Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43

Tabular Output Report in Format: HTML

Building: Warehouse

Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904

Simulation Timestamp: 2023-10-16 10:43:54


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 444.93 92.02 92.02
Net Site Energy 444.93 92.02 92.02
Total Source Energy 1405.91 290.77 290.77
Net Source Energy 1405.91 290.77 290.77


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4835.13
Net Conditioned Building Area 4835.13
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 1.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 10.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 150.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 92.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 139.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 25.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 24.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.61
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 443.40 1.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.61
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 1.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 10.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 150.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 92.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 139.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 25.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 24.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.61
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 1.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 10.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 150.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 92.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 139.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 25.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 24.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.61
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 12.58 0.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01
Other 28.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 91.70 0.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 12.58 0.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01
Other 28.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 91.70 0.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 443.400 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 443.400 100.00
     
Total On-Site and Utility Electric Sources 443.400 100.00
Total Electricity End Uses 443.400 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 51.61 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 51.61 100.00
Total Water End Uses 51.61 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.33
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 1930.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

| Environment |

ZoneCoolingSummaryMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

ZoneHeatingSummaryMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

ZoneElectricSummaryMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

SpaceGainsMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

PeakSpaceGainsMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

SpaceGainComponentsAtCoolingPeakMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

ComfortReportSimple55Monthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

OccupantComfortDataSummaryMonthly

| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |

DXReportMonthly

| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |

WindowReportMonthly

| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |

WindowEnergyReportMonthly

| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |

WindowZoneSummaryMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

WindowEnergyZoneSummaryMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |

CoilReportMonthly

| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |

FanReportMonthly

| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |

ZoneTemperatureOscillationReportMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-OFFICE | PSZ-FINE STORAGE |

AirLoopSystemComponentLoadsMonthly

| PSZ-OFFICE | PSZ-FINE STORAGE |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-OFFICE | PSZ-FINE STORAGE |

MechanicalVentilationLoadsMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
RunPeriod RUNPERIOD 1
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Latitude [deg] 32.58
Longitude [deg] -117.0
Elevation [m] 159.00
Time Zone -8.0
North Axis Angle [deg] 90.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 2496.99 858.34 390.15 858.34 390.15
Above Ground Wall Area [m2] 2496.99 858.34 390.15 858.34 390.15
Window Opening Area [m2] 17.66 6.51 0.00 0.00 11.15
Gross Window-Wall Ratio [%] 0.71 0.76 0.00 0.00 2.86
Above Ground Window-Wall Ratio [%] 0.71 0.76 0.00 0.00 2.86


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 2496.99 858.34 390.15 858.34 390.15
Above Ground Wall Area [m2] 2496.99 858.34 390.15 858.34 390.15
Window Opening Area [m2] 17.66 6.51 0.00 0.00 11.15
Gross Window-Wall Ratio [%] 0.71 0.76 0.00 0.00 2.86
Above Ground Window-Wall Ratio [%] 0.71 0.76 0.00 0.00 2.86


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 4598.25
Skylight Area [m2] 68.38
Skylight-Roof Ratio [%] 1.49


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
ZONE1 OFFICE 236.88 Yes Yes 1010.76 1.00 149.56 0.00 17.66 17.66 8.9961 18.58 8.0737
ZONE2 FINE STORAGE 1393.41 Yes Yes 2953.02 1.00 760.80 0.00 0.00 0.00 9.2031 46.45 0.0000
ZONE3 BULK STORAGE 3204.84 Yes Yes 35277.63 1.00 1586.63 0.00 0.00 0.00 5.6188 46.45 2.5587
Total 4835.13     39241.41   2496.99 0.00 17.66 17.66 6.8172 43.27 2.0915
Conditioned Total 4835.13     39241.41   2496.99 0.00 17.66 17.66 6.8172 43.27 2.0915
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
ZONE1 OFFICE 236.88 Yes Yes 1.00 ZONE1 OFFICE GENERAL ZONE1 OFFICE 8.9961 18.58 8.0737  
ZONE2 FINE STORAGE 1393.41 Yes Yes 1.00 ZONE2 FINE STORAGE GENERAL ZONE2 FINE STORAGE 9.2031 46.45 0.0000  
ZONE3 BULK STORAGE 3204.84 Yes Yes 1.00 ZONE3 BULK STORAGE GENERAL ZONE3 BULK STORAGE 5.6188 46.45 2.5587  
Total 4835.13             6.8172 21.63 2.0915  
Conditioned Total 4835.13             6.8172 21.63 2.0915  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 4835.13 4835.13 0.00 0.00 6.8172 43.27 2.0915
Total 4835.13 4835.13 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 05-DEC-16:49 02-JAN-07:10 - - - - - - - - - - 02-JAN-12:09
Heating 0.00 17274.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 355.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 14003.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 6958.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 10112.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2157.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1601.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 35188.43 17274.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 17274.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 355.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 14003.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 6958.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 10112.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 2157.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 1601.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 1.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 32.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 477.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 293.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 441.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 82.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 78.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1404.25 1.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 6.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 98.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 91.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 17.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 16.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 290.43 0.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 6.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 98.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 91.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 17.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 16.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 290.43 0.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ZONE1 OFFICE DIRECT AIR 1.05
ZONE2 FINE STORAGE DIRECT AIR 2.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:UnitHeater

Design Size Maximum Supply Air Flow Rate [m3/s]
ZONE3 BULK STORAGE UNIT HEATER 0.976836
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
ZONE3UNITHEATER ZONE3HIRADIANT FAN 0.976836
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL 39235.43
PSZ-OFFICE HEATING COIL 25858.40
PSZ-FINE STORAGE HEATING COIL 73076.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:HighTemperatureRadiant

User-Specified Heating Design Capacity [W]
ZONE3 BULK STORAGE HIRADIANT 27379.34
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-OFFICE 1.05 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.05
PSZ-FINE STORAGE 2.31 2.31 2.31 2.31 2.31 2.31 1.00 1.00 2.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-OFFICE_OA_CONTROLLER 1.05 0.102285
PSZ-FINE STORAGE_OA_CONTROLLER 2.31 0.424711
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
PSZ-OFFICE_ADDAQ SUPPLY FAN 1.05 1167.05
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN 2.31 2475.42
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] User-Specified Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Design Size Maximum Supply Air Temperature [C] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-OFFICE_UNITARY_PACKAGE_DX 1.05 1.05 1.05 1.05 17990.76 25858.40 40.00 1.00
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX 2.31 2.31 2.31 1.53 47969.37 73076.21 40.00 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
PSZ-OFFICE COOLING COIL 1.05 0.527048 0.702733 17990.76 8995.38 0.800580 0.800580
PSZ-FINE STORAGE COOLING COIL 2.31 1.16 1.54 47969.37 23984.69 0.762500 0.762500
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
OFFICE FRONT WALL OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 |
OFFICE LEFT WALL OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 |
FINE STORAGE FRONT WALL FINE STORAGE OVERHEAD DOOR1 |
FINE STORAGE RIGHT WALL FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR |
FINE STORAGE LEFT WALL FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR |
FINE STORAGE ROOF FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 |
BULK STORAGE RIGHT WALL BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 |
BULK STORAGE REAR WALL BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 |
BULK STORAGE LEFT WALL BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 |
BULK STORAGE ROOF SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.80 14.30 13.60 13.20 13.30 12.60 15.30 15.60 17.70 19.40 19.70 18.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 32.58 -116.98 -8.00 159.00 99429 1.1818


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.00 7.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 Warehouse 90.000 Urban 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.220 370.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 3 102 78


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 ZONE1 OFFICE 0.0 0.00 0.00 0.00 4.57 -12.95 2.13 1 1 1 0.00 9.14 -25.91 5.60E-016 0.00 4.27 4.27 1010.76 TARP TARP 236.88 149.56 128.00 17.66 6 6 0 Yes
2 ZONE2 FINE STORAGE 0.0 0.00 0.00 0.00 14.29 -22.82 4.51 1 1 1 0.00 30.48 -45.72 1.87E-015 0.00 8.53 7.81 2953.02 TARP TARP 1393.41 760.80 727.17 20.81 11 20 0 Yes
3 ZONE3 BULK STORAGE 0.0 0.00 0.00 0.00 65.53 -22.86 4.27 1 1 1 30.48 100.58 -45.72 6.16E-015 0.00 8.53 8.53 35277.63 TARP TARP 3204.84 1586.63 1471.35 47.57 6 52 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 ZONE1 OFFICE 236.88 12.7 18.581 5.382E-002 8.996 8.074 0.000 0.000 0.000 0.000 17.070 No
2 ZONE2 FINE STORAGE 1393.41 30.0 46.447 2.153E-002 9.203 0.000 0.000 0.000 0.000 0.000 9.203 No
3 ZONE3 BULK STORAGE 3204.84 69.0 46.447 2.153E-002 5.619 2.559 0.000 0.000 0.000 0.000 8.177 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 OFFICE PEOPLE BLDG_OCC_SCH ZONE1 OFFICE 236.88 12.7 12.7 5.382E-002 18.581 0.300 0.700 AutoCalculate OFFICE ACTIVITY SCHEDULE No 3.8200E-008 0 13
2 ZONE2 FINE STORAGEPEOPLE BLDG_OCC_SCH ZONE2 FINE STORAGE 1393.41 30.0 30.0 2.153E-002 46.447 0.300 0.700 AutoCalculate ZONE2 FINE STORAGE ACTIVITY SCHEDULE No 3.8200E-008 0 30
3 ZONE3 BULK STORAGEPEOPLE BLDG_OCC_SCH ZONE3 BULK STORAGE 3204.84 69.0 69.0 2.153E-002 46.447 0.300 0.700 AutoCalculate ZONE3 BULK STORAGE ACTIVITY SCHEDULE No 3.8200E-008 0 69


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 OFFICE LIGHTS LTG_SCH_OFFICE ZONE1 OFFICE 236.88 12.7 2131.000 8.996 167.154 0.000 0.370 0.180 0.450 1.000 LightsWired 0.000 2131.000
2 FINE STORAGE AREA LIGHTS LTG_SCH_FINE_STORAGE ZONE2 FINE STORAGE 1393.41 30.0 12823.730 9.203 427.458 0.000 0.420 0.180 0.400 1.000 LightsWired 0.000 12823.730
3 BULK STORAGE AREA LIGHTS LTG_SCH_BULK_STORAGE ZONE3 BULK STORAGE 3204.84 69.0 18007.220 5.619 260.974 0.000 0.420 0.180 0.400 1.000 LightsWired 0.000 18007.220


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 OFFICE PLUG LOAD OFFICE_PLUG_SCH ZONE1 OFFICE 236.88 12.7 1912.500 8.074 150.015 0.000 0.000 0.000 1.000 MiscPlug 0.000 1912.500
2 BULK STORAGE PLUG LOAD BULK STORAGE PLUG SCHEDULE ZONE3 BULK STORAGE 3204.84 69.0 8200.120 2.559 118.842 0.000 0.000 0.000 1.000 MiscPlug 0.000 8200.120


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 NONRES_ROOF 16 2 2 0.167 0.2043 0.750 0.900 0.450 0.700 Smooth
2 SEMIHEATED_ROOF 18 2 2 0.167 0.2043 0.750 0.900 0.450 0.700 Smooth
3 NONRES_EXT_WALL_GRD 19 3 4 0.167 0.5832 0.900 0.900 0.700 0.700 Smooth
4 SEMIHEATED_EXT_WALL_GRD 25 3 4 0.167 0.5832 0.900 0.900 0.700 0.700 Smooth
5 SWINGING DOOR_CON 41 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
6 SWINGING DOOR_SEMI 42 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
7 OVERHEAD DOOR_SEMI 44 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
8 OVERHEAD DOOR_CON 45 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
9 BULK STORAGE PRODUCTS 46 1 18 0.500 0.5914 0.900 0.900 0.700 0.700 Rough
10 INTERIOR WALL 47 5 5 2.167 0.7747 0.900 0.900 0.700 0.700 Smooth
11 INSULATEDCEILING 48 2 3 0.333 10.06 0.900 0.900 0.700 0.700 MediumRough
12 OFFICEFLOOR_FFACTOR 49 2 7 0.167 0.1926 0.000 0.900 0.000 0.700 MediumRough
13 FINESTORAGEFLOOR_FFACTOR 50 2 7 0.167 0.7922E-01 0.000 0.900 0.000 0.700 MediumRough
14 BULKSTORAGEFLOOR_FFACTOR 51 2 7 0.167 0.7415E-01 0.000 0.900 0.000 0.700 MediumRough
15 iz-INTERIOR WALL 52 5 5 2.167 0.7747 0.900 0.900 0.700 0.700 MediumSmooth
16 iz-SEMIHEATED_EXT_WALL_GRD 53 3 4 0.167 0.5832 0.900 0.900 0.700 0.700 MediumSmooth
17 iz-INSULATEDCEILING 54 2 3 0.333 10.06 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 F08 METAL ROOF SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
2 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.894
3 F08 METAL ROOF SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
4 SEMIHEATED_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.894
5 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
6 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.615
7 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.615
10 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
11 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
12 OPAQUE DOOR PANEL_SEMI 0.0000 0.000 0.000 0.000 0.2887
13 OVERHEAD DOOR_SEMI PANEL 0.0000 0.000 0.000 0.000 0.8346
14 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
15 BULK STORAGE PRODUCTS MATERIAL 2.4384 1.442 200.231 836.800 1.691
16 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
17 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
18 INTERIOR WALL ADDI INSUL 0.0000 0.043 22.426 836.800 0.5871E-06
19 STEEL FRAME/CAVITY 0.0889 0.084 641.379 502.080 1.057
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 INTERIOR WALL ADDI INSUL 0.0000 0.043 22.426 836.800 0.5871E-06
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 5.116
24 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
25 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 12.55
26 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
27 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 13.41
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
30 STEEL FRAME/CAVITY 0.0889 0.084 641.379 502.080 1.057
31 INTERIOR WALL ADDI INSUL 0.0000 0.043 22.426 836.800 0.5871E-06
32 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
33 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
34 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
35 SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.615
36 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
37 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
38 INTERIOR WALL ADDI INSUL 0.0000 0.043 22.426 836.800 0.5871E-06


CTF

Time Outside Cross Inside Flux (except final one)
1 2 0.93400083E-12 0.71827744E-17 0.33026303E-17 0.0000000
2 1 -5.2160660 0.53236032E-04 -0.78408200E-04 0.17906231E-12
3 0 5.4203831 0.20426382 0.20439547  
4 2 0.93400083E-12 0.71827744E-17 0.33026303E-17 0.0000000
5 1 -5.2160660 0.53236032E-04 -0.78408200E-04 0.17906231E-12
6 0 5.4203831 0.20426382 0.20439547  
7 4 0.76147947E-12 0.16972320E-15 -0.23941589E-14 0.12030052E-15
8 3 -0.37802266E-03 0.40617527E-06 -0.54770175E-04 0.14612398E-12
9 2 1.7236739 0.89444888E-02 1.1283884 -0.72472748E-04
10 1 -7.1497137 0.23277257 -17.021073 0.33034766
11 0 5.8169840 0.14884880 16.283305  
12 4 0.76147947E-12 0.16972320E-15 -0.23941589E-14 0.12030052E-15
13 3 -0.37802266E-03 0.40617527E-06 -0.54770175E-04 0.14612398E-12
14 2 1.7236739 0.89444888E-02 1.1283884 -0.72472748E-04
15 1 -7.1497137 0.23277257 -17.021073 0.33034766
16 0 5.8169840 0.14884880 16.283305  
17 1 0.0000000 0.0000000 -0.0000000 -0.0000000
18 0 3.4637404 3.4637404 3.4637404  
19 1 0.0000000 0.0000000 -0.0000000 -0.0000000
20 0 3.4637404 3.4637404 3.4637404  
21 1 0.0000000 0.0000000 -0.0000000 -0.0000000
22 0 1.1981135 1.1981135 1.1981135  
23 1 0.0000000 0.0000000 -0.0000000 -0.0000000
24 0 1.1981135 1.1981135 1.1981135  
25 18 0.12003549E-12 -0.36149852E-21 0.11999160E-12 -0.69171859E-14
26 17 -0.26702818E-10 0.22043783E-17 -0.26702965E-10 0.15647703E-11
27 16 0.26199194E-08 0.46087291E-16 0.26199192E-08 -0.15597178E-09
28 15 -0.14918350E-06 -0.27301975E-15 -0.14918350E-06 0.90448703E-08
29 14 0.54929883E-05 0.10218664E-13 0.54929883E-05 -0.34010628E-06
30 13 -0.13812653E-03 0.13886261E-11 -0.13812653E-03 0.87613853E-05
31 12 0.24466257E-02 0.76740851E-10 0.24466257E-02 -0.15954016E-03
32 11 -0.31099262E-01 0.20215154E-08 -0.31099262E-01 0.20926433E-02
33 10 0.28694928 0.26940884E-07 0.28694928 -0.20002833E-01
34 9 -1.9353699 0.18750649E-06 -1.9353699 0.14030665
35 8 9.5767226 0.68900696E-06 9.5767226 -0.72468789
36 7 -34.784653 0.13258951E-05 -34.784653 2.7565275
37 6 92.438040 0.12976568E-05 92.438040 -7.6923258
38 5 -178.18614 0.60985027E-06 -178.18614 15.604270
39 4 245.02895 0.12430126E-06 245.02895 -22.615757
40 3 -233.27712 0.91617964E-08 -233.27712 22.714127
41 2 145.61910 0.16319500E-09 145.61910 -14.964058
42 1 -53.478849 0.26256209E-11 -53.478849 5.7996512
43 0 8.7411694 -0.39181092E-12 8.7411694  
44 5 -0.68112304E-12 0.61645773E-13 -0.20199983E-12 0.95058421E-15
45 4 0.71499529E-06 0.73238302E-07 0.28552134E-06 -0.33479849E-12
46 3 -0.58529659E-02 0.62218017E-03 -0.21917430E-02 0.29169470E-06
47 2 1.2914758 0.88958368E-01 0.40042664 -0.15953103E-02
48 1 -8.6129398 0.38073474 -3.1694576 0.22491773
49 0 7.9317533 0.13060792 3.3724149  
50 3 -0.49407978E-15 0.44230608E-16 -0.53860842E-16 0.0000000
51 2 0.54884850E-03 0.14309697E-03 0.26444340E-03 -0.39739853E-15
52 1 -3.9407614 2.0053241 -3.6132068 0.31450573E-03
53 0 13.994357 8.0573072 13.672611  
54 7 -0.21936956E-08 -0.76657665E-15 0.52174295E-14 -0.76362207E-16
55 6 0.54250385E-05 0.36865710E-08 0.31904099E-02 -0.26763832E-04
56 5 -0.38781740E-03 0.21819055E-05 -0.22375527 0.19564212E-02
57 4 0.89061350E-02 0.99303795E-04 4.8300570 -0.45269896E-01
58 3 -0.78164548E-01 0.78949647E-03 -38.024306 0.39868569
59 2 0.27748674 0.13132576E-02 116.48957 -1.4180145
60 1 -0.40047331 0.39992572E-03 -143.91062 2.0490943
61 0 0.19524127 0.97244710E-05 60.838472  
62 7 -0.53942680E-08 -0.11156834E-13 0.16318657E-14 -0.36257882E-16
63 6 0.25438785E-05 0.15223906E-08 0.31992327E-02 -0.26837845E-04
64 5 -0.16605865E-03 0.89659996E-06 -0.22425660 0.19608463E-02
65 4 0.37075836E-02 0.40698259E-04 4.8384045 -0.45350141E-01
66 3 -0.32199378E-01 0.32283529E-03 -38.071448 0.39920679
67 2 0.11382527 0.53586778E-03 116.58131 -1.4192416
68 1 -0.16395953 0.16275009E-03 -143.96461 2.0499819
69 0 0.79856572E-01 0.39490086E-05 60.838472  
70 7 -0.57660871E-08 -0.13610624E-13 0.89936022E-15 -0.28491615E-16
71 6 0.24333103E-05 0.14269892E-08 0.31996257E-02 -0.26841142E-04
72 5 -0.15663594E-03 0.83977476E-06 -0.22427892 0.19610433E-02
73 4 0.34808858E-02 0.38103208E-04 4.8387759 -0.45353710E-01
74 3 -0.30176241E-01 0.30214868E-03 -38.073544 0.39922996
75 2 0.10659492 0.50136596E-03 116.58539 -1.4192962
76 1 -0.15349297 0.15221123E-03 -143.96701 2.0500213
77 0 0.74745977E-01 0.36906361E-05 60.838472  
78 5 -0.20199983E-12 0.61645773E-13 -0.68112304E-12 0.95058421E-15
79 4 0.28552134E-06 0.73238302E-07 0.71499529E-06 -0.33479849E-12
80 3 -0.21917430E-02 0.62218017E-03 -0.58529659E-02 0.29169470E-06
81 2 0.40042664 0.88958368E-01 1.2914758 -0.15953103E-02
82 1 -3.1694576 0.38073474 -8.6129398 0.22491773
83 0 3.3724149 0.13060792 7.9317533  
84 4 -0.23941589E-14 0.16972320E-15 0.76147947E-12 0.12030052E-15
85 3 -0.54770175E-04 0.40617527E-06 -0.37802266E-03 0.14612398E-12
86 2 1.1283884 0.89444888E-02 1.7236739 -0.72472748E-04
87 1 -17.021073 0.23277257 -7.1497137 0.33034766
88 0 16.283305 0.14884880 5.8169840  
89 3 -0.53860842E-16 0.44230608E-16 -0.49407978E-15 0.0000000
90 2 0.26444340E-03 0.14309697E-03 0.54884850E-03 -0.39739853E-15
91 1 -3.6132068 2.0053241 -3.9407614 0.31450573E-03
92 0 13.672611 8.0573072 13.994357  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.4637_SHGC_SOUTH_0.25 34 1 VerySmooth 2.636 2.636 1.000 0.251    
2 NONRESWINDOW_U_0.4637_SHGC_NORTH_0.25 35 1 VerySmooth 2.636 2.636 1.000 0.251    
3 NONRESWINDOW_U_0.4637_SHGC_EAST_0.25 36 1 VerySmooth 2.636 2.636 1.000 0.251    
4 NONRESWINDOW_U_0.4637_SHGC_WEST_0.25 37 1 VerySmooth 2.636 2.636 1.000 0.251    
5 SKYLIGHT_U_0.9_SHGC_0.6 38 1 VerySmooth 5.108 5.108 1.000 0.601    
6 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 39 1 VerySmooth 5.108 5.108 1.000 0.601    
7 SKYLIGHT DOUBLE CLEAR 43 3 VerySmooth 3.715 3.715 1.000 0.720    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 NONRES WINDOW GLAZING LAYER SOUTH SpectralAverage   2.49037E-002 0.16139 0.61562 0.61562 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11941 1.00000 No
2 NONRES WINDOW GLAZING LAYER NORTH SpectralAverage   2.49037E-002 0.16139 0.61562 0.61562 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11941 1.00000 No
3 NONRES WINDOW GLAZING LAYER EAST SpectralAverage   2.49037E-002 0.16139 0.61562 0.61562 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11941 1.00000 No
4 NONRES WINDOW GLAZING LAYER WEST SpectralAverage   2.49037E-002 0.16139 0.61562 0.61562 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11941 1.00000 No
5 NONRES SKYLIGHT GLAZING LAYER SpectralAverage   2.00000E-003 0.46039 0.10300 0.10300 0.60000 0.13030 0.15164 0.00000 0.84000 0.84000 6.93520E-002 1.00000 No
6 SEMIHEATED SKYLIGHT GLAZING LAYER SpectralAverage   2.00000E-003 0.46039 0.10300 0.10300 0.60000 0.13030 0.15164 0.00000 0.84000 0.84000 6.93520E-002 1.00000 No
7 CLEAR 2.5MM SpectralAverage   2.50000E-003 0.80000 7.50000E-002 7.50000E-002 0.90100 8.10000E-002 8.10000E-002 0.00000 0.84000 0.84000 0.90000 1.00000 No
8 CLEAR 2.5MM SpectralAverage   2.50000E-003 0.80000 7.50000E-002 7.50000E-002 0.90100 8.10000E-002 8.10000E-002 0.00000 0.84000 0.84000 0.90000 1.00000 No


WindowMaterial:Gas

Material Name GasType Thickness {m}
1 AIR 3MM Air 3.200E-003


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 ZONE1 OFFICE 4 0
2 ZONE2 FINE STORAGE 14 0
3 ZONE3 BULK STORAGE 32 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 ZONE1 OFFICE 0  
2 ZONE2 FINE STORAGE 0  
3 ZONE3 BULK STORAGE 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 7.5708E-002 6154.7 1.055 0.5308


FenestrationAssembly

Construction Name Frame and Divider Name NFRC Product Type Assembly U-Factor {W/m2-K} Assembly SHGC Assembly Visible Transmittance
1 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES CurtainWall 4.867 0.602 0.602
2 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED CurtainWall 4.867 0.602 0.602


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 OFFICE INFILTRATION OFFICE INFIL SCHEDULE ZONE1 OFFICE 236.88 12.7 8.518E-002 3.596E-004 5.551E-004 0.303 0.000 0.000 0.224 0.000
2 OFFICE DOOR INFILTRATION INFIL_DOOR_OPENING_SCH ZONE1 OFFICE 236.88 12.7 0.289 1.219E-003 1.882E-003 1.029 1.000 0.000 0.000 0.000
3 FINE STORAGE INFILTRATION FINE SORAGE INFIL SCHEDULE ZONE2 FINE STORAGE 1393.41 30.0 0.433 3.110E-004 1.981E-004 0.528 0.000 0.000 0.224 0.000
4 BULK STORAGE INFILTRATION BULK STORAGE INFIL_BASE SCHEDULE ZONE3 BULK STORAGE 3204.84 69.0 2.710 8.455E-004 5.523E-004 0.277 0.000 0.000 0.224 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 BULK STORAGE VENTILATION-1 ALWAYS ON SCHEDULE ZONE3 BULK STORAGE 3204.84 69.0 37.760 1.178E-002 0.547 3.853 Exhaust 31.136 0.5 1.000 0.000 0.000 0.000 29.44 100.00 -100.00 -100.00 100.00 40.00
2 BULK STORAGE VENTILATION-2 ALWAYS ON SCHEDULE ZONE3 BULK STORAGE 3204.84 69.0 0.944 2.945E-004 1.368E-002 9.632E-002 Natural 0.000 1.0 0.000 0.000 0.224 0.000 -73.33 29.44 -100.00 -100.00 100.00 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 ZONE1 OFFICE Mixing/Well-Stirred
2 ZONE2 FINE STORAGE Mixing/Well-Stirred
3 ZONE3 BULK STORAGE Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone ZONE1 OFFICE 1.2000
3 Zone ZONE2 FINE STORAGE 1.2000
4 Zone ZONE3 BULK STORAGE 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone ZONE1 OFFICE 1.2000
3 Zone ZONE2 FINE STORAGE 1.2000
4 Zone ZONE3 BULK STORAGE 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT1 1.4083E-004
2 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT2 1.2157E-003
3 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT1 1.2544E-004
4 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT2 1.3238E-003
5 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT1 1.2358E-004
6 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT2 1.3020E-003
7 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT1 1.5848E-004
8 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT2 7.1816E-004
9 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT1 2.5202E-004
10 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT2 6.4828E-004
11 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT1 2.1339E-004
12 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT2 7.3465E-004
13 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT1 2.4304E-004
14 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT2 5.0917E-004
15 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT1 3.7680E-004
16 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT2 2.3855E-004
17 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT1 5.6085E-004
18 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT2 2.9291E-004
19 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT1 4.7452E-004
20 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT2 3.2686E-004
21 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT1 7.1867E-004
22 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT2 2.1428E-004
23 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT1 1.2141E-003
24 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT2 1.2648E-004
25 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT1 1.1536E-003
26 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT2 1.5956E-004
27 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT1 1.0673E-003
28 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT2 1.7205E-004
29 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT1 1.7071E-003
30 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT2 1.2708E-004
31 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT1 2.0450E-003
32 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT2 9.8226E-005
33 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT1 1.3023E-003
34 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT2 1.1188E-004
35 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT1 1.3895E-003
36 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT2 1.1703E-004
37 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT1 1.5134E-003
38 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT2 9.9260E-005
39 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT1 9.2695E-004
40 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT2 8.9692E-005
41 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT1 7.6396E-004
42 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT2 9.3194E-005
43 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT1 8.6372E-004
44 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT2 9.5652E-005
45 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT1 6.2920E-004
46 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT2 8.9104E-005
47 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT1 2.9222E-004
48 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT2 8.6649E-005
49 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT1 1.3839E-003
50 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT2 9.3972E-005
51 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT1 1.6339E-003
52 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT2 9.6511E-005
53 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT1 9.5628E-004
54 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT2 8.9575E-005
55 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT1 3.8087E-004
56 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT2 8.6800E-005
57 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT1 2.9436E-003
58 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT2 1.1469E-004
59 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT1 3.3297E-003
60 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT2 1.2026E-004
61 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT1 2.9531E-003
62 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT2 1.0082E-004
63 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT1 1.7041E-003
64 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT2 9.0163E-005
65 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT1 2.4709E-003
66 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT2 1.7178E-004
67 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT1 2.3336E-003
68 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT2 1.8657E-004
69 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT1 3.4905E-003
70 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT2 1.3340E-004
71 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT1 5.3936E-003
72 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT2 1.0000E-004
73 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT1 8.9079E-004
74 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT2 3.6039E-004
75 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT1 7.4115E-004
76 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT2 4.0933E-004
77 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT1 1.0735E-003
78 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT2 2.4731E-004
79 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT1 2.4816E-003
80 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT2 1.3510E-004
81 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT1 3.1686E-004
82 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT2 1.0829E-003
83 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT1 2.6211E-004
84 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT2 1.2747E-003
85 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT1 2.9129E-004
86 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT2 7.2826E-004
87 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT1 5.2488E-004
88 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT2 2.9545E-004
89 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT1 1.5494E-004
90 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT2 2.6852E-003
91 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT1 1.3565E-004
92 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT2 3.0966E-003
93 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT1 1.3049E-004
94 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT2 2.4323E-003
95 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT1 1.7796E-004
96 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT2 1.2088E-003
97 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT1 1.0606E-004
98 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT2 2.8119E-003
99 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT1 9.8659E-005
100 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT2 2.7814E-003
101 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT1 9.5512E-005
102 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT2 3.8258E-003
103 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT1 1.1032E-004
104 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT2 4.8081E-003
105 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT1 1.0239E-004
106 Clear Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT2 1.2618E-003
107 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT1 9.6059E-005
108 Clear Turbid Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT2 1.2057E-003
109 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT1 9.4245E-005
110 Intermediate Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT2 1.8303E-003
111 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT1 1.0681E-004
112 Overcast Sky 12/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT2 1.8985E-003
113 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT1 6.3813E-005
114 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT2 8.8794E-005
115 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT1 5.7616E-005
116 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT2 7.5928E-005
117 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT1 5.6608E-005
118 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT2 7.0095E-005
119 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT1 6.6895E-005
120 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT2 9.7927E-005
121 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT1 8.4489E-005
122 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT2 7.4291E-005
123 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT1 7.2845E-005
124 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT2 6.5181E-005
125 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT1 6.8273E-005
126 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT2 6.1350E-005
127 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT1 9.2525E-005
128 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT2 7.8810E-005
129 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT1 6.4329E-005
130 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.4643E-005
131 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT1 5.7806E-005
132 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.3069E-005
133 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT1 5.5551E-005
134 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.3781E-005
135 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT1 6.6871E-005
136 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.6561E-005
137 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT1 3.3174E-004
138 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.6525E-004
139 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT1 3.8401E-004
140 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.7717E-004
141 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT1 2.1220E-004
142 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.4077E-004
143 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT1 9.3769E-005
144 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT2 7.9618E-005
145 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.2669E-004
146 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT2 3.8282E-004
147 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.3421E-004
148 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT2 4.4732E-004
149 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.0889E-004
150 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT2 2.3503E-004
151 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT1 6.7372E-005
152 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT2 9.9357E-005
153 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.0937E-004
154 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.9294E-005
155 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.1256E-004
156 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.8639E-005
157 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.0203E-004
158 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.0293E-005
159 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT1 6.7347E-005
160 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.6616E-005
161 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.7722E-004
162 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT2 7.4435E-005
163 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT1 3.1363E-004
164 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT2 7.4336E-005
165 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.9861E-004
166 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT2 7.3296E-005
167 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT1 9.3747E-005
168 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.6604E-005
169 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.8813E-004
170 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.2678E-003
171 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.9542E-004
172 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.5290E-003
173 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.8418E-004
174 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT2 7.5114E-004
175 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.0580E-004
176 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT2 2.5939E-004
177 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT1 8.5245E-004
178 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT2 2.9314E-004
179 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.0019E-003
180 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT2 3.1010E-004
181 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT1 5.8851E-004
182 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT2 2.9046E-004
183 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT1 2.2604E-004
184 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.5435E-004
185 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT1 6.5784E-004
186 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT2 9.2440E-005
187 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT1 7.5055E-004
188 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT2 9.0140E-005
189 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT1 5.2959E-004
190 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT2 9.8048E-005
191 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.2591E-004
192 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT2 7.2647E-005
193 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.6002E-004
194 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.2558E-005
195 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.6090E-004
196 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.1222E-005
197 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.6895E-004
198 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.4461E-005
199 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.0571E-004
200 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.9813E-005
201 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.3254E-003
202 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT2 1.0933E-004
203 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.4601E-003
204 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT2 1.0292E-004
205 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.4179E-003
206 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT2 1.2668E-004
207 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT1 7.8581E-004
208 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT2 9.9167E-005
209 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.6439E-003
210 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT2 4.6715E-004
211 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.8667E-003
212 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT2 4.6988E-004
213 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.5738E-003
214 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT2 5.8561E-004
215 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT1 7.8668E-004
216 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT2 3.7823E-004
217 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.1663E-004
218 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.5059E-005
219 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.0764E-004
220 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.2932E-005
221 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.6993E-004
222 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.7854E-005
223 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.9061E-004
224 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.3526E-005
225 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.5016E-004
226 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT2 2.7088E-003
227 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.4728E-004
228 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT2 3.1832E-003
229 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.9748E-004
230 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT2 2.2542E-003
231 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.9089E-004
232 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.0419E-003
233 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT1 2.3669E-004
234 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.5793E-005
235 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT1 2.1335E-004
236 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.3046E-005
237 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT1 3.2400E-004
238 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.8527E-005
239 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT1 2.9941E-004
240 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.6221E-005
241 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.5409E-003
242 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.1494E-004
243 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.5028E-003
244 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.0438E-004
245 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.1714E-003
246 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.3801E-004
247 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.4248E-003
248 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.2491E-004
249 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.7230E-003
250 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT2 5.3135E-004
251 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.7208E-003
252 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT2 4.8829E-004
253 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT1 2.3561E-003
254 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT2 7.8689E-004
255 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT1 2.4293E-003
256 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT2 7.8036E-004
257 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.6100E-004
258 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT2 2.7489E-003
259 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.4037E-004
260 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT2 2.8171E-003
261 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT1 3.5652E-004
262 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT2 3.5798E-003
263 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT1 3.0001E-004
264 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT2 3.9796E-003
265 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.9725E-004
266 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.4370E-005
267 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.7008E-004
268 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.1427E-005
269 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT1 2.4867E-004
270 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.5783E-005
271 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT1 2.9778E-004
272 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.6189E-005
273 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.0592E-004
274 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.2591E-003
275 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.7973E-004
276 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.0818E-003
277 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.7018E-004
278 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.6691E-003
279 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.9837E-004
280 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT2 3.9047E-003
281 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT1 8.7216E-004
282 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.0450E-004
283 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT1 7.4397E-004
284 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT2 9.2842E-005
285 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.1906E-003
286 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.1770E-004
287 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.3879E-003
288 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.2457E-004
289 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT1 9.0347E-004
290 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT2 3.8911E-004
291 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT1 7.7802E-004
292 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT2 3.3142E-004
293 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.2622E-003
294 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT2 5.3325E-004
295 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT1 2.3924E-003
296 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT2 7.7331E-004
297 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.3720E-004
298 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT2 4.3366E-004
299 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.1778E-004
300 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT2 3.5102E-004
301 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.4940E-004
302 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT2 4.6128E-004
303 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.8861E-004
304 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.0100E-003
305 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT1 3.5924E-004
306 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT2 2.1876E-004
307 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT1 2.9344E-004
308 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.8109E-004
309 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT1 3.9620E-004
310 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT2 2.3131E-004
311 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT1 7.6558E-004
312 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT2 3.7122E-004
313 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT1 8.4903E-005
314 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.4791E-005
315 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT1 7.3020E-005
316 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.0702E-005
317 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT1 6.7539E-005
318 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT2 4.9904E-005
319 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT1 9.2504E-005
320 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.6374E-005
321 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.3643E-004
322 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.1355E-005
323 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.1610E-004
324 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.8663E-005
325 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.4044E-004
326 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.1180E-005
327 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.8833E-004
328 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.3453E-005
329 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT1 8.9665E-005
330 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.7269E-004
331 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT1 7.8189E-005
332 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.4065E-004
333 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT1 8.3076E-005
334 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.4484E-004
335 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.0461E-004
336 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT2 2.5303E-004
337 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.5601E-004
338 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.1948E-004
339 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.2837E-004
340 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.0034E-004
341 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.3469E-004
342 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.0273E-004
343 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT1 2.2098E-004
344 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.5178E-004
345 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT1 9.0338E-005
346 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.7818E-005
347 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT1 7.8237E-005
348 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.5654E-005
349 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT1 7.9997E-005
350 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.6853E-005
351 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.0452E-004
352 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.9739E-005
353 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT1 3.5891E-004
354 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT2 8.5325E-005
355 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.9160E-004
356 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT2 7.5647E-005
357 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT1 3.8133E-004
358 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT2 8.5191E-005
359 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT1 7.6474E-004
360 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT2 9.8551E-005
361 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.5692E-004
362 Clear Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT2 6.7317E-005
363 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.2863E-004
364 Clear Turbid Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT2 6.0667E-005
365 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.3168E-004
366 Intermediate Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT2 6.1916E-005
367 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.2086E-004
368 Overcast Sky 12/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT2 7.2207E-005
369 Clear Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT1 3.7627E-003
370 Clear Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT2 4.3590E-004
371 Clear Turbid Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT1 3.4277E-003
372 Clear Turbid Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT2 4.0232E-004
373 Intermediate Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT1 3.1486E-003
374 Intermediate Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT2 3.7868E-004
375 Overcast Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT1 1.7938E-003
376 Overcast Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT2 3.1762E-004
377 Clear Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 4.4413E-004
378 Clear Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 3.9387E-003
379 Clear Turbid Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 4.1830E-004
380 Clear Turbid Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 3.3667E-003
381 Intermediate Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 3.8630E-004
382 Intermediate Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 3.3423E-003
383 Overcast Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 3.1395E-004
384 Overcast Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 2.4070E-003
385 Clear Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT1 3.1005E-003
386 Clear Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT2 2.2271E-004
387 Clear Turbid Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT1 2.3095E-003
388 Clear Turbid Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT2 1.7609E-004
389 Intermediate Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT1 1.4521E-003
390 Intermediate Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT2 1.3365E-004
391 Overcast Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT1 2.2519E-003
392 Overcast Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT2 1.9331E-004
393 Clear Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 3.0396E-003
394 Clear Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 2.2247E-004
395 Clear Turbid Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 2.2823E-003
396 Clear Turbid Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 1.7596E-004
397 Intermediate Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 1.5265E-003
398 Intermediate Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 1.3378E-004
399 Overcast Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 2.2518E-003
400 Overcast Sky 12/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 1.9331E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 ZONE1 OFFICE Cooling 10478.54035 12574.24842 0.87841 1.05410 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:10:00 30.64733 8.23245E-003 236.87965 12.74874 0.10228 0.00000
2 ZONE1 OFFICE Heating 7107.77851 8529.33421 0.20310 0.24372 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 3.80000 5.05843E-003 236.87965 12.74874 0.10228 0.00000
3 ZONE2 FINE STORAGE Cooling 29501.59811 35401.91774 1.92781 2.31337 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 31.30000 8.23349E-003 1393.40969 30.00000 0.42471 0.00000
4 ZONE2 FINE STORAGE Heating 14039.11376 16846.93651 0.33825 0.42471 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 06:00:00 3.80000 5.05843E-003 1393.40969 30.00000 0.42471 0.00000
5 ZONE3 BULK STORAGE Cooling 0.00000 0.00000 0.00000 0.97684 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 31.30000 8.23349E-003 3204.84228 69.00000 0.97684 0.00000
6 ZONE3 BULK STORAGE Heating 22816.11360 27379.33632 0.56805 0.97684 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 3204.84228 69.00000 0.97684 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-OFFICE Cooling Sensible 15724.09 1.05410 1.05410 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
2 PSZ-OFFICE Heating Sensible 7586.03 0.24372 0.24372 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00
3 PSZ-FINE STORAGE Cooling Sensible 42701.17 2.31337 2.31337 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
4 PSZ-FINE STORAGE Heating Sensible 18257.59 0.42471 0.42471 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONE1 OFFICE DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.05410
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONE2 FINE STORAGE DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 2.31337
3 ZoneHVAC:UnitHeater ZONE3 BULK STORAGE UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 0.97684
4 Fan:ConstantVolume ZONE3UNITHEATER ZONE3HIRADIANT FAN Design Size Maximum Flow Rate [m3/s] 0.97684
5 Coil:Heating:Fuel ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL Design Size Nominal Capacity [W] 39235.42577
6 ZoneHVAC:HighTemperatureRadiant ZONE3 BULK STORAGE HIRADIANT User-Specified Heating Design Capacity [W] 27379.33632
7 AirLoopHVAC PSZ-OFFICE Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.05410
8 AirLoopHVAC PSZ-OFFICE Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.05410
9 AirLoopHVAC PSZ-OFFICE Sum of Air Terminal Maximum Flow Rates [m3/s] 1.05410
10 AirLoopHVAC PSZ-OFFICE Adjusted Heating Design Air Flow Rate [m3/s] 1.05410
11 AirLoopHVAC PSZ-OFFICE Adjusted Cooling Design Air Flow Rate [m3/s] 1.05410
12 AirLoopHVAC PSZ-OFFICE Adjusted Main Design Air Flow Rate [m3/s] 1.05410
13 AirLoopHVAC PSZ-OFFICE User Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-OFFICE Calculated Heating Air Flow Ratio [] 1.00000
15 AirLoopHVAC PSZ-FINE STORAGE Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.31337
16 AirLoopHVAC PSZ-FINE STORAGE Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.31337
17 AirLoopHVAC PSZ-FINE STORAGE Sum of Air Terminal Maximum Flow Rates [m3/s] 2.31337
18 AirLoopHVAC PSZ-FINE STORAGE Adjusted Heating Design Air Flow Rate [m3/s] 2.31337
19 AirLoopHVAC PSZ-FINE STORAGE Adjusted Cooling Design Air Flow Rate [m3/s] 2.31337
20 AirLoopHVAC PSZ-FINE STORAGE Adjusted Main Design Air Flow Rate [m3/s] 2.31337
21 AirLoopHVAC PSZ-FINE STORAGE User Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-FINE STORAGE Calculated Heating Air Flow Ratio [] 1.00000
23 AirLoopHVAC PSZ-OFFICE Design Supply Air Flow Rate [m3/s] 1.05410
24 AirLoopHVAC PSZ-FINE STORAGE Design Supply Air Flow Rate [m3/s] 2.31337
25 Controller:OutdoorAir PSZ-OFFICE_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.05410
26 Controller:OutdoorAir PSZ-OFFICE_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.10228
27 Fan:SystemModel PSZ-OFFICE_ADDAQ SUPPLY FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.05410
28 Fan:SystemModel PSZ-OFFICE_ADDAQ SUPPLY FAN Design Electric Power Consumption [W] 1167.05226
29 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.05410
30 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.05410
31 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.05410
32 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.05410
33 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.05410
34 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.52705
35 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.70273
36 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 17990.76000
37 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 8995.38000
38 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80058
39 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80058
40 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 17990.76000
41 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 25858.40046
42 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
43 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
44 Coil:Heating:Fuel PSZ-OFFICE HEATING COIL Design Size Nominal Capacity [W] 25858.40046
45 Controller:OutdoorAir PSZ-FINE STORAGE_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.31337
46 Controller:OutdoorAir PSZ-FINE STORAGE_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.42471
47 Fan:SystemModel PSZ-FINE STORAGE_ADDAQ SUPPLY FAN Design Size Design Maximum Air Flow Rate [m3/s] 2.31337
48 Fan:SystemModel PSZ-FINE STORAGE_ADDAQ SUPPLY FAN Design Electric Power Consumption [W] 2475.41888
49 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 2.31337
50 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 2.31337
51 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 2.31337
52 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.52683
53 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 2.31337
54 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 1.15669
55 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 1.54225
56 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 47969.37000
57 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 23984.68500
58 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.76250
59 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.76250
60 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 47969.37000
61 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 73076.21387
62 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
63 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
64 Coil:Heating:Fuel PSZ-FINE STORAGE HEATING COIL Design Size Nominal Capacity [W] 73076.21387


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL 17172.7     12.24 11.96  
2 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL 46172.7     11.73 11.46  


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 ZONE1 OFFICE RunPeriod: RUNPERIOD 1 2.2429198838E-002 1.7503334131E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 ZONE2 FINE STORAGE RunPeriod: RUNPERIOD 1 3.2329396495E-002 3.0361960844E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 ZONE3 BULK STORAGE RunPeriod: RUNPERIOD 1 2.0119471338E-002 1.9362080296E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 7622.19 328.95 0.00 64.71 57.17 8073.07



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 3.80 0.00 3.80 Wetbulb [C] 3.00 120.00
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 31.30 8.90 18.40 Wetbulb [C] 4.10 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 2.00 2      
Feb 59.00 53      
Mar 58.58 43      
Apr 46.42 14      
May 18.00 12      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 3.00 6      
Oct 0.00 0      
Nov 18.00 12      
Dec 4.00 4      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
OFFICE FRONT WALL NONRES_EXT_WALL_GRD 0.30 0.536 0.583 110.54 97.44 270.00 90.00 W
OFFICE LEFT WALL NONRES_EXT_WALL_GRD 0.30 0.536 0.583 39.02 30.56 0.00 90.00 N
OFFICE FLOOR OFFICEFLOOR_FFACTOR 1.00 0.187 0.193 236.88 236.88 90.00 180.00  
FINE STORAGE FRONT WALL NONRES_EXT_WALL_GRD 0.30 0.536 0.583 169.07 161.64 270.00 90.00 W
FINE STORAGE RIGHT WALL NONRES_EXT_WALL_GRD 0.30 0.536 0.583 260.10 243.29 180.00 90.00 S
FINE STORAGE LEFT WALL NONRES_EXT_WALL_GRD 0.30 0.536 0.583 182.07 172.69 0.00 90.00 N
FINE STORAGE OFFICE FRONT WALL NONRES_EXT_WALL_GRD 0.30 0.536 0.583 110.54 110.54 270.00 90.00 W
FINE STORAGE OFFICE LEFT WALL NONRES_EXT_WALL_GRD 0.30 0.536 0.583 39.02 39.02 0.00 90.00 N
FINE STORAGE FLOOR FINESTORAGEFLOOR_FFACTOR 1.00 0.078 0.079 1156.53 1156.53 90.00 180.00  
FINE STORAGE ROOF NONRES_ROOF 0.55 0.199 0.204 1393.41 1372.60 90.00 0.00  
BULK STORAGE RIGHT WALL SEMIHEATED_EXT_WALL_GRD 0.30 0.536 0.583 598.24 568.60 180.00 90.00 S
BULK STORAGE REAR WALL SEMIHEATED_EXT_WALL_GRD 0.30 0.536 0.583 390.15 358.48 90.00 90.00 E
BULK STORAGE LEFT WALL SEMIHEATED_EXT_WALL_GRD 0.30 0.536 0.583 598.24 544.27 0.00 90.00 N
BULK STORAGE FLOOR BULKSTORAGEFLOOR_FFACTOR 1.00 0.073 0.074 3204.84 3204.84 90.00 180.00  
BULK STORAGE ROOF SEMIHEATED_ROOF 0.55 0.199 0.204 3204.84 3157.28 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
OFFICE RIGHT WALL INTERIOR WALL 0.30 0.653 0.775 39.02 39.02 180.00 90.00 S
OFFICE REAR WALL INTERIOR WALL 0.30 0.653 0.775 110.54 110.54 90.00 90.00 E
OFFICE ROOF INSULATEDCEILING 0.30 2.711 10.063 236.88 236.88 90.00 0.00  
iz-OFFICE RIGHT WALL iz-INTERIOR WALL 0.30 0.653 0.775 39.02 39.02 0.00 90.00 N
iz-OFFICE REAR WALL iz-INTERIOR WALL 0.30 0.653 0.775 110.54 110.54 270.00 90.00 W
iz-BULK STORAGE FRONT WALL iz-SEMIHEATED_EXT_WALL_GRD 0.30 0.512 0.583 390.15 390.15 270.00 90.00 W
iz-OFFICE ROOF iz-INSULATEDCEILING 0.30 2.711 10.063 236.88 236.88 270.00 180.00  
BULK STORAGE FRONT WALL SEMIHEATED_EXT_WALL_GRD 0.30 0.512 0.583 390.15 390.15 90.00 90.00 E
BULK STORAGE PRODUCTS SURFACE BULK STORAGE PRODUCTS 0.30   0.591 6028.45   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
OFFICE FRONT WALL WINDOW 1 NONRESWINDOW_U_0.4637_SHGC_WEST_0.25   5.58 0.00 0.00 5.58 5.58 2.636 0.251 0.251             No OFFICE FRONT WALL 270.00 90.00 W
OFFICE FRONT WALL WINDOW2 NONRESWINDOW_U_0.4637_SHGC_WEST_0.25   5.58 0.00 0.00 5.58 5.58 2.636 0.251 0.251             No OFFICE FRONT WALL 270.00 90.00 W
OFFICE LEFT WALL WINDOW1 NONRESWINDOW_U_0.4637_SHGC_NORTH_0.25   3.25 0.00 0.00 3.25 3.25 2.636 0.251 0.251             No OFFICE LEFT WALL 0.00 90.00 N
OFFICE LEFT WALL WINDOW2 NONRESWINDOW_U_0.4637_SHGC_NORTH_0.25   3.25 0.00 0.00 3.25 3.25 2.636 0.251 0.251             No OFFICE LEFT WALL 0.00 90.00 N
FINESTORAGE_SKYLIGHT_1 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_6 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_7 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_8 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_9 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_10 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_5 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_4 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_3 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_2 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_14 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_13 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_12 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_11 SKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No FINE STORAGE ROOF 180.00 0.00  
SKYLIGHT_R8C1 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R8C2 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R8C4 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R1C2 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R1C1 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R1C4 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R1C3 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R2C1 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R2C2 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R2C3 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R2C4 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R3C4 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R3C2 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R3C3 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R3C1 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R4C4 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R4C3 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R4C2 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R4C1 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R5C4 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R5C1 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R5C3 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R5C2 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R6C1 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R6C2 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R8C3 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R6C4 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R7C1 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R7C2 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R7C4 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R6C3 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R7C3 SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No BULK STORAGE ROOF 180.00 0.00  
Total or Average             86.04 4.600 0.529 0.530                      
North Total or Average             6.51 2.636 0.251 0.251                      
Non-North Total or Average             79.53 4.761 0.552 0.553                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
OFFICE FRONT DOOR SWINGING DOOR_CON 2.281 3.464 1.95 OFFICE FRONT WALL
OFFICE LEFT WALL DOOR SWINGING DOOR_CON 2.281 3.464 1.95 OFFICE LEFT WALL
FINE STORAGE OVERHEAD DOOR1 OVERHEAD DOOR_CON 1.016 1.198 7.43 FINE STORAGE FRONT WALL
FINE STORAGE OVERHEAD DOOR2 OVERHEAD DOOR_CON 1.016 1.198 7.43 FINE STORAGE RIGHT WALL
FINE STORAGE OVERHEAD DOOR3 OVERHEAD DOOR_CON 1.016 1.198 7.43 FINE STORAGE RIGHT WALL
FINE STORAGE RIGHT DOOR SWINGING DOOR_CON 2.281 3.464 1.95 FINE STORAGE RIGHT WALL
FINE STORAGE OVERHEAD DOOR4 OVERHEAD DOOR_CON 1.016 1.198 7.43 FINE STORAGE LEFT WALL
FINE STORAGE LEFT DOOR SWINGING DOOR_CON 2.281 3.464 1.95 FINE STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR8 OVERHEAD DOOR_SEMI 1.016 1.198 5.95 BULK STORAGE RIGHT WALL
BULK STORAGE OVERHEAD DOOR9 OVERHEAD DOOR_SEMI 1.016 1.198 5.95 BULK STORAGE RIGHT WALL
BULK STORAGE OVERHEAD DOOR10 OVERHEAD DOOR_SEMI 1.016 1.198 5.95 BULK STORAGE RIGHT WALL
BULK STORAGE OVERHEAD DOOR11 OVERHEAD DOOR_SEMI 1.016 1.198 5.95 BULK STORAGE RIGHT WALL
BULK STORAGE DOOR1 SWINGING DOOR_SEMI 2.281 3.464 1.95 BULK STORAGE RIGHT WALL
BULK STORAGE DOOR2 SWINGING DOOR_SEMI 2.281 3.464 1.95 BULK STORAGE RIGHT WALL
BULK STORAGE DOOR3 SWINGING DOOR_SEMI 2.281 3.464 1.95 BULK STORAGE RIGHT WALL
BULK STORAGE OVERHEAD DOOR12 OVERHEAD DOOR_SEMI 1.016 1.198 7.43 BULK STORAGE REAR WALL
BULK STORAGE OVERHEAD DOOR13 OVERHEAD DOOR_SEMI 1.016 1.198 7.43 BULK STORAGE REAR WALL
BULK STORAGE OVERHEAD DOOR14 OVERHEAD DOOR_SEMI 1.016 1.198 7.43 BULK STORAGE REAR WALL
BULK STORAGE OVERHEAD DOOR15 OVERHEAD DOOR_SEMI 1.016 1.198 7.43 BULK STORAGE REAR WALL
BULK STORAGE DOOR4 SWINGING DOOR_SEMI 2.281 3.464 1.95 BULK STORAGE REAR WALL
BULK STORAGE OVERHEAD DOOR1 OVERHEAD DOOR_SEMI 1.016 1.198 7.43 BULK STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR2 OVERHEAD DOOR_SEMI 1.016 1.198 7.43 BULK STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR3 OVERHEAD DOOR_SEMI 1.016 1.198 7.43 BULK STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR4 OVERHEAD DOOR_SEMI 1.016 1.198 7.43 BULK STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR5 OVERHEAD DOOR_SEMI 1.016 1.198 7.43 BULK STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR6 OVERHEAD DOOR_SEMI 1.016 1.198 7.43 BULK STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR7 OVERHEAD DOOR_SEMI 1.016 1.198 7.43 BULK STORAGE LEFT WALL
BULK STORAGE DOOR5 SWINGING DOOR_SEMI 2.281 3.464 1.95 BULK STORAGE LEFT WALL


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
OFFICE FRONT WALL WINDOW 1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
OFFICE FRONT WALL WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
OFFICE LEFT WALL WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OFFICE LEFT WALL WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FINESTORAGE_SKYLIGHT_1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_6 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_7 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_8 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_9 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_10 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_14 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_13 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R8C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R8C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R8C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R1C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R1C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R1C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R1C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R2C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R2C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R2C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R2C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R3C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R3C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R3C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R3C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R4C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R4C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R4C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R4C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R5C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R5C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R5C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R5C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R6C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R6C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R8C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R6C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R7C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R7C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R7C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R6C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R7C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
OFFICE LIGHTS ZONE1 OFFICE ZONE1 OFFICE GENERAL 8.9961 236.88 2131.00 LightsWired LTG_SCH_OFFICE 51.55 168.00 46.80 0.0000 Y 18.72
FINE STORAGE AREA LIGHTS ZONE2 FINE STORAGE ZONE2 FINE STORAGE GENERAL 9.2031 1393.41 12823.73 LightsWired LTG_SCH_FINE_STORAGE 34.09 168.00 24.58 0.0000 Y 59.18
BULK STORAGE AREA LIGHTS ZONE3 BULK STORAGE ZONE3 BULK STORAGE GENERAL 5.6188 3204.84 18007.22 LightsWired LTG_SCH_BULK_STORAGE 34.09 168.00 21.54 0.0000 Y 72.82
Interior Lighting Total       6.8172 4835.13 32961.95               150.73


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
ZONE2 FINE STORAGE_DAYLREFPT1 ZONE2 FINE STORAGE ZONE2 FINE STORAGE_DAYLCTRL SplitFlux Stepped 0.25 12823.73 3205.93
ZONE2 FINE STORAGE_DAYLREFPT2 ZONE2 FINE STORAGE ZONE2 FINE STORAGE_DAYLCTRL SplitFlux Stepped 0.25 12823.73 3205.93
ZONE3 BULK STORAGE_DAYLREFPT1 ZONE3 BULK STORAGE ZONE3 BULK STORAGE_DAYLCTRL SplitFlux Stepped 0.25 18007.22 4501.81
ZONE3 BULK STORAGE_DAYLREFPT2 ZONE3 BULK STORAGE ZONE3 BULK STORAGE_DAYLCTRL SplitFlux Stepped 0.25 18007.22 4501.81
ZONE1 OFFICE_DAYLREFPT1 ZONE1 OFFICE ZONE1 OFFICE_DAYLCTRL SplitFlux Continuous/Off 0.14 2131.00 309.00
ZONE1 OFFICE_DAYLREFPT2 ZONE1 OFFICE ZONE1 OFFICE_DAYLCTRL SplitFlux Continuous/Off 0.05 2131.00 106.55


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 94.73 AstronomicalClock -   42.14 42.14 0.75
EXTERIOR_LIGHTS_B 6863.48 AstronomicalClock -   83.75 71.27 91.82
Exterior Lighting Total 6958.21           92.57



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-OFFICE COOLING COIL Coil:Cooling:DX:MultiSpeed   17990.76 14403.04 3587.72 0.80 4.12    
PSZ-FINE STORAGE COOLING COIL Coil:Cooling:DX:MultiSpeed   47969.37 36576.64 11392.73 0.76 3.73    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-OFFICE COOLING COIL   17172.7     12.24 11.96  
PSZ-FINE STORAGE COOLING COIL   46172.7     11.73 11.46  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-OFFICE COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-FINE STORAGE COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL Coil:Heating:Fuel   39235.43 0.80
PSZ-OFFICE HEATING COIL Coil:Heating:Fuel   25858.40 0.80
PSZ-FINE STORAGE HEATING COIL Coil:Heating:Fuel   73076.21 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
ZONE3UNITHEATER ZONE3HIRADIANT FAN Fan:ConstantVolume 0.54 49.80 0.98 90.76 92.91 1.00 4.17 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-OFFICE_ADDAQ SUPPLY FAN Fan:SystemModel 0.56 622.50 1.05 1167.05 1107.16 1.00 1.39 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN Fan:SystemModel 0.58 622.50 2.31 2475.42 1070.05 1.00 1.29 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
None                


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.08 6154.75 1.00 1.06 0.53



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
ZONE1 OFFICE 10478.54 12574.25 53.08 0.878 1.054 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:10:00 23.90 23.90 0.00829 30.65 0.00823 0.102 0.00
ZONE2 FINE STORAGE 29501.60 35401.92 25.41 1.928 2.313 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 26.70 26.70 0.00836 31.30 0.00823 0.425 0.00
ZONE3 BULK STORAGE 0.00 0.00 0.00 0.000 0.977 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 0.00 31.62 0.00830 31.30 0.00823 0.977 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
ZONE1 OFFICE 7107.78 8529.33 36.01 0.203 0.244 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 21.10 21.10 0.00786 3.80 0.00506 0.102 0.00
ZONE2 FINE STORAGE 14039.11 16846.94 12.09 0.338 0.425 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 06:00:00 15.56 15.56 0.00681 3.80 0.00506 0.425 0.00
ZONE3 BULK STORAGE 22816.11 27379.34 8.54 0.568 0.977 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10.00 10.00 0.00580 3.80 0.00506 0.977 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-OFFICE 1.05 1.05 0.24 0.24 1.0541 1.0541 1.0541 1.0000 1.0000
PSZ-FINE STORAGE 2.31 2.31 0.42 0.42 2.3134 2.3134 2.3134 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL COIL:HEATING:FUEL ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT 39235.426 39235.426 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 39235.43 39235.43 0.976836 10.00 7.81 0.00580078 43.33 21.93 0.00800000 3.80 0.00505843 3.80 0.0000 10.00 0.00580078 74.8195 27379.34 0.00 -999.00 -999.00
PSZ-OFFICE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-OFFICE 17990.760 14403.043 1.054100 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:10:00 8995.38 8591.66 0.702733 25.48 16.53 0.00828332 12.00 11.09 0.00800000 30.77 0.00823264 18.27 14.5553 23.90 0.00828877 44.0711 10475.28 0.00 -999.00 -999.00
PSZ-OFFICE HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-OFFICE 25858.400 25858.400 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 25858.40 25858.40 1.054097 19.34 13.66 0.00758649 40.00 20.96 0.00800000 3.80 0.00505843 3.80 9.7035 21.10 0.00785817 49.5635 7107.78 0.00 -999.00 -999.00
PSZ-FINE STORAGE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-FINE STORAGE 47969.370 36576.645 2.313370 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 23984.69 22901.02 1.542247 28.43 17.59 0.00834038 12.00 11.09 0.00800000 31.30 0.00823349 18.45 27.5385 26.70 0.00836442 37.6460 29501.60 0.00 -999.00 -999.00
PSZ-FINE STORAGE HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-FINE STORAGE 73076.214 73076.214 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 73076.21 73076.21 2.313373 13.40 10.10 0.00647835 40.00 20.96 0.00800000 3.80 0.00505843 3.80 18.3590 15.56 0.00679765 60.8078 13790.46 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL COIL:HEATING:FUEL Zone Equipment ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT ZONE3 BULK STORAGE N/A N/A N/A Yes No unknown No 39235.426 39235.426 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ZONE3UNITHEATER ZONE3HIRADIANT FAN Fan:ConstantVolume 0.976836 1.15440386   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 39235.43 39235.43 1.0000 1.15440386 0.976836 10.00 7.81 0.00580078 24663.0 43.33 21.93 0.00800000 64191.6 -999.0 -999.00 -999.00 -999.00 0.000 39235.43 3.80 0.00505843 3.80 0.00000000 0.0000 10.00 0.00580078 10.00 0.00580078 74.8195 27379.34 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-OFFICE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-OFFICE ZONE1 OFFICE Coincident CoolingDesignCapacity N/A No No unknown No 17990.760 14403.043 1.054100 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.2383 1004.8586 1.1818 PSZ-OFFICE_ADDAQ SUPPLY FAN Fan:SystemModel 1.054097 1.24570887   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:10:00 Sensible 8995.38 8591.66 1.0000 0.83047526 0.702733 25.48 16.53 0.00828332 46715.6 12.00 11.09 0.00800000 32244.1 -999.0 -999.00 -999.00 -999.00 0.000 8995.38 30.77 0.00823264 18.27 0.10228463 14.5553 23.90 0.00828877 23.90 0.00828877 44.0711 10475.28 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-OFFICE HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-OFFICE ZONE1 OFFICE Coincident HeatingDesignCapacity N/A Yes No unknown No 25858.400 25858.400 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-OFFICE_ADDAQ SUPPLY FAN Fan:SystemModel 1.054097 1.24570887   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 Sensible 25858.40 25858.40 1.0000 1.24570887 1.054097 19.34 13.66 0.00758649 38682.2 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 25858.40 3.80 0.00505843 3.80 0.10228463 9.7035 21.01 0.00785817 21.10 0.00785817 49.5635 7107.78 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-FINE STORAGE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-FINE STORAGE ZONE2 FINE STORAGE Coincident CoolingDesignCapacity N/A No No unknown No 47969.370 36576.645 2.313370 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.3444 1004.8586 1.1818 PSZ-FINE STORAGE_ADDAQ SUPPLY FAN Fan:SystemModel 2.313373 2.73389531   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 Sensible 23984.69 22901.02 1.0000 1.82259420 1.542247 28.43 17.59 0.00834038 49868.3 12.00 11.09 0.00800000 32244.1 -999.0 -999.00 -999.00 -999.00 0.000 23984.69 31.30 0.00823349 18.45 0.42471127 27.5385 26.70 0.00836442 26.70 0.00836442 37.6460 29501.60 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-FINE STORAGE HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-FINE STORAGE ZONE2 FINE STORAGE Coincident HeatingDesignCapacity N/A Yes No unknown No 73076.214 73076.214 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-FINE STORAGE_ADDAQ SUPPLY FAN Fan:SystemModel 2.313373 2.73389531   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 73076.21 73076.21 1.0000 2.73389531 2.313373 13.40 10.10 0.00647835 29827.7 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 73076.21 3.80 0.00505843 3.80 0.42471127 18.3590 15.56 0.00679765 15.56 0.00679765 60.8078 13790.46 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PSZ-OFFICE_OA_CONTROLLER DifferentialDryBulb 0.10 1.05 -      
PSZ-FINE STORAGE_OA_CONTROLLER DifferentialDryBulb 0.42 2.31 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
ZONE1 OFFICE 1601.33 1961.50 295.83
ZONE2 FINE STORAGE 2217.17 2583.67 1298.50
ZONE3 BULK STORAGE 2422.67 2898.50 1830.83
Facility 2785.33 3033.17 1930.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
ZONE1 OFFICE 0.33 0.00 0.33 0.00
ZONE2 FINE STORAGE 0.33 1.83 0.00 0.00
ZONE3 BULK STORAGE 0.00 0.00 0.00 0.00
Facility 0.67 1.83 0.33 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
ZONE1 OFFICE 9.51 12.75 1010.76 1.355 0.399 0.000 0.000
ZONE2 FINE STORAGE 22.37 30.00 2953.02 0.583 0.178 0.000 0.000
ZONE3 BULK STORAGE 51.45 69.00 35277.63 0.000 0.115 0.000 0.044
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
ZONE1 OFFICE 9.51 12.75 1010.76 0.000 0.000 0.000 0.000
ZONE2 FINE STORAGE 22.37 30.00 2953.02 0.000 0.000 0.000 0.000
ZONE3 BULK STORAGE 51.45 69.00 35277.63 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
ZONE1 OFFICE PSZ-OFFICE 9.51 12.75 1010.76 236.88 0.1023 0.102
ZONE2 FINE STORAGE PSZ-FINE STORAGE 22.37 30.00 2953.02 1393.41 0.4247 0.425
ZONE3 BULK STORAGE   51.45 69.00 35277.63 3204.84   0.977
Total Facility   83.33 111.75 39241.41 4835.13 0.5270 1.504


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
ZONE1 OFFICE 4855942.10 0.00 4855942.10 1849054.15 6704996.25 3225648.14 5712.44 875.75 2171.81 0.00
ZONE2 FINE STORAGE 6137930.51 0.00 6137930.51 4130661.33 10268591.83 13393694.68 5714.08 2291.87 754.05 17.67
ZONE3 BULK STORAGE 0.00 10325075.72 10325075.72 25131564.63 35456640.36 30805497.77 8699.74 6.67 53.60 4402.83
Total Facility 10993872.61 10325075.72 21318948.33 31111280.11 52430228.44 47424840.58 8713.40 2445.97 2367.16 4404.08


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
ZONE1 OFFICE 0.3710 0.0000 0.3710 0.1096 0.4806 0.1023 588.44 875.75 2171.81
ZONE2 FINE STORAGE 0.4644 0.0000 0.4644 0.1429 0.6072 0.4247 606.00 2291.87 738.13
ZONE3 BULK STORAGE 0.0000 0.4172 0.4172 1.1039 1.5211 0.9768 3587.07 5.33 43.60
Total Facility 0.8353 0.4172 1.2526 1.3564 2.6089 1.5038 3589.40 2444.63 2341.24


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-OFFICE 6781812.67 0.00 6781812.67 3225648.14 5710.11 0.00 3049.89 0.00
PSZ-FINE STORAGE 8572238.72 0.00 8572238.72 13393694.68 5713.50 0.00 3046.50 17.67


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-OFFICE 0.5181 0.0000 0.5181 0.1023 586.11 0.00 3049.89
PSZ-FINE STORAGE 0.6485 0.0000 0.6485 0.4247 606.00 0.00 3030.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-OFFICE 0.00 2056.59 999.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-FINE STORAGE 0.00 2802.49 250.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-OFFICE 0.0000 0.6534 0.5411 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-FINE STORAGE 0.0000 0.7533 1.0478 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Surfaces by Class

Total Outdoors
Wall 16 10
Floor 4 3
Roof 3 2
Internal Mass 1 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 50 50
Door 28 28
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 3
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 429
Defaulted Fields 391
Fields with Defaults 1171
Autosized Fields 43
Autosizable Fields 97
Autocalculated Fields 128
Autocalculatable Fields 206



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 443.40 2146.58 12-MAR-14:30 35188.43 05-DEC-16:50
Electricity:Building 290.02 1663.58 12-MAR-14:30 25603.42 15-DEC-16:00
Electricity:Zone:ZONE1 OFFICE 50.67 815.73 19-FEB-15:50 3198.43 02-JAN-16:50
Electricity:SpaceType:GENERAL 290.02 1663.58 12-MAR-14:30 25603.42 15-DEC-16:00
InteriorLights:Electricity 150.73 1089.83 12-MAR-14:30 15490.80 15-DEC-16:00
InteriorLights:Electricity:Zone:ZONE1 OFFICE 18.72 241.98 19-FEB-15:50 1285.93 02-JAN-16:50
InteriorLights:Electricity:SpaceType:GENERAL 150.73 1089.83 12-MAR-14:30 15490.80 15-DEC-16:00
LightsWired:InteriorLights:Electricity 150.73 1089.83 12-MAR-14:30 15490.80 15-DEC-16:00
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE 18.72 241.98 19-FEB-15:50 1285.93 02-JAN-16:50
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 150.73 1089.83 12-MAR-14:30 15490.80 15-DEC-16:00
Electricity:Zone:ZONE2 FINE STORAGE 59.18 352.65 01-JAN-12:00 5995.09 02-JAN-15:50
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE 59.18 352.65 01-JAN-12:00 5995.09 02-JAN-15:50
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE 59.18 352.65 01-JAN-12:00 5995.09 02-JAN-15:50
Electricity:Zone:ZONE3 BULK STORAGE 180.17 495.20 01-JAN-09:00 16618.50 25-NOV-16:00
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE 72.82 495.20 01-JAN-09:00 8418.38 25-NOV-16:00
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE 72.82 495.20 01-JAN-09:00 8418.38 25-NOV-16:00
InteriorEquipment:Electricity 139.29 573.75 01-JAN-00:10 10112.62 02-JAN-08:10
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE 31.95 573.75 01-JAN-00:10 1912.50 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 139.29 573.75 01-JAN-00:10 10112.62 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 139.29 573.75 01-JAN-00:10 10112.62 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE 31.95 573.75 01-JAN-00:10 1912.50 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 139.29 573.75 01-JAN-00:10 10112.62 02-JAN-08:10
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE 107.34 0.00 01-JAN-00:10 8200.12 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE 107.34 0.00 01-JAN-00:10 8200.12 02-JAN-08:10
Fans:Electricity 25.99 0.00 01-JAN-00:10 3309.87 31-JUL-12:40
Fans:Electricity:Zone:ZONE3 BULK STORAGE 0.00 0.00 01-JAN-00:10 1152.65 31-JUL-12:40
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 1152.65 31-JUL-12:40
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE 0.00 0.00 01-JAN-00:10 1152.65 31-JUL-12:40
ElectricityPurchased:Facility 443.40 2146.58 12-MAR-14:30 35188.43 05-DEC-16:50
ElectricityPurchased:Plant 443.40 2146.58 12-MAR-14:30 35188.43 05-DEC-16:50
Cogeneration:ElectricityPurchased 443.40 2146.58 12-MAR-14:30 35188.43 05-DEC-16:50
General:Cogeneration:ElectricityPurchased 443.40 2146.58 12-MAR-14:30 35188.43 05-DEC-16:50
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 443.40 2146.58 12-MAR-14:30 35188.43 05-DEC-16:50
ElectricityNet:Plant 443.40 2146.58 12-MAR-14:30 35188.43 05-DEC-16:50
Cogeneration:ElectricityNet 443.40 2146.58 12-MAR-14:30 35188.43 05-DEC-16:50
General:Cogeneration:ElectricityNet 443.40 2146.58 12-MAR-14:30 35188.43 05-DEC-16:50
Electricity:HVAC 36.12 0.00 01-JAN-00:10 10814.86 16-OCT-11:10
General:Fans:Electricity 25.99 0.00 01-JAN-00:10 2215.27 02-JAN-07:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 10.13 0.00 01-JAN-00:10 8657.64 16-OCT-11:10
General:Cooling:Electricity 10.13 0.00 01-JAN-00:10 8657.64 16-OCT-11:10
ExteriorLights:Electricity 92.57 0.00 01-JAN-07:00 6958.21 01-JAN-06:10
General:ExteriorLights:Electricity 92.57 0.00 01-JAN-07:00 6958.21 01-JAN-06:10
Electricity:Plant 24.69 483.00 01-JAN-00:10 1799.35 31-JAN-12:40
WaterSystems:Electricity 24.69 483.00 01-JAN-00:10 1799.35 31-JAN-12:40
Water Heater:WaterSystems:Electricity 24.69 483.00 01-JAN-00:10 1799.35 31-JAN-12:40


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 1.53 0.00 01-JAN-00:10 17274.98 02-JAN-07:10
NaturalGas:HVAC 1.53 0.00 01-JAN-00:10 17274.98 02-JAN-07:10
Heating:NaturalGas 1.53 0.00 01-JAN-00:10 17274.98 02-JAN-07:10
General:Heating:NaturalGas 1.53 0.00 01-JAN-00:10 17274.98 02-JAN-07:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Facility 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 120.43 0.00 01-JAN-00:10 53136.72 16-OCT-12:00
EnergyTransfer:Building 72.84 0.00 01-JAN-00:10 22381.86 16-OCT-12:00
EnergyTransfer:Zone:ZONE1 OFFICE 34.34 0.00 01-JAN-00:10 12708.31 03-JAN-07:10
Heating:EnergyTransfer 3.94 0.00 01-JAN-00:10 14390.58 02-JAN-07:10
Heating:EnergyTransfer:Zone:ZONE1 OFFICE 2.64 0.00 01-JAN-00:10 12708.31 03-JAN-07:10
General:Heating:EnergyTransfer 3.94 0.00 01-JAN-00:10 14390.58 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE 2.64 0.00 01-JAN-00:10 12708.31 03-JAN-07:10
Cooling:EnergyTransfer 68.90 0.00 01-JAN-00:10 22381.86 16-OCT-12:00
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE 31.70 0.00 01-JAN-00:10 10423.39 16-OCT-11:10
General:Cooling:EnergyTransfer 68.90 0.00 01-JAN-00:10 22381.86 16-OCT-12:00
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE 31.70 0.00 01-JAN-00:10 10423.39 16-OCT-11:10
EnergyTransfer:Zone:ZONE2 FINE STORAGE 38.50 0.00 01-JAN-00:10 15714.08 04-JUL-16:50
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE 1.30 0.00 01-JAN-00:10 7764.20 03-JAN-02:10
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE 1.30 0.00 01-JAN-00:10 7764.20 03-JAN-02:10
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE 37.20 0.00 01-JAN-00:10 15714.08 04-JUL-16:50
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE 37.20 0.00 01-JAN-00:10 15714.08 04-JUL-16:50
EnergyTransfer:Zone:ZONE3 BULK STORAGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:HVAC 47.59 0.00 01-JAN-00:10 32170.25 17-AUG-15:00
HeatingCoils:EnergyTransfer 1.04 0.00 01-JAN-00:10 12759.81 02-JAN-07:10
CoolingCoils:EnergyTransfer 46.55 0.00 01-JAN-00:10 32170.25 17-AUG-15:00
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
ZONE1 OFFICE 0.000 0.000 2.636 -31.705 0.000 0.000 9.280 18.723 31.946 9.876 0.000 0.235 0.000 0.000 -6.977 0.000 -14.036 -19.978
ZONE2 FINE STORAGE 0.000 0.000 1.305 -37.197 0.000 0.000 21.119 59.181 0.000 73.304 0.000 0.225 0.002 0.000 -17.029 0.000 -33.336 -67.574
ZONE3 BULK STORAGE 0.000 0.000 0.000 0.000 0.000 0.000 50.472 72.823 107.344 636.099 0.000 4.623 0.009 0.000 -117.510 0.000 -240.257 -513.595
Total Facility 0.000 0.000 3.941 -68.901 0.000 0.000 80.871 150.728 139.290 719.280 0.000 5.084 0.012 0.000 -141.515 0.000 -287.629 -601.146


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
ZONE1 OFFICE 29-APR-07:02 0.00 0.00 0.00 -20678.11 0.00 0.00 801.66 1205.23 1912.50 0.00 0.00 0.00 16926.48 0.00 -114.50 0.00 -53.26 0.00
ZONE2 FINE STORAGE 30-JUL-13:33 0.00 0.00 0.00 -38753.95 0.00 0.00 0.00 352.65 0.00 9954.62 0.00 0.00 29178.42 0.00 -0.00 0.00 -731.74 0.00
ZONE3 BULK STORAGE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 30-JUL-13:33 0.00 0.00 0.00 -38753.95 0.00 0.00 0.00 1103.16 573.75 124945.86 0.00 0.00 0.00 0.00 0.00 0.00 -9069.85 -78798.96


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
ZONE1 OFFICE 02-JAN-07:01 0.00 0.00 26022.92 0.00 0.00 0.00 267.82 695.03 956.25 0.00 0.00 0.00 0.00 0.00 -219.81 0.00 -2854.02 -24868.18
ZONE2 FINE STORAGE 02-JAN-07:01 0.00 0.00 23716.38 0.00 0.00 0.00 671.03 4231.83 0.00 0.00 0.00 0.00 0.00 0.00 -436.68 0.00 -1416.22 -26766.35
ZONE3 BULK STORAGE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-JAN-07:01 0.00 0.00 49739.30 0.00 0.00 0.00 2463.07 10869.24 3006.28 0.00 0.00 0.00 0.00 0.00 -6165.10 0.00 -12290.38 -47622.41



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-OFFICE 1.0541 0.0000 12.7487 1.0000 Calculated from schedules 0.1023 1.0541 0.0970 1.0000 Not calculated 0.1023 0.0970    
PSZ-FINE STORAGE 2.3134 0.0000 30.0000 1.0000 Calculated from schedules 0.4247 2.3134 0.1836 1.0000 Not calculated 0.4247 0.1836    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-OFFICE 1.0541 0.0000 12.7487 1.0000 Calculated from schedules 0.1023 1.0541 1.0000 1.0000 Not calculated 0.1023 0.0970    
PSZ-FINE STORAGE 2.3134 0.0000 30.0000 1.0000 Calculated from schedules 0.4247 2.3134 1.0000 1.0000 Not calculated 0.4247 0.1836    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
ZONE1 OFFICE PSZ-OFFICE 0.000000 12.7487 0.000432 236.88 0.1023 1.0000 0.1023 1.000 0.1023
ZONE2 FINE STORAGE PSZ-FINE STORAGE 0.000000 30.0000 0.000305 1393.41 0.4247 1.0000 0.4247 1.000 0.4247


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-OFFICE 0.000000 12.75 0.000432 236.8796 0.1023 0.1023 0.1023
PSZ-FINE STORAGE 0.000000 30.00 0.000305 1393.4097 0.4247 0.4247 0.4247


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
ZONE1 OFFICE PSZ-OFFICE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.0541 1.0541 1.0541 No 0.1023 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ZONE2 FINE STORAGE PSZ-FINE STORAGE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 2.3134 2.3134 2.3134 No 0.4247 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-OFFICE 1.0541 1.0541 1.0541 1.0541 0.1023 1.0000
PSZ-FINE STORAGE 2.3134 2.3134 2.3134 2.3134 0.4247 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
ZONE1 OFFICE PSZ-OFFICE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.0541 1.0541 1.0541 No 0.1023 0.4197 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ZONE2 FINE STORAGE PSZ-FINE STORAGE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 2.3134 2.3134 2.3134 No 0.4247 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-OFFICE 1.0541 1.0541 1.0541 1.0541 0.1023 1.0000
PSZ-FINE STORAGE 2.3134 2.3134 2.3134 2.3134 0.4247 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Total gross floor area [m2] 4835.13
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
ZONE1 OFFICE 236.88 236.88 0.00 69.73
ZONE2 FINE STORAGE 1393.41 1393.41 0.00 69.73
ZONE3 BULK STORAGE 3204.84 3204.84 0.00 69.73
Totals 4835.13 4835.13 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.33
Number of hours cooling loads not met 0.00
Number of hours not met 0.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 1.53 17274.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 10.13 8657.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 150.73 15490.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 92.57 6958.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 139.29 10112.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 1152.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 25.99 2215.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 24.69 1799.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 139.29 443.40
Natural Gas 0.00 1.53
Additional 0.00 0.00
Total 139.29 444.93


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 31.17
Space Heating 0.00
Space Cooling 2.10
Fans (All) 5.38
Service Water Heating 5.11
Receptacle Equipment 28.81
Miscellaneous (All) 91.70
Subtotal 91.70


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.32
Service Water Heating 0.00
Miscellaneous (All) 0.32
Subtotal 0.32


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 33.88
Space Heating 0.34
Space Cooling 2.28
Fans (All) 5.84
Service Water Heating 5.55
Receptacle Equipment 31.31
Miscellaneous 20.81


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2688. 8760.
LTG_SCH_BULK_STORAGE 1777. 8760.
LTG_SCH_FINE_STORAGE 1777. 8760.
OFFICE_PLUG_SCH 4700. 8760.
BULK STORAGE PLUG SCHEDULE 3744. 7488.
BLDG_OCC_SCH 2861. 3744.
OFFICE PEOPLE SCHEDULE 2861. 3744.
FANSCHED 3432. 3432.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
OFFICE DHW SCHEDULE 1825. 5016.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 5550. 8760.
EXTERIOR LIGHT SCHEDULE 5475. 5475.
ALWAYS OFF SCHEDULE 0. 0.
OA DAMPER OFF DURING OFF HRS SCHEDULE 2808. 2808.
OA DAMPER ALWAYS ON SCHEDULE 8760. 8760.
MINOA_SCHED 8760. 8760.
ALWAYS ON SCHEDULE 8760. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
INFIL_DOOR_OPENING_SCH 1154. 3380.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 2600. 2600.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6935. 8760.
SZ_SYSTEM_OA_MAX_FRAC_SCH 6132. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
BULK STORAGE HEATING SETPOINT SCHEDULE ZONE3 BULK STORAGE HEATING SP January 10.00 365 10.00 365
OFFICE HEATING SCHEDULE ZONE1 OFFICE DUAL SP CONTROL January 21.10 365 15.60 365
OFFICE COOLING SCHEDULE ZONE1 OFFICE DUAL SP CONTROL July 23.90 365 29.40 365
FINE STORAGE HEATING SETPOINT SCHEDULE ZONE2 FINE STORAGE DUAL SP CONTROL January 15.56 365 15.56 365
FINE STORAGE COOLING SETPOINT SCHEDULE ZONE2 FINE STORAGE DUAL SP CONTROL July 26.70 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
ZONE1 OFFICE 8325.83 434.17 0.00 0.00 0.00
ZONE2 FINE STORAGE 7796.83 963.17 0.00 0.00 0.00
ZONE3 BULK STORAGE 7415.33 1344.67 0.00 0.00 0.00
Min 7415.33 434.17 0.00 0.00 0.00
Max 8325.83 1344.67 0.00 0.00 0.00
Average 7846.00 914.00 0.00 0.00 0.00
Sum 23538.00 2742.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
ZONE1 OFFICE 33026.00 1.00 0.00 0.00 0.00
ZONE2 FINE STORAGE 62373.50 20345.50 0.00 0.00 0.00
ZONE3 BULK STORAGE 146669.33 44523.67 0.00 0.00 0.00
Min 33026.00 1.00 0.00 0.00 0.00
Max 146669.33 44523.67 0.00 0.00 0.00
Average 80689.61 21623.39 0.00 0.00 0.00
Sum 242068.83 64870.17 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
ZONE1 OFFICE 7348.67 1411.33 0.00 0.00 0.00
ZONE2 FINE STORAGE 6505.50 2254.50 0.00 0.00 0.00
ZONE3 BULK STORAGE 6516.17 2243.83 0.00 0.00 0.00
Min 6505.50 1411.33 0.00 0.00 0.00
Max 7348.67 2254.50 0.00 0.00 0.00
Average 6790.11 1969.89 0.00 0.00 0.00
Sum 20370.33 5909.67 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
ZONE1 OFFICE 32620.50 406.50 0.00 0.00 0.00
ZONE2 FINE STORAGE 53673.50 29045.50 0.00 0.00 0.00
ZONE3 BULK STORAGE 134411.50 56781.50 0.00 0.00 0.00
Min 32620.50 406.50 0.00 0.00 0.00
Max 134411.50 56781.50 0.00 0.00 0.00
Average 73568.50 28744.50 0.00 0.00 0.00
Sum 220705.50 86233.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 10:43:54

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
ZONE1 OFFICE 0.00 0.00 8760.00 0.00
ZONE2 FINE STORAGE 0.00 0.00 8760.00 0.00
ZONE3 BULK STORAGE 0.00 8760.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 8760.00 0.00
Average 0.00 2920.00 5840.00 0.00
Sum 0.00 8760.00 17520.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
ZONE1 OFFICE 0.00 0.00 33027.00 0.00
ZONE2 FINE STORAGE 0.00 0.00 82719.00 0.00
ZONE3 BULK STORAGE 0.00 191193.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 191193.00 82719.00 0.00
Average 0.00 63731.00 38582.00 0.00
Sum 0.00 191193.00 115746.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.666955E+09 3181.49 18-JAN-14:50 23.27 14.80 0.594762E+09 768.98 19-JAN-13:30 21.50 15.64
February 0.536919E+09 3218.84 03-FEB-15:20 22.33 9.30 0.550058E+09 768.97 01-FEB-13:50 22.33 9.30
March 0.685389E+09 4016.82 23-MAR-15:50 21.17 17.23 0.641209E+09 769.01 23-MAR-15:50 21.17 17.23
April 0.219643E+10 20680.60 29-APR-07:02 14.33 11.79 0.625987E+09 879.26 29-APR-07:10 14.33 11.79
May 0.278025E+10 19818.92 20-MAY-07:03 14.17 11.80 0.656391E+09 879.31 06-MAY-07:10 14.17 11.80
June 0.397152E+10 18362.50 03-JUN-07:02 17.17 14.02 0.661597E+09 879.39 24-JUN-07:10 18.17 14.44
July 0.525745E+10 17931.41 08-JUL-07:02 17.00 14.51 0.639411E+09 879.39 22-JUL-07:10 19.33 17.20
August 0.550494E+10 16542.37 21-AUG-07:03 17.00 15.07 0.690102E+09 879.39 19-AUG-07:10 17.00 15.07
September 0.415798E+10 19681.14 02-SEP-07:02 16.17 12.63 0.637029E+09 879.39 30-SEP-07:10 23.92 14.07
October 0.376151E+10 19782.54 07-OCT-07:02 17.00 12.30 0.634715E+09 879.39 03-OCT-07:10 17.00 12.30
November 0.131211E+10 3548.67 04-NOV-15:00 16.70 10.78 0.595088E+09 768.99 10-NOV-13:30 20.50 16.08
December 0.872894E+09 3474.68 05-DEC-15:10 24.67 13.10 0.607624E+09 768.98 07-DEC-14:09 20.67 15.41
                     
Annual Sum or Average 0.317043E+11         0.753397E+10        
Minimum of Months 0.536919E+09 3181.49   14.17 9.30 0.550058E+09 768.97   14.17 9.30
Maximum of Months 0.550494E+10 20680.60   24.67 17.23 0.690102E+09 879.39   23.92 17.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.130706E+10 4295.39 28-JAN-08:70 8.67 6.43 0.119137E+10 1929.35 18-JAN-14:30 8.67 6.43
February 0.152506E+10 3848.10 25-FEB-12:55 10.00 9.41 0.109192E+10 1920.95 03-FEB-15:20 10.00 9.41
March 0.198405E+10 4966.97 29-MAR-15:00 8.00 6.48 0.128041E+10 2076.57 23-MAR-14:50 8.00 6.48
April 0.195682E+10 4396.68 27-APR-14:10 20.03 15.47 0.152075E+10 2246.83 26-APR-14:20 20.03 15.47
May 0.233492E+10 6492.86 03-MAY-13:30 23.50 15.91 0.165814E+10 2246.86 04-MAY-12:39 23.33 16.64
June 0.367046E+10 30075.26 25-JUN-14:52 21.00 16.52 0.181018E+10 2246.88 21-JUN-13:50 21.00 16.52
July 0.749641E+10 38749.73 30-JUL-13:33 24.00 19.50 0.184002E+10 2246.92 31-JUL-14:39 26.33 20.59
August 0.739178E+10 31379.70 19-AUG-17:12 23.67 17.53 0.198132E+10 2246.91 19-AUG-13:50 23.67 17.53
September 0.367257E+10 29407.84 04-SEP-14:45 21.00 16.06 0.177674E+10 2246.87 06-SEP-14:20 22.00 17.40
October 0.285080E+10 27040.96 01-OCT-14:10 23.83 19.83 0.172593E+10 2246.87 18-OCT-14:00 22.00 18.09
November 0.161004E+10 4683.96 01-NOV-07:13 11.33 11.16 0.131153E+10 2002.76 18-NOV-14:20 25.33 14.85
December 0.139644E+10 4797.60 01-DEC-08:63 9.33 9.16 0.125778E+10 1974.23 05-DEC-15:20 24.33 12.97
                     
Annual Sum or Average 0.371964E+11         0.184461E+11        
Minimum of Months 0.130706E+10 3848.10   8.00 6.43 0.109192E+10 1920.95   8.00 6.43
Maximum of Months 0.749641E+10 38749.73   24.00 19.83 0.198132E+10 2246.92   26.33 20.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83 8.36 0.229687E+10 3517.78 24-JAN-15:00 24.00 15.05
February 0.00 0.00 01-FEB-00:10 13.23 11.35 0.217132E+10 3639.20 03-FEB-15:09 22.67 9.08
March 0.00 0.00 01-MAR-00:10 7.63 6.62 0.248870E+10 3797.12 23-MAR-14:50 22.17 17.39
April 0.00 0.00 01-APR-00:10 9.63 8.61 0.299131E+10 4604.48 26-APR-14:09 25.50 16.68
May 0.00 0.00 01-MAY-00:10 15.20 14.50 0.346132E+10 4929.40 04-MAY-12:50 23.17 16.65
June 0.00 0.00 01-JUN-00:10 13.07 12.03 0.395840E+10 5663.33 30-JUN-15:30 22.85 17.86
July 0.00 0.00 01-JUL-00:10 16.43 15.81 0.465722E+10 6290.03 31-JUL-12:39 28.00 21.19
August 0.00 0.00 01-AUG-00:10 18.07 17.20 0.510905E+10 6276.17 17-AUG-14:09 27.78 21.12
September 0.00 0.00 01-SEP-00:10 16.07 14.83 0.415464E+10 6145.84 30-SEP-14:39 32.00 17.28
October 0.00 0.00 01-OCT-00:10 18.42 17.39 0.396547E+10 6019.91 16-OCT-12:00 34.10 16.81
November 0.00 0.00 01-NOV-00:10 14.77 11.07 0.274947E+10 4212.88 01-NOV-14:30 17.00 13.18
December 0.00 0.00 01-DEC-00:10 10.63 5.44 0.252496E+10 3757.65 05-DEC-15:30 24.00 12.83
                     
Annual Sum or Average 0.00         0.405287E+11        
Minimum of Months 0.00 0.00   7.63 5.44 0.217132E+10 3517.78   17.00 9.08
Maximum of Months 0.00 0.00   18.42 17.39 0.510905E+10 6290.03   34.10 21.19



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.574168E+09 26023.12 02-JAN-07:01 11.00
February 0.322837E+09 23931.69 28-FEB-07:03 11.33
March 0.460908E+09 25840.61 30-MAR-06:02 5.58
April 0.144503E+09 25341.40 01-APR-06:02 7.67
May 0.124792E+09 2278.28 15-MAY-07:03 13.50
June 0.106502E+09 1511.12 07-JUN-06:20 14.00
July 88937870.87 1755.42 24-JUL-06:07 16.17
August 0.100627E+09 1537.66 28-AUG-06:10 14.00
September 94653786.28 1529.29 30-SEP-06:07 23.78
October 95535458.23 1703.69 19-OCT-06:15 11.67
November 0.180205E+09 9228.66 24-NOV-08:63 10.67
December 0.342332E+09 25603.19 15-DEC-07:02 6.50
         
Annual Sum or Average 0.263600E+10      
Minimum of Months 88937870.87 1511.12   5.58
Maximum of Months 0.574168E+09 26023.12   23.78



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.264821E+09 23716.39 02-JAN-07:01 11.00
February 84378530.58 1786.19 01-FEB-12:00 26.00
March 0.101161E+09 1094.85 11-MAR-11:00 24.00
April 97330897.18 1638.89 01-APR-12:00 24.00
May 68699336.29 1061.74 25-MAY-07:00 14.00
June 66803021.07 1030.68 06-JUN-07:00 17.00
July 56029729.39 933.18 08-JUL-07:00 17.00
August 70054573.10 956.48 21-AUG-07:00 17.00
September 71224487.95 1678.21 29-SEP-07:45 28.00
October 93794622.90 2320.54 14-OCT-08:40 29.67
November 0.114286E+09 1578.17 18-NOV-13:00 26.00
December 0.216028E+09 2289.51 16-DEC-13:00 26.00
         
Annual Sum or Average 0.130461E+10      
Minimum of Months 56029729.39 933.18   11.00
Maximum of Months 0.264821E+09 23716.39   29.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.159926E+10 1285.93 02-JAN-16:49 0.267964E+10 1912.50 02-JAN-08:09
February 0.143853E+10 1274.48 27-FEB-16:00 0.243949E+10 1912.50 01-FEB-08:09
March 0.162851E+10 1257.11 16-MAR-07:10 0.277107E+10 1912.50 01-MAR-08:09
April 0.152665E+10 1247.07 15-APR-07:10 0.263007E+10 1912.50 01-APR-07:10
May 0.157414E+10 1244.71 09-MAY-07:10 0.272536E+10 1912.50 01-MAY-07:10
June 0.154791E+10 1238.50 09-JUN-07:10 0.267579E+10 1912.50 01-JUN-07:10
July 0.153839E+10 1230.25 12-JUL-07:10 0.267964E+10 1912.50 01-JUL-07:10
August 0.161167E+10 1245.69 21-AUG-07:10 0.277107E+10 1912.50 01-AUG-07:10
September 0.153336E+10 1261.03 18-SEP-07:10 0.263007E+10 1912.50 01-SEP-07:10
October 0.158918E+10 1261.84 24-OCT-07:10 0.267964E+10 1912.50 02-OCT-07:10
November 0.153142E+10 1285.93 06-NOV-16:00 0.258435E+10 1912.50 01-NOV-07:10
December 0.160388E+10 1285.93 01-DEC-16:40 0.267964E+10 1912.50 01-DEC-08:09
             
Annual Sum or Average 0.187229E+11     0.319458E+11    
Minimum of Months 0.143853E+10 1230.25   0.243949E+10 1912.50  
Maximum of Months 0.162851E+10 1285.93   0.277107E+10 1912.50  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.559341E+10 5995.09 02-JAN-15:50 0.00 0.00
February 0.461799E+10 5495.50 25-FEB-15:50 0.00 0.00
March 0.503974E+10 5289.79 01-MAR-16:49 0.00 0.00
April 0.456398E+10 5289.79 01-APR-07:10 0.00 0.00
May 0.450986E+10 4995.91 09-MAY-08:09 0.00 0.00
June 0.449606E+10 4848.97 09-JUN-07:10 0.00 0.00
July 0.449971E+10 4995.91 05-JUL-08:09 0.00 0.00
August 0.486172E+10 5289.79 31-AUG-07:10 0.00 0.00
September 0.475372E+10 5495.50 21-SEP-08:09 0.00 0.00
October 0.529640E+10 5995.09 27-OCT-08:09 0.00 0.00
November 0.520655E+10 5995.09 06-NOV-15:39 0.00 0.00
December 0.574201E+10 5995.09 01-DEC-15:00 0.00 0.00
           
Annual Sum or Average 0.591811E+11     0.00 0.00
Minimum of Months 0.449606E+10 4848.97   0.00 0.00
Maximum of Months 0.574201E+10 5995.09   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.680398E+10 7716.84 02-JAN-15:00 0.885613E+10 8200.12 02-JAN-08:09
February 0.573576E+10 7427.98 25-FEB-16:40 0.814764E+10 8200.12 01-FEB-08:09
March 0.625795E+10 6808.98 01-MAR-16:00 0.957200E+10 8200.12 01-MAR-08:09
April 0.563717E+10 5942.38 01-APR-06:10 0.885613E+10 8200.12 01-APR-07:10
May 0.566227E+10 4951.99 04-MAY-06:10 0.921037E+10 8200.12 01-MAY-07:10
June 0.557859E+10 4951.99 06-JUN-06:10 0.921037E+10 8200.12 01-JUN-07:10
July 0.553580E+10 4951.99 08-JUL-06:10 0.885613E+10 8200.12 01-JUL-07:10
August 0.595949E+10 5942.38 21-AUG-06:10 0.956462E+10 8200.12 01-AUG-07:10
September 0.582576E+10 6313.78 21-SEP-08:09 0.884875E+10 8200.12 01-SEP-07:10
October 0.644622E+10 7427.98 28-OCT-07:10 0.886351E+10 8200.12 02-OCT-07:10
November 0.639915E+10 8418.38 25-NOV-15:00 0.850188E+10 8200.12 01-NOV-07:10
December 0.698133E+10 8418.38 15-DEC-15:00 0.885613E+10 8200.12 01-DEC-08:09
             
Annual Sum or Average 0.728235E+11     0.107344E+12    
Minimum of Months 0.553580E+10 4951.99   0.814764E+10 8200.12  
Maximum of Months 0.698133E+10 8418.38   0.957200E+10 8200.12  



Table of Contents

Report: SpaceGainsMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.138726E+10 0.159926E+10 0.267964E+10 0.00 0.00 0.00 0.00 4286510.29 0.135523E+10
February 0.127628E+10 0.143853E+10 0.243949E+10 0.00 0.00 0.00 0.00 1457895.12 0.143410E+10
March 0.149825E+10 0.162851E+10 0.277107E+10 0.00 0.00 0.00 0.00 25399.86 0.179774E+10
April 0.138726E+10 0.152665E+10 0.263007E+10 0.00 0.00 0.00 0.00 5157160.47 0.121743E+10
May 0.144276E+10 0.157414E+10 0.272536E+10 0.00 0.00 0.00 0.00 66789.32 0.136774E+10
June 0.144276E+10 0.154791E+10 0.267579E+10 0.00 0.00 0.00 0.00 1244183.58 0.975320E+09
July 0.138726E+10 0.153839E+10 0.267964E+10 0.00 0.00 0.00 0.00 32867842.64 0.686718E+09
August 0.149825E+10 0.161167E+10 0.277107E+10 0.00 0.00 0.00 0.00 33302978.92 0.784579E+09
September 0.138726E+10 0.153336E+10 0.263007E+10 0.00 0.00 0.00 0.00 52052859.41 0.844993E+09
October 0.138726E+10 0.158918E+10 0.267964E+10 0.00 0.00 0.00 0.00 97793823.92 0.917452E+09
November 0.133177E+10 0.153142E+10 0.258435E+10 0.00 0.00 0.00 0.00 2020663.37 0.134027E+10
December 0.138726E+10 0.160388E+10 0.267964E+10 0.00 0.00 0.00 0.00 5198030.67 0.131486E+10
                   
Annual Sum or Average 0.168137E+11 0.187229E+11 0.319458E+11 0.00 0.00 0.00 0.00 0.235474E+09 0.140364E+11
Minimum of Months 0.127628E+10 0.143853E+10 0.243949E+10 0.00 0.00 0.00 0.00 25399.86 0.686718E+09
Maximum of Months 0.149825E+10 0.162851E+10 0.277107E+10 0.00 0.00 0.00 0.00 97793823.92 0.179774E+10



Table of Contents

Report: SpaceGainsMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.326447E+10 0.559341E+10 0.00 0.00 0.00 0.00 0.00 19548665.65 0.241460E+10
February 0.300332E+10 0.461799E+10 0.00 0.00 0.00 0.00 0.00 1086193.78 0.305399E+10
March 0.352563E+10 0.503974E+10 0.00 0.00 0.00 0.00 0.00 208246.64 0.367395E+10
April 0.326447E+10 0.456398E+10 0.00 0.00 0.00 0.00 0.00 6366042.81 0.295080E+10
May 0.339505E+10 0.450986E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.369727E+10
June 0.339505E+10 0.449606E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.262846E+10
July 0.326447E+10 0.449971E+10 0.00 0.00 0.00 0.00 0.00 3407752.92 0.212622E+10
August 0.352563E+10 0.486172E+10 0.00 0.00 0.00 0.00 0.00 2089274.76 0.245622E+10
September 0.326447E+10 0.475372E+10 0.00 0.00 0.00 0.00 0.00 46962403.96 0.220136E+10
October 0.326447E+10 0.529640E+10 0.00 0.00 0.00 0.00 0.00 0.119892E+09 0.270760E+10
November 0.313390E+10 0.520655E+10 0.00 0.00 0.00 0.00 0.00 10227329.19 0.278223E+10
December 0.326447E+10 0.574201E+10 0.00 0.00 0.00 0.00 0.00 15553049.58 0.264315E+10
                   
Annual Sum or Average 0.395654E+11 0.591811E+11 0.00 0.00 0.00 0.00 0.00 0.225341E+09 0.333358E+11
Minimum of Months 0.300332E+10 0.449606E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.212622E+10
Maximum of Months 0.352563E+10 0.574201E+10 0.00 0.00 0.00 0.00 0.00 0.119892E+09 0.369727E+10



Table of Contents

Report: SpaceGainsMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.750829E+10 0.680398E+10 0.885613E+10 0.00 0.00 0.00 0.00 0.609321E+09 0.103262E+11
February 0.690763E+10 0.573576E+10 0.814764E+10 0.00 0.00 0.00 0.00 86972576.02 0.136387E+11
March 0.810895E+10 0.625795E+10 0.957200E+10 0.00 0.00 0.00 0.00 0.150785E+09 0.163351E+11
April 0.750829E+10 0.563717E+10 0.885613E+10 0.00 0.00 0.00 0.00 0.282771E+09 0.128293E+11
May 0.780862E+10 0.566227E+10 0.921037E+10 0.00 0.00 0.00 0.00 0.00 0.176321E+11
June 0.780862E+10 0.557859E+10 0.921037E+10 0.00 0.00 0.00 0.00 0.00 0.134627E+11
July 0.750829E+10 0.553580E+10 0.885613E+10 0.00 0.00 0.00 0.00 0.00 0.146096E+11
August 0.810895E+10 0.595949E+10 0.956462E+10 0.00 0.00 0.00 0.00 0.00 0.168793E+11
September 0.750829E+10 0.582576E+10 0.884875E+10 0.00 0.00 0.00 0.00 0.310391E+09 0.129569E+11
October 0.750829E+10 0.644622E+10 0.886351E+10 0.00 0.00 0.00 0.00 0.941814E+09 0.147935E+11
November 0.720796E+10 0.639915E+10 0.850188E+10 0.00 0.00 0.00 0.00 0.262629E+09 0.137439E+11
December 0.750829E+10 0.698133E+10 0.885613E+10 0.00 0.00 0.00 0.00 0.695832E+09 0.120060E+11
                   
Annual Sum or Average 0.910005E+11 0.728235E+11 0.107344E+12 0.00 0.00 0.00 0.00 0.334052E+10 0.169213E+12
Minimum of Months 0.690763E+10 0.553580E+10 0.814764E+10 0.00 0.00 0.00 0.00 0.00 0.103262E+11
Maximum of Months 0.810895E+10 0.698133E+10 0.957200E+10 0.00 0.00 0.00 0.00 0.941814E+09 0.176321E+11



Table of Contents

Report: PeakSpaceGainsMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1680.92 02-JAN-08:09 1285.93 02-JAN-16:49 1912.50 02-JAN-08:09 0.00 0.00 0.00 0.00 746.58 18-JAN-13:00 6656.68 09-JAN-07:10
February 1680.92 01-FEB-08:09 1274.48 27-FEB-16:00 1912.50 01-FEB-08:09 0.00 0.00 0.00 0.00 638.63 01-FEB-12:10 5272.00 10-FEB-07:05
March 1680.92 01-MAR-08:09 1257.11 16-MAR-07:10 1912.50 01-MAR-08:09 0.00 0.00 0.00 0.00 2.80 11-MAR-14:00 6229.97 30-MAR-06:05
April 1680.92 01-APR-07:10 1247.07 15-APR-07:10 1912.50 01-APR-07:10 0.00 0.00 0.00 0.00 754.99 26-APR-11:10 4814.83 17-APR-16:05
May 1680.92 01-MAY-07:10 1244.71 09-MAY-07:10 1912.50 01-MAY-07:10 0.00 0.00 0.00 0.00 34.85 03-MAY-12:00 4360.48 12-MAY-16:05
June 1680.92 01-JUN-07:10 1238.50 09-JUN-07:10 1912.50 01-JUN-07:10 0.00 0.00 0.00 0.00 339.42 29-JUN-11:10 3823.02 05-JUN-06:10
July 1680.92 01-JUL-07:10 1230.25 12-JUL-07:10 1912.50 01-JUL-07:10 0.00 0.00 0.00 0.00 1479.21 19-JUL-12:00 3811.96 17-JUL-06:10
August 1680.92 01-AUG-07:10 1245.69 21-AUG-07:10 1912.50 01-AUG-07:10 0.00 0.00 0.00 0.00 1458.98 18-AUG-12:00 4040.27 28-AUG-06:10
September 1680.92 01-SEP-07:10 1261.03 18-SEP-07:10 1912.50 01-SEP-07:10 0.00 0.00 0.00 0.00 4197.54 29-SEP-12:00 4020.85 20-SEP-06:10
October 1680.92 02-OCT-07:10 1261.84 24-OCT-07:10 1912.50 02-OCT-07:10 0.00 0.00 0.00 0.00 4614.22 16-OCT-11:10 5000.72 19-OCT-06:05
November 1680.92 01-NOV-07:10 1285.93 06-NOV-16:00 1912.50 01-NOV-07:10 0.00 0.00 0.00 0.00 114.38 19-NOV-13:00 4879.00 30-NOV-07:10
December 1680.92 01-DEC-08:09 1285.93 01-DEC-16:40 1912.50 01-DEC-08:09 0.00 0.00 0.00 0.00 751.24 19-DEC-13:00 5744.54 22-DEC-07:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1680.92   1230.25   1912.50   0.00 0.00 0.00 0.00 2.80   3811.96  
Maximum of Months 1680.92   1285.93   1912.50   0.00 0.00 0.00 0.00 4614.22   6656.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 3955.50 02-JAN-08:09 5995.09 02-JAN-15:50 0.00 0.00 0.00 0.00 0.00 1027.06 15-JAN-10:00 4402.02 27-JAN-05:00
February 3955.50 01-FEB-08:09 5495.50 25-FEB-15:50 0.00 0.00 0.00 0.00 0.00 257.10 01-FEB-12:00 4502.95 25-FEB-16:10
March 3955.50 01-MAR-08:09 5289.79 01-MAR-16:49 0.00 0.00 0.00 0.00 0.00 66.33 12-MAR-10:00 6573.14 28-MAR-15:10
April 3955.50 01-APR-07:10 5289.79 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 461.20 02-APR-13:00 7224.27 17-APR-16:25
May 3955.50 01-MAY-07:10 4995.91 09-MAY-08:09 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 6464.04 12-MAY-16:00
June 3955.50 01-JUN-07:10 4848.97 09-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JUN-00:10 3601.25 12-JUN-16:00
July 3955.50 01-JUL-07:10 4995.91 05-JUL-08:09 0.00 0.00 0.00 0.00 0.00 220.75 31-JUL-13:00 4067.36 20-JUL-18:00
August 3955.50 01-AUG-07:10 5289.79 31-AUG-07:10 0.00 0.00 0.00 0.00 0.00 177.82 17-AUG-14:00 3093.93 21-AUG-17:00
September 3955.50 01-SEP-07:10 5495.50 21-SEP-08:09 0.00 0.00 0.00 0.00 0.00 2249.71 29-SEP-15:10 3732.42 02-SEP-15:10
October 3955.50 02-OCT-07:10 5995.09 27-OCT-08:09 0.00 0.00 0.00 0.00 0.00 2171.04 14-OCT-15:10 4141.18 07-OCT-08:00
November 3955.50 01-NOV-07:10 5995.09 06-NOV-15:39 0.00 0.00 0.00 0.00 0.00 736.66 19-NOV-13:00 4481.11 30-NOV-07:10
December 3955.50 01-DEC-08:09 5995.09 01-DEC-15:00 0.00 0.00 0.00 0.00 0.00 781.43 25-DEC-12:00 4520.64 13-DEC-08:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 3955.50   4848.97   0.00 0.00 0.00 0.00 0.00 0.00   3093.93  
Maximum of Months 3955.50   5995.09   0.00 0.00 0.00 0.00 0.00 2249.71   7224.27  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 9097.65 02-JAN-08:09 7716.84 02-JAN-15:00 8200.12 02-JAN-08:09 0.00 0.00 0.00 0.00 8510.67 14-JAN-13:10 19527.52 27-JAN-05:00
February 9097.65 01-FEB-08:09 7427.98 25-FEB-16:40 8200.12 01-FEB-08:09 0.00 0.00 0.00 0.00 6656.08 01-FEB-12:00 23754.76 25-FEB-13:10
March 9097.65 01-MAR-08:09 6808.98 01-MAR-16:00 8200.12 01-MAR-08:09 0.00 0.00 0.00 0.00 5914.91 11-MAR-13:10 28897.86 28-MAR-08:00
April 9097.65 01-APR-07:10 5942.38 01-APR-06:10 8200.12 01-APR-07:10 0.00 0.00 0.00 0.00 8298.46 01-APR-12:10 29438.16 17-APR-16:00
May 9097.65 01-MAY-07:10 4951.99 04-MAY-06:10 8200.12 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 29106.10 12-MAY-16:00
June 9097.65 01-JUN-07:10 4951.99 06-JUN-06:10 8200.12 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:10 15315.85 12-JUN-16:00
July 9097.65 01-JUL-07:10 4951.99 08-JUL-06:10 8200.12 01-JUL-07:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:10 21138.05 20-JUL-09:00
August 9097.65 01-AUG-07:10 5942.38 21-AUG-06:10 8200.12 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:10 15399.39 22-AUG-16:00
September 9097.65 01-SEP-07:10 6313.78 21-SEP-08:09 8200.12 01-SEP-07:10 0.00 0.00 0.00 0.00 12051.57 29-SEP-12:10 18955.75 02-SEP-15:00
October 9097.65 02-OCT-07:10 7427.98 28-OCT-07:10 8200.12 02-OCT-07:10 0.00 0.00 0.00 0.00 19669.08 16-OCT-10:00 21865.14 07-OCT-08:00
November 9097.65 01-NOV-07:10 8418.38 25-NOV-15:00 8200.12 01-NOV-07:10 0.00 0.00 0.00 0.00 5823.15 19-NOV-13:00 18658.93 01-NOV-08:00
December 9097.65 01-DEC-08:09 8418.38 15-DEC-15:00 8200.12 01-DEC-08:09 0.00 0.00 0.00 0.00 13611.43 18-DEC-11:00 21813.64 12-DEC-13:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 9097.65   4951.99   8200.12   0.00 0.00 0.00 0.00 0.00   15315.85  
Maximum of Months 9097.65   8418.38   8200.12   0.00 0.00 0.00 0.00 19669.08   29438.16  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3181.49 18-JAN-14:50 1680.92 1061.41 1912.50 0.00 0.00 0.00 0.00 0.00 46.12
February 3218.84 03-FEB-15:20 1680.92 1052.90 1912.50 0.00 0.00 0.00 0.00 0.00 115.90
March 4016.82 23-MAR-15:50 1680.92 1035.17 1912.50 0.00 0.00 0.00 0.00 0.00 264.34
April 20680.60 29-APR-07:02 8404.61 6026.14 9562.50 0.00 0.00 0.00 0.00 0.00 53.26
May 19818.92 20-MAY-07:03 6723.69 4719.89 7650.00 0.00 0.00 0.00 0.00 0.00 368.59
June 18362.50 03-JUN-07:02 8404.61 5834.69 9562.50 0.00 0.00 0.00 0.00 0.00 491.88
July 17931.41 08-JUL-07:02 8404.61 5884.20 9562.50 0.00 0.00 0.00 0.00 0.00 323.53
August 16542.37 21-AUG-07:03 6723.69 4982.77 7650.00 0.00 0.00 0.00 0.00 0.00 687.74
September 19681.14 02-SEP-07:02 8404.61 6157.26 9562.50 0.00 0.00 0.00 0.00 0.00 270.50
October 19782.54 07-OCT-07:02 8404.61 6151.39 9562.50 0.00 0.00 0.00 0.00 0.00 653.35
November 3548.67 04-NOV-15:00 1680.92 1055.64 1912.50 0.00 0.00 0.00 0.00 0.00 131.24
December 3474.68 05-DEC-15:10 1680.92 1057.12 1912.50 0.00 0.00 0.00 0.00 53.73 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3181.49   1680.92 1035.17 1912.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20680.60   8404.61 6157.26 9562.50 0.00 0.00 0.00 0.00 53.73 687.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4295.39 28-JAN-08:70 3955.50 5289.79 0.00 0.00 0.00 0.00 0.00 0.00 1999.72
February 3848.10 25-FEB-12:55 4192.83 6994.28 0.00 0.00 0.00 0.00 0.00 0.00 2487.57
March 4966.97 29-MAR-15:00 3955.50 2997.55 0.00 0.00 0.00 0.00 0.00 0.00 627.44
April 4396.68 27-APR-14:10 3955.50 3497.14 0.00 0.00 0.00 0.00 0.00 0.00 740.24
May 6492.86 03-MAY-13:30 3955.50 2997.55 0.00 0.00 0.00 0.00 0.00 0.00 571.57
June 30075.26 25-JUN-14:52 0.00 2057.14 0.00 0.00 0.00 0.00 0.00 0.00 1775.96
July 38749.73 30-JUL-13:33 0.00 1057.96 0.00 0.00 0.00 0.00 0.00 0.00 731.74
August 31379.70 19-AUG-17:12 0.00 2586.12 0.00 0.00 0.00 0.00 0.00 0.00 442.62
September 29407.84 04-SEP-14:45 0.00 940.41 0.00 0.00 0.00 0.00 0.00 0.00 1523.20
October 27040.96 01-OCT-14:10 0.00 1586.94 0.00 0.00 0.00 0.00 0.00 0.00 820.96
November 4683.96 01-NOV-07:13 11866.50 14546.92 0.00 0.00 0.00 0.00 0.00 0.00 3444.19
December 4797.60 01-DEC-08:63 11866.50 13224.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3848.10   0.00 940.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38749.73   11866.50 14546.92 0.00 0.00 0.00 0.00 0.00 0.00 3444.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 990.40 0.00 0.00 0.00 0.00 0.00 0.00 7597.13
February 0.00 01-FEB-00:10 0.00 990.40 2050.03 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 01-MAR-00:10 0.00 990.40 2050.03 0.00 0.00 0.00 0.00 0.00 6400.32
April 0.00 01-APR-00:10 0.00 990.40 2050.03 0.00 0.00 0.00 0.00 0.00 9312.54
May 0.00 01-MAY-00:10 0.00 990.40 2050.03 0.00 0.00 0.00 0.00 0.00 5792.53
June 0.00 01-JUN-00:10 0.00 990.40 2050.03 0.00 0.00 0.00 0.00 0.00 4637.84
July 0.00 01-JUL-00:10 0.00 990.40 2050.03 0.00 0.00 0.00 0.00 0.00 3675.08
August 0.00 01-AUG-00:10 0.00 990.40 2050.03 0.00 0.00 0.00 0.00 0.00 5394.24
September 0.00 01-SEP-00:10 0.00 990.40 2050.03 0.00 0.00 0.00 0.00 0.00 5913.22
October 0.00 01-OCT-00:10 0.00 990.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 01-NOV-00:10 0.00 990.40 2050.03 0.00 0.00 0.00 0.00 0.00 9119.41
December 0.00 01-DEC-00:10 0.00 990.40 2050.03 0.00 0.00 0.00 0.00 0.00 7136.02
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 990.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00   0.00 990.40 2050.03 0.00 0.00 0.00 0.00 0.00 9312.54



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.391933E+11 34874.79 14-JAN-16:00 0.583805E+09 17274.98 02-JAN-07:10
February 0.341992E+11 27864.77 25-FEB-16:00 0.226752E+09 8491.03 10-FEB-07:10
March 0.377855E+11 26761.18 09-MAR-16:00 0.412125E+09 13934.73 30-MAR-06:10
April 0.345972E+11 25858.22 21-APR-14:00 20515868.45 6464.60 01-APR-06:10
May 0.348610E+11 24939.22 09-MAY-07:19 782636.53 1304.39 15-MAY-07:10
June 0.349040E+11 27015.14 29-JUN-15:00 0.00 0.00 01-JUN-00:10
July 0.366454E+11 29898.35 31-JUL-13:39 0.00 0.00 01-JUL-00:10
August 0.391878E+11 31183.91 17-AUG-14:09 0.00 0.00 01-AUG-00:10
September 0.363237E+11 31513.65 29-SEP-15:50 0.00 0.00 01-SEP-00:10
October 0.387969E+11 32403.45 17-OCT-14:00 0.00 0.00 01-OCT-00:10
November 0.371972E+11 34832.95 30-NOV-16:49 38403717.59 4943.29 24-NOV-08:09
December 0.397084E+11 35188.43 05-DEC-16:49 0.249550E+09 10903.73 15-DEC-07:10
             
Annual Sum or Average 0.443400E+12     0.153193E+10    
Minimum of Months 0.341992E+11 24939.22   0.00 0.00  
Maximum of Months 0.397084E+11 35188.43   0.583805E+09 17274.98  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.139966E+11 0.933749E+10 0.115358E+11 0.00 0.213785E+10 0.00 0.00 69286712.83 0.00 0.00 0.00 0.211627E+10 0.00
February 0.117923E+11 0.791146E+10 0.105871E+11 0.00 0.196480E+10 0.00 0.00 19664528.22 0.00 0.00 0.00 0.192385E+10 0.00
March 0.129262E+11 0.800152E+10 0.123431E+11 0.00 0.230657E+10 0.00 0.00 45396537.28 0.00 0.00 0.00 0.216273E+10 0.00
April 0.117278E+11 0.700013E+10 0.114862E+11 0.00 0.213565E+10 0.00 0.00 0.204335E+09 0.00 0.00 0.00 0.204313E+10 0.00
May 0.117463E+11 0.661763E+10 0.119357E+11 0.00 0.222107E+10 0.00 0.00 0.243641E+09 0.00 0.00 0.00 0.209662E+10 0.00
June 0.116226E+11 0.611326E+10 0.118862E+11 0.00 0.222738E+10 0.00 0.00 0.102354E+10 0.00 0.00 0.00 0.203113E+10 0.00
July 0.115739E+11 0.641783E+10 0.115358E+11 0.00 0.218763E+10 0.00 0.00 0.289138E+10 0.00 0.00 0.00 0.203888E+10 0.00
August 0.124329E+11 0.693691E+10 0.123357E+11 0.00 0.234001E+10 0.00 0.00 0.305361E+10 0.00 0.00 0.00 0.208865E+10 0.00
September 0.121128E+11 0.742597E+10 0.114788E+11 0.00 0.213760E+10 0.00 0.00 0.116499E+10 0.00 0.00 0.00 0.200344E+10 0.00
October 0.133318E+11 0.844406E+10 0.115432E+11 0.00 0.214563E+10 0.00 0.00 0.126787E+10 0.00 0.00 0.00 0.206442E+10 0.00
November 0.131371E+11 0.884545E+10 0.110862E+11 0.00 0.205022E+10 0.00 0.00 62890463.31 0.00 0.00 0.00 0.201529E+10 0.00
December 0.143272E+11 0.952119E+10 0.115358E+11 0.00 0.213565E+10 0.00 0.00 83173876.85 0.00 0.00 0.00 0.210543E+10 0.00
                           
Annual Sum or Average 0.150728E+12 0.925729E+11 0.139290E+12 0.00 0.259901E+11 0.00 0.00 0.101298E+11 0.00 0.00 0.00 0.246898E+11 0.00
Minimum of Months 0.115739E+11 0.611326E+10 0.105871E+11 0.00 0.196480E+10 0.00 0.00 19664528.22 0.00 0.00 0.00 0.192385E+10 0.00
Maximum of Months 0.143272E+11 0.952119E+10 0.123431E+11 0.00 0.234001E+10 0.00 0.00 0.305361E+10 0.00 0.00 0.00 0.216273E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.583805E+09 0.00 0.00 0.00 0.00
February 0.00 0.00 0.226752E+09 0.00 0.00 0.00 0.00
March 0.00 0.00 0.412125E+09 0.00 0.00 0.00 0.00
April 0.00 0.00 20515868.45 0.00 0.00 0.00 0.00
May 0.00 0.00 782636.53 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 38403717.59 0.00 0.00 0.00 0.00
December 0.00 0.00 0.249550E+09 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.153193E+10 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.583805E+09 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY [] HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 14788.84 21-JAN-15:00 6958.21 01-JAN-06:10 10112.62 02-JAN-08:09 0.00 2215.27 02-JAN-07:10 0.00 0.00 01-JAN-00:10
February 13992.25 27-FEB-16:00 6958.21 01-FEB-06:10 10112.62 01-FEB-08:09 0.00 2157.22 01-FEB-08:09 0.00 0.00 01-FEB-00:10
March 13133.94 01-MAR-16:00 6958.21 01-MAR-06:10 10112.62 01-MAR-08:09 0.00 2157.22 07-MAR-07:10 0.00 0.00 01-MAR-00:10
April 11837.81 21-APR-14:00 6958.21 01-APR-05:10 10112.62 01-APR-07:10 0.00 2157.22 01-APR-06:10 0.00 0.00 01-APR-00:10
May 11140.00 09-MAY-08:09 6958.21 01-MAY-18:30 10112.62 01-MAY-07:10 0.00 2157.22 03-MAY-12:50 0.00 0.00 01-MAY-00:10
June 11039.46 09-JUN-07:10 6958.21 01-JUN-18:49 10112.62 01-JUN-07:10 0.00 2157.22 03-JUN-07:10 0.00 0.00 01-JUN-00:10
July 10999.51 19-JUL-07:10 6958.21 01-JUL-18:00 10112.62 01-JUL-07:10 0.00 3309.87 31-JUL-12:39 0.00 0.00 01-JUL-00:10
August 11466.80 31-AUG-07:10 6958.21 01-AUG-18:49 10112.62 01-AUG-07:10 0.00 3309.87 17-AUG-14:09 0.00 0.00 01-AUG-00:10
September 13060.33 21-SEP-08:09 6958.21 01-SEP-05:10 10112.62 01-SEP-07:10 0.00 2157.22 01-SEP-10:39 0.00 0.00 01-SEP-00:10
October 14251.23 30-OCT-08:09 6958.21 01-OCT-05:10 10112.62 02-OCT-07:10 0.00 2157.22 02-OCT-07:10 0.00 0.00 01-OCT-00:10
November 15488.05 25-NOV-15:00 6958.21 01-NOV-05:10 10112.62 01-NOV-07:10 0.00 2157.22 01-NOV-07:19 0.00 0.00 01-NOV-00:10
December 15490.80 15-DEC-15:00 6958.21 01-DEC-06:10 10112.62 01-DEC-08:09 0.00 2157.22 14-DEC-07:10 0.00 0.00 01-DEC-00:10
                         
Annual Sum or Average             0.00     0.00    
Minimum of Months 10999.51   6958.21   10112.62   0.00 2157.22   0.00 0.00  
Maximum of Months 15490.80   6958.21   10112.62   0.00 3309.87   0.00 0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 930.92 24-JAN-15:20 0.00 0.00 0.00 1799.35 31-JAN-12:39 0.00
February 828.17 01-FEB-11:00 0.00 0.00 0.00 1799.22 11-FEB-12:00 0.00
March 1045.24 23-MAR-13:00 0.00 0.00 0.00 1797.28 02-MAR-12:50 0.00
April 2899.35 26-APR-13:09 0.00 0.00 0.00 1791.61 01-APR-11:09 0.00
May 2524.34 04-MAY-12:09 0.00 0.00 0.00 1783.84 01-MAY-11:30 0.00
June 5820.77 29-JUN-18:10 0.00 0.00 0.00 1775.49 01-JUN-11:30 0.00
July 7114.13 31-JUL-13:30 0.00 0.00 0.00 1769.11 03-JUL-11:20 0.00
August 7218.22 17-AUG-14:09 0.00 0.00 0.00 1768.56 31-AUG-11:39 0.00
September 8085.46 29-SEP-11:00 0.00 0.00 0.00 1773.98 30-SEP-11:09 0.00
October 8657.64 16-OCT-11:09 0.00 0.00 0.00 1781.99 31-OCT-11:30 0.00
November 1019.10 18-NOV-13:00 0.00 0.00 0.00 1789.43 28-NOV-12:09 0.00
December 1005.38 05-DEC-14:00 0.00 0.00 0.00 1796.08 28-DEC-12:09 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 828.17   0.00 0.00 0.00 1768.56   0.00
Maximum of Months 8657.64   0.00 0.00 0.00 1799.35   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 34874.79 14-JAN-16:00 14003.70 10112.62 6958.21 0.00 2157.22 0.00 0.00 495.94 0.00
February 27864.77 25-FEB-16:00 13991.86 10112.62 0.00 0.00 2157.22 0.00 0.00 0.00 0.00
March 26761.18 09-MAR-16:00 13133.94 10112.62 0.00 0.00 2157.22 0.00 0.00 0.00 0.00
April 25858.22 21-APR-14:00 11837.81 10112.62 0.00 0.00 2157.22 0.00 0.00 0.00 0.00
May 24939.22 09-MAY-07:19 11043.10 10112.62 0.00 0.00 2157.22 0.00 0.00 0.00 0.00
June 27015.14 29-JUN-15:00 9335.50 10112.62 0.00 0.00 2157.22 0.00 0.00 3813.60 0.00
July 29898.35 31-JUL-13:39 8834.15 10112.62 0.00 0.00 2157.22 0.00 0.00 7091.11 0.00
August 31183.91 17-AUG-14:09 8808.60 10112.62 0.00 0.00 3309.87 0.00 0.00 7218.22 0.00
September 31513.65 29-SEP-15:50 11014.32 10112.62 0.00 0.00 2157.22 0.00 0.00 6632.20 0.00
October 32403.45 17-OCT-14:00 12931.81 10112.62 0.00 0.00 2157.22 0.00 0.00 5458.39 0.00
November 34832.95 30-NOV-16:49 14003.70 10112.62 6958.21 0.00 2157.22 0.00 0.00 0.00 0.00
December 35188.43 05-DEC-16:49 14003.70 10112.62 6958.21 0.00 2157.22 0.00 0.00 355.22 0.00
                       
Annual Sum or Average           0.00   0.00     0.00
Minimum of Months 24939.22   8808.60 10112.62 0.00 0.00 2157.22 0.00 0.00 0.00 0.00
Maximum of Months 35188.43   14003.70 10112.62 6958.21 0.00 3309.87 0.00 0.00 7218.22 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 17274.98 02-JAN-07:10 0.00 0.00 0.00
February 0.00 0.00 8491.03 10-FEB-07:10 0.00 0.00 0.00
March 0.00 0.00 13934.73 30-MAR-06:10 0.00 0.00 0.00
April 0.00 0.00 6464.60 01-APR-06:10 0.00 0.00 0.00
May 0.00 0.00 1304.39 15-MAY-07:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 4943.29 24-NOV-08:09 0.00 0.00 0.00
December 0.00 0.00 10903.73 15-DEC-07:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 17274.98   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 17.16 0.33 17.16 0.00 17.16 0.00 17.16
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 17.16 0.33 17.16 0.00 17.16 0.00 17.16
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 17.16 0.33 17.16 0.00 17.16 0.00 17.16



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 14.98 0.00 14.98 0.00 14.98 0.00 14.98
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 27.34 0.00 27.34
July 0.00 0.00 0.00 0.00 0.83 27.32 0.00 27.32
August 0.00 0.00 0.00 0.00 0.67 27.29 0.00 27.29
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.17 27.38 0.00 27.38
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 14.98 0.00 14.98 1.83 25.42 0.00 25.42
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 14.98 0.00 14.98 0.83 27.38 0.00 27.38



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 300.00 22.66 65.33 22.24 65.33 21.96
February 276.00 22.72 42.17 22.38 42.17 22.12
March 311.00 22.60 55.33 22.26 50.17 21.99
April 180.83 23.27 54.33 23.34 5.17 23.27
May 135.50 23.45 77.83 23.63 0.00 23.63
June 31.17 23.57 216.33 24.02 1.00 24.02
July 12.50 25.41 300.00 24.25 12.50 24.30
August 27.83 25.04 324.00 24.25 27.83 24.30
September 17.00 23.99 272.17 24.07 12.00 24.08
October 93.50 23.79 132.50 23.98 18.33 24.05
November 278.17 23.21 15.83 23.06 15.83 22.93
December 298.00 22.92 45.50 22.57 45.50 22.29
             
Annual Sum or Average 1961.50 23.02 1601.33 23.27 295.83 23.12
Minimum of Months 12.50 22.60 15.83 22.24 0.00 21.96
Maximum of Months 311.00 25.41 324.00 24.25 65.33 24.30



Table of Contents

Report: ComfortReportSimple55Monthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 298.17 20.77 137.83 20.20 137.83 19.90
February 276.00 20.86 109.00 20.37 109.00 20.09
March 305.17 20.61 135.33 20.29 119.67 19.99
April 152.33 22.33 126.67 23.59 9.00 23.44
May 118.33 22.85 169.33 24.45 3.83 24.44
June 115.67 25.81 266.67 25.96 86.50 26.09
July 233.33 26.66 300.00 26.57 233.33 26.60
August 265.00 26.60 324.00 26.51 265.00 26.54
September 143.00 26.31 285.83 26.13 136.67 26.21
October 114.83 24.86 223.00 25.71 64.00 25.83
November 266.17 22.26 45.00 21.99 39.17 21.74
December 295.67 21.37 94.50 20.88 94.50 20.57
             
Annual Sum or Average 2583.67 23.01 2217.17 23.70 1298.50 23.69
Minimum of Months 114.83 20.61 45.00 20.20 3.83 19.90
Maximum of Months 305.17 26.66 324.00 26.57 265.00 26.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 300.00 19.11 223.83 18.83 223.83 18.73
February 276.00 19.45 223.67 19.28 223.67 19.21
March 324.00 19.20 269.83 19.02 269.83 18.94
April 269.50 21.73 50.17 21.54 39.33 21.30
May 226.67 22.75 46.33 23.12 1.67 23.10
June 128.00 24.74 195.17 25.42 47.83 25.65
July 259.50 28.00 300.00 27.87 259.50 27.91
August 299.00 28.10 324.00 28.02 299.00 28.05
September 108.50 26.79 294.67 26.36 107.00 26.46
October 119.33 25.31 202.17 25.91 66.33 26.12
November 288.00 21.50 70.50 21.18 70.50 20.96
December 300.00 20.10 222.33 19.90 222.33 19.82
             
Annual Sum or Average 2898.50 22.54 2422.67 22.96 1830.83 22.91
Minimum of Months 108.50 19.11 46.33 18.83 1.67 18.73
Maximum of Months 324.00 28.10 324.00 28.02 299.00 28.05



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: OFFICE PEOPLE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 300.00000 0.00000 0.00000 0.00000 0.00000
February 276.00000 0.00000 0.00000 0.00000 0.00000
March 324.00000 0.00000 0.00000 0.00000 0.00000
April 300.00000 0.00000 0.00000 0.00000 0.00000
May 312.00000 0.00000 0.00000 0.00000 0.00000
June 312.00000 0.00000 0.00000 0.00000 0.00000
July 300.00000 0.00000 0.00000 0.00000 0.00000
August 324.00000 0.00000 0.00000 0.00000 0.00000
September 300.00000 0.00000 0.00000 0.00000 0.00000
October 300.00000 0.00000 0.00000 0.00000 0.00000
November 288.00000 0.00000 0.00000 0.00000 0.00000
December 300.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3636.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 276.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 324.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ZONE2 FINE STORAGEPEOPLE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 300.00000 0.00000 0.00000 0.00000 0.00000
February 276.00000 0.00000 0.00000 0.00000 0.00000
March 324.00000 0.00000 0.00000 0.00000 0.00000
April 300.00000 0.00000 0.00000 0.00000 0.00000
May 312.00000 0.00000 0.00000 0.00000 0.00000
June 312.00000 0.00000 0.00000 0.00000 0.00000
July 300.00000 0.00000 0.00000 0.00000 0.00000
August 324.00000 0.00000 0.00000 0.00000 0.00000
September 300.00000 0.00000 0.00000 0.00000 0.00000
October 300.00000 0.00000 0.00000 0.00000 0.00000
November 288.00000 0.00000 0.00000 0.00000 0.00000
December 300.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3636.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 276.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 324.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ZONE3 BULK STORAGEPEOPLE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 300.00000 0.00000 0.00000 0.00000 0.00000
February 276.00000 0.00000 0.00000 0.00000 0.00000
March 324.00000 0.00000 0.00000 0.00000 0.00000
April 300.00000 0.00000 0.00000 0.00000 0.00000
May 312.00000 0.00000 0.00000 0.00000 0.00000
June 312.00000 0.00000 0.00000 0.00000 0.00000
July 300.00000 0.00000 0.00000 0.00000 0.00000
August 324.00000 0.00000 0.00000 0.00000 0.00000
September 300.00000 0.00000 0.00000 0.00000 0.00000
October 300.00000 0.00000 0.00000 0.00000 0.00000
November 288.00000 0.00000 0.00000 0.00000 0.00000
December 300.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3636.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 276.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 324.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-OFFICE COOLING COIL

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.322798E+09 69286712.83 39.67 0.312300E+09 10497456.13 0.00 0.49 24-JAN-15:30 0.00 01-JAN-00:10 4443.07 24-JAN-15:30 4336.29 24-JAN-15:20 627.10 17-JAN-14:00 930.92 24-JAN-15:20 0.00 01-JAN-00:10
February 91626588.23 19664528.22 17.42 91456689.44 169898.80 0.00 0.44 01-FEB-12:00 0.00 01-FEB-00:10 3797.75 01-FEB-12:10 3797.75 01-FEB-12:10 136.50 01-FEB-13:40 828.17 01-FEB-12:00 0.00 01-FEB-00:10
March 0.213530E+09 45396537.28 29.42 0.186062E+09 27467810.08 0.00 0.53 23-MAR-14:00 0.00 01-MAR-00:10 5109.26 23-MAR-14:00 4015.74 11-MAR-14:00 1314.54 23-MAR-15:00 1045.24 23-MAR-14:00 0.00 01-MAR-00:10
April 0.919646E+09 0.192452E+09 102.38 0.768134E+09 0.151512E+09 0.00 1.00 15-APR-07:03 0.00 01-APR-00:10 16923.89 29-APR-07:02 13077.40 29-APR-07:02 4541.84 15-APR-07:03 3409.12 29-APR-07:02 0.00 01-APR-00:10
May 0.107017E+10 0.223975E+09 118.71 0.916117E+09 0.154055E+09 0.00 1.00 06-MAY-07:02 0.00 01-MAY-00:10 18138.40 06-MAY-07:02 12625.98 20-MAY-07:03 7362.39 06-MAY-07:02 3645.68 06-MAY-07:02 0.00 01-MAY-00:10
June 0.346300E+10 0.695547E+09 200.09 0.265169E+10 0.811311E+09 0.00 1.00 03-JUN-07:02 0.00 01-JUN-00:10 19298.72 30-JUN-07:02 13523.80 24-JUN-07:02 8108.11 30-JUN-07:02 3846.87 30-JUN-07:02 0.00 01-JUN-00:10
July 0.672164E+10 0.131667E+10 245.07 0.488440E+10 0.183724E+10 0.00 1.00 01-JUL-07:02 0.00 01-JUL-00:10 19862.98 25-JUL-07:02 13562.83 10-JUL-07:03 9729.87 20-JUL-07:03 3936.39 25-JUL-07:02 0.00 01-JUL-00:10
August 0.740216E+10 0.144353E+10 263.60 0.527374E+10 0.212842E+10 0.00 1.00 01-AUG-07:03 0.00 01-AUG-00:10 20372.97 19-AUG-07:02 12330.50 30-AUG-07:03 10320.58 18-AUG-07:03 4012.73 19-AUG-07:02 0.00 01-AUG-00:10
September 0.382630E+10 0.788917E+09 203.34 0.291287E+10 0.913425E+09 0.00 1.00 02-SEP-07:02 0.00 01-SEP-00:10 20144.12 22-SEP-07:03 17907.80 29-SEP-07:02 9963.84 22-SEP-07:03 3979.01 22-SEP-07:03 0.00 01-SEP-00:10
October 0.371751E+10 0.775798E+09 203.04 0.312859E+10 0.588910E+09 0.00 1.00 02-OCT-07:02 0.00 01-OCT-00:10 20353.94 05-OCT-07:02 17270.69 14-OCT-07:02 9810.37 05-OCT-07:04 4009.96 05-OCT-07:02 0.00 01-OCT-00:10
November 0.294344E+09 62890463.31 46.50 0.290783E+09 3560265.11 0.00 0.53 18-NOV-14:00 0.00 01-NOV-00:10 4777.58 18-NOV-14:10 4777.58 18-NOV-14:10 513.13 10-NOV-13:10 1019.10 18-NOV-14:00 0.00 01-NOV-00:10
December 0.387515E+09 83173876.85 59.92 0.385886E+09 1628743.41 0.00 0.55 05-DEC-15:00 0.00 01-DEC-00:10 4775.82 05-DEC-15:00 4775.82 05-DEC-15:00 340.47 07-DEC-14:00 1005.38 05-DEC-15:00 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.284302E+11 0.571730E+10 1529.16 0.218020E+11 0.662820E+10 0.00                            
Minimum of Months 91626588.23 19664528.22 17.42 91456689.44 169898.80 0.00 0.44   0.00   3797.75   3797.75   136.50   828.17   0.00  
Maximum of Months 0.740216E+10 0.144353E+10 263.60 0.527374E+10 0.212842E+10 0.00 1.00   0.00   20372.97   17907.80   10320.58   4012.73   0.00  



Table of Contents

Report: DXReportMonthly

For: PSZ-FINE STORAGE COOLING COIL

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 45387212.24 11882587.51 4.00 40237883.14 5149329.10 0.00 0.24 26-APR-13:10 0.00 01-APR-00:10 5380.52 26-APR-13:10 4807.38 26-APR-13:20 621.50 26-APR-13:10 1409.86 26-APR-13:10 0.00 01-APR-00:10
May 77141036.89 19665653.93 9.17 65003344.65 12137692.24 0.00 0.20 04-MAY-12:10 0.00 01-MAY-00:10 4416.63 04-MAY-12:10 3934.42 03-MAY-13:00 786.42 04-MAY-12:30 1113.67 04-MAY-12:10 0.00 01-MAY-00:10
June 0.134796E+10 0.327995E+09 70.00 0.933914E+09 0.414048E+09 0.00 1.00 18-JUN-14:45 0.00 01-JUN-00:10 53499.37 29-JUN-17:22 40098.75 25-JUN-12:52 20893.24 29-JUN-18:05 11668.48 29-JUN-17:22 0.00 01-JUN-00:10
July 0.664509E+10 0.157471E+10 194.00 0.451082E+10 0.213428E+10 0.00 1.00 01-JUL-17:23 0.00 01-JUL-00:10 55341.21 30-JUL-09:42 39031.45 09-JUL-15:15 24827.90 29-JUL-17:23 12164.27 23-JUL-11:05 0.00 01-JUL-00:10
August 0.675318E+10 0.161009E+10 202.77 0.445610E+10 0.229709E+10 0.00 1.00 03-AUG-17:25 0.00 01-AUG-00:10 55379.17 06-AUG-10:25 38762.71 19-AUG-17:27 22386.49 16-AUG-17:45 12156.19 06-AUG-13:05 0.00 01-AUG-00:10
September 0.141461E+10 0.376070E+09 59.65 0.124825E+10 0.166365E+09 0.00 1.00 04-SEP-14:45 0.00 01-SEP-00:10 53208.47 10-SEP-13:42 37061.15 04-SEP-14:45 19166.09 10-SEP-12:55 11619.87 10-SEP-13:42 0.00 01-SEP-00:10
October 0.183614E+10 0.492072E+09 67.51 0.167157E+10 0.164576E+09 0.00 1.00 01-OCT-11:23 0.00 01-OCT-00:10 55351.52 01-OCT-12:05 35456.63 01-OCT-12:05 22201.16 01-OCT-15:32 12233.39 01-OCT-12:05 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.181195E+11 0.441248E+10 607.11 0.129259E+11 0.519364E+10 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.675318E+10 0.161009E+10 202.77 0.451082E+10 0.229709E+10 0.00 1.00   0.00   55379.17   40098.75   24827.90   12233.39   0.00  



Table of Contents

Report: WindowReportMonthly

For: OFFICE FRONT WALL WINDOW 1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 64.41 32.49 31.93 86.83 81.79 0.00 0.00 0.00
February 76.77 35.42 41.35 97.98 73.79 0.00 0.00 0.00
March 87.97 38.91 49.07 114.15 76.32 0.00 0.00 0.00
April 121.11 62.93 58.18 169.52 70.71 0.00 0.00 0.00
May 119.00 54.83 64.17 159.26 68.04 0.00 0.00 0.00
June 126.35 63.19 63.16 176.45 57.35 0.00 0.00 0.00
July 133.76 71.59 62.17 194.46 56.36 0.00 0.00 0.00
August 125.30 67.83 57.47 185.49 58.51 0.00 0.00 0.00
September 107.28 57.35 49.94 154.62 63.92 0.00 0.00 0.00
October 82.11 44.85 37.26 121.74 69.08 0.00 0.00 0.00
November 74.04 38.67 35.37 98.82 81.37 0.00 0.00 0.00
December 65.28 34.91 30.37 88.15 86.01 0.00 0.00 0.00
                 
Annual Sum or Average 98.70 50.31 48.39 137.48 70.26 0.00 0.00 0.00
Minimum of Months 64.41 32.49 30.37 86.83 56.36 0.00 0.00 0.00
Maximum of Months 133.76 71.59 64.17 194.46 86.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: OFFICE FRONT WALL WINDOW2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 64.41 32.49 31.93 86.83 81.79 0.00 0.00 0.00
February 76.77 35.42 41.35 97.98 73.79 0.00 0.00 0.00
March 87.97 38.91 49.07 114.15 76.32 0.00 0.00 0.00
April 121.11 62.93 58.18 169.52 70.71 0.00 0.00 0.00
May 119.00 54.83 64.17 159.26 68.04 0.00 0.00 0.00
June 126.35 63.19 63.16 176.45 57.35 0.00 0.00 0.00
July 133.76 71.59 62.17 194.46 56.36 0.00 0.00 0.00
August 125.30 67.83 57.47 185.49 58.51 0.00 0.00 0.00
September 107.28 57.35 49.94 154.62 63.92 0.00 0.00 0.00
October 82.11 44.85 37.26 121.74 69.08 0.00 0.00 0.00
November 74.04 38.67 35.37 98.82 81.37 0.00 0.00 0.00
December 65.28 34.91 30.37 88.15 86.01 0.00 0.00 0.00
                 
Annual Sum or Average 98.70 50.31 48.39 137.48 70.26 0.00 0.00 0.00
Minimum of Months 64.41 32.49 30.37 86.83 56.36 0.00 0.00 0.00
Maximum of Months 133.76 71.59 64.17 194.46 86.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: OFFICE LEFT WALL WINDOW1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.63 0.00 14.63 10.96 49.08 0.00 0.00 0.00
February 18.36 0.00 18.36 12.82 44.50 0.00 0.00 0.00
March 22.50 0.00 22.50 18.23 45.88 0.00 0.00 0.00
April 25.99 0.15 25.84 21.91 41.71 0.00 0.00 0.00
May 31.35 1.63 29.72 27.22 38.34 0.00 0.00 0.00
June 33.15 3.20 29.95 33.10 32.29 0.00 0.00 0.00
July 31.39 2.59 28.80 32.65 32.04 0.00 0.00 0.00
August 26.20 0.61 25.59 26.43 33.84 0.00 0.00 0.00
September 22.10 0.01 22.09 20.88 38.67 0.00 0.00 0.00
October 17.52 0.00 17.52 18.64 41.38 0.00 0.00 0.00
November 15.87 0.00 15.87 11.05 49.21 0.00 0.00 0.00
December 13.62 0.00 13.62 9.25 51.85 0.00 0.00 0.00
                 
Annual Sum or Average 22.74 0.69 22.06 20.31 41.55 0.00 0.00 0.00
Minimum of Months 13.62 0.00 13.62 9.25 32.04 0.00 0.00 0.00
Maximum of Months 33.15 3.20 29.95 33.10 51.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: OFFICE LEFT WALL WINDOW2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.63 0.00 14.63 10.96 49.08 0.00 0.00 0.00
February 18.36 0.00 18.36 12.82 44.50 0.00 0.00 0.00
March 22.50 0.00 22.50 18.23 45.88 0.00 0.00 0.00
April 25.99 0.15 25.84 21.91 41.71 0.00 0.00 0.00
May 31.35 1.63 29.72 27.22 38.34 0.00 0.00 0.00
June 33.15 3.20 29.95 33.10 32.29 0.00 0.00 0.00
July 31.39 2.59 28.80 32.65 32.04 0.00 0.00 0.00
August 26.20 0.61 25.59 26.43 33.84 0.00 0.00 0.00
September 22.10 0.01 22.09 20.88 38.67 0.00 0.00 0.00
October 17.52 0.00 17.52 18.64 41.38 0.00 0.00 0.00
November 15.87 0.00 15.87 11.05 49.21 0.00 0.00 0.00
December 13.62 0.00 13.62 9.25 51.85 0.00 0.00 0.00
                 
Annual Sum or Average 22.74 0.69 22.06 20.31 41.55 0.00 0.00 0.00
Minimum of Months 13.62 0.00 13.62 9.25 32.04 0.00 0.00 0.00
Maximum of Months 33.15 3.20 29.95 33.10 51.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_6

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_7

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_8

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_9

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_10

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_5

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_14

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_13

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_12

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_11

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 96.92 44.95 12.33 0.00 0.00
February 89.79 50.54 39.25 107.33 39.04 1.83 0.00 0.00
March 116.06 65.62 50.44 142.80 38.78 15.83 0.00 0.00
April 173.39 125.15 48.24 216.43 37.70 0.00 0.00 0.00
May 173.00 110.14 62.86 212.49 35.80 0.00 0.00 0.00
June 183.45 125.20 58.25 227.96 30.57 0.00 0.00 0.00
July 201.04 149.63 51.41 252.55 31.85 0.00 0.00 0.00
August 186.36 142.05 44.31 234.86 33.48 0.00 0.00 0.00
September 143.71 101.67 42.03 178.86 36.12 0.00 0.00 0.00
October 103.19 71.18 32.00 128.33 40.46 0.00 0.00 0.00
November 84.13 53.98 30.15 101.32 45.45 2.50 0.00 0.00
December 73.69 50.23 23.46 88.83 48.54 4.50 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 166.03 38.57 37.00 0.00 0.00
Minimum of Months 73.69 50.23 23.46 88.83 30.57 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.55 48.54 15.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R8C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R8C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R8C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R1C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R1C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R1C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R1C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R2C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R2C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R2C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R2C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R3C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R3C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R3C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R3C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R4C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R4C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R4C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R4C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R5C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R5C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R5C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R5C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R6C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R6C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R8C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R6C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R7C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R7C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R7C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R6C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R7C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.97 52.12 26.85 100.23 41.59 10.33 0.00 0.00
February 89.79 50.54 39.25 110.71 36.25 2.83 0.00 0.00
March 116.06 65.62 50.44 147.22 35.13 38.83 0.00 0.00
April 173.39 125.15 48.24 221.98 33.89 5.83 0.00 0.00
May 173.00 110.14 62.86 216.78 33.69 0.00 0.00 0.00
June 183.45 125.20 58.25 231.71 28.87 0.00 0.00 0.00
July 201.04 149.63 51.41 252.07 34.10 0.00 0.00 0.00
August 186.36 142.05 44.31 233.57 36.66 0.00 0.00 0.00
September 143.71 101.67 42.03 179.92 37.11 0.33 0.00 0.00
October 103.19 71.18 32.00 129.24 41.44 0.00 0.00 0.00
November 84.13 53.98 30.15 103.46 44.33 0.33 0.00 0.00
December 73.69 50.23 23.46 91.48 46.22 4.83 0.00 0.00
                 
Annual Sum or Average 134.13 91.69 42.44 168.49 37.46 63.33 0.00 0.00
Minimum of Months 73.69 50.23 23.46 91.48 28.87 0.00 0.00 0.00
Maximum of Months 201.04 149.63 62.86 252.07 46.22 38.83 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: OFFICE FRONT WALL WINDOW 1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.172520E+09 87008483.01 85511893.36 0.232569E+09 0.219063E+09
February 0.185716E+09 85688879.95 0.100027E+09 0.237043E+09 0.178517E+09
March 0.235631E+09 0.104204E+09 0.131426E+09 0.305746E+09 0.204404E+09
April 0.313911E+09 0.163121E+09 0.150790E+09 0.439405E+09 0.183275E+09
May 0.318735E+09 0.146851E+09 0.171884E+09 0.426570E+09 0.182247E+09
June 0.327495E+09 0.163791E+09 0.163703E+09 0.457366E+09 0.148645E+09
July 0.358267E+09 0.191752E+09 0.166515E+09 0.520829E+09 0.150946E+09
August 0.335603E+09 0.181687E+09 0.153916E+09 0.496815E+09 0.156714E+09
September 0.278082E+09 0.148640E+09 0.129443E+09 0.400767E+09 0.165693E+09
October 0.219931E+09 0.120139E+09 99791852.06 0.326061E+09 0.185033E+09
November 0.191911E+09 0.100220E+09 91690786.11 0.256151E+09 0.210902E+09
December 0.174848E+09 93503618.68 81344281.86 0.236101E+09 0.230357E+09
           
Annual Sum or Average 0.311265E+10 0.158661E+10 0.152604E+10 0.433542E+10 0.221580E+10
Minimum of Months 0.172520E+09 85688879.95 81344281.86 0.232569E+09 0.148645E+09
Maximum of Months 0.358267E+09 0.191752E+09 0.171884E+09 0.520829E+09 0.230357E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: OFFICE FRONT WALL WINDOW2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.172520E+09 87008483.01 85511893.36 0.232569E+09 0.219063E+09
February 0.185716E+09 85688879.95 0.100027E+09 0.237043E+09 0.178517E+09
March 0.235631E+09 0.104204E+09 0.131426E+09 0.305746E+09 0.204404E+09
April 0.313911E+09 0.163121E+09 0.150790E+09 0.439405E+09 0.183275E+09
May 0.318735E+09 0.146851E+09 0.171884E+09 0.426570E+09 0.182247E+09
June 0.327495E+09 0.163791E+09 0.163703E+09 0.457366E+09 0.148645E+09
July 0.358267E+09 0.191752E+09 0.166515E+09 0.520829E+09 0.150946E+09
August 0.335603E+09 0.181687E+09 0.153916E+09 0.496815E+09 0.156714E+09
September 0.278082E+09 0.148640E+09 0.129443E+09 0.400767E+09 0.165693E+09
October 0.219931E+09 0.120139E+09 99791852.06 0.326061E+09 0.185033E+09
November 0.191911E+09 0.100220E+09 91690786.11 0.256151E+09 0.210902E+09
December 0.174848E+09 93503618.68 81344281.86 0.236101E+09 0.230357E+09
           
Annual Sum or Average 0.311265E+10 0.158661E+10 0.152604E+10 0.433542E+10 0.221580E+10
Minimum of Months 0.172520E+09 85688879.95 81344281.86 0.232569E+09 0.148645E+09
Maximum of Months 0.358267E+09 0.191752E+09 0.171884E+09 0.520829E+09 0.230357E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: OFFICE LEFT WALL WINDOW1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 39180440.36 0.00 39180440.36 29356975.24 0.131449E+09
February 44422348.44 0.00 44422348.44 31011030.79 0.107648E+09
March 60275496.02 1891.92 60273604.10 48839852.40 0.122878E+09
April 67377058.44 401407.28 66975651.16 56791372.89 0.108114E+09
May 83958900.97 4364064.65 79594836.32 72899373.28 0.102677E+09
June 85915259.84 8287439.62 77627820.23 85806867.98 83707628.59
July 84079046.43 6931707.61 77147338.82 87439914.19 85806076.66
August 70175901.41 1637363.10 68538538.31 70788249.86 90630870.69
September 57278866.92 20196.66 57258670.27 54121073.15 0.100229E+09
October 46938181.22 0.00 46938181.22 49938077.86 0.110839E+09
November 41128196.19 0.00 41128196.19 28647004.67 0.127540E+09
December 36473657.13 0.00 36473657.13 24788500.75 0.138867E+09
           
Annual Sum or Average 0.717203E+09 21644070.83 0.695559E+09 0.640428E+09 0.131039E+10
Minimum of Months 36473657.13 0.00 36473657.13 24788500.75 83707628.59
Maximum of Months 85915259.84 8287439.62 79594836.32 87439914.19 0.138867E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: OFFICE LEFT WALL WINDOW2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 39179352.82 0.00 39179352.82 29355964.83 0.131448E+09
February 44421026.75 0.00 44421026.75 31009565.22 0.107647E+09
March 60273709.52 1891.83 60271817.69 48837625.11 0.122877E+09
April 67375371.63 401388.47 66973983.16 56789601.69 0.108114E+09
May 83956469.13 4363860.10 79592609.03 72896089.20 0.102677E+09
June 85912769.02 8287051.17 77625717.85 85803339.76 83707390.08
July 84076837.05 6931382.71 77145454.34 87436968.39 85805668.54
August 70174221.71 1637286.35 68536935.35 70786430.99 90630450.92
September 57277403.05 20195.71 57257207.34 54119433.29 0.100229E+09
October 46936925.77 0.00 46936925.77 49936784.52 0.110838E+09
November 41127040.51 0.00 41127040.51 28645883.43 0.127540E+09
December 36472664.03 0.00 36472664.03 24787741.01 0.138866E+09
           
Annual Sum or Average 0.717184E+09 21643056.35 0.695541E+09 0.640405E+09 0.131038E+10
Minimum of Months 36472664.03 0.00 36472664.03 24787741.01 83707390.08
Maximum of Months 85912769.02 8287051.17 79592609.03 87436968.39 0.138866E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_6

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_7

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_8

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_9

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_10

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_5

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_14

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_13

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_12

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_11

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.259602E+09 0.120385E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.259641E+09 94448022.05
March 0.310856E+09 0.175765E+09 0.135091E+09 0.382482E+09 0.103861E+09
April 0.449426E+09 0.324386E+09 0.125040E+09 0.560978E+09 97708536.88
May 0.463373E+09 0.295012E+09 0.168362E+09 0.569133E+09 95886732.25
June 0.475502E+09 0.324514E+09 0.150988E+09 0.590860E+09 79234912.35
July 0.538472E+09 0.400770E+09 0.137702E+09 0.676421E+09 85312198.46
August 0.499156E+09 0.380478E+09 0.118679E+09 0.629044E+09 89663801.68
September 0.372487E+09 0.263538E+09 0.108950E+09 0.463597E+09 93627659.78
October 0.276374E+09 0.190655E+09 85718368.22 0.343721E+09 0.108379E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.262615E+09 0.117813E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.237921E+09 0.130006E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.523601E+10 0.121633E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.237921E+09 79234912.35
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.676421E+09 0.130006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R8C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R8C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R8C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R1C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R1C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R1C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R1C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R2C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R2C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R2C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R2C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R3C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R3C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R3C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R3C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R4C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R4C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R4C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R4C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R5C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R5C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R5C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R5C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R6C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R6C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R8C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R6C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R7C1

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R7C2

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R7C4

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R6C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R7C3

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211517E+09 0.139600E+09 71916697.35 0.268466E+09 0.111390E+09
February 0.217217E+09 0.122263E+09 94954173.61 0.267823E+09 87689072.53
March 0.310856E+09 0.175765E+09 0.135091E+09 0.394310E+09 94094702.24
April 0.449426E+09 0.324386E+09 0.125040E+09 0.575376E+09 87836086.31
May 0.463373E+09 0.295012E+09 0.168362E+09 0.580611E+09 90236990.95
June 0.475502E+09 0.324514E+09 0.150988E+09 0.600582E+09 74837750.74
July 0.538472E+09 0.400770E+09 0.137702E+09 0.675134E+09 91323633.91
August 0.499156E+09 0.380478E+09 0.118679E+09 0.625605E+09 98190892.12
September 0.372487E+09 0.263538E+09 0.108950E+09 0.466351E+09 96196119.81
October 0.276374E+09 0.190655E+09 85718368.22 0.346150E+09 0.110984E+09
November 0.218068E+09 0.139920E+09 78148097.78 0.268179E+09 0.114902E+09
December 0.197367E+09 0.134537E+09 62830658.66 0.245013E+09 0.123793E+09
           
Annual Sum or Average 0.422982E+10 0.289144E+10 0.133838E+10 0.531360E+10 0.118147E+10
Minimum of Months 0.197367E+09 0.122263E+09 62830658.66 0.245013E+09 74837750.74
Maximum of Months 0.538472E+09 0.400770E+09 0.168362E+09 0.675134E+09 0.123793E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 192.85 259.00 158.08 64.97 93.11 0.00 0.00
February 218.81 233.78 190.26 70.84 119.42 0.00 0.00
March 262.00 241.61 220.96 77.81 143.14 0.00 0.00
April 380.95 222.92 294.20 126.17 168.03 0.00 0.00
May 371.28 211.08 300.70 112.91 187.78 0.00 0.00
June 417.25 177.42 318.99 132.78 186.21 0.00 0.00
July 452.30 174.89 330.31 148.36 181.95 0.00 0.00
August 422.59 183.45 303.00 136.89 166.11 0.00 0.00
September 348.17 202.37 258.77 114.71 144.06 0.00 0.00
October 278.48 218.64 199.27 89.71 109.56 0.00 0.00
November 216.18 257.57 179.81 77.33 102.48 0.00 0.00
December 191.62 272.52 157.80 69.82 87.98 0.00 0.00
               
Annual Sum or Average 313.17 221.24 242.89 101.99 140.89 0.00 0.00
Minimum of Months 191.62 174.89 157.80 64.97 87.98 0.00 0.00
Maximum of Months 452.30 272.52 330.31 148.36 187.78 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1356.94 629.25 1105.60 729.69 375.91 0.00 0.00
February 1502.55 546.57 1257.04 707.54 549.50 0.00 0.00
March 1999.23 542.88 1624.85 918.72 706.12 0.00 0.00
April 3029.97 527.75 2427.46 1752.09 675.37 0.00 0.00
May 2974.86 501.20 2422.05 1542.03 880.03 0.00 0.00
June 3191.37 427.97 2568.30 1752.78 815.52 0.00 0.00
July 3535.65 445.93 2814.59 2094.83 719.77 0.00 0.00
August 3288.02 468.67 2609.09 1988.76 620.33 0.00 0.00
September 2504.00 505.70 2011.89 1423.43 588.46 0.00 0.00
October 1796.63 566.50 1444.60 996.55 448.05 0.00 0.00
November 1418.45 636.34 1177.84 755.74 422.10 0.00 0.00
December 1243.61 679.54 1031.64 703.22 328.42 0.00 0.00
               
Annual Sum or Average 2324.46 539.97 1877.77 1283.62 594.16 0.00 0.00
Minimum of Months 1243.61 427.97 1031.64 703.22 328.42 0.00 0.00
Maximum of Months 3535.65 679.54 2814.59 2094.83 880.03 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 13081.61 4503.06 2527.08 1667.86 859.22 0.00 0.00
February 14698.55 3767.27 2873.24 1617.23 1256.01 0.00 0.00
March 20303.40 3499.59 3713.93 2099.94 1613.99 0.00 0.00
April 27625.52 3266.58 5548.47 4004.77 1543.70 0.00 0.00
May 26341.10 3234.14 5536.12 3524.63 2011.49 0.00 0.00
June 26843.56 2775.27 5870.39 4006.35 1864.05 0.00 0.00
July 30847.33 3295.74 6433.35 4788.17 1645.18 0.00 0.00
August 26932.53 3554.88 5963.64 4545.73 1417.91 0.00 0.00
September 19773.38 3669.53 4598.61 3253.55 1345.06 0.00 0.00
October 15716.31 4125.33 3301.95 2277.84 1024.11 0.00 0.00
November 13593.00 4570.57 2692.20 1727.40 964.79 0.00 0.00
December 12161.05 4890.25 2358.03 1607.37 750.66 0.00 0.00
               
Annual Sum or Average 20694.54 3764.75 4292.05 2933.98 1358.07 0.00 0.00
Minimum of Months 12161.05 2775.27 2358.03 1607.37 750.66 0.00 0.00
Maximum of Months 30847.33 4890.25 6433.35 4788.17 2011.49 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.516524E+09 0.693696E+09 0.423401E+09 0.174017E+09 0.249384E+09 0.00 0.00
February 0.529342E+09 0.565565E+09 0.460275E+09 0.171378E+09 0.288898E+09 0.00 0.00
March 0.701740E+09 0.647133E+09 0.591811E+09 0.208412E+09 0.383398E+09 0.00 0.00
April 0.987426E+09 0.577813E+09 0.762575E+09 0.327045E+09 0.435530E+09 0.00 0.00
May 0.994435E+09 0.565346E+09 0.805385E+09 0.302430E+09 0.502955E+09 0.00 0.00
June 0.108152E+10 0.459885E+09 0.826817E+09 0.344157E+09 0.482660E+09 0.00 0.00
July 0.121145E+10 0.468418E+09 0.884690E+09 0.397366E+09 0.487323E+09 0.00 0.00
August 0.113186E+10 0.491346E+09 0.811556E+09 0.366648E+09 0.444908E+09 0.00 0.00
September 0.902466E+09 0.524537E+09 0.670721E+09 0.297320E+09 0.373401E+09 0.00 0.00
October 0.745870E+09 0.585615E+09 0.533737E+09 0.240278E+09 0.293459E+09 0.00 0.00
November 0.560327E+09 0.667616E+09 0.466077E+09 0.200440E+09 0.265637E+09 0.00 0.00
December 0.513239E+09 0.729908E+09 0.422642E+09 0.187007E+09 0.235635E+09 0.00 0.00
               
Annual Sum or Average 0.987620E+10 0.697688E+10 0.765969E+10 0.321650E+10 0.444319E+10 0.00 0.00
Minimum of Months 0.513239E+09 0.459885E+09 0.422642E+09 0.171378E+09 0.235635E+09 0.00 0.00
Maximum of Months 0.121145E+10 0.729908E+09 0.884690E+09 0.397366E+09 0.502955E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.363442E+10 0.168540E+10 0.296123E+10 0.195440E+10 0.100683E+10 0.00 0.00
February 0.363497E+10 0.132227E+10 0.304104E+10 0.171168E+10 0.132936E+10 0.00 0.00
March 0.535475E+10 0.145405E+10 0.435199E+10 0.246071E+10 0.189128E+10 0.00 0.00
April 0.785369E+10 0.136792E+10 0.629197E+10 0.454141E+10 0.175056E+10 0.00 0.00
May 0.796786E+10 0.134241E+10 0.648723E+10 0.413016E+10 0.235706E+10 0.00 0.00
June 0.827204E+10 0.110929E+10 0.665703E+10 0.454320E+10 0.211383E+10 0.00 0.00
July 0.946989E+10 0.119437E+10 0.753860E+10 0.561078E+10 0.192782E+10 0.00 0.00
August 0.880662E+10 0.125529E+10 0.698819E+10 0.532669E+10 0.166150E+10 0.00 0.00
September 0.649036E+10 0.131079E+10 0.521482E+10 0.368953E+10 0.152529E+10 0.00 0.00
October 0.481209E+10 0.151731E+10 0.386923E+10 0.266917E+10 0.120006E+10 0.00 0.00
November 0.367661E+10 0.164939E+10 0.305295E+10 0.195888E+10 0.109407E+10 0.00 0.00
December 0.333089E+10 0.182008E+10 0.276314E+10 0.188351E+10 0.879629E+09 0.00 0.00
               
Annual Sum or Average 0.733042E+11 0.170286E+11 0.592174E+11 0.404801E+11 0.187373E+11 0.00 0.00
Minimum of Months 0.333089E+10 0.110929E+10 0.276314E+10 0.171168E+10 0.879629E+09 0.00 0.00
Maximum of Months 0.946989E+10 0.182008E+10 0.753860E+10 0.561078E+10 0.235706E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.350378E+11 0.120610E+11 0.676853E+10 0.446720E+10 0.230133E+10 0.00 0.00
February 0.355587E+11 0.911377E+10 0.695095E+10 0.391241E+10 0.303853E+10 0.00 0.00
March 0.543806E+11 0.937331E+10 0.994740E+10 0.562448E+10 0.432292E+10 0.00 0.00
April 0.716054E+11 0.846697E+10 0.143816E+11 0.103804E+11 0.400128E+10 0.00 0.00
May 0.705520E+11 0.866232E+10 0.148279E+11 0.944037E+10 0.538758E+10 0.00 0.00
June 0.695785E+11 0.719351E+10 0.152161E+11 0.103845E+11 0.483161E+10 0.00 0.00
July 0.826215E+11 0.882731E+10 0.172311E+11 0.128246E+11 0.440645E+10 0.00 0.00
August 0.721361E+11 0.952139E+10 0.159730E+11 0.121753E+11 0.379772E+10 0.00 0.00
September 0.512526E+11 0.951143E+10 0.119196E+11 0.843320E+10 0.348638E+10 0.00 0.00
October 0.420946E+11 0.110493E+11 0.884395E+10 0.610097E+10 0.274299E+10 0.00 0.00
November 0.352331E+11 0.118469E+11 0.697817E+10 0.447743E+10 0.250074E+10 0.00 0.00
December 0.325721E+11 0.130980E+11 0.631575E+10 0.430517E+10 0.201058E+10 0.00 0.00
               
Annual Sum or Average 0.652623E+12 0.118725E+12 0.135354E+12 0.925260E+11 0.428281E+11 0.00 0.00
Minimum of Months 0.325721E+11 0.719351E+10 0.631575E+10 0.391241E+10 0.201058E+10 0.00 0.00
Maximum of Months 0.826215E+11 0.130980E+11 0.172311E+11 0.128246E+11 0.538758E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.22 9.61 5.99 2.23 0.81 45.19 208.20 0.00
February 13.28 10.20 7.03 3.12 2.96 66.07 175.60 0.04
March 12.64 10.61 8.97 2.93 3.55 84.90 179.28 0.03
April 15.30 12.62 10.61 2.62 4.76 81.20 282.81 0.02
May 15.56 12.65 10.56 2.92 6.17 105.80 234.18 0.01
June 17.67 14.80 13.02 2.53 9.03 98.05 261.27 0.00
July 19.43 16.76 15.28 2.35 9.62 86.54 312.15 0.00
August 19.66 17.23 15.95 2.55 9.62 74.58 307.55 0.00
September 18.47 15.50 13.65 2.19 8.99 70.75 240.05 0.00
October 18.77 13.72 9.60 2.71 7.74 53.88 216.36 0.00
November 14.32 10.43 6.22 2.47 2.41 50.75 207.87 0.01
December 13.59 8.82 3.19 2.50 0.05 39.49 221.83 0.00
                 
Annual Sum or Average 16.01 12.76 10.02 2.59 5.49 71.44 237.65 0.01
Minimum of Months 12.64 8.82 3.19 2.19 0.05 39.49 175.60 0.00
Maximum of Months 19.66 17.23 15.95 3.12 9.62 105.80 312.15 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 26.00 13-JAN-13:00 15.46 8.00 3.10 11.84 120.00 725.00
February 26.00 01-FEB-11:00 14.67 6.00 4.10 10.11 166.00 715.50
March 24.00 11-MAR-10:00 13.82 6.00 2.60 8.15 120.00 907.00
April 27.00 26-APR-12:00 17.13 11.00 4.10 12.22 159.00 884.00
May 24.00 03-MAY-11:00 15.05 9.00 4.10 12.98 187.00 842.50
June 25.00 29-JUN-10:00 19.59 17.00 4.60 11.65 177.50 829.00
July 28.00 19-JUL-10:00 20.49 17.00 3.60 14.65 173.00 813.00
August 28.00 14-AUG-10:00 21.19 18.00 3.60 14.84 148.00 840.00
September 36.00 29-SEP-10:00 17.91 5.00 3.60 19.35 159.50 790.00
October 37.00 16-OCT-10:00 17.87 4.00 5.70 20.05 122.00 871.50
November 27.00 19-NOV-12:00 14.96 6.00 4.10 11.07 128.50 796.00
December 26.00 05-DEC-09:00 13.09 1.00 3.60 8.94 75.50 857.00
                 
Annual Sum or Average                
Minimum of Months 24.00   13.09 1.00 2.60 8.15 75.50 715.50
Maximum of Months 37.00   21.19 18.00 5.70 20.05 187.00 907.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.00 08-JAN-06:00 -0.3 -2.0 3.10 -15.5 11.50 193.50
February 5.00 04-FEB-05:00 0.22 -8.0 4.10 -10.9 0.00 0.00
March 4.00 07-MAR-04:00 3.53 3.00 0.00 -11.4 0.00 0.00
April 7.00 01-APR-05:00 4.33 1.00 4.10 -9.0 23.50 211.00
May 8.00 14-MAY-03:00 7.45 7.00 1.50 -6.6 0.00 0.00
June 11.00 13-JUN-03:00 9.85 9.00 2.10 -3.4 0.00 0.00
July 13.00 06-JUL-00:00 13.00 13.00 0.00 -0.6 0.00 0.00
August 14.00 24-AUG-01:00 14.00 14.00 0.00 0.51 0.00 0.00
September 11.00 20-SEP-02:00 9.85 9.00 1.50 -3.4 0.00 0.00
October 9.00 12-OCT-04:00 6.56 4.00 3.10 -6.4 0.00 0.00
November 7.00 05-NOV-01:00 5.54 4.00 3.10 -8.3 0.00 0.00
December 5.00 03-DEC-00:00 5.00 5.00 2.10 -0.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 1.00   -0.3 -8.0 0.00 -15.5 0.00 0.00
Maximum of Months 14.00   14.00 14.00 4.10 0.51 23.50 211.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 17.04 17-JAN-11:00 24.00 13.00 3.10 12.79 223.50 9.00
February 16.80 11-FEB-13:00 18.00 16.20 1.10 15.02 241.00 12.50
March 17.41 22-MAR-12:00 22.00 15.00 3.10 8.35 145.50 876.00
April 18.33 26-APR-10:00 26.00 14.00 4.10 12.03 141.50 915.50
May 16.69 05-MAY-14:00 18.00 16.00 5.10 8.74 303.50 269.00
June 19.59 29-JUN-10:00 25.00 17.00 4.60 11.65 177.50 829.00
July 21.19 19-JUL-11:00 28.00 18.00 4.60 14.84 182.50 808.00
August 21.20 18-AUG-11:00 28.00 18.00 3.60 17.21 244.00 667.50
September 21.85 22-SEP-11:00 26.00 20.00 2.60 20.05 284.00 21.00
October 21.09 01-OCT-11:00 26.00 19.00 3.60 13.16 102.00 899.50
November 16.52 10-NOV-12:00 21.00 14.00 5.10 7.15 131.00 808.50
December 15.64 07-DEC-12:00 20.00 13.00 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 15.64   18.00 13.00 1.10 5.94 89.00 9.00
Maximum of Months 21.85   28.00 20.00 5.10 20.05 303.50 915.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 17-JAN-12:00 22.00 16.85 2.10 11.65 241.50 67.50
February 16.20 11-FEB-13:00 18.00 16.80 1.10 15.02 241.00 12.50
March 15.00 23-MAR-15:20 21.67 17.34 3.77 8.02 112.00 809.83
April 15.00 26-APR-21:19 16.00 15.39 2.23 6.15 0.00 0.00
May 16.00 05-MAY-14:00 18.00 16.69 5.10 8.74 303.50 269.00
June 17.00 28-JUN-08:00 19.00 17.66 1.50 16.12 285.00 428.50
July 18.00 18-JUL-10:00 26.00 20.47 4.60 12.79 169.00 819.00
August 18.10 14-AUG-09:00 26.90 20.93 3.40 13.73 139.00 817.00
September 20.00 22-SEP-09:00 22.00 20.55 1.50 16.30 296.00 18.00
October 19.00 01-OCT-07:10 19.17 19.06 0.25 16.82 53.33 0.00
November 15.00 10-NOV-17:19 16.67 15.62 2.77 3.34 0.00 0.00
December 13.00 07-DEC-12:00 20.00 15.64 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 13.00   16.00 15.39 0.25 3.34 0.00 0.00
Maximum of Months 20.00   26.90 20.93 5.10 16.82 303.50 868.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 17.43 27.46 0.00
February 18.00 13.00 16.00 17.38 30.87 0.00
March 18.00 13.00 16.00 17.83 38.09 0.00
April 18.00 13.00 16.00 18.69 55.75 0.00
May 18.00 13.00 16.00 19.73 55.13 0.00
June 18.00 13.00 16.00 20.65 58.21 0.00
July 18.00 13.00 16.00 21.22 63.49 0.00
August 18.00 13.00 16.00 21.28 59.02 0.00
September 18.00 13.00 16.00 20.81 46.26 0.00
October 18.00 13.00 16.00 19.94 34.64 0.00
November 18.00 13.00 16.00 18.91 29.25 0.00
December 18.00 13.00 16.00 17.99 26.27 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.33 43.77 0.00
Minimum of Months 18.00 13.00 16.00 17.38 26.27 0.00
Maximum of Months 18.00 13.00 16.00 21.28 63.49 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.822806E+09 -742377177.7 0.00 0.00 744.00 0.00 -80428498.2 59.00 0.00 0.00
February 0.755010E+09 -682807394.3 0.00 0.00 672.00 0.00 -72202763.2 58.99 0.00 0.00
March 0.869059E+09 -789289996.4 0.00 0.00 744.00 0.00 -79769072.2 59.00 0.00 0.00
April 0.791523E+09 -718026380.7 0.00 0.00 720.00 0.00 -73496334.6 58.99 0.00 0.00
May 0.802460E+09 -727625790.4 0.00 0.00 744.00 0.00 -74833867.6 58.99 0.00 0.00
June 0.778994E+09 -708294813.2 0.00 0.00 720.00 0.00 -70699219.4 58.99 0.00 0.00
July 0.745573E+09 -674426093.8 0.00 0.00 744.00 0.00 -71147008.5 58.99 0.00 0.00
August 0.794990E+09 -723274680.0 0.00 0.00 744.00 0.00 -71715101.2 58.99 0.00 0.00
September 0.750903E+09 -680579558.1 0.00 0.00 720.00 0.00 -70323027.2 58.99 0.00 0.00
October 0.770990E+09 -697610153.4 0.00 0.00 744.00 0.00 -73379423.4 58.99 0.00 0.00
November 0.762978E+09 -687596272.6 0.00 0.00 720.00 0.00 -75381994.1 58.99 0.00 0.00
December 0.811541E+09 -732058221.6 0.00 0.00 744.00 0.00 -79483198.7 58.99 0.00 0.00
                     
Annual Sum or Average 0.945683E+10 -0.856397E+10 0.00 0.00 8760.00 0.00 -892859508.2 58.99 0.00 0.00
Minimum of Months 0.745573E+09 -789289996.4 0.00 0.00 672.00 0.00 -80428498.2 58.99 0.00 0.00
Maximum of Months 0.869059E+09 -674426093.8 0.00 0.00 744.00 0.00 -70323027.2 59.00 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: ZONE2 FINE STORAGE_DAYLCTRL

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.79 0.50 01-JAN-11:00 206.13 0.00 0.00 46.83 174.99 0.00 0.00 27.67
February 279.67 0.72 0.50 01-FEB-11:30 271.92 0.00 0.00 94.50 1032.71 0.00 0.00 81.83
March 338.17 0.69 0.50 02-MAR-09:30 1322.48 0.00 0.00 177.67 349.77 0.00 0.00 113.33
April 358.33 0.68 0.50 01-APR-10:30 318.06 0.00 0.00 182.50 259.28 0.00 0.00 132.00
May 393.83 0.66 0.50 01-MAY-09:50 386.52 0.00 0.00 236.33 2897.47 0.00 0.00 164.83
June 381.00 0.67 0.50 01-JUN-09:00 2480.19 0.00 0.00 221.83 1053.01 0.00 0.00 142.17
July 408.67 0.68 0.50 01-JUL-09:30 336.93 0.00 0.00 216.33 3521.25 0.00 0.00 138.50
August 390.67 0.69 0.50 01-AUG-09:39 300.46 0.00 0.00 188.33 1095.15 0.00 0.00 129.50
September 328.83 0.69 0.50 01-SEP-10:39 300.54 0.00 0.00 145.50 246.63 0.00 0.00 100.00
October 296.17 0.76 0.50 01-OCT-10:09 2129.17 0.00 0.00 98.83 195.18 0.00 0.00 48.83
November 300.00 0.78 0.50 01-NOV-09:39 218.90 0.00 0.00 62.67 185.43 0.00 0.00 45.50
December 297.00 0.82 0.50 01-DEC-10:39 179.19 0.00 0.00 29.83 153.46 0.00 0.00 16.00
                         
Annual Sum or Average 4065.67 0.71     712.86 0.00 0.00 1701.17 1033.19 0.00 0.00 1140.17
Minimum of Months 279.67 0.66 0.50   179.19 0.00 0.00 29.83 153.46 0.00 0.00 16.00
Maximum of Months 408.67 0.82 0.50   2480.19 0.00 0.00 236.33 3521.25 0.00 0.00 164.83



Table of Contents

Report: DaylightingReportMonthly

For: ZONE3 BULK STORAGE_DAYLCTRL

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.65 0.50 01-JAN-08:00 242.67 13.61 0.00 181.00 199.57 17.48 40.00 127.67
February 279.67 0.61 0.50 01-FEB-08:50 313.39 14.66 0.00 203.00 1274.52 18.48 62.83 166.50
March 338.17 0.60 0.50 01-MAR-08:00 374.43 15.10 0.00 267.67 422.99 18.92 105.67 230.50
April 358.33 0.58 0.50 01-APR-07:49 2194.00 16.44 38.83 292.17 310.38 19.05 106.17 242.17
May 393.83 0.58 0.50 01-MAY-06:40 422.65 15.38 8.83 331.67 358.29 19.26 121.50 281.50
June 381.00 0.57 0.50 01-JUN-06:40 398.49 14.95 2.50 325.67 333.98 18.79 100.33 274.00
July 408.67 0.58 0.50 01-JUL-06:49 373.25 14.70 2.67 332.33 313.32 18.67 120.67 274.50
August 390.67 0.59 0.50 01-AUG-07:10 2364.87 16.07 36.67 306.83 291.19 18.63 109.67 249.17
September 328.83 0.59 0.50 01-SEP-06:00 347.31 14.45 1.00 266.67 286.62 18.37 75.67 214.00
October 296.17 0.64 0.50 01-OCT-09:39 3575.22 15.41 36.17 205.50 1348.78 19.18 67.83 167.67
November 300.00 0.65 0.50 01-NOV-07:00 255.50 13.35 0.00 186.50 209.69 17.13 41.83 134.17
December 297.00 0.68 0.50 01-DEC-08:20 211.22 12.81 0.00 158.00 172.91 16.64 13.00 96.50
                         
Annual Sum or Average 4065.67 0.61     929.43 14.82 126.67 3057.00 439.63 18.44 965.17 2458.33
Minimum of Months 279.67 0.57 0.50   211.22 12.81 0.00 158.00 172.91 16.64 13.00 96.50
Maximum of Months 408.67 0.68 0.50   3575.22 16.44 38.83 332.33 1348.78 19.26 121.50 281.50



Table of Contents

Report: DaylightingReportMonthly

For: ZONE1 OFFICE_DAYLCTRL

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.91 0.82 30-JAN-15:50 302.56 22.49 111.67 36.67 101.04 19.88 86.17 0.00
February 279.67 0.90 0.80 07-FEB-15:30 318.38 22.82 126.17 45.83 155.82 22.17 125.00 12.83
March 338.17 0.90 0.80 01-MAR-15:20 269.57 21.99 144.00 54.67 219.48 23.05 156.50 36.00
April 358.33 0.89 0.80 01-APR-14:39 237.92 20.51 131.17 64.67 339.06 22.14 155.17 63.50
May 393.83 0.89 0.80 01-MAY-15:09 240.48 20.29 132.67 59.33 298.93 21.65 183.17 68.00
June 381.00 0.88 0.80 01-JUN-14:00 242.86 20.22 130.67 60.00 232.52 21.81 168.83 71.83
July 408.67 0.88 0.80 01-JUL-15:30 240.79 20.24 144.33 60.00 238.42 21.83 191.50 78.83
August 390.67 0.89 0.80 01-AUG-15:09 230.02 20.23 141.50 60.17 342.94 21.70 175.00 72.50
September 328.83 0.89 0.80 01-SEP-15:09 254.87 21.83 142.67 59.00 258.92 23.75 162.00 49.67
October 296.17 0.91 0.80 01-OCT-15:20 354.69 22.66 110.67 40.33 258.04 22.49 103.00 25.83
November 300.00 0.91 0.80 03-NOV-15:30 271.52 22.60 132.33 37.67 108.95 19.82 106.00 0.00
December 297.00 0.92 0.82 02-DEC-15:30 247.30 22.25 114.17 30.67 95.10 19.44 82.50 0.00
                         
Annual Sum or Average 4065.67 0.90     264.03 21.37 1562.00 609.00 228.54 21.69 1694.83 479.00
Minimum of Months 279.67 0.88 0.80   230.02 20.22 110.67 30.67 95.10 19.44 82.50 0.00
Maximum of Months 408.67 0.92 0.82   354.69 22.82 144.33 64.67 342.94 23.75 191.50 78.83



Table of Contents

Report: CoilReportMonthly

For: PSZ-OFFICE HEATING COIL

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.354812E+09 25858.40 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.153470E+09 24535.79 28-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.280575E+09 25858.40 01-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 14272526.15 25858.40 01-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 513316.30 2566.58 15-MAY-07:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 25845833.29 10450.02 24-NOV-08:63 0.00 0.00 0.00 0.00 0.00
December 0.169254E+09 25858.40 13-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.998744E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.354812E+09 25858.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-FINE STORAGE HEATING COIL

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 44219417.13 22850.74 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 44219417.13     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 44219417.13 22850.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-OFFICE COOLING COIL

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.322798E+09 0.312300E+09 4443.07 24-JAN-15:30 4329.45 0.00
February 0.00 0.00 91626588.23 91456689.44 3797.75 01-FEB-12:10 3797.75 0.00
March 0.00 0.00 0.213530E+09 0.186062E+09 5109.26 23-MAR-14:00 3991.59 0.00
April 0.00 0.00 0.919646E+09 0.768134E+09 16923.89 29-APR-07:02 13077.40 0.00
May 0.00 0.00 0.107017E+10 0.916117E+09 18138.40 06-MAY-07:02 10776.01 0.00
June 0.00 0.00 0.346300E+10 0.265169E+10 19298.72 30-JUN-07:02 11190.61 0.00
July 0.00 0.00 0.672164E+10 0.488440E+10 19862.98 25-JUL-07:02 10943.08 0.00
August 0.00 0.00 0.740216E+10 0.527374E+10 20372.97 19-AUG-07:02 10811.44 0.00
September 0.00 0.00 0.382630E+10 0.291287E+10 20144.12 22-SEP-07:03 10180.27 0.00
October 0.00 0.00 0.371751E+10 0.312859E+10 20353.94 05-OCT-07:02 10566.54 0.00
November 0.00 0.00 0.294344E+09 0.290783E+09 4777.58 18-NOV-14:10 4777.58 0.00
December 0.00 0.00 0.387515E+09 0.385886E+09 4775.82 05-DEC-15:00 4775.82 0.00
                 
Annual Sum or Average 0.00 0.00 0.284302E+11 0.218020E+11       0.00
Minimum of Months 0.00 0.00 91626588.23 91456689.44 3797.75   3797.75 0.00
Maximum of Months 0.00 0.00 0.740216E+10 0.527374E+10 20372.97   13077.40 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-FINE STORAGE COOLING COIL

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 45387212.24 40237883.14 5380.52 26-APR-13:10 4759.02 0.00
May 0.00 0.00 77141036.89 65003344.65 4416.63 04-MAY-12:10 3648.80 0.00
June 0.00 0.00 0.134796E+10 0.933914E+09 53499.37 29-JUN-17:22 33991.29 0.00
July 0.00 0.00 0.664509E+10 0.451082E+10 55341.21 30-JUL-09:42 33519.51 0.00
August 0.00 0.00 0.675318E+10 0.445610E+10 55379.17 06-AUG-10:25 33911.02 0.00
September 0.00 0.00 0.141461E+10 0.124825E+10 53208.47 10-SEP-13:42 35106.72 0.00
October 0.00 0.00 0.183614E+10 0.167157E+10 55351.52 01-OCT-12:05 35456.63 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.181195E+11 0.129259E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.675318E+10 0.451082E+10 55379.17   35456.63 0.00



Table of Contents

Report: FanReportMonthly

For: ZONE3UNITHEATER ZONE3HIRADIANT FAN

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: PSZ-OFFICE_ADDAQ SUPPLY FAN

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.115611E+10 0.34 1167.05 02-JAN-10:00 0.92
February 0.106295E+10 0.35 1167.05 01-FEB-10:10 0.92
March 0.124789E+10 0.37 1167.05 01-MAR-07:50 0.92
April 0.115538E+10 0.35 1167.05 01-APR-12:40 0.92
May 0.120160E+10 0.35 1167.05 01-MAY-07:10 0.92
June 0.120160E+10 0.36 1167.05 01-JUN-11:10 0.92
July 0.115538E+10 0.34 1167.05 01-JUL-07:08 0.91
August 0.124781E+10 0.36 1167.05 01-AUG-09:30 0.92
September 0.115538E+10 0.35 1167.05 01-SEP-11:40 0.92
October 0.115538E+10 0.34 1167.05 02-OCT-07:20 0.91
November 0.110917E+10 0.34 1167.05 07-NOV-14:20 0.92
December 0.115538E+10 0.34 1167.05 01-DEC-07:50 0.92
           
Annual Sum or Average 0.140040E+11 0.35      
Minimum of Months 0.106295E+10 0.34 1167.05   0.91
Maximum of Months 0.124789E+10 0.37 1167.05   0.92



Table of Contents

Report: FanReportMonthly

For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.981740E+09 0.20 1454.60 02-JAN-07:01 0.68
February 0.901845E+09 0.20 990.17 01-FEB-07:10 0.54
March 0.105869E+10 0.21 990.17 01-MAR-07:02 0.54
April 0.980266E+09 0.21 990.17 26-APR-12:40 0.54
May 0.101948E+10 0.21 990.17 03-MAY-14:50 0.54
June 0.102579E+10 0.21 1497.73 29-JUN-17:20 0.69
July 0.103052E+10 0.21 2475.42 30-JUL-13:33 0.88
August 0.109035E+10 0.22 1649.71 19-AUG-17:12 0.73
September 0.982213E+09 0.21 990.17 21-SEP-13:50 0.53
October 0.990253E+09 0.20 1608.13 01-OCT-14:10 0.72
November 0.941055E+09 0.20 990.17 01-NOV-06:05 0.54
December 0.980266E+09 0.20 990.17 01-DEC-07:05 0.54
           
Annual Sum or Average 0.119825E+11 0.21      
Minimum of Months 0.901845E+09 0.20 990.17   0.53
Maximum of Months 0.109035E+10 0.22 2475.42   0.88



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.122540E+10 0.00 0.00
February 0.00 0.00 0.00 0.108262E+10 0.00 0.00
March 0.00 0.00 0.00 0.129328E+10 0.00 0.00
April 0.00 0.00 0.00 0.134783E+10 0.00 0.00
May 0.00 0.00 0.00 0.142557E+10 0.00 0.00
June 0.00 0.00 0.00 0.189714E+10 0.00 0.00
July 0.00 0.00 0.00 0.247205E+10 0.00 0.00
August 0.00 0.00 0.00 0.269134E+10 0.00 0.00
September 0.00 0.00 0.00 0.194430E+10 0.00 0.00
October 0.00 0.00 0.00 0.193118E+10 0.00 0.00
November 0.00 0.00 0.00 0.117206E+10 0.00 0.00
December 0.00 0.00 0.00 0.123856E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.197213E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.108262E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.269134E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.981740E+09 0.00 0.00
February 0.00 0.00 0.00 0.901845E+09 0.00 0.00
March 0.00 0.00 0.00 0.105869E+10 0.00 0.00
April 0.00 0.00 0.00 0.992148E+09 0.00 0.00
May 0.00 0.00 0.00 0.103914E+10 0.00 0.00
June 0.00 0.00 0.00 0.135378E+10 0.00 0.00
July 0.00 0.00 0.00 0.260523E+10 0.00 0.00
August 0.00 0.00 0.00 0.270044E+10 0.00 0.00
September 0.00 0.00 0.00 0.135828E+10 0.00 0.00
October 0.00 0.00 0.00 0.148232E+10 0.00 0.00
November 0.00 0.00 0.00 0.941055E+09 0.00 0.00
December 0.00 0.00 0.00 0.980266E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.163949E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.901845E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.270044E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.115611E+10 0.322798E+09 0.354812E+09 0.00 0.00 0.00 0.00 0.00
February 0.106295E+10 91626588.23 0.153470E+09 0.00 0.00 0.00 0.00 0.00
March 0.124789E+10 0.213530E+09 0.280575E+09 0.00 0.00 0.00 0.00 0.00
April 0.115538E+10 0.919646E+09 14272526.15 0.00 0.00 0.00 0.00 0.00
May 0.120160E+10 0.107017E+10 513316.30 0.00 0.00 0.00 0.00 0.00
June 0.120160E+10 0.346300E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.115538E+10 0.672164E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.124781E+10 0.740216E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115538E+10 0.382630E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.115538E+10 0.371751E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.110917E+10 0.294344E+09 25845833.29 0.00 0.00 0.00 0.00 0.00
December 0.115538E+10 0.387515E+09 0.169254E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.140040E+11 0.284302E+11 0.998744E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.106295E+10 91626588.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.124789E+10 0.740216E+10 0.354812E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.981740E+09 0.00 44219417.13 0.00 0.00 0.00 0.00 0.00
February 0.901845E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.105869E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.980266E+09 45387212.24 0.00 0.00 0.00 0.00 0.00 0.00
May 0.101948E+10 77141036.89 0.00 0.00 0.00 0.00 0.00 0.00
June 0.102579E+10 0.129738E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.103052E+10 0.626488E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.109035E+10 0.649068E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.982213E+09 0.139341E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.990253E+09 0.179394E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.941055E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.980266E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.119825E+11 0.173628E+11 44219417.13 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.901845E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.109035E+10 0.649068E+10 44219417.13 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.115611E+10 0.00 0.00 0.00 69286712.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.106295E+10 0.00 0.00 0.00 19664528.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.124789E+10 0.00 0.00 0.00 45396537.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115538E+10 0.00 0.00 0.00 0.192452E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.120160E+10 0.00 0.00 0.00 0.223975E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.120160E+10 0.00 0.00 0.00 0.695547E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.115538E+10 0.00 0.00 0.00 0.131667E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.124781E+10 0.00 0.00 0.00 0.144353E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115538E+10 0.00 0.00 0.00 0.788917E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.115538E+10 0.00 0.00 0.00 0.775798E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.110917E+10 0.00 0.00 0.00 62890463.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.115538E+10 0.00 0.00 0.00 83173876.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.140040E+11 0.00 0.00 0.00 0.571730E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.106295E+10 0.00 0.00 0.00 19664528.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.124789E+10 0.00 0.00 0.00 0.144353E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.981740E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.901845E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.105869E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.980266E+09 0.00 0.00 0.00 11882587.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.101948E+10 0.00 0.00 0.00 19665653.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.102579E+10 0.00 0.00 0.00 0.327995E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.103052E+10 0.00 0.00 0.00 0.157471E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.109035E+10 0.00 0.00 0.00 0.161009E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.982213E+09 0.00 0.00 0.00 0.376070E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.990253E+09 0.00 0.00 0.00 0.492072E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.941055E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.980266E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.119825E+11 0.00 0.00 0.00 0.441248E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.901845E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.109035E+10 0.00 0.00 0.00 0.161009E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.464128E+09 3892028.85 0.00 999658.01 2155.32 76638751.38 0.102385E+10 0.00 0.28
February 0.532498E+09 3350651.01 0.00 808357.91 0.00 28892755.43 0.992473E+09 0.00 0.27
March 0.617373E+09 0.00 0.00 1061092.68 0.00 58997603.49 0.115936E+10 0.00 0.29
April 0.133025E+09 4054613.02 0.00 3555844.95 0.00 1697425.35 0.266183E+10 0.00 0.63
May 65722135.57 5384933.10 0.00 4624732.34 0.00 167863.82 0.325506E+10 0.00 0.71
June 16297579.54 0.114926E+09 0.00 5604160.42 0.00 0.00 0.237839E+10 0.00 0.87
July 5130786.34 0.504096E+09 0.00 4759632.86 0.00 0.00 0.986425E+09 0.00 0.71
August 6302273.02 0.654511E+09 0.00 3812042.61 0.00 0.00 0.877046E+09 0.00 0.75
September 4501733.40 0.126450E+09 0.00 5421991.36 0.00 0.00 0.214861E+10 0.00 0.80
October 35184396.70 0.251657E+09 0.00 4085390.58 12820.06 0.00 0.180935E+10 0.00 0.64
November 0.227844E+09 1467918.21 0.00 2117879.84 0.00 2413284.42 0.208353E+10 0.00 0.43
December 0.423369E+09 1898453.99 0.00 1344767.46 0.00 25661480.72 0.126517E+10 0.00 0.36
                   
Annual Sum or Average 0.253138E+10 0.167169E+10 0.00 38195551.01 14975.37 0.194469E+09 0.206411E+11 0.00 0.56
Minimum of Months 4501733.40 0.00 0.00 808357.91 0.00 0.00 0.877046E+09 0.00 0.27
Maximum of Months 0.617373E+09 0.654511E+09 0.00 5604160.42 12820.06 76638751.38 0.325506E+10 0.00 0.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.265942E+10 0.00 0.00 0.00 23666313.92 0.00 0.00 0.00 0.18
February 0.279733E+10 0.00 0.00 0.00 3536368.38 0.00 0.00 0.00 0.18
March 0.355877E+10 0.00 0.00 0.00 165482.39 0.00 0.00 0.00 0.19
April 0.338988E+10 0.00 0.00 241275.66 1317628.10 0.00 0.309909E+09 0.00 0.19
May 0.361755E+10 0.00 0.00 624257.57 319067.52 0.00 0.584610E+09 0.00 0.20
June 0.212938E+10 0.00 0.00 4266466.87 0.00 0.00 0.255222E+10 0.00 0.30
July 0.410712E+09 0.188824E+09 0.00 10189608.34 0.00 0.00 0.395179E+10 0.00 0.41
August 0.565345E+09 0.177353E+09 0.00 9538799.27 0.00 0.00 0.361199E+10 0.00 0.43
September 0.174591E+10 94366741.49 0.00 3477312.17 0.00 0.00 0.284130E+10 0.00 0.27
October 0.203896E+10 0.199076E+09 0.00 1559782.28 9595564.32 0.00 0.111078E+10 0.00 0.23
November 0.311948E+10 0.00 0.00 0.00 581207.20 0.00 0.00 0.00 0.18
December 0.262200E+10 0.00 0.00 0.00 9176877.36 0.00 0.00 0.00 0.18
                   
Annual Sum or Average 0.286547E+11 0.659619E+09 0.00 29897502.15 48358509.19 0.00 0.149626E+11 0.00 0.24
Minimum of Months 0.410712E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.361755E+10 0.199076E+09 0.00 10189608.34 23666313.92 0.00 0.395179E+10 0.00 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 10:43:54

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.370856E+12 0.205370E+11 0.00 0.419747E+10 0.576858E+09
February 0.429871E+12 0.268429E+11 0.00 0.434512E+10 0.184573E+09
March 0.609356E+12 0.317173E+11 0.00 0.539540E+10 0.390477E+09
April 0.816644E+12 0.251704E+11 0.00 0.649477E+10 0.117561E+10
May 0.855229E+12 0.341976E+11 0.00 0.752266E+10 0.139122E+10
June 0.855652E+12 0.266520E+11 0.00 0.697866E+10 0.583451E+10
July 0.931423E+12 0.276703E+11 0.00 0.469817E+10 0.162581E+11
August 0.864872E+12 0.319978E+11 0.00 0.425066E+10 0.172090E+11
September 0.679846E+12 0.257909E+11 0.00 0.652848E+10 0.640590E+10
October 0.474107E+12 0.277394E+11 0.00 0.453958E+10 0.682152E+10
November 0.401174E+12 0.272738E+11 0.00 0.543335E+10 0.369792E+09
December 0.333164E+12 0.233588E+11 0.00 0.432647E+10 0.550985E+09
           
Annual Sum or Average 0.762219E+13 0.328948E+12 0.00 0.647108E+11 0.571685E+11
Minimum of Months 0.333164E+12 0.205370E+11 0.00 0.419747E+10 0.184573E+09
Maximum of Months 0.931423E+12 0.341976E+11 0.00 0.752266E+10 0.172090E+11