Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 10:44:01
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 539.69 | 111.62 | 111.62 |
Net Site Energy | 539.69 | 111.62 | 111.62 |
Total Source Energy | 1358.71 | 281.01 | 281.01 |
Net Source Energy | 1358.71 | 281.01 | 281.01 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 168.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 108.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 371.43 | 168.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 168.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 2.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 108.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 23.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 168.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 108.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 23.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 37.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.59 | 34.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 76.82 | 34.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 37.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.59 | 34.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 76.82 | 34.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 371.428 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 371.428 | 100.00 |
Total On-Site and Utility Electric Sources | 371.428 | 100.00 |
Total Electricity End Uses | 371.428 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 14.50 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2704.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 7.6766 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.3906 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5498 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5498 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 7.6766 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.3906 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.5498 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.5498 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.5498 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-JAN-16:40 | 10-JAN-17:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 94944.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9388.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2151.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1616.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28761.62 | 94944.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 94944.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9388.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2151.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1616.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 182.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 342.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 230.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 73.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 82.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1176.31 | 182.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 37.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 70.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 243.28 | 37.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 37.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 70.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 243.28 | 37.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.934349 |
ZONE2 FINE STORAGE DIRECT AIR | 1.71 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.03 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.03 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 41778.82 |
PSZ-OFFICE HEATING COIL | 24339.36 |
PSZ-FINE STORAGE HEATING COIL | 59988.75 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 41778.82 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.934349 | 0.934349 | 0.934349 | 0.934349 | 0.934349 | 0.934349 | 1.00 | 1.00 | 0.934349 |
PSZ-FINE STORAGE | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.00 | 1.00 | 1.71 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.934349 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.71 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.934349 | 1034.47 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.71 | 1824.51 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.934349 | 0.934349 | 0.934349 | 0.934349 | 15466.79 | 24339.36 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.71 | 1.71 | 1.71 | 1.13 | 32873.55 | 59988.75 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.934350 | 0.467174 | 0.622900 | 15466.79 | 7733.40 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 1.71 | 0.852539 | 1.14 | 32873.55 | 16436.78 | 0.790670 | 0.790670 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 7.677 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.750 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.391 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.949 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1818.427 | 7.677 | 142.636 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1818.427 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10866.415 | 3.391 | 157.484 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10866.415 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1413 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5841E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.5469E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.998 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.04 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.21 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
2 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
3 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
4 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
5 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
6 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
7 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
8 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
9 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
10 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
11 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
12 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
13 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
14 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
15 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
16 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.30042996E-08 | -0.19492532E-14 | 0.18571942E-14 | -0.50265421E-16 |
55 | 6 | 0.40686135E-05 | 0.27025218E-08 | 0.31944093E-02 | -0.26797382E-04 |
56 | 5 | -0.28598357E-03 | 0.15982348E-05 | -0.22398257 | 0.19584275E-02 |
57 | 4 | 0.65354345E-02 | 0.72696005E-04 | 4.8338424 | -0.45306284E-01 |
58 | 3 | -0.57256805E-01 | 0.57768437E-03 | -38.045688 | 0.39892203 |
59 | 2 | 0.20312160 | 0.96045137E-03 | 116.53119 | -1.4185711 |
60 | 1 | -0.29305691 | 0.29236276E-03 | -143.93511 | 2.0494970 |
61 | 0 | 0.14285049 | 0.70905046E-05 | 60.838472 | |
62 | 7 | -0.73310212E-08 | 0.16277859E-15 | -0.15558641E-14 | 0.17403554E-16 |
63 | 6 | 0.21213446E-05 | 0.11327280E-08 | 0.32008460E-02 | -0.26851379E-04 |
64 | 5 | -0.12816801E-03 | 0.66411688E-06 | -0.22434819 | 0.19616548E-02 |
65 | 4 | 0.27852559E-02 | 0.30072908E-04 | 4.8399282 | -0.45364789E-01 |
66 | 3 | -0.23934818E-01 | 0.23808113E-03 | -38.080046 | 0.39930184 |
67 | 2 | 0.84241938E-01 | 0.39442809E-03 | 116.59803 | -1.4194653 |
68 | 1 | -0.12110434 | 0.11951395E-03 | -143.97445 | 2.0501436 |
69 | 0 | 0.58923671E-01 | 0.28881054E-05 | 60.838472 | |
70 | 7 | -0.78336681E-08 | 0.23380828E-15 | -0.37470831E-14 | 0.17001158E-16 |
71 | 6 | 0.20573783E-05 | 0.10635783E-08 | 0.32011355E-02 | -0.26853807E-04 |
72 | 5 | -0.12166809E-03 | 0.62270931E-06 | -0.22436462 | 0.19617998E-02 |
73 | 4 | 0.26229018E-02 | 0.28177105E-04 | 4.8402013 | -0.45367414E-01 |
74 | 3 | -0.22467346E-01 | 0.22293819E-03 | -38.081586 | 0.39931887 |
75 | 2 | 0.78971204E-01 | 0.36912476E-03 | 116.60102 | -1.4195054 |
76 | 1 | -0.11345740 | 0.11176675E-03 | -143.97621 | 2.0501725 |
77 | 0 | 0.55185584E-01 | 0.26976542E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20666597E-14 | 0.96147816E-16 | 0.79647225E-12 | 0.11382549E-15 |
85 | 3 | -0.56581374E-04 | 0.28930881E-06 | -0.38972706E-03 | 0.15282143E-12 |
86 | 2 | 1.1494565 | 0.62914578E-02 | 1.7513786 | -0.74717338E-04 |
87 | 1 | -17.155584 | 0.16244765 | -7.1131205 | 0.33567575 |
88 | 0 | 16.278262 | 0.10333854 | 5.6342095 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3818_SHGC_SOUTH_0.38 | 34 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.381 | ||
2 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.38 | 35 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.381 | ||
3 | NONRESWINDOW_U_0.3818_SHGC_EAST_0.38 | 36 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.381 | ||
4 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.381 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.6 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.44070E-002 | 0.29373 | 0.49835 | 0.49835 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.44070E-002 | 0.29373 | 0.49835 | 0.49835 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.44070E-002 | 0.29373 | 0.49835 | 0.49835 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.44070E-002 | 0.29373 | 0.49835 | 0.49835 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.056 | 0.5354 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.099 | 0.605 | 0.602 |
2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.605 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4929E-004 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6970E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2995E-004 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9663E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2585E-004 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1017E-003 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5727E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2026E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.7842E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.9658E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3055E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4669E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5411E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.4095E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7631E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3735E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8699E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6509E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.8790E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9501E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4045E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9853E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2192E-003 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2548E-004 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7941E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5988E-004 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.7269E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7464E-004 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5928E-003 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2306E-004 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0518E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7651E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4230E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1445E-004 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4920E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2160E-004 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2897E-003 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7684E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3050E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9351E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6824E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.4163E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2032E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7704E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3867E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8078E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9123E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6423E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4487E-003 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0358E-004 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7475E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1004E-004 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.0099E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9453E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8041E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6567E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4280E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4118E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6999E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5664E-004 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6438E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0184E-004 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7108E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9807E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2078E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4956E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0385E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9243E-004 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5647E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3823E-004 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3923E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9389E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4487E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0730E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8210E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4479E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2249E-003 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6547E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4880E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3403E-004 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5062E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2546E-003 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8644E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5247E-003 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2635E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0728E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2548E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9448E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6412E-004 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2500E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4119E-004 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5685E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3705E-004 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1679E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7670E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2140E-003 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0721E-004 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4304E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8156E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3386E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.6506E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.7454E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0952E-004 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8074E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0362E-004 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0233E-003 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5452E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3375E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4249E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6646E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0607E-004 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9054E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6756E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5564E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8934E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.0263E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6747E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3652E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6204E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6978E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1243E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6955E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6980E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6849E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0402E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5275E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1603E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7987E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5272E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3448E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8217E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1686E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8608E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4353E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6179E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6280E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9923E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4408E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4746E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8261E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9203E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5376E-004 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2840E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8788E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0977E-004 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1407E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1414E-004 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2994E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0045E-004 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3661E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6674E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8401E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4626E-004 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1947E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6116E-004 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2010E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1063E-004 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1658E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6649E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6333E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6582E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9631E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6894E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3995E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1738E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8108E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2818E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6078E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5604E-004 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0796E-003 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5720E-004 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3067E-003 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6679E-004 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5185E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0481E-004 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5886E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0199E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9786E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8791E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4864E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8710E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1988E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2532E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5335E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7057E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0981E-004 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0427E-003 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1189E-004 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5084E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0742E-004 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2519E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1885E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0599E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5223E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2006E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4470E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8785E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6708E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0473E-004 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9439E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3896E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2524E-004 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5589E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2189E-004 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4175E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4263E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8908E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8211E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0751E-003 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6299E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1533E-003 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9221E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2722E-003 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5211E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8995E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7855E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6029E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7180E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6119E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5409E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0805E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1000E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8972E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3063E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0782E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8963E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9820E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1624E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7081E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8540E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9000E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0465E-003 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6549E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6945E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4622E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4352E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8093E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2122E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9915E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5702E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4898E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2581E-004 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4486E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1671E-004 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2733E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5872E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4291E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2389E-004 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3009E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8459E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2252E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5066E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0700E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0781E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4336E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8360E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3114E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1741E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0735E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1321E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3552E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2753E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9975E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9790E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1173E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4511E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8564E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1605E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9781E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9026E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9750E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5670E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0263E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2302E-003 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7396E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0441E-003 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6564E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8114E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9810E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9042E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9414E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1001E-004 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6472E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8929E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3758E-003 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3587E-004 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3923E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2355E-004 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6853E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1603E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3255E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5958E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2753E-003 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4113E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3968E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7651E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4567E-004 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8375E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2270E-004 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8793E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5079E-004 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2357E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8771E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0145E-003 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0090E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3527E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2206E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9598E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2581E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7687E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6872E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7148E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0076E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4493E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6385E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0132E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1764E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1847E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1582E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5852E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4367E-004 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0772E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2320E-004 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8036E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6518E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3481E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8744E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2992E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6244E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9373E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2032E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5559E-004 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3993E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6000E-004 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0363E-004 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5247E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7577E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2720E-004 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4180E-004 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0647E-004 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4346E-004 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1651E-004 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2024E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5078E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3607E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6831E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0955E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4545E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9207E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8157E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0355E-004 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9366E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9469E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7583E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2040E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8040E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5027E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6053E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6788E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7598E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7254E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7931E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4025E-004 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1134E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4882E-004 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6900E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2011E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1450E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.3800E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.4203E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.8269E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.7797E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.5934E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.4797E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7169E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.7716E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.5989E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.0175E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.1277E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.0753E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.5954E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.9782E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.7173E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.6541E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.2751E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.7694E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.9865E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9718E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.6791E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.2069E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.4076E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9067E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.5063E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.7774E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.1028E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.9761E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.4646E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2022E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.4076E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.9067E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9363.73455 | 11236.48146 | 0.77862 | 0.93435 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 25.24733 | 8.40527E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7673.27426 | 9207.92911 | 0.21753 | 0.26104 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30000 | 2.65759E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 21921.05776 | 26305.26932 | 1.42090 | 1.70508 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 17373.27438 | 20847.92926 | 0.41521 | 0.49826 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -4.30000 | 2.65759E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | 25.21700 | 8.40522E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 34815.68316 | 41778.81980 | 0.85981 | 1.03177 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13484.29 | 0.93435 | 0.93435 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9033.50 | 0.26104 | 0.26104 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 29852.53 | 1.70508 | 1.70508 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 24676.19 | 0.49826 | 0.49826 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93435 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.70508 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.03177 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.03177 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 41778.81662 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 41778.81980 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.93435 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.93435 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.93435 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.93435 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.93435 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.93435 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.70508 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.70508 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.70508 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.70508 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.70508 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.70508 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.93435 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.70508 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.93435 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.93435 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1034.47230 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.93435 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.93435 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.93435 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.93435 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.93435 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46717 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62290 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15466.79000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7733.39500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15466.79000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24339.36405 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 24339.36405 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.70508 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.70508 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1824.51443 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.70508 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.70508 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.70508 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.12535 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.70508 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85254 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.13672 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32873.55000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16436.77500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79067 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79067 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32873.55000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59988.74641 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 59988.74641 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 14741.8 | 12.15 | 11.88 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 31549.7 | 11.75 | 11.48 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1447236440 | 0.1574182984 | Pass | Pass | 2.1357552456 | 11.0970156415 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2947251714 | 0.2733021719 | Pass | Pass | 2.0830399528 | 7.9238876152 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.5571106545E-005 | 6.9375105803E-005 | Pass | Pass | 5.7437545035E-002 | 5.6029620701E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7308.91 | 327.39 | 0.00 | 99.64 | 59.88 | 7795.87 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.058 | 0.058 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.199 | 0.204 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.054 | 0.055 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.199 | 0.204 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.38 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.169 | 0.381 | 0.381 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.38 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.169 | 0.381 | 0.381 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.38 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.169 | 0.381 | 0.381 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.38 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.169 | 0.381 | 0.381 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 3.832 | 0.559 | 0.557 | |||||||||||||||||
North Total or Average | 6.51 | 2.169 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 79.53 | 3.968 | 0.573 | 0.571 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 7.6766 | 236.88 | 1818.43 | LightsWired | LTG_SCH_OFFICE | 49.99 | 168.00 | 45.18 | 0.0000 | Y | 15.42 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 26.10 | 0.0000 | Y | 45.64 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.3906 | 3204.84 | 10866.42 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 23.01 | 0.0000 | Y | 46.95 |
Interior Lighting Total | 4.5498 | 4835.13 | 21998.92 | 108.01 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 9314.08 | 2328.52 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 9314.08 | 2328.52 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10866.42 | 2716.60 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10866.42 | 2716.60 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1818.43 | 263.67 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.05 | 1818.43 | 90.92 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 93.17 | AstronomicalClock | - | 42.50 | 42.50 | 0.74 | |
EXTERIOR_LIGHTS_B | 5399.43 | AstronomicalClock | - | 83.54 | 71.23 | 72.19 | |
Exterior Lighting Total | 5492.60 | 72.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15466.79 | 12383.64 | 3083.15 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32873.55 | 25992.13 | 6881.42 | 0.79 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 14741.8 | 12.15 | 11.88 | ||||
PSZ-FINE STORAGE COOLING COIL | 31549.7 | 11.75 | 11.48 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 41778.82 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 24339.36 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 59988.75 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.03 | 95.86 | 92.91 | 1.00 | 4.12 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.93 | 1034.47 | 1107.16 | 1.00 | 1.42 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.71 | 1824.51 | 1070.05 | 1.00 | 1.34 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.54 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9363.73 | 11236.48 | 47.44 | 0.779 | 0.934 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 23.90 | 23.90 | 0.00833 | 25.25 | 0.00841 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 21921.06 | 26305.27 | 18.88 | 1.421 | 1.705 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00850 | 26.40 | 0.00841 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | 0.00 | 29.43 | 0.00900 | 25.22 | 0.00841 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7673.27 | 9207.93 | 38.87 | 0.218 | 0.261 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00798 | -4.30 | 0.00266 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 17373.27 | 20847.93 | 14.96 | 0.415 | 0.498 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00700 | -4.30 | 0.00266 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 34815.68 | 41778.82 | 13.04 | 0.860 | 1.032 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00562 | -4.30 | 0.00266 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.93 | 0.93 | 0.26 | 0.26 | 0.9343 | 0.9343 | 0.9343 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.71 | 1.71 | 0.50 | 0.50 | 1.7051 | 1.7051 | 1.7051 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 41778.817 | 41778.817 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 41778.82 | 41778.82 | 1.031771 | 10.00 | 7.67 | 0.00562487 | 43.33 | 22.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 10.00 | 0.00562487 | 73.1618 | 41778.82 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 15466.790 | 12383.640 | 0.934350 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 7733.40 | 7307.40 | 0.622900 | 24.97 | 16.48 | 0.00833683 | 12.00 | 11.16 | 0.00800000 | 25.37 | 0.00840546 | 16.68 | 16.4207 | 23.90 | 0.00832839 | 44.6385 | 9359.79 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 24339.364 | 24339.364 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 24339.36 | 24339.36 | 0.934349 | 18.24 | 13.12 | 0.00739616 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 10.9472 | 21.10 | 0.00797867 | 50.7215 | 7673.27 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 32873.550 | 25992.130 | 1.705080 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 16436.78 | 15355.03 | 1.136720 | 27.50 | 17.47 | 0.00847762 | 12.00 | 11.16 | 0.00800000 | 26.40 | 0.00840708 | 17.04 | 37.3629 | 26.70 | 0.00850101 | 38.5622 | 21921.06 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 59988.746 | 59988.746 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 59988.75 | 59988.75 | 1.705078 | 10.61 | 8.30 | 0.00591968 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 24.9086 | 15.56 | 0.00700175 | 63.1216 | 17373.27 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 41778.817 | 41778.817 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.031771 | 1.22922295 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 41778.82 | 41778.82 | 1.0000 | 1.22922295 | 1.031771 | 10.00 | 7.67 | 0.00562487 | 24219.4 | 43.33 | 22.02 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41778.82 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 10.00 | 0.00562487 | 10.00 | 0.00562487 | 73.1618 | 41778.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15466.790 | 12383.640 | 0.934350 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3377 | 1004.8586 | 1.1914 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.934349 | 1.11315686 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | Sensible | 7733.40 | 7307.40 | 1.0000 | 0.74210563 | 0.622900 | 24.97 | 16.48 | 0.00833683 | 46328.6 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7733.40 | 25.37 | 0.00840546 | 16.68 | 0.10228463 | 16.4207 | 23.90 | 0.00832839 | 23.90 | 0.00832839 | 44.6385 | 9359.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24339.364 | 24339.364 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.934349 | 1.11315686 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 24339.36 | 24339.36 | 1.0000 | 1.11315686 | 0.934349 | 18.24 | 13.12 | 0.00739616 | 37077.0 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24339.36 | -4.30 | 0.00265759 | -4.30 | 0.10228463 | 10.9472 | 21.01 | 0.00797867 | 21.10 | 0.00797867 | 50.7215 | 7673.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32873.550 | 25992.130 | 1.705080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5995 | 1004.8586 | 1.1914 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.705078 | 2.03138262 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 16436.78 | 15355.03 | 1.0000 | 1.35425639 | 1.136720 | 27.50 | 17.47 | 0.00847762 | 49273.2 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16436.78 | 26.40 | 0.00840708 | 17.04 | 0.42471127 | 37.3629 | 26.70 | 0.00850101 | 26.70 | 0.00850101 | 38.5622 | 21921.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59988.746 | 59988.746 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.705078 | 2.03138262 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 59988.75 | 59988.75 | 1.0000 | 2.03138262 | 1.705078 | 10.61 | 8.30 | 0.00591968 | 25584.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59988.75 | -4.30 | 0.00265759 | -4.30 | 0.42471127 | 24.9086 | 15.56 | 0.00700175 | 15.56 | 0.00700175 | 63.1216 | 17373.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.71 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2178.33 | 3232.83 | 2053.50 |
ZONE2 FINE STORAGE | 2709.00 | 3182.17 | 2359.33 |
ZONE3 BULK STORAGE | 2742.33 | 3551.50 | 2693.33 |
Facility | 3056.50 | 3562.33 | 2704.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 10.33 | 0.00 | 8.17 | 0.00 |
ZONE2 FINE STORAGE | 136.83 | 0.33 | 8.33 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 145.17 | 0.33 | 14.50 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.48 | 12.75 | 1010.76 | 0.340 | 0.385 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.30 | 30.00 | 2953.02 | 0.434 | 0.135 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.30 | 69.00 | 35277.63 | 0.000 | 0.083 | 0.000 | 0.031 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.48 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.30 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.30 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.48 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.30 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.30 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.08 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1234012.43 | 0.00 | 1234012.43 | 1841204.07 | 3075216.50 | 3225648.14 | 5423.46 | 3336.54 | 0.00 | 25.58 |
ZONE2 FINE STORAGE | 4652573.11 | 0.00 | 4652573.11 | 3862596.58 | 8515169.69 | 13393694.68 | 5729.34 | 3012.83 | 17.82 | 1.16 |
ZONE3 BULK STORAGE | 0.00 | 9256655.69 | 9256655.69 | 22204480.09 | 31461135.78 | 30805497.77 | 8693.33 | 7.17 | 59.50 | 4172.83 |
Total Facility | 5886585.55 | 9256655.69 | 15143241.24 | 27908280.74 | 43051521.97 | 47424840.58 | 8717.17 | 3339.20 | 77.32 | 4173.75 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0942 | 0.0000 | 0.0942 | 0.1068 | 0.2011 | 0.1023 | 299.46 | 3336.54 | 0.00 |
ZONE2 FINE STORAGE | 0.3553 | 0.0000 | 0.3553 | 0.1100 | 0.4652 | 0.4247 | 606.00 | 3012.83 | 17.17 |
ZONE3 BULK STORAGE | 0.0000 | 0.3089 | 0.3089 | 0.8217 | 1.1307 | 0.9768 | 3592.00 | 4.50 | 39.50 |
Total Facility | 0.4495 | 0.3089 | 0.7584 | 1.0386 | 1.7970 | 1.5038 | 3593.17 | 3336.54 | 56.67 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1751516.85 | 0.00 | 1751516.85 | 3225648.14 | 5421.76 | 0.00 | 3338.24 | 23.89 |
PSZ-FINE STORAGE | 6603629.50 | 0.00 | 6603629.50 | 13393694.68 | 5729.17 | 0.17 | 3030.66 | 1.16 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1337 | 0.0000 | 0.1337 | 0.1023 | 297.76 | 0.00 | 3338.24 |
PSZ-FINE STORAGE | 0.5042 | 0.0000 | 0.5042 | 0.4247 | 606.00 | 0.00 | 3030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3434.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 3021.99 | 9.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1426 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6044 | 0.9527 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 429 |
Defaulted Fields | 391 |
Fields with Defaults | 1171 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 371.43 | 1811.97 | 16-APR-13:50 | 28761.62 | 10-JAN-16:40 |
Electricity:Building | 247.30 | 1328.97 | 16-APR-13:50 | 20611.15 | 25-NOV-15:30 |
Electricity:Zone:ZONE1 OFFICE | 47.37 | 774.00 | 19-FEB-15:30 | 2976.64 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 247.30 | 1328.97 | 16-APR-13:50 | 20611.15 | 25-NOV-15:30 |
InteriorLights:Electricity | 108.01 | 755.22 | 16-APR-13:50 | 10498.53 | 25-NOV-15:30 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 15.42 | 200.25 | 19-FEB-15:30 | 1064.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 108.01 | 755.22 | 16-APR-13:50 | 10498.53 | 25-NOV-15:30 |
LightsWired:InteriorLights:Electricity | 108.01 | 755.22 | 16-APR-13:50 | 10498.53 | 25-NOV-15:30 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 15.42 | 200.25 | 19-FEB-15:30 | 1064.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 108.01 | 755.22 | 16-APR-13:50 | 10498.53 | 25-NOV-15:30 |
Electricity:Zone:ZONE2 FINE STORAGE | 45.64 | 256.14 | 12-FEB-12:10 | 4354.33 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 45.64 | 256.14 | 12-FEB-12:10 | 4354.33 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 45.64 | 256.14 | 12-FEB-12:10 | 4354.33 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 154.29 | 298.83 | 16-JAN-11:20 | 13280.17 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 46.95 | 298.83 | 16-JAN-11:20 | 5080.05 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 46.95 | 298.83 | 16-JAN-11:20 | 5080.05 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 23.08 | 0.00 | 04-JAN-18:10 | 2255.27 | 10-JAN-18:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 371.43 | 1811.97 | 16-APR-13:50 | 28761.62 | 10-JAN-16:40 |
ElectricityPurchased:Plant | 371.43 | 1811.97 | 16-APR-13:50 | 28761.62 | 10-JAN-16:40 |
Cogeneration:ElectricityPurchased | 371.43 | 1811.97 | 16-APR-13:50 | 28761.62 | 10-JAN-16:40 |
General:Cogeneration:ElectricityPurchased | 371.43 | 1811.97 | 16-APR-13:50 | 28761.62 | 10-JAN-16:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 371.43 | 1811.97 | 16-APR-13:50 | 28761.62 | 10-JAN-16:40 |
ElectricityNet:Plant | 371.43 | 1811.97 | 16-APR-13:50 | 28761.62 | 10-JAN-16:40 |
Cogeneration:ElectricityNet | 371.43 | 1811.97 | 16-APR-13:50 | 28761.62 | 10-JAN-16:40 |
General:Cogeneration:ElectricityNet | 371.43 | 1811.97 | 16-APR-13:50 | 28761.62 | 10-JAN-16:40 |
Electricity:HVAC | 25.15 | 0.00 | 04-JAN-18:10 | 6309.68 | 22-JUL-15:10 |
General:Fans:Electricity | 23.08 | 0.00 | 04-JAN-18:10 | 2255.27 | 10-JAN-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 2.07 | 0.00 | 01-JAN-00:10 | 4545.40 | 22-JUL-15:10 |
General:Cooling:Electricity | 2.07 | 0.00 | 01-JAN-00:10 | 4545.40 | 22-JUL-15:10 |
ExteriorLights:Electricity | 72.93 | 0.00 | 01-JAN-08:20 | 5492.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 72.93 | 0.00 | 01-JAN-08:20 | 5492.60 | 01-JAN-06:10 |
Electricity:Plant | 26.04 | 483.00 | 01-JAN-00:10 | 2416.61 | 16-FEB-12:30 |
WaterSystems:Electricity | 26.04 | 483.00 | 01-JAN-00:10 | 2416.61 | 16-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 26.04 | 483.00 | 01-JAN-00:10 | 2416.61 | 16-FEB-12:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 168.26 | 0.00 | 04-JAN-18:10 | 94944.80 | 10-JAN-18:00 |
NaturalGas:HVAC | 168.26 | 0.00 | 04-JAN-18:10 | 94944.80 | 10-JAN-18:00 |
Heating:NaturalGas | 168.26 | 0.00 | 04-JAN-18:10 | 94944.80 | 10-JAN-18:00 |
General:Heating:NaturalGas | 168.26 | 0.00 | 04-JAN-18:10 | 94944.80 | 10-JAN-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 273.82 | 0.00 | 04-JAN-18:10 | 133120.11 | 10-JAN-18:00 |
EnergyTransfer:Building | 143.60 | 0.00 | 04-JAN-18:10 | 64597.27 | 28-DEC-07:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 32.70 | 0.00 | 01-JAN-00:10 | 18663.45 | 10-JAN-07:10 |
Heating:EnergyTransfer | 108.61 | 0.00 | 04-JAN-18:10 | 64597.27 | 28-DEC-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 24.60 | 0.00 | 01-JAN-00:10 | 18663.45 | 10-JAN-07:10 |
General:Heating:EnergyTransfer | 108.61 | 0.00 | 04-JAN-18:10 | 64597.27 | 28-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 24.60 | 0.00 | 01-JAN-00:10 | 18663.45 | 10-JAN-07:10 |
Cooling:EnergyTransfer | 34.99 | 0.00 | 01-JAN-00:10 | 15768.13 | 22-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 8.10 | 0.00 | 01-JAN-00:10 | 7313.08 | 22-JUL-07:10 |
General:Cooling:EnergyTransfer | 34.99 | 0.00 | 01-JAN-00:10 | 15768.13 | 22-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 8.10 | 0.00 | 01-JAN-00:10 | 7313.08 | 22-JUL-07:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 73.59 | 0.00 | 01-JAN-00:40 | 24515.48 | 10-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 46.70 | 0.00 | 01-JAN-00:40 | 24515.48 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 46.70 | 0.00 | 01-JAN-00:40 | 24515.48 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 26.89 | 0.00 | 01-JAN-00:10 | 10951.06 | 23-JUL-11:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 26.89 | 0.00 | 01-JAN-00:10 | 10951.06 | 23-JUL-11:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 37.32 | 0.00 | 02-JAN-08:10 | 37429.85 | 30-DEC-01:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 37.32 | 0.00 | 02-JAN-08:10 | 37429.85 | 30-DEC-01:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 37.32 | 0.00 | 02-JAN-08:10 | 37429.85 | 30-DEC-01:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 130.22 | 0.00 | 04-JAN-18:10 | 71638.10 | 10-JAN-18:00 |
HeatingCoils:EnergyTransfer | 120.34 | 0.00 | 04-JAN-18:10 | 71638.10 | 10-JAN-18:00 |
CoolingCoils:EnergyTransfer | 9.88 | 0.00 | 01-JAN-00:10 | 19582.51 | 22-JUL-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 24.595 | -8.100 | 0.000 | 0.000 | 10.197 | 15.422 | 31.946 | 9.702 | 0.000 | 0.025 | 0.000 | 0.000 | -7.435 | 0.000 | -24.574 | -51.778 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 46.700 | -26.889 | 0.000 | 0.000 | 27.541 | 45.642 | 0.000 | 43.322 | 0.000 | 0.010 | 0.001 | 0.000 | -16.814 | 0.000 | -41.885 | -77.626 |
ZONE3 BULK STORAGE | 37.317 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 69.501 | 46.946 | 107.344 | 421.946 | 0.000 | 0.741 | 0.001 | 0.000 | -118.571 | 0.000 | -232.332 | -332.891 |
Total Facility | 37.317 | 0.000 | 71.295 | -34.990 | 0.000 | 0.000 | 107.239 | 108.010 | 139.290 | 474.970 | 0.000 | 0.776 | 0.002 | 0.000 | -142.821 | 0.000 | -298.791 | -462.295 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 22-JUL-07:02 | 0.00 | 0.00 | 0.00 | -14260.62 | 0.00 | 0.00 | 801.54 | 955.23 | 1912.50 | 374.12 | 0.00 | 0.00 | 10239.63 | 0.00 | -0.00 | 0.00 | -22.39 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-13:12 | 0.00 | 0.00 | 0.00 | -22473.80 | 0.00 | 0.00 | 0.00 | 256.14 | 0.00 | 8999.26 | 0.00 | 0.00 | 14549.56 | 0.00 | -0.00 | 0.00 | -1331.15 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-JUL-13:12 | 0.00 | 0.00 | 0.00 | -22473.80 | 0.00 | 0.00 | 0.00 | 758.73 | 573.75 | 115349.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7286.56 | -86921.36 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 20-OCT-06:01 | 0.00 | 0.00 | 23782.62 | 0.00 | 0.00 | 0.00 | 267.51 | 580.44 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -225.25 | 0.00 | -2672.66 | -22688.92 |
ZONE2 FINE STORAGE | 10-JAN-06:03 | 0.00 | 0.00 | 61062.12 | 0.00 | 0.00 | 0.00 | 365.28 | 512.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1531.41 | 0.00 | -4210.29 | -56197.97 |
ZONE3 BULK STORAGE | 30-DEC-00:55 | 37429.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13027.20 | 0.00 | -25720.72 | -1329.54 |
Total Facility | 28-DEC-06:43 | 33253.33 | 0.00 | 80496.22 | 0.00 | 0.00 | 0.00 | 1421.50 | 1427.79 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12942.69 | 0.00 | -33284.29 | -72995.63 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9343 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9343 | 0.1095 | 1.0000 | Not calculated | 0.1023 | 0.1095 | ||
PSZ-FINE STORAGE | 1.7051 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.7051 | 0.2491 | 1.0000 | Not calculated | 0.4247 | 0.2491 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9343 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9343 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1095 | ||
PSZ-FINE STORAGE | 1.7051 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.7051 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2491 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9343 | 0.9343 | 0.9343 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7051 | 1.7051 | 1.7051 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9343 | 0.9343 | 0.9343 | 0.9343 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.7051 | 1.7051 | 1.7051 | 1.7051 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9343 | 0.9343 | 0.9343 | No | 0.1023 | 0.3918 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7051 | 1.7051 | 1.7051 | No | 0.4247 | 0.8524 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9343 | 0.9343 | 0.9343 | 0.9343 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.7051 | 1.7051 | 1.7051 | 1.7051 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 14.50 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 14.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 168.26 | 94944.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2.07 | 4545.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 108.01 | 10498.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.93 | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 23.08 | 2255.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.04 | 2416.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 371.43 |
Natural Gas | 0.00 | 168.26 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 539.69 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 22.34 |
Space Heating | 0.00 |
Space Cooling | 0.43 |
Fans (All) | 4.77 |
Service Water Heating | 5.39 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 76.82 |
Subtotal | 76.82 |
Natural Gas [MJ/m2] | |
Space Heating | 34.80 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 34.80 |
Subtotal | 34.80 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 20.01 |
Space Heating | 31.18 |
Space Cooling | 0.38 |
Fans (All) | 4.28 |
Service Water Heating | 4.83 |
Receptacle Equipment | 25.81 |
Miscellaneous | 13.51 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2607. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8739.00 | 21.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8734.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 25.50 | 0.00 | 0.00 | 0.00 |
Average | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
Sum | 26233.50 | 46.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 82235.00 | 484.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 191193.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 191193.00 | 484.00 | 0.00 | 0.00 | 0.00 |
Average | 102151.67 | 161.33 | 0.00 | 0.00 | 0.00 |
Sum | 306455.00 | 484.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8738.33 | 21.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8651.17 | 108.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8651.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 108.83 | 0.00 | 0.00 | 0.00 |
Average | 8716.50 | 43.50 | 0.00 | 0.00 | 0.00 |
Sum | 26149.50 | 130.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 80194.00 | 2525.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 191193.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 191193.00 | 2525.00 | 0.00 | 0.00 | 0.00 |
Average | 101471.33 | 841.67 | 0.00 | 0.00 | 0.00 |
Sum | 304414.00 | 2525.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7219740.13 | 2328.11 | 10-JAN-08:05 | -5.7 | -6.7 | 0.493618E+09 | 604.22 | 28-JAN-08:20 | 7.03 | 6.45 |
February | 7038776.65 | 2039.78 | 18-FEB-07:05 | -1.7 | -1.7 | 0.454134E+09 | 603.31 | 01-FEB-08:20 | -1.7 | -1.7 |
March | 8728019.83 | 1691.52 | 21-MAR-07:05 | 1.33 | 0.86 | 0.533327E+09 | 622.34 | 25-MAR-13:39 | 12.67 | 9.93 |
April | 0.233573E+09 | 3148.67 | 29-APR-15:50 | 20.00 | 12.39 | 0.527653E+09 | 768.97 | 29-APR-15:20 | 20.00 | 12.39 |
May | 0.475122E+09 | 2951.64 | 25-MAY-16:00 | 18.00 | 13.90 | 0.571639E+09 | 768.99 | 23-MAY-15:09 | 18.00 | 13.90 |
June | 0.143287E+10 | 5557.41 | 13-JUN-16:00 | 26.50 | 17.70 | 0.636194E+09 | 769.27 | 23-JUN-12:09 | 16.50 | 14.26 |
July | 0.231840E+10 | 14260.28 | 22-JUL-07:02 | 23.17 | 16.28 | 0.627054E+09 | 879.39 | 22-JUL-07:10 | 23.17 | 16.28 |
August | 0.243469E+10 | 5335.18 | 14-AUG-16:00 | 26.00 | 15.86 | 0.679044E+09 | 793.69 | 19-AUG-07:10 | 12.67 | 11.93 |
September | 0.108439E+10 | 4017.05 | 13-SEP-16:00 | 23.00 | 16.22 | 0.610830E+09 | 771.28 | 25-SEP-08:50 | 19.33 | 13.41 |
October | 82121625.99 | 1618.65 | 07-OCT-07:07 | 4.00 | 3.46 | 0.515638E+09 | 768.97 | 02-OCT-15:00 | 4.00 | 3.46 |
November | 9136283.10 | 1801.23 | 29-NOV-08:05 | -0.7 | -1.6 | 0.473999E+09 | 613.65 | 10-NOV-15:39 | -0.7 | -1.6 |
December | 7090961.75 | 1905.69 | 30-DEC-07:05 | -0.8 | -2.2 | 0.493609E+09 | 603.70 | 02-DEC-08:20 | -0.8 | -2.2 |
Annual Sum or Average | 0.810037E+10 | 0.661674E+10 | ||||||||
Minimum of Months | 7038776.65 | 1618.65 | -5.7 | -6.7 | 0.454134E+09 | 603.31 | -1.7 | -2.2 | ||
Maximum of Months | 0.243469E+10 | 14260.28 | 26.50 | 17.70 | 0.679044E+09 | 879.39 | 23.17 | 16.28 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138835E+10 | 4930.09 | 21-JAN-16:50 | 4.35 | 3.81 | 0.663664E+09 | 933.24 | 19-JAN-15:20 | 4.35 | 3.81 |
February | 0.186757E+10 | 4975.42 | 23-FEB-15:30 | 4.50 | 4.26 | 0.610579E+09 | 925.40 | 27-FEB-16:10 | 8.00 | 6.56 |
March | 0.241156E+10 | 5918.43 | 15-MAR-09:05 | 2.00 | 1.57 | 0.732944E+09 | 1022.34 | 25-MAR-13:20 | 13.33 | 10.57 |
April | 0.268519E+10 | 5914.53 | 08-APR-07:03 | 2.50 | 1.05 | 0.921643E+09 | 1840.93 | 29-APR-15:09 | 20.00 | 12.69 |
May | 0.312195E+10 | 5974.11 | 01-MAY-15:00 | 8.00 | 6.98 | 0.107798E+10 | 1842.25 | 22-MAY-15:30 | 23.50 | 15.68 |
June | 0.297838E+10 | 5370.84 | 07-JUN-10:00 | 7.00 | 6.47 | 0.139965E+10 | 2246.82 | 13-JUN-15:00 | 26.50 | 17.70 |
July | 0.300894E+10 | 22474.48 | 23-JUL-13:12 | 21.67 | 16.29 | 0.152750E+10 | 2246.82 | 22-JUL-10:30 | 21.67 | 16.29 |
August | 0.240685E+10 | 4709.10 | 19-AUG-07:05 | 12.67 | 11.93 | 0.166801E+10 | 2246.80 | 14-AUG-15:39 | 12.67 | 11.93 |
September | 0.212770E+10 | 5515.13 | 28-SEP-07:03 | 8.17 | 7.16 | 0.128346E+10 | 2059.27 | 13-SEP-15:09 | 8.17 | 7.16 |
October | 0.214161E+10 | 6041.34 | 06-OCT-07:03 | 3.83 | 3.69 | 0.833935E+09 | 1499.86 | 07-OCT-15:20 | 18.67 | 9.96 |
November | 0.183398E+10 | 5473.45 | 16-NOV-08:05 | 3.17 | 2.71 | 0.653018E+09 | 1012.17 | 10-NOV-14:30 | 3.17 | 2.71 |
December | 0.916586E+09 | 4013.54 | 26-DEC-14:40 | 6.00 | 3.11 | 0.651700E+09 | 845.59 | 21-DEC-14:00 | 6.00 | 3.11 |
Annual Sum or Average | 0.268887E+11 | 0.120241E+11 | ||||||||
Minimum of Months | 0.916586E+09 | 4013.54 | 2.00 | 1.05 | 0.610579E+09 | 845.59 | 3.17 | 2.71 | ||
Maximum of Months | 0.312195E+10 | 22474.48 | 21.67 | 16.29 | 0.166801E+10 | 2246.82 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 | 1.45 | 0.796092E+09 | 1200.55 | 19-JAN-15:50 | 8.17 | 7.46 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 5.79 | 0.750587E+09 | 1184.13 | 04-FEB-14:00 | 9.00 | 6.57 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 | 3.71 | 0.101404E+10 | 1536.67 | 25-MAR-13:39 | 12.67 | 9.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 4.23 | 1.84 | 0.163781E+10 | 3210.15 | 29-APR-15:50 | 20.00 | 12.39 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 | 0.199040E+10 | 3063.80 | 26-MAY-15:30 | 15.00 | 12.39 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.39 | 0.264166E+10 | 4200.13 | 26-JUN-15:30 | 22.50 | 17.36 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 | 0.307153E+10 | 5005.96 | 22-JUL-15:50 | 29.00 | 16.64 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 | 0.348351E+10 | 4517.64 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 | 0.267112E+10 | 3936.97 | 13-SEP-15:50 | 23.00 | 16.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.83 | 0.173260E+10 | 2954.18 | 07-OCT-15:39 | 18.33 | 9.81 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.29 | 0.978208E+09 | 1640.28 | 10-NOV-15:09 | 11.83 | 8.42 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 | 3.53 | 0.731664E+09 | 1067.42 | 02-DEC-14:50 | 9.00 | 7.93 |
Annual Sum or Average | 0.00 | 0.214992E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.92 | 1.45 | 0.731664E+09 | 1067.42 | 8.17 | 6.57 | ||
Maximum of Months | 0.00 | 0.00 | 12.43 | 10.95 | 0.348351E+10 | 5005.96 | 29.00 | 17.36 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.455242E+10 | 23295.30 | 23-JAN-07:01 | 7.00 |
February | 0.375502E+10 | 23359.55 | 27-FEB-06:01 | 6.00 |
March | 0.389137E+10 | 23454.25 | 18-MAR-06:01 | 9.00 |
April | 0.133851E+10 | 23291.64 | 10-APR-06:01 | 7.17 |
May | 0.798180E+09 | 23566.47 | 19-MAY-06:01 | 9.00 |
June | 0.133196E+09 | 22476.76 | 08-JUN-06:03 | 7.50 |
July | 40035672.97 | 9064.54 | 05-JUL-07:03 | 12.17 |
August | 24030994.14 | 1787.33 | 31-AUG-07:03 | 13.00 |
September | 0.181841E+09 | 10120.54 | 07-SEP-07:03 | 10.33 |
October | 0.165978E+10 | 23782.16 | 20-OCT-06:01 | 11.17 |
November | 0.344911E+10 | 23577.69 | 24-NOV-07:02 | 11.00 |
December | 0.477258E+10 | 23204.34 | 05-DEC-07:01 | 6.00 |
Annual Sum or Average | 0.245961E+11 | |||
Minimum of Months | 24030994.14 | 1787.33 | 6.00 | |
Maximum of Months | 0.477258E+10 | 23782.16 | 13.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101448E+11 | 61062.17 | 10-JAN-06:03 | -4.0 |
February | 0.882063E+10 | 60135.37 | 17-FEB-04:13 | -2.0 |
March | 0.571807E+10 | 36066.15 | 25-MAR-06:01 | 1.17 |
April | 0.429915E+09 | 31972.00 | 11-APR-06:01 | 5.33 |
May | 60507048.09 | 759.66 | 30-MAY-07:00 | 8.00 |
June | 55052181.67 | 764.87 | 28-JUN-07:00 | 11.00 |
July | 54349572.76 | 778.89 | 11-JUL-06:50 | 12.83 |
August | 59213797.76 | 770.63 | 19-AUG-07:00 | 12.00 |
September | 55330136.58 | 765.64 | 27-SEP-06:50 | 9.67 |
October | 0.109311E+10 | 44005.65 | 17-OCT-06:01 | 7.17 |
November | 0.675837E+10 | 60565.78 | 28-NOV-06:01 | 1.00 |
December | 0.134505E+11 | 60541.95 | 27-DEC-06:01 | -2.0 |
Annual Sum or Average | 0.466998E+11 | |||
Minimum of Months | 54349572.76 | 759.66 | -4.0 | |
Maximum of Months | 0.134505E+11 | 61062.17 | 12.83 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103100E+11 | 35989.87 | 10-JAN-05:53 | -4.0 |
February | 0.556747E+10 | 24508.49 | 19-FEB-22:00 | 0.00 |
March | 0.375393E+09 | 11735.21 | 04-MAR-06:00 | 3.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.171280E+10 | 22205.39 | 29-NOV-03:57 | -1.0 |
December | 0.193514E+11 | 37429.97 | 30-DEC-00:55 | -2.0 |
Annual Sum or Average | 0.373170E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.193514E+11 | 37429.97 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.134747E+10 | 1064.14 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.120125E+10 | 1059.92 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.135460E+10 | 1052.82 | 15-MAR-07:10 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.123446E+10 | 1043.89 | 10-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.126884E+10 | 1012.93 | 04-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.124020E+10 | 994.29 | 14-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.123889E+10 | 1010.95 | 07-JUL-07:30 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.130401E+10 | 1034.53 | 22-AUG-07:30 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.125184E+10 | 1038.95 | 08-SEP-07:30 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.131109E+10 | 1063.76 | 31-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.129881E+10 | 1064.14 | 06-NOV-16:49 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.137059E+10 | 1064.14 | 01-DEC-15:30 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.154221E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.120125E+10 | 994.29 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.137059E+10 | 1064.14 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.450743E+10 | 4354.33 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.381194E+10 | 4354.33 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.397093E+10 | 4354.33 | 13-MAR-08:09 | 0.00 | 0.00 |
April | 0.336061E+10 | 3991.47 | 03-APR-08:09 | 0.00 | 0.00 |
May | 0.331671E+10 | 3628.61 | 05-MAY-08:09 | 0.00 | 0.00 |
June | 0.320110E+10 | 3628.61 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.319887E+10 | 3628.61 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.354824E+10 | 3991.47 | 08-AUG-08:09 | 0.00 | 0.00 |
September | 0.366973E+10 | 4354.33 | 23-SEP-08:09 | 0.00 | 0.00 |
October | 0.408851E+10 | 4354.33 | 03-OCT-08:09 | 0.00 | 0.00 |
November | 0.430766E+10 | 4354.33 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.466001E+10 | 4354.33 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.456417E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.319887E+10 | 3628.61 | 0.00 | 0.00 | |
Maximum of Months | 0.466001E+10 | 4354.33 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.473653E+10 | 5080.05 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.389828E+10 | 5080.05 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.398358E+10 | 4482.40 | 03-MAR-16:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.342631E+10 | 4482.40 | 10-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.340302E+10 | 3585.92 | 01-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.331273E+10 | 3287.09 | 17-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.328734E+10 | 2988.26 | 01-JUL-06:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.360168E+10 | 3810.04 | 08-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.364141E+10 | 4482.40 | 25-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.411113E+10 | 5080.05 | 20-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.450095E+10 | 5080.05 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.504276E+10 | 5080.05 | 01-DEC-14:50 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.469457E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.328734E+10 | 2988.26 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.504276E+10 | 5080.05 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.134747E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242363E+10 |
February | 0.127628E+10 | 0.120125E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225465E+10 |
March | 0.149825E+10 | 0.135460E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230307E+10 |
April | 0.138726E+10 | 0.123446E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169729E+10 |
May | 0.144276E+10 | 0.126884E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3689.62 | 0.236987E+10 |
June | 0.144276E+10 | 0.124020E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6837240.05 | 0.189170E+10 |
July | 0.138726E+10 | 0.123889E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13723682.46 | 0.161880E+10 |
August | 0.149825E+10 | 0.130401E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4875889.09 | 0.147846E+10 |
September | 0.138726E+10 | 0.125184E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148892E+10 |
October | 0.138726E+10 | 0.131109E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184569E+10 |
November | 0.133177E+10 | 0.129881E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235385E+10 |
December | 0.138726E+10 | 0.137059E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284809E+10 |
Annual Sum or Average | 0.168137E+11 | 0.154221E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25440501.23 | 0.245740E+11 |
Minimum of Months | 0.127628E+10 | 0.120125E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147846E+10 |
Maximum of Months | 0.149825E+10 | 0.137059E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13723682.46 | 0.284809E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.450743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205487E+10 |
February | 0.300332E+10 | 0.381194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285017E+10 |
March | 0.352563E+10 | 0.397093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181113E+10 |
April | 0.326447E+10 | 0.336061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31949.50 | 0.205049E+10 |
May | 0.339505E+10 | 0.331671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536077E+10 |
June | 0.339505E+10 | 0.320110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320281.29 | 0.485430E+10 |
July | 0.326447E+10 | 0.319887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8757386.77 | 0.475055E+10 |
August | 0.352563E+10 | 0.354824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574270.38 | 0.389024E+10 |
September | 0.326447E+10 | 0.366973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326436E+10 |
October | 0.326447E+10 | 0.408851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259184E+10 |
November | 0.313390E+10 | 0.430766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338408E+10 |
December | 0.326447E+10 | 0.466001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502249E+10 |
Annual Sum or Average | 0.395654E+11 | 0.456417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9683887.94 | 0.418853E+11 |
Minimum of Months | 0.300332E+10 | 0.319887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181113E+10 |
Maximum of Months | 0.352563E+10 | 0.466001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8757386.77 | 0.536077E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.473653E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29466241.11 | 0.666803E+10 |
February | 0.690763E+10 | 0.389828E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875206E+10 |
March | 0.810895E+10 | 0.398358E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 937609.04 | 0.588012E+10 |
April | 0.750829E+10 | 0.342631E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39246299.72 | 0.847248E+10 |
May | 0.780862E+10 | 0.340302E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93958620.14 | 0.228170E+11 |
June | 0.780862E+10 | 0.331273E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143369E+09 | 0.198896E+11 |
July | 0.750829E+10 | 0.328734E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145372E+09 | 0.204547E+11 |
August | 0.810895E+10 | 0.360168E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23529762.61 | 0.178160E+11 |
September | 0.750829E+10 | 0.364141E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14211543.57 | 0.154493E+11 |
October | 0.750829E+10 | 0.411113E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121513E+11 |
November | 0.720796E+10 | 0.450095E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28396406.28 | 0.106055E+11 |
December | 0.750829E+10 | 0.504276E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11163237.29 | 0.142719E+11 |
Annual Sum or Average | 0.910005E+11 | 0.469457E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529651E+09 | 0.163228E+12 |
Minimum of Months | 0.690763E+10 | 0.328734E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588012E+10 |
Maximum of Months | 0.810895E+10 | 0.504276E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145372E+09 | 0.228170E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1064.14 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10542.72 | 10-JAN-18:00 |
February | 1680.92 | 01-FEB-08:09 | 1059.92 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 9056.76 | 17-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1052.82 | 15-MAR-07:10 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 7665.52 | 08-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 1043.89 | 10-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6303.53 | 20-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1012.93 | 04-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 22-MAY-15:00 | 6978.46 | 01-MAY-16:03 |
June | 1680.92 | 01-JUN-07:10 | 994.29 | 14-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.29 | 13-JUN-17:00 | 5572.20 | 08-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1010.95 | 07-JUL-07:30 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1872.48 | 21-JUL-17:00 | 4754.86 | 20-JUL-06:03 |
August | 1680.92 | 01-AUG-07:10 | 1034.53 | 22-AUG-07:30 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1165.71 | 14-AUG-17:00 | 4943.72 | 24-AUG-06:03 |
September | 1680.92 | 01-SEP-07:10 | 1038.95 | 08-SEP-07:30 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5599.75 | 20-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1063.76 | 31-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 6912.14 | 04-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1064.14 | 06-NOV-16:49 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8980.68 | 29-NOV-08:00 |
December | 1680.92 | 01-DEC-08:09 | 1064.14 | 01-DEC-15:30 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 9614.96 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 994.29 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4754.86 | |||||
Maximum of Months | 1680.92 | 1064.14 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1872.48 | 10542.72 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 4354.33 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7181.69 | 10-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 4354.33 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4535.64 | 01-FEB-16:10 |
March | 3955.50 | 01-MAR-08:09 | 4354.33 | 13-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 7242.05 | 31-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 3991.47 | 03-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.88 | 30-APR-19:00 | 4171.93 | 24-APR-15:10 |
May | 3955.50 | 01-MAY-07:10 | 3628.61 | 05-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 9270.67 | 01-MAY-15:05 |
June | 3955.50 | 01-JUN-07:10 | 3628.61 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.21 | 12-JUN-18:00 | 6250.45 | 07-JUN-15:05 |
July | 3955.50 | 01-JUL-07:10 | 3628.61 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.09 | 22-JUL-15:10 | 5709.41 | 30-JUL-19:00 |
August | 3955.50 | 01-AUG-07:10 | 3991.47 | 08-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.49 | 14-AUG-18:00 | 6041.72 | 22-AUG-16:00 |
September | 3955.50 | 01-SEP-07:10 | 4354.33 | 23-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5634.22 | 29-SEP-15:10 |
October | 3955.50 | 02-OCT-07:10 | 4354.33 | 03-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4706.69 | 01-OCT-24:00 |
November | 3955.50 | 01-NOV-07:10 | 4354.33 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6334.85 | 15-NOV-07:02 |
December | 3955.50 | 01-DEC-08:09 | 4354.33 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 10545.41 | 02-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3628.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4171.93 | ||||
Maximum of Months | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.09 | 10545.41 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 5080.05 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3308.51 | 29-JAN-06:00 | 24888.83 | 10-JAN-16:00 |
February | 9097.65 | 01-FEB-08:09 | 5080.05 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 13327.53 | 01-FEB-16:00 |
March | 9097.65 | 01-MAR-08:09 | 4482.40 | 03-MAR-16:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 204.59 | 19-MAR-12:00 | 22789.51 | 31-MAR-08:00 |
April | 9097.65 | 01-APR-07:10 | 4482.40 | 10-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1931.20 | 30-APR-14:00 | 15339.12 | 24-APR-12:10 |
May | 9097.65 | 01-MAY-07:10 | 3585.92 | 01-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4281.74 | 22-MAY-15:00 | 36846.66 | 01-MAY-13:00 |
June | 9097.65 | 01-JUN-07:10 | 3287.09 | 17-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5956.16 | 13-JUN-15:00 | 24968.24 | 07-JUN-15:00 |
July | 9097.65 | 01-JUL-07:10 | 2988.26 | 01-JUL-06:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3569.21 | 22-JUL-15:00 | 22284.13 | 30-JUL-19:00 |
August | 9097.65 | 01-AUG-07:10 | 3810.04 | 08-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2372.28 | 14-AUG-18:00 | 23253.43 | 22-AUG-16:00 |
September | 9097.65 | 01-SEP-07:10 | 4482.40 | 25-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 926.00 | 24-SEP-16:00 | 20149.06 | 19-SEP-15:00 |
October | 9097.65 | 02-OCT-07:10 | 5080.05 | 20-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19886.37 | 01-OCT-24:00 |
November | 9097.65 | 01-NOV-07:10 | 5080.05 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5315.48 | 24-NOV-12:00 | 17435.25 | 03-NOV-07:10 |
December | 9097.65 | 01-DEC-08:09 | 5080.05 | 01-DEC-14:50 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5221.35 | 23-DEC-11:00 | 20626.90 | 28-DEC-08:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2988.26 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13327.53 | |||||
Maximum of Months | 9097.65 | 5080.05 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 5956.16 | 36846.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2328.11 | 10-JAN-08:05 | 6723.69 | 4250.16 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1641.33 |
February | 2039.78 | 18-FEB-07:05 | 2117.96 | 3482.65 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.77 |
March | 1691.52 | 21-MAR-07:05 | 6723.69 | 4115.84 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1074.96 |
April | 3148.67 | 29-APR-15:50 | 1680.92 | 856.64 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.11 |
May | 2951.64 | 25-MAY-16:00 | 1680.92 | 856.64 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.19 |
June | 5557.41 | 13-JUN-16:00 | 1680.92 | 856.64 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 278.93 | 0.00 |
July | 14260.28 | 22-JUL-07:02 | 8404.61 | 4776.14 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.39 |
August | 5335.18 | 14-AUG-16:00 | 1680.92 | 856.64 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 211.32 | 0.00 |
September | 4017.05 | 13-SEP-16:00 | 1680.92 | 856.64 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.24 |
October | 1618.65 | 07-OCT-07:07 | 5042.77 | 3089.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.33 |
November | 1801.23 | 29-NOV-08:05 | 6723.69 | 4235.26 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2086.48 |
December | 1905.69 | 30-DEC-07:05 | 2117.96 | 3482.65 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1618.65 | 1680.92 | 856.64 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14260.28 | 8404.61 | 4776.14 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 278.93 | 2086.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4930.09 | 21-JAN-16:50 | 3955.50 | 3842.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.36 |
February | 4975.42 | 23-FEB-15:30 | 3955.50 | 3265.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.19 |
March | 5918.43 | 15-MAR-09:05 | 7911.00 | 7982.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.19 |
April | 5914.53 | 08-APR-07:03 | 11866.50 | 11526.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5974.11 | 01-MAY-15:00 | 3955.50 | 2177.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3764.30 |
June | 5370.84 | 07-JUN-10:00 | 3955.50 | 2540.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2278.24 |
July | 22474.48 | 23-JUL-13:12 | 0.00 | 1280.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1331.15 |
August | 4709.10 | 19-AUG-07:05 | 7911.00 | 7684.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2444.00 |
September | 5515.13 | 28-SEP-07:03 | 11866.50 | 11526.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6041.34 | 06-OCT-07:03 | 11866.50 | 11526.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5473.45 | 16-NOV-08:05 | 15822.00 | 15368.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4013.54 | 26-DEC-14:40 | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4013.54 | 0.00 | 1280.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22474.48 | 15822.00 | 15368.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3764.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1792.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.06 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 1195.31 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2893.47 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 1195.31 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:05 | 0.00 | 1195.31 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3683.28 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7114.95 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9031.04 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15840.82 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7605.71 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9067.40 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12885.13 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5509.05 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 1195.31 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2490.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1792.96 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15840.82 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.348200E+11 | 28761.62 | 10-JAN-16:40 | 0.391313E+11 | 94944.80 | 10-JAN-17:00 |
February | 0.302132E+11 | 24107.77 | 01-FEB-09:09 | 0.283239E+11 | 53736.83 | 17-FEB-04:19 |
March | 0.324308E+11 | 23309.31 | 15-MAR-08:20 | 0.169620E+11 | 32285.80 | 04-MAR-06:19 |
April | 0.286040E+11 | 22811.50 | 10-APR-08:09 | 0.285046E+10 | 27050.13 | 11-APR-06:10 |
May | 0.284925E+11 | 21046.53 | 04-MAY-07:10 | 0.129894E+10 | 15837.22 | 05-MAY-06:10 |
June | 0.278406E+11 | 21355.84 | 13-JUN-14:00 | 0.162998E+09 | 10708.70 | 08-JUN-06:10 |
July | 0.280515E+11 | 23688.61 | 22-JUL-14:00 | 30473360.52 | 5940.25 | 05-JUL-06:10 |
August | 0.304244E+11 | 22997.00 | 08-AUG-08:30 | 1361341.23 | 1139.36 | 31-AUG-07:10 |
September | 0.298979E+11 | 22859.32 | 25-SEP-07:10 | 0.248732E+09 | 8067.93 | 21-SEP-06:10 |
October | 0.320062E+11 | 24050.79 | 31-OCT-08:09 | 0.436127E+10 | 26166.91 | 23-OCT-06:10 |
November | 0.329435E+11 | 28519.70 | 28-NOV-16:40 | 0.191530E+11 | 60900.78 | 28-NOV-07:10 |
December | 0.357031E+11 | 28679.79 | 27-DEC-16:40 | 0.557377E+11 | 85540.65 | 28-DEC-07:10 |
Annual Sum or Average | 0.371428E+12 | 0.168262E+12 | ||||
Minimum of Months | 0.278406E+11 | 21046.53 | 1361341.23 | 1139.36 | ||
Maximum of Months | 0.357031E+11 | 28761.62 | 0.557377E+11 | 94944.80 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.105914E+11 | 0.826839E+10 | 0.115358E+11 | 0.00 | 0.219150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223288E+10 | 0.00 |
February | 0.891147E+10 | 0.671184E+10 | 0.105871E+11 | 0.00 | 0.196695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203586E+10 | 0.00 |
March | 0.930911E+10 | 0.639322E+10 | 0.123431E+11 | 0.00 | 0.208880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229659E+10 | 0.00 |
April | 0.802138E+10 | 0.513836E+10 | 0.114862E+11 | 0.00 | 0.176069E+10 | 0.00 | 0.00 | 30087807.91 | 0.00 | 0.00 | 0.00 | 0.216728E+10 | 0.00 |
May | 0.798857E+10 | 0.446455E+10 | 0.119357E+11 | 0.00 | 0.181677E+10 | 0.00 | 0.00 | 65844161.68 | 0.00 | 0.00 | 0.00 | 0.222100E+10 | 0.00 |
June | 0.775403E+10 | 0.389319E+10 | 0.118862E+11 | 0.00 | 0.181650E+10 | 0.00 | 0.00 | 0.343957E+09 | 0.00 | 0.00 | 0.00 | 0.214673E+10 | 0.00 |
July | 0.772511E+10 | 0.419098E+10 | 0.115358E+11 | 0.00 | 0.175234E+10 | 0.00 | 0.00 | 0.703219E+09 | 0.00 | 0.00 | 0.00 | 0.214405E+10 | 0.00 |
August | 0.845393E+10 | 0.490547E+10 | 0.123357E+11 | 0.00 | 0.188637E+10 | 0.00 | 0.00 | 0.647783E+09 | 0.00 | 0.00 | 0.00 | 0.219513E+10 | 0.00 |
September | 0.856298E+10 | 0.573156E+10 | 0.114788E+11 | 0.00 | 0.174664E+10 | 0.00 | 0.00 | 0.276585E+09 | 0.00 | 0.00 | 0.00 | 0.210131E+10 | 0.00 |
October | 0.951074E+10 | 0.699960E+10 | 0.115432E+11 | 0.00 | 0.178046E+10 | 0.00 | 0.00 | 3875074.11 | 0.00 | 0.00 | 0.00 | 0.216841E+10 | 0.00 |
November | 0.101074E+11 | 0.771549E+10 | 0.110862E+11 | 0.00 | 0.191791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211645E+10 | 0.00 |
December | 0.110734E+11 | 0.852215E+10 | 0.115358E+11 | 0.00 | 0.235549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221635E+10 | 0.00 |
Annual Sum or Average | 0.108010E+12 | 0.729348E+11 | 0.139290E+12 | 0.00 | 0.230804E+11 | 0.00 | 0.00 | 0.207135E+10 | 0.00 | 0.00 | 0.00 | 0.260420E+11 | 0.00 |
Minimum of Months | 0.772511E+10 | 0.389319E+10 | 0.105871E+11 | 0.00 | 0.174664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203586E+10 | 0.00 |
Maximum of Months | 0.110734E+11 | 0.852215E+10 | 0.123431E+11 | 0.00 | 0.235549E+10 | 0.00 | 0.00 | 0.703219E+09 | 0.00 | 0.00 | 0.00 | 0.229659E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.391313E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.283239E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.169620E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.285046E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.129894E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.162998E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 30473360.52 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1361341.23 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.248732E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.436127E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.191530E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.557377E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168262E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 1361341.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.557377E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 10493.04 | 03-JAN-15:00 | 5492.60 | 01-JAN-06:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 2255.27 | 10-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 10479.80 | 01-FEB-09:09 | 5492.60 | 01-FEB-06:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 2034.20 | 17-FEB-07:19 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9622.38 | 15-MAR-08:09 | 5492.60 | 01-MAR-06:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 2006.73 | 04-MAR-07:19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 9368.34 | 10-APR-07:10 | 5492.60 | 01-APR-05:10 | 10112.62 | 01-APR-07:10 | 0.00 | 1876.22 | 11-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7523.08 | 04-MAY-07:10 | 5492.60 | 01-MAY-19:19 | 10112.62 | 01-MAY-07:10 | 0.00 | 1764.28 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7184.27 | 14-JUN-07:10 | 5492.60 | 01-JUN-19:00 | 10112.62 | 01-JUN-07:10 | 0.00 | 1764.28 | 01-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 7521.10 | 07-JUL-07:30 | 5492.60 | 01-JUL-20:19 | 10112.62 | 01-JUL-07:10 | 0.00 | 1764.28 | 21-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 8822.35 | 08-AUG-08:09 | 5492.60 | 01-AUG-19:49 | 10112.62 | 01-AUG-07:10 | 0.00 | 1764.28 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 9345.28 | 27-SEP-07:10 | 5492.60 | 01-SEP-05:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 1764.28 | 01-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 10483.28 | 31-OCT-08:09 | 5492.60 | 01-OCT-05:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 1887.28 | 28-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 10498.53 | 25-NOV-15:30 | 5492.60 | 01-NOV-05:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 2145.68 | 29-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 10498.53 | 01-DEC-15:30 | 5492.60 | 01-DEC-06:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 2192.15 | 28-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7184.27 | 5492.60 | 10112.62 | 0.00 | 1764.28 | 0.00 | 0.00 | |||||
Maximum of Months | 10498.53 | 5492.60 | 10112.62 | 0.00 | 2255.27 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2409.42 | 30-JAN-12:50 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2416.61 | 16-FEB-12:30 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2409.60 | 01-MAR-12:20 | 0.00 |
April | 789.19 | 29-APR-15:50 | 0.00 | 0.00 | 0.00 | 2350.51 | 01-APR-11:00 | 0.00 |
May | 863.62 | 22-MAY-15:50 | 0.00 | 0.00 | 0.00 | 2232.64 | 05-MAY-11:00 | 0.00 |
June | 2445.51 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2118.75 | 01-JUN-11:39 | 0.00 |
July | 4545.40 | 22-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1998.90 | 03-JUL-11:00 | 0.00 |
August | 1732.38 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1920.38 | 17-AUG-11:00 | 0.00 |
September | 1125.92 | 13-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1953.70 | 14-SEP-11:00 | 0.00 |
October | 359.09 | 07-OCT-15:30 | 0.00 | 0.00 | 0.00 | 2122.26 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2239.15 | 28-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2349.84 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1920.38 | 0.00 | ||
Maximum of Months | 4545.40 | 0.00 | 0.00 | 0.00 | 2416.61 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 28761.62 | 10-JAN-16:40 | 9388.60 | 10112.62 | 5492.60 | 0.00 | 2151.61 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24107.77 | 01-FEB-09:09 | 10479.80 | 10112.62 | 0.00 | 0.00 | 1825.97 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23309.31 | 15-MAR-08:20 | 9619.15 | 10112.62 | 0.00 | 0.00 | 1889.06 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22811.50 | 10-APR-08:09 | 9249.45 | 10112.62 | 0.00 | 0.00 | 1764.28 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21046.53 | 04-MAY-07:10 | 7523.08 | 10112.62 | 0.00 | 0.00 | 1764.28 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21355.84 | 13-JUN-14:00 | 5573.83 | 10112.62 | 0.00 | 0.00 | 1764.28 | 0.00 | 0.00 | 2120.22 | 0.00 |
July | 23688.61 | 22-JUL-14:00 | 5573.83 | 10112.62 | 0.00 | 0.00 | 1764.28 | 0.00 | 0.00 | 4461.26 | 0.00 |
August | 22997.00 | 08-AUG-08:30 | 8820.26 | 10112.62 | 0.00 | 0.00 | 1764.28 | 0.00 | 0.00 | 630.44 | 0.00 |
September | 22859.32 | 25-SEP-07:10 | 9343.20 | 10112.62 | 0.00 | 0.00 | 1764.28 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24050.79 | 31-OCT-08:09 | 10483.28 | 10112.62 | 0.00 | 0.00 | 1777.76 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28519.70 | 28-NOV-16:40 | 9388.60 | 10112.62 | 5492.60 | 0.00 | 1912.86 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28679.79 | 27-DEC-16:40 | 9388.60 | 10112.62 | 5492.60 | 0.00 | 2070.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21046.53 | 5573.83 | 10112.62 | 0.00 | 0.00 | 1764.28 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28761.62 | 10483.28 | 10112.62 | 5492.60 | 0.00 | 2151.61 | 0.00 | 0.00 | 4461.26 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 94944.80 | 10-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 53736.83 | 17-FEB-04:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 32285.80 | 04-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 27050.13 | 11-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 15837.22 | 05-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 10708.70 | 08-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 5940.25 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1139.36 | 31-AUG-07:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 8067.93 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 26166.91 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 60900.78 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 85540.65 | 28-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 1139.36 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 94944.80 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 16.35 | 2.17 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
February | 1.33 | 16.63 | 1.17 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
March | 1.00 | 17.21 | 1.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
April | 0.17 | 17.22 | 0.17 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 17.15 | 0.33 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
November | 1.00 | 17.12 | 1.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
December | 3.33 | 16.47 | 2.33 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
Annual Sum or Average | 10.33 | 16.62 | 8.17 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 17.22 | 2.33 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.50 | 14.87 | 1.83 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
February | 22.17 | 14.92 | 1.33 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
March | 7.17 | 14.96 | 0.17 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
April | 1.33 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.00 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5.33 | 14.98 | 0.17 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
November | 22.33 | 14.93 | 1.17 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
December | 51.00 | 14.87 | 3.67 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
Annual Sum or Average | 136.83 | 14.90 | 8.33 | 14.90 | 0.33 | 14.93 | 0.00 | 14.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.00 | 14.98 | 3.67 | 14.98 | 0.33 | 27.28 | 0.00 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.72 | 300.00 | 20.72 | 300.00 | 20.72 |
February | 276.00 | 20.72 | 276.00 | 20.72 | 276.00 | 20.72 |
March | 324.00 | 20.73 | 324.00 | 20.73 | 324.00 | 20.73 |
April | 300.00 | 21.37 | 199.00 | 21.08 | 199.00 | 20.96 |
May | 310.50 | 21.80 | 117.17 | 21.43 | 117.17 | 21.22 |
June | 253.33 | 22.98 | 24.00 | 22.88 | 13.00 | 22.75 |
July | 137.67 | 23.22 | 82.50 | 23.41 | 5.17 | 23.33 |
August | 162.00 | 23.37 | 36.50 | 23.47 | 0.00 | 23.47 |
September | 281.33 | 23.03 | 22.50 | 22.81 | 22.50 | 22.62 |
October | 300.00 | 21.14 | 208.67 | 20.92 | 208.67 | 20.83 |
November | 288.00 | 20.73 | 288.00 | 20.73 | 288.00 | 20.73 |
December | 300.00 | 20.72 | 300.00 | 20.72 | 300.00 | 20.72 |
Annual Sum or Average | 3232.83 | 21.54 | 2178.33 | 21.27 | 2053.50 | 21.11 |
Minimum of Months | 137.67 | 20.72 | 22.50 | 20.72 | 0.00 | 20.72 |
Maximum of Months | 324.00 | 23.37 | 324.00 | 23.47 | 324.00 | 23.47 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.69 | 300.00 | 15.69 | 300.00 | 15.69 |
February | 276.00 | 15.69 | 276.00 | 15.69 | 276.00 | 15.69 |
March | 324.00 | 15.85 | 324.00 | 15.85 | 324.00 | 15.85 |
April | 300.00 | 18.33 | 258.00 | 18.05 | 258.00 | 17.95 |
May | 308.00 | 19.44 | 215.83 | 19.01 | 215.83 | 18.83 |
June | 240.33 | 21.67 | 86.83 | 21.95 | 37.67 | 21.68 |
July | 140.50 | 22.56 | 153.83 | 23.88 | 20.33 | 23.85 |
August | 135.00 | 22.81 | 149.33 | 24.07 | 0.00 | 24.07 |
September | 270.33 | 21.55 | 78.67 | 21.35 | 61.00 | 21.07 |
October | 300.00 | 17.46 | 278.50 | 17.34 | 278.50 | 17.29 |
November | 288.00 | 15.86 | 288.00 | 15.86 | 288.00 | 15.86 |
December | 300.00 | 15.57 | 300.00 | 15.57 | 300.00 | 15.57 |
Annual Sum or Average | 3182.17 | 18.04 | 2709.00 | 17.89 | 2359.33 | 17.52 |
Minimum of Months | 135.00 | 15.57 | 78.67 | 15.57 | 0.00 | 15.57 |
Maximum of Months | 324.00 | 22.81 | 324.00 | 24.07 | 324.00 | 24.07 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 11.05 | 300.00 | 11.05 | 300.00 | 11.05 |
February | 276.00 | 11.17 | 276.00 | 11.17 | 276.00 | 11.17 |
March | 324.00 | 12.02 | 324.00 | 12.02 | 324.00 | 12.02 |
April | 300.00 | 16.01 | 298.33 | 16.00 | 298.33 | 15.99 |
May | 312.00 | 17.45 | 312.00 | 17.45 | 312.00 | 17.45 |
June | 312.00 | 20.24 | 152.33 | 19.78 | 152.33 | 19.56 |
July | 253.67 | 21.87 | 70.00 | 21.96 | 35.33 | 21.73 |
August | 285.83 | 22.74 | 14.33 | 22.83 | 0.00 | 22.83 |
September | 300.00 | 20.79 | 107.33 | 20.44 | 107.33 | 20.24 |
October | 300.00 | 16.56 | 300.00 | 16.56 | 300.00 | 16.56 |
November | 288.00 | 12.54 | 288.00 | 12.54 | 288.00 | 12.54 |
December | 300.00 | 10.60 | 300.00 | 10.60 | 300.00 | 10.60 |
Annual Sum or Average | 3551.50 | 16.02 | 2742.33 | 15.26 | 2693.33 | 14.91 |
Minimum of Months | 253.67 | 10.60 | 14.33 | 10.60 | 0.00 | 10.60 |
Maximum of Months | 324.00 | 22.74 | 324.00 | 22.83 | 324.00 | 22.83 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.140862E+09 | 30087807.91 | 22.33 | 0.138876E+09 | 1985493.79 | 0.00 | 0.49 | 29-APR-15:50 | 0.00 | 01-APR-00:05 | 3803.92 | 29-APR-15:50 | 3698.81 | 29-APR-15:50 | 118.06 | 29-APR-15:00 | 789.19 | 29-APR-15:50 | 0.00 | 01-APR-00:05 |
May | 0.309312E+09 | 65844161.68 | 46.42 | 0.278217E+09 | 31095638.47 | 0.00 | 0.52 | 22-MAY-15:50 | 0.00 | 01-MAY-00:10 | 4197.50 | 22-MAY-15:50 | 3778.44 | 22-MAY-15:50 | 582.18 | 23-MAY-15:00 | 863.62 | 22-MAY-15:50 | 0.00 | 01-MAY-00:10 |
June | 0.161345E+10 | 0.336950E+09 | 168.58 | 0.140105E+10 | 0.212395E+09 | 0.00 | 0.91 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 | 7778.22 | 13-JUN-16:00 | 6911.73 | 13-JUN-16:00 | 1255.33 | 26-JUN-16:00 | 1562.87 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.286368E+10 | 0.590048E+09 | 219.91 | 0.250944E+10 | 0.354233E+09 | 0.00 | 1.00 | 21-JUL-16:50 | 0.00 | 01-JUL-00:10 | 15959.43 | 22-JUL-07:02 | 15692.11 | 22-JUL-07:02 | 1296.72 | 24-JUL-16:00 | 3199.97 | 22-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.312956E+10 | 0.646597E+09 | 250.11 | 0.273755E+10 | 0.392010E+09 | 0.00 | 0.85 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 | 7038.09 | 14-AUG-16:00 | 6626.93 | 14-AUG-16:00 | 1166.00 | 18-AUG-16:00 | 1422.82 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.131064E+10 | 0.276585E+09 | 164.39 | 0.115079E+10 | 0.159849E+09 | 0.00 | 0.67 | 13-SEP-16:00 | 0.00 | 01-SEP-00:10 | 5618.69 | 13-SEP-16:00 | 4937.18 | 13-SEP-16:00 | 873.96 | 12-SEP-14:20 | 1125.92 | 13-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 17675071.54 | 3875074.11 | 8.17 | 17638562.45 | 36509.09 | 0.00 | 0.23 | 07-OCT-15:40 | 0.00 | 01-OCT-00:10 | 1657.38 | 07-OCT-15:30 | 1657.38 | 07-OCT-15:30 | 11.81 | 02-OCT-15:50 | 359.09 | 07-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.938517E+10 | 0.194999E+10 | 879.91 | 0.823357E+10 | 0.115160E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.312956E+10 | 0.646597E+09 | 250.11 | 0.273755E+10 | 0.392010E+09 | 0.00 | 1.00 | 0.00 | 15959.43 | 15692.11 | 1296.72 | 3199.97 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 27215580.00 | 7006938.33 | 3.50 | 23943030.03 | 3272549.98 | 0.00 | 0.23 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 | 3445.20 | 13-JUN-16:00 | 3080.36 | 13-JUN-16:00 | 380.05 | 13-JUN-15:40 | 882.64 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.463134E+09 | 0.113171E+09 | 15.59 | 0.440704E+09 | 22430052.14 | 0.00 | 1.00 | 22-JUL-17:12 | 0.00 | 01-JUL-00:10 | 34649.17 | 23-JUL-16:15 | 27441.19 | 23-JUL-12:32 | 8486.17 | 23-JUL-17:15 | 7507.45 | 23-JUL-16:15 | 0.00 | 01-JUL-00:10 |
August | 4480147.02 | 1186111.61 | 2.00 | 4446344.76 | 33802.26 | 0.00 | 0.08 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 | 1180.12 | 14-AUG-16:00 | 1180.12 | 14-AUG-16:00 | 17.06 | 14-AUG-15:30 | 309.56 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.494830E+09 | 0.121364E+09 | 21.09 | 0.469094E+09 | 25736404.38 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.463134E+09 | 0.113171E+09 | 15.59 | 0.440704E+09 | 22430052.14 | 0.00 | 1.00 | 0.00 | 34649.17 | 27441.19 | 8486.17 | 7507.45 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.23 | 14.45 | 29.78 | 32.04 | 101.44 | 0.00 | 0.00 | 0.00 |
February | 78.24 | 33.23 | 45.01 | 70.32 | 94.97 | 0.00 | 0.00 | 0.00 |
March | 70.51 | 13.55 | 56.96 | 54.17 | 74.68 | 0.00 | 0.00 | 0.00 |
April | 165.92 | 65.74 | 100.19 | 187.56 | 65.63 | 0.00 | 0.00 | 0.00 |
May | 194.61 | 78.90 | 115.71 | 215.11 | 58.37 | 0.00 | 0.00 | 0.00 |
June | 210.56 | 86.88 | 123.68 | 241.70 | 52.05 | 0.00 | 0.00 | 0.00 |
July | 214.45 | 94.61 | 119.85 | 252.30 | 52.35 | 0.00 | 0.00 | 0.00 |
August | 179.98 | 77.84 | 102.14 | 212.91 | 58.43 | 0.00 | 0.00 | 0.00 |
September | 145.69 | 65.85 | 79.84 | 169.20 | 67.08 | 0.00 | 0.00 | 0.00 |
October | 77.36 | 27.91 | 49.45 | 76.51 | 73.77 | 0.00 | 0.00 | 0.00 |
November | 41.87 | 12.33 | 29.55 | 30.91 | 87.67 | 0.00 | 0.00 | 0.00 |
December | 23.52 | 4.90 | 18.62 | 10.61 | 114.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 120.70 | 48.03 | 72.67 | 129.63 | 75.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.52 | 4.90 | 18.62 | 10.61 | 52.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.45 | 94.61 | 123.68 | 252.30 | 114.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.23 | 14.45 | 29.78 | 32.04 | 101.44 | 0.00 | 0.00 | 0.00 |
February | 78.24 | 33.23 | 45.01 | 70.32 | 94.97 | 0.00 | 0.00 | 0.00 |
March | 70.51 | 13.55 | 56.96 | 54.17 | 74.68 | 0.00 | 0.00 | 0.00 |
April | 165.92 | 65.74 | 100.19 | 187.56 | 65.63 | 0.00 | 0.00 | 0.00 |
May | 194.61 | 78.90 | 115.71 | 215.11 | 58.37 | 0.00 | 0.00 | 0.00 |
June | 210.56 | 86.88 | 123.68 | 241.70 | 52.05 | 0.00 | 0.00 | 0.00 |
July | 214.45 | 94.61 | 119.85 | 252.30 | 52.35 | 0.00 | 0.00 | 0.00 |
August | 179.98 | 77.84 | 102.14 | 212.91 | 58.43 | 0.00 | 0.00 | 0.00 |
September | 145.69 | 65.85 | 79.84 | 169.20 | 67.08 | 0.00 | 0.00 | 0.00 |
October | 77.36 | 27.91 | 49.45 | 76.51 | 73.77 | 0.00 | 0.00 | 0.00 |
November | 41.87 | 12.33 | 29.55 | 30.91 | 87.67 | 0.00 | 0.00 | 0.00 |
December | 23.52 | 4.90 | 18.62 | 10.61 | 114.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 120.70 | 48.03 | 72.67 | 129.63 | 75.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.52 | 4.90 | 18.62 | 10.61 | 52.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.45 | 94.61 | 123.68 | 252.30 | 114.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.91 | 0.00 | 12.91 | 2.29 | 61.95 | 0.00 | 0.00 | 0.00 |
February | 20.15 | 0.00 | 20.15 | 5.80 | 57.17 | 0.00 | 0.00 | 0.00 |
March | 27.89 | 0.00 | 27.89 | 14.31 | 45.01 | 0.00 | 0.00 | 0.00 |
April | 45.48 | 0.25 | 45.23 | 36.48 | 37.98 | 0.00 | 0.00 | 0.00 |
May | 57.02 | 2.95 | 54.07 | 45.19 | 32.17 | 0.00 | 0.00 | 0.00 |
June | 62.59 | 3.83 | 58.76 | 56.23 | 28.92 | 0.00 | 0.00 | 0.00 |
July | 59.51 | 3.36 | 56.14 | 54.29 | 28.91 | 0.00 | 0.00 | 0.00 |
August | 47.01 | 0.91 | 46.10 | 41.42 | 32.93 | 0.00 | 0.00 | 0.00 |
September | 35.64 | 0.02 | 35.62 | 28.95 | 39.73 | 0.00 | 0.00 | 0.00 |
October | 22.82 | 0.00 | 22.82 | 13.30 | 43.73 | 0.00 | 0.00 | 0.00 |
November | 13.71 | 0.00 | 13.71 | 3.35 | 52.15 | 0.00 | 0.00 | 0.00 |
December | 9.34 | 0.00 | 9.34 | 0.49 | 67.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.57 | 0.95 | 33.62 | 25.27 | 43.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.34 | 0.00 | 9.34 | 0.49 | 28.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.59 | 3.83 | 58.76 | 56.23 | 67.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.91 | 0.00 | 12.91 | 2.29 | 61.95 | 0.00 | 0.00 | 0.00 |
February | 20.15 | 0.00 | 20.15 | 5.80 | 57.17 | 0.00 | 0.00 | 0.00 |
March | 27.89 | 0.00 | 27.89 | 14.31 | 45.01 | 0.00 | 0.00 | 0.00 |
April | 45.47 | 0.25 | 45.23 | 36.48 | 37.98 | 0.00 | 0.00 | 0.00 |
May | 57.02 | 2.95 | 54.07 | 45.19 | 32.17 | 0.00 | 0.00 | 0.00 |
June | 62.59 | 3.83 | 58.76 | 56.23 | 28.92 | 0.00 | 0.00 | 0.00 |
July | 59.50 | 3.36 | 56.14 | 54.28 | 28.91 | 0.00 | 0.00 | 0.00 |
August | 47.01 | 0.91 | 46.10 | 41.42 | 32.93 | 0.00 | 0.00 | 0.00 |
September | 35.64 | 0.02 | 35.62 | 28.95 | 39.73 | 0.00 | 0.00 | 0.00 |
October | 22.82 | 0.00 | 22.82 | 13.30 | 43.73 | 0.00 | 0.00 | 0.00 |
November | 13.71 | 0.00 | 13.71 | 3.35 | 52.15 | 0.00 | 0.00 | 0.00 |
December | 9.34 | 0.00 | 9.34 | 0.49 | 67.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.57 | 0.95 | 33.62 | 25.27 | 43.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.34 | 0.00 | 9.34 | 0.49 | 28.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.59 | 3.83 | 58.76 | 56.23 | 67.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 18.28 | 48.29 | 6.17 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 38.07 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 50.73 | 35.51 | 7.00 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 147.67 | 33.66 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 172.68 | 30.92 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 186.28 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 190.27 | 29.29 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 164.17 | 34.30 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 119.39 | 38.34 | 0.67 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 55.58 | 37.64 | 21.17 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 21.45 | 41.74 | 2.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 9.76 | 53.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 98.12 | 38.08 | 37.67 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 9.76 | 27.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 190.27 | 53.62 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.87 | 6.61 | 17.26 | 23.53 | 33.13 | 118.00 | 0.00 | 0.00 |
February | 41.52 | 14.78 | 26.74 | 44.74 | 32.09 | 40.83 | 0.00 | 0.00 |
March | 51.96 | 9.87 | 42.09 | 57.55 | 25.13 | 10.83 | 0.00 | 0.00 |
April | 126.06 | 67.38 | 58.68 | 153.74 | 28.82 | 0.00 | 0.00 | 0.00 |
May | 151.02 | 83.30 | 67.72 | 178.74 | 27.02 | 0.00 | 0.00 | 0.00 |
June | 160.88 | 86.59 | 74.29 | 193.11 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 163.10 | 94.79 | 68.32 | 195.54 | 26.27 | 0.00 | 0.00 | 0.00 |
August | 140.58 | 84.74 | 55.84 | 167.81 | 32.25 | 0.00 | 0.00 | 0.00 |
September | 103.57 | 61.62 | 41.95 | 122.13 | 36.55 | 2.33 | 0.00 | 0.00 |
October | 53.09 | 23.23 | 29.86 | 57.34 | 35.65 | 26.67 | 0.00 | 0.00 |
November | 26.11 | 7.63 | 18.48 | 25.41 | 30.52 | 33.67 | 0.00 | 0.00 |
December | 16.63 | 4.10 | 12.53 | 13.93 | 35.33 | 6.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.41 | 45.52 | 42.88 | 103.05 | 30.53 | 238.33 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 4.10 | 12.53 | 13.93 | 23.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.10 | 94.79 | 74.29 | 195.54 | 36.55 | 118.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118466E+09 | 38704346.47 | 79761221.34 | 85817671.99 | 0.271709E+09 |
February | 0.189279E+09 | 80398761.05 | 0.108881E+09 | 0.170123E+09 | 0.229762E+09 |
March | 0.188864E+09 | 36303582.83 | 0.152560E+09 | 0.145099E+09 | 0.200025E+09 |
April | 0.430071E+09 | 0.170391E+09 | 0.259680E+09 | 0.486162E+09 | 0.170123E+09 |
May | 0.521245E+09 | 0.211320E+09 | 0.309924E+09 | 0.576162E+09 | 0.156332E+09 |
June | 0.545784E+09 | 0.225196E+09 | 0.320587E+09 | 0.626489E+09 | 0.134905E+09 |
July | 0.574394E+09 | 0.253401E+09 | 0.320993E+09 | 0.675758E+09 | 0.140205E+09 |
August | 0.482070E+09 | 0.208490E+09 | 0.273580E+09 | 0.570254E+09 | 0.156493E+09 |
September | 0.377622E+09 | 0.170679E+09 | 0.206943E+09 | 0.438570E+09 | 0.173882E+09 |
October | 0.207202E+09 | 74752083.80 | 0.132450E+09 | 0.204935E+09 | 0.197595E+09 |
November | 0.108539E+09 | 31953652.74 | 76585343.64 | 80121435.74 | 0.227231E+09 |
December | 62991728.83 | 13111787.98 | 49879940.85 | 28413927.88 | 0.306953E+09 |
Annual Sum or Average | 0.380653E+10 | 0.151470E+10 | 0.229183E+10 | 0.408791E+10 | 0.236521E+10 |
Minimum of Months | 62991728.83 | 13111787.98 | 49879940.85 | 28413927.88 | 0.134905E+09 |
Maximum of Months | 0.574394E+09 | 0.253401E+09 | 0.320993E+09 | 0.675758E+09 | 0.306953E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118466E+09 | 38704346.47 | 79761221.34 | 85817671.99 | 0.271709E+09 |
February | 0.189279E+09 | 80398761.05 | 0.108881E+09 | 0.170123E+09 | 0.229762E+09 |
March | 0.188864E+09 | 36303582.83 | 0.152560E+09 | 0.145099E+09 | 0.200025E+09 |
April | 0.430071E+09 | 0.170391E+09 | 0.259680E+09 | 0.486162E+09 | 0.170123E+09 |
May | 0.521245E+09 | 0.211320E+09 | 0.309924E+09 | 0.576162E+09 | 0.156332E+09 |
June | 0.545784E+09 | 0.225196E+09 | 0.320587E+09 | 0.626489E+09 | 0.134905E+09 |
July | 0.574394E+09 | 0.253401E+09 | 0.320993E+09 | 0.675758E+09 | 0.140205E+09 |
August | 0.482070E+09 | 0.208490E+09 | 0.273580E+09 | 0.570254E+09 | 0.156493E+09 |
September | 0.377622E+09 | 0.170679E+09 | 0.206943E+09 | 0.438570E+09 | 0.173882E+09 |
October | 0.207202E+09 | 74752083.80 | 0.132450E+09 | 0.204935E+09 | 0.197595E+09 |
November | 0.108539E+09 | 31953652.74 | 76585343.64 | 80121435.74 | 0.227231E+09 |
December | 62991728.83 | 13111787.98 | 49879940.85 | 28413927.88 | 0.306953E+09 |
Annual Sum or Average | 0.380653E+10 | 0.151470E+10 | 0.229183E+10 | 0.408791E+10 | 0.236521E+10 |
Minimum of Months | 62991728.83 | 13111787.98 | 49879940.85 | 28413927.88 | 0.134905E+09 |
Maximum of Months | 0.574394E+09 | 0.253401E+09 | 0.320993E+09 | 0.675758E+09 | 0.306953E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34569656.69 | 0.00 | 34569656.69 | 6135766.73 | 0.165938E+09 |
February | 48757919.88 | 0.00 | 48757919.88 | 14024684.62 | 0.138317E+09 |
March | 74709325.25 | 1058.91 | 74708266.34 | 38332808.49 | 0.120565E+09 |
April | 0.117874E+09 | 637971.16 | 0.117236E+09 | 94558611.66 | 98436168.81 |
May | 0.152729E+09 | 7902725.09 | 0.144826E+09 | 0.121047E+09 | 86167957.76 |
June | 0.162240E+09 | 9923470.49 | 0.152317E+09 | 0.145757E+09 | 74971462.60 |
July | 0.159382E+09 | 9012731.00 | 0.150370E+09 | 0.145401E+09 | 77445482.75 |
August | 0.125916E+09 | 2439432.28 | 0.123477E+09 | 0.110943E+09 | 88190341.67 |
September | 92386794.19 | 55538.11 | 92331256.08 | 75032828.61 | 0.102975E+09 |
October | 61129597.21 | 0.00 | 61129597.21 | 35633976.94 | 0.117135E+09 |
November | 35544954.04 | 0.00 | 35544954.04 | 8689702.45 | 0.135184E+09 |
December | 25012887.13 | 0.00 | 25012887.13 | 1321176.75 | 0.180848E+09 |
Annual Sum or Average | 0.109025E+10 | 29972927.05 | 0.106028E+10 | 0.796878E+09 | 0.138617E+10 |
Minimum of Months | 25012887.13 | 0.00 | 25012887.13 | 1321176.75 | 74971462.60 |
Maximum of Months | 0.162240E+09 | 9923470.49 | 0.152317E+09 | 0.145757E+09 | 0.180848E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34568471.84 | 0.00 | 34568471.84 | 6135088.32 | 0.165938E+09 |
February | 48756291.65 | 0.00 | 48756291.65 | 14023339.84 | 0.138317E+09 |
March | 74706663.97 | 1058.86 | 74705605.11 | 38329988.97 | 0.120565E+09 |
April | 0.117870E+09 | 637941.26 | 0.117232E+09 | 94554387.82 | 98435849.84 |
May | 0.152724E+09 | 7902354.68 | 0.144822E+09 | 0.121041E+09 | 86167675.70 |
June | 0.162235E+09 | 9923005.37 | 0.152312E+09 | 0.145751E+09 | 74971211.08 |
July | 0.159378E+09 | 9012308.57 | 0.150365E+09 | 0.145394E+09 | 77445111.06 |
August | 0.125913E+09 | 2439317.94 | 0.123473E+09 | 0.110939E+09 | 88189735.27 |
September | 92384093.86 | 55535.51 | 92328558.35 | 75029883.05 | 0.102975E+09 |
October | 61127603.02 | 0.00 | 61127603.02 | 35631985.76 | 0.117134E+09 |
November | 35543732.70 | 0.00 | 35543732.70 | 8688865.06 | 0.135184E+09 |
December | 25012016.75 | 0.00 | 25012016.75 | 1320905.42 | 0.180848E+09 |
Annual Sum or Average | 0.109022E+10 | 29971522.18 | 0.106025E+10 | 0.796839E+09 | 0.138617E+10 |
Minimum of Months | 25012016.75 | 0.00 | 25012016.75 | 1320905.42 | 74971211.08 |
Maximum of Months | 0.162235E+09 | 9923005.37 | 0.152312E+09 | 0.145751E+09 | 0.180848E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 48960712.86 | 0.129338E+09 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 92105297.91 | 0.112232E+09 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.135870E+09 | 95115258.40 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.382769E+09 | 87252959.66 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.462506E+09 | 82809637.31 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.482845E+09 | 71947591.59 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.509623E+09 | 78460487.44 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.439700E+09 | 91874039.34 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.309466E+09 | 99366910.73 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.148879E+09 | 0.100817E+09 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 55586151.85 | 0.108199E+09 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 0.143619E+09 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.309446E+10 | 0.120103E+10 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 26146310.11 | 71947591.59 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.509623E+09 | 0.143619E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63936073.71 | 17702201.82 | 46233871.89 | 63022521.47 | 88743248.70 |
February | 0.100442E+09 | 35762613.77 | 64678973.30 | 0.108235E+09 | 77629488.66 |
March | 0.139178E+09 | 26436240.06 | 0.112741E+09 | 0.154151E+09 | 67307597.31 |
April | 0.326752E+09 | 0.174661E+09 | 0.152092E+09 | 0.398484E+09 | 74689888.87 |
May | 0.404492E+09 | 0.223111E+09 | 0.181380E+09 | 0.478749E+09 | 72370631.19 |
June | 0.416994E+09 | 0.224447E+09 | 0.192547E+09 | 0.500539E+09 | 61225845.43 |
July | 0.436855E+09 | 0.253878E+09 | 0.182977E+09 | 0.523738E+09 | 70348501.41 |
August | 0.376542E+09 | 0.226975E+09 | 0.149567E+09 | 0.449468E+09 | 86388006.11 |
September | 0.268449E+09 | 0.159711E+09 | 0.108738E+09 | 0.316567E+09 | 94750361.47 |
October | 0.142209E+09 | 62225511.32 | 79983293.24 | 0.153576E+09 | 95484988.80 |
November | 67664725.88 | 19770168.54 | 47894557.34 | 65852718.66 | 79111575.84 |
December | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 94623247.44 |
Annual Sum or Average | 0.278804E+10 | 0.143565E+10 | 0.135239E+10 | 0.324969E+10 | 0.962673E+09 |
Minimum of Months | 44529470.18 | 10970547.99 | 33558922.19 | 37309265.59 | 61225845.43 |
Maximum of Months | 0.436855E+09 | 0.253878E+09 | 0.192547E+09 | 0.523738E+09 | 95484988.80 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 64.23 | 322.36 | 114.27 | 28.90 | 85.37 | 0.00 | 0.00 |
February | 149.26 | 301.32 | 196.79 | 66.47 | 130.32 | 0.00 | 0.00 |
March | 134.80 | 237.22 | 196.81 | 27.11 | 169.70 | 0.00 | 0.00 |
April | 446.90 | 206.03 | 422.80 | 131.97 | 290.83 | 0.00 | 0.00 |
May | 518.01 | 178.48 | 503.26 | 163.70 | 339.57 | 0.00 | 0.00 |
June | 593.32 | 159.39 | 546.31 | 181.42 | 364.89 | 0.00 | 0.00 |
July | 610.74 | 160.09 | 547.92 | 195.95 | 351.97 | 0.00 | 0.00 |
August | 507.48 | 181.53 | 453.99 | 157.50 | 296.49 | 0.00 | 0.00 |
September | 394.77 | 212.09 | 362.66 | 131.74 | 230.92 | 0.00 | 0.00 |
October | 178.17 | 233.55 | 200.37 | 55.82 | 144.55 | 0.00 | 0.00 |
November | 66.68 | 277.80 | 111.18 | 24.66 | 86.52 | 0.00 | 0.00 |
December | 20.80 | 362.84 | 65.71 | 9.79 | 55.92 | 0.00 | 0.00 |
Annual Sum or Average | 307.64 | 235.77 | 310.55 | 97.96 | 212.59 | 0.00 | 0.00 |
Minimum of Months | 20.80 | 159.39 | 65.71 | 9.79 | 55.92 | 0.00 | 0.00 |
Maximum of Months | 610.74 | 362.84 | 547.92 | 195.95 | 364.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 255.92 | 676.05 | 334.19 | 92.53 | 241.66 | 0.00 | 0.00 |
February | 533.02 | 649.49 | 581.26 | 206.96 | 374.30 | 0.00 | 0.00 |
March | 710.19 | 497.17 | 727.48 | 138.18 | 589.30 | 0.00 | 0.00 |
April | 2067.43 | 471.27 | 1764.87 | 943.38 | 821.48 | 0.00 | 0.00 |
May | 2417.52 | 432.85 | 2114.28 | 1166.20 | 948.08 | 0.00 | 0.00 |
June | 2607.96 | 388.61 | 2252.28 | 1212.29 | 1039.99 | 0.00 | 0.00 |
July | 2663.80 | 410.11 | 2283.44 | 1327.02 | 956.42 | 0.00 | 0.00 |
August | 2298.31 | 480.23 | 1968.19 | 1186.40 | 781.79 | 0.00 | 0.00 |
September | 1671.50 | 536.70 | 1449.96 | 862.64 | 587.32 | 0.00 | 0.00 |
October | 778.19 | 526.97 | 743.33 | 325.25 | 418.07 | 0.00 | 0.00 |
November | 300.23 | 584.41 | 365.47 | 106.78 | 258.69 | 0.00 | 0.00 |
December | 136.67 | 750.70 | 232.76 | 57.34 | 175.41 | 0.00 | 0.00 |
Annual Sum or Average | 1373.74 | 533.18 | 1237.72 | 637.34 | 600.38 | 0.00 | 0.00 |
Minimum of Months | 136.67 | 388.61 | 232.76 | 57.34 | 175.41 | 0.00 | 0.00 |
Maximum of Months | 2663.80 | 750.70 | 2283.44 | 1327.02 | 1039.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3209.09 | 6036.51 | 763.87 | 211.50 | 552.38 | 0.00 | 0.00 |
February | 5904.47 | 5761.13 | 1328.59 | 473.05 | 855.54 | 0.00 | 0.00 |
March | 7538.61 | 4171.59 | 1662.81 | 315.85 | 1346.97 | 0.00 | 0.00 |
April | 20465.12 | 3005.72 | 4033.98 | 2156.30 | 1877.68 | 0.00 | 0.00 |
May | 24485.34 | 2602.30 | 4832.64 | 2665.61 | 2167.03 | 0.00 | 0.00 |
June | 26899.19 | 2267.77 | 5148.07 | 2770.95 | 2377.12 | 0.00 | 0.00 |
July | 25078.61 | 2521.78 | 5219.29 | 3033.19 | 2186.11 | 0.00 | 0.00 |
August | 21254.09 | 3118.51 | 4498.71 | 2711.76 | 1786.95 | 0.00 | 0.00 |
September | 16336.65 | 3559.79 | 3314.19 | 1971.74 | 1342.45 | 0.00 | 0.00 |
October | 7815.41 | 4262.66 | 1699.03 | 743.44 | 955.59 | 0.00 | 0.00 |
November | 3173.92 | 5166.19 | 835.37 | 244.08 | 591.29 | 0.00 | 0.00 |
December | 1987.88 | 6576.60 | 532.01 | 131.07 | 400.94 | 0.00 | 0.00 |
Annual Sum or Average | 13709.62 | 4080.23 | 2829.06 | 1456.77 | 1372.29 | 0.00 | 0.00 |
Minimum of Months | 1987.88 | 2267.77 | 532.01 | 131.07 | 400.94 | 0.00 | 0.00 |
Maximum of Months | 26899.19 | 6576.60 | 5219.29 | 3033.19 | 2377.12 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.172022E+09 | 0.863411E+09 | 0.306069E+09 | 77408692.93 | 0.228661E+09 | 0.00 | 0.00 |
February | 0.361080E+09 | 0.728945E+09 | 0.476073E+09 | 0.160798E+09 | 0.315275E+09 | 0.00 | 0.00 |
March | 0.361049E+09 | 0.635367E+09 | 0.527144E+09 | 72609283.44 | 0.454535E+09 | 0.00 | 0.00 |
April | 0.115836E+10 | 0.534042E+09 | 0.109589E+10 | 0.342057E+09 | 0.753829E+09 | 0.00 | 0.00 |
May | 0.138745E+10 | 0.478035E+09 | 0.134794E+10 | 0.438446E+09 | 0.909496E+09 | 0.00 | 0.00 |
June | 0.153788E+10 | 0.413149E+09 | 0.141604E+10 | 0.470239E+09 | 0.945803E+09 | 0.00 | 0.00 |
July | 0.163580E+10 | 0.428788E+09 | 0.146755E+10 | 0.524828E+09 | 0.942721E+09 | 0.00 | 0.00 |
August | 0.135924E+10 | 0.486217E+09 | 0.121597E+10 | 0.421860E+09 | 0.794110E+09 | 0.00 | 0.00 |
September | 0.102324E+10 | 0.549746E+09 | 0.940016E+09 | 0.341469E+09 | 0.598546E+09 | 0.00 | 0.00 |
October | 0.477207E+09 | 0.625529E+09 | 0.536661E+09 | 0.149504E+09 | 0.387156E+09 | 0.00 | 0.00 |
November | 0.172838E+09 | 0.720045E+09 | 0.288167E+09 | 63907305.49 | 0.224259E+09 | 0.00 | 0.00 |
December | 55709774.04 | 0.971841E+09 | 0.176008E+09 | 26223575.96 | 0.149785E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.970187E+10 | 0.743512E+10 | 0.979353E+10 | 0.308935E+10 | 0.670418E+10 | 0.00 | 0.00 |
Minimum of Months | 55709774.04 | 0.413149E+09 | 0.176008E+09 | 26223575.96 | 0.149785E+09 | 0.00 | 0.00 |
Maximum of Months | 0.163580E+10 | 0.971841E+09 | 0.146755E+10 | 0.524828E+09 | 0.945803E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.685450E+09 | 0.181073E+10 | 0.895105E+09 | 0.247831E+09 | 0.647274E+09 | 0.00 | 0.00 |
February | 0.128947E+10 | 0.157125E+10 | 0.140618E+10 | 0.500677E+09 | 0.905506E+09 | 0.00 | 0.00 |
March | 0.190218E+10 | 0.133161E+10 | 0.194849E+10 | 0.370107E+09 | 0.157838E+10 | 0.00 | 0.00 |
April | 0.535877E+10 | 0.122154E+10 | 0.457453E+10 | 0.244525E+10 | 0.212929E+10 | 0.00 | 0.00 |
May | 0.647509E+10 | 0.115933E+10 | 0.566289E+10 | 0.312356E+10 | 0.253932E+10 | 0.00 | 0.00 |
June | 0.675983E+10 | 0.100727E+10 | 0.583792E+10 | 0.314226E+10 | 0.269566E+10 | 0.00 | 0.00 |
July | 0.713472E+10 | 0.109845E+10 | 0.611597E+10 | 0.355429E+10 | 0.256168E+10 | 0.00 | 0.00 |
August | 0.615579E+10 | 0.128624E+10 | 0.527159E+10 | 0.317765E+10 | 0.209394E+10 | 0.00 | 0.00 |
September | 0.433253E+10 | 0.139114E+10 | 0.375829E+10 | 0.223595E+10 | 0.152234E+10 | 0.00 | 0.00 |
October | 0.208430E+10 | 0.141144E+10 | 0.199092E+10 | 0.871157E+09 | 0.111977E+10 | 0.00 | 0.00 |
November | 0.778206E+09 | 0.151479E+10 | 0.947306E+09 | 0.276782E+09 | 0.670524E+09 | 0.00 | 0.00 |
December | 0.366048E+09 | 0.201067E+10 | 0.623413E+09 | 0.153588E+09 | 0.469825E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.433224E+11 | 0.168145E+11 | 0.390326E+11 | 0.200991E+11 | 0.189335E+11 | 0.00 | 0.00 |
Minimum of Months | 0.366048E+09 | 0.100727E+10 | 0.623413E+09 | 0.153588E+09 | 0.469825E+09 | 0.00 | 0.00 |
Maximum of Months | 0.713472E+10 | 0.201067E+10 | 0.611597E+10 | 0.355429E+10 | 0.269566E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.859523E+10 | 0.161682E+11 | 0.204595E+10 | 0.566470E+09 | 0.147948E+10 | 0.00 | 0.00 |
February | 0.142841E+11 | 0.139373E+11 | 0.321413E+10 | 0.114440E+10 | 0.206973E+10 | 0.00 | 0.00 |
March | 0.201914E+11 | 0.111732E+11 | 0.445368E+10 | 0.845960E+09 | 0.360772E+10 | 0.00 | 0.00 |
April | 0.530456E+11 | 0.779083E+10 | 0.104561E+11 | 0.558914E+10 | 0.486694E+10 | 0.00 | 0.00 |
May | 0.655815E+11 | 0.697000E+10 | 0.129437E+11 | 0.713957E+10 | 0.580417E+10 | 0.00 | 0.00 |
June | 0.697227E+11 | 0.587806E+10 | 0.133438E+11 | 0.718231E+10 | 0.616150E+10 | 0.00 | 0.00 |
July | 0.671705E+11 | 0.675433E+10 | 0.139794E+11 | 0.812409E+10 | 0.585527E+10 | 0.00 | 0.00 |
August | 0.569269E+11 | 0.835261E+10 | 0.120494E+11 | 0.726319E+10 | 0.478616E+10 | 0.00 | 0.00 |
September | 0.423446E+11 | 0.922698E+10 | 0.859038E+10 | 0.511075E+10 | 0.347963E+10 | 0.00 | 0.00 |
October | 0.209328E+11 | 0.114171E+11 | 0.455068E+10 | 0.199122E+10 | 0.255947E+10 | 0.00 | 0.00 |
November | 0.822681E+10 | 0.133908E+11 | 0.216527E+10 | 0.632645E+09 | 0.153263E+10 | 0.00 | 0.00 |
December | 0.532433E+10 | 0.176148E+11 | 0.142494E+10 | 0.351058E+09 | 0.107389E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.432347E+12 | 0.128674E+12 | 0.892174E+11 | 0.459408E+11 | 0.432766E+11 | 0.00 | 0.00 |
Minimum of Months | 0.532433E+10 | 0.587806E+10 | 0.142494E+10 | 0.351058E+09 | 0.107389E+10 | 0.00 | 0.00 |
Maximum of Months | 0.697227E+11 | 0.176148E+11 | 0.139794E+11 | 0.812409E+10 | 0.616150E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.939589E+09 | -869209182.9 | 0.00 | 0.00 | 744.00 | 0.00 | -70380249.8 | 58.99 | 0.00 | 0.00 |
February | 0.867357E+09 | -803824070.3 | 0.00 | 0.00 | 672.00 | 0.00 | -63533429.2 | 58.99 | 0.00 | 0.00 |
March | 0.100279E+10 | -933151845.0 | 0.00 | 0.00 | 744.00 | 0.00 | -69640853.9 | 58.99 | 0.00 | 0.00 |
April | 0.915416E+09 | -850510637.7 | 0.00 | 0.00 | 720.00 | 0.00 | -64905852.9 | 58.99 | 0.00 | 0.00 |
May | 0.926693E+09 | -860902328.2 | 0.00 | 0.00 | 744.00 | 0.00 | -65790709.9 | 58.99 | 0.00 | 0.00 |
June | 0.894683E+09 | -834449820.4 | 0.00 | 0.00 | 720.00 | 0.00 | -60233570.5 | 58.99 | 0.00 | 0.00 |
July | 0.850321E+09 | -789579875.5 | 0.00 | 0.00 | 744.00 | 0.00 | -60740789.0 | 59.01 | 0.00 | 0.00 |
August | 0.901943E+09 | -841406674.6 | 0.00 | 0.00 | 744.00 | 0.00 | -60536624.0 | 59.00 | 0.00 | 0.00 |
September | 0.848865E+09 | -788041174.8 | 0.00 | 0.00 | 720.00 | 0.00 | -60823772.2 | 59.01 | 0.00 | 0.00 |
October | 0.874641E+09 | -806684663.1 | 0.00 | 0.00 | 744.00 | 0.00 | -67956494.7 | 58.99 | 0.00 | 0.00 |
November | 0.864352E+09 | -796616755.0 | 0.00 | 0.00 | 720.00 | 0.00 | -67735550.0 | 58.99 | 0.00 | 0.00 |
December | 0.922558E+09 | -851917484.2 | 0.00 | 0.00 | 744.00 | 0.00 | -70640494.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.108092E+11 | -0.100263E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -782918390.9 | 59.00 | 0.00 | 0.00 |
Minimum of Months | 0.848865E+09 | -933151845.0 | 0.00 | 0.00 | 672.00 | 0.00 | -70640494.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.100279E+10 | -788041174.8 | 0.00 | 0.00 | 744.00 | 0.00 | -60233570.5 | 59.01 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.89 | 0.67 | 09-JAN-12:20 | 134.81 | 0.00 | 0.00 | 0.00 | 107.37 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.80 | 0.50 | 10-FEB-13:30 | 186.10 | 0.00 | 0.00 | 14.50 | 1069.75 | 0.00 | 0.00 | 44.17 |
March | 215.50 | 0.74 | 0.50 | 01-MAR-12:50 | 259.96 | 0.00 | 0.00 | 101.17 | 225.79 | 0.00 | 0.00 | 51.33 |
April | 359.67 | 0.70 | 0.50 | 01-APR-09:00 | 315.23 | 0.00 | 0.00 | 180.83 | 251.56 | 0.00 | 0.00 | 125.17 |
May | 417.17 | 0.68 | 0.50 | 01-MAY-09:20 | 339.50 | 0.00 | 0.00 | 226.50 | 262.84 | 0.00 | 0.00 | 159.83 |
June | 410.67 | 0.66 | 0.50 | 01-JUN-10:39 | 376.12 | 0.00 | 0.00 | 238.00 | 289.89 | 0.00 | 0.00 | 173.00 |
July | 429.00 | 0.68 | 0.50 | 01-JUL-10:00 | 341.93 | 0.00 | 0.00 | 234.67 | 266.18 | 0.00 | 0.00 | 158.33 |
August | 396.33 | 0.70 | 0.50 | 01-AUG-09:39 | 306.97 | 0.00 | 0.00 | 191.17 | 244.65 | 0.00 | 0.00 | 134.67 |
September | 337.67 | 0.74 | 0.50 | 01-SEP-09:50 | 251.51 | 0.00 | 0.00 | 110.17 | 206.47 | 0.00 | 0.00 | 69.50 |
October | 234.00 | 0.77 | 0.50 | 01-OCT-10:50 | 218.17 | 0.00 | 0.00 | 42.67 | 177.66 | 0.00 | 0.00 | 15.17 |
November | 171.33 | 0.86 | 0.67 | 02-NOV-12:20 | 153.26 | 0.00 | 0.00 | 0.00 | 123.72 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.91 | 0.75 | 02-DEC-11:20 | 122.43 | 0.00 | 0.00 | 0.00 | 99.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.73 | 278.45 | 0.00 | 0.00 | 1339.67 | 278.10 | 0.00 | 0.00 | 931.17 | ||
Minimum of Months | 131.67 | 0.66 | 0.50 | 122.43 | 0.00 | 0.00 | 0.00 | 99.37 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 429.00 | 0.91 | 0.75 | 376.12 | 0.00 | 0.00 | 238.00 | 1069.75 | 0.00 | 0.00 | 173.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.75 | 0.50 | 02-JAN-12:20 | 157.02 | 11.50 | 0.00 | 55.83 | 127.66 | 14.77 | 0.00 | 20.33 |
February | 217.00 | 0.67 | 0.50 | 01-FEB-11:00 | 216.77 | 13.22 | 0.00 | 122.67 | 176.25 | 16.76 | 17.33 | 81.67 |
March | 215.50 | 0.62 | 0.50 | 01-MAR-11:39 | 527.24 | 14.98 | 8.67 | 219.00 | 439.86 | 17.62 | 42.83 | 184.50 |
April | 359.67 | 0.60 | 0.50 | 01-APR-07:00 | 661.06 | 15.99 | 16.50 | 287.33 | 559.68 | 19.18 | 131.67 | 244.67 |
May | 417.17 | 0.59 | 0.50 | 01-MAY-07:10 | 391.40 | 15.47 | 2.17 | 339.83 | 784.36 | 19.90 | 136.00 | 286.83 |
June | 410.67 | 0.57 | 0.50 | 01-JUN-07:10 | 430.82 | 16.00 | 1.83 | 347.67 | 1368.17 | 21.40 | 139.67 | 295.67 |
July | 429.00 | 0.58 | 0.50 | 01-JUL-07:19 | 395.73 | 15.55 | 3.17 | 350.50 | 948.78 | 20.42 | 141.83 | 295.67 |
August | 396.33 | 0.60 | 0.50 | 01-AUG-07:40 | 355.80 | 15.08 | 0.17 | 307.50 | 291.12 | 18.91 | 118.33 | 260.33 |
September | 337.67 | 0.62 | 0.50 | 01-SEP-08:09 | 295.06 | 14.57 | 0.00 | 242.00 | 242.91 | 18.51 | 99.67 | 193.83 |
October | 234.00 | 0.63 | 0.50 | 01-OCT-08:50 | 862.33 | 14.12 | 0.00 | 165.67 | 443.95 | 19.17 | 52.17 | 126.00 |
November | 171.33 | 0.71 | 0.50 | 01-NOV-12:20 | 179.14 | 12.38 | 0.00 | 68.83 | 146.20 | 15.71 | 0.00 | 31.50 |
December | 131.67 | 0.77 | 0.50 | 02-DEC-11:20 | 143.99 | 11.55 | 0.00 | 21.83 | 118.85 | 14.84 | 0.00 | 1.33 |
Annual Sum or Average | 3515.67 | 0.62 | 407.09 | 14.69 | 32.50 | 2528.67 | 568.14 | 18.76 | 879.50 | 2022.33 | ||
Minimum of Months | 131.67 | 0.57 | 0.50 | 143.99 | 11.50 | 0.00 | 21.83 | 118.85 | 14.77 | 0.00 | 1.33 | |
Maximum of Months | 429.00 | 0.77 | 0.50 | 862.33 | 16.00 | 16.50 | 350.50 | 1368.17 | 21.40 | 141.83 | 295.67 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.92 | 0.82 | 19-JAN-15:30 | 197.64 | 22.22 | 77.33 | 14.00 | 88.81 | 19.45 | 58.17 | 0.00 |
February | 217.00 | 0.90 | 0.80 | 09-FEB-15:30 | 461.25 | 24.04 | 111.83 | 42.17 | 131.23 | 20.89 | 107.00 | 4.00 |
March | 215.50 | 0.89 | 0.80 | 02-MAR-16:40 | 287.78 | 23.05 | 139.17 | 33.50 | 197.43 | 23.46 | 157.50 | 13.83 |
April | 359.67 | 0.86 | 0.80 | 01-APR-13:00 | 364.85 | 22.50 | 223.50 | 119.83 | 326.96 | 23.64 | 269.00 | 78.50 |
May | 417.17 | 0.86 | 0.80 | 01-MAY-13:50 | 333.03 | 21.83 | 236.83 | 123.17 | 362.31 | 22.90 | 305.67 | 95.33 |
June | 410.67 | 0.85 | 0.80 | 01-JUN-14:09 | 360.65 | 22.15 | 243.17 | 143.50 | 459.82 | 23.19 | 301.00 | 96.33 |
July | 429.00 | 0.86 | 0.80 | 01-JUL-14:00 | 350.75 | 21.91 | 239.17 | 145.33 | 471.37 | 23.01 | 309.00 | 109.17 |
August | 396.33 | 0.87 | 0.80 | 01-AUG-14:09 | 354.72 | 22.08 | 225.00 | 127.67 | 354.74 | 23.00 | 280.67 | 97.00 |
September | 337.67 | 0.87 | 0.80 | 01-SEP-14:09 | 431.03 | 23.79 | 186.67 | 103.83 | 331.83 | 24.27 | 215.83 | 70.83 |
October | 234.00 | 0.89 | 0.80 | 01-OCT-14:20 | 312.52 | 23.66 | 127.67 | 48.67 | 168.19 | 22.76 | 132.67 | 16.50 |
November | 171.33 | 0.91 | 0.82 | 03-NOV-15:20 | 196.39 | 21.93 | 72.50 | 10.00 | 97.84 | 19.92 | 58.33 | 0.00 |
December | 131.67 | 0.94 | 0.83 | 25-DEC-14:30 | 140.15 | 18.69 | 28.83 | 0.00 | 75.09 | 18.68 | 23.67 | 0.00 |
Annual Sum or Average | 3515.67 | 0.88 | 335.89 | 22.40 | 1911.67 | 911.67 | 303.45 | 22.57 | 2218.50 | 581.50 | ||
Minimum of Months | 131.67 | 0.85 | 0.80 | 140.15 | 18.69 | 28.83 | 0.00 | 75.09 | 18.68 | 23.67 | 0.00 | |
Maximum of Months | 429.00 | 0.94 | 0.83 | 461.25 | 24.04 | 243.17 | 145.33 | 471.37 | 24.27 | 309.00 | 109.17 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.549045E+10 | 24339.36 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.452388E+10 | 24339.36 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.461870E+10 | 24339.36 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155032E+10 | 24339.36 | 01-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.882733E+09 | 24339.36 | 05-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109432E+09 | 24184.98 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20355873.14 | 10136.36 | 05-JUL-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 885512.60 | 2237.86 | 31-AUG-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166576E+09 | 11479.83 | 20-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185624E+10 | 24339.36 | 04-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.403081E+10 | 24339.36 | 01-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.568506E+10 | 24339.36 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 885512.60 | 2237.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.568506E+10 | 24339.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125634E+11 | 59988.75 | 09-JAN-23:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101103E+11 | 59934.66 | 17-FEB-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.657354E+10 | 35381.28 | 25-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.390301E+09 | 31290.20 | 11-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109725E+10 | 43403.85 | 17-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.759395E+10 | 59988.75 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161056E+11 | 59988.75 | 25-DEC-17:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.544343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161056E+11 | 59988.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102161E+11 | 35894.02 | 10-JAN-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.550075E+10 | 24412.59 | 19-FEB-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366156E+09 | 11639.36 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169167E+10 | 22109.53 | 29-NOV-03:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191917E+11 | 37334.11 | 30-DEC-00:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.191917E+11 | 37334.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.140862E+09 | 0.138876E+09 | 3803.92 | 29-APR-15:50 | 3698.81 | 0.00 |
May | 0.00 | 0.00 | 0.309312E+09 | 0.278217E+09 | 4197.50 | 22-MAY-15:50 | 3778.44 | 0.00 |
June | 0.00 | 0.00 | 0.161345E+10 | 0.140105E+10 | 7778.22 | 13-JUN-16:00 | 6911.73 | 0.00 |
July | 0.00 | 0.00 | 0.286368E+10 | 0.250944E+10 | 15959.43 | 22-JUL-07:02 | 15692.11 | 0.00 |
August | 0.00 | 0.00 | 0.312956E+10 | 0.273755E+10 | 7038.09 | 14-AUG-16:00 | 6626.93 | 0.00 |
September | 0.00 | 0.00 | 0.131064E+10 | 0.115079E+10 | 5618.69 | 13-SEP-16:00 | 4937.18 | 0.00 |
October | 0.00 | 0.00 | 17675071.54 | 17638562.45 | 1657.38 | 07-OCT-15:30 | 1657.38 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.938517E+10 | 0.823357E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.312956E+10 | 0.273755E+10 | 15959.43 | 15692.11 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 27215580.00 | 23943030.03 | 3445.20 | 13-JUN-16:00 | 3080.36 | 0.00 |
July | 0.00 | 0.00 | 0.463134E+09 | 0.440704E+09 | 34649.17 | 23-JUL-16:15 | 26719.37 | 0.00 |
August | 0.00 | 0.00 | 4480147.02 | 4446344.76 | 1180.12 | 14-AUG-16:00 | 1180.12 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.494830E+09 | 0.469094E+09 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.463134E+09 | 0.440704E+09 | 34649.17 | 26719.37 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 93589399.45 | 0.03 | 95.86 | 01-JAN-00:03 | 0.08 |
February | 66260017.92 | 0.02 | 95.86 | 03-FEB-03:50 | 0.08 |
March | 9202780.27 | 0.00 | 95.86 | 03-MAR-20:30 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 21026435.66 | 0.01 | 95.86 | 19-NOV-07:40 | 0.08 |
December | 0.159011E+09 | 0.05 | 95.86 | 01-DEC-00:05 | 0.08 |
Annual Sum or Average | 0.349090E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159011E+09 | 0.05 | 95.86 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.104111E+10 | 0.38 | 1034.47 | 02-JAN-06:11 | 0.92 |
February | 0.955450E+09 | 0.37 | 1034.47 | 01-FEB-06:02 | 0.92 |
March | 0.111759E+10 | 0.39 | 1034.47 | 01-MAR-06:02 | 0.92 |
April | 0.102697E+10 | 0.36 | 1034.47 | 01-APR-06:02 | 0.92 |
May | 0.106536E+10 | 0.35 | 1034.47 | 01-MAY-06:20 | 0.92 |
June | 0.106509E+10 | 0.36 | 1034.47 | 01-JUN-06:20 | 0.91 |
July | 0.102413E+10 | 0.34 | 1034.47 | 01-JUL-06:10 | 0.91 |
August | 0.110606E+10 | 0.36 | 1034.47 | 01-AUG-06:05 | 0.91 |
September | 0.102413E+10 | 0.35 | 1034.47 | 01-SEP-06:05 | 0.91 |
October | 0.102669E+10 | 0.34 | 1034.47 | 11-OCT-08:40 | 0.91 |
November | 0.993286E+09 | 0.35 | 1034.47 | 01-NOV-06:02 | 0.92 |
December | 0.104383E+10 | 0.38 | 1034.47 | 01-DEC-06:02 | 0.92 |
Annual Sum or Average | 0.124897E+11 | 0.36 | |||
Minimum of Months | 0.955450E+09 | 0.34 | 1034.47 | 0.91 | |
Maximum of Months | 0.111759E+10 | 0.39 | 1034.47 | 0.92 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105680E+10 | 0.50 | 1824.51 | 09-JAN-23:23 | 0.89 |
February | 0.945236E+09 | 0.51 | 1822.87 | 17-FEB-04:13 | 0.89 |
March | 0.962006E+09 | 0.43 | 1375.46 | 25-MAR-06:01 | 0.77 |
April | 0.733712E+09 | 0.22 | 1300.81 | 11-APR-06:01 | 0.75 |
May | 0.751408E+09 | 0.21 | 729.81 | 01-MAY-06:10 | 0.54 |
June | 0.751408E+09 | 0.21 | 729.81 | 13-JUN-14:10 | 0.53 |
July | 0.728216E+09 | 0.20 | 1076.91 | 23-JUL-13:12 | 0.68 |
August | 0.780308E+09 | 0.21 | 729.81 | 14-AUG-16:50 | 0.54 |
September | 0.722508E+09 | 0.20 | 729.81 | 01-SEP-06:05 | 0.53 |
October | 0.753767E+09 | 0.24 | 1521.86 | 17-OCT-06:01 | 0.81 |
November | 0.903598E+09 | 0.43 | 1824.51 | 28-NOV-06:01 | 0.89 |
December | 0.115265E+10 | 0.55 | 1824.51 | 25-DEC-17:53 | 0.89 |
Annual Sum or Average | 0.102416E+11 | 0.33 | |||
Minimum of Months | 0.722508E+09 | 0.20 | 729.81 | 0.53 | |
Maximum of Months | 0.115265E+10 | 0.55 | 1824.51 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.104111E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.955450E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.111759E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.105706E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.113120E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.140204E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.161418E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.175265E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.130071E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.103056E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.993286E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.104383E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.144397E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.955450E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.175265E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.105680E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.945236E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.962006E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.733712E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.751408E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.758415E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.841387E+09 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.781494E+09 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.722508E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.753767E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.903598E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.115265E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.103630E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.722508E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.115265E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.104111E+10 | 0.00 | 0.549045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.955450E+09 | 0.00 | 0.452388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111759E+10 | 0.00 | 0.461870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102697E+10 | 0.140862E+09 | 0.155032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106536E+10 | 0.309312E+09 | 0.882733E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106509E+10 | 0.161345E+10 | 0.109432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102413E+10 | 0.286368E+10 | 20355873.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110606E+10 | 0.312956E+10 | 885512.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102413E+10 | 0.131064E+10 | 0.166576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102669E+10 | 17675071.54 | 0.185624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.993286E+09 | 0.00 | 0.403081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104383E+10 | 0.00 | 0.568506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124897E+11 | 0.938517E+10 | 0.289354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.955450E+09 | 0.00 | 885512.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111759E+10 | 0.312956E+10 | 0.568506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.105680E+10 | 0.00 | 0.125634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.945236E+09 | 0.00 | 0.101103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.962006E+09 | 0.00 | 0.657354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.733712E+09 | 0.00 | 0.390301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.751408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.751408E+09 | 27215580.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.728216E+09 | 0.441111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.780308E+09 | 4480147.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.722508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.753767E+09 | 0.00 | 0.109725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.903598E+09 | 0.00 | 0.759395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115265E+10 | 0.00 | 0.161056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102416E+11 | 0.472806E+09 | 0.544343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.722508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115265E+10 | 0.441111E+09 | 0.161056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.104111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.955450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102697E+10 | 0.00 | 0.00 | 0.00 | 30087807.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106536E+10 | 0.00 | 0.00 | 0.00 | 65844161.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106509E+10 | 0.00 | 0.00 | 0.00 | 0.336950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102413E+10 | 0.00 | 0.00 | 0.00 | 0.590048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110606E+10 | 0.00 | 0.00 | 0.00 | 0.646597E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102413E+10 | 0.00 | 0.00 | 0.00 | 0.276585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102669E+10 | 0.00 | 0.00 | 0.00 | 3875074.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.993286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124897E+11 | 0.00 | 0.00 | 0.00 | 0.194999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.955450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111759E+10 | 0.00 | 0.00 | 0.00 | 0.646597E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.105680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.945236E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.962006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.733712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.751408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.751408E+09 | 0.00 | 0.00 | 0.00 | 7006938.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.728216E+09 | 0.00 | 0.00 | 0.00 | 0.113171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.780308E+09 | 0.00 | 0.00 | 0.00 | 1186111.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.722508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.753767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.903598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102416E+11 | 0.00 | 0.00 | 0.00 | 0.121364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.722508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115265E+10 | 0.00 | 0.00 | 0.00 | 0.113171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17532269.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218369E+10 | 0.00 | 0.00 | 0.14 |
February | 23118626.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189545E+10 | 0.00 | 0.00 | 0.14 |
March | 34227895.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205529E+10 | 0.00 | 0.00 | 0.15 |
April | 0.700248E+09 | 0.00 | 0.00 | 191712.27 | 212856.36 | 0.747245E+09 | 98082714.66 | 0.00 | 0.14 |
May | 0.937438E+09 | 0.00 | 0.00 | 433945.64 | 0.00 | 0.395527E+09 | 0.203178E+09 | 0.00 | 0.14 |
June | 0.496363E+09 | 5457682.93 | 0.00 | 2017123.99 | 0.00 | 50002121.23 | 0.683900E+09 | 0.00 | 0.15 |
July | 0.219686E+09 | 6941543.13 | 0.00 | 3394264.40 | 24754.49 | 11410525.97 | 0.698461E+09 | 0.00 | 0.14 |
August | 0.174625E+09 | 13380.57 | 0.00 | 4046494.73 | 0.00 | 868284.03 | 0.696434E+09 | 0.00 | 0.15 |
September | 0.420633E+09 | 0.00 | 0.00 | 1695115.48 | 0.00 | 78900554.91 | 0.587419E+09 | 0.00 | 0.14 |
October | 0.517286E+09 | 0.00 | 0.00 | 26076.40 | 0.00 | 0.926082E+09 | 49078976.67 | 0.00 | 0.14 |
November | 47003504.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172246E+10 | 0.00 | 0.00 | 0.14 |
December | 13486989.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214566E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.360165E+10 | 12412606.63 | 0.00 | 11804732.91 | 237610.86 | 0.122126E+11 | 0.301655E+10 | 0.00 | 0.14 |
Minimum of Months | 13486989.67 | 0.00 | 0.00 | 0.00 | 0.00 | 868284.03 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.937438E+09 | 6941543.13 | 0.00 | 4046494.73 | 212856.36 | 0.218369E+10 | 0.698461E+09 | 0.00 | 0.15 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.309077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219084E+10 | 0.00 | 0.00 | 0.17 |
February | 0.345540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959849E+09 | 0.00 | 0.00 | 0.18 |
March | 0.423666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467049E+09 | 0.00 | 0.00 | 0.19 |
April | 0.395789E+10 | 0.00 | 0.00 | 0.00 | 4047827.53 | 0.00 | 0.00 | 0.00 | 0.18 |
May | 0.434665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
June | 0.432457E+10 | 0.00 | 0.00 | 65167.69 | 0.00 | 0.00 | 67650091.61 | 0.00 | 0.19 |
July | 0.384558E+10 | 0.00 | 0.00 | 857476.74 | 481512.07 | 0.00 | 0.322794E+09 | 0.00 | 0.18 |
August | 0.393040E+10 | 0.00 | 0.00 | 39422.28 | 0.00 | 0.00 | 0.128271E+09 | 0.00 | 0.19 |
September | 0.346350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
October | 0.336596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40577237.16 | 0.00 | 0.00 | 0.17 |
November | 0.309937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788729E+09 | 0.00 | 0.00 | 0.17 |
December | 0.221245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278223E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.433292E+11 | 0.00 | 0.00 | 962066.70 | 4529339.60 | 0.722927E+10 | 0.518715E+09 | 0.00 | 0.18 |
Minimum of Months | 0.221245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.434665E+10 | 0.00 | 0.00 | 857476.74 | 4047827.53 | 0.278223E+10 | 0.322794E+09 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.146277E+12 | 0.150096E+11 | 0.00 | 0.104378E+11 | 0.108608E+11 |
February | 0.255830E+12 | 0.189213E+11 | 0.00 | 0.901472E+10 | 0.818902E+10 |
March | 0.334084E+12 | 0.142165E+11 | 0.00 | 0.947494E+10 | 0.540365E+10 |
April | 0.954745E+12 | 0.175758E+11 | 0.00 | 0.806026E+10 | 0.108079E+10 |
May | 0.114131E+13 | 0.424909E+11 | 0.00 | 0.835930E+10 | 0.791364E+09 |
June | 0.116518E+13 | 0.380999E+11 | 0.00 | 0.781766E+10 | 0.203819E+10 |
July | 0.119543E+13 | 0.391467E+11 | 0.00 | 0.731263E+10 | 0.404015E+10 |
August | 0.989099E+12 | 0.347522E+11 | 0.00 | 0.707410E+10 | 0.378230E+10 |
September | 0.716434E+12 | 0.303535E+11 | 0.00 | 0.688379E+10 | 0.166938E+10 |
October | 0.314254E+12 | 0.243666E+11 | 0.00 | 0.726085E+10 | 0.142933E+10 |
November | 0.933111E+11 | 0.224757E+11 | 0.00 | 0.802067E+10 | 0.583661E+10 |
December | 0.295283E+10 | 0.299774E+11 | 0.00 | 0.992535E+10 | 0.147554E+11 |
Annual Sum or Average | 0.730891E+13 | 0.327386E+12 | 0.00 | 0.996421E+11 | 0.598770E+11 |