Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:44
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 10:44:05
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 761.50 | 157.49 | 157.49 |
Net Site Energy | 761.50 | 157.49 | 157.49 |
Total Source Energy | 1591.46 | 329.14 | 329.14 |
Net Source Energy | 1591.46 | 329.14 | 329.14 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 393.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 92.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 367.73 | 393.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 393.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 92.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 393.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 92.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 25.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 32.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.82 | 81.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 76.05 | 81.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 32.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.82 | 81.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 76.05 | 81.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 367.733 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 367.733 | 100.00 |
Total On-Site and Utility Electric Sources | 367.733 | 100.00 |
Total Electricity End Uses | 367.733 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 25.17 |
Time Setpoint Not Met During Occupied Cooling | 1.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3211.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:44 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.0858 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.1969 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3435 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3435 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.0858 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.1969 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.3435 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.3435 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.3435 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-14:20 | 06-FEB-00:10 | - | - | - | - | - | - | - | - | - | - | 25-AUG-11:09 |
Heating | 0.00 | 207619.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 11270.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5065.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4568.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1727.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32666.82 | 207619.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 207619.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 11270.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5065.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2262.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1727.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 426.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 64.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 294.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 195.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 97.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 80.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1164.61 | 426.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 88.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 60.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 240.86 | 88.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 88.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 60.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 240.86 | 88.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.960775 |
ZONE2 FINE STORAGE DIRECT AIR | 2.13 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 3.45 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 3.45 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 141091.10 |
PSZ-OFFICE HEATING COIL | 25947.70 |
PSZ-FINE STORAGE HEATING COIL | 76594.74 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 141091.10 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.960775 | 0.960775 | 0.960775 | 0.960775 | 0.960775 | 0.960775 | 1.00 | 1.00 | 0.960775 |
PSZ-FINE STORAGE | 2.13 | 2.13 | 2.13 | 2.13 | 2.13 | 2.13 | 1.00 | 1.00 | 2.13 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.960775 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.13 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.960775 | 1063.73 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.13 | 2284.11 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.960775 | 0.960775 | 0.960775 | 0.960775 | 18831.41 | 25947.70 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.13 | 2.13 | 2.13 | 1.41 | 53006.95 | 76594.74 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.960770 | 0.480387 | 0.640513 | 18831.41 | 9415.70 | 0.784510 | 0.784510 |
PSZ-FINE STORAGE COOLING COIL | 2.13 | 1.07 | 1.42 | 53006.95 | 26503.47 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.086 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.160 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.197 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.756 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1441.602 | 6.086 | 113.078 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1441.602 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10245.499 | 3.197 | 148.485 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10245.499 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1360 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5623E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.5264E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.276 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.71 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.92 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
2 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
3 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
4 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
5 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
6 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
7 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
8 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
9 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
10 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
11 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
12 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
13 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
14 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
15 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
16 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.31240856E-08 | -0.21887765E-14 | 0.14182747E-14 | -0.45258500E-16 |
55 | 6 | 0.39303604E-05 | 0.26006625E-08 | 0.31948254E-02 | -0.26800873E-04 |
56 | 5 | -0.27546567E-03 | 0.15375372E-05 | -0.22400621 | 0.19586362E-02 |
57 | 4 | 0.62896480E-02 | 0.69930755E-04 | 4.8342361 | -0.45310069E-01 |
58 | 3 | -0.55086064E-01 | 0.55565958E-03 | -38.047911 | 0.39894661 |
59 | 2 | 0.19539610 | 0.92379386E-03 | 116.53551 | -1.4186290 |
60 | 1 | -0.28189481 | 0.28115072E-03 | -143.93766 | 2.0495388 |
61 | 0 | 0.13740557 | 0.68297879E-05 | 60.838472 | |
62 | 7 | -0.76172223E-08 | 0.19992769E-15 | -0.36679418E-14 | 0.15936503E-16 |
63 | 6 | 0.20832875E-05 | 0.10921259E-08 | 0.32010154E-02 | -0.26852800E-04 |
64 | 5 | -0.12434769E-03 | 0.63986796E-06 | -0.22435781 | 0.19617397E-02 |
65 | 4 | 0.26900562E-02 | 0.28962460E-04 | 4.8400881 | -0.45366326E-01 |
66 | 3 | -0.23075003E-01 | 0.22921474E-03 | -38.080948 | 0.39931181 |
67 | 2 | 0.81154666E-01 | 0.37960809E-03 | 116.59978 | -1.4194888 |
68 | 1 | -0.11662584 | 0.11498440E-03 | -143.97548 | 2.0501605 |
69 | 0 | 0.56734574E-01 | 0.27738523E-05 | 60.838472 | |
70 | 7 | -0.81392023E-08 | 0.28718252E-15 | -0.25842544E-14 | 0.71742475E-17 |
71 | 6 | 0.20245979E-05 | 0.10259199E-08 | 0.32012942E-02 | -0.26855138E-04 |
72 | 5 | -0.11816234E-03 | 0.60006224E-06 | -0.22437362 | 0.19618793E-02 |
73 | 4 | 0.25345016E-02 | 0.27140048E-04 | 4.8403509 | -0.45368853E-01 |
74 | 3 | -0.21665828E-01 | 0.21464768E-03 | -38.082430 | 0.39932820 |
75 | 2 | 0.76088909E-01 | 0.35527252E-03 | 116.60266 | -1.4195273 |
76 | 1 | -0.10927342 | 0.10751462E-03 | -143.97718 | 2.0501884 |
77 | 0 | 0.53139756E-01 | 0.25964760E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20666597E-14 | 0.96147816E-16 | 0.79647225E-12 | 0.11382549E-15 |
85 | 3 | -0.56581374E-04 | 0.28930881E-06 | -0.38972706E-03 | 0.15282143E-12 |
86 | 2 | 1.1494565 | 0.62914578E-02 | 1.7513786 | -0.74717338E-04 |
87 | 1 | -17.155584 | 0.16244765 | -7.1131205 | 0.33567575 |
88 | 0 | 16.278262 | 0.10333854 | 5.6342095 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3624_SHGC_SOUTH_0.36 | 34 | 1 | VerySmooth | 2.059 | 2.059 | 1.000 | 0.361 | ||
2 | NONRESWINDOW_U_0.3624_SHGC_NORTH_0.36 | 35 | 1 | VerySmooth | 2.059 | 2.059 | 1.000 | 0.361 | ||
3 | NONRESWINDOW_U_0.3624_SHGC_EAST_0.36 | 36 | 1 | VerySmooth | 2.059 | 2.059 | 1.000 | 0.361 | ||
4 | NONRESWINDOW_U_0.3624_SHGC_WEST_0.36 | 37 | 1 | VerySmooth | 2.059 | 2.059 | 1.000 | 0.361 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.6 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.63294E-002 | 0.27318 | 0.51973 | 0.51973 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11606 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.63294E-002 | 0.27318 | 0.51973 | 0.51973 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11606 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.63294E-002 | 0.27318 | 0.51973 | 0.51973 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11606 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.63294E-002 | 0.27318 | 0.51973 | 0.51973 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11606 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.056 | 0.5354 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.099 | 0.605 | 0.602 |
2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.605 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 3.407E-002 | 1.438E-004 | 2.220E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.173 | 1.244E-004 | 7.923E-005 | 0.211 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.168 | 6.763E-004 | 4.417E-004 | 0.221 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4159E-004 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0170E-003 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2463E-004 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0750E-003 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2305E-004 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1965E-003 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5727E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2026E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5780E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6233E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1552E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2658E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4380E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7536E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7631E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3735E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.5868E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7667E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.6710E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0750E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1307E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0664E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2192E-003 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2548E-004 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0451E-003 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5757E-004 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4411E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7038E-004 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6195E-003 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2479E-004 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0518E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7651E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0956E-003 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1117E-004 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1328E-003 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1668E-004 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3929E-003 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8086E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3050E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9351E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5237E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2094E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2303E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.4629E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8382E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8225E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9123E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6423E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6584E-003 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.5376E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9991E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8736E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9875E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9083E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8041E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6567E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8405E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2118E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2048E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2926E-004 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8897E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0080E-004 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7108E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9807E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3555E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9460E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2011E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1724E-004 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5014E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3526E-004 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3923E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9389E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9841E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.4944E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4368E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.2757E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1223E-003 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5846E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4880E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3403E-004 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2496E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3755E-003 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6662E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6625E-003 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0290E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7356E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2548E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9448E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5571E-004 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6530E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3505E-004 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0633E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3191E-004 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3948E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7670E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2140E-003 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0466E-004 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6604E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.6589E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6020E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5191E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.7879E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0952E-004 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8074E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0114E-004 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1197E-003 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4025E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0406E-003 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3479E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7198E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0607E-004 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9054E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3705E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9660E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6868E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5922E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5915E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0719E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6204E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6978E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5445E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3812E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2825E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4400E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8242E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2407E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1603E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7987E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3399E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3431E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6730E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1756E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6364E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3766E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6179E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6280E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1933E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9643E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6982E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1796E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0445E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4848E-004 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2840E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8788E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1513E-004 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7811E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2029E-004 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7413E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0374E-004 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4582E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6674E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8401E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2330E-004 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9642E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3061E-004 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9147E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0658E-004 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0700E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6649E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6333E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5277E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9620E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1339E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.1005E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1123E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5511E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2818E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6078E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6729E-004 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4634E-003 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7032E-004 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7919E-003 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7375E-004 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6779E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0481E-004 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5886E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1903E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4352E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3243E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7490E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4110E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1110E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2532E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5335E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0587E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8864E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4534E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8104E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6453E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0267E-004 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2519E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1885E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7961E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2902E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8558E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1692E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7981E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5259E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0473E-004 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9439E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4382E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1534E-004 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6068E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1000E-004 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4735E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3455E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8908E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8211E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3249E-003 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2107E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4617E-003 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3644E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4199E-003 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3177E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8995E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7855E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3676E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5150E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3173E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3081E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9154E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9029E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8972E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3063E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2295E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4044E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1530E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7976E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8082E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1117E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9000E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0465E-003 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4953E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5434E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2758E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2690E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5333E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9851E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9915E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5702E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5482E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1858E-004 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5120E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0848E-004 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2446E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4774E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4291E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2389E-004 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4853E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6145E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4368E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2215E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1796E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5456E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4336E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8360E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4009E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4868E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1699E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4997E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4067E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4224E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9975E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9790E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0184E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3553E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7494E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0590E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7120E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6898E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9750E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5670E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9895E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2256E-003 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7151E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0438E-003 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6265E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6953E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9810E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9042E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7503E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0544E-004 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4566E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3966E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2629E-003 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2558E-004 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3923E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2355E-004 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6551E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9898E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3469E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4135E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2354E-003 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8275E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3968E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7651E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3739E-004 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4611E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1655E-004 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5850E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4693E-004 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8090E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8771E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0145E-003 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6876E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2234E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9792E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8410E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0132E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4999E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6872E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7148E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5201E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3619E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2707E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9451E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8561E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0354E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1582E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5852E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3723E-004 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0247E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1691E-004 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7519E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5060E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1863E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8744E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2992E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0360E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7783E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7817E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4352E-004 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1989E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4930E-004 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0363E-004 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5247E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6084E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2025E-004 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3078E-004 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0063E-004 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3620E-004 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0767E-004 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2024E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5078E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9857E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6605E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7648E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4375E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3277E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7119E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0355E-004 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9366E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6793E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4750E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9799E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5168E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0745E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9447E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6788E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7598E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6020E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6247E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3050E-004 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9594E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3749E-004 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3583E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2011E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1450E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.1045E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.9995E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.5797E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.4416E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.3810E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.2296E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5740E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.5211E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.1295E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.5244E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.6965E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.6584E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.3397E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.6811E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.4696E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4619E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.5896E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.2950E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.4277E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.5933E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2582E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9638E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.2283E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.7542E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.6346E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.2967E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.4489E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.5942E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2092E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9628E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.2283E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.7542E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9726.67237 | 11672.00685 | 0.80065 | 0.96077 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 31.55733 | 1.41187E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 9091.75824 | 10910.10989 | 0.25521 | 0.30625 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70000 | 1.50390E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 27721.31760 | 33265.58112 | 1.77883 | 2.13459 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 32.10000 | 1.41196E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 26246.19981 | 31495.43977 | 0.62085 | 0.74502 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -10.70000 | 1.50390E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 32.10000 | 1.41196E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 117575.91697 | 141091.10036 | 2.87384 | 3.44861 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14778.81 | 0.96077 | 0.96077 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 10946.56 | 0.30625 | 0.30625 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 40719.37 | 2.13459 | 2.13459 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 35512.46 | 0.74502 | 0.74502 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96077 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.13459 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.44861 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 3.44861 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 141091.09646 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 141091.10036 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96077 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96077 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96077 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96077 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96077 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.96077 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.13459 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.13459 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.13459 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.13459 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.13459 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.13459 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.96077 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.13459 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96077 |
26 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96077 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1063.73017 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96077 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96077 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96077 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96077 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96077 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48039 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64051 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18831.41000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9415.70500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78451 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78451 |
39 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18831.41000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25947.69578 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
43 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25947.69578 |
44 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.13459 |
45 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.13459 |
46 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2284.11228 |
47 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.13459 |
48 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.13459 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.13459 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.40883 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.13459 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.06730 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.42306 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 53006.95000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 26503.47500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
58 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 53006.95000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 76594.73720 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 76594.73720 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 18085.4 | 13.10 | 12.80 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 51347.8 | 12.58 | 12.29 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2692912284 | 0.2396026389 | Pass | Pass | 0.3671307662 | 0.8717764137 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5516243819 | 0.5192281290 | Pass | Pass | 0.5803815484 | 0.6931500682 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.5936749825E-005 | 9.4199826334E-005 | Pass | Pass | 2.6424447955E-002 | 2.0952813057E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8507.08 | 514.51 | 0.00 | 53.11 | 207.39 | 9282.17 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.133 | 0.136 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.056 | 0.056 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.199 | 0.204 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.052 | 0.053 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.199 | 0.204 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.3624_SHGC_WEST_0.36 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.059 | 0.361 | 0.361 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.3624_SHGC_WEST_0.36 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.059 | 0.361 | 0.361 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.3624_SHGC_NORTH_0.36 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.059 | 0.361 | 0.361 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.3624_SHGC_NORTH_0.36 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.059 | 0.361 | 0.361 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 3.810 | 0.555 | 0.552 | |||||||||||||||||
North Total or Average | 6.51 | 2.059 | 0.361 | 0.361 | |||||||||||||||||
Non-North Total or Average | 79.53 | 3.953 | 0.571 | 0.568 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.0858 | 236.88 | 1441.60 | LightsWired | LTG_SCH_OFFICE | 47.92 | 168.00 | 38.84 | 0.0000 | Y | 10.51 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 23.69 | 0.0000 | Y | 41.42 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.1969 | 3204.84 | 10245.50 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 21.33 | 0.0000 | Y | 41.02 |
Interior Lighting Total | 4.3435 | 4835.13 | 21001.18 | 92.95 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1441.60 | 418.06 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1441.60 | 144.16 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 93.17 | AstronomicalClock | - | 42.43 | 42.43 | 0.74 | |
EXTERIOR_LIGHTS_B | 4307.58 | AstronomicalClock | - | 83.64 | 63.04 | 50.97 | |
EXTERIOR_LIGHTS_C | 1091.85 | AstronomicalClock | - | 83.64 | 49.20 | 10.08 | |
Exterior Lighting Total | 5492.60 | 61.80 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18831.41 | 14773.43 | 4057.98 | 0.78 | 4.32 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 53006.95 | 37162.11 | 15844.84 | 0.70 | 3.92 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 18085.4 | 13.10 | 12.80 | ||||
PSZ-FINE STORAGE COOLING COIL | 51347.8 | 12.58 | 12.29 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 141091.10 | 0.81 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25947.70 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 76594.74 | 0.81 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.45 | 320.41 | 92.91 | 1.00 | 3.30 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1063.73 | 1107.16 | 1.00 | 1.41 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.13 | 2284.11 | 1070.05 | 1.00 | 1.31 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.54 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9726.67 | 11672.01 | 49.27 | 0.801 | 0.961 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 23.90 | 23.90 | 0.00846 | 31.56 | 0.01412 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 27721.32 | 33265.58 | 23.87 | 1.779 | 2.135 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 26.70 | 26.70 | 0.00886 | 32.10 | 0.01412 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 0.00 | 32.29 | 0.01419 | 32.10 | 0.01412 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9091.76 | 10910.11 | 46.06 | 0.255 | 0.306 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00747 | -10.70 | 0.00150 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 26246.20 | 31495.44 | 22.60 | 0.621 | 0.745 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00617 | -10.70 | 0.00150 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 117575.92 | 141091.10 | 44.02 | 2.874 | 3.449 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00445 | -10.70 | 0.00150 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.96 | 0.96 | 0.31 | 0.31 | 0.9608 | 0.9608 | 0.9608 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.13 | 2.13 | 0.75 | 0.75 | 2.1346 | 2.1346 | 2.1346 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 141091.096 | 141091.096 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 141091.10 | 141091.10 | 3.448611 | 10.00 | 6.34 | 0.00444628 | 43.33 | 22.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 10.00 | 0.00444628 | 58.5503 | 141091.10 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 18831.410 | 14773.429 | 0.960770 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 9415.70 | 7995.12 | 0.640513 | 25.63 | 17.42 | 0.00906175 | 12.00 | 11.25 | 0.00800000 | 31.66 | 0.01411884 | 23.01 | 15.9692 | 23.90 | 0.00845889 | 45.7950 | 9721.85 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25947.696 | 25947.696 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25947.70 | 25947.70 | 0.960775 | 17.67 | 12.43 | 0.00683523 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 10.6461 | 21.10 | 0.00747043 | 48.0212 | 9091.76 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 53006.950 | 37162.113 | 2.134590 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 26503.47 | 20934.90 | 1.423060 | 28.64 | 19.10 | 0.00990631 | 12.00 | 11.25 | 0.00800000 | 32.10 | 0.01411964 | 23.13 | 29.8449 | 26.70 | 0.00885977 | 40.5828 | 27719.74 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 76594.737 | 76594.737 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 76594.74 | 76594.74 | 2.134590 | 10.33 | 7.46 | 0.00523817 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.8966 | 15.56 | 0.00616571 | 56.2406 | 26246.20 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 141091.096 | 141091.096 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 3.448611 | 4.15073129 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 141091.10 | 141091.10 | 1.0000 | 4.15073129 | 3.448611 | 10.00 | 6.34 | 0.00444628 | 21246.1 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 141091.10 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 10.00 | 0.00444628 | 10.00 | 0.00444628 | 58.5503 | 141091.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18831.410 | 14773.429 | 0.960770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6853 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.960775 | 1.15638368 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | Sensible | 9415.70 | 7995.12 | 1.0000 | 0.77091863 | 0.640513 | 25.63 | 17.42 | 0.00906175 | 48843.7 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9415.70 | 31.66 | 0.01411884 | 23.01 | 0.10228460 | 15.9692 | 23.90 | 0.00845889 | 23.90 | 0.00845889 | 45.7950 | 9721.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25947.696 | 25947.696 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.960775 | 1.15638368 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 25947.70 | 25947.70 | 1.0000 | 1.15638368 | 0.960775 | 17.67 | 12.43 | 0.00683523 | 35074.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25947.70 | -10.70 | 0.00150390 | -10.70 | 0.10228460 | 10.6461 | 21.05 | 0.00747043 | 21.10 | 0.00747043 | 48.0212 | 9091.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 53006.950 | 37162.113 | 2.134590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2553 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.134590 | 2.56918189 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 26503.47 | 20934.90 | 1.0000 | 1.71278787 | 1.423060 | 28.64 | 19.10 | 0.00990631 | 54082.5 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26503.47 | 32.10 | 0.01411964 | 23.13 | 0.42471127 | 29.8449 | 26.70 | 0.00885977 | 26.70 | 0.00885977 | 40.5828 | 27719.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 76594.737 | 76594.737 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.134590 | 2.56918189 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 76594.74 | 76594.74 | 1.0000 | 2.56918189 | 2.134590 | 10.33 | 7.46 | 0.00523817 | 23582.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76594.74 | -10.70 | 0.00150390 | -10.70 | 0.42471127 | 19.8966 | 15.56 | 0.00616571 | 15.56 | 0.00616571 | 56.2406 | 26246.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 0.96 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 2.13 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
ZONE1 OFFICE | ZONE1_OFFICE_DCV | 0.002360 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
ZONE2 FINE STORAGE | ZONE2_FINE_STORAGE_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2895.33 | 2501.00 | 1899.17 |
ZONE2 FINE STORAGE | 3197.17 | 3223.83 | 2847.00 |
ZONE3 BULK STORAGE | 3289.17 | 3411.17 | 3119.50 |
Facility | 3478.17 | 3485.67 | 3211.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 24.50 | 0.50 | 13.00 | 0.50 |
ZONE2 FINE STORAGE | 217.33 | 39.83 | 16.17 | 0.83 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 234.67 | 40.33 | 25.17 | 1.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.568 | 0.374 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.494 | 0.119 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.145 | 0.000 | 0.283 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.072 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.474 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2047643.28 | 0.00 | 2047643.28 | 1737557.95 | 3785201.22 | 2577844.23 | 5699.76 | 2426.84 | 633.40 | 0.10 |
ZONE2 FINE STORAGE | 5261722.46 | 0.00 | 5261722.46 | 3337742.01 | 8599464.47 | 13393694.68 | 5709.75 | 2710.42 | 339.83 | 8.96 |
ZONE3 BULK STORAGE | 0.00 | 52978995.44 | 52978995.44 | 38154454.61 | 91133450.05 | 30805497.77 | 7231.90 | 81.89 | 1446.21 | 4981.50 |
Total Facility | 7309365.73 | 52978995.44 | 60288361.17 | 43229754.57 | 0.10E+09 | 46777036.68 | 8020.88 | 2951.33 | 2189.88 | 4981.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1564 | 0.0000 | 0.1564 | 0.1035 | 0.2599 | 0.0952 | 575.86 | 2426.84 | 633.30 |
ZONE2 FINE STORAGE | 0.3996 | 0.0000 | 0.3996 | 0.0970 | 0.4965 | 0.4247 | 594.63 | 2710.42 | 330.95 |
ZONE3 BULK STORAGE | 0.0000 | 2.6615 | 2.6615 | 1.4218 | 4.0833 | 0.9768 | 2841.23 | 36.83 | 757.94 |
Total Facility | 0.5560 | 2.6615 | 3.2175 | 1.6222 | 4.8397 | 1.4967 | 2896.88 | 2906.27 | 1493.34 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2966299.76 | 0.00 | 2966299.76 | 2577844.23 | 5698.60 | 0.00 | 3061.40 | 0.10 |
PSZ-FINE STORAGE | 7622338.95 | 0.00 | 7622338.95 | 13393694.68 | 5703.75 | 0.58 | 3055.67 | 8.96 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2266 | 0.0000 | 0.2266 | 0.0952 | 574.70 | 0.00 | 3061.30 |
PSZ-FINE STORAGE | 0.5788 | 0.0000 | 0.5788 | 0.4247 | 588.63 | 0.58 | 3046.79 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 316.11 | 321.51 | 0.00 | 0.00 | 0.00 | 2426.42 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 239.08 | 126.68 | 0.00 | 0.00 | 0.00 | 2700.72 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.9743 | 0.5293 | 0.0000 | 0.0000 | 0.0000 | 0.1427 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 1.4300 | 0.9051 | 0.0000 | 0.0000 | 0.0000 | 0.6154 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 430 |
Defaulted Fields | 389 |
Fields with Defaults | 1172 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 367.73 | 1606.07 | 26-MAR-14:00 | 32666.82 | 04-AUG-14:20 |
Electricity:Building | 231.63 | 1123.07 | 19-MAR-14:20 | 19515.73 | 27-DEC-16:00 |
Electricity:Zone:ZONE1 OFFICE | 39.68 | 585.18 | 12-FEB-16:10 | 2643.62 | 02-JAN-16:40 |
Electricity:SpaceType:GENERAL | 229.46 | 1123.07 | 19-MAR-14:20 | 19515.73 | 27-DEC-16:00 |
InteriorLights:Electricity | 92.95 | 653.19 | 19-MAR-14:20 | 9480.56 | 27-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.51 | 115.30 | 12-FEB-16:10 | 808.57 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 92.95 | 653.19 | 19-MAR-14:20 | 9480.56 | 27-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 92.95 | 653.19 | 19-MAR-14:20 | 9480.56 | 27-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.51 | 115.30 | 12-FEB-16:10 | 808.57 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 92.95 | 653.19 | 19-MAR-14:20 | 9480.56 | 27-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 41.43 | 256.14 | 01-JAN-11:50 | 4210.22 | 08-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 41.43 | 256.14 | 01-JAN-11:50 | 4210.22 | 08-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 41.43 | 256.14 | 01-JAN-11:50 | 4210.22 | 08-DEC-16:00 |
Electricity:Zone:ZONE3 BULK STORAGE | 150.53 | 281.75 | 01-JAN-09:50 | 13000.56 | 15-AUG-16:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 41.02 | 281.75 | 01-JAN-09:50 | 4502.34 | 08-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 41.02 | 281.75 | 01-JAN-09:50 | 4502.34 | 08-DEC-16:00 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 30.65 | 0.00 | 17-JAN-18:10 | 4569.13 | 04-AUG-14:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 2.17 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-JUL-15:30 |
Ventilation (simple):Fans:Electricity | 2.17 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-JUL-15:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 2.17 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-JUL-15:30 |
ElectricityPurchased:Facility | 367.73 | 1606.07 | 26-MAR-14:00 | 32666.82 | 04-AUG-14:20 |
ElectricityPurchased:Plant | 367.73 | 1606.07 | 26-MAR-14:00 | 32666.82 | 04-AUG-14:20 |
Cogeneration:ElectricityPurchased | 367.73 | 1606.07 | 26-MAR-14:00 | 32666.82 | 04-AUG-14:20 |
General:Cogeneration:ElectricityPurchased | 367.73 | 1606.07 | 26-MAR-14:00 | 32666.82 | 04-AUG-14:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 367.73 | 1606.07 | 26-MAR-14:00 | 32666.82 | 04-AUG-14:20 |
ElectricityNet:Plant | 367.73 | 1606.07 | 26-MAR-14:00 | 32666.82 | 04-AUG-14:20 |
Cogeneration:ElectricityNet | 367.73 | 1606.07 | 26-MAR-14:00 | 32666.82 | 04-AUG-14:20 |
General:Cogeneration:ElectricityNet | 367.73 | 1606.07 | 26-MAR-14:00 | 32666.82 | 04-AUG-14:20 |
Electricity:HVAC | 48.99 | 0.00 | 17-JAN-18:10 | 14123.52 | 19-JUN-12:00 |
General:Fans:Electricity | 28.48 | 0.00 | 17-JAN-18:10 | 2873.30 | 06-FEB-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 20.52 | 0.00 | 01-JAN-00:10 | 11987.51 | 19-JUN-12:00 |
General:Cooling:Electricity | 20.52 | 0.00 | 01-JAN-00:10 | 11987.51 | 19-JUN-12:00 |
ExteriorLights:Electricity | 61.80 | 0.00 | 01-JAN-07:30 | 5492.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.80 | 0.00 | 01-JAN-07:30 | 5492.60 | 01-JAN-06:10 |
Electricity:Plant | 25.31 | 483.00 | 03-FEB-06:10 | 2461.17 | 09-FEB-13:00 |
WaterSystems:Electricity | 25.31 | 483.00 | 03-FEB-06:10 | 2461.17 | 09-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 25.31 | 483.00 | 03-FEB-06:10 | 2461.17 | 09-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 393.77 | 0.00 | 17-JAN-18:10 | 207619.42 | 06-FEB-00:10 |
NaturalGas:HVAC | 393.77 | 0.00 | 17-JAN-18:10 | 207619.42 | 06-FEB-00:10 |
Heating:NaturalGas | 393.77 | 0.00 | 17-JAN-18:10 | 207619.42 | 06-FEB-00:10 |
General:Heating:NaturalGas | 393.77 | 0.00 | 17-JAN-18:10 | 207619.42 | 06-FEB-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-AUG-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-AUG-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-AUG-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-AUG-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-AUG-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-AUG-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-AUG-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-AUG-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 769.36 | 0.00 | 17-JAN-18:10 | 333010.05 | 06-FEB-00:10 |
EnergyTransfer:Building | 372.51 | 0.00 | 17-JAN-18:10 | 166958.55 | 06-FEB-00:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 50.42 | 0.00 | 01-JAN-00:40 | 24766.26 | 06-FEB-07:10 |
Heating:EnergyTransfer | 289.82 | 0.00 | 17-JAN-18:10 | 166958.55 | 06-FEB-00:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 24.76 | 0.00 | 01-JAN-00:40 | 24766.26 | 06-FEB-07:10 |
General:Heating:EnergyTransfer | 289.82 | 0.00 | 17-JAN-18:10 | 166958.55 | 06-FEB-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 24.76 | 0.00 | 01-JAN-00:40 | 24766.26 | 06-FEB-07:10 |
Cooling:EnergyTransfer | 82.70 | 0.00 | 01-JAN-00:10 | 28371.73 | 18-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 25.67 | 0.00 | 01-JAN-00:10 | 10960.36 | 19-JUN-12:00 |
General:Cooling:EnergyTransfer | 82.70 | 0.00 | 01-JAN-00:10 | 28371.73 | 18-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 25.67 | 0.00 | 01-JAN-00:10 | 10960.36 | 19-JUN-12:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 114.57 | 0.00 | 01-JAN-00:40 | 37529.26 | 06-FEB-04:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 57.54 | 0.00 | 01-JAN-00:40 | 37529.26 | 06-FEB-04:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 57.54 | 0.00 | 01-JAN-00:40 | 37529.26 | 06-FEB-04:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 57.03 | 0.00 | 01-JAN-00:10 | 19942.53 | 10-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 57.03 | 0.00 | 01-JAN-00:10 | 19942.53 | 10-JUL-13:40 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 207.52 | 0.00 | 02-JAN-10:50 | 130212.35 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 207.52 | 0.00 | 02-JAN-10:50 | 130212.35 | 06-FEB-01:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 207.52 | 0.00 | 02-JAN-10:50 | 130212.35 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 396.85 | 0.00 | 17-JAN-18:10 | 166051.50 | 06-FEB-00:10 |
HeatingCoils:EnergyTransfer | 301.88 | 0.00 | 17-JAN-18:10 | 166051.50 | 06-FEB-00:10 |
CoolingCoils:EnergyTransfer | 94.97 | 0.00 | 01-JAN-00:10 | 50543.97 | 04-AUG-14:20 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 24.755 | -25.668 | 0.000 | 0.000 | 9.924 | 10.511 | 29.165 | 10.871 | 0.000 | 0.924 | 0.000 | 0.000 | -6.542 | 0.000 | -20.669 | -33.270 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 57.542 | -57.025 | 0.000 | 0.000 | 24.775 | 41.425 | 0.000 | 51.024 | 0.000 | 0.438 | 0.002 | 0.000 | -16.369 | 0.000 | -36.453 | -65.356 |
ZONE3 BULK STORAGE | 207.520 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 60.602 | 41.015 | 107.344 | 508.532 | 0.000 | 9.047 | 0.002 | 0.000 | -124.169 | 0.000 | -441.035 | -368.857 |
Total Facility | 207.520 | 0.000 | 82.297 | -82.693 | 0.000 | 0.000 | 95.302 | 92.951 | 136.508 | 570.427 | 0.000 | 10.409 | 0.004 | 0.000 | -147.081 | 0.000 | -498.157 | -467.483 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 23-SEP-07:02 | 0.00 | 0.00 | 0.00 | -23247.99 | 0.00 | 0.00 | 801.53 | 740.41 | 1835.05 | 0.00 | 0.00 | 0.00 | 20341.81 | 0.00 | -157.08 | 0.00 | -313.73 | 0.00 |
ZONE2 FINE STORAGE | 20-AUG-12:23 | 0.00 | 0.00 | 0.00 | -48768.93 | 0.00 | 0.00 | 0.00 | 256.14 | 0.00 | 10180.09 | 0.00 | 33.85 | 38298.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-JUL-06:01 | 0.00 | 0.00 | 0.00 | -52206.18 | 0.00 | 0.00 | 1144.05 | 4880.63 | 2967.56 | 12017.62 | 0.00 | 0.00 | 34705.38 | 0.00 | 0.00 | 0.00 | -3509.06 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 06-FEB-06:42 | 0.00 | 0.00 | 26997.23 | 0.00 | 0.00 | 0.00 | 149.12 | 241.53 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -921.95 | 0.00 | -2856.58 | -24159.87 |
ZONE2 FINE STORAGE | 06-FEB-02:62 | 0.00 | 0.00 | 78721.26 | 0.00 | 0.00 | 0.00 | 0.00 | 512.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2247.49 | 0.00 | -7426.09 | -69559.95 |
ZONE3 BULK STORAGE | 06-FEB-01:00 | 130211.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13473.88 | 0.00 | -107209.57 | -12141.65 |
Total Facility | 06-FEB-00:02 | 124956.23 | 0.00 | 102106.61 | 0.00 | 0.00 | 0.00 | 0.00 | 1264.80 | 2519.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25624.33 | 0.00 | -112223.58 | -92999.63 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9608 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9608 | 0.1065 | 1.0000 | Not calculated | 0.1023 | 0.1065 | ||
PSZ-FINE STORAGE | 2.1346 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.1346 | 0.1990 | 1.0000 | Not calculated | 0.4247 | 0.1990 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9608 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9608 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1065 | ||
PSZ-FINE STORAGE | 2.1346 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.1346 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1990 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.002360 | 12.7487 | 0.000305 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.002360 | 12.75 | 0.000305 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9608 | 0.9608 | 0.9608 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1346 | 2.1346 | 2.1346 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9608 | 0.9608 | 0.9608 | 0.9608 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.1346 | 2.1346 | 2.1346 | 2.1346 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9608 | 0.9608 | 0.9608 | No | 0.1023 | 0.3340 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1346 | 2.1346 | 2.1346 | No | 0.4247 | 0.5701 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9608 | 0.9608 | 0.9608 | 0.9608 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.1346 | 2.1346 | 2.1346 | 2.1346 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 25.17 |
Number of hours cooling loads not met | 1.33 |
Number of hours not met | 26.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 393.77 | 207619.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 20.52 | 11987.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 92.95 | 9480.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.80 | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 2.17 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 28.48 | 2873.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.31 | 2461.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 367.73 |
Natural Gas | 0.00 | 393.77 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 761.50 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 19.22 |
Space Heating | 0.00 |
Space Cooling | 4.24 |
Fans (All) | 6.34 |
Service Water Heating | 5.24 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 76.05 |
Subtotal | 76.05 |
Natural Gas [MJ/m2] | |
Space Heating | 81.44 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 81.44 |
Subtotal | 81.44 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.21 |
Space Heating | 51.71 |
Space Cooling | 2.69 |
Fans (All) | 4.02 |
Service Water Heating | 3.32 |
Receptacle Equipment | 17.93 |
Miscellaneous | 8.12 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2499. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7505.50 | 1254.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7070.33 | 1689.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6597.67 | 1800.17 | 362.17 | 0.00 | 0.00 |
Min | 6597.67 | 1254.50 | 0.00 | 0.00 | 0.00 |
Max | 7505.50 | 1800.17 | 362.17 | 0.00 | 0.00 |
Average | 7057.83 | 1581.44 | 120.72 | 0.00 | 0.00 |
Sum | 21173.50 | 4744.33 | 362.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 32965.17 | 61.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 62841.00 | 19878.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 140503.17 | 39435.50 | 11254.33 | 0.00 | 0.00 |
Min | 32965.17 | 61.83 | 0.00 | 0.00 | 0.00 |
Max | 140503.17 | 39435.50 | 11254.33 | 0.00 | 0.00 |
Average | 78769.78 | 19791.78 | 3751.44 | 0.00 | 0.00 |
Sum | 236309.33 | 59375.33 | 11254.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 6993.83 | 1766.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 6505.67 | 2254.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6366.50 | 2272.83 | 120.67 | 0.00 | 0.00 |
Min | 6366.50 | 1766.17 | 0.00 | 0.00 | 0.00 |
Max | 6993.83 | 2272.83 | 120.67 | 0.00 | 0.00 |
Average | 6622.00 | 2097.78 | 40.22 | 0.00 | 0.00 |
Sum | 19866.00 | 6293.33 | 120.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31160.33 | 1866.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 58511.50 | 24207.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 135162.33 | 51465.67 | 4565.00 | 0.00 | 0.00 |
Min | 31160.33 | 1866.67 | 0.00 | 0.00 | 0.00 |
Max | 135162.33 | 51465.67 | 4565.00 | 0.00 | 0.00 |
Average | 74944.72 | 25846.61 | 1521.67 | 0.00 | 0.00 |
Sum | 224834.17 | 77539.83 | 4565.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:05
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6468744.74 | 2661.50 | 14-JAN-08:05 | -8.3 | -9.2 | 0.492126E+09 | 603.89 | 24-JAN-08:20 | 10.20 | 10.20 |
February | 5846508.02 | 2195.68 | 25-FEB-08:05 | -3.6 | -6.4 | 0.452733E+09 | 603.60 | 18-FEB-08:20 | -3.6 | -6.4 |
March | 19363066.22 | 2079.54 | 23-MAR-07:05 | -2.9 | -5.5 | 0.534715E+09 | 715.71 | 27-MAR-15:00 | 22.20 | 16.34 |
April | 0.205764E+09 | 2420.23 | 10-APR-15:00 | 20.00 | 11.58 | 0.533935E+09 | 768.98 | 08-APR-13:20 | 20.00 | 11.58 |
May | 0.154085E+10 | 17335.70 | 30-MAY-07:02 | 23.17 | 16.07 | 0.636594E+09 | 879.39 | 30-MAY-07:10 | 23.17 | 16.07 |
June | 0.497407E+10 | 22150.98 | 03-JUN-07:02 | 15.18 | 10.91 | 0.666720E+09 | 879.41 | 19-JUN-07:10 | 27.57 | 23.75 |
July | 0.619658E+10 | 18629.10 | 11-JUL-06:02 | 20.87 | 15.63 | 0.642772E+09 | 879.42 | 29-JUL-07:10 | 22.98 | 19.73 |
August | 0.684051E+10 | 20507.16 | 25-AUG-07:02 | 18.48 | 12.49 | 0.693984E+09 | 879.42 | 22-AUG-07:10 | 18.48 | 12.49 |
September | 0.420831E+10 | 23259.83 | 23-SEP-07:02 | 12.88 | 7.59 | 0.639271E+09 | 879.39 | 01-SEP-07:10 | 12.88 | 7.59 |
October | 0.162898E+10 | 17863.53 | 14-OCT-07:03 | 14.50 | 13.58 | 0.615378E+09 | 858.00 | 14-OCT-07:10 | 14.50 | 13.58 |
November | 35232336.86 | 2128.76 | 24-NOV-08:05 | -3.5 | -5.0 | 0.489417E+09 | 768.96 | 04-NOV-15:00 | -3.5 | -5.0 |
December | 6719601.96 | 2222.17 | 22-DEC-08:05 | -4.1 | -6.4 | 0.492182E+09 | 603.74 | 05-DEC-08:20 | -4.1 | -6.4 |
Annual Sum or Average | 0.256687E+11 | 0.688983E+10 | ||||||||
Minimum of Months | 5846508.02 | 2079.54 | -8.3 | -9.2 | 0.452733E+09 | 603.60 | -4.1 | -6.4 | ||
Maximum of Months | 0.684051E+10 | 23259.83 | 23.17 | 16.07 | 0.693984E+09 | 879.42 | 27.57 | 23.75 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103617E+10 | 5022.42 | 26-JAN-11:30 | 3.60 | 0.17 | 0.655407E+09 | 928.80 | 17-JAN-14:50 | 3.60 | 0.17 |
February | 0.116974E+10 | 7644.90 | 25-FEB-09:05 | -2.0 | -5.5 | 0.602647E+09 | 889.32 | 24-FEB-15:39 | -2.0 | -5.5 |
March | 0.261862E+10 | 7220.44 | 17-MAR-10:35 | -1.1 | -2.3 | 0.780783E+09 | 1288.46 | 27-MAR-15:00 | 22.20 | 16.34 |
April | 0.213947E+10 | 6069.86 | 12-APR-07:03 | 4.60 | -0.6 | 0.952702E+09 | 1827.74 | 10-APR-14:00 | 4.60 | -0.6 |
May | 0.238267E+10 | 27124.53 | 31-MAY-17:22 | 22.25 | 19.08 | 0.146632E+10 | 2246.87 | 30-MAY-15:00 | 22.25 | 19.08 |
June | 0.797045E+10 | 40511.23 | 25-JUN-14:43 | 26.70 | 22.72 | 0.190401E+10 | 2246.95 | 19-JUN-12:09 | 26.70 | 22.72 |
July | 0.136599E+11 | 46631.04 | 04-JUL-16:23 | 25.55 | 18.12 | 0.185449E+10 | 2246.97 | 07-JUL-14:09 | 32.70 | 23.73 |
August | 0.148001E+11 | 48769.49 | 20-AUG-12:23 | 27.25 | 15.63 | 0.200157E+10 | 2246.96 | 02-AUG-13:09 | 27.25 | 15.63 |
September | 0.564772E+10 | 46906.32 | 04-SEP-14:13 | 25.73 | 18.51 | 0.175907E+10 | 2246.93 | 05-SEP-13:00 | 26.10 | 21.22 |
October | 0.235752E+10 | 6259.44 | 28-OCT-07:10 | 4.27 | 1.31 | 0.139769E+10 | 2246.81 | 05-OCT-14:09 | 4.27 | 1.31 |
November | 0.189100E+10 | 4871.92 | 20-NOV-11:00 | 4.40 | 2.31 | 0.758688E+09 | 1476.00 | 04-NOV-13:09 | 4.40 | 2.31 |
December | 0.135374E+10 | 5683.17 | 07-DEC-09:15 | 2.07 | -0.8 | 0.656580E+09 | 891.68 | 19-DEC-14:50 | 10.10 | 4.89 |
Annual Sum or Average | 0.570271E+11 | 0.147899E+11 | ||||||||
Minimum of Months | 0.103617E+10 | 4871.92 | -2.0 | -5.5 | 0.602647E+09 | 889.32 | -2.0 | -5.5 | ||
Maximum of Months | 0.148001E+11 | 48769.49 | 27.25 | 22.72 | 0.200157E+10 | 2246.97 | 32.70 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -9.6 | -11.5 | 0.698135E+09 | 1072.43 | 17-JAN-15:09 | 10.50 | 5.04 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 | -4.2 | 0.623814E+09 | 1019.57 | 18-FEB-15:30 | 6.70 | 3.06 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.52 | 4.35 | 0.912267E+09 | 1699.78 | 27-MAR-15:00 | 22.20 | 16.34 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 | 0.142743E+10 | 2746.05 | 10-APR-14:50 | 20.10 | 11.41 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 | 0.264032E+10 | 5142.98 | 31-MAY-14:39 | 26.47 | 19.78 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.59 | 0.454462E+10 | 8403.20 | 19-JUN-12:20 | 36.13 | 24.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.29 | 0.516232E+10 | 7848.94 | 07-JUL-12:20 | 33.53 | 23.31 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 | 0.562039E+10 | 7933.88 | 24-AUG-15:39 | 33.90 | 19.89 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 | 0.429009E+10 | 6949.07 | 01-SEP-14:20 | 30.93 | 17.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 | 0.262939E+10 | 4632.68 | 04-OCT-14:30 | 24.15 | 19.04 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 | 0.116003E+10 | 2612.63 | 04-NOV-13:30 | 17.25 | 12.82 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.97 | 2.86 | 0.689311E+09 | 1091.36 | 20-DEC-11:00 | 8.90 | 5.16 |
Annual Sum or Average | 0.00 | 0.303981E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 0.623814E+09 | 1019.57 | 6.70 | 3.06 | ||
Maximum of Months | 0.00 | 0.00 | 23.90 | 21.46 | 0.562039E+10 | 8403.20 | 36.13 | 24.17 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.598931E+10 | 26702.12 | 02-JAN-07:13 | -11.5 |
February | 0.576127E+10 | 26997.18 | 06-FEB-06:42 | -13.2 |
March | 0.383592E+10 | 26355.40 | 22-MAR-06:01 | -2.8 |
April | 0.138794E+10 | 26250.67 | 03-APR-06:01 | 2.38 |
May | 0.236060E+09 | 25681.75 | 01-MAY-06:02 | 7.67 |
June | 66707500.40 | 1711.32 | 23-JUN-06:05 | 21.38 |
July | 22113175.71 | 1716.64 | 11-JUL-06:04 | 20.87 |
August | 35365571.21 | 1816.35 | 23-AUG-06:05 | 19.18 |
September | 75407010.17 | 1622.78 | 11-SEP-06:15 | 12.43 |
October | 0.206325E+09 | 14895.48 | 31-OCT-06:03 | 5.68 |
November | 0.249626E+10 | 26388.19 | 24-NOV-07:01 | -4.3 |
December | 0.464307E+10 | 26348.46 | 22-DEC-07:01 | -4.9 |
Annual Sum or Average | 0.247557E+11 | |||
Minimum of Months | 22113175.71 | 1622.78 | -13.2 | |
Maximum of Months | 0.598931E+10 | 26997.18 | 21.38 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173092E+11 | 78661.37 | 02-JAN-00:02 | -10.7 |
February | 0.156660E+11 | 78721.24 | 06-FEB-02:62 | -13.4 |
March | 0.592651E+10 | 73016.31 | 22-MAR-05:01 | -2.3 |
April | 0.116924E+10 | 30139.70 | 05-APR-06:01 | 6.97 |
May | 78195867.01 | 911.43 | 23-MAY-07:00 | 16.10 |
June | 40275502.44 | 1100.22 | 24-JUN-06:04 | 22.30 |
July | 6517042.00 | 1494.73 | 10-JUL-06:05 | 26.20 |
August | 20909367.60 | 1306.50 | 17-AUG-06:03 | 25.78 |
September | 51543753.04 | 1094.39 | 02-SEP-06:03 | 21.70 |
October | 74057719.24 | 920.05 | 27-OCT-06:50 | 6.02 |
November | 0.484481E+10 | 71861.06 | 24-NOV-06:01 | -4.4 |
December | 0.123544E+11 | 77590.40 | 31-DEC-22:42 | -7.7 |
Annual Sum or Average | 0.575417E+11 | |||
Minimum of Months | 6517042.00 | 911.43 | -13.4 | |
Maximum of Months | 0.173092E+11 | 78721.24 | 26.20 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.703498E+11 | 112395.75 | 01-JAN-21:00 | -8.3 |
February | 0.674949E+11 | 130212.35 | 06-FEB-01:00 | -13.3 |
March | 0.164912E+11 | 72557.70 | 22-MAR-07:03 | -2.7 |
April | 0.233932E+09 | 13053.60 | 02-APR-05:55 | 3.30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.109106E+11 | 71993.66 | 23-NOV-01:55 | -2.8 |
December | 0.420403E+11 | 116283.52 | 31-DEC-21:52 | -7.2 |
Annual Sum or Average | 0.207521E+12 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.703498E+11 | 130212.35 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.958981E+09 | 808.57 | 02-JAN-16:40 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.840602E+09 | 797.02 | 15-FEB-16:00 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.916613E+09 | 773.04 | 16-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.854033E+09 | 747.53 | 21-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.847744E+09 | 747.36 | 08-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.822180E+09 | 738.73 | 29-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.818139E+09 | 746.04 | 15-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.854209E+09 | 754.05 | 16-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.855362E+09 | 769.35 | 27-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.868692E+09 | 781.97 | 06-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.903052E+09 | 808.57 | 06-NOV-16:49 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.971097E+09 | 808.57 | 01-DEC-16:30 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.105107E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.818139E+09 | 738.73 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.971097E+09 | 808.57 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.403217E+10 | 4167.54 | 09-JAN-15:00 | 0.00 | 0.00 |
February | 0.347317E+10 | 3998.24 | 02-FEB-15:00 | 0.00 | 0.00 |
March | 0.361538E+10 | 3656.54 | 16-MAR-08:09 | 0.00 | 0.00 |
April | 0.319521E+10 | 3552.60 | 06-APR-08:09 | 0.00 | 0.00 |
May | 0.313180E+10 | 3344.07 | 04-MAY-08:09 | 0.00 | 0.00 |
June | 0.305509E+10 | 3154.89 | 29-JUN-07:10 | 0.00 | 0.00 |
July | 0.301728E+10 | 3230.48 | 14-JUL-08:09 | 0.00 | 0.00 |
August | 0.327527E+10 | 3366.81 | 22-AUG-08:09 | 0.00 | 0.00 |
September | 0.328834E+10 | 3587.06 | 30-SEP-08:09 | 0.00 | 0.00 |
October | 0.350106E+10 | 3838.27 | 31-OCT-14:00 | 0.00 | 0.00 |
November | 0.366855E+10 | 4192.22 | 15-NOV-15:00 | 0.00 | 0.00 |
December | 0.417193E+10 | 4210.22 | 08-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.414253E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.301728E+10 | 3154.89 | 0.00 | 0.00 | |
Maximum of Months | 0.417193E+10 | 4210.22 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.395072E+10 | 4422.54 | 09-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.337257E+10 | 4106.55 | 02-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.352846E+10 | 3727.40 | 02-MAR-16:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.316518E+10 | 3124.37 | 06-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.314756E+10 | 2937.85 | 04-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.309845E+10 | 2763.20 | 29-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.306609E+10 | 2912.98 | 15-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.329083E+10 | 3075.81 | 16-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.324517E+10 | 3390.79 | 27-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.346107E+10 | 3783.65 | 31-OCT-14:00 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.359721E+10 | 4470.77 | 15-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.409217E+10 | 4502.34 | 08-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.410155E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.306609E+10 | 2763.20 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.409217E+10 | 4502.34 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.958981E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347023E+10 |
February | 0.127628E+10 | 0.840602E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335587E+10 |
March | 0.149825E+10 | 0.916613E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280349E+10 |
April | 0.138726E+10 | 0.854033E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5494881.80 | 0.162249E+10 |
May | 0.144276E+10 | 0.847744E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21522073.81 | 0.110074E+10 |
June | 0.144276E+10 | 0.822180E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148982E+09 | 0.572192E+09 |
July | 0.138726E+10 | 0.818139E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304563E+09 | 0.183564E+09 |
August | 0.149825E+10 | 0.854209E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379722E+09 | 0.252185E+09 |
September | 0.138726E+10 | 0.855362E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62068433.63 | 0.645721E+09 |
October | 0.138726E+10 | 0.868692E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1301970.42 | 0.138366E+10 |
November | 0.133177E+10 | 0.903052E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229677E+10 |
December | 0.138726E+10 | 0.971097E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298237E+10 |
Annual Sum or Average | 0.168137E+11 | 0.105107E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923655E+09 | 0.206693E+11 |
Minimum of Months | 0.127628E+10 | 0.818139E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183564E+09 |
Maximum of Months | 0.149825E+10 | 0.971097E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379722E+09 | 0.347023E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.403217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623195E+10 |
February | 0.300332E+10 | 0.347317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568806E+10 |
March | 0.352563E+10 | 0.361538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3566036.42 | 0.417437E+10 |
April | 0.326447E+10 | 0.319521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19124935.53 | 0.252069E+10 |
May | 0.339505E+10 | 0.313180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5519586.71 | 0.189483E+10 |
June | 0.339505E+10 | 0.305509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66412318.17 | 0.156888E+10 |
July | 0.326447E+10 | 0.301728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124891E+09 | 0.592137E+09 |
August | 0.352563E+10 | 0.327527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203849E+09 | 0.706148E+09 |
September | 0.326447E+10 | 0.328834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14812869.25 | 0.146210E+10 |
October | 0.326447E+10 | 0.350106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278347E+10 |
November | 0.313390E+10 | 0.366855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372674E+10 |
December | 0.326447E+10 | 0.417193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510408E+10 |
Annual Sum or Average | 0.395654E+11 | 0.414253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438176E+09 | 0.364534E+11 |
Minimum of Months | 0.300332E+10 | 0.301728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592137E+09 |
Maximum of Months | 0.352563E+10 | 0.417193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203849E+09 | 0.623195E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.395072E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31595701.82 | 0.430101E+11 |
February | 0.690763E+10 | 0.337257E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422167E+11 |
March | 0.810895E+10 | 0.352846E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674779E+09 | 0.246988E+11 |
April | 0.750829E+10 | 0.316518E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172262E+10 | 0.150834E+11 |
May | 0.780862E+10 | 0.314756E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466401E+09 | 0.118018E+11 |
June | 0.780862E+10 | 0.309845E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347413E+09 | 0.163968E+11 |
July | 0.750829E+10 | 0.306609E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24007409.77 | 0.109693E+11 |
August | 0.810895E+10 | 0.329083E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51487593.02 | 0.123733E+11 |
September | 0.750829E+10 | 0.324517E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3493916.35 | 0.175850E+11 |
October | 0.750829E+10 | 0.346107E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70368349.40 | 0.220786E+11 |
November | 0.720796E+10 | 0.359721E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51353459.25 | 0.248144E+11 |
December | 0.750829E+10 | 0.409217E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18428346.19 | 0.317664E+11 |
Annual Sum or Average | 0.910005E+11 | 0.410155E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346195E+10 | 0.272795E+12 |
Minimum of Months | 0.690763E+10 | 0.306609E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109693E+11 |
Maximum of Months | 0.810895E+10 | 0.409217E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172262E+10 | 0.430101E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 808.57 | 02-JAN-16:40 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 13157.49 | 02-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 797.02 | 15-FEB-16:00 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 14687.34 | 06-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 773.04 | 16-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 10574.40 | 22-MAR-07:00 |
April | 1680.92 | 01-APR-07:10 | 747.53 | 21-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 606.20 | 07-APR-12:00 | 6981.70 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 747.36 | 08-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.45 | 30-MAY-12:00 | 4856.02 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 738.73 | 29-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4393.25 | 19-JUN-12:00 | 4242.08 | 02-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 746.04 | 15-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3433.51 | 07-JUL-12:00 | 2032.28 | 05-JUL-06:02 |
August | 1680.92 | 01-AUG-07:10 | 754.05 | 16-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3451.82 | 24-AUG-16:03 | 3070.41 | 08-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 769.35 | 27-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2108.59 | 01-SEP-12:00 | 5088.56 | 11-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 781.97 | 06-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.53 | 25-OCT-11:10 | 6133.95 | 18-OCT-06:05 |
November | 1680.92 | 01-NOV-07:10 | 808.57 | 06-NOV-16:49 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9665.39 | 22-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 808.57 | 01-DEC-16:30 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 10007.66 | 22-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 738.73 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.28 | |||||
Maximum of Months | 1680.92 | 808.57 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 4393.25 | 14687.34 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 4167.54 | 09-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 9675.56 | 14-JAN-17:00 |
February | 3955.50 | 01-FEB-08:09 | 3998.24 | 02-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8955.33 | 06-FEB-01:00 |
March | 3955.50 | 01-MAR-08:09 | 3656.54 | 16-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.93 | 27-MAR-16:00 | 9131.46 | 22-MAR-07:00 |
April | 3955.50 | 01-APR-07:10 | 3552.60 | 06-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717.53 | 07-APR-17:00 | 4471.70 | 11-APR-04:00 |
May | 3955.50 | 01-MAY-07:10 | 3344.07 | 04-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.54 | 29-MAY-12:00 | 2515.75 | 03-MAY-06:40 |
June | 3955.50 | 01-JUN-07:10 | 3154.89 | 29-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1495.75 | 19-JUN-17:00 | 2580.21 | 06-JUN-15:10 |
July | 3955.50 | 01-JUL-07:10 | 3230.48 | 14-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1324.31 | 10-JUL-15:10 | 1129.18 | 15-JUL-08:00 |
August | 3955.50 | 01-AUG-07:10 | 3366.81 | 22-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2176.74 | 24-AUG-17:00 | 1471.55 | 20-AUG-06:00 |
September | 3955.50 | 01-SEP-07:10 | 3587.06 | 30-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.73 | 01-SEP-15:10 | 1943.25 | 23-SEP-07:00 |
October | 3955.50 | 02-OCT-07:10 | 3838.27 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4539.49 | 26-OCT-17:00 |
November | 3955.50 | 01-NOV-07:10 | 4192.22 | 15-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6295.08 | 23-NOV-01:53 |
December | 3955.50 | 01-DEC-08:09 | 4210.22 | 08-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 8751.28 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3154.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1129.18 | ||||
Maximum of Months | 3955.50 | 4210.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2176.74 | 9675.56 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4422.54 | 09-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3006.94 | 18-JAN-16:00 | 71076.61 | 14-JAN-17:00 |
February | 9097.65 | 01-FEB-08:09 | 4106.55 | 02-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 68319.43 | 06-FEB-01:00 |
March | 9097.65 | 01-MAR-08:09 | 3727.40 | 02-MAR-16:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16468.90 | 27-MAR-16:00 | 61129.56 | 22-MAR-07:05 |
April | 9097.65 | 01-APR-07:10 | 3124.37 | 06-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19286.19 | 07-APR-14:00 | 27507.80 | 12-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 2937.85 | 04-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6808.52 | 09-MAY-14:00 | 15238.50 | 24-MAY-13:00 |
June | 9097.65 | 01-JUN-07:10 | 2763.20 | 29-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9576.35 | 19-JUN-10:52 | 19232.00 | 30-JUN-16:00 |
July | 9097.65 | 01-JUL-07:10 | 2912.98 | 15-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 865.54 | 07-JUL-11:00 | 15056.50 | 11-JUL-08:00 |
August | 9097.65 | 01-AUG-07:10 | 3075.81 | 16-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2269.48 | 24-AUG-15:00 | 17524.83 | 19-AUG-09:00 |
September | 9097.65 | 01-SEP-07:10 | 3390.79 | 27-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1073.22 | 14-SEP-14:00 | 19886.03 | 23-SEP-09:00 |
October | 9097.65 | 02-OCT-07:10 | 3783.65 | 31-OCT-14:00 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5819.03 | 25-OCT-14:00 | 36500.82 | 28-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 4470.77 | 15-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2996.45 | 26-NOV-15:10 | 42211.62 | 23-NOV-01:53 |
December | 9097.65 | 01-DEC-08:09 | 4502.34 | 08-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.24 | 17-DEC-12:00 | 63487.50 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2763.20 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15056.50 | |||||
Maximum of Months | 9097.65 | 4502.34 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 19286.19 | 71076.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2661.50 | 14-JAN-08:05 | 6723.69 | 3057.91 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1752.00 |
February | 2195.68 | 25-FEB-08:05 | 6723.69 | 2892.71 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1010.31 |
March | 2079.54 | 23-MAR-07:05 | 6723.69 | 2788.89 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1696.06 |
April | 2420.23 | 10-APR-15:00 | 1680.92 | 493.23 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.55 |
May | 17335.70 | 30-MAY-07:02 | 8404.61 | 3073.40 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.14 |
June | 22150.98 | 03-JUN-07:02 | 8404.61 | 3195.38 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.21 |
July | 18629.10 | 11-JUL-06:02 | 1764.97 | 1800.26 | 4587.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1974.95 |
August | 20507.16 | 25-AUG-07:02 | 8404.61 | 3344.64 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.73 |
September | 23259.83 | 23-SEP-07:02 | 8404.61 | 3702.04 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.73 |
October | 17863.53 | 14-OCT-07:03 | 6723.69 | 3092.83 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 |
November | 2128.76 | 24-NOV-08:05 | 6723.69 | 2876.34 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1374.33 |
December | 2222.17 | 22-DEC-08:05 | 6723.69 | 3013.27 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2079.54 | 1680.92 | 493.23 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | |
Maximum of Months | 23259.83 | 8404.61 | 3702.04 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1974.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5022.42 | 26-JAN-11:30 | 3955.50 | 2177.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 611.56 |
February | 7644.90 | 25-FEB-09:05 | 7911.00 | 7186.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1769.70 |
March | 7220.44 | 17-MAR-10:35 | 7911.00 | 5098.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1377.90 |
April | 6069.86 | 12-APR-07:03 | 11866.50 | 10135.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4185.43 |
May | 27124.53 | 31-MAY-17:22 | 0.00 | 1939.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.10 |
June | 40511.23 | 25-JUN-14:43 | 0.00 | 768.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.14 |
July | 46631.04 | 04-JUL-16:23 | 0.00 | 920.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.28 |
August | 48769.49 | 20-AUG-12:23 | 0.00 | 768.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.85 | 0.00 |
September | 46906.32 | 04-SEP-14:13 | 0.00 | 768.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.91 |
October | 6259.44 | 28-OCT-07:10 | 3955.50 | 3509.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2328.37 |
November | 4871.92 | 20-NOV-11:00 | 3955.50 | 2572.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.72 |
December | 5683.17 | 07-DEC-09:15 | 7911.00 | 7371.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1465.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4871.92 | 0.00 | 768.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48769.49 | 11866.50 | 10135.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.85 | 4185.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 2817.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50590.71 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 1690.51 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14066.89 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 1127.00 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5220.23 |
April | 0.00 | 01-APR-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6315.85 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2922.41 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4401.08 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6465.90 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4070.58 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5166.76 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 563.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14036.14 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9336.41 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 1127.00 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9682.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 563.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2922.41 | |
Maximum of Months | 0.00 | 0.00 | 2817.51 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50590.71 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.324974E+11 | 28655.41 | 11-JAN-16:00 | 0.126120E+12 | 187963.48 | 01-JAN-20:49 |
February | 0.286390E+11 | 22870.40 | 06-FEB-16:00 | 0.120109E+12 | 207619.42 | 06-FEB-00:10 |
March | 0.304501E+11 | 21851.36 | 16-MAR-08:09 | 0.366338E+11 | 130596.14 | 22-MAR-07:10 |
April | 0.270457E+11 | 20937.41 | 06-APR-07:10 | 0.402167E+10 | 34920.59 | 02-APR-06:10 |
May | 0.273620E+11 | 24878.66 | 31-MAY-14:09 | 0.101738E+09 | 10469.74 | 01-MAY-06:10 |
June | 0.299910E+11 | 32551.70 | 19-JUN-12:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.340282E+11 | 31923.73 | 08-JUL-12:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.364133E+11 | 32666.82 | 04-AUG-14:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.296830E+11 | 28839.57 | 14-SEP-13:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.291923E+11 | 22058.52 | 31-OCT-14:39 | 0.101181E+09 | 8695.95 | 31-OCT-06:10 |
November | 0.296857E+11 | 28520.94 | 22-NOV-16:49 | 0.255622E+11 | 111784.25 | 23-NOV-02:09 |
December | 0.327451E+11 | 28533.54 | 30-DEC-16:00 | 0.811215E+11 | 174448.25 | 31-DEC-21:49 |
Annual Sum or Average | 0.367733E+12 | 0.393771E+12 | ||||
Minimum of Months | 0.270457E+11 | 20937.41 | 0.00 | 0.00 | ||
Maximum of Months | 0.364133E+11 | 32666.82 | 0.126120E+12 | 207619.42 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.894187E+10 | 0.681056E+10 | 0.112984E+11 | 0.00 | 0.320736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223927E+10 | 0.00 |
February | 0.768634E+10 | 0.557496E+10 | 0.103734E+11 | 0.00 | 0.296018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204413E+10 | 0.00 |
March | 0.806045E+10 | 0.538029E+10 | 0.121089E+11 | 0.00 | 0.260985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229059E+10 | 0.00 |
April | 0.721443E+10 | 0.441367E+10 | 0.112578E+11 | 0.00 | 0.200756E+10 | 0.00 | 0.00 | 18391216.16 | 0.00 | 0.00 | 0.00 | 0.213385E+10 | 0.00 |
May | 0.712710E+10 | 0.396797E+10 | 0.117000E+11 | 0.00 | 0.203895E+10 | 0.00 | 0.00 | 0.381568E+09 | 0.00 | 0.00 | 0.00 | 0.214646E+10 | 0.00 |
June | 0.697573E+10 | 0.356142E+10 | 0.116594E+11 | 0.00 | 0.224176E+10 | 0.00 | 0.00 | 0.351401E+10 | 0.00 | 0.00 | 0.00 | 0.203871E+10 | 0.00 |
July | 0.690151E+10 | 0.377060E+10 | 0.112984E+11 | 0.00 | 0.294187E+10 | 0.00 | 0.00 | 0.709665E+10 | 0.00 | 0.00 | 0.00 | 0.201924E+10 | 0.00 |
August | 0.742032E+10 | 0.424840E+10 | 0.121016E+11 | 0.00 | 0.337397E+10 | 0.00 | 0.00 | 0.721030E+10 | 0.00 | 0.00 | 0.00 | 0.205873E+10 | 0.00 |
September | 0.738888E+10 | 0.485857E+10 | 0.112504E+11 | 0.00 | 0.207362E+10 | 0.00 | 0.00 | 0.212382E+10 | 0.00 | 0.00 | 0.00 | 0.198770E+10 | 0.00 |
October | 0.783082E+10 | 0.584496E+10 | 0.113057E+11 | 0.00 | 0.195760E+10 | 0.00 | 0.00 | 0.171337E+09 | 0.00 | 0.00 | 0.00 | 0.208180E+10 | 0.00 |
November | 0.816881E+10 | 0.638112E+10 | 0.108562E+11 | 0.00 | 0.220866E+10 | 0.00 | 0.00 | 23.05 | 0.00 | 0.00 | 0.00 | 0.207098E+10 | 0.00 |
December | 0.923519E+10 | 0.698522E+10 | 0.112984E+11 | 0.00 | 0.302478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220157E+10 | 0.00 |
Annual Sum or Average | 0.929514E+11 | 0.617977E+11 | 0.136508E+12 | 0.00 | 0.306462E+11 | 0.00 | 0.00 | 0.205161E+11 | 0.00 | 0.00 | 0.00 | 0.253130E+11 | 0.00 |
Minimum of Months | 0.690151E+10 | 0.356142E+10 | 0.103734E+11 | 0.00 | 0.195760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198770E+10 | 0.00 |
Maximum of Months | 0.923519E+10 | 0.698522E+10 | 0.121089E+11 | 0.00 | 0.337397E+10 | 0.00 | 0.00 | 0.721030E+10 | 0.00 | 0.00 | 0.00 | 0.229059E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.126120E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.120109E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.366338E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.402167E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.101738E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.101181E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.255622E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.811215E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.393771E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.126120E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 9381.76 | 09-JAN-15:00 | 5492.60 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2783.68 | 02-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 8634.93 | 02-FEB-15:00 | 5492.60 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2873.30 | 06-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 7989.12 | 02-MAR-16:00 | 5492.60 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2623.63 | 22-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 7278.90 | 06-APR-07:10 | 5492.60 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2090.89 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 6900.52 | 08-MAY-07:10 | 5492.60 | 01-MAY-18:49 | 10035.17 | 01-MAY-07:10 | 0.00 | 1977.38 | 01-MAY-07:40 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 6656.83 | 29-JUN-07:10 | 4946.68 | 01-JUN-19:19 | 10035.17 | 01-JUN-07:10 | 0.00 | 4531.24 | 19-JUN-13:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 6880.19 | 15-JUL-07:10 | 4946.68 | 01-JUL-19:30 | 10035.17 | 01-JUL-07:10 | 0.00 | 4507.37 | 08-JUL-12:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7125.57 | 16-AUG-07:10 | 5492.60 | 08-AUG-18:00 | 10035.17 | 01-AUG-07:10 | 0.00 | 4569.13 | 04-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7600.73 | 27-SEP-07:10 | 5492.60 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4282.67 | 01-SEP-10:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8382.02 | 31-OCT-14:00 | 5492.60 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 1977.38 | 02-OCT-12:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9456.70 | 15-NOV-15:00 | 5492.60 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2569.28 | 22-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 9480.56 | 27-DEC-15:00 | 5492.60 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2564.08 | 22-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 6656.83 | 4946.68 | 10035.17 | 0.00 | 1977.38 | 0.00 | 0.00 | |||||
Maximum of Months | 9480.56 | 5492.60 | 10035.17 | 0.00 | 4569.13 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2456.11 | 31-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2461.17 | 09-FEB-12:00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2428.88 | 01-MAR-12:00 | 0.00 |
April | 865.14 | 07-APR-15:09 | 0.00 | 0.00 | 0.00 | 2259.14 | 01-APR-11:50 | 0.00 |
May | 6127.76 | 31-MAY-18:19 | 0.00 | 0.00 | 0.00 | 1971.28 | 01-MAY-11:50 | 0.00 |
June | 11987.51 | 19-JUN-11:00 | 0.00 | 0.00 | 0.00 | 1791.59 | 01-JUN-11:09 | 0.00 |
July | 10710.21 | 07-JUL-11:00 | 0.00 | 0.00 | 0.00 | 1770.40 | 01-JUL-11:09 | 0.00 |
August | 11286.01 | 04-AUG-13:00 | 0.00 | 0.00 | 0.00 | 1762.02 | 31-AUG-11:20 | 0.00 |
September | 8275.52 | 07-SEP-13:00 | 0.00 | 0.00 | 0.00 | 1776.61 | 30-SEP-11:09 | 0.00 |
October | 1967.13 | 04-OCT-14:30 | 0.00 | 0.00 | 0.00 | 1802.37 | 31-OCT-11:09 | 0.00 |
November | 0.02 | 04-NOV-15:00 | 0.00 | 0.00 | 0.00 | 2084.61 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2333.86 | 30-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1762.02 | 0.00 | ||
Maximum of Months | 11987.51 | 0.00 | 0.00 | 0.00 | 2461.17 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 28655.41 | 11-JAN-16:00 | 8876.89 | 10035.17 | 5492.60 | 0.00 | 2633.98 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22870.40 | 06-FEB-16:00 | 8502.18 | 10035.17 | 0.00 | 0.00 | 2714.68 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21851.36 | 16-MAR-08:09 | 7741.94 | 10035.17 | 0.00 | 0.00 | 2387.23 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20937.41 | 06-APR-07:10 | 7278.90 | 10035.17 | 0.00 | 0.00 | 1977.38 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24878.66 | 31-MAY-14:09 | 5065.28 | 10035.17 | 0.00 | 0.00 | 1977.38 | 0.00 | 0.00 | 6045.36 | 0.00 |
June | 32551.70 | 19-JUN-12:20 | 5148.02 | 10035.17 | 0.00 | 0.00 | 4491.87 | 0.00 | 0.00 | 11133.21 | 0.00 |
July | 31923.73 | 08-JUL-12:30 | 5090.18 | 10035.17 | 0.00 | 0.00 | 4503.52 | 0.00 | 0.00 | 10560.63 | 0.00 |
August | 32666.82 | 04-AUG-14:20 | 5065.28 | 10035.17 | 0.00 | 0.00 | 4568.26 | 0.00 | 0.00 | 11270.36 | 0.00 |
September | 28839.57 | 14-SEP-13:39 | 5081.59 | 10035.17 | 0.00 | 0.00 | 4282.67 | 0.00 | 0.00 | 7736.55 | 0.00 |
October | 22058.52 | 31-OCT-14:39 | 8283.06 | 10035.17 | 0.00 | 0.00 | 1977.38 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28520.94 | 22-NOV-16:49 | 8876.89 | 10035.17 | 5492.60 | 0.00 | 2508.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28533.54 | 30-DEC-16:00 | 8876.89 | 10035.17 | 5492.60 | 0.00 | 2513.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 20937.41 | 5065.28 | 10035.17 | 0.00 | 0.00 | 1977.38 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32666.82 | 8876.89 | 10035.17 | 5492.60 | 0.00 | 4568.26 | 0.00 | 0.00 | 11270.36 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 187963.48 | 01-JAN-20:49 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 207619.42 | 06-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 130596.14 | 22-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 34920.59 | 02-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 10469.74 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 8695.95 | 31-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 111784.25 | 23-NOV-02:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 174448.25 | 31-DEC-21:49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 207619.42 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 15.88 | 3.83 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
February | 8.67 | 15.75 | 3.67 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 |
March | 1.83 | 16.90 | 1.67 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
April | 0.67 | 17.17 | 0.67 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.08 | 0.50 | 25.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 16.15 | 0.83 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
December | 3.00 | 16.56 | 2.33 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
Annual Sum or Average | 24.50 | 16.04 | 13.00 | 16.36 | 0.50 | 16.48 | 0.50 | 16.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.83 | 17.17 | 3.83 | 17.17 | 0.50 | 25.08 | 0.50 | 25.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 69.83 | 14.71 | 3.67 | 14.71 | 0.00 | 14.71 | 0.00 | 14.71 |
February | 63.50 | 14.71 | 4.67 | 14.71 | 0.00 | 14.71 | 0.00 | 14.71 |
March | 21.67 | 14.94 | 2.17 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
April | 1.50 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.33 | 0.00 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.38 | 0.17 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.34 | 0.67 | 27.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.33 | 0.00 | 27.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19.33 | 14.86 | 1.33 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
December | 41.50 | 14.88 | 4.33 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
Annual Sum or Average | 217.33 | 14.78 | 16.17 | 14.78 | 39.83 | 16.61 | 0.83 | 16.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 69.83 | 14.96 | 4.67 | 14.96 | 16.00 | 27.38 | 0.67 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.62 | 300.00 | 20.62 | 300.00 | 20.62 |
February | 276.00 | 20.62 | 276.00 | 20.62 | 276.00 | 20.62 |
March | 324.00 | 20.69 | 311.50 | 20.67 | 311.50 | 20.66 |
April | 300.00 | 21.48 | 185.67 | 21.14 | 185.67 | 20.98 |
May | 252.00 | 23.03 | 68.00 | 23.01 | 39.00 | 22.89 |
June | 63.50 | 24.91 | 289.17 | 24.43 | 63.50 | 24.50 |
July | 80.83 | 25.56 | 300.00 | 24.67 | 80.83 | 24.83 |
August | 49.00 | 25.66 | 324.00 | 24.58 | 49.00 | 24.70 |
September | 59.00 | 24.48 | 212.33 | 24.36 | 25.50 | 24.46 |
October | 208.67 | 23.06 | 102.83 | 23.18 | 42.33 | 23.09 |
November | 288.00 | 20.98 | 225.83 | 20.80 | 225.83 | 20.74 |
December | 300.00 | 20.63 | 300.00 | 20.63 | 300.00 | 20.63 |
Annual Sum or Average | 2501.00 | 21.68 | 2895.33 | 21.98 | 1899.17 | 21.78 |
Minimum of Months | 49.00 | 20.62 | 68.00 | 20.62 | 25.50 | 20.62 |
Maximum of Months | 324.00 | 25.66 | 324.00 | 24.67 | 311.50 | 24.83 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.60 | 300.00 | 15.60 | 300.00 | 15.60 |
February | 276.00 | 15.60 | 276.00 | 15.60 | 276.00 | 15.60 |
March | 324.00 | 16.30 | 324.00 | 16.30 | 324.00 | 16.30 |
April | 300.00 | 18.62 | 231.67 | 18.19 | 231.67 | 18.02 |
May | 222.67 | 22.00 | 149.00 | 22.49 | 84.50 | 22.32 |
June | 241.00 | 26.54 | 309.17 | 26.50 | 241.00 | 26.51 |
July | 292.17 | 26.71 | 300.00 | 26.71 | 292.17 | 26.71 |
August | 280.00 | 26.71 | 324.00 | 26.69 | 280.00 | 26.70 |
September | 155.17 | 25.99 | 250.67 | 26.18 | 127.50 | 26.28 |
October | 244.83 | 22.37 | 152.50 | 22.66 | 110.00 | 22.61 |
November | 288.00 | 17.00 | 280.17 | 16.94 | 280.17 | 16.92 |
December | 300.00 | 15.62 | 300.00 | 15.62 | 300.00 | 15.62 |
Annual Sum or Average | 3223.83 | 20.32 | 3197.17 | 20.51 | 2847.00 | 20.37 |
Minimum of Months | 155.17 | 15.60 | 149.00 | 15.60 | 84.50 | 15.60 |
Maximum of Months | 324.00 | 26.71 | 324.00 | 26.71 | 324.00 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.37 | 300.00 | 10.37 | 300.00 | 10.37 |
February | 276.00 | 10.23 | 276.00 | 10.23 | 276.00 | 10.23 |
March | 324.00 | 11.35 | 324.00 | 11.35 | 324.00 | 11.35 |
April | 300.00 | 14.87 | 300.00 | 14.87 | 300.00 | 14.87 |
May | 293.17 | 19.76 | 187.33 | 19.48 | 170.17 | 19.19 |
June | 231.50 | 27.23 | 288.50 | 27.12 | 218.67 | 27.22 |
July | 300.00 | 29.31 | 300.00 | 29.31 | 300.00 | 29.31 |
August | 324.00 | 29.41 | 324.00 | 29.41 | 324.00 | 29.41 |
September | 192.50 | 27.28 | 227.83 | 27.38 | 158.67 | 27.60 |
October | 282.00 | 20.32 | 173.50 | 20.07 | 160.00 | 19.85 |
November | 288.00 | 13.52 | 288.00 | 13.52 | 288.00 | 13.52 |
December | 300.00 | 10.31 | 300.00 | 10.31 | 300.00 | 10.31 |
Annual Sum or Average | 3411.17 | 18.31 | 3289.17 | 18.34 | 3119.50 | 18.22 |
Minimum of Months | 192.50 | 10.23 | 173.50 | 10.23 | 158.67 | 10.23 |
Maximum of Months | 324.00 | 29.41 | 324.00 | 29.41 | 324.00 | 29.41 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 87910779.46 | 18391216.16 | 18.83 | 83890865.01 | 4019914.46 | 0.00 | 0.45 | 07-APR-15:10 | 0.00 | 01-APR-00:10 | 4227.85 | 07-APR-15:10 | 4227.85 | 07-APR-15:10 | 271.87 | 08-APR-13:00 | 865.14 | 07-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 0.883918E+09 | 0.175914E+09 | 73.61 | 0.811736E+09 | 72181722.65 | 0.00 | 1.00 | 30-MAY-07:02 | 0.00 | 01-MAY-00:10 | 20621.35 | 31-MAY-07:02 | 17279.83 | 30-MAY-07:02 | 6982.99 | 31-MAY-07:02 | 3899.01 | 31-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.684082E+10 | 0.131269E+10 | 249.42 | 0.519173E+10 | 0.164909E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 23443.32 | 19-JUN-06:02 | 18027.18 | 22-JUN-07:02 | 12286.16 | 27-JUN-06:02 | 4316.11 | 19-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.103983E+11 | 0.199270E+10 | 268.36 | 0.749035E+10 | 0.290800E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 24304.83 | 21-JUL-06:02 | 18667.12 | 12-JUL-06:02 | 13682.19 | 28-JUL-06:03 | 4384.00 | 22-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.104594E+11 | 0.204164E+10 | 283.59 | 0.813958E+10 | 0.231984E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 24284.79 | 04-AUG-06:02 | 18746.03 | 13-AUG-15:02 | 12604.26 | 12-AUG-06:02 | 4391.66 | 04-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.472281E+10 | 0.899627E+09 | 200.33 | 0.370858E+10 | 0.101423E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 23366.70 | 14-SEP-06:03 | 16255.81 | 02-SEP-06:02 | 13508.50 | 14-SEP-06:03 | 4252.16 | 14-SEP-06:03 | 0.00 | 01-SEP-00:10 |
October | 0.854709E+09 | 0.166779E+09 | 70.60 | 0.629850E+09 | 0.224859E+09 | 0.00 | 1.00 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 | 20986.73 | 06-OCT-07:03 | 11368.48 | 06-OCT-07:03 | 9618.24 | 06-OCT-07:03 | 3952.51 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 108.09 | 23.05 | 0.50 | 102.06 | 6.02 | 0.00 | 0.00 | 04-NOV-16:00 | 0.00 | 01-NOV-00:10 | 0.09 | 04-NOV-16:00 | 0.08 | 04-NOV-16:00 | 0.01 | 04-NOV-16:00 | 0.02 | 04-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.342479E+11 | 0.660774E+10 | 1165.25 | 0.260557E+11 | 0.819223E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.104594E+11 | 0.204164E+10 | 283.59 | 0.813958E+10 | 0.290800E+10 | 0.00 | 1.00 | 0.00 | 24304.83 | 18746.03 | 13682.19 | 4391.66 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.864575E+09 | 0.205654E+09 | 21.10 | 0.678308E+09 | 0.186267E+09 | 0.00 | 1.00 | 30-MAY-17:46 | 0.00 | 01-MAY-00:10 | 59674.20 | 31-MAY-17:22 | 34644.15 | 31-MAY-17:22 | 25030.05 | 31-MAY-17:22 | 12366.99 | 31-MAY-17:22 | 0.00 | 01-MAY-00:10 |
June | 0.954001E+10 | 0.220132E+10 | 213.05 | 0.663086E+10 | 0.290915E+10 | 0.00 | 1.00 | 01-JUN-18:02 | 0.00 | 01-JUN-00:10 | 65098.40 | 21-JUN-17:22 | 51480.04 | 01-JUN-18:55 | 37424.01 | 21-JUN-17:22 | 13423.40 | 19-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 0.224647E+11 | 0.510394E+10 | 366.00 | 0.147307E+11 | 0.773393E+10 | 0.00 | 1.00 | 01-JUL-19:05 | 0.00 | 01-JUL-00:10 | 65051.61 | 21-JUL-06:02 | 50455.75 | 04-JUL-16:23 | 31797.38 | 18-JUL-17:25 | 13174.76 | 21-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.224849E+11 | 0.516867E+10 | 360.80 | 0.159796E+11 | 0.650530E+10 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 63162.33 | 06-AUG-09:05 | 52268.20 | 20-AUG-12:23 | 34744.17 | 06-AUG-09:05 | 13290.77 | 04-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 0.535388E+10 | 0.122419E+10 | 131.95 | 0.385540E+10 | 0.149849E+10 | 0.00 | 1.00 | 01-SEP-17:13 | 0.00 | 01-SEP-00:10 | 55953.16 | 14-SEP-18:05 | 51194.43 | 10-SEP-15:05 | 15574.77 | 07-SEP-17:13 | 12427.10 | 14-SEP-18:05 | 0.00 | 01-SEP-00:10 |
October | 18711821.64 | 4557861.50 | 3.83 | 11945907.61 | 6765914.03 | 0.00 | 0.09 | 04-OCT-13:30 | 0.00 | 01-OCT-00:10 | 2191.60 | 04-OCT-13:30 | 1434.39 | 04-OCT-13:20 | 773.67 | 04-OCT-14:30 | 534.91 | 04-OCT-13:30 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.607267E+11 | 0.139083E+11 | 1096.73 | 0.418868E+11 | 0.188399E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.224849E+11 | 0.516867E+10 | 366.00 | 0.159796E+11 | 0.773393E+10 | 0.00 | 1.00 | 0.00 | 65098.40 | 52268.20 | 37424.01 | 13423.40 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 58.21 | 23.91 | 34.29 | 41.35 | 119.53 | 0.00 | 0.00 | 0.00 |
February | 85.31 | 37.43 | 47.89 | 67.16 | 121.13 | 0.00 | 0.00 | 0.00 |
March | 126.94 | 58.85 | 68.09 | 130.00 | 73.16 | 0.00 | 0.00 | 0.00 |
April | 137.73 | 58.80 | 78.93 | 157.13 | 53.72 | 0.00 | 0.00 | 0.00 |
May | 160.97 | 61.16 | 99.81 | 197.17 | 40.99 | 0.00 | 0.00 | 0.00 |
June | 176.17 | 71.21 | 104.95 | 231.48 | 31.45 | 0.00 | 0.00 | 0.00 |
July | 164.78 | 62.05 | 102.73 | 230.40 | 20.55 | 0.00 | 0.00 | 0.00 |
August | 182.19 | 84.27 | 97.91 | 255.62 | 27.19 | 0.00 | 0.00 | 0.00 |
September | 129.60 | 56.62 | 72.98 | 162.70 | 45.31 | 0.00 | 0.00 | 0.00 |
October | 128.02 | 62.15 | 65.88 | 149.83 | 67.47 | 0.00 | 0.00 | 0.00 |
November | 60.39 | 17.52 | 42.87 | 49.47 | 81.57 | 0.00 | 0.00 | 0.00 |
December | 53.62 | 23.23 | 30.39 | 39.70 | 107.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 122.25 | 51.55 | 70.70 | 143.20 | 65.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.62 | 17.52 | 30.39 | 39.70 | 20.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.19 | 84.27 | 104.95 | 255.62 | 121.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 58.21 | 23.91 | 34.29 | 41.35 | 119.53 | 0.00 | 0.00 | 0.00 |
February | 85.31 | 37.43 | 47.89 | 67.16 | 121.13 | 0.00 | 0.00 | 0.00 |
March | 126.94 | 58.85 | 68.09 | 130.00 | 73.16 | 0.00 | 0.00 | 0.00 |
April | 137.73 | 58.80 | 78.93 | 157.13 | 53.72 | 0.00 | 0.00 | 0.00 |
May | 160.97 | 61.16 | 99.81 | 197.17 | 40.99 | 0.00 | 0.00 | 0.00 |
June | 176.17 | 71.21 | 104.95 | 231.48 | 31.45 | 0.00 | 0.00 | 0.00 |
July | 164.78 | 62.05 | 102.73 | 230.40 | 20.55 | 0.00 | 0.00 | 0.00 |
August | 182.19 | 84.27 | 97.91 | 255.62 | 27.19 | 0.00 | 0.00 | 0.00 |
September | 129.60 | 56.62 | 72.98 | 162.70 | 45.31 | 0.00 | 0.00 | 0.00 |
October | 128.02 | 62.15 | 65.88 | 149.83 | 67.47 | 0.00 | 0.00 | 0.00 |
November | 60.39 | 17.52 | 42.87 | 49.47 | 81.57 | 0.00 | 0.00 | 0.00 |
December | 53.62 | 23.23 | 30.39 | 39.70 | 107.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 122.25 | 51.55 | 70.70 | 143.20 | 65.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.62 | 17.52 | 30.39 | 39.70 | 20.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.19 | 84.27 | 104.95 | 255.62 | 121.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.40 | 0.00 | 16.40 | 2.15 | 73.94 | 0.00 | 0.00 | 0.00 |
February | 22.44 | 0.00 | 22.44 | 3.84 | 75.69 | 0.00 | 0.00 | 0.00 |
March | 31.13 | 0.00 | 31.13 | 16.37 | 45.17 | 0.00 | 0.00 | 0.00 |
April | 37.40 | 0.12 | 37.28 | 30.51 | 31.77 | 0.00 | 0.00 | 0.00 |
May | 49.79 | 1.80 | 47.99 | 51.17 | 23.13 | 0.00 | 0.00 | 0.00 |
June | 52.50 | 2.74 | 49.76 | 62.97 | 17.62 | 0.00 | 0.00 | 0.00 |
July | 50.94 | 1.93 | 49.01 | 69.36 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 45.11 | 0.61 | 44.50 | 60.20 | 15.57 | 0.00 | 0.00 | 0.00 |
September | 33.96 | 0.02 | 33.95 | 34.66 | 26.90 | 0.00 | 0.00 | 0.00 |
October | 29.37 | 0.00 | 29.37 | 22.72 | 40.44 | 0.00 | 0.00 | 0.00 |
November | 20.60 | 0.00 | 20.60 | 8.96 | 49.30 | 0.00 | 0.00 | 0.00 |
December | 14.30 | 0.00 | 14.30 | 1.60 | 66.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.73 | 0.61 | 33.12 | 30.55 | 39.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.30 | 0.00 | 14.30 | 1.60 | 11.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.50 | 2.74 | 49.76 | 69.36 | 75.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.40 | 0.00 | 16.40 | 2.15 | 73.94 | 0.00 | 0.00 | 0.00 |
February | 22.44 | 0.00 | 22.44 | 3.84 | 75.69 | 0.00 | 0.00 | 0.00 |
March | 31.13 | 0.00 | 31.13 | 16.37 | 45.17 | 0.00 | 0.00 | 0.00 |
April | 37.40 | 0.12 | 37.28 | 30.51 | 31.77 | 0.00 | 0.00 | 0.00 |
May | 49.79 | 1.80 | 47.99 | 51.17 | 23.13 | 0.00 | 0.00 | 0.00 |
June | 52.50 | 2.74 | 49.76 | 62.96 | 17.62 | 0.00 | 0.00 | 0.00 |
July | 50.94 | 1.93 | 49.01 | 69.36 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 45.11 | 0.61 | 44.50 | 60.20 | 15.57 | 0.00 | 0.00 | 0.00 |
September | 33.96 | 0.02 | 33.95 | 34.65 | 26.90 | 0.00 | 0.00 | 0.00 |
October | 29.37 | 0.00 | 29.37 | 22.72 | 40.44 | 0.00 | 0.00 | 0.00 |
November | 20.60 | 0.00 | 20.60 | 8.96 | 49.30 | 0.00 | 0.00 | 0.00 |
December | 14.30 | 0.00 | 14.30 | 1.60 | 66.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.73 | 0.61 | 33.12 | 30.55 | 39.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.30 | 0.00 | 14.30 | 1.60 | 11.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.50 | 2.74 | 49.76 | 69.36 | 75.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 29.84 | 61.90 | 1.17 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 55.33 | 62.93 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 100.94 | 38.62 | 0.00 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 132.41 | 30.31 | 0.00 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 174.06 | 24.69 | 6.17 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 193.96 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 193.98 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 198.55 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 127.36 | 29.42 | 2.17 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 101.83 | 40.22 | 15.00 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 47.38 | 44.19 | 1.00 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 26.60 | 55.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 115.57 | 37.08 | 25.50 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 26.60 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 198.55 | 62.93 | 15.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.24 | 15.71 | 22.53 | 36.44 | 44.19 | 34.33 | 0.00 | 0.00 |
February | 62.45 | 33.77 | 28.68 | 63.21 | 46.09 | 0.00 | 0.00 | 0.00 |
March | 93.56 | 51.90 | 41.66 | 110.41 | 25.67 | 5.67 | 0.00 | 0.00 |
April | 115.61 | 65.16 | 50.45 | 140.87 | 21.96 | 39.50 | 0.00 | 0.00 |
May | 145.80 | 79.08 | 66.72 | 181.84 | 19.25 | 16.83 | 0.00 | 0.00 |
June | 159.28 | 90.68 | 68.60 | 195.47 | 20.75 | 0.00 | 0.00 | 0.00 |
July | 153.64 | 83.76 | 69.87 | 190.24 | 19.60 | 0.00 | 0.00 | 0.00 |
August | 157.73 | 99.40 | 58.34 | 194.77 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 108.18 | 63.22 | 44.96 | 126.77 | 31.16 | 1.67 | 0.00 | 0.00 |
October | 90.12 | 52.68 | 37.44 | 106.13 | 35.03 | 30.67 | 0.00 | 0.00 |
November | 48.80 | 19.35 | 29.45 | 52.48 | 34.09 | 16.67 | 0.00 | 0.00 |
December | 33.90 | 15.44 | 18.46 | 32.87 | 38.40 | 8.33 | 0.00 | 0.00 |
Annual Sum or Average | 100.84 | 55.99 | 44.86 | 119.65 | 30.11 | 153.67 | 0.00 | 0.00 |
Minimum of Months | 33.90 | 15.44 | 18.46 | 32.87 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.28 | 99.40 | 69.87 | 195.47 | 46.09 | 39.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.155901E+09 | 64047165.69 | 91854058.42 | 0.110755E+09 | 0.320152E+09 |
February | 0.206391E+09 | 90544604.43 | 0.115847E+09 | 0.162477E+09 | 0.293048E+09 |
March | 0.340008E+09 | 0.157627E+09 | 0.182381E+09 | 0.348182E+09 | 0.195964E+09 |
April | 0.356984E+09 | 0.152402E+09 | 0.204582E+09 | 0.407274E+09 | 0.139246E+09 |
May | 0.431142E+09 | 0.163815E+09 | 0.267326E+09 | 0.528104E+09 | 0.109789E+09 |
June | 0.456628E+09 | 0.184588E+09 | 0.272041E+09 | 0.599987E+09 | 81522027.24 |
July | 0.441356E+09 | 0.166205E+09 | 0.275151E+09 | 0.617104E+09 | 55049956.83 |
August | 0.487965E+09 | 0.225713E+09 | 0.262252E+09 | 0.684665E+09 | 72832141.61 |
September | 0.335936E+09 | 0.146767E+09 | 0.189169E+09 | 0.421716E+09 | 0.117445E+09 |
October | 0.342902E+09 | 0.166459E+09 | 0.176443E+09 | 0.401293E+09 | 0.180707E+09 |
November | 0.156518E+09 | 45411848.97 | 0.111106E+09 | 0.128214E+09 | 0.211434E+09 |
December | 0.143627E+09 | 62221948.61 | 81405021.27 | 0.106333E+09 | 0.288690E+09 |
Annual Sum or Average | 0.385536E+10 | 0.162580E+10 | 0.222956E+10 | 0.451610E+10 | 0.206588E+10 |
Minimum of Months | 0.143627E+09 | 45411848.97 | 81405021.27 | 0.106333E+09 | 55049956.83 |
Maximum of Months | 0.487965E+09 | 0.225713E+09 | 0.275151E+09 | 0.684665E+09 | 0.320152E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.155901E+09 | 64047165.69 | 91854058.42 | 0.110755E+09 | 0.320152E+09 |
February | 0.206391E+09 | 90544604.43 | 0.115847E+09 | 0.162477E+09 | 0.293048E+09 |
March | 0.340008E+09 | 0.157627E+09 | 0.182381E+09 | 0.348182E+09 | 0.195964E+09 |
April | 0.356984E+09 | 0.152402E+09 | 0.204582E+09 | 0.407274E+09 | 0.139246E+09 |
May | 0.431142E+09 | 0.163815E+09 | 0.267326E+09 | 0.528104E+09 | 0.109789E+09 |
June | 0.456628E+09 | 0.184588E+09 | 0.272041E+09 | 0.599987E+09 | 81522027.24 |
July | 0.441356E+09 | 0.166205E+09 | 0.275151E+09 | 0.617104E+09 | 55049956.83 |
August | 0.487965E+09 | 0.225713E+09 | 0.262252E+09 | 0.684665E+09 | 72832141.61 |
September | 0.335936E+09 | 0.146767E+09 | 0.189169E+09 | 0.421716E+09 | 0.117445E+09 |
October | 0.342902E+09 | 0.166459E+09 | 0.176443E+09 | 0.401293E+09 | 0.180707E+09 |
November | 0.156518E+09 | 45411848.97 | 0.111106E+09 | 0.128214E+09 | 0.211434E+09 |
December | 0.143627E+09 | 62221948.61 | 81405021.27 | 0.106333E+09 | 0.288690E+09 |
Annual Sum or Average | 0.385536E+10 | 0.162580E+10 | 0.222956E+10 | 0.451610E+10 | 0.206588E+10 |
Minimum of Months | 0.143627E+09 | 45411848.97 | 81405021.27 | 0.106333E+09 | 55049956.83 |
Maximum of Months | 0.487965E+09 | 0.225713E+09 | 0.275151E+09 | 0.684665E+09 | 0.320152E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43921429.48 | 0.00 | 43921429.48 | 5757682.89 | 0.198046E+09 |
February | 54288098.32 | 0.00 | 54288098.32 | 9281884.34 | 0.183110E+09 |
March | 83376366.01 | 4767.51 | 83371598.50 | 43852649.54 | 0.120972E+09 |
April | 96942994.66 | 318480.93 | 96624513.73 | 79079147.79 | 82350316.00 |
May | 0.133355E+09 | 4826136.24 | 0.128529E+09 | 0.137048E+09 | 61957620.33 |
June | 0.136077E+09 | 7090001.18 | 0.128987E+09 | 0.163210E+09 | 45676223.50 |
July | 0.136438E+09 | 5172588.48 | 0.131265E+09 | 0.185783E+09 | 31364805.69 |
August | 0.120829E+09 | 1639075.02 | 0.119190E+09 | 0.161247E+09 | 41696777.79 |
September | 88032212.02 | 40962.35 | 87991249.66 | 89825974.16 | 69718099.49 |
October | 78676730.93 | 0.00 | 78676730.93 | 60848006.04 | 0.108314E+09 |
November | 53403953.99 | 0.00 | 53403953.99 | 23223086.13 | 0.127798E+09 |
December | 38311171.30 | 0.00 | 38311171.30 | 4274073.18 | 0.178339E+09 |
Annual Sum or Average | 0.106365E+10 | 19092011.72 | 0.104456E+10 | 0.963430E+09 | 0.124934E+10 |
Minimum of Months | 38311171.30 | 0.00 | 38311171.30 | 4274073.18 | 31364805.69 |
Maximum of Months | 0.136438E+09 | 7090001.18 | 0.131265E+09 | 0.185783E+09 | 0.198046E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43919992.00 | 0.00 | 43919992.00 | 5757010.56 | 0.198046E+09 |
February | 54286438.57 | 0.00 | 54286438.57 | 9281054.27 | 0.183111E+09 |
March | 83373843.40 | 4767.29 | 83369076.11 | 43850152.12 | 0.120972E+09 |
April | 96940089.42 | 318466.01 | 96621623.42 | 79075874.60 | 82350078.95 |
May | 0.133351E+09 | 4825910.03 | 0.128525E+09 | 0.137042E+09 | 61957269.98 |
June | 0.136073E+09 | 7089668.87 | 0.128983E+09 | 0.163204E+09 | 45675880.36 |
July | 0.136434E+09 | 5172346.04 | 0.131261E+09 | 0.185777E+09 | 31364414.89 |
August | 0.120825E+09 | 1638998.19 | 0.119186E+09 | 0.161243E+09 | 41696222.23 |
September | 88029622.19 | 40960.43 | 87988661.75 | 89822931.86 | 69717638.07 |
October | 78674412.10 | 0.00 | 78674412.10 | 60845470.62 | 0.108314E+09 |
November | 53402203.35 | 0.00 | 53402203.35 | 23221460.61 | 0.127798E+09 |
December | 38309943.38 | 0.00 | 38309943.38 | 4273601.61 | 0.178339E+09 |
Annual Sum or Average | 0.106362E+10 | 19091116.85 | 0.104453E+10 | 0.963395E+09 | 0.124934E+10 |
Minimum of Months | 38309943.38 | 0.00 | 38309943.38 | 4273601.61 | 31364414.89 |
Maximum of Months | 0.136434E+09 | 7089668.87 | 0.131261E+09 | 0.185777E+09 | 0.198046E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 79936654.05 | 0.165780E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.133849E+09 | 0.152250E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.270357E+09 | 0.103439E+09 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.343215E+09 | 78556704.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.466198E+09 | 66118255.76 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.502743E+09 | 55173404.07 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.519548E+09 | 42183132.17 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.531797E+09 | 57431170.42 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.330110E+09 | 76258981.60 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.272739E+09 | 0.107713E+09 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.122820E+09 | 0.114543E+09 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 0.149795E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.364456E+10 | 0.116924E+10 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 71251117.43 | 42183132.17 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.531797E+09 | 0.165780E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102422E+09 | 42073629.70 | 60348746.95 | 97603554.47 | 0.118346E+09 |
February | 0.151082E+09 | 81704943.49 | 69376970.56 | 0.152909E+09 | 0.111492E+09 |
March | 0.250593E+09 | 0.139007E+09 | 0.111586E+09 | 0.295719E+09 | 68756745.53 |
April | 0.299665E+09 | 0.168907E+09 | 0.130758E+09 | 0.365129E+09 | 56927137.97 |
May | 0.390509E+09 | 0.211812E+09 | 0.178697E+09 | 0.487051E+09 | 51560076.23 |
June | 0.412848E+09 | 0.235041E+09 | 0.177807E+09 | 0.506655E+09 | 53787660.60 |
July | 0.411501E+09 | 0.224349E+09 | 0.187152E+09 | 0.509526E+09 | 52483421.07 |
August | 0.422476E+09 | 0.266225E+09 | 0.156251E+09 | 0.521674E+09 | 70283733.58 |
September | 0.280394E+09 | 0.163855E+09 | 0.116539E+09 | 0.328595E+09 | 80758063.09 |
October | 0.241384E+09 | 0.141103E+09 | 0.100281E+09 | 0.284252E+09 | 93820354.47 |
November | 0.126492E+09 | 50166525.16 | 76325205.88 | 0.136026E+09 | 88353746.97 |
December | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 0.102837E+09 |
Annual Sum or Average | 0.318016E+10 | 0.176561E+10 | 0.141455E+10 | 0.377317E+10 | 0.949407E+09 |
Minimum of Months | 90796109.28 | 41365025.85 | 49431083.44 | 88036133.81 | 51560076.23 |
Maximum of Months | 0.422476E+09 | 0.266225E+09 | 0.187152E+09 | 0.521674E+09 | 0.118346E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 80.77 | 380.71 | 149.21 | 47.82 | 101.38 | 0.00 | 0.00 |
February | 134.43 | 386.09 | 215.51 | 74.85 | 140.65 | 0.00 | 0.00 |
March | 288.51 | 232.44 | 316.15 | 117.71 | 198.44 | 0.00 | 0.00 |
April | 374.11 | 169.82 | 350.25 | 117.84 | 232.41 | 0.00 | 0.00 |
May | 495.47 | 127.04 | 421.52 | 125.93 | 295.59 | 0.00 | 0.00 |
June | 587.79 | 97.05 | 457.33 | 147.90 | 309.43 | 0.00 | 0.00 |
July | 598.92 | 63.92 | 431.45 | 127.97 | 303.48 | 0.00 | 0.00 |
August | 631.27 | 85.14 | 454.59 | 169.77 | 284.83 | 0.00 | 0.00 |
September | 393.90 | 143.60 | 327.14 | 113.28 | 213.86 | 0.00 | 0.00 |
October | 343.01 | 213.74 | 314.80 | 124.30 | 190.50 | 0.00 | 0.00 |
November | 114.25 | 259.15 | 161.98 | 35.04 | 126.94 | 0.00 | 0.00 |
December | 76.62 | 342.77 | 135.86 | 46.46 | 89.39 | 0.00 | 0.00 |
Annual Sum or Average | 344.70 | 207.45 | 311.96 | 104.32 | 207.64 | 0.00 | 0.00 |
Minimum of Months | 76.62 | 63.92 | 135.86 | 35.04 | 89.39 | 0.00 | 0.00 |
Maximum of Months | 631.27 | 386.09 | 457.33 | 169.77 | 309.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 417.83 | 866.53 | 535.36 | 219.92 | 315.44 | 0.00 | 0.00 |
February | 774.59 | 881.07 | 874.32 | 472.83 | 401.49 | 0.00 | 0.00 |
March | 1413.15 | 540.68 | 1309.85 | 726.59 | 583.26 | 0.00 | 0.00 |
April | 1853.79 | 424.30 | 1618.56 | 912.31 | 706.25 | 0.00 | 0.00 |
May | 2436.82 | 345.60 | 2041.19 | 1107.14 | 934.05 | 0.00 | 0.00 |
June | 2715.43 | 298.00 | 2229.89 | 1269.51 | 960.37 | 0.00 | 0.00 |
July | 2715.68 | 220.49 | 2150.92 | 1172.67 | 978.24 | 0.00 | 0.00 |
August | 2779.70 | 300.19 | 2208.28 | 1391.56 | 816.73 | 0.00 | 0.00 |
September | 1783.00 | 411.89 | 1514.47 | 885.02 | 629.46 | 0.00 | 0.00 |
October | 1425.61 | 563.01 | 1261.71 | 737.54 | 524.17 | 0.00 | 0.00 |
November | 663.38 | 618.67 | 683.21 | 270.96 | 412.25 | 0.00 | 0.00 |
December | 372.43 | 782.98 | 474.59 | 216.22 | 258.38 | 0.00 | 0.00 |
Annual Sum or Average | 1617.96 | 519.07 | 1411.79 | 783.82 | 627.97 | 0.00 | 0.00 |
Minimum of Months | 372.43 | 220.49 | 474.59 | 216.22 | 258.38 | 0.00 | 0.00 |
Maximum of Months | 2779.70 | 881.07 | 2229.89 | 1391.56 | 978.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5375.40 | 9192.68 | 1223.68 | 502.67 | 721.01 | 0.00 | 0.00 |
February | 9225.93 | 9653.70 | 1998.44 | 1080.75 | 917.68 | 0.00 | 0.00 |
March | 15047.22 | 4099.55 | 2993.95 | 1660.78 | 1333.17 | 0.00 | 0.00 |
April | 18671.37 | 2478.55 | 3699.57 | 2085.27 | 1614.29 | 0.00 | 0.00 |
May | 23969.24 | 1849.07 | 4665.58 | 2530.61 | 2134.97 | 0.00 | 0.00 |
June | 25888.28 | 2036.41 | 5096.88 | 2901.74 | 2195.14 | 0.00 | 0.00 |
July | 30588.53 | 2115.94 | 4916.38 | 2680.39 | 2235.99 | 0.00 | 0.00 |
August | 30003.14 | 2915.58 | 5047.50 | 3180.70 | 1866.80 | 0.00 | 0.00 |
September | 17023.30 | 3075.98 | 3461.66 | 2022.90 | 1438.76 | 0.00 | 0.00 |
October | 13809.57 | 3473.89 | 2883.91 | 1685.81 | 1198.10 | 0.00 | 0.00 |
November | 7194.70 | 5073.87 | 1561.63 | 619.34 | 942.29 | 0.00 | 0.00 |
December | 4591.15 | 7146.49 | 1084.78 | 494.21 | 590.57 | 0.00 | 0.00 |
Annual Sum or Average | 16839.91 | 4396.81 | 3226.95 | 1791.59 | 1435.37 | 0.00 | 0.00 |
Minimum of Months | 4591.15 | 1849.07 | 1084.78 | 494.21 | 590.57 | 0.00 | 0.00 |
Maximum of Months | 30588.53 | 9653.70 | 5096.88 | 3180.70 | 2235.99 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.216332E+09 | 0.101970E+10 | 0.399644E+09 | 0.128094E+09 | 0.271550E+09 | 0.00 | 0.00 |
February | 0.325222E+09 | 0.934021E+09 | 0.521357E+09 | 0.181089E+09 | 0.340268E+09 | 0.00 | 0.00 |
March | 0.772751E+09 | 0.622557E+09 | 0.846766E+09 | 0.315263E+09 | 0.531503E+09 | 0.00 | 0.00 |
April | 0.969696E+09 | 0.440186E+09 | 0.907851E+09 | 0.305441E+09 | 0.602410E+09 | 0.00 | 0.00 |
May | 0.132706E+10 | 0.340252E+09 | 0.112899E+10 | 0.337283E+09 | 0.791707E+09 | 0.00 | 0.00 |
June | 0.152356E+10 | 0.251562E+09 | 0.118541E+10 | 0.383355E+09 | 0.802051E+09 | 0.00 | 0.00 |
July | 0.160415E+10 | 0.171208E+09 | 0.115558E+10 | 0.342756E+09 | 0.812829E+09 | 0.00 | 0.00 |
August | 0.169079E+10 | 0.228027E+09 | 0.121758E+10 | 0.454704E+09 | 0.762880E+09 | 0.00 | 0.00 |
September | 0.102098E+10 | 0.372224E+09 | 0.847934E+09 | 0.293615E+09 | 0.554319E+09 | 0.00 | 0.00 |
October | 0.918711E+09 | 0.572475E+09 | 0.843155E+09 | 0.332919E+09 | 0.510237E+09 | 0.00 | 0.00 |
November | 0.296132E+09 | 0.671725E+09 | 0.419843E+09 | 90823697.94 | 0.329019E+09 | 0.00 | 0.00 |
December | 0.205232E+09 | 0.918076E+09 | 0.363875E+09 | 0.124444E+09 | 0.239431E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108706E+11 | 0.654202E+10 | 0.983799E+10 | 0.328979E+10 | 0.654820E+10 | 0.00 | 0.00 |
Minimum of Months | 0.205232E+09 | 0.171208E+09 | 0.363875E+09 | 90823697.94 | 0.239431E+09 | 0.00 | 0.00 |
Maximum of Months | 0.169079E+10 | 0.101970E+10 | 0.121758E+10 | 0.454704E+09 | 0.812829E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111911E+10 | 0.232092E+10 | 0.143391E+10 | 0.589031E+09 | 0.844882E+09 | 0.00 | 0.00 |
February | 0.187389E+10 | 0.213149E+10 | 0.211515E+10 | 0.114387E+10 | 0.971278E+09 | 0.00 | 0.00 |
March | 0.378499E+10 | 0.144815E+10 | 0.350831E+10 | 0.194610E+10 | 0.156220E+10 | 0.00 | 0.00 |
April | 0.480502E+10 | 0.109979E+10 | 0.419531E+10 | 0.236470E+10 | 0.183061E+10 | 0.00 | 0.00 |
May | 0.652678E+10 | 0.925656E+09 | 0.546713E+10 | 0.296537E+10 | 0.250176E+10 | 0.00 | 0.00 |
June | 0.703840E+10 | 0.772428E+09 | 0.577987E+10 | 0.329057E+10 | 0.248929E+10 | 0.00 | 0.00 |
July | 0.727367E+10 | 0.590564E+09 | 0.576101E+10 | 0.314088E+10 | 0.262013E+10 | 0.00 | 0.00 |
August | 0.744515E+10 | 0.804036E+09 | 0.591466E+10 | 0.372714E+10 | 0.218752E+10 | 0.00 | 0.00 |
September | 0.462154E+10 | 0.106763E+10 | 0.392552E+10 | 0.229397E+10 | 0.163155E+10 | 0.00 | 0.00 |
October | 0.381834E+10 | 0.150798E+10 | 0.337937E+10 | 0.197544E+10 | 0.140393E+10 | 0.00 | 0.00 |
November | 0.171948E+10 | 0.160360E+10 | 0.177088E+10 | 0.702331E+09 | 0.106855E+10 | 0.00 | 0.00 |
December | 0.997516E+09 | 0.209713E+10 | 0.127115E+10 | 0.579110E+09 | 0.692035E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.510239E+11 | 0.163694E+11 | 0.445223E+11 | 0.247185E+11 | 0.198037E+11 | 0.00 | 0.00 |
Minimum of Months | 0.997516E+09 | 0.590564E+09 | 0.127115E+10 | 0.579110E+09 | 0.692035E+09 | 0.00 | 0.00 |
Maximum of Months | 0.744515E+10 | 0.232092E+10 | 0.591466E+10 | 0.372714E+10 | 0.262013E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.143975E+11 | 0.246217E+11 | 0.327752E+10 | 0.134636E+10 | 0.193116E+10 | 0.00 | 0.00 |
February | 0.223194E+11 | 0.233542E+11 | 0.483462E+10 | 0.261456E+10 | 0.222006E+10 | 0.00 | 0.00 |
March | 0.403025E+11 | 0.109802E+11 | 0.801898E+10 | 0.444823E+10 | 0.357075E+10 | 0.00 | 0.00 |
April | 0.483962E+11 | 0.642440E+10 | 0.958928E+10 | 0.540503E+10 | 0.418425E+10 | 0.00 | 0.00 |
May | 0.641992E+11 | 0.495254E+10 | 0.124963E+11 | 0.677799E+10 | 0.571831E+10 | 0.00 | 0.00 |
June | 0.671024E+11 | 0.527836E+10 | 0.132111E+11 | 0.752131E+10 | 0.568981E+10 | 0.00 | 0.00 |
July | 0.819283E+11 | 0.566734E+10 | 0.131680E+11 | 0.717916E+10 | 0.598887E+10 | 0.00 | 0.00 |
August | 0.803604E+11 | 0.780908E+10 | 0.135192E+11 | 0.851919E+10 | 0.500005E+10 | 0.00 | 0.00 |
September | 0.441244E+11 | 0.797294E+10 | 0.897261E+10 | 0.524336E+10 | 0.372925E+10 | 0.00 | 0.00 |
October | 0.369875E+11 | 0.930445E+10 | 0.772428E+10 | 0.451529E+10 | 0.320899E+10 | 0.00 | 0.00 |
November | 0.186487E+11 | 0.131515E+11 | 0.404774E+10 | 0.160533E+10 | 0.244241E+10 | 0.00 | 0.00 |
December | 0.122969E+11 | 0.191411E+11 | 0.290548E+10 | 0.132368E+10 | 0.158179E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.531063E+12 | 0.138658E+12 | 0.101765E+12 | 0.564995E+11 | 0.452657E+11 | 0.00 | 0.00 |
Minimum of Months | 0.122969E+11 | 0.495254E+10 | 0.290548E+10 | 0.132368E+10 | 0.158179E+10 | 0.00 | 0.00 |
Maximum of Months | 0.819283E+11 | 0.246217E+11 | 0.135192E+11 | 0.851919E+10 | 0.598887E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.945675E+09 | -874644676.3 | 0.00 | 0.00 | 744.00 | 0.00 | -71029925.2 | 59.00 | 0.00 | 0.00 |
February | 0.875640E+09 | -811513545.8 | 0.00 | 0.00 | 672.00 | 0.00 | -64126933.8 | 58.99 | 0.00 | 0.00 |
March | 0.996849E+09 | -926988885.7 | 0.00 | 0.00 | 744.00 | 0.00 | -69859936.9 | 58.99 | 0.00 | 0.00 |
April | 0.882027E+09 | -817021915.8 | 0.00 | 0.00 | 720.00 | 0.00 | -65004979.5 | 58.99 | 0.00 | 0.00 |
May | 0.852760E+09 | -790947566.9 | 0.00 | 0.00 | 744.00 | 0.00 | -61812420.2 | 59.00 | 0.00 | 0.00 |
June | 0.786553E+09 | -730935437.5 | 0.00 | 0.00 | 720.00 | 0.00 | -55617416.2 | 58.99 | 0.00 | 0.00 |
July | 0.725402E+09 | -669083971.5 | 0.00 | 0.00 | 744.00 | 0.00 | -56318223.2 | 59.00 | 0.00 | 0.00 |
August | 0.765141E+09 | -708610797.1 | 0.00 | 0.00 | 744.00 | 0.00 | -56530042.7 | 58.99 | 0.00 | 0.00 |
September | 0.735668E+09 | -679653150.4 | 0.00 | 0.00 | 720.00 | 0.00 | -56015336.6 | 58.99 | 0.00 | 0.00 |
October | 0.788180E+09 | -726391665.8 | 0.00 | 0.00 | 744.00 | 0.00 | -61788667.5 | 58.99 | 0.00 | 0.00 |
November | 0.818814E+09 | -752095112.7 | 0.00 | 0.00 | 720.00 | 0.00 | -66719203.9 | 59.00 | 0.00 | 0.00 |
December | 0.907433E+09 | -836729642.9 | 0.00 | 0.00 | 744.00 | 0.00 | -70703251.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.100801E+11 | -0.932462E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -755526336.9 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.725402E+09 | -926988885.7 | 0.00 | 0.00 | 672.00 | 0.00 | -71029925.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.996849E+09 | -669083971.5 | 0.00 | 0.00 | 744.00 | 0.00 | -55617416.2 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.50 | 01-JAN-11:50 | 178.00 | 0.00 | 0.00 | 12.17 | 146.29 | 0.00 | 0.00 | 0.00 |
February | 216.00 | 0.72 | 0.50 | 01-FEB-10:30 | 193.15 | 0.00 | 0.00 | 36.33 | 163.87 | 0.00 | 0.00 | 11.00 |
March | 275.00 | 0.66 | 0.50 | 01-MAR-10:50 | 273.59 | 0.00 | 0.00 | 107.50 | 1095.08 | 0.00 | 0.00 | 71.00 |
April | 261.17 | 0.66 | 0.50 | 02-APR-09:30 | 292.82 | 0.00 | 0.00 | 160.17 | 237.33 | 0.00 | 0.00 | 101.50 |
May | 372.00 | 0.63 | 0.50 | 01-MAY-09:09 | 365.10 | 0.00 | 0.00 | 217.00 | 283.75 | 0.00 | 0.00 | 152.33 |
June | 351.83 | 0.63 | 0.50 | 01-JUN-08:50 | 389.00 | 0.00 | 0.00 | 228.50 | 1558.78 | 0.00 | 0.00 | 167.67 |
July | 365.17 | 0.62 | 0.50 | 01-JUL-09:09 | 409.35 | 0.00 | 0.00 | 242.17 | 1604.18 | 0.00 | 0.00 | 178.67 |
August | 389.17 | 0.64 | 0.50 | 01-AUG-09:20 | 342.08 | 0.00 | 0.00 | 203.50 | 276.56 | 0.00 | 0.00 | 154.67 |
September | 285.33 | 0.66 | 0.50 | 01-SEP-09:50 | 284.22 | 0.00 | 0.00 | 137.50 | 1013.61 | 0.00 | 0.00 | 96.17 |
October | 305.50 | 0.67 | 0.50 | 02-OCT-09:50 | 252.27 | 0.00 | 0.00 | 104.50 | 641.50 | 0.00 | 0.00 | 80.00 |
November | 240.83 | 0.71 | 0.50 | 01-NOV-10:30 | 208.48 | 0.00 | 0.00 | 37.67 | 170.60 | 0.00 | 0.00 | 12.00 |
December | 211.17 | 0.81 | 0.50 | 01-DEC-10:50 | 134.99 | 0.00 | 0.00 | 6.33 | 112.75 | 0.00 | 0.00 | 1.33 |
Annual Sum or Average | 3472.67 | 0.67 | 294.04 | 0.00 | 0.00 | 1493.33 | 669.57 | 0.00 | 0.00 | 1026.33 | ||
Minimum of Months | 199.50 | 0.62 | 0.50 | 134.99 | 0.00 | 0.00 | 6.33 | 112.75 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 389.17 | 0.81 | 0.50 | 409.35 | 0.00 | 0.00 | 242.17 | 1604.18 | 0.00 | 0.00 | 178.67 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.62 | 0.50 | 01-JAN-09:50 | 603.64 | 12.93 | 0.00 | 107.67 | 518.57 | 16.41 | 10.17 | 78.33 |
February | 216.00 | 0.62 | 0.50 | 01-FEB-08:00 | 826.47 | 13.24 | 0.00 | 149.33 | 822.15 | 17.02 | 34.50 | 115.67 |
March | 275.00 | 0.58 | 0.50 | 01-MAR-08:20 | 802.98 | 16.22 | 24.83 | 234.17 | 1368.55 | 18.04 | 73.83 | 185.67 |
April | 261.17 | 0.58 | 0.50 | 01-APR-14:39 | 340.42 | 14.63 | 2.50 | 263.50 | 282.70 | 18.53 | 80.50 | 226.83 |
May | 372.00 | 0.56 | 0.50 | 01-MAY-06:30 | 1989.35 | 16.95 | 49.17 | 326.00 | 351.32 | 19.12 | 120.50 | 289.33 |
June | 351.83 | 0.56 | 0.50 | 01-JUN-06:19 | 3323.45 | 16.61 | 47.17 | 322.67 | 1791.22 | 18.89 | 109.67 | 284.67 |
July | 365.17 | 0.56 | 0.50 | 01-JUL-06:40 | 3654.34 | 17.21 | 57.67 | 324.33 | 1969.58 | 20.77 | 130.00 | 301.00 |
August | 389.17 | 0.57 | 0.50 | 01-AUG-06:49 | 1264.44 | 15.55 | 24.50 | 302.17 | 331.96 | 19.00 | 132.50 | 262.50 |
September | 285.33 | 0.58 | 0.50 | 01-SEP-07:40 | 1310.19 | 14.43 | 1.17 | 246.00 | 464.56 | 19.23 | 84.00 | 211.33 |
October | 305.50 | 0.58 | 0.50 | 01-OCT-14:39 | 956.56 | 14.44 | 0.00 | 223.50 | 366.41 | 18.85 | 92.33 | 181.83 |
November | 240.83 | 0.60 | 0.50 | 01-NOV-08:30 | 243.72 | 13.97 | 0.00 | 159.33 | 202.00 | 17.40 | 39.17 | 117.83 |
December | 211.17 | 0.69 | 0.50 | 01-DEC-09:39 | 160.06 | 11.47 | 0.00 | 71.33 | 131.25 | 15.00 | 0.33 | 33.00 |
Annual Sum or Average | 3472.67 | 0.59 | 1469.50 | 15.12 | 207.00 | 2730.00 | 766.38 | 18.46 | 907.50 | 2288.00 | ||
Minimum of Months | 199.50 | 0.56 | 0.50 | 160.06 | 11.47 | 0.00 | 71.33 | 131.25 | 15.00 | 0.33 | 33.00 | |
Maximum of Months | 389.17 | 0.69 | 0.50 | 3654.34 | 17.21 | 57.67 | 326.00 | 1969.58 | 20.77 | 132.50 | 301.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.81 | 0.63 | 29-JAN-15:30 | 291.89 | 23.43 | 95.67 | 24.33 | 112.59 | 20.63 | 82.67 | 0.00 |
February | 216.00 | 0.78 | 0.61 | 11-FEB-16:19 | 476.87 | 24.43 | 116.33 | 47.17 | 161.25 | 22.54 | 111.67 | 9.83 |
March | 275.00 | 0.74 | 0.61 | 01-MAR-14:20 | 451.80 | 25.17 | 168.33 | 85.50 | 344.04 | 25.47 | 192.83 | 50.67 |
April | 261.17 | 0.74 | 0.61 | 01-APR-15:30 | 389.31 | 22.64 | 163.33 | 80.33 | 444.52 | 24.60 | 206.33 | 60.50 |
May | 372.00 | 0.72 | 0.61 | 01-MAY-13:30 | 323.83 | 21.64 | 203.17 | 108.33 | 273.01 | 22.85 | 266.50 | 79.33 |
June | 351.83 | 0.71 | 0.61 | 01-JUN-13:50 | 345.68 | 21.79 | 210.33 | 135.17 | 323.73 | 23.04 | 260.83 | 96.50 |
July | 365.17 | 0.71 | 0.61 | 01-JUL-14:09 | 347.13 | 21.86 | 233.33 | 143.67 | 306.33 | 22.99 | 279.17 | 88.50 |
August | 389.17 | 0.72 | 0.61 | 01-AUG-14:09 | 333.10 | 21.88 | 226.83 | 134.00 | 472.21 | 23.14 | 282.50 | 105.67 |
September | 285.33 | 0.75 | 0.61 | 01-SEP-13:00 | 432.59 | 23.07 | 169.83 | 82.83 | 419.69 | 25.05 | 208.00 | 56.00 |
October | 305.50 | 0.74 | 0.61 | 01-OCT-15:50 | 518.59 | 25.44 | 196.67 | 103.17 | 255.97 | 23.60 | 217.33 | 30.67 |
November | 240.83 | 0.80 | 0.63 | 02-NOV-14:30 | 237.04 | 23.18 | 129.17 | 21.67 | 117.55 | 20.99 | 115.00 | 0.00 |
December | 211.17 | 0.84 | 0.65 | 24-DEC-12:30 | 203.33 | 22.35 | 93.17 | 13.83 | 93.91 | 19.70 | 62.17 | 0.00 |
Annual Sum or Average | 3472.67 | 0.75 | 365.00 | 22.94 | 2006.17 | 980.00 | 295.21 | 23.04 | 2285.00 | 577.67 | ||
Minimum of Months | 199.50 | 0.71 | 0.61 | 203.33 | 21.64 | 93.17 | 13.83 | 93.91 | 19.70 | 62.17 | 0.00 | |
Maximum of Months | 389.17 | 0.84 | 0.65 | 518.59 | 25.44 | 233.33 | 143.67 | 472.21 | 25.47 | 282.50 | 105.67 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.688322E+10 | 25947.70 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.670939E+10 | 25947.70 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433854E+10 | 25947.70 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136769E+10 | 25947.70 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69228159.69 | 25947.70 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 67743271.19 | 14841.49 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276002E+10 | 25947.70 | 01-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.539594E+10 | 25947.70 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.688322E+10 | 25947.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.209451E+11 | 76594.74 | 01-JAN-00:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193228E+11 | 76594.74 | 05-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.699884E+10 | 72662.68 | 22-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116516E+10 | 29379.40 | 05-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.565731E+10 | 71491.96 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151029E+11 | 76594.74 | 31-DEC-19:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.691921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209451E+11 | 76594.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.696842E+11 | 112075.59 | 01-JAN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.668705E+11 | 129891.92 | 06-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161935E+11 | 72238.76 | 22-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.218644E+09 | 12734.39 | 02-APR-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107405E+11 | 71673.25 | 23-NOV-01:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.413841E+11 | 115963.13 | 31-DEC-21:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.696842E+11 | 129891.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 87910779.46 | 83890865.01 | 4227.85 | 07-APR-15:10 | 4227.85 | 0.00 |
May | 0.00 | 0.00 | 0.883918E+09 | 0.811736E+09 | 20621.35 | 31-MAY-07:02 | 13638.36 | 0.00 |
June | 0.00 | 0.00 | 0.684082E+10 | 0.519173E+10 | 23443.32 | 19-JUN-06:02 | 13947.24 | 0.00 |
July | 0.00 | 0.00 | 0.103983E+11 | 0.749035E+10 | 24304.83 | 21-JUL-06:02 | 12753.90 | 0.00 |
August | 0.00 | 0.00 | 0.104594E+11 | 0.813958E+10 | 24284.79 | 04-AUG-06:02 | 12904.98 | 0.00 |
September | 0.00 | 0.00 | 0.472281E+10 | 0.370858E+10 | 23366.70 | 14-SEP-06:03 | 9858.20 | 0.00 |
October | 0.00 | 0.00 | 0.854709E+09 | 0.629850E+09 | 20986.73 | 06-OCT-07:03 | 11368.48 | 0.00 |
November | 0.00 | 0.00 | 108.09 | 102.06 | 0.09 | 04-NOV-16:00 | 0.08 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.342479E+11 | 0.260557E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.104594E+11 | 0.813958E+10 | 24304.83 | 13947.24 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.864575E+09 | 0.678308E+09 | 59674.20 | 31-MAY-17:22 | 34644.15 | 0.00 |
June | 0.00 | 0.00 | 0.954001E+10 | 0.663086E+10 | 65098.40 | 21-JUN-17:22 | 27674.39 | 0.00 |
July | 0.00 | 0.00 | 0.224647E+11 | 0.147307E+11 | 65051.61 | 21-JUL-06:02 | 34775.01 | 0.00 |
August | 0.00 | 0.00 | 0.224849E+11 | 0.159796E+11 | 63162.33 | 06-AUG-09:05 | 28418.16 | 0.00 |
September | 0.00 | 0.00 | 0.535388E+10 | 0.385540E+10 | 55953.16 | 14-SEP-18:05 | 46015.28 | 0.00 |
October | 0.00 | 0.00 | 18711821.64 | 11945907.61 | 2191.60 | 04-OCT-13:30 | 1431.49 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.607267E+11 | 0.418868E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.224849E+11 | 0.159796E+11 | 65098.40 | 46015.28 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.663862E+09 | 0.06 | 320.41 | 01-JAN-00:02 | 0.08 |
February | 0.623442E+09 | 0.06 | 320.41 | 01-FEB-00:03 | 0.08 |
March | 0.296413E+09 | 0.03 | 320.41 | 01-MAR-00:05 | 0.08 |
April | 15187529.87 | 0.00 | 320.41 | 02-APR-02:20 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.169274E+09 | 0.02 | 320.41 | 20-NOV-02:10 | 0.08 |
December | 0.654986E+09 | 0.06 | 320.41 | 01-DEC-00:05 | 0.08 |
Annual Sum or Average | 0.242316E+10 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.663862E+09 | 0.06 | 320.41 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109493E+10 | 0.45 | 1063.73 | 02-JAN-07:17 | 0.91 |
February | 0.100658E+10 | 0.45 | 1063.73 | 01-FEB-07:04 | 0.91 |
March | 0.114997E+10 | 0.38 | 1063.73 | 01-MAR-08:00 | 0.91 |
April | 0.105598E+10 | 0.35 | 1063.73 | 01-APR-06:08 | 0.91 |
May | 0.109522E+10 | 0.35 | 1063.73 | 01-MAY-07:40 | 0.91 |
June | 0.109522E+10 | 0.36 | 1063.73 | 01-JUN-07:50 | 0.90 |
July | 0.105341E+10 | 0.33 | 1063.73 | 01-JUL-06:03 | 0.89 |
August | 0.113772E+10 | 0.36 | 1063.73 | 01-AUG-06:30 | 0.89 |
September | 0.105309E+10 | 0.34 | 1063.73 | 01-SEP-06:10 | 0.89 |
October | 0.105309E+10 | 0.33 | 1063.73 | 02-OCT-12:40 | 0.90 |
November | 0.101906E+10 | 0.35 | 1063.73 | 01-NOV-06:06 | 0.91 |
December | 0.107006E+10 | 0.37 | 1063.73 | 01-DEC-08:63 | 0.91 |
Annual Sum or Average | 0.128843E+11 | 0.37 | |||
Minimum of Months | 0.100658E+10 | 0.33 | 1063.73 | 0.89 | |
Maximum of Months | 0.114997E+10 | 0.45 | 1063.73 | 0.91 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144858E+10 | 0.55 | 2284.11 | 01-JAN-00:06 | 0.88 |
February | 0.133016E+10 | 0.55 | 2284.11 | 05-FEB-05:23 | 0.88 |
March | 0.116346E+10 | 0.39 | 2166.86 | 22-MAR-05:01 | 0.88 |
April | 0.936389E+09 | 0.24 | 1439.31 | 05-APR-06:01 | 0.70 |
May | 0.943736E+09 | 0.21 | 913.64 | 31-MAY-10:00 | 0.53 |
June | 0.995432E+09 | 0.23 | 2284.11 | 19-JUN-17:10 | 0.87 |
July | 0.106859E+10 | 0.27 | 2284.11 | 02-JUL-13:13 | 0.87 |
August | 0.112216E+10 | 0.28 | 2284.11 | 01-AUG-17:10 | 0.87 |
September | 0.936679E+09 | 0.22 | 2284.11 | 04-SEP-13:33 | 0.87 |
October | 0.904508E+09 | 0.20 | 913.64 | 04-OCT-14:20 | 0.52 |
November | 0.102032E+10 | 0.34 | 2131.94 | 24-NOV-06:01 | 0.88 |
December | 0.129974E+10 | 0.53 | 2284.11 | 31-DEC-19:23 | 0.88 |
Annual Sum or Average | 0.131697E+11 | 0.33 | |||
Minimum of Months | 0.904508E+09 | 0.20 | 913.64 | 0.52 | |
Maximum of Months | 0.144858E+10 | 0.55 | 2284.11 | 0.88 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.109493E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.100658E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.114997E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.107437E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.127113E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.240791E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.304612E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.317936E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.195272E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.121987E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.101906E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.107006E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.194921E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.100658E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.317936E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.144858E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133016E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.116346E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.936389E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.114939E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.319676E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.617253E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.629082E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.216087E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.909066E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.102032E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.129974E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.270781E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.909066E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.629082E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109493E+10 | 0.00 | 0.688322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100658E+10 | 0.00 | 0.670939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114997E+10 | 0.00 | 0.433854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105598E+10 | 87910779.46 | 0.136769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109522E+10 | 0.883918E+09 | 69228159.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109522E+10 | 0.684082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105341E+10 | 0.103983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113772E+10 | 0.104594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105309E+10 | 0.472281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105309E+10 | 0.854709E+09 | 67743271.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101906E+10 | 108.09 | 0.276002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107006E+10 | 0.00 | 0.539594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128843E+11 | 0.342479E+11 | 0.275918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114997E+10 | 0.104594E+11 | 0.688322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144858E+10 | 0.00 | 0.209451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133016E+10 | 0.00 | 0.193228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116346E+10 | 0.00 | 0.699884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.936389E+09 | 0.00 | 0.116516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.943736E+09 | 0.856126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.995432E+09 | 0.941265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106859E+10 | 0.224157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112216E+10 | 0.222227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.936679E+09 | 0.522842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.904508E+09 | 18711821.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102032E+10 | 0.00 | 0.565731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129974E+10 | 0.00 | 0.151029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131697E+11 | 0.601542E+11 | 0.691921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.904508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144858E+10 | 0.224157E+11 | 0.209451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105598E+10 | 0.00 | 0.00 | 0.00 | 18391216.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109522E+10 | 0.00 | 0.00 | 0.00 | 0.175914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109522E+10 | 0.00 | 0.00 | 0.00 | 0.131269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105341E+10 | 0.00 | 0.00 | 0.00 | 0.199270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113772E+10 | 0.00 | 0.00 | 0.00 | 0.204164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105309E+10 | 0.00 | 0.00 | 0.00 | 0.899627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105309E+10 | 0.00 | 0.00 | 0.00 | 0.166779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101906E+10 | 0.00 | 0.00 | 0.00 | 23.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128843E+11 | 0.00 | 0.00 | 0.00 | 0.660774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114997E+10 | 0.00 | 0.00 | 0.00 | 0.204164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.936389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.943736E+09 | 0.00 | 0.00 | 0.00 | 0.205654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.995432E+09 | 0.00 | 0.00 | 0.00 | 0.220132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106859E+10 | 0.00 | 0.00 | 0.00 | 0.510394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112216E+10 | 0.00 | 0.00 | 0.00 | 0.516867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.936679E+09 | 0.00 | 0.00 | 0.00 | 0.122419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.904508E+09 | 0.00 | 0.00 | 0.00 | 4557861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131697E+11 | 0.00 | 0.00 | 0.00 | 0.139083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.904508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144858E+10 | 0.00 | 0.00 | 0.00 | 0.516867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 21492144.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215529E+10 | 0.00 | 0.00 | 0.12 |
February | 21318504.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210556E+10 | 0.00 | 0.00 | 0.12 |
March | 0.185305E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168062E+10 | 0.00 | 0.00 | 0.13 |
April | 0.537867E+09 | 1669267.23 | 0.00 | 179386.31 | 37005.71 | 0.616184E+09 | 0.242661E+09 | 0.00 | 0.17 |
May | 0.355789E+09 | 35985540.15 | 0.00 | 2028557.46 | 297534.83 | 11600947.31 | 0.171490E+10 | 0.00 | 0.39 |
June | 10029419.00 | 0.549162E+09 | 0.00 | 3437068.37 | 5254734.86 | 0.00 | 0.858718E+09 | 0.00 | 0.39 |
July | 433881.26 | 0.139753E+10 | 0.00 | 1350357.55 | 7777456.62 | 0.00 | 48703091.33 | 0.00 | 0.15 |
August | 4985800.06 | 0.117321E+10 | 0.00 | 2502595.00 | 6386269.35 | 0.00 | 0.231998E+09 | 0.00 | 0.24 |
September | 26779978.81 | 0.312840E+09 | 0.00 | 4291273.30 | 3758264.80 | 0.00 | 0.168239E+10 | 0.00 | 0.49 |
October | 0.359832E+09 | 22380663.09 | 0.00 | 2188244.32 | 757055.40 | 9275398.26 | 0.181761E+10 | 0.00 | 0.39 |
November | 0.345735E+09 | 0.00 | 0.00 | 12529.41 | 0.00 | 0.113745E+10 | 36550950.38 | 0.00 | 0.12 |
December | 24245802.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201906E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.189381E+10 | 0.349278E+10 | 0.00 | 15990011.72 | 24268321.56 | 0.973505E+10 | 0.663354E+10 | 0.00 | 0.24 |
Minimum of Months | 433881.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.537867E+09 | 0.139753E+10 | 0.00 | 4291273.30 | 7777456.62 | 0.215529E+10 | 0.181761E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.275374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361800E+10 | 0.00 | 0.00 | 0.17 |
February | 0.278308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361032E+10 | 0.00 | 0.00 | 0.18 |
March | 0.450638E+10 | 0.00 | 0.00 | 0.00 | 9098109.88 | 0.698168E+09 | 0.00 | 0.00 | 0.19 |
April | 0.356135E+10 | 0.00 | 0.00 | 0.00 | 12408715.92 | 74521124.05 | 0.00 | 0.00 | 0.18 |
May | 0.346172E+10 | 55284179.14 | 0.00 | 159882.85 | 202977.09 | 0.00 | 25017422.66 | 0.00 | 0.19 |
June | 0.600256E+09 | 0.938678E+09 | 0.00 | 5118800.77 | 336266.53 | 0.00 | 0.237012E+10 | 0.00 | 0.30 |
July | 90743.14 | 0.386429E+10 | 0.00 | 1513398.55 | 0.00 | 0.00 | 0.377268E+09 | 0.00 | 0.21 |
August | 33907078.18 | 0.373955E+10 | 0.00 | 6816137.66 | 0.00 | 0.00 | 0.103894E+10 | 0.00 | 0.27 |
September | 0.175351E+10 | 0.440111E+09 | 0.00 | 3823336.86 | 0.00 | 0.00 | 0.183034E+10 | 0.00 | 0.26 |
October | 0.389352E+10 | 0.00 | 0.00 | 138379.09 | 0.00 | 0.00 | 0.136960E+09 | 0.00 | 0.18 |
November | 0.364547E+10 | 0.00 | 0.00 | 0.00 | 330234.79 | 0.539709E+09 | 0.00 | 0.00 | 0.17 |
December | 0.335305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242660E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.303461E+11 | 0.903791E+10 | 0.00 | 17569935.79 | 22376304.21 | 0.109673E+11 | 0.577866E+10 | 0.00 | 0.21 |
Minimum of Months | 90743.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.450638E+10 | 0.386429E+10 | 0.00 | 6816137.66 | 12408715.92 | 0.361800E+10 | 0.237012E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:44:05
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.226711E+12 | 0.770808E+11 | 0.00 | 0.854852E+10 | 0.286045E+11 |
February | 0.407214E+12 | 0.742344E+11 | 0.00 | 0.852028E+10 | 0.272062E+11 |
March | 0.753304E+12 | 0.450300E+11 | 0.00 | 0.712936E+10 | 0.910286E+10 |
April | 0.830280E+12 | 0.262739E+11 | 0.00 | 0.505683E+10 | 0.137647E+10 |
May | 0.111357E+13 | 0.230113E+11 | 0.00 | 0.547945E+10 | 0.216257E+10 |
June | 0.111267E+13 | 0.289676E+11 | 0.00 | 0.236917E+10 | 0.198948E+11 |
July | 0.110621E+13 | 0.276617E+11 | 0.00 | -0.483304E+10 | 0.399597E+11 |
August | 0.108058E+13 | 0.327795E+11 | 0.00 | -0.344856E+10 | 0.401546E+11 |
September | 0.744564E+12 | 0.342941E+11 | 0.00 | 0.456594E+10 | 0.122005E+11 |
October | 0.677921E+12 | 0.409951E+11 | 0.00 | 0.619639E+10 | 0.107820E+10 |
November | 0.286667E+12 | 0.461106E+11 | 0.00 | 0.570460E+10 | 0.640442E+10 |
December | 0.167383E+12 | 0.580716E+11 | 0.00 | 0.782296E+10 | 0.192385E+11 |
Annual Sum or Average | 0.850708E+13 | 0.514511E+12 | 0.00 | 0.531119E+11 | 0.207383E+12 |
Minimum of Months | 0.167383E+12 | 0.230113E+11 | 0.00 | -0.483304E+10 | 0.107820E+10 |
Maximum of Months | 0.111357E+13 | 0.770808E+11 | 0.00 | 0.854852E+10 | 0.401546E+11 |