Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 10:43:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2068.29 | 427.76 | 427.76 |
Net Site Energy | 2068.29 | 427.76 | 427.76 |
Total Source Energy | 3612.60 | 747.16 | 747.16 |
Net Source Energy | 3612.60 | 747.16 | 747.16 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1410.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 108.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 51.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 657.98 | 1410.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1410.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 327.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 108.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 51.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 28.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1410.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 327.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 108.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 51.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 28.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 90.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 17.01 | 291.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 136.08 | 291.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 90.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 17.01 | 291.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 136.08 | 291.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 657.981 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 657.981 | 100.00 |
Total On-Site and Utility Electric Sources | 657.981 | 100.00 |
Total Electricity End Uses | 657.981 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 106.83 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2873.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 96.62 |
Skylight-Roof Ratio [%] | 2.10 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.6485 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 12.8090 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 5.4896 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.7537 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.7537 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 8.6485 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 12.8090 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 5.4896 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.7537 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.7537 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.7537 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 05-JAN-15:39 | 28-JAN-17:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 233314.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 31354.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3797.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2692.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 54943.40 | 233314.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 233314.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 31354.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3797.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 2692.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1528.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1037.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 344.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 164.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2083.83 | 1528.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 316.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 33.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 430.98 | 316.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 316.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 33.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 430.98 | 316.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.00 |
ZONE2 FINE STORAGE DIRECT AIR | 2.29 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 2.53 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 2.53 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 101852.77 |
PSZ-OFFICE HEATING COIL | 30315.80 |
PSZ-FINE STORAGE HEATING COIL | 95780.97 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 101852.76 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.000000 | 1.00 |
PSZ-FINE STORAGE | 2.29 | 2.29 | 2.29 | 2.29 | 2.29 | 2.29 | 1.00 | 1.00 | 2.29 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.00 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.29 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.00 | 1110.83 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.29 | 2451.90 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 1.00 | 16608.43 | 30315.80 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.29 | 2.29 | 2.29 | 2.29 | 42280.07 | 95780.97 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.00 | 0.501658 | 1.00 | 16608.43 | 8304.25 | 16608.43 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 2.29 | 1.15 | 2.29 | 42280.07 | 20949.23 | 42280.07 | 0.800830 | 0.800830 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 121 | 97 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 25.27 | 11 | 23 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 71.35 | 6 | 68 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 8.649 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 16.722 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 12.809 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.809 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 5.490 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.048 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2048.656 | 8.649 | 160.695 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2048.656 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 17848.242 | 12.809 | 594.941 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 17848.242 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 17593.267 | 5.490 | 254.975 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 17593.267 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1041 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.4317E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.4042E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 9.529 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 23.09 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 24.66 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
2 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
3 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
4 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
5 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
6 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
7 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
8 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
9 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
10 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
11 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
12 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
13 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
14 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
15 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
16 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.40943546E-08 | -0.48941433E-14 | 0.10002011E-14 | -0.40158259E-16 |
55 | 6 | 0.31272124E-05 | 0.19933103E-08 | 0.31973031E-02 | -0.26821658E-04 |
56 | 5 | -0.21335304E-03 | 0.11766416E-05 | -0.22414699 | 0.19598788E-02 |
57 | 4 | 0.48316011E-02 | 0.53476752E-04 | 4.8365802 | -0.45332602E-01 |
58 | 3 | -0.42187430E-01 | 0.42463702E-03 | -38.061149 | 0.39909293 |
59 | 2 | 0.14945981 | 0.70555311E-03 | 116.56127 | -1.4189736 |
60 | 1 | -0.21550367 | 0.21454475E-03 | -143.95282 | 2.0497880 |
61 | 0 | 0.10501452 | 0.52166033E-05 | 60.838472 | |
62 | 7 | -0.99354594E-08 | 0.85994744E-15 | -0.36446392E-14 | 0.33402613E-16 |
63 | 6 | 0.19007305E-05 | 0.85218543E-09 | 0.32020323E-02 | -0.26861330E-04 |
64 | 5 | -0.10257637E-03 | 0.49552608E-06 | -0.22441548 | 0.19622488E-02 |
65 | 4 | 0.21308868E-02 | 0.22341873E-04 | 4.8410464 | -0.45375540E-01 |
66 | 3 | -0.17974913E-01 | 0.17625076E-03 | -38.086349 | 0.39937154 |
67 | 2 | 0.62772635E-01 | 0.29099605E-03 | 116.61028 | -1.4196292 |
68 | 1 | -0.89915137E-01 | 0.87799409E-04 | -143.98166 | 2.0502620 |
69 | 0 | 0.43667207E-01 | 0.21083643E-05 | 60.838472 | |
70 | 7 | -0.10614037E-07 | 0.12466653E-14 | -0.85452615E-14 | 0.12855439E-15 |
71 | 6 | 0.18765462E-05 | 0.80237200E-09 | 0.32022472E-02 | -0.26863133E-04 |
72 | 5 | -0.98338504E-04 | 0.46542478E-06 | -0.22442766 | 0.19623563E-02 |
73 | 4 | 0.20165412E-02 | 0.20956150E-04 | 4.8412485 | -0.45377483E-01 |
74 | 3 | -0.16916006E-01 | 0.16514078E-03 | -38.087488 | 0.39938413 |
75 | 2 | 0.58934009E-01 | 0.27235831E-03 | 116.61249 | -1.4196588 |
76 | 1 | -0.84323034E-01 | 0.82076304E-04 | -143.98296 | 2.0502833 |
77 | 0 | 0.40927925E-01 | 0.19639094E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20666597E-14 | 0.96147816E-16 | 0.79647225E-12 | 0.11382549E-15 |
85 | 3 | -0.56581374E-04 | 0.28930881E-06 | -0.38972706E-03 | 0.15282143E-12 |
86 | 2 | 1.1494565 | 0.62914578E-02 | 1.7513786 | -0.74717338E-04 |
87 | 1 | -17.155584 | 0.16244765 | -7.1131205 | 0.33567575 |
88 | 0 | 16.278262 | 0.10333854 | 5.6342095 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.2921_SHGC_SOUTH_0.45 | 34 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.2921_SHGC_NORTH_0.45 | 35 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.2921_SHGC_EAST_0.45 | 36 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.2921_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.45 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.456 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.456 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30035 | 0.25772 | 0.25772 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30035 | 0.25772 | 0.25772 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE2 FINE STORAGE | 17 | 0 |
2 | ZONE3 BULK STORAGE | 48 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE2 FINE STORAGE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.099 | 0.453 | 0.451 |
2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.453 | 0.451 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2603E-004 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.0503E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0814E-004 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.0312E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8567E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8352E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1606E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3296E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5459E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7670E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0987E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9482E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0924E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6035E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.7779E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7507E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3846E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5564E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.4870E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6931E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3402E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2410E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.0450E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2702E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7818E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3504E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6079E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4327E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1810E-004 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2820E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1123E-004 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8493E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5683E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4565E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4751E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5054E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9285E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6063E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6368E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5142E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2215E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9546E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1950E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9641E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3286E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2997E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0789E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3753E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4795E-004 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3883E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5786E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8992E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.7663E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5084E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8083E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4244E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2875E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.4995E-005 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3793E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0574E-004 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6227E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1556E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2717E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6600E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5628E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4301E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4447E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6594E-004 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1465E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9452E-005 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.0410E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3591E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.5004E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5976E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1601E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0925E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1946E-003 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4764E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8539E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8974E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3260E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0152E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5373E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0925E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2509E-003 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3241E-005 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5269E-003 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2321E-005 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6234E-004 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7182E-005 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.4942E-004 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1192E-005 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.2496E-004 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.9554E-005 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8936E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6268E-005 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1617E-004 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5632E-005 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3343E-004 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7562E-005 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1773E-004 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4328E-005 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1486E-004 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4139E-005 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1651E-004 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4854E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6106E-004 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4711E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8784E-004 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.7182E-004 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8834E-004 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1726E-004 |
113 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3771E-004 |
114 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1391E-003 |
115 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1783E-004 |
116 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2530E-003 |
117 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1102E-004 |
118 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2632E-003 |
119 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3035E-004 |
120 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0060E-004 |
121 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3602E-005 |
122 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6052E-003 |
123 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5462E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5275E-003 |
125 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4455E-005 |
126 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0574E-003 |
127 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1002E-005 |
128 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.5996E-003 |
129 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1040E-005 |
130 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2142E-004 |
131 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3284E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5551E-004 |
133 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1787E-005 |
134 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2509E-003 |
135 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8473E-005 |
136 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4173E-003 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5559E-005 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2020E-005 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8238E-005 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8783E-005 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3588E-005 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9847E-005 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8839E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1433E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8882E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2644E-005 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6103E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4543E-005 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6044E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2975E-005 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7481E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7481E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9801E-005 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6665E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8662E-005 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6022E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2235E-005 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9989E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2851E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1028E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5736E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8669E-004 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7832E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2558E-004 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0974E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6158E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8391E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8069E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0652E-005 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2193E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2389E-005 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6510E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4967E-005 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2509E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9183E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2479E-005 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5429E-005 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7766E-005 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5877E-005 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7394E-005 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4646E-005 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0456E-005 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2872E-005 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1031E-005 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4067E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8122E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9400E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7018E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1991E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4929E-005 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8375E-005 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1426E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0074E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5935E-004 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0008E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3633E-004 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0624E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3628E-004 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7197E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9091E-004 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0289E-004 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9806E-004 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3321E-004 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4842E-004 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7074E-004 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9915E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6610E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1295E-004 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6223E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4701E-005 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5077E-004 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0205E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0217E-004 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5714E-005 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6601E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3004E-005 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6571E-005 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7868E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6566E-005 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7412E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6509E-005 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0674E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3995E-005 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1175E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1348E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0627E-004 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0122E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0862E-004 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6064E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0329E-004 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8470E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2340E-005 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7241E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2540E-004 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8655E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6121E-004 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6382E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3316E-004 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8535E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7956E-004 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6982E-005 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7864E-005 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6428E-005 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7326E-005 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8076E-005 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0816E-005 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5177E-005 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1298E-005 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4071E-004 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1588E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3347E-004 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9671E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7804E-004 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0674E-003 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4001E-004 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7659E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6455E-005 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7748E-005 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5434E-005 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7146E-005 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8629E-005 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0839E-005 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5974E-005 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1370E-005 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0273E-003 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0486E-004 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0005E-003 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0130E-004 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7665E-003 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2045E-004 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8124E-003 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1239E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4874E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6015E-004 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8597E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4805E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5648E-003 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9036E-004 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8158E-003 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8061E-004 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7387E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3527E-003 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5696E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2951E-003 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3742E-004 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5667E-003 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2117E-004 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9796E-003 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5104E-005 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7537E-005 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3821E-005 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6894E-005 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7797E-005 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0731E-005 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5964E-005 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1369E-005 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7234E-004 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0445E-003 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4871E-004 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9965E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0204E-004 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8199E-003 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1995E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9232E-003 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4685E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0102E-005 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5626E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3629E-005 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3033E-003 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0781E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7848E-003 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0987E-005 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5464E-004 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4758E-004 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4131E-004 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1208E-004 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1606E-003 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5010E-004 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7881E-003 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7534E-004 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3069E-004 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5527E-004 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0978E-004 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7100E-004 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1832E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9082E-004 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3831E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5273E-004 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8351E-004 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0294E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1053E-004 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7434E-004 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7725E-004 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4430E-004 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6954E-004 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7432E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5776E-005 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1735E-005 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4346E-005 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8333E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8722E-005 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0587E-005 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7466E-005 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1261E-005 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3301E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7263E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1957E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6603E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5964E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0519E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5155E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1296E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4540E-005 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7715E-004 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1316E-005 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4385E-004 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5606E-005 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3871E-004 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6327E-005 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8618E-004 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6271E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0802E-004 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3176E-004 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1996E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2009E-004 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9612E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6234E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1106E-004 |
369 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1443E-005 |
370 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6962E-005 |
371 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0169E-005 |
372 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6304E-005 |
373 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3922E-005 |
374 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0254E-005 |
375 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3970E-005 |
376 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1172E-005 |
377 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5709E-004 |
378 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0431E-005 |
379 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9711E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4080E-005 |
381 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1804E-004 |
382 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7693E-005 |
383 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6891E-004 |
384 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1889E-005 |
385 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5317E-004 |
386 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3400E-005 |
387 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2647E-004 |
388 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8479E-005 |
389 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2993E-004 |
390 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3579E-005 |
391 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6225E-004 |
392 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2685E-005 |
393 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7357E-004 |
394 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4353E-005 |
395 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9574E-004 |
396 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4994E-005 |
397 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
398 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1834E-005 |
399 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7132E-005 |
400 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6576E-005 |
401 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2006E-004 |
402 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4664E-005 |
403 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1327E-004 |
404 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3285E-005 |
405 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8878E-004 |
406 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6959E-005 |
407 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2073E-004 |
408 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1151E-005 |
409 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1983E-004 |
410 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8466E-005 |
411 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0580E-004 |
412 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6490E-005 |
413 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3946E-004 |
414 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1158E-005 |
415 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3811E-004 |
416 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9170E-005 |
417 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6545E-005 |
418 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4938E-005 |
419 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7190E-005 |
420 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3140E-005 |
421 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4010E-005 |
422 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6959E-005 |
423 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6264E-005 |
424 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6523E-005 |
425 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1576E-005 |
426 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1993E-005 |
427 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6055E-005 |
428 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0474E-005 |
429 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6818E-005 |
430 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3817E-005 |
431 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8821E-005 |
432 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4273E-005 |
433 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1632E-004 |
434 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5509E-005 |
435 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2779E-004 |
436 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5085E-005 |
437 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1513E-004 |
438 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5450E-005 |
439 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3980E-004 |
440 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9222E-005 |
441 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2572E-004 |
442 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1817E-005 |
443 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4701E-004 |
444 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3217E-005 |
445 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3988E-005 |
446 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7980E-005 |
447 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9165E-005 |
448 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4312E-005 |
449 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7659E-004 |
450 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2017E-005 |
451 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6105E-004 |
452 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0124E-005 |
453 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4398E-004 |
454 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5189E-005 |
455 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1951E-004 |
456 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1128E-005 |
457 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5224E-005 |
458 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1524E-005 |
459 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3032E-005 |
460 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0733E-005 |
461 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0142E-005 |
462 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4032E-005 |
463 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6274E-005 |
464 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3215E-005 |
465 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2252E-005 |
466 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9054E-005 |
467 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9275E-005 |
468 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8119E-005 |
469 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3499E-005 |
470 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1918E-005 |
471 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2499E-005 |
472 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2391E-005 |
473 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2650E-005 |
474 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1713E-005 |
475 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5330E-005 |
476 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1407E-005 |
477 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4323E-005 |
478 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3218E-005 |
479 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2635E-005 |
480 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2402E-005 |
481 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5815E-005 |
482 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1242E-005 |
483 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9783E-005 |
484 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1182E-005 |
485 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4867E-005 |
486 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2383E-005 |
487 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7239E-005 |
488 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1883E-005 |
489 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0261E-005 |
490 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9985E-005 |
491 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6748E-005 |
492 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9026E-005 |
493 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3996E-005 |
494 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2857E-005 |
495 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9925E-005 |
496 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2891E-005 |
497 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8837E-005 |
498 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0862E-005 |
499 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5396E-005 |
500 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9943E-005 |
501 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5325E-005 |
502 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3655E-005 |
503 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6196E-005 |
504 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3211E-005 |
505 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6582E-005 |
506 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1827E-005 |
507 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6827E-005 |
508 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1254E-005 |
509 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4790E-005 |
510 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3851E-005 |
511 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0083E-005 |
512 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2900E-005 |
513 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6147E-005 |
514 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8190E-005 |
515 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3857E-005 |
516 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7314E-005 |
517 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6767E-005 |
518 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1073E-005 |
519 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7154E-005 |
520 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1873E-005 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10005.06040 | 12006.07248 | 0.83610 | 1.00332 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 25.97200 | 7.00497E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 11231.23615 | 13477.48337 | 0.32029 | 0.38434 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90000 | 6.45023E-005 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 29312.71372 | 35175.25646 | 1.90950 | 2.29139 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.99200 | 7.00652E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 37990.96696 | 45589.16035 | 0.91254 | 1.09504 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -41.90000 | 6.45023E-005 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40000 | 7.00714E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 84877.30263 | 101852.76316 | 2.10665 | 2.52797 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14474.02 | 1.00332 | 1.00332 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 16345.14 | 0.38434 | 0.38434 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 40322.30 | 2.29139 | 2.29139 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 60950.46 | 1.09504 | 1.09504 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00332 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.29139 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.52797 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 2.52797 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 101852.76543 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 101852.76316 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00332 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00332 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00332 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00332 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00332 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.00332 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.29139 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.29139 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.29139 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.29139 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.29139 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.29139 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.00332 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.29139 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00332 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00332 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1110.82918 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00332 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00332 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00332 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00332 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00332 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50166 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.00332 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16608.43000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8304.25426 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16608.43000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16608.43000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30315.79775 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 30315.79775 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.29139 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.29139 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2451.90063 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.29139 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.29139 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.29139 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.29139 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.29139 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.14570 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.29139 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 42280.07000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 20949.22657 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 42280.07000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80083 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80083 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42280.07000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 95780.97015 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 95780.97015 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 15829.9 | 11.75 | 11.07 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 40501.3 | 11.50 | 10.83 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.4116032197 | 0.3879753092 | Pass | Pass | 1.6549184137 | 4.2058933731 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.8104710106 | 0.7899945155 | Pass | Pass | 0.7159217857 | 0.7002023287 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.5507245024E-005 | 2.3748664142E-005 | Pass | Pass | 3.2791660509E-002 | 3.3681235624E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4997.85 | 665.37 | 0.00 | 158.01 | 344.35 | 6165.62 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.102 | 0.104 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.043 | 0.043 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.165 | 0.168 | 1393.41 | 1368.14 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.040 | 0.040 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.165 | 0.168 | 3204.84 | 3133.49 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.2921_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.659 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.2921_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.659 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.2921_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.659 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.2921_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.659 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_17 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_16 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_15 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.45 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.456 | 0.451 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.453 | 0.451 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 114.28 | 3.860 | 0.455 | 0.451 | |||||||||||||||||
North Total or Average | 6.51 | 1.659 | 0.451 | 0.452 | |||||||||||||||||
Non-North Total or Average | 107.77 | 3.993 | 0.455 | 0.451 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_17 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_16 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_15 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R8C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R3C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R4C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R5C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R6C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R7C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R4_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R6_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R7_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R8_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R3_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R5_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R4_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R7_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R6_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R5_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R3_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R8_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 8.6485 | 236.88 | 2048.66 | LightsWired | LTG_SCH_OFFICE | 51.24 | 168.00 | 50.44 | 0.0000 | Y | 19.40 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 12.8090 | 1393.41 | 17848.24 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 50.64 | 0.0000 | Y | 169.68 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 5.4896 | 3204.84 | 17593.27 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 41.93 | 0.0000 | Y | 138.46 |
Interior Lighting Total | 7.7537 | 4835.13 | 37490.17 | 327.54 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17848.24 | 6603.85 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17848.24 | 6603.85 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17593.27 | 6509.51 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17593.27 | 6509.51 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6986.42 | AstronomicalClock | - | 83.06 | 83.06 | 108.93 | |
Exterior Lighting Total | 6986.42 | 108.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16608.43 | 13297.71 | 3310.72 | 0.80 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 42280.07 | 33859.15 | 8420.92 | 0.80 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 15829.9 | 11.75 | 11.07 | ||||
PSZ-FINE STORAGE COOLING COIL | 40501.3 | 11.50 | 10.83 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 101852.77 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 30315.80 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 95780.97 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.53 | 234.88 | 92.91 | 1.00 | 3.44 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1110.83 | 1107.16 | 1.00 | 1.40 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.29 | 2451.90 | 1070.05 | 1.00 | 1.30 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10005.06 | 12006.07 | 50.68 | 0.836 | 1.003 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00826 | 25.97 | 0.00700 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 29312.71 | 35175.26 | 25.24 | 1.909 | 2.291 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.70 | 26.70 | 0.00825 | 26.99 | 0.00701 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 0.00 | 29.61 | 0.00722 | 27.40 | 0.00701 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11231.24 | 13477.48 | 56.90 | 0.320 | 0.384 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00828 | -41.90 | 0.00006 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 37990.97 | 45589.16 | 32.72 | 0.913 | 1.095 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00777 | -41.90 | 0.00006 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 84877.30 | 101852.76 | 31.78 | 2.107 | 2.528 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00736 | -41.90 | 0.00006 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.00 | 1.00 | 0.38 | 0.38 | 1.0033 | 1.0033 | 1.0033 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.29 | 2.29 | 1.10 | 1.10 | 2.2914 | 2.2914 | 2.2914 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 101852.765 | 101852.765 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 101852.77 | 101852.77 | 2.527975 | 10.00 | 9.58 | 0.00736457 | 43.33 | 21.96 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 10.00 | 0.00736457 | 95.0470 | 101852.76 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 16608.430 | 13297.706 | 1.003320 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 16608.43 | 16234.46 | 1.003320 | 25.03 | 16.28 | 0.00813429 | 12.00 | 11.12 | 0.00800000 | 25.97 | 0.00700497 | 15.63 | 10.1946 | 23.90 | 0.00826249 | 44.0687 | 10005.06 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 30315.798 | 30315.798 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 30315.80 | 30315.80 | 1.003315 | 14.63 | 11.66 | 0.00744547 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 10.1947 | 21.10 | 0.00828335 | 52.3672 | 11231.24 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 42280.070 | 33859.148 | 2.291390 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 42280.07 | 42177.71 | 2.291390 | 27.68 | 17.10 | 0.00801669 | 12.00 | 11.12 | 0.00800000 | 27.20 | 0.00700683 | 16.07 | 18.5351 | 26.70 | 0.00824681 | 37.2378 | 29275.50 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 95780.970 | 95780.970 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 95780.97 | 95780.97 | 2.291395 | 4.91 | 4.91 | 0.00633814 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 18.5351 | 15.56 | 0.00776553 | 69.5698 | 37990.97 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 101852.765 | 101852.765 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 2.527975 | 2.99676059 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 101852.77 | 101852.77 | 1.0000 | 2.99676059 | 2.527975 | 10.00 | 9.58 | 0.00736457 | 28603.0 | 43.33 | 21.96 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 101852.77 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 10.00 | 0.00736457 | 10.00 | 0.00736457 | 95.0470 | 101852.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16608.430 | 13297.706 | 1.003320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9612 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.003315 | 1.18936926 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 16608.43 | 16234.46 | 1.0000 | 1.18937495 | 1.003320 | 25.03 | 16.28 | 0.00813429 | 45869.3 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16608.43 | 25.97 | 0.00700497 | 15.63 | 0.10228463 | 10.1946 | 23.90 | 0.00826249 | 23.90 | 0.00826249 | 44.0687 | 10005.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30315.798 | 30315.798 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.003315 | 1.18936926 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 30315.80 | 30315.80 | 1.0000 | 1.18936926 | 1.003315 | 14.63 | 11.66 | 0.00744547 | 33528.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30315.80 | -41.90 | 0.00006450 | -41.90 | 0.10228463 | 10.1947 | 21.05 | 0.00828335 | 21.10 | 0.00828335 | 52.3672 | 11231.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 42280.070 | 33859.148 | 2.291390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7426 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.291395 | 2.71630930 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 42280.07 | 42177.71 | 1.0000 | 2.71630374 | 2.291390 | 27.68 | 17.10 | 0.00801669 | 48272.3 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42280.07 | 27.20 | 0.00700683 | 16.07 | 0.42471127 | 18.5351 | 26.70 | 0.00824681 | 26.70 | 0.00824681 | 37.2378 | 29275.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 95780.970 | 95780.970 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.291395 | 2.71630930 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 95780.97 | 95780.97 | 1.0000 | 2.71630930 | 2.291395 | 4.91 | 4.91 | 0.00633814 | 20842.0 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 95780.97 | -41.90 | 0.00006450 | -41.90 | 0.42471127 | 18.5351 | 15.56 | 0.00776553 | 15.56 | 0.00776553 | 69.5698 | 37990.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.00 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.29 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2690.33 | 2985.67 | 2348.00 |
ZONE2 FINE STORAGE | 3127.67 | 2904.83 | 2479.83 |
ZONE3 BULK STORAGE | 3055.67 | 3331.17 | 2841.67 |
Facility | 3516.50 | 3363.50 | 2873.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 166.83 | 0.00 | 51.00 | 0.00 |
ZONE2 FINE STORAGE | 672.00 | 0.83 | 29.83 | 0.00 |
ZONE3 BULK STORAGE | 134.00 | 0.00 | 43.17 | 0.00 |
Facility | 879.00 | 0.83 | 106.83 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.620 | 0.405 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.516 | 0.147 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 0.000 | 0.087 | 0.000 | 0.033 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.29 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.04 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2228782.45 | 0.00 | 2228782.45 | 1971242.25 | 4200024.70 | 3225648.14 | 5722.08 | 2264.61 | 773.30 | 0.00 |
ZONE2 FINE STORAGE | 5487401.16 | 0.00 | 5487401.16 | 4361427.52 | 9848828.68 | 13393694.68 | 5726.21 | 2696.17 | 337.63 | 3.00 |
ZONE3 BULK STORAGE | 0.00 | 10266576.17 | 10266576.17 | 24470699.40 | 34737275.57 | 30805497.77 | 8651.17 | 10.50 | 98.33 | 4375.33 |
Total Facility | 7716183.61 | 10266576.17 | 17982759.78 | 30803369.17 | 48786128.95 | 47424840.58 | 8717.83 | 2754.74 | 913.04 | 4375.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1703 | 0.0000 | 0.1703 | 0.1119 | 0.2821 | 0.1023 | 598.08 | 2264.61 | 773.30 |
ZONE2 FINE STORAGE | 0.4179 | 0.0000 | 0.4179 | 0.1192 | 0.5371 | 0.4247 | 605.21 | 2696.17 | 334.63 |
ZONE3 BULK STORAGE | 0.0000 | 0.3240 | 0.3240 | 0.8584 | 1.1824 | 0.9768 | 3593.83 | 3.50 | 38.67 |
Total Facility | 0.5882 | 0.3240 | 0.9122 | 1.0895 | 2.0017 | 1.5038 | 3593.83 | 2747.74 | 850.37 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3132032.90 | 0.00 | 3132032.90 | 3225648.14 | 5721.58 | 0.00 | 3038.42 | 0.00 |
PSZ-FINE STORAGE | 7711260.04 | 0.00 | 7711260.04 | 13393694.68 | 5723.96 | 0.00 | 3036.04 | 3.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2393 | 0.0000 | 0.2393 | 0.1023 | 597.58 | 0.00 | 3038.42 |
PSZ-FINE STORAGE | 0.5873 | 0.0000 | 0.5873 | 0.4247 | 602.96 | 0.00 | 3033.04 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2575.58 | 464.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2807.00 | 236.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2458 | 0.5107 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6610 | 1.1975 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 69 | 69 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 444 |
Defaulted Fields | 429 |
Fields with Defaults | 1213 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 147 |
Autocalculatable Fields | 244 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 657.98 | 2265.47 | 23-APR-14:00 | 54943.40 | 05-JAN-15:40 |
Electricity:Building | 466.83 | 1782.47 | 23-APR-14:00 | 41466.67 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 51.34 | 860.99 | 01-JAN-00:10 | 3141.26 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 466.83 | 1782.47 | 23-APR-14:00 | 41466.67 | 02-JAN-09:10 |
InteriorLights:Electricity | 327.54 | 1208.72 | 23-APR-14:00 | 31354.05 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 19.40 | 287.24 | 01-JAN-00:10 | 1228.76 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 327.54 | 1208.72 | 23-APR-14:00 | 31354.05 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 327.54 | 1208.72 | 23-APR-14:00 | 31354.05 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 19.40 | 287.24 | 01-JAN-00:10 | 1228.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 327.54 | 1208.72 | 23-APR-14:00 | 31354.05 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 169.68 | 464.05 | 23-APR-14:00 | 15171.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 169.68 | 464.05 | 23-APR-14:00 | 15171.01 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 169.68 | 464.05 | 23-APR-14:00 | 15171.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 245.81 | 457.42 | 05-MAR-11:00 | 23154.40 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 138.46 | 457.42 | 05-MAR-11:00 | 14954.28 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 138.46 | 457.42 | 05-MAR-11:00 | 14954.28 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 51.81 | 0.00 | 18-MAR-17:10 | 3797.61 | 04-JAN-15:40 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 657.98 | 2265.47 | 23-APR-14:00 | 54943.40 | 05-JAN-15:40 |
ElectricityPurchased:Plant | 657.98 | 2265.47 | 23-APR-14:00 | 54943.40 | 05-JAN-15:40 |
Cogeneration:ElectricityPurchased | 657.98 | 2265.47 | 23-APR-14:00 | 54943.40 | 05-JAN-15:40 |
General:Cogeneration:ElectricityPurchased | 657.98 | 2265.47 | 23-APR-14:00 | 54943.40 | 05-JAN-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 657.98 | 2265.47 | 23-APR-14:00 | 54943.40 | 05-JAN-15:40 |
ElectricityNet:Plant | 657.98 | 2265.47 | 23-APR-14:00 | 54943.40 | 05-JAN-15:40 |
Cogeneration:ElectricityNet | 657.98 | 2265.47 | 23-APR-14:00 | 54943.40 | 05-JAN-15:40 |
General:Cogeneration:ElectricityNet | 657.98 | 2265.47 | 23-APR-14:00 | 54943.40 | 05-JAN-15:40 |
Electricity:HVAC | 53.81 | 0.00 | 18-MAR-17:10 | 10776.34 | 29-JUL-16:00 |
General:Fans:Electricity | 51.81 | 0.00 | 18-MAR-17:10 | 3797.61 | 04-JAN-15:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1.99 | 0.00 | 01-JAN-00:10 | 7213.61 | 29-JUL-16:00 |
General:Cooling:Electricity | 1.99 | 0.00 | 01-JAN-00:10 | 7213.61 | 29-JUL-16:00 |
ExteriorLights:Electricity | 108.93 | 0.00 | 01-JAN-11:20 | 6986.42 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 108.93 | 0.00 | 01-JAN-11:20 | 6986.42 | 01-JAN-00:10 |
Electricity:Plant | 28.42 | 483.00 | 03-JAN-06:20 | 3132.98 | 13-JAN-12:40 |
WaterSystems:Electricity | 28.42 | 483.00 | 03-JAN-06:20 | 3132.98 | 13-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 28.42 | 483.00 | 03-JAN-06:20 | 3132.98 | 13-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1410.31 | 0.00 | 18-MAR-17:10 | 233314.99 | 28-JAN-17:10 |
NaturalGas:HVAC | 1410.31 | 0.00 | 18-MAR-17:10 | 233314.99 | 28-JAN-17:10 |
Heating:NaturalGas | 1410.31 | 0.00 | 18-MAR-17:10 | 233314.99 | 28-JAN-17:10 |
General:Heating:NaturalGas | 1410.31 | 0.00 | 18-MAR-17:10 | 233314.99 | 28-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2124.52 | 0.00 | 18-MAR-17:10 | 359402.84 | 29-JAN-00:10 |
EnergyTransfer:Building | 1040.21 | 0.00 | 18-MAR-17:10 | 180274.93 | 29-JAN-00:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 86.73 | 0.00 | 01-JAN-00:40 | 31493.97 | 27-FEB-07:20 |
Heating:EnergyTransfer | 1006.19 | 0.00 | 18-MAR-17:10 | 180274.93 | 29-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 75.44 | 0.00 | 01-JAN-00:40 | 31493.97 | 27-FEB-07:20 |
General:Heating:EnergyTransfer | 1006.19 | 0.00 | 18-MAR-17:10 | 180274.93 | 29-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 75.44 | 0.00 | 01-JAN-00:40 | 31493.97 | 27-FEB-07:20 |
Cooling:EnergyTransfer | 34.01 | 0.00 | 01-JAN-00:10 | 21925.72 | 23-JUN-18:20 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 11.29 | 0.00 | 01-JAN-00:10 | 7798.51 | 22-JUL-07:10 |
General:Cooling:EnergyTransfer | 34.01 | 0.00 | 01-JAN-00:10 | 21925.72 | 23-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 11.29 | 0.00 | 01-JAN-00:10 | 7798.51 | 22-JUL-07:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 233.25 | 0.00 | 01-JAN-00:40 | 70316.51 | 29-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 210.52 | 0.00 | 01-JAN-00:40 | 70316.51 | 29-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 210.52 | 0.00 | 01-JAN-00:40 | 70316.51 | 29-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 22.72 | 0.00 | 01-JAN-00:10 | 21925.72 | 23-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 22.72 | 0.00 | 01-JAN-00:10 | 21925.72 | 23-JUN-18:20 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 720.23 | 0.00 | 21-JAN-13:10 | 102858.65 | 28-JAN-09:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 720.23 | 0.00 | 21-JAN-13:10 | 102858.65 | 28-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 720.23 | 0.00 | 21-JAN-13:10 | 102858.65 | 28-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1084.31 | 0.00 | 18-MAR-17:10 | 180300.19 | 28-JAN-17:10 |
HeatingCoils:EnergyTransfer | 1076.13 | 0.00 | 18-MAR-17:10 | 180300.19 | 28-JAN-17:10 |
CoolingCoils:EnergyTransfer | 8.18 | 0.00 | 01-JAN-00:10 | 27524.55 | 29-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 75.441 | -11.290 | 0.000 | 0.000 | 10.272 | 19.398 | 31.946 | 8.818 | 0.000 | 0.051 | 0.000 | 0.000 | -12.994 | 0.000 | -50.018 | -71.624 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 210.521 | -22.725 | 0.000 | 0.000 | 27.231 | 169.679 | 0.000 | 22.490 | 0.000 | 0.022 | 0.001 | 0.000 | -46.345 | 0.000 | -86.629 | -274.244 |
ZONE3 BULK STORAGE | 720.229 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 72.933 | 138.464 | 107.344 | 229.805 | 0.000 | 1.373 | 0.005 | 0.000 | -549.011 | 0.000 | -504.810 | -216.325 |
Total Facility | 720.229 | 0.000 | 285.962 | -34.015 | 0.000 | 0.000 | 110.436 | 327.541 | 139.290 | 261.112 | 0.000 | 1.447 | 0.007 | 0.000 | -608.351 | 0.000 | -641.457 | -562.193 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-JUN-07:02 | 0.00 | 0.00 | 0.00 | -23178.21 | 0.00 | 0.00 | 801.53 | 1228.76 | 1912.50 | 314.59 | 0.00 | 0.00 | 18920.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-12:01 | 0.00 | 0.00 | 0.00 | -44420.23 | 0.00 | 0.00 | 0.00 | 1124.44 | 0.00 | 7205.99 | 0.00 | 0.00 | 36151.43 | 0.00 | -0.00 | 0.00 | -61.63 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-JUL-12:01 | 0.00 | 0.00 | 0.00 | -44420.23 | 0.00 | 0.00 | 0.00 | 1869.11 | 573.75 | 111304.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -416.28 | -68910.55 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-FEB-06:31 | 0.00 | 0.00 | 32309.51 | 0.00 | 0.00 | 0.00 | 154.28 | 367.04 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1046.46 | 0.00 | -4958.36 | -27399.75 |
ZONE2 FINE STORAGE | 12-JAN-00:41 | 0.00 | 0.00 | 99394.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4352.81 | 0.00 | -8495.87 | -88330.77 |
ZONE3 BULK STORAGE | 28-JAN-09:10 | 102855.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8539.94 | 14954.28 | 8200.12 | 0.00 | 0.00 | 0.00 | 18110.64 | 0.00 | -23396.35 | 0.00 | -129264.46 | 0.00 |
Total Facility | 28-JAN-06:01 | 102125.81 | 0.00 | 129616.71 | 0.00 | 0.00 | 0.00 | 1461.75 | 3911.19 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41390.49 | 0.00 | -105018.75 | -93329.99 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0033 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0033 | 0.1019 | 1.0000 | Not calculated | 0.1023 | 0.1019 | ||
PSZ-FINE STORAGE | 2.2914 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.2914 | 0.1854 | 1.0000 | Not calculated | 0.4247 | 0.1854 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0033 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0033 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1019 | ||
PSZ-FINE STORAGE | 2.2914 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.2914 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1854 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0033 | 1.0033 | 1.0033 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2914 | 2.2914 | 2.2914 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0033 | 1.0033 | 1.0033 | 1.0033 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.2914 | 2.2914 | 2.2914 | 2.2914 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0033 | 1.0033 | 1.0033 | No | 0.1023 | 0.2661 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2914 | 2.2914 | 2.2914 | No | 0.4247 | 0.3878 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0033 | 1.0033 | 1.0033 | 1.0033 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.2914 | 2.2914 | 2.2914 | 2.2914 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 106.83 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 106.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1410.31 | 233314.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1.99 | 7213.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 327.54 | 31354.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 108.93 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 51.81 | 3797.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 28.42 | 3132.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 657.98 |
Natural Gas | 0.00 | 1410.31 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 2068.29 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 67.74 |
Space Heating | 0.00 |
Space Cooling | 0.41 |
Fans (All) | 10.72 |
Service Water Heating | 5.88 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 136.08 |
Subtotal | 136.08 |
Natural Gas [MJ/m2] | |
Space Heating | 291.68 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 291.68 |
Subtotal | 291.68 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.84 |
Space Heating | 68.19 |
Space Cooling | 0.10 |
Fans (All) | 2.51 |
Service Water Heating | 1.37 |
Receptacle Equipment | 6.73 |
Miscellaneous | 5.27 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2672. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8686.67 | 73.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8684.50 | 75.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8748.33 | 11.67 | 0.00 | 0.00 | 0.00 |
Min | 8684.50 | 11.67 | 0.00 | 0.00 | 0.00 |
Max | 8748.33 | 75.50 | 0.00 | 0.00 | 0.00 |
Average | 8706.50 | 53.50 | 0.00 | 0.00 | 0.00 |
Sum | 26119.50 | 160.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 81051.00 | 1668.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 190546.83 | 646.17 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 190546.83 | 1668.00 | 0.00 | 0.00 | 0.00 |
Average | 101541.61 | 771.39 | 0.00 | 0.00 | 0.00 |
Sum | 304624.83 | 2314.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8683.17 | 76.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8602.00 | 158.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8739.00 | 21.00 | 0.00 | 0.00 | 0.00 |
Min | 8602.00 | 21.00 | 0.00 | 0.00 | 0.00 |
Max | 8739.00 | 158.00 | 0.00 | 0.00 | 0.00 |
Average | 8674.72 | 85.28 | 0.00 | 0.00 | 0.00 |
Sum | 26024.17 | 255.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 79543.00 | 3176.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 190179.33 | 1013.67 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 190179.33 | 3176.00 | 0.00 | 0.00 | 0.00 |
Average | 100916.44 | 1396.56 | 0.00 | 0.00 | 0.00 |
Sum | 302749.33 | 4189.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:37
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 27573.00 | 0.00 |
Sum | 0.00 | 191193.00 | 82719.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 233323.11 | 2187.82 | 11-JAN-13:05 | -33.3 | -33.4 | 0.492372E+09 | 603.25 | 07-JAN-15:50 | -33.3 | -33.4 |
February | 76104.19 | 380.52 | 11-FEB-08:07 | -6.0 | -6.5 | 0.453626E+09 | 603.25 | 02-FEB-15:00 | -6.0 | -6.5 |
March | 363238.43 | 1243.79 | 18-MAR-07:07 | -1.7 | -3.2 | 0.532882E+09 | 603.25 | 03-MAR-14:00 | -1.7 | -3.2 |
April | 31163490.00 | 1718.84 | 19-APR-07:07 | -0.7 | -2.6 | 0.500339E+09 | 768.40 | 22-APR-15:00 | 15.00 | 6.60 |
May | 0.525205E+09 | 3291.31 | 13-MAY-15:50 | 20.00 | 9.32 | 0.594122E+09 | 768.97 | 12-MAY-12:09 | 20.00 | 9.32 |
June | 0.313739E+10 | 23179.01 | 17-JUN-07:02 | 10.18 | 8.41 | 0.656460E+09 | 879.39 | 17-JUN-07:10 | 10.18 | 8.41 |
July | 0.411084E+10 | 19624.51 | 01-JUL-07:02 | 13.22 | 11.22 | 0.635702E+09 | 879.39 | 29-JUL-07:10 | 16.88 | 12.95 |
August | 0.304811E+10 | 22798.71 | 26-AUG-07:02 | 9.27 | 8.27 | 0.676146E+09 | 879.39 | 26-AUG-07:10 | 9.27 | 8.27 |
September | 0.422850E+09 | 3063.98 | 02-SEP-15:00 | 16.70 | 10.81 | 0.539133E+09 | 768.96 | 12-SEP-15:30 | 14.40 | 8.32 |
October | 13220521.57 | 1950.29 | 14-OCT-07:07 | -4.6 | -6.2 | 0.493732E+09 | 629.85 | 03-OCT-15:09 | -4.6 | -6.2 |
November | 226183.46 | 1031.50 | 18-NOV-08:07 | -11.6 | -12.0 | 0.473696E+09 | 603.25 | 04-NOV-13:30 | -11.6 | -12.0 |
December | 313097.69 | 1972.58 | 15-DEC-13:05 | -32.7 | -32.9 | 0.493087E+09 | 603.25 | 20-DEC-13:50 | -19.0 | -19.3 |
Annual Sum or Average | 0.112900E+11 | 0.654130E+10 | ||||||||
Minimum of Months | 76104.19 | 380.52 | -33.3 | -33.4 | 0.453626E+09 | 603.25 | -33.3 | -33.4 | ||
Maximum of Months | 0.411084E+10 | 23179.01 | 20.00 | 11.22 | 0.676146E+09 | 879.39 | 20.00 | 12.95 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10617108.99 | 7591.45 | 19-JAN-15:15 | -5.7 | -6.5 | 0.649150E+09 | 787.42 | 11-JAN-11:39 | -5.7 | -6.5 |
February | 0.369594E+09 | 5527.31 | 09-FEB-14:00 | -0.6 | -1.6 | 0.597230E+09 | 787.42 | 27-FEB-13:09 | -29.8 | -30.0 |
March | 0.114560E+10 | 7684.21 | 07-MAR-15:15 | -5.9 | -6.8 | 0.705924E+09 | 997.62 | 22-MAR-15:09 | 5.60 | 2.29 |
April | 0.220842E+10 | 6958.65 | 08-APR-14:40 | -3.0 | -5.9 | 0.776985E+09 | 1502.65 | 22-APR-13:00 | 15.60 | 7.03 |
May | 0.174657E+10 | 6321.24 | 27-MAY-08:15 | 0.77 | -0.4 | 0.124581E+10 | 2073.80 | 12-MAY-13:50 | 0.77 | -0.4 |
June | 0.294704E+10 | 44302.59 | 22-JUN-17:41 | 23.40 | 12.49 | 0.176639E+10 | 2246.86 | 30-JUN-12:50 | 26.52 | 17.31 |
July | 0.506397E+10 | 44421.55 | 23-JUL-12:01 | 24.08 | 15.73 | 0.180514E+10 | 2246.90 | 22-JUL-10:39 | 24.08 | 15.73 |
August | 0.391040E+10 | 43697.06 | 02-AUG-18:35 | 22.40 | 14.49 | 0.179293E+10 | 2246.82 | 25-AUG-14:39 | 23.13 | 15.39 |
September | 0.328582E+10 | 7161.54 | 30-SEP-10:00 | -3.3 | -4.0 | 0.102964E+10 | 1951.18 | 02-SEP-15:09 | -3.3 | -4.0 |
October | 0.197495E+10 | 11227.46 | 27-OCT-12:03 | -13.0 | -13.9 | 0.692983E+09 | 1221.55 | 03-OCT-15:09 | -13.0 | -13.9 |
November | 61964786.69 | 11699.35 | 03-NOV-12:13 | -14.0 | -14.4 | 0.623251E+09 | 787.42 | 04-NOV-13:30 | -9.2 | -10.7 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.649149E+09 | 787.42 | 12-DEC-11:30 | -22.2 | -22.5 |
Annual Sum or Average | 0.227249E+11 | 0.123346E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.597230E+09 | 787.42 | -29.8 | -30.0 | ||
Maximum of Months | 0.506397E+10 | 44421.55 | 24.08 | 15.73 | 0.180514E+10 | 2246.90 | 26.52 | 17.31 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.621448E+09 | 790.35 | 21-JAN-14:09 | -5.6 | -6.1 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.585561E+09 | 832.44 | 11-FEB-16:10 | -0.2 | -2.0 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.2 | 0.708060E+09 | 1072.07 | 22-MAR-15:39 | 5.60 | 2.48 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.3 | 0.807926E+09 | 1590.83 | 22-APR-15:00 | 15.00 | 6.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 | 0.169227E+10 | 2741.65 | 13-MAY-15:50 | 20.00 | 9.32 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 | 0.299951E+10 | 4808.70 | 30-JUN-15:09 | 27.38 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.363206E+10 | 5520.73 | 29-JUL-15:00 | 30.00 | 18.34 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 | 0.340133E+10 | 5306.53 | 04-AUG-15:09 | 22.70 | 14.61 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.164230E+10 | 3240.61 | 02-SEP-15:30 | 16.70 | 10.62 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 | 0.715039E+09 | 1319.22 | 03-OCT-15:30 | 12.25 | 6.65 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.618578E+09 | 804.95 | 02-NOV-15:09 | -8.9 | -9.5 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.643683E+09 | 780.37 | 27-DEC-13:09 | -23.4 | -23.6 |
Annual Sum or Average | 0.00 | 0.180678E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.585561E+09 | 780.37 | -23.4 | -23.6 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.363206E+10 | 5520.73 | 30.00 | 18.34 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139098E+11 | 32276.74 | 30-JAN-06:31 | -25.6 |
February | 0.115006E+11 | 32309.43 | 24-FEB-06:31 | -25.6 |
March | 0.110967E+11 | 31883.50 | 31-MAR-06:02 | -25.6 |
April | 0.483890E+10 | 30930.78 | 05-APR-05:52 | -13.3 |
May | 0.729762E+09 | 30380.37 | 04-MAY-06:01 | 4.18 |
June | 0.125691E+09 | 8811.49 | 02-JUN-07:03 | 9.50 |
July | 92632769.86 | 1782.17 | 17-JUL-06:15 | 8.67 |
August | 0.165488E+09 | 10045.58 | 31-AUG-07:03 | -0.1 |
September | 0.140678E+10 | 30342.03 | 28-SEP-06:02 | -2.8 |
October | 0.661923E+10 | 31150.65 | 27-OCT-06:12 | -18.5 |
November | 0.114378E+11 | 31254.73 | 29-NOV-07:13 | -28.9 |
December | 0.135191E+11 | 31530.24 | 22-DEC-06:32 | -25.5 |
Annual Sum or Average | 0.754425E+11 | |||
Minimum of Months | 92632769.86 | 1782.17 | -28.9 | |
Maximum of Months | 0.139098E+11 | 32309.43 | 9.50 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.421974E+11 | 99394.43 | 12-JAN-00:41 | -36.1 |
February | 0.347854E+11 | 99331.88 | 23-FEB-21:21 | -23.1 |
March | 0.282490E+11 | 98761.42 | 14-MAR-05:01 | -18.2 |
April | 0.119531E+11 | 98311.49 | 02-APR-20:22 | -12.8 |
May | 0.312334E+09 | 18735.78 | 28-MAY-03:10 | 0.78 |
June | 0.182039E+09 | 2461.17 | 06-JUN-07:00 | 10.60 |
July | 0.132127E+09 | 2465.53 | 20-JUL-07:00 | 14.40 |
August | 0.177982E+09 | 2446.31 | 19-AUG-07:00 | 8.90 |
September | 0.118755E+10 | 51522.39 | 30-SEP-04:43 | -4.3 |
October | 0.167446E+11 | 97200.85 | 30-OCT-04:22 | -14.4 |
November | 0.325922E+11 | 98242.61 | 10-NOV-02:62 | -19.6 |
December | 0.420075E+11 | 98386.79 | 15-DEC-00:42 | -30.5 |
Annual Sum or Average | 0.210521E+12 | |||
Minimum of Months | 0.132127E+09 | 2446.31 | -36.1 | |
Maximum of Months | 0.421974E+11 | 99394.43 | 14.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142285E+12 | 102858.65 | 28-JAN-09:10 | -20.1 |
February | 0.118309E+12 | 102760.76 | 25-FEB-12:00 | -23.9 |
March | 0.113605E+12 | 102199.26 | 02-MAR-04:57 | -26.7 |
April | 0.491393E+11 | 102278.57 | 02-APR-20:03 | -12.4 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 52560986.05 | 8947.35 | 30-SEP-05:00 | -4.4 |
October | 0.612522E+11 | 93420.36 | 27-OCT-04:00 | -17.8 |
November | 0.956456E+11 | 98454.25 | 10-NOV-01:52 | -20.0 |
December | 0.139941E+12 | 102404.49 | 22-DEC-14:10 | -23.7 |
Annual Sum or Average | 0.720229E+12 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.142285E+12 | 102858.65 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162246E+10 | 1228.76 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.147976E+10 | 1228.76 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.169071E+10 | 1228.76 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.159765E+10 | 1228.76 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.165659E+10 | 1228.76 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.163177E+10 | 1228.76 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.162246E+10 | 1228.76 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.169071E+10 | 1228.76 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.159765E+10 | 1228.76 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.162246E+10 | 1228.76 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.156352E+10 | 1228.76 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.162246E+10 | 1228.76 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.193982E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.147976E+10 | 1228.76 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.169071E+10 | 1228.76 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.169072E+11 | 15171.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.151900E+11 | 15171.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.156863E+11 | 15171.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.127495E+11 | 15171.01 | 03-APR-08:09 | 0.00 | 0.00 |
May | 0.117701E+11 | 15171.01 | 02-MAY-08:09 | 0.00 | 0.00 |
June | 0.101066E+11 | 15171.01 | 07-JUN-08:09 | 0.00 | 0.00 |
July | 0.106330E+11 | 15171.01 | 11-JUL-08:09 | 0.00 | 0.00 |
August | 0.129010E+11 | 15171.01 | 10-AUG-08:09 | 0.00 | 0.00 |
September | 0.144110E+11 | 15171.01 | 09-SEP-08:09 | 0.00 | 0.00 |
October | 0.161715E+11 | 15171.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.162443E+11 | 15171.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.169084E+11 | 15171.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.169679E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.101066E+11 | 15171.01 | 0.00 | 0.00 | |
Maximum of Months | 0.169084E+11 | 15171.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.166175E+11 | 14954.28 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.139827E+11 | 14954.28 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.121943E+11 | 14954.28 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.855400E+10 | 13194.95 | 01-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.764384E+10 | 11265.56 | 06-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.659287E+10 | 9940.20 | 07-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.698066E+10 | 11265.56 | 29-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.860829E+10 | 13194.95 | 30-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.106877E+11 | 14954.28 | 21-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.142095E+11 | 14954.28 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.157257E+11 | 14954.28 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.166668E+11 | 14954.28 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.138464E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.659287E+10 | 9940.20 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.166668E+11 | 14954.28 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700760E+10 |
February | 0.127628E+10 | 0.147976E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550488E+10 |
March | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641621E+10 |
April | 0.138726E+10 | 0.159765E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415477E+10 |
May | 0.144276E+10 | 0.165659E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241367E+10 |
June | 0.144276E+10 | 0.163177E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15824344.46 | 0.160323E+10 |
July | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29312621.26 | 0.127246E+10 |
August | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6139574.28 | 0.195672E+10 |
September | 0.138726E+10 | 0.159765E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243189E+10 |
October | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470578E+10 |
November | 0.133177E+10 | 0.156352E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580098E+10 |
December | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675017E+10 |
Annual Sum or Average | 0.168137E+11 | 0.193982E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51276540.00 | 0.500184E+11 |
Minimum of Months | 0.127628E+10 | 0.147976E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127246E+10 |
Maximum of Months | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29312621.26 | 0.700760E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.169072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100997E+11 |
February | 0.300332E+10 | 0.151900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835895E+10 |
March | 0.352563E+10 | 0.156863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120535E+11 |
April | 0.326447E+10 | 0.127495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108926E+11 |
May | 0.339505E+10 | 0.117701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636468E+10 |
June | 0.339505E+10 | 0.101066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1508814.31 | 0.479654E+10 |
July | 0.326447E+10 | 0.106330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20802301.97 | 0.390464E+10 |
August | 0.352563E+10 | 0.129010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86736.85 | 0.498093E+10 |
September | 0.326447E+10 | 0.144110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426004E+10 |
October | 0.326447E+10 | 0.161715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943997E+10 |
November | 0.313390E+10 | 0.162443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377984E+10 |
December | 0.326447E+10 | 0.169084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769729E+10 |
Annual Sum or Average | 0.395654E+11 | 0.169679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22397853.13 | 0.866286E+11 |
Minimum of Months | 0.300332E+10 | 0.101066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377984E+10 |
Maximum of Months | 0.352563E+10 | 0.169084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20802301.97 | 0.120535E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.166175E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456001E+11 |
February | 0.690763E+10 | 0.139827E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373814E+11 |
March | 0.810895E+10 | 0.121943E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520502E+11 |
April | 0.750829E+10 | 0.855400E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46144224.54 | 0.380576E+11 |
May | 0.780862E+10 | 0.764384E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500270E+09 | 0.184950E+11 |
June | 0.780862E+10 | 0.659287E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206960E+09 | 0.151901E+11 |
July | 0.750829E+10 | 0.698066E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97212871.24 | 0.166870E+11 |
August | 0.810895E+10 | 0.860829E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99284379.57 | 0.219913E+11 |
September | 0.750829E+10 | 0.106877E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176003E+11 |
October | 0.750829E+10 | 0.142095E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19928343.93 | 0.373673E+11 |
November | 0.720796E+10 | 0.157257E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171385E+11 |
December | 0.750829E+10 | 0.166668E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374139E+11 |
Annual Sum or Average | 0.910005E+11 | 0.138464E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969800E+09 | 0.354973E+12 |
Minimum of Months | 0.690763E+10 | 0.659287E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151901E+11 |
Maximum of Months | 0.810895E+10 | 0.166668E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500270E+09 | 0.520502E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1228.76 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 24792.00 | 12-JAN-12:02 |
February | 1680.92 | 01-FEB-08:09 | 1228.76 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 23660.59 | 27-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1228.76 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 21089.79 | 01-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 1228.76 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 18432.11 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1228.76 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 7748.73 | 16-MAY-07:00 |
June | 1680.92 | 01-JUN-07:10 | 1228.76 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 827.98 | 29-JUN-16:10 | 5473.99 | 07-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1228.76 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2450.40 | 21-JUL-16:10 | 6111.35 | 17-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1228.76 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 719.91 | 11-AUG-16:10 | 8983.17 | 31-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1228.76 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 10517.86 | 29-SEP-07:00 |
October | 1680.92 | 02-OCT-07:10 | 1228.76 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 17845.96 | 31-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1228.76 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 21952.34 | 29-NOV-08:00 |
December | 1680.92 | 01-DEC-08:09 | 1228.76 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 23514.27 | 15-DEC-12:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5473.99 | |||||
Maximum of Months | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2450.40 | 24792.00 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 15171.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 34932.16 | 28-JAN-17:00 |
February | 3955.50 | 01-FEB-08:09 | 15171.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 21109.00 | 23-FEB-17:00 |
March | 3955.50 | 01-MAR-08:09 | 15171.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 16048.16 | 25-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 15171.01 | 03-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 18088.89 | 01-APR-18:52 |
May | 3955.50 | 01-MAY-07:10 | 15171.01 | 02-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 10180.39 | 16-MAY-07:00 |
June | 3955.50 | 01-JUN-07:10 | 15171.01 | 07-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.49 | 30-JUN-15:10 | 9183.62 | 24-JUN-21:00 |
July | 3955.50 | 01-JUL-07:10 | 15171.01 | 11-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2764.01 | 21-JUL-16:00 | 5927.84 | 04-JUL-17:00 |
August | 3955.50 | 01-AUG-07:10 | 15171.01 | 10-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.52 | 11-AUG-17:40 | 9068.91 | 29-AUG-20:00 |
September | 3955.50 | 01-SEP-07:10 | 15171.01 | 09-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5221.73 | 21-SEP-15:10 |
October | 3955.50 | 02-OCT-07:10 | 15171.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 11980.71 | 27-OCT-06:02 |
November | 3955.50 | 01-NOV-07:10 | 15171.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 11730.60 | 03-NOV-20:00 |
December | 3955.50 | 01-DEC-08:09 | 15171.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 13620.66 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5221.73 | ||||
Maximum of Months | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2764.01 | 34932.16 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 14954.28 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 129291.65 | 28-JAN-15:00 |
February | 9097.65 | 01-FEB-08:09 | 14954.28 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 89775.21 | 25-FEB-12:00 |
March | 9097.65 | 01-MAR-08:09 | 14954.28 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 68307.77 | 25-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 13194.95 | 01-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2063.15 | 22-APR-14:00 | 65116.81 | 01-APR-18:52 |
May | 9097.65 | 01-MAY-07:10 | 11265.56 | 06-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8936.80 | 30-MAY-18:00 | 44954.97 | 27-MAY-11:00 |
June | 9097.65 | 01-JUN-07:10 | 9940.20 | 07-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6576.44 | 30-JUN-15:00 | 34249.59 | 24-JUN-21:00 |
July | 9097.65 | 01-JUL-07:10 | 11265.56 | 29-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10728.55 | 21-JUL-16:00 | 21616.19 | 04-JUL-17:00 |
August | 9097.65 | 01-AUG-07:10 | 13194.95 | 30-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4784.33 | 23-AUG-18:00 | 41801.34 | 31-AUG-09:00 |
September | 9097.65 | 01-SEP-07:10 | 14954.28 | 21-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 21590.96 | 21-SEP-14:00 |
October | 9097.65 | 02-OCT-07:10 | 14954.28 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2185.24 | 01-OCT-16:30 | 48555.38 | 31-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 14954.28 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 49305.50 | 01-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 14954.28 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 70004.50 | 22-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 9940.20 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21590.96 | |||||
Maximum of Months | 9097.65 | 14954.28 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 10728.55 | 129291.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2187.82 | 11-JAN-13:05 | 10085.53 | 7372.58 | 11475.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3303.41 |
February | 380.52 | 11-FEB-08:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.08 |
March | 1243.79 | 18-MAR-07:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.40 |
April | 1718.84 | 19-APR-07:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1163.36 |
May | 3291.31 | 13-MAY-15:50 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.72 |
June | 23179.01 | 17-JUN-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 19624.51 | 01-JUL-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.32 |
August | 22798.71 | 26-AUG-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.72 |
September | 3063.98 | 02-SEP-15:00 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.14 |
October | 1950.29 | 14-OCT-07:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.50 |
November | 1031.50 | 18-NOV-08:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.74 |
December | 1972.58 | 15-DEC-13:05 | 10085.53 | 7372.58 | 11475.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3825.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 380.52 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23179.01 | 10085.53 | 7372.58 | 11475.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3825.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7591.45 | 19-JAN-15:15 | 7911.00 | 30342.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5527.31 | 09-FEB-14:00 | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 916.65 |
March | 7684.21 | 07-MAR-15:15 | 7911.00 | 26599.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.78 |
April | 6958.65 | 08-APR-14:40 | 3955.50 | 11428.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3017.58 |
May | 6321.24 | 27-MAY-08:15 | 7911.00 | 26599.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3890.08 |
June | 44302.59 | 22-JUN-17:41 | 0.00 | 12101.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1171.91 |
July | 44421.55 | 23-JUL-12:01 | 0.00 | 8995.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.63 |
August | 43697.06 | 02-AUG-18:35 | 0.00 | 3129.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.91 |
September | 7161.54 | 30-SEP-10:00 | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1873.32 |
October | 11227.46 | 27-OCT-12:03 | 11866.50 | 45513.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2685.32 |
November | 11699.35 | 03-NOV-12:13 | 11866.50 | 45513.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 8924.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 3129.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44421.55 | 11866.50 | 45513.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3890.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 10555.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25686.04 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 8796.63 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20189.95 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 8796.63 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10066.39 |
April | 0.00 | 01-APR-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34937.70 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5098.63 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3558.92 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5193.07 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10214.23 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6403.34 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 1759.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10936.81 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20529.07 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 8796.63 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 1759.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 10555.96 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34937.70 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.693212E+11 | 54943.40 | 05-JAN-15:39 | 0.278575E+12 | 233314.99 | 28-JAN-17:10 |
February | 0.594044E+11 | 53981.50 | 04-FEB-09:09 | 0.229130E+12 | 231503.97 | 24-FEB-17:00 |
March | 0.593975E+11 | 50389.95 | 18-MAR-07:10 | 0.211879E+12 | 206677.10 | 16-MAR-07:00 |
April | 0.478599E+11 | 43403.55 | 13-APR-07:10 | 0.886905E+11 | 190478.36 | 02-APR-07:10 |
May | 0.436577E+11 | 43071.21 | 09-MAY-08:20 | 0.109482E+10 | 17922.36 | 03-MAY-06:10 |
June | 0.392439E+11 | 39907.71 | 07-JUN-07:10 | 15849268.72 | 4898.49 | 02-JUN-07:10 |
July | 0.413237E+11 | 43465.79 | 29-JUL-08:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.481067E+11 | 43149.60 | 30-AUG-07:10 | 80002218.22 | 8728.62 | 31-AUG-06:10 |
September | 0.523968E+11 | 46735.99 | 30-SEP-08:09 | 0.411434E+10 | 33715.48 | 30-SEP-05:10 |
October | 0.616148E+11 | 53963.56 | 31-OCT-08:39 | 0.117589E+12 | 168863.37 | 27-OCT-06:10 |
November | 0.652795E+11 | 54794.91 | 30-NOV-15:39 | 0.202455E+12 | 189299.96 | 29-NOV-07:00 |
December | 0.703753E+11 | 54942.87 | 30-DEC-15:39 | 0.276684E+12 | 217789.74 | 01-DEC-17:00 |
Annual Sum or Average | 0.657981E+12 | 0.141031E+13 | ||||
Minimum of Months | 0.392439E+11 | 39907.71 | 0.00 | 0.00 | ||
Maximum of Months | 0.703753E+11 | 54943.40 | 0.278575E+12 | 233314.99 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.351472E+11 | 0.150320E+11 | 0.115358E+11 | 0.00 | 0.517046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243574E+10 | 0.00 |
February | 0.306524E+11 | 0.112467E+11 | 0.105871E+11 | 0.00 | 0.470201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221606E+10 | 0.00 |
March | 0.295713E+11 | 0.981313E+10 | 0.123431E+11 | 0.00 | 0.515695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251301E+10 | 0.00 |
April | 0.229011E+11 | 0.690817E+10 | 0.114862E+11 | 0.00 | 0.417715E+10 | 0.00 | 0.00 | 7.00 | 0.00 | 0.00 | 0.00 | 0.238728E+10 | 0.00 |
May | 0.210705E+11 | 0.451462E+10 | 0.119357E+11 | 0.00 | 0.367204E+10 | 0.00 | 0.00 | 5656224.08 | 0.00 | 0.00 | 0.00 | 0.245909E+10 | 0.00 |
June | 0.183313E+11 | 0.251511E+10 | 0.118862E+11 | 0.00 | 0.367377E+10 | 0.00 | 0.00 | 0.472476E+09 | 0.00 | 0.00 | 0.00 | 0.236509E+10 | 0.00 |
July | 0.192362E+11 | 0.349600E+10 | 0.115358E+11 | 0.00 | 0.355180E+10 | 0.00 | 0.00 | 0.116938E+10 | 0.00 | 0.00 | 0.00 | 0.233459E+10 | 0.00 |
August | 0.232000E+11 | 0.603208E+10 | 0.123357E+11 | 0.00 | 0.381148E+10 | 0.00 | 0.00 | 0.344553E+09 | 0.00 | 0.00 | 0.00 | 0.238292E+10 | 0.00 |
September | 0.266964E+11 | 0.838790E+10 | 0.114788E+11 | 0.00 | 0.356219E+10 | 0.00 | 0.00 | 8.09 | 0.00 | 0.00 | 0.00 | 0.227148E+10 | 0.00 |
October | 0.320034E+11 | 0.113138E+11 | 0.115432E+11 | 0.00 | 0.441196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234241E+10 | 0.00 |
November | 0.335336E+11 | 0.135690E+11 | 0.110862E+11 | 0.00 | 0.479732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229339E+10 | 0.00 |
December | 0.351976E+11 | 0.160967E+11 | 0.115358E+11 | 0.00 | 0.512690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241829E+10 | 0.00 |
Annual Sum or Average | 0.327541E+12 | 0.108925E+12 | 0.139290E+12 | 0.00 | 0.518140E+11 | 0.00 | 0.00 | 0.199207E+10 | 0.00 | 0.00 | 0.00 | 0.284194E+11 | 0.00 |
Minimum of Months | 0.183313E+11 | 0.251511E+10 | 0.105871E+11 | 0.00 | 0.355180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221606E+10 | 0.00 |
Maximum of Months | 0.351976E+11 | 0.160967E+11 | 0.123431E+11 | 0.00 | 0.517046E+10 | 0.00 | 0.00 | 0.116938E+10 | 0.00 | 0.00 | 0.00 | 0.251301E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.278575E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.229130E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.211879E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.886905E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.109482E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 15849268.72 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 80002218.22 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.411434E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.117589E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.202455E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.276684E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.141031E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.278575E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 31354.05 | 02-JAN-09:09 | 6986.42 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 3797.61 | 04-JAN-15:39 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 31354.05 | 01-FEB-09:09 | 6986.42 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 3797.61 | 03-FEB-16:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 31354.05 | 01-MAR-09:09 | 6986.42 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 3797.61 | 01-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27809.90 | 01-APR-07:10 | 6986.42 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 3797.61 | 05-APR-09:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27665.32 | 06-MAY-08:09 | 6986.42 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 3562.73 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 24555.14 | 07-JUN-07:10 | 6986.42 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 3562.73 | 01-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 27665.32 | 29-JUL-08:09 | 6986.42 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 3562.73 | 01-JUL-06:19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 27809.90 | 30-AUG-07:10 | 6986.42 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 3562.73 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 31354.05 | 21-SEP-08:09 | 6986.42 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 3562.73 | 01-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 31354.05 | 02-OCT-08:09 | 6986.42 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 3797.61 | 21-OCT-11:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 31354.05 | 01-NOV-08:09 | 6986.42 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 3797.61 | 24-NOV-14:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 31354.05 | 01-DEC-09:09 | 6986.42 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 3797.61 | 29-DEC-17:40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 24555.14 | 6986.42 | 10112.62 | 0.00 | 3562.73 | 0.00 | 0.00 | |||||
Maximum of Months | 31354.05 | 6986.42 | 10112.62 | 0.00 | 3797.61 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3132.98 | 13-JAN-12:39 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3131.63 | 01-FEB-12:00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3131.64 | 11-MAR-12:00 | 0.00 |
April | 0.01 | 22-APR-15:00 | 0.00 | 0.00 | 0.00 | 3131.45 | 05-APR-11:00 | 0.00 |
May | 556.37 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 3131.56 | 03-MAY-11:20 | 0.00 |
June | 5327.82 | 30-JUN-14:50 | 0.00 | 0.00 | 0.00 | 3033.30 | 02-JUN-11:30 | 0.00 |
July | 7213.61 | 29-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2890.42 | 01-JUL-11:20 | 0.00 |
August | 4832.70 | 11-AUG-17:40 | 0.00 | 0.00 | 0.00 | 2762.47 | 02-AUG-11:00 | 0.00 |
September | 0.00 | 09-SEP-16:00 | 0.00 | 0.00 | 0.00 | 2746.70 | 30-SEP-11:30 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2851.22 | 30-OCT-11:39 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2990.31 | 28-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 3131.31 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2746.70 | 0.00 | ||
Maximum of Months | 7213.61 | 0.00 | 0.00 | 0.00 | 3132.98 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 54943.40 | 05-JAN-15:39 | 31354.05 | 10112.62 | 6986.42 | 0.00 | 3797.61 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53981.50 | 04-FEB-09:09 | 31354.05 | 10112.62 | 6986.42 | 0.00 | 3797.61 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50389.95 | 18-MAR-07:10 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 3797.61 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43403.55 | 13-APR-07:10 | 27809.90 | 10112.62 | 0.00 | 0.00 | 3797.61 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43071.21 | 09-MAY-08:20 | 27665.32 | 10112.62 | 0.00 | 0.00 | 3562.73 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39907.71 | 07-JUN-07:10 | 24555.14 | 10112.62 | 0.00 | 0.00 | 3562.73 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43465.79 | 29-JUL-08:30 | 27665.32 | 10112.62 | 0.00 | 0.00 | 3562.73 | 0.00 | 0.00 | 417.11 | 0.00 |
August | 43149.60 | 30-AUG-07:10 | 27809.90 | 10112.62 | 0.00 | 0.00 | 3562.73 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46735.99 | 30-SEP-08:09 | 31354.05 | 10112.62 | 0.00 | 0.00 | 3562.73 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 53963.56 | 31-OCT-08:39 | 31354.05 | 10112.62 | 6986.42 | 0.00 | 3797.61 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 54794.91 | 30-NOV-15:39 | 31354.05 | 10112.62 | 6986.42 | 0.00 | 3797.61 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 54942.87 | 30-DEC-15:39 | 31354.05 | 10112.62 | 6986.42 | 0.00 | 3797.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 39907.71 | 24555.14 | 10112.62 | 0.00 | 0.00 | 3562.73 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54943.40 | 31354.05 | 10112.62 | 6986.42 | 0.00 | 3797.61 | 0.00 | 0.00 | 417.11 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 233314.99 | 28-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 231503.97 | 24-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 206677.10 | 16-MAR-07:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 190478.36 | 02-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 17922.36 | 03-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 4898.49 | 02-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 8728.62 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 33715.48 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 168863.37 | 27-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 189299.96 | 29-NOV-07:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 217789.74 | 01-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 233314.99 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.00 | 15.64 | 12.67 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
February | 39.17 | 15.54 | 9.17 | 15.97 | 0.00 | 15.97 | 0.00 | 15.97 |
March | 24.83 | 15.56 | 7.33 | 15.89 | 0.00 | 15.89 | 0.00 | 15.89 |
April | 10.00 | 15.62 | 4.00 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
May | 0.33 | 17.18 | 0.33 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.17 | 17.18 | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
October | 7.83 | 15.86 | 3.83 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
November | 11.00 | 15.93 | 5.33 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
December | 25.50 | 15.82 | 8.17 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 |
Annual Sum or Average | 166.83 | 15.67 | 51.00 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.00 | 17.18 | 12.67 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 115.17 | 14.11 | 4.17 | 14.11 | 0.00 | 14.11 | 0.00 | 14.11 |
February | 102.00 | 14.18 | 3.83 | 14.18 | 0.00 | 14.18 | 0.00 | 14.18 |
March | 101.67 | 14.34 | 5.33 | 14.33 | 0.00 | 14.33 | 0.00 | 14.33 |
April | 49.00 | 14.53 | 3.67 | 14.53 | 0.00 | 14.53 | 0.00 | 14.53 |
May | 0.67 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.31 | 0.00 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3.00 | 14.95 | 0.67 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
October | 73.17 | 14.61 | 3.83 | 14.61 | 0.00 | 14.61 | 0.00 | 14.61 |
November | 112.17 | 14.34 | 4.17 | 14.34 | 0.00 | 14.34 | 0.00 | 14.34 |
December | 115.17 | 14.17 | 4.17 | 14.17 | 0.00 | 14.17 | 0.00 | 14.17 |
Annual Sum or Average | 672.00 | 14.30 | 29.83 | 14.29 | 0.83 | 14.31 | 0.00 | 14.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.17 | 14.99 | 5.33 | 14.99 | 0.83 | 27.31 | 0.00 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 76.50 | 7.57 | 28.17 | 7.61 | 0.00 | 7.61 | 0.00 | 7.61 |
February | 57.50 | 8.46 | 15.00 | 8.46 | 0.00 | 8.46 | 0.00 | 8.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.00 | 7.95 | 43.17 | 7.96 | 0.00 | 7.96 | 0.00 | 7.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 76.50 | 8.46 | 28.17 | 8.46 | 0.00 | 8.46 | 0.00 | 8.46 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.65 | 300.00 | 20.65 | 300.00 | 20.65 |
February | 276.00 | 20.68 | 276.00 | 20.68 | 276.00 | 20.68 |
March | 324.00 | 20.69 | 324.00 | 20.69 | 324.00 | 20.69 |
April | 300.00 | 20.84 | 282.33 | 20.78 | 282.33 | 20.76 |
May | 312.00 | 22.23 | 119.50 | 21.78 | 119.50 | 21.52 |
June | 128.00 | 23.47 | 56.83 | 23.62 | 3.67 | 23.56 |
July | 26.33 | 23.26 | 210.17 | 24.04 | 0.00 | 24.04 |
August | 131.33 | 23.18 | 83.83 | 23.46 | 4.83 | 23.39 |
September | 300.00 | 21.64 | 149.67 | 21.29 | 149.67 | 21.12 |
October | 300.00 | 20.72 | 300.00 | 20.72 | 300.00 | 20.72 |
November | 288.00 | 20.70 | 288.00 | 20.70 | 288.00 | 20.70 |
December | 300.00 | 20.69 | 300.00 | 20.69 | 300.00 | 20.69 |
Annual Sum or Average | 2985.67 | 21.21 | 2690.33 | 21.17 | 2348.00 | 21.03 |
Minimum of Months | 26.33 | 20.65 | 56.83 | 20.65 | 0.00 | 20.65 |
Maximum of Months | 324.00 | 23.47 | 324.00 | 24.04 | 324.00 | 24.04 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
February | 276.00 | 15.54 | 276.00 | 15.54 | 276.00 | 15.54 |
March | 324.00 | 15.58 | 324.00 | 15.58 | 324.00 | 15.58 |
April | 300.00 | 16.85 | 297.67 | 16.83 | 297.67 | 16.83 |
May | 304.33 | 20.84 | 148.50 | 20.24 | 148.50 | 19.94 |
June | 76.17 | 23.29 | 209.83 | 25.36 | 6.33 | 25.33 |
July | 41.67 | 25.29 | 275.33 | 26.27 | 24.50 | 26.30 |
August | 96.17 | 22.96 | 203.33 | 24.97 | 9.83 | 24.88 |
September | 298.50 | 19.41 | 205.00 | 18.94 | 205.00 | 18.75 |
October | 300.00 | 15.99 | 300.00 | 15.99 | 300.00 | 15.99 |
November | 288.00 | 15.54 | 288.00 | 15.54 | 288.00 | 15.54 |
December | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
Annual Sum or Average | 2904.83 | 17.27 | 3127.67 | 17.85 | 2479.83 | 17.41 |
Minimum of Months | 41.67 | 15.54 | 148.50 | 15.54 | 6.33 | 15.54 |
Maximum of Months | 324.00 | 25.29 | 324.00 | 26.27 | 324.00 | 26.30 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 9.78 | 300.00 | 9.78 | 300.00 | 9.78 |
February | 276.00 | 9.91 | 276.00 | 9.91 | 276.00 | 9.91 |
March | 324.00 | 10.08 | 324.00 | 10.08 | 324.00 | 10.08 |
April | 300.00 | 11.10 | 300.00 | 11.10 | 300.00 | 11.10 |
May | 312.00 | 15.95 | 312.00 | 15.95 | 312.00 | 15.95 |
June | 282.83 | 21.25 | 93.50 | 20.73 | 88.83 | 20.37 |
July | 108.00 | 22.88 | 149.00 | 24.40 | 0.67 | 24.39 |
August | 240.33 | 21.70 | 114.67 | 22.04 | 53.67 | 21.70 |
September | 300.00 | 16.05 | 298.50 | 16.03 | 298.50 | 16.03 |
October | 300.00 | 10.49 | 300.00 | 10.49 | 300.00 | 10.49 |
November | 288.00 | 10.00 | 288.00 | 10.00 | 288.00 | 10.00 |
December | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
Annual Sum or Average | 3331.17 | 13.44 | 3055.67 | 13.16 | 2841.67 | 12.77 |
Minimum of Months | 108.00 | 9.78 | 93.50 | 9.78 | 0.67 | 9.78 |
Maximum of Months | 324.00 | 22.88 | 324.00 | 24.40 | 324.00 | 24.39 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 28.10 | 7.00 | 0.17 | 28.10 | 0.00 | 0.00 | 0.00 | 22-APR-16:00 | 0.00 | 01-APR-00:10 | 0.05 | 22-APR-16:00 | 0.05 | 22-APR-16:00 | 0.00 | 01-APR-00:10 | 0.01 | 22-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 22981580.97 | 5656224.08 | 9.17 | 22981580.97 | -0.0 | 0.00 | 0.17 | 31-MAY-16:00 | 0.00 | 01-MAY-00:10 | 2291.05 | 31-MAY-16:00 | 2291.05 | 31-MAY-16:00 | 0.00 | 31-MAY-16:00 | 556.37 | 31-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.133434E+10 | 0.318062E+09 | 116.29 | 0.128486E+10 | 49473137.18 | 0.00 | 1.00 | 10-JUN-07:02 | 0.00 | 01-JUN-00:10 | 15654.92 | 24-JUN-07:02 | 13591.42 | 10-JUN-07:02 | 4891.52 | 24-JUN-07:02 | 3319.38 | 24-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.276396E+10 | 0.655915E+09 | 173.42 | 0.256151E+10 | 0.202452E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 16364.53 | 08-JUL-07:02 | 15191.69 | 12-JUL-07:03 | 5808.52 | 08-JUL-07:02 | 3467.48 | 08-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.114326E+10 | 0.271804E+09 | 95.00 | 0.106230E+10 | 80954387.34 | 0.00 | 1.00 | 05-AUG-07:02 | 0.00 | 01-AUG-00:10 | 15760.94 | 05-AUG-07:02 | 13798.81 | 12-AUG-07:02 | 4170.42 | 05-AUG-07:02 | 3342.21 | 05-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 32.44 | 8.09 | 0.83 | 32.44 | 0.00 | 0.00 | 0.00 | 09-SEP-17:00 | 0.00 | 01-SEP-00:10 | 0.02 | 09-SEP-17:00 | 0.02 | 09-SEP-17:00 | 0.00 | 09-SEP-16:40 | 0.00 | 09-SEP-17:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.526454E+10 | 0.125144E+10 | 394.88 | 0.493166E+10 | 0.332879E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.276396E+10 | 0.655915E+09 | 173.42 | 0.256151E+10 | 0.202452E+09 | 0.00 | 1.00 | 0.00 | 16364.53 | 15191.69 | 5808.52 | 3467.48 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.603960E+09 | 0.154414E+09 | 28.66 | 0.594572E+09 | 9388323.27 | 0.00 | 1.00 | 20-JUN-17:23 | 0.00 | 01-JUN-00:10 | 42202.73 | 20-JUN-17:23 | 42202.73 | 20-JUN-17:23 | 1325.76 | 30-JUN-12:10 | 9827.87 | 20-JUN-17:50 | 0.00 | 01-JUN-00:10 |
July | 0.202414E+10 | 0.513469E+09 | 75.93 | 0.200494E+10 | 19194143.66 | 0.00 | 1.00 | 11-JUL-17:11 | 0.00 | 01-JUL-00:10 | 44713.01 | 29-JUL-19:33 | 42995.45 | 23-JUL-17:25 | 8055.51 | 24-JUL-17:45 | 10267.97 | 29-JUL-19:33 | 0.00 | 01-JUL-00:10 |
August | 0.286936E+09 | 72749362.39 | 26.25 | 0.284333E+09 | 2602423.28 | 0.00 | 1.00 | 02-AUG-17:25 | 0.00 | 01-AUG-00:10 | 42197.65 | 11-AUG-17:35 | 42197.65 | 11-AUG-17:35 | 174.73 | 25-AUG-14:20 | 9665.40 | 11-AUG-17:35 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.291503E+10 | 0.740632E+09 | 130.84 | 0.288385E+10 | 31184890.21 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.202414E+10 | 0.513469E+09 | 75.93 | 0.200494E+10 | 19194143.66 | 0.00 | 1.00 | 0.00 | 44713.01 | 42995.45 | 8055.51 | 10267.97 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.61 | 0.99 | 4.62 | 0.00 | 261.23 | 0.00 | 0.00 | 0.00 |
February | 33.38 | 11.74 | 21.64 | 8.04 | 216.54 | 0.00 | 0.00 | 0.00 |
March | 100.17 | 43.40 | 56.76 | 63.44 | 149.22 | 0.00 | 0.00 | 0.00 |
April | 235.94 | 122.20 | 113.74 | 241.41 | 77.96 | 0.00 | 0.00 | 0.00 |
May | 229.16 | 104.28 | 124.88 | 246.26 | 38.39 | 0.00 | 0.00 | 0.00 |
June | 251.33 | 107.18 | 144.15 | 277.06 | 25.59 | 0.00 | 0.00 | 0.00 |
July | 210.06 | 79.33 | 130.73 | 229.62 | 31.29 | 0.00 | 0.00 | 0.00 |
August | 173.15 | 73.51 | 99.64 | 181.00 | 45.60 | 0.00 | 0.00 | 0.00 |
September | 104.40 | 43.57 | 60.83 | 91.47 | 69.25 | 0.00 | 0.00 | 0.00 |
October | 40.94 | 12.30 | 28.64 | 18.44 | 130.14 | 0.00 | 0.00 | 0.00 |
November | 16.44 | 5.98 | 10.45 | 2.09 | 247.95 | 0.00 | 0.00 | 0.00 |
December | 1.48 | 0.16 | 1.32 | 0.00 | 279.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.14 | 50.49 | 66.64 | 113.66 | 130.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.48 | 0.16 | 1.32 | 0.00 | 25.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.33 | 122.20 | 144.15 | 277.06 | 279.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.61 | 0.99 | 4.62 | 0.00 | 261.23 | 0.00 | 0.00 | 0.00 |
February | 33.38 | 11.74 | 21.64 | 8.04 | 216.54 | 0.00 | 0.00 | 0.00 |
March | 100.17 | 43.40 | 56.76 | 63.44 | 149.22 | 0.00 | 0.00 | 0.00 |
April | 235.94 | 122.20 | 113.74 | 241.41 | 77.96 | 0.00 | 0.00 | 0.00 |
May | 229.16 | 104.28 | 124.88 | 246.26 | 38.39 | 0.00 | 0.00 | 0.00 |
June | 251.33 | 107.18 | 144.15 | 277.06 | 25.59 | 0.00 | 0.00 | 0.00 |
July | 210.06 | 79.33 | 130.73 | 229.62 | 31.29 | 0.00 | 0.00 | 0.00 |
August | 173.15 | 73.51 | 99.64 | 181.00 | 45.60 | 0.00 | 0.00 | 0.00 |
September | 104.40 | 43.57 | 60.83 | 91.47 | 69.25 | 0.00 | 0.00 | 0.00 |
October | 40.94 | 12.30 | 28.64 | 18.44 | 130.14 | 0.00 | 0.00 | 0.00 |
November | 16.44 | 5.98 | 10.45 | 2.09 | 247.95 | 0.00 | 0.00 | 0.00 |
December | 1.48 | 0.16 | 1.32 | 0.00 | 279.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.14 | 50.49 | 66.64 | 113.66 | 130.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.48 | 0.16 | 1.32 | 0.00 | 25.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.33 | 122.20 | 144.15 | 277.06 | 279.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.00 | 2.36 | 0.00 | 154.34 | 0.00 | 0.00 | 0.00 |
February | 10.44 | 0.00 | 10.44 | 0.00 | 135.29 | 0.00 | 0.00 | 0.00 |
March | 28.00 | 0.01 | 27.99 | 3.77 | 95.42 | 0.00 | 0.00 | 0.00 |
April | 50.96 | 1.45 | 49.51 | 27.64 | 45.88 | 0.00 | 0.00 | 0.00 |
May | 78.17 | 12.70 | 65.47 | 70.09 | 20.01 | 0.00 | 0.00 | 0.00 |
June | 100.74 | 22.17 | 78.57 | 99.61 | 11.53 | 0.00 | 0.00 | 0.00 |
July | 85.03 | 14.05 | 70.98 | 83.21 | 15.60 | 0.00 | 0.00 | 0.00 |
August | 54.62 | 2.99 | 51.63 | 43.88 | 25.25 | 0.00 | 0.00 | 0.00 |
September | 30.36 | 0.09 | 30.27 | 14.19 | 41.96 | 0.00 | 0.00 | 0.00 |
October | 14.69 | 0.00 | 14.69 | 2.02 | 80.39 | 0.00 | 0.00 | 0.00 |
November | 4.56 | 0.00 | 4.56 | 0.00 | 151.12 | 0.00 | 0.00 | 0.00 |
December | 0.72 | 0.00 | 0.72 | 0.00 | 163.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.53 | 4.48 | 34.05 | 28.86 | 78.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.72 | 0.00 | 0.72 | 0.00 | 11.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.74 | 22.17 | 78.57 | 99.61 | 163.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.00 | 2.36 | 0.00 | 154.34 | 0.00 | 0.00 | 0.00 |
February | 10.44 | 0.00 | 10.44 | 0.00 | 135.29 | 0.00 | 0.00 | 0.00 |
March | 28.00 | 0.01 | 27.99 | 3.77 | 95.42 | 0.00 | 0.00 | 0.00 |
April | 50.96 | 1.45 | 49.51 | 27.64 | 45.88 | 0.00 | 0.00 | 0.00 |
May | 78.17 | 12.70 | 65.47 | 70.08 | 20.01 | 0.00 | 0.00 | 0.00 |
June | 100.74 | 22.17 | 78.57 | 99.61 | 11.53 | 0.00 | 0.00 | 0.00 |
July | 85.02 | 14.05 | 70.98 | 83.20 | 15.60 | 0.00 | 0.00 | 0.00 |
August | 54.62 | 2.99 | 51.63 | 43.88 | 25.25 | 0.00 | 0.00 | 0.00 |
September | 30.36 | 0.09 | 30.27 | 14.18 | 41.96 | 0.00 | 0.00 | 0.00 |
October | 14.69 | 0.00 | 14.69 | 2.02 | 80.39 | 0.00 | 0.00 | 0.00 |
November | 4.56 | 0.00 | 4.56 | 0.00 | 151.12 | 0.00 | 0.00 | 0.00 |
December | 0.72 | 0.00 | 0.72 | 0.00 | 163.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.53 | 4.47 | 34.05 | 28.86 | 78.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.72 | 0.00 | 0.72 | 0.00 | 11.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.74 | 22.17 | 78.57 | 99.61 | 163.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_17
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_16
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_15
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 165.69 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.00 | 144.59 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 16.56 | 98.09 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 68.10 | 54.87 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 102.26 | 29.74 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 111.55 | 21.52 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 100.09 | 24.70 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 69.45 | 33.97 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 28.72 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 3.91 | 83.47 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 162.31 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 41.95 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 21.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 111.55 | 175.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.75 | 0.16 | 1.60 | 0.00 | 139.01 | 0.00 | 0.00 | 0.00 |
February | 8.85 | 2.13 | 6.73 | 0.03 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 31.08 | 13.11 | 17.97 | 22.75 | 78.68 | 0.00 | 0.00 | 0.00 |
April | 62.61 | 33.64 | 28.96 | 79.07 | 41.10 | 0.00 | 0.00 | 0.00 |
May | 81.82 | 46.46 | 35.36 | 114.05 | 21.69 | 0.00 | 0.00 | 0.00 |
June | 88.86 | 44.23 | 44.63 | 122.26 | 15.67 | 0.00 | 0.00 | 0.00 |
July | 79.70 | 38.46 | 41.24 | 105.74 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 59.92 | 28.97 | 30.95 | 74.73 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 12.71 | 19.62 | 33.63 | 38.80 | 0.00 | 0.00 | 0.00 |
October | 13.27 | 3.17 | 10.10 | 7.10 | 62.12 | 8.50 | 0.00 | 0.00 |
November | 3.33 | 0.27 | 3.06 | 0.00 | 137.03 | 0.00 | 0.00 | 0.00 |
December | 0.49 | 0.01 | 0.48 | 0.00 | 149.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.82 | 18.70 | 20.12 | 46.86 | 70.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 0.01 | 0.48 | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.86 | 46.46 | 44.63 | 122.26 | 149.34 | 8.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 15030620.33 | 2648468.72 | 12382151.60 | 0.00 | 0.699688E+09 |
February | 80746669.30 | 28397081.48 | 52349587.82 | 19442821.61 | 0.523855E+09 |
March | 0.268285E+09 | 0.116256E+09 | 0.152029E+09 | 0.169924E+09 | 0.399677E+09 |
April | 0.611559E+09 | 0.316741E+09 | 0.294817E+09 | 0.625728E+09 | 0.202067E+09 |
May | 0.613770E+09 | 0.279302E+09 | 0.334469E+09 | 0.659577E+09 | 0.102831E+09 |
June | 0.651442E+09 | 0.277799E+09 | 0.373643E+09 | 0.718136E+09 | 66328710.70 |
July | 0.562626E+09 | 0.212483E+09 | 0.350143E+09 | 0.615017E+09 | 83802888.00 |
August | 0.463775E+09 | 0.196900E+09 | 0.266875E+09 | 0.484790E+09 | 0.122130E+09 |
September | 0.270593E+09 | 0.112932E+09 | 0.157661E+09 | 0.237085E+09 | 0.179503E+09 |
October | 0.109666E+09 | 32945973.55 | 76720035.04 | 49385315.01 | 0.348576E+09 |
November | 42605946.70 | 15511955.51 | 27093991.19 | 5405003.09 | 0.642682E+09 |
December | 3958592.44 | 432233.62 | 3526358.83 | 0.00 | 0.749388E+09 |
Annual Sum or Average | 0.369406E+10 | 0.159235E+10 | 0.210171E+10 | 0.358449E+10 | 0.412053E+10 |
Minimum of Months | 3958592.44 | 432233.62 | 3526358.83 | 0.00 | 66328710.70 |
Maximum of Months | 0.651442E+09 | 0.316741E+09 | 0.373643E+09 | 0.718136E+09 | 0.749388E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 15030620.33 | 2648468.72 | 12382151.60 | 0.00 | 0.699688E+09 |
February | 80746669.30 | 28397081.48 | 52349587.82 | 19442821.61 | 0.523855E+09 |
March | 0.268285E+09 | 0.116256E+09 | 0.152029E+09 | 0.169924E+09 | 0.399677E+09 |
April | 0.611559E+09 | 0.316741E+09 | 0.294817E+09 | 0.625728E+09 | 0.202067E+09 |
May | 0.613770E+09 | 0.279302E+09 | 0.334469E+09 | 0.659577E+09 | 0.102831E+09 |
June | 0.651442E+09 | 0.277799E+09 | 0.373643E+09 | 0.718136E+09 | 66328710.70 |
July | 0.562626E+09 | 0.212483E+09 | 0.350143E+09 | 0.615017E+09 | 83802888.00 |
August | 0.463775E+09 | 0.196900E+09 | 0.266875E+09 | 0.484790E+09 | 0.122130E+09 |
September | 0.270593E+09 | 0.112932E+09 | 0.157661E+09 | 0.237085E+09 | 0.179503E+09 |
October | 0.109666E+09 | 32945973.55 | 76720035.04 | 49385315.01 | 0.348576E+09 |
November | 42605946.70 | 15511955.51 | 27093991.19 | 5405003.09 | 0.642682E+09 |
December | 3958592.44 | 432233.62 | 3526358.83 | 0.00 | 0.749388E+09 |
Annual Sum or Average | 0.369406E+10 | 0.159235E+10 | 0.210171E+10 | 0.358449E+10 | 0.412053E+10 |
Minimum of Months | 3958592.44 | 432233.62 | 3526358.83 | 0.00 | 66328710.70 |
Maximum of Months | 0.651442E+09 | 0.316741E+09 | 0.373643E+09 | 0.718136E+09 | 0.749388E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6324012.93 | 0.00 | 6324012.93 | 0.00 | 0.413379E+09 |
February | 25249854.44 | 0.00 | 25249854.44 | 0.00 | 0.327298E+09 |
March | 74992053.45 | 26013.52 | 74966039.93 | 10105319.53 | 0.255574E+09 |
April | 0.132087E+09 | 3749549.60 | 0.128338E+09 | 71649600.18 | 0.118923E+09 |
May | 0.209376E+09 | 34023158.09 | 0.175353E+09 | 0.187719E+09 | 53593028.83 |
June | 0.261119E+09 | 57459443.73 | 0.203660E+09 | 0.258194E+09 | 29890310.04 |
July | 0.227735E+09 | 37628989.61 | 0.190106E+09 | 0.222857E+09 | 41781792.00 |
August | 0.146289E+09 | 8005493.63 | 0.138283E+09 | 0.117529E+09 | 67623222.87 |
September | 78703925.51 | 233396.05 | 78470529.45 | 36768275.97 | 0.108751E+09 |
October | 39354522.63 | 0.00 | 39354522.63 | 5413990.97 | 0.215328E+09 |
November | 11819129.46 | 0.00 | 11819129.46 | 0.00 | 0.391704E+09 |
December | 1918373.75 | 0.00 | 1918373.75 | 0.00 | 0.438658E+09 |
Annual Sum or Average | 0.121497E+10 | 0.141126E+09 | 0.107384E+10 | 0.910237E+09 | 0.246250E+10 |
Minimum of Months | 1918373.75 | 0.00 | 1918373.75 | 0.00 | 29890310.04 |
Maximum of Months | 0.261119E+09 | 57459443.73 | 0.203660E+09 | 0.258194E+09 | 0.438658E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6323784.35 | 0.00 | 6323784.35 | 0.00 | 0.413379E+09 |
February | 25248999.58 | 0.00 | 25248999.58 | 0.00 | 0.327298E+09 |
March | 74989665.67 | 26012.30 | 74963653.37 | 10104128.44 | 0.255575E+09 |
April | 0.132083E+09 | 3749373.85 | 0.128334E+09 | 71645656.65 | 0.118924E+09 |
May | 0.209369E+09 | 34021563.38 | 0.175347E+09 | 0.187711E+09 | 53592852.30 |
June | 0.261110E+09 | 57456750.53 | 0.203653E+09 | 0.258182E+09 | 29890286.85 |
July | 0.227727E+09 | 37627225.89 | 0.190100E+09 | 0.222847E+09 | 41781769.33 |
August | 0.146284E+09 | 8005118.40 | 0.138279E+09 | 0.117523E+09 | 67623050.00 |
September | 78701324.89 | 233385.12 | 78467939.78 | 36765852.32 | 0.108751E+09 |
October | 39353174.47 | 0.00 | 39353174.47 | 5413486.71 | 0.215328E+09 |
November | 11818702.27 | 0.00 | 11818702.27 | 0.00 | 0.391703E+09 |
December | 1918301.37 | 0.00 | 1918301.37 | 0.00 | 0.438657E+09 |
Annual Sum or Average | 0.121493E+10 | 0.141119E+09 | 0.107381E+10 | 0.910193E+09 | 0.246250E+10 |
Minimum of Months | 1918301.37 | 0.00 | 1918301.37 | 0.00 | 29890286.85 |
Maximum of Months | 0.261110E+09 | 57456750.53 | 0.203653E+09 | 0.258182E+09 | 0.438657E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_17
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_16
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_15
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.443797E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 0.00 | 0.349802E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 44360660.49 | 0.262721E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.176521E+09 | 0.142231E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.273896E+09 | 79653028.02 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.289135E+09 | 55790128.12 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.268093E+09 | 66145677.31 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.186004E+09 | 90997996.16 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 74452093.59 | 0.121853E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 10466192.83 | 0.223555E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.420703E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.468951E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.132293E+10 | 0.272620E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 55790128.12 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.289135E+09 | 0.468951E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C6
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5_C4
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8_C5
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4699038.96 | 417208.73 | 4281830.23 | 0.00 | 0.372322E+09 |
February | 21420845.37 | 5147698.96 | 16273146.41 | 61352.70 | 0.286472E+09 |
March | 83237070.68 | 35102417.27 | 48134653.41 | 60934614.05 | 0.210733E+09 |
April | 0.162281E+09 | 87206731.36 | 75074582.59 | 0.204958E+09 | 0.106532E+09 |
May | 0.219146E+09 | 0.124435E+09 | 94711673.35 | 0.305480E+09 | 58081512.04 |
June | 0.230331E+09 | 0.114656E+09 | 0.115675E+09 | 0.316901E+09 | 40612027.28 |
July | 0.213471E+09 | 0.103017E+09 | 0.110454E+09 | 0.283211E+09 | 57168838.25 |
August | 0.160493E+09 | 77602226.32 | 82890591.87 | 0.200166E+09 | 78670502.15 |
September | 83788065.78 | 32934837.41 | 50853228.37 | 87181813.39 | 0.100577E+09 |
October | 35535758.66 | 8491387.89 | 27044370.77 | 19012026.83 | 0.166395E+09 |
November | 8642682.92 | 699060.55 | 7943622.37 | 0.00 | 0.355181E+09 |
December | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 0.399995E+09 |
Annual Sum or Average | 0.122437E+10 | 0.589734E+09 | 0.634632E+09 | 0.147791E+10 | 0.223274E+10 |
Minimum of Months | 1319650.49 | 24351.12 | 1295299.37 | 0.00 | 40612027.28 |
Maximum of Months | 0.230331E+09 | 0.124435E+09 | 0.115675E+09 | 0.316901E+09 | 0.399995E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 831.14 | 15.95 | 1.98 | 13.97 | 0.00 | 0.00 |
February | 8.00 | 695.59 | 87.63 | 23.48 | 64.15 | 0.00 | 0.00 |
March | 122.57 | 477.43 | 256.33 | 86.83 | 169.50 | 0.00 | 0.00 |
April | 533.83 | 243.41 | 573.80 | 247.29 | 326.51 | 0.00 | 0.00 |
May | 624.32 | 108.44 | 614.65 | 233.96 | 380.69 | 0.00 | 0.00 |
June | 744.04 | 64.94 | 704.13 | 258.69 | 445.45 | 0.00 | 0.00 |
July | 618.45 | 86.58 | 590.17 | 186.76 | 403.41 | 0.00 | 0.00 |
August | 443.96 | 135.89 | 455.54 | 153.01 | 302.54 | 0.00 | 0.00 |
September | 208.27 | 219.39 | 269.52 | 87.32 | 182.20 | 0.00 | 0.00 |
October | 36.11 | 416.26 | 111.28 | 24.60 | 86.67 | 0.00 | 0.00 |
November | 1.35 | 795.32 | 41.99 | 11.97 | 30.03 | 0.00 | 0.00 |
December | 0.00 | 887.13 | 4.39 | 0.32 | 4.07 | 0.00 | 0.00 |
Annual Sum or Average | 279.61 | 412.05 | 311.33 | 109.94 | 201.39 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 64.94 | 4.39 | 0.32 | 4.07 | 0.00 | 0.00 |
Maximum of Months | 744.04 | 887.13 | 704.13 | 258.69 | 445.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2816.81 | 29.83 | 2.65 | 27.18 | 0.00 | 0.00 |
February | 0.00 | 2458.10 | 150.53 | 36.17 | 114.35 | 0.00 | 0.00 |
March | 281.56 | 1667.51 | 528.31 | 222.80 | 305.51 | 0.00 | 0.00 |
April | 1157.74 | 932.84 | 1064.35 | 571.96 | 492.39 | 0.00 | 0.00 |
May | 1738.44 | 505.56 | 1390.94 | 789.80 | 601.14 | 0.00 | 0.00 |
June | 1896.33 | 365.91 | 1510.66 | 751.99 | 758.67 | 0.00 | 0.00 |
July | 1701.61 | 419.83 | 1354.92 | 653.86 | 701.06 | 0.00 | 0.00 |
August | 1180.58 | 577.57 | 1018.66 | 492.55 | 526.11 | 0.00 | 0.00 |
September | 488.30 | 799.19 | 549.54 | 216.01 | 333.53 | 0.00 | 0.00 |
October | 66.43 | 1418.92 | 225.55 | 53.90 | 171.65 | 0.00 | 0.00 |
November | 0.00 | 2759.24 | 56.68 | 4.58 | 52.10 | 0.00 | 0.00 |
December | 0.00 | 2976.47 | 8.38 | 0.15 | 8.22 | 0.00 | 0.00 |
Annual Sum or Average | 713.15 | 1469.60 | 660.01 | 317.91 | 342.11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 365.91 | 8.38 | 0.15 | 8.22 | 0.00 | 0.00 |
Maximum of Months | 1896.33 | 2976.47 | 1510.66 | 789.80 | 758.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 47937.69 | 84.21 | 7.48 | 76.74 | 0.00 | 0.00 |
February | 3.67 | 44350.42 | 425.02 | 102.14 | 322.88 | 0.00 | 0.00 |
March | 3616.08 | 29818.34 | 1491.70 | 629.08 | 862.63 | 0.00 | 0.00 |
April | 12333.09 | 12447.93 | 3005.21 | 1614.94 | 1390.27 | 0.00 | 0.00 |
May | 18757.73 | 3179.87 | 3927.35 | 2230.01 | 1697.34 | 0.00 | 0.00 |
June | 19304.23 | 2257.26 | 4265.39 | 2123.27 | 2142.13 | 0.00 | 0.00 |
July | 17353.90 | 3077.16 | 3825.65 | 1846.19 | 1979.46 | 0.00 | 0.00 |
August | 11623.03 | 4304.94 | 2876.22 | 1390.72 | 1485.49 | 0.00 | 0.00 |
September | 5599.47 | 6700.40 | 1551.63 | 609.90 | 941.73 | 0.00 | 0.00 |
October | 1086.08 | 18257.27 | 636.84 | 152.18 | 484.67 | 0.00 | 0.00 |
November | 0.00 | 42728.55 | 160.05 | 12.95 | 147.10 | 0.00 | 0.00 |
December | 0.00 | 48285.90 | 23.65 | 0.44 | 23.21 | 0.00 | 0.00 |
Annual Sum or Average | 7514.38 | 21826.12 | 1863.57 | 897.62 | 965.95 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 2257.26 | 23.65 | 0.44 | 23.21 | 0.00 | 0.00 |
Maximum of Months | 19304.23 | 48285.90 | 4265.39 | 2230.01 | 2142.13 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.222613E+10 | 42709037.93 | 5296937.45 | 37412100.49 | 0.00 | 0.00 |
February | 19360909.87 | 0.168278E+10 | 0.211992E+09 | 56794162.96 | 0.155198E+09 | 0.00 | 0.00 |
March | 0.328292E+09 | 0.127874E+10 | 0.686551E+09 | 0.232563E+09 | 0.453988E+09 | 0.00 | 0.00 |
April | 0.138369E+10 | 0.630920E+09 | 0.148729E+10 | 0.640982E+09 | 0.846306E+09 | 0.00 | 0.00 |
May | 0.167219E+10 | 0.290455E+09 | 0.164629E+10 | 0.626648E+09 | 0.101964E+10 | 0.00 | 0.00 |
June | 0.192855E+10 | 0.168336E+09 | 0.182511E+10 | 0.670514E+09 | 0.115460E+10 | 0.00 | 0.00 |
July | 0.165646E+10 | 0.231885E+09 | 0.158071E+10 | 0.500221E+09 | 0.108049E+10 | 0.00 | 0.00 |
August | 0.118909E+10 | 0.363970E+09 | 0.122012E+10 | 0.409811E+09 | 0.810311E+09 | 0.00 | 0.00 |
September | 0.539848E+09 | 0.568652E+09 | 0.698592E+09 | 0.226330E+09 | 0.472261E+09 | 0.00 | 0.00 |
October | 96705991.10 | 0.111492E+10 | 0.298040E+09 | 65891947.10 | 0.232148E+09 | 0.00 | 0.00 |
November | 3511937.94 | 0.206147E+10 | 0.108850E+09 | 31023911.01 | 77825814.12 | 0.00 | 0.00 |
December | 0.00 | 0.237609E+10 | 11753860.01 | 864467.23 | 10889392.78 | 0.00 | 0.00 |
Annual Sum or Average | 0.881770E+10 | 0.129943E+11 | 0.981801E+10 | 0.346694E+10 | 0.635107E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.168336E+09 | 11753860.01 | 864467.23 | 10889392.78 | 0.00 | 0.00 |
Maximum of Months | 0.192855E+10 | 0.237609E+10 | 0.182511E+10 | 0.670514E+09 | 0.115460E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.754455E+10 | 79883662.37 | 7092548.40 | 72791113.97 | 0.00 | 0.00 |
February | 0.00 | 0.594663E+10 | 0.364154E+09 | 87510882.26 | 0.276643E+09 | 0.00 | 0.00 |
March | 0.754131E+09 | 0.446626E+10 | 0.141503E+10 | 0.596741E+09 | 0.818289E+09 | 0.00 | 0.00 |
April | 0.300086E+10 | 0.241793E+10 | 0.275878E+10 | 0.148251E+10 | 0.127627E+10 | 0.00 | 0.00 |
May | 0.465623E+10 | 0.135410E+10 | 0.372549E+10 | 0.211539E+10 | 0.161010E+10 | 0.00 | 0.00 |
June | 0.491529E+10 | 0.948432E+09 | 0.391563E+10 | 0.194916E+10 | 0.196647E+10 | 0.00 | 0.00 |
July | 0.455759E+10 | 0.112448E+10 | 0.362901E+10 | 0.175129E+10 | 0.187771E+10 | 0.00 | 0.00 |
August | 0.316208E+10 | 0.154697E+10 | 0.272838E+10 | 0.131924E+10 | 0.140914E+10 | 0.00 | 0.00 |
September | 0.126569E+10 | 0.207150E+10 | 0.142440E+10 | 0.559892E+09 | 0.864505E+09 | 0.00 | 0.00 |
October | 0.177925E+09 | 0.380043E+10 | 0.604108E+09 | 0.144354E+09 | 0.459754E+09 | 0.00 | 0.00 |
November | 0.00 | 0.715194E+10 | 0.146926E+09 | 11884029.43 | 0.135042E+09 | 0.00 | 0.00 |
December | 0.00 | 0.797217E+10 | 22434058.26 | 413969.01 | 22020089.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.224898E+11 | 0.463454E+11 | 0.208142E+11 | 0.100255E+11 | 0.107887E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.948432E+09 | 22434058.26 | 413969.01 | 22020089.25 | 0.00 | 0.00 |
Maximum of Months | 0.491529E+10 | 0.797217E+10 | 0.391563E+10 | 0.211539E+10 | 0.196647E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.128396E+12 | 0.225554E+09 | 20026019.01 | 0.205528E+09 | 0.00 | 0.00 |
February | 8885141.59 | 0.107293E+12 | 0.102820E+10 | 0.247090E+09 | 0.781111E+09 | 0.00 | 0.00 |
March | 0.968532E+10 | 0.798655E+11 | 0.399538E+10 | 0.168492E+10 | 0.231046E+10 | 0.00 | 0.00 |
April | 0.319674E+11 | 0.322650E+11 | 0.778950E+10 | 0.418592E+10 | 0.360358E+10 | 0.00 | 0.00 |
May | 0.502407E+11 | 0.851696E+10 | 0.105190E+11 | 0.597286E+10 | 0.454616E+10 | 0.00 | 0.00 |
June | 0.500366E+11 | 0.585082E+10 | 0.110559E+11 | 0.550351E+10 | 0.555239E+10 | 0.00 | 0.00 |
July | 0.464807E+11 | 0.824187E+10 | 0.102466E+11 | 0.494483E+10 | 0.530178E+10 | 0.00 | 0.00 |
August | 0.311311E+11 | 0.115303E+11 | 0.770366E+10 | 0.372491E+10 | 0.397875E+10 | 0.00 | 0.00 |
September | 0.145138E+11 | 0.173674E+11 | 0.402183E+10 | 0.158087E+10 | 0.244095E+10 | 0.00 | 0.00 |
October | 0.290895E+10 | 0.489003E+11 | 0.170572E+10 | 0.407587E+09 | 0.129813E+10 | 0.00 | 0.00 |
November | 0.00 | 0.110752E+12 | 0.414849E+09 | 33554906.62 | 0.381294E+09 | 0.00 | 0.00 |
December | 0.00 | 0.129329E+12 | 63343223.32 | 1168853.66 | 62174369.66 | 0.00 | 0.00 |
Annual Sum or Average | 0.236973E+12 | 0.688308E+12 | 0.587696E+11 | 0.283072E+11 | 0.304623E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.585082E+10 | 63343223.32 | 1168853.66 | 62174369.66 | 0.00 | 0.00 |
Maximum of Months | 0.502407E+11 | 0.129329E+12 | 0.110559E+11 | 0.597286E+10 | 0.555239E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.114210E+10 | -0.105362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88475614.5 | 59.00 | 0.00 | 0.00 |
February | 0.104778E+10 | -967992873.5 | 0.00 | 0.00 | 672.00 | 0.00 | -79785912.1 | 59.00 | 0.00 | 0.00 |
March | 0.121936E+10 | -0.113140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87957652.2 | 59.00 | 0.00 | 0.00 |
April | 0.113479E+10 | -0.105104E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -83756071.5 | 59.00 | 0.00 | 0.00 |
May | 0.116587E+10 | -0.108503E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -80832610.6 | 59.00 | 0.00 | 0.00 |
June | 0.111303E+10 | -0.104139E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -71638129.6 | 59.00 | 0.00 | 0.00 |
July | 0.104080E+10 | -968508489.6 | 0.00 | 0.00 | 744.00 | 0.00 | -72292721.8 | 59.00 | 0.00 | 0.00 |
August | 0.108899E+10 | -0.101499E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -74009651.7 | 58.99 | 0.00 | 0.00 |
September | 0.101937E+10 | -940059327.2 | 0.00 | 0.00 | 720.00 | 0.00 | -79314892.6 | 58.99 | 0.00 | 0.00 |
October | 0.104848E+10 | -960836228.1 | 0.00 | 0.00 | 744.00 | 0.00 | -87644061.1 | 58.99 | 0.00 | 0.00 |
November | 0.104151E+10 | -955946307.8 | 0.00 | 0.00 | 720.00 | 0.00 | -85558781.3 | 58.99 | 0.00 | 0.00 |
December | 0.112465E+10 | -0.103624E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88407495.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131867E+11 | -0.122071E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -979673594.8 | 59.00 | 0.00 | 0.00 |
Minimum of Months | 0.101937E+10 | -0.113140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88475614.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.121936E+10 | -940059327.2 | 0.00 | 0.00 | 744.00 | 0.00 | -71638129.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 1.00 | 0.88 | 31-JAN-11:30 | 28.30 | 0.00 | 0.00 | 0.00 | 21.17 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.97 | 0.75 | 19-FEB-13:30 | 66.51 | 0.00 | 0.00 | 0.00 | 50.47 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.86 | 0.38 | 24-MAR-12:30 | 125.64 | 0.00 | 0.00 | 2.67 | 96.28 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.78 | 0.26 | 14-APR-11:20 | 162.80 | 0.00 | 0.00 | 32.50 | 126.56 | 0.00 | 0.00 | 9.00 |
May | 545.00 | 0.76 | 0.26 | 03-MAY-11:20 | 357.77 | 0.00 | 0.00 | 85.50 | 361.83 | 0.00 | 0.00 | 29.00 |
June | 583.50 | 0.72 | 0.26 | 01-JUN-11:09 | 1089.58 | 0.00 | 0.00 | 149.83 | 358.32 | 0.00 | 0.00 | 62.00 |
July | 562.83 | 0.73 | 0.26 | 02-JUL-10:20 | 440.82 | 0.00 | 0.00 | 120.50 | 365.56 | 0.00 | 0.00 | 66.67 |
August | 467.17 | 0.77 | 0.26 | 01-AUG-11:20 | 170.45 | 0.00 | 0.00 | 42.00 | 193.19 | 0.00 | 0.00 | 18.67 |
September | 356.33 | 0.86 | 0.38 | 01-SEP-10:39 | 128.40 | 0.00 | 0.00 | 1.83 | 97.03 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.94 | 0.75 | 01-OCT-09:20 | 88.29 | 0.00 | 0.00 | 0.00 | 64.88 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 1.00 | 0.88 | 01-NOV-12:39 | 38.97 | 0.00 | 0.00 | 0.00 | 28.90 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 1.00 | 1.00 | 04-DEC-10:50 | 9.12 | 0.00 | 0.00 | 0.00 | 6.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.81 | 335.66 | 0.00 | 0.00 | 434.83 | 211.26 | 0.00 | 0.00 | 185.33 | ||
Minimum of Months | 71.17 | 0.72 | 0.26 | 9.12 | 0.00 | 0.00 | 0.00 | 6.83 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 1.00 | 1.00 | 1089.58 | 0.00 | 0.00 | 149.83 | 365.56 | 0.00 | 0.00 | 66.67 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.99 | 0.75 | 29-JAN-11:09 | 33.33 | 5.76 | 0.00 | 0.00 | 27.76 | 6.25 | 0.00 | 0.00 |
February | 205.83 | 0.87 | 0.51 | 21-FEB-11:50 | 79.24 | 11.01 | 0.00 | 0.00 | 65.67 | 11.62 | 0.00 | 0.00 |
March | 329.50 | 0.65 | 0.26 | 05-MAR-10:00 | 152.39 | 14.88 | 25.50 | 90.50 | 127.27 | 15.60 | 46.50 | 58.33 |
April | 421.83 | 0.56 | 0.26 | 01-APR-09:00 | 197.70 | 15.99 | 80.50 | 187.83 | 408.24 | 18.37 | 105.00 | 152.17 |
May | 545.00 | 0.56 | 0.26 | 01-MAY-07:19 | 208.97 | 15.83 | 124.67 | 258.50 | 172.88 | 16.56 | 150.33 | 194.50 |
June | 583.50 | 0.54 | 0.26 | 01-JUN-07:40 | 309.01 | 16.88 | 142.50 | 318.00 | 213.99 | 16.45 | 153.83 | 240.33 |
July | 562.83 | 0.54 | 0.26 | 01-JUL-09:09 | 228.04 | 15.90 | 122.17 | 295.33 | 771.23 | 16.55 | 144.00 | 229.33 |
August | 467.17 | 0.55 | 0.26 | 01-AUG-07:19 | 204.06 | 15.82 | 83.67 | 214.00 | 291.10 | 16.53 | 108.83 | 164.00 |
September | 356.33 | 0.64 | 0.26 | 01-SEP-08:20 | 254.12 | 14.58 | 30.33 | 104.50 | 128.29 | 15.26 | 44.83 | 53.67 |
October | 265.50 | 0.79 | 0.38 | 01-OCT-09:50 | 161.05 | 12.25 | 0.00 | 13.50 | 86.18 | 12.83 | 0.00 | 0.00 |
November | 135.83 | 0.96 | 0.63 | 01-NOV-13:20 | 45.06 | 6.80 | 0.00 | 0.00 | 36.74 | 7.36 | 0.00 | 0.00 |
December | 71.17 | 1.00 | 1.00 | 04-DEC-10:50 | 10.68 | 0.98 | 0.00 | 0.00 | 8.83 | 1.23 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.63 | 200.24 | 14.51 | 609.33 | 1482.17 | 269.92 | 15.19 | 753.33 | 1092.33 | ||
Minimum of Months | 71.17 | 0.54 | 0.26 | 10.68 | 0.98 | 0.00 | 0.00 | 8.83 | 1.23 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 1.00 | 1.00 | 309.01 | 16.88 | 142.50 | 318.00 | 771.23 | 18.37 | 153.83 | 240.33 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169936E+11 | 30315.80 | 01-JAN-10:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138487E+11 | 30315.80 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133186E+11 | 30315.80 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.565115E+10 | 30315.80 | 01-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.639786E+09 | 30315.80 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10517509.85 | 10195.90 | 02-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 53299487.26 | 12600.49 | 31-AUG-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163438E+10 | 30315.80 | 18-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.808116E+10 | 30315.80 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143815E+11 | 30315.80 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168614E+11 | 30315.80 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.914741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.169936E+11 | 30315.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.544088E+11 | 95780.97 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.435799E+11 | 95780.97 | 01-FEB-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357365E+11 | 95780.97 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133745E+11 | 95780.97 | 01-APR-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95674402.01 | 18486.01 | 28-MAY-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108760E+10 | 51074.81 | 30-SEP-04:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205271E+11 | 95780.97 | 13-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.441144E+11 | 95780.97 | 01-NOV-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.552428E+11 | 95780.97 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.552428E+11 | 95780.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141656E+12 | 101852.77 | 02-JAN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117757E+12 | 101852.77 | 01-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113022E+12 | 101852.77 | 02-MAR-00:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.488283E+11 | 101852.77 | 01-APR-18:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49026860.81 | 8712.43 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.608206E+11 | 93185.49 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.950452E+11 | 98219.54 | 10-NOV-01:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139312E+12 | 101852.77 | 01-DEC-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.716490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141656E+12 | 101852.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 28.10 | 28.10 | 0.05 | 22-APR-16:00 | 0.05 | 0.00 |
May | 0.00 | 0.00 | 22981580.97 | 22981580.97 | 2291.05 | 31-MAY-16:00 | 2291.05 | 0.00 |
June | 0.00 | 0.00 | 0.133434E+10 | 0.128486E+10 | 15654.92 | 24-JUN-07:02 | 10763.41 | 0.00 |
July | 0.00 | 0.00 | 0.276396E+10 | 0.256151E+10 | 16364.53 | 08-JUL-07:02 | 10556.00 | 0.00 |
August | 0.00 | 0.00 | 0.114326E+10 | 0.106230E+10 | 15760.94 | 05-AUG-07:02 | 11590.53 | 0.00 |
September | 0.00 | 0.00 | 32.44 | 32.44 | 0.02 | 09-SEP-17:00 | 0.02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.526454E+10 | 0.493166E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.276396E+10 | 0.256151E+10 | 16364.53 | 11590.53 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.603960E+09 | 0.594572E+09 | 42202.73 | 20-JUN-17:23 | 42202.73 | 0.00 |
July | 0.00 | 0.00 | 0.202414E+10 | 0.200494E+10 | 44713.01 | 29-JUL-19:33 | 42082.21 | 0.00 |
August | 0.00 | 0.00 | 0.286936E+09 | 0.284333E+09 | 42197.65 | 11-AUG-17:35 | 42197.65 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.291503E+10 | 0.288385E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202414E+10 | 0.200494E+10 | 44713.01 | 42202.73 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.628103E+09 | 0.08 | 234.88 | 01-JAN-00:02 | 0.08 |
February | 0.553977E+09 | 0.08 | 234.88 | 01-FEB-00:02 | 0.08 |
March | 0.581504E+09 | 0.07 | 234.88 | 01-MAR-00:02 | 0.08 |
April | 0.309753E+09 | 0.04 | 234.88 | 01-APR-00:10 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 3452666.40 | 0.00 | 234.88 | 30-SEP-04:30 | 0.08 |
October | 0.429934E+09 | 0.05 | 234.88 | 01-OCT-00:10 | 0.08 |
November | 0.600341E+09 | 0.08 | 234.88 | 01-NOV-00:10 | 0.08 |
December | 0.629090E+09 | 0.08 | 234.88 | 01-DEC-00:02 | 0.08 |
Annual Sum or Average | 0.373616E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.629090E+09 | 0.08 | 234.88 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.124206E+10 | 0.71 | 1110.83 | 02-JAN-08:50 | 0.93 |
February | 0.113569E+10 | 0.69 | 1110.83 | 01-FEB-14:40 | 0.93 |
March | 0.128848E+10 | 0.66 | 1110.83 | 01-MAR-16:10 | 0.93 |
April | 0.113705E+10 | 0.46 | 1110.83 | 01-APR-07:20 | 0.93 |
May | 0.114466E+10 | 0.36 | 1110.83 | 01-MAY-06:50 | 0.92 |
June | 0.114371E+10 | 0.36 | 1110.83 | 07-JUN-14:20 | 0.92 |
July | 0.109972E+10 | 0.34 | 1110.83 | 01-JUL-07:08 | 0.92 |
August | 0.118770E+10 | 0.37 | 1110.83 | 01-AUG-16:10 | 0.92 |
September | 0.110193E+10 | 0.36 | 1110.83 | 01-SEP-06:30 | 0.92 |
October | 0.113926E+10 | 0.46 | 1110.83 | 02-OCT-08:50 | 0.92 |
November | 0.114578E+10 | 0.65 | 1110.83 | 02-NOV-06:20 | 0.93 |
December | 0.122220E+10 | 0.70 | 1110.83 | 02-DEC-14:10 | 0.93 |
Annual Sum or Average | 0.139882E+11 | 0.51 | |||
Minimum of Months | 0.109972E+10 | 0.34 | 1110.83 | 0.92 | |
Maximum of Months | 0.128848E+10 | 0.71 | 1110.83 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.330030E+10 | 0.78 | 2451.90 | 04-JAN-15:40 | 0.90 |
February | 0.301234E+10 | 0.78 | 2451.90 | 02-FEB-07:50 | 0.90 |
March | 0.328697E+10 | 0.77 | 2451.90 | 01-MAR-14:00 | 0.90 |
April | 0.273034E+10 | 0.59 | 2451.90 | 05-APR-10:00 | 0.90 |
May | 0.252738E+10 | 0.35 | 2451.90 | 01-MAY-06:03 | 0.89 |
June | 0.253006E+10 | 0.35 | 2451.90 | 22-JUN-11:50 | 0.89 |
July | 0.245208E+10 | 0.33 | 2451.90 | 01-JUL-06:10 | 0.88 |
August | 0.262378E+10 | 0.35 | 2451.90 | 10-AUG-14:10 | 0.89 |
September | 0.245681E+10 | 0.39 | 2451.90 | 28-SEP-06:10 | 0.89 |
October | 0.284277E+10 | 0.68 | 2451.90 | 03-OCT-06:03 | 0.89 |
November | 0.305119E+10 | 0.77 | 2451.90 | 06-NOV-11:00 | 0.90 |
December | 0.327561E+10 | 0.79 | 2451.90 | 16-DEC-10:20 | 0.90 |
Annual Sum or Average | 0.340896E+11 | 0.58 | |||
Minimum of Months | 0.245208E+10 | 0.33 | 2451.90 | 0.88 | |
Maximum of Months | 0.330030E+10 | 0.79 | 2451.90 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.124206E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.113569E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.128848E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.113705E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.115031E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.146177E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.175564E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.145950E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.110193E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.113926E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.114578E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.122220E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.152397E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.110193E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.175564E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.330030E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.301234E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.328697E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.273034E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.252738E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.268447E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.296555E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.269653E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.245681E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.284277E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.305119E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.327561E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.348303E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.245681E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.330030E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.124206E+10 | 0.00 | 0.169936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113569E+10 | 0.00 | 0.138487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128848E+10 | 0.00 | 0.133186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113705E+10 | 28.10 | 0.565115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114466E+10 | 22981580.97 | 0.639786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114371E+10 | 0.133434E+10 | 10517509.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109972E+10 | 0.276396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118770E+10 | 0.114326E+10 | 53299487.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110193E+10 | 32.44 | 0.163438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113926E+10 | 0.00 | 0.808116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114578E+10 | 0.00 | 0.143815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122220E+10 | 0.00 | 0.168614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139882E+11 | 0.526454E+10 | 0.914741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128848E+10 | 0.276396E+10 | 0.169936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.330030E+10 | 0.00 | 0.544088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.301234E+10 | 0.00 | 0.435799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.328697E+10 | 0.00 | 0.357365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.273034E+10 | 0.00 | 0.133745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.252738E+10 | 0.00 | 95674402.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.253006E+10 | 0.603960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.245208E+10 | 0.202414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.262378E+10 | 0.286936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.245681E+10 | 0.00 | 0.108760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.284277E+10 | 0.00 | 0.205271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.305119E+10 | 0.00 | 0.441144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327561E+10 | 0.00 | 0.552428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.340896E+11 | 0.291503E+10 | 0.268167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.245208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.330030E+10 | 0.202414E+10 | 0.552428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.124206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113705E+10 | 0.00 | 0.00 | 0.00 | 7.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114466E+10 | 0.00 | 0.00 | 0.00 | 5656224.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114371E+10 | 0.00 | 0.00 | 0.00 | 0.318062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109972E+10 | 0.00 | 0.00 | 0.00 | 0.655915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118770E+10 | 0.00 | 0.00 | 0.00 | 0.271804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110193E+10 | 0.00 | 0.00 | 0.00 | 8.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139882E+11 | 0.00 | 0.00 | 0.00 | 0.125144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128848E+10 | 0.00 | 0.00 | 0.00 | 0.655915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.330030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.301234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.328697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.273034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.252738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.253006E+10 | 0.00 | 0.00 | 0.00 | 0.154414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.245208E+10 | 0.00 | 0.00 | 0.00 | 0.513469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.262378E+10 | 0.00 | 0.00 | 0.00 | 72749362.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.245681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.284277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.305119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.340896E+11 | 0.00 | 0.00 | 0.00 | 0.740632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.245208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.330030E+10 | 0.00 | 0.00 | 0.00 | 0.513469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 678895.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451164E+10 | 0.00 | 0.00 | 0.12 |
February | 700860.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364411E+10 | 0.00 | 0.00 | 0.13 |
March | 1229194.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369108E+10 | 0.00 | 0.00 | 0.13 |
April | 0.268663E+09 | 0.00 | 0.00 | 186.05 | 0.00 | 0.188632E+10 | 2171912.08 | 0.00 | 0.13 |
May | 0.738863E+09 | 0.00 | 0.00 | 668048.01 | 0.00 | 0.210400E+09 | 0.886579E+09 | 0.00 | 0.21 |
June | 93020270.16 | 4930423.43 | 0.00 | 5102211.26 | 0.00 | 763590.29 | 0.332752E+10 | 0.00 | 0.62 |
July | 34126568.07 | 19557638.37 | 0.00 | 6539436.66 | 0.00 | 0.00 | 0.286785E+10 | 0.00 | 0.65 |
August | 0.218659E+09 | 165835.59 | 0.00 | 5075004.88 | 0.00 | 9830117.12 | 0.327416E+10 | 0.00 | 0.56 |
September | 0.961215E+09 | 0.00 | 0.00 | 243294.64 | 0.00 | 0.684897E+09 | 0.345874E+09 | 0.00 | 0.15 |
October | 90369698.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271026E+10 | 0.00 | 0.00 | 0.12 |
November | 800536.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428152E+10 | 0.00 | 0.00 | 0.12 |
December | 1560492.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475436E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.240989E+10 | 24653897.39 | 0.00 | 17628181.49 | 0.00 | 0.263852E+11 | 0.107042E+11 | 0.00 | 0.26 |
Minimum of Months | 678895.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.961215E+09 | 19557638.37 | 0.00 | 6539436.66 | 0.00 | 0.475436E+10 | 0.332752E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156610E+11 | 0.00 | 0.00 | 0.17 |
February | 0.161071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107503E+11 | 0.00 | 0.00 | 0.18 |
March | 0.450675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760370E+10 | 0.00 | 0.00 | 0.19 |
April | 0.499179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162829E+10 | 0.00 | 0.00 | 0.18 |
May | 0.462424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
June | 0.343994E+10 | 0.00 | 0.00 | 2659957.99 | 0.00 | 0.00 | 0.263145E+10 | 0.00 | 0.29 |
July | 0.162969E+10 | 11203472.59 | 0.00 | 6774363.67 | 0.00 | 0.00 | 0.520391E+10 | 0.00 | 0.39 |
August | 0.404100E+10 | 0.00 | 0.00 | 3057045.81 | 0.00 | 0.00 | 0.329221E+10 | 0.00 | 0.29 |
September | 0.616449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25243134.24 | 0.00 | 0.00 | 0.18 |
October | 0.528006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359124E+10 | 0.00 | 0.00 | 0.17 |
November | 0.722652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142387E+11 | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167583E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.371254E+11 | 11203472.59 | 0.00 | 12491367.46 | 0.00 | 0.702568E+11 | 0.111276E+11 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.616449E+10 | 11203472.59 | 0.00 | 6774363.67 | 0.00 | 0.167583E+11 | 0.520391E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:37
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.133526E+12 | 0.830916E+11 | 0.00 | 0.202874E+11 | 0.655154E+11 |
February | 0.117444E+11 | 0.683060E+11 | 0.00 | 0.160058E+11 | 0.539445E+11 |
March | 0.406239E+12 | 0.940896E+11 | 0.00 | 0.158028E+11 | 0.498023E+11 |
April | 0.779128E+12 | 0.706143E+11 | 0.00 | 0.877723E+10 | 0.208365E+11 |
May | 0.101175E+13 | 0.365964E+11 | 0.00 | 0.646075E+10 | 0.387994E+09 |
June | 0.106643E+13 | 0.306746E+11 | 0.00 | 0.950222E+10 | 0.241610E+10 |
July | 0.977618E+12 | 0.331758E+11 | 0.00 | 0.971956E+10 | 0.595749E+10 |
August | 0.725403E+12 | 0.424384E+11 | 0.00 | 0.108438E+11 | 0.180145E+10 |
September | 0.325441E+12 | 0.339293E+11 | 0.00 | 0.818197E+10 | 0.134333E+10 |
October | 0.758807E+11 | 0.689114E+11 | 0.00 | 0.116719E+11 | 0.281604E+11 |
November | -0.892245E+11 | 0.349480E+11 | 0.00 | 0.192437E+11 | 0.489142E+11 |
December | -0.159032E+12 | 0.685960E+11 | 0.00 | 0.215142E+11 | 0.652683E+11 |
Annual Sum or Average | 0.499785E+13 | 0.665371E+12 | 0.00 | 0.158011E+12 | 0.344348E+12 |
Minimum of Months | -0.159032E+12 | 0.306746E+11 | 0.00 | 0.646075E+10 | 0.387994E+09 |
Maximum of Months | 0.106643E+13 | 0.940896E+11 | 0.00 | 0.215142E+11 | 0.655154E+11 |