Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:44
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 10:44:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 463.43 | 95.85 | 95.85 |
Net Site Energy | 463.43 | 95.85 | 95.85 |
Total Source Energy | 1465.91 | 303.18 | 303.18 |
Net Source Energy | 1465.91 | 303.18 | 303.18 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 99.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 88.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 462.58 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 99.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 88.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 30.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 23.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 99.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 88.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 53.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 31.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 36.36 | 0.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 95.67 | 0.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 31.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 36.36 | 0.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 95.67 | 0.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 462.577 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 462.577 | 100.00 |
Total On-Site and Utility Electric Sources | 462.577 | 100.00 |
Total Electricity End Uses | 462.577 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 10.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2744.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:44 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.0858 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.1969 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3435 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3435 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.0858 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.1969 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.3435 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.3435 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.3435 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-JUN-14:00 | 03-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 16752.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18933.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5424.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5030.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1655.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 41077.31 | 16752.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 16752.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 18933.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5424.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2724.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1655.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 314.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 281.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 194.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 170.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 71.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1464.98 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 65.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 58.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 35.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 302.99 | 0.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 65.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 58.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 35.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 302.99 | 0.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.08 |
ZONE2 FINE STORAGE DIRECT AIR | 2.61 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 38969.34 |
PSZ-OFFICE HEATING COIL | 26014.25 |
PSZ-FINE STORAGE HEATING COIL | 79987.58 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
PSZ-FINE STORAGE | 2.61 | 2.61 | 2.61 | 2.61 | 2.61 | 2.61 | 1.00 | 1.000000 | 2.61 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.08 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.61 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.08 | 1198.63 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.61 | 2796.98 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 0.714526 | 22465.59 | 26014.25 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.61 | 2.61 | 2.61 | 1.73 | 64908.93 | 79987.58 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.08 | 0.541308 | 0.721747 | 22465.59 | 11232.80 | 0.762280 | 0.762280 |
PSZ-FINE STORAGE COOLING COIL | 2.61 | 1.31 | 1.74 | 64908.93 | 32454.47 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.086 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.160 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.197 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.756 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1441.602 | 6.086 | 113.078 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1441.602 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10245.499 | 3.197 | 148.485 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10245.499 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2043 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2043 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
2 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
3 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
4 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
5 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
6 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
7 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
8 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
9 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
10 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
11 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
12 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
13 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
14 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
15 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
16 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.23941589E-14 | 0.16972320E-15 | 0.76147947E-12 | 0.12030052E-15 |
85 | 3 | -0.54770175E-04 | 0.40617527E-06 | -0.37802266E-03 | 0.14612398E-12 |
86 | 2 | 1.1283884 | 0.89444888E-02 | 1.7236739 | -0.72472748E-04 |
87 | 1 | -17.021073 | 0.23277257 | -7.1497137 | 0.33034766 |
88 | 0 | 16.283305 | 0.14884880 | 5.8169840 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.23 | 34 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.231 | ||
2 | NONRESWINDOW_U_0.5032_SHGC_NORTH_0.23 | 35 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.231 | ||
3 | NONRESWINDOW_U_0.5032_SHGC_EAST_0.23 | 36 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.231 | ||
4 | NONRESWINDOW_U_0.5032_SHGC_WEST_0.23 | 37 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.231 | ||
5 | SKYLIGHT_U_0.9_SHGC_0.6 | 38 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93170E-002 | 0.14129 | 0.63059 | 0.63059 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93170E-002 | 0.14129 | 0.63059 | 0.63059 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93170E-002 | 0.14129 | 0.63059 | 0.63059 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93170E-002 | 0.14129 | 0.63059 | 0.63059 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.056 | 0.5354 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.867 | 0.602 | 0.602 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.602 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 2.130E-002 | 8.990E-005 | 1.388E-004 | 7.585E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.108 | 7.775E-005 | 4.952E-005 | 0.132 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.032 | 6.340E-004 | 4.141E-004 | 0.207 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3994E-004 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9414E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2587E-004 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1979E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1949E-004 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0766E-003 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5848E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1816E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4749E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.2479E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1053E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.4886E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2260E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.1758E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7680E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3855E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.4668E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0673E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.6075E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1646E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2840E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8679E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2141E-003 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2648E-004 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0556E-003 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2955E-004 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5708E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3362E-004 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4682E-003 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1880E-004 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0450E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8226E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9973E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0119E-004 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0131E-003 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0331E-004 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2623E-003 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.6743E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2695E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9692E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.0439E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9660E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3232E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1074E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.1358E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8553E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9222E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6649E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4291E-003 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1958E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6837E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3821E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8911E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9475E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8087E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6800E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.5143E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0766E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3296E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1110E-004 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7120E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9497E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7041E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0163E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0538E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5155E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0206E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6025E-004 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.0204E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2881E-004 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3936E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0000E-004 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1764E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0316E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7675E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.3438E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1020E-003 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3391E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4816E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3510E-004 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0648E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0199E-003 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5779E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1871E-003 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8752E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2340E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2488E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9545E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5139E-004 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.3323E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3484E-004 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.2020E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2967E-004 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1029E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7796E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2088E-003 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0598E-004 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.6398E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9993E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.7863E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5868E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5271E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1032E-004 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8081E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0324E-004 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1217E-003 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7850E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0436E-003 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3758E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5681E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0681E-004 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8985E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4037E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6137E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8153E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4881E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4347E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8999E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6895E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7927E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2817E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2274E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2262E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4751E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5992E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2253E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2525E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8810E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3222E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5333E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7959E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4271E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6680E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4566E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6871E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6561E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0990E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8877E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2685E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0642E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7694E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4865E-004 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3769E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9618E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5819E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8236E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5912E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1636E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3823E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1095E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7372E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9357E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3054E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3442E-004 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3100E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0842E-004 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1856E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7347E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6616E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7278E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4490E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0671E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6543E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9861E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7204E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3747E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6604E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4143E-004 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3834E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3852E-004 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0956E-003 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5235E-004 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7961E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0580E-004 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5939E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1326E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8125E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6359E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2020E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7295E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2720E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2604E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5435E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1940E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0866E-004 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5445E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0949E-004 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8816E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0586E-004 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2591E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2647E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9964E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6990E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0939E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6382E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8708E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6597E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0571E-004 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9813E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1032E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2927E-004 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4470E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2595E-004 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7903E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3910E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8581E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9167E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2026E-003 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4995E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3006E-003 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9465E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3370E-003 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9365E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8668E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7823E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7685E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9571E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7933E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8085E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0756E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0444E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9061E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3526E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9871E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2902E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8695E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9156E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4164E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5323E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9089E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0419E-003 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8769E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9556E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7092E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7332E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6850E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1151E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9941E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6221E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1350E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3133E-004 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2223E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2266E-004 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6687E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5154E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4248E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2491E-004 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5807E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8995E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5487E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7226E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1319E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2773E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4293E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8036E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2668E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3555E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0252E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5615E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9000E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0531E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0001E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9796E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1727E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6884E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9255E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4434E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7472E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7976E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9778E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6189E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9348E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3551E-003 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6646E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1876E-003 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2389E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7226E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9837E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9047E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8396E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1244E-004 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6699E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0194E-004 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3235E-003 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2715E-004 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3879E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2457E-004 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8956E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3724E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6399E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8473E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1392E-003 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9708E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3924E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7331E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3435E-004 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2508E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1467E-004 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4849E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2900E-004 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4956E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8861E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0100E-003 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5033E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1936E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8686E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8580E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5784E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4548E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6558E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7122E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2138E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4588E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2035E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1401E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7593E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0975E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2504E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6374E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3813E-004 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2777E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2015E-004 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0618E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4959E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2766E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8833E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3453E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9172E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6551E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7838E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3684E-004 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5952E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4035E-004 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0461E-004 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5303E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5128E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1542E-004 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2550E-004 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9134E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2530E-004 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0562E-004 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2098E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5178E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8511E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8662E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8346E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7046E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2863E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7944E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0452E-004 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9739E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5514E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7072E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9429E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8640E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9264E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9904E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6474E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8551E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5014E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7091E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2555E-004 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1610E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3203E-004 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4029E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2086E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2207E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7776E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4424E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.3873E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0309E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2647E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9214E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.6504E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9229E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.4402E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.2134E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.0776E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.6333E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.9757E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.4080E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.8891E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2145E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5918E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9466E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.9702E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.5538E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3696E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.1900E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.0718E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.7790E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.6869E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9509E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.0058E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.5559E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.2180E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.1875E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.0717E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.7790E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10689.20908 | 12827.05090 | 0.90218 | 1.08262 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 41.51500 | 9.15709E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 5783.01038 | 6939.61245 | 0.16625 | 0.19950 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 6.30000 | 6.07234E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 33108.01583 | 39729.61900 | 2.17824 | 2.61388 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00000 | 9.15790E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 8398.40528 | 10078.08634 | 0.20374 | 0.42471 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 6.30000 | 6.07234E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.97684 | 00:10:00 | 6.30000 | 6.07234E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17324.91 | 1.08262 | 1.08262 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 6242.34 | 0.19950 | 0.19950 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 52982.03 | 2.61388 | 2.61388 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 16881.75 | 0.42471 | 0.42471 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08262 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.61388 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 38969.33751 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08262 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08262 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08262 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08262 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.08262 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.08262 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.61388 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.61388 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.61388 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.61388 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.61388 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.61388 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.08262 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.61388 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.08262 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.08262 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1198.62731 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.08262 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.08262 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.08262 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71453 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.08262 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54131 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.72175 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22465.59000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11232.79500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76228 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76228 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22465.59000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26014.25261 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26014.25261 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.61388 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.61388 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2796.97794 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.61388 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.61388 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.61388 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.72516 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.61388 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.30694 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.74259 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 64908.93000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32454.46500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 64908.93000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 79987.58288 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 79987.58288 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21624.8 | 11.90 | 11.63 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 62877.2 | 12.06 | 11.79 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 3.3437596685E-002 | 2.0639814294E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 4.3302468614E-002 | 3.1945585805E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.2085394794E-002 | 1.3625627078E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5921.20 | 251.31 | 0.00 | -96.9 | 479.38 | 6555.02 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.55 | 0.199 | 0.204 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.55 | 0.199 | 0.204 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5032_SHGC_WEST_0.23 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.861 | 0.231 | 0.231 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5032_SHGC_WEST_0.23 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.861 | 0.231 | 0.231 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5032_SHGC_NORTH_0.23 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.861 | 0.231 | 0.231 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5032_SHGC_NORTH_0.23 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.861 | 0.231 | 0.231 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.647 | 0.525 | 0.526 | |||||||||||||||||
North Total or Average | 6.51 | 2.861 | 0.231 | 0.231 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.793 | 0.549 | 0.550 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.0858 | 236.88 | 1441.60 | LightsWired | LTG_SCH_OFFICE | 47.92 | 168.00 | 39.97 | 0.0000 | Y | 10.82 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 22.09 | 0.0000 | Y | 38.62 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.1969 | 3204.84 | 10245.50 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 20.46 | 0.0000 | Y | 39.36 |
Interior Lighting Total | 4.3435 | 4835.13 | 21001.18 | 88.79 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1441.60 | 418.06 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1441.60 | 144.16 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 93.17 | AstronomicalClock | - | 41.75 | 41.75 | 0.73 | |
EXTERIOR_LIGHTS_B | 4307.58 | AstronomicalClock | - | 83.75 | 62.75 | 50.74 | |
EXTERIOR_LIGHTS_C | 1091.85 | AstronomicalClock | - | 83.75 | 48.85 | 10.01 | |
Exterior Lighting Total | 5492.60 | 61.48 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22465.59 | 17125.07 | 5340.52 | 0.76 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 64908.93 | 45506.35 | 19402.58 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21624.8 | 11.90 | 11.63 | ||||
PSZ-FINE STORAGE COOLING COIL | 62877.2 | 12.06 | 11.79 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 38969.34 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26014.25 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 79987.58 | 0.81 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1198.63 | 1107.16 | 1.00 | 1.38 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.61 | 2796.98 | 1070.05 | 1.00 | 1.28 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.54 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10689.21 | 12827.05 | 54.15 | 0.902 | 1.083 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 23.90 | 23.90 | 0.00829 | 41.52 | 0.00916 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 33108.02 | 39729.62 | 28.51 | 2.178 | 2.614 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 26.70 | 26.70 | 0.00836 | 42.00 | 0.00916 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 0.00 | 41.05 | 0.00924 | 41.90 | 0.00916 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 5783.01 | 6939.61 | 29.30 | 0.166 | 0.200 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00877 | 6.30 | 0.00607 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 8398.41 | 10078.09 | 7.23 | 0.204 | 0.425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00799 | 6.30 | 0.00607 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | 00:10:00 | 10.00 | 12.11 | 0.00700 | 6.30 | 0.00607 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.08 | 1.08 | 0.20 | 0.20 | 1.0826 | 1.0826 | 1.0826 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.61 | 2.61 | 0.42 | 0.42 | 2.6139 | 2.6139 | 2.6139 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 38969.338 | 38969.338 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 38969.34 | 38969.34 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 43.33 | 21.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22465.590 | 17125.070 | 1.082620 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 11232.80 | 10618.97 | 0.721747 | 26.50 | 16.89 | 0.00837405 | 12.00 | 11.03 | 0.00800000 | 41.61 | 0.00915725 | 22.16 | 14.1718 | 23.90 | 0.00829230 | 43.7915 | 10684.89 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26014.253 | 26014.253 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26014.25 | 26014.25 | 1.082616 | 19.63 | 14.55 | 0.00851256 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 9.4479 | 21.10 | 0.00876717 | 54.8369 | 5783.01 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 64908.930 | 45506.353 | 2.613880 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 32454.47 | 30546.77 | 1.742587 | 30.08 | 18.18 | 0.00849225 | 12.00 | 11.03 | 0.00800000 | 42.00 | 0.00915790 | 22.26 | 24.3725 | 26.70 | 0.00836311 | 37.3859 | 33108.02 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 79987.583 | 79987.583 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 79987.58 | 79987.58 | 2.613883 | 14.06 | 11.80 | 0.00790716 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.2483 | 15.56 | 0.00826313 | 73.2368 | 8142.63 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 38969.338 | 38969.338 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.14659581 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 38969.34 | 38969.34 | 1.0000 | 1.14659581 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 30204.6 | 43.33 | 21.85 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38969.34 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 10.00 | 0.00800000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22465.590 | 17125.070 | 1.082620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4069 | 1004.8586 | 1.1738 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.082616 | 1.27075844 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | Sensible | 11232.80 | 10618.97 | 1.0000 | 0.84717574 | 0.721747 | 26.50 | 16.89 | 0.00837405 | 47981.2 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11232.80 | 41.61 | 0.00915725 | 22.16 | 0.10228460 | 14.1718 | 23.90 | 0.00829230 | 23.90 | 0.00829230 | 43.7915 | 10684.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26014.253 | 26014.253 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.082616 | 1.27075844 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26014.25 | 26014.25 | 1.0000 | 1.27075844 | 1.082616 | 19.63 | 14.55 | 0.00851256 | 41322.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26014.25 | 6.30 | 0.00607234 | 6.30 | 0.10228460 | 9.4479 | 21.02 | 0.00876717 | 21.10 | 0.00876717 | 54.8369 | 5783.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 64908.930 | 45506.353 | 2.613880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6267 | 1004.8586 | 1.1738 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.613883 | 3.06813739 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | Sensible | 32454.47 | 30546.77 | 1.0000 | 2.04542289 | 1.742587 | 30.08 | 18.18 | 0.00849225 | 51937.2 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32454.47 | 42.00 | 0.00915790 | 22.26 | 0.42471127 | 24.3725 | 26.70 | 0.00836311 | 26.70 | 0.00836311 | 37.3859 | 33108.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 79987.583 | 79987.583 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.613883 | 3.06813739 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 79987.58 | 79987.58 | 1.0000 | 3.06813739 | 2.613883 | 14.06 | 11.80 | 0.00790716 | 34105.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79987.58 | 6.30 | 0.00607234 | 6.30 | 0.42471127 | 16.2483 | 15.56 | 0.00826313 | 15.56 | 0.00826313 | 73.2368 | 8142.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2672.17 | 1274.50 | 552.33 |
ZONE2 FINE STORAGE | 2973.50 | 2829.17 | 2260.67 |
ZONE3 BULK STORAGE | 3026.50 | 3269.83 | 2708.17 |
Facility | 3113.67 | 3414.67 | 2744.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.17 | 8.67 | 0.17 | 6.50 |
ZONE2 FINE STORAGE | 0.00 | 252.17 | 0.00 | 4.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.17 | 260.67 | 0.17 | 10.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.346 | 0.315 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.44 | 30.00 | 2953.02 | 0.496 | 0.026 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.051 | 0.000 | 1.839 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.44 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.072 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.44 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.57 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.474 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1234791.87 | 0.00 | 1234791.87 | 1205274.28 | 2440066.14 | 2577844.23 | 5424.51 | 2424.28 | 911.21 | 82.87 |
ZONE2 FINE STORAGE | 5779271.86 | 0.00 | 5779271.86 | 562725.07 | 6341996.93 | 13393694.68 | 5401.97 | 3358.03 | 0.00 | 1476.09 |
ZONE3 BULK STORAGE | 0.00 | 0.46E+09 | 0.46E+09 | 10410922.62 | 0.47E+09 | 30805497.77 | 5126.63 | 0.17 | 3633.20 | 3966.20 |
Total Facility | 7014063.72 | 0.46E+09 | 0.47E+09 | 12178921.97 | 0.48E+09 | 46777036.68 | 7109.12 | 3358.48 | 4120.87 | 4023.75 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0940 | 0.0000 | 0.0940 | 0.0856 | 0.1796 | 0.0952 | 301.01 | 2424.17 | 910.83 |
ZONE2 FINE STORAGE | 0.3909 | 0.0000 | 0.3909 | 0.0204 | 0.4114 | 0.4247 | 303.00 | 3333.00 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 16.6809 | 16.6809 | 0.4758 | 17.1567 | 0.9768 | 1910.16 | 0.00 | 1725.84 |
Total Facility | 0.4849 | 16.6809 | 17.1658 | 0.5819 | 17.7477 | 1.4967 | 1985.12 | 3333.17 | 2213.51 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1701275.95 | 0.00 | 1701275.95 | 2577844.23 | 5419.26 | 0.12 | 3340.62 | 80.86 |
PSZ-FINE STORAGE | 7962541.73 | 0.00 | 7962541.73 | 13393694.68 | 5346.95 | 9.39 | 3403.66 | 1475.21 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1295 | 0.0000 | 0.1295 | 0.0952 | 299.16 | 0.08 | 3336.76 |
PSZ-FINE STORAGE | 0.5386 | 0.0000 | 0.5386 | 0.4247 | 302.22 | 0.08 | 3333.70 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3445.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 4868.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1400 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5772 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 430 |
Defaulted Fields | 389 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 462.58 | 1606.07 | 12-MAR-15:40 | 41077.31 | 10-JUN-15:00 |
Electricity:Building | 255.42 | 1123.07 | 12-MAR-15:40 | 20064.35 | 18-JUL-07:10 |
Electricity:Zone:ZONE1 OFFICE | 39.98 | 585.18 | 05-MAR-16:10 | 2631.36 | 11-OCT-07:10 |
Electricity:SpaceType:GENERAL | 225.30 | 1123.07 | 12-MAR-15:40 | 18277.63 | 11-OCT-07:10 |
InteriorLights:Electricity | 88.80 | 653.19 | 12-MAR-15:40 | 8242.46 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.82 | 115.30 | 05-MAR-16:10 | 796.30 | 11-OCT-07:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 88.80 | 653.19 | 12-MAR-15:40 | 8242.46 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 88.80 | 653.19 | 12-MAR-15:40 | 8242.46 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.82 | 115.30 | 05-MAR-16:10 | 796.30 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 88.80 | 653.19 | 12-MAR-15:40 | 8242.46 | 11-OCT-07:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 38.62 | 256.14 | 01-JAN-10:20 | 3745.13 | 07-SEP-08:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 38.62 | 256.14 | 01-JAN-10:20 | 3745.13 | 07-SEP-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 38.62 | 256.14 | 01-JAN-10:20 | 3745.13 | 07-SEP-08:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 176.82 | 281.75 | 01-JAN-08:50 | 13970.67 | 18-JUL-07:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 39.36 | 281.75 | 01-JAN-08:50 | 3809.65 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 39.36 | 281.75 | 01-JAN-08:50 | 3809.65 | 11-OCT-07:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 53.87 | 0.00 | 01-JAN-00:10 | 5184.03 | 07-JUN-16:20 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 30.12 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-MAR-15:40 |
Ventilation (simple):Fans:Electricity | 30.12 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-MAR-15:40 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 30.12 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-MAR-15:40 |
ElectricityPurchased:Facility | 462.58 | 1606.07 | 19-MAR-15:50 | 41077.31 | 10-JUN-15:00 |
ElectricityPurchased:Plant | 462.58 | 1606.07 | 19-MAR-15:50 | 41077.31 | 10-JUN-15:00 |
Cogeneration:ElectricityPurchased | 462.58 | 1606.07 | 19-MAR-15:50 | 41077.31 | 10-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 462.58 | 1606.07 | 19-MAR-15:50 | 41077.31 | 10-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 462.58 | 1606.07 | 19-MAR-15:50 | 41077.31 | 10-JUN-15:00 |
ElectricityNet:Plant | 462.58 | 1606.07 | 19-MAR-15:50 | 41077.31 | 10-JUN-15:00 |
Cogeneration:ElectricityNet | 462.58 | 1606.07 | 19-MAR-15:50 | 41077.31 | 10-JUN-15:00 |
General:Cogeneration:ElectricityNet | 462.58 | 1606.07 | 19-MAR-15:50 | 41077.31 | 10-JUN-15:00 |
Electricity:HVAC | 123.11 | 0.00 | 01-JAN-00:10 | 22112.43 | 08-JUN-16:20 |
General:Fans:Electricity | 23.75 | 0.00 | 01-JAN-00:10 | 2878.74 | 07-JUN-16:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 99.36 | 0.00 | 01-JAN-00:10 | 19266.72 | 10-JUN-15:50 |
General:Cooling:Electricity | 99.36 | 0.00 | 01-JAN-00:10 | 19266.72 | 10-JUN-15:50 |
ExteriorLights:Electricity | 61.48 | 0.00 | 01-JAN-07:20 | 5492.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.48 | 0.00 | 01-JAN-07:20 | 5492.60 | 01-JAN-06:10 |
Electricity:Plant | 22.56 | 483.00 | 01-JAN-00:10 | 1769.67 | 18-JAN-12:20 |
WaterSystems:Electricity | 22.56 | 483.00 | 01-JAN-00:10 | 1769.67 | 18-JAN-12:20 |
Water Heater:WaterSystems:Electricity | 22.56 | 483.00 | 01-JAN-00:10 | 1769.67 | 18-JAN-12:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.85 | 0.00 | 01-JAN-00:10 | 16752.93 | 03-JAN-07:10 |
NaturalGas:HVAC | 0.85 | 0.00 | 01-JAN-00:10 | 16752.93 | 03-JAN-07:10 |
Heating:NaturalGas | 0.85 | 0.00 | 01-JAN-00:10 | 16752.93 | 03-JAN-07:10 |
General:Heating:NaturalGas | 0.85 | 0.00 | 01-JAN-00:10 | 16752.93 | 03-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 620.37 | 0.00 | 01-JAN-00:10 | 102618.06 | 09-JUN-16:20 |
EnergyTransfer:Building | 240.04 | 0.00 | 01-JAN-00:10 | 43367.09 | 12-JUN-16:20 |
EnergyTransfer:Zone:ZONE1 OFFICE | 70.04 | 0.00 | 01-JAN-00:10 | 15833.13 | 12-JUN-16:20 |
Heating:EnergyTransfer | 0.72 | 0.00 | 01-JAN-00:10 | 11491.64 | 03-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.53 | 0.00 | 01-JAN-00:10 | 11491.64 | 03-JAN-07:10 |
General:Heating:EnergyTransfer | 0.72 | 0.00 | 01-JAN-00:10 | 11491.64 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.53 | 0.00 | 01-JAN-00:10 | 11491.64 | 03-JAN-07:10 |
Cooling:EnergyTransfer | 239.32 | 0.00 | 01-JAN-00:10 | 43367.09 | 12-JUN-16:20 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 69.51 | 0.00 | 01-JAN-00:10 | 15833.13 | 12-JUN-16:20 |
General:Cooling:EnergyTransfer | 239.32 | 0.00 | 01-JAN-00:10 | 43367.09 | 12-JUN-16:20 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 69.51 | 0.00 | 01-JAN-00:10 | 15833.13 | 12-JUN-16:20 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 170.00 | 0.00 | 01-JAN-00:10 | 30367.73 | 11-JUN-15:30 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.19 | 0.00 | 01-JAN-00:10 | 1272.60 | 06-FEB-15:00 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.19 | 0.00 | 01-JAN-00:10 | 1272.60 | 06-FEB-15:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 169.81 | 0.00 | 01-JAN-00:10 | 30367.73 | 11-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 169.81 | 0.00 | 01-JAN-00:10 | 30367.73 | 11-JUN-15:30 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 380.33 | 0.00 | 01-JAN-00:10 | 65592.04 | 22-JUN-16:20 |
HeatingCoils:EnergyTransfer | 0.58 | 0.00 | 01-JAN-00:10 | 12580.32 | 03-JAN-07:10 |
CoolingCoils:EnergyTransfer | 379.75 | 0.00 | 01-JAN-00:10 | 65592.04 | 22-JUN-16:20 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.531 | -69.509 | 0.000 | 0.000 | 9.136 | 10.816 | 29.165 | 11.399 | 0.000 | 6.122 | 9.665 | 0.000 | -4.266 | 0.000 | -3.060 | -0.003 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.186 | -169.806 | 0.000 | 0.000 | 18.640 | 38.622 | 0.000 | 73.804 | 0.000 | 2.146 | 49.797 | 0.000 | -12.114 | 0.000 | -1.274 | -0.003 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28.111 | 39.358 | 107.344 | 801.624 | 0.000 | 123.032 | 0.000 | 0.000 | -130.051 | 0.000 | -336.253 | -633.165 |
Total Facility | 0.000 | 0.000 | 0.717 | -239.315 | 0.000 | 0.000 | 55.887 | 88.795 | 136.508 | 886.827 | 0.000 | 131.300 | 59.463 | 0.000 | -146.431 | 0.000 | -340.587 | -633.171 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 29-APR-06:01 | 0.00 | 0.00 | 0.00 | -21334.37 | 0.00 | 0.00 | 130.76 | 418.92 | 917.53 | 18.27 | 0.00 | 0.00 | 19849.55 | 0.00 | -0.00 | 0.00 | -0.65 | 0.00 |
ZONE2 FINE STORAGE | 22-OCT-15:13 | 0.00 | 0.00 | 0.00 | -55435.56 | 0.00 | 0.00 | 0.00 | 322.04 | 0.00 | 4809.42 | 0.00 | 89.87 | 50214.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-APR-06:01 | 0.00 | 0.00 | 0.00 | -67500.39 | 0.00 | 0.00 | 1052.09 | 6151.06 | 2967.56 | 61.01 | 0.00 | 212.14 | 129907.41 | 0.00 | -5902.05 | 0.00 | -66948.84 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 03-JAN-07:01 | 0.00 | 0.00 | 24866.50 | 0.00 | 0.00 | 0.00 | 265.97 | 441.04 | 917.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -541.65 | 0.00 | -4583.46 | -21365.92 |
ZONE2 FINE STORAGE | 25-AUG-06:03 | 0.00 | 0.00 | 2724.40 | 0.00 | 0.00 | 0.00 | 339.00 | 2957.98 | 0.00 | 0.00 | 0.00 | 61.04 | 0.00 | 0.00 | -49.62 | 0.00 | 0.00 | -6032.80 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JAN-07:01 | -4107.77 | 4107.77 | 24866.50 | -4107.77 | 0.00 | 0.00 | 2342.93 | 6895.71 | 2967.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24317.45 | 0.00 | -7530.27 | -1117.21 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0826 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0826 | 0.0945 | 1.0000 | Not calculated | 0.1023 | 0.0945 | ||
PSZ-FINE STORAGE | 2.6139 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6139 | 0.1625 | 1.0000 | Not calculated | 0.4247 | 0.1625 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0826 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0826 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0945 | ||
PSZ-FINE STORAGE | 2.6139 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6139 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1625 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.002360 | 12.7487 | 0.000305 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.002360 | 12.75 | 0.000305 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0826 | 1.0826 | 1.0826 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6139 | 2.6139 | 2.6139 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0826 | 1.0826 | 1.0826 | 1.0826 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6139 | 2.6139 | 2.6139 | 2.6139 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0826 | 1.0826 | 1.0826 | No | 0.1023 | 0.5127 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6139 | 2.6139 | 2.6139 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0826 | 1.0826 | 1.0826 | 1.0826 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6139 | 2.6139 | 2.6139 | 2.6139 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 10.33 |
Number of hours not met | 10.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.85 | 16752.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 99.36 | 19266.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 88.80 | 8242.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.48 | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 30.12 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 23.75 | 2878.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.56 | 1769.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 462.58 |
Natural Gas | 0.00 | 0.85 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 463.43 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 18.36 |
Space Heating | 0.00 |
Space Cooling | 20.55 |
Fans (All) | 11.14 |
Service Water Heating | 4.67 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 95.67 |
Subtotal | 95.67 |
Natural Gas [MJ/m2] | |
Space Heating | 0.18 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.18 |
Subtotal | 0.18 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.16 |
Space Heating | 0.18 |
Space Cooling | 21.44 |
Fans (All) | 11.62 |
Service Water Heating | 4.87 |
Receptacle Equipment | 29.46 |
Miscellaneous | 13.27 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2499. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 5605.33 | 3154.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 5148.67 | 3611.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2644.33 | 2588.50 | 2663.67 | 863.50 | 0.00 |
Min | 2644.33 | 2588.50 | 0.00 | 0.00 | 0.00 |
Max | 5605.33 | 3611.33 | 2663.67 | 863.50 | 0.00 |
Average | 4466.11 | 3118.17 | 887.89 | 287.83 | 0.00 |
Sum | 13398.33 | 9354.50 | 2663.67 | 863.50 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 32858.33 | 168.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 39834.00 | 42885.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 51056.83 | 56108.33 | 58007.67 | 26020.17 | 0.00 |
Min | 32858.33 | 168.67 | 0.00 | 0.00 | 0.00 |
Max | 51056.83 | 56108.33 | 58007.67 | 26020.17 | 0.00 |
Average | 41249.72 | 33054.00 | 19335.89 | 8673.39 | 0.00 |
Sum | 123749.17 | 99162.00 | 58007.67 | 26020.17 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 5350.67 | 3409.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 4812.33 | 3947.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2636.83 | 3256.17 | 2226.17 | 632.17 | 8.67 |
Min | 2636.83 | 3256.17 | 0.00 | 0.00 | 0.00 |
Max | 5350.67 | 3947.67 | 2226.17 | 632.17 | 8.67 |
Average | 4266.61 | 3537.72 | 742.06 | 210.72 | 2.89 |
Sum | 12799.83 | 10613.17 | 2226.17 | 632.17 | 8.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31083.50 | 1943.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 36481.50 | 46237.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 50005.50 | 72485.00 | 49794.17 | 18542.33 | 366.00 |
Min | 31083.50 | 1943.50 | 0.00 | 0.00 | 0.00 |
Max | 50005.50 | 72485.00 | 49794.17 | 18542.33 | 366.00 |
Average | 39190.17 | 40222.00 | 16598.06 | 6180.78 | 122.00 |
Sum | 117570.50 | 120666.00 | 49794.17 | 18542.33 | 366.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:04
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.761496E+09 | 2753.99 | 14-JAN-16:00 | 21.30 | 15.07 | 0.585799E+09 | 768.99 | 28-JAN-14:39 | 18.30 | 11.43 |
February | 0.178970E+10 | 17349.53 | 25-FEB-08:62 | 18.73 | 15.95 | 0.569386E+09 | 855.66 | 25-FEB-08:09 | 18.73 | 15.95 |
March | 0.473137E+10 | 20454.59 | 25-MAR-07:03 | 16.12 | 11.64 | 0.688911E+09 | 879.39 | 18-MAR-07:10 | 16.12 | 11.64 |
April | 0.697287E+10 | 21334.06 | 29-APR-06:01 | 26.67 | 18.04 | 0.642612E+09 | 879.45 | 27-APR-07:10 | 26.67 | 18.04 |
May | 0.890670E+10 | 20704.15 | 08-MAY-05:02 | 28.90 | 19.72 | 0.669089E+09 | 879.45 | 22-MAY-07:10 | 30.28 | 24.90 |
June | 0.924279E+10 | 19979.99 | 08-JUN-05:02 | 31.85 | 24.58 | 0.669122E+09 | 879.45 | 30-JUN-07:10 | 31.05 | 23.48 |
July | 0.842589E+10 | 17955.34 | 05-JUL-05:02 | 32.57 | 24.73 | 0.643435E+09 | 879.46 | 10-JUL-07:10 | 31.18 | 25.84 |
August | 0.866226E+10 | 17559.14 | 07-AUG-05:02 | 29.53 | 24.79 | 0.694863E+09 | 879.45 | 10-AUG-07:10 | 28.68 | 26.20 |
September | 0.758073E+10 | 18561.84 | 27-SEP-06:01 | 23.70 | 20.40 | 0.643371E+09 | 879.39 | 07-SEP-07:10 | 23.70 | 20.40 |
October | 0.657545E+10 | 20460.21 | 23-OCT-06:02 | 19.08 | 14.21 | 0.642251E+09 | 879.41 | 21-OCT-07:10 | 19.08 | 14.21 |
November | 0.414186E+10 | 19308.21 | 04-NOV-07:02 | 15.18 | 13.64 | 0.611053E+09 | 874.55 | 04-NOV-07:10 | 15.18 | 13.64 |
December | 0.171908E+10 | 4800.54 | 01-DEC-15:00 | 23.40 | 13.35 | 0.617394E+09 | 769.01 | 18-DEC-15:39 | 21.43 | 14.86 |
Annual Sum or Average | 0.695102E+11 | 0.767729E+10 | ||||||||
Minimum of Months | 0.761496E+09 | 2753.99 | 15.18 | 11.64 | 0.569386E+09 | 768.99 | 15.18 | 11.43 | ||
Maximum of Months | 0.924279E+10 | 21334.06 | 32.57 | 24.79 | 0.694863E+09 | 879.46 | 31.18 | 26.20 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143444E+10 | 5072.15 | 21-JAN-07:10 | 5.63 | 5.28 | 0.119875E+10 | 1840.80 | 26-JAN-14:20 | 22.20 | 13.80 |
February | 0.126388E+10 | 4593.98 | 27-FEB-07:03 | 11.00 | 10.65 | 0.137575E+10 | 2251.91 | 21-FEB-16:00 | 11.00 | 10.65 |
March | 0.624637E+10 | 50473.49 | 12-MAR-14:23 | 31.35 | 19.49 | 0.193796E+10 | 2246.93 | 29-MAR-12:50 | 31.77 | 19.79 |
April | 0.185831E+11 | 53048.10 | 23-APR-15:23 | 31.80 | 19.70 | 0.185313E+10 | 2246.96 | 28-APR-15:20 | 39.27 | 20.81 |
May | 0.281686E+11 | 52365.74 | 07-MAY-09:03 | 34.20 | 20.38 | 0.192891E+10 | 2247.03 | 08-MAY-15:09 | 39.63 | 21.27 |
June | 0.291243E+11 | 51180.84 | 18-JUN-15:23 | 32.85 | 23.22 | 0.192884E+10 | 2247.04 | 07-JUN-15:30 | 32.85 | 23.22 |
July | 0.252588E+11 | 48030.39 | 04-JUL-11:02 | 36.57 | 24.91 | 0.185462E+10 | 2247.00 | 07-JUL-10:50 | 37.82 | 24.81 |
August | 0.221530E+11 | 46477.44 | 06-AUG-13:02 | 35.40 | 26.32 | 0.200303E+10 | 2247.00 | 04-AUG-14:50 | 35.40 | 26.32 |
September | 0.178382E+11 | 48820.08 | 24-SEP-13:43 | 35.02 | 24.62 | 0.185484E+10 | 2246.94 | 18-SEP-12:09 | 35.02 | 24.62 |
October | 0.133245E+11 | 55435.35 | 22-OCT-15:13 | 30.80 | 17.65 | 0.184775E+10 | 2246.94 | 06-OCT-13:09 | 30.80 | 17.65 |
November | 0.459303E+10 | 26926.94 | 05-NOV-14:05 | 29.33 | 17.25 | 0.170882E+10 | 2246.90 | 08-NOV-13:30 | 29.50 | 17.18 |
December | 0.182134E+10 | 5769.78 | 21-DEC-07:03 | 5.68 | 4.75 | 0.143336E+10 | 2246.81 | 01-DEC-15:20 | 5.68 | 4.75 |
Annual Sum or Average | 0.169810E+12 | 0.209258E+11 | ||||||||
Minimum of Months | 0.126388E+10 | 4593.98 | 5.63 | 4.75 | 0.119875E+10 | 1840.80 | 5.68 | 4.75 | ||
Maximum of Months | 0.291243E+11 | 55435.35 | 36.57 | 26.32 | 0.200303E+10 | 2251.91 | 39.63 | 26.32 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 | 0.263382E+10 | 3721.34 | 26-JAN-14:50 | 21.75 | 13.69 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.85 | 0.293390E+10 | 4866.48 | 24-FEB-15:39 | 26.33 | 17.45 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 | 0.501820E+10 | 8322.16 | 28-MAR-15:39 | 35.53 | 18.66 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.77 | 0.610963E+10 | 9097.65 | 14-APR-12:50 | 37.48 | 20.98 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.24 | 0.705016E+10 | 9097.65 | 01-MAY-09:39 | 37.13 | 21.69 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.58 | 0.709208E+10 | 9097.65 | 02-JUN-12:09 | 37.00 | 21.32 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.65 | 0.626795E+10 | 9097.65 | 01-JUL-10:39 | 36.73 | 27.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 | 0.639562E+10 | 9097.65 | 07-AUG-12:00 | 36.50 | 26.41 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 | 0.574242E+10 | 8903.85 | 26-SEP-15:20 | 36.00 | 22.61 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.85 | 0.547461E+10 | 9035.65 | 02-OCT-15:09 | 36.32 | 21.08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 | 0.462801E+10 | 6649.26 | 04-NOV-14:30 | 30.25 | 17.36 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 | 0.354349E+10 | 5528.93 | 01-DEC-15:09 | 23.22 | 13.42 |
Annual Sum or Average | 0.00 | 0.628899E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.263382E+10 | 3721.34 | 21.75 | 13.42 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.709208E+10 | 9097.65 | 37.48 | 27.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338534E+09 | 24868.46 | 03-JAN-07:01 | 5.50 |
February | 68577976.28 | 13709.76 | 02-FEB-08:62 | 8.07 |
March | 5295109.15 | 1286.16 | 28-MAR-16:03 | 35.40 |
April | 11543548.29 | 1908.68 | 15-APR-16:03 | 39.58 |
May | 10933267.59 | 2138.86 | 27-MAY-16:03 | 42.00 |
June | 8607451.21 | 2260.96 | 10-JUN-16:03 | 43.12 |
July | 7312676.33 | 1671.05 | 07-JUL-16:03 | 39.98 |
August | 8175925.59 | 1462.59 | 05-AUG-16:03 | 35.70 |
September | 9080974.54 | 1371.78 | 30-SEP-16:03 | 34.78 |
October | 5747686.61 | 1256.73 | 02-OCT-16:03 | 35.72 |
November | 2392697.29 | 802.20 | 04-NOV-16:03 | 29.18 |
December | 55193426.99 | 13017.09 | 21-DEC-08:62 | 6.25 |
Annual Sum or Average | 0.531395E+09 | |||
Minimum of Months | 2392697.29 | 802.20 | 5.50 | |
Maximum of Months | 0.338534E+09 | 24868.46 | 43.12 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61122383.70 | 922.76 | 04-JAN-14:00 | 21.40 |
February | 87150471.98 | 1272.60 | 06-FEB-15:00 | 25.50 |
March | 3617731.00 | 582.12 | 03-MAR-17:50 | 25.67 |
April | 1259284.49 | 2286.23 | 28-APR-06:02 | 28.03 |
May | 2171184.11 | 2690.57 | 23-MAY-06:03 | 28.98 |
June | 1870844.71 | 2656.44 | 20-JUN-06:02 | 29.32 |
July | 793926.07 | 2420.86 | 21-JUL-06:02 | 28.83 |
August | 2183503.76 | 2723.98 | 25-AUG-06:03 | 29.17 |
September | 2999242.61 | 1736.45 | 02-SEP-06:03 | 27.25 |
October | 155903.91 | 877.03 | 04-OCT-06:03 | 25.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 22587432.03 | 829.73 | 28-DEC-14:00 | 24.60 |
Annual Sum or Average | 0.185912E+09 | |||
Minimum of Months | 0.00 | 0.00 | 17.72 | |
Maximum of Months | 87150471.98 | 2723.98 | 29.32 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932217E+09 | 789.68 | 18-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.835721E+09 | 787.97 | 10-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.927579E+09 | 793.48 | 18-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.875955E+09 | 750.86 | 03-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.901620E+09 | 769.52 | 24-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.884333E+09 | 782.81 | 24-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.897893E+09 | 786.02 | 26-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.944017E+09 | 788.66 | 16-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.885591E+09 | 791.64 | 09-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.908952E+09 | 796.30 | 11-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.888233E+09 | 779.40 | 03-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.933499E+09 | 784.68 | 29-DEC-16:00 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.108156E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.835721E+09 | 750.86 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.944017E+09 | 796.30 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.345903E+10 | 3532.83 | 18-JAN-08:09 | 0.00 | 0.00 |
February | 0.304790E+10 | 3522.46 | 10-FEB-09:09 | 0.00 | 0.00 |
March | 0.334677E+10 | 3601.01 | 18-MAR-07:10 | 0.00 | 0.00 |
April | 0.308253E+10 | 3328.75 | 08-APR-07:10 | 0.00 | 0.00 |
May | 0.313176E+10 | 3352.09 | 03-MAY-08:09 | 0.00 | 0.00 |
June | 0.307951E+10 | 3624.14 | 24-JUN-08:09 | 0.00 | 0.00 |
July | 0.305455E+10 | 3571.94 | 27-JUL-08:09 | 0.00 | 0.00 |
August | 0.325353E+10 | 3704.90 | 16-AUG-08:09 | 0.00 | 0.00 |
September | 0.311026E+10 | 3745.13 | 07-SEP-08:09 | 0.00 | 0.00 |
October | 0.326277E+10 | 3636.51 | 11-OCT-07:10 | 0.00 | 0.00 |
November | 0.329487E+10 | 3613.54 | 27-NOV-16:00 | 0.00 | 0.00 |
December | 0.349846E+10 | 3611.64 | 29-DEC-16:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386219E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.304790E+10 | 3328.75 | 0.00 | 0.00 | |
Maximum of Months | 0.349846E+10 | 3745.13 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.349554E+10 | 3614.50 | 03-JAN-16:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.307339E+10 | 3531.39 | 10-FEB-08:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.341718E+10 | 3729.86 | 18-MAR-07:10 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.313287E+10 | 3381.01 | 01-APR-06:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.319170E+10 | 3132.49 | 13-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.316341E+10 | 3386.71 | 24-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.315786E+10 | 3487.12 | 26-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.336018E+10 | 3567.46 | 16-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.320483E+10 | 3659.71 | 09-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.332188E+10 | 3809.65 | 11-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.330615E+10 | 3795.77 | 27-NOV-16:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.353295E+10 | 3778.22 | 29-DEC-16:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.393579E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.307339E+10 | 3132.49 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.353295E+10 | 3809.65 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.932217E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5406.83 | 0.829672E+09 |
February | 0.127628E+10 | 0.835721E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17462022.65 | 0.531826E+09 |
March | 0.149825E+10 | 0.927579E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254479E+09 | 0.318126E+09 |
April | 0.138726E+10 | 0.875955E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746736E+09 | 72152134.93 |
May | 0.144276E+10 | 0.901620E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121227E+10 | 8537061.27 |
June | 0.144276E+10 | 0.884333E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120742E+10 | 1772778.03 |
July | 0.138726E+10 | 0.897893E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803360E+09 | 2953129.70 |
August | 0.149825E+10 | 0.944017E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756213E+09 | 7425889.85 |
September | 0.138726E+10 | 0.885591E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569315E+09 | 21363208.63 |
October | 0.138726E+10 | 0.908952E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427465E+09 | 0.158936E+09 |
November | 0.133177E+10 | 0.888233E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126966E+09 | 0.375122E+09 |
December | 0.138726E+10 | 0.933499E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 321344.59 | 0.731737E+09 |
Annual Sum or Average | 0.168137E+11 | 0.108156E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612201E+10 | 0.305962E+10 |
Minimum of Months | 0.127628E+10 | 0.835721E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5406.83 | 1772778.03 |
Maximum of Months | 0.149825E+10 | 0.944017E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121227E+10 | 0.829672E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.345903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128056.17 | 0.238870E+09 |
February | 0.300332E+10 | 0.304790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176437.18 | 0.322333E+09 |
March | 0.352563E+10 | 0.334677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45953430.26 | 0.253980E+09 |
April | 0.326447E+10 | 0.308253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283268E+09 | 33921242.59 |
May | 0.339505E+10 | 0.313176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543624E+09 | 12734512.17 |
June | 0.339505E+10 | 0.307951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399850E+09 | 5945700.69 |
July | 0.326447E+10 | 0.305455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418195E+09 | 3494651.91 |
August | 0.352563E+10 | 0.325353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233719E+09 | 5583175.98 |
September | 0.326447E+10 | 0.311026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143086E+09 | 15175248.98 |
October | 0.326447E+10 | 0.326277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70918268.74 | 37087595.63 |
November | 0.313390E+10 | 0.329487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6217307.02 | 95016021.70 |
December | 0.326447E+10 | 0.349846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653846.35 | 0.250300E+09 |
Annual Sum or Average | 0.395654E+11 | 0.386219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214579E+10 | 0.127444E+10 |
Minimum of Months | 0.300332E+10 | 0.304790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128056.17 | 3494651.91 |
Maximum of Months | 0.352563E+10 | 0.349846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543624E+09 | 0.322333E+09 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.349554E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35598757.03 | 0.357501E+10 |
February | 0.690763E+10 | 0.307339E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141324E+09 | 0.446140E+10 |
March | 0.810895E+10 | 0.341718E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282126E+09 | 0.508625E+10 |
April | 0.750829E+10 | 0.313287E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445303E+09 | 0.133324E+10 |
May | 0.780862E+10 | 0.319170E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696912E+09 | 0.113739E+10 |
June | 0.780862E+10 | 0.316341E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349034E+09 | 0.748013E+09 |
July | 0.750829E+10 | 0.315786E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169324E+09 | 0.968873E+09 |
August | 0.810895E+10 | 0.336018E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104395E+09 | 0.915682E+09 |
September | 0.750829E+10 | 0.320483E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106810E+09 | 0.107117E+10 |
October | 0.750829E+10 | 0.332188E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48453943.93 | 0.119511E+10 |
November | 0.720796E+10 | 0.330615E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6547.66 | 0.252629E+10 |
December | 0.750829E+10 | 0.353295E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14744086.81 | 0.457522E+10 |
Annual Sum or Average | 0.910005E+11 | 0.393579E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239403E+10 | 0.275936E+11 |
Minimum of Months | 0.690763E+10 | 0.307339E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6547.66 | 0.748013E+09 |
Maximum of Months | 0.810895E+10 | 0.353295E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696912E+09 | 0.508625E+10 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 789.68 | 18-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 | 08-JAN-15:00 | 5460.23 | 05-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 787.97 | 10-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 903.13 | 22-FEB-13:00 | 4617.51 | 02-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 793.48 | 18-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3479.87 | 28-MAR-16:03 | 3549.86 | 16-MAR-06:03 |
April | 1680.92 | 01-APR-07:10 | 750.86 | 03-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4978.82 | 27-APR-16:03 | 2425.88 | 11-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 769.52 | 24-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6106.87 | 03-MAY-16:03 | 1138.73 | 15-MAY-06:01 |
June | 1680.92 | 01-JUN-07:10 | 782.81 | 24-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6248.81 | 07-JUN-16:03 | 107.60 | 28-JUN-06:01 |
July | 1680.92 | 01-JUL-07:10 | 786.02 | 26-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4827.13 | 07-JUL-12:00 | 610.03 | 26-JUL-06:01 |
August | 1680.92 | 01-AUG-07:10 | 788.66 | 16-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4029.81 | 07-AUG-16:03 | 970.57 | 16-AUG-06:01 |
September | 1680.92 | 01-SEP-07:10 | 791.64 | 09-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3760.19 | 29-SEP-12:00 | 1206.06 | 27-SEP-06:01 |
October | 1680.92 | 02-OCT-07:10 | 796.30 | 11-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3803.19 | 02-OCT-12:00 | 3386.76 | 31-OCT-06:05 |
November | 1680.92 | 01-NOV-07:10 | 779.40 | 03-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1788.61 | 09-NOV-13:00 | 4661.80 | 27-NOV-07:03 |
December | 1680.92 | 01-DEC-08:09 | 784.68 | 29-DEC-16:00 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.42 | 28-DEC-14:00 | 5321.78 | 21-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 750.86 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 | 107.60 | |||||
Maximum of Months | 1680.92 | 796.30 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 6248.81 | 5460.23 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3532.83 | 18-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.38 | 08-JAN-15:00 | 736.30 | 31-JAN-08:10 |
February | 3955.50 | 01-FEB-08:09 | 3522.46 | 10-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.96 | 05-FEB-15:00 | 1018.32 | 18-FEB-08:20 |
March | 3955.50 | 01-MAR-08:09 | 3601.01 | 18-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.38 | 27-MAR-15:10 | 1730.19 | 24-MAR-24:00 |
April | 3955.50 | 01-APR-07:10 | 3328.75 | 08-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1762.20 | 15-APR-15:10 | 416.91 | 22-APR-17:55 |
May | 3955.50 | 01-MAY-07:10 | 3352.09 | 03-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1943.72 | 05-MAY-15:10 | 182.34 | 15-MAY-03:20 |
June | 3955.50 | 01-JUN-07:10 | 3624.14 | 24-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1978.70 | 06-JUN-15:10 | 182.69 | 18-JUN-04:45 |
July | 3955.50 | 01-JUL-07:10 | 3571.94 | 27-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 995.87 | 20-JUL-15:10 | 151.70 | 19-JUL-03:00 |
August | 3955.50 | 01-AUG-07:10 | 3704.90 | 16-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.36 | 07-AUG-15:10 | 155.83 | 15-AUG-23:48 |
September | 3955.50 | 01-SEP-07:10 | 3745.13 | 07-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.56 | 22-SEP-15:10 | 136.41 | 08-SEP-21:00 |
October | 3955.50 | 02-OCT-07:10 | 3636.51 | 11-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.93 | 03-OCT-15:10 | 280.50 | 12-OCT-03:00 |
November | 3955.50 | 01-NOV-07:10 | 3613.54 | 27-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.54 | 03-NOV-15:10 | 355.84 | 28-NOV-05:00 |
December | 3955.50 | 01-DEC-08:09 | 3611.64 | 29-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.06 | 24-DEC-14:00 | 756.53 | 29-DEC-17:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3328.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.38 | 136.41 | ||||
Maximum of Months | 3955.50 | 3745.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1978.70 | 1730.19 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3614.50 | 03-JAN-16:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1689.86 | 12-JAN-15:00 | 11405.33 | 31-JAN-08:10 |
February | 9097.65 | 01-FEB-08:09 | 3531.39 | 10-FEB-08:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2105.49 | 19-FEB-15:00 | 14056.39 | 18-FEB-08:10 |
March | 9097.65 | 01-MAR-08:09 | 3729.86 | 18-MAR-07:10 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3290.77 | 27-MAR-13:20 | 23693.67 | 24-MAR-23:00 |
April | 9097.65 | 01-APR-07:10 | 3381.01 | 01-APR-06:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4086.69 | 15-APR-14:00 | 8282.51 | 22-APR-18:00 |
May | 9097.65 | 01-MAY-07:10 | 3132.49 | 13-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3589.78 | 27-MAY-15:00 | 6280.85 | 24-MAY-07:04 |
June | 9097.65 | 01-JUN-07:10 | 3386.71 | 24-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.93 | 06-JUN-15:00 | 8985.58 | 24-JUN-10:45 |
July | 9097.65 | 01-JUL-07:10 | 3487.12 | 26-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1037.08 | 01-JUL-12:10 | 5281.17 | 18-JUL-12:30 |
August | 9097.65 | 01-AUG-07:10 | 3567.46 | 16-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 758.00 | 07-AUG-14:00 | 4443.42 | 10-AUG-15:55 |
September | 9097.65 | 01-SEP-07:10 | 3659.71 | 09-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.99 | 29-SEP-13:00 | 3147.87 | 08-SEP-21:00 |
October | 9097.65 | 02-OCT-07:10 | 3809.65 | 11-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1114.46 | 03-OCT-14:00 | 5728.03 | 23-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 3795.77 | 27-NOV-16:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.91 | 04-NOV-13:00 | 7974.24 | 02-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 3778.22 | 29-DEC-16:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.72 | 24-DEC-14:00 | 9909.16 | 29-DEC-17:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 3132.49 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 10.91 | 3147.87 | |||||
Maximum of Months | 9097.65 | 3809.65 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 4086.69 | 23693.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2753.99 | 14-JAN-16:00 | 1680.92 | 620.21 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 |
February | 17349.53 | 25-FEB-08:62 | 6723.69 | 2963.91 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.03 |
March | 20454.59 | 25-MAR-07:03 | 6723.69 | 3017.60 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.12 |
April | 21334.06 | 29-APR-06:01 | 2823.95 | 3351.33 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
May | 20704.15 | 08-MAY-05:02 | 924.51 | 1207.63 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 | 0.00 |
June | 19979.99 | 08-JUN-05:02 | 924.51 | 1207.63 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 196.06 | 0.00 |
July | 17955.34 | 05-JUL-05:02 | 1109.41 | 1449.16 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.84 | 0.00 |
August | 17559.14 | 07-AUG-05:02 | 1109.41 | 1449.16 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.02 | 0.00 |
September | 18561.84 | 27-SEP-06:01 | 2470.96 | 3087.31 | 6422.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1206.06 |
October | 20460.21 | 23-OCT-06:02 | 1764.97 | 2205.22 | 4587.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2427.55 |
November | 19308.21 | 04-NOV-07:02 | 8404.61 | 3893.53 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4800.54 | 01-DEC-15:00 | 1680.92 | 572.35 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2753.99 | 924.51 | 572.35 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21334.06 | 8404.61 | 3893.53 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 196.06 | 2427.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5072.15 | 21-JAN-07:10 | 830.65 | 3073.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4593.98 | 27-FEB-07:03 | 2491.97 | 8640.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.56 |
March | 50473.49 | 12-MAR-14:23 | 0.00 | 768.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.77 | 0.00 |
April | 53048.10 | 23-APR-15:23 | 0.00 | 768.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.91 | 0.00 |
May | 52365.74 | 07-MAY-09:03 | 0.00 | 885.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.70 | 0.00 |
June | 51180.84 | 18-JUN-15:23 | 0.00 | 1024.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 0.00 |
July | 48030.39 | 04-JUL-11:02 | 0.00 | 1024.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.93 | 0.00 |
August | 46477.44 | 06-AUG-13:02 | 0.00 | 1024.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.43 | 0.00 |
September | 48820.08 | 24-SEP-13:43 | 0.00 | 1024.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.69 | 0.00 |
October | 55435.35 | 22-OCT-15:13 | 0.00 | 966.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.87 | 0.00 |
November | 26926.94 | 05-NOV-14:05 | 0.00 | 512.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.38 | 0.00 |
December | 5769.78 | 21-DEC-07:03 | 2491.97 | 9220.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4593.98 | 0.00 | 512.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55435.35 | 2491.97 | 9220.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.70 | 141.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 563.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.76 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.61 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.60 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 640.75 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 563.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1347.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 563.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1347.31 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.291528E+11 | 21474.02 | 14-JAN-16:00 | 0.626160E+09 | 16752.93 | 03-JAN-07:10 |
February | 0.264547E+11 | 21613.43 | 22-FEB-16:00 | 0.119704E+09 | 6555.50 | 02-FEB-07:19 |
March | 0.327616E+11 | 29785.01 | 28-MAR-14:39 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.396606E+11 | 34683.13 | 26-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.488961E+11 | 39402.81 | 03-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.501805E+11 | 41077.31 | 10-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.486603E+11 | 39319.22 | 10-JUL-13:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.480702E+11 | 37729.53 | 07-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.416676E+11 | 34656.53 | 14-SEP-14:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.371108E+11 | 33213.27 | 03-OCT-14:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.303425E+11 | 28007.31 | 08-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.296196E+11 | 22443.01 | 02-DEC-16:00 | 0.107341E+09 | 7643.15 | 21-DEC-07:19 |
Annual Sum or Average | 0.462577E+12 | 0.853205E+09 | ||||
Minimum of Months | 0.264547E+11 | 21474.02 | 0.00 | 0.00 | ||
Maximum of Months | 0.501805E+11 | 41077.31 | 0.626160E+09 | 16752.93 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.788679E+10 | 0.618440E+10 | 0.112984E+11 | 0.00 | 0.159408E+10 | 0.00 | 0.00 | 0.151281E+09 | 0.00 | 0.00 | 0.00 | 0.203789E+10 | 0.00 |
February | 0.695701E+10 | 0.527177E+10 | 0.103734E+11 | 0.00 | 0.145801E+10 | 0.00 | 0.00 | 0.559305E+09 | 0.00 | 0.00 | 0.00 | 0.183517E+10 | 0.00 |
March | 0.769153E+10 | 0.532756E+10 | 0.121089E+11 | 0.00 | 0.209324E+10 | 0.00 | 0.00 | 0.352123E+10 | 0.00 | 0.00 | 0.00 | 0.201908E+10 | 0.00 |
April | 0.709135E+10 | 0.465754E+10 | 0.112578E+11 | 0.00 | 0.542280E+10 | 0.00 | 0.00 | 0.936921E+10 | 0.00 | 0.00 | 0.00 | 0.186190E+10 | 0.00 |
May | 0.722508E+10 | 0.437514E+10 | 0.117000E+11 | 0.00 | 0.809111E+10 | 0.00 | 0.00 | 0.156442E+11 | 0.00 | 0.00 | 0.00 | 0.186055E+10 | 0.00 |
June | 0.712726E+10 | 0.400760E+10 | 0.116594E+11 | 0.00 | 0.822512E+10 | 0.00 | 0.00 | 0.173995E+11 | 0.00 | 0.00 | 0.00 | 0.176167E+10 | 0.00 |
July | 0.711030E+10 | 0.426962E+10 | 0.112984E+11 | 0.00 | 0.794864E+10 | 0.00 | 0.00 | 0.162635E+11 | 0.00 | 0.00 | 0.00 | 0.176987E+10 | 0.00 |
August | 0.755773E+10 | 0.461242E+10 | 0.121016E+11 | 0.00 | 0.701258E+10 | 0.00 | 0.00 | 0.149688E+11 | 0.00 | 0.00 | 0.00 | 0.181706E+10 | 0.00 |
September | 0.720068E+10 | 0.494096E+10 | 0.112504E+11 | 0.00 | 0.505084E+10 | 0.00 | 0.00 | 0.114380E+11 | 0.00 | 0.00 | 0.00 | 0.178675E+10 | 0.00 |
October | 0.749360E+10 | 0.562416E+10 | 0.113057E+11 | 0.00 | 0.367641E+10 | 0.00 | 0.00 | 0.711384E+10 | 0.00 | 0.00 | 0.00 | 0.189702E+10 | 0.00 |
November | 0.748925E+10 | 0.587360E+10 | 0.108562E+11 | 0.00 | 0.171567E+10 | 0.00 | 0.00 | 0.251243E+10 | 0.00 | 0.00 | 0.00 | 0.189535E+10 | 0.00 |
December | 0.796491E+10 | 0.633929E+10 | 0.112984E+11 | 0.00 | 0.158427E+10 | 0.00 | 0.00 | 0.417509E+09 | 0.00 | 0.00 | 0.00 | 0.201525E+10 | 0.00 |
Annual Sum or Average | 0.887955E+11 | 0.614841E+11 | 0.136508E+12 | 0.00 | 0.538728E+11 | 0.00 | 0.00 | 0.993589E+11 | 0.00 | 0.00 | 0.00 | 0.225576E+11 | 0.00 |
Minimum of Months | 0.695701E+10 | 0.400760E+10 | 0.103734E+11 | 0.00 | 0.145801E+10 | 0.00 | 0.00 | 0.151281E+09 | 0.00 | 0.00 | 0.00 | 0.176167E+10 | 0.00 |
Maximum of Months | 0.796491E+10 | 0.633929E+10 | 0.121089E+11 | 0.00 | 0.822512E+10 | 0.00 | 0.00 | 0.173995E+11 | 0.00 | 0.00 | 0.00 | 0.203789E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.626160E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.119704E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.107341E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.853205E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.626160E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 7914.48 | 18-JAN-08:09 | 5492.60 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 1946.03 | 03-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 7824.10 | 10-FEB-08:09 | 5492.60 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 1778.04 | 25-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8124.35 | 18-MAR-07:10 | 5492.60 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 3993.66 | 28-MAR-16:19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 6919.76 | 03-APR-07:10 | 5492.60 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 4320.81 | 27-APR-16:19 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7056.62 | 24-MAY-07:10 | 5492.60 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 5046.26 | 03-MAY-16:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7665.69 | 24-JUN-08:09 | 5492.60 | 01-JUN-05:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 5184.03 | 07-JUN-16:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 7756.47 | 26-JUL-07:10 | 5492.60 | 01-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 5031.82 | 03-JUL-16:19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7923.72 | 16-AUG-08:09 | 5492.60 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4773.78 | 07-AUG-11:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 8042.88 | 07-SEP-08:09 | 5492.60 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4392.59 | 14-SEP-11:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8242.46 | 11-OCT-07:10 | 5492.60 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 4253.11 | 02-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 8179.49 | 27-NOV-16:00 | 5492.60 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 3903.54 | 08-NOV-14:39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 8174.54 | 29-DEC-16:00 | 5492.60 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 1740.14 | 21-DEC-07:19 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 6919.76 | 5492.60 | 10035.17 | 0.00 | 1740.14 | 0.00 | 0.00 | |||||
Maximum of Months | 8242.46 | 5492.60 | 10035.17 | 0.00 | 5184.03 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 870.99 | 14-JAN-15:50 | 0.00 | 0.00 | 0.00 | 1769.67 | 18-JAN-12:20 | 0.00 |
February | 2931.41 | 22-FEB-14:00 | 0.00 | 0.00 | 0.00 | 1767.47 | 01-FEB-12:09 | 0.00 |
March | 9186.59 | 28-MAR-15:30 | 0.00 | 0.00 | 0.00 | 1754.34 | 01-MAR-12:09 | 0.00 |
April | 13748.08 | 27-APR-15:09 | 0.00 | 0.00 | 0.00 | 1730.14 | 01-APR-11:50 | 0.00 |
May | 18178.47 | 03-MAY-16:19 | 0.00 | 0.00 | 0.00 | 1703.07 | 01-MAY-11:09 | 0.00 |
June | 19266.72 | 10-JUN-15:50 | 0.00 | 0.00 | 0.00 | 1679.22 | 01-JUN-11:39 | 0.00 |
July | 17971.33 | 03-JUL-16:19 | 0.00 | 0.00 | 0.00 | 1665.77 | 01-JUL-11:30 | 0.00 |
August | 16330.65 | 07-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1676.14 | 31-AUG-11:20 | 0.00 |
September | 13612.02 | 14-SEP-14:50 | 0.00 | 0.00 | 0.00 | 1698.13 | 30-SEP-11:20 | 0.00 |
October | 12284.11 | 03-OCT-14:09 | 0.00 | 0.00 | 0.00 | 1725.88 | 31-OCT-11:39 | 0.00 |
November | 6366.04 | 09-NOV-13:50 | 0.00 | 0.00 | 0.00 | 1750.56 | 30-NOV-12:09 | 0.00 |
December | 1810.94 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 | 1766.69 | 30-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 870.99 | 0.00 | 0.00 | 0.00 | 1665.77 | 0.00 | ||
Maximum of Months | 19266.72 | 0.00 | 0.00 | 0.00 | 1769.67 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 21474.02 | 14-JAN-16:00 | 7432.75 | 10035.17 | 0.00 | 0.00 | 1598.24 | 0.00 | 0.00 | 812.38 | 0.00 |
February | 21613.43 | 22-FEB-16:00 | 6345.60 | 10035.17 | 0.00 | 0.00 | 1598.24 | 0.00 | 0.00 | 2041.62 | 0.00 |
March | 29785.01 | 28-MAR-14:39 | 5095.01 | 10035.17 | 0.00 | 0.00 | 3903.54 | 0.00 | 0.00 | 9045.59 | 0.00 |
April | 34683.13 | 26-APR-14:00 | 5086.62 | 10035.17 | 0.00 | 0.00 | 4237.63 | 0.00 | 0.00 | 13639.88 | 0.00 |
May | 39402.81 | 03-MAY-14:00 | 5150.48 | 10035.17 | 0.00 | 0.00 | 4863.46 | 0.00 | 0.00 | 17675.63 | 0.00 |
June | 41077.31 | 10-JUN-14:00 | 5424.06 | 10035.17 | 0.00 | 0.00 | 5030.03 | 0.00 | 0.00 | 18933.02 | 0.00 |
July | 39319.22 | 10-JUL-13:39 | 5152.47 | 10035.17 | 0.00 | 0.00 | 4905.00 | 0.00 | 0.00 | 17597.10 | 0.00 |
August | 37729.53 | 07-AUG-14:50 | 5084.18 | 10035.17 | 0.00 | 0.00 | 4722.05 | 0.00 | 0.00 | 16239.84 | 0.00 |
September | 34656.53 | 14-SEP-14:39 | 5085.10 | 10035.17 | 0.00 | 0.00 | 4267.22 | 0.00 | 0.00 | 13604.38 | 0.00 |
October | 33213.27 | 03-OCT-14:09 | 5145.09 | 10035.17 | 0.00 | 0.00 | 4071.37 | 0.00 | 0.00 | 12284.11 | 0.00 |
November | 28007.31 | 08-NOV-15:00 | 6846.53 | 10035.17 | 0.00 | 0.00 | 3903.54 | 0.00 | 0.00 | 5671.30 | 0.00 |
December | 22443.01 | 02-DEC-16:00 | 8068.84 | 10035.17 | 0.00 | 0.00 | 1598.24 | 0.00 | 0.00 | 1149.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21474.02 | 5084.18 | 10035.17 | 0.00 | 0.00 | 1598.24 | 0.00 | 0.00 | 812.38 | 0.00 | |
Maximum of Months | 41077.31 | 8068.84 | 10035.17 | 0.00 | 0.00 | 5030.03 | 0.00 | 0.00 | 18933.02 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 16752.93 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 6555.50 | 02-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 7643.15 | 21-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 16752.93 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.21 | 0.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.85 | 0.50 | 28.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.26 | 0.83 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.32 | 2.33 | 25.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.37 | 2.33 | 26.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.33 | 0.50 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 30.07 | 0.00 | 30.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 17.21 | 0.17 | 17.21 | 8.67 | 26.69 | 6.50 | 26.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.21 | 0.17 | 17.21 | 3.00 | 30.07 | 2.33 | 30.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.33 | 0.00 | 27.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 27.48 | 0.17 | 27.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 | 27.56 | 0.17 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 56.83 | 27.53 | 1.33 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 49.17 | 27.52 | 0.83 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 27.44 | 0.67 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 27.39 | 0.83 | 27.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.45 | 0.00 | 27.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.27 | 0.00 | 27.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 252.17 | 27.50 | 4.00 | 27.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 56.83 | 27.56 | 1.33 | 27.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 299.17 | 22.56 | 55.83 | 22.19 | 55.83 | 21.93 |
February | 193.17 | 23.12 | 33.33 | 23.13 | 9.50 | 23.01 |
March | 24.50 | 23.52 | 223.83 | 24.18 | 0.00 | 24.18 |
April | 11.00 | 27.86 | 300.00 | 24.54 | 11.00 | 24.65 |
May | 44.17 | 26.78 | 312.00 | 24.76 | 44.17 | 24.99 |
June | 77.17 | 25.82 | 312.00 | 24.75 | 77.17 | 24.92 |
July | 108.00 | 25.42 | 300.00 | 24.73 | 108.00 | 24.87 |
August | 131.50 | 25.29 | 324.00 | 24.72 | 131.50 | 24.84 |
September | 91.50 | 25.59 | 300.00 | 24.74 | 91.50 | 24.90 |
October | 17.17 | 26.93 | 300.00 | 24.54 | 17.17 | 24.66 |
November | 20.67 | 23.31 | 202.50 | 24.11 | 0.00 | 24.11 |
December | 256.50 | 23.20 | 8.67 | 23.14 | 6.50 | 23.07 |
Annual Sum or Average | 1274.50 | 23.99 | 2672.17 | 24.21 | 552.33 | 24.30 |
Minimum of Months | 11.00 | 22.56 | 8.67 | 22.19 | 0.00 | 21.93 |
Maximum of Months | 299.17 | 27.86 | 324.00 | 24.76 | 131.50 | 24.99 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.98 | 110.33 | 20.38 | 110.33 | 20.03 |
February | 165.67 | 22.21 | 114.83 | 23.16 | 28.67 | 22.90 |
March | 119.67 | 26.21 | 286.83 | 26.33 | 102.00 | 26.40 |
April | 218.67 | 26.70 | 300.00 | 26.69 | 218.67 | 26.69 |
May | 292.00 | 26.71 | 312.00 | 26.71 | 292.00 | 26.71 |
June | 306.50 | 26.71 | 312.00 | 26.71 | 306.50 | 26.71 |
July | 299.50 | 26.71 | 300.00 | 26.71 | 299.50 | 26.71 |
August | 322.33 | 26.71 | 324.00 | 26.71 | 322.33 | 26.71 |
September | 280.83 | 26.72 | 300.00 | 26.72 | 280.83 | 26.72 |
October | 220.33 | 26.70 | 300.00 | 26.66 | 220.33 | 26.67 |
November | 84.83 | 25.73 | 248.50 | 26.14 | 60.50 | 26.23 |
December | 218.83 | 22.28 | 65.00 | 22.64 | 19.00 | 22.46 |
Annual Sum or Average | 2829.17 | 25.45 | 2973.50 | 25.83 | 2260.67 | 25.93 |
Minimum of Months | 84.83 | 20.98 | 65.00 | 20.38 | 19.00 | 20.03 |
Maximum of Months | 322.33 | 26.72 | 324.00 | 26.72 | 322.33 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.63 | 116.17 | 20.29 | 116.17 | 20.10 |
February | 222.00 | 22.20 | 60.83 | 22.49 | 19.33 | 22.32 |
March | 210.33 | 28.47 | 302.00 | 28.16 | 194.67 | 28.36 |
April | 300.00 | 31.97 | 300.00 | 31.97 | 300.00 | 31.97 |
May | 312.00 | 34.57 | 312.00 | 34.57 | 312.00 | 34.57 |
June | 312.00 | 34.75 | 312.00 | 34.75 | 312.00 | 34.75 |
July | 300.00 | 32.50 | 300.00 | 32.50 | 300.00 | 32.50 |
August | 324.00 | 31.36 | 324.00 | 31.36 | 324.00 | 31.36 |
September | 300.00 | 30.89 | 300.00 | 30.89 | 300.00 | 30.89 |
October | 300.00 | 30.16 | 300.00 | 30.16 | 300.00 | 30.16 |
November | 227.00 | 28.70 | 288.00 | 28.44 | 227.00 | 28.52 |
December | 162.50 | 22.88 | 111.50 | 24.04 | 3.00 | 24.07 |
Annual Sum or Average | 3269.83 | 29.60 | 3026.50 | 30.07 | 2708.17 | 30.39 |
Minimum of Months | 162.50 | 20.63 | 60.83 | 20.29 | 3.00 | 20.10 |
Maximum of Months | 324.00 | 34.75 | 324.00 | 34.75 | 324.00 | 34.75 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.608745E+09 | 0.151281E+09 | 101.33 | 0.543168E+09 | 65576700.22 | 0.00 | 0.35 | 14-JAN-16:00 | 0.00 | 01-JAN-00:10 | 3587.64 | 14-JAN-15:50 | 2912.86 | 14-JAN-16:00 | 676.78 | 14-JAN-15:30 | 870.99 | 14-JAN-15:50 | 0.00 | 01-JAN-00:10 |
February | 0.204840E+10 | 0.499006E+09 | 170.51 | 0.178741E+10 | 0.260991E+09 | 0.00 | 1.00 | 25-FEB-08:62 | 0.00 | 01-FEB-00:10 | 24101.51 | 25-FEB-08:62 | 19011.33 | 25-FEB-08:62 | 5090.18 | 25-FEB-08:62 | 5206.67 | 25-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.602823E+10 | 0.148092E+10 | 268.04 | 0.532131E+10 | 0.706912E+09 | 0.00 | 1.00 | 04-MAR-08:63 | 0.00 | 01-MAR-00:10 | 24540.02 | 11-MAR-08:62 | 22097.27 | 25-MAR-07:03 | 5459.84 | 11-MAR-08:62 | 5321.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.919498E+10 | 0.241588E+10 | 271.23 | 0.836436E+10 | 0.830620E+09 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:10 | 25230.95 | 19-APR-06:02 | 23291.92 | 29-APR-06:01 | 7458.46 | 25-APR-07:04 | 5649.90 | 27-APR-16:05 | 0.00 | 01-APR-00:10 |
May | 0.132315E+11 | 0.362974E+10 | 307.97 | 0.109901E+11 | 0.224140E+10 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:10 | 27009.91 | 24-MAY-06:01 | 23326.28 | 08-MAY-05:02 | 11870.14 | 24-MAY-07:02 | 6358.59 | 01-MAY-16:08 | 0.00 | 01-MAY-00:10 |
June | 0.150329E+11 | 0.403387E+10 | 307.42 | 0.113846E+11 | 0.364825E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 27849.48 | 28-JUN-06:01 | 22943.70 | 13-JUN-05:02 | 14340.66 | 28-JUN-07:02 | 6435.52 | 08-JUN-16:08 | 0.00 | 01-JUN-00:10 |
July | 0.154473E+11 | 0.385307E+10 | 305.79 | 0.101653E+11 | 0.528198E+10 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 28514.56 | 28-JUL-06:01 | 20523.67 | 05-JUL-05:02 | 14942.68 | 18-JUL-07:03 | 6222.87 | 03-JUL-16:08 | 0.00 | 01-JUL-00:10 |
August | 0.163636E+11 | 0.395152E+10 | 311.66 | 0.103175E+11 | 0.604611E+10 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 28738.69 | 22-AUG-06:01 | 19745.71 | 07-AUG-05:02 | 14852.40 | 24-AUG-07:02 | 6071.18 | 07-AUG-16:05 | 0.00 | 01-AUG-00:10 |
September | 0.132583E+11 | 0.318558E+10 | 279.33 | 0.891522E+10 | 0.434306E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:10 | 28767.87 | 09-SEP-06:01 | 20148.13 | 27-SEP-06:01 | 15190.42 | 13-SEP-07:03 | 5985.42 | 13-SEP-06:01 | 0.00 | 01-SEP-00:10 |
October | 0.911788E+10 | 0.221796E+10 | 269.19 | 0.750513E+10 | 0.161275E+10 | 0.00 | 1.00 | 02-OCT-06:01 | 0.00 | 01-OCT-00:10 | 26937.45 | 13-OCT-07:02 | 22164.86 | 23-OCT-06:02 | 11950.55 | 13-OCT-07:02 | 5650.80 | 13-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.505455E+10 | 0.121992E+10 | 232.67 | 0.450438E+10 | 0.550175E+09 | 0.00 | 1.00 | 04-NOV-07:02 | 0.00 | 01-NOV-00:10 | 24086.73 | 18-NOV-08:62 | 20380.66 | 04-NOV-07:02 | 5175.26 | 18-NOV-08:62 | 5204.05 | 18-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.167424E+10 | 0.409680E+09 | 176.81 | 0.150127E+10 | 0.172969E+09 | 0.00 | 0.53 | 02-DEC-15:00 | 0.00 | 01-DEC-00:10 | 5422.34 | 02-DEC-15:00 | 5229.95 | 02-DEC-15:00 | 734.41 | 16-DEC-16:00 | 1282.61 | 02-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.107061E+12 | 0.270484E+11 | 3001.96 | 0.812998E+11 | 0.257608E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.608745E+09 | 0.151281E+09 | 101.33 | 0.543168E+09 | 65576700.22 | 0.00 | 0.35 | 0.00 | 3587.64 | 2912.86 | 676.78 | 870.99 | 0.00 | |||||||
Maximum of Months | 0.163636E+11 | 0.403387E+10 | 311.66 | 0.113846E+11 | 0.604611E+10 | 0.00 | 1.00 | 0.00 | 28767.87 | 23326.28 | 15190.42 | 6435.52 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.227547E+09 | 60298283.16 | 22.17 | 0.195431E+09 | 32116150.44 | 0.00 | 0.18 | 22-FEB-14:50 | 0.00 | 01-FEB-00:10 | 5187.35 | 22-FEB-14:50 | 4498.49 | 22-FEB-14:50 | 1032.97 | 24-FEB-15:00 | 1387.43 | 22-FEB-14:50 | 0.00 | 01-FEB-00:10 |
March | 0.769219E+10 | 0.204031E+10 | 215.53 | 0.659878E+10 | 0.109341E+10 | 0.00 | 1.00 | 12-MAR-11:45 | 0.00 | 01-MAR-00:10 | 61686.73 | 12-MAR-14:23 | 57192.50 | 12-MAR-14:23 | 5645.14 | 12-MAR-10:30 | 15568.39 | 12-MAR-14:23 | 0.00 | 01-MAR-00:10 |
April | 0.251115E+11 | 0.695333E+10 | 416.86 | 0.228199E+11 | 0.229161E+10 | 0.00 | 1.00 | 01-APR-17:10 | 0.00 | 01-APR-00:10 | 64454.61 | 02-APR-13:03 | 60648.90 | 20-APR-17:43 | 8891.60 | 18-APR-17:08 | 18027.93 | 16-APR-15:13 | 0.00 | 01-APR-00:10 |
May | 0.425242E+11 | 0.120145E+11 | 552.20 | 0.356973E+11 | 0.682686E+10 | 0.00 | 1.00 | 01-MAY-05:08 | 0.00 | 01-MAY-00:15 | 67438.18 | 20-MAY-18:23 | 60880.82 | 07-MAY-09:03 | 22868.70 | 24-MAY-06:01 | 18913.41 | 18-MAY-17:08 | 0.00 | 01-MAY-00:10 |
June | 0.483215E+11 | 0.133657E+11 | 553.55 | 0.369271E+11 | 0.113944E+11 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:15 | 71789.67 | 26-JUN-17:10 | 60143.65 | 04-JUN-11:43 | 26201.41 | 20-JUN-17:10 | 19414.11 | 10-JUN-17:06 | 0.00 | 01-JUN-00:10 |
July | 0.480497E+11 | 0.124105E+11 | 558.53 | 0.311865E+11 | 0.168632E+11 | 0.00 | 1.00 | 01-JUL-00:25 | 0.00 | 01-JUL-00:15 | 73412.99 | 19-JUL-17:10 | 57298.60 | 04-JUL-17:42 | 28848.11 | 19-JUL-17:10 | 18915.75 | 02-JUL-16:23 | 0.00 | 01-JUL-00:10 |
August | 0.441370E+11 | 0.110173E+11 | 542.26 | 0.268910E+11 | 0.172459E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:15 | 75187.56 | 18-AUG-17:10 | 53700.65 | 06-AUG-15:43 | 32123.94 | 16-AUG-17:13 | 18314.74 | 07-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 0.328297E+11 | 0.825244E+10 | 469.97 | 0.213898E+11 | 0.114399E+11 | 0.00 | 1.00 | 01-SEP-14:20 | 0.00 | 01-SEP-00:15 | 76359.65 | 09-SEP-06:01 | 55455.59 | 24-SEP-13:43 | 37595.57 | 09-SEP-06:01 | 18033.59 | 14-SEP-17:08 | 0.00 | 01-SEP-00:10 |
October | 0.188108E+11 | 0.489588E+10 | 333.41 | 0.152650E+11 | 0.354582E+10 | 0.00 | 1.00 | 01-OCT-09:35 | 0.00 | 01-OCT-00:30 | 63907.25 | 08-OCT-11:53 | 62290.81 | 22-OCT-15:13 | 12767.07 | 12-OCT-17:17 | 16996.79 | 01-OCT-14:53 | 0.00 | 01-OCT-00:10 |
November | 0.495706E+10 | 0.129251E+10 | 171.17 | 0.423867E+10 | 0.718388E+09 | 0.00 | 1.00 | 05-NOV-14:05 | 0.00 | 01-NOV-00:10 | 31788.54 | 05-NOV-14:05 | 29760.91 | 05-NOV-14:05 | 4165.56 | 19-NOV-14:00 | 7774.20 | 05-NOV-14:05 | 0.00 | 01-NOV-00:10 |
December | 30211254.65 | 7829485.62 | 5.33 | 28390293.59 | 1820961.06 | 0.00 | 0.08 | 01-DEC-14:50 | 0.00 | 01-DEC-00:10 | 2195.43 | 01-DEC-14:50 | 2060.81 | 01-DEC-14:50 | 137.89 | 01-DEC-15:10 | 567.18 | 01-DEC-14:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.272691E+12 | 0.723105E+11 | 3840.98 | 0.201238E+12 | 0.714535E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.483215E+11 | 0.133657E+11 | 558.53 | 0.369271E+11 | 0.172459E+11 | 0.00 | 1.00 | 0.00 | 76359.65 | 62290.81 | 37595.57 | 19414.11 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.65 | 20.86 | 32.79 | 70.99 | 89.03 | 0.00 | 0.00 | 0.00 |
February | 61.28 | 22.55 | 38.73 | 90.50 | 76.34 | 0.00 | 0.00 | 0.00 |
March | 79.88 | 32.10 | 47.78 | 138.01 | 54.26 | 0.00 | 0.00 | 0.00 |
April | 96.54 | 45.19 | 51.35 | 202.86 | 24.05 | 0.00 | 0.00 | 0.00 |
May | 91.45 | 38.73 | 52.72 | 219.81 | 7.30 | 0.00 | 0.00 | 0.00 |
June | 86.27 | 33.68 | 52.59 | 216.38 | 5.21 | 0.00 | 0.00 | 0.00 |
July | 63.78 | 12.37 | 51.41 | 156.83 | 3.06 | 0.00 | 0.00 | 0.00 |
August | 58.48 | 10.26 | 48.22 | 135.32 | 6.91 | 0.00 | 0.00 | 0.00 |
September | 64.60 | 19.11 | 45.48 | 133.75 | 17.54 | 0.00 | 0.00 | 0.00 |
October | 67.05 | 26.68 | 40.37 | 127.90 | 50.91 | 0.00 | 0.00 | 0.00 |
November | 60.65 | 25.84 | 34.81 | 97.26 | 83.08 | 0.00 | 0.00 | 0.00 |
December | 51.96 | 19.85 | 32.12 | 67.26 | 97.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.62 | 25.57 | 44.05 | 138.20 | 42.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.96 | 10.26 | 32.12 | 67.26 | 3.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.54 | 45.19 | 52.72 | 219.81 | 97.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.65 | 20.86 | 32.79 | 70.99 | 89.03 | 0.00 | 0.00 | 0.00 |
February | 61.28 | 22.55 | 38.73 | 90.50 | 76.34 | 0.00 | 0.00 | 0.00 |
March | 79.88 | 32.10 | 47.78 | 138.01 | 54.26 | 0.00 | 0.00 | 0.00 |
April | 96.54 | 45.19 | 51.35 | 202.86 | 24.05 | 0.00 | 0.00 | 0.00 |
May | 91.45 | 38.73 | 52.72 | 219.81 | 7.30 | 0.00 | 0.00 | 0.00 |
June | 86.27 | 33.68 | 52.59 | 216.38 | 5.21 | 0.00 | 0.00 | 0.00 |
July | 63.78 | 12.37 | 51.41 | 156.83 | 3.06 | 0.00 | 0.00 | 0.00 |
August | 58.48 | 10.26 | 48.22 | 135.32 | 6.91 | 0.00 | 0.00 | 0.00 |
September | 64.60 | 19.11 | 45.48 | 133.75 | 17.54 | 0.00 | 0.00 | 0.00 |
October | 67.05 | 26.68 | 40.37 | 127.90 | 50.91 | 0.00 | 0.00 | 0.00 |
November | 60.65 | 25.84 | 34.81 | 97.26 | 83.08 | 0.00 | 0.00 | 0.00 |
December | 51.96 | 19.85 | 32.12 | 67.26 | 97.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.62 | 25.57 | 44.05 | 138.20 | 42.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.96 | 10.26 | 32.12 | 67.26 | 3.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.54 | 45.19 | 52.72 | 219.81 | 97.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.93 | 0.00 | 14.93 | 11.09 | 53.06 | 0.00 | 0.00 | 0.00 |
February | 17.71 | 0.00 | 17.71 | 18.58 | 45.01 | 0.00 | 0.00 | 0.00 |
March | 21.34 | 0.00 | 21.34 | 32.54 | 31.77 | 0.00 | 0.00 | 0.00 |
April | 23.21 | 0.12 | 23.09 | 54.96 | 13.74 | 0.00 | 0.00 | 0.00 |
May | 25.74 | 0.80 | 24.94 | 75.53 | 4.13 | 0.00 | 0.00 | 0.00 |
June | 26.49 | 0.92 | 25.57 | 80.63 | 3.01 | 0.00 | 0.00 | 0.00 |
July | 26.23 | 0.45 | 25.78 | 70.66 | 1.71 | 0.00 | 0.00 | 0.00 |
August | 24.12 | 0.13 | 23.99 | 59.62 | 3.96 | 0.00 | 0.00 | 0.00 |
September | 21.43 | 0.00 | 21.42 | 46.77 | 10.13 | 0.00 | 0.00 | 0.00 |
October | 18.56 | 0.00 | 18.56 | 34.22 | 29.63 | 0.00 | 0.00 | 0.00 |
November | 15.72 | 0.00 | 15.72 | 18.30 | 48.83 | 0.00 | 0.00 | 0.00 |
December | 14.57 | 0.00 | 14.57 | 10.25 | 58.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.85 | 0.20 | 20.65 | 42.88 | 25.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.57 | 0.00 | 14.57 | 10.25 | 1.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.49 | 0.92 | 25.78 | 80.63 | 58.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.93 | 0.00 | 14.93 | 11.09 | 53.06 | 0.00 | 0.00 | 0.00 |
February | 17.71 | 0.00 | 17.71 | 18.58 | 45.01 | 0.00 | 0.00 | 0.00 |
March | 21.34 | 0.00 | 21.34 | 32.54 | 31.77 | 0.00 | 0.00 | 0.00 |
April | 23.21 | 0.12 | 23.09 | 54.96 | 13.74 | 0.00 | 0.00 | 0.00 |
May | 25.73 | 0.80 | 24.94 | 75.53 | 4.13 | 0.00 | 0.00 | 0.00 |
June | 26.49 | 0.92 | 25.57 | 80.62 | 3.01 | 0.00 | 0.00 | 0.00 |
July | 26.23 | 0.45 | 25.78 | 70.66 | 1.71 | 0.00 | 0.00 | 0.00 |
August | 24.12 | 0.13 | 23.99 | 59.62 | 3.96 | 0.00 | 0.00 | 0.00 |
September | 21.42 | 0.00 | 21.42 | 46.76 | 10.13 | 0.00 | 0.00 | 0.00 |
October | 18.56 | 0.00 | 18.56 | 34.22 | 29.63 | 0.00 | 0.00 | 0.00 |
November | 15.72 | 0.00 | 15.72 | 18.30 | 48.83 | 0.00 | 0.00 | 0.00 |
December | 14.57 | 0.00 | 14.57 | 10.25 | 58.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.85 | 0.20 | 20.65 | 42.88 | 25.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.57 | 0.00 | 14.57 | 10.25 | 1.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.49 | 0.92 | 25.78 | 80.62 | 58.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 96.82 | 46.22 | 75.50 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 125.69 | 41.96 | 12.33 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 176.49 | 34.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 240.39 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 262.05 | 12.03 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 248.03 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 176.11 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 151.33 | 8.05 | 0.00 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 147.35 | 15.51 | 0.00 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 161.77 | 34.36 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 126.42 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 92.55 | 52.17 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 167.17 | 27.44 | 88.00 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 92.55 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 262.05 | 52.17 | 75.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.79 | 43.17 | 37.63 | 98.08 | 46.42 | 113.33 | 0.00 | 0.00 |
February | 101.57 | 56.46 | 45.11 | 128.12 | 40.63 | 2.00 | 0.00 | 0.00 |
March | 136.71 | 81.63 | 55.08 | 175.18 | 37.98 | 0.00 | 0.00 | 0.00 |
April | 175.44 | 122.44 | 52.99 | 231.46 | 31.93 | 0.00 | 0.00 | 0.00 |
May | 186.02 | 128.21 | 57.81 | 246.38 | 24.94 | 0.00 | 0.00 | 0.00 |
June | 174.10 | 110.40 | 63.70 | 230.88 | 23.02 | 5.50 | 0.00 | 0.00 |
July | 122.32 | 43.69 | 78.63 | 163.64 | 15.54 | 3.00 | 0.00 | 0.00 |
August | 105.80 | 30.08 | 75.71 | 142.87 | 15.90 | 20.67 | 0.00 | 0.00 |
September | 108.41 | 45.66 | 62.75 | 140.47 | 23.35 | 28.67 | 0.00 | 0.00 |
October | 121.63 | 77.02 | 44.61 | 156.68 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 101.26 | 66.49 | 34.78 | 123.40 | 55.83 | 0.00 | 0.00 | 0.00 |
December | 78.44 | 42.26 | 36.18 | 91.51 | 56.58 | 20.17 | 0.00 | 0.00 |
Annual Sum or Average | 124.39 | 70.57 | 53.82 | 160.76 | 34.47 | 193.33 | 0.00 | 0.00 |
Minimum of Months | 78.44 | 30.08 | 34.78 | 91.51 | 15.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.02 | 128.21 | 78.63 | 246.38 | 56.58 | 113.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.143684E+09 | 55864696.37 | 87819068.21 | 0.190134E+09 | 0.238455E+09 |
February | 0.148240E+09 | 54543302.02 | 93696263.96 | 0.218942E+09 | 0.184686E+09 |
March | 0.213944E+09 | 85974829.33 | 0.127969E+09 | 0.369656E+09 | 0.145328E+09 |
April | 0.250240E+09 | 0.117133E+09 | 0.133107E+09 | 0.525803E+09 | 62327266.72 |
May | 0.244936E+09 | 0.103731E+09 | 0.141204E+09 | 0.588738E+09 | 19551919.01 |
June | 0.223600E+09 | 87286149.72 | 0.136314E+09 | 0.560860E+09 | 13508357.37 |
July | 0.170822E+09 | 33130241.30 | 0.137691E+09 | 0.420055E+09 | 8202057.75 |
August | 0.156634E+09 | 27491716.71 | 0.129143E+09 | 0.362447E+09 | 18505608.34 |
September | 0.167432E+09 | 49542120.11 | 0.117890E+09 | 0.346683E+09 | 45455101.01 |
October | 0.179588E+09 | 71452901.15 | 0.108135E+09 | 0.342576E+09 | 0.136357E+09 |
November | 0.157202E+09 | 66966142.66 | 90235750.70 | 0.252092E+09 | 0.215339E+09 |
December | 0.139182E+09 | 53154198.35 | 86027774.67 | 0.180148E+09 | 0.261347E+09 |
Annual Sum or Average | 0.219550E+10 | 0.806271E+09 | 0.138923E+10 | 0.435813E+10 | 0.134906E+10 |
Minimum of Months | 0.139182E+09 | 27491716.71 | 86027774.67 | 0.180148E+09 | 8202057.75 |
Maximum of Months | 0.250240E+09 | 0.117133E+09 | 0.141204E+09 | 0.588738E+09 | 0.261347E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.143684E+09 | 55864696.37 | 87819068.21 | 0.190134E+09 | 0.238455E+09 |
February | 0.148240E+09 | 54543302.02 | 93696263.96 | 0.218942E+09 | 0.184686E+09 |
March | 0.213944E+09 | 85974829.33 | 0.127969E+09 | 0.369656E+09 | 0.145328E+09 |
April | 0.250240E+09 | 0.117133E+09 | 0.133107E+09 | 0.525803E+09 | 62327266.72 |
May | 0.244936E+09 | 0.103731E+09 | 0.141204E+09 | 0.588738E+09 | 19551919.01 |
June | 0.223600E+09 | 87286149.72 | 0.136314E+09 | 0.560860E+09 | 13508357.37 |
July | 0.170822E+09 | 33130241.30 | 0.137691E+09 | 0.420055E+09 | 8202057.75 |
August | 0.156634E+09 | 27491716.71 | 0.129143E+09 | 0.362447E+09 | 18505608.34 |
September | 0.167432E+09 | 49542120.11 | 0.117890E+09 | 0.346683E+09 | 45455101.01 |
October | 0.179588E+09 | 71452901.15 | 0.108135E+09 | 0.342576E+09 | 0.136357E+09 |
November | 0.157202E+09 | 66966142.66 | 90235750.70 | 0.252092E+09 | 0.215339E+09 |
December | 0.139182E+09 | 53154198.35 | 86027774.67 | 0.180148E+09 | 0.261347E+09 |
Annual Sum or Average | 0.219550E+10 | 0.806271E+09 | 0.138923E+10 | 0.435813E+10 | 0.134906E+10 |
Minimum of Months | 0.139182E+09 | 27491716.71 | 86027774.67 | 0.180148E+09 | 8202057.75 |
Maximum of Months | 0.250240E+09 | 0.117133E+09 | 0.141204E+09 | 0.588738E+09 | 0.261347E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39997906.46 | 0.00 | 39997906.46 | 29697296.02 | 0.142117E+09 |
February | 42840664.72 | 0.00 | 42840664.72 | 44938545.97 | 0.108885E+09 |
March | 57169009.89 | 5454.26 | 57163555.62 | 87146919.92 | 85101681.22 |
April | 60160653.73 | 299255.54 | 59861398.20 | 0.142457E+09 | 35613746.51 |
May | 68929513.88 | 2132931.50 | 66796582.38 | 0.202298E+09 | 11051557.35 |
June | 68654853.97 | 2382367.95 | 66272486.02 | 0.208981E+09 | 7808867.25 |
July | 70262634.33 | 1208177.70 | 69054456.63 | 0.189264E+09 | 4579813.82 |
August | 64615035.70 | 360314.11 | 64254721.59 | 0.159690E+09 | 10600637.15 |
September | 55534348.53 | 7050.68 | 55527297.85 | 0.121217E+09 | 26268224.22 |
October | 49709036.90 | 0.00 | 49709036.90 | 91654885.24 | 79353724.82 |
November | 40745849.47 | 0.00 | 40745849.47 | 47429667.53 | 0.126572E+09 |
December | 39018672.16 | 0.00 | 39018672.16 | 27454355.41 | 0.156832E+09 |
Annual Sum or Average | 0.657638E+09 | 6395551.75 | 0.651243E+09 | 0.135223E+10 | 0.794786E+09 |
Minimum of Months | 39018672.16 | 0.00 | 39018672.16 | 27454355.41 | 4579813.82 |
Maximum of Months | 70262634.33 | 2382367.95 | 69054456.63 | 0.208981E+09 | 0.156832E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39996682.52 | 0.00 | 39996682.52 | 29696098.17 | 0.142116E+09 |
February | 42839388.01 | 0.00 | 42839388.01 | 44937112.32 | 0.108884E+09 |
March | 57167381.66 | 5454.01 | 57161927.65 | 87144955.04 | 85100532.12 |
April | 60159125.56 | 299241.51 | 59859884.05 | 0.142456E+09 | 35612857.96 |
May | 68927677.98 | 2132831.53 | 66794846.45 | 0.202296E+09 | 11050976.66 |
June | 68652902.57 | 2382256.29 | 66270646.28 | 0.208979E+09 | 7808597.93 |
July | 70260289.98 | 1208121.07 | 69052168.90 | 0.189260E+09 | 4579551.56 |
August | 64612834.96 | 360297.22 | 64252537.74 | 0.159687E+09 | 10600213.17 |
September | 55532566.87 | 7050.35 | 55525516.52 | 0.121214E+09 | 26267482.36 |
October | 49707648.58 | 0.00 | 49707648.58 | 91653333.51 | 79352356.55 |
November | 40744721.82 | 0.00 | 40744721.82 | 47428667.23 | 0.126571E+09 |
December | 39017482.79 | 0.00 | 39017482.79 | 27453230.18 | 0.156831E+09 |
Annual Sum or Average | 0.657619E+09 | 6395251.98 | 0.651223E+09 | 0.135221E+10 | 0.794775E+09 |
Minimum of Months | 39017482.79 | 0.00 | 39017482.79 | 27453230.18 | 4579551.56 |
Maximum of Months | 70260289.98 | 2382256.29 | 69052168.90 | 0.208979E+09 | 0.156831E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.259330E+09 | 0.123785E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.304058E+09 | 0.101509E+09 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.472708E+09 | 93697915.63 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.623102E+09 | 59579628.69 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.701867E+09 | 32216557.85 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.642887E+09 | 20937780.08 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.471684E+09 | 14484438.72 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.405333E+09 | 21557236.90 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.381936E+09 | 40212564.61 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.433274E+09 | 92028389.43 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.327685E+09 | 0.125566E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.247879E+09 | 0.139724E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.527174E+10 | 0.865299E+09 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.247879E+09 | 14484438.72 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.701867E+09 | 0.139724E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216391E+09 | 0.115615E+09 | 0.100777E+09 | 0.262705E+09 | 0.124343E+09 |
February | 0.245715E+09 | 0.136585E+09 | 0.109131E+09 | 0.309938E+09 | 98284826.46 |
March | 0.366163E+09 | 0.218650E+09 | 0.147513E+09 | 0.469193E+09 | 0.101726E+09 |
April | 0.454728E+09 | 0.317371E+09 | 0.137357E+09 | 0.599945E+09 | 82771841.93 |
May | 0.498237E+09 | 0.343389E+09 | 0.154848E+09 | 0.659899E+09 | 66811466.29 |
June | 0.451266E+09 | 0.286148E+09 | 0.165118E+09 | 0.598449E+09 | 59657865.61 |
July | 0.327621E+09 | 0.117015E+09 | 0.210605E+09 | 0.438281E+09 | 41611344.64 |
August | 0.283364E+09 | 80570313.15 | 0.202794E+09 | 0.382663E+09 | 42584489.66 |
September | 0.280992E+09 | 0.118352E+09 | 0.162640E+09 | 0.364097E+09 | 60532363.32 |
October | 0.325781E+09 | 0.206289E+09 | 0.119493E+09 | 0.419650E+09 | 0.112564E+09 |
November | 0.262475E+09 | 0.172331E+09 | 90143970.14 | 0.319856E+09 | 0.144699E+09 |
December | 0.210104E+09 | 0.113193E+09 | 96911217.47 | 0.245091E+09 | 0.151538E+09 |
Annual Sum or Average | 0.392284E+10 | 0.222551E+10 | 0.169733E+10 | 0.506977E+10 | 0.108712E+10 |
Minimum of Months | 0.210104E+09 | 80570313.15 | 90143970.14 | 0.245091E+09 | 41611344.64 |
Maximum of Months | 0.498237E+09 | 0.343389E+09 | 0.210605E+09 | 0.659899E+09 | 0.151538E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 161.89 | 281.92 | 137.16 | 41.71 | 95.44 | 0.00 | 0.00 |
February | 217.08 | 241.63 | 157.97 | 45.09 | 112.88 | 0.00 | 0.00 |
March | 340.61 | 171.57 | 202.44 | 64.20 | 138.24 | 0.00 | 0.00 |
April | 515.55 | 75.49 | 239.51 | 90.61 | 148.89 | 0.00 | 0.00 |
May | 590.58 | 22.75 | 234.37 | 79.05 | 155.32 | 0.00 | 0.00 |
June | 593.99 | 16.43 | 225.50 | 69.19 | 156.32 | 0.00 | 0.00 |
July | 454.97 | 9.53 | 180.02 | 25.64 | 154.38 | 0.00 | 0.00 |
August | 389.85 | 21.70 | 165.21 | 20.80 | 144.41 | 0.00 | 0.00 |
September | 361.03 | 55.34 | 172.04 | 38.23 | 133.81 | 0.00 | 0.00 |
October | 324.19 | 161.02 | 171.22 | 53.35 | 117.86 | 0.00 | 0.00 |
November | 230.19 | 262.89 | 152.74 | 51.67 | 101.07 | 0.00 | 0.00 |
December | 151.71 | 308.95 | 133.06 | 39.69 | 93.37 | 0.00 | 0.00 |
Annual Sum or Average | 361.45 | 135.26 | 180.94 | 51.54 | 129.41 | 0.00 | 0.00 |
Minimum of Months | 151.71 | 9.53 | 133.06 | 20.80 | 93.37 | 0.00 | 0.00 |
Maximum of Months | 593.99 | 308.95 | 239.51 | 90.61 | 156.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1355.52 | 647.02 | 1131.08 | 604.32 | 526.76 | 0.00 | 0.00 |
February | 1759.60 | 587.43 | 1421.96 | 790.42 | 631.54 | 0.00 | 0.00 |
March | 2470.85 | 489.76 | 1913.93 | 1142.88 | 771.05 | 0.00 | 0.00 |
April | 3365.52 | 321.80 | 2456.09 | 1714.20 | 741.90 | 0.00 | 0.00 |
May | 3668.66 | 168.40 | 2604.29 | 1794.90 | 809.39 | 0.00 | 0.00 |
June | 3472.39 | 113.09 | 2437.40 | 1545.55 | 891.84 | 0.00 | 0.00 |
July | 2465.49 | 75.71 | 1712.47 | 611.64 | 1100.83 | 0.00 | 0.00 |
August | 2118.68 | 112.68 | 1481.15 | 421.14 | 1060.00 | 0.00 | 0.00 |
September | 2062.92 | 217.20 | 1517.70 | 639.24 | 878.46 | 0.00 | 0.00 |
October | 2264.72 | 481.03 | 1702.86 | 1078.27 | 624.59 | 0.00 | 0.00 |
November | 1769.90 | 678.21 | 1417.69 | 930.80 | 486.89 | 0.00 | 0.00 |
December | 1295.66 | 730.34 | 1098.22 | 591.66 | 506.56 | 0.00 | 0.00 |
Annual Sum or Average | 2340.32 | 384.14 | 1741.49 | 987.99 | 753.51 | 0.00 | 0.00 |
Minimum of Months | 1295.66 | 75.71 | 1098.22 | 421.14 | 486.89 | 0.00 | 0.00 |
Maximum of Months | 3668.66 | 730.34 | 2604.29 | 1794.90 | 1100.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12915.39 | 4772.23 | 2585.32 | 1381.30 | 1204.02 | 0.00 | 0.00 |
February | 16093.22 | 4082.57 | 3250.20 | 1806.68 | 1443.53 | 0.00 | 0.00 |
March | 24014.92 | 3942.99 | 4374.71 | 2612.31 | 1762.40 | 0.00 | 0.00 |
April | 39316.42 | 4933.47 | 5613.92 | 3918.16 | 1695.76 | 0.00 | 0.00 |
May | 49068.10 | 4442.68 | 5952.65 | 4102.62 | 1850.03 | 0.00 | 0.00 |
June | 44903.58 | 4164.75 | 5571.19 | 3532.69 | 2038.50 | 0.00 | 0.00 |
July | 32178.90 | 2685.26 | 3914.22 | 1398.03 | 2516.19 | 0.00 | 0.00 |
August | 26294.04 | 2719.48 | 3385.47 | 962.61 | 2422.87 | 0.00 | 0.00 |
September | 24860.10 | 4059.32 | 3469.04 | 1461.13 | 2007.91 | 0.00 | 0.00 |
October | 25610.91 | 5688.59 | 3892.25 | 2464.62 | 1427.63 | 0.00 | 0.00 |
November | 16762.10 | 5859.99 | 3240.43 | 2127.54 | 1112.89 | 0.00 | 0.00 |
December | 11594.35 | 5891.77 | 2510.21 | 1352.37 | 1157.84 | 0.00 | 0.00 |
Annual Sum or Average | 27007.81 | 4436.36 | 3980.56 | 2258.25 | 1722.30 | 0.00 | 0.00 |
Minimum of Months | 11594.35 | 2685.26 | 2510.21 | 962.61 | 1112.89 | 0.00 | 0.00 |
Maximum of Months | 49068.10 | 5891.77 | 5952.65 | 4102.62 | 2516.19 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.433599E+09 | 0.755082E+09 | 0.367362E+09 | 0.111729E+09 | 0.255633E+09 | 0.00 | 0.00 |
February | 0.525169E+09 | 0.584551E+09 | 0.382159E+09 | 0.109087E+09 | 0.273073E+09 | 0.00 | 0.00 |
March | 0.912283E+09 | 0.459539E+09 | 0.542225E+09 | 0.171961E+09 | 0.370264E+09 | 0.00 | 0.00 |
April | 0.133631E+10 | 0.195676E+09 | 0.620800E+09 | 0.234864E+09 | 0.385935E+09 | 0.00 | 0.00 |
May | 0.158181E+10 | 60944843.01 | 0.627729E+09 | 0.211729E+09 | 0.416000E+09 | 0.00 | 0.00 |
June | 0.153963E+10 | 42580640.67 | 0.584507E+09 | 0.179337E+09 | 0.405170E+09 | 0.00 | 0.00 |
July | 0.121860E+10 | 25526998.29 | 0.482166E+09 | 68676781.38 | 0.413489E+09 | 0.00 | 0.00 |
August | 0.104418E+10 | 58121477.86 | 0.442496E+09 | 55704044.74 | 0.386792E+09 | 0.00 | 0.00 |
September | 0.935782E+09 | 0.143431E+09 | 0.445930E+09 | 99098341.25 | 0.346832E+09 | 0.00 | 0.00 |
October | 0.868307E+09 | 0.431267E+09 | 0.458593E+09 | 0.142906E+09 | 0.315688E+09 | 0.00 | 0.00 |
November | 0.596645E+09 | 0.681423E+09 | 0.395894E+09 | 0.133932E+09 | 0.261962E+09 | 0.00 | 0.00 |
December | 0.406328E+09 | 0.827481E+09 | 0.356400E+09 | 0.106308E+09 | 0.250092E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113986E+11 | 0.426562E+10 | 0.570626E+10 | 0.162533E+10 | 0.408093E+10 | 0.00 | 0.00 |
Minimum of Months | 0.406328E+09 | 25526998.29 | 0.356400E+09 | 55704044.74 | 0.250092E+09 | 0.00 | 0.00 |
Maximum of Months | 0.158181E+10 | 0.827481E+09 | 0.627729E+09 | 0.234864E+09 | 0.416000E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.363063E+10 | 0.173299E+10 | 0.302948E+10 | 0.161860E+10 | 0.141087E+10 | 0.00 | 0.00 |
February | 0.425681E+10 | 0.142112E+10 | 0.344001E+10 | 0.191219E+10 | 0.152783E+10 | 0.00 | 0.00 |
March | 0.661792E+10 | 0.131177E+10 | 0.512628E+10 | 0.306110E+10 | 0.206518E+10 | 0.00 | 0.00 |
April | 0.872343E+10 | 0.834115E+09 | 0.636619E+10 | 0.444320E+10 | 0.192299E+10 | 0.00 | 0.00 |
May | 0.982613E+10 | 0.451032E+09 | 0.697532E+10 | 0.480745E+10 | 0.216787E+10 | 0.00 | 0.00 |
June | 0.900042E+10 | 0.293129E+09 | 0.631773E+10 | 0.400607E+10 | 0.231166E+10 | 0.00 | 0.00 |
July | 0.660358E+10 | 0.202782E+09 | 0.458669E+10 | 0.163822E+10 | 0.294847E+10 | 0.00 | 0.00 |
August | 0.567467E+10 | 0.301801E+09 | 0.396710E+10 | 0.112798E+10 | 0.283911E+10 | 0.00 | 0.00 |
September | 0.534710E+10 | 0.562976E+09 | 0.393389E+10 | 0.165692E+10 | 0.227697E+10 | 0.00 | 0.00 |
October | 0.606584E+10 | 0.128840E+10 | 0.456094E+10 | 0.288804E+10 | 0.167290E+10 | 0.00 | 0.00 |
November | 0.458759E+10 | 0.175793E+10 | 0.367465E+10 | 0.241263E+10 | 0.126202E+10 | 0.00 | 0.00 |
December | 0.347030E+10 | 0.195614E+10 | 0.294146E+10 | 0.158471E+10 | 0.135676E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.738044E+11 | 0.121142E+11 | 0.549197E+11 | 0.311571E+11 | 0.237626E+11 | 0.00 | 0.00 |
Minimum of Months | 0.347030E+10 | 0.202782E+09 | 0.294146E+10 | 0.112798E+10 | 0.126202E+10 | 0.00 | 0.00 |
Maximum of Months | 0.982613E+10 | 0.195614E+10 | 0.697532E+10 | 0.480745E+10 | 0.294847E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.345926E+11 | 0.127819E+11 | 0.692452E+10 | 0.369967E+10 | 0.322485E+10 | 0.00 | 0.00 |
February | 0.389327E+11 | 0.987656E+10 | 0.786289E+10 | 0.437071E+10 | 0.349218E+10 | 0.00 | 0.00 |
March | 0.643216E+11 | 0.105609E+11 | 0.117172E+11 | 0.699680E+10 | 0.472042E+10 | 0.00 | 0.00 |
April | 0.101908E+12 | 0.127876E+11 | 0.145513E+11 | 0.101559E+11 | 0.439542E+10 | 0.00 | 0.00 |
May | 0.131424E+12 | 0.118993E+11 | 0.159436E+11 | 0.109885E+11 | 0.495513E+10 | 0.00 | 0.00 |
June | 0.116390E+12 | 0.107950E+11 | 0.144405E+11 | 0.915674E+10 | 0.528379E+10 | 0.00 | 0.00 |
July | 0.861880E+11 | 0.719220E+10 | 0.104839E+11 | 0.374449E+10 | 0.673936E+10 | 0.00 | 0.00 |
August | 0.704260E+11 | 0.728387E+10 | 0.906765E+10 | 0.257825E+10 | 0.648940E+10 | 0.00 | 0.00 |
September | 0.644374E+11 | 0.105218E+11 | 0.899174E+10 | 0.378725E+10 | 0.520449E+10 | 0.00 | 0.00 |
October | 0.685963E+11 | 0.152363E+11 | 0.104250E+11 | 0.660123E+10 | 0.382377E+10 | 0.00 | 0.00 |
November | 0.434474E+11 | 0.151891E+11 | 0.839919E+10 | 0.551459E+10 | 0.288461E+10 | 0.00 | 0.00 |
December | 0.310543E+11 | 0.157805E+11 | 0.672334E+10 | 0.362218E+10 | 0.310116E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.851718E+12 | 0.139905E+12 | 0.125531E+12 | 0.712162E+11 | 0.543146E+11 | 0.00 | 0.00 |
Minimum of Months | 0.310543E+11 | 0.719220E+10 | 0.672334E+10 | 0.257825E+10 | 0.288461E+10 | 0.00 | 0.00 |
Maximum of Months | 0.131424E+12 | 0.157805E+11 | 0.159436E+11 | 0.109885E+11 | 0.673936E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.744299E+09 | -679984742.2 | 0.00 | 0.00 | 744.00 | 0.00 | -64314546.8 | 58.99 | 0.00 | 0.00 |
February | 0.666919E+09 | -611538735.2 | 0.00 | 0.00 | 672.00 | 0.00 | -55380757.1 | 58.99 | 0.00 | 0.00 |
March | 0.724940E+09 | -666827924.4 | 0.00 | 0.00 | 744.00 | 0.00 | -58112254.5 | 58.99 | 0.00 | 0.00 |
April | 0.610294E+09 | -556019142.8 | 0.00 | 0.00 | 720.00 | 0.00 | -54274985.0 | 58.99 | 0.00 | 0.00 |
May | 0.566270E+09 | -510907638.5 | 0.00 | 0.00 | 744.00 | 0.00 | -55362716.5 | 59.00 | 0.00 | 0.00 |
June | 0.509965E+09 | -456436630.0 | 0.00 | 0.00 | 720.00 | 0.00 | -53528738.3 | 58.99 | 0.00 | 0.00 |
July | 0.475744E+09 | -420687807.4 | 0.00 | 0.00 | 744.00 | 0.00 | -55056324.0 | 58.98 | 0.00 | 0.00 |
August | 0.523290E+09 | -467772727.5 | 0.00 | 0.00 | 744.00 | 0.00 | -55517766.3 | 58.99 | 0.00 | 0.00 |
September | 0.535262E+09 | -481497530.8 | 0.00 | 0.00 | 720.00 | 0.00 | -53764025.4 | 58.99 | 0.00 | 0.00 |
October | 0.602742E+09 | -546570651.5 | 0.00 | 0.00 | 744.00 | 0.00 | -56171391.8 | 58.99 | 0.00 | 0.00 |
November | 0.643211E+09 | -586882368.1 | 0.00 | 0.00 | 720.00 | 0.00 | -56328902.3 | 58.99 | 0.00 | 0.00 |
December | 0.721733E+09 | -659823146.7 | 0.00 | 0.00 | 744.00 | 0.00 | -61909404.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.732467E+10 | -0.664495E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -679721812.4 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.475744E+09 | -679984742.2 | 0.00 | 0.00 | 672.00 | 0.00 | -64314546.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.744299E+09 | -420687807.4 | 0.00 | 0.00 | 744.00 | 0.00 | -53528738.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.67 | 0.50 | 01-JAN-10:20 | 256.67 | 0.00 | 0.00 | 123.00 | 885.86 | 0.00 | 0.00 | 90.50 |
February | 303.83 | 0.64 | 0.50 | 01-FEB-10:09 | 1607.30 | 0.00 | 0.00 | 145.00 | 892.05 | 0.00 | 0.00 | 113.17 |
March | 364.50 | 0.63 | 0.50 | 01-MAR-10:09 | 427.35 | 0.00 | 0.00 | 201.17 | 287.87 | 0.00 | 0.00 | 165.83 |
April | 379.83 | 0.63 | 0.50 | 01-APR-09:30 | 334.63 | 0.00 | 0.00 | 207.17 | 1666.00 | 0.00 | 0.00 | 171.33 |
May | 406.00 | 0.62 | 0.50 | 01-MAY-09:39 | 2278.18 | 0.00 | 0.00 | 237.67 | 271.99 | 0.00 | 0.00 | 155.67 |
June | 386.67 | 0.61 | 0.50 | 01-JUN-08:00 | 1286.47 | 0.00 | 0.00 | 245.50 | 285.48 | 0.00 | 0.00 | 147.33 |
July | 379.83 | 0.60 | 0.50 | 01-JUL-09:20 | 1155.51 | 0.00 | 0.00 | 260.50 | 355.39 | 0.00 | 0.00 | 188.00 |
August | 372.50 | 0.61 | 0.50 | 01-AUG-08:50 | 748.85 | 0.00 | 0.00 | 245.00 | 527.91 | 0.00 | 0.00 | 191.00 |
September | 344.33 | 0.61 | 0.50 | 01-SEP-08:00 | 420.28 | 0.00 | 0.00 | 213.67 | 329.25 | 0.00 | 0.00 | 165.17 |
October | 347.33 | 0.63 | 0.50 | 01-OCT-09:50 | 309.51 | 0.00 | 0.00 | 176.00 | 492.16 | 0.00 | 0.00 | 142.17 |
November | 317.83 | 0.66 | 0.50 | 01-NOV-10:09 | 250.45 | 0.00 | 0.00 | 116.50 | 1224.54 | 0.00 | 0.00 | 97.83 |
December | 315.50 | 0.67 | 0.50 | 01-DEC-10:30 | 249.12 | 0.00 | 0.00 | 117.00 | 212.17 | 0.00 | 0.00 | 81.33 |
Annual Sum or Average | 4237.50 | 0.63 | 803.26 | 0.00 | 0.00 | 2288.17 | 609.92 | 0.00 | 0.00 | 1709.33 | ||
Minimum of Months | 303.83 | 0.60 | 0.50 | 249.12 | 0.00 | 0.00 | 116.50 | 212.17 | 0.00 | 0.00 | 81.33 | |
Maximum of Months | 406.00 | 0.67 | 0.50 | 2278.18 | 0.00 | 0.00 | 260.50 | 1666.00 | 0.00 | 0.00 | 191.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.59 | 0.50 | 01-JAN-08:50 | 298.13 | 14.26 | 0.00 | 217.83 | 246.70 | 17.95 | 88.33 | 179.00 |
February | 303.83 | 0.57 | 0.50 | 01-FEB-08:39 | 349.63 | 15.13 | 0.00 | 224.50 | 1081.19 | 20.61 | 99.33 | 194.67 |
March | 364.50 | 0.56 | 0.50 | 01-MAR-08:09 | 406.05 | 15.54 | 0.83 | 279.50 | 383.63 | 19.51 | 129.50 | 249.83 |
April | 379.83 | 0.57 | 0.50 | 01-APR-07:30 | 2305.01 | 15.04 | 7.50 | 296.83 | 2631.92 | 19.00 | 123.67 | 259.33 |
May | 406.00 | 0.56 | 0.50 | 01-MAY-07:10 | 410.29 | 15.10 | 17.83 | 323.83 | 346.24 | 18.88 | 123.00 | 288.83 |
June | 386.67 | 0.56 | 0.50 | 01-JUN-07:19 | 448.87 | 15.14 | 28.83 | 317.17 | 379.69 | 18.69 | 113.33 | 285.50 |
July | 379.83 | 0.55 | 0.50 | 01-JUL-06:49 | 531.96 | 16.23 | 26.33 | 314.17 | 466.50 | 19.55 | 118.00 | 293.17 |
August | 372.50 | 0.55 | 0.50 | 01-AUG-07:10 | 757.68 | 16.11 | 23.33 | 299.33 | 679.00 | 19.59 | 126.67 | 279.50 |
September | 344.33 | 0.56 | 0.50 | 01-SEP-07:19 | 590.46 | 15.94 | 16.83 | 274.00 | 453.03 | 20.77 | 133.33 | 255.67 |
October | 347.33 | 0.57 | 0.50 | 01-OCT-07:30 | 356.79 | 14.86 | 0.00 | 263.00 | 656.58 | 18.99 | 111.00 | 231.00 |
November | 317.83 | 0.58 | 0.50 | 01-NOV-07:00 | 293.59 | 14.32 | 0.00 | 224.83 | 1787.18 | 20.05 | 94.67 | 199.83 |
December | 315.50 | 0.59 | 0.50 | 01-DEC-08:39 | 290.69 | 14.40 | 0.00 | 215.33 | 240.23 | 18.11 | 82.67 | 180.50 |
Annual Sum or Average | 4237.50 | 0.57 | 604.52 | 15.20 | 121.50 | 3250.33 | 776.91 | 19.30 | 1343.50 | 2896.83 | ||
Minimum of Months | 303.83 | 0.55 | 0.50 | 290.69 | 14.26 | 0.00 | 215.33 | 240.23 | 17.95 | 82.67 | 179.00 | |
Maximum of Months | 406.00 | 0.59 | 0.50 | 2305.01 | 16.23 | 28.83 | 323.83 | 2631.92 | 20.77 | 133.33 | 293.17 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.83 | 0.65 | 31-JAN-16:10 | 209.13 | 21.98 | 140.50 | 24.17 | 97.02 | 19.62 | 110.50 | 0.00 |
February | 303.83 | 0.81 | 0.63 | 20-FEB-16:30 | 260.73 | 22.67 | 135.50 | 34.67 | 113.52 | 20.48 | 117.50 | 0.00 |
March | 364.50 | 0.79 | 0.61 | 02-MAR-16:10 | 295.29 | 22.56 | 164.67 | 56.00 | 226.36 | 23.10 | 177.50 | 38.17 |
April | 379.83 | 0.79 | 0.61 | 01-APR-15:20 | 215.28 | 19.87 | 127.50 | 41.33 | 186.21 | 21.02 | 155.33 | 48.17 |
May | 406.00 | 0.79 | 0.61 | 01-MAY-15:20 | 215.47 | 19.27 | 113.33 | 37.00 | 177.65 | 20.55 | 150.67 | 43.17 |
June | 386.67 | 0.79 | 0.61 | 01-JUN-15:30 | 224.27 | 19.12 | 107.67 | 39.83 | 174.44 | 20.38 | 147.17 | 32.67 |
July | 379.83 | 0.80 | 0.61 | 01-JUL-15:20 | 215.80 | 19.19 | 99.17 | 27.67 | 138.20 | 20.30 | 136.00 | 11.33 |
August | 372.50 | 0.81 | 0.61 | 04-AUG-15:20 | 203.58 | 19.00 | 93.00 | 23.83 | 126.52 | 19.98 | 131.17 | 6.33 |
September | 344.33 | 0.80 | 0.61 | 01-SEP-15:09 | 242.91 | 20.84 | 126.50 | 45.83 | 164.31 | 21.52 | 147.83 | 17.50 |
October | 347.33 | 0.80 | 0.61 | 01-OCT-15:30 | 226.08 | 22.04 | 148.50 | 41.67 | 150.40 | 22.34 | 148.67 | 20.50 |
November | 317.83 | 0.82 | 0.61 | 01-NOV-16:10 | 250.98 | 22.82 | 138.67 | 28.67 | 112.87 | 21.19 | 115.00 | 2.67 |
December | 315.50 | 0.83 | 0.65 | 02-DEC-15:30 | 279.56 | 23.35 | 144.83 | 42.00 | 96.48 | 19.87 | 107.83 | 0.00 |
Annual Sum or Average | 4237.50 | 0.80 | 235.41 | 20.94 | 1539.83 | 442.67 | 149.39 | 20.87 | 1645.17 | 220.50 | ||
Minimum of Months | 303.83 | 0.79 | 0.61 | 203.58 | 19.00 | 93.00 | 23.83 | 96.48 | 19.62 | 107.83 | 0.00 | |
Maximum of Months | 406.00 | 0.83 | 0.65 | 295.29 | 23.35 | 164.67 | 56.00 | 226.36 | 23.10 | 177.50 | 48.17 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.425911E+09 | 26014.25 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80510053.21 | 15404.99 | 02-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 72847888.55 | 14932.72 | 21-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.425911E+09 | 26014.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 969059.19 | 1722.28 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 969059.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 969059.19 | 1722.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.608745E+09 | 0.543168E+09 | 3587.64 | 14-JAN-15:50 | 2911.88 | 0.00 |
February | 0.00 | 0.00 | 0.204840E+10 | 0.178741E+10 | 24101.51 | 25-FEB-08:62 | 19011.33 | 0.00 |
March | 0.00 | 0.00 | 0.602823E+10 | 0.532131E+10 | 24540.02 | 11-MAR-08:62 | 19080.18 | 0.00 |
April | 0.00 | 0.00 | 0.919498E+10 | 0.836436E+10 | 25230.95 | 19-APR-06:02 | 20271.61 | 0.00 |
May | 0.00 | 0.00 | 0.132315E+11 | 0.109901E+11 | 27009.91 | 24-MAY-06:01 | 17395.41 | 0.00 |
June | 0.00 | 0.00 | 0.150329E+11 | 0.113846E+11 | 27849.48 | 28-JUN-06:01 | 15585.31 | 0.00 |
July | 0.00 | 0.00 | 0.154473E+11 | 0.101653E+11 | 28514.56 | 28-JUL-06:01 | 14600.66 | 0.00 |
August | 0.00 | 0.00 | 0.163636E+11 | 0.103175E+11 | 28738.69 | 22-AUG-06:01 | 14596.35 | 0.00 |
September | 0.00 | 0.00 | 0.132583E+11 | 0.891522E+10 | 28767.87 | 09-SEP-06:01 | 14961.64 | 0.00 |
October | 0.00 | 0.00 | 0.911788E+10 | 0.750513E+10 | 26937.45 | 13-OCT-07:02 | 14986.89 | 0.00 |
November | 0.00 | 0.00 | 0.505455E+10 | 0.450438E+10 | 24086.73 | 18-NOV-08:62 | 18911.47 | 0.00 |
December | 0.00 | 0.00 | 0.167424E+10 | 0.150127E+10 | 5422.34 | 02-DEC-15:00 | 5229.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.107061E+12 | 0.812998E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.608745E+09 | 0.543168E+09 | 3587.64 | 2911.88 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.163636E+11 | 0.113846E+11 | 28767.87 | 20271.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.227547E+09 | 0.195431E+09 | 5187.35 | 22-FEB-14:50 | 4498.49 | 0.00 |
March | 0.00 | 0.00 | 0.769219E+10 | 0.659878E+10 | 61686.73 | 12-MAR-14:23 | 57192.50 | 0.00 |
April | 0.00 | 0.00 | 0.251115E+11 | 0.228199E+11 | 64454.61 | 02-APR-13:03 | 58624.46 | 0.00 |
May | 0.00 | 0.00 | 0.425242E+11 | 0.356973E+11 | 67438.18 | 20-MAY-18:23 | 52846.29 | 0.00 |
June | 0.00 | 0.00 | 0.483215E+11 | 0.369271E+11 | 71789.67 | 26-JUN-17:10 | 47427.32 | 0.00 |
July | 0.00 | 0.00 | 0.480497E+11 | 0.311865E+11 | 73412.99 | 19-JUL-17:10 | 44564.88 | 0.00 |
August | 0.00 | 0.00 | 0.441370E+11 | 0.268910E+11 | 75187.56 | 18-AUG-17:10 | 44319.53 | 0.00 |
September | 0.00 | 0.00 | 0.328297E+11 | 0.213898E+11 | 76359.65 | 09-SEP-06:01 | 38764.08 | 0.00 |
October | 0.00 | 0.00 | 0.188108E+11 | 0.152650E+11 | 63907.25 | 08-OCT-11:53 | 60228.60 | 0.00 |
November | 0.00 | 0.00 | 0.495706E+10 | 0.423867E+10 | 31788.54 | 05-NOV-14:05 | 29760.91 | 0.00 |
December | 0.00 | 0.00 | 30211254.65 | 28390293.59 | 2195.43 | 01-DEC-14:50 | 2060.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.272691E+12 | 0.201238E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.483215E+11 | 0.369271E+11 | 76359.65 | 60228.60 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.486461E+09 | 0.21 | 1198.63 | 02-JAN-07:01 | 0.93 |
February | 0.439018E+09 | 0.21 | 1198.63 | 25-FEB-08:62 | 0.92 |
March | 0.513840E+09 | 0.22 | 1198.63 | 11-MAR-08:62 | 0.92 |
April | 0.516246E+09 | 0.23 | 1198.63 | 01-APR-07:02 | 0.92 |
May | 0.674810E+09 | 0.28 | 1198.63 | 01-MAY-06:01 | 0.92 |
June | 0.745956E+09 | 0.30 | 1198.63 | 01-JUN-06:01 | 0.92 |
July | 0.715592E+09 | 0.28 | 1198.63 | 01-JUL-06:02 | 0.92 |
August | 0.742498E+09 | 0.29 | 1198.63 | 01-AUG-06:01 | 0.91 |
September | 0.605595E+09 | 0.25 | 1198.63 | 01-SEP-06:01 | 0.91 |
October | 0.499419E+09 | 0.22 | 1198.63 | 02-OCT-06:01 | 0.92 |
November | 0.455925E+09 | 0.21 | 1198.63 | 04-NOV-07:02 | 0.92 |
December | 0.476670E+09 | 0.21 | 892.27 | 21-DEC-08:62 | 0.81 |
Annual Sum or Average | 0.687203E+10 | 0.24 | |||
Minimum of Months | 0.439018E+09 | 0.21 | 892.27 | 0.81 | |
Maximum of Months | 0.745956E+09 | 0.30 | 1198.63 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110762E+10 | 0.20 | 1154.93 | 02-JAN-07:10 | 0.55 |
February | 0.101900E+10 | 0.20 | 1118.79 | 21-FEB-13:20 | 0.54 |
March | 0.122744E+10 | 0.23 | 2670.67 | 12-MAR-14:23 | 0.88 |
April | 0.138021E+10 | 0.34 | 2796.98 | 02-APR-13:03 | 0.89 |
May | 0.181134E+10 | 0.44 | 2796.98 | 01-MAY-17:06 | 0.89 |
June | 0.193351E+10 | 0.46 | 2796.98 | 01-JUN-17:08 | 0.89 |
July | 0.182975E+10 | 0.44 | 2796.98 | 01-JUL-17:08 | 0.88 |
August | 0.169851E+10 | 0.42 | 2796.98 | 01-AUG-17:08 | 0.89 |
September | 0.143392E+10 | 0.37 | 2796.98 | 01-SEP-17:08 | 0.89 |
October | 0.125346E+10 | 0.27 | 2796.98 | 01-OCT-10:53 | 0.89 |
November | 0.107943E+10 | 0.21 | 1120.94 | 05-NOV-14:05 | 0.54 |
December | 0.110760E+10 | 0.20 | 1118.79 | 01-DEC-14:00 | 0.54 |
Annual Sum or Average | 0.168818E+11 | 0.31 | |||
Minimum of Months | 0.101900E+10 | 0.20 | 1118.79 | 0.54 | |
Maximum of Months | 0.193351E+10 | 0.46 | 2796.98 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.637741E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.938024E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.199476E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.293212E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.430455E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.477982E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.456866E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.469402E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.379117E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.271738E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.167585E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.886350E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.339205E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.637741E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.477982E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.110762E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.107929E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.326775E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.833353E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.138258E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.152992E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.142402E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.127158E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.968636E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.614935E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.237193E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.111543E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.891923E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.107929E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.152992E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.486461E+09 | 0.608745E+09 | 0.425911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.439018E+09 | 0.204840E+10 | 80510053.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.513840E+09 | 0.602823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.516246E+09 | 0.919498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.674810E+09 | 0.132315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.745956E+09 | 0.150329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.715592E+09 | 0.154473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.742498E+09 | 0.163636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.605595E+09 | 0.132583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.499419E+09 | 0.911788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.455925E+09 | 0.505455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.476670E+09 | 0.167424E+10 | 72847888.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.687203E+10 | 0.107061E+12 | 0.579269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.439018E+09 | 0.608745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.745956E+09 | 0.163636E+11 | 0.425911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.110762E+10 | 0.00 | 969059.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101900E+10 | 0.227547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122744E+10 | 0.769219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138021E+10 | 0.251115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181134E+10 | 0.425242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193351E+10 | 0.483215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182975E+10 | 0.480497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169851E+10 | 0.441370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143392E+10 | 0.328297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125346E+10 | 0.188108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107943E+10 | 0.495706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110760E+10 | 30211254.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168818E+11 | 0.272691E+12 | 969059.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193351E+10 | 0.483215E+11 | 969059.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.486461E+09 | 0.00 | 0.00 | 0.00 | 0.151281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.439018E+09 | 0.00 | 0.00 | 0.00 | 0.499006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.513840E+09 | 0.00 | 0.00 | 0.00 | 0.148092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.516246E+09 | 0.00 | 0.00 | 0.00 | 0.241588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.674810E+09 | 0.00 | 0.00 | 0.00 | 0.362974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.745956E+09 | 0.00 | 0.00 | 0.00 | 0.403387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.715592E+09 | 0.00 | 0.00 | 0.00 | 0.385307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.742498E+09 | 0.00 | 0.00 | 0.00 | 0.395152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.605595E+09 | 0.00 | 0.00 | 0.00 | 0.318558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.499419E+09 | 0.00 | 0.00 | 0.00 | 0.221796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.455925E+09 | 0.00 | 0.00 | 0.00 | 0.121992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.476670E+09 | 0.00 | 0.00 | 0.00 | 0.409680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.687203E+10 | 0.00 | 0.00 | 0.00 | 0.270484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.439018E+09 | 0.00 | 0.00 | 0.00 | 0.151281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.745956E+09 | 0.00 | 0.00 | 0.00 | 0.403387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.110762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101900E+10 | 0.00 | 0.00 | 0.00 | 60298283.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122744E+10 | 0.00 | 0.00 | 0.00 | 0.204031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138021E+10 | 0.00 | 0.00 | 0.00 | 0.695333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181134E+10 | 0.00 | 0.00 | 0.00 | 0.120145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193351E+10 | 0.00 | 0.00 | 0.00 | 0.133657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182975E+10 | 0.00 | 0.00 | 0.00 | 0.124105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169851E+10 | 0.00 | 0.00 | 0.00 | 0.110173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143392E+10 | 0.00 | 0.00 | 0.00 | 0.825244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125346E+10 | 0.00 | 0.00 | 0.00 | 0.489588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107943E+10 | 0.00 | 0.00 | 0.00 | 0.129251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110760E+10 | 0.00 | 0.00 | 0.00 | 7829485.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168818E+11 | 0.00 | 0.00 | 0.00 | 0.723105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193351E+10 | 0.00 | 0.00 | 0.00 | 0.133657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.569715E+09 | 0.00 | 0.00 | 922112.19 | 0.00 | 0.166045E+09 | 0.327739E+09 | 0.00 | 0.14 |
February | 0.269761E+09 | 16733500.23 | 0.00 | 2205506.68 | 589186.45 | 31651405.58 | 0.322641E+09 | 0.00 | 0.14 |
March | 67617065.06 | 0.318103E+09 | 0.00 | 3408792.72 | 3441010.98 | 0.00 | 0.173533E+09 | 0.00 | 0.15 |
April | 4765867.81 | 0.969250E+09 | 0.00 | 808446.83 | 10276624.24 | 0.00 | 7085840.71 | 0.00 | 0.14 |
May | 4386.21 | 0.221503E+10 | 0.00 | 107586.62 | 16715015.76 | 0.00 | 61037.96 | 0.00 | 0.15 |
June | 0.00 | 0.300451E+10 | 0.00 | 45678.44 | 21265910.96 | 0.00 | 82.19 | 0.00 | 0.15 |
July | 0.00 | 0.358034E+10 | 0.00 | 0.00 | 25085893.46 | 0.00 | 0.00 | 0.00 | 0.14 |
August | 0.00 | 0.379629E+10 | 0.00 | 0.00 | 28274941.78 | 0.00 | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.276217E+10 | 0.00 | 8800.27 | 25969497.37 | 0.00 | 0.00 | 0.00 | 0.15 |
October | 15673177.98 | 0.981189E+09 | 0.00 | 1566427.20 | 9553161.40 | 0.00 | 27848247.85 | 0.00 | 0.14 |
November | 0.105171E+09 | 0.166322E+09 | 0.00 | 2734628.17 | 2800452.10 | 0.00 | 0.207552E+09 | 0.00 | 0.14 |
December | 0.395759E+09 | 0.00 | 0.00 | 2574147.93 | 0.00 | 32025647.73 | 0.532999E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.142847E+10 | 0.178099E+11 | 0.00 | 14382127.07 | 0.143972E+09 | 0.229722E+09 | 0.159946E+10 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.569715E+09 | 0.379629E+10 | 0.00 | 3408792.72 | 28274941.78 | 0.166045E+09 | 0.532999E+09 | 0.00 | 0.15 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.355905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
February | 0.290201E+10 | 0.00 | 0.00 | 238700.81 | 0.00 | 0.00 | 0.180214E+09 | 0.00 | 0.20 |
March | 0.114642E+10 | 0.510372E+09 | 0.00 | 4146843.15 | 5665172.00 | 0.00 | 0.101219E+10 | 0.00 | 0.22 |
April | 40265298.13 | 0.335358E+10 | 0.00 | 2118866.37 | 19560269.42 | 0.00 | 0.106947E+09 | 0.00 | 0.24 |
May | 0.00 | 0.996920E+10 | 0.00 | 0.00 | 13518026.33 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.145203E+11 | 0.00 | 0.00 | 10676454.83 | 0.00 | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.174325E+11 | 0.00 | 0.00 | 6626228.66 | 0.00 | 0.00 | 0.00 | 0.27 |
August | 0.00 | 0.171160E+11 | 0.00 | 0.00 | 21136292.25 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.111447E+11 | 0.00 | 0.00 | 45831159.63 | 0.00 | 0.00 | 0.00 | 0.24 |
October | 0.188504E+09 | 0.273017E+10 | 0.00 | 2123523.65 | 21971975.58 | 0.00 | 0.207705E+09 | 0.00 | 0.21 |
November | 0.151486E+10 | 85844101.88 | 0.00 | 4684847.39 | 0.00 | 0.00 | 0.907021E+09 | 0.00 | 0.20 |
December | 0.410668E+10 | 0.00 | 0.00 | 68044.19 | 0.00 | 0.00 | 80014856.77 | 0.00 | 0.19 |
Annual Sum or Average | 0.134578E+11 | 0.768627E+11 | 0.00 | 13380825.55 | 0.144986E+09 | 0.00 | 0.249409E+10 | 0.00 | 0.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Maximum of Months | 0.410668E+10 | 0.174325E+11 | 0.00 | 4684847.39 | 45831159.63 | 0.00 | 0.101219E+10 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:44:04
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.333109E+12 | 0.970939E+10 | 0.00 | 0.150118E+11 | 0.959305E+09 |
February | 0.390064E+12 | 0.104209E+11 | 0.00 | 0.111511E+11 | 0.287445E+10 |
March | 0.563249E+12 | 0.105669E+11 | 0.00 | 0.477097E+10 | 0.172416E+11 |
April | 0.645208E+12 | 0.158374E+11 | 0.00 | -0.727930E+10 | 0.436757E+11 |
May | 0.699537E+12 | 0.295039E+11 | 0.00 | -0.190640E+11 | 0.713999E+11 |
June | 0.649114E+12 | 0.343885E+11 | 0.00 | -0.271925E+11 | 0.807539E+11 |
July | 0.531292E+12 | 0.368120E+11 | 0.00 | -0.340002E+11 | 0.797605E+11 |
August | 0.454913E+12 | 0.346587E+11 | 0.00 | -0.343656E+11 | 0.754694E+11 |
September | 0.476449E+12 | 0.257510E+11 | 0.00 | -0.262610E+11 | 0.575260E+11 |
October | 0.473737E+12 | 0.202257E+11 | 0.00 | -0.615687E+10 | 0.350426E+11 |
November | 0.395675E+12 | 0.111455E+11 | 0.00 | 0.939621E+10 | 0.125240E+11 |
December | 0.308848E+12 | 0.122871E+11 | 0.00 | 0.170744E+11 | 0.215645E+10 |
Annual Sum or Average | 0.592120E+13 | 0.251307E+12 | 0.00 | -0.969150E+11 | 0.479384E+12 |
Minimum of Months | 0.308848E+12 | 0.970939E+10 | 0.00 | -0.343656E+11 | 0.959305E+09 |
Maximum of Months | 0.699537E+12 | 0.368120E+11 | 0.00 | 0.170744E+11 | 0.807539E+11 |