 | 0.735226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.336321E+10 | 0.758293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.306181E+10 | 0.213289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.307125E+10 | 0.339068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.292558E+10 | 2583525.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304748E+10 | 82.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371928E+11 | 0.222512E+11 | 66091449.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.280368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.336321E+10 | 0.758293E+10 | 66091449.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.120644E+10 | 0.00 | 0.00 | 0.00 | 0.111640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110910E+10 | 0.00 | 0.00 | 0.00 | 31601373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130211E+10 | 0.00 | 0.00 | 0.00 | 68549043.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120555E+10 | 0.00 | 0.00 | 0.00 | 0.273901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125377E+10 | 0.00 | 0.00 | 0.00 | 0.302021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125377E+10 | 0.00 | 0.00 | 0.00 | 0.897827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120555E+10 | 0.00 | 0.00 | 0.00 | 0.164724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130199E+10 | 0.00 | 0.00 | 0.00 | 0.180220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120555E+10 | 0.00 | 0.00 | 0.00 | 0.101799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120555E+10 | 0.00 | 0.00 | 0.00 | 0.992453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115733E+10 | 0.00 | 0.00 | 0.00 | 95248257.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120555E+10 | 0.00 | 0.00 | 0.00 | 0.138339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146122E+11 | 0.00 | 0.00 | 0.00 | 0.737900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110910E+10 | 0.00 | 0.00 | 0.00 | 31601373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130211E+10 | 0.00 | 0.00 | 0.00 | 0.180220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.305015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.329128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.305025E+10 | 0.00 | 0.00 | 0.00 | 52001873.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.316938E+10 | 0.00 | 0.00 | 0.00 | 25399422.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.318453E+10 | 0.00 | 0.00 | 0.00 | 0.365759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.317425E+10 | 0.00 | 0.00 | 0.00 | 0.178821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.336321E+10 | 0.00 | 0.00 | 0.00 | 0.186092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.306181E+10 | 0.00 | 0.00 | 0.00 | 0.585412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.307125E+10 | 0.00 | 0.00 | 0.00 | 0.930387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.292558E+10 | 0.00 | 0.00 | 0.00 | 697489.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304748E+10 | 0.00 | 0.00 | 0.00 | 21.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371928E+11 | 0.00 | 0.00 | 0.00 | 0.560879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.280368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.336321E+10 | 0.00 | 0.00 | 0.00 | 0.186092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.349772E+09 | 6150543.15 | 0.00 | 1643411.46 | 0.00 | 60167210.69 | 0.151395E+10 | 0.00 | 0.35 |
February | 0.434173E+09 | 3577413.34 | 0.00 | 1268313.35 | 0.00 | 25890757.86 | 0.137525E+10 | 0.00 | 0.32 |
March | 0.516623E+09 | 0.00 | 0.00 | 1543471.37 | 0.00 | 56898580.63 | 0.152161E+10 | 0.00 | 0.34 |
April | 0.102462E+09 | 6126015.02 | 0.00 | 4161934.41 | 0.00 | 1419910.10 | 0.287933E+10 | 0.00 | 0.68 |
May | 60201779.80 | 7174728.39 | 0.00 | 5081458.22 | 0.00 | 166442.93 | 0.337462E+10 | 0.00 | 0.75 |
June | 14578959.05 | 0.147108E+09 | 0.00 | 5994685.91 | 0.00 | 0.00 | 0.243539E+10 | 0.00 | 0.91 |
July | 9223503.72 | 0.572665E+09 | 0.00 | 5080018.56 | 0.00 | 0.00 | 0.986798E+09 | 0.00 | 0.74 |
August | 7289176.94 | 0.753318E+09 | 0.00 | 3803964.75 | 0.00 | 0.00 | 0.893356E+09 | 0.00 | 0.78 |
September | 5137616.91 | 0.160309E+09 | 0.00 | 5822850.24 | 0.00 | 0.00 | 0.218610E+10 | 0.00 | 0.84 |
October | 33241888.99 | 0.280502E+09 | 0.00 | 4415143.81 | 16079.03 | 0.00 | 0.183595E+10 | 0.00 | 0.67 |
November | 0.179578E+09 | 1621223.62 | 0.00 | 2843928.65 | 0.00 | 1371312.16 | 0.247676E+10 | 0.00 | 0.50 |
December | 0.289954E+09 | 2168855.63 | 0.00 | 2224110.67 | 0.00 | 16652065.03 | 0.180882E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.200224E+10 | 0.194072E+10 | 0.00 | 43883291.40 | 16079.03 | 0.162566E+09 | 0.232879E+11 | 0.00 | 0.61 |
Minimum of Months | 5137616.91 | 0.00 | 0.00 | 1268313.35 | 0.00 | 0.00 | 0.893356E+09 | 0.00 | 0.32 |
Maximum of Months | 0.516623E+09 | 0.753318E+09 | 0.00 | 5994685.91 | 16079.03 | 60167210.69 | 0.337462E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.341068E+10 | 0.00 | 0.00 | 0.00 | 3025671.33 | 0.00 | 0.00 | 0.00 | 0.18 |
February | 0.332762E+10 | 0.00 | 0.00 | 0.00 | 626177.36 | 0.00 | 0.00 | 0.00 | 0.18 |
March | 0.406379E+10 | 0.00 | 0.00 | 19857.40 | 0.00 | 0.00 | 52198800.75 | 0.00 | 0.19 |
April | 0.312093E+10 | 0.00 | 0.00 | 1404275.73 | 324779.75 | 0.00 | 0.175359E+10 | 0.00 | 0.26 |
May | 0.303305E+10 | 147006.73 | 0.00 | 1822293.48 | 0.00 | 0.00 | 0.237079E+10 | 0.00 | 0.27 |
June | 0.144239E+10 | 0.00 | 0.00 | 7304818.63 | 0.00 | 0.00 | 0.608446E+10 | 0.00 | 0.52 |
July | 88534490.08 | 0.246916E+09 | 0.00 | 15384465.14 | 0.00 | 0.00 | 0.813393E+10 | 0.00 | 0.76 |
August | 0.107757E+09 | 0.231684E+09 | 0.00 | 14310423.13 | 0.00 | 0.00 | 0.778978E+10 | 0.00 | 0.81 |
September | 0.715425E+09 | 0.117657E+09 | 0.00 | 6943145.88 | 0.00 | 0.00 | 0.682984E+10 | 0.00 | 0.50 |
October | 0.116744E+10 | 0.266248E+09 | 0.00 | 4573811.71 | 0.00 | 0.00 | 0.406599E+10 | 0.00 | 0.41 |
November | 0.377297E+10 | 0.00 | 0.00 | 1491.34 | 0.00 | 0.00 | 25164720.72 | 0.00 | 0.18 |
December | 0.344788E+10 | 0.00 | 0.00 | 5573.00 | 0.00 | 0.00 | 34568167.40 | 0.00 | 0.18 |
Annual Sum or Average | 0.276985E+11 | 0.862651E+09 | 0.00 | 51770155.43 | 3976628.44 | 0.00 | 0.371403E+11 | 0.00 | 0.37 |
Minimum of Months | 88534490.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.406379E+10 | 0.266248E+09 | 0.00 | 15384465.14 | 3025671.33 | 0.00 | 0.813393E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.372744E+12 | 0.272155E+11 | 0.00 | 0.532704E+10 | 0.754263E+09 |
February | 0.431387E+12 | 0.350700E+11 | 0.00 | 0.516000E+10 | 0.229633E+09 |
March | 0.610686E+12 | 0.413637E+11 | 0.00 | 0.621268E+10 | 0.486239E+09 |
April | 0.817675E+12 | 0.336918E+11 | 0.00 | 0.785684E+10 | 0.168463E+10 |
May | 0.856085E+12 | 0.446946E+11 | 0.00 | 0.883841E+10 | 0.168979E+10 |
June | 0.856307E+12 | 0.348778E+11 | 0.00 | 0.984300E+10 | 0.660144E+10 |
July | 0.931932E+12 | 0.358338E+11 | 0.00 | 0.846338E+10 | 0.179616E+11 |
August | 0.865231E+12 | 0.404744E+11 | 0.00 | 0.786348E+10 | 0.191141E+11 |
September | 0.680767E+12 | 0.315776E+11 | 0.00 | 0.947667E+10 | 0.800188E+10 |
October | 0.475550E+12 | 0.355676E+11 | 0.00 | 0.656483E+10 | 0.941111E+10 |
November | 0.403014E+12 | 0.352568E+11 | 0.00 | 0.645706E+10 | 0.500329E+09 |
December | 0.335501E+12 | 0.310735E+11 | 0.00 | 0.559794E+10 | 0.774436E+09 |
Annual Sum or Average | 0.763688E+13 | 0.426697E+12 | 0.00 | 0.876613E+11 | 0.672095E+11 |
Minimum of Months | 0.335501E+12 | 0.272155E+11 | 0.00 | 0.516000E+10 | 0.229633E+09 |
Maximum of Months | 0.931932E+12 | 0.446946E+11 | 0.00 | 0.984300E+10 | 0.191141E+11 |