Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2024-07-03 12:21:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 9920.60 | 874.42 | 874.42 |
Net Site Energy | 9920.60 | 874.42 | 874.42 |
Total Source Energy | 22586.36 | 1990.81 | 1990.81 |
Net Source Energy | 22586.36 | 1990.81 | 1990.81 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 353.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1203.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 545.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 591.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 81.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 110.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.78 | 2451.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5680.48 | 4240.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 353.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1203.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 545.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 591.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 81.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 110.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.78 | 2451.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 353.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1203.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 545.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 591.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 81.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 110.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.78 | 2451.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 204.84 | 216.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 230.65 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 500.69 | 373.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 204.84 | 216.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 230.65 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 500.69 | 373.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5680.476 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5680.476 | 100.00 |
Total On-Site and Utility Electric Sources | 5680.476 | 100.00 |
Total Electricity End Uses | 5680.476 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 582.81 | 58.48 |
Air to Air Heat Recovery for Heating | 413.82 | 41.52 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 996.63 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 11.00 |
Time Setpoint Not Met During Occupied Cooling | 74.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7981.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.7179 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.2862 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8577 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8577 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.7179 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.2862 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8577 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8577 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.7137 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-JUL-18:10 | 01-FEB-18:30 | - | - | - | - | - | - | - | - | - | - | 29-MAR-20:19 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 168606.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 36642.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 77265.07 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 28142.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 29340.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4079.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4751.03 | 238093.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1689.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 358783.06 | 342342.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 168606.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 36642.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 47590.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1023.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 26968.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 29340.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4079.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4751.03 | 238093.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 791.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 669.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1119.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3810.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1728.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.66 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2576.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1872.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 256.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 350.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.17 | 2657.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 139.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 17990.07 | 4596.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 98.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 335.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 152.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 165.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 30.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 234.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1585.69 | 405.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 98.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 335.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 152.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 165.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 30.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 234.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1585.69 | 405.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
BASEMENT VAV BOX COMPONENT | 2.23 | 0.675019 | 0.574000 | 1.28 | 1.00 | 0.500000 | 0.000564 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.302126 | 0.169163 | 0.393000 | 0.118735 | 0.468600 | 0.500000 | 0.002252 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.227175 | 0.260520 | 0.606000 | 0.137668 | 0.694721 | 0.500000 | 0.001462 |
MECH_FLR_1 VAV BOX COMPONENT | 0.197717 | 0.632991 | 0.010000 | 0.001977 | 1.00 | 0.500000 | 0.000602 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.110151 | 0.655522 | 0.787000 | 0.086689 | 1.00 | 0.500000 | 0.000581 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.37 | 0.017620 | 0.010000 | 0.033750 | 0.300000 | 0.500000 | 0.021623 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.36 | 0.105569 | 0.744000 | 1.01 | 0.744000 | 0.500000 | 0.003609 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.61 | 0.216088 | 0.616000 | 2.84 | 0.616000 | 0.500000 | 0.001763 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.18 | 1.00 | 0.606000 | 0.712653 | 1.00 | 0.500000 | 0.000377 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.20 | 0.114756 | 0.809000 | 1.78 | 0.809000 | 0.500000 | 0.003320 |
DINING_FLR_6 VAV BOX COMPONENT | 2.31 | 0.109301 | 0.771000 | 1.78 | 0.771000 | 0.500000 | 0.003486 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.23 | 0.063488 | 0.247000 | 0.550837 | 0.300000 | 0.500000 | 0.010794 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.676849 | 0.463972 | 0.278000 | 0.188164 | 1.00 | 0.500000 | 0.000821 |
Design Size Nominal Capacity [W] | |
BASEMENT VAV BOX REHEAT COIL | 35368.45 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3275.19 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 3797.43 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1920.24 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 2391.23 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 2489.78 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 27976.39 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 78384.62 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5530.61 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5540.37 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 31862.63 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 32058.98 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5510.49 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5520.26 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 19657.80 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1709.88 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1713.72 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8208.50 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 49144.59 |
DINING_FLR_6 VAV BOX REHEAT COIL | 49173.51 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 15194.28 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7593.93 |
FLR_3_DOAS HEATING COIL | 16512.40 |
VAV WITH REHEAT HEATING COIL | 168279.36 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.929491 | 0.000292 |
ROOM_2_FLR_3 FAN COIL | 0.918884 | 0.000288 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.25 | 0.001610 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.62 | 0.001843 |
ROOM_5_FLR_3 FAN COIL | 0.839304 | 0.000264 |
ROOM_6_FLR_3 FAN COIL | 0.831998 | 0.000262 |
ROOM_1_FLR_6 FAN COIL | 0.245474 | 0.000077 |
ROOM_2_FLR_6 FAN COIL | 0.242410 | 0.000076 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.10 | 0.000350 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 0.929491 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 0.918884 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 5.25 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 5.62 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 0.839304 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 0.831998 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.245474 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.242410 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.10 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008642 | 12.80 | 0.008500 | 0.000292 | 0.929491 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008644 | 12.80 | 0.008500 | 0.000288 | 0.918884 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008557 | 12.80 | 0.008500 | 0.001610 | 5.25 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008811 | 12.80 | 0.008500 | 0.001843 | 5.62 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008658 | 12.80 | 0.008500 | 0.000264 | 0.839304 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008660 | 12.80 | 0.008500 | 0.000262 | 0.831998 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008635 | 12.80 | 0.008500 | 0.000077 | 0.245474 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008637 | 12.80 | 0.008500 | 0.000076 | 0.242410 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008715 | 12.80 | 0.008500 | 0.000350 | 1.10 | |
FLR_3_DOAS COOLING COIL | 34.40 | 6.70 | 0.014473 | 11.91 | 0.008500 | 0.002607 | 2.05 | 91161.11 |
VAV WITH REHEAT COOLING COIL | 28.63 | 6.70 | 0.011863 | 10.92 | 0.008500 | 0.018511 | 20.91 | 647250.16 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 13.03 | 10.53 | 21.02 | 10.53 | 20.91 | 20.91 | 0.300000 | 0.503842 | 20.91 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 20.91 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 9.33 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002607 | 0.000183 |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.018511 | 0.000026 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 20.91 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.026182 | 4232.43 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1 | 0.026182 | 3.14 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.026182 | 2930.26 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.026182 | 915466.31 | 916054.30 | 104.43 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.718 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.098 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.286 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.976 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13293.583 | 6.718 | 124.824 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13293.583 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 406.155 | 4.286 | 199.096 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 406.155 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9589 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8756 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.56372661E-17 | 0.35603042E-16 | -0.14834456E-09 | -0.22354951E-17 |
29 | 8 | 0.21681598E-07 | 0.12895413E-12 | 0.37576420E-03 | -0.24652724E-09 |
30 | 7 | -0.12181032E-01 | 0.67087143E-08 | -0.22998674E-01 | 0.13850277E-03 |
31 | 6 | 0.40370585 | 0.23395349E-05 | 0.47069069 | -0.47283774E-02 |
32 | 5 | -5.1745154 | 0.87537405E-04 | -4.4305073 | 0.62984858E-01 |
33 | 4 | 32.931872 | 0.71743813E-03 | 21.398312 | -0.42118042 |
34 | 3 | -111.07522 | 0.15662534E-02 | -55.540939 | 1.5130129 |
35 | 2 | 196.98158 | 0.88235367E-03 | 77.798628 | -2.8983416 |
36 | 1 | -171.10930 | 0.94326468E-04 | -55.232514 | 2.7446195 |
37 | 0 | 57.057407 | 0.53780718E-06 | 15.562302 | |
38 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
39 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
40 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
41 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
42 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
43 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
44 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
45 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
46 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
47 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
48 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
49 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
50 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
51 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
52 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
53 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
54 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
55 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
56 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
57 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
58 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
59 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
60 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
61 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
62 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
63 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
64 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
65 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
66 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
67 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
68 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
69 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
70 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
71 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
72 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
73 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
74 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
75 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
76 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
77 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
78 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
79 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
80 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
81 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
82 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
83 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
84 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
85 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
86 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
87 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
88 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
89 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
90 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
91 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
92 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
93 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.43_SHGC_0.248 | 37 | 1 | VerySmooth | 2.443 | 2.443 | 1.000 | 0.249 | ||
2 | RESWINDOW_U_0.43_SHGC_0.248 | 38 | 1 | VerySmooth | 2.443 | 2.443 | 1.000 | 0.249 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.91147E-002 | 0.15938 | 0.62162 | 0.62162 | 0.27280 | 0.15674 | 0.22697 | 0.00000 | 0.84000 | 0.84000 | 0.12243 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.91147E-002 | 0.15938 | 0.62162 | 0.62162 | 0.27280 | 0.15674 | 0.22697 | 0.00000 | 0.84000 | 0.84000 | 0.12243 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.7749E-002 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.0000E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1093 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.3218E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.1393E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.5745E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.8929E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.5818E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1071 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.9122E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1194 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.3048E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.8370E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.2591E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2502E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3131E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.2924E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3032E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7730E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.8813E-003 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7162E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.8597E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8489E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0072E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.2924E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3032E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7730E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.8813E-003 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7162E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.8597E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8489E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0072E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 29641.65103 | 29641.65103 | 2.23382 | 2.23382 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 28.93750 | 1.44633E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1410.52208 | 1410.52208 | 6.27084E-002 | 0.85446 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4008.56289 | 4008.56289 | 0.30213 | 0.30213 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2571.27619 | 2571.27619 | 0.11431 | 0.11431 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3014.13222 | 3014.13222 | 0.22717 | 0.22717 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12000 | 1.44691E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 861.57404 | 861.57404 | 3.83030E-002 | 9.17347E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2623.86714 | 2623.86714 | 0.19772 | 0.19772 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:10:00 | 29.50750 | 1.44643E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1565.88366 | 1565.88366 | 6.96144E-002 | 6.96144E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1461.78213 | 1461.78213 | 0.11015 | 0.11015 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 31.88250 | 1.44687E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1049.27106 | 1049.27106 | 4.66474E-002 | 5.77652E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44783.73239 | 44783.73239 | 3.37497 | 3.37497 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 33.92500 | 1.44724E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2030.34785 | 2030.34785 | 9.02617E-002 | 9.02617E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18071.53411 | 18071.53411 | 1.36321 | 1.36321 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6523.77414 | 6523.77414 | 0.29002 | 0.67639 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 61188.91179 | 61188.91179 | 4.61311 | 4.61311 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 15318.65223 | 15318.65223 | 0.68102 | 1.89399 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9152.92132 | 9152.92132 | 0.92949 | 0.92949 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5530.66193 | 5530.66193 | 0.24732 | 0.24732 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9048.46900 | 9048.46900 | 0.91888 | 0.91888 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5540.42184 | 5540.42184 | 0.24775 | 0.24775 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 51728.97663 | 51728.97663 | 5.25281 | 5.25281 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 31862.78563 | 31862.78563 | 1.42484 | 1.42484 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 55346.95984 | 55346.95984 | 5.62064 | 5.62064 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 32059.13189 | 32059.13189 | 1.43362 | 1.43362 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8264.81559 | 8264.81559 | 0.83930 | 0.83930 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5510.54381 | 5510.54381 | 0.24642 | 0.24642 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8192.86989 | 8192.86989 | 0.83200 | 0.83200 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.26500 | 1.44675E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5520.30932 | 5520.30932 | 0.24685 | 0.24685 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 15605.18360 | 15605.18360 | 1.17600 | 1.17600 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9054.02165 | 9054.02165 | 0.40252 | 0.47476 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2417.24234 | 2417.24234 | 0.24547 | 0.24547 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1709.89669 | 1709.89669 | 7.64622E-002 | 7.64622E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2387.07031 | 2387.07031 | 0.24241 | 0.24241 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1713.73701 | 1713.73701 | 7.66339E-002 | 7.66339E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 10787.50782 | 10787.50782 | 1.09551 | 1.09551 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8208.55756 | 8208.55756 | 0.36707 | 0.36707 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29186.86141 | 29186.86141 | 2.20227 | 2.20227 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5858.22053 | 5858.22053 | 0.26044 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30643.92004 | 30643.92004 | 2.31217 | 2.31217 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5991.24980 | 5991.24980 | 0.26635 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29514.52739 | 29514.52739 | 2.23011 | 2.23011 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.54500 | 1.44717E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2420.34506 | 2420.34506 | 0.10759 | 0.36735 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -6.30000 | 2.29779E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 8981.69099 | 8981.69099 | 0.67685 | 0.67685 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 34.40000 | 1.44733E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6192.53192 | 6192.53192 | 0.27530 | 0.27530 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -6.30000 | 2.29779E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 51689.19 | 15.34983 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 55039.41 | 4.36697 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 386181.19 | 20.90515 | 20.90515 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 196989.16 | 7.34152 | 7.34152 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23382 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.67502 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57400 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28221 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.64429E-004 |
8 | Coil:Heating:Electric | BASEMENT VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 35368.45457 |
9 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.30213 |
10 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16916 |
11 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.39300 |
12 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11874 |
13 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46860 |
14 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.25227E-003 |
16 | Coil:Heating:Electric | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3275.19374 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22717 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26052 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.60600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13767 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69472 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46246E-003 |
24 | Coil:Heating:Electric | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3797.42955 |
25 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.19772 |
26 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.63299 |
27 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
28 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.97717E-003 |
29 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
30 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.01905E-004 |
32 | Coil:Heating:Electric | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 1920.24025 |
33 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.11015 |
34 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.65552 |
35 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.78700 |
36 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.66890E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.81216E-004 |
40 | Coil:Heating:Electric | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2391.22698 |
41 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.37497 |
42 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.76198E-002 |
43 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
44 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.37497E-002 |
45 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16234E-002 |
48 | Coil:Heating:Electric | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2489.77562 |
49 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.36321 |
50 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10557 |
51 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.74400 |
52 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01423 |
53 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74400 |
54 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.60901E-003 |
56 | Coil:Heating:Electric | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27976.39145 |
57 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.61311 |
58 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21609 |
59 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.61600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84167 |
61 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61600 |
62 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.76317E-003 |
64 | Coil:Heating:Electric | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 78384.62087 |
65 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
66 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.92949 |
67 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.92949 |
68 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.91634E-004 |
69 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70400 |
70 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
71 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64237E-003 |
72 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
73 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
74 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.91634E-004 |
75 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.92949 |
76 | Coil:Heating:Electric | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 5530.60758 |
77 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
78 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.91888 |
79 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.91888 |
80 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.88451E-004 |
81 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70399 |
82 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
83 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64424E-003 |
84 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
85 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
86 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.88451E-004 |
87 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.91888 |
88 | Coil:Heating:Electric | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 5540.36741 |
89 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
90 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.25281 |
91 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 5.25281 |
92 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.61035E-003 |
93 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70462 |
94 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
95 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55694E-003 |
96 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
97 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
98 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.61035E-003 |
99 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.25281 |
100 | Coil:Heating:Electric | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 31862.63289 |
101 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
102 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.62064 |
103 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 5.62064 |
104 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.84336E-003 |
105 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70368 |
106 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
107 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.81085E-003 |
108 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
109 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
110 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.84336E-003 |
111 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.62064 |
112 | Coil:Heating:Electric | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 32058.97831 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.83930 |
115 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.83930 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.64450E-004 |
117 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70397 |
118 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
119 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65811E-003 |
120 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
121 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
122 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.64450E-004 |
123 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.83930 |
124 | Coil:Heating:Electric | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 5510.48963 |
125 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
126 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.83200 |
127 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.83200 |
128 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.62249E-004 |
129 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70397 |
130 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
131 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65955E-003 |
132 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
133 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
134 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.62249E-004 |
135 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.83200 |
136 | Coil:Heating:Electric | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 5520.25506 |
137 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17600 |
138 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
139 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.60600 |
140 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71265 |
141 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
142 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
143 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.77498E-004 |
144 | Coil:Heating:Electric | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19657.80339 |
145 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24547 |
147 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.24547 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.68657E-005 |
149 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70401 |
150 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63497E-003 |
152 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.68657E-005 |
155 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24547 |
156 | Coil:Heating:Electric | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 1709.88065 |
157 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
158 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24241 |
159 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.24241 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.59385E-005 |
161 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70401 |
162 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
163 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63654E-003 |
164 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
165 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
166 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.59385E-005 |
167 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24241 |
168 | Coil:Heating:Electric | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 1713.72094 |
169 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
170 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.09551 |
171 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.09551 |
172 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.50462E-004 |
173 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70374 |
174 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
175 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71539E-003 |
176 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
177 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
178 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.50462E-004 |
179 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.09551 |
180 | Coil:Heating:Electric | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 8208.49595 |
181 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.20227 |
182 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11476 |
183 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.80900 |
184 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78164 |
185 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80900 |
186 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.32010E-003 |
188 | Coil:Heating:Electric | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 49144.58517 |
189 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31217 |
190 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10930 |
191 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.77100 |
192 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78268 |
193 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77100 |
194 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
195 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.48578E-003 |
196 | Coil:Heating:Electric | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 49173.51353 |
197 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23011 |
198 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.34875E-002 |
199 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24700 |
200 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55084 |
201 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
202 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07939E-002 |
204 | Coil:Heating:Electric | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15194.28028 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67685 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.46397 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27800 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18816 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.21170E-004 |
212 | Coil:Heating:Electric | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7593.93351 |
213 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
214 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
215 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
216 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
217 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
218 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
219 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
221 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.03033 |
222 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.53290 |
223 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.01966 |
224 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.53290 |
225 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 20.90515 |
226 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.90515 |
227 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50384 |
229 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
230 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.90515 |
231 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
232 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
233 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
234 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 34.40000 |
235 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
236 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.90668 |
237 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.44733E-002 |
238 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
239 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 91161.10877 |
240 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.60720E-003 |
241 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
242 | Coil:Heating:Electric | FLR_3_DOAS HEATING COIL | Design Size Nominal Capacity [W] | 16512.40431 |
243 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
244 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.60720E-003 |
245 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.82645E-004 |
246 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.90515 |
247 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 9.32920 |
248 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.63468 |
249 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92058 |
251 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.18626E-002 |
252 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
253 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 647250.16479 |
254 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.85113E-002 |
255 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 20.90515 |
256 | Coil:Heating:Electric | VAV WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 168279.35992 |
257 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 20.90515 |
258 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.85113E-002 |
259 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.57244E-005 |
260 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.61822E-002 |
261 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4232.43226 |
262 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.61822E-002 |
263 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.14187 |
264 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.61822E-002 |
265 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2930.25560 |
266 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.61822E-002 |
267 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 915466.31092 |
268 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 916054.30000 |
269 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 104.43019 |
270 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
271 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
272 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
273 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
274 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 15377.96 | 13028.22 | 2349.74 | 0.85 | 3414.17 | 34.63 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 15207.66 | 12881.25 | 2326.41 | 0.85 | 3374.09 | 34.22 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 85530.44 | 73174.28 | 12356.16 | 0.86 | 19595.60 | 198.75 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 95838.49 | 79744.84 | 16093.65 | 0.83 | 20196.74 | 204.85 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 13925.67 | 11777.22 | 2148.45 | 0.85 | 3074.45 | 31.18 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 13808.05 | 11675.89 | 2132.17 | 0.85 | 3046.94 | 30.90 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4055.75 | 3438.88 | 616.87 | 0.85 | 902.86 | 9.16 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4006.28 | 3396.34 | 609.94 | 0.85 | 891.34 | 9.04 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 18366.47 | 15436.03 | 2930.44 | 0.84 | 3980.21 | 40.37 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 64827.35 | 41208.20 | 23619.15 | 0.64 | 8819.06 | 89.45 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 607517.48 | 397194.05 | 210323.44 | 0.65 | 91676.19 | 929.83 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.43_SHGC_0.248 | N/A | 2.443 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.7088078348E-002 | 2.2194512748E-002 | Pass | Pass | 5.4558147200E-003 | 1.7491514422E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5787681117E-005 | 5.3294577564E-005 | Pass | Pass | 1.1423747263 | 12.1129084895 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6882528395E-002 | 2.6723914224E-002 | Pass | Pass | 1.0856806948E-002 | 2.8022751104E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5381449549E-002 | 1.6854069460E-002 | Pass | Pass | 5.4253461012E-003 | 1.7071800216E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.2298435453E-006 | 1.4301541098E-005 | Pass | Pass | 2.1087440729E-002 | 3.3878958585E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.8841938580E-004 | 4.3004711442E-004 | Pass | Pass | 2.0851394486E-002 | 6.0930055610E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.1240001686E-002 | 3.5937106963E-002 | Pass | Pass | 2.2581691701E-002 | 6.3902071283E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.8868806428E-002 | 4.6882735125E-002 | Pass | Pass | 1.1761325724E-002 | 2.6113550039E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.0140598892E-002 | 0.1551084865 | Pass | Pass | 0.1305807982 | 0.5251572891 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.1766542604E-002 | 0.1612255886 | Pass | Pass | 0.1289875122 | 0.5234806412 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.4867493781E-002 | 4.5243403448E-002 | Pass | Pass | 7.2495670612E-003 | 7.3277104697E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.0163384970E-002 | 0.1139729225 | Pass | Pass | 0.3609337410 | 2.2360194829 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.8669704572E-002 | 0.1507343022 | Pass | Pass | 0.1361778265 | 0.5503648626 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.0298286742E-002 | 0.1567059033 | Pass | Pass | 0.1340316358 | 0.5465533668 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.4267083456E-005 | 2.8936060110E-005 | Pass | Pass | 4.1410488862E-002 | 9.9109147244E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.1160072202E-002 | 0.2244060292 | Pass | Pass | 9.5422238702E-002 | 0.3505760012 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.3027093427E-002 | 0.2313354231 | Pass | Pass | 9.4097078392E-002 | 0.3461246514 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.5219945331E-002 | 0.1053819407 | Pass | Pass | 0.1112293883 | 0.3242421675 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.8735459502E-002 | 9.6856937167E-002 | Pass | Pass | 1.0359965804E-002 | 2.3002034792E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.0496747585E-002 | 9.3346390163E-002 | Pass | Pass | 9.0039987744E-003 | 2.0596401520E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.0936195568E-003 | 1.9664007989E-003 | Pass | Pass | 2.2410476146E-002 | 4.4382736622E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.7338207504E-003 | 6.7368600357E-003 | Pass | Pass | 2.5882593759E-002 | 4.2931096452E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3007.13 | 22.69 | 559.08 | 2194.39 | 6193.09 | 11976.37 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.443 | 0.249 | 0.274 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.443 | 0.249 | 0.274 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.443 | 0.249 | 0.274 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.443 | 0.249 | 0.274 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.443 | 0.249 | 0.274 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.443 | 0.249 | 0.274 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.443 | 0.249 | 0.274 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.443 | 0.249 | 0.274 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.443 | 0.249 | 0.274 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.443 | 0.249 | 0.274 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.443 | 0.249 | 0.274 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.443 | 0.249 | 0.274 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.443 | 0.249 | 0.274 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.443 | 0.249 | 0.274 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.443 | 0.249 | 0.274 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.443 | 0.249 | 0.274 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.443 | 0.249 | 0.274 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.43_SHGC_0.248 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.443 | 0.249 | 0.274 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.443 | 0.249 | 0.274 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.443 | 0.249 | 0.274 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.443 | 0.249 | 0.274 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.443 | 0.249 | 0.274 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.443 | 0.249 | 0.274 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.43_SHGC_0.248 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.443 | 0.249 | 0.274 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.443 | 0.249 | 0.274 | |||||||||||||||||
North Total or Average | 432.95 | 2.443 | 0.249 | 0.274 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.443 | 0.249 | 0.274 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.7179 | 1978.83 | 13293.58 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 122.93 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.2862 | 94.76 | 406.16 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 2.31 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.29 | 0.0000 | Y | 12.90 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.53 | 0.0000 | Y | 92.21 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.78 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.79 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 6.96 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.27 | 0.0000 | Y | 28.40 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.27 | 0.0000 | Y | 28.40 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8577 | 11345.29 | 66457.67 | 366.16 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.77 | 83.77 | 194.02 | |
Exterior Lighting Total | 12338.45 | 194.02 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 916054.30 | 2.96 | 916054.30 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10197.21 | 15377.96 | 13028.22 | 2349.74 | 0.85 | - | 3414.17 | 34.63 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10085.92 | 15207.66 | 12881.25 | 2326.41 | 0.85 | - | 3374.09 | 34.22 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 56307.11 | 85530.44 | 73174.28 | 12356.16 | 0.86 | - | 19595.60 | 198.75 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 64454.46 | 95838.49 | 79744.84 | 16093.65 | 0.83 | - | 20196.74 | 204.85 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9246.73 | 13925.67 | 11777.22 | 2148.45 | 0.85 | - | 3074.45 | 31.18 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9169.77 | 13808.05 | 11675.89 | 2132.17 | 0.85 | - | 3046.94 | 30.90 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2687.67 | 4055.75 | 3438.88 | 616.87 | 0.85 | - | 902.86 | 9.16 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2655.25 | 4006.28 | 3396.34 | 609.94 | 0.85 | - | 891.34 | 9.04 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 12254.21 | 18366.47 | 15436.03 | 2930.44 | 0.84 | - | 3980.21 | 40.37 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 91161.11 | 64827.35 | 41208.20 | 23619.15 | 0.64 | - | 8819.06 | 89.45 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 647250.16 | 607517.48 | 397194.05 | 210323.44 | 0.65 | - | 91676.19 | 929.83 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | 35368.45 | 1.00 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3275.19 | 1.00 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3797.43 | 1.00 | |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 1920.24 | 1.00 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2391.23 | 1.00 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2489.78 | 1.00 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 27976.39 | 1.00 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 78384.62 | 1.00 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 5530.61 | 1.00 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 5540.37 | 1.00 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 31862.63 | 1.00 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 32058.98 | 1.00 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 5510.49 | 1.00 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 5520.26 | 1.00 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19657.80 | 1.00 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 1709.88 | 1.00 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 1713.72 | 1.00 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 8208.50 | 1.00 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 49144.59 | 1.00 | |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 49173.51 | 1.00 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15194.28 | 1.00 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7593.93 | 1.00 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | 16512.40 | 1.00 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | 168279.36 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.93 | 654.02 | 703.64 | 1.00 | 1.22 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.92 | 646.56 | 703.64 | 1.00 | 1.22 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 5.25 | 3696.06 | 703.64 | 1.00 | 0.97 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 5.62 | 3954.89 | 703.64 | 1.00 | 0.96 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.84 | 590.56 | 703.64 | 1.00 | 1.24 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.83 | 585.42 | 703.64 | 1.00 | 1.25 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 172.72 | 703.64 | 1.00 | 1.87 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.24 | 170.57 | 703.64 | 1.00 | 1.88 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.10 | 770.84 | 703.64 | 1.00 | 1.18 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 20.91 | 46840.89 | 2240.64 | 1.00 | 1.11 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.026182 | 4232.43 | 161652.92 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.026182 | 2930.26 | 111917.77 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 29641.65 | 29641.65 | 14.98 | 2.234 | 2.234 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00931 | 28.94 | 0.01446 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4008.56 | 4008.56 | 59.77 | 0.302 | 0.302 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00918 | 34.40 | 0.01447 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3014.13 | 3014.13 | 38.81 | 0.227 | 0.227 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.00 | 24.00 | 0.00948 | 32.12 | 0.01447 | 0.092 | 0.00 |
MECH_FLR_1 | 2623.87 | 2623.87 | 15.98 | 0.198 | 0.198 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:10:00 | 24.00 | 24.00 | 0.00884 | 29.51 | 0.01446 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1461.78 | 1461.78 | 15.43 | 0.110 | 0.110 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00893 | 31.88 | 0.01447 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44783.73 | 44783.73 | 573.86 | 3.375 | 3.375 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00855 | 33.92 | 0.01447 | 0.000 | 0.00 |
CAFE_FLR_1 | 18071.53 | 18071.53 | 95.69 | 1.363 | 1.363 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.01031 | 34.40 | 0.01447 | 0.676 | 0.00 |
LOBBY_FLR_1 | 61188.91 | 61188.91 | 46.77 | 4.613 | 4.613 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.99 | 0.01009 | 34.40 | 0.01447 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9152.92 | 9152.92 | 234.56 | 0.929 | 0.929 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00864 | 32.91 | 0.01447 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9048.47 | 9048.47 | 231.91 | 0.919 | 0.919 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00864 | 32.75 | 0.01447 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 51728.98 | 51728.98 | 2109.33 | 5.253 | 5.253 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00856 | 34.40 | 0.01447 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 55346.96 | 55346.96 | 2256.25 | 5.621 | 5.621 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 21.11 | 21.11 | 0.00881 | 34.02 | 0.01447 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8264.82 | 8264.82 | 211.80 | 0.839 | 0.839 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 21.11 | 21.11 | 0.00866 | 31.50 | 0.01447 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8192.87 | 8192.87 | 209.98 | 0.832 | 0.832 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00866 | 31.26 | 0.01447 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 15605.18 | 15605.18 | 40.07 | 1.176 | 1.176 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00977 | 34.30 | 0.01447 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2417.24 | 2417.24 | 61.95 | 0.245 | 0.245 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00863 | 32.91 | 0.01447 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2387.07 | 2387.07 | 61.18 | 0.242 | 0.242 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00864 | 32.91 | 0.01447 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10787.51 | 10787.51 | 439.76 | 1.096 | 1.096 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00872 | 34.40 | 0.01447 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29186.86 | 29186.86 | 88.00 | 2.202 | 2.202 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01045 | 34.40 | 0.01447 | 1.188 | 0.00 |
DINING_FLR_6 | 30643.92 | 30643.92 | 92.40 | 2.312 | 2.312 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01035 | 34.40 | 0.01447 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29514.53 | 29514.53 | 285.70 | 2.230 | 2.230 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01015 | 33.55 | 0.01447 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 8981.69 | 8981.69 | 21.79 | 0.677 | 0.677 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00910 | 34.40 | 0.01447 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1410.52 | 1410.52 | 0.71 | 0.063 | 0.854 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00796 | -6.30 | 0.00230 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2571.28 | 2571.28 | 38.34 | 0.114 | 0.114 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00777 | -6.30 | 0.00230 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 861.57 | 861.57 | 11.09 | 0.038 | 0.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00774 | -6.30 | 0.00230 | 0.092 | 0.00 |
MECH_FLR_1 | 1565.88 | 1565.88 | 9.53 | 0.070 | 0.070 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00766 | -6.30 | 0.00230 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1049.27 | 1049.27 | 11.07 | 0.047 | 0.058 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00771 | -6.30 | 0.00230 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2030.35 | 2030.35 | 26.02 | 0.090 | 0.090 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00764 | -6.30 | 0.00230 | 0.000 | 0.00 |
CAFE_FLR_1 | 6523.77 | 6523.77 | 34.54 | 0.290 | 0.676 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00780 | -6.30 | 0.00230 | 0.676 | 0.00 |
LOBBY_FLR_1 | 15318.65 | 15318.65 | 11.71 | 0.681 | 1.894 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5530.66 | 5530.66 | 141.73 | 0.247 | 0.247 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00775 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5540.42 | 5540.42 | 142.00 | 0.248 | 0.248 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00775 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 31862.79 | 31862.79 | 1299.26 | 1.425 | 1.425 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00777 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 32059.13 | 32059.13 | 1306.91 | 1.434 | 1.434 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00777 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5510.54 | 5510.54 | 141.22 | 0.246 | 0.246 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00775 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5520.31 | 5520.31 | 141.48 | 0.247 | 0.247 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00775 | -6.30 | 0.00230 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9054.02 | 9054.02 | 23.25 | 0.403 | 0.475 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00781 | -6.30 | 0.00230 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1709.90 | 1709.90 | 43.82 | 0.076 | 0.076 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00780 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1713.74 | 1713.74 | 43.92 | 0.077 | 0.077 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00780 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8208.56 | 8208.56 | 334.63 | 0.367 | 0.367 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00781 | -6.30 | 0.00230 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5858.22 | 5858.22 | 17.66 | 0.260 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00785 | -6.30 | 0.00230 | 1.188 | 0.00 |
DINING_FLR_6 | 5991.25 | 5991.25 | 18.06 | 0.266 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00786 | -6.30 | 0.00230 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2420.35 | 2420.35 | 23.43 | 0.108 | 0.367 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00714 | -6.30 | 0.00230 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6192.53 | 6192.53 | 15.03 | 0.275 | 0.275 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00788 | -6.30 | 0.00230 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 15.35 | 2.05 | 4.37 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 20.91 | 20.91 | 7.34 | 7.34 | 20.9052 | 10.5329 | 20.9052 | 0.5038 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 35368.455 | 35368.455 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 35368.45 | 23569.37 | 0.854459 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00795846 | 49.6068 | 1410.52 | 0.00 | -999.00 | -999.00 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3275.194 | 3275.194 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 3275.19 | 3153.11 | 0.114310 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00776905 | 48.4417 | 2571.28 | 0.00 | -999.00 | -999.00 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 3797.430 | 3797.430 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 3797.43 | 2530.41 | 0.091735 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00773558 | 48.2351 | 861.57 | 0.00 | -999.00 | -999.00 |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1920.240 | 1920.240 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1920.24 | 1920.24 | 0.069614 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00766087 | 47.7751 | 1565.88 | 0.00 | -999.00 | -999.00 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 2391.227 | 2391.227 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 2391.23 | 1593.39 | 0.057765 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00770558 | 48.0504 | 1049.27 | 0.00 | -999.00 | -999.00 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 2489.776 | 2489.776 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2489.78 | 2489.78 | 0.090262 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00764398 | 47.6714 | 2030.35 | 0.00 | -999.00 | -999.00 |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 27976.391 | 27976.391 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 27976.39 | 18657.50 | 0.676389 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00779772 | 48.6181 | 6523.77 | 0.00 | -999.00 | -999.00 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 78384.621 | 78384.621 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 78384.62 | 52243.77 | 1.893991 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00775575 | 48.3594 | 15318.65 | 0.00 | -999.00 | -999.00 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10197.212 | -999.000 | 0.929491 | 0.00029163 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 10197.21 | 9868.92 | 0.929491 | 21.70 | 15.32 | 0.00864237 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00864237 | 53.4477 | 9152.92 | 0.00 | 10579.43 | 10579.43 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5530.608 | 5530.608 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5530.61 | 5352.56 | 0.247317 | 21.70 | 15.32 | 0.00864237 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00775290 | 48.0139 | 5530.66 | 0.00 | -999.00 | -999.00 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10085.917 | -999.000 | 0.918884 | 0.00028845 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 10085.92 | 9757.08 | 0.918884 | 21.70 | 15.32 | 0.00864424 | 12.80 | 11.77 | 0.00850000 | 32.75 | 0.01447025 | 23.10 | 0.0000 | 21.11 | 0.00864424 | 53.4592 | 9048.47 | 0.00 | 10463.83 | 10463.83 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5540.367 | 5540.367 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5540.37 | 5359.73 | 0.247753 | 21.70 | 15.32 | 0.00864424 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00775333 | 48.0165 | 5540.42 | 0.00 | -999.00 | -999.00 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 56307.114 | -999.000 | 5.252805 | 0.00161035 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 56307.11 | 55567.87 | 5.252805 | 21.70 | 15.25 | 0.00855694 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00855694 | 52.9249 | 51728.98 | 0.00 | 58444.65 | 58444.65 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 31862.633 | 31862.633 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 31862.63 | 31444.32 | 1.424845 | 21.70 | 15.25 | 0.00855694 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00777183 | 48.1290 | 31862.79 | 0.00 | -999.00 | -999.00 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 64454.464 | -999.000 | 5.620641 | 0.00184336 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | 7/21 15:40:00 | 64454.46 | 60089.97 | 5.620641 | 21.70 | 15.47 | 0.00881085 | 12.80 | 11.77 | 0.00850000 | 34.02 | 0.01447257 | 23.44 | 0.0000 | 21.11 | 0.00881085 | 54.4756 | 55346.96 | 0.00 | 66826.12 | 64233.05 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 32058.978 | 32058.978 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 32058.98 | 29888.12 | 1.433625 | 21.70 | 15.47 | 0.00881085 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00777311 | 48.1369 | 32059.13 | 0.00 | -999.00 | -999.00 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9246.726 | -999.000 | 0.839304 | 0.00026445 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | 7/21 10:30:00 | 9246.73 | 8917.31 | 0.839304 | 21.70 | 15.34 | 0.00865811 | 12.80 | 11.77 | 0.00850000 | 31.50 | 0.01446797 | 22.76 | 0.0000 | 21.11 | 0.00865811 | 53.5437 | 8264.82 | 0.00 | 9592.30 | 9592.30 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5510.490 | 5510.490 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5510.49 | 5314.18 | 0.246417 | 21.70 | 15.34 | 0.00865811 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00775203 | 48.0086 | 5510.54 | 0.00 | -999.00 | -999.00 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9169.771 | -999.000 | 0.831998 | 0.00026225 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 9169.77 | 8840.22 | 0.831998 | 21.70 | 15.34 | 0.00865955 | 12.80 | 11.77 | 0.00850000 | 31.26 | 0.01446754 | 22.70 | 0.0000 | 21.11 | 0.00865955 | 53.5525 | 8192.87 | 0.00 | 9512.37 | 9512.37 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5520.255 | 5520.255 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5520.26 | 5321.87 | 0.246854 | 21.70 | 15.34 | 0.00865955 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00775247 | 48.0113 | 5520.31 | 0.00 | -999.00 | -999.00 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 19657.803 | 19657.803 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 19657.80 | 13095.82 | 0.474762 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00781434 | 48.7199 | 9054.02 | 0.00 | -999.00 | -999.00 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2687.673 | -999.000 | 0.245474 | 0.00007687 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 2687.67 | 2605.51 | 0.245474 | 21.70 | 15.32 | 0.00863497 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00863497 | 53.4025 | 2417.24 | 0.00 | 2788.56 | 2788.56 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1709.881 | 1709.881 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1709.88 | 1657.61 | 0.076462 | 21.70 | 15.32 | 0.00863497 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00779847 | 48.2926 | 1709.90 | 0.00 | -999.00 | -999.00 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2655.254 | -999.000 | 0.242410 | 0.00007594 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 2655.25 | 2573.16 | 0.242410 | 21.70 | 15.32 | 0.00863654 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00863654 | 53.4122 | 2387.07 | 0.00 | 2754.89 | 2754.89 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1713.721 | 1713.721 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1713.72 | 1660.74 | 0.076634 | 21.70 | 15.32 | 0.00863654 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00779892 | 48.2954 | 1713.74 | 0.00 | -999.00 | -999.00 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12254.212 | -999.000 | 1.095508 | 0.00035046 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 12254.21 | 11667.05 | 1.095508 | 21.70 | 15.39 | 0.00871539 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00871539 | 53.8936 | 10787.51 | 0.00 | 12709.10 | 12709.10 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8208.496 | 8208.496 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8208.50 | 7815.19 | 0.367068 | 21.70 | 15.39 | 0.00871539 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00780642 | 48.3410 | 8208.56 | 0.00 | -999.00 | -999.00 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 49144.585 | 49144.585 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 49144.59 | 32764.15 | 1.187797 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00785407 | 48.9646 | 5858.22 | 0.00 | -999.00 | -999.00 |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 49173.514 | 49173.514 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 49173.51 | 32764.15 | 1.187797 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00785723 | 48.9841 | 5991.25 | 0.00 | -999.00 | -999.00 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 15194.280 | 15194.280 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 15194.28 | 10132.98 | 0.367350 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00714093 | 44.5746 | 2420.35 | 0.00 | -999.00 | -999.00 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7593.934 | 7593.934 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 7593.93 | 7593.93 | 0.275302 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00787851 | 49.1150 | 6192.53 | 0.00 | -999.00 | -999.00 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 91161.109 | -999.000 | 2.051317 | 0.00260720 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 91161.11 | 55491.40 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 11.91 | 11.41 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 99.9965 | 21.11 | 0.00868920 | 53.7327 | 150702.98 | 0.00 | 92683.44 | 56170.47 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | FLR_3_DOAS | 16512.404 | 16512.404 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 16512.40 | 16512.40 | 0.615395 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 333.3216 | 21.11 | 0.00777264 | 48.1340 | 97656.05 | 0.00 | -999.00 | -999.00 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 647250.165 | -999.000 | 20.905154 | 0.01851127 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 647250.16 | 437784.82 | 20.905154 | 28.63 | 20.16 | 0.01186256 | 10.92 | 10.92 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 44.6263 | 23.99 | 0.00976204 | 50.5884 | 277209.33 | 0.00 | 661255.28 | 436075.09 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV WITH REHEAT | 168279.360 | 168279.360 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 168279.36 | 168279.36 | 6.271546 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 148.7544 | 21.01 | 0.00779039 | 48.5349 | 60039.22 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | No | unknown | No | 35368.455 | 35368.455 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 35368.45 | 23569.37 | 1.0000 | 0.99200670 | 0.854459 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35368.45 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00795846 | 21.00 | 0.00795846 | 49.6068 | 1410.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 3275.194 | 3275.194 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 3275.19 | 3153.11 | 1.0000 | 0.13271074 | 0.114310 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3275.19 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00776905 | 21.00 | 0.00776905 | 48.4417 | 2571.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 3797.430 | 3797.430 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 3797.43 | 2530.41 | 1.0000 | 0.10650178 | 0.091735 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3797.43 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00773558 | 21.00 | 0.00773558 | 48.2351 | 861.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 1920.240 | 1920.240 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 1920.24 | 1920.24 | 1.0000 | 0.08082064 | 0.069614 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1920.24 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00766087 | 21.00 | 0.00766087 | 47.7751 | 1565.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 2391.227 | 2391.227 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 2391.23 | 1593.39 | 1.0000 | 0.06706399 | 0.057765 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2391.23 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00770558 | 21.00 | 0.00770558 | 48.0504 | 1049.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 2489.776 | 2489.776 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2489.78 | 2489.78 | 1.0000 | 0.10479171 | 0.090262 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2489.78 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00764398 | 21.00 | 0.00764398 | 47.6714 | 2030.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 27976.391 | 27976.391 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 27976.39 | 18657.50 | 1.0000 | 0.78527220 | 0.676389 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27976.39 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00779772 | 21.00 | 0.00779772 | 48.6181 | 6523.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 78384.621 | 78384.621 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 78384.62 | 52243.77 | 1.0000 | 2.19887860 | 1.893991 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 78384.62 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00775575 | 21.00 | 0.00775575 | 48.3594 | 15318.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10197.212 | -999.000 | 0.929491 | 0.00029163 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9057 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.929491 | 1.07911718 | 4197.9300 | 999.8980 | 26.17954975 | 15.03 | 6.70 | 8.33 | 915466.31 | 1.1139 | 1.113861 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 10197.21 | 9868.92 | 1.0000 | 1.07911718 | 0.929491 | 21.70 | 15.32 | 0.00864237 | 43771.8 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.29160378 | 6.70 | 15.03 | 8.33 | 0.000 | 10197.21 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00864237 | 21.11 | 0.00864237 | 53.4477 | 9152.92 | 0.00 | 10579.43 | 10579.43 | 1.07911718 | 21.70 | 15.69 | 0.00864237 | 43771.8 | 12.10 | 11.95 | 0.00864237 | 33968.0 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5530.608 | 5530.608 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.929491 | 1.07911718 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 5530.61 | 5352.56 | 1.0000 | 0.28712897 | 0.247317 | 21.70 | 15.32 | 0.00864237 | 43771.8 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5530.61 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00775290 | 21.11 | 0.00775290 | 48.0139 | 5530.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10085.917 | -999.000 | 0.918884 | 0.00028845 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9092 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.918884 | 1.06680244 | 4197.9300 | 999.8980 | 26.17954975 | 15.03 | 6.70 | 8.33 | 915466.31 | 1.1017 | 1.101704 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 10085.92 | 9757.08 | 1.0000 | 1.06680244 | 0.918884 | 21.70 | 15.32 | 0.00864424 | 43776.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.28842113 | 6.70 | 15.03 | 8.33 | 0.000 | 10085.92 | 32.75 | 0.01447025 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00864424 | 21.11 | 0.00864424 | 53.4592 | 9048.47 | 0.00 | 10463.83 | 10463.83 | 1.06680244 | 21.70 | 15.69 | 0.00864424 | 43776.5 | 12.10 | 11.95 | 0.00864424 | 33967.9 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5540.367 | 5540.367 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.918884 | 1.06680244 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 5540.37 | 5359.73 | 1.0000 | 0.28763566 | 0.247753 | 21.70 | 15.32 | 0.00864424 | 43776.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5540.37 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00775333 | 21.11 | 0.00775333 | 48.0165 | 5540.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 56307.114 | -999.000 | 5.252805 | 0.00161035 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7469 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.252805 | 6.09838339 | 4197.9300 | 999.8980 | 26.17954975 | 15.03 | 6.70 | 8.33 | 915466.31 | 6.1506 | 6.150534 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 56307.11 | 55567.87 | 1.0000 | 6.09838339 | 5.252805 | 21.70 | 15.25 | 0.00855694 | 43555.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 1.61018198 | 6.70 | 15.03 | 8.33 | 0.000 | 56307.11 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00855694 | 21.11 | 0.00855694 | 52.9249 | 51728.98 | 0.00 | 58444.65 | 58444.65 | 6.09838339 | 21.70 | 15.61 | 0.00855694 | 43555.3 | 12.32 | 11.96 | 0.00855694 | 33971.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 31862.633 | 31862.633 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.252805 | 6.09838339 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 31862.63 | 31444.32 | 1.0000 | 1.65421120 | 1.424845 | 21.70 | 15.25 | 0.00855694 | 43555.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31862.63 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00777183 | 21.11 | 0.00777183 | 48.1290 | 31862.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 64454.464 | -999.000 | 5.620641 | 0.00184336 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2189 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.620641 | 6.52543214 | 4197.9300 | 999.8980 | 26.17954975 | 15.03 | 6.70 | 8.33 | 915466.31 | 7.0406 | 7.040484 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | unknown | unknown | 7/21 15:40:00 | Sensible | 64454.46 | 60089.97 | 1.0000 | 6.52543214 | 5.620641 | 21.70 | 15.47 | 0.00881085 | 44199.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 1.84316705 | 6.70 | 15.03 | 8.33 | 0.000 | 64454.46 | 34.02 | 0.01447257 | 23.44 | 0.00000000 | 0.0000 | 21.11 | 0.00881085 | 21.11 | 0.00881085 | 54.4756 | 55346.96 | 0.00 | 66826.12 | 64233.05 | 6.52543214 | 21.70 | 15.84 | 0.00881085 | 44199.6 | 12.06 | 11.95 | 0.00865337 | 33958.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 32058.978 | 32058.978 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.620641 | 6.52543214 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 32058.98 | 29888.12 | 1.0000 | 1.66440486 | 1.433625 | 21.70 | 15.47 | 0.00881085 | 44199.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32058.98 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00777311 | 21.11 | 0.00777311 | 48.1369 | 32059.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9246.726 | -999.000 | 0.839304 | 0.00026445 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9350 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.839304 | 0.97441193 | 4197.9300 | 999.8980 | 26.17954975 | 15.03 | 6.70 | 8.33 | 915466.31 | 1.0101 | 1.010038 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | unknown | unknown | 7/21 10:30:00 | Sensible | 9246.73 | 8917.31 | 1.0000 | 0.97441193 | 0.839304 | 21.70 | 15.34 | 0.00865811 | 43811.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.26442329 | 6.70 | 15.03 | 8.33 | 0.000 | 9246.73 | 31.50 | 0.01446797 | 22.76 | 0.00000000 | 0.0000 | 21.11 | 0.00865811 | 21.11 | 0.00865811 | 53.5437 | 8264.82 | 0.00 | 9592.30 | 9592.30 | 0.97441193 | 21.70 | 15.70 | 0.00865811 | 43811.7 | 12.06 | 11.95 | 0.00865811 | 33967.6 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5510.490 | 5510.490 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.839304 | 0.97441193 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 5510.49 | 5314.18 | 1.0000 | 0.28608452 | 0.246417 | 21.70 | 15.34 | 0.00865811 | 43811.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5510.49 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00775203 | 21.11 | 0.00775203 | 48.0086 | 5510.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9169.771 | -999.000 | 0.831998 | 0.00026225 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9377 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.831998 | 0.96592972 | 4197.9300 | 999.8980 | 26.17954975 | 15.03 | 6.70 | 8.33 | 915466.31 | 1.0017 | 1.001632 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 9169.77 | 8840.22 | 1.0000 | 0.96592972 | 0.831998 | 21.70 | 15.34 | 0.00865955 | 43815.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.26222264 | 6.70 | 15.03 | 8.33 | 0.000 | 9169.77 | 31.26 | 0.01446754 | 22.70 | 0.00000000 | 0.0000 | 21.11 | 0.00865955 | 21.11 | 0.00865955 | 53.5525 | 8192.87 | 0.00 | 9512.37 | 9512.37 | 0.96592972 | 21.70 | 15.70 | 0.00865955 | 43815.4 | 12.06 | 11.95 | 0.00865955 | 33967.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5520.255 | 5520.255 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.831998 | 0.96592972 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 5520.26 | 5321.87 | 1.0000 | 0.28659150 | 0.246854 | 21.70 | 15.34 | 0.00865955 | 43815.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5520.26 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00775247 | 21.11 | 0.00775247 | 48.0113 | 5520.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 19657.803 | 19657.803 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 19657.80 | 13095.82 | 1.0000 | 0.55118776 | 0.474762 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19657.80 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00781434 | 21.00 | 0.00781434 | 48.7199 | 9054.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2687.673 | -999.000 | 0.245474 | 0.00007687 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8920 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.245474 | 0.28498939 | 4197.9300 | 999.8980 | 26.17954975 | 15.03 | 6.70 | 8.33 | 915466.31 | 0.2936 | 0.293580 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 2687.67 | 2605.51 | 1.0000 | 0.28498939 | 0.245474 | 21.70 | 15.32 | 0.00863497 | 43753.0 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.07685784 | 6.70 | 15.03 | 8.33 | 0.000 | 2687.67 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00863497 | 21.11 | 0.00863497 | 53.4025 | 2417.24 | 0.00 | 2788.56 | 2788.56 | 0.28498939 | 21.70 | 15.68 | 0.00863497 | 43753.0 | 12.12 | 11.95 | 0.00863497 | 33968.2 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 1709.881 | 1709.881 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.245474 | 0.28498939 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1709.88 | 1657.61 | 1.0000 | 0.08877079 | 0.076462 | 21.70 | 15.32 | 0.00863497 | 43753.0 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1709.88 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00779847 | 21.11 | 0.00779847 | 48.2926 | 1709.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2655.254 | -999.000 | 0.242410 | 0.00007594 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8949 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.242410 | 0.28143227 | 4197.9300 | 999.8980 | 26.17954975 | 15.03 | 6.70 | 8.33 | 915466.31 | 0.2900 | 0.290039 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 2655.25 | 2573.16 | 1.0000 | 0.28143227 | 0.242410 | 21.70 | 15.32 | 0.00863654 | 43757.0 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.07593078 | 6.70 | 15.03 | 8.33 | 0.000 | 2655.25 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00863654 | 21.11 | 0.00863654 | 53.4122 | 2387.07 | 0.00 | 2754.89 | 2754.89 | 0.28143227 | 21.70 | 15.68 | 0.00863654 | 43757.0 | 12.12 | 11.95 | 0.00863654 | 33968.2 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 1713.721 | 1713.721 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.242410 | 0.28143227 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1713.72 | 1660.74 | 1.0000 | 0.08897016 | 0.076634 | 21.70 | 15.32 | 0.00863654 | 43757.0 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1713.72 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00779892 | 21.11 | 0.00779892 | 48.2954 | 1713.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12254.212 | -999.000 | 1.095508 | 0.00035046 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0415 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.095508 | 1.27185913 | 4197.9300 | 999.8980 | 26.17954975 | 15.03 | 6.70 | 8.33 | 915466.31 | 1.3386 | 1.338551 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 12254.21 | 11667.05 | 1.0000 | 1.27185913 | 1.095508 | 21.70 | 15.39 | 0.00871539 | 43957.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.35042661 | 6.70 | 15.03 | 8.33 | 0.000 | 12254.21 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00871539 | 21.11 | 0.00871539 | 53.8936 | 10787.51 | 0.00 | 12709.10 | 12709.10 | 1.27185913 | 21.70 | 15.75 | 0.00871539 | 43957.1 | 11.92 | 11.92 | 0.00871539 | 33964.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 8208.496 | 8208.496 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.095508 | 1.27185913 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 8208.50 | 7815.19 | 1.0000 | 0.42615703 | 0.367068 | 21.70 | 15.39 | 0.00871539 | 43957.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8208.50 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00780642 | 21.11 | 0.00780642 | 48.3410 | 8208.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 49144.585 | 49144.585 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 49144.59 | 32764.15 | 1.0000 | 1.37900446 | 1.187797 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49144.59 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00785407 | 21.00 | 0.00785407 | 48.9646 | 5858.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 49173.514 | 49173.514 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 49173.51 | 32764.15 | 1.0000 | 1.37900446 | 1.187797 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49173.51 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00785723 | 21.00 | 0.00785723 | 48.9841 | 5991.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 15194.280 | 15194.280 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 15194.28 | 10132.98 | 1.0000 | 0.42648515 | 0.367350 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15194.28 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.58 | 0.00714093 | 21.00 | 0.00714093 | 44.5746 | 2420.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 7593.934 | 7593.934 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 7593.93 | 7593.93 | 1.0000 | 0.31961968 | 0.275302 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7593.93 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00787851 | 21.00 | 0.00787851 | 49.1150 | 6192.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 91161.109 | -999.000 | 2.051317 | 0.00260720 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.7451 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 26.17954975 | 15.03 | 6.70 | 8.33 | 915466.31 | 9.9579 | 9.957888 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 91161.11 | 55491.40 | 1.0000 | 2.38153119 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 71688.8 | 11.91 | 11.41 | 0.00850000 | 33410.4 | 2.60693021 | 6.70 | 15.03 | 8.33 | 2195.006 | 88966.10 | 34.40 | 0.01447326 | 23.54 | 2.05124512 | 99.9965 | 21.11 | 0.00868776 | 21.11 | 0.00868920 | 53.7327 | 150702.98 | 0.00 | 92683.44 | 56170.47 | 2.38153119 | 34.40 | 23.99 | 0.01447326 | 71688.8 | 11.54 | 11.47 | 0.00839502 | 32771.2 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16512.404 | 16512.404 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 16512.40 | 16512.40 | 1.0000 | 0.71445936 | 0.615395 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16512.40 | -6.30 | 0.00229779 | -6.30 | 2.05124512 | 333.3216 | 21.11 | 0.00777177 | 21.11 | 0.00777264 | 48.1340 | 97656.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 647250.165 | -999.000 | 20.905154 | 0.01851127 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.8919 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.905154 | 24.27039315 | 4197.9300 | 999.8980 | 26.17954975 | 15.03 | 6.70 | 8.33 | 915466.31 | 70.7017 | 70.701691 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 647250.16 | 437784.82 | 1.0000 | 24.27039315 | 20.905154 | 28.63 | 20.16 | 0.01186256 | 59072.3 | 10.92 | 10.92 | 0.00850000 | 32404.0 | 18.50938444 | 6.70 | 15.03 | 8.33 | 46840.895 | 600409.27 | 34.40 | 0.01447326 | 23.54 | 9.32920000 | 44.6263 | 23.99 | 0.00975857 | 23.99 | 0.00976204 | 50.5884 | 277209.33 | 0.00 | 661255.28 | 436075.09 | 24.27039315 | 28.63 | 20.57 | 0.01186256 | 59072.3 | 11.14 | 11.08 | 0.00818323 | 31826.9 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 168279.360 | 168279.360 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.905154 | 24.27039315 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 168279.36 | 168279.36 | 1.0000 | 7.28111795 | 6.271546 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 168279.36 | -6.30 | 0.00229779 | -6.30 | 9.32920000 | 148.7544 | 20.98 | 0.00778202 | 21.01 | 0.00779039 | 48.5349 | 60039.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 20.91 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1070.33 | 6685.33 | 185.67 |
RETAIL_1_FLR_1 | 3931.67 | 5351.67 | 1212.50 |
RETAIL_2_FLR_1 | 1714.17 | 6902.67 | 703.50 |
MECH_FLR_1 | 3346.67 | 4220.00 | 93.67 |
STORAGE_FLR_1 | 600.50 | 8740.33 | 600.50 |
LAUNDRY_FLR_1 | 8760.00 | 4739.00 | 4739.00 |
CAFE_FLR_1 | 1964.33 | 7522.00 | 1412.00 |
LOBBY_FLR_1 | 2181.83 | 7145.17 | 1469.17 |
ROOM_1_FLR_3 | 1029.00 | 8211.00 | 1023.83 |
ROOM_2_FLR_3 | 1905.00 | 8095.83 | 1829.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1117.67 | 8753.67 | 1117.33 |
ROOM_5_FLR_3 | 962.83 | 8131.67 | 961.33 |
ROOM_6_FLR_3 | 1874.50 | 8055.33 | 1794.67 |
CORRIDOR_FLR_3 | 1355.50 | 8359.67 | 1337.17 |
ROOM_1_FLR_6 | 1755.00 | 8027.00 | 1716.33 |
ROOM_2_FLR_6 | 2621.17 | 7900.83 | 2498.17 |
ROOM_3_MULT9_FLR_6 | 632.67 | 8190.67 | 625.50 |
BANQUET_FLR_6 | 2678.00 | 6380.67 | 1383.33 |
DINING_FLR_6 | 3631.50 | 5277.67 | 1384.67 |
KITCHEN_FLR_6 | 8743.83 | 6432.67 | 6432.67 |
CORRIDOR_FLR_6 | 4021.00 | 5186.83 | 1028.83 |
Facility | 8760.00 | 8760.00 | 7981.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 3.50 | 7.33 | 3.50 | 7.33 |
ROOM_2_FLR_3 | 7.67 | 11.67 | 7.67 | 11.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1.00 | 26.83 | 1.00 | 26.83 |
ROOM_5_FLR_3 | 2.67 | 2.67 | 2.67 | 2.67 |
ROOM_6_FLR_3 | 6.17 | 32.33 | 6.17 | 32.33 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 2.33 | 15.83 | 2.33 | 15.83 |
ROOM_2_FLR_6 | 5.00 | 17.83 | 5.00 | 17.83 |
ROOM_3_MULT9_FLR_6 | 0.83 | 19.83 | 0.83 | 19.83 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 2.17 | 0.00 | 2.17 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 11.00 | 74.67 | 11.00 | 74.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.738 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.328 | 0.061 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.219 | 0.020 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.152 | 0.023 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.624 | 0.023 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 15.817 | 0.065 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 3.671 | 0.048 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.498 | 0.020 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.341 | 0.079 | 0.000 | 0.068 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.079 | 0.000 | 0.069 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.388 | 0.035 | 0.000 | 0.108 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.341 | 0.079 | 0.000 | 0.068 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.079 | 0.000 | 0.069 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.406 | 0.010 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.341 | 0.079 | 0.000 | 0.082 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.342 | 0.079 | 0.000 | 0.081 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.388 | 0.064 | 0.000 | 0.130 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.800 | 0.023 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.830 | 0.023 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 15.959 | 0.066 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.495 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.512 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.911 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.901 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.006 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.442 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 6.089 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 2.627 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.136 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.288 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 3.589 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 3.635 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 4.505 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.310 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.79 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.56 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.09 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.25 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 30673135.43 | 0.00 | 30673135.43 | 0.00 | 30673135.43 | 26946214.98 | 4795.28 | 135.96 | 3828.75 | 0.00 |
RETAIL_1_FLR_1 | 3035626.99 | 0.00 | 3035626.99 | 139599.38 | 3175226.37 | 2498216.28 | 3580.34 | 125.40 | 5054.26 | 0.00 |
RETAIL_2_FLR_1 | 3230893.19 | 0.00 | 3230893.19 | 53885.54 | 3284778.73 | 2892943.94 | 5089.70 | 102.03 | 3568.27 | 0.00 |
MECH_FLR_1 | 847184.38 | 0.00 | 847184.38 | 127353.40 | 974537.78 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2024976.70 | 0.00 | 2024976.70 | 73475.90 | 2098452.60 | 1821682.01 | 5211.33 | 71.47 | 3477.20 | 0.00 |
LAUNDRY_FLR_1 | 41985275.40 | 0.00 | 41985275.40 | 173894.57 | 42159169.97 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23692162.83 | 0.00 | 23692162.83 | 308592.34 | 24000755.18 | 21330615.53 | 5214.61 | 70.26 | 3475.13 | 0.00 |
LOBBY_FLR_1 | 66785583.82 | 0.00 | 66785583.82 | 881718.81 | 67667302.63 | 59728886.00 | 4992.16 | 183.86 | 3583.98 | 0.00 |
ROOM_1_FLR_3 | 1406076.84 | 70130.92 | 1476207.75 | 81027.53 | 1557235.28 | 1946875.62 | 2433.33 | 5505.17 | 821.50 | 0.00 |
ROOM_2_FLR_3 | 1405912.09 | 70794.99 | 1476707.08 | 81021.35 | 1557728.43 | 1946647.51 | 2433.33 | 5512.10 | 814.57 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 4162.77 | 1104074.74 | 22607.59 | 1126682.33 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 406.33 |
ROOM_4_MULT19_FLR_3 | 19070354.14 | 69618.73 | 19139972.87 | 22613.77 | 19162586.64 | 26405105.73 | 2433.33 | 5550.11 | 776.56 | 0.00 |
ROOM_5_FLR_3 | 1406076.84 | 70143.17 | 1476220.00 | 81027.53 | 1557247.53 | 1946875.62 | 2433.33 | 5505.17 | 821.50 | 0.00 |
ROOM_6_FLR_3 | 1405912.09 | 70270.92 | 1476183.01 | 81021.35 | 1557204.36 | 1946647.51 | 2433.33 | 5505.28 | 821.39 | 0.00 |
CORRIDOR_FLR_3 | 16646932.40 | 0.00 | 16646932.40 | 97978.58 | 16744910.98 | 14972100.18 | 5210.00 | 72.35 | 3477.65 | 0.00 |
ROOM_1_FLR_6 | 351519.21 | 83737.09 | 435256.30 | 81044.19 | 516300.49 | 486718.90 | 2190.45 | 5506.46 | 1063.09 | 0.00 |
ROOM_2_FLR_6 | 351478.02 | 82691.00 | 434169.02 | 81038.01 | 515207.03 | 486661.88 | 2193.05 | 5519.78 | 1047.18 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2258331.41 | 83911.28 | 2342242.69 | 41465.04 | 2383707.73 | 3126920.42 | 2433.33 | 5502.50 | 824.17 | 0.00 |
BANQUET_FLR_6 | 41772489.98 | 0.00 | 41772489.98 | 197889.55 | 41970379.52 | 37458366.31 | 5163.19 | 97.13 | 3499.68 | 0.00 |
DINING_FLR_6 | 41998079.01 | 0.00 | 41998079.01 | 197889.55 | 42195968.56 | 37458366.31 | 5057.12 | 99.12 | 3603.76 | 0.00 |
KITCHEN_FLR_6 | 43050007.18 | 0.00 | 43050007.18 | 177157.02 | 43227164.20 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 5340198.57 | 0.00 | 5340198.57 | 173391.41 | 5513589.98 | 3961413.96 | 2568.08 | 87.35 | 6104.56 | 0.00 |
Total Facility | 0.19E+10 | 7654383.33 | 0.20E+10 | 8165243.82 | 0.20E+10 | 0.43E+10 | 8760.00 | 5999.35 | 8760.00 | 406.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9726 | 0.0000 | 0.9726 | 0.0000 | 0.9726 | 0.8545 | 4795.28 | 135.96 | 3828.75 |
RETAIL_1_FLR_1 | 0.0963 | 0.0000 | 0.0963 | 0.0044 | 0.1007 | 0.0792 | 3580.34 | 125.40 | 5054.26 |
RETAIL_2_FLR_1 | 0.1025 | 0.0000 | 0.1025 | 0.0017 | 0.1042 | 0.0917 | 5089.70 | 102.03 | 3568.27 |
MECH_FLR_1 | 0.0269 | 0.0000 | 0.0269 | 0.0040 | 0.0309 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0642 | 0.0000 | 0.0642 | 0.0023 | 0.0665 | 0.0578 | 5211.33 | 71.47 | 3477.20 |
LAUNDRY_FLR_1 | 1.3313 | 0.0000 | 1.3313 | 0.0055 | 1.3369 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7513 | 0.0000 | 0.7513 | 0.0098 | 0.7611 | 0.6764 | 5214.61 | 70.26 | 3475.13 |
LOBBY_FLR_1 | 2.1178 | 0.0000 | 2.1178 | 0.0280 | 2.1457 | 1.8940 | 4992.16 | 183.86 | 3583.98 |
ROOM_1_FLR_3 | 0.0446 | 0.0022 | 0.0468 | 0.0026 | 0.0494 | 0.0617 | 2433.33 | 5505.17 | 821.50 |
ROOM_2_FLR_3 | 0.0446 | 0.0022 | 0.0468 | 0.0026 | 0.0494 | 0.0617 | 2433.33 | 5512.10 | 814.57 |
ROOM_4_MULT19_FLR_3 | 0.6047 | 0.0022 | 0.6069 | 0.0007 | 0.6076 | 0.8373 | 2433.33 | 5550.11 | 776.56 |
ROOM_5_FLR_3 | 0.0446 | 0.0022 | 0.0468 | 0.0026 | 0.0494 | 0.0617 | 2433.33 | 5505.17 | 821.50 |
ROOM_6_FLR_3 | 0.0446 | 0.0022 | 0.0468 | 0.0026 | 0.0494 | 0.0617 | 2433.33 | 5505.28 | 821.39 |
CORRIDOR_FLR_3 | 0.5279 | 0.0000 | 0.5279 | 0.0031 | 0.5310 | 0.4748 | 5210.00 | 72.35 | 3477.65 |
ROOM_1_FLR_6 | 0.0111 | 0.0027 | 0.0138 | 0.0026 | 0.0164 | 0.0154 | 2190.45 | 5506.46 | 1063.09 |
ROOM_2_FLR_6 | 0.0111 | 0.0026 | 0.0138 | 0.0026 | 0.0163 | 0.0154 | 2193.05 | 5519.78 | 1047.18 |
ROOM_3_MULT9_FLR_6 | 0.0716 | 0.0027 | 0.0743 | 0.0013 | 0.0756 | 0.0992 | 2433.33 | 5502.50 | 824.17 |
BANQUET_FLR_6 | 1.3246 | 0.0000 | 1.3246 | 0.0063 | 1.3309 | 1.1878 | 5163.19 | 97.13 | 3499.68 |
DINING_FLR_6 | 1.3318 | 0.0000 | 1.3318 | 0.0063 | 1.3380 | 1.1878 | 5057.12 | 99.12 | 3603.76 |
KITCHEN_FLR_6 | 1.3651 | 0.0000 | 1.3651 | 0.0056 | 1.3707 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.1693 | 0.0000 | 0.1693 | 0.0055 | 0.1748 | 0.1256 | 2568.08 | 87.35 | 6104.56 |
Total Facility | 59.1037 | 0.2327 | 59.3364 | 0.2044 | 59.5408 | 73.9670 | 8760.00 | 5999.35 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 38758673.79 | 605460.87 | 39364134.66 | 64690340.46 | 8759.83 | 0.17 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.43E+09 | 0.00 | 0.43E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.2290 | 0.0192 | 1.2482 | 2.0513 | 8759.83 | 0.17 | 0.00 |
VAV WITH REHEAT | 13.7233 | 0.0000 | 13.7233 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6691.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 151.61 | 5063.59 | 0.00 | 0.00 | 0.00 | 3544.80 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6091 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 12.5016 | 15.4373 | 0.0000 | 0.0000 | 0.0000 | 11.3344 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1276 |
Defaulted Fields | 1144 |
Fields with Defaults | 3765 |
Autosized Fields | 294 |
Autosizable Fields | 344 |
Autocalculated Fields | 279 |
Autocalculatable Fields | 538 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5680.48 | 71624.86 | 21-MAR-01:40 | 358783.06 | 06-JUL-18:10 |
Electricity:Building | 2201.24 | 29107.25 | 02-JAN-02:10 | 132137.22 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 266.04 | 3144.96 | 02-JAN-02:10 | 19685.67 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2194.15 | 28966.11 | 02-JAN-02:10 | 131895.89 | 02-JAN-20:10 |
InteriorLights:Electricity | 545.70 | 5072.43 | 02-JAN-02:10 | 45764.37 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 122.93 | 1117.06 | 02-JAN-02:10 | 10053.14 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 545.70 | 5072.43 | 02-JAN-02:10 | 45764.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 545.70 | 5072.43 | 02-JAN-02:10 | 45764.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 122.93 | 1117.06 | 02-JAN-02:10 | 10053.14 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 545.70 | 5072.43 | 02-JAN-02:10 | 45764.37 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.91 | 71.95 | 02-JAN-02:10 | 430.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.31 | 20.97 | 02-JAN-02:10 | 188.71 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.31 | 20.97 | 02-JAN-02:10 | 188.71 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.24 | 378.04 | 02-JAN-02:10 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.90 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.90 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 241.21 | 2998.53 | 02-JAN-02:10 | 18013.24 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 92.21 | 887.12 | 02-JAN-02:10 | 7984.04 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 92.21 | 887.12 | 02-JAN-02:10 | 7984.04 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 253.77 | 3619.58 | 02-JAN-10:10 | 20179.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 253.84 | 3620.57 | 02-JAN-10:10 | 20185.51 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 3.85 | 55.20 | 01-JAN-02:10 | 290.10 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 3.85 | 55.19 | 01-JAN-02:10 | 290.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.06 | 428.75 | 02-JAN-10:10 | 2390.39 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 204.26 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.40 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.40 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 204.26 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.40 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.40 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.20 | 732.86 | 03-DEC-23:30 | 2790.47 | 23-APR-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1416.22 | 2245.48 | 06-FEB-02:10 | 178898.05 | 06-JUL-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 15.86 | 0.00 | 01-JAN-11:10 | 1313.91 | 12-APR-10:40 |
MedTempRefrigeration:Refrigeration:Electricity | 21.25 | 636.00 | 14-FEB-04:30 | 716.72 | 28-OCT-13:10 |
Fans:Electricity | 591.32 | 12465.12 | 06-MAR-04:00 | 37294.75 | 18-AUG-21:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 1076.99 | 13573.25 | 21-MAR-01:40 | 157525.36 | 03-JAN-16:20 |
ExteriorEquipment:Electricity | 813.52 | 9997.87 | 02-JAN-02:20 | 49590.83 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.52 | 379.07 | 02-JAN-02:20 | 1274.03 | 02-JAN-07:20 |
ElectricityPurchased:Facility | 5680.48 | 71624.86 | 21-MAR-01:40 | 358783.06 | 06-JUL-18:10 |
ElectricityPurchased:Plant | 5680.48 | 71624.86 | 21-MAR-01:40 | 358783.06 | 06-JUL-18:10 |
Cogeneration:ElectricityPurchased | 5680.48 | 71624.86 | 21-MAR-01:40 | 358783.06 | 06-JUL-18:10 |
General:Cogeneration:ElectricityPurchased | 5680.48 | 71624.86 | 21-MAR-01:40 | 358783.06 | 06-JUL-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5680.48 | 71624.86 | 21-MAR-01:40 | 358783.06 | 06-JUL-18:10 |
ElectricityNet:Plant | 5680.48 | 71624.86 | 21-MAR-01:40 | 358783.06 | 06-JUL-18:10 |
Cogeneration:ElectricityNet | 5680.48 | 71624.86 | 21-MAR-01:40 | 358783.06 | 06-JUL-18:10 |
General:Cogeneration:ElectricityNet | 5680.48 | 71624.86 | 21-MAR-01:40 | 358783.06 | 06-JUL-18:10 |
Heating:Electricity | 353.50 | 0.00 | 19-JAN-20:30 | 133727.51 | 03-JAN-10:50 |
General:Heating:Electricity | 353.50 | 0.00 | 19-JAN-20:30 | 133727.51 | 03-JAN-10:50 |
General:Fans:Electricity | 591.32 | 12465.12 | 06-MAR-04:00 | 37294.75 | 18-AUG-21:20 |
ExteriorLights:Electricity | 194.02 | 0.00 | 01-JAN-07:50 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 194.02 | 0.00 | 01-JAN-07:50 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 110.66 | 0.00 | 01-JAN-08:00 | 8265.52 | 05-JAN-00:10 |
General:HeatRecovery:Electricity | 110.66 | 0.00 | 01-JAN-08:00 | 8265.52 | 05-JAN-00:10 |
WaterSystems:Electricity | 94.78 | 1222.48 | 15-NOV-03:30 | 4751.13 | 11-DEC-07:40 |
Water Heater:WaterSystems:Electricity | 94.78 | 1222.48 | 15-NOV-03:30 | 4751.13 | 11-DEC-07:40 |
Cooling:Electricity | 1203.19 | 0.00 | 01-JAN-00:10 | 168606.43 | 06-JUL-18:10 |
General:Cooling:Electricity | 1203.19 | 0.00 | 01-JAN-00:10 | 168606.43 | 06-JUL-18:10 |
Pumps:Electricity | 81.15 | 47.91 | 05-JAN-08:00 | 4079.47 | 06-JUL-18:10 |
General:Pumps:Electricity | 81.15 | 47.91 | 05-JAN-08:00 | 4079.47 | 06-JUL-18:10 |
WIRED_LTG_ELECTRICITY | 19.21 | 0.00 | 01-JAN-00:10 | 1610.91 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4240.12 | 21378.04 | 11-MAY-01:40 | 342342.08 | 01-FEB-18:30 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2451.28 | 8016.14 | 11-MAY-01:40 | 240337.15 | 02-FEB-21:20 |
WaterSystems:NaturalGas | 2451.28 | 8016.14 | 11-MAY-01:40 | 240337.15 | 02-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 2451.28 | 8016.14 | 11-MAY-01:40 | 240337.15 | 02-FEB-21:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4763.11 | 0.00 | 01-JAN-00:10 | 601839.18 | 23-AUG-22:00 |
PlantLoopCoolingDemand:HVAC | 4763.11 | 0.00 | 01-JAN-00:10 | 601839.18 | 23-AUG-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 4763.11 | 0.00 | 01-JAN-00:10 | 601839.18 | 23-AUG-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 29-MAR-20:20 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 29-MAR-20:20 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 29-MAR-20:20 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 08-NOV-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 29-MAR-20:20 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 29-MAR-20:20 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 29-MAR-20:20 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 08-NOV-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:20 | 0.00 | 02-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:20 | 0.00 | 02-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 22856.63 | 119678.45 | 09-FEB-15:00 | 2346825.05 | 06-JUL-18:10 |
EnergyTransfer:Building | 5096.12 | 77830.71 | 08-JAN-15:00 | 329257.17 | 02-AUG-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 702.80 | 8232.39 | 12-FEB-04:00 | 34917.86 | 08-JUL-10:50 |
Refrigeration:EnergyTransfer | 185.89 | 4017.16 | 13-FEB-23:10 | 10368.65 | 04-APR-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.94 | 2008.58 | 13-FEB-23:10 | 5184.32 | 04-APR-06:30 |
General:Refrigeration:EnergyTransfer | 92.94 | 2008.58 | 13-FEB-23:10 | 5184.32 | 04-APR-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.94 | 2008.58 | 13-FEB-23:10 | 5184.32 | 04-APR-06:30 |
EnergyTransfer:Plant | 11647.27 | 11563.18 | 26-OCT-02:20 | 1396962.78 | 23-AUG-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.67 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.28 | 1996.28 | 14-FEB-04:30 | 2559.69 | 28-OCT-13:10 |
EnergyTransfer:Zone:BASEMENT | 369.78 | 5134.14 | 09-APR-15:00 | 20638.16 | 08-NOV-22:00 |
Heating:EnergyTransfer | 75.77 | 0.00 | 01-JAN-08:00 | 69151.95 | 07-JAN-16:30 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 75.77 | 0.00 | 01-JAN-08:00 | 69151.95 | 07-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4927.40 | 65815.23 | 08-JAN-15:00 | 325649.78 | 02-AUG-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 369.78 | 5134.14 | 09-APR-15:00 | 20638.16 | 08-NOV-22:00 |
General:Cooling:EnergyTransfer | 4927.40 | 65815.23 | 08-JAN-15:00 | 325649.78 | 02-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 369.78 | 5134.14 | 09-APR-15:00 | 20638.16 | 08-NOV-22:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.87 | 0.03 | 04-JAN-09:00 | 3178.90 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.43 | 0.00 | 01-JAN-00:10 | 1330.31 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.43 | 0.00 | 01-JAN-00:10 | 1330.31 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.44 | 0.00 | 01-JAN-17:00 | 3178.90 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.44 | 0.00 | 01-JAN-17:00 | 3178.90 | 10-OCT-13:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.96 | 226.56 | 08-JAN-16:00 | 2055.06 | 18-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.96 | 226.56 | 08-JAN-16:00 | 2055.06 | 18-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.96 | 226.56 | 08-JAN-16:00 | 2055.06 | 18-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 12.79 | 0.05 | 08-JAN-18:40 | 1809.73 | 07-JUL-21:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 292.49 | 08-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 292.49 | 08-JAN-13:50 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 12.76 | 0.00 | 07-JAN-10:50 | 1809.73 | 07-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 12.76 | 0.00 | 07-JAN-10:50 | 1809.73 | 07-JUL-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 18.69 | 0.02 | 10-FEB-13:30 | 1038.06 | 19-AUG-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.19 | 0.00 | 01-JAN-00:10 | 340.99 | 12-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.19 | 0.00 | 01-JAN-00:10 | 340.99 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 18.50 | 0.00 | 03-JAN-11:00 | 1038.06 | 19-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 18.50 | 0.00 | 03-JAN-11:00 | 1038.06 | 19-AUG-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 592.77 | 7835.97 | 13-FEB-05:00 | 39433.14 | 07-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 592.77 | 7835.97 | 13-FEB-05:00 | 39433.14 | 07-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 592.77 | 7835.97 | 13-FEB-05:00 | 39433.14 | 07-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 252.53 | 24.08 | 09-JAN-09:10 | 11637.76 | 08-JUL-17:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 252.53 | 24.08 | 09-JAN-09:10 | 11637.76 | 08-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 252.53 | 24.08 | 09-JAN-09:10 | 11637.76 | 08-JUL-17:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 809.52 | 7898.28 | 08-JAN-16:00 | 39155.72 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 809.52 | 7898.28 | 08-JAN-16:00 | 39155.72 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 809.52 | 7898.28 | 08-JAN-16:00 | 39155.72 | 18-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 60.10 | 0.00 | 01-JAN-08:00 | 9732.09 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 7.82 | 0.00 | 01-JAN-08:00 | 5345.17 | 07-JAN-19:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 7.82 | 0.00 | 01-JAN-08:00 | 5345.17 | 07-JAN-19:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 52.28 | 0.00 | 01-JAN-00:10 | 9732.09 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 52.28 | 0.00 | 01-JAN-00:10 | 9732.09 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 52.72 | 0.00 | 01-JAN-08:00 | 10087.84 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 10.70 | 0.00 | 01-JAN-08:00 | 5582.51 | 12-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 10.70 | 0.00 | 01-JAN-08:00 | 5582.51 | 12-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 42.02 | 0.00 | 01-JAN-00:10 | 10087.84 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 42.02 | 0.00 | 01-JAN-00:10 | 10087.84 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 265.44 | 0.00 | 01-JAN-00:10 | 37009.19 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 265.44 | 0.00 | 01-JAN-00:10 | 37009.19 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 265.44 | 0.00 | 01-JAN-00:10 | 37009.19 | 10-OCT-13:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 410.91 | 0.00 | 01-JAN-08:00 | 66831.83 | 27-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 21.75 | 0.00 | 01-JAN-00:10 | 29861.66 | 07-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 21.75 | 0.00 | 01-JAN-00:10 | 29861.66 | 07-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 389.17 | 0.00 | 01-JAN-08:00 | 66831.83 | 27-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 389.17 | 0.00 | 01-JAN-08:00 | 66831.83 | 27-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 60.37 | 0.00 | 01-JAN-08:00 | 8907.75 | 07-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 7.86 | 0.00 | 01-JAN-08:00 | 5426.25 | 07-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 7.86 | 0.00 | 01-JAN-08:00 | 5426.25 | 07-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 52.51 | 0.00 | 01-JAN-00:10 | 8907.75 | 07-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 52.51 | 0.00 | 01-JAN-00:10 | 8907.75 | 07-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 53.01 | 0.00 | 01-JAN-08:00 | 9532.49 | 07-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 10.66 | 0.00 | 01-JAN-08:00 | 5523.82 | 07-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 10.66 | 0.00 | 01-JAN-08:00 | 5523.82 | 07-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 42.34 | 0.00 | 01-JAN-00:10 | 9532.49 | 07-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 42.34 | 0.00 | 01-JAN-00:10 | 9532.49 | 07-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 169.94 | 0.42 | 08-FEB-10:40 | 9060.00 | 19-AUG-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.58 | 0.00 | 01-JAN-00:10 | 3126.90 | 09-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.58 | 0.00 | 01-JAN-00:10 | 3126.90 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 169.36 | 0.00 | 02-JAN-09:10 | 9060.00 | 19-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 169.36 | 0.00 | 02-JAN-09:10 | 9060.00 | 19-AUG-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 16.39 | 0.00 | 01-JAN-08:00 | 2686.03 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 3.36 | 0.00 | 01-JAN-08:00 | 1726.39 | 07-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 3.36 | 0.00 | 01-JAN-08:00 | 1726.39 | 07-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.03 | 0.00 | 01-JAN-00:10 | 2686.03 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.03 | 0.00 | 01-JAN-00:10 | 2686.03 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 15.02 | 0.00 | 01-JAN-08:00 | 2706.52 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.34 | 0.00 | 01-JAN-08:00 | 1744.09 | 12-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.34 | 0.00 | 01-JAN-08:00 | 1744.09 | 12-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.68 | 0.00 | 01-JAN-00:10 | 2706.52 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.68 | 0.00 | 01-JAN-00:10 | 2706.52 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 87.90 | 0.00 | 01-JAN-08:00 | 13157.97 | 11-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 6.86 | 0.00 | 01-JAN-08:00 | 8119.07 | 07-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 6.86 | 0.00 | 01-JAN-08:00 | 8119.07 | 07-JAN-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 81.04 | 0.00 | 01-JAN-00:10 | 13157.97 | 11-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 81.04 | 0.00 | 01-JAN-00:10 | 13157.97 | 11-OCT-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 489.87 | 7877.08 | 13-FEB-09:30 | 22168.26 | 07-JUL-22:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 489.87 | 7877.08 | 13-FEB-09:30 | 22168.26 | 07-JUL-22:00 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 489.87 | 7877.08 | 13-FEB-09:30 | 22168.26 | 07-JUL-22:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 513.18 | 9469.94 | 08-JAN-16:00 | 23547.13 | 07-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 513.18 | 9469.94 | 08-JAN-16:00 | 23547.13 | 07-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 513.18 | 9469.94 | 08-JAN-16:00 | 23547.13 | 07-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 609.85 | 5932.64 | 12-FEB-04:00 | 29856.35 | 08-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 609.85 | 5932.64 | 12-FEB-04:00 | 29856.35 | 08-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 68.56 | 0.11 | 24-JAN-04:40 | 6176.49 | 08-JUL-16:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.18 | 0.00 | 01-JAN-00:10 | 2893.58 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.18 | 0.00 | 01-JAN-00:10 | 2893.58 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 67.37 | 0.00 | 02-JAN-07:10 | 6176.49 | 08-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 67.37 | 0.00 | 02-JAN-07:10 | 6176.49 | 08-JUL-16:10 |
PlantLoopHeatingDemand:Facility | 689.09 | 7890.45 | 03-AUG-00:30 | 52969.01 | 01-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 689.09 | 7890.45 | 03-AUG-00:30 | 52969.01 | 01-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 689.09 | 7890.45 | 03-AUG-00:30 | 52969.01 | 01-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 689.09 | 7890.45 | 03-AUG-00:30 | 52969.01 | 01-FEB-07:10 |
EnergyTransfer:HVAC | 6113.24 | 0.00 | 22-FEB-08:20 | 710278.01 | 06-JUL-18:10 |
HeatingCoils:EnergyTransfer | 353.50 | 0.00 | 19-JAN-20:30 | 133727.51 | 03-JAN-10:50 |
CoolingCoils:EnergyTransfer | 4763.11 | 0.00 | 01-JAN-00:10 | 601839.18 | 23-AUG-22:00 |
HeatRecoveryForHeating:EnergyTransfer | 413.82 | 0.00 | 01-JAN-08:00 | 318094.35 | 12-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 582.81 | 0.00 | 01-JAN-00:10 | 162844.98 | 07-JUL-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 689.09 | 7890.45 | 03-AUG-00:30 | 52969.01 | 01-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 689.09 | 7890.45 | 03-AUG-00:30 | 52969.01 | 01-FEB-07:10 |
Chillers:EnergyTransfer | 4831.03 | 0.00 | 01-JAN-00:10 | 607188.50 | 23-AUG-22:00 |
HeatRejection:EnergyTransfer | 6034.22 | 0.00 | 01-JAN-00:10 | 763300.59 | 23-AUG-22:00 |
General:HeatRejection:EnergyTransfer | 6034.22 | 0.00 | 01-JAN-00:10 | 763300.59 | 23-AUG-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -369.783 | 0.000 | 0.000 | 143.587 | 122.932 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -39.841 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.430 | -35.442 | 0.000 | 0.000 | 14.697 | 6.265 | 10.186 | 18.384 | 0.000 | 0.144 | 0.000 | 0.000 | -8.458 | 0.000 | -1.206 | -4.998 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -37.956 | 0.000 | 0.000 | 16.998 | 7.255 | 11.795 | 0.000 | 0.000 | 0.068 | 2.306 | 0.000 | 0.000 | 0.000 | -0.466 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.033 | -12.759 | 0.000 | 0.000 | 3.419 | 8.366 | 12.471 | 0.000 | 0.000 | 0.129 | 0.000 | 0.000 | 0.000 | 0.000 | -1.215 | -10.444 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.192 | -18.502 | 0.000 | 0.000 | 2.917 | 2.308 | 3.598 | 0.000 | 0.000 | 0.108 | 9.960 | 0.000 | 0.000 | 0.000 | -0.580 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -592.775 | 0.000 | 0.000 | 10.551 | 4.900 | 658.131 | 0.000 | 0.000 | 0.176 | 0.000 | 0.000 | 0.000 | 0.000 | -1.753 | -79.229 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -252.532 | 0.000 | 0.000 | 198.426 | 12.896 | 14.341 | 53.272 | 0.000 | 0.465 | 0.000 | 0.000 | -23.310 | 0.000 | -2.559 | -0.998 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -809.529 | 0.000 | 0.000 | 563.778 | 92.208 | 148.998 | 69.464 | 0.000 | 1.147 | 0.000 | 0.000 | -32.718 | 0.000 | -7.868 | -25.480 |
ROOM_1_FLR_3 | 10.427 | -43.416 | 0.000 | -11.468 | 0.000 | 0.000 | 9.680 | 4.922 | 10.478 | 38.810 | 0.000 | 0.655 | 0.921 | 0.000 | -17.766 | 0.000 | -3.243 | -0.000 |
ROOM_2_FLR_3 | 13.650 | -33.054 | 0.000 | -11.908 | 0.000 | 0.000 | 9.582 | 4.922 | 10.477 | 29.798 | 0.000 | 0.526 | 0.000 | 0.000 | -18.837 | 0.000 | -3.594 | -1.561 |
ROOM_3_MULT19_FLR_3 | 0.000 | -249.707 | 0.000 | -15.731 | 0.000 | 0.000 | 0.000 | 58.777 | 194.997 | 199.294 | 0.000 | 0.802 | 0.004 | 0.000 | -138.591 | 0.000 | -22.421 | -27.419 |
ROOM_4_MULT19_FLR_3 | 43.880 | -251.167 | 0.000 | -160.110 | 0.000 | 0.000 | 182.385 | 58.793 | 195.050 | 90.209 | 0.000 | 3.359 | 0.000 | 0.000 | -105.072 | 0.000 | -30.548 | -26.780 |
ROOM_5_FLR_3 | 10.462 | -43.626 | 0.000 | -11.477 | 0.000 | 0.000 | 9.673 | 4.922 | 10.478 | 38.672 | 0.000 | 0.654 | 0.660 | 0.000 | -17.167 | 0.000 | -3.251 | -0.000 |
ROOM_6_FLR_3 | 13.609 | -33.381 | 0.000 | -11.903 | 0.000 | 0.000 | 9.587 | 4.922 | 10.477 | 29.169 | 0.000 | 0.528 | 0.001 | 0.000 | -17.730 | 0.000 | -3.527 | -1.750 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.580 | -169.356 | 0.000 | 0.000 | 117.432 | 56.739 | 0.000 | 35.149 | 0.000 | 0.496 | 0.000 | 0.000 | -23.211 | 0.000 | -3.202 | -14.626 |
ROOM_1_FLR_6 | 4.134 | -10.945 | 0.000 | -2.864 | 0.000 | 0.000 | 2.424 | 1.231 | 2.620 | 9.637 | 0.000 | 0.167 | 0.000 | 0.000 | -4.385 | 0.000 | -0.837 | -1.181 |
ROOM_2_FLR_6 | 5.178 | -8.544 | 0.000 | -2.970 | 0.000 | 0.000 | 2.399 | 1.230 | 2.619 | 7.404 | 0.000 | 0.132 | 0.000 | 0.000 | -4.655 | 0.000 | -0.929 | -1.864 |
ROOM_3_MULT9_FLR_6 | 9.991 | -65.652 | 0.000 | -18.511 | 0.000 | 0.000 | 21.722 | 6.962 | 23.098 | 49.239 | 0.000 | 0.929 | 0.000 | 0.000 | -20.383 | 0.000 | -4.878 | -2.516 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -489.871 | 0.000 | 0.000 | 336.703 | 28.398 | 175.857 | 9.725 | 0.000 | 0.269 | 0.000 | 0.000 | -14.055 | 0.000 | -1.751 | -45.276 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -513.190 | 0.000 | 0.000 | 331.455 | 28.398 | 175.857 | 9.390 | 0.000 | 0.254 | 0.000 | 0.000 | -14.697 | 0.000 | -1.800 | -15.668 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -609.844 | 0.000 | 0.000 | 27.946 | 13.339 | 540.650 | 18.568 | 0.000 | 0.175 | 21.661 | 0.000 | -10.693 | 0.000 | -1.802 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 1.183 | -67.374 | 0.000 | 0.000 | 29.708 | 15.012 | 0.000 | 16.116 | 0.000 | 0.171 | 17.900 | 0.000 | -11.174 | 0.000 | -1.544 | -0.000 |
Total Facility | 111.330 | -739.493 | 2.418 | -4225.855 | 0.000 | 0.000 | 2045.068 | 545.696 | 2355.282 | 722.300 | 0.000 | 11.352 | 53.415 | 0.000 | -482.899 | 0.000 | -98.977 | -299.633 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-NOV-22:00 | 0.00 | 0.00 | 0.00 | -20639.13 | 0.00 | 0.00 | 5924.42 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3346.92 |
RETAIL_1_FLR_1 | 10-OCT-13:30 | 0.00 | 0.00 | 0.00 | -3178.86 | 0.00 | 0.00 | 150.60 | 142.31 | 252.59 | 4081.86 | 0.00 | 24.33 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1472.83 |
RETAIL_2_FLR_1 | 18-AUG-21:00 | 0.00 | 0.00 | 0.00 | -2055.10 | 0.00 | 0.00 | 697.61 | 527.34 | 752.15 | 0.00 | 0.00 | 13.63 | 64.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 07-JUL-21:00 | 0.00 | 0.00 | 0.00 | -1809.78 | 0.00 | 0.00 | 147.52 | 608.16 | 795.27 | 0.00 | 0.00 | 30.00 | 228.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 19-AUG-10:35 | 0.00 | 0.00 | 0.00 | -1041.05 | 0.00 | 0.00 | 45.51 | 52.42 | 89.22 | 0.00 | 0.00 | 23.87 | 830.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 07-JUL-20:00 | 0.00 | 0.00 | 0.00 | -39432.54 | 0.00 | 0.00 | 408.81 | 400.68 | 44299.38 | 0.00 | 0.00 | 44.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5720.33 |
CAFE_FLR_1 | 13-APR-16:04 | 0.00 | 0.00 | 0.00 | -11903.91 | 0.00 | 0.00 | 5399.39 | 96.16 | 355.63 | 3216.45 | 0.00 | 43.64 | 2792.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -39161.79 | 0.00 | 0.00 | 26440.07 | 5322.69 | 7389.94 | 621.14 | 0.00 | 214.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -826.52 |
ROOM_1_FLR_3 | 27-FEB-16:11 | 0.00 | -12102.95 | 0.00 | -711.85 | 0.00 | 0.00 | 235.28 | 106.08 | 200.18 | 6657.03 | 0.00 | 0.00 | 5617.03 | 0.00 | -0.00 | 0.00 | -0.81 | 0.00 |
ROOM_2_FLR_3 | 09-MAY-20:41 | 0.00 | -12698.62 | 0.00 | -581.49 | 0.00 | 0.00 | 365.96 | 337.15 | 726.90 | 0.00 | 0.00 | 0.00 | 13388.67 | 0.00 | -1418.56 | 0.00 | -120.01 | 0.00 |
ROOM_3_MULT19_FLR_3 | 10-OCT-13:30 | 0.00 | -37007.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.71 | 2352.88 | 47822.99 | 0.00 | 132.02 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14567.29 |
ROOM_4_MULT19_FLR_3 | 09-MAY-20:41 | 0.00 | -78814.02 | 0.00 | -7806.70 | 0.00 | 0.00 | 7151.40 | 4027.42 | 13532.74 | 0.00 | 0.00 | 0.00 | 69538.52 | 0.00 | -6997.09 | 0.00 | -632.26 | 0.00 |
ROOM_5_FLR_3 | 27-FEB-16:11 | 0.00 | -10904.68 | 0.00 | -709.32 | 0.00 | 0.00 | 235.28 | 106.08 | 200.18 | 2079.16 | 0.00 | 0.64 | 8992.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 04-JUN-08:51 | 0.00 | -10940.06 | 0.00 | -925.05 | 0.00 | 0.00 | 107.86 | 212.14 | 653.15 | 6763.66 | 0.00 | 0.00 | 4140.69 | 0.00 | -0.00 | 0.00 | -12.39 | 0.00 |
CORRIDOR_FLR_3 | 19-AUG-10:35 | 0.00 | 0.00 | 0.00 | -9073.21 | 0.00 | 0.00 | 1805.02 | 1288.89 | 0.00 | 4775.26 | 0.00 | 118.46 | 1085.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 27-FEB-16:11 | 0.00 | -3194.18 | 0.00 | -177.93 | 0.00 | 0.00 | 58.82 | 26.52 | 50.05 | 1653.97 | 0.00 | 0.00 | 1583.56 | 0.00 | -0.00 | 0.00 | -0.81 | 0.00 |
ROOM_2_FLR_6 | 09-MAY-20:41 | 0.00 | -3417.68 | 0.00 | -151.80 | 0.00 | 0.00 | 88.93 | 84.29 | 181.72 | 0.00 | 0.00 | 0.00 | 3614.43 | 0.00 | -368.65 | 0.00 | -31.25 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10-MAR-16:11 | 0.00 | -14445.89 | 0.00 | -1107.18 | 0.00 | 0.00 | 529.38 | 150.05 | 441.28 | 2221.37 | 0.00 | 0.00 | 12724.41 | 0.00 | -0.00 | 0.00 | -513.41 | 0.00 |
BANQUET_FLR_6 | 07-JUL-22:00 | 0.00 | 0.00 | 0.00 | -22168.08 | 0.00 | 0.00 | 15644.53 | 1842.08 | 6747.90 | 223.10 | 0.00 | 37.64 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2327.18 |
DINING_FLR_6 | 07-JUL-21:20 | 0.00 | 0.00 | 0.00 | -23555.24 | 0.00 | 0.00 | 15643.80 | 1842.08 | 6747.90 | 268.57 | 0.00 | 43.17 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -990.29 |
KITCHEN_FLR_6 | 13-MAY-17:35 | 0.00 | 0.00 | 0.00 | -30558.25 | 0.00 | 0.00 | 923.69 | 727.22 | 26450.81 | 668.03 | 0.00 | 8.84 | 1779.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 08-JUL-16:10 | 0.00 | 0.00 | 0.00 | -6175.84 | 0.00 | 0.00 | 771.16 | 341.02 | 0.00 | 1527.98 | 0.00 | 74.26 | 3461.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-AUG-18:02 | 0.00 | -146311.45 | 0.00 | -200239.40 | 0.00 | 0.00 | 77937.01 | 36835.56 | 120174.13 | 32953.46 | 0.00 | 2374.20 | 76276.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 12-FEB-06:00 | 0.00 | 0.00 | 1330.32 | 0.00 | 0.00 | 0.00 | 626.53 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1598.66 | 0.00 | -196.16 | -492.40 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 08-JAN-13:50 | 0.00 | 0.00 | 292.48 | 0.00 | 0.00 | 0.00 | 43.84 | 152.04 | 265.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -110.20 | -643.24 |
STORAGE_FLR_1 | 12-FEB-07:00 | 0.00 | 0.00 | 341.00 | 0.00 | 0.00 | 0.00 | 118.04 | 62.90 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -105.45 | -518.44 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 22-NOV-09:09 | 5801.97 | 409.12 | 0.00 | -409.12 | 0.00 | 0.00 | 106.64 | 166.70 | 453.05 | 432.34 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -258.35 | -6702.35 |
ROOM_2_FLR_3 | 17-JAN-19:10 | 5808.14 | 409.33 | 0.00 | -409.33 | 0.00 | 0.00 | 419.19 | 337.15 | 484.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1633.31 | 0.00 | -212.54 | -5203.23 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 19-MAR-08:03 | 30887.07 | 5533.62 | 0.00 | -5533.62 | 0.00 | 0.00 | 2723.33 | 2534.11 | 12159.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7364.23 | 0.00 | -1144.18 | -39795.96 |
ROOM_5_FLR_3 | 02-FEB-19:09 | 5717.83 | 408.69 | 0.00 | -408.69 | 0.00 | 0.00 | 407.76 | 337.19 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2624.13 | 0.00 | -305.65 | -4017.66 |
ROOM_6_FLR_3 | 13-FEB-19:10 | 5738.71 | 406.03 | 0.00 | -406.03 | 0.00 | 0.00 | 418.61 | 337.15 | 484.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1684.79 | 0.00 | -209.40 | -5084.88 |
CORRIDOR_FLR_3 | 09-JAN-09:03 | 0.00 | 0.00 | 3152.17 | 0.00 | 0.00 | 0.00 | 1385.78 | 2062.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2348.64 | 0.00 | -384.50 | -3867.03 |
ROOM_1_FLR_6 | 17-DEC-19:09 | 1789.93 | 101.96 | 0.00 | -101.96 | 0.00 | 0.00 | 87.54 | 94.72 | 121.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -595.63 | 0.00 | -69.59 | -1428.14 |
ROOM_2_FLR_6 | 12-FEB-09:13 | 1779.88 | 84.69 | 0.00 | -84.69 | 0.00 | 0.00 | 37.60 | 53.04 | 163.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -656.76 | 0.00 | -102.70 | -1274.34 |
ROOM_3_MULT9_FLR_6 | 17-JAN-16:19 | 8360.33 | 657.14 | 0.00 | -657.14 | 0.00 | 0.00 | 649.53 | 150.05 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -823.34 | 0.00 | -248.17 | -8529.68 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 12-FEB-06:00 | 0.00 | 0.00 | 2893.63 | 0.00 | 0.00 | 0.00 | 1283.30 | 272.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2135.24 | 0.00 | -244.39 | -2070.12 |
Total Facility | 07-JAN-16:23 | -8580.23 | 80842.58 | 6092.07 | -80842.58 | 0.00 | 0.00 | 36696.40 | 12231.35 | 74529.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47767.39 | 0.00 | -8172.86 | -65029.30 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 21.0197 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 20.9052 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 13.0303 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5329 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2338 | 2.2338 | 1.2822 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3021 | 0.3021 | 0.1187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2272 | 0.2272 | 0.1377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1977 | 0.1977 | 0.0020 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1102 | 0.1102 | 0.0867 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3750 | 3.3750 | 0.0337 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3632 | 1.3632 | 1.0142 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6131 | 4.6131 | 2.8417 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1760 | 1.1760 | 0.7127 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2023 | 2.2023 | 1.7816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3122 | 2.3122 | 1.7827 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2301 | 2.2301 | 0.5508 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6768 | 0.6768 | 0.1882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 21.0197 | 20.9052 | 21.0197 | 10.5329 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2822 | 1.2822 | 1.2822 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1511 | 0.1511 | 0.1187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1377 | 0.1377 | 0.1377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0989 | 0.0989 | 0.0020 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0867 | 0.0867 | 0.0867 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6875 | 1.6875 | 0.0337 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0142 | 1.0142 | 1.0142 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8417 | 2.8417 | 2.8417 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7127 | 0.7127 | 0.7127 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7816 | 1.7816 | 1.7816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7827 | 1.7827 | 1.7827 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1151 | 1.1151 | 0.5508 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3384 | 0.3384 | 0.1882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 13.0303 | 10.5329 | 10.5329 | 10.5329 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 11.00 |
Number of hours cooling loads not met | 74.67 |
Number of hours not met | 85.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 353.50 | 133727.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1203.19 | 168606.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 545.70 | 45764.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 194.02 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.52 | 1274.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 591.32 | 37294.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 81.15 | 4079.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 110.66 | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.78 | 4751.13 | 2451.28 | 240337.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.86 | 1313.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.25 | 716.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1692.65 | 5680.48 |
Natural Gas | 1788.84 | 4240.12 |
Additional | 0.00 | 0.00 |
Total | 3481.49 | 9920.60 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 48.10 |
Space Heating | 31.16 |
Space Cooling | 106.05 |
Fans (All) | 52.12 |
Service Water Heating | 8.35 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 500.69 |
Subtotal | 500.69 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 216.06 |
Miscellaneous (All) | 373.73 |
Subtotal | 373.73 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.50 |
Space Heating | 3.56 |
Space Cooling | 12.13 |
Fans (All) | 5.96 |
Service Water Heating | 25.66 |
Receptacle Equipment | 34.65 |
Miscellaneous | 12.53 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7964.67 | 795.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7964.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 795.33 | 0.00 | 0.00 | 0.00 |
Average | 8723.44 | 36.56 | 0.00 | 0.00 | 0.00 |
Sum | 191915.67 | 804.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8656.33 | 103.67 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8729.67 | 30.33 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8396.67 | 363.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 7752.50 | 1007.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8567.50 | 192.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7342.67 | 1417.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8614.17 | 145.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8522.67 | 237.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8742.83 | 17.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8535.33 | 224.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 7859.33 | 900.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 7781.50 | 978.50 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8632.67 | 127.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8598.83 | 161.17 | 0.00 | 0.00 | 0.00 |
Min | 7342.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1417.33 | 0.00 | 0.00 | 0.00 |
Average | 8490.15 | 269.85 | 0.00 | 0.00 | 0.00 |
Sum | 186783.33 | 5936.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 49255.00 | 924.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59150.50 | 5.50 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8947.00 | 30.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 663910.33 | 46506.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1748524.50 | 366904.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4118.17 | 35.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4121.33 | 32.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4117.33 | 36.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100307.00 | 51.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4109.00 | 45.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1047315.67 | 198399.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1033568.50 | 212146.50 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107399.50 | 869.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 103073.50 | 2872.50 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1748524.50 | 366904.50 | 0.00 | 0.00 | 0.00 |
Average | 251211.61 | 37675.44 | 0.00 | 0.00 | 0.00 |
Sum | 5526655.33 | 828859.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290743E+11 | 13060.96 | 31-JAN-21:00 | 17.20 | 12.43 | 0.732962E+10 | 4569.21 | 27-JAN-22:10 | 17.20 | 12.43 |
February | 0.246356E+11 | 12600.56 | 01-FEB-21:00 | 9.40 | 8.81 | 0.629712E+10 | 4490.45 | 01-FEB-22:10 | 8.72 | 8.24 |
March | 0.255421E+11 | 12122.68 | 30-MAR-18:10 | 26.02 | 17.62 | 0.661033E+10 | 4255.10 | 01-MAR-22:10 | 26.02 | 17.62 |
April | 0.220457E+11 | 11957.42 | 14-APR-18:01 | 24.45 | 15.36 | 0.611732E+10 | 3914.36 | 14-APR-22:10 | 17.12 | 12.34 |
May | 0.260842E+11 | 13251.95 | 13-MAY-17:35 | 25.77 | 14.38 | 0.652273E+10 | 4074.07 | 26-MAY-22:10 | 18.12 | 17.79 |
June | 0.291514E+11 | 14152.39 | 25-JUN-10:35 | 29.80 | 23.29 | 0.690193E+10 | 4447.36 | 16-JUN-22:10 | 29.80 | 23.29 |
July | 0.325054E+11 | 15017.60 | 20-JUL-18:10 | 32.12 | 22.73 | 0.748539E+10 | 4685.36 | 28-JUL-22:10 | 17.70 | 17.38 |
August | 0.348521E+11 | 15840.98 | 27-AUG-10:35 | 29.47 | 22.52 | 0.792677E+10 | 4837.09 | 07-AUG-22:10 | 29.47 | 22.52 |
September | 0.364414E+11 | 19598.68 | 28-SEP-21:00 | 15.60 | 13.52 | 0.790427E+10 | 4837.09 | 14-SEP-22:10 | 15.60 | 13.52 |
October | 0.384298E+11 | 20558.48 | 12-OCT-21:00 | 12.20 | 9.05 | 0.819572E+10 | 4839.58 | 12-OCT-23:49 | 9.08 | 6.62 |
November | 0.370398E+11 | 20638.16 | 08-NOV-22:00 | 13.90 | 7.06 | 0.793214E+10 | 4839.03 | 06-NOV-05:49 | 13.90 | 7.06 |
December | 0.339796E+11 | 18522.78 | 01-DEC-21:53 | 3.90 | 0.00 | 0.805131E+10 | 4837.18 | 27-DEC-22:30 | 8.05 | 4.69 |
Annual Sum or Average | 0.369782E+12 | 0.872747E+11 | ||||||||
Minimum of Months | 0.220457E+11 | 11957.42 | 3.90 | 0.00 | 0.611732E+10 | 3914.36 | 8.05 | 4.69 | ||
Maximum of Months | 0.384298E+11 | 20638.16 | 32.12 | 23.29 | 0.819572E+10 | 4839.58 | 29.80 | 23.29 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127282E+10 | 2040.04 | 29-JAN-13:00 | 13.90 | 6.14 | 0.638156E+09 | 431.10 | 31-JAN-22:19 | 14.13 | 10.68 |
February | 0.160545E+10 | 2410.31 | 21-FEB-14:25 | 22.25 | 10.82 | 0.596093E+09 | 488.69 | 28-FEB-22:19 | 18.37 | 10.65 |
March | 0.268129E+10 | 2384.59 | 30-MAR-13:40 | 27.43 | 17.97 | 0.719207E+09 | 491.84 | 13-MAR-22:10 | 27.43 | 17.97 |
April | 0.287106E+10 | 2511.41 | 17-APR-15:13 | 28.90 | 16.41 | 0.721183E+09 | 491.84 | 12-APR-22:10 | 28.90 | 16.41 |
May | 0.325671E+10 | 2032.85 | 16-MAY-18:05 | 28.22 | 17.07 | 0.785026E+09 | 491.84 | 05-MAY-22:10 | 28.22 | 17.07 |
June | 0.374314E+10 | 2267.89 | 13-JUN-18:03 | 31.93 | 21.91 | 0.796368E+09 | 491.84 | 08-JUN-22:10 | 31.93 | 21.91 |
July | 0.419772E+10 | 2572.13 | 07-JUL-18:17 | 33.70 | 23.11 | 0.825696E+09 | 491.84 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.456936E+10 | 2891.29 | 19-AUG-13:40 | 33.70 | 23.70 | 0.837671E+09 | 491.84 | 07-AUG-22:10 | 33.70 | 23.70 |
September | 0.371965E+10 | 3014.25 | 24-SEP-12:30 | 28.60 | 19.85 | 0.779605E+09 | 491.84 | 14-SEP-22:10 | 28.60 | 19.85 |
October | 0.318271E+10 | 3178.90 | 10-OCT-13:30 | 28.85 | 20.88 | 0.748586E+09 | 491.84 | 11-OCT-22:10 | 14.40 | 8.97 |
November | 0.253450E+10 | 2565.01 | 08-NOV-13:40 | 20.20 | 9.59 | 0.674049E+09 | 474.79 | 08-NOV-22:19 | 13.33 | 6.86 |
December | 0.180783E+10 | 2354.86 | 10-DEC-13:00 | 15.60 | 7.72 | 0.655758E+09 | 476.40 | 12-DEC-22:40 | 18.30 | 14.79 |
Annual Sum or Average | 0.354422E+11 | 0.877740E+10 | ||||||||
Minimum of Months | 0.127282E+10 | 2032.85 | 13.90 | 6.14 | 0.596093E+09 | 431.10 | 13.33 | 6.86 | ||
Maximum of Months | 0.456936E+10 | 3178.90 | 33.70 | 23.70 | 0.837671E+09 | 491.84 | 33.70 | 23.70 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241206E+10 | 1317.58 | 31-JAN-21:00 | 17.20 | 12.43 | 0.761543E+09 | 517.79 | 31-JAN-23:10 | 12.22 | 9.67 |
February | 0.236552E+10 | 1453.30 | 28-FEB-21:00 | 20.60 | 11.78 | 0.710619E+09 | 554.54 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.304507E+10 | 1565.65 | 30-MAR-18:10 | 26.02 | 17.62 | 0.844411E+09 | 569.55 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.312447E+10 | 1613.19 | 13-APR-16:04 | 26.60 | 14.97 | 0.838309E+09 | 569.55 | 12-APR-22:10 | 26.60 | 14.97 |
May | 0.342958E+10 | 1703.08 | 19-MAY-21:00 | 23.90 | 16.26 | 0.893460E+09 | 569.55 | 31-MAY-22:10 | 21.73 | 18.83 |
June | 0.358016E+10 | 1840.87 | 27-JUN-21:00 | 27.20 | 20.99 | 0.899557E+09 | 569.55 | 08-JUN-22:10 | 27.20 | 20.99 |
July | 0.379927E+10 | 2007.52 | 07-JUL-21:00 | 30.60 | 22.80 | 0.933172E+09 | 569.55 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.387274E+10 | 2055.06 | 18-AUG-21:00 | 31.10 | 22.83 | 0.946861E+09 | 569.55 | 07-AUG-22:10 | 31.10 | 22.83 |
September | 0.347708E+10 | 1922.83 | 08-SEP-21:00 | 25.60 | 21.61 | 0.888506E+09 | 569.55 | 14-SEP-22:10 | 18.62 | 13.88 |
October | 0.324625E+10 | 1686.05 | 11-OCT-21:00 | 16.10 | 9.61 | 0.872094E+09 | 569.55 | 10-OCT-22:10 | 16.10 | 9.61 |
November | 0.289743E+10 | 1440.39 | 06-NOV-21:00 | 12.20 | 6.19 | 0.806196E+09 | 551.05 | 06-NOV-23:10 | 10.40 | 5.30 |
December | 0.270590E+10 | 1412.74 | 12-DEC-21:00 | 18.30 | 14.62 | 0.790521E+09 | 545.39 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.379555E+11 | 0.101852E+11 | ||||||||
Minimum of Months | 0.236552E+10 | 1317.58 | 12.20 | 6.19 | 0.710619E+09 | 517.79 | 10.40 | 5.30 | ||
Maximum of Months | 0.387274E+10 | 2055.06 | 31.10 | 22.83 | 0.946861E+09 | 569.55 | 31.10 | 22.83 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39500381.65 | 164.53 | 20-JAN-22:00 | 11.70 | 8.29 | 0.170415E+09 | 120.45 | 31-JAN-22:49 | 12.98 | 10.12 |
February | 81512585.68 | 714.82 | 28-FEB-22:00 | 18.90 | 10.96 | 0.163887E+09 | 120.45 | 22-FEB-22:10 | 18.90 | 10.96 |
March | 0.307031E+09 | 1056.82 | 30-MAR-21:00 | 23.90 | 16.89 | 0.200594E+09 | 120.45 | 13-MAR-21:00 | 23.90 | 16.89 |
April | 0.657263E+09 | 1079.13 | 19-APR-21:00 | 18.90 | 16.14 | 0.197446E+09 | 120.45 | 19-APR-21:19 | 18.53 | 16.00 |
May | 0.131330E+10 | 1336.95 | 30-MAY-21:00 | 23.90 | 21.18 | 0.205438E+09 | 120.46 | 10-MAY-03:09 | 23.90 | 21.18 |
June | 0.215294E+10 | 1626.01 | 13-JUN-21:00 | 28.30 | 21.76 | 0.199178E+09 | 120.45 | 14-JUN-21:30 | 26.15 | 20.57 |
July | 0.253186E+10 | 1809.73 | 07-JUL-21:00 | 30.60 | 22.80 | 0.205008E+09 | 120.45 | 17-JUL-21:30 | 25.85 | 20.47 |
August | 0.267559E+10 | 1779.46 | 18-AUG-21:00 | 31.10 | 22.83 | 0.205875E+09 | 120.45 | 02-AUG-21:30 | 31.10 | 22.83 |
September | 0.181597E+10 | 1610.51 | 07-SEP-20:00 | 27.20 | 22.45 | 0.198648E+09 | 120.45 | 07-SEP-21:30 | 25.00 | 21.07 |
October | 0.820963E+09 | 1217.55 | 18-OCT-21:00 | 23.30 | 22.56 | 0.204164E+09 | 120.47 | 12-OCT-23:49 | 23.30 | 22.56 |
November | 0.280423E+09 | 822.84 | 03-NOV-21:00 | 18.30 | 16.18 | 0.193028E+09 | 120.46 | 06-NOV-05:49 | 9.50 | 8.91 |
December | 82314574.03 | 675.98 | 13-DEC-22:00 | 13.30 | 12.92 | 0.186145E+09 | 120.45 | 11-DEC-22:10 | 13.30 | 12.92 |
Annual Sum or Average | 0.127587E+11 | 0.232983E+10 | ||||||||
Minimum of Months | 39500381.65 | 164.53 | 11.70 | 8.29 | 0.163887E+09 | 120.45 | 9.50 | 8.91 | ||
Maximum of Months | 0.267559E+10 | 1809.73 | 31.10 | 22.83 | 0.205875E+09 | 120.47 | 31.10 | 22.83 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367405E+09 | 676.45 | 31-JAN-21:00 | 17.20 | 12.43 | 0.116766E+09 | 71.26 | 31-JAN-23:10 | 12.22 | 9.67 |
February | 0.716016E+09 | 748.09 | 28-FEB-11:35 | 21.67 | 12.20 | 0.106191E+09 | 75.39 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.147556E+10 | 850.81 | 30-MAR-18:10 | 26.02 | 17.62 | 0.120832E+09 | 79.11 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.165837E+10 | 915.86 | 13-APR-16:04 | 26.60 | 14.97 | 0.120681E+09 | 79.36 | 18-APR-22:10 | 19.32 | 14.41 |
May | 0.190622E+10 | 942.22 | 16-MAY-16:56 | 28.90 | 17.49 | 0.130836E+09 | 82.16 | 19-MAY-22:10 | 21.93 | 15.69 |
June | 0.203262E+10 | 1007.94 | 25-JUN-10:35 | 29.80 | 23.29 | 0.134619E+09 | 85.72 | 28-JUN-22:10 | 26.10 | 21.34 |
July | 0.216783E+10 | 1036.14 | 08-JUL-10:35 | 33.17 | 24.62 | 0.141217E+09 | 87.87 | 07-JUL-22:10 | 33.17 | 24.62 |
August | 0.218868E+10 | 1040.97 | 19-AUG-10:35 | 32.03 | 24.19 | 0.142977E+09 | 87.92 | 18-AUG-22:10 | 32.03 | 24.19 |
September | 0.194495E+10 | 992.01 | 09-SEP-10:35 | 30.03 | 23.84 | 0.131593E+09 | 85.51 | 07-SEP-22:10 | 30.03 | 23.84 |
October | 0.174230E+10 | 879.69 | 11-OCT-10:35 | 24.67 | 19.78 | 0.126127E+09 | 81.20 | 18-OCT-22:10 | 22.80 | 22.03 |
November | 0.141662E+10 | 789.17 | 05-NOV-10:35 | 18.33 | 17.01 | 0.116324E+09 | 76.41 | 03-NOV-22:10 | 18.33 | 17.01 |
December | 0.885094E+09 | 748.90 | 13-DEC-11:35 | 19.80 | 17.47 | 0.117314E+09 | 74.75 | 13-DEC-23:10 | 12.62 | 12.25 |
Annual Sum or Average | 0.185017E+11 | 0.150548E+10 | ||||||||
Minimum of Months | 0.367405E+09 | 676.45 | 17.20 | 12.20 | 0.106191E+09 | 71.26 | 12.22 | 9.67 | ||
Maximum of Months | 0.218868E+10 | 1040.97 | 33.17 | 24.62 | 0.142977E+09 | 87.92 | 33.17 | 24.62 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.469543E+11 | 37490.09 | 31-JAN-21:00 | 17.20 | 12.43 | 0.649368E+09 | 383.51 | 27-JAN-22:19 | 17.20 | 12.43 |
February | 0.432792E+11 | 37983.67 | 28-FEB-21:00 | 20.60 | 11.78 | 0.587083E+09 | 382.19 | 02-FEB-22:10 | 20.60 | 11.78 |
March | 0.496566E+11 | 38382.08 | 30-MAR-20:00 | 24.40 | 16.98 | 0.652385E+09 | 381.59 | 28-MAR-21:19 | 24.40 | 16.98 |
April | 0.488196E+11 | 38529.37 | 17-APR-20:00 | 22.80 | 15.38 | 0.629470E+09 | 381.61 | 19-APR-21:19 | 18.53 | 16.00 |
May | 0.515418E+11 | 38869.63 | 19-MAY-20:00 | 25.60 | 17.28 | 0.650710E+09 | 382.76 | 10-MAY-03:09 | 25.60 | 17.28 |
June | 0.509166E+11 | 39218.17 | 13-JUN-20:00 | 29.40 | 21.98 | 0.630879E+09 | 381.70 | 16-JUN-21:10 | 23.80 | 21.09 |
July | 0.527729E+11 | 39433.14 | 07-JUL-20:00 | 31.10 | 23.22 | 0.649346E+09 | 381.67 | 25-JUL-21:19 | 22.80 | 21.95 |
August | 0.531145E+11 | 39339.09 | 18-AUG-20:00 | 31.70 | 22.32 | 0.652102E+09 | 381.72 | 01-AUG-21:10 | 31.70 | 22.32 |
September | 0.500775E+11 | 39109.19 | 07-SEP-20:00 | 27.20 | 22.45 | 0.629207E+09 | 382.07 | 15-SEP-21:10 | 24.82 | 18.06 |
October | 0.502237E+11 | 38520.36 | 10-OCT-20:00 | 22.20 | 19.19 | 0.649648E+09 | 383.00 | 12-OCT-23:49 | 9.08 | 6.62 |
November | 0.475948E+11 | 37890.37 | 03-NOV-20:00 | 18.90 | 16.38 | 0.628129E+09 | 382.75 | 06-NOV-05:49 | 9.50 | 8.91 |
December | 0.478180E+11 | 37746.96 | 12-DEC-21:00 | 18.30 | 14.62 | 0.649353E+09 | 382.83 | 07-DEC-00:00 | 18.30 | 14.62 |
Annual Sum or Average | 0.592769E+12 | 0.765768E+10 | ||||||||
Minimum of Months | 0.432792E+11 | 37490.09 | 17.20 | 11.78 | 0.587083E+09 | 381.59 | 9.08 | 6.62 | ||
Maximum of Months | 0.531145E+11 | 39433.14 | 31.70 | 23.22 | 0.652385E+09 | 383.51 | 31.70 | 22.32 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163607E+11 | 10255.21 | 29-JAN-11:35 | 12.43 | 5.39 | 0.853938E+10 | 5772.25 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.161403E+11 | 10662.31 | 26-FEB-11:35 | 22.07 | 11.70 | 0.792611E+10 | 6090.76 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.206022E+11 | 10888.89 | 30-MAR-15:11 | 27.80 | 17.21 | 0.922026E+10 | 6278.68 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.207194E+11 | 11902.71 | 13-APR-16:04 | 26.60 | 14.97 | 0.896709E+10 | 6200.57 | 17-APR-22:10 | 19.72 | 13.80 |
May | 0.224971E+11 | 11330.74 | 13-MAY-15:11 | 26.87 | 14.67 | 0.944908E+10 | 6242.02 | 18-MAY-21:40 | 22.07 | 16.54 |
June | 0.231993E+11 | 11086.41 | 24-JUN-17:40 | 32.40 | 22.18 | 0.946691E+10 | 6431.34 | 13-JUN-22:10 | 32.40 | 22.18 |
July | 0.246184E+11 | 11643.69 | 08-JUL-17:20 | 34.40 | 23.36 | 0.987251E+10 | 6460.40 | 14-JUL-22:10 | 27.80 | 21.43 |
August | 0.253750E+11 | 11651.50 | 02-AUG-18:10 | 32.80 | 23.11 | 0.101263E+11 | 6460.69 | 18-AUG-22:30 | 29.15 | 23.19 |
September | 0.230138E+11 | 11607.54 | 24-SEP-10:35 | 27.23 | 19.06 | 0.946311E+10 | 6460.40 | 25-SEP-22:10 | 23.03 | 19.17 |
October | 0.219792E+11 | 11440.60 | 10-OCT-15:35 | 29.63 | 20.59 | 0.944428E+10 | 6416.77 | 10-OCT-21:40 | 21.10 | 18.64 |
November | 0.197768E+11 | 11089.65 | 11-NOV-11:35 | 18.50 | 11.57 | 0.880072E+10 | 6064.85 | 08-NOV-22:40 | 18.50 | 11.57 |
December | 0.182472E+11 | 10638.72 | 10-DEC-11:35 | 12.93 | 6.50 | 0.876616E+10 | 6078.81 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.252529E+12 | 0.110042E+12 | ||||||||
Minimum of Months | 0.161403E+11 | 10255.21 | 12.43 | 5.39 | 0.792611E+10 | 5772.25 | 13.37 | 10.31 | ||
Maximum of Months | 0.253750E+11 | 11902.71 | 34.40 | 23.36 | 0.101263E+11 | 6460.69 | 32.40 | 23.19 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.562227E+11 | 28371.00 | 31-JAN-21:00 | 17.20 | 12.43 | 0.272137E+11 | 18432.21 | 31-JAN-23:10 | 12.22 | 9.67 |
February | 0.537901E+11 | 30278.76 | 28-FEB-21:00 | 20.60 | 11.78 | 0.252416E+11 | 19185.82 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.655319E+11 | 32354.75 | 30-MAR-21:07 | 23.72 | 16.82 | 0.294692E+11 | 19186.00 | 29-MAR-22:10 | 23.72 | 16.82 |
April | 0.658591E+11 | 33401.67 | 13-APR-16:04 | 26.60 | 14.97 | 0.288452E+11 | 19186.13 | 12-APR-22:10 | 26.60 | 14.97 |
May | 0.712889E+11 | 33684.24 | 13-MAY-17:35 | 25.77 | 14.38 | 0.304612E+11 | 19186.10 | 03-MAY-22:10 | 25.77 | 14.38 |
June | 0.734848E+11 | 35940.64 | 13-JUN-22:00 | 27.20 | 20.99 | 0.303528E+11 | 19186.17 | 08-JUN-22:10 | 27.20 | 20.99 |
July | 0.779094E+11 | 38119.75 | 07-JUL-21:10 | 30.40 | 22.79 | 0.314309E+11 | 19186.16 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.797003E+11 | 39155.72 | 18-AUG-21:10 | 30.82 | 22.88 | 0.318347E+11 | 19186.08 | 07-AUG-22:10 | 30.82 | 22.88 |
September | 0.723927E+11 | 37376.55 | 07-SEP-21:10 | 25.40 | 21.43 | 0.302387E+11 | 19186.10 | 14-SEP-22:10 | 18.62 | 13.88 |
October | 0.693707E+11 | 34452.06 | 10-OCT-21:10 | 21.10 | 18.77 | 0.302504E+11 | 19186.00 | 10-OCT-22:10 | 21.02 | 18.59 |
November | 0.632343E+11 | 30095.54 | 08-NOV-21:00 | 15.00 | 7.39 | 0.284024E+11 | 19183.29 | 08-NOV-22:00 | 12.20 | 6.43 |
December | 0.607379E+11 | 29887.64 | 12-DEC-21:00 | 18.30 | 14.62 | 0.282076E+11 | 19185.56 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.809523E+12 | 0.351948E+12 | ||||||||
Minimum of Months | 0.537901E+11 | 28371.00 | 15.00 | 7.39 | 0.252416E+11 | 18432.21 | 12.20 | 6.43 | ||
Maximum of Months | 0.797003E+11 | 39155.72 | 30.82 | 22.88 | 0.318347E+11 | 19186.17 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52691367.07 | 3105.45 | 28-JAN-16:11 | 12.20 | 4.56 | 94283868.03 | 56.69 | 30-JAN-00:00 | 5.60 | 1.58 |
February | 0.191671E+09 | 3203.77 | 27-FEB-16:11 | 22.60 | 11.36 | 86160655.06 | 56.69 | 21-FEB-22:19 | 22.60 | 11.36 |
March | 0.644006E+09 | 3166.72 | 10-MAR-16:11 | 20.20 | 8.87 | 98052665.90 | 59.80 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.108108E+10 | 3199.05 | 09-APR-18:01 | 20.45 | 11.08 | 95518185.54 | 56.69 | 17-APR-23:19 | 18.13 | 13.51 |
May | 0.152756E+10 | 3185.27 | 09-MAY-18:01 | 19.63 | 9.69 | 99229496.38 | 56.69 | 04-MAY-21:49 | 19.63 | 9.69 |
June | 0.201472E+10 | 2803.94 | 26-JUN-18:02 | 23.22 | 21.66 | 96332586.84 | 56.69 | 26-JUN-03:39 | 23.22 | 21.66 |
July | 0.225024E+10 | 2806.84 | 27-JUL-15:12 | 23.67 | 20.88 | 99469807.17 | 56.70 | 21-JUL-21:19 | 23.67 | 20.88 |
August | 0.236568E+10 | 2800.70 | 07-AUG-18:02 | 25.10 | 21.19 | 99634357.99 | 56.69 | 18-AUG-04:19 | 23.30 | 21.80 |
September | 0.162034E+10 | 2851.77 | 09-SEP-18:02 | 23.80 | 21.22 | 95981729.66 | 56.69 | 24-SEP-23:49 | 22.80 | 18.61 |
October | 0.882593E+09 | 3020.44 | 31-OCT-18:01 | 12.20 | 6.42 | 98128990.47 | 56.69 | 10-OCT-22:30 | 12.20 | 6.42 |
November | 0.338545E+09 | 3154.71 | 14-NOV-16:11 | 18.87 | 9.04 | 94054017.69 | 56.69 | 02-NOV-21:30 | 18.87 | 9.04 |
December | 0.100433E+09 | 3110.81 | 09-DEC-16:11 | 13.87 | 6.13 | 95275366.11 | 56.69 | 13-DEC-00:30 | 17.25 | 14.56 |
Annual Sum or Average | 0.130696E+11 | 0.115212E+10 | ||||||||
Minimum of Months | 52691367.07 | 2800.70 | 12.20 | 4.56 | 86160655.06 | 56.69 | 5.60 | 1.58 | ||
Maximum of Months | 0.236568E+10 | 3203.77 | 25.10 | 21.66 | 99634357.99 | 59.80 | 23.67 | 21.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14891626.96 | 1580.23 | 14-JAN-16:17 | 3.53 | -1.7 | 92997242.94 | 56.83 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 68781055.01 | 2866.06 | 24-FEB-19:01 | 12.52 | 5.38 | 85856479.84 | 66.29 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.346070E+09 | 3063.09 | 18-MAR-18:01 | 10.82 | 2.80 | 99641265.91 | 71.47 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.769071E+09 | 3304.88 | 26-APR-18:41 | 14.60 | 7.53 | 0.100010E+09 | 74.37 | 14-APR-21:30 | 14.60 | 7.53 |
May | 0.126429E+10 | 3320.03 | 09-MAY-20:41 | 13.68 | 6.54 | 0.105014E+09 | 75.51 | 09-MAY-18:10 | 13.68 | 6.54 |
June | 0.187346E+10 | 2814.52 | 16-JUN-21:51 | 23.30 | 20.62 | 99892622.95 | 81.41 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.209845E+10 | 2822.12 | 02-JUL-21:51 | 22.80 | 18.09 | 0.102797E+09 | 79.45 | 18-JUL-21:10 | 22.80 | 21.57 |
August | 0.214785E+10 | 2850.07 | 08-AUG-18:01 | 26.88 | 23.69 | 0.101953E+09 | 75.26 | 23-AUG-21:19 | 23.90 | 23.53 |
September | 0.128187E+10 | 3075.59 | 18-SEP-16:01 | 25.40 | 17.60 | 0.100160E+09 | 74.83 | 11-SEP-21:00 | 25.40 | 17.60 |
October | 0.482690E+09 | 2936.06 | 15-OCT-16:21 | 24.15 | 17.28 | 0.100914E+09 | 71.88 | 10-OCT-21:10 | 24.15 | 17.28 |
November | 0.125284E+09 | 2806.72 | 06-NOV-19:12 | 13.87 | 6.89 | 93712071.19 | 62.26 | 02-NOV-21:40 | 13.87 | 6.89 |
December | 31348744.01 | 2834.70 | 09-DEC-16:11 | 13.87 | 6.13 | 93903544.38 | 60.14 | 12-DEC-22:19 | 18.30 | 14.70 |
Annual Sum or Average | 0.105041E+11 | 0.117685E+10 | ||||||||
Minimum of Months | 14891626.96 | 1580.23 | 3.53 | -1.7 | 85856479.84 | 56.83 | 13.68 | 6.54 | ||
Maximum of Months | 0.214785E+10 | 3320.03 | 26.88 | 23.69 | 0.105014E+09 | 81.41 | 25.40 | 23.53 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23710032.30 | 261.87 | 29-JAN-13:30 | 14.45 | 6.22 | 0.00 | 0.00 | 01-JAN-00:10 | 14.45 | 6.22 |
February | 77216068.81 | 373.43 | 26-FEB-14:25 | 24.70 | 12.65 | 0.00 | 0.00 | 01-FEB-00:10 | 24.70 | 12.65 |
March | 0.214517E+09 | 350.98 | 13-MAR-16:10 | 24.40 | 14.19 | 0.00 | 0.00 | 01-MAR-00:10 | 24.40 | 14.19 |
April | 0.254463E+09 | 328.39 | 15-APR-13:50 | 27.62 | 15.00 | 0.00 | 0.00 | 01-APR-00:10 | 27.62 | 15.00 |
May | 0.326443E+09 | 268.99 | 19-MAY-17:20 | 30.20 | 19.07 | 0.00 | 0.00 | 01-MAY-00:10 | 30.20 | 19.07 |
June | 0.428364E+09 | 305.81 | 13-JUN-17:20 | 32.60 | 22.18 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 22.18 |
July | 0.500537E+09 | 343.71 | 08-JUL-17:30 | 34.40 | 23.36 | 0.00 | 0.00 | 01-JUL-00:10 | 34.40 | 23.36 |
August | 0.581155E+09 | 383.72 | 19-AUG-13:40 | 33.70 | 23.70 | 0.00 | 0.00 | 01-AUG-00:10 | 33.70 | 23.70 |
September | 0.446870E+09 | 449.80 | 24-SEP-12:40 | 28.70 | 19.86 | 0.00 | 0.00 | 01-SEP-00:10 | 28.70 | 19.86 |
October | 0.333999E+09 | 486.96 | 10-OCT-13:30 | 28.85 | 20.88 | 0.00 | 0.00 | 01-OCT-00:10 | 28.85 | 20.88 |
November | 0.206245E+09 | 429.80 | 15-NOV-14:00 | 21.10 | 11.33 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 11.33 |
December | 99128237.58 | 409.84 | 10-DEC-14:30 | 17.50 | 8.24 | 0.00 | 0.00 | 01-DEC-00:10 | 17.50 | 8.24 |
Annual Sum or Average | 0.349265E+10 | 0.00 | ||||||||
Minimum of Months | 23710032.30 | 261.87 | 14.45 | 6.22 | 0.00 | 0.00 | 14.45 | 6.22 | ||
Maximum of Months | 0.581155E+09 | 486.96 | 34.40 | 23.70 | 0.00 | 0.00 | 34.40 | 23.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47282939.23 | 845.41 | 01-JAN-09:02 | 11.78 | 10.88 | 94649865.79 | 63.27 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.114604E+09 | 1064.09 | 28-FEB-22:52 | 17.30 | 10.02 | 86690315.28 | 68.13 | 28-FEB-22:00 | 17.30 | 10.02 |
March | 0.282413E+09 | 1062.26 | 31-MAR-20:12 | 13.87 | 8.46 | 98403365.10 | 69.93 | 28-MAR-21:10 | 13.87 | 8.46 |
April | 0.422941E+09 | 1061.81 | 09-APR-20:11 | 13.70 | 8.28 | 98327087.29 | 72.60 | 24-APR-21:10 | 13.22 | 9.86 |
May | 0.591770E+09 | 1139.75 | 09-MAY-20:41 | 13.68 | 6.54 | 0.103357E+09 | 73.43 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.770776E+09 | 1024.35 | 03-JUN-15:12 | 30.00 | 18.78 | 98890387.84 | 77.38 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.838594E+09 | 1024.98 | 18-JUL-15:12 | 31.70 | 22.33 | 0.102083E+09 | 76.20 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.833349E+09 | 1027.39 | 17-AUG-15:12 | 33.30 | 24.03 | 0.101298E+09 | 74.58 | 31-AUG-21:19 | 21.67 | 19.98 |
September | 0.587799E+09 | 1026.93 | 04-SEP-18:01 | 26.83 | 21.37 | 99318315.27 | 75.00 | 01-SEP-21:10 | 26.83 | 21.37 |
October | 0.344577E+09 | 1073.75 | 11-OCT-21:51 | 14.40 | 8.97 | 99827353.97 | 72.19 | 18-OCT-21:10 | 23.22 | 22.46 |
November | 0.199584E+09 | 1011.82 | 28-NOV-19:02 | 11.52 | 4.78 | 94148098.92 | 67.57 | 03-NOV-21:49 | 11.52 | 4.78 |
December | 86934150.00 | 870.93 | 31-DEC-09:02 | 5.68 | 5.64 | 95444430.50 | 64.41 | 12-DEC-22:00 | 5.68 | 5.64 |
Annual Sum or Average | 0.512062E+10 | 0.117244E+10 | ||||||||
Minimum of Months | 47282939.23 | 845.41 | 5.68 | 4.78 | 86690315.28 | 63.27 | 5.68 | 4.78 | ||
Maximum of Months | 0.838594E+09 | 1139.75 | 33.30 | 24.03 | 0.103357E+09 | 77.38 | 26.83 | 22.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50501821.18 | 2765.13 | 29-JAN-16:11 | 16.33 | 6.57 | 94389028.58 | 56.69 | 30-JAN-00:00 | 5.60 | 1.58 |
February | 0.209494E+09 | 2903.57 | 27-FEB-16:11 | 22.60 | 11.36 | 86342150.17 | 56.69 | 21-FEB-22:00 | 22.60 | 11.36 |
March | 0.581546E+09 | 2876.92 | 10-MAR-16:11 | 20.20 | 8.87 | 98213312.81 | 56.92 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.104606E+10 | 2878.10 | 09-APR-18:01 | 20.45 | 11.08 | 95800047.00 | 56.69 | 19-APR-21:40 | 18.17 | 15.86 |
May | 0.156176E+10 | 2876.90 | 09-MAY-18:01 | 19.63 | 9.69 | 99444924.47 | 56.69 | 06-MAY-23:40 | 19.63 | 9.69 |
June | 0.206120E+10 | 2643.20 | 05-JUN-08:61 | 23.77 | 18.74 | 96444975.76 | 56.69 | 29-JUN-02:49 | 23.30 | 20.62 |
July | 0.232759E+10 | 2675.45 | 21-JUL-08:61 | 26.15 | 22.30 | 99524289.98 | 56.69 | 26-JUL-01:39 | 22.20 | 21.84 |
August | 0.238222E+10 | 2650.96 | 01-AUG-08:61 | 26.38 | 22.61 | 99672160.31 | 56.70 | 16-AUG-21:19 | 28.33 | 23.63 |
September | 0.162861E+10 | 2603.70 | 09-SEP-08:62 | 25.55 | 21.79 | 96072942.66 | 56.69 | 12-SEP-00:40 | 21.30 | 19.62 |
October | 0.861681E+09 | 2591.81 | 31-OCT-18:01 | 12.20 | 6.42 | 98296660.95 | 56.69 | 10-OCT-22:30 | 12.20 | 6.42 |
November | 0.316750E+09 | 2851.42 | 14-NOV-16:11 | 18.87 | 9.04 | 94270444.02 | 56.69 | 02-NOV-21:49 | 18.87 | 9.04 |
December | 99784552.92 | 2726.06 | 09-DEC-16:11 | 13.87 | 6.13 | 95424940.65 | 56.69 | 12-DEC-22:19 | 18.30 | 14.70 |
Annual Sum or Average | 0.131272E+11 | 0.115390E+10 | ||||||||
Minimum of Months | 50501821.18 | 2591.81 | 12.20 | 6.13 | 86342150.17 | 56.69 | 5.60 | 1.58 | ||
Maximum of Months | 0.238222E+10 | 2903.57 | 26.38 | 22.61 | 99672160.31 | 56.92 | 28.33 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15889666.76 | 1704.60 | 28-JAN-09:06 | -1.1 | -3.4 | 93029300.36 | 57.43 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 89771089.17 | 2325.10 | 27-FEB-22:42 | 14.60 | 8.14 | 85792381.98 | 65.59 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.324878E+09 | 2603.81 | 12-MAR-19:01 | 14.22 | 6.79 | 98870744.47 | 68.29 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.759208E+09 | 2787.20 | 14-APR-08:51 | 19.40 | 14.17 | 99392108.97 | 71.88 | 17-APR-21:00 | 20.00 | 13.85 |
May | 0.129529E+10 | 2948.34 | 16-MAY-08:51 | 21.70 | 15.85 | 0.104814E+09 | 75.66 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.189089E+10 | 2966.36 | 04-JUN-08:51 | 24.40 | 18.28 | 0.100250E+09 | 78.16 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.214045E+10 | 2780.81 | 17-JUL-08:51 | 26.10 | 21.47 | 0.103393E+09 | 79.89 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.214599E+10 | 2829.34 | 26-AUG-08:51 | 24.40 | 19.19 | 0.102250E+09 | 76.64 | 07-AUG-21:00 | 24.40 | 19.19 |
September | 0.127589E+10 | 2857.45 | 15-SEP-08:51 | 21.70 | 14.94 | 0.100241E+09 | 74.39 | 01-SEP-21:10 | 21.70 | 14.94 |
October | 0.488825E+09 | 2594.07 | 11-OCT-15:11 | 26.83 | 19.13 | 0.100318E+09 | 71.35 | 17-OCT-21:10 | 23.22 | 20.61 |
November | 0.128716E+09 | 2451.01 | 11-NOV-09:01 | 9.63 | 7.91 | 93275758.37 | 62.67 | 03-NOV-21:30 | 9.63 | 7.91 |
December | 29857736.89 | 1760.52 | 02-DEC-09:04 | -0.8 | -3.4 | 93873402.92 | 59.61 | 12-DEC-22:19 | 18.30 | 14.70 |
Annual Sum or Average | 0.105857E+11 | 0.117550E+10 | ||||||||
Minimum of Months | 15889666.76 | 1704.60 | -1.1 | -3.4 | 85792381.98 | 57.43 | 9.63 | 7.91 | ||
Maximum of Months | 0.214599E+10 | 2966.36 | 26.83 | 21.47 | 0.104814E+09 | 79.89 | 24.40 | 21.95 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147442E+10 | 1405.01 | 31-JAN-19:00 | 17.80 | 12.69 | 0.120066E+10 | 736.12 | 31-JAN-22:49 | 12.98 | 10.12 |
February | 0.193439E+10 | 1643.21 | 27-FEB-19:10 | 19.82 | 10.52 | 0.110394E+10 | 801.15 | 28-FEB-22:49 | 17.57 | 10.18 |
March | 0.349434E+10 | 1842.95 | 30-MAR-18:10 | 26.02 | 17.62 | 0.129396E+10 | 829.98 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.379980E+10 | 2044.18 | 13-APR-16:04 | 26.60 | 14.97 | 0.132062E+10 | 864.75 | 19-APR-21:49 | 17.98 | 15.78 |
May | 0.424840E+10 | 2079.42 | 16-MAY-16:56 | 28.90 | 17.49 | 0.142517E+10 | 882.60 | 19-MAY-22:10 | 21.93 | 15.69 |
June | 0.447962E+10 | 2183.95 | 25-JUN-10:35 | 29.80 | 23.29 | 0.145845E+10 | 924.11 | 29-JUN-21:49 | 25.18 | 21.75 |
July | 0.478657E+10 | 2255.49 | 08-JUL-17:50 | 34.40 | 23.36 | 0.153369E+10 | 938.93 | 21-JUL-21:49 | 27.98 | 21.29 |
August | 0.481378E+10 | 2268.13 | 19-AUG-10:35 | 32.03 | 24.19 | 0.154832E+10 | 948.32 | 18-AUG-21:49 | 32.03 | 24.19 |
September | 0.428803E+10 | 2159.21 | 09-SEP-10:35 | 30.03 | 23.84 | 0.142379E+10 | 913.77 | 08-SEP-21:49 | 30.03 | 23.84 |
October | 0.377726E+10 | 1916.75 | 11-OCT-18:10 | 21.73 | 13.14 | 0.134645E+10 | 863.73 | 11-OCT-21:49 | 14.68 | 9.09 |
November | 0.306456E+10 | 1635.04 | 11-NOV-11:35 | 18.50 | 11.57 | 0.120803E+10 | 784.63 | 08-NOV-22:49 | 18.50 | 11.57 |
December | 0.217778E+10 | 1513.37 | 12-DEC-11:35 | 19.83 | 16.13 | 0.120815E+10 | 765.56 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.423389E+11 | 0.160712E+11 | ||||||||
Minimum of Months | 0.147442E+10 | 1405.01 | 17.80 | 10.52 | 0.110394E+10 | 736.12 | 12.98 | 9.09 | ||
Maximum of Months | 0.481378E+10 | 2268.13 | 34.40 | 24.19 | 0.154832E+10 | 948.32 | 32.03 | 24.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39129365.57 | 3253.95 | 28-JAN-16:11 | 12.20 | 4.56 | 93569276.10 | 56.69 | 30-JAN-00:00 | 5.60 | 1.58 |
February | 0.169172E+09 | 3372.19 | 27-FEB-16:11 | 22.60 | 11.36 | 85587752.88 | 56.69 | 28-FEB-22:49 | 17.57 | 10.18 |
March | 0.593767E+09 | 3330.69 | 10-MAR-16:11 | 20.20 | 8.87 | 97674746.69 | 58.34 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.105605E+10 | 3370.41 | 09-APR-18:01 | 20.45 | 11.08 | 95316074.25 | 56.69 | 12-APR-21:00 | 17.80 | 13.32 |
May | 0.155683E+10 | 3345.76 | 09-MAY-18:01 | 19.63 | 9.69 | 99130816.04 | 56.69 | 08-MAY-21:40 | 19.63 | 9.69 |
June | 0.207755E+10 | 2909.72 | 26-JUN-18:02 | 23.22 | 21.66 | 96290633.55 | 56.69 | 28-JUN-00:49 | 23.98 | 20.50 |
July | 0.232859E+10 | 2963.58 | 07-JUL-18:02 | 33.80 | 23.16 | 99435163.43 | 56.69 | 14-JUL-01:39 | 23.90 | 21.73 |
August | 0.244377E+10 | 2961.74 | 18-AUG-18:02 | 33.72 | 23.57 | 99615858.24 | 56.69 | 08-AUG-22:49 | 33.72 | 23.57 |
September | 0.159440E+10 | 2976.85 | 09-SEP-18:02 | 23.80 | 21.22 | 95855123.47 | 56.69 | 28-SEP-23:30 | 13.60 | 12.34 |
October | 0.807406E+09 | 3189.82 | 31-OCT-18:01 | 12.20 | 6.42 | 97749366.53 | 56.70 | 05-OCT-02:30 | 12.20 | 6.42 |
November | 0.285189E+09 | 3314.26 | 14-NOV-16:11 | 18.87 | 9.04 | 93607445.40 | 56.70 | 06-NOV-01:49 | 18.87 | 9.04 |
December | 79482653.48 | 3263.57 | 09-DEC-16:11 | 13.87 | 6.13 | 94554197.46 | 56.69 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.130313E+11 | 0.114839E+10 | ||||||||
Minimum of Months | 39129365.57 | 2909.72 | 12.20 | 4.56 | 85587752.88 | 56.69 | 5.60 | 1.58 | ||
Maximum of Months | 0.244377E+10 | 3372.19 | 33.80 | 23.57 | 99615858.24 | 58.34 | 33.72 | 23.57 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10090810.58 | 897.20 | 10-JAN-16:14 | 4.80 | 2.02 | 92447784.57 | 56.69 | 30-JAN-00:00 | 5.60 | 1.58 |
February | 54245221.30 | 2992.37 | 24-FEB-19:01 | 12.52 | 5.38 | 85404034.57 | 66.29 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.304764E+09 | 3222.17 | 12-MAR-19:01 | 14.22 | 6.79 | 99247716.87 | 71.78 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.751152E+09 | 3486.31 | 26-APR-18:41 | 14.60 | 7.53 | 0.100151E+09 | 76.00 | 14-APR-21:30 | 14.60 | 7.53 |
May | 0.132364E+10 | 3569.49 | 09-MAY-20:41 | 13.68 | 6.54 | 0.105129E+09 | 78.76 | 09-MAY-18:10 | 13.68 | 6.54 |
June | 0.196738E+10 | 2937.67 | 07-JUN-21:51 | 17.80 | 12.14 | 99703281.87 | 82.92 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.220830E+10 | 2962.71 | 02-JUL-21:51 | 22.80 | 18.09 | 0.102528E+09 | 79.59 | 18-JUL-21:10 | 22.80 | 21.57 |
August | 0.224569E+10 | 2972.18 | 08-AUG-18:01 | 26.88 | 23.69 | 0.101731E+09 | 74.94 | 07-AUG-21:00 | 26.88 | 23.69 |
September | 0.128124E+10 | 3216.35 | 18-SEP-16:01 | 25.40 | 17.60 | 99816688.71 | 74.46 | 11-SEP-21:00 | 25.40 | 17.60 |
October | 0.418934E+09 | 3140.69 | 15-OCT-16:21 | 24.15 | 17.28 | 0.100450E+09 | 71.84 | 10-OCT-21:19 | 24.15 | 17.28 |
November | 92620211.21 | 2624.77 | 06-NOV-19:12 | 13.87 | 6.89 | 93087638.23 | 61.58 | 02-NOV-21:40 | 13.87 | 6.89 |
December | 21897816.41 | 1750.50 | 07-DEC-16:11 | 14.80 | 6.67 | 93158376.09 | 58.77 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.106800E+11 | 0.117285E+10 | ||||||||
Minimum of Months | 10090810.58 | 897.20 | 4.80 | 2.02 | 85404034.57 | 56.69 | 5.60 | 1.58 | ||
Maximum of Months | 0.224569E+10 | 3569.49 | 26.88 | 23.69 | 0.105129E+09 | 82.92 | 26.88 | 23.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175183E+09 | 1698.52 | 29-JAN-16:11 | 16.33 | 6.57 | 96218974.70 | 59.68 | 11-JAN-22:10 | 16.33 | 6.57 |
February | 0.266694E+09 | 1712.10 | 28-FEB-19:01 | 21.52 | 12.04 | 87510492.02 | 61.17 | 16-FEB-22:49 | 21.52 | 12.04 |
March | 0.548805E+09 | 1728.23 | 10-MAR-16:11 | 20.20 | 8.87 | 98412162.74 | 62.58 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.680392E+09 | 1712.40 | 09-APR-18:01 | 20.45 | 11.08 | 95513981.25 | 56.69 | 20-APR-21:00 | 18.90 | 15.41 |
May | 0.873950E+09 | 1708.23 | 10-MAY-18:01 | 20.92 | 10.48 | 99141804.95 | 56.69 | 16-MAY-22:00 | 21.70 | 15.85 |
June | 0.111644E+10 | 1533.76 | 15-JUN-18:02 | 25.40 | 20.43 | 96282736.82 | 56.69 | 12-JUN-21:10 | 25.40 | 20.43 |
July | 0.127552E+10 | 1547.45 | 27-JUL-15:12 | 23.67 | 20.88 | 99420243.35 | 56.70 | 31-JUL-21:10 | 26.05 | 23.10 |
August | 0.142201E+10 | 1543.34 | 08-AUG-18:01 | 26.88 | 23.69 | 99623680.42 | 56.70 | 01-AUG-21:00 | 26.88 | 23.69 |
September | 0.106983E+10 | 1550.56 | 04-SEP-18:01 | 26.83 | 21.37 | 95961825.34 | 56.69 | 09-SEP-23:49 | 22.20 | 20.70 |
October | 0.776107E+09 | 1692.77 | 12-OCT-18:01 | 17.23 | 10.36 | 98490288.45 | 56.69 | 16-OCT-22:30 | 20.00 | 17.29 |
November | 0.507051E+09 | 1726.50 | 14-NOV-16:11 | 18.87 | 9.04 | 95132936.19 | 58.03 | 08-NOV-00:49 | 18.87 | 9.04 |
December | 0.292240E+09 | 1705.89 | 19-DEC-16:11 | 14.23 | 5.16 | 97024719.52 | 64.30 | 10-DEC-00:20 | 14.23 | 5.16 |
Annual Sum or Average | 0.900422E+10 | 0.115873E+10 | ||||||||
Minimum of Months | 0.175183E+09 | 1533.76 | 14.23 | 5.16 | 87510492.02 | 56.69 | 14.23 | 5.16 | ||
Maximum of Months | 0.142201E+10 | 1728.23 | 26.88 | 23.69 | 99623680.42 | 64.30 | 26.88 | 23.69 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.346506E+11 | 17549.58 | 19-JAN-23:10 | 18.22 | 16.49 | 0.161195E+11 | 11121.84 | 19-JAN-23:10 | 18.22 | 16.49 |
February | 0.330808E+11 | 18377.68 | 28-FEB-22:20 | 18.37 | 10.65 | 0.149154E+11 | 11348.55 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.401028E+11 | 20716.50 | 30-MAR-21:07 | 23.72 | 16.82 | 0.172635E+11 | 11348.79 | 29-MAR-22:10 | 23.72 | 16.82 |
April | 0.409495E+11 | 21012.23 | 13-APR-16:04 | 26.60 | 14.97 | 0.170081E+11 | 11349.08 | 24-APR-21:19 | 13.13 | 10.01 |
May | 0.444960E+11 | 21327.07 | 13-MAY-17:35 | 25.77 | 14.38 | 0.179428E+11 | 11348.97 | 10-MAY-21:40 | 25.77 | 14.38 |
June | 0.448928E+11 | 21699.43 | 13-JUN-22:00 | 27.20 | 20.99 | 0.176908E+11 | 11349.06 | 26-JUN-22:10 | 22.80 | 21.63 |
July | 0.469254E+11 | 22168.26 | 07-JUL-22:00 | 29.40 | 22.70 | 0.182543E+11 | 11349.07 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.469623E+11 | 21905.02 | 18-AUG-22:00 | 29.40 | 23.06 | 0.183773E+11 | 11348.94 | 07-AUG-22:10 | 29.40 | 23.06 |
September | 0.430244E+11 | 20913.06 | 06-SEP-22:00 | 26.70 | 22.61 | 0.173729E+11 | 11348.94 | 11-SEP-22:10 | 23.22 | 19.91 |
October | 0.411324E+11 | 20417.21 | 18-OCT-21:10 | 23.22 | 22.46 | 0.173474E+11 | 11348.79 | 11-OCT-22:10 | 23.22 | 22.46 |
November | 0.373659E+11 | 18249.52 | 03-NOV-21:54 | 17.80 | 16.05 | 0.163112E+11 | 11348.32 | 02-NOV-22:10 | 17.80 | 16.05 |
December | 0.362833E+11 | 17952.46 | 12-DEC-23:10 | 18.22 | 14.85 | 0.164019E+11 | 11311.04 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.489866E+12 | 0.205005E+12 | ||||||||
Minimum of Months | 0.330808E+11 | 17549.58 | 17.80 | 10.65 | 0.149154E+11 | 11121.84 | 13.13 | 9.75 | ||
Maximum of Months | 0.469623E+11 | 22168.26 | 29.40 | 23.06 | 0.183773E+11 | 11349.08 | 29.40 | 23.06 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372330E+11 | 18897.84 | 19-JAN-22:10 | 18.30 | 16.51 | 0.166853E+11 | 11347.42 | 31-JAN-22:49 | 12.98 | 10.12 |
February | 0.352421E+11 | 20306.34 | 28-FEB-22:10 | 18.63 | 10.80 | 0.154235E+11 | 11348.56 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.420883E+11 | 21404.00 | 30-MAR-21:53 | 22.80 | 16.45 | 0.177667E+11 | 11348.80 | 29-MAR-22:10 | 22.80 | 16.45 |
April | 0.426684E+11 | 21630.94 | 13-APR-16:04 | 26.60 | 14.97 | 0.174243E+11 | 11349.03 | 24-APR-21:19 | 13.13 | 10.01 |
May | 0.461956E+11 | 21994.15 | 18-MAY-21:53 | 21.70 | 16.42 | 0.183179E+11 | 11348.96 | 10-MAY-21:40 | 21.70 | 16.42 |
June | 0.466105E+11 | 23087.56 | 13-JUN-22:00 | 27.20 | 20.99 | 0.180170E+11 | 11349.06 | 26-JUN-22:10 | 22.80 | 21.63 |
July | 0.487349E+11 | 23547.13 | 07-JUL-21:20 | 30.20 | 22.78 | 0.185704E+11 | 11349.07 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.487666E+11 | 23265.63 | 18-AUG-21:30 | 30.25 | 22.97 | 0.186845E+11 | 11348.95 | 07-AUG-22:10 | 30.25 | 22.97 |
September | 0.446241E+11 | 22290.66 | 06-SEP-22:00 | 26.70 | 22.61 | 0.177274E+11 | 11348.94 | 11-SEP-22:10 | 23.22 | 19.91 |
October | 0.429134E+11 | 21405.71 | 18-OCT-21:53 | 22.80 | 21.95 | 0.177936E+11 | 11348.80 | 11-OCT-22:10 | 22.80 | 21.95 |
November | 0.393971E+11 | 20285.49 | 03-NOV-21:10 | 18.22 | 16.16 | 0.168426E+11 | 11348.34 | 02-NOV-22:10 | 18.22 | 16.16 |
December | 0.387109E+11 | 20026.86 | 12-DEC-22:10 | 18.30 | 14.66 | 0.169992E+11 | 11347.99 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.513185E+12 | 0.210253E+12 | ||||||||
Minimum of Months | 0.352421E+11 | 18897.84 | 18.22 | 10.80 | 0.154235E+11 | 11347.42 | 12.98 | 9.75 | ||
Maximum of Months | 0.487666E+11 | 23547.13 | 30.25 | 22.97 | 0.186845E+11 | 11349.07 | 30.25 | 22.97 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.458335E+11 | 26063.20 | 29-JAN-11:35 | 12.43 | 5.39 | 0.188680E+11 | 11319.70 | 07-JAN-18:40 | 12.43 | 5.39 |
February | 0.429558E+11 | 27187.12 | 26-FEB-11:50 | 22.43 | 11.86 | 0.170436E+11 | 11321.52 | 18-FEB-18:19 | 22.43 | 11.86 |
March | 0.504867E+11 | 27586.81 | 30-MAR-18:03 | 26.02 | 17.62 | 0.188762E+11 | 11319.57 | 18-MAR-17:10 | 26.02 | 17.62 |
April | 0.507391E+11 | 30420.01 | 13-APR-16:04 | 26.60 | 14.97 | 0.182631E+11 | 11337.01 | 15-APR-17:00 | 25.00 | 15.39 |
May | 0.542958E+11 | 30551.22 | 13-MAY-17:35 | 25.77 | 14.38 | 0.188720E+11 | 11376.35 | 13-MAY-17:30 | 25.77 | 14.38 |
June | 0.540696E+11 | 29472.13 | 25-JUN-10:40 | 29.80 | 23.29 | 0.182662E+11 | 11346.51 | 10-JUN-17:30 | 29.80 | 23.29 |
July | 0.563450E+11 | 29856.35 | 08-JUL-10:50 | 33.53 | 24.57 | 0.188682E+11 | 11319.67 | 15-JUL-17:10 | 33.30 | 24.04 |
August | 0.564197E+11 | 29758.62 | 27-AUG-10:40 | 29.47 | 22.52 | 0.188755E+11 | 11319.68 | 12-AUG-17:10 | 29.47 | 22.52 |
September | 0.525362E+11 | 29279.10 | 09-SEP-10:50 | 30.32 | 23.97 | 0.182617E+11 | 11321.51 | 30-SEP-17:19 | 17.60 | 15.56 |
October | 0.513898E+11 | 28171.40 | 09-OCT-10:50 | 24.03 | 18.11 | 0.188689E+11 | 11321.48 | 28-OCT-17:19 | 17.03 | 17.03 |
November | 0.476009E+11 | 26827.53 | 11-NOV-11:50 | 18.95 | 11.69 | 0.182586E+11 | 11319.41 | 04-NOV-17:10 | 18.95 | 11.69 |
December | 0.471800E+11 | 26329.61 | 12-DEC-11:50 | 20.22 | 16.28 | 0.188680E+11 | 11319.43 | 30-DEC-18:10 | 8.22 | 7.70 |
Annual Sum or Average | 0.609852E+12 | 0.222190E+12 | ||||||||
Minimum of Months | 0.429558E+11 | 26063.20 | 12.43 | 5.39 | 0.170436E+11 | 11319.41 | 8.22 | 5.39 | ||
Maximum of Months | 0.564197E+11 | 30551.22 | 33.53 | 24.57 | 0.188762E+11 | 11376.35 | 33.30 | 24.04 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168704E+10 | 1702.99 | 31-JAN-21:00 | 17.20 | 12.43 | 0.128588E+10 | 862.61 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.242218E+10 | 2063.21 | 28-FEB-18:15 | 22.43 | 12.28 | 0.122932E+10 | 974.64 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.443405E+10 | 3482.36 | 30-MAR-15:10 | 27.80 | 17.14 | 0.152666E+10 | 1007.40 | 29-MAR-22:10 | 27.80 | 17.14 |
April | 0.525315E+10 | 5527.25 | 17-APR-15:13 | 28.90 | 16.41 | 0.157701E+10 | 1007.40 | 19-APR-21:19 | 18.53 | 16.00 |
May | 0.681785E+10 | 5371.27 | 16-MAY-15:35 | 29.40 | 17.64 | 0.170072E+10 | 1007.40 | 31-MAY-22:10 | 21.73 | 18.83 |
June | 0.858637E+10 | 5437.65 | 13-JUN-15:40 | 32.40 | 22.24 | 0.166303E+10 | 1007.40 | 08-JUN-22:10 | 32.40 | 22.24 |
July | 0.964606E+10 | 6176.49 | 08-JUL-16:10 | 36.32 | 23.83 | 0.171373E+10 | 1007.40 | 13-JUL-21:30 | 23.30 | 21.29 |
August | 0.995955E+10 | 6149.17 | 18-AUG-15:10 | 34.50 | 23.13 | 0.172179E+10 | 1007.40 | 02-AUG-21:30 | 34.50 | 23.13 |
September | 0.699106E+10 | 5393.72 | 07-SEP-15:13 | 31.70 | 23.19 | 0.164884E+10 | 1007.40 | 14-SEP-22:10 | 18.62 | 13.88 |
October | 0.497533E+10 | 4161.20 | 10-OCT-15:10 | 29.08 | 20.63 | 0.159205E+10 | 1007.40 | 10-OCT-22:10 | 21.02 | 18.59 |
November | 0.382943E+10 | 2091.99 | 05-NOV-17:15 | 21.10 | 17.61 | 0.139490E+10 | 952.99 | 05-NOV-23:10 | 14.72 | 14.72 |
December | 0.277120E+10 | 1908.08 | 13-DEC-11:35 | 19.80 | 17.47 | 0.131839E+10 | 923.07 | 12-DEC-23:10 | 19.80 | 17.47 |
Annual Sum or Average | 0.673733E+11 | 0.183723E+11 | ||||||||
Minimum of Months | 0.168704E+10 | 1702.99 | 17.20 | 12.28 | 0.122932E+10 | 862.61 | 13.37 | 10.31 | ||
Maximum of Months | 0.995955E+10 | 6176.49 | 36.32 | 23.83 | 0.172179E+10 | 1007.40 | 34.50 | 23.13 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265117E+09 | 1073.17 | 08-JAN-05:20 | -5.4 |
February | 0.127888E+09 | 1330.31 | 12-FEB-06:00 | -12.2 |
March | 95253.51 | 33.30 | 23-MAR-08:03 | 6.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 6016447.58 | 414.11 | 21-NOV-07:10 | -2.8 |
December | 30973057.63 | 583.50 | 01-DEC-07:20 | -3.7 |
Annual Sum or Average | 0.430089E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.265117E+09 | 1330.31 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23881065.06 | 292.49 | 08-JAN-13:50 | -0.7 |
February | 8627402.94 | 204.43 | 13-FEB-10:54 | 0.60 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 32508468.00 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 23881065.06 | 292.49 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118517E+09 | 335.09 | 08-JAN-06:00 | -5.0 |
February | 73016843.47 | 340.99 | 12-FEB-07:00 | -12.8 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 753968.29 | 39.25 | 18-DEC-08:05 | -5.0 |
Annual Sum or Average | 0.192288E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.118517E+09 | 340.99 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.789095E+09 | 1426.11 | 07-JAN-16:23 | -4.5 |
February | 0.447595E+09 | 1415.18 | 12-FEB-09:13 | -9.8 |
March | 57137807.24 | 1346.59 | 23-MAR-08:61 | 6.97 |
April | 15398176.20 | 1324.84 | 06-APR-08:62 | 5.37 |
May | 1449478.74 | 910.12 | 11-MAY-08:03 | 12.15 |
June | 459525.67 | 975.55 | 02-JUN-08:04 | 22.48 |
July | 212142.76 | 486.58 | 28-JUL-18:05 | 18.90 |
August | 133727.07 | 516.15 | 25-AUG-08:04 | 22.15 |
September | 1244278.57 | 749.70 | 01-SEP-08:05 | 20.18 |
October | 37566225.75 | 1339.84 | 26-OCT-08:61 | 5.05 |
November | 0.140732E+09 | 1450.53 | 22-NOV-09:09 | 1.05 |
December | 0.463664E+09 | 1416.46 | 31-DEC-19:09 | 5.50 |
Annual Sum or Average | 0.195469E+10 | |||
Minimum of Months | 133727.07 | 486.58 | -9.8 | |
Maximum of Months | 0.789095E+09 | 1450.53 | 22.48 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103276E+10 | 1452.04 | 17-JAN-19:10 | 4.40 |
February | 0.593220E+09 | 1434.99 | 12-FEB-09:13 | -9.8 |
March | 81417471.29 | 1349.14 | 23-MAR-08:61 | 6.97 |
April | 18989939.40 | 1329.81 | 06-APR-08:62 | 5.37 |
May | 1046609.86 | 942.22 | 13-MAY-08:53 | 20.00 |
June | 203544.35 | 579.95 | 02-JUN-08:54 | 23.90 |
July | 120438.33 | 234.34 | 28-JUL-21:55 | 17.80 |
August | 72541.38 | 323.34 | 25-AUG-08:54 | 24.40 |
September | 852076.88 | 830.18 | 15-SEP-08:53 | 21.70 |
October | 50378583.30 | 1352.27 | 26-OCT-08:61 | 5.05 |
November | 0.231461E+09 | 1410.35 | 21-NOV-09:12 | 0.33 |
December | 0.664836E+09 | 1402.25 | 18-DEC-09:13 | -1.3 |
Annual Sum or Average | 0.267536E+10 | |||
Minimum of Months | 72541.38 | 234.34 | -9.8 | |
Maximum of Months | 0.103276E+10 | 1452.04 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137804E+09 | 406.36 | 07-JAN-16:23 | -4.5 |
February | 76556991.37 | 404.92 | 03-FEB-16:11 | 1.50 |
March | 4466744.25 | 406.42 | 19-MAR-08:03 | 4.27 |
April | 4731731.64 | 353.60 | 06-APR-00:53 | 2.20 |
May | 149739.43 | 202.86 | 15-MAY-21:56 | 22.20 |
June | 26173.88 | 86.67 | 01-JUN-21:56 | 22.80 |
July | 4164.53 | 23.12 | 29-JUL-08:58 | 17.80 |
August | 958.78 | 11.19 | 30-AUG-21:56 | 22.80 |
September | 100066.56 | 264.43 | 19-SEP-08:54 | 19.40 |
October | 1118883.01 | 353.37 | 25-OCT-08:10 | 7.30 |
November | 13016976.04 | 388.52 | 21-NOV-16:11 | 8.67 |
December | 48164866.47 | 402.23 | 09-DEC-09:03 | 3.68 |
Annual Sum or Average | 0.286141E+09 | |||
Minimum of Months | 958.78 | 11.19 | -4.5 | |
Maximum of Months | 0.137804E+09 | 406.42 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.801223E+09 | 1412.81 | 07-JAN-16:23 | -4.5 |
February | 0.445223E+09 | 1429.48 | 02-FEB-19:09 | -2.3 |
March | 63529034.72 | 1336.77 | 23-MAR-08:61 | 6.97 |
April | 15463598.22 | 1300.48 | 06-APR-08:03 | 5.37 |
May | 308678.24 | 689.45 | 26-MAY-08:05 | 20.10 |
June | 26767.21 | 187.12 | 23-JUN-08:06 | 24.18 |
July | 196155.92 | 434.12 | 28-JUL-08:06 | 19.40 |
August | 62650.80 | 227.86 | 24-AUG-08:06 | 23.80 |
September | 553393.53 | 728.78 | 30-SEP-15:15 | 17.97 |
October | 38957048.47 | 1320.05 | 31-OCT-08:62 | 7.80 |
November | 0.141415E+09 | 1345.05 | 30-NOV-16:11 | 7.20 |
December | 0.459168E+09 | 1420.86 | 31-DEC-19:09 | 5.50 |
Annual Sum or Average | 0.196613E+10 | |||
Minimum of Months | 26767.21 | 187.12 | -4.5 | |
Maximum of Months | 0.801223E+09 | 1429.48 | 24.18 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104551E+10 | 1432.62 | 17-JAN-19:10 | 4.40 |
February | 0.580758E+09 | 1434.68 | 13-FEB-19:10 | 4.90 |
March | 88119234.76 | 1339.53 | 23-MAR-08:61 | 6.97 |
April | 19121534.05 | 1103.87 | 09-APR-20:13 | 13.70 |
May | 551260.08 | 911.22 | 10-MAY-21:24 | 14.15 |
June | 37663.69 | 344.25 | 08-JUN-21:55 | 18.90 |
July | 41651.18 | 195.26 | 28-JUL-08:56 | 19.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 348155.29 | 637.44 | 29-SEP-08:04 | 14.78 |
October | 53553365.97 | 1322.40 | 31-OCT-08:62 | 7.80 |
November | 0.226462E+09 | 1349.42 | 30-NOV-16:11 | 7.20 |
December | 0.651491E+09 | 1394.46 | 02-DEC-19:12 | 0.73 |
Annual Sum or Average | 0.266600E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.73 | |
Maximum of Months | 0.104551E+10 | 1434.68 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109780E+09 | 788.07 | 09-JAN-09:03 | -3.2 |
February | 33796500.51 | 514.60 | 12-FEB-08:62 | -11.9 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 1541517.15 | 133.26 | 18-DEC-07:40 | -5.4 |
Annual Sum or Average | 0.145118E+09 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.109780E+09 | 788.07 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123585E+10 | 1769.59 | 07-JAN-16:23 | -4.5 |
February | 0.729961E+09 | 1762.96 | 12-FEB-09:13 | -9.8 |
March | 0.147330E+09 | 1659.78 | 23-MAR-08:61 | 6.97 |
April | 43074527.73 | 1637.48 | 26-APR-08:61 | 8.35 |
May | 1542069.28 | 1078.93 | 24-MAY-18:04 | 19.40 |
June | 693500.19 | 928.49 | 02-JUN-08:04 | 22.48 |
July | 381072.52 | 583.23 | 13-JUL-08:04 | 26.97 |
August | 333854.47 | 815.63 | 25-AUG-08:04 | 22.15 |
September | 2325813.39 | 1060.24 | 28-SEP-15:14 | 19.03 |
October | 0.100685E+09 | 1656.40 | 26-OCT-08:61 | 5.05 |
November | 0.298337E+09 | 1720.61 | 21-NOV-09:12 | 0.33 |
December | 0.795126E+09 | 1789.96 | 17-DEC-19:09 | -0.2 |
Annual Sum or Average | 0.335564E+10 | |||
Minimum of Months | 333854.47 | 583.23 | -9.8 | |
Maximum of Months | 0.123585E+10 | 1789.96 | 26.97 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154620E+10 | 1777.73 | 27-JAN-09:11 | -4.4 |
February | 0.921599E+09 | 1779.90 | 12-FEB-09:13 | -9.8 |
March | 0.191985E+09 | 1663.85 | 23-MAR-08:61 | 6.97 |
April | 47964443.15 | 1643.03 | 06-APR-08:62 | 5.37 |
May | 1409523.45 | 918.44 | 13-MAY-08:53 | 20.00 |
June | 483725.49 | 981.78 | 07-JUN-08:53 | 18.90 |
July | 125178.13 | 457.83 | 28-JUL-21:55 | 17.80 |
August | 197388.70 | 502.54 | 30-AUG-21:54 | 22.80 |
September | 1375866.28 | 780.87 | 14-SEP-08:03 | 15.55 |
October | 0.129028E+09 | 1672.38 | 26-OCT-08:61 | 5.05 |
November | 0.443349E+09 | 1751.55 | 21-NOV-09:12 | 0.33 |
December | 0.105861E+10 | 1749.28 | 18-DEC-09:13 | -1.3 |
Annual Sum or Average | 0.434233E+10 | |||
Minimum of Months | 125178.13 | 457.83 | -9.8 | |
Maximum of Months | 0.154620E+10 | 1779.90 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329774E+09 | 928.93 | 17-JAN-16:19 | 4.23 |
February | 0.177652E+09 | 928.61 | 07-FEB-09:09 | 2.98 |
March | 23638646.16 | 870.98 | 23-MAR-08:61 | 6.97 |
April | 10501738.52 | 858.83 | 06-APR-08:62 | 5.37 |
May | 497345.82 | 454.29 | 10-MAY-18:04 | 20.92 |
June | 175695.98 | 400.83 | 08-JUN-08:03 | 17.57 |
July | 143620.75 | 264.00 | 28-JUL-18:05 | 18.90 |
August | 110382.81 | 160.91 | 21-AUG-08:06 | 22.88 |
September | 619362.73 | 460.99 | 30-SEP-15:15 | 17.97 |
October | 14066746.64 | 859.74 | 31-OCT-08:62 | 7.80 |
November | 43021792.77 | 876.48 | 30-NOV-16:11 | 7.20 |
December | 0.162344E+09 | 887.66 | 31-DEC-16:19 | 5.60 |
Annual Sum or Average | 0.762545E+09 | |||
Minimum of Months | 110382.81 | 160.91 | 2.98 | |
Maximum of Months | 0.329774E+09 | 928.93 | 22.88 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.725999E+09 | 2349.60 | 08-JAN-05:30 | -5.3 |
February | 0.364633E+09 | 2893.58 | 12-FEB-06:00 | -12.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 8725698.02 | 778.50 | 22-NOV-07:10 | -3.2 |
December | 83611394.02 | 1457.66 | 18-DEC-07:40 | -5.4 |
Annual Sum or Average | 0.118297E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.725999E+09 | 2893.58 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104372E+11 | 10053.14 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.942384E+10 | 10053.14 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.104694E+11 | 10053.14 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.100833E+11 | 10053.14 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.104553E+11 | 10053.14 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.101296E+11 | 10053.14 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.104091E+11 | 10053.14 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.104734E+11 | 10053.14 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.100874E+11 | 10053.14 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.104332E+11 | 10053.14 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.101215E+11 | 10053.14 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.104091E+11 | 10053.14 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.122932E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.942384E+10 | 10053.14 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.104734E+11 | 10053.14 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.195918E+09 | 188.71 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.176896E+09 | 188.71 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.196522E+09 | 188.71 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.189275E+09 | 188.71 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.196257E+09 | 188.71 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.190143E+09 | 188.71 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.195389E+09 | 188.71 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.196597E+09 | 188.71 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.189351E+09 | 188.71 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.195842E+09 | 188.71 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.189992E+09 | 188.71 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.195389E+09 | 188.71 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.230757E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.176896E+09 | 188.71 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.196597E+09 | 188.71 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.122979E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.110068E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.111972E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.997299E+09 | 1573.46 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.962420E+09 | 1573.46 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.899232E+09 | 1573.46 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.943564E+09 | 1573.46 | 03-JUL-19:49 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.997611E+09 | 1573.46 | 01-AUG-19:40 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.106266E+10 | 1573.46 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.118214E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.117360E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.122692E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.128956E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.899232E+09 | 1573.46 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.122979E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.793377E+10 | 7984.04 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.716042E+10 | 7984.04 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.786925E+10 | 7984.04 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.752002E+10 | 7984.04 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.773628E+10 | 7984.04 | 01-MAY-19:19 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.746635E+10 | 7984.04 | 01-JUN-19:40 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.768962E+10 | 7984.04 | 03-JUL-19:49 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.777186E+10 | 7984.04 | 01-AUG-19:40 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.757132E+10 | 7984.04 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.790113E+10 | 7984.04 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.767578E+10 | 7984.04 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.791266E+10 | 7984.04 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.922085E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.716042E+10 | 7984.04 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.793377E+10 | 7984.04 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65789991.58 | 59.53 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 59414784.75 | 59.53 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 65267117.48 | 59.53 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 63743496.62 | 59.53 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 65528554.53 | 59.53 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 63237765.93 | 59.53 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 66042856.93 | 59.53 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 65267117.48 | 59.53 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 63760640.03 | 59.53 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 65781419.88 | 59.53 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 63490631.27 | 59.53 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 66051428.64 | 59.53 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.773376E+09 | 0.256575E+10 | ||||
Minimum of Months | 59414784.75 | 59.53 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 66051428.64 | 59.53 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.257076E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.231074E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244775E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.226157E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.225174E+10 | 2763.12 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.214107E+10 | 2763.12 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.222655E+10 | 2763.12 | 03-JUL-19:49 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.229869E+10 | 2763.12 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.233007E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.252976E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.246628E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.256310E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.283981E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.214107E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.257076E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.257076E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.231074E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244775E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.226157E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.225174E+10 | 2763.12 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.214107E+10 | 2763.12 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.222655E+10 | 2763.12 | 03-JUL-19:49 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.229869E+10 | 2763.12 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.233007E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.252976E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.246628E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.256310E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.283981E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.214107E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.257076E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.104372E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.942384E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.104694E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.100833E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.104553E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.101296E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.104091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.104734E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.100874E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.104332E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.101215E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.104091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.122932E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.942384E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.104734E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259278E+09 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60545.60 | 0.183258E+09 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 848049.55 | 0.125123E+09 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4207961.90 | 81174767.28 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11035802.41 | 45965802.36 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31473019.21 | 18930638.44 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40797981.23 | 11518004.02 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39506046.47 | 4954339.11 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13478781.17 | 28127394.41 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2106416.05 | 99592510.95 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46739.32 | 0.143739E+09 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204544E+09 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143561E+09 | 0.120621E+10 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4954339.11 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40797981.23 | 0.259278E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100170E+09 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 166566.85 | 70983259.56 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 709241.24 | 48110063.14 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2938082.44 | 31776760.90 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6277802.75 | 17768647.06 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14394026.62 | 7263785.73 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17794276.55 | 4244119.62 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17265480.15 | 1722017.71 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6923653.55 | 10862732.88 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1519894.88 | 38323711.74 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 123104.86 | 55753353.67 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7544.99 | 79402853.71 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68119674.87 | 0.466381E+09 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1722017.71 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17794276.55 | 0.100170E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244512E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94400.35 | 0.178241E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 685507.37 | 0.130094E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3538838.87 | 87906950.47 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9446296.54 | 50316918.39 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28329323.16 | 19658867.11 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37002311.95 | 12219039.17 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35968352.57 | 4979537.49 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12058434.34 | 30699395.71 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1779086.19 | 0.104687E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14656.33 | 0.149118E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202846E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128917E+09 | 0.121528E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4979537.49 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37002311.95 | 0.244512E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.195918E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 181.59 | 0.133343E+09 |
February | 0.339028E+09 | 0.176896E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 412319.30 | 92504965.77 |
March | 0.376747E+09 | 0.196522E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1513902.22 | 58135985.52 |
April | 0.363528E+09 | 0.189275E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5246698.28 | 37098083.50 |
May | 0.375778E+09 | 0.196257E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10174655.84 | 19271385.05 |
June | 0.364321E+09 | 0.190143E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21855278.21 | 7117732.24 |
July | 0.374985E+09 | 0.195389E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26698363.42 | 3722823.62 |
August | 0.376571E+09 | 0.196597E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26937877.63 | 1020422.58 |
September | 0.363352E+09 | 0.189351E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11516259.25 | 11089500.56 |
October | 0.375161E+09 | 0.195842E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2832662.79 | 45451796.22 |
November | 0.362735E+09 | 0.189992E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 311504.55 | 68778654.36 |
December | 0.374985E+09 | 0.195389E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43002.54 | 0.102878E+09 |
Annual Sum or Average | 0.442217E+10 | 0.230757E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107543E+09 | 0.580412E+09 |
Minimum of Months | 0.339028E+09 | 0.176896E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 181.59 | 1020422.58 |
Maximum of Months | 0.376747E+09 | 0.196597E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26937877.63 | 0.133343E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370614E+09 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 75418.76 | 0.266222E+09 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 897622.22 | 0.183665E+09 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 4669619.18 | 0.121425E+09 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 12900239.29 | 68711933.49 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 38682065.92 | 26841681.58 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 50523683.15 | 16683087.18 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 49109874.28 | 6797729.71 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 16464423.82 | 41917612.83 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 2429607.37 | 0.144080E+09 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 8877.86 | 0.209412E+09 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296897E+09 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.175761E+09 | 0.175327E+10 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6797729.71 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 50523683.15 | 0.370614E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.122979E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572248E+09 |
February | 0.236489E+11 | 0.110068E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 720606.68 | 0.402953E+09 |
March | 0.262800E+11 | 0.111972E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4363502.98 | 0.263836E+09 |
April | 0.253579E+11 | 0.997299E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19501240.70 | 0.165905E+09 |
May | 0.262123E+11 | 0.962420E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44957559.89 | 86185478.10 |
June | 0.254132E+11 | 0.899232E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99425144.66 | 32156633.68 |
July | 0.261570E+11 | 0.943564E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119671E+09 | 16040324.53 |
August | 0.262677E+11 | 0.997611E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116918E+09 | 5452690.59 |
September | 0.253456E+11 | 0.106266E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48494758.74 | 49514521.79 |
October | 0.261693E+11 | 0.118214E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9514769.13 | 0.205973E+09 |
November | 0.253025E+11 | 0.117360E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1047638.10 | 0.309221E+09 |
December | 0.261570E+11 | 0.122692E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25117.94 | 0.449951E+09 |
Annual Sum or Average | 0.308468E+12 | 0.128956E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464640E+09 | 0.255944E+10 |
Minimum of Months | 0.236489E+11 | 0.899232E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5452690.59 |
Maximum of Months | 0.262800E+11 | 0.122979E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119671E+09 | 0.572248E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.793377E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168247E+10 |
February | 0.702046E+11 | 0.716042E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2306900.13 | 0.119613E+10 |
March | 0.780153E+11 | 0.786925E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10859953.03 | 0.811922E+09 |
April | 0.752779E+11 | 0.752002E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48244040.29 | 0.532774E+09 |
May | 0.778146E+11 | 0.773628E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106443E+09 | 0.298278E+09 |
June | 0.754422E+11 | 0.746635E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244511E+09 | 0.122481E+09 |
July | 0.776503E+11 | 0.768962E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300743E+09 | 72379920.10 |
August | 0.779788E+11 | 0.777186E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291364E+09 | 29386624.58 |
September | 0.752414E+11 | 0.757132E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116304E+09 | 0.184117E+09 |
October | 0.776868E+11 | 0.790113E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24098001.54 | 0.647886E+09 |
November | 0.751137E+11 | 0.767578E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1713107.89 | 0.945722E+09 |
December | 0.776503E+11 | 0.791266E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74823.80 | 0.134426E+10 |
Annual Sum or Average | 0.915726E+12 | 0.922085E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114666E+10 | 0.786780E+10 |
Minimum of Months | 0.702046E+11 | 0.716042E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29386624.58 |
Maximum of Months | 0.780153E+11 | 0.793377E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300743E+09 | 0.168247E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146397E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 186849.20 | 0.102242E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1247369.02 | 66206425.18 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4248636.83 | 40449311.53 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10228809.55 | 18400748.42 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27027055.18 | 4842430.43 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34947259.77 | 2022983.04 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37042244.56 | 300489.64 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14440207.78 | 9203404.93 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2642615.51 | 49027458.72 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 160284.07 | 77255254.37 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6549.14 | 0.114165E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132178E+09 | 0.630513E+09 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300489.64 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37042244.56 | 0.146397E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144131E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 154728.65 | 0.101059E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1030403.61 | 66448820.75 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3884527.38 | 42785848.06 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9581644.55 | 21658831.28 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25902154.31 | 6508627.40 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33721477.51 | 3551847.59 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35691381.34 | 977273.11 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13377404.05 | 11136535.66 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264537.20 | 49995574.93 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 111716.35 | 75939688.49 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7122.24 | 0.111698E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125727E+09 | 0.635891E+09 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 977273.11 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35691381.34 | 0.144131E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 65789991.58 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43511686.02 |
February | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34951217.84 |
March | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9526.23 | 29239669.27 |
April | 0.00 | 63743496.62 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85972.67 | 20986569.06 |
May | 0.00 | 65528554.53 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 480880.02 | 13771746.03 |
June | 0.00 | 63237765.93 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2494717.81 | 6742573.05 |
July | 0.00 | 66042856.93 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3536661.77 | 5115726.36 |
August | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3187036.52 | 3645242.46 |
September | 0.00 | 63760640.03 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 700010.87 | 9813769.14 |
October | 0.00 | 65781419.88 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52325.02 | 24113804.12 |
November | 0.00 | 63490631.27 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32610755.49 |
December | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41429162.43 |
Annual Sum or Average | 0.00 | 0.773376E+09 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10547130.90 | 0.265932E+09 |
Minimum of Months | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3645242.46 |
Maximum of Months | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3536661.77 | 43511686.02 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40913726.33 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67834.36 | 28623591.70 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 331286.46 | 18353202.58 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1192819.94 | 11693125.02 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2761903.02 | 5776007.82 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7311456.20 | 1666947.08 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9496195.57 | 888733.05 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10079311.27 | 200140.49 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3848530.19 | 3007371.09 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 722112.12 | 13836475.27 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45253.05 | 21374179.93 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7161.22 | 31807258.19 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35863863.41 | 0.178141E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200140.49 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10079311.27 | 40913726.33 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146714E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 187918.40 | 0.102683E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1259214.06 | 66793829.13 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4253985.68 | 40988921.07 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10192590.84 | 18657115.47 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26981979.61 | 4948073.62 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34894164.26 | 2058766.24 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36994079.08 | 315524.18 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14424774.39 | 9308236.07 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2645921.35 | 49370023.21 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 165722.16 | 77635450.52 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6516.92 | 0.114496E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132007E+09 | 0.633969E+09 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315524.18 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36994079.08 | 0.146714E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144300E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 139916.19 | 0.101292E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1072187.07 | 66506759.13 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3850236.22 | 42934055.10 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9508768.43 | 21974760.59 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25716397.33 | 7038775.56 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33518084.75 | 4083537.24 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35562895.83 | 1268641.40 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13283709.86 | 11447538.82 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2261753.91 | 50053090.69 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 161618.92 | 75766340.67 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17070.40 | 0.111833E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125093E+09 | 0.638498E+09 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1268641.40 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35562895.83 | 0.144300E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.11 | 0.178313E+09 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394091.46 | 0.124518E+09 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1604284.63 | 81188170.93 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5430457.68 | 53987521.52 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11312402.41 | 29417264.14 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25913909.61 | 11642564.82 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31734024.99 | 6962193.09 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31409024.89 | 2426699.75 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12785739.63 | 17440007.89 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3021896.33 | 63857491.14 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383085.30 | 93015417.55 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44642.24 | 0.137782E+09 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124034E+09 | 0.800551E+09 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.11 | 2426699.75 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31734024.99 | 0.178313E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145797E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 177888.84 | 0.101846E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1212702.69 | 66104896.67 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4138690.24 | 40544654.25 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10029050.93 | 18581644.37 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26690855.11 | 4929506.58 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34546799.96 | 2061971.58 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36593057.19 | 304449.88 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14164993.91 | 9238433.87 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2569842.23 | 48917800.37 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 148500.49 | 77069173.28 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5946.67 | 0.113547E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130278E+09 | 0.628943E+09 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304449.88 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36593057.19 | 0.145797E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143878E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 152390.51 | 0.100885E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 996088.50 | 66289342.41 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3765263.06 | 43063387.07 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9402429.24 | 21912817.82 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25610323.10 | 6474458.89 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33381847.52 | 3441133.29 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35325934.91 | 882663.07 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13150683.40 | 11000047.65 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2199397.15 | 49763719.62 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 112206.60 | 75559794.96 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9159.70 | 0.111105E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124106E+09 | 0.634256E+09 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 882663.07 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35325934.91 | 0.143878E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76798753.80 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87383.06 | 53653015.74 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 618337.68 | 34482918.72 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2117022.99 | 20943178.62 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5144962.28 | 9517534.33 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13679215.73 | 2523751.92 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17697212.51 | 1056505.55 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18723882.70 | 158333.79 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7233452.18 | 4782467.77 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1298352.47 | 25580238.58 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72897.81 | 40577191.38 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2940.98 | 60053299.11 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66675660.39 | 0.330127E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158333.79 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18723882.70 | 76798753.80 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.257076E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378694E+09 |
February | 0.415303E+11 | 0.231074E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 736412.37 | 0.269191E+09 |
March | 0.461508E+11 | 0.244775E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2686779.60 | 0.181106E+09 |
April | 0.445315E+11 | 0.226157E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11040168.46 | 0.120346E+09 |
May | 0.460320E+11 | 0.225174E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23760491.68 | 67525535.57 |
June | 0.446286E+11 | 0.214107E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55927696.35 | 26996469.02 |
July | 0.459349E+11 | 0.222655E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69308451.00 | 15493452.10 |
August | 0.461292E+11 | 0.229869E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69101633.88 | 5887773.27 |
September | 0.445099E+11 | 0.233007E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29209895.15 | 39373531.23 |
October | 0.459565E+11 | 0.252976E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6751752.39 | 0.140783E+09 |
November | 0.444343E+11 | 0.246628E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 537606.12 | 0.206700E+09 |
December | 0.459349E+11 | 0.256310E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66555.33 | 0.298703E+09 |
Annual Sum or Average | 0.541708E+12 | 0.283981E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269127E+09 | 0.175080E+10 |
Minimum of Months | 0.415303E+11 | 0.214107E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5887773.27 |
Maximum of Months | 0.461508E+11 | 0.257076E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69308451.00 | 0.378694E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.257076E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385191E+09 |
February | 0.415303E+11 | 0.231074E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 586581.78 | 0.275049E+09 |
March | 0.461508E+11 | 0.244775E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2284012.53 | 0.187000E+09 |
April | 0.445315E+11 | 0.226157E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9873355.54 | 0.124402E+09 |
May | 0.460320E+11 | 0.225174E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21884670.30 | 70358974.66 |
June | 0.446286E+11 | 0.214107E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53299476.59 | 28529481.77 |
July | 0.459349E+11 | 0.222655E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66587415.36 | 16903141.44 |
August | 0.461292E+11 | 0.229869E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65979150.43 | 6782257.19 |
September | 0.445099E+11 | 0.233007E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27135965.87 | 41707608.06 |
October | 0.459565E+11 | 0.252976E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6003409.07 | 0.145602E+09 |
November | 0.444343E+11 | 0.246628E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 371650.73 | 0.213086E+09 |
December | 0.459349E+11 | 0.256310E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39982.56 | 0.305846E+09 |
Annual Sum or Average | 0.541708E+12 | 0.283981E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254046E+09 | 0.180046E+10 |
Minimum of Months | 0.415303E+11 | 0.214107E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6782257.19 |
Maximum of Months | 0.461508E+11 | 0.257076E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66587415.36 | 0.385191E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379316E+09 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 64804.35 | 0.272758E+09 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 842277.52 | 0.188734E+09 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 4410318.09 | 0.125111E+09 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 12677758.47 | 71231856.80 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 38585611.55 | 28134938.52 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 50527939.74 | 17682943.69 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 48933004.43 | 7450607.51 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 16229160.47 | 43759646.57 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 2355818.97 | 0.148337E+09 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 5612.59 | 0.214974E+09 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304187E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.174632E+09 | 0.180168E+10 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7450607.51 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 50527939.74 | 0.379316E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318646E+09 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175240.63 | 0.228393E+09 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1008361.61 | 0.161968E+09 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4746171.25 | 0.112926E+09 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12409880.62 | 67740091.38 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37720630.48 | 27279423.23 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49365419.46 | 17241356.05 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47794638.69 | 7319863.22 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15845315.93 | 41384604.71 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2317382.62 | 0.130926E+09 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98782.30 | 0.179822E+09 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250021E+09 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171482E+09 | 0.154367E+10 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7319863.22 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49365419.46 | 0.318646E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 10053.14 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 10053.14 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 10053.14 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 10053.14 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 10053.14 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 10053.14 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 10053.14 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 10053.14 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 10053.14 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 10053.14 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 10053.14 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 10053.14 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 159.67 | 27-JAN-07:52 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 | 26-FEB-15:00 | 200.36 | 12-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.08 | 30-MAR-14:30 | 110.80 | 19-MAR-06:53 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.29 | 17-APR-15:40 | 116.94 | 06-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.01 | 19-MAY-14:00 | 74.15 | 11-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.69 | 06-JUN-15:00 | 60.41 | 10-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.16 | 08-JUL-15:00 | 32.08 | 28-JUL-23:00 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.35 | 02-AUG-16:00 | 27.17 | 25-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 | 07-SEP-16:00 | 55.73 | 14-SEP-05:00 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 | 10-OCT-16:00 | 103.88 | 26-OCT-06:53 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.16 | 19-NOV-15:40 | 136.53 | 22-NOV-06:50 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 152.24 | 18-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 62.16 | 200.36 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 62.30 | 27-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 | 26-FEB-15:00 | 77.34 | 12-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.27 | 30-MAR-14:00 | 44.71 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 12-APR-14:00 | 47.54 | 06-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.44 | 30-MAY-14:00 | 31.27 | 11-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.64 | 06-JUN-15:00 | 24.89 | 10-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 | 08-JUL-16:00 | 12.91 | 28-JUL-23:00 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 01-AUG-15:00 | 10.93 | 25-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 | 07-SEP-15:00 | 22.95 | 14-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.55 | 10-OCT-16:00 | 42.61 | 26-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 | 19-NOV-15:00 | 54.16 | 22-NOV-06:10 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 | 12-DEC-14:00 | 59.16 | 18-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 | 77.34 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 149.13 | 27-JAN-07:52 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 | 26-FEB-15:00 | 183.37 | 12-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.40 | 30-MAR-14:00 | 110.81 | 19-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 | 12-APR-14:00 | 118.69 | 06-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.11 | 19-MAY-14:00 | 79.80 | 11-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.25 | 06-JUN-15:00 | 62.83 | 10-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.71 | 08-JUL-15:00 | 32.61 | 28-JUL-23:20 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.58 | 02-AUG-16:00 | 26.99 | 25-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.81 | 07-SEP-16:00 | 59.75 | 29-SEP-04:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.31 | 10-OCT-16:00 | 107.78 | 26-OCT-07:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 | 19-NOV-15:00 | 133.13 | 22-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 145.42 | 18-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.99 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 56.71 | 183.37 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 188.71 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 | 31-JAN-15:00 | 84.04 | 27-JAN-07:52 |
February | 220.32 | 01-FEB-00:10 | 188.71 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.35 | 26-FEB-15:00 | 105.45 | 12-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 188.71 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 | 30-MAR-16:00 | 58.32 | 19-MAR-06:53 |
April | 220.32 | 01-APR-00:10 | 188.71 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.40 | 12-APR-14:00 | 61.55 | 06-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 188.71 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.23 | 19-MAY-16:40 | 39.02 | 11-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 188.71 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 06-JUN-15:00 | 30.98 | 10-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 188.71 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.47 | 08-JUL-16:00 | 14.64 | 28-JUL-23:00 |
August | 220.32 | 01-AUG-00:10 | 188.71 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.22 | 01-AUG-16:50 | 12.27 | 25-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 188.71 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 07-SEP-16:00 | 28.74 | 29-SEP-04:00 |
October | 220.32 | 01-OCT-23:10 | 188.71 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 | 10-OCT-16:00 | 54.68 | 26-OCT-06:57 |
November | 220.32 | 01-NOV-00:10 | 188.71 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 19-NOV-15:00 | 71.86 | 22-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 188.71 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 | 12-DEC-14:00 | 80.13 | 18-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 | 12.27 | |||||
Maximum of Months | 220.32 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 35.47 | 105.45 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 220.43 | 27-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 6.32 | 26-FEB-15:00 | 271.73 | 12-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 23.78 | 30-MAR-14:30 | 158.82 | 19-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 34.38 | 17-APR-15:40 | 166.48 | 06-APR-05:00 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 41.12 | 19-MAY-14:00 | 108.97 | 11-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 63.15 | 06-JUN-15:00 | 85.80 | 10-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 77.44 | 08-JUL-15:00 | 44.53 | 28-JUL-23:20 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 67.71 | 02-AUG-16:00 | 36.85 | 25-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 47.54 | 07-SEP-16:00 | 81.59 | 29-SEP-04:00 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 37.29 | 10-OCT-16:00 | 150.05 | 26-OCT-06:53 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 2.52 | 05-NOV-16:00 | 191.06 | 22-NOV-06:00 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 211.02 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 36.85 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 77.44 | 271.73 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 352.95 | 27-JAN-07:52 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.49 | 28-FEB-14:30 | 442.90 | 12-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.21 | 30-MAR-15:00 | 244.92 | 19-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.88 | 17-APR-16:00 | 266.13 | 06-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1573.46 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.23 | 19-MAY-17:00 | 166.03 | 11-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 1573.46 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.55 | 06-JUN-15:00 | 135.75 | 10-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1573.46 | 03-JUL-19:49 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.62 | 08-JUL-16:00 | 67.24 | 28-JUL-23:00 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 01-AUG-19:40 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.55 | 01-AUG-17:00 | 51.48 | 25-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.36 | 07-SEP-12:00 | 125.38 | 29-SEP-04:00 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.55 | 10-OCT-16:00 | 240.11 | 26-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 19-NOV-15:40 | 306.29 | 22-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 12-DEC-15:40 | 336.52 | 18-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.48 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 156.62 | 442.90 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 7984.04 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1047.72 | 14-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 7984.04 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.71 | 28-FEB-14:30 | 1274.03 | 12-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 7984.04 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.91 | 30-MAR-14:00 | 746.29 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 7984.04 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.87 | 12-APR-14:00 | 802.16 | 06-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 7984.04 | 01-MAY-19:19 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.13 | 30-MAY-14:00 | 519.16 | 11-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 7984.04 | 01-JUN-19:40 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.61 | 06-JUN-15:00 | 420.04 | 10-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 7984.04 | 03-JUL-19:49 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.15 | 08-JUL-16:00 | 222.41 | 28-JUL-23:00 |
August | 45622.98 | 01-AUG-00:10 | 7984.04 | 01-AUG-19:40 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.17 | 01-AUG-15:00 | 181.92 | 25-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 7984.04 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.71 | 07-SEP-15:00 | 393.52 | 29-SEP-04:00 |
October | 45622.98 | 01-OCT-23:10 | 7984.04 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.34 | 10-OCT-16:00 | 723.18 | 26-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 7984.04 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.38 | 19-NOV-15:00 | 916.28 | 22-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 7984.04 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 12-DEC-15:00 | 985.09 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.92 | |||||
Maximum of Months | 45622.98 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 432.15 | 1274.03 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 93.17 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.11 | 26-FEB-16:19 | 116.82 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 30-MAR-16:00 | 64.45 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 17-APR-15:20 | 68.37 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 | 19-MAY-16:00 | 41.85 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.01 | 06-JUN-15:20 | 31.16 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 | 08-JUL-16:00 | 15.18 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.70 | 02-AUG-16:00 | 10.53 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 07-SEP-16:00 | 29.22 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 10-OCT-16:00 | 60.78 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 05-NOV-16:00 | 79.75 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 | 12-DEC-16:17 | 88.51 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 | 116.82 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 93.17 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.11 | 26-FEB-16:17 | 116.81 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 30-MAR-16:00 | 64.45 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 17-APR-15:20 | 68.37 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 | 19-MAY-16:00 | 41.85 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.01 | 06-JUN-15:20 | 31.16 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.11 | 08-JUL-16:00 | 16.02 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.70 | 02-AUG-16:00 | 12.69 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 07-SEP-16:00 | 29.22 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 10-OCT-16:00 | 60.77 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 05-NOV-16:00 | 79.74 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 12-DEC-14:00 | 88.50 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.69 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 44.11 | 116.81 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 59.53 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 28.22 | 27-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 59.53 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 30.66 | 12-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 59.53 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 30-MAR-14:10 | 22.10 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 59.53 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 12-APR-14:00 | 22.52 | 06-APR-05:00 |
May | 0.00 | 01-MAY-00:10 | 59.53 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 | 19-MAY-14:00 | 16.38 | 11-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 59.53 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 06-JUN-15:00 | 13.36 | 10-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 59.53 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 08-JUL-15:00 | 8.09 | 28-JUL-23:00 |
August | 0.00 | 01-AUG-00:10 | 59.53 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 | 02-AUG-16:00 | 7.07 | 25-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 59.53 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 07-SEP-16:00 | 12.45 | 14-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 59.53 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 10-OCT-16:00 | 21.30 | 26-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 59.53 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 25.49 | 22-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 59.53 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 28.29 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.07 | |||||
Maximum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 30.66 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 26.00 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 | 28-FEB-14:00 | 32.60 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 30-MAR-16:00 | 18.18 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 | 17-APR-15:20 | 19.10 | 06-APR-05:20 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 | 19-MAY-16:00 | 11.68 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 06-JUN-15:20 | 8.70 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 | 08-JUL-15:20 | 4.80 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.08 | 02-AUG-16:00 | 3.43 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 | 07-SEP-16:00 | 8.16 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 | 10-OCT-16:00 | 17.37 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 05-NOV-16:00 | 22.26 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 | 12-DEC-14:00 | 24.78 | 18-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 | 32.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 93.17 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.11 | 26-FEB-16:19 | 116.82 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 30-MAR-15:50 | 64.59 | 19-MAR-06:53 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 17-APR-15:20 | 68.37 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 | 19-MAY-16:00 | 41.85 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.01 | 06-JUN-15:20 | 31.16 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.15 | 08-JUL-15:20 | 15.11 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.71 | 02-AUG-16:00 | 10.93 | 25-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 07-SEP-16:00 | 29.47 | 14-SEP-07:10 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 10-OCT-16:00 | 60.78 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 05-NOV-16:00 | 79.75 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 | 12-DEC-16:17 | 88.51 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 44.15 | 116.82 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 93.17 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.11 | 26-FEB-16:19 | 116.81 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 30-MAR-16:00 | 64.45 | 19-MAR-06:53 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 17-APR-15:18 | 68.37 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 | 19-MAY-16:00 | 41.85 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.01 | 06-JUN-15:20 | 31.16 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.15 | 08-JUL-15:20 | 15.80 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.71 | 02-AUG-16:00 | 12.96 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 07-SEP-16:00 | 29.57 | 14-SEP-07:10 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 10-OCT-16:00 | 60.77 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 05-NOV-16:00 | 79.74 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | 12-DEC-14:00 | 88.50 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.96 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 44.15 | 116.81 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 31-JAN-15:00 | 112.24 | 27-JAN-07:52 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 | 26-FEB-15:00 | 140.80 | 12-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.64 | 30-MAR-14:00 | 78.05 | 19-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.46 | 12-APR-14:00 | 84.18 | 06-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.25 | 30-MAY-14:00 | 54.95 | 11-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.34 | 06-JUN-15:00 | 43.99 | 10-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.07 | 08-JUL-16:00 | 21.95 | 28-JUL-23:00 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.94 | 01-AUG-17:00 | 18.25 | 25-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.15 | 07-SEP-15:00 | 40.59 | 29-SEP-04:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.48 | 10-OCT-16:00 | 73.97 | 26-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 | 19-NOV-15:00 | 95.99 | 22-NOV-07:00 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 | 12-DEC-15:00 | 107.02 | 18-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 18.25 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.07 | 140.80 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 93.39 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 | 26-FEB-16:19 | 117.05 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 30-MAR-16:00 | 64.66 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 | 17-APR-15:20 | 68.58 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 | 19-MAY-16:00 | 42.05 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.85 | 06-JUN-15:20 | 31.35 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.88 | 08-JUL-16:00 | 14.12 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.43 | 01-AUG-16:50 | 10.01 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 07-SEP-16:00 | 29.41 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 | 10-OCT-16:00 | 60.98 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 | 05-NOV-16:00 | 79.96 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 12-DEC-16:19 | 88.72 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 43.88 | 117.05 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 93.39 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 | 26-FEB-16:17 | 117.04 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 30-MAR-16:00 | 64.65 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 | 17-APR-15:20 | 68.57 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.23 | 19-MAY-16:00 | 42.05 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.84 | 06-JUN-15:20 | 31.35 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.86 | 08-JUL-16:00 | 15.59 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.44 | 02-AUG-16:00 | 11.72 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 07-SEP-16:00 | 29.41 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 | 10-OCT-16:00 | 60.98 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 | 05-NOV-16:00 | 79.95 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 | 12-DEC-14:00 | 88.72 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.72 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 43.86 | 117.04 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 47.78 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 | 26-FEB-16:20 | 59.89 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 | 30-MAR-16:00 | 33.08 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 | 17-APR-15:20 | 35.09 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.93 | 19-MAY-16:00 | 21.51 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 06-JUN-15:20 | 16.04 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.49 | 08-JUL-16:00 | 7.58 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 | 02-AUG-16:00 | 5.28 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.43 | 07-SEP-16:00 | 15.05 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.01 | 10-OCT-16:00 | 31.20 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 | 05-NOV-16:00 | 40.91 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 12-DEC-16:20 | 45.39 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 22.49 | 59.89 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 235.91 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.70 | 26-FEB-15:00 | 289.65 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.61 | 30-MAR-14:00 | 169.58 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.74 | 12-APR-14:00 | 180.24 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.73 | 19-MAY-14:00 | 117.88 | 11-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.28 | 06-JUN-15:00 | 93.91 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:49 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.60 | 08-JUL-16:00 | 51.39 | 28-JUL-23:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.68 | 01-AUG-15:00 | 40.01 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.61 | 07-SEP-12:00 | 88.01 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 | 10-OCT-16:00 | 160.96 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | 19-NOV-15:00 | 204.83 | 22-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 | 12-DEC-15:00 | 220.66 | 18-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 98.60 | 289.65 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 238.36 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.11 | 26-FEB-15:00 | 292.41 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.56 | 30-MAR-14:00 | 172.30 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.71 | 12-APR-14:00 | 182.23 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.84 | 19-MAY-14:00 | 119.71 | 11-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.40 | 06-JUN-15:00 | 95.40 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:49 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.53 | 08-JUL-16:00 | 51.39 | 28-JUL-23:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.77 | 01-AUG-15:00 | 41.59 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.63 | 07-SEP-12:00 | 89.51 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.05 | 10-OCT-16:00 | 163.17 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.01 | 19-NOV-15:00 | 207.30 | 22-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 12-DEC-15:00 | 223.06 | 18-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.59 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 96.53 | 292.41 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 225.29 | 27-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 5.84 | 26-FEB-15:00 | 277.53 | 12-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 23.64 | 30-MAR-14:30 | 162.49 | 19-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 30.94 | 12-APR-14:00 | 170.29 | 06-APR-05:00 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 41.31 | 19-MAY-15:50 | 111.65 | 11-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 63.77 | 06-JUN-15:00 | 88.07 | 10-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 78.32 | 08-JUL-15:00 | 46.02 | 28-JUL-23:40 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 68.43 | 02-AUG-16:00 | 38.16 | 25-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 47.87 | 07-SEP-16:00 | 83.78 | 29-SEP-04:00 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 37.44 | 10-OCT-16:00 | 153.54 | 26-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 2.00 | 05-NOV-16:00 | 195.34 | 22-NOV-06:00 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 215.70 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 38.16 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 78.32 | 277.53 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 199.06 | 27-JAN-07:52 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 | 26-FEB-15:00 | 249.62 | 12-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.06 | 30-MAR-14:00 | 138.33 | 19-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 17-APR-15:40 | 151.64 | 06-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.36 | 19-MAY-14:00 | 102.35 | 11-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.34 | 06-JUN-15:00 | 83.38 | 10-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.59 | 08-JUL-15:00 | 45.06 | 28-JUL-23:20 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.88 | 02-AUG-16:00 | 37.40 | 25-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.77 | 07-SEP-16:00 | 77.24 | 29-SEP-04:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.55 | 10-OCT-16:00 | 132.87 | 26-OCT-05:00 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 | 19-NOV-15:00 | 170.30 | 22-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 189.82 | 18-DEC-07:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.40 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.59 | 249.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13060.96 | 31-JAN-21:00 | 8945.92 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12600.56 | 01-FEB-21:00 | 8945.92 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12122.68 | 30-MAR-18:10 | 62621.41 | 62552.56 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11957.42 | 14-APR-18:01 | 62621.41 | 62552.56 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13251.95 | 13-MAY-17:35 | 30671.71 | 26808.37 | 28390.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14152.39 | 25-JUN-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15017.60 | 20-JUL-18:10 | 53675.50 | 53616.48 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15840.98 | 27-AUG-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19598.68 | 28-SEP-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20558.48 | 12-OCT-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20638.16 | 08-NOV-22:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18522.78 | 01-DEC-21:53 | 71567.33 | 62552.56 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11957.42 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20638.16 | 71567.33 | 62552.56 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2040.04 | 29-JAN-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.28 |
February | 2410.31 | 21-FEB-14:25 | 519.79 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 |
March | 2384.59 | 30-MAR-13:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 17.27 | 0.00 |
April | 2511.41 | 17-APR-15:13 | 3898.44 | 853.86 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 0.00 |
May | 2032.85 | 16-MAY-18:05 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 21.51 | 0.00 |
June | 2267.89 | 13-JUN-18:03 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 39.35 | 0.00 |
July | 2572.13 | 07-JUL-18:17 | 2728.91 | 1366.17 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 0.00 |
August | 2891.29 | 19-AUG-13:40 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 47.82 | 0.00 |
September | 3014.25 | 24-SEP-12:30 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 | 0.00 |
October | 3178.90 | 10-OCT-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 0.00 |
November | 2565.01 | 08-NOV-13:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 |
December | 2354.86 | 10-DEC-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2032.85 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3178.90 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 54.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1317.58 | 31-JAN-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 |
February | 1453.30 | 28-FEB-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 |
March | 1565.65 | 30-MAR-18:10 | 7373.52 | 3691.40 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | 0.00 |
April | 1613.19 | 13-APR-16:04 | 3762.00 | 823.97 | 1462.51 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 | 0.00 |
May | 1703.08 | 19-MAY-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
June | 1840.87 | 27-JUN-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 | 0.00 |
July | 2007.52 | 07-JUL-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 | 0.00 |
August | 2055.06 | 18-AUG-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 | 0.00 |
September | 1922.83 | 08-SEP-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | 0.00 |
October | 1686.05 | 11-OCT-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 |
November | 1440.39 | 06-NOV-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 |
December | 1412.74 | 12-DEC-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1317.58 | 1053.36 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2055.06 | 7373.52 | 3691.40 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 | 22.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 164.53 | 20-JAN-22:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.41 |
February | 714.82 | 28-FEB-22:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 |
March | 1056.82 | 30-MAR-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
April | 1079.13 | 19-APR-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.24 |
May | 1336.95 | 30-MAY-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 1626.01 | 13-JUN-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 | 0.00 |
July | 1809.73 | 07-JUL-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 0.00 |
August | 1779.46 | 18-AUG-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 32.22 | 0.00 |
September | 1610.51 | 07-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 | 0.00 |
October | 1217.55 | 18-OCT-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.28 |
November | 822.84 | 03-NOV-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.20 |
December | 675.98 | 13-DEC-22:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 164.53 | 222.77 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1809.73 | 254.59 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 32.22 | 59.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 676.45 | 31-JAN-21:00 | 171.36 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 |
February | 748.09 | 28-FEB-11:35 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 0.00 |
March | 850.81 | 30-MAR-18:10 | 1199.52 | 1174.19 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 11.03 | 0.00 |
April | 915.86 | 13-APR-16:04 | 612.00 | 262.09 | 446.08 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 | 0.00 |
May | 942.22 | 16-MAY-16:56 | 979.20 | 419.35 | 713.73 | 0.00 | 0.00 | 0.00 | 0.00 | 18.66 | 0.00 |
June | 1007.94 | 25-JUN-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 0.00 |
July | 1036.14 | 08-JUL-10:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 26.93 | 0.00 |
August | 1040.97 | 19-AUG-10:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 23.87 | 0.00 |
September | 992.01 | 09-SEP-10:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 | 0.00 |
October | 879.69 | 11-OCT-10:35 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 | 0.00 |
November | 789.17 | 05-NOV-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 |
December | 748.90 | 13-DEC-11:35 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 676.45 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1040.97 | 1199.52 | 1174.19 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 26.93 | 11.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37490.09 | 31-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 44.66 |
February | 37983.67 | 28-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 21.82 |
March | 38382.08 | 30-MAR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 2.51 | 0.00 |
April | 38529.37 | 17-APR-20:00 | 1411.20 | 801.37 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
May | 38869.63 | 19-MAY-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 10.12 | 0.00 |
June | 39218.17 | 13-JUN-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 33.71 | 0.00 |
July | 39433.14 | 07-JUL-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 44.00 | 0.00 |
August | 39339.09 | 18-AUG-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 47.61 | 0.00 |
September | 39109.19 | 07-SEP-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 20.06 | 0.00 |
October | 38520.36 | 10-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 11.51 |
November | 37890.37 | 03-NOV-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 33.16 |
December | 37746.96 | 12-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 37.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37490.09 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39433.14 | 1411.20 | 801.37 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 47.61 | 44.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10255.21 | 29-JAN-11:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.13 |
February | 10662.31 | 26-FEB-11:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.85 |
March | 10888.89 | 30-MAR-15:11 | 59766.00 | 673.09 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 51.95 | 0.00 |
April | 11902.71 | 13-APR-16:04 | 42690.00 | 480.78 | 1778.13 | 0.00 | 0.00 | 0.00 | 0.00 | 43.64 | 0.00 |
May | 11330.74 | 13-MAY-15:11 | 35859.60 | 673.09 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 52.36 | 0.00 |
June | 11086.41 | 24-JUN-17:40 | 10245.60 | 230.77 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 109.99 | 0.00 |
July | 11643.69 | 08-JUL-17:20 | 20491.20 | 461.55 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 128.20 | 0.00 |
August | 11651.50 | 02-AUG-18:10 | 71719.20 | 1846.19 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 110.76 | 0.00 |
September | 11607.54 | 24-SEP-10:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 51.19 | 0.00 |
October | 11440.60 | 10-OCT-15:35 | 17076.00 | 192.31 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 65.36 | 0.00 |
November | 11089.65 | 11-NOV-11:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.75 |
December | 10638.72 | 10-DEC-11:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10255.21 | 10245.60 | 192.31 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11902.71 | 71719.20 | 1846.19 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 128.20 | 122.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28371.00 | 31-JAN-21:00 | 35484.54 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.98 |
February | 30278.76 | 28-FEB-21:00 | 35484.54 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.25 |
March | 32354.75 | 30-MAR-21:07 | 136868.94 | 15968.07 | 22169.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.18 |
April | 33401.67 | 13-APR-16:04 | 126730.50 | 9536.49 | 18474.86 | 0.00 | 0.00 | 0.00 | 0.00 | 124.33 | 0.00 |
May | 33684.24 | 13-MAY-17:35 | 121661.28 | 18677.70 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 96.61 | 0.00 |
June | 35940.64 | 13-JUN-22:00 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 102.14 | 0.00 |
July | 38119.75 | 07-JUL-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 201.63 | 0.00 |
August | 39155.72 | 18-AUG-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 214.47 | 0.00 |
September | 37376.55 | 07-SEP-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 44.76 | 0.00 |
October | 34452.06 | 10-OCT-21:10 | 91245.96 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.38 |
November | 30095.54 | 08-NOV-21:00 | 35484.54 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.24 |
December | 29887.64 | 12-DEC-21:00 | 35484.54 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 28371.00 | 35484.54 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39155.72 | 136868.94 | 18677.70 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 214.47 | 283.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3105.45 | 28-JAN-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.09 |
February | 3203.77 | 27-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
March | 3166.72 | 10-MAR-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 |
April | 3199.05 | 09-APR-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 |
May | 3185.27 | 09-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.84 |
June | 2803.94 | 26-JUN-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
July | 2806.84 | 27-JUL-15:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 | 0.00 |
August | 2800.70 | 07-AUG-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 | 0.00 |
September | 2851.77 | 09-SEP-18:02 | 702.00 | 568.30 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 0.00 |
October | 3020.44 | 31-OCT-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.52 |
November | 3154.71 | 14-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 |
December | 3110.81 | 09-DEC-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2800.70 | 378.00 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3203.77 | 970.20 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 | 32.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1580.23 | 14-JAN-16:17 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.68 |
February | 2866.06 | 24-FEB-19:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.64 |
March | 3063.09 | 18-MAR-18:01 | 819.00 | 662.94 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 |
April | 3304.88 | 26-APR-18:41 | 1247.40 | 758.59 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 |
May | 3320.03 | 09-MAY-20:41 | 1602.00 | 842.88 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 |
June | 2814.52 | 16-JUN-21:51 | 1260.00 | 444.17 | 626.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 | 0.00 |
July | 2822.12 | 02-JUL-21:51 | 970.20 | 563.50 | 626.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 2850.07 | 08-AUG-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 | 0.00 |
September | 3075.59 | 18-SEP-16:01 | 972.00 | 265.18 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 0.00 |
October | 2936.06 | 15-OCT-16:21 | 858.60 | 281.28 | 948.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 0.00 |
November | 2806.72 | 06-NOV-19:12 | 693.00 | 421.44 | 605.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 |
December | 2834.70 | 09-DEC-16:11 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1580.23 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3320.03 | 1602.00 | 842.88 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 | 56.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 261.87 | 29-JAN-13:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.64 |
February | 373.43 | 26-FEB-14:25 | 0.00 | 39.29 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.66 |
March | 350.98 | 13-MAR-16:10 | 0.00 | 16.67 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
April | 328.39 | 15-APR-13:50 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 0.00 |
May | 268.99 | 19-MAY-17:20 | 0.00 | 79.76 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 | 0.00 |
June | 305.81 | 13-JUN-17:20 | 0.00 | 79.76 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 4.72 | 0.00 |
July | 343.71 | 08-JUL-17:30 | 0.00 | 50.60 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 6.13 | 0.00 |
August | 383.72 | 19-AUG-13:40 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 0.00 |
September | 449.80 | 24-SEP-12:40 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
October | 486.96 | 10-OCT-13:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 0.00 |
November | 429.80 | 15-NOV-14:00 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 |
December | 409.84 | 10-DEC-14:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 261.87 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 486.96 | 0.00 | 79.76 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 6.13 | 10.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 845.41 | 01-JAN-09:02 | 216.00 | 133.37 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 |
February | 1064.09 | 28-FEB-22:52 | 1080.00 | 239.36 | 526.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 |
March | 1062.26 | 31-MAR-20:12 | 961.20 | 317.95 | 1068.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 |
April | 1061.81 | 09-APR-20:11 | 1247.40 | 535.88 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 |
May | 1139.75 | 09-MAY-20:41 | 1602.00 | 529.92 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 |
June | 1024.35 | 03-JUN-15:12 | 324.00 | 117.89 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 0.00 |
July | 1024.98 | 18-JUL-15:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 | 0.00 |
August | 1027.39 | 17-AUG-15:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 | 0.00 |
September | 1026.93 | 04-SEP-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 0.00 |
October | 1073.75 | 11-OCT-21:51 | 1260.00 | 279.25 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 |
November | 1011.82 | 28-NOV-19:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.95 |
December | 870.93 | 31-DEC-09:02 | 324.00 | 200.06 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 845.41 | 216.00 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1139.75 | 1602.00 | 535.88 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 | 13.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2765.13 | 29-JAN-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 |
February | 2903.57 | 27-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | 0.00 |
March | 2876.92 | 10-MAR-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
April | 2878.10 | 09-APR-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 |
May | 2876.90 | 09-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 |
June | 2643.20 | 05-JUN-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 | 0.00 |
July | 2675.45 | 21-JUL-08:61 | 360.00 | 416.75 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 | 0.00 |
August | 2650.96 | 01-AUG-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 10.49 | 0.00 |
September | 2603.70 | 09-SEP-08:62 | 324.00 | 318.25 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 | 0.00 |
October | 2591.81 | 31-OCT-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 |
November | 2851.42 | 14-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 |
December | 2726.06 | 09-DEC-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2591.81 | 252.00 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2903.57 | 970.20 | 663.02 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 10.49 | 28.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1704.60 | 28-JAN-09:06 | 378.00 | 371.25 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.61 |
February | 2325.10 | 27-FEB-22:42 | 900.00 | 317.26 | 447.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.42 |
March | 2603.81 | 12-MAR-19:01 | 819.00 | 662.94 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.11 |
April | 2787.20 | 14-APR-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 |
May | 2948.34 | 16-MAY-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 |
June | 2966.36 | 04-JUN-08:51 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 |
July | 2780.81 | 17-JUL-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 | 0.00 |
August | 2829.34 | 26-AUG-08:51 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 |
September | 2857.45 | 15-SEP-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 |
October | 2594.07 | 11-OCT-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 | 0.00 |
November | 2451.01 | 11-NOV-09:01 | 378.00 | 371.25 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.33 |
December | 1760.52 | 02-DEC-09:04 | 378.00 | 371.25 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1704.60 | 360.00 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2966.36 | 900.00 | 662.94 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 | 73.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1405.01 | 31-JAN-19:00 | 1257.42 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 |
February | 1643.21 | 27-FEB-19:10 | 12322.72 | 7217.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.45 |
March | 1842.95 | 30-MAR-18:10 | 12322.72 | 7217.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.02 | 0.00 |
April | 2044.18 | 13-APR-16:04 | 6287.10 | 1611.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 0.00 |
May | 2079.42 | 16-MAY-16:56 | 10059.36 | 2577.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.39 | 0.00 |
June | 2183.95 | 25-JUN-10:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.21 | 0.00 |
July | 2255.49 | 08-JUL-17:50 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.14 | 0.00 |
August | 2268.13 | 19-AUG-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.61 | 0.00 |
September | 2159.21 | 09-SEP-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 | 0.00 |
October | 1916.75 | 11-OCT-18:10 | 12322.72 | 7217.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 |
November | 1635.04 | 11-NOV-11:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 |
December | 1513.37 | 12-DEC-11:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1405.01 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2268.13 | 12322.72 | 7217.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.14 | 11.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3253.95 | 28-JAN-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.10 |
February | 3372.19 | 27-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
March | 3330.69 | 10-MAR-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 |
April | 3370.41 | 09-APR-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.78 |
May | 3345.76 | 09-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 |
June | 2909.72 | 26-JUN-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 | 0.00 |
July | 2963.58 | 07-JUL-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 | 0.00 |
August | 2961.74 | 18-AUG-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 30.88 | 0.00 |
September | 2976.85 | 09-SEP-18:02 | 702.00 | 568.30 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 | 0.00 |
October | 3189.82 | 31-OCT-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.86 |
November | 3314.26 | 14-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 |
December | 3263.57 | 09-DEC-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2909.72 | 378.00 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3372.19 | 970.20 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 | 32.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 897.20 | 10-JAN-16:14 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.37 |
February | 2992.37 | 24-FEB-19:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.53 |
March | 3222.17 | 12-MAR-19:01 | 819.00 | 662.94 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 |
April | 3486.31 | 26-APR-18:41 | 1247.40 | 758.59 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 |
May | 3569.49 | 09-MAY-20:41 | 1602.00 | 842.88 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 |
June | 2937.67 | 07-JUN-21:51 | 1620.00 | 571.07 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 |
July | 2962.71 | 02-JUL-21:51 | 970.20 | 563.50 | 626.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
August | 2972.18 | 08-AUG-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 | 0.00 |
September | 3216.35 | 18-SEP-16:01 | 972.00 | 265.18 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | 0.00 |
October | 3140.69 | 15-OCT-16:21 | 858.60 | 281.28 | 948.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 |
November | 2624.77 | 06-NOV-19:12 | 693.00 | 421.44 | 605.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 |
December | 1750.50 | 07-DEC-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 897.20 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3569.49 | 1620.00 | 842.88 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 | 52.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1698.52 | 29-JAN-16:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.10 |
February | 1712.10 | 28-FEB-19:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 |
March | 1728.23 | 10-MAR-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
April | 1712.40 | 09-APR-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 |
May | 1708.23 | 10-MAY-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 |
June | 1533.76 | 15-JUN-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 | 0.00 |
July | 1547.45 | 27-JUL-15:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | 0.00 |
August | 1543.34 | 08-AUG-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 | 0.00 |
September | 1550.56 | 04-SEP-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.03 | 0.00 |
October | 1692.77 | 12-OCT-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.41 |
November | 1726.50 | 14-NOV-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 |
December | 1705.89 | 19-DEC-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1533.76 | 378.00 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1728.23 | 970.20 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 | 13.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17549.58 | 19-JAN-23:10 | 26988.77 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.12 |
February | 18377.68 | 28-FEB-22:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.03 |
March | 20716.50 | 30-MAR-21:07 | 80966.30 | 5526.25 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 |
April | 21012.23 | 13-APR-16:04 | 74968.80 | 2302.60 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 0.00 |
May | 21327.07 | 13-MAY-17:35 | 71970.05 | 4421.00 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 0.00 |
June | 21699.43 | 13-JUN-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 | 0.00 |
July | 22168.26 | 07-JUL-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.64 | 0.00 |
August | 21905.02 | 18-AUG-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.65 | 0.00 |
September | 20913.06 | 06-SEP-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 18.60 | 0.00 |
October | 20417.21 | 18-OCT-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 |
November | 18249.52 | 03-NOV-21:54 | 134943.84 | 9210.41 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.84 |
December | 17952.46 | 12-DEC-23:10 | 26988.77 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17549.58 | 26988.77 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22168.26 | 134943.84 | 9210.41 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 37.65 | 46.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18897.84 | 19-JAN-22:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.27 |
February | 20306.34 | 28-FEB-22:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.09 |
March | 21404.00 | 30-MAR-21:53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 |
April | 21630.94 | 13-APR-16:04 | 74968.80 | 2302.60 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 0.00 |
May | 21994.15 | 18-MAY-21:53 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 |
June | 23087.56 | 13-JUN-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 | 0.00 |
July | 23547.13 | 07-JUL-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 43.17 | 0.00 |
August | 23265.63 | 18-AUG-21:30 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 43.53 | 0.00 |
September | 22290.66 | 06-SEP-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 18.60 | 0.00 |
October | 21405.71 | 18-OCT-21:53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.46 |
November | 20285.49 | 03-NOV-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.59 |
December | 20026.86 | 12-DEC-22:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18897.84 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23547.13 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 43.53 | 43.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26063.20 | 29-JAN-11:35 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 80.01 |
February | 27187.12 | 26-FEB-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 |
March | 27586.81 | 30-MAR-18:03 | 13075.94 | 6787.40 | 102231.89 | 104966.55 | 0.00 | 0.00 | 0.00 | 12.28 | 0.00 |
April | 30420.01 | 13-APR-16:04 | 6671.40 | 1515.04 | 73022.78 | 112464.16 | 0.00 | 0.00 | 0.00 | 14.15 | 0.00 |
May | 30551.22 | 13-MAY-17:35 | 6404.54 | 2908.88 | 58418.22 | 89971.33 | 0.00 | 0.00 | 0.00 | 8.84 | 0.00 |
June | 29472.13 | 25-JUN-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 36.33 | 0.00 |
July | 29856.35 | 08-JUL-10:50 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 58.97 | 0.00 |
August | 29758.62 | 27-AUG-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 34.06 | 0.00 |
September | 29279.10 | 09-SEP-10:50 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 39.48 | 0.00 |
October | 28171.40 | 09-OCT-10:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
November | 26827.53 | 11-NOV-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 |
December | 26329.61 | 12-DEC-11:50 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 25.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26063.20 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30551.22 | 13075.94 | 6787.40 | 102231.89 | 112464.16 | 0.00 | 0.00 | 0.00 | 58.97 | 80.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1702.99 | 31-JAN-21:00 | 1863.12 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.72 |
February | 2063.21 | 28-FEB-18:15 | 2661.60 | 1636.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 |
March | 3482.36 | 30-MAR-15:10 | 2661.60 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.06 | 0.00 |
April | 5527.25 | 17-APR-15:13 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.91 | 0.00 |
May | 5371.27 | 16-MAY-15:35 | 5323.20 | 1364.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.44 | 0.00 |
June | 5437.65 | 13-JUN-15:40 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.09 | 0.00 |
July | 6176.49 | 08-JUL-16:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.26 | 0.00 |
August | 6149.17 | 18-AUG-15:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.58 | 0.00 |
September | 5393.72 | 07-SEP-15:13 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.76 | 0.00 |
October | 4161.20 | 10-OCT-15:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 | 0.00 |
November | 2091.99 | 05-NOV-17:15 | 2129.28 | 1364.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 |
December | 1908.08 | 13-DEC-11:35 | 1064.64 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1702.99 | 1064.64 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6176.49 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.26 | 33.72 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.462125E+12 | 306368.27 | 02-JAN-07:40 | 0.384406E+12 | 342332.89 | 30-JAN-18:19 |
February | 0.390797E+12 | 305130.73 | 12-FEB-07:10 | 0.347569E+12 | 342342.08 | 01-FEB-18:30 |
March | 0.398744E+12 | 281279.57 | 06-MAR-07:30 | 0.379073E+12 | 339491.03 | 01-MAR-18:30 |
April | 0.410863E+12 | 322776.78 | 06-APR-06:10 | 0.355993E+12 | 330517.13 | 03-APR-17:30 |
May | 0.471781E+12 | 310605.43 | 30-MAY-18:10 | 0.354865E+12 | 319442.57 | 01-MAY-17:19 |
June | 0.541888E+12 | 341675.53 | 28-JUN-18:10 | 0.332130E+12 | 305675.41 | 08-JUN-17:10 |
July | 0.610401E+12 | 358783.06 | 06-JUL-18:10 | 0.335869E+12 | 295452.90 | 07-JUL-17:30 |
August | 0.629299E+12 | 354012.93 | 18-AUG-18:19 | 0.335603E+12 | 295193.83 | 31-AUG-17:30 |
September | 0.508176E+12 | 336084.83 | 07-SEP-18:00 | 0.330526E+12 | 303550.31 | 29-SEP-17:19 |
October | 0.423122E+12 | 322869.78 | 18-OCT-19:00 | 0.352704E+12 | 316156.92 | 31-OCT-17:49 |
November | 0.396278E+12 | 301885.03 | 14-NOV-07:10 | 0.354100E+12 | 328611.71 | 30-NOV-18:49 |
December | 0.437002E+12 | 313873.13 | 07-DEC-07:19 | 0.377282E+12 | 338388.96 | 29-DEC-18:49 |
Annual Sum or Average | 0.568048E+13 | 0.424012E+13 | ||||
Minimum of Months | 0.390797E+12 | 281279.57 | 0.330526E+12 | 295193.83 | ||
Maximum of Months | 0.629299E+12 | 358783.06 | 0.384406E+12 | 342342.08 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.469146E+11 | 0.192036E+11 | 0.140003E+12 | 0.690929E+11 | 0.460105E+11 | 0.240430E+10 | 0.113646E+12 | 0.353086E+10 | 0.00 | 0.00 | 0.955208E+10 | 0.804707E+10 | 0.00 |
February | 0.423283E+11 | 0.163904E+11 | 0.126445E+12 | 0.624066E+11 | 0.418433E+11 | 0.366074E+10 | 0.697980E+11 | 0.115398E+11 | 0.00 | 0.00 | 0.575077E+10 | 0.727159E+10 | 0.00 |
March | 0.464568E+11 | 0.167606E+11 | 0.140056E+12 | 0.690952E+11 | 0.473426E+11 | 0.686765E+10 | 0.236595E+11 | 0.342056E+11 | 0.00 | 0.00 | 0.251793E+10 | 0.804567E+10 | 0.00 |
April | 0.445793E+11 | 0.148358E+11 | 0.135446E+12 | 0.668634E+11 | 0.473197E+11 | 0.765533E+10 | 0.117964E+11 | 0.668066E+11 | 0.00 | 0.00 | 0.413444E+10 | 0.779699E+10 | 0.00 |
May | 0.457970E+11 | 0.141251E+11 | 0.140035E+12 | 0.690935E+11 | 0.509463E+11 | 0.835322E+10 | 0.810735E+09 | 0.122701E+12 | 0.00 | 0.00 | 0.809698E+10 | 0.804707E+10 | 0.00 |
June | 0.441798E+11 | 0.131404E+11 | 0.135537E+12 | 0.668655E+11 | 0.525805E+11 | 0.844454E+10 | 0.249453E+09 | 0.194158E+12 | 0.00 | 0.00 | 0.152855E+11 | 0.778857E+10 | 0.00 |
July | 0.456894E+11 | 0.137771E+11 | 0.139944E+12 | 0.690910E+11 | 0.554644E+11 | 0.895402E+10 | 26477728.16 | 0.245973E+12 | 0.00 | 0.00 | 0.196575E+11 | 0.805551E+10 | 0.00 |
August | 0.459470E+11 | 0.147839E+11 | 0.140067E+12 | 0.690949E+11 | 0.564438E+11 | 0.906663E+10 | 9458725.70 | 0.261519E+12 | 0.00 | 0.00 | 0.205348E+11 | 0.804707E+10 | 0.00 |
September | 0.448439E+11 | 0.156205E+11 | 0.135457E+12 | 0.668636E+11 | 0.511407E+11 | 0.829345E+10 | 0.274479E+09 | 0.162113E+12 | 0.00 | 0.00 | 0.121086E+11 | 0.779842E+10 | 0.00 |
October | 0.467429E+11 | 0.175749E+11 | 0.139992E+12 | 0.690928E+11 | 0.495047E+11 | 0.764816E+10 | 0.824202E+10 | 0.673620E+11 | 0.00 | 0.00 | 0.515542E+10 | 0.804567E+10 | 0.00 |
November | 0.453465E+11 | 0.182634E+11 | 0.135531E+12 | 0.668648E+11 | 0.464262E+11 | 0.607783E+10 | 0.372216E+11 | 0.259679E+11 | 0.00 | 0.00 | 0.318707E+10 | 0.778013E+10 | 0.00 |
December | 0.468706E+11 | 0.195441E+11 | 0.139944E+12 | 0.690918E+11 | 0.462959E+11 | 0.372155E+10 | 0.877681E+11 | 0.730948E+10 | 0.00 | 0.00 | 0.467490E+10 | 0.805552E+10 | 0.00 |
Annual Sum or Average | 0.545696E+12 | 0.194020E+12 | 0.164846E+13 | 0.813516E+12 | 0.591318E+12 | 0.811474E+11 | 0.353502E+12 | 0.120319E+13 | 0.00 | 0.00 | 0.110656E+12 | 0.947793E+11 | 0.00 |
Minimum of Months | 0.423283E+11 | 0.131404E+11 | 0.126445E+12 | 0.624066E+11 | 0.418433E+11 | 0.240430E+10 | 9458725.70 | 0.353086E+10 | 0.00 | 0.00 | 0.251793E+10 | 0.727159E+10 | 0.00 |
Maximum of Months | 0.469146E+11 | 0.195441E+11 | 0.140067E+12 | 0.690952E+11 | 0.564438E+11 | 0.906663E+10 | 0.113646E+12 | 0.261519E+12 | 0.00 | 0.00 | 0.205348E+11 | 0.805552E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.00 | 0.00 | 0.232488E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.00 | 0.00 | 0.210365E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.00 | 0.00 | 0.227049E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.00 | 0.00 | 0.209038E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.00 | 0.00 | 0.202886E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.00 | 0.00 | 0.185016E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.00 | 0.00 | 0.184049E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.00 | 0.00 | 0.183564E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.00 | 0.00 | 0.183555E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.00 | 0.00 | 0.200801E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.00 | 0.00 | 0.207009E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.00 | 0.00 | 0.225462E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.00 | 0.00 | 0.245128E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.00 | 0.00 | 0.183555E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.00 | 0.00 | 0.232488E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 45764.37 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 49590.83 | 02-JAN-07:19 | 28012.72 | 06-JAN-19:10 | 3055.37 | 31-JAN-13:00 | 133727.51 | 03-JAN-10:50 |
February | 45764.37 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 49590.83 | 01-FEB-07:19 | 26738.33 | 03-FEB-19:10 | 3146.45 | 26-FEB-16:19 | 128034.60 | 03-FEB-16:19 |
March | 45764.37 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 49590.83 | 01-MAR-07:19 | 28829.08 | 30-MAR-21:00 | 3435.86 | 13-MAR-16:30 | 97237.29 | 19-MAR-06:40 |
April | 45764.37 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 49590.83 | 03-APR-06:19 | 28875.73 | 17-APR-21:00 | 3653.46 | 12-APR-15:50 | 117205.40 | 06-APR-06:19 |
May | 45764.37 | 01-MAY-19:19 | 12338.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 49590.45 | 08-MAY-06:19 | 30972.53 | 31-MAY-21:00 | 3712.94 | 15-MAY-18:00 | 25083.56 | 16-MAY-13:50 |
June | 45764.37 | 01-JUN-19:40 | 12338.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 49590.26 | 23-JUN-06:19 | 34113.11 | 13-JUN-21:40 | 3932.10 | 28-JUN-18:10 | 42904.42 | 08-JUN-14:50 |
July | 45764.37 | 03-JUL-19:49 | 12338.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 49590.38 | 28-JUL-06:19 | 35907.87 | 07-JUL-21:19 | 4079.47 | 06-JUL-18:10 | 2090.18 | 28-JUL-10:50 |
August | 45764.37 | 01-AUG-19:40 | 12338.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 49590.83 | 25-AUG-06:19 | 37294.75 | 18-AUG-21:19 | 4028.74 | 10-AUG-18:10 | 1426.77 | 30-AUG-21:00 |
September | 45764.37 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 49590.83 | 01-SEP-06:19 | 36670.37 | 07-SEP-21:19 | 3875.63 | 07-SEP-18:10 | 15943.98 | 22-SEP-14:50 |
October | 45764.37 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 49590.83 | 02-OCT-06:19 | 32166.67 | 10-OCT-21:00 | 3659.28 | 18-OCT-18:30 | 103584.32 | 26-OCT-06:40 |
November | 45764.37 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 49590.83 | 01-NOV-06:19 | 28167.65 | 08-NOV-21:19 | 3280.04 | 05-NOV-15:39 | 113607.83 | 25-NOV-06:10 |
December | 45764.37 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 49590.83 | 01-DEC-07:19 | 27103.20 | 13-DEC-21:10 | 3078.04 | 13-DEC-11:39 | 121640.89 | 21-DEC-09:09 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45764.37 | 12338.45 | 88863.15 | 49590.26 | 26738.33 | 3055.37 | 1426.77 | |||||||
Maximum of Months | 45764.37 | 12338.45 | 88863.15 | 49590.83 | 37294.75 | 4079.47 | 133727.51 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 35579.36 | 19-JAN-20:00 | 0.00 | 0.00 | 8265.52 | 05-JAN-00:10 | 4751.12 | 10-JAN-07:49 | 0.00 |
February | 65618.44 | 26-FEB-16:19 | 0.00 | 0.00 | 8265.52 | 01-FEB-06:10 | 4751.13 | 21-FEB-07:40 | 0.00 |
March | 92031.10 | 30-MAR-15:30 | 0.00 | 0.00 | 8265.52 | 11-MAR-13:30 | 4751.12 | 13-MAR-06:40 | 0.00 |
April | 93163.30 | 17-APR-18:10 | 0.00 | 0.00 | 8265.52 | 02-APR-12:50 | 4751.13 | 03-APR-06:40 | 0.00 |
May | 122371.83 | 30-MAY-18:10 | 0.00 | 0.00 | 8265.52 | 01-MAY-15:39 | 4751.13 | 08-MAY-06:40 | 0.00 |
June | 152303.37 | 28-JUN-18:10 | 0.00 | 0.00 | 8265.52 | 01-JUN-08:30 | 4751.13 | 19-JUN-06:40 | 0.00 |
July | 168606.43 | 06-JUL-18:10 | 0.00 | 0.00 | 8265.52 | 01-JUL-00:10 | 4751.13 | 03-JUL-06:40 | 0.00 |
August | 162945.11 | 17-AUG-18:10 | 0.00 | 0.00 | 8265.52 | 01-AUG-00:10 | 4751.13 | 28-AUG-06:40 | 0.00 |
September | 146568.42 | 07-SEP-15:30 | 0.00 | 0.00 | 8265.52 | 01-SEP-09:20 | 4751.13 | 18-SEP-06:40 | 0.00 |
October | 129725.94 | 18-OCT-21:00 | 0.00 | 0.00 | 8265.52 | 01-OCT-15:30 | 4751.13 | 23-OCT-06:40 | 0.00 |
November | 80294.58 | 05-NOV-15:20 | 0.00 | 0.00 | 8265.52 | 05-NOV-15:20 | 4751.13 | 27-NOV-07:40 | 0.00 |
December | 46458.72 | 13-DEC-11:39 | 0.00 | 0.00 | 8265.52 | 01-DEC-00:49 | 4751.13 | 11-DEC-07:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 35579.36 | 0.00 | 0.00 | 8265.52 | 4751.12 | 0.00 | |||
Maximum of Months | 168606.43 | 0.00 | 0.00 | 8265.52 | 4751.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 306368.27 | 02-JAN-07:40 | 25474.78 | 88863.15 | 12338.45 | 49590.83 | 20086.46 | 2249.50 | 97398.15 | 2796.78 | 0.00 |
February | 305130.73 | 12-FEB-07:10 | 19950.89 | 72981.59 | 12338.45 | 49251.47 | 17925.92 | 47.91 | 119125.39 | 0.00 | 0.00 |
March | 281279.57 | 06-MAR-07:30 | 24693.92 | 88863.15 | 0.00 | 49590.50 | 19983.38 | 2249.16 | 85559.19 | 2775.96 | 0.00 |
April | 322776.78 | 06-APR-06:10 | 25474.78 | 88863.15 | 12338.45 | 49586.49 | 20515.27 | 2985.38 | 110665.90 | 4776.70 | 0.00 |
May | 310605.43 | 30-MAY-18:10 | 36875.77 | 77265.07 | 0.00 | 28142.63 | 27944.21 | 3663.33 | 0.00 | 122371.83 | 0.00 |
June | 341675.53 | 28-JUN-18:10 | 36642.55 | 77265.07 | 0.00 | 28142.52 | 28682.98 | 3932.10 | 0.00 | 152303.37 | 0.00 |
July | 358783.06 | 06-JUL-18:10 | 36642.55 | 77265.07 | 0.00 | 28142.52 | 29340.55 | 4079.47 | 0.00 | 168606.43 | 0.00 |
August | 354012.93 | 18-AUG-18:19 | 36865.54 | 77265.07 | 0.00 | 28149.01 | 30800.04 | 3849.27 | 0.00 | 162740.97 | 0.00 |
September | 336084.83 | 07-SEP-18:00 | 40691.94 | 77265.07 | 12338.45 | 28151.58 | 28262.87 | 3745.94 | 0.00 | 130922.83 | 0.00 |
October | 322869.78 | 18-OCT-19:00 | 45764.37 | 86131.51 | 12338.45 | 10977.17 | 26529.29 | 3651.21 | 0.00 | 123563.66 | 0.00 |
November | 301885.03 | 14-NOV-07:10 | 25474.78 | 88863.15 | 12338.45 | 49586.49 | 21905.68 | 2985.16 | 88088.56 | 4188.94 | 0.00 |
December | 313873.13 | 07-DEC-07:19 | 25474.78 | 88863.15 | 12338.45 | 49590.83 | 19967.58 | 2249.40 | 105759.08 | 2057.79 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 281279.57 | 19950.89 | 72981.59 | 0.00 | 10977.17 | 17925.92 | 47.91 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 358783.06 | 45764.37 | 88863.15 | 12338.45 | 49590.83 | 30800.04 | 4079.47 | 119125.39 | 168606.43 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 0.00 | 0.00 | 240334.83 | 31-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 0.00 | 0.00 | 240337.15 | 02-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 0.00 | 0.00 | 238065.58 | 01-MAR-21:19 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 0.00 | 0.00 | 228129.19 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 0.00 | 0.00 | 216568.00 | 01-MAY-20:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 0.00 | 0.00 | 203969.01 | 01-JUN-20:49 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 0.00 | 0.00 | 193901.98 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 0.00 | 0.00 | 193750.44 | 31-AUG-20:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 0.00 | 0.00 | 202162.21 | 29-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 0.00 | 0.00 | 214979.59 | 31-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 0.00 | 0.00 | 226842.56 | 30-NOV-21:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 0.00 | 0.00 | 237157.40 | 28-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 104248.32 | 0.00 | 0.00 | 0.00 | 193750.44 | 0.00 | ||
Maximum of Months | 104248.32 | 0.00 | 0.00 | 0.00 | 240337.15 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.46 | 2.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 1.17 | 20.52 | 1.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.75 | 3.00 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.76 | 2.67 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.75 | 1.00 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.50 | 20.48 | 3.50 | 20.48 | 7.33 | 21.13 | 7.33 | 21.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.52 | 2.33 | 20.52 | 3.00 | 21.76 | 3.00 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 20.45 | 4.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
February | 2.17 | 20.47 | 2.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.73 | 2.67 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.77 | 5.83 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.73 | 2.67 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.84 | 0.33 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
November | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
December | 1.17 | 20.53 | 1.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Annual Sum or Average | 7.67 | 20.47 | 7.67 | 20.47 | 11.67 | 21.02 | 11.67 | 21.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 20.54 | 4.00 | 20.54 | 5.83 | 21.84 | 5.83 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.35 | 0.67 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
February | 0.33 | 20.33 | 0.33 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.76 | 2.00 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.74 | 7.00 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 21.78 | 10.33 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 21.75 | 5.33 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.79 | 1.33 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 20.34 | 1.00 | 20.34 | 26.83 | 21.66 | 26.83 | 21.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.35 | 0.67 | 20.35 | 10.33 | 21.79 | 10.33 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.45 | 2.17 | 20.45 | 0.17 | 20.50 | 0.17 | 20.55 |
February | 0.50 | 20.52 | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
Annual Sum or Average | 2.67 | 20.46 | 2.67 | 20.46 | 2.67 | 20.88 | 2.67 | 21.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 20.52 | 2.17 | 20.52 | 1.17 | 21.77 | 1.17 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 20.47 | 4.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 1.50 | 20.50 | 1.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 22.04 | 0.83 | 22.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 22.07 | 3.83 | 22.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 22.19 | 7.50 | 22.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 22.15 | 10.00 | 22.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 22.09 | 6.33 | 22.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 22.12 | 3.67 | 22.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.55 | 0.50 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Annual Sum or Average | 6.17 | 20.48 | 6.17 | 20.48 | 32.33 | 21.68 | 32.33 | 21.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.17 | 20.55 | 4.17 | 20.55 | 10.00 | 22.19 | 10.00 | 22.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.43 | 1.83 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
February | 0.50 | 20.47 | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.71 | 0.83 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.73 | 2.50 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.79 | 5.17 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.80 | 4.83 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.82 | 1.33 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 20.44 | 2.33 | 20.44 | 15.83 | 21.47 | 15.83 | 21.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.47 | 1.83 | 20.47 | 5.17 | 21.82 | 5.17 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.42 | 3.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
February | 1.33 | 20.40 | 1.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.70 | 1.00 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.75 | 4.17 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.80 | 7.50 | 21.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.77 | 4.33 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.86 | 0.50 | 21.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.81 | 0.17 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 5.00 | 20.42 | 5.00 | 20.42 | 17.83 | 21.29 | 17.83 | 21.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.52 | 3.33 | 20.52 | 7.50 | 21.86 | 7.50 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.47 | 0.83 | 20.47 | 0.67 | 20.84 | 0.67 | 21.04 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.84 | 1.17 | 21.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.84 | 0.83 | 21.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.75 | 1.67 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.75 | 2.17 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.82 | 4.50 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.86 | 3.00 | 21.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.86 | 3.17 | 21.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.81 | 1.00 | 21.81 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.79 | 1.33 | 21.79 |
Annual Sum or Average | 0.83 | 20.47 | 0.83 | 20.47 | 19.83 | 21.71 | 19.83 | 21.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.47 | 0.83 | 20.47 | 4.50 | 21.86 | 4.50 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.73 | 1.00 | 24.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.75 | 0.50 | 24.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.61 | 0.67 | 24.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 24.70 | 2.17 | 24.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.75 | 1.00 | 24.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
February | 672.00 | 22.17 | 0.00 | 22.17 | 0.00 | 22.17 |
March | 744.00 | 21.61 | 2.33 | 21.61 | 2.33 | 21.61 |
April | 720.00 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
May | 744.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
June | 720.00 | 22.36 | 0.67 | 22.36 | 0.67 | 22.36 |
July | 735.67 | 22.88 | 9.33 | 22.89 | 9.33 | 22.89 |
August | 383.17 | 23.22 | 229.17 | 23.41 | 79.00 | 23.44 |
September | 87.17 | 23.86 | 440.33 | 23.94 | 70.83 | 23.94 |
October | 130.00 | 23.79 | 237.67 | 23.90 | 20.83 | 23.91 |
November | 372.17 | 23.89 | 124.50 | 23.91 | 2.67 | 23.91 |
December | 633.17 | 23.66 | 26.33 | 23.67 | 0.00 | 23.67 |
Annual Sum or Average | 6685.33 | 22.44 | 1070.33 | 22.64 | 185.67 | 22.67 |
Minimum of Months | 87.17 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
Maximum of Months | 744.00 | 23.89 | 440.33 | 23.94 | 79.00 | 23.94 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 730.00 | 21.36 | 267.67 | 21.27 | 267.67 | 21.21 |
February | 627.33 | 21.53 | 165.17 | 21.43 | 162.67 | 21.36 |
March | 609.17 | 22.12 | 69.83 | 22.26 | 10.17 | 22.24 |
April | 503.50 | 22.34 | 131.17 | 22.65 | 11.50 | 22.65 |
May | 350.67 | 22.77 | 367.50 | 23.25 | 76.50 | 23.23 |
June | 190.67 | 23.45 | 586.17 | 23.78 | 117.17 | 23.78 |
July | 168.83 | 23.62 | 690.33 | 23.86 | 141.00 | 23.85 |
August | 162.83 | 23.94 | 742.50 | 23.96 | 162.83 | 23.95 |
September | 239.17 | 23.05 | 524.17 | 23.61 | 107.33 | 23.61 |
October | 460.00 | 22.23 | 220.17 | 22.75 | 36.50 | 22.78 |
November | 616.17 | 21.97 | 59.00 | 22.06 | 21.50 | 22.03 |
December | 693.33 | 21.52 | 108.00 | 21.49 | 97.67 | 21.43 |
Annual Sum or Average | 5351.67 | 22.12 | 3931.67 | 22.69 | 1212.50 | 22.66 |
Minimum of Months | 162.83 | 21.36 | 59.00 | 21.27 | 10.17 | 21.21 |
Maximum of Months | 730.00 | 23.94 | 742.50 | 23.96 | 267.67 | 23.95 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.42 | 6.83 | 21.42 | 6.83 | 21.42 |
February | 672.00 | 21.70 | 16.00 | 21.69 | 16.00 | 21.67 |
March | 719.67 | 22.27 | 6.33 | 22.29 | 0.00 | 22.29 |
April | 650.00 | 22.49 | 22.50 | 22.52 | 12.33 | 22.52 |
May | 555.00 | 22.69 | 165.67 | 22.87 | 81.67 | 22.91 |
June | 421.33 | 23.09 | 303.83 | 23.38 | 123.33 | 23.42 |
July | 353.00 | 23.20 | 399.67 | 23.52 | 149.00 | 23.56 |
August | 285.50 | 23.45 | 449.33 | 23.69 | 167.50 | 23.72 |
September | 394.50 | 22.97 | 268.00 | 23.28 | 102.50 | 23.32 |
October | 653.50 | 22.57 | 67.83 | 22.66 | 36.17 | 22.69 |
November | 711.83 | 22.25 | 8.00 | 22.26 | 8.00 | 22.26 |
December | 742.33 | 21.75 | 0.17 | 21.75 | 0.17 | 21.75 |
Annual Sum or Average | 6902.67 | 22.34 | 1714.17 | 22.61 | 703.50 | 22.68 |
Minimum of Months | 285.50 | 21.42 | 0.17 | 21.42 | 0.00 | 21.42 |
Maximum of Months | 744.00 | 23.45 | 449.33 | 23.69 | 167.50 | 23.72 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.50 | 22.00 | 17.83 | 22.03 | 17.83 | 22.05 |
February | 664.17 | 22.60 | 58.00 | 22.67 | 58.00 | 22.74 |
March | 610.67 | 23.59 | 11.00 | 23.59 | 0.00 | 23.59 |
April | 384.17 | 23.83 | 85.50 | 23.86 | 1.67 | 23.86 |
May | 118.33 | 24.00 | 399.67 | 24.00 | 3.83 | 24.00 |
June | 74.67 | 24.00 | 540.67 | 24.00 | 0.00 | 24.00 |
July | 0.00 | 0.00 | 744.00 | 24.00 | 0.00 | 24.00 |
August | 0.00 | 0.00 | 744.00 | 24.00 | 0.00 | 24.00 |
September | 0.00 | 0.00 | 535.50 | 24.00 | 0.00 | 24.00 |
October | 353.83 | 23.87 | 175.67 | 23.91 | 10.67 | 23.91 |
November | 572.50 | 23.58 | 31.00 | 23.60 | 1.67 | 23.60 |
December | 701.17 | 22.84 | 3.83 | 22.84 | 0.00 | 22.84 |
Annual Sum or Average | 4220.00 | 23.09 | 3346.67 | 23.49 | 93.67 | 23.49 |
Minimum of Months | 0.00 | 0.00 | 3.83 | 22.03 | 0.00 | 22.05 |
Maximum of Months | 740.50 | 24.00 | 744.00 | 24.00 | 58.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 295.67 | 21.00 | 295.67 | 21.00 |
February | 672.00 | 21.05 | 179.83 | 21.04 | 179.83 | 21.03 |
March | 744.00 | 21.24 | 22.50 | 21.24 | 22.50 | 21.23 |
April | 720.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
May | 744.00 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
June | 720.00 | 22.60 | 0.00 | 22.60 | 0.00 | 22.60 |
July | 733.17 | 22.78 | 0.00 | 22.78 | 0.00 | 22.78 |
August | 735.17 | 22.87 | 0.00 | 22.87 | 0.00 | 22.87 |
September | 720.00 | 22.40 | 0.00 | 22.40 | 0.00 | 22.40 |
October | 744.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
November | 720.00 | 21.25 | 5.33 | 21.24 | 5.33 | 21.24 |
December | 744.00 | 21.04 | 97.17 | 21.04 | 97.17 | 21.03 |
Annual Sum or Average | 8740.33 | 21.79 | 600.50 | 21.74 | 600.50 | 21.70 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.87 | 295.67 | 22.87 | 295.67 | 22.87 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 160.17 | 24.00 | 744.00 | 24.00 | 160.17 | 24.00 |
February | 170.17 | 24.00 | 672.00 | 24.00 | 170.17 | 24.00 |
March | 260.50 | 24.00 | 744.00 | 24.00 | 260.50 | 24.00 |
April | 340.17 | 24.00 | 720.00 | 24.00 | 340.17 | 24.00 |
May | 537.83 | 24.00 | 744.00 | 24.00 | 537.83 | 24.00 |
June | 573.00 | 24.00 | 720.00 | 24.00 | 573.00 | 24.00 |
July | 648.67 | 24.00 | 744.00 | 24.00 | 648.67 | 24.00 |
August | 656.83 | 24.00 | 744.00 | 24.00 | 656.83 | 24.00 |
September | 565.67 | 24.00 | 720.00 | 24.00 | 565.67 | 24.00 |
October | 390.00 | 24.00 | 744.00 | 24.00 | 390.00 | 24.00 |
November | 249.00 | 24.00 | 720.00 | 24.00 | 249.00 | 24.00 |
December | 187.00 | 24.00 | 744.00 | 24.00 | 187.00 | 24.00 |
Annual Sum or Average | 4739.00 | 24.00 | 8760.00 | 24.00 | 4739.00 | 24.00 |
Minimum of Months | 160.17 | 24.00 | 672.00 | 24.00 | 160.17 | 24.00 |
Maximum of Months | 656.83 | 24.00 | 744.00 | 24.00 | 656.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.17 | 21.37 | 55.67 | 21.35 | 55.67 | 21.34 |
February | 659.83 | 21.56 | 27.50 | 21.55 | 27.50 | 21.54 |
March | 695.67 | 21.86 | 27.17 | 21.91 | 12.00 | 21.92 |
April | 657.67 | 21.89 | 59.17 | 21.95 | 53.83 | 22.00 |
May | 668.67 | 22.02 | 190.17 | 22.20 | 168.33 | 22.30 |
June | 584.50 | 22.35 | 239.83 | 22.61 | 201.83 | 22.74 |
July | 549.67 | 22.54 | 363.67 | 22.80 | 284.00 | 22.91 |
August | 463.17 | 22.84 | 464.33 | 23.04 | 283.67 | 23.14 |
September | 517.17 | 22.36 | 340.67 | 22.65 | 215.50 | 22.75 |
October | 608.33 | 22.08 | 141.67 | 22.26 | 78.67 | 22.32 |
November | 658.17 | 21.81 | 46.00 | 21.89 | 27.33 | 21.92 |
December | 719.00 | 21.56 | 8.50 | 21.57 | 3.67 | 21.58 |
Annual Sum or Average | 7522.00 | 21.97 | 1964.33 | 22.19 | 1412.00 | 22.30 |
Minimum of Months | 463.17 | 21.37 | 8.50 | 21.35 | 3.67 | 21.34 |
Maximum of Months | 740.17 | 22.84 | 464.33 | 23.04 | 284.00 | 23.14 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.89 | 4.67 | 21.90 | 4.67 | 21.90 |
February | 668.33 | 22.12 | 11.50 | 22.13 | 11.50 | 22.15 |
March | 692.83 | 22.53 | 35.17 | 22.58 | 21.17 | 22.61 |
April | 616.67 | 22.60 | 100.33 | 22.73 | 70.67 | 22.79 |
May | 607.00 | 22.82 | 268.00 | 23.06 | 192.83 | 23.16 |
June | 497.00 | 23.15 | 332.00 | 23.42 | 213.50 | 23.52 |
July | 481.17 | 23.35 | 423.17 | 23.57 | 294.67 | 23.64 |
August | 396.33 | 23.59 | 450.50 | 23.72 | 292.33 | 23.78 |
September | 461.50 | 23.20 | 373.67 | 23.45 | 239.50 | 23.52 |
October | 574.83 | 22.76 | 126.50 | 22.92 | 89.83 | 23.00 |
November | 684.00 | 22.60 | 42.50 | 22.65 | 34.33 | 22.69 |
December | 721.50 | 22.20 | 13.83 | 22.23 | 4.17 | 22.24 |
Annual Sum or Average | 7145.17 | 22.65 | 2181.83 | 22.91 | 1469.17 | 23.02 |
Minimum of Months | 396.33 | 21.89 | 4.67 | 21.90 | 4.17 | 21.90 |
Maximum of Months | 744.00 | 23.59 | 450.50 | 23.72 | 294.67 | 23.78 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.89 | 420.67 | 20.81 | 420.67 | 20.77 |
February | 671.50 | 21.08 | 248.50 | 20.96 | 248.50 | 20.88 |
March | 735.00 | 21.49 | 18.50 | 21.47 | 18.50 | 21.44 |
April | 694.50 | 21.59 | 6.17 | 21.60 | 6.17 | 21.61 |
May | 688.50 | 21.62 | 3.00 | 21.62 | 3.00 | 21.62 |
June | 619.67 | 21.54 | 4.83 | 21.55 | 4.83 | 21.56 |
July | 624.17 | 21.50 | 13.33 | 21.53 | 10.50 | 21.55 |
August | 609.17 | 21.46 | 8.50 | 21.49 | 6.67 | 21.50 |
September | 645.67 | 21.56 | 6.83 | 21.58 | 6.33 | 21.59 |
October | 718.67 | 21.50 | 34.67 | 21.49 | 34.67 | 21.48 |
November | 716.17 | 21.40 | 47.83 | 21.37 | 47.83 | 21.35 |
December | 744.00 | 21.09 | 216.17 | 21.01 | 216.17 | 20.96 |
Annual Sum or Average | 8211.00 | 21.39 | 1029.00 | 21.32 | 1023.83 | 21.27 |
Minimum of Months | 609.17 | 20.89 | 3.00 | 20.81 | 3.00 | 20.77 |
Maximum of Months | 744.00 | 21.62 | 420.67 | 21.62 | 420.67 | 21.62 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.62 | 560.67 | 20.57 | 560.67 | 20.54 |
February | 672.00 | 20.93 | 311.50 | 20.78 | 311.50 | 20.70 |
March | 733.83 | 21.54 | 41.00 | 21.49 | 40.50 | 21.45 |
April | 676.17 | 21.87 | 32.50 | 21.94 | 19.33 | 21.95 |
May | 637.33 | 21.96 | 70.17 | 22.14 | 48.50 | 22.21 |
June | 592.83 | 21.86 | 61.67 | 22.06 | 50.67 | 22.19 |
July | 605.17 | 21.85 | 94.17 | 22.10 | 83.50 | 22.27 |
August | 610.00 | 21.77 | 66.17 | 21.96 | 61.83 | 22.11 |
September | 650.50 | 21.98 | 63.33 | 22.13 | 56.83 | 22.22 |
October | 710.00 | 21.62 | 64.50 | 21.65 | 57.17 | 21.66 |
November | 720.00 | 21.25 | 113.17 | 21.18 | 113.17 | 21.13 |
December | 744.00 | 20.80 | 426.17 | 20.71 | 426.17 | 20.67 |
Annual Sum or Average | 8095.83 | 21.48 | 1905.00 | 21.43 | 1829.83 | 21.38 |
Minimum of Months | 592.83 | 20.62 | 32.50 | 20.57 | 19.33 | 20.54 |
Maximum of Months | 744.00 | 21.98 | 560.67 | 22.14 | 560.67 | 22.27 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 370.50 | 20.83 | 370.50 | 20.80 |
February | 672.00 | 21.11 | 214.17 | 21.01 | 214.17 | 20.95 |
March | 744.00 | 21.46 | 14.67 | 21.45 | 14.67 | 21.44 |
April | 719.67 | 21.84 | 7.50 | 21.85 | 7.50 | 21.86 |
May | 742.67 | 22.07 | 32.67 | 22.11 | 32.67 | 22.15 |
June | 718.67 | 22.04 | 51.50 | 22.13 | 51.33 | 22.21 |
July | 742.17 | 22.05 | 83.67 | 22.18 | 83.50 | 22.29 |
August | 743.50 | 21.97 | 64.00 | 22.07 | 64.00 | 22.16 |
September | 719.00 | 22.03 | 47.00 | 22.11 | 47.00 | 22.18 |
October | 744.00 | 21.64 | 30.00 | 21.67 | 30.00 | 21.70 |
November | 720.00 | 21.32 | 22.00 | 21.31 | 22.00 | 21.29 |
December | 744.00 | 21.06 | 180.00 | 21.01 | 180.00 | 20.97 |
Annual Sum or Average | 8753.67 | 21.63 | 1117.67 | 21.60 | 1117.33 | 21.59 |
Minimum of Months | 672.00 | 20.91 | 7.50 | 20.83 | 7.50 | 20.80 |
Maximum of Months | 744.00 | 22.07 | 370.50 | 22.18 | 370.50 | 22.29 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.93 | 402.83 | 20.85 | 402.83 | 20.81 |
February | 672.00 | 21.14 | 232.33 | 21.02 | 232.33 | 20.95 |
March | 744.00 | 21.58 | 22.17 | 21.55 | 22.17 | 21.53 |
April | 708.17 | 21.70 | 4.17 | 21.70 | 4.17 | 21.71 |
May | 694.50 | 21.67 | 2.50 | 21.67 | 2.50 | 21.68 |
June | 589.33 | 21.47 | 1.50 | 21.48 | 1.00 | 21.48 |
July | 572.00 | 21.35 | 9.17 | 21.37 | 8.33 | 21.39 |
August | 573.17 | 21.36 | 4.83 | 21.37 | 4.67 | 21.39 |
September | 640.33 | 21.57 | 6.00 | 21.58 | 6.00 | 21.59 |
October | 730.17 | 21.57 | 33.83 | 21.56 | 33.83 | 21.55 |
November | 720.00 | 21.45 | 42.17 | 21.43 | 42.17 | 21.41 |
December | 744.00 | 21.13 | 201.33 | 21.06 | 201.33 | 21.01 |
Annual Sum or Average | 8131.67 | 21.41 | 962.83 | 21.34 | 961.33 | 21.29 |
Minimum of Months | 572.00 | 20.93 | 1.50 | 20.85 | 1.00 | 20.81 |
Maximum of Months | 744.00 | 21.70 | 402.83 | 21.70 | 402.83 | 21.71 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.64 | 548.00 | 20.58 | 548.00 | 20.56 |
February | 672.00 | 20.96 | 311.00 | 20.81 | 311.00 | 20.73 |
March | 744.00 | 21.57 | 40.83 | 21.53 | 40.83 | 21.50 |
April | 710.33 | 21.99 | 19.33 | 22.03 | 15.17 | 22.05 |
May | 647.67 | 22.06 | 70.83 | 22.24 | 47.33 | 22.32 |
June | 549.83 | 21.84 | 71.67 | 22.16 | 51.83 | 22.34 |
July | 559.17 | 21.85 | 100.17 | 22.22 | 85.67 | 22.46 |
August | 569.33 | 21.72 | 69.50 | 21.99 | 62.67 | 22.19 |
September | 652.50 | 22.04 | 67.83 | 22.22 | 57.67 | 22.34 |
October | 742.50 | 21.73 | 56.33 | 21.74 | 55.50 | 21.74 |
November | 720.00 | 21.22 | 104.33 | 21.17 | 104.33 | 21.14 |
December | 744.00 | 20.81 | 414.67 | 20.74 | 414.67 | 20.70 |
Annual Sum or Average | 8055.33 | 21.51 | 1874.50 | 21.48 | 1794.67 | 21.44 |
Minimum of Months | 549.83 | 20.64 | 19.33 | 20.58 | 15.17 | 20.56 |
Maximum of Months | 744.00 | 22.06 | 548.00 | 22.24 | 548.00 | 22.46 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 148.67 | 21.01 | 148.67 | 21.01 |
February | 672.00 | 21.15 | 137.83 | 21.13 | 137.83 | 21.11 |
March | 744.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
April | 720.00 | 22.15 | 20.00 | 22.16 | 20.00 | 22.17 |
May | 744.00 | 22.58 | 110.00 | 22.59 | 110.00 | 22.60 |
June | 688.50 | 23.12 | 161.33 | 23.14 | 161.33 | 23.16 |
July | 554.17 | 23.28 | 237.17 | 23.32 | 227.17 | 23.34 |
August | 569.00 | 23.36 | 251.17 | 23.40 | 242.83 | 23.41 |
September | 716.00 | 22.92 | 159.50 | 22.94 | 159.50 | 22.95 |
October | 744.00 | 22.04 | 45.50 | 22.07 | 45.50 | 22.09 |
November | 720.00 | 21.34 | 11.33 | 21.34 | 11.33 | 21.34 |
December | 744.00 | 21.06 | 73.00 | 21.05 | 73.00 | 21.05 |
Annual Sum or Average | 8359.67 | 22.09 | 1355.50 | 22.16 | 1337.17 | 22.21 |
Minimum of Months | 554.17 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 23.36 | 251.17 | 23.40 | 242.83 | 23.41 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.75 | 565.67 | 20.69 | 565.67 | 20.67 |
February | 670.17 | 20.96 | 343.67 | 20.83 | 343.67 | 20.77 |
March | 730.00 | 21.41 | 57.50 | 21.35 | 57.50 | 21.31 |
April | 675.50 | 21.51 | 36.33 | 21.52 | 36.33 | 21.52 |
May | 653.67 | 21.51 | 19.67 | 21.52 | 19.33 | 21.53 |
June | 589.17 | 21.44 | 17.33 | 21.48 | 15.00 | 21.51 |
July | 596.50 | 21.42 | 44.00 | 21.52 | 26.50 | 21.56 |
August | 584.67 | 21.39 | 32.50 | 21.48 | 18.00 | 21.51 |
September | 620.17 | 21.47 | 30.17 | 21.51 | 26.17 | 21.54 |
October | 704.67 | 21.40 | 67.33 | 21.36 | 67.33 | 21.32 |
November | 714.50 | 21.31 | 131.83 | 21.25 | 131.83 | 21.21 |
December | 744.00 | 20.96 | 409.00 | 20.86 | 409.00 | 20.82 |
Annual Sum or Average | 8027.00 | 21.28 | 1755.00 | 21.20 | 1716.33 | 21.14 |
Minimum of Months | 584.67 | 20.75 | 17.33 | 20.69 | 15.00 | 20.67 |
Maximum of Months | 744.00 | 21.51 | 565.67 | 21.52 | 565.67 | 21.56 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.53 | 633.50 | 20.49 | 633.50 | 20.48 |
February | 669.67 | 20.83 | 397.33 | 20.70 | 397.33 | 20.64 |
March | 727.83 | 21.44 | 99.50 | 21.36 | 98.17 | 21.28 |
April | 644.67 | 21.76 | 76.00 | 21.87 | 53.67 | 21.87 |
May | 598.33 | 21.84 | 103.50 | 22.10 | 68.17 | 22.17 |
June | 565.50 | 21.76 | 74.00 | 21.99 | 61.17 | 22.13 |
July | 582.50 | 21.77 | 127.17 | 22.07 | 104.33 | 22.24 |
August | 584.17 | 21.68 | 87.00 | 21.90 | 77.00 | 22.06 |
September | 619.50 | 21.86 | 91.17 | 22.02 | 83.67 | 22.12 |
October | 701.17 | 21.50 | 120.33 | 21.52 | 109.50 | 21.49 |
November | 719.50 | 21.14 | 251.83 | 21.05 | 251.83 | 21.00 |
December | 744.00 | 20.66 | 559.83 | 20.60 | 559.83 | 20.57 |
Annual Sum or Average | 7900.83 | 21.36 | 2621.17 | 21.32 | 2498.17 | 21.26 |
Minimum of Months | 565.50 | 20.53 | 74.00 | 20.49 | 53.67 | 20.48 |
Maximum of Months | 744.00 | 21.86 | 633.50 | 22.10 | 633.50 | 22.24 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.26 | 243.33 | 21.12 | 243.33 | 21.03 |
February | 663.17 | 21.34 | 139.67 | 21.22 | 139.67 | 21.14 |
March | 726.33 | 21.56 | 16.00 | 21.54 | 16.00 | 21.52 |
April | 687.17 | 21.59 | 4.33 | 21.59 | 4.33 | 21.59 |
May | 705.33 | 21.64 | 7.50 | 21.65 | 7.50 | 21.66 |
June | 650.00 | 21.61 | 15.67 | 21.64 | 15.67 | 21.67 |
July | 647.83 | 21.56 | 26.00 | 21.60 | 26.00 | 21.64 |
August | 627.33 | 21.52 | 21.00 | 21.55 | 21.00 | 21.59 |
September | 639.00 | 21.54 | 13.83 | 21.57 | 12.67 | 21.59 |
October | 679.83 | 21.47 | 33.50 | 21.49 | 27.50 | 21.48 |
November | 685.83 | 21.52 | 21.83 | 21.50 | 21.83 | 21.48 |
December | 734.83 | 21.39 | 90.00 | 21.31 | 90.00 | 21.25 |
Annual Sum or Average | 8190.67 | 21.50 | 632.67 | 21.46 | 625.50 | 21.43 |
Minimum of Months | 627.33 | 21.26 | 4.33 | 21.12 | 4.33 | 21.03 |
Maximum of Months | 744.00 | 21.64 | 243.33 | 21.65 | 243.33 | 21.67 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 732.33 | 21.81 | 4.50 | 21.82 | 4.50 | 21.83 |
February | 649.67 | 22.00 | 14.83 | 22.03 | 10.83 | 22.05 |
March | 627.50 | 22.24 | 67.50 | 22.37 | 13.50 | 22.39 |
April | 499.67 | 22.38 | 159.00 | 22.66 | 61.00 | 22.74 |
May | 416.67 | 22.75 | 345.67 | 23.08 | 176.83 | 23.17 |
June | 324.17 | 23.18 | 442.00 | 23.35 | 205.33 | 23.44 |
July | 366.00 | 23.37 | 532.67 | 23.41 | 287.33 | 23.50 |
August | 365.67 | 23.40 | 523.33 | 23.45 | 286.00 | 23.53 |
September | 438.50 | 22.83 | 384.50 | 23.13 | 222.00 | 23.23 |
October | 579.83 | 22.32 | 138.83 | 22.55 | 82.33 | 22.64 |
November | 660.50 | 22.16 | 48.50 | 22.24 | 29.83 | 22.29 |
December | 720.17 | 21.95 | 16.67 | 21.98 | 3.83 | 21.99 |
Annual Sum or Average | 6380.67 | 22.40 | 2678.00 | 22.72 | 1383.33 | 22.84 |
Minimum of Months | 324.17 | 21.81 | 4.50 | 21.82 | 3.83 | 21.83 |
Maximum of Months | 732.33 | 23.40 | 532.67 | 23.45 | 287.33 | 23.53 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 708.00 | 22.08 | 19.83 | 22.13 | 4.67 | 22.14 |
February | 584.50 | 22.21 | 39.17 | 22.30 | 11.50 | 22.32 |
March | 514.83 | 22.42 | 113.33 | 22.64 | 16.17 | 22.67 |
April | 358.50 | 22.58 | 248.00 | 22.99 | 60.83 | 23.06 |
May | 285.50 | 23.17 | 482.17 | 23.35 | 180.17 | 23.43 |
June | 240.33 | 23.67 | 572.00 | 23.53 | 203.50 | 23.61 |
July | 293.33 | 23.81 | 656.00 | 23.56 | 282.67 | 23.64 |
August | 293.33 | 23.85 | 652.17 | 23.59 | 283.17 | 23.66 |
September | 307.67 | 23.31 | 497.17 | 23.42 | 224.17 | 23.50 |
October | 439.00 | 22.48 | 232.67 | 22.85 | 82.83 | 22.94 |
November | 578.17 | 22.38 | 86.50 | 22.53 | 31.00 | 22.58 |
December | 674.50 | 22.22 | 32.50 | 22.28 | 4.00 | 22.29 |
Annual Sum or Average | 5277.67 | 22.64 | 3631.50 | 22.99 | 1384.67 | 23.10 |
Minimum of Months | 240.33 | 22.08 | 19.83 | 22.13 | 4.00 | 22.14 |
Maximum of Months | 708.00 | 23.85 | 656.00 | 23.59 | 283.17 | 23.66 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.33 | 23.99 | 739.67 | 23.99 | 466.33 | 23.99 |
February | 442.00 | 23.99 | 661.17 | 23.99 | 442.00 | 23.99 |
March | 523.83 | 23.99 | 744.00 | 23.99 | 523.83 | 23.99 |
April | 526.83 | 24.00 | 720.00 | 24.00 | 526.83 | 24.00 |
May | 573.50 | 23.99 | 744.00 | 23.99 | 573.50 | 23.99 |
June | 575.17 | 23.99 | 720.00 | 23.99 | 575.17 | 23.99 |
July | 611.17 | 23.99 | 744.00 | 23.99 | 611.17 | 23.99 |
August | 613.83 | 23.99 | 744.00 | 23.99 | 613.83 | 23.99 |
September | 565.83 | 23.99 | 720.00 | 23.99 | 565.83 | 23.99 |
October | 545.17 | 23.99 | 744.00 | 23.99 | 545.17 | 23.99 |
November | 501.00 | 23.99 | 720.00 | 23.99 | 501.00 | 23.99 |
December | 488.00 | 23.99 | 743.00 | 23.99 | 488.00 | 23.99 |
Annual Sum or Average | 6432.67 | 23.99 | 8743.83 | 23.99 | 6432.67 | 23.99 |
Minimum of Months | 442.00 | 23.99 | 661.17 | 23.99 | 442.00 | 23.99 |
Maximum of Months | 613.83 | 24.00 | 744.00 | 24.00 | 613.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.12 | 203.17 | 21.10 | 203.17 | 21.08 |
February | 672.00 | 21.63 | 160.00 | 21.51 | 160.00 | 21.43 |
March | 666.33 | 22.57 | 31.83 | 22.63 | 3.67 | 22.64 |
April | 430.00 | 23.09 | 139.33 | 23.29 | 33.33 | 23.31 |
May | 206.83 | 23.68 | 542.50 | 23.88 | 115.50 | 23.87 |
June | 116.33 | 23.90 | 617.00 | 23.98 | 77.17 | 23.99 |
July | 89.50 | 23.97 | 744.00 | 23.99 | 89.50 | 23.99 |
August | 76.50 | 24.00 | 744.00 | 24.00 | 76.50 | 24.00 |
September | 187.33 | 23.77 | 581.67 | 23.93 | 137.00 | 23.93 |
October | 541.67 | 22.92 | 175.17 | 23.16 | 52.33 | 23.20 |
November | 712.33 | 22.20 | 17.33 | 22.21 | 15.67 | 22.22 |
December | 744.00 | 21.35 | 65.00 | 21.32 | 65.00 | 21.30 |
Annual Sum or Average | 5186.83 | 22.26 | 4021.00 | 22.87 | 1028.83 | 22.85 |
Minimum of Months | 76.50 | 21.12 | 17.33 | 21.10 | 3.67 | 21.08 |
Maximum of Months | 744.00 | 24.00 | 744.00 | 24.00 | 203.17 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.68806 | 30.24699 | -0.0655 | 5.26847 |
February | 672.00000 | 22.17410 | 33.04154 | -0.1778 | 5.90527 |
March | 744.00000 | 21.61474 | 40.03917 | -0.2757 | 6.86163 |
April | 720.00000 | 21.24701 | 51.14128 | -0.3094 | 7.20665 |
May | 744.00000 | 21.50967 | 61.01990 | -1.3372 | 42.29438 |
June | 720.00000 | 22.36184 | 59.39529 | -1.0343 | 27.84714 |
July | 744.00000 | 22.89281 | 61.08872 | -0.8268 | 19.64224 |
August | 744.00000 | 23.44849 | 59.26704 | -0.6331 | 13.64016 |
September | 720.00000 | 23.83741 | 56.71175 | -0.5007 | 10.37512 |
October | 744.00000 | 23.90040 | 47.02439 | 0.37418 | 8.03476 |
November | 720.00000 | 23.91690 | 35.86911 | 0.30078 | 7.07045 |
December | 744.00000 | 23.68410 | 31.54336 | 0.20160 | 6.04184 |
Annual Sum or Average | 8760.00000 | 22.77714 | 47.27617 | -0.3582 | 13.41265 |
Minimum of Months | 672.00000 | 21.24701 | 30.24699 | -1.3372 | 5.26847 |
Maximum of Months | 744.00000 | 23.91690 | 61.08872 | 0.37418 | 42.29438 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.41219 | 32.23011 | -0.4040 | 9.57570 |
February | 672.00000 | 21.69248 | 34.03295 | -0.2926 | 8.51983 |
March | 744.00000 | 22.43237 | 38.42790 | -0.0261 | 6.88562 |
April | 720.00000 | 22.77833 | 47.21111 | 0.12965 | 6.86100 |
May | 744.00000 | 23.29361 | 55.62235 | -0.6256 | 14.62102 |
June | 720.00000 | 23.77345 | 55.22983 | -0.4204 | 9.43196 |
July | 744.00000 | 23.84751 | 58.39035 | -0.3525 | 7.98352 |
August | 744.00000 | 23.95749 | 57.92120 | -0.2945 | 6.95521 |
September | 720.00000 | 23.57099 | 58.04450 | -0.4761 | 11.03431 |
October | 744.00000 | 22.86119 | 50.21737 | 0.17704 | 7.55595 |
November | 720.00000 | 22.24506 | 39.51540 | -0.0711 | 6.89305 |
December | 744.00000 | 21.68112 | 34.99514 | -0.2825 | 8.34691 |
Annual Sum or Average | 8760.00000 | 22.80130 | 46.89010 | -0.2449 | 8.72550 |
Minimum of Months | 672.00000 | 21.41219 | 32.23011 | -0.6256 | 6.86100 |
Maximum of Months | 744.00000 | 23.95749 | 58.39035 | 0.17704 | 14.62102 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.42444 | 32.32841 | -0.3380 | 7.75606 |
February | 672.00000 | 21.70424 | 34.01572 | -0.2500 | 7.00472 |
March | 744.00000 | 22.31543 | 38.85619 | -0.0502 | 5.77332 |
April | 720.00000 | 22.59810 | 47.90802 | 0.08386 | 5.80322 |
May | 744.00000 | 22.91023 | 56.92437 | -0.7676 | 18.15317 |
June | 720.00000 | 23.31700 | 56.82578 | -0.6103 | 13.47143 |
July | 744.00000 | 23.41544 | 59.91189 | -0.5494 | 11.85421 |
August | 744.00000 | 23.53336 | 59.54335 | -0.5061 | 10.75738 |
September | 720.00000 | 23.22950 | 59.27969 | -0.6292 | 13.93870 |
October | 744.00000 | 22.69607 | 50.81003 | 0.12871 | 5.97542 |
November | 720.00000 | 22.26280 | 39.66138 | -0.0607 | 5.67539 |
December | 744.00000 | 21.75207 | 34.94535 | -0.2286 | 6.66291 |
Annual Sum or Average | 8760.00000 | 22.60109 | 47.65916 | -0.3154 | 9.41836 |
Minimum of Months | 672.00000 | 21.42444 | 32.32841 | -0.7676 | 5.67539 |
Maximum of Months | 744.00000 | 23.53336 | 59.91189 | 0.12871 | 18.15317 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.00015 | 24.41224 | 0.79042 | 19.01820 |
February | 672.00000 | 23.99996 | 26.23758 | 0.82656 | 20.33844 |
March | 744.00000 | 23.99969 | 31.53572 | 0.90388 | 23.13526 |
April | 720.00000 | 23.99944 | 40.36894 | 0.98509 | 26.27013 |
May | 744.00000 | 23.99969 | 49.41409 | 0.44308 | 10.71000 |
June | 720.00000 | 23.99982 | 50.45200 | 0.48485 | 11.51957 |
July | 744.00000 | 23.99987 | 53.62910 | 0.51576 | 12.02472 |
August | 744.00000 | 23.99996 | 53.63179 | 0.52304 | 12.22776 |
September | 720.00000 | 23.99990 | 52.53676 | 0.47422 | 11.22169 |
October | 744.00000 | 23.99983 | 43.19060 | 0.99984 | 26.79983 |
November | 720.00000 | 23.99982 | 32.18744 | 0.89763 | 22.85745 |
December | 744.00000 | 24.00000 | 27.16764 | 0.83198 | 20.48276 |
Annual Sum or Average | 8760.00000 | 23.99984 | 40.47513 | 0.72232 | 18.03259 |
Minimum of Months | 672.00000 | 23.99944 | 24.41224 | 0.44308 | 10.71000 |
Maximum of Months | 744.00000 | 24.00015 | 53.63179 | 0.99984 | 26.79983 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.38206 | 34.70370 | -0.3082 | 7.65045 |
February | 672.00000 | 21.58998 | 36.54226 | -0.2166 | 6.91761 |
March | 744.00000 | 21.93510 | 41.98065 | -0.0448 | 5.96033 |
April | 720.00000 | 21.97484 | 51.86027 | 0.04031 | 5.82697 |
May | 744.00000 | 22.10634 | 61.70835 | -0.8766 | 22.15749 |
June | 720.00000 | 22.41031 | 61.95442 | -0.7309 | 17.31568 |
July | 744.00000 | 22.55130 | 65.09890 | -0.6447 | 14.70720 |
August | 744.00000 | 22.78616 | 64.36401 | -0.5488 | 12.17114 |
September | 720.00000 | 22.49787 | 63.99641 | -0.6925 | 16.43666 |
October | 744.00000 | 22.23901 | 54.38511 | 0.13141 | 6.42142 |
November | 720.00000 | 21.92477 | 42.74124 | -0.0478 | 6.05599 |
December | 744.00000 | 21.60562 | 37.58975 | -0.1999 | 6.69506 |
Annual Sum or Average | 8760.00000 | 22.08637 | 51.49178 | -0.3458 | 10.71619 |
Minimum of Months | 672.00000 | 21.38206 | 34.70370 | -0.8766 | 5.82697 |
Maximum of Months | 744.00000 | 22.78616 | 65.09890 | 0.13141 | 22.15749 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.89002 | 34.36383 | -0.2002 | 6.37698 |
February | 672.00000 | 22.12681 | 36.06638 | -0.1196 | 6.12866 |
March | 744.00000 | 22.59780 | 41.14657 | 0.05004 | 5.79314 |
April | 720.00000 | 22.74339 | 50.34662 | 0.15319 | 6.18089 |
May | 744.00000 | 22.95176 | 59.56325 | -0.7076 | 16.47608 |
June | 720.00000 | 23.25051 | 59.74469 | -0.5800 | 12.96440 |
July | 744.00000 | 23.33628 | 62.79309 | -0.5204 | 11.39663 |
August | 744.00000 | 23.44332 | 62.38731 | -0.4777 | 10.35986 |
September | 720.00000 | 23.26797 | 61.85783 | -0.5635 | 12.39088 |
October | 744.00000 | 22.93704 | 52.94507 | 0.22424 | 6.65118 |
November | 720.00000 | 22.64812 | 41.71405 | 0.06551 | 5.72674 |
December | 744.00000 | 22.24154 | 36.92992 | -0.0821 | 5.76803 |
Annual Sum or Average | 8760.00000 | 22.78954 | 50.06508 | -0.2307 | 8.86841 |
Minimum of Months | 672.00000 | 21.89002 | 34.36383 | -0.7076 | 5.72674 |
Maximum of Months | 744.00000 | 23.44332 | 62.79309 | 0.22424 | 16.47608 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.88871 | 43.50658 | -0.5413 | 11.76153 |
February | 672.00000 | 21.08018 | 44.44579 | -0.4495 | 10.22961 |
March | 744.00000 | 21.51009 | 45.70969 | -0.2537 | 7.26508 |
April | 720.00000 | 21.65562 | 51.73295 | -0.1389 | 6.38241 |
May | 744.00000 | 21.74315 | 54.51278 | -1.1643 | 34.88576 |
June | 720.00000 | 21.78964 | 52.40553 | -1.1029 | 32.16030 |
July | 744.00000 | 21.79489 | 53.94304 | -1.0752 | 30.92590 |
August | 744.00000 | 21.80295 | 53.02261 | -1.0656 | 30.53213 |
September | 720.00000 | 21.74637 | 55.58041 | -1.1410 | 33.85971 |
October | 744.00000 | 21.56278 | 55.77437 | -0.1612 | 6.45882 |
November | 720.00000 | 21.40868 | 48.85163 | -0.2984 | 7.73613 |
December | 744.00000 | 21.09145 | 46.56947 | -0.4460 | 9.78553 |
Annual Sum or Average | 8760.00000 | 21.50813 | 50.53642 | -0.6547 | 18.54971 |
Minimum of Months | 672.00000 | 20.88871 | 43.50658 | -1.1643 | 6.38241 |
Maximum of Months | 744.00000 | 21.80295 | 55.77437 | -0.1389 | 34.88576 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.62251 | 44.13328 | -0.6277 | 13.90145 |
February | 672.00000 | 20.93118 | 44.82304 | -0.5111 | 11.63177 |
March | 744.00000 | 21.56973 | 46.21124 | -0.2660 | 7.57714 |
April | 720.00000 | 22.00236 | 51.85653 | -0.0793 | 6.55098 |
May | 744.00000 | 22.22954 | 55.05824 | -1.0244 | 29.27264 |
June | 720.00000 | 22.15064 | 53.01586 | -0.9940 | 27.99264 |
July | 744.00000 | 22.13840 | 54.98674 | -0.9699 | 26.95142 |
August | 744.00000 | 22.05674 | 54.22882 | -0.9967 | 27.91718 |
September | 720.00000 | 22.13367 | 57.14667 | -1.0394 | 29.68958 |
October | 744.00000 | 21.73218 | 57.06480 | -0.1479 | 6.68532 |
November | 720.00000 | 21.25074 | 49.87821 | -0.3638 | 8.61934 |
December | 744.00000 | 20.79698 | 47.49361 | -0.5388 | 11.66661 |
Annual Sum or Average | 8760.00000 | 21.63760 | 51.36011 | -0.6310 | 17.40929 |
Minimum of Months | 672.00000 | 20.62251 | 44.13328 | -1.0394 | 6.55098 |
Maximum of Months | 744.00000 | 22.22954 | 57.14667 | -0.0793 | 29.68958 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.91013 | 40.63765 | -0.5247 | 11.15456 |
February | 672.00000 | 21.11196 | 41.08360 | -0.4515 | 9.80661 |
March | 744.00000 | 21.46182 | 43.36887 | -0.3126 | 7.53766 |
April | 720.00000 | 21.83652 | 49.70760 | -0.1625 | 6.34695 |
May | 744.00000 | 22.06936 | 55.02318 | -1.1467 | 33.80534 |
June | 720.00000 | 22.04257 | 54.70217 | -1.1251 | 33.02722 |
July | 744.00000 | 22.05423 | 57.08644 | -1.0988 | 31.94816 |
August | 744.00000 | 21.97069 | 56.66525 | -1.1328 | 33.34357 |
September | 720.00000 | 22.03261 | 57.26746 | -1.1457 | 33.80139 |
October | 744.00000 | 21.63650 | 54.15180 | -0.1973 | 6.35500 |
November | 720.00000 | 21.32100 | 45.98901 | -0.3487 | 7.97838 |
December | 744.00000 | 21.06290 | 43.77061 | -0.4532 | 9.62205 |
Annual Sum or Average | 8760.00000 | 21.62808 | 50.00588 | -0.6766 | 18.78345 |
Minimum of Months | 672.00000 | 20.91013 | 40.63765 | -1.1467 | 6.34695 |
Maximum of Months | 744.00000 | 22.06936 | 57.26746 | -0.1625 | 33.80534 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.92508 | 43.41676 | -0.5338 | 11.58125 |
February | 672.00000 | 21.13728 | 44.24781 | -0.4339 | 9.97529 |
March | 744.00000 | 21.57862 | 45.36171 | -0.2438 | 7.21311 |
April | 720.00000 | 21.72264 | 51.04979 | -0.1274 | 6.35736 |
May | 744.00000 | 21.77924 | 53.47811 | -1.1508 | 34.34349 |
June | 720.00000 | 21.80908 | 51.81580 | -1.0917 | 31.74714 |
July | 744.00000 | 21.80600 | 53.37426 | -1.0648 | 30.56473 |
August | 744.00000 | 21.81087 | 52.77172 | -1.0609 | 30.40196 |
September | 720.00000 | 21.76180 | 55.01148 | -1.1361 | 33.68967 |
October | 744.00000 | 21.60385 | 54.95229 | -0.1564 | 6.45128 |
November | 720.00000 | 21.45481 | 48.60994 | -0.2903 | 7.60207 |
December | 744.00000 | 21.12999 | 46.42407 | -0.4368 | 9.57122 |
Annual Sum or Average | 8760.00000 | 21.54503 | 50.07314 | -0.6454 | 18.34283 |
Minimum of Months | 672.00000 | 20.92508 | 43.41676 | -1.1508 | 6.35736 |
Maximum of Months | 744.00000 | 21.81087 | 55.01148 | -0.1274 | 34.34349 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.64166 | 44.08438 | -0.6236 | 13.77545 |
February | 672.00000 | 20.96292 | 44.70243 | -0.5001 | 11.33612 |
March | 744.00000 | 21.56914 | 46.06242 | -0.2700 | 7.41529 |
April | 720.00000 | 22.02421 | 51.25696 | -0.0773 | 6.34550 |
May | 744.00000 | 22.27735 | 54.07568 | -1.0078 | 28.74402 |
June | 720.00000 | 22.24329 | 52.39651 | -0.9617 | 27.42760 |
July | 744.00000 | 22.23054 | 54.36800 | -0.9357 | 26.51320 |
August | 744.00000 | 22.10954 | 53.91371 | -0.9793 | 27.72951 |
September | 720.00000 | 22.18592 | 56.33305 | -1.0250 | 29.38432 |
October | 744.00000 | 21.73842 | 56.25607 | -0.1508 | 6.52497 |
November | 720.00000 | 21.22016 | 49.86305 | -0.3710 | 8.51259 |
December | 744.00000 | 20.81057 | 47.41732 | -0.5343 | 11.48815 |
Annual Sum or Average | 8760.00000 | 21.67086 | 50.92784 | -0.6208 | 17.13814 |
Minimum of Months | 672.00000 | 20.64166 | 44.08438 | -1.0250 | 6.34550 |
Maximum of Months | 744.00000 | 22.27735 | 56.33305 | -0.0773 | 29.38432 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.75434 | 44.78103 | -0.6051 | 13.39473 |
February | 672.00000 | 20.96732 | 45.73189 | -0.4998 | 11.48523 |
March | 744.00000 | 21.44155 | 46.84700 | -0.2805 | 7.78335 |
April | 720.00000 | 21.62172 | 53.13423 | -0.1471 | 6.63749 |
May | 744.00000 | 21.73116 | 55.65245 | -1.1599 | 34.90032 |
June | 720.00000 | 21.78615 | 53.07231 | -1.0934 | 31.95698 |
July | 744.00000 | 21.79199 | 54.84712 | -1.0625 | 30.59041 |
August | 744.00000 | 21.80202 | 53.71315 | -1.0533 | 30.21126 |
September | 720.00000 | 21.72762 | 57.15322 | -1.1439 | 34.17405 |
October | 744.00000 | 21.49829 | 57.77931 | -0.1821 | 6.80304 |
November | 720.00000 | 21.32574 | 50.34117 | -0.3340 | 8.42145 |
December | 744.00000 | 20.95544 | 48.13496 | -0.5023 | 11.06353 |
Annual Sum or Average | 8760.00000 | 21.45244 | 51.79706 | -0.6733 | 18.99844 |
Minimum of Months | 672.00000 | 20.75434 | 44.78103 | -1.1599 | 6.63749 |
Maximum of Months | 744.00000 | 21.80202 | 57.77931 | -0.1471 | 34.90032 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.52832 | 45.38185 | -0.6851 | 15.58039 |
February | 672.00000 | 20.84544 | 46.08911 | -0.5576 | 12.89574 |
March | 744.00000 | 21.49408 | 47.31836 | -0.2949 | 8.20272 |
April | 720.00000 | 21.99303 | 52.99439 | -0.0810 | 6.92765 |
May | 744.00000 | 22.22427 | 55.78804 | -1.0151 | 29.33033 |
June | 720.00000 | 22.12577 | 53.49792 | -0.9887 | 27.96650 |
July | 744.00000 | 22.10923 | 55.71353 | -0.9631 | 26.80689 |
August | 744.00000 | 22.03293 | 54.84726 | -0.9899 | 27.75131 |
September | 720.00000 | 22.08671 | 58.50746 | -1.0488 | 30.31699 |
October | 744.00000 | 21.65173 | 59.06437 | -0.1725 | 7.14780 |
November | 720.00000 | 21.14141 | 51.44257 | -0.4072 | 9.53439 |
December | 744.00000 | 20.66271 | 49.09112 | -0.5970 | 13.20007 |
Annual Sum or Average | 8760.00000 | 21.57776 | 52.51262 | -0.6510 | 18.00562 |
Minimum of Months | 672.00000 | 20.52832 | 45.38185 | -1.0488 | 6.92765 |
Maximum of Months | 744.00000 | 22.22427 | 59.06437 | -0.0810 | 30.31699 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.26044 | 43.57825 | -0.4187 | 9.97398 |
February | 672.00000 | 21.36268 | 44.22119 | -0.3572 | 8.91905 |
March | 744.00000 | 21.59783 | 45.06822 | -0.2316 | 7.23677 |
April | 720.00000 | 21.67068 | 51.71475 | -0.1554 | 6.58342 |
May | 744.00000 | 21.73024 | 55.58117 | -1.2047 | 36.83070 |
June | 720.00000 | 21.78051 | 54.01289 | -1.1521 | 34.40227 |
July | 744.00000 | 21.78685 | 55.60741 | -1.1205 | 32.93965 |
August | 744.00000 | 21.80221 | 54.18699 | -1.1012 | 32.15666 |
September | 720.00000 | 21.74508 | 55.82343 | -1.1613 | 34.91953 |
October | 744.00000 | 21.63337 | 54.32466 | -0.1414 | 6.50632 |
November | 720.00000 | 21.60613 | 47.53634 | -0.2247 | 7.21409 |
December | 744.00000 | 21.41117 | 46.06045 | -0.3326 | 8.43910 |
Annual Sum or Average | 8760.00000 | 21.61675 | 50.67791 | -0.6353 | 18.90381 |
Minimum of Months | 672.00000 | 21.26044 | 43.57825 | -1.2047 | 6.50632 |
Maximum of Months | 744.00000 | 21.80221 | 55.82343 | -0.1414 | 36.83070 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.83910 | 34.04393 | -0.1805 | 6.51197 |
February | 672.00000 | 22.04974 | 35.75382 | -0.0918 | 6.29351 |
March | 744.00000 | 22.42674 | 41.08387 | 0.07922 | 6.12690 |
April | 720.00000 | 22.66988 | 50.14254 | 0.22388 | 6.89235 |
May | 744.00000 | 22.88591 | 59.31593 | -0.5832 | 13.13821 |
June | 720.00000 | 23.06582 | 59.83686 | -0.4860 | 10.89236 |
July | 744.00000 | 23.10123 | 63.07394 | -0.4430 | 9.93898 |
August | 744.00000 | 23.11086 | 63.05814 | -0.4398 | 9.92595 |
September | 720.00000 | 22.89602 | 62.59964 | -0.5577 | 12.55024 |
October | 744.00000 | 22.53332 | 53.56962 | 0.19780 | 6.66248 |
November | 720.00000 | 22.25238 | 42.04054 | 0.02347 | 6.02357 |
December | 744.00000 | 21.99050 | 36.92104 | -0.1043 | 6.15038 |
Annual Sum or Average | 8760.00000 | 22.57105 | 50.19933 | -0.1977 | 8.43582 |
Minimum of Months | 672.00000 | 21.83910 | 34.04393 | -0.5832 | 6.02357 |
Maximum of Months | 744.00000 | 23.11086 | 63.07394 | 0.22388 | 13.13821 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.15058 | 33.58984 | -0.0736 | 6.07995 |
February | 672.00000 | 22.37399 | 35.23482 | 0.01487 | 6.19621 |
March | 744.00000 | 22.73985 | 40.48534 | 0.17667 | 6.56734 |
April | 720.00000 | 22.94142 | 49.46054 | 0.30825 | 7.74672 |
May | 744.00000 | 23.12650 | 58.54565 | -0.4765 | 10.63197 |
June | 720.00000 | 23.28878 | 59.08481 | -0.3852 | 8.89220 |
July | 744.00000 | 23.31549 | 62.28720 | -0.3449 | 8.15404 |
August | 744.00000 | 23.32002 | 62.28196 | -0.3436 | 8.17570 |
September | 720.00000 | 23.13032 | 61.80209 | -0.4540 | 10.21503 |
October | 744.00000 | 22.81238 | 52.81625 | 0.28442 | 7.45867 |
November | 720.00000 | 22.58750 | 41.39189 | 0.12832 | 6.32772 |
December | 744.00000 | 22.33901 | 36.35502 | 0.00893 | 5.98092 |
Annual Sum or Average | 8760.00000 | 22.84611 | 49.52316 | -0.0972 | 7.70808 |
Minimum of Months | 672.00000 | 22.15058 | 33.58984 | -0.4765 | 5.98092 |
Maximum of Months | 744.00000 | 23.32002 | 62.28720 | 0.30825 | 10.63197 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99119 | 32.53528 | 0.95832 | 25.87034 |
February | 672.00000 | 23.99113 | 34.05021 | 1.00616 | 27.92837 |
March | 744.00000 | 23.99185 | 38.78011 | 1.10174 | 32.03955 |
April | 720.00000 | 23.99947 | 47.30901 | 1.20050 | 36.61297 |
May | 744.00000 | 23.99427 | 55.96332 | 0.74402 | 20.11358 |
June | 720.00000 | 23.99397 | 56.87635 | 0.79629 | 21.70372 |
July | 744.00000 | 23.99204 | 59.93873 | 0.83148 | 22.68081 |
August | 744.00000 | 23.99208 | 59.90300 | 0.83191 | 22.62926 |
September | 720.00000 | 23.99275 | 58.94635 | 0.76322 | 20.38775 |
October | 744.00000 | 23.99152 | 50.04168 | 1.19520 | 36.18658 |
November | 720.00000 | 23.99116 | 39.55200 | 1.07919 | 30.98907 |
December | 744.00000 | 23.99106 | 34.94812 | 1.00432 | 27.78296 |
Annual Sum or Average | 8760.00000 | 23.99270 | 47.47763 | 0.95897 | 27.06629 |
Minimum of Months | 672.00000 | 23.99106 | 32.53528 | 0.74402 | 20.11358 |
Maximum of Months | 744.00000 | 23.99947 | 59.93873 | 1.20050 | 36.61297 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00407 | 29.86954 | -0.5027 | 10.44228 |
February | 672.00000 | 21.04814 | 32.04316 | -0.4590 | 9.66756 |
March | 744.00000 | 21.24235 | 37.86152 | -0.3425 | 7.87405 |
April | 720.00000 | 21.55551 | 47.35308 | -0.2012 | 6.32254 |
May | 744.00000 | 22.01056 | 56.61883 | -1.1172 | 31.56695 |
June | 720.00000 | 22.59834 | 56.07490 | -0.9079 | 22.70545 |
July | 744.00000 | 22.79077 | 59.20604 | -0.8183 | 19.28694 |
August | 744.00000 | 22.87462 | 59.01461 | -0.7892 | 18.20709 |
September | 720.00000 | 22.40216 | 59.02209 | -0.9602 | 24.69601 |
October | 744.00000 | 21.67606 | 50.51577 | -0.1503 | 5.86104 |
November | 720.00000 | 21.24655 | 38.61548 | -0.3373 | 7.76316 |
December | 744.00000 | 21.04152 | 33.09304 | -0.4437 | 9.37409 |
Annual Sum or Average | 8760.00000 | 21.79524 | 46.68695 | -0.5867 | 14.51039 |
Minimum of Months | 672.00000 | 21.00407 | 29.86954 | -1.1172 | 5.86104 |
Maximum of Months | 744.00000 | 22.87462 | 59.20604 | -0.1503 | 31.56695 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01009 | 34.15684 | -0.4875 | 10.08732 |
February | 672.00000 | 21.15206 | 36.17612 | -0.4313 | 9.13195 |
March | 744.00000 | 21.61042 | 41.44751 | -0.2685 | 6.92554 |
April | 720.00000 | 22.15220 | 50.12063 | -0.0783 | 5.61258 |
May | 744.00000 | 22.58359 | 59.19398 | -0.9672 | 25.00460 |
June | 720.00000 | 23.13696 | 58.79827 | -0.7710 | 17.78367 |
July | 744.00000 | 23.36172 | 61.65682 | -0.6711 | 14.62135 |
August | 744.00000 | 23.41790 | 61.55239 | -0.6520 | 13.99711 |
September | 720.00000 | 22.92033 | 61.66593 | -0.8298 | 19.75324 |
October | 744.00000 | 22.04036 | 53.85545 | -0.0841 | 5.62423 |
November | 720.00000 | 21.34181 | 42.72684 | -0.3308 | 7.58780 |
December | 744.00000 | 21.05894 | 37.33111 | -0.4449 | 9.35603 |
Annual Sum or Average | 8760.00000 | 22.15444 | 49.96520 | -0.5019 | 12.14223 |
Minimum of Months | 672.00000 | 21.01009 | 34.15684 | -0.9672 | 5.61258 |
Maximum of Months | 744.00000 | 23.41790 | 61.66593 | -0.0783 | 25.00460 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.12289 | 33.79091 | -0.4666 | 9.86464 |
February | 672.00000 | 21.63191 | 35.19226 | -0.3197 | 8.17408 |
March | 744.00000 | 22.70046 | 39.14922 | -0.0086 | 6.04722 |
April | 720.00000 | 23.41738 | 46.66999 | 0.22797 | 6.89452 |
May | 744.00000 | 23.88129 | 54.52746 | -0.5098 | 10.73683 |
June | 720.00000 | 23.98154 | 54.47158 | -0.4459 | 9.28775 |
July | 744.00000 | 23.99357 | 57.50480 | -0.4102 | 8.52304 |
August | 744.00000 | 23.99957 | 57.33563 | -0.4050 | 8.42692 |
September | 720.00000 | 23.90954 | 57.52406 | -0.4732 | 9.85947 |
October | 744.00000 | 23.18599 | 50.59053 | 0.19104 | 6.69948 |
November | 720.00000 | 22.21150 | 40.74233 | -0.1244 | 6.30042 |
December | 744.00000 | 21.35190 | 36.62958 | -0.3738 | 8.55768 |
Annual Sum or Average | 8760.00000 | 22.95506 | 47.07670 | -0.2600 | 8.28403 |
Minimum of Months | 672.00000 | 21.12289 | 33.79091 | -0.5098 | 6.04722 |
Maximum of Months | 744.00000 | 23.99957 | 57.52406 | 0.22797 | 10.73683 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.01002 | 43.56254 | -0.2022 | 6.73867 |
February | 672.00000 | 22.62023 | 44.31213 | -0.0506 | 6.55170 |
March | 744.00000 | 23.65922 | 43.46914 | 0.20055 | 6.14129 |
April | 720.00000 | 23.90880 | 46.55630 | 0.29646 | 7.05132 |
May | 744.00000 | 23.99940 | 52.57348 | -0.5427 | 11.27574 |
June | 720.00000 | 23.99990 | 52.70731 | -0.4990 | 10.29512 |
July | 744.00000 | 23.99988 | 56.22677 | -0.4624 | 9.47162 |
August | 744.00000 | 23.99987 | 56.17744 | -0.4567 | 9.36003 |
September | 720.00000 | 23.99990 | 55.13878 | -0.4954 | 10.18296 |
October | 744.00000 | 23.93610 | 49.55239 | 0.33306 | 7.42094 |
November | 720.00000 | 23.66476 | 43.67597 | 0.20643 | 6.22844 |
December | 744.00000 | 22.90274 | 45.75534 | 0.02863 | 5.53300 |
Annual Sum or Average | 8760.00000 | 23.56244 | 49.17786 | -0.1379 | 8.02839 |
Minimum of Months | 672.00000 | 22.01002 | 43.46914 | -0.5427 | 5.53300 |
Maximum of Months | 744.00000 | 23.99990 | 56.22677 | 0.33306 | 11.27574 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.353086E+10 | 42260.36 | 19-JAN-22:53 | 215.28 | 0.160068E+11 | 0.00 | 0.195377E+11 | 1.35 | 4.72 | 01-JAN-07:10 | 0.00 | 0.00 |
February | 0.115398E+11 | 80563.19 | 26-FEB-16:11 | 334.47 | 0.504681E+11 | 0.00 | 0.620079E+11 | 2.29 | 4.72 | 01-FEB-00:50 | 0.00 | 0.00 |
March | 0.342056E+11 | 102565.24 | 30-MAR-18:03 | 631.20 | 0.147622E+12 | 0.00 | 0.181827E+12 | 3.86 | 4.72 | 01-MAR-02:00 | 0.00 | 0.00 |
April | 0.668066E+11 | 110866.98 | 17-APR-15:13 | 695.10 | 0.281040E+12 | 0.00 | 0.347846E+12 | 4.27 | 4.72 | 01-APR-01:40 | 0.00 | 0.00 |
May | 0.122701E+12 | 133936.35 | 30-MAY-18:03 | 743.79 | 0.508526E+12 | 0.00 | 0.631227E+12 | 4.27 | 4.72 | 09-MAY-22:20 | 0.00 | 0.00 |
June | 0.194158E+12 | 161148.31 | 28-JUN-18:03 | 720.00 | 0.764315E+12 | 0.00 | 0.958473E+12 | 4.03 | 4.72 | 08-JUN-02:00 | 0.00 | 0.00 |
July | 0.245973E+12 | 175732.66 | 06-JUL-18:03 | 744.00 | 0.954232E+12 | 0.00 | 0.120021E+13 | 3.95 | 4.58 | 28-JUL-21:53 | 0.00 | 0.00 |
August | 0.261519E+12 | 174238.21 | 10-AUG-18:03 | 744.00 | 0.101212E+13 | 0.00 | 0.127364E+13 | 3.92 | 4.44 | 25-AUG-06:00 | 0.00 | 0.00 |
September | 0.162113E+12 | 155807.98 | 07-SEP-18:03 | 720.00 | 0.662449E+12 | 0.00 | 0.824563E+12 | 4.19 | 4.72 | 14-SEP-04:40 | 0.00 | 0.00 |
October | 0.673620E+11 | 141476.19 | 18-OCT-21:52 | 693.99 | 0.287090E+12 | 0.00 | 0.354453E+12 | 4.18 | 4.72 | 03-OCT-03:00 | 0.00 | 0.00 |
November | 0.259679E+11 | 93157.27 | 05-NOV-15:13 | 559.88 | 0.114259E+12 | 0.00 | 0.140227E+12 | 3.56 | 4.72 | 01-NOV-05:40 | 0.00 | 0.00 |
December | 0.730948E+10 | 46980.51 | 13-DEC-11:35 | 339.56 | 0.328967E+11 | 0.00 | 0.402062E+11 | 2.13 | 4.72 | 01-DEC-12:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.120319E+13 | 7141.26 | 0.483103E+13 | 0.00 | 0.603422E+13 | 3.50 | 0.00 | 0.00 | ||||
Minimum of Months | 0.353086E+10 | 42260.36 | 215.28 | 0.160068E+11 | 0.00 | 0.195377E+11 | 1.35 | 4.44 | 0.00 | 0.00 | ||
Maximum of Months | 0.261519E+12 | 175732.66 | 744.00 | 0.101212E+13 | 0.00 | 0.127364E+13 | 4.27 | 4.72 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.661161E+09 | 0.00 | 29.17 | 0.498469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13220.25 | 19-JAN-22:53 | 12205.06 | 31-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.183359E+10 | 0.00 | 83.00 | 0.181283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16188.18 | 28-FEB-16:11 | 16188.18 | 28-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.676203E+10 | 0.00 | 233.83 | 0.617111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22693.82 | 28-MAR-15:11 | 18082.64 | 30-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.136130E+11 | 0.00 | 357.67 | 0.108952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28889.99 | 30-APR-15:13 | 18443.02 | 17-APR-15:12 | 0.00 | 0.00 | 0.00 |
May | 0.289445E+11 | 0.00 | 515.50 | 0.191736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39092.00 | 30-MAY-21:50 | 19094.55 | 19-MAY-15:12 | 0.00 | 0.00 | 0.00 |
June | 0.428769E+11 | 0.00 | 533.67 | 0.268716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45326.50 | 29-JUN-08:03 | 20526.86 | 06-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.536037E+11 | 0.00 | 568.33 | 0.303210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49419.14 | 26-JUL-08:03 | 21491.75 | 08-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.548217E+11 | 0.00 | 568.33 | 0.314505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47944.72 | 24-AUG-08:61 | 20876.30 | 01-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.383916E+11 | 0.00 | 531.00 | 0.234458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45948.22 | 17-SEP-08:03 | 19667.55 | 07-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.154476E+11 | 0.00 | 294.00 | 0.952848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43943.86 | 18-OCT-21:52 | 18695.53 | 10-OCT-15:12 | 0.00 | 0.00 | 0.00 |
November | 0.541787E+10 | 0.00 | 161.83 | 0.391160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27191.69 | 19-NOV-24:00 | 16616.00 | 05-NOV-15:12 | 0.00 | 0.00 | 0.00 |
December | 0.111289E+10 | 0.00 | 48.50 | 0.884908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19514.41 | 12-DEC-13:30 | 14602.71 | 12-DEC-16:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263487E+12 | 0.00 | 3924.83 | 0.164965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.661161E+09 | 0.00 | 29.17 | 0.498469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13220.25 | 12205.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.548217E+11 | 0.00 | 568.33 | 0.314505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49419.14 | 21491.75 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.961446E+10 | 0.00 | 59.32 | 0.800158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 144602.17 | 19-JAN-21:00 | 101655.92 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.327683E+11 | 0.00 | 146.28 | 0.321511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163518.19 | 28-FEB-17:00 | 163518.19 | 28-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.954473E+11 | 0.00 | 341.00 | 0.920253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 236635.18 | 30-MAR-18:10 | 229880.27 | 30-MAR-19:10 | 0.00 | 0.00 | 0.00 |
April | 0.195651E+12 | 0.00 | 498.25 | 0.172162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 262579.72 | 17-APR-17:15 | 262579.72 | 17-APR-17:15 | 0.00 | 0.00 | 0.00 |
May | 0.372470E+12 | 0.00 | 686.67 | 0.279831E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 342117.28 | 30-MAY-21:10 | 283820.66 | 16-MAY-18:15 | 0.00 | 0.00 | 0.00 |
June | 0.576425E+12 | 0.00 | 702.33 | 0.393037E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 400677.59 | 26-JUN-18:10 | 280142.16 | 10-JUN-17:20 | 0.00 | 0.00 | 0.00 |
July | 0.734330E+12 | 0.00 | 744.00 | 0.445844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 405407.16 | 18-JUL-19:50 | 255621.17 | 08-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.781520E+12 | 0.00 | 744.00 | 0.467266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 470616.02 | 23-AUG-21:00 | 254362.64 | 02-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 0.503432E+12 | 0.00 | 698.00 | 0.336112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 405168.39 | 27-SEP-18:07 | 236504.97 | 07-SEP-18:10 | 0.00 | 0.00 | 0.00 |
October | 0.203016E+12 | 0.00 | 423.33 | 0.145510E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 430642.65 | 18-OCT-19:40 | 210254.40 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.738528E+11 | 0.00 | 257.65 | 0.609510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 251189.70 | 27-NOV-19:05 | 161384.26 | 27-NOV-19:05 | 0.00 | 0.00 | 0.00 |
December | 0.164799E+11 | 0.00 | 82.09 | 0.139202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188817.44 | 13-DEC-11:35 | 132934.12 | 12-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.359501E+13 | 0.00 | 5382.93 | 0.244681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.961446E+10 | 0.00 | 59.32 | 0.800158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 144602.17 | 101655.92 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.781520E+12 | 0.00 | 744.00 | 0.467266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 470616.02 | 283820.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.115839E+09 | 0.00 | 34.69 | 98042805.60 | 0.00 | 0.00 | 0.00 | 0.00 | 13589.40 | 28-JAN-16:11 | 13589.40 | 28-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.564252E+09 | 0.00 | 118.03 | 0.449537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13591.51 | 28-FEB-19:01 | 13591.51 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.223407E+10 | 0.00 | 367.55 | 0.140457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13995.63 | 28-MAR-15:11 | 13587.48 | 06-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.418175E+10 | 0.00 | 544.58 | 0.219349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14444.23 | 02-APR-15:11 | 13587.08 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.642857E+10 | 0.00 | 662.96 | 0.326608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14844.54 | 27-MAY-08:62 | 13591.00 | 09-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.866313E+10 | 0.00 | 678.56 | 0.493159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15401.75 | 29-JUN-08:62 | 11933.26 | 26-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.993661E+10 | 0.00 | 701.38 | 0.583139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16121.84 | 27-JUL-08:61 | 12082.21 | 27-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.104657E+11 | 0.00 | 710.60 | 0.621937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15827.51 | 29-AUG-08:62 | 12047.76 | 07-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.694681E+10 | 0.00 | 643.75 | 0.356254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15678.84 | 17-SEP-08:62 | 12195.98 | 09-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.340826E+10 | 0.00 | 472.01 | 0.162743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15335.81 | 18-OCT-08:62 | 13315.20 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.107293E+10 | 0.00 | 247.62 | 0.575538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14873.49 | 04-NOV-15:12 | 13589.41 | 07-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.278419E+09 | 0.00 | 74.52 | 0.165396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14033.68 | 13-DEC-16:12 | 13589.78 | 09-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.542964E+11 | 0.00 | 5256.25 | 0.303250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.115839E+09 | 0.00 | 34.69 | 98042805.60 | 0.00 | 0.00 | 0.00 | 0.00 | 13589.40 | 11933.26 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.104657E+11 | 0.00 | 710.60 | 0.621937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16121.84 | 13591.51 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6971892.47 | 0.00 | 2.57 | 4662746.38 | 0.00 | 0.00 | 0.00 | 0.00 | 6449.85 | 14-JAN-16:17 | 6449.85 | 14-JAN-16:17 | 0.00 | 0.00 | 0.00 |
February | 92542739.50 | 0.00 | 40.58 | 57235569.95 | 0.00 | 0.00 | 0.00 | 0.00 | 12657.99 | 24-FEB-19:01 | 12657.99 | 24-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.929400E+09 | 0.00 | 198.17 | 0.479676E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13712.06 | 28-MAR-18:01 | 13427.64 | 18-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.266110E+10 | 0.00 | 388.37 | 0.125698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14538.98 | 02-APR-15:11 | 14161.98 | 26-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.501487E+10 | 0.00 | 491.86 | 0.260036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15383.33 | 07-MAY-17:41 | 14129.54 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.785487E+10 | 0.00 | 562.77 | 0.470849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16270.36 | 26-JUN-08:21 | 12110.70 | 16-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.901318E+10 | 0.00 | 588.13 | 0.554393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16435.01 | 23-JUL-08:51 | 12102.58 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.931607E+10 | 0.00 | 619.05 | 0.561095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17407.09 | 20-AUG-07:52 | 12865.58 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.519016E+10 | 0.00 | 486.25 | 0.261476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15834.46 | 17-SEP-08:52 | 12801.89 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.152104E+10 | 0.00 | 278.88 | 0.584020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15259.57 | 18-OCT-21:52 | 12812.59 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.176024E+09 | 0.00 | 83.25 | 70054612.99 | 0.00 | 0.00 | 0.00 | 0.00 | 13940.00 | 05-NOV-15:12 | 12736.10 | 06-NOV-19:12 | 0.00 | 0.00 | 0.00 |
December | 24722644.05 | 0.00 | 13.19 | 14064900.61 | 0.00 | 0.00 | 0.00 | 0.00 | 12512.68 | 09-DEC-16:11 | 12512.68 | 09-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418010E+11 | 0.00 | 3753.07 | 0.235452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6971892.47 | 0.00 | 2.57 | 4662746.38 | 0.00 | 0.00 | 0.00 | 0.00 | 6449.85 | 6449.85 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.931607E+10 | 0.00 | 619.05 | 0.561095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17407.09 | 14161.98 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.106741E+10 | 0.00 | 43.22 | 0.873524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20584.12 | 29-JAN-13:30 | 20584.12 | 29-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.510618E+10 | 0.00 | 124.17 | 0.483142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29306.01 | 26-FEB-14:25 | 29306.01 | 26-FEB-14:25 | 0.00 | 0.00 | 0.00 |
March | 0.158248E+11 | 0.00 | 452.98 | 0.102517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30216.82 | 30-MAR-13:30 | 27551.14 | 13-MAR-16:10 | 0.00 | 0.00 | 0.00 |
April | 0.193001E+11 | 0.00 | 558.88 | 0.808866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26562.78 | 15-APR-13:40 | 20689.10 | 10-APR-16:10 | 0.00 | 0.00 | 0.00 |
May | 0.259864E+11 | 0.00 | 683.06 | 0.925339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22997.17 | 30-MAY-16:20 | 12311.57 | 19-MAY-17:20 | 0.00 | 0.00 | 0.00 |
June | 0.349441E+11 | 0.00 | 704.58 | 0.142671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26458.62 | 13-JUN-17:15 | 15763.90 | 13-JUN-17:20 | 0.00 | 0.00 | 0.00 |
July | 0.416446E+11 | 0.00 | 740.42 | 0.181586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29478.20 | 08-JUL-17:15 | 19659.44 | 08-JUL-17:30 | 0.00 | 0.00 | 0.00 |
August | 0.484782E+11 | 0.00 | 743.00 | 0.234025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33081.56 | 19-AUG-15:10 | 24179.41 | 19-AUG-13:40 | 0.00 | 0.00 | 0.00 |
September | 0.363918E+11 | 0.00 | 689.10 | 0.169782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37269.73 | 24-SEP-12:30 | 32771.74 | 24-SEP-12:40 | 0.00 | 0.00 | 0.00 |
October | 0.259432E+11 | 0.00 | 545.68 | 0.132045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40376.09 | 10-OCT-13:30 | 38203.48 | 10-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 0.151946E+11 | 0.00 | 414.64 | 0.112478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33897.25 | 06-NOV-13:40 | 33713.96 | 15-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.676942E+10 | 0.00 | 197.16 | 0.535071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32423.50 | 12-DEC-12:30 | 32154.12 | 10-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276651E+12 | 0.00 | 5896.90 | 0.135908E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.106741E+10 | 0.00 | 43.22 | 0.873524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20584.12 | 12311.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.484782E+11 | 0.00 | 743.00 | 0.234025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40376.09 | 38203.48 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.105166E+10 | 0.00 | 45.20 | 0.477995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75932.26 | 20-JAN-09:03 | 66922.09 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.395168E+10 | 0.00 | 142.90 | 0.234123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84568.15 | 18-FEB-09:02 | 80934.97 | 28-FEB-22:52 | 0.00 | 0.00 | 0.00 |
March | 0.124347E+11 | 0.00 | 316.52 | 0.739579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82119.05 | 28-MAR-21:52 | 81457.55 | 31-MAR-20:12 | 0.00 | 0.00 | 0.00 |
April | 0.247414E+11 | 0.00 | 368.94 | 0.141353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89916.80 | 30-APR-21:52 | 80468.93 | 25-APR-19:01 | 0.00 | 0.00 | 0.00 |
May | 0.396896E+11 | 0.00 | 430.37 | 0.232655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95314.10 | 07-MAY-17:41 | 85231.24 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.549097E+11 | 0.00 | 513.45 | 0.348094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99574.16 | 26-JUN-08:21 | 75157.53 | 03-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.616546E+11 | 0.00 | 542.30 | 0.390691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101253.23 | 23-JUL-08:51 | 74949.65 | 11-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.614714E+11 | 0.00 | 565.50 | 0.377471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110187.06 | 20-AUG-07:52 | 76806.23 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.397925E+11 | 0.00 | 427.95 | 0.222544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98314.49 | 17-SEP-08:52 | 75071.97 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.181195E+11 | 0.00 | 363.10 | 0.835851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97828.30 | 18-OCT-21:52 | 81854.60 | 11-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.762546E+10 | 0.00 | 236.34 | 0.416255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88209.51 | 05-NOV-21:52 | 78624.81 | 06-NOV-19:12 | 0.00 | 0.00 | 0.00 |
December | 0.232633E+10 | 0.00 | 102.91 | 0.115270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85609.87 | 13-DEC-21:03 | 68237.33 | 30-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327769E+12 | 0.00 | 4055.48 | 0.195170E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.105166E+10 | 0.00 | 45.20 | 0.477995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75932.26 | 66922.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.616546E+11 | 0.00 | 565.50 | 0.390691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110187.06 | 85231.24 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.105682E+09 | 0.00 | 29.95 | 78945897.22 | 0.00 | 0.00 | 0.00 | 0.00 | 12025.72 | 29-JAN-16:11 | 12025.72 | 29-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.646021E+09 | 0.00 | 132.63 | 0.503384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12283.78 | 28-FEB-19:01 | 12283.78 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.197828E+10 | 0.00 | 391.97 | 0.112065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12801.38 | 30-MAR-08:62 | 12281.09 | 06-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.405010E+10 | 0.00 | 566.82 | 0.206637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13102.80 | 02-APR-15:11 | 12277.97 | 09-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.662286E+10 | 0.00 | 688.21 | 0.344013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13484.09 | 27-MAY-08:62 | 12281.46 | 09-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.889652E+10 | 0.00 | 697.34 | 0.511728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13882.17 | 23-JUN-08:61 | 11033.97 | 02-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.102948E+11 | 0.00 | 715.01 | 0.615714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14579.15 | 27-JUL-08:61 | 10959.63 | 06-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.105525E+11 | 0.00 | 720.76 | 0.634821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13795.71 | 24-AUG-08:61 | 11008.50 | 01-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.701028E+10 | 0.00 | 654.29 | 0.366990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14194.44 | 17-SEP-08:62 | 10950.71 | 01-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.336349E+10 | 0.00 | 487.48 | 0.159740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13929.66 | 18-OCT-08:62 | 11348.34 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.973658E+09 | 0.00 | 249.24 | 0.486632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13392.84 | 04-NOV-15:12 | 12279.57 | 14-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.261909E+09 | 0.00 | 75.68 | 0.130485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12564.24 | 13-DEC-16:12 | 11883.16 | 09-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.547561E+11 | 0.00 | 5409.38 | 0.307165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.105682E+09 | 0.00 | 29.95 | 78945897.22 | 0.00 | 0.00 | 0.00 | 0.00 | 12025.72 | 10950.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.105525E+11 | 0.00 | 720.76 | 0.634821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14579.15 | 12283.78 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9799459.22 | 0.00 | 2.88 | 5314965.72 | 0.00 | 0.00 | 0.00 | 0.00 | 7363.40 | 28-JAN-09:06 | 7363.40 | 28-JAN-09:06 | 0.00 | 0.00 | 0.00 |
February | 0.175404E+09 | 0.00 | 48.20 | 0.105085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11627.99 | 20-FEB-09:01 | 10276.22 | 27-FEB-22:42 | 0.00 | 0.00 | 0.00 |
March | 0.850304E+09 | 0.00 | 204.39 | 0.387364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12393.80 | 28-MAR-18:01 | 11332.25 | 12-MAR-19:01 | 0.00 | 0.00 | 0.00 |
April | 0.264809E+10 | 0.00 | 413.63 | 0.127927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13300.78 | 02-APR-15:11 | 11740.93 | 09-APR-20:11 | 0.00 | 0.00 | 0.00 |
May | 0.519487E+10 | 0.00 | 515.58 | 0.273944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14216.46 | 07-MAY-08:51 | 12300.32 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.797124E+10 | 0.00 | 576.50 | 0.477792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15399.17 | 13-JUN-08:62 | 12084.46 | 04-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.923466E+10 | 0.00 | 598.69 | 0.575787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15307.71 | 23-JUL-08:51 | 11358.25 | 07-JUL-06:51 | 0.00 | 0.00 | 0.00 |
August | 0.934985E+10 | 0.00 | 627.19 | 0.563917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15847.00 | 20-AUG-07:52 | 11897.12 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.520780E+10 | 0.00 | 502.24 | 0.265674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14911.94 | 07-SEP-08:31 | 11753.39 | 15-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.160455E+10 | 0.00 | 299.15 | 0.667261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13865.02 | 18-OCT-21:52 | 10940.58 | 02-OCT-15:12 | 0.00 | 0.00 | 0.00 |
November | 0.199611E+09 | 0.00 | 73.76 | 74850465.28 | 0.00 | 0.00 | 0.00 | 0.00 | 13435.26 | 05-NOV-15:12 | 10638.64 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 19343705.52 | 0.00 | 10.40 | 6472603.69 | 0.00 | 0.00 | 0.00 | 0.00 | 7538.67 | 02-DEC-09:04 | 7538.67 | 02-DEC-09:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.424655E+11 | 0.00 | 3872.61 | 0.240968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9799459.22 | 0.00 | 2.88 | 5314965.72 | 0.00 | 0.00 | 0.00 | 0.00 | 7363.40 | 7363.40 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.934985E+10 | 0.00 | 627.19 | 0.575787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15847.00 | 12300.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 20541250.02 | 0.00 | 18.97 | 17905366.21 | 0.00 | 0.00 | 0.00 | 0.00 | 3587.51 | 28-JAN-16:11 | 3587.51 | 28-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.129339E+09 | 0.00 | 90.71 | 0.106333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3587.45 | 28-FEB-19:01 | 3587.45 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.533628E+09 | 0.00 | 307.08 | 0.344088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3708.02 | 28-MAR-15:11 | 3586.94 | 06-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.103006E+10 | 0.00 | 492.91 | 0.573302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3917.93 | 23-APR-08:62 | 3586.32 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.163554E+10 | 0.00 | 651.20 | 0.862221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4064.27 | 27-MAY-08:62 | 3587.07 | 09-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.223913E+10 | 0.00 | 677.15 | 0.128563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4269.56 | 23-JUN-08:61 | 3111.11 | 26-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.257716E+10 | 0.00 | 697.55 | 0.152146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4488.20 | 30-JUL-08:62 | 3134.07 | 27-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.271125E+10 | 0.00 | 708.21 | 0.161223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4377.90 | 29-AUG-08:62 | 3161.79 | 07-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.170711E+10 | 0.00 | 618.66 | 0.881839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.95 | 17-SEP-08:62 | 3197.28 | 09-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.792825E+09 | 0.00 | 403.32 | 0.398353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4201.29 | 18-OCT-08:62 | 3534.63 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.237603E+09 | 0.00 | 184.69 | 0.132556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4012.89 | 04-NOV-15:12 | 3587.44 | 07-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 56880879.37 | 0.00 | 57.30 | 34821570.31 | 0.00 | 0.00 | 0.00 | 0.00 | 3768.98 | 13-DEC-16:12 | 3587.68 | 09-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136711E+11 | 0.00 | 4907.73 | 0.777074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 20541250.02 | 0.00 | 18.97 | 17905366.21 | 0.00 | 0.00 | 0.00 | 0.00 | 3587.45 | 3111.11 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.271125E+10 | 0.00 | 708.21 | 0.161223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4488.20 | 3587.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 927537.57 | 0.00 | 0.77 | 442843.93 | 0.00 | 0.00 | 0.00 | 0.00 | 832.54 | 10-JAN-16:14 | 605.33 | 29-JAN-19:03 | 0.00 | 0.00 | 0.00 |
February | 18107558.64 | 0.00 | 21.27 | 11716544.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3324.41 | 24-FEB-19:01 | 3324.41 | 24-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.211839E+09 | 0.00 | 160.51 | 0.111570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3610.15 | 30-MAR-08:52 | 3546.12 | 12-MAR-19:01 | 0.00 | 0.00 | 0.00 |
April | 0.654527E+09 | 0.00 | 356.37 | 0.326748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3907.08 | 02-APR-15:11 | 3752.83 | 26-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.131686E+10 | 0.00 | 494.84 | 0.707786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4111.02 | 07-MAY-17:41 | 3810.82 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.207079E+10 | 0.00 | 565.10 | 0.126098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4470.18 | 26-JUN-08:21 | 3153.03 | 03-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.237987E+10 | 0.00 | 588.82 | 0.147746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4449.60 | 23-JUL-08:51 | 3202.61 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.244528E+10 | 0.00 | 619.12 | 0.148028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4795.91 | 20-AUG-07:52 | 3439.20 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.129577E+10 | 0.00 | 477.60 | 0.657607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4330.57 | 17-SEP-08:52 | 3364.82 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.333610E+09 | 0.00 | 216.07 | 0.136060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4182.25 | 18-OCT-21:52 | 3387.77 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 28457352.51 | 0.00 | 40.57 | 11510102.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3743.07 | 05-NOV-21:52 | 2957.43 | 06-NOV-19:12 | 0.00 | 0.00 | 0.00 |
December | 2888509.09 | 0.00 | 5.05 | 1667367.85 | 0.00 | 0.00 | 0.00 | 0.00 | 1842.12 | 07-DEC-16:11 | 1748.70 | 09-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107589E+11 | 0.00 | 3546.08 | 0.618383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 927537.57 | 0.00 | 0.77 | 442843.93 | 0.00 | 0.00 | 0.00 | 0.00 | 832.54 | 605.33 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.244528E+10 | 0.00 | 619.12 | 0.148028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4795.91 | 3810.82 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.128197E+10 | 0.00 | 149.69 | 0.993529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16089.22 | 26-JAN-16:11 | 16089.22 | 26-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.198152E+10 | 0.00 | 215.44 | 0.158998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16090.14 | 26-FEB-19:01 | 16090.14 | 26-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.434622E+10 | 0.00 | 465.22 | 0.288231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16234.59 | 31-MAR-15:11 | 16089.04 | 18-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.584301E+10 | 0.00 | 545.94 | 0.318679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17276.41 | 21-APR-18:01 | 16083.21 | 09-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.811913E+10 | 0.00 | 654.50 | 0.407270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17803.98 | 27-MAY-08:62 | 16088.93 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.106635E+11 | 0.00 | 670.30 | 0.583509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19804.14 | 23-JUN-08:61 | 14338.13 | 15-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.125948E+11 | 0.00 | 693.71 | 0.717099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20569.91 | 27-JUL-08:61 | 14437.15 | 27-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.140394E+11 | 0.00 | 706.22 | 0.854982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20097.94 | 29-AUG-08:62 | 14507.01 | 19-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.102647E+11 | 0.00 | 636.34 | 0.578842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19583.32 | 17-SEP-08:62 | 14395.94 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.688502E+10 | 0.00 | 545.35 | 0.405125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18953.40 | 18-OCT-08:62 | 16090.19 | 12-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.412052E+10 | 0.00 | 424.67 | 0.267496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17527.32 | 04-NOV-15:12 | 16091.29 | 14-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.230724E+10 | 0.00 | 247.60 | 0.166599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16640.11 | 13-DEC-16:12 | 16094.66 | 27-DEC-17:21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.824470E+11 | 0.00 | 5954.98 | 0.484618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.128197E+10 | 0.00 | 149.69 | 0.993529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16089.22 | 14338.13 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.140394E+11 | 0.00 | 706.22 | 0.854982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20569.91 | 16094.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 520.68 | 361.70 | 158.98 | 598.47 | 564.40 | 0.00 | 0.00 | 0.00 |
February | 485.02 | 323.58 | 161.44 | 606.57 | 472.13 | 0.00 | 0.00 | 0.00 |
March | 443.52 | 232.74 | 210.78 | 614.54 | 312.15 | 0.00 | 0.00 | 0.00 |
April | 333.78 | 111.36 | 222.42 | 518.00 | 250.03 | 0.00 | 0.00 | 0.00 |
May | 268.30 | 32.83 | 235.47 | 442.59 | 159.78 | 0.00 | 0.00 | 0.00 |
June | 246.36 | 13.75 | 232.60 | 474.11 | 96.68 | 0.00 | 0.00 | 0.00 |
July | 247.12 | 16.67 | 230.46 | 501.06 | 62.34 | 0.00 | 0.00 | 0.00 |
August | 297.77 | 55.96 | 241.81 | 607.44 | 50.69 | 0.00 | 0.00 | 0.00 |
September | 336.19 | 130.81 | 205.38 | 586.97 | 130.02 | 0.00 | 0.00 | 0.00 |
October | 472.07 | 305.12 | 166.95 | 710.78 | 283.69 | 0.00 | 0.00 | 0.00 |
November | 515.76 | 344.17 | 171.59 | 698.77 | 376.70 | 0.00 | 0.00 | 0.00 |
December | 517.01 | 363.70 | 153.31 | 636.52 | 472.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 389.87 | 190.39 | 199.48 | 582.94 | 268.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.36 | 13.75 | 153.31 | 442.59 | 50.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 520.68 | 363.70 | 241.81 | 710.78 | 564.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1466.20 | 1018.53 | 447.67 | 1683.48 | 1616.70 | 0.00 | 0.00 | 0.00 |
February | 1365.78 | 911.17 | 454.61 | 1712.22 | 1351.29 | 0.00 | 0.00 | 0.00 |
March | 1248.92 | 655.38 | 593.54 | 1758.30 | 868.34 | 0.00 | 0.00 | 0.00 |
April | 939.90 | 313.58 | 626.32 | 1506.03 | 673.59 | 0.00 | 0.00 | 0.00 |
May | 755.53 | 92.46 | 663.07 | 1323.84 | 405.78 | 0.00 | 0.00 | 0.00 |
June | 693.72 | 38.73 | 654.99 | 1438.84 | 229.17 | 0.00 | 0.00 | 0.00 |
July | 695.89 | 46.94 | 648.95 | 1514.61 | 139.84 | 0.00 | 0.00 | 0.00 |
August | 838.51 | 157.59 | 680.92 | 1803.63 | 109.24 | 0.00 | 0.00 | 0.00 |
September | 946.68 | 368.34 | 578.34 | 1719.21 | 322.76 | 0.00 | 0.00 | 0.00 |
October | 1329.32 | 859.19 | 470.13 | 2033.48 | 777.61 | 0.00 | 0.00 | 0.00 |
November | 1452.34 | 969.15 | 483.19 | 1981.99 | 1060.46 | 0.00 | 0.00 | 0.00 |
December | 1455.88 | 1024.16 | 431.72 | 1794.07 | 1352.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1097.86 | 536.13 | 561.73 | 1689.25 | 739.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 693.72 | 38.73 | 431.72 | 1323.84 | 109.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1466.20 | 1024.16 | 680.92 | 2033.48 | 1616.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1904.67 | 1323.13 | 581.55 | 2213.10 | 2221.72 | 0.00 | 0.00 | 0.00 |
February | 1774.23 | 1183.66 | 590.56 | 2252.17 | 1863.66 | 0.00 | 0.00 | 0.00 |
March | 1622.42 | 851.37 | 771.05 | 2304.01 | 1213.58 | 0.00 | 0.00 | 0.00 |
April | 1220.99 | 407.36 | 813.62 | 1961.56 | 956.28 | 0.00 | 0.00 | 0.00 |
May | 981.47 | 120.11 | 861.37 | 1707.77 | 592.47 | 0.00 | 0.00 | 0.00 |
June | 901.18 | 50.31 | 850.87 | 1849.03 | 342.87 | 0.00 | 0.00 | 0.00 |
July | 904.00 | 60.98 | 843.02 | 1950.22 | 215.43 | 0.00 | 0.00 | 0.00 |
August | 1089.28 | 204.72 | 884.56 | 2344.09 | 166.19 | 0.00 | 0.00 | 0.00 |
September | 1229.79 | 478.50 | 751.29 | 2234.27 | 475.67 | 0.00 | 0.00 | 0.00 |
October | 1726.86 | 1116.14 | 610.72 | 2665.72 | 1096.01 | 0.00 | 0.00 | 0.00 |
November | 1886.68 | 1258.98 | 627.69 | 2596.07 | 1480.87 | 0.00 | 0.00 | 0.00 |
December | 1891.27 | 1330.44 | 560.83 | 2353.51 | 1876.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1426.18 | 696.47 | 729.71 | 2202.68 | 1037.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 901.18 | 50.31 | 560.83 | 1707.77 | 166.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1904.67 | 1330.44 | 884.56 | 2665.72 | 2221.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.95 | 71.51 | 31.43 | 119.76 | 113.04 | 0.00 | 0.00 | 0.00 |
February | 95.90 | 63.98 | 31.92 | 121.29 | 93.04 | 0.00 | 0.00 | 0.00 |
March | 87.69 | 46.02 | 41.68 | 123.07 | 57.70 | 0.00 | 0.00 | 0.00 |
April | 65.99 | 22.02 | 43.98 | 104.58 | 44.48 | 0.00 | 0.00 | 0.00 |
May | 53.05 | 6.49 | 46.56 | 91.81 | 24.52 | 0.00 | 0.00 | 0.00 |
June | 48.71 | 2.72 | 45.99 | 102.49 | 11.37 | 0.00 | 0.00 | 0.00 |
July | 48.86 | 3.30 | 45.57 | 109.44 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 58.88 | 11.07 | 47.81 | 131.43 | 2.70 | 0.00 | 0.00 | 0.00 |
September | 66.47 | 25.86 | 40.61 | 122.34 | 16.89 | 0.00 | 0.00 | 0.00 |
October | 93.34 | 60.33 | 33.01 | 144.07 | 49.44 | 0.00 | 0.00 | 0.00 |
November | 101.97 | 68.05 | 33.93 | 140.87 | 70.50 | 0.00 | 0.00 | 0.00 |
December | 102.22 | 71.91 | 30.31 | 127.81 | 92.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.09 | 37.64 | 39.44 | 119.93 | 48.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.71 | 2.72 | 30.31 | 91.81 | 2.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.95 | 71.91 | 47.81 | 144.07 | 113.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.08 | 38.17 | 43.92 | 64.61 | 238.16 | 0.00 | 0.00 | 0.00 |
February | 94.04 | 44.07 | 49.96 | 97.21 | 192.81 | 0.00 | 0.00 | 0.00 |
March | 137.97 | 66.54 | 71.43 | 177.66 | 111.63 | 0.00 | 0.00 | 0.00 |
April | 155.47 | 71.11 | 84.36 | 233.58 | 81.88 | 0.00 | 0.00 | 0.00 |
May | 156.43 | 59.37 | 97.06 | 261.81 | 45.42 | 0.00 | 0.00 | 0.00 |
June | 164.35 | 63.28 | 101.07 | 313.78 | 21.11 | 0.00 | 0.00 | 0.00 |
July | 154.70 | 57.22 | 97.48 | 310.35 | 10.01 | 0.00 | 0.00 | 0.00 |
August | 151.95 | 56.83 | 95.12 | 306.94 | 5.04 | 0.00 | 0.00 | 0.00 |
September | 124.13 | 51.89 | 72.24 | 216.37 | 31.66 | 0.00 | 0.00 | 0.00 |
October | 110.45 | 57.43 | 53.02 | 157.74 | 97.33 | 0.00 | 0.00 | 0.00 |
November | 87.72 | 39.23 | 48.49 | 102.01 | 145.04 | 0.00 | 0.00 | 0.00 |
December | 72.66 | 31.83 | 40.83 | 62.89 | 194.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.48 | 53.12 | 71.36 | 192.59 | 97.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.66 | 31.83 | 40.83 | 62.89 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 164.35 | 71.11 | 101.07 | 313.78 | 238.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.39 | 0.00 | 19.39 | 3.07 | 134.32 | 0.00 | 0.00 | 0.00 |
February | 21.49 | 0.00 | 21.49 | 10.36 | 107.41 | 0.00 | 0.00 | 0.00 |
March | 30.18 | 0.00 | 30.18 | 23.70 | 61.75 | 0.00 | 0.00 | 0.00 |
April | 36.59 | 0.21 | 36.38 | 44.90 | 45.46 | 0.00 | 0.00 | 0.00 |
May | 43.66 | 1.37 | 42.29 | 68.26 | 24.88 | 0.00 | 0.00 | 0.00 |
June | 48.02 | 3.15 | 44.87 | 97.65 | 11.37 | 0.00 | 0.00 | 0.00 |
July | 45.48 | 2.33 | 43.15 | 99.71 | 5.89 | 0.00 | 0.00 | 0.00 |
August | 40.39 | 0.47 | 39.92 | 91.92 | 3.00 | 0.00 | 0.00 | 0.00 |
September | 30.49 | 0.01 | 30.48 | 52.94 | 18.36 | 0.00 | 0.00 | 0.00 |
October | 23.17 | 0.00 | 23.17 | 24.15 | 53.46 | 0.00 | 0.00 | 0.00 |
November | 20.73 | 0.00 | 20.73 | 13.31 | 78.22 | 0.00 | 0.00 | 0.00 |
December | 17.92 | 0.00 | 17.92 | 4.04 | 106.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.51 | 0.63 | 30.88 | 44.70 | 53.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.92 | 0.00 | 17.92 | 3.07 | 3.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.02 | 3.15 | 44.87 | 99.71 | 134.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.08 | 38.17 | 43.92 | 68.25 | 233.91 | 0.00 | 0.00 | 0.00 |
February | 94.04 | 44.07 | 49.96 | 100.55 | 189.90 | 0.00 | 0.00 | 0.00 |
March | 137.97 | 66.54 | 71.43 | 179.99 | 111.18 | 0.00 | 0.00 | 0.00 |
April | 155.47 | 71.11 | 84.36 | 233.35 | 84.31 | 0.00 | 0.00 | 0.00 |
May | 156.43 | 59.37 | 97.06 | 259.48 | 48.77 | 0.00 | 0.00 | 0.00 |
June | 164.35 | 63.28 | 101.07 | 311.05 | 22.77 | 0.00 | 0.00 | 0.00 |
July | 154.70 | 57.22 | 97.48 | 307.74 | 11.34 | 0.00 | 0.00 | 0.00 |
August | 151.95 | 56.83 | 95.12 | 305.70 | 5.68 | 0.00 | 0.00 | 0.00 |
September | 124.13 | 51.89 | 72.24 | 215.89 | 33.99 | 0.00 | 0.00 | 0.00 |
October | 110.45 | 57.43 | 53.02 | 159.86 | 97.79 | 0.00 | 0.00 | 0.00 |
November | 87.72 | 39.23 | 48.49 | 106.18 | 142.26 | 0.00 | 0.00 | 0.00 |
December | 72.66 | 31.83 | 40.83 | 67.12 | 190.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.48 | 53.12 | 71.36 | 193.43 | 97.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.66 | 31.83 | 40.83 | 67.12 | 5.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 164.35 | 71.11 | 101.07 | 311.05 | 233.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.34 | 57.20 | 25.14 | 90.74 | 98.51 | 0.00 | 0.00 | 0.00 |
February | 76.70 | 51.17 | 25.53 | 88.65 | 93.14 | 0.00 | 0.00 | 0.00 |
March | 70.14 | 36.81 | 33.33 | 85.67 | 70.75 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 17.61 | 35.17 | 70.94 | 57.77 | 0.00 | 0.00 | 0.00 |
May | 42.43 | 5.19 | 37.24 | 59.77 | 38.84 | 0.00 | 0.00 | 0.00 |
June | 38.96 | 2.18 | 36.78 | 65.97 | 24.42 | 0.00 | 0.00 | 0.00 |
July | 39.08 | 2.64 | 36.45 | 70.38 | 17.94 | 0.00 | 0.00 | 0.00 |
August | 47.09 | 8.85 | 38.24 | 87.58 | 15.53 | 0.00 | 0.00 | 0.00 |
September | 53.17 | 20.69 | 32.48 | 84.24 | 32.91 | 0.00 | 0.00 | 0.00 |
October | 74.65 | 48.25 | 26.40 | 103.08 | 64.25 | 0.00 | 0.00 | 0.00 |
November | 81.56 | 54.43 | 27.14 | 99.75 | 83.56 | 0.00 | 0.00 | 0.00 |
December | 81.76 | 57.52 | 24.25 | 91.21 | 98.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.66 | 30.11 | 31.55 | 83.15 | 57.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.96 | 2.18 | 24.25 | 59.77 | 15.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.34 | 57.52 | 38.24 | 103.08 | 98.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.51 | 0.00 | 15.51 | 2.20 | 112.54 | 0.00 | 0.00 | 0.00 |
February | 17.20 | 0.00 | 17.20 | 8.26 | 89.39 | 0.00 | 0.00 | 0.00 |
March | 24.15 | 0.00 | 24.15 | 20.04 | 49.23 | 0.00 | 0.00 | 0.00 |
April | 29.28 | 0.17 | 29.11 | 38.08 | 35.39 | 0.00 | 0.00 | 0.00 |
May | 34.93 | 1.10 | 33.84 | 57.51 | 18.74 | 0.00 | 0.00 | 0.00 |
June | 38.42 | 2.52 | 35.90 | 82.06 | 7.90 | 0.00 | 0.00 | 0.00 |
July | 36.39 | 1.86 | 34.52 | 84.05 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 32.32 | 0.38 | 31.94 | 78.33 | 1.64 | 0.00 | 0.00 | 0.00 |
September | 24.40 | 0.01 | 24.39 | 45.09 | 13.59 | 0.00 | 0.00 | 0.00 |
October | 18.54 | 0.00 | 18.54 | 20.52 | 42.61 | 0.00 | 0.00 | 0.00 |
November | 16.59 | 0.00 | 16.59 | 10.68 | 64.34 | 0.00 | 0.00 | 0.00 |
December | 14.34 | 0.00 | 14.34 | 2.80 | 89.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.21 | 0.51 | 24.71 | 37.64 | 43.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.34 | 0.00 | 14.34 | 2.20 | 1.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.42 | 2.52 | 35.90 | 84.05 | 112.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.11 | 36.47 | 43.63 | 55.04 | 231.38 | 0.00 | 0.00 | 0.00 |
February | 100.54 | 54.12 | 46.42 | 97.66 | 182.36 | 0.00 | 0.00 | 0.00 |
March | 126.49 | 57.70 | 68.79 | 150.23 | 103.67 | 0.00 | 0.00 | 0.00 |
April | 152.90 | 69.79 | 83.11 | 222.97 | 75.51 | 0.00 | 0.00 | 0.00 |
May | 167.50 | 70.84 | 96.67 | 276.10 | 41.92 | 0.00 | 0.00 | 0.00 |
June | 173.25 | 72.57 | 100.68 | 327.20 | 19.23 | 0.00 | 0.00 | 0.00 |
July | 168.87 | 70.85 | 98.02 | 333.34 | 9.64 | 0.00 | 0.00 | 0.00 |
August | 154.77 | 61.39 | 93.38 | 312.24 | 4.74 | 0.00 | 0.00 | 0.00 |
September | 126.85 | 56.05 | 70.80 | 219.95 | 30.12 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 56.47 | 52.02 | 147.52 | 90.87 | 0.00 | 0.00 | 0.00 |
November | 86.41 | 38.98 | 47.43 | 88.81 | 133.92 | 0.00 | 0.00 | 0.00 |
December | 74.98 | 34.13 | 40.85 | 55.63 | 183.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.89 | 56.60 | 70.29 | 191.06 | 91.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.98 | 34.13 | 40.85 | 55.04 | 4.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.25 | 72.57 | 100.68 | 333.34 | 231.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.95 | 71.51 | 31.43 | 119.16 | 112.76 | 0.00 | 0.00 | 0.00 |
February | 95.90 | 63.98 | 31.92 | 120.31 | 92.83 | 0.00 | 0.00 | 0.00 |
March | 87.69 | 46.02 | 41.68 | 122.22 | 57.19 | 0.00 | 0.00 | 0.00 |
April | 65.99 | 22.02 | 43.98 | 103.69 | 44.19 | 0.00 | 0.00 | 0.00 |
May | 53.05 | 6.49 | 46.56 | 90.95 | 24.37 | 0.00 | 0.00 | 0.00 |
June | 48.71 | 2.72 | 45.99 | 101.76 | 11.22 | 0.00 | 0.00 | 0.00 |
July | 48.86 | 3.30 | 45.57 | 108.81 | 5.33 | 0.00 | 0.00 | 0.00 |
August | 58.88 | 11.07 | 47.81 | 131.14 | 2.61 | 0.00 | 0.00 | 0.00 |
September | 66.47 | 25.86 | 40.61 | 121.89 | 16.71 | 0.00 | 0.00 | 0.00 |
October | 93.34 | 60.33 | 33.01 | 143.36 | 49.10 | 0.00 | 0.00 | 0.00 |
November | 101.97 | 68.05 | 33.93 | 140.24 | 70.19 | 0.00 | 0.00 | 0.00 |
December | 102.22 | 71.91 | 30.31 | 127.20 | 92.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.09 | 37.64 | 39.44 | 119.24 | 48.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.71 | 2.72 | 30.31 | 90.95 | 2.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.95 | 71.91 | 47.81 | 143.36 | 112.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.39 | 0.00 | 19.39 | 2.92 | 134.37 | 0.00 | 0.00 | 0.00 |
February | 21.49 | 0.00 | 21.49 | 9.92 | 107.54 | 0.00 | 0.00 | 0.00 |
March | 30.18 | 0.00 | 30.18 | 23.24 | 61.04 | 0.00 | 0.00 | 0.00 |
April | 36.59 | 0.21 | 36.38 | 44.06 | 44.87 | 0.00 | 0.00 | 0.00 |
May | 43.66 | 1.37 | 42.29 | 67.14 | 24.50 | 0.00 | 0.00 | 0.00 |
June | 48.02 | 3.15 | 44.87 | 96.36 | 11.16 | 0.00 | 0.00 | 0.00 |
July | 45.48 | 2.33 | 43.15 | 98.55 | 5.86 | 0.00 | 0.00 | 0.00 |
August | 40.39 | 0.47 | 39.92 | 91.31 | 2.90 | 0.00 | 0.00 | 0.00 |
September | 30.49 | 0.01 | 30.48 | 52.16 | 18.13 | 0.00 | 0.00 | 0.00 |
October | 23.17 | 0.00 | 23.17 | 23.47 | 52.89 | 0.00 | 0.00 | 0.00 |
November | 20.73 | 0.00 | 20.73 | 13.06 | 77.69 | 0.00 | 0.00 | 0.00 |
December | 17.92 | 0.00 | 17.92 | 3.85 | 106.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.51 | 0.63 | 30.88 | 44.03 | 53.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.92 | 0.00 | 17.92 | 2.92 | 2.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.02 | 3.15 | 44.87 | 98.55 | 134.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.11 | 36.47 | 43.63 | 57.10 | 225.34 | 0.00 | 0.00 | 0.00 |
February | 100.54 | 54.12 | 46.42 | 100.62 | 178.66 | 0.00 | 0.00 | 0.00 |
March | 126.49 | 57.70 | 68.79 | 153.15 | 102.57 | 0.00 | 0.00 | 0.00 |
April | 152.90 | 69.79 | 83.11 | 223.13 | 77.53 | 0.00 | 0.00 | 0.00 |
May | 167.50 | 70.84 | 96.67 | 273.30 | 44.90 | 0.00 | 0.00 | 0.00 |
June | 173.25 | 72.57 | 100.68 | 323.10 | 20.67 | 0.00 | 0.00 | 0.00 |
July | 168.87 | 70.85 | 98.02 | 329.35 | 10.91 | 0.00 | 0.00 | 0.00 |
August | 154.77 | 61.39 | 93.38 | 310.15 | 5.28 | 0.00 | 0.00 | 0.00 |
September | 126.85 | 56.05 | 70.80 | 218.61 | 32.19 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 56.47 | 52.02 | 149.79 | 90.74 | 0.00 | 0.00 | 0.00 |
November | 86.41 | 38.98 | 47.43 | 93.18 | 130.19 | 0.00 | 0.00 | 0.00 |
December | 74.98 | 34.13 | 40.85 | 58.68 | 177.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.89 | 56.60 | 70.29 | 191.33 | 90.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.98 | 34.13 | 40.85 | 57.10 | 5.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.25 | 72.57 | 100.68 | 329.35 | 225.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.56 | 0.00 | 24.56 | 3.40 | 183.45 | 0.00 | 0.00 | 0.00 |
February | 27.22 | 0.00 | 27.22 | 12.79 | 145.17 | 0.00 | 0.00 | 0.00 |
March | 38.22 | 0.00 | 38.22 | 31.31 | 81.40 | 0.00 | 0.00 | 0.00 |
April | 46.34 | 0.27 | 46.07 | 59.71 | 60.12 | 0.00 | 0.00 | 0.00 |
May | 55.29 | 1.73 | 53.56 | 90.00 | 34.09 | 0.00 | 0.00 | 0.00 |
June | 60.81 | 3.99 | 56.83 | 124.63 | 18.23 | 0.00 | 0.00 | 0.00 |
July | 57.59 | 2.95 | 54.64 | 125.09 | 11.33 | 0.00 | 0.00 | 0.00 |
August | 51.15 | 0.60 | 50.55 | 114.06 | 7.74 | 0.00 | 0.00 | 0.00 |
September | 38.61 | 0.02 | 38.60 | 67.59 | 27.83 | 0.00 | 0.00 | 0.00 |
October | 29.34 | 0.00 | 29.34 | 31.00 | 72.64 | 0.00 | 0.00 | 0.00 |
November | 26.26 | 0.00 | 26.26 | 16.55 | 104.83 | 0.00 | 0.00 | 0.00 |
December | 22.70 | 0.00 | 22.70 | 4.09 | 145.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.91 | 0.80 | 39.11 | 56.93 | 74.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.70 | 0.00 | 22.70 | 3.40 | 7.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.81 | 3.99 | 56.83 | 125.09 | 183.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.05 | 0.00 | 9.05 | 1.25 | 67.63 | 0.00 | 0.00 | 0.00 |
February | 10.03 | 0.00 | 10.03 | 4.72 | 53.52 | 0.00 | 0.00 | 0.00 |
March | 14.09 | 0.00 | 14.09 | 11.54 | 30.01 | 0.00 | 0.00 | 0.00 |
April | 17.08 | 0.10 | 16.98 | 22.01 | 22.16 | 0.00 | 0.00 | 0.00 |
May | 20.38 | 0.64 | 19.74 | 33.18 | 12.57 | 0.00 | 0.00 | 0.00 |
June | 22.42 | 1.47 | 20.95 | 45.94 | 6.72 | 0.00 | 0.00 | 0.00 |
July | 21.23 | 1.09 | 20.14 | 46.11 | 4.18 | 0.00 | 0.00 | 0.00 |
August | 18.86 | 0.22 | 18.64 | 42.05 | 2.85 | 0.00 | 0.00 | 0.00 |
September | 14.23 | 0.01 | 14.23 | 24.92 | 10.26 | 0.00 | 0.00 | 0.00 |
October | 10.82 | 0.00 | 10.82 | 11.43 | 26.78 | 0.00 | 0.00 | 0.00 |
November | 9.68 | 0.00 | 9.68 | 6.10 | 38.64 | 0.00 | 0.00 | 0.00 |
December | 8.37 | 0.00 | 8.37 | 1.51 | 53.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.71 | 0.30 | 14.42 | 20.99 | 27.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.37 | 0.00 | 8.37 | 1.25 | 2.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.42 | 1.47 | 20.95 | 46.11 | 67.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 48.03 | 33.37 | 14.67 | 55.48 | 55.30 | 0.00 | 0.00 | 0.00 |
February | 44.75 | 29.85 | 14.89 | 56.70 | 45.39 | 0.00 | 0.00 | 0.00 |
March | 40.92 | 21.47 | 19.45 | 58.54 | 28.06 | 0.00 | 0.00 | 0.00 |
April | 30.79 | 10.27 | 20.52 | 49.84 | 22.37 | 0.00 | 0.00 | 0.00 |
May | 24.75 | 3.03 | 21.72 | 43.65 | 13.32 | 0.00 | 0.00 | 0.00 |
June | 22.73 | 1.27 | 21.46 | 47.57 | 7.25 | 0.00 | 0.00 | 0.00 |
July | 22.80 | 1.54 | 21.26 | 50.02 | 4.36 | 0.00 | 0.00 | 0.00 |
August | 27.47 | 5.16 | 22.31 | 60.11 | 2.90 | 0.00 | 0.00 | 0.00 |
September | 31.01 | 12.07 | 18.95 | 57.10 | 10.17 | 0.00 | 0.00 | 0.00 |
October | 43.55 | 28.15 | 15.40 | 67.90 | 24.99 | 0.00 | 0.00 | 0.00 |
November | 47.58 | 31.75 | 15.83 | 66.57 | 34.10 | 0.00 | 0.00 | 0.00 |
December | 47.70 | 33.55 | 14.14 | 59.61 | 44.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.97 | 17.56 | 18.40 | 56.10 | 24.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.73 | 1.27 | 14.14 | 43.65 | 2.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.03 | 33.55 | 22.31 | 67.90 | 55.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 130.38 | 90.57 | 39.81 | 150.59 | 150.11 | 0.00 | 0.00 | 0.00 |
February | 121.45 | 81.02 | 40.42 | 153.91 | 123.19 | 0.00 | 0.00 | 0.00 |
March | 111.06 | 58.28 | 52.78 | 158.88 | 76.16 | 0.00 | 0.00 | 0.00 |
April | 83.58 | 27.88 | 55.69 | 135.29 | 60.72 | 0.00 | 0.00 | 0.00 |
May | 67.18 | 8.22 | 58.96 | 118.48 | 36.16 | 0.00 | 0.00 | 0.00 |
June | 61.69 | 3.44 | 58.24 | 129.12 | 19.67 | 0.00 | 0.00 | 0.00 |
July | 61.88 | 4.17 | 57.71 | 135.78 | 11.84 | 0.00 | 0.00 | 0.00 |
August | 74.56 | 14.01 | 60.55 | 163.16 | 7.88 | 0.00 | 0.00 | 0.00 |
September | 84.18 | 32.75 | 51.43 | 154.98 | 27.61 | 0.00 | 0.00 | 0.00 |
October | 118.21 | 76.40 | 41.80 | 184.29 | 67.84 | 0.00 | 0.00 | 0.00 |
November | 129.14 | 86.18 | 42.97 | 180.68 | 92.55 | 0.00 | 0.00 | 0.00 |
December | 129.46 | 91.07 | 38.39 | 161.81 | 122.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.62 | 47.67 | 49.95 | 152.26 | 66.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.69 | 3.44 | 38.39 | 118.48 | 7.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.38 | 91.07 | 60.55 | 184.29 | 150.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.95 | 71.51 | 31.43 | 119.44 | 112.33 | 0.00 | 0.00 | 0.00 |
February | 95.90 | 63.98 | 31.92 | 120.72 | 92.31 | 0.17 | 0.00 | 0.00 |
March | 87.69 | 46.02 | 41.68 | 122.04 | 57.02 | 0.00 | 0.00 | 0.00 |
April | 65.99 | 22.02 | 43.98 | 103.51 | 43.96 | 0.00 | 0.00 | 0.00 |
May | 53.05 | 6.49 | 46.56 | 90.69 | 24.12 | 0.00 | 0.00 | 0.00 |
June | 48.71 | 2.72 | 45.99 | 101.74 | 10.92 | 0.00 | 0.00 | 0.00 |
July | 48.86 | 3.30 | 45.57 | 108.74 | 5.03 | 0.00 | 0.00 | 0.00 |
August | 58.88 | 11.07 | 47.81 | 130.65 | 2.40 | 0.00 | 0.00 | 0.00 |
September | 66.47 | 25.86 | 40.61 | 121.52 | 16.29 | 0.00 | 0.00 | 0.00 |
October | 93.34 | 60.33 | 33.01 | 143.17 | 48.59 | 0.67 | 0.00 | 0.00 |
November | 101.97 | 68.05 | 33.93 | 140.26 | 69.65 | 0.00 | 0.00 | 0.00 |
December | 102.22 | 71.91 | 30.31 | 127.43 | 91.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.09 | 37.64 | 39.44 | 119.17 | 47.63 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 48.71 | 2.72 | 30.31 | 90.69 | 2.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.95 | 71.91 | 47.81 | 143.17 | 112.33 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.08 | 38.17 | 43.92 | 64.58 | 236.67 | 0.00 | 0.00 | 0.00 |
February | 94.04 | 44.07 | 49.96 | 96.69 | 191.10 | 1.17 | 0.00 | 0.00 |
March | 137.97 | 66.54 | 71.43 | 175.91 | 110.12 | 0.00 | 0.00 | 0.00 |
April | 155.47 | 71.11 | 84.36 | 231.26 | 80.84 | 0.00 | 0.00 | 0.00 |
May | 156.43 | 59.37 | 97.06 | 259.12 | 44.63 | 0.00 | 0.00 | 0.00 |
June | 164.35 | 63.28 | 101.07 | 311.29 | 20.20 | 0.00 | 0.00 | 0.00 |
July | 154.70 | 57.22 | 97.48 | 308.32 | 9.30 | 0.00 | 0.00 | 0.00 |
August | 151.95 | 56.83 | 95.12 | 305.03 | 4.48 | 0.00 | 0.00 | 0.00 |
September | 124.13 | 51.89 | 72.24 | 214.88 | 30.46 | 0.00 | 0.00 | 0.00 |
October | 110.45 | 57.43 | 53.02 | 156.53 | 95.49 | 0.67 | 0.00 | 0.00 |
November | 87.72 | 39.23 | 48.49 | 101.40 | 143.18 | 0.00 | 0.00 | 0.00 |
December | 72.66 | 31.83 | 40.83 | 62.90 | 192.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.48 | 53.12 | 71.36 | 191.17 | 96.15 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 72.66 | 31.83 | 40.83 | 62.90 | 4.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 164.35 | 71.11 | 101.07 | 311.29 | 236.67 | 1.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.39 | 0.00 | 19.39 | 3.20 | 133.55 | 0.00 | 0.00 | 0.00 |
February | 21.49 | 0.00 | 21.49 | 10.52 | 106.58 | 1.33 | 0.00 | 0.00 |
March | 30.18 | 0.00 | 30.18 | 23.64 | 61.07 | 0.00 | 0.00 | 0.00 |
April | 36.59 | 0.21 | 36.38 | 44.33 | 45.31 | 0.00 | 0.00 | 0.00 |
May | 43.66 | 1.37 | 42.29 | 67.30 | 24.83 | 0.00 | 0.00 | 0.00 |
June | 48.02 | 3.15 | 44.87 | 97.00 | 11.04 | 0.00 | 0.00 | 0.00 |
July | 45.48 | 2.33 | 43.15 | 99.12 | 5.60 | 0.00 | 0.00 | 0.00 |
August | 40.39 | 0.47 | 39.92 | 91.48 | 2.69 | 0.00 | 0.00 | 0.00 |
September | 30.49 | 0.01 | 30.48 | 52.67 | 17.75 | 0.00 | 0.00 | 0.00 |
October | 23.17 | 0.00 | 23.17 | 24.27 | 52.56 | 0.83 | 0.00 | 0.00 |
November | 20.73 | 0.00 | 20.73 | 13.62 | 77.06 | 0.00 | 0.00 | 0.00 |
December | 17.92 | 0.00 | 17.92 | 4.36 | 105.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.51 | 0.63 | 30.88 | 44.49 | 53.36 | 2.17 | 0.00 | 0.00 |
Minimum of Months | 17.92 | 0.00 | 17.92 | 3.20 | 2.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.02 | 3.15 | 44.87 | 99.12 | 133.55 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.08 | 38.17 | 43.92 | 68.31 | 232.70 | 0.00 | 0.00 | 0.00 |
February | 94.04 | 44.07 | 49.96 | 100.18 | 188.39 | 1.33 | 0.00 | 0.00 |
March | 137.97 | 66.54 | 71.43 | 178.51 | 109.76 | 0.00 | 0.00 | 0.00 |
April | 155.47 | 71.11 | 84.36 | 230.86 | 83.88 | 0.00 | 0.00 | 0.00 |
May | 156.43 | 59.37 | 97.06 | 256.54 | 48.47 | 0.00 | 0.00 | 0.00 |
June | 164.35 | 63.28 | 101.07 | 308.56 | 21.97 | 0.00 | 0.00 | 0.00 |
July | 154.70 | 57.22 | 97.48 | 305.73 | 10.64 | 0.00 | 0.00 | 0.00 |
August | 151.95 | 56.83 | 95.12 | 303.85 | 5.06 | 0.00 | 0.00 | 0.00 |
September | 124.13 | 51.89 | 72.24 | 214.46 | 32.82 | 0.00 | 0.00 | 0.00 |
October | 110.45 | 57.43 | 53.02 | 158.99 | 96.01 | 0.67 | 0.00 | 0.00 |
November | 87.72 | 39.23 | 48.49 | 106.13 | 140.15 | 0.00 | 0.00 | 0.00 |
December | 72.66 | 31.83 | 40.83 | 67.56 | 188.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.48 | 53.12 | 71.36 | 192.14 | 96.08 | 2.00 | 0.00 | 0.00 |
Minimum of Months | 72.66 | 31.83 | 40.83 | 67.56 | 5.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 164.35 | 71.11 | 101.07 | 308.56 | 232.70 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 150.98 | 104.88 | 46.10 | 167.51 | 172.10 | 0.00 | 0.00 | 0.00 |
February | 140.64 | 93.83 | 46.81 | 171.16 | 141.31 | 0.00 | 0.00 | 0.00 |
March | 128.61 | 67.49 | 61.12 | 176.34 | 85.38 | 0.00 | 0.00 | 0.00 |
April | 96.79 | 32.29 | 64.50 | 152.02 | 63.94 | 0.00 | 0.00 | 0.00 |
May | 77.80 | 9.52 | 68.28 | 135.31 | 34.15 | 0.00 | 0.00 | 0.00 |
June | 71.44 | 3.99 | 67.45 | 153.09 | 14.80 | 0.00 | 0.00 | 0.00 |
July | 71.66 | 4.83 | 66.83 | 163.64 | 6.56 | 0.00 | 0.00 | 0.00 |
August | 86.35 | 16.23 | 70.12 | 195.44 | 2.99 | 0.00 | 0.00 | 0.00 |
September | 97.49 | 37.93 | 59.55 | 179.17 | 23.44 | 0.00 | 0.00 | 0.00 |
October | 136.89 | 88.48 | 48.41 | 207.52 | 73.31 | 0.00 | 0.00 | 0.00 |
November | 149.56 | 99.80 | 49.76 | 200.50 | 106.80 | 0.00 | 0.00 | 0.00 |
December | 149.92 | 105.46 | 44.46 | 179.58 | 141.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 113.05 | 55.21 | 57.84 | 173.48 | 71.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.44 | 3.99 | 44.46 | 135.31 | 2.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.98 | 105.46 | 70.12 | 207.52 | 172.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.72 | 0.00 | 135.72 | 15.91 | 1070.44 | 0.00 | 0.00 | 0.00 |
February | 150.43 | 0.00 | 150.43 | 63.48 | 863.24 | 0.00 | 0.00 | 0.00 |
March | 211.25 | 0.00 | 211.25 | 156.52 | 501.31 | 0.00 | 0.00 | 0.00 |
April | 256.14 | 1.50 | 254.65 | 314.55 | 367.87 | 0.00 | 0.00 | 0.00 |
May | 305.61 | 9.59 | 296.03 | 481.88 | 216.10 | 0.00 | 0.00 | 0.00 |
June | 336.12 | 22.04 | 314.08 | 683.96 | 116.84 | 0.00 | 0.00 | 0.00 |
July | 318.33 | 16.31 | 302.02 | 693.90 | 73.26 | 0.00 | 0.00 | 0.00 |
August | 282.74 | 3.32 | 279.41 | 636.75 | 53.04 | 0.00 | 0.00 | 0.00 |
September | 213.42 | 0.08 | 213.34 | 373.68 | 170.69 | 0.00 | 0.00 | 0.00 |
October | 162.16 | 0.00 | 162.16 | 164.76 | 439.91 | 0.00 | 0.00 | 0.00 |
November | 145.13 | 0.00 | 145.13 | 80.50 | 634.46 | 0.00 | 0.00 | 0.00 |
December | 125.46 | 0.00 | 125.46 | 18.07 | 865.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 220.59 | 4.42 | 216.17 | 308.38 | 445.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 125.46 | 0.00 | 125.46 | 15.91 | 53.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.12 | 22.04 | 314.08 | 693.90 | 1070.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.72 | 0.00 | 135.72 | 14.01 | 1107.57 | 0.00 | 0.00 | 0.00 |
February | 150.43 | 0.00 | 150.43 | 58.69 | 897.17 | 0.00 | 0.00 | 0.00 |
March | 211.25 | 0.00 | 211.25 | 146.01 | 525.14 | 0.00 | 0.00 | 0.00 |
April | 256.14 | 1.50 | 254.65 | 301.76 | 384.19 | 0.00 | 0.00 | 0.00 |
May | 305.61 | 9.59 | 296.03 | 467.37 | 227.59 | 0.00 | 0.00 | 0.00 |
June | 336.12 | 22.04 | 314.08 | 667.35 | 125.13 | 0.00 | 0.00 | 0.00 |
July | 318.33 | 16.31 | 302.02 | 676.97 | 80.25 | 0.00 | 0.00 | 0.00 |
August | 282.74 | 3.32 | 279.41 | 620.26 | 60.10 | 0.00 | 0.00 | 0.00 |
September | 213.42 | 0.08 | 213.34 | 360.75 | 182.88 | 0.00 | 0.00 | 0.00 |
October | 162.16 | 0.00 | 162.16 | 155.90 | 461.13 | 0.00 | 0.00 | 0.00 |
November | 145.13 | 0.00 | 145.13 | 72.67 | 663.29 | 0.00 | 0.00 | 0.00 |
December | 125.46 | 0.00 | 125.46 | 15.11 | 903.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 220.59 | 4.42 | 216.17 | 297.76 | 466.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 125.46 | 0.00 | 125.46 | 14.01 | 60.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.12 | 22.04 | 314.08 | 676.97 | 1107.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.39 | 0.00 | 19.39 | 2.88 | 155.58 | 0.00 | 0.00 | 0.00 |
February | 21.49 | 0.00 | 21.49 | 10.83 | 125.99 | 0.00 | 0.00 | 0.00 |
March | 30.18 | 0.00 | 30.18 | 27.79 | 73.42 | 0.00 | 0.00 | 0.00 |
April | 36.59 | 0.21 | 36.38 | 54.68 | 53.87 | 0.00 | 0.00 | 0.00 |
May | 43.66 | 1.37 | 42.29 | 82.75 | 32.99 | 0.00 | 0.00 | 0.00 |
June | 48.02 | 3.15 | 44.87 | 114.12 | 19.37 | 0.00 | 0.00 | 0.00 |
July | 45.48 | 2.33 | 43.15 | 117.02 | 12.86 | 0.00 | 0.00 | 0.00 |
August | 40.39 | 0.47 | 39.92 | 108.63 | 9.86 | 0.00 | 0.00 | 0.00 |
September | 30.49 | 0.01 | 30.48 | 66.18 | 25.07 | 0.00 | 0.00 | 0.00 |
October | 23.17 | 0.00 | 23.17 | 30.00 | 63.25 | 0.00 | 0.00 | 0.00 |
November | 20.73 | 0.00 | 20.73 | 15.31 | 91.59 | 0.00 | 0.00 | 0.00 |
December | 17.92 | 0.00 | 17.92 | 3.55 | 125.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.51 | 0.63 | 30.88 | 53.05 | 65.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.92 | 0.00 | 17.92 | 2.88 | 9.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.02 | 3.15 | 44.87 | 117.02 | 155.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.20 | 72.94 | 87.26 | 112.12 | 525.29 | 0.00 | 0.00 | 0.00 |
February | 201.06 | 108.23 | 92.83 | 204.49 | 424.44 | 0.00 | 0.00 | 0.00 |
March | 252.96 | 115.39 | 137.58 | 326.71 | 252.49 | 0.00 | 0.00 | 0.00 |
April | 305.79 | 139.57 | 166.21 | 489.47 | 190.65 | 0.00 | 0.00 | 0.00 |
May | 334.98 | 141.66 | 193.32 | 605.71 | 122.10 | 0.00 | 0.00 | 0.00 |
June | 346.48 | 145.12 | 201.36 | 714.57 | 72.23 | 0.00 | 0.00 | 0.00 |
July | 337.71 | 141.68 | 196.02 | 727.10 | 48.38 | 0.00 | 0.00 | 0.00 |
August | 309.52 | 122.78 | 186.75 | 684.01 | 37.11 | 0.00 | 0.00 | 0.00 |
September | 253.68 | 112.09 | 141.59 | 492.30 | 92.26 | 0.00 | 0.00 | 0.00 |
October | 216.97 | 112.93 | 104.03 | 328.19 | 221.92 | 0.00 | 0.00 | 0.00 |
November | 172.80 | 77.95 | 94.85 | 196.32 | 309.85 | 0.00 | 0.00 | 0.00 |
December | 149.95 | 68.26 | 81.69 | 115.09 | 421.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 253.76 | 113.20 | 140.56 | 417.46 | 225.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 149.95 | 68.26 | 81.69 | 112.12 | 37.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 346.48 | 145.12 | 201.36 | 727.10 | 525.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.95 | 71.51 | 31.43 | 120.54 | 128.59 | 0.00 | 0.00 | 0.00 |
February | 95.90 | 63.98 | 31.92 | 123.36 | 108.01 | 0.00 | 0.00 | 0.00 |
March | 87.69 | 46.02 | 41.68 | 129.80 | 69.23 | 0.00 | 0.00 | 0.00 |
April | 65.99 | 22.02 | 43.98 | 114.76 | 54.23 | 0.00 | 0.00 | 0.00 |
May | 53.05 | 6.49 | 46.56 | 105.15 | 34.05 | 0.00 | 0.00 | 0.00 |
June | 48.71 | 2.72 | 45.99 | 117.60 | 20.09 | 0.00 | 0.00 | 0.00 |
July | 48.86 | 3.30 | 45.57 | 125.05 | 12.99 | 0.00 | 0.00 | 0.00 |
August | 58.88 | 11.07 | 47.81 | 147.34 | 9.87 | 0.00 | 0.00 | 0.00 |
September | 66.47 | 25.86 | 40.61 | 136.11 | 24.81 | 0.00 | 0.00 | 0.00 |
October | 93.34 | 60.33 | 33.01 | 152.99 | 59.67 | 0.00 | 0.00 | 0.00 |
November | 101.97 | 68.05 | 33.93 | 146.88 | 81.65 | 0.00 | 0.00 | 0.00 |
December | 102.22 | 71.91 | 30.31 | 129.68 | 106.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.09 | 37.64 | 39.44 | 129.16 | 58.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.71 | 2.72 | 30.31 | 105.15 | 9.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.95 | 71.91 | 47.81 | 152.99 | 128.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.56 | 0.00 | 24.56 | 2.92 | 187.81 | 0.00 | 0.00 | 0.00 |
February | 27.22 | 0.00 | 27.22 | 10.65 | 152.01 | 0.00 | 0.00 | 0.00 |
March | 38.22 | 0.00 | 38.22 | 25.22 | 91.35 | 0.00 | 0.00 | 0.00 |
April | 46.34 | 0.27 | 46.07 | 51.07 | 69.46 | 0.00 | 0.00 | 0.00 |
May | 55.29 | 1.73 | 53.56 | 79.15 | 42.16 | 0.00 | 0.00 | 0.00 |
June | 60.81 | 3.99 | 56.83 | 115.00 | 22.85 | 0.00 | 0.00 | 0.00 |
July | 57.59 | 2.95 | 54.64 | 116.62 | 14.76 | 0.00 | 0.00 | 0.00 |
August | 51.15 | 0.60 | 50.55 | 106.00 | 11.07 | 0.00 | 0.00 | 0.00 |
September | 38.61 | 0.02 | 38.60 | 59.76 | 34.72 | 0.00 | 0.00 | 0.00 |
October | 29.34 | 0.00 | 29.34 | 25.09 | 83.10 | 0.00 | 0.00 | 0.00 |
November | 26.26 | 0.00 | 26.26 | 12.76 | 114.14 | 0.00 | 0.00 | 0.00 |
December | 22.70 | 0.00 | 22.70 | 3.06 | 151.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.91 | 0.80 | 39.11 | 50.84 | 80.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.70 | 0.00 | 22.70 | 2.92 | 11.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.81 | 3.99 | 56.83 | 116.62 | 187.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.97 | 0.00 | 21.97 | 2.61 | 168.03 | 0.00 | 0.00 | 0.00 |
February | 24.35 | 0.00 | 24.35 | 9.52 | 136.00 | 0.00 | 0.00 | 0.00 |
March | 34.20 | 0.00 | 34.20 | 22.57 | 81.73 | 0.00 | 0.00 | 0.00 |
April | 41.46 | 0.24 | 41.22 | 45.69 | 62.15 | 0.00 | 0.00 | 0.00 |
May | 49.47 | 1.55 | 47.92 | 70.81 | 37.72 | 0.00 | 0.00 | 0.00 |
June | 54.41 | 3.57 | 50.84 | 102.89 | 20.44 | 0.00 | 0.00 | 0.00 |
July | 51.53 | 2.64 | 48.89 | 104.34 | 13.20 | 0.00 | 0.00 | 0.00 |
August | 45.77 | 0.54 | 45.23 | 94.84 | 9.90 | 0.00 | 0.00 | 0.00 |
September | 34.55 | 0.01 | 34.53 | 53.46 | 31.07 | 0.00 | 0.00 | 0.00 |
October | 26.25 | 0.00 | 26.25 | 22.44 | 74.35 | 0.00 | 0.00 | 0.00 |
November | 23.49 | 0.00 | 23.49 | 11.42 | 102.12 | 0.00 | 0.00 | 0.00 |
December | 20.31 | 0.00 | 20.31 | 2.74 | 135.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.71 | 0.72 | 34.99 | 45.48 | 72.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.31 | 0.00 | 20.31 | 2.61 | 9.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.41 | 3.57 | 50.84 | 104.34 | 168.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 384.33 | 266.99 | 117.35 | 434.90 | 450.75 | 0.00 | 0.00 | 0.00 |
February | 358.01 | 238.84 | 119.17 | 440.11 | 380.02 | 0.00 | 0.00 | 0.00 |
March | 327.38 | 171.79 | 155.59 | 443.52 | 250.85 | 0.00 | 0.00 | 0.00 |
April | 246.38 | 82.20 | 164.18 | 370.75 | 206.54 | 0.00 | 0.00 | 0.00 |
May | 198.05 | 24.24 | 173.81 | 318.00 | 131.99 | 0.00 | 0.00 | 0.00 |
June | 181.85 | 10.15 | 171.69 | 353.45 | 72.97 | 0.00 | 0.00 | 0.00 |
July | 182.41 | 12.30 | 170.11 | 375.78 | 45.82 | 0.00 | 0.00 | 0.00 |
August | 219.80 | 41.31 | 178.49 | 456.54 | 33.55 | 0.00 | 0.00 | 0.00 |
September | 248.15 | 96.55 | 151.60 | 431.66 | 101.56 | 0.00 | 0.00 | 0.00 |
October | 348.45 | 225.22 | 123.23 | 518.86 | 227.52 | 0.00 | 0.00 | 0.00 |
November | 380.70 | 254.04 | 126.66 | 513.38 | 295.54 | 0.00 | 0.00 | 0.00 |
December | 381.63 | 268.46 | 113.17 | 465.30 | 372.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 287.78 | 140.54 | 147.25 | 426.85 | 213.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 181.85 | 10.15 | 113.17 | 318.00 | 33.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 384.33 | 268.46 | 178.49 | 518.86 | 450.75 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139459E+10 | 0.968782E+09 | 0.425804E+09 | 0.160295E+10 | 0.151169E+10 |
February | 0.117336E+10 | 0.782797E+09 | 0.390560E+09 | 0.146742E+10 | 0.114217E+10 |
March | 0.118792E+10 | 0.623368E+09 | 0.564555E+09 | 0.164599E+10 | 0.836067E+09 |
April | 0.865158E+09 | 0.288646E+09 | 0.576512E+09 | 0.134267E+10 | 0.648085E+09 |
May | 0.718628E+09 | 87942952.17 | 0.630685E+09 | 0.118543E+10 | 0.427947E+09 |
June | 0.638554E+09 | 35650458.33 | 0.602904E+09 | 0.122890E+10 | 0.250589E+09 |
July | 0.661899E+09 | 44646457.89 | 0.617253E+09 | 0.134203E+10 | 0.166973E+09 |
August | 0.797559E+09 | 0.149894E+09 | 0.647665E+09 | 0.162696E+10 | 0.135759E+09 |
September | 0.871397E+09 | 0.339052E+09 | 0.532345E+09 | 0.152142E+10 | 0.337002E+09 |
October | 0.126439E+10 | 0.817230E+09 | 0.447163E+09 | 0.190375E+10 | 0.759829E+09 |
November | 0.133685E+10 | 0.892082E+09 | 0.444765E+09 | 0.181122E+10 | 0.976395E+09 |
December | 0.138477E+10 | 0.974137E+09 | 0.410633E+09 | 0.170486E+10 | 0.126505E+10 |
Annual Sum or Average | 0.122951E+11 | 0.600423E+10 | 0.629084E+10 | 0.183836E+11 | 0.845755E+10 |
Minimum of Months | 0.638554E+09 | 35650458.33 | 0.390560E+09 | 0.118543E+10 | 0.135759E+09 |
Maximum of Months | 0.139459E+10 | 0.974137E+09 | 0.647665E+09 | 0.190375E+10 | 0.151169E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.392706E+10 | 0.272803E+10 | 0.119904E+10 | 0.450903E+10 | 0.433016E+10 |
February | 0.330410E+10 | 0.220430E+10 | 0.109979E+10 | 0.414220E+10 | 0.326903E+10 |
March | 0.334511E+10 | 0.175536E+10 | 0.158975E+10 | 0.470942E+10 | 0.232575E+10 |
April | 0.243623E+10 | 0.812809E+09 | 0.162342E+10 | 0.390364E+10 | 0.174593E+10 |
May | 0.202361E+10 | 0.247642E+09 | 0.177597E+10 | 0.354577E+10 | 0.108683E+10 |
June | 0.179813E+10 | 0.100389E+09 | 0.169774E+10 | 0.372946E+10 | 0.594004E+09 |
July | 0.186386E+10 | 0.125721E+09 | 0.173814E+10 | 0.405673E+10 | 0.374560E+09 |
August | 0.224587E+10 | 0.422090E+09 | 0.182378E+10 | 0.483084E+10 | 0.292600E+09 |
September | 0.245380E+10 | 0.954749E+09 | 0.149905E+10 | 0.445619E+10 | 0.836596E+09 |
October | 0.356045E+10 | 0.230127E+10 | 0.125918E+10 | 0.544648E+10 | 0.208276E+10 |
November | 0.376447E+10 | 0.251204E+10 | 0.125243E+10 | 0.513732E+10 | 0.274871E+10 |
December | 0.389942E+10 | 0.274311E+10 | 0.115631E+10 | 0.480524E+10 | 0.362325E+10 |
Annual Sum or Average | 0.346221E+11 | 0.169075E+11 | 0.177146E+11 | 0.532723E+11 | 0.233102E+11 |
Minimum of Months | 0.179813E+10 | 0.100389E+09 | 0.109979E+10 | 0.354577E+10 | 0.292600E+09 |
Maximum of Months | 0.392706E+10 | 0.274311E+10 | 0.182378E+10 | 0.544648E+10 | 0.433016E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.510148E+10 | 0.354386E+10 | 0.155762E+10 | 0.592757E+10 | 0.595064E+10 |
February | 0.429221E+10 | 0.286352E+10 | 0.142869E+10 | 0.544846E+10 | 0.450856E+10 |
March | 0.434549E+10 | 0.228032E+10 | 0.206517E+10 | 0.617106E+10 | 0.325045E+10 |
April | 0.316480E+10 | 0.105589E+10 | 0.210891E+10 | 0.508437E+10 | 0.247867E+10 |
May | 0.262878E+10 | 0.321700E+09 | 0.230708E+10 | 0.457409E+10 | 0.158687E+10 |
June | 0.233587E+10 | 0.130411E+09 | 0.220546E+10 | 0.479268E+10 | 0.888729E+09 |
July | 0.242127E+10 | 0.163319E+09 | 0.225795E+10 | 0.522346E+10 | 0.576996E+09 |
August | 0.291752E+10 | 0.548319E+09 | 0.236920E+10 | 0.627842E+10 | 0.445134E+09 |
September | 0.318762E+10 | 0.124027E+10 | 0.194735E+10 | 0.579122E+10 | 0.123293E+10 |
October | 0.462523E+10 | 0.298948E+10 | 0.163575E+10 | 0.713987E+10 | 0.293556E+10 |
November | 0.489026E+10 | 0.326329E+10 | 0.162698E+10 | 0.672902E+10 | 0.383841E+10 |
December | 0.506557E+10 | 0.356345E+10 | 0.150212E+10 | 0.630363E+10 | 0.502535E+10 |
Annual Sum or Average | 0.449761E+11 | 0.219638E+11 | 0.230123E+11 | 0.694639E+11 | 0.327183E+11 |
Minimum of Months | 0.233587E+10 | 0.130411E+09 | 0.142869E+10 | 0.457409E+10 | 0.445134E+09 |
Maximum of Months | 0.510148E+10 | 0.356345E+10 | 0.236920E+10 | 0.713987E+10 | 0.595064E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275734E+09 | 0.191545E+09 | 84189446.79 | 0.320758E+09 | 0.302776E+09 |
February | 0.231994E+09 | 0.154772E+09 | 77221105.23 | 0.293429E+09 | 0.225081E+09 |
March | 0.234874E+09 | 0.123251E+09 | 0.111623E+09 | 0.329621E+09 | 0.154556E+09 |
April | 0.171058E+09 | 57070367.83 | 0.113987E+09 | 0.271065E+09 | 0.115287E+09 |
May | 0.142086E+09 | 17387832.05 | 0.124699E+09 | 0.245895E+09 | 65682253.96 |
June | 0.126255E+09 | 7048707.90 | 0.119206E+09 | 0.265645E+09 | 29473617.00 |
July | 0.130870E+09 | 8827371.52 | 0.122043E+09 | 0.293133E+09 | 14477063.07 |
August | 0.157692E+09 | 29636534.88 | 0.128056E+09 | 0.352035E+09 | 7243833.14 |
September | 0.172291E+09 | 67036435.04 | 0.105255E+09 | 0.317093E+09 | 43791402.51 |
October | 0.249993E+09 | 0.161580E+09 | 88412715.82 | 0.385886E+09 | 0.132427E+09 |
November | 0.264318E+09 | 0.176380E+09 | 87938230.82 | 0.365146E+09 | 0.182740E+09 |
December | 0.273793E+09 | 0.192604E+09 | 81189647.76 | 0.342328E+09 | 0.247792E+09 |
Annual Sum or Average | 0.243096E+10 | 0.118714E+10 | 0.124382E+10 | 0.378203E+10 | 0.152133E+10 |
Minimum of Months | 0.126255E+09 | 7048707.90 | 77221105.23 | 0.245895E+09 | 7243833.14 |
Maximum of Months | 0.275734E+09 | 0.192604E+09 | 0.128056E+09 | 0.385886E+09 | 0.302776E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219849E+09 | 0.102224E+09 | 0.117625E+09 | 0.173038E+09 | 0.637897E+09 |
February | 0.227500E+09 | 0.106626E+09 | 0.120874E+09 | 0.235168E+09 | 0.466448E+09 |
March | 0.369530E+09 | 0.178222E+09 | 0.191308E+09 | 0.475853E+09 | 0.298981E+09 |
April | 0.402975E+09 | 0.184312E+09 | 0.218663E+09 | 0.605452E+09 | 0.212221E+09 |
May | 0.418984E+09 | 0.159021E+09 | 0.259962E+09 | 0.701244E+09 | 0.121642E+09 |
June | 0.425988E+09 | 0.164024E+09 | 0.261964E+09 | 0.813307E+09 | 54711197.94 |
July | 0.414335E+09 | 0.153256E+09 | 0.261080E+09 | 0.831241E+09 | 26815347.71 |
August | 0.406982E+09 | 0.152218E+09 | 0.254764E+09 | 0.822118E+09 | 13501067.73 |
September | 0.321755E+09 | 0.134509E+09 | 0.187246E+09 | 0.560833E+09 | 82062974.38 |
October | 0.295829E+09 | 0.153811E+09 | 0.142018E+09 | 0.422488E+09 | 0.260697E+09 |
November | 0.227376E+09 | 0.101680E+09 | 0.125697E+09 | 0.264410E+09 | 0.375940E+09 |
December | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.168448E+09 | 0.522243E+09 |
Annual Sum or Average | 0.392571E+10 | 0.167515E+10 | 0.225056E+10 | 0.607360E+10 | 0.307316E+10 |
Minimum of Months | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.168448E+09 | 13501067.73 |
Maximum of Months | 0.425988E+09 | 0.184312E+09 | 0.261964E+09 | 0.831241E+09 | 0.637897E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51932557.31 | 0.00 | 51932557.31 | 8224546.18 | 0.359767E+09 |
February | 51991662.66 | 0.00 | 51991662.66 | 25053408.02 | 0.259835E+09 |
March | 80833881.57 | 1627.95 | 80832253.62 | 63466106.39 | 0.165388E+09 |
April | 94850140.82 | 553965.08 | 94296175.74 | 0.116382E+09 | 0.117841E+09 |
May | 0.116941E+09 | 3667679.90 | 0.113274E+09 | 0.182833E+09 | 66631359.54 |
June | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.253103E+09 | 29476957.71 |
July | 0.121807E+09 | 6241532.89 | 0.115565E+09 | 0.267066E+09 | 15787471.48 |
August | 0.108187E+09 | 1270984.59 | 0.106916E+09 | 0.246191E+09 | 8040555.59 |
September | 79030084.51 | 31067.06 | 78999017.45 | 0.137210E+09 | 47586199.84 |
October | 62049703.82 | 0.00 | 62049703.82 | 64681773.11 | 0.143190E+09 |
November | 53740831.96 | 0.00 | 53740831.96 | 34499460.28 | 0.202746E+09 |
December | 48007784.18 | 0.00 | 48007784.18 | 10827330.19 | 0.285911E+09 |
Annual Sum or Average | 0.993838E+09 | 19929300.33 | 0.973909E+09 | 0.140954E+10 | 0.170220E+10 |
Minimum of Months | 48007784.18 | 0.00 | 48007784.18 | 8224546.18 | 8040555.59 |
Maximum of Months | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.267066E+09 | 0.359767E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219849E+09 | 0.102224E+09 | 0.117625E+09 | 0.182791E+09 | 0.626493E+09 |
February | 0.227500E+09 | 0.106626E+09 | 0.120874E+09 | 0.243239E+09 | 0.459406E+09 |
March | 0.369530E+09 | 0.178222E+09 | 0.191308E+09 | 0.482088E+09 | 0.297789E+09 |
April | 0.402975E+09 | 0.184312E+09 | 0.218663E+09 | 0.604838E+09 | 0.218535E+09 |
May | 0.418984E+09 | 0.159021E+09 | 0.259962E+09 | 0.694982E+09 | 0.130635E+09 |
June | 0.425988E+09 | 0.164024E+09 | 0.261964E+09 | 0.806233E+09 | 59031442.11 |
July | 0.414335E+09 | 0.153256E+09 | 0.261080E+09 | 0.824261E+09 | 30366082.92 |
August | 0.406982E+09 | 0.152218E+09 | 0.254764E+09 | 0.818795E+09 | 15211236.08 |
September | 0.321755E+09 | 0.134509E+09 | 0.187246E+09 | 0.559576E+09 | 88099810.00 |
October | 0.295829E+09 | 0.153811E+09 | 0.142018E+09 | 0.428174E+09 | 0.261927E+09 |
November | 0.227376E+09 | 0.101680E+09 | 0.125697E+09 | 0.275227E+09 | 0.368741E+09 |
December | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.179762E+09 | 0.510692E+09 |
Annual Sum or Average | 0.392571E+10 | 0.167515E+10 | 0.225056E+10 | 0.609997E+10 | 0.306693E+10 |
Minimum of Months | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.179762E+09 | 15211236.08 |
Maximum of Months | 0.425988E+09 | 0.184312E+09 | 0.261964E+09 | 0.824261E+09 | 0.626493E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.220544E+09 | 0.153205E+09 | 67338165.69 | 0.243041E+09 | 0.263858E+09 |
February | 0.185558E+09 | 0.123793E+09 | 61764600.87 | 0.214470E+09 | 0.225322E+09 |
March | 0.187862E+09 | 98580876.18 | 89280789.68 | 0.229449E+09 | 0.189496E+09 |
April | 0.136819E+09 | 45647216.27 | 91171836.45 | 0.183877E+09 | 0.149740E+09 |
May | 0.113647E+09 | 13907499.81 | 99739018.35 | 0.160095E+09 | 0.104026E+09 |
June | 0.100984E+09 | 5637845.11 | 95345682.42 | 0.170998E+09 | 63305668.81 |
July | 0.104675E+09 | 7060493.07 | 97614864.41 | 0.188500E+09 | 48037956.87 |
August | 0.126129E+09 | 23704513.72 | 0.102424E+09 | 0.234566E+09 | 41593922.25 |
September | 0.137805E+09 | 53618484.76 | 84186968.45 | 0.218356E+09 | 85306955.11 |
October | 0.199955E+09 | 0.129239E+09 | 70716109.13 | 0.276092E+09 | 0.172093E+09 |
November | 0.211412E+09 | 0.141076E+09 | 70336596.60 | 0.258565E+09 | 0.216579E+09 |
December | 0.218991E+09 | 0.154052E+09 | 64938803.63 | 0.244286E+09 | 0.264204E+09 |
Annual Sum or Average | 0.194438E+10 | 0.949522E+09 | 0.994858E+09 | 0.262230E+10 | 0.182356E+10 |
Minimum of Months | 0.100984E+09 | 5637845.11 | 61764600.87 | 0.160095E+09 | 41593922.25 |
Maximum of Months | 0.220544E+09 | 0.154052E+09 | 0.102424E+09 | 0.276092E+09 | 0.264204E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41551553.01 | 0.00 | 41551553.01 | 5905196.66 | 0.301417E+09 |
February | 41598843.56 | 0.00 | 41598843.56 | 19988764.84 | 0.216248E+09 |
March | 64675677.25 | 1302.53 | 64674374.72 | 53679300.75 | 0.131860E+09 |
April | 75890171.00 | 443230.81 | 75446940.19 | 98700911.65 | 91730140.26 |
May | 93565486.34 | 2934532.86 | 90630953.48 | 0.154045E+09 | 50189374.79 |
June | 99586189.44 | 6530819.87 | 93055369.57 | 0.212694E+09 | 20481898.75 |
July | 97458282.54 | 4993888.19 | 92464394.35 | 0.225128E+09 | 10235517.43 |
August | 86561042.70 | 1016922.46 | 85544120.25 | 0.209794E+09 | 4381074.59 |
September | 63232448.32 | 24856.94 | 63207591.38 | 0.116880E+09 | 35227721.49 |
October | 49646343.09 | 0.00 | 49646343.09 | 54965019.54 | 0.114124E+09 |
November | 42998364.49 | 0.00 | 42998364.49 | 27690305.22 | 0.166777E+09 |
December | 38411318.30 | 0.00 | 38411318.30 | 7491892.91 | 0.239859E+09 |
Annual Sum or Average | 0.795176E+09 | 15945553.66 | 0.779230E+09 | 0.118696E+10 | 0.138253E+10 |
Minimum of Months | 38411318.30 | 0.00 | 38411318.30 | 5905196.66 | 4381074.59 |
Maximum of Months | 99586189.44 | 6530819.87 | 93055369.57 | 0.225128E+09 | 0.301417E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214559E+09 | 97692218.39 | 0.116866E+09 | 0.147423E+09 | 0.619724E+09 |
February | 0.243222E+09 | 0.130930E+09 | 0.112292E+09 | 0.236257E+09 | 0.441157E+09 |
March | 0.338793E+09 | 0.154540E+09 | 0.184254E+09 | 0.402369E+09 | 0.277657E+09 |
April | 0.396326E+09 | 0.180898E+09 | 0.215428E+09 | 0.577927E+09 | 0.195716E+09 |
May | 0.448639E+09 | 0.189725E+09 | 0.258913E+09 | 0.739519E+09 | 0.112268E+09 |
June | 0.449066E+09 | 0.188091E+09 | 0.260975E+09 | 0.848090E+09 | 49838664.10 |
July | 0.452288E+09 | 0.189756E+09 | 0.262532E+09 | 0.892828E+09 | 25823820.01 |
August | 0.414545E+09 | 0.164438E+09 | 0.250107E+09 | 0.836306E+09 | 12707677.72 |
September | 0.328787E+09 | 0.145278E+09 | 0.183509E+09 | 0.570111E+09 | 78059542.21 |
October | 0.290585E+09 | 0.151252E+09 | 0.139332E+09 | 0.395116E+09 | 0.243382E+09 |
November | 0.223962E+09 | 0.101027E+09 | 0.122935E+09 | 0.230206E+09 | 0.347133E+09 |
December | 0.200830E+09 | 91417601.72 | 0.109412E+09 | 0.149008E+09 | 0.491772E+09 |
Annual Sum or Average | 0.400160E+10 | 0.178505E+10 | 0.221656E+10 | 0.602516E+10 | 0.289524E+10 |
Minimum of Months | 0.200830E+09 | 91417601.72 | 0.109412E+09 | 0.147423E+09 | 12707677.72 |
Maximum of Months | 0.452288E+09 | 0.189756E+09 | 0.262532E+09 | 0.892828E+09 | 0.619724E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275734E+09 | 0.191545E+09 | 84189446.79 | 0.319161E+09 | 0.302018E+09 |
February | 0.231994E+09 | 0.154772E+09 | 77221105.23 | 0.291047E+09 | 0.224566E+09 |
March | 0.234874E+09 | 0.123251E+09 | 0.111623E+09 | 0.327351E+09 | 0.153179E+09 |
April | 0.171058E+09 | 57070367.83 | 0.113987E+09 | 0.268770E+09 | 0.114539E+09 |
May | 0.142086E+09 | 17387832.05 | 0.124699E+09 | 0.243600E+09 | 65270098.05 |
June | 0.126255E+09 | 7048707.90 | 0.119206E+09 | 0.263758E+09 | 29082081.26 |
July | 0.130870E+09 | 8827371.52 | 0.122043E+09 | 0.291431E+09 | 14273067.01 |
August | 0.157692E+09 | 29636534.88 | 0.128056E+09 | 0.351239E+09 | 6989398.69 |
September | 0.172291E+09 | 67036435.04 | 0.105255E+09 | 0.315934E+09 | 43324327.90 |
October | 0.249993E+09 | 0.161580E+09 | 88412715.82 | 0.383977E+09 | 0.131507E+09 |
November | 0.264318E+09 | 0.176380E+09 | 87938230.82 | 0.363514E+09 | 0.181931E+09 |
December | 0.273793E+09 | 0.192604E+09 | 81189647.76 | 0.340680E+09 | 0.247284E+09 |
Annual Sum or Average | 0.243096E+10 | 0.118714E+10 | 0.124382E+10 | 0.376046E+10 | 0.151396E+10 |
Minimum of Months | 0.126255E+09 | 7048707.90 | 77221105.23 | 0.243600E+09 | 6989398.69 |
Maximum of Months | 0.275734E+09 | 0.192604E+09 | 0.128056E+09 | 0.383977E+09 | 0.302018E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51932557.31 | 0.00 | 51932557.31 | 7813664.59 | 0.359903E+09 |
February | 51991662.66 | 0.00 | 51991662.66 | 24007159.43 | 0.260172E+09 |
March | 80833881.57 | 1627.95 | 80832253.62 | 62258846.64 | 0.163495E+09 |
April | 94850140.82 | 553965.08 | 94296175.74 | 0.114213E+09 | 0.116300E+09 |
May | 0.116941E+09 | 3667679.90 | 0.113274E+09 | 0.179836E+09 | 65628168.69 |
June | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.249774E+09 | 28920519.26 |
July | 0.121807E+09 | 6241532.89 | 0.115565E+09 | 0.263953E+09 | 15708563.11 |
August | 0.108187E+09 | 1270984.59 | 0.106916E+09 | 0.244556E+09 | 7756430.79 |
September | 79030084.51 | 31067.06 | 78999017.45 | 0.135211E+09 | 47000272.92 |
October | 62049703.82 | 0.00 | 62049703.82 | 62854029.78 | 0.141657E+09 |
November | 53740831.96 | 0.00 | 53740831.96 | 33854228.05 | 0.201369E+09 |
December | 48007784.18 | 0.00 | 48007784.18 | 10318651.80 | 0.286067E+09 |
Annual Sum or Average | 0.993838E+09 | 19929300.33 | 0.973909E+09 | 0.138865E+10 | 0.169398E+10 |
Minimum of Months | 48007784.18 | 0.00 | 48007784.18 | 7813664.59 | 7756430.79 |
Maximum of Months | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.263953E+09 | 0.359903E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214559E+09 | 97692218.39 | 0.116866E+09 | 0.152931E+09 | 0.603539E+09 |
February | 0.243222E+09 | 0.130930E+09 | 0.112292E+09 | 0.243432E+09 | 0.432219E+09 |
March | 0.338793E+09 | 0.154540E+09 | 0.184254E+09 | 0.410199E+09 | 0.274712E+09 |
April | 0.396326E+09 | 0.180898E+09 | 0.215428E+09 | 0.578351E+09 | 0.200958E+09 |
May | 0.448639E+09 | 0.189725E+09 | 0.258913E+09 | 0.732006E+09 | 0.120263E+09 |
June | 0.449066E+09 | 0.188091E+09 | 0.260975E+09 | 0.837478E+09 | 53577776.10 |
July | 0.452288E+09 | 0.189756E+09 | 0.262532E+09 | 0.882136E+09 | 29221184.86 |
August | 0.414545E+09 | 0.164438E+09 | 0.250107E+09 | 0.830710E+09 | 14138546.90 |
September | 0.328787E+09 | 0.145278E+09 | 0.183509E+09 | 0.566633E+09 | 83430610.65 |
October | 0.290585E+09 | 0.151252E+09 | 0.139332E+09 | 0.401207E+09 | 0.243032E+09 |
November | 0.223962E+09 | 0.101027E+09 | 0.122935E+09 | 0.241528E+09 | 0.337455E+09 |
December | 0.200830E+09 | 91417601.72 | 0.109412E+09 | 0.157182E+09 | 0.476218E+09 |
Annual Sum or Average | 0.400160E+10 | 0.178505E+10 | 0.221656E+10 | 0.603379E+10 | 0.286876E+10 |
Minimum of Months | 0.200830E+09 | 91417601.72 | 0.109412E+09 | 0.152931E+09 | 14138546.90 |
Maximum of Months | 0.452288E+09 | 0.189756E+09 | 0.262532E+09 | 0.882136E+09 | 0.603539E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 65769307.07 | 0.00 | 65769307.07 | 9111050.54 | 0.491362E+09 |
February | 65844160.26 | 0.00 | 65844160.26 | 30949405.10 | 0.351204E+09 |
March | 0.102371E+09 | 2061.70 | 0.102369E+09 | 83856904.53 | 0.218016E+09 |
April | 0.120122E+09 | 701561.82 | 0.119420E+09 | 0.154779E+09 | 0.155838E+09 |
May | 0.148099E+09 | 4644885.18 | 0.143454E+09 | 0.241066E+09 | 91318338.25 |
June | 0.157629E+09 | 10337218.86 | 0.147291E+09 | 0.323044E+09 | 47264061.50 |
July | 0.154261E+09 | 7904507.59 | 0.146356E+09 | 0.335051E+09 | 30357043.98 |
August | 0.137012E+09 | 1609621.79 | 0.135402E+09 | 0.305485E+09 | 20737850.14 |
September | 0.100087E+09 | 39344.47 | 0.100047E+09 | 0.175194E+09 | 72140313.85 |
October | 78582034.76 | 0.00 | 78582034.76 | 83024198.21 | 0.194550E+09 |
November | 68059372.82 | 0.00 | 68059372.82 | 42894340.27 | 0.271709E+09 |
December | 60798829.53 | 0.00 | 60798829.53 | 10954851.46 | 0.389406E+09 |
Annual Sum or Average | 0.125863E+10 | 25239201.40 | 0.123339E+10 | 0.179541E+10 | 0.233390E+10 |
Minimum of Months | 60798829.53 | 0.00 | 60798829.53 | 9111050.54 | 20737850.14 |
Maximum of Months | 0.157629E+09 | 10337218.86 | 0.147291E+09 | 0.335051E+09 | 0.491362E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24245289.88 | 0.00 | 24245289.88 | 3358710.49 | 0.181136E+09 |
February | 24272883.86 | 0.00 | 24272883.86 | 11409232.23 | 0.129468E+09 |
March | 37738193.39 | 760.03 | 37737433.36 | 30913127.25 | 80369828.53 |
April | 44281839.34 | 258624.74 | 44023214.60 | 57058006.71 | 57448413.49 |
May | 54595368.27 | 1712297.01 | 52883071.26 | 88866963.42 | 33663720.67 |
June | 58108442.55 | 3810726.90 | 54297715.64 | 0.119087E+09 | 17423490.12 |
July | 56866810.98 | 2913928.80 | 53952882.19 | 0.123513E+09 | 11190863.40 |
August | 50508282.37 | 593373.24 | 49914909.13 | 0.112615E+09 | 7644830.25 |
September | 36896070.74 | 14504.00 | 36881566.74 | 64583906.06 | 26593906.78 |
October | 28968591.84 | 0.00 | 28968591.84 | 30606157.22 | 71719281.86 |
November | 25089502.94 | 0.00 | 25089502.94 | 15812629.94 | 0.100163E+09 |
December | 22412966.05 | 0.00 | 22412966.05 | 4038411.85 | 0.143551E+09 |
Annual Sum or Average | 0.463984E+09 | 9304214.71 | 0.454680E+09 | 0.661863E+09 | 0.860374E+09 |
Minimum of Months | 22412966.05 | 0.00 | 22412966.05 | 3358710.49 | 7644830.25 |
Maximum of Months | 58108442.55 | 3810726.90 | 54297715.64 | 0.123513E+09 | 0.181136E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128657E+09 | 89374067.16 | 39282456.62 | 0.148605E+09 | 0.148128E+09 |
February | 0.108247E+09 | 72216185.45 | 36031056.52 | 0.137180E+09 | 0.109803E+09 |
March | 0.109591E+09 | 57508234.04 | 52082926.70 | 0.156782E+09 | 75151466.39 |
April | 79814893.20 | 26628803.66 | 53186089.54 | 0.129194E+09 | 57982742.93 |
May | 66296941.32 | 8113092.37 | 58183848.95 | 0.116913E+09 | 35680017.86 |
June | 58909847.01 | 3288898.70 | 55620948.31 | 0.123309E+09 | 18780299.49 |
July | 61063516.46 | 4118815.98 | 56944700.48 | 0.133985E+09 | 11682125.41 |
August | 73578575.46 | 13828287.75 | 59750287.71 | 0.161007E+09 | 7779249.57 |
September | 80390320.73 | 31278930.45 | 49111390.28 | 0.148001E+09 | 26369448.08 |
October | 0.116646E+09 | 75392769.76 | 41253016.93 | 0.181861E+09 | 66945302.68 |
November | 0.123330E+09 | 82298153.11 | 41031624.14 | 0.172540E+09 | 88380559.98 |
December | 0.127751E+09 | 89868054.48 | 37882762.48 | 0.159671E+09 | 0.120434E+09 |
Annual Sum or Average | 0.113428E+10 | 0.553914E+09 | 0.580361E+09 | 0.176905E+10 | 0.767116E+09 |
Minimum of Months | 58909847.01 | 3288898.70 | 36031056.52 | 0.116913E+09 | 7779249.57 |
Maximum of Months | 0.128657E+09 | 89868054.48 | 59750287.71 | 0.181861E+09 | 0.148128E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.349200E+09 | 0.242579E+09 | 0.106621E+09 | 0.403346E+09 | 0.402050E+09 |
February | 0.293805E+09 | 0.196009E+09 | 97795657.39 | 0.372335E+09 | 0.298027E+09 |
March | 0.297453E+09 | 0.156089E+09 | 0.141364E+09 | 0.425538E+09 | 0.203976E+09 |
April | 0.216634E+09 | 72276019.92 | 0.144358E+09 | 0.350660E+09 | 0.157377E+09 |
May | 0.179943E+09 | 22020592.18 | 0.157923E+09 | 0.317325E+09 | 96842866.66 |
June | 0.159893E+09 | 8926743.81 | 0.150967E+09 | 0.334686E+09 | 50973574.23 |
July | 0.165739E+09 | 11179309.05 | 0.154560E+09 | 0.363663E+09 | 31707677.88 |
August | 0.199707E+09 | 37532801.47 | 0.162175E+09 | 0.437007E+09 | 21114472.15 |
September | 0.218196E+09 | 84897415.22 | 0.133298E+09 | 0.401705E+09 | 71572075.83 |
October | 0.316601E+09 | 0.204631E+09 | 0.111969E+09 | 0.493609E+09 | 0.181703E+09 |
November | 0.334742E+09 | 0.223374E+09 | 0.111368E+09 | 0.468310E+09 | 0.239883E+09 |
December | 0.346742E+09 | 0.243920E+09 | 0.102822E+09 | 0.433380E+09 | 0.326884E+09 |
Annual Sum or Average | 0.307866E+10 | 0.150344E+10 | 0.157522E+10 | 0.480156E+10 | 0.208211E+10 |
Minimum of Months | 0.159893E+09 | 8926743.81 | 97795657.39 | 0.317325E+09 | 21114472.15 |
Maximum of Months | 0.349200E+09 | 0.243920E+09 | 0.162175E+09 | 0.493609E+09 | 0.402050E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275734E+09 | 0.191545E+09 | 84189446.79 | 0.319912E+09 | 0.300873E+09 |
February | 0.231994E+09 | 0.154772E+09 | 77221105.23 | 0.292041E+09 | 0.223328E+09 |
March | 0.234874E+09 | 0.123251E+09 | 0.111623E+09 | 0.326884E+09 | 0.152731E+09 |
April | 0.171058E+09 | 57070367.83 | 0.113987E+09 | 0.268297E+09 | 0.113942E+09 |
May | 0.142086E+09 | 17387832.05 | 0.124699E+09 | 0.242907E+09 | 64604869.01 |
June | 0.126255E+09 | 7048707.90 | 0.119206E+09 | 0.263708E+09 | 28309771.64 |
July | 0.130870E+09 | 8827371.52 | 0.122043E+09 | 0.291240E+09 | 13473688.67 |
August | 0.157692E+09 | 29636534.88 | 0.128056E+09 | 0.349945E+09 | 6430369.79 |
September | 0.172291E+09 | 67036435.04 | 0.105255E+09 | 0.314969E+09 | 42234322.03 |
October | 0.249993E+09 | 0.161580E+09 | 88412715.82 | 0.383476E+09 | 0.130152E+09 |
November | 0.264318E+09 | 0.176380E+09 | 87938230.82 | 0.363558E+09 | 0.180536E+09 |
December | 0.273793E+09 | 0.192604E+09 | 81189647.76 | 0.341305E+09 | 0.245443E+09 |
Annual Sum or Average | 0.243096E+10 | 0.118714E+10 | 0.124382E+10 | 0.375824E+10 | 0.150206E+10 |
Minimum of Months | 0.126255E+09 | 7048707.90 | 77221105.23 | 0.242907E+09 | 6430369.79 |
Maximum of Months | 0.275734E+09 | 0.192604E+09 | 0.128056E+09 | 0.383476E+09 | 0.300873E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219849E+09 | 0.102224E+09 | 0.117625E+09 | 0.172971E+09 | 0.633884E+09 |
February | 0.227500E+09 | 0.106626E+09 | 0.120874E+09 | 0.233922E+09 | 0.462320E+09 |
March | 0.369530E+09 | 0.178222E+09 | 0.191308E+09 | 0.471170E+09 | 0.294958E+09 |
April | 0.402975E+09 | 0.184312E+09 | 0.218663E+09 | 0.599435E+09 | 0.209543E+09 |
May | 0.418984E+09 | 0.159021E+09 | 0.259962E+09 | 0.694031E+09 | 0.119528E+09 |
June | 0.425988E+09 | 0.164024E+09 | 0.261964E+09 | 0.806864E+09 | 52362775.74 |
July | 0.414335E+09 | 0.153256E+09 | 0.261080E+09 | 0.825812E+09 | 24905949.22 |
August | 0.406982E+09 | 0.152218E+09 | 0.254764E+09 | 0.816988E+09 | 11992662.81 |
September | 0.321755E+09 | 0.134509E+09 | 0.187246E+09 | 0.556974E+09 | 78939512.05 |
October | 0.295829E+09 | 0.153811E+09 | 0.142018E+09 | 0.419255E+09 | 0.255759E+09 |
November | 0.227376E+09 | 0.101680E+09 | 0.125697E+09 | 0.262818E+09 | 0.371123E+09 |
December | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.168460E+09 | 0.516750E+09 |
Annual Sum or Average | 0.392571E+10 | 0.167515E+10 | 0.225056E+10 | 0.602870E+10 | 0.303206E+10 |
Minimum of Months | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.168460E+09 | 11992662.81 |
Maximum of Months | 0.425988E+09 | 0.184312E+09 | 0.261964E+09 | 0.825812E+09 | 0.633884E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51932557.31 | 0.00 | 51932557.31 | 8562194.40 | 0.357689E+09 |
February | 51991662.66 | 0.00 | 51991662.66 | 25449426.28 | 0.257840E+09 |
March | 80833881.57 | 1627.95 | 80832253.62 | 63324552.57 | 0.163575E+09 |
April | 94850140.82 | 553965.08 | 94296175.74 | 0.114899E+09 | 0.117434E+09 |
May | 0.116941E+09 | 3667679.90 | 0.113274E+09 | 0.180246E+09 | 66492355.37 |
June | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.251429E+09 | 28610680.15 |
July | 0.121807E+09 | 6241532.89 | 0.115565E+09 | 0.265477E+09 | 14997912.63 |
August | 0.108187E+09 | 1270984.59 | 0.106916E+09 | 0.245018E+09 | 7195861.87 |
September | 79030084.51 | 31067.06 | 78999017.45 | 0.136511E+09 | 46015572.36 |
October | 62049703.82 | 0.00 | 62049703.82 | 64992402.51 | 0.140766E+09 |
November | 53740831.96 | 0.00 | 53740831.96 | 35299770.89 | 0.199748E+09 |
December | 48007784.18 | 0.00 | 48007784.18 | 11677714.78 | 0.282507E+09 |
Annual Sum or Average | 0.993838E+09 | 19929300.33 | 0.973909E+09 | 0.140289E+10 | 0.168287E+10 |
Minimum of Months | 48007784.18 | 0.00 | 48007784.18 | 8562194.40 | 7195861.87 |
Maximum of Months | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.265477E+09 | 0.357689E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219849E+09 | 0.102224E+09 | 0.117625E+09 | 0.182965E+09 | 0.623258E+09 |
February | 0.227500E+09 | 0.106626E+09 | 0.120874E+09 | 0.242346E+09 | 0.455761E+09 |
March | 0.369530E+09 | 0.178222E+09 | 0.191308E+09 | 0.478133E+09 | 0.293977E+09 |
April | 0.402975E+09 | 0.184312E+09 | 0.218663E+09 | 0.598381E+09 | 0.217416E+09 |
May | 0.418984E+09 | 0.159021E+09 | 0.259962E+09 | 0.687121E+09 | 0.129824E+09 |
June | 0.425988E+09 | 0.164024E+09 | 0.261964E+09 | 0.799792E+09 | 56953281.83 |
July | 0.414335E+09 | 0.153256E+09 | 0.261080E+09 | 0.818864E+09 | 28491587.57 |
August | 0.406982E+09 | 0.152218E+09 | 0.254764E+09 | 0.813820E+09 | 13565490.46 |
September | 0.321755E+09 | 0.134509E+09 | 0.187246E+09 | 0.555887E+09 | 85079657.50 |
October | 0.295829E+09 | 0.153811E+09 | 0.142018E+09 | 0.425827E+09 | 0.257154E+09 |
November | 0.227376E+09 | 0.101680E+09 | 0.125697E+09 | 0.275092E+09 | 0.363278E+09 |
December | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.180948E+09 | 0.505316E+09 |
Annual Sum or Average | 0.392571E+10 | 0.167515E+10 | 0.225056E+10 | 0.605918E+10 | 0.303007E+10 |
Minimum of Months | 0.194602E+09 | 85244676.27 | 0.109357E+09 | 0.180948E+09 | 13565490.46 |
Maximum of Months | 0.425988E+09 | 0.184312E+09 | 0.261964E+09 | 0.818864E+09 | 0.623258E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.404391E+09 | 0.280919E+09 | 0.123472E+09 | 0.448650E+09 | 0.460941E+09 |
February | 0.340241E+09 | 0.226989E+09 | 0.113252E+09 | 0.414080E+09 | 0.341856E+09 |
March | 0.344465E+09 | 0.180759E+09 | 0.163706E+09 | 0.472298E+09 | 0.228672E+09 |
April | 0.250873E+09 | 83699171.49 | 0.167174E+09 | 0.394026E+09 | 0.165739E+09 |
May | 0.208383E+09 | 25500924.42 | 0.182882E+09 | 0.362415E+09 | 91471011.32 |
June | 0.185164E+09 | 10337606.61 | 0.174827E+09 | 0.396805E+09 | 38367518.62 |
July | 0.191934E+09 | 12946187.50 | 0.178988E+09 | 0.438304E+09 | 17579755.68 |
August | 0.231271E+09 | 43464822.63 | 0.187806E+09 | 0.523461E+09 | 8001264.39 |
September | 0.252681E+09 | 98315365.50 | 0.154366E+09 | 0.464418E+09 | 60745469.31 |
October | 0.366639E+09 | 0.236973E+09 | 0.129666E+09 | 0.555811E+09 | 0.196343E+09 |
November | 0.387648E+09 | 0.258678E+09 | 0.128970E+09 | 0.519698E+09 | 0.276818E+09 |
December | 0.401544E+09 | 0.282472E+09 | 0.119072E+09 | 0.480984E+09 | 0.378245E+09 |
Annual Sum or Average | 0.356523E+10 | 0.174105E+10 | 0.182418E+10 | 0.547095E+10 | 0.226478E+10 |
Minimum of Months | 0.185164E+09 | 10337606.61 | 0.113252E+09 | 0.362415E+09 | 8001264.39 |
Maximum of Months | 0.404391E+09 | 0.282472E+09 | 0.187806E+09 | 0.555811E+09 | 0.460941E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.363514E+09 | 0.00 | 0.363514E+09 | 42600656.51 | 0.286706E+10 |
February | 0.363928E+09 | 0.00 | 0.363928E+09 | 0.153571E+09 | 0.208835E+10 |
March | 0.565816E+09 | 11395.24 | 0.565804E+09 | 0.419219E+09 | 0.134271E+10 |
April | 0.663926E+09 | 3877608.68 | 0.660048E+09 | 0.815323E+09 | 0.953515E+09 |
May | 0.818558E+09 | 25672786.98 | 0.792886E+09 | 0.129066E+10 | 0.578815E+09 |
June | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.177282E+10 | 0.302861E+09 |
July | 0.852615E+09 | 43689075.52 | 0.808926E+09 | 0.185855E+10 | 0.196213E+09 |
August | 0.757280E+09 | 8896555.21 | 0.748384E+09 | 0.170546E+10 | 0.142064E+09 |
September | 0.553190E+09 | 217461.16 | 0.552972E+09 | 0.968581E+09 | 0.442420E+09 |
October | 0.434331E+09 | 0.00 | 0.434331E+09 | 0.441299E+09 | 0.117824E+10 |
November | 0.376172E+09 | 0.00 | 0.376172E+09 | 0.208663E+09 | 0.164453E+10 |
December | 0.336042E+09 | 0.00 | 0.336042E+09 | 48406778.72 | 0.231795E+10 |
Annual Sum or Average | 0.695660E+10 | 0.139500E+09 | 0.681710E+10 | 0.972515E+10 | 0.140547E+11 |
Minimum of Months | 0.336042E+09 | 0.00 | 0.336042E+09 | 42600656.51 | 0.142064E+09 |
Maximum of Months | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.185855E+10 | 0.286706E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.363514E+09 | 0.00 | 0.363514E+09 | 37523579.59 | 0.296651E+10 |
February | 0.363928E+09 | 0.00 | 0.363928E+09 | 0.141994E+09 | 0.217044E+10 |
March | 0.565816E+09 | 11395.24 | 0.565804E+09 | 0.391068E+09 | 0.140653E+10 |
April | 0.663926E+09 | 3877608.68 | 0.660048E+09 | 0.782155E+09 | 0.995829E+09 |
May | 0.818558E+09 | 25672786.98 | 0.792886E+09 | 0.125180E+10 | 0.609577E+09 |
June | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.172978E+10 | 0.324342E+09 |
July | 0.852615E+09 | 43689075.52 | 0.808926E+09 | 0.181321E+10 | 0.214935E+09 |
August | 0.757280E+09 | 8896555.21 | 0.748384E+09 | 0.166130E+10 | 0.160967E+09 |
September | 0.553190E+09 | 217461.16 | 0.552972E+09 | 0.935053E+09 | 0.474035E+09 |
October | 0.434331E+09 | 0.00 | 0.434331E+09 | 0.417568E+09 | 0.123510E+10 |
November | 0.376172E+09 | 0.00 | 0.376172E+09 | 0.188364E+09 | 0.171924E+10 |
December | 0.336042E+09 | 0.00 | 0.336042E+09 | 40466229.26 | 0.241906E+10 |
Annual Sum or Average | 0.695660E+10 | 0.139500E+09 | 0.681710E+10 | 0.939029E+10 | 0.146966E+11 |
Minimum of Months | 0.336042E+09 | 0.00 | 0.336042E+09 | 37523579.59 | 0.160967E+09 |
Maximum of Months | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.181321E+10 | 0.296651E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51932557.31 | 0.00 | 51932557.31 | 7721977.44 | 0.416692E+09 |
February | 51991662.66 | 0.00 | 51991662.66 | 26211148.60 | 0.304805E+09 |
March | 80833881.57 | 1627.95 | 80832253.62 | 74424817.64 | 0.196653E+09 |
April | 94850140.82 | 553965.08 | 94296175.74 | 0.141720E+09 | 0.139638E+09 |
May | 0.116941E+09 | 3667679.90 | 0.113274E+09 | 0.221636E+09 | 88368201.21 |
June | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.295796E+09 | 50209803.89 |
July | 0.121807E+09 | 6241532.89 | 0.115565E+09 | 0.313434E+09 | 34432782.62 |
August | 0.108187E+09 | 1270984.59 | 0.106916E+09 | 0.290953E+09 | 26411793.44 |
September | 79030084.51 | 31067.06 | 78999017.45 | 0.171549E+09 | 64981329.89 |
October | 62049703.82 | 0.00 | 62049703.82 | 80341151.45 | 0.169417E+09 |
November | 53740831.96 | 0.00 | 53740831.96 | 39671922.96 | 0.237395E+09 |
December | 48007784.18 | 0.00 | 48007784.18 | 9518062.89 | 0.336526E+09 |
Annual Sum or Average | 0.993838E+09 | 19929300.33 | 0.973909E+09 | 0.167298E+10 | 0.206553E+10 |
Minimum of Months | 48007784.18 | 0.00 | 48007784.18 | 7721977.44 | 26411793.44 |
Maximum of Months | 0.124466E+09 | 8162442.86 | 0.116304E+09 | 0.313434E+09 | 0.416692E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429087E+09 | 0.195371E+09 | 0.233716E+09 | 0.300307E+09 | 0.140695E+10 |
February | 0.486410E+09 | 0.261841E+09 | 0.224569E+09 | 0.494702E+09 | 0.102682E+10 |
March | 0.677538E+09 | 0.309057E+09 | 0.368481E+09 | 0.875052E+09 | 0.676259E+09 |
April | 0.792596E+09 | 0.361770E+09 | 0.430826E+09 | 0.126870E+10 | 0.494176E+09 |
May | 0.897213E+09 | 0.379424E+09 | 0.517790E+09 | 0.162235E+10 | 0.327024E+09 |
June | 0.898068E+09 | 0.376155E+09 | 0.521913E+09 | 0.185216E+10 | 0.187221E+09 |
July | 0.904512E+09 | 0.379485E+09 | 0.525027E+09 | 0.194747E+10 | 0.129576E+09 |
August | 0.829031E+09 | 0.328853E+09 | 0.500178E+09 | 0.183205E+10 | 99404795.45 |
September | 0.657527E+09 | 0.290535E+09 | 0.366992E+09 | 0.127605E+10 | 0.239131E+09 |
October | 0.581128E+09 | 0.302483E+09 | 0.278645E+09 | 0.879029E+09 | 0.594398E+09 |
November | 0.447892E+09 | 0.202040E+09 | 0.245852E+09 | 0.508862E+09 | 0.803124E+09 |
December | 0.401631E+09 | 0.182822E+09 | 0.218809E+09 | 0.308251E+09 | 0.112901E+10 |
Annual Sum or Average | 0.800263E+10 | 0.356984E+10 | 0.443280E+10 | 0.131650E+11 | 0.711309E+10 |
Minimum of Months | 0.401631E+09 | 0.182822E+09 | 0.218809E+09 | 0.300307E+09 | 99404795.45 |
Maximum of Months | 0.904512E+09 | 0.379485E+09 | 0.525027E+09 | 0.194747E+10 | 0.140695E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275734E+09 | 0.191545E+09 | 84189446.79 | 0.322858E+09 | 0.344418E+09 |
February | 0.231994E+09 | 0.154772E+09 | 77221105.23 | 0.298422E+09 | 0.261294E+09 |
March | 0.234874E+09 | 0.123251E+09 | 0.111623E+09 | 0.347653E+09 | 0.185430E+09 |
April | 0.171058E+09 | 57070367.83 | 0.113987E+09 | 0.297462E+09 | 0.140566E+09 |
May | 0.142086E+09 | 17387832.05 | 0.124699E+09 | 0.281643E+09 | 91187984.41 |
June | 0.126255E+09 | 7048707.90 | 0.119206E+09 | 0.304831E+09 | 52081635.79 |
July | 0.130870E+09 | 8827371.52 | 0.122043E+09 | 0.334928E+09 | 34803412.28 |
August | 0.157692E+09 | 29636534.88 | 0.128056E+09 | 0.394640E+09 | 26438224.23 |
September | 0.172291E+09 | 67036435.04 | 0.105255E+09 | 0.352793E+09 | 64298851.35 |
October | 0.249993E+09 | 0.161580E+09 | 88412715.82 | 0.409762E+09 | 0.159810E+09 |
November | 0.264318E+09 | 0.176380E+09 | 87938230.82 | 0.380717E+09 | 0.211639E+09 |
December | 0.273793E+09 | 0.192604E+09 | 81189647.76 | 0.347345E+09 | 0.285611E+09 |
Annual Sum or Average | 0.243096E+10 | 0.118714E+10 | 0.124382E+10 | 0.407305E+10 | 0.185758E+10 |
Minimum of Months | 0.126255E+09 | 7048707.90 | 77221105.23 | 0.281643E+09 | 26438224.23 |
Maximum of Months | 0.275734E+09 | 0.192604E+09 | 0.128056E+09 | 0.409762E+09 | 0.344418E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 65769307.07 | 0.00 | 65769307.07 | 7812025.28 | 0.503036E+09 |
February | 65844160.26 | 0.00 | 65844160.26 | 25753825.51 | 0.367743E+09 |
March | 0.102371E+09 | 2061.70 | 0.102369E+09 | 67555018.39 | 0.244676E+09 |
April | 0.120122E+09 | 701561.82 | 0.119420E+09 | 0.132375E+09 | 0.180052E+09 |
May | 0.148099E+09 | 4644885.18 | 0.143454E+09 | 0.211993E+09 | 0.112925E+09 |
June | 0.157629E+09 | 10337218.86 | 0.147291E+09 | 0.298090E+09 | 59226521.36 |
July | 0.154261E+09 | 7904507.59 | 0.146356E+09 | 0.312344E+09 | 39523004.87 |
August | 0.137012E+09 | 1609621.79 | 0.135402E+09 | 0.283901E+09 | 29643692.84 |
September | 0.100087E+09 | 39344.47 | 0.100047E+09 | 0.154885E+09 | 90000669.68 |
October | 78582034.76 | 0.00 | 78582034.76 | 67190887.12 | 0.222567E+09 |
November | 68059372.82 | 0.00 | 68059372.82 | 33078959.33 | 0.295845E+09 |
December | 60798829.53 | 0.00 | 60798829.53 | 8194554.33 | 0.404975E+09 |
Annual Sum or Average | 0.125863E+10 | 25239201.40 | 0.123339E+10 | 0.160317E+10 | 0.255021E+10 |
Minimum of Months | 60798829.53 | 0.00 | 60798829.53 | 7812025.28 | 29643692.84 |
Maximum of Months | 0.157629E+09 | 10337218.86 | 0.147291E+09 | 0.312344E+09 | 0.503036E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58844048.24 | 0.00 | 58844048.24 | 6989448.62 | 0.450059E+09 |
February | 58911019.67 | 0.00 | 58911019.67 | 23042045.27 | 0.329021E+09 |
March | 91591731.14 | 1844.61 | 91589886.53 | 60441730.92 | 0.218912E+09 |
April | 0.107473E+09 | 627690.02 | 0.106846E+09 | 0.118436E+09 | 0.161093E+09 |
May | 0.132505E+09 | 4155796.37 | 0.128349E+09 | 0.189671E+09 | 0.101034E+09 |
June | 0.141031E+09 | 9248748.88 | 0.131782E+09 | 0.266702E+09 | 52990193.07 |
July | 0.138017E+09 | 7072192.89 | 0.130945E+09 | 0.279455E+09 | 35361382.21 |
August | 0.122585E+09 | 1440134.72 | 0.121145E+09 | 0.254007E+09 | 26522324.31 |
September | 89547874.12 | 35201.64 | 89512672.48 | 0.138577E+09 | 80523940.18 |
October | 70307644.25 | 0.00 | 70307644.25 | 60115941.30 | 0.199132E+09 |
November | 60892978.73 | 0.00 | 60892978.73 | 29595870.25 | 0.264692E+09 |
December | 54396943.15 | 0.00 | 54396943.15 | 7331698.81 | 0.362318E+09 |
Annual Sum or Average | 0.112610E+10 | 22581609.12 | 0.110352E+10 | 0.143436E+10 | 0.228166E+10 |
Minimum of Months | 54396943.15 | 0.00 | 54396943.15 | 6989448.62 | 26522324.31 |
Maximum of Months | 0.141031E+09 | 9248748.88 | 0.131782E+09 | 0.279455E+09 | 0.450059E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102940E+10 | 0.715094E+09 | 0.314304E+09 | 0.116484E+10 | 0.120730E+10 |
February | 0.866101E+09 | 0.577812E+09 | 0.288289E+09 | 0.106472E+10 | 0.919332E+09 |
March | 0.876854E+09 | 0.460131E+09 | 0.416723E+09 | 0.118792E+10 | 0.671864E+09 |
April | 0.638610E+09 | 0.213061E+09 | 0.425549E+09 | 0.960983E+09 | 0.535363E+09 |
May | 0.530451E+09 | 64913958.36 | 0.465537E+09 | 0.851724E+09 | 0.353511E+09 |
June | 0.471346E+09 | 26314927.01 | 0.445031E+09 | 0.916150E+09 | 0.189148E+09 |
July | 0.488578E+09 | 32955208.31 | 0.455622E+09 | 0.100648E+10 | 0.122730E+09 |
August | 0.588712E+09 | 0.110642E+09 | 0.478070E+09 | 0.122279E+10 | 89873654.03 |
September | 0.643214E+09 | 0.250267E+09 | 0.392947E+09 | 0.111885E+10 | 0.263256E+09 |
October | 0.933299E+09 | 0.603228E+09 | 0.330071E+09 | 0.138971E+10 | 0.609397E+09 |
November | 0.986778E+09 | 0.658479E+09 | 0.328300E+09 | 0.133068E+10 | 0.766039E+09 |
December | 0.102215E+10 | 0.719047E+09 | 0.303105E+09 | 0.124626E+10 | 0.996591E+09 |
Annual Sum or Average | 0.907549E+10 | 0.443194E+10 | 0.464355E+10 | 0.134611E+11 | 0.672441E+10 |
Minimum of Months | 0.471346E+09 | 26314927.01 | 0.288289E+09 | 0.851724E+09 | 89873654.03 |
Maximum of Months | 0.102940E+10 | 0.719047E+09 | 0.478070E+09 | 0.138971E+10 | 0.120730E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 598.47 | 564.40 | 520.68 | 361.70 | 158.98 | 0.00 | 0.00 |
February | 606.57 | 472.13 | 485.02 | 323.58 | 161.44 | 0.00 | 0.00 |
March | 614.54 | 312.15 | 443.52 | 232.74 | 210.78 | 0.00 | 0.00 |
April | 518.00 | 250.03 | 333.78 | 111.36 | 222.42 | 0.00 | 0.00 |
May | 442.59 | 159.78 | 268.30 | 32.83 | 235.47 | 0.00 | 0.00 |
June | 474.11 | 96.68 | 246.36 | 13.75 | 232.60 | 0.00 | 0.00 |
July | 501.06 | 62.34 | 247.12 | 16.67 | 230.46 | 0.00 | 0.00 |
August | 607.44 | 50.69 | 297.77 | 55.96 | 241.81 | 0.00 | 0.00 |
September | 586.97 | 130.02 | 336.19 | 130.81 | 205.38 | 0.00 | 0.00 |
October | 710.78 | 283.69 | 472.07 | 305.12 | 166.95 | 0.00 | 0.00 |
November | 698.77 | 376.70 | 515.76 | 344.17 | 171.59 | 0.00 | 0.00 |
December | 636.52 | 472.32 | 517.01 | 363.70 | 153.31 | 0.00 | 0.00 |
Annual Sum or Average | 582.94 | 268.19 | 389.87 | 190.39 | 199.48 | 0.00 | 0.00 |
Minimum of Months | 442.59 | 50.69 | 246.36 | 13.75 | 153.31 | 0.00 | 0.00 |
Maximum of Months | 710.78 | 564.40 | 520.68 | 363.70 | 241.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1683.48 | 1616.70 | 1466.20 | 1018.53 | 447.67 | 0.00 | 0.00 |
February | 1712.22 | 1351.29 | 1365.78 | 911.17 | 454.61 | 0.00 | 0.00 |
March | 1758.30 | 868.34 | 1248.92 | 655.38 | 593.54 | 0.00 | 0.00 |
April | 1506.03 | 673.59 | 939.90 | 313.58 | 626.32 | 0.00 | 0.00 |
May | 1323.84 | 405.78 | 755.53 | 92.46 | 663.07 | 0.00 | 0.00 |
June | 1438.84 | 229.17 | 693.72 | 38.73 | 654.99 | 0.00 | 0.00 |
July | 1514.61 | 139.84 | 695.89 | 46.94 | 648.95 | 0.00 | 0.00 |
August | 1803.63 | 109.24 | 838.51 | 157.59 | 680.92 | 0.00 | 0.00 |
September | 1719.21 | 322.76 | 946.68 | 368.34 | 578.34 | 0.00 | 0.00 |
October | 2033.48 | 777.61 | 1329.32 | 859.19 | 470.13 | 0.00 | 0.00 |
November | 1981.99 | 1060.46 | 1452.34 | 969.15 | 483.19 | 0.00 | 0.00 |
December | 1794.07 | 1352.77 | 1455.88 | 1024.16 | 431.72 | 0.00 | 0.00 |
Annual Sum or Average | 1689.25 | 739.16 | 1097.86 | 536.13 | 561.73 | 0.00 | 0.00 |
Minimum of Months | 1323.84 | 109.24 | 693.72 | 38.73 | 431.72 | 0.00 | 0.00 |
Maximum of Months | 2033.48 | 1616.70 | 1466.20 | 1024.16 | 680.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2213.10 | 2221.72 | 1904.67 | 1323.13 | 581.55 | 0.00 | 0.00 |
February | 2252.17 | 1863.66 | 1774.23 | 1183.66 | 590.56 | 0.00 | 0.00 |
March | 2304.01 | 1213.58 | 1622.42 | 851.37 | 771.05 | 0.00 | 0.00 |
April | 1961.56 | 956.28 | 1220.99 | 407.36 | 813.62 | 0.00 | 0.00 |
May | 1707.77 | 592.47 | 981.47 | 120.11 | 861.37 | 0.00 | 0.00 |
June | 1849.03 | 342.87 | 901.18 | 50.31 | 850.87 | 0.00 | 0.00 |
July | 1950.22 | 215.43 | 904.00 | 60.98 | 843.02 | 0.00 | 0.00 |
August | 2344.09 | 166.19 | 1089.28 | 204.72 | 884.56 | 0.00 | 0.00 |
September | 2234.27 | 475.67 | 1229.79 | 478.50 | 751.29 | 0.00 | 0.00 |
October | 2665.72 | 1096.01 | 1726.86 | 1116.14 | 610.72 | 0.00 | 0.00 |
November | 2596.07 | 1480.87 | 1886.68 | 1258.98 | 627.69 | 0.00 | 0.00 |
December | 2353.51 | 1876.25 | 1891.27 | 1330.44 | 560.83 | 0.00 | 0.00 |
Annual Sum or Average | 2202.68 | 1037.49 | 1426.18 | 696.47 | 729.71 | 0.00 | 0.00 |
Minimum of Months | 1707.77 | 166.19 | 901.18 | 50.31 | 560.83 | 0.00 | 0.00 |
Maximum of Months | 2665.72 | 2221.72 | 1904.67 | 1330.44 | 884.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 167.38 | 334.22 | 185.03 | 109.68 | 75.35 | 0.00 | 0.00 |
February | 205.75 | 273.10 | 189.94 | 108.05 | 81.88 | 0.00 | 0.00 |
March | 297.40 | 166.01 | 225.66 | 112.56 | 113.10 | 0.00 | 0.00 |
April | 337.00 | 125.19 | 221.46 | 93.13 | 128.34 | 0.00 | 0.00 |
May | 353.45 | 69.77 | 209.48 | 65.86 | 143.62 | 0.00 | 0.00 |
June | 416.24 | 32.45 | 213.06 | 66.00 | 147.06 | 0.00 | 0.00 |
July | 419.78 | 15.41 | 203.56 | 60.51 | 143.04 | 0.00 | 0.00 |
August | 438.38 | 7.74 | 210.83 | 67.90 | 142.93 | 0.00 | 0.00 |
September | 338.59 | 48.44 | 190.60 | 77.76 | 112.85 | 0.00 | 0.00 |
October | 299.17 | 144.13 | 203.79 | 117.75 | 86.03 | 0.00 | 0.00 |
November | 235.46 | 208.11 | 189.70 | 107.28 | 82.42 | 0.00 | 0.00 |
December | 176.63 | 273.43 | 174.88 | 103.74 | 71.14 | 0.00 | 0.00 |
Annual Sum or Average | 307.67 | 140.84 | 201.57 | 90.76 | 110.81 | 0.00 | 0.00 |
Minimum of Months | 167.38 | 7.74 | 174.88 | 60.51 | 71.14 | 0.00 | 0.00 |
Maximum of Months | 438.38 | 334.22 | 225.66 | 117.75 | 147.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 64.08 | 360.99 | 101.47 | 38.17 | 63.31 | 0.00 | 0.00 |
February | 105.84 | 292.25 | 115.53 | 44.07 | 71.46 | 0.00 | 0.00 |
March | 201.90 | 171.14 | 168.15 | 66.54 | 101.61 | 0.00 | 0.00 |
April | 277.37 | 128.90 | 192.06 | 71.32 | 120.74 | 0.00 | 0.00 |
May | 327.16 | 73.07 | 200.09 | 60.74 | 139.35 | 0.00 | 0.00 |
June | 407.97 | 33.42 | 212.37 | 66.43 | 145.94 | 0.00 | 0.00 |
July | 407.15 | 16.93 | 200.17 | 59.55 | 140.62 | 0.00 | 0.00 |
August | 397.56 | 8.62 | 192.34 | 57.31 | 135.04 | 0.00 | 0.00 |
September | 268.72 | 52.25 | 154.62 | 51.91 | 102.72 | 0.00 | 0.00 |
October | 182.95 | 150.19 | 133.62 | 57.43 | 76.19 | 0.00 | 0.00 |
November | 117.89 | 218.87 | 108.46 | 39.23 | 69.23 | 0.00 | 0.00 |
December | 67.56 | 293.82 | 90.58 | 31.83 | 58.75 | 0.00 | 0.00 |
Annual Sum or Average | 236.22 | 149.33 | 156.00 | 53.75 | 102.25 | 0.00 | 0.00 |
Minimum of Months | 64.08 | 8.62 | 90.58 | 31.83 | 58.75 | 0.00 | 0.00 |
Maximum of Months | 407.97 | 360.99 | 212.37 | 71.32 | 145.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 90.74 | 98.51 | 82.34 | 57.20 | 25.14 | 0.00 | 0.00 |
February | 88.65 | 93.14 | 76.70 | 51.17 | 25.53 | 0.00 | 0.00 |
March | 85.67 | 70.75 | 70.14 | 36.81 | 33.33 | 0.00 | 0.00 |
April | 70.94 | 57.77 | 52.79 | 17.61 | 35.17 | 0.00 | 0.00 |
May | 59.77 | 38.84 | 42.43 | 5.19 | 37.24 | 0.00 | 0.00 |
June | 65.97 | 24.42 | 38.96 | 2.18 | 36.78 | 0.00 | 0.00 |
July | 70.38 | 17.94 | 39.08 | 2.64 | 36.45 | 0.00 | 0.00 |
August | 87.58 | 15.53 | 47.09 | 8.85 | 38.24 | 0.00 | 0.00 |
September | 84.24 | 32.91 | 53.17 | 20.69 | 32.48 | 0.00 | 0.00 |
October | 103.08 | 64.25 | 74.65 | 48.25 | 26.40 | 0.00 | 0.00 |
November | 99.75 | 83.56 | 81.56 | 54.43 | 27.14 | 0.00 | 0.00 |
December | 91.21 | 98.64 | 81.76 | 57.52 | 24.25 | 0.00 | 0.00 |
Annual Sum or Average | 83.15 | 57.82 | 61.66 | 30.11 | 31.55 | 0.00 | 0.00 |
Minimum of Months | 59.77 | 15.53 | 38.96 | 2.18 | 24.25 | 0.00 | 0.00 |
Maximum of Months | 103.08 | 98.64 | 82.34 | 57.52 | 38.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.20 | 112.54 | 15.51 | 0.00 | 15.51 | 0.00 | 0.00 |
February | 8.26 | 89.39 | 17.20 | 0.00 | 17.20 | 0.00 | 0.00 |
March | 20.04 | 49.23 | 24.15 | 0.00 | 24.15 | 0.00 | 0.00 |
April | 38.08 | 35.39 | 29.28 | 0.17 | 29.11 | 0.00 | 0.00 |
May | 57.51 | 18.74 | 34.93 | 1.10 | 33.84 | 0.00 | 0.00 |
June | 82.06 | 7.90 | 38.42 | 2.52 | 35.90 | 0.00 | 0.00 |
July | 84.05 | 3.82 | 36.39 | 1.86 | 34.52 | 0.00 | 0.00 |
August | 78.33 | 1.64 | 32.32 | 0.38 | 31.94 | 0.00 | 0.00 |
September | 45.09 | 13.59 | 24.40 | 0.01 | 24.39 | 0.00 | 0.00 |
October | 20.52 | 42.61 | 18.54 | 0.00 | 18.54 | 0.00 | 0.00 |
November | 10.68 | 64.34 | 16.59 | 0.00 | 16.59 | 0.00 | 0.00 |
December | 2.80 | 89.55 | 14.34 | 0.00 | 14.34 | 0.00 | 0.00 |
Annual Sum or Average | 37.64 | 43.84 | 25.21 | 0.51 | 24.71 | 0.00 | 0.00 |
Minimum of Months | 2.20 | 1.64 | 14.34 | 0.00 | 14.34 | 0.00 | 0.00 |
Maximum of Months | 84.05 | 112.54 | 38.42 | 2.52 | 35.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 159.49 | 329.42 | 183.05 | 107.99 | 75.07 | 0.00 | 0.00 |
February | 209.78 | 267.00 | 196.44 | 118.10 | 78.34 | 0.00 | 0.00 |
March | 269.64 | 158.05 | 214.18 | 103.72 | 110.47 | 0.00 | 0.00 |
April | 323.39 | 116.43 | 218.90 | 91.81 | 127.09 | 0.00 | 0.00 |
May | 365.44 | 64.67 | 220.55 | 77.33 | 143.22 | 0.00 | 0.00 |
June | 428.14 | 29.63 | 221.96 | 75.29 | 146.67 | 0.00 | 0.00 |
July | 442.01 | 14.83 | 217.73 | 74.14 | 143.58 | 0.00 | 0.00 |
August | 443.33 | 7.30 | 213.65 | 72.46 | 141.19 | 0.00 | 0.00 |
September | 341.32 | 46.31 | 193.32 | 81.91 | 111.41 | 0.00 | 0.00 |
October | 289.25 | 138.33 | 201.83 | 116.80 | 85.03 | 0.00 | 0.00 |
November | 226.18 | 201.24 | 188.38 | 107.02 | 81.36 | 0.00 | 0.00 |
December | 174.53 | 267.64 | 177.20 | 106.04 | 71.16 | 0.00 | 0.00 |
Annual Sum or Average | 306.57 | 136.09 | 203.98 | 94.25 | 109.73 | 0.00 | 0.00 |
Minimum of Months | 159.49 | 7.30 | 177.20 | 72.46 | 71.16 | 0.00 | 0.00 |
Maximum of Months | 443.33 | 329.42 | 221.96 | 118.10 | 146.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 49.63 | 349.32 | 99.50 | 36.47 | 63.02 | 0.00 | 0.00 |
February | 100.40 | 276.06 | 122.03 | 54.12 | 67.91 | 0.00 | 0.00 |
March | 171.15 | 158.36 | 156.67 | 57.70 | 98.97 | 0.00 | 0.00 |
April | 263.99 | 119.20 | 189.50 | 70.00 | 119.49 | 0.00 | 0.00 |
May | 339.85 | 68.81 | 211.16 | 72.20 | 138.96 | 0.00 | 0.00 |
June | 419.36 | 31.72 | 221.27 | 75.71 | 145.56 | 0.00 | 0.00 |
July | 427.89 | 16.76 | 214.34 | 73.18 | 141.17 | 0.00 | 0.00 |
August | 401.44 | 8.16 | 195.17 | 61.87 | 133.30 | 0.00 | 0.00 |
September | 270.04 | 49.59 | 157.34 | 56.06 | 101.28 | 0.00 | 0.00 |
October | 169.34 | 139.71 | 131.66 | 56.47 | 75.19 | 0.00 | 0.00 |
November | 99.88 | 201.51 | 107.14 | 38.98 | 68.16 | 0.00 | 0.00 |
December | 53.30 | 275.36 | 92.91 | 34.13 | 58.77 | 0.00 | 0.00 |
Annual Sum or Average | 231.23 | 140.55 | 158.40 | 57.24 | 101.17 | 0.00 | 0.00 |
Minimum of Months | 49.63 | 8.16 | 92.91 | 34.13 | 58.77 | 0.00 | 0.00 |
Maximum of Months | 427.89 | 349.32 | 221.27 | 75.71 | 145.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.92 | 425.69 | 212.02 | 123.94 | 88.08 | 0.00 | 0.00 |
February | 208.32 | 347.47 | 203.44 | 110.87 | 92.57 | 0.00 | 0.00 |
March | 256.88 | 212.23 | 204.28 | 79.75 | 124.53 | 0.00 | 0.00 |
April | 266.48 | 165.00 | 177.80 | 38.53 | 139.27 | 0.00 | 0.00 |
May | 284.55 | 95.39 | 167.61 | 13.62 | 153.99 | 0.00 | 0.00 |
June | 346.27 | 50.87 | 167.65 | 10.17 | 157.48 | 0.00 | 0.00 |
July | 356.54 | 31.25 | 163.50 | 9.75 | 153.75 | 0.00 | 0.00 |
August | 379.26 | 21.27 | 172.05 | 20.00 | 152.05 | 0.00 | 0.00 |
September | 304.50 | 75.79 | 168.04 | 44.84 | 123.20 | 0.00 | 0.00 |
October | 291.10 | 188.73 | 201.91 | 104.55 | 97.36 | 0.00 | 0.00 |
November | 259.69 | 259.92 | 212.66 | 117.93 | 94.73 | 0.00 | 0.00 |
December | 205.37 | 344.34 | 208.22 | 124.62 | 83.60 | 0.00 | 0.00 |
Annual Sum or Average | 278.64 | 184.01 | 188.21 | 66.33 | 121.88 | 0.00 | 0.00 |
Minimum of Months | 179.92 | 21.27 | 163.50 | 9.75 | 83.60 | 0.00 | 0.00 |
Maximum of Months | 379.26 | 425.69 | 212.66 | 124.62 | 157.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 167.36 | 332.33 | 185.03 | 109.68 | 75.35 | 0.00 | 0.00 |
February | 204.92 | 270.93 | 189.94 | 108.05 | 81.88 | 0.00 | 0.00 |
March | 294.72 | 163.90 | 225.66 | 112.56 | 113.10 | 0.00 | 0.00 |
April | 333.59 | 123.62 | 221.46 | 93.13 | 128.34 | 0.00 | 0.00 |
May | 349.63 | 68.57 | 209.48 | 65.86 | 143.62 | 0.00 | 0.00 |
June | 413.00 | 31.10 | 213.06 | 66.00 | 147.06 | 0.00 | 0.00 |
July | 417.05 | 14.32 | 203.56 | 60.51 | 143.04 | 0.00 | 0.00 |
August | 435.68 | 6.88 | 210.83 | 67.90 | 142.93 | 0.00 | 0.00 |
September | 336.29 | 46.64 | 190.60 | 77.76 | 112.85 | 0.00 | 0.00 |
October | 297.15 | 141.53 | 203.79 | 117.75 | 86.03 | 0.00 | 0.00 |
November | 234.48 | 205.66 | 189.70 | 107.28 | 82.42 | 0.00 | 0.00 |
December | 176.62 | 270.87 | 174.88 | 103.74 | 71.14 | 0.00 | 0.00 |
Annual Sum or Average | 305.60 | 139.03 | 201.57 | 90.76 | 110.81 | 0.00 | 0.00 |
Minimum of Months | 167.36 | 6.88 | 174.88 | 60.51 | 71.14 | 0.00 | 0.00 |
Maximum of Months | 435.68 | 332.33 | 225.66 | 117.75 | 147.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 64.54 | 359.27 | 101.47 | 38.17 | 63.31 | 0.00 | 0.00 |
February | 105.75 | 290.03 | 115.53 | 44.07 | 71.46 | 0.00 | 0.00 |
March | 200.34 | 169.02 | 168.15 | 66.54 | 101.61 | 0.00 | 0.00 |
April | 274.25 | 128.25 | 192.06 | 71.32 | 120.74 | 0.00 | 0.00 |
May | 323.27 | 72.73 | 200.09 | 60.74 | 139.35 | 0.00 | 0.00 |
June | 404.90 | 32.35 | 212.37 | 66.43 | 145.94 | 0.00 | 0.00 |
July | 404.59 | 15.98 | 200.17 | 59.55 | 140.62 | 0.00 | 0.00 |
August | 395.28 | 7.70 | 192.34 | 57.31 | 135.04 | 0.00 | 0.00 |
September | 267.02 | 50.47 | 154.62 | 51.91 | 102.72 | 0.00 | 0.00 |
October | 182.17 | 147.49 | 133.62 | 57.43 | 76.19 | 0.00 | 0.00 |
November | 118.22 | 215.69 | 108.46 | 39.23 | 69.23 | 0.00 | 0.00 |
December | 68.56 | 290.78 | 90.58 | 31.83 | 58.75 | 0.00 | 0.00 |
Annual Sum or Average | 234.78 | 147.60 | 156.00 | 53.75 | 102.25 | 0.00 | 0.00 |
Minimum of Months | 64.54 | 7.70 | 90.58 | 31.83 | 58.75 | 0.00 | 0.00 |
Maximum of Months | 404.90 | 359.27 | 212.37 | 71.32 | 145.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 167.51 | 172.10 | 150.98 | 104.88 | 46.10 | 0.00 | 0.00 |
February | 171.16 | 141.31 | 140.64 | 93.83 | 46.81 | 0.00 | 0.00 |
March | 176.34 | 85.38 | 128.61 | 67.49 | 61.12 | 0.00 | 0.00 |
April | 152.02 | 63.94 | 96.79 | 32.29 | 64.50 | 0.00 | 0.00 |
May | 135.31 | 34.15 | 77.80 | 9.52 | 68.28 | 0.00 | 0.00 |
June | 153.09 | 14.80 | 71.44 | 3.99 | 67.45 | 0.00 | 0.00 |
July | 163.64 | 6.56 | 71.66 | 4.83 | 66.83 | 0.00 | 0.00 |
August | 195.44 | 2.99 | 86.35 | 16.23 | 70.12 | 0.00 | 0.00 |
September | 179.17 | 23.44 | 97.49 | 37.93 | 59.55 | 0.00 | 0.00 |
October | 207.52 | 73.31 | 136.89 | 88.48 | 48.41 | 0.00 | 0.00 |
November | 200.50 | 106.80 | 149.56 | 99.80 | 49.76 | 0.00 | 0.00 |
December | 179.58 | 141.22 | 149.92 | 105.46 | 44.46 | 0.00 | 0.00 |
Annual Sum or Average | 173.48 | 71.82 | 113.05 | 55.21 | 57.84 | 0.00 | 0.00 |
Minimum of Months | 135.31 | 2.99 | 71.44 | 3.99 | 44.46 | 0.00 | 0.00 |
Maximum of Months | 207.52 | 172.10 | 150.98 | 105.46 | 70.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15.91 | 1070.44 | 135.72 | 0.00 | 135.72 | 0.00 | 0.00 |
February | 63.48 | 863.24 | 150.43 | 0.00 | 150.43 | 0.00 | 0.00 |
March | 156.52 | 501.31 | 211.25 | 0.00 | 211.25 | 0.00 | 0.00 |
April | 314.55 | 367.87 | 256.14 | 1.50 | 254.65 | 0.00 | 0.00 |
May | 481.88 | 216.10 | 305.61 | 9.59 | 296.03 | 0.00 | 0.00 |
June | 683.96 | 116.84 | 336.12 | 22.04 | 314.08 | 0.00 | 0.00 |
July | 693.90 | 73.26 | 318.33 | 16.31 | 302.02 | 0.00 | 0.00 |
August | 636.75 | 53.04 | 282.74 | 3.32 | 279.41 | 0.00 | 0.00 |
September | 373.68 | 170.69 | 213.42 | 0.08 | 213.34 | 0.00 | 0.00 |
October | 164.76 | 439.91 | 162.16 | 0.00 | 162.16 | 0.00 | 0.00 |
November | 80.50 | 634.46 | 145.13 | 0.00 | 145.13 | 0.00 | 0.00 |
December | 18.07 | 865.42 | 125.46 | 0.00 | 125.46 | 0.00 | 0.00 |
Annual Sum or Average | 308.38 | 445.67 | 220.59 | 4.42 | 216.17 | 0.00 | 0.00 |
Minimum of Months | 15.91 | 53.04 | 125.46 | 0.00 | 125.46 | 0.00 | 0.00 |
Maximum of Months | 693.90 | 1070.44 | 336.12 | 22.04 | 314.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.01 | 1107.57 | 135.72 | 0.00 | 135.72 | 0.00 | 0.00 |
February | 58.69 | 897.17 | 150.43 | 0.00 | 150.43 | 0.00 | 0.00 |
March | 146.01 | 525.14 | 211.25 | 0.00 | 211.25 | 0.00 | 0.00 |
April | 301.76 | 384.19 | 256.14 | 1.50 | 254.65 | 0.00 | 0.00 |
May | 467.37 | 227.59 | 305.61 | 9.59 | 296.03 | 0.00 | 0.00 |
June | 667.35 | 125.13 | 336.12 | 22.04 | 314.08 | 0.00 | 0.00 |
July | 676.97 | 80.25 | 318.33 | 16.31 | 302.02 | 0.00 | 0.00 |
August | 620.26 | 60.10 | 282.74 | 3.32 | 279.41 | 0.00 | 0.00 |
September | 360.75 | 182.88 | 213.42 | 0.08 | 213.34 | 0.00 | 0.00 |
October | 155.90 | 461.13 | 162.16 | 0.00 | 162.16 | 0.00 | 0.00 |
November | 72.67 | 663.29 | 145.13 | 0.00 | 145.13 | 0.00 | 0.00 |
December | 15.11 | 903.17 | 125.46 | 0.00 | 125.46 | 0.00 | 0.00 |
Annual Sum or Average | 297.76 | 466.03 | 220.59 | 4.42 | 216.17 | 0.00 | 0.00 |
Minimum of Months | 14.01 | 60.10 | 125.46 | 0.00 | 125.46 | 0.00 | 0.00 |
Maximum of Months | 676.97 | 1107.57 | 336.12 | 22.04 | 314.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 191.50 | 765.42 | 282.54 | 144.46 | 138.08 | 0.00 | 0.00 |
February | 310.47 | 630.23 | 318.45 | 172.21 | 146.24 | 0.00 | 0.00 |
March | 476.44 | 387.29 | 370.84 | 161.41 | 209.43 | 0.00 | 0.00 |
April | 653.39 | 293.24 | 408.37 | 161.80 | 246.57 | 0.00 | 0.00 |
May | 791.88 | 187.40 | 431.69 | 149.52 | 282.17 | 0.00 | 0.00 |
June | 945.45 | 110.85 | 443.21 | 150.99 | 292.22 | 0.00 | 0.00 |
July | 969.04 | 74.09 | 432.04 | 147.31 | 284.74 | 0.00 | 0.00 |
August | 939.95 | 56.81 | 408.79 | 134.32 | 274.47 | 0.00 | 0.00 |
September | 693.89 | 141.43 | 350.64 | 137.96 | 212.67 | 0.00 | 0.00 |
October | 506.11 | 339.78 | 333.47 | 173.26 | 160.21 | 0.00 | 0.00 |
November | 347.70 | 472.28 | 295.51 | 146.00 | 149.51 | 0.00 | 0.00 |
December | 221.78 | 627.26 | 270.10 | 140.17 | 129.93 | 0.00 | 0.00 |
Annual Sum or Average | 588.78 | 339.07 | 362.36 | 151.47 | 210.89 | 0.00 | 0.00 |
Minimum of Months | 191.50 | 56.81 | 270.10 | 134.32 | 129.93 | 0.00 | 0.00 |
Maximum of Months | 969.04 | 765.42 | 443.21 | 173.26 | 292.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 393.97 | 760.15 | 430.86 | 266.99 | 163.87 | 0.00 | 0.00 |
February | 429.74 | 637.48 | 409.58 | 238.84 | 170.74 | 0.00 | 0.00 |
March | 485.02 | 417.64 | 399.80 | 171.79 | 228.00 | 0.00 | 0.00 |
April | 466.71 | 337.36 | 334.18 | 82.71 | 251.47 | 0.00 | 0.00 |
May | 466.37 | 210.28 | 302.81 | 27.52 | 275.29 | 0.00 | 0.00 |
June | 569.22 | 114.14 | 297.07 | 17.71 | 279.36 | 0.00 | 0.00 |
July | 595.64 | 72.69 | 291.54 | 17.90 | 273.64 | 0.00 | 0.00 |
August | 657.04 | 54.20 | 316.72 | 42.45 | 274.27 | 0.00 | 0.00 |
September | 544.67 | 167.15 | 321.31 | 96.58 | 224.73 | 0.00 | 0.00 |
October | 559.82 | 378.40 | 404.04 | 225.22 | 178.82 | 0.00 | 0.00 |
November | 520.79 | 495.03 | 430.45 | 254.04 | 176.41 | 0.00 | 0.00 |
December | 437.52 | 624.98 | 424.64 | 268.46 | 156.18 | 0.00 | 0.00 |
Annual Sum or Average | 511.05 | 354.32 | 363.40 | 142.05 | 221.35 | 0.00 | 0.00 |
Minimum of Months | 393.97 | 54.20 | 291.54 | 17.71 | 156.18 | 0.00 | 0.00 |
Maximum of Months | 657.04 | 760.15 | 430.86 | 268.46 | 279.36 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160295E+10 | 0.151169E+10 | 0.139459E+10 | 0.968782E+09 | 0.425804E+09 | 0.00 | 0.00 |
February | 0.146742E+10 | 0.114217E+10 | 0.117336E+10 | 0.782797E+09 | 0.390560E+09 | 0.00 | 0.00 |
March | 0.164599E+10 | 0.836067E+09 | 0.118792E+10 | 0.623368E+09 | 0.564555E+09 | 0.00 | 0.00 |
April | 0.134267E+10 | 0.648085E+09 | 0.865158E+09 | 0.288646E+09 | 0.576512E+09 | 0.00 | 0.00 |
May | 0.118543E+10 | 0.427947E+09 | 0.718628E+09 | 87942952.17 | 0.630685E+09 | 0.00 | 0.00 |
June | 0.122890E+10 | 0.250589E+09 | 0.638554E+09 | 35650458.33 | 0.602904E+09 | 0.00 | 0.00 |
July | 0.134203E+10 | 0.166973E+09 | 0.661899E+09 | 44646457.89 | 0.617253E+09 | 0.00 | 0.00 |
August | 0.162696E+10 | 0.135759E+09 | 0.797559E+09 | 0.149894E+09 | 0.647665E+09 | 0.00 | 0.00 |
September | 0.152142E+10 | 0.337002E+09 | 0.871397E+09 | 0.339052E+09 | 0.532345E+09 | 0.00 | 0.00 |
October | 0.190375E+10 | 0.759829E+09 | 0.126439E+10 | 0.817230E+09 | 0.447163E+09 | 0.00 | 0.00 |
November | 0.181122E+10 | 0.976395E+09 | 0.133685E+10 | 0.892082E+09 | 0.444765E+09 | 0.00 | 0.00 |
December | 0.170486E+10 | 0.126505E+10 | 0.138477E+10 | 0.974137E+09 | 0.410633E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.183836E+11 | 0.845755E+10 | 0.122951E+11 | 0.600423E+10 | 0.629084E+10 | 0.00 | 0.00 |
Minimum of Months | 0.118543E+10 | 0.135759E+09 | 0.638554E+09 | 35650458.33 | 0.390560E+09 | 0.00 | 0.00 |
Maximum of Months | 0.190375E+10 | 0.151169E+10 | 0.139459E+10 | 0.974137E+09 | 0.647665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.450903E+10 | 0.433016E+10 | 0.392706E+10 | 0.272803E+10 | 0.119904E+10 | 0.00 | 0.00 |
February | 0.414220E+10 | 0.326903E+10 | 0.330410E+10 | 0.220430E+10 | 0.109979E+10 | 0.00 | 0.00 |
March | 0.470942E+10 | 0.232575E+10 | 0.334511E+10 | 0.175536E+10 | 0.158975E+10 | 0.00 | 0.00 |
April | 0.390364E+10 | 0.174593E+10 | 0.243623E+10 | 0.812809E+09 | 0.162342E+10 | 0.00 | 0.00 |
May | 0.354577E+10 | 0.108683E+10 | 0.202361E+10 | 0.247642E+09 | 0.177597E+10 | 0.00 | 0.00 |
June | 0.372946E+10 | 0.594004E+09 | 0.179813E+10 | 0.100389E+09 | 0.169774E+10 | 0.00 | 0.00 |
July | 0.405673E+10 | 0.374560E+09 | 0.186386E+10 | 0.125721E+09 | 0.173814E+10 | 0.00 | 0.00 |
August | 0.483084E+10 | 0.292600E+09 | 0.224587E+10 | 0.422090E+09 | 0.182378E+10 | 0.00 | 0.00 |
September | 0.445619E+10 | 0.836596E+09 | 0.245380E+10 | 0.954749E+09 | 0.149905E+10 | 0.00 | 0.00 |
October | 0.544648E+10 | 0.208276E+10 | 0.356045E+10 | 0.230127E+10 | 0.125918E+10 | 0.00 | 0.00 |
November | 0.513732E+10 | 0.274871E+10 | 0.376447E+10 | 0.251204E+10 | 0.125243E+10 | 0.00 | 0.00 |
December | 0.480524E+10 | 0.362325E+10 | 0.389942E+10 | 0.274311E+10 | 0.115631E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.532723E+11 | 0.233102E+11 | 0.346221E+11 | 0.169075E+11 | 0.177146E+11 | 0.00 | 0.00 |
Minimum of Months | 0.354577E+10 | 0.292600E+09 | 0.179813E+10 | 0.100389E+09 | 0.109979E+10 | 0.00 | 0.00 |
Maximum of Months | 0.544648E+10 | 0.433016E+10 | 0.392706E+10 | 0.274311E+10 | 0.182378E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.592757E+10 | 0.595064E+10 | 0.510148E+10 | 0.354386E+10 | 0.155762E+10 | 0.00 | 0.00 |
February | 0.544846E+10 | 0.450856E+10 | 0.429221E+10 | 0.286352E+10 | 0.142869E+10 | 0.00 | 0.00 |
March | 0.617106E+10 | 0.325045E+10 | 0.434549E+10 | 0.228032E+10 | 0.206517E+10 | 0.00 | 0.00 |
April | 0.508437E+10 | 0.247867E+10 | 0.316480E+10 | 0.105589E+10 | 0.210891E+10 | 0.00 | 0.00 |
May | 0.457409E+10 | 0.158687E+10 | 0.262878E+10 | 0.321700E+09 | 0.230708E+10 | 0.00 | 0.00 |
June | 0.479268E+10 | 0.888729E+09 | 0.233587E+10 | 0.130411E+09 | 0.220546E+10 | 0.00 | 0.00 |
July | 0.522346E+10 | 0.576996E+09 | 0.242127E+10 | 0.163319E+09 | 0.225795E+10 | 0.00 | 0.00 |
August | 0.627842E+10 | 0.445134E+09 | 0.291752E+10 | 0.548319E+09 | 0.236920E+10 | 0.00 | 0.00 |
September | 0.579122E+10 | 0.123293E+10 | 0.318762E+10 | 0.124027E+10 | 0.194735E+10 | 0.00 | 0.00 |
October | 0.713987E+10 | 0.293556E+10 | 0.462523E+10 | 0.298948E+10 | 0.163575E+10 | 0.00 | 0.00 |
November | 0.672902E+10 | 0.383841E+10 | 0.489026E+10 | 0.326329E+10 | 0.162698E+10 | 0.00 | 0.00 |
December | 0.630363E+10 | 0.502535E+10 | 0.506557E+10 | 0.356345E+10 | 0.150212E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.694639E+11 | 0.327183E+11 | 0.449761E+11 | 0.219638E+11 | 0.230123E+11 | 0.00 | 0.00 |
Minimum of Months | 0.457409E+10 | 0.445134E+09 | 0.233587E+10 | 0.130411E+09 | 0.142869E+10 | 0.00 | 0.00 |
Maximum of Months | 0.713987E+10 | 0.595064E+10 | 0.510148E+10 | 0.356345E+10 | 0.236920E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.448307E+09 | 0.895184E+09 | 0.495584E+09 | 0.293769E+09 | 0.201815E+09 | 0.00 | 0.00 |
February | 0.497749E+09 | 0.660680E+09 | 0.459494E+09 | 0.261398E+09 | 0.198096E+09 | 0.00 | 0.00 |
March | 0.796569E+09 | 0.444632E+09 | 0.604404E+09 | 0.301473E+09 | 0.302931E+09 | 0.00 | 0.00 |
April | 0.873512E+09 | 0.324503E+09 | 0.574032E+09 | 0.241382E+09 | 0.332650E+09 | 0.00 | 0.00 |
May | 0.946690E+09 | 0.186876E+09 | 0.561070E+09 | 0.176409E+09 | 0.384661E+09 | 0.00 | 0.00 |
June | 0.107888E+10 | 84117958.25 | 0.552243E+09 | 0.171073E+09 | 0.381170E+09 | 0.00 | 0.00 |
July | 0.112434E+10 | 41263288.23 | 0.545206E+09 | 0.162083E+09 | 0.383122E+09 | 0.00 | 0.00 |
August | 0.117415E+10 | 20743903.89 | 0.564675E+09 | 0.181855E+09 | 0.382820E+09 | 0.00 | 0.00 |
September | 0.877628E+09 | 0.125557E+09 | 0.494046E+09 | 0.201546E+09 | 0.292500E+09 | 0.00 | 0.00 |
October | 0.801290E+09 | 0.386039E+09 | 0.545822E+09 | 0.315392E+09 | 0.230431E+09 | 0.00 | 0.00 |
November | 0.610300E+09 | 0.539423E+09 | 0.491695E+09 | 0.278059E+09 | 0.213635E+09 | 0.00 | 0.00 |
December | 0.473099E+09 | 0.732359E+09 | 0.468395E+09 | 0.277848E+09 | 0.190547E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.970253E+10 | 0.444138E+10 | 0.635667E+10 | 0.286229E+10 | 0.349438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.448307E+09 | 20743903.89 | 0.459494E+09 | 0.162083E+09 | 0.190547E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117415E+10 | 0.895184E+09 | 0.604404E+09 | 0.315392E+09 | 0.384661E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.171643E+09 | 0.966888E+09 | 0.271782E+09 | 0.102224E+09 | 0.169558E+09 | 0.00 | 0.00 |
February | 0.256057E+09 | 0.707005E+09 | 0.279492E+09 | 0.106626E+09 | 0.172866E+09 | 0.00 | 0.00 |
March | 0.540758E+09 | 0.458381E+09 | 0.450364E+09 | 0.178224E+09 | 0.272140E+09 | 0.00 | 0.00 |
April | 0.718955E+09 | 0.334111E+09 | 0.497825E+09 | 0.184866E+09 | 0.312959E+09 | 0.00 | 0.00 |
May | 0.876263E+09 | 0.195714E+09 | 0.535925E+09 | 0.162689E+09 | 0.373236E+09 | 0.00 | 0.00 |
June | 0.105746E+10 | 86629329.40 | 0.550455E+09 | 0.172187E+09 | 0.378268E+09 | 0.00 | 0.00 |
July | 0.109051E+10 | 45331939.49 | 0.536142E+09 | 0.159497E+09 | 0.376645E+09 | 0.00 | 0.00 |
August | 0.106482E+10 | 23082248.72 | 0.515169E+09 | 0.153489E+09 | 0.361680E+09 | 0.00 | 0.00 |
September | 0.696534E+09 | 0.135434E+09 | 0.400785E+09 | 0.134540E+09 | 0.266245E+09 | 0.00 | 0.00 |
October | 0.490018E+09 | 0.402278E+09 | 0.357879E+09 | 0.153811E+09 | 0.204068E+09 | 0.00 | 0.00 |
November | 0.305561E+09 | 0.567322E+09 | 0.281117E+09 | 0.101680E+09 | 0.179438E+09 | 0.00 | 0.00 |
December | 0.180951E+09 | 0.786965E+09 | 0.242610E+09 | 85244676.27 | 0.157365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.744952E+10 | 0.470914E+10 | 0.491954E+10 | 0.169508E+10 | 0.322447E+10 | 0.00 | 0.00 |
Minimum of Months | 0.171643E+09 | 23082248.72 | 0.242610E+09 | 85244676.27 | 0.157365E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109051E+10 | 0.966888E+09 | 0.550455E+09 | 0.184866E+09 | 0.378268E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.243041E+09 | 0.263858E+09 | 0.220544E+09 | 0.153205E+09 | 67338165.69 | 0.00 | 0.00 |
February | 0.214470E+09 | 0.225322E+09 | 0.185558E+09 | 0.123793E+09 | 61764600.87 | 0.00 | 0.00 |
March | 0.229449E+09 | 0.189496E+09 | 0.187862E+09 | 98580876.18 | 89280789.68 | 0.00 | 0.00 |
April | 0.183877E+09 | 0.149740E+09 | 0.136819E+09 | 45647216.27 | 91171836.45 | 0.00 | 0.00 |
May | 0.160095E+09 | 0.104026E+09 | 0.113647E+09 | 13907499.81 | 99739018.35 | 0.00 | 0.00 |
June | 0.170998E+09 | 63305668.81 | 0.100984E+09 | 5637845.11 | 95345682.42 | 0.00 | 0.00 |
July | 0.188500E+09 | 48037956.87 | 0.104675E+09 | 7060493.07 | 97614864.41 | 0.00 | 0.00 |
August | 0.234566E+09 | 41593922.25 | 0.126129E+09 | 23704513.72 | 0.102424E+09 | 0.00 | 0.00 |
September | 0.218356E+09 | 85306955.11 | 0.137805E+09 | 53618484.76 | 84186968.45 | 0.00 | 0.00 |
October | 0.276092E+09 | 0.172093E+09 | 0.199955E+09 | 0.129239E+09 | 70716109.13 | 0.00 | 0.00 |
November | 0.258565E+09 | 0.216579E+09 | 0.211412E+09 | 0.141076E+09 | 70336596.60 | 0.00 | 0.00 |
December | 0.244286E+09 | 0.264204E+09 | 0.218991E+09 | 0.154052E+09 | 64938803.63 | 0.00 | 0.00 |
Annual Sum or Average | 0.262230E+10 | 0.182356E+10 | 0.194438E+10 | 0.949522E+09 | 0.994858E+09 | 0.00 | 0.00 |
Minimum of Months | 0.160095E+09 | 41593922.25 | 0.100984E+09 | 5637845.11 | 61764600.87 | 0.00 | 0.00 |
Maximum of Months | 0.276092E+09 | 0.264204E+09 | 0.220544E+09 | 0.154052E+09 | 0.102424E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5905196.66 | 0.301417E+09 | 41551553.01 | 0.00 | 41551553.01 | 0.00 | 0.00 |
February | 19988764.84 | 0.216248E+09 | 41598843.56 | 0.00 | 41598843.56 | 0.00 | 0.00 |
March | 53679300.75 | 0.131860E+09 | 64675677.25 | 1302.53 | 64674374.72 | 0.00 | 0.00 |
April | 98700911.65 | 91730140.26 | 75890171.00 | 443230.81 | 75446940.19 | 0.00 | 0.00 |
May | 0.154045E+09 | 50189374.79 | 93565486.34 | 2934532.86 | 90630953.48 | 0.00 | 0.00 |
June | 0.212694E+09 | 20481898.75 | 99586189.44 | 6530819.87 | 93055369.57 | 0.00 | 0.00 |
July | 0.225128E+09 | 10235517.43 | 97458282.54 | 4993888.19 | 92464394.35 | 0.00 | 0.00 |
August | 0.209794E+09 | 4381074.59 | 86561042.70 | 1016922.46 | 85544120.25 | 0.00 | 0.00 |
September | 0.116880E+09 | 35227721.49 | 63232448.32 | 24856.94 | 63207591.38 | 0.00 | 0.00 |
October | 54965019.54 | 0.114124E+09 | 49646343.09 | 0.00 | 49646343.09 | 0.00 | 0.00 |
November | 27690305.22 | 0.166777E+09 | 42998364.49 | 0.00 | 42998364.49 | 0.00 | 0.00 |
December | 7491892.91 | 0.239859E+09 | 38411318.30 | 0.00 | 38411318.30 | 0.00 | 0.00 |
Annual Sum or Average | 0.118696E+10 | 0.138253E+10 | 0.795176E+09 | 15945553.66 | 0.779230E+09 | 0.00 | 0.00 |
Minimum of Months | 5905196.66 | 4381074.59 | 38411318.30 | 0.00 | 38411318.30 | 0.00 | 0.00 |
Maximum of Months | 0.225128E+09 | 0.301417E+09 | 99586189.44 | 6530819.87 | 93055369.57 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.427172E+09 | 0.882331E+09 | 0.490293E+09 | 0.289237E+09 | 0.201056E+09 | 0.00 | 0.00 |
February | 0.507496E+09 | 0.645915E+09 | 0.475216E+09 | 0.285702E+09 | 0.189513E+09 | 0.00 | 0.00 |
March | 0.722199E+09 | 0.423316E+09 | 0.573667E+09 | 0.277790E+09 | 0.295877E+09 | 0.00 | 0.00 |
April | 0.838219E+09 | 0.301777E+09 | 0.567384E+09 | 0.237968E+09 | 0.329416E+09 | 0.00 | 0.00 |
May | 0.978797E+09 | 0.173216E+09 | 0.590725E+09 | 0.207113E+09 | 0.383612E+09 | 0.00 | 0.00 |
June | 0.110973E+10 | 76801458.90 | 0.575320E+09 | 0.195140E+09 | 0.380181E+09 | 0.00 | 0.00 |
July | 0.118388E+10 | 39720220.30 | 0.583158E+09 | 0.198584E+09 | 0.384575E+09 | 0.00 | 0.00 |
August | 0.118741E+10 | 19561801.28 | 0.572237E+09 | 0.194075E+09 | 0.378163E+09 | 0.00 | 0.00 |
September | 0.884703E+09 | 0.120042E+09 | 0.501078E+09 | 0.212314E+09 | 0.288763E+09 | 0.00 | 0.00 |
October | 0.774720E+09 | 0.370515E+09 | 0.540578E+09 | 0.312833E+09 | 0.227745E+09 | 0.00 | 0.00 |
November | 0.586267E+09 | 0.521611E+09 | 0.488280E+09 | 0.277407E+09 | 0.210873E+09 | 0.00 | 0.00 |
December | 0.467466E+09 | 0.716834E+09 | 0.474623E+09 | 0.284021E+09 | 0.190602E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.966806E+10 | 0.429164E+10 | 0.643256E+10 | 0.297218E+10 | 0.346038E+10 | 0.00 | 0.00 |
Minimum of Months | 0.427172E+09 | 19561801.28 | 0.474623E+09 | 0.194075E+09 | 0.189513E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118741E+10 | 0.882331E+09 | 0.590725E+09 | 0.312833E+09 | 0.384575E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.132916E+09 | 0.935613E+09 | 0.266491E+09 | 97692218.39 | 0.168799E+09 | 0.00 | 0.00 |
February | 0.242889E+09 | 0.667841E+09 | 0.295214E+09 | 0.130930E+09 | 0.164284E+09 | 0.00 | 0.00 |
March | 0.458411E+09 | 0.424160E+09 | 0.419627E+09 | 0.154541E+09 | 0.265086E+09 | 0.00 | 0.00 |
April | 0.684265E+09 | 0.308959E+09 | 0.491176E+09 | 0.181452E+09 | 0.309724E+09 | 0.00 | 0.00 |
May | 0.910260E+09 | 0.184309E+09 | 0.565580E+09 | 0.193393E+09 | 0.372187E+09 | 0.00 | 0.00 |
June | 0.108697E+10 | 82215372.28 | 0.573532E+09 | 0.196253E+09 | 0.377279E+09 | 0.00 | 0.00 |
July | 0.114606E+10 | 44901387.02 | 0.574095E+09 | 0.195998E+09 | 0.378097E+09 | 0.00 | 0.00 |
August | 0.107522E+10 | 21849684.66 | 0.522732E+09 | 0.165709E+09 | 0.357023E+09 | 0.00 | 0.00 |
September | 0.699941E+09 | 0.128528E+09 | 0.407817E+09 | 0.145309E+09 | 0.262508E+09 | 0.00 | 0.00 |
October | 0.453562E+09 | 0.374190E+09 | 0.352634E+09 | 0.151252E+09 | 0.201382E+09 | 0.00 | 0.00 |
November | 0.258884E+09 | 0.522326E+09 | 0.277703E+09 | 0.101027E+09 | 0.176676E+09 | 0.00 | 0.00 |
December | 0.142747E+09 | 0.737532E+09 | 0.248838E+09 | 91417601.72 | 0.157420E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.729213E+10 | 0.443242E+10 | 0.499544E+10 | 0.180497E+10 | 0.319046E+10 | 0.00 | 0.00 |
Minimum of Months | 0.132916E+09 | 21849684.66 | 0.248838E+09 | 91417601.72 | 0.157420E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114606E+10 | 0.935613E+09 | 0.574095E+09 | 0.196253E+09 | 0.378097E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.481904E+09 | 0.114016E+10 | 0.567871E+09 | 0.331954E+09 | 0.235918E+09 | 0.00 | 0.00 |
February | 0.503979E+09 | 0.840606E+09 | 0.492169E+09 | 0.268226E+09 | 0.223944E+09 | 0.00 | 0.00 |
March | 0.688022E+09 | 0.568446E+09 | 0.547153E+09 | 0.213600E+09 | 0.333553E+09 | 0.00 | 0.00 |
April | 0.690717E+09 | 0.427673E+09 | 0.460852E+09 | 99865010.13 | 0.360987E+09 | 0.00 | 0.00 |
May | 0.762146E+09 | 0.255480E+09 | 0.448935E+09 | 36490866.73 | 0.412444E+09 | 0.00 | 0.00 |
June | 0.897536E+09 | 0.131851E+09 | 0.434540E+09 | 26363588.28 | 0.408177E+09 | 0.00 | 0.00 |
July | 0.954965E+09 | 83690081.85 | 0.437930E+09 | 26116561.42 | 0.411813E+09 | 0.00 | 0.00 |
August | 0.101581E+10 | 56971371.24 | 0.460806E+09 | 53564084.25 | 0.407242E+09 | 0.00 | 0.00 |
September | 0.789264E+09 | 0.196456E+09 | 0.435569E+09 | 0.116230E+09 | 0.319339E+09 | 0.00 | 0.00 |
October | 0.779683E+09 | 0.505500E+09 | 0.540797E+09 | 0.280024E+09 | 0.260773E+09 | 0.00 | 0.00 |
November | 0.673126E+09 | 0.673705E+09 | 0.551221E+09 | 0.305672E+09 | 0.245549E+09 | 0.00 | 0.00 |
December | 0.550056E+09 | 0.922287E+09 | 0.557704E+09 | 0.333788E+09 | 0.223916E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.878721E+10 | 0.580283E+10 | 0.593555E+10 | 0.209189E+10 | 0.384365E+10 | 0.00 | 0.00 |
Minimum of Months | 0.481904E+09 | 56971371.24 | 0.434540E+09 | 26116561.42 | 0.223916E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101581E+10 | 0.114016E+10 | 0.567871E+09 | 0.333788E+09 | 0.412444E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.448248E+09 | 0.890121E+09 | 0.495584E+09 | 0.293769E+09 | 0.201815E+09 | 0.00 | 0.00 |
February | 0.495745E+09 | 0.655430E+09 | 0.459494E+09 | 0.261398E+09 | 0.198096E+09 | 0.00 | 0.00 |
March | 0.789366E+09 | 0.439001E+09 | 0.604404E+09 | 0.301473E+09 | 0.302931E+09 | 0.00 | 0.00 |
April | 0.864661E+09 | 0.320413E+09 | 0.574032E+09 | 0.241382E+09 | 0.332650E+09 | 0.00 | 0.00 |
May | 0.936461E+09 | 0.183656E+09 | 0.561070E+09 | 0.176409E+09 | 0.384661E+09 | 0.00 | 0.00 |
June | 0.107050E+10 | 80600277.88 | 0.552243E+09 | 0.171073E+09 | 0.381170E+09 | 0.00 | 0.00 |
July | 0.111702E+10 | 38349124.45 | 0.545206E+09 | 0.162083E+09 | 0.383122E+09 | 0.00 | 0.00 |
August | 0.116693E+10 | 18421019.43 | 0.564675E+09 | 0.181855E+09 | 0.382820E+09 | 0.00 | 0.00 |
September | 0.871662E+09 | 0.120893E+09 | 0.494046E+09 | 0.201546E+09 | 0.292500E+09 | 0.00 | 0.00 |
October | 0.795899E+09 | 0.379079E+09 | 0.545822E+09 | 0.315392E+09 | 0.230431E+09 | 0.00 | 0.00 |
November | 0.607784E+09 | 0.533067E+09 | 0.491695E+09 | 0.278059E+09 | 0.213635E+09 | 0.00 | 0.00 |
December | 0.473065E+09 | 0.725493E+09 | 0.468395E+09 | 0.277848E+09 | 0.190547E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.963734E+10 | 0.438452E+10 | 0.635667E+10 | 0.286229E+10 | 0.349438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.448248E+09 | 18421019.43 | 0.459494E+09 | 0.162083E+09 | 0.190547E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116693E+10 | 0.890121E+09 | 0.604404E+09 | 0.315392E+09 | 0.384661E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.172859E+09 | 0.962279E+09 | 0.271782E+09 | 0.102224E+09 | 0.169558E+09 | 0.00 | 0.00 |
February | 0.255825E+09 | 0.701632E+09 | 0.279492E+09 | 0.106626E+09 | 0.172866E+09 | 0.00 | 0.00 |
March | 0.536600E+09 | 0.452693E+09 | 0.450364E+09 | 0.178224E+09 | 0.272140E+09 | 0.00 | 0.00 |
April | 0.710853E+09 | 0.332423E+09 | 0.497825E+09 | 0.184866E+09 | 0.312959E+09 | 0.00 | 0.00 |
May | 0.865838E+09 | 0.194788E+09 | 0.535925E+09 | 0.162689E+09 | 0.373236E+09 | 0.00 | 0.00 |
June | 0.104950E+10 | 83839441.02 | 0.550455E+09 | 0.172187E+09 | 0.378268E+09 | 0.00 | 0.00 |
July | 0.108366E+10 | 42806133.66 | 0.536142E+09 | 0.159497E+09 | 0.376645E+09 | 0.00 | 0.00 |
August | 0.105871E+10 | 20632591.38 | 0.515169E+09 | 0.153489E+09 | 0.361680E+09 | 0.00 | 0.00 |
September | 0.692116E+09 | 0.130814E+09 | 0.400785E+09 | 0.134540E+09 | 0.266245E+09 | 0.00 | 0.00 |
October | 0.487933E+09 | 0.395033E+09 | 0.357879E+09 | 0.153811E+09 | 0.204068E+09 | 0.00 | 0.00 |
November | 0.306430E+09 | 0.559064E+09 | 0.281117E+09 | 0.101680E+09 | 0.179438E+09 | 0.00 | 0.00 |
December | 0.183633E+09 | 0.778830E+09 | 0.242610E+09 | 85244676.27 | 0.157365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.740395E+10 | 0.465483E+10 | 0.491954E+10 | 0.169508E+10 | 0.322447E+10 | 0.00 | 0.00 |
Minimum of Months | 0.172859E+09 | 20632591.38 | 0.242610E+09 | 85244676.27 | 0.157365E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108366E+10 | 0.962279E+09 | 0.550455E+09 | 0.184866E+09 | 0.378268E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.448650E+09 | 0.460941E+09 | 0.404391E+09 | 0.280919E+09 | 0.123472E+09 | 0.00 | 0.00 |
February | 0.414080E+09 | 0.341856E+09 | 0.340241E+09 | 0.226989E+09 | 0.113252E+09 | 0.00 | 0.00 |
March | 0.472298E+09 | 0.228672E+09 | 0.344465E+09 | 0.180759E+09 | 0.163706E+09 | 0.00 | 0.00 |
April | 0.394026E+09 | 0.165739E+09 | 0.250873E+09 | 83699171.49 | 0.167174E+09 | 0.00 | 0.00 |
May | 0.362415E+09 | 91471011.32 | 0.208383E+09 | 25500924.42 | 0.182882E+09 | 0.00 | 0.00 |
June | 0.396805E+09 | 38367518.62 | 0.185164E+09 | 10337606.61 | 0.174827E+09 | 0.00 | 0.00 |
July | 0.438304E+09 | 17579755.68 | 0.191934E+09 | 12946187.50 | 0.178988E+09 | 0.00 | 0.00 |
August | 0.523461E+09 | 8001264.39 | 0.231271E+09 | 43464822.63 | 0.187806E+09 | 0.00 | 0.00 |
September | 0.464418E+09 | 60745469.31 | 0.252681E+09 | 98315365.50 | 0.154366E+09 | 0.00 | 0.00 |
October | 0.555811E+09 | 0.196343E+09 | 0.366639E+09 | 0.236973E+09 | 0.129666E+09 | 0.00 | 0.00 |
November | 0.519698E+09 | 0.276818E+09 | 0.387648E+09 | 0.258678E+09 | 0.128970E+09 | 0.00 | 0.00 |
December | 0.480984E+09 | 0.378245E+09 | 0.401544E+09 | 0.282472E+09 | 0.119072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.547095E+10 | 0.226478E+10 | 0.356523E+10 | 0.174105E+10 | 0.182418E+10 | 0.00 | 0.00 |
Minimum of Months | 0.362415E+09 | 8001264.39 | 0.185164E+09 | 10337606.61 | 0.113252E+09 | 0.00 | 0.00 |
Maximum of Months | 0.555811E+09 | 0.460941E+09 | 0.404391E+09 | 0.282472E+09 | 0.187806E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 42600656.51 | 0.286706E+10 | 0.363514E+09 | 0.00 | 0.363514E+09 | 0.00 | 0.00 |
February | 0.153571E+09 | 0.208835E+10 | 0.363928E+09 | 0.00 | 0.363928E+09 | 0.00 | 0.00 |
March | 0.419219E+09 | 0.134271E+10 | 0.565816E+09 | 11395.24 | 0.565804E+09 | 0.00 | 0.00 |
April | 0.815323E+09 | 0.953515E+09 | 0.663926E+09 | 3877608.68 | 0.660048E+09 | 0.00 | 0.00 |
May | 0.129066E+10 | 0.578815E+09 | 0.818558E+09 | 25672786.98 | 0.792886E+09 | 0.00 | 0.00 |
June | 0.177282E+10 | 0.302861E+09 | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.00 | 0.00 |
July | 0.185855E+10 | 0.196213E+09 | 0.852615E+09 | 43689075.52 | 0.808926E+09 | 0.00 | 0.00 |
August | 0.170546E+10 | 0.142064E+09 | 0.757280E+09 | 8896555.21 | 0.748384E+09 | 0.00 | 0.00 |
September | 0.968581E+09 | 0.442420E+09 | 0.553190E+09 | 217461.16 | 0.552972E+09 | 0.00 | 0.00 |
October | 0.441299E+09 | 0.117824E+10 | 0.434331E+09 | 0.00 | 0.434331E+09 | 0.00 | 0.00 |
November | 0.208663E+09 | 0.164453E+10 | 0.376172E+09 | 0.00 | 0.376172E+09 | 0.00 | 0.00 |
December | 48406778.72 | 0.231795E+10 | 0.336042E+09 | 0.00 | 0.336042E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.972515E+10 | 0.140547E+11 | 0.695660E+10 | 0.139500E+09 | 0.681710E+10 | 0.00 | 0.00 |
Minimum of Months | 42600656.51 | 0.142064E+09 | 0.336042E+09 | 0.00 | 0.336042E+09 | 0.00 | 0.00 |
Maximum of Months | 0.185855E+10 | 0.286706E+10 | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 37523579.59 | 0.296651E+10 | 0.363514E+09 | 0.00 | 0.363514E+09 | 0.00 | 0.00 |
February | 0.141994E+09 | 0.217044E+10 | 0.363928E+09 | 0.00 | 0.363928E+09 | 0.00 | 0.00 |
March | 0.391068E+09 | 0.140653E+10 | 0.565816E+09 | 11395.24 | 0.565804E+09 | 0.00 | 0.00 |
April | 0.782155E+09 | 0.995829E+09 | 0.663926E+09 | 3877608.68 | 0.660048E+09 | 0.00 | 0.00 |
May | 0.125180E+10 | 0.609577E+09 | 0.818558E+09 | 25672786.98 | 0.792886E+09 | 0.00 | 0.00 |
June | 0.172978E+10 | 0.324342E+09 | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.00 | 0.00 |
July | 0.181321E+10 | 0.214935E+09 | 0.852615E+09 | 43689075.52 | 0.808926E+09 | 0.00 | 0.00 |
August | 0.166130E+10 | 0.160967E+09 | 0.757280E+09 | 8896555.21 | 0.748384E+09 | 0.00 | 0.00 |
September | 0.935053E+09 | 0.474035E+09 | 0.553190E+09 | 217461.16 | 0.552972E+09 | 0.00 | 0.00 |
October | 0.417568E+09 | 0.123510E+10 | 0.434331E+09 | 0.00 | 0.434331E+09 | 0.00 | 0.00 |
November | 0.188364E+09 | 0.171924E+10 | 0.376172E+09 | 0.00 | 0.376172E+09 | 0.00 | 0.00 |
December | 40466229.26 | 0.241906E+10 | 0.336042E+09 | 0.00 | 0.336042E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.939029E+10 | 0.146966E+11 | 0.695660E+10 | 0.139500E+09 | 0.681710E+10 | 0.00 | 0.00 |
Minimum of Months | 37523579.59 | 0.160967E+09 | 0.336042E+09 | 0.00 | 0.336042E+09 | 0.00 | 0.00 |
Maximum of Months | 0.181321E+10 | 0.296651E+10 | 0.871231E+09 | 57134936.06 | 0.814096E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.512926E+09 | 0.205010E+10 | 0.756754E+09 | 0.386915E+09 | 0.369838E+09 | 0.00 | 0.00 |
February | 0.751083E+09 | 0.152466E+10 | 0.770395E+09 | 0.416614E+09 | 0.353782E+09 | 0.00 | 0.00 |
March | 0.127610E+10 | 0.103731E+10 | 0.993246E+09 | 0.432310E+09 | 0.560936E+09 | 0.00 | 0.00 |
April | 0.169358E+10 | 0.760071E+09 | 0.105850E+10 | 0.419394E+09 | 0.639109E+09 | 0.00 | 0.00 |
May | 0.212098E+10 | 0.501936E+09 | 0.115624E+10 | 0.400479E+09 | 0.755762E+09 | 0.00 | 0.00 |
June | 0.245060E+10 | 0.287326E+09 | 0.114879E+10 | 0.391366E+09 | 0.757422E+09 | 0.00 | 0.00 |
July | 0.259547E+10 | 0.198447E+09 | 0.115719E+10 | 0.394554E+09 | 0.762635E+09 | 0.00 | 0.00 |
August | 0.251756E+10 | 0.152172E+09 | 0.109491E+10 | 0.359761E+09 | 0.735150E+09 | 0.00 | 0.00 |
September | 0.179856E+10 | 0.366577E+09 | 0.908848E+09 | 0.357603E+09 | 0.551245E+09 | 0.00 | 0.00 |
October | 0.135557E+10 | 0.910059E+09 | 0.893171E+09 | 0.464063E+09 | 0.429108E+09 | 0.00 | 0.00 |
November | 0.901232E+09 | 0.122414E+10 | 0.765951E+09 | 0.378420E+09 | 0.387531E+09 | 0.00 | 0.00 |
December | 0.594017E+09 | 0.168005E+10 | 0.723432E+09 | 0.375426E+09 | 0.348007E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.185677E+11 | 0.106928E+11 | 0.114274E+11 | 0.477691E+10 | 0.665052E+10 | 0.00 | 0.00 |
Minimum of Months | 0.512926E+09 | 0.152172E+09 | 0.723432E+09 | 0.357603E+09 | 0.348007E+09 | 0.00 | 0.00 |
Maximum of Months | 0.259547E+10 | 0.205010E+10 | 0.115719E+10 | 0.464063E+09 | 0.762635E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105522E+10 | 0.203597E+10 | 0.115401E+10 | 0.715094E+09 | 0.438918E+09 | 0.00 | 0.00 |
February | 0.103962E+10 | 0.154220E+10 | 0.990856E+09 | 0.577812E+09 | 0.413045E+09 | 0.00 | 0.00 |
March | 0.129908E+10 | 0.111861E+10 | 0.107082E+10 | 0.460135E+09 | 0.610681E+09 | 0.00 | 0.00 |
April | 0.120971E+10 | 0.874427E+09 | 0.866205E+09 | 0.214390E+09 | 0.651815E+09 | 0.00 | 0.00 |
May | 0.124914E+10 | 0.563219E+09 | 0.811054E+09 | 73714639.91 | 0.737340E+09 | 0.00 | 0.00 |
June | 0.147543E+10 | 0.295853E+09 | 0.770005E+09 | 45900894.75 | 0.724104E+09 | 0.00 | 0.00 |
July | 0.159535E+10 | 0.194689E+09 | 0.780855E+09 | 47931908.78 | 0.732924E+09 | 0.00 | 0.00 |
August | 0.175982E+10 | 0.145161E+09 | 0.848309E+09 | 0.113692E+09 | 0.734618E+09 | 0.00 | 0.00 |
September | 0.141180E+10 | 0.433263E+09 | 0.832848E+09 | 0.250342E+09 | 0.582507E+09 | 0.00 | 0.00 |
October | 0.149943E+10 | 0.101351E+10 | 0.108219E+10 | 0.603228E+09 | 0.478961E+09 | 0.00 | 0.00 |
November | 0.134989E+10 | 0.128311E+10 | 0.111573E+10 | 0.658479E+09 | 0.457252E+09 | 0.00 | 0.00 |
December | 0.117185E+10 | 0.167394E+10 | 0.113735E+10 | 0.719047E+09 | 0.418301E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.161163E+11 | 0.111740E+11 | 0.114602E+11 | 0.447976E+10 | 0.698046E+10 | 0.00 | 0.00 |
Minimum of Months | 0.103962E+10 | 0.145161E+09 | 0.770005E+09 | 45900894.75 | 0.413045E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175982E+10 | 0.203597E+10 | 0.115401E+10 | 0.719047E+09 | 0.737340E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.117662E+12 | -0.115869E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179295E+10 | 82.17 | 0.00 | 0.00 |
February | 0.106427E+12 | -0.104794E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.163342E+10 | 82.17 | 0.00 | 0.00 |
March | 0.115277E+12 | -0.113452E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.182530E+10 | 82.17 | 0.00 | 0.00 |
April | 0.106966E+12 | -0.105189E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.177717E+10 | 82.17 | 0.00 | 0.00 |
May | 0.104874E+12 | -0.103045E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.182850E+10 | 82.17 | 0.00 | 0.00 |
June | 0.966056E+11 | -0.948609E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174467E+10 | 82.17 | 0.00 | 0.00 |
July | 0.967805E+11 | -0.949937E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178682E+10 | 82.17 | 0.00 | 0.00 |
August | 0.965487E+11 | -0.947787E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177006E+10 | 82.17 | 0.00 | 0.00 |
September | 0.960004E+11 | -0.942988E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170160E+10 | 82.17 | 0.00 | 0.00 |
October | 0.104012E+12 | -0.102256E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175641E+10 | 82.17 | 0.00 | 0.00 |
November | 0.106127E+12 | -0.104428E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169927E+10 | 82.17 | 0.00 | 0.00 |
December | 0.114643E+12 | -0.112881E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176292E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.126192E+13 | -0.124085E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210791E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.960004E+11 | -0.115869E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.182850E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.117662E+12 | -0.942988E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.163342E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804707E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164108860.4 | 82.17 | 0.00 | 0.00 |
February | 0.727159E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148227533.3 | 82.17 | 0.00 | 0.00 |
March | 0.804566E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164107360.6 | 82.17 | 0.00 | 0.00 |
April | 0.779700E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158793380.2 | 82.17 | 0.00 | 0.00 |
May | 0.804706E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164099925.3 | 82.17 | 0.00 | 0.00 |
June | 0.778857E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158807389.9 | 82.17 | 0.00 | 0.00 |
July | 0.805551E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164106824.1 | 82.17 | 0.00 | 0.00 |
August | 0.804707E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164106764.2 | 82.17 | 0.00 | 0.00 |
September | 0.779842E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158810538.0 | 82.17 | 0.00 | 0.00 |
October | 0.804566E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164108146.7 | 82.17 | 0.00 | 0.00 |
November | 0.778014E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158815131.9 | 82.17 | 0.00 | 0.00 |
December | 0.805551E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164109158.8 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947793E+11 | -0.928471E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193220E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727159E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164109158.8 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805551E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148227533.3 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.691501E+11 | -0.675889E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156116E+10 | 60.05 | 0.00 | 0.00 |
February | 0.626086E+11 | -0.611792E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.142947E+10 | 60.05 | 0.00 | 0.00 |
March | 0.671660E+11 | -0.655600E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.160601E+10 | 60.05 | 0.00 | 0.00 |
April | 0.610041E+11 | -0.594350E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.156910E+10 | 60.05 | 0.00 | 0.00 |
May | 0.581558E+11 | -0.565454E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.161044E+10 | 60.05 | 0.00 | 0.00 |
June | 0.520663E+11 | -0.505422E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152405E+10 | 60.05 | 0.00 | 0.00 |
July | 0.511145E+11 | -0.495619E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155266E+10 | 60.05 | 0.00 | 0.00 |
August | 0.509565E+11 | -0.494271E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152943E+10 | 60.05 | 0.00 | 0.00 |
September | 0.514979E+11 | -0.500336E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146434E+10 | 60.05 | 0.00 | 0.00 |
October | 0.573421E+11 | -0.558316E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151051E+10 | 60.05 | 0.00 | 0.00 |
November | 0.602147E+11 | -0.587536E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146112E+10 | 60.05 | 0.00 | 0.00 |
December | 0.665232E+11 | -0.650037E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151953E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.707800E+12 | -0.689462E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.183378E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.509565E+11 | -0.675889E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.161044E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.691501E+11 | -0.494271E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.142947E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.87 | 0.86 | 01-JAN-09:09 | 5249.07 | 34.02 | 271.17 | 275.67 | 809.35 | 25.49 | 166.00 | 246.00 |
February | 263.00 | 0.87 | 0.86 | 01-FEB-13:39 | 4656.01 | 30.85 | 192.00 | 250.00 | 570.23 | 21.88 | 110.17 | 205.00 |
March | 351.67 | 0.87 | 0.86 | 01-MAR-08:50 | 1153.27 | 19.53 | 11.17 | 322.17 | 443.53 | 20.94 | 161.00 | 256.83 |
April | 369.33 | 0.87 | 0.86 | 01-APR-08:30 | 922.31 | 19.03 | 0.00 | 328.33 | 365.46 | 20.76 | 149.50 | 250.17 |
May | 407.00 | 0.87 | 0.86 | 01-MAY-07:49 | 873.68 | 18.99 | 0.00 | 362.67 | 346.48 | 20.72 | 187.67 | 278.00 |
June | 411.67 | 0.87 | 0.86 | 01-JUN-07:19 | 806.51 | 18.76 | 0.00 | 363.50 | 324.41 | 20.50 | 172.50 | 260.83 |
July | 411.00 | 0.87 | 0.86 | 01-JUL-08:30 | 853.43 | 18.85 | 0.00 | 368.67 | 340.34 | 20.58 | 205.17 | 277.00 |
August | 390.50 | 0.87 | 0.86 | 01-AUG-07:40 | 1056.86 | 19.51 | 0.67 | 355.17 | 413.23 | 21.22 | 233.50 | 289.33 |
September | 298.50 | 0.87 | 0.86 | 01-SEP-07:49 | 1111.59 | 19.45 | 0.17 | 312.50 | 438.85 | 21.18 | 174.83 | 238.50 |
October | 293.50 | 0.87 | 0.86 | 01-OCT-10:39 | 2681.40 | 24.71 | 106.17 | 294.17 | 453.66 | 21.01 | 107.00 | 221.00 |
November | 299.00 | 0.87 | 0.86 | 01-NOV-08:30 | 5220.85 | 34.77 | 286.00 | 275.67 | 655.98 | 25.15 | 178.50 | 245.67 |
December | 285.17 | 0.87 | 0.86 | 01-DEC-07:00 | 4912.35 | 34.52 | 270.50 | 271.50 | 907.09 | 26.64 | 174.00 | 236.67 |
Annual Sum or Average | 4071.00 | 0.87 | 2217.69 | 23.58 | 1137.83 | 3780.00 | 484.14 | 21.96 | 2019.83 | 3005.00 | ||
Minimum of Months | 263.00 | 0.87 | 0.86 | 806.51 | 18.76 | 0.00 | 250.00 | 324.41 | 20.50 | 107.00 | 205.00 | |
Maximum of Months | 411.67 | 0.87 | 0.86 | 5249.07 | 34.77 | 286.00 | 368.67 | 907.09 | 26.64 | 233.50 | 289.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.24 | 0.22 | 01-JAN-08:00 | 5565.96 | 34.15 | 272.83 | 283.00 | 1125.55 | 25.40 | 176.17 | 265.50 |
February | 263.00 | 0.26 | 0.22 | 01-FEB-10:20 | 4957.35 | 30.95 | 193.17 | 260.83 | 870.96 | 21.95 | 110.17 | 226.17 |
March | 351.67 | 0.26 | 0.22 | 01-MAR-08:20 | 1398.59 | 19.97 | 32.67 | 334.00 | 688.05 | 21.23 | 179.50 | 301.17 |
April | 369.33 | 0.26 | 0.22 | 01-APR-07:00 | 1103.12 | 19.70 | 12.83 | 344.67 | 545.69 | 21.22 | 189.83 | 305.83 |
May | 407.00 | 0.26 | 0.22 | 01-MAY-07:10 | 1019.64 | 19.81 | 15.33 | 383.00 | 491.90 | 21.32 | 255.17 | 334.67 |
June | 411.67 | 0.26 | 0.22 | 01-JUN-06:49 | 940.08 | 19.62 | 10.83 | 382.83 | 457.49 | 21.14 | 240.17 | 336.17 |
July | 411.00 | 0.26 | 0.22 | 01-JUL-06:40 | 991.12 | 19.70 | 18.67 | 386.50 | 477.51 | 21.20 | 256.50 | 338.17 |
August | 390.50 | 0.25 | 0.22 | 01-AUG-06:00 | 1226.51 | 20.24 | 52.83 | 369.17 | 582.24 | 21.74 | 277.17 | 332.33 |
September | 298.50 | 0.26 | 0.22 | 01-SEP-07:10 | 1321.83 | 20.03 | 34.00 | 325.33 | 648.41 | 21.56 | 197.67 | 291.17 |
October | 293.50 | 0.26 | 0.22 | 01-OCT-07:00 | 2976.12 | 24.82 | 114.33 | 306.50 | 745.51 | 21.07 | 118.50 | 267.67 |
November | 299.00 | 0.25 | 0.22 | 01-NOV-07:00 | 5524.60 | 34.85 | 287.17 | 282.50 | 957.69 | 25.12 | 182.33 | 266.83 |
December | 285.17 | 0.24 | 0.22 | 01-DEC-07:49 | 5234.59 | 34.63 | 272.33 | 280.17 | 1227.09 | 26.56 | 180.50 | 259.67 |
Annual Sum or Average | 4071.00 | 0.26 | 2437.19 | 24.09 | 1317.00 | 3938.50 | 702.66 | 22.29 | 2363.67 | 3525.33 | ||
Minimum of Months | 263.00 | 0.24 | 0.22 | 940.08 | 19.62 | 10.83 | 260.83 | 457.49 | 21.07 | 110.17 | 226.17 | |
Maximum of Months | 411.67 | 0.26 | 0.22 | 5565.96 | 34.85 | 287.17 | 386.50 | 1227.09 | 26.56 | 277.17 | 338.17 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.67 | 0.60 | 01-JAN-10:00 | 329.20 | 14.06 | 0.00 | 212.83 | 152.64 | 17.48 | 0.00 | 56.67 |
February | 263.00 | 0.68 | 0.60 | 01-FEB-13:39 | 339.50 | 14.24 | 0.00 | 200.83 | 160.98 | 17.63 | 0.00 | 75.50 |
March | 351.67 | 0.64 | 0.60 | 01-MAR-08:00 | 439.69 | 15.76 | 0.00 | 315.67 | 205.17 | 19.01 | 0.00 | 174.83 |
April | 369.33 | 0.63 | 0.60 | 01-APR-08:30 | 534.57 | 16.66 | 0.00 | 341.67 | 243.39 | 19.86 | 6.33 | 226.67 |
May | 407.00 | 0.61 | 0.60 | 01-MAY-07:19 | 680.64 | 18.16 | 18.33 | 391.50 | 310.35 | 21.68 | 106.83 | 348.33 |
June | 411.67 | 0.61 | 0.60 | 01-JUN-06:30 | 756.99 | 19.76 | 55.67 | 393.67 | 347.48 | 23.17 | 185.83 | 366.83 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-05:00 | 769.25 | 18.68 | 27.50 | 395.00 | 336.08 | 22.54 | 173.67 | 355.67 |
August | 390.50 | 0.62 | 0.60 | 01-AUG-06:40 | 675.47 | 17.55 | 0.00 | 370.67 | 305.92 | 20.72 | 73.17 | 327.00 |
September | 298.50 | 0.63 | 0.60 | 01-SEP-07:30 | 494.94 | 16.49 | 0.00 | 316.00 | 232.62 | 19.67 | 0.00 | 204.00 |
October | 293.50 | 0.67 | 0.60 | 01-OCT-10:39 | 345.34 | 14.69 | 0.00 | 230.00 | 169.25 | 18.09 | 0.00 | 100.17 |
November | 299.00 | 0.66 | 0.60 | 01-NOV-09:50 | 340.60 | 14.31 | 0.00 | 242.17 | 160.46 | 17.68 | 0.00 | 58.17 |
December | 285.17 | 0.67 | 0.60 | 01-DEC-09:00 | 318.83 | 14.11 | 0.00 | 213.83 | 149.97 | 17.56 | 0.00 | 38.00 |
Annual Sum or Average | 4071.00 | 0.64 | 527.50 | 16.49 | 101.50 | 3623.83 | 242.09 | 19.88 | 545.83 | 2331.83 | ||
Minimum of Months | 263.00 | 0.61 | 0.60 | 318.83 | 14.06 | 0.00 | 200.83 | 149.97 | 17.48 | 0.00 | 38.00 | |
Maximum of Months | 411.67 | 0.68 | 0.60 | 769.25 | 19.76 | 55.67 | 395.00 | 347.48 | 23.17 | 185.83 | 366.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.67 | 0.60 | 01-JAN-10:00 | 329.20 | 14.06 | 0.00 | 212.83 | 152.64 | 17.48 | 0.00 | 56.67 |
February | 263.00 | 0.68 | 0.60 | 01-FEB-13:39 | 339.50 | 14.24 | 0.00 | 200.83 | 160.98 | 17.63 | 0.00 | 75.50 |
March | 351.67 | 0.64 | 0.60 | 01-MAR-08:00 | 439.69 | 15.76 | 0.00 | 315.67 | 205.17 | 19.01 | 0.00 | 174.83 |
April | 369.33 | 0.63 | 0.60 | 01-APR-08:30 | 534.57 | 16.66 | 0.00 | 341.67 | 243.39 | 19.86 | 6.33 | 226.67 |
May | 407.00 | 0.61 | 0.60 | 01-MAY-07:19 | 680.64 | 18.16 | 18.33 | 391.50 | 310.35 | 21.68 | 106.67 | 348.33 |
June | 411.67 | 0.61 | 0.60 | 01-JUN-06:30 | 756.99 | 19.76 | 55.67 | 393.67 | 347.48 | 23.17 | 185.83 | 366.83 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-05:00 | 769.25 | 18.68 | 27.50 | 395.00 | 336.08 | 22.54 | 173.67 | 355.67 |
August | 390.50 | 0.62 | 0.60 | 01-AUG-06:40 | 675.47 | 17.55 | 0.00 | 370.67 | 305.92 | 20.72 | 73.17 | 327.00 |
September | 298.50 | 0.63 | 0.60 | 01-SEP-07:30 | 494.94 | 16.49 | 0.00 | 316.00 | 232.62 | 19.67 | 0.00 | 204.00 |
October | 293.50 | 0.67 | 0.60 | 01-OCT-10:39 | 345.34 | 14.69 | 0.00 | 230.00 | 169.25 | 18.09 | 0.00 | 100.17 |
November | 299.00 | 0.66 | 0.60 | 01-NOV-09:50 | 340.60 | 14.31 | 0.00 | 242.17 | 160.46 | 17.68 | 0.00 | 58.17 |
December | 285.17 | 0.67 | 0.60 | 01-DEC-09:00 | 318.83 | 14.11 | 0.00 | 213.83 | 149.97 | 17.56 | 0.00 | 38.00 |
Annual Sum or Average | 4071.00 | 0.64 | 527.50 | 16.49 | 101.50 | 3623.83 | 242.09 | 19.88 | 545.67 | 2331.83 | ||
Minimum of Months | 263.00 | 0.61 | 0.60 | 318.83 | 14.06 | 0.00 | 200.83 | 149.97 | 17.48 | 0.00 | 38.00 | |
Maximum of Months | 411.67 | 0.68 | 0.60 | 769.25 | 19.76 | 55.67 | 395.00 | 347.48 | 23.17 | 185.83 | 366.83 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.680441E+09 | 4218.14 | 07-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.578344E+09 | 5201.21 | 12-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35395838.37 | 1148.21 | 22-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118520E+09 | 2084.25 | 18-DEC-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.680441E+09 | 5201.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.548495E+11 | 89957.24 | 10-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356248E+11 | 90062.71 | 11-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182441E+11 | 84542.00 | 19-MAR-06:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.815800E+10 | 85697.36 | 06-APR-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.495663E+09 | 44950.33 | 13-MAY-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193893E+09 | 42904.42 | 08-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109727E+09 | 15943.98 | 22-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.509493E+10 | 72643.83 | 26-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.263904E+11 | 91098.34 | 21-NOV-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.548781E+11 | 87865.45 | 09-DEC-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.548781E+11 | 91098.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2589488.35 | 1339.32 | 27-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171728E+10 | 5261.70 | 10-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86182393.79 | 3861.88 | 01-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171728E+10 | 5261.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121802E+10 | 1825.59 | 08-JAN-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.703466E+09 | 2082.05 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101434E+09 | 835.03 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32726690.84 | 678.58 | 06-APR-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 64123435.09 | 746.90 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140014E+09 | 1174.71 | 21-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.618805E+09 | 1342.63 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121802E+10 | 2082.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160444E+09 | 647.13 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95248570.08 | 550.52 | 13-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3884425.85 | 351.94 | 23-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 102369.86 | 95.74 | 06-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 559812.13 | 115.24 | 31-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 516201.38 | 157.30 | 22-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26530733.03 | 318.42 | 22-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.160444E+09 | 647.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 30836774.99 | 374.61 | 08-JAN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11178446.55 | 260.77 | 13-FEB-10:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42015221.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30836774.99 | 374.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125421E+10 | 885.31 | 08-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.742672E+09 | 891.50 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148062E+09 | 497.67 | 23-MAR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29264848.90 | 410.98 | 07-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17531412.85 | 295.27 | 26-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136716E+09 | 513.28 | 22-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.639860E+09 | 631.00 | 18-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125421E+10 | 891.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.246515E+10 | 6416.12 | 09-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166761E+10 | 5768.71 | 07-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.651217E+09 | 5025.57 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.366424E+09 | 3799.36 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153786E+09 | 2529.94 | 10-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35764893.63 | 2431.50 | 08-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15027336.06 | 2090.18 | 28-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1336973.72 | 1196.56 | 31-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82838778.99 | 3168.22 | 29-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.460187E+09 | 4864.93 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.534726E+09 | 4714.91 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142353E+10 | 4706.16 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.785760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1336973.72 | 1196.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246515E+10 | 6416.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111076E+10 | 10139.33 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.486345E+09 | 7744.18 | 06-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19122820.30 | 3109.55 | 23-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1773731.13 | 807.48 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1035359.37 | 646.14 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116997E+09 | 4245.37 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111076E+10 | 10139.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.691954E+10 | 7665.85 | 09-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.401036E+10 | 6569.29 | 12-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217858E+09 | 3847.63 | 23-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202487E+09 | 3819.53 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.734006E+09 | 4465.37 | 22-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387571E+10 | 5049.54 | 18-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.691954E+10 | 7665.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237334E+10 | 3540.73 | 08-JAN-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126622E+10 | 4082.89 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5989115.46 | 512.09 | 23-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112011E+09 | 1979.82 | 22-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.808867E+09 | 2646.74 | 18-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237334E+10 | 4082.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100866E+10 | 4491.73 | 27-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.558463E+09 | 4539.84 | 13-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50594766.43 | 3076.95 | 20-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15297715.13 | 2912.69 | 07-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 553788.68 | 495.71 | 11-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28856650.98 | 2932.41 | 26-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117482E+09 | 3298.39 | 22-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.454553E+09 | 3941.65 | 04-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100866E+10 | 4539.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.217268E+09 | 2845.19 | 27-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112203E+09 | 2882.34 | 13-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2008136.38 | 1195.73 | 20-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1347647.32 | 956.10 | 06-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1734116.07 | 1321.96 | 26-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4786025.70 | 1712.71 | 21-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36061957.13 | 2244.82 | 04-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.375409E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.217268E+09 | 2882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.369750E+10 | 5530.61 | 01-JAN-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.219604E+10 | 5530.61 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433480E+09 | 5530.61 | 18-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117821E+09 | 5530.61 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7398661.51 | 3879.23 | 11-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2814688.19 | 4302.51 | 02-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1572409.09 | 2360.36 | 28-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1014979.06 | 2530.96 | 25-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9514114.78 | 3431.85 | 01-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.295083E+09 | 5530.61 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.885843E+09 | 5530.61 | 20-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239320E+10 | 5530.61 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1014979.06 | 2360.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.369750E+10 | 5530.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.467815E+10 | 5540.37 | 01-JAN-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280797E+10 | 5540.37 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.583596E+09 | 5540.37 | 03-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133867E+09 | 5540.37 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5942669.18 | 4153.97 | 13-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1550171.51 | 2812.45 | 02-JUN-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 975760.32 | 1363.09 | 29-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 867295.56 | 1828.61 | 25-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5463520.44 | 3775.56 | 15-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377178E+09 | 5540.37 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133373E+10 | 5540.37 | 08-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322300E+10 | 5540.37 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 867295.56 | 1363.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.467815E+10 | 5540.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176750E+11 | 32058.98 | 01-JAN-22:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.995337E+10 | 32058.98 | 01-FEB-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116299E+10 | 32058.98 | 03-MAR-02:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.628916E+09 | 32058.98 | 05-APR-22:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36194837.58 | 22693.98 | 15-MAY-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9997021.26 | 14216.72 | 01-JUN-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3481847.93 | 8906.89 | 14-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1894063.15 | 8695.26 | 30-AUG-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26241043.93 | 26438.98 | 19-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.366916E+09 | 32058.98 | 25-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295005E+10 | 32058.98 | 07-NOV-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.933926E+10 | 32058.98 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1894063.15 | 8695.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176750E+11 | 32058.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.375796E+10 | 5510.49 | 01-JAN-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.219364E+10 | 5510.49 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.465505E+09 | 5510.49 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118411E+09 | 5510.49 | 06-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2715532.32 | 3204.39 | 26-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 208937.90 | 1311.13 | 23-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1175094.43 | 2206.13 | 28-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 444286.10 | 1470.10 | 24-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6280926.47 | 3277.01 | 30-SEP-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.306960E+09 | 5510.49 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.886016E+09 | 5510.49 | 20-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237178E+10 | 5510.49 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 208937.90 | 1311.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.375796E+10 | 5510.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.474223E+10 | 5520.26 | 01-JAN-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275701E+10 | 5520.26 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.612953E+09 | 5520.26 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138194E+09 | 4646.65 | 09-APR-20:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3459831.01 | 3903.02 | 10-MAY-21:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 325566.40 | 1837.26 | 08-JUN-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 364117.57 | 1284.10 | 28-JUL-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30405.40 | 414.81 | 30-AUG-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2886526.35 | 2850.86 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.401101E+09 | 5520.26 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131625E+10 | 5520.26 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318217E+10 | 5520.26 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 30405.40 | 414.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.474223E+10 | 5520.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136689E+10 | 1709.88 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.836191E+09 | 1709.88 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224569E+09 | 1709.88 | 03-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71022005.20 | 1709.88 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4587817.62 | 1171.18 | 24-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 939483.54 | 1039.75 | 02-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 639169.56 | 709.94 | 13-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 515895.63 | 930.33 | 25-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8087313.44 | 1150.12 | 28-SEP-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157736E+09 | 1709.88 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.400809E+09 | 1709.88 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.932278E+09 | 1709.88 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 515895.63 | 709.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136689E+10 | 1709.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167674E+10 | 1713.72 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103313E+10 | 1713.72 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.276259E+09 | 1713.72 | 03-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73040492.98 | 1713.72 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2073215.02 | 1025.81 | 13-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 690001.11 | 1077.03 | 07-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 224784.73 | 560.69 | 28-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 361675.92 | 626.50 | 30-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4395727.45 | 850.33 | 14-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193829E+09 | 1713.72 | 06-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.558774E+09 | 1713.72 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119769E+10 | 1713.72 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.501720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 224784.73 | 560.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167674E+10 | 1713.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.376293E+10 | 8208.50 | 01-JAN-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216380E+10 | 8208.50 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.453223E+09 | 8208.50 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194663E+09 | 8208.50 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12177366.23 | 4858.32 | 10-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3268658.97 | 4241.60 | 08-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3017208.47 | 3128.47 | 28-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2993151.16 | 2351.12 | 21-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19044050.39 | 4782.48 | 30-SEP-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271035E+09 | 8208.50 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.683083E+09 | 8208.50 | 08-NOV-00:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213114E+10 | 8208.50 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.970038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2993151.16 | 2351.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.376293E+10 | 8208.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.661161E+09 | 0.498469E+09 | 13220.25 | 19-JAN-22:53 | 7342.46 | 0.03 |
February | 0.00 | 0.00 | 0.183359E+10 | 0.181283E+10 | 16188.18 | 28-FEB-16:11 | 16188.18 | 0.04 |
March | 0.00 | 0.00 | 0.676203E+10 | 0.617111E+10 | 22693.82 | 28-MAR-15:11 | 16461.65 | 0.20 |
April | 0.00 | 0.00 | 0.136130E+11 | 0.108952E+11 | 28889.99 | 30-APR-15:13 | 15803.14 | 0.44 |
May | 0.00 | 0.00 | 0.289445E+11 | 0.191736E+11 | 39092.00 | 30-MAY-21:50 | 15428.41 | 0.67 |
June | 0.00 | 0.00 | 0.428769E+11 | 0.268716E+11 | 45326.50 | 29-JUN-08:03 | 17336.41 | 0.71 |
July | 0.00 | 0.00 | 0.536037E+11 | 0.303210E+11 | 49419.14 | 26-JUL-08:03 | 16840.26 | 0.76 |
August | 0.00 | 0.00 | 0.548217E+11 | 0.314505E+11 | 47944.72 | 24-AUG-08:61 | 17407.09 | 0.76 |
September | 0.00 | 0.00 | 0.383916E+11 | 0.234458E+11 | 45948.22 | 17-SEP-08:03 | 17077.80 | 0.74 |
October | 0.00 | 0.00 | 0.154476E+11 | 0.952848E+10 | 43943.86 | 18-OCT-21:52 | 15925.77 | 0.35 |
November | 0.00 | 0.00 | 0.541787E+10 | 0.391160E+10 | 27191.69 | 19-NOV-24:00 | 13347.24 | 0.15 |
December | 0.00 | 0.00 | 0.111289E+10 | 0.884908E+09 | 19514.41 | 12-DEC-13:30 | 14270.63 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.263487E+12 | 0.164965E+12 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 0.661161E+09 | 0.498469E+09 | 13220.25 | 7342.46 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.548217E+11 | 0.314505E+11 | 49419.14 | 17407.09 | 0.76 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.961446E+10 | 0.800158E+10 | 144602.17 | 19-JAN-21:00 | 78180.24 | 0.05 |
February | 0.00 | 0.00 | 0.327683E+11 | 0.321511E+11 | 163518.19 | 28-FEB-17:00 | 163518.19 | 0.07 |
March | 0.00 | 0.00 | 0.954473E+11 | 0.920253E+11 | 236635.18 | 30-MAR-18:10 | 204101.84 | 0.27 |
April | 0.00 | 0.00 | 0.195651E+12 | 0.172162E+12 | 262579.72 | 17-APR-17:15 | 262579.72 | 0.58 |
May | 0.00 | 0.00 | 0.372470E+12 | 0.279831E+12 | 342117.28 | 30-MAY-21:10 | 187423.18 | 0.88 |
June | 0.00 | 0.00 | 0.576425E+12 | 0.393037E+12 | 400677.59 | 26-JUN-18:10 | 198842.25 | 0.91 |
July | 0.00 | 0.00 | 0.734330E+12 | 0.445844E+12 | 405407.16 | 18-JUL-19:50 | 193852.11 | 1.00 |
August | 0.00 | 0.00 | 0.781520E+12 | 0.467266E+12 | 470616.02 | 23-AUG-21:00 | 205996.96 | 1.00 |
September | 0.00 | 0.00 | 0.503432E+12 | 0.336112E+12 | 405168.39 | 27-SEP-18:07 | 194527.65 | 0.97 |
October | 0.00 | 0.00 | 0.203016E+12 | 0.145510E+12 | 430642.65 | 18-OCT-19:40 | 200421.21 | 0.47 |
November | 0.00 | 0.00 | 0.738528E+11 | 0.609510E+11 | 251189.70 | 27-NOV-19:05 | 161384.26 | 0.21 |
December | 0.00 | 0.00 | 0.164799E+11 | 0.139202E+11 | 188817.44 | 13-DEC-11:35 | 104708.58 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.359501E+13 | 0.244681E+13 | 0.54 | |||
Minimum of Months | 0.00 | 0.00 | 0.961446E+10 | 0.800158E+10 | 144602.17 | 78180.24 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.781520E+12 | 0.467266E+12 | 470616.02 | 262579.72 | 1.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.115839E+09 | 98042805.60 | 13589.40 | 28-JAN-16:11 | 13589.40 | 0.02 |
February | 0.00 | 0.00 | 0.564252E+09 | 0.449537E+09 | 13591.51 | 28-FEB-19:01 | 13591.51 | 0.08 |
March | 0.00 | 0.00 | 0.223407E+10 | 0.140457E+10 | 13995.63 | 28-MAR-15:11 | 10707.26 | 0.34 |
April | 0.00 | 0.00 | 0.418175E+10 | 0.219349E+10 | 14444.23 | 02-APR-15:11 | 10352.56 | 0.72 |
May | 0.00 | 0.00 | 0.642857E+10 | 0.326608E+10 | 14844.54 | 27-MAY-08:62 | 9532.51 | 0.86 |
June | 0.00 | 0.00 | 0.866313E+10 | 0.493159E+10 | 15401.75 | 29-JUN-08:62 | 9588.05 | 0.94 |
July | 0.00 | 0.00 | 0.993661E+10 | 0.583139E+10 | 16121.84 | 27-JUL-08:61 | 8994.40 | 0.94 |
August | 0.00 | 0.00 | 0.104657E+11 | 0.621937E+10 | 15827.51 | 29-AUG-08:62 | 9235.38 | 0.96 |
September | 0.00 | 0.00 | 0.694681E+10 | 0.356254E+10 | 15678.84 | 17-SEP-08:62 | 9348.75 | 0.89 |
October | 0.00 | 0.00 | 0.340826E+10 | 0.162743E+10 | 15335.81 | 18-OCT-08:62 | 8897.73 | 0.63 |
November | 0.00 | 0.00 | 0.107293E+10 | 0.575538E+09 | 14873.49 | 04-NOV-15:12 | 9310.51 | 0.27 |
December | 0.00 | 0.00 | 0.278419E+09 | 0.165396E+09 | 14033.68 | 13-DEC-16:12 | 9321.03 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.542964E+11 | 0.303250E+11 | 0.56 | |||
Minimum of Months | 0.00 | 0.00 | 0.115839E+09 | 98042805.60 | 13589.40 | 8897.73 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.104657E+11 | 0.621937E+10 | 16121.84 | 13591.51 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6971892.47 | 4662746.38 | 6449.85 | 14-JAN-16:17 | 6449.85 | 0.00 |
February | 0.00 | 0.00 | 92542739.50 | 57235569.95 | 12657.99 | 24-FEB-19:01 | 12657.99 | 0.04 |
March | 0.00 | 0.00 | 0.929400E+09 | 0.479676E+09 | 13712.06 | 28-MAR-18:01 | 10685.63 | 0.20 |
April | 0.00 | 0.00 | 0.266110E+10 | 0.125698E+10 | 14538.98 | 02-APR-15:11 | 10033.41 | 0.52 |
May | 0.00 | 0.00 | 0.501487E+10 | 0.260036E+10 | 15383.33 | 07-MAY-17:41 | 11529.93 | 0.64 |
June | 0.00 | 0.00 | 0.785487E+10 | 0.470849E+10 | 16270.36 | 26-JUN-08:21 | 9823.81 | 0.78 |
July | 0.00 | 0.00 | 0.901318E+10 | 0.554393E+10 | 16435.01 | 23-JUL-08:51 | 9456.57 | 0.79 |
August | 0.00 | 0.00 | 0.931607E+10 | 0.561095E+10 | 17407.09 | 20-AUG-07:52 | 9563.18 | 0.83 |
September | 0.00 | 0.00 | 0.519016E+10 | 0.261476E+10 | 15834.46 | 17-SEP-08:52 | 8732.81 | 0.68 |
October | 0.00 | 0.00 | 0.152104E+10 | 0.584020E+09 | 15259.57 | 18-OCT-21:52 | 9155.27 | 0.37 |
November | 0.00 | 0.00 | 0.176024E+09 | 70054612.99 | 13940.00 | 05-NOV-15:12 | 10509.12 | 0.09 |
December | 0.00 | 0.00 | 24722644.05 | 14064900.61 | 12512.68 | 09-DEC-16:11 | 12512.68 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.418010E+11 | 0.235452E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 6971892.47 | 4662746.38 | 6449.85 | 6449.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.931607E+10 | 0.561095E+10 | 17407.09 | 12657.99 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.106741E+10 | 0.873524E+09 | 20584.12 | 29-JAN-13:30 | 20584.12 | 0.02 |
February | 0.00 | 0.00 | 0.510618E+10 | 0.483142E+10 | 29306.01 | 26-FEB-14:25 | 29306.01 | 0.02 |
March | 0.00 | 0.00 | 0.158248E+11 | 0.102517E+11 | 30216.82 | 30-MAR-13:30 | 20223.12 | 0.35 |
April | 0.00 | 0.00 | 0.193001E+11 | 0.808866E+10 | 26562.78 | 15-APR-13:40 | 17835.13 | 0.72 |
May | 0.00 | 0.00 | 0.259864E+11 | 0.925339E+10 | 22997.17 | 30-MAY-16:20 | 11683.90 | 0.92 |
June | 0.00 | 0.00 | 0.349441E+11 | 0.142671E+11 | 26458.62 | 13-JUN-17:15 | 15762.75 | 0.98 |
July | 0.00 | 0.00 | 0.416446E+11 | 0.181586E+11 | 29478.20 | 08-JUL-17:15 | 19649.66 | 1.00 |
August | 0.00 | 0.00 | 0.484782E+11 | 0.234025E+11 | 33081.56 | 19-AUG-15:10 | 23057.44 | 1.00 |
September | 0.00 | 0.00 | 0.363918E+11 | 0.169782E+11 | 37269.73 | 24-SEP-12:30 | 32578.36 | 0.96 |
October | 0.00 | 0.00 | 0.259432E+11 | 0.132045E+11 | 40376.09 | 10-OCT-13:30 | 38203.48 | 0.73 |
November | 0.00 | 0.00 | 0.151946E+11 | 0.112478E+11 | 33897.25 | 06-NOV-13:40 | 28204.86 | 0.29 |
December | 0.00 | 0.00 | 0.676942E+10 | 0.535071E+10 | 32423.50 | 12-DEC-12:30 | 22601.07 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.276651E+12 | 0.135908E+12 | 0.59 | |||
Minimum of Months | 0.00 | 0.00 | 0.106741E+10 | 0.873524E+09 | 20584.12 | 11683.90 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.484782E+11 | 0.234025E+11 | 40376.09 | 38203.48 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.105166E+10 | 0.477995E+09 | 75932.26 | 20-JAN-09:03 | 63192.77 | 0.06 |
February | 0.00 | 0.00 | 0.395168E+10 | 0.234123E+10 | 84568.15 | 18-FEB-09:02 | 62492.95 | 0.14 |
March | 0.00 | 0.00 | 0.124347E+11 | 0.739579E+10 | 82119.05 | 28-MAR-21:52 | 66995.80 | 0.28 |
April | 0.00 | 0.00 | 0.247414E+11 | 0.141353E+11 | 89916.80 | 30-APR-21:52 | 62629.26 | 0.47 |
May | 0.00 | 0.00 | 0.396896E+11 | 0.232655E+11 | 95314.10 | 07-MAY-17:41 | 67846.14 | 0.56 |
June | 0.00 | 0.00 | 0.549097E+11 | 0.348094E+11 | 99574.16 | 26-JUN-08:21 | 57799.32 | 0.71 |
July | 0.00 | 0.00 | 0.616546E+11 | 0.390691E+11 | 101253.23 | 23-JUL-08:51 | 57743.48 | 0.73 |
August | 0.00 | 0.00 | 0.614714E+11 | 0.377471E+11 | 110187.06 | 20-AUG-07:52 | 55026.81 | 0.76 |
September | 0.00 | 0.00 | 0.397925E+11 | 0.222544E+11 | 98314.49 | 17-SEP-08:52 | 55262.59 | 0.59 |
October | 0.00 | 0.00 | 0.181195E+11 | 0.835851E+10 | 97828.30 | 18-OCT-21:52 | 57214.53 | 0.48 |
November | 0.00 | 0.00 | 0.762546E+10 | 0.416255E+10 | 88209.51 | 05-NOV-21:52 | 60515.23 | 0.22 |
December | 0.00 | 0.00 | 0.232633E+10 | 0.115270E+10 | 85609.87 | 13-DEC-21:03 | 60313.82 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.327769E+12 | 0.195170E+12 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.105166E+10 | 0.477995E+09 | 75932.26 | 55026.81 | 0.06 | |
Maximum of Months | 0.00 | 0.00 | 0.616546E+11 | 0.390691E+11 | 110187.06 | 67846.14 | 0.76 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.105682E+09 | 78945897.22 | 12025.72 | 29-JAN-16:11 | 12025.72 | 0.02 |
February | 0.00 | 0.00 | 0.646021E+09 | 0.503384E+09 | 12283.78 | 28-FEB-19:01 | 12283.78 | 0.10 |
March | 0.00 | 0.00 | 0.197828E+10 | 0.112065E+10 | 12801.38 | 30-MAR-08:62 | 9328.67 | 0.38 |
April | 0.00 | 0.00 | 0.405010E+10 | 0.206637E+10 | 13102.80 | 02-APR-15:11 | 9343.53 | 0.75 |
May | 0.00 | 0.00 | 0.662286E+10 | 0.344013E+10 | 13484.09 | 27-MAY-08:62 | 8717.74 | 0.90 |
June | 0.00 | 0.00 | 0.889652E+10 | 0.511728E+10 | 13882.17 | 23-JUN-08:61 | 8730.73 | 0.97 |
July | 0.00 | 0.00 | 0.102948E+11 | 0.615714E+10 | 14579.15 | 27-JUL-08:61 | 8154.80 | 0.96 |
August | 0.00 | 0.00 | 0.105525E+11 | 0.634821E+10 | 13795.71 | 24-AUG-08:61 | 8789.95 | 0.97 |
September | 0.00 | 0.00 | 0.701028E+10 | 0.366990E+10 | 14194.44 | 17-SEP-08:62 | 8460.22 | 0.91 |
October | 0.00 | 0.00 | 0.336349E+10 | 0.159740E+10 | 13929.66 | 18-OCT-08:62 | 8176.01 | 0.65 |
November | 0.00 | 0.00 | 0.973658E+09 | 0.486632E+09 | 13392.84 | 04-NOV-15:12 | 8348.11 | 0.28 |
December | 0.00 | 0.00 | 0.261909E+09 | 0.130485E+09 | 12564.24 | 13-DEC-16:12 | 8567.58 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.547561E+11 | 0.307165E+11 | 0.58 | |||
Minimum of Months | 0.00 | 0.00 | 0.105682E+09 | 78945897.22 | 12025.72 | 8154.80 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.105525E+11 | 0.634821E+10 | 14579.15 | 12283.78 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9799459.22 | 5314965.72 | 7363.40 | 28-JAN-09:06 | 7363.40 | 0.00 |
February | 0.00 | 0.00 | 0.175404E+09 | 0.105085E+09 | 11627.99 | 20-FEB-09:01 | 10100.19 | 0.05 |
March | 0.00 | 0.00 | 0.850304E+09 | 0.387364E+09 | 12393.80 | 28-MAR-18:01 | 9730.56 | 0.23 |
April | 0.00 | 0.00 | 0.264809E+10 | 0.127927E+10 | 13300.78 | 02-APR-15:11 | 9018.47 | 0.55 |
May | 0.00 | 0.00 | 0.519487E+10 | 0.273944E+10 | 14216.46 | 07-MAY-08:51 | 11236.31 | 0.67 |
June | 0.00 | 0.00 | 0.797124E+10 | 0.477792E+10 | 15399.17 | 13-JUN-08:62 | 11514.05 | 0.80 |
July | 0.00 | 0.00 | 0.923466E+10 | 0.575787E+10 | 15307.71 | 23-JUL-08:51 | 10343.58 | 0.80 |
August | 0.00 | 0.00 | 0.934985E+10 | 0.563917E+10 | 15847.00 | 20-AUG-07:52 | 8752.72 | 0.84 |
September | 0.00 | 0.00 | 0.520780E+10 | 0.265674E+10 | 14911.94 | 07-SEP-08:31 | 10567.60 | 0.70 |
October | 0.00 | 0.00 | 0.160455E+10 | 0.667261E+09 | 13865.02 | 18-OCT-21:52 | 8322.39 | 0.40 |
November | 0.00 | 0.00 | 0.199611E+09 | 74850465.28 | 13435.26 | 05-NOV-15:12 | 8819.60 | 0.09 |
December | 0.00 | 0.00 | 19343705.52 | 6472603.69 | 7538.67 | 02-DEC-09:04 | 7538.67 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.424655E+11 | 0.240968E+11 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 9799459.22 | 5314965.72 | 7363.40 | 7363.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.934985E+10 | 0.575787E+10 | 15847.00 | 11514.05 | 0.84 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 20541250.02 | 17905366.21 | 3587.51 | 28-JAN-16:11 | 3587.51 | 0.01 |
February | 0.00 | 0.00 | 0.129339E+09 | 0.106333E+09 | 3587.45 | 28-FEB-19:01 | 3587.45 | 0.06 |
March | 0.00 | 0.00 | 0.533628E+09 | 0.344088E+09 | 3708.02 | 28-MAR-15:11 | 2812.80 | 0.29 |
April | 0.00 | 0.00 | 0.103006E+10 | 0.573302E+09 | 3917.93 | 23-APR-08:62 | 2263.80 | 0.65 |
May | 0.00 | 0.00 | 0.163554E+10 | 0.862221E+09 | 4064.27 | 27-MAY-08:62 | 2284.13 | 0.85 |
June | 0.00 | 0.00 | 0.223913E+10 | 0.128563E+10 | 4269.56 | 23-JUN-08:61 | 2359.46 | 0.94 |
July | 0.00 | 0.00 | 0.257716E+10 | 0.152146E+10 | 4488.20 | 30-JUL-08:62 | 2151.52 | 0.94 |
August | 0.00 | 0.00 | 0.271125E+10 | 0.161223E+10 | 4377.90 | 29-AUG-08:62 | 2265.78 | 0.95 |
September | 0.00 | 0.00 | 0.170711E+10 | 0.881839E+09 | 4402.95 | 17-SEP-08:62 | 2241.75 | 0.86 |
October | 0.00 | 0.00 | 0.792825E+09 | 0.398353E+09 | 4201.29 | 18-OCT-08:62 | 2119.82 | 0.54 |
November | 0.00 | 0.00 | 0.237603E+09 | 0.132556E+09 | 4012.89 | 04-NOV-15:12 | 2373.94 | 0.20 |
December | 0.00 | 0.00 | 56880879.37 | 34821570.31 | 3768.98 | 13-DEC-16:12 | 2389.38 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.136711E+11 | 0.777074E+10 | 0.53 | |||
Minimum of Months | 0.00 | 0.00 | 20541250.02 | 17905366.21 | 3587.45 | 2119.82 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.271125E+10 | 0.161223E+10 | 4488.20 | 3587.51 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 927537.57 | 442843.93 | 832.54 | 10-JAN-16:14 | 581.57 | 0.00 |
February | 0.00 | 0.00 | 18107558.64 | 11716544.56 | 3324.41 | 24-FEB-19:01 | 3324.41 | 0.02 |
March | 0.00 | 0.00 | 0.211839E+09 | 0.111570E+09 | 3610.15 | 30-MAR-08:52 | 2435.34 | 0.17 |
April | 0.00 | 0.00 | 0.654527E+09 | 0.326748E+09 | 3907.08 | 02-APR-15:11 | 2582.99 | 0.48 |
May | 0.00 | 0.00 | 0.131686E+10 | 0.707786E+09 | 4111.02 | 07-MAY-17:41 | 3091.57 | 0.65 |
June | 0.00 | 0.00 | 0.207079E+10 | 0.126098E+10 | 4470.18 | 26-JUN-08:21 | 2415.02 | 0.78 |
July | 0.00 | 0.00 | 0.237987E+10 | 0.147746E+10 | 4449.60 | 23-JUL-08:51 | 2365.59 | 0.79 |
August | 0.00 | 0.00 | 0.244528E+10 | 0.148028E+10 | 4795.91 | 20-AUG-07:52 | 2277.97 | 0.83 |
September | 0.00 | 0.00 | 0.129577E+10 | 0.657607E+09 | 4330.57 | 17-SEP-08:52 | 2136.19 | 0.66 |
October | 0.00 | 0.00 | 0.333610E+09 | 0.136060E+09 | 4182.25 | 18-OCT-21:52 | 2282.77 | 0.29 |
November | 0.00 | 0.00 | 28457352.51 | 11510102.08 | 3743.07 | 05-NOV-21:52 | 2318.60 | 0.05 |
December | 0.00 | 0.00 | 2888509.09 | 1667367.85 | 1842.12 | 07-DEC-16:11 | 1669.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.107589E+11 | 0.618383E+10 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 927537.57 | 442843.93 | 832.54 | 581.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.244528E+10 | 0.148028E+10 | 4795.91 | 3324.41 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.128197E+10 | 0.993529E+09 | 16089.22 | 26-JAN-16:11 | 16089.22 | 0.12 |
February | 0.00 | 0.00 | 0.198152E+10 | 0.158998E+10 | 16090.14 | 26-FEB-19:01 | 16090.14 | 0.18 |
March | 0.00 | 0.00 | 0.434622E+10 | 0.288231E+10 | 16234.59 | 31-MAR-15:11 | 13054.34 | 0.44 |
April | 0.00 | 0.00 | 0.584301E+10 | 0.318679E+10 | 17276.41 | 21-APR-18:01 | 12281.33 | 0.72 |
May | 0.00 | 0.00 | 0.811913E+10 | 0.407270E+10 | 17803.98 | 27-MAY-08:62 | 10936.64 | 0.86 |
June | 0.00 | 0.00 | 0.106635E+11 | 0.583509E+10 | 19804.14 | 23-JUN-08:61 | 10253.95 | 0.93 |
July | 0.00 | 0.00 | 0.125948E+11 | 0.717099E+10 | 20569.91 | 27-JUL-08:61 | 9512.57 | 0.93 |
August | 0.00 | 0.00 | 0.140394E+11 | 0.854982E+10 | 20097.94 | 29-AUG-08:62 | 10000.62 | 0.95 |
September | 0.00 | 0.00 | 0.102647E+11 | 0.578842E+10 | 19583.32 | 17-SEP-08:62 | 10415.40 | 0.88 |
October | 0.00 | 0.00 | 0.688502E+10 | 0.405125E+10 | 18953.40 | 18-OCT-08:62 | 9912.96 | 0.72 |
November | 0.00 | 0.00 | 0.412052E+10 | 0.267496E+10 | 17527.32 | 04-NOV-15:12 | 11636.15 | 0.49 |
December | 0.00 | 0.00 | 0.230724E+10 | 0.166599E+10 | 16640.11 | 13-DEC-16:12 | 12065.02 | 0.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.824470E+11 | 0.484618E+11 | 0.62 | |||
Minimum of Months | 0.00 | 0.00 | 0.128197E+10 | 0.993529E+09 | 16089.22 | 9512.57 | 0.12 | |
Maximum of Months | 0.00 | 0.00 | 0.140394E+11 | 0.854982E+10 | 20569.91 | 16090.14 | 0.95 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5976.26 | 187605.85 | 19-JAN-22:53 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 20861.47 | 334210.62 | 26-FEB-16:11 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 55115.62 | 407161.02 | 30-MAR-18:03 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 108425.87 | 414775.41 | 02-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 189861.98 | 503287.38 | 30-MAY-21:51 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 294874.42 | 562718.48 | 26-JUN-21:52 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 356269.35 | 581087.00 | 25-JUL-21:52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 377883.83 | 645291.56 | 23-AUG-21:52 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 255574.61 | 562103.66 | 16-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 107187.30 | 568610.93 | 18-OCT-21:52 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 44081.42 | 385855.98 | 05-NOV-15:13 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 12282.21 | 204105.05 | 13-DEC-11:35 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 153190.92 | 0.00 | ||||
Minimum of Months | 5976.26 | 187605.85 | 0.00 | 0.00 | ||
Maximum of Months | 377883.83 | 645291.56 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25127.80 | 52865.58 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 25181.90 | 52868.03 | 01-FEB-07:48 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 24371.46 | 52032.79 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22826.94 | 49168.15 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21010.68 | 45776.96 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 19400.55 | 41973.33 | 01-JUN-06:55 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18406.83 | 39074.92 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18356.59 | 38929.45 | 31-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19204.52 | 41387.40 | 29-SEP-06:53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20744.43 | 45223.06 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22564.04 | 48905.73 | 30-NOV-07:55 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24164.02 | 51621.86 | 29-DEC-07:38 |
Annual Sum or Average | 0.00 | 21760.58 | ||||
Minimum of Months | 0.00 | 0.00 | 18356.59 | 38929.45 | ||
Maximum of Months | 0.00 | 0.00 | 25181.90 | 52868.03 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261333E+10 | 0.69 | 1299.30 | 01-JAN-00:05 | 0.91 |
February | 0.236042E+10 | 0.69 | 1299.30 | 01-FEB-00:05 | 0.91 |
March | 0.261333E+10 | 0.69 | 1299.30 | 01-MAR-00:05 | 0.91 |
April | 0.252903E+10 | 0.69 | 1299.30 | 01-APR-00:10 | 0.91 |
May | 0.261333E+10 | 0.69 | 1299.30 | 01-MAY-00:10 | 0.90 |
June | 0.252903E+10 | 0.69 | 1299.30 | 01-JUN-00:10 | 0.90 |
July | 0.261333E+10 | 0.69 | 1299.30 | 01-JUL-00:10 | 0.90 |
August | 0.261333E+10 | 0.69 | 1299.30 | 01-AUG-00:10 | 0.90 |
September | 0.252903E+10 | 0.69 | 1299.30 | 01-SEP-00:10 | 0.90 |
October | 0.261333E+10 | 0.69 | 1299.30 | 01-OCT-00:10 | 0.90 |
November | 0.252903E+10 | 0.69 | 1299.30 | 01-NOV-00:10 | 0.91 |
December | 0.261333E+10 | 0.69 | 1299.30 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.307698E+11 | 0.69 | |||
Minimum of Months | 0.236042E+10 | 0.69 | 1299.30 | 0.90 | |
Maximum of Months | 0.261333E+10 | 0.69 | 1299.30 | 0.91 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.401727E+11 | 0.94 | 21292.04 | 22-JAN-20:10 | 1.17 |
February | 0.367253E+11 | 0.95 | 21604.25 | 28-FEB-22:10 | 1.17 |
March | 0.415300E+11 | 0.96 | 25011.23 | 30-MAR-21:07 | 1.27 |
April | 0.407326E+11 | 0.96 | 24735.79 | 18-APR-21:10 | 1.26 |
May | 0.430211E+11 | 0.97 | 25875.61 | 19-MAY-21:15 | 1.30 |
June | 0.432216E+11 | 0.99 | 28651.68 | 13-JUN-21:40 | 1.38 |
July | 0.452521E+11 | 1.00 | 29808.21 | 07-JUL-21:20 | 1.42 |
August | 0.459721E+11 | 1.01 | 31287.20 | 18-AUG-21:40 | 1.46 |
September | 0.429871E+11 | 0.99 | 31380.66 | 07-SEP-21:20 | 1.46 |
October | 0.430186E+11 | 0.97 | 28267.35 | 10-OCT-21:10 | 1.37 |
November | 0.410016E+11 | 0.97 | 23414.01 | 09-NOV-21:10 | 1.23 |
December | 0.408377E+11 | 0.95 | 22637.78 | 01-DEC-19:30 | 1.21 |
Annual Sum or Average | 0.504473E+12 | 0.97 | |||
Minimum of Months | 0.367253E+11 | 0.94 | 21292.04 | 1.17 | |
Maximum of Months | 0.459721E+11 | 1.01 | 31380.66 | 1.46 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:05 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:05 | 0.27 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:05 | 0.28 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:10 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:10 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:10 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:10 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:10 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:05 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | -0.0 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | -0.0 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | -0.0 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:10 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:03 | 0.28 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159639E+09 | 0.43 | 654.02 | 01-JAN-16:12 | 0.59 |
February | 0.119706E+09 | 0.42 | 654.02 | 01-FEB-09:01 | 0.60 |
March | 0.121586E+09 | 0.45 | 654.02 | 02-MAR-16:12 | 0.59 |
April | 0.191224E+09 | 0.49 | 654.02 | 01-APR-08:62 | 0.59 |
May | 0.268661E+09 | 0.53 | 654.02 | 01-MAY-15:11 | 0.59 |
June | 0.357708E+09 | 0.56 | 654.02 | 01-JUN-08:61 | 0.59 |
July | 0.406291E+09 | 0.56 | 654.02 | 01-JUL-08:61 | 0.59 |
August | 0.425241E+09 | 0.57 | 654.02 | 01-AUG-08:61 | 0.59 |
September | 0.283332E+09 | 0.54 | 654.02 | 01-SEP-08:62 | 0.59 |
October | 0.162366E+09 | 0.48 | 654.02 | 01-OCT-08:62 | 0.59 |
November | 86842969.11 | 0.44 | 654.02 | 01-NOV-15:11 | 0.59 |
December | 0.110762E+09 | 0.42 | 654.02 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.269336E+10 | 0.49 | |||
Minimum of Months | 86842969.11 | 0.42 | 654.02 | 0.59 | |
Maximum of Months | 0.425241E+09 | 0.57 | 654.02 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.193478E+09 | 0.45 | 646.56 | 01-JAN-16:12 | 0.59 |
February | 0.121280E+09 | 0.41 | 646.56 | 01-FEB-09:01 | 0.60 |
March | 66842076.73 | 0.34 | 646.56 | 03-MAR-09:02 | 0.59 |
April | 0.124541E+09 | 0.37 | 646.56 | 01-APR-08:62 | 0.59 |
May | 0.209893E+09 | 0.39 | 646.56 | 01-MAY-08:53 | 0.59 |
June | 0.329293E+09 | 0.46 | 646.56 | 01-JUN-08:51 | 0.59 |
July | 0.377303E+09 | 0.47 | 646.56 | 01-JUL-08:31 | 0.59 |
August | 0.381867E+09 | 0.49 | 646.56 | 01-AUG-07:51 | 0.59 |
September | 0.210638E+09 | 0.40 | 646.56 | 01-SEP-08:51 | 0.59 |
October | 81229239.18 | 0.34 | 646.56 | 01-OCT-21:52 | 0.59 |
November | 62367302.39 | 0.35 | 646.56 | 05-NOV-08:62 | 0.59 |
December | 0.132102E+09 | 0.40 | 646.56 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.229083E+10 | 0.41 | |||
Minimum of Months | 62367302.39 | 0.34 | 646.56 | 0.59 | |
Maximum of Months | 0.381867E+09 | 0.49 | 646.56 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 43887564.71 | 0.03 | 682.05 | 29-JAN-13:30 | 0.60 |
February | 0.185209E+09 | 0.11 | 925.87 | 26-FEB-14:25 | 0.60 |
March | 0.584310E+09 | 0.36 | 902.06 | 30-MAR-13:40 | 0.59 |
April | 0.703482E+09 | 0.46 | 844.92 | 15-APR-13:50 | 0.59 |
May | 0.897132E+09 | 0.54 | 709.88 | 19-MAY-17:20 | 0.59 |
June | 0.115053E+10 | 0.58 | 799.78 | 13-JUN-17:15 | 0.59 |
July | 0.133073E+10 | 0.59 | 887.77 | 08-JUL-17:30 | 0.59 |
August | 0.152559E+10 | 0.59 | 978.45 | 19-AUG-13:40 | 0.59 |
September | 0.118636E+10 | 0.57 | 1131.80 | 24-SEP-12:40 | 0.59 |
October | 0.893070E+09 | 0.44 | 1218.89 | 10-OCT-13:30 | 0.59 |
November | 0.552936E+09 | 0.34 | 1111.55 | 12-NOV-14:00 | 0.60 |
December | 0.249580E+09 | 0.16 | 1006.40 | 10-DEC-14:30 | 0.60 |
Annual Sum or Average | 0.930282E+10 | 0.40 | |||
Minimum of Months | 43887564.71 | 0.03 | 682.05 | 0.59 | |
Maximum of Months | 0.152559E+10 | 0.59 | 1218.89 | 0.60 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.836925E+09 | 0.39 | 3954.89 | 01-JAN-09:02 | 0.59 |
February | 0.629625E+09 | 0.37 | 3954.89 | 01-FEB-16:11 | 0.60 |
March | 0.625014E+09 | 0.32 | 3954.89 | 01-MAR-09:02 | 0.59 |
April | 0.107725E+10 | 0.33 | 3954.89 | 01-APR-08:62 | 0.59 |
May | 0.163019E+10 | 0.34 | 3954.89 | 01-MAY-08:53 | 0.59 |
June | 0.235287E+10 | 0.42 | 3954.89 | 01-JUN-08:51 | 0.59 |
July | 0.259748E+10 | 0.43 | 3954.89 | 01-JUL-08:31 | 0.59 |
August | 0.256503E+10 | 0.45 | 3954.89 | 01-AUG-07:51 | 0.59 |
September | 0.159262E+10 | 0.35 | 3954.89 | 01-SEP-08:51 | 0.59 |
October | 0.765895E+09 | 0.31 | 3954.89 | 01-OCT-08:53 | 0.59 |
November | 0.481042E+09 | 0.34 | 3954.89 | 01-NOV-21:53 | 0.59 |
December | 0.514545E+09 | 0.39 | 3954.89 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.156685E+11 | 0.37 | |||
Minimum of Months | 0.481042E+09 | 0.31 | 3954.89 | 0.59 | |
Maximum of Months | 0.259748E+10 | 0.45 | 3954.89 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146228E+09 | 0.42 | 590.56 | 01-JAN-16:12 | 0.59 |
February | 0.114098E+09 | 0.43 | 590.56 | 01-FEB-09:01 | 0.60 |
March | 0.108339E+09 | 0.47 | 590.56 | 02-MAR-16:12 | 0.59 |
April | 0.179557E+09 | 0.52 | 590.56 | 01-APR-08:62 | 0.59 |
May | 0.269660E+09 | 0.55 | 590.56 | 01-MAY-15:11 | 0.59 |
June | 0.365993E+09 | 0.57 | 590.56 | 01-JUN-08:61 | 0.59 |
July | 0.420567E+09 | 0.57 | 590.56 | 01-JUL-08:61 | 0.59 |
August | 0.427194E+09 | 0.57 | 590.56 | 01-AUG-08:61 | 0.59 |
September | 0.281349E+09 | 0.54 | 590.56 | 01-SEP-08:62 | 0.59 |
October | 0.153228E+09 | 0.50 | 590.56 | 01-OCT-08:62 | 0.59 |
November | 78707660.05 | 0.44 | 590.56 | 01-NOV-15:11 | 0.59 |
December | 99448124.25 | 0.41 | 590.56 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.264437E+10 | 0.50 | |||
Minimum of Months | 78707660.05 | 0.41 | 590.56 | 0.59 | |
Maximum of Months | 0.427194E+09 | 0.57 | 590.56 | 0.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.179582E+09 | 0.44 | 585.42 | 01-JAN-16:12 | 0.59 |
February | 0.112011E+09 | 0.40 | 585.42 | 01-FEB-09:01 | 0.60 |
March | 61299164.34 | 0.35 | 585.42 | 03-MAR-09:02 | 0.59 |
April | 0.119396E+09 | 0.39 | 585.42 | 01-APR-08:62 | 0.59 |
May | 0.214396E+09 | 0.41 | 585.42 | 01-MAY-08:53 | 0.59 |
June | 0.334719E+09 | 0.48 | 585.42 | 01-JUN-08:51 | 0.59 |
July | 0.385944E+09 | 0.48 | 585.42 | 01-JUL-08:31 | 0.59 |
August | 0.384555E+09 | 0.50 | 585.42 | 01-AUG-07:51 | 0.59 |
September | 0.208289E+09 | 0.42 | 585.42 | 01-SEP-08:51 | 0.59 |
October | 81309490.04 | 0.36 | 585.42 | 01-OCT-21:52 | 0.59 |
November | 57023341.70 | 0.34 | 585.42 | 01-NOV-08:62 | 0.59 |
December | 0.117999E+09 | 0.39 | 585.42 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.225652E+10 | 0.41 | |||
Minimum of Months | 57023341.70 | 0.34 | 585.42 | 0.59 | |
Maximum of Months | 0.385944E+09 | 0.50 | 585.42 | 0.60 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 49346965.07 | 0.44 | 172.72 | 01-JAN-09:02 | 0.59 |
February | 36097302.64 | 0.44 | 172.72 | 01-FEB-09:01 | 0.60 |
March | 32526206.13 | 0.45 | 172.72 | 03-MAR-09:02 | 0.59 |
April | 48636127.14 | 0.49 | 172.72 | 01-APR-15:12 | 0.59 |
May | 69391727.64 | 0.53 | 172.72 | 01-MAY-15:11 | 0.59 |
June | 94039121.75 | 0.56 | 172.72 | 01-JUN-08:61 | 0.59 |
July | 0.107757E+09 | 0.56 | 172.72 | 01-JUL-08:61 | 0.59 |
August | 0.111877E+09 | 0.57 | 172.72 | 01-AUG-08:61 | 0.59 |
September | 70948150.58 | 0.53 | 172.72 | 01-SEP-08:62 | 0.59 |
October | 40308439.75 | 0.48 | 172.72 | 01-OCT-15:11 | 0.59 |
November | 24856474.83 | 0.44 | 172.72 | 01-NOV-08:62 | 0.59 |
December | 35150523.76 | 0.43 | 172.72 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.720935E+09 | 0.49 | |||
Minimum of Months | 24856474.83 | 0.43 | 172.72 | 0.59 | |
Maximum of Months | 0.111877E+09 | 0.57 | 172.72 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 59007791.25 | 0.49 | 170.57 | 01-JAN-09:02 | 0.59 |
February | 37142689.06 | 0.43 | 170.57 | 01-FEB-09:01 | 0.60 |
March | 19119549.47 | 0.35 | 170.57 | 03-MAR-09:02 | 0.59 |
April | 31859158.76 | 0.37 | 170.57 | 02-APR-15:11 | 0.59 |
May | 55870730.87 | 0.40 | 170.57 | 01-MAY-21:51 | 0.59 |
June | 88388226.69 | 0.47 | 170.57 | 01-JUN-08:51 | 0.59 |
July | 0.101826E+09 | 0.47 | 170.57 | 01-JUL-08:31 | 0.59 |
August | 0.101596E+09 | 0.49 | 170.57 | 01-AUG-07:51 | 0.59 |
September | 53444660.45 | 0.40 | 170.57 | 01-SEP-08:51 | 0.59 |
October | 20818891.96 | 0.34 | 170.57 | 01-OCT-21:52 | 0.59 |
November | 20376870.32 | 0.36 | 170.57 | 01-NOV-08:62 | 0.59 |
December | 41376072.13 | 0.43 | 170.57 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.630827E+09 | 0.42 | |||
Minimum of Months | 19119549.47 | 0.34 | 170.57 | 0.59 | |
Maximum of Months | 0.101826E+09 | 0.49 | 170.57 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.188289E+09 | 0.46 | 770.84 | 01-JAN-16:12 | 0.59 |
February | 0.166739E+09 | 0.45 | 770.84 | 01-FEB-09:01 | 0.59 |
March | 0.212252E+09 | 0.48 | 770.84 | 02-MAR-16:12 | 0.59 |
April | 0.258202E+09 | 0.50 | 770.84 | 01-APR-08:62 | 0.59 |
May | 0.328567E+09 | 0.53 | 770.84 | 01-MAY-15:11 | 0.59 |
June | 0.432437E+09 | 0.55 | 770.84 | 01-JUN-08:61 | 0.59 |
July | 0.502991E+09 | 0.55 | 770.84 | 01-JUL-08:61 | 0.59 |
August | 0.567355E+09 | 0.56 | 770.84 | 01-AUG-08:61 | 0.59 |
September | 0.413706E+09 | 0.53 | 770.84 | 01-SEP-08:62 | 0.59 |
October | 0.306560E+09 | 0.51 | 770.84 | 01-OCT-08:62 | 0.59 |
November | 0.207486E+09 | 0.49 | 770.84 | 01-NOV-15:11 | 0.59 |
December | 0.175884E+09 | 0.47 | 770.84 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.376047E+10 | 0.51 | |||
Minimum of Months | 0.166739E+09 | 0.45 | 770.84 | 0.59 | |
Maximum of Months | 0.567355E+09 | 0.56 | 770.84 | 0.60 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 5059100.20 | 4598722.08 | 81.64 | 19-JAN-22:53 | 74.21 | 74.21 | 6.72 | 4.59 |
February | 16596470.88 | 15086192.03 | 241.58 | 26-FEB-16:13 | 219.60 | 219.60 | 6.72 | 7.76 |
March | 80864737.58 | 73506046.46 | 523.23 | 30-MAR-18:03 | 475.62 | 475.62 | 6.72 | 11.00 |
April | 0.198604E+09 | 0.180531E+09 | 806.92 | 13-APR-16:04 | 733.49 | 733.49 | 6.72 | 13.27 |
May | 0.378711E+09 | 0.344248E+09 | 789.63 | 15-MAY-18:03 | 717.77 | 717.77 | 6.72 | 13.15 |
June | 0.725142E+09 | 0.659154E+09 | 1012.64 | 28-JUN-18:03 | 920.49 | 920.49 | 6.72 | 14.61 |
July | 0.977305E+09 | 0.888371E+09 | 1141.91 | 06-JUL-18:03 | 1037.99 | 1037.99 | 6.72 | 15.37 |
August | 0.108992E+10 | 0.990737E+09 | 1136.15 | 10-AUG-18:03 | 1032.76 | 1032.76 | 6.72 | 15.34 |
September | 0.574052E+09 | 0.521813E+09 | 984.86 | 07-SEP-18:03 | 895.24 | 895.24 | 6.72 | 14.44 |
October | 0.199005E+09 | 0.180895E+09 | 808.19 | 18-OCT-18:03 | 734.65 | 734.65 | 6.72 | 13.28 |
November | 47540560.54 | 43214369.53 | 360.67 | 05-NOV-15:12 | 327.85 | 327.85 | 6.72 | 9.32 |
December | 11271920.41 | 10246175.65 | 114.41 | 12-DEC-22:53 | 104.00 | 104.00 | 6.72 | 5.43 |
Annual Sum or Average | 0.430407E+10 | 0.391240E+10 | ||||||
Minimum of Months | 5059100.20 | 4598722.08 | 81.64 | 74.21 | 74.21 | 6.72 | 4.59 | |
Maximum of Months | 0.108992E+10 | 0.990737E+09 | 1141.91 | 1037.99 | 1037.99 | 6.72 | 15.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.227093E+10 | 0.206427E+10 | 2930.26 | 01-JAN-01:00 | 2663.60 | 2663.60 | 6.74 | 26.18 |
February | 0.352825E+10 | 0.320718E+10 | 2930.26 | 01-FEB-00:05 | 2663.60 | 2663.60 | 6.77 | 26.18 |
March | 0.665847E+10 | 0.605255E+10 | 2930.26 | 01-MAR-00:05 | 2663.60 | 2663.60 | 7.10 | 26.18 |
April | 0.733255E+10 | 0.666529E+10 | 2930.26 | 01-APR-00:10 | 2663.60 | 2663.60 | 6.84 | 26.18 |
May | 0.784620E+10 | 0.713219E+10 | 2930.26 | 01-MAY-00:10 | 2663.60 | 2663.60 | 7.89 | 26.18 |
June | 0.759522E+10 | 0.690406E+10 | 2930.26 | 01-JUN-00:10 | 2663.60 | 2663.60 | 9.02 | 26.18 |
July | 0.784840E+10 | 0.713419E+10 | 2930.26 | 01-JUL-00:10 | 2663.60 | 2663.60 | 9.99 | 26.18 |
August | 0.784840E+10 | 0.713419E+10 | 2930.26 | 01-AUG-00:10 | 2663.60 | 2663.60 | 9.63 | 26.18 |
September | 0.759522E+10 | 0.690406E+10 | 2930.26 | 01-SEP-00:10 | 2663.60 | 2663.60 | 8.89 | 26.18 |
October | 0.732085E+10 | 0.665465E+10 | 2930.26 | 01-OCT-00:10 | 2663.60 | 2663.60 | 7.42 | 26.18 |
November | 0.590612E+10 | 0.536866E+10 | 2930.26 | 01-NOV-00:10 | 2663.60 | 2663.60 | 6.73 | 26.18 |
December | 0.358196E+10 | 0.325600E+10 | 2930.26 | 01-DEC-09:04 | 2663.60 | 2663.60 | 6.77 | 26.18 |
Annual Sum or Average | 0.753326E+11 | 0.684773E+11 | ||||||
Minimum of Months | 0.227093E+10 | 0.206427E+10 | 2930.26 | 2663.60 | 2663.60 | 6.73 | 26.18 | |
Maximum of Months | 0.784840E+10 | 0.713419E+10 | 2930.26 | 2663.60 | 2663.60 | 9.99 | 26.18 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 49.39 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 50.28 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 50.43 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.31 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 53.80 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 54.32 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.70 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.86 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.73 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.69 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 53.87 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 51.00 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.39 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.86 | 0.37 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5976.26 | 187605.85 | 19-JAN-22:53 | 8.41 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 20861.47 | 334210.62 | 26-FEB-16:11 | 9.75 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 55115.62 | 407161.02 | 30-MAR-18:03 | 10.41 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 108425.87 | 414775.41 | 02-APR-18:03 | 10.48 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 189861.98 | 503287.38 | 30-MAY-21:51 | 11.29 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 294874.42 | 562718.48 | 26-JUN-21:52 | 11.83 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 356269.35 | 581087.00 | 25-JUL-21:52 | 12.00 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 377883.83 | 645291.56 | 23-AUG-21:52 | 12.59 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 255574.61 | 562103.66 | 16-SEP-18:03 | 11.83 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 107187.30 | 568610.93 | 18-OCT-21:52 | 11.89 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 44081.42 | 385855.98 | 05-NOV-15:13 | 10.22 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 12282.21 | 204105.05 | 13-DEC-11:35 | 8.56 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 153190.92 | 0.00 | ||||||
Minimum of Months | 5976.26 | 187605.85 | 8.41 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 377883.83 | 645291.56 | 12.59 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 49.39 | 60.05 | 25127.80 | 52865.58 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 50.28 | 60.05 | 25181.90 | 52868.03 | 01-FEB-07:48 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 50.43 | 60.05 | 24371.46 | 52032.79 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.31 | 60.05 | 22826.94 | 49168.15 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 53.80 | 60.05 | 21010.68 | 45776.96 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 54.32 | 60.05 | 19400.55 | 41973.33 | 01-JUN-06:55 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.70 | 60.05 | 18406.83 | 39074.92 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 54.86 | 60.05 | 18356.59 | 38929.45 | 31-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.73 | 60.05 | 19204.52 | 41387.40 | 29-SEP-06:53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.69 | 60.05 | 20744.43 | 45223.06 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 53.87 | 60.05 | 22564.04 | 48905.73 | 30-NOV-07:55 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 51.00 | 60.05 | 24164.02 | 51621.86 | 29-DEC-07:38 |
Annual Sum or Average | 0.00 | 21760.58 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.39 | 60.05 | 18356.59 | 38929.45 | ||
Maximum of Months | 0.00 | 0.00 | 54.86 | 60.05 | 25181.90 | 52868.03 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.661161E+09 | 0.329377E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.183359E+10 | 0.293877E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.676203E+10 | 0.261333E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.136130E+11 | 0.252903E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.289445E+11 | 0.261333E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.428769E+11 | 0.252903E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.536037E+11 | 0.261333E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.548217E+11 | 0.261333E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.383916E+11 | 0.252903E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.154476E+11 | 0.261333E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.541787E+10 | 0.256442E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.111289E+10 | 0.273185E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.263487E+12 | 0.321825E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.661161E+09 | 0.252903E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.548217E+11 | 0.329377E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.961446E+10 | 0.111780E+12 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.327683E+11 | 0.820038E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.954473E+11 | 0.609769E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.195651E+12 | 0.510531E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.372470E+12 | 0.437573E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.576425E+12 | 0.434513E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.734330E+12 | 0.452671E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.781520E+12 | 0.459734E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.503432E+12 | 0.431796E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.203016E+12 | 0.488908E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.738528E+11 | 0.691733E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.164799E+11 | 0.103717E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.359501E+13 | 0.749224E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.961446E+10 | 0.431796E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.781520E+12 | 0.111780E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261333E+10 | 0.661161E+09 | 0.680441E+09 | 0.426517E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.183359E+10 | 0.578344E+09 | 0.267141E+11 | 849875.19 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.676203E+10 | 0.00 | 0.120909E+11 | 0.352454E+09 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.136130E+11 | 0.00 | 0.562505E+10 | 0.701430E+09 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.289445E+11 | 0.00 | 0.987460E+09 | 0.425360E+10 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.428769E+11 | 0.00 | 0.308457E+09 | 0.173612E+11 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 0.536037E+11 | 0.00 | 0.00 | 0.286590E+11 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 0.548217E+11 | 0.00 | 137700.68 | 0.372881E+11 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.383916E+11 | 0.00 | 0.187699E+09 | 0.131726E+11 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.154476E+11 | 0.00 | 0.737372E+10 | 0.214776E+10 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.541787E+10 | 35395838.37 | 0.171563E+11 | 85632618.49 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.111289E+10 | 0.118520E+09 | 0.307829E+11 | 1250842.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.263487E+12 | 0.141270E+10 | 0.143878E+12 | 0.104024E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 0.661161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.548217E+11 | 0.680441E+09 | 0.426517E+11 | 0.372881E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.401727E+11 | 0.961446E+10 | 0.716077E+11 | 0.142332E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.367253E+11 | 0.327683E+11 | 0.452786E+11 | 0.774537E+11 | 27565555.91 | 0.00 | 0.00 | 0.00 |
March | 0.415300E+11 | 0.954473E+11 | 0.194469E+11 | 0.825019E+09 | 0.489210E+09 | 0.00 | 0.00 | 0.00 |
April | 0.407326E+11 | 0.195651E+12 | 0.103204E+11 | 0.124781E+10 | 0.349526E+10 | 0.00 | 0.00 | 0.00 |
May | 0.430211E+11 | 0.372470E+12 | 0.736185E+09 | 0.00 | 0.219478E+11 | 0.00 | 0.00 | 0.00 |
June | 0.432216E+11 | 0.576425E+12 | 0.229658E+09 | 0.00 | 0.844708E+11 | 0.00 | 0.00 | 0.00 |
July | 0.452521E+11 | 0.734330E+12 | 15027336.06 | 0.00 | 0.136035E+12 | 0.00 | 0.00 | 0.00 |
August | 0.459721E+11 | 0.781520E+12 | 1336973.72 | 0.00 | 0.170255E+12 | 0.00 | 0.00 | 0.00 |
September | 0.429871E+11 | 0.503432E+12 | 0.192566E+09 | 0.00 | 0.524268E+11 | 0.00 | 0.00 | 0.00 |
October | 0.430186E+11 | 0.203016E+12 | 0.587218E+10 | 0.00 | 0.946477E+10 | 0.00 | 0.00 | 0.00 |
November | 0.410016E+11 | 0.738528E+11 | 0.281717E+11 | 0.106490E+11 | 0.178089E+09 | 0.00 | 0.00 | 0.00 |
December | 0.408377E+11 | 0.164799E+11 | 0.628791E+11 | 0.374306E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.504473E+12 | 0.359501E+13 | 0.244751E+12 | 0.269938E+12 | 0.478790E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.367253E+11 | 0.961446E+10 | 1336973.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.459721E+11 | 0.781520E+12 | 0.716077E+11 | 0.142332E+12 | 0.170255E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261333E+10 | 0.00 | 0.661161E+09 | 0.00 | 0.00 | 0.680441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.00 | 0.183359E+10 | 0.00 | 0.00 | 0.578344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.00 | 0.676203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.00 | 0.136130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.00 | 0.289445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.00 | 0.428769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 0.00 | 0.536037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 0.00 | 0.548217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.00 | 0.383916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.00 | 0.154476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.00 | 0.541787E+10 | 0.00 | 0.00 | 35395838.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.00 | 0.111289E+10 | 0.00 | 0.00 | 0.118520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.00 | 0.263487E+12 | 0.00 | 0.00 | 0.141270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 0.00 | 0.661161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.00 | 0.548217E+11 | 0.00 | 0.00 | 0.680441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.401727E+11 | 0.00 | 0.961446E+10 | 0.00 | 0.00 | 0.716077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.367253E+11 | 0.00 | 0.327683E+11 | 0.00 | 0.00 | 0.452786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.415300E+11 | 0.00 | 0.954473E+11 | 0.00 | 0.00 | 0.194469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.407326E+11 | 0.00 | 0.195651E+12 | 0.00 | 0.00 | 0.103204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.430211E+11 | 0.00 | 0.372470E+12 | 0.00 | 0.00 | 0.736185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.432216E+11 | 0.00 | 0.576425E+12 | 0.00 | 0.00 | 0.229658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.452521E+11 | 0.00 | 0.734330E+12 | 0.00 | 0.00 | 15027336.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.459721E+11 | 0.00 | 0.781520E+12 | 0.00 | 0.00 | 1336973.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.429871E+11 | 0.00 | 0.503432E+12 | 0.00 | 0.00 | 0.192566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.430186E+11 | 0.00 | 0.203016E+12 | 0.00 | 0.00 | 0.587218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.410016E+11 | 0.00 | 0.738528E+11 | 0.00 | 0.00 | 0.281717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408377E+11 | 0.00 | 0.164799E+11 | 0.00 | 0.00 | 0.628791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.504473E+12 | 0.00 | 0.359501E+13 | 0.00 | 0.00 | 0.244751E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.367253E+11 | 0.00 | 0.961446E+10 | 0.00 | 0.00 | 1336973.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.459721E+11 | 0.00 | 0.781520E+12 | 0.00 | 0.00 | 0.716077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.463928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
February | 0.391417E+11 | 0.00 | 0.00 | 0.00 | 1007948.25 | 0.00 | 0.00 | 0.00 | 0.72 |
March | 0.375645E+11 | 0.00 | 0.00 | 0.00 | 30020682.40 | 0.00 | 0.00 | 0.00 | 0.80 |
April | 0.273074E+11 | 0.00 | 0.00 | 0.00 | 0.440861E+09 | 0.00 | 0.00 | 0.00 | 0.83 |
May | 0.155519E+11 | 0.00 | 0.00 | 0.00 | 0.262694E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
June | 0.549393E+10 | 0.00 | 0.00 | 0.00 | 0.106282E+11 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.662555E+09 | 0.484845E+09 | 0.00 | 36626.81 | 0.173108E+11 | 0.00 | 12609638.69 | 0.00 | 0.60 |
August | 34117795.97 | 0.854553E+10 | 0.00 | 449502.45 | 0.123051E+11 | 0.00 | 0.273282E+09 | 0.00 | 0.60 |
September | 0.184637E+09 | 0.717656E+10 | 0.00 | 23630767.64 | 0.150158E+10 | 0.00 | 0.101451E+11 | 0.00 | 0.78 |
October | 0.576749E+09 | 0.210892E+10 | 0.00 | 52968940.02 | 0.172418E+09 | 0.00 | 0.335081E+11 | 0.00 | 0.87 |
November | 0.663699E+09 | 52525057.12 | 0.00 | 63189504.70 | 9889877.47 | 0.00 | 0.432930E+11 | 0.00 | 0.85 |
December | 0.137872E+11 | 0.00 | 0.00 | 28691561.71 | 92761.60 | 0.00 | 0.344819E+11 | 0.00 | 0.69 |
Annual Sum or Average | 0.187361E+12 | 0.183684E+11 | 0.00 | 0.168967E+09 | 0.450268E+11 | 0.00 | 0.121714E+12 | 0.00 | 0.74 |
Minimum of Months | 34117795.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.463928E+11 | 0.854553E+10 | 0.00 | 63189504.70 | 0.173108E+11 | 0.00 | 0.432930E+11 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.289897E+10 | 0.00 | 0.00 | 232180.51 | 0.00 | 0.119265E+10 | 0.219783E+09 | 0.00 | 1.08 |
February | 0.276267E+10 | 119342.93 | 0.00 | 641853.64 | 0.00 | 0.632745E+09 | 0.253089E+09 | 0.00 | 1.24 |
March | 0.297542E+10 | 2360627.21 | 0.00 | 1240461.64 | 968964.27 | 12242906.64 | 0.529611E+09 | 0.00 | 1.40 |
April | 0.217716E+10 | 15433824.39 | 0.00 | 1492440.44 | 27785441.97 | 0.00 | 0.363261E+09 | 0.00 | 1.46 |
May | 0.106152E+10 | 0.219256E+09 | 0.00 | 1123222.15 | 45844843.09 | 0.00 | 0.387863E+09 | 0.00 | 1.41 |
June | 0.286930E+09 | 0.116410E+10 | 0.00 | 732036.69 | 39777287.99 | 0.00 | 0.228012E+09 | 0.00 | 1.29 |
July | 27733500.90 | 0.197732E+10 | 0.00 | 101437.44 | 0.114401E+09 | 0.00 | 35252596.06 | 0.00 | 1.25 |
August | 2357643.20 | 0.258954E+10 | 0.00 | 81460.34 | 19536684.81 | 0.00 | 26831397.77 | 0.00 | 1.33 |
September | 0.561460E+09 | 0.836623E+09 | 0.00 | 1593121.13 | 0.119035E+09 | 0.00 | 0.348245E+09 | 0.00 | 1.44 |
October | 0.209489E+10 | 0.171990E+09 | 0.00 | 2417743.17 | 58985990.69 | 0.00 | 0.848698E+09 | 0.00 | 1.49 |
November | 0.312796E+10 | 2401419.46 | 0.00 | 1318642.08 | 3659185.33 | 62727315.33 | 0.568840E+09 | 0.00 | 1.39 |
December | 0.371308E+10 | 0.00 | 0.00 | 654470.24 | 8589.92 | 0.303936E+09 | 0.425065E+09 | 0.00 | 1.17 |
Annual Sum or Average | 0.216901E+11 | 0.697915E+10 | 0.00 | 11629069.47 | 0.430003E+09 | 0.220431E+10 | 0.423455E+10 | 0.00 | 1.33 |
Minimum of Months | 2357643.20 | 0.00 | 0.00 | 81460.34 | 0.00 | 0.00 | 26831397.77 | 0.00 | 1.08 |
Maximum of Months | 0.371308E+10 | 0.258954E+10 | 0.00 | 2417743.17 | 0.119035E+09 | 0.119265E+10 | 0.848698E+09 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.498108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
February | 0.415096E+10 | 0.00 | 0.00 | 22032.92 | 108221.08 | 0.00 | 51577551.91 | 0.00 | 1.21 |
March | 0.377445E+10 | 19047.28 | 0.00 | 148157.54 | 3204204.28 | 0.00 | 0.258712E+09 | 0.00 | 1.35 |
April | 0.244994E+10 | 77270.09 | 0.00 | 420552.38 | 47257009.28 | 0.00 | 0.482307E+09 | 0.00 | 1.41 |
May | 0.106169E+10 | 42432295.84 | 0.00 | 776124.75 | 0.239895E+09 | 0.00 | 0.609087E+09 | 0.00 | 1.36 |
June | 0.156371E+09 | 0.478901E+09 | 0.00 | 639429.77 | 0.676100E+09 | 0.00 | 0.435451E+09 | 0.00 | 1.15 |
July | 18500441.60 | 0.940479E+09 | 0.00 | 123221.57 | 0.100399E+10 | 0.00 | 53888143.99 | 0.00 | 1.04 |
August | 2358769.77 | 0.137451E+10 | 0.00 | 89891.58 | 0.913161E+09 | 0.00 | 30719249.71 | 0.00 | 1.03 |
September | 0.425285E+09 | 0.350395E+09 | 0.00 | 751369.44 | 0.550743E+09 | 0.00 | 0.609859E+09 | 0.00 | 1.25 |
October | 0.264699E+10 | 70105321.20 | 0.00 | 447610.44 | 0.155102E+09 | 0.00 | 0.655218E+09 | 0.00 | 1.33 |
November | 0.406358E+10 | 0.00 | 0.00 | 45695.66 | 6531806.77 | 0.00 | 0.165902E+09 | 0.00 | 1.30 |
December | 0.504374E+10 | 0.00 | 0.00 | 7064.40 | 9959.60 | 0.00 | 36608302.69 | 0.00 | 1.14 |
Annual Sum or Average | 0.287749E+11 | 0.325692E+10 | 0.00 | 3471150.46 | 0.359610E+10 | 0.00 | 0.338933E+10 | 0.00 | 1.22 |
Minimum of Months | 2358769.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
Maximum of Months | 0.504374E+10 | 0.137451E+10 | 0.00 | 776124.75 | 0.100399E+10 | 0.00 | 0.655218E+09 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 66525526.87 | 0.00 | 0.00 | 2935.06 | 0.00 | 12684994.73 | 1939934.01 | 0.00 | 0.01 |
February | 53703733.66 | 0.00 | 0.00 | 98449.36 | 1554.26 | 5347032.30 | 47838855.88 | 0.00 | 0.02 |
March | 38485674.47 | 513872.63 | 0.00 | 575579.92 | 3539.15 | 0.00 | 0.236676E+09 | 0.00 | 0.06 |
April | 12841138.66 | 6326682.31 | 0.00 | 1365798.23 | 88468.46 | 0.00 | 0.462288E+09 | 0.00 | 0.12 |
May | 131296.92 | 96024030.83 | 0.00 | 1896032.82 | 0.00 | 0.00 | 0.526990E+09 | 0.00 | 0.22 |
June | 0.00 | 0.661134E+09 | 0.00 | 1095761.37 | 0.00 | 0.00 | 0.278788E+09 | 0.00 | 0.30 |
July | 0.00 | 0.118957E+10 | 0.00 | 185617.79 | 0.00 | 0.00 | 35838900.24 | 0.00 | 0.30 |
August | 0.00 | 0.149164E+10 | 0.00 | 127319.51 | 0.00 | 0.00 | 20111182.59 | 0.00 | 0.32 |
September | 0.00 | 0.463690E+09 | 0.00 | 1453781.08 | 0.00 | 0.00 | 0.426460E+09 | 0.00 | 0.28 |
October | 12055944.53 | 86622459.83 | 0.00 | 1282262.90 | 0.00 | 0.00 | 0.572362E+09 | 0.00 | 0.14 |
November | 39656320.85 | 495192.03 | 0.00 | 505621.90 | 41718.14 | 0.00 | 0.255693E+09 | 0.00 | 0.05 |
December | 69014782.85 | 370.29 | 0.00 | 80393.94 | 0.00 | 0.00 | 42882353.49 | 0.00 | 0.01 |
Annual Sum or Average | 0.292414E+09 | 0.399602E+10 | 0.00 | 8669553.89 | 135280.02 | 18032027.03 | 0.290787E+10 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2935.06 | 0.00 | 0.00 | 1939934.01 | 0.00 | 0.01 |
Maximum of Months | 69014782.85 | 0.149164E+10 | 0.00 | 1896032.82 | 88468.46 | 12684994.73 | 0.572362E+09 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111961E+10 | 0.00 | 0.00 | 0.55 |
February | 0.198156E+10 | 0.00 | 0.00 | 0.00 | 68146.41 | 0.664777E+09 | 0.00 | 0.00 | 0.62 |
March | 0.253970E+10 | 0.00 | 0.00 | 0.00 | 2029669.28 | 0.00 | 0.00 | 0.00 | 0.69 |
April | 0.184623E+10 | 0.00 | 0.00 | 0.00 | 29806216.09 | 0.00 | 0.00 | 0.00 | 0.72 |
May | 0.105145E+10 | 0.00 | 0.00 | 0.00 | 0.177605E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
June | 0.371439E+09 | 0.00 | 0.00 | 0.00 | 0.718562E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 45649695.94 | 0.00 | 0.00 | 0.00 | 0.120314E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 20806653.29 | 0.00 | 0.00 | 0.00 | 0.140593E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 0.649450E+09 | 0.00 | 0.00 | 0.00 | 0.561677E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 0.207826E+10 | 0.00 | 0.00 | 0.00 | 0.141728E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
November | 0.266332E+10 | 0.00 | 0.00 | 0.00 | 4113053.94 | 0.00 | 0.00 | 0.00 | 0.67 |
December | 0.313593E+10 | 0.00 | 0.00 | 0.00 | 6271.52 | 63147429.41 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.184007E+11 | 0.00 | 0.00 | 0.00 | 0.424467E+10 | 0.184754E+10 | 0.00 | 0.00 | 0.62 |
Minimum of Months | 20806653.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.313593E+10 | 0.00 | 0.00 | 0.00 | 0.140593E+10 | 0.111961E+10 | 0.00 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.115662E+09 | 0.00 | 0.00 | 0.630620E+11 | 0.00 | 13.56 |
February | 0.00 | 1180318.72 | 0.00 | 0.101654E+09 | 0.00 | 0.00 | 0.535066E+11 | 0.00 | 15.58 |
March | 0.00 | 38973706.54 | 0.00 | 0.108592E+09 | 0.00 | 0.00 | 0.519668E+11 | 0.00 | 17.85 |
April | 0.00 | 0.559132E+09 | 0.00 | 0.105529E+09 | 0.00 | 0.00 | 0.373979E+11 | 0.00 | 18.58 |
May | 0.00 | 0.360646E+10 | 0.00 | 77437986.63 | 0.00 | 0.00 | 0.204078E+11 | 0.00 | 17.76 |
June | 0.00 | 0.151778E+11 | 0.00 | 30977170.92 | 0.00 | 0.00 | 0.710599E+10 | 0.00 | 14.89 |
July | 0.00 | 0.252805E+11 | 0.00 | 4339525.51 | 0.00 | 0.00 | 0.759137E+09 | 0.00 | 13.26 |
August | 0.00 | 0.297440E+11 | 0.00 | 2583484.70 | 0.00 | 0.00 | 0.355398E+09 | 0.00 | 13.15 |
September | 0.00 | 0.119184E+11 | 0.00 | 46778558.04 | 0.00 | 0.00 | 0.131623E+11 | 0.00 | 16.21 |
October | 0.00 | 0.303077E+10 | 0.00 | 92389850.83 | 0.00 | 0.00 | 0.429887E+11 | 0.00 | 17.55 |
November | 0.00 | 78700284.24 | 0.00 | 0.105427E+09 | 0.00 | 0.00 | 0.550982E+11 | 0.00 | 16.96 |
December | 0.00 | 102749.09 | 0.00 | 0.112399E+09 | 0.00 | 0.00 | 0.647283E+11 | 0.00 | 14.55 |
Annual Sum or Average | 0.00 | 0.894360E+11 | 0.00 | 0.903771E+09 | 0.00 | 0.00 | 0.410539E+12 | 0.00 | 15.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2583484.70 | 0.00 | 0.00 | 0.355398E+09 | 0.00 | 13.15 |
Maximum of Months | 0.00 | 0.297440E+11 | 0.00 | 0.115662E+09 | 0.00 | 0.00 | 0.647283E+11 | 0.00 | 18.58 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.333814E+11 | 0.00 | 0.00 | 586544.12 | 0.00 | 0.00 | 0.331460E+10 | 0.00 | 3.25 |
February | 0.250018E+11 | 144125.82 | 0.00 | 1884958.08 | 653159.65 | 0.00 | 0.595737E+10 | 0.00 | 3.66 |
March | 0.170796E+11 | 7371702.45 | 0.00 | 4532600.36 | 16374609.70 | 0.00 | 0.126293E+11 | 0.00 | 4.09 |
April | 0.112897E+11 | 34239771.36 | 0.00 | 4876041.36 | 0.314481E+09 | 0.00 | 0.103055E+11 | 0.00 | 4.25 |
May | 0.369224E+10 | 0.494243E+09 | 0.00 | 6264854.85 | 0.158367E+10 | 0.00 | 0.860303E+10 | 0.00 | 4.10 |
June | 0.116075E+10 | 0.411964E+10 | 0.00 | 2962136.62 | 0.428725E+10 | 0.00 | 0.318198E+10 | 0.00 | 3.44 |
July | 61301184.48 | 0.792093E+10 | 0.00 | 789744.36 | 0.615607E+10 | 0.00 | 0.471992E+09 | 0.00 | 3.08 |
August | 35670297.56 | 0.117834E+11 | 0.00 | 533854.06 | 0.467133E+10 | 0.00 | 0.207225E+09 | 0.00 | 3.04 |
September | 0.223843E+10 | 0.365949E+10 | 0.00 | 5452148.41 | 0.291228E+10 | 0.00 | 0.535442E+10 | 0.00 | 3.75 |
October | 0.112740E+11 | 0.859632E+09 | 0.00 | 6950823.85 | 0.798523E+09 | 0.00 | 0.130339E+11 | 0.00 | 4.04 |
November | 0.187917E+11 | 7551642.33 | 0.00 | 4831513.45 | 40569430.30 | 0.00 | 0.123632E+11 | 0.00 | 3.94 |
December | 0.302671E+11 | 0.00 | 0.00 | 1935411.21 | 73374.28 | 0.00 | 0.715889E+10 | 0.00 | 3.45 |
Annual Sum or Average | 0.154274E+12 | 0.288867E+11 | 0.00 | 41600630.74 | 0.207813E+11 | 0.00 | 0.825814E+11 | 0.00 | 3.67 |
Minimum of Months | 35670297.56 | 0.00 | 0.00 | 533854.06 | 0.00 | 0.00 | 0.207225E+09 | 0.00 | 3.04 |
Maximum of Months | 0.333814E+11 | 0.117834E+11 | 0.00 | 6950823.85 | 0.615607E+10 | 0.00 | 0.130339E+11 | 0.00 | 4.25 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100208E+12 | 0.00 | 0.00 | 578290.37 | 0.00 | 0.00 | 0.260835E+10 | 0.00 | 1.32 |
February | 0.756170E+11 | 0.00 | 0.00 | 4328091.82 | 2233844.88 | 0.00 | 0.111271E+11 | 0.00 | 1.48 |
March | 0.530638E+11 | 1694829.19 | 0.00 | 15508399.25 | 64837899.95 | 0.00 | 0.301802E+11 | 0.00 | 1.66 |
April | 0.291389E+11 | 26303943.83 | 0.00 | 22628358.54 | 0.950746E+09 | 0.00 | 0.314001E+11 | 0.00 | 1.73 |
May | 0.829836E+10 | 0.982432E+09 | 0.00 | 34263448.42 | 0.485013E+10 | 0.00 | 0.261941E+11 | 0.00 | 1.67 |
June | 0.213693E+10 | 0.982801E+10 | 0.00 | 18365375.47 | 0.140258E+11 | 0.00 | 0.100803E+11 | 0.00 | 1.41 |
July | 75010131.58 | 0.198626E+11 | 0.00 | 4601620.34 | 0.202696E+11 | 0.00 | 0.142349E+10 | 0.00 | 1.28 |
August | 48382091.27 | 0.288962E+11 | 0.00 | 2496763.99 | 0.185648E+11 | 0.00 | 0.647096E+09 | 0.00 | 1.27 |
September | 0.519586E+10 | 0.900303E+10 | 0.00 | 27045661.96 | 0.961876E+10 | 0.00 | 0.162209E+11 | 0.00 | 1.54 |
October | 0.321429E+11 | 0.190157E+10 | 0.00 | 25936232.38 | 0.276870E+10 | 0.00 | 0.360632E+11 | 0.00 | 1.64 |
November | 0.556724E+11 | 5345199.02 | 0.00 | 13623430.48 | 0.129481E+09 | 0.00 | 0.316190E+11 | 0.00 | 1.60 |
December | 0.922787E+11 | 0.00 | 0.00 | 4104777.84 | 205581.01 | 0.00 | 0.125834E+11 | 0.00 | 1.40 |
Annual Sum or Average | 0.453876E+12 | 0.705072E+11 | 0.00 | 0.173480E+09 | 0.712453E+11 | 0.00 | 0.210147E+12 | 0.00 | 1.50 |
Minimum of Months | 48382091.27 | 0.00 | 0.00 | 578290.37 | 0.00 | 0.00 | 0.647096E+09 | 0.00 | 1.27 |
Maximum of Months | 0.100208E+12 | 0.288962E+11 | 0.00 | 34263448.42 | 0.202696E+11 | 0.00 | 0.360632E+11 | 0.00 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 69847372.04 | 0.00 | 0.00 | 746859.04 | 0.00 | 0.123874E+10 | 0.116376E+09 | 0.00 | 0.34 |
February | 76634979.37 | 2507.83 | 0.00 | 2152464.58 | 0.00 | 0.860991E+09 | 0.296865E+09 | 0.00 | 0.34 |
March | 72631495.11 | 9351918.63 | 2424.51 | 5513537.36 | 166270.53 | 0.300324E+09 | 0.728283E+09 | 2952.05 | 0.34 |
April | 23203215.22 | 42115746.98 | 52721.30 | 8090443.93 | 3128902.99 | 84000437.82 | 0.660073E+09 | 9710.05 | 0.34 |
May | 1636528.20 | 0.252952E+09 | 19392.60 | 5360385.15 | 1262473.20 | 959629.57 | 0.271534E+09 | 3168.26 | 0.34 |
June | 160868.49 | 0.756323E+09 | 123501.60 | 2582918.54 | 0.00 | 123930.20 | 0.122117E+09 | 6757.00 | 0.34 |
July | 0.00 | 0.107631E+10 | 254088.14 | 215402.96 | 2989519.36 | 84695.60 | 3586787.59 | 3887.06 | 0.34 |
August | 0.00 | 0.117252E+10 | 176521.67 | 65920.60 | 0.00 | 10892.14 | 260143.62 | 3893.91 | 0.34 |
September | 1415937.09 | 0.566726E+09 | 319210.94 | 2870291.19 | 4824931.19 | 1057906.10 | 0.157363E+09 | 10271.44 | 0.34 |
October | 35655106.06 | 0.149344E+09 | 107953.25 | 5927320.81 | 3126023.68 | 0.192880E+09 | 0.640965E+09 | 11588.23 | 0.34 |
November | 44801791.83 | 8143968.14 | 497.26 | 3529146.80 | 1412108.46 | 0.521168E+09 | 0.600206E+09 | 3282.29 | 0.34 |
December | 78996363.76 | 268213.90 | 0.00 | 1323738.64 | 302486.85 | 0.109553E+10 | 0.217604E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.404984E+09 | 0.403406E+10 | 1056311.25 | 38378429.59 | 17212716.26 | 0.429587E+10 | 0.381523E+10 | 55510.28 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 65920.60 | 0.00 | 10892.14 | 260143.62 | 0.00 | 0.34 |
Maximum of Months | 78996363.76 | 0.117252E+10 | 319210.94 | 8090443.93 | 4824931.19 | 0.123874E+10 | 0.728283E+09 | 11588.23 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 64126913.51 | 0.00 | 0.00 | 89566.31 | 0.00 | 0.132940E+10 | 31925866.35 | 0.00 | 0.34 |
February | 0.104659E+09 | 2507.53 | 0.00 | 466770.54 | 0.00 | 0.957000E+09 | 0.174372E+09 | 0.00 | 0.34 |
March | 0.212899E+09 | 7608011.15 | 12431.30 | 1896084.85 | 1898092.80 | 0.400185E+09 | 0.491642E+09 | 3914.64 | 0.34 |
April | 0.152062E+09 | 33105412.06 | 106152.33 | 5452969.37 | 12081293.49 | 84743206.66 | 0.533018E+09 | 8915.05 | 0.34 |
May | 90620191.88 | 0.214975E+09 | 321697.67 | 3023425.96 | 38886501.31 | 635503.71 | 0.185178E+09 | 24655.95 | 0.34 |
June | 25596066.44 | 0.642767E+09 | 221924.87 | 2160386.87 | 0.113369E+09 | 85673.19 | 97128218.98 | 7298.40 | 0.34 |
July | 3751734.83 | 0.921455E+09 | 267528.99 | 65056.92 | 0.157703E+09 | 15632.37 | 54006.62 | 3993.59 | 0.34 |
August | 336916.89 | 0.105618E+10 | 320238.90 | 0.00 | 0.116059E+09 | 0.00 | 0.00 | 3606.97 | 0.34 |
September | 56647045.51 | 0.454270E+09 | 339887.72 | 1746450.43 | 0.117187E+09 | 753620.82 | 0.103541E+09 | 17527.46 | 0.34 |
October | 0.153059E+09 | 0.114822E+09 | 370554.13 | 1983040.21 | 37358296.07 | 0.256606E+09 | 0.463677E+09 | 20942.34 | 0.34 |
November | 0.148676E+09 | 4906771.24 | 16479.95 | 658646.37 | 4633128.48 | 0.732131E+09 | 0.288103E+09 | 2356.40 | 0.34 |
December | 0.102676E+09 | 253299.19 | 0.00 | 234969.15 | 317334.70 | 0.121871E+10 | 71671057.53 | 0.00 | 0.34 |
Annual Sum or Average | 0.111511E+10 | 0.345035E+10 | 1976895.85 | 17777366.98 | 0.599492E+09 | 0.498026E+10 | 0.244031E+10 | 93210.79 | 0.34 |
Minimum of Months | 336916.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.212899E+09 | 0.105618E+10 | 370554.13 | 5452969.37 | 0.157703E+09 | 0.132940E+10 | 0.533018E+09 | 24655.95 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.947704E+09 | 0.00 | 0.00 | 162669.71 | 5269244.00 | 0.00 | 0.114845E+09 | 0.00 | 0.02 |
February | 0.714324E+09 | 0.00 | 0.00 | 799977.24 | 0.00 | 0.00 | 0.265597E+09 | 0.00 | 0.02 |
March | 0.319133E+09 | 20792895.81 | 0.00 | 1716810.56 | 1828149.03 | 0.00 | 0.766246E+09 | 0.00 | 0.02 |
April | 0.172668E+09 | 89646427.12 | 0.00 | 1654764.76 | 21314182.90 | 0.00 | 0.325854E+09 | 0.00 | 0.02 |
May | 10776293.58 | 0.338189E+09 | 0.00 | 398917.56 | 1713563.31 | 0.00 | 0.118666E+09 | 0.00 | 0.02 |
June | 0.00 | 0.582705E+09 | 0.00 | 133171.93 | 0.00 | 0.00 | 52697287.60 | 0.00 | 0.02 |
July | 0.00 | 0.834269E+09 | 0.00 | 0.00 | 49356780.84 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.962038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 25686800.45 | 0.642270E+09 | 0.00 | 308828.17 | 25192289.65 | 0.00 | 21963116.48 | 0.00 | 0.02 |
October | 0.184346E+09 | 0.238331E+09 | 0.00 | 2002756.07 | 15920734.00 | 0.00 | 0.511679E+09 | 0.00 | 0.02 |
November | 0.325363E+09 | 47172140.09 | 0.00 | 2039308.91 | 9151679.67 | 0.00 | 0.748176E+09 | 0.00 | 0.02 |
December | 0.702000E+09 | 79732.81 | 0.00 | 1126796.68 | 0.00 | 0.00 | 0.629044E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.340200E+10 | 0.375549E+10 | 0.00 | 10344001.60 | 0.129747E+09 | 0.00 | 0.355477E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.947704E+09 | 0.962038E+09 | 0.00 | 2039308.91 | 49356780.84 | 0.00 | 0.766246E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130180E+10 | 0.00 | 0.00 | 7826466.30 | 0.00 | 0.129114E+11 | 0.511555E+10 | 0.00 | 0.38 |
February | 0.170784E+10 | 15296.09 | 14003.48 | 19460409.73 | 0.00 | 0.722354E+10 | 0.782153E+10 | 4713.63 | 0.39 |
March | 0.288785E+10 | 99293127.11 | 208384.53 | 40921367.00 | 29631879.89 | 0.504544E+09 | 0.115774E+11 | 32928.69 | 0.39 |
April | 0.207451E+10 | 0.426612E+09 | 220195.18 | 74213082.05 | 0.187649E+09 | 0.118333E+09 | 0.824911E+10 | 10810.39 | 0.39 |
May | 0.125248E+10 | 0.273841E+10 | 1428579.00 | 38447087.14 | 0.708265E+09 | 2700737.83 | 0.249705E+10 | 65672.39 | 0.39 |
June | 0.369206E+09 | 0.867819E+10 | 484373.10 | 22143816.12 | 0.158095E+10 | 652243.27 | 0.130315E+10 | 11564.83 | 0.39 |
July | 50890032.36 | 0.124237E+11 | 637924.01 | 1291489.94 | 0.221744E+10 | 31053.59 | 504525.71 | 2710.95 | 0.39 |
August | 4570075.44 | 0.141274E+11 | 521174.01 | 0.00 | 0.177724E+10 | 0.00 | 0.00 | 683.68 | 0.39 |
September | 0.775408E+09 | 0.582194E+10 | 1667848.50 | 23501363.47 | 0.193268E+10 | 3444429.86 | 0.140441E+10 | 26114.64 | 0.39 |
October | 0.207616E+10 | 0.149205E+10 | 3035475.99 | 39440493.39 | 0.574410E+09 | 0.114157E+09 | 0.964350E+10 | 54476.55 | 0.39 |
November | 0.201670E+10 | 66254096.88 | 545421.07 | 32251526.77 | 62845608.45 | 0.188945E+10 | 0.119261E+11 | 13394.14 | 0.39 |
December | 0.143801E+10 | 3435851.54 | 0.00 | 15269163.14 | 4304454.77 | 0.773326E+10 | 0.971259E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.159554E+11 | 0.458774E+11 | 8763378.87 | 0.314766E+09 | 0.907540E+10 | 0.305015E+11 | 0.692508E+11 | 223069.90 | 0.39 |
Minimum of Months | 4570075.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.288785E+10 | 0.141274E+11 | 3035475.99 | 74213082.05 | 0.221744E+10 | 0.129114E+11 | 0.119261E+11 | 65672.39 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68253894.45 | 0.00 | 0.00 | 876376.63 | 0.00 | 0.123258E+10 | 0.124001E+09 | 0.00 | 0.34 |
February | 70376070.50 | 1127.80 | 702.87 | 2691631.72 | 0.00 | 0.859131E+09 | 0.304445E+09 | 677.16 | 0.34 |
March | 52864760.03 | 9347880.97 | 14475.95 | 5231103.57 | 159401.88 | 0.311466E+09 | 0.737190E+09 | 1806.91 | 0.34 |
April | 15720001.82 | 42948442.19 | 61784.42 | 8279851.32 | 2294536.35 | 75381694.89 | 0.675986E+09 | 2318.36 | 0.34 |
May | 4092.15 | 0.253827E+09 | 0.00 | 5841121.83 | 410133.87 | 483205.35 | 0.273162E+09 | 0.00 | 0.34 |
June | 0.00 | 0.756436E+09 | 16455.33 | 2867686.48 | 0.00 | 0.00 | 0.122117E+09 | 1247.37 | 0.34 |
July | 0.00 | 0.107647E+10 | 90305.17 | 212005.88 | 2989519.36 | 84695.60 | 3590184.66 | 3593.55 | 0.34 |
August | 0.00 | 0.117260E+10 | 102027.79 | 85486.49 | 0.00 | 0.00 | 251469.88 | 2927.77 | 0.34 |
September | 1415937.09 | 0.566932E+09 | 121399.69 | 3126541.38 | 4824931.19 | 590265.83 | 0.157574E+09 | 2895.55 | 0.34 |
October | 28002961.30 | 0.149389E+09 | 70524.00 | 5839160.21 | 3126023.68 | 0.189282E+09 | 0.652304E+09 | 4355.88 | 0.34 |
November | 41973360.88 | 8427389.09 | 212.69 | 3586134.39 | 1128687.50 | 0.512861E+09 | 0.611285E+09 | 3566.87 | 0.34 |
December | 78337322.84 | 268213.90 | 0.00 | 1303432.25 | 302486.85 | 0.106989E+10 | 0.243919E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.356948E+09 | 0.403665E+10 | 477887.91 | 39940532.16 | 15235720.68 | 0.425175E+10 | 0.390582E+10 | 23389.43 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 85486.49 | 0.00 | 0.00 | 251469.88 | 0.00 | 0.34 |
Maximum of Months | 78337322.84 | 0.117260E+10 | 121399.69 | 8279851.32 | 4824931.19 | 0.123258E+10 | 0.737190E+09 | 4355.88 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 70906061.02 | 0.00 | 0.00 | 98161.56 | 0.00 | 0.132478E+10 | 29751925.08 | 0.00 | 0.34 |
February | 0.111180E+09 | 2507.53 | 0.00 | 868460.21 | 0.00 | 0.932767E+09 | 0.191683E+09 | 0.00 | 0.34 |
March | 0.211550E+09 | 7593657.16 | 24946.75 | 2118195.39 | 1898092.80 | 0.404201E+09 | 0.488753E+09 | 5753.18 | 0.34 |
April | 0.148201E+09 | 34169455.53 | 110774.21 | 5790494.86 | 11018489.20 | 82414717.01 | 0.538870E+09 | 3053.97 | 0.34 |
May | 88843885.06 | 0.215799E+09 | 176225.88 | 3273543.53 | 38226267.27 | 328127.63 | 0.187012E+09 | 6104.04 | 0.34 |
June | 25365798.11 | 0.645056E+09 | 23930.63 | 2386210.44 | 0.111285E+09 | 59906.39 | 97158430.54 | 297.68 | 0.34 |
July | 3751734.83 | 0.925363E+09 | 33766.81 | 63919.28 | 0.154033E+09 | 2079.33 | 68697.30 | 771.15 | 0.34 |
August | 336916.89 | 0.105752E+10 | 0.00 | 0.00 | 0.115050E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
September | 56304033.20 | 0.456011E+09 | 153276.18 | 1843753.41 | 0.115646E+09 | 351609.07 | 0.104188E+09 | 3688.79 | 0.34 |
October | 0.150916E+09 | 0.117547E+09 | 312702.66 | 2313737.91 | 34702613.40 | 0.290606E+09 | 0.431489E+09 | 9631.94 | 0.34 |
November | 0.148676E+09 | 4906771.24 | 17206.85 | 912157.33 | 4633128.48 | 0.696584E+09 | 0.323397E+09 | 1629.50 | 0.34 |
December | 0.106013E+09 | 253299.19 | 0.00 | 166569.83 | 317334.70 | 0.121873E+10 | 68378253.09 | 0.00 | 0.34 |
Annual Sum or Average | 0.112204E+10 | 0.346422E+10 | 852829.98 | 19835203.76 | 0.586809E+09 | 0.495083E+10 | 0.246075E+10 | 30930.26 | 0.34 |
Minimum of Months | 336916.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.211550E+09 | 0.105752E+10 | 312702.66 | 5790494.86 | 0.154033E+09 | 0.132478E+10 | 0.538870E+09 | 9631.94 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342016E+10 | 0.00 | 0.00 | 0.36 |
February | 0.200908E+11 | 0.00 | 0.00 | 0.00 | 560218.10 | 0.166419E+10 | 0.00 | 0.00 | 0.40 |
March | 0.208783E+11 | 0.00 | 0.00 | 0.00 | 16685509.14 | 0.00 | 0.00 | 0.00 | 0.45 |
April | 0.151775E+11 | 0.00 | 0.00 | 0.00 | 0.245031E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.864376E+10 | 0.00 | 0.00 | 0.00 | 0.146006E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.305353E+10 | 0.00 | 0.00 | 0.00 | 0.590715E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.375277E+09 | 0.432282E+09 | 0.00 | 0.00 | 0.945853E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 0.171047E+09 | 0.532572E+09 | 0.00 | 0.00 | 0.110253E+11 | 0.00 | 0.00 | 0.00 | 0.34 |
September | 0.533900E+10 | 0.00 | 0.00 | 0.00 | 0.461744E+10 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 0.170850E+11 | 0.00 | 0.00 | 0.00 | 0.116511E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
November | 0.218946E+11 | 0.00 | 0.00 | 0.00 | 33812601.83 | 0.00 | 0.00 | 0.00 | 0.43 |
December | 0.259452E+11 | 0.00 | 0.00 | 0.00 | 51556.94 | 0.353830E+09 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.161019E+12 | 0.964854E+09 | 0.00 | 0.00 | 0.339297E+11 | 0.543818E+10 | 0.00 | 0.00 | 0.41 |
Minimum of Months | 0.171047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.259452E+11 | 0.532572E+09 | 0.00 | 0.00 | 0.110253E+11 | 0.342016E+10 | 0.00 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16582522.33 | 0.00 | 0.00 | 133676.63 | 0.00 | 0.318199E+09 | 21511647.50 | 0.00 | 0.34 |
February | 17515975.98 | 626.96 | 0.00 | 478993.75 | 0.00 | 0.236539E+09 | 54626822.69 | 0.00 | 0.34 |
March | 18638831.35 | 2337979.66 | 337.34 | 1235883.61 | 41567.63 | 0.129258E+09 | 0.127555E+09 | 1006.80 | 0.34 |
April | 5543852.61 | 10580134.19 | 13015.88 | 1864544.70 | 731028.30 | 37104056.07 | 0.149329E+09 | 2591.95 | 0.34 |
May | 386135.41 | 63442548.55 | 4888.43 | 1230765.16 | 111143.77 | 1228548.36 | 67027125.90 | 751.78 | 0.34 |
June | 0.00 | 0.189070E+09 | 39520.50 | 606166.06 | 0.00 | 61512.84 | 30578568.43 | 3486.05 | 0.34 |
July | 0.00 | 0.269021E+09 | 57592.56 | 43813.64 | 807368.36 | 11315.82 | 916592.08 | 3636.74 | 0.34 |
August | 0.00 | 0.293077E+09 | 96461.62 | 15109.13 | 0.00 | 2723.04 | 66406.93 | 3002.42 | 0.34 |
September | 353984.27 | 0.141500E+09 | 112616.68 | 605664.51 | 1353129.36 | 3292852.72 | 36424215.79 | 4628.38 | 0.34 |
October | 9764810.56 | 37286543.40 | 75892.90 | 1297243.63 | 781505.92 | 86940724.64 | 0.120854E+09 | 3525.49 | 0.34 |
November | 11047216.36 | 2106847.27 | 133.79 | 745391.50 | 282171.88 | 0.180425E+09 | 0.100209E+09 | 811.10 | 0.34 |
December | 18130302.10 | 67053.48 | 0.00 | 274567.39 | 75621.71 | 0.297006E+09 | 32952314.27 | 0.00 | 0.34 |
Annual Sum or Average | 97963630.97 | 0.100849E+10 | 400459.69 | 8531819.72 | 4183536.94 | 0.129007E+10 | 0.742051E+09 | 23440.71 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 15109.13 | 0.00 | 2723.04 | 66406.93 | 0.00 | 0.34 |
Maximum of Months | 18638831.35 | 0.293077E+09 | 112616.68 | 1864544.70 | 1353129.36 | 0.318199E+09 | 0.149329E+09 | 4628.38 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11098575.06 | 0.00 | 0.00 | 10334.93 | 0.00 | 0.343060E+09 | 2216337.55 | 0.00 | 0.34 |
February | 24810192.40 | 626.88 | 0.00 | 86493.47 | 0.00 | 0.262239E+09 | 21988462.63 | 0.00 | 0.34 |
March | 53210735.06 | 1902002.79 | 2637.45 | 366959.95 | 474523.20 | 0.149430E+09 | 73647440.07 | 1449.04 | 0.34 |
April | 38089361.91 | 8358169.64 | 26240.76 | 1255442.06 | 2938506.75 | 36983966.44 | 0.117490E+09 | 2526.08 | 0.34 |
May | 22460446.18 | 53764611.57 | 79062.44 | 710812.71 | 9700076.02 | 154912.24 | 46538217.10 | 8135.61 | 0.34 |
June | 6358804.20 | 0.160672E+09 | 74074.06 | 516361.80 | 28342148.84 | 26557.61 | 24340862.77 | 2798.05 | 0.34 |
July | 937933.71 | 0.230317E+09 | 43843.17 | 13717.97 | 39495920.91 | 3388.26 | 16567.74 | 776.64 | 0.34 |
August | 84229.22 | 0.264009E+09 | 115516.40 | 0.00 | 29014726.00 | 0.00 | 0.00 | 2343.10 | 0.34 |
September | 14086482.08 | 0.113169E+09 | 95093.40 | 362872.44 | 29682284.51 | 1695289.39 | 24527307.51 | 6961.90 | 0.34 |
October | 38365903.43 | 29017751.14 | 92938.20 | 348406.97 | 9026628.92 | 0.103332E+09 | 76784518.61 | 5679.91 | 0.34 |
November | 35870654.40 | 1226692.81 | 4284.74 | 92331.41 | 1158282.12 | 0.219261E+09 | 37168312.73 | 424.35 | 0.34 |
December | 20185787.29 | 63324.80 | 0.00 | 32869.52 | 79333.67 | 0.319534E+09 | 8569478.18 | 0.00 | 0.34 |
Annual Sum or Average | 0.265559E+09 | 0.862501E+09 | 533690.62 | 3796603.23 | 0.149912E+09 | 0.143572E+10 | 0.433288E+09 | 31094.67 | 0.34 |
Minimum of Months | 84229.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 53210735.06 | 0.264009E+09 | 115516.40 | 1255442.06 | 39495920.91 | 0.343060E+09 | 0.117490E+09 | 8135.61 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 72183790.56 | 0.00 | 0.00 | 5954190.84 | 0.00 | 0.157104E+10 | 0.640685E+09 | 0.00 | 0.38 |
February | 82623311.29 | 1811.38 | 417.78 | 6935816.24 | 0.00 | 0.103685E+10 | 0.859790E+09 | 1798.72 | 0.39 |
March | 58661592.37 | 15157669.59 | 0.00 | 10007276.41 | 138342.02 | 0.322511E+09 | 0.138640E+10 | 0.00 | 0.39 |
April | 28494298.96 | 68485661.83 | 19612.22 | 11067860.51 | 4263295.58 | 0.139278E+09 | 0.106649E+10 | 145.64 | 0.39 |
May | 549279.58 | 0.406253E+09 | 0.00 | 6768438.96 | 2083003.24 | 1439170.72 | 0.440139E+09 | 0.00 | 0.39 |
June | 0.00 | 0.121467E+10 | 273968.48 | 2953383.99 | 0.00 | 356064.70 | 0.197432E+09 | 8767.11 | 0.39 |
July | 0.00 | 0.172817E+10 | 536200.35 | 275706.12 | 5186929.44 | 136031.50 | 5831077.05 | 8908.94 | 0.39 |
August | 0.00 | 0.188263E+10 | 870651.18 | 99413.03 | 0.00 | 0.00 | 441780.12 | 11233.88 | 0.39 |
September | 2274168.19 | 0.909182E+09 | 448831.88 | 4248815.68 | 8873076.24 | 4093159.35 | 0.250711E+09 | 6405.98 | 0.39 |
October | 27748351.73 | 0.239993E+09 | 61292.40 | 11496917.01 | 5020776.46 | 0.195171E+09 | 0.117163E+10 | 2888.96 | 0.39 |
November | 31035887.81 | 13784049.30 | 4809.08 | 10980354.53 | 1565244.65 | 0.423438E+09 | 0.141324E+10 | 195.46 | 0.39 |
December | 57478686.39 | 916615.22 | 0.00 | 7535054.69 | 0.00 | 0.120961E+10 | 0.963428E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.361049E+09 | 0.647924E+10 | 2215783.36 | 78323228.01 | 27130667.63 | 0.490392E+10 | 0.839622E+10 | 40344.70 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 99413.03 | 0.00 | 0.00 | 441780.12 | 0.00 | 0.38 |
Maximum of Months | 82623311.29 | 0.188263E+10 | 870651.18 | 11496917.01 | 8873076.24 | 0.157104E+10 | 0.141324E+10 | 11233.88 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.319669E+11 | 0.00 | 0.00 | 12994846.84 | 0.00 | 0.00 | 0.324830E+11 | 0.00 | 4.23 |
February | 0.221768E+11 | 0.00 | 0.00 | 16398527.52 | 1400547.44 | 0.00 | 0.321982E+11 | 0.00 | 4.77 |
March | 0.149229E+11 | 19626243.99 | 0.00 | 27609159.80 | 22087593.98 | 0.00 | 0.372681E+11 | 0.00 | 5.33 |
April | 0.705958E+10 | 0.369617E+09 | 0.00 | 32388132.25 | 0.242961E+09 | 0.00 | 0.309566E+11 | 0.00 | 5.56 |
May | 0.166436E+10 | 0.291539E+10 | 0.00 | 35077794.21 | 0.746376E+09 | 0.00 | 0.200561E+11 | 0.00 | 5.38 |
June | 0.450792E+09 | 0.129517E+11 | 0.00 | 14928222.98 | 0.194016E+10 | 0.00 | 0.723263E+10 | 0.00 | 4.52 |
July | 5755085.06 | 0.221297E+11 | 0.00 | 3273023.46 | 0.281030E+10 | 0.00 | 0.934763E+09 | 0.00 | 4.06 |
August | 10329384.58 | 0.261483E+11 | 0.00 | 1569100.07 | 0.304529E+10 | 0.00 | 0.417640E+09 | 0.00 | 4.00 |
September | 0.113806E+10 | 0.972658E+10 | 0.00 | 19091453.64 | 0.187215E+10 | 0.00 | 0.122594E+11 | 0.00 | 4.91 |
October | 0.995985E+10 | 0.218701E+10 | 0.00 | 25783988.71 | 0.742698E+09 | 0.00 | 0.327576E+11 | 0.00 | 5.26 |
November | 0.176454E+11 | 33315437.33 | 0.00 | 21628005.93 | 51216199.16 | 0.00 | 0.370710E+11 | 0.00 | 5.12 |
December | 0.269807E+11 | 0.00 | 0.00 | 16266913.53 | 128892.55 | 0.00 | 0.387507E+11 | 0.00 | 4.49 |
Annual Sum or Average | 0.133981E+12 | 0.764812E+11 | 0.00 | 0.227009E+09 | 0.114748E+11 | 0.00 | 0.282386E+12 | 0.00 | 4.80 |
Minimum of Months | 5755085.06 | 0.00 | 0.00 | 1569100.07 | 0.00 | 0.00 | 0.417640E+09 | 0.00 | 4.00 |
Maximum of Months | 0.319669E+11 | 0.261483E+11 | 0.00 | 35077794.21 | 0.304529E+10 | 0.00 | 0.387507E+11 | 0.00 | 5.56 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.257203E+11 | 0.00 | 0.00 | 19423472.55 | 0.00 | 0.00 | 0.387748E+11 | 0.00 | 4.24 |
February | 0.176240E+11 | 1037759.56 | 0.00 | 23345588.09 | 363612.29 | 0.00 | 0.368337E+11 | 0.00 | 4.78 |
March | 0.107274E+11 | 30821988.21 | 0.00 | 36223967.36 | 10916404.09 | 0.00 | 0.416460E+11 | 0.00 | 5.35 |
April | 0.421182E+10 | 0.485933E+09 | 0.00 | 41104396.25 | 0.127072E+09 | 0.00 | 0.340163E+11 | 0.00 | 5.59 |
May | 0.773143E+09 | 0.315435E+10 | 0.00 | 41934830.32 | 0.520743E+09 | 0.00 | 0.211109E+11 | 0.00 | 5.42 |
June | 0.294409E+09 | 0.137179E+11 | 0.00 | 17690607.39 | 0.130587E+10 | 0.00 | 0.744797E+10 | 0.00 | 4.57 |
July | 4987443.08 | 0.234020E+11 | 0.00 | 3695287.63 | 0.176962E+10 | 0.00 | 0.942869E+09 | 0.00 | 4.11 |
August | 1700554.55 | 0.274784E+11 | 0.00 | 1853676.00 | 0.203335E+10 | 0.00 | 0.427920E+09 | 0.00 | 4.05 |
September | 0.602300E+09 | 0.104769E+11 | 0.00 | 22798758.75 | 0.118753E+10 | 0.00 | 0.128955E+11 | 0.00 | 4.95 |
October | 0.713565E+10 | 0.251244E+10 | 0.00 | 32994736.38 | 0.435072E+09 | 0.00 | 0.357309E+11 | 0.00 | 5.29 |
November | 0.137246E+11 | 52740032.39 | 0.00 | 29713029.36 | 31841362.61 | 0.00 | 0.410855E+11 | 0.00 | 5.14 |
December | 0.214139E+11 | 0.00 | 0.00 | 24315772.38 | 128968.42 | 0.00 | 0.443726E+11 | 0.00 | 4.50 |
Annual Sum or Average | 0.102234E+12 | 0.813125E+11 | 0.00 | 0.295094E+09 | 0.742251E+10 | 0.00 | 0.315285E+12 | 0.00 | 4.83 |
Minimum of Months | 1700554.55 | 0.00 | 0.00 | 1853676.00 | 0.00 | 0.00 | 0.427920E+09 | 0.00 | 4.05 |
Maximum of Months | 0.257203E+11 | 0.274784E+11 | 0.00 | 41934830.32 | 0.203335E+10 | 0.00 | 0.443726E+11 | 0.00 | 5.59 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.113950E+09 | 0.00 | 0.00 | 0.606161E+11 | 0.00 | 13.16 |
February | 0.00 | 1709037.74 | 0.00 | 0.102460E+09 | 0.00 | 0.00 | 0.510219E+11 | 0.00 | 15.43 |
March | 0.00 | 52122912.34 | 0.00 | 0.110456E+09 | 0.00 | 0.00 | 0.500176E+11 | 0.00 | 17.96 |
April | 0.00 | 0.760375E+09 | 0.00 | 0.105090E+09 | 0.00 | 0.00 | 0.347824E+11 | 0.00 | 18.67 |
May | 0.00 | 0.449270E+10 | 0.00 | 73717261.70 | 0.00 | 0.00 | 0.186381E+11 | 0.00 | 17.86 |
June | 0.00 | 0.171743E+11 | 0.00 | 29822301.10 | 0.00 | 0.00 | 0.654068E+10 | 0.00 | 15.32 |
July | 0.00 | 0.281847E+11 | 0.00 | 3963820.04 | 0.00 | 0.00 | 0.707543E+09 | 0.00 | 13.86 |
August | 0.00 | 0.322917E+11 | 0.00 | 2613952.13 | 0.00 | 0.00 | 0.356804E+09 | 0.00 | 13.73 |
September | 0.00 | 0.132396E+11 | 0.00 | 47035752.48 | 0.00 | 0.00 | 0.120230E+11 | 0.00 | 16.48 |
October | 0.00 | 0.331303E+10 | 0.00 | 93605011.98 | 0.00 | 0.00 | 0.405056E+11 | 0.00 | 17.67 |
November | 0.00 | 0.103878E+09 | 0.00 | 0.105097E+09 | 0.00 | 0.00 | 0.517768E+11 | 0.00 | 17.04 |
December | 0.00 | 161266.64 | 0.00 | 0.110878E+09 | 0.00 | 0.00 | 0.618612E+11 | 0.00 | 14.40 |
Annual Sum or Average | 0.00 | 0.996144E+11 | 0.00 | 0.898689E+09 | 0.00 | 0.00 | 0.388848E+12 | 0.00 | 15.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2613952.13 | 0.00 | 0.00 | 0.356804E+09 | 0.00 | 13.16 |
Maximum of Months | 0.00 | 0.322917E+11 | 0.00 | 0.113950E+09 | 0.00 | 0.00 | 0.618612E+11 | 0.00 | 18.67 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.465922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214891E+10 | 0.00 | 0.00 | 0.36 |
February | 0.467612E+10 | 0.00 | 0.00 | 0.00 | 147916.04 | 0.106791E+10 | 0.00 | 0.00 | 0.40 |
March | 0.525274E+10 | 2794060.51 | 0.00 | 483111.76 | 2071967.02 | 0.00 | 0.266558E+09 | 0.00 | 0.46 |
April | 0.308568E+10 | 40610881.21 | 0.00 | 3483315.42 | 32234722.60 | 0.00 | 0.101554E+10 | 0.00 | 0.51 |
May | 0.825810E+09 | 0.598439E+09 | 0.00 | 5294543.07 | 5178610.48 | 0.00 | 0.162600E+10 | 0.00 | 0.56 |
June | 0.192582E+09 | 0.280561E+10 | 0.00 | 3009657.10 | 70584.29 | 0.00 | 0.736697E+09 | 0.00 | 0.60 |
July | 4412228.53 | 0.479644E+10 | 0.00 | 468202.29 | 3773511.93 | 0.00 | 0.110925E+09 | 0.00 | 0.60 |
August | 0.00 | 0.568110E+10 | 0.00 | 339677.78 | 0.00 | 0.00 | 57771290.73 | 0.00 | 0.61 |
September | 0.648674E+09 | 0.183628E+10 | 0.00 | 3380041.69 | 4170519.35 | 0.00 | 0.857356E+09 | 0.00 | 0.55 |
October | 0.390724E+10 | 0.309807E+09 | 0.00 | 1481049.11 | 57935023.32 | 0.00 | 0.636026E+09 | 0.00 | 0.47 |
November | 0.568811E+10 | 881899.70 | 0.00 | 0.00 | 8045741.68 | 92793485.67 | 0.00 | 0.00 | 0.44 |
December | 0.649631E+10 | 0.00 | 0.00 | 0.00 | 13612.73 | 0.447488E+09 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.354369E+11 | 0.160720E+11 | 0.00 | 17939598.22 | 0.113642E+09 | 0.375710E+10 | 0.530688E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.649631E+10 | 0.568110E+10 | 0.00 | 5294543.07 | 57935023.32 | 0.214891E+10 | 0.162600E+10 | 0.00 | 0.61 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.178151E+12 | 0.803308E+10 | 0.223377E+12 | 0.625447E+12 | 0.325573E+11 |
February | 0.185948E+12 | 0.599075E+10 | 0.160535E+12 | 0.487701E+12 | 0.735089E+11 |
March | 0.276435E+12 | 0.460715E+10 | 0.114198E+12 | 0.394826E+12 | 0.194146E+12 |
April | 0.312517E+12 | 0.277319E+10 | 0.679532E+11 | 0.278153E+12 | 0.361205E+12 |
May | 0.344137E+12 | 0.648621E+09 | 0.118674E+11 | 0.102852E+12 | 0.645711E+12 |
June | 0.350949E+12 | -0.234069E+10 | -0.717431E+11 | -0.152674E+12 | 0.972775E+12 |
July | 0.326411E+12 | -0.449572E+10 | -0.130690E+12 | -0.334442E+12 | 0.121464E+13 |
August | 0.301233E+12 | -0.532948E+10 | -0.151958E+12 | -0.409315E+12 | 0.128792E+13 |
September | 0.225940E+12 | -0.126024E+10 | -0.389538E+11 | -0.538720E+11 | 0.838307E+12 |
October | 0.215177E+12 | 0.286022E+10 | 0.720001E+11 | 0.290768E+12 | 0.367269E+12 |
November | 0.148773E+12 | 0.474296E+10 | 0.124120E+12 | 0.429655E+12 | 0.152300E+12 |
December | 0.141462E+12 | 0.646285E+10 | 0.178379E+12 | 0.535216E+12 | 0.527460E+11 |
Annual Sum or Average | 0.300713E+13 | 0.226927E+11 | 0.559084E+12 | 0.219432E+13 | 0.619309E+13 |
Minimum of Months | 0.141462E+12 | -0.532948E+10 | -0.151958E+12 | -0.409315E+12 | 0.325573E+11 |
Maximum of Months | 0.350949E+12 | 0.803308E+10 | 0.223377E+12 | 0.625447E+12 | 0.128792E+13 |