Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 10:43:52
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 530.93 | 109.81 | 109.81 |
Net Site Energy | 530.93 | 109.81 | 109.81 |
Total Source Energy | 1681.38 | 347.74 | 347.74 |
Net Source Energy | 1681.38 | 347.74 | 347.74 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 93.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 146.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 35.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 530.89 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 93.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 146.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 13.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 22.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 93.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 146.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 35.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 49.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 31.52 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 109.80 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 49.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 31.52 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 109.80 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 530.892 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 530.892 | 100.00 |
Total On-Site and Utility Electric Sources | 530.892 | 100.00 |
Total Electricity End Uses | 530.892 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 9.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3039.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.9961 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 5.6188 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 6.8172 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 6.8172 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 8.9961 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 9.2031 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 5.6188 | 46.45 | 2.5587 | |
Total | 4835.13 | 6.8172 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 6.8172 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 6.8172 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-JUN-15:50 | 25-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 24-MAY-11:09 |
Heating | 0.00 | 4800.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13588.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9861.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1578.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 39507.43 | 4800.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 4800.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 13588.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9861.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2061.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1578.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 296.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 464.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 292.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 113.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 72.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1681.33 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 61.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 96.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 347.73 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 61.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 96.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 347.73 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.13 |
ZONE2 FINE STORAGE DIRECT AIR | 2.64 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 39930.58 |
PSZ-OFFICE HEATING COIL | 27371.50 |
PSZ-FINE STORAGE HEATING COIL | 81514.15 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.00 | 1.00 | 1.13 |
PSZ-FINE STORAGE | 2.64 | 2.64 | 2.64 | 2.64 | 2.64 | 2.64 | 1.00 | 1.00 | 2.64 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.13 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.64 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.13 | 1247.39 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.64 | 2825.35 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.13 | 1.13 | 1.13 | 0.743597 | 23238.14 | 27371.50 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.64 | 2.64 | 2.64 | 1.74 | 65567.36 | 81514.15 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.13 | 0.563331 | 0.751107 | 23238.14 | 11619.07 | 0.764070 | 0.764070 |
PSZ-FINE STORAGE COOLING COIL | 2.64 | 1.32 | 1.76 | 65567.36 | 32783.68 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 8.996 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 9.203 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.203 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 5.619 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.177 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2131.000 | 8.996 | 167.154 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2131.000 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 12823.730 | 9.203 | 427.458 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12823.730 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 18007.220 | 5.619 | 260.974 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 18007.220 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2587 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2587 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.865 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.865 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.31452820E-09 | 0.26304591E-14 | 0.87829942E-15 | 0.0000000 |
2 | 1 | -5.2160429 | 0.46652437E-04 | -0.61920073E-04 | 0.60300157E-10 |
3 | 0 | 5.4747659 | 0.25867629 | 0.25878486 | |
4 | 2 | 0.31452820E-09 | 0.26304591E-14 | 0.87829942E-15 | 0.0000000 |
5 | 1 | -5.2160429 | 0.46652437E-04 | -0.61920073E-04 | 0.60300157E-10 |
6 | 0 | 5.4747659 | 0.25867629 | 0.25878486 | |
7 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
8 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
9 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
10 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
11 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
12 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
13 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
14 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
15 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
16 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.23941589E-14 | 0.16972320E-15 | 0.76147947E-12 | 0.12030052E-15 |
85 | 3 | -0.54770175E-04 | 0.40617527E-06 | -0.37802266E-03 | 0.14612398E-12 |
86 | 2 | 1.1283884 | 0.89444888E-02 | 1.7236739 | -0.72472748E-04 |
87 | 1 | -17.021073 | 0.23277257 | -7.1497137 | 0.33034766 |
88 | 0 | 16.283305 | 0.14884880 | 5.8169840 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.504_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.504_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.504_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.504_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.251 | ||
5 | SKYLIGHT_U_0.9_SHGC_0.6 | 38 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.16139 | 0.61064 | 0.61064 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.16139 | 0.61064 | 0.61064 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.16139 | 0.61064 | 0.61064 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.16139 | 0.61064 | 0.61064 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.867 | 0.602 | 0.602 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.602 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3881E-004 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8972E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2529E-004 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1397E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1884E-004 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0601E-003 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5848E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1816E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4514E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.0867E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0931E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.2852E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1964E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.0548E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7680E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3855E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.4823E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9801E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.6356E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0548E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2064E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8210E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2141E-003 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2648E-004 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0775E-003 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2576E-004 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8172E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2884E-004 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4654E-003 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1717E-004 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0450E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8226E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0031E-003 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9582E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0169E-003 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0127E-004 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2482E-003 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.6219E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2695E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9692E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.8771E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9014E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.1125E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0224E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.9945E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8460E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9222E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6649E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2648E-003 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0932E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4700E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2483E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4087E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9310E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8087E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6800E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.9976E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0498E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9415E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0767E-004 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.9525E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8755E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7041E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0163E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2564E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4409E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2634E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5073E-004 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.2060E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2638E-004 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3936E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0000E-004 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3081E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7838E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9200E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0257E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1055E-003 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2548E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4816E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3510E-004 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0390E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0755E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5666E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0413E-003 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8418E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8857E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2488E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9545E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5007E-004 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7847E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3417E-004 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7747E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2889E-004 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2942E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7796E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2088E-003 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0558E-004 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.9241E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9873E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.1355E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5826E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7775E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1032E-004 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8081E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0289E-004 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1452E-003 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7762E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0706E-003 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3748E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5656E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0681E-004 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8985E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3598E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5134E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7932E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4323E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4081E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8476E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6895E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7927E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1865E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1757E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1731E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4495E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5510E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1862E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2525E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8810E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2944E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5403E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7850E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4378E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6403E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4574E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6871E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6561E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9648E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7617E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0982E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9030E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7049E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4365E-004 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3769E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9618E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3479E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5617E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3081E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8271E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1654E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0159E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7372E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9357E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2156E-004 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2720E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2744E-004 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2688E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0570E-004 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1562E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7347E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6616E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4684E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2425E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7333E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3969E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8987E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5913E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3747E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6604E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3880E-004 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4276E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3541E-004 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7143E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4825E-004 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4849E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0580E-004 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5939E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8718E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6296E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3018E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9667E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5770E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1784E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2604E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5435E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4065E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0682E-004 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5214E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0723E-004 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6285E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0390E-004 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2591E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2647E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9375E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6749E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0197E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6091E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8259E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6186E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0571E-004 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9813E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1341E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2855E-004 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4828E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2510E-004 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8125E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3664E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8581E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9167E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2010E-003 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4771E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2976E-003 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9134E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3280E-003 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8632E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8668E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7823E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7517E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9490E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7721E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7988E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0215E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9958E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9061E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3526E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9731E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4378E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8537E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0983E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3530E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6159E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9089E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0419E-003 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9037E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9613E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7400E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7398E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6354E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0676E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9941E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6221E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2657E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3167E-004 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3823E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2305E-004 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7686E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4906E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4248E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2491E-004 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6385E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0605E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6174E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9127E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1673E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2744E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4293E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8036E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2703E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6368E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0297E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9094E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8297E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2957E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0001E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9796E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1926E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6994E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9478E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4564E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7075E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7604E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9778E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6189E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9353E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4017E-003 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6674E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2391E-003 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1878E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7582E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9837E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9047E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0142E-003 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1288E-004 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0046E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0246E-004 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3403E-003 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2523E-004 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3879E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2457E-004 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0751E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4489E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8383E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9319E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1430E-003 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9317E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3924E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7331E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3355E-004 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2438E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1425E-004 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4946E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2653E-004 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4563E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8861E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0100E-003 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4860E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1968E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8658E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8662E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5300E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4205E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6558E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7122E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1304E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4500E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1583E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1409E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7101E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0826E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2504E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6374E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3829E-004 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2874E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2054E-004 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0744E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4736E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2543E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8833E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3453E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8406E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6336E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7409E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3566E-004 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5043E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3845E-004 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0461E-004 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5303E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4924E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1461E-004 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2434E-004 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8753E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2353E-004 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0430E-004 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2098E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5178E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8147E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8737E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8213E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7156E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1971E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7857E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0452E-004 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9739E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5539E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7160E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9568E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8821E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8869E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8799E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6474E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8551E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4853E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6995E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2471E-004 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1624E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3028E-004 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3547E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2086E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2207E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9668E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.6899E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5397E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.2450E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.3665E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1031E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7938E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1762E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.6786E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4516E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.2820E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.8236E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1576E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.5212E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1395E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.4070E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7574E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.0806E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.1027E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.6670E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.4545E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.2758E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2519E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9331E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.8476E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.0849E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.1328E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.6691E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.2913E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.2731E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2518E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9331E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11396.86507 | 13676.23809 | 0.93888 | 1.12666 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 32.44067 | 1.71658E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 6017.04038 | 7220.44846 | 0.16882 | 0.20259 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 8.70000 | 6.99286E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 34259.05344 | 41110.86413 | 2.20033 | 2.64040 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.13300 | 1.71671E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 9402.74275 | 11283.29130 | 0.22261 | 0.42471 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 8.70000 | 6.99286E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.13300 | 1.71671E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.97684 | 00:10:00 | 8.70000 | 6.99286E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17257.89 | 1.12666 | 1.12666 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 6170.51 | 0.20259 | 0.20259 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 50219.17 | 2.64040 | 2.64040 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 16066.25 | 0.42471 | 0.42471 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12666 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.64040 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 39930.58449 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12666 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12666 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12666 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12666 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.12666 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.12666 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.64040 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.64040 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.64040 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.64040 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.64040 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.64040 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.12666 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.64040 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.12666 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.12666 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1247.39318 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.12666 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12666 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12666 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74360 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.12666 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56333 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.75111 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23238.14000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11619.07000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76407 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76407 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23238.14000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27371.49710 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 27371.49710 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.64040 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.64040 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2825.35017 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.64040 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.64040 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.64040 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.74266 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.64040 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.32020 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.76027 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 65567.36000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32783.68000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 65567.36000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 81514.15035 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 81514.15035 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 22363.2 | 11.89 | 11.62 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 63515.0 | 12.06 | 11.79 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 3.2677731481E-002 | 2.5233966742E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 9.0558818605E-002 | 0.1288443237 | Pass | Pass | 1.1044266161 | 9.0301878718 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.0342754975E-002 | 2.9244807188E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6771.33 | 338.59 | 0.00 | -67.1 | 486.61 | 7529.41 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.55 | 0.250 | 0.259 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.55 | 0.250 | 0.259 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.504_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.865 | 0.251 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.504_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.865 | 0.251 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.504_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.865 | 0.251 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.504_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.865 | 0.251 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.647 | 0.529 | 0.530 | |||||||||||||||||
North Total or Average | 6.51 | 2.865 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.793 | 0.552 | 0.553 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 8.9961 | 236.88 | 2131.00 | LightsWired | LTG_SCH_OFFICE | 51.55 | 168.00 | 46.59 | 0.0000 | Y | 18.64 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 9.2031 | 1393.41 | 12823.73 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 23.58 | 0.0000 | Y | 56.77 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 5.6188 | 3204.84 | 18007.22 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 21.09 | 0.0000 | Y | 71.28 |
Interior Lighting Total | 6.8172 | 4835.13 | 32961.95 | 146.69 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12823.73 | 3205.93 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12823.73 | 3205.93 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18007.22 | 4501.81 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18007.22 | 4501.81 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2131.00 | 309.00 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.05 | 2131.00 | 106.55 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 94.73 | AstronomicalClock | - | 41.82 | 41.82 | 0.74 | |
EXTERIOR_LIGHTS_B | 6863.48 | AstronomicalClock | - | 83.82 | 71.22 | 91.76 | |
Exterior Lighting Total | 6958.21 | 92.51 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23238.14 | 17755.57 | 5482.57 | 0.76 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 65567.36 | 45967.96 | 19599.40 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 22363.2 | 11.89 | 11.62 | ||||
PSZ-FINE STORAGE COOLING COIL | 63515.0 | 12.06 | 11.79 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 39930.58 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 27371.50 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 81514.15 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.13 | 1247.39 | 1107.16 | 1.00 | 1.37 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.64 | 2825.35 | 1070.05 | 1.00 | 1.28 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11396.87 | 13676.24 | 57.73 | 0.939 | 1.127 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 23.90 | 23.90 | 0.00864 | 32.44 | 0.01717 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 34259.05 | 41110.86 | 29.50 | 2.200 | 2.640 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.70 | 0.00941 | 33.13 | 0.01717 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 33.37 | 0.01724 | 33.13 | 0.01717 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 6017.04 | 7220.45 | 30.48 | 0.169 | 0.203 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00814 | 8.70 | 0.00699 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 9402.74 | 11283.29 | 8.10 | 0.223 | 0.425 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00743 | 8.70 | 0.00699 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | 00:10:00 | 10.00 | 11.32 | 0.00704 | 8.70 | 0.00699 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.13 | 1.13 | 0.20 | 0.20 | 1.1267 | 1.1267 | 1.1267 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.64 | 2.64 | 0.42 | 0.42 | 2.6404 | 2.6404 | 2.6404 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 39930.584 | 39930.584 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 39930.58 | 39930.58 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 43.33 | 22.13 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 23238.140 | 17755.566 | 1.126660 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 11619.07 | 9392.44 | 0.751107 | 25.58 | 17.69 | 0.00941360 | 12.00 | 11.25 | 0.00800000 | 32.53 | 0.01716594 | 25.15 | 13.6179 | 23.90 | 0.00863902 | 46.7262 | 11390.10 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 27371.497 | 27371.497 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 27371.50 | 27371.50 | 1.126662 | 19.90 | 14.45 | 0.00803445 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 9.0786 | 21.10 | 0.00813845 | 52.2163 | 6017.04 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 65567.360 | 45967.965 | 2.640400 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 32783.68 | 23902.59 | 1.760267 | 28.61 | 19.66 | 0.01065982 | 12.00 | 11.25 | 0.00800000 | 33.20 | 0.01716721 | 25.32 | 24.1277 | 26.70 | 0.00941201 | 43.0501 | 34248.77 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 81514.150 | 81514.150 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 81514.15 | 81514.15 | 2.640398 | 14.46 | 11.63 | 0.00736509 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 16.0851 | 15.56 | 0.00743644 | 67.6279 | 9164.87 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39930.584 | 39930.584 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.17487860 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 39930.58 | 39930.58 | 1.0000 | 1.17487860 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 30204.6 | 43.33 | 22.13 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39930.58 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 10.00 | 0.00800000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23238.140 | 17755.566 | 1.126660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.3394 | 1004.8586 | 1.2027 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.126662 | 1.35507971 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 11619.07 | 9392.44 | 1.0000 | 0.90338523 | 0.751107 | 25.58 | 17.69 | 0.00941360 | 49696.4 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11619.07 | 32.53 | 0.01716594 | 25.15 | 0.10228463 | 13.6179 | 23.90 | 0.00863902 | 23.90 | 0.00863902 | 46.7262 | 11390.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27371.497 | 27371.497 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.126662 | 1.35507971 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 27371.50 | 27371.50 | 1.0000 | 1.35507971 | 1.126662 | 19.90 | 14.45 | 0.00803445 | 40385.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27371.50 | 8.70 | 0.00699286 | 8.70 | 0.10228463 | 9.0786 | 21.02 | 0.00813845 | 21.10 | 0.00813845 | 52.2163 | 6017.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 65567.360 | 45967.965 | 2.640400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6561 | 1004.8586 | 1.2027 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.640398 | 3.17570891 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 32783.68 | 23902.59 | 1.0000 | 2.11714126 | 1.760267 | 28.61 | 19.66 | 0.01065982 | 55975.0 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32783.68 | 33.20 | 0.01716721 | 25.32 | 0.42471127 | 24.1277 | 26.70 | 0.00941201 | 26.70 | 0.00941201 | 43.0501 | 34248.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 81514.150 | 81514.150 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.640398 | 3.17570891 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 81514.15 | 81514.15 | 1.0000 | 3.17570891 | 2.640398 | 14.46 | 11.63 | 0.00736509 | 33143.6 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81514.15 | 8.70 | 0.00699286 | 8.70 | 0.42471127 | 16.0851 | 15.56 | 0.00743644 | 15.56 | 0.00743644 | 67.6279 | 9164.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3225.50 | 895.17 | 688.50 |
ZONE2 FINE STORAGE | 3384.33 | 3161.17 | 2970.33 |
ZONE3 BULK STORAGE | 3319.33 | 3224.50 | 2988.33 |
Facility | 3413.50 | 3313.67 | 3039.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 6.67 | 0.00 | 4.83 |
ZONE2 FINE STORAGE | 0.00 | 174.50 | 0.00 | 4.17 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 181.17 | 0.00 | 9.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.342 | 0.425 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.492 | 0.251 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.160 | 0.000 | 1.160 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.56 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1230701.98 | 0.00 | 1230701.98 | 2211417.14 | 3442119.12 | 3225648.14 | 5426.79 | 3333.21 | 0.00 | 39.04 |
ZONE2 FINE STORAGE | 5569039.18 | 0.00 | 5569039.18 | 6521899.17 | 12090938.34 | 13393694.68 | 5412.29 | 3347.71 | 0.00 | 1104.81 |
ZONE3 BULK STORAGE | 0.00 | 0.22E+09 | 0.22E+09 | 38196385.74 | 0.26E+09 | 30805497.77 | 6807.32 | 46.36 | 1906.32 | 4868.06 |
Total Facility | 6799741.16 | 0.22E+09 | 0.23E+09 | 46929702.05 | 0.27E+09 | 47424840.58 | 7496.12 | 3363.31 | 1906.32 | 4894.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0938 | 0.0000 | 0.0938 | 0.1163 | 0.2101 | 0.1023 | 302.79 | 3333.21 | 0.00 |
ZONE2 FINE STORAGE | 0.3898 | 0.0000 | 0.3898 | 0.1990 | 0.5888 | 0.4247 | 303.00 | 3333.00 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 10.7455 | 10.7455 | 1.5043 | 12.2498 | 0.9768 | 2366.04 | 31.75 | 1238.21 |
Total Facility | 0.4836 | 10.7455 | 11.2291 | 1.8197 | 13.0488 | 1.5038 | 2372.12 | 3334.04 | 1238.21 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1780303.65 | 0.00 | 1780303.65 | 3225648.14 | 5424.79 | 0.33 | 3334.87 | 37.81 |
PSZ-FINE STORAGE | 8056086.20 | 0.00 | 8056086.20 | 13393694.68 | 5363.45 | 8.11 | 3388.44 | 1104.11 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1357 | 0.0000 | 0.1357 | 0.1023 | 301.75 | 0.00 | 3334.25 |
PSZ-FINE STORAGE | 0.5639 | 0.0000 | 0.5639 | 0.4247 | 302.57 | 0.19 | 3333.23 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3380.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 4457.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1476 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6115 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 429 |
Defaulted Fields | 391 |
Fields with Defaults | 1171 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 530.89 | 2146.58 | 23-APR-15:30 | 39507.43 | 09-JUN-15:50 |
Electricity:Building | 299.42 | 1663.58 | 23-APR-15:10 | 25286.67 | 07-NOV-15:50 |
Electricity:Zone:ZONE1 OFFICE | 50.58 | 815.73 | 19-FEB-16:10 | 3198.43 | 27-SEP-07:10 |
Electricity:SpaceType:GENERAL | 285.98 | 1663.58 | 16-APR-15:00 | 24384.31 | 29-DEC-09:10 |
InteriorLights:Electricity | 146.69 | 1089.83 | 16-APR-15:00 | 14271.69 | 29-DEC-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.64 | 241.98 | 19-FEB-16:10 | 1285.93 | 27-SEP-07:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 146.69 | 1089.83 | 16-APR-15:00 | 14271.69 | 29-DEC-09:10 |
LightsWired:InteriorLights:Electricity | 146.69 | 1089.83 | 16-APR-15:00 | 14271.69 | 29-DEC-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.64 | 241.98 | 19-FEB-16:10 | 1285.93 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 146.69 | 1089.83 | 16-APR-15:00 | 14271.69 | 29-DEC-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 56.77 | 352.65 | 01-JAN-11:00 | 5995.09 | 09-JAN-15:50 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 56.77 | 352.65 | 01-JAN-11:00 | 5995.09 | 09-JAN-15:50 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 56.77 | 352.65 | 01-JAN-11:00 | 5995.09 | 09-JAN-15:50 |
Electricity:Zone:ZONE3 BULK STORAGE | 192.07 | 495.20 | 01-JAN-09:50 | 16819.20 | 07-NOV-15:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 71.28 | 495.20 | 01-JAN-09:50 | 7427.98 | 04-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 71.28 | 495.20 | 01-JAN-09:50 | 7427.98 | 04-JAN-17:00 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 35.92 | 0.00 | 01-JAN-00:10 | 4721.98 | 27-JUL-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 13.44 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-MAY-15:30 |
Ventilation (simple):Fans:Electricity | 13.44 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-MAY-15:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 13.44 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-MAY-15:30 |
ElectricityPurchased:Facility | 530.89 | 2146.58 | 23-APR-15:30 | 39507.43 | 09-JUN-15:50 |
ElectricityPurchased:Plant | 530.89 | 2146.58 | 23-APR-15:30 | 39507.43 | 09-JUN-15:50 |
Cogeneration:ElectricityPurchased | 530.89 | 2146.58 | 23-APR-15:30 | 39507.43 | 09-JUN-15:50 |
General:Cogeneration:ElectricityPurchased | 530.89 | 2146.58 | 23-APR-15:30 | 39507.43 | 09-JUN-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 530.89 | 2146.58 | 23-APR-15:30 | 39507.43 | 09-JUN-15:50 |
ElectricityNet:Plant | 530.89 | 2146.58 | 23-APR-15:30 | 39507.43 | 09-JUN-15:50 |
Cogeneration:ElectricityNet | 530.89 | 2146.58 | 23-APR-15:30 | 39507.43 | 09-JUN-15:50 |
General:Cogeneration:ElectricityNet | 530.89 | 2146.58 | 23-APR-15:30 | 39507.43 | 09-JUN-15:50 |
Electricity:HVAC | 116.18 | 0.00 | 01-JAN-00:10 | 18150.57 | 27-JUL-16:10 |
General:Fans:Electricity | 22.48 | 0.00 | 01-JAN-00:10 | 2416.69 | 27-JUL-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 93.69 | 0.00 | 01-JAN-00:10 | 15733.88 | 27-JUL-16:10 |
General:Cooling:Electricity | 93.69 | 0.00 | 01-JAN-00:10 | 15733.88 | 27-JUL-16:10 |
ExteriorLights:Electricity | 92.51 | 0.00 | 01-JAN-07:20 | 6958.21 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.51 | 0.00 | 01-JAN-07:20 | 6958.21 | 01-JAN-06:10 |
Electricity:Plant | 22.79 | 483.00 | 01-JAN-00:10 | 1741.21 | 18-JAN-12:10 |
WaterSystems:Electricity | 22.79 | 483.00 | 01-JAN-00:10 | 1741.21 | 18-JAN-12:10 |
Water Heater:WaterSystems:Electricity | 22.79 | 483.00 | 01-JAN-00:10 | 1741.21 | 18-JAN-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.04 | 0.00 | 01-JAN-00:10 | 4800.20 | 25-JAN-08:10 |
NaturalGas:HVAC | 0.04 | 0.00 | 01-JAN-00:10 | 4800.20 | 25-JAN-08:10 |
Heating:NaturalGas | 0.04 | 0.00 | 01-JAN-00:10 | 4800.20 | 25-JAN-08:10 |
General:Heating:NaturalGas | 0.04 | 0.00 | 01-JAN-00:10 | 4800.20 | 25-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 620.46 | 0.00 | 01-JAN-00:10 | 95649.70 | 27-JUL-16:10 |
EnergyTransfer:Building | 227.52 | 0.00 | 01-JAN-00:10 | 35181.09 | 27-JUL-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 77.89 | 0.00 | 01-JAN-00:10 | 12027.90 | 27-JUL-16:10 |
Heating:EnergyTransfer | 0.14 | 0.00 | 01-JAN-00:10 | 3081.33 | 25-JAN-08:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.07 | 0.00 | 01-JAN-00:10 | 3081.33 | 25-JAN-08:10 |
General:Heating:EnergyTransfer | 0.14 | 0.00 | 01-JAN-00:10 | 3081.33 | 25-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.07 | 0.00 | 01-JAN-00:10 | 3081.33 | 25-JAN-08:10 |
Cooling:EnergyTransfer | 227.38 | 0.00 | 01-JAN-00:10 | 35181.09 | 27-JUL-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 77.82 | 0.00 | 01-JAN-00:10 | 12027.90 | 27-JUL-16:10 |
General:Cooling:EnergyTransfer | 227.38 | 0.00 | 01-JAN-00:10 | 35181.09 | 27-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 77.82 | 0.00 | 01-JAN-00:10 | 12027.90 | 27-JUL-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 149.63 | 0.00 | 01-JAN-00:10 | 25982.90 | 06-AUG-14:30 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.07 | 0.00 | 01-JAN-00:10 | 1023.52 | 23-JAN-17:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.07 | 0.00 | 01-JAN-00:10 | 1023.52 | 23-JAN-17:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 149.57 | 0.00 | 01-JAN-00:10 | 25982.90 | 06-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 149.57 | 0.00 | 01-JAN-00:10 | 25982.90 | 06-AUG-14:30 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 392.94 | 0.00 | 01-JAN-00:10 | 60468.61 | 27-JUL-16:10 |
HeatingCoils:EnergyTransfer | 0.03 | 0.00 | 01-JAN-00:10 | 3460.53 | 25-JAN-08:10 |
CoolingCoils:EnergyTransfer | 392.91 | 0.00 | 01-JAN-00:10 | 60468.61 | 27-JUL-16:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.072 | -77.811 | 0.000 | 0.000 | 9.072 | 18.637 | 31.946 | 11.132 | 0.000 | 4.792 | 11.317 | 0.000 | -3.601 | 0.000 | -5.556 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.066 | -149.558 | 0.000 | 0.000 | 17.600 | 56.770 | 0.000 | 70.757 | 0.000 | 5.480 | 28.509 | 0.000 | -10.310 | 0.000 | -19.314 | -0.004 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32.592 | 71.283 | 107.344 | 757.724 | 0.000 | 7.084 | 0.012 | 0.000 | -99.572 | 0.000 | -332.090 | -544.366 |
Total Facility | 0.000 | 0.000 | 0.137 | -227.369 | 0.000 | 0.000 | 59.265 | 146.690 | 139.290 | 839.613 | 0.000 | 17.357 | 39.838 | 0.000 | -113.483 | 0.000 | -356.960 | -544.370 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 20-APR-07:03 | 0.00 | 0.00 | 0.00 | -19858.40 | 0.00 | 0.00 | 823.05 | 1212.05 | 1912.50 | 51.64 | 0.00 | 0.00 | 16166.57 | 0.00 | -0.00 | 0.00 | -307.41 | 0.00 |
ZONE2 FINE STORAGE | 09-APR-16:03 | 0.00 | 0.00 | 0.00 | -55093.16 | 0.00 | 0.00 | 0.00 | 528.98 | 0.00 | 5160.21 | 0.00 | 71.10 | 49332.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-AUG-06:01 | 0.00 | 0.00 | 0.00 | -58889.89 | 0.00 | 0.00 | 1077.44 | 10863.25 | 3006.28 | 0.00 | 0.00 | 27.32 | 50506.89 | 0.00 | -4287.89 | 0.00 | -2303.41 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 25-JAN-08:62 | 0.00 | 0.00 | 12325.60 | 0.00 | 0.00 | 0.00 | 1137.28 | 1248.11 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -374.36 | 0.00 | -1289.24 | -14959.88 |
ZONE2 FINE STORAGE | 01-AUG-06:02 | 0.00 | 0.00 | 2279.68 | 0.00 | 0.00 | 0.00 | 338.71 | 4231.83 | 0.00 | 207.47 | 0.00 | 522.63 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7580.32 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-JAN-08:62 | -4187.69 | 4187.69 | 12325.60 | -4187.69 | 0.00 | 0.00 | 9696.09 | 12727.88 | 10112.62 | 1023.33 | 0.00 | 0.00 | 0.00 | 0.00 | -374.36 | 0.00 | -33479.59 | -7843.89 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1267 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1267 | 0.0908 | 1.0000 | Not calculated | 0.1023 | 0.0908 | ||
PSZ-FINE STORAGE | 2.6404 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6404 | 0.1609 | 1.0000 | Not calculated | 0.4247 | 0.1609 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1267 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1267 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0908 | ||
PSZ-FINE STORAGE | 2.6404 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6404 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1609 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1267 | 1.1267 | 1.1267 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6404 | 2.6404 | 2.6404 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1267 | 1.1267 | 1.1267 | 1.1267 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6404 | 2.6404 | 2.6404 | 2.6404 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1267 | 1.1267 | 1.1267 | No | 0.1023 | 0.5049 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6404 | 2.6404 | 2.6404 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1267 | 1.1267 | 1.1267 | 1.1267 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6404 | 2.6404 | 2.6404 | 2.6404 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 9.00 |
Number of hours not met | 9.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.04 | 4800.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 93.69 | 15733.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 146.69 | 14271.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.51 | 6958.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 13.44 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 22.48 | 2416.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.79 | 1741.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 530.89 |
Natural Gas | 0.00 | 0.04 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 530.93 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 30.34 |
Space Heating | 0.00 |
Space Cooling | 19.38 |
Fans (All) | 7.43 |
Service Water Heating | 4.71 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 109.80 |
Subtotal | 109.80 |
Natural Gas [MJ/m2] | |
Space Heating | 0.01 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.01 |
Subtotal | 0.01 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 27.63 |
Space Heating | 0.01 |
Space Cooling | 17.65 |
Fans (All) | 6.77 |
Service Water Heating | 4.29 |
Receptacle Equipment | 26.23 |
Miscellaneous | 17.42 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2688. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 4836.33 | 3790.17 | 133.50 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2686.67 | 6073.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2510.50 | 3043.50 | 3206.00 | 0.00 | 0.00 |
Min | 2510.50 | 3043.50 | 0.00 | 0.00 | 0.00 |
Max | 4836.33 | 6073.33 | 3206.00 | 0.00 | 0.00 |
Average | 3344.50 | 4302.33 | 1113.17 | 0.00 | 0.00 |
Sum | 10033.50 | 12907.00 | 3339.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 32803.17 | 223.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 15880.50 | 66838.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 43191.00 | 67077.00 | 80925.00 | 0.00 | 0.00 |
Min | 15880.50 | 223.83 | 0.00 | 0.00 | 0.00 |
Max | 43191.00 | 67077.00 | 80925.00 | 0.00 | 0.00 |
Average | 30624.89 | 44713.11 | 26975.00 | 0.00 | 0.00 |
Sum | 91874.67 | 134139.33 | 80925.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 3690.33 | 5064.83 | 4.83 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 1429.50 | 7330.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1446.00 | 5884.33 | 1429.67 | 0.00 | 0.00 |
Min | 1429.50 | 5064.83 | 0.00 | 0.00 | 0.00 |
Max | 3690.33 | 7330.50 | 1429.67 | 0.00 | 0.00 |
Average | 2188.61 | 6093.22 | 478.17 | 0.00 | 0.00 |
Sum | 6565.83 | 18279.67 | 1434.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 29683.67 | 3343.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 10636.00 | 72083.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 26517.00 | 118246.67 | 46429.33 | 0.00 | 0.00 |
Min | 10636.00 | 3343.33 | 0.00 | 0.00 | 0.00 |
Max | 29683.67 | 118246.67 | 46429.33 | 0.00 | 0.00 |
Average | 22278.89 | 64557.67 | 15476.44 | 0.00 | 0.00 |
Sum | 66836.67 | 193673.00 | 46429.33 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:52
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374604E+10 | 15163.04 | 13-JAN-08:62 | 23.07 | 19.92 | 0.632463E+09 | 879.39 | 14-JAN-08:09 | 21.15 | 19.82 |
February | 0.400908E+10 | 16558.94 | 16-FEB-08:62 | 22.98 | 18.55 | 0.583196E+09 | 879.38 | 18-FEB-08:09 | 23.40 | 20.75 |
March | 0.515919E+10 | 16939.30 | 03-MAR-08:62 | 22.48 | 18.10 | 0.685814E+09 | 879.39 | 25-MAR-07:10 | 22.38 | 19.30 |
April | 0.644437E+10 | 19859.44 | 20-APR-07:03 | 21.47 | 15.09 | 0.640424E+09 | 879.39 | 28-APR-07:10 | 23.40 | 18.92 |
May | 0.780186E+10 | 18085.61 | 08-MAY-06:02 | 24.08 | 19.23 | 0.666920E+09 | 879.39 | 12-MAY-07:10 | 25.87 | 22.94 |
June | 0.808831E+10 | 16040.11 | 17-JUN-06:01 | 25.10 | 21.21 | 0.667313E+09 | 879.39 | 09-JUN-07:10 | 25.10 | 21.21 |
July | 0.836743E+10 | 15931.80 | 06-JUL-06:01 | 24.08 | 22.05 | 0.641678E+09 | 879.39 | 28-JUL-07:10 | 25.28 | 24.00 |
August | 0.877742E+10 | 16293.02 | 30-AUG-06:01 | 24.68 | 23.02 | 0.692990E+09 | 879.45 | 21-AUG-07:10 | 24.68 | 23.02 |
September | 0.797522E+10 | 15750.63 | 05-SEP-06:01 | 22.38 | 21.49 | 0.641592E+09 | 879.39 | 22-SEP-07:10 | 27.80 | 25.67 |
October | 0.743748E+10 | 19234.32 | 18-OCT-06:01 | 25.00 | 18.59 | 0.641426E+09 | 879.39 | 03-OCT-07:10 | 25.00 | 18.59 |
November | 0.579556E+10 | 16491.40 | 20-NOV-07:02 | 24.40 | 20.33 | 0.613580E+09 | 879.39 | 30-NOV-08:09 | 25.68 | 24.45 |
December | 0.421335E+10 | 18810.95 | 02-DEC-07:02 | 20.78 | 19.15 | 0.634091E+09 | 879.39 | 06-DEC-08:09 | 24.08 | 21.55 |
Annual Sum or Average | 0.778153E+11 | 0.774149E+10 | ||||||||
Minimum of Months | 0.374604E+10 | 15163.04 | 20.78 | 15.09 | 0.583196E+09 | 879.38 | 21.15 | 18.59 | ||
Maximum of Months | 0.877742E+10 | 19859.44 | 25.10 | 23.02 | 0.692990E+09 | 879.45 | 27.80 | 25.67 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276293E+10 | 20366.18 | 01-JAN-15:00 | 26.10 | 21.82 | 0.170418E+10 | 2246.82 | 09-JAN-16:30 | 21.15 | 13.87 |
February | 0.329243E+10 | 29966.42 | 19-FEB-14:55 | 27.20 | 21.86 | 0.160535E+10 | 2254.48 | 08-FEB-16:40 | 27.20 | 21.86 |
March | 0.586671E+10 | 39723.30 | 28-MAR-17:10 | 25.92 | 20.77 | 0.190928E+10 | 2246.87 | 11-MAR-14:20 | 25.92 | 20.77 |
April | 0.116348E+11 | 55093.69 | 09-APR-16:03 | 27.12 | 18.61 | 0.184873E+10 | 2246.95 | 11-APR-13:39 | 28.53 | 21.98 |
May | 0.169894E+11 | 51142.35 | 02-MAY-17:08 | 28.12 | 19.68 | 0.192837E+10 | 2246.95 | 11-MAY-13:20 | 29.40 | 23.01 |
June | 0.194316E+11 | 49195.78 | 11-JUN-13:53 | 31.70 | 23.81 | 0.192900E+10 | 2246.97 | 08-JUN-15:00 | 31.70 | 23.81 |
July | 0.226057E+11 | 48763.23 | 16-JUL-14:02 | 31.10 | 24.30 | 0.185477E+10 | 2247.00 | 27-JUL-14:39 | 34.23 | 25.01 |
August | 0.208195E+11 | 47716.82 | 06-AUG-14:23 | 31.95 | 25.24 | 0.200316E+10 | 2247.00 | 23-AUG-13:39 | 32.77 | 25.41 |
September | 0.194041E+11 | 48743.80 | 03-SEP-13:53 | 24.40 | 21.27 | 0.185479E+10 | 2246.98 | 20-SEP-14:09 | 32.12 | 25.35 |
October | 0.149420E+11 | 49973.38 | 15-OCT-15:33 | 29.07 | 20.86 | 0.185439E+10 | 2246.95 | 13-OCT-13:30 | 29.07 | 20.86 |
November | 0.746514E+10 | 31156.93 | 03-NOV-17:10 | 27.80 | 24.12 | 0.175870E+10 | 2246.80 | 04-NOV-07:49 | 26.02 | 24.58 |
December | 0.435263E+10 | 28742.42 | 10-DEC-16:15 | 27.93 | 22.51 | 0.171427E+10 | 2249.12 | 18-DEC-14:30 | 25.00 | 19.78 |
Annual Sum or Average | 0.149567E+12 | 0.219650E+11 | ||||||||
Minimum of Months | 0.276293E+10 | 20366.18 | 24.40 | 18.61 | 0.160535E+10 | 2246.80 | 21.15 | 13.87 | ||
Maximum of Months | 0.226057E+11 | 55093.69 | 31.95 | 25.24 | 0.200316E+10 | 2254.48 | 34.23 | 25.41 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 | 0.379795E+10 | 5575.39 | 07-JAN-14:09 | 27.80 | 22.72 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 | 0.352778E+10 | 5634.91 | 22-FEB-16:10 | 27.43 | 14.84 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 | 0.439148E+10 | 5979.40 | 30-MAR-14:20 | 26.50 | 20.57 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 | 0.494360E+10 | 7369.46 | 17-APR-15:20 | 32.03 | 19.94 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 | 0.543182E+10 | 8156.50 | 22-MAY-13:30 | 34.15 | 23.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 | 0.554457E+10 | 7322.31 | 10-JUN-15:50 | 31.70 | 24.34 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 26.83 | 23.72 | 0.562095E+10 | 8708.12 | 29-JUL-15:00 | 35.60 | 24.39 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 | 0.593070E+10 | 8066.18 | 23-AUG-13:09 | 33.62 | 25.44 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 | 24.00 | 0.540317E+10 | 7480.68 | 13-SEP-14:09 | 32.12 | 24.21 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 | 23.96 | 0.521208E+10 | 7376.20 | 14-OCT-13:30 | 31.95 | 24.19 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 | 0.451782E+10 | 6390.62 | 03-NOV-13:50 | 29.40 | 24.41 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 | 21.22 | 0.408613E+10 | 6273.42 | 08-DEC-14:09 | 27.70 | 22.74 |
Annual Sum or Average | 0.00 | 0.584080E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.352778E+10 | 5575.39 | 26.50 | 14.84 | ||
Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.593070E+10 | 8708.12 | 35.60 | 25.44 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7380676.46 | 12325.31 | 25-JAN-08:62 | 10.18 |
February | 7451418.08 | 7107.12 | 04-FEB-08:63 | 7.25 |
March | 11045783.52 | 11794.43 | 16-MAR-07:03 | 6.97 |
April | 4274674.43 | 645.81 | 07-APR-06:05 | 23.40 |
May | 6114535.39 | 753.85 | 20-MAY-06:06 | 25.78 |
June | 5888268.75 | 963.59 | 08-JUN-06:07 | 28.30 |
July | 5599374.17 | 820.13 | 08-JUL-06:20 | 27.07 |
August | 5952897.95 | 948.64 | 19-AUG-06:20 | 27.97 |
September | 4663352.06 | 905.70 | 09-SEP-06:20 | 27.80 |
October | 4300857.57 | 779.42 | 18-OCT-06:04 | 25.00 |
November | 3280182.02 | 803.74 | 29-NOV-07:05 | 25.00 |
December | 5820653.19 | 11912.18 | 15-DEC-08:62 | 8.68 |
Annual Sum or Average | 71772673.60 | |||
Minimum of Months | 3280182.02 | 645.81 | 6.97 | |
Maximum of Months | 11045783.52 | 12325.31 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8302517.80 | 1023.52 | 23-JAN-17:10 | 26.32 |
February | 26565630.24 | 925.81 | 07-FEB-12:30 | 25.85 |
March | 1409883.78 | 336.56 | 18-MAR-16:20 | 25.00 |
April | 106013.35 | 510.91 | 12-APR-06:03 | 25.10 |
May | 1223798.58 | 831.53 | 19-MAY-06:03 | 25.28 |
June | 1943301.61 | 2049.75 | 08-JUN-06:03 | 28.30 |
July | 1281344.78 | 1105.41 | 12-JUL-06:03 | 26.10 |
August | 2844973.29 | 2279.77 | 01-AUG-06:02 | 28.30 |
September | 1293761.63 | 2049.15 | 09-SEP-06:03 | 27.80 |
October | 1097496.90 | 1490.97 | 02-OCT-06:03 | 26.70 |
November | 2146497.39 | 825.95 | 04-NOV-06:03 | 25.60 |
December | 17336207.02 | 568.64 | 22-DEC-12:30 | 25.00 |
Annual Sum or Average | 65551426.38 | |||
Minimum of Months | 106013.35 | 336.56 | 25.00 | |
Maximum of Months | 26565630.24 | 2279.77 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.159463E+10 | 1267.28 | 04-JAN-16:00 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.143430E+10 | 1248.93 | 07-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.162103E+10 | 1258.99 | 14-MAR-07:10 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.152659E+10 | 1258.56 | 12-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.157615E+10 | 1246.95 | 27-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.155255E+10 | 1271.18 | 15-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.153141E+10 | 1241.85 | 05-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.160131E+10 | 1258.92 | 28-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.152881E+10 | 1285.93 | 27-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.156089E+10 | 1271.74 | 31-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.151974E+10 | 1264.76 | 24-NOV-08:09 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.158972E+10 | 1279.50 | 15-DEC-16:00 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.186371E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.143430E+10 | 1241.85 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.162103E+10 | 1285.93 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.526209E+10 | 5995.09 | 09-JAN-15:50 | 0.00 | 0.00 |
February | 0.454051E+10 | 5495.50 | 07-FEB-09:09 | 0.00 | 0.00 |
March | 0.504360E+10 | 5995.09 | 15-MAR-08:09 | 0.00 | 0.00 |
April | 0.450607E+10 | 5289.79 | 03-APR-07:10 | 0.00 | 0.00 |
May | 0.460420E+10 | 5289.79 | 02-MAY-07:10 | 0.00 | 0.00 |
June | 0.455259E+10 | 5495.50 | 13-JUN-08:09 | 0.00 | 0.00 |
July | 0.437205E+10 | 5289.79 | 25-JUL-07:10 | 0.00 | 0.00 |
August | 0.463532E+10 | 5289.79 | 28-AUG-07:10 | 0.00 | 0.00 |
September | 0.447447E+10 | 5495.50 | 26-SEP-08:09 | 0.00 | 0.00 |
October | 0.478923E+10 | 5995.09 | 23-OCT-08:09 | 0.00 | 0.00 |
November | 0.477155E+10 | 5495.50 | 02-NOV-08:09 | 0.00 | 0.00 |
December | 0.521815E+10 | 5995.09 | 06-DEC-15:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.567698E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.437205E+10 | 5289.79 | 0.00 | 0.00 | |
Maximum of Months | 0.526209E+10 | 5995.09 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.642820E+10 | 7427.98 | 04-JAN-16:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.564252E+10 | 6808.98 | 07-FEB-08:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.628556E+10 | 7427.98 | 13-MAR-07:10 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.565767E+10 | 6189.98 | 03-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.577082E+10 | 6189.98 | 02-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.573955E+10 | 7427.98 | 15-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.555727E+10 | 5942.38 | 05-JUL-06:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.593451E+10 | 6189.98 | 12-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.571291E+10 | 7427.98 | 27-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.603959E+10 | 7427.98 | 18-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.600817E+10 | 7427.98 | 02-NOV-07:10 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.650624E+10 | 7427.98 | 01-DEC-16:49 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.712830E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.555727E+10 | 5942.38 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.650624E+10 | 7427.98 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.159463E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52955666.35 | 0.962026E+09 |
February | 0.127628E+10 | 0.143430E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113946E+09 | 0.819600E+09 |
March | 0.149825E+10 | 0.162103E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129810E+09 | 0.952709E+09 |
April | 0.138726E+10 | 0.152659E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279251E+09 | 0.477017E+09 |
May | 0.144276E+10 | 0.157615E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608444E+09 | 0.264206E+09 |
June | 0.144276E+10 | 0.155255E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644446E+09 | 96297617.65 |
July | 0.138726E+10 | 0.153141E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720036E+09 | 88487572.30 |
August | 0.149825E+10 | 0.160131E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778960E+09 | 77871220.92 |
September | 0.138726E+10 | 0.152881E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626844E+09 | 0.114480E+09 |
October | 0.138726E+10 | 0.156089E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497839E+09 | 0.210580E+09 |
November | 0.133177E+10 | 0.151974E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276677E+09 | 0.544059E+09 |
December | 0.138726E+10 | 0.158972E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63071705.03 | 0.948290E+09 |
Annual Sum or Average | 0.168137E+11 | 0.186371E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479228E+10 | 0.555562E+10 |
Minimum of Months | 0.127628E+10 | 0.143430E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52955666.35 | 77871220.92 |
Maximum of Months | 0.149825E+10 | 0.162103E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778960E+09 | 0.962026E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.526209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10212548.42 | 0.278453E+10 |
February | 0.300332E+10 | 0.454051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15809166.11 | 0.335065E+10 |
March | 0.352563E+10 | 0.504360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37757281.63 | 0.362880E+10 |
April | 0.326447E+10 | 0.450607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174958E+09 | 0.200252E+10 |
May | 0.339505E+10 | 0.460420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685506E+09 | 0.947345E+09 |
June | 0.339505E+10 | 0.455259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923032E+09 | 0.279030E+09 |
July | 0.326447E+10 | 0.437205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983358E+09 | 0.204210E+09 |
August | 0.352563E+10 | 0.463532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109052E+10 | 0.197457E+09 |
September | 0.326447E+10 | 0.447447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987653E+09 | 0.296407E+09 |
October | 0.326447E+10 | 0.478923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473374E+09 | 0.650942E+09 |
November | 0.313390E+10 | 0.477155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78806931.60 | 0.210107E+10 |
December | 0.326447E+10 | 0.521815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19399080.82 | 0.287126E+10 |
Annual Sum or Average | 0.395654E+11 | 0.567698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548039E+10 | 0.193142E+11 |
Minimum of Months | 0.300332E+10 | 0.437205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10212548.42 | 0.197457E+09 |
Maximum of Months | 0.352563E+10 | 0.526209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109052E+10 | 0.362880E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.642820E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108020E+09 | 0.144838E+11 |
February | 0.690763E+10 | 0.564252E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380217E+09 | 0.145141E+11 |
March | 0.810895E+10 | 0.628556E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62914340.36 | 0.193128E+11 |
April | 0.750829E+10 | 0.565767E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7430419.16 | 0.164600E+11 |
May | 0.780862E+10 | 0.577082E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83733371.75 | 0.115247E+11 |
June | 0.780862E+10 | 0.573955E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2817481.95 | 0.570140E+10 |
July | 0.750829E+10 | 0.555727E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86310524.33 | 0.390623E+10 |
August | 0.810895E+10 | 0.593451E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23314099.37 | 0.457789E+10 |
September | 0.750829E+10 | 0.571291E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5403790.98 | 0.495173E+10 |
October | 0.750829E+10 | 0.603959E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12284378.87 | 0.863348E+10 |
November | 0.720796E+10 | 0.600817E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11053690.61 | 0.143424E+11 |
December | 0.750829E+10 | 0.650624E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60925368.51 | 0.167624E+11 |
Annual Sum or Average | 0.910005E+11 | 0.712830E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844424E+09 | 0.135171E+12 |
Minimum of Months | 0.690763E+10 | 0.555727E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2817481.95 | 0.390623E+10 |
Maximum of Months | 0.810895E+10 | 0.650624E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380217E+09 | 0.193128E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1267.28 | 04-JAN-16:00 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.13 | 02-JAN-12:10 | 5235.57 | 25-JAN-07:03 |
February | 1680.92 | 01-FEB-08:09 | 1248.93 | 07-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1520.43 | 02-FEB-13:00 | 5426.39 | 03-FEB-07:03 |
March | 1680.92 | 01-MAR-08:09 | 1258.99 | 14-MAR-07:10 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2362.00 | 13-MAR-16:50 | 6834.20 | 16-MAR-06:03 |
April | 1680.92 | 01-APR-07:10 | 1258.56 | 12-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3004.95 | 17-APR-17:00 | 3751.14 | 19-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 1246.95 | 27-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3916.88 | 22-MAY-16:10 | 1789.14 | 01-MAY-06:03 |
June | 1680.92 | 01-JUN-07:10 | 1271.18 | 15-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2946.52 | 09-JUN-16:10 | 1290.22 | 14-JUN-06:02 |
July | 1680.92 | 01-JUL-07:10 | 1241.85 | 05-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4529.71 | 27-JUL-16:10 | 1233.43 | 07-JUL-06:01 |
August | 1680.92 | 01-AUG-07:10 | 1258.92 | 28-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3412.97 | 23-AUG-12:00 | 1651.35 | 14-AUG-06:01 |
September | 1680.92 | 01-SEP-07:10 | 1285.93 | 27-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3396.17 | 18-SEP-16:10 | 1944.55 | 05-SEP-06:01 |
October | 1680.92 | 02-OCT-07:10 | 1271.74 | 31-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3159.52 | 03-OCT-16:10 | 2016.41 | 31-OCT-06:02 |
November | 1680.92 | 01-NOV-07:10 | 1264.76 | 24-NOV-08:09 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1844.45 | 03-NOV-16:10 | 5414.61 | 27-NOV-07:03 |
December | 1680.92 | 01-DEC-08:09 | 1279.50 | 15-DEC-16:00 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.12 | 08-DEC-13:00 | 6231.28 | 27-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1241.85 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.13 | 1233.43 | |||||
Maximum of Months | 1680.92 | 1285.93 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4529.71 | 6834.20 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 5995.09 | 09-JAN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.26 | 07-JAN-13:00 | 6644.92 | 24-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 5495.50 | 07-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.29 | 02-FEB-14:00 | 7869.13 | 03-FEB-09:00 |
March | 3955.50 | 01-MAR-08:09 | 5995.09 | 15-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1740.71 | 13-MAR-17:00 | 8225.92 | 15-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 5289.79 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2837.91 | 15-APR-17:00 | 3947.76 | 18-APR-08:00 |
May | 3955.50 | 01-MAY-07:10 | 5289.79 | 02-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4590.46 | 22-MAY-15:20 | 3096.15 | 10-MAY-15:10 |
June | 3955.50 | 01-JUN-07:10 | 5495.50 | 13-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2396.50 | 08-JUN-16:00 | 1819.35 | 18-JUN-20:00 |
July | 3955.50 | 01-JUL-07:10 | 5289.79 | 25-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3973.79 | 27-JUL-16:00 | 1437.61 | 04-JUL-03:00 |
August | 3955.50 | 01-AUG-07:10 | 5289.79 | 28-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3070.59 | 16-AUG-16:00 | 2209.94 | 14-AUG-03:00 |
September | 3955.50 | 01-SEP-07:10 | 5495.50 | 26-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3067.34 | 18-SEP-16:00 | 1308.67 | 19-SEP-23:30 |
October | 3955.50 | 02-OCT-07:10 | 5995.09 | 23-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3023.89 | 03-OCT-15:10 | 2206.67 | 16-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 5495.50 | 02-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.47 | 03-NOV-16:00 | 7651.34 | 11-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 5995.09 | 06-DEC-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1228.45 | 10-DEC-15:00 | 7342.73 | 27-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 5289.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.26 | 1308.67 | ||||
Maximum of Months | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4590.46 | 8225.92 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 7427.98 | 04-JAN-16:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4136.94 | 29-JAN-12:00 | 32829.96 | 24-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 6808.98 | 07-FEB-08:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8983.17 | 08-FEB-13:10 | 36677.69 | 03-FEB-09:00 |
March | 9097.65 | 01-MAR-08:09 | 7427.98 | 13-MAR-07:10 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2470.42 | 13-MAR-16:00 | 41410.75 | 15-MAR-08:00 |
April | 9097.65 | 01-APR-07:10 | 6189.98 | 03-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 923.05 | 16-APR-12:53 | 25455.56 | 18-APR-09:00 |
May | 9097.65 | 01-MAY-07:10 | 6189.98 | 02-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3964.29 | 29-MAY-11:00 | 27150.20 | 10-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 7427.98 | 15-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 468.35 | 11-JUN-12:33 | 20016.64 | 22-JUN-09:00 |
July | 9097.65 | 01-JUL-07:10 | 5942.38 | 05-JUL-06:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1556.80 | 27-JUL-16:00 | 14012.98 | 14-JUL-15:00 |
August | 9097.65 | 01-AUG-07:10 | 6189.98 | 12-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1219.16 | 22-AUG-10:55 | 16748.46 | 12-AUG-08:00 |
September | 9097.65 | 01-SEP-07:10 | 7427.98 | 27-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 676.44 | 07-SEP-17:55 | 11784.17 | 02-SEP-12:10 |
October | 9097.65 | 02-OCT-07:10 | 7427.98 | 18-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.32 | 03-OCT-10:45 | 16317.05 | 13-OCT-15:52 |
November | 9097.65 | 01-NOV-07:10 | 7427.98 | 02-NOV-07:10 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1896.60 | 17-NOV-15:00 | 38487.68 | 11-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 7427.98 | 01-DEC-16:49 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2534.91 | 24-DEC-12:00 | 34208.81 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 5942.38 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 468.35 | 11784.17 | |||||
Maximum of Months | 9097.65 | 7427.98 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 8983.17 | 41410.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15163.04 | 13-JAN-08:62 | 8404.61 | 6232.36 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.17 |
February | 16558.94 | 16-FEB-08:62 | 8404.61 | 6116.37 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.71 |
March | 16939.30 | 03-MAR-08:62 | 6723.69 | 4862.34 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.42 |
April | 19859.44 | 20-APR-07:03 | 6723.69 | 4848.21 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.41 |
May | 18085.61 | 08-MAY-06:02 | 2117.96 | 4086.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.15 |
June | 16040.11 | 17-JUN-06:01 | 2470.96 | 4797.46 | 6693.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.63 |
July | 15931.80 | 06-JUL-06:01 | 2470.96 | 4806.44 | 6693.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1189.09 |
August | 16293.02 | 30-AUG-06:01 | 2470.96 | 4898.67 | 6693.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 944.58 |
September | 15750.63 | 05-SEP-06:01 | 2470.96 | 4903.84 | 6693.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1944.55 |
October | 19234.32 | 18-OCT-06:01 | 2470.96 | 4909.93 | 6693.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 823.35 |
November | 16491.40 | 20-NOV-07:02 | 2117.96 | 4124.21 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 990.91 |
December | 18810.95 | 02-DEC-07:02 | 1764.97 | 3460.50 | 4781.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15163.04 | 1764.97 | 3460.50 | 4781.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 | |
Maximum of Months | 19859.44 | 8404.61 | 6232.36 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1944.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20366.18 | 01-JAN-15:00 | 0.00 | 705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.36 |
February | 29966.42 | 19-FEB-14:55 | 0.00 | 940.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.26 | 0.00 |
March | 39723.30 | 28-MAR-17:10 | 0.00 | 2586.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.54 |
April | 55093.69 | 09-APR-16:03 | 0.00 | 1586.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 | 0.00 |
May | 51142.35 | 02-MAY-17:08 | 0.00 | 3232.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.21 | 0.00 |
June | 49195.78 | 11-JUN-13:53 | 0.00 | 1410.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1355.66 | 0.00 |
July | 48763.23 | 16-JUL-14:02 | 0.00 | 1410.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1320.89 | 0.00 |
August | 47716.82 | 06-AUG-14:23 | 0.00 | 1410.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1534.45 | 0.00 |
September | 48743.80 | 03-SEP-13:53 | 0.00 | 1057.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 691.72 |
October | 49973.38 | 15-OCT-15:33 | 0.00 | 1410.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 829.65 | 0.00 |
November | 31156.93 | 03-NOV-17:10 | 0.00 | 2821.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.63 | 0.00 |
December | 28742.42 | 10-DEC-16:15 | 0.00 | 1293.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 20366.18 | 0.00 | 705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55093.69 | 0.00 | 3232.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1534.45 | 691.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 990.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8746.65 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6594.29 |
April | 0.00 | 01-APR-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6141.13 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5358.20 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2538.02 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 1980.79 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1290.60 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 774.75 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2786.95 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 990.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 941.74 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7426.84 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3196.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 990.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1980.79 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8746.65 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.392409E+11 | 32436.63 | 03-JAN-15:30 | 12322726.38 | 4800.20 | 25-JAN-08:09 |
February | 0.356156E+11 | 32126.63 | 11-FEB-16:40 | 4782076.62 | 4262.95 | 04-FEB-08:09 |
March | 0.407211E+11 | 31430.55 | 09-MAR-16:00 | 14093822.17 | 4761.15 | 16-MAR-07:10 |
April | 0.409538E+11 | 36091.14 | 15-APR-15:39 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.462239E+11 | 36874.60 | 31-MAY-14:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.486573E+11 | 39507.43 | 09-JUN-15:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.504972E+11 | 39439.65 | 27-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.519060E+11 | 38550.49 | 22-AUG-12:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.490790E+11 | 38119.52 | 20-SEP-14:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.467997E+11 | 37020.05 | 25-OCT-14:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.409622E+11 | 36959.32 | 07-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.402350E+11 | 35363.69 | 06-DEC-15:50 | 9567649.01 | 4733.48 | 15-DEC-08:09 |
Annual Sum or Average | 0.530892E+12 | 40766274.18 | ||||
Minimum of Months | 0.356156E+11 | 31430.55 | 0.00 | 0.00 | ||
Maximum of Months | 0.519060E+11 | 39507.43 | 14093822.17 | 4800.20 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.132849E+11 | 0.900350E+10 | 0.115358E+11 | 0.00 | 0.161891E+10 | 0.00 | 0.00 | 0.181929E+10 | 0.00 | 0.00 | 0.00 | 0.197851E+10 | 0.00 |
February | 0.116173E+11 | 0.771106E+10 | 0.105871E+11 | 0.00 | 0.149856E+10 | 0.00 | 0.00 | 0.241027E+10 | 0.00 | 0.00 | 0.00 | 0.179121E+10 | 0.00 |
March | 0.129502E+11 | 0.796812E+10 | 0.123431E+11 | 0.00 | 0.177316E+10 | 0.00 | 0.00 | 0.368985E+10 | 0.00 | 0.00 | 0.00 | 0.199671E+10 | 0.00 |
April | 0.116903E+11 | 0.715460E+10 | 0.114862E+11 | 0.00 | 0.212482E+10 | 0.00 | 0.00 | 0.661920E+10 | 0.00 | 0.00 | 0.00 | 0.187868E+10 | 0.00 |
May | 0.119512E+11 | 0.689099E+10 | 0.119357E+11 | 0.00 | 0.327319E+10 | 0.00 | 0.00 | 0.102570E+11 | 0.00 | 0.00 | 0.00 | 0.191583E+10 | 0.00 |
June | 0.118447E+11 | 0.644069E+10 | 0.118862E+11 | 0.00 | 0.446684E+10 | 0.00 | 0.00 | 0.121717E+11 | 0.00 | 0.00 | 0.00 | 0.184728E+10 | 0.00 |
July | 0.114607E+11 | 0.672816E+10 | 0.115358E+11 | 0.00 | 0.517649E+10 | 0.00 | 0.00 | 0.137323E+11 | 0.00 | 0.00 | 0.00 | 0.186367E+10 | 0.00 |
August | 0.121711E+11 | 0.717071E+10 | 0.123357E+11 | 0.00 | 0.498296E+10 | 0.00 | 0.00 | 0.133380E+11 | 0.00 | 0.00 | 0.00 | 0.190744E+10 | 0.00 |
September | 0.117162E+11 | 0.747607E+10 | 0.114788E+11 | 0.00 | 0.449161E+10 | 0.00 | 0.00 | 0.120715E+11 | 0.00 | 0.00 | 0.00 | 0.184489E+10 | 0.00 |
October | 0.123897E+11 | 0.830211E+10 | 0.115432E+11 | 0.00 | 0.315500E+10 | 0.00 | 0.00 | 0.949217E+10 | 0.00 | 0.00 | 0.00 | 0.191752E+10 | 0.00 |
November | 0.122995E+11 | 0.854903E+10 | 0.110862E+11 | 0.00 | 0.172457E+10 | 0.00 | 0.00 | 0.542318E+10 | 0.00 | 0.00 | 0.00 | 0.187969E+10 | 0.00 |
December | 0.133141E+11 | 0.911205E+10 | 0.115358E+11 | 0.00 | 0.163696E+10 | 0.00 | 0.00 | 0.266700E+10 | 0.00 | 0.00 | 0.00 | 0.196914E+10 | 0.00 |
Annual Sum or Average | 0.146690E+12 | 0.925071E+11 | 0.139290E+12 | 0.00 | 0.359231E+11 | 0.00 | 0.00 | 0.936914E+11 | 0.00 | 0.00 | 0.00 | 0.227906E+11 | 0.00 |
Minimum of Months | 0.114607E+11 | 0.644069E+10 | 0.105871E+11 | 0.00 | 0.149856E+10 | 0.00 | 0.00 | 0.181929E+10 | 0.00 | 0.00 | 0.00 | 0.179121E+10 | 0.00 |
Maximum of Months | 0.133141E+11 | 0.911205E+10 | 0.123431E+11 | 0.00 | 0.517649E+10 | 0.00 | 0.00 | 0.137323E+11 | 0.00 | 0.00 | 0.00 | 0.199671E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 12322726.38 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 4782076.62 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 14093822.17 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 9567649.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40766274.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 14093822.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 14246.30 | 26-JAN-09:09 | 6958.21 | 01-JAN-06:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 1928.47 | 07-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 13347.70 | 07-FEB-08:09 | 6958.21 | 01-FEB-06:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 1928.47 | 02-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 14250.11 | 15-MAR-08:09 | 6958.21 | 01-MAR-06:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 1987.73 | 14-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 12738.33 | 12-APR-07:10 | 6958.21 | 01-APR-05:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4166.32 | 13-APR-11:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 12702.52 | 06-MAY-07:10 | 6958.21 | 01-MAY-05:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4296.60 | 22-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 13988.95 | 15-JUN-07:10 | 6958.21 | 01-JUN-05:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 4392.92 | 08-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 11661.81 | 05-JUL-07:10 | 6958.21 | 01-JUL-05:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 4721.98 | 27-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 12738.69 | 28-AUG-07:10 | 6958.21 | 01-AUG-05:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 4504.15 | 16-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 14003.70 | 27-SEP-07:10 | 6958.21 | 01-SEP-05:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 4434.72 | 18-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 14243.03 | 23-OCT-08:09 | 6958.21 | 01-OCT-05:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4336.08 | 03-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 13978.40 | 29-NOV-16:00 | 6958.21 | 01-NOV-05:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4083.00 | 03-NOV-11:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 14271.69 | 29-DEC-09:09 | 6958.21 | 01-DEC-06:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 2781.74 | 08-DEC-14:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 11661.81 | 6958.21 | 10112.62 | 0.00 | 1928.47 | 0.00 | 0.00 | |||||
Maximum of Months | 14271.69 | 6958.21 | 10112.62 | 0.00 | 4721.98 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 8321.84 | 02-JAN-14:39 | 0.00 | 0.00 | 0.00 | 1741.21 | 18-JAN-12:09 | 0.00 |
February | 8437.39 | 11-FEB-14:20 | 0.00 | 0.00 | 0.00 | 1740.47 | 03-FEB-12:39 | 0.00 |
March | 9050.89 | 27-MAR-15:30 | 0.00 | 0.00 | 0.00 | 1735.29 | 01-MAR-12:00 | 0.00 |
April | 12065.77 | 15-APR-15:00 | 0.00 | 0.00 | 0.00 | 1725.00 | 01-APR-11:00 | 0.00 |
May | 13231.04 | 22-MAY-15:50 | 0.00 | 0.00 | 0.00 | 1713.47 | 01-MAY-11:39 | 0.00 |
June | 13867.20 | 08-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1702.88 | 01-JUN-11:39 | 0.00 |
July | 15733.88 | 27-JUL-16:10 | 0.00 | 0.00 | 0.00 | 1696.85 | 01-JUL-11:09 | 0.00 |
August | 14448.10 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1701.12 | 31-AUG-11:39 | 0.00 |
September | 14098.57 | 18-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1710.85 | 30-SEP-11:39 | 0.00 |
October | 12963.65 | 03-OCT-11:39 | 0.00 | 0.00 | 0.00 | 1722.83 | 31-OCT-11:50 | 0.00 |
November | 10441.93 | 10-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1733.24 | 30-NOV-12:20 | 0.00 |
December | 8519.95 | 08-DEC-14:20 | 0.00 | 0.00 | 0.00 | 1739.74 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8321.84 | 0.00 | 0.00 | 0.00 | 1696.85 | 0.00 | ||
Maximum of Months | 15733.88 | 0.00 | 0.00 | 0.00 | 1741.21 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 32436.63 | 03-JAN-15:30 | 12416.30 | 10112.62 | 0.00 | 0.00 | 1629.10 | 0.00 | 0.00 | 6566.81 | 0.00 |
February | 32126.63 | 11-FEB-16:40 | 11014.32 | 10112.62 | 0.00 | 0.00 | 1629.10 | 0.00 | 0.00 | 7781.98 | 0.00 |
March | 31430.55 | 09-MAR-16:00 | 11014.32 | 10112.62 | 0.00 | 0.00 | 1629.10 | 0.00 | 0.00 | 7087.55 | 0.00 |
April | 36091.14 | 15-APR-15:39 | 8453.87 | 10112.62 | 0.00 | 0.00 | 4061.39 | 0.00 | 0.00 | 11879.82 | 0.00 |
May | 36874.60 | 31-MAY-14:30 | 8252.11 | 10112.62 | 0.00 | 0.00 | 4168.18 | 0.00 | 0.00 | 12661.84 | 0.00 |
June | 39507.43 | 09-JUN-15:50 | 9861.04 | 10112.62 | 0.00 | 0.00 | 4366.67 | 0.00 | 0.00 | 13588.51 | 0.00 |
July | 39439.65 | 27-JUL-15:00 | 7394.06 | 10112.62 | 0.00 | 0.00 | 4675.86 | 0.00 | 0.00 | 15679.86 | 0.00 |
August | 38550.49 | 22-AUG-12:50 | 8328.62 | 10112.62 | 0.00 | 0.00 | 4385.24 | 0.00 | 0.00 | 14047.41 | 0.00 |
September | 38119.52 | 20-SEP-14:09 | 8261.50 | 10112.62 | 0.00 | 0.00 | 4344.67 | 0.00 | 0.00 | 13717.18 | 0.00 |
October | 37020.05 | 25-OCT-14:39 | 10515.69 | 10112.62 | 0.00 | 0.00 | 4019.22 | 0.00 | 0.00 | 10677.96 | 0.00 |
November | 36959.32 | 07-NOV-14:00 | 12427.68 | 10112.62 | 0.00 | 0.00 | 3935.49 | 0.00 | 0.00 | 8809.91 | 0.00 |
December | 35363.69 | 06-DEC-15:50 | 14132.82 | 10112.62 | 0.00 | 0.00 | 1629.10 | 0.00 | 0.00 | 7781.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 31430.55 | 7394.06 | 10112.62 | 0.00 | 0.00 | 1629.10 | 0.00 | 0.00 | 6566.81 | 0.00 | |
Maximum of Months | 39507.43 | 14132.82 | 10112.62 | 0.00 | 0.00 | 4675.86 | 0.00 | 0.00 | 15679.86 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 4800.20 | 25-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 4262.95 | 04-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 4761.15 | 16-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 4733.48 | 15-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 4800.20 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 30.04 | 0.00 | 30.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 29.98 | 0.00 | 29.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.81 | 0.83 | 26.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.53 | 0.83 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.73 | 1.00 | 26.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.50 | 1.17 | 27.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.65 | 1.00 | 25.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.67 | 27.43 | 4.83 | 27.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 30.04 | 1.17 | 30.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.28 | 0.00 | 27.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.31 | 0.00 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.41 | 0.00 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 27.38 | 0.00 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 27.39 | 1.17 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 27.47 | 1.67 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 27.41 | 0.67 | 27.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 27.46 | 0.67 | 27.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 27.39 | 0.00 | 27.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.31 | 0.00 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.36 | 0.00 | 27.36 |
Annual Sum or Average | 0.00 | 0.00 | 174.50 | 27.42 | 4.17 | 27.41 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 27.47 | 1.67 | 27.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 87.50 | 23.76 | 174.50 | 23.97 | 23.33 | 24.06 |
February | 73.83 | 23.92 | 200.00 | 24.03 | 28.83 | 24.10 |
March | 82.00 | 24.22 | 239.83 | 24.19 | 36.50 | 24.33 |
April | 36.83 | 26.14 | 298.50 | 24.50 | 36.83 | 24.66 |
May | 68.17 | 25.94 | 312.00 | 24.64 | 68.17 | 24.84 |
June | 85.17 | 25.71 | 312.00 | 24.67 | 85.17 | 24.86 |
July | 80.67 | 25.73 | 300.00 | 24.68 | 80.67 | 24.86 |
August | 91.00 | 25.65 | 324.00 | 24.67 | 91.00 | 24.84 |
September | 80.17 | 25.72 | 300.00 | 24.67 | 80.17 | 24.85 |
October | 72.00 | 25.78 | 300.00 | 24.64 | 72.00 | 24.83 |
November | 64.33 | 25.24 | 273.33 | 24.44 | 58.67 | 24.60 |
December | 73.50 | 23.95 | 191.33 | 24.11 | 27.17 | 24.22 |
Annual Sum or Average | 895.17 | 25.09 | 3225.50 | 24.47 | 688.50 | 24.64 |
Minimum of Months | 36.83 | 23.76 | 174.50 | 23.97 | 23.33 | 24.06 |
Maximum of Months | 91.00 | 26.14 | 324.00 | 24.68 | 91.00 | 24.86 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 179.83 | 25.07 | 223.00 | 25.60 | 121.67 | 25.73 |
February | 195.83 | 25.48 | 226.33 | 25.82 | 157.50 | 25.90 |
March | 237.00 | 25.87 | 272.67 | 26.15 | 197.50 | 26.26 |
April | 267.83 | 26.67 | 300.00 | 26.64 | 267.83 | 26.65 |
May | 310.33 | 26.70 | 312.00 | 26.70 | 310.33 | 26.70 |
June | 312.00 | 26.72 | 312.00 | 26.72 | 312.00 | 26.72 |
July | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
August | 323.50 | 26.72 | 324.00 | 26.72 | 323.50 | 26.72 |
September | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
October | 294.83 | 26.71 | 300.00 | 26.71 | 294.83 | 26.71 |
November | 245.67 | 26.48 | 278.67 | 26.51 | 237.67 | 26.54 |
December | 194.33 | 25.44 | 235.67 | 25.78 | 147.50 | 25.91 |
Annual Sum or Average | 3161.17 | 26.38 | 3384.33 | 26.46 | 2970.33 | 26.51 |
Minimum of Months | 179.83 | 25.07 | 223.00 | 25.60 | 121.67 | 25.73 |
Maximum of Months | 323.50 | 26.72 | 324.00 | 26.72 | 323.50 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 184.67 | 24.73 | 192.00 | 25.30 | 106.00 | 25.46 |
February | 192.33 | 24.62 | 221.83 | 25.13 | 146.33 | 25.17 |
March | 239.17 | 26.01 | 253.00 | 26.29 | 190.50 | 26.44 |
April | 293.67 | 28.68 | 300.00 | 28.66 | 293.67 | 28.67 |
May | 312.00 | 29.46 | 312.00 | 29.46 | 312.00 | 29.46 |
June | 312.00 | 29.83 | 312.00 | 29.83 | 312.00 | 29.83 |
July | 300.00 | 30.56 | 300.00 | 30.56 | 300.00 | 30.56 |
August | 324.00 | 30.23 | 324.00 | 30.23 | 324.00 | 30.23 |
September | 300.00 | 30.02 | 300.00 | 30.02 | 300.00 | 30.02 |
October | 300.00 | 29.47 | 300.00 | 29.47 | 300.00 | 29.47 |
November | 244.00 | 28.24 | 282.00 | 28.10 | 241.17 | 28.16 |
December | 222.67 | 26.15 | 222.50 | 26.46 | 162.67 | 26.68 |
Annual Sum or Average | 3224.50 | 28.52 | 3319.33 | 28.59 | 2988.33 | 28.71 |
Minimum of Months | 184.67 | 24.62 | 192.00 | 25.13 | 106.00 | 25.17 |
Maximum of Months | 324.00 | 30.56 | 324.00 | 30.56 | 324.00 | 30.56 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.522905E+10 | 0.121935E+10 | 236.43 | 0.388097E+10 | 0.134808E+10 | 0.00 | 1.00 | 02-JAN-08:62 | 0.00 | 01-JAN-00:10 | 28453.47 | 07-JAN-08:62 | 16927.56 | 13-JAN-08:62 | 13285.44 | 07-JAN-08:04 | 5923.22 | 07-JAN-08:62 | 0.00 | 01-JAN-00:10 |
February | 0.580702E+10 | 0.135174E+10 | 224.79 | 0.436271E+10 | 0.144431E+10 | 0.00 | 1.00 | 02-FEB-08:62 | 0.00 | 01-FEB-00:10 | 28471.63 | 02-FEB-08:62 | 18423.73 | 16-FEB-08:62 | 13267.86 | 02-FEB-08:62 | 5950.78 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.755919E+10 | 0.173186E+10 | 267.18 | 0.551277E+10 | 0.204642E+10 | 0.00 | 1.00 | 03-MAR-08:62 | 0.00 | 01-MAR-00:10 | 29689.46 | 06-MAR-07:03 | 19075.36 | 03-MAR-08:62 | 15551.08 | 14-MAR-07:02 | 6071.63 | 06-MAR-07:03 | 0.00 | 01-MAR-00:10 |
April | 0.968164E+10 | 0.222640E+10 | 267.24 | 0.713622E+10 | 0.254542E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 29584.50 | 13-APR-06:02 | 22083.30 | 20-APR-07:03 | 13606.78 | 13-APR-06:03 | 6088.91 | 13-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.128460E+11 | 0.298147E+10 | 285.36 | 0.887509E+10 | 0.397093E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 30327.56 | 30-MAY-06:01 | 19934.24 | 08-MAY-06:02 | 16415.83 | 27-MAY-06:03 | 6167.10 | 31-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.143173E+11 | 0.331395E+10 | 287.32 | 0.929302E+10 | 0.502432E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 30182.19 | 22-JUN-06:02 | 17630.46 | 17-JUN-06:01 | 15687.59 | 19-JUN-06:04 | 6262.04 | 08-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.147647E+11 | 0.350079E+10 | 287.12 | 0.976158E+10 | 0.500311E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:05 | 29884.42 | 24-JUL-06:01 | 17599.91 | 22-JUL-06:01 | 14764.37 | 27-JUL-07:02 | 6225.21 | 14-JUL-06:01 | 0.00 | 01-JUL-00:05 |
August | 0.156317E+11 | 0.366314E+10 | 303.79 | 0.101586E+11 | 0.547308E+10 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 30327.56 | 14-AUG-06:01 | 17910.07 | 30-AUG-06:01 | 15886.10 | 28-AUG-06:04 | 6248.81 | 11-AUG-06:01 | 0.00 | 01-AUG-00:10 |
September | 0.139867E+11 | 0.325167E+10 | 284.46 | 0.916451E+10 | 0.482216E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:10 | 30195.58 | 20-SEP-06:01 | 17145.31 | 06-SEP-06:02 | 15401.11 | 22-SEP-06:06 | 6242.98 | 22-SEP-06:01 | 0.00 | 01-SEP-00:10 |
October | 0.124765E+11 | 0.287836E+10 | 276.58 | 0.845158E+10 | 0.402491E+10 | 0.00 | 1.00 | 02-OCT-05:03 | 0.00 | 01-OCT-00:10 | 30076.69 | 05-OCT-06:02 | 21085.50 | 18-OCT-06:01 | 17271.66 | 04-OCT-06:06 | 6205.62 | 02-OCT-06:01 | 0.00 | 01-OCT-00:10 |
November | 0.944615E+10 | 0.215269E+10 | 251.90 | 0.644273E+10 | 0.300342E+10 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 29898.68 | 24-NOV-07:02 | 18418.86 | 07-NOV-07:03 | 16680.42 | 30-NOV-07:04 | 6174.75 | 04-NOV-06:01 | 0.00 | 01-NOV-00:10 |
December | 0.601357E+10 | 0.138831E+10 | 245.40 | 0.440806E+10 | 0.160551E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 29703.11 | 09-DEC-07:02 | 20516.37 | 02-DEC-07:02 | 15011.62 | 23-DEC-08:62 | 6097.02 | 09-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.127759E+12 | 0.296597E+11 | 3217.57 | 0.874478E+11 | 0.403117E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.522905E+10 | 0.121935E+10 | 224.79 | 0.388097E+10 | 0.134808E+10 | 0.00 | 1.00 | 0.00 | 28453.47 | 16927.56 | 13267.86 | 5923.22 | 0.00 | |||||||
Maximum of Months | 0.156317E+11 | 0.366314E+10 | 303.79 | 0.101586E+11 | 0.547308E+10 | 0.00 | 1.00 | 0.00 | 30327.56 | 22083.30 | 17271.66 | 6262.04 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.242669E+10 | 0.599940E+09 | 90.75 | 0.147508E+10 | 0.951610E+09 | 0.00 | 0.92 | 01-JAN-15:00 | 0.00 | 01-JAN-00:10 | 34039.03 | 01-JAN-15:00 | 22180.20 | 01-JAN-15:00 | 11858.83 | 01-JAN-15:00 | 7679.32 | 01-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.425109E+10 | 0.105852E+10 | 146.17 | 0.294333E+10 | 0.130776E+10 | 0.00 | 1.00 | 19-FEB-13:00 | 0.00 | 01-FEB-00:10 | 50864.40 | 19-FEB-14:15 | 32889.54 | 19-FEB-14:55 | 19868.85 | 19-FEB-13:35 | 11420.77 | 19-FEB-14:55 | 0.00 | 01-FEB-00:10 |
March | 0.805934E+10 | 0.195799E+10 | 191.10 | 0.512083E+10 | 0.293851E+10 | 0.00 | 1.00 | 05-MAR-11:30 | 0.00 | 01-MAR-00:10 | 64093.36 | 27-MAR-17:10 | 42928.26 | 28-MAR-17:10 | 25461.49 | 05-MAR-11:30 | 14299.50 | 27-MAR-17:10 | 0.00 | 01-MAR-00:10 |
April | 0.180943E+11 | 0.439280E+10 | 303.41 | 0.122846E+11 | 0.580965E+10 | 0.00 | 1.00 | 01-APR-17:08 | 0.00 | 01-APR-00:10 | 75524.50 | 13-APR-17:06 | 59953.56 | 09-APR-16:03 | 27641.35 | 01-APR-17:08 | 17279.51 | 15-APR-17:06 | 0.00 | 01-APR-00:10 |
May | 0.300720E+11 | 0.727550E+10 | 400.97 | 0.191084E+11 | 0.109636E+11 | 0.00 | 1.00 | 01-MAY-17:10 | 0.00 | 01-MAY-00:10 | 82250.55 | 30-MAY-06:01 | 56187.73 | 02-MAY-17:08 | 42356.96 | 31-MAY-06:01 | 17990.53 | 29-MAY-12:03 | 0.00 | 01-MAY-00:10 |
June | 0.369344E+11 | 0.885774E+10 | 461.61 | 0.221189E+11 | 0.148155E+11 | 0.00 | 1.00 | 01-JUN-00:23 | 0.00 | 01-JUN-00:10 | 83585.52 | 07-JUN-06:01 | 54005.43 | 11-JUN-13:53 | 44729.78 | 07-JUN-06:01 | 17748.94 | 07-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.421784E+11 | 0.102315E+11 | 491.84 | 0.261568E+11 | 0.160216E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:10 | 80398.56 | 03-JUL-06:01 | 53292.67 | 16-JUL-14:02 | 37107.68 | 03-JUL-06:01 | 18010.27 | 27-JUL-17:06 | 0.00 | 01-JUL-00:05 |
August | 0.402125E+11 | 0.967489E+10 | 490.08 | 0.240101E+11 | 0.162024E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:15 | 79911.32 | 15-AUG-06:01 | 52460.65 | 06-AUG-14:23 | 42058.25 | 14-AUG-06:01 | 18026.40 | 20-AUG-11:43 | 0.00 | 01-AUG-00:10 |
September | 0.366690E+11 | 0.881979E+10 | 454.09 | 0.221235E+11 | 0.145454E+11 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:15 | 80016.63 | 25-SEP-06:01 | 53819.07 | 04-SEP-12:33 | 35234.50 | 25-SEP-06:01 | 17839.67 | 18-SEP-17:43 | 0.00 | 01-SEP-00:10 |
October | 0.274081E+11 | 0.661381E+10 | 380.97 | 0.168689E+11 | 0.105392E+11 | 0.00 | 1.00 | 01-OCT-10:35 | 0.00 | 01-OCT-00:15 | 83960.73 | 03-OCT-06:01 | 55329.82 | 15-OCT-16:13 | 50328.57 | 03-OCT-06:01 | 17845.82 | 29-OCT-11:23 | 0.00 | 01-OCT-00:10 |
November | 0.135671E+11 | 0.327050E+10 | 244.90 | 0.799537E+10 | 0.557169E+10 | 0.00 | 1.00 | 01-NOV-17:12 | 0.00 | 01-NOV-00:10 | 63834.97 | 04-NOV-06:01 | 34693.89 | 03-NOV-17:10 | 36902.26 | 04-NOV-06:01 | 13738.82 | 03-NOV-17:10 | 0.00 | 01-NOV-00:10 |
December | 0.527617E+10 | 0.127870E+10 | 121.02 | 0.330722E+10 | 0.196895E+10 | 0.00 | 1.00 | 03-DEC-13:25 | 0.00 | 01-DEC-00:10 | 51399.46 | 10-DEC-11:35 | 31860.34 | 10-DEC-16:15 | 23554.96 | 10-DEC-11:35 | 11388.77 | 10-DEC-11:35 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.265149E+12 | 0.640317E+11 | 3776.91 | 0.163513E+12 | 0.101636E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.242669E+10 | 0.599940E+09 | 90.75 | 0.147508E+10 | 0.951610E+09 | 0.00 | 0.92 | 0.00 | 34039.03 | 22180.20 | 11858.83 | 7679.32 | 0.00 | |||||||
Maximum of Months | 0.421784E+11 | 0.102315E+11 | 491.84 | 0.261568E+11 | 0.162024E+11 | 0.00 | 1.00 | 0.00 | 83960.73 | 59953.56 | 50328.57 | 18026.40 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.51 | 26.65 | 34.86 | 84.90 | 66.97 | 0.00 | 0.00 | 0.00 |
February | 76.78 | 34.86 | 41.91 | 118.32 | 55.52 | 0.00 | 0.00 | 0.00 |
March | 95.57 | 43.72 | 51.85 | 146.95 | 48.65 | 0.00 | 0.00 | 0.00 |
April | 104.67 | 48.35 | 56.32 | 172.49 | 38.20 | 0.00 | 0.00 | 0.00 |
May | 95.85 | 37.00 | 58.84 | 170.41 | 24.44 | 0.00 | 0.00 | 0.00 |
June | 81.16 | 22.81 | 58.36 | 150.40 | 14.85 | 0.00 | 0.00 | 0.00 |
July | 90.64 | 28.09 | 62.54 | 173.04 | 19.05 | 0.00 | 0.00 | 0.00 |
August | 90.36 | 29.40 | 60.96 | 165.83 | 17.02 | 0.00 | 0.00 | 0.00 |
September | 77.05 | 22.74 | 54.31 | 144.10 | 20.26 | 0.00 | 0.00 | 0.00 |
October | 76.62 | 29.88 | 46.74 | 134.77 | 29.82 | 0.00 | 0.00 | 0.00 |
November | 63.14 | 23.10 | 40.04 | 101.69 | 42.40 | 0.00 | 0.00 | 0.00 |
December | 63.47 | 28.44 | 35.03 | 92.67 | 58.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.44 | 31.25 | 50.19 | 138.08 | 36.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.51 | 22.74 | 34.86 | 84.90 | 14.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.67 | 48.35 | 62.54 | 173.04 | 66.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.51 | 26.65 | 34.86 | 84.90 | 66.97 | 0.00 | 0.00 | 0.00 |
February | 76.78 | 34.86 | 41.91 | 118.32 | 55.52 | 0.00 | 0.00 | 0.00 |
March | 95.57 | 43.72 | 51.85 | 146.95 | 48.65 | 0.00 | 0.00 | 0.00 |
April | 104.67 | 48.35 | 56.32 | 172.49 | 38.20 | 0.00 | 0.00 | 0.00 |
May | 95.85 | 37.00 | 58.84 | 170.41 | 24.44 | 0.00 | 0.00 | 0.00 |
June | 81.16 | 22.81 | 58.36 | 150.40 | 14.85 | 0.00 | 0.00 | 0.00 |
July | 90.64 | 28.09 | 62.54 | 173.04 | 19.05 | 0.00 | 0.00 | 0.00 |
August | 90.36 | 29.40 | 60.96 | 165.83 | 17.02 | 0.00 | 0.00 | 0.00 |
September | 77.05 | 22.74 | 54.31 | 144.10 | 20.26 | 0.00 | 0.00 | 0.00 |
October | 76.62 | 29.88 | 46.74 | 134.77 | 29.82 | 0.00 | 0.00 | 0.00 |
November | 63.14 | 23.10 | 40.04 | 101.69 | 42.40 | 0.00 | 0.00 | 0.00 |
December | 63.47 | 28.44 | 35.03 | 92.67 | 58.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.44 | 31.25 | 50.19 | 138.08 | 36.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.51 | 22.74 | 34.86 | 84.90 | 14.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.67 | 48.35 | 62.54 | 173.04 | 66.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.50 | 0.00 | 16.50 | 15.59 | 40.18 | 0.00 | 0.00 | 0.00 |
February | 19.53 | 0.00 | 19.53 | 23.99 | 32.93 | 0.00 | 0.00 | 0.00 |
March | 23.30 | 0.00 | 23.30 | 28.54 | 29.02 | 0.00 | 0.00 | 0.00 |
April | 26.16 | 0.15 | 26.02 | 38.49 | 22.31 | 0.00 | 0.00 | 0.00 |
May | 29.70 | 1.19 | 28.50 | 52.81 | 13.75 | 0.00 | 0.00 | 0.00 |
June | 31.79 | 2.22 | 29.57 | 60.41 | 7.98 | 0.00 | 0.00 | 0.00 |
July | 32.15 | 1.49 | 30.66 | 64.04 | 10.76 | 0.00 | 0.00 | 0.00 |
August | 28.61 | 0.32 | 28.28 | 53.58 | 9.67 | 0.00 | 0.00 | 0.00 |
September | 25.31 | 0.01 | 25.30 | 48.35 | 11.63 | 0.00 | 0.00 | 0.00 |
October | 21.19 | 0.00 | 21.19 | 36.32 | 17.30 | 0.00 | 0.00 | 0.00 |
November | 18.43 | 0.00 | 18.43 | 25.83 | 24.81 | 0.00 | 0.00 | 0.00 |
December | 16.32 | 0.00 | 16.32 | 17.30 | 35.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.11 | 0.45 | 23.66 | 38.84 | 21.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.32 | 0.00 | 16.32 | 15.59 | 7.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.15 | 2.22 | 30.66 | 64.04 | 40.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.50 | 0.00 | 16.50 | 15.59 | 40.18 | 0.00 | 0.00 | 0.00 |
February | 19.53 | 0.00 | 19.53 | 23.99 | 32.93 | 0.00 | 0.00 | 0.00 |
March | 23.30 | 0.00 | 23.30 | 28.54 | 29.02 | 0.00 | 0.00 | 0.00 |
April | 26.16 | 0.15 | 26.02 | 38.48 | 22.30 | 0.00 | 0.00 | 0.00 |
May | 29.70 | 1.19 | 28.50 | 52.81 | 13.75 | 0.00 | 0.00 | 0.00 |
June | 31.79 | 2.22 | 29.57 | 60.41 | 7.98 | 0.00 | 0.00 | 0.00 |
July | 32.15 | 1.49 | 30.65 | 64.04 | 10.76 | 0.00 | 0.00 | 0.00 |
August | 28.60 | 0.32 | 28.28 | 53.57 | 9.67 | 0.00 | 0.00 | 0.00 |
September | 25.31 | 0.01 | 25.30 | 48.35 | 11.63 | 0.00 | 0.00 | 0.00 |
October | 21.19 | 0.00 | 21.19 | 36.32 | 17.30 | 0.00 | 0.00 | 0.00 |
November | 18.43 | 0.00 | 18.43 | 25.83 | 24.81 | 0.00 | 0.00 | 0.00 |
December | 16.32 | 0.00 | 16.32 | 17.30 | 35.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.11 | 0.45 | 23.65 | 38.84 | 21.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.32 | 0.00 | 16.32 | 15.59 | 7.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.15 | 2.22 | 30.65 | 64.04 | 40.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 104.41 | 37.03 | 13.00 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 132.56 | 31.88 | 2.00 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 165.44 | 28.81 | 2.00 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 198.45 | 25.02 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 200.91 | 17.69 | 1.67 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 193.50 | 13.28 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 213.73 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 188.66 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 169.97 | 15.77 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 144.62 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 111.89 | 27.37 | 3.67 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.38 | 31.92 | 20.83 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 160.26 | 23.35 | 43.17 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.38 | 13.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 213.73 | 37.03 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.62 | 51.63 | 33.99 | 106.13 | 36.56 | 28.50 | 0.00 | 0.00 |
February | 104.67 | 63.68 | 40.98 | 135.32 | 30.29 | 11.17 | 0.00 | 0.00 |
March | 130.51 | 79.43 | 51.08 | 167.53 | 28.33 | 3.33 | 0.00 | 0.00 |
April | 151.97 | 94.31 | 57.66 | 196.29 | 28.61 | 0.00 | 0.00 | 0.00 |
May | 150.09 | 84.34 | 65.75 | 197.02 | 22.51 | 0.00 | 0.00 | 0.00 |
June | 142.71 | 71.21 | 71.50 | 188.33 | 19.18 | 0.00 | 0.00 | 0.00 |
July | 155.41 | 81.32 | 74.09 | 207.43 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 141.33 | 69.87 | 71.45 | 182.40 | 20.91 | 0.33 | 0.00 | 0.00 |
September | 124.57 | 60.60 | 63.96 | 164.88 | 22.15 | 0.00 | 0.00 | 0.00 |
October | 109.55 | 61.17 | 48.38 | 140.57 | 28.77 | 2.33 | 0.00 | 0.00 |
November | 87.47 | 45.49 | 41.98 | 110.70 | 30.73 | 16.50 | 0.00 | 0.00 |
December | 78.49 | 43.15 | 35.34 | 97.80 | 33.31 | 26.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.95 | 67.20 | 54.75 | 157.97 | 26.87 | 88.50 | 0.00 | 0.00 |
Minimum of Months | 78.49 | 43.15 | 33.99 | 97.80 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.41 | 94.31 | 74.09 | 207.43 | 36.56 | 28.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164749E+09 | 71392666.40 | 93356002.58 | 0.227400E+09 | 0.179364E+09 |
February | 0.185738E+09 | 84338084.82 | 0.101400E+09 | 0.286230E+09 | 0.134302E+09 |
March | 0.255964E+09 | 0.117096E+09 | 0.138868E+09 | 0.393587E+09 | 0.130308E+09 |
April | 0.271300E+09 | 0.125316E+09 | 0.145984E+09 | 0.447081E+09 | 99023224.66 |
May | 0.256714E+09 | 99106069.09 | 0.157608E+09 | 0.456423E+09 | 65458562.27 |
June | 0.210375E+09 | 59111613.78 | 0.151263E+09 | 0.389838E+09 | 38492363.90 |
July | 0.242760E+09 | 75242658.89 | 0.167517E+09 | 0.463477E+09 | 51010884.18 |
August | 0.242021E+09 | 78738705.95 | 0.163282E+09 | 0.444165E+09 | 45596143.91 |
September | 0.199712E+09 | 58945310.18 | 0.140766E+09 | 0.373507E+09 | 52516456.84 |
October | 0.205221E+09 | 80021493.34 | 0.125200E+09 | 0.360966E+09 | 79869602.10 |
November | 0.163672E+09 | 59878912.06 | 0.103793E+09 | 0.263578E+09 | 0.109900E+09 |
December | 0.169989E+09 | 76169279.17 | 93820015.02 | 0.248220E+09 | 0.157608E+09 |
Annual Sum or Average | 0.256821E+10 | 0.985357E+09 | 0.158286E+10 | 0.435447E+10 | 0.114345E+10 |
Minimum of Months | 0.163672E+09 | 58945310.18 | 93356002.58 | 0.227400E+09 | 38492363.90 |
Maximum of Months | 0.271300E+09 | 0.125316E+09 | 0.167517E+09 | 0.463477E+09 | 0.179364E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164749E+09 | 71392666.40 | 93356002.58 | 0.227400E+09 | 0.179364E+09 |
February | 0.185738E+09 | 84338084.82 | 0.101400E+09 | 0.286230E+09 | 0.134302E+09 |
March | 0.255964E+09 | 0.117096E+09 | 0.138868E+09 | 0.393587E+09 | 0.130308E+09 |
April | 0.271300E+09 | 0.125316E+09 | 0.145984E+09 | 0.447081E+09 | 99023224.66 |
May | 0.256714E+09 | 99106069.09 | 0.157608E+09 | 0.456423E+09 | 65458562.27 |
June | 0.210375E+09 | 59111613.78 | 0.151263E+09 | 0.389838E+09 | 38492363.90 |
July | 0.242760E+09 | 75242658.89 | 0.167517E+09 | 0.463477E+09 | 51010884.18 |
August | 0.242021E+09 | 78738705.95 | 0.163282E+09 | 0.444165E+09 | 45596143.91 |
September | 0.199712E+09 | 58945310.18 | 0.140766E+09 | 0.373507E+09 | 52516456.84 |
October | 0.205221E+09 | 80021493.34 | 0.125200E+09 | 0.360966E+09 | 79869602.10 |
November | 0.163672E+09 | 59878912.06 | 0.103793E+09 | 0.263578E+09 | 0.109900E+09 |
December | 0.169989E+09 | 76169279.17 | 93820015.02 | 0.248220E+09 | 0.157608E+09 |
Annual Sum or Average | 0.256821E+10 | 0.985357E+09 | 0.158286E+10 | 0.435447E+10 | 0.114345E+10 |
Minimum of Months | 0.163672E+09 | 58945310.18 | 93356002.58 | 0.227400E+09 | 38492363.90 |
Maximum of Months | 0.271300E+09 | 0.125316E+09 | 0.167517E+09 | 0.463477E+09 | 0.179364E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44200942.80 | 0.00 | 44200942.80 | 41752194.92 | 0.107630E+09 |
February | 47255766.37 | 0.00 | 47255766.37 | 58043812.40 | 79658256.90 |
March | 62417380.03 | 4141.41 | 62413238.62 | 76448016.14 | 77720511.41 |
April | 67815532.76 | 378857.14 | 67436675.63 | 99754679.72 | 57814930.29 |
May | 79537874.93 | 3197547.58 | 76340327.35 | 0.141453E+09 | 36829090.25 |
June | 82399703.48 | 5762947.00 | 76636756.48 | 0.156588E+09 | 20691728.28 |
July | 86110223.25 | 4003386.61 | 82106836.64 | 0.171535E+09 | 28830834.15 |
August | 76616653.93 | 863217.67 | 75753436.26 | 0.143497E+09 | 25893010.94 |
September | 65602266.60 | 13154.38 | 65589112.23 | 0.125336E+09 | 30149393.25 |
October | 56766728.86 | 0.00 | 56766728.86 | 97284450.68 | 46330192.45 |
November | 47766746.87 | 0.00 | 47766746.87 | 66959779.94 | 64314437.77 |
December | 43720244.59 | 0.00 | 43720244.59 | 46334113.77 | 94562293.30 |
Annual Sum or Average | 0.760210E+09 | 14223251.78 | 0.745987E+09 | 0.122498E+10 | 0.670425E+09 |
Minimum of Months | 43720244.59 | 0.00 | 43720244.59 | 41752194.92 | 20691728.28 |
Maximum of Months | 86110223.25 | 5762947.00 | 82106836.64 | 0.171535E+09 | 0.107630E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44199655.73 | 0.00 | 44199655.73 | 41750763.20 | 0.107630E+09 |
February | 47254414.45 | 0.00 | 47254414.45 | 58042131.57 | 79657497.33 |
March | 62415613.29 | 4141.22 | 62411472.07 | 76445680.46 | 77719711.57 |
April | 67813648.65 | 378839.38 | 67434809.27 | 99752118.36 | 57814199.38 |
May | 79535459.88 | 3197397.70 | 76338062.18 | 0.141449E+09 | 36828404.64 |
June | 82397054.97 | 5762676.89 | 76634378.09 | 0.156583E+09 | 20691094.58 |
July | 86107547.34 | 4003198.96 | 82104348.38 | 0.171531E+09 | 28830120.88 |
August | 76614306.39 | 863177.21 | 75751129.18 | 0.143493E+09 | 25892320.32 |
September | 65600260.41 | 13153.76 | 65587106.65 | 0.125333E+09 | 30148707.17 |
October | 56765046.97 | 0.00 | 56765046.97 | 97282154.60 | 46329332.60 |
November | 47765281.59 | 0.00 | 47765281.59 | 66957836.27 | 64313585.67 |
December | 43718921.59 | 0.00 | 43718921.59 | 46332473.98 | 94561588.71 |
Annual Sum or Average | 0.760187E+09 | 14222585.12 | 0.745965E+09 | 0.122495E+10 | 0.670416E+09 |
Minimum of Months | 43718921.59 | 0.00 | 43718921.59 | 41750763.20 | 20691094.58 |
Maximum of Months | 86107547.34 | 5762676.89 | 82104348.38 | 0.171531E+09 | 0.107630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.279661E+09 | 99170275.06 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.320689E+09 | 77118924.30 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.443126E+09 | 77154459.47 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.514394E+09 | 64846996.44 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.538120E+09 | 47393513.89 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.501541E+09 | 34432480.67 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.572447E+09 | 40599370.35 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.505317E+09 | 38392859.90 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.440567E+09 | 40884058.10 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.387362E+09 | 60019471.04 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.290013E+09 | 70937881.95 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.260819E+09 | 85496178.62 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.505406E+10 | 0.736446E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.260819E+09 | 34432480.67 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.572447E+09 | 99170275.06 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229329E+09 | 0.138292E+09 | 91036785.71 | 0.284246E+09 | 97909890.56 |
February | 0.253217E+09 | 0.154066E+09 | 99150350.95 | 0.327364E+09 | 73287865.11 |
March | 0.349552E+09 | 0.212749E+09 | 0.136803E+09 | 0.448710E+09 | 75883242.03 |
April | 0.393913E+09 | 0.244453E+09 | 0.149460E+09 | 0.508796E+09 | 74163961.92 |
May | 0.402009E+09 | 0.225903E+09 | 0.176106E+09 | 0.527687E+09 | 60283713.93 |
June | 0.369909E+09 | 0.184579E+09 | 0.185329E+09 | 0.488145E+09 | 49714283.39 |
July | 0.416249E+09 | 0.217806E+09 | 0.198442E+09 | 0.555576E+09 | 56759566.67 |
August | 0.378527E+09 | 0.187146E+09 | 0.191381E+09 | 0.488547E+09 | 56006691.19 |
September | 0.322877E+09 | 0.157086E+09 | 0.165791E+09 | 0.427375E+09 | 57412720.19 |
October | 0.293418E+09 | 0.163833E+09 | 0.129584E+09 | 0.376493E+09 | 77069630.63 |
November | 0.226717E+09 | 0.117899E+09 | 0.108818E+09 | 0.286940E+09 | 79656756.60 |
December | 0.210228E+09 | 0.115561E+09 | 94666689.08 | 0.261952E+09 | 89224211.00 |
Annual Sum or Average | 0.384594E+10 | 0.211938E+10 | 0.172657E+10 | 0.498183E+10 | 0.847373E+09 |
Minimum of Months | 0.210228E+09 | 0.115561E+09 | 91036785.71 | 0.261952E+09 | 49714283.39 |
Maximum of Months | 0.416249E+09 | 0.244453E+09 | 0.198442E+09 | 0.555576E+09 | 97909890.56 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 198.86 | 212.18 | 156.03 | 53.31 | 102.72 | 0.00 | 0.00 |
February | 283.57 | 175.84 | 192.62 | 69.72 | 122.90 | 0.00 | 0.00 |
March | 349.46 | 153.81 | 237.74 | 87.44 | 150.30 | 0.00 | 0.00 |
April | 421.06 | 120.13 | 261.66 | 96.99 | 164.68 | 0.00 | 0.00 |
May | 445.77 | 75.71 | 251.08 | 76.39 | 174.69 | 0.00 | 0.00 |
June | 420.68 | 44.72 | 225.91 | 50.06 | 175.85 | 0.00 | 0.00 |
July | 473.69 | 59.13 | 245.57 | 59.17 | 186.40 | 0.00 | 0.00 |
August | 438.64 | 53.20 | 237.93 | 59.44 | 178.49 | 0.00 | 0.00 |
September | 384.85 | 63.73 | 204.72 | 45.49 | 159.22 | 0.00 | 0.00 |
October | 341.98 | 94.03 | 195.63 | 59.75 | 135.88 | 0.00 | 0.00 |
November | 254.63 | 134.01 | 163.15 | 46.20 | 116.94 | 0.00 | 0.00 |
December | 218.24 | 186.59 | 159.58 | 56.88 | 102.70 | 0.00 | 0.00 |
Annual Sum or Average | 352.99 | 114.18 | 211.09 | 63.39 | 147.69 | 0.00 | 0.00 |
Minimum of Months | 198.86 | 44.72 | 156.03 | 45.49 | 102.70 | 0.00 | 0.00 |
Maximum of Months | 473.69 | 212.18 | 261.66 | 96.99 | 186.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1461.79 | 518.36 | 1198.70 | 722.85 | 475.85 | 0.00 | 0.00 |
February | 1855.84 | 446.29 | 1465.37 | 891.59 | 573.79 | 0.00 | 0.00 |
March | 2316.22 | 403.29 | 1827.11 | 1112.04 | 715.07 | 0.00 | 0.00 |
April | 2778.36 | 350.25 | 2127.61 | 1320.35 | 807.27 | 0.00 | 0.00 |
May | 2812.76 | 247.73 | 2101.30 | 1180.80 | 920.51 | 0.00 | 0.00 |
June | 2708.94 | 185.98 | 1997.96 | 996.96 | 1001.01 | 0.00 | 0.00 |
July | 2992.18 | 212.21 | 2175.73 | 1138.47 | 1037.26 | 0.00 | 0.00 |
August | 2641.29 | 200.68 | 1978.56 | 978.21 | 1000.35 | 0.00 | 0.00 |
September | 2379.61 | 220.82 | 1743.94 | 848.46 | 895.48 | 0.00 | 0.00 |
October | 2024.74 | 313.72 | 1533.69 | 856.36 | 677.34 | 0.00 | 0.00 |
November | 1566.43 | 383.15 | 1224.55 | 636.80 | 587.75 | 0.00 | 0.00 |
December | 1363.30 | 446.89 | 1098.86 | 604.04 | 494.82 | 0.00 | 0.00 |
Annual Sum or Average | 2243.68 | 326.94 | 1707.36 | 940.87 | 766.49 | 0.00 | 0.00 |
Minimum of Months | 1363.30 | 185.98 | 1098.86 | 604.04 | 475.85 | 0.00 | 0.00 |
Maximum of Months | 2992.18 | 518.36 | 2175.73 | 1320.35 | 1037.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13270.40 | 3867.69 | 2739.89 | 1652.23 | 1087.66 | 0.00 | 0.00 |
February | 17072.75 | 3109.11 | 3349.43 | 2037.91 | 1311.51 | 0.00 | 0.00 |
March | 21818.51 | 2994.94 | 4176.25 | 2541.81 | 1634.45 | 0.00 | 0.00 |
April | 29154.27 | 3065.69 | 4863.12 | 3017.94 | 1845.18 | 0.00 | 0.00 |
May | 32547.95 | 2786.11 | 4802.98 | 2698.96 | 2104.02 | 0.00 | 0.00 |
June | 33658.70 | 2997.07 | 4566.78 | 2278.76 | 2288.02 | 0.00 | 0.00 |
July | 39692.56 | 3614.95 | 4973.10 | 2602.23 | 2370.88 | 0.00 | 0.00 |
August | 33335.22 | 3528.05 | 4522.43 | 2235.91 | 2286.51 | 0.00 | 0.00 |
September | 30799.44 | 3448.93 | 3986.14 | 1939.34 | 2046.80 | 0.00 | 0.00 |
October | 23318.72 | 3764.74 | 3505.59 | 1957.39 | 1548.20 | 0.00 | 0.00 |
November | 15830.07 | 3296.37 | 2798.98 | 1455.54 | 1343.43 | 0.00 | 0.00 |
December | 12729.75 | 3519.60 | 2511.69 | 1380.66 | 1131.02 | 0.00 | 0.00 |
Annual Sum or Average | 25313.47 | 3336.04 | 3902.53 | 2150.56 | 1751.97 | 0.00 | 0.00 |
Minimum of Months | 12729.75 | 2786.11 | 2511.69 | 1380.66 | 1087.66 | 0.00 | 0.00 |
Maximum of Months | 39692.56 | 3867.69 | 4973.10 | 3017.94 | 2370.88 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.532621E+09 | 0.568306E+09 | 0.417898E+09 | 0.142785E+09 | 0.275113E+09 | 0.00 | 0.00 |
February | 0.686023E+09 | 0.425397E+09 | 0.465986E+09 | 0.168676E+09 | 0.297310E+09 | 0.00 | 0.00 |
March | 0.935981E+09 | 0.411969E+09 | 0.636761E+09 | 0.234200E+09 | 0.402561E+09 | 0.00 | 0.00 |
April | 0.109138E+10 | 0.311386E+09 | 0.678229E+09 | 0.251390E+09 | 0.426839E+09 | 0.00 | 0.00 |
May | 0.119395E+10 | 0.202774E+09 | 0.672501E+09 | 0.204607E+09 | 0.467894E+09 | 0.00 | 0.00 |
June | 0.109039E+10 | 0.115910E+09 | 0.585547E+09 | 0.129749E+09 | 0.455798E+09 | 0.00 | 0.00 |
July | 0.126872E+10 | 0.158386E+09 | 0.657737E+09 | 0.158492E+09 | 0.499246E+09 | 0.00 | 0.00 |
August | 0.117484E+10 | 0.142501E+09 | 0.637272E+09 | 0.159204E+09 | 0.478068E+09 | 0.00 | 0.00 |
September | 0.997536E+09 | 0.165185E+09 | 0.530626E+09 | 0.117917E+09 | 0.412709E+09 | 0.00 | 0.00 |
October | 0.915958E+09 | 0.251858E+09 | 0.523975E+09 | 0.160043E+09 | 0.363932E+09 | 0.00 | 0.00 |
November | 0.659993E+09 | 0.347348E+09 | 0.422875E+09 | 0.119758E+09 | 0.303117E+09 | 0.00 | 0.00 |
December | 0.584539E+09 | 0.499772E+09 | 0.427418E+09 | 0.152339E+09 | 0.275079E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111319E+11 | 0.360079E+10 | 0.665682E+10 | 0.199916E+10 | 0.465767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.532621E+09 | 0.115910E+09 | 0.417898E+09 | 0.117917E+09 | 0.275079E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126872E+10 | 0.568306E+09 | 0.678229E+09 | 0.251390E+09 | 0.499246E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.391525E+10 | 0.138838E+10 | 0.321060E+10 | 0.193608E+10 | 0.127451E+10 | 0.00 | 0.00 |
February | 0.448964E+10 | 0.107966E+10 | 0.354503E+10 | 0.215693E+10 | 0.138810E+10 | 0.00 | 0.00 |
March | 0.620377E+10 | 0.108016E+10 | 0.489373E+10 | 0.297849E+10 | 0.191524E+10 | 0.00 | 0.00 |
April | 0.720152E+10 | 0.907858E+09 | 0.551478E+10 | 0.342234E+10 | 0.209244E+10 | 0.00 | 0.00 |
May | 0.753369E+10 | 0.663509E+09 | 0.562813E+10 | 0.316265E+10 | 0.246549E+10 | 0.00 | 0.00 |
June | 0.702157E+10 | 0.482055E+09 | 0.517872E+10 | 0.258411E+10 | 0.259461E+10 | 0.00 | 0.00 |
July | 0.801426E+10 | 0.568391E+09 | 0.582748E+10 | 0.304929E+10 | 0.277819E+10 | 0.00 | 0.00 |
August | 0.707444E+10 | 0.537500E+09 | 0.529938E+10 | 0.262004E+10 | 0.267934E+10 | 0.00 | 0.00 |
September | 0.616794E+10 | 0.572377E+09 | 0.452028E+10 | 0.219921E+10 | 0.232107E+10 | 0.00 | 0.00 |
October | 0.542306E+10 | 0.840273E+09 | 0.410785E+10 | 0.229367E+10 | 0.181418E+10 | 0.00 | 0.00 |
November | 0.406019E+10 | 0.993130E+09 | 0.317404E+10 | 0.165059E+10 | 0.152345E+10 | 0.00 | 0.00 |
December | 0.365147E+10 | 0.119695E+10 | 0.294319E+10 | 0.161786E+10 | 0.132533E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.707568E+11 | 0.103103E+11 | 0.538432E+11 | 0.296713E+11 | 0.241720E+11 | 0.00 | 0.00 |
Minimum of Months | 0.365147E+10 | 0.482055E+09 | 0.294319E+10 | 0.161786E+10 | 0.127451E+10 | 0.00 | 0.00 |
Maximum of Months | 0.801426E+10 | 0.138838E+10 | 0.582748E+10 | 0.342234E+10 | 0.277819E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.355434E+11 | 0.103592E+11 | 0.733851E+10 | 0.442534E+10 | 0.291318E+10 | 0.00 | 0.00 |
February | 0.413024E+11 | 0.752156E+10 | 0.810293E+10 | 0.493012E+10 | 0.317281E+10 | 0.00 | 0.00 |
March | 0.584387E+11 | 0.802165E+10 | 0.111857E+11 | 0.680797E+10 | 0.437770E+10 | 0.00 | 0.00 |
April | 0.755679E+11 | 0.794626E+10 | 0.126052E+11 | 0.782250E+10 | 0.478271E+10 | 0.00 | 0.00 |
May | 0.871764E+11 | 0.746232E+10 | 0.128643E+11 | 0.722890E+10 | 0.563540E+10 | 0.00 | 0.00 |
June | 0.872434E+11 | 0.776839E+10 | 0.118371E+11 | 0.590654E+10 | 0.593054E+10 | 0.00 | 0.00 |
July | 0.106313E+12 | 0.968227E+10 | 0.133200E+11 | 0.696980E+10 | 0.635016E+10 | 0.00 | 0.00 |
August | 0.892851E+11 | 0.944952E+10 | 0.121129E+11 | 0.598867E+10 | 0.612420E+10 | 0.00 | 0.00 |
September | 0.798321E+11 | 0.893963E+10 | 0.103321E+11 | 0.502676E+10 | 0.530531E+10 | 0.00 | 0.00 |
October | 0.624569E+11 | 0.100835E+11 | 0.938936E+10 | 0.524266E+10 | 0.414670E+10 | 0.00 | 0.00 |
November | 0.410315E+11 | 0.854419E+10 | 0.725495E+10 | 0.377277E+10 | 0.348218E+10 | 0.00 | 0.00 |
December | 0.340954E+11 | 0.942691E+10 | 0.672730E+10 | 0.369797E+10 | 0.302933E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.798286E+12 | 0.105205E+12 | 0.123070E+12 | 0.678200E+11 | 0.552502E+11 | 0.00 | 0.00 |
Minimum of Months | 0.340954E+11 | 0.746232E+10 | 0.672730E+10 | 0.369797E+10 | 0.291318E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106313E+12 | 0.103592E+11 | 0.133200E+11 | 0.782250E+10 | 0.635016E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.684995E+09 | -611936438.1 | 0.00 | 0.00 | 744.00 | 0.00 | -73058723.9 | 58.99 | 0.00 | 0.00 |
February | 0.622777E+09 | -556830465.4 | 0.00 | 0.00 | 672.00 | 0.00 | -65946813.1 | 58.99 | 0.00 | 0.00 |
March | 0.702795E+09 | -630608202.3 | 0.00 | 0.00 | 744.00 | 0.00 | -72186843.8 | 58.99 | 0.00 | 0.00 |
April | 0.626861E+09 | -558835205.0 | 0.00 | 0.00 | 720.00 | 0.00 | -68025686.6 | 58.99 | 0.00 | 0.00 |
May | 0.621786E+09 | -552226104.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69560075.1 | 58.99 | 0.00 | 0.00 |
June | 0.595030E+09 | -527946480.3 | 0.00 | 0.00 | 720.00 | 0.00 | -67083598.8 | 58.99 | 0.00 | 0.00 |
July | 0.570009E+09 | -501273180.4 | 0.00 | 0.00 | 744.00 | 0.00 | -68736247.0 | 58.99 | 0.00 | 0.00 |
August | 0.614014E+09 | -544827027.4 | 0.00 | 0.00 | 744.00 | 0.00 | -69187158.2 | 58.99 | 0.00 | 0.00 |
September | 0.592738E+09 | -525947742.6 | 0.00 | 0.00 | 720.00 | 0.00 | -66790586.7 | 58.99 | 0.00 | 0.00 |
October | 0.623662E+09 | -554356919.4 | 0.00 | 0.00 | 744.00 | 0.00 | -69305194.0 | 58.99 | 0.00 | 0.00 |
November | 0.627569E+09 | -559010586.9 | 0.00 | 0.00 | 720.00 | 0.00 | -68558363.0 | 58.99 | 0.00 | 0.00 |
December | 0.675516E+09 | -603010716.0 | 0.00 | 0.00 | 744.00 | 0.00 | -72505083.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.755775E+10 | -0.672681E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -830944373.3 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.570009E+09 | -630608202.3 | 0.00 | 0.00 | 672.00 | 0.00 | -73058723.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.702795E+09 | -501273180.4 | 0.00 | 0.00 | 744.00 | 0.00 | -65946813.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.75 | 0.50 | 01-JAN-10:00 | 246.35 | 0.00 | 0.00 | 101.33 | 1002.03 | 0.00 | 0.00 | 80.00 |
February | 304.33 | 0.72 | 0.50 | 01-FEB-10:30 | 1795.09 | 0.00 | 0.00 | 128.83 | 713.09 | 0.00 | 0.00 | 88.67 |
March | 362.67 | 0.70 | 0.50 | 02-MAR-13:09 | 468.04 | 0.00 | 0.00 | 173.33 | 275.00 | 0.00 | 0.00 | 133.50 |
April | 357.50 | 0.67 | 0.50 | 01-APR-10:20 | 388.70 | 0.00 | 0.00 | 199.00 | 1150.54 | 0.00 | 0.00 | 159.17 |
May | 389.00 | 0.67 | 0.50 | 01-MAY-09:00 | 1619.76 | 0.00 | 0.00 | 234.17 | 300.61 | 0.00 | 0.00 | 166.17 |
June | 388.17 | 0.68 | 0.50 | 01-JUN-09:39 | 471.85 | 0.00 | 0.00 | 232.83 | 301.90 | 0.00 | 0.00 | 163.50 |
July | 403.83 | 0.66 | 0.50 | 01-JUL-09:09 | 992.01 | 0.00 | 0.00 | 255.67 | 325.43 | 0.00 | 0.00 | 184.17 |
August | 348.33 | 0.65 | 0.50 | 01-AUG-09:50 | 1548.80 | 0.00 | 0.00 | 248.83 | 363.42 | 0.00 | 0.00 | 191.83 |
September | 349.67 | 0.65 | 0.50 | 01-SEP-09:20 | 432.66 | 0.00 | 0.00 | 214.00 | 346.39 | 0.00 | 0.00 | 172.83 |
October | 323.50 | 0.69 | 0.50 | 02-OCT-11:39 | 340.58 | 0.00 | 0.00 | 180.50 | 394.51 | 0.00 | 0.00 | 146.00 |
November | 314.83 | 0.70 | 0.50 | 01-NOV-09:39 | 299.60 | 0.00 | 0.00 | 141.50 | 919.90 | 0.00 | 0.00 | 117.17 |
December | 282.67 | 0.71 | 0.50 | 01-DEC-10:00 | 272.56 | 0.00 | 0.00 | 109.33 | 228.41 | 0.00 | 0.00 | 75.50 |
Annual Sum or Average | 4111.50 | 0.68 | 756.87 | 0.00 | 0.00 | 2219.33 | 513.37 | 0.00 | 0.00 | 1678.50 | ||
Minimum of Months | 282.67 | 0.65 | 0.50 | 246.35 | 0.00 | 0.00 | 101.33 | 228.41 | 0.00 | 0.00 | 75.50 | |
Maximum of Months | 403.83 | 0.75 | 0.50 | 1795.09 | 0.00 | 0.00 | 255.67 | 1150.54 | 0.00 | 0.00 | 191.83 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.63 | 0.50 | 01-JAN-09:50 | 959.69 | 13.91 | 0.00 | 206.33 | 605.63 | 20.22 | 83.67 | 191.17 |
February | 304.33 | 0.61 | 0.50 | 01-FEB-08:00 | 730.31 | 14.67 | 0.00 | 214.00 | 276.01 | 18.47 | 86.00 | 180.50 |
March | 362.67 | 0.60 | 0.50 | 01-MAR-10:09 | 389.77 | 15.08 | 4.83 | 264.83 | 327.49 | 19.03 | 112.83 | 226.17 |
April | 357.50 | 0.58 | 0.50 | 01-APR-07:30 | 433.64 | 15.53 | 13.67 | 287.50 | 1565.56 | 19.45 | 122.33 | 256.17 |
May | 389.00 | 0.58 | 0.50 | 01-MAY-07:30 | 456.60 | 15.75 | 16.67 | 311.33 | 394.74 | 19.52 | 127.50 | 274.83 |
June | 388.17 | 0.59 | 0.50 | 01-JUN-07:19 | 477.83 | 15.54 | 17.83 | 296.50 | 418.19 | 19.19 | 123.33 | 273.83 |
July | 403.83 | 0.57 | 0.50 | 01-JUL-06:00 | 505.61 | 16.28 | 29.33 | 324.00 | 437.48 | 19.99 | 151.17 | 297.50 |
August | 348.33 | 0.57 | 0.50 | 01-AUG-07:30 | 809.82 | 16.24 | 33.67 | 312.00 | 674.10 | 19.99 | 137.17 | 284.00 |
September | 349.67 | 0.57 | 0.50 | 01-SEP-07:30 | 1443.93 | 16.29 | 25.50 | 282.33 | 1248.61 | 19.98 | 139.33 | 255.67 |
October | 323.50 | 0.60 | 0.50 | 02-OCT-08:09 | 389.60 | 15.39 | 1.50 | 257.50 | 323.30 | 19.23 | 116.67 | 225.17 |
November | 314.83 | 0.61 | 0.50 | 01-NOV-08:09 | 342.36 | 15.12 | 0.00 | 222.50 | 284.36 | 18.81 | 93.00 | 193.50 |
December | 282.67 | 0.61 | 0.50 | 01-DEC-08:39 | 314.97 | 14.54 | 0.00 | 208.67 | 260.80 | 18.17 | 72.83 | 176.33 |
Annual Sum or Average | 4111.50 | 0.59 | 601.04 | 15.42 | 143.00 | 3187.50 | 575.96 | 19.37 | 1365.83 | 2834.83 | ||
Minimum of Months | 282.67 | 0.57 | 0.50 | 314.97 | 13.91 | 0.00 | 206.33 | 260.80 | 18.17 | 72.83 | 176.33 | |
Maximum of Months | 403.83 | 0.63 | 0.50 | 1443.93 | 16.29 | 33.67 | 324.00 | 1565.56 | 20.22 | 151.17 | 297.50 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.91 | 0.82 | 22-JAN-15:39 | 253.15 | 22.22 | 124.50 | 24.00 | 102.60 | 19.81 | 98.50 | 0.00 |
February | 304.33 | 0.90 | 0.80 | 10-FEB-16:10 | 333.99 | 22.65 | 132.17 | 41.50 | 230.75 | 22.20 | 131.33 | 20.67 |
March | 362.67 | 0.89 | 0.80 | 01-MAR-16:10 | 370.29 | 22.78 | 158.00 | 66.83 | 307.01 | 23.46 | 175.33 | 50.00 |
April | 357.50 | 0.89 | 0.80 | 01-APR-16:10 | 237.68 | 20.72 | 132.17 | 41.33 | 219.16 | 21.94 | 168.00 | 47.83 |
May | 389.00 | 0.89 | 0.80 | 01-MAY-15:09 | 238.49 | 20.12 | 119.83 | 42.33 | 194.22 | 21.44 | 173.67 | 41.17 |
June | 388.17 | 0.89 | 0.80 | 01-JUN-14:09 | 234.57 | 19.41 | 104.33 | 48.33 | 171.93 | 20.70 | 158.33 | 28.17 |
July | 403.83 | 0.88 | 0.80 | 01-JUL-15:09 | 258.65 | 20.29 | 139.17 | 64.83 | 193.91 | 21.53 | 196.83 | 42.33 |
August | 348.33 | 0.88 | 0.80 | 01-AUG-16:19 | 262.81 | 20.68 | 146.67 | 64.67 | 198.56 | 21.83 | 193.17 | 43.83 |
September | 349.67 | 0.89 | 0.80 | 01-SEP-14:39 | 260.05 | 21.31 | 146.67 | 54.67 | 176.92 | 22.05 | 182.33 | 28.67 |
October | 323.50 | 0.89 | 0.80 | 02-OCT-15:09 | 282.23 | 23.24 | 166.50 | 62.50 | 199.55 | 23.66 | 179.67 | 25.00 |
November | 314.83 | 0.90 | 0.80 | 01-NOV-16:10 | 217.25 | 22.42 | 148.83 | 29.00 | 129.39 | 21.78 | 143.67 | 7.00 |
December | 282.67 | 0.90 | 0.82 | 05-DEC-15:09 | 236.34 | 23.30 | 136.17 | 27.67 | 114.81 | 20.87 | 113.50 | 0.00 |
Annual Sum or Average | 4111.50 | 0.89 | 265.31 | 21.48 | 1655.00 | 567.67 | 189.40 | 21.79 | 1914.33 | 334.67 | ||
Minimum of Months | 282.67 | 0.88 | 0.80 | 217.25 | 19.41 | 104.33 | 24.00 | 102.60 | 19.81 | 98.50 | 0.00 | |
Maximum of Months | 403.83 | 0.91 | 0.82 | 370.29 | 23.30 | 166.50 | 66.83 | 307.01 | 23.66 | 196.83 | 50.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8400612.38 | 13842.12 | 25-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3291773.68 | 8846.19 | 04-FEB-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9587540.16 | 13715.40 | 16-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6481456.78 | 13625.79 | 15-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27761383.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9587540.16 | 13842.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.522905E+10 | 0.388097E+10 | 28453.47 | 07-JAN-08:62 | 15183.34 | 0.00 |
February | 0.00 | 0.00 | 0.580702E+10 | 0.436271E+10 | 28471.63 | 02-FEB-08:62 | 15203.76 | 0.00 |
March | 0.00 | 0.00 | 0.755919E+10 | 0.551277E+10 | 29689.46 | 06-MAR-07:03 | 14789.99 | 0.00 |
April | 0.00 | 0.00 | 0.968164E+10 | 0.713622E+10 | 29584.50 | 13-APR-06:02 | 16073.43 | 0.00 |
May | 0.00 | 0.00 | 0.128460E+11 | 0.887509E+10 | 30327.56 | 30-MAY-06:01 | 15439.92 | 0.00 |
June | 0.00 | 0.00 | 0.143173E+11 | 0.929302E+10 | 30182.19 | 22-JUN-06:02 | 15089.37 | 0.00 |
July | 0.00 | 0.00 | 0.147647E+11 | 0.976158E+10 | 29884.42 | 24-JUL-06:01 | 16143.82 | 0.00 |
August | 0.00 | 0.00 | 0.156317E+11 | 0.101586E+11 | 30327.56 | 14-AUG-06:01 | 14896.28 | 0.00 |
September | 0.00 | 0.00 | 0.139867E+11 | 0.916451E+10 | 30195.58 | 20-SEP-06:01 | 15201.59 | 0.00 |
October | 0.00 | 0.00 | 0.124765E+11 | 0.845158E+10 | 30076.69 | 05-OCT-06:02 | 15241.52 | 0.00 |
November | 0.00 | 0.00 | 0.944615E+10 | 0.644273E+10 | 29898.68 | 24-NOV-07:02 | 14839.53 | 0.00 |
December | 0.00 | 0.00 | 0.601357E+10 | 0.440806E+10 | 29703.11 | 09-DEC-07:02 | 15719.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.127759E+12 | 0.874478E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.522905E+10 | 0.388097E+10 | 28453.47 | 14789.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.156317E+11 | 0.101586E+11 | 30327.56 | 16143.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.242669E+10 | 0.147508E+10 | 34039.03 | 01-JAN-15:00 | 22180.20 | 0.00 |
February | 0.00 | 0.00 | 0.425109E+10 | 0.294333E+10 | 50864.40 | 19-FEB-14:15 | 31618.03 | 0.00 |
March | 0.00 | 0.00 | 0.805934E+10 | 0.512083E+10 | 64093.36 | 27-MAR-17:10 | 42074.43 | 0.00 |
April | 0.00 | 0.00 | 0.180943E+11 | 0.122846E+11 | 75524.50 | 13-APR-17:06 | 48587.27 | 0.00 |
May | 0.00 | 0.00 | 0.300720E+11 | 0.191084E+11 | 82250.55 | 30-MAY-06:01 | 41762.81 | 0.00 |
June | 0.00 | 0.00 | 0.369344E+11 | 0.221189E+11 | 83585.52 | 07-JUN-06:01 | 38855.74 | 0.00 |
July | 0.00 | 0.00 | 0.421784E+11 | 0.261568E+11 | 80398.56 | 03-JUL-06:01 | 43290.88 | 0.00 |
August | 0.00 | 0.00 | 0.402125E+11 | 0.240101E+11 | 79911.32 | 15-AUG-06:01 | 43180.35 | 0.00 |
September | 0.00 | 0.00 | 0.366690E+11 | 0.221235E+11 | 80016.63 | 25-SEP-06:01 | 44782.13 | 0.00 |
October | 0.00 | 0.00 | 0.274081E+11 | 0.168689E+11 | 83960.73 | 03-OCT-06:01 | 33632.16 | 0.00 |
November | 0.00 | 0.00 | 0.135671E+11 | 0.799537E+10 | 63834.97 | 04-NOV-06:01 | 26932.71 | 0.00 |
December | 0.00 | 0.00 | 0.527617E+10 | 0.330722E+10 | 51399.46 | 10-DEC-11:35 | 27844.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.265149E+12 | 0.163513E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.242669E+10 | 0.147508E+10 | 34039.03 | 22180.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.421784E+11 | 0.261568E+11 | 83960.73 | 48587.27 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.495584E+09 | 0.20 | 1247.39 | 02-JAN-08:62 | 0.89 |
February | 0.456066E+09 | 0.21 | 1247.39 | 02-FEB-08:62 | 0.89 |
March | 0.538499E+09 | 0.22 | 1247.39 | 03-MAR-08:62 | 0.90 |
April | 0.512729E+09 | 0.21 | 1247.39 | 01-APR-06:02 | 0.89 |
May | 0.583842E+09 | 0.23 | 1247.39 | 01-MAY-07:02 | 0.89 |
June | 0.630798E+09 | 0.25 | 1247.39 | 01-JUN-06:01 | 0.89 |
July | 0.665710E+09 | 0.25 | 1247.39 | 01-JUL-06:01 | 0.89 |
August | 0.700902E+09 | 0.26 | 1247.39 | 01-AUG-06:01 | 0.89 |
September | 0.620079E+09 | 0.25 | 1247.39 | 01-SEP-06:01 | 0.89 |
October | 0.563965E+09 | 0.22 | 1247.39 | 02-OCT-06:01 | 0.89 |
November | 0.488197E+09 | 0.20 | 1247.39 | 01-NOV-07:03 | 0.89 |
December | 0.497346E+09 | 0.20 | 1247.39 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.675372E+10 | 0.22 | |||
Minimum of Months | 0.456066E+09 | 0.20 | 1247.39 | 0.89 | |
Maximum of Months | 0.700902E+09 | 0.26 | 1247.39 | 0.90 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112332E+10 | 0.20 | 1130.14 | 02-JAN-16:50 | 0.52 |
February | 0.104249E+10 | 0.21 | 1726.01 | 19-FEB-14:55 | 0.68 |
March | 0.123466E+10 | 0.22 | 2316.50 | 27-MAR-17:10 | 0.79 |
April | 0.122665E+10 | 0.25 | 2825.35 | 09-APR-12:43 | 0.87 |
May | 0.139024E+10 | 0.29 | 2825.35 | 02-MAY-17:08 | 0.87 |
June | 0.149288E+10 | 0.35 | 2825.35 | 03-JUN-17:08 | 0.87 |
July | 0.157280E+10 | 0.36 | 2825.35 | 01-JUL-17:06 | 0.87 |
August | 0.158958E+10 | 0.36 | 2825.35 | 01-AUG-06:01 | 0.86 |
September | 0.147501E+10 | 0.35 | 2825.35 | 01-SEP-06:01 | 0.86 |
October | 0.132314E+10 | 0.28 | 2825.35 | 03-OCT-06:01 | 0.86 |
November | 0.112100E+10 | 0.21 | 2104.65 | 03-NOV-17:10 | 0.75 |
December | 0.113823E+10 | 0.20 | 1642.00 | 10-DEC-11:35 | 0.66 |
Annual Sum or Average | 0.157300E+11 | 0.27 | |||
Minimum of Months | 0.104249E+10 | 0.20 | 1130.14 | 0.52 | |
Maximum of Months | 0.158958E+10 | 0.36 | 2825.35 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.171493E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.180781E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.227036E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.273913E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.356531E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.394475E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.416650E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.436404E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.387175E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.344232E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.264089E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.188565E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.364134E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.171493E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.436404E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.172326E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.210101E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.319265E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.561944E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.866575E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.103506E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.118043E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.112645E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.102948E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.793696E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.439149E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.241693E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.797617E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.172326E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.118043E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.495584E+09 | 0.522905E+10 | 8400612.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.456066E+09 | 0.580702E+10 | 3291773.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.538499E+09 | 0.755919E+10 | 9587540.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.512729E+09 | 0.968164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.583842E+09 | 0.128460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.630798E+09 | 0.143173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.665710E+09 | 0.147647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.700902E+09 | 0.156317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.620079E+09 | 0.139867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.563965E+09 | 0.124765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.488197E+09 | 0.944615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.497346E+09 | 0.601357E+10 | 6481456.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.675372E+10 | 0.127759E+12 | 27761383.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.456066E+09 | 0.522905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.700902E+09 | 0.156317E+11 | 9587540.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.112332E+10 | 0.242669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104249E+10 | 0.425109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123466E+10 | 0.805934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122665E+10 | 0.180943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139024E+10 | 0.300720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149288E+10 | 0.369344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157280E+10 | 0.421784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158958E+10 | 0.402125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147501E+10 | 0.366690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132314E+10 | 0.274081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112100E+10 | 0.135671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113823E+10 | 0.527617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157300E+11 | 0.265149E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104249E+10 | 0.242669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158958E+10 | 0.421784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.495584E+09 | 0.00 | 0.00 | 0.00 | 0.121935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.456066E+09 | 0.00 | 0.00 | 0.00 | 0.135174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.538499E+09 | 0.00 | 0.00 | 0.00 | 0.173186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.512729E+09 | 0.00 | 0.00 | 0.00 | 0.222640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.583842E+09 | 0.00 | 0.00 | 0.00 | 0.298147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.630798E+09 | 0.00 | 0.00 | 0.00 | 0.331395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.665710E+09 | 0.00 | 0.00 | 0.00 | 0.350079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.700902E+09 | 0.00 | 0.00 | 0.00 | 0.366314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.620079E+09 | 0.00 | 0.00 | 0.00 | 0.325167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.563965E+09 | 0.00 | 0.00 | 0.00 | 0.287836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.488197E+09 | 0.00 | 0.00 | 0.00 | 0.215269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.497346E+09 | 0.00 | 0.00 | 0.00 | 0.138831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.675372E+10 | 0.00 | 0.00 | 0.00 | 0.296597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.456066E+09 | 0.00 | 0.00 | 0.00 | 0.121935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.700902E+09 | 0.00 | 0.00 | 0.00 | 0.366314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.112332E+10 | 0.00 | 0.00 | 0.00 | 0.599940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104249E+10 | 0.00 | 0.00 | 0.00 | 0.105852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123466E+10 | 0.00 | 0.00 | 0.00 | 0.195799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122665E+10 | 0.00 | 0.00 | 0.00 | 0.439280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139024E+10 | 0.00 | 0.00 | 0.00 | 0.727550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149288E+10 | 0.00 | 0.00 | 0.00 | 0.885774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157280E+10 | 0.00 | 0.00 | 0.00 | 0.102315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158958E+10 | 0.00 | 0.00 | 0.00 | 0.967489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147501E+10 | 0.00 | 0.00 | 0.00 | 0.881979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132314E+10 | 0.00 | 0.00 | 0.00 | 0.661381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112100E+10 | 0.00 | 0.00 | 0.00 | 0.327050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113823E+10 | 0.00 | 0.00 | 0.00 | 0.127870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157300E+11 | 0.00 | 0.00 | 0.00 | 0.640317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104249E+10 | 0.00 | 0.00 | 0.00 | 0.599940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158958E+10 | 0.00 | 0.00 | 0.00 | 0.102315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136125E+09 | 0.427044E+09 | 0.00 | 2277469.25 | 82472.00 | 4342504.57 | 0.285952E+09 | 0.00 | 0.14 |
February | 86437685.61 | 0.500850E+09 | 0.00 | 1885021.81 | 161166.14 | 556937.89 | 0.126238E+09 | 0.00 | 0.14 |
March | 0.109457E+09 | 0.697554E+09 | 0.00 | 2305523.54 | 376188.51 | 4288269.25 | 0.199181E+09 | 0.00 | 0.15 |
April | 14286978.45 | 0.110055E+10 | 0.00 | 1839557.82 | 1340308.11 | 0.00 | 38581928.62 | 0.00 | 0.14 |
May | 800412.85 | 0.185843E+10 | 0.00 | 1112893.49 | 2910161.71 | 0.00 | 2392114.01 | 0.00 | 0.14 |
June | 5227.23 | 0.244510E+10 | 0.00 | 418003.07 | 6850446.97 | 0.00 | 40480.09 | 0.00 | 0.15 |
July | 0.00 | 0.272902E+10 | 0.00 | 30271.37 | 9873504.03 | 0.00 | 0.00 | 0.00 | 0.14 |
August | 0.00 | 0.277430E+10 | 0.00 | 221253.89 | 9406825.95 | 0.00 | 9629.73 | 0.00 | 0.15 |
September | 90321.30 | 0.243305E+10 | 0.00 | 473310.25 | 5392910.09 | 0.00 | 446344.11 | 0.00 | 0.14 |
October | 816223.64 | 0.191802E+10 | 0.00 | 658238.82 | 3956726.29 | 0.00 | 2743746.05 | 0.00 | 0.14 |
November | 27654462.40 | 0.131184E+10 | 0.00 | 1312142.21 | 1418528.61 | 0.00 | 26233346.77 | 0.00 | 0.14 |
December | 0.105061E+09 | 0.548291E+09 | 0.00 | 2616080.62 | 591315.89 | 2622323.16 | 0.265831E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.480735E+09 | 0.187441E+11 | 0.00 | 15149766.13 | 42360554.30 | 11810034.87 | 0.947649E+09 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.427044E+09 | 0.00 | 30271.37 | 82472.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.136125E+09 | 0.277430E+10 | 0.00 | 2616080.62 | 9873504.03 | 4342504.57 | 0.285952E+09 | 0.00 | 0.15 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.256227E+10 | 0.176166E+09 | 0.00 | 1048015.81 | 9745009.74 | 0.00 | 0.395412E+09 | 0.00 | 0.20 |
February | 0.111423E+10 | 0.229926E+09 | 0.00 | 3027140.14 | 274749.36 | 0.00 | 0.641503E+09 | 0.00 | 0.20 |
March | 0.152743E+10 | 0.605737E+09 | 0.00 | 2852960.97 | 0.00 | 0.00 | 0.674781E+09 | 0.00 | 0.22 |
April | 0.241639E+09 | 0.205765E+10 | 0.00 | 3722544.50 | 931482.17 | 0.00 | 0.454159E+09 | 0.00 | 0.22 |
May | 23562381.33 | 0.494264E+10 | 0.00 | 946597.68 | 3063416.83 | 0.00 | 57670966.48 | 0.00 | 0.23 |
June | 375255.83 | 0.821378E+10 | 0.00 | 199596.19 | 14161477.31 | 0.00 | 8817539.68 | 0.00 | 0.25 |
July | 0.00 | 0.103742E+11 | 0.00 | 0.00 | 13604031.57 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.954889E+10 | 0.00 | 272199.66 | 21943234.73 | 0.00 | 24563092.53 | 0.00 | 0.25 |
September | 615500.21 | 0.816996E+10 | 0.00 | 174641.67 | 12633173.11 | 0.00 | 13049439.81 | 0.00 | 0.24 |
October | 21752729.46 | 0.513884E+10 | 0.00 | 838734.57 | 8978425.88 | 0.00 | 85960960.41 | 0.00 | 0.22 |
November | 0.404184E+09 | 0.232202E+10 | 0.00 | 1283535.74 | 2834109.15 | 0.00 | 0.310301E+09 | 0.00 | 0.20 |
December | 0.212443E+10 | 0.557409E+09 | 0.00 | 1740887.21 | 1531446.78 | 0.00 | 0.454545E+09 | 0.00 | 0.20 |
Annual Sum or Average | 0.802049E+10 | 0.523372E+11 | 0.00 | 16106854.13 | 89700556.64 | 0.00 | 0.312076E+10 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.176166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.256227E+10 | 0.103742E+11 | 0.00 | 3722544.50 | 21943234.73 | 0.00 | 0.674781E+09 | 0.00 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:52
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.418010E+12 | 0.286373E+11 | 0.00 | 0.938110E+10 | 0.947895E+10 |
February | 0.455302E+12 | 0.272780E+11 | 0.00 | 0.592729E+10 | 0.124699E+11 |
March | 0.629159E+12 | 0.343446E+11 | 0.00 | 0.501815E+10 | 0.193129E+11 |
April | 0.691095E+12 | 0.301949E+11 | 0.00 | -919135770.5 | 0.343951E+11 |
May | 0.675399E+12 | 0.248786E+11 | 0.00 | -0.892236E+10 | 0.531750E+11 |
June | 0.617074E+12 | 0.268818E+11 | 0.00 | -0.166550E+11 | 0.634234E+11 |
July | 0.676762E+12 | 0.293094E+11 | 0.00 | -0.203828E+11 | 0.706754E+11 |
August | 0.707665E+12 | 0.284214E+11 | 0.00 | -0.192181E+11 | 0.691822E+11 |
September | 0.557439E+12 | 0.260794E+11 | 0.00 | -0.164324E+11 | 0.627271E+11 |
October | 0.533294E+12 | 0.245857E+11 | 0.00 | -0.108438E+11 | 0.493768E+11 |
November | 0.397766E+12 | 0.266288E+11 | 0.00 | -848253530.3 | 0.284364E+11 |
December | 0.412358E+12 | 0.313493E+11 | 0.00 | 0.675788E+10 | 0.139598E+11 |
Annual Sum or Average | 0.677133E+13 | 0.338589E+12 | 0.00 | -0.671374E+11 | 0.486613E+12 |
Minimum of Months | 0.397766E+12 | 0.245857E+11 | 0.00 | -0.203828E+11 | 0.947895E+10 |
Maximum of Months | 0.707665E+12 | 0.343446E+11 | 0.00 | 0.938110E+10 | 0.706754E+11 |