Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2024-07-03 12:21:26
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10403.04 | 916.95 | 916.95 |
Net Site Energy | 10403.04 | 916.95 | 916.95 |
Total Source Energy | 24621.15 | 2170.17 | 2170.17 |
Net Source Energy | 24621.15 | 2170.17 | 2170.17 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 79.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2102.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 545.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 617.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 107.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 159.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.78 | 2207.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6406.27 | 3996.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 79.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 2102.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 545.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 617.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 107.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 159.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.78 | 2207.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 79.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2102.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 545.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 617.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 107.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 159.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.78 | 2207.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 264.53 | 194.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 234.96 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 564.66 | 352.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 264.53 | 194.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 234.96 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 564.66 | 352.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6406.266 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6406.266 | 100.00 |
Total On-Site and Utility Electric Sources | 6406.266 | 100.00 |
Total Electricity End Uses | 6406.266 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 1750.25 | 97.03 |
Air to Air Heat Recovery for Heating | 53.65 | 2.97 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1803.90 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1.67 |
Time Setpoint Not Met During Occupied Cooling | 80.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8176.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.7179 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.2862 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8577 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8577 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.7179 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.2862 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8577 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8577 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.7137 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-SEP-18:40 | 23-JAN-18:30 | - | - | - | - | - | - | - | - | - | - | 08-FEB-21:10 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 189434.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38103.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 74342.86 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 28092.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27529.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4331.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4357.06 | 211731.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1675.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 388470.48 | 315979.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 189434.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 38103.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 44668.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 973.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 26968.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 27529.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4331.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4357.06 | 211731.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 216.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 789.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 669.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 250.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6659.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1727.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.66 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2576.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1954.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 339.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 504.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.17 | 2393.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 140.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 20288.64 | 4332.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 22.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 587.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 152.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 172.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 29.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 44.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 210.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1788.29 | 381.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 22.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 587.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 152.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 172.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 29.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 44.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 210.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1788.29 | 381.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
BASEMENT VAV BOX COMPONENT | 2.44 | 0.617105 | 0.525000 | 1.28 | 1.00 | 0.500000 | 0.000617 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.307723 | 0.166085 | 0.386000 | 0.118781 | 0.460076 | 0.500000 | 0.002294 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.224394 | 0.263749 | 0.613000 | 0.137554 | 0.703330 | 0.500000 | 0.001445 |
MECH_FLR_1 VAV BOX COMPONENT | 0.193381 | 0.647185 | 0.010000 | 0.001934 | 1.00 | 0.500000 | 0.000589 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.106112 | 0.680474 | 0.817000 | 0.086694 | 1.00 | 0.500000 | 0.000560 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.27 | 0.018207 | 0.010000 | 0.032661 | 0.300000 | 0.500000 | 0.020926 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.36 | 0.105852 | 0.746000 | 1.01 | 0.746000 | 0.500000 | 0.003599 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.52 | 0.220347 | 0.628000 | 2.84 | 0.628000 | 0.500000 | 0.001729 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.16 | 1.00 | 0.614000 | 0.712142 | 1.00 | 0.500000 | 0.000372 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.13 | 0.118676 | 0.837000 | 1.78 | 0.837000 | 0.500000 | 0.003210 |
DINING_FLR_6 VAV BOX COMPONENT | 2.23 | 0.113088 | 0.797000 | 1.78 | 0.797000 | 0.500000 | 0.003369 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.15 | 0.065793 | 0.256000 | 0.550899 | 0.300000 | 0.500000 | 0.010416 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.674759 | 0.465409 | 0.279000 | 0.188258 | 1.00 | 0.500000 | 0.000819 |
Design Size Nominal Capacity [W] | |
BASEMENT VAV BOX REHEAT COIL | 36671.00 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3395.52 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 3932.16 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1284.83 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 2478.26 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 1723.55 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 28993.34 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 81215.14 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 3621.78 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 3620.42 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 21150.03 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 21132.22 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 3619.45 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 3618.08 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 20357.56 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1126.96 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1126.87 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 5456.20 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 50952.40 |
DINING_FLR_6 VAV BOX REHEAT COIL | 50915.04 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 15748.22 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 5381.61 |
FLR_3_DOAS HEATING COIL | 9002.65 |
VAV WITH REHEAT HEATING COIL | 90712.02 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.943548 | 0.000307 |
ROOM_2_FLR_3 FAN COIL | 0.918252 | 0.000299 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.36 | 0.001706 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.39 | 0.001840 |
ROOM_5_FLR_3 FAN COIL | 0.851098 | 0.000279 |
ROOM_6_FLR_3 FAN COIL | 0.831043 | 0.000272 |
ROOM_1_FLR_6 FAN COIL | 0.249479 | 0.000081 |
ROOM_2_FLR_6 FAN COIL | 0.242581 | 0.000079 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.12 | 0.000373 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 0.943548 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 0.918252 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 5.36 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 5.39 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 0.851098 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 0.831043 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.249479 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.242581 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.12 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008658 | 12.80 | 0.008500 | 0.000307 | 0.943548 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008662 | 12.80 | 0.008500 | 0.000299 | 0.918252 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008575 | 12.80 | 0.008500 | 0.001706 | 5.36 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008833 | 12.80 | 0.008500 | 0.001840 | 5.39 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008676 | 12.80 | 0.008500 | 0.000279 | 0.851098 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008680 | 12.80 | 0.008500 | 0.000272 | 0.831043 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008649 | 12.80 | 0.008500 | 0.000081 | 0.249479 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008654 | 12.80 | 0.008500 | 0.000079 | 0.242581 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008724 | 12.80 | 0.008500 | 0.000373 | 1.12 | |
FLR_3_DOAS COOLING COIL | 33.90 | 6.70 | 0.016536 | 11.94 | 0.008500 | 0.003036 | 2.05 | 106169.29 |
VAV WITH REHEAT COOLING COIL | 28.46 | 6.70 | 0.012806 | 10.99 | 0.008500 | 0.020506 | 20.67 | 716979.16 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 12.93 | 10.53 | 20.78 | 10.53 | 20.67 | 20.67 | 0.300000 | 0.509474 | 20.67 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 20.67 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 9.33 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003036 | 0.000157 |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.020506 | 0.000023 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 20.67 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.028778 | 4652.12 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1 | 0.028778 | 3.45 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.028778 | 3220.82 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.028778 | 1006244.09 | 1006826.14 | 114.78 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.718 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.098 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.286 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.976 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13293.583 | 6.718 | 124.824 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13293.583 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 406.155 | 4.286 | 199.096 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 406.155 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.173 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.393 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.408 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6855 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5506 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5431 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | 0.12938067E-14 | 0.41601190E-16 | -0.13825196E-09 | -0.61617685E-17 |
29 | 8 | 0.20259350E-07 | 0.15574452E-12 | 0.36060849E-03 | -0.23035579E-09 |
30 | 7 | -0.11728067E-01 | 0.82340017E-08 | -0.22346249E-01 | 0.13335239E-03 |
31 | 6 | 0.39139693 | 0.28900057E-05 | 0.46018966 | -0.45832853E-02 |
32 | 5 | -5.0543823 | 0.10873450E-03 | -4.3497742 | 0.61495273E-01 |
33 | 4 | 32.400414 | 0.89561747E-03 | 21.082566 | -0.41412424 |
34 | 3 | -109.94425 | 0.19639160E-02 | -54.916625 | 1.4966738 |
35 | 2 | 195.86041 | 0.11107406E-02 | 77.226367 | -2.8805378 |
36 | 1 | -170.69506 | 0.11917429E-03 | -55.066722 | 2.7373596 |
37 | 0 | 57.057407 | 0.68218560E-06 | 15.590186 | |
38 | 9 | 0.75525440E-15 | 0.44740194E-16 | -0.12773695E-09 | -0.17413973E-17 |
39 | 8 | 0.18775242E-07 | 0.18212309E-12 | 0.34440251E-03 | -0.21348098E-09 |
40 | 7 | -0.11242372E-01 | 0.98045077E-08 | -0.21646224E-01 | 0.12782986E-03 |
41 | 6 | 0.37819669 | 0.34662877E-05 | 0.44889448 | -0.44276875E-02 |
42 | 5 | -4.9255264 | 0.13123097E-03 | -4.2627871 | 0.59897552E-01 |
43 | 4 | 31.830222 | 0.10869568E-02 | 20.742026 | -0.40655401 |
44 | 3 | -108.73045 | 0.23952585E-02 | -54.243141 | 1.4791387 |
45 | 2 | 194.65663 | 0.13606195E-02 | 76.609648 | -2.8614229 |
46 | 1 | -170.25011 | 0.14657319E-03 | -54.889188 | 2.7295613 |
47 | 0 | 57.057407 | 0.84265852E-06 | 15.620975 | |
48 | 9 | 0.85297796E-15 | 0.46957990E-16 | -0.12703153E-09 | -0.54240268E-18 |
49 | 8 | 0.18675511E-07 | 0.18384479E-12 | 0.34329809E-03 | -0.21234699E-09 |
50 | 7 | -0.11209220E-01 | 0.99091673E-08 | -0.21598424E-01 | 0.12745291E-03 |
51 | 6 | 0.37729561 | 0.35050755E-05 | 0.44812211 | -0.44170661E-02 |
52 | 5 | -4.9167295 | 0.13275736E-03 | -4.2568331 | 0.59788477E-01 |
53 | 4 | 31.791289 | 0.11000280E-02 | 20.718704 | -0.40603713 |
54 | 3 | -108.64755 | 0.24248953E-02 | -54.197012 | 1.4779412 |
55 | 2 | 194.57440 | 0.13778728E-02 | 76.567430 | -2.8601173 |
56 | 1 | -170.21971 | 0.14847322E-03 | -54.877080 | 2.7290284 |
57 | 0 | 57.057407 | 0.85387380E-06 | 15.623112 | |
58 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
59 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
60 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
61 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
62 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
63 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
64 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
65 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
66 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
67 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
68 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
69 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
70 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
71 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
72 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
73 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
74 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
75 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
76 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
77 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.462_SHGC_0.248 | 37 | 1 | VerySmooth | 2.626 | 2.626 | 1.000 | 0.249 | ||
2 | RESWINDOW_U_0.462_SHGC_0.248 | 38 | 1 | VerySmooth | 2.626 | 2.626 | 1.000 | 0.249 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.51275E-002 | 0.15938 | 0.61781 | 0.61781 | 0.27280 | 0.15674 | 0.22697 | 0.00000 | 0.84000 | 0.84000 | 0.11970 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.51275E-002 | 0.15938 | 0.61781 | 0.61781 | 0.27280 | 0.15674 | 0.22697 | 0.00000 | 0.84000 | 0.84000 | 0.11970 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 8.6622E-002 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.3789E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.4836E-002 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.5331E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.8035E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.3716E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.8929E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.5818E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 9.6197E-002 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.2118E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1052 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.4149E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.5079E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.0336E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2502E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3131E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.1925E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.2343E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7048E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.4009E-003 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6177E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.4568E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8489E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0072E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.1925E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.2343E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7048E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.4009E-003 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6177E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.4568E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8489E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0072E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33601.93820 | 33601.93820 | 2.44345 | 2.44345 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 20:30:00 | 29.59450 | 1.65283E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 4.60000 | 5.25715E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4231.18366 | 4231.18366 | 0.30772 | 0.30772 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 1711.42431 | 1711.42431 | 7.34169E-002 | 7.92179E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3085.43694 | 3085.43694 | 0.22439 | 0.22439 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 32.13567 | 1.65331E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 574.61894 | 574.61894 | 2.46502E-002 | 9.17347E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2659.56951 | 2659.56951 | 0.19338 | 0.19338 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:20:00 | 30.52933 | 1.65300E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1047.72011 | 1047.72011 | 4.49455E-002 | 4.49455E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1459.34838 | 1459.34838 | 0.10611 | 0.10611 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 33.58400 | 1.65358E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 678.25984 | 678.25984 | 2.90963E-002 | 5.77652E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44913.69859 | 44913.69859 | 3.26609 | 3.26609 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 33.58400 | 1.65358E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1405.48799 | 1405.48799 | 6.02927E-002 | 6.02927E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18678.61799 | 18678.61799 | 1.35957 | 1.35957 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 4311.77111 | 4311.77111 | 0.18497 | 0.67639 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 62187.60979 | 62187.60979 | 4.52395 | 4.52395 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 33.90000 | 1.65364E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 10047.86267 | 10047.86267 | 0.43104 | 1.89399 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9628.88605 | 9628.88605 | 0.94355 | 0.94355 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 3621.80119 | 3621.80119 | 0.15628 | 0.15628 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9370.73851 | 9370.73851 | 0.91825 | 0.91825 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 3620.43482 | 3620.43482 | 0.15622 | 0.15622 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 54655.94041 | 54655.94041 | 5.35544 | 5.35544 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 33.90000 | 1.65364E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 21150.08351 | 21150.08351 | 0.91263 | 0.91263 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 55039.51636 | 55039.51636 | 5.39345 | 5.39345 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 33.74200 | 1.65361E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 21132.27477 | 21132.27477 | 0.91187 | 0.91187 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8685.42525 | 8685.42525 | 0.85110 | 0.85110 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 31.29300 | 1.65315E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 3619.46742 | 3619.46742 | 0.15618 | 0.15618 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8480.75524 | 8480.75524 | 0.83104 | 0.83104 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 30.89800 | 1.65307E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 3618.10055 | 3618.10055 | 0.15612 | 0.15612 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 15950.13224 | 15950.13224 | 1.15984 | 1.15984 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65362E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 6107.61246 | 6107.61246 | 0.26201 | 0.47476 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2545.92775 | 2545.92775 | 0.24948 | 0.24948 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 32.89933 | 1.65345E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1126.96320 | 1126.96320 | 4.86286E-002 | 4.86286E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2475.53914 | 2475.53914 | 0.24258 | 0.24258 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1126.87938 | 1126.87938 | 4.86250E-002 | 4.86250E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11473.32404 | 11473.32404 | 1.12431 | 1.12431 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 33.90000 | 1.65364E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 5456.22463 | 5456.22463 | 0.23544 | 0.23544 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29248.90317 | 29248.90317 | 2.12951 | 2.12951 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 33.90000 | 1.65364E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 3938.25266 | 3938.25266 | 0.16894 | 1.18780 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30694.81339 | 30694.81339 | 2.23475 | 2.23475 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 33.90000 | 1.65364E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 4029.80008 | 4029.80008 | 0.17287 | 1.18780 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 4.60000 | 5.25715E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29516.14387 | 29516.14387 | 2.15195 | 2.15195 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 33.18900 | 1.65350E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1125.50620 | 1125.50620 | 4.82769E-002 | 0.36735 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 4.60000 | 5.25715E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9279.35016 | 9279.35016 | 0.67476 | 0.67476 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.90000 | 1.65364E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 4209.63833 | 4209.63833 | 0.18059 | 0.18059 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 4.60000 | 5.25715E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 52327.60 | 15.25758 | 2.05125 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 30007.77 | 2.78200 | 2.05125 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 391390.70 | 20.66938 | 20.66938 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 104701.11 | 7.15707 | 7.15707 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.44345 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61711 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28281 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.17399E-004 |
8 | Coil:Heating:Electric | BASEMENT VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 36670.99890 |
9 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.30772 |
10 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16609 |
11 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.38600 |
12 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11878 |
13 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46008 |
14 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29400E-003 |
16 | Coil:Heating:Electric | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3395.52491 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22439 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26375 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.61300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13755 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70333 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44456E-003 |
24 | Coil:Heating:Electric | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3932.15893 |
25 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.19338 |
26 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.64719 |
27 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
28 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93381E-003 |
29 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
30 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.88703E-004 |
32 | Coil:Heating:Electric | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 1284.82945 |
33 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10611 |
34 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.68047 |
35 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.81700 |
36 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.66936E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.59904E-004 |
40 | Coil:Heating:Electric | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2478.25640 |
41 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.26609 |
42 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.82071E-002 |
43 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
44 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.26609E-002 |
45 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09259E-002 |
48 | Coil:Heating:Electric | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 1723.55069 |
49 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.35957 |
50 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10585 |
51 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.74600 |
52 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01424 |
53 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74600 |
54 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.59937E-003 |
56 | Coil:Heating:Electric | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 28993.33687 |
57 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.52395 |
58 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22035 |
59 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.62800 |
60 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84104 |
61 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62800 |
62 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72909E-003 |
64 | Coil:Heating:Electric | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 81215.13928 |
65 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
66 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.94355 |
67 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.94355 |
68 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.07403E-004 |
69 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68307 |
70 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
71 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65806E-003 |
72 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
73 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
74 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.07403E-004 |
75 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.94355 |
76 | Coil:Heating:Electric | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 3621.78179 |
77 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
78 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.91825 |
79 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.91825 |
80 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.99491E-004 |
81 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68306 |
82 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
83 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.66216E-003 |
84 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
85 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
86 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.99491E-004 |
87 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.91825 |
88 | Coil:Heating:Electric | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 3620.41543 |
89 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
90 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.35544 |
91 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 5.35544 |
92 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.70604E-003 |
93 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68373 |
94 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
95 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57509E-003 |
96 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
97 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
98 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.70604E-003 |
99 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.35544 |
100 | Coil:Heating:Electric | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 21150.02872 |
101 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
102 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.39345 |
103 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 5.39345 |
104 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.83980E-003 |
105 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68281 |
106 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
107 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.83339E-003 |
108 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
109 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
110 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.83980E-003 |
111 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.39345 |
112 | Coil:Heating:Electric | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 21132.22001 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.85110 |
115 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.85110 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.78602E-004 |
117 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68304 |
118 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
119 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.67578E-003 |
120 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
121 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
122 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.78602E-004 |
123 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.85110 |
124 | Coil:Heating:Electric | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 3619.44803 |
125 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
126 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.83104 |
127 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.83104 |
128 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.72333E-004 |
129 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68303 |
130 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
131 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.67987E-003 |
132 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
133 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
134 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.72333E-004 |
135 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.83104 |
136 | Coil:Heating:Electric | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 3618.08116 |
137 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15984 |
138 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
139 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.61400 |
140 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71214 |
141 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
142 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
143 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.72312E-004 |
144 | Coil:Heating:Electric | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20357.56191 |
145 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24948 |
147 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.24948 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.10921E-005 |
149 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68308 |
150 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64949E-003 |
152 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.10921E-005 |
155 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24948 |
156 | Coil:Heating:Electric | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 1126.95738 |
157 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
158 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24258 |
159 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.24258 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.89392E-005 |
161 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68308 |
162 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
163 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65369E-003 |
164 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
165 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
166 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.89392E-005 |
167 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24258 |
168 | Coil:Heating:Electric | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 1126.87356 |
169 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
170 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.12431 |
171 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.12431 |
172 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.72810E-004 |
173 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68285 |
174 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
175 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72443E-003 |
176 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
177 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
178 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.72810E-004 |
179 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.12431 |
180 | Coil:Heating:Electric | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 5456.20202 |
181 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.12951 |
182 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11868 |
183 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.83700 |
184 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78240 |
185 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83700 |
186 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21041E-003 |
188 | Coil:Heating:Electric | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 50952.40443 |
189 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23475 |
190 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11309 |
191 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.79700 |
192 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78109 |
193 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79700 |
194 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
195 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36906E-003 |
196 | Coil:Heating:Electric | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 50915.03929 |
197 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15195 |
198 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.57934E-002 |
199 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
200 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55090 |
201 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
202 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04156E-002 |
204 | Coil:Heating:Electric | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15748.21928 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67476 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.46541 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27900 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18826 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.18635E-004 |
212 | Coil:Heating:Electric | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5381.61032 |
213 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
214 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
215 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
216 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
217 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
218 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
219 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
221 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.93493 |
222 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.53051 |
223 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.77549 |
224 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.53051 |
225 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 20.66938 |
226 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.66938 |
227 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50947 |
229 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
230 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.66938 |
231 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
232 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
233 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
234 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 33.90000 |
235 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
236 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.94120 |
237 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.65364E-002 |
238 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
239 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 106169.29401 |
240 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.03643E-003 |
241 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
242 | Coil:Heating:Electric | FLR_3_DOAS HEATING COIL | Design Size Nominal Capacity [W] | 9002.64818 |
243 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
244 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.03643E-003 |
245 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.56826E-004 |
246 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.66938 |
247 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 9.32920 |
248 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.46218 |
249 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.98958 |
251 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.28062E-002 |
252 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
253 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 716979.16051 |
254 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.05055E-002 |
255 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 20.66938 |
256 | Coil:Heating:Electric | VAV WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 90712.02142 |
257 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 20.66938 |
258 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.05055E-002 |
259 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.32226E-005 |
260 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.87785E-002 |
261 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4652.12090 |
262 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.87785E-002 |
263 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.45341 |
264 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.87785E-002 |
265 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3220.82020 |
266 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.87785E-002 |
267 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1006244.09238 |
268 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1006826.14000 |
269 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 114.77818 |
270 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
271 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
272 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
273 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
274 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 15638.59 | 13430.02 | 2208.57 | 0.86 | 2846.08 | 28.87 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 15230.63 | 13074.08 | 2156.54 | 0.86 | 2769.48 | 28.09 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 87407.53 | 75731.28 | 11676.26 | 0.87 | 16179.17 | 164.10 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 92213.11 | 77819.84 | 14393.27 | 0.84 | 16258.00 | 164.90 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 14151.46 | 12130.57 | 2020.89 | 0.86 | 2566.08 | 26.03 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 13828.13 | 11848.42 | 1979.71 | 0.86 | 2505.37 | 25.41 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4128.51 | 3548.64 | 579.87 | 0.86 | 752.69 | 7.63 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4017.42 | 3451.64 | 565.79 | 0.86 | 731.80 | 7.42 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 18860.05 | 16086.64 | 2773.41 | 0.85 | 3390.02 | 34.38 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 67560.94 | 43498.54 | 24062.41 | 0.64 | 9155.92 | 92.86 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 619589.30 | 410912.02 | 208677.28 | 0.66 | 88905.09 | 901.72 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.462_SHGC_0.248 | N/A | 2.626 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6457422377E-002 | 2.0713058925E-002 | Pass | Pass | 8.9199807996E-003 | 1.8367854007E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3702878334E-002 | 2.7283891446E-002 | Pass | Pass | 2.0700738495E-002 | 2.5453768097E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4674001809E-002 | 2.5822368206E-002 | Pass | Pass | 8.9728917114E-003 | 1.8161973790E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6043769601E-005 | 2.0101529689E-005 | Pass | Pass | 2.1322784445E-002 | 4.5386004510E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.1410977575E-002 | 1.0807574603E-002 | Pass | Pass | 9.4276175779E-003 | 2.0708879312E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4333069816E-004 | 3.6749139842E-004 | Pass | Pass | 1.9560274962E-002 | 5.6815839331E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.2465912509E-002 | 6.0832190621E-002 | Pass | Pass | 1.0778456726E-002 | 1.5885429223E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.0012055845E-002 | 3.5479451076E-002 | Pass | Pass | 9.1772760260E-003 | 1.7558268642E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2646792995E-002 | 0.3161963106 | Pass | Pass | 0.3029130850 | 2.7267879363 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.4583508991E-002 | 0.2674149012 | Pass | Pass | 0.1208697523 | 0.4871549447 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.1631940282E-005 | 1.1227935560E-004 | Pass | Pass | 3.5137845990E-002 | 4.4584989790E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.4058064357E-002 | 0.2147593842 | Pass | Pass | 8.6579971486E-002 | 0.2731287162 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2618772260E-002 | 0.3268003150 | Pass | Pass | 9.8930923905E-002 | 0.3202681090 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 0.1114319910 | 0.3281801804 | Pass | Pass | 0.1015254264 | 0.3534836562 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.0362097858E-002 | 8.5714503377E-003 | Pass | Pass | 8.8225084525E-003 | 1.8867746988E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.0278788007E-002 | 0.3088412108 | Pass | Pass | 0.2755689520 | 2.3304146919 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.9497472184E-002 | 0.2575254153 | Pass | Pass | 0.1272910618 | 0.5228835911 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2642536368E-002 | 0.3204846000 | Pass | Pass | 9.9728909489E-002 | 0.3366568598 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.5490216304E-002 | 8.9295557762E-002 | Pass | Pass | 1.0971550437E-002 | 2.1323539965E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.5219033858E-002 | 8.7955306062E-002 | Pass | Pass | 1.0693652650E-002 | 2.0457216229E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.5267172628E-003 | 2.2435817924E-003 | Pass | Pass | 2.0933168096E-002 | 3.9426806334E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.9288282705E-003 | 1.0083239573E-002 | Pass | Pass | 1.5963068231E-002 | 2.0035899543E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3141.94 | -23.6 | -765.4 | -1604.9 | 10572.18 | 11320.21 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.626 | 0.249 | 0.274 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.626 | 0.249 | 0.274 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.626 | 0.249 | 0.274 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.626 | 0.249 | 0.274 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.626 | 0.249 | 0.274 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.626 | 0.249 | 0.274 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.626 | 0.249 | 0.274 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.626 | 0.249 | 0.274 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.626 | 0.249 | 0.274 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.626 | 0.249 | 0.274 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.626 | 0.249 | 0.274 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.626 | 0.249 | 0.274 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.626 | 0.249 | 0.274 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.626 | 0.249 | 0.274 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.626 | 0.249 | 0.274 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.626 | 0.249 | 0.274 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.626 | 0.249 | 0.274 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.626 | 0.249 | 0.274 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.626 | 0.249 | 0.274 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.626 | 0.249 | 0.274 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.626 | 0.249 | 0.274 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.462_SHGC_0.248 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.626 | 0.249 | 0.274 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.626 | 0.249 | 0.274 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.626 | 0.249 | 0.274 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.626 | 0.249 | 0.274 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.626 | 0.249 | 0.274 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.626 | 0.249 | 0.274 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.626 | 0.249 | 0.274 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.626 | 0.249 | 0.274 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.462_SHGC_0.248 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.626 | 0.249 | 0.274 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.626 | 0.249 | 0.274 | |||||||||||||||||
North Total or Average | 432.95 | 2.626 | 0.249 | 0.274 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.626 | 0.249 | 0.274 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.7179 | 1978.83 | 13293.58 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 122.93 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.2862 | 94.76 | 406.16 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 2.31 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.34 | 0.0000 | Y | 12.91 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.51 | 0.0000 | Y | 92.18 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.78 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.79 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 6.96 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.15 | 0.0000 | Y | 28.32 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.15 | 0.0000 | Y | 28.32 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8577 | 11345.29 | 66457.67 | 366.00 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.73 | 83.73 | 193.92 | |
Exterior Lighting Total | 12338.45 | 193.92 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1006826.14 | 2.96 | 1006826.14 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10748.61 | 15638.59 | 13430.02 | 2208.57 | 0.86 | - | 2846.08 | 28.87 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10471.96 | 15230.63 | 13074.08 | 2156.54 | 0.86 | - | 2769.48 | 28.09 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 59653.25 | 87407.53 | 75731.28 | 11676.26 | 0.87 | - | 16179.17 | 164.10 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 64330.07 | 92213.11 | 77819.84 | 14393.27 | 0.84 | - | 16258.00 | 164.90 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9741.55 | 14151.46 | 12130.57 | 2020.89 | 0.86 | - | 2566.08 | 26.03 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9522.36 | 13828.13 | 11848.42 | 1979.71 | 0.86 | - | 2505.37 | 25.41 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2835.45 | 4128.51 | 3548.64 | 579.87 | 0.86 | - | 752.69 | 7.63 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2760.17 | 4017.42 | 3451.64 | 565.79 | 0.86 | - | 731.80 | 7.42 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13035.63 | 18860.05 | 16086.64 | 2773.41 | 0.85 | - | 3390.02 | 34.38 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 106169.29 | 67560.94 | 43498.54 | 24062.41 | 0.64 | - | 9155.92 | 92.86 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 716979.16 | 619589.30 | 410912.02 | 208677.28 | 0.66 | - | 88905.09 | 901.72 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | 36671.00 | 1.00 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3395.52 | 1.00 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3932.16 | 1.00 | |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 1284.83 | 1.00 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2478.26 | 1.00 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 1723.55 | 1.00 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 28993.34 | 1.00 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 81215.14 | 1.00 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 3621.78 | 1.00 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 3620.42 | 1.00 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 21150.03 | 1.00 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 21132.22 | 1.00 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 3619.45 | 1.00 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 3618.08 | 1.00 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20357.56 | 1.00 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 1126.96 | 1.00 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 1126.87 | 1.00 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 5456.20 | 1.00 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 50952.40 | 1.00 | |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 50915.04 | 1.00 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15748.22 | 1.00 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5381.61 | 1.00 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | 9002.65 | 1.00 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | 90712.02 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.94 | 663.91 | 703.64 | 1.00 | 1.21 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.92 | 646.12 | 703.64 | 1.00 | 1.22 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 5.36 | 3768.28 | 703.64 | 1.00 | 0.97 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 5.39 | 3795.02 | 703.64 | 1.00 | 0.97 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.85 | 598.86 | 703.64 | 1.00 | 1.24 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.83 | 584.75 | 703.64 | 1.00 | 1.25 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 175.54 | 703.64 | 1.00 | 1.85 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.24 | 170.69 | 703.64 | 1.00 | 1.88 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.12 | 791.10 | 703.64 | 1.00 | 1.17 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 20.67 | 46312.61 | 2240.64 | 1.00 | 1.11 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.028778 | 4652.12 | 161652.92 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028778 | 3220.82 | 111917.77 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33601.94 | 33601.94 | 16.98 | 2.443 | 2.443 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 20:30:00 | 24.00 | 24.00 | 0.00922 | 29.59 | 0.01653 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4231.18 | 4231.18 | 63.08 | 0.308 | 0.308 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00918 | 33.90 | 0.01654 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3085.44 | 3085.44 | 39.73 | 0.224 | 0.224 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 24.00 | 24.00 | 0.00947 | 32.14 | 0.01653 | 0.092 | 0.00 |
MECH_FLR_1 | 2659.57 | 2659.57 | 16.19 | 0.193 | 0.193 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:20:00 | 24.00 | 24.00 | 0.00888 | 30.53 | 0.01653 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1459.35 | 1459.35 | 15.40 | 0.106 | 0.106 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 24.00 | 24.00 | 0.00897 | 33.58 | 0.01654 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44913.70 | 44913.70 | 575.53 | 3.266 | 3.266 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 24.00 | 24.00 | 0.00855 | 33.58 | 0.01654 | 0.000 | 0.00 |
CAFE_FLR_1 | 18678.62 | 18678.62 | 98.90 | 1.360 | 1.360 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 23.99 | 0.01026 | 33.90 | 0.01654 | 0.676 | 0.00 |
LOBBY_FLR_1 | 62187.61 | 62187.61 | 47.54 | 4.524 | 4.524 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 23.99 | 0.01007 | 33.90 | 0.01654 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9628.89 | 9628.89 | 246.76 | 0.944 | 0.944 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00866 | 32.79 | 0.01653 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9370.74 | 9370.74 | 240.17 | 0.918 | 0.918 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00866 | 32.79 | 0.01653 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 54655.94 | 54655.94 | 2228.69 | 5.355 | 5.355 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 21.11 | 21.11 | 0.00858 | 33.90 | 0.01654 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 55039.52 | 55039.52 | 2243.71 | 5.393 | 5.393 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 21.11 | 21.11 | 0.00883 | 33.74 | 0.01654 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8685.43 | 8685.43 | 222.58 | 0.851 | 0.851 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 21.11 | 21.11 | 0.00868 | 31.29 | 0.01653 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8480.76 | 8480.76 | 217.36 | 0.831 | 0.831 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 21.11 | 21.11 | 0.00868 | 30.90 | 0.01653 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 15950.13 | 15950.13 | 40.96 | 1.160 | 1.160 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00977 | 33.82 | 0.01654 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2545.93 | 2545.93 | 65.24 | 0.249 | 0.249 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 21.11 | 21.11 | 0.00865 | 32.90 | 0.01653 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2475.54 | 2475.54 | 63.45 | 0.243 | 0.243 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00865 | 32.79 | 0.01653 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11473.32 | 11473.32 | 467.72 | 1.124 | 1.124 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 21.11 | 21.11 | 0.00872 | 33.90 | 0.01654 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29248.90 | 29248.90 | 88.19 | 2.130 | 2.130 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 23.98 | 0.01045 | 33.90 | 0.01654 | 1.188 | 0.00 |
DINING_FLR_6 | 30694.81 | 30694.81 | 92.55 | 2.235 | 2.235 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 23.99 | 0.01036 | 33.90 | 0.01654 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29516.14 | 29516.14 | 285.72 | 2.152 | 2.152 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01016 | 33.19 | 0.01654 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9279.35 | 9279.35 | 22.52 | 0.675 | 0.675 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00910 | 33.90 | 0.01654 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 23.61 | 0.00526 | 4.60 | 0.00526 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 1711.42 | 1711.42 | 25.52 | 0.073 | 0.079 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00784 | 4.60 | 0.00526 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 574.62 | 574.62 | 7.40 | 0.025 | 0.092 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00782 | 4.60 | 0.00526 | 0.092 | 0.00 |
MECH_FLR_1 | 1047.72 | 1047.72 | 6.38 | 0.045 | 0.045 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00776 | 4.60 | 0.00526 | 0.000 | 0.00 |
STORAGE_FLR_1 | 678.26 | 678.26 | 7.16 | 0.029 | 0.058 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00779 | 4.60 | 0.00526 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1405.49 | 1405.49 | 18.01 | 0.060 | 0.060 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00776 | 4.60 | 0.00526 | 0.000 | 0.00 |
CAFE_FLR_1 | 4311.77 | 4311.77 | 22.83 | 0.185 | 0.676 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00786 | 4.60 | 0.00526 | 0.676 | 0.00 |
LOBBY_FLR_1 | 10047.86 | 10047.86 | 7.68 | 0.431 | 1.894 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00783 | 4.60 | 0.00526 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 3621.80 | 3621.80 | 92.81 | 0.156 | 0.156 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00782 | 4.60 | 0.00526 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 3620.43 | 3620.43 | 92.79 | 0.156 | 0.156 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00782 | 4.60 | 0.00526 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 21150.08 | 21150.08 | 862.43 | 0.913 | 0.913 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00784 | 4.60 | 0.00526 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 21132.27 | 21132.27 | 861.47 | 0.912 | 0.912 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00784 | 4.60 | 0.00526 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 3619.47 | 3619.47 | 92.75 | 0.156 | 0.156 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00782 | 4.60 | 0.00526 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 3618.10 | 3618.10 | 92.73 | 0.156 | 0.156 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00782 | 4.60 | 0.00526 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 6107.61 | 6107.61 | 15.68 | 0.262 | 0.475 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00787 | 4.60 | 0.00526 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1126.96 | 1126.96 | 28.88 | 0.049 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00786 | 4.60 | 0.00526 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1126.88 | 1126.88 | 28.88 | 0.049 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00786 | 4.60 | 0.00526 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 5456.22 | 5456.22 | 222.43 | 0.235 | 0.235 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00786 | 4.60 | 0.00526 | 0.099 | 0.00 |
BANQUET_FLR_6 | 3938.25 | 3938.25 | 11.87 | 0.169 | 1.188 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00790 | 4.60 | 0.00526 | 1.188 | 0.00 |
DINING_FLR_6 | 4029.80 | 4029.80 | 12.15 | 0.173 | 1.188 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 21.00 | 21.00 | 0.00790 | 4.60 | 0.00526 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1125.51 | 1125.51 | 10.90 | 0.048 | 0.367 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00600 | 4.60 | 0.00526 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 4209.64 | 4209.64 | 10.21 | 0.181 | 0.181 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 21.00 | 21.00 | 0.00792 | 4.60 | 0.00526 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 15.26 | 2.05 | 2.78 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 20.67 | 20.67 | 7.16 | 7.16 | 20.6694 | 10.5305 | 20.6694 | 0.5095 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 36670.999 | 36670.999 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 36671.00 | 24425.89 | 0.854459 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | -999.00 | -999.00 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3395.525 | 3395.525 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3395.52 | 2264.55 | 0.079218 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00783772 | 50.6397 | 1711.42 | 0.00 | -999.00 | -999.00 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 3932.159 | 3932.159 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3932.16 | 2622.36 | 0.091735 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00781505 | 50.4948 | 574.62 | 0.00 | -999.00 | -999.00 |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1284.829 | 1284.829 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1284.83 | 1284.83 | 0.044946 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00776495 | 50.1750 | 1047.72 | 0.00 | -999.00 | -999.00 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 2478.256 | 2478.256 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2478.26 | 1651.30 | 0.057765 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00778856 | 50.3257 | 678.26 | 0.00 | -999.00 | -999.00 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 1723.551 | 1723.551 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1723.55 | 1723.55 | 0.060293 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00776115 | 50.1511 | 1405.49 | 0.00 | -999.00 | -999.00 |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 28993.337 | 28993.337 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 28993.34 | 19335.52 | 0.676389 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00785657 | 50.7599 | 4311.77 | 0.00 | -999.00 | -999.00 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 81215.139 | 81215.139 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 81215.14 | 54142.33 | 1.893991 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00782618 | 50.5658 | 10047.86 | 0.00 | -999.00 | -999.00 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10748.609 | -999.000 | 0.943548 | 0.00030740 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 10748.61 | 10345.39 | 0.943548 | 21.68 | 15.68 | 0.00865806 | 12.80 | 12.09 | 0.00850000 | 32.79 | 0.01653429 | 24.84 | 0.0000 | 21.11 | 0.00865806 | 55.4895 | 9628.89 | 0.00 | 10767.36 | 10767.36 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 3621.782 | 3621.782 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3621.78 | 3485.92 | 0.156281 | 21.68 | 15.68 | 0.00865806 | 12.80 | 12.09 | 0.00850000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.11 | 0.00782395 | 50.2083 | 3621.80 | 0.00 | -999.00 | -999.00 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10471.963 | -999.000 | 0.918252 | 0.00029949 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 10471.96 | 10069.31 | 0.918252 | 21.68 | 15.69 | 0.00866216 | 12.80 | 12.09 | 0.00850000 | 32.79 | 0.01653429 | 24.84 | 0.0000 | 21.11 | 0.00866216 | 55.5155 | 9370.74 | 0.00 | 10490.15 | 10490.15 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 3620.415 | 3620.415 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3620.42 | 3481.21 | 0.156222 | 21.68 | 15.69 | 0.00866216 | 12.80 | 12.09 | 0.00850000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.11 | 0.00782390 | 50.2080 | 3620.43 | 0.00 | -999.00 | -999.00 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 59653.250 | -999.000 | 5.355437 | 0.00170604 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | unknown | 8/21 14:10:00 | 59653.25 | 58568.86 | 5.355437 | 21.68 | 15.61 | 0.00857509 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 0.0000 | 21.11 | 0.00857509 | 54.9631 | 54655.94 | 0.00 | 59755.53 | 59755.53 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 21150.029 | 21150.029 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21150.03 | 20765.56 | 0.912635 | 21.68 | 15.61 | 0.00857509 | 12.80 | 12.09 | 0.00850000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.11 | 0.00783922 | 50.3048 | 21150.08 | 0.00 | -999.00 | -999.00 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 64330.072 | -999.000 | 5.393445 | 0.00183980 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | unknown | 8/21 15:20:00 | 64330.07 | 59443.11 | 5.393445 | 21.68 | 15.84 | 0.00883339 | 12.80 | 12.09 | 0.00850000 | 33.74 | 0.01653608 | 25.09 | 0.0000 | 21.11 | 0.00883339 | 56.5978 | 55039.52 | 0.00 | 64448.88 | 62023.30 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 21132.220 | 21132.220 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21132.22 | 19526.87 | 0.911866 | 21.68 | 15.84 | 0.00883339 | 12.80 | 12.09 | 0.00850000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.11 | 0.00783905 | 50.3037 | 21132.27 | 0.00 | -999.00 | -999.00 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9741.545 | -999.000 | 0.851098 | 0.00027860 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | unknown | 8/21 10:20:00 | 9741.55 | 9336.82 | 0.851098 | 21.68 | 15.70 | 0.00867578 | 12.80 | 12.09 | 0.00850000 | 31.29 | 0.01653147 | 24.45 | 0.0000 | 21.11 | 0.00867578 | 55.6016 | 8685.43 | 0.00 | 9758.24 | 9758.24 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 3619.448 | 3619.448 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3619.45 | 3469.08 | 0.156180 | 21.68 | 15.70 | 0.00867578 | 12.80 | 12.09 | 0.00850000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.11 | 0.00782384 | 50.2076 | 3619.47 | 0.00 | -999.00 | -999.00 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9522.362 | -999.000 | 0.831043 | 0.00027233 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | 8/21 10:00:00 | 9522.36 | 9117.95 | 0.831043 | 21.68 | 15.70 | 0.00867987 | 12.80 | 12.09 | 0.00850000 | 30.90 | 0.01653072 | 24.35 | 0.0000 | 21.11 | 0.00867987 | 55.6274 | 8480.76 | 0.00 | 9538.61 | 9538.61 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 3618.081 | 3618.081 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3618.08 | 3464.42 | 0.156121 | 21.68 | 15.70 | 0.00867987 | 12.80 | 12.09 | 0.00850000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.11 | 0.00782379 | 50.2073 | 3618.10 | 0.00 | -999.00 | -999.00 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 20357.562 | 20357.562 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 20357.56 | 13571.73 | 0.474762 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00787057 | 50.8489 | 6107.61 | 0.00 | -999.00 | -999.00 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2835.455 | -999.000 | 0.249479 | 0.00008109 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | 8/21 16:50:00 | 2835.45 | 2734.65 | 0.249479 | 21.68 | 15.68 | 0.00864949 | 12.80 | 12.09 | 0.00850000 | 32.90 | 0.01653449 | 24.87 | 0.0000 | 21.11 | 0.00864949 | 55.4354 | 2545.93 | 0.00 | 2840.44 | 2840.44 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1126.957 | 1126.957 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1126.96 | 1086.89 | 0.048629 | 21.68 | 15.68 | 0.00864949 | 12.80 | 12.09 | 0.00850000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.11 | 0.00785672 | 50.4159 | 1126.96 | 0.00 | -999.00 | -999.00 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2760.174 | -999.000 | 0.242581 | 0.00007894 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 2760.17 | 2659.39 | 0.242581 | 21.68 | 15.68 | 0.00865369 | 12.80 | 12.09 | 0.00850000 | 32.79 | 0.01653429 | 24.84 | 0.0000 | 21.11 | 0.00865369 | 55.4619 | 2475.54 | 0.00 | 2765.01 | 2765.01 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1126.874 | 1126.874 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1126.87 | 1085.73 | 0.048625 | 21.68 | 15.68 | 0.00865369 | 12.80 | 12.09 | 0.00850000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.11 | 0.00785672 | 50.4159 | 1126.88 | 0.00 | -999.00 | -999.00 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13035.627 | -999.000 | 1.124307 | 0.00037281 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | unknown | 8/21 14:10:00 | 13035.63 | 12352.02 | 1.124307 | 21.68 | 15.74 | 0.00872443 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 0.0000 | 21.11 | 0.00872443 | 55.9096 | 11473.32 | 0.00 | 13059.38 | 13059.38 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 5456.202 | 5456.202 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5456.20 | 5170.07 | 0.235437 | 21.68 | 15.74 | 0.00872443 | 12.80 | 12.09 | 0.00850000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.11 | 0.00786338 | 50.4581 | 5456.22 | 0.00 | -999.00 | -999.00 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 50952.404 | 50952.404 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 50952.40 | 33954.82 | 1.187797 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00789770 | 51.0221 | 3938.25 | 0.00 | -999.00 | -999.00 |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 50915.039 | 50915.039 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 50915.04 | 33954.82 | 1.187797 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00789993 | 51.0365 | 4029.80 | 0.00 | -999.00 | -999.00 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 15748.219 | 15748.219 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 15748.22 | 10501.22 | 0.367350 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00600351 | 38.9082 | 1125.51 | 0.00 | -999.00 | -999.00 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 5381.610 | 5381.610 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 5381.61 | 5162.32 | 0.180587 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00791557 | 51.1362 | 4209.64 | 0.00 | -999.00 | -999.00 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 106169.294 | -999.000 | 2.051317 | 0.00303643 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 106169.29 | 55739.80 | 2.051317 | 33.90 | 25.13 | 0.01653638 | 11.94 | 11.73 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 99.9965 | 21.11 | 0.00870592 | 55.7912 | 155461.24 | 0.00 | 106304.33 | 56559.20 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | FLR_3_DOAS | 9002.648 | 9002.648 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9002.65 | 9002.65 | 0.615395 | 4.60 | 4.60 | 0.00525715 | 16.70 | 13.18 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 333.3216 | 21.11 | 0.00783924 | 50.3049 | 64472.23 | 0.00 | -999.00 | -999.00 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 716979.161 | -999.000 | 20.669377 | 0.02050551 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 716979.16 | 437592.12 | 20.669377 | 28.46 | 21.19 | 0.01280617 | 10.99 | 10.99 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 45.1354 | 23.99 | 0.00974313 | 52.3261 | 284051.14 | 0.00 | 717912.28 | 436611.63 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV WITH REHEAT | 90712.021 | 90712.021 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | 90712.02 | 90712.02 | 6.200813 | 4.60 | 4.60 | 0.00525715 | 16.70 | 13.18 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 150.4512 | 21.66 | 0.00720251 | 44.7426 | 38450.33 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | No | unknown | No | 36670.999 | 36670.999 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 36671.00 | 24425.89 | 1.0000 | 1.02805663 | 0.854459 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36671.00 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 3395.525 | 3395.525 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3395.52 | 2264.55 | 1.0000 | 0.09531238 | 0.079218 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3395.52 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00783772 | 21.00 | 0.00783772 | 50.6397 | 1711.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 3932.159 | 3932.159 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3932.16 | 2622.36 | 1.0000 | 0.11037209 | 0.091735 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3932.16 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00781505 | 21.00 | 0.00781505 | 50.4948 | 574.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 1284.829 | 1284.829 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1284.83 | 1284.83 | 1.0000 | 0.05407695 | 0.044946 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1284.83 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00776495 | 21.00 | 0.00776495 | 50.1750 | 1047.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 2478.256 | 2478.256 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2478.26 | 1651.30 | 1.0000 | 0.06950113 | 0.057765 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2478.26 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00778856 | 21.00 | 0.00778856 | 50.3257 | 678.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 1723.551 | 1723.551 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1723.55 | 1723.55 | 1.0000 | 0.07254221 | 0.060293 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1723.55 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00776115 | 21.00 | 0.00776115 | 50.1511 | 1405.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 28993.337 | 28993.337 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 28993.34 | 19335.52 | 1.0000 | 0.81380931 | 0.676389 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28993.34 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00785657 | 21.00 | 0.00785657 | 50.7599 | 4311.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 81215.139 | 81215.139 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 81215.14 | 54142.33 | 1.0000 | 2.27878673 | 1.893991 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81215.14 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00782618 | 21.00 | 0.00782618 | 50.5658 | 10047.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10748.609 | -999.000 | 0.943548 | 0.00030740 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9349 | 1004.8586 | 1.2032 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.943548 | 1.13524543 | 4197.9300 | 999.8980 | 28.77551796 | 15.03 | 6.70 | 8.33 | 1006244.09 | 1.0682 | 1.068171 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 10748.61 | 10345.39 | 1.0000 | 1.13524543 | 0.943548 | 21.68 | 15.68 | 0.00865806 | 43790.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.30737177 | 6.70 | 15.03 | 8.33 | 0.000 | 10748.61 | 32.79 | 0.01653429 | 24.84 | 0.00000000 | 0.0000 | 21.11 | 0.00865806 | 21.11 | 0.00865806 | 55.4895 | 9628.89 | 0.00 | 10767.36 | 10767.36 | 1.13524543 | 21.68 | 15.69 | 0.00865806 | 43790.3 | 12.39 | 12.09 | 0.00865806 | 34305.7 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 3621.782 | 3621.782 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2032 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.943548 | 1.13524543 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3621.78 | 3485.92 | 1.0000 | 0.18803221 | 0.156281 | 21.68 | 15.68 | 0.00865806 | 43790.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3621.78 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.11 | 0.00782395 | 21.11 | 0.00782395 | 50.2083 | 3621.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10471.963 | -999.000 | 0.918252 | 0.00029949 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9425 | 1004.8586 | 1.2032 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.918252 | 1.10481071 | 4197.9300 | 999.8980 | 28.77551796 | 15.03 | 6.70 | 8.33 | 1006244.09 | 1.0407 | 1.040679 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 10471.96 | 10069.31 | 1.0000 | 1.10481071 | 0.918252 | 21.68 | 15.69 | 0.00866216 | 43800.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.29946068 | 6.70 | 15.03 | 8.33 | 0.000 | 10471.96 | 32.79 | 0.01653429 | 24.84 | 0.00000000 | 0.0000 | 21.11 | 0.00866216 | 21.11 | 0.00866216 | 55.5155 | 9370.74 | 0.00 | 10490.15 | 10490.15 | 1.10481071 | 21.68 | 15.70 | 0.00866216 | 43800.7 | 12.38 | 12.09 | 0.00866216 | 34305.7 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 3620.415 | 3620.415 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2032 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.918252 | 1.10481071 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3620.42 | 3481.21 | 1.0000 | 0.18796128 | 0.156222 | 21.68 | 15.69 | 0.00866216 | 43800.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3620.42 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.11 | 0.00782390 | 21.11 | 0.00782390 | 50.2080 | 3620.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 59653.250 | -999.000 | 5.355437 | 0.00170604 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7807 | 1004.8586 | 1.2032 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.355437 | 6.44348418 | 4197.9300 | 999.8980 | 28.77551796 | 15.03 | 6.70 | 8.33 | 1006244.09 | 5.9283 | 5.928197 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | unknown | unknown | unknown | 8/21 14:10:00 | Sensible | 59653.25 | 58568.86 | 1.0000 | 6.44348418 | 5.355437 | 21.68 | 15.61 | 0.00857509 | 43580.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 1.70586951 | 6.70 | 15.03 | 8.33 | 0.000 | 59653.25 | 33.90 | 0.01653638 | 25.13 | 0.00000000 | 0.0000 | 21.11 | 0.00857509 | 21.11 | 0.00857509 | 54.9631 | 54655.94 | 0.00 | 59755.53 | 59755.53 | 6.44348418 | 21.68 | 15.62 | 0.00857509 | 43580.1 | 12.60 | 12.09 | 0.00857509 | 34306.3 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 21150.029 | 21150.029 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2032 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.355437 | 6.44348418 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 21150.03 | 20765.56 | 1.0000 | 1.09805209 | 0.912635 | 21.68 | 15.61 | 0.00857509 | 43580.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21150.03 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.11 | 0.00783922 | 21.11 | 0.00783922 | 50.3048 | 21150.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 64330.072 | -999.000 | 5.393445 | 0.00183980 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2608 | 1004.8586 | 1.2032 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.393445 | 6.48921494 | 4197.9300 | 999.8980 | 28.77551796 | 15.03 | 6.70 | 8.33 | 1006244.09 | 6.3931 | 6.392969 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | unknown | unknown | unknown | 8/21 15:20:00 | Sensible | 64330.07 | 59443.11 | 1.0000 | 6.48921494 | 5.393445 | 21.68 | 15.84 | 0.00883339 | 44235.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 1.83960987 | 6.70 | 15.03 | 8.33 | 0.000 | 64330.07 | 33.74 | 0.01653608 | 25.09 | 0.00000000 | 0.0000 | 21.11 | 0.00883339 | 21.11 | 0.00883339 | 56.5978 | 55039.52 | 0.00 | 64448.88 | 62023.30 | 6.48921494 | 21.68 | 15.85 | 0.00883339 | 44235.6 | 12.32 | 12.09 | 0.00868529 | 34303.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 21132.220 | 21132.220 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2032 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.393445 | 6.48921494 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 21132.22 | 19526.87 | 1.0000 | 1.09712751 | 0.911866 | 21.68 | 15.84 | 0.00883339 | 44235.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21132.22 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.11 | 0.00783905 | 21.11 | 0.00783905 | 50.3037 | 21132.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9741.545 | -999.000 | 0.851098 | 0.00027860 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9678 | 1004.8586 | 1.2032 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.851098 | 1.02401302 | 4197.9300 | 999.8980 | 28.77551796 | 15.03 | 6.70 | 8.33 | 1006244.09 | 0.9681 | 0.968091 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | unknown | unknown | unknown | 8/21 10:20:00 | Sensible | 9741.55 | 9336.82 | 1.0000 | 1.02401302 | 0.851098 | 21.68 | 15.70 | 0.00867578 | 43835.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.27857333 | 6.70 | 15.03 | 8.33 | 0.000 | 9741.55 | 31.29 | 0.01653147 | 24.45 | 0.00000000 | 0.0000 | 21.11 | 0.00867578 | 21.11 | 0.00867578 | 55.6016 | 8685.43 | 0.00 | 9758.24 | 9758.24 | 1.02401302 | 21.68 | 15.71 | 0.00867578 | 43835.3 | 12.35 | 12.09 | 0.00867578 | 34305.9 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 3619.448 | 3619.448 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2032 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.851098 | 1.02401302 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3619.45 | 3469.08 | 1.0000 | 0.18791105 | 0.156180 | 21.68 | 15.70 | 0.00867578 | 43835.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3619.45 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.11 | 0.00782384 | 21.11 | 0.00782384 | 50.2076 | 3619.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9522.362 | -999.000 | 0.831043 | 0.00027233 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9754 | 1004.8586 | 1.2032 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.831043 | 0.99988313 | 4197.9300 | 999.8980 | 28.77551796 | 15.03 | 6.70 | 8.33 | 1006244.09 | 0.9463 | 0.946310 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | unknown | unknown | 8/21 10:00:00 | Sensible | 9522.36 | 9117.95 | 1.0000 | 0.99988313 | 0.831043 | 21.68 | 15.70 | 0.00867987 | 43845.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.27230548 | 6.70 | 15.03 | 8.33 | 0.000 | 9522.36 | 30.90 | 0.01653072 | 24.35 | 0.00000000 | 0.0000 | 21.11 | 0.00867987 | 21.11 | 0.00867987 | 55.6274 | 8480.76 | 0.00 | 9538.61 | 9538.61 | 0.99988313 | 21.68 | 15.71 | 0.00867987 | 43845.7 | 12.34 | 12.09 | 0.00867987 | 34305.9 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 3618.081 | 3618.081 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2032 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.831043 | 0.99988313 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3618.08 | 3464.42 | 1.0000 | 0.18784009 | 0.156121 | 21.68 | 15.70 | 0.00867987 | 43845.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3618.08 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.11 | 0.00782379 | 21.11 | 0.00782379 | 50.2073 | 3618.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 20357.562 | 20357.562 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 20357.56 | 13571.73 | 1.0000 | 0.57121814 | 0.474762 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20357.56 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00787057 | 21.00 | 0.00787057 | 50.8489 | 6107.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2835.455 | -999.000 | 0.249479 | 0.00008109 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9190 | 1004.8586 | 1.2032 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.249479 | 0.30016462 | 4197.9300 | 999.8980 | 28.77551796 | 15.03 | 6.70 | 8.33 | 1006244.09 | 0.2818 | 0.281781 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | unknown | unknown | 8/21 16:50:00 | Sensible | 2835.45 | 2734.65 | 1.0000 | 0.30016462 | 0.249479 | 21.68 | 15.68 | 0.00864949 | 43768.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.08108386 | 6.70 | 15.03 | 8.33 | 0.000 | 2835.45 | 32.90 | 0.01653449 | 24.87 | 0.00000000 | 0.0000 | 21.11 | 0.00864949 | 21.11 | 0.00864949 | 55.4354 | 2545.93 | 0.00 | 2840.44 | 2840.44 | 0.30016462 | 21.68 | 15.69 | 0.00864949 | 43768.5 | 12.41 | 12.09 | 0.00864949 | 34305.6 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 1126.957 | 1126.957 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2032 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.249479 | 0.30016462 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1126.96 | 1086.89 | 1.0000 | 0.05850830 | 0.048629 | 21.68 | 15.68 | 0.00864949 | 43768.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1126.96 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.11 | 0.00785672 | 21.11 | 0.00785672 | 50.4159 | 1126.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2760.174 | -999.000 | 0.242581 | 0.00007894 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9268 | 1004.8586 | 1.2032 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.242581 | 0.29186593 | 4197.9300 | 999.8980 | 28.77551796 | 15.03 | 6.70 | 8.33 | 1006244.09 | 0.2743 | 0.274300 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 2760.17 | 2659.39 | 1.0000 | 0.29186593 | 0.242581 | 21.68 | 15.68 | 0.00865369 | 43779.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.07893111 | 6.70 | 15.03 | 8.33 | 0.000 | 2760.17 | 32.79 | 0.01653429 | 24.84 | 0.00000000 | 0.0000 | 21.11 | 0.00865369 | 21.11 | 0.00865369 | 55.4619 | 2475.54 | 0.00 | 2765.01 | 2765.01 | 0.29186593 | 21.68 | 15.69 | 0.00865369 | 43779.2 | 12.40 | 12.09 | 0.00865369 | 34305.6 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 1126.874 | 1126.874 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2032 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.242581 | 0.29186593 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1126.87 | 1085.73 | 1.0000 | 0.05850395 | 0.048625 | 21.68 | 15.68 | 0.00865369 | 43779.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1126.87 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.11 | 0.00785672 | 21.11 | 0.00785672 | 50.4159 | 1126.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13035.627 | -999.000 | 1.124307 | 0.00037281 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0583 | 1004.8586 | 1.2032 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.124307 | 1.35272848 | 4197.9300 | 999.8980 | 28.77551796 | 15.03 | 6.70 | 8.33 | 1006244.09 | 1.2955 | 1.295449 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | unknown | unknown | unknown | 8/21 14:10:00 | Sensible | 13035.63 | 12352.02 | 1.0000 | 1.35272848 | 1.124307 | 21.68 | 15.74 | 0.00872443 | 43958.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.37277228 | 6.70 | 15.03 | 8.33 | 0.000 | 13035.63 | 33.90 | 0.01653638 | 25.13 | 0.00000000 | 0.0000 | 21.11 | 0.00872443 | 21.11 | 0.00872443 | 55.9096 | 11473.32 | 0.00 | 13059.38 | 13059.38 | 1.35272848 | 21.68 | 15.75 | 0.00872443 | 43958.7 | 12.23 | 12.09 | 0.00872443 | 34304.6 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 5456.202 | 5456.202 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2032 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.124307 | 1.35272848 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 5456.20 | 5170.07 | 1.0000 | 0.28327036 | 0.235437 | 21.68 | 15.74 | 0.00872443 | 43958.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5456.20 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.11 | 0.00786338 | 21.11 | 0.00786338 | 50.4581 | 5456.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 50952.404 | 50952.404 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 50952.40 | 33954.82 | 1.0000 | 1.42911803 | 1.187797 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50952.40 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00789770 | 21.00 | 0.00789770 | 51.0221 | 3938.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 50915.039 | 50915.039 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 50915.04 | 33954.82 | 1.0000 | 1.42911803 | 1.187797 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50915.04 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00789993 | 21.00 | 0.00789993 | 51.0365 | 4029.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 15748.219 | 15748.219 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 15748.22 | 10501.22 | 1.0000 | 0.44198379 | 0.367350 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15748.22 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.06 | 0.00600351 | 21.00 | 0.00600351 | 38.9082 | 1125.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 5381.610 | 5381.610 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 5381.61 | 5162.32 | 1.0000 | 0.21727607 | 0.180587 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5381.61 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00791557 | 21.00 | 0.00791557 | 51.1362 | 4209.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 106169.294 | -999.000 | 2.051317 | 0.00303643 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1035.5803 | 1004.8586 | 1.2032 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46799022 | 4197.9300 | 999.8980 | 28.77551796 | 15.03 | 6.70 | 8.33 | 1006244.09 | 10.5510 | 10.551048 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 106169.29 | 55739.80 | 1.0000 | 2.46807700 | 2.051317 | 33.90 | 25.13 | 0.01653638 | 76462.7 | 11.94 | 11.73 | 0.00850000 | 33445.7 | 3.03611862 | 6.70 | 15.03 | 8.33 | 2195.006 | 103974.29 | 33.90 | 0.01653638 | 25.13 | 2.05124512 | 99.9965 | 21.11 | 0.00870474 | 21.11 | 0.00870592 | 55.7912 | 155461.24 | 0.00 | 106304.33 | 56559.20 | 2.46807700 | 33.90 | 25.14 | 0.01653638 | 76462.7 | 11.77 | 11.72 | 0.00854715 | 33391.0 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9002.648 | 9002.648 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46799022 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9002.65 | 9002.65 | 1.0000 | 0.74042310 | 0.615395 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 16.70 | 13.18 | 0.00800000 | 37036.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9002.65 | 4.60 | 0.00525715 | 4.60 | 2.05124512 | 333.3216 | 21.11 | 0.00783838 | 21.11 | 0.00783924 | 50.3049 | 64472.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 716979.161 | -999.000 | 20.669377 | 0.02050551 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.6460 | 1004.8586 | 1.2032 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.669377 | 24.86871072 | 4197.9300 | 999.8980 | 28.77551796 | 15.03 | 6.70 | 8.33 | 1006244.09 | 71.2530 | 71.253006 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 716979.16 | 437592.12 | 1.0000 | 24.86871072 | 20.669377 | 28.46 | 21.19 | 0.01280617 | 61305.0 | 10.99 | 10.99 | 0.00850000 | 32474.4 | 20.50342146 | 6.70 | 15.03 | 8.33 | 46312.605 | 670666.56 | 33.90 | 0.01653638 | 25.13 | 9.32920000 | 45.1354 | 23.99 | 0.00973744 | 23.99 | 0.00974313 | 52.3261 | 284051.14 | 0.00 | 717912.28 | 436611.63 | 24.86871072 | 28.46 | 21.20 | 0.01280617 | 61305.0 | 11.39 | 11.33 | 0.00832128 | 32436.9 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 90712.021 | 90712.021 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.669377 | 24.86871072 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | Sensible | 90712.02 | 90712.02 | 1.0000 | 7.46061322 | 6.200813 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 16.70 | 13.18 | 0.00800000 | 37036.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90712.02 | 4.60 | 0.00525715 | 4.60 | 9.32920000 | 150.4512 | 18.43 | 0.00746550 | 21.66 | 0.00720251 | 44.7426 | 38450.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 20.67 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2107.33 | 4614.50 | 0.00 |
RETAIL_1_FLR_1 | 5829.17 | 2369.17 | 100.67 |
RETAIL_2_FLR_1 | 2704.83 | 4703.33 | 0.00 |
MECH_FLR_1 | 5432.00 | 2017.33 | 39.17 |
STORAGE_FLR_1 | 6.67 | 8697.67 | 6.67 |
LAUNDRY_FLR_1 | 8760.00 | 6074.00 | 6074.00 |
CAFE_FLR_1 | 2940.67 | 6420.33 | 1710.33 |
LOBBY_FLR_1 | 3393.00 | 6190.50 | 2068.33 |
ROOM_1_FLR_3 | 82.50 | 7821.17 | 79.00 |
ROOM_2_FLR_3 | 571.83 | 7780.67 | 476.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 310.17 | 8755.00 | 309.00 |
ROOM_5_FLR_3 | 70.33 | 7684.17 | 69.17 |
ROOM_6_FLR_3 | 512.50 | 7687.67 | 439.50 |
CORRIDOR_FLR_3 | 745.83 | 8062.50 | 740.83 |
ROOM_1_FLR_6 | 329.83 | 7551.50 | 256.00 |
ROOM_2_FLR_6 | 995.50 | 7514.50 | 845.00 |
ROOM_3_MULT9_FLR_6 | 156.00 | 7726.50 | 70.00 |
BANQUET_FLR_6 | 3523.50 | 5501.33 | 1667.33 |
DINING_FLR_6 | 4741.17 | 4156.50 | 1595.83 |
KITCHEN_FLR_6 | 8759.00 | 6769.67 | 6769.67 |
CORRIDOR_FLR_6 | 5705.83 | 2760.17 | 237.83 |
Facility | 8760.00 | 8760.00 | 8176.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 8.67 | 0.00 | 8.67 |
ROOM_2_FLR_3 | 0.67 | 11.00 | 0.67 | 11.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 51.50 | 0.00 | 51.50 |
ROOM_5_FLR_3 | 0.00 | 1.33 | 0.00 | 1.33 |
ROOM_6_FLR_3 | 0.17 | 19.33 | 0.17 | 19.33 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.67 | 16.67 | 0.67 | 16.67 |
ROOM_2_FLR_6 | 1.67 | 17.17 | 1.67 | 17.17 |
ROOM_3_MULT9_FLR_6 | 0.00 | 22.00 | 0.00 | 22.00 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.17 | 0.00 | 0.17 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1.67 | 80.00 | 1.67 | 80.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.718 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.371 | 0.060 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.169 | 0.020 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.217 | 0.022 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.597 | 0.022 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 14.689 | 0.064 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 3.515 | 0.047 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.437 | 0.019 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.341 | 0.077 | 0.000 | 0.057 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.077 | 0.000 | 0.062 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.388 | 0.034 | 0.000 | 0.096 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.341 | 0.077 | 0.000 | 0.057 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.077 | 0.000 | 0.061 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.389 | 0.009 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.341 | 0.077 | 0.000 | 0.066 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.342 | 0.077 | 0.000 | 0.070 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.388 | 0.063 | 0.000 | 0.105 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.592 | 0.022 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.611 | 0.022 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 15.016 | 0.064 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.530 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.528 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.932 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.903 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.006 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.438 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 6.287 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.612 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.142 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.285 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.579 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.601 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 5.077 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.313 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 29775271.79 | 0.00 | 29775271.79 | 0.00 | 29775271.79 | 26946214.98 | 5030.79 | 232.57 | 3496.63 | 0.00 |
RETAIL_1_FLR_1 | 3127422.21 | 0.00 | 3127422.21 | 136304.61 | 3263726.82 | 2498216.28 | 2777.90 | 205.60 | 5776.51 | 0.00 |
RETAIL_2_FLR_1 | 3091916.46 | 0.00 | 3091916.46 | 52613.75 | 3144530.22 | 2892943.94 | 5963.67 | 93.46 | 2702.86 | 0.00 |
MECH_FLR_1 | 1205232.53 | 0.00 | 1205232.53 | 124347.66 | 1329580.19 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1935607.57 | 0.00 | 1935607.57 | 71741.75 | 2007349.32 | 1821682.01 | 6133.44 | 42.29 | 2584.27 | 0.00 |
LAUNDRY_FLR_1 | 38958474.41 | 0.00 | 38958474.41 | 169790.37 | 39128264.78 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 22646546.56 | 0.00 | 22646546.56 | 301309.07 | 22947855.63 | 21330615.53 | 6135.66 | 40.96 | 2583.38 | 0.00 |
LOBBY_FLR_1 | 63954588.64 | 0.00 | 63954588.64 | 860908.82 | 64815497.46 | 59728886.00 | 5867.67 | 191.46 | 2700.87 | 0.00 |
ROOM_1_FLR_3 | 1406076.84 | 58933.07 | 1465009.90 | 79114.93 | 1544124.83 | 1946875.62 | 2433.33 | 5507.00 | 819.67 | 0.00 |
ROOM_2_FLR_3 | 1405912.09 | 63166.83 | 1469078.92 | 79108.89 | 1548187.82 | 1946647.51 | 2433.33 | 5511.12 | 815.54 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 168.58 | 1100080.55 | 22073.95 | 1122154.50 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 366.83 |
ROOM_4_MULT19_FLR_3 | 19070354.14 | 61554.41 | 19131908.54 | 22079.99 | 19153988.53 | 26405105.73 | 2433.33 | 5594.16 | 732.51 | 0.00 |
ROOM_5_FLR_3 | 1406076.84 | 59008.48 | 1465085.32 | 79114.93 | 1544200.25 | 1946875.62 | 2433.33 | 5507.00 | 819.67 | 0.00 |
ROOM_6_FLR_3 | 1405912.09 | 62495.26 | 1468407.35 | 79108.89 | 1547516.25 | 1946647.51 | 2433.33 | 5507.19 | 819.47 | 0.00 |
CORRIDOR_FLR_3 | 15899989.59 | 0.00 | 15899989.59 | 95665.87 | 15995655.45 | 14972100.18 | 6134.81 | 41.47 | 2583.72 | 0.00 |
ROOM_1_FLR_6 | 351519.21 | 67868.98 | 419388.19 | 79130.90 | 498519.08 | 486718.90 | 2245.49 | 5510.51 | 1004.00 | 0.00 |
ROOM_2_FLR_6 | 351478.02 | 71854.03 | 423332.06 | 79124.86 | 502456.91 | 486661.88 | 2236.01 | 5520.61 | 1003.38 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2258331.41 | 68065.92 | 2326397.33 | 40486.14 | 2366883.47 | 3126920.42 | 2433.33 | 5504.50 | 822.17 | 0.00 |
BANQUET_FLR_6 | 39920986.24 | 0.00 | 39920986.24 | 193217.76 | 40114203.99 | 37458366.31 | 6108.27 | 66.62 | 2585.11 | 0.00 |
DINING_FLR_6 | 40050526.88 | 0.00 | 40050526.88 | 193217.76 | 40243744.64 | 37458366.31 | 5935.00 | 98.64 | 2726.35 | 0.00 |
KITCHEN_FLR_6 | 40478425.01 | 0.00 | 40478425.01 | 172974.69 | 40651399.70 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 5705973.85 | 0.00 | 5705973.85 | 169297.98 | 5875271.82 | 3961413.96 | 1206.83 | 85.82 | 7467.36 | 0.00 |
Total Facility | 0.19E+10 | 6417677.91 | 0.19E+10 | 7972508.85 | 0.19E+10 | 0.43E+10 | 8760.00 | 6074.60 | 8760.00 | 366.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9442 | 0.0000 | 0.9442 | 0.0000 | 0.9442 | 0.8545 | 5030.79 | 232.57 | 3496.63 |
RETAIL_1_FLR_1 | 0.0992 | 0.0000 | 0.0992 | 0.0043 | 0.1035 | 0.0792 | 2777.90 | 205.60 | 5776.51 |
RETAIL_2_FLR_1 | 0.0980 | 0.0000 | 0.0980 | 0.0017 | 0.0997 | 0.0917 | 5963.67 | 93.46 | 2702.86 |
MECH_FLR_1 | 0.0382 | 0.0000 | 0.0382 | 0.0039 | 0.0422 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0614 | 0.0000 | 0.0614 | 0.0023 | 0.0637 | 0.0578 | 6133.44 | 42.29 | 2584.27 |
LAUNDRY_FLR_1 | 1.2354 | 0.0000 | 1.2354 | 0.0054 | 1.2407 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7181 | 0.0000 | 0.7181 | 0.0096 | 0.7277 | 0.6764 | 6135.66 | 40.96 | 2583.38 |
LOBBY_FLR_1 | 2.0280 | 0.0000 | 2.0280 | 0.0273 | 2.0553 | 1.8940 | 5867.67 | 191.46 | 2700.87 |
ROOM_1_FLR_3 | 0.0446 | 0.0019 | 0.0465 | 0.0025 | 0.0490 | 0.0617 | 2433.33 | 5507.00 | 819.67 |
ROOM_2_FLR_3 | 0.0446 | 0.0020 | 0.0466 | 0.0025 | 0.0491 | 0.0617 | 2433.33 | 5511.12 | 815.54 |
ROOM_4_MULT19_FLR_3 | 0.6047 | 0.0020 | 0.6067 | 0.0007 | 0.6074 | 0.8373 | 2433.33 | 5594.16 | 732.51 |
ROOM_5_FLR_3 | 0.0446 | 0.0019 | 0.0465 | 0.0025 | 0.0490 | 0.0617 | 2433.33 | 5507.00 | 819.67 |
ROOM_6_FLR_3 | 0.0446 | 0.0020 | 0.0466 | 0.0025 | 0.0491 | 0.0617 | 2433.33 | 5507.19 | 819.47 |
CORRIDOR_FLR_3 | 0.5042 | 0.0000 | 0.5042 | 0.0030 | 0.5072 | 0.4748 | 6134.81 | 41.47 | 2583.72 |
ROOM_1_FLR_6 | 0.0111 | 0.0022 | 0.0133 | 0.0025 | 0.0158 | 0.0154 | 2245.49 | 5510.51 | 1004.00 |
ROOM_2_FLR_6 | 0.0111 | 0.0023 | 0.0134 | 0.0025 | 0.0159 | 0.0154 | 2236.01 | 5520.61 | 1003.38 |
ROOM_3_MULT9_FLR_6 | 0.0716 | 0.0022 | 0.0738 | 0.0013 | 0.0751 | 0.0992 | 2433.33 | 5504.50 | 822.17 |
BANQUET_FLR_6 | 1.2659 | 0.0000 | 1.2659 | 0.0061 | 1.2720 | 1.1878 | 6108.27 | 66.62 | 2585.11 |
DINING_FLR_6 | 1.2700 | 0.0000 | 1.2700 | 0.0061 | 1.2761 | 1.1878 | 5935.00 | 98.64 | 2726.35 |
KITCHEN_FLR_6 | 1.2836 | 0.0000 | 1.2836 | 0.0055 | 1.2890 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.1809 | 0.0000 | 0.1809 | 0.0054 | 0.1863 | 0.1256 | 1206.83 | 85.82 | 7467.36 |
Total Facility | 58.5782 | 0.2031 | 58.7813 | 0.1996 | 58.9809 | 73.9670 | 8760.00 | 6074.60 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 41626871.17 | 513115.56 | 42139986.73 | 64690340.46 | 8756.50 | 1.83 | 1.67 | 0.00 |
VAV WITH REHEAT | 0.44E+09 | 0.00 | 0.44E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.3200 | 0.0163 | 1.3363 | 2.0513 | 8756.50 | 1.83 | 1.67 |
VAV WITH REHEAT | 14.0810 | 0.0000 | 14.0810 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6691.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 160.65 | 3245.74 | 0.00 | 0.00 | 0.00 | 5353.61 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.7281 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 13.3372 | 17.3004 | 0.0000 | 0.0000 | 0.0000 | 12.1569 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1276 |
Defaulted Fields | 1144 |
Fields with Defaults | 3765 |
Autosized Fields | 294 |
Autosizable Fields | 344 |
Autocalculated Fields | 279 |
Autocalculatable Fields | 538 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6406.27 | 73210.95 | 15-MAR-03:00 | 388470.48 | 09-SEP-18:40 |
Electricity:Building | 2201.08 | 29107.25 | 02-JAN-02:10 | 132137.22 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 266.04 | 3144.96 | 02-JAN-02:10 | 19685.67 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2193.99 | 28966.11 | 02-JAN-02:10 | 131895.89 | 02-JAN-20:10 |
InteriorLights:Electricity | 545.53 | 5072.43 | 02-JAN-02:10 | 45764.37 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 122.93 | 1117.06 | 02-JAN-02:10 | 10053.14 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 545.53 | 5072.43 | 02-JAN-02:10 | 45764.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 545.53 | 5072.43 | 02-JAN-02:10 | 45764.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 122.93 | 1117.06 | 02-JAN-02:10 | 10053.14 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 545.53 | 5072.43 | 02-JAN-02:10 | 45764.37 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.91 | 71.95 | 02-JAN-02:10 | 430.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.31 | 20.97 | 02-JAN-02:10 | 188.71 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.31 | 20.97 | 02-JAN-02:10 | 188.71 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.25 | 378.04 | 02-JAN-02:10 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.91 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.91 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 241.18 | 2998.53 | 02-JAN-02:10 | 18013.24 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 92.18 | 887.12 | 02-JAN-02:10 | 7984.04 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 92.18 | 887.12 | 02-JAN-02:10 | 7984.04 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 253.77 | 3619.58 | 02-JAN-10:10 | 20179.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 253.84 | 3620.57 | 02-JAN-10:10 | 20185.51 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 3.85 | 55.20 | 01-JAN-02:10 | 290.10 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 3.85 | 55.19 | 01-JAN-02:10 | 290.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.06 | 428.75 | 02-JAN-10:10 | 2390.39 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 204.18 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.32 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.32 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 204.18 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.32 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.32 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.42 | 732.86 | 04-FEB-23:30 | 2791.32 | 24-DEC-11:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 2342.12 | 2247.94 | 09-MAR-02:50 | 206807.70 | 09-SEP-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 15.89 | 0.00 | 01-JAN-11:10 | 1310.18 | 10-SEP-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 21.44 | 637.77 | 04-FEB-23:50 | 716.80 | 15-FEB-14:10 |
Fans:Electricity | 617.14 | 12575.30 | 06-DEC-04:00 | 38051.64 | 06-OCT-21:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 877.15 | 13513.82 | 04-MAR-04:00 | 133520.81 | 21-DEC-07:20 |
ExteriorEquipment:Electricity | 813.52 | 9997.87 | 02-JAN-02:20 | 49590.83 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.52 | 379.07 | 02-JAN-02:20 | 1274.03 | 02-JAN-07:20 |
ElectricityPurchased:Facility | 6406.27 | 73210.95 | 15-MAR-03:00 | 388470.48 | 09-SEP-18:40 |
ElectricityPurchased:Plant | 6406.27 | 73210.95 | 15-MAR-03:00 | 388470.48 | 09-SEP-18:40 |
Cogeneration:ElectricityPurchased | 6406.27 | 73210.95 | 15-MAR-03:00 | 388470.48 | 09-SEP-18:40 |
General:Cogeneration:ElectricityPurchased | 6406.27 | 73210.95 | 15-MAR-03:00 | 388470.48 | 09-SEP-18:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6406.27 | 73210.95 | 15-MAR-03:00 | 388470.48 | 09-SEP-18:40 |
ElectricityNet:Plant | 6406.27 | 73210.95 | 15-MAR-03:00 | 388470.48 | 09-SEP-18:40 |
Cogeneration:ElectricityNet | 6406.27 | 73210.95 | 15-MAR-03:00 | 388470.48 | 09-SEP-18:40 |
General:Cogeneration:ElectricityNet | 6406.27 | 73210.95 | 15-MAR-03:00 | 388470.48 | 09-SEP-18:40 |
Heating:Electricity | 79.23 | 0.00 | 01-JAN-00:10 | 111895.67 | 21-DEC-07:20 |
General:Heating:Electricity | 79.23 | 0.00 | 01-JAN-00:10 | 111895.67 | 21-DEC-07:20 |
General:Fans:Electricity | 617.14 | 12575.30 | 06-DEC-04:00 | 38051.64 | 06-OCT-21:20 |
ExteriorLights:Electricity | 193.92 | 0.00 | 01-JAN-07:30 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.92 | 0.00 | 01-JAN-07:30 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 159.26 | 0.00 | 01-JAN-00:10 | 8265.52 | 01-JAN-13:10 |
General:HeatRecovery:Electricity | 159.26 | 0.00 | 01-JAN-00:10 | 8265.52 | 01-JAN-13:10 |
WaterSystems:Electricity | 94.78 | 1222.48 | 10-NOV-03:10 | 4751.13 | 02-JAN-19:50 |
Water Heater:WaterSystems:Electricity | 94.78 | 1222.48 | 10-NOV-03:10 | 4751.13 | 02-JAN-19:50 |
Cooling:Electricity | 2102.90 | 0.00 | 04-JAN-01:10 | 196711.45 | 10-SEP-15:20 |
General:Cooling:Electricity | 2102.90 | 0.00 | 04-JAN-01:10 | 196711.45 | 10-SEP-15:20 |
Pumps:Electricity | 107.12 | 47.91 | 13-JAN-23:40 | 4500.86 | 09-AUG-18:10 |
General:Pumps:Electricity | 107.12 | 47.91 | 13-JAN-23:40 | 4500.86 | 09-AUG-18:10 |
WIRED_LTG_ELECTRICITY | 19.20 | 0.00 | 01-JAN-00:10 | 1610.91 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3996.78 | 21474.20 | 21-JUL-01:20 | 315979.62 | 23-JAN-18:30 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2207.94 | 8112.31 | 21-JUL-01:20 | 214776.90 | 18-JAN-21:50 |
WaterSystems:NaturalGas | 2207.94 | 8112.31 | 21-JUL-01:20 | 214776.90 | 18-JAN-21:50 |
Water Heater:WaterSystems:NaturalGas | 2207.94 | 8112.31 | 21-JUL-01:20 | 214776.90 | 18-JAN-21:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 8220.90 | 0.00 | 04-JAN-01:10 | 610466.59 | 09-AUG-18:20 |
PlantLoopCoolingDemand:HVAC | 8220.90 | 0.00 | 04-JAN-01:10 | 610466.59 | 09-AUG-18:20 |
CoolingCoils:PlantLoopCoolingDemand | 8220.90 | 0.00 | 04-JAN-01:10 | 610466.59 | 09-AUG-18:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-FEB-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-FEB-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-FEB-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-FEB-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-FEB-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-FEB-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 35378.93 | 121889.99 | 21-MAR-13:50 | 2561337.14 | 09-SEP-18:10 |
EnergyTransfer:Building | 5861.56 | 95806.61 | 11-MAR-15:00 | 331261.40 | 28-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 727.79 | 9236.57 | 05-FEB-04:00 | 35130.03 | 10-SEP-10:50 |
Refrigeration:EnergyTransfer | 188.69 | 4017.37 | 04-FEB-23:30 | 10377.77 | 01-SEP-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 94.35 | 2008.69 | 04-FEB-23:30 | 5188.88 | 01-SEP-06:20 |
General:Refrigeration:EnergyTransfer | 94.35 | 2008.69 | 04-FEB-23:30 | 5188.88 | 01-SEP-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 94.35 | 2008.69 | 04-FEB-23:30 | 5188.88 | 01-SEP-06:20 |
EnergyTransfer:Plant | 19413.34 | 10977.69 | 16-NOV-03:40 | 1431912.22 | 09-SEP-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.74 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 72.61 | 2008.63 | 04-FEB-23:50 | 2560.29 | 15-FEB-14:10 |
EnergyTransfer:Zone:BASEMENT | 424.12 | 8675.33 | 18-APR-13:20 | 21621.00 | 27-OCT-21:00 |
Heating:EnergyTransfer | 9.75 | 0.00 | 01-JAN-00:10 | 22166.76 | 05-FEB-07:00 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 9.75 | 0.00 | 01-JAN-00:10 | 22166.76 | 05-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5757.46 | 91621.39 | 05-FEB-06:00 | 327650.99 | 28-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 424.12 | 8675.33 | 18-APR-13:20 | 21621.00 | 27-OCT-21:00 |
General:Cooling:EnergyTransfer | 5757.46 | 91621.39 | 05-FEB-06:00 | 327650.99 | 28-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 424.12 | 8675.33 | 18-APR-13:20 | 21621.00 | 27-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.38 | 2.56 | 12-MAR-03:50 | 3946.19 | 16-DEC-13:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 368.27 | 05-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 368.27 | 05-FEB-07:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.37 | 0.00 | 21-JAN-07:10 | 3946.19 | 16-DEC-13:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.37 | 0.00 | 21-JAN-07:10 | 3946.19 | 16-DEC-13:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 42.63 | 699.80 | 11-MAR-17:00 | 2064.53 | 30-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 42.63 | 699.80 | 11-MAR-17:00 | 2064.53 | 30-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 42.63 | 699.80 | 11-MAR-17:00 | 2064.53 | 30-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 20.54 | 15.56 | 21-DEC-06:10 | 1944.65 | 19-JUL-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 20.54 | 15.56 | 21-DEC-06:10 | 1944.65 | 19-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 20.54 | 15.56 | 21-DEC-06:10 | 1944.65 | 19-JUL-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 23.28 | 119.54 | 21-DEC-10:20 | 1089.68 | 10-SEP-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 23.28 | 119.54 | 21-DEC-10:20 | 1089.68 | 10-SEP-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 23.28 | 119.54 | 21-DEC-10:20 | 1089.68 | 10-SEP-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.09 | 8400.97 | 06-FEB-05:00 | 39476.19 | 07-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.09 | 8400.97 | 06-FEB-05:00 | 39476.19 | 07-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.09 | 8400.97 | 06-FEB-05:00 | 39476.19 | 07-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 285.51 | 2645.06 | 11-MAR-13:50 | 13085.53 | 10-DEC-11:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 285.51 | 2645.06 | 11-MAR-13:50 | 13085.53 | 10-DEC-11:40 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 285.51 | 2645.06 | 11-MAR-13:50 | 13085.53 | 10-DEC-11:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 889.06 | 17356.11 | 11-MAR-17:00 | 39782.68 | 05-OCT-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 889.06 | 17356.11 | 11-MAR-17:00 | 39782.68 | 05-OCT-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 889.06 | 17356.11 | 11-MAR-17:00 | 39782.68 | 05-OCT-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 79.05 | 0.00 | 01-JAN-08:00 | 10605.71 | 10-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.95 | 0.00 | 01-JAN-00:10 | 2632.18 | 05-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.95 | 0.00 | 01-JAN-00:10 | 2632.18 | 05-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 78.10 | 0.00 | 01-JAN-08:00 | 10605.71 | 10-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 78.10 | 0.00 | 01-JAN-08:00 | 10605.71 | 10-SEP-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 66.00 | 0.00 | 01-JAN-08:00 | 9869.06 | 10-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 1.68 | 0.00 | 01-JAN-00:10 | 3410.12 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 1.68 | 0.00 | 01-JAN-00:10 | 3410.12 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 64.32 | 0.00 | 01-JAN-08:00 | 9869.06 | 10-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 64.32 | 0.00 | 01-JAN-08:00 | 9869.06 | 10-SEP-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 423.39 | 0.00 | 03-JAN-01:30 | 46183.85 | 10-DEC-13:40 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 423.39 | 0.00 | 03-JAN-01:30 | 46183.85 | 10-DEC-13:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 423.39 | 0.00 | 03-JAN-01:30 | 46183.85 | 10-DEC-13:40 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 548.58 | 0.00 | 01-JAN-08:00 | 66994.36 | 28-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 2.14 | 0.00 | 01-JAN-00:10 | 10217.32 | 04-FEB-21:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 2.14 | 0.00 | 01-JAN-00:10 | 10217.32 | 04-FEB-21:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 546.44 | 0.00 | 01-JAN-08:00 | 66994.36 | 28-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 546.44 | 0.00 | 01-JAN-08:00 | 66994.36 | 28-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 79.63 | 0.00 | 01-JAN-08:00 | 9104.66 | 29-MAY-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.99 | 0.00 | 01-JAN-00:10 | 2702.87 | 05-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.99 | 0.00 | 01-JAN-00:10 | 2702.87 | 05-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 78.64 | 0.00 | 01-JAN-08:00 | 9104.66 | 29-MAY-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 78.64 | 0.00 | 01-JAN-08:00 | 9104.66 | 29-MAY-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 67.05 | 0.00 | 01-JAN-08:00 | 9624.09 | 29-MAY-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 1.76 | 0.00 | 01-JAN-00:10 | 2966.04 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 1.76 | 0.00 | 01-JAN-00:10 | 2966.04 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 65.29 | 0.00 | 01-JAN-08:00 | 9624.09 | 29-MAY-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 65.29 | 0.00 | 01-JAN-08:00 | 9624.09 | 29-MAY-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 209.01 | 2204.60 | 06-FEB-07:10 | 9331.70 | 10-SEP-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 209.01 | 2204.60 | 06-FEB-07:10 | 9331.70 | 10-SEP-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 209.01 | 2204.60 | 06-FEB-07:10 | 9331.70 | 10-SEP-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 20.39 | 0.00 | 01-JAN-08:00 | 2924.58 | 10-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.57 | 0.00 | 01-JAN-00:10 | 991.68 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.57 | 0.00 | 01-JAN-00:10 | 991.68 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.81 | 0.00 | 01-JAN-08:00 | 2924.58 | 10-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.81 | 0.00 | 01-JAN-08:00 | 2924.58 | 10-SEP-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.43 | 0.00 | 01-JAN-08:00 | 2719.52 | 10-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.91 | 0.00 | 01-JAN-00:10 | 1117.98 | 05-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.91 | 0.00 | 01-JAN-00:10 | 1117.98 | 05-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.52 | 0.00 | 01-JAN-08:00 | 2719.52 | 10-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.52 | 0.00 | 01-JAN-08:00 | 2719.52 | 10-SEP-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 123.40 | 0.00 | 01-JAN-08:00 | 13838.12 | 02-NOV-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.74 | 0.00 | 01-JAN-00:10 | 3457.27 | 11-MAR-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.74 | 0.00 | 01-JAN-00:10 | 3457.27 | 11-MAR-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 122.66 | 0.00 | 01-JAN-08:00 | 13838.12 | 02-NOV-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 122.66 | 0.00 | 01-JAN-08:00 | 13838.12 | 02-NOV-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 525.85 | 10096.45 | 21-DEC-10:10 | 22101.84 | 07-JUL-22:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 525.85 | 10096.45 | 21-DEC-10:10 | 22101.84 | 07-JUL-22:00 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 525.85 | 10096.45 | 21-DEC-10:10 | 22101.84 | 07-JUL-22:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 545.74 | 11743.04 | 21-DEC-10:20 | 23487.40 | 07-JUL-22:00 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 545.74 | 11743.04 | 21-DEC-10:20 | 23487.40 | 07-JUL-22:00 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 545.74 | 11743.04 | 21-DEC-10:20 | 23487.40 | 07-JUL-22:00 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 633.44 | 6942.95 | 05-FEB-04:00 | 30057.39 | 10-SEP-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 633.44 | 6942.95 | 05-FEB-04:00 | 30057.39 | 10-SEP-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 89.63 | 150.04 | 21-DEC-07:10 | 6431.82 | 10-SEP-13:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 89.63 | 150.04 | 21-DEC-07:10 | 6431.82 | 10-SEP-13:50 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 89.63 | 150.04 | 21-DEC-07:10 | 6431.82 | 10-SEP-13:50 |
PlantLoopHeatingDemand:Facility | 598.80 | 7055.05 | 24-JUL-00:10 | 45068.30 | 23-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 598.80 | 7055.05 | 24-JUL-00:10 | 45068.30 | 23-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 598.80 | 7055.05 | 24-JUL-00:10 | 45068.30 | 23-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 598.80 | 7055.05 | 24-JUL-00:10 | 45068.30 | 23-JAN-07:10 |
EnergyTransfer:HVAC | 10104.03 | 89.18 | 28-JAN-08:00 | 818552.55 | 09-SEP-21:00 |
HeatingCoils:EnergyTransfer | 79.23 | 0.00 | 01-JAN-00:10 | 111895.67 | 21-DEC-07:20 |
CoolingCoils:EnergyTransfer | 8220.90 | 0.00 | 04-JAN-01:10 | 610466.59 | 09-AUG-18:20 |
HeatRecoveryForHeating:EnergyTransfer | 53.65 | 0.00 | 01-JAN-00:10 | 203934.44 | 05-FEB-07:20 |
HeatRecoveryForCooling:EnergyTransfer | 1750.25 | 0.00 | 01-JAN-00:10 | 236617.61 | 09-SEP-23:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 598.80 | 7055.05 | 24-JUL-00:10 | 45068.30 | 23-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 598.80 | 7055.05 | 24-JUL-00:10 | 45068.30 | 23-JAN-07:10 |
Chillers:EnergyTransfer | 8308.65 | 0.00 | 04-JAN-01:10 | 613164.34 | 09-AUG-18:10 |
HeatRejection:EnergyTransfer | 10411.55 | 0.00 | 04-JAN-01:10 | 802410.49 | 10-SEP-15:30 |
General:HeatRejection:EnergyTransfer | 10411.55 | 0.00 | 04-JAN-01:10 | 802410.49 | 10-SEP-15:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -424.125 | 0.000 | 0.000 | 139.267 | 122.932 | 143.105 | 0.000 | 0.000 | 0.000 | 18.820 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.006 | -46.373 | 0.000 | 0.000 | 14.113 | 6.265 | 10.186 | 21.176 | 0.000 | 0.283 | 0.001 | 0.000 | -4.954 | 0.000 | -0.577 | -0.124 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -42.630 | 0.000 | 0.000 | 16.565 | 7.255 | 11.795 | 0.000 | 0.000 | 0.131 | 7.101 | 0.000 | 0.000 | 0.000 | -0.216 | 0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -20.542 | 0.000 | 0.000 | 3.349 | 8.366 | 12.471 | 0.000 | 0.000 | 0.254 | 0.000 | 0.000 | 0.000 | 0.000 | -0.591 | -3.308 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -23.283 | 0.000 | 0.000 | 2.853 | 2.308 | 3.598 | 0.000 | 0.000 | 0.208 | 14.567 | 0.000 | 0.000 | 0.000 | -0.249 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -607.097 | 0.000 | 0.000 | 10.551 | 4.900 | 658.131 | 0.000 | 0.000 | 0.347 | 0.000 | 0.000 | 0.000 | 0.000 | -0.827 | -66.006 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -285.515 | 0.000 | 0.000 | 194.757 | 12.911 | 14.341 | 62.078 | 0.000 | 0.896 | 14.560 | 0.000 | -12.873 | 0.000 | -1.154 | -0.000 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -889.070 | 0.000 | 0.000 | 553.798 | 92.177 | 148.998 | 80.968 | 0.000 | 2.184 | 32.854 | 0.000 | -18.257 | 0.000 | -3.652 | -0.000 |
ROOM_1_FLR_3 | 1.762 | -65.813 | 0.000 | -13.102 | 0.000 | 0.000 | 9.623 | 4.922 | 10.478 | 46.471 | 0.000 | 1.225 | 15.164 | 0.000 | -9.002 | 0.000 | -1.728 | -0.002 |
ROOM_2_FLR_3 | 2.830 | -51.887 | 0.000 | -13.588 | 0.000 | 0.000 | 9.511 | 4.922 | 10.477 | 36.671 | 0.000 | 1.080 | 11.601 | 0.000 | -9.506 | 0.000 | -2.111 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.000 | -405.424 | 0.000 | -17.957 | 0.000 | 0.000 | 0.000 | 58.777 | 194.997 | 230.962 | 0.000 | 1.437 | 40.564 | 0.000 | -91.559 | 0.000 | -11.796 | -0.003 |
ROOM_4_MULT19_FLR_3 | 7.658 | -369.592 | 0.000 | -182.327 | 0.000 | 0.000 | 181.507 | 58.793 | 195.050 | 127.610 | 0.000 | 6.542 | 47.079 | 0.000 | -50.891 | 0.000 | -21.428 | -0.007 |
ROOM_5_FLR_3 | 1.827 | -66.364 | 0.000 | -13.107 | 0.000 | 0.000 | 9.617 | 4.922 | 10.478 | 47.035 | 0.000 | 1.224 | 14.864 | 0.000 | -8.753 | 0.000 | -1.743 | -0.000 |
ROOM_6_FLR_3 | 2.920 | -52.885 | 0.000 | -13.558 | 0.000 | 0.000 | 9.522 | 4.922 | 10.477 | 37.026 | 0.000 | 1.080 | 11.530 | 0.000 | -9.003 | 0.000 | -2.030 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -209.013 | 0.000 | 0.000 | 113.886 | 56.739 | 0.000 | 43.881 | 0.000 | 0.966 | 7.178 | 0.000 | -12.194 | 0.000 | -1.443 | -0.000 |
ROOM_1_FLR_6 | 0.874 | -16.835 | 0.000 | -3.276 | 0.000 | 0.000 | 2.407 | 1.231 | 2.620 | 11.530 | 0.000 | 0.308 | 3.808 | 0.000 | -2.215 | 0.000 | -0.451 | -0.000 |
ROOM_2_FLR_6 | 1.288 | -13.510 | 0.000 | -3.394 | 0.000 | 0.000 | 2.380 | 1.230 | 2.619 | 9.102 | 0.000 | 0.269 | 2.907 | 0.000 | -2.340 | 0.000 | -0.553 | -0.000 |
ROOM_3_MULT9_FLR_6 | 1.484 | -102.318 | 0.000 | -21.076 | 0.000 | 0.000 | 21.629 | 6.962 | 23.098 | 58.919 | 0.000 | 1.603 | 22.932 | 0.000 | -10.310 | 0.000 | -2.923 | -0.000 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -525.850 | 0.000 | 0.000 | 334.334 | 28.324 | 175.857 | 13.367 | 0.000 | 0.529 | 0.001 | 0.000 | -7.249 | 0.000 | -0.787 | -18.526 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -545.749 | 0.000 | 0.000 | 329.634 | 28.324 | 175.857 | 12.919 | 0.000 | 0.499 | 7.022 | 0.000 | -7.689 | 0.000 | -0.816 | -0.001 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -633.434 | 0.000 | 0.000 | 27.946 | 13.339 | 540.650 | 22.394 | 0.000 | 0.344 | 35.719 | 0.000 | -6.106 | 0.000 | -0.853 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -89.635 | 0.000 | 0.000 | 28.607 | 15.012 | 0.000 | 19.678 | 0.000 | 0.337 | 33.052 | 0.000 | -6.304 | 0.000 | -0.749 | 0.000 |
Total Facility | 20.643 | -1144.628 | 0.006 | -4623.700 | 0.000 | 0.000 | 2015.856 | 545.533 | 2355.282 | 881.787 | 0.000 | 21.745 | 341.324 | 0.000 | -269.206 | 0.000 | -56.676 | -87.979 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 27-OCT-21:00 | 0.00 | 0.00 | 0.00 | -21621.48 | 0.00 | 0.00 | 5924.42 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2364.58 |
RETAIL_1_FLR_1 | 16-DEC-13:30 | 0.00 | 0.00 | 0.00 | -3945.97 | 0.00 | 0.00 | 225.91 | 142.31 | 252.59 | 4654.43 | 0.00 | 18.35 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1347.61 |
RETAIL_2_FLR_1 | 30-AUG-21:00 | 0.00 | 0.00 | 0.00 | -2064.64 | 0.00 | 0.00 | 697.61 | 527.34 | 752.15 | 0.00 | 0.00 | 10.66 | 76.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 19-JUL-20:00 | 0.00 | 0.00 | 0.00 | -1944.68 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 23.37 | 268.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 10-SEP-10:35 | 0.00 | 0.00 | 0.00 | -1092.30 | 0.00 | 0.00 | 45.16 | 62.90 | 101.96 | 0.00 | 0.00 | 30.05 | 852.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 07-JUL-20:00 | 0.00 | 0.00 | 0.00 | -39475.20 | 0.00 | 0.00 | 408.87 | 400.68 | 44299.38 | 0.00 | 0.00 | 35.12 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5668.84 |
CAFE_FLR_1 | 10-DEC-11:35 | 0.00 | 0.00 | 0.00 | -13162.40 | 0.00 | 0.00 | 2968.66 | 115.39 | 406.43 | 13708.44 | 0.00 | 32.41 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4068.93 |
LOBBY_FLR_1 | 05-OCT-21:10 | 0.00 | 0.00 | 0.00 | -39789.87 | 0.00 | 0.00 | 26439.89 | 5322.69 | 7389.94 | 264.39 | 0.00 | 104.99 | 267.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 10-APR-15:11 | 0.00 | -11963.93 | 0.00 | -692.38 | 0.00 | 0.00 | 235.28 | 106.08 | 200.18 | 6478.99 | 0.00 | 0.00 | 5915.71 | 0.00 | -0.00 | 0.00 | -279.94 | 0.00 |
ROOM_2_FLR_3 | 10-APR-19:11 | 0.00 | -11960.60 | 0.00 | -561.49 | 0.00 | 0.00 | 328.60 | 378.82 | 653.15 | 0.00 | 0.00 | 0.00 | 12621.18 | 0.00 | -1345.55 | 0.00 | -114.12 | 0.00 |
ROOM_3_MULT19_FLR_3 | 10-DEC-13:40 | 0.00 | -46185.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1492.91 | 2548.95 | 54344.74 | 0.00 | 18.52 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12219.24 |
ROOM_4_MULT19_FLR_3 | 10-APR-19:11 | 0.00 | -70252.41 | 0.00 | -7196.63 | 0.00 | 0.00 | 6548.10 | 4525.19 | 12159.85 | 0.00 | 0.00 | 0.00 | 61247.38 | 0.00 | -6453.49 | 0.00 | -578.00 | 0.00 |
ROOM_5_FLR_3 | 10-APR-15:11 | 0.00 | -10772.53 | 0.00 | -689.69 | 0.00 | 0.00 | 235.28 | 106.08 | 200.18 | 1276.24 | 0.00 | 0.00 | 9920.71 | 0.00 | -0.00 | 0.00 | -276.28 | 0.00 |
ROOM_6_FLR_3 | 01-OCT-08:51 | 0.00 | -10585.47 | 0.00 | -903.48 | 0.00 | 0.00 | 114.25 | 212.14 | 653.15 | 5632.77 | 0.00 | 0.00 | 4910.39 | 0.00 | -0.00 | 0.00 | -33.75 | 0.00 |
CORRIDOR_FLR_3 | 10-SEP-10:35 | 0.00 | 0.00 | 0.00 | -9343.30 | 0.00 | 0.00 | 1811.62 | 1546.67 | 0.00 | 5394.15 | 0.00 | 153.82 | 437.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 10-APR-15:11 | 0.00 | -3158.14 | 0.00 | -172.95 | 0.00 | 0.00 | 58.82 | 26.52 | 50.05 | 1594.52 | 0.00 | 0.00 | 1681.77 | 0.00 | -0.00 | 0.00 | -80.59 | 0.00 |
ROOM_2_FLR_6 | 10-APR-19:11 | 0.00 | -3236.59 | 0.00 | -148.22 | 0.00 | 0.00 | 79.53 | 94.71 | 163.29 | 0.00 | 0.00 | 0.00 | 3430.11 | 0.00 | -352.78 | 0.00 | -30.05 | 0.00 |
ROOM_3_MULT9_FLR_6 | 22-NOV-16:11 | 0.00 | -14594.09 | 0.00 | -1087.97 | 0.00 | 0.00 | 529.36 | 150.05 | 441.28 | 3919.05 | 0.00 | 0.00 | 11356.54 | 0.00 | -0.00 | 0.00 | -714.22 | 0.00 |
BANQUET_FLR_6 | 07-JUL-22:00 | 0.00 | 0.00 | 0.00 | -22101.68 | 0.00 | 0.00 | 15644.42 | 1842.08 | 6747.90 | 217.74 | 0.00 | 31.25 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2381.71 |
DINING_FLR_6 | 07-JUL-22:00 | 0.00 | 0.00 | 0.00 | -23487.26 | 0.00 | 0.00 | 15644.30 | 1842.08 | 6747.90 | 201.16 | 0.00 | 31.25 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -979.43 |
KITCHEN_FLR_6 | 24-MAR-16:51 | 0.00 | 0.00 | 0.00 | -30067.88 | 0.00 | 0.00 | 738.40 | 303.01 | 26450.81 | 750.62 | 0.00 | 15.74 | 1809.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 10-SEP-13:50 | 0.00 | 0.00 | 0.00 | -6432.48 | 0.00 | 0.00 | 308.45 | 272.82 | 0.00 | 2575.47 | 0.00 | 73.37 | 3202.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-OCT-18:02 | 0.00 | -150579.36 | 0.00 | -203759.42 | 0.00 | 0.00 | 77929.98 | 40691.94 | 120174.13 | 14269.86 | 0.00 | 2262.88 | 99009.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 05-FEB-07:00 | 0.00 | 0.00 | 368.28 | 0.00 | 0.00 | 0.00 | 626.56 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1265.11 | 0.00 | -144.94 | -44.23 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 26-DEC-19:03 | 4055.24 | 421.98 | 0.00 | -421.98 | 0.00 | 0.00 | 357.76 | 337.19 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1552.92 | 0.00 | -144.42 | -3537.50 |
ROOM_2_FLR_3 | 26-NOV-19:04 | 3989.82 | 424.90 | 0.00 | -424.90 | 0.00 | 0.00 | 286.43 | 378.82 | 484.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1159.88 | 0.00 | -81.23 | -3898.57 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 13-FEB-09:03 | 19967.30 | 5717.10 | 0.00 | -5717.10 | 0.00 | 0.00 | 1817.46 | 1991.09 | 8433.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3818.04 | 0.00 | -913.96 | -27477.31 |
ROOM_5_FLR_3 | 26-DEC-16:14 | 4012.61 | 415.91 | 0.00 | -415.91 | 0.00 | 0.00 | 235.28 | 106.08 | 200.18 | 956.83 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -102.18 | -5408.81 |
ROOM_6_FLR_3 | 13-FEB-16:13 | 3874.80 | 420.22 | 0.00 | -420.22 | 0.00 | 0.00 | 255.81 | 106.07 | 200.16 | 96.13 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -83.17 | -4449.80 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 13-FEB-19:03 | 1231.06 | 105.87 | 0.00 | -105.87 | 0.00 | 0.00 | 89.47 | 84.30 | 121.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -445.49 | 0.00 | -41.34 | -1039.16 |
ROOM_2_FLR_6 | 05-FEB-09:15 | 1173.02 | 102.69 | 0.00 | -102.69 | 0.00 | 0.00 | 37.66 | 53.04 | 163.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -409.37 | 0.00 | -71.79 | -945.84 |
ROOM_3_MULT9_FLR_6 | 11-MAR-16:23 | 5327.00 | 665.94 | 0.00 | -665.94 | 0.00 | 0.00 | 332.94 | 176.84 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -352.21 | 0.00 | -148.30 | -5824.01 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-MAR-19:04 | -100287.81 | 144318.21 | 0.00 | -144318.21 | 0.00 | 0.00 | 71585.33 | 38103.40 | 113070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25253.82 | 0.00 | -2923.21 | -94294.08 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 20.7755 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 20.6694 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 12.9349 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5305 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4435 | 2.4435 | 1.2828 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3077 | 0.3077 | 0.1188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2244 | 0.2244 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1934 | 0.1934 | 0.0019 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1061 | 0.1061 | 0.0867 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2661 | 3.2661 | 0.0327 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3596 | 1.3596 | 1.0142 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5240 | 4.5240 | 2.8410 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1598 | 1.1598 | 0.7121 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1295 | 2.1295 | 1.7824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2347 | 2.2347 | 1.7811 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1520 | 2.1520 | 0.5509 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6748 | 0.6748 | 0.1883 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 20.7755 | 20.6694 | 20.7755 | 10.5305 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2828 | 1.2828 | 1.2828 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1539 | 0.1539 | 0.1188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1376 | 0.1376 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0967 | 0.0967 | 0.0019 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0867 | 0.0867 | 0.0867 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6330 | 1.6330 | 0.0327 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0142 | 1.0142 | 1.0142 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8410 | 2.8410 | 2.8410 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7121 | 0.7121 | 0.7121 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7824 | 1.7824 | 1.7824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7811 | 1.7811 | 1.7811 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0760 | 1.0760 | 0.5509 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3374 | 0.3374 | 0.1883 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 12.9349 | 10.5305 | 10.5305 | 10.5305 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 1.67 |
Number of hours cooling loads not met | 80.00 |
Number of hours not met | 81.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 79.23 | 111895.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2102.90 | 196711.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 545.53 | 45764.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.92 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.52 | 1274.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 617.14 | 38051.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 107.12 | 4500.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 159.26 | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.78 | 4751.13 | 2207.94 | 214776.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.89 | 1310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.44 | 716.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1692.87 | 6406.27 |
Natural Gas | 1788.84 | 3996.78 |
Additional | 0.00 | 0.00 |
Total | 3481.71 | 10403.04 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 48.08 |
Space Heating | 6.98 |
Space Cooling | 185.35 |
Fans (All) | 54.40 |
Service Water Heating | 8.35 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 564.66 |
Subtotal | 564.66 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 194.61 |
Miscellaneous (All) | 352.29 |
Subtotal | 352.29 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.24 |
Space Heating | 0.76 |
Space Cooling | 20.21 |
Fans (All) | 5.93 |
Service Water Heating | 22.14 |
Receptacle Equipment | 33.04 |
Miscellaneous | 12.67 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6312.67 | 2447.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6312.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2447.33 | 0.00 | 0.00 | 0.00 |
Average | 8648.43 | 111.57 | 0.00 | 0.00 | 0.00 |
Sum | 190265.50 | 2454.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4153.67 | 0.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4153.33 | 0.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.67 | 0.00 | 0.00 | 0.00 |
Average | 288887.00 | 0.05 | 0.00 | 0.00 | 0.00 |
Sum | 6355514.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8298.00 | 462.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8712.17 | 47.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8716.83 | 43.17 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8077.67 | 682.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 6823.33 | 1936.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8547.00 | 213.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 5211.33 | 3548.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8604.67 | 155.33 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8539.33 | 220.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8743.83 | 16.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8471.83 | 288.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 7269.50 | 1490.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 6958.33 | 1801.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8448.83 | 311.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8381.17 | 378.83 | 0.00 | 0.00 | 0.00 |
Min | 5211.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3548.67 | 0.00 | 0.00 | 0.00 |
Average | 8231.68 | 528.32 | 0.00 | 0.00 | 0.00 |
Sum | 181097.00 | 11623.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529204.33 | 126.67 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 46078.67 | 4100.33 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58632.83 | 523.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8925.17 | 51.83 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 623147.83 | 87269.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1412478.67 | 702950.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4072.00 | 82.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4089.00 | 65.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4090.00 | 64.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100319.00 | 39.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4039.83 | 114.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 915476.33 | 330238.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 853191.67 | 392523.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 105813.50 | 2455.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 99224.33 | 6721.67 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1412478.67 | 702950.33 | 0.00 | 0.00 | 0.00 |
Average | 219463.19 | 69423.86 | 0.00 | 0.00 | 0.00 |
Sum | 4828190.17 | 1527324.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365464E+11 | 18575.60 | 20-JAN-22:00 | 9.00 | 6.59 | 0.810579E+10 | 4838.68 | 03-JAN-22:19 | 9.00 | 6.59 |
February | 0.298872E+11 | 16390.12 | 01-FEB-22:00 | 17.70 | 16.96 | 0.693191E+10 | 4837.08 | 02-FEB-23:10 | 21.42 | 20.52 |
March | 0.309810E+11 | 14823.95 | 24-MAR-16:51 | 26.60 | 16.35 | 0.730817E+10 | 4658.01 | 01-MAR-22:10 | 26.60 | 16.35 |
April | 0.289829E+11 | 14048.07 | 23-APR-10:35 | 26.43 | 20.52 | 0.678352E+10 | 4350.28 | 03-APR-22:10 | 26.43 | 20.52 |
May | 0.315269E+11 | 14650.98 | 29-MAY-10:35 | 29.63 | 23.21 | 0.716348E+10 | 4461.02 | 26-MAY-22:10 | 29.63 | 23.21 |
June | 0.317000E+11 | 15118.75 | 28-JUN-18:10 | 32.02 | 24.80 | 0.711343E+10 | 4552.19 | 23-JUN-22:10 | 32.02 | 24.80 |
July | 0.352414E+11 | 16089.13 | 16-JUL-10:35 | 30.77 | 25.98 | 0.775124E+10 | 4837.00 | 14-JUL-21:30 | 30.77 | 25.98 |
August | 0.401318E+11 | 20590.82 | 16-AUG-21:00 | 20.40 | 20.40 | 0.819438E+10 | 4837.09 | 09-AUG-22:10 | 20.40 | 20.40 |
September | 0.397130E+11 | 21242.07 | 13-SEP-21:00 | 23.70 | 22.33 | 0.793256E+10 | 4837.09 | 20-SEP-21:19 | 23.87 | 21.31 |
October | 0.414134E+11 | 21621.00 | 27-OCT-21:00 | 13.00 | 8.47 | 0.819666E+10 | 4837.17 | 05-OCT-00:30 | 13.00 | 8.47 |
November | 0.391632E+11 | 21257.24 | 09-NOV-22:00 | 16.60 | 12.80 | 0.792911E+10 | 4837.10 | 30-NOV-22:30 | 15.05 | 12.93 |
December | 0.388353E+11 | 20746.57 | 01-DEC-22:00 | 14.00 | 12.85 | 0.818400E+10 | 4837.09 | 15-DEC-23:10 | 22.00 | 20.57 |
Annual Sum or Average | 0.424123E+12 | 0.915943E+11 | ||||||||
Minimum of Months | 0.289829E+11 | 14048.07 | 9.00 | 6.59 | 0.678352E+10 | 4350.28 | 9.00 | 6.59 | ||
Maximum of Months | 0.414134E+11 | 21621.00 | 32.02 | 25.98 | 0.819666E+10 | 4838.68 | 32.02 | 25.98 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323168E+10 | 3843.73 | 01-JAN-13:00 | 25.00 | 18.55 | 0.731732E+09 | 491.84 | 18-JAN-23:10 | 17.83 | 17.83 |
February | 0.301126E+10 | 3045.65 | 27-FEB-13:50 | 25.32 | 19.85 | 0.674261E+09 | 491.84 | 28-FEB-23:10 | 18.20 | 17.81 |
March | 0.301396E+10 | 2672.43 | 05-MAR-13:00 | 27.70 | 18.32 | 0.744739E+09 | 491.84 | 17-MAR-22:10 | 19.47 | 18.02 |
April | 0.331463E+10 | 2333.83 | 22-APR-13:30 | 29.95 | 20.45 | 0.759266E+09 | 491.84 | 20-APR-22:10 | 29.95 | 20.45 |
May | 0.407543E+10 | 2340.67 | 04-MAY-15:23 | 32.80 | 21.80 | 0.830829E+09 | 491.84 | 19-MAY-21:40 | 24.07 | 22.86 |
June | 0.414260E+10 | 2418.54 | 28-JUN-18:13 | 31.83 | 24.61 | 0.808963E+09 | 491.84 | 06-JUN-22:10 | 31.83 | 24.61 |
July | 0.439270E+10 | 2479.06 | 19-JUL-18:03 | 29.90 | 23.96 | 0.834074E+09 | 491.84 | 12-JUL-22:10 | 29.90 | 23.96 |
August | 0.453947E+10 | 2687.10 | 31-AUG-13:30 | 31.90 | 24.83 | 0.838059E+09 | 491.84 | 16-AUG-22:10 | 31.90 | 24.83 |
September | 0.433065E+10 | 3378.37 | 10-SEP-12:00 | 35.20 | 27.76 | 0.805212E+09 | 491.84 | 01-SEP-21:10 | 35.20 | 27.76 |
October | 0.481450E+10 | 3606.33 | 07-OCT-12:40 | 32.33 | 26.58 | 0.823822E+09 | 491.87 | 05-OCT-00:30 | 32.33 | 26.58 |
November | 0.393176E+10 | 3666.66 | 06-NOV-13:30 | 27.75 | 20.95 | 0.761580E+09 | 491.84 | 30-NOV-22:30 | 15.05 | 12.93 |
December | 0.357357E+10 | 3946.19 | 16-DEC-13:30 | 27.50 | 21.97 | 0.748825E+09 | 491.84 | 15-DEC-23:10 | 27.50 | 21.97 |
Annual Sum or Average | 0.463722E+11 | 0.936136E+10 | ||||||||
Minimum of Months | 0.301126E+10 | 2333.83 | 25.00 | 18.32 | 0.674261E+09 | 491.84 | 15.05 | 12.93 | ||
Maximum of Months | 0.481450E+10 | 3946.19 | 35.20 | 27.76 | 0.838059E+09 | 491.87 | 35.20 | 27.76 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319794E+10 | 1599.57 | 19-JAN-19:10 | 22.00 | 20.56 | 0.847030E+09 | 569.55 | 19-JAN-23:10 | 21.00 | 21.00 |
February | 0.295493E+10 | 1636.92 | 27-FEB-22:00 | 18.80 | 18.03 | 0.774537E+09 | 569.55 | 28-FEB-23:10 | 18.20 | 17.81 |
March | 0.327105E+10 | 1630.90 | 24-MAR-16:51 | 26.60 | 16.35 | 0.860103E+09 | 569.55 | 06-MAR-23:10 | 26.60 | 16.35 |
April | 0.341950E+10 | 1765.85 | 28-APR-21:00 | 23.80 | 23.06 | 0.863504E+09 | 569.55 | 28-APR-22:10 | 23.90 | 23.16 |
May | 0.383043E+10 | 1943.27 | 04-MAY-21:00 | 24.40 | 21.68 | 0.927390E+09 | 569.55 | 19-MAY-21:40 | 24.07 | 22.86 |
June | 0.379704E+10 | 2013.94 | 13-JUN-21:00 | 27.20 | 21.55 | 0.907356E+09 | 569.55 | 06-JUN-22:10 | 27.20 | 21.55 |
July | 0.393511E+10 | 2049.70 | 07-JUL-21:00 | 29.40 | 24.96 | 0.936004E+09 | 569.55 | 12-JUL-22:10 | 23.98 | 22.76 |
August | 0.394795E+10 | 2064.53 | 30-AUG-21:00 | 29.30 | 22.51 | 0.942730E+09 | 569.55 | 16-AUG-22:10 | 29.30 | 22.51 |
September | 0.374389E+10 | 1972.13 | 01-SEP-20:52 | 25.10 | 22.75 | 0.904142E+09 | 569.55 | 01-SEP-21:10 | 25.12 | 22.88 |
October | 0.383198E+10 | 2057.74 | 05-OCT-21:00 | 27.00 | 24.12 | 0.929377E+09 | 569.55 | 02-OCT-22:10 | 27.00 | 24.12 |
November | 0.339250E+10 | 1822.69 | 07-NOV-22:00 | 25.00 | 23.72 | 0.862554E+09 | 569.55 | 06-NOV-23:10 | 25.00 | 23.72 |
December | 0.330724E+10 | 1774.71 | 15-DEC-22:00 | 23.00 | 22.28 | 0.863290E+09 | 569.55 | 15-DEC-23:10 | 22.00 | 20.57 |
Annual Sum or Average | 0.426295E+11 | 0.106180E+11 | ||||||||
Minimum of Months | 0.295493E+10 | 1599.57 | 18.80 | 16.35 | 0.774537E+09 | 569.55 | 18.20 | 16.35 | ||
Maximum of Months | 0.394795E+10 | 2064.53 | 29.40 | 24.96 | 0.942730E+09 | 569.55 | 29.30 | 24.12 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.407090E+09 | 1137.58 | 19-JAN-22:00 | 21.00 | 21.00 | 0.198816E+09 | 120.47 | 03-JAN-01:19 | 21.00 | 21.00 |
February | 0.523576E+09 | 1127.59 | 28-FEB-21:00 | 19.40 | 18.28 | 0.180984E+09 | 120.46 | 04-FEB-00:49 | 19.40 | 18.28 |
March | 0.696819E+09 | 1163.56 | 30-MAR-21:00 | 18.80 | 18.47 | 0.202562E+09 | 120.45 | 30-MAR-21:19 | 18.80 | 18.47 |
April | 0.128875E+10 | 1449.91 | 28-APR-20:00 | 23.30 | 22.57 | 0.198730E+09 | 120.45 | 17-APR-21:00 | 23.30 | 22.57 |
May | 0.248526E+10 | 1695.11 | 25-MAY-21:00 | 27.80 | 24.87 | 0.205441E+09 | 120.45 | 11-MAY-21:30 | 27.80 | 24.87 |
June | 0.273353E+10 | 1898.75 | 28-JUN-21:00 | 28.30 | 24.28 | 0.199177E+09 | 120.45 | 12-JUN-21:30 | 28.30 | 24.28 |
July | 0.292599E+10 | 1944.65 | 19-JUL-20:00 | 28.90 | 24.51 | 0.205007E+09 | 120.45 | 19-JUL-21:30 | 28.05 | 24.96 |
August | 0.285503E+10 | 1864.35 | 21-AUG-21:00 | 28.10 | 22.82 | 0.205874E+09 | 120.45 | 03-AUG-21:30 | 28.10 | 22.82 |
September | 0.248214E+10 | 1859.22 | 10-SEP-20:00 | 28.50 | 25.08 | 0.198647E+09 | 120.45 | 11-SEP-21:30 | 25.70 | 22.41 |
October | 0.230096E+10 | 1813.61 | 06-OCT-20:00 | 27.00 | 26.21 | 0.205104E+09 | 120.45 | 05-OCT-00:30 | 27.00 | 26.21 |
November | 0.112506E+10 | 1476.74 | 02-NOV-20:00 | 25.00 | 23.33 | 0.198155E+09 | 120.45 | 30-NOV-23:10 | 14.70 | 13.02 |
December | 0.717658E+09 | 1354.32 | 15-DEC-22:00 | 23.00 | 22.28 | 0.201353E+09 | 120.45 | 27-DEC-22:40 | 16.67 | 15.42 |
Annual Sum or Average | 0.205419E+11 | 0.239985E+10 | ||||||||
Minimum of Months | 0.407090E+09 | 1127.59 | 18.80 | 18.28 | 0.180984E+09 | 120.45 | 14.70 | 13.02 | ||
Maximum of Months | 0.292599E+10 | 1944.65 | 28.90 | 26.21 | 0.205874E+09 | 120.47 | 28.30 | 26.21 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152917E+10 | 912.77 | 01-JAN-11:35 | 23.33 | 17.94 | 0.120738E+09 | 79.60 | 19-JAN-23:10 | 21.00 | 21.00 |
February | 0.144936E+10 | 905.83 | 26-FEB-11:35 | 25.73 | 19.91 | 0.110838E+09 | 79.40 | 28-FEB-23:10 | 18.20 | 17.81 |
March | 0.167411E+10 | 917.62 | 24-MAR-16:51 | 26.60 | 16.35 | 0.124423E+09 | 79.60 | 30-MAR-22:10 | 18.78 | 18.48 |
April | 0.188421E+10 | 983.05 | 29-APR-10:35 | 29.60 | 23.18 | 0.125816E+09 | 82.83 | 28-APR-22:10 | 29.60 | 23.18 |
May | 0.220229E+10 | 1046.92 | 29-MAY-10:35 | 29.63 | 23.21 | 0.139905E+09 | 85.78 | 12-MAY-22:10 | 29.63 | 23.21 |
June | 0.219959E+10 | 1076.88 | 17-JUN-10:35 | 31.50 | 25.18 | 0.138273E+09 | 88.04 | 16-JUN-22:10 | 31.50 | 25.18 |
July | 0.229030E+10 | 1088.85 | 08-JUL-10:35 | 32.43 | 25.07 | 0.143230E+09 | 88.58 | 07-JUL-22:10 | 32.43 | 25.07 |
August | 0.226727E+10 | 1055.16 | 06-AUG-10:35 | 30.67 | 26.61 | 0.143295E+09 | 88.09 | 24-AUG-22:10 | 29.77 | 24.11 |
September | 0.213520E+10 | 1092.23 | 10-SEP-10:35 | 34.17 | 27.58 | 0.136151E+09 | 87.33 | 10-SEP-23:10 | 27.60 | 24.24 |
October | 0.214605E+10 | 1071.53 | 07-OCT-10:35 | 31.00 | 26.42 | 0.138441E+09 | 87.27 | 06-OCT-21:00 | 31.00 | 26.42 |
November | 0.183062E+10 | 969.44 | 02-NOV-10:35 | 28.43 | 24.09 | 0.124395E+09 | 83.34 | 03-NOV-22:10 | 22.57 | 22.33 |
December | 0.167479E+10 | 959.48 | 16-DEC-11:35 | 26.67 | 22.08 | 0.124100E+09 | 82.25 | 15-DEC-23:10 | 26.67 | 22.08 |
Annual Sum or Average | 0.232830E+11 | 0.156960E+10 | ||||||||
Minimum of Months | 0.144936E+10 | 905.83 | 23.33 | 16.35 | 0.110838E+09 | 79.40 | 18.20 | 17.81 | ||
Maximum of Months | 0.229030E+10 | 1092.23 | 34.17 | 27.58 | 0.143295E+09 | 88.58 | 32.43 | 26.42 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.493872E+11 | 38368.66 | 19-JAN-21:00 | 21.00 | 21.00 | 0.649347E+09 | 383.03 | 03-JAN-22:19 | 21.00 | 21.00 |
February | 0.449691E+11 | 38365.26 | 24-FEB-21:00 | 18.80 | 18.04 | 0.587078E+09 | 382.99 | 04-FEB-00:49 | 18.80 | 18.04 |
March | 0.502846E+11 | 38489.99 | 30-MAR-20:00 | 18.80 | 18.47 | 0.652386E+09 | 381.65 | 22-MAR-02:09 | 18.80 | 18.47 |
April | 0.497007E+11 | 38894.62 | 21-APR-19:56 | 23.80 | 20.03 | 0.629495E+09 | 381.66 | 28-APR-21:19 | 23.83 | 23.09 |
May | 0.528573E+11 | 39270.25 | 04-MAY-20:00 | 25.60 | 22.38 | 0.650715E+09 | 381.72 | 05-MAY-21:10 | 26.60 | 22.72 |
June | 0.515262E+11 | 39412.38 | 13-JUN-20:00 | 30.60 | 21.74 | 0.630879E+09 | 381.68 | 09-JUN-21:10 | 30.60 | 21.74 |
July | 0.531136E+11 | 39476.19 | 07-JUL-20:00 | 29.40 | 24.64 | 0.649337E+09 | 381.65 | 11-JUL-21:10 | 22.98 | 22.18 |
August | 0.531392E+11 | 39330.94 | 02-AUG-20:00 | 27.90 | 21.66 | 0.652094E+09 | 381.72 | 01-AUG-21:10 | 27.90 | 21.66 |
September | 0.508648E+11 | 39143.94 | 01-SEP-20:00 | 23.90 | 22.40 | 0.629202E+09 | 381.73 | 08-SEP-21:10 | 25.73 | 23.17 |
October | 0.522797E+11 | 39216.42 | 05-OCT-20:00 | 27.00 | 24.12 | 0.649651E+09 | 381.68 | 05-OCT-00:30 | 27.00 | 24.12 |
November | 0.492702E+11 | 38833.02 | 02-NOV-20:00 | 25.00 | 23.33 | 0.628129E+09 | 381.65 | 01-NOV-21:19 | 25.00 | 23.33 |
December | 0.496964E+11 | 38404.32 | 15-DEC-21:00 | 23.00 | 22.28 | 0.649344E+09 | 382.79 | 05-DEC-05:10 | 23.00 | 22.28 |
Annual Sum or Average | 0.607089E+12 | 0.765766E+10 | ||||||||
Minimum of Months | 0.449691E+11 | 38365.26 | 18.80 | 18.04 | 0.587078E+09 | 381.65 | 18.80 | 18.04 | ||
Maximum of Months | 0.531392E+11 | 39476.19 | 30.60 | 24.64 | 0.652386E+09 | 383.03 | 30.60 | 24.12 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225430E+11 | 12911.64 | 01-JAN-11:35 | 23.33 | 17.94 | 0.928446E+10 | 6376.04 | 19-JAN-22:40 | 21.00 | 21.00 |
February | 0.205733E+11 | 11908.14 | 26-FEB-11:35 | 25.73 | 19.91 | 0.842947E+10 | 6223.70 | 27-FEB-23:10 | 19.40 | 18.62 |
March | 0.218277E+11 | 11970.27 | 24-MAR-16:51 | 26.60 | 16.35 | 0.927615E+10 | 6203.67 | 06-MAR-23:10 | 26.60 | 16.35 |
April | 0.223327E+11 | 11001.26 | 22-APR-17:20 | 29.77 | 21.51 | 0.908708E+10 | 6226.67 | 21-APR-21:40 | 29.77 | 21.51 |
May | 0.248607E+11 | 11401.37 | 04-MAY-18:10 | 29.53 | 23.53 | 0.975773E+10 | 6349.15 | 25-MAY-21:40 | 27.40 | 24.00 |
June | 0.243955E+11 | 11595.54 | 28-JUN-18:10 | 32.02 | 24.80 | 0.951943E+10 | 6368.08 | 28-JUN-22:10 | 27.88 | 24.53 |
July | 0.254233E+11 | 11733.50 | 22-JUL-17:20 | 34.27 | 26.43 | 0.985083E+10 | 6433.23 | 07-JUL-21:40 | 34.27 | 26.43 |
August | 0.256647E+11 | 11865.39 | 24-AUG-18:10 | 33.48 | 25.47 | 0.998512E+10 | 6460.45 | 30-AUG-22:10 | 28.42 | 22.69 |
September | 0.247604E+11 | 12487.80 | 10-SEP-10:35 | 34.17 | 27.58 | 0.962175E+10 | 6447.44 | 22-SEP-21:40 | 26.60 | 21.18 |
October | 0.261152E+11 | 12570.82 | 07-OCT-10:35 | 31.00 | 26.42 | 0.100601E+11 | 6460.75 | 13-OCT-22:30 | 27.00 | 23.08 |
November | 0.238273E+11 | 13101.60 | 11-NOV-11:35 | 26.43 | 22.12 | 0.938758E+10 | 6460.45 | 07-NOV-23:10 | 26.43 | 22.12 |
December | 0.231886E+11 | 13159.56 | 10-DEC-11:35 | 26.67 | 20.77 | 0.945156E+10 | 6412.98 | 15-DEC-22:40 | 22.33 | 21.13 |
Annual Sum or Average | 0.285512E+12 | 0.113711E+12 | ||||||||
Minimum of Months | 0.205733E+11 | 11001.26 | 23.33 | 16.35 | 0.842947E+10 | 6203.67 | 19.40 | 16.35 | ||
Maximum of Months | 0.261152E+11 | 13159.56 | 34.27 | 27.58 | 0.100601E+11 | 6460.75 | 34.27 | 26.43 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.689030E+11 | 34385.95 | 19-JAN-22:10 | 21.00 | 21.00 | 0.295061E+11 | 19185.93 | 18-JAN-23:10 | 21.00 | 21.00 |
February | 0.630536E+11 | 33348.38 | 02-FEB-22:10 | 21.58 | 20.54 | 0.268096E+11 | 19186.03 | 28-FEB-23:10 | 18.20 | 17.81 |
March | 0.694090E+11 | 33918.32 | 24-MAR-16:51 | 26.60 | 16.35 | 0.296971E+11 | 19186.13 | 17-MAR-22:10 | 26.60 | 16.35 |
April | 0.705987E+11 | 34185.56 | 28-APR-21:52 | 23.90 | 23.16 | 0.292939E+11 | 19186.17 | 28-APR-22:10 | 23.90 | 23.16 |
May | 0.783624E+11 | 36213.08 | 12-MAY-21:10 | 26.60 | 22.01 | 0.312668E+11 | 19186.22 | 19-MAY-21:40 | 24.07 | 22.86 |
June | 0.773762E+11 | 37652.33 | 28-JUN-21:10 | 28.22 | 24.33 | 0.304965E+11 | 19186.10 | 06-JUN-22:10 | 28.22 | 24.33 |
July | 0.805491E+11 | 38604.25 | 07-JUL-21:10 | 29.22 | 24.98 | 0.314552E+11 | 19186.22 | 12-JUL-22:10 | 23.98 | 22.76 |
August | 0.809293E+11 | 38898.56 | 24-AUG-22:00 | 30.00 | 24.17 | 0.316974E+11 | 19186.11 | 16-AUG-22:10 | 30.00 | 24.17 |
September | 0.771655E+11 | 38128.53 | 10-SEP-20:10 | 28.45 | 24.95 | 0.305405E+11 | 19186.21 | 01-SEP-21:10 | 28.45 | 24.95 |
October | 0.798797E+11 | 39782.68 | 05-OCT-21:10 | 27.17 | 24.16 | 0.315106E+11 | 19186.12 | 02-OCT-22:10 | 27.17 | 24.16 |
November | 0.718834E+11 | 37185.42 | 07-NOV-22:10 | 24.88 | 23.63 | 0.296796E+11 | 19186.07 | 30-NOV-22:30 | 15.05 | 12.93 |
December | 0.709530E+11 | 36146.45 | 15-DEC-22:10 | 22.83 | 21.99 | 0.299746E+11 | 19186.11 | 15-DEC-23:10 | 22.00 | 20.57 |
Annual Sum or Average | 0.889063E+12 | 0.361928E+12 | ||||||||
Minimum of Months | 0.630536E+11 | 33348.38 | 21.00 | 16.35 | 0.268096E+11 | 19185.93 | 15.05 | 12.93 | ||
Maximum of Months | 0.809293E+11 | 39782.68 | 30.00 | 24.98 | 0.316974E+11 | 19186.22 | 30.00 | 24.95 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.684934E+09 | 3083.79 | 10-JAN-16:11 | 15.00 | 6.86 | 98133228.28 | 56.69 | 17-JAN-00:40 | 17.00 | 16.79 |
February | 0.832262E+09 | 3115.71 | 13-FEB-16:11 | 14.60 | 6.15 | 88872776.87 | 56.69 | 27-FEB-22:49 | 19.30 | 18.52 |
March | 0.964063E+09 | 3099.12 | 03-MAR-19:01 | 18.62 | 10.00 | 98435422.05 | 56.69 | 17-MAR-21:10 | 20.82 | 18.38 |
April | 0.152779E+10 | 3164.20 | 10-APR-15:11 | 19.80 | 9.80 | 95981602.46 | 56.69 | 30-APR-00:30 | 24.90 | 22.08 |
May | 0.216342E+10 | 2884.15 | 31-MAY-15:12 | 27.07 | 22.63 | 99596815.80 | 56.70 | 24-MAY-22:10 | 27.07 | 22.63 |
June | 0.226108E+10 | 2892.68 | 20-JUN-18:02 | 28.72 | 24.13 | 96428054.12 | 56.70 | 28-JUN-21:10 | 28.22 | 24.33 |
July | 0.233880E+10 | 2893.81 | 27-JUL-18:02 | 26.28 | 24.29 | 99550184.14 | 56.70 | 18-JUL-21:10 | 26.28 | 24.29 |
August | 0.233353E+10 | 2894.40 | 07-AUG-18:02 | 26.00 | 24.54 | 99655466.67 | 56.69 | 15-AUG-22:49 | 24.53 | 21.94 |
September | 0.211453E+10 | 2903.33 | 20-SEP-15:12 | 26.97 | 22.49 | 96337940.40 | 56.69 | 26-SEP-21:10 | 24.40 | 23.14 |
October | 0.210742E+10 | 3118.97 | 27-OCT-15:11 | 17.67 | 9.35 | 99444490.70 | 56.69 | 25-OCT-22:49 | 17.67 | 9.35 |
November | 0.126990E+10 | 3157.36 | 22-NOV-16:11 | 19.03 | 8.93 | 95912685.65 | 56.69 | 07-NOV-23:40 | 19.03 | 8.93 |
December | 0.927730E+09 | 3108.81 | 26-DEC-16:11 | 13.10 | 5.89 | 98242058.34 | 59.03 | 18-DEC-01:39 | 13.10 | 5.89 |
Annual Sum or Average | 0.195255E+11 | 0.116659E+10 | ||||||||
Minimum of Months | 0.684934E+09 | 2884.15 | 13.10 | 5.89 | 88872776.87 | 56.69 | 13.10 | 5.89 | ||
Maximum of Months | 0.233880E+10 | 3164.20 | 28.72 | 24.54 | 99655466.67 | 59.03 | 28.22 | 24.33 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290043E+09 | 2804.90 | 18-JAN-16:12 | 24.00 | 20.20 | 98755546.23 | 70.95 | 19-JAN-22:10 | 21.00 | 21.00 |
February | 0.422655E+09 | 3010.41 | 13-FEB-16:11 | 14.60 | 6.15 | 91146037.98 | 72.69 | 27-FEB-22:40 | 19.20 | 18.43 |
March | 0.603541E+09 | 3056.72 | 20-MAR-18:01 | 13.62 | 9.24 | 0.102281E+09 | 74.01 | 17-MAR-21:10 | 13.62 | 9.24 |
April | 0.118107E+10 | 3130.52 | 10-APR-19:11 | 14.03 | 8.70 | 0.102189E+09 | 80.91 | 28-APR-21:10 | 23.82 | 23.08 |
May | 0.209835E+10 | 2949.49 | 27-MAY-18:51 | 25.00 | 22.66 | 0.101017E+09 | 79.39 | 19-MAY-21:10 | 25.00 | 22.66 |
June | 0.226580E+10 | 2847.88 | 29-JUN-18:02 | 27.70 | 25.57 | 97096075.82 | 75.90 | 06-JUN-21:19 | 27.70 | 25.57 |
July | 0.232207E+10 | 2816.53 | 31-JUL-15:12 | 26.13 | 25.00 | 0.100324E+09 | 83.01 | 12-JUL-21:10 | 26.13 | 25.00 |
August | 0.221580E+10 | 2828.45 | 07-AUG-18:02 | 26.00 | 24.54 | 0.101018E+09 | 76.67 | 16-AUG-21:19 | 20.53 | 20.53 |
September | 0.185382E+10 | 3128.78 | 02-SEP-18:11 | 25.00 | 22.43 | 99326083.41 | 77.53 | 14-SEP-21:10 | 23.30 | 21.76 |
October | 0.165844E+10 | 3009.10 | 27-OCT-18:31 | 14.33 | 8.99 | 0.102513E+09 | 75.78 | 02-OCT-21:10 | 14.33 | 8.99 |
November | 0.710586E+09 | 2820.96 | 06-NOV-19:01 | 24.40 | 19.34 | 98889414.38 | 74.42 | 06-NOV-22:10 | 22.85 | 19.34 |
December | 0.458864E+09 | 2920.73 | 26-DEC-16:11 | 13.10 | 5.89 | 99987711.76 | 76.28 | 15-DEC-22:10 | 13.10 | 5.89 |
Annual Sum or Average | 0.160810E+11 | 0.119454E+10 | ||||||||
Minimum of Months | 0.290043E+09 | 2804.90 | 13.10 | 5.89 | 91146037.98 | 70.95 | 13.10 | 5.89 | ||
Maximum of Months | 0.232207E+10 | 3130.52 | 27.70 | 25.57 | 0.102513E+09 | 83.01 | 27.70 | 25.57 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.376165E+09 | 604.33 | 01-JAN-14:00 | 26.00 | 17.88 | 0.00 | 0.00 | 01-JAN-00:10 | 26.00 | 17.88 |
February | 0.349402E+09 | 470.09 | 02-FEB-13:30 | 28.00 | 20.71 | 0.00 | 0.00 | 01-FEB-00:10 | 28.00 | 20.71 |
March | 0.277258E+09 | 405.06 | 05-MAR-13:30 | 27.70 | 18.32 | 0.00 | 0.00 | 01-MAR-00:10 | 27.70 | 18.32 |
April | 0.335982E+09 | 294.92 | 22-APR-13:30 | 29.95 | 20.45 | 0.00 | 0.00 | 01-APR-00:10 | 29.95 | 20.45 |
May | 0.482472E+09 | 310.97 | 04-MAY-16:20 | 32.43 | 21.45 | 0.00 | 0.00 | 01-MAY-00:10 | 32.43 | 21.45 |
June | 0.484045E+09 | 308.43 | 28-JUN-17:20 | 32.60 | 24.82 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 24.82 |
July | 0.527652E+09 | 336.23 | 19-JUL-17:20 | 32.20 | 25.05 | 0.00 | 0.00 | 01-JUL-00:10 | 32.20 | 25.05 |
August | 0.556302E+09 | 365.23 | 30-AUG-16:20 | 35.83 | 23.47 | 0.00 | 0.00 | 01-AUG-00:10 | 35.83 | 23.47 |
September | 0.551568E+09 | 465.40 | 10-SEP-13:30 | 35.40 | 27.53 | 0.00 | 0.00 | 01-SEP-00:10 | 35.40 | 27.53 |
October | 0.650239E+09 | 515.17 | 13-OCT-13:30 | 32.60 | 23.24 | 0.00 | 0.00 | 01-OCT-00:10 | 32.60 | 23.24 |
November | 0.538948E+09 | 571.34 | 06-NOV-14:00 | 28.30 | 21.15 | 0.00 | 0.00 | 01-NOV-00:10 | 28.30 | 21.15 |
December | 0.440828E+09 | 607.68 | 10-DEC-13:40 | 27.00 | 20.22 | 0.00 | 0.00 | 01-DEC-00:10 | 27.00 | 20.22 |
Annual Sum or Average | 0.557086E+10 | 0.00 | ||||||||
Minimum of Months | 0.277258E+09 | 294.92 | 26.00 | 17.88 | 0.00 | 0.00 | 26.00 | 17.88 | ||
Maximum of Months | 0.650239E+09 | 607.68 | 35.83 | 27.53 | 0.00 | 0.00 | 35.83 | 27.53 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232104E+09 | 949.97 | 03-JAN-19:02 | 8.83 | 4.92 | 98109444.58 | 70.68 | 02-JAN-22:10 | 8.83 | 4.92 |
February | 0.270082E+09 | 957.67 | 12-FEB-19:02 | 10.42 | 6.40 | 89956987.07 | 70.81 | 28-FEB-22:00 | 18.30 | 17.87 |
March | 0.381281E+09 | 992.38 | 20-MAR-18:01 | 13.62 | 9.24 | 0.100845E+09 | 72.71 | 07-MAR-22:49 | 13.62 | 9.24 |
April | 0.543650E+09 | 1019.07 | 10-APR-19:11 | 14.03 | 8.70 | 0.100180E+09 | 76.96 | 28-APR-21:10 | 23.82 | 23.08 |
May | 0.864538E+09 | 1004.89 | 21-MAY-08:61 | 26.10 | 23.27 | 0.100563E+09 | 75.90 | 19-MAY-21:10 | 26.10 | 23.27 |
June | 0.899380E+09 | 1004.04 | 26-JUN-08:61 | 26.28 | 24.22 | 96822649.75 | 72.82 | 06-JUN-21:10 | 26.28 | 24.22 |
July | 0.935312E+09 | 1002.76 | 08-JUL-15:12 | 31.33 | 24.74 | 99926685.83 | 79.46 | 12-JUL-21:10 | 23.90 | 22.65 |
August | 0.885084E+09 | 1000.90 | 17-AUG-18:02 | 30.52 | 25.42 | 0.100548E+09 | 75.15 | 16-AUG-21:30 | 30.52 | 25.42 |
September | 0.772744E+09 | 1000.52 | 03-SEP-18:02 | 29.72 | 24.14 | 98591800.82 | 76.34 | 14-SEP-21:10 | 23.30 | 21.76 |
October | 0.691934E+09 | 1008.14 | 27-OCT-18:31 | 14.33 | 8.99 | 0.101421E+09 | 72.81 | 16-OCT-21:10 | 14.33 | 8.99 |
November | 0.400941E+09 | 1001.29 | 05-NOV-18:01 | 24.82 | 19.45 | 97726036.06 | 71.85 | 03-NOV-21:10 | 24.82 | 19.45 |
December | 0.312953E+09 | 943.86 | 17-DEC-09:51 | 19.00 | 14.29 | 99297894.01 | 74.28 | 15-DEC-22:10 | 19.00 | 14.29 |
Annual Sum or Average | 0.719000E+10 | 0.118399E+10 | ||||||||
Minimum of Months | 0.232104E+09 | 943.86 | 8.83 | 4.92 | 89956987.07 | 70.68 | 8.83 | 4.92 | ||
Maximum of Months | 0.935312E+09 | 1019.07 | 31.33 | 25.42 | 0.101421E+09 | 79.46 | 30.52 | 25.42 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.639968E+09 | 2703.82 | 10-JAN-16:11 | 15.00 | 6.86 | 98419783.96 | 56.69 | 01-JAN-03:00 | 15.00 | 6.86 |
February | 0.765473E+09 | 2811.75 | 13-FEB-16:11 | 14.60 | 6.15 | 89066894.71 | 56.69 | 27-FEB-22:10 | 18.90 | 18.13 |
March | 0.998809E+09 | 2775.72 | 03-MAR-19:01 | 18.62 | 10.00 | 98676267.64 | 56.69 | 30-MAR-21:10 | 18.80 | 18.47 |
April | 0.149877E+10 | 2865.67 | 10-APR-15:11 | 19.80 | 9.80 | 96145937.96 | 56.69 | 05-APR-21:00 | 19.80 | 9.80 |
May | 0.229124E+10 | 2701.09 | 07-MAY-08:62 | 26.05 | 22.54 | 99648737.96 | 56.69 | 24-MAY-23:10 | 25.18 | 23.57 |
June | 0.233827E+10 | 2682.38 | 11-JUN-08:62 | 25.47 | 21.10 | 96466724.39 | 56.69 | 29-JUN-04:00 | 25.00 | 24.50 |
July | 0.246320E+10 | 2685.57 | 15-JUL-08:61 | 28.07 | 25.02 | 99580560.69 | 56.70 | 07-JUL-21:49 | 28.07 | 25.02 |
August | 0.236508E+10 | 2668.09 | 24-AUG-08:61 | 27.28 | 24.27 | 99680047.13 | 56.69 | 17-AUG-23:49 | 27.28 | 24.27 |
September | 0.212067E+10 | 2708.25 | 11-SEP-08:61 | 26.88 | 24.73 | 96364743.66 | 56.69 | 02-SEP-02:20 | 26.88 | 24.73 |
October | 0.208219E+10 | 2841.26 | 27-OCT-15:11 | 17.67 | 9.35 | 99480478.95 | 56.69 | 18-OCT-21:00 | 17.67 | 9.35 |
November | 0.126192E+10 | 2857.89 | 22-NOV-16:11 | 19.03 | 8.93 | 96099843.32 | 56.69 | 02-NOV-23:30 | 19.03 | 8.93 |
December | 0.834347E+09 | 2808.59 | 26-DEC-16:11 | 13.10 | 5.89 | 98327617.44 | 56.69 | 15-DEC-22:40 | 13.10 | 5.89 |
Annual Sum or Average | 0.196599E+11 | 0.116796E+10 | ||||||||
Minimum of Months | 0.639968E+09 | 2668.09 | 13.10 | 5.89 | 89066894.71 | 56.69 | 13.10 | 5.89 | ||
Maximum of Months | 0.246320E+10 | 2865.67 | 28.07 | 25.02 | 99680047.13 | 56.70 | 28.07 | 25.02 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271621E+09 | 2537.70 | 01-JAN-09:51 | 20.00 | 16.19 | 98318643.47 | 70.18 | 19-JAN-22:10 | 21.00 | 21.00 |
February | 0.384036E+09 | 2544.12 | 26-FEB-09:51 | 20.50 | 19.00 | 90407082.47 | 69.81 | 28-FEB-22:30 | 18.55 | 18.33 |
March | 0.644825E+09 | 2771.39 | 19-MAR-08:51 | 17.70 | 12.90 | 0.102002E+09 | 72.18 | 07-MAR-22:40 | 17.70 | 12.90 |
April | 0.117038E+10 | 2809.40 | 20-APR-08:51 | 22.70 | 19.03 | 0.101597E+09 | 78.70 | 28-APR-21:10 | 23.82 | 23.08 |
May | 0.221801E+10 | 2695.84 | 02-MAY-08:11 | 25.57 | 22.40 | 0.101232E+09 | 79.62 | 19-MAY-21:10 | 24.32 | 23.17 |
June | 0.233842E+10 | 2772.13 | 11-JUN-08:11 | 25.93 | 21.07 | 97212931.36 | 74.64 | 06-JUN-21:19 | 25.93 | 21.07 |
July | 0.244984E+10 | 2632.29 | 18-JUL-08:62 | 28.58 | 24.22 | 0.100235E+09 | 80.33 | 12-JUL-21:10 | 28.58 | 24.22 |
August | 0.224834E+10 | 2617.29 | 10-AUG-18:02 | 27.65 | 25.84 | 0.101000E+09 | 75.29 | 16-AUG-21:19 | 20.53 | 20.53 |
September | 0.185946E+10 | 2700.31 | 22-SEP-08:51 | 25.00 | 21.54 | 99276261.07 | 76.61 | 14-SEP-21:10 | 25.00 | 21.54 |
October | 0.163363E+10 | 2872.35 | 01-OCT-08:51 | 22.00 | 15.88 | 0.102311E+09 | 74.65 | 03-OCT-21:10 | 23.17 | 19.17 |
November | 0.703150E+09 | 2620.66 | 06-NOV-09:51 | 23.80 | 20.03 | 98888752.25 | 73.06 | 06-NOV-22:10 | 22.85 | 19.34 |
December | 0.400430E+09 | 2636.19 | 17-DEC-09:51 | 19.00 | 14.29 | 99328943.40 | 72.74 | 15-DEC-22:10 | 19.00 | 14.29 |
Annual Sum or Average | 0.163221E+11 | 0.119181E+10 | ||||||||
Minimum of Months | 0.271621E+09 | 2537.70 | 17.70 | 12.90 | 90407082.47 | 69.81 | 17.70 | 12.90 | ||
Maximum of Months | 0.244984E+10 | 2872.35 | 28.58 | 25.84 | 0.102311E+09 | 80.33 | 28.58 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371120E+10 | 2071.73 | 01-JAN-11:35 | 23.33 | 17.94 | 0.129880E+10 | 867.39 | 02-JAN-00:40 | 17.67 | 16.82 |
February | 0.344388E+10 | 2003.41 | 26-FEB-11:35 | 25.73 | 19.91 | 0.118987E+10 | 866.15 | 28-FEB-23:10 | 18.20 | 17.81 |
March | 0.389137E+10 | 2027.91 | 04-MAR-16:16 | 25.13 | 14.62 | 0.134295E+10 | 860.11 | 01-MAR-00:10 | 25.13 | 14.62 |
April | 0.419779E+10 | 2158.09 | 29-APR-10:35 | 29.60 | 23.18 | 0.136976E+10 | 896.22 | 28-APR-22:10 | 29.60 | 23.18 |
May | 0.482254E+10 | 2243.09 | 29-MAY-10:35 | 29.63 | 23.21 | 0.150961E+10 | 916.73 | 12-MAY-21:49 | 29.63 | 23.21 |
June | 0.477144E+10 | 2301.03 | 17-JUN-10:35 | 31.50 | 25.18 | 0.148251E+10 | 932.05 | 16-JUN-21:49 | 31.50 | 25.18 |
July | 0.496887E+10 | 2320.73 | 08-JUL-10:35 | 32.43 | 25.07 | 0.153605E+10 | 935.90 | 07-JUL-21:00 | 32.43 | 25.07 |
August | 0.492181E+10 | 2279.17 | 24-AUG-18:10 | 33.48 | 25.47 | 0.153670E+10 | 934.44 | 24-AUG-22:10 | 29.77 | 24.11 |
September | 0.469775E+10 | 2335.65 | 10-SEP-10:35 | 34.17 | 27.58 | 0.147429E+10 | 932.93 | 11-SEP-21:49 | 25.63 | 22.39 |
October | 0.479001E+10 | 2333.56 | 07-OCT-10:35 | 31.00 | 26.42 | 0.151345E+10 | 942.36 | 13-OCT-21:49 | 27.08 | 22.81 |
November | 0.412884E+10 | 2125.91 | 07-NOV-11:35 | 27.70 | 23.93 | 0.136285E+10 | 905.05 | 07-NOV-22:49 | 24.42 | 23.26 |
December | 0.390747E+10 | 2123.48 | 16-DEC-11:35 | 26.67 | 22.08 | 0.134083E+10 | 884.53 | 15-DEC-22:49 | 26.67 | 22.08 |
Annual Sum or Average | 0.522530E+11 | 0.169577E+11 | ||||||||
Minimum of Months | 0.344388E+10 | 2003.41 | 23.33 | 14.62 | 0.118987E+10 | 860.11 | 17.67 | 14.62 | ||
Maximum of Months | 0.496887E+10 | 2335.65 | 34.17 | 27.58 | 0.153670E+10 | 942.36 | 32.43 | 25.18 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.625718E+09 | 3236.31 | 10-JAN-16:11 | 15.00 | 6.86 | 97813141.77 | 56.69 | 16-JAN-04:10 | 14.50 | 13.71 |
February | 0.799944E+09 | 3275.70 | 13-FEB-16:11 | 14.60 | 6.15 | 88662491.20 | 56.69 | 28-FEB-04:10 | 18.68 | 18.25 |
March | 0.940447E+09 | 3260.05 | 13-MAR-18:01 | 15.72 | 9.49 | 98203617.96 | 56.69 | 01-MAR-01:19 | 15.72 | 9.49 |
April | 0.155913E+10 | 3331.22 | 10-APR-15:11 | 19.80 | 9.80 | 95913313.39 | 56.70 | 25-APR-21:30 | 21.65 | 20.29 |
May | 0.227319E+10 | 3023.05 | 27-MAY-18:02 | 24.08 | 22.01 | 99591590.67 | 56.70 | 24-MAY-21:30 | 24.08 | 22.01 |
June | 0.239483E+10 | 3041.82 | 19-JUN-18:02 | 27.80 | 24.82 | 96424859.65 | 56.70 | 20-JUN-22:00 | 25.60 | 23.64 |
July | 0.245774E+10 | 3046.62 | 31-JUL-18:02 | 25.78 | 24.31 | 99544207.87 | 56.70 | 28-JUL-22:49 | 25.78 | 24.31 |
August | 0.243762E+10 | 3039.27 | 07-AUG-18:02 | 26.00 | 24.54 | 99646010.33 | 56.70 | 20-AUG-23:00 | 27.00 | 24.12 |
September | 0.217075E+10 | 3053.86 | 10-SEP-15:12 | 35.17 | 27.19 | 96319071.01 | 56.70 | 18-SEP-22:40 | 25.90 | 24.33 |
October | 0.210478E+10 | 3270.74 | 27-OCT-15:11 | 17.67 | 9.35 | 99374496.16 | 56.70 | 06-OCT-01:49 | 17.67 | 9.35 |
November | 0.118533E+10 | 3320.04 | 22-NOV-16:11 | 19.03 | 8.93 | 95756148.50 | 56.70 | 06-NOV-22:00 | 19.03 | 8.93 |
December | 0.862247E+09 | 3262.84 | 26-DEC-16:11 | 13.10 | 5.89 | 97927811.71 | 56.69 | 15-DEC-22:40 | 13.10 | 5.89 |
Annual Sum or Average | 0.198117E+11 | 0.116518E+10 | ||||||||
Minimum of Months | 0.625718E+09 | 3023.05 | 13.10 | 5.89 | 88662491.20 | 56.69 | 13.10 | 5.89 | ||
Maximum of Months | 0.245774E+10 | 3331.22 | 35.17 | 27.19 | 99646010.33 | 56.70 | 27.00 | 24.33 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256697E+09 | 2987.30 | 16-JAN-16:11 | 24.33 | 18.34 | 98278170.24 | 71.23 | 31-JAN-22:30 | 19.15 | 19.15 |
February | 0.397651E+09 | 3141.04 | 13-FEB-16:11 | 14.60 | 6.15 | 90952248.66 | 72.70 | 27-FEB-22:30 | 19.10 | 18.33 |
March | 0.587952E+09 | 3175.33 | 20-MAR-18:01 | 13.62 | 9.24 | 0.102279E+09 | 76.18 | 17-MAR-21:10 | 13.62 | 9.24 |
April | 0.123742E+10 | 3384.81 | 10-APR-19:11 | 14.03 | 8.70 | 0.102472E+09 | 82.51 | 28-APR-21:10 | 23.82 | 23.08 |
May | 0.222054E+10 | 3151.47 | 27-MAY-18:51 | 25.00 | 22.66 | 0.100936E+09 | 79.98 | 19-MAY-21:10 | 25.00 | 22.66 |
June | 0.240695E+10 | 3031.32 | 28-JUN-18:02 | 32.02 | 24.80 | 97046588.68 | 75.91 | 06-JUN-21:40 | 32.02 | 24.80 |
July | 0.244469E+10 | 2995.30 | 14-JUL-18:02 | 26.20 | 24.21 | 0.100398E+09 | 87.16 | 12-JUL-21:10 | 26.20 | 24.21 |
August | 0.232634E+10 | 2968.70 | 07-AUG-18:02 | 26.00 | 24.54 | 0.100995E+09 | 78.01 | 16-AUG-21:19 | 20.53 | 20.53 |
September | 0.192146E+10 | 3252.07 | 02-SEP-18:11 | 25.00 | 22.43 | 99303445.15 | 78.08 | 19-SEP-21:10 | 22.70 | 21.61 |
October | 0.166772E+10 | 3144.36 | 27-OCT-18:31 | 14.33 | 8.99 | 0.102244E+09 | 75.72 | 02-OCT-21:10 | 14.33 | 8.99 |
November | 0.642070E+09 | 2955.22 | 06-NOV-19:01 | 24.40 | 19.34 | 98372326.60 | 73.77 | 03-NOV-21:10 | 24.40 | 19.34 |
December | 0.414904E+09 | 2972.92 | 26-DEC-16:11 | 13.10 | 5.89 | 99449754.90 | 76.51 | 15-DEC-22:10 | 13.10 | 5.89 |
Annual Sum or Average | 0.165244E+11 | 0.119273E+10 | ||||||||
Minimum of Months | 0.256697E+09 | 2955.22 | 13.10 | 5.89 | 90952248.66 | 71.23 | 13.10 | 5.89 | ||
Maximum of Months | 0.244469E+10 | 3384.81 | 32.02 | 24.80 | 0.102472E+09 | 87.16 | 32.02 | 24.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.835086E+09 | 1592.38 | 19-JAN-16:12 | 24.67 | 20.76 | 98973515.40 | 59.89 | 07-JAN-01:30 | 24.67 | 20.76 |
February | 0.794931E+09 | 1716.35 | 13-FEB-16:11 | 14.60 | 6.15 | 89400063.74 | 59.34 | 17-FEB-22:30 | 5.60 | 3.97 |
March | 0.730681E+09 | 1702.05 | 03-MAR-19:01 | 18.62 | 10.00 | 98619075.42 | 59.15 | 12-MAR-23:19 | 9.07 | 7.73 |
April | 0.897416E+09 | 1618.65 | 10-APR-18:01 | 16.23 | 9.35 | 95929689.92 | 56.69 | 28-APR-23:10 | 23.88 | 23.10 |
May | 0.127979E+10 | 1600.27 | 16-MAY-18:02 | 25.50 | 22.43 | 99588528.31 | 56.70 | 18-MAY-21:10 | 26.10 | 22.56 |
June | 0.128840E+10 | 1600.90 | 29-JUN-18:02 | 27.70 | 25.57 | 96415040.64 | 56.70 | 14-JUN-21:10 | 27.70 | 25.57 |
July | 0.137337E+10 | 1603.74 | 15-JUL-18:02 | 29.22 | 25.04 | 99540438.62 | 56.70 | 19-JUL-21:30 | 28.05 | 24.96 |
August | 0.141665E+10 | 1605.48 | 09-AUG-18:02 | 28.18 | 26.59 | 99646113.55 | 56.70 | 21-AUG-21:30 | 27.90 | 22.97 |
September | 0.136641E+10 | 1616.07 | 24-SEP-15:12 | 30.50 | 25.17 | 96345693.57 | 56.69 | 18-SEP-02:20 | 30.50 | 25.17 |
October | 0.149841E+10 | 1685.20 | 27-OCT-18:01 | 14.83 | 8.99 | 99480273.07 | 56.70 | 19-OCT-21:19 | 14.83 | 8.99 |
November | 0.117012E+10 | 1742.55 | 22-NOV-16:11 | 19.03 | 8.93 | 96198793.03 | 59.21 | 15-NOV-03:00 | 19.03 | 8.93 |
December | 0.977579E+09 | 1604.71 | 16-DEC-16:12 | 25.67 | 21.77 | 98888350.69 | 59.67 | 18-DEC-02:39 | 4.33 | 0.76 |
Annual Sum or Average | 0.136288E+11 | 0.116903E+10 | ||||||||
Minimum of Months | 0.730681E+09 | 1592.38 | 14.60 | 6.15 | 89400063.74 | 56.69 | 4.33 | 0.76 | ||
Maximum of Months | 0.149841E+10 | 1742.55 | 30.50 | 26.59 | 99646113.55 | 59.89 | 30.50 | 25.57 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399744E+11 | 19071.23 | 19-JAN-22:53 | 21.00 | 21.00 | 0.167348E+11 | 11348.63 | 31-JAN-23:10 | 18.80 | 18.80 |
February | 0.370990E+11 | 19192.05 | 02-FEB-22:53 | 21.50 | 20.56 | 0.153219E+11 | 11348.83 | 28-FEB-23:10 | 18.20 | 17.81 |
March | 0.420606E+11 | 20940.19 | 24-MAR-16:51 | 26.60 | 16.35 | 0.172471E+11 | 11348.97 | 17-MAR-22:10 | 26.60 | 16.35 |
April | 0.432123E+11 | 20727.32 | 21-APR-21:10 | 25.42 | 20.26 | 0.170615E+11 | 11349.09 | 28-APR-22:10 | 23.90 | 23.16 |
May | 0.474398E+11 | 21473.06 | 25-MAY-22:00 | 27.20 | 23.57 | 0.180863E+11 | 11349.13 | 19-MAY-21:40 | 27.20 | 23.57 |
June | 0.466428E+11 | 21801.15 | 13-JUN-22:00 | 26.70 | 20.63 | 0.176406E+11 | 11348.98 | 06-JUN-22:10 | 26.70 | 20.63 |
July | 0.481186E+11 | 22101.84 | 07-JUL-22:00 | 28.30 | 25.04 | 0.181451E+11 | 11349.19 | 12-JUL-22:10 | 23.98 | 22.76 |
August | 0.477486E+11 | 21837.23 | 24-AUG-22:00 | 30.00 | 24.17 | 0.181993E+11 | 11348.98 | 16-AUG-22:10 | 30.00 | 24.17 |
September | 0.453283E+11 | 21308.01 | 12-SEP-21:10 | 23.38 | 21.67 | 0.174326E+11 | 11348.98 | 14-SEP-22:10 | 23.38 | 22.05 |
October | 0.457989E+11 | 21225.23 | 06-OCT-21:20 | 26.67 | 25.88 | 0.178211E+11 | 11348.98 | 03-OCT-22:10 | 26.67 | 25.88 |
November | 0.413850E+11 | 20266.59 | 01-NOV-21:20 | 25.20 | 22.76 | 0.167231E+11 | 11348.83 | 06-NOV-23:10 | 22.53 | 19.36 |
December | 0.410370E+11 | 19971.03 | 15-DEC-22:20 | 22.67 | 21.70 | 0.169600E+11 | 11348.98 | 15-DEC-23:10 | 22.00 | 20.57 |
Annual Sum or Average | 0.525845E+12 | 0.207373E+12 | ||||||||
Minimum of Months | 0.370990E+11 | 19071.23 | 21.00 | 16.35 | 0.153219E+11 | 11348.63 | 18.20 | 16.35 | ||
Maximum of Months | 0.481186E+11 | 22101.84 | 30.00 | 25.88 | 0.181993E+11 | 11349.19 | 30.00 | 25.88 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.418268E+11 | 20991.36 | 19-JAN-22:10 | 21.00 | 21.00 | 0.172200E+11 | 11348.65 | 02-JAN-22:30 | 21.00 | 21.00 |
February | 0.387124E+11 | 20988.19 | 02-FEB-22:10 | 21.58 | 20.54 | 0.157400E+11 | 11348.83 | 28-FEB-23:10 | 18.20 | 17.81 |
March | 0.438307E+11 | 21618.70 | 24-MAR-16:51 | 26.60 | 16.35 | 0.177023E+11 | 11348.98 | 17-MAR-22:10 | 26.60 | 16.35 |
April | 0.447693E+11 | 21960.74 | 28-APR-21:52 | 23.90 | 23.16 | 0.174352E+11 | 11349.10 | 28-APR-22:10 | 23.90 | 23.16 |
May | 0.491056E+11 | 22873.90 | 25-MAY-22:00 | 27.20 | 23.57 | 0.184525E+11 | 11349.12 | 19-MAY-21:40 | 27.20 | 23.57 |
June | 0.483093E+11 | 23195.35 | 13-JUN-22:00 | 26.70 | 20.63 | 0.179837E+11 | 11348.98 | 06-JUN-22:10 | 26.70 | 20.63 |
July | 0.498373E+11 | 23487.40 | 07-JUL-22:00 | 28.30 | 25.04 | 0.184968E+11 | 11349.19 | 12-JUL-22:10 | 23.98 | 22.76 |
August | 0.494315E+11 | 23233.81 | 24-AUG-22:00 | 30.00 | 24.17 | 0.185560E+11 | 11348.98 | 16-AUG-22:10 | 30.00 | 24.17 |
September | 0.468911E+11 | 22257.43 | 05-SEP-22:00 | 26.20 | 22.79 | 0.177858E+11 | 11349.20 | 01-SEP-21:10 | 26.20 | 22.79 |
October | 0.473753E+11 | 22590.49 | 05-OCT-22:00 | 28.00 | 24.31 | 0.181835E+11 | 11348.99 | 02-OCT-22:10 | 28.00 | 24.31 |
November | 0.428891E+11 | 21527.96 | 01-NOV-22:00 | 25.00 | 22.66 | 0.171068E+11 | 11348.84 | 06-NOV-23:10 | 22.53 | 19.36 |
December | 0.427649E+11 | 21109.80 | 15-DEC-22:52 | 22.00 | 20.57 | 0.174115E+11 | 11348.99 | 15-DEC-23:10 | 22.00 | 20.57 |
Annual Sum or Average | 0.545743E+12 | 0.212074E+12 | ||||||||
Minimum of Months | 0.387124E+11 | 20988.19 | 21.00 | 16.35 | 0.157400E+11 | 11348.65 | 18.20 | 16.35 | ||
Maximum of Months | 0.498373E+11 | 23487.40 | 30.00 | 25.04 | 0.185560E+11 | 11349.20 | 30.00 | 24.31 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.499794E+11 | 27990.28 | 01-JAN-11:40 | 23.33 | 17.94 | 0.188681E+11 | 11319.54 | 14-JAN-18:10 | 13.22 | 10.82 |
February | 0.460075E+11 | 28293.28 | 26-FEB-11:40 | 25.73 | 19.91 | 0.170437E+11 | 11319.64 | 25-FEB-18:10 | 25.73 | 19.91 |
March | 0.516306E+11 | 30058.92 | 24-MAR-16:51 | 26.60 | 16.35 | 0.188762E+11 | 11319.65 | 25-MAR-17:10 | 23.02 | 18.50 |
April | 0.521039E+11 | 29256.80 | 23-APR-10:40 | 26.43 | 20.52 | 0.182624E+11 | 11319.69 | 22-APR-17:10 | 26.43 | 20.52 |
May | 0.561506E+11 | 29708.28 | 29-MAY-10:40 | 29.63 | 23.21 | 0.188718E+11 | 11319.66 | 06-MAY-17:10 | 29.63 | 23.21 |
June | 0.548608E+11 | 29602.16 | 17-JUN-10:50 | 31.60 | 25.15 | 0.182661E+11 | 11319.68 | 10-JUN-17:10 | 31.60 | 25.15 |
July | 0.566345E+11 | 29846.58 | 23-JUL-10:40 | 30.77 | 25.99 | 0.188681E+11 | 11319.68 | 15-JUL-17:10 | 30.77 | 25.99 |
August | 0.562782E+11 | 29374.68 | 06-AUG-10:40 | 30.67 | 26.61 | 0.188755E+11 | 11319.65 | 26-AUG-17:10 | 31.77 | 22.88 |
September | 0.537523E+11 | 30057.39 | 10-SEP-10:50 | 34.28 | 27.62 | 0.182616E+11 | 11319.68 | 09-SEP-17:10 | 34.28 | 27.62 |
October | 0.547709E+11 | 29632.04 | 07-OCT-10:50 | 31.00 | 26.42 | 0.188690E+11 | 11319.68 | 07-OCT-17:10 | 30.50 | 25.80 |
November | 0.506402E+11 | 28600.65 | 02-NOV-10:40 | 28.43 | 24.09 | 0.182587E+11 | 11319.67 | 04-NOV-17:10 | 23.72 | 21.04 |
December | 0.506296E+11 | 28211.23 | 16-DEC-11:40 | 26.67 | 22.08 | 0.188681E+11 | 11319.60 | 02-DEC-18:10 | 26.67 | 22.08 |
Annual Sum or Average | 0.633438E+12 | 0.222189E+12 | ||||||||
Minimum of Months | 0.460075E+11 | 27990.28 | 23.33 | 16.35 | 0.170437E+11 | 11319.54 | 13.22 | 10.82 | ||
Maximum of Months | 0.566345E+11 | 30058.92 | 34.28 | 27.62 | 0.188762E+11 | 11319.69 | 34.28 | 27.62 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462979E+10 | 4651.01 | 01-JAN-14:10 | 25.83 | 18.00 | 0.150139E+10 | 1007.39 | 19-JAN-23:10 | 21.00 | 21.00 |
February | 0.453812E+10 | 4203.36 | 27-FEB-15:10 | 26.00 | 20.45 | 0.140229E+10 | 1007.40 | 27-FEB-23:10 | 19.40 | 18.62 |
March | 0.517988E+10 | 3767.24 | 29-MAR-15:10 | 27.10 | 21.35 | 0.159300E+10 | 1007.40 | 30-MAR-22:10 | 18.78 | 18.48 |
April | 0.647329E+10 | 5189.51 | 28-APR-15:10 | 33.12 | 23.52 | 0.163571E+10 | 1007.41 | 17-APR-21:10 | 33.12 | 23.52 |
May | 0.953270E+10 | 5812.78 | 04-MAY-15:35 | 32.80 | 21.73 | 0.171817E+10 | 1007.40 | 19-MAY-21:40 | 24.07 | 22.86 |
June | 0.999392E+10 | 5822.11 | 30-JUN-15:23 | 33.05 | 23.60 | 0.166578E+10 | 1007.40 | 12-JUN-21:30 | 33.05 | 23.60 |
July | 0.103780E+11 | 6098.60 | 22-JUL-17:03 | 34.63 | 26.60 | 0.171454E+10 | 1007.40 | 12-JUL-22:10 | 34.63 | 26.60 |
August | 0.101111E+11 | 5904.06 | 30-AUG-15:50 | 35.70 | 23.57 | 0.172180E+10 | 1007.40 | 16-AUG-22:10 | 35.70 | 23.57 |
September | 0.900698E+10 | 6431.82 | 10-SEP-13:50 | 35.67 | 27.34 | 0.166134E+10 | 1007.40 | 14-SEP-22:10 | 23.38 | 22.05 |
October | 0.871417E+10 | 6227.72 | 07-OCT-13:00 | 33.00 | 26.99 | 0.170542E+10 | 1007.42 | 05-OCT-00:30 | 33.00 | 26.99 |
November | 0.581505E+10 | 5288.21 | 02-NOV-14:10 | 29.40 | 24.42 | 0.159607E+10 | 1007.40 | 06-NOV-23:10 | 22.53 | 19.36 |
December | 0.526121E+10 | 5045.76 | 16-DEC-13:30 | 27.50 | 21.97 | 0.155742E+10 | 1007.40 | 15-DEC-23:10 | 27.50 | 21.97 |
Annual Sum or Average | 0.896341E+11 | 0.194729E+11 | ||||||||
Minimum of Months | 0.453812E+10 | 3767.24 | 25.83 | 18.00 | 0.140229E+10 | 1007.39 | 18.78 | 18.48 | ||
Maximum of Months | 0.103780E+11 | 6431.82 | 35.70 | 27.34 | 0.172180E+10 | 1007.42 | 35.70 | 26.99 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16693.96 | 27.82 | 21-JAN-07:10 | 1.17 |
February | 4182624.98 | 368.27 | 05-FEB-07:00 | -3.4 |
March | 759301.71 | 84.09 | 11-MAR-12:50 | 7.02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 877665.70 | 215.78 | 20-DEC-07:30 | 1.50 |
Annual Sum or Average | 5836286.35 | |||
Minimum of Months | 0.00 | 0.00 | -3.4 | |
Maximum of Months | 4182624.98 | 368.27 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67908065.68 | 996.64 | 10-JAN-16:14 | 15.00 |
February | 55759233.47 | 999.31 | 16-FEB-16:14 | 12.20 |
March | 47034645.43 | 1006.30 | 20-MAR-18:04 | 13.62 |
April | 1131191.04 | 989.75 | 11-APR-08:03 | 14.18 |
May | 835829.53 | 607.11 | 20-MAY-08:05 | 25.18 |
June | 559137.27 | 604.79 | 20-JUN-08:05 | 28.07 |
July | 346375.69 | 591.22 | 14-JUL-08:04 | 23.90 |
August | 411891.34 | 538.77 | 29-AUG-08:04 | 25.50 |
September | 459269.46 | 623.40 | 27-SEP-08:04 | 24.22 |
October | 649968.39 | 993.80 | 27-OCT-18:04 | 14.83 |
November | 2824969.01 | 999.63 | 12-NOV-09:04 | 8.58 |
December | 58476548.54 | 1013.79 | 26-DEC-19:03 | 10.00 |
Annual Sum or Average | 0.236397E+09 | |||
Minimum of Months | 346375.69 | 538.77 | 8.58 | |
Maximum of Months | 67908065.68 | 1013.79 | 28.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153341E+09 | 986.86 | 25-JAN-19:03 | 10.83 |
February | 96589806.84 | 990.00 | 13-FEB-16:14 | 14.60 |
March | 59166143.42 | 937.23 | 20-MAR-18:04 | 13.62 |
April | 870804.56 | 988.63 | 11-APR-08:03 | 14.18 |
May | 309008.96 | 439.24 | 31-MAY-21:55 | 23.60 |
June | 154110.88 | 366.87 | 23-JUN-08:05 | 28.07 |
July | 19616.20 | 81.55 | 17-JUL-08:05 | 28.07 |
August | 88342.54 | 328.39 | 21-AUG-08:05 | 28.17 |
September | 235301.74 | 483.16 | 14-SEP-06:05 | 24.50 |
October | 676283.22 | 994.65 | 27-OCT-18:34 | 14.33 |
November | 5465479.55 | 997.50 | 26-NOV-19:04 | 14.75 |
December | 0.102076E+09 | 920.22 | 20-DEC-09:13 | 2.33 |
Annual Sum or Average | 0.418992E+09 | |||
Minimum of Months | 19616.20 | 81.55 | 2.33 | |
Maximum of Months | 0.153341E+09 | 997.50 | 28.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7782535.02 | 259.37 | 14-JAN-09:04 | 11.28 |
February | 7022148.62 | 262.74 | 13-FEB-09:03 | 7.98 |
March | 4064787.30 | 258.79 | 09-MAR-09:04 | 4.18 |
April | 58507.82 | 176.76 | 17-APR-21:57 | 20.80 |
May | 16.64 | 0.19 | 14-MAY-21:56 | 24.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 6055.12 | 70.64 | 14-JUL-08:56 | 23.90 |
August | 1273.38 | 8.87 | 15-AUG-21:57 | 24.20 |
September | 1178.06 | 11.78 | 14-SEP-06:07 | 24.50 |
October | 92552.70 | 195.29 | 27-OCT-18:36 | 14.33 |
November | 756659.96 | 257.94 | 23-NOV-19:05 | 11.62 |
December | 8427206.67 | 258.63 | 07-DEC-09:04 | 14.33 |
Annual Sum or Average | 28212921.30 | |||
Minimum of Months | 0.00 | 0.00 | 4.18 | |
Maximum of Months | 8427206.67 | 262.74 | 24.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 75073276.75 | 954.96 | 27-JAN-16:14 | 17.33 |
February | 57280540.16 | 995.78 | 13-FEB-16:14 | 14.60 |
March | 45399051.44 | 941.54 | 03-MAR-19:04 | 18.62 |
April | 628322.08 | 817.07 | 10-APR-18:04 | 16.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 72177.53 | 406.18 | 29-SEP-08:05 | 24.68 |
October | 377312.34 | 983.11 | 27-OCT-18:04 | 14.83 |
November | 1579158.01 | 955.68 | 17-NOV-19:04 | 17.80 |
December | 67563472.24 | 1003.18 | 26-DEC-16:14 | 13.10 |
Annual Sum or Average | 0.247973E+09 | |||
Minimum of Months | 0.00 | 0.00 | 13.10 | |
Maximum of Months | 75073276.75 | 1003.18 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158816E+09 | 885.64 | 27-JAN-19:03 | 13.67 |
February | 95412437.50 | 968.73 | 13-FEB-16:13 | 14.60 |
March | 58002407.44 | 922.69 | 09-MAR-16:13 | 13.30 |
April | 469729.55 | 617.50 | 10-APR-19:13 | 14.03 |
May | 115541.88 | 463.34 | 31-MAY-21:55 | 23.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 29091.68 | 206.47 | 11-JUL-21:56 | 23.90 |
August | 13749.66 | 91.63 | 15-AUG-21:56 | 24.20 |
September | 75328.50 | 586.72 | 14-SEP-06:05 | 24.50 |
October | 372314.59 | 651.04 | 28-OCT-08:05 | 10.43 |
November | 6527876.05 | 917.79 | 14-NOV-19:04 | 14.15 |
December | 0.120597E+09 | 963.70 | 17-DEC-19:04 | 10.83 |
Annual Sum or Average | 0.440431E+09 | |||
Minimum of Months | 0.00 | 0.00 | 10.43 | |
Maximum of Months | 0.158816E+09 | 968.73 | 24.50 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181226E+09 | 1094.98 | 21-JAN-09:02 | 4.33 |
February | 0.122323E+09 | 1231.03 | 13-FEB-19:03 | 8.53 |
March | 0.107094E+09 | 1152.23 | 11-MAR-16:23 | 11.05 |
April | 1272565.40 | 1048.95 | 02-APR-08:03 | 13.80 |
May | 1155437.92 | 731.66 | 22-MAY-08:04 | 26.78 |
June | 803241.68 | 622.58 | 20-JUN-08:05 | 28.07 |
July | 780418.34 | 630.41 | 31-JUL-08:04 | 25.78 |
August | 862956.00 | 628.20 | 29-AUG-08:04 | 25.50 |
September | 652261.21 | 603.37 | 09-SEP-08:05 | 26.78 |
October | 1551775.87 | 1028.17 | 27-OCT-18:04 | 14.83 |
November | 14081275.12 | 1146.20 | 27-NOV-19:04 | 19.85 |
December | 0.142021E+09 | 1146.74 | 21-DEC-09:13 | 6.67 |
Annual Sum or Average | 0.573824E+09 | |||
Minimum of Months | 652261.21 | 603.37 | 4.33 | |
Maximum of Months | 0.181226E+09 | 1231.03 | 28.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329394E+09 | 1156.79 | 05-JAN-09:13 | 7.00 |
February | 0.187544E+09 | 1173.04 | 05-FEB-09:15 | -0.0 |
March | 0.127879E+09 | 1152.10 | 11-MAR-16:23 | 11.05 |
April | 935371.95 | 1073.09 | 02-APR-08:03 | 13.80 |
May | 542648.91 | 554.84 | 20-MAY-08:05 | 25.18 |
June | 285715.42 | 534.10 | 03-JUN-08:05 | 27.98 |
July | 233500.12 | 391.65 | 31-JUL-08:04 | 25.78 |
August | 312892.71 | 561.87 | 21-AUG-08:05 | 28.17 |
September | 403133.23 | 566.98 | 09-SEP-08:05 | 26.78 |
October | 1614647.67 | 1010.91 | 27-OCT-18:34 | 14.33 |
November | 32138964.96 | 1099.64 | 16-NOV-09:01 | 13.67 |
December | 0.226729E+09 | 1164.91 | 20-DEC-09:13 | 2.33 |
Annual Sum or Average | 0.908014E+09 | |||
Minimum of Months | 233500.12 | 391.65 | -0.0 | |
Maximum of Months | 0.329394E+09 | 1173.04 | 28.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20725083.14 | 534.77 | 04-JAN-23:02 | 4.00 |
February | 19498450.07 | 534.94 | 05-FEB-22:02 | 5.48 |
March | 21016374.83 | 591.89 | 11-MAR-16:23 | 11.05 |
April | 533583.87 | 470.55 | 11-APR-08:03 | 14.18 |
May | 55474.28 | 254.25 | 13-MAY-08:05 | 25.28 |
June | 46077.30 | 149.25 | 06-JUN-08:06 | 24.78 |
July | 20534.92 | 92.42 | 03-JUL-08:05 | 27.57 |
August | 51450.62 | 95.30 | 04-AUG-08:05 | 27.98 |
September | 59561.93 | 280.49 | 29-SEP-08:05 | 24.68 |
October | 235756.27 | 301.10 | 28-OCT-08:05 | 10.43 |
November | 1235107.23 | 534.29 | 16-NOV-02:42 | 9.00 |
December | 19286198.70 | 566.48 | 20-DEC-09:02 | 2.17 |
Annual Sum or Average | 82763653.17 | |||
Minimum of Months | 20534.92 | 92.42 | 2.17 | |
Maximum of Months | 21016374.83 | 591.89 | 27.98 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104372E+11 | 10053.14 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.942384E+10 | 10053.14 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.104694E+11 | 10053.14 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.100833E+11 | 10053.14 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.104553E+11 | 10053.14 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.101296E+11 | 10053.14 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.104091E+11 | 10053.14 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.104734E+11 | 10053.14 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.100874E+11 | 10053.14 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.104332E+11 | 10053.14 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.101215E+11 | 10053.14 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.104091E+11 | 10053.14 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.122932E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.942384E+10 | 10053.14 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.104734E+11 | 10053.14 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.195918E+09 | 188.71 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.176896E+09 | 188.71 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.196522E+09 | 188.71 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.189275E+09 | 188.71 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.196257E+09 | 188.71 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.190143E+09 | 188.71 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.195389E+09 | 188.71 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.196597E+09 | 188.71 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.189351E+09 | 188.71 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.195842E+09 | 188.71 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.189992E+09 | 188.71 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.195389E+09 | 188.71 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.230757E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.176896E+09 | 188.71 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.196597E+09 | 188.71 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.119847E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.105778E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.111974E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.102920E+10 | 1573.46 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.998198E+09 | 1573.46 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.935696E+09 | 1573.46 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.968199E+09 | 1573.46 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.103472E+10 | 1573.46 | 01-AUG-19:19 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.105933E+10 | 1573.46 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.115116E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.114633E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.121179E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.129106E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.935696E+09 | 1573.46 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.121179E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.790155E+10 | 7984.04 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.711624E+10 | 7984.04 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.786826E+10 | 7984.04 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.753992E+10 | 7984.04 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.776771E+10 | 7984.04 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.749880E+10 | 7984.04 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.770833E+10 | 7984.04 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.780090E+10 | 7984.04 | 01-AUG-19:19 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.756447E+10 | 7984.04 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.786633E+10 | 7984.04 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.764935E+10 | 7984.04 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.789552E+10 | 7984.04 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.921774E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.711624E+10 | 7984.04 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.790155E+10 | 7984.04 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65789991.58 | 59.53 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 59414784.75 | 59.53 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 65267117.48 | 59.53 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 63743496.62 | 59.53 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 65528554.53 | 59.53 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 63237765.93 | 59.53 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 66042856.93 | 59.53 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 65267117.48 | 59.53 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 63760640.03 | 59.53 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 65781419.88 | 59.53 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 63490631.27 | 59.53 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 66051428.64 | 59.53 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.773376E+09 | 0.256575E+10 | ||||
Minimum of Months | 59414784.75 | 59.53 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 66051428.64 | 59.53 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253460E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.225209E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.243912E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.228468E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.229003E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.217755E+10 | 2763.12 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.225416E+10 | 2763.12 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.233483E+10 | 2763.12 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.231998E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.246309E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.243985E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.253450E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.283245E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.217755E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.253460E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253460E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.225209E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.243912E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.228468E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.229003E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.217755E+10 | 2763.12 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.225416E+10 | 2763.12 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.233483E+10 | 2763.12 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.231998E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.246309E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.243985E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.253450E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.283245E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.217755E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.253460E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.104372E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.942384E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.104694E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.100833E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.104553E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.101296E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.104091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.104734E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.100874E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.104332E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.101215E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.104091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.122932E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.942384E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.104734E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 799034.41 | 0.138428E+09 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1339120.50 | 0.101352E+09 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3367681.15 | 87607631.27 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10708820.95 | 40221361.79 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42914901.87 | 1131834.24 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50194293.57 | 930703.96 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55564106.95 | 132874.26 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49676539.35 | 1392608.39 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33810094.69 | 2767269.82 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26098220.04 | 21476831.57 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5176056.05 | 70015277.23 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2913484.30 | 0.111272E+09 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282562E+09 | 0.576727E+09 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 799034.41 | 132874.26 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55564106.95 | 0.138428E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 812474.40 | 52032573.68 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1212030.87 | 37900324.13 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2581741.49 | 33713982.35 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5940699.31 | 15265195.94 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19609065.84 | 356581.22 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22089592.45 | 332483.54 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24146751.28 | 21450.51 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21707847.01 | 461394.04 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15448706.85 | 860990.93 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12088057.95 | 7836098.41 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3123841.76 | 25522172.84 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1842007.47 | 41885684.67 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130603E+09 | 0.216189E+09 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 812474.40 | 21450.51 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24146751.28 | 52032573.68 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 685672.55 | 0.137793E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1227803.70 | 0.102081E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2906757.95 | 93530843.19 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9181120.65 | 45029587.67 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38176622.41 | 1363238.77 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45377595.22 | 1117683.80 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50239647.98 | 181453.36 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45042066.93 | 1422209.94 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30358275.94 | 2975833.05 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23757038.19 | 21742943.55 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4658414.61 | 70728749.45 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2651507.77 | 0.112707E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254263E+09 | 0.590673E+09 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 685672.55 | 181453.36 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50239647.98 | 0.137793E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.195918E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1658653.35 | 62626689.26 |
February | 0.339028E+09 | 0.176896E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2420720.64 | 44717135.79 |
March | 0.376747E+09 | 0.196522E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4617895.78 | 39501621.63 |
April | 0.363528E+09 | 0.189275E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9948531.21 | 15680300.72 |
May | 0.375778E+09 | 0.196257E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31086623.95 | 69901.82 |
June | 0.364321E+09 | 0.190143E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33740632.13 | 169281.28 |
July | 0.374985E+09 | 0.195389E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36699690.82 | 6058.88 |
August | 0.376571E+09 | 0.196597E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33591632.37 | 281415.58 |
September | 0.363352E+09 | 0.189351E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25156780.53 | 389009.70 |
October | 0.375161E+09 | 0.195842E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19834013.46 | 8092536.80 |
November | 0.362735E+09 | 0.189992E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5719769.03 | 28244720.27 |
December | 0.374985E+09 | 0.195389E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3290816.53 | 49516175.70 |
Annual Sum or Average | 0.442217E+10 | 0.230757E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207766E+09 | 0.249295E+09 |
Minimum of Months | 0.339028E+09 | 0.176896E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1658653.35 | 6058.88 |
Maximum of Months | 0.376747E+09 | 0.196597E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36699690.82 | 62626689.26 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 935730.32 | 0.195105E+09 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 1665547.25 | 0.144297E+09 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 3918200.20 | 0.131613E+09 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 12531444.28 | 61512242.93 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 52128924.03 | 1860791.70 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 61960889.74 | 1525622.44 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 68601695.43 | 247702.63 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 61502468.20 | 1941798.37 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 41452576.00 | 4063180.50 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 32438526.27 | 29688098.81 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 6359782.62 | 96755152.41 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 3602994.37 | 0.158010E+09 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.347099E+09 | 0.826619E+09 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 935730.32 | 247702.63 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 68601695.43 | 0.195105E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.119847E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4458510.10 | 0.289415E+09 |
February | 0.236489E+11 | 0.105778E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6309022.15 | 0.206111E+09 |
March | 0.262800E+11 | 0.111974E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16948427.15 | 0.178805E+09 |
April | 0.253579E+11 | 0.102920E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43325657.63 | 71185736.66 |
May | 0.262123E+11 | 0.998198E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139411E+09 | 564807.79 |
June | 0.254132E+11 | 0.935696E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154449E+09 | 932705.91 |
July | 0.261570E+11 | 0.968199E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167047E+09 | 19581.27 |
August | 0.262677E+11 | 0.103472E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149521E+09 | 1322410.78 |
September | 0.253456E+11 | 0.105933E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108858E+09 | 2455319.87 |
October | 0.261693E+11 | 0.115116E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77659897.59 | 37264749.39 |
November | 0.253025E+11 | 0.114633E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18752407.26 | 0.136116E+09 |
December | 0.261570E+11 | 0.121179E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9539141.62 | 0.230101E+09 |
Annual Sum or Average | 0.308468E+12 | 0.129106E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.896280E+09 | 0.115429E+10 |
Minimum of Months | 0.236489E+11 | 0.935696E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4458510.10 | 19581.27 |
Maximum of Months | 0.262800E+11 | 0.121179E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167047E+09 | 0.289415E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.790155E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12539706.46 | 0.878371E+09 |
February | 0.702046E+11 | 0.711624E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19075411.34 | 0.638852E+09 |
March | 0.780153E+11 | 0.786826E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42385990.24 | 0.568433E+09 |
April | 0.752779E+11 | 0.753992E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102458E+09 | 0.254956E+09 |
May | 0.778146E+11 | 0.776771E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329360E+09 | 7140160.23 |
June | 0.754422E+11 | 0.749880E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372102E+09 | 6356604.33 |
July | 0.776503E+11 | 0.770833E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404826E+09 | 424274.19 |
August | 0.779788E+11 | 0.780090E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364646E+09 | 8279821.30 |
September | 0.752414E+11 | 0.756447E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258210E+09 | 15838973.57 |
October | 0.776868E+11 | 0.786633E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199491E+09 | 0.132079E+09 |
November | 0.751137E+11 | 0.764935E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50046709.10 | 0.432483E+09 |
December | 0.776503E+11 | 0.789552E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28437876.01 | 0.708592E+09 |
Annual Sum or Average | 0.915726E+12 | 0.921774E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218358E+10 | 0.365181E+10 |
Minimum of Months | 0.702046E+11 | 0.711624E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12539706.46 | 424274.19 |
Maximum of Months | 0.780153E+11 | 0.790155E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404826E+09 | 0.878371E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1097368.96 | 71167480.24 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638613.03 | 50123499.25 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3693722.18 | 43141517.85 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10473763.00 | 15423136.90 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41096263.74 | 2703.46 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45187366.84 | 8310.16 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49443811.41 | 10434.11 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45420888.77 | 47558.64 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34695388.36 | 167568.96 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26651236.53 | 7398359.51 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6137150.07 | 30158814.00 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3137450.17 | 54972078.35 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268673E+09 | 0.272621E+09 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1097368.96 | 2703.46 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49443811.41 | 71167480.24 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1034587.79 | 70406868.30 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1537899.32 | 50931404.69 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3336738.69 | 45154057.91 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9548984.21 | 18903328.21 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40077515.73 | 73395.04 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44701559.04 | 98645.65 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49068884.48 | 167636.05 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44771196.32 | 355716.75 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33185957.51 | 769308.08 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25663145.62 | 8653302.69 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5663508.40 | 31546886.67 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2865434.40 | 55193926.13 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261455E+09 | 0.282254E+09 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1034587.79 | 73395.04 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49068884.48 | 70406868.30 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 65789991.58 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 477.49 | 31404252.98 |
February | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10808.43 | 24100103.68 |
March | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64036.80 | 22373875.62 |
April | 0.00 | 63743496.62 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 523094.29 | 12945018.38 |
May | 0.00 | 65528554.53 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2938674.27 | 2575200.79 |
June | 0.00 | 63237765.93 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3659953.42 | 1758038.66 |
July | 0.00 | 66042856.93 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3990720.68 | 1261273.76 |
August | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3626338.67 | 2054128.73 |
September | 0.00 | 63760640.03 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2201111.99 | 3324868.18 |
October | 0.00 | 65781419.88 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624661.19 | 7500928.71 |
November | 0.00 | 63490631.27 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 177436.01 | 18052177.65 |
December | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84805.33 | 26247523.18 |
Annual Sum or Average | 0.00 | 0.773376E+09 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18902118.58 | 0.153597E+09 |
Minimum of Months | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 477.49 | 1261273.76 |
Maximum of Months | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3990720.68 | 31404252.98 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 358337.39 | 19558374.47 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 517210.43 | 14014276.59 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1031541.25 | 12407387.59 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2774752.38 | 4932277.47 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11300442.26 | 7085.47 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12556865.03 | 17533.87 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13773622.11 | 14152.43 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12597812.80 | 72405.01 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9373766.81 | 146142.23 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7294153.30 | 2261556.79 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1712592.58 | 8560755.44 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 875061.41 | 15303752.20 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74166157.75 | 77295699.56 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 358337.39 | 7085.47 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13773622.11 | 19558374.47 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1092075.60 | 71677005.56 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1633857.82 | 50484337.19 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3658253.05 | 43607585.54 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10433543.65 | 15649614.93 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40996456.60 | 2733.35 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45105189.32 | 8599.14 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49366967.33 | 10492.66 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45363861.09 | 46830.46 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34651390.89 | 172756.40 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26631745.13 | 7450159.06 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6126307.99 | 30397835.59 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3137543.58 | 55146388.95 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268197E+09 | 0.274654E+09 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1092075.60 | 2733.35 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49366967.33 | 71677005.56 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1012150.15 | 70388385.53 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1532961.67 | 50780877.87 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3227086.67 | 45487705.94 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9462998.06 | 18872811.09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39905967.33 | 156283.34 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44594931.28 | 164357.60 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48995944.93 | 99661.33 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44706404.20 | 339295.49 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33121127.80 | 771693.23 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25556843.58 | 8653227.50 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5545282.77 | 31842354.15 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2819858.98 | 54761452.46 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260482E+09 | 0.282318E+09 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1012150.15 | 99661.33 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48995944.93 | 70388385.53 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1720502.41 | 87873695.51 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2472911.24 | 63088149.23 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4950919.19 | 56565115.31 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10947430.27 | 24538144.89 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36340746.14 | 324576.42 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40627278.07 | 413009.59 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44200452.95 | 25008.10 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40261124.39 | 608365.64 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28559302.39 | 1094851.09 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21939747.28 | 13102032.28 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5933886.74 | 42704042.03 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3527211.34 | 70534296.68 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241482E+09 | 0.360871E+09 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1720502.41 | 25008.10 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44200452.95 | 87873695.51 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056364.29 | 71169578.54 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1581667.75 | 50229085.04 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3585204.50 | 43199257.41 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10249681.75 | 15618619.03 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40608885.60 | 3475.61 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44714352.87 | 11752.65 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48959905.61 | 13672.10 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44947134.69 | 53539.34 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34246226.04 | 173505.57 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26283694.01 | 7435490.94 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5994673.06 | 30327618.63 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056581.42 | 54952424.29 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265284E+09 | 0.273188E+09 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056364.29 | 3475.61 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48959905.61 | 71169578.54 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 990925.98 | 70145269.13 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1471454.21 | 50977092.83 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3225412.55 | 45325889.15 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9348013.53 | 19297405.78 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39647137.48 | 69952.02 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44251981.69 | 85930.89 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48593465.28 | 222536.24 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44340784.67 | 387719.07 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32799880.06 | 811717.99 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25366720.64 | 8557006.77 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5562379.29 | 31426009.42 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2806737.03 | 54931782.12 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258405E+09 | 0.282238E+09 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 990925.98 | 69952.02 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48593465.28 | 70145269.13 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 529416.72 | 37243451.23 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 800661.86 | 26259136.04 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1818562.82 | 22468228.53 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5256798.16 | 8020662.69 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20789785.61 | 1776.20 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22900242.34 | 6019.94 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25063885.96 | 6878.31 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23001618.73 | 27003.38 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17505336.69 | 90748.42 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13413902.13 | 3855473.40 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3043983.42 | 15773175.11 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1547546.94 | 28802038.06 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135672E+09 | 0.142555E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 529416.72 | 1776.20 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25063885.96 | 37243451.23 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.253460E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4133584.77 | 0.189507E+09 |
February | 0.415303E+11 | 0.225209E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5866744.23 | 0.138616E+09 |
March | 0.461508E+11 | 0.243912E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10878779.99 | 0.125998E+09 |
April | 0.445315E+11 | 0.228468E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23974996.62 | 56398774.23 |
May | 0.460320E+11 | 0.229003E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76831556.59 | 1243869.84 |
June | 0.446286E+11 | 0.217755E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86468029.97 | 1245901.30 |
July | 0.459349E+11 | 0.225416E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94892415.38 | 86689.72 |
August | 0.461292E+11 | 0.233483E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86912469.68 | 1519202.40 |
September | 0.445099E+11 | 0.231998E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63837135.10 | 2849788.11 |
October | 0.459565E+11 | 0.246309E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51758760.64 | 27056782.79 |
November | 0.444343E+11 | 0.243985E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14629223.92 | 90190537.07 |
December | 0.459349E+11 | 0.253450E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8692116.29 | 0.151836E+09 |
Annual Sum or Average | 0.541708E+12 | 0.283245E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528876E+09 | 0.786549E+09 |
Minimum of Months | 0.415303E+11 | 0.217755E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4133584.77 | 86689.72 |
Maximum of Months | 0.461508E+11 | 0.253460E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94892415.38 | 0.189507E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.253460E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3570067.02 | 0.195157E+09 |
February | 0.415303E+11 | 0.225209E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5156038.62 | 0.143246E+09 |
March | 0.461508E+11 | 0.243912E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9722972.35 | 0.130658E+09 |
April | 0.445315E+11 | 0.228468E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22225765.03 | 59437095.88 |
May | 0.460320E+11 | 0.229003E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72627662.99 | 1690946.23 |
June | 0.446286E+11 | 0.217755E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82334634.29 | 1513738.67 |
July | 0.459349E+11 | 0.225416E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90389986.01 | 116906.12 |
August | 0.461292E+11 | 0.233483E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82659596.21 | 1823048.78 |
September | 0.445099E+11 | 0.231998E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60013599.11 | 3490618.42 |
October | 0.459565E+11 | 0.246309E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48726478.52 | 28651678.74 |
November | 0.444343E+11 | 0.243985E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13408293.86 | 93861257.28 |
December | 0.459349E+11 | 0.253450E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7965666.85 | 0.156833E+09 |
Annual Sum or Average | 0.541708E+12 | 0.283245E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498801E+09 | 0.816479E+09 |
Minimum of Months | 0.415303E+11 | 0.217755E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3570067.02 | 116906.12 |
Maximum of Months | 0.461508E+11 | 0.253460E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90389986.01 | 0.195157E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 877237.07 | 0.200447E+09 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 1587523.31 | 0.148472E+09 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3779048.05 | 0.135619E+09 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 12364207.24 | 63931628.48 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 51709359.77 | 2179356.43 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 61667689.83 | 1719719.52 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 68284529.20 | 326509.97 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 61170695.91 | 2176411.45 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 41038308.49 | 4580259.86 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 32148891.02 | 31047564.85 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 6213729.42 | 99979822.92 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3529705.43 | 0.162582E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.344371E+09 | 0.853061E+09 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 877237.07 | 326509.97 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 68284529.20 | 0.200447E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 948965.17 | 0.171318E+09 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1610794.98 | 0.128170E+09 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3836531.25 | 0.117401E+09 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12132154.28 | 59622445.64 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50488767.15 | 2146900.72 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60233279.69 | 1689347.47 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66703094.06 | 325477.72 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59749389.90 | 2141029.56 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40066006.48 | 4507399.51 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31393261.75 | 29257778.89 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6106831.58 | 91328433.19 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3480233.64 | 0.140843E+09 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336749E+09 | 0.748752E+09 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 948965.17 | 325477.72 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66703094.06 | 0.171318E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 10053.14 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 10053.14 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 10053.14 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 10053.14 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 10053.14 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 10053.14 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 10053.14 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 10053.14 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 10053.14 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 10053.14 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 10053.14 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 10053.14 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 | 02-JAN-15:00 | 121.35 | 05-JAN-06:00 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.37 | 02-FEB-13:00 | 144.94 | 05-FEB-07:50 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.21 | 26-MAR-14:00 | 115.38 | 09-MAR-06:57 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.76 | 28-APR-15:00 | 73.82 | 11-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.95 | 07-MAY-14:00 | 14.86 | 07-MAY-01:00 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.24 | 14-JUN-14:00 | 15.22 | 07-JUN-02:00 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.84 | 22-JUL-16:00 | 9.63 | 11-JUL-19:55 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.55 | 30-AUG-16:00 | 20.43 | 25-AUG-24:00 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.11 | 09-SEP-16:51 | 25.88 | 07-SEP-20:00 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.25 | 05-OCT-15:00 | 67.72 | 28-OCT-08:00 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.23 | 01-NOV-14:00 | 89.88 | 12-NOV-08:00 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.32 | 13-DEC-15:00 | 121.70 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 | 9.63 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 63.11 | 144.94 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.31 | 16-JAN-15:00 | 49.13 | 05-JAN-06:00 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 | 02-FEB-13:00 | 57.25 | 05-FEB-08:00 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 | 26-MAR-14:00 | 47.55 | 09-MAR-06:10 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 28-APR-15:00 | 31.12 | 11-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.34 | 28-MAY-16:00 | 5.43 | 07-MAY-01:00 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 | 14-JUN-14:00 | 6.06 | 07-JUN-02:00 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 | 22-JUL-16:00 | 3.60 | 11-JUL-20:00 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 30-AUG-16:00 | 7.69 | 25-AUG-24:00 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 | 09-SEP-16:51 | 9.92 | 07-SEP-20:00 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 05-OCT-15:00 | 27.81 | 28-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 01-NOV-14:00 | 34.64 | 12-NOV-08:00 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 | 13-DEC-15:00 | 48.57 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 9.31 | 3.60 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 | 57.25 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 | 02-JAN-15:00 | 121.78 | 05-JAN-07:53 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.40 | 02-FEB-13:00 | 142.39 | 05-FEB-07:40 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.47 | 26-MAR-14:00 | 119.17 | 09-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.57 | 28-APR-15:00 | 80.52 | 11-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.48 | 07-MAY-14:00 | 14.24 | 07-MAY-01:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.30 | 14-JUN-14:00 | 16.60 | 07-JUN-02:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.41 | 22-JUL-16:00 | 8.79 | 11-JUL-19:55 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.06 | 30-AUG-16:00 | 18.66 | 25-AUG-24:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.57 | 09-SEP-16:52 | 23.62 | 07-SEP-20:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.75 | 05-OCT-15:00 | 71.63 | 28-OCT-08:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.49 | 01-NOV-14:00 | 86.29 | 12-NOV-08:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.57 | 13-DEC-15:00 | 119.79 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 | 8.79 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 57.57 | 142.39 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 188.71 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.20 | 16-JAN-15:00 | 63.87 | 05-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 188.71 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 | 02-FEB-13:00 | 76.29 | 05-FEB-08:00 |
March | 220.32 | 01-MAR-00:10 | 188.71 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 | 26-MAR-14:00 | 60.73 | 09-MAR-06:57 |
April | 220.32 | 01-APR-00:10 | 188.71 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.35 | 28-APR-15:00 | 38.66 | 11-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 188.71 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.85 | 28-MAY-16:00 | 4.78 | 07-MAY-01:00 |
June | 220.32 | 01-JUN-00:10 | 188.71 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.35 | 14-JUN-14:00 | 5.84 | 07-JUN-02:00 |
July | 220.32 | 01-JUL-00:10 | 188.71 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.65 | 22-JUL-16:00 | 2.06 | 11-JUL-20:00 |
August | 220.32 | 01-AUG-00:10 | 188.71 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.19 | 30-AUG-16:00 | 7.76 | 25-AUG-24:00 |
September | 220.32 | 01-SEP-00:10 | 188.71 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.63 | 09-SEP-17:00 | 10.34 | 07-SEP-20:00 |
October | 220.32 | 01-OCT-23:10 | 188.71 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.08 | 05-OCT-15:00 | 34.92 | 28-OCT-05:30 |
November | 220.32 | 01-NOV-00:10 | 188.71 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.26 | 01-NOV-14:00 | 43.54 | 12-NOV-08:00 |
December | 220.32 | 01-DEC-00:10 | 188.71 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.35 | 13-DEC-15:00 | 64.05 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 15.20 | 2.06 | |||||
Maximum of Months | 220.32 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 36.63 | 76.29 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 19.58 | 16-JAN-15:00 | 172.76 | 05-JAN-06:00 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 27.86 | 02-FEB-13:00 | 202.75 | 05-FEB-07:57 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 38.87 | 26-MAR-14:00 | 165.39 | 09-MAR-06:53 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 59.49 | 28-APR-15:00 | 109.95 | 11-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 63.46 | 07-MAY-14:00 | 19.44 | 07-MAY-01:00 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 70.05 | 14-JUN-14:00 | 22.66 | 07-JUN-02:00 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 77.03 | 22-JUL-16:00 | 12.00 | 11-JUL-20:00 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 77.92 | 30-AUG-16:00 | 25.47 | 25-AUG-24:00 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 78.61 | 09-SEP-16:51 | 32.25 | 07-SEP-20:00 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 63.84 | 05-OCT-15:00 | 97.81 | 28-OCT-08:00 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 38.91 | 01-NOV-14:00 | 117.83 | 12-NOV-08:00 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 39.01 | 13-DEC-15:00 | 173.24 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 19.58 | 12.00 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 78.61 | 202.75 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.35 | 02-JAN-15:00 | 276.48 | 05-JAN-06:00 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.73 | 02-FEB-13:00 | 320.40 | 05-FEB-07:57 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.25 | 30-MAR-13:00 | 263.90 | 09-MAR-06:00 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.06 | 28-APR-15:00 | 165.33 | 11-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1573.46 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.69 | 28-MAY-16:00 | 18.39 | 07-MAY-01:00 |
June | 15368.40 | 01-JUN-00:10 | 1573.46 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.09 | 14-JUN-14:00 | 28.27 | 07-JUN-02:00 |
July | 15368.40 | 01-JUL-00:10 | 1573.46 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.40 | 22-JUL-16:00 | 5.79 | 11-JUL-20:10 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 01-AUG-19:19 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.57 | 30-AUG-16:00 | 37.12 | 25-AUG-24:00 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.51 | 09-SEP-17:00 | 41.37 | 07-SEP-21:10 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.98 | 05-OCT-15:00 | 152.85 | 28-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.93 | 01-NOV-14:00 | 191.65 | 12-NOV-08:00 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.17 | 13-DEC-15:00 | 274.82 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 59.73 | 5.79 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 160.40 | 320.40 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 7984.04 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.98 | 02-JAN-15:00 | 829.52 | 05-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 7984.04 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.05 | 02-FEB-13:00 | 958.20 | 05-FEB-08:00 |
March | 45622.98 | 01-MAR-00:10 | 7984.04 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.91 | 26-MAR-14:00 | 797.98 | 09-MAR-06:00 |
April | 45622.98 | 01-APR-00:10 | 7984.04 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.45 | 28-APR-15:00 | 517.45 | 11-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 7984.04 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.12 | 28-MAY-16:00 | 86.54 | 07-MAY-01:00 |
June | 45622.98 | 01-JUN-00:10 | 7984.04 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.06 | 14-JUN-14:00 | 108.08 | 07-JUN-02:00 |
July | 45622.98 | 01-JUL-00:10 | 7984.04 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 437.41 | 22-JUL-16:00 | 55.43 | 11-JUL-20:10 |
August | 45622.98 | 01-AUG-00:10 | 7984.04 | 01-AUG-19:19 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 425.45 | 30-AUG-16:00 | 129.12 | 25-AUG-24:00 |
September | 45622.98 | 01-SEP-00:10 | 7984.04 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.38 | 09-SEP-17:00 | 157.29 | 07-SEP-20:20 |
October | 45622.98 | 01-OCT-23:10 | 7984.04 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.67 | 05-OCT-15:00 | 472.46 | 28-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 7984.04 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.94 | 01-NOV-14:00 | 577.78 | 12-NOV-08:00 |
December | 45622.98 | 01-DEC-00:10 | 7984.04 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.59 | 13-DEC-15:00 | 821.71 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 154.98 | 55.43 | |||||
Maximum of Months | 45622.98 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 437.41 | 958.20 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 02-JAN-16:20 | 70.95 | 05-JAN-06:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 | 25-FEB-17:00 | 84.66 | 05-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27-MAR-15:18 | 67.49 | 09-MAR-06:53 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 | 28-APR-15:20 | 41.94 | 11-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.01 | 28-MAY-16:00 | 1.78 | 31-MAY-13:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 | 10-JUN-16:00 | 1.78 | 01-JUN-13:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 | 22-JUL-16:00 | 1.79 | 13-JUL-11:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.69 | 30-AUG-16:00 | 5.53 | 16-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.65 | 09-SEP-16:50 | 13.07 | 07-SEP-18:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.57 | 05-OCT-15:20 | 40.12 | 28-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | 02-NOV-15:20 | 48.87 | 12-NOV-08:40 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.88 | 13-DEC-16:20 | 71.15 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 1.78 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 44.69 | 84.66 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 02-JAN-16:18 | 70.95 | 05-JAN-06:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 | 25-FEB-17:00 | 84.65 | 05-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27-MAR-15:18 | 67.48 | 09-MAR-06:53 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 | 28-APR-15:20 | 41.94 | 11-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.01 | 28-MAY-16:00 | 4.69 | 17-MAY-21:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 | 10-JUN-16:00 | 4.59 | 07-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 | 22-JUL-16:00 | 11.67 | 12-JUL-17:40 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.70 | 30-AUG-16:00 | 12.46 | 16-AUG-18:02 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.65 | 09-SEP-16:50 | 16.51 | 07-SEP-18:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.30 | 05-OCT-15:20 | 39.23 | 28-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | 02-NOV-15:20 | 47.09 | 12-NOV-08:10 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.88 | 13-DEC-16:20 | 71.15 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 4.59 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 44.70 | 84.65 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 59.53 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 | 02-JAN-15:00 | 24.79 | 05-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 59.53 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 02-FEB-13:00 | 27.11 | 05-FEB-08:00 |
March | 0.00 | 01-MAR-00:10 | 59.53 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 26-MAR-14:00 | 23.33 | 09-MAR-07:20 |
April | 0.00 | 01-APR-00:10 | 59.53 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.48 | 28-APR-15:00 | 16.71 | 11-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 59.53 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 | 07-MAY-14:00 | 4.89 | 07-MAY-01:00 |
June | 0.00 | 01-JUN-00:10 | 59.53 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 14-JUN-14:00 | 5.29 | 07-JUN-02:00 |
July | 0.00 | 01-JUL-00:10 | 59.53 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.77 | 22-JUL-16:00 | 3.90 | 11-JUL-20:00 |
August | 0.00 | 01-AUG-00:10 | 59.53 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 30-AUG-16:00 | 5.67 | 25-AUG-24:00 |
September | 0.00 | 01-SEP-00:10 | 59.53 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 09-SEP-17:00 | 6.56 | 07-SEP-18:00 |
October | 0.00 | 01-OCT-00:10 | 59.53 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 | 05-OCT-15:00 | 15.18 | 28-OCT-08:00 |
November | 0.00 | 01-NOV-00:10 | 59.53 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 01-NOV-14:00 | 17.79 | 12-NOV-07:53 |
December | 0.00 | 01-DEC-00:10 | 59.53 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 | 13-DEC-15:00 | 23.61 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 | 3.90 | |||||
Maximum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 27.11 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.13 | 02-JAN-16:50 | 19.97 | 05-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 | 25-FEB-17:00 | 23.63 | 05-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 | 27-MAR-15:20 | 19.18 | 09-MAR-06:53 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.81 | 28-APR-15:20 | 11.71 | 11-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.61 | 28-MAY-16:00 | 0.82 | 17-MAY-21:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 10-JUN-16:00 | 1.20 | 07-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 | 22-JUL-16:00 | 0.98 | 12-JUL-18:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.48 | 30-AUG-16:00 | 3.07 | 16-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 09-SEP-16:50 | 4.11 | 07-SEP-18:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.13 | 05-OCT-15:20 | 11.68 | 28-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 02-NOV-15:20 | 13.78 | 12-NOV-08:10 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.11 | 13-DEC-16:18 | 19.86 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.13 | 0.82 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.48 | 23.63 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 02-JAN-16:18 | 71.33 | 05-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 | 25-FEB-17:00 | 84.66 | 05-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27-MAR-15:18 | 67.49 | 09-MAR-06:53 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 | 28-APR-15:20 | 41.94 | 11-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.01 | 28-MAY-16:00 | 1.78 | 31-MAY-13:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 | 10-JUN-16:00 | 1.78 | 01-JUN-13:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 | 22-JUL-16:00 | 1.79 | 13-JUL-11:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.71 | 30-AUG-16:00 | 5.53 | 16-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.66 | 09-SEP-16:50 | 13.07 | 07-SEP-18:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 | 05-OCT-15:20 | 43.25 | 28-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 | 02-NOV-15:20 | 52.24 | 12-NOV-08:10 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.88 | 13-DEC-16:20 | 71.15 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 1.78 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 44.71 | 84.66 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 02-JAN-16:18 | 70.95 | 05-JAN-06:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 | 25-FEB-17:00 | 84.65 | 05-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27-MAR-15:18 | 67.48 | 09-MAR-06:53 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 | 28-APR-15:20 | 41.94 | 11-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.01 | 28-MAY-16:00 | 6.06 | 03-MAY-07:30 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 | 10-JUN-16:00 | 6.88 | 11-JUN-07:50 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 | 22-JUL-16:00 | 6.60 | 12-JUL-18:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.70 | 30-AUG-16:00 | 11.16 | 16-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.65 | 09-SEP-16:50 | 16.82 | 07-SEP-18:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 | 05-OCT-15:20 | 42.38 | 28-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | 02-NOV-15:18 | 51.78 | 12-NOV-08:10 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.88 | 13-DEC-16:20 | 71.15 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 6.06 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 44.70 | 84.65 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 16-JAN-15:00 | 87.57 | 05-JAN-06:00 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.94 | 02-FEB-13:00 | 101.91 | 05-FEB-07:55 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.72 | 26-MAR-14:00 | 84.76 | 09-MAR-06:00 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.80 | 28-APR-15:00 | 54.11 | 11-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 | 28-MAY-16:00 | 8.34 | 07-MAY-01:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.64 | 14-JUN-14:00 | 10.06 | 07-JUN-02:00 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.47 | 22-JUL-16:00 | 4.79 | 11-JUL-19:55 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.61 | 30-AUG-16:00 | 12.72 | 25-AUG-24:00 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.54 | 09-SEP-17:00 | 15.82 | 07-SEP-20:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.56 | 05-OCT-15:00 | 49.94 | 28-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.77 | 01-NOV-14:00 | 61.20 | 12-NOV-08:00 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.37 | 13-DEC-15:00 | 86.24 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 4.79 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.54 | 101.91 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 02-JAN-16:20 | 71.17 | 05-JAN-06:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 | 25-FEB-17:00 | 84.88 | 05-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 | 27-MAR-15:18 | 67.70 | 09-MAR-06:53 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.57 | 28-APR-15:20 | 42.15 | 11-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 28-MAY-16:00 | 1.97 | 31-MAY-13:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.76 | 10-JUN-16:00 | 1.97 | 01-JUN-13:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 | 22-JUL-16:00 | 1.98 | 12-JUL-15:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.18 | 30-AUG-16:00 | 5.71 | 16-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.49 | 09-SEP-16:50 | 13.26 | 07-SEP-18:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.32 | 05-OCT-15:20 | 37.90 | 28-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.01 | 02-NOV-15:20 | 47.14 | 12-NOV-08:10 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 | 13-DEC-16:20 | 71.37 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 1.97 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 44.49 | 84.88 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 02-JAN-16:18 | 71.16 | 05-JAN-06:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 | 25-FEB-17:00 | 84.88 | 05-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 | 27-MAR-15:18 | 67.70 | 09-MAR-06:53 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.47 | 28-APR-15:20 | 42.14 | 11-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.82 | 28-MAY-16:00 | 4.84 | 17-MAY-21:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.75 | 10-JUN-16:00 | 4.12 | 06-JUN-21:30 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.15 | 22-JUL-16:00 | 14.14 | 12-JUL-17:50 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.44 | 30-AUG-16:00 | 14.82 | 16-AUG-18:02 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.48 | 09-SEP-16:50 | 16.98 | 07-SEP-18:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.72 | 05-OCT-15:20 | 37.07 | 28-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 02-NOV-15:20 | 45.83 | 12-NOV-08:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 | 13-DEC-16:20 | 71.36 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 4.12 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 44.48 | 84.88 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 | 02-JAN-16:20 | 36.60 | 05-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 25-FEB-17:00 | 43.43 | 05-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27-MAR-15:20 | 34.64 | 09-MAR-06:53 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.90 | 28-APR-15:20 | 21.56 | 11-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 28-MAY-16:00 | 1.00 | 31-MAY-13:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.32 | 10-JUN-16:00 | 1.01 | 01-JUN-13:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.60 | 22-JUL-16:00 | 1.01 | 13-JUL-11:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.78 | 30-AUG-16:00 | 2.92 | 16-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 | 09-SEP-16:50 | 6.79 | 07-SEP-18:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 | 05-OCT-15:20 | 21.21 | 28-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 02-NOV-15:20 | 26.24 | 12-NOV-08:10 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 | 13-DEC-16:20 | 36.51 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 | 1.00 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 22.78 | 43.43 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.92 | 16-JAN-15:00 | 184.01 | 05-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.52 | 02-FEB-13:00 | 216.24 | 05-FEB-08:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.38 | 26-MAR-14:00 | 177.70 | 09-MAR-06:10 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.25 | 28-APR-15:00 | 116.66 | 11-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.08 | 28-MAY-16:00 | 15.36 | 07-MAY-01:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.52 | 14-JUN-14:00 | 23.12 | 07-JUN-02:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.97 | 22-JUL-16:00 | 11.14 | 11-JUL-20:10 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.63 | 30-AUG-16:00 | 27.61 | 16-AUG-21:10 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.24 | 09-SEP-16:51 | 33.17 | 07-SEP-20:20 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.27 | 05-OCT-15:00 | 104.09 | 28-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.23 | 02-NOV-13:00 | 127.05 | 12-NOV-08:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.60 | 13-DEC-15:00 | 183.94 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 38.92 | 11.14 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 99.97 | 216.24 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.63 | 16-JAN-15:00 | 186.08 | 05-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 | 02-FEB-13:00 | 218.92 | 05-FEB-08:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.31 | 26-MAR-14:00 | 179.56 | 09-MAR-06:10 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.33 | 28-APR-15:00 | 118.64 | 11-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.92 | 28-MAY-16:00 | 17.01 | 07-MAY-01:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.57 | 14-JUN-14:00 | 24.60 | 07-JUN-02:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.78 | 22-JUL-16:00 | 13.27 | 11-JUL-20:10 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.64 | 30-AUG-16:00 | 28.91 | 25-AUG-24:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.14 | 09-SEP-16:51 | 35.27 | 07-SEP-20:20 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.42 | 05-OCT-15:00 | 105.66 | 28-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.33 | 02-NOV-13:00 | 129.00 | 12-NOV-08:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.78 | 13-DEC-15:00 | 186.19 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.63 | 13.27 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 97.78 | 218.92 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 19.33 | 16-JAN-15:00 | 176.71 | 05-JAN-06:00 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 27.79 | 02-FEB-13:00 | 207.29 | 05-FEB-08:00 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 38.98 | 26-MAR-14:00 | 169.21 | 09-MAR-06:53 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 60.01 | 28-APR-15:00 | 112.68 | 11-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 64.04 | 07-MAY-14:00 | 20.48 | 07-MAY-01:00 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 70.76 | 14-JUN-14:00 | 23.75 | 07-JUN-02:00 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 77.91 | 22-JUL-16:00 | 12.86 | 11-JUL-19:55 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 78.82 | 30-AUG-16:00 | 26.63 | 25-AUG-24:00 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 79.46 | 09-SEP-16:51 | 33.47 | 07-SEP-20:00 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 64.44 | 05-OCT-15:00 | 100.29 | 28-OCT-08:00 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 39.02 | 02-NOV-13:00 | 120.74 | 12-NOV-08:00 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 39.12 | 13-DEC-15:00 | 177.22 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 19.33 | 12.86 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 79.46 | 207.29 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 | 16-JAN-15:00 | 153.67 | 05-JAN-06:00 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 | 02-FEB-13:00 | 180.79 | 05-FEB-07:55 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.10 | 26-MAR-14:00 | 152.08 | 09-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.66 | 28-APR-15:00 | 101.39 | 11-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 | 07-MAY-14:00 | 20.06 | 07-MAY-01:00 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.20 | 14-JUN-14:00 | 23.27 | 07-JUN-02:00 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.15 | 22-JUL-16:00 | 12.64 | 11-JUL-19:55 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.05 | 30-AUG-16:00 | 26.08 | 25-AUG-24:00 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 | 09-SEP-16:51 | 32.84 | 07-SEP-20:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.00 | 05-OCT-15:00 | 92.03 | 28-OCT-05:00 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.13 | 01-NOV-14:00 | 113.46 | 12-NOV-08:00 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.24 | 13-DEC-15:00 | 151.89 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 | 12.64 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 | 180.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18575.60 | 20-JAN-22:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16390.12 | 01-FEB-22:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14823.95 | 24-MAR-16:51 | 44729.58 | 19548.08 | 24841.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14048.07 | 23-APR-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14650.98 | 29-MAY-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15118.75 | 28-JUN-18:10 | 53675.50 | 53616.48 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16089.13 | 16-JUL-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20590.82 | 16-AUG-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21242.07 | 13-SEP-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21621.00 | 27-OCT-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21257.24 | 09-NOV-22:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20746.57 | 01-DEC-22:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14048.07 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21621.00 | 53675.50 | 53616.48 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3843.73 | 01-JAN-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 | 0.00 |
February | 3045.65 | 27-FEB-13:50 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 0.00 |
March | 2672.43 | 05-MAR-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 | 0.00 |
April | 2333.83 | 22-APR-13:30 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 31.02 | 0.00 |
May | 2340.67 | 04-MAY-15:23 | 1949.22 | 426.93 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 45.24 | 0.00 |
June | 2418.54 | 28-JUN-18:13 | 2728.91 | 1366.17 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 | 0.00 |
July | 2479.06 | 19-JUL-18:03 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 30.71 | 0.00 |
August | 2687.10 | 31-AUG-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 | 0.00 |
September | 3378.37 | 10-SEP-12:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 57.25 | 0.00 |
October | 3606.33 | 07-OCT-12:40 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 43.04 | 0.00 |
November | 3666.66 | 06-NOV-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 19.68 | 0.00 |
December | 3946.19 | 16-DEC-13:30 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 18.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2333.83 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 | 0.00 | |
Maximum of Months | 3946.19 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 57.25 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1599.57 | 19-JAN-19:10 | 6320.16 | 3164.06 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
February | 1636.92 | 27-FEB-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 |
March | 1630.90 | 24-MAR-16:51 | 5266.80 | 1153.56 | 2047.51 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 | 0.00 |
April | 1765.85 | 28-APR-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
May | 1943.27 | 04-MAY-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
June | 2013.94 | 13-JUN-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 | 0.00 |
July | 2049.70 | 07-JUL-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.88 | 0.00 |
August | 2064.53 | 30-AUG-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.66 | 0.00 |
September | 1972.13 | 01-SEP-20:52 | 12038.40 | 5273.43 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 2.24 | 0.00 |
October | 2057.74 | 05-OCT-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 | 0.00 |
November | 1822.69 | 07-NOV-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 | 0.00 |
December | 1774.71 | 15-DEC-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1599.57 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2064.53 | 12038.40 | 5273.43 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 10.88 | 10.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1137.58 | 19-JAN-22:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 |
February | 1127.59 | 28-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.59 |
March | 1163.56 | 30-MAR-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 |
April | 1449.91 | 28-APR-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 |
May | 1695.11 | 25-MAY-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 | 0.00 |
June | 1898.75 | 28-JUN-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 20.53 | 0.00 |
July | 1944.65 | 19-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 0.00 |
August | 1864.35 | 21-AUG-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 19.56 | 0.00 |
September | 1859.22 | 10-SEP-20:00 | 190.94 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 21.45 | 0.00 |
October | 1813.61 | 06-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 | 0.00 |
November | 1476.74 | 02-NOV-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 | 0.00 |
December | 1354.32 | 15-DEC-22:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1127.59 | 190.94 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1944.65 | 254.59 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 25.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 912.77 | 01-JAN-11:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 0.00 |
February | 905.83 | 26-FEB-11:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 | 0.00 |
March | 917.62 | 24-MAR-16:51 | 856.80 | 366.93 | 624.51 | 0.00 | 0.00 | 0.00 | 0.00 | 14.41 | 0.00 |
April | 983.05 | 29-APR-10:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 | 0.00 |
May | 1046.92 | 29-MAY-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 19.27 | 0.00 |
June | 1076.88 | 17-JUN-10:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 23.39 | 0.00 |
July | 1088.85 | 08-JUL-10:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 | 0.00 |
August | 1055.16 | 06-AUG-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 21.64 | 0.00 |
September | 1092.23 | 10-SEP-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 30.05 | 0.00 |
October | 1071.53 | 07-OCT-10:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 22.28 | 0.00 |
November | 969.44 | 02-NOV-10:35 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 16.99 | 0.00 |
December | 959.48 | 16-DEC-11:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 12.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 905.83 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 0.00 | |
Maximum of Months | 1092.23 | 856.80 | 366.93 | 624.51 | 0.00 | 0.00 | 0.00 | 0.00 | 30.05 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38368.66 | 19-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 |
February | 38365.26 | 24-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 35.08 |
March | 38489.99 | 30-MAR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 34.87 |
April | 38894.62 | 21-APR-19:56 | 3528.00 | 2003.42 | 22864.00 | 198632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 |
May | 39270.25 | 04-MAY-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 10.49 | 0.00 |
June | 39412.38 | 13-JUN-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 42.58 | 0.00 |
July | 39476.19 | 07-JUL-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 35.12 | 0.00 |
August | 39330.94 | 02-AUG-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 25.41 | 0.00 |
September | 39143.94 | 01-SEP-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 39216.42 | 05-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 19.60 | 0.00 |
November | 38833.02 | 02-NOV-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 6.57 | 0.00 |
December | 38404.32 | 15-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 38365.26 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39476.19 | 3528.00 | 2003.42 | 22864.00 | 198632.88 | 0.00 | 0.00 | 0.00 | 42.58 | 35.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12911.64 | 01-JAN-11:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
February | 11908.14 | 26-FEB-11:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 33.73 | 0.00 |
March | 11970.27 | 24-MAR-16:51 | 59766.00 | 673.09 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 49.08 | 0.00 |
April | 11001.26 | 22-APR-17:20 | 20491.20 | 461.55 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 87.50 | 0.00 |
May | 11401.37 | 04-MAY-18:10 | 71719.20 | 2527.56 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 83.11 | 0.00 |
June | 11595.54 | 28-JUN-18:10 | 71719.20 | 1846.19 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 110.22 | 0.00 |
July | 11733.50 | 22-JUL-17:20 | 20491.20 | 461.55 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 134.92 | 0.00 |
August | 11865.39 | 24-AUG-18:10 | 71719.20 | 2692.02 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 123.58 | 0.00 |
September | 12487.80 | 10-SEP-10:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 128.85 | 0.00 |
October | 12570.82 | 07-OCT-10:35 | 10245.60 | 192.31 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 93.23 | 0.00 |
November | 13101.60 | 11-NOV-11:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 | 0.00 |
December | 13159.56 | 10-DEC-11:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11001.26 | 10245.60 | 192.31 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13159.56 | 71719.20 | 2692.02 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 134.92 | 5.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34385.95 | 19-JAN-22:10 | 91245.96 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.32 |
February | 33348.38 | 02-FEB-22:10 | 91245.96 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.29 |
March | 33918.32 | 24-MAR-16:51 | 177422.70 | 13351.08 | 25864.80 | 0.00 | 0.00 | 0.00 | 0.00 | 136.64 | 0.00 |
April | 34185.56 | 28-APR-21:52 | 410606.82 | 47904.21 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 |
May | 36213.08 | 12-MAY-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 86.31 | 0.00 |
June | 37652.33 | 28-JUN-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 139.46 | 0.00 |
July | 38604.25 | 07-JUL-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 172.20 | 0.00 |
August | 38898.56 | 24-AUG-22:00 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 197.46 | 0.00 |
September | 38128.53 | 10-SEP-20:10 | 81107.52 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 146.94 | 0.00 |
October | 39782.68 | 05-OCT-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 104.99 | 0.00 |
November | 37185.42 | 07-NOV-22:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 29.39 | 0.00 |
December | 36146.45 | 15-DEC-22:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 33348.38 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39782.68 | 410606.82 | 47904.21 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 197.46 | 101.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3083.79 | 10-JAN-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 |
February | 3115.71 | 13-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.47 |
March | 3099.12 | 03-MAR-19:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 |
April | 3164.20 | 10-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 |
May | 2884.15 | 31-MAY-15:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 | 0.00 |
June | 2892.68 | 20-JUN-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 0.00 |
July | 2893.81 | 27-JUL-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 | 0.00 |
August | 2894.40 | 07-AUG-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 | 0.00 |
September | 2903.33 | 20-SEP-15:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 | 0.00 |
October | 3118.97 | 27-OCT-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 |
November | 3157.36 | 22-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.22 |
December | 3108.81 | 26-DEC-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2884.15 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3164.20 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 30.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2804.90 | 18-JAN-16:12 | 583.20 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 0.00 |
February | 3010.41 | 13-FEB-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.18 |
March | 3056.72 | 20-MAR-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 |
April | 3130.52 | 10-APR-19:11 | 1247.40 | 852.35 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.53 |
May | 2949.49 | 27-MAY-18:51 | 1053.00 | 852.35 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 0.00 |
June | 2847.88 | 29-JUN-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 | 0.00 |
July | 2816.53 | 31-JUL-15:12 | 583.20 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 | 0.00 |
August | 2828.45 | 07-AUG-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 | 0.00 |
September | 3128.78 | 02-SEP-18:11 | 1170.00 | 947.05 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 |
October | 3009.10 | 27-OCT-18:31 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 |
November | 2820.96 | 06-NOV-19:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 | 0.00 |
December | 2920.73 | 26-DEC-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2804.90 | 583.20 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3130.52 | 1247.40 | 947.05 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 | 28.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 604.33 | 01-JAN-14:00 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
February | 470.09 | 02-FEB-13:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | 0.00 |
March | 405.06 | 05-MAR-13:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 0.00 |
April | 294.92 | 22-APR-13:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2.73 | 0.00 |
May | 310.97 | 04-MAY-16:20 | 0.00 | 16.67 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 | 0.00 |
June | 308.43 | 28-JUN-17:20 | 0.00 | 79.76 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 0.00 |
July | 336.23 | 19-JUL-17:20 | 0.00 | 79.76 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | 0.00 |
August | 365.23 | 30-AUG-16:20 | 0.00 | 16.67 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 | 0.00 |
September | 465.40 | 10-SEP-13:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 | 0.00 |
October | 515.17 | 13-OCT-13:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 | 0.00 |
November | 571.34 | 06-NOV-14:00 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 | 0.00 |
December | 607.68 | 10-DEC-13:40 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 294.92 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 607.68 | 0.00 | 79.76 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 | 0.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 949.97 | 03-JAN-19:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 |
February | 957.67 | 12-FEB-19:02 | 702.00 | 357.25 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 |
March | 992.38 | 20-MAR-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.66 |
April | 1019.07 | 10-APR-19:11 | 1247.40 | 535.88 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 |
May | 1004.89 | 21-MAY-08:61 | 378.00 | 233.40 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 2.69 | 0.00 |
June | 1004.04 | 26-JUN-08:61 | 252.00 | 183.39 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 0.00 |
July | 1002.76 | 08-JUL-15:12 | 324.00 | 117.89 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 0.00 |
August | 1000.90 | 17-AUG-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 0.00 |
September | 1000.52 | 03-SEP-18:02 | 702.00 | 357.25 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.74 | 0.00 |
October | 1008.14 | 27-OCT-18:31 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.25 |
November | 1001.29 | 05-NOV-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
December | 943.86 | 17-DEC-09:51 | 486.00 | 300.09 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 943.86 | 252.00 | 117.89 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1019.07 | 1247.40 | 535.88 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 11.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2703.82 | 10-JAN-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 |
February | 2811.75 | 13-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.28 |
March | 2775.72 | 03-MAR-19:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.30 |
April | 2865.67 | 10-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.66 |
May | 2701.09 | 07-MAY-08:62 | 324.00 | 318.25 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 | 0.00 |
June | 2682.38 | 11-JUN-08:62 | 324.00 | 318.25 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 8.21 | 0.00 |
July | 2685.57 | 15-JUL-08:61 | 378.00 | 371.29 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 | 0.00 |
August | 2668.09 | 24-AUG-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 13.73 | 0.00 |
September | 2708.25 | 11-SEP-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 | 0.00 |
October | 2841.26 | 27-OCT-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 |
November | 2857.89 | 22-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 |
December | 2808.59 | 26-DEC-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2668.09 | 252.00 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2865.67 | 970.20 | 590.08 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 | 30.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2537.70 | 01-JAN-09:51 | 432.00 | 424.28 | 1306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.66 |
February | 2544.12 | 26-FEB-09:51 | 432.00 | 424.28 | 1306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.11 |
March | 2771.39 | 19-MAR-08:51 | 486.00 | 477.32 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 |
April | 2809.40 | 20-APR-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 |
May | 2695.84 | 02-MAY-08:11 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | 0.00 |
June | 2772.13 | 11-JUN-08:11 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 0.00 |
July | 2632.29 | 18-JUL-08:62 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 0.00 |
August | 2617.29 | 10-AUG-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 15.07 | 0.00 |
September | 2700.31 | 22-SEP-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 |
October | 2872.35 | 01-OCT-08:51 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.44 |
November | 2620.66 | 06-NOV-09:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 |
December | 2636.19 | 17-DEC-09:51 | 486.00 | 477.32 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2537.70 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2872.35 | 831.60 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 19.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2071.73 | 01-JAN-11:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | 0.00 |
February | 2003.41 | 26-FEB-11:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 | 0.00 |
March | 2027.91 | 04-MAR-16:16 | 5281.16 | 2255.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 | 0.00 |
April | 2158.09 | 29-APR-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.39 | 0.00 |
May | 2243.09 | 29-MAY-10:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 0.00 |
June | 2301.03 | 17-JUN-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.60 | 0.00 |
July | 2320.73 | 08-JUL-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 0.00 |
August | 2279.17 | 24-AUG-18:10 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.86 | 0.00 |
September | 2335.65 | 10-SEP-10:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.46 | 0.00 |
October | 2333.56 | 07-OCT-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 0.00 |
November | 2125.91 | 07-NOV-11:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.69 | 0.00 |
December | 2123.48 | 16-DEC-11:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2003.41 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | 0.00 | |
Maximum of Months | 2335.65 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.46 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3236.31 | 10-JAN-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.87 |
February | 3275.70 | 13-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 |
March | 3260.05 | 13-MAR-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.71 |
April | 3331.22 | 10-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 |
May | 3023.05 | 27-MAY-18:02 | 702.00 | 568.30 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | 0.00 |
June | 3041.82 | 19-JUN-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 15.73 | 0.00 |
July | 3046.62 | 31-JUL-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 | 0.00 |
August | 3039.27 | 07-AUG-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 | 0.00 |
September | 3053.86 | 10-SEP-15:12 | 324.00 | 187.54 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 | 0.00 |
October | 3270.74 | 27-OCT-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 |
November | 3320.04 | 22-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 |
December | 3262.84 | 26-DEC-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3023.05 | 324.00 | 185.64 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3331.22 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 | 30.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2987.30 | 16-JAN-16:11 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.92 | 0.00 |
February | 3141.04 | 13-FEB-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 |
March | 3175.33 | 20-MAR-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 |
April | 3384.81 | 10-APR-19:11 | 1247.40 | 852.35 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.05 |
May | 3151.47 | 27-MAY-18:51 | 1053.00 | 852.35 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3.48 | 0.00 |
June | 3031.32 | 28-JUN-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 | 0.00 |
July | 2995.30 | 14-JUL-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.66 | 0.00 |
August | 2968.70 | 07-AUG-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 0.00 |
September | 3252.07 | 02-SEP-18:11 | 1170.00 | 947.05 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 |
October | 3144.36 | 27-OCT-18:31 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.91 |
November | 2955.22 | 06-NOV-19:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 0.00 |
December | 2972.92 | 26-DEC-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2955.22 | 378.00 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3384.81 | 1247.40 | 947.05 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 | 30.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1592.38 | 19-JAN-16:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 |
February | 1716.35 | 13-FEB-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 |
March | 1702.05 | 03-MAR-19:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 |
April | 1618.65 | 10-APR-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 |
May | 1600.27 | 16-MAY-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 | 0.00 |
June | 1600.90 | 29-JUN-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 | 0.00 |
July | 1603.74 | 15-JUL-18:02 | 702.00 | 357.25 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.02 | 0.00 |
August | 1605.48 | 09-AUG-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.41 | 0.00 |
September | 1616.07 | 24-SEP-15:12 | 324.00 | 117.89 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 | 0.00 |
October | 1685.20 | 27-OCT-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 |
November | 1742.55 | 22-NOV-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.11 |
December | 1604.71 | 16-DEC-16:12 | 324.00 | 117.89 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1592.38 | 324.00 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1742.55 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 | 13.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19071.23 | 19-JAN-22:53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.51 |
February | 19192.05 | 02-FEB-22:53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.65 |
March | 20940.19 | 24-MAR-16:51 | 104956.32 | 3223.64 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 31.03 | 0.00 |
April | 20727.32 | 21-APR-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 10.03 | 0.00 |
May | 21473.06 | 25-MAY-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 | 0.00 |
June | 21801.15 | 13-JUN-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 0.00 |
July | 22101.84 | 07-JUL-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 | 0.00 |
August | 21837.23 | 24-AUG-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 43.59 | 0.00 |
September | 21308.01 | 12-SEP-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 |
October | 21225.23 | 06-OCT-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.21 | 0.00 |
November | 20266.59 | 01-NOV-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 8.42 | 0.00 |
December | 19971.03 | 15-DEC-22:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19071.23 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22101.84 | 161932.61 | 11052.49 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 43.59 | 23.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20991.36 | 19-JAN-22:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.43 |
February | 20988.19 | 02-FEB-22:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 |
March | 21618.70 | 24-MAR-16:51 | 104956.32 | 3223.64 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 0.00 |
April | 21960.74 | 28-APR-21:52 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 |
May | 22873.90 | 25-MAY-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 0.00 |
June | 23195.35 | 13-JUN-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 0.00 |
July | 23487.40 | 07-JUL-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 | 0.00 |
August | 23233.81 | 24-AUG-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 43.59 | 0.00 |
September | 22257.43 | 05-SEP-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 | 0.00 |
October | 22590.49 | 05-OCT-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.95 | 0.00 |
November | 21527.96 | 01-NOV-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 | 0.00 |
December | 21109.80 | 15-DEC-22:52 | 215910.14 | 14736.65 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20988.19 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23487.40 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 43.59 | 23.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27990.28 | 01-JAN-11:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 |
February | 28293.28 | 26-FEB-11:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 11.00 | 0.00 |
March | 30058.92 | 24-MAR-16:51 | 9339.96 | 2121.06 | 102231.89 | 157449.82 | 0.00 | 0.00 | 0.00 | 15.74 | 0.00 |
April | 29256.80 | 23-APR-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 15.70 | 0.00 |
May | 29708.28 | 29-MAY-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 36.60 | 0.00 |
June | 29602.16 | 17-JUN-10:50 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 49.27 | 0.00 |
July | 29846.58 | 23-JUL-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 43.68 | 0.00 |
August | 29374.68 | 06-AUG-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 43.50 | 0.00 |
September | 30057.39 | 10-SEP-10:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 65.34 | 0.00 |
October | 29632.04 | 07-OCT-10:50 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 45.53 | 0.00 |
November | 28600.65 | 02-NOV-10:40 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 28.86 | 0.00 |
December | 28211.23 | 16-DEC-11:40 | 1601.14 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 17.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27990.28 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30058.92 | 9339.96 | 2121.06 | 102231.89 | 157449.82 | 0.00 | 0.00 | 0.00 | 65.34 | 5.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4651.01 | 01-JAN-14:10 | 1064.64 | 545.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 0.00 |
February | 4203.36 | 27-FEB-15:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 | 0.00 |
March | 3767.24 | 29-MAR-15:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 0.00 |
April | 5189.51 | 28-APR-15:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.54 | 0.00 |
May | 5812.78 | 04-MAY-15:35 | 2661.60 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.54 | 0.00 |
June | 5822.11 | 30-JUN-15:23 | 3992.40 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.87 | 0.00 |
July | 6098.60 | 22-JUL-17:03 | 6387.84 | 3273.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.09 | 0.00 |
August | 5904.06 | 30-AUG-15:50 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.40 | 0.00 |
September | 6431.82 | 10-SEP-13:50 | 532.32 | 272.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.37 | 0.00 |
October | 6227.72 | 07-OCT-13:00 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.95 | 0.00 |
November | 5288.21 | 02-NOV-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.28 | 0.00 |
December | 5045.76 | 16-DEC-13:30 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3767.24 | 532.32 | 272.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 0.00 | |
Maximum of Months | 6431.82 | 6387.84 | 3273.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.40 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.428267E+12 | 313844.41 | 04-JAN-07:19 | 0.357945E+12 | 315979.62 | 23-JAN-18:30 |
February | 0.395934E+12 | 312879.52 | 17-FEB-07:10 | 0.322217E+12 | 315929.70 | 01-FEB-18:30 |
March | 0.440783E+12 | 306741.72 | 07-MAR-19:00 | 0.351262E+12 | 312819.48 | 01-MAR-18:19 |
April | 0.480118E+12 | 321959.14 | 28-APR-19:00 | 0.331153E+12 | 303606.99 | 03-APR-17:19 |
May | 0.622058E+12 | 346129.56 | 25-MAY-18:10 | 0.332674E+12 | 295118.82 | 01-MAY-17:40 |
June | 0.618940E+12 | 362888.44 | 28-JUN-18:10 | 0.314455E+12 | 288321.54 | 01-JUN-17:30 |
July | 0.663004E+12 | 369675.46 | 18-JUL-18:10 | 0.320832E+12 | 281439.66 | 03-JUL-17:00 |
August | 0.654291E+12 | 373886.29 | 24-AUG-18:10 | 0.322284E+12 | 283664.64 | 31-AUG-17:49 |
September | 0.619194E+12 | 388470.48 | 09-SEP-18:40 | 0.317396E+12 | 290936.11 | 29-SEP-17:30 |
October | 0.584235E+12 | 365774.53 | 24-OCT-18:00 | 0.336947E+12 | 300999.67 | 31-OCT-17:30 |
November | 0.451376E+12 | 338682.85 | 02-NOV-18:10 | 0.335469E+12 | 308980.77 | 30-NOV-18:30 |
December | 0.448065E+12 | 321530.22 | 15-DEC-20:00 | 0.354144E+12 | 314445.47 | 29-DEC-18:49 |
Annual Sum or Average | 0.640627E+13 | 0.399678E+13 | ||||
Minimum of Months | 0.395934E+12 | 306741.72 | 0.314455E+12 | 281439.66 | ||
Maximum of Months | 0.663004E+12 | 388470.48 | 0.357945E+12 | 315979.62 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.467787E+11 | 0.186261E+11 | 0.140003E+12 | 0.690928E+11 | 0.480240E+11 | 0.759276E+10 | 0.298691E+11 | 0.518468E+11 | 0.00 | 0.00 | 0.463215E+10 | 0.804706E+10 | 0.00 |
February | 0.421240E+11 | 0.160869E+11 | 0.126445E+12 | 0.624065E+11 | 0.435412E+11 | 0.732641E+10 | 0.173249E+11 | 0.652798E+11 | 0.00 | 0.00 | 0.473119E+10 | 0.727159E+10 | 0.00 |
March | 0.464386E+11 | 0.167013E+11 | 0.140056E+12 | 0.690952E+11 | 0.482245E+11 | 0.811770E+10 | 0.118128E+11 | 0.823996E+11 | 0.00 | 0.00 | 0.613030E+10 | 0.804567E+10 | 0.00 |
April | 0.446773E+11 | 0.150875E+11 | 0.135446E+12 | 0.668635E+11 | 0.486441E+11 | 0.890501E+10 | 0.424472E+09 | 0.138331E+12 | 0.00 | 0.00 | 0.102922E+11 | 0.779701E+10 | 0.00 |
May | 0.459408E+11 | 0.146211E+11 | 0.140035E+12 | 0.690936E+11 | 0.545057E+11 | 0.973400E+10 | 27246443.70 | 0.255122E+12 | 0.00 | 0.00 | 0.211454E+11 | 0.804707E+10 | 0.00 |
June | 0.443217E+11 | 0.136216E+11 | 0.135537E+12 | 0.668656E+11 | 0.538302E+11 | 0.953832E+10 | 23109865.13 | 0.263454E+12 | 0.00 | 0.00 | 0.202945E+11 | 0.778858E+10 | 0.00 |
July | 0.457880E+11 | 0.143546E+11 | 0.139944E+12 | 0.690911E+11 | 0.557826E+11 | 0.100008E+11 | 16447178.81 | 0.295068E+12 | 0.00 | 0.00 | 0.211337E+11 | 0.805551E+10 | 0.00 |
August | 0.460854E+11 | 0.151393E+11 | 0.140067E+12 | 0.690950E+11 | 0.565406E+11 | 0.993527E+10 | 12545540.82 | 0.284584E+12 | 0.00 | 0.00 | 0.209979E+11 | 0.804707E+10 | 0.00 |
September | 0.448136E+11 | 0.157093E+11 | 0.135457E+12 | 0.668636E+11 | 0.538009E+11 | 0.952810E+10 | 12637615.72 | 0.261210E+12 | 0.00 | 0.00 | 0.203342E+11 | 0.779842E+10 | 0.00 |
October | 0.465438E+11 | 0.173602E+11 | 0.139992E+12 | 0.690926E+11 | 0.553274E+11 | 0.962382E+10 | 63897996.40 | 0.218379E+12 | 0.00 | 0.00 | 0.160266E+11 | 0.804566E+10 | 0.00 |
November | 0.452399E+11 | 0.177378E+11 | 0.135531E+12 | 0.668647E+11 | 0.495163E+11 | 0.876946E+10 | 0.145200E+10 | 0.107865E+12 | 0.00 | 0.00 | 0.697884E+10 | 0.778013E+10 | 0.00 |
December | 0.467811E+11 | 0.188704E+11 | 0.139944E+12 | 0.690917E+11 | 0.494038E+11 | 0.804853E+10 | 0.181903E+11 | 0.793543E+11 | 0.00 | 0.00 | 0.656545E+10 | 0.805551E+10 | 0.00 |
Annual Sum or Average | 0.545533E+12 | 0.193916E+12 | 0.164846E+13 | 0.813516E+12 | 0.617141E+12 | 0.107120E+12 | 0.792294E+11 | 0.210290E+13 | 0.00 | 0.00 | 0.159262E+12 | 0.947793E+11 | 0.00 |
Minimum of Months | 0.421240E+11 | 0.136216E+11 | 0.126445E+12 | 0.624065E+11 | 0.435412E+11 | 0.732641E+10 | 12545540.82 | 0.518468E+11 | 0.00 | 0.00 | 0.463215E+10 | 0.727159E+10 | 0.00 |
Maximum of Months | 0.467811E+11 | 0.188704E+11 | 0.140067E+12 | 0.690952E+11 | 0.565406E+11 | 0.100008E+11 | 0.298691E+11 | 0.295068E+12 | 0.00 | 0.00 | 0.211454E+11 | 0.805551E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.00 | 0.00 | 0.206027E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.00 | 0.00 | 0.185013E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.00 | 0.00 | 0.199238E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.00 | 0.00 | 0.184197E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.00 | 0.00 | 0.180695E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.00 | 0.00 | 0.167342E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.00 | 0.00 | 0.169012E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.00 | 0.00 | 0.170245E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.00 | 0.00 | 0.170425E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.00 | 0.00 | 0.185044E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.00 | 0.00 | 0.188378E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.00 | 0.00 | 0.202324E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.00 | 0.00 | 0.220794E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.00 | 0.00 | 0.167342E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.00 | 0.00 | 0.206027E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 45764.37 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 49590.83 | 02-JAN-07:19 | 30155.92 | 19-JAN-22:00 | 3817.96 | 19-JAN-22:00 | 109879.84 | 05-JAN-04:00 |
February | 45764.37 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 49590.83 | 01-FEB-07:19 | 27957.37 | 02-FEB-22:00 | 3766.39 | 24-FEB-16:49 | 106020.45 | 04-FEB-23:00 |
March | 45764.37 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 49590.83 | 13-MAR-06:19 | 27580.18 | 06-MAR-22:00 | 3868.21 | 30-MAR-18:10 | 107120.10 | 09-MAR-07:10 |
April | 45764.37 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 49590.83 | 03-APR-06:19 | 31308.41 | 28-APR-21:00 | 4056.91 | 29-APR-18:10 | 31943.96 | 18-APR-12:00 |
May | 45764.37 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 49590.22 | 19-MAY-06:19 | 33153.83 | 19-MAY-21:40 | 4210.47 | 25-MAY-18:10 | 1908.86 | 31-MAY-21:00 |
June | 45764.37 | 01-JUN-19:19 | 12338.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 49589.97 | 07-JUN-06:19 | 33637.07 | 28-JUN-21:40 | 4433.12 | 29-JUN-18:10 | 1581.85 | 07-JUN-10:50 |
July | 45764.37 | 03-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 49590.13 | 26-JUL-06:19 | 34236.49 | 07-JUL-21:19 | 4448.50 | 05-JUL-18:10 | 2042.12 | 14-JUL-08:00 |
August | 45764.37 | 01-AUG-19:19 | 12338.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 49590.83 | 28-AUG-06:19 | 37114.35 | 24-AUG-21:40 | 4500.86 | 09-AUG-18:10 | 1740.48 | 17-AUG-08:09 |
September | 45764.37 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 49590.83 | 01-SEP-06:19 | 36879.39 | 01-SEP-21:19 | 4441.44 | 09-SEP-18:10 | 2420.18 | 14-SEP-06:10 |
October | 45764.37 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 49590.83 | 02-OCT-06:19 | 38051.64 | 06-OCT-21:19 | 4395.65 | 06-OCT-19:00 | 8407.67 | 29-OCT-15:09 |
November | 45764.37 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 49590.83 | 01-NOV-06:19 | 33158.39 | 03-NOV-21:00 | 4136.63 | 02-NOV-18:10 | 35137.55 | 15-NOV-04:49 |
December | 45764.37 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 49590.83 | 01-DEC-07:19 | 32906.36 | 15-DEC-22:00 | 3950.82 | 15-DEC-20:00 | 111895.67 | 21-DEC-07:19 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45764.37 | 12338.45 | 88863.15 | 49589.97 | 27580.18 | 3766.39 | 1581.85 | |||||||
Maximum of Months | 45764.37 | 12338.45 | 88863.15 | 49590.83 | 38051.64 | 4500.86 | 111895.67 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 113911.88 | 19-JAN-22:00 | 0.00 | 0.00 | 8265.52 | 01-JAN-13:09 | 4751.13 | 02-JAN-19:49 | 0.00 |
February | 106380.02 | 24-FEB-16:19 | 0.00 | 0.00 | 8265.52 | 01-FEB-13:30 | 4751.13 | 27-FEB-07:40 | 0.00 |
March | 107267.49 | 07-MAR-19:00 | 0.00 | 0.00 | 8265.52 | 04-MAR-13:00 | 4751.13 | 27-MAR-06:40 | 0.00 |
April | 152351.72 | 28-APR-15:00 | 0.00 | 0.00 | 8265.52 | 01-APR-04:30 | 4751.13 | 17-APR-06:40 | 0.00 |
May | 156609.15 | 25-MAY-18:10 | 0.00 | 0.00 | 8265.52 | 01-MAY-00:10 | 4751.13 | 30-MAY-06:40 | 0.00 |
June | 172453.45 | 28-JUN-18:10 | 0.00 | 0.00 | 8265.52 | 01-JUN-00:10 | 4751.12 | 05-JUN-06:30 | 0.00 |
July | 188228.97 | 22-JUL-16:10 | 0.00 | 0.00 | 8265.52 | 01-JUL-00:10 | 4751.13 | 03-JUL-06:40 | 0.00 |
August | 183293.93 | 24-AUG-18:10 | 0.00 | 0.00 | 8265.52 | 01-AUG-00:10 | 4751.13 | 14-AUG-06:40 | 0.00 |
September | 196711.45 | 10-SEP-15:20 | 0.00 | 0.00 | 8265.52 | 01-SEP-00:10 | 4751.13 | 18-SEP-06:40 | 0.00 |
October | 168957.73 | 07-OCT-15:30 | 0.00 | 0.00 | 8265.52 | 01-OCT-00:10 | 4751.13 | 02-OCT-06:40 | 0.00 |
November | 144079.94 | 02-NOV-15:20 | 0.00 | 0.00 | 8265.52 | 01-NOV-00:10 | 4751.13 | 20-NOV-07:40 | 0.00 |
December | 124014.39 | 16-DEC-22:00 | 0.00 | 0.00 | 8265.52 | 02-DEC-13:09 | 4751.12 | 18-DEC-07:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 106380.02 | 0.00 | 0.00 | 8265.52 | 4751.12 | 0.00 | |||
Maximum of Months | 196711.45 | 0.00 | 0.00 | 8265.52 | 4751.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 313844.41 | 04-JAN-07:19 | 25474.78 | 88863.15 | 12338.45 | 49590.83 | 19691.20 | 2198.50 | 105793.81 | 2330.59 | 0.00 |
February | 312879.52 | 17-FEB-07:10 | 25474.78 | 88863.15 | 12338.45 | 49586.49 | 19812.02 | 2197.67 | 104125.36 | 2029.24 | 0.00 |
March | 306741.72 | 07-MAR-19:00 | 40691.94 | 77265.07 | 12338.45 | 28151.71 | 24431.02 | 3771.75 | 0.00 | 107267.49 | 0.00 |
April | 321959.14 | 28-APR-19:00 | 45764.37 | 86131.51 | 12338.45 | 10977.17 | 25117.47 | 3978.68 | 0.00 | 125597.46 | 0.00 |
May | 346129.56 | 25-MAY-18:10 | 36855.78 | 77265.07 | 0.00 | 28142.59 | 28339.33 | 4210.47 | 0.00 | 156609.15 | 0.00 |
June | 362888.44 | 28-JUN-18:10 | 36833.67 | 77265.07 | 0.00 | 28142.59 | 29099.62 | 4387.04 | 0.00 | 172453.45 | 0.00 |
July | 369675.46 | 18-JUL-18:10 | 36820.10 | 77265.07 | 0.00 | 28142.59 | 29563.04 | 4352.03 | 0.00 | 179188.73 | 0.00 |
August | 373886.29 | 24-AUG-18:10 | 37392.61 | 77265.07 | 0.00 | 28142.60 | 28662.91 | 4421.94 | 0.00 | 183293.93 | 0.00 |
September | 388470.48 | 09-SEP-18:40 | 38103.40 | 74342.86 | 12338.45 | 28092.99 | 27529.05 | 4331.41 | 0.00 | 189434.37 | 0.00 |
October | 365774.53 | 24-OCT-18:00 | 40691.94 | 77265.07 | 12338.45 | 28151.71 | 29067.55 | 4284.58 | 0.00 | 159629.87 | 0.00 |
November | 338682.85 | 02-NOV-18:10 | 40691.94 | 77265.07 | 12338.45 | 28144.63 | 27856.88 | 4136.63 | 0.00 | 133540.68 | 0.00 |
December | 321530.22 | 15-DEC-20:00 | 45764.37 | 86131.51 | 12338.45 | 10977.17 | 26683.01 | 3950.82 | 0.00 | 123630.20 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 306741.72 | 25474.78 | 74342.86 | 0.00 | 10977.17 | 19691.20 | 2197.67 | 0.00 | 2029.24 | 0.00 | |
Maximum of Months | 388470.48 | 45764.37 | 88863.15 | 12338.45 | 49590.83 | 29563.04 | 4421.94 | 105793.81 | 189434.37 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 0.00 | 0.00 | 214776.90 | 18-JAN-21:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 0.00 | 0.00 | 214629.74 | 01-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 0.00 | 0.00 | 211123.45 | 01-MAR-21:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 0.00 | 0.00 | 202488.74 | 03-APR-20:19 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 0.00 | 0.00 | 193669.90 | 01-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 0.00 | 0.00 | 184523.29 | 01-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 0.00 | 0.00 | 179376.18 | 03-JUL-20:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 0.00 | 0.00 | 181823.22 | 31-AUG-20:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 0.00 | 0.00 | 187999.29 | 29-SEP-20:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 0.00 | 0.00 | 198181.31 | 31-OCT-20:30 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 0.00 | 0.00 | 205870.24 | 30-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 0.00 | 0.00 | 213179.21 | 27-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 104248.32 | 0.00 | 0.00 | 0.00 | 179376.18 | 0.00 | ||
Maximum of Months | 104248.32 | 0.00 | 0.00 | 0.00 | 214776.90 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.70 | 1.00 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.76 | 2.00 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.84 | 2.17 | 21.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.82 | 0.33 | 21.82 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
Annual Sum or Average | 0.00 | 0.00 | 8.67 | 21.76 | 8.67 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.84 | 2.17 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
February | 0.17 | 20.11 | 0.17 | 20.11 | 0.00 | 20.11 | 0.00 | 20.11 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.71 | 1.67 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.73 | 3.00 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.76 | 1.17 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.72 | 1.33 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.81 | 1.83 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.79 | 1.50 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.47 | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Annual Sum or Average | 0.67 | 20.40 | 0.67 | 20.40 | 11.00 | 21.61 | 11.00 | 21.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.54 | 0.33 | 20.54 | 3.00 | 21.81 | 3.00 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.74 | 1.17 | 21.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.75 | 3.83 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 21.70 | 8.17 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 21.73 | 9.17 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 21.73 | 8.00 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 21.73 | 8.00 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.80 | 7.00 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.80 | 4.50 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.77 | 1.00 | 21.77 |
Annual Sum or Average | 0.00 | 0.00 | 51.50 | 21.74 | 51.50 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 21.80 | 9.17 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 21.71 | 1.33 | 21.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.79 | 0.67 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.88 | 0.33 | 21.88 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.79 | 0.83 | 21.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.97 | 1.83 | 21.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 22.08 | 3.50 | 22.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.90 | 2.00 | 21.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.01 | 1.67 | 22.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.97 | 0.83 | 21.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.92 | 2.33 | 21.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 22.19 | 3.33 | 22.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.11 | 1.17 | 22.11 |
December | 0.17 | 20.49 | 0.17 | 20.49 | 0.67 | 21.47 | 0.67 | 21.66 |
Annual Sum or Average | 0.17 | 20.49 | 0.17 | 20.49 | 19.33 | 21.98 | 19.33 | 21.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.47 | 0.33 | 21.66 |
Maximum of Months | 0.17 | 20.49 | 0.17 | 20.49 | 3.50 | 22.19 | 3.50 | 22.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
February | 0.17 | 20.31 | 0.17 | 20.31 | 0.67 | 21.27 | 0.67 | 21.46 |
March | 0.17 | 20.40 | 0.17 | 20.40 | 0.17 | 20.83 | 0.17 | 21.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.79 | 1.17 | 21.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.79 | 2.17 | 21.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.79 | 2.50 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.83 | 1.50 | 21.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.78 | 2.33 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.87 | 2.00 | 21.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.83 | 3.00 | 21.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
December | 0.33 | 20.36 | 0.33 | 20.36 | 0.50 | 20.95 | 0.50 | 21.19 |
Annual Sum or Average | 0.67 | 20.36 | 0.67 | 20.36 | 16.67 | 21.70 | 16.67 | 21.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 20.83 | 0.17 | 21.05 |
Maximum of Months | 0.33 | 20.40 | 0.33 | 20.40 | 3.00 | 21.87 | 3.00 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.33 | 0.50 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
February | 0.50 | 20.26 | 0.50 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
March | 0.17 | 20.40 | 0.17 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.80 | 1.33 | 21.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.80 | 2.83 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.81 | 3.83 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.84 | 2.17 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.75 | 2.83 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.84 | 2.50 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.82 | 1.67 | 21.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.34 | 0.50 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Annual Sum or Average | 1.67 | 20.32 | 1.67 | 20.32 | 17.17 | 21.57 | 17.17 | 21.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.40 | 0.50 | 20.40 | 3.83 | 21.84 | 3.83 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.79 | 2.17 | 21.79 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.76 | 1.83 | 21.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.72 | 1.50 | 21.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.75 | 2.00 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.84 | 2.50 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.87 | 4.50 | 21.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.79 | 3.00 | 21.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.83 | 3.00 | 21.83 |
Annual Sum or Average | 0.00 | 0.00 | 22.00 | 21.80 | 22.00 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.87 | 4.50 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.66 | 0.17 | 24.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.66 | 0.17 | 24.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.66 | 0.17 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 323.00 | 23.68 | 124.83 | 23.74 | 0.00 | 23.74 |
February | 609.33 | 23.09 | 19.00 | 23.12 | 0.00 | 23.12 |
March | 743.67 | 22.60 | 0.00 | 22.60 | 0.00 | 22.60 |
April | 720.00 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
May | 744.00 | 22.42 | 0.00 | 22.42 | 0.00 | 22.42 |
June | 720.00 | 22.66 | 0.00 | 22.66 | 0.00 | 22.66 |
July | 432.50 | 23.04 | 8.67 | 23.05 | 0.00 | 23.05 |
August | 15.83 | 23.21 | 470.17 | 23.96 | 0.00 | 23.96 |
September | 0.00 | 0.00 | 504.67 | 23.98 | 0.00 | 23.98 |
October | 40.00 | 23.89 | 452.83 | 23.98 | 0.00 | 23.98 |
November | 86.50 | 23.85 | 316.17 | 23.95 | 0.00 | 23.95 |
December | 179.67 | 23.80 | 211.00 | 23.90 | 0.00 | 23.90 |
Annual Sum or Average | 4614.50 | 22.79 | 2107.33 | 23.16 | 0.00 | 23.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.22 | 0.00 | 22.22 |
Maximum of Months | 744.00 | 23.89 | 504.67 | 23.98 | 0.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 465.33 | 22.14 | 170.33 | 22.60 | 4.17 | 22.59 |
February | 387.00 | 22.25 | 236.83 | 22.81 | 16.50 | 22.76 |
March | 442.50 | 22.08 | 215.00 | 22.63 | 7.83 | 22.61 |
April | 286.00 | 22.63 | 319.17 | 23.29 | 0.00 | 23.29 |
May | 10.17 | 23.62 | 728.67 | 23.91 | 7.50 | 23.91 |
June | 14.50 | 23.81 | 709.33 | 23.95 | 14.00 | 23.95 |
July | 20.83 | 23.85 | 737.33 | 23.96 | 20.83 | 23.96 |
August | 10.17 | 23.90 | 744.00 | 23.97 | 10.17 | 23.97 |
September | 7.17 | 23.92 | 708.00 | 23.94 | 7.17 | 23.94 |
October | 84.67 | 22.95 | 624.83 | 23.85 | 7.50 | 23.85 |
November | 249.00 | 22.70 | 351.00 | 23.42 | 0.00 | 23.42 |
December | 391.83 | 22.14 | 284.67 | 22.87 | 5.00 | 22.85 |
Annual Sum or Average | 2369.17 | 22.34 | 5829.17 | 23.46 | 100.67 | 23.46 |
Minimum of Months | 7.17 | 22.08 | 170.33 | 22.60 | 0.00 | 22.59 |
Maximum of Months | 465.33 | 23.92 | 744.00 | 23.97 | 20.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 675.50 | 22.32 | 25.83 | 22.37 | 0.00 | 22.37 |
February | 556.00 | 22.34 | 53.83 | 22.46 | 0.00 | 22.46 |
March | 623.83 | 22.32 | 37.67 | 22.40 | 0.00 | 22.40 |
April | 485.50 | 22.59 | 134.83 | 22.84 | 0.00 | 22.84 |
May | 269.33 | 22.78 | 342.17 | 23.33 | 0.00 | 23.33 |
June | 213.67 | 22.83 | 390.67 | 23.45 | 0.00 | 23.45 |
July | 190.83 | 22.85 | 415.83 | 23.51 | 0.00 | 23.51 |
August | 169.67 | 22.88 | 426.67 | 23.55 | 0.00 | 23.55 |
September | 182.83 | 22.84 | 380.67 | 23.48 | 0.00 | 23.48 |
October | 235.00 | 22.86 | 321.17 | 23.41 | 0.00 | 23.41 |
November | 504.67 | 22.72 | 100.17 | 22.89 | 0.00 | 22.89 |
December | 596.50 | 22.41 | 75.33 | 22.55 | 0.00 | 22.55 |
Annual Sum or Average | 4703.33 | 22.54 | 2704.83 | 23.00 | 0.00 | 23.00 |
Minimum of Months | 169.67 | 22.32 | 25.83 | 22.37 | 0.00 | 22.37 |
Maximum of Months | 675.50 | 22.88 | 426.67 | 23.55 | 0.00 | 23.55 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 505.67 | 23.45 | 125.50 | 23.55 | 13.67 | 23.55 |
February | 347.67 | 23.44 | 176.83 | 23.63 | 23.33 | 23.64 |
March | 350.17 | 23.55 | 176.33 | 23.70 | 0.00 | 23.70 |
April | 118.50 | 23.99 | 333.50 | 24.00 | 0.00 | 24.00 |
May | 0.00 | 0.00 | 737.17 | 24.00 | 0.00 | 24.00 |
June | 0.00 | 0.00 | 713.00 | 24.00 | 0.00 | 24.00 |
July | 0.00 | 0.00 | 744.00 | 24.00 | 0.00 | 24.00 |
August | 0.00 | 0.00 | 744.00 | 24.00 | 0.00 | 24.00 |
September | 0.00 | 0.00 | 720.00 | 24.00 | 0.00 | 24.00 |
October | 77.17 | 24.00 | 544.67 | 24.00 | 0.00 | 24.00 |
November | 222.17 | 23.97 | 233.00 | 23.98 | 0.00 | 23.98 |
December | 396.00 | 23.59 | 184.00 | 23.72 | 2.17 | 23.72 |
Annual Sum or Average | 2017.33 | 23.60 | 5432.00 | 23.89 | 39.17 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 125.50 | 23.55 | 0.00 | 23.55 |
Maximum of Months | 505.67 | 24.00 | 744.00 | 24.00 | 23.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
February | 672.00 | 21.42 | 6.67 | 21.42 | 6.67 | 21.42 |
March | 744.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
April | 720.00 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
May | 744.00 | 22.68 | 0.00 | 22.68 | 0.00 | 22.68 |
June | 707.50 | 22.87 | 0.00 | 22.87 | 0.00 | 22.87 |
July | 708.00 | 22.92 | 0.00 | 22.92 | 0.00 | 22.92 |
August | 736.50 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
September | 714.33 | 22.75 | 0.00 | 22.75 | 0.00 | 22.75 |
October | 743.33 | 22.59 | 0.00 | 22.59 | 0.00 | 22.59 |
November | 720.00 | 21.88 | 0.00 | 21.88 | 0.00 | 21.88 |
December | 744.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
Annual Sum or Average | 8697.67 | 22.19 | 6.67 | 22.19 | 6.67 | 22.19 |
Minimum of Months | 672.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
Maximum of Months | 744.00 | 22.92 | 6.67 | 22.92 | 6.67 | 22.92 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 313.83 | 24.00 | 744.00 | 24.00 | 313.83 | 24.00 |
February | 342.67 | 24.00 | 672.00 | 24.00 | 342.67 | 24.00 |
March | 388.83 | 24.00 | 744.00 | 24.00 | 388.83 | 24.00 |
April | 502.50 | 24.00 | 720.00 | 24.00 | 502.50 | 24.00 |
May | 637.67 | 24.00 | 744.00 | 24.00 | 637.67 | 24.00 |
June | 624.33 | 24.00 | 720.00 | 24.00 | 624.33 | 24.00 |
July | 654.00 | 24.00 | 744.00 | 24.00 | 654.00 | 24.00 |
August | 646.17 | 24.00 | 744.00 | 24.00 | 646.17 | 24.00 |
September | 618.83 | 24.00 | 720.00 | 24.00 | 618.83 | 24.00 |
October | 572.83 | 24.00 | 744.00 | 24.00 | 572.83 | 24.00 |
November | 404.33 | 24.00 | 720.00 | 24.00 | 404.33 | 24.00 |
December | 368.00 | 24.00 | 744.00 | 24.00 | 368.00 | 24.00 |
Annual Sum or Average | 6074.00 | 24.00 | 8760.00 | 24.00 | 6074.00 | 24.00 |
Minimum of Months | 313.83 | 24.00 | 672.00 | 24.00 | 313.83 | 24.00 |
Maximum of Months | 654.00 | 24.00 | 744.00 | 24.00 | 654.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 625.83 | 22.02 | 123.33 | 22.21 | 57.00 | 22.27 |
February | 537.67 | 22.03 | 167.33 | 22.26 | 90.17 | 22.34 |
March | 659.33 | 21.90 | 112.17 | 22.05 | 84.17 | 22.14 |
April | 653.17 | 22.02 | 145.17 | 22.20 | 130.50 | 22.32 |
May | 600.83 | 22.33 | 250.33 | 22.61 | 209.00 | 22.75 |
June | 562.83 | 22.37 | 264.83 | 22.67 | 206.67 | 22.81 |
July | 512.33 | 22.44 | 299.17 | 22.76 | 202.67 | 22.90 |
August | 473.00 | 22.60 | 337.33 | 22.89 | 216.83 | 23.02 |
September | 430.33 | 22.61 | 374.33 | 22.89 | 205.00 | 23.00 |
October | 344.00 | 22.79 | 444.33 | 23.07 | 158.50 | 23.16 |
November | 473.00 | 22.39 | 230.83 | 22.68 | 87.33 | 22.75 |
December | 548.00 | 22.08 | 191.50 | 22.40 | 62.50 | 22.47 |
Annual Sum or Average | 6420.33 | 22.26 | 2940.67 | 22.56 | 1710.33 | 22.68 |
Minimum of Months | 344.00 | 21.90 | 112.17 | 22.05 | 57.00 | 22.14 |
Maximum of Months | 659.33 | 22.79 | 444.33 | 23.07 | 216.83 | 23.16 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 673.50 | 22.66 | 89.50 | 22.77 | 65.00 | 22.84 |
February | 583.67 | 22.68 | 134.33 | 22.85 | 104.33 | 22.94 |
March | 663.00 | 22.58 | 145.50 | 22.76 | 108.50 | 22.85 |
April | 595.17 | 22.79 | 216.17 | 23.02 | 169.67 | 23.13 |
May | 537.50 | 23.16 | 385.50 | 23.42 | 258.50 | 23.52 |
June | 485.00 | 23.23 | 393.50 | 23.50 | 245.00 | 23.59 |
July | 459.83 | 23.31 | 422.00 | 23.56 | 256.00 | 23.64 |
August | 414.50 | 23.39 | 426.67 | 23.62 | 244.17 | 23.69 |
September | 392.50 | 23.42 | 416.00 | 23.62 | 243.83 | 23.69 |
October | 332.83 | 23.40 | 415.17 | 23.60 | 187.17 | 23.67 |
November | 475.17 | 23.00 | 201.67 | 23.21 | 104.67 | 23.28 |
December | 577.83 | 22.75 | 147.00 | 22.94 | 81.50 | 23.03 |
Annual Sum or Average | 6190.50 | 22.97 | 3393.00 | 23.26 | 2068.33 | 23.36 |
Minimum of Months | 332.83 | 22.58 | 89.50 | 22.76 | 65.00 | 22.84 |
Maximum of Months | 673.50 | 23.42 | 426.67 | 23.62 | 258.50 | 23.69 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 723.67 | 21.53 | 14.50 | 21.53 | 14.50 | 21.53 |
February | 635.67 | 21.53 | 25.17 | 21.51 | 25.17 | 21.50 |
March | 716.83 | 21.53 | 15.83 | 21.51 | 15.83 | 21.49 |
April | 664.83 | 21.61 | 2.50 | 21.62 | 2.50 | 21.62 |
May | 647.00 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
June | 604.50 | 21.51 | 0.17 | 21.51 | 0.00 | 21.51 |
July | 616.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
August | 607.50 | 21.46 | 0.33 | 21.46 | 0.00 | 21.46 |
September | 604.83 | 21.51 | 4.83 | 21.52 | 3.33 | 21.53 |
October | 627.67 | 21.50 | 2.33 | 21.51 | 0.83 | 21.51 |
November | 669.33 | 21.62 | 1.17 | 21.62 | 1.17 | 21.62 |
December | 703.33 | 21.50 | 15.67 | 21.50 | 15.67 | 21.50 |
Annual Sum or Average | 7821.17 | 21.53 | 82.50 | 21.53 | 79.00 | 21.53 |
Minimum of Months | 604.50 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
Maximum of Months | 723.67 | 21.62 | 25.17 | 21.62 | 25.17 | 21.62 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 732.00 | 21.47 | 83.83 | 21.48 | 81.33 | 21.48 |
February | 632.83 | 21.63 | 93.50 | 21.66 | 83.17 | 21.66 |
March | 702.50 | 21.76 | 74.00 | 21.84 | 62.83 | 21.86 |
April | 608.17 | 22.00 | 71.17 | 22.22 | 36.00 | 22.29 |
May | 633.33 | 21.67 | 12.83 | 21.72 | 6.67 | 21.74 |
June | 594.00 | 21.56 | 12.00 | 21.61 | 7.33 | 21.63 |
July | 612.33 | 21.54 | 8.83 | 21.59 | 4.50 | 21.62 |
August | 616.67 | 21.62 | 21.67 | 21.70 | 19.17 | 21.76 |
September | 611.33 | 21.82 | 62.17 | 22.01 | 54.00 | 22.13 |
October | 639.33 | 21.82 | 34.83 | 21.92 | 28.67 | 21.98 |
November | 684.83 | 21.89 | 26.83 | 21.95 | 23.17 | 21.99 |
December | 713.33 | 21.59 | 70.17 | 21.61 | 69.17 | 21.63 |
Annual Sum or Average | 7780.67 | 21.69 | 571.83 | 21.77 | 476.00 | 21.81 |
Minimum of Months | 594.00 | 21.47 | 8.83 | 21.48 | 4.50 | 21.48 |
Maximum of Months | 732.00 | 22.00 | 93.50 | 22.22 | 83.17 | 22.29 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.43 | 35.67 | 21.47 | 35.67 | 21.51 |
February | 672.00 | 21.61 | 30.33 | 21.61 | 30.33 | 21.62 |
March | 743.67 | 21.75 | 32.00 | 21.81 | 32.00 | 21.86 |
April | 719.17 | 22.09 | 29.83 | 22.14 | 29.83 | 22.19 |
May | 743.50 | 21.87 | 4.67 | 21.88 | 4.67 | 21.89 |
June | 718.83 | 21.83 | 7.17 | 21.85 | 6.67 | 21.86 |
July | 742.83 | 21.81 | 4.83 | 21.83 | 4.33 | 21.85 |
August | 743.67 | 21.86 | 20.50 | 21.90 | 20.50 | 21.94 |
September | 719.33 | 21.98 | 55.17 | 22.08 | 55.00 | 22.17 |
October | 744.00 | 21.93 | 32.17 | 21.98 | 32.17 | 22.03 |
November | 720.00 | 21.80 | 18.00 | 21.83 | 18.00 | 21.86 |
December | 744.00 | 21.59 | 39.83 | 21.64 | 39.83 | 21.68 |
Annual Sum or Average | 8755.00 | 21.80 | 310.17 | 21.84 | 309.00 | 21.87 |
Minimum of Months | 672.00 | 21.43 | 4.67 | 21.47 | 4.33 | 21.51 |
Maximum of Months | 744.00 | 22.09 | 55.17 | 22.14 | 55.00 | 22.19 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 731.67 | 21.61 | 11.50 | 21.62 | 11.33 | 21.62 |
February | 656.50 | 21.63 | 21.33 | 21.62 | 21.33 | 21.61 |
March | 721.33 | 21.60 | 14.00 | 21.58 | 14.00 | 21.57 |
April | 662.00 | 21.64 | 1.33 | 21.64 | 1.33 | 21.65 |
May | 595.83 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
June | 554.17 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
July | 574.33 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
August | 580.67 | 21.38 | 0.00 | 21.38 | 0.00 | 21.38 |
September | 592.83 | 21.48 | 3.67 | 21.49 | 3.00 | 21.50 |
October | 615.67 | 21.47 | 0.67 | 21.48 | 0.67 | 21.48 |
November | 682.17 | 21.68 | 0.83 | 21.68 | 0.67 | 21.69 |
December | 717.00 | 21.56 | 17.00 | 21.55 | 16.83 | 21.55 |
Annual Sum or Average | 7684.17 | 21.53 | 70.33 | 21.53 | 69.17 | 21.52 |
Minimum of Months | 554.17 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
Maximum of Months | 731.67 | 21.68 | 21.33 | 21.68 | 21.33 | 21.69 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.17 | 21.50 | 62.33 | 21.53 | 61.33 | 21.56 |
February | 668.67 | 21.72 | 73.50 | 21.72 | 72.67 | 21.73 |
March | 721.17 | 21.87 | 61.33 | 21.94 | 56.17 | 21.99 |
April | 634.17 | 22.12 | 50.33 | 22.27 | 35.50 | 22.36 |
May | 574.33 | 21.52 | 24.67 | 21.64 | 6.00 | 21.67 |
June | 539.50 | 21.40 | 16.17 | 21.49 | 7.50 | 21.53 |
July | 564.67 | 21.40 | 7.50 | 21.44 | 4.50 | 21.47 |
August | 580.50 | 21.52 | 21.50 | 21.61 | 19.00 | 21.68 |
September | 584.67 | 21.77 | 58.50 | 21.96 | 51.83 | 22.10 |
October | 635.50 | 21.84 | 33.83 | 21.96 | 28.00 | 22.04 |
November | 703.33 | 21.98 | 25.50 | 22.05 | 22.50 | 22.10 |
December | 739.00 | 21.60 | 77.33 | 21.62 | 74.50 | 21.63 |
Annual Sum or Average | 7687.67 | 21.70 | 512.50 | 21.78 | 439.50 | 21.83 |
Minimum of Months | 539.50 | 21.40 | 7.50 | 21.44 | 4.50 | 21.47 |
Maximum of Months | 742.17 | 22.12 | 77.33 | 22.27 | 74.50 | 22.36 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.72 | 4.00 | 21.72 | 4.00 | 21.73 |
February | 672.00 | 21.84 | 3.83 | 21.84 | 3.83 | 21.85 |
March | 744.00 | 21.97 | 4.83 | 21.98 | 4.83 | 21.98 |
April | 720.00 | 22.52 | 28.67 | 22.53 | 28.67 | 22.55 |
May | 716.50 | 23.16 | 110.67 | 23.18 | 110.67 | 23.18 |
June | 627.50 | 23.27 | 117.00 | 23.29 | 117.00 | 23.30 |
July | 567.50 | 23.32 | 122.67 | 23.35 | 122.67 | 23.36 |
August | 632.17 | 23.30 | 123.17 | 23.31 | 123.17 | 23.33 |
September | 609.17 | 23.24 | 113.83 | 23.26 | 112.33 | 23.27 |
October | 565.67 | 23.11 | 78.50 | 23.15 | 75.00 | 23.18 |
November | 720.00 | 22.52 | 27.50 | 22.54 | 27.50 | 22.55 |
December | 744.00 | 22.02 | 11.17 | 22.03 | 11.17 | 22.04 |
Annual Sum or Average | 8062.50 | 22.62 | 745.83 | 22.68 | 740.83 | 22.73 |
Minimum of Months | 565.67 | 21.72 | 3.83 | 21.72 | 3.83 | 21.73 |
Maximum of Months | 744.00 | 23.32 | 123.17 | 23.35 | 123.17 | 23.36 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 712.00 | 21.45 | 60.83 | 21.42 | 60.83 | 21.40 |
February | 622.50 | 21.45 | 58.33 | 21.43 | 57.33 | 21.41 |
March | 696.83 | 21.43 | 54.17 | 21.40 | 54.17 | 21.37 |
April | 633.67 | 21.52 | 10.17 | 21.54 | 8.67 | 21.55 |
May | 612.00 | 21.47 | 7.50 | 21.49 | 0.00 | 21.49 |
June | 565.17 | 21.39 | 11.17 | 21.43 | 1.00 | 21.43 |
July | 588.83 | 21.40 | 9.33 | 21.43 | 0.00 | 21.43 |
August | 584.33 | 21.39 | 9.67 | 21.42 | 1.50 | 21.42 |
September | 581.00 | 21.44 | 23.17 | 21.50 | 7.67 | 21.52 |
October | 612.00 | 21.44 | 24.83 | 21.51 | 9.33 | 21.54 |
November | 652.83 | 21.55 | 8.83 | 21.57 | 5.17 | 21.58 |
December | 690.33 | 21.41 | 51.83 | 21.40 | 50.33 | 21.38 |
Annual Sum or Average | 7551.50 | 21.45 | 329.83 | 21.46 | 256.00 | 21.46 |
Minimum of Months | 565.17 | 21.39 | 7.50 | 21.40 | 0.00 | 21.37 |
Maximum of Months | 712.00 | 21.55 | 60.83 | 21.57 | 60.83 | 21.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 727.17 | 21.37 | 171.00 | 21.34 | 169.17 | 21.31 |
February | 619.00 | 21.53 | 158.00 | 21.57 | 143.83 | 21.55 |
March | 679.67 | 21.66 | 136.17 | 21.75 | 116.00 | 21.76 |
April | 573.17 | 21.90 | 102.67 | 22.22 | 57.33 | 22.31 |
May | 604.17 | 21.60 | 28.83 | 21.69 | 19.50 | 21.74 |
June | 556.50 | 21.44 | 25.50 | 21.54 | 11.50 | 21.58 |
July | 584.00 | 21.47 | 18.83 | 21.56 | 5.67 | 21.60 |
August | 586.17 | 21.53 | 33.83 | 21.65 | 27.33 | 21.74 |
September | 582.50 | 21.74 | 78.83 | 21.97 | 65.50 | 22.11 |
October | 618.67 | 21.73 | 50.50 | 21.85 | 42.33 | 21.93 |
November | 677.17 | 21.81 | 46.67 | 21.88 | 43.17 | 21.93 |
December | 706.33 | 21.48 | 144.67 | 21.47 | 143.67 | 21.46 |
Annual Sum or Average | 7514.50 | 21.60 | 995.50 | 21.70 | 845.00 | 21.73 |
Minimum of Months | 556.50 | 21.37 | 18.83 | 21.34 | 5.67 | 21.31 |
Maximum of Months | 727.17 | 21.90 | 171.00 | 22.22 | 169.17 | 22.31 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 675.83 | 21.56 | 15.67 | 21.59 | 6.17 | 21.60 |
February | 598.17 | 21.53 | 14.50 | 21.54 | 11.50 | 21.53 |
March | 697.17 | 21.52 | 18.17 | 21.52 | 18.17 | 21.51 |
April | 667.83 | 21.62 | 7.00 | 21.63 | 7.00 | 21.64 |
May | 670.83 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
June | 641.67 | 21.61 | 0.83 | 21.61 | 0.83 | 21.62 |
July | 655.33 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
August | 636.50 | 21.54 | 1.00 | 21.55 | 1.00 | 21.55 |
September | 616.50 | 21.55 | 12.17 | 21.58 | 7.00 | 21.59 |
October | 608.83 | 21.46 | 32.67 | 21.55 | 7.00 | 21.57 |
November | 606.67 | 21.49 | 24.50 | 21.56 | 2.50 | 21.57 |
December | 651.17 | 21.48 | 29.50 | 21.54 | 8.83 | 21.55 |
Annual Sum or Average | 7726.50 | 21.55 | 156.00 | 21.57 | 70.00 | 21.58 |
Minimum of Months | 598.17 | 21.46 | 0.00 | 21.52 | 0.00 | 21.51 |
Maximum of Months | 697.17 | 21.63 | 32.67 | 21.63 | 18.17 | 21.64 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 693.17 | 22.12 | 79.00 | 22.25 | 60.67 | 22.33 |
February | 590.67 | 22.21 | 126.17 | 22.42 | 93.50 | 22.53 |
March | 610.17 | 22.27 | 150.50 | 22.50 | 88.83 | 22.60 |
April | 457.50 | 22.53 | 275.83 | 22.87 | 137.17 | 22.98 |
May | 334.17 | 23.06 | 442.67 | 23.30 | 206.67 | 23.39 |
June | 279.50 | 23.23 | 475.67 | 23.37 | 196.17 | 23.45 |
July | 276.17 | 23.22 | 490.17 | 23.37 | 189.00 | 23.45 |
August | 307.67 | 23.12 | 460.00 | 23.34 | 198.17 | 23.43 |
September | 347.67 | 22.95 | 415.17 | 23.23 | 194.17 | 23.33 |
October | 417.00 | 22.65 | 346.50 | 23.03 | 151.17 | 23.14 |
November | 550.83 | 22.33 | 156.67 | 22.58 | 88.50 | 22.69 |
December | 636.83 | 22.20 | 105.17 | 22.37 | 63.33 | 22.46 |
Annual Sum or Average | 5501.33 | 22.53 | 3523.50 | 22.89 | 1667.33 | 23.01 |
Minimum of Months | 276.17 | 22.12 | 79.00 | 22.25 | 60.67 | 22.33 |
Maximum of Months | 693.17 | 23.23 | 490.17 | 23.37 | 206.67 | 23.45 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 608.17 | 22.33 | 108.83 | 22.51 | 61.17 | 22.60 |
February | 497.00 | 22.44 | 178.67 | 22.71 | 94.50 | 22.82 |
March | 482.67 | 22.48 | 210.50 | 22.79 | 90.33 | 22.89 |
April | 314.67 | 22.83 | 377.83 | 23.17 | 136.67 | 23.26 |
May | 215.50 | 23.71 | 601.83 | 23.50 | 195.33 | 23.58 |
June | 191.50 | 23.82 | 621.33 | 23.52 | 182.17 | 23.59 |
July | 188.67 | 23.81 | 632.33 | 23.52 | 176.00 | 23.60 |
August | 202.50 | 23.77 | 616.17 | 23.52 | 186.83 | 23.60 |
September | 218.83 | 23.55 | 547.33 | 23.48 | 183.00 | 23.55 |
October | 275.17 | 23.03 | 450.83 | 23.32 | 142.17 | 23.40 |
November | 435.67 | 22.50 | 238.67 | 22.86 | 86.00 | 22.95 |
December | 526.17 | 22.37 | 156.83 | 22.62 | 61.67 | 22.71 |
Annual Sum or Average | 4156.50 | 22.81 | 4741.17 | 23.15 | 1595.83 | 23.25 |
Minimum of Months | 188.67 | 22.33 | 108.83 | 22.51 | 61.17 | 22.60 |
Maximum of Months | 608.17 | 23.82 | 632.33 | 23.52 | 195.33 | 23.60 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 529.67 | 23.99 | 744.00 | 23.99 | 529.67 | 23.99 |
February | 486.67 | 23.99 | 671.00 | 23.99 | 486.67 | 23.99 |
March | 545.00 | 23.99 | 744.00 | 23.99 | 545.00 | 23.99 |
April | 552.50 | 23.99 | 720.00 | 23.99 | 552.50 | 23.99 |
May | 602.83 | 23.99 | 744.00 | 23.99 | 602.83 | 23.99 |
June | 589.33 | 23.99 | 720.00 | 23.99 | 589.33 | 23.99 |
July | 614.33 | 23.99 | 744.00 | 23.99 | 614.33 | 23.99 |
August | 608.33 | 23.99 | 744.00 | 23.99 | 608.33 | 23.99 |
September | 580.00 | 23.99 | 720.00 | 23.99 | 580.00 | 23.99 |
October | 584.50 | 23.99 | 744.00 | 23.99 | 584.50 | 23.99 |
November | 537.33 | 23.99 | 720.00 | 23.99 | 537.33 | 23.99 |
December | 539.17 | 23.99 | 744.00 | 23.99 | 539.17 | 23.99 |
Annual Sum or Average | 6769.67 | 23.99 | 8759.00 | 23.99 | 6769.67 | 23.99 |
Minimum of Months | 486.67 | 23.99 | 671.00 | 23.99 | 486.67 | 23.99 |
Maximum of Months | 614.33 | 23.99 | 744.00 | 23.99 | 614.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 621.83 | 22.41 | 100.00 | 22.60 | 29.17 | 22.64 |
February | 483.83 | 22.61 | 180.17 | 22.95 | 46.50 | 22.99 |
March | 488.33 | 22.76 | 231.33 | 23.13 | 40.83 | 23.17 |
April | 193.83 | 23.53 | 444.50 | 23.84 | 51.33 | 23.84 |
May | 5.33 | 24.00 | 744.00 | 24.00 | 5.33 | 24.00 |
June | 1.33 | 24.00 | 720.00 | 24.00 | 1.33 | 24.00 |
July | 2.33 | 24.00 | 744.00 | 24.00 | 2.33 | 24.00 |
August | 1.17 | 24.00 | 744.00 | 24.00 | 1.17 | 24.00 |
September | 3.67 | 24.00 | 720.00 | 24.00 | 3.67 | 24.00 |
October | 84.33 | 23.53 | 606.17 | 23.94 | 6.00 | 23.94 |
November | 357.00 | 23.32 | 265.00 | 23.59 | 26.33 | 23.60 |
December | 517.17 | 22.59 | 206.67 | 22.98 | 23.83 | 23.01 |
Annual Sum or Average | 2760.17 | 22.78 | 5705.83 | 23.59 | 237.83 | 23.60 |
Minimum of Months | 1.17 | 22.41 | 100.00 | 22.60 | 1.17 | 22.64 |
Maximum of Months | 621.83 | 24.00 | 744.00 | 24.00 | 51.33 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.76215 | 44.09320 | 0.31426 | 7.26633 |
February | 672.00000 | 23.14814 | 49.29544 | 0.18484 | 6.02568 |
March | 744.00000 | 22.60500 | 50.09532 | 0.04700 | 5.30816 |
April | 720.00000 | 22.21665 | 59.25587 | 0.00276 | 5.20926 |
May | 744.00000 | 22.42327 | 63.03082 | -0.9838 | 25.62938 |
June | 720.00000 | 22.66252 | 61.95822 | -0.9013 | 22.34923 |
July | 744.00000 | 23.25604 | 60.10255 | -0.6932 | 15.34550 |
August | 744.00000 | 23.84108 | 58.08980 | -0.4817 | 9.96554 |
September | 720.00000 | 23.88966 | 57.96160 | -0.4607 | 9.53021 |
October | 744.00000 | 23.90315 | 54.69611 | 0.43613 | 9.06296 |
November | 720.00000 | 23.91078 | 49.11456 | 0.39692 | 8.44473 |
December | 744.00000 | 23.88463 | 46.08524 | 0.36503 | 7.96006 |
Annual Sum or Average | 8760.00000 | 23.29444 | 54.49579 | -0.1495 | 11.04492 |
Minimum of Months | 672.00000 | 22.21665 | 44.09320 | -0.9838 | 5.20926 |
Maximum of Months | 744.00000 | 23.91078 | 63.03082 | 0.43613 | 25.62938 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.78037 | 46.43357 | 0.13627 | 7.64781 |
February | 672.00000 | 22.92359 | 49.65224 | 0.19895 | 8.26750 |
March | 744.00000 | 22.76202 | 49.59785 | 0.14349 | 7.89179 |
April | 720.00000 | 23.30003 | 56.24260 | 0.34179 | 8.39623 |
May | 744.00000 | 23.89884 | 58.93826 | -0.3383 | 7.53424 |
June | 720.00000 | 23.94529 | 58.44415 | -0.3120 | 7.13267 |
July | 744.00000 | 23.96030 | 58.65320 | -0.2980 | 6.94355 |
August | 744.00000 | 23.96681 | 58.53171 | -0.2884 | 6.83390 |
September | 720.00000 | 23.92509 | 58.86068 | -0.3048 | 7.17195 |
October | 744.00000 | 23.83498 | 55.36511 | 0.53277 | 11.55250 |
November | 720.00000 | 23.45648 | 50.73715 | 0.37101 | 9.05341 |
December | 744.00000 | 22.95278 | 48.51544 | 0.20733 | 8.51438 |
Annual Sum or Average | 8760.00000 | 23.47810 | 54.18052 | 0.03122 | 8.07830 |
Minimum of Months | 672.00000 | 22.76202 | 46.43357 | -0.3383 | 6.83390 |
Maximum of Months | 744.00000 | 23.96681 | 58.93826 | 0.53277 | 11.55250 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.43138 | 47.52644 | 0.04056 | 5.84579 |
February | 672.00000 | 22.53525 | 50.96359 | 0.09229 | 6.29012 |
March | 744.00000 | 22.50100 | 50.48757 | 0.07989 | 6.21010 |
April | 720.00000 | 22.90579 | 57.45799 | 0.23591 | 6.77902 |
May | 744.00000 | 23.31978 | 60.68927 | -0.5763 | 12.46865 |
June | 720.00000 | 23.41843 | 60.12442 | -0.5402 | 11.59747 |
July | 744.00000 | 23.45423 | 60.22261 | -0.5259 | 11.24885 |
August | 744.00000 | 23.48335 | 60.18173 | -0.5153 | 10.97662 |
September | 720.00000 | 23.42797 | 60.51440 | -0.5354 | 11.45670 |
October | 744.00000 | 23.38081 | 57.20877 | 0.36855 | 8.24614 |
November | 720.00000 | 22.96221 | 52.40213 | 0.21785 | 6.55341 |
December | 744.00000 | 22.62567 | 49.69186 | 0.10783 | 6.27505 |
Annual Sum or Average | 8760.00000 | 23.03973 | 55.63892 | -0.1307 | 8.67706 |
Minimum of Months | 672.00000 | 22.43138 | 47.52644 | -0.5763 | 5.84579 |
Maximum of Months | 744.00000 | 23.48335 | 60.68927 | 0.36855 | 12.46865 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99990 | 39.75166 | 0.95563 | 25.17062 |
February | 672.00000 | 23.99983 | 43.22936 | 0.98914 | 26.57237 |
March | 744.00000 | 23.99976 | 42.62794 | 0.99481 | 26.75554 |
April | 720.00000 | 23.99973 | 49.95323 | 1.07240 | 29.90977 |
May | 744.00000 | 23.99980 | 54.00574 | 0.51732 | 12.08831 |
June | 720.00000 | 23.99983 | 53.76782 | 0.52778 | 12.34015 |
July | 744.00000 | 23.99973 | 53.91364 | 0.52819 | 12.27743 |
August | 744.00000 | 23.99986 | 54.00288 | 0.52558 | 12.28321 |
September | 720.00000 | 23.99986 | 54.15526 | 0.51164 | 11.94124 |
October | 744.00000 | 23.99987 | 50.98957 | 1.10159 | 31.17042 |
November | 720.00000 | 23.99984 | 45.38901 | 1.02998 | 28.13256 |
December | 744.00000 | 23.99982 | 42.18691 | 0.98080 | 26.16025 |
Annual Sum or Average | 8760.00000 | 23.99982 | 48.68551 | 0.81006 | 21.19676 |
Minimum of Months | 672.00000 | 23.99973 | 39.75166 | 0.51164 | 11.94124 |
Maximum of Months | 744.00000 | 23.99990 | 54.15526 | 1.10159 | 31.17042 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.17903 | 50.52348 | 0.10012 | 6.46956 |
February | 672.00000 | 22.18581 | 54.26492 | 0.13036 | 6.76771 |
March | 744.00000 | 21.99048 | 54.21853 | 0.06501 | 6.32327 |
April | 720.00000 | 22.07317 | 62.37121 | 0.15875 | 6.22569 |
May | 744.00000 | 22.39939 | 66.04001 | -0.6892 | 15.86712 |
June | 720.00000 | 22.45295 | 65.61865 | -0.6647 | 15.14596 |
July | 744.00000 | 22.52270 | 65.58450 | -0.6341 | 14.33639 |
August | 744.00000 | 22.62981 | 65.33277 | -0.5932 | 13.20094 |
September | 720.00000 | 22.67029 | 65.31851 | -0.5800 | 12.91119 |
October | 744.00000 | 22.87358 | 61.07853 | 0.40806 | 9.30126 |
November | 720.00000 | 22.61295 | 55.72099 | 0.27864 | 7.59201 |
December | 744.00000 | 22.35956 | 52.73273 | 0.17049 | 7.33117 |
Annual Sum or Average | 8760.00000 | 22.41390 | 59.92089 | -0.1560 | 10.14647 |
Minimum of Months | 672.00000 | 21.99048 | 50.52348 | -0.6892 | 6.22569 |
Maximum of Months | 744.00000 | 22.87358 | 66.04001 | 0.40806 | 15.86712 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.72676 | 49.63597 | 0.14804 | 6.17045 |
February | 672.00000 | 22.76514 | 53.20725 | 0.18427 | 6.64659 |
March | 744.00000 | 22.67924 | 52.85716 | 0.15843 | 6.52900 |
April | 720.00000 | 22.90301 | 60.24011 | 0.27360 | 7.22697 |
May | 744.00000 | 23.23740 | 63.64286 | -0.5488 | 12.10973 |
June | 720.00000 | 23.30329 | 63.14786 | -0.5218 | 11.48989 |
July | 744.00000 | 23.34429 | 63.16446 | -0.5040 | 11.05295 |
August | 744.00000 | 23.38417 | 63.10006 | -0.4891 | 10.66621 |
September | 720.00000 | 23.38454 | 63.28496 | -0.4913 | 10.68173 |
October | 744.00000 | 23.40374 | 59.77628 | 0.42196 | 9.15338 |
November | 720.00000 | 23.14084 | 54.69981 | 0.30341 | 7.45056 |
December | 744.00000 | 22.89287 | 51.83602 | 0.21114 | 6.83357 |
Annual Sum or Average | 8760.00000 | 23.09890 | 58.23392 | -0.0729 | 8.84809 |
Minimum of Months | 672.00000 | 22.67924 | 49.63597 | -0.5488 | 6.17045 |
Maximum of Months | 744.00000 | 23.40374 | 63.64286 | 0.42196 | 12.10973 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.58360 | 53.92230 | -0.1847 | 6.69109 |
February | 672.00000 | 21.62594 | 54.27234 | -0.1498 | 6.61664 |
March | 744.00000 | 21.59131 | 54.00966 | -0.1565 | 6.61112 |
April | 720.00000 | 21.74405 | 55.72103 | -0.0537 | 5.99612 |
May | 744.00000 | 21.79840 | 53.94266 | -1.0825 | 31.21444 |
June | 720.00000 | 21.80228 | 53.29101 | -1.0674 | 30.57344 |
July | 744.00000 | 21.80270 | 53.53919 | -1.0648 | 30.45438 |
August | 744.00000 | 21.80355 | 53.71092 | -1.0645 | 30.46984 |
September | 720.00000 | 21.80058 | 54.79121 | -1.0728 | 30.88132 |
October | 744.00000 | 21.78574 | 52.99891 | -0.0183 | 5.98825 |
November | 720.00000 | 21.73804 | 53.47064 | -0.0871 | 6.14443 |
December | 744.00000 | 21.60182 | 53.92047 | -0.1592 | 6.66112 |
Annual Sum or Average | 8760.00000 | 21.72344 | 53.95948 | -0.5158 | 16.58609 |
Minimum of Months | 672.00000 | 21.58360 | 52.99891 | -1.0825 | 5.98825 |
Maximum of Months | 744.00000 | 21.80355 | 55.72103 | -0.0183 | 31.21444 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.50547 | 56.37732 | -0.2355 | 7.46846 |
February | 672.00000 | 21.74981 | 56.92805 | -0.1468 | 7.20841 |
March | 744.00000 | 21.87685 | 55.13453 | -0.1104 | 6.97082 |
April | 720.00000 | 22.29022 | 56.57983 | 0.05848 | 6.50231 |
May | 744.00000 | 21.93005 | 54.17599 | -1.0438 | 29.66250 |
June | 720.00000 | 21.87410 | 53.38435 | -1.0425 | 29.59271 |
July | 744.00000 | 21.86679 | 53.49473 | -1.0451 | 29.84857 |
August | 744.00000 | 21.91877 | 54.22806 | -1.0344 | 29.33280 |
September | 720.00000 | 22.06422 | 56.10812 | -1.0036 | 28.33170 |
October | 744.00000 | 22.05505 | 54.68166 | 0.02382 | 6.13605 |
November | 720.00000 | 21.96905 | 56.20368 | -0.0637 | 6.22551 |
December | 744.00000 | 21.66409 | 56.60612 | -0.1741 | 7.18804 |
Annual Sum or Average | 8760.00000 | 21.89658 | 55.30936 | -0.4873 | 16.26363 |
Minimum of Months | 672.00000 | 21.50547 | 53.38435 | -1.0451 | 6.13605 |
Maximum of Months | 744.00000 | 22.29022 | 56.92805 | 0.05848 | 29.84857 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.43338 | 54.00746 | -0.2682 | 7.19818 |
February | 672.00000 | 21.60974 | 55.20977 | -0.2036 | 6.79915 |
March | 744.00000 | 21.74743 | 53.22994 | -0.1691 | 6.54155 |
April | 720.00000 | 22.08817 | 56.67575 | -0.0393 | 5.92443 |
May | 744.00000 | 21.87393 | 55.36085 | -1.1684 | 34.78311 |
June | 720.00000 | 21.83294 | 54.78469 | -1.1736 | 35.04036 |
July | 744.00000 | 21.81817 | 54.67171 | -1.1780 | 35.27632 |
August | 744.00000 | 21.86240 | 55.62965 | -1.1667 | 34.76106 |
September | 720.00000 | 21.98302 | 57.46980 | -1.1289 | 33.22411 |
October | 744.00000 | 21.93160 | 55.72810 | -0.0680 | 5.87829 |
November | 720.00000 | 21.80124 | 54.73446 | -0.1418 | 6.14129 |
December | 744.00000 | 21.58591 | 54.71619 | -0.2133 | 6.85672 |
Annual Sum or Average | 8760.00000 | 21.79746 | 55.17665 | -0.5792 | 18.27516 |
Minimum of Months | 672.00000 | 21.43338 | 53.22994 | -1.1780 | 5.87829 |
Maximum of Months | 744.00000 | 22.08817 | 57.46980 | -0.0393 | 35.27632 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.64321 | 53.55610 | -0.1762 | 6.61089 |
February | 672.00000 | 21.67271 | 54.20166 | -0.1438 | 6.52083 |
March | 744.00000 | 21.65030 | 52.98949 | -0.1437 | 6.55971 |
April | 720.00000 | 21.77682 | 54.91217 | -0.0503 | 6.01371 |
May | 744.00000 | 21.81060 | 53.36372 | -1.0674 | 30.63685 |
June | 720.00000 | 21.81272 | 52.88617 | -1.0566 | 30.17553 |
July | 744.00000 | 21.81215 | 53.15275 | -1.0504 | 29.91200 |
August | 744.00000 | 21.81044 | 53.45766 | -1.0592 | 30.29070 |
September | 720.00000 | 21.80676 | 54.51440 | -1.0704 | 30.80345 |
October | 744.00000 | 21.79419 | 52.97580 | -0.0174 | 5.99966 |
November | 720.00000 | 21.76840 | 53.12536 | -0.0809 | 6.11406 |
December | 744.00000 | 21.62199 | 53.99350 | -0.1621 | 6.64939 |
Annual Sum or Average | 8760.00000 | 21.74851 | 53.58616 | -0.5089 | 16.41704 |
Minimum of Months | 672.00000 | 21.62199 | 52.88617 | -1.0704 | 5.99966 |
Maximum of Months | 744.00000 | 21.81272 | 54.91217 | -0.0174 | 30.80345 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.50455 | 56.21042 | -0.2390 | 7.28085 |
February | 672.00000 | 21.72918 | 56.98674 | -0.1555 | 6.94142 |
March | 744.00000 | 21.92896 | 54.20027 | -0.0989 | 6.86593 |
April | 720.00000 | 22.29700 | 55.95640 | 0.05725 | 6.46586 |
May | 744.00000 | 21.96101 | 53.72473 | -1.0226 | 29.03293 |
June | 720.00000 | 21.89581 | 53.10501 | -1.0278 | 29.16933 |
July | 744.00000 | 21.86751 | 53.22369 | -1.0328 | 29.28963 |
August | 744.00000 | 21.92474 | 54.00742 | -1.0293 | 29.16123 |
September | 720.00000 | 22.07272 | 55.81426 | -1.0007 | 28.25430 |
October | 744.00000 | 22.06804 | 54.50934 | 0.02452 | 6.21854 |
November | 720.00000 | 22.01981 | 55.57482 | -0.0552 | 6.23457 |
December | 744.00000 | 21.61775 | 56.89573 | -0.1911 | 7.19625 |
Annual Sum or Average | 8760.00000 | 21.90692 | 55.00017 | -0.4833 | 16.06709 |
Minimum of Months | 672.00000 | 21.50455 | 53.10501 | -1.0328 | 6.21854 |
Maximum of Months | 744.00000 | 22.29700 | 56.98674 | 0.05725 | 29.28963 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.52792 | 55.55209 | -0.2089 | 7.10391 |
February | 672.00000 | 21.58712 | 55.87529 | -0.1630 | 6.94534 |
March | 744.00000 | 21.55127 | 55.45913 | -0.1682 | 6.93827 |
April | 720.00000 | 21.73677 | 56.82625 | -0.0477 | 6.11886 |
May | 744.00000 | 21.79978 | 54.35238 | -1.0669 | 30.72226 |
June | 720.00000 | 21.80450 | 53.54214 | -1.0492 | 30.00585 |
July | 744.00000 | 21.80430 | 53.78169 | -1.0489 | 29.95647 |
August | 744.00000 | 21.80402 | 54.13124 | -1.0498 | 30.02447 |
September | 720.00000 | 21.79953 | 55.52169 | -1.0624 | 30.59884 |
October | 744.00000 | 21.77607 | 53.99920 | -0.0160 | 6.10538 |
November | 720.00000 | 21.71656 | 54.99394 | -0.0954 | 6.32332 |
December | 744.00000 | 21.54895 | 55.54740 | -0.1799 | 7.03951 |
Annual Sum or Average | 8760.00000 | 21.70505 | 54.95492 | -0.5154 | 16.54924 |
Minimum of Months | 672.00000 | 21.52792 | 53.54214 | -1.0669 | 6.10538 |
Maximum of Months | 744.00000 | 21.80450 | 56.82625 | -0.0160 | 30.72226 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.41925 | 58.11097 | -0.2682 | 8.15239 |
February | 672.00000 | 21.70461 | 58.44670 | -0.1626 | 7.72513 |
March | 744.00000 | 21.85096 | 56.32503 | -0.1187 | 7.43509 |
April | 720.00000 | 22.30462 | 57.27239 | 0.07087 | 6.80352 |
May | 744.00000 | 21.92401 | 54.50733 | -1.0298 | 29.22108 |
June | 720.00000 | 21.87136 | 53.61038 | -1.0253 | 29.06105 |
July | 744.00000 | 21.87362 | 53.66222 | -1.0273 | 29.36578 |
August | 744.00000 | 21.91711 | 54.56775 | -1.0199 | 28.91296 |
September | 720.00000 | 22.05976 | 56.74164 | -0.9926 | 28.07028 |
October | 744.00000 | 22.02089 | 55.60782 | 0.02119 | 6.23503 |
November | 720.00000 | 21.90689 | 57.78169 | -0.0819 | 6.46666 |
December | 744.00000 | 21.57993 | 58.37208 | -0.2030 | 7.74090 |
Annual Sum or Average | 8760.00000 | 21.86895 | 56.23134 | -0.4889 | 16.32140 |
Minimum of Months | 672.00000 | 21.41925 | 53.61038 | -1.0298 | 6.23503 |
Maximum of Months | 744.00000 | 22.30462 | 58.44670 | 0.07087 | 29.36578 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.71895 | 52.17252 | -0.1238 | 6.56113 |
February | 672.00000 | 21.72946 | 52.83109 | -0.1100 | 6.52574 |
March | 744.00000 | 21.63858 | 53.37189 | -0.1500 | 6.65098 |
April | 720.00000 | 21.74069 | 56.52665 | -0.0769 | 6.10378 |
May | 744.00000 | 21.79664 | 54.62636 | -1.1220 | 32.97440 |
June | 720.00000 | 21.79877 | 54.11776 | -1.1152 | 32.67745 |
July | 744.00000 | 21.80080 | 54.08110 | -1.1079 | 32.34945 |
August | 744.00000 | 21.80267 | 54.15845 | -1.1013 | 32.11016 |
September | 720.00000 | 21.80400 | 55.11151 | -1.0956 | 31.95803 |
October | 744.00000 | 21.79591 | 53.33637 | -0.0170 | 6.12724 |
November | 720.00000 | 21.78320 | 52.31064 | -0.0575 | 6.28424 |
December | 744.00000 | 21.70877 | 52.68385 | -0.1075 | 6.60629 |
Annual Sum or Average | 8760.00000 | 21.75988 | 53.77702 | -0.5180 | 17.31012 |
Minimum of Months | 672.00000 | 21.63858 | 52.17252 | -1.1220 | 6.10378 |
Maximum of Months | 744.00000 | 21.80400 | 56.52665 | -0.0170 | 32.97440 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.19430 | 50.53273 | 0.07674 | 6.16246 |
February | 672.00000 | 22.32158 | 54.01890 | 0.14443 | 6.60727 |
March | 744.00000 | 22.43218 | 53.13164 | 0.17847 | 6.75653 |
April | 720.00000 | 22.70869 | 60.37902 | 0.32485 | 7.90896 |
May | 744.00000 | 22.97127 | 63.91431 | -0.4784 | 10.65464 |
June | 720.00000 | 23.03813 | 63.43348 | -0.4465 | 9.97973 |
July | 744.00000 | 23.03860 | 63.57619 | -0.4457 | 9.98738 |
August | 744.00000 | 23.01006 | 63.80010 | -0.4610 | 10.32195 |
September | 720.00000 | 22.94065 | 64.18308 | -0.4955 | 11.05650 |
October | 744.00000 | 22.82466 | 61.16406 | 0.37397 | 8.62771 |
November | 720.00000 | 22.51961 | 55.95706 | 0.22751 | 6.96068 |
December | 744.00000 | 22.32928 | 52.90339 | 0.13884 | 6.49561 |
Annual Sum or Average | 8760.00000 | 22.69597 | 58.93371 | -0.0733 | 8.46952 |
Minimum of Months | 672.00000 | 22.19430 | 50.53273 | -0.4955 | 6.16246 |
Maximum of Months | 744.00000 | 23.03860 | 64.18308 | 0.37397 | 11.05650 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.49128 | 49.82096 | 0.16909 | 6.59292 |
February | 672.00000 | 22.60617 | 53.27934 | 0.23266 | 7.23121 |
March | 744.00000 | 22.71395 | 52.41473 | 0.26555 | 7.46615 |
April | 720.00000 | 22.95234 | 59.61752 | 0.40022 | 8.99674 |
May | 744.00000 | 23.20485 | 63.11099 | -0.3753 | 8.68395 |
June | 720.00000 | 23.26733 | 62.63653 | -0.3443 | 8.15215 |
July | 744.00000 | 23.26676 | 62.77884 | -0.3440 | 8.16528 |
August | 744.00000 | 23.23895 | 63.00478 | -0.3593 | 8.44119 |
September | 720.00000 | 23.17180 | 63.38869 | -0.3938 | 9.04059 |
October | 744.00000 | 23.05443 | 60.42084 | 0.44544 | 9.80181 |
November | 720.00000 | 22.76601 | 55.26902 | 0.30338 | 7.75908 |
December | 744.00000 | 22.60455 | 52.20865 | 0.22426 | 7.07835 |
Annual Sum or Average | 8760.00000 | 22.94662 | 58.18008 | 0.01720 | 8.12068 |
Minimum of Months | 672.00000 | 22.49128 | 49.82096 | -0.3938 | 6.59292 |
Maximum of Months | 744.00000 | 23.26733 | 63.38869 | 0.44544 | 9.80181 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99168 | 47.17722 | 1.14544 | 34.01872 |
February | 672.00000 | 23.99167 | 50.44360 | 1.18751 | 35.99799 |
March | 744.00000 | 23.99250 | 49.78479 | 1.19817 | 36.42033 |
April | 720.00000 | 23.99242 | 56.73841 | 1.29061 | 40.76219 |
May | 744.00000 | 23.99189 | 60.47986 | 0.82706 | 22.39520 |
June | 720.00000 | 23.99186 | 60.20984 | 0.84075 | 22.92031 |
July | 744.00000 | 23.99187 | 60.34445 | 0.84216 | 22.89051 |
August | 744.00000 | 23.99212 | 60.45855 | 0.83086 | 22.48748 |
September | 720.00000 | 23.99214 | 60.64986 | 0.81125 | 21.77388 |
October | 744.00000 | 23.99208 | 57.66638 | 1.31675 | 42.02293 |
November | 720.00000 | 23.99203 | 52.39406 | 1.23099 | 37.91946 |
December | 744.00000 | 23.99176 | 49.48289 | 1.17473 | 35.34271 |
Annual Sum or Average | 8760.00000 | 23.99200 | 55.50522 | 1.05712 | 31.21133 |
Minimum of Months | 672.00000 | 23.99167 | 47.17722 | 0.81125 | 21.77388 |
Maximum of Months | 744.00000 | 23.99250 | 60.64986 | 1.31675 | 42.02293 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.29099 | 47.40781 | -0.2719 | 7.14276 |
February | 672.00000 | 21.42474 | 51.09533 | -0.2138 | 6.70583 |
March | 744.00000 | 21.51381 | 50.18027 | -0.1947 | 6.45913 |
April | 720.00000 | 21.95219 | 57.49813 | -0.0326 | 5.39970 |
May | 744.00000 | 22.67845 | 60.10801 | -0.8498 | 20.32580 |
June | 720.00000 | 22.87416 | 59.25342 | -0.7839 | 18.05475 |
July | 744.00000 | 22.94195 | 59.37455 | -0.7586 | 17.24826 |
August | 744.00000 | 22.89908 | 59.51157 | -0.7735 | 17.68373 |
September | 720.00000 | 22.75019 | 60.14463 | -0.8225 | 19.40163 |
October | 744.00000 | 22.58948 | 56.89042 | 0.13210 | 5.68736 |
November | 720.00000 | 21.87798 | 52.45378 | -0.0824 | 5.66457 |
December | 744.00000 | 21.54095 | 49.58063 | -0.1913 | 6.55640 |
Annual Sum or Average | 8760.00000 | 22.19897 | 55.30361 | -0.4048 | 11.39066 |
Minimum of Months | 672.00000 | 21.29099 | 47.40781 | -0.8498 | 5.39970 |
Maximum of Months | 744.00000 | 22.94195 | 60.14463 | 0.13210 | 20.32580 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.71673 | 50.58771 | -0.1840 | 6.28883 |
February | 672.00000 | 21.83778 | 54.13711 | -0.1306 | 6.15871 |
March | 744.00000 | 21.97105 | 53.19763 | -0.1028 | 5.91894 |
April | 720.00000 | 22.52060 | 60.00031 | 0.08017 | 5.45963 |
May | 744.00000 | 23.17737 | 62.68221 | -0.7289 | 16.24986 |
June | 720.00000 | 23.30967 | 62.06502 | -0.6849 | 14.93106 |
July | 744.00000 | 23.38207 | 62.08020 | -0.6586 | 14.19172 |
August | 744.00000 | 23.33961 | 62.27386 | -0.6732 | 14.58430 |
September | 720.00000 | 23.28887 | 62.53945 | -0.6887 | 15.08928 |
October | 744.00000 | 23.23033 | 59.17951 | 0.26036 | 6.68558 |
November | 720.00000 | 22.51992 | 54.98172 | 0.04891 | 5.47018 |
December | 744.00000 | 22.02108 | 52.54115 | -0.0939 | 6.06220 |
Annual Sum or Average | 8760.00000 | 22.69758 | 58.03355 | -0.2976 | 9.78184 |
Minimum of Months | 672.00000 | 21.71673 | 50.58771 | -0.7289 | 5.45963 |
Maximum of Months | 744.00000 | 23.38207 | 62.68221 | 0.26036 | 16.24986 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.64300 | 47.99963 | 0.03674 | 6.33304 |
February | 672.00000 | 22.96069 | 50.79783 | 0.13928 | 6.99261 |
March | 744.00000 | 23.14994 | 49.80589 | 0.18155 | 7.15622 |
April | 720.00000 | 23.82226 | 55.49060 | 0.40214 | 8.66463 |
May | 744.00000 | 23.99966 | 57.94222 | -0.4061 | 8.44366 |
June | 720.00000 | 23.99959 | 57.46181 | -0.3986 | 8.31878 |
July | 744.00000 | 23.99969 | 57.62256 | -0.3968 | 8.28793 |
August | 744.00000 | 23.99970 | 57.78150 | -0.3996 | 8.33368 |
September | 720.00000 | 23.99951 | 58.24140 | -0.4064 | 8.47482 |
October | 744.00000 | 23.93441 | 55.38582 | 0.45111 | 9.44469 |
November | 720.00000 | 23.62133 | 51.52413 | 0.31768 | 7.64135 |
December | 744.00000 | 23.00049 | 49.55564 | 0.14270 | 6.97036 |
Annual Sum or Average | 8760.00000 | 23.59647 | 54.14457 | -0.0295 | 7.92558 |
Minimum of Months | 672.00000 | 22.64300 | 47.99963 | -0.4064 | 6.33304 |
Maximum of Months | 744.00000 | 23.99970 | 58.24140 | 0.45111 | 9.44469 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.62467 | 52.29064 | 0.25963 | 6.75801 |
February | 672.00000 | 23.70674 | 53.70148 | 0.29567 | 7.32924 |
March | 744.00000 | 23.78553 | 51.14144 | 0.30076 | 7.29234 |
April | 720.00000 | 23.99791 | 54.25300 | 0.39699 | 8.38648 |
May | 744.00000 | 23.99987 | 56.91816 | -0.4598 | 9.42051 |
June | 720.00000 | 23.99987 | 56.44009 | -0.4504 | 9.24049 |
July | 744.00000 | 23.99985 | 56.80356 | -0.4439 | 9.11808 |
August | 744.00000 | 23.99986 | 56.77634 | -0.4463 | 9.16262 |
September | 720.00000 | 23.99986 | 57.14212 | -0.4531 | 9.31440 |
October | 744.00000 | 23.99989 | 53.55389 | 0.42549 | 8.87408 |
November | 720.00000 | 23.98969 | 49.76182 | 0.35999 | 7.85532 |
December | 744.00000 | 23.77709 | 51.52641 | 0.30342 | 7.24975 |
Annual Sum or Average | 8760.00000 | 23.90739 | 54.19418 | 0.00548 | 8.33769 |
Minimum of Months | 672.00000 | 23.62467 | 49.76182 | -0.4598 | 6.75801 |
Maximum of Months | 744.00000 | 23.99989 | 57.14212 | 0.42549 | 9.42051 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.518468E+11 | 123141.67 | 19-JAN-22:53 | 632.05 | 0.224854E+12 | 0.00 | 0.276701E+12 | 3.86 | 4.72 | 03-JAN-04:03 | 0.00 | 0.00 |
February | 0.652798E+11 | 116282.06 | 24-FEB-16:13 | 606.55 | 0.281459E+12 | 0.00 | 0.346739E+12 | 4.04 | 4.72 | 03-FEB-22:40 | 0.00 | 0.00 |
March | 0.823996E+11 | 118241.17 | 30-MAR-18:03 | 668.71 | 0.348713E+12 | 0.00 | 0.431113E+12 | 3.97 | 4.72 | 08-MAR-23:02 | 0.00 | 0.00 |
April | 0.138331E+12 | 156059.57 | 28-APR-15:35 | 720.00 | 0.572684E+12 | 0.00 | 0.711015E+12 | 4.26 | 4.72 | 03-APR-02:00 | 0.00 | 0.00 |
May | 0.255122E+12 | 166621.29 | 25-MAY-18:03 | 744.00 | 0.991885E+12 | 0.00 | 0.124701E+13 | 3.91 | 4.33 | 02-MAY-05:10 | 0.00 | 0.00 |
June | 0.263454E+12 | 179519.77 | 28-JUN-18:03 | 720.00 | 0.100604E+13 | 0.00 | 0.126949E+13 | 3.85 | 4.35 | 01-JUN-05:10 | 0.00 | 0.00 |
July | 0.295068E+12 | 191028.41 | 22-JUL-15:35 | 744.00 | 0.111558E+13 | 0.00 | 0.141064E+13 | 3.82 | 4.28 | 11-JUL-20:05 | 0.00 | 0.00 |
August | 0.284584E+12 | 193691.17 | 24-AUG-18:03 | 744.00 | 0.108918E+13 | 0.00 | 0.137376E+13 | 3.86 | 4.42 | 16-AUG-21:05 | 0.00 | 0.00 |
September | 0.261210E+12 | 208781.81 | 09-SEP-18:03 | 720.00 | 0.102478E+13 | 0.00 | 0.128599E+13 | 3.96 | 4.51 | 07-SEP-20:00 | 0.00 | 0.00 |
October | 0.218379E+12 | 180890.35 | 07-OCT-08:03 | 744.00 | 0.864087E+12 | 0.00 | 0.108247E+13 | 4.07 | 4.72 | 28-OCT-00:40 | 0.00 | 0.00 |
November | 0.107865E+12 | 154332.84 | 02-NOV-15:13 | 715.60 | 0.451534E+12 | 0.00 | 0.559400E+12 | 4.35 | 4.72 | 09-NOV-08:20 | 0.00 | 0.00 |
December | 0.793543E+11 | 133474.22 | 16-DEC-22:53 | 662.16 | 0.337865E+12 | 0.00 | 0.417219E+12 | 3.98 | 4.72 | 04-DEC-01:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.210290E+13 | 8421.06 | 0.830865E+13 | 0.00 | 0.104115E+14 | 3.99 | 0.00 | 0.00 | ||||
Minimum of Months | 0.518468E+11 | 116282.06 | 606.55 | 0.224854E+12 | 0.00 | 0.276701E+12 | 3.82 | 4.28 | 0.00 | 0.00 | ||
Maximum of Months | 0.295068E+12 | 208781.81 | 744.00 | 0.111558E+13 | 0.00 | 0.141064E+13 | 4.35 | 4.72 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.122810E+11 | 0.00 | 226.83 | 0.648380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39430.36 | 20-JAN-03:00 | 18048.76 | 02-JAN-16:12 | 0.00 | 0.00 | 0.00 |
February | 0.157649E+11 | 0.00 | 306.83 | 0.820893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37158.87 | 02-FEB-22:52 | 18530.21 | 02-FEB-13:15 | 0.00 | 0.00 | 0.00 |
March | 0.214882E+11 | 0.00 | 371.33 | 0.124012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42711.49 | 07-MAR-20:00 | 19054.51 | 30-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.359402E+11 | 0.00 | 498.67 | 0.209158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47849.55 | 28-APR-20:10 | 20808.87 | 28-APR-15:12 | 0.00 | 0.00 | 0.00 |
May | 0.556196E+11 | 0.00 | 568.33 | 0.326812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45374.19 | 17-MAY-21:20 | 20977.02 | 28-MAY-15:12 | 0.00 | 0.00 | 0.00 |
June | 0.556888E+11 | 0.00 | 550.00 | 0.320694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42271.90 | 06-JUN-20:00 | 21043.22 | 28-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.629139E+11 | 0.00 | 568.33 | 0.335666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47912.61 | 12-JUL-21:00 | 21883.13 | 22-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.605654E+11 | 0.00 | 568.33 | 0.331211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48381.23 | 12-AUG-21:10 | 21690.17 | 03-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.587743E+11 | 0.00 | 550.00 | 0.314213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49372.22 | 05-SEP-08:62 | 21878.93 | 10-SEP-12:20 | 0.00 | 0.00 | 0.00 |
October | 0.476503E+11 | 0.00 | 540.83 | 0.278038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51492.62 | 22-OCT-08:03 | 20952.57 | 05-OCT-15:12 | 0.00 | 0.00 | 0.00 |
November | 0.249222E+11 | 0.00 | 424.83 | 0.151495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48216.32 | 03-NOV-21:10 | 19420.92 | 02-NOV-12:20 | 0.00 | 0.00 | 0.00 |
December | 0.203708E+11 | 0.00 | 292.00 | 0.104368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45545.87 | 15-DEC-21:10 | 18971.91 | 13-DEC-16:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471980E+12 | 0.00 | 5466.33 | 0.264259E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.122810E+11 | 0.00 | 226.83 | 0.648380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37158.87 | 18048.76 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.629139E+11 | 0.00 | 568.33 | 0.335666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51492.62 | 21883.13 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.151639E+12 | 0.00 | 335.00 | 0.988923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 363063.80 | 19-JAN-21:00 | 186749.02 | 19-JAN-11:35 | 0.00 | 0.00 | 0.00 |
February | 0.200000E+12 | 0.00 | 422.00 | 0.125235E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 329982.42 | 02-FEB-19:10 | 191398.86 | 26-FEB-11:35 | 0.00 | 0.00 | 0.00 |
March | 0.257455E+12 | 0.00 | 515.39 | 0.177293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 367531.46 | 07-MAR-20:00 | 236715.08 | 24-MAR-17:15 | 0.00 | 0.00 | 0.00 |
April | 0.434618E+12 | 0.00 | 665.50 | 0.289845E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 429635.48 | 28-APR-20:50 | 248685.84 | 18-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.770488E+12 | 0.00 | 744.00 | 0.470982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 427815.74 | 19-MAY-20:20 | 248285.38 | 25-MAY-18:10 | 0.00 | 0.00 | 0.00 |
June | 0.778782E+12 | 0.00 | 720.00 | 0.470905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 433366.28 | 29-JUN-17:15 | 254930.37 | 28-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.870710E+12 | 0.00 | 744.00 | 0.494478E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 445967.16 | 22-JUL-10:35 | 257467.59 | 22-JUL-17:15 | 0.00 | 0.00 | 0.00 |
August | 0.850143E+12 | 0.00 | 744.00 | 0.492168E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 461133.42 | 09-AUG-20:20 | 263558.34 | 24-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 0.803697E+12 | 0.00 | 720.00 | 0.455915E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 468213.77 | 10-SEP-10:35 | 264424.04 | 09-SEP-18:10 | 0.00 | 0.00 | 0.00 |
October | 0.657474E+12 | 0.00 | 714.17 | 0.406705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 471780.85 | 23-OCT-20:50 | 253253.41 | 05-OCT-18:08 | 0.00 | 0.00 | 0.00 |
November | 0.326295E+12 | 0.00 | 582.00 | 0.222208E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 462677.43 | 03-NOV-19:40 | 219950.91 | 01-NOV-18:05 | 0.00 | 0.00 | 0.00 |
December | 0.240164E+12 | 0.00 | 418.28 | 0.152642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 417572.73 | 15-DEC-21:00 | 201658.73 | 10-DEC-11:35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.634146E+13 | 0.00 | 7324.33 | 0.385727E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.151639E+12 | 0.00 | 335.00 | 0.988923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 329982.42 | 186749.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.870710E+12 | 0.00 | 744.00 | 0.494478E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 471780.85 | 264424.04 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.267045E+10 | 0.00 | 381.18 | 0.123089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15743.48 | 19-JAN-09:02 | 13512.78 | 10-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.341798E+10 | 0.00 | 432.31 | 0.160976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15297.01 | 24-FEB-09:02 | 13512.29 | 05-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.386352E+10 | 0.00 | 488.28 | 0.180225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15956.61 | 18-MAR-08:62 | 13513.22 | 20-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.640653E+10 | 0.00 | 639.82 | 0.331108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15633.89 | 01-APR-08:62 | 13513.16 | 10-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.937468E+10 | 0.00 | 708.60 | 0.529560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14122.08 | 02-MAY-08:61 | 12458.12 | 20-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.981409E+10 | 0.00 | 689.85 | 0.580072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14546.53 | 07-JUN-08:61 | 12387.49 | 20-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.102450E+11 | 0.00 | 712.87 | 0.599369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13732.15 | 12-JUL-08:61 | 12440.39 | 27-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.102282E+11 | 0.00 | 713.04 | 0.594525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14903.65 | 29-AUG-08:61 | 12405.56 | 07-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.934917E+10 | 0.00 | 685.68 | 0.521921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16704.33 | 05-SEP-08:62 | 12481.60 | 20-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.905685E+10 | 0.00 | 696.49 | 0.529401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15398.87 | 22-OCT-08:62 | 13512.18 | 27-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.513906E+10 | 0.00 | 611.39 | 0.254947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15675.21 | 01-NOV-08:62 | 13514.31 | 23-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.372539E+10 | 0.00 | 457.97 | 0.179012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16181.31 | 12-DEC-09:02 | 13509.63 | 26-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.832908E+11 | 0.00 | 7217.49 | 0.458421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.267045E+10 | 0.00 | 381.18 | 0.123089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13732.15 | 12387.49 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.102450E+11 | 0.00 | 713.04 | 0.599369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16704.33 | 13514.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.859486E+09 | 0.00 | 154.28 | 0.323173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15258.20 | 19-JAN-22:52 | 12176.14 | 10-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.139578E+10 | 0.00 | 216.63 | 0.556904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14934.79 | 02-FEB-22:52 | 13150.79 | 13-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.204418E+10 | 0.00 | 304.97 | 0.838152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15184.69 | 07-MAR-09:51 | 13390.35 | 20-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.458245E+10 | 0.00 | 447.92 | 0.238624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16559.99 | 29-APR-07:51 | 13407.04 | 10-APR-19:11 | 0.00 | 0.00 | 0.00 |
May | 0.901858E+10 | 0.00 | 667.29 | 0.522826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15797.28 | 05-MAY-07:51 | 12382.15 | 27-MAY-18:51 | 0.00 | 0.00 | 0.00 |
June | 0.979730E+10 | 0.00 | 668.35 | 0.595744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16531.52 | 06-JUN-07:52 | 12153.83 | 29-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.101341E+11 | 0.00 | 701.65 | 0.604121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15919.44 | 12-JUL-21:51 | 11998.00 | 27-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.963338E+10 | 0.00 | 676.75 | 0.565298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16517.99 | 29-AUG-08:61 | 12076.23 | 07-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.799489E+10 | 0.00 | 603.73 | 0.443162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17222.45 | 05-SEP-08:41 | 12950.47 | 02-SEP-18:11 | 0.00 | 0.00 | 0.00 |
October | 0.692760E+10 | 0.00 | 565.85 | 0.384973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17781.41 | 21-OCT-08:61 | 13144.12 | 27-OCT-18:31 | 0.00 | 0.00 | 0.00 |
November | 0.243562E+10 | 0.00 | 370.73 | 0.103938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15312.89 | 02-NOV-08:51 | 12634.95 | 23-NOV-17:42 | 0.00 | 0.00 | 0.00 |
December | 0.151448E+10 | 0.00 | 231.37 | 0.621993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15660.38 | 15-DEC-09:52 | 12823.18 | 26-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.663379E+11 | 0.00 | 5609.53 | 0.369271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.859486E+09 | 0.00 | 154.28 | 0.323173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14934.79 | 11998.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101341E+11 | 0.00 | 701.65 | 0.604121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17781.41 | 13407.04 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.291264E+11 | 0.00 | 565.40 | 0.172406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47899.21 | 01-JAN-14:00 | 39042.02 | 16-JAN-14:30 | 0.00 | 0.00 | 0.00 |
February | 0.275001E+11 | 0.00 | 540.76 | 0.154158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39433.39 | 02-FEB-13:30 | 34992.75 | 02-FEB-13:30 | 0.00 | 0.00 | 0.00 |
March | 0.215521E+11 | 0.00 | 524.21 | 0.940574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33461.01 | 06-MAR-13:10 | 26194.16 | 05-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.269070E+11 | 0.00 | 667.31 | 0.100869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26111.56 | 28-APR-16:20 | 14610.42 | 28-APR-16:20 | 0.00 | 0.00 | 0.00 |
May | 0.403132E+11 | 0.00 | 738.25 | 0.163992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27110.72 | 04-MAY-16:10 | 16086.07 | 04-MAY-16:20 | 0.00 | 0.00 | 0.00 |
June | 0.405821E+11 | 0.00 | 715.33 | 0.168985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29029.38 | 17-JUN-08:00 | 15900.68 | 17-JUN-08:00 | 0.00 | 0.00 | 0.00 |
July | 0.447443E+11 | 0.00 | 739.06 | 0.192358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30747.09 | 09-JUL-08:00 | 18606.95 | 19-JUL-17:20 | 0.00 | 0.00 | 0.00 |
August | 0.467968E+11 | 0.00 | 743.00 | 0.211515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31888.77 | 30-AUG-16:10 | 21759.66 | 30-AUG-16:20 | 0.00 | 0.00 | 0.00 |
September | 0.463045E+11 | 0.00 | 717.17 | 0.220812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39812.74 | 10-SEP-15:10 | 34281.37 | 10-SEP-13:30 | 0.00 | 0.00 | 0.00 |
October | 0.533162E+11 | 0.00 | 734.50 | 0.308723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43990.04 | 07-OCT-15:10 | 39086.99 | 09-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 0.428264E+11 | 0.00 | 679.45 | 0.255856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45293.18 | 06-NOV-14:00 | 39295.52 | 26-NOV-14:50 | 0.00 | 0.00 | 0.00 |
December | 0.346187E+11 | 0.00 | 581.23 | 0.205669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48126.86 | 10-DEC-13:40 | 39363.90 | 01-DEC-13:15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454588E+12 | 0.00 | 7945.67 | 0.224940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.215521E+11 | 0.00 | 524.21 | 0.940574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26111.56 | 14610.42 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.533162E+11 | 0.00 | 743.00 | 0.308723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48126.86 | 39363.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.993110E+10 | 0.00 | 230.76 | 0.455799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91760.77 | 19-JAN-22:52 | 73043.89 | 03-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.140223E+11 | 0.00 | 248.97 | 0.680929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90679.23 | 02-FEB-22:52 | 73599.88 | 12-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.208409E+11 | 0.00 | 336.35 | 0.110434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90168.18 | 18-MAR-21:51 | 75398.37 | 20-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.346100E+11 | 0.00 | 392.93 | 0.199558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98350.39 | 29-APR-07:51 | 76361.61 | 10-APR-19:11 | 0.00 | 0.00 | 0.00 |
May | 0.627555E+11 | 0.00 | 610.95 | 0.396560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92989.24 | 05-MAY-07:51 | 72742.59 | 01-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.661124E+11 | 0.00 | 617.10 | 0.433074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97120.50 | 06-JUN-07:52 | 72700.19 | 26-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.690933E+11 | 0.00 | 645.25 | 0.453436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92718.95 | 12-JUL-21:51 | 72634.57 | 29-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.650289E+11 | 0.00 | 617.12 | 0.415734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96824.82 | 29-AUG-08:61 | 72583.29 | 31-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.558320E+11 | 0.00 | 545.95 | 0.340515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103660.32 | 05-SEP-08:41 | 72722.72 | 03-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.477349E+11 | 0.00 | 504.82 | 0.284752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107606.97 | 21-OCT-08:61 | 76248.43 | 27-OCT-18:31 | 0.00 | 0.00 | 0.00 |
November | 0.221612E+11 | 0.00 | 355.80 | 0.113927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89104.25 | 02-NOV-08:51 | 75496.13 | 23-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.156794E+11 | 0.00 | 299.64 | 0.777932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92980.85 | 12-DEC-09:52 | 71240.38 | 26-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.483802E+12 | 0.00 | 5405.63 | 0.293946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.993110E+10 | 0.00 | 230.76 | 0.455799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89104.25 | 71240.38 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.690933E+11 | 0.00 | 645.25 | 0.453436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107606.97 | 76361.61 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.249423E+10 | 0.00 | 392.78 | 0.110613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14121.17 | 30-JAN-19:01 | 11790.72 | 10-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.311838E+10 | 0.00 | 448.95 | 0.140336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13792.04 | 02-FEB-09:02 | 12204.16 | 13-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.406687E+10 | 0.00 | 516.11 | 0.196935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14503.07 | 18-MAR-08:62 | 11976.14 | 03-MAR-19:01 | 0.00 | 0.00 | 0.00 |
April | 0.631445E+10 | 0.00 | 662.70 | 0.322573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14068.55 | 01-APR-08:62 | 12208.16 | 10-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.994350E+10 | 0.00 | 722.43 | 0.590088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12387.14 | 23-MAY-08:61 | 11262.29 | 07-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.101524E+11 | 0.00 | 701.52 | 0.617142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12965.16 | 07-JUN-08:61 | 11263.37 | 22-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.107784E+11 | 0.00 | 724.01 | 0.662566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12551.08 | 12-JUL-18:02 | 11270.34 | 29-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.103703E+11 | 0.00 | 721.68 | 0.619835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12910.25 | 17-AUG-08:61 | 11280.43 | 08-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.938930E+10 | 0.00 | 693.78 | 0.536535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14995.15 | 05-SEP-08:62 | 11280.01 | 30-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.895682E+10 | 0.00 | 704.28 | 0.529186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13830.33 | 20-OCT-08:61 | 12207.06 | 27-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.514167E+10 | 0.00 | 627.39 | 0.260523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14175.76 | 01-NOV-08:62 | 12205.82 | 22-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.334226E+10 | 0.00 | 460.06 | 0.155307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14634.26 | 12-DEC-09:02 | 12205.33 | 26-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.840686E+11 | 0.00 | 7375.70 | 0.474164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.249423E+10 | 0.00 | 392.78 | 0.110613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12387.14 | 11262.29 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107784E+11 | 0.00 | 724.01 | 0.662566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14995.15 | 12208.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.787938E+09 | 0.00 | 155.86 | 0.284743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14336.46 | 19-JAN-09:51 | 10591.20 | 01-JAN-09:51 | 0.00 | 0.00 | 0.00 |
February | 0.122797E+10 | 0.00 | 219.82 | 0.474361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13948.14 | 24-FEB-09:51 | 10634.24 | 14-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.227213E+10 | 0.00 | 323.81 | 0.101553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14827.52 | 07-MAR-09:51 | 11577.32 | 19-MAR-08:51 | 0.00 | 0.00 | 0.00 |
April | 0.457744E+10 | 0.00 | 472.72 | 0.235067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15381.81 | 29-APR-07:51 | 11559.08 | 10-APR-19:11 | 0.00 | 0.00 | 0.00 |
May | 0.955410E+10 | 0.00 | 677.20 | 0.577180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14813.66 | 02-MAY-08:11 | 11558.10 | 29-MAY-07:02 | 0.00 | 0.00 | 0.00 |
June | 0.101155E+11 | 0.00 | 678.26 | 0.629169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15283.96 | 06-JUN-07:52 | 11661.44 | 12-JUN-07:11 | 0.00 | 0.00 | 0.00 |
July | 0.106802E+11 | 0.00 | 711.33 | 0.667478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14313.94 | 12-JUL-21:51 | 11017.79 | 24-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.978355E+10 | 0.00 | 683.99 | 0.586483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15595.82 | 29-AUG-08:61 | 11116.05 | 20-AUG-07:41 | 0.00 | 0.00 | 0.00 |
September | 0.803887E+10 | 0.00 | 609.52 | 0.452187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15735.15 | 05-SEP-08:41 | 11023.80 | 18-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.685159E+10 | 0.00 | 576.51 | 0.382819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16682.23 | 21-OCT-08:61 | 11758.88 | 01-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.244696E+10 | 0.00 | 364.02 | 0.110365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14908.53 | 11-NOV-09:41 | 11000.57 | 06-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.126804E+10 | 0.00 | 219.64 | 0.497972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15033.32 | 16-DEC-09:51 | 10976.14 | 17-DEC-09:51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.676042E+11 | 0.00 | 5692.66 | 0.386801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.787938E+09 | 0.00 | 155.86 | 0.284743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13948.14 | 10591.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.106802E+11 | 0.00 | 711.33 | 0.667478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16682.23 | 11758.88 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.627133E+09 | 0.00 | 323.17 | 0.298618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4311.06 | 19-JAN-09:02 | 3570.45 | 10-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.830018E+09 | 0.00 | 386.95 | 0.406449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4169.65 | 24-FEB-09:02 | 3569.17 | 13-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.958002E+09 | 0.00 | 456.45 | 0.460394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4434.25 | 18-MAR-08:62 | 3570.54 | 13-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.164011E+10 | 0.00 | 622.57 | 0.876743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4311.10 | 30-APR-08:61 | 3570.42 | 10-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.247304E+10 | 0.00 | 709.28 | 0.140250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3903.36 | 12-MAY-08:61 | 3274.82 | 20-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.260831E+10 | 0.00 | 690.22 | 0.155230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4047.32 | 07-JUN-08:61 | 3280.53 | 19-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.270182E+10 | 0.00 | 713.57 | 0.158548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3830.16 | 12-JUL-08:61 | 3301.38 | 31-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.268269E+10 | 0.00 | 712.23 | 0.155967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4147.18 | 29-AUG-08:61 | 3276.32 | 07-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.241300E+10 | 0.00 | 683.20 | 0.133551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4665.87 | 05-SEP-08:62 | 3296.42 | 15-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.226944E+10 | 0.00 | 679.08 | 0.130908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4279.79 | 20-OCT-08:61 | 3570.17 | 27-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.120478E+10 | 0.00 | 559.13 | 0.601454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4300.51 | 01-NOV-08:62 | 3569.74 | 22-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.881616E+09 | 0.00 | 400.52 | 0.433266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4472.69 | 12-DEC-09:02 | 3569.52 | 26-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212900E+11 | 0.00 | 6936.35 | 0.118215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.627133E+09 | 0.00 | 323.17 | 0.298618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3830.16 | 3274.82 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.270182E+10 | 0.00 | 713.57 | 0.158548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4665.87 | 3570.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.194004E+09 | 0.00 | 132.02 | 72419528.32 | 0.00 | 0.00 | 0.00 | 0.00 | 4158.40 | 19-JAN-22:52 | 3186.28 | 31-JAN-16:12 | 0.00 | 0.00 | 0.00 |
February | 0.335655E+09 | 0.00 | 192.28 | 0.137711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4066.14 | 02-FEB-22:52 | 3458.37 | 13-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.509638E+09 | 0.00 | 278.28 | 0.214861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4128.50 | 18-MAR-21:51 | 3502.16 | 20-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.121278E+10 | 0.00 | 443.24 | 0.651687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4508.72 | 28-APR-08:31 | 3638.81 | 10-APR-19:11 | 0.00 | 0.00 | 0.00 |
May | 0.239876E+10 | 0.00 | 668.19 | 0.140462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4320.39 | 05-MAY-07:51 | 3328.74 | 27-MAY-18:51 | 0.00 | 0.00 | 0.00 |
June | 0.261329E+10 | 0.00 | 669.88 | 0.160231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4599.86 | 06-JUN-07:52 | 3177.08 | 19-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.267865E+10 | 0.00 | 701.71 | 0.160335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4206.89 | 12-JUL-21:51 | 3199.11 | 14-JUL-16:52 | 0.00 | 0.00 | 0.00 |
August | 0.254125E+10 | 0.00 | 676.62 | 0.149419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4498.13 | 29-AUG-08:61 | 3187.44 | 07-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.208514E+10 | 0.00 | 603.52 | 0.114866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4687.73 | 05-SEP-08:41 | 3416.18 | 14-SEP-16:52 | 0.00 | 0.00 | 0.00 |
October | 0.175096E+10 | 0.00 | 553.10 | 0.960097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4946.10 | 21-OCT-08:61 | 3459.08 | 27-OCT-18:31 | 0.00 | 0.00 | 0.00 |
November | 0.553409E+09 | 0.00 | 303.95 | 0.240962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4188.27 | 02-NOV-08:51 | 3347.56 | 23-NOV-17:42 | 0.00 | 0.00 | 0.00 |
December | 0.351832E+09 | 0.00 | 183.73 | 0.148679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4259.56 | 15-DEC-09:52 | 3293.38 | 26-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172254E+11 | 0.00 | 5406.53 | 0.967955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.194004E+09 | 0.00 | 132.02 | 72419528.32 | 0.00 | 0.00 | 0.00 | 0.00 | 4066.14 | 3177.08 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.267865E+10 | 0.00 | 701.71 | 0.160335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4946.10 | 3638.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.759273E+10 | 0.00 | 539.05 | 0.457456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19546.86 | 30-JAN-19:01 | 14849.12 | 02-JAN-19:01 | 0.00 | 0.00 | 0.00 |
February | 0.746086E+10 | 0.00 | 526.67 | 0.437432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18996.05 | 02-FEB-19:02 | 16198.03 | 13-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.663926E+10 | 0.00 | 530.73 | 0.355556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20123.65 | 18-MAR-08:62 | 16187.68 | 03-MAR-19:01 | 0.00 | 0.00 | 0.00 |
April | 0.833933E+10 | 0.00 | 642.52 | 0.422860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19868.99 | 28-APR-08:62 | 15578.64 | 10-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.122446E+11 | 0.00 | 704.26 | 0.695179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17978.30 | 05-MAY-08:61 | 14959.40 | 16-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.123051E+11 | 0.00 | 685.73 | 0.713363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18355.70 | 06-JUN-08:61 | 14969.39 | 01-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.132136E+11 | 0.00 | 709.92 | 0.780757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17458.47 | 12-JUL-18:02 | 14974.65 | 15-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.137232E+11 | 0.00 | 709.31 | 0.825587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18866.71 | 29-AUG-08:61 | 14971.80 | 11-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.134802E+11 | 0.00 | 686.04 | 0.802229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21696.71 | 05-SEP-08:62 | 15016.90 | 20-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.143615E+11 | 0.00 | 703.77 | 0.917895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19476.40 | 12-OCT-08:62 | 16189.59 | 27-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.108803E+11 | 0.00 | 660.84 | 0.681756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19486.42 | 29-NOV-09:02 | 16200.00 | 22-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.901217E+10 | 0.00 | 576.02 | 0.560254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20631.63 | 12-DEC-09:02 | 14741.10 | 15-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129253E+12 | 0.00 | 7674.84 | 0.765032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.663926E+10 | 0.00 | 526.67 | 0.355556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17458.47 | 14741.10 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.143615E+11 | 0.00 | 709.92 | 0.917895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21696.71 | 16200.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.60 | 454.96 | 182.64 | 924.75 | 361.00 | 0.00 | 0.00 | 0.00 |
February | 573.82 | 370.06 | 203.76 | 851.53 | 306.51 | 0.00 | 0.00 | 0.00 |
March | 374.71 | 172.44 | 202.26 | 576.23 | 263.05 | 0.00 | 0.00 | 0.00 |
April | 273.48 | 64.21 | 209.27 | 467.09 | 163.85 | 0.00 | 0.00 | 0.00 |
May | 210.36 | 10.37 | 200.00 | 444.59 | 35.08 | 0.00 | 0.00 | 0.00 |
June | 206.11 | 1.80 | 204.31 | 445.74 | 28.87 | 0.00 | 0.00 | 0.00 |
July | 215.49 | 3.53 | 211.96 | 468.54 | 15.63 | 0.00 | 0.00 | 0.00 |
August | 249.46 | 25.87 | 223.59 | 539.32 | 27.86 | 0.00 | 0.00 | 0.00 |
September | 305.88 | 81.43 | 224.46 | 609.02 | 45.28 | 0.00 | 0.00 | 0.00 |
October | 468.02 | 241.46 | 226.55 | 849.15 | 98.39 | 0.00 | 0.00 | 0.00 |
November | 607.38 | 419.91 | 187.48 | 953.81 | 233.74 | 0.00 | 0.00 | 0.00 |
December | 623.22 | 447.89 | 175.33 | 938.62 | 315.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 394.51 | 190.23 | 204.28 | 671.48 | 157.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 206.11 | 1.80 | 175.33 | 444.59 | 15.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 637.60 | 454.96 | 226.55 | 953.81 | 361.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1795.45 | 1281.15 | 514.30 | 2631.30 | 996.92 | 0.00 | 0.00 | 0.00 |
February | 1615.83 | 1042.06 | 573.77 | 2433.30 | 832.91 | 0.00 | 0.00 | 0.00 |
March | 1055.15 | 485.59 | 569.56 | 1665.80 | 712.96 | 0.00 | 0.00 | 0.00 |
April | 770.10 | 180.80 | 589.30 | 1392.99 | 407.51 | 0.00 | 0.00 | 0.00 |
May | 592.37 | 29.19 | 563.18 | 1382.60 | 60.66 | 0.00 | 0.00 | 0.00 |
June | 580.39 | 5.07 | 575.31 | 1390.46 | 46.15 | 0.00 | 0.00 | 0.00 |
July | 606.79 | 9.94 | 596.85 | 1459.97 | 19.35 | 0.00 | 0.00 | 0.00 |
August | 702.46 | 72.84 | 629.62 | 1640.14 | 46.59 | 0.00 | 0.00 | 0.00 |
September | 861.35 | 229.30 | 632.05 | 1810.85 | 84.14 | 0.00 | 0.00 | 0.00 |
October | 1317.90 | 679.94 | 637.96 | 2454.16 | 238.37 | 0.00 | 0.00 | 0.00 |
November | 1710.35 | 1182.43 | 527.92 | 2722.09 | 615.30 | 0.00 | 0.00 | 0.00 |
December | 1754.95 | 1261.24 | 493.71 | 2665.11 | 863.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1110.92 | 535.68 | 575.24 | 1968.48 | 408.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 580.39 | 5.07 | 493.71 | 1382.60 | 19.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1795.45 | 1281.15 | 637.96 | 2722.09 | 996.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2332.39 | 1664.28 | 668.11 | 3470.57 | 1371.09 | 0.00 | 0.00 | 0.00 |
February | 2099.05 | 1353.69 | 745.36 | 3206.63 | 1155.31 | 0.00 | 0.00 | 0.00 |
March | 1370.70 | 630.81 | 739.89 | 2182.79 | 1009.04 | 0.00 | 0.00 | 0.00 |
April | 1000.41 | 234.87 | 765.54 | 1804.46 | 598.55 | 0.00 | 0.00 | 0.00 |
May | 769.53 | 37.93 | 731.60 | 1761.43 | 107.48 | 0.00 | 0.00 | 0.00 |
June | 753.96 | 6.59 | 747.37 | 1768.79 | 87.10 | 0.00 | 0.00 | 0.00 |
July | 788.26 | 12.91 | 775.35 | 1856.51 | 43.87 | 0.00 | 0.00 | 0.00 |
August | 912.54 | 94.63 | 817.91 | 2109.67 | 83.68 | 0.00 | 0.00 | 0.00 |
September | 1118.95 | 297.87 | 821.07 | 2351.66 | 141.58 | 0.00 | 0.00 | 0.00 |
October | 1712.03 | 883.28 | 828.75 | 3228.38 | 339.79 | 0.00 | 0.00 | 0.00 |
November | 2221.84 | 1536.04 | 685.80 | 3590.31 | 852.33 | 0.00 | 0.00 | 0.00 |
December | 2279.78 | 1638.42 | 641.36 | 3516.09 | 1192.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1443.15 | 695.88 | 747.27 | 2567.48 | 578.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 753.96 | 6.59 | 641.36 | 1761.43 | 43.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2332.39 | 1664.28 | 828.75 | 3590.31 | 1371.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 126.07 | 89.95 | 36.11 | 186.78 | 65.60 | 0.00 | 0.00 | 0.00 |
February | 113.45 | 73.17 | 40.29 | 172.51 | 54.33 | 0.00 | 0.00 | 0.00 |
March | 74.09 | 34.10 | 39.99 | 116.88 | 45.90 | 0.00 | 0.00 | 0.00 |
April | 54.07 | 12.69 | 41.38 | 96.89 | 24.50 | 0.00 | 0.00 | 0.00 |
May | 41.59 | 2.05 | 39.54 | 101.69 | 1.30 | 0.00 | 0.00 | 0.00 |
June | 40.75 | 0.36 | 40.40 | 102.96 | 0.86 | 0.00 | 0.00 | 0.00 |
July | 42.61 | 0.70 | 41.91 | 110.17 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 49.32 | 5.11 | 44.21 | 122.49 | 0.76 | 0.00 | 0.00 | 0.00 |
September | 60.48 | 16.10 | 44.38 | 132.91 | 1.30 | 0.00 | 0.00 | 0.00 |
October | 92.54 | 47.74 | 44.79 | 178.44 | 10.97 | 0.00 | 0.00 | 0.00 |
November | 120.09 | 83.02 | 37.07 | 194.75 | 36.77 | 0.00 | 0.00 | 0.00 |
December | 123.22 | 88.56 | 34.67 | 189.91 | 54.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.00 | 37.61 | 40.39 | 142.06 | 24.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.75 | 0.36 | 34.67 | 96.89 | 0.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 126.07 | 89.95 | 44.79 | 194.75 | 65.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.35 | 60.21 | 51.14 | 146.51 | 133.56 | 0.00 | 0.00 | 0.00 |
February | 126.37 | 64.07 | 62.30 | 174.85 | 108.79 | 0.00 | 0.00 | 0.00 |
March | 123.89 | 54.66 | 69.24 | 180.27 | 87.10 | 0.00 | 0.00 | 0.00 |
April | 154.03 | 70.78 | 83.25 | 258.16 | 44.52 | 0.00 | 0.00 | 0.00 |
May | 128.43 | 41.88 | 86.55 | 277.30 | 2.37 | 0.00 | 0.00 | 0.00 |
June | 142.52 | 50.01 | 92.51 | 311.11 | 1.58 | 0.00 | 0.00 | 0.00 |
July | 129.91 | 35.93 | 93.98 | 295.10 | 0.19 | 0.00 | 0.00 | 0.00 |
August | 131.28 | 39.91 | 91.37 | 291.40 | 1.39 | 0.00 | 0.00 | 0.00 |
September | 121.17 | 41.57 | 79.60 | 252.11 | 2.32 | 0.00 | 0.00 | 0.00 |
October | 124.33 | 53.86 | 70.46 | 240.95 | 21.20 | 0.00 | 0.00 | 0.00 |
November | 106.28 | 53.40 | 52.88 | 164.02 | 74.27 | 0.00 | 0.00 | 0.00 |
December | 101.88 | 54.02 | 47.86 | 143.07 | 108.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 125.05 | 51.56 | 73.48 | 228.14 | 48.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.88 | 35.93 | 47.86 | 143.07 | 0.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 154.03 | 70.78 | 93.98 | 311.11 | 133.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.78 | 0.00 | 21.78 | 18.24 | 73.33 | 0.00 | 0.00 | 0.00 |
February | 25.69 | 0.00 | 25.69 | 24.42 | 60.85 | 0.00 | 0.00 | 0.00 |
March | 29.81 | 0.00 | 29.81 | 34.90 | 49.16 | 0.00 | 0.00 | 0.00 |
April | 35.31 | 0.24 | 35.08 | 54.63 | 26.43 | 0.00 | 0.00 | 0.00 |
May | 39.88 | 1.46 | 38.42 | 96.59 | 1.49 | 0.00 | 0.00 | 0.00 |
June | 45.35 | 3.18 | 42.17 | 112.18 | 0.94 | 0.00 | 0.00 | 0.00 |
July | 44.02 | 1.70 | 42.32 | 112.52 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 39.51 | 0.39 | 39.12 | 100.84 | 1.07 | 0.00 | 0.00 | 0.00 |
September | 34.03 | 0.01 | 34.02 | 79.76 | 2.12 | 0.00 | 0.00 | 0.00 |
October | 29.56 | 0.00 | 29.56 | 64.34 | 12.35 | 0.00 | 0.00 | 0.00 |
November | 22.44 | 0.00 | 22.44 | 28.83 | 41.20 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 20.04 | 59.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 0.58 | 31.75 | 62.51 | 27.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 18.24 | 0.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.35 | 3.18 | 42.32 | 112.52 | 73.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.35 | 60.21 | 51.14 | 151.59 | 130.91 | 0.00 | 0.00 | 0.00 |
February | 126.37 | 64.07 | 62.30 | 178.46 | 108.45 | 0.00 | 0.00 | 0.00 |
March | 123.89 | 54.66 | 69.24 | 181.10 | 88.87 | 0.00 | 0.00 | 0.00 |
April | 154.03 | 70.78 | 83.25 | 256.06 | 48.39 | 0.00 | 0.00 | 0.00 |
May | 128.43 | 41.88 | 86.55 | 276.10 | 2.72 | 0.00 | 0.00 | 0.00 |
June | 142.52 | 50.01 | 92.51 | 310.12 | 1.80 | 0.00 | 0.00 | 0.00 |
July | 129.91 | 35.93 | 93.98 | 294.35 | 0.43 | 0.00 | 0.00 | 0.00 |
August | 131.28 | 39.91 | 91.37 | 291.05 | 1.93 | 0.00 | 0.00 | 0.00 |
September | 121.17 | 41.57 | 79.60 | 251.59 | 3.77 | 0.00 | 0.00 | 0.00 |
October | 124.33 | 53.86 | 70.46 | 242.25 | 22.61 | 0.00 | 0.00 | 0.00 |
November | 106.28 | 53.40 | 52.88 | 167.05 | 74.72 | 0.00 | 0.00 | 0.00 |
December | 101.88 | 54.02 | 47.86 | 147.12 | 107.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 125.05 | 51.56 | 73.48 | 229.13 | 49.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.88 | 35.93 | 47.86 | 147.12 | 0.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 154.03 | 70.78 | 93.98 | 310.12 | 130.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.83 | 71.95 | 28.88 | 134.66 | 78.98 | 0.00 | 0.00 | 0.00 |
February | 90.74 | 58.52 | 32.22 | 123.44 | 68.04 | 0.00 | 0.00 | 0.00 |
March | 59.26 | 27.27 | 31.99 | 80.65 | 61.32 | 0.00 | 0.00 | 0.00 |
April | 43.25 | 10.15 | 33.10 | 64.03 | 40.49 | 0.00 | 0.00 | 0.00 |
May | 33.27 | 1.64 | 31.63 | 60.88 | 13.54 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 0.28 | 32.31 | 61.62 | 11.89 | 0.00 | 0.00 | 0.00 |
July | 34.08 | 0.56 | 33.52 | 64.16 | 8.63 | 0.00 | 0.00 | 0.00 |
August | 39.45 | 4.09 | 35.36 | 75.96 | 11.61 | 0.00 | 0.00 | 0.00 |
September | 48.37 | 12.88 | 35.50 | 87.54 | 16.12 | 0.00 | 0.00 | 0.00 |
October | 74.01 | 38.19 | 35.83 | 125.22 | 26.47 | 0.00 | 0.00 | 0.00 |
November | 96.05 | 66.41 | 29.65 | 141.37 | 52.69 | 0.00 | 0.00 | 0.00 |
December | 98.56 | 70.83 | 27.73 | 138.49 | 70.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.39 | 30.08 | 32.31 | 96.37 | 38.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.59 | 0.28 | 27.73 | 60.88 | 8.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.83 | 71.95 | 35.83 | 141.37 | 78.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.42 | 0.00 | 17.42 | 15.20 | 58.80 | 0.00 | 0.00 | 0.00 |
February | 20.56 | 0.00 | 20.56 | 20.82 | 48.15 | 0.00 | 0.00 | 0.00 |
March | 23.85 | 0.00 | 23.85 | 29.56 | 38.81 | 0.00 | 0.00 | 0.00 |
April | 28.25 | 0.19 | 28.06 | 46.62 | 19.41 | 0.00 | 0.00 | 0.00 |
May | 31.91 | 1.17 | 30.74 | 82.06 | 0.70 | 0.00 | 0.00 | 0.00 |
June | 36.28 | 2.54 | 33.74 | 95.05 | 0.49 | 0.00 | 0.00 | 0.00 |
July | 35.22 | 1.36 | 33.86 | 95.51 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 31.61 | 0.32 | 31.30 | 86.01 | 0.56 | 0.00 | 0.00 | 0.00 |
September | 27.23 | 0.01 | 27.22 | 68.45 | 1.06 | 0.00 | 0.00 | 0.00 |
October | 23.65 | 0.00 | 23.65 | 55.61 | 8.81 | 0.00 | 0.00 | 0.00 |
November | 17.95 | 0.00 | 17.95 | 24.73 | 31.68 | 0.00 | 0.00 | 0.00 |
December | 16.20 | 0.00 | 16.20 | 16.88 | 47.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.87 | 0.47 | 25.40 | 53.24 | 21.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.20 | 0.00 | 16.20 | 15.20 | 0.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.28 | 2.54 | 33.86 | 95.51 | 58.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.50 | 53.15 | 51.35 | 128.58 | 127.61 | 0.00 | 0.00 | 0.00 |
February | 116.72 | 56.35 | 60.37 | 153.28 | 103.27 | 0.00 | 0.00 | 0.00 |
March | 137.45 | 66.36 | 71.09 | 197.57 | 82.65 | 0.00 | 0.00 | 0.00 |
April | 150.63 | 68.07 | 82.55 | 249.88 | 42.63 | 0.00 | 0.00 | 0.00 |
May | 155.17 | 67.36 | 87.81 | 320.82 | 2.35 | 0.00 | 0.00 | 0.00 |
June | 157.07 | 62.23 | 94.85 | 336.22 | 1.45 | 0.00 | 0.00 | 0.00 |
July | 151.63 | 55.51 | 96.12 | 332.58 | 0.19 | 0.00 | 0.00 | 0.00 |
August | 139.81 | 48.11 | 91.70 | 304.61 | 1.35 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 42.50 | 81.17 | 255.89 | 2.29 | 0.00 | 0.00 | 0.00 |
October | 122.39 | 51.68 | 70.70 | 235.36 | 19.88 | 0.00 | 0.00 | 0.00 |
November | 108.12 | 55.04 | 53.08 | 161.05 | 69.77 | 0.00 | 0.00 | 0.00 |
December | 85.30 | 38.69 | 46.61 | 111.66 | 105.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 129.41 | 55.40 | 74.02 | 232.74 | 46.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.30 | 38.69 | 46.61 | 111.66 | 0.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 157.07 | 68.07 | 96.12 | 336.22 | 127.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 126.07 | 89.95 | 36.11 | 185.96 | 65.09 | 0.00 | 0.00 | 0.00 |
February | 113.45 | 73.17 | 40.29 | 171.78 | 53.72 | 0.00 | 0.00 | 0.00 |
March | 74.09 | 34.10 | 39.99 | 115.69 | 45.63 | 0.00 | 0.00 | 0.00 |
April | 54.07 | 12.69 | 41.38 | 96.17 | 24.13 | 0.00 | 0.00 | 0.00 |
May | 41.59 | 2.05 | 39.54 | 100.81 | 1.26 | 0.00 | 0.00 | 0.00 |
June | 40.75 | 0.36 | 40.40 | 102.37 | 0.81 | 0.00 | 0.00 | 0.00 |
July | 42.61 | 0.70 | 41.91 | 109.44 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 49.32 | 5.11 | 44.21 | 122.17 | 0.73 | 0.00 | 0.00 | 0.00 |
September | 60.48 | 16.10 | 44.38 | 132.70 | 1.23 | 0.00 | 0.00 | 0.00 |
October | 92.54 | 47.74 | 44.79 | 178.19 | 10.72 | 0.00 | 0.00 | 0.00 |
November | 120.09 | 83.02 | 37.07 | 194.08 | 36.44 | 0.00 | 0.00 | 0.00 |
December | 123.22 | 88.56 | 34.67 | 189.69 | 54.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.00 | 37.61 | 40.39 | 141.45 | 24.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.75 | 0.36 | 34.67 | 96.17 | 0.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 126.07 | 89.95 | 44.79 | 194.08 | 65.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.78 | 0.00 | 21.78 | 17.54 | 72.52 | 0.00 | 0.00 | 0.00 |
February | 25.69 | 0.00 | 25.69 | 23.79 | 59.80 | 0.00 | 0.00 | 0.00 |
March | 29.81 | 0.00 | 29.81 | 33.65 | 48.76 | 0.00 | 0.00 | 0.00 |
April | 35.31 | 0.24 | 35.08 | 53.69 | 25.63 | 0.00 | 0.00 | 0.00 |
May | 39.88 | 1.46 | 38.42 | 95.58 | 1.46 | 0.00 | 0.00 | 0.00 |
June | 45.35 | 3.18 | 42.17 | 111.50 | 0.89 | 0.00 | 0.00 | 0.00 |
July | 44.02 | 1.70 | 42.32 | 111.84 | 0.21 | 0.00 | 0.00 | 0.00 |
August | 39.51 | 0.39 | 39.12 | 100.49 | 1.01 | 0.00 | 0.00 | 0.00 |
September | 34.03 | 0.01 | 34.02 | 79.48 | 2.00 | 0.00 | 0.00 | 0.00 |
October | 29.56 | 0.00 | 29.56 | 63.84 | 11.89 | 0.00 | 0.00 | 0.00 |
November | 22.44 | 0.00 | 22.44 | 27.80 | 40.66 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 19.69 | 58.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 0.58 | 31.75 | 61.81 | 26.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 17.54 | 0.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.35 | 3.18 | 42.32 | 111.84 | 72.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.50 | 53.15 | 51.35 | 133.15 | 123.52 | 0.00 | 0.00 | 0.00 |
February | 116.72 | 56.35 | 60.37 | 156.71 | 101.63 | 0.00 | 0.00 | 0.00 |
March | 137.45 | 66.36 | 71.09 | 198.22 | 83.99 | 0.00 | 0.00 | 0.00 |
April | 150.63 | 68.07 | 82.55 | 247.64 | 45.96 | 0.00 | 0.00 | 0.00 |
May | 155.17 | 67.36 | 87.81 | 319.27 | 2.69 | 0.00 | 0.00 | 0.00 |
June | 157.07 | 62.23 | 94.85 | 334.96 | 1.62 | 0.00 | 0.00 | 0.00 |
July | 151.63 | 55.51 | 96.12 | 332.00 | 0.42 | 0.00 | 0.00 | 0.00 |
August | 139.81 | 48.11 | 91.70 | 304.23 | 1.87 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 42.50 | 81.17 | 255.23 | 3.65 | 0.00 | 0.00 | 0.00 |
October | 122.39 | 51.68 | 70.70 | 236.20 | 20.90 | 0.00 | 0.00 | 0.00 |
November | 108.12 | 55.04 | 53.08 | 163.44 | 69.77 | 0.00 | 0.00 | 0.00 |
December | 85.30 | 38.69 | 46.61 | 115.43 | 103.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 129.41 | 55.40 | 74.02 | 233.48 | 46.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.30 | 38.69 | 46.61 | 115.43 | 0.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 157.07 | 68.07 | 96.12 | 334.96 | 123.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.58 | 0.00 | 27.58 | 22.95 | 99.04 | 0.00 | 0.00 | 0.00 |
February | 32.54 | 0.00 | 32.54 | 32.12 | 80.64 | 0.00 | 0.00 | 0.00 |
March | 37.75 | 0.00 | 37.75 | 46.52 | 65.51 | 0.00 | 0.00 | 0.00 |
April | 44.72 | 0.30 | 44.42 | 72.93 | 35.03 | 0.00 | 0.00 | 0.00 |
May | 50.50 | 1.85 | 48.65 | 119.13 | 4.15 | 0.00 | 0.00 | 0.00 |
June | 57.43 | 4.03 | 53.40 | 137.60 | 3.14 | 0.00 | 0.00 | 0.00 |
July | 55.75 | 2.15 | 53.59 | 135.67 | 1.16 | 0.00 | 0.00 | 0.00 |
August | 50.04 | 0.50 | 49.54 | 122.24 | 2.99 | 0.00 | 0.00 | 0.00 |
September | 43.10 | 0.01 | 43.09 | 97.37 | 5.48 | 0.00 | 0.00 | 0.00 |
October | 37.43 | 0.00 | 37.43 | 78.06 | 19.81 | 0.00 | 0.00 | 0.00 |
November | 28.42 | 0.00 | 28.42 | 36.28 | 57.79 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 0.00 | 25.64 | 25.15 | 82.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.95 | 0.74 | 40.21 | 77.44 | 37.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 0.00 | 25.64 | 22.95 | 1.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.43 | 4.03 | 53.59 | 137.60 | 99.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.17 | 0.00 | 10.17 | 8.46 | 36.51 | 0.00 | 0.00 | 0.00 |
February | 11.99 | 0.00 | 11.99 | 11.84 | 29.73 | 0.00 | 0.00 | 0.00 |
March | 13.92 | 0.00 | 13.92 | 17.15 | 24.15 | 0.00 | 0.00 | 0.00 |
April | 16.49 | 0.11 | 16.38 | 26.88 | 12.91 | 0.00 | 0.00 | 0.00 |
May | 18.62 | 0.68 | 17.94 | 43.92 | 1.53 | 0.00 | 0.00 | 0.00 |
June | 21.17 | 1.48 | 19.69 | 50.72 | 1.16 | 0.00 | 0.00 | 0.00 |
July | 20.55 | 0.79 | 19.76 | 50.01 | 0.43 | 0.00 | 0.00 | 0.00 |
August | 18.45 | 0.18 | 18.26 | 45.06 | 1.10 | 0.00 | 0.00 | 0.00 |
September | 15.89 | 0.00 | 15.88 | 35.90 | 2.02 | 0.00 | 0.00 | 0.00 |
October | 13.80 | 0.00 | 13.80 | 28.77 | 7.30 | 0.00 | 0.00 | 0.00 |
November | 10.48 | 0.00 | 10.48 | 13.37 | 21.30 | 0.00 | 0.00 | 0.00 |
December | 9.45 | 0.00 | 9.45 | 9.27 | 30.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.10 | 0.27 | 14.82 | 28.55 | 13.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.45 | 0.00 | 9.45 | 8.46 | 0.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.17 | 1.48 | 19.76 | 50.72 | 36.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 58.82 | 41.97 | 16.85 | 88.31 | 31.99 | 0.00 | 0.00 | 0.00 |
February | 52.94 | 34.14 | 18.80 | 81.79 | 26.53 | 0.00 | 0.00 | 0.00 |
March | 34.57 | 15.91 | 18.66 | 55.61 | 23.09 | 0.00 | 0.00 | 0.00 |
April | 25.23 | 5.92 | 19.31 | 46.20 | 13.12 | 0.00 | 0.00 | 0.00 |
May | 19.41 | 0.96 | 18.45 | 45.96 | 1.54 | 0.00 | 0.00 | 0.00 |
June | 19.01 | 0.17 | 18.85 | 46.16 | 1.19 | 0.00 | 0.00 | 0.00 |
July | 19.88 | 0.33 | 19.55 | 48.70 | 0.42 | 0.00 | 0.00 | 0.00 |
August | 23.01 | 2.39 | 20.63 | 55.03 | 1.11 | 0.00 | 0.00 | 0.00 |
September | 28.22 | 7.51 | 20.71 | 60.49 | 2.02 | 0.00 | 0.00 | 0.00 |
October | 43.18 | 22.28 | 20.90 | 82.20 | 7.00 | 0.00 | 0.00 | 0.00 |
November | 56.03 | 38.74 | 17.30 | 91.47 | 19.23 | 0.00 | 0.00 | 0.00 |
December | 57.49 | 41.32 | 16.17 | 89.50 | 27.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.40 | 17.55 | 18.85 | 65.87 | 12.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.01 | 0.17 | 16.17 | 45.96 | 0.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.82 | 41.97 | 20.90 | 91.47 | 31.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.65 | 113.92 | 45.73 | 239.69 | 86.81 | 0.00 | 0.00 | 0.00 |
February | 143.68 | 92.66 | 51.02 | 222.00 | 72.01 | 0.00 | 0.00 | 0.00 |
March | 93.83 | 43.18 | 50.65 | 150.94 | 62.67 | 0.00 | 0.00 | 0.00 |
April | 68.48 | 16.08 | 52.40 | 125.39 | 35.60 | 0.00 | 0.00 | 0.00 |
May | 52.68 | 2.60 | 50.08 | 124.75 | 4.18 | 0.00 | 0.00 | 0.00 |
June | 51.61 | 0.45 | 51.16 | 125.27 | 3.22 | 0.00 | 0.00 | 0.00 |
July | 53.96 | 0.88 | 53.07 | 132.19 | 1.15 | 0.00 | 0.00 | 0.00 |
August | 62.46 | 6.48 | 55.99 | 149.37 | 3.01 | 0.00 | 0.00 | 0.00 |
September | 76.59 | 20.39 | 56.20 | 164.19 | 5.48 | 0.00 | 0.00 | 0.00 |
October | 117.19 | 60.46 | 56.73 | 223.11 | 19.00 | 0.00 | 0.00 | 0.00 |
November | 152.09 | 105.14 | 46.94 | 248.26 | 52.18 | 0.00 | 0.00 | 0.00 |
December | 156.05 | 112.15 | 43.90 | 242.91 | 74.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.79 | 47.63 | 51.15 | 178.80 | 34.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.61 | 0.45 | 43.90 | 124.75 | 1.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.65 | 113.92 | 56.73 | 248.26 | 86.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 126.07 | 89.95 | 36.11 | 185.46 | 64.95 | 0.00 | 0.00 | 0.00 |
February | 113.45 | 73.17 | 40.29 | 171.09 | 53.76 | 0.00 | 0.00 | 0.00 |
March | 74.09 | 34.10 | 39.99 | 115.70 | 45.25 | 0.00 | 0.00 | 0.00 |
April | 54.07 | 12.69 | 41.38 | 95.68 | 24.08 | 0.00 | 0.00 | 0.00 |
May | 41.59 | 2.05 | 39.54 | 100.98 | 1.16 | 0.00 | 0.00 | 0.00 |
June | 40.75 | 0.36 | 40.40 | 102.19 | 0.77 | 0.00 | 0.00 | 0.00 |
July | 42.61 | 0.70 | 41.91 | 109.67 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 49.32 | 5.11 | 44.21 | 121.79 | 0.69 | 0.00 | 0.00 | 0.00 |
September | 60.48 | 16.10 | 44.38 | 132.17 | 1.20 | 0.00 | 0.00 | 0.00 |
October | 92.54 | 47.74 | 44.79 | 177.26 | 10.62 | 0.00 | 0.00 | 0.00 |
November | 120.09 | 83.02 | 37.07 | 193.52 | 36.08 | 0.00 | 0.00 | 0.00 |
December | 123.22 | 88.56 | 34.67 | 188.67 | 54.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.00 | 37.61 | 40.39 | 141.05 | 24.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.75 | 0.36 | 34.67 | 95.68 | 0.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 126.07 | 89.95 | 44.79 | 193.52 | 64.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.35 | 60.21 | 51.14 | 144.83 | 131.96 | 0.00 | 0.00 | 0.00 |
February | 126.37 | 64.07 | 62.30 | 172.78 | 107.51 | 0.00 | 0.00 | 0.00 |
March | 123.89 | 54.66 | 69.24 | 178.12 | 85.78 | 0.00 | 0.00 | 0.00 |
April | 154.03 | 70.78 | 83.25 | 255.14 | 43.65 | 0.00 | 0.00 | 0.00 |
May | 128.43 | 41.88 | 86.55 | 275.32 | 2.12 | 0.00 | 0.00 | 0.00 |
June | 142.52 | 50.01 | 92.51 | 308.85 | 1.41 | 0.00 | 0.00 | 0.00 |
July | 129.91 | 35.93 | 93.98 | 293.31 | 0.17 | 0.00 | 0.00 | 0.00 |
August | 131.28 | 39.91 | 91.37 | 289.67 | 1.26 | 0.00 | 0.00 | 0.00 |
September | 121.17 | 41.57 | 79.60 | 250.75 | 2.12 | 0.00 | 0.00 | 0.00 |
October | 124.33 | 53.86 | 70.46 | 239.53 | 20.46 | 0.00 | 0.00 | 0.00 |
November | 106.28 | 53.40 | 52.88 | 162.65 | 72.68 | 0.00 | 0.00 | 0.00 |
December | 101.88 | 54.02 | 47.86 | 141.73 | 107.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 125.05 | 51.56 | 73.48 | 226.29 | 47.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.88 | 35.93 | 47.86 | 141.73 | 0.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 154.03 | 70.78 | 93.98 | 308.85 | 131.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.78 | 0.00 | 21.78 | 18.33 | 72.39 | 0.00 | 0.00 | 0.00 |
February | 25.69 | 0.00 | 25.69 | 24.21 | 60.27 | 0.00 | 0.00 | 0.00 |
March | 29.81 | 0.00 | 29.81 | 34.45 | 48.81 | 0.00 | 0.00 | 0.00 |
April | 35.31 | 0.24 | 35.08 | 53.70 | 26.45 | 0.00 | 0.00 | 0.00 |
May | 39.88 | 1.46 | 38.42 | 95.91 | 1.36 | 0.00 | 0.00 | 0.00 |
June | 45.35 | 3.18 | 42.17 | 111.38 | 0.84 | 0.00 | 0.00 | 0.00 |
July | 44.02 | 1.70 | 42.32 | 111.82 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 39.51 | 0.39 | 39.12 | 100.39 | 1.03 | 0.00 | 0.00 | 0.00 |
September | 34.03 | 0.01 | 34.02 | 79.45 | 2.05 | 0.00 | 0.00 | 0.00 |
October | 29.56 | 0.00 | 29.56 | 64.24 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 22.44 | 0.00 | 22.44 | 28.86 | 40.23 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 20.11 | 58.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 0.58 | 31.75 | 62.14 | 26.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 18.33 | 0.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.35 | 3.18 | 42.32 | 111.82 | 72.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.35 | 60.21 | 51.14 | 150.62 | 129.11 | 0.00 | 0.00 | 0.00 |
February | 126.37 | 64.07 | 62.30 | 176.74 | 107.25 | 0.00 | 0.00 | 0.00 |
March | 123.89 | 54.66 | 69.24 | 178.89 | 87.99 | 0.00 | 0.00 | 0.00 |
April | 154.03 | 70.78 | 83.25 | 252.70 | 48.18 | 0.00 | 0.00 | 0.00 |
May | 128.43 | 41.88 | 86.55 | 274.09 | 2.47 | 0.00 | 0.00 | 0.00 |
June | 142.52 | 50.01 | 92.51 | 307.85 | 1.62 | 0.00 | 0.00 | 0.00 |
July | 129.91 | 35.93 | 93.98 | 292.46 | 0.46 | 0.00 | 0.00 | 0.00 |
August | 131.28 | 39.91 | 91.37 | 289.29 | 1.84 | 0.00 | 0.00 | 0.00 |
September | 121.17 | 41.57 | 79.60 | 250.12 | 3.65 | 0.00 | 0.00 | 0.00 |
October | 124.33 | 53.86 | 70.46 | 241.02 | 21.84 | 0.00 | 0.00 | 0.00 |
November | 106.28 | 53.40 | 52.88 | 166.20 | 72.83 | 0.00 | 0.00 | 0.00 |
December | 101.88 | 54.02 | 47.86 | 146.36 | 105.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 125.05 | 51.56 | 73.48 | 227.42 | 48.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.88 | 35.93 | 47.86 | 146.36 | 0.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 154.03 | 70.78 | 93.98 | 307.85 | 129.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 184.89 | 131.93 | 52.96 | 266.94 | 99.07 | 0.00 | 0.00 | 0.00 |
February | 166.39 | 107.31 | 59.08 | 247.33 | 81.05 | 0.00 | 0.00 | 0.00 |
March | 108.65 | 50.00 | 58.65 | 168.50 | 67.26 | 0.00 | 0.00 | 0.00 |
April | 79.30 | 18.62 | 60.68 | 142.33 | 33.90 | 0.00 | 0.00 | 0.00 |
May | 61.00 | 3.01 | 57.99 | 152.57 | 1.28 | 0.00 | 0.00 | 0.00 |
June | 59.77 | 0.52 | 59.24 | 155.34 | 0.88 | 0.00 | 0.00 | 0.00 |
July | 62.49 | 1.02 | 61.46 | 165.99 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 72.34 | 7.50 | 64.84 | 183.04 | 0.81 | 0.00 | 0.00 | 0.00 |
September | 88.70 | 23.61 | 65.09 | 196.66 | 1.42 | 0.00 | 0.00 | 0.00 |
October | 135.71 | 70.02 | 65.69 | 260.59 | 15.47 | 0.00 | 0.00 | 0.00 |
November | 176.12 | 121.76 | 54.36 | 281.13 | 54.53 | 0.00 | 0.00 | 0.00 |
December | 180.72 | 129.88 | 50.84 | 272.71 | 82.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 114.40 | 55.16 | 59.24 | 207.59 | 36.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 59.77 | 0.52 | 50.84 | 142.33 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.89 | 131.93 | 65.69 | 281.13 | 99.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.43 | 0.00 | 152.43 | 119.14 | 584.57 | 0.00 | 0.00 | 0.00 |
February | 179.84 | 0.00 | 179.84 | 168.12 | 482.88 | 0.00 | 0.00 | 0.00 |
March | 208.66 | 0.00 | 208.66 | 244.00 | 403.01 | 0.00 | 0.00 | 0.00 |
April | 247.19 | 1.67 | 245.52 | 391.44 | 220.21 | 0.00 | 0.00 | 0.00 |
May | 279.13 | 10.21 | 268.92 | 650.53 | 34.07 | 0.00 | 0.00 | 0.00 |
June | 317.42 | 22.25 | 295.17 | 756.15 | 27.12 | 0.00 | 0.00 | 0.00 |
July | 308.12 | 11.90 | 296.22 | 746.28 | 11.82 | 0.00 | 0.00 | 0.00 |
August | 276.58 | 2.76 | 273.82 | 673.13 | 24.10 | 0.00 | 0.00 | 0.00 |
September | 238.22 | 0.06 | 238.16 | 542.83 | 42.72 | 0.00 | 0.00 | 0.00 |
October | 206.89 | 0.00 | 206.89 | 441.10 | 120.24 | 0.00 | 0.00 | 0.00 |
November | 157.06 | 0.00 | 157.06 | 200.92 | 336.01 | 0.00 | 0.00 | 0.00 |
December | 141.70 | 0.00 | 141.70 | 134.44 | 486.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 226.33 | 4.08 | 222.25 | 423.87 | 229.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.70 | 0.00 | 141.70 | 119.14 | 11.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 317.42 | 22.25 | 296.22 | 756.15 | 584.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.43 | 0.00 | 152.43 | 111.32 | 610.36 | 0.00 | 0.00 | 0.00 |
February | 179.84 | 0.00 | 179.84 | 159.03 | 505.43 | 0.00 | 0.00 | 0.00 |
March | 208.66 | 0.00 | 208.66 | 232.79 | 423.62 | 0.00 | 0.00 | 0.00 |
April | 247.19 | 1.67 | 245.52 | 378.25 | 233.80 | 0.00 | 0.00 | 0.00 |
May | 279.13 | 10.21 | 268.92 | 631.70 | 41.57 | 0.00 | 0.00 | 0.00 |
June | 317.42 | 22.25 | 295.17 | 736.67 | 33.36 | 0.00 | 0.00 | 0.00 |
July | 308.12 | 11.90 | 296.22 | 724.86 | 16.18 | 0.00 | 0.00 | 0.00 |
August | 276.58 | 2.76 | 273.82 | 653.26 | 30.28 | 0.00 | 0.00 | 0.00 |
September | 238.22 | 0.06 | 238.16 | 526.01 | 52.12 | 0.00 | 0.00 | 0.00 |
October | 206.89 | 0.00 | 206.89 | 425.71 | 131.15 | 0.00 | 0.00 | 0.00 |
November | 157.06 | 0.00 | 157.06 | 191.53 | 353.51 | 0.00 | 0.00 | 0.00 |
December | 141.70 | 0.00 | 141.70 | 126.72 | 510.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 226.33 | 4.08 | 222.25 | 409.65 | 243.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.70 | 0.00 | 141.70 | 111.32 | 16.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 317.42 | 22.25 | 296.22 | 736.67 | 610.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.78 | 0.00 | 21.78 | 19.43 | 87.86 | 0.00 | 0.00 | 0.00 |
February | 25.69 | 0.00 | 25.69 | 28.02 | 72.47 | 0.00 | 0.00 | 0.00 |
March | 29.81 | 0.00 | 29.81 | 39.35 | 62.10 | 0.00 | 0.00 | 0.00 |
April | 35.31 | 0.24 | 35.08 | 64.88 | 34.20 | 0.00 | 0.00 | 0.00 |
May | 39.88 | 1.46 | 38.42 | 105.89 | 8.45 | 0.00 | 0.00 | 0.00 |
June | 45.35 | 3.18 | 42.17 | 123.27 | 7.34 | 0.00 | 0.00 | 0.00 |
July | 44.02 | 1.70 | 42.32 | 120.56 | 4.41 | 0.00 | 0.00 | 0.00 |
August | 39.51 | 0.39 | 39.12 | 108.96 | 6.47 | 0.00 | 0.00 | 0.00 |
September | 34.03 | 0.01 | 34.02 | 89.13 | 9.59 | 0.00 | 0.00 | 0.00 |
October | 29.56 | 0.00 | 29.56 | 71.83 | 20.71 | 0.00 | 0.00 | 0.00 |
November | 22.44 | 0.00 | 22.44 | 34.49 | 49.76 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 22.78 | 72.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 0.58 | 31.75 | 69.29 | 36.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 19.43 | 4.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.35 | 3.18 | 42.32 | 123.27 | 87.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.99 | 106.30 | 102.69 | 273.64 | 301.77 | 0.00 | 0.00 | 0.00 |
February | 233.42 | 112.69 | 120.73 | 329.68 | 248.97 | 0.00 | 0.00 | 0.00 |
March | 274.88 | 132.72 | 142.16 | 419.02 | 217.49 | 0.00 | 0.00 | 0.00 |
April | 301.23 | 136.14 | 165.09 | 538.43 | 124.99 | 0.00 | 0.00 | 0.00 |
May | 310.31 | 134.71 | 175.60 | 674.46 | 31.97 | 0.00 | 0.00 | 0.00 |
June | 314.13 | 124.45 | 189.68 | 712.06 | 27.68 | 0.00 | 0.00 | 0.00 |
July | 303.23 | 111.00 | 192.23 | 694.37 | 16.79 | 0.00 | 0.00 | 0.00 |
August | 279.59 | 96.21 | 183.38 | 638.15 | 24.40 | 0.00 | 0.00 | 0.00 |
September | 247.31 | 84.98 | 162.32 | 545.14 | 36.20 | 0.00 | 0.00 | 0.00 |
October | 244.75 | 103.36 | 141.40 | 501.67 | 75.42 | 0.00 | 0.00 | 0.00 |
November | 216.22 | 110.08 | 106.15 | 354.09 | 174.07 | 0.00 | 0.00 | 0.00 |
December | 170.59 | 77.38 | 93.21 | 242.79 | 258.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.81 | 110.79 | 148.02 | 494.49 | 127.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 170.59 | 77.38 | 93.21 | 242.79 | 16.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.13 | 136.14 | 192.23 | 712.06 | 301.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 126.07 | 89.95 | 36.11 | 192.41 | 77.93 | 0.00 | 0.00 | 0.00 |
February | 113.45 | 73.17 | 40.29 | 179.18 | 65.14 | 0.00 | 0.00 | 0.00 |
March | 74.09 | 34.10 | 39.99 | 122.64 | 59.38 | 0.00 | 0.00 | 0.00 |
April | 54.07 | 12.69 | 41.38 | 106.42 | 34.53 | 0.00 | 0.00 | 0.00 |
May | 41.59 | 2.05 | 39.54 | 110.18 | 8.47 | 0.00 | 0.00 | 0.00 |
June | 40.75 | 0.36 | 40.40 | 113.68 | 7.38 | 0.00 | 0.00 | 0.00 |
July | 42.61 | 0.70 | 41.91 | 117.43 | 4.43 | 0.00 | 0.00 | 0.00 |
August | 49.32 | 5.11 | 44.21 | 130.35 | 6.49 | 0.00 | 0.00 | 0.00 |
September | 60.48 | 16.10 | 44.38 | 142.26 | 9.59 | 0.00 | 0.00 | 0.00 |
October | 92.54 | 47.74 | 44.79 | 187.94 | 19.94 | 0.00 | 0.00 | 0.00 |
November | 120.09 | 83.02 | 37.07 | 204.24 | 46.10 | 0.00 | 0.00 | 0.00 |
December | 123.22 | 88.56 | 34.67 | 196.74 | 66.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.00 | 37.61 | 40.39 | 150.15 | 33.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.75 | 0.36 | 34.67 | 106.42 | 4.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 126.07 | 89.95 | 44.79 | 204.24 | 77.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.58 | 0.00 | 27.58 | 18.39 | 109.08 | 0.00 | 0.00 | 0.00 |
February | 32.54 | 0.00 | 32.54 | 25.97 | 91.18 | 0.00 | 0.00 | 0.00 |
March | 37.75 | 0.00 | 37.75 | 38.93 | 75.78 | 0.00 | 0.00 | 0.00 |
April | 44.72 | 0.30 | 44.42 | 62.83 | 44.15 | 0.00 | 0.00 | 0.00 |
May | 50.50 | 1.85 | 48.65 | 107.77 | 7.78 | 0.00 | 0.00 | 0.00 |
June | 57.43 | 4.03 | 53.40 | 126.95 | 6.09 | 0.00 | 0.00 | 0.00 |
July | 55.75 | 2.15 | 53.59 | 124.76 | 3.05 | 0.00 | 0.00 | 0.00 |
August | 50.04 | 0.50 | 49.54 | 111.67 | 5.60 | 0.00 | 0.00 | 0.00 |
September | 43.10 | 0.01 | 43.09 | 88.53 | 9.95 | 0.00 | 0.00 | 0.00 |
October | 37.43 | 0.00 | 37.43 | 70.14 | 24.98 | 0.00 | 0.00 | 0.00 |
November | 28.42 | 0.00 | 28.42 | 29.86 | 67.60 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 0.00 | 25.64 | 20.10 | 92.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.95 | 0.74 | 40.21 | 69.09 | 44.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 0.00 | 25.64 | 18.39 | 3.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.43 | 4.03 | 53.59 | 126.95 | 109.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.68 | 0.00 | 24.68 | 16.45 | 97.59 | 0.00 | 0.00 | 0.00 |
February | 29.11 | 0.00 | 29.11 | 23.23 | 81.58 | 0.00 | 0.00 | 0.00 |
March | 33.78 | 0.00 | 33.78 | 34.83 | 67.80 | 0.00 | 0.00 | 0.00 |
April | 40.01 | 0.27 | 39.74 | 56.21 | 39.50 | 0.00 | 0.00 | 0.00 |
May | 45.18 | 1.65 | 43.53 | 96.42 | 6.96 | 0.00 | 0.00 | 0.00 |
June | 51.38 | 3.60 | 47.78 | 113.58 | 5.45 | 0.00 | 0.00 | 0.00 |
July | 49.88 | 1.93 | 47.95 | 111.63 | 2.73 | 0.00 | 0.00 | 0.00 |
August | 44.77 | 0.45 | 44.33 | 99.91 | 5.01 | 0.00 | 0.00 | 0.00 |
September | 38.56 | 0.01 | 38.55 | 79.21 | 8.90 | 0.00 | 0.00 | 0.00 |
October | 33.49 | 0.00 | 33.49 | 62.76 | 22.35 | 0.00 | 0.00 | 0.00 |
November | 25.42 | 0.00 | 25.42 | 26.72 | 60.48 | 0.00 | 0.00 | 0.00 |
December | 22.94 | 0.00 | 22.94 | 17.99 | 82.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.64 | 0.66 | 35.98 | 61.81 | 39.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.94 | 0.00 | 22.94 | 16.45 | 2.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.38 | 3.60 | 47.95 | 113.58 | 97.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 470.64 | 335.83 | 134.82 | 681.47 | 278.79 | 0.00 | 0.00 | 0.00 |
February | 423.56 | 273.15 | 150.40 | 626.18 | 237.74 | 0.00 | 0.00 | 0.00 |
March | 276.59 | 127.29 | 149.30 | 417.38 | 212.90 | 0.00 | 0.00 | 0.00 |
April | 201.87 | 47.39 | 154.48 | 338.55 | 132.35 | 0.00 | 0.00 | 0.00 |
May | 155.28 | 7.65 | 147.63 | 334.51 | 23.54 | 0.00 | 0.00 | 0.00 |
June | 152.14 | 1.33 | 150.81 | 338.36 | 18.67 | 0.00 | 0.00 | 0.00 |
July | 159.06 | 2.61 | 156.45 | 357.72 | 9.00 | 0.00 | 0.00 | 0.00 |
August | 184.14 | 19.09 | 165.04 | 408.49 | 16.92 | 0.00 | 0.00 | 0.00 |
September | 225.79 | 60.11 | 165.68 | 456.27 | 29.47 | 0.00 | 0.00 | 0.00 |
October | 345.46 | 178.23 | 167.23 | 630.43 | 70.70 | 0.00 | 0.00 | 0.00 |
November | 448.33 | 309.95 | 138.38 | 704.36 | 178.57 | 0.00 | 0.00 | 0.00 |
December | 460.02 | 330.61 | 129.42 | 691.49 | 244.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 291.21 | 140.42 | 150.79 | 498.15 | 120.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 152.14 | 1.33 | 129.42 | 334.51 | 9.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 470.64 | 335.83 | 167.23 | 704.36 | 278.79 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170776E+10 | 0.121857E+10 | 0.489185E+09 | 0.247685E+10 | 0.966896E+09 |
February | 0.138817E+10 | 0.895243E+09 | 0.492932E+09 | 0.206002E+10 | 0.741502E+09 |
March | 0.100361E+10 | 0.461874E+09 | 0.541741E+09 | 0.154337E+10 | 0.704547E+09 |
April | 0.708863E+09 | 0.166423E+09 | 0.542439E+09 | 0.121069E+10 | 0.424697E+09 |
May | 0.563440E+09 | 27768379.07 | 0.535672E+09 | 0.119079E+10 | 93963987.59 |
June | 0.534233E+09 | 4670372.97 | 0.529563E+09 | 0.115535E+10 | 74831091.81 |
July | 0.577157E+09 | 9455235.71 | 0.567702E+09 | 0.125494E+10 | 41861896.33 |
August | 0.668153E+09 | 69286625.40 | 0.598867E+09 | 0.144452E+10 | 74623174.53 |
September | 0.792854E+09 | 0.211066E+09 | 0.581788E+09 | 0.157857E+10 | 0.117370E+09 |
October | 0.125353E+10 | 0.646732E+09 | 0.606801E+09 | 0.227437E+10 | 0.263515E+09 |
November | 0.157434E+10 | 0.108840E+10 | 0.485937E+09 | 0.247229E+10 | 0.605852E+09 |
December | 0.166924E+10 | 0.119964E+10 | 0.469597E+09 | 0.251399E+10 | 0.844456E+09 |
Annual Sum or Average | 0.124414E+11 | 0.599913E+10 | 0.644222E+10 | 0.211757E+11 | 0.495412E+10 |
Minimum of Months | 0.534233E+09 | 4670372.97 | 0.469597E+09 | 0.115535E+10 | 41861896.33 |
Maximum of Months | 0.170776E+10 | 0.121857E+10 | 0.606801E+09 | 0.251399E+10 | 0.966896E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.480894E+10 | 0.343142E+10 | 0.137751E+10 | 0.704767E+10 | 0.267015E+10 |
February | 0.390901E+10 | 0.252095E+10 | 0.138806E+10 | 0.588664E+10 | 0.201496E+10 |
March | 0.282611E+10 | 0.130061E+10 | 0.152551E+10 | 0.446169E+10 | 0.190960E+10 |
April | 0.199611E+10 | 0.468637E+09 | 0.152747E+10 | 0.361063E+10 | 0.105627E+10 |
May | 0.158661E+10 | 78193924.59 | 0.150842E+10 | 0.370315E+10 | 0.162478E+09 |
June | 0.150437E+10 | 13151462.36 | 0.149121E+10 | 0.360408E+10 | 0.119630E+09 |
July | 0.162524E+10 | 26625320.33 | 0.159861E+10 | 0.391037E+10 | 51822189.64 |
August | 0.188148E+10 | 0.195107E+09 | 0.168637E+10 | 0.439295E+10 | 0.124795E+09 |
September | 0.223262E+10 | 0.594347E+09 | 0.163828E+10 | 0.469373E+10 | 0.218096E+09 |
October | 0.352987E+10 | 0.182116E+10 | 0.170871E+10 | 0.657323E+10 | 0.638440E+09 |
November | 0.443322E+10 | 0.306486E+10 | 0.136837E+10 | 0.705565E+10 | 0.159485E+10 |
December | 0.470046E+10 | 0.337811E+10 | 0.132235E+10 | 0.713824E+10 | 0.231197E+10 |
Annual Sum or Average | 0.350340E+11 | 0.168932E+11 | 0.181409E+11 | 0.620780E+11 | 0.128731E+11 |
Minimum of Months | 0.150437E+10 | 13151462.36 | 0.132235E+10 | 0.360408E+10 | 51822189.64 |
Maximum of Months | 0.480894E+10 | 0.343142E+10 | 0.170871E+10 | 0.713824E+10 | 0.267015E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.624708E+10 | 0.445762E+10 | 0.178947E+10 | 0.929557E+10 | 0.367232E+10 |
February | 0.507803E+10 | 0.327485E+10 | 0.180317E+10 | 0.775748E+10 | 0.279492E+10 |
March | 0.367128E+10 | 0.168956E+10 | 0.198172E+10 | 0.584639E+10 | 0.270262E+10 |
April | 0.259306E+10 | 0.608787E+09 | 0.198428E+10 | 0.467717E+10 | 0.155144E+10 |
May | 0.206110E+10 | 0.101578E+09 | 0.195952E+10 | 0.471782E+10 | 0.287886E+09 |
June | 0.195426E+10 | 17084498.06 | 0.193717E+10 | 0.458470E+10 | 0.225759E+09 |
July | 0.211127E+10 | 34587806.38 | 0.207669E+10 | 0.497247E+10 | 0.117505E+09 |
August | 0.244414E+10 | 0.253455E+09 | 0.219069E+10 | 0.565054E+10 | 0.224131E+09 |
September | 0.290031E+10 | 0.772091E+09 | 0.212821E+10 | 0.609550E+10 | 0.366977E+09 |
October | 0.458550E+10 | 0.236578E+10 | 0.221971E+10 | 0.864689E+10 | 0.910083E+09 |
November | 0.575901E+10 | 0.398143E+10 | 0.177758E+10 | 0.930608E+10 | 0.220923E+10 |
December | 0.610616E+10 | 0.438835E+10 | 0.171781E+10 | 0.941750E+10 | 0.319423E+10 |
Annual Sum or Average | 0.455112E+11 | 0.219452E+11 | 0.235660E+11 | 0.809681E+11 | 0.182571E+11 |
Minimum of Months | 0.195426E+10 | 17084498.06 | 0.171781E+10 | 0.458470E+10 | 0.117505E+09 |
Maximum of Months | 0.624708E+10 | 0.445762E+10 | 0.221971E+10 | 0.941750E+10 | 0.367232E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.337654E+09 | 0.240933E+09 | 96721089.53 | 0.500281E+09 | 0.175695E+09 |
February | 0.274467E+09 | 0.177005E+09 | 97461971.73 | 0.417344E+09 | 0.131429E+09 |
March | 0.198433E+09 | 91320349.86 | 0.107112E+09 | 0.313053E+09 | 0.122927E+09 |
April | 0.140156E+09 | 32904767.04 | 0.107251E+09 | 0.251147E+09 | 63491571.05 |
May | 0.111403E+09 | 5490285.46 | 0.105913E+09 | 0.272374E+09 | 3473955.60 |
June | 0.105628E+09 | 923412.95 | 0.104705E+09 | 0.266861E+09 | 2234080.08 |
July | 0.114115E+09 | 1869462.49 | 0.112246E+09 | 0.295078E+09 | 284978.78 |
August | 0.132107E+09 | 13699155.83 | 0.118407E+09 | 0.328086E+09 | 2041692.00 |
September | 0.156762E+09 | 41731333.14 | 0.115030E+09 | 0.344504E+09 | 3375677.06 |
October | 0.247846E+09 | 0.127870E+09 | 0.119976E+09 | 0.477934E+09 | 29392792.36 |
November | 0.311274E+09 | 0.215195E+09 | 96078786.59 | 0.504798E+09 | 95297183.06 |
December | 0.330037E+09 | 0.237189E+09 | 92848057.14 | 0.508644E+09 | 0.147004E+09 |
Annual Sum or Average | 0.245988E+10 | 0.118613E+10 | 0.127375E+10 | 0.448010E+10 | 0.776647E+09 |
Minimum of Months | 0.105628E+09 | 923412.95 | 92848057.14 | 0.251147E+09 | 284978.78 |
Maximum of Months | 0.337654E+09 | 0.240933E+09 | 0.119976E+09 | 0.508644E+09 | 0.175695E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.298244E+09 | 0.161272E+09 | 0.136972E+09 | 0.392412E+09 | 0.357735E+09 |
February | 0.305712E+09 | 0.155000E+09 | 0.150712E+09 | 0.423009E+09 | 0.263174E+09 |
March | 0.331836E+09 | 0.146390E+09 | 0.185446E+09 | 0.482828E+09 | 0.233280E+09 |
April | 0.399253E+09 | 0.183461E+09 | 0.215793E+09 | 0.669140E+09 | 0.115385E+09 |
May | 0.343981E+09 | 0.112169E+09 | 0.231812E+09 | 0.742724E+09 | 6335893.47 |
June | 0.369411E+09 | 0.129617E+09 | 0.239794E+09 | 0.806409E+09 | 4101424.50 |
July | 0.347950E+09 | 96224762.86 | 0.251726E+09 | 0.790395E+09 | 507857.73 |
August | 0.351619E+09 | 0.106906E+09 | 0.244713E+09 | 0.780491E+09 | 3726371.86 |
September | 0.314066E+09 | 0.107744E+09 | 0.206321E+09 | 0.653472E+09 | 6015960.45 |
October | 0.333003E+09 | 0.144272E+09 | 0.188731E+09 | 0.645365E+09 | 56772270.41 |
November | 0.275471E+09 | 0.138400E+09 | 0.137071E+09 | 0.425133E+09 | 0.192516E+09 |
December | 0.272884E+09 | 0.144687E+09 | 0.128198E+09 | 0.383207E+09 | 0.291344E+09 |
Annual Sum or Average | 0.394343E+10 | 0.162614E+10 | 0.231729E+10 | 0.719458E+10 | 0.153089E+10 |
Minimum of Months | 0.272884E+09 | 96224762.86 | 0.128198E+09 | 0.383207E+09 | 507857.73 |
Maximum of Months | 0.399253E+09 | 0.183461E+09 | 0.251726E+09 | 0.806409E+09 | 0.357735E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58327907.02 | 0.00 | 58327907.02 | 48854064.43 | 0.196404E+09 |
February | 62153545.47 | 0.00 | 62153545.47 | 59067424.78 | 0.147205E+09 |
March | 79841902.97 | 1125.76 | 79840777.21 | 93464291.43 | 0.131669E+09 |
April | 91534057.12 | 617796.44 | 90916260.68 | 0.141588E+09 | 68502222.23 |
May | 0.106807E+09 | 3906776.86 | 0.102900E+09 | 0.258718E+09 | 3986618.68 |
June | 0.117542E+09 | 8239618.13 | 0.109302E+09 | 0.290764E+09 | 2437970.74 |
July | 0.117901E+09 | 4553346.89 | 0.113347E+09 | 0.301369E+09 | 649510.66 |
August | 0.105832E+09 | 1055095.64 | 0.104777E+09 | 0.270095E+09 | 2859122.83 |
September | 88213490.93 | 23834.84 | 88189656.09 | 0.206736E+09 | 5489256.33 |
October | 79164007.13 | 0.00 | 79164007.13 | 0.172324E+09 | 33088889.46 |
November | 58159526.36 | 0.00 | 58159526.36 | 74718475.20 | 0.106790E+09 |
December | 54222419.22 | 0.00 | 54222419.22 | 53669998.27 | 0.160251E+09 |
Annual Sum or Average | 0.101970E+10 | 18397594.56 | 0.100130E+10 | 0.197137E+10 | 0.859332E+09 |
Minimum of Months | 54222419.22 | 0.00 | 54222419.22 | 48854064.43 | 649510.66 |
Maximum of Months | 0.117901E+09 | 8239618.13 | 0.113347E+09 | 0.301369E+09 | 0.196404E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.298244E+09 | 0.161272E+09 | 0.136972E+09 | 0.406009E+09 | 0.350629E+09 |
February | 0.305712E+09 | 0.155000E+09 | 0.150712E+09 | 0.431723E+09 | 0.262365E+09 |
March | 0.331836E+09 | 0.146390E+09 | 0.185446E+09 | 0.485053E+09 | 0.238023E+09 |
April | 0.399253E+09 | 0.183461E+09 | 0.215793E+09 | 0.663697E+09 | 0.125430E+09 |
May | 0.343981E+09 | 0.112169E+09 | 0.231812E+09 | 0.739497E+09 | 7283912.53 |
June | 0.369411E+09 | 0.129617E+09 | 0.239794E+09 | 0.803835E+09 | 4661863.66 |
July | 0.347950E+09 | 96224762.86 | 0.251726E+09 | 0.788400E+09 | 1154555.16 |
August | 0.351619E+09 | 0.106906E+09 | 0.244713E+09 | 0.779537E+09 | 5177009.05 |
September | 0.314066E+09 | 0.107744E+09 | 0.206321E+09 | 0.652108E+09 | 9779397.61 |
October | 0.333003E+09 | 0.144272E+09 | 0.188731E+09 | 0.648846E+09 | 60553017.94 |
November | 0.275471E+09 | 0.138400E+09 | 0.137071E+09 | 0.432985E+09 | 0.193678E+09 |
December | 0.272884E+09 | 0.144687E+09 | 0.128198E+09 | 0.394051E+09 | 0.287958E+09 |
Annual Sum or Average | 0.394343E+10 | 0.162614E+10 | 0.231729E+10 | 0.722574E+10 | 0.154669E+10 |
Minimum of Months | 0.272884E+09 | 96224762.86 | 0.128198E+09 | 0.394051E+09 | 1154555.16 |
Maximum of Months | 0.399253E+09 | 0.183461E+09 | 0.251726E+09 | 0.803835E+09 | 0.350629E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270070E+09 | 0.192708E+09 | 77361486.51 | 0.360664E+09 | 0.211550E+09 |
February | 0.219530E+09 | 0.141576E+09 | 77954074.42 | 0.298636E+09 | 0.164597E+09 |
March | 0.158715E+09 | 73041753.85 | 85672903.76 | 0.216002E+09 | 0.164240E+09 |
April | 0.112102E+09 | 26318579.58 | 85783597.12 | 0.165963E+09 | 0.104946E+09 |
May | 89104705.65 | 4391355.05 | 84713350.61 | 0.163052E+09 | 36265487.51 |
June | 84485891.04 | 738583.48 | 83747307.56 | 0.159727E+09 | 30826014.44 |
July | 91273890.15 | 1495272.62 | 89778617.52 | 0.171842E+09 | 23118474.86 |
August | 0.105664E+09 | 10957145.58 | 94707071.18 | 0.203441E+09 | 31091465.71 |
September | 0.125385E+09 | 33378428.44 | 92006075.66 | 0.226911E+09 | 41771217.69 |
October | 0.198237E+09 | 0.102276E+09 | 95961691.86 | 0.335382E+09 | 70897545.78 |
November | 0.248970E+09 | 0.172122E+09 | 76847746.33 | 0.366434E+09 | 0.136562E+09 |
December | 0.263977E+09 | 0.189714E+09 | 74263676.67 | 0.370919E+09 | 0.188853E+09 |
Annual Sum or Average | 0.196751E+10 | 0.948716E+09 | 0.101880E+10 | 0.303897E+10 | 0.120472E+10 |
Minimum of Months | 84485891.04 | 738583.48 | 74263676.67 | 0.159727E+09 | 23118474.86 |
Maximum of Months | 0.270070E+09 | 0.192708E+09 | 95961691.86 | 0.370919E+09 | 0.211550E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46668510.97 | 0.00 | 46668510.97 | 40701497.51 | 0.157485E+09 |
February | 49729427.42 | 0.00 | 49729427.42 | 50356229.37 | 0.116484E+09 |
March | 63881989.17 | 900.73 | 63881088.45 | 79179671.40 | 0.103950E+09 |
April | 73236952.39 | 494302.67 | 72742649.72 | 0.120836E+09 | 50310610.69 |
May | 85457088.95 | 3125835.78 | 82331253.17 | 0.219783E+09 | 1886224.79 |
June | 94046028.79 | 6592568.27 | 87453460.52 | 0.246372E+09 | 1278055.89 |
July | 94332927.68 | 3643160.37 | 90689767.31 | 0.255806E+09 | 286515.21 |
August | 84676640.22 | 844188.40 | 83832451.82 | 0.230361E+09 | 1501451.08 |
September | 70580147.31 | 19070.40 | 70561076.91 | 0.177427E+09 | 2745029.90 |
October | 63339600.62 | 0.00 | 63339600.62 | 0.148932E+09 | 23607083.28 |
November | 46533788.58 | 0.00 | 46533788.58 | 64108474.58 | 82125396.91 |
December | 43383685.37 | 0.00 | 43383685.37 | 45217029.59 | 0.127963E+09 |
Annual Sum or Average | 0.815867E+09 | 14720026.61 | 0.801147E+09 | 0.167908E+10 | 0.669623E+09 |
Minimum of Months | 43383685.37 | 0.00 | 43383685.37 | 40701497.51 | 286515.21 |
Maximum of Months | 94332927.68 | 6592568.27 | 90689767.31 | 0.255806E+09 | 0.157485E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279900E+09 | 0.142369E+09 | 0.137531E+09 | 0.344390E+09 | 0.341784E+09 |
February | 0.282364E+09 | 0.136319E+09 | 0.146045E+09 | 0.370824E+09 | 0.249835E+09 |
March | 0.368150E+09 | 0.177750E+09 | 0.190400E+09 | 0.529180E+09 | 0.221379E+09 |
April | 0.390423E+09 | 0.176445E+09 | 0.213978E+09 | 0.647700E+09 | 0.110495E+09 |
May | 0.415601E+09 | 0.180422E+09 | 0.235180E+09 | 0.859277E+09 | 6285902.71 |
June | 0.407137E+09 | 0.161298E+09 | 0.245839E+09 | 0.871472E+09 | 3767189.54 |
July | 0.406119E+09 | 0.148668E+09 | 0.257451E+09 | 0.890770E+09 | 498676.94 |
August | 0.374455E+09 | 0.128852E+09 | 0.245602E+09 | 0.815873E+09 | 3628511.47 |
September | 0.320535E+09 | 0.110148E+09 | 0.210387E+09 | 0.663255E+09 | 5944701.64 |
October | 0.327799E+09 | 0.138428E+09 | 0.189371E+09 | 0.630390E+09 | 53253377.94 |
November | 0.280247E+09 | 0.142668E+09 | 0.137580E+09 | 0.417444E+09 | 0.180834E+09 |
December | 0.228467E+09 | 0.103631E+09 | 0.124835E+09 | 0.299074E+09 | 0.283723E+09 |
Annual Sum or Average | 0.408120E+10 | 0.174700E+10 | 0.233420E+10 | 0.733965E+10 | 0.146143E+10 |
Minimum of Months | 0.228467E+09 | 0.103631E+09 | 0.124835E+09 | 0.299074E+09 | 498676.94 |
Maximum of Months | 0.415601E+09 | 0.180422E+09 | 0.257451E+09 | 0.890770E+09 | 0.341784E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.337654E+09 | 0.240933E+09 | 96721089.53 | 0.498086E+09 | 0.174343E+09 |
February | 0.274467E+09 | 0.177005E+09 | 97461971.73 | 0.415574E+09 | 0.129963E+09 |
March | 0.198433E+09 | 91320349.86 | 0.107112E+09 | 0.309852E+09 | 0.122203E+09 |
April | 0.140156E+09 | 32904767.04 | 0.107251E+09 | 0.249282E+09 | 62541163.42 |
May | 0.111403E+09 | 5490285.46 | 0.105913E+09 | 0.270011E+09 | 3377714.49 |
June | 0.105628E+09 | 923412.95 | 0.104705E+09 | 0.265348E+09 | 2106268.04 |
July | 0.114115E+09 | 1869462.49 | 0.112246E+09 | 0.293127E+09 | 262691.82 |
August | 0.132107E+09 | 13699155.83 | 0.118407E+09 | 0.327212E+09 | 1946687.29 |
September | 0.156762E+09 | 41731333.14 | 0.115030E+09 | 0.343963E+09 | 3197740.45 |
October | 0.247846E+09 | 0.127870E+09 | 0.119976E+09 | 0.477273E+09 | 28704170.77 |
November | 0.311274E+09 | 0.215195E+09 | 96078786.59 | 0.503054E+09 | 94464652.37 |
December | 0.330037E+09 | 0.237189E+09 | 92848057.14 | 0.508070E+09 | 0.145350E+09 |
Annual Sum or Average | 0.245988E+10 | 0.118613E+10 | 0.127375E+10 | 0.446085E+10 | 0.768459E+09 |
Minimum of Months | 0.105628E+09 | 923412.95 | 92848057.14 | 0.249282E+09 | 262691.82 |
Maximum of Months | 0.337654E+09 | 0.240933E+09 | 0.119976E+09 | 0.508070E+09 | 0.174343E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58327907.02 | 0.00 | 58327907.02 | 46973606.51 | 0.194242E+09 |
February | 62153545.47 | 0.00 | 62153545.47 | 57550372.81 | 0.144674E+09 |
March | 79841902.97 | 1125.76 | 79840777.21 | 90137251.75 | 0.130600E+09 |
April | 91534057.12 | 617796.44 | 90916260.68 | 0.139153E+09 | 66425017.51 |
May | 0.106807E+09 | 3906776.86 | 0.102900E+09 | 0.256010E+09 | 3908893.64 |
June | 0.117542E+09 | 8239618.13 | 0.109302E+09 | 0.289009E+09 | 2305706.71 |
July | 0.117901E+09 | 4553346.89 | 0.113347E+09 | 0.299549E+09 | 574809.94 |
August | 0.105832E+09 | 1055095.64 | 0.104777E+09 | 0.269155E+09 | 2699138.90 |
September | 88213490.93 | 23834.84 | 88189656.09 | 0.206010E+09 | 5171958.83 |
October | 79164007.13 | 0.00 | 79164007.13 | 0.170986E+09 | 31839786.66 |
November | 58159526.36 | 0.00 | 58159526.36 | 72062347.31 | 0.105383E+09 |
December | 54222419.22 | 0.00 | 54222419.22 | 52725988.65 | 0.157175E+09 |
Annual Sum or Average | 0.101970E+10 | 18397594.56 | 0.100130E+10 | 0.194932E+10 | 0.845000E+09 |
Minimum of Months | 54222419.22 | 0.00 | 54222419.22 | 46973606.51 | 574809.94 |
Maximum of Months | 0.117901E+09 | 8239618.13 | 0.113347E+09 | 0.299549E+09 | 0.194242E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279900E+09 | 0.142369E+09 | 0.137531E+09 | 0.356617E+09 | 0.330829E+09 |
February | 0.282364E+09 | 0.136319E+09 | 0.146045E+09 | 0.379122E+09 | 0.245853E+09 |
March | 0.368150E+09 | 0.177750E+09 | 0.190400E+09 | 0.530916E+09 | 0.224962E+09 |
April | 0.390423E+09 | 0.176445E+09 | 0.213978E+09 | 0.641894E+09 | 0.119129E+09 |
May | 0.415601E+09 | 0.180422E+09 | 0.235180E+09 | 0.855142E+09 | 7210564.24 |
June | 0.407137E+09 | 0.161298E+09 | 0.245839E+09 | 0.868223E+09 | 4208160.52 |
July | 0.406119E+09 | 0.148668E+09 | 0.257451E+09 | 0.889225E+09 | 1126100.65 |
August | 0.374455E+09 | 0.128852E+09 | 0.245602E+09 | 0.814844E+09 | 5017729.34 |
September | 0.320535E+09 | 0.110148E+09 | 0.210387E+09 | 0.661564E+09 | 9465324.20 |
October | 0.327799E+09 | 0.138428E+09 | 0.189371E+09 | 0.632648E+09 | 55979574.23 |
November | 0.280247E+09 | 0.142668E+09 | 0.137580E+09 | 0.423643E+09 | 0.180836E+09 |
December | 0.228467E+09 | 0.103631E+09 | 0.124835E+09 | 0.309159E+09 | 0.276983E+09 |
Annual Sum or Average | 0.408120E+10 | 0.174700E+10 | 0.233420E+10 | 0.736300E+10 | 0.146160E+10 |
Minimum of Months | 0.228467E+09 | 0.103631E+09 | 0.124835E+09 | 0.309159E+09 | 1126100.65 |
Maximum of Months | 0.415601E+09 | 0.180422E+09 | 0.257451E+09 | 0.889225E+09 | 0.330829E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73868613.95 | 0.00 | 73868613.95 | 61478539.77 | 0.265260E+09 |
February | 78713543.66 | 0.00 | 78713543.66 | 77693551.16 | 0.195083E+09 |
March | 0.101115E+09 | 1425.70 | 0.101113E+09 | 0.124601E+09 | 0.175461E+09 |
April | 0.115922E+09 | 782400.21 | 0.115140E+09 | 0.189026E+09 | 90793565.82 |
May | 0.135265E+09 | 4947686.39 | 0.130317E+09 | 0.319073E+09 | 11110889.11 |
June | 0.148859E+09 | 10434956.47 | 0.138425E+09 | 0.356657E+09 | 8129555.42 |
July | 0.149314E+09 | 5766526.54 | 0.143547E+09 | 0.363377E+09 | 3116635.25 |
August | 0.134029E+09 | 1336212.06 | 0.132693E+09 | 0.327403E+09 | 8005600.83 |
September | 0.111717E+09 | 30185.32 | 0.111687E+09 | 0.252391E+09 | 14205986.88 |
October | 0.100256E+09 | 0.00 | 0.100256E+09 | 0.209064E+09 | 53061229.52 |
November | 73655370.47 | 0.00 | 73655370.47 | 94033823.40 | 0.149782E+09 |
December | 68669272.70 | 0.00 | 68669272.70 | 67356073.69 | 0.220148E+09 |
Annual Sum or Average | 0.129138E+10 | 23299392.69 | 0.126808E+10 | 0.244215E+10 | 0.119416E+10 |
Minimum of Months | 68669272.70 | 0.00 | 68669272.70 | 61478539.77 | 3116635.25 |
Maximum of Months | 0.149314E+09 | 10434956.47 | 0.143547E+09 | 0.363377E+09 | 0.265260E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27231029.76 | 0.00 | 27231029.76 | 22663535.38 | 97785820.43 |
February | 29017071.47 | 0.00 | 29017071.47 | 28641060.00 | 71915838.63 |
March | 37275077.18 | 525.57 | 37274551.61 | 45933181.95 | 64682131.99 |
April | 42733688.92 | 288425.11 | 42445263.80 | 69682815.49 | 33470267.83 |
May | 49864126.46 | 1823922.07 | 48040204.39 | 0.117624E+09 | 4095933.79 |
June | 54875764.31 | 3846757.03 | 51029007.28 | 0.131478E+09 | 2996890.74 |
July | 55043169.53 | 2125780.45 | 52917389.08 | 0.133956E+09 | 1148920.80 |
August | 49408735.40 | 492583.09 | 48916152.31 | 0.120694E+09 | 2951195.95 |
September | 41183445.79 | 11127.56 | 41172318.23 | 93041819.76 | 5236914.99 |
October | 36958594.00 | 0.00 | 36958594.00 | 77069558.36 | 19560566.29 |
November | 27152419.38 | 0.00 | 27152419.38 | 34664760.94 | 55215922.76 |
December | 25314337.29 | 0.00 | 25314337.29 | 24830237.76 | 81155731.81 |
Annual Sum or Average | 0.476057E+09 | 8589120.90 | 0.467468E+09 | 0.900279E+09 | 0.440216E+09 |
Minimum of Months | 25314337.29 | 0.00 | 25314337.29 | 22663535.38 | 1148920.80 |
Maximum of Months | 55043169.53 | 3846757.03 | 52917389.08 | 0.133956E+09 | 97785820.43 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.157548E+09 | 0.112418E+09 | 45129670.62 | 0.236525E+09 | 85668634.04 |
February | 0.128065E+09 | 82589773.70 | 45475363.27 | 0.197875E+09 | 64186811.34 |
March | 92587934.17 | 42609707.25 | 49978226.92 | 0.148950E+09 | 61847631.78 |
April | 65396032.81 | 15353231.71 | 50042801.11 | 0.119745E+09 | 33996028.62 |
May | 51980206.15 | 2561745.07 | 49418461.08 | 0.123107E+09 | 4127406.86 |
June | 49285770.05 | 430860.76 | 48854909.28 | 0.119634E+09 | 3078004.33 |
July | 53245623.69 | 872283.67 | 52373340.02 | 0.130445E+09 | 1133775.16 |
August | 61640378.36 | 6391970.91 | 55248407.45 | 0.147398E+09 | 2972211.88 |
September | 73144424.01 | 19471671.88 | 53672752.13 | 0.156796E+09 | 5236927.09 |
October | 0.115644E+09 | 59663650.55 | 55980304.17 | 0.220168E+09 | 18750870.60 |
November | 0.145239E+09 | 0.100409E+09 | 44829974.66 | 0.237080E+09 | 49835283.94 |
December | 0.153994E+09 | 0.110672E+09 | 43322529.31 | 0.239707E+09 | 73598154.04 |
Annual Sum or Average | 0.114777E+10 | 0.553444E+09 | 0.594327E+09 | 0.207743E+10 | 0.404432E+09 |
Minimum of Months | 49285770.05 | 430860.76 | 43322529.31 | 0.119634E+09 | 1133775.16 |
Maximum of Months | 0.157548E+09 | 0.112418E+09 | 55980304.17 | 0.239707E+09 | 85668634.04 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427618E+09 | 0.305126E+09 | 0.122491E+09 | 0.641977E+09 | 0.232522E+09 |
February | 0.347595E+09 | 0.224166E+09 | 0.123429E+09 | 0.537072E+09 | 0.174216E+09 |
March | 0.251303E+09 | 0.115651E+09 | 0.135651E+09 | 0.404281E+09 | 0.167867E+09 |
April | 0.177498E+09 | 41671811.28 | 0.135826E+09 | 0.325011E+09 | 92272175.41 |
May | 0.141085E+09 | 6953100.12 | 0.134132E+09 | 0.334138E+09 | 11202626.47 |
June | 0.133772E+09 | 1169444.24 | 0.132602E+09 | 0.324711E+09 | 8354333.34 |
July | 0.144520E+09 | 2367556.29 | 0.142152E+09 | 0.354055E+09 | 3077297.69 |
August | 0.167305E+09 | 17349116.49 | 0.149955E+09 | 0.400068E+09 | 8067231.61 |
September | 0.198529E+09 | 52850100.32 | 0.145679E+09 | 0.425577E+09 | 14214091.30 |
October | 0.313881E+09 | 0.161939E+09 | 0.151942E+09 | 0.597580E+09 | 50893698.22 |
November | 0.394209E+09 | 0.272531E+09 | 0.121678E+09 | 0.643483E+09 | 0.135263E+09 |
December | 0.417971E+09 | 0.300385E+09 | 0.117586E+09 | 0.650614E+09 | 0.199760E+09 |
Annual Sum or Average | 0.311528E+10 | 0.150216E+10 | 0.161312E+10 | 0.563857E+10 | 0.109771E+10 |
Minimum of Months | 0.133772E+09 | 1169444.24 | 0.117586E+09 | 0.324711E+09 | 3077297.69 |
Maximum of Months | 0.427618E+09 | 0.305126E+09 | 0.151942E+09 | 0.650614E+09 | 0.232522E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.337654E+09 | 0.240933E+09 | 96721089.53 | 0.496744E+09 | 0.173960E+09 |
February | 0.274467E+09 | 0.177005E+09 | 97461971.73 | 0.413892E+09 | 0.130067E+09 |
March | 0.198433E+09 | 91320349.86 | 0.107112E+09 | 0.309896E+09 | 0.121209E+09 |
April | 0.140156E+09 | 32904767.04 | 0.107251E+09 | 0.248015E+09 | 62405633.49 |
May | 0.111403E+09 | 5490285.46 | 0.105913E+09 | 0.270466E+09 | 3104954.90 |
June | 0.105628E+09 | 923412.95 | 0.104705E+09 | 0.264870E+09 | 1985163.22 |
July | 0.114115E+09 | 1869462.49 | 0.112246E+09 | 0.293734E+09 | 245592.74 |
August | 0.132107E+09 | 13699155.83 | 0.118407E+09 | 0.326205E+09 | 1851455.99 |
September | 0.156762E+09 | 41731333.14 | 0.115030E+09 | 0.342586E+09 | 3097565.72 |
October | 0.247846E+09 | 0.127870E+09 | 0.119976E+09 | 0.474769E+09 | 28434928.72 |
November | 0.311274E+09 | 0.215195E+09 | 96078786.59 | 0.501603E+09 | 93511602.53 |
December | 0.330037E+09 | 0.237189E+09 | 92848057.14 | 0.505340E+09 | 0.144893E+09 |
Annual Sum or Average | 0.245988E+10 | 0.118613E+10 | 0.127375E+10 | 0.444812E+10 | 0.764766E+09 |
Minimum of Months | 0.105628E+09 | 923412.95 | 92848057.14 | 0.248015E+09 | 245592.74 |
Maximum of Months | 0.337654E+09 | 0.240933E+09 | 0.119976E+09 | 0.505340E+09 | 0.173960E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.298244E+09 | 0.161272E+09 | 0.136972E+09 | 0.387902E+09 | 0.353444E+09 |
February | 0.305712E+09 | 0.155000E+09 | 0.150712E+09 | 0.417985E+09 | 0.260081E+09 |
March | 0.331836E+09 | 0.146390E+09 | 0.185446E+09 | 0.477084E+09 | 0.229761E+09 |
April | 0.399253E+09 | 0.183461E+09 | 0.215793E+09 | 0.661331E+09 | 0.113143E+09 |
May | 0.343981E+09 | 0.112169E+09 | 0.231812E+09 | 0.737404E+09 | 5690781.72 |
June | 0.369411E+09 | 0.129617E+09 | 0.239794E+09 | 0.800550E+09 | 3653393.38 |
July | 0.347950E+09 | 96224762.86 | 0.251726E+09 | 0.785608E+09 | 443223.74 |
August | 0.351619E+09 | 0.106906E+09 | 0.244713E+09 | 0.775848E+09 | 3366501.28 |
September | 0.314066E+09 | 0.107744E+09 | 0.206321E+09 | 0.649933E+09 | 5495657.96 |
October | 0.333003E+09 | 0.144272E+09 | 0.188731E+09 | 0.641554E+09 | 54793196.18 |
November | 0.275471E+09 | 0.138400E+09 | 0.137071E+09 | 0.421577E+09 | 0.188385E+09 |
December | 0.272884E+09 | 0.144687E+09 | 0.128198E+09 | 0.379610E+09 | 0.286735E+09 |
Annual Sum or Average | 0.394343E+10 | 0.162614E+10 | 0.231729E+10 | 0.713639E+10 | 0.150499E+10 |
Minimum of Months | 0.272884E+09 | 96224762.86 | 0.128198E+09 | 0.379610E+09 | 443223.74 |
Maximum of Months | 0.399253E+09 | 0.183461E+09 | 0.251726E+09 | 0.800550E+09 | 0.353444E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58327907.02 | 0.00 | 58327907.02 | 49092139.24 | 0.193894E+09 |
February | 62153545.47 | 0.00 | 62153545.47 | 58566075.85 | 0.145794E+09 |
March | 79841902.97 | 1125.76 | 79840777.21 | 92279092.93 | 0.130733E+09 |
April | 91534057.12 | 617796.44 | 90916260.68 | 0.139183E+09 | 68567996.39 |
May | 0.106807E+09 | 3906776.86 | 0.102900E+09 | 0.256891E+09 | 3631981.69 |
June | 0.117542E+09 | 8239618.13 | 0.109302E+09 | 0.288692E+09 | 2164850.82 |
July | 0.117901E+09 | 4553346.89 | 0.113347E+09 | 0.299506E+09 | 694376.65 |
August | 0.105832E+09 | 1055095.64 | 0.104777E+09 | 0.268871E+09 | 2747795.89 |
September | 88213490.93 | 23834.84 | 88189656.09 | 0.205930E+09 | 5316764.54 |
October | 79164007.13 | 0.00 | 79164007.13 | 0.172070E+09 | 31923072.72 |
November | 58159526.36 | 0.00 | 58159526.36 | 74809348.89 | 0.104283E+09 |
December | 54222419.22 | 0.00 | 54222419.22 | 53867723.54 | 0.157515E+09 |
Annual Sum or Average | 0.101970E+10 | 18397594.56 | 0.100130E+10 | 0.195976E+10 | 0.847265E+09 |
Minimum of Months | 54222419.22 | 0.00 | 54222419.22 | 49092139.24 | 694376.65 |
Maximum of Months | 0.117901E+09 | 8239618.13 | 0.113347E+09 | 0.299506E+09 | 0.193894E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.298244E+09 | 0.161272E+09 | 0.136972E+09 | 0.403417E+09 | 0.345800E+09 |
February | 0.305712E+09 | 0.155000E+09 | 0.150712E+09 | 0.427573E+09 | 0.259449E+09 |
March | 0.331836E+09 | 0.146390E+09 | 0.185446E+09 | 0.479139E+09 | 0.235661E+09 |
April | 0.399253E+09 | 0.183461E+09 | 0.215793E+09 | 0.655002E+09 | 0.124882E+09 |
May | 0.343981E+09 | 0.112169E+09 | 0.231812E+09 | 0.734126E+09 | 6623626.27 |
June | 0.369411E+09 | 0.129617E+09 | 0.239794E+09 | 0.797955E+09 | 4195176.29 |
July | 0.347950E+09 | 96224762.86 | 0.251726E+09 | 0.783318E+09 | 1223198.80 |
August | 0.351619E+09 | 0.106906E+09 | 0.244713E+09 | 0.774833E+09 | 4936248.67 |
September | 0.314066E+09 | 0.107744E+09 | 0.206321E+09 | 0.648306E+09 | 9472536.07 |
October | 0.333003E+09 | 0.144272E+09 | 0.188731E+09 | 0.645550E+09 | 58482875.57 |
November | 0.275471E+09 | 0.138400E+09 | 0.137071E+09 | 0.430777E+09 | 0.188780E+09 |
December | 0.272884E+09 | 0.144687E+09 | 0.128198E+09 | 0.392022E+09 | 0.282638E+09 |
Annual Sum or Average | 0.394343E+10 | 0.162614E+10 | 0.231729E+10 | 0.717202E+10 | 0.152215E+10 |
Minimum of Months | 0.272884E+09 | 96224762.86 | 0.128198E+09 | 0.392022E+09 | 1223198.80 |
Maximum of Months | 0.399253E+09 | 0.183461E+09 | 0.251726E+09 | 0.797955E+09 | 0.345800E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.495202E+09 | 0.353351E+09 | 0.141851E+09 | 0.714978E+09 | 0.265361E+09 |
February | 0.402532E+09 | 0.259595E+09 | 0.142937E+09 | 0.598330E+09 | 0.196064E+09 |
March | 0.291021E+09 | 0.133930E+09 | 0.157091E+09 | 0.451301E+09 | 0.180142E+09 |
April | 0.205552E+09 | 48257998.75 | 0.157294E+09 | 0.368924E+09 | 87870701.15 |
May | 0.163383E+09 | 8052030.53 | 0.155331E+09 | 0.408653E+09 | 3440611.62 |
June | 0.154914E+09 | 1354273.71 | 0.153560E+09 | 0.402641E+09 | 2278559.25 |
July | 0.167361E+09 | 2741746.16 | 0.164619E+09 | 0.444575E+09 | 199701.20 |
August | 0.193747E+09 | 20091126.73 | 0.173656E+09 | 0.490253E+09 | 2170241.15 |
September | 0.229906E+09 | 61203005.02 | 0.168703E+09 | 0.509755E+09 | 3676234.85 |
October | 0.363490E+09 | 0.187534E+09 | 0.175956E+09 | 0.697974E+09 | 41425962.76 |
November | 0.456513E+09 | 0.315604E+09 | 0.140909E+09 | 0.728688E+09 | 0.141348E+09 |
December | 0.484031E+09 | 0.347861E+09 | 0.136171E+09 | 0.730432E+09 | 0.221588E+09 |
Annual Sum or Average | 0.360765E+10 | 0.173958E+10 | 0.186808E+10 | 0.654650E+10 | 0.114557E+10 |
Minimum of Months | 0.154914E+09 | 1354273.71 | 0.136171E+09 | 0.368924E+09 | 199701.20 |
Maximum of Months | 0.495202E+09 | 0.353351E+09 | 0.175956E+09 | 0.730432E+09 | 0.265361E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.408280E+09 | 0.00 | 0.408280E+09 | 0.319095E+09 | 0.156572E+10 |
February | 0.435058E+09 | 0.00 | 0.435058E+09 | 0.406708E+09 | 0.116819E+10 |
March | 0.558872E+09 | 7880.00 | 0.558864E+09 | 0.653519E+09 | 0.107943E+10 |
April | 0.640714E+09 | 4324411.30 | 0.636390E+09 | 0.101462E+10 | 0.570789E+09 |
May | 0.747622E+09 | 27346402.29 | 0.720276E+09 | 0.174237E+10 | 91259660.90 |
June | 0.822763E+09 | 57675142.49 | 0.765087E+09 | 0.195993E+10 | 70285795.04 |
July | 0.825272E+09 | 31872221.09 | 0.793400E+09 | 0.199884E+10 | 31668497.43 |
August | 0.740794E+09 | 7385389.76 | 0.733409E+09 | 0.180292E+10 | 64543369.23 |
September | 0.617471E+09 | 166837.56 | 0.617304E+09 | 0.140700E+10 | 0.110738E+09 |
October | 0.554127E+09 | 0.00 | 0.554127E+09 | 0.118143E+10 | 0.322048E+09 |
November | 0.407101E+09 | 0.00 | 0.407101E+09 | 0.520779E+09 | 0.870946E+09 |
December | 0.379543E+09 | 0.00 | 0.379543E+09 | 0.360076E+09 | 0.130373E+10 |
Annual Sum or Average | 0.713762E+10 | 0.128778E+09 | 0.700884E+10 | 0.133673E+11 | 0.724934E+10 |
Minimum of Months | 0.379543E+09 | 0.00 | 0.379543E+09 | 0.319095E+09 | 31668497.43 |
Maximum of Months | 0.825272E+09 | 57675142.49 | 0.793400E+09 | 0.199884E+10 | 0.156572E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.408280E+09 | 0.00 | 0.408280E+09 | 0.298159E+09 | 0.163478E+10 |
February | 0.435058E+09 | 0.00 | 0.435058E+09 | 0.384737E+09 | 0.122274E+10 |
March | 0.558872E+09 | 7880.00 | 0.558864E+09 | 0.623500E+09 | 0.113463E+10 |
April | 0.640714E+09 | 4324411.30 | 0.636390E+09 | 0.980436E+09 | 0.606005E+09 |
May | 0.747622E+09 | 27346402.29 | 0.720276E+09 | 0.169194E+10 | 0.111350E+09 |
June | 0.822763E+09 | 57675142.49 | 0.765087E+09 | 0.190946E+10 | 86473498.07 |
July | 0.825272E+09 | 31872221.09 | 0.793400E+09 | 0.194148E+10 | 43343037.65 |
August | 0.740794E+09 | 7385389.76 | 0.733409E+09 | 0.174969E+10 | 81093861.29 |
September | 0.617471E+09 | 166837.56 | 0.617304E+09 | 0.136342E+10 | 0.135101E+09 |
October | 0.554127E+09 | 0.00 | 0.554127E+09 | 0.114021E+10 | 0.351274E+09 |
November | 0.407101E+09 | 0.00 | 0.407101E+09 | 0.496451E+09 | 0.916301E+09 |
December | 0.379543E+09 | 0.00 | 0.379543E+09 | 0.339400E+09 | 0.136615E+10 |
Annual Sum or Average | 0.713762E+10 | 0.128778E+09 | 0.700884E+10 | 0.129189E+11 | 0.768923E+10 |
Minimum of Months | 0.379543E+09 | 0.00 | 0.379543E+09 | 0.298159E+09 | 43343037.65 |
Maximum of Months | 0.825272E+09 | 57675142.49 | 0.793400E+09 | 0.194148E+10 | 0.163478E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58327907.02 | 0.00 | 58327907.02 | 52035139.43 | 0.235335E+09 |
February | 62153545.47 | 0.00 | 62153545.47 | 67796299.52 | 0.175312E+09 |
March | 79841902.97 | 1125.76 | 79840777.21 | 0.105382E+09 | 0.166339E+09 |
April | 91534057.12 | 617796.44 | 90916260.68 | 0.168159E+09 | 88639246.88 |
May | 0.106807E+09 | 3906776.86 | 0.102900E+09 | 0.283619E+09 | 22622908.59 |
June | 0.117542E+09 | 8239618.13 | 0.109302E+09 | 0.319522E+09 | 19016682.92 |
July | 0.117901E+09 | 4553346.89 | 0.113347E+09 | 0.322902E+09 | 11812593.46 |
August | 0.105832E+09 | 1055095.64 | 0.104777E+09 | 0.291843E+09 | 17324946.32 |
September | 88213490.93 | 23834.84 | 88189656.09 | 0.231018E+09 | 24861033.48 |
October | 79164007.13 | 0.00 | 79164007.13 | 0.192390E+09 | 55481317.29 |
November | 58159526.36 | 0.00 | 58159526.36 | 89386380.11 | 0.128977E+09 |
December | 54222419.22 | 0.00 | 54222419.22 | 61017824.22 | 0.195160E+09 |
Annual Sum or Average | 0.101970E+10 | 18397594.56 | 0.100130E+10 | 0.218507E+10 | 0.114088E+10 |
Minimum of Months | 54222419.22 | 0.00 | 54222419.22 | 52035139.43 | 11812593.46 |
Maximum of Months | 0.117901E+09 | 8239618.13 | 0.113347E+09 | 0.322902E+09 | 0.235335E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559760E+09 | 0.284717E+09 | 0.275043E+09 | 0.732914E+09 | 0.808260E+09 |
February | 0.564688E+09 | 0.272618E+09 | 0.292069E+09 | 0.797562E+09 | 0.602302E+09 |
March | 0.736248E+09 | 0.355475E+09 | 0.380773E+09 | 0.112231E+10 | 0.582534E+09 |
April | 0.780791E+09 | 0.352866E+09 | 0.427926E+09 | 0.139560E+10 | 0.323973E+09 |
May | 0.831143E+09 | 0.360817E+09 | 0.470326E+09 | 0.180647E+10 | 85617975.31 |
June | 0.814216E+09 | 0.322573E+09 | 0.491643E+09 | 0.184566E+10 | 71755104.50 |
July | 0.812180E+09 | 0.297315E+09 | 0.514865E+09 | 0.185980E+10 | 44960235.76 |
August | 0.748856E+09 | 0.257686E+09 | 0.491170E+09 | 0.170923E+10 | 65347583.51 |
September | 0.641024E+09 | 0.220281E+09 | 0.420744E+09 | 0.141301E+10 | 93826716.91 |
October | 0.655551E+09 | 0.276837E+09 | 0.378714E+09 | 0.134368E+10 | 0.202008E+09 |
November | 0.560455E+09 | 0.285315E+09 | 0.275140E+09 | 0.917813E+09 | 0.451184E+09 |
December | 0.456901E+09 | 0.207248E+09 | 0.249653E+09 | 0.650281E+09 | 0.691395E+09 |
Annual Sum or Average | 0.816181E+10 | 0.349375E+10 | 0.466807E+10 | 0.155943E+11 | 0.402316E+10 |
Minimum of Months | 0.456901E+09 | 0.207248E+09 | 0.249653E+09 | 0.650281E+09 | 44960235.76 |
Maximum of Months | 0.831143E+09 | 0.360817E+09 | 0.514865E+09 | 0.185980E+10 | 0.808260E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.337654E+09 | 0.240933E+09 | 96721089.53 | 0.515347E+09 | 0.208740E+09 |
February | 0.274467E+09 | 0.177005E+09 | 97461971.73 | 0.433465E+09 | 0.157586E+09 |
March | 0.198433E+09 | 91320349.86 | 0.107112E+09 | 0.328471E+09 | 0.159032E+09 |
April | 0.140156E+09 | 32904767.04 | 0.107251E+09 | 0.275839E+09 | 89496783.05 |
May | 0.111403E+09 | 5490285.46 | 0.105913E+09 | 0.295119E+09 | 22692811.60 |
June | 0.105628E+09 | 923412.95 | 0.104705E+09 | 0.294657E+09 | 19137705.81 |
July | 0.114115E+09 | 1869462.49 | 0.112246E+09 | 0.314520E+09 | 11870640.04 |
August | 0.132107E+09 | 13699155.83 | 0.118407E+09 | 0.349133E+09 | 17382415.09 |
September | 0.156762E+09 | 41731333.14 | 0.115030E+09 | 0.368745E+09 | 24855703.24 |
October | 0.247846E+09 | 0.127870E+09 | 0.119976E+09 | 0.503377E+09 | 53407485.68 |
November | 0.311274E+09 | 0.215195E+09 | 96078786.59 | 0.529394E+09 | 0.119502E+09 |
December | 0.330037E+09 | 0.237189E+09 | 92848057.14 | 0.526948E+09 | 0.178854E+09 |
Annual Sum or Average | 0.245988E+10 | 0.118613E+10 | 0.127375E+10 | 0.473502E+10 | 0.106256E+10 |
Minimum of Months | 0.105628E+09 | 923412.95 | 92848057.14 | 0.275839E+09 | 11870640.04 |
Maximum of Months | 0.337654E+09 | 0.240933E+09 | 0.119976E+09 | 0.529394E+09 | 0.208740E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73868613.95 | 0.00 | 73868613.95 | 49255516.82 | 0.292150E+09 |
February | 78713543.66 | 0.00 | 78713543.66 | 62823204.88 | 0.220572E+09 |
March | 0.101115E+09 | 1425.70 | 0.101113E+09 | 0.104276E+09 | 0.202971E+09 |
April | 0.115922E+09 | 782400.21 | 0.115140E+09 | 0.162852E+09 | 0.114446E+09 |
May | 0.135265E+09 | 4947686.39 | 0.130317E+09 | 0.288651E+09 | 20842904.89 |
June | 0.148859E+09 | 10434956.47 | 0.138425E+09 | 0.329054E+09 | 15796557.30 |
July | 0.149314E+09 | 5766526.54 | 0.143547E+09 | 0.334168E+09 | 8179413.11 |
August | 0.134029E+09 | 1336212.06 | 0.132693E+09 | 0.299093E+09 | 15004905.68 |
September | 0.111717E+09 | 30185.32 | 0.111687E+09 | 0.229476E+09 | 25787582.39 |
October | 0.100256E+09 | 0.00 | 0.100256E+09 | 0.187876E+09 | 66907335.21 |
November | 73655370.47 | 0.00 | 73655370.47 | 77406615.18 | 0.175217E+09 |
December | 68669272.70 | 0.00 | 68669272.70 | 53848108.28 | 0.247672E+09 |
Annual Sum or Average | 0.129138E+10 | 23299392.69 | 0.126808E+10 | 0.217878E+10 | 0.140555E+10 |
Minimum of Months | 68669272.70 | 0.00 | 68669272.70 | 49255516.82 | 8179413.11 |
Maximum of Months | 0.149314E+09 | 10434956.47 | 0.143547E+09 | 0.334168E+09 | 0.292150E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66090528.79 | 0.00 | 66090528.79 | 44069097.53 | 0.261380E+09 |
February | 70425305.76 | 0.00 | 70425305.76 | 56208159.44 | 0.197347E+09 |
March | 90467734.17 | 1275.58 | 90466458.59 | 93295729.73 | 0.181599E+09 |
April | 0.103716E+09 | 700016.43 | 0.103016E+09 | 0.145705E+09 | 0.102395E+09 |
May | 0.121022E+09 | 4426713.76 | 0.116595E+09 | 0.258257E+09 | 18648225.98 |
June | 0.133185E+09 | 9336195.09 | 0.123849E+09 | 0.294406E+09 | 14133239.67 |
July | 0.133591E+09 | 5159333.14 | 0.128432E+09 | 0.298982E+09 | 7318151.90 |
August | 0.119916E+09 | 1195513.99 | 0.118721E+09 | 0.267600E+09 | 13424945.96 |
September | 99953462.42 | 27006.92 | 99926455.50 | 0.205313E+09 | 23072247.67 |
October | 89699619.96 | 0.00 | 89699619.96 | 0.168093E+09 | 59862380.98 |
November | 65899739.04 | 0.00 | 65899739.04 | 69255991.89 | 0.156767E+09 |
December | 61438658.47 | 0.00 | 61438658.47 | 48178106.51 | 0.221589E+09 |
Annual Sum or Average | 0.115541E+10 | 20846054.92 | 0.113456E+10 | 0.194936E+10 | 0.125754E+10 |
Minimum of Months | 61438658.47 | 0.00 | 61438658.47 | 44069097.53 | 7318151.90 |
Maximum of Months | 0.133591E+09 | 9336195.09 | 0.128432E+09 | 0.298982E+09 | 0.261380E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126056E+10 | 0.899475E+09 | 0.361089E+09 | 0.182524E+10 | 0.746714E+09 |
February | 0.102467E+10 | 0.660812E+09 | 0.363855E+09 | 0.151485E+10 | 0.575151E+09 |
March | 0.740809E+09 | 0.340926E+09 | 0.399883E+09 | 0.111792E+10 | 0.570242E+09 |
April | 0.523243E+09 | 0.122843E+09 | 0.400399E+09 | 0.877530E+09 | 0.343057E+09 |
May | 0.415901E+09 | 20496871.65 | 0.395404E+09 | 0.895961E+09 | 63056433.02 |
June | 0.394342E+09 | 3447375.71 | 0.390895E+09 | 0.877033E+09 | 48389701.63 |
July | 0.426025E+09 | 6979260.55 | 0.419046E+09 | 0.958128E+09 | 24095115.12 |
August | 0.493193E+09 | 51143030.85 | 0.442050E+09 | 0.109410E+10 | 45331028.25 |
September | 0.585239E+09 | 0.155796E+09 | 0.429443E+09 | 0.118266E+10 | 76390332.87 |
October | 0.925283E+09 | 0.477377E+09 | 0.447906E+09 | 0.168855E+10 | 0.189371E+09 |
November | 0.116208E+10 | 0.803387E+09 | 0.358691E+09 | 0.182571E+10 | 0.462853E+09 |
December | 0.123213E+10 | 0.885498E+09 | 0.346629E+09 | 0.185210E+10 | 0.655549E+09 |
Annual Sum or Average | 0.918347E+10 | 0.442818E+10 | 0.475529E+10 | 0.157098E+11 | 0.380020E+10 |
Minimum of Months | 0.394342E+09 | 3447375.71 | 0.346629E+09 | 0.877033E+09 | 24095115.12 |
Maximum of Months | 0.126056E+10 | 0.899475E+09 | 0.447906E+09 | 0.185210E+10 | 0.746714E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 924.75 | 361.00 | 637.60 | 454.96 | 182.64 | 0.00 | 0.00 |
February | 851.53 | 306.51 | 573.82 | 370.06 | 203.76 | 0.00 | 0.00 |
March | 576.23 | 263.05 | 374.71 | 172.44 | 202.26 | 0.00 | 0.00 |
April | 467.09 | 163.85 | 273.48 | 64.21 | 209.27 | 0.00 | 0.00 |
May | 444.59 | 35.08 | 210.36 | 10.37 | 200.00 | 0.00 | 0.00 |
June | 445.74 | 28.87 | 206.11 | 1.80 | 204.31 | 0.00 | 0.00 |
July | 468.54 | 15.63 | 215.49 | 3.53 | 211.96 | 0.00 | 0.00 |
August | 539.32 | 27.86 | 249.46 | 25.87 | 223.59 | 0.00 | 0.00 |
September | 609.02 | 45.28 | 305.88 | 81.43 | 224.46 | 0.00 | 0.00 |
October | 849.15 | 98.39 | 468.02 | 241.46 | 226.55 | 0.00 | 0.00 |
November | 953.81 | 233.74 | 607.38 | 419.91 | 187.48 | 0.00 | 0.00 |
December | 938.62 | 315.28 | 623.22 | 447.89 | 175.33 | 0.00 | 0.00 |
Annual Sum or Average | 671.48 | 157.09 | 394.51 | 190.23 | 204.28 | 0.00 | 0.00 |
Minimum of Months | 444.59 | 15.63 | 206.11 | 1.80 | 175.33 | 0.00 | 0.00 |
Maximum of Months | 953.81 | 361.00 | 637.60 | 454.96 | 226.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2631.30 | 996.92 | 1795.45 | 1281.15 | 514.30 | 0.00 | 0.00 |
February | 2433.30 | 832.91 | 1615.83 | 1042.06 | 573.77 | 0.00 | 0.00 |
March | 1665.80 | 712.96 | 1055.15 | 485.59 | 569.56 | 0.00 | 0.00 |
April | 1392.99 | 407.51 | 770.10 | 180.80 | 589.30 | 0.00 | 0.00 |
May | 1382.60 | 60.66 | 592.37 | 29.19 | 563.18 | 0.00 | 0.00 |
June | 1390.46 | 46.15 | 580.39 | 5.07 | 575.31 | 0.00 | 0.00 |
July | 1459.97 | 19.35 | 606.79 | 9.94 | 596.85 | 0.00 | 0.00 |
August | 1640.14 | 46.59 | 702.46 | 72.84 | 629.62 | 0.00 | 0.00 |
September | 1810.85 | 84.14 | 861.35 | 229.30 | 632.05 | 0.00 | 0.00 |
October | 2454.16 | 238.37 | 1317.90 | 679.94 | 637.96 | 0.00 | 0.00 |
November | 2722.09 | 615.30 | 1710.35 | 1182.43 | 527.92 | 0.00 | 0.00 |
December | 2665.11 | 863.19 | 1754.95 | 1261.24 | 493.71 | 0.00 | 0.00 |
Annual Sum or Average | 1968.48 | 408.20 | 1110.92 | 535.68 | 575.24 | 0.00 | 0.00 |
Minimum of Months | 1382.60 | 19.35 | 580.39 | 5.07 | 493.71 | 0.00 | 0.00 |
Maximum of Months | 2722.09 | 996.92 | 1795.45 | 1281.15 | 637.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3470.57 | 1371.09 | 2332.39 | 1664.28 | 668.11 | 0.00 | 0.00 |
February | 3206.63 | 1155.31 | 2099.05 | 1353.69 | 745.36 | 0.00 | 0.00 |
March | 2182.79 | 1009.04 | 1370.70 | 630.81 | 739.89 | 0.00 | 0.00 |
April | 1804.46 | 598.55 | 1000.41 | 234.87 | 765.54 | 0.00 | 0.00 |
May | 1761.43 | 107.48 | 769.53 | 37.93 | 731.60 | 0.00 | 0.00 |
June | 1768.79 | 87.10 | 753.96 | 6.59 | 747.37 | 0.00 | 0.00 |
July | 1856.51 | 43.87 | 788.26 | 12.91 | 775.35 | 0.00 | 0.00 |
August | 2109.67 | 83.68 | 912.54 | 94.63 | 817.91 | 0.00 | 0.00 |
September | 2351.66 | 141.58 | 1118.95 | 297.87 | 821.07 | 0.00 | 0.00 |
October | 3228.38 | 339.79 | 1712.03 | 883.28 | 828.75 | 0.00 | 0.00 |
November | 3590.31 | 852.33 | 2221.84 | 1536.04 | 685.80 | 0.00 | 0.00 |
December | 3516.09 | 1192.59 | 2279.78 | 1638.42 | 641.36 | 0.00 | 0.00 |
Annual Sum or Average | 2567.48 | 578.93 | 1443.15 | 695.88 | 747.27 | 0.00 | 0.00 |
Minimum of Months | 1761.43 | 43.87 | 753.96 | 6.59 | 641.36 | 0.00 | 0.00 |
Maximum of Months | 3590.31 | 1371.09 | 2332.39 | 1664.28 | 828.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 326.24 | 192.11 | 237.42 | 150.17 | 87.25 | 0.00 | 0.00 |
February | 342.71 | 158.45 | 239.82 | 137.24 | 102.59 | 0.00 | 0.00 |
March | 295.66 | 131.50 | 197.98 | 88.75 | 109.23 | 0.00 | 0.00 |
April | 354.49 | 68.45 | 208.11 | 83.47 | 124.63 | 0.00 | 0.00 |
May | 378.99 | 3.66 | 170.02 | 43.93 | 126.09 | 0.00 | 0.00 |
June | 414.07 | 2.44 | 183.27 | 50.36 | 132.91 | 0.00 | 0.00 |
July | 405.27 | 0.30 | 172.52 | 36.62 | 135.89 | 0.00 | 0.00 |
August | 413.89 | 2.15 | 180.60 | 45.03 | 135.57 | 0.00 | 0.00 |
September | 384.99 | 3.60 | 181.65 | 57.67 | 123.98 | 0.00 | 0.00 |
October | 419.10 | 31.88 | 216.86 | 101.61 | 115.26 | 0.00 | 0.00 |
November | 355.30 | 107.57 | 226.37 | 136.42 | 89.95 | 0.00 | 0.00 |
December | 328.69 | 159.37 | 225.11 | 142.58 | 82.53 | 0.00 | 0.00 |
Annual Sum or Average | 368.40 | 71.36 | 203.05 | 89.18 | 113.87 | 0.00 | 0.00 |
Minimum of Months | 295.66 | 0.30 | 170.02 | 36.62 | 82.53 | 0.00 | 0.00 |
Maximum of Months | 419.10 | 192.11 | 239.82 | 150.17 | 135.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 166.52 | 200.94 | 133.13 | 60.21 | 72.92 | 0.00 | 0.00 |
February | 200.40 | 166.83 | 152.06 | 64.07 | 87.99 | 0.00 | 0.00 |
March | 214.69 | 136.73 | 153.70 | 54.66 | 99.05 | 0.00 | 0.00 |
April | 310.01 | 74.15 | 189.35 | 71.02 | 118.33 | 0.00 | 0.00 |
May | 372.65 | 4.17 | 168.31 | 43.34 | 124.97 | 0.00 | 0.00 |
June | 422.26 | 2.70 | 187.87 | 53.19 | 134.68 | 0.00 | 0.00 |
July | 406.87 | 0.67 | 173.93 | 37.63 | 136.30 | 0.00 | 0.00 |
August | 391.87 | 2.99 | 170.79 | 40.31 | 130.48 | 0.00 | 0.00 |
September | 331.31 | 5.86 | 155.20 | 41.58 | 113.62 | 0.00 | 0.00 |
October | 306.36 | 34.73 | 153.89 | 53.86 | 100.02 | 0.00 | 0.00 |
November | 194.78 | 114.82 | 128.72 | 53.40 | 75.32 | 0.00 | 0.00 |
December | 165.08 | 165.26 | 122.13 | 54.02 | 68.11 | 0.00 | 0.00 |
Annual Sum or Average | 290.71 | 75.36 | 157.38 | 52.15 | 105.23 | 0.00 | 0.00 |
Minimum of Months | 165.08 | 0.67 | 122.13 | 37.63 | 68.11 | 0.00 | 0.00 |
Maximum of Months | 422.26 | 200.94 | 189.35 | 71.02 | 136.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 134.66 | 78.98 | 100.83 | 71.95 | 28.88 | 0.00 | 0.00 |
February | 123.44 | 68.04 | 90.74 | 58.52 | 32.22 | 0.00 | 0.00 |
March | 80.65 | 61.32 | 59.26 | 27.27 | 31.99 | 0.00 | 0.00 |
April | 64.03 | 40.49 | 43.25 | 10.15 | 33.10 | 0.00 | 0.00 |
May | 60.88 | 13.54 | 33.27 | 1.64 | 31.63 | 0.00 | 0.00 |
June | 61.62 | 11.89 | 32.59 | 0.28 | 32.31 | 0.00 | 0.00 |
July | 64.16 | 8.63 | 34.08 | 0.56 | 33.52 | 0.00 | 0.00 |
August | 75.96 | 11.61 | 39.45 | 4.09 | 35.36 | 0.00 | 0.00 |
September | 87.54 | 16.12 | 48.37 | 12.88 | 35.50 | 0.00 | 0.00 |
October | 125.22 | 26.47 | 74.01 | 38.19 | 35.83 | 0.00 | 0.00 |
November | 141.37 | 52.69 | 96.05 | 66.41 | 29.65 | 0.00 | 0.00 |
December | 138.49 | 70.51 | 98.56 | 70.83 | 27.73 | 0.00 | 0.00 |
Annual Sum or Average | 96.37 | 38.20 | 62.39 | 30.08 | 32.31 | 0.00 | 0.00 |
Minimum of Months | 60.88 | 8.63 | 32.59 | 0.28 | 27.73 | 0.00 | 0.00 |
Maximum of Months | 141.37 | 78.98 | 100.83 | 71.95 | 35.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15.20 | 58.80 | 17.42 | 0.00 | 17.42 | 0.00 | 0.00 |
February | 20.82 | 48.15 | 20.56 | 0.00 | 20.56 | 0.00 | 0.00 |
March | 29.56 | 38.81 | 23.85 | 0.00 | 23.85 | 0.00 | 0.00 |
April | 46.62 | 19.41 | 28.25 | 0.19 | 28.06 | 0.00 | 0.00 |
May | 82.06 | 0.70 | 31.91 | 1.17 | 30.74 | 0.00 | 0.00 |
June | 95.05 | 0.49 | 36.28 | 2.54 | 33.74 | 0.00 | 0.00 |
July | 95.51 | 0.11 | 35.22 | 1.36 | 33.86 | 0.00 | 0.00 |
August | 86.01 | 0.56 | 31.61 | 0.32 | 31.30 | 0.00 | 0.00 |
September | 68.45 | 1.06 | 27.23 | 0.01 | 27.22 | 0.00 | 0.00 |
October | 55.61 | 8.81 | 23.65 | 0.00 | 23.65 | 0.00 | 0.00 |
November | 24.73 | 31.68 | 17.95 | 0.00 | 17.95 | 0.00 | 0.00 |
December | 16.88 | 47.78 | 16.20 | 0.00 | 16.20 | 0.00 | 0.00 |
Annual Sum or Average | 53.24 | 21.23 | 25.87 | 0.47 | 25.40 | 0.00 | 0.00 |
Minimum of Months | 15.20 | 0.11 | 16.20 | 0.00 | 16.20 | 0.00 | 0.00 |
Maximum of Months | 95.51 | 58.80 | 36.28 | 2.54 | 33.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 309.59 | 187.75 | 230.57 | 143.11 | 87.46 | 0.00 | 0.00 |
February | 321.95 | 153.88 | 230.17 | 129.52 | 100.66 | 0.00 | 0.00 |
March | 311.38 | 126.40 | 211.54 | 100.46 | 111.08 | 0.00 | 0.00 |
April | 344.80 | 65.50 | 204.70 | 80.77 | 123.93 | 0.00 | 0.00 |
May | 421.62 | 3.60 | 196.76 | 69.41 | 127.35 | 0.00 | 0.00 |
June | 438.57 | 2.25 | 197.83 | 62.59 | 135.24 | 0.00 | 0.00 |
July | 442.02 | 0.28 | 194.23 | 56.20 | 138.03 | 0.00 | 0.00 |
August | 426.78 | 2.08 | 189.13 | 53.22 | 135.91 | 0.00 | 0.00 |
September | 388.58 | 3.52 | 184.14 | 58.60 | 125.55 | 0.00 | 0.00 |
October | 413.33 | 30.37 | 214.92 | 99.42 | 115.50 | 0.00 | 0.00 |
November | 353.73 | 104.81 | 228.21 | 138.06 | 90.15 | 0.00 | 0.00 |
December | 298.26 | 157.11 | 208.52 | 127.25 | 81.27 | 0.00 | 0.00 |
Annual Sum or Average | 372.87 | 69.39 | 207.42 | 93.01 | 114.41 | 0.00 | 0.00 |
Minimum of Months | 298.26 | 0.28 | 184.14 | 53.22 | 81.27 | 0.00 | 0.00 |
Maximum of Months | 442.02 | 187.75 | 230.57 | 143.11 | 138.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 145.04 | 190.40 | 126.28 | 53.15 | 73.13 | 0.00 | 0.00 |
February | 175.82 | 156.75 | 142.41 | 56.35 | 86.06 | 0.00 | 0.00 |
March | 228.64 | 129.52 | 167.26 | 66.36 | 100.90 | 0.00 | 0.00 |
April | 300.28 | 70.53 | 185.94 | 68.31 | 117.63 | 0.00 | 0.00 |
May | 414.85 | 4.15 | 195.04 | 68.82 | 126.22 | 0.00 | 0.00 |
June | 446.46 | 2.51 | 202.42 | 65.41 | 137.01 | 0.00 | 0.00 |
July | 443.83 | 0.63 | 195.65 | 57.21 | 138.44 | 0.00 | 0.00 |
August | 404.72 | 2.88 | 179.32 | 48.50 | 130.82 | 0.00 | 0.00 |
September | 334.69 | 5.62 | 157.70 | 42.50 | 115.19 | 0.00 | 0.00 |
October | 299.46 | 32.20 | 151.94 | 51.68 | 100.26 | 0.00 | 0.00 |
November | 188.05 | 107.23 | 130.56 | 55.04 | 75.52 | 0.00 | 0.00 |
December | 132.11 | 159.09 | 105.54 | 38.69 | 66.85 | 0.00 | 0.00 |
Annual Sum or Average | 293.52 | 71.37 | 161.75 | 55.98 | 105.77 | 0.00 | 0.00 |
Minimum of Months | 132.11 | 0.63 | 105.54 | 38.69 | 66.85 | 0.00 | 0.00 |
Maximum of Months | 446.46 | 190.40 | 202.42 | 68.82 | 138.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 347.57 | 242.50 | 256.22 | 155.89 | 100.33 | 0.00 | 0.00 |
February | 340.59 | 201.75 | 241.15 | 126.80 | 114.35 | 0.00 | 0.00 |
March | 268.92 | 174.12 | 180.06 | 59.09 | 120.97 | 0.00 | 0.00 |
April | 271.30 | 96.56 | 154.92 | 22.41 | 132.51 | 0.00 | 0.00 |
May | 333.67 | 11.31 | 141.20 | 6.08 | 135.12 | 0.00 | 0.00 |
June | 359.67 | 8.62 | 149.23 | 6.13 | 143.10 | 0.00 | 0.00 |
July | 366.56 | 3.15 | 150.14 | 4.16 | 145.98 | 0.00 | 0.00 |
August | 371.68 | 8.19 | 153.97 | 9.55 | 144.42 | 0.00 | 0.00 |
September | 357.94 | 15.00 | 163.80 | 27.92 | 135.88 | 0.00 | 0.00 |
October | 411.70 | 52.67 | 211.60 | 82.74 | 128.86 | 0.00 | 0.00 |
November | 384.20 | 145.33 | 247.01 | 143.88 | 103.13 | 0.00 | 0.00 |
December | 359.30 | 207.03 | 248.64 | 153.47 | 95.17 | 0.00 | 0.00 |
Annual Sum or Average | 347.87 | 96.66 | 191.23 | 66.19 | 125.03 | 0.00 | 0.00 |
Minimum of Months | 268.92 | 3.15 | 141.20 | 4.16 | 95.17 | 0.00 | 0.00 |
Maximum of Months | 411.70 | 242.50 | 256.22 | 155.89 | 145.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 323.58 | 190.20 | 237.42 | 150.17 | 87.25 | 0.00 | 0.00 |
February | 339.36 | 156.77 | 239.82 | 137.24 | 102.59 | 0.00 | 0.00 |
March | 292.34 | 129.55 | 197.98 | 88.75 | 109.23 | 0.00 | 0.00 |
April | 350.23 | 67.13 | 208.11 | 83.47 | 124.63 | 0.00 | 0.00 |
May | 376.29 | 3.28 | 170.02 | 43.93 | 126.09 | 0.00 | 0.00 |
June | 411.04 | 2.17 | 183.27 | 50.36 | 132.91 | 0.00 | 0.00 |
July | 402.98 | 0.26 | 172.52 | 36.62 | 135.89 | 0.00 | 0.00 |
August | 411.45 | 1.94 | 180.60 | 45.03 | 135.57 | 0.00 | 0.00 |
September | 382.88 | 3.28 | 181.65 | 57.67 | 123.98 | 0.00 | 0.00 |
October | 416.51 | 30.80 | 216.86 | 101.61 | 115.26 | 0.00 | 0.00 |
November | 352.89 | 105.48 | 226.37 | 136.42 | 89.95 | 0.00 | 0.00 |
December | 326.34 | 157.09 | 225.11 | 142.58 | 82.53 | 0.00 | 0.00 |
Annual Sum or Average | 365.61 | 70.24 | 203.05 | 89.18 | 113.87 | 0.00 | 0.00 |
Minimum of Months | 292.34 | 0.26 | 170.02 | 36.62 | 82.53 | 0.00 | 0.00 |
Maximum of Months | 416.51 | 190.20 | 239.82 | 150.17 | 135.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 165.71 | 198.26 | 133.13 | 60.21 | 72.92 | 0.00 | 0.00 |
February | 198.45 | 165.02 | 152.06 | 64.07 | 87.99 | 0.00 | 0.00 |
March | 211.98 | 135.43 | 153.70 | 54.66 | 99.05 | 0.00 | 0.00 |
April | 305.65 | 73.88 | 189.35 | 71.02 | 118.33 | 0.00 | 0.00 |
May | 369.98 | 3.80 | 168.31 | 43.34 | 124.97 | 0.00 | 0.00 |
June | 419.20 | 2.43 | 187.87 | 53.19 | 134.68 | 0.00 | 0.00 |
July | 404.28 | 0.71 | 173.93 | 37.63 | 136.30 | 0.00 | 0.00 |
August | 389.67 | 2.86 | 170.79 | 40.31 | 130.48 | 0.00 | 0.00 |
September | 329.53 | 5.67 | 155.20 | 41.58 | 113.62 | 0.00 | 0.00 |
October | 305.02 | 33.51 | 153.89 | 53.86 | 100.02 | 0.00 | 0.00 |
November | 193.94 | 111.95 | 128.72 | 53.40 | 75.32 | 0.00 | 0.00 |
December | 164.45 | 162.31 | 122.13 | 54.02 | 68.11 | 0.00 | 0.00 |
Annual Sum or Average | 288.63 | 74.20 | 157.38 | 52.15 | 105.23 | 0.00 | 0.00 |
Minimum of Months | 164.45 | 0.71 | 122.13 | 37.63 | 68.11 | 0.00 | 0.00 |
Maximum of Months | 419.20 | 198.26 | 189.35 | 71.02 | 136.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 266.94 | 99.07 | 184.89 | 131.93 | 52.96 | 0.00 | 0.00 |
February | 247.33 | 81.05 | 166.39 | 107.31 | 59.08 | 0.00 | 0.00 |
March | 168.50 | 67.26 | 108.65 | 50.00 | 58.65 | 0.00 | 0.00 |
April | 142.33 | 33.90 | 79.30 | 18.62 | 60.68 | 0.00 | 0.00 |
May | 152.57 | 1.28 | 61.00 | 3.01 | 57.99 | 0.00 | 0.00 |
June | 155.34 | 0.88 | 59.77 | 0.52 | 59.24 | 0.00 | 0.00 |
July | 165.99 | 0.07 | 62.49 | 1.02 | 61.46 | 0.00 | 0.00 |
August | 183.04 | 0.81 | 72.34 | 7.50 | 64.84 | 0.00 | 0.00 |
September | 196.66 | 1.42 | 88.70 | 23.61 | 65.09 | 0.00 | 0.00 |
October | 260.59 | 15.47 | 135.71 | 70.02 | 65.69 | 0.00 | 0.00 |
November | 281.13 | 54.53 | 176.12 | 121.76 | 54.36 | 0.00 | 0.00 |
December | 272.71 | 82.73 | 180.72 | 129.88 | 50.84 | 0.00 | 0.00 |
Annual Sum or Average | 207.59 | 36.33 | 114.40 | 55.16 | 59.24 | 0.00 | 0.00 |
Minimum of Months | 142.33 | 0.07 | 59.77 | 0.52 | 50.84 | 0.00 | 0.00 |
Maximum of Months | 281.13 | 99.07 | 184.89 | 131.93 | 65.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 119.14 | 584.57 | 152.43 | 0.00 | 152.43 | 0.00 | 0.00 |
February | 168.12 | 482.88 | 179.84 | 0.00 | 179.84 | 0.00 | 0.00 |
March | 244.00 | 403.01 | 208.66 | 0.00 | 208.66 | 0.00 | 0.00 |
April | 391.44 | 220.21 | 247.19 | 1.67 | 245.52 | 0.00 | 0.00 |
May | 650.53 | 34.07 | 279.13 | 10.21 | 268.92 | 0.00 | 0.00 |
June | 756.15 | 27.12 | 317.42 | 22.25 | 295.17 | 0.00 | 0.00 |
July | 746.28 | 11.82 | 308.12 | 11.90 | 296.22 | 0.00 | 0.00 |
August | 673.13 | 24.10 | 276.58 | 2.76 | 273.82 | 0.00 | 0.00 |
September | 542.83 | 42.72 | 238.22 | 0.06 | 238.16 | 0.00 | 0.00 |
October | 441.10 | 120.24 | 206.89 | 0.00 | 206.89 | 0.00 | 0.00 |
November | 200.92 | 336.01 | 157.06 | 0.00 | 157.06 | 0.00 | 0.00 |
December | 134.44 | 486.76 | 141.70 | 0.00 | 141.70 | 0.00 | 0.00 |
Annual Sum or Average | 423.87 | 229.88 | 226.33 | 4.08 | 222.25 | 0.00 | 0.00 |
Minimum of Months | 119.14 | 11.82 | 141.70 | 0.00 | 141.70 | 0.00 | 0.00 |
Maximum of Months | 756.15 | 584.57 | 317.42 | 22.25 | 296.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 111.32 | 610.36 | 152.43 | 0.00 | 152.43 | 0.00 | 0.00 |
February | 159.03 | 505.43 | 179.84 | 0.00 | 179.84 | 0.00 | 0.00 |
March | 232.79 | 423.62 | 208.66 | 0.00 | 208.66 | 0.00 | 0.00 |
April | 378.25 | 233.80 | 247.19 | 1.67 | 245.52 | 0.00 | 0.00 |
May | 631.70 | 41.57 | 279.13 | 10.21 | 268.92 | 0.00 | 0.00 |
June | 736.67 | 33.36 | 317.42 | 22.25 | 295.17 | 0.00 | 0.00 |
July | 724.86 | 16.18 | 308.12 | 11.90 | 296.22 | 0.00 | 0.00 |
August | 653.26 | 30.28 | 276.58 | 2.76 | 273.82 | 0.00 | 0.00 |
September | 526.01 | 52.12 | 238.22 | 0.06 | 238.16 | 0.00 | 0.00 |
October | 425.71 | 131.15 | 206.89 | 0.00 | 206.89 | 0.00 | 0.00 |
November | 191.53 | 353.51 | 157.06 | 0.00 | 157.06 | 0.00 | 0.00 |
December | 126.72 | 510.06 | 141.70 | 0.00 | 141.70 | 0.00 | 0.00 |
Annual Sum or Average | 409.65 | 243.82 | 226.33 | 4.08 | 222.25 | 0.00 | 0.00 |
Minimum of Months | 111.32 | 16.18 | 141.70 | 0.00 | 141.70 | 0.00 | 0.00 |
Maximum of Months | 736.67 | 610.36 | 317.42 | 22.25 | 296.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 471.16 | 453.25 | 356.83 | 196.26 | 160.58 | 0.00 | 0.00 |
February | 526.35 | 376.04 | 372.56 | 185.86 | 186.71 | 0.00 | 0.00 |
March | 575.80 | 333.77 | 378.78 | 166.81 | 211.96 | 0.00 | 0.00 |
April | 707.65 | 191.64 | 390.62 | 149.07 | 241.55 | 0.00 | 0.00 |
May | 890.50 | 48.86 | 391.78 | 138.22 | 253.56 | 0.00 | 0.00 |
June | 948.95 | 42.34 | 400.23 | 127.98 | 272.24 | 0.00 | 0.00 |
July | 932.33 | 25.60 | 389.86 | 113.40 | 276.46 | 0.00 | 0.00 |
August | 877.42 | 37.31 | 368.43 | 101.72 | 266.71 | 0.00 | 0.00 |
September | 776.50 | 55.35 | 341.82 | 101.09 | 240.73 | 0.00 | 0.00 |
October | 760.69 | 115.32 | 366.85 | 151.10 | 215.75 | 0.00 | 0.00 |
November | 588.27 | 265.38 | 358.75 | 193.10 | 165.66 | 0.00 | 0.00 |
December | 453.75 | 389.22 | 314.05 | 165.93 | 148.12 | 0.00 | 0.00 |
Annual Sum or Average | 710.11 | 193.63 | 369.15 | 148.98 | 220.16 | 0.00 | 0.00 |
Minimum of Months | 453.75 | 25.60 | 314.05 | 101.09 | 148.12 | 0.00 | 0.00 |
Maximum of Months | 948.95 | 453.25 | 400.23 | 196.26 | 276.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 695.81 | 464.96 | 522.90 | 335.83 | 187.07 | 0.00 | 0.00 |
February | 662.44 | 397.55 | 485.20 | 273.15 | 212.05 | 0.00 | 0.00 |
March | 488.52 | 353.86 | 348.11 | 127.29 | 220.83 | 0.00 | 0.00 |
April | 457.33 | 215.75 | 286.61 | 47.97 | 238.64 | 0.00 | 0.00 |
May | 538.32 | 37.90 | 250.97 | 11.15 | 239.81 | 0.00 | 0.00 |
June | 578.56 | 29.88 | 260.95 | 8.96 | 251.99 | 0.00 | 0.00 |
July | 594.00 | 14.67 | 264.68 | 6.69 | 258.00 | 0.00 | 0.00 |
August | 620.01 | 27.48 | 278.95 | 20.04 | 258.91 | 0.00 | 0.00 |
September | 624.01 | 48.31 | 307.45 | 60.13 | 247.32 | 0.00 | 0.00 |
October | 762.46 | 117.16 | 416.38 | 178.23 | 238.15 | 0.00 | 0.00 |
November | 751.34 | 297.04 | 502.17 | 309.95 | 192.22 | 0.00 | 0.00 |
December | 716.12 | 406.49 | 508.60 | 330.61 | 177.99 | 0.00 | 0.00 |
Annual Sum or Average | 624.00 | 199.89 | 368.79 | 141.82 | 226.98 | 0.00 | 0.00 |
Minimum of Months | 457.33 | 14.67 | 250.97 | 6.69 | 177.99 | 0.00 | 0.00 |
Maximum of Months | 762.46 | 464.96 | 522.90 | 335.83 | 258.91 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.247685E+10 | 0.966896E+09 | 0.170776E+10 | 0.121857E+10 | 0.489185E+09 | 0.00 | 0.00 |
February | 0.206002E+10 | 0.741502E+09 | 0.138817E+10 | 0.895243E+09 | 0.492932E+09 | 0.00 | 0.00 |
March | 0.154337E+10 | 0.704547E+09 | 0.100361E+10 | 0.461874E+09 | 0.541741E+09 | 0.00 | 0.00 |
April | 0.121069E+10 | 0.424697E+09 | 0.708863E+09 | 0.166423E+09 | 0.542439E+09 | 0.00 | 0.00 |
May | 0.119079E+10 | 93963987.59 | 0.563440E+09 | 27768379.07 | 0.535672E+09 | 0.00 | 0.00 |
June | 0.115535E+10 | 74831091.81 | 0.534233E+09 | 4670372.97 | 0.529563E+09 | 0.00 | 0.00 |
July | 0.125494E+10 | 41861896.33 | 0.577157E+09 | 9455235.71 | 0.567702E+09 | 0.00 | 0.00 |
August | 0.144452E+10 | 74623174.53 | 0.668153E+09 | 69286625.40 | 0.598867E+09 | 0.00 | 0.00 |
September | 0.157857E+10 | 0.117370E+09 | 0.792854E+09 | 0.211066E+09 | 0.581788E+09 | 0.00 | 0.00 |
October | 0.227437E+10 | 0.263515E+09 | 0.125353E+10 | 0.646732E+09 | 0.606801E+09 | 0.00 | 0.00 |
November | 0.247229E+10 | 0.605852E+09 | 0.157434E+10 | 0.108840E+10 | 0.485937E+09 | 0.00 | 0.00 |
December | 0.251399E+10 | 0.844456E+09 | 0.166924E+10 | 0.119964E+10 | 0.469597E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.211757E+11 | 0.495412E+10 | 0.124414E+11 | 0.599913E+10 | 0.644222E+10 | 0.00 | 0.00 |
Minimum of Months | 0.115535E+10 | 41861896.33 | 0.534233E+09 | 4670372.97 | 0.469597E+09 | 0.00 | 0.00 |
Maximum of Months | 0.251399E+10 | 0.966896E+09 | 0.170776E+10 | 0.121857E+10 | 0.606801E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.704767E+10 | 0.267015E+10 | 0.480894E+10 | 0.343142E+10 | 0.137751E+10 | 0.00 | 0.00 |
February | 0.588664E+10 | 0.201496E+10 | 0.390901E+10 | 0.252095E+10 | 0.138806E+10 | 0.00 | 0.00 |
March | 0.446169E+10 | 0.190960E+10 | 0.282611E+10 | 0.130061E+10 | 0.152551E+10 | 0.00 | 0.00 |
April | 0.361063E+10 | 0.105627E+10 | 0.199611E+10 | 0.468637E+09 | 0.152747E+10 | 0.00 | 0.00 |
May | 0.370315E+10 | 0.162478E+09 | 0.158661E+10 | 78193924.59 | 0.150842E+10 | 0.00 | 0.00 |
June | 0.360408E+10 | 0.119630E+09 | 0.150437E+10 | 13151462.36 | 0.149121E+10 | 0.00 | 0.00 |
July | 0.391037E+10 | 51822189.64 | 0.162524E+10 | 26625320.33 | 0.159861E+10 | 0.00 | 0.00 |
August | 0.439295E+10 | 0.124795E+09 | 0.188148E+10 | 0.195107E+09 | 0.168637E+10 | 0.00 | 0.00 |
September | 0.469373E+10 | 0.218096E+09 | 0.223262E+10 | 0.594347E+09 | 0.163828E+10 | 0.00 | 0.00 |
October | 0.657323E+10 | 0.638440E+09 | 0.352987E+10 | 0.182116E+10 | 0.170871E+10 | 0.00 | 0.00 |
November | 0.705565E+10 | 0.159485E+10 | 0.443322E+10 | 0.306486E+10 | 0.136837E+10 | 0.00 | 0.00 |
December | 0.713824E+10 | 0.231197E+10 | 0.470046E+10 | 0.337811E+10 | 0.132235E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.620780E+11 | 0.128731E+11 | 0.350340E+11 | 0.168932E+11 | 0.181409E+11 | 0.00 | 0.00 |
Minimum of Months | 0.360408E+10 | 51822189.64 | 0.150437E+10 | 13151462.36 | 0.132235E+10 | 0.00 | 0.00 |
Maximum of Months | 0.713824E+10 | 0.267015E+10 | 0.480894E+10 | 0.343142E+10 | 0.170871E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.929557E+10 | 0.367232E+10 | 0.624708E+10 | 0.445762E+10 | 0.178947E+10 | 0.00 | 0.00 |
February | 0.775748E+10 | 0.279492E+10 | 0.507803E+10 | 0.327485E+10 | 0.180317E+10 | 0.00 | 0.00 |
March | 0.584639E+10 | 0.270262E+10 | 0.367128E+10 | 0.168956E+10 | 0.198172E+10 | 0.00 | 0.00 |
April | 0.467717E+10 | 0.155144E+10 | 0.259306E+10 | 0.608787E+09 | 0.198428E+10 | 0.00 | 0.00 |
May | 0.471782E+10 | 0.287886E+09 | 0.206110E+10 | 0.101578E+09 | 0.195952E+10 | 0.00 | 0.00 |
June | 0.458470E+10 | 0.225759E+09 | 0.195426E+10 | 17084498.06 | 0.193717E+10 | 0.00 | 0.00 |
July | 0.497247E+10 | 0.117505E+09 | 0.211127E+10 | 34587806.38 | 0.207669E+10 | 0.00 | 0.00 |
August | 0.565054E+10 | 0.224131E+09 | 0.244414E+10 | 0.253455E+09 | 0.219069E+10 | 0.00 | 0.00 |
September | 0.609550E+10 | 0.366977E+09 | 0.290031E+10 | 0.772091E+09 | 0.212821E+10 | 0.00 | 0.00 |
October | 0.864689E+10 | 0.910083E+09 | 0.458550E+10 | 0.236578E+10 | 0.221971E+10 | 0.00 | 0.00 |
November | 0.930608E+10 | 0.220923E+10 | 0.575901E+10 | 0.398143E+10 | 0.177758E+10 | 0.00 | 0.00 |
December | 0.941750E+10 | 0.319423E+10 | 0.610616E+10 | 0.438835E+10 | 0.171781E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.809681E+11 | 0.182571E+11 | 0.455112E+11 | 0.219452E+11 | 0.235660E+11 | 0.00 | 0.00 |
Minimum of Months | 0.458470E+10 | 0.117505E+09 | 0.195426E+10 | 17084498.06 | 0.171781E+10 | 0.00 | 0.00 |
Maximum of Months | 0.941750E+10 | 0.367232E+10 | 0.624708E+10 | 0.445762E+10 | 0.221971E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.873805E+09 | 0.514542E+09 | 0.635898E+09 | 0.402205E+09 | 0.233693E+09 | 0.00 | 0.00 |
February | 0.829078E+09 | 0.383327E+09 | 0.580179E+09 | 0.332005E+09 | 0.248174E+09 | 0.00 | 0.00 |
March | 0.791888E+09 | 0.352215E+09 | 0.530269E+09 | 0.237710E+09 | 0.292559E+09 | 0.00 | 0.00 |
April | 0.918830E+09 | 0.177418E+09 | 0.539409E+09 | 0.216365E+09 | 0.323044E+09 | 0.00 | 0.00 |
May | 0.101510E+10 | 9807074.15 | 0.455384E+09 | 0.117659E+09 | 0.337725E+09 | 0.00 | 0.00 |
June | 0.107327E+10 | 6334094.08 | 0.475039E+09 | 0.130540E+09 | 0.344499E+09 | 0.00 | 0.00 |
July | 0.108547E+10 | 791544.35 | 0.462065E+09 | 98094225.35 | 0.363971E+09 | 0.00 | 0.00 |
August | 0.110856E+10 | 5747088.71 | 0.483725E+09 | 0.120605E+09 | 0.363120E+09 | 0.00 | 0.00 |
September | 0.997902E+09 | 9318463.22 | 0.470827E+09 | 0.149475E+09 | 0.321352E+09 | 0.00 | 0.00 |
October | 0.112251E+10 | 85379320.86 | 0.580849E+09 | 0.272142E+09 | 0.308707E+09 | 0.00 | 0.00 |
November | 0.920942E+09 | 0.278825E+09 | 0.586745E+09 | 0.353595E+09 | 0.233150E+09 | 0.00 | 0.00 |
December | 0.880364E+09 | 0.426861E+09 | 0.602922E+09 | 0.381876E+09 | 0.221046E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116177E+11 | 0.225057E+10 | 0.640331E+10 | 0.281227E+10 | 0.359104E+10 | 0.00 | 0.00 |
Minimum of Months | 0.791888E+09 | 791544.35 | 0.455384E+09 | 98094225.35 | 0.221046E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112251E+10 | 0.514542E+09 | 0.635898E+09 | 0.402205E+09 | 0.363971E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.446020E+09 | 0.538189E+09 | 0.356572E+09 | 0.161272E+09 | 0.195300E+09 | 0.00 | 0.00 |
February | 0.484806E+09 | 0.403586E+09 | 0.367866E+09 | 0.155000E+09 | 0.212866E+09 | 0.00 | 0.00 |
March | 0.575037E+09 | 0.366211E+09 | 0.411678E+09 | 0.146391E+09 | 0.265287E+09 | 0.00 | 0.00 |
April | 0.803545E+09 | 0.192192E+09 | 0.490787E+09 | 0.184078E+09 | 0.306709E+09 | 0.00 | 0.00 |
May | 0.998117E+09 | 11172519.82 | 0.450788E+09 | 0.116075E+09 | 0.334713E+09 | 0.00 | 0.00 |
June | 0.109450E+10 | 7000755.66 | 0.486953E+09 | 0.137856E+09 | 0.349096E+09 | 0.00 | 0.00 |
July | 0.108976E+10 | 1797312.53 | 0.465851E+09 | 0.100778E+09 | 0.365073E+09 | 0.00 | 0.00 |
August | 0.104959E+10 | 7998440.63 | 0.457450E+09 | 0.107961E+09 | 0.349489E+09 | 0.00 | 0.00 |
September | 0.858753E+09 | 15177298.41 | 0.402279E+09 | 0.107768E+09 | 0.294511E+09 | 0.00 | 0.00 |
October | 0.820551E+09 | 93023193.91 | 0.412167E+09 | 0.144272E+09 | 0.267895E+09 | 0.00 | 0.00 |
November | 0.504859E+09 | 0.297624E+09 | 0.333630E+09 | 0.138400E+09 | 0.195231E+09 | 0.00 | 0.00 |
December | 0.442156E+09 | 0.442644E+09 | 0.327107E+09 | 0.144687E+09 | 0.182420E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.916770E+10 | 0.237661E+10 | 0.496313E+10 | 0.164454E+10 | 0.331859E+10 | 0.00 | 0.00 |
Minimum of Months | 0.442156E+09 | 1797312.53 | 0.327107E+09 | 0.100778E+09 | 0.182420E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109450E+10 | 0.538189E+09 | 0.490787E+09 | 0.184078E+09 | 0.365073E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.360664E+09 | 0.211550E+09 | 0.270070E+09 | 0.192708E+09 | 77361486.51 | 0.00 | 0.00 |
February | 0.298636E+09 | 0.164597E+09 | 0.219530E+09 | 0.141576E+09 | 77954074.42 | 0.00 | 0.00 |
March | 0.216002E+09 | 0.164240E+09 | 0.158715E+09 | 73041753.85 | 85672903.76 | 0.00 | 0.00 |
April | 0.165963E+09 | 0.104946E+09 | 0.112102E+09 | 26318579.58 | 85783597.12 | 0.00 | 0.00 |
May | 0.163052E+09 | 36265487.51 | 89104705.65 | 4391355.05 | 84713350.61 | 0.00 | 0.00 |
June | 0.159727E+09 | 30826014.44 | 84485891.04 | 738583.48 | 83747307.56 | 0.00 | 0.00 |
July | 0.171842E+09 | 23118474.86 | 91273890.15 | 1495272.62 | 89778617.52 | 0.00 | 0.00 |
August | 0.203441E+09 | 31091465.71 | 0.105664E+09 | 10957145.58 | 94707071.18 | 0.00 | 0.00 |
September | 0.226911E+09 | 41771217.69 | 0.125385E+09 | 33378428.44 | 92006075.66 | 0.00 | 0.00 |
October | 0.335382E+09 | 70897545.78 | 0.198237E+09 | 0.102276E+09 | 95961691.86 | 0.00 | 0.00 |
November | 0.366434E+09 | 0.136562E+09 | 0.248970E+09 | 0.172122E+09 | 76847746.33 | 0.00 | 0.00 |
December | 0.370919E+09 | 0.188853E+09 | 0.263977E+09 | 0.189714E+09 | 74263676.67 | 0.00 | 0.00 |
Annual Sum or Average | 0.303897E+10 | 0.120472E+10 | 0.196751E+10 | 0.948716E+09 | 0.101880E+10 | 0.00 | 0.00 |
Minimum of Months | 0.159727E+09 | 23118474.86 | 84485891.04 | 738583.48 | 74263676.67 | 0.00 | 0.00 |
Maximum of Months | 0.370919E+09 | 0.211550E+09 | 0.270070E+09 | 0.192708E+09 | 95961691.86 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 40701497.51 | 0.157485E+09 | 46668510.97 | 0.00 | 46668510.97 | 0.00 | 0.00 |
February | 50356229.37 | 0.116484E+09 | 49729427.42 | 0.00 | 49729427.42 | 0.00 | 0.00 |
March | 79179671.40 | 0.103950E+09 | 63881989.17 | 900.73 | 63881088.45 | 0.00 | 0.00 |
April | 0.120836E+09 | 50310610.69 | 73236952.39 | 494302.67 | 72742649.72 | 0.00 | 0.00 |
May | 0.219783E+09 | 1886224.79 | 85457088.95 | 3125835.78 | 82331253.17 | 0.00 | 0.00 |
June | 0.246372E+09 | 1278055.89 | 94046028.79 | 6592568.27 | 87453460.52 | 0.00 | 0.00 |
July | 0.255806E+09 | 286515.21 | 94332927.68 | 3643160.37 | 90689767.31 | 0.00 | 0.00 |
August | 0.230361E+09 | 1501451.08 | 84676640.22 | 844188.40 | 83832451.82 | 0.00 | 0.00 |
September | 0.177427E+09 | 2745029.90 | 70580147.31 | 19070.40 | 70561076.91 | 0.00 | 0.00 |
October | 0.148932E+09 | 23607083.28 | 63339600.62 | 0.00 | 63339600.62 | 0.00 | 0.00 |
November | 64108474.58 | 82125396.91 | 46533788.58 | 0.00 | 46533788.58 | 0.00 | 0.00 |
December | 45217029.59 | 0.127963E+09 | 43383685.37 | 0.00 | 43383685.37 | 0.00 | 0.00 |
Annual Sum or Average | 0.167908E+10 | 0.669623E+09 | 0.815867E+09 | 14720026.61 | 0.801147E+09 | 0.00 | 0.00 |
Minimum of Months | 40701497.51 | 286515.21 | 43383685.37 | 0.00 | 43383685.37 | 0.00 | 0.00 |
Maximum of Months | 0.255806E+09 | 0.157485E+09 | 94332927.68 | 6592568.27 | 90689767.31 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.829207E+09 | 0.502858E+09 | 0.617554E+09 | 0.383302E+09 | 0.234252E+09 | 0.00 | 0.00 |
February | 0.778861E+09 | 0.372261E+09 | 0.556831E+09 | 0.313324E+09 | 0.243507E+09 | 0.00 | 0.00 |
March | 0.834008E+09 | 0.338557E+09 | 0.566583E+09 | 0.269070E+09 | 0.297513E+09 | 0.00 | 0.00 |
April | 0.893726E+09 | 0.169781E+09 | 0.530579E+09 | 0.209350E+09 | 0.321229E+09 | 0.00 | 0.00 |
May | 0.112926E+10 | 9637056.63 | 0.527004E+09 | 0.185912E+09 | 0.341092E+09 | 0.00 | 0.00 |
June | 0.113677E+10 | 5822824.49 | 0.512765E+09 | 0.162221E+09 | 0.350544E+09 | 0.00 | 0.00 |
July | 0.118390E+10 | 761032.09 | 0.520234E+09 | 0.150538E+09 | 0.369696E+09 | 0.00 | 0.00 |
August | 0.114308E+10 | 5566426.73 | 0.506561E+09 | 0.142551E+09 | 0.364010E+09 | 0.00 | 0.00 |
September | 0.100720E+10 | 9123250.90 | 0.477297E+09 | 0.151879E+09 | 0.325417E+09 | 0.00 | 0.00 |
October | 0.110706E+10 | 81349973.75 | 0.575645E+09 | 0.266298E+09 | 0.309347E+09 | 0.00 | 0.00 |
November | 0.916863E+09 | 0.271665E+09 | 0.591521E+09 | 0.357863E+09 | 0.233658E+09 | 0.00 | 0.00 |
December | 0.798864E+09 | 0.420793E+09 | 0.558504E+09 | 0.340821E+09 | 0.217683E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.117588E+11 | 0.218817E+10 | 0.654108E+10 | 0.293313E+10 | 0.360795E+10 | 0.00 | 0.00 |
Minimum of Months | 0.778861E+09 | 761032.09 | 0.477297E+09 | 0.142551E+09 | 0.217683E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118390E+10 | 0.502858E+09 | 0.617554E+09 | 0.383302E+09 | 0.369696E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.388473E+09 | 0.509954E+09 | 0.338228E+09 | 0.142369E+09 | 0.195859E+09 | 0.00 | 0.00 |
February | 0.425350E+09 | 0.379205E+09 | 0.344517E+09 | 0.136319E+09 | 0.208199E+09 | 0.00 | 0.00 |
March | 0.612398E+09 | 0.346907E+09 | 0.447992E+09 | 0.177751E+09 | 0.270241E+09 | 0.00 | 0.00 |
April | 0.778315E+09 | 0.182822E+09 | 0.481957E+09 | 0.177063E+09 | 0.304894E+09 | 0.00 | 0.00 |
May | 0.111114E+10 | 11103917.08 | 0.522408E+09 | 0.184328E+09 | 0.338080E+09 | 0.00 | 0.00 |
June | 0.115722E+10 | 6502193.27 | 0.524679E+09 | 0.169537E+09 | 0.355142E+09 | 0.00 | 0.00 |
July | 0.118875E+10 | 1676263.01 | 0.524019E+09 | 0.153222E+09 | 0.370798E+09 | 0.00 | 0.00 |
August | 0.108399E+10 | 7712787.08 | 0.480286E+09 | 0.129907E+09 | 0.350379E+09 | 0.00 | 0.00 |
September | 0.867514E+09 | 14576345.69 | 0.408748E+09 | 0.110172E+09 | 0.298577E+09 | 0.00 | 0.00 |
October | 0.802065E+09 | 86250317.80 | 0.406963E+09 | 0.138428E+09 | 0.268535E+09 | 0.00 | 0.00 |
November | 0.487438E+09 | 0.277951E+09 | 0.338407E+09 | 0.142668E+09 | 0.195739E+09 | 0.00 | 0.00 |
December | 0.353841E+09 | 0.426114E+09 | 0.282689E+09 | 0.103631E+09 | 0.179058E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.925650E+10 | 0.225078E+10 | 0.510089E+10 | 0.176540E+10 | 0.333550E+10 | 0.00 | 0.00 |
Minimum of Months | 0.353841E+09 | 1676263.01 | 0.282689E+09 | 0.103631E+09 | 0.179058E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118875E+10 | 0.509954E+09 | 0.524679E+09 | 0.184328E+09 | 0.370798E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.930931E+09 | 0.649523E+09 | 0.686265E+09 | 0.417545E+09 | 0.268720E+09 | 0.00 | 0.00 |
February | 0.823944E+09 | 0.488065E+09 | 0.583391E+09 | 0.306755E+09 | 0.276635E+09 | 0.00 | 0.00 |
March | 0.720277E+09 | 0.466369E+09 | 0.482280E+09 | 0.158263E+09 | 0.324017E+09 | 0.00 | 0.00 |
April | 0.703205E+09 | 0.250273E+09 | 0.401550E+09 | 58095868.31 | 0.343454E+09 | 0.00 | 0.00 |
May | 0.893703E+09 | 30297147.09 | 0.378194E+09 | 16286453.65 | 0.361907E+09 | 0.00 | 0.00 |
June | 0.932275E+09 | 22353920.65 | 0.386793E+09 | 15882018.50 | 0.370911E+09 | 0.00 | 0.00 |
July | 0.981788E+09 | 8430225.52 | 0.402122E+09 | 11132146.95 | 0.390990E+09 | 0.00 | 0.00 |
August | 0.995499E+09 | 21932443.20 | 0.412383E+09 | 25569882.54 | 0.386813E+09 | 0.00 | 0.00 |
September | 0.927793E+09 | 38881344.39 | 0.424574E+09 | 72363085.09 | 0.352211E+09 | 0.00 | 0.00 |
October | 0.110269E+10 | 0.141078E+09 | 0.566740E+09 | 0.221603E+09 | 0.345137E+09 | 0.00 | 0.00 |
November | 0.995849E+09 | 0.376684E+09 | 0.640256E+09 | 0.372940E+09 | 0.267315E+09 | 0.00 | 0.00 |
December | 0.962344E+09 | 0.554499E+09 | 0.665949E+09 | 0.411057E+09 | 0.254892E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109703E+11 | 0.304839E+10 | 0.603050E+10 | 0.208749E+10 | 0.394300E+10 | 0.00 | 0.00 |
Minimum of Months | 0.703205E+09 | 8430225.52 | 0.378194E+09 | 11132146.95 | 0.254892E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110269E+10 | 0.649523E+09 | 0.686265E+09 | 0.417545E+09 | 0.390990E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.866673E+09 | 0.509430E+09 | 0.635898E+09 | 0.402205E+09 | 0.233693E+09 | 0.00 | 0.00 |
February | 0.820981E+09 | 0.379252E+09 | 0.580179E+09 | 0.332005E+09 | 0.248174E+09 | 0.00 | 0.00 |
March | 0.783004E+09 | 0.346994E+09 | 0.530269E+09 | 0.237710E+09 | 0.292559E+09 | 0.00 | 0.00 |
April | 0.907803E+09 | 0.174004E+09 | 0.539409E+09 | 0.216365E+09 | 0.323044E+09 | 0.00 | 0.00 |
May | 0.100787E+10 | 8791816.12 | 0.455384E+09 | 0.117659E+09 | 0.337725E+09 | 0.00 | 0.00 |
June | 0.106542E+10 | 5637316.11 | 0.475039E+09 | 0.130540E+09 | 0.344499E+09 | 0.00 | 0.00 |
July | 0.107934E+10 | 687646.91 | 0.462065E+09 | 98094225.35 | 0.363971E+09 | 0.00 | 0.00 |
August | 0.110203E+10 | 5192981.16 | 0.483725E+09 | 0.120605E+09 | 0.363120E+09 | 0.00 | 0.00 |
September | 0.992438E+09 | 8511936.93 | 0.470827E+09 | 0.149475E+09 | 0.321352E+09 | 0.00 | 0.00 |
October | 0.111558E+10 | 82484983.77 | 0.580849E+09 | 0.272142E+09 | 0.308707E+09 | 0.00 | 0.00 |
November | 0.914683E+09 | 0.273399E+09 | 0.586745E+09 | 0.353595E+09 | 0.233150E+09 | 0.00 | 0.00 |
December | 0.874067E+09 | 0.420744E+09 | 0.602922E+09 | 0.381876E+09 | 0.221046E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115299E+11 | 0.221513E+10 | 0.640331E+10 | 0.281227E+10 | 0.359104E+10 | 0.00 | 0.00 |
Minimum of Months | 0.783004E+09 | 687646.91 | 0.455384E+09 | 98094225.35 | 0.221046E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111558E+10 | 0.509430E+09 | 0.635898E+09 | 0.402205E+09 | 0.363971E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.443845E+09 | 0.531030E+09 | 0.356572E+09 | 0.161272E+09 | 0.195300E+09 | 0.00 | 0.00 |
February | 0.480101E+09 | 0.399206E+09 | 0.367866E+09 | 0.155000E+09 | 0.212866E+09 | 0.00 | 0.00 |
March | 0.567772E+09 | 0.362748E+09 | 0.411678E+09 | 0.146391E+09 | 0.265287E+09 | 0.00 | 0.00 |
April | 0.792234E+09 | 0.191500E+09 | 0.490787E+09 | 0.184078E+09 | 0.306709E+09 | 0.00 | 0.00 |
May | 0.990947E+09 | 10186054.27 | 0.450788E+09 | 0.116075E+09 | 0.334713E+09 | 0.00 | 0.00 |
June | 0.108657E+10 | 6288296.27 | 0.486953E+09 | 0.137856E+09 | 0.349096E+09 | 0.00 | 0.00 |
July | 0.108281E+10 | 1908581.16 | 0.465851E+09 | 0.100778E+09 | 0.365073E+09 | 0.00 | 0.00 |
August | 0.104369E+10 | 7670603.57 | 0.457450E+09 | 0.107961E+09 | 0.349489E+09 | 0.00 | 0.00 |
September | 0.854132E+09 | 14685441.36 | 0.402279E+09 | 0.107768E+09 | 0.294511E+09 | 0.00 | 0.00 |
October | 0.816978E+09 | 89764110.28 | 0.412167E+09 | 0.144272E+09 | 0.267895E+09 | 0.00 | 0.00 |
November | 0.502691E+09 | 0.290167E+09 | 0.333630E+09 | 0.138400E+09 | 0.195231E+09 | 0.00 | 0.00 |
December | 0.440458E+09 | 0.434722E+09 | 0.327107E+09 | 0.144687E+09 | 0.182420E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.910224E+10 | 0.233988E+10 | 0.496313E+10 | 0.164454E+10 | 0.331859E+10 | 0.00 | 0.00 |
Minimum of Months | 0.440458E+09 | 1908581.16 | 0.327107E+09 | 0.100778E+09 | 0.182420E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108657E+10 | 0.531030E+09 | 0.490787E+09 | 0.184078E+09 | 0.365073E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.714978E+09 | 0.265361E+09 | 0.495202E+09 | 0.353351E+09 | 0.141851E+09 | 0.00 | 0.00 |
February | 0.598330E+09 | 0.196064E+09 | 0.402532E+09 | 0.259595E+09 | 0.142937E+09 | 0.00 | 0.00 |
March | 0.451301E+09 | 0.180142E+09 | 0.291021E+09 | 0.133930E+09 | 0.157091E+09 | 0.00 | 0.00 |
April | 0.368924E+09 | 87870701.15 | 0.205552E+09 | 48257998.75 | 0.157294E+09 | 0.00 | 0.00 |
May | 0.408653E+09 | 3440611.62 | 0.163383E+09 | 8052030.53 | 0.155331E+09 | 0.00 | 0.00 |
June | 0.402641E+09 | 2278559.25 | 0.154914E+09 | 1354273.71 | 0.153560E+09 | 0.00 | 0.00 |
July | 0.444575E+09 | 199701.20 | 0.167361E+09 | 2741746.16 | 0.164619E+09 | 0.00 | 0.00 |
August | 0.490253E+09 | 2170241.15 | 0.193747E+09 | 20091126.73 | 0.173656E+09 | 0.00 | 0.00 |
September | 0.509755E+09 | 3676234.85 | 0.229906E+09 | 61203005.02 | 0.168703E+09 | 0.00 | 0.00 |
October | 0.697974E+09 | 41425962.76 | 0.363490E+09 | 0.187534E+09 | 0.175956E+09 | 0.00 | 0.00 |
November | 0.728688E+09 | 0.141348E+09 | 0.456513E+09 | 0.315604E+09 | 0.140909E+09 | 0.00 | 0.00 |
December | 0.730432E+09 | 0.221588E+09 | 0.484031E+09 | 0.347861E+09 | 0.136171E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.654650E+10 | 0.114557E+10 | 0.360765E+10 | 0.173958E+10 | 0.186808E+10 | 0.00 | 0.00 |
Minimum of Months | 0.368924E+09 | 199701.20 | 0.154914E+09 | 1354273.71 | 0.136171E+09 | 0.00 | 0.00 |
Maximum of Months | 0.730432E+09 | 0.265361E+09 | 0.495202E+09 | 0.353351E+09 | 0.175956E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.319095E+09 | 0.156572E+10 | 0.408280E+09 | 0.00 | 0.408280E+09 | 0.00 | 0.00 |
February | 0.406708E+09 | 0.116819E+10 | 0.435058E+09 | 0.00 | 0.435058E+09 | 0.00 | 0.00 |
March | 0.653519E+09 | 0.107943E+10 | 0.558872E+09 | 7880.00 | 0.558864E+09 | 0.00 | 0.00 |
April | 0.101462E+10 | 0.570789E+09 | 0.640714E+09 | 4324411.30 | 0.636390E+09 | 0.00 | 0.00 |
May | 0.174237E+10 | 91259660.90 | 0.747622E+09 | 27346402.29 | 0.720276E+09 | 0.00 | 0.00 |
June | 0.195993E+10 | 70285795.04 | 0.822763E+09 | 57675142.49 | 0.765087E+09 | 0.00 | 0.00 |
July | 0.199884E+10 | 31668497.43 | 0.825272E+09 | 31872221.09 | 0.793400E+09 | 0.00 | 0.00 |
August | 0.180292E+10 | 64543369.23 | 0.740794E+09 | 7385389.76 | 0.733409E+09 | 0.00 | 0.00 |
September | 0.140700E+10 | 0.110738E+09 | 0.617471E+09 | 166837.56 | 0.617304E+09 | 0.00 | 0.00 |
October | 0.118143E+10 | 0.322048E+09 | 0.554127E+09 | 0.00 | 0.554127E+09 | 0.00 | 0.00 |
November | 0.520779E+09 | 0.870946E+09 | 0.407101E+09 | 0.00 | 0.407101E+09 | 0.00 | 0.00 |
December | 0.360076E+09 | 0.130373E+10 | 0.379543E+09 | 0.00 | 0.379543E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.133673E+11 | 0.724934E+10 | 0.713762E+10 | 0.128778E+09 | 0.700884E+10 | 0.00 | 0.00 |
Minimum of Months | 0.319095E+09 | 31668497.43 | 0.379543E+09 | 0.00 | 0.379543E+09 | 0.00 | 0.00 |
Maximum of Months | 0.199884E+10 | 0.156572E+10 | 0.825272E+09 | 57675142.49 | 0.793400E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.298159E+09 | 0.163478E+10 | 0.408280E+09 | 0.00 | 0.408280E+09 | 0.00 | 0.00 |
February | 0.384737E+09 | 0.122274E+10 | 0.435058E+09 | 0.00 | 0.435058E+09 | 0.00 | 0.00 |
March | 0.623500E+09 | 0.113463E+10 | 0.558872E+09 | 7880.00 | 0.558864E+09 | 0.00 | 0.00 |
April | 0.980436E+09 | 0.606005E+09 | 0.640714E+09 | 4324411.30 | 0.636390E+09 | 0.00 | 0.00 |
May | 0.169194E+10 | 0.111350E+09 | 0.747622E+09 | 27346402.29 | 0.720276E+09 | 0.00 | 0.00 |
June | 0.190946E+10 | 86473498.07 | 0.822763E+09 | 57675142.49 | 0.765087E+09 | 0.00 | 0.00 |
July | 0.194148E+10 | 43343037.65 | 0.825272E+09 | 31872221.09 | 0.793400E+09 | 0.00 | 0.00 |
August | 0.174969E+10 | 81093861.29 | 0.740794E+09 | 7385389.76 | 0.733409E+09 | 0.00 | 0.00 |
September | 0.136342E+10 | 0.135101E+09 | 0.617471E+09 | 166837.56 | 0.617304E+09 | 0.00 | 0.00 |
October | 0.114021E+10 | 0.351274E+09 | 0.554127E+09 | 0.00 | 0.554127E+09 | 0.00 | 0.00 |
November | 0.496451E+09 | 0.916301E+09 | 0.407101E+09 | 0.00 | 0.407101E+09 | 0.00 | 0.00 |
December | 0.339400E+09 | 0.136615E+10 | 0.379543E+09 | 0.00 | 0.379543E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129189E+11 | 0.768923E+10 | 0.713762E+10 | 0.128778E+09 | 0.700884E+10 | 0.00 | 0.00 |
Minimum of Months | 0.298159E+09 | 43343037.65 | 0.379543E+09 | 0.00 | 0.379543E+09 | 0.00 | 0.00 |
Maximum of Months | 0.194148E+10 | 0.163478E+10 | 0.825272E+09 | 57675142.49 | 0.793400E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126195E+10 | 0.121399E+10 | 0.955742E+09 | 0.525650E+09 | 0.430092E+09 | 0.00 | 0.00 |
February | 0.127333E+10 | 0.909712E+09 | 0.901308E+09 | 0.449623E+09 | 0.451685E+09 | 0.00 | 0.00 |
March | 0.154221E+10 | 0.893957E+09 | 0.101452E+10 | 0.446796E+09 | 0.567726E+09 | 0.00 | 0.00 |
April | 0.183423E+10 | 0.496736E+09 | 0.101248E+10 | 0.386388E+09 | 0.626093E+09 | 0.00 | 0.00 |
May | 0.238513E+10 | 0.130854E+09 | 0.104935E+10 | 0.370214E+09 | 0.679139E+09 | 0.00 | 0.00 |
June | 0.245968E+10 | 0.109753E+09 | 0.103739E+10 | 0.331736E+09 | 0.705651E+09 | 0.00 | 0.00 |
July | 0.249714E+10 | 68564357.11 | 0.104420E+10 | 0.303738E+09 | 0.740458E+09 | 0.00 | 0.00 |
August | 0.235007E+10 | 99920707.86 | 0.986794E+09 | 0.272440E+09 | 0.714354E+09 | 0.00 | 0.00 |
September | 0.201269E+10 | 0.143457E+09 | 0.886000E+09 | 0.262036E+09 | 0.623964E+09 | 0.00 | 0.00 |
October | 0.203742E+10 | 0.308874E+09 | 0.982561E+09 | 0.404707E+09 | 0.577854E+09 | 0.00 | 0.00 |
November | 0.152480E+10 | 0.687868E+09 | 0.929888E+09 | 0.500510E+09 | 0.429378E+09 | 0.00 | 0.00 |
December | 0.121532E+10 | 0.104248E+10 | 0.841161E+09 | 0.444438E+09 | 0.396723E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.223940E+11 | 0.610617E+10 | 0.116414E+11 | 0.469828E+10 | 0.694312E+10 | 0.00 | 0.00 |
Minimum of Months | 0.121532E+10 | 68564357.11 | 0.841161E+09 | 0.262036E+09 | 0.396723E+09 | 0.00 | 0.00 |
Maximum of Months | 0.249714E+10 | 0.121399E+10 | 0.104935E+10 | 0.525650E+09 | 0.740458E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.186366E+10 | 0.124534E+10 | 0.140052E+10 | 0.899475E+09 | 0.501048E+09 | 0.00 | 0.00 |
February | 0.160256E+10 | 0.961755E+09 | 0.117381E+10 | 0.660812E+09 | 0.512993E+09 | 0.00 | 0.00 |
March | 0.130846E+10 | 0.947775E+09 | 0.932391E+09 | 0.340929E+09 | 0.591462E+09 | 0.00 | 0.00 |
April | 0.118540E+10 | 0.559212E+09 | 0.742881E+09 | 0.124326E+09 | 0.618555E+09 | 0.00 | 0.00 |
May | 0.144184E+10 | 0.101520E+09 | 0.672187E+09 | 29871271.80 | 0.642316E+09 | 0.00 | 0.00 |
June | 0.149963E+10 | 77459956.44 | 0.676387E+09 | 23218527.27 | 0.653168E+09 | 0.00 | 0.00 |
July | 0.159098E+10 | 39293735.62 | 0.708931E+09 | 17905120.23 | 0.691025E+09 | 0.00 | 0.00 |
August | 0.166064E+10 | 73605469.35 | 0.747139E+09 | 53674756.89 | 0.693464E+09 | 0.00 | 0.00 |
September | 0.161743E+10 | 0.125231E+09 | 0.796909E+09 | 0.155853E+09 | 0.641056E+09 | 0.00 | 0.00 |
October | 0.204218E+10 | 0.313810E+09 | 0.111524E+10 | 0.477377E+09 | 0.637862E+09 | 0.00 | 0.00 |
November | 0.194747E+10 | 0.769934E+09 | 0.130163E+10 | 0.803387E+09 | 0.498246E+09 | 0.00 | 0.00 |
December | 0.191807E+10 | 0.108875E+10 | 0.136224E+10 | 0.885498E+09 | 0.476737E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.196783E+11 | 0.630369E+10 | 0.116303E+11 | 0.447233E+10 | 0.715793E+10 | 0.00 | 0.00 |
Minimum of Months | 0.118540E+10 | 39293735.62 | 0.672187E+09 | 17905120.23 | 0.476737E+09 | 0.00 | 0.00 |
Maximum of Months | 0.204218E+10 | 0.124534E+10 | 0.140052E+10 | 0.899475E+09 | 0.693464E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.106263E+12 | -0.104502E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176058E+10 | 82.17 | 0.00 | 0.00 |
February | 0.955044E+11 | -0.938975E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.160692E+10 | 82.17 | 0.00 | 0.00 |
March | 0.103299E+12 | -0.101504E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179547E+10 | 82.17 | 0.00 | 0.00 |
April | 0.962657E+11 | -0.945168E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174888E+10 | 82.17 | 0.00 | 0.00 |
May | 0.953161E+11 | -0.935152E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180095E+10 | 82.17 | 0.00 | 0.00 |
June | 0.889900E+11 | -0.872541E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173588E+10 | 82.17 | 0.00 | 0.00 |
July | 0.903001E+11 | -0.885242E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177586E+10 | 82.17 | 0.00 | 0.00 |
August | 0.908127E+11 | -0.890545E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175821E+10 | 82.17 | 0.00 | 0.00 |
September | 0.903403E+11 | -0.886402E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170007E+10 | 82.17 | 0.00 | 0.00 |
October | 0.972185E+11 | -0.954621E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175634E+10 | 82.17 | 0.00 | 0.00 |
November | 0.980936E+11 | -0.963942E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169946E+10 | 82.17 | 0.00 | 0.00 |
December | 0.104669E+12 | -0.102912E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175689E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.115707E+13 | -0.113618E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208955E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.889900E+11 | -0.104502E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.180095E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.106263E+12 | -0.872541E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.160692E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804707E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164107603.6 | 82.17 | 0.00 | 0.00 |
February | 0.727159E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148226266.5 | 82.17 | 0.00 | 0.00 |
March | 0.804566E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164105714.6 | 82.17 | 0.00 | 0.00 |
April | 0.779701E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158811766.5 | 82.17 | 0.00 | 0.00 |
May | 0.804707E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164107292.2 | 82.17 | 0.00 | 0.00 |
June | 0.778858E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158813616.8 | 82.17 | 0.00 | 0.00 |
July | 0.805551E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164107308.3 | 82.17 | 0.00 | 0.00 |
August | 0.804707E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164106645.4 | 82.17 | 0.00 | 0.00 |
September | 0.779842E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158812700.9 | 82.17 | 0.00 | 0.00 |
October | 0.804566E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164106697.9 | 82.17 | 0.00 | 0.00 |
November | 0.778013E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158812973.3 | 82.17 | 0.00 | 0.00 |
December | 0.805551E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164107356.0 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947793E+11 | -0.928471E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193223E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727159E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164107603.6 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805551E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148226266.5 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.592910E+11 | -0.577747E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151630E+10 | 60.05 | 0.00 | 0.00 |
February | 0.531623E+11 | -0.517696E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.139273E+10 | 60.05 | 0.00 | 0.00 |
March | 0.567997E+11 | -0.552351E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156465E+10 | 60.05 | 0.00 | 0.00 |
April | 0.517473E+11 | -0.502174E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152989E+10 | 60.05 | 0.00 | 0.00 |
May | 0.498851E+11 | -0.483129E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157226E+10 | 60.05 | 0.00 | 0.00 |
June | 0.454806E+11 | -0.439687E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.151187E+10 | 60.05 | 0.00 | 0.00 |
July | 0.455142E+11 | -0.439767E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153747E+10 | 60.05 | 0.00 | 0.00 |
August | 0.459931E+11 | -0.444801E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151300E+10 | 60.05 | 0.00 | 0.00 |
September | 0.466081E+11 | -0.451458E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146223E+10 | 60.05 | 0.00 | 0.00 |
October | 0.514768E+11 | -0.499664E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151041E+10 | 60.05 | 0.00 | 0.00 |
November | 0.532792E+11 | -0.518178E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146138E+10 | 60.05 | 0.00 | 0.00 |
December | 0.579088E+11 | -0.563976E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151118E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.617146E+12 | -0.599063E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.180834E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.454806E+11 | -0.577747E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.157226E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.592910E+11 | -0.439687E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.139273E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.87 | 0.86 | 01-JAN-07:49 | 6978.53 | 37.08 | 301.50 | 298.83 | 706.43 | 25.75 | 207.33 | 276.17 |
February | 295.50 | 0.87 | 0.86 | 01-FEB-11:39 | 2643.22 | 27.63 | 152.33 | 281.83 | 545.27 | 22.29 | 179.33 | 251.67 |
March | 296.00 | 0.87 | 0.86 | 02-MAR-12:39 | 1074.70 | 19.96 | 6.00 | 324.00 | 429.03 | 21.50 | 175.33 | 261.00 |
April | 347.33 | 0.87 | 0.86 | 01-APR-07:00 | 849.82 | 18.95 | 0.00 | 326.33 | 347.27 | 20.68 | 160.67 | 253.83 |
May | 353.67 | 0.87 | 0.86 | 01-MAY-07:40 | 782.23 | 18.94 | 0.00 | 353.33 | 317.11 | 20.68 | 149.67 | 258.17 |
June | 394.00 | 0.87 | 0.86 | 01-JUN-07:10 | 735.30 | 18.55 | 0.00 | 353.50 | 299.65 | 20.31 | 154.83 | 254.83 |
July | 390.00 | 0.87 | 0.86 | 01-JUL-07:10 | 823.12 | 18.79 | 0.00 | 363.83 | 326.44 | 20.53 | 162.67 | 273.17 |
August | 380.83 | 0.87 | 0.86 | 01-AUG-07:30 | 967.66 | 18.98 | 0.00 | 349.17 | 375.41 | 20.69 | 197.67 | 282.33 |
September | 342.17 | 0.87 | 0.86 | 01-SEP-07:30 | 1151.98 | 19.15 | 1.83 | 320.00 | 440.39 | 20.88 | 192.17 | 265.50 |
October | 330.00 | 0.87 | 0.86 | 01-OCT-07:19 | 1650.15 | 22.45 | 60.67 | 315.67 | 560.98 | 22.03 | 239.00 | 276.67 |
November | 308.00 | 0.87 | 0.86 | 01-NOV-08:39 | 5905.60 | 34.53 | 265.83 | 290.83 | 649.06 | 24.48 | 202.17 | 268.17 |
December | 282.83 | 0.87 | 0.86 | 01-DEC-07:49 | 7094.30 | 37.72 | 279.50 | 285.50 | 851.46 | 26.46 | 195.17 | 262.33 |
Annual Sum or Average | 4027.67 | 0.87 | 2373.37 | 23.80 | 1067.67 | 3862.83 | 472.45 | 22.02 | 2216.00 | 3183.83 | ||
Minimum of Months | 282.83 | 0.87 | 0.86 | 735.30 | 18.55 | 0.00 | 281.83 | 299.65 | 20.31 | 149.67 | 251.67 | |
Maximum of Months | 394.00 | 0.87 | 0.86 | 7094.30 | 37.72 | 301.50 | 363.83 | 851.46 | 26.46 | 239.00 | 282.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.25 | 0.22 | 01-JAN-07:49 | 7348.68 | 37.14 | 301.50 | 302.67 | 1074.11 | 25.51 | 193.33 | 292.17 |
February | 295.50 | 0.25 | 0.22 | 01-FEB-11:39 | 2969.02 | 27.58 | 154.67 | 288.17 | 870.42 | 22.32 | 164.17 | 270.50 |
March | 296.00 | 0.25 | 0.22 | 02-MAR-12:39 | 1308.62 | 20.41 | 31.83 | 334.17 | 663.21 | 21.77 | 186.33 | 302.67 |
April | 347.33 | 0.27 | 0.22 | 01-APR-07:30 | 1010.21 | 19.69 | 21.33 | 339.50 | 507.19 | 21.20 | 212.83 | 305.50 |
May | 353.67 | 0.26 | 0.22 | 01-MAY-06:00 | 910.90 | 19.81 | 9.50 | 372.83 | 445.32 | 21.32 | 216.17 | 326.17 |
June | 394.00 | 0.26 | 0.22 | 01-JUN-06:40 | 856.29 | 19.47 | 2.67 | 370.00 | 420.21 | 21.00 | 229.67 | 326.67 |
July | 390.00 | 0.25 | 0.22 | 01-JUL-06:40 | 951.72 | 19.70 | 13.83 | 379.67 | 454.55 | 21.20 | 226.00 | 336.17 |
August | 380.83 | 0.26 | 0.22 | 01-AUG-06:00 | 1116.59 | 19.80 | 25.83 | 360.33 | 523.76 | 21.29 | 250.17 | 327.50 |
September | 342.17 | 0.26 | 0.22 | 01-SEP-07:10 | 1335.57 | 19.86 | 44.00 | 331.00 | 623.24 | 21.39 | 224.83 | 301.50 |
October | 330.00 | 0.25 | 0.22 | 01-OCT-06:00 | 1927.73 | 22.71 | 96.00 | 324.17 | 837.74 | 22.25 | 241.67 | 300.00 |
November | 308.00 | 0.25 | 0.22 | 01-NOV-07:00 | 6253.89 | 34.57 | 266.00 | 296.00 | 995.59 | 24.35 | 185.33 | 283.50 |
December | 282.83 | 0.25 | 0.22 | 01-DEC-07:40 | 7488.10 | 37.78 | 279.50 | 290.83 | 1241.61 | 26.19 | 173.17 | 276.83 |
Annual Sum or Average | 4027.67 | 0.26 | 2598.83 | 24.32 | 1246.67 | 3989.33 | 696.95 | 22.34 | 2503.67 | 3649.17 | ||
Minimum of Months | 282.83 | 0.25 | 0.22 | 856.29 | 19.47 | 2.67 | 288.17 | 420.21 | 21.00 | 164.17 | 270.50 | |
Maximum of Months | 394.00 | 0.27 | 0.22 | 7488.10 | 37.78 | 301.50 | 379.67 | 1241.61 | 26.19 | 250.17 | 336.17 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.67 | 0.60 | 01-JAN-09:09 | 323.97 | 14.40 | 0.00 | 264.50 | 166.61 | 17.87 | 0.00 | 83.00 |
February | 295.50 | 0.65 | 0.60 | 01-FEB-11:50 | 370.83 | 15.41 | 0.00 | 260.00 | 190.57 | 18.83 | 0.00 | 125.33 |
March | 296.00 | 0.63 | 0.60 | 02-MAR-12:39 | 444.71 | 16.35 | 0.00 | 320.00 | 217.76 | 19.60 | 0.17 | 193.67 |
April | 347.33 | 0.63 | 0.60 | 01-APR-07:49 | 547.51 | 16.77 | 0.00 | 338.00 | 257.83 | 19.97 | 28.83 | 275.17 |
May | 353.67 | 0.61 | 0.60 | 01-MAY-06:00 | 704.93 | 17.53 | 0.00 | 379.83 | 315.88 | 21.51 | 106.17 | 327.83 |
June | 394.00 | 0.61 | 0.60 | 01-JUN-06:19 | 824.85 | 17.48 | 0.00 | 380.17 | 347.62 | 23.01 | 173.00 | 348.83 |
July | 390.00 | 0.61 | 0.60 | 01-JUL-06:19 | 829.16 | 18.34 | 19.17 | 387.83 | 348.17 | 21.96 | 154.00 | 343.83 |
August | 380.83 | 0.62 | 0.60 | 01-AUG-06:00 | 713.81 | 17.23 | 0.00 | 361.33 | 311.47 | 20.59 | 74.17 | 321.83 |
September | 342.17 | 0.63 | 0.60 | 01-SEP-07:10 | 584.98 | 16.57 | 0.00 | 324.33 | 260.81 | 19.72 | 10.83 | 259.17 |
October | 330.00 | 0.63 | 0.60 | 01-OCT-07:30 | 479.54 | 16.31 | 0.00 | 307.50 | 230.26 | 19.57 | 0.00 | 224.00 |
November | 308.00 | 0.66 | 0.60 | 01-NOV-09:00 | 328.15 | 14.71 | 0.00 | 255.50 | 170.27 | 18.18 | 0.00 | 86.00 |
December | 282.83 | 0.66 | 0.60 | 01-DEC-09:09 | 322.31 | 14.46 | 0.00 | 252.83 | 168.03 | 17.97 | 0.00 | 61.17 |
Annual Sum or Average | 4027.67 | 0.63 | 558.91 | 16.42 | 19.17 | 3831.83 | 255.68 | 20.05 | 547.17 | 2649.83 | ||
Minimum of Months | 282.83 | 0.61 | 0.60 | 322.31 | 14.40 | 0.00 | 252.83 | 166.61 | 17.87 | 0.00 | 61.17 | |
Maximum of Months | 394.00 | 0.67 | 0.60 | 829.16 | 18.34 | 19.17 | 387.83 | 348.17 | 23.01 | 173.00 | 348.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.67 | 0.60 | 01-JAN-09:09 | 323.97 | 14.40 | 0.00 | 264.50 | 166.61 | 17.87 | 0.00 | 83.00 |
February | 295.50 | 0.65 | 0.60 | 01-FEB-11:50 | 370.83 | 15.41 | 0.00 | 260.00 | 190.57 | 18.83 | 0.00 | 125.33 |
March | 296.00 | 0.63 | 0.60 | 02-MAR-12:39 | 444.71 | 16.35 | 0.00 | 320.00 | 217.76 | 19.60 | 0.17 | 193.67 |
April | 347.33 | 0.63 | 0.60 | 01-APR-07:49 | 547.51 | 16.77 | 0.00 | 338.00 | 257.83 | 19.97 | 28.83 | 275.17 |
May | 353.67 | 0.61 | 0.60 | 01-MAY-06:00 | 704.93 | 17.53 | 0.00 | 379.83 | 315.88 | 21.51 | 106.17 | 327.83 |
June | 394.00 | 0.61 | 0.60 | 01-JUN-06:19 | 824.85 | 17.48 | 0.00 | 380.17 | 347.62 | 23.01 | 173.00 | 348.83 |
July | 390.00 | 0.61 | 0.60 | 01-JUL-06:19 | 829.16 | 18.34 | 19.17 | 387.83 | 348.17 | 21.96 | 154.00 | 343.83 |
August | 380.83 | 0.62 | 0.60 | 01-AUG-06:00 | 713.81 | 17.23 | 0.00 | 361.33 | 311.47 | 20.59 | 74.17 | 321.83 |
September | 342.17 | 0.63 | 0.60 | 01-SEP-07:10 | 584.98 | 16.57 | 0.00 | 324.33 | 260.81 | 19.72 | 10.83 | 259.17 |
October | 330.00 | 0.63 | 0.60 | 01-OCT-07:30 | 479.54 | 16.31 | 0.00 | 307.50 | 230.26 | 19.57 | 0.00 | 224.00 |
November | 308.00 | 0.66 | 0.60 | 01-NOV-09:00 | 328.15 | 14.71 | 0.00 | 255.50 | 170.27 | 18.18 | 0.00 | 86.00 |
December | 282.83 | 0.66 | 0.60 | 01-DEC-09:09 | 322.31 | 14.46 | 0.00 | 252.83 | 168.03 | 17.97 | 0.00 | 61.17 |
Annual Sum or Average | 4027.67 | 0.63 | 558.91 | 16.42 | 19.17 | 3831.83 | 255.68 | 20.05 | 547.17 | 2649.83 | ||
Minimum of Months | 282.83 | 0.61 | 0.60 | 322.31 | 14.40 | 0.00 | 252.83 | 166.61 | 17.87 | 0.00 | 61.17 | |
Maximum of Months | 394.00 | 0.67 | 0.60 | 829.16 | 18.34 | 19.17 | 387.83 | 348.17 | 23.01 | 173.00 | 348.83 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14936343.15 | 1276.70 | 05-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14936343.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14936343.15 | 1276.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225810E+11 | 89097.30 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125704E+11 | 89123.50 | 04-FEB-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.772808E+10 | 87336.10 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223876E+09 | 31943.96 | 18-APR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6335910.40 | 8407.67 | 29-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.931122E+09 | 22072.04 | 12-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126165E+11 | 88938.78 | 21-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.566574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225810E+11 | 89123.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 50154650.64 | 805.93 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 59718013.35 | 1146.95 | 05-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110193E+09 | 868.29 | 11-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 73549684.80 | 996.10 | 20-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110193E+09 | 1146.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 180108.33 | 203.40 | 06-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5357845.86 | 308.75 | 12-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 655133.93 | 215.05 | 21-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6193088.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5357845.86 | 308.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159291E+09 | 468.07 | 10-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124046E+09 | 531.99 | 06-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107182E+09 | 499.97 | 12-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 49088.44 | 81.81 | 16-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 96328149.94 | 519.98 | 21-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.486896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159291E+09 | 531.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.206443E+09 | 3728.51 | 13-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161489E+09 | 2673.96 | 17-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.638352E+09 | 4397.02 | 11-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139619E+09 | 2263.33 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10891725.62 | 1729.75 | 22-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13197546.19 | 1774.30 | 07-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8069812.99 | 1877.45 | 13-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2099725.56 | 813.78 | 17-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 788456.04 | 649.35 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4869875.79 | 1645.08 | 17-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4155507.78 | 1607.57 | 20-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.308050E+09 | 3961.85 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 788456.04 | 649.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.638352E+09 | 4397.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12504528.27 | 1437.93 | 11-MAR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12504528.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12504528.27 | 1437.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 39197737.63 | 2272.72 | 10-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 40778260.05 | 2487.08 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157660E+09 | 2451.35 | 11-MAR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 63114898.45 | 2042.01 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157660E+09 | 2487.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2852957.29 | 595.41 | 10-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11013919.87 | 774.03 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5538795.93 | 488.48 | 12-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13979654.44 | 1098.62 | 21-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33385327.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13979654.44 | 1098.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104269E+09 | 3404.54 | 10-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 69058947.59 | 3599.77 | 06-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45411196.77 | 3565.78 | 13-MAR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7492343.20 | 2251.48 | 11-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1108622.94 | 709.37 | 18-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13324463.84 | 2610.30 | 16-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 90707387.39 | 3177.31 | 21-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104269E+09 | 3599.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 14171745.13 | 1856.09 | 05-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7181538.19 | 2258.16 | 06-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4945448.40 | 2262.16 | 13-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 306795.94 | 314.14 | 16-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7104092.32 | 1854.80 | 21-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33709619.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14171745.13 | 2262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.511453E+09 | 3621.78 | 05-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358717E+09 | 3621.78 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320995E+09 | 3621.78 | 03-MAR-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6139175.59 | 3621.78 | 11-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4742866.75 | 2848.88 | 20-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3403588.62 | 2840.68 | 20-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2656830.60 | 2755.81 | 14-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2805726.88 | 2614.40 | 29-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2935339.44 | 2939.65 | 27-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4048044.28 | 3621.78 | 27-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32950145.84 | 3621.78 | 12-NOV-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408313E+09 | 3621.78 | 01-DEC-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2656830.60 | 2614.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.511453E+09 | 3621.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.956875E+09 | 3620.42 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.569076E+09 | 3620.42 | 03-FEB-16:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388594E+09 | 3620.42 | 09-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4919268.45 | 3620.42 | 11-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2068491.62 | 2239.18 | 31-MAY-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1083443.85 | 1947.56 | 23-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 538607.43 | 884.47 | 17-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 888095.06 | 1804.84 | 21-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2012536.17 | 2410.47 | 14-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4955094.52 | 3620.42 | 27-OCT-18:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79831121.96 | 3620.42 | 14-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.661117E+09 | 3620.42 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.267196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 538607.43 | 884.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.956875E+09 | 3620.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.264078E+10 | 21132.22 | 03-JAN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169639E+10 | 21132.22 | 04-FEB-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.882253E+09 | 21132.22 | 03-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17204115.48 | 20577.50 | 17-APR-21:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4774039.59 | 8005.03 | 14-MAY-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1872233.65 | 5548.66 | 09-JUN-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2261643.45 | 13103.63 | 14-JUL-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3096145.41 | 8715.70 | 15-AUG-21:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2619647.48 | 8899.29 | 14-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21144062.06 | 19369.96 | 27-OCT-18:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151659E+09 | 21132.22 | 15-NOV-03:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182287E+10 | 21132.22 | 04-DEC-01:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.724692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1872233.65 | 5548.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.264078E+10 | 21132.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.546924E+09 | 3619.45 | 10-JAN-09:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361973E+09 | 3619.45 | 03-FEB-16:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318986E+09 | 3619.45 | 03-MAR-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3850717.81 | 3510.41 | 10-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 46803.41 | 391.09 | 22-MAY-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25689.95 | 299.72 | 07-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 65735.89 | 487.95 | 17-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 579583.24 | 2135.38 | 29-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3287463.45 | 3619.45 | 27-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32662794.40 | 3619.45 | 13-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.463005E+09 | 3619.45 | 20-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.546924E+09 | 3619.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.984454E+09 | 3618.08 | 04-JAN-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.564016E+09 | 3618.08 | 04-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388601E+09 | 3618.08 | 09-MAR-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3523320.75 | 2770.34 | 17-APR-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 662068.27 | 2339.36 | 31-MAY-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32302.48 | 430.70 | 06-JUN-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 212282.61 | 1377.36 | 11-JUL-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 296947.80 | 945.08 | 15-AUG-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 635638.60 | 2813.04 | 14-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4344551.37 | 2847.23 | 28-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87385243.40 | 3487.62 | 14-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.737976E+09 | 3618.08 | 17-DEC-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 32302.48 | 430.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.984454E+09 | 3618.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.258543E+09 | 1126.96 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167221E+09 | 1126.96 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153932E+09 | 1126.96 | 09-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5244055.82 | 1093.16 | 02-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1559075.92 | 831.62 | 22-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1136771.16 | 734.65 | 20-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1142447.51 | 735.28 | 31-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1188022.49 | 744.79 | 29-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1024381.41 | 716.21 | 09-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4325346.73 | 1071.67 | 27-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34324770.19 | 1119.97 | 14-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201873E+09 | 1126.96 | 19-DEC-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.831514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1024381.41 | 716.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.258543E+09 | 1126.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.423257E+09 | 1126.87 | 03-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244452E+09 | 1126.87 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177527E+09 | 1126.87 | 09-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3423695.32 | 1117.30 | 02-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 777214.81 | 670.86 | 20-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 446346.01 | 651.97 | 03-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 447964.61 | 511.34 | 31-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 538856.45 | 678.21 | 21-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 728195.68 | 682.01 | 09-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5334026.03 | 1057.23 | 27-OCT-18:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65961756.65 | 1126.87 | 15-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304498E+09 | 1126.87 | 04-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 446346.01 | 511.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.423257E+09 | 1126.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.389471E+09 | 5456.20 | 04-JAN-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304231E+09 | 5456.20 | 04-FEB-19:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366660E+09 | 5456.20 | 08-MAR-23:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9180496.56 | 4676.32 | 11-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1724157.70 | 3139.19 | 13-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1911943.22 | 2246.25 | 06-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1117589.60 | 1721.69 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1566285.28 | 1744.83 | 04-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1313837.65 | 3365.52 | 29-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4144998.84 | 3225.60 | 28-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18264946.92 | 5456.20 | 15-NOV-03:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.320611E+09 | 5456.20 | 04-DEC-01:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1117589.60 | 1721.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.389471E+09 | 5456.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.122810E+11 | 0.648380E+10 | 39430.36 | 20-JAN-03:00 | 13702.57 | 0.28 |
February | 0.00 | 0.00 | 0.157649E+11 | 0.820893E+10 | 37158.87 | 02-FEB-22:52 | 14436.47 | 0.44 |
March | 0.00 | 0.00 | 0.214882E+11 | 0.124012E+11 | 42711.49 | 07-MAR-20:00 | 16276.01 | 0.44 |
April | 0.00 | 0.00 | 0.359402E+11 | 0.209158E+11 | 47849.55 | 28-APR-20:10 | 17342.89 | 0.67 |
May | 0.00 | 0.00 | 0.556196E+11 | 0.326812E+11 | 45374.19 | 17-MAY-21:20 | 16997.26 | 0.76 |
June | 0.00 | 0.00 | 0.556888E+11 | 0.320694E+11 | 42271.90 | 06-JUN-20:00 | 16422.32 | 0.76 |
July | 0.00 | 0.00 | 0.629139E+11 | 0.335666E+11 | 47912.61 | 12-JUL-21:00 | 18118.92 | 0.76 |
August | 0.00 | 0.00 | 0.605654E+11 | 0.331211E+11 | 48381.23 | 12-AUG-21:10 | 16997.13 | 0.76 |
September | 0.00 | 0.00 | 0.587743E+11 | 0.314213E+11 | 49372.22 | 05-SEP-08:62 | 18150.01 | 0.76 |
October | 0.00 | 0.00 | 0.476503E+11 | 0.278038E+11 | 51492.62 | 22-OCT-08:03 | 17549.22 | 0.70 |
November | 0.00 | 0.00 | 0.249222E+11 | 0.151495E+11 | 48216.32 | 03-NOV-21:10 | 16670.35 | 0.55 |
December | 0.00 | 0.00 | 0.203708E+11 | 0.104368E+11 | 45545.87 | 15-DEC-21:10 | 16748.69 | 0.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.471980E+12 | 0.264259E+12 | 0.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.122810E+11 | 0.648380E+10 | 37158.87 | 13702.57 | 0.28 | |
Maximum of Months | 0.00 | 0.00 | 0.629139E+11 | 0.335666E+11 | 51492.62 | 18150.01 | 0.76 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.151639E+12 | 0.988923E+11 | 363063.80 | 19-JAN-21:00 | 172745.98 | 0.40 |
February | 0.00 | 0.00 | 0.200000E+12 | 0.125235E+12 | 329982.42 | 02-FEB-19:10 | 179912.21 | 0.60 |
March | 0.00 | 0.00 | 0.257455E+12 | 0.177293E+12 | 367531.46 | 07-MAR-20:00 | 181189.57 | 0.58 |
April | 0.00 | 0.00 | 0.434618E+12 | 0.289845E+12 | 429635.48 | 28-APR-20:50 | 197341.37 | 0.87 |
May | 0.00 | 0.00 | 0.770488E+12 | 0.470982E+12 | 427815.74 | 19-MAY-20:20 | 201311.27 | 1.00 |
June | 0.00 | 0.00 | 0.778782E+12 | 0.470905E+12 | 433366.28 | 29-JUN-17:15 | 223823.50 | 1.00 |
July | 0.00 | 0.00 | 0.870710E+12 | 0.494478E+12 | 445967.16 | 22-JUL-10:35 | 228592.22 | 1.00 |
August | 0.00 | 0.00 | 0.850143E+12 | 0.492168E+12 | 461133.42 | 09-AUG-20:20 | 211288.87 | 1.00 |
September | 0.00 | 0.00 | 0.803697E+12 | 0.455915E+12 | 468213.77 | 10-SEP-10:35 | 249492.24 | 1.00 |
October | 0.00 | 0.00 | 0.657474E+12 | 0.406705E+12 | 471780.85 | 23-OCT-20:50 | 213106.81 | 0.91 |
November | 0.00 | 0.00 | 0.326295E+12 | 0.222208E+12 | 462677.43 | 03-NOV-19:40 | 208737.27 | 0.73 |
December | 0.00 | 0.00 | 0.240164E+12 | 0.152642E+12 | 417572.73 | 15-DEC-21:00 | 199083.87 | 0.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.634146E+13 | 0.385727E+13 | 0.80 | |||
Minimum of Months | 0.00 | 0.00 | 0.151639E+12 | 0.988923E+11 | 329982.42 | 172745.98 | 0.40 | |
Maximum of Months | 0.00 | 0.00 | 0.870710E+12 | 0.494478E+12 | 471780.85 | 249492.24 | 1.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.267045E+10 | 0.123089E+10 | 15743.48 | 19-JAN-09:02 | 9864.51 | 0.50 |
February | 0.00 | 0.00 | 0.341798E+10 | 0.160976E+10 | 15297.01 | 24-FEB-09:02 | 10185.48 | 0.62 |
March | 0.00 | 0.00 | 0.386352E+10 | 0.180225E+10 | 15956.61 | 18-MAR-08:62 | 9591.45 | 0.64 |
April | 0.00 | 0.00 | 0.640653E+10 | 0.331108E+10 | 15633.89 | 01-APR-08:62 | 9681.47 | 0.88 |
May | 0.00 | 0.00 | 0.937468E+10 | 0.529560E+10 | 14122.08 | 02-MAY-08:61 | 11158.36 | 0.95 |
June | 0.00 | 0.00 | 0.981409E+10 | 0.580072E+10 | 14546.53 | 07-JUN-08:61 | 10806.41 | 0.96 |
July | 0.00 | 0.00 | 0.102450E+11 | 0.599369E+10 | 13732.15 | 12-JUL-08:61 | 11463.79 | 0.96 |
August | 0.00 | 0.00 | 0.102282E+11 | 0.594525E+10 | 14903.65 | 29-AUG-08:61 | 10554.51 | 0.96 |
September | 0.00 | 0.00 | 0.934917E+10 | 0.521921E+10 | 16704.33 | 05-SEP-08:62 | 9107.59 | 0.95 |
October | 0.00 | 0.00 | 0.905685E+10 | 0.529401E+10 | 15398.87 | 22-OCT-08:62 | 10150.30 | 0.92 |
November | 0.00 | 0.00 | 0.513906E+10 | 0.254947E+10 | 15675.21 | 01-NOV-08:62 | 9979.09 | 0.82 |
December | 0.00 | 0.00 | 0.372539E+10 | 0.179012E+10 | 16181.31 | 12-DEC-09:02 | 9303.27 | 0.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.832908E+11 | 0.458421E+11 | 0.81 | |||
Minimum of Months | 0.00 | 0.00 | 0.267045E+10 | 0.123089E+10 | 13732.15 | 9107.59 | 0.50 | |
Maximum of Months | 0.00 | 0.00 | 0.102450E+11 | 0.599369E+10 | 16704.33 | 11463.79 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.859486E+09 | 0.323173E+09 | 15258.20 | 19-JAN-22:52 | 9496.81 | 0.20 |
February | 0.00 | 0.00 | 0.139578E+10 | 0.556904E+09 | 14934.79 | 02-FEB-22:52 | 9471.13 | 0.31 |
March | 0.00 | 0.00 | 0.204418E+10 | 0.838152E+09 | 15184.69 | 07-MAR-09:51 | 9622.07 | 0.41 |
April | 0.00 | 0.00 | 0.458245E+10 | 0.238624E+10 | 16559.99 | 29-APR-07:51 | 10566.64 | 0.62 |
May | 0.00 | 0.00 | 0.901858E+10 | 0.522826E+10 | 15797.28 | 05-MAY-07:51 | 11027.05 | 0.90 |
June | 0.00 | 0.00 | 0.979730E+10 | 0.595744E+10 | 16531.52 | 06-JUN-07:52 | 10202.40 | 0.93 |
July | 0.00 | 0.00 | 0.101341E+11 | 0.604121E+10 | 15919.44 | 12-JUL-21:51 | 10823.03 | 0.94 |
August | 0.00 | 0.00 | 0.963338E+10 | 0.565298E+10 | 16517.99 | 29-AUG-08:61 | 9995.33 | 0.91 |
September | 0.00 | 0.00 | 0.799489E+10 | 0.443162E+10 | 17222.45 | 05-SEP-08:41 | 8240.14 | 0.84 |
October | 0.00 | 0.00 | 0.692760E+10 | 0.384973E+10 | 17781.41 | 21-OCT-08:61 | 9175.46 | 0.75 |
November | 0.00 | 0.00 | 0.243562E+10 | 0.103938E+10 | 15312.89 | 02-NOV-08:51 | 9290.27 | 0.50 |
December | 0.00 | 0.00 | 0.151448E+10 | 0.621993E+09 | 15660.38 | 15-DEC-09:52 | 8988.92 | 0.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.663379E+11 | 0.369271E+11 | 0.64 | |||
Minimum of Months | 0.00 | 0.00 | 0.859486E+09 | 0.323173E+09 | 14934.79 | 8240.14 | 0.20 | |
Maximum of Months | 0.00 | 0.00 | 0.101341E+11 | 0.604121E+10 | 17781.41 | 11027.05 | 0.94 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.291264E+11 | 0.172406E+11 | 47899.21 | 01-JAN-14:00 | 37940.43 | 0.64 |
February | 0.00 | 0.00 | 0.275001E+11 | 0.154158E+11 | 39433.39 | 02-FEB-13:30 | 34992.75 | 0.70 |
March | 0.00 | 0.00 | 0.215521E+11 | 0.940574E+10 | 33461.01 | 06-MAR-13:10 | 24780.90 | 0.67 |
April | 0.00 | 0.00 | 0.269070E+11 | 0.100869E+11 | 26111.56 | 28-APR-16:20 | 14610.42 | 0.92 |
May | 0.00 | 0.00 | 0.403132E+11 | 0.163992E+11 | 27110.72 | 04-MAY-16:10 | 15980.26 | 0.99 |
June | 0.00 | 0.00 | 0.405821E+11 | 0.168985E+11 | 29029.38 | 17-JUN-08:00 | 15900.68 | 0.99 |
July | 0.00 | 0.00 | 0.447443E+11 | 0.192358E+11 | 30747.09 | 09-JUL-08:00 | 17893.46 | 0.99 |
August | 0.00 | 0.00 | 0.467968E+11 | 0.211515E+11 | 31888.77 | 30-AUG-16:10 | 21687.22 | 1.00 |
September | 0.00 | 0.00 | 0.463045E+11 | 0.220812E+11 | 39812.74 | 10-SEP-15:10 | 32029.92 | 1.00 |
October | 0.00 | 0.00 | 0.533162E+11 | 0.308723E+11 | 43990.04 | 07-OCT-15:10 | 37439.83 | 0.97 |
November | 0.00 | 0.00 | 0.428264E+11 | 0.255856E+11 | 45293.18 | 06-NOV-14:00 | 34074.13 | 0.89 |
December | 0.00 | 0.00 | 0.346187E+11 | 0.205669E+11 | 48126.86 | 10-DEC-13:40 | 37599.96 | 0.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.454588E+12 | 0.224940E+12 | 0.88 | |||
Minimum of Months | 0.00 | 0.00 | 0.215521E+11 | 0.940574E+10 | 26111.56 | 14610.42 | 0.64 | |
Maximum of Months | 0.00 | 0.00 | 0.533162E+11 | 0.308723E+11 | 48126.86 | 37940.43 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.993110E+10 | 0.455799E+10 | 91760.77 | 19-JAN-22:52 | 56917.07 | 0.30 |
February | 0.00 | 0.00 | 0.140223E+11 | 0.680929E+10 | 90679.23 | 02-FEB-22:52 | 57741.45 | 0.34 |
March | 0.00 | 0.00 | 0.208409E+11 | 0.110434E+11 | 90168.18 | 18-MAR-21:51 | 58696.53 | 0.43 |
April | 0.00 | 0.00 | 0.346100E+11 | 0.199558E+11 | 98350.39 | 29-APR-07:51 | 61764.73 | 0.54 |
May | 0.00 | 0.00 | 0.627555E+11 | 0.396560E+11 | 92989.24 | 05-MAY-07:51 | 62226.84 | 0.82 |
June | 0.00 | 0.00 | 0.661124E+11 | 0.433074E+11 | 97120.50 | 06-JUN-07:52 | 58795.44 | 0.86 |
July | 0.00 | 0.00 | 0.690933E+11 | 0.453436E+11 | 92718.95 | 12-JUL-21:51 | 63838.98 | 0.87 |
August | 0.00 | 0.00 | 0.650289E+11 | 0.415734E+11 | 96824.82 | 29-AUG-08:61 | 58520.26 | 0.83 |
September | 0.00 | 0.00 | 0.558320E+11 | 0.340515E+11 | 103660.32 | 05-SEP-08:41 | 46518.74 | 0.76 |
October | 0.00 | 0.00 | 0.477349E+11 | 0.284752E+11 | 107606.97 | 21-OCT-08:61 | 52648.36 | 0.66 |
November | 0.00 | 0.00 | 0.221612E+11 | 0.113927E+11 | 89104.25 | 02-NOV-08:51 | 56513.47 | 0.47 |
December | 0.00 | 0.00 | 0.156794E+11 | 0.777932E+10 | 92980.85 | 12-DEC-09:52 | 52610.89 | 0.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.483802E+12 | 0.293946E+12 | 0.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.993110E+10 | 0.455799E+10 | 89104.25 | 46518.74 | 0.30 | |
Maximum of Months | 0.00 | 0.00 | 0.690933E+11 | 0.453436E+11 | 107606.97 | 63838.98 | 0.87 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.249423E+10 | 0.110613E+10 | 14121.17 | 30-JAN-19:01 | 8828.84 | 0.52 |
February | 0.00 | 0.00 | 0.311838E+10 | 0.140336E+10 | 13792.04 | 02-FEB-09:02 | 9000.70 | 0.65 |
March | 0.00 | 0.00 | 0.406687E+10 | 0.196935E+10 | 14503.07 | 18-MAR-08:62 | 8618.71 | 0.68 |
April | 0.00 | 0.00 | 0.631445E+10 | 0.322573E+10 | 14068.55 | 01-APR-08:62 | 9011.50 | 0.91 |
May | 0.00 | 0.00 | 0.994350E+10 | 0.590088E+10 | 12387.14 | 23-MAY-08:61 | 10352.90 | 0.97 |
June | 0.00 | 0.00 | 0.101524E+11 | 0.617142E+10 | 12965.16 | 07-JUN-08:61 | 9915.49 | 0.97 |
July | 0.00 | 0.00 | 0.107784E+11 | 0.662566E+10 | 12551.08 | 12-JUL-18:02 | 10249.30 | 0.97 |
August | 0.00 | 0.00 | 0.103703E+11 | 0.619835E+10 | 12910.25 | 17-AUG-08:61 | 10000.14 | 0.97 |
September | 0.00 | 0.00 | 0.938930E+10 | 0.536535E+10 | 14995.15 | 05-SEP-08:62 | 8333.28 | 0.96 |
October | 0.00 | 0.00 | 0.895682E+10 | 0.529186E+10 | 13830.33 | 20-OCT-08:61 | 9255.28 | 0.93 |
November | 0.00 | 0.00 | 0.514167E+10 | 0.260523E+10 | 14175.76 | 01-NOV-08:62 | 9026.20 | 0.84 |
December | 0.00 | 0.00 | 0.334226E+10 | 0.155307E+10 | 14634.26 | 12-DEC-09:02 | 8382.14 | 0.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.840686E+11 | 0.474164E+11 | 0.83 | |||
Minimum of Months | 0.00 | 0.00 | 0.249423E+10 | 0.110613E+10 | 12387.14 | 8333.28 | 0.52 | |
Maximum of Months | 0.00 | 0.00 | 0.107784E+11 | 0.662566E+10 | 14995.15 | 10352.90 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.787938E+09 | 0.284743E+09 | 14336.46 | 19-JAN-09:51 | 9921.60 | 0.21 |
February | 0.00 | 0.00 | 0.122797E+10 | 0.474361E+09 | 13948.14 | 24-FEB-09:51 | 10004.84 | 0.32 |
March | 0.00 | 0.00 | 0.227213E+10 | 0.101553E+10 | 14827.52 | 07-MAR-09:51 | 10348.07 | 0.43 |
April | 0.00 | 0.00 | 0.457744E+10 | 0.235067E+10 | 15381.81 | 29-APR-07:51 | 10565.69 | 0.65 |
May | 0.00 | 0.00 | 0.955410E+10 | 0.577180E+10 | 14813.66 | 02-MAY-08:11 | 10946.16 | 0.91 |
June | 0.00 | 0.00 | 0.101155E+11 | 0.629169E+10 | 15283.96 | 06-JUN-07:52 | 9674.93 | 0.94 |
July | 0.00 | 0.00 | 0.106802E+11 | 0.667478E+10 | 14313.94 | 12-JUL-21:51 | 9554.56 | 0.96 |
August | 0.00 | 0.00 | 0.978355E+10 | 0.586483E+10 | 15595.82 | 29-AUG-08:61 | 10103.42 | 0.92 |
September | 0.00 | 0.00 | 0.803887E+10 | 0.452187E+10 | 15735.15 | 05-SEP-08:41 | 7642.49 | 0.85 |
October | 0.00 | 0.00 | 0.685159E+10 | 0.382819E+10 | 16682.23 | 21-OCT-08:61 | 9203.49 | 0.76 |
November | 0.00 | 0.00 | 0.244696E+10 | 0.110365E+10 | 14908.53 | 11-NOV-09:41 | 10480.16 | 0.50 |
December | 0.00 | 0.00 | 0.126804E+10 | 0.497972E+09 | 15033.32 | 16-DEC-09:51 | 9931.96 | 0.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.676042E+11 | 0.386801E+11 | 0.65 | |||
Minimum of Months | 0.00 | 0.00 | 0.787938E+09 | 0.284743E+09 | 13948.14 | 7642.49 | 0.21 | |
Maximum of Months | 0.00 | 0.00 | 0.106802E+11 | 0.667478E+10 | 16682.23 | 10946.16 | 0.96 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.627133E+09 | 0.298618E+09 | 4311.06 | 19-JAN-09:02 | 2403.66 | 0.43 |
February | 0.00 | 0.00 | 0.830018E+09 | 0.406449E+09 | 4169.65 | 24-FEB-09:02 | 2486.70 | 0.56 |
March | 0.00 | 0.00 | 0.958002E+09 | 0.460394E+09 | 4434.25 | 18-MAR-08:62 | 2351.11 | 0.60 |
April | 0.00 | 0.00 | 0.164011E+10 | 0.876743E+09 | 4311.10 | 30-APR-08:61 | 2476.37 | 0.85 |
May | 0.00 | 0.00 | 0.247304E+10 | 0.140250E+10 | 3903.36 | 12-MAY-08:61 | 2821.66 | 0.95 |
June | 0.00 | 0.00 | 0.260831E+10 | 0.155230E+10 | 4047.32 | 07-JUN-08:61 | 2691.90 | 0.96 |
July | 0.00 | 0.00 | 0.270182E+10 | 0.158548E+10 | 3830.16 | 12-JUL-08:61 | 2872.29 | 0.96 |
August | 0.00 | 0.00 | 0.268269E+10 | 0.155967E+10 | 4147.18 | 29-AUG-08:61 | 2619.60 | 0.96 |
September | 0.00 | 0.00 | 0.241300E+10 | 0.133551E+10 | 4665.87 | 05-SEP-08:62 | 2191.37 | 0.95 |
October | 0.00 | 0.00 | 0.226944E+10 | 0.130908E+10 | 4279.79 | 20-OCT-08:61 | 2508.55 | 0.90 |
November | 0.00 | 0.00 | 0.120478E+10 | 0.601454E+09 | 4300.51 | 01-NOV-08:62 | 2483.36 | 0.75 |
December | 0.00 | 0.00 | 0.881616E+09 | 0.433266E+09 | 4472.69 | 12-DEC-09:02 | 2207.04 | 0.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.212900E+11 | 0.118215E+11 | 0.78 | |||
Minimum of Months | 0.00 | 0.00 | 0.627133E+09 | 0.298618E+09 | 3830.16 | 2191.37 | 0.43 | |
Maximum of Months | 0.00 | 0.00 | 0.270182E+10 | 0.158548E+10 | 4665.87 | 2872.29 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.194004E+09 | 72419528.32 | 4158.40 | 19-JAN-22:52 | 2403.62 | 0.18 |
February | 0.00 | 0.00 | 0.335655E+09 | 0.137711E+09 | 4066.14 | 02-FEB-22:52 | 2405.81 | 0.28 |
March | 0.00 | 0.00 | 0.509638E+09 | 0.214861E+09 | 4128.50 | 18-MAR-21:51 | 2525.57 | 0.37 |
April | 0.00 | 0.00 | 0.121278E+10 | 0.651687E+09 | 4508.72 | 28-APR-08:31 | 2370.41 | 0.61 |
May | 0.00 | 0.00 | 0.239876E+10 | 0.140462E+10 | 4320.39 | 05-MAY-07:51 | 2763.56 | 0.90 |
June | 0.00 | 0.00 | 0.261329E+10 | 0.160231E+10 | 4599.86 | 06-JUN-07:52 | 2457.94 | 0.93 |
July | 0.00 | 0.00 | 0.267865E+10 | 0.160335E+10 | 4206.89 | 12-JUL-21:51 | 3000.69 | 0.94 |
August | 0.00 | 0.00 | 0.254125E+10 | 0.149419E+10 | 4498.13 | 29-AUG-08:61 | 2456.56 | 0.91 |
September | 0.00 | 0.00 | 0.208514E+10 | 0.114866E+10 | 4687.73 | 05-SEP-08:41 | 2017.22 | 0.84 |
October | 0.00 | 0.00 | 0.175096E+10 | 0.960097E+09 | 4946.10 | 21-OCT-08:61 | 2146.70 | 0.73 |
November | 0.00 | 0.00 | 0.553409E+09 | 0.240962E+09 | 4188.27 | 02-NOV-08:51 | 2311.63 | 0.42 |
December | 0.00 | 0.00 | 0.351832E+09 | 0.148679E+09 | 4259.56 | 15-DEC-09:52 | 2239.44 | 0.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.172254E+11 | 0.967955E+10 | 0.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.194004E+09 | 72419528.32 | 4066.14 | 2017.22 | 0.18 | |
Maximum of Months | 0.00 | 0.00 | 0.267865E+10 | 0.160335E+10 | 4946.10 | 3000.69 | 0.94 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.759273E+10 | 0.457456E+10 | 19546.86 | 30-JAN-19:01 | 11399.94 | 0.72 |
February | 0.00 | 0.00 | 0.746086E+10 | 0.437432E+10 | 18996.05 | 02-FEB-19:02 | 11791.49 | 0.75 |
March | 0.00 | 0.00 | 0.663926E+10 | 0.355556E+10 | 20123.65 | 18-MAR-08:62 | 10816.94 | 0.69 |
April | 0.00 | 0.00 | 0.833933E+10 | 0.422860E+10 | 19868.99 | 28-APR-08:62 | 11202.33 | 0.88 |
May | 0.00 | 0.00 | 0.122446E+11 | 0.695179E+10 | 17978.30 | 05-MAY-08:61 | 12682.82 | 0.95 |
June | 0.00 | 0.00 | 0.123051E+11 | 0.713363E+10 | 18355.70 | 06-JUN-08:61 | 12293.70 | 0.95 |
July | 0.00 | 0.00 | 0.132136E+11 | 0.780757E+10 | 17458.47 | 12-JUL-18:02 | 13047.74 | 0.95 |
August | 0.00 | 0.00 | 0.137232E+11 | 0.825587E+10 | 18866.71 | 29-AUG-08:61 | 11968.65 | 0.95 |
September | 0.00 | 0.00 | 0.134802E+11 | 0.802229E+10 | 21696.71 | 05-SEP-08:62 | 9679.38 | 0.95 |
October | 0.00 | 0.00 | 0.143615E+11 | 0.917895E+10 | 19476.40 | 12-OCT-08:62 | 11500.63 | 0.93 |
November | 0.00 | 0.00 | 0.108803E+11 | 0.681756E+10 | 19486.42 | 29-NOV-09:02 | 11462.51 | 0.88 |
December | 0.00 | 0.00 | 0.901217E+10 | 0.560254E+10 | 20631.63 | 12-DEC-09:02 | 10282.10 | 0.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.129253E+12 | 0.765032E+11 | 0.87 | |||
Minimum of Months | 0.00 | 0.00 | 0.663926E+10 | 0.355556E+10 | 17458.47 | 9679.38 | 0.69 | |
Maximum of Months | 0.00 | 0.00 | 0.143615E+11 | 0.917895E+10 | 21696.71 | 13047.74 | 0.95 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 83951.02 | 525784.93 | 19-JAN-22:53 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 116344.00 | 488357.63 | 02-FEB-22:53 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 130194.64 | 487516.15 | 30-MAR-18:03 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 220942.94 | 541560.80 | 29-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 370327.39 | 582661.98 | 24-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 388131.02 | 626872.27 | 29-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 416508.65 | 622789.25 | 05-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 406653.04 | 652380.48 | 09-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 395361.86 | 636525.65 | 09-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 322613.07 | 635660.22 | 07-OCT-08:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 174203.08 | 595379.08 | 03-NOV-21:51 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 126144.27 | 555451.80 | 16-DEC-22:53 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 263465.63 | 0.00 | ||||
Minimum of Months | 83951.02 | 487516.15 | 0.00 | 0.00 | ||
Maximum of Months | 416508.65 | 652380.48 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 21468.89 | 44976.44 | 23-JAN-07:34 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 21297.98 | 44905.70 | 01-FEB-07:40 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 20522.06 | 43885.08 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 19275.36 | 41432.90 | 03-APR-06:55 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 17941.20 | 38838.95 | 01-MAY-06:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 16868.03 | 36168.05 | 01-JUN-06:58 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16324.59 | 34387.68 | 03-JUL-06:57 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16512.25 | 35143.66 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 17321.50 | 37261.62 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18557.67 | 40205.80 | 31-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 19891.95 | 42793.63 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 20955.45 | 44485.84 | 29-DEC-07:50 |
Annual Sum or Average | 0.00 | 18898.07 | ||||
Minimum of Months | 0.00 | 0.00 | 16324.59 | 34387.68 | ||
Maximum of Months | 0.00 | 0.00 | 21468.89 | 44976.44 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261333E+10 | 0.67 | 1299.30 | 16-JAN-16:23 | 0.87 |
February | 0.236042E+10 | 0.67 | 1299.30 | 01-FEB-00:05 | 0.87 |
March | 0.261333E+10 | 0.67 | 1299.30 | 01-MAR-00:05 | 0.87 |
April | 0.252903E+10 | 0.67 | 1299.30 | 04-APR-15:25 | 0.87 |
May | 0.261333E+10 | 0.67 | 1299.30 | 01-MAY-15:15 | 0.87 |
June | 0.252903E+10 | 0.67 | 1299.30 | 02-JUN-15:25 | 0.87 |
July | 0.261333E+10 | 0.67 | 1299.30 | 07-JUL-16:30 | 0.87 |
August | 0.261333E+10 | 0.67 | 1299.30 | 03-AUG-15:50 | 0.87 |
September | 0.252903E+10 | 0.67 | 1299.30 | 01-SEP-15:27 | 0.87 |
October | 0.261333E+10 | 0.67 | 1299.30 | 01-OCT-15:35 | 0.87 |
November | 0.252903E+10 | 0.67 | 1299.30 | 07-NOV-16:15 | 0.87 |
December | 0.261333E+10 | 0.67 | 1299.30 | 08-DEC-16:23 | 0.87 |
Annual Sum or Average | 0.307698E+11 | 0.67 | |||
Minimum of Months | 0.236042E+10 | 0.67 | 1299.30 | 0.87 | |
Maximum of Months | 0.261333E+10 | 0.67 | 1299.30 | 0.87 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.415316E+11 | 0.93 | 25170.25 | 19-JAN-22:10 | 1.24 |
February | 0.374491E+11 | 0.93 | 23393.51 | 02-FEB-22:10 | 1.18 |
March | 0.415723E+11 | 0.93 | 23348.29 | 06-MAR-22:10 | 1.18 |
April | 0.410693E+11 | 0.94 | 24694.88 | 28-APR-21:20 | 1.23 |
May | 0.443272E+11 | 0.96 | 27144.28 | 25-MAY-21:20 | 1.30 |
June | 0.434886E+11 | 0.97 | 28086.48 | 28-JUN-21:40 | 1.33 |
July | 0.450113E+11 | 0.97 | 28497.94 | 19-JUL-21:40 | 1.34 |
August | 0.459662E+11 | 0.98 | 31396.80 | 24-AUG-21:40 | 1.42 |
September | 0.440661E+11 | 0.98 | 29916.58 | 11-SEP-21:20 | 1.38 |
October | 0.455863E+11 | 0.98 | 32469.06 | 06-OCT-21:20 | 1.45 |
November | 0.420872E+11 | 0.95 | 28271.59 | 02-NOV-21:20 | 1.33 |
December | 0.424052E+11 | 0.94 | 27510.98 | 15-DEC-22:10 | 1.31 |
Annual Sum or Average | 0.514560E+12 | 0.95 | |||
Minimum of Months | 0.374491E+11 | 0.93 | 23348.29 | 1.18 | |
Maximum of Months | 0.459662E+11 | 0.98 | 32469.06 | 1.45 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.26 | 76.61 | 01-JAN-00:05 | 0.26 |
February | 0.185347E+09 | 0.26 | 76.61 | 01-FEB-00:05 | 0.26 |
March | 0.205205E+09 | 0.26 | 76.61 | 01-MAR-00:05 | 0.26 |
April | 0.198586E+09 | 0.26 | 76.61 | 01-APR-00:10 | 0.26 |
May | 0.205205E+09 | 0.26 | 76.61 | 01-MAY-00:10 | 0.26 |
June | 0.198586E+09 | 0.26 | 76.61 | 01-JUN-00:10 | 0.26 |
July | 0.205205E+09 | 0.26 | 76.61 | 01-JUL-00:10 | 0.26 |
August | 0.205205E+09 | 0.26 | 76.61 | 01-AUG-00:10 | 0.26 |
September | 0.198586E+09 | 0.26 | 76.61 | 01-SEP-00:10 | 0.26 |
October | 0.205205E+09 | 0.26 | 76.61 | 01-OCT-00:10 | 0.26 |
November | 0.198586E+09 | 0.26 | 76.61 | 01-NOV-00:10 | 0.26 |
December | 0.205205E+09 | 0.26 | 76.61 | 01-DEC-00:05 | 0.26 |
Annual Sum or Average | 0.241613E+10 | 0.26 | |||
Minimum of Months | 0.185347E+09 | 0.26 | 76.61 | 0.26 | |
Maximum of Months | 0.205205E+09 | 0.26 | 76.61 | 0.26 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | -0.0 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:10 | 0.26 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.26 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.26 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.26 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.26 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.26 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.26 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.26 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.26 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.26 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.26 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.26 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.26 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.26 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147206E+09 | 0.46 | 663.91 | 01-JAN-09:02 | 0.57 |
February | 0.166154E+09 | 0.47 | 663.91 | 01-FEB-16:12 | 0.57 |
March | 0.187156E+09 | 0.47 | 663.91 | 01-MAR-09:02 | 0.57 |
April | 0.268743E+09 | 0.51 | 663.91 | 01-APR-08:62 | 0.57 |
May | 0.379229E+09 | 0.55 | 663.91 | 01-MAY-08:61 | 0.57 |
June | 0.401162E+09 | 0.55 | 663.91 | 01-JUN-08:61 | 0.57 |
July | 0.412683E+09 | 0.55 | 663.91 | 01-JUL-08:62 | 0.57 |
August | 0.411952E+09 | 0.55 | 663.91 | 01-AUG-08:61 | 0.57 |
September | 0.373662E+09 | 0.55 | 663.91 | 01-SEP-08:62 | 0.57 |
October | 0.371416E+09 | 0.54 | 663.91 | 01-OCT-08:61 | 0.57 |
November | 0.219846E+09 | 0.51 | 663.91 | 01-NOV-08:62 | 0.57 |
December | 0.182916E+09 | 0.47 | 663.91 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.352212E+10 | 0.51 | |||
Minimum of Months | 0.147206E+09 | 0.46 | 663.91 | 0.57 | |
Maximum of Months | 0.412683E+09 | 0.55 | 663.91 | 0.57 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 95409077.33 | 0.34 | 646.12 | 01-JAN-09:51 | 0.57 |
February | 93206144.42 | 0.33 | 646.12 | 01-FEB-16:12 | 0.57 |
March | 0.111589E+09 | 0.34 | 646.12 | 01-MAR-09:02 | 0.57 |
April | 0.191572E+09 | 0.36 | 646.12 | 01-APR-08:52 | 0.57 |
May | 0.367597E+09 | 0.51 | 646.12 | 01-MAY-08:61 | 0.57 |
June | 0.405074E+09 | 0.53 | 646.12 | 01-JUN-08:61 | 0.57 |
July | 0.409340E+09 | 0.54 | 646.12 | 01-JUL-08:62 | 0.57 |
August | 0.388488E+09 | 0.52 | 646.12 | 01-AUG-08:61 | 0.57 |
September | 0.320084E+09 | 0.48 | 646.12 | 01-SEP-08:62 | 0.57 |
October | 0.280408E+09 | 0.44 | 646.12 | 01-OCT-08:51 | 0.57 |
November | 0.108332E+09 | 0.34 | 646.12 | 01-NOV-08:52 | 0.57 |
December | 0.103573E+09 | 0.35 | 646.12 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.287467E+10 | 0.42 | |||
Minimum of Months | 93206144.42 | 0.33 | 646.12 | 0.57 | |
Maximum of Months | 0.409340E+09 | 0.54 | 646.12 | 0.57 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.103978E+10 | 0.44 | 1969.98 | 01-JAN-14:00 | 0.57 |
February | 0.947919E+09 | 0.46 | 1179.06 | 02-FEB-13:30 | 0.57 |
March | 0.770612E+09 | 0.40 | 1024.03 | 05-MAR-13:30 | 0.57 |
April | 0.941885E+09 | 0.53 | 783.23 | 28-APR-16:20 | 0.57 |
May | 0.131300E+10 | 0.57 | 818.07 | 04-MAY-16:20 | 0.57 |
June | 0.131336E+10 | 0.57 | 819.93 | 17-JUN-08:00 | 0.57 |
July | 0.142470E+10 | 0.57 | 875.49 | 19-JUL-17:20 | 0.57 |
August | 0.149096E+10 | 0.57 | 942.80 | 30-AUG-16:20 | 0.57 |
September | 0.147131E+10 | 0.57 | 1166.76 | 10-SEP-13:30 | 0.57 |
October | 0.170934E+10 | 0.57 | 1773.03 | 13-OCT-13:30 | 0.57 |
November | 0.145509E+10 | 0.54 | 1878.08 | 06-NOV-13:30 | 0.57 |
December | 0.121327E+10 | 0.45 | 1943.12 | 10-DEC-13:30 | 0.57 |
Annual Sum or Average | 0.150912E+11 | 0.52 | |||
Minimum of Months | 0.770612E+09 | 0.40 | 783.23 | 0.57 | |
Maximum of Months | 0.170934E+10 | 0.57 | 1969.98 | 0.57 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587959E+09 | 0.32 | 3795.02 | 01-JAN-09:51 | 0.57 |
February | 0.663155E+09 | 0.30 | 3795.02 | 01-FEB-09:53 | 0.57 |
March | 0.921139E+09 | 0.31 | 3795.02 | 01-MAR-09:02 | 0.57 |
April | 0.141302E+10 | 0.31 | 3795.02 | 01-APR-08:52 | 0.57 |
May | 0.264319E+10 | 0.47 | 3795.02 | 01-MAY-08:61 | 0.57 |
June | 0.281317E+10 | 0.49 | 3795.02 | 01-JUN-07:32 | 0.57 |
July | 0.290890E+10 | 0.50 | 3795.02 | 01-JUL-08:62 | 0.57 |
August | 0.271839E+10 | 0.48 | 3795.02 | 01-AUG-08:61 | 0.57 |
September | 0.230044E+10 | 0.43 | 3795.02 | 01-SEP-08:62 | 0.57 |
October | 0.197780E+10 | 0.39 | 3795.02 | 01-OCT-08:51 | 0.57 |
November | 0.922499E+09 | 0.29 | 3795.02 | 01-NOV-08:52 | 0.57 |
December | 0.775626E+09 | 0.31 | 3795.02 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.206453E+11 | 0.38 | |||
Minimum of Months | 0.587959E+09 | 0.29 | 3795.02 | 0.57 | |
Maximum of Months | 0.290890E+10 | 0.50 | 3795.02 | 0.57 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137243E+09 | 0.47 | 598.86 | 01-JAN-09:02 | 0.57 |
February | 0.150068E+09 | 0.48 | 598.86 | 01-FEB-16:12 | 0.57 |
March | 0.188532E+09 | 0.49 | 598.86 | 01-MAR-09:02 | 0.57 |
April | 0.258392E+09 | 0.53 | 598.86 | 01-APR-08:62 | 0.57 |
May | 0.405120E+09 | 0.56 | 598.86 | 01-MAY-08:61 | 0.57 |
June | 0.416590E+09 | 0.56 | 598.86 | 01-JUN-08:61 | 0.57 |
July | 0.440323E+09 | 0.56 | 598.86 | 01-JUL-08:62 | 0.57 |
August | 0.418556E+09 | 0.56 | 598.86 | 01-AUG-08:61 | 0.57 |
September | 0.373212E+09 | 0.55 | 598.86 | 01-SEP-08:62 | 0.57 |
October | 0.366375E+09 | 0.55 | 598.86 | 01-OCT-08:61 | 0.57 |
November | 0.218593E+09 | 0.52 | 598.86 | 01-NOV-08:62 | 0.57 |
December | 0.165930E+09 | 0.48 | 598.86 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.353893E+10 | 0.53 | |||
Minimum of Months | 0.137243E+09 | 0.47 | 598.86 | 0.57 | |
Maximum of Months | 0.440323E+09 | 0.56 | 598.86 | 0.57 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 87035581.84 | 0.34 | 584.75 | 01-JAN-09:51 | 0.57 |
February | 81694947.64 | 0.33 | 584.75 | 01-FEB-16:12 | 0.57 |
March | 0.116681E+09 | 0.35 | 584.75 | 01-MAR-09:02 | 0.57 |
April | 0.189486E+09 | 0.38 | 584.75 | 01-APR-08:52 | 0.57 |
May | 0.395498E+09 | 0.52 | 584.75 | 01-MAY-08:61 | 0.57 |
June | 0.421015E+09 | 0.54 | 584.75 | 01-JUN-07:32 | 0.57 |
July | 0.438991E+09 | 0.55 | 584.75 | 01-JUL-08:62 | 0.57 |
August | 0.397648E+09 | 0.53 | 584.75 | 01-AUG-08:61 | 0.57 |
September | 0.321584E+09 | 0.48 | 584.75 | 01-SEP-08:62 | 0.57 |
October | 0.278838E+09 | 0.45 | 584.75 | 01-OCT-08:51 | 0.57 |
November | 0.106633E+09 | 0.34 | 584.75 | 01-NOV-08:52 | 0.57 |
December | 93469864.93 | 0.34 | 584.75 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.292858E+10 | 0.43 | |||
Minimum of Months | 81694947.64 | 0.33 | 584.75 | 0.57 | |
Maximum of Months | 0.438991E+09 | 0.55 | 584.75 | 0.57 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 40430481.16 | 0.45 | 175.54 | 01-JAN-09:02 | 0.57 |
February | 43711161.04 | 0.47 | 175.54 | 01-FEB-16:12 | 0.57 |
March | 49581358.80 | 0.48 | 175.54 | 01-MAR-09:02 | 0.57 |
April | 69826179.48 | 0.51 | 175.54 | 01-APR-08:62 | 0.57 |
May | 0.101979E+09 | 0.55 | 175.54 | 01-MAY-08:61 | 0.57 |
June | 0.108545E+09 | 0.55 | 175.54 | 01-JUN-08:61 | 0.57 |
July | 0.110118E+09 | 0.55 | 175.54 | 01-JUL-08:62 | 0.57 |
August | 0.109255E+09 | 0.55 | 175.54 | 01-AUG-08:61 | 0.57 |
September | 97389924.81 | 0.54 | 175.54 | 01-SEP-08:62 | 0.57 |
October | 94143875.53 | 0.53 | 175.54 | 01-OCT-08:61 | 0.57 |
November | 52882807.99 | 0.51 | 175.54 | 01-NOV-08:62 | 0.57 |
December | 47650451.54 | 0.47 | 175.54 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.925513E+09 | 0.51 | |||
Minimum of Months | 40430481.16 | 0.45 | 175.54 | 0.57 | |
Maximum of Months | 0.110118E+09 | 0.55 | 175.54 | 0.57 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 30143990.27 | 0.34 | 170.69 | 01-JAN-09:51 | 0.57 |
February | 26683748.59 | 0.33 | 170.69 | 01-FEB-16:12 | 0.57 |
March | 31086225.90 | 0.35 | 170.69 | 01-MAR-09:02 | 0.57 |
April | 51668086.55 | 0.36 | 170.69 | 01-APR-08:52 | 0.57 |
May | 99229998.10 | 0.51 | 170.69 | 01-MAY-08:61 | 0.57 |
June | 0.109722E+09 | 0.53 | 170.69 | 01-JUN-08:61 | 0.57 |
July | 0.109275E+09 | 0.54 | 170.69 | 01-JUL-08:62 | 0.57 |
August | 0.103541E+09 | 0.52 | 170.69 | 01-AUG-08:61 | 0.57 |
September | 84208743.95 | 0.48 | 170.69 | 01-SEP-08:62 | 0.57 |
October | 71706142.68 | 0.44 | 170.69 | 01-OCT-08:51 | 0.57 |
November | 26489292.41 | 0.34 | 170.69 | 01-NOV-08:52 | 0.57 |
December | 30267861.53 | 0.35 | 170.69 | 01-DEC-21:02 | 0.57 |
Annual Sum or Average | 0.774022E+09 | 0.43 | |||
Minimum of Months | 26489292.41 | 0.33 | 170.69 | 0.57 | |
Maximum of Months | 0.109722E+09 | 0.54 | 170.69 | 0.57 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.345753E+09 | 0.51 | 791.10 | 01-JAN-09:02 | 0.57 |
February | 0.323458E+09 | 0.51 | 791.10 | 01-FEB-16:12 | 0.57 |
March | 0.294451E+09 | 0.49 | 791.10 | 01-MAR-09:02 | 0.57 |
April | 0.337248E+09 | 0.51 | 791.10 | 01-APR-08:62 | 0.57 |
May | 0.492359E+09 | 0.54 | 791.10 | 01-MAY-08:61 | 0.57 |
June | 0.500043E+09 | 0.55 | 791.10 | 01-JUN-08:61 | 0.57 |
July | 0.535651E+09 | 0.55 | 791.10 | 01-JUL-08:62 | 0.57 |
August | 0.554225E+09 | 0.55 | 791.10 | 01-AUG-08:61 | 0.57 |
September | 0.539971E+09 | 0.55 | 791.10 | 01-SEP-08:62 | 0.57 |
October | 0.609791E+09 | 0.54 | 791.10 | 01-OCT-08:61 | 0.57 |
November | 0.465781E+09 | 0.53 | 791.10 | 01-NOV-08:62 | 0.57 |
December | 0.404553E+09 | 0.51 | 791.10 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.540328E+10 | 0.53 | |||
Minimum of Months | 0.294451E+09 | 0.49 | 791.10 | 0.57 | |
Maximum of Months | 0.609791E+09 | 0.55 | 791.10 | 0.57 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.135893E+09 | 0.123526E+09 | 606.22 | 19-JAN-22:53 | 551.06 | 551.06 | 6.72 | 12.37 |
February | 0.177631E+09 | 0.161466E+09 | 535.76 | 24-FEB-16:12 | 487.01 | 487.01 | 6.72 | 11.72 |
March | 0.235747E+09 | 0.214294E+09 | 674.62 | 30-MAR-18:03 | 613.23 | 613.23 | 6.72 | 12.96 |
April | 0.432471E+09 | 0.393116E+09 | 870.78 | 29-APR-18:03 | 791.54 | 791.54 | 6.72 | 14.47 |
May | 0.979041E+09 | 0.889948E+09 | 1010.89 | 25-MAY-18:03 | 918.90 | 918.90 | 6.72 | 15.42 |
June | 0.106578E+10 | 0.968792E+09 | 1256.32 | 29-JUN-18:03 | 1142.00 | 1142.00 | 6.72 | 16.90 |
July | 0.124582E+10 | 0.113245E+10 | 1243.43 | 05-JUL-18:03 | 1130.28 | 1130.28 | 6.72 | 16.83 |
August | 0.118031E+10 | 0.107290E+10 | 1321.03 | 09-AUG-18:03 | 1200.81 | 1200.81 | 6.72 | 17.26 |
September | 0.105556E+10 | 0.959504E+09 | 1262.83 | 09-SEP-18:03 | 1147.91 | 1147.91 | 6.72 | 16.94 |
October | 0.868862E+09 | 0.789796E+09 | 1214.17 | 07-OCT-18:03 | 1103.68 | 1103.68 | 6.72 | 16.66 |
November | 0.347940E+09 | 0.316277E+09 | 945.30 | 02-NOV-18:03 | 859.28 | 859.28 | 6.72 | 14.99 |
December | 0.242551E+09 | 0.220479E+09 | 682.09 | 15-DEC-21:00 | 620.02 | 620.02 | 6.72 | 13.02 |
Annual Sum or Average | 0.796760E+10 | 0.724255E+10 | ||||||
Minimum of Months | 0.135893E+09 | 0.123526E+09 | 535.76 | 487.01 | 487.01 | 6.72 | 11.72 | |
Maximum of Months | 0.124582E+10 | 0.113245E+10 | 1321.03 | 1200.81 | 1200.81 | 6.72 | 17.26 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.732856E+10 | 0.666166E+10 | 3220.82 | 01-JAN-00:05 | 2927.73 | 2927.73 | 7.92 | 28.78 |
February | 0.703289E+10 | 0.639289E+10 | 3220.82 | 01-FEB-00:05 | 2927.73 | 2927.73 | 8.64 | 28.78 |
March | 0.775364E+10 | 0.704806E+10 | 3220.82 | 01-MAR-00:05 | 2927.73 | 2927.73 | 8.27 | 28.78 |
April | 0.834837E+10 | 0.758866E+10 | 3220.82 | 01-APR-00:10 | 2927.73 | 2927.73 | 9.14 | 28.78 |
May | 0.862664E+10 | 0.784162E+10 | 3220.82 | 01-MAY-00:10 | 2927.73 | 2927.73 | 8.81 | 28.78 |
June | 0.834837E+10 | 0.758866E+10 | 3220.82 | 01-JUN-00:10 | 2927.73 | 2927.73 | 9.57 | 28.78 |
July | 0.862664E+10 | 0.784162E+10 | 3220.82 | 01-JUL-00:10 | 2927.73 | 2927.73 | 9.65 | 28.78 |
August | 0.862664E+10 | 0.784162E+10 | 3220.82 | 01-AUG-00:10 | 2927.73 | 2927.73 | 9.52 | 28.78 |
September | 0.834837E+10 | 0.758866E+10 | 3220.82 | 01-SEP-00:10 | 2927.73 | 2927.73 | 9.81 | 28.78 |
October | 0.862664E+10 | 0.784162E+10 | 3220.82 | 01-OCT-00:10 | 2927.73 | 2927.73 | 9.40 | 28.78 |
November | 0.829735E+10 | 0.754229E+10 | 3220.82 | 01-NOV-00:10 | 2927.73 | 2927.73 | 9.44 | 28.78 |
December | 0.767766E+10 | 0.697900E+10 | 3220.82 | 01-DEC-00:05 | 2927.73 | 2927.73 | 7.01 | 28.78 |
Annual Sum or Average | 0.976418E+11 | 0.887564E+11 | ||||||
Minimum of Months | 0.703289E+10 | 0.639289E+10 | 3220.82 | 2927.73 | 2927.73 | 7.01 | 28.78 | |
Maximum of Months | 0.862664E+10 | 0.784162E+10 | 3220.82 | 2927.73 | 2927.73 | 9.81 | 28.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 50.88 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 51.75 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 51.94 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 54.37 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 54.75 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 55.11 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 55.35 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 55.40 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 55.25 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 54.33 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 54.56 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 52.13 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 50.88 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 55.40 | 0.37 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 83951.02 | 525784.93 | 19-JAN-22:53 | 11.06 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 116344.00 | 488357.63 | 02-FEB-22:53 | 10.75 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 130194.64 | 487516.15 | 30-MAR-18:03 | 10.74 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 220942.94 | 541560.80 | 29-APR-18:03 | 11.19 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 370327.39 | 582661.98 | 24-MAY-18:03 | 11.53 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 388131.02 | 626872.27 | 29-JUN-18:03 | 11.90 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 416508.65 | 622789.25 | 05-JUL-18:03 | 11.87 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 406653.04 | 652380.48 | 09-AUG-18:03 | 12.11 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 395361.86 | 636525.65 | 09-SEP-18:03 | 11.98 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 322613.07 | 635660.22 | 07-OCT-08:03 | 11.97 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 174203.08 | 595379.08 | 03-NOV-21:51 | 11.64 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 126144.27 | 555451.80 | 16-DEC-22:53 | 11.31 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 263465.63 | 0.00 | ||||||
Minimum of Months | 83951.02 | 487516.15 | 10.74 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 416508.65 | 652380.48 | 12.11 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 50.88 | 60.05 | 21468.89 | 44976.44 | 23-JAN-07:34 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 51.75 | 60.05 | 21297.98 | 44905.70 | 01-FEB-07:40 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 51.94 | 60.05 | 20522.06 | 43885.08 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 54.37 | 60.05 | 19275.36 | 41432.90 | 03-APR-06:55 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 54.75 | 60.05 | 17941.20 | 38838.95 | 01-MAY-06:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 55.11 | 60.05 | 16868.03 | 36168.05 | 01-JUN-06:58 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 55.35 | 60.05 | 16324.59 | 34387.68 | 03-JUL-06:57 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 55.40 | 60.05 | 16512.25 | 35143.66 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 55.25 | 60.05 | 17321.50 | 37261.62 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.33 | 60.05 | 18557.67 | 40205.80 | 31-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 54.56 | 60.05 | 19891.95 | 42793.63 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 52.13 | 60.05 | 20955.45 | 44485.84 | 29-DEC-07:50 |
Annual Sum or Average | 0.00 | 18898.07 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.88 | 60.05 | 16324.59 | 34387.68 | ||
Maximum of Months | 0.00 | 0.00 | 55.40 | 60.05 | 21468.89 | 44976.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.122810E+11 | 0.261333E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.157649E+11 | 0.237536E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.214882E+11 | 0.261333E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.359402E+11 | 0.252903E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.556196E+11 | 0.261333E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.556888E+11 | 0.252903E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.629139E+11 | 0.261333E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.605654E+11 | 0.261333E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.587743E+11 | 0.252903E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.476503E+11 | 0.261333E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.249222E+11 | 0.252903E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.203708E+11 | 0.261333E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.471980E+12 | 0.307848E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.122810E+11 | 0.237536E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.629139E+11 | 0.261333E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.151639E+12 | 0.646890E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.200000E+12 | 0.504930E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.257455E+12 | 0.503875E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.434618E+12 | 0.414403E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.770488E+12 | 0.443381E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.778782E+12 | 0.435018E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.870710E+12 | 0.450194E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.850143E+12 | 0.459683E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.803697E+12 | 0.440669E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.657474E+12 | 0.455986E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.326295E+12 | 0.430362E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.240164E+12 | 0.556752E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.634146E+13 | 0.574214E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.151639E+12 | 0.414403E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.870710E+12 | 0.646890E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261333E+10 | 0.122810E+11 | 0.00 | 0.148203E+11 | 0.684977E+09 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.157649E+11 | 14936343.15 | 0.835995E+10 | 0.103765E+10 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.214882E+11 | 0.00 | 0.652791E+10 | 0.232105E+10 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.359402E+11 | 0.00 | 0.640678E+09 | 0.821983E+10 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.556196E+11 | 0.00 | 0.00 | 0.412466E+11 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.556888E+11 | 0.00 | 0.00 | 0.443427E+11 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 0.629139E+11 | 0.00 | 0.00 | 0.540845E+11 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 0.605654E+11 | 0.00 | 0.00 | 0.479117E+11 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.587743E+11 | 0.00 | 0.00 | 0.406954E+11 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.476503E+11 | 0.00 | 0.359109E+09 | 0.292098E+11 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.249222E+11 | 0.00 | 0.311004E+10 | 0.689250E+10 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.203708E+11 | 0.00 | 0.101903E+11 | 0.216198E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.471980E+12 | 14936343.15 | 0.440083E+11 | 0.278809E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 0.122810E+11 | 0.00 | 0.00 | 0.684977E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.629139E+11 | 14936343.15 | 0.148203E+11 | 0.540845E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.415316E+11 | 0.151639E+12 | 0.231574E+11 | 0.210163E+10 | 0.509251E+10 | 0.00 | 0.00 | 0.00 |
February | 0.374491E+11 | 0.200000E+12 | 0.130439E+11 | 0.551708E+10 | 0.841797E+10 | 0.00 | 0.00 | 0.00 |
March | 0.415723E+11 | 0.257455E+12 | 0.881523E+10 | 0.538588E+09 | 0.165323E+11 | 0.00 | 0.00 | 0.00 |
April | 0.410693E+11 | 0.434618E+12 | 0.370987E+09 | 0.00 | 0.392102E+11 | 0.00 | 0.00 | 0.00 |
May | 0.443272E+11 | 0.770488E+12 | 10891725.62 | 0.00 | 0.205553E+12 | 0.00 | 0.00 | 0.00 |
June | 0.434886E+11 | 0.778782E+12 | 13197546.19 | 0.00 | 0.235380E+12 | 0.00 | 0.00 | 0.00 |
July | 0.450113E+11 | 0.870710E+12 | 8069812.99 | 0.00 | 0.307217E+12 | 0.00 | 0.00 | 0.00 |
August | 0.459662E+11 | 0.850143E+12 | 2099725.56 | 0.00 | 0.258509E+12 | 0.00 | 0.00 | 0.00 |
September | 0.440661E+11 | 0.803697E+12 | 788456.04 | 0.00 | 0.207748E+12 | 0.00 | 0.00 | 0.00 |
October | 0.455863E+11 | 0.657474E+12 | 12314409.12 | 0.00 | 0.143716E+12 | 0.00 | 0.00 | 0.00 |
November | 0.420872E+11 | 0.326295E+12 | 0.948958E+09 | 0.00 | 0.305085E+11 | 0.00 | 0.00 | 0.00 |
December | 0.424052E+11 | 0.240164E+12 | 0.132700E+11 | 0.148056E+10 | 0.135556E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.514560E+12 | 0.634146E+13 | 0.596538E+11 | 0.963786E+10 | 0.147144E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.374491E+11 | 0.151639E+12 | 788456.04 | 0.00 | 0.509251E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.459662E+11 | 0.870710E+12 | 0.231574E+11 | 0.551708E+10 | 0.307217E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261333E+10 | 0.00 | 0.122810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.00 | 0.157649E+11 | 0.00 | 0.00 | 14936343.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.00 | 0.214882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.00 | 0.359402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.00 | 0.556196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.00 | 0.556888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 0.00 | 0.629139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 0.00 | 0.605654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.00 | 0.587743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.00 | 0.476503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.00 | 0.249222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.00 | 0.203708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.00 | 0.471980E+12 | 0.00 | 0.00 | 14936343.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 0.00 | 0.122810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.00 | 0.629139E+11 | 0.00 | 0.00 | 14936343.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.415316E+11 | 0.00 | 0.151639E+12 | 0.00 | 0.00 | 0.231574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.374491E+11 | 0.00 | 0.200000E+12 | 0.00 | 0.00 | 0.130439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.415723E+11 | 0.00 | 0.257455E+12 | 0.00 | 0.00 | 0.881523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.410693E+11 | 0.00 | 0.434618E+12 | 0.00 | 0.00 | 0.370987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.443272E+11 | 0.00 | 0.770488E+12 | 0.00 | 0.00 | 10891725.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.434886E+11 | 0.00 | 0.778782E+12 | 0.00 | 0.00 | 13197546.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.450113E+11 | 0.00 | 0.870710E+12 | 0.00 | 0.00 | 8069812.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.459662E+11 | 0.00 | 0.850143E+12 | 0.00 | 0.00 | 2099725.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.440661E+11 | 0.00 | 0.803697E+12 | 0.00 | 0.00 | 788456.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.455863E+11 | 0.00 | 0.657474E+12 | 0.00 | 0.00 | 12314409.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.420872E+11 | 0.00 | 0.326295E+12 | 0.00 | 0.00 | 0.948958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.424052E+11 | 0.00 | 0.240164E+12 | 0.00 | 0.00 | 0.132700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.514560E+12 | 0.00 | 0.634146E+13 | 0.00 | 0.00 | 0.596538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.374491E+11 | 0.00 | 0.151639E+12 | 0.00 | 0.00 | 788456.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.459662E+11 | 0.00 | 0.870710E+12 | 0.00 | 0.00 | 0.231574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.592151E+10 | 0.626124E+09 | 0.00 | 35816867.43 | 0.813008E+09 | 0.00 | 0.314681E+11 | 0.00 | 0.78 |
February | 0.226983E+11 | 0.142376E+09 | 0.00 | 2535524.89 | 0.138694E+10 | 0.00 | 0.378163E+10 | 0.00 | 0.80 |
March | 0.262774E+11 | 0.00 | 0.00 | 28659.51 | 0.289623E+10 | 0.00 | 0.166231E+09 | 0.00 | 0.79 |
April | 0.127094E+11 | 0.00 | 0.00 | 0.00 | 0.662964E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.208452E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 88249234.67 | 0.00 | 0.00 | 0.00 | 0.222949E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.540981E+10 | 0.00 | 0.00 | 0.230871E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.245249E+11 | 0.00 | 267204.75 | 0.308769E+10 | 0.00 | 51792966.40 | 0.00 | 0.63 |
September | 0.00 | 0.245587E+11 | 0.00 | 0.00 | 0.148887E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 51036976.83 | 0.171247E+11 | 0.00 | 19741696.80 | 0.869935E+09 | 0.00 | 0.834873E+10 | 0.00 | 0.75 |
November | 0.426807E+09 | 0.539834E+10 | 0.00 | 47754020.93 | 0.325281E+09 | 0.00 | 0.249054E+11 | 0.00 | 0.89 |
December | 0.103886E+10 | 0.361515E+10 | 0.00 | 48235989.01 | 0.387783E+09 | 0.00 | 0.317752E+11 | 0.00 | 0.81 |
Annual Sum or Average | 0.692116E+11 | 0.814001E+11 | 0.00 | 0.154380E+09 | 0.841127E+11 | 0.00 | 0.100497E+12 | 0.00 | 0.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.325281E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.262774E+11 | 0.245587E+11 | 0.00 | 48235989.01 | 0.230871E+11 | 0.00 | 0.317752E+11 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.258612E+10 | 0.143602E+09 | 0.00 | 2087661.37 | 26617470.91 | 938561.07 | 0.897557E+09 | 0.00 | 1.42 |
February | 0.193420E+10 | 0.208748E+09 | 0.00 | 1413991.95 | 4772492.91 | 29023267.02 | 0.531034E+09 | 0.00 | 1.48 |
March | 0.209460E+10 | 0.259252E+09 | 0.00 | 1079358.24 | 49478335.82 | 27834340.33 | 0.334787E+09 | 0.00 | 1.39 |
April | 0.985270E+09 | 0.605901E+09 | 0.00 | 486518.11 | 90440756.19 | 0.00 | 0.192233E+09 | 0.00 | 1.35 |
May | 0.00 | 0.218868E+10 | 0.00 | 0.00 | 60166094.11 | 0.00 | 0.00 | 0.00 | 1.15 |
June | 7066.45 | 0.250438E+10 | 0.00 | 14035.19 | 23542131.61 | 0.00 | 8150273.12 | 0.00 | 1.20 |
July | 0.00 | 0.329435E+10 | 0.00 | 0.00 | 22513824.87 | 0.00 | 0.00 | 0.00 | 1.23 |
August | 0.00 | 0.311378E+10 | 0.00 | 18395.84 | 18887785.71 | 0.00 | 4788341.09 | 0.00 | 1.27 |
September | 0.00 | 0.288536E+10 | 0.00 | 0.00 | 50377253.04 | 0.00 | 0.00 | 0.00 | 1.26 |
October | 0.355063E+09 | 0.229543E+10 | 0.00 | 1217389.71 | 11797614.92 | 0.00 | 0.352525E+09 | 0.00 | 1.54 |
November | 0.123458E+10 | 0.680897E+09 | 0.00 | 2959062.99 | 25287198.31 | 0.00 | 0.102909E+10 | 0.00 | 1.66 |
December | 0.210956E+10 | 0.437384E+09 | 0.00 | 2344227.13 | 47335382.21 | 20194240.47 | 0.818730E+09 | 0.00 | 1.50 |
Annual Sum or Average | 0.112994E+11 | 0.186178E+11 | 0.00 | 11620640.53 | 0.431216E+09 | 77990408.88 | 0.416890E+10 | 0.00 | 1.37 |
Minimum of Months | 0.00 | 0.143602E+09 | 0.00 | 0.00 | 4772492.91 | 0.00 | 0.00 | 0.00 | 1.15 |
Maximum of Months | 0.258612E+10 | 0.329435E+10 | 0.00 | 2959062.99 | 90440756.19 | 29023267.02 | 0.102909E+10 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.365726E+10 | 35808634.41 | 0.00 | 144486.88 | 0.114059E+09 | 0.00 | 0.219743E+09 | 0.00 | 1.27 |
February | 0.258044E+10 | 18125786.17 | 0.00 | 333448.85 | 0.145824E+09 | 0.00 | 0.258321E+09 | 0.00 | 1.34 |
March | 0.256198E+10 | 60230432.17 | 0.00 | 207961.39 | 0.250398E+09 | 0.00 | 0.273318E+09 | 0.00 | 1.33 |
April | 0.109766E+10 | 0.276619E+09 | 0.00 | 257951.39 | 0.437723E+09 | 0.00 | 0.264924E+09 | 0.00 | 1.29 |
May | 0.00 | 0.103763E+10 | 0.00 | 0.00 | 0.121742E+10 | 0.00 | 0.00 | 0.00 | 1.01 |
June | 8183.24 | 0.124542E+10 | 0.00 | 20506.97 | 0.118142E+10 | 0.00 | 9434101.27 | 0.00 | 1.02 |
July | 0.00 | 0.167825E+10 | 0.00 | 0.00 | 0.142328E+10 | 0.00 | 0.00 | 0.00 | 1.01 |
August | 0.00 | 0.153484E+10 | 0.00 | 12599.45 | 0.130316E+10 | 0.00 | 5553801.63 | 0.00 | 1.01 |
September | 0.00 | 0.141276E+10 | 0.00 | 0.00 | 0.119661E+10 | 0.00 | 0.00 | 0.00 | 1.01 |
October | 0.411472E+09 | 0.105993E+10 | 0.00 | 404940.92 | 0.739978E+09 | 0.00 | 0.381351E+09 | 0.00 | 1.15 |
November | 0.188197E+10 | 0.237009E+09 | 0.00 | 359476.80 | 0.331134E+09 | 0.00 | 0.525934E+09 | 0.00 | 1.35 |
December | 0.293546E+10 | 0.152260E+09 | 0.00 | 180846.19 | 0.254354E+09 | 0.00 | 0.299206E+09 | 0.00 | 1.26 |
Annual Sum or Average | 0.151262E+11 | 0.874887E+10 | 0.00 | 1922218.84 | 0.859537E+10 | 0.00 | 0.223779E+10 | 0.00 | 1.17 |
Minimum of Months | 0.00 | 18125786.17 | 0.00 | 0.00 | 0.114059E+09 | 0.00 | 0.00 | 0.00 | 1.01 |
Maximum of Months | 0.365726E+10 | 0.167825E+10 | 0.00 | 404940.92 | 0.142328E+10 | 0.00 | 0.525934E+09 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 40610867.68 | 44069186.03 | 0.00 | 501744.78 | 28199.30 | 0.00 | 0.200343E+09 | 0.00 | 0.06 |
February | 25660316.97 | 41877940.20 | 0.00 | 687056.13 | 77913.64 | 0.00 | 0.217989E+09 | 0.00 | 0.09 |
March | 20730462.19 | 95747057.84 | 0.00 | 819559.93 | 18810.59 | 0.00 | 0.281513E+09 | 0.00 | 0.11 |
April | 434720.96 | 0.309401E+09 | 0.00 | 1130645.84 | 0.00 | 0.00 | 0.327064E+09 | 0.00 | 0.19 |
May | 0.00 | 0.132275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.162253E+10 | 0.00 | 27183.23 | 0.00 | 0.00 | 4892355.42 | 0.00 | 0.32 |
July | 0.00 | 0.213974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
August | 0.00 | 0.189584E+10 | 0.00 | 19445.59 | 0.00 | 0.00 | 3720488.09 | 0.00 | 0.33 |
September | 0.00 | 0.160430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.111575E+10 | 0.00 | 931811.05 | 0.00 | 0.00 | 0.303383E+09 | 0.00 | 0.29 |
November | 3850615.51 | 0.271386E+09 | 0.00 | 1251036.29 | 90.50 | 0.00 | 0.495992E+09 | 0.00 | 0.17 |
December | 26601765.37 | 0.176033E+09 | 0.00 | 625976.22 | 157491.48 | 0.00 | 0.267599E+09 | 0.00 | 0.10 |
Annual Sum or Average | 0.117889E+09 | 0.106394E+11 | 0.00 | 5994459.08 | 282505.50 | 0.00 | 0.210250E+10 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 41877940.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Maximum of Months | 40610867.68 | 0.213974E+10 | 0.00 | 1251036.29 | 157491.48 | 0.00 | 0.495992E+09 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.244358E+10 | 0.00 | 0.00 | 0.00 | 94303624.00 | 0.00 | 0.00 | 0.00 | 0.65 |
February | 0.178919E+10 | 0.00 | 0.00 | 0.00 | 0.103317E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
March | 0.178709E+10 | 0.00 | 0.00 | 0.00 | 0.195730E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
April | 0.858914E+09 | 0.00 | 0.00 | 0.00 | 0.448036E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.140874E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 5963956.19 | 0.00 | 0.00 | 0.00 | 0.150671E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.192581E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 3508243.02 | 0.00 | 0.00 | 0.00 | 0.175820E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.162452E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 0.498172E+09 | 0.00 | 0.00 | 0.00 | 0.111408E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 0.151782E+10 | 0.00 | 0.00 | 0.00 | 0.354687E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
December | 0.203877E+10 | 0.00 | 0.00 | 0.00 | 0.255001E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
Annual Sum or Average | 0.109430E+11 | 0.00 | 0.00 | 0.00 | 0.107891E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 94303624.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.244358E+10 | 0.00 | 0.00 | 0.00 | 0.192581E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.199502E+10 | 0.00 | 98854666.99 | 0.00 | 0.00 | 0.486408E+11 | 0.00 | 15.87 |
February | 0.00 | 0.196360E+10 | 0.00 | 83790435.40 | 0.00 | 0.00 | 0.351621E+11 | 0.00 | 16.92 |
March | 0.00 | 0.400378E+10 | 0.00 | 85534819.11 | 0.00 | 0.00 | 0.356329E+11 | 0.00 | 16.78 |
April | 0.00 | 0.923722E+10 | 0.00 | 58937283.50 | 0.00 | 0.00 | 0.171630E+11 | 0.00 | 16.27 |
May | 0.00 | 0.289878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.64 |
June | 0.00 | 0.311001E+11 | 0.00 | 467511.96 | 0.00 | 0.00 | 78142270.85 | 0.00 | 12.68 |
July | 0.00 | 0.395543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 |
August | 0.00 | 0.360954E+11 | 0.00 | 291824.48 | 0.00 | 0.00 | 56128327.94 | 0.00 | 12.63 |
September | 0.00 | 0.330407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.59 |
October | 0.00 | 0.225577E+11 | 0.00 | 29996952.07 | 0.00 | 0.00 | 0.976241E+10 | 0.00 | 14.42 |
November | 0.00 | 0.721120E+10 | 0.00 | 78181711.07 | 0.00 | 0.00 | 0.308046E+11 | 0.00 | 17.18 |
December | 0.00 | 0.532686E+10 | 0.00 | 85724728.63 | 0.00 | 0.00 | 0.410639E+11 | 0.00 | 15.89 |
Annual Sum or Average | 0.00 | 0.221074E+12 | 0.00 | 0.521780E+09 | 0.00 | 0.00 | 0.218364E+12 | 0.00 | 14.69 |
Minimum of Months | 0.00 | 0.196360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.59 |
Maximum of Months | 0.00 | 0.395543E+11 | 0.00 | 98854666.99 | 0.00 | 0.00 | 0.486408E+11 | 0.00 | 17.18 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159602E+11 | 0.572747E+09 | 0.00 | 5534633.49 | 0.530656E+09 | 0.00 | 0.126219E+11 | 0.00 | 3.85 |
February | 0.124598E+11 | 0.777551E+09 | 0.00 | 4955933.56 | 0.431160E+09 | 0.00 | 0.846714E+10 | 0.00 | 4.06 |
March | 0.127218E+11 | 0.956566E+09 | 0.00 | 3907530.69 | 0.133329E+10 | 0.00 | 0.818152E+10 | 0.00 | 4.02 |
April | 0.462373E+10 | 0.248200E+10 | 0.00 | 2853822.94 | 0.275962E+10 | 0.00 | 0.542193E+10 | 0.00 | 3.88 |
May | 0.00 | 0.801633E+10 | 0.00 | 0.00 | 0.846463E+10 | 0.00 | 0.00 | 0.00 | 3.02 |
June | 60338.20 | 0.902119E+10 | 0.00 | 179713.81 | 0.860595E+10 | 0.00 | 69532789.38 | 0.00 | 3.03 |
July | 0.00 | 0.123802E+11 | 0.00 | 0.00 | 0.101500E+11 | 0.00 | 0.00 | 0.00 | 3.01 |
August | 0.00 | 0.124786E+11 | 0.00 | 67521.54 | 0.809150E+10 | 0.00 | 40975718.23 | 0.00 | 3.01 |
September | 0.00 | 0.124167E+11 | 0.00 | 0.00 | 0.658878E+10 | 0.00 | 0.00 | 0.00 | 3.01 |
October | 0.197165E+10 | 0.107019E+11 | 0.00 | 3173496.14 | 0.234242E+10 | 0.00 | 0.385334E+10 | 0.00 | 3.44 |
November | 0.531765E+10 | 0.298089E+10 | 0.00 | 7690787.29 | 0.116945E+10 | 0.00 | 0.124317E+11 | 0.00 | 4.09 |
December | 0.128066E+11 | 0.192803E+10 | 0.00 | 6120307.88 | 0.105662E+10 | 0.00 | 0.110393E+11 | 0.00 | 3.82 |
Annual Sum or Average | 0.658615E+11 | 0.747127E+11 | 0.00 | 34483747.35 | 0.515241E+11 | 0.00 | 0.621274E+11 | 0.00 | 3.52 |
Minimum of Months | 0.00 | 0.572747E+09 | 0.00 | 0.00 | 0.431160E+09 | 0.00 | 0.00 | 0.00 | 3.01 |
Maximum of Months | 0.159602E+11 | 0.124786E+11 | 0.00 | 7690787.29 | 0.101500E+11 | 0.00 | 0.126219E+11 | 0.00 | 4.09 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.574958E+11 | 0.927225E+09 | 0.00 | 13605789.88 | 0.217834E+10 | 0.00 | 0.225752E+11 | 0.00 | 1.56 |
February | 0.376489E+11 | 0.428548E+09 | 0.00 | 17946306.59 | 0.296187E+10 | 0.00 | 0.209792E+11 | 0.00 | 1.65 |
March | 0.364279E+11 | 0.151446E+10 | 0.00 | 16258824.88 | 0.490347E+10 | 0.00 | 0.221292E+11 | 0.00 | 1.63 |
April | 0.111289E+11 | 0.587566E+10 | 0.00 | 14675236.78 | 0.884621E+10 | 0.00 | 0.170059E+11 | 0.00 | 1.58 |
May | 0.00 | 0.218349E+11 | 0.00 | 0.00 | 0.247057E+11 | 0.00 | 0.00 | 0.00 | 1.23 |
June | 0.00 | 0.243107E+11 | 0.00 | 882022.74 | 0.257547E+11 | 0.00 | 0.194564E+09 | 0.00 | 1.25 |
July | 0.00 | 0.331191E+11 | 0.00 | 0.00 | 0.310237E+11 | 0.00 | 0.00 | 0.00 | 1.24 |
August | 0.00 | 0.310580E+11 | 0.00 | 381921.73 | 0.276356E+11 | 0.00 | 0.114587E+09 | 0.00 | 1.25 |
September | 0.00 | 0.302225E+11 | 0.00 | 0.00 | 0.237471E+11 | 0.00 | 0.00 | 0.00 | 1.24 |
October | 0.535892E+10 | 0.249362E+11 | 0.00 | 14294808.18 | 0.124330E+11 | 0.00 | 0.110429E+11 | 0.00 | 1.42 |
November | 0.186415E+11 | 0.690047E+10 | 0.00 | 23809982.07 | 0.488890E+10 | 0.00 | 0.311023E+11 | 0.00 | 1.66 |
December | 0.415864E+11 | 0.420344E+10 | 0.00 | 14166930.10 | 0.420691E+10 | 0.00 | 0.252248E+11 | 0.00 | 1.55 |
Annual Sum or Average | 0.208288E+12 | 0.185331E+12 | 0.00 | 0.116022E+09 | 0.173285E+12 | 0.00 | 0.150368E+12 | 0.00 | 1.44 |
Minimum of Months | 0.00 | 0.428548E+09 | 0.00 | 0.00 | 0.217834E+10 | 0.00 | 0.00 | 0.00 | 1.23 |
Maximum of Months | 0.574958E+11 | 0.331191E+11 | 0.00 | 23809982.07 | 0.310237E+11 | 0.00 | 0.311023E+11 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 38936996.60 | 0.100744E+09 | 14031.41 | 5069898.96 | 2187575.12 | 0.401330E+09 | 0.602762E+09 | 2603.82 | 0.34 |
February | 29074822.39 | 0.116990E+09 | 37510.76 | 4582379.01 | 200633.73 | 0.236288E+09 | 0.455269E+09 | 6400.25 | 0.34 |
March | 34386564.65 | 0.232777E+09 | 145795.81 | 5121621.90 | 103620.69 | 0.216499E+09 | 0.503998E+09 | 13123.45 | 0.34 |
April | 9180768.13 | 0.496965E+09 | 114063.02 | 4647480.10 | 651904.46 | 827629.30 | 0.301687E+09 | 8359.62 | 0.34 |
May | 0.00 | 0.122978E+10 | 1501581.46 | 0.00 | 0.00 | 0.00 | 0.00 | 33292.63 | 0.34 |
June | 0.00 | 0.132757E+10 | 1118637.79 | 0.00 | 0.00 | 0.00 | 0.00 | 21732.89 | 0.34 |
July | 0.00 | 0.163688E+10 | 1574504.42 | 0.00 | 0.00 | 0.00 | 0.00 | 13557.64 | 0.34 |
August | 0.00 | 0.146674E+10 | 1464060.02 | 0.00 | 0.00 | 0.00 | 0.00 | 16805.44 | 0.34 |
September | 0.00 | 0.127686E+10 | 1083136.80 | 71013.53 | 0.00 | 0.00 | 235312.66 | 19482.23 | 0.34 |
October | 205527.63 | 0.929005E+09 | 337048.27 | 2425295.58 | 0.00 | 726477.73 | 0.171707E+09 | 5896.97 | 0.34 |
November | 0.00 | 0.321823E+09 | 238846.44 | 6308145.46 | 308724.68 | 11116965.82 | 0.610268E+09 | 12682.40 | 0.34 |
December | 21374239.71 | 0.295954E+09 | 210056.05 | 4730839.04 | 982643.12 | 0.281403E+09 | 0.587354E+09 | 9028.21 | 0.34 |
Annual Sum or Average | 0.133159E+09 | 0.943209E+10 | 7839272.25 | 32956673.58 | 4435101.79 | 0.114819E+10 | 0.323328E+10 | 162965.56 | 0.34 |
Minimum of Months | 0.00 | 0.100744E+09 | 14031.41 | 0.00 | 0.00 | 0.00 | 0.00 | 2603.82 | 0.34 |
Maximum of Months | 38936996.60 | 0.163688E+10 | 1574504.42 | 6308145.46 | 2187575.12 | 0.401330E+09 | 0.610268E+09 | 33292.63 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129902E+09 | 75242810.05 | 180584.43 | 1301598.11 | 27504149.21 | 0.634369E+09 | 0.282403E+09 | 8966.79 | 0.34 |
February | 0.123723E+09 | 91386277.80 | 220045.32 | 1433238.75 | 25604331.62 | 0.323924E+09 | 0.276049E+09 | 10158.82 | 0.34 |
March | 0.129947E+09 | 0.179629E+09 | 436121.14 | 2183540.77 | 52924848.20 | 0.258448E+09 | 0.369338E+09 | 22259.82 | 0.34 |
April | 0.105013E+09 | 0.387590E+09 | 125482.03 | 2396186.68 | 0.109961E+09 | 847094.34 | 0.208050E+09 | 4846.08 | 0.34 |
May | 0.00 | 0.115874E+10 | 946009.63 | 0.00 | 71472441.41 | 0.00 | 0.00 | 12490.59 | 0.34 |
June | 0.00 | 0.129674E+10 | 591739.46 | 0.00 | 31215254.47 | 0.00 | 0.00 | 6104.86 | 0.34 |
July | 0.00 | 0.161037E+10 | 310431.60 | 0.00 | 27586865.36 | 0.00 | 0.00 | 712.88 | 0.34 |
August | 0.00 | 0.139904E+10 | 556308.50 | 0.00 | 68443750.68 | 0.00 | 0.00 | 3380.72 | 0.34 |
September | 306290.29 | 0.115827E+10 | 653168.79 | 0.00 | 0.118880E+09 | 0.00 | 0.00 | 10187.96 | 0.34 |
October | 47926099.13 | 0.853305E+09 | 696649.39 | 1165589.65 | 75225337.05 | 502847.35 | 0.125449E+09 | 12229.89 | 0.34 |
November | 0.148682E+09 | 0.252059E+09 | 490154.85 | 1915677.12 | 69776076.08 | 53983892.31 | 0.423038E+09 | 20599.30 | 0.34 |
December | 0.124354E+09 | 0.213930E+09 | 408362.40 | 1250807.38 | 82773481.89 | 0.437509E+09 | 0.331643E+09 | 9606.82 | 0.34 |
Annual Sum or Average | 0.809853E+09 | 0.867631E+10 | 5615057.54 | 11646638.46 | 0.761367E+09 | 0.170958E+10 | 0.201597E+10 | 121544.53 | 0.34 |
Minimum of Months | 0.00 | 75242810.05 | 125482.03 | 0.00 | 25604331.62 | 0.00 | 0.00 | 712.88 | 0.34 |
Maximum of Months | 0.148682E+09 | 0.161037E+10 | 946009.63 | 2396186.68 | 0.118880E+09 | 0.634369E+09 | 0.423038E+09 | 22259.82 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 58324777.32 | 0.234732E+09 | 0.00 | 2760602.31 | 0.00 | 0.00 | 0.914458E+09 | 0.00 | 0.02 |
February | 55497967.14 | 0.447588E+09 | 0.00 | 1397122.26 | 0.00 | 0.00 | 0.587657E+09 | 0.00 | 0.02 |
March | 0.299517E+09 | 0.409597E+09 | 0.00 | 1187068.63 | 0.00 | 0.00 | 0.409592E+09 | 0.00 | 0.02 |
April | 22872.44 | 0.416275E+09 | 0.00 | 655682.95 | 1192394.32 | 0.00 | 0.246322E+09 | 0.00 | 0.02 |
May | 0.00 | 0.979620E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.948151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
July | 0.00 | 0.133179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.122834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 0.00 | 0.132240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.891497E+09 | 0.00 | 600849.40 | 0.00 | 0.00 | 89115297.33 | 0.00 | 0.02 |
November | 24293.15 | 0.384479E+09 | 0.00 | 2292641.27 | 1126152.37 | 0.00 | 0.442209E+09 | 0.00 | 0.02 |
December | 0.146463E+09 | 0.312918E+09 | 0.00 | 2373382.50 | 13829626.50 | 0.00 | 0.588965E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.559850E+09 | 0.890738E+10 | 0.00 | 11267349.32 | 16148173.19 | 0.00 | 0.327832E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.234732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.299517E+09 | 0.133179E+10 | 0.00 | 2760602.31 | 13829626.50 | 0.00 | 0.914458E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.176204E+10 | 0.975768E+09 | 2516159.76 | 29335969.21 | 0.417961E+09 | 0.115159E+10 | 0.112722E+11 | 27386.59 | 0.39 |
February | 0.167823E+10 | 0.112519E+10 | 1791465.89 | 29629782.55 | 0.463000E+09 | 0.108123E+10 | 0.704686E+10 | 47501.21 | 0.39 |
March | 0.176913E+10 | 0.230583E+10 | 898071.49 | 38291674.24 | 0.853903E+09 | 0.224513E+09 | 0.827588E+10 | 42391.04 | 0.39 |
April | 0.144386E+10 | 0.504160E+10 | 218949.12 | 33276820.27 | 0.170892E+10 | 5275599.46 | 0.280808E+10 | 7167.12 | 0.39 |
May | 0.00 | 0.152691E+11 | 0.00 | 0.00 | 0.143102E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.173434E+11 | 0.00 | 0.00 | 0.677675E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.215257E+11 | 807081.90 | 0.00 | 0.695687E+09 | 0.00 | 0.00 | 5297.91 | 0.39 |
August | 0.00 | 0.185880E+11 | 1241035.31 | 0.00 | 0.132398E+10 | 0.00 | 0.00 | 962.25 | 0.39 |
September | 4154644.08 | 0.151417E+11 | 787786.99 | 0.00 | 0.219029E+10 | 0.00 | 0.00 | 845.00 | 0.39 |
October | 0.653553E+09 | 0.110903E+11 | 0.00 | 15345634.41 | 0.151425E+10 | 9806823.60 | 0.169566E+10 | 0.00 | 0.39 |
November | 0.203094E+10 | 0.321541E+10 | 900467.65 | 33716927.14 | 0.115608E+10 | 61899035.48 | 0.638673E+10 | 35514.26 | 0.39 |
December | 0.171898E+10 | 0.276456E+10 | 449015.60 | 33043516.17 | 0.126525E+10 | 0.812628E+09 | 0.957219E+10 | 14991.22 | 0.39 |
Annual Sum or Average | 0.110609E+11 | 0.114386E+12 | 9610033.71 | 0.212640E+09 | 0.136980E+11 | 0.334694E+10 | 0.470576E+11 | 182056.61 | 0.39 |
Minimum of Months | 0.00 | 0.975768E+09 | 0.00 | 0.00 | 0.417961E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.203094E+10 | 0.215257E+11 | 2516159.76 | 38291674.24 | 0.219029E+10 | 0.115159E+10 | 0.112722E+11 | 47501.21 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26749155.06 | 0.100751E+09 | 8717.36 | 5135897.03 | 2187575.12 | 0.414899E+09 | 0.601314E+09 | 975.12 | 0.34 |
February | 21205488.14 | 0.117222E+09 | 10672.61 | 4619394.06 | 1154.77 | 0.227393E+09 | 0.471997E+09 | 397.92 | 0.34 |
March | 23385447.00 | 0.233028E+09 | 9922.17 | 5146789.63 | 0.00 | 0.229844E+09 | 0.501630E+09 | 1985.92 | 0.34 |
April | 27003.09 | 0.496997E+09 | 89026.34 | 4713396.96 | 651904.46 | 558431.66 | 0.311044E+09 | 1224.81 | 0.34 |
May | 0.00 | 0.123131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
June | 0.00 | 0.132871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.163846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 0.00 | 0.146822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.127782E+10 | 143724.88 | 74973.71 | 0.00 | 0.00 | 231352.48 | 3563.93 | 0.34 |
October | 0.00 | 0.929280E+09 | 65865.23 | 2411280.36 | 0.00 | 336796.34 | 0.172316E+09 | 2726.54 | 0.34 |
November | 0.00 | 0.322067E+09 | 7177.72 | 6752087.26 | 308724.68 | 15383773.72 | 0.605557E+09 | 351.71 | 0.34 |
December | 21858321.68 | 0.296045E+09 | 124355.05 | 4663935.86 | 982643.12 | 0.317646E+09 | 0.550693E+09 | 4488.73 | 0.34 |
Annual Sum or Average | 93225414.96 | 0.943992E+10 | 459461.36 | 33517754.88 | 4132002.15 | 0.120606E+10 | 0.321478E+10 | 15714.68 | 0.34 |
Minimum of Months | 0.00 | 0.100751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 26749155.06 | 0.163846E+10 | 143724.88 | 6752087.26 | 2187575.12 | 0.414899E+09 | 0.605557E+09 | 4488.73 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130113E+09 | 75546875.41 | 190392.27 | 1246090.92 | 27191180.59 | 0.624785E+09 | 0.291831E+09 | 8062.21 | 0.34 |
February | 0.123720E+09 | 90256294.83 | 104172.48 | 1590270.96 | 26858480.74 | 0.307904E+09 | 0.291915E+09 | 1865.51 | 0.34 |
March | 0.127046E+09 | 0.182317E+09 | 189006.38 | 2322085.95 | 50501383.35 | 0.274977E+09 | 0.355571E+09 | 5568.40 | 0.34 |
April | 97961826.39 | 0.388788E+09 | 273622.70 | 2638540.85 | 0.108615E+09 | 454959.19 | 0.215250E+09 | 5454.71 | 0.34 |
May | 0.00 | 0.115965E+10 | 193053.30 | 0.00 | 71318157.62 | 0.00 | 0.00 | 4782.05 | 0.34 |
June | 0.00 | 0.129753E+10 | 0.00 | 0.00 | 31031084.09 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.161058E+10 | 102713.40 | 0.00 | 27586865.36 | 0.00 | 0.00 | 1339.22 | 0.34 |
August | 0.00 | 0.139941E+10 | 188146.51 | 0.00 | 68443750.68 | 0.00 | 0.00 | 625.83 | 0.34 |
September | 306290.29 | 0.115905E+10 | 128846.70 | 0.00 | 0.118627E+09 | 0.00 | 0.00 | 3092.39 | 0.34 |
October | 47487037.14 | 0.854230E+09 | 161319.61 | 1105155.76 | 74843563.94 | 493796.83 | 0.125958E+09 | 4155.14 | 0.34 |
November | 0.148431E+09 | 0.253057E+09 | 196654.48 | 2596494.17 | 69086806.80 | 69199186.49 | 0.407393E+09 | 5024.03 | 0.34 |
December | 0.124149E+09 | 0.213554E+09 | 254685.00 | 1486714.29 | 83304968.73 | 0.448171E+09 | 0.320950E+09 | 8062.87 | 0.34 |
Annual Sum or Average | 0.799215E+09 | 0.868398E+10 | 1982612.83 | 12985352.89 | 0.757408E+09 | 0.172598E+10 | 0.200887E+10 | 48032.35 | 0.34 |
Minimum of Months | 0.00 | 75546875.41 | 0.00 | 0.00 | 26858480.74 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.148431E+09 | 0.161058E+10 | 273622.70 | 2638540.85 | 0.118627E+09 | 0.624785E+09 | 0.407393E+09 | 8062.87 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.200727E+11 | 0.00 | 0.00 | 0.00 | 0.774654E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
February | 0.146972E+11 | 0.00 | 0.00 | 0.00 | 0.848692E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
March | 0.146800E+11 | 0.00 | 0.00 | 0.00 | 0.160781E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
April | 0.705552E+10 | 0.00 | 0.00 | 0.00 | 0.368038E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.115720E+11 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 48990736.88 | 56547271.90 | 0.00 | 0.00 | 0.123203E+11 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.212524E+09 | 0.00 | 0.00 | 0.156070E+11 | 0.00 | 0.00 | 0.00 | 0.33 |
August | 28818355.69 | 92691624.93 | 0.00 | 0.00 | 0.143500E+11 | 0.00 | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.145929E+09 | 0.00 | 0.00 | 0.131987E+11 | 0.00 | 0.00 | 0.00 | 0.33 |
October | 0.409222E+10 | 0.435733E+09 | 0.00 | 0.00 | 0.871583E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
November | 0.124680E+11 | 0.00 | 0.00 | 0.00 | 0.291357E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
December | 0.167474E+11 | 0.00 | 0.00 | 0.00 | 0.209470E+10 | 0.00 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.898910E+11 | 0.943425E+09 | 0.00 | 0.00 | 0.876836E+11 | 0.00 | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.774654E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.200727E+11 | 0.435733E+09 | 0.00 | 0.00 | 0.156070E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10796929.99 | 25177456.97 | 11868.06 | 1097196.62 | 546893.78 | 0.143649E+09 | 0.106482E+09 | 924.29 | 0.34 |
February | 7163685.18 | 29260000.19 | 9859.43 | 1021408.64 | 37659.38 | 80626798.99 | 92491730.34 | 1118.33 | 0.34 |
March | 7983443.71 | 58209372.77 | 47808.66 | 1181185.80 | 0.00 | 85015917.12 | 95820864.91 | 2767.02 | 0.34 |
April | 1401872.52 | 0.124244E+09 | 26045.67 | 1098415.93 | 162976.11 | 1348563.32 | 75236812.06 | 2276.93 | 0.34 |
May | 0.00 | 0.307376E+09 | 440682.73 | 0.00 | 0.00 | 0.00 | 0.00 | 11646.78 | 0.34 |
June | 0.00 | 0.331737E+09 | 433285.22 | 0.00 | 0.00 | 0.00 | 0.00 | 7843.98 | 0.34 |
July | 0.00 | 0.409051E+09 | 557361.16 | 0.00 | 0.00 | 0.00 | 0.00 | 7832.03 | 0.34 |
August | 0.00 | 0.366620E+09 | 426057.01 | 0.00 | 0.00 | 0.00 | 0.00 | 8906.29 | 0.34 |
September | 0.00 | 0.319144E+09 | 340132.72 | 17636.50 | 0.00 | 0.00 | 58945.04 | 6798.62 | 0.34 |
October | 507575.70 | 0.232126E+09 | 208111.89 | 529280.97 | 0.00 | 2332079.21 | 40397130.19 | 3438.63 | 0.34 |
November | 107455.12 | 80465086.08 | 49780.57 | 1355371.86 | 77181.17 | 28436973.45 | 0.127024E+09 | 3818.17 | 0.34 |
December | 5794039.33 | 73936290.56 | 102130.83 | 999492.61 | 245660.78 | 0.110858E+09 | 0.106064E+09 | 4967.84 | 0.34 |
Annual Sum or Average | 33755001.55 | 0.235734E+10 | 2653123.95 | 7299988.93 | 1070371.22 | 0.452267E+09 | 0.643575E+09 | 62338.92 | 0.34 |
Minimum of Months | 0.00 | 25177456.97 | 9859.43 | 0.00 | 0.00 | 0.00 | 0.00 | 924.29 | 0.34 |
Maximum of Months | 10796929.99 | 0.409051E+09 | 557361.16 | 1355371.86 | 546893.78 | 0.143649E+09 | 0.127024E+09 | 11646.78 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 32475525.60 | 19043332.50 | 226160.57 | 221510.73 | 6460323.87 | 0.190687E+09 | 38609620.24 | 4310.69 | 0.34 |
February | 30587071.21 | 23022209.43 | 41826.40 | 272415.26 | 6238940.64 | 0.105898E+09 | 44524947.57 | 2226.92 | 0.34 |
March | 32000152.08 | 45493592.09 | 76315.35 | 470923.04 | 12678937.32 | 90985515.56 | 66522559.43 | 4277.69 | 0.34 |
April | 25797141.38 | 97061014.01 | 38260.00 | 568600.21 | 27318582.15 | 444721.54 | 52265934.66 | 2456.46 | 0.34 |
May | 0.00 | 0.289651E+09 | 267876.39 | 0.00 | 17868110.35 | 0.00 | 0.00 | 5767.64 | 0.34 |
June | 0.00 | 0.324142E+09 | 190766.16 | 0.00 | 7803813.62 | 0.00 | 0.00 | 2840.67 | 0.34 |
July | 0.00 | 0.402385E+09 | 283797.88 | 0.00 | 6896716.34 | 0.00 | 0.00 | 2275.37 | 0.34 |
August | 0.00 | 0.349657E+09 | 240944.99 | 0.00 | 17110937.67 | 0.00 | 0.00 | 3141.53 | 0.34 |
September | 76572.57 | 0.289465E+09 | 301292.10 | 0.00 | 29683062.61 | 0.00 | 0.00 | 4291.95 | 0.34 |
October | 11981524.78 | 0.213309E+09 | 241128.83 | 236398.07 | 18754370.60 | 2602306.70 | 28940708.69 | 5333.51 | 0.34 |
November | 37136473.20 | 63219431.21 | 136240.85 | 316131.83 | 17226031.25 | 50062605.42 | 69389711.10 | 4719.69 | 0.34 |
December | 31082982.98 | 53516366.75 | 95927.40 | 197988.00 | 20665170.18 | 0.143828E+09 | 48580112.41 | 2881.63 | 0.34 |
Annual Sum or Average | 0.201137E+09 | 0.216996E+10 | 2140536.89 | 2283967.13 | 0.188705E+09 | 0.584508E+09 | 0.348834E+09 | 44523.75 | 0.34 |
Minimum of Months | 0.00 | 19043332.50 | 38260.00 | 0.00 | 6238940.64 | 0.00 | 0.00 | 2226.92 | 0.34 |
Maximum of Months | 37136473.20 | 0.402385E+09 | 301292.10 | 568600.21 | 29683062.61 | 0.190687E+09 | 69389711.10 | 5767.64 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9887517.63 | 0.162204E+09 | 14210.61 | 14271283.89 | 3128378.02 | 0.245829E+09 | 0.141339E+10 | 1356.70 | 0.39 |
February | 4411644.03 | 0.188282E+09 | 11165.73 | 10453213.96 | 0.00 | 0.187381E+09 | 0.962537E+09 | 141.91 | 0.39 |
March | 34121700.08 | 0.374271E+09 | 18370.65 | 8561706.70 | 0.00 | 0.271298E+09 | 0.906680E+09 | 755.20 | 0.39 |
April | 43370.26 | 0.795276E+09 | 275301.91 | 6207782.22 | 3872344.04 | 1521509.00 | 0.500312E+09 | 6501.08 | 0.39 |
May | 0.00 | 0.197707E+10 | 565685.64 | 0.00 | 0.00 | 0.00 | 0.00 | 5755.81 | 0.39 |
June | 0.00 | 0.213325E+10 | 816596.97 | 0.00 | 0.00 | 0.00 | 0.00 | 4138.87 | 0.39 |
July | 0.00 | 0.263117E+10 | 398183.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1569.70 | 0.39 |
August | 0.00 | 0.235711E+10 | 1027147.47 | 0.00 | 0.00 | 0.00 | 0.00 | 4377.34 | 0.39 |
September | 0.00 | 0.205225E+10 | 312204.66 | 107990.08 | 0.00 | 0.00 | 384007.25 | 6408.24 | 0.39 |
October | 0.00 | 0.149240E+10 | 237550.34 | 3954342.41 | 0.00 | 739865.28 | 0.276480E+09 | 6972.74 | 0.39 |
November | 0.00 | 0.517686E+09 | 100617.18 | 13504363.04 | 0.00 | 2273823.91 | 0.992374E+09 | 845.22 | 0.39 |
December | 10105249.49 | 0.475564E+09 | 123787.41 | 12350558.60 | 1578245.06 | 0.197076E+09 | 0.121773E+10 | 2918.16 | 0.39 |
Annual Sum or Average | 58569481.49 | 0.151565E+11 | 3900822.23 | 69411240.90 | 8578967.12 | 0.906120E+09 | 0.626988E+10 | 41740.95 | 0.39 |
Minimum of Months | 0.00 | 0.162204E+09 | 11165.73 | 0.00 | 0.00 | 0.00 | 0.00 | 141.91 | 0.39 |
Maximum of Months | 34121700.08 | 0.263117E+10 | 1027147.47 | 14271283.89 | 3872344.04 | 0.271298E+09 | 0.141339E+10 | 6972.74 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170405E+11 | 0.853057E+09 | 0.00 | 18936149.20 | 0.108721E+10 | 0.00 | 0.331802E+11 | 0.00 | 5.01 |
February | 0.112706E+11 | 0.902046E+09 | 0.00 | 20703334.32 | 0.122339E+10 | 0.00 | 0.254946E+11 | 0.00 | 5.28 |
March | 0.991963E+10 | 0.254745E+10 | 0.00 | 23130576.57 | 0.147884E+10 | 0.00 | 0.268044E+11 | 0.00 | 5.24 |
April | 0.231786E+10 | 0.729874E+10 | 0.00 | 19376611.87 | 0.194642E+10 | 0.00 | 0.153318E+11 | 0.00 | 5.08 |
May | 0.00 | 0.255926E+11 | 0.00 | 0.00 | 0.355214E+10 | 0.00 | 0.00 | 0.00 | 3.96 |
June | 0.00 | 0.279204E+11 | 0.00 | 545605.38 | 0.328591E+10 | 0.00 | 0.122072E+09 | 0.00 | 3.98 |
July | 0.00 | 0.358757E+11 | 0.00 | 0.00 | 0.399500E+10 | 0.00 | 0.00 | 0.00 | 3.95 |
August | 0.00 | 0.322221E+11 | 0.00 | 202003.39 | 0.417315E+10 | 0.00 | 71926698.50 | 0.00 | 3.95 |
September | 0.00 | 0.292550E+11 | 0.00 | 0.00 | 0.430340E+10 | 0.00 | 0.00 | 0.00 | 3.93 |
October | 0.162326E+10 | 0.195450E+11 | 0.00 | 9957819.13 | 0.346454E+10 | 0.00 | 0.862143E+10 | 0.00 | 4.49 |
November | 0.682716E+10 | 0.534681E+10 | 0.00 | 19810883.52 | 0.197000E+10 | 0.00 | 0.243594E+11 | 0.00 | 5.33 |
December | 0.141841E+11 | 0.347341E+10 | 0.00 | 16742810.69 | 0.177718E+10 | 0.00 | 0.277160E+11 | 0.00 | 4.97 |
Annual Sum or Average | 0.631831E+11 | 0.190832E+12 | 0.00 | 0.129406E+09 | 0.322572E+11 | 0.00 | 0.161702E+12 | 0.00 | 4.59 |
Minimum of Months | 0.00 | 0.853057E+09 | 0.00 | 0.00 | 0.108721E+10 | 0.00 | 0.00 | 0.00 | 3.93 |
Maximum of Months | 0.170405E+11 | 0.358757E+11 | 0.00 | 23130576.57 | 0.430340E+10 | 0.00 | 0.331802E+11 | 0.00 | 5.33 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138204E+11 | 0.142578E+10 | 0.00 | 25821965.27 | 0.521175E+09 | 0.00 | 0.363704E+11 | 0.00 | 5.02 |
February | 0.871453E+10 | 0.153853E+10 | 0.00 | 26912811.62 | 0.589234E+09 | 0.00 | 0.280444E+11 | 0.00 | 5.29 |
March | 0.812226E+10 | 0.322646E+10 | 0.00 | 29804908.13 | 0.803579E+09 | 0.00 | 0.286161E+11 | 0.00 | 5.26 |
April | 0.156216E+10 | 0.808732E+10 | 0.00 | 24024876.68 | 0.119230E+10 | 0.00 | 0.161351E+11 | 0.00 | 5.10 |
May | 0.00 | 0.267295E+11 | 0.00 | 0.00 | 0.255869E+10 | 0.00 | 0.00 | 0.00 | 3.98 |
June | 0.00 | 0.289444E+11 | 0.00 | 607524.49 | 0.245329E+10 | 0.00 | 0.121920E+09 | 0.00 | 4.01 |
July | 0.00 | 0.373049E+11 | 0.00 | 0.00 | 0.282236E+10 | 0.00 | 0.00 | 0.00 | 3.98 |
August | 0.00 | 0.335778E+11 | 0.00 | 234063.85 | 0.301500E+10 | 0.00 | 71841743.59 | 0.00 | 3.98 |
September | 0.00 | 0.305603E+11 | 0.00 | 0.00 | 0.314484E+10 | 0.00 | 0.00 | 0.00 | 3.96 |
October | 0.755935E+09 | 0.207139E+11 | 0.00 | 12189163.41 | 0.237811E+10 | 0.00 | 0.951649E+10 | 0.00 | 4.51 |
November | 0.516670E+10 | 0.621043E+10 | 0.00 | 25035448.44 | 0.113148E+10 | 0.00 | 0.260472E+11 | 0.00 | 5.34 |
December | 0.106785E+11 | 0.422775E+10 | 0.00 | 22781598.29 | 0.103203E+10 | 0.00 | 0.311959E+11 | 0.00 | 4.97 |
Annual Sum or Average | 0.488204E+11 | 0.202547E+12 | 0.00 | 0.167412E+09 | 0.216421E+11 | 0.00 | 0.176119E+12 | 0.00 | 4.61 |
Minimum of Months | 0.00 | 0.142578E+10 | 0.00 | 0.00 | 0.521175E+09 | 0.00 | 0.00 | 0.00 | 3.96 |
Maximum of Months | 0.138204E+11 | 0.373049E+11 | 0.00 | 29804908.13 | 0.314484E+10 | 0.00 | 0.363704E+11 | 0.00 | 5.34 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.223288E+10 | 0.00 | 99176506.78 | 0.00 | 0.00 | 0.455795E+11 | 0.00 | 16.05 |
February | 0.00 | 0.251984E+10 | 0.00 | 81877906.03 | 0.00 | 0.00 | 0.330184E+11 | 0.00 | 16.86 |
March | 0.00 | 0.463410E+10 | 0.00 | 85018763.48 | 0.00 | 0.00 | 0.333317E+11 | 0.00 | 16.88 |
April | 0.00 | 0.100781E+11 | 0.00 | 58754345.46 | 0.00 | 0.00 | 0.157436E+11 | 0.00 | 16.51 |
May | 0.00 | 0.316535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 |
June | 0.00 | 0.341230E+11 | 0.00 | 428287.07 | 0.00 | 0.00 | 72782830.64 | 0.00 | 13.25 |
July | 0.00 | 0.435483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 |
August | 0.00 | 0.395901E+11 | 0.00 | 236691.77 | 0.00 | 0.00 | 46606211.38 | 0.00 | 13.16 |
September | 0.00 | 0.361540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.09 |
October | 0.00 | 0.247096E+11 | 0.00 | 30465323.75 | 0.00 | 0.00 | 0.907216E+10 | 0.00 | 14.77 |
November | 0.00 | 0.782611E+10 | 0.00 | 80459703.63 | 0.00 | 0.00 | 0.286298E+11 | 0.00 | 17.37 |
December | 0.00 | 0.571743E+10 | 0.00 | 87099026.10 | 0.00 | 0.00 | 0.385403E+11 | 0.00 | 16.04 |
Annual Sum or Average | 0.00 | 0.242787E+12 | 0.00 | 0.523517E+09 | 0.00 | 0.00 | 0.204035E+12 | 0.00 | 15.02 |
Minimum of Months | 0.00 | 0.223288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.09 |
Maximum of Months | 0.00 | 0.435483E+11 | 0.00 | 99176506.78 | 0.00 | 0.00 | 0.455795E+11 | 0.00 | 17.37 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.510193E+10 | 0.140630E+09 | 0.00 | 509722.05 | 90286122.67 | 0.00 | 0.212327E+09 | 0.00 | 0.43 |
February | 0.371119E+10 | 0.254000E+09 | 0.00 | 551524.30 | 36524302.91 | 0.00 | 0.176899E+09 | 0.00 | 0.47 |
March | 0.360160E+10 | 0.468692E+09 | 0.00 | 896998.79 | 48227177.96 | 0.00 | 0.288467E+09 | 0.00 | 0.47 |
April | 0.118457E+10 | 0.139629E+10 | 0.00 | 2250509.41 | 27242170.91 | 0.00 | 0.709469E+09 | 0.00 | 0.51 |
May | 0.00 | 0.523444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.613016E+10 | 0.00 | 87928.93 | 0.00 | 0.00 | 15923761.37 | 0.00 | 0.61 |
July | 0.00 | 0.784059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.695964E+10 | 0.00 | 49696.30 | 0.00 | 0.00 | 9425935.90 | 0.00 | 0.60 |
September | 0.00 | 0.604112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.535850E+09 | 0.427038E+10 | 0.00 | 1984873.63 | 2913816.19 | 0.00 | 0.618476E+09 | 0.00 | 0.58 |
November | 0.271846E+10 | 0.112160E+10 | 0.00 | 1577325.59 | 17724886.71 | 0.00 | 0.606103E+09 | 0.00 | 0.51 |
December | 0.421779E+10 | 0.705231E+09 | 0.00 | 740765.69 | 35811228.71 | 0.00 | 0.243363E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.210714E+11 | 0.405628E+11 | 0.00 | 8649344.68 | 0.258730E+09 | 0.00 | 0.288045E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.140630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.510193E+10 | 0.784059E+10 | 0.00 | 2250509.41 | 90286122.67 | 0.00 | 0.709469E+09 | 0.00 | 0.61 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.216726E+12 | 0.384285E+10 | 0.101884E+12 | 0.358269E+12 | 0.290036E+12 |
February | 0.234804E+12 | 0.256594E+10 | 0.662011E+11 | 0.251859E+12 | 0.358905E+12 |
March | 0.282197E+12 | 0.212858E+10 | 0.546225E+11 | 0.225544E+12 | 0.444585E+12 |
April | 0.302461E+12 | -423078572.7 | -0.127784E+11 | 0.147634E+11 | 0.724895E+12 |
May | 0.308111E+12 | -0.548501E+10 | -0.162380E+12 | -0.445024E+12 | 0.126080E+13 |
June | 0.302457E+12 | -0.588358E+10 | -0.179938E+12 | -0.490491E+12 | 0.128260E+13 |
July | 0.315542E+12 | -0.743244E+10 | -0.231263E+12 | -0.630071E+12 | 0.142380E+13 |
August | 0.293641E+12 | -0.676770E+10 | -0.206056E+12 | -0.555041E+12 | 0.138722E+13 |
September | 0.250322E+12 | -0.619111E+10 | -0.178153E+12 | -0.480509E+12 | 0.129951E+13 |
October | 0.263128E+12 | -0.353383E+10 | -0.107391E+12 | -0.258046E+12 | 0.109653E+13 |
November | 0.181803E+12 | 0.105955E+10 | 0.213633E+11 | 0.143317E+12 | 0.572593E+12 |
December | 0.190752E+12 | 0.255898E+10 | 0.684382E+11 | 0.260481E+12 | 0.430658E+12 |
Annual Sum or Average | 0.314194E+13 | -0.235609E+11 | -0.765450E+12 | -0.160495E+13 | 0.105721E+14 |
Minimum of Months | 0.181803E+12 | -0.743244E+10 | -0.231263E+12 | -0.630071E+12 | 0.290036E+12 |
Maximum of Months | 0.315542E+12 | 0.384285E+10 | 0.101884E+12 | 0.358269E+12 | 0.142380E+13 |