Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 10:44:01
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1588.18 | 328.47 | 328.47 |
Net Site Energy | 1588.18 | 328.47 | 328.47 |
Total Source Energy | 2525.35 | 522.29 | 522.29 |
Net Source Energy | 2525.35 | 522.29 | 522.29 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1202.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 128.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 385.87 | 1202.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1202.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 3.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 128.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 27.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1202.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 128.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 28.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 27.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 39.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 12.21 | 248.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 79.81 | 248.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 39.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 12.21 | 248.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 79.81 | 248.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 385.868 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 385.868 | 100.00 |
Total On-Site and Utility Electric Sources | 385.868 | 100.00 |
Total Electricity End Uses | 385.868 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 76.83 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3055.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.0858 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.1969 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3435 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3435 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.0858 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.1969 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.3435 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.3435 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.3435 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-14:00 | 04-JAN-17:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 259009.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7297.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9081.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1739.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1874.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30028.30 | 259009.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 259009.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7297.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9081.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1739.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1874.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1303.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 11.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 406.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 196.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 89.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 86.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1222.04 | 1303.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 84.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 252.74 | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 84.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 252.74 | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.908473 |
ZONE2 FINE STORAGE DIRECT AIR | 1.46 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 3.39 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 3.39 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 133094.40 |
PSZ-OFFICE HEATING COIL | 26335.59 |
PSZ-FINE STORAGE HEATING COIL | 65046.93 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 133094.41 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.908473 | 0.908473 | 0.908473 | 0.908473 | 0.908473 | 0.908473 | 1.00 | 1.000000 | 0.908473 |
PSZ-FINE STORAGE | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.00 | 1.00 | 1.46 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.908473 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.46 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.908473 | 1005.82 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.46 | 1558.60 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.908473 | 0.908473 | 0.908473 | 0.908473 | 16249.45 | 26335.59 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.46 | 1.46 | 1.46 | 0.961334 | 35195.16 | 65046.93 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.908470 | 0.454236 | 0.605647 | 16249.45 | 8124.73 | 0.800260 | 0.800260 |
PSZ-FINE STORAGE COOLING COIL | 1.46 | 0.728284 | 0.971047 | 35195.16 | 17597.58 | 0.709870 | 0.709870 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.086 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.160 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.197 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.756 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1441.602 | 6.086 | 113.078 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1441.602 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10245.499 | 3.197 | 148.485 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10245.499 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.3594 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.3594 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1333 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5514E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.5162E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.3594 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.683 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.683 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.423 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.06 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 19.29 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.683 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
2 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
3 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
4 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
5 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
6 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
7 | 4 | 0.80665485E-12 | 0.79663208E-16 | -0.19922917E-14 | 0.11242754E-15 |
8 | 3 | -0.39309894E-03 | 0.25494770E-06 | -0.57103696E-04 | 0.15477097E-12 |
9 | 2 | 1.7593081 | 0.55246375E-02 | 1.1554888 | -0.75363915E-04 |
10 | 1 | -7.1027742 | 0.14233178 | -17.193999 | 0.33719959 |
11 | 0 | 5.5821243 | 0.90408510E-01 | 16.276832 | |
12 | 4 | 0.80665485E-12 | 0.79663208E-16 | -0.19922917E-14 | 0.11242754E-15 |
13 | 3 | -0.39309894E-03 | 0.25494770E-06 | -0.57103696E-04 | 0.15477097E-12 |
14 | 2 | 1.7593081 | 0.55246375E-02 | 1.1554888 | -0.75363915E-04 |
15 | 1 | -7.1027742 | 0.14233178 | -17.193999 | 0.33719959 |
16 | 0 | 5.5821243 | 0.90408510E-01 | 16.276832 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.31875017E-08 | -0.23223167E-14 | 0.11745088E-14 | -0.42051331E-16 |
55 | 6 | 0.38616340E-05 | 0.25494915E-08 | 0.31950331E-02 | -0.26802615E-04 |
56 | 5 | -0.27022284E-03 | 0.15072689E-05 | -0.22401801 | 0.19587403E-02 |
57 | 4 | 0.61670379E-02 | 0.68550054E-04 | 4.8344327 | -0.45311958E-01 |
58 | 3 | -0.54002887E-01 | 0.54467183E-03 | -38.049021 | 0.39895888 |
59 | 2 | 0.19154071 | 0.90547994E-03 | 116.53767 | -1.4186579 |
60 | 1 | -0.27632409 | 0.27557907E-03 | -143.93893 | 2.0495597 |
61 | 0 | 0.13468807 | 0.66882102E-05 | 60.838472 | |
62 | 7 | -0.77687407E-08 | 0.22327722E-15 | -0.37072247E-14 | 0.17899991E-16 |
63 | 6 | 0.20649052E-05 | 0.10720148E-08 | 0.32011002E-02 | -0.26853511E-04 |
64 | 5 | -0.12245401E-03 | 0.62775152E-06 | -0.22436262 | 0.19617821E-02 |
65 | 4 | 0.26426329E-02 | 0.28408139E-04 | 4.8401680 | -0.45367094E-01 |
66 | 3 | -0.22645990E-01 | 0.22478354E-03 | -38.081398 | 0.39931679 |
67 | 2 | 0.79613263E-01 | 0.37221057E-03 | 116.60066 | -1.4195005 |
68 | 1 | -0.11438919 | 0.11271005E-03 | -143.97600 | 2.0501690 |
69 | 0 | 0.55641142E-01 | 0.27215667E-05 | 60.838472 | |
70 | 7 | -0.83009558E-08 | 0.33403291E-15 | -0.19532641E-14 | 0.15868102E-16 |
71 | 6 | 0.20088932E-05 | 0.10070834E-08 | 0.32013735E-02 | -0.26855804E-04 |
72 | 5 | -0.11642674E-03 | 0.58876086E-06 | -0.22437813 | 0.19619190E-02 |
73 | 4 | 0.24904828E-02 | 0.26622057E-04 | 4.8404258 | -0.45369573E-01 |
74 | 3 | -0.21265961E-01 | 0.21050699E-03 | -38.082852 | 0.39933286 |
75 | 2 | 0.74649925E-01 | 0.34834796E-03 | 116.60348 | -1.4195383 |
76 | 1 | -0.10718390 | 0.10539310E-03 | -143.97766 | 2.0501963 |
77 | 0 | 0.52117880E-01 | 0.25440643E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.19922917E-14 | 0.79663208E-16 | 0.80665485E-12 | 0.11242754E-15 |
85 | 3 | -0.57103696E-04 | 0.25494770E-06 | -0.39309894E-03 | 0.15477097E-12 |
86 | 2 | 1.1554888 | 0.55246375E-02 | 1.7593081 | -0.75363915E-04 |
87 | 1 | -17.193999 | 0.14233178 | -7.1027742 | 0.33719959 |
88 | 0 | 16.276832 | 0.90408510E-01 | 5.5821243 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.2918_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.2918_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.2918_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.2918_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.6 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.24991E-002 | 0.31435 | 0.48861 | 0.48861 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.90509E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.24991E-002 | 0.31435 | 0.48861 | 0.48861 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.90509E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.24991E-002 | 0.31435 | 0.48861 | 0.48861 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.90509E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.24991E-002 | 0.31435 | 0.48861 | 0.48861 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.90509E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.056 | 0.5354 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.605 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 3.407E-002 | 1.438E-004 | 2.220E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.173 | 1.244E-004 | 7.923E-005 | 0.211 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.168 | 6.763E-004 | 4.417E-004 | 0.221 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2735E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9430E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0239E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4660E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4409E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4814E-004 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1956E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0107E-003 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7437E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7844E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6826E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7197E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0404E-003 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3687E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0668E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3870E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6547E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3917E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9433E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1315E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5057E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4798E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1712E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1460E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2350E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7844E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0723E-003 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0373E-003 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6554E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0770E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8710E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4783E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.6884E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.7718E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.1108E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.1014E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.8492E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.7748E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.8588E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.0150E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.9649E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.3546E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.4749E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.3655E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.8955E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.2591E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.9581E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.8441E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.5855E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.9825E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.2222E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1400E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.8304E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.3275E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.5867E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0556E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.8277E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.9909E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.3444E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1445E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.6077E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3225E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.5866E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.0556E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 8817.74597 | 10581.29516 | 0.75706 | 0.90847 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27228E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10320.42398 | 12384.50878 | 0.30231 | 0.36277 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -32.70000 | 1.83376E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 18135.83215 | 21762.99859 | 1.21381 | 1.45657 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 29.85200 | 1.27254E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 30476.54404 | 36571.85285 | 0.75200 | 0.90240 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -32.70000 | 1.83376E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 110912.00816 | 133094.40979 | 2.82779 | 3.39335 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13078.11 | 0.90847 | 0.90847 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 14345.57 | 0.36277 | 0.36277 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 26453.03 | 1.45657 | 1.45657 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 49340.77 | 0.90240 | 0.90240 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90847 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.45657 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.39335 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 3.39335 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 133094.39930 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 133094.40979 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.90847 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.90847 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.90847 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.90847 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.90847 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.90847 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.45657 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45657 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.45657 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.45657 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.45657 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.45657 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.90847 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.45657 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.90847 |
26 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.90847 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1005.82362 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.90847 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.90847 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.90847 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90847 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.90847 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45424 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.60565 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16249.45000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8124.72500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80026 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80026 |
39 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16249.45000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26335.59011 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
43 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26335.59011 |
44 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.45657 |
45 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.45657 |
46 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1558.59592 |
47 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.45657 |
48 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.45657 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.45657 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96133 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.45657 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72828 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97105 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35195.16000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17597.58000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70987 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70987 |
58 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35195.16000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 65046.93167 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 65046.93167 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 15544.3 | 13.33 | 13.03 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 34063.1 | 13.23 | 12.92 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.4206173954 | 0.3853805851 | Pass | Pass | 1.8122975459 | 4.3246650979 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.7623699277 | 0.6944160070 | Pass | Pass | 0.7233254479 | 0.6443025104 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.7159680415E-005 | 9.9861438193E-005 | Pass | Pass | 2.2181413224E-002 | 1.8930867548E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7541.27 | 726.70 | 0.00 | 106.30 | 289.16 | 8663.47 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.341 | 0.359 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.341 | 0.359 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.131 | 0.133 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.341 | 0.359 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.341 | 0.359 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.341 | 0.359 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.341 | 0.359 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.341 | 0.359 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.055 | 0.055 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.165 | 0.168 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.341 | 0.359 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.341 | 0.359 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.341 | 0.359 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.051 | 0.052 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.165 | 0.168 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.331 | 0.359 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.331 | 0.359 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.2918_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.657 | 0.401 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.2918_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.657 | 0.401 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.2918_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.657 | 0.401 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.2918_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.657 | 0.401 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 2.848 | 0.494 | 0.493 | |||||||||||||||||
North Total or Average | 6.51 | 1.657 | 0.401 | 0.401 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.145 | 0.517 | 0.516 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.0858 | 236.88 | 1441.60 | LightsWired | LTG_SCH_OFFICE | 47.92 | 168.00 | 39.18 | 0.0000 | Y | 10.60 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 33.37 | 0.0000 | Y | 58.34 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.1969 | 3204.84 | 10245.50 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 30.91 | 0.0000 | Y | 59.44 |
Interior Lighting Total | 4.3435 | 4835.13 | 21001.18 | 128.39 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.12 | 10245.50 | 1188.48 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1441.60 | 418.06 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1441.60 | 144.16 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 93.17 | AstronomicalClock | - | 42.55 | 42.55 | 0.74 | |
EXTERIOR_LIGHTS_B | 4307.58 | AstronomicalClock | - | 83.52 | 63.04 | 50.97 | |
EXTERIOR_LIGHTS_C | 1091.85 | AstronomicalClock | - | 83.52 | 49.92 | 10.23 | |
Exterior Lighting Total | 5492.60 | 61.95 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16249.45 | 13003.78 | 3245.67 | 0.80 | 4.53 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35195.16 | 24983.99 | 10211.17 | 0.71 | 4.18 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 15544.3 | 13.33 | 13.03 | ||||
PSZ-FINE STORAGE COOLING COIL | 34063.1 | 13.23 | 12.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 133094.40 | 0.81 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26335.59 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 65046.93 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.39 | 315.28 | 92.91 | 1.00 | 3.30 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.91 | 1005.82 | 1107.16 | 1.00 | 1.43 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.46 | 1558.60 | 1070.05 | 1.00 | 1.37 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.54 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8817.75 | 10581.30 | 44.67 | 0.757 | 0.908 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00844 | 28.36 | 0.01272 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 18135.83 | 21763.00 | 15.62 | 1.214 | 1.457 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 26.70 | 26.70 | 0.00903 | 29.85 | 0.01273 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 30.10 | 0.01279 | 29.98 | 0.01273 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10320.42 | 12384.51 | 52.28 | 0.302 | 0.363 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00806 | -32.70 | 0.00018 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 30476.54 | 36571.85 | 26.25 | 0.752 | 0.902 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00720 | -32.70 | 0.00018 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 110912.01 | 133094.41 | 41.53 | 2.828 | 3.393 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00564 | -32.70 | 0.00018 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.91 | 0.91 | 0.36 | 0.36 | 0.9085 | 0.9085 | 0.9085 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.46 | 1.46 | 0.90 | 0.90 | 1.4566 | 1.4566 | 1.4566 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 133094.399 | 133094.399 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 133094.40 | 133094.40 | 3.393354 | 10.00 | 7.44 | 0.00564181 | 43.33 | 21.64 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 10.00 | 0.00564181 | 71.0837 | 133094.41 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 16249.450 | 13003.785 | 0.908470 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 8124.73 | 7056.34 | 0.605647 | 25.38 | 16.79 | 0.00892824 | 12.00 | 10.89 | 0.00800000 | 28.69 | 0.01272339 | 20.72 | 16.8885 | 23.90 | 0.00844566 | 43.8370 | 8800.38 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26335.590 | 26335.590 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26335.59 | 26335.59 | 0.908473 | 15.00 | 11.30 | 0.00717523 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 11.2590 | 21.10 | 0.00806231 | 49.6348 | 10320.42 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 35195.160 | 24983.988 | 1.456570 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 17597.58 | 13697.74 | 0.971047 | 28.60 | 18.78 | 0.01010722 | 12.00 | 10.89 | 0.00800000 | 30.10 | 0.01272586 | 21.13 | 43.7375 | 26.70 | 0.00902655 | 39.6291 | 18102.06 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 65046.932 | 65046.932 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 65046.93 | 65046.93 | 1.456567 | 1.49 | 1.49 | 0.00515538 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 29.1584 | 15.56 | 0.00720186 | 62.8675 | 30476.54 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 133094.399 | 133094.399 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 3.393354 | 3.91567534 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 133094.40 | 133094.40 | 1.0000 | 3.91567534 | 3.393354 | 10.00 | 7.44 | 0.00564181 | 24260.0 | 43.33 | 21.64 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 133094.40 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 10.00 | 0.00564181 | 10.00 | 0.00564181 | 71.0837 | 133094.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16249.450 | 13003.785 | 0.908470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4371 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.908473 | 1.04830937 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 8124.73 | 7056.34 | 1.0000 | 0.69887074 | 0.605647 | 25.38 | 16.79 | 0.00892824 | 48252.0 | 12.00 | 10.89 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8124.73 | 28.69 | 0.01272339 | 20.72 | 0.10228460 | 16.8885 | 23.90 | 0.00844566 | 23.90 | 0.00844566 | 43.8370 | 8800.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26335.590 | 26335.590 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.908473 | 1.04830937 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26335.59 | 26335.59 | 1.0000 | 1.04830937 | 0.908473 | 15.00 | 11.30 | 0.00717523 | 33217.0 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26335.59 | -32.70 | 0.00018338 | -32.70 | 0.10228460 | 11.2590 | 21.05 | 0.00806231 | 21.10 | 0.00806231 | 49.6348 | 10320.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35195.160 | 24983.988 | 1.456570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6288 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.456567 | 1.68076927 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 17597.58 | 13697.74 | 1.0000 | 1.12051489 | 0.971047 | 28.60 | 18.78 | 0.01010722 | 54551.0 | 12.00 | 10.89 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17597.58 | 30.10 | 0.01272586 | 21.13 | 0.42471127 | 43.7375 | 26.70 | 0.00902655 | 26.70 | 0.00902655 | 39.6291 | 18102.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 65046.932 | 65046.932 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.456567 | 1.68076927 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 65046.93 | 65046.93 | 1.0000 | 1.68076927 | 1.456567 | 1.49 | 1.49 | 0.00515538 | 14401.2 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65046.93 | -32.70 | 0.00018338 | -32.70 | 0.42471127 | 29.1584 | 15.56 | 0.00720186 | 15.56 | 0.00720186 | 62.8675 | 30476.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.91 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.46 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
ZONE1 OFFICE | ZONE1_OFFICE_DCV | 0.002360 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
ZONE2 FINE STORAGE | ZONE2_FINE_STORAGE_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2889.67 | 3066.67 | 2434.33 |
ZONE2 FINE STORAGE | 3154.17 | 3231.00 | 2821.00 |
ZONE3 BULK STORAGE | 3211.67 | 3328.17 | 2955.00 |
Facility | 3376.50 | 3389.33 | 3055.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 112.83 | 0.00 | 50.17 | 0.00 |
ZONE2 FINE STORAGE | 518.67 | 0.83 | 25.50 | 0.00 |
ZONE3 BULK STORAGE | 40.00 | 0.00 | 16.83 | 0.00 |
Facility | 619.67 | 0.83 | 76.83 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.567 | 0.374 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.446 | 0.098 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.121 | 0.000 | 0.057 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.072 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.29 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.04 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.474 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2042195.52 | 0.00 | 2042195.52 | 1664415.46 | 3706610.98 | 2577844.23 | 5719.88 | 2389.57 | 650.56 | 0.00 |
ZONE2 FINE STORAGE | 4762971.74 | 0.00 | 4762971.74 | 2642470.95 | 7405442.69 | 13393694.68 | 5728.83 | 2873.67 | 157.50 | 0.50 |
ZONE3 BULK STORAGE | 0.00 | 15949858.85 | 15949858.85 | 30794821.73 | 46744680.58 | 30805497.77 | 8272.00 | 55.83 | 432.17 | 4777.50 |
Total Facility | 6805167.26 | 15949858.85 | 22755026.11 | 35101708.13 | 57856734.24 | 46777036.68 | 8505.67 | 3004.56 | 1160.45 | 4777.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1560 | 0.0000 | 0.1560 | 0.1038 | 0.2599 | 0.0952 | 595.88 | 2389.57 | 650.56 |
ZONE2 FINE STORAGE | 0.3638 | 0.0000 | 0.3638 | 0.0801 | 0.4439 | 0.4247 | 605.33 | 2873.67 | 157.00 |
ZONE3 BULK STORAGE | 0.0000 | 0.5637 | 0.5637 | 1.2023 | 1.7659 | 0.9768 | 3366.17 | 27.83 | 242.00 |
Total Facility | 0.5198 | 0.5637 | 1.0835 | 1.3862 | 2.4697 | 1.4967 | 3381.67 | 2976.56 | 969.78 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2719270.28 | 0.00 | 2719270.28 | 2577844.23 | 5719.38 | 0.00 | 3040.62 | 0.00 |
PSZ-FINE STORAGE | 6342417.17 | 0.00 | 6342417.17 | 13393694.68 | 5728.83 | 0.00 | 3031.17 | 0.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2077 | 0.0000 | 0.2077 | 0.0952 | 595.38 | 0.00 | 3040.62 |
PSZ-FINE STORAGE | 0.4844 | 0.0000 | 0.4844 | 0.4247 | 605.33 | 0.00 | 3030.67 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 353.66 | 298.56 | 0.00 | 0.00 | 0.00 | 2389.40 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 131.17 | 37.14 | 0.00 | 0.00 | 0.00 | 2862.86 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.8484 | 0.4783 | 0.0000 | 0.0000 | 0.0000 | 0.1312 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.9006 | 0.6823 | 0.0000 | 0.0000 | 0.0000 | 0.5657 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 390 |
Defaulted Fields | 317 |
Fields with Defaults | 1047 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 385.87 | 2078.59 | 16-APR-13:50 | 30028.30 | 30-JUN-15:00 |
Electricity:Building | 264.90 | 1595.59 | 02-APR-14:30 | 19911.39 | 15-NOV-16:00 |
Electricity:Zone:ZONE1 OFFICE | 39.77 | 585.18 | 19-FEB-15:10 | 2643.62 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 264.90 | 1595.59 | 02-APR-14:30 | 19911.39 | 15-NOV-16:00 |
InteriorLights:Electricity | 128.39 | 1125.71 | 02-APR-14:30 | 9876.22 | 15-NOV-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.60 | 115.30 | 19-FEB-15:10 | 808.57 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 128.39 | 1125.71 | 02-APR-14:30 | 9876.22 | 15-NOV-16:00 |
LightsWired:InteriorLights:Electricity | 128.39 | 1125.71 | 02-APR-14:30 | 9876.22 | 15-NOV-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.60 | 115.30 | 19-FEB-15:10 | 808.57 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 128.39 | 1125.71 | 02-APR-14:30 | 9876.22 | 15-NOV-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 58.34 | 512.27 | 01-JAN-00:10 | 4354.33 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 58.34 | 512.27 | 01-JAN-00:10 | 4354.33 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 58.34 | 512.27 | 01-JAN-00:10 | 4354.33 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 166.79 | 498.14 | 08-JAN-10:50 | 12950.01 | 20-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 59.44 | 498.14 | 08-JAN-10:50 | 4749.89 | 20-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 59.44 | 498.14 | 08-JAN-10:50 | 4749.89 | 20-DEC-16:00 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 28.18 | 0.00 | 19-MAR-14:00 | 2656.93 | 09-JAN-08:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 385.87 | 2078.59 | 16-APR-13:50 | 30028.30 | 30-JUN-15:00 |
ElectricityPurchased:Plant | 385.87 | 2078.59 | 16-APR-13:50 | 30028.30 | 30-JUN-15:00 |
Cogeneration:ElectricityPurchased | 385.87 | 2078.59 | 16-APR-13:50 | 30028.30 | 30-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 385.87 | 2078.59 | 16-APR-13:50 | 30028.30 | 30-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 385.87 | 2078.59 | 16-APR-13:50 | 30028.30 | 30-JUN-15:00 |
ElectricityNet:Plant | 385.87 | 2078.59 | 16-APR-13:50 | 30028.30 | 30-JUN-15:00 |
Cogeneration:ElectricityNet | 385.87 | 2078.59 | 16-APR-13:50 | 30028.30 | 30-JUN-15:00 |
General:Cogeneration:ElectricityNet | 385.87 | 2078.59 | 16-APR-13:50 | 30028.30 | 30-JUN-15:00 |
Electricity:HVAC | 31.69 | 0.00 | 19-MAR-14:00 | 9488.24 | 29-JUN-16:00 |
General:Fans:Electricity | 28.18 | 0.00 | 19-MAR-14:00 | 2656.93 | 09-JAN-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 3.51 | 0.00 | 01-JAN-00:10 | 7739.62 | 29-JUN-16:00 |
General:Cooling:Electricity | 3.51 | 0.00 | 01-JAN-00:10 | 7739.62 | 29-JUN-16:00 |
ExteriorLights:Electricity | 61.95 | 0.00 | 01-JAN-08:20 | 5492.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.95 | 0.00 | 01-JAN-08:20 | 5492.60 | 01-JAN-06:10 |
Electricity:Plant | 27.33 | 483.00 | 02-JAN-06:10 | 3095.64 | 25-FEB-12:10 |
WaterSystems:Electricity | 27.33 | 483.00 | 02-JAN-06:10 | 3095.64 | 25-FEB-12:10 |
Water Heater:WaterSystems:Electricity | 27.33 | 483.00 | 02-JAN-06:10 | 3095.64 | 25-FEB-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1202.31 | 0.00 | 19-MAR-13:50 | 259009.08 | 04-JAN-18:00 |
NaturalGas:HVAC | 1202.31 | 0.00 | 19-MAR-13:50 | 259009.08 | 04-JAN-18:00 |
Heating:NaturalGas | 1202.31 | 0.00 | 19-MAR-13:50 | 259009.08 | 04-JAN-18:00 |
General:Heating:NaturalGas | 1202.31 | 0.00 | 19-MAR-13:50 | 259009.08 | 04-JAN-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1861.73 | 0.00 | 19-MAR-14:00 | 388446.77 | 04-JAN-18:00 |
EnergyTransfer:Building | 909.61 | 0.00 | 19-MAR-14:00 | 192672.05 | 04-JAN-07:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 67.38 | 0.00 | 01-JAN-00:40 | 27351.90 | 09-JAN-08:00 |
Heating:EnergyTransfer | 880.52 | 0.00 | 19-MAR-14:00 | 192672.05 | 04-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 56.56 | 0.00 | 01-JAN-00:40 | 27351.90 | 09-JAN-08:00 |
General:Heating:EnergyTransfer | 880.52 | 0.00 | 19-MAR-14:00 | 192672.05 | 04-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 56.56 | 0.00 | 01-JAN-00:40 | 27351.90 | 09-JAN-08:00 |
Cooling:EnergyTransfer | 29.09 | 0.00 | 01-JAN-00:10 | 18026.68 | 30-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 10.82 | 0.00 | 01-JAN-00:10 | 8506.73 | 29-JUN-16:20 |
General:Cooling:EnergyTransfer | 29.09 | 0.00 | 01-JAN-00:10 | 18026.68 | 30-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 10.82 | 0.00 | 01-JAN-00:10 | 8506.73 | 29-JUN-16:20 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 165.53 | 0.00 | 01-JAN-00:40 | 42241.63 | 05-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 147.26 | 0.00 | 01-JAN-00:40 | 42241.63 | 05-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 147.26 | 0.00 | 01-JAN-00:40 | 42241.63 | 05-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 18.27 | 0.00 | 01-JAN-00:10 | 10967.94 | 30-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 18.27 | 0.00 | 01-JAN-00:10 | 10967.94 | 30-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 676.69 | 0.00 | 17-JAN-13:10 | 134244.56 | 12-FEB-22:30 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 676.69 | 0.00 | 17-JAN-13:10 | 134244.56 | 12-FEB-22:30 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 676.69 | 0.00 | 17-JAN-13:10 | 134244.56 | 12-FEB-22:30 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 952.13 | 0.00 | 19-MAR-13:50 | 206050.44 | 04-JAN-18:00 |
HeatingCoils:EnergyTransfer | 934.39 | 0.00 | 19-MAR-13:50 | 206050.44 | 04-JAN-18:00 |
CoolingCoils:EnergyTransfer | 17.73 | 0.00 | 01-JAN-00:10 | 35839.20 | 30-JUN-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 56.560 | -10.820 | 0.000 | 0.000 | 10.229 | 10.604 | 29.165 | 10.718 | 0.000 | 0.311 | 0.000 | 0.000 | -9.625 | 0.000 | -34.383 | -62.759 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 147.263 | -18.268 | 0.000 | 0.000 | 27.368 | 58.344 | 0.000 | 0.000 | 0.000 | 0.252 | 0.001 | 0.000 | 0.000 | 0.000 | -48.343 | -166.616 |
ZONE3 BULK STORAGE | 676.693 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 70.551 | 59.443 | 107.344 | 123.563 | 0.000 | 12.799 | 0.000 | 0.000 | -82.625 | 0.000 | -631.601 | -336.166 |
Total Facility | 676.693 | 0.000 | 203.823 | -29.088 | 0.000 | 0.000 | 108.148 | 128.391 | 136.508 | 134.281 | 0.000 | 13.362 | 0.001 | 0.000 | -92.250 | 0.000 | -714.327 | -565.540 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 08-JUL-07:02 | 0.00 | 0.00 | 0.00 | -18718.31 | 0.00 | 0.00 | 801.53 | 748.92 | 1835.05 | 0.00 | 0.00 | 0.00 | 15700.94 | 0.00 | -132.68 | 0.00 | -235.46 | 0.00 |
ZONE2 FINE STORAGE | 29-JUL-17:17 | 0.00 | 0.00 | 0.00 | -23614.53 | 0.00 | 0.00 | 0.00 | 512.27 | 0.00 | 0.00 | 0.00 | 170.41 | 22931.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-JUL-07:02 | 0.00 | 0.00 | 0.00 | -23668.38 | 0.00 | 0.00 | 7851.82 | 8566.70 | 10035.17 | 0.00 | 0.00 | 0.00 | 18773.39 | 0.00 | -1712.13 | 0.00 | -19846.57 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-DEC-06:32 | 0.00 | 0.00 | 27626.95 | 0.00 | 0.00 | 0.00 | 150.64 | 241.53 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1065.12 | 0.00 | -3417.13 | -24087.38 |
ZONE2 FINE STORAGE | 04-JAN-06:01 | 0.00 | 0.00 | 67602.25 | 0.00 | 0.00 | 0.00 | 379.26 | 512.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -9283.65 | -59210.14 |
ZONE3 BULK STORAGE | 12-FEB-22:30 | 134233.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.50 | 0.00 | 0.00 | 0.00 | 0.00 | 10372.19 | 0.00 | -4340.22 | 0.00 | -140829.24 | 0.00 |
Total Facility | 04-JAN-06:01 | 133975.61 | 0.00 | 94210.28 | 0.00 | 0.00 | 0.00 | 1462.58 | 1317.30 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11375.00 | 0.00 | -136905.40 | -85285.93 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9085 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9085 | 0.1126 | 1.0000 | Not calculated | 0.1023 | 0.1126 | ||
PSZ-FINE STORAGE | 1.4566 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.4566 | 0.2916 | 1.0000 | Not calculated | 0.4247 | 0.2916 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9085 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9085 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1126 | ||
PSZ-FINE STORAGE | 1.4566 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.4566 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2916 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.002360 | 12.7487 | 0.000305 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.002360 | 12.75 | 0.000305 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9085 | 0.9085 | 0.9085 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4566 | 1.4566 | 1.4566 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9085 | 0.9085 | 0.9085 | 0.9085 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.4566 | 1.4566 | 1.4566 | 1.4566 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9085 | 0.9085 | 0.9085 | No | 0.1023 | 0.2820 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4566 | 1.4566 | 1.4566 | No | 0.4247 | 0.4706 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9085 | 0.9085 | 0.9085 | 0.9085 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.4566 | 1.4566 | 1.4566 | 1.4566 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 76.83 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 76.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1202.31 | 259009.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3.51 | 7739.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 128.39 | 9876.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.95 | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 28.18 | 2656.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 27.33 | 3095.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 385.87 |
Natural Gas | 0.00 | 1202.31 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 1588.18 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 26.55 |
Space Heating | 0.00 |
Space Cooling | 0.73 |
Fans (All) | 5.83 |
Service Water Heating | 5.65 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 79.81 |
Subtotal | 79.81 |
Natural Gas [MJ/m2] | |
Space Heating | 248.66 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 248.66 |
Subtotal | 248.66 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.08 |
Space Heating | 75.70 |
Space Cooling | 0.22 |
Fans (All) | 1.77 |
Service Water Heating | 1.72 |
Receptacle Equipment | 8.60 |
Miscellaneous | 3.90 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2499. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8539.17 | 220.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8395.50 | 364.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8573.17 | 186.83 | 0.00 | 0.00 | 0.00 |
Min | 8395.50 | 186.83 | 0.00 | 0.00 | 0.00 |
Max | 8573.17 | 364.50 | 0.00 | 0.00 | 0.00 |
Average | 8502.61 | 257.39 | 0.00 | 0.00 | 0.00 |
Sum | 25507.83 | 772.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33025.67 | 1.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 75924.50 | 6794.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 184136.83 | 7056.17 | 0.00 | 0.00 | 0.00 |
Min | 33025.67 | 1.33 | 0.00 | 0.00 | 0.00 |
Max | 184136.83 | 7056.17 | 0.00 | 0.00 | 0.00 |
Average | 97695.67 | 4617.33 | 0.00 | 0.00 | 0.00 |
Sum | 293087.00 | 13852.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7973.17 | 786.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7693.33 | 1066.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7947.83 | 812.17 | 0.00 | 0.00 | 0.00 |
Min | 7693.33 | 786.83 | 0.00 | 0.00 | 0.00 |
Max | 7973.17 | 1066.67 | 0.00 | 0.00 | 0.00 |
Average | 7871.44 | 888.56 | 0.00 | 0.00 | 0.00 |
Sum | 23614.33 | 2665.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31789.83 | 1237.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 69418.50 | 13300.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 169694.17 | 21498.83 | 0.00 | 0.00 | 0.00 |
Min | 31789.83 | 1237.17 | 0.00 | 0.00 | 0.00 |
Max | 169694.17 | 21498.83 | 0.00 | 0.00 | 0.00 |
Average | 90300.83 | 12012.17 | 0.00 | 0.00 | 0.00 |
Sum | 270902.50 | 36036.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2539184.26 | 2649.26 | 21-JAN-08:05 | -22.1 | -22.3 | 0.490676E+09 | 603.25 | 19-JAN-08:20 | -22.1 | -22.3 |
February | 3995043.70 | 2744.38 | 11-FEB-08:05 | -15.5 | -15.9 | 0.452470E+09 | 603.25 | 09-FEB-08:20 | -15.5 | -15.9 |
March | 6590786.54 | 2782.10 | 18-MAR-07:05 | -20.6 | -20.8 | 0.531391E+09 | 603.26 | 25-MAR-07:19 | -3.1 | -3.6 |
April | 7085204.68 | 1991.50 | 07-APR-07:05 | -3.4 | -5.4 | 0.495122E+09 | 701.20 | 13-APR-15:00 | 20.00 | 8.11 |
May | 0.586446E+09 | 12054.02 | 27-MAY-07:03 | 17.20 | 13.08 | 0.586515E+09 | 836.62 | 27-MAY-07:10 | 17.20 | 13.08 |
June | 0.197840E+10 | 12955.24 | 24-JUN-07:03 | 17.30 | 16.96 | 0.650626E+09 | 879.39 | 30-JUN-07:10 | 26.02 | 21.73 |
July | 0.386248E+10 | 18719.95 | 08-JUL-07:02 | 13.40 | 11.20 | 0.639051E+09 | 879.39 | 29-JUL-07:10 | 22.48 | 20.28 |
August | 0.325960E+10 | 17521.82 | 05-AUG-07:02 | 15.78 | 12.69 | 0.686717E+09 | 879.39 | 12-AUG-07:10 | 17.30 | 16.55 |
September | 0.106538E+10 | 18269.74 | 02-SEP-07:02 | 13.17 | 11.14 | 0.587484E+09 | 879.39 | 02-SEP-07:10 | 13.17 | 11.14 |
October | 35655332.07 | 2157.30 | 25-OCT-07:05 | -3.2 | -3.4 | 0.499801E+09 | 768.92 | 21-OCT-15:00 | -3.2 | -3.4 |
November | 7240619.91 | 2239.48 | 04-NOV-07:05 | -4.3 | -5.3 | 0.472689E+09 | 631.86 | 01-NOV-15:00 | -4.3 | -5.3 |
December | 5114346.96 | 2594.51 | 09-DEC-08:05 | -13.5 | -13.8 | 0.491769E+09 | 603.26 | 30-DEC-08:20 | -4.5 | -5.2 |
Annual Sum or Average | 0.108205E+11 | 0.658431E+10 | ||||||||
Minimum of Months | 2539184.26 | 1991.50 | -22.1 | -22.3 | 0.452470E+09 | 603.25 | -22.1 | -22.3 | ||
Maximum of Months | 0.386248E+10 | 18719.95 | 17.30 | 16.96 | 0.686717E+09 | 879.39 | 26.02 | 21.73 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -21.9 | -22.1 | 0.649208E+09 | 787.42 | 31-JAN-10:30 | -15.6 | -16.0 |
February | 0.251199E+09 | 10015.54 | 23-FEB-11:03 | -6.6 | -7.9 | 0.597345E+09 | 787.44 | 23-FEB-11:20 | -6.5 | -7.8 |
March | 0.759544E+09 | 6783.94 | 31-MAR-08:55 | 0.00 | -1.8 | 0.702690E+09 | 892.28 | 31-MAR-15:09 | 8.40 | 2.82 |
April | 0.162616E+10 | 5434.36 | 19-APR-10:20 | 3.33 | -2.1 | 0.712882E+09 | 1234.38 | 13-APR-15:00 | 3.33 | -2.1 |
May | 0.169759E+10 | 6050.44 | 20-MAY-07:15 | 6.30 | 3.49 | 0.115488E+10 | 2172.63 | 25-MAY-15:00 | 29.10 | 19.63 |
June | 0.185378E+10 | 19622.24 | 30-JUN-17:12 | 30.73 | 21.04 | 0.154787E+10 | 2246.90 | 30-JUN-14:39 | 30.73 | 21.04 |
July | 0.340331E+10 | 23618.97 | 29-JUL-17:17 | 29.43 | 21.23 | 0.178341E+10 | 2246.89 | 22-JUL-14:50 | 29.43 | 21.23 |
August | 0.260328E+10 | 6425.30 | 09-AUG-14:40 | 27.60 | 21.71 | 0.180352E+10 | 2246.83 | 04-AUG-15:09 | 27.60 | 21.71 |
September | 0.279326E+10 | 8305.41 | 06-SEP-07:03 | 4.05 | 3.63 | 0.122733E+10 | 2246.80 | 01-SEP-12:39 | 4.05 | 3.63 |
October | 0.245216E+10 | 7105.49 | 04-OCT-07:03 | 0.37 | 0.10 | 0.736416E+09 | 1325.70 | 21-OCT-15:09 | 20.00 | 11.21 |
November | 0.826690E+09 | 7569.09 | 22-NOV-10:35 | -1.7 | -4.8 | 0.632966E+09 | 1047.29 | 01-NOV-15:09 | -1.7 | -4.8 |
December | 791910.81 | 191.12 | 28-DEC-14:30 | -1.7 | -3.6 | 0.649284E+09 | 787.42 | 19-DEC-11:39 | -1.7 | -3.6 |
Annual Sum or Average | 0.182678E+11 | 0.121978E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -21.9 | -22.1 | 0.597345E+09 | 787.42 | -15.6 | -16.0 | ||
Maximum of Months | 0.340331E+10 | 23618.97 | 30.73 | 21.71 | 0.180352E+10 | 2246.90 | 30.73 | 21.71 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -21.9 | -22.1 | 0.634917E+09 | 818.70 | 27-JAN-14:50 | -14.4 | -15.6 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -23.1 | -23.5 | 0.594778E+09 | 874.49 | 11-FEB-15:09 | -6.1 | -8.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 | -3.3 | 0.710232E+09 | 1022.94 | 23-MAR-14:20 | 0.20 | -4.3 |
April | 0.00 | 0.00 | 01-APR-00:05 | 3.52 | 0.38 | 0.824231E+09 | 1691.90 | 18-APR-14:09 | 17.33 | 10.22 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.4 | 0.182135E+10 | 3606.50 | 25-MAY-15:30 | 29.00 | 19.65 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.306676E+10 | 5866.98 | 30-JUN-15:30 | 31.95 | 24.59 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.57 | 0.408729E+10 | 5972.21 | 24-JUL-15:30 | 29.15 | 18.97 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.389410E+10 | 5410.36 | 08-AUG-15:00 | 30.60 | 22.99 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.247276E+10 | 5055.82 | 01-SEP-15:00 | 26.10 | 17.64 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.104549E+10 | 2192.55 | 02-OCT-13:39 | 10.37 | 9.55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 | 0.656830E+09 | 1359.24 | 01-NOV-14:30 | 18.05 | 13.35 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.640449E+09 | 781.80 | 02-DEC-15:20 | -17.6 | -18.4 |
Annual Sum or Average | 0.00 | 0.204492E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.594778E+09 | 781.80 | -17.6 | -18.4 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.408729E+10 | 5972.21 | 31.95 | 24.59 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125923E+11 | 27607.20 | 25-JAN-06:32 | -25.2 |
February | 0.950246E+10 | 27571.24 | 01-FEB-06:32 | -22.8 |
March | 0.879374E+10 | 27265.58 | 07-MAR-06:42 | -21.3 |
April | 0.441450E+10 | 26886.00 | 05-APR-06:01 | -13.5 |
May | 0.101743E+10 | 26685.63 | 01-MAY-06:01 | -3.5 |
June | 0.142204E+09 | 9131.92 | 02-JUN-07:03 | 10.18 |
July | 80456640.28 | 1458.53 | 18-JUL-06:15 | 11.87 |
August | 0.111839E+09 | 1572.53 | 25-AUG-06:15 | 9.80 |
September | 0.372839E+09 | 26085.56 | 28-SEP-06:02 | 6.70 |
October | 0.281816E+10 | 26809.94 | 30-OCT-06:01 | -9.4 |
November | 0.572879E+10 | 27063.10 | 29-NOV-07:13 | -18.0 |
December | 0.109858E+11 | 27626.90 | 19-DEC-06:32 | -25.7 |
Annual Sum or Average | 0.565605E+11 | |||
Minimum of Months | 80456640.28 | 1458.53 | -25.7 | |
Maximum of Months | 0.125923E+11 | 27626.90 | 11.87 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375178E+11 | 67602.30 | 04-JAN-06:01 | -29.0 |
February | 0.269374E+11 | 67188.12 | 13-FEB-04:02 | -22.9 |
March | 0.205962E+11 | 66683.58 | 15-MAR-04:22 | -21.9 |
April | 0.802196E+10 | 65704.72 | 05-APR-03:42 | -12.2 |
May | 0.763165E+09 | 30640.28 | 01-MAY-03:15 | -2.3 |
June | 85663821.62 | 1723.14 | 24-JUN-16:03 | 28.98 |
July | 45066951.72 | 586.95 | 08-JUL-07:00 | 13.30 |
August | 53669946.02 | 635.46 | 31-AUG-07:00 | 17.20 |
September | 53809296.37 | 623.41 | 27-SEP-07:00 | 6.70 |
October | 0.348594E+10 | 62583.63 | 30-OCT-06:01 | -9.4 |
November | 0.153106E+11 | 65993.37 | 25-NOV-04:03 | -18.0 |
December | 0.343921E+11 | 67314.26 | 24-DEC-08:62 | -31.1 |
Annual Sum or Average | 0.147263E+12 | |||
Minimum of Months | 45066951.72 | 586.95 | -31.1 | |
Maximum of Months | 0.375178E+11 | 67602.30 | 28.98 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183148E+12 | 134128.18 | 04-JAN-12:00 | -28.3 |
February | 0.136015E+12 | 134244.56 | 12-FEB-22:30 | -16.1 |
March | 0.889338E+11 | 112054.46 | 15-MAR-04:54 | -22.2 |
April | 0.257617E+11 | 70213.39 | 04-APR-18:57 | -7.2 |
May | 0.216226E+09 | 13689.10 | 01-MAY-04:00 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.209491E+10 | 32447.22 | 31-OCT-21:00 | -2.2 |
November | 0.680516E+11 | 93128.43 | 25-NOV-02:00 | -15.6 |
December | 0.172472E+12 | 134185.34 | 18-DEC-13:20 | -22.8 |
Annual Sum or Average | 0.676694E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.3 | |
Maximum of Months | 0.183148E+12 | 134244.56 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.960484E+09 | 808.57 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.824187E+09 | 787.64 | 02-FEB-16:00 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.928270E+09 | 784.07 | 13-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.854626E+09 | 775.30 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.831448E+09 | 707.30 | 19-MAY-08:30 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.820856E+09 | 751.86 | 30-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.816548E+09 | 748.92 | 08-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.876996E+09 | 774.74 | 31-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.856044E+09 | 776.88 | 19-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.917199E+09 | 807.09 | 31-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.931487E+09 | 808.57 | 06-NOV-16:49 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.985502E+09 | 808.57 | 01-DEC-16:19 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.106036E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.816548E+09 | 707.30 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.985502E+09 | 808.57 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.485298E+10 | 4354.33 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.444173E+10 | 4354.33 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.513145E+10 | 4354.33 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.480872E+10 | 4354.33 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.499222E+10 | 4354.33 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.494796E+10 | 4354.33 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.485298E+10 | 4354.33 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.513145E+10 | 4354.33 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.480872E+10 | 4354.33 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.485298E+10 | 4354.33 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.466948E+10 | 4354.33 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.485298E+10 | 4354.33 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.583437E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.444173E+10 | 4354.33 | 0.00 | 0.00 | |
Maximum of Months | 0.513145E+10 | 4354.33 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.511038E+10 | 4735.46 | 05-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.460487E+10 | 4668.97 | 08-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.523131E+10 | 4626.70 | 17-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.484965E+10 | 4542.99 | 06-APR-08:30 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.496051E+10 | 4446.10 | 06-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.490540E+10 | 4375.02 | 10-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.481641E+10 | 4337.06 | 31-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.511589E+10 | 4515.70 | 31-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.486121E+10 | 4601.61 | 13-SEP-08:30 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.498936E+10 | 4672.30 | 19-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.488431E+10 | 4737.73 | 29-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.511402E+10 | 4749.89 | 20-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.594433E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.460487E+10 | 4337.06 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.523131E+10 | 4749.89 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.960484E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646799E+10 |
February | 0.127628E+10 | 0.824187E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496053E+10 |
March | 0.149825E+10 | 0.928270E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439913E+10 |
April | 0.138726E+10 | 0.854626E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6125716.30 | 0.248298E+10 |
May | 0.144276E+10 | 0.831448E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46587421.88 | 0.113780E+10 |
June | 0.144276E+10 | 0.820856E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109005E+09 | 0.666512E+09 |
July | 0.138726E+10 | 0.816548E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98691967.90 | 0.558565E+09 |
August | 0.149825E+10 | 0.876996E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49060806.75 | 0.878788E+09 |
September | 0.138726E+10 | 0.856044E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1591664.62 | 0.141003E+10 |
October | 0.138726E+10 | 0.917199E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222789E+10 |
November | 0.133177E+10 | 0.931487E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340465E+10 |
December | 0.138726E+10 | 0.985502E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578790E+10 |
Annual Sum or Average | 0.168137E+11 | 0.106036E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311063E+09 | 0.343828E+11 |
Minimum of Months | 0.127628E+10 | 0.816548E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558565E+09 |
Maximum of Months | 0.149825E+10 | 0.985502E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109005E+09 | 0.646799E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.485298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871860E+10 |
February | 0.300332E+10 | 0.444173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726499E+10 |
March | 0.352563E+10 | 0.513145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512676E+10 |
April | 0.326447E+10 | 0.480872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47573009.22 | 0.359408E+10 |
May | 0.339505E+10 | 0.499222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68306414.79 | 0.150836E+10 |
June | 0.339505E+10 | 0.494796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71036974.39 | 0.102696E+10 |
July | 0.326447E+10 | 0.485298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47188709.99 | 0.109128E+10 |
August | 0.352563E+10 | 0.513145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13372710.32 | 0.145744E+10 |
September | 0.326447E+10 | 0.480872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1222228.80 | 0.201795E+10 |
October | 0.326447E+10 | 0.485298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3175446.67 | 0.247233E+10 |
November | 0.313390E+10 | 0.466948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34493.41 | 0.521813E+10 |
December | 0.326447E+10 | 0.485298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.884613E+10 |
Annual Sum or Average | 0.395654E+11 | 0.583437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251910E+09 | 0.483430E+11 |
Minimum of Months | 0.300332E+10 | 0.444173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102696E+10 |
Maximum of Months | 0.352563E+10 | 0.513145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71036974.39 | 0.884613E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.511038E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815702E+11 |
February | 0.690763E+10 | 0.460487E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659355E+11 |
March | 0.810895E+10 | 0.523131E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2198911.18 | 0.440428E+11 |
April | 0.750829E+10 | 0.484965E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180991E+10 | 0.240978E+11 |
May | 0.780862E+10 | 0.496051E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335714E+10 | 0.941869E+10 |
June | 0.780862E+10 | 0.490540E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164312E+10 | 0.733817E+10 |
July | 0.750829E+10 | 0.481641E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339203E+09 | 0.111888E+11 |
August | 0.810895E+10 | 0.511589E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286718E+09 | 0.143980E+11 |
September | 0.750829E+10 | 0.486121E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111756E+09 | 0.188636E+11 |
October | 0.750829E+10 | 0.498936E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726597E+09 | 0.177587E+11 |
November | 0.720796E+10 | 0.488431E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254254E+09 | 0.400348E+11 |
December | 0.750829E+10 | 0.511402E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.797566E+11 |
Annual Sum or Average | 0.910005E+11 | 0.594433E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853089E+10 | 0.414404E+12 |
Minimum of Months | 0.690763E+10 | 0.460487E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733817E+10 |
Maximum of Months | 0.810895E+10 | 0.523131E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335714E+10 | 0.815702E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 808.57 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 22183.31 | 06-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 787.64 | 02-FEB-16:00 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 21677.67 | 14-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 784.07 | 13-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 18370.36 | 15-MAR-07:00 |
April | 1680.92 | 01-APR-07:10 | 775.30 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.28 | 23-APR-16:00 | 12766.17 | 05-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 707.30 | 19-MAY-08:30 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.77 | 25-MAY-16:03 | 8671.70 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 751.86 | 30-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3647.61 | 29-JUN-16:03 | 4096.05 | 09-JUN-11:05 |
July | 1680.92 | 01-JUL-07:10 | 748.92 | 08-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1740.91 | 28-JUL-16:03 | 4465.36 | 18-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 774.74 | 31-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2194.07 | 08-AUG-16:03 | 5119.07 | 25-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 776.88 | 19-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 531.36 | 01-SEP-16:03 | 7212.18 | 06-SEP-06:03 |
October | 1680.92 | 02-OCT-07:10 | 807.09 | 31-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 11677.67 | 30-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 808.57 | 06-NOV-16:49 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 15515.20 | 29-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 808.57 | 01-DEC-16:19 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 21303.15 | 20-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 707.30 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4096.05 | |||||
Maximum of Months | 1680.92 | 808.57 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 3647.61 | 22183.31 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 4354.33 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 10703.95 | 04-JAN-16:10 |
February | 3955.50 | 01-FEB-08:09 | 4354.33 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 13057.03 | 12-FEB-23:00 |
March | 3955.50 | 01-MAR-08:09 | 4354.33 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 7972.61 | 14-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 4354.33 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2202.19 | 23-APR-16:00 | 6514.94 | 26-APR-15:10 |
May | 3955.50 | 01-MAY-07:10 | 4354.33 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1086.98 | 10-MAY-15:10 | 3127.20 | 20-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 4354.33 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1787.06 | 29-JUN-16:00 | 2848.91 | 09-JUN-08:00 |
July | 3955.50 | 01-JUL-07:10 | 4354.33 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1221.88 | 15-JUL-15:10 | 2043.46 | 06-JUL-22:00 |
August | 3955.50 | 01-AUG-07:10 | 4354.33 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922.20 | 08-AUG-16:00 | 3847.26 | 17-AUG-15:10 |
September | 3955.50 | 01-SEP-07:10 | 4354.33 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.44 | 24-SEP-15:00 | 3428.13 | 20-SEP-06:10 |
October | 3955.50 | 02-OCT-07:10 | 4354.33 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.81 | 19-OCT-15:10 | 4285.46 | 31-OCT-17:00 |
November | 3955.50 | 01-NOV-07:10 | 4354.33 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.09 | 01-NOV-15:10 | 6430.99 | 22-NOV-01:37 |
December | 3955.50 | 01-DEC-08:09 | 4354.33 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13144.71 | 18-DEC-16:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2043.46 | ||||
Maximum of Months | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2202.19 | 13144.71 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4735.46 | 05-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 125242.07 | 04-JAN-12:00 |
February | 9097.65 | 01-FEB-08:09 | 4668.97 | 08-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 96541.07 | 12-FEB-23:00 |
March | 9097.65 | 01-MAR-08:09 | 4626.70 | 17-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 723.67 | 26-MAR-16:00 | 61648.68 | 14-MAR-15:50 |
April | 9097.65 | 01-APR-07:10 | 4542.99 | 06-APR-08:30 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29399.24 | 23-APR-16:00 | 42869.75 | 26-APR-15:00 |
May | 9097.65 | 01-MAY-07:10 | 4446.10 | 06-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19623.04 | 10-MAY-15:00 | 19762.01 | 20-MAY-07:10 |
June | 9097.65 | 01-JUN-07:10 | 4375.02 | 10-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14824.46 | 29-JUN-16:00 | 26768.29 | 09-JUN-09:00 |
July | 9097.65 | 01-JUL-07:10 | 4337.06 | 31-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9053.75 | 15-JUL-15:00 | 29983.70 | 03-JUL-10:55 |
August | 9097.65 | 01-AUG-07:10 | 4515.70 | 31-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7607.73 | 08-AUG-16:00 | 42637.41 | 17-AUG-14:00 |
September | 9097.65 | 01-SEP-07:10 | 4601.61 | 13-SEP-08:30 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4810.17 | 24-SEP-15:00 | 24839.61 | 20-SEP-07:10 |
October | 9097.65 | 02-OCT-07:10 | 4672.30 | 19-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16407.73 | 19-OCT-15:00 | 30103.77 | 05-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 4737.73 | 29-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8375.58 | 01-NOV-14:00 | 51897.15 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 4749.89 | 20-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 112779.79 | 18-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 4337.06 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19762.01 | |||||
Maximum of Months | 9097.65 | 4749.89 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 29399.24 | 125242.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2649.26 | 21-JAN-08:05 | 6723.69 | 3125.43 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.46 |
February | 2744.38 | 11-FEB-08:05 | 6723.69 | 3061.11 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.05 |
March | 2782.10 | 18-MAR-07:05 | 6723.69 | 2970.41 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1991.50 | 07-APR-07:05 | 6723.69 | 2811.19 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1709.44 |
May | 12054.02 | 27-MAY-07:03 | 5042.77 | 1756.32 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.08 |
June | 12955.24 | 24-JUN-07:03 | 6723.69 | 2927.22 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.71 |
July | 18719.95 | 08-JUL-07:02 | 8404.61 | 3744.60 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.46 |
August | 17521.82 | 05-AUG-07:02 | 8404.61 | 3234.43 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.46 |
September | 18269.74 | 02-SEP-07:02 | 8404.61 | 3550.05 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.10 |
October | 2157.30 | 25-OCT-07:05 | 6723.69 | 3106.17 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1297.93 |
November | 2239.48 | 04-NOV-07:05 | 6723.69 | 3225.07 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.68 |
December | 2594.51 | 09-DEC-08:05 | 6723.69 | 3221.57 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 777.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1991.50 | 5042.77 | 1756.32 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18719.95 | 8404.61 | 3744.60 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1709.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 2561.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3743.16 |
February | 10015.54 | 23-FEB-11:03 | 11866.50 | 13063.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1391.18 |
March | 6783.94 | 31-MAR-08:55 | 7911.00 | 8708.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.69 |
April | 5434.36 | 19-APR-10:20 | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2245.61 |
May | 6050.44 | 20-MAY-07:15 | 7911.00 | 7684.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2795.12 |
June | 19622.24 | 30-JUN-17:12 | 0.00 | 2049.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.25 | 0.00 |
July | 23618.97 | 29-JUL-17:17 | 0.00 | 1536.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.41 | 0.00 |
August | 6425.30 | 09-AUG-14:40 | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 0.00 |
September | 8305.41 | 06-SEP-07:03 | 15822.00 | 15368.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.20 |
October | 7105.49 | 04-OCT-07:03 | 15822.00 | 15368.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1296.60 |
November | 7569.09 | 22-NOV-10:35 | 7911.00 | 8708.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.24 |
December | 191.12 | 28-DEC-14:30 | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 1536.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23618.97 | 15822.00 | 15368.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.25 | 3743.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 2817.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30461.36 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2817.51 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48545.69 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 1690.51 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12866.10 |
April | 0.00 | 01-APR-00:05 | 0.00 | 1127.00 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8998.78 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2085.06 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5956.05 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3715.60 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6631.94 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3485.92 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 563.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4951.78 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8992.05 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1690.51 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25163.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 563.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2085.06 | |
Maximum of Months | 0.00 | 0.00 | 2817.51 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48545.69 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.354959E+11 | 28734.41 | 05-JAN-08:09 | 0.316912E+12 | 259009.08 | 04-JAN-17:00 |
February | 0.313014E+11 | 24472.87 | 01-FEB-13:20 | 0.233982E+12 | 237062.05 | 13-FEB-07:10 |
March | 0.344241E+11 | 24433.57 | 03-MAR-15:50 | 0.164280E+12 | 189588.48 | 15-MAR-05:10 |
April | 0.304963E+11 | 23850.16 | 03-APR-12:39 | 0.531702E+11 | 112213.15 | 04-APR-06:10 |
May | 0.302200E+11 | 24037.84 | 26-MAY-12:30 | 0.210907E+10 | 35666.65 | 01-MAY-03:20 |
June | 0.301784E+11 | 30028.30 | 30-JUN-14:00 | 16956502.50 | 4917.54 | 02-JUN-07:10 |
July | 0.305813E+11 | 28490.03 | 15-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.319521E+11 | 27679.37 | 08-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.304112E+11 | 25654.21 | 01-SEP-14:00 | 0.387992E+09 | 10290.88 | 28-SEP-06:10 |
October | 0.321478E+11 | 23599.30 | 30-OCT-08:09 | 0.138384E+11 | 64823.42 | 30-OCT-06:10 |
November | 0.330242E+11 | 28317.44 | 25-NOV-16:00 | 0.122085E+12 | 149782.60 | 25-NOV-08:00 |
December | 0.356352E+11 | 28605.79 | 26-DEC-08:09 | 0.295525E+12 | 255322.25 | 18-DEC-17:40 |
Annual Sum or Average | 0.385868E+12 | 0.120231E+13 | ||||
Minimum of Months | 0.301784E+11 | 23599.30 | 0.00 | 0.00 | ||
Maximum of Months | 0.356352E+11 | 30028.30 | 0.316912E+12 | 259009.08 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.109238E+11 | 0.733455E+10 | 0.112984E+11 | 0.00 | 0.355416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238496E+10 | 0.00 |
February | 0.987079E+10 | 0.585179E+10 | 0.103734E+11 | 0.00 | 0.301449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219098E+10 | 0.00 |
March | 0.112910E+11 | 0.542972E+10 | 0.121089E+11 | 0.00 | 0.311358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248082E+10 | 0.00 |
April | 0.105130E+11 | 0.420175E+10 | 0.112578E+11 | 0.00 | 0.219853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232524E+10 | 0.00 |
May | 0.107842E+11 | 0.355851E+10 | 0.117000E+11 | 0.00 | 0.169899E+10 | 0.00 | 0.00 | 0.126260E+09 | 0.00 | 0.00 | 0.00 | 0.235206E+10 | 0.00 |
June | 0.106742E+11 | 0.307274E+10 | 0.116594E+11 | 0.00 | 0.168212E+10 | 0.00 | 0.00 | 0.848118E+09 | 0.00 | 0.00 | 0.00 | 0.224180E+10 | 0.00 |
July | 0.104859E+11 | 0.331755E+10 | 0.112984E+11 | 0.00 | 0.162325E+10 | 0.00 | 0.00 | 0.165296E+10 | 0.00 | 0.00 | 0.00 | 0.220321E+10 | 0.00 |
August | 0.111243E+11 | 0.394282E+10 | 0.121016E+11 | 0.00 | 0.174201E+10 | 0.00 | 0.00 | 0.799454E+09 | 0.00 | 0.00 | 0.00 | 0.224189E+10 | 0.00 |
September | 0.105260E+11 | 0.479266E+10 | 0.112504E+11 | 0.00 | 0.161297E+10 | 0.00 | 0.00 | 86186146.51 | 0.00 | 0.00 | 0.00 | 0.214299E+10 | 0.00 |
October | 0.107595E+11 | 0.604599E+10 | 0.113057E+11 | 0.00 | 0.180894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222763E+10 | 0.00 |
November | 0.104853E+11 | 0.680954E+10 | 0.108562E+11 | 0.00 | 0.267277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220044E+10 | 0.00 |
December | 0.109525E+11 | 0.758831E+10 | 0.112984E+11 | 0.00 | 0.345950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233656E+10 | 0.00 |
Annual Sum or Average | 0.128391E+12 | 0.619459E+11 | 0.136508E+12 | 0.00 | 0.281813E+11 | 0.00 | 0.00 | 0.351298E+10 | 0.00 | 0.00 | 0.00 | 0.273286E+11 | 0.00 |
Minimum of Months | 0.987079E+10 | 0.307274E+10 | 0.103734E+11 | 0.00 | 0.161297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214299E+10 | 0.00 |
Maximum of Months | 0.112910E+11 | 0.758831E+10 | 0.121089E+11 | 0.00 | 0.355416E+10 | 0.00 | 0.00 | 0.165296E+10 | 0.00 | 0.00 | 0.00 | 0.248082E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.316912E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.233982E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.164280E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.531702E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.210907E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 16956502.50 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.387992E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.138384E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.122085E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.295525E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.120231E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.316912E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 9830.28 | 09-JAN-09:09 | 5492.60 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2656.93 | 09-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 9694.01 | 27-FEB-09:09 | 5492.60 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2579.60 | 14-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9700.78 | 17-MAR-08:09 | 5492.60 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2482.69 | 15-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 9598.48 | 06-APR-08:30 | 5492.60 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2256.11 | 04-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 9484.55 | 06-MAY-08:09 | 4946.68 | 01-MAY-19:30 | 10035.17 | 01-MAY-07:10 | 0.00 | 2000.70 | 02-MAY-06:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 9455.16 | 10-JUN-08:09 | 4946.68 | 01-JUN-19:00 | 10035.17 | 01-JUN-07:10 | 0.00 | 1778.29 | 30-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 9343.14 | 31-JUL-08:09 | 4946.68 | 01-JUL-20:19 | 10035.17 | 01-JUL-07:10 | 0.00 | 1629.26 | 10-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 9623.39 | 31-AUG-08:09 | 5492.60 | 15-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 1629.26 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 9688.09 | 13-SEP-08:30 | 5492.60 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1629.26 | 01-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 9769.37 | 19-OCT-08:09 | 5492.60 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2230.72 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9876.22 | 15-NOV-15:00 | 5492.60 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2385.26 | 25-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 9869.19 | 13-DEC-15:00 | 5492.60 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2602.42 | 20-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9343.14 | 4946.68 | 10035.17 | 0.00 | 1629.26 | 0.00 | 0.00 | |||||
Maximum of Months | 9876.22 | 5492.60 | 10035.17 | 0.00 | 2656.93 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3060.95 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3095.64 | 25-FEB-12:09 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3094.79 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 3029.34 | 01-APR-11:09 | 0.00 |
May | 1332.91 | 25-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2873.91 | 01-MAY-11:39 | 0.00 |
June | 7739.62 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2640.40 | 01-JUN-11:09 | 0.00 |
July | 5940.68 | 15-JUL-14:30 | 0.00 | 0.00 | 0.00 | 2400.42 | 01-JUL-11:30 | 0.00 |
August | 5300.95 | 08-AUG-15:30 | 0.00 | 0.00 | 0.00 | 2211.54 | 01-AUG-11:20 | 0.00 |
September | 3119.58 | 01-SEP-15:30 | 0.00 | 0.00 | 0.00 | 2256.34 | 30-SEP-11:50 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2472.90 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2714.42 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2910.74 | 28-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2211.54 | 0.00 | ||
Maximum of Months | 7739.62 | 0.00 | 0.00 | 0.00 | 3095.64 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 28734.41 | 05-JAN-08:09 | 8876.89 | 10035.17 | 5492.60 | 0.00 | 2656.05 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24472.87 | 01-FEB-13:20 | 9562.56 | 10035.17 | 0.00 | 0.00 | 2261.38 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24433.57 | 03-MAR-15:50 | 9626.14 | 10035.17 | 0.00 | 0.00 | 2124.38 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23850.16 | 03-APR-12:39 | 9204.06 | 10035.17 | 0.00 | 0.00 | 2043.06 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24037.84 | 26-MAY-12:30 | 9126.32 | 10035.17 | 0.00 | 0.00 | 1629.26 | 0.00 | 0.00 | 1055.64 | 0.00 |
June | 30028.30 | 30-JUN-14:00 | 9081.72 | 10035.17 | 0.00 | 0.00 | 1739.82 | 0.00 | 0.00 | 7297.10 | 0.00 |
July | 28490.03 | 15-JUL-14:30 | 9081.72 | 10035.17 | 0.00 | 0.00 | 1629.26 | 0.00 | 0.00 | 5940.68 | 0.00 |
August | 27679.37 | 08-AUG-14:00 | 9081.72 | 10035.17 | 0.00 | 0.00 | 1629.26 | 0.00 | 0.00 | 5140.16 | 0.00 |
September | 25654.21 | 01-SEP-14:00 | 9081.72 | 10035.17 | 0.00 | 0.00 | 1629.26 | 0.00 | 0.00 | 3116.84 | 0.00 |
October | 23599.30 | 30-OCT-08:09 | 9729.34 | 10035.17 | 0.00 | 0.00 | 2143.03 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28317.44 | 25-NOV-16:00 | 8876.89 | 10035.17 | 5492.60 | 0.00 | 2288.85 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28605.79 | 26-DEC-08:09 | 8876.89 | 10035.17 | 5492.60 | 0.00 | 2530.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 23599.30 | 8876.89 | 10035.17 | 0.00 | 0.00 | 1629.26 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30028.30 | 9729.34 | 10035.17 | 5492.60 | 0.00 | 2656.05 | 0.00 | 0.00 | 7297.10 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 259009.08 | 04-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 237062.05 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 189588.48 | 15-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 112213.15 | 04-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 35666.65 | 01-MAY-03:20 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 4917.54 | 02-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 10290.88 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 64823.42 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 149782.60 | 25-NOV-08:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 255322.25 | 18-DEC-17:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 259009.08 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.33 | 16.22 | 17.50 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
February | 14.83 | 16.40 | 8.17 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
March | 13.50 | 16.15 | 6.83 | 16.53 | 0.00 | 16.53 | 0.00 | 16.53 |
April | 4.50 | 16.29 | 3.50 | 16.45 | 0.00 | 16.45 | 0.00 | 16.45 |
May | 0.50 | 17.10 | 0.50 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.00 | 16.75 | 0.83 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
November | 5.67 | 16.17 | 3.67 | 16.42 | 0.00 | 16.42 | 0.00 | 16.42 |
December | 30.50 | 15.75 | 9.17 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
Annual Sum or Average | 112.83 | 16.12 | 50.17 | 16.57 | 0.00 | 16.57 | 0.00 | 16.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.33 | 17.10 | 17.50 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 114.83 | 14.32 | 4.33 | 14.32 | 0.00 | 14.32 | 0.00 | 14.32 |
February | 99.17 | 14.49 | 4.17 | 14.49 | 0.00 | 14.49 | 0.00 | 14.49 |
March | 88.67 | 14.66 | 5.33 | 14.66 | 0.00 | 14.66 | 0.00 | 14.66 |
April | 30.17 | 14.84 | 3.00 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
May | 1.17 | 14.97 | 0.17 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.30 | 0.00 | 27.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5.50 | 14.95 | 0.33 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
November | 66.50 | 14.77 | 4.00 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
December | 112.67 | 14.39 | 4.17 | 14.39 | 0.00 | 14.39 | 0.00 | 14.39 |
Annual Sum or Average | 518.67 | 14.52 | 25.50 | 14.52 | 0.83 | 14.54 | 0.00 | 14.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.83 | 14.97 | 5.33 | 14.96 | 0.83 | 27.30 | 0.00 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.17 | 8.55 | 12.00 | 8.40 | 0.00 | 8.40 | 0.00 | 8.40 |
February | 3.33 | 8.92 | 0.00 | 8.92 | 0.00 | 8.92 | 0.00 | 8.92 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11.50 | 8.72 | 4.83 | 8.60 | 0.00 | 8.60 | 0.00 | 8.60 |
Annual Sum or Average | 40.00 | 8.63 | 16.83 | 8.49 | 0.00 | 8.49 | 0.00 | 8.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.17 | 8.92 | 12.00 | 8.92 | 0.00 | 8.92 | 0.00 | 8.92 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.54 | 300.00 | 20.54 | 300.00 | 20.54 |
February | 276.00 | 20.60 | 276.00 | 20.60 | 276.00 | 20.60 |
March | 324.00 | 20.61 | 324.00 | 20.61 | 324.00 | 20.61 |
April | 300.00 | 20.69 | 295.17 | 20.68 | 295.17 | 20.67 |
May | 293.33 | 22.04 | 133.83 | 21.65 | 127.17 | 21.41 |
June | 248.33 | 23.47 | 124.67 | 23.60 | 75.50 | 23.61 |
July | 59.83 | 24.35 | 263.17 | 24.24 | 54.33 | 24.27 |
August | 108.17 | 23.82 | 234.00 | 24.04 | 62.33 | 24.06 |
September | 269.00 | 22.55 | 83.83 | 22.41 | 64.83 | 22.24 |
October | 300.00 | 20.79 | 268.83 | 20.71 | 268.83 | 20.68 |
November | 288.00 | 20.63 | 286.17 | 20.63 | 286.17 | 20.63 |
December | 300.00 | 20.59 | 300.00 | 20.59 | 300.00 | 20.59 |
Annual Sum or Average | 3066.67 | 21.35 | 2889.67 | 21.38 | 2434.33 | 21.24 |
Minimum of Months | 59.83 | 20.54 | 83.83 | 20.54 | 54.33 | 20.54 |
Maximum of Months | 324.00 | 24.35 | 324.00 | 24.24 | 324.00 | 24.27 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
February | 276.00 | 15.54 | 276.00 | 15.54 | 276.00 | 15.54 |
March | 324.00 | 15.56 | 324.00 | 15.56 | 324.00 | 15.56 |
April | 300.00 | 16.21 | 300.00 | 16.21 | 300.00 | 16.21 |
May | 287.33 | 19.75 | 209.50 | 19.48 | 191.83 | 19.23 |
June | 266.50 | 23.31 | 152.83 | 23.80 | 123.83 | 23.93 |
July | 141.83 | 26.30 | 282.33 | 26.21 | 137.00 | 26.26 |
August | 185.33 | 25.04 | 257.67 | 25.40 | 138.50 | 25.50 |
September | 262.00 | 20.81 | 163.83 | 20.68 | 141.83 | 20.43 |
October | 300.00 | 16.48 | 300.00 | 16.48 | 300.00 | 16.48 |
November | 288.00 | 15.65 | 288.00 | 15.65 | 288.00 | 15.65 |
December | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
Annual Sum or Average | 3231.00 | 18.16 | 3154.17 | 18.29 | 2821.00 | 18.06 |
Minimum of Months | 141.83 | 15.54 | 152.83 | 15.54 | 123.83 | 15.54 |
Maximum of Months | 324.00 | 26.30 | 324.00 | 26.21 | 324.00 | 26.26 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 9.92 | 300.00 | 9.92 | 300.00 | 9.92 |
February | 276.00 | 10.02 | 276.00 | 10.02 | 276.00 | 10.02 |
March | 324.00 | 10.10 | 324.00 | 10.10 | 324.00 | 10.10 |
April | 300.00 | 11.22 | 300.00 | 11.22 | 300.00 | 11.22 |
May | 312.00 | 16.44 | 277.33 | 16.15 | 277.33 | 16.04 |
June | 300.67 | 21.69 | 192.83 | 21.76 | 182.33 | 21.74 |
July | 149.00 | 26.37 | 268.83 | 26.26 | 134.17 | 26.37 |
August | 188.17 | 23.96 | 201.33 | 24.58 | 98.17 | 24.70 |
September | 290.33 | 19.74 | 183.33 | 19.35 | 175.00 | 19.10 |
October | 300.00 | 12.68 | 300.00 | 12.68 | 300.00 | 12.68 |
November | 288.00 | 10.27 | 288.00 | 10.27 | 288.00 | 10.27 |
December | 300.00 | 9.97 | 300.00 | 9.97 | 300.00 | 9.97 |
Annual Sum or Average | 3328.17 | 14.41 | 3211.67 | 14.41 | 2955.00 | 14.11 |
Minimum of Months | 149.00 | 9.92 | 183.33 | 9.92 | 98.17 | 9.92 |
Maximum of Months | 324.00 | 26.37 | 324.00 | 26.26 | 324.00 | 26.37 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.646434E+09 | 0.126260E+09 | 59.44 | 0.562428E+09 | 84006739.16 | 0.00 | 1.00 | 27-MAY-07:03 | 0.00 | 01-MAY-00:10 | 10731.36 | 27-MAY-07:03 | 8243.57 | 27-MAY-07:03 | 2487.79 | 27-MAY-07:03 | 1903.33 | 27-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.245808E+10 | 0.467237E+09 | 145.06 | 0.186529E+10 | 0.592791E+09 | 0.00 | 1.00 | 24-JUN-07:03 | 0.00 | 01-JUN-00:10 | 19617.91 | 30-JUN-06:03 | 11372.44 | 30-JUN-07:02 | 8986.24 | 24-JUN-07:03 | 3538.82 | 30-JUN-06:03 | 0.00 | 01-JUN-00:10 |
July | 0.480765E+10 | 0.880483E+09 | 220.50 | 0.357451E+10 | 0.123314E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 19094.67 | 22-JUL-07:02 | 11555.03 | 08-JUL-07:02 | 10323.18 | 05-JUL-07:04 | 3382.62 | 22-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.308298E+10 | 0.566678E+09 | 178.20 | 0.224977E+10 | 0.833210E+09 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 18123.92 | 30-AUG-07:03 | 12048.57 | 05-AUG-07:02 | 9381.12 | 30-AUG-07:03 | 3257.56 | 30-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.337376E+09 | 62974140.90 | 33.93 | 0.286381E+09 | 50994296.42 | 0.00 | 1.00 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 | 15266.83 | 02-SEP-07:02 | 10838.58 | 02-SEP-07:02 | 4428.25 | 02-SEP-07:02 | 2795.66 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.113325E+11 | 0.210363E+10 | 637.13 | 0.853837E+10 | 0.279414E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.480765E+10 | 0.880483E+09 | 220.50 | 0.357451E+10 | 0.123314E+10 | 0.00 | 1.00 | 0.00 | 19617.91 | 12048.57 | 10323.18 | 3538.82 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.172153E+10 | 0.380881E+09 | 44.69 | 0.108960E+10 | 0.631930E+09 | 0.00 | 1.00 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 | 38250.16 | 30-JUN-19:25 | 27583.28 | 30-JUN-19:25 | 10666.89 | 30-JUN-19:25 | 7721.44 | 30-JUN-19:25 | 0.00 | 01-JUN-00:10 |
July | 0.352807E+10 | 0.772476E+09 | 130.90 | 0.225885E+10 | 0.126922E+10 | 0.00 | 1.00 | 02-JUL-15:35 | 0.00 | 01-JUL-00:10 | 43154.71 | 23-JUL-09:55 | 28934.68 | 02-JUL-15:35 | 21899.42 | 23-JUL-09:55 | 8385.23 | 23-JUL-09:55 | 0.00 | 01-JUL-00:10 |
August | 0.104657E+10 | 0.232776E+09 | 56.67 | 0.656899E+09 | 0.389671E+09 | 0.00 | 0.75 | 08-AUG-15:10 | 0.00 | 01-AUG-00:10 | 14494.73 | 08-AUG-15:10 | 8707.56 | 08-AUG-15:10 | 5787.17 | 08-AUG-15:10 | 3172.91 | 08-AUG-15:10 | 0.00 | 01-AUG-00:10 |
September | 0.103660E+09 | 23212005.61 | 6.33 | 74460516.00 | 29199481.44 | 0.00 | 0.43 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 | 7375.02 | 01-SEP-15:00 | 5545.30 | 01-SEP-15:00 | 1934.30 | 01-SEP-14:00 | 1648.74 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.639983E+10 | 0.140934E+10 | 238.60 | 0.407981E+10 | 0.232002E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.352807E+10 | 0.772476E+09 | 130.90 | 0.225885E+10 | 0.126922E+10 | 0.00 | 1.00 | 0.00 | 43154.71 | 28934.68 | 21899.42 | 8385.23 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.39 | 26.72 | 36.67 | 30.21 | 210.36 | 0.00 | 0.00 | 0.00 |
February | 102.50 | 46.84 | 55.66 | 75.46 | 163.56 | 0.00 | 0.00 | 0.00 |
March | 134.89 | 69.15 | 65.74 | 119.70 | 122.11 | 0.00 | 0.00 | 0.00 |
April | 171.90 | 87.06 | 84.84 | 186.37 | 68.01 | 0.00 | 0.00 | 0.00 |
May | 211.69 | 101.16 | 110.52 | 260.50 | 38.55 | 0.00 | 0.00 | 0.00 |
June | 203.95 | 88.26 | 115.69 | 257.96 | 30.76 | 0.00 | 0.00 | 0.00 |
July | 218.14 | 101.69 | 116.45 | 276.26 | 36.19 | 0.00 | 0.00 | 0.00 |
August | 178.64 | 80.91 | 97.73 | 220.47 | 40.87 | 0.00 | 0.00 | 0.00 |
September | 139.93 | 62.76 | 77.17 | 158.52 | 54.93 | 0.00 | 0.00 | 0.00 |
October | 88.53 | 35.57 | 52.96 | 84.92 | 71.95 | 0.00 | 0.00 | 0.00 |
November | 54.00 | 18.39 | 35.61 | 33.19 | 116.80 | 0.00 | 0.00 | 0.00 |
December | 47.68 | 16.58 | 31.11 | 16.86 | 203.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.78 | 61.34 | 73.44 | 143.76 | 96.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.68 | 16.58 | 31.11 | 16.86 | 30.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 218.14 | 101.69 | 116.45 | 276.26 | 210.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.39 | 26.72 | 36.67 | 30.21 | 210.36 | 0.00 | 0.00 | 0.00 |
February | 102.50 | 46.84 | 55.66 | 75.46 | 163.56 | 0.00 | 0.00 | 0.00 |
March | 134.89 | 69.15 | 65.74 | 119.70 | 122.11 | 0.00 | 0.00 | 0.00 |
April | 171.90 | 87.06 | 84.84 | 186.37 | 68.01 | 0.00 | 0.00 | 0.00 |
May | 211.69 | 101.16 | 110.52 | 260.50 | 38.55 | 0.00 | 0.00 | 0.00 |
June | 203.95 | 88.26 | 115.69 | 257.96 | 30.76 | 0.00 | 0.00 | 0.00 |
July | 218.14 | 101.69 | 116.45 | 276.26 | 36.19 | 0.00 | 0.00 | 0.00 |
August | 178.64 | 80.91 | 97.73 | 220.47 | 40.87 | 0.00 | 0.00 | 0.00 |
September | 139.93 | 62.76 | 77.17 | 158.52 | 54.93 | 0.00 | 0.00 | 0.00 |
October | 88.53 | 35.57 | 52.96 | 84.92 | 71.95 | 0.00 | 0.00 | 0.00 |
November | 54.00 | 18.39 | 35.61 | 33.19 | 116.80 | 0.00 | 0.00 | 0.00 |
December | 47.68 | 16.58 | 31.11 | 16.86 | 203.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.78 | 61.34 | 73.44 | 143.76 | 96.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.68 | 16.58 | 31.11 | 16.86 | 30.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 218.14 | 101.69 | 116.45 | 276.26 | 210.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.52 | 0.00 | 16.52 | 0.37 | 134.60 | 0.00 | 0.00 | 0.00 |
February | 25.38 | 0.00 | 25.38 | 3.35 | 103.15 | 0.00 | 0.00 | 0.00 |
March | 31.23 | 0.00 | 31.23 | 8.14 | 75.52 | 0.00 | 0.00 | 0.00 |
April | 41.01 | 0.40 | 40.62 | 27.82 | 39.87 | 0.00 | 0.00 | 0.00 |
May | 57.59 | 3.08 | 54.51 | 61.40 | 21.20 | 0.00 | 0.00 | 0.00 |
June | 64.18 | 6.99 | 57.19 | 76.15 | 17.01 | 0.00 | 0.00 | 0.00 |
July | 61.26 | 5.15 | 56.11 | 70.79 | 19.95 | 0.00 | 0.00 | 0.00 |
August | 46.77 | 0.94 | 45.83 | 49.32 | 23.23 | 0.00 | 0.00 | 0.00 |
September | 36.36 | 0.03 | 36.33 | 30.78 | 32.54 | 0.00 | 0.00 | 0.00 |
October | 25.22 | 0.00 | 25.22 | 13.81 | 43.20 | 0.00 | 0.00 | 0.00 |
November | 16.70 | 0.00 | 16.70 | 2.51 | 72.23 | 0.00 | 0.00 | 0.00 |
December | 14.00 | 0.00 | 14.00 | 0.07 | 128.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.41 | 1.39 | 35.02 | 28.86 | 59.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.00 | 0.00 | 14.00 | 0.07 | 17.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.18 | 6.99 | 57.19 | 76.15 | 134.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.52 | 0.00 | 16.52 | 0.37 | 134.60 | 0.00 | 0.00 | 0.00 |
February | 25.37 | 0.00 | 25.37 | 3.35 | 103.15 | 0.00 | 0.00 | 0.00 |
March | 31.23 | 0.00 | 31.23 | 8.14 | 75.52 | 0.00 | 0.00 | 0.00 |
April | 41.01 | 0.40 | 40.62 | 27.82 | 39.87 | 0.00 | 0.00 | 0.00 |
May | 57.59 | 3.08 | 54.51 | 61.40 | 21.20 | 0.00 | 0.00 | 0.00 |
June | 64.18 | 6.99 | 57.19 | 76.14 | 17.00 | 0.00 | 0.00 | 0.00 |
July | 61.26 | 5.15 | 56.11 | 70.79 | 19.95 | 0.00 | 0.00 | 0.00 |
August | 46.76 | 0.94 | 45.83 | 49.32 | 23.23 | 0.00 | 0.00 | 0.00 |
September | 36.35 | 0.03 | 36.33 | 30.78 | 32.54 | 0.00 | 0.00 | 0.00 |
October | 25.22 | 0.00 | 25.22 | 13.81 | 43.20 | 0.00 | 0.00 | 0.00 |
November | 16.70 | 0.00 | 16.70 | 2.51 | 72.23 | 0.00 | 0.00 | 0.00 |
December | 14.00 | 0.00 | 14.00 | 0.07 | 128.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.40 | 1.39 | 35.02 | 28.86 | 59.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.00 | 0.00 | 14.00 | 0.07 | 17.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.18 | 6.99 | 57.19 | 76.14 | 134.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.99 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.57 | 84.19 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.78 | 59.54 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.53 | 33.37 | 3.17 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 180.03 | 21.37 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 188.21 | 20.61 | 25.50 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 186.20 | 28.04 | 8.00 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.52 | 27.91 | 8.00 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.91 | 32.99 | 3.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.80 | 34.74 | 13.67 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.38 | 54.54 | 14.17 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.65 | 50.46 | 76.33 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 20.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 188.21 | 107.99 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.99 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.57 | 84.19 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.78 | 59.54 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.53 | 33.37 | 3.17 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 180.03 | 21.37 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 188.21 | 20.61 | 25.50 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 186.20 | 28.04 | 8.00 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.52 | 27.91 | 8.00 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.91 | 32.99 | 3.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.80 | 34.74 | 13.67 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.38 | 54.54 | 14.17 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.65 | 50.46 | 76.33 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 20.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 188.21 | 107.99 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.99 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.57 | 84.19 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.78 | 59.54 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.53 | 33.37 | 3.17 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 180.03 | 21.37 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 188.21 | 20.61 | 25.50 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 186.20 | 28.04 | 8.00 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.52 | 27.91 | 8.00 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.91 | 32.99 | 3.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.80 | 34.74 | 13.67 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.38 | 54.54 | 14.17 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.65 | 50.46 | 76.33 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 20.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 188.21 | 107.99 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.99 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.57 | 84.19 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.78 | 59.54 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.53 | 33.37 | 3.17 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 180.03 | 21.37 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 188.21 | 20.61 | 25.50 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 186.20 | 28.04 | 8.00 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.52 | 27.91 | 8.00 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.91 | 32.99 | 3.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.80 | 34.74 | 13.67 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.38 | 54.54 | 14.17 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.65 | 50.46 | 76.33 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 20.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 188.21 | 107.99 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.99 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.57 | 84.19 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.78 | 59.54 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.53 | 33.37 | 3.17 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 180.03 | 21.37 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 188.21 | 20.61 | 25.50 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 186.20 | 28.04 | 8.00 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.52 | 27.91 | 8.00 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.91 | 32.99 | 3.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.80 | 34.74 | 13.67 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.38 | 54.54 | 14.17 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.65 | 50.46 | 76.33 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 20.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 188.21 | 107.99 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.99 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.57 | 84.19 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.78 | 59.54 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.53 | 33.37 | 3.17 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 180.03 | 21.37 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 188.21 | 20.61 | 25.50 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 186.20 | 28.04 | 8.00 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.52 | 27.91 | 8.00 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.91 | 32.99 | 3.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.80 | 34.74 | 13.67 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.38 | 54.54 | 14.17 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.65 | 50.46 | 76.33 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 20.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 188.21 | 107.99 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.99 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.57 | 84.19 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.78 | 59.54 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.53 | 33.37 | 3.17 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 180.03 | 21.37 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 188.21 | 20.61 | 25.50 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 186.20 | 28.04 | 8.00 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.52 | 27.91 | 8.00 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.91 | 32.99 | 3.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.80 | 34.74 | 13.67 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.38 | 54.54 | 14.17 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.65 | 50.46 | 76.33 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 20.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 188.21 | 107.99 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.99 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.57 | 84.19 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.78 | 59.54 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.53 | 33.37 | 3.17 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 180.03 | 21.37 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 188.21 | 20.61 | 25.50 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 186.20 | 28.04 | 8.00 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.52 | 27.91 | 8.00 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.91 | 32.99 | 3.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.80 | 34.74 | 13.67 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.38 | 54.54 | 14.17 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.65 | 50.46 | 76.33 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 20.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 188.21 | 107.99 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.99 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.57 | 84.19 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.78 | 59.54 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.53 | 33.37 | 3.17 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 180.03 | 21.37 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 188.21 | 20.61 | 25.50 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 186.20 | 28.04 | 8.00 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.52 | 27.91 | 8.00 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.91 | 32.99 | 3.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.80 | 34.74 | 13.67 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.38 | 54.54 | 14.17 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.65 | 50.46 | 76.33 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 20.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 188.21 | 107.99 | 25.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.99 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.57 | 84.19 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.78 | 59.54 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.53 | 33.37 | 3.17 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 180.03 | 21.37 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 188.21 | 20.61 | 25.50 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 186.20 | 28.04 | 8.00 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.52 | 27.91 | 8.00 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.91 | 32.99 | 3.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.80 | 34.74 | 13.67 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.38 | 54.54 | 14.17 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.65 | 50.46 | 76.33 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 20.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 188.21 | 107.99 | 25.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169774E+09 | 71559832.50 | 98214585.15 | 80918704.72 | 0.563438E+09 |
February | 0.247968E+09 | 0.113318E+09 | 0.134650E+09 | 0.182552E+09 | 0.395674E+09 |
March | 0.361298E+09 | 0.185218E+09 | 0.176080E+09 | 0.320614E+09 | 0.327067E+09 |
April | 0.445567E+09 | 0.225668E+09 | 0.219899E+09 | 0.483058E+09 | 0.176285E+09 |
May | 0.566978E+09 | 0.270953E+09 | 0.296025E+09 | 0.697731E+09 | 0.103246E+09 |
June | 0.528645E+09 | 0.228772E+09 | 0.299872E+09 | 0.668641E+09 | 79728173.62 |
July | 0.584257E+09 | 0.272357E+09 | 0.311900E+09 | 0.739947E+09 | 96920791.41 |
August | 0.478460E+09 | 0.216703E+09 | 0.261757E+09 | 0.590505E+09 | 0.109465E+09 |
September | 0.362699E+09 | 0.162674E+09 | 0.200024E+09 | 0.410874E+09 | 0.142385E+09 |
October | 0.237119E+09 | 95273739.73 | 0.141845E+09 | 0.227444E+09 | 0.192709E+09 |
November | 0.139966E+09 | 47669071.52 | 92296860.30 | 86024738.71 | 0.302740E+09 |
December | 0.127714E+09 | 44400978.20 | 83313132.21 | 45153870.77 | 0.543754E+09 |
Annual Sum or Average | 0.425044E+10 | 0.193457E+10 | 0.231588E+10 | 0.453346E+10 | 0.303341E+10 |
Minimum of Months | 0.127714E+09 | 44400978.20 | 83313132.21 | 45153870.77 | 79728173.62 |
Maximum of Months | 0.584257E+09 | 0.272357E+09 | 0.311900E+09 | 0.739947E+09 | 0.563438E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169774E+09 | 71559832.50 | 98214585.15 | 80918704.72 | 0.563438E+09 |
February | 0.247968E+09 | 0.113318E+09 | 0.134650E+09 | 0.182552E+09 | 0.395674E+09 |
March | 0.361298E+09 | 0.185218E+09 | 0.176080E+09 | 0.320614E+09 | 0.327067E+09 |
April | 0.445567E+09 | 0.225668E+09 | 0.219899E+09 | 0.483058E+09 | 0.176285E+09 |
May | 0.566978E+09 | 0.270953E+09 | 0.296025E+09 | 0.697731E+09 | 0.103246E+09 |
June | 0.528645E+09 | 0.228772E+09 | 0.299872E+09 | 0.668641E+09 | 79728173.62 |
July | 0.584257E+09 | 0.272357E+09 | 0.311900E+09 | 0.739947E+09 | 96920791.41 |
August | 0.478460E+09 | 0.216703E+09 | 0.261757E+09 | 0.590505E+09 | 0.109465E+09 |
September | 0.362699E+09 | 0.162674E+09 | 0.200024E+09 | 0.410874E+09 | 0.142385E+09 |
October | 0.237119E+09 | 95273739.73 | 0.141845E+09 | 0.227444E+09 | 0.192709E+09 |
November | 0.139966E+09 | 47669071.52 | 92296860.30 | 86024738.71 | 0.302740E+09 |
December | 0.127714E+09 | 44400978.20 | 83313132.21 | 45153870.77 | 0.543754E+09 |
Annual Sum or Average | 0.425044E+10 | 0.193457E+10 | 0.231588E+10 | 0.453346E+10 | 0.303341E+10 |
Minimum of Months | 0.127714E+09 | 44400978.20 | 83313132.21 | 45153870.77 | 79728173.62 |
Maximum of Months | 0.584257E+09 | 0.272357E+09 | 0.311900E+09 | 0.739947E+09 | 0.563438E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44246669.44 | 0.00 | 44246669.44 | 1002201.57 | 0.360501E+09 |
February | 61388954.64 | 0.00 | 61388954.64 | 8095730.46 | 0.249533E+09 |
March | 83642873.68 | 5828.24 | 83637045.44 | 21796999.43 | 0.202272E+09 |
April | 0.106306E+09 | 1028697.59 | 0.105277E+09 | 72109929.16 | 0.103336E+09 |
May | 0.154258E+09 | 8250543.86 | 0.146007E+09 | 0.164456E+09 | 56788535.87 |
June | 0.166359E+09 | 18123904.71 | 0.148235E+09 | 0.197372E+09 | 44077288.65 |
July | 0.164086E+09 | 13802339.20 | 0.150284E+09 | 0.189603E+09 | 53438240.44 |
August | 0.125256E+09 | 2507701.84 | 0.122749E+09 | 0.132111E+09 | 62212667.58 |
September | 94232278.19 | 66497.31 | 94165780.88 | 79793991.27 | 84331054.17 |
October | 67543133.82 | 0.00 | 67543133.82 | 36997101.97 | 0.115702E+09 |
November | 43279466.01 | 0.00 | 43279466.01 | 6499146.68 | 0.187227E+09 |
December | 37489296.07 | 0.00 | 37489296.07 | 192194.99 | 0.343915E+09 |
Annual Sum or Average | 0.114809E+10 | 43785512.75 | 0.110430E+10 | 0.910029E+09 | 0.186333E+10 |
Minimum of Months | 37489296.07 | 0.00 | 37489296.07 | 192194.99 | 44077288.65 |
Maximum of Months | 0.166359E+09 | 18123904.71 | 0.150284E+09 | 0.197372E+09 | 0.360501E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44245208.51 | 0.00 | 44245208.51 | 1001994.96 | 0.360502E+09 |
February | 61387023.07 | 0.00 | 61387023.07 | 8094880.31 | 0.249534E+09 |
March | 83640353.04 | 5827.97 | 83634525.07 | 21795230.31 | 0.202272E+09 |
April | 0.106303E+09 | 1028649.37 | 0.105274E+09 | 72106729.98 | 0.103336E+09 |
May | 0.154253E+09 | 8250157.15 | 0.146003E+09 | 0.164450E+09 | 56788138.42 |
June | 0.166354E+09 | 18123055.22 | 0.148230E+09 | 0.197365E+09 | 44076946.08 |
July | 0.164081E+09 | 13801692.26 | 0.150279E+09 | 0.189596E+09 | 53437825.54 |
August | 0.125253E+09 | 2507584.30 | 0.122745E+09 | 0.132107E+09 | 62212344.56 |
September | 94229348.21 | 66494.19 | 94162854.02 | 79790587.20 | 84330810.32 |
October | 67540881.23 | 0.00 | 67540881.23 | 36994775.46 | 0.115701E+09 |
November | 43277991.42 | 0.00 | 43277991.42 | 6498446.26 | 0.187227E+09 |
December | 37488017.62 | 0.00 | 37488017.62 | 192122.11 | 0.343916E+09 |
Annual Sum or Average | 0.114805E+10 | 43783460.46 | 0.110427E+10 | 0.909992E+09 | 0.186333E+10 |
Minimum of Months | 37488017.62 | 0.00 | 37488017.62 | 192122.11 | 44076946.08 |
Maximum of Months | 0.166354E+09 | 18123055.22 | 0.150279E+09 | 0.197365E+09 | 0.360502E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31392321.84 | 0.289249E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105403E+09 | 0.203667E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208327E+09 | 0.159472E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.353887E+09 | 86493833.49 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.482195E+09 | 57228845.32 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.487834E+09 | 53418588.35 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.498725E+09 | 75114485.44 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.392440E+09 | 74752034.39 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264160E+09 | 85505232.68 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146781E+09 | 93056863.40 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60590697.66 | 0.141368E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 0.271909E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.304787E+10 | 0.159123E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 53418588.35 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.498725E+09 | 0.289249E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31392321.84 | 0.289249E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105403E+09 | 0.203667E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208327E+09 | 0.159472E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.353887E+09 | 86493833.49 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.482195E+09 | 57228845.32 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.487834E+09 | 53418588.35 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.498725E+09 | 75114485.44 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.392440E+09 | 74752034.39 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264160E+09 | 85505232.68 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146781E+09 | 93056863.40 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60590697.66 | 0.141368E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 0.271909E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.304787E+10 | 0.159123E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 53418588.35 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.498725E+09 | 0.289249E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31392321.84 | 0.289249E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105403E+09 | 0.203667E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208327E+09 | 0.159472E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.353887E+09 | 86493833.49 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.482195E+09 | 57228845.32 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.487834E+09 | 53418588.35 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.498725E+09 | 75114485.44 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.392440E+09 | 74752034.39 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264160E+09 | 85505232.68 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146781E+09 | 93056863.40 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60590697.66 | 0.141368E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 0.271909E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.304787E+10 | 0.159123E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 53418588.35 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.498725E+09 | 0.289249E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31392321.84 | 0.289249E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105403E+09 | 0.203667E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208327E+09 | 0.159472E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.353887E+09 | 86493833.49 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.482195E+09 | 57228845.32 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.487834E+09 | 53418588.35 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.498725E+09 | 75114485.44 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.392440E+09 | 74752034.39 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264160E+09 | 85505232.68 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146781E+09 | 93056863.40 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60590697.66 | 0.141368E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 0.271909E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.304787E+10 | 0.159123E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 53418588.35 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.498725E+09 | 0.289249E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31392321.84 | 0.289249E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105403E+09 | 0.203667E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208327E+09 | 0.159472E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.353887E+09 | 86493833.49 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.482195E+09 | 57228845.32 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.487834E+09 | 53418588.35 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.498725E+09 | 75114485.44 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.392440E+09 | 74752034.39 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264160E+09 | 85505232.68 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146781E+09 | 93056863.40 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60590697.66 | 0.141368E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 0.271909E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.304787E+10 | 0.159123E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 53418588.35 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.498725E+09 | 0.289249E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31392321.84 | 0.289249E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105403E+09 | 0.203667E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208327E+09 | 0.159472E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.353887E+09 | 86493833.49 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.482195E+09 | 57228845.32 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.487834E+09 | 53418588.35 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.498725E+09 | 75114485.44 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.392440E+09 | 74752034.39 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264160E+09 | 85505232.68 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146781E+09 | 93056863.40 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60590697.66 | 0.141368E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 0.271909E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.304787E+10 | 0.159123E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 53418588.35 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.498725E+09 | 0.289249E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31392321.84 | 0.289249E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105403E+09 | 0.203667E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208327E+09 | 0.159472E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.353887E+09 | 86493833.49 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.482195E+09 | 57228845.32 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.487834E+09 | 53418588.35 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.498725E+09 | 75114485.44 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.392440E+09 | 74752034.39 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264160E+09 | 85505232.68 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146781E+09 | 93056863.40 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60590697.66 | 0.141368E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 0.271909E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.304787E+10 | 0.159123E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 53418588.35 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.498725E+09 | 0.289249E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31392321.84 | 0.289249E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105403E+09 | 0.203667E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208327E+09 | 0.159472E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.353887E+09 | 86493833.49 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.482195E+09 | 57228845.32 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.487834E+09 | 53418588.35 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.498725E+09 | 75114485.44 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.392440E+09 | 74752034.39 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264160E+09 | 85505232.68 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146781E+09 | 93056863.40 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60590697.66 | 0.141368E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 0.271909E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.304787E+10 | 0.159123E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 53418588.35 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.498725E+09 | 0.289249E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31392321.84 | 0.289249E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105403E+09 | 0.203667E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208327E+09 | 0.159472E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.353887E+09 | 86493833.49 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.482195E+09 | 57228845.32 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.487834E+09 | 53418588.35 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.498725E+09 | 75114485.44 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.392440E+09 | 74752034.39 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264160E+09 | 85505232.68 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146781E+09 | 93056863.40 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60590697.66 | 0.141368E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 0.271909E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.304787E+10 | 0.159123E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 53418588.35 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.498725E+09 | 0.289249E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31392321.84 | 0.289249E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105403E+09 | 0.203667E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208327E+09 | 0.159472E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.353887E+09 | 86493833.49 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.482195E+09 | 57228845.32 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.487834E+09 | 53418588.35 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.498725E+09 | 75114485.44 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.392440E+09 | 74752034.39 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264160E+09 | 85505232.68 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146781E+09 | 93056863.40 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60590697.66 | 0.141368E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 0.271909E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.304787E+10 | 0.159123E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16135655.19 | 53418588.35 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.498725E+09 | 0.289249E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 44.67 | 673.42 | 159.81 | 53.43 | 106.38 | 0.00 | 0.00 |
February | 145.59 | 521.39 | 255.75 | 93.68 | 162.07 | 0.00 | 0.00 |
March | 248.84 | 388.42 | 332.24 | 138.31 | 193.93 | 0.00 | 0.00 |
April | 427.13 | 214.52 | 425.83 | 174.92 | 250.91 | 0.00 | 0.00 |
May | 641.52 | 117.21 | 538.56 | 208.49 | 330.07 | 0.00 | 0.00 |
June | 666.04 | 93.36 | 536.27 | 190.51 | 345.76 | 0.00 | 0.00 |
July | 691.57 | 109.74 | 558.80 | 213.68 | 345.12 | 0.00 | 0.00 |
August | 539.00 | 127.60 | 450.80 | 163.69 | 287.11 | 0.00 | 0.00 |
September | 377.69 | 174.02 | 352.57 | 125.57 | 227.00 | 0.00 | 0.00 |
October | 195.78 | 228.61 | 227.49 | 71.14 | 156.35 | 0.00 | 0.00 |
November | 65.76 | 372.43 | 141.39 | 36.78 | 104.61 | 0.00 | 0.00 |
December | 21.84 | 650.82 | 123.36 | 33.15 | 90.20 | 0.00 | 0.00 |
Annual Sum or Average | 339.88 | 305.20 | 342.37 | 125.47 | 216.91 | 0.00 | 0.00 |
Minimum of Months | 21.84 | 93.36 | 123.36 | 33.15 | 90.20 | 0.00 | 0.00 |
Maximum of Months | 691.57 | 673.42 | 558.80 | 213.68 | 345.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 647.56 | 8961.17 | 311.95 | 108.94 | 203.01 | 0.00 | 0.00 |
February | 2274.33 | 6567.54 | 552.84 | 254.38 | 298.46 | 0.00 | 0.00 |
March | 3793.08 | 4152.22 | 796.65 | 450.62 | 346.03 | 0.00 | 0.00 |
April | 5893.09 | 1819.33 | 1160.99 | 731.16 | 429.83 | 0.00 | 0.00 |
May | 7364.52 | 686.67 | 1423.93 | 799.55 | 624.38 | 0.00 | 0.00 |
June | 7766.79 | 620.68 | 1502.58 | 865.49 | 637.09 | 0.00 | 0.00 |
July | 7032.53 | 843.05 | 1536.00 | 915.28 | 620.72 | 0.00 | 0.00 |
August | 5524.75 | 842.43 | 1223.90 | 690.38 | 533.51 | 0.00 | 0.00 |
September | 4050.83 | 1011.85 | 889.33 | 460.40 | 428.93 | 0.00 | 0.00 |
October | 2181.95 | 1519.52 | 510.93 | 195.14 | 315.79 | 0.00 | 0.00 |
November | 1117.21 | 3409.35 | 305.12 | 93.44 | 211.67 | 0.00 | 0.00 |
December | 328.46 | 8058.72 | 242.15 | 61.58 | 180.57 | 0.00 | 0.00 |
Annual Sum or Average | 4004.32 | 3196.45 | 872.96 | 469.87 | 403.09 | 0.00 | 0.00 |
Minimum of Months | 328.46 | 620.68 | 242.15 | 61.58 | 180.57 | 0.00 | 0.00 |
Maximum of Months | 7766.79 | 8961.17 | 1536.00 | 915.28 | 637.09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119639E+09 | 0.180368E+10 | 0.428041E+09 | 0.143120E+09 | 0.284921E+09 | 0.00 | 0.00 |
February | 0.352219E+09 | 0.126134E+10 | 0.618713E+09 | 0.226636E+09 | 0.392077E+09 | 0.00 | 0.00 |
March | 0.666485E+09 | 0.104034E+10 | 0.889878E+09 | 0.370448E+09 | 0.519431E+09 | 0.00 | 0.00 |
April | 0.110713E+10 | 0.556038E+09 | 0.110374E+10 | 0.453394E+09 | 0.650349E+09 | 0.00 | 0.00 |
May | 0.171824E+10 | 0.313938E+09 | 0.144247E+10 | 0.558406E+09 | 0.884060E+09 | 0.00 | 0.00 |
June | 0.172639E+10 | 0.241979E+09 | 0.139000E+10 | 0.493792E+09 | 0.896210E+09 | 0.00 | 0.00 |
July | 0.185231E+10 | 0.293933E+09 | 0.149668E+10 | 0.572317E+09 | 0.924363E+09 | 0.00 | 0.00 |
August | 0.144365E+10 | 0.341773E+09 | 0.120743E+10 | 0.438422E+09 | 0.769007E+09 | 0.00 | 0.00 |
September | 0.978968E+09 | 0.451069E+09 | 0.913859E+09 | 0.325482E+09 | 0.588377E+09 | 0.00 | 0.00 |
October | 0.524380E+09 | 0.612321E+09 | 0.609321E+09 | 0.190547E+09 | 0.418774E+09 | 0.00 | 0.00 |
November | 0.170460E+09 | 0.965347E+09 | 0.366489E+09 | 95338143.03 | 0.271151E+09 | 0.00 | 0.00 |
December | 58507428.26 | 0.174315E+10 | 0.330406E+09 | 88801956.40 | 0.241604E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107184E+11 | 0.962491E+10 | 0.107970E+11 | 0.395670E+10 | 0.684032E+10 | 0.00 | 0.00 |
Minimum of Months | 58507428.26 | 0.241979E+09 | 0.330406E+09 | 88801956.40 | 0.241604E+09 | 0.00 | 0.00 |
Maximum of Months | 0.185231E+10 | 0.180368E+10 | 0.149668E+10 | 0.572317E+09 | 0.924363E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.173442E+10 | 0.240016E+11 | 0.835526E+09 | 0.291791E+09 | 0.543735E+09 | 0.00 | 0.00 |
February | 0.550205E+10 | 0.158882E+11 | 0.133743E+10 | 0.615386E+09 | 0.722040E+09 | 0.00 | 0.00 |
March | 0.101594E+11 | 0.111213E+11 | 0.213374E+10 | 0.120694E+10 | 0.926799E+09 | 0.00 | 0.00 |
April | 0.152749E+11 | 0.471571E+10 | 0.300928E+10 | 0.189517E+10 | 0.111411E+10 | 0.00 | 0.00 |
May | 0.197251E+11 | 0.183918E+10 | 0.381386E+10 | 0.214153E+10 | 0.167233E+10 | 0.00 | 0.00 |
June | 0.201315E+11 | 0.160881E+10 | 0.389469E+10 | 0.224334E+10 | 0.165134E+10 | 0.00 | 0.00 |
July | 0.188359E+11 | 0.225801E+10 | 0.411403E+10 | 0.245148E+10 | 0.166255E+10 | 0.00 | 0.00 |
August | 0.147975E+11 | 0.225636E+10 | 0.327809E+10 | 0.184913E+10 | 0.142897E+10 | 0.00 | 0.00 |
September | 0.104997E+11 | 0.262272E+10 | 0.230515E+10 | 0.119336E+10 | 0.111180E+10 | 0.00 | 0.00 |
October | 0.584414E+10 | 0.406989E+10 | 0.136848E+10 | 0.522659E+09 | 0.845821E+09 | 0.00 | 0.00 |
November | 0.289582E+10 | 0.883703E+10 | 0.790858E+09 | 0.242202E+09 | 0.548656E+09 | 0.00 | 0.00 |
December | 0.879741E+09 | 0.215845E+11 | 0.648580E+09 | 0.164944E+09 | 0.483636E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126280E+12 | 0.100803E+12 | 0.275297E+11 | 0.148179E+11 | 0.127118E+11 | 0.00 | 0.00 |
Minimum of Months | 0.879741E+09 | 0.160881E+10 | 0.648580E+09 | 0.164944E+09 | 0.483636E+09 | 0.00 | 0.00 |
Maximum of Months | 0.201315E+11 | 0.240016E+11 | 0.411403E+10 | 0.245148E+10 | 0.167233E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.109149E+10 | -0.102007E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -71427713.4 | 59.00 | 0.00 | 0.00 |
February | 0.102274E+10 | -958342427.7 | 0.00 | 0.00 | 672.00 | 0.00 | -64401088.3 | 59.00 | 0.00 | 0.00 |
March | 0.118667E+10 | -0.111572E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -70948293.5 | 59.00 | 0.00 | 0.00 |
April | 0.107328E+10 | -0.100534E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -67938226.7 | 58.99 | 0.00 | 0.00 |
May | 0.105817E+10 | -993236461.3 | 0.00 | 0.00 | 744.00 | 0.00 | -64933954.8 | 58.99 | 0.00 | 0.00 |
June | 0.989756E+09 | -930608417.6 | 0.00 | 0.00 | 720.00 | 0.00 | -59147610.1 | 58.99 | 0.00 | 0.00 |
July | 0.909980E+09 | -852047397.1 | 0.00 | 0.00 | 744.00 | 0.00 | -57933000.5 | 58.98 | 0.00 | 0.00 |
August | 0.947750E+09 | -888794044.9 | 0.00 | 0.00 | 744.00 | 0.00 | -58955637.8 | 58.99 | 0.00 | 0.00 |
September | 0.891198E+09 | -830480185.6 | 0.00 | 0.00 | 720.00 | 0.00 | -60717974.0 | 58.99 | 0.00 | 0.00 |
October | 0.934052E+09 | -864909085.7 | 0.00 | 0.00 | 744.00 | 0.00 | -69143387.9 | 58.99 | 0.00 | 0.00 |
November | 0.948194E+09 | -879474906.3 | 0.00 | 0.00 | 720.00 | 0.00 | -68719162.4 | 59.00 | 0.00 | 0.00 |
December | 0.104291E+10 | -971531407.8 | 0.00 | 0.00 | 744.00 | 0.00 | -71378511.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.120962E+11 | -0.113106E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -785644561.2 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.891198E+09 | -0.111572E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -71427713.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.118667E+10 | -830480185.6 | 0.00 | 0.00 | 744.00 | 0.00 | -57933000.5 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.94 | 0.88 | 03-JAN-12:20 | 124.63 | 8.94 | 0.00 | 45.50 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.93 | 0.88 | 02-FEB-10:39 | 155.16 | 10.22 | 0.00 | 74.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.92 | 0.88 | 02-MAR-10:39 | 167.91 | 10.50 | 0.00 | 112.17 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.92 | 0.88 | 01-APR-08:20 | 197.93 | 11.03 | 0.00 | 158.67 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.90 | 0.88 | 01-MAY-09:09 | 967.09 | 12.57 | 0.00 | 271.67 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.90 | 0.88 | 01-JUN-07:19 | 406.70 | 12.90 | 1.83 | 284.83 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.90 | 0.88 | 01-JUL-07:19 | 1053.52 | 14.06 | 27.67 | 291.50 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.90 | 0.88 | 01-AUG-07:49 | 284.79 | 12.71 | 0.00 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.91 | 0.88 | 01-SEP-14:09 | 213.22 | 11.58 | 0.00 | 161.50 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.92 | 0.88 | 01-OCT-08:30 | 173.99 | 10.58 | 0.00 | 110.83 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.93 | 0.88 | 01-NOV-09:09 | 130.29 | 9.33 | 0.00 | 39.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.93 | 0.88 | 01-DEC-11:20 | 120.81 | 8.84 | 0.00 | 22.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.92 | 390.16 | 11.43 | 29.50 | 1819.83 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 226.33 | 0.90 | 0.88 | 120.81 | 8.84 | 0.00 | 22.17 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 437.50 | 0.94 | 0.88 | 1053.52 | 14.06 | 27.67 | 291.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.83 | 0.64 | 31-JAN-15:09 | 245.19 | 22.71 | 118.00 | 18.67 | 100.13 | 20.34 | 89.17 | 0.00 |
February | 265.33 | 0.78 | 0.61 | 18-FEB-15:50 | 496.30 | 24.76 | 161.50 | 52.00 | 137.80 | 21.47 | 146.50 | 0.00 |
March | 254.17 | 0.75 | 0.61 | 02-MAR-16:10 | 514.29 | 24.20 | 164.00 | 71.00 | 435.71 | 24.85 | 179.67 | 40.17 |
April | 296.33 | 0.75 | 0.61 | 02-APR-14:30 | 371.29 | 22.23 | 173.50 | 88.00 | 400.80 | 23.50 | 214.50 | 61.50 |
May | 437.50 | 0.73 | 0.61 | 01-MAY-14:00 | 313.32 | 21.59 | 237.83 | 131.00 | 419.66 | 22.71 | 287.67 | 81.33 |
June | 401.83 | 0.72 | 0.61 | 01-JUN-14:00 | 341.36 | 21.80 | 221.17 | 127.83 | 415.39 | 23.03 | 292.33 | 89.33 |
July | 409.17 | 0.71 | 0.61 | 01-JUL-13:50 | 355.50 | 22.14 | 224.33 | 144.50 | 484.14 | 23.32 | 305.17 | 104.83 |
August | 352.83 | 0.72 | 0.61 | 01-AUG-14:09 | 350.51 | 22.43 | 207.17 | 122.67 | 397.39 | 23.38 | 255.17 | 84.50 |
September | 344.17 | 0.76 | 0.61 | 01-SEP-14:30 | 445.78 | 23.52 | 196.67 | 86.17 | 378.26 | 23.98 | 219.33 | 47.83 |
October | 299.00 | 0.79 | 0.61 | 01-OCT-14:20 | 316.14 | 22.97 | 154.33 | 38.00 | 134.13 | 21.64 | 150.83 | 4.67 |
November | 255.50 | 0.84 | 0.65 | 09-NOV-14:39 | 180.12 | 21.05 | 94.17 | 6.33 | 91.58 | 19.85 | 79.33 | 0.00 |
December | 226.33 | 0.86 | 0.72 | 16-DEC-14:30 | 155.82 | 19.83 | 60.17 | 0.00 | 86.58 | 19.86 | 56.50 | 0.00 |
Annual Sum or Average | 3785.50 | 0.76 | 344.66 | 22.41 | 2012.83 | 886.17 | 315.03 | 22.51 | 2276.17 | 514.17 | ||
Minimum of Months | 226.33 | 0.71 | 0.61 | 155.82 | 19.83 | 60.17 | 0.00 | 86.58 | 19.85 | 56.50 | 0.00 | |
Maximum of Months | 437.50 | 0.86 | 0.72 | 514.29 | 24.76 | 237.83 | 144.50 | 484.14 | 24.85 | 305.17 | 104.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.153750E+11 | 26335.59 | 01-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114583E+11 | 26335.59 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104851E+11 | 26335.59 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.491603E+10 | 26335.59 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.865634E+09 | 26335.59 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11315369.33 | 10371.24 | 02-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.259048E+09 | 26335.59 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.322088E+10 | 26335.59 | 03-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.679069E+10 | 26335.59 | 01-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134775E+11 | 26335.59 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.668596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.153750E+11 | 26335.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.503022E+11 | 65046.93 | 01-JAN-00:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358959E+11 | 65046.93 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.281511E+11 | 65046.93 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.999427E+10 | 65046.93 | 03-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.391834E+09 | 30361.15 | 01-MAY-03:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.444527E+10 | 62320.80 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200659E+11 | 65046.93 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.459262E+11 | 65046.93 | 01-DEC-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195173E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.503022E+11 | 65046.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.182308E+12 | 133094.40 | 03-JAN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135277E+12 | 133094.40 | 01-FEB-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.881746E+11 | 111739.18 | 15-MAR-04:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.254056E+11 | 69898.10 | 04-APR-18:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205779E+09 | 13373.83 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199740E+10 | 32131.94 | 31-OCT-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.673671E+11 | 92813.15 | 25-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171627E+12 | 133094.40 | 16-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.672362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.182308E+12 | 133094.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.646434E+09 | 0.562428E+09 | 10731.36 | 27-MAY-07:03 | 8243.57 | 0.00 |
June | 0.00 | 0.00 | 0.245808E+10 | 0.186529E+10 | 19617.91 | 30-JUN-06:03 | 11365.27 | 0.00 |
July | 0.00 | 0.00 | 0.480765E+10 | 0.357451E+10 | 19094.67 | 22-JUL-07:02 | 9435.93 | 0.00 |
August | 0.00 | 0.00 | 0.308298E+10 | 0.224977E+10 | 18123.92 | 30-AUG-07:03 | 8742.80 | 0.00 |
September | 0.00 | 0.00 | 0.337376E+09 | 0.286381E+09 | 15266.83 | 02-SEP-07:02 | 10838.58 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.113325E+11 | 0.853837E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.480765E+10 | 0.357451E+10 | 19617.91 | 11365.27 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.172153E+10 | 0.108960E+10 | 38250.16 | 30-JUN-19:25 | 27583.28 | 0.00 |
July | 0.00 | 0.00 | 0.352807E+10 | 0.225885E+10 | 43154.71 | 23-JUL-09:55 | 21255.29 | 0.00 |
August | 0.00 | 0.00 | 0.104657E+10 | 0.656899E+09 | 14494.73 | 08-AUG-15:10 | 8707.56 | 0.00 |
September | 0.00 | 0.00 | 0.103660E+09 | 74460516.00 | 7375.02 | 01-SEP-15:00 | 5545.30 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.639983E+10 | 0.407981E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.352807E+10 | 0.225885E+10 | 43154.71 | 27583.28 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.839711E+09 | 0.08 | 315.28 | 01-JAN-00:02 | 0.08 |
February | 0.737010E+09 | 0.08 | 315.28 | 01-FEB-00:02 | 0.08 |
March | 0.757976E+09 | 0.07 | 315.28 | 01-MAR-00:03 | 0.08 |
April | 0.355602E+09 | 0.03 | 315.28 | 01-APR-00:05 | 0.08 |
May | 10404174.80 | 0.00 | 315.28 | 01-MAY-00:10 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 97074103.70 | 0.01 | 315.28 | 12-OCT-05:33 | 0.08 |
November | 0.683743E+09 | 0.07 | 315.28 | 01-NOV-00:10 | 0.08 |
December | 0.843684E+09 | 0.08 | 315.28 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.432520E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.843684E+09 | 0.08 | 315.28 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112344E+10 | 0.71 | 1005.82 | 14-JAN-07:06 | 0.95 |
February | 0.100321E+10 | 0.66 | 1005.82 | 07-FEB-08:05 | 0.95 |
March | 0.113445E+10 | 0.56 | 1005.82 | 04-MAR-15:40 | 0.95 |
April | 0.101626E+10 | 0.43 | 1005.82 | 07-APR-12:50 | 0.95 |
May | 0.103799E+10 | 0.37 | 1005.82 | 01-MAY-15:00 | 0.95 |
June | 0.103560E+10 | 0.37 | 1005.82 | 23-JUN-11:20 | 0.93 |
July | 0.995765E+09 | 0.35 | 1005.82 | 03-JUL-13:10 | 0.93 |
August | 0.107543E+10 | 0.37 | 1005.82 | 08-AUG-08:20 | 0.93 |
September | 0.995765E+09 | 0.36 | 1005.82 | 02-SEP-09:10 | 0.94 |
October | 0.100148E+10 | 0.36 | 1005.82 | 02-OCT-11:50 | 0.94 |
November | 0.987472E+09 | 0.46 | 1005.82 | 09-NOV-07:10 | 0.95 |
December | 0.110235E+10 | 0.67 | 1005.82 | 08-DEC-08:00 | 0.95 |
Annual Sum or Average | 0.125092E+11 | 0.47 | |||
Minimum of Months | 0.987472E+09 | 0.35 | 1005.82 | 0.93 | |
Maximum of Months | 0.113445E+10 | 0.71 | 1005.82 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159101E+10 | 0.67 | 1558.60 | 01-JAN-00:06 | 0.92 |
February | 0.127427E+10 | 0.65 | 1558.60 | 01-FEB-00:02 | 0.92 |
March | 0.122115E+10 | 0.59 | 1558.60 | 02-MAR-06:01 | 0.92 |
April | 0.826670E+09 | 0.44 | 1558.60 | 03-APR-05:11 | 0.92 |
May | 0.650592E+09 | 0.23 | 961.85 | 10-MAY-06:01 | 0.72 |
June | 0.646524E+09 | 0.22 | 1247.35 | 29-JUN-18:00 | 0.81 |
July | 0.627483E+09 | 0.21 | 1558.60 | 23-JUL-10:53 | 0.90 |
August | 0.666580E+09 | 0.22 | 623.44 | 04-AUG-15:00 | 0.55 |
September | 0.617204E+09 | 0.21 | 623.44 | 01-SEP-13:40 | 0.55 |
October | 0.710390E+09 | 0.34 | 1519.40 | 30-OCT-06:01 | 0.91 |
November | 0.100155E+10 | 0.57 | 1558.60 | 13-NOV-06:01 | 0.92 |
December | 0.151347E+10 | 0.66 | 1558.60 | 01-DEC-02:62 | 0.92 |
Annual Sum or Average | 0.113469E+11 | 0.42 | |||
Minimum of Months | 0.617204E+09 | 0.21 | 623.44 | 0.55 | |
Maximum of Months | 0.159101E+10 | 0.67 | 1558.60 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.112344E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.100321E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.113445E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.101626E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.116425E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.150283E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.187625E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.164210E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.105874E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.100148E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.987472E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.110235E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.146128E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.987472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.187625E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.159101E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.127427E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.122115E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.826670E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.650592E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.102740E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.139996E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.899356E+09 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.640416E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.710390E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.100155E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.151347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.127562E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.640416E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.159101E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.112344E+10 | 0.00 | 0.153750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100321E+10 | 0.00 | 0.114583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113445E+10 | 0.00 | 0.104851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101626E+10 | 0.00 | 0.491603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103799E+10 | 0.646434E+09 | 0.865634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103560E+10 | 0.245808E+10 | 11315369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.995765E+09 | 0.480765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107543E+10 | 0.308298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.995765E+09 | 0.337376E+09 | 0.259048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100148E+10 | 0.00 | 0.322088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.987472E+09 | 0.00 | 0.679069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110235E+10 | 0.00 | 0.134775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125092E+11 | 0.113325E+11 | 0.668596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.987472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113445E+10 | 0.480765E+10 | 0.153750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.159101E+10 | 0.00 | 0.503022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127427E+10 | 0.00 | 0.358959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122115E+10 | 0.00 | 0.281511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.826670E+09 | 0.00 | 0.999427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.650592E+09 | 0.00 | 0.391834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.646524E+09 | 0.171763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.627483E+09 | 0.350743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.666580E+09 | 0.104657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.617204E+09 | 0.103660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.710390E+09 | 0.00 | 0.444527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100155E+10 | 0.00 | 0.200659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151347E+10 | 0.00 | 0.459262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113469E+11 | 0.637529E+10 | 0.195173E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.617204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159101E+10 | 0.350743E+10 | 0.503022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.112344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103799E+10 | 0.00 | 0.00 | 0.00 | 0.126260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103560E+10 | 0.00 | 0.00 | 0.00 | 0.467237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.995765E+09 | 0.00 | 0.00 | 0.00 | 0.880483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107543E+10 | 0.00 | 0.00 | 0.00 | 0.566678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.995765E+09 | 0.00 | 0.00 | 0.00 | 62974140.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.987472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125092E+11 | 0.00 | 0.00 | 0.00 | 0.210363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.987472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113445E+10 | 0.00 | 0.00 | 0.00 | 0.880483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.159101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.826670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.650592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.646524E+09 | 0.00 | 0.00 | 0.00 | 0.380881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.627483E+09 | 0.00 | 0.00 | 0.00 | 0.772476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.666580E+09 | 0.00 | 0.00 | 0.00 | 0.232776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.617204E+09 | 0.00 | 0.00 | 0.00 | 23212005.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.710390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113469E+11 | 0.00 | 0.00 | 0.00 | 0.140934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.617204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159101E+10 | 0.00 | 0.00 | 0.00 | 0.772476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8616691.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408362E+10 | 0.00 | 0.00 | 0.12 |
February | 14541141.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311676E+10 | 0.00 | 0.00 | 0.12 |
March | 22768829.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302160E+10 | 0.00 | 0.00 | 0.13 |
April | 0.105348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163311E+10 | 0.00 | 0.00 | 0.12 |
May | 0.459868E+09 | 24674032.14 | 0.00 | 484951.77 | 403564.06 | 0.339417E+09 | 0.341944E+09 | 0.00 | 0.21 |
June | 0.207808E+09 | 0.285803E+09 | 0.00 | 1584798.95 | 3201941.64 | 2029093.70 | 0.117260E+10 | 0.00 | 0.44 |
July | 12258386.99 | 0.517140E+09 | 0.00 | 3360021.79 | 3728998.48 | 0.00 | 0.130748E+10 | 0.00 | 0.47 |
August | 46235374.67 | 0.220468E+09 | 0.00 | 3739549.48 | 3120546.23 | 0.00 | 0.204040E+10 | 0.00 | 0.56 |
September | 0.632835E+09 | 8172626.91 | 0.00 | 1407839.79 | 74837.19 | 78725782.77 | 0.127697E+10 | 0.00 | 0.29 |
October | 0.281492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136667E+10 | 0.00 | 0.00 | 0.12 |
November | 29615062.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222581E+10 | 0.00 | 0.00 | 0.12 |
December | 15419978.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377292E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.183681E+10 | 0.105626E+10 | 0.00 | 10577161.78 | 10529887.60 | 0.196407E+11 | 0.613939E+10 | 0.00 | 0.24 |
Minimum of Months | 8616691.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.632835E+09 | 0.517140E+09 | 0.00 | 3739549.48 | 3728998.48 | 0.408362E+10 | 0.204040E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147122E+11 | 0.00 | 0.00 | 0.17 |
February | 0.873835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990809E+10 | 0.00 | 0.00 | 0.17 |
March | 0.227132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766499E+10 | 0.00 | 0.00 | 0.19 |
April | 0.337133E+10 | 0.00 | 0.00 | 0.00 | 2918000.12 | 0.151845E+10 | 0.00 | 0.00 | 0.18 |
May | 0.268356E+10 | 0.00 | 0.00 | 0.00 | 34055621.01 | 17199022.63 | 0.00 | 0.00 | 0.18 |
June | 0.230982E+10 | 0.420540E+09 | 0.00 | 154258.66 | 3079042.49 | 0.00 | 77432646.14 | 0.00 | 0.20 |
July | 0.146843E+10 | 0.459321E+09 | 0.00 | 1900259.50 | 660639.59 | 0.00 | 0.115214E+10 | 0.00 | 0.22 |
August | 0.287458E+10 | 98961990.39 | 0.00 | 975851.49 | 251979.58 | 0.00 | 0.761271E+09 | 0.00 | 0.21 |
September | 0.408385E+10 | 0.00 | 0.00 | 168498.40 | 0.00 | 0.00 | 79217684.37 | 0.00 | 0.19 |
October | 0.414173E+10 | 0.00 | 0.00 | 0.00 | 3064010.60 | 0.471231E+09 | 0.00 | 0.00 | 0.17 |
November | 0.262216E+10 | 0.00 | 0.00 | 0.00 | 5388167.45 | 0.433048E+10 | 0.00 | 0.00 | 0.17 |
December | 61381175.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133081E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.267620E+11 | 0.978823E+09 | 0.00 | 3198868.05 | 49417460.86 | 0.519308E+11 | 0.207006E+10 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.414173E+10 | 0.459321E+09 | 0.00 | 1900259.50 | 34055621.01 | 0.147122E+11 | 0.115214E+10 | 0.00 | 0.22 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.234964E+12 | 0.140627E+12 | 0.00 | 0.188045E+11 | 0.689248E+11 |
February | 0.422419E+12 | 0.113427E+12 | 0.00 | 0.139132E+11 | 0.513511E+11 |
March | 0.647921E+12 | 0.775868E+11 | 0.00 | 0.129807E+11 | 0.374695E+11 |
April | 0.850472E+12 | 0.414091E+11 | 0.00 | 0.662532E+10 | 0.128543E+11 |
May | 0.103426E+13 | 0.140456E+11 | 0.00 | 0.378334E+10 | 0.141851E+10 |
June | 0.106248E+13 | 0.126275E+11 | 0.00 | 0.305881E+10 | 0.503337E+10 |
July | 0.110152E+13 | 0.226026E+11 | 0.00 | 0.296472E+10 | 0.998868E+10 |
August | 0.917626E+12 | 0.272900E+11 | 0.00 | 0.540439E+10 | 0.492900E+10 |
September | 0.657508E+12 | 0.356247E+11 | 0.00 | 0.614492E+10 | 0.656165E+09 |
October | 0.337922E+12 | 0.328919E+11 | 0.00 | 0.625806E+10 | 0.417489E+10 |
November | 0.139419E+12 | 0.706598E+11 | 0.00 | 0.920267E+10 | 0.278616E+11 |
December | 0.134762E+12 | 0.137909E+12 | 0.00 | 0.171578E+11 | 0.644948E+11 |
Annual Sum or Average | 0.754127E+13 | 0.726701E+12 | 0.00 | 0.106298E+12 | 0.289157E+12 |
Minimum of Months | 0.134762E+12 | 0.126275E+11 | 0.00 | 0.296472E+10 | 0.656165E+09 |
Maximum of Months | 0.110152E+13 | 0.140627E+12 | 0.00 | 0.188045E+11 | 0.689248E+11 |