Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904

Simulation Timestamp: 2024-07-03 12:21:30


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 9098.96 802.00 802.00
Net Site Energy 9098.96 802.00 802.00
Total Source Energy 19572.47 1725.16 1725.16
Net Source Energy 19572.47 1725.16 1725.16


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 169.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 661.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 546.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 193.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1648.46 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 813.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 590.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 68.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 94.78 2479.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 44.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 4661.16 4437.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 169.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 661.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 546.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 193.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 872.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 8.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 4.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 21.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 789.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 590.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 68.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 94.78 2479.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 15.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 21.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 169.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 661.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 546.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 193.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1648.46 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 813.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 590.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 68.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 94.78 2479.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 44.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 124.71 233.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 220.91 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 410.85 391.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 124.71 233.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 220.91 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 410.85 391.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 4661.157 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 4661.157 100.00
     
Total On-Site and Utility Electric Sources 4661.157 100.00
Total Electricity End Uses 4661.157 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 63.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 7314.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| FLR_3_DOAS | VAV WITH REHEAT |

AirLoopSystemComponentLoadsMonthly

| FLR_3_DOAS | VAV WITH REHEAT |

AirLoopSystemComponentEnergyUseMonthly

| FLR_3_DOAS | VAV WITH REHEAT |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
RunPeriod RUNPERIOD 1
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Latitude [deg] 32.58
Longitude [deg] -117.0
Elevation [m] 159.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 6.7179 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 9.6995 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 9.6995 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 4.6285 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 4.2862 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.7049 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 9.2569 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 9.0417 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.4132 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.4132 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 4.4132 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.4132 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 9.2569 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 9.2569 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.7327 4.65 2931.5031
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 4.4132 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.8577 7.07 41.0437
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.8577 7.07 41.0437
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 6.7179 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 9.6995 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 9.6995 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 4.6285 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 4.2862 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.7049 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 9.2569 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 9.0417 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.4132 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.4132 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.4132 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.4132 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.4132 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.4132 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 4.4132 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.4132 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.4132 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.4132 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 9.2569 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 9.2569 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.7327 4.65 2931.5031  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 4.4132 18.58 0.0000  
Total 11345.29             5.8577 3.54 41.0437  
Conditioned Total 11345.29             5.8577 3.54 41.0437  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 3.7137 8.82 37.1717
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-SEP-18:00 06-JAN-22:00 - - - - - - - - - - 05-MAY-20:30
Heating 0.00 70568.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 102034.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 40691.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 12338.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 77265.07 54264.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 28151.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 27841.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 3545.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4751.07 212863.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1314.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 297934.06 337696.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 70568.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 102034.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 40691.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 12338.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 47590.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 24992.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 29272.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1032.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 26968.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 27841.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 3545.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4751.07 212863.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 228.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 426.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 658.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 184.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2095.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1729.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 614.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5220.66 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2576.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1868.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 216.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 300.17 2687.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 140.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 14761.89 4810.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 16.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 184.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 152.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 54.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 460.16 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 227.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 164.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 19.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 26.46 236.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1301.15 424.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 16.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 184.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 152.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 54.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 460.16 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 227.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 164.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 19.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 26.46 236.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1301.15 424.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.14 0.703568 0.598000 1.28 1.00 0.500000 0.000542 0.000058 1.28 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.303135 0.168600 0.392000 0.118829 0.467041 0.500000 0.002260 0.000020 0.118829 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.218135 0.271317 0.631000 0.137643 0.723511 0.500000 0.001404 0.000011 0.137643 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.177412 0.705438 0.010000 0.001774 1.00 0.500000 0.000540 0.000011 0.043333 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.096538 0.747960 0.898000 0.086691 1.00 0.500000 0.000509 0.000010 0.086691 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.30 0.018022 0.010000 0.032996 0.300000 0.500000 0.021141 0.000014 0.056828 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.37 0.105314 0.742000 1.01 0.742000 0.500000 0.003618 0.000083 1.01 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.50 0.221580 0.632000 2.84 0.632000 0.500000 0.001719 0.000215 2.84 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.11 1.00 0.641000 0.712251 1.00 0.500000 0.000357 0.000084 0.712251 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.10 0.120503 0.850000 1.78 0.850000 0.500000 0.003162 0.000115 1.78 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.20 0.114684 0.809000 1.78 0.809000 0.500000 0.003322 0.000115 1.78 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.15 0.065893 0.256000 0.550064 0.300000 0.500000 0.010400 0.000034 0.550064 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.627156 0.500735 0.300000 0.188147 1.00 0.500000 0.000761 0.000045 0.188147 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 6641.11 0.000058 138.49
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2270.30 0.000020 55.15
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1269.74 0.000011 27.60
MECH_FLR_1 VAV BOX REHEAT COIL 1216.62 0.000011 33.20
STORAGE_FLR_1 VAV BOX REHEAT COIL 1114.09 0.000010 25.18
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 1595.50 0.000014 43.54
CAFE_FLR_1 VAV BOX REHEAT COIL 9464.77 0.000083 205.97
LOBBY_FLR_1 VAV BOX REHEAT COIL 24529.72 0.000215 529.86
ROOM_1_FLR_3 FAN COIL HEATING COIL 3518.50 0.000031 100.53
ROOM_2_FLR_3 FAN COIL HEATING COIL 3518.56 0.000031 100.53
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 20516.37 0.000179 586.19
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 20527.82 0.000180 586.52
ROOM_5_FLR_3 FAN COIL HEATING COIL 3517.97 0.000031 100.52
ROOM_6_FLR_3 FAN COIL HEATING COIL 3518.03 0.000031 100.52
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 9565.47 0.000084 217.58
ROOM_1_FLR_6 FAN COIL HEATING COIL 1103.83 0.000010 31.54
ROOM_2_FLR_6 FAN COIL HEATING COIL 1103.51 0.000010 31.53
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 5348.55 0.000047 152.82
BANQUET_FLR_6 VAV BOX REHEAT COIL 13090.60 0.000115 279.03
DINING_FLR_6 VAV BOX REHEAT COIL 13179.06 0.000115 281.06
KITCHEN_FLR_6 VAV BOX REHEAT COIL 3862.15 0.000034 82.05
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 5114.35 0.000045 137.86
FLR_3_DOAS HEATING COIL 9427.25 0.000082 168.97
VAV WITH REHEAT HEATING COIL 92765.46 0.000812 1662.67
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 0.905932 0.000031 0.000284
ROOM_2_FLR_3 FAN COIL 0.869795 0.000031 0.000273
ROOM_3_MULT19_FLR_3 FAN COIL 5.33 0.000179 0.001636
ROOM_4_MULT19_FLR_3 FAN COIL 4.99 0.000180 0.001652
ROOM_5_FLR_3 FAN COIL 0.802420 0.000031 0.000252
ROOM_6_FLR_3 FAN COIL 0.770767 0.000031 0.000243
ROOM_1_FLR_6 FAN COIL 0.235626 0.000010 0.000074
ROOM_2_FLR_6 FAN COIL 0.225690 0.000010 0.000071
ROOM_3_MULT9_FLR_6 FAN COIL 1.10 0.000047 0.000350
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL_FANCOILFAN 0.905932
ROOM_2_FLR_3 FAN COIL_FANCOILFAN 0.869795
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN 5.33
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN 4.99
ROOM_5_FLR_3 FAN COIL_FANCOILFAN 0.802420
ROOM_6_FLR_3 FAN COIL_FANCOILFAN 0.770767
ROOM_1_FLR_6 FAN COIL_FANCOILFAN 0.235626
ROOM_2_FLR_6 FAN COIL_FANCOILFAN 0.225690
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN 1.10
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008579 12.80 0.008500 0.000284 0.905932  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008583 12.80 0.008500 0.000273 0.869795  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008497 12.80 0.008497 0.001636 5.33  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008782 12.80 0.008500 0.001652 4.99  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008589 12.80 0.008500 0.000252 0.802420  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008593 12.80 0.008500 0.000243 0.770767  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008576 12.80 0.008500 0.000074 0.235626  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008580 12.80 0.008500 0.000071 0.225690  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008651 12.80 0.008500 0.000350 1.10  
FLR_3_DOAS COOLING COIL 31.30 6.70 0.008233 11.91 0.008233 0.001371 2.05 47946.25
VAV WITH REHEAT COOLING COIL 27.37 6.70 0.009052 10.94 0.008500 0.012397 20.19 433469.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
VAV WITH REHEAT 12.92 10.53 20.29 10.53 20.19 20.19 0.300000 0.521796 20.19
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
VAV WITH REHEAT_OA_CONTROLLER 20.19  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
FLR_3_DOAS_COOLC_CONTROLLER 0.001371 0.000347
FLR_3_DOAS_HEATC_CONTROLLER 0.000082  
VAV WITH REHEAT_COOLC_CONTROLLER 0.012397 0.000038
VAV WITH REHEAT_HEATC_CONTROLLER 0.000812  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 20.19
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.018604 3007.35  
HEATSYS1 PUMP 0.002255 672.43 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.002255 0.270620
COOLSYS1 0.018604 2.23
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 257779.33 257779.33 0.002255
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.018604 2082.09
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.018604 650484.22 651062.22 74.22
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.80 14.30 13.60 13.20 13.30 12.60 15.30 15.60 17.70 19.40 19.70 18.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 32.58 -116.98 -8.00 159.00 99429 1.1818


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.00 7.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 6.718 5.380 0.000 0.000 0.000 0.000 12.098 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 9.699 10.760 0.000 0.000 0.000 0.000 20.459 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 9.699 10.760 0.000 0.000 0.000 0.000 20.459 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 4.628 5.380 0.000 0.000 0.000 0.000 10.008 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 4.286 2.690 0.000 0.000 0.000 0.000 6.976 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.705 61.680 535.850 0.000 0.000 0.000 603.235 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 9.257 5.380 0.000 0.000 0.000 0.000 14.637 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 9.042 8.070 0.000 0.000 0.000 0.000 17.112 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 4.413 0.000 0.000 0.000 0.000 0.000 4.413 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 9.257 67.820 0.000 0.000 0.000 0.000 77.077 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 9.257 67.820 0.000 0.000 0.000 0.000 77.077 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.733 512.243 2419.260 0.000 0.000 0.000 2943.236 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 4.413 0.000 0.000 0.000 0.000 0.000 4.413 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 13293.583 6.718 124.824 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 13293.583
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 650.557 9.699 60.075 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 650.557
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 753.347 9.699 60.076 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 753.347
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 760.196 4.628 286.650 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 760.196
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 406.155 4.286 199.096 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 406.155
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 445.205 5.705 53.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 445.205
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1748.285 9.257 12.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1748.285
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 11828.200 9.042 28.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11828.200
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 108.229 4.413 72.152 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.229
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 108.258 4.413 72.172 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.258
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 1718.521 4.413 82.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1718.521
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 108.258 4.413 72.172 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.258
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3070.136 9.257 12.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3070.136
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3070.136 9.257 12.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3070.136
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1212.035 11.733 54.503 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1212.035
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 1818.789 4.413 82.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1818.789


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 277.500 2.686 12.479 0.000 0.250 0.000 0.750 ReachInFreezer 277.500 277.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 156.700 1.517 7.046 0.000 0.250 0.000 0.750 ReachInRefrigerator 156.700 156.700


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 2.390 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.9589 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.167 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.181 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.021 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.034 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.3181 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.3181 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.4184
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.8756
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.6894
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6793
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8120
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.7993
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 2.883
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 2.883
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 2.3900722 2.3900722 2.3900722  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
21 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
22 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
23 0 21.361010 0.87247630E-01 5.4456762  
24 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
25 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
26 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
27 0 21.361010 0.87247630E-01 5.4456762  
28 9 -0.56372661E-17 0.35603042E-16 -0.14834456E-09 -0.22354951E-17
29 8 0.21681598E-07 0.12895413E-12 0.37576420E-03 -0.24652724E-09
30 7 -0.12181032E-01 0.67087143E-08 -0.22998674E-01 0.13850277E-03
31 6 0.40370585 0.23395349E-05 0.47069069 -0.47283774E-02
32 5 -5.1745154 0.87537405E-04 -4.4305073 0.62984858E-01
33 4 32.931872 0.71743813E-03 21.398312 -0.42118042
34 3 -111.07522 0.15662534E-02 -55.540939 1.5130129
35 2 196.98158 0.88235367E-03 77.798628 -2.8983416
36 1 -171.10930 0.94326468E-04 -55.232514 2.7446195
37 0 57.057407 0.53780718E-06 15.562302  
38 9 0.13788181E-14 0.42316407E-16 -0.13850765E-09 -0.36591458E-17
39 8 0.20295421E-07 0.15509090E-12 0.36099725E-03 -0.23076592E-09
40 7 -0.11739701E-01 0.81955471E-08 -0.22363010E-01 0.13348467E-03
41 6 0.39171309 0.28760220E-05 0.46045976 -0.45870120E-02
42 5 -5.0574682 0.10819265E-03 -4.3518524 0.61533536E-01
43 4 32.414067 0.89103805E-03 21.090697 -0.41430552
44 3 -109.97331 0.19536482E-02 -54.932704 1.4970936
45 2 195.88922 0.11048200E-02 77.241099 -2.8809953
46 1 -170.70571 0.11852782E-03 -55.070977 2.7375462
47 0 57.057407 0.67841551E-06 15.589460  
48 9 0.13857471E-14 0.43057560E-16 -0.13784678E-09 -0.68945926E-17
49 8 0.20202246E-07 0.15680163E-12 0.35999259E-03 -0.22970649E-09
50 7 -0.11709634E-01 0.82948599E-08 -0.22319691E-01 0.13314280E-03
51 6 0.39089600 0.29121450E-05 0.45976168 -0.45773805E-02
52 5 -5.0494928 0.10959277E-03 -4.3464810 0.61434646E-01
53 4 32.378781 0.90287364E-03 21.069680 -0.41383702
54 3 -109.89821 0.19801908E-02 -54.891143 1.4960086
55 2 195.81476 0.11201274E-02 77.203021 -2.8798128
56 1 -170.67819 0.12019965E-03 -55.059979 2.7370639
57 0 57.057407 0.68811227E-06 15.591337  
58 9 0.14302076E-15 0.35792568E-16 -0.14541430E-09 -0.27421543E-17
59 8 0.21269444E-07 0.13686051E-12 0.37140784E-03 -0.24184090E-09
60 7 -0.12050952E-01 0.71525680E-08 -0.22811354E-01 0.13702371E-03
61 6 0.40017121 0.24988627E-05 0.46767819 -0.46867126E-02
62 5 -5.1400200 0.93645327E-04 -4.4073602 0.62557131E-01
63 4 32.779281 0.76858103E-03 21.307814 -0.41915444
64 3 -110.75053 0.16800125E-02 -55.362013 1.5083221
65 2 196.65975 0.94749847E-03 77.634567 -2.8932310
66 1 -170.99041 0.10139533E-03 -55.184883 2.7425359
67 0 57.057407 0.57877233E-06 15.570231  
68 9 0.33566835E-16 0.35384250E-16 -0.14478218E-09 -0.87565041E-18
69 8 0.21180494E-07 0.13854999E-12 0.37046393E-03 -0.24082951E-09
70 7 -0.12022754E-01 0.72481687E-08 -0.22770744E-01 0.13670309E-03
71 6 0.39940498 0.25332696E-05 0.46702484 -0.46776806E-02
72 5 -5.1325420 0.94967185E-04 -4.4023386 0.62464408E-01
73 4 32.746200 0.77967008E-03 21.288178 -0.41871522
74 3 -110.68014 0.17047184E-02 -55.323188 1.5073051
75 2 196.58997 0.96166638E-03 77.598974 -2.8921229
76 1 -170.96463 0.10293464E-03 -55.174560 2.7420841
77 0 57.057407 0.58770932E-06 15.571958  
78 7 -0.11407965E-14 0.23474115E-16 -0.22119674E-13 0.51962024E-15
79 6 0.16676876E-10 0.39440661E-11 0.52102403E-09 -0.18553030E-10
80 5 -0.80001662E-07 0.19215958E-07 -0.21848785E-05 0.17095694E-06
81 4 0.10228101E-03 0.72538432E-05 0.17630655E-02 -0.28160064E-03
82 3 -0.15120274E-01 0.25611913E-03 -0.21515117 0.43248511E-01
83 2 0.21482172 0.11124906E-02 2.8969963 -0.61829830
84 1 -0.54366453 0.69706713E-03 -7.1337069 1.5687761
85 0 0.34594624 0.12518961E-04 4.4521846  
86 7 -0.22119674E-13 0.23474115E-16 -0.11407965E-14 0.51962024E-15
87 6 0.52102403E-09 0.39440661E-11 0.16676876E-10 -0.18553030E-10
88 5 -0.21848785E-05 0.19215958E-07 -0.80001662E-07 0.17095694E-06
89 4 0.17630655E-02 0.72538432E-05 0.10228101E-03 -0.28160064E-03
90 3 -0.21515117 0.25611913E-03 -0.15120274E-01 0.43248511E-01
91 2 2.8969963 0.11124906E-02 0.21482172 -0.61829830
92 1 -7.1337069 0.69706713E-03 -0.54366453 1.5687761
93 0 4.4521846 0.12518961E-04 0.34594624  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.43_SHGC_0.248 37 1 VerySmooth 2.443 2.443 1.000 0.249    
2 RESWINDOW_U_0.43_SHGC_0.248 38 1 VerySmooth 2.443 2.443 1.000 0.249    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   2.91147E-002 0.15938 0.62162 0.62162 0.27280 0.15674 0.22697 0.00000 0.84000 0.84000 0.12243 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   2.91147E-002 0.15938 0.62162 0.62162 0.27280 0.15674 0.22697 0.00000 0.84000 0.84000 0.12243 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 2.320
2 RACK2 1 0 Zone Air-Cooled 6.980


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 11.511 0.4388
2 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.219 1.1187
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 5.775 0.3748


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 1.764E-002 2.631E-004 1.298E-004 0.239 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 6.811E-003 8.769E-005 2.388E-004 7.967E-002 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 1.610E-002 9.800E-005 2.563E-004 8.904E-002 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 9.287E-003 9.800E-005 2.127E-004 8.904E-002 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 2.198E-002 2.816E-004 2.506E-004 0.256 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 3.900E-002 2.065E-004 1.137E-004 0.188 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.111 8.519E-005 1.629E-004 7.740E-002 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 1.024E-002 2.624E-004 2.563E-004 0.310 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 1.024E-002 2.624E-004 2.563E-004 0.310 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 2.857E-003 1.165E-004 2.563E-004 0.138 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 2.858E-003 1.165E-004 2.563E-004 0.138 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 1.024E-002 2.624E-004 2.563E-004 0.310 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 1.024E-002 2.624E-004 2.563E-004 0.310 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 1.238E-002 3.180E-005 2.563E-004 3.755E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 1.024E-002 2.624E-004 1.297E-004 0.310 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 1.024E-002 2.624E-004 1.297E-004 0.310 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 5.239E-003 2.136E-004 1.165E-004 0.252 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 2.500E-002 7.539E-005 5.825E-005 8.904E-002 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 2.500E-002 7.539E-005 5.825E-005 8.904E-002 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 2.238E-002 2.167E-004 1.174E-004 0.256 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 2.191E-002 5.316E-005 4.403E-005 6.278E-002 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 9.4948E-002
2 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.2664E-002
3 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1055
4 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.6571E-002
5 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 7.1675E-002
6 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 2.6641E-002
7 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 2.8929E-002
8 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 9.5818E-003
9 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1073
10 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.2191E-002
11 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1194
12 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.6910E-002
13 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 7.9345E-002
14 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 3.3627E-002
15 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 3.2502E-002
16 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.3131E-002
17 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.3103E-002
18 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.3205E-002
19 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.7800E-002
20 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.9750E-003
21 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.7027E-002
22 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 6.8012E-003
23 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.8489E-002
24 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.0072E-002
25 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.3103E-002
26 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.3205E-002
27 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.7800E-002
28 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.9750E-003
29 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.7027E-002
30 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 6.8012E-003
31 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.8489E-002
32 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.0072E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 28948.45805 28948.45805 2.14317 2.14317 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:30:00 27.33950 8.22721E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446   00:10:00 3.80000 5.05843E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 4094.15278 4094.15278 0.30313 0.30313 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 30.92917 8.23290E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 1654.77247 1654.77247 7.22713E-002 7.92179E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 2946.08982 2946.08982 0.21814 0.21814 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 30.05400 8.23151E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 556.76526 556.76526 2.43166E-002 9.17347E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 2396.62178 2396.62178 0.17741 0.17741 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 28.49650 8.22904E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 992.18449 992.18449 4.33334E-002 4.33334E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1304.09791 1304.09791 9.65380E-002 9.65380E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 31.21100 8.23335E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 665.06577 665.06577 2.90466E-002 5.77652E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44569.35995 44569.35995 3.29960 3.29960 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 31.30000 8.23349E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 1301.18489 1301.18489 5.68285E-002 5.68285E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 18440.62601 18440.62601 1.36651 1.36651 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 30.92917 8.23290E-003 188.86188 142.30000 0.67638 0.00000
14 CAFE_FLR_1 Heating 4212.29606 4212.29606 0.18397 0.67638 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 188.86188 142.30000 0.67638 0.00000
15 LOBBY_FLR_1 Cooling 60742.68390 60742.68390 4.49878 4.49878 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.07750 8.23314E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 9801.87249 9801.87249 0.42809 1.89399 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 9081.10057 9081.10057 0.90593 0.90593 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 30.52867 8.23226E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 3518.52410 3518.52410 0.15457 0.15457 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 8718.85953 8718.85953 0.86979 0.86979 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 3518.58465 3518.58465 0.15457 0.15457 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 53460.13542 53460.13542 5.33295 5.33295 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.07750 8.23314E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 20516.42567 20516.42567 0.90131 0.90131 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 50034.95279 50034.95279 4.99167 4.99167 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 31.30000 8.23349E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 20527.87842 20527.87842 0.90182 0.90182 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 8043.49410 8043.49410 0.80242 0.80242 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 27.16150 8.22694E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 3517.98520 3517.98520 0.15455 0.15455 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 7726.19724 7726.19724 0.77077 0.77077 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 26.65717 8.22614E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 3518.04572 3518.04572 0.15455 0.15455 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 15009.05311 15009.05311 1.11116 1.11116 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 31.30000 8.23349E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 5875.68908 5875.68908 0.25662 0.47476 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2361.93090 2361.93090 0.23563 0.23563 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 30.52867 8.23226E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1103.83363 1103.83363 4.84925E-002 4.84925E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2262.32449 2262.32449 0.22569 0.22569 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1103.51408 1103.51408 4.84785E-002 4.84785E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 10976.56951 10976.56951 1.09505 1.09505 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.07750 8.23314E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 5348.57708 5348.57708 0.23497 0.23497 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 28293.20591 28293.20591 2.09723 2.09723 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 31.30000 8.23349E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 3855.24774 3855.24774 0.16838 1.18780 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 29729.45688 29729.45688 2.20365 2.20365 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 31.30000 8.23349E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 3943.24902 3943.24902 0.17222 1.18780 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 3.80000 5.05843E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 28947.41488 28947.41488 2.14869 2.14869 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 30.49900 8.23222E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 1024.76956 1024.76956 4.47516E-002 0.36735 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 3.80000 5.05843E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 8471.46201 8471.46201 0.62716 0.62716 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 31.22583 8.23338E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 4139.58687 4139.58687 0.18080 0.18080 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 3.80000 5.05843E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 FLR_3_DOAS Cooling Sensible 45064.07 14.48699 2.05125 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 FLR_3_DOAS Heating Sensible 31423.05 2.75332 2.05125 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
3 VAV WITH REHEAT Cooling Sensible 349105.35 20.18526 20.18526 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 VAV WITH REHEAT Heating Sensible 109563.25 7.15211 7.15211 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:30:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.14317
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.70357
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.59800
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.28162
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.41526E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.80993E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.28162
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6641.11042
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.80993E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 138.48891
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.30313
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16860
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.39200
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11883
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.46704
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.25979E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.98616E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.11883
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2270.30202
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.98616E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 55.14921
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.21814
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27132
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.63100
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13764
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.72351
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.40426E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.11082E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13764
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1269.73684
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.11082E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 27.59949
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.17741
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.70544
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000E-002
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.77412E-003
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.40090E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.06435E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.33334E-002
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1216.62037
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.06435E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 33.20372
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.65380E-002
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.74796
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.89800
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.66911E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.09385E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.74655E-006
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.66911E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1114.09070
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.74655E-006
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 25.17915
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.29960
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.80222E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000E-002
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.29960E-002
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.11406E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.39582E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.68285E-002
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1595.50399
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.39582E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 43.54411
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.36651
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10531
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.74200
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.01395
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.74200
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.61775E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.28019E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.01395
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9464.77094
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.28019E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 205.96791
99 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.49878
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22158
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.63200
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.84323
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.63200
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.71947E-003
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.14597E-004
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.84323
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24529.72372
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.14597E-004
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 529.85689
113 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
114 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.90593
115 Fan:OnOff ROOM_1_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.90593
116 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.07814E-005
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.84116E-004
118 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69391
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57936E-003
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.84116E-004
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.90593
125 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3518.50397
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.07814E-005
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 100.53116
128 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
129 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.86979
130 Fan:OnOff ROOM_2_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.86979
131 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.07819E-005
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.73022E-004
133 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69391
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58255E-003
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.73022E-004
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.86979
140 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3518.56452
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.07819E-005
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 100.53289
143 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
144 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.33295
145 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 5.33295
146 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.79486E-004
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.63624E-003
148 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69437
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.49744E-003
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.49744E-003
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.63624E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.33295
155 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 20516.36887
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.79486E-004
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 586.19136
158 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
159 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 4.99167
160 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 4.99167
161 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.79586E-004
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.65223E-003
163 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69340
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.78192E-003
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.65223E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 4.99167
170 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 20527.82160
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.79586E-004
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 586.51857
173 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
174 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.80242
175 Fan:OnOff ROOM_5_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.80242
176 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.07767E-005
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.52351E-004
178 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69390
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58949E-003
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.52351E-004
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.80242
185 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3517.96507
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.07767E-005
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 100.51576
188 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
189 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.77077
190 Fan:OnOff ROOM_6_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.77077
191 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.07772E-005
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.42637E-004
193 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69389
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.59313E-003
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.42637E-004
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.77077
200 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3518.02559
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.07772E-005
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 100.51749
203 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.11116
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.64100
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.71225
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.56684E-004
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.36829E-005
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.71225
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
214 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9565.46598
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.36829E-005
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 217.57719
217 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
218 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.23563
219 Fan:OnOff ROOM_1_FLR_6 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.23563
220 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 9.65676E-006
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 7.38361E-005
222 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69392
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57636E-003
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.38361E-005
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.23563
229 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1103.82755
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.65676E-006
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 31.53802
232 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
233 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.22569
234 Fan:OnOff ROOM_2_FLR_6 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.22569
235 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 9.65397E-006
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 7.07856E-005
237 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69391
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57963E-003
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.07856E-005
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.22569
244 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1103.50800
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.65397E-006
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 31.52889
247 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
248 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.09505
249 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 1.09505
250 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.67915E-005
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.50133E-004
252 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69361
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.65077E-003
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.50133E-004
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.09505
259 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5348.55344
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.67915E-005
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 152.81566
262 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.09723
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12050
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.85000
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.78264
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.85000
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.16174E-003
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.14522E-004
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.78264
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
273 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13090.60349
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.14522E-004
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 279.02806
276 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.20365
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11468
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.80900
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.78276
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.80900
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.32218E-003
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.15296E-004
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.78276
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
287 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13179.06175
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.15296E-004
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 281.05552
290 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.14869
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.58933E-002
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25600
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.55006
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.03998E-002
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.37877E-005
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.55006
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
301 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3862.14606
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.37877E-005
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 82.05076
304 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.62716
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.50074
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.18815
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.60881E-004
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.47425E-005
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.18815
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
315 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5114.34684
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.47425E-005
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 137.85875
318 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
319 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
320 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
321 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
322 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
323 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
324 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
325 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
326 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 12.91877
327 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 10.53259
328 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 20.29116
329 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 10.53259
330 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 20.18526
331 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 20.18526
332 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
333 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.52180
334 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 20.18526
336 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
338 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 31.30000
339 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
340 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.91243
341 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.23349E-003
342 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.23349E-003
343 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 47946.24805
344 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.37126E-003
345 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
346 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 9427.24706
347 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.24737E-005
348 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 168.96790
349 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
350 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.37126E-003
351 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 3.47266E-004
352 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.24737E-005
353 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 20.18526
354 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.36886
355 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
356 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.94422
357 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.05165E-003
358 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
359 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 433469.04399
360 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.23972E-002
361 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 20.18526
362 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 92765.45985
363 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.11553E-004
364 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1662.66836
365 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 20.18526
366 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.23972E-002
367 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 3.84113E-005
368 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.11553E-004
369 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 1.86038E-002
370 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 3007.35305
371 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.25517E-003
372 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.27062
373 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.25517E-003
374 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 672.43264
375 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
376 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 257779.32866
377 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 257779.33000
378 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.25517E-003
379 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 1.86038E-002
380 PlantLoop COOLSYS1 Plant Loop Volume [m3] 2.23245
381 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 1.86038E-002
382 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 2082.09195
383 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 1.86038E-002
384 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 650484.22187
385 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 651062.22000
386 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 74.22109
387 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
388 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
389 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
390 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
391 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 6675.46
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2280.17
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1276.06
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 1221.25
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1119.36
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 1601.57
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 9511.89
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 24652.61
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 3789.49
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 3789.55
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 22096.37
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 22108.70
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 3788.91
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 3788.97
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 9610.41
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1188.83
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1188.48
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 5760.39
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 13156.96
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 13245.84
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 3881.78
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 5134.03
23 Coil:Heating:Water FLR_3_DOAS HEATING COIL 7911.32
24 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 77848.54


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 14804.80 12737.57 2067.23 0.86 2995.50 30.38
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 14222.73 12232.35 1990.37 0.86 2875.08 29.16
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 85859.58 74551.50 11308.08 0.87 17803.90 180.58
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 84632.82 71255.40 13377.42 0.84 16291.75 165.24
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 13137.99 11290.59 1847.40 0.86 2650.53 26.88
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 12630.14 10849.51 1780.63 0.86 2547.87 25.84
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 3848.47 3312.22 536.25 0.86 779.35 7.90
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 3688.43 3173.30 515.12 0.86 746.23 7.57
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 18134.55 15479.34 2655.22 0.85 3600.54 36.52
10 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 51303.12 35829.51 15473.61 0.70 7298.17 74.02
11 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 500759.57 351957.62 148801.96 0.70 78984.18 801.10


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 4.09 13.95


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.390 2.390   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.167 0.994   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.167 0.994   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.167 0.994   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.167 0.994   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.43_SHGC_0.248 N/A 2.443 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.7073392109E-002 2.1880179877E-002 Pass Pass 6.2736193795E-003 1.8168516968E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 4.3079072414E-002 6.1020741193E-002 Pass Pass 3.1793737480E-002 5.0695799015E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 2.4454434494E-002 2.9728137915E-002 Pass Pass 9.8596289182E-003 2.3972927018E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 1.6146674699E-002 1.6526254435E-002 Pass Pass 6.5383839304E-003 1.7919319984E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 4.8448023187E-004 3.3626485019E-004 Pass Pass 1.7195041593E-002 2.3452959596E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 9.4381793265E-005 1.4331591362E-004 Pass Pass 2.0736513831E-002 5.9936329615E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 3.3768952878E-002 5.8314679702E-002 Pass Pass 2.0917936061E-002 4.6361336343E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 3.7764571124E-002 4.3863126322E-002 Pass Pass 8.7564019584E-003 2.1125263632E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 3.7091437050E-002 0.1007035951 Pass Pass 0.8746991736 6.0560307186 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 2.4879996064E-002 5.8769046521E-002 Pass Pass 0.1968559656 1.2844983553 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 5.2081029841E-002 6.7739971619E-002 Pass Pass 1.8497624854E-002 0.1087216306 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 4.6801049582E-002 0.1327696449 Pass Pass 0.2387225805 1.0496612917 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 5.1666507394E-002 0.1883268106 Pass Pass 0.3349392454 1.1887846961 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 3.9907700086E-002 0.1592080022 Pass Pass 0.4451573234 1.8297932707 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 3.5049231002E-003 7.3536180867E-003 Pass Pass 2.2537216286E-002 4.2925753978E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 3.7732867369E-002 7.9694997711E-002 Pass Pass 0.2069973502 0.7713530175 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 4.1479803532E-002 0.1130728155 Pass Pass 8.9685681779E-002 0.2981086681 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 7.9734612305E-002 0.2329171998 Pass Pass 0.2424947102 0.6009619923 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 5.0370235561E-002 9.4095639888E-002 Pass Pass 1.0042386646E-002 2.1099078132E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 5.2155240258E-002 9.3507099310E-002 Pass Pass 9.5170732063E-003 2.1418828056E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 8.9950394058E-004 1.6385538545E-003 Pass Pass 2.3144404363E-002 4.3326720343E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 1.8127299494E-002 1.4471274103E-002 Pass Pass 7.8940684434E-003 2.0842297669E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3533.89 38.10 985.07 3873.77 3754.70 12185.53



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 3.80 0.00 3.80 Wetbulb [C] 3.00 120.00
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 31.30 8.90 18.40 Wetbulb [C] 4.10 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 2.00 2      
Feb 59.00 53      
Mar 58.58 43      
Apr 46.42 14      
May 18.00 12      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 3.00 6      
Oct 0.00 0      
Nov 18.00 12      
Dec 4.00 4      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.886 1.021 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.886 1.021 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.886 1.021 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.886 1.021 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.886 1.021 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.886 1.021 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.886 1.021 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.886 1.021 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.886 1.021 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.886 1.021 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 0.994 1.167 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 0.994 1.167 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 0.994 1.167 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 0.994 1.167 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.896 1.034 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.896 1.034 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.896 1.034 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.896 1.034 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.896 1.034 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.004 1.181 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.221 0.228 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.293 0.318 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.293 0.318 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.293 0.318 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.293 0.318 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.293 0.318 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.293 0.318 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.293 0.318 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.293 0.318 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.293 0.318 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.293 0.318 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.298 0.318 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.288 0.318 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.288 0.318 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.288 0.318 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.298 0.318 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.298 0.318 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.298 0.318 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   23.26 0.00 0.00 23.26 23.26 2.443 0.249 0.274             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   65.50 0.00 0.00 65.50 65.50 2.443 0.249 0.274             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   85.08 0.00 0.00 85.08 85.08 2.443 0.249 0.274             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.43_SHGC_0.248   4.60 0.00 0.00 4.60 18.40 2.443 0.249 0.274             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.43_SHGC_0.248   8.58 0.00 0.00 8.58 34.34 2.443 0.249 0.274             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.43_SHGC_0.248   4.60 0.00 0.00 4.60 18.40 2.443 0.249 0.274             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.43_SHGC_0.248   8.58 0.00 0.00 8.58 34.34 2.443 0.249 0.274             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.43_SHGC_0.248   3.68 0.00 0.00 3.68 279.56 2.443 0.249 0.274             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.43_SHGC_0.248   3.68 0.00 0.00 3.68 279.65 2.443 0.249 0.274             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.43_SHGC_0.248   8.58 0.00 0.00 8.58 34.34 2.443 0.249 0.274             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.43_SHGC_0.248   4.60 0.00 0.00 4.60 18.40 2.443 0.249 0.274             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.43_SHGC_0.248   4.60 0.00 0.00 4.60 18.40 2.443 0.249 0.274             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.43_SHGC_0.248   8.58 0.00 0.00 8.58 34.34 2.443 0.249 0.274             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   5.82 0.00 0.00 5.82 23.30 2.443 0.249 0.274             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   2.15 0.00 0.00 2.15 8.59 2.443 0.249 0.274             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   2.15 0.00 0.00 2.15 8.58 2.443 0.249 0.274             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   5.82 0.00 0.00 5.82 23.30 2.443 0.249 0.274             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.43_SHGC_0.248   4.60 0.00 0.00 4.60 4.60 2.443 0.249 0.274             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.43_SHGC_0.248   8.58 0.00 0.00 8.58 8.58 2.443 0.249 0.274             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.43_SHGC_0.248   4.60 0.00 0.00 4.60 4.60 2.443 0.249 0.274             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.43_SHGC_0.248   8.58 0.00 0.00 8.58 8.58 2.443 0.249 0.274             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.43_SHGC_0.248   6.74 0.00 0.00 6.74 60.70 2.443 0.249 0.274             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   32.19 0.00 0.00 32.19 32.19 2.443 0.249 0.274             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   32.19 0.00 0.00 32.19 32.19 2.443 0.249 0.274             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   4.60 0.00 0.00 4.60 4.60 2.443 0.249 0.274             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   17.17 0.00 0.00 17.17 17.17 2.443 0.249 0.274             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   4.60 0.00 0.00 4.60 4.60 2.443 0.249 0.274             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   5.82 0.00 0.00 5.82 5.82 2.443 0.249 0.274             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   5.21 0.00 0.00 5.21 5.21 2.443 0.249 0.274             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.43_SHGC_0.248   17.17 0.00 0.00 17.17 17.17 2.443 0.249 0.274             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.443 0.249 0.274                      
North Total or Average             432.95 2.443 0.249 0.274                      
Non-North Total or Average             780.84 2.443 0.249 0.274                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.760 2.390 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 6.7179 1978.83 13293.58 LightsWired LTG_SCH_BASEMENT 49.32 168.00 49.26 0.0000 Y 122.93
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 9.6995 67.07 650.56 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 6.26
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 9.6995 77.67 753.35 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 7.25
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 4.6285 164.24 760.20 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 8.37
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 4.2862 94.76 406.16 LightsWired LTG_SCH_STORAGE 30.30 168.00 30.27 0.0000 Y 2.31
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.7049 78.04 445.21 LightsWired LTG_SCH_LAUNDRY 58.69 168.00 58.63 0.0000 Y 4.90
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 9.2569 188.86 1748.29 LightsWired LTG_SCH_DINING 58.69 168.00 39.81 0.0000 Y 13.07
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 9.0417 1308.19 11828.20 LightsWired LTG_SCH_LOBBY 44.02 168.00 41.55 0.0000 Y 92.24
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.4132 156.09 688.85 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.4132 156.07 688.77 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.4132 1863.81 8225.38 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 58.78
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.4132 1864.32 8227.62 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 58.79
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.4132 156.09 688.85 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.4132 156.07 688.77 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 4.4132 1557.62 6874.08 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 56.74
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.4132 39.02 172.21 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 1.23
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.4132 39.02 172.19 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 1.23
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.4132 220.77 974.32 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 6.96
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 9.2569 331.66 3070.14 LightsWired LTG_SCH_DINING 58.69 168.00 49.40 0.0000 Y 28.47
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 9.2569 331.66 3070.14 LightsWired LTG_SCH_DINING 58.69 168.00 49.40 0.0000 Y 28.47
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.7327 103.30 1212.04 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 13.34
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 4.4132 412.12 1818.79 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 15.01
Interior Lighting Total       5.8577 11345.29 66457.67               366.51


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 11828.20 827.97
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 11828.20 827.97
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1748.29 681.83
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1748.29 681.83
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 3070.14 614.03
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 3070.14 614.03
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 3070.14 614.03
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 3070.14 614.03


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 12338.45 AstronomicalClock -   83.75 83.75 193.98
Exterior Lighting Total 12338.45           193.98



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 257779.33 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 651062.22 2.96 651062.22 2.96 4.09 13.95


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9934.37 14804.80 12737.57 2067.23 0.86 - 2995.50 30.38
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9546.44 14222.73 12232.35 1990.37 0.86 - 2875.08 29.16
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 57212.34 85859.58 74551.50 11308.08 0.87 - 17803.90 180.58
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 57771.71 84632.82 71255.40 13377.42 0.84 - 16291.75 165.24
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 8823.68 13137.99 11290.59 1847.40 0.86 - 2650.53 26.88
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 8484.02 12630.14 10849.51 1780.63 0.86 - 2547.87 25.84
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2581.74 3848.47 3312.22 536.25 0.86 - 779.35 7.90
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2475.08 3688.43 3173.30 515.12 0.86 - 746.23 7.57
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 12242.70 18134.55 15479.34 2655.22 0.85 - 3600.54 36.52
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 47946.25 51303.12 35829.51 15473.61 0.70 - 7298.17 74.02
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 433469.04 500759.57 351957.62 148801.96 0.70 - 78984.18 801.10
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 6641.11 6675.46 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2270.30 2280.17 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1269.74 1276.06 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1216.62 1221.25 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1114.09 1119.36 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1595.50 1601.57 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 9464.77 9511.89 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 24529.72 24652.61 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3518.50 3789.49 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3518.56 3789.55 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 20516.37 22096.37 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 20527.82 22108.70 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3517.97 3788.91 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3518.03 3788.97 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 9565.47 9610.41 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1103.83 1188.83 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1103.51 1188.48 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 5348.55 5760.39 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 13090.60 13156.96 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 13179.06 13245.84 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 3862.15 3881.78 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 5114.35 5134.03 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 9427.25 7911.32 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 92765.46 77848.54 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.24 0.00 0.00 1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.91 637.45 703.64 1.00 1.22 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00
ROOM_2_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.87 612.02 703.64 1.00 1.23 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 5.33 3752.46 703.64 1.00 0.97 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 4.99 3512.32 703.64 1.00 0.97 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00
ROOM_5_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.80 564.61 703.64 1.00 1.26 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00
ROOM_6_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.77 542.34 703.64 1.00 1.27 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00
ROOM_1_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.24 165.80 703.64 1.00 1.90 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00
ROOM_2_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.23 158.80 703.64 1.00 1.94 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 1.10 770.52 703.64 1.00 1.18 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 20.19 45227.86 2240.64 1.00 1.11 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.018604 3007.35 161652.92 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.002255 672.43 298174.34 0.91 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.018604 2082.09 111917.77 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 11.51 0.44
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.22 1.12
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 5.78 0.37



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 28948.46 28948.46 14.63 2.143 2.143 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:30:00 24.00 24.00 0.00933 27.34 0.00823 0.854 0.00
RETAIL_1_FLR_1 4094.15 4094.15 61.04 0.303 0.303 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 24.00 24.00 0.00909 30.93 0.00823 0.079 0.00
RETAIL_2_FLR_1 2946.09 2946.09 37.93 0.218 0.218 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00946 30.05 0.00823 0.092 0.00
MECH_FLR_1 2396.62 2396.62 14.59 0.177 0.177 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 24.00 24.00 0.00874 28.50 0.00823 0.000 0.00
STORAGE_FLR_1 1304.10 1304.10 13.76 0.097 0.097 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 24.00 24.00 0.00884 31.21 0.00823 0.058 0.00
LAUNDRY_FLR_1 44569.36 44569.36 571.11 3.300 3.300 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 24.00 24.00 0.00854 31.30 0.00823 0.000 0.00
CAFE_FLR_1 18440.63 18440.63 97.64 1.367 1.367 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 24.00 23.99 0.01023 30.93 0.00823 0.676 0.00
LOBBY_FLR_1 60742.68 60742.68 46.43 4.499 4.499 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 23.99 0.01006 31.08 0.00823 1.894 0.00
ROOM_1_FLR_3 9081.10 9081.10 232.72 0.906 0.906 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 21.11 21.11 0.00858 30.53 0.00823 0.062 0.00
ROOM_2_FLR_3 8718.86 8718.86 223.46 0.870 0.870 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00858 30.41 0.00823 0.062 0.00
ROOM_3_MULT19_FLR_3 53460.14 53460.14 2179.92 5.333 5.333 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 21.11 21.11 0.00850 31.08 0.00823 0.837 0.00
ROOM_4_MULT19_FLR_3 50034.95 50034.95 2039.70 4.992 4.992 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 21.11 21.11 0.00878 31.30 0.00823 0.837 0.00
ROOM_5_FLR_3 8043.49 8043.49 206.13 0.802 0.802 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 21.11 21.11 0.00859 27.16 0.00823 0.062 0.00
ROOM_6_FLR_3 7726.20 7726.20 198.02 0.771 0.771 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 21.11 21.11 0.00859 26.66 0.00823 0.062 0.00
CORRIDOR_FLR_3 15009.05 15009.05 38.54 1.111 1.111 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 24.00 24.00 0.00976 31.30 0.00823 0.475 0.00
ROOM_1_FLR_6 2361.93 2361.93 60.53 0.236 0.236 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 21.11 21.11 0.00858 30.53 0.00823 0.015 0.00
ROOM_2_FLR_6 2262.32 2262.32 57.98 0.226 0.226 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00858 30.41 0.00823 0.015 0.00
ROOM_3_MULT9_FLR_6 10976.57 10976.57 447.47 1.095 1.095 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 21.11 21.11 0.00865 31.08 0.00823 0.099 0.00
BANQUET_FLR_6 28293.21 28293.21 85.31 2.097 2.097 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 24.00 23.98 0.01049 31.30 0.00823 1.188 0.00
DINING_FLR_6 29729.46 29729.46 89.64 2.204 2.204 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 24.00 23.98 0.01039 31.30 0.00823 1.188 0.00
KITCHEN_FLR_6 28947.41 28947.41 280.21 2.149 2.149 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 24.00 23.97 0.01017 30.50 0.00823 0.367 0.00
CORRIDOR_FLR_6 8471.46 8471.46 20.56 0.627 0.627 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00909 31.23 0.00823 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854   00:10:00 21.00 21.62 0.00506 3.80 0.00506 0.854 0.00
RETAIL_1_FLR_1 1654.77 1654.77 24.67 0.072 0.079 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00782 3.80 0.00506 0.079 0.00
RETAIL_2_FLR_1 556.77 556.77 7.17 0.024 0.092 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00780 3.80 0.00506 0.092 0.00
MECH_FLR_1 992.18 992.18 6.04 0.043 0.043 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00774 3.80 0.00506 0.000 0.00
STORAGE_FLR_1 665.07 665.07 7.02 0.029 0.058 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00777 3.80 0.00506 0.058 0.00
LAUNDRY_FLR_1 1301.18 1301.18 16.67 0.057 0.057 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00773 3.80 0.00506 0.000 0.00
CAFE_FLR_1 4212.30 4212.30 22.30 0.184 0.676 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00784 3.80 0.00506 0.676 0.00
LOBBY_FLR_1 9801.87 9801.87 7.49 0.428 1.894 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00781 3.80 0.00506 1.894 0.00
ROOM_1_FLR_3 3518.52 3518.52 90.17 0.155 0.155 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00781 3.80 0.00506 0.062 0.00
ROOM_2_FLR_3 3518.58 3518.58 90.18 0.155 0.155 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00781 3.80 0.00506 0.062 0.00
ROOM_3_MULT19_FLR_3 20516.43 20516.43 836.59 0.901 0.901 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00783 3.80 0.00506 0.837 0.00
ROOM_4_MULT19_FLR_3 20527.88 20527.88 836.83 0.902 0.902 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00783 3.80 0.00506 0.837 0.00
ROOM_5_FLR_3 3517.99 3517.99 90.15 0.155 0.155 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00781 3.80 0.00506 0.062 0.00
ROOM_6_FLR_3 3518.05 3518.05 90.17 0.155 0.155 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00781 3.80 0.00506 0.062 0.00
CORRIDOR_FLR_3 5875.69 5875.69 15.09 0.257 0.475 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00786 3.80 0.00506 0.475 0.00
ROOM_1_FLR_6 1103.83 1103.83 28.29 0.048 0.048 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00785 3.80 0.00506 0.015 0.00
ROOM_2_FLR_6 1103.51 1103.51 28.28 0.048 0.048 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00785 3.80 0.00506 0.015 0.00
ROOM_3_MULT9_FLR_6 5348.58 5348.58 218.04 0.235 0.235 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00785 3.80 0.00506 0.099 0.00
BANQUET_FLR_6 3855.25 3855.25 11.62 0.168 1.188 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00789 3.80 0.00506 1.188 0.00
DINING_FLR_6 3943.25 3943.25 11.89 0.172 1.188 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 21.00 21.00 0.00789 3.80 0.00506 1.188 0.00
KITCHEN_FLR_6 1024.77 1024.77 9.92 0.045 0.367 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 21.00 21.00 0.00585 3.80 0.00506 0.367 0.00
CORRIDOR_FLR_6 4139.59 4139.59 10.04 0.181 0.181 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 21.00 21.00 0.00791 3.80 0.00506 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
FLR_3_DOAS 14.49 2.05 2.75 2.05 2.0513 2.0513 2.0513 1.0000 0.3000
VAV WITH REHEAT 20.19 20.19 7.15 7.15 20.1853 10.5326 20.1853 0.5218 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 6641.110 6641.110 1.281618 0.00005810 138.489   12/21 00:10:00   12/21 00:10:00 6641.11 6641.11 1.281618 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00800000 50.7558 0.00 0.00 6678.44 6678.44
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 2270.302 2270.302 0.118829 0.00001986 55.149 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2270.30 2270.30 0.118829 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00782283 49.6462 1654.77 0.00 2282.12 2282.12
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1269.737 1269.737 0.137643 0.00001111 27.599 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1269.74 1269.74 0.137643 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00779838 49.4927 556.77 0.00 1276.78 1276.78
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 1216.620 1216.620 0.043333 0.00001064 33.204 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1216.62 1216.62 0.043333 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00773837 49.1165 992.18 0.00 1222.65 1222.65
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1114.091 1114.091 0.086691 0.00000975 25.179 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1114.09 1114.09 0.086691 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00777205 49.3276 665.07 0.00 1120.10 1120.10
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 1595.504 1595.504 0.056828 0.00001396 43.544 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1595.50 1595.50 0.056828 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00772885 49.0571 1301.18 0.00 1603.42 1603.42
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 9464.771 9464.771 1.013949 0.00008280 205.968 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 9464.77 9464.77 1.013949 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00784491 49.7845 4212.30 0.00 9517.24 9517.24
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 24529.724 24529.724 2.843227 0.00021460 529.857 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 24529.72 24529.72 2.843227 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00781171 49.5762 9801.87 0.00 24665.99 24665.99
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 9934.367 -999.000 0.905932 0.00028412 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown 8/21 16:20:00 9934.37 9748.77 0.905932 21.69 15.44 0.00857936 12.80 11.93 0.00850000 30.53 0.00823226 18.20 0.0000 21.11 0.00857936 54.0131 9081.10 0.00 10123.57 10123.57
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 3518.504 3518.504 0.154572 0.00003078 100.531 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3518.50 3518.50 0.154572 21.11 14.54 0.00780867 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00780867 49.2207 3518.52 0.00 3793.06 3793.06
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 9546.440 -999.000 0.869795 0.00027302 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 9546.44 9361.05 0.869795 21.69 15.44 0.00858255 12.80 11.93 0.00850000 30.41 0.00823207 18.16 0.0000 21.11 0.00858255 54.0330 8718.86 0.00 9728.13 9728.13
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 3518.565 3518.565 0.154575 0.00003078 100.533 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3518.56 3518.56 0.154575 21.11 14.54 0.00780869 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00780869 49.2208 3518.58 0.00 3793.13 3793.13
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 57212.341 -999.000 5.332947 0.00163624 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown 8/21 13:30:00 57212.34 57212.34 5.332947 21.69 15.37 0.00849744 12.80 11.93 0.00849744 31.08 0.00823314 18.38 0.0000 21.11 0.00849744 53.5031 53460.14 0.00 58313.80 58313.80
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 20516.369 20516.369 0.901314 0.00017949 586.191 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 20516.37 20516.37 0.901314 21.11 14.55 0.00782502 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00782502 49.3222 20516.43 0.00 22117.36 22117.36
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 57771.707 -999.000 4.991666 0.00165223 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 unknown 8/21 14:50:00 57771.71 54111.86 4.991666 21.69 15.62 0.00878192 12.80 11.93 0.00850000 31.30 0.00823349 18.45 0.0000 21.11 0.00878192 55.2716 50034.95 0.00 58853.04 57215.21
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 20527.822 20527.822 0.901817 0.00017959 586.519 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 20527.82 20527.82 0.901817 21.11 14.55 0.00782506 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00782506 49.3224 20527.88 0.00 22129.70 22129.70
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 8823.683 -999.000 0.802420 0.00025235 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 unknown 8/21 09:30:00 8823.68 8638.22 0.802420 21.69 15.45 0.00858949 12.80 11.93 0.00850000 27.16 0.00822694 17.07 0.0000 21.11 0.00858949 54.0761 8043.49 0.00 8991.35 8991.35
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 3517.965 3517.965 0.154549 0.00003078 100.516 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3517.97 3517.97 0.154549 21.11 14.54 0.00780864 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00780864 49.2205 3517.99 0.00 3792.48 3792.48
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 8484.025 -999.000 0.770767 0.00024264 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown 8/21 09:10:00 8484.02 8298.62 0.770767 21.69 15.45 0.00859313 12.80 11.93 0.00850000 26.66 0.00822614 16.89 0.0000 21.11 0.00859313 54.0987 7726.20 0.00 8646.52 8646.52
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 3518.026 3518.026 0.154551 0.00003078 100.517 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3518.03 3518.03 0.154551 21.11 14.54 0.00780866 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00780866 49.2206 3518.05 0.00 3792.55 3792.55
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 9565.466 9565.466 0.712251 0.00008368 217.577 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 9565.47 9565.47 0.712251 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00785807 49.8667 5875.69 0.00 9616.97 9616.97
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2581.741 -999.000 0.235626 0.00007384 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown 8/21 16:20:00 2581.74 2535.30 0.235626 21.69 15.44 0.00857636 12.80 11.93 0.00850000 30.53 0.00823226 18.20 0.0000 21.11 0.00857636 53.9945 2361.93 0.00 2630.95 2630.95
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1103.828 1103.828 0.048493 0.00000966 31.538 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1103.83 1103.83 0.048493 21.11 14.57 0.00784546 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00784546 49.4497 1103.83 0.00 1189.96 1189.96
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2475.080 -999.000 0.225690 0.00007079 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 2475.08 2428.68 0.225690 21.69 15.44 0.00857963 12.80 11.93 0.00850000 30.41 0.00823207 18.16 0.0000 21.11 0.00857963 54.0148 2262.32 0.00 2522.22 2522.22
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1103.508 1103.508 0.048478 0.00000965 31.529 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1103.51 1103.51 0.048478 21.11 14.57 0.00784543 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00784543 49.4495 1103.51 0.00 1189.62 1189.62
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 12242.703 -999.000 1.095053 0.00035013 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown 8/21 13:30:00 12242.70 11815.35 1.095053 21.69 15.50 0.00865077 12.80 11.93 0.00850000 31.08 0.00823314 18.38 0.0000 21.11 0.00865077 54.4573 10976.57 0.00 12474.10 12474.10
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 5348.553 5348.553 0.234969 0.00004679 152.816 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5348.55 5348.55 0.234969 21.11 14.58 0.00785276 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00785276 49.4950 5348.58 0.00 5765.92 5765.92
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 13090.603 13090.603 1.782644 0.00011452 279.028 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 13090.60 13090.60 1.782644 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00788960 50.0643 3855.25 0.00 13163.62 13163.62
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 13179.062 13179.062 1.782756 0.00011530 281.056 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 13179.06 13179.06 1.782756 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00789196 50.0793 3943.25 0.00 13252.56 13252.56
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 3862.146 3862.146 0.550064 0.00003379 82.051 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 3862.15 3862.15 0.550064 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00585044 37.2513 1024.77 0.00 3883.71 3883.71
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 5114.347 5114.347 0.188147 0.00004474 137.859 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 5114.35 5114.35 0.188147 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00790927 50.1877 4139.59 0.00 5139.79 5139.79
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 47946.248 -999.000 2.051317 0.00137126 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 47946.25 47946.25 2.051317 31.30 18.45 0.00823349 11.91 11.29 0.00823349 31.30 0.00823349 18.45 99.9965 21.11 0.00863640 54.3672 145218.51 0.00 48578.76 48578.76
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 9427.247 9427.247 0.615395 0.00008247 168.968 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 9427.25 9427.25 0.615395 3.80 3.80 0.00505843 16.70 13.02 0.00800000 3.80 0.00505843 3.80 333.3216 21.11 0.00782518 49.3232 62673.37 0.00 9576.38 9576.38
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 433469.044 -999.000 20.185255 0.01239716 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 433469.04 399174.56 20.185255 27.37 17.81 0.00905165 10.94 10.94 0.00850000 31.30 0.00823349 18.45 46.2179 23.99 0.00975691 51.4676 272375.45 0.00 439595.81 390316.33
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 92765.460 92765.460 6.055577 0.00081155 1662.668 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:30:00 92765.46 92765.46 6.055577 3.80 3.80 0.00505843 16.70 13.02 0.00800000 3.80 0.00505843 3.80 154.0596 21.13 0.00713609 44.9707 37335.59 0.00 94232.92 94232.92



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 6641.110 6641.110 1.281618 0.00005810 138.489 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 2.5255 2.576277   12/21 00:10:00 unknown unknown   12/21 00:10:00 Sensible 6641.11 6641.11 1.0000 1.51458931 1.281618 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.05809340 60.00 32.22 27.78 0.000 6641.11 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 50.7558 0.00 0.00 6678.44 6678.44 1.51458931 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 2270.302 2270.302 0.118829 0.00001986 55.149 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 0.8633 0.880715 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2270.30 2270.30 1.0000 0.14042926 0.118829 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.01985957 60.00 32.22 27.78 0.000 2270.30 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00782283 21.00 0.00782283 49.6462 1654.77 0.00 2282.12 2282.12 0.14042926 16.60 13.15 0.00800000 36934.7 32.54 18.87 0.00800000 53185.7
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1269.737 1269.737 0.137643 0.00001111 27.599 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 0.4828 0.492567 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1269.74 1269.74 1.0000 0.16266384 0.137643 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.01110708 60.00 32.22 27.78 0.000 1269.74 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00779838 21.00 0.00779838 49.4927 556.77 0.00 1276.78 1276.78 0.16266384 16.60 13.15 0.00800000 36934.7 24.30 16.06 0.00800000 44783.9
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 1216.620 1216.620 0.043333 0.00001064 33.204 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 0.4627 0.471962 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1216.62 1216.62 1.0000 0.05121052 0.043333 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.01064244 60.00 32.22 27.78 0.000 1216.62 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00773837 21.00 0.00773837 49.1165 992.18 0.00 1222.65 1222.65 0.05121052 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60809.8
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1114.091 1114.091 0.086691 0.00000975 25.179 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 0.4237 0.432188 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1114.09 1114.09 1.0000 0.10244970 0.086691 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.00974556 60.00 32.22 27.78 0.000 1114.09 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00777205 21.00 0.00777205 49.3276 665.07 0.00 1120.10 1120.10 0.10244970 16.60 13.15 0.00800000 36934.7 27.32 17.13 0.00800000 47867.9
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 1595.504 1595.504 0.056828 0.00001396 43.544 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 0.6067 0.618942 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1595.50 1595.50 1.0000 0.06715870 0.056828 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.01395674 60.00 32.22 27.78 0.000 1595.50 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00772885 21.00 0.00772885 49.0571 1301.18 0.00 1603.42 1603.42 0.06715870 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60809.8
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 9464.771 9464.771 1.013949 0.00008280 205.968 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 3.5992 3.671656 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 9464.77 9464.77 1.0000 1.19826368 1.013949 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.08279350 60.00 32.22 27.78 0.000 9464.77 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00784491 21.00 0.00784491 49.7845 4212.30 0.00 9517.24 9517.24 1.19826368 16.60 13.15 0.00800000 36934.7 24.39 16.10 0.00800000 44877.3
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 24529.724 24529.724 2.843227 0.00021460 529.857 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 9.3281 9.515784 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 24529.72 24529.72 1.0000 3.36006460 2.843227 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.21457483 60.00 32.22 27.78 0.000 24529.72 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00781171 21.00 0.00781171 49.5762 9801.87 0.00 24665.99 24665.99 3.36006460 16.60 13.15 0.00800000 36934.7 23.80 15.88 0.00800000 44275.7
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 9934.367 -999.000 0.905932 0.00028412 -999.000 -999.0000 1.00000 1.00000 1020.7886 1004.8586 1.1818 ROOM_1_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.905932 1.07061062   4197.9300 999.8980 18.60186863 15.03 6.70 8.33 650484.22 1.5272 1.527198 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown unknown unknown 8/21 16:20:00 Sensible 9934.37 9748.77 1.0000 1.07061062 0.905932 21.69 15.44 0.00857936 43601.4 12.80 11.93 0.00850000 34322.2 0.28408736 6.70 15.03 8.33 0.000 9934.37 30.53 0.00823226 18.20 0.00000000 0.0000 21.11 0.00857936 21.11 0.00857936 54.0131 9081.10 0.00 10123.57 10123.57 1.07061062 21.69 15.63 0.00857936 43601.4 12.43 12.03 0.00857936 34145.5
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 3518.504 3518.504 0.154572 0.00003078 100.531 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_1_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.905932 1.07061062   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 1.3380 1.364929 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3518.50 3518.50 1.0000 0.18267022 0.154572 21.11 14.54 0.00780867 41048.5 40.00 20.96 0.00800000 60796.0 0.03077827 60.00 32.22 27.78 0.000 3518.50 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00780867 21.11 0.00780867 49.2207 3518.52 0.00 3793.06 3793.06 0.18267022 16.60 12.96 0.00780867 36450.3 36.97 20.13 0.00780867 57214.9
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 9546.440 -999.000 0.869795 0.00027302 -999.000 -999.0000 1.00000 1.00000 1020.7945 1004.8586 1.1818 ROOM_2_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.869795 1.02790483   4197.9300 999.8980 18.60186863 15.03 6.70 8.33 650484.22 1.4676 1.467562 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 9546.44 9361.05 1.0000 1.02790483 0.869795 21.69 15.44 0.00858255 43609.5 12.80 11.93 0.00850000 34322.2 0.27299404 6.70 15.03 8.33 0.000 9546.44 30.41 0.00823207 18.16 0.00000000 0.0000 21.11 0.00858255 21.11 0.00858255 54.0330 8718.86 0.00 9728.13 9728.13 1.02790483 21.69 15.63 0.00858255 43609.5 12.42 12.03 0.00858255 34145.4
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 3518.565 3518.565 0.154575 0.00003078 100.533 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_2_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.869795 1.02790483   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 1.3380 1.364952 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3518.56 3518.56 1.0000 0.18267337 0.154575 21.11 14.54 0.00780869 41048.5 40.00 20.96 0.00800000 60796.0 0.03077880 60.00 32.22 27.78 0.000 3518.56 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00780869 21.11 0.00780869 49.2208 3518.58 0.00 3793.13 3793.13 0.18267337 16.60 12.96 0.00780869 36450.4 36.97 20.13 0.00780869 57214.9
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 57212.341 -999.000 5.332947 0.00163624 -999.000 -999.0000 1.00000 1.00000 1020.6363 1004.8586 1.1818 ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 5.332947 6.30236281   4197.9300 999.8980 18.60186863 15.03 6.70 8.33 650484.22 8.7953 8.795182 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown unknown unknown 8/21 13:30:00 Sensible 57212.34 57212.34 1.0000 6.30236281 5.332947 21.69 15.37 0.00849744 43393.6 12.80 11.93 0.00849744 34315.7 1.63606823 6.70 15.03 8.33 0.000 57212.34 31.08 0.00823314 18.38 0.00000000 0.0000 21.11 0.00849744 21.11 0.00849744 53.5031 53460.14 0.00 58313.80 58313.80 6.30236281 21.69 15.56 0.00849744 43393.6 12.63 12.03 0.00849744 34141.0
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 20516.369 20516.369 0.901314 0.00017949 586.191 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 5.332947 6.30236281   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 7.8019 7.958888 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 20516.37 20516.37 1.0000 1.06515389 0.901314 21.11 14.55 0.00782502 41090.1 40.00 20.96 0.00800000 60796.0 0.17946784 60.00 32.22 27.78 0.000 20516.37 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00782502 21.11 0.00782502 49.3222 20516.43 0.00 22117.36 22117.36 1.06515389 16.60 12.98 0.00782502 36491.7 36.97 20.14 0.00782502 57256.2
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 57771.707 -999.000 4.991666 0.00165223 -999.000 -999.0000 1.00000 1.00000 1021.1651 1004.8586 1.1818 ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 4.991666 5.89904479   4197.9300 999.8980 18.60186863 15.03 6.70 8.33 650484.22 8.8813 8.881173 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 unknown unknown unknown 8/21 14:50:00 Sensible 57771.71 54111.86 1.0000 5.89904479 4.991666 21.69 15.62 0.00878192 44115.6 12.80 11.93 0.00850000 34322.2 1.65206411 6.70 15.03 8.33 0.000 57771.71 31.30 0.00823349 18.45 0.00000000 0.0000 21.11 0.00878192 21.11 0.00878192 55.2716 50034.95 0.00 58853.04 57215.21 5.89904479 21.69 15.81 0.00878192 44115.6 12.20 12.02 0.00867190 34138.9
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 20527.822 20527.822 0.901817 0.00017959 586.519 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 4.991666 5.89904479   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 7.8062 7.963331 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 20527.82 20527.82 1.0000 1.06574848 0.901817 21.11 14.55 0.00782506 41090.2 40.00 20.96 0.00800000 60796.0 0.17956802 60.00 32.22 27.78 0.000 20527.82 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00782506 21.11 0.00782506 49.3224 20527.88 0.00 22129.70 22129.70 1.06574848 16.60 12.98 0.00782506 36491.8 36.97 20.14 0.00782506 57256.3
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 8823.683 -999.000 0.802420 0.00025235 -999.000 -999.0000 1.00000 1.00000 1020.8074 1004.8586 1.1818 ROOM_5_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.802420 0.94828310   4197.9300 999.8980 18.60186863 15.03 6.70 8.33 650484.22 1.3565 1.356454 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 unknown unknown unknown 8/21 09:30:00 Sensible 8823.68 8638.22 1.0000 0.94828310 0.802420 21.69 15.45 0.00858949 43627.1 12.80 11.93 0.00850000 34322.2 0.25232576 6.70 15.03 8.33 0.000 8823.68 27.16 0.00822694 17.07 0.00000000 0.0000 21.11 0.00858949 21.11 0.00858949 54.0761 8043.49 0.00 8991.35 8991.35 0.94828310 21.69 15.64 0.00858949 43627.1 12.41 12.03 0.00858949 34145.4
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 3517.965 3517.965 0.154549 0.00003078 100.516 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_5_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.802420 0.94828310   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 1.3378 1.364720 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3517.97 3517.97 1.0000 0.18264224 0.154549 21.11 14.54 0.00780864 41048.4 40.00 20.96 0.00800000 60796.0 0.03077355 60.00 32.22 27.78 0.000 3517.97 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00780864 21.11 0.00780864 49.2205 3517.99 0.00 3792.48 3792.48 0.18264224 16.60 12.96 0.00780864 36450.3 36.97 20.13 0.00780864 57214.8
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 8484.025 -999.000 0.770767 0.00024264 -999.000 -999.0000 1.00000 1.00000 1020.8142 1004.8586 1.1818 ROOM_6_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.770767 0.91087577   4197.9300 999.8980 18.60186863 15.03 6.70 8.33 650484.22 1.3043 1.304239 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown unknown unknown 8/21 09:10:00 Sensible 8484.02 8298.62 1.0000 0.91087577 0.770767 21.69 15.45 0.00859313 43636.3 12.80 11.93 0.00850000 34322.2 0.24261275 6.70 15.03 8.33 0.000 8484.02 26.66 0.00822614 16.89 0.00000000 0.0000 21.11 0.00859313 21.11 0.00859313 54.0987 7726.20 0.00 8646.52 8646.52 0.91087577 21.69 15.64 0.00859313 43636.3 12.39 12.03 0.00859313 34143.8
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 3518.026 3518.026 0.154551 0.00003078 100.517 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_6_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.770767 0.91087577   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 1.3378 1.364743 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3518.03 3518.03 1.0000 0.18264539 0.154551 21.11 14.54 0.00780866 41048.4 40.00 20.96 0.00800000 60796.0 0.03077408 60.00 32.22 27.78 0.000 3518.03 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00780866 21.11 0.00780866 49.2206 3518.05 0.00 3792.55 3792.55 0.18264539 16.60 12.96 0.00780866 36450.3 36.97 20.13 0.00780866 57214.8
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 9565.466 9565.466 0.712251 0.00008368 217.577 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 3.6375 3.710719 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 9565.47 9565.47 1.0000 0.84172271 0.712251 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.08367433 60.00 32.22 27.78 0.000 9565.47 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00785807 21.00 0.00785807 49.8667 5875.69 0.00 9616.97 9616.97 0.84172271 16.60 13.15 0.00800000 36934.7 27.80 17.29 0.00800000 48360.1
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2581.741 -999.000 0.235626 0.00007384 -999.000 -999.0000 1.00000 1.00000 1020.7830 1004.8586 1.1818 ROOM_1_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.235626 0.27845825   4197.9300 999.8980 18.60186863 15.03 6.70 8.33 650484.22 0.3969 0.396888 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown unknown unknown 8/21 16:20:00 Sensible 2581.74 2535.30 1.0000 0.27845825 0.235626 21.69 15.44 0.00857636 43593.8 12.80 11.93 0.00850000 34322.2 0.07382857 6.70 15.03 8.33 0.000 2581.74 30.53 0.00823226 18.20 0.00000000 0.0000 21.11 0.00857636 21.11 0.00857636 53.9945 2361.93 0.00 2630.95 2630.95 0.27845825 21.69 15.63 0.00857636 43593.8 12.44 12.03 0.00857636 34145.5
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1103.828 1103.828 0.048493 0.00000966 31.538 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_1_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.235626 0.27845825   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 0.4198 0.428206 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1103.83 1103.83 1.0000 0.05730743 0.048493 21.11 14.57 0.00784546 41141.9 40.00 20.96 0.00800000 60796.0 0.00965578 60.00 32.22 27.78 0.000 1103.83 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00784546 21.11 0.00784546 49.4497 1103.83 0.00 1189.96 1189.96 0.05730743 16.60 13.00 0.00784546 36543.5 36.97 20.15 0.00784546 57308.0
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2475.080 -999.000 0.225690 0.00007079 -999.000 -999.0000 1.00000 1.00000 1020.7891 1004.8586 1.1818 ROOM_2_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.225690 0.26671532   4197.9300 999.8980 18.60186863 15.03 6.70 8.33 650484.22 0.3805 0.380491 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 2475.08 2428.68 1.0000 0.26671532 0.225690 21.69 15.44 0.00857963 43602.1 12.80 11.93 0.00850000 34322.2 0.07077843 6.70 15.03 8.33 0.000 2475.08 30.41 0.00823207 18.16 0.00000000 0.0000 21.11 0.00857963 21.11 0.00857963 54.0148 2262.32 0.00 2522.22 2522.22 0.26671532 21.69 15.63 0.00857963 43602.1 12.43 12.03 0.00857963 34145.5
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1103.508 1103.508 0.048478 0.00000965 31.529 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_2_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.225690 0.26671532   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 0.4196 0.428082 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1103.51 1103.51 1.0000 0.05729084 0.048478 21.11 14.57 0.00784543 41141.8 40.00 20.96 0.00800000 60796.0 0.00965298 60.00 32.22 27.78 0.000 1103.51 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00784543 21.11 0.00784543 49.4495 1103.51 0.00 1189.62 1189.62 0.05729084 16.60 13.00 0.00784543 36543.4 36.97 20.15 0.00784543 57307.9
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 12242.703 -999.000 1.095053 0.00035013 -999.000 -999.0000 1.00000 1.00000 1020.9213 1004.8586 1.1818 ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 1.095053 1.29411069   4197.9300 999.8980 18.60186863 15.03 6.70 8.33 650484.22 1.8821 1.882056 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown unknown unknown 8/21 13:30:00 Sensible 12242.70 11815.35 1.0000 1.29411069 1.095053 21.69 15.50 0.00865077 43782.5 12.80 11.93 0.00850000 34322.2 0.35009750 6.70 15.03 8.33 0.000 12242.70 31.08 0.00823314 18.38 0.00000000 0.0000 21.11 0.00865077 21.11 0.00865077 54.4573 10976.57 0.00 12474.10 12474.10 1.29411069 21.69 15.69 0.00865077 43782.5 12.25 12.02 0.00865077 34143.4
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 5348.553 5348.553 0.234969 0.00004679 152.816 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 1.095053 1.29411069   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 2.0339 2.074857 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5348.55 5348.55 1.0000 0.27768141 0.234969 21.11 14.58 0.00785276 41160.5 40.00 20.96 0.00800000 60796.0 0.04678671 60.00 32.22 27.78 0.000 5348.55 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00785276 21.11 0.00785276 49.4950 5348.58 0.00 5765.92 5765.92 0.27768141 16.60 13.01 0.00785276 36561.9 36.97 20.16 0.00785276 57326.5
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 13090.603 13090.603 1.782644 0.00011452 279.028 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 4.9780 5.078221 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 13090.60 13090.60 1.0000 2.10669058 1.782644 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.11451063 60.00 32.22 27.78 0.000 13090.60 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00788960 21.00 0.00788960 50.0643 3855.25 0.00 13163.62 13163.62 2.10669058 16.60 13.15 0.00800000 36934.7 22.73 15.49 0.00800000 43183.2
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 13179.062 13179.062 1.782756 0.00011530 281.056 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 5.0117 5.112536 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 Sensible 13179.06 13179.06 1.0000 2.10682321 1.782756 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.11528442 60.00 32.22 27.78 0.000 13179.06 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00789196 21.00 0.00789196 50.0793 3943.25 0.00 13252.56 13252.56 2.10682321 16.60 13.15 0.00800000 36934.7 22.77 15.51 0.00800000 43225.0
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 3862.146 3862.146 0.550064 0.00003379 82.051 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 1.4687 1.498237 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 Sensible 3862.15 3862.15 1.0000 0.65005420 0.550064 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.03378429 60.00 32.22 27.78 0.000 3862.15 3.80 0.00505843 3.80 0.00000000 0.0000 19.95 0.00585044 21.00 0.00585044 37.2513 1024.77 0.00 3883.71 3883.71 0.65005420 16.60 13.15 0.00800000 36934.7 22.46 15.39 0.00800000 42909.2
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 5114.347 5114.347 0.188147 0.00004474 137.859 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 1.9449 1.984002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 Sensible 5114.35 5114.35 1.0000 0.22234780 0.188147 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.04473797 60.00 32.22 27.78 0.000 5114.35 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00790927 21.00 0.00790927 50.1877 4139.59 0.00 5139.79 5139.79 0.22234780 16.60 13.15 0.00800000 36934.7 39.27 20.96 0.00800000 60050.7
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 47946.248 -999.000 2.051317 0.00137126 -999.000 -999.0000 1.00000 1.00000 1020.1456 1004.8586 1.1818 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.42411771   4197.9300 999.8980 18.60186863 15.03 6.70 8.33 650484.22 7.3709 7.370855 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 Sensible 47946.25 47946.25 1.0000 2.42420295 2.051317 31.30 18.45 0.00823349 52522.0 11.91 11.29 0.00823349 32743.9 1.37111674 6.70 15.03 8.33 2195.006 45751.24 31.30 0.00823349 18.45 2.05124512 99.9965 21.11 0.00862984 21.11 0.00863640 54.3672 145218.51 0.00 48578.76 48578.76 2.42420295 31.30 18.65 0.00823349 52522.0 11.66 11.35 0.00823349 32483.0
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 9427.247 9427.247 0.615395 0.00008247 168.968 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.42411771   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 3.5850 3.657100 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 9427.25 9427.25 1.0000 0.72726088 0.615395 3.80 3.80 0.00505843 16505.0 16.70 13.02 0.00800000 37036.7 0.08246526 60.00 32.22 27.78 0.000 9427.25 3.80 0.00505843 3.80 2.05124512 333.3216 21.11 0.00782445 21.11 0.00782518 49.3232 62673.37 0.00 9576.38 9576.38 0.72726088 2.80 2.80 0.00505843 15490.7 15.78 9.78 0.00505843 28658.4
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 433469.044 -999.000 20.185255 0.01239716 -999.000 -999.0000 1.00000 1.00000 1021.6666 1004.8586 1.1818 VAV WITH REHEAT FAN Fan:VariableVolume 20.185255 23.85450382   4197.9300 999.8980 18.60186863 15.03 6.70 8.33 650484.22 66.6379 66.637903 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 Sensible 433469.04 399174.56 1.0000 23.85450382 20.185255 27.37 17.81 0.00905165 50599.5 10.94 10.94 0.00850000 32428.1 12.39589515 6.70 15.03 8.33 45227.862 388241.18 31.30 0.00823349 18.45 9.32920000 46.2179 23.99 0.00975517 23.99 0.00975691 51.4676 272375.45 0.00 439595.81 390316.33 23.85450382 27.37 18.01 0.00905165 50599.5 11.35 11.22 0.00823254 32171.3
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 92765.460 92765.460 6.055577 0.00081155 1662.668 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 VAV WITH REHEAT FAN Fan:VariableVolume 20.185255 23.85450382   4197.9300 999.8980 2.25493597 54.44 82.22 27.78 262967.24 35.2764 35.986384 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:30:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:30:00 Sensible 92765.46 92765.46 1.0000 7.15635115 6.055577 3.80 3.80 0.00505843 16505.0 16.70 13.02 0.00800000 37036.7 0.81146992 60.00 32.22 27.78 0.000 92765.46 3.80 0.00505843 3.80 9.32920000 154.0596 18.42 0.00742526 21.13 0.00713609 44.9707 37335.59 0.00 94232.92 94232.92 7.15635115 2.80 2.80 0.00505843 15490.7 15.78 9.78 0.00505843 28658.4



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 20.19 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000914 0.000000 0.000000 Sum   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 0.50 8604.17 0.00
RETAIL_1_FLR_1 1740.33 5823.17 10.67
RETAIL_2_FLR_1 346.33 7688.33 7.00
MECH_FLR_1 1054.83 3330.33 37.17
STORAGE_FLR_1 0.00 8760.00 0.00
LAUNDRY_FLR_1 8760.00 4496.50 4496.50
CAFE_FLR_1 1040.83 7808.83 603.83
LOBBY_FLR_1 1077.67 7574.83 788.33
ROOM_1_FLR_3 40.00 8258.67 38.83
ROOM_2_FLR_3 886.17 7727.67 292.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 137.67 8729.00 133.83
ROOM_5_FLR_3 50.33 8658.50 50.33
ROOM_6_FLR_3 517.17 8264.50 295.33
CORRIDOR_FLR_3 244.00 8760.00 244.00
ROOM_1_FLR_6 216.83 8069.00 210.33
ROOM_2_FLR_6 1288.67 7608.00 681.83
ROOM_3_MULT9_FLR_6 29.67 8150.50 16.00
BANQUET_FLR_6 1610.00 6822.00 757.83
DINING_FLR_6 2561.17 5241.67 762.50
KITCHEN_FLR_6 8760.00 6442.50 6442.50
CORRIDOR_FLR_6 2051.83 5829.83 317.83
Facility 8760.00 8760.00 7314.83
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 4.00 0.00 4.00
ROOM_2_FLR_3 0.00 8.00 0.00 8.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 20.50 0.00 20.50
ROOM_5_FLR_3 0.00 2.17 0.00 2.17
ROOM_6_FLR_3 0.00 28.83 0.00 28.83
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 9.67 0.00 9.67
ROOM_2_FLR_6 0.00 18.33 0.00 18.33
ROOM_3_MULT9_FLR_6 0.00 9.50 0.00 9.50
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 63.83 0.00 63.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.78 106.50 4826.41 0.865 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.575 0.061 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 1.456 0.020 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.126 0.023 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.748 0.023 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 18.751 0.066 0.000 0.000
CAFE_FLR_1 82.55 142.30 748.35 4.405 0.048 0.000 0.000
LOBBY_FLR_1 245.05 422.44 5183.56 1.788 0.020 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.342 0.079 0.000 0.094
ROOM_2_FLR_3 0.95 1.50 118.93 0.343 0.079 0.000 0.095
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.389 0.035 0.000 0.157
ROOM_5_FLR_3 0.95 1.50 118.94 0.343 0.079 0.000 0.094
ROOM_6_FLR_3 0.95 1.50 118.93 0.343 0.079 0.000 0.102
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.488 0.010 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.343 0.079 0.000 0.105
ROOM_2_FLR_6 0.95 1.50 118.93 0.343 0.079 0.000 0.096
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.389 0.064 0.000 0.167
BANQUET_FLR_6 144.96 249.90 1010.89 5.745 0.023 0.000 0.000
DINING_FLR_6 144.96 249.90 1010.89 5.766 0.023 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 19.010 0.066 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.510 0.016 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.78 106.50 4826.41 0.548 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 0.943 0.001 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 0.945 0.000 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.006 0.000 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.474 0.000 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 6.657 0.001 0.000 0.000
CAFE_FLR_1 82.55 142.30 748.35 2.804 0.001 0.000 0.000
LOBBY_FLR_1 245.05 422.44 5183.56 1.158 0.000 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.000 0.001 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.000 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.000 0.001 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.309 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.000 0.001 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.000 0.001 0.000 0.000
BANQUET_FLR_6 144.96 249.90 1010.89 3.690 0.000 0.000 0.000
DINING_FLR_6 144.96 249.90 1010.89 3.722 0.000 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 5.852 0.001 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.316 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.78 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.27 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.55 142.30 748.35 188.86 0.0000 0.173
LOBBY_FLR_1 VAV WITH REHEAT 245.05 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.96 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.96 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.11 1604.23 35184.81 11345.29 0.0000 137.081


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 35824407.46 0.00 35824407.46 0.00 35824407.46 26946214.98 1477.96 58.44 7223.60 0.00
RETAIL_1_FLR_1 3592407.79 0.00 3592407.79 139545.61 3731953.40 2498216.28 1163.20 67.27 7529.53 0.00
RETAIL_2_FLR_1 3848146.30 0.00 3848146.30 53864.78 3902011.09 2892943.94 1476.21 59.44 7224.35 0.00
MECH_FLR_1 697371.77 0.00 697371.77 127304.34 824676.12 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 2423230.97 0.00 2423230.97 73447.59 2496678.56 1821682.01 1476.38 58.19 7225.43 0.00
LAUNDRY_FLR_1 49612637.52 0.00 49612637.52 173827.58 49786465.10 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 28343460.55 0.00 28343460.55 308473.47 28651934.02 14544917.54 28.92 26.00 8705.08 0.00
LOBBY_FLR_1 79501350.63 0.00 79501350.63 881379.17 80382729.80 59728886.00 1475.04 58.39 7226.57 0.00
ROOM_1_FLR_3 1406076.84 96093.95 1502170.78 80996.32 1583167.11 1946875.62 2433.33 5215.00 1111.67 0.00
ROOM_2_FLR_3 1405912.09 96761.33 1502673.42 80990.14 1583663.56 1946647.51 2433.33 5295.72 1030.94 0.00
ROOM_3_MULT19_FLR_3 1099911.97 216.08 1100128.05 22598.88 1122726.94 26397887.27 8395.00 365.00 0.00 367.33
ROOM_4_MULT19_FLR_3 19070354.14 100998.21 19171352.34 22605.06 19193957.41 26405105.73 2433.33 5226.06 1100.61 0.00
ROOM_5_FLR_3 1406076.84 96244.38 1502321.22 80996.32 1583317.54 1946875.62 2433.33 5214.92 1111.75 0.00
ROOM_6_FLR_3 1405912.09 103942.50 1509854.59 80990.14 1590844.73 1946647.51 2433.33 5214.83 1111.83 0.00
CORRIDOR_FLR_3 19909170.88 0.00 19909170.88 97940.85 20007111.73 14972100.18 1477.21 58.61 7224.18 0.00
ROOM_1_FLR_6 351519.21 107873.42 459392.63 81012.99 540405.62 486718.90 2031.33 5227.80 1500.87 0.00
ROOM_2_FLR_6 351478.02 97451.92 448929.94 81006.80 529936.75 486661.88 2106.08 5391.70 1262.22 0.00
ROOM_3_MULT9_FLR_6 2258331.41 107721.83 2366053.24 41449.08 2407502.32 3126920.42 2433.33 5214.83 1111.83 0.00
BANQUET_FLR_6 49860159.00 0.00 49860159.00 197813.35 50057972.35 37458366.31 1476.38 58.19 7225.43 0.00
DINING_FLR_6 49991736.37 0.00 49991736.37 197813.35 50189549.73 37458366.31 1475.21 58.31 7226.49 0.00
KITCHEN_FLR_6 51119719.71 0.00 51119719.71 177088.81 51296808.52 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 5484521.95 0.00 5484521.95 173324.65 5657846.60 3961413.96 1011.14 69.41 7679.45 0.00
Total Facility 0.20E+10 10439276.72 0.20E+10 8162099.07 0.20E+10 0.43E+10 8760.00 5795.13 8760.00 367.33


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.1360 0.0000 1.1360 0.0000 1.1360 0.8545 1477.96 58.44 7223.60
RETAIL_1_FLR_1 0.1139 0.0000 0.1139 0.0044 0.1183 0.0792 1163.20 67.27 7529.53
RETAIL_2_FLR_1 0.1220 0.0000 0.1220 0.0017 0.1237 0.0917 1476.21 59.44 7224.35
MECH_FLR_1 0.0221 0.0000 0.0221 0.0040 0.0262 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0768 0.0000 0.0768 0.0023 0.0792 0.0578 1476.38 58.19 7225.43
LAUNDRY_FLR_1 1.5732 0.0000 1.5732 0.0055 1.5787 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.8988 0.0000 0.8988 0.0098 0.9085 0.4612 28.92 26.00 8705.08
LOBBY_FLR_1 2.5210 0.0000 2.5210 0.0279 2.5489 1.8940 1475.04 58.39 7226.57
ROOM_1_FLR_3 0.0446 0.0030 0.0476 0.0026 0.0502 0.0617 2433.33 5215.00 1111.67
ROOM_2_FLR_3 0.0446 0.0031 0.0476 0.0026 0.0502 0.0617 2433.33 5295.72 1030.94
ROOM_4_MULT19_FLR_3 0.6047 0.0032 0.6079 0.0007 0.6086 0.8373 2433.33 5226.06 1100.61
ROOM_5_FLR_3 0.0446 0.0031 0.0476 0.0026 0.0502 0.0617 2433.33 5214.92 1111.75
ROOM_6_FLR_3 0.0446 0.0033 0.0479 0.0026 0.0504 0.0617 2433.33 5214.83 1111.83
CORRIDOR_FLR_3 0.6313 0.0000 0.6313 0.0031 0.6344 0.4748 1477.21 58.61 7224.18
ROOM_1_FLR_6 0.0111 0.0034 0.0146 0.0026 0.0171 0.0154 2031.33 5227.80 1500.87
ROOM_2_FLR_6 0.0111 0.0031 0.0142 0.0026 0.0168 0.0154 2106.08 5391.70 1262.22
ROOM_3_MULT9_FLR_6 0.0716 0.0034 0.0750 0.0013 0.0763 0.0992 2433.33 5214.83 1111.83
BANQUET_FLR_6 1.5811 0.0000 1.5811 0.0063 1.5873 1.1878 1476.38 58.19 7225.43
DINING_FLR_6 1.5852 0.0000 1.5852 0.0063 1.5915 1.1878 1475.21 58.31 7226.49
KITCHEN_FLR_6 1.6210 0.0000 1.6210 0.0056 1.6266 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.1739 0.0000 0.1739 0.0055 0.1794 0.1256 1011.14 69.41 7679.45
Total Facility 61.2889 0.3305 61.6194 0.2044 61.8238 73.7518 8760.00 5795.13 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
FLR_3_DOAS 40160055.99 807303.63 40967359.62 64690340.46 8758.83 1.17 0.00 0.00
VAV WITH REHEAT 0.53E+09 0.00 0.53E+09 0.21E+09 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
FLR_3_DOAS 1.2735 0.0256 1.2991 2.0513 8758.83 1.17 0.00
VAV WITH REHEAT 16.8379 0.0000 16.8379 6.7817 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
FLR_3_DOAS 0.00 0.00 0.00 0.00 6691.67 0.00 0.00 0.00 0.00 0.00
VAV WITH REHEAT 0.00 45.03 8049.88 0.00 0.00 0.00 665.09 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
FLR_3_DOAS 0.0000 0.0000 0.0000 0.0000 1.6673 0.0000 0.0000 0.0000 0.0000 0.0000
VAV WITH REHEAT 0.0000 13.0385 17.3135 0.0000 0.0000 0.0000 11.3637 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1336
Defaulted Fields 1181
Fields with Defaults 3961
Autosized Fields 347
Autosizable Fields 400
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 4661.16 59365.36 13-MAY-05:00 297934.06 29-SEP-19:00
Electricity:Building 2201.60 28839.50 03-JUN-05:00 132137.22 02-JAN-20:10
Electricity:Zone:BASEMENT 266.04 3144.96 02-JAN-02:10 19685.67 02-JAN-20:10
Electricity:SpaceType:GENERAL 2194.50 28698.35 03-JUN-05:00 131895.89 02-JAN-20:10
InteriorLights:Electricity 546.05 4804.68 03-JUN-05:00 45764.37 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 122.93 1117.06 02-JAN-02:10 10053.14 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 546.05 4804.68 03-JUN-05:00 45764.37 02-JAN-20:10
LightsWired:InteriorLights:Electricity 546.05 4804.68 03-JUN-05:00 45764.37 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 122.93 1117.06 02-JAN-02:10 10053.14 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 546.05 4804.68 03-JUN-05:00 45764.37 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 16.45 201.26 02-JAN-02:10 1197.92 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 6.26 56.92 02-JAN-02:10 512.31 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 6.26 56.92 02-JAN-02:10 512.31 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 19.05 233.06 02-JAN-02:10 1387.19 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 7.25 65.92 02-JAN-02:10 593.26 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 7.25 65.92 02-JAN-02:10 593.26 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 20.84 252.75 02-JAN-02:10 1523.62 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 8.37 76.02 02-JAN-02:10 684.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 8.37 76.02 02-JAN-02:10 684.18 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 5.91 71.95 02-JAN-02:10 430.87 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.31 20.97 02-JAN-02:10 188.71 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.31 20.97 02-JAN-02:10 188.71 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.84 1007.22 02-JAN-02:10 4973.49 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.90 44.52 02-JAN-02:10 400.68 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.90 44.52 02-JAN-02:10 400.68 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 27.41 323.64 03-JUN-05:00 2538.73 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 13.07 76.92 01-JAN-13:10 1573.46 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 13.07 76.92 01-JAN-13:10 1573.46 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 241.24 2964.72 03-JUN-05:00 18013.24 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 92.25 853.30 03-JUN-05:00 7984.04 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 92.25 853.30 03-JUN-05:00 7984.04 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 15.40 220.79 01-JAN-02:10 1160.40 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 15.40 220.76 01-JAN-02:10 1160.26 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 253.77 3619.58 02-JAN-10:10 20179.99 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 58.78 497.64 01-JAN-02:10 4523.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 58.78 497.64 01-JAN-02:10 4523.96 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 253.84 3620.57 02-JAN-10:10 20185.51 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 58.79 497.77 01-JAN-02:10 4525.19 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 58.79 497.77 01-JAN-02:10 4525.19 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 15.40 220.79 01-JAN-02:10 1160.40 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 15.40 220.76 01-JAN-02:10 1160.26 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 56.74 515.56 02-JAN-02:10 4640.01 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 56.74 515.56 02-JAN-02:10 4640.01 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 56.74 515.56 02-JAN-02:10 4640.01 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 3.85 55.20 01-JAN-02:10 290.10 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.23 10.42 01-JAN-02:10 94.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.23 10.42 01-JAN-02:10 94.72 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 3.85 55.19 01-JAN-02:10 290.07 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.23 10.42 01-JAN-02:10 94.71 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.23 10.42 01-JAN-02:10 94.71 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 30.06 428.75 02-JAN-10:10 2390.39 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 6.96 58.95 01-JAN-02:10 535.88 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 6.96 58.95 01-JAN-02:10 535.88 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 204.33 2466.55 03-JUN-05:00 9511.03 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 28.47 217.24 03-JUN-05:00 2763.12 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 28.47 217.24 03-JUN-05:00 2763.12 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 204.33 2466.55 03-JUN-05:00 9511.03 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 28.47 217.24 03-JUN-05:00 2763.12 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 28.47 217.24 03-JUN-05:00 2763.12 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 444.45 5944.83 02-JAN-02:10 18636.09 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.34 121.20 02-JAN-02:10 1090.83 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.34 121.20 02-JAN-02:10 1090.83 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 15.01 136.41 02-JAN-02:10 1227.68 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 15.01 136.41 02-JAN-02:10 1227.68 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 15.01 136.41 02-JAN-02:10 1227.68 02-JAN-20:10
InteriorEquipment:Electricity 1648.46 23893.67 02-JAN-02:10 88863.15 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1648.46 23893.67 02-JAN-02:10 88863.15 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 424.02 5682.48 01-JAN-00:10 16179.04 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
Refrigeration:Electricity 44.27 732.85 25-OCT-22:30 2790.01 01-OCT-10:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 861.99 2417.45 17-NOV-03:40 139728.49 16-OCT-12:10
LowTempRefrigeration:Refrigeration:Electricity 15.87 0.00 01-JAN-11:10 1306.97 30-SEP-10:50
MedTempRefrigeration:Refrigeration:Electricity 21.31 636.00 03-FEB-04:20 716.56 11-FEB-14:10
Fans:Electricity 590.07 13114.46 22-FEB-04:00 32130.08 16-OCT-22:00
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 611.59 13493.53 22-FEB-04:00 32951.37 16-OCT-22:00
ExteriorEquipment:Electricity 813.52 9997.87 02-JAN-02:20 49590.83 03-NOV-06:20
Transformer:ExteriorEquipment:Electricity 21.52 379.04 03-JUN-05:00 1274.03 03-NOV-06:20
ElectricityPurchased:Facility 4661.16 59365.36 13-MAY-05:00 297934.06 29-SEP-19:00
ElectricityPurchased:Plant 4661.16 59365.36 13-MAY-05:00 297934.06 29-SEP-19:00
Cogeneration:ElectricityPurchased 4661.16 59365.36 13-MAY-05:00 297934.06 29-SEP-19:00
General:Cogeneration:ElectricityPurchased 4661.16 59365.36 13-MAY-05:00 297934.06 29-SEP-19:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 4661.16 59365.36 13-MAY-05:00 297934.06 29-SEP-19:00
ElectricityNet:Plant 4661.16 59365.36 13-MAY-05:00 297934.06 29-SEP-19:00
Cogeneration:ElectricityNet 4661.16 59365.36 13-MAY-05:00 297934.06 29-SEP-19:00
General:Cogeneration:ElectricityNet 4661.16 59365.36 13-MAY-05:00 297934.06 29-SEP-19:00
General:Fans:Electricity 590.07 13114.46 22-FEB-04:00 32130.08 16-OCT-22:00
ExteriorLights:Electricity 193.98 0.00 01-JAN-07:00 12338.45 01-JAN-00:10
General:ExteriorLights:Electricity 193.98 0.00 01-JAN-07:00 12338.45 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 789.09 9600.00 01-JAN-00:10 48128.80 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
WaterSystems:Electricity 94.78 1222.48 03-JAN-02:30 4751.13 22-MAY-06:40
Water Heater:WaterSystems:Electricity 94.78 1222.48 03-JAN-02:30 4751.13 22-MAY-06:40
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 661.78 0.00 01-JAN-00:30 133252.95 16-OCT-12:10
General:Cooling:Electricity 661.78 0.00 01-JAN-00:30 133252.95 16-OCT-12:10
Pumps:Electricity 68.25 47.91 24-FEB-16:10 3579.84 29-SEP-15:20
General:Pumps:Electricity 68.25 47.91 24-FEB-16:10 3579.84 29-SEP-15:20
WIRED_LTG_ELECTRICITY 19.22 0.00 01-JAN-00:10 1610.91 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 4437.81 23627.42 09-AUG-01:30 337696.64 06-JAN-23:00
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 2648.97 10265.30 02-AUG-00:20 283432.39 06-JAN-23:00
WaterSystems:NaturalGas 2479.18 10265.30 02-AUG-00:20 226545.67 03-FEB-21:30
Water Heater:WaterSystems:NaturalGas 2479.18 10265.30 02-AUG-00:20 226545.67 03-FEB-21:30
Heating:NaturalGas 169.78 0.00 04-JAN-13:40 145374.46 08-JAN-06:50
Boiler:Heating:NaturalGas 169.78 0.00 04-JAN-13:40 145374.46 08-JAN-06:50


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 2814.53 0.00 01-JAN-00:20 455747.19 17-AUG-15:30
PlantLoopCoolingDemand:HVAC 2814.53 0.00 01-JAN-00:20 455747.19 17-AUG-15:30
CoolingCoils:PlantLoopCoolingDemand 2814.53 0.00 01-JAN-00:20 455747.19 17-AUG-15:30


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 05-MAY-20:30
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 05-MAY-20:30
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 05-MAY-20:30
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 05-MAY-20:30
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 05-MAY-20:30
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 05-MAY-20:30
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 04-JAN-08:00
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 04-JAN-08:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 15220.82 125006.47 28-MAR-14:00 1770863.55 17-AUG-15:30
EnergyTransfer:Building 4987.39 93298.19 29-MAR-12:00 296394.57 16-OCT-18:10
EnergyTransfer:Zone:KITCHEN_FLR_6 706.04 10150.66 30-MAR-03:00 34114.47 30-SEP-10:50
Refrigeration:EnergyTransfer 186.82 4016.99 03-FEB-23:20 10366.59 08-SEP-06:40
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 93.41 2008.50 03-FEB-23:20 5183.30 08-SEP-06:40
General:Refrigeration:EnergyTransfer 93.41 2008.50 03-FEB-23:20 5183.30 08-SEP-06:40
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 93.41 2008.50 03-FEB-23:20 5183.30 08-SEP-06:40
EnergyTransfer:Plant 7308.35 18389.84 24-FEB-16:10 1056588.98 17-AUG-15:30
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.69 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 71.72 1996.27 03-FEB-04:20 2558.55 11-FEB-14:10
EnergyTransfer:Zone:BASEMENT 366.47 9432.63 05-JUN-13:20 15462.84 15-OCT-10:40
Heating:EnergyTransfer 5.91 0.00 01-JAN-08:00 10514.09 25-FEB-16:20
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 5.91 0.00 01-JAN-08:00 10514.09 25-FEB-16:20
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 4888.06 90559.82 29-MAR-12:00 292836.33 16-OCT-18:10
Cooling:EnergyTransfer:Zone:BASEMENT 366.47 9432.63 05-JUN-13:20 15462.84 15-OCT-10:40
General:Cooling:EnergyTransfer 4888.06 90559.82 29-MAR-12:00 292836.33 16-OCT-18:10
General:Cooling:EnergyTransfer:Zone:BASEMENT 366.47 9432.63 05-JUN-13:20 15462.84 15-OCT-10:40
EnergyTransfer:Zone:RETAIL_1_FLR_1 37.78 42.76 30-MAR-06:10 3976.68 16-OCT-12:10
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 37.78 42.76 30-MAR-06:10 3976.68 16-OCT-12:10
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 37.78 42.76 30-MAR-06:10 3976.68 16-OCT-12:10
EnergyTransfer:Zone:RETAIL_2_FLR_1 38.89 706.42 29-MAR-12:10 1763.49 16-OCT-21:00
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 38.89 706.42 29-MAR-12:10 1763.49 16-OCT-21:00
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 38.89 706.42 29-MAR-12:10 1763.49 16-OCT-21:00
EnergyTransfer:Zone:MECH_FLR_1 8.11 15.23 29-MAR-14:10 1352.01 16-OCT-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:MECH_FLR_1 8.11 15.23 29-MAR-14:10 1352.01 16-OCT-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 8.11 15.23 29-MAR-14:10 1352.01 16-OCT-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 20.64 170.72 29-MAR-12:10 978.21 30-SEP-10:40
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 20.64 170.72 29-MAR-12:10 978.21 30-SEP-10:40
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 20.64 170.72 29-MAR-12:10 978.21 30-SEP-10:40
EnergyTransfer:Zone:LAUNDRY_FLR_1 593.13 8756.86 30-MAR-04:00 38820.66 29-SEP-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 593.13 8756.86 30-MAR-04:00 38820.66 29-SEP-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 593.13 8756.86 30-MAR-04:00 38820.66 29-SEP-20:00
EnergyTransfer:Zone:CAFE_FLR_1 261.82 2389.32 29-MAR-12:10 13246.96 15-OCT-10:40
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 261.82 2389.32 29-MAR-12:10 13246.96 15-OCT-10:40
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 261.82 2389.32 29-MAR-12:10 13246.96 15-OCT-10:40
EnergyTransfer:Zone:LOBBY_FLR_1 821.94 16339.82 29-MAR-12:10 35417.19 16-OCT-20:20
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 821.94 16339.82 29-MAR-12:10 35417.19 16-OCT-20:20
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 821.94 16339.82 29-MAR-12:10 35417.19 16-OCT-20:20
EnergyTransfer:Zone:ROOM_1_FLR_3 49.62 0.00 01-JAN-08:00 9343.90 30-SEP-15:20
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.59 0.00 01-JAN-08:00 1461.69 29-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.59 0.00 01-JAN-08:00 1461.69 29-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 49.03 0.00 01-JAN-00:10 9343.90 30-SEP-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 49.03 0.00 01-JAN-00:10 9343.90 30-SEP-15:20
EnergyTransfer:Zone:ROOM_2_FLR_3 30.44 0.00 01-JAN-08:00 8767.70 17-AUG-15:20
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 1.19 0.00 01-JAN-08:00 1671.74 30-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 1.19 0.00 01-JAN-08:00 1671.74 30-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 29.25 0.00 01-JAN-00:10 8767.70 17-AUG-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 29.25 0.00 01-JAN-00:10 8767.70 17-AUG-15:20
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 291.40 0.00 01-JAN-00:10 46698.40 16-OCT-12:20
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 291.40 0.00 01-JAN-00:10 46698.40 16-OCT-12:20
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 291.40 0.00 01-JAN-00:10 46698.40 16-OCT-12:20
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 327.75 0.00 01-JAN-08:00 58089.08 22-JUN-20:30
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.35 0.00 01-JAN-00:10 5259.76 12-FEB-16:20
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.35 0.00 01-JAN-00:10 5259.76 12-FEB-16:20
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 327.39 0.00 01-JAN-08:00 58089.08 22-JUN-20:30
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 327.39 0.00 01-JAN-08:00 58089.08 22-JUN-20:30
EnergyTransfer:Zone:ROOM_5_FLR_3 45.87 0.00 01-JAN-08:00 9128.16 15-OCT-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 0.66 0.00 01-JAN-07:10 1692.64 30-MAR-04:00
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 0.66 0.00 01-JAN-07:10 1692.64 30-MAR-04:00
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 45.21 0.00 01-JAN-00:10 9128.16 15-OCT-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 45.21 0.00 01-JAN-00:10 9128.16 15-OCT-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 29.01 0.00 01-JAN-08:00 9451.87 17-OCT-08:40
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 1.35 0.00 01-JAN-07:20 1779.36 30-MAR-04:00
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 1.35 0.00 01-JAN-07:20 1779.36 30-MAR-04:00
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 27.67 0.00 01-JAN-00:10 9451.87 17-OCT-08:40
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 27.67 0.00 01-JAN-00:10 9451.87 17-OCT-08:40
EnergyTransfer:Zone:CORRIDOR_FLR_3 185.88 1534.67 29-MAR-12:10 8614.44 30-SEP-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 185.88 1534.67 29-MAR-12:10 8614.44 30-SEP-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 185.88 1534.67 29-MAR-12:10 8614.44 30-SEP-10:40
EnergyTransfer:Zone:ROOM_1_FLR_6 12.19 0.00 01-JAN-08:00 2490.77 30-SEP-15:20
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.50 0.00 01-JAN-08:00 594.46 29-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.50 0.00 01-JAN-08:00 594.46 29-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 11.69 0.00 01-JAN-00:10 2490.77 30-SEP-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 11.69 0.00 01-JAN-00:10 2490.77 30-SEP-15:20
EnergyTransfer:Zone:ROOM_2_FLR_6 7.93 0.00 01-JAN-08:00 2342.90 18-AUG-15:20
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 0.90 0.00 01-JAN-08:00 663.10 30-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 0.90 0.00 01-JAN-08:00 663.10 30-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 7.02 0.00 01-JAN-00:10 2342.90 18-AUG-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 7.02 0.00 01-JAN-00:10 2342.90 18-AUG-15:20
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 80.71 0.00 01-JAN-08:00 12975.45 30-OCT-15:20
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.37 0.00 01-JAN-00:10 2119.28 30-MAR-04:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.37 0.00 01-JAN-00:10 2119.28 30-MAR-04:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 80.34 0.00 01-JAN-00:30 12975.45 30-OCT-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 80.34 0.00 01-JAN-00:30 12975.45 30-OCT-15:20
EnergyTransfer:Zone:BANQUET_FLR_6 495.03 10845.39 29-MAR-12:10 19714.43 19-JUL-18:10
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 495.03 10845.39 29-MAR-12:10 19714.43 19-JUL-18:10
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 495.03 10845.39 29-MAR-12:10 19714.43 19-JUL-18:10
EnergyTransfer:Zone:DINING_FLR_6 515.65 11993.67 29-MAR-11:00 20972.74 29-SEP-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 515.65 11993.67 29-MAR-11:00 20972.74 29-SEP-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 515.65 11993.67 29-MAR-11:00 20972.74 29-SEP-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 612.63 7814.01 30-MAR-03:00 29094.77 30-SEP-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 612.63 7814.01 30-MAR-03:00 29094.77 30-SEP-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 61.09 979.75 30-MAR-06:20 5439.34 30-SEP-13:30
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 61.09 979.75 30-MAR-06:20 5439.34 30-SEP-13:30
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 61.09 979.75 30-MAR-06:20 5439.34 30-SEP-13:30
PlantLoopHeatingDemand:Facility 809.98 9088.53 04-AUG-02:10 139408.14 08-JAN-07:10
PlantLoopHeatingDemand:Plant 699.43 9088.53 04-AUG-02:10 48539.47 02-FEB-07:10
WaterSystems:PlantLoopHeatingDemand 699.43 9088.53 04-AUG-02:10 48539.47 02-FEB-07:10
General:WaterSystems:PlantLoopHeatingDemand 699.43 9088.53 04-AUG-02:10 48539.47 02-FEB-07:10
EnergyTransfer:HVAC 2925.08 0.00 24-FEB-16:10 455747.19 17-AUG-15:30
HeatingCoils:EnergyTransfer 110.55 0.00 04-JAN-13:40 110454.74 08-JAN-06:50
PlantLoopHeatingDemand:HVAC 110.55 0.00 04-JAN-13:40 110454.74 08-JAN-06:50
HeatingCoils:PlantLoopHeatingDemand 110.55 0.00 04-JAN-13:40 110454.74 08-JAN-06:50
CoolingCoils:EnergyTransfer 2814.53 0.00 01-JAN-00:20 455747.19 17-AUG-15:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 699.43 9088.53 04-AUG-02:10 48539.47 02-FEB-07:10
WaterUse:WaterSystems:EnergyTransfer 699.43 9088.53 04-AUG-02:10 48539.47 02-FEB-07:10
Boilers:EnergyTransfer 109.45 0.00 04-JAN-13:40 109821.79 08-JAN-06:50
Chillers:EnergyTransfer 2872.14 0.00 01-JAN-00:30 457938.42 17-AUG-15:30
HeatRejection:EnergyTransfer 3533.92 0.00 01-JAN-00:30 581594.47 17-AUG-15:30
General:HeatRejection:EnergyTransfer 3533.92 0.00 01-JAN-00:30 581594.47 17-AUG-15:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -366.472 0.000 0.000 144.311 122.932 143.105 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 -43.877
RETAIL_1_FLR_1 0.000 0.000 0.000 -37.776 0.000 0.000 14.751 6.265 10.186 20.746 0.000 0.014 0.001 0.000 -8.408 0.000 -1.172 -4.605
RETAIL_2_FLR_1 0.000 0.000 0.000 -38.895 0.000 0.000 17.017 7.255 11.795 0.000 0.000 0.011 3.261 0.000 0.000 0.000 -0.444 -0.000
MECH_FLR_1 0.000 0.000 0.000 -8.108 0.000 0.000 3.346 8.366 12.471 0.000 0.000 0.012 0.000 0.000 0.000 0.000 -1.238 -14.850
STORAGE_FLR_1 0.000 0.000 0.000 -20.637 0.000 0.000 2.961 2.308 3.598 0.000 0.000 0.021 12.265 0.000 0.000 0.000 -0.516 0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -593.128 0.000 0.000 10.551 4.900 658.131 0.000 0.000 0.016 0.000 0.000 0.000 0.000 -1.707 -78.764
CAFE_FLR_1 0.000 0.000 0.000 -261.825 0.000 0.000 199.628 13.067 14.341 59.685 0.000 0.082 0.002 0.000 -22.560 0.000 -2.353 -0.065
LOBBY_FLR_1 0.000 0.000 0.000 -821.944 0.000 0.000 565.477 92.246 148.998 78.136 0.000 0.188 0.000 0.000 -31.851 0.000 -7.446 -23.805
ROOM_1_FLR_3 1.821 -39.271 0.000 -10.987 0.000 0.000 9.636 4.922 10.478 43.681 0.000 0.092 0.798 0.000 -17.136 0.000 -4.035 -0.001
ROOM_2_FLR_3 3.106 -19.329 0.000 -11.838 0.000 0.000 9.429 4.922 10.477 31.158 0.000 0.059 0.000 0.000 -17.769 0.000 -4.950 -5.266
ROOM_3_MULT19_FLR_3 0.000 -274.760 0.000 -16.637 0.000 0.000 0.000 58.777 194.997 224.884 0.000 0.064 0.008 0.000 -144.867 0.000 -22.356 -20.101
ROOM_4_MULT19_FLR_3 5.512 -177.839 0.000 -154.693 0.000 0.000 181.588 58.793 195.050 68.121 0.000 0.431 0.000 0.000 -93.517 0.000 -52.708 -30.738
ROOM_5_FLR_3 2.003 -35.563 0.000 -10.990 0.000 0.000 9.630 4.922 10.478 40.608 0.000 0.092 0.001 0.000 -16.730 0.000 -4.049 -0.401
ROOM_6_FLR_3 3.357 -18.009 0.000 -11.663 0.000 0.000 9.493 4.922 10.477 27.935 0.000 0.057 0.000 0.000 -16.909 0.000 -4.835 -4.824
CORRIDOR_FLR_3 0.000 0.000 0.000 -185.882 0.000 0.000 118.299 56.739 0.000 36.843 0.000 0.081 0.000 0.000 -21.993 0.000 -2.985 -1.101
ROOM_1_FLR_6 1.060 -9.499 0.000 -2.748 0.000 0.000 2.411 1.231 2.620 10.797 0.000 0.023 0.000 0.000 -4.233 0.000 -1.058 -0.605
ROOM_2_FLR_6 1.634 -4.776 0.000 -2.977 0.000 0.000 2.352 1.230 2.619 7.673 0.000 0.015 0.000 0.000 -4.411 0.000 -1.249 -2.110
ROOM_3_MULT9_FLR_6 1.451 -63.752 0.000 -17.670 0.000 0.000 21.664 6.962 23.098 54.666 0.000 0.147 0.140 0.000 -19.779 0.000 -6.927 -0.003
BANQUET_FLR_6 0.000 0.000 0.000 -495.030 0.000 0.000 338.904 28.469 175.857 7.373 0.000 0.051 0.000 0.000 -12.278 0.000 -1.634 -41.713
DINING_FLR_6 0.000 0.000 0.000 -515.654 0.000 0.000 333.610 28.469 175.857 7.019 0.000 0.044 0.000 0.000 -12.836 0.000 -1.694 -14.817
KITCHEN_FLR_6 0.000 0.000 0.000 -612.624 0.000 0.000 27.948 13.339 540.650 18.989 0.000 0.016 23.195 0.000 -9.755 0.000 -1.758 -0.000
CORRIDOR_FLR_6 0.000 0.000 0.000 -61.089 0.000 0.000 29.309 15.012 0.000 17.094 0.000 0.016 12.217 0.000 -10.995 0.000 -1.564 -0.000
Total Facility 19.943 -642.796 0.000 -4259.268 0.000 0.000 2052.318 546.048 2355.282 755.408 0.000 1.534 51.895 0.000 -466.028 0.000 -126.678 -287.646


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 15-OCT-10:35 0.00 0.00 0.00 -15512.14 0.00 0.00 2377.23 3351.05 4055.80 0.00 0.00 0.00 5728.06 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 16-OCT-12:10 0.00 0.00 0.00 -3976.80 0.00 0.00 150.60 142.31 252.59 4692.43 0.00 58.25 0.00 0.00 -0.00 0.00 0.00 -1319.38
RETAIL_2_FLR_1 16-OCT-21:00 0.00 0.00 0.00 -1763.07 0.00 0.00 697.64 527.34 752.15 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -12.24 -201.82
MECH_FLR_1 16-OCT-20:00 0.00 0.00 0.00 -1351.98 0.00 0.00 129.08 684.18 839.45 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -14.33 -286.39
STORAGE_FLR_1 30-SEP-10:35 0.00 0.00 0.00 -981.01 0.00 0.00 47.38 52.42 89.22 0.00 0.00 22.24 769.75 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 29-SEP-20:00 0.00 0.00 0.00 -38819.77 0.00 0.00 408.86 400.68 44299.38 0.00 0.00 6.40 0.00 0.00 -0.00 0.00 0.00 -6295.55
CAFE_FLR_1 15-OCT-10:35 0.00 0.00 0.00 -13361.24 0.00 0.00 2981.55 115.39 406.43 12720.99 0.00 88.46 0.00 0.00 -0.00 0.00 0.00 -2951.58
LOBBY_FLR_1 16-OCT-21:52 0.00 0.00 0.00 -35535.21 0.00 0.00 26441.15 5322.69 7389.94 0.00 0.00 0.00 0.00 0.00 -1221.91 0.00 -132.67 -2263.98
ROOM_1_FLR_3 14-OCT-08:61 0.00 -11672.53 0.00 -732.23 0.00 0.00 130.71 212.17 653.23 2417.40 0.00 58.69 8932.57 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 14-OCT-08:61 0.00 -11528.39 0.00 -765.21 0.00 0.00 126.73 212.14 653.15 1212.45 0.00 53.38 10035.75 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 16-OCT-12:20 0.00 -46698.66 0.00 0.00 0.00 0.00 0.00 1266.71 2352.88 54481.00 0.00 531.70 0.00 0.00 -0.00 0.00 0.00 -11933.62
ROOM_4_MULT19_FLR_3 14-OCT-08:61 0.00 -68449.68 0.00 -10514.23 0.00 0.00 2431.42 2534.11 12159.85 6595.95 0.00 273.03 54969.56 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 14-OCT-08:61 0.00 -10530.94 0.00 -746.29 0.00 0.00 130.71 212.17 653.23 6903.46 0.00 56.41 3321.26 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 17-OCT-08:21 0.00 -11652.39 0.00 -925.33 0.00 0.00 72.14 166.68 452.99 6461.39 0.00 25.79 5398.72 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 30-SEP-10:35 0.00 0.00 0.00 -8626.68 0.00 0.00 1877.76 1288.89 0.00 6382.13 0.00 108.80 0.00 0.00 -0.00 0.00 0.00 -1030.90
ROOM_1_FLR_6 26-OCT-15:11 0.00 -3032.91 0.00 -183.01 0.00 0.00 58.82 26.52 50.05 1522.49 0.00 0.00 1574.02 0.00 -0.00 0.00 -15.97 0.00
ROOM_2_FLR_6 23-APR-18:11 0.00 -2952.12 0.00 -171.57 0.00 0.00 62.44 94.71 121.15 0.00 0.00 0.00 3209.68 0.00 -332.83 0.00 -31.46 0.00
ROOM_3_MULT9_FLR_6 14-OCT-08:61 0.00 -14360.49 0.00 -1190.58 0.00 0.00 294.10 300.09 1439.98 5352.22 0.00 65.02 8099.64 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 19-JUL-18:10 0.00 0.00 0.00 -20051.18 0.00 0.00 13633.69 1582.65 6747.90 769.69 0.00 0.00 0.00 0.00 -0.00 0.00 -0.61 -2682.14
DINING_FLR_6 29-SEP-21:10 0.00 0.00 0.00 -21235.66 0.00 0.00 15789.12 1842.08 6747.90 0.00 0.00 3.56 0.00 0.00 -185.84 0.00 0.00 -2961.17
KITCHEN_FLR_6 30-SEP-10:50 0.00 0.00 0.00 -29104.71 0.00 0.00 463.47 303.01 23951.61 2357.65 0.00 42.73 1986.25 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 30-SEP-13:30 0.00 0.00 0.00 -5439.26 0.00 0.00 462.69 341.02 0.00 2887.50 0.00 49.26 1698.79 0.00 -0.00 0.00 0.00 0.00
Total Facility 16-OCT-15:11 0.00 -151011.11 0.00 -165995.05 0.00 0.00 55564.32 11549.47 73604.29 79990.32 0.00 1705.34 94592.42 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 23-FEB-16:14 3986.71 413.84 0.00 -413.84 0.00 0.00 235.28 106.08 200.18 505.08 0.00 0.00 0.00 0.00 -0.00 0.00 -87.84 -4945.50
ROOM_2_FLR_3 22-JAN-16:14 3885.68 418.23 0.00 -418.23 0.00 0.00 131.71 125.01 221.23 0.00 0.00 0.00 0.00 0.00 -385.49 0.00 -85.05 -3893.09
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 09-JAN-09:03 19095.38 5590.30 0.00 -5590.30 0.00 0.00 1829.47 1991.09 8433.45 0.00 0.00 0.00 0.00 0.00 -1729.56 0.00 -644.96 -28974.86
ROOM_5_FLR_3 09-JAN-16:14 3818.34 411.97 0.00 -411.97 0.00 0.00 235.86 106.08 200.18 0.00 0.00 0.00 0.00 0.00 -376.21 0.00 -76.15 -3908.11
ROOM_6_FLR_3 28-DEC-19:03 3703.70 415.89 0.00 -415.89 0.00 0.00 361.31 337.15 484.60 0.00 0.00 0.00 0.00 0.00 -1220.05 0.00 -104.56 -3562.16
CORRIDOR_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 23-FEB-16:14 1178.66 104.71 0.00 -104.71 0.00 0.00 58.82 26.52 50.05 118.23 0.00 0.00 0.00 0.00 -0.00 0.00 -22.35 -1409.93
ROOM_2_FLR_6 27-DEC-19:03 1158.46 103.88 0.00 -103.88 0.00 0.00 90.42 84.29 121.15 0.00 0.00 0.00 0.00 0.00 -278.85 0.00 -22.08 -1153.39
ROOM_3_MULT9_FLR_6 12-MAY-15:14 5523.27 673.36 0.00 -673.36 0.00 0.00 586.93 150.05 441.28 366.30 0.00 0.00 0.00 0.00 -0.00 0.00 -3119.28 -3948.55
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 23-FEB-16:14 -95220.81 128019.39 0.00 -128019.39 0.00 0.00 58487.54 11572.34 73604.29 1668.68 0.00 0.00 0.00 0.00 -4610.24 0.00 -2729.51 -42772.29



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV WITH REHEAT 20.2912 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 20.1853 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV WITH REHEAT 12.9188 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.5326 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.003540 142.3000 0.000914 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000
VAV WITH REHEAT   0.00 0.000970 6694.0231 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1432 2.1432 1.2816 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3031 0.3031 0.1188 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2181 0.2181 0.1376 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1774 0.1774 0.0018 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0965 0.0965 0.0867 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2996 3.2996 0.0330 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3665 1.3665 1.0139 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.4988 4.4988 2.8432 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1112 1.1112 0.7123 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.0972 2.0972 1.7826 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2037 2.2037 1.7828 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1487 2.1487 0.5501 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6272 0.6272 0.1881 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000
VAV WITH REHEAT 20.2912 20.1853 20.2912 10.5326 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2816 1.2816 1.2816 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1516 0.1516 0.1188 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1376 0.1376 0.1376 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0887 0.0887 0.0018 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0867 0.0867 0.0867 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6498 1.6498 0.0330 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0139 1.0139 1.0139 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8432 2.8432 2.8432 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7123 0.7123 0.7123 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7826 1.7826 1.7826 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7828 1.7828 1.7828 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0743 1.0743 0.5501 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3136 0.3136 0.1881 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000
VAV WITH REHEAT 12.9188 10.5326 10.5326 10.5326 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 63.83
Number of hours not met 63.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 169.78 145374.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 661.78 133252.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 546.05 45764.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 193.98 12338.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 872.72 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 8.75 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 4.94 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 21.52 1274.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 789.09 48128.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 590.07 32130.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 68.25 3579.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 94.78 4751.13 2479.18 226545.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 15.87 1306.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 21.31 716.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1692.73 4661.16
Natural Gas 1788.84 4437.81
Additional 0.00 0.00
Total 3481.57 9098.96


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 48.13
Space Heating 0.00
Space Cooling 58.33
Fans (All) 52.01
Service Water Heating 8.35
Receptacle Equipment 145.30
Miscellaneous (All) 410.85
Subtotal 410.85


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 14.97
Service Water Heating 218.52
Miscellaneous (All) 391.16
Subtotal 391.16


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.00
Space Heating 1.87
Space Cooling 7.27
Fans (All) 6.49
Service Water Heating 28.29
Receptacle Equipment 37.78
Miscellaneous 12.31


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 486. 5110.
ELEVATOR_STANDBY_SCH 7671. 8760.
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2572. 8760.
LTG_SCH_LOBBY 2295. 8760.
LTG_SCH_STORAGE 1580. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 3061. 8760.
LTG_SCH_GUESTROOM 1980. 8760.
LTG_SCH_CORRIDOR 2295. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 8760. 8760.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 15.56 365 15.56 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 26.67 365 26.67 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8706.67 53.33 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 7078.17 1681.83 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8754.33 5.67 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8634.67 125.33 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 7078.17 0.00 0.00 0.00 0.00
Max 8760.00 1681.83 0.00 0.00 0.00
Average 8675.17 84.83 0.00 0.00 0.00
Sum 190853.83 1866.17 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4150.50 3.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4134.33 19.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 19.67 0.00 0.00 0.00
Average 288885.99 1.05 0.00 0.00 0.00
Sum 6355491.83 23.17 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8744.00 16.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8356.50 403.50 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8502.17 257.83 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 5853.67 2906.33 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8750.50 9.50 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8627.33 132.67 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8759.83 0.17 0.00 0.00 0.00
ROOM_2_FLR_6 8335.17 424.83 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8478.33 281.67 0.00 0.00 0.00
DINING_FLR_6 8324.67 435.33 0.00 0.00 0.00
KITCHEN_FLR_6 8718.00 42.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8568.50 191.50 0.00 0.00 0.00
Min 5853.67 0.00 0.00 0.00 0.00
Max 8760.00 2906.33 0.00 0.00 0.00
Average 8528.12 231.88 0.00 0.00 0.00
Sum 187618.67 5101.33 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8962.33 14.67 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 1963063.17 152365.83 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4050.33 103.67 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4153.17 0.83 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4145.17 8.83 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 3957.17 196.83 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1182892.50 62822.50 0.00 0.00 0.00
DINING_FLR_6 1148942.00 96773.00 0.00 0.00 0.00
KITCHEN_FLR_6 107885.00 384.00 0.00 0.00 0.00
CORRIDOR_FLR_6 102414.17 3531.83 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1963063.17 152365.83 0.00 0.00 0.00
Average 274514.23 14372.82 0.00 0.00 0.00
Sum 6039313.00 316202.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:30

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.324648E+11 14521.45 22-JAN-11:35 16.67 11.79 0.766506E+10 4750.28 13-JAN-23:10 16.67 11.79
February 0.270784E+11 14135.47 01-FEB-11:35 25.00 14.29 0.653899E+10 4655.69 01-FEB-23:10 13.00 11.39
March 0.292354E+11 13588.08 12-MAR-10:35 21.33 14.69 0.711217E+10 4392.99 03-MAR-23:10 21.33 14.69
April 0.283518E+11 13666.69 30-APR-10:35 25.67 16.97 0.679265E+10 4355.12 14-APR-22:10 25.67 16.97
May 0.292138E+11 13497.55 04-MAY-18:10 18.83 14.89 0.701880E+10 4353.07 26-MAY-22:10 11.00 8.46
June 0.281918E+11 13529.08 25-JUN-10:35 23.00 17.26 0.673746E+10 4309.71 09-JUN-22:10 23.00 17.26
July 0.309208E+11 14388.30 23-JUL-10:35 25.67 20.39 0.717828E+10 4474.52 28-JUL-22:10 18.00 17.35
August 0.313996E+11 14380.85 13-AUG-10:35 24.00 19.90 0.729167E+10 4502.84 31-AUG-22:10 16.65 15.39
September 0.313310E+11 15083.82 30-SEP-10:35 30.57 17.23 0.726473E+10 4660.53 28-SEP-22:10 30.57 17.23
October 0.335194E+11 15512.97 15-OCT-10:35 31.67 16.43 0.772299E+10 4803.13 20-OCT-22:10 16.00 13.03
November 0.322009E+11 15015.09 19-NOV-11:35 26.00 15.32 0.753784E+10 4831.15 30-NOV-23:10 11.03 5.21
December 0.325632E+11 14370.16 07-DEC-19:10 14.83 13.74 0.768934E+10 4808.45 01-DEC-23:10 14.83 13.74
                     
Annual Sum or Average 0.366471E+12         0.865500E+11        
Minimum of Months 0.270784E+11 13497.55   14.83 11.79 0.653899E+10 4309.71   11.00 5.21
Maximum of Months 0.335194E+11 15512.97   31.67 20.39 0.772299E+10 4831.15   30.57 17.35



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.332055E+10 3314.36 14-JAN-12:40 25.33 11.70 0.722718E+09 477.97 18-JAN-22:30 16.50 13.26
February 0.270317E+10 2952.85 02-FEB-12:40 19.33 12.36 0.639955E+09 477.96 01-FEB-22:30 19.33 12.36
March 0.267311E+10 2600.76 11-MAR-13:00 24.00 13.82 0.693952E+09 475.92 23-MAR-21:19 13.67 13.10
April 0.282569E+10 1910.62 08-APR-12:40 22.33 16.70 0.703327E+09 480.66 26-APR-22:10 16.00 15.29
May 0.271726E+10 1512.72 04-MAY-12:30 23.50 16.62 0.704885E+09 483.36 04-MAY-21:40 17.00 15.07
June 0.279672E+10 1431.73 29-JUN-18:10 21.50 18.39 0.710871E+09 479.28 28-JUN-21:40 21.50 18.39
July 0.313701E+10 1569.53 31-JUL-12:40 28.00 21.19 0.769134E+09 491.84 31-JUL-22:10 18.65 17.88
August 0.337803E+10 1969.11 27-AUG-12:00 23.00 18.42 0.792749E+09 491.84 09-AUG-22:10 23.00 18.42
September 0.341028E+10 3398.98 30-SEP-12:00 32.00 17.11 0.755023E+09 491.84 13-SEP-22:10 32.00 17.11
October 0.390010E+10 3976.68 16-OCT-12:10 35.68 17.48 0.781155E+09 491.84 18-OCT-21:30 14.50 14.21
November 0.337150E+10 3604.24 19-NOV-12:30 26.50 15.22 0.716795E+09 481.73 20-NOV-22:30 14.00 12.84
December 0.354261E+10 3463.38 19-DEC-12:40 25.67 11.48 0.732359E+09 491.83 05-DEC-23:10 25.67 11.48
                     
Annual Sum or Average 0.377760E+11         0.872292E+10        
Minimum of Months 0.267311E+10 1431.73   19.33 11.48 0.639955E+09 475.92   13.67 11.48
Maximum of Months 0.390010E+10 3976.68   35.68 21.19 0.792749E+09 491.84   32.00 18.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.315862E+10 1469.61 18-JAN-19:10 18.83 14.20 0.842762E+09 549.50 20-JAN-23:10 13.83 13.83
February 0.281277E+10 1487.54 03-FEB-21:00 13.00 7.33 0.756330E+09 554.05 03-FEB-23:10 11.67 3.87
March 0.306299E+10 1498.28 23-MAR-18:10 16.50 14.36 0.829857E+09 552.92 24-MAR-22:10 13.00 11.29
April 0.314904E+10 1548.14 26-APR-18:10 18.67 15.37 0.825939E+09 560.83 27-APR-22:10 14.00 12.84
May 0.321394E+10 1549.15 04-MAY-18:10 18.83 14.89 0.848267E+09 561.45 03-MAY-22:10 18.83 14.89
June 0.323542E+10 1575.66 29-JUN-18:10 21.50 18.39 0.840161E+09 564.86 30-JUN-22:10 16.13 16.03
July 0.350211E+10 1614.97 19-JUL-18:10 22.67 18.90 0.887235E+09 569.55 26-JUL-22:10 17.00 15.84
August 0.355342E+10 1616.94 17-AUG-18:10 20.77 18.28 0.900653E+09 569.55 09-AUG-22:10 20.77 18.28
September 0.336214E+10 1719.39 29-SEP-21:00 24.60 13.50 0.860657E+09 569.54 28-SEP-22:10 24.60 13.50
October 0.347958E+10 1763.49 16-OCT-21:00 18.00 11.03 0.890369E+09 569.55 18-OCT-21:30 14.50 14.21
November 0.315557E+10 1542.36 19-NOV-11:35 26.00 15.32 0.832085E+09 554.46 01-NOV-22:10 26.00 15.32
December 0.320899E+10 1505.26 05-DEC-21:00 16.00 9.09 0.852242E+09 560.02 05-DEC-23:10 17.33 9.21
                     
Annual Sum or Average 0.388946E+11         0.101666E+11        
Minimum of Months 0.281277E+10 1469.61   13.00 7.33 0.756330E+09 549.50   11.67 3.87
Maximum of Months 0.355342E+10 1763.49   26.00 18.90 0.900653E+09 569.55   26.00 18.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.308362E+09 813.92 18-JAN-22:00 17.00 13.48 0.201210E+09 120.45 25-JAN-22:30 14.00 14.00
February 0.223234E+09 724.79 03-FEB-21:00 13.00 7.33 0.182692E+09 120.45 09-FEB-00:20 8.00 6.97
March 0.207501E+09 684.56 24-MAR-21:00 13.00 11.87 0.201315E+09 120.45 13-MAR-00:40 13.00 11.87
April 0.425761E+09 832.68 26-APR-21:00 16.00 15.39 0.197674E+09 120.45 26-APR-21:30 16.00 15.39
May 0.563505E+09 953.09 04-MAY-21:00 17.00 15.07 0.205160E+09 120.45 24-MAY-21:40 16.00 14.13
June 0.917128E+09 1043.58 30-JUN-21:00 16.00 14.76 0.199178E+09 120.45 30-JUN-21:30 16.05 15.44
July 0.126874E+10 1146.97 19-JUL-21:00 18.00 18.00 0.205008E+09 120.45 19-JUL-21:30 18.00 17.68
August 0.125470E+10 1126.94 18-AUG-21:00 19.00 17.66 0.205875E+09 120.45 17-AUG-21:30 19.00 17.66
September 0.101151E+10 1269.33 29-SEP-21:00 24.60 13.50 0.198648E+09 120.45 20-SEP-21:40 24.60 13.50
October 0.114537E+10 1352.01 16-OCT-20:00 21.00 13.07 0.205104E+09 120.45 31-OCT-21:10 16.88 14.87
November 0.440365E+09 778.68 10-NOV-22:00 15.00 13.80 0.197808E+09 120.45 09-NOV-22:40 15.00 13.80
December 0.341375E+09 844.60 05-DEC-22:00 17.00 9.46 0.203059E+09 120.45 01-DEC-01:10 17.00 9.46
                     
Annual Sum or Average 0.810755E+10         0.240273E+10        
Minimum of Months 0.207501E+09 684.56   13.00 7.33 0.182692E+09 120.45   8.00 6.97
Maximum of Months 0.126874E+10 1352.01   24.60 18.00 0.205875E+09 120.45   24.60 17.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.159205E+10 835.85 20-JAN-11:35 21.67 15.71 0.120020E+09 75.79 18-JAN-23:10 21.67 15.71
February 0.143460E+10 812.24 04-FEB-11:35 20.67 8.25 0.107994E+09 74.62 03-FEB-23:10 20.67 8.25
March 0.151889E+10 827.03 19-MAR-10:35 19.33 15.06 0.119214E+09 74.28 24-MAR-22:10 13.00 11.29
April 0.165966E+10 867.29 30-APR-10:35 25.67 16.97 0.117664E+09 75.83 27-APR-22:10 25.67 16.97
May 0.175120E+10 874.51 04-MAY-10:35 22.00 15.73 0.122976E+09 77.33 04-MAY-22:10 16.83 15.02
June 0.179257E+10 903.68 25-JUN-10:35 23.00 17.26 0.122809E+09 78.32 30-JUN-22:10 16.13 16.03
July 0.193709E+10 941.42 23-JUL-10:35 25.67 20.39 0.129258E+09 79.46 19-JUL-22:10 25.67 20.39
August 0.193611E+10 934.24 19-AUG-10:35 24.67 20.11 0.129739E+09 79.46 18-AUG-22:10 24.67 20.11
September 0.181239E+10 981.03 30-SEP-10:35 30.57 17.23 0.123473E+09 80.99 29-SEP-22:10 30.57 17.23
October 0.189057E+10 971.51 15-OCT-10:35 31.67 16.43 0.128594E+09 81.79 16-OCT-22:10 20.17 11.06
November 0.165899E+10 868.13 19-NOV-11:35 26.00 15.32 0.118187E+09 75.66 01-NOV-22:10 26.00 15.32
December 0.165330E+10 840.60 19-DEC-11:35 25.00 11.16 0.120759E+09 76.34 05-DEC-23:10 25.00 11.16
                     
Annual Sum or Average 0.206374E+11         0.146069E+10        
Minimum of Months 0.143460E+10 812.24   19.33 8.25 0.107994E+09 74.28   13.00 8.25
Maximum of Months 0.193709E+10 981.03   31.67 20.39 0.129739E+09 81.79   30.57 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.496211E+11 37929.76 24-JAN-21:00 17.00 11.91 0.649326E+09 381.55 04-JAN-23:49 17.00 11.91
February 0.446682E+11 37838.34 03-FEB-21:00 13.00 7.33 0.587065E+09 381.56 24-FEB-00:10 13.00 11.87
March 0.495631E+11 38062.26 23-MAR-20:00 14.00 13.42 0.652384E+09 381.57 10-MAR-22:10 14.00 13.42
April 0.486039E+11 38312.42 26-APR-20:00 17.00 15.07 0.629492E+09 381.58 26-APR-21:19 16.00 15.39
May 0.503310E+11 38322.27 04-MAY-20:00 17.00 15.07 0.650704E+09 381.56 15-MAY-21:10 13.83 12.68
June 0.492764E+11 38344.48 30-JUN-20:00 16.00 15.39 0.630867E+09 381.58 29-JUN-21:19 16.00 15.39
July 0.513016E+11 38565.65 19-JUL-20:00 19.00 18.34 0.649333E+09 381.59 17-JUL-21:19 19.00 18.34
August 0.515888E+11 38533.52 18-AUG-20:00 19.00 17.66 0.652081E+09 381.58 31-AUG-21:19 16.90 16.06
September 0.492336E+11 38820.66 29-SEP-20:00 25.00 13.58 0.629190E+09 381.59 29-SEP-21:10 24.58 13.52
October 0.509371E+11 38754.72 16-OCT-20:00 21.00 13.07 0.649635E+09 381.63 17-OCT-21:10 18.00 14.87
November 0.483772E+11 37844.75 28-NOV-21:00 13.00 6.31 0.628116E+09 381.59 28-NOV-22:00 9.00 4.95
December 0.496257E+11 38065.20 05-DEC-21:00 16.00 9.09 0.649326E+09 381.71 01-DEC-01:10 16.00 9.09
                     
Annual Sum or Average 0.593128E+12         0.765752E+10        
Minimum of Months 0.446682E+11 37838.34   13.00 6.31 0.587065E+09 381.55   9.00 4.95
Maximum of Months 0.515888E+11 38820.66   25.00 18.34 0.652384E+09 381.71   24.58 18.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.226526E+11 12545.84 14-JAN-11:35 26.00 11.75 0.929859E+10 6041.60 20-JAN-23:10 13.83 13.83
February 0.193843E+11 11740.80 04-FEB-11:35 20.67 8.25 0.826952E+10 6016.08 01-FEB-22:40 20.67 8.25
March 0.206058E+11 11862.59 11-MAR-11:35 24.00 13.82 0.901650E+10 5930.88 23-MAR-21:40 13.33 12.77
April 0.208677E+11 10538.79 08-APR-10:35 21.67 16.37 0.877008E+10 5905.35 26-APR-22:10 16.00 15.29
May 0.204680E+11 9857.86 04-MAY-18:10 18.83 14.89 0.893119E+10 5936.79 04-MAY-22:10 16.83 15.02
June 0.204688E+11 9828.98 29-JUN-18:10 21.50 18.39 0.878035E+10 5879.40 27-JUN-22:10 21.50 18.39
July 0.222314E+11 10414.47 30-JUL-10:35 24.67 20.10 0.916592E+10 5953.74 31-JUL-22:10 18.65 17.88
August 0.231279E+11 10825.91 27-AUG-10:35 23.33 18.72 0.938585E+10 6016.39 18-AUG-22:10 23.33 18.72
September 0.225199E+11 12598.08 30-SEP-10:35 30.57 17.23 0.912995E+10 6408.84 29-SEP-21:40 30.57 17.23
October 0.240732E+11 13360.74 15-OCT-10:35 31.67 16.43 0.961426E+10 6427.32 16-OCT-22:10 20.17 11.06
November 0.223059E+11 13148.76 19-NOV-10:53 26.00 15.07 0.907821E+10 6105.69 27-NOV-22:40 16.00 5.61
December 0.231188E+11 12430.80 30-DEC-11:35 21.33 11.09 0.939969E+10 6190.92 05-DEC-23:10 21.33 11.09
                     
Annual Sum or Average 0.261824E+12         0.108840E+12        
Minimum of Months 0.193843E+11 9828.98   18.83 8.25 0.826952E+10 5879.40   13.33 5.61
Maximum of Months 0.240732E+11 13360.74   31.67 20.10 0.961426E+10 6427.32   30.57 18.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.686400E+11 32088.77 22-JAN-11:35 16.67 11.79 0.295575E+11 19183.48 20-JAN-23:10 16.67 11.79
February 0.608044E+11 31280.51 04-FEB-11:35 20.67 8.25 0.264606E+11 19177.16 03-FEB-23:10 20.67 8.25
March 0.661343E+11 31414.93 11-MAR-11:35 24.00 13.82 0.290212E+11 18966.79 24-MAR-22:10 13.00 11.29
April 0.661942E+11 31119.25 26-APR-18:10 18.67 15.37 0.283595E+11 18980.67 26-APR-22:10 16.00 15.29
May 0.676021E+11 31410.77 04-MAY-18:10 18.83 14.89 0.291873E+11 19122.86 04-MAY-22:10 16.83 15.02
June 0.673240E+11 31599.93 29-JUN-18:10 21.50 18.39 0.286999E+11 19091.97 28-JUN-22:10 21.50 18.39
July 0.717698E+11 32309.83 19-JUL-18:10 22.67 18.90 0.299351E+11 19186.19 26-JUL-22:10 17.00 15.84
August 0.728400E+11 32307.46 17-AUG-18:10 20.77 18.28 0.303722E+11 19186.19 02-AUG-22:10 20.77 18.28
September 0.699288E+11 34668.73 30-SEP-10:35 30.57 17.23 0.293005E+11 19186.04 13-SEP-22:10 30.57 17.23
October 0.734052E+11 35536.82 16-OCT-21:52 20.00 11.09 0.305794E+11 19186.09 18-OCT-21:30 14.50 14.21
November 0.677438E+11 33624.64 19-NOV-11:35 26.00 15.32 0.289507E+11 19185.15 27-NOV-23:10 16.00 5.58
December 0.695546E+11 31884.82 30-DEC-11:35 21.33 11.09 0.298250E+11 19185.61 05-DEC-23:10 21.33 11.09
                     
Annual Sum or Average 0.821941E+12         0.350249E+12        
Minimum of Months 0.608044E+11 31119.25   16.67 8.25 0.264606E+11 18966.79   13.00 5.58
Maximum of Months 0.734052E+11 35536.82   30.57 18.90 0.305794E+11 19186.19   30.57 18.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.596500E+09 3053.25 14-JAN-16:11 23.00 12.42 98364164.17 56.69 20-JAN-22:00 14.00 14.00
February 0.526096E+09 3065.39 03-FEB-16:11 20.00 10.06 88557123.78 56.69 16-FEB-22:19 12.00 11.46
March 0.547714E+09 2715.12 05-MAR-16:11 14.33 11.15 98071536.33 56.69 15-MAR-21:10 13.00 12.35
April 0.991469E+09 2866.03 01-APR-18:02 17.83 8.84 95703299.94 56.69 27-APR-21:10 14.00 12.84
May 0.944720E+09 2838.61 24-MAY-08:61 18.00 8.80 98825098.39 56.69 03-MAY-21:19 18.00 8.80
June 0.121267E+10 2774.45 28-JUN-18:01 18.67 16.49 95915812.37 56.69 28-JUN-21:49 17.00 16.37
July 0.161906E+10 2787.62 17-JUL-18:01 21.83 18.48 99288792.63 56.69 18-JUL-21:49 17.17 17.06
August 0.166381E+10 2775.55 17-AUG-18:02 20.77 18.28 99410499.96 56.69 11-AUG-21:40 20.77 18.28
September 0.136871E+10 2733.30 21-SEP-15:12 27.33 19.76 95987574.36 56.69 30-SEP-23:10 18.23 17.87
October 0.135068E+10 3101.25 14-OCT-08:61 27.67 13.01 99095201.49 56.69 17-OCT-22:49 16.33 12.39
November 0.757796E+09 3025.79 27-NOV-16:11 19.33 7.38 95520675.69 56.69 10-NOV-23:19 19.33 7.38
December 0.678023E+09 3061.56 19-DEC-16:11 20.33 7.94 98487292.08 56.69 07-DEC-22:30 20.33 7.94
                     
Annual Sum or Average 0.122572E+11         0.116323E+10        
Minimum of Months 0.526096E+09 2715.12   14.33 7.38 88557123.78 56.69   12.00 7.38
Maximum of Months 0.166381E+10 3101.25   27.67 19.76 99410499.96 56.69   20.77 18.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.201714E+09 2718.28 09-JAN-16:11 15.00 9.49 97633818.62 64.02 18-JAN-22:40 16.33 13.19
February 0.234003E+09 2877.66 06-FEB-16:11 14.67 10.54 88156521.97 56.69 01-FEB-22:10 14.67 10.54
March 0.296034E+09 2622.39 19-MAR-18:11 13.67 12.71 98294960.35 57.38 22-MAR-18:10 15.50 14.39
April 0.641114E+09 2893.88 19-APR-18:01 14.00 12.24 99017414.85 74.45 26-APR-21:40 16.00 15.39
May 0.711110E+09 2824.18 24-MAY-08:51 18.00 9.64 0.103283E+09 74.72 03-MAY-21:40 18.00 9.64
June 0.862040E+09 2692.62 04-JUN-19:31 15.00 13.18 0.105515E+09 78.76 30-JUN-18:10 18.83 16.43
July 0.115138E+10 2589.43 09-JUL-21:51 17.00 14.51 0.112084E+09 78.42 07-JUL-21:10 17.00 14.51
August 0.109230E+10 2531.90 21-AUG-20:11 15.00 13.80 0.111218E+09 77.29 09-AUG-21:40 15.00 13.80
September 0.838801E+09 2626.16 30-SEP-08:61 25.38 14.89 0.102421E+09 73.29 13-SEP-21:40 25.38 14.89
October 0.755577E+09 3073.46 14-OCT-08:61 27.67 13.01 0.104209E+09 74.58 16-OCT-21:40 19.33 11.10
November 0.312297E+09 2734.19 28-NOV-19:01 12.33 7.07 95472151.58 65.65 10-NOV-22:10 12.33 7.07
December 0.216559E+09 2783.94 19-DEC-19:01 14.00 4.98 97776586.07 64.54 05-DEC-22:40 14.00 4.98
                     
Annual Sum or Average 0.731293E+10         0.121508E+10        
Minimum of Months 0.201714E+09 2531.90   12.33 4.98 88156521.97 56.69   12.33 4.98
Maximum of Months 0.115138E+10 3073.46   27.67 14.89 0.112084E+09 78.76   25.38 16.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.420274E+09 553.77 14-JAN-12:40 25.33 11.70 0.00 0.00 01-JAN-00:10 25.33 11.70
February 0.270301E+09 489.66 02-FEB-12:40 19.33 12.36 0.00 0.00 01-FEB-00:10 19.33 12.36
March 0.202385E+09 410.34 11-MAR-13:10 24.00 13.64 0.00 0.00 01-MAR-00:10 24.00 13.64
April 0.221519E+09 284.73 08-APR-12:50 22.17 16.56 0.00 0.00 01-APR-00:10 22.17 16.56
May 0.132033E+09 201.52 04-MAY-12:30 23.50 16.62 0.00 0.00 01-MAY-00:10 23.50 16.62
June 0.168255E+09 180.89 30-JUN-06:52 18.00 16.69 0.00 0.00 01-JUN-00:10 18.00 16.69
July 0.256340E+09 213.21 30-JUL-08:00 20.00 18.03 0.00 0.00 01-JUL-00:10 20.00 18.03
August 0.347190E+09 270.92 30-AUG-13:00 24.00 18.12 0.00 0.00 01-AUG-00:10 24.00 18.12
September 0.394896E+09 507.52 30-SEP-13:05 32.00 16.98 0.00 0.00 01-SEP-00:10 32.00 16.98
October 0.512710E+09 614.45 16-OCT-12:20 35.37 17.35 0.00 0.00 01-OCT-00:10 35.37 17.35
November 0.430797E+09 584.78 19-NOV-12:30 26.50 15.22 0.00 0.00 01-NOV-00:10 26.50 15.22
December 0.477509E+09 566.84 19-DEC-13:00 26.00 11.60 0.00 0.00 01-DEC-00:10 26.00 11.60
                     
Annual Sum or Average 0.383421E+10         0.00        
Minimum of Months 0.132033E+09 180.89   18.00 11.60 0.00 0.00   18.00 11.60
Maximum of Months 0.512710E+09 614.45   35.37 18.12 0.00 0.00   35.37 18.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.239262E+09 933.73 16-JAN-09:02 15.33 6.47 97477451.42 67.85 18-JAN-22:49 16.17 13.11
February 0.248187E+09 922.76 03-FEB-19:01 13.83 7.99 87840249.85 57.50 13-FEB-21:19 14.67 14.08
March 0.287403E+09 851.14 13-MAR-18:01 13.00 11.39 97581355.02 57.26 15-MAR-01:10 8.00 7.91
April 0.358852E+09 925.04 02-APR-08:51 19.00 9.47 95840979.94 70.48 25-APR-21:10 14.83 14.24
May 0.414420E+09 932.07 24-MAY-08:51 18.00 9.64 0.100041E+09 71.07 04-MAY-21:00 18.00 9.64
June 0.441976E+09 904.91 24-JUN-08:51 21.00 15.98 0.100332E+09 73.82 30-JUN-21:00 16.10 16.10
July 0.511851E+09 930.26 18-JUL-18:01 23.33 19.62 0.105857E+09 75.03 07-JUL-21:10 23.33 19.62
August 0.480669E+09 878.15 14-AUG-15:12 25.67 19.05 0.105334E+09 72.95 16-AUG-21:00 17.80 17.16
September 0.400962E+09 862.08 03-SEP-08:51 20.00 15.11 98837625.23 70.75 22-SEP-21:00 17.00 16.37
October 0.408481E+09 1039.01 14-OCT-08:61 27.67 13.01 0.102090E+09 73.20 04-OCT-21:19 27.67 13.01
November 0.274659E+09 949.94 19-NOV-09:41 25.67 13.67 94448754.13 67.21 10-NOV-22:10 25.67 13.67
December 0.241073E+09 933.55 19-DEC-19:01 14.00 4.98 97236964.45 67.70 06-DEC-22:10 14.00 4.98
                     
Annual Sum or Average 0.430780E+10         0.118292E+10        
Minimum of Months 0.239262E+09 851.14   13.00 4.98 87840249.85 57.26   8.00 4.98
Maximum of Months 0.511851E+09 1039.01   27.67 19.62 0.105857E+09 75.03   27.67 19.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.621971E+09 2735.41 14-JAN-16:11 23.00 12.42 98695103.19 56.69 20-JAN-23:19 13.67 13.67
February 0.491920E+09 2730.37 03-FEB-09:01 18.50 7.20 88622730.04 56.69 16-FEB-22:10 12.00 11.46
March 0.535043E+09 2452.33 24-MAR-15:11 18.00 15.28 98268405.52 56.69 23-MAR-22:00 18.00 15.28
April 0.901672E+09 2726.99 02-APR-08:61 17.33 8.66 95835710.58 56.69 27-APR-02:20 15.67 15.06
May 0.818441E+09 2733.82 24-MAY-08:61 18.00 8.80 98925174.62 56.69 03-MAY-01:10 18.00 8.80
June 0.103412E+10 2496.54 20-JUN-15:11 21.67 15.69 95962659.33 56.69 30-JUN-02:20 17.00 16.37
July 0.146909E+10 2529.44 02-JUL-08:61 19.50 16.59 99461987.28 56.69 24-JUL-21:49 18.00 17.35
August 0.157236E+10 2533.40 13-AUG-08:61 22.33 18.30 99578292.93 56.69 16-AUG-21:00 17.80 17.16
September 0.118955E+10 2504.42 09-SEP-15:11 21.67 18.54 95895789.57 56.69 30-SEP-23:49 18.37 17.42
October 0.128791E+10 2819.36 14-OCT-08:61 27.67 13.01 99152831.40 56.69 04-OCT-21:10 27.67 13.01
November 0.706435E+09 2755.11 27-NOV-09:01 21.17 8.41 95663491.65 56.69 20-NOV-23:30 21.17 8.41
December 0.673700E+09 2772.75 05-DEC-09:01 24.33 12.02 98732781.88 56.69 07-DEC-22:40 12.27 12.24
                     
Annual Sum or Average 0.113022E+11         0.116479E+10        
Minimum of Months 0.491920E+09 2452.33   17.33 7.20 88622730.04 56.69   12.00 8.41
Maximum of Months 0.157236E+10 2819.36   27.67 18.54 99578292.93 56.69   27.67 17.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.235313E+09 2568.35 14-JAN-09:52 22.00 9.25 97723640.90 63.18 24-JAN-22:40 15.00 11.13
February 0.222704E+09 2655.25 03-FEB-09:51 21.00 8.28 87910670.00 56.69 01-FEB-22:19 21.00 8.28
March 0.303635E+09 2616.58 23-MAR-08:51 19.00 14.76 98113837.33 56.69 23-MAR-21:40 13.33 12.77
April 0.611118E+09 2862.21 02-APR-08:51 19.00 9.47 97694390.49 70.36 26-APR-21:49 16.00 15.39
May 0.644951E+09 2949.46 24-MAY-08:51 18.00 9.64 0.101756E+09 71.52 04-MAY-21:40 18.00 9.64
June 0.783421E+09 2769.92 23-JUN-08:51 21.00 15.42 0.102014E+09 72.40 30-JUN-21:49 16.08 15.88
July 0.108072E+10 2737.65 04-JUL-08:51 22.00 15.83 0.108579E+09 74.20 19-JUL-21:40 18.00 17.57
August 0.106221E+10 2643.78 22-AUG-08:51 19.00 14.76 0.108404E+09 73.86 15-AUG-21:40 19.00 14.76
September 0.730958E+09 2684.66 12-SEP-08:51 21.00 15.98 0.100383E+09 69.91 13-SEP-21:40 17.00 16.37
October 0.716680E+09 3144.43 17-OCT-08:21 27.50 13.36 0.103447E+09 72.87 16-OCT-21:40 27.50 13.36
November 0.296797E+09 2584.35 28-NOV-09:52 21.00 8.49 95059663.06 62.24 10-NOV-22:10 21.00 8.49
December 0.227933E+09 2815.31 05-DEC-09:41 25.67 12.88 97796519.05 64.46 05-DEC-22:40 17.67 9.41
                     
Annual Sum or Average 0.691644E+10         0.119888E+10        
Minimum of Months 0.222704E+09 2568.35   18.00 8.28 87910670.00 56.69   13.33 8.28
Maximum of Months 0.108072E+10 3144.43   27.50 15.98 0.108579E+09 74.20   27.50 17.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.364146E+10 1844.41 22-JAN-11:35 16.67 11.79 0.129079E+10 808.81 20-JAN-23:10 16.67 11.79
February 0.326944E+10 1814.81 04-FEB-11:35 20.67 8.25 0.116386E+10 806.82 03-FEB-23:10 20.67 8.25
March 0.351728E+10 1822.03 12-MAR-10:35 21.33 14.69 0.127211E+10 802.87 24-MAR-21:49 13.00 11.39
April 0.371207E+10 1912.81 30-APR-10:35 25.67 16.97 0.127414E+10 816.07 27-APR-21:49 25.67 16.97
May 0.386112E+10 1915.57 04-MAY-10:35 22.00 15.73 0.132589E+10 836.02 04-MAY-22:10 16.83 15.02
June 0.393866E+10 1973.16 25-JUN-10:35 23.00 17.26 0.132384E+10 849.51 30-JUN-22:10 16.13 16.03
July 0.432393E+10 2060.22 23-JUL-10:35 25.67 20.39 0.141091E+10 861.20 31-JUL-22:10 18.65 17.88
August 0.438224E+10 2079.22 19-AUG-10:35 24.67 20.11 0.143035E+10 870.52 18-AUG-22:10 24.67 20.11
September 0.407046E+10 2156.67 30-SEP-10:35 30.57 17.23 0.135090E+10 872.77 29-SEP-22:10 30.57 17.23
October 0.426982E+10 2148.07 16-OCT-10:35 36.33 17.49 0.141253E+10 896.14 17-OCT-22:10 17.67 13.97
November 0.372126E+10 1920.68 19-NOV-11:35 26.00 15.32 0.128589E+10 839.87 01-NOV-00:10 26.00 15.32
December 0.376256E+10 1839.05 05-DEC-11:35 23.33 12.89 0.131314E+10 820.71 05-DEC-23:10 17.33 9.21
                     
Annual Sum or Average 0.464703E+11         0.158544E+11        
Minimum of Months 0.326944E+10 1814.81   16.67 8.25 0.116386E+10 802.87   13.00 8.25
Maximum of Months 0.438224E+10 2156.67   36.33 20.39 0.143035E+10 896.14   30.57 20.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.497445E+09 3171.30 14-JAN-16:11 23.00 12.42 98058120.84 56.70 19-JAN-02:30 12.00 10.35
February 0.440016E+09 3180.09 03-FEB-16:11 20.00 10.06 88265013.45 56.69 01-FEB-22:19 20.00 10.06
March 0.497535E+09 2823.55 15-MAR-15:11 16.67 14.39 97843659.80 56.69 23-MAR-22:10 12.83 12.37
April 0.972096E+09 3006.54 01-APR-18:02 17.83 8.84 95625700.10 56.69 11-APR-04:10 12.83 12.37
May 0.913517E+09 2920.87 24-MAY-08:61 18.00 8.80 98763814.30 56.69 23-MAY-04:40 18.00 8.80
June 0.122611E+10 2866.12 28-JUN-18:01 18.67 16.49 95874561.23 56.69 25-JUN-00:30 18.67 16.49
July 0.166930E+10 2894.59 17-JUL-18:01 21.83 18.48 99254573.52 56.69 19-JUL-21:40 18.00 17.57
August 0.169056E+10 2885.94 03-AUG-18:01 18.83 17.02 99357022.52 56.69 18-AUG-21:40 19.00 17.66
September 0.133495E+10 2811.15 24-SEP-15:11 18.67 16.96 95903392.10 56.69 07-SEP-00:49 18.67 16.96
October 0.125690E+10 3215.93 26-OCT-15:11 22.33 12.84 98960227.66 56.70 07-OCT-03:00 22.33 12.84
November 0.632358E+09 3135.85 30-NOV-16:11 17.67 10.64 95264355.92 56.69 10-NOV-22:10 17.67 10.64
December 0.558453E+09 3179.84 19-DEC-16:11 20.33 7.94 98144595.56 56.69 20-DEC-00:30 9.50 1.81
                     
Annual Sum or Average 0.116892E+11         0.116132E+10        
Minimum of Months 0.440016E+09 2811.15   16.67 7.94 88265013.45 56.69   9.50 1.81
Maximum of Months 0.169056E+10 3215.93   23.00 18.48 99357022.52 56.70   22.33 17.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.130768E+09 2775.92 09-JAN-16:11 15.00 9.49 97095175.45 62.70 18-JAN-22:30 16.50 13.26
February 0.163891E+09 2971.99 06-FEB-16:11 14.67 10.54 87788280.70 56.69 01-FEB-22:19 14.67 10.54
March 0.241698E+09 2828.97 19-MAR-18:11 13.67 12.71 98201031.71 60.31 22-MAR-18:10 15.50 14.39
April 0.610179E+09 3123.67 23-APR-18:11 14.67 13.07 99712188.44 79.13 26-APR-18:10 18.67 15.37
May 0.691963E+09 2975.55 18-MAY-19:11 13.67 12.32 0.104064E+09 77.30 03-MAY-18:10 13.67 12.32
June 0.915268E+09 2887.22 04-JUN-19:31 15.00 13.18 0.107318E+09 84.25 30-JUN-18:10 18.83 16.43
July 0.126052E+10 2748.93 08-JUL-21:11 15.00 13.80 0.114180E+09 83.28 25-JUL-18:10 20.67 18.14
August 0.116588E+10 2655.97 21-AUG-20:11 15.00 13.80 0.112810E+09 81.53 03-AUG-18:10 15.00 13.80
September 0.823289E+09 2752.89 21-SEP-15:12 27.33 19.76 0.102873E+09 74.36 13-SEP-21:40 27.33 19.76
October 0.680842E+09 3101.98 14-OCT-08:61 27.67 13.01 0.103881E+09 74.29 16-OCT-21:40 19.33 11.10
November 0.204875E+09 2755.47 28-NOV-19:01 12.33 7.07 95003342.70 63.66 10-NOV-22:10 12.33 7.07
December 0.134655E+09 2819.93 19-DEC-19:01 14.00 4.98 97121080.40 62.83 05-DEC-22:40 14.00 4.98
                     
Annual Sum or Average 0.702383E+10         0.122005E+10        
Minimum of Months 0.130768E+09 2655.97   12.33 4.98 87788280.70 56.69   12.33 4.98
Maximum of Months 0.126052E+10 3123.67   27.67 19.76 0.114180E+09 84.25   27.33 19.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.878236E+09 1719.83 14-JAN-16:11 23.00 12.42 99174050.45 57.36 12-JAN-05:49 23.00 12.42
February 0.602919E+09 1709.78 03-FEB-16:11 20.00 10.06 89115045.52 57.39 10-FEB-03:00 8.50 8.42
March 0.520717E+09 1507.09 24-MAR-18:01 13.00 11.87 98518671.85 57.32 02-MAR-04:19 13.00 11.87
April 0.601523E+09 1620.68 01-APR-18:02 17.83 8.84 95635750.47 56.69 13-APR-21:10 14.00 13.42
May 0.427274E+09 1543.24 24-MAY-08:61 18.00 8.80 98421944.56 56.69 25-MAY-22:10 15.00 13.80
June 0.505710E+09 1510.04 21-JUN-15:11 22.00 16.41 95518040.16 56.69 30-JUN-00:10 17.00 16.90
July 0.712301E+09 1547.70 18-JUL-18:01 23.33 19.62 99085492.44 56.69 31-JUL-21:10 18.95 17.72
August 0.869541E+09 1551.03 02-AUG-15:11 22.67 18.32 99296035.58 56.69 14-AUG-21:40 18.33 17.46
September 0.884487E+09 1537.34 21-SEP-15:12 27.33 19.76 95830290.98 56.69 06-SEP-21:49 27.33 19.76
October 0.108714E+10 1727.93 14-OCT-08:61 27.67 13.01 99184897.68 56.69 19-OCT-22:00 17.00 13.94
November 0.881384E+09 1703.46 27-NOV-09:01 21.17 8.41 96068551.77 57.35 26-NOV-05:30 21.17 8.41
December 0.955482E+09 1716.75 19-DEC-16:11 20.33 7.94 99242994.87 57.37 29-DEC-04:40 8.00 2.08
                     
Annual Sum or Average 0.892671E+10         0.116509E+10        
Minimum of Months 0.427274E+09 1507.09   13.00 7.94 89115045.52 56.69   8.00 2.08
Maximum of Months 0.108714E+10 1727.93   27.67 19.76 99296035.58 57.39   27.33 19.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.397916E+11 18383.65 18-JAN-19:10 18.83 14.20 0.167716E+11 11270.19 18-JAN-23:10 15.67 12.73
February 0.362047E+11 17993.18 01-FEB-22:00 13.00 11.87 0.152509E+11 11149.74 01-FEB-23:10 13.00 11.39
March 0.402896E+11 18482.31 23-MAR-18:10 16.50 14.36 0.169581E+11 11244.64 24-MAR-22:10 13.00 11.29
April 0.406741E+11 19224.45 26-APR-18:10 18.67 15.37 0.166282E+11 11348.95 26-APR-22:10 16.00 15.29
May 0.423996E+11 19400.11 04-MAY-18:10 18.83 14.89 0.173190E+11 11348.91 03-MAY-22:10 18.83 14.89
June 0.423634E+11 19835.23 29-JUN-18:10 21.50 18.39 0.170446E+11 11349.12 19-JUN-22:10 21.50 18.39
July 0.446827E+11 20050.39 19-JUL-18:10 22.67 18.90 0.176312E+11 11349.12 07-JUL-21:30 22.67 18.90
August 0.445214E+11 19688.14 17-AUG-18:10 20.77 18.28 0.176918E+11 11349.08 02-AUG-22:10 20.77 18.28
September 0.419433E+11 19610.55 29-SEP-21:20 24.57 13.54 0.168984E+11 11348.80 11-SEP-22:10 24.57 13.54
October 0.429589E+11 19638.80 04-OCT-21:20 21.00 18.98 0.173902E+11 11348.89 16-OCT-22:10 20.17 11.06
November 0.392596E+11 18153.02 01-NOV-18:10 15.83 12.41 0.163989E+11 11221.60 01-NOV-22:10 13.83 11.14
December 0.399400E+11 18351.25 05-DEC-22:00 17.00 9.46 0.168208E+11 11326.45 05-DEC-23:10 17.33 9.21
                     
Annual Sum or Average 0.495029E+12         0.202804E+12        
Minimum of Months 0.362047E+11 17993.18   13.00 9.46 0.152509E+11 11149.74   13.00 9.21
Maximum of Months 0.446827E+11 20050.39   24.57 18.98 0.176918E+11 11349.12   24.57 18.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.416739E+11 19672.31 18-JAN-22:10 16.83 13.41 0.172832E+11 11348.37 24-JAN-23:10 14.33 10.84
February 0.379095E+11 18728.55 01-FEB-23:00 13.00 11.29 0.157178E+11 11344.94 24-FEB-00:10 13.00 11.87
March 0.422676E+11 19216.42 24-MAR-21:10 13.00 11.77 0.174957E+11 11344.20 13-MAR-22:40 13.00 11.77
April 0.424248E+11 20645.79 26-APR-21:10 16.00 15.39 0.170818E+11 11348.99 25-APR-21:30 16.00 15.39
May 0.442226E+11 20868.95 04-MAY-21:10 17.00 15.07 0.177784E+11 11348.92 03-MAY-22:10 17.00 15.07
June 0.440326E+11 20943.80 27-JUN-21:10 17.00 16.37 0.174402E+11 11349.12 19-JUN-22:10 17.00 16.37
July 0.462957E+11 21062.11 19-JUL-21:10 18.00 17.89 0.180150E+11 11349.09 07-JUL-21:30 18.00 17.89
August 0.461103E+11 20998.83 18-AUG-21:10 19.00 17.66 0.180626E+11 11349.09 02-AUG-22:10 19.00 17.66
September 0.434939E+11 21234.67 29-SEP-21:10 24.58 13.52 0.172738E+11 11348.81 12-SEP-22:10 24.58 13.52
October 0.445507E+11 20974.03 16-OCT-21:10 18.33 11.06 0.177794E+11 11348.90 16-OCT-22:10 20.17 11.06
November 0.409402E+11 19083.18 10-NOV-22:10 15.00 13.80 0.168589E+11 11348.37 10-NOV-22:30 15.00 13.80
December 0.417312E+11 19614.42 05-DEC-22:10 17.17 9.45 0.173109E+11 11348.28 05-DEC-23:10 17.33 9.21
                     
Annual Sum or Average 0.515653E+12         0.208098E+12        
Minimum of Months 0.379095E+11 18728.55   13.00 9.45 0.157178E+11 11344.20   13.00 9.21
Maximum of Months 0.462957E+11 21234.67   24.58 17.89 0.180626E+11 11349.12   24.58 17.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.503798E+11 27239.42 14-JAN-11:50 26.00 11.78 0.188680E+11 11319.57 14-JAN-18:10 20.67 11.38
February 0.454401E+11 27066.22 01-FEB-11:50 25.50 14.48 0.170436E+11 11319.53 04-FEB-18:10 13.83 11.23
March 0.505649E+11 27917.66 19-MAR-10:35 19.33 15.06 0.188761E+11 11319.50 11-MAR-18:10 19.33 15.06
April 0.505162E+11 28327.74 30-APR-10:40 25.67 16.97 0.182623E+11 11319.63 08-APR-17:10 25.67 16.97
May 0.521688E+11 27982.27 04-MAY-10:50 22.00 15.56 0.188717E+11 11319.62 20-MAY-17:10 17.50 12.79
June 0.515090E+11 28347.66 25-JUN-10:40 23.00 17.26 0.182660E+11 11319.62 17-JUN-17:10 23.00 17.26
July 0.541687E+11 28761.66 23-JUL-10:40 25.67 20.39 0.188681E+11 11319.66 08-JUL-17:10 25.67 20.39
August 0.542376E+11 28613.75 19-AUG-10:40 24.67 20.11 0.188754E+11 11319.66 12-AUG-17:10 24.67 20.11
September 0.513958E+11 29094.77 30-SEP-10:50 30.78 17.57 0.182615E+11 11319.65 30-SEP-17:10 25.50 17.63
October 0.527156E+11 29001.78 15-OCT-10:40 31.67 16.43 0.188688E+11 11319.61 14-OCT-17:10 31.67 16.43
November 0.491677E+11 27825.70 19-NOV-11:50 26.00 15.39 0.182586E+11 11319.52 25-NOV-18:10 13.00 11.21
December 0.503674E+11 27090.70 05-DEC-11:50 23.17 12.83 0.188680E+11 11319.53 23-DEC-18:10 10.83 10.73
                     
Annual Sum or Average 0.612632E+12         0.222188E+12        
Minimum of Months 0.454401E+11 27066.22   19.33 11.78 0.170436E+11 11319.50   10.83 10.73
Maximum of Months 0.542376E+11 29094.77   31.67 20.39 0.188761E+11 11319.66   31.67 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.446335E+10 2359.67 20-JAN-11:35 21.67 15.71 0.149306E+10 968.09 18-JAN-22:40 21.67 15.71
February 0.403389E+10 2257.46 04-FEB-11:50 20.83 8.35 0.135606E+10 944.65 01-FEB-22:49 20.83 8.35
March 0.441646E+10 2334.01 11-MAR-11:35 24.00 13.82 0.149037E+10 971.24 24-MAR-21:49 13.00 11.39
April 0.475971E+10 2765.77 27-APR-14:10 20.03 15.47 0.153090E+10 1000.29 27-APR-22:10 14.00 12.84
May 0.494778E+10 3207.99 04-MAY-12:00 24.00 16.55 0.159298E+10 1007.40 04-MAY-22:10 16.83 15.02
June 0.528951E+10 3225.71 30-JUN-15:35 22.80 17.87 0.160958E+10 1007.40 29-JUN-22:10 22.80 17.87
July 0.621355E+10 3676.43 30-JUL-13:30 24.00 19.60 0.169713E+10 1007.40 26-JUL-22:10 24.00 19.60
August 0.638561E+10 3919.37 19-AUG-13:10 27.00 20.18 0.170694E+10 1007.40 03-AUG-22:10 27.00 20.18
September 0.559133E+10 5439.34 30-SEP-13:30 32.00 17.24 0.161805E+10 1007.40 13-SEP-22:10 32.00 17.24
October 0.586263E+10 5335.87 16-OCT-12:30 35.05 17.21 0.166103E+10 1007.40 18-OCT-21:30 14.50 14.21
November 0.455830E+10 3042.65 19-NOV-13:00 27.00 14.96 0.149796E+10 989.51 01-NOV-00:10 27.00 14.96
December 0.456690E+10 2771.40 19-DEC-13:00 26.00 11.60 0.151743E+10 983.18 05-DEC-23:10 26.00 11.60
                     
Annual Sum or Average 0.610890E+11         0.187715E+11        
Minimum of Months 0.403389E+10 2257.46   20.03 8.35 0.135606E+10 944.65   13.00 8.35
Maximum of Months 0.638561E+10 5439.34   35.05 20.18 0.170694E+10 1007.40   32.00 20.18



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 35129896.03 979.94 09-JAN-16:14 15.00
February 22049700.97 996.71 23-FEB-16:14 14.00
March 47119644.68 989.69 06-MAR-16:14 12.00
April 7226563.93 969.32 19-APR-08:03 14.33
May 3966787.75 962.92 15-MAY-08:03 16.17
June 1662801.68 891.99 08-JUN-15:15 18.00
July 1095570.85 823.09 03-JUL-08:05 19.33
August 1152381.60 838.17 09-AUG-08:05 19.50
September 1581145.03 717.39 13-SEP-08:05 20.33
October 2369516.81 946.94 25-OCT-18:04 18.50
November 4753923.08 975.20 21-NOV-19:04 13.17
December 19224088.14 981.41 19-DEC-19:04 14.00
         
Annual Sum or Average 0.147332E+09      
Minimum of Months 1095570.85 717.39   12.00
Maximum of Months 47119644.68 996.71   20.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 97922803.94 971.46 22-JAN-16:14 14.33
February 37919273.03 966.75 07-FEB-17:04 13.83
March 65366617.13 963.47 06-MAR-16:14 12.00
April 7724292.13 963.13 14-APR-18:04 12.83
May 3191312.91 940.68 01-MAY-08:53 17.00
June 811796.68 919.66 02-JUN-08:53 19.00
July 210653.31 541.34 10-JUL-08:54 21.00
August 289294.41 495.99 06-AUG-08:54 24.00
September 1347148.19 926.15 15-SEP-08:53 18.00
October 1602876.36 923.85 15-OCT-08:04 29.67
November 16896303.36 955.53 04-NOV-18:04 12.00
December 64032062.74 966.96 17-DEC-19:03 13.17
         
Annual Sum or Average 0.297314E+09      
Minimum of Months 210653.31 495.99   12.00
Maximum of Months 97922803.94 971.46   29.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 957235.53 251.26 09-JAN-09:03 11.50
February 687963.13 248.81 26-FEB-16:14 12.40
March 782789.70 248.53 02-MAR-09:04 13.17
April 160018.15 216.70 03-APR-08:53 20.00
May 133930.80 229.50 24-MAY-08:54 18.00
June 43565.39 221.62 02-JUN-08:54 19.00
July 5206.21 85.63 08-JUL-08:56 19.00
August 19413.29 178.95 22-AUG-08:54 19.00
September 158651.08 235.95 19-SEP-08:54 17.00
October 172027.99 209.67 13-OCT-08:53 24.00
November 604072.23 249.60 21-NOV-16:14 14.33
December 929914.15 249.01 26-DEC-19:04 12.00
         
Annual Sum or Average 4654787.64      
Minimum of Months 5206.21 85.63   11.50
Maximum of Months 957235.53 251.26   24.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 35090236.68 954.57 09-JAN-16:14 15.00
February 27259415.54 941.77 23-FEB-16:14 14.00
March 56468107.26 945.21 04-MAR-16:14 14.67
April 6472497.33 939.03 14-APR-18:04 12.83
May 4915048.94 922.20 22-MAY-18:04 16.50
June 1498972.04 917.69 01-JUN-18:04 16.83
July 173234.93 807.52 09-JUL-18:05 17.83
August 36579.76 329.62 21-AUG-18:04 16.83
September 1577311.51 895.21 05-SEP-18:04 17.83
October 1576015.45 929.98 25-OCT-18:04 18.50
November 6635453.16 947.36 02-NOV-15:14 14.67
December 22538732.00 945.13 19-DEC-19:04 14.00
         
Annual Sum or Average 0.164242E+09      
Minimum of Months 36579.76 329.62   12.83
Maximum of Months 56468107.26 954.57   18.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 94990531.85 919.40 07-JAN-09:04 15.50
February 50137867.12 920.27 24-FEB-16:13 14.00
March 78959045.16 874.15 14-MAR-18:03 12.00
April 6504711.57 918.58 18-APR-18:04 13.83
May 3352617.16 879.55 13-MAY-18:04 13.67
June 588262.58 767.66 07-JUN-08:05 15.33
July 110448.96 446.75 11-JUL-21:54 16.00
August 102669.41 244.22 01-AUG-21:55 16.00
September 937193.06 624.86 02-SEP-19:14 15.00
October 795365.83 672.66 07-OCT-08:55 19.00
November 26220881.47 924.63 23-NOV-19:03 12.67
December 74299078.65 925.90 28-DEC-19:03 12.83
         
Annual Sum or Average 0.336999E+09      
Minimum of Months 102669.41 244.22   12.00
Maximum of Months 94990531.85 925.90   19.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.117902E+09 1152.42 23-JAN-16:14 17.00
February 83732868.86 1178.71 23-FEB-16:14 14.00
March 0.127928E+09 1091.65 30-MAR-08:62 9.50
April 17065461.28 1052.79 06-APR-18:04 13.00
May 13268415.77 958.50 27-MAY-08:03 16.33
June 1558570.40 796.14 08-JUN-15:15 18.00
July 927956.33 719.53 03-JUL-08:05 19.33
August 905612.40 682.17 09-AUG-08:05 19.50
September 1380439.99 910.54 21-SEP-18:04 19.00
October 5397032.95 1068.41 26-OCT-08:03 18.83
November 38796752.54 1151.48 24-NOV-16:13 15.67
December 93713821.11 1066.71 14-DEC-19:03 11.83
         
Annual Sum or Average 0.502577E+09      
Minimum of Months 905612.40 682.17   9.50
Maximum of Months 0.127928E+09 1178.71   19.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.251946E+09 1117.21 22-JAN-16:14 14.33
February 0.139625E+09 1067.32 09-FEB-09:01 11.90
March 0.167598E+09 1093.73 30-MAR-08:62 9.50
April 18583160.26 986.42 14-APR-18:04 12.83
May 10554989.77 1048.12 24-MAY-08:53 18.00
June 680398.51 665.40 08-JUN-19:05 14.00
July 131647.15 409.41 21-JUL-08:54 20.00
August 243028.77 461.23 22-AUG-21:55 16.30
September 1408016.08 832.60 02-SEP-08:54 18.00
October 6968666.81 1045.67 16-OCT-08:04 28.50
November 93130774.74 1148.67 23-NOV-19:03 12.67
December 0.213337E+09 1158.45 27-DEC-19:03 14.17
         
Annual Sum or Average 0.904207E+09      
Minimum of Months 131647.15 409.41   9.50
Maximum of Months 0.251946E+09 1158.45   28.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3145601.20 456.54 16-JAN-16:15 18.00
February 4598564.19 502.83 11-FEB-16:15 17.67
March 19983553.12 479.99 30-MAR-08:62 9.50
April 2865613.94 530.83 22-APR-15:14 16.67
May 3159618.20 613.82 12-MAY-15:14 15.67
June 1337294.12 528.28 14-JUN-18:04 17.83
July 611529.69 415.29 12-JUL-18:05 18.83
August 445204.04 347.95 31-AUG-08:05 20.50
September 841443.64 423.55 01-SEP-18:04 16.67
October 673785.23 513.39 24-OCT-15:15 19.00
November 463219.72 486.36 11-NOV-16:15 16.67
December 2572995.71 433.13 01-DEC-19:05 12.83
         
Annual Sum or Average 40698422.80      
Minimum of Months 445204.04 347.95   9.50
Maximum of Months 19983553.12 613.82   20.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:05 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104372E+11 10053.14 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.942384E+10 10053.14 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.104694E+11 10053.14 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.100833E+11 10053.14 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.104553E+11 10053.14 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.101296E+11 10053.14 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.104091E+11 10053.14 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.104734E+11 10053.14 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.100874E+11 10053.14 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.104332E+11 10053.14 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.101215E+11 10053.14 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.104091E+11 10053.14 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.122932E+12     0.143105E+12    
Minimum of Months 0.942384E+10 10053.14   0.109726E+11 9632.53  
Maximum of Months 0.104734E+11 10053.14   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.531884E+09 512.31 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.480243E+09 512.31 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.533523E+09 512.31 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.513850E+09 512.31 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.532806E+09 512.31 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.516207E+09 512.31 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.530449E+09 512.31 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.533728E+09 512.31 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.514055E+09 512.31 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.531679E+09 512.31 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.515797E+09 512.31 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.530449E+09 512.31 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.626467E+10     0.101856E+11    
Minimum of Months 0.480243E+09 512.31   0.780982E+09 685.60  
Maximum of Months 0.533728E+09 512.31   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.615923E+09 593.26 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.556123E+09 593.26 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.617822E+09 593.26 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.595041E+09 593.26 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.616991E+09 593.26 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.597770E+09 593.26 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.614262E+09 593.26 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.618059E+09 593.26 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.595278E+09 593.26 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.615686E+09 593.26 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.597295E+09 593.26 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.614262E+09 593.26 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.725451E+10     0.117950E+11    
Minimum of Months 0.556123E+09 593.26   0.904380E+09 793.93  
Maximum of Months 0.618059E+09 593.26   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.710312E+09 684.18 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.641347E+09 684.18 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.712502E+09 684.18 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.686229E+09 684.18 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.711544E+09 684.18 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.689376E+09 684.18 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.708397E+09 684.18 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.712775E+09 684.18 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.686503E+09 684.18 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.710039E+09 684.18 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.688829E+09 684.18 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.708397E+09 684.18 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.836625E+10     0.124712E+11    
Minimum of Months 0.641347E+09 684.18   0.956227E+09 839.45  
Maximum of Months 0.712775E+09 684.18   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.195918E+09 188.71 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.176896E+09 188.71 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.196522E+09 188.71 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.189275E+09 188.71 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.196257E+09 188.71 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.190143E+09 188.71 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.195389E+09 188.71 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.196597E+09 188.71 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.189351E+09 188.71 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.195842E+09 188.71 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.189992E+09 188.71 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.195389E+09 188.71 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.230757E+10     0.359760E+10    
Minimum of Months 0.176896E+09 188.71   0.275845E+09 242.16  
Maximum of Months 0.196597E+09 188.71   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.415991E+09 400.68 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.375602E+09 400.68 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.417273E+09 400.68 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.401887E+09 400.68 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.416712E+09 400.68 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.403730E+09 400.68 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.414869E+09 400.68 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.417433E+09 400.68 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.402047E+09 400.68 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.415830E+09 400.68 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.403409E+09 400.68 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.414869E+09 400.68 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.489965E+10     0.679355E+11    
Minimum of Months 0.375602E+09 400.68   0.520895E+10 4572.80  
Maximum of Months 0.417433E+09 400.68   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.120040E+10 1573.46 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.105199E+10 1573.46 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.114368E+10 1573.46 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.103851E+10 1573.46 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.101289E+10 1573.46 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.966336E+09 1573.46 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.100337E+10 1573.46 03-JUL-19:10 0.121533E+10 965.27 03-JUL-19:10
August 0.104741E+10 1573.46 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.109359E+10 1573.46 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.116826E+10 1573.46 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.114805E+10 1573.46 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.119218E+10 1573.46 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.130667E+11     0.143405E+11    
Minimum of Months 0.966336E+09 1573.46   0.109956E+10 965.27  
Maximum of Months 0.120040E+10 1573.46   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.790292E+10 7984.04 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.710893E+10 7984.04 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.788233E+10 7984.04 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.753869E+10 7984.04 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.776795E+10 7984.04 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.751622E+10 7984.04 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.772805E+10 7984.04 03-JUL-19:10 0.126273E+11 10029.21 03-JUL-19:10
August 0.780580E+10 7984.04 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.759112E+10 7984.04 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.788027E+10 7984.04 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.764821E+10 7984.04 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.787598E+10 7984.04 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.922465E+11     0.148998E+12    
Minimum of Months 0.710893E+10 7984.04   0.114244E+11 10029.21  
Maximum of Months 0.790292E+10 7984.04   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65789991.58 59.53 01-JAN-19:10 0.217935E+09 232.19 01-JAN-08:09
February 59414784.75 59.53 01-FEB-20:10 0.196843E+09 232.19 01-FEB-07:10
March 65267117.48 59.53 01-MAR-20:10 0.217824E+09 232.19 01-MAR-07:10
April 63743496.62 59.53 01-APR-18:10 0.210923E+09 232.19 01-APR-07:10
May 65528554.53 59.53 01-MAY-19:10 0.217879E+09 232.19 01-MAY-06:10
June 63237765.93 59.53 01-JUN-19:10 0.210812E+09 232.19 01-JUN-06:10
July 66042856.93 59.53 01-JUL-18:10 0.217991E+09 232.19 01-JUL-07:10
August 65267117.48 59.53 01-AUG-19:10 0.217824E+09 232.19 01-AUG-06:10
September 63760640.03 59.53 01-SEP-19:10 0.210923E+09 232.19 01-SEP-06:10
October 65781419.88 59.53 01-OCT-18:10 0.217935E+09 232.19 01-OCT-07:10
November 63490631.27 59.53 01-NOV-19:10 0.210867E+09 232.19 01-NOV-06:10
December 66051428.64 59.53 01-DEC-20:10 0.217991E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.773376E+09     0.256575E+10    
Minimum of Months 59414784.75 59.53   0.196843E+09 232.19  
Maximum of Months 66051428.64 59.53   0.217991E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65807981.74 59.54 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 59431031.62 59.54 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 65284964.65 59.54 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 63760927.16 59.54 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 65546473.20 59.54 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 63255058.18 59.54 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 66060916.23 59.54 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 65284964.65 59.54 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 63778075.26 59.54 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 65799407.69 59.54 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 63507992.67 59.54 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 66069490.28 59.54 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.773587E+09     0.256645E+10    
Minimum of Months 59431031.62 59.54   0.196897E+09 232.26  
Maximum of Months 66069490.28 59.54   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.120431E+10 1160.00 02-JAN-20:10 0.00 0.00
February 0.108739E+10 1160.00 01-FEB-20:10 0.00 0.00
March 0.120803E+10 1160.00 01-MAR-20:10 0.00 0.00
April 0.116348E+10 1160.00 03-APR-19:10 0.00 0.00
May 0.120640E+10 1160.00 01-MAY-19:10 0.00 0.00
June 0.116882E+10 1160.00 01-JUN-19:10 0.00 0.00
July 0.120107E+10 1160.00 03-JUL-19:10 0.00 0.00
August 0.120849E+10 1160.00 01-AUG-19:10 0.00 0.00
September 0.116395E+10 1160.00 01-SEP-19:10 0.00 0.00
October 0.120385E+10 1160.00 02-OCT-19:10 0.00 0.00
November 0.116789E+10 1160.00 01-NOV-19:10 0.00 0.00
December 0.120107E+10 1160.00 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.141847E+11     0.00 0.00
Minimum of Months 0.108739E+10 1160.00   0.00 0.00
Maximum of Months 0.120849E+10 1160.00   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65807981.74 59.54 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 59431031.62 59.54 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 65284964.65 59.54 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 63760927.16 59.54 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 65546473.20 59.54 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 63255058.18 59.54 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 66060916.23 59.54 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 65284964.65 59.54 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 63778075.26 59.54 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 65799407.69 59.54 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 63507992.67 59.54 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 66069490.28 59.54 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.773587E+09     0.256645E+10    
Minimum of Months 59431031.62 59.54   0.196897E+09 232.26  
Maximum of Months 66069490.28 59.54   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.253144E+10 2763.12 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.224276E+10 2763.12 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.245427E+10 2763.12 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.228981E+10 2763.12 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.230079E+10 2763.12 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.220577E+10 2763.12 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.228247E+10 2763.12 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.234263E+10 2763.12 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.235154E+10 2763.12 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.249998E+10 2763.12 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.243818E+10 2763.12 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.252984E+10 2763.12 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.284695E+11     0.175857E+12    
Minimum of Months 0.220577E+10 2763.12   0.134904E+11 6747.90  
Maximum of Months 0.253144E+10 2763.12   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.253144E+10 2763.12 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.224276E+10 2763.12 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.245427E+10 2763.12 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.228981E+10 2763.12 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.230079E+10 2763.12 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.220577E+10 2763.12 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.228247E+10 2763.12 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.234263E+10 2763.12 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.235154E+10 2763.12 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.249998E+10 2763.12 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.243818E+10 2763.12 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.252984E+10 2763.12 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.284695E+11     0.175857E+12    
Minimum of Months 0.220577E+10 2763.12   0.134904E+11 6747.90  
Maximum of Months 0.253144E+10 2763.12   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113250E+10 1090.83 02-JAN-20:10 0.360126E+11 16179.04 01-JAN-07:10
February 0.102255E+10 1090.83 01-FEB-20:10 0.325275E+11 16179.04 01-FEB-07:10
March 0.113599E+10 1090.83 01-MAR-20:10 0.360126E+11 16179.04 01-MAR-07:10
April 0.109410E+10 1090.83 03-APR-19:10 0.348509E+11 16179.04 01-APR-06:10
May 0.113446E+10 1090.83 01-MAY-19:10 0.360126E+11 16179.04 01-MAY-06:10
June 0.109912E+10 1090.83 01-JUN-19:10 0.348509E+11 16179.04 01-JUN-06:10
July 0.112945E+10 1090.83 03-JUL-19:10 0.360126E+11 16179.04 01-JUL-06:10
August 0.113643E+10 1090.83 01-AUG-19:10 0.360126E+11 16179.04 01-AUG-06:10
September 0.109454E+10 1090.83 01-SEP-19:10 0.348509E+11 16179.04 01-SEP-06:10
October 0.113207E+10 1090.83 02-OCT-19:10 0.360126E+11 16179.04 01-OCT-06:10
November 0.109825E+10 1090.83 01-NOV-19:10 0.348509E+11 16179.04 01-NOV-06:10
December 0.112945E+10 1090.83 01-DEC-20:10 0.360126E+11 16179.04 01-DEC-07:10
             
Annual Sum or Average 0.133389E+11     0.424019E+12    
Minimum of Months 0.102255E+10 1090.83   0.325275E+11 16179.04  
Maximum of Months 0.113643E+10 1090.83   0.360126E+11 16179.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.127458E+10 1227.68 02-JAN-20:10 0.00 0.00
February 0.115083E+10 1227.68 01-FEB-20:10 0.00 0.00
March 0.127851E+10 1227.68 01-MAR-20:10 0.00 0.00
April 0.123137E+10 1227.68 03-APR-19:10 0.00 0.00
May 0.127679E+10 1227.68 01-MAY-19:10 0.00 0.00
June 0.123701E+10 1227.68 01-JUN-19:10 0.00 0.00
July 0.127114E+10 1227.68 03-JUL-19:10 0.00 0.00
August 0.127900E+10 1227.68 01-AUG-19:10 0.00 0.00
September 0.123186E+10 1227.68 01-SEP-19:10 0.00 0.00
October 0.127409E+10 1227.68 02-OCT-19:10 0.00 0.00
November 0.123603E+10 1227.68 01-NOV-19:10 0.00 0.00
December 0.127114E+10 1227.68 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.150123E+11     0.00 0.00
Minimum of Months 0.115083E+10 1227.68   0.00 0.00
Maximum of Months 0.127900E+10 1227.68   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.104372E+11 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.942384E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.104694E+11 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.100833E+11 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.104553E+11 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.101296E+11 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.104091E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.104734E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.100874E+11 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.104332E+11 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.101215E+11 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.104091E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.122932E+12 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.942384E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.104734E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.531884E+09 0.864900E+09 0.00 0.00 0.00 0.00 301158.13 0.138907E+09
February 0.179968E+10 0.480243E+09 0.780982E+09 0.00 0.00 0.00 0.00 30870.44 0.119501E+09
March 0.199990E+10 0.533523E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.00 0.138222E+09
April 0.192973E+10 0.513850E+09 0.835931E+09 0.00 0.00 0.00 0.00 282036.59 0.102680E+09
May 0.199475E+10 0.532806E+09 0.865939E+09 0.00 0.00 0.00 0.00 0.00 96415317.55
June 0.193394E+10 0.516207E+09 0.838659E+09 0.00 0.00 0.00 0.00 299724.85 68691907.42
July 0.199054E+10 0.530449E+09 0.863211E+09 0.00 0.00 0.00 0.00 1904595.85 54718051.14
August 0.199896E+10 0.533728E+09 0.866978E+09 0.00 0.00 0.00 0.00 1752982.58 55454385.71
September 0.192879E+10 0.514055E+09 0.836191E+09 0.00 0.00 0.00 0.00 3262433.75 70192009.53
October 0.199148E+10 0.531679E+09 0.864640E+09 0.00 0.00 0.00 0.00 6047930.98 71707671.03
November 0.192552E+10 0.515797E+09 0.838269E+09 0.00 0.00 0.00 0.00 280923.73 0.120933E+09
December 0.199054E+10 0.530449E+09 0.863211E+09 0.00 0.00 0.00 0.00 176943.26 0.134816E+09
                   
Annual Sum or Average 0.234744E+11 0.626467E+10 0.101856E+11 0.00 0.00 0.00 0.00 14339600.17 0.117224E+10
Minimum of Months 0.179968E+10 0.480243E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 54718051.14
Maximum of Months 0.199990E+10 0.533728E+09 0.866978E+09 0.00 0.00 0.00 0.00 6047930.98 0.138907E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.615923E+09 0.100156E+10 0.00 0.00 0.00 0.00 430779.22 52247782.30
February 0.208403E+10 0.556123E+09 0.904380E+09 0.00 0.00 0.00 0.00 63073.02 45617215.14
March 0.231589E+10 0.617822E+09 0.100366E+10 0.00 0.00 0.00 0.00 86896.85 53488065.78
April 0.223463E+10 0.595041E+09 0.968011E+09 0.00 0.00 0.00 0.00 445630.43 39093444.50
May 0.230993E+10 0.616991E+09 0.100276E+10 0.00 0.00 0.00 0.00 85574.88 38110336.95
June 0.223950E+10 0.597770E+09 0.971170E+09 0.00 0.00 0.00 0.00 522117.71 26898904.77
July 0.230505E+10 0.614262E+09 0.999601E+09 0.00 0.00 0.00 0.00 1846148.96 20768663.26
August 0.231480E+10 0.618059E+09 0.100396E+10 0.00 0.00 0.00 0.00 2078941.72 20329114.52
September 0.223354E+10 0.595278E+09 0.968312E+09 0.00 0.00 0.00 0.00 1626918.82 25256877.24
October 0.230614E+10 0.615686E+09 0.100126E+10 0.00 0.00 0.00 0.00 3236644.04 26372211.54
November 0.222975E+10 0.597295E+09 0.970719E+09 0.00 0.00 0.00 0.00 309297.93 45148802.87
December 0.230505E+10 0.614262E+09 0.999601E+09 0.00 0.00 0.00 0.00 363628.80 50631502.81
                   
Annual Sum or Average 0.271834E+11 0.725451E+10 0.117950E+11 0.00 0.00 0.00 0.00 11095652.37 0.443963E+09
Minimum of Months 0.208403E+10 0.556123E+09 0.904380E+09 0.00 0.00 0.00 0.00 63073.02 20329114.52
Maximum of Months 0.231589E+10 0.618059E+09 0.100396E+10 0.00 0.00 0.00 0.00 3236644.04 53488065.78



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.710312E+09 0.105898E+10 0.00 0.00 0.00 0.00 238388.98 0.140743E+09
February 0.440737E+09 0.641347E+09 0.956227E+09 0.00 0.00 0.00 0.00 28161.29 0.125512E+09
March 0.489771E+09 0.712502E+09 0.106120E+10 0.00 0.00 0.00 0.00 9753.09 0.146521E+09
April 0.472586E+09 0.686229E+09 0.102351E+10 0.00 0.00 0.00 0.00 225898.37 0.110013E+09
May 0.488511E+09 0.711544E+09 0.106025E+10 0.00 0.00 0.00 0.00 0.00 0.110523E+09
June 0.473617E+09 0.689376E+09 0.102685E+10 0.00 0.00 0.00 0.00 16899.23 79828746.80
July 0.487480E+09 0.708397E+09 0.105691E+10 0.00 0.00 0.00 0.00 1276245.86 60483533.04
August 0.489542E+09 0.712775E+09 0.106152E+10 0.00 0.00 0.00 0.00 1457310.77 57644650.89
September 0.472357E+09 0.686503E+09 0.102382E+10 0.00 0.00 0.00 0.00 2891103.51 72423171.69
October 0.487709E+09 0.710039E+09 0.105866E+10 0.00 0.00 0.00 0.00 5504003.47 73930308.92
November 0.471555E+09 0.688829E+09 0.102637E+10 0.00 0.00 0.00 0.00 256265.67 0.123456E+09
December 0.487480E+09 0.708397E+09 0.105691E+10 0.00 0.00 0.00 0.00 174443.71 0.136840E+09
                   
Annual Sum or Average 0.574883E+10 0.836625E+10 0.124712E+11 0.00 0.00 0.00 0.00 12078473.94 0.123792E+10
Minimum of Months 0.440737E+09 0.641347E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 57644650.89
Maximum of Months 0.489771E+09 0.712775E+09 0.106152E+10 0.00 0.00 0.00 0.00 5504003.47 0.146521E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.195918E+09 0.305485E+09 0.00 0.00 0.00 0.00 894307.12 62637232.73
February 0.339028E+09 0.176896E+09 0.275845E+09 0.00 0.00 0.00 0.00 162999.30 54595315.71
March 0.376747E+09 0.196522E+09 0.306128E+09 0.00 0.00 0.00 0.00 296416.67 65218192.14
April 0.363528E+09 0.189275E+09 0.295253E+09 0.00 0.00 0.00 0.00 989244.99 45342359.57
May 0.375778E+09 0.196257E+09 0.305852E+09 0.00 0.00 0.00 0.00 265986.09 44829069.12
June 0.364321E+09 0.190143E+09 0.296217E+09 0.00 0.00 0.00 0.00 1150550.76 30627190.03
July 0.374985E+09 0.195389E+09 0.304889E+09 0.00 0.00 0.00 0.00 3424393.65 22167136.85
August 0.376571E+09 0.196597E+09 0.306219E+09 0.00 0.00 0.00 0.00 4105716.88 21079829.30
September 0.363352E+09 0.189351E+09 0.295345E+09 0.00 0.00 0.00 0.00 2955634.79 27168337.51
October 0.375161E+09 0.195842E+09 0.305393E+09 0.00 0.00 0.00 0.00 5370551.29 29034139.41
November 0.362735E+09 0.189992E+09 0.296079E+09 0.00 0.00 0.00 0.00 701921.46 52982643.86
December 0.374985E+09 0.195389E+09 0.304889E+09 0.00 0.00 0.00 0.00 929080.33 60103925.71
                   
Annual Sum or Average 0.442217E+10 0.230757E+10 0.359760E+10 0.00 0.00 0.00 0.00 21246803.33 0.515785E+09
Minimum of Months 0.339028E+09 0.176896E+09 0.275845E+09 0.00 0.00 0.00 0.00 162999.30 21079829.30
Maximum of Months 0.376747E+09 0.196597E+09 0.306219E+09 0.00 0.00 0.00 0.00 5370551.29 65218192.14



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.415991E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 293164.97 0.196219E+09
February 0.139600E+10 0.375602E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 38453.27 0.174359E+09
March 0.155131E+10 0.417273E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 0.00 0.205257E+09
April 0.149688E+10 0.401887E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 284520.17 0.151410E+09
May 0.154732E+10 0.416712E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 0.00 0.151268E+09
June 0.150015E+10 0.403730E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 23060.27 0.108999E+09
July 0.154405E+10 0.414869E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 1742672.58 82584103.31
August 0.155059E+10 0.417433E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 1989891.02 78707967.09
September 0.149615E+10 0.402047E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 3947623.85 98887272.50
October 0.154478E+10 0.415830E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 7515122.01 0.100944E+09
November 0.149361E+10 0.403409E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 349891.47 0.169079E+09
December 0.154405E+10 0.414869E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 220381.40 0.188878E+09
                   
Annual Sum or Average 0.182090E+11 0.489965E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 16404781.00 0.170659E+10
Minimum of Months 0.139600E+10 0.375602E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 78707967.09
Maximum of Months 0.155131E+10 0.417433E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 7515122.01 0.205257E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.120040E+10 0.121771E+10 0.00 0.00 0.00 0.00 1887202.59 0.293669E+09
February 0.236489E+11 0.105199E+10 0.109956E+10 0.00 0.00 0.00 0.00 204562.08 0.252378E+09
March 0.262800E+11 0.114368E+10 0.122027E+10 0.00 0.00 0.00 0.00 185455.28 0.293406E+09
April 0.253579E+11 0.103851E+10 0.117692E+10 0.00 0.00 0.00 0.00 3067458.74 0.203885E+09
May 0.262123E+11 0.101289E+10 0.121917E+10 0.00 0.00 0.00 0.00 1285682.52 0.194057E+09
June 0.254132E+11 0.966336E+09 0.118076E+10 0.00 0.00 0.00 0.00 7411763.93 0.131083E+09
July 0.261570E+11 0.100337E+10 0.121533E+10 0.00 0.00 0.00 0.00 19363894.31 95691158.80
August 0.262677E+11 0.104741E+10 0.122063E+10 0.00 0.00 0.00 0.00 19161531.83 94966327.28
September 0.253456E+11 0.109359E+10 0.117729E+10 0.00 0.00 0.00 0.00 10475580.58 0.125010E+09
October 0.261693E+11 0.116826E+10 0.121734E+10 0.00 0.00 0.00 0.00 17661235.04 0.135863E+09
November 0.253025E+11 0.114805E+10 0.118021E+10 0.00 0.00 0.00 0.00 805918.89 0.248681E+09
December 0.261570E+11 0.119218E+10 0.121533E+10 0.00 0.00 0.00 0.00 718981.11 0.284104E+09
                   
Annual Sum or Average 0.308468E+12 0.130667E+11 0.143405E+11 0.00 0.00 0.00 0.00 82229266.89 0.235279E+10
Minimum of Months 0.236489E+11 0.966336E+09 0.109956E+10 0.00 0.00 0.00 0.00 185455.28 94966327.28
Maximum of Months 0.262800E+11 0.120040E+10 0.122063E+10 0.00 0.00 0.00 0.00 19363894.31 0.293669E+09



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.790292E+10 0.126520E+11 0.00 0.00 0.00 0.00 5955374.61 0.887042E+09
February 0.702046E+11 0.710893E+10 0.114244E+11 0.00 0.00 0.00 0.00 805625.99 0.772383E+09
March 0.780153E+11 0.788233E+10 0.126786E+11 0.00 0.00 0.00 0.00 1028980.09 0.902136E+09
April 0.752779E+11 0.753869E+10 0.122282E+11 0.00 0.00 0.00 0.00 7108884.35 0.650314E+09
May 0.778146E+11 0.776795E+10 0.126672E+11 0.00 0.00 0.00 0.00 1772216.00 0.635437E+09
June 0.754422E+11 0.751622E+10 0.122682E+11 0.00 0.00 0.00 0.00 10648582.42 0.446569E+09
July 0.776503E+11 0.772805E+10 0.126273E+11 0.00 0.00 0.00 0.00 35119812.42 0.338688E+09
August 0.779788E+11 0.780580E+10 0.126824E+11 0.00 0.00 0.00 0.00 38761235.29 0.331431E+09
September 0.752414E+11 0.759112E+10 0.122320E+11 0.00 0.00 0.00 0.00 26871127.15 0.417339E+09
October 0.776868E+11 0.788027E+10 0.126482E+11 0.00 0.00 0.00 0.00 51498317.47 0.443467E+09
November 0.751137E+11 0.764821E+10 0.122624E+11 0.00 0.00 0.00 0.00 3934035.88 0.762423E+09
December 0.776503E+11 0.787598E+10 0.126273E+11 0.00 0.00 0.00 0.00 4340127.10 0.858709E+09
                   
Annual Sum or Average 0.915726E+12 0.922465E+11 0.148998E+12 0.00 0.00 0.00 0.00 0.187844E+09 0.744594E+10
Minimum of Months 0.702046E+11 0.710893E+10 0.114244E+11 0.00 0.00 0.00 0.00 805625.99 0.331431E+09
Maximum of Months 0.780153E+11 0.790292E+10 0.126824E+11 0.00 0.00 0.00 0.00 51498317.47 0.902136E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 455348.79 72191001.20
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 80037.81 63236520.55
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 69012.88 75413618.47
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 402291.84 52582477.79
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 31769.56 51477158.83
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 468857.45 33342025.78
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 2370099.65 22037876.61
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 2789118.34 20581241.49
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 2809437.15 29464497.47
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 4917491.74 30178859.42
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 358684.15 60547569.89
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 395744.37 68992673.73
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 15147893.74 0.580046E+09
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 31769.56 20581241.49
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 4917491.74 75413618.47



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 547041.43 70708380.95
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 97397.87 62384639.95
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 94760.67 75134186.91
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 371887.62 54997072.52
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 20430.97 55019507.57
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 301195.51 40214758.44
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 1964808.44 30793940.37
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 2284286.38 28449806.69
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 2710794.75 34149245.38
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 4752151.93 33583073.02
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 435016.84 60067194.98
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 552736.14 67736284.51
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 14132508.55 0.613238E+09
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 20430.97 28449806.69
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 4752151.93 75134186.91



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 65789991.58 0.217935E+09 0.00 0.00 0.00 0.00 0.00 31580795.33
February 0.00 59414784.75 0.196843E+09 0.00 0.00 0.00 0.00 0.00 27971920.06
March 0.00 65267117.48 0.217824E+09 0.00 0.00 0.00 0.00 0.00 32257261.23
April 0.00 63743496.62 0.210923E+09 0.00 0.00 0.00 0.00 263.50 25491256.43
May 0.00 65528554.53 0.217879E+09 0.00 0.00 0.00 0.00 0.00 25556245.99
June 0.00 63237765.93 0.210812E+09 0.00 0.00 0.00 0.00 0.00 20039784.72
July 0.00 66042856.93 0.217991E+09 0.00 0.00 0.00 0.00 20210.45 16687007.22
August 0.00 65267117.48 0.217824E+09 0.00 0.00 0.00 0.00 13568.19 16169444.99
September 0.00 63760640.03 0.210923E+09 0.00 0.00 0.00 0.00 296106.14 18630544.43
October 0.00 65781419.88 0.217935E+09 0.00 0.00 0.00 0.00 507401.22 18825103.26
November 0.00 63490631.27 0.210867E+09 0.00 0.00 0.00 0.00 203.15 27963955.60
December 0.00 66051428.64 0.217991E+09 0.00 0.00 0.00 0.00 0.00 30735727.03
                   
Annual Sum or Average 0.00 0.773376E+09 0.256575E+10 0.00 0.00 0.00 0.00 837752.65 0.291909E+09
Minimum of Months 0.00 59414784.75 0.196843E+09 0.00 0.00 0.00 0.00 0.00 16169444.99
Maximum of Months 0.00 66051428.64 0.217991E+09 0.00 0.00 0.00 0.00 507401.22 32257261.23



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 65807981.74 0.217995E+09 0.00 0.00 0.00 0.00 197442.55 19636862.29
February 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 37039.66 17284713.57
March 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 42354.24 20783910.84
April 0.293479E+09 63760927.16 0.210981E+09 0.00 0.00 0.00 0.00 141698.69 14546681.98
May 0.303504E+09 65546473.20 0.217939E+09 0.00 0.00 0.00 0.00 14312.84 14549679.35
June 0.293842E+09 63255058.18 0.210869E+09 0.00 0.00 0.00 0.00 110150.29 10163206.41
July 0.303141E+09 66060916.23 0.218051E+09 0.00 0.00 0.00 0.00 601074.12 7399477.14
August 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 725920.96 6822287.91
September 0.293479E+09 63778075.26 0.210981E+09 0.00 0.00 0.00 0.00 787862.12 8690753.84
October 0.303322E+09 65799407.69 0.217995E+09 0.00 0.00 0.00 0.00 1427323.48 8911008.77
November 0.293661E+09 63507992.67 0.210925E+09 0.00 0.00 0.00 0.00 172161.80 16402645.89
December 0.303141E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 216037.53 18699467.16
                   
Annual Sum or Average 0.357224E+10 0.773587E+09 0.256645E+10 0.00 0.00 0.00 0.00 4473378.26 0.163891E+09
Minimum of Months 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 14312.84 6822287.91
Maximum of Months 0.303685E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 1427323.48 20783910.84



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 441872.28 72598459.91
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 77703.64 63344864.80
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 64521.64 75788003.76
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 381696.85 52864454.52
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 30387.94 51772266.31
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 435532.74 33438972.62
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 2337107.44 22222537.37
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 2731183.36 20734553.43
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 2797747.05 29442389.85
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 4913326.84 30293529.29
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 352141.16 60745584.17
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 389048.40 69275788.17
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 14952269.35 0.582521E+09
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 30387.94 20734553.43
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 4913326.84 75788003.76



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 502323.29 70857426.67
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 69604.36 62243999.82
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 64020.81 75275730.42
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 287004.04 54378475.51
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 18449.39 54349814.87
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 258657.24 38319026.37
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 1885560.74 29135124.90
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 2155070.58 27247670.97
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 2658613.10 32965879.45
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 4573911.55 33256257.00
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 399720.89 59680117.09
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 466442.58 67749152.26
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 13339378.55 0.605459E+09
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 18449.39 27247670.97
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 4573911.55 75275730.42



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.120431E+10 0.00 0.00 0.00 0.00 0.00 922153.63 88128952.20
February 0.348285E+10 0.108739E+10 0.00 0.00 0.00 0.00 0.00 143900.83 77173454.58
March 0.387034E+10 0.120803E+10 0.00 0.00 0.00 0.00 0.00 215100.44 90675285.98
April 0.373454E+10 0.116348E+10 0.00 0.00 0.00 0.00 0.00 918571.22 65278578.79
May 0.386038E+10 0.120640E+10 0.00 0.00 0.00 0.00 0.00 160809.70 64506249.55
June 0.374269E+10 0.116882E+10 0.00 0.00 0.00 0.00 0.00 848905.08 44909250.52
July 0.385223E+10 0.120107E+10 0.00 0.00 0.00 0.00 0.00 3094785.23 34329104.05
August 0.386853E+10 0.120849E+10 0.00 0.00 0.00 0.00 0.00 3466250.85 33362948.41
September 0.373273E+10 0.116395E+10 0.00 0.00 0.00 0.00 0.00 3087047.99 41663030.16
October 0.385404E+10 0.120385E+10 0.00 0.00 0.00 0.00 0.00 5830342.43 44376007.91
November 0.372639E+10 0.116789E+10 0.00 0.00 0.00 0.00 0.00 656530.92 76214611.30
December 0.385223E+10 0.120107E+10 0.00 0.00 0.00 0.00 0.00 804844.31 85716232.54
                   
Annual Sum or Average 0.454292E+11 0.141847E+11 0.00 0.00 0.00 0.00 0.00 20149242.62 0.746334E+09
Minimum of Months 0.348285E+10 0.108739E+10 0.00 0.00 0.00 0.00 0.00 143900.83 33362948.41
Maximum of Months 0.387034E+10 0.120849E+10 0.00 0.00 0.00 0.00 0.00 5830342.43 90675285.98



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 433149.58 72334862.73
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 77206.34 63325211.48
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 63375.20 75606926.31
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 375005.42 52977982.64
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 27108.54 51948563.93
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 422271.73 33765211.36
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 2259785.98 22407736.05
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 2658388.92 20902471.25
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 2762257.11 29807423.86
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 4827211.84 30427949.39
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 345201.02 60741836.47
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 378996.80 69105420.92
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 14629958.48 0.583352E+09
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 27108.54 20902471.25
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 4827211.84 75606926.31



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 541516.39 70565797.47
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 101251.51 62352215.11
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 80882.40 75439970.52
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 332290.61 55991351.03
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 17244.54 56074115.15
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 267992.13 41747422.17
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 1872793.48 32436633.65
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 2171413.17 29743320.47
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 2676298.54 34844667.47
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 4701594.32 33677757.11
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 438239.18 60011919.17
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 573848.95 67472875.59
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 13775365.21 0.620358E+09
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 17244.54 29743320.47
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 4701594.32 75439970.52



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 65807981.74 0.217995E+09 0.00 0.00 0.00 0.00 205351.45 37664272.90
February 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 37912.77 32964616.93
March 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 30068.48 39186716.62
April 0.293479E+09 63760927.16 0.210981E+09 0.00 0.00 0.00 0.00 189165.79 27159669.85
May 0.303504E+09 65546473.20 0.217939E+09 0.00 0.00 0.00 0.00 14140.25 26437132.82
June 0.293842E+09 63255058.18 0.210869E+09 0.00 0.00 0.00 0.00 224430.89 17089171.07
July 0.303141E+09 66060916.23 0.218051E+09 0.00 0.00 0.00 0.00 1171626.79 11369344.24
August 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 1363358.14 10651866.71
September 0.293479E+09 63778075.26 0.210981E+09 0.00 0.00 0.00 0.00 1410375.07 15239628.01
October 0.303322E+09 65799407.69 0.217995E+09 0.00 0.00 0.00 0.00 2451338.60 15707401.78
November 0.293661E+09 63507992.67 0.210925E+09 0.00 0.00 0.00 0.00 165748.04 31554720.01
December 0.303141E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 186753.55 35998250.77
                   
Annual Sum or Average 0.357224E+10 0.773587E+09 0.256645E+10 0.00 0.00 0.00 0.00 7450269.83 0.301023E+09
Minimum of Months 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 14140.25 10651866.71
Maximum of Months 0.303685E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 2451338.60 39186716.62



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.253144E+10 0.149358E+11 0.00 0.00 0.00 0.00 2108185.28 0.190638E+09
February 0.415303E+11 0.224276E+10 0.134904E+11 0.00 0.00 0.00 0.00 415965.39 0.168836E+09
March 0.461508E+11 0.245427E+10 0.149358E+11 0.00 0.00 0.00 0.00 525244.36 0.200884E+09
April 0.445315E+11 0.228981E+10 0.144540E+11 0.00 0.00 0.00 0.00 1891703.57 0.145457E+09
May 0.460320E+11 0.230079E+10 0.149358E+11 0.00 0.00 0.00 0.00 446152.85 0.144802E+09
June 0.446286E+11 0.220577E+10 0.144540E+11 0.00 0.00 0.00 0.00 2254031.89 0.102427E+09
July 0.459349E+11 0.228247E+10 0.149358E+11 0.00 0.00 0.00 0.00 8038565.62 76837569.86
August 0.461292E+11 0.234263E+10 0.149358E+11 0.00 0.00 0.00 0.00 9896082.87 73454814.74
September 0.445099E+11 0.235154E+10 0.144540E+11 0.00 0.00 0.00 0.00 7180817.60 90330092.32
October 0.459565E+11 0.249998E+10 0.149358E+11 0.00 0.00 0.00 0.00 14410482.85 94163019.42
November 0.444343E+11 0.243818E+10 0.144540E+11 0.00 0.00 0.00 0.00 1729523.79 0.162763E+09
December 0.459349E+11 0.252984E+10 0.149358E+11 0.00 0.00 0.00 0.00 2259797.18 0.183285E+09
                   
Annual Sum or Average 0.541708E+12 0.284695E+11 0.175857E+12 0.00 0.00 0.00 0.00 51156553.24 0.163388E+10
Minimum of Months 0.415303E+11 0.220577E+10 0.134904E+11 0.00 0.00 0.00 0.00 415965.39 73454814.74
Maximum of Months 0.461508E+11 0.253144E+10 0.149358E+11 0.00 0.00 0.00 0.00 14410482.85 0.200884E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.253144E+10 0.149358E+11 0.00 0.00 0.00 0.00 1778278.20 0.196737E+09
February 0.415303E+11 0.224276E+10 0.134904E+11 0.00 0.00 0.00 0.00 342094.85 0.174586E+09
March 0.461508E+11 0.245427E+10 0.149358E+11 0.00 0.00 0.00 0.00 374700.34 0.207447E+09
April 0.445315E+11 0.228981E+10 0.144540E+11 0.00 0.00 0.00 0.00 1489119.71 0.150767E+09
May 0.460320E+11 0.230079E+10 0.149358E+11 0.00 0.00 0.00 0.00 283710.74 0.150471E+09
June 0.446286E+11 0.220577E+10 0.144540E+11 0.00 0.00 0.00 0.00 1637412.72 0.106853E+09
July 0.459349E+11 0.228247E+10 0.149358E+11 0.00 0.00 0.00 0.00 6817536.75 80476966.11
August 0.461292E+11 0.234263E+10 0.149358E+11 0.00 0.00 0.00 0.00 8456773.84 76716597.67
September 0.445099E+11 0.235154E+10 0.144540E+11 0.00 0.00 0.00 0.00 6498689.79 94382584.55
October 0.459565E+11 0.249998E+10 0.149358E+11 0.00 0.00 0.00 0.00 13431608.75 98081088.67
November 0.444343E+11 0.243818E+10 0.144540E+11 0.00 0.00 0.00 0.00 1480124.18 0.168242E+09
December 0.459349E+11 0.252984E+10 0.149358E+11 0.00 0.00 0.00 0.00 1879194.28 0.189037E+09
                   
Annual Sum or Average 0.541708E+12 0.284695E+11 0.175857E+12 0.00 0.00 0.00 0.00 44469244.15 0.169380E+10
Minimum of Months 0.415303E+11 0.220577E+10 0.134904E+11 0.00 0.00 0.00 0.00 283710.74 76716597.67
Maximum of Months 0.461508E+11 0.253144E+10 0.149358E+11 0.00 0.00 0.00 0.00 13431608.75 0.207447E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.113250E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 271311.18 0.201593E+09
February 0.369574E+10 0.102255E+10 0.293798E+11 0.275852E+11 0.00 0.00 0.00 35997.68 0.179172E+09
March 0.410691E+10 0.113599E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.210823E+09
April 0.396281E+10 0.109410E+10 0.314783E+11 0.295556E+11 0.00 0.00 0.00 273328.10 0.155884E+09
May 0.409635E+10 0.113446E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.155808E+09
June 0.397146E+10 0.109912E+10 0.314783E+11 0.295556E+11 0.00 0.00 0.00 19541.73 0.112679E+09
July 0.408770E+10 0.112945E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 1683557.90 85729445.58
August 0.410499E+10 0.113643E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 1906198.09 81748649.00
September 0.396089E+10 0.109454E+10 0.314783E+11 0.295556E+11 0.00 0.00 0.00 3941429.69 0.102291E+09
October 0.408962E+10 0.113207E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 7501634.66 0.104363E+09
November 0.395417E+10 0.109825E+10 0.314783E+11 0.295556E+11 0.00 0.00 0.00 335289.52 0.173884E+09
December 0.408770E+10 0.112945E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 202932.60 0.194113E+09
                   
Annual Sum or Average 0.482060E+11 0.133389E+11 0.382987E+12 0.359593E+12 0.00 0.00 0.00 16171221.14 0.175809E+10
Minimum of Months 0.369574E+10 0.102255E+10 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 81748649.00
Maximum of Months 0.410691E+10 0.113643E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 7501634.66 0.210823E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.127458E+10 0.00 0.00 0.00 0.00 0.00 472847.37 0.173069E+09
February 0.368610E+10 0.115083E+10 0.00 0.00 0.00 0.00 0.00 65316.06 0.153737E+09
March 0.409620E+10 0.127851E+10 0.00 0.00 0.00 0.00 0.00 13959.01 0.180125E+09
April 0.395248E+10 0.123137E+10 0.00 0.00 0.00 0.00 0.00 335742.25 0.138557E+09
May 0.408566E+10 0.127679E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.138891E+09
June 0.396110E+10 0.123701E+10 0.00 0.00 0.00 0.00 0.00 18686.34 0.104406E+09
July 0.407704E+10 0.127114E+10 0.00 0.00 0.00 0.00 0.00 1638909.23 82354483.14
August 0.409429E+10 0.127900E+10 0.00 0.00 0.00 0.00 0.00 1853862.80 78648220.89
September 0.395056E+10 0.123186E+10 0.00 0.00 0.00 0.00 0.00 3897477.84 95809196.98
October 0.407896E+10 0.127409E+10 0.00 0.00 0.00 0.00 0.00 7372387.30 96649494.98
November 0.394385E+10 0.123603E+10 0.00 0.00 0.00 0.00 0.00 354309.50 0.153225E+09
December 0.407704E+10 0.127114E+10 0.00 0.00 0.00 0.00 0.00 313167.40 0.168829E+09
                   
Annual Sum or Average 0.480803E+11 0.150123E+11 0.00 0.00 0.00 0.00 0.00 16336665.10 0.156430E+10
Minimum of Months 0.368610E+10 0.115083E+10 0.00 0.00 0.00 0.00 0.00 0.00 78648220.89
Maximum of Months 0.409620E+10 0.127900E+10 0.00 0.00 0.00 0.00 0.00 7372387.30 0.180125E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 10053.14 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 10053.14 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 10053.14 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 10053.14 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 10053.14 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 10053.14 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 10053.14 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 10053.14 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 10053.14 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 10053.14 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 10053.14 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 10053.14 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   10053.14   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   10053.14   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 512.31 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 10.34 14-JAN-11:00 112.90 08-JAN-07:00
February 1169.53 01-FEB-00:10 512.31 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 10.28 01-FEB-12:00 92.29 04-FEB-06:00
March 1169.53 01-MAR-00:10 512.31 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 95.77 08-MAR-02:00
April 1169.53 01-APR-00:10 512.31 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 15.38 26-APR-13:00 76.90 01-APR-06:00
May 1169.53 01-MAY-00:10 512.31 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 73.42 19-MAY-05:00
June 1169.53 01-JUN-00:10 512.31 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 10.10 29-JUN-11:00 57.20 12-JUN-21:00
July 1169.53 01-JUL-00:10 512.31 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 23.24 19-JUL-11:00 51.04 06-JUL-01:00
August 1169.53 01-AUG-00:10 512.31 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 20.51 14-AUG-11:00 46.83 28-AUG-03:00
September 1169.53 01-SEP-00:10 512.31 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 59.71 29-SEP-11:00 60.53 20-SEP-03:00
October 1169.53 01-OCT-23:10 512.31 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 64.60 16-OCT-11:00 72.58 30-OCT-03:00
November 1169.53 01-NOV-00:10 512.31 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 15.38 19-NOV-13:00 89.83 29-NOV-23:00
December 1169.53 01-DEC-00:10 512.31 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 10.36 16-DEC-13:00 93.68 03-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   512.31   685.60   0.00 0.00 0.00 0.00 0.00   46.83  
Maximum of Months 1169.53   512.31   685.60   0.00 0.00 0.00 0.00 64.60   112.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 593.26 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 7.93 18-JAN-13:00 45.86 08-JAN-07:00
February 1354.32 01-FEB-00:10 593.26 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 7.93 01-FEB-12:00 37.79 04-FEB-06:00
March 1354.32 01-MAR-00:10 593.26 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 4.10 11-MAR-11:50 39.45 08-MAR-02:00
April 1354.32 01-APR-00:10 593.26 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 9.68 26-APR-13:00 31.33 01-APR-06:00
May 1354.32 01-MAY-00:10 593.26 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 3.92 03-MAY-12:00 30.96 19-MAY-05:00
June 1354.32 01-JUN-00:10 593.26 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 6.07 29-JUN-11:00 24.33 13-JUN-04:40
July 1354.32 01-JUL-00:10 593.26 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 11.78 19-JUL-11:00 21.06 06-JUL-01:00
August 1354.32 01-AUG-00:10 593.26 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 11.74 14-AUG-11:00 18.84 24-AUG-02:00
September 1354.32 01-SEP-00:10 593.26 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 26.23 29-SEP-11:00 24.87 20-SEP-03:00
October 1354.32 01-OCT-23:10 593.26 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 27.58 16-OCT-11:00 29.39 27-OCT-04:30
November 1354.32 01-NOV-00:10 593.26 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 8.73 19-NOV-13:00 35.41 29-NOV-23:00
December 1354.32 01-DEC-00:10 593.26 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 7.61 16-DEC-13:00 37.79 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   593.26   793.93   0.00 0.00 0.00 0.00 3.92   18.84  
Maximum of Months 1354.32   593.26   793.93   0.00 0.00 0.00 0.00 27.58   45.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 684.18 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 11.21 13-JAN-14:00 115.40 08-JAN-07:00
February 286.42 01-FEB-00:10 684.18 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 9.38 01-FEB-12:00 95.52 04-FEB-06:00
March 286.42 01-MAR-00:10 684.18 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 0.95 11-MAR-11:50 98.86 08-MAR-02:00
April 286.42 01-APR-00:10 684.18 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 14.03 26-APR-13:00 80.85 01-APR-06:00
May 286.42 01-MAY-00:10 684.18 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 80.07 27-MAY-03:00
June 286.42 01-JUN-00:10 684.18 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 4.70 29-JUN-11:00 64.65 13-JUN-04:00
July 286.42 01-JUL-00:10 684.18 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 18.66 19-JUL-12:00 53.97 06-JUL-01:00
August 286.42 01-AUG-00:10 684.18 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 18.70 18-AUG-12:00 48.85 31-AUG-04:00
September 286.42 01-SEP-00:10 684.18 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 54.47 29-SEP-11:00 64.20 20-SEP-04:00
October 286.42 01-OCT-23:10 684.18 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 58.94 16-OCT-11:00 74.93 30-OCT-04:00
November 286.42 01-NOV-00:10 684.18 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 14.03 19-NOV-13:00 85.56 24-NOV-01:00
December 286.42 01-DEC-00:10 684.18 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 10.78 16-DEC-13:00 96.19 03-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   684.18   839.45   0.00 0.00 0.00 0.00 0.00   48.85  
Maximum of Months 286.42   684.18   839.45   0.00 0.00 0.00 0.00 58.94   115.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 188.71 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 13.19 13-JAN-14:00 59.42 08-JAN-07:00
February 220.32 01-FEB-00:10 188.71 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 12.83 01-FEB-12:00 47.59 04-FEB-06:00
March 220.32 01-MAR-00:10 188.71 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 8.07 11-MAR-11:50 49.93 08-MAR-02:00
April 220.32 01-APR-00:10 188.71 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 14.99 26-APR-13:00 40.47 01-APR-06:00
May 220.32 01-MAY-00:10 188.71 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 6.84 03-MAY-12:00 38.69 27-MAY-03:00
June 220.32 01-JUN-00:10 188.71 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 9.24 29-JUN-11:00 30.15 13-JUN-05:00
July 220.32 01-JUL-00:10 188.71 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 16.84 19-JUL-11:00 25.19 06-JUL-01:00
August 220.32 01-AUG-00:10 188.71 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 17.11 14-AUG-11:00 22.06 28-AUG-06:00
September 220.32 01-SEP-00:10 188.71 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 37.22 29-SEP-11:00 30.09 20-SEP-03:00
October 220.32 01-OCT-23:10 188.71 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 38.90 16-OCT-11:00 36.20 27-OCT-04:30
November 220.32 01-NOV-00:10 188.71 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 14.60 19-NOV-13:00 42.91 29-NOV-23:00
December 220.32 01-DEC-00:10 188.71 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 13.29 16-DEC-13:00 47.45 03-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   188.71   242.16   0.00 0.00 0.00 0.00 6.84   22.06  
Maximum of Months 220.32   188.71   242.16   0.00 0.00 0.00 0.00 38.90   59.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 400.68 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 12.88 14-JAN-11:00 161.70 08-JAN-07:00
February 907.20 01-FEB-00:10 400.68 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 12.81 01-FEB-12:00 131.10 04-FEB-06:00
March 907.20 01-MAR-00:10 400.68 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 0.00 01-MAR-00:05 139.00 08-MAR-02:00
April 907.20 01-APR-00:10 400.68 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 19.16 26-APR-13:00 116.29 01-APR-06:00
May 907.20 01-MAY-00:10 400.68 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 0.00 01-MAY-00:10 109.66 15-MAY-05:00
June 907.20 01-JUN-00:10 400.68 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 6.41 29-JUN-11:00 88.27 13-JUN-05:00
July 907.20 01-JUL-00:10 400.68 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 25.49 19-JUL-12:00 73.70 06-JUL-01:00
August 907.20 01-AUG-00:10 400.68 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 25.54 18-AUG-12:00 66.71 31-AUG-04:00
September 907.20 01-SEP-00:10 400.68 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 74.38 29-SEP-11:00 87.65 20-SEP-04:00
October 907.20 01-OCT-23:10 400.68 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 80.47 16-OCT-11:00 102.31 30-OCT-04:00
November 907.20 01-NOV-00:10 400.68 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 19.17 19-NOV-13:00 116.83 24-NOV-01:00
December 907.20 01-DEC-00:10 400.68 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 12.91 16-DEC-13:00 131.42 22-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   400.68   4572.80   39726.58   0.00 0.00 0.00 0.00   66.71  
Maximum of Months 907.20   400.68   4572.80   39726.58   0.00 0.00 0.00 80.47   161.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1573.46 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 38.43 15-JAN-14:00 251.65 08-JAN-07:00
February 15368.40 01-FEB-00:10 1573.46 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 35.26 01-FEB-12:00 212.66 04-FEB-06:00
March 15368.40 01-MAR-00:10 1573.46 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 14.21 11-MAR-11:50 222.35 08-MAR-02:00
April 15368.40 01-APR-00:10 1573.46 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 58.73 26-APR-13:00 173.04 01-APR-06:00
May 15368.40 01-MAY-00:10 1573.46 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 29.32 03-MAY-12:00 171.02 19-MAY-05:00
June 15368.40 01-JUN-00:10 1573.46 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 45.66 29-JUN-11:00 135.27 13-JUN-05:00
July 15368.40 01-JUL-00:10 1573.46 03-JUL-19:10 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 79.00 19-JUL-11:00 112.55 06-JUL-01:00
August 15368.40 01-AUG-00:10 1573.46 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 77.08 14-AUG-10:50 102.63 28-AUG-04:20
September 15368.40 01-SEP-00:10 1573.46 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 147.33 29-SEP-10:50 137.05 20-SEP-03:00
October 15368.40 01-OCT-23:10 1573.46 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 148.76 16-OCT-11:00 164.67 30-OCT-03:00
November 15368.40 01-NOV-00:10 1573.46 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 34.02 19-NOV-13:00 195.76 29-NOV-23:00
December 15368.40 01-DEC-00:10 1573.46 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 29.40 05-DEC-09:55 212.78 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1573.46   965.27   0.00 0.00 0.00 0.00 14.21   102.63  
Maximum of Months 15368.40   1573.46   965.27   0.00 0.00 0.00 0.00 148.76   251.65  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 7984.04 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 114.62 18-JAN-13:00 765.60 08-JAN-07:00
February 45622.98 01-FEB-00:10 7984.04 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 120.15 01-FEB-12:00 638.67 04-FEB-06:00
March 45622.98 01-MAR-00:10 7984.04 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 56.12 11-MAR-11:50 665.80 08-MAR-02:00
April 45622.98 01-APR-00:10 7984.04 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 162.18 26-APR-13:00 533.98 01-APR-06:00
May 45622.98 01-MAY-00:10 7984.04 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 68.66 03-MAY-12:00 523.40 19-MAY-05:00
June 45622.98 01-JUN-00:10 7984.04 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 110.16 29-JUN-11:00 418.96 13-JUN-05:00
July 45622.98 01-JUL-00:10 7984.04 03-JUL-19:10 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 203.15 19-JUL-11:00 352.70 06-JUL-01:00
August 45622.98 01-AUG-00:10 7984.04 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 200.81 14-AUG-11:00 319.03 28-AUG-05:00
September 45622.98 01-SEP-00:10 7984.04 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 428.94 29-SEP-11:00 420.36 20-SEP-03:00
October 45622.98 01-OCT-23:10 7984.04 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 447.33 16-OCT-11:00 498.28 27-OCT-04:40
November 45622.98 01-NOV-00:10 7984.04 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 127.96 19-NOV-13:00 590.32 29-NOV-23:00
December 45622.98 01-DEC-00:10 7984.04 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 104.45 16-DEC-13:00 636.84 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   7984.04   10029.21   0.00 0.00 0.00 0.00 56.12   319.03  
Maximum of Months 45622.98   7984.04   10029.21   0.00 0.00 0.00 0.00 447.33   765.60  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 13.83 14-JAN-10:51 66.02 08-JAN-07:00
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 8.56 01-FEB-09:51 51.93 04-FEB-06:00
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 8.07 11-MAR-10:50 55.55 08-MAR-02:00
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 10.86 30-APR-09:52 45.11 01-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 4.79 03-MAY-09:52 42.01 15-MAY-02:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 8.06 29-JUN-09:50 32.13 13-JUN-05:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 16.93 19-JUL-09:50 25.46 06-JUL-01:00
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 16.72 15-AUG-09:51 25.72 28-AUG-07:10
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 39.21 29-SEP-09:51 31.90 20-SEP-04:00
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 39.30 16-OCT-11:00 38.63 30-OCT-04:00
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 14.52 19-NOV-10:00 45.32 24-NOV-01:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 14.54 05-DEC-10:00 52.06 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 4.79   25.46  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 39.30   66.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 14.32 14-JAN-10:51 66.02 08-JAN-07:00
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 9.95 01-FEB-12:00 51.93 04-FEB-06:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 8.21 11-MAR-10:52 55.55 08-MAR-04:00
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 10.91 30-APR-09:52 45.11 01-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 4.79 03-MAY-09:52 42.01 15-MAY-02:00
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 8.06 29-JUN-09:50 32.12 13-JUN-04:50
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 16.93 19-JUL-09:50 29.28 07-JUL-21:00
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 16.69 15-AUG-09:51 28.53 26-AUG-18:00
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 39.42 29-SEP-09:51 31.90 20-SEP-03:50
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 39.42 16-OCT-09:51 38.63 30-OCT-04:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 14.52 19-NOV-09:58 45.32 24-NOV-01:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 14.54 05-DEC-10:00 52.06 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 4.79   28.53  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 39.42   66.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 59.53 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 22.83 08-JAN-07:00
February 0.00 01-FEB-00:10 59.53 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 19.12 04-FEB-06:00
March 0.00 01-MAR-00:10 59.53 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 19.85 08-MAR-02:00
April 0.00 01-APR-00:10 59.53 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 0.24 26-APR-13:00 15.66 15-APR-22:00
May 0.00 01-MAY-00:10 59.53 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 15.85 27-MAY-03:00
June 0.00 01-JUN-00:10 59.53 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:10 13.26 13-JUN-04:00
July 0.00 01-JUL-00:10 59.53 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 1.07 19-JUL-12:00 11.83 06-JUL-01:00
August 0.00 01-AUG-00:10 59.53 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 1.07 18-AUG-12:00 11.02 24-AUG-02:00
September 0.00 01-SEP-00:10 59.53 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 7.49 29-SEP-11:00 13.65 20-SEP-03:00
October 0.00 01-OCT-00:10 59.53 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 8.28 16-OCT-11:00 15.69 30-OCT-03:00
November 0.00 01-NOV-00:10 59.53 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.24 19-NOV-13:00 17.61 24-NOV-01:00
December 0.00 01-DEC-00:10 59.53 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 19.52 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   59.53   232.19   0.00 0.00 0.00 0.00 0.00   11.02  
Maximum of Months 0.00   59.53   232.19   0.00 0.00 0.00 0.00 8.28   22.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 59.54 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 4.10 13-JAN-14:00 18.43 08-JAN-07:00
February 180.00 01-FEB-00:10 59.54 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 3.10 01-FEB-12:00 14.49 04-FEB-06:00
March 180.00 01-MAR-00:10 59.54 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 2.31 11-MAR-10:52 15.50 08-MAR-04:00
April 180.00 01-APR-00:10 59.54 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 3.95 26-APR-13:00 12.59 01-APR-06:00
May 180.00 01-MAY-00:10 59.54 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 1.40 03-MAY-09:52 11.78 14-MAY-05:00
June 180.00 01-JUN-00:10 59.54 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 2.25 29-JUN-09:50 8.97 13-JUN-04:40
July 180.00 01-JUL-00:10 59.54 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 4.72 19-JUL-09:50 7.76 07-JUL-21:00
August 180.00 01-AUG-00:10 59.54 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 4.72 15-AUG-09:51 7.36 21-AUG-20:10
September 180.00 01-SEP-00:10 59.54 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 11.07 29-SEP-09:51 8.90 20-SEP-04:00
October 180.00 01-OCT-00:10 59.54 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 11.08 16-OCT-09:51 10.78 30-OCT-04:00
November 180.00 01-NOV-00:10 59.54 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 4.05 19-NOV-09:58 12.65 24-NOV-01:00
December 180.00 01-DEC-00:10 59.54 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 4.06 05-DEC-10:00 14.53 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 1.40   7.36  
Maximum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 11.08   18.43  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 13.60 14-JAN-10:51 66.02 08-JAN-07:00
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 8.56 01-FEB-09:54 51.93 04-FEB-06:00
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 8.07 11-MAR-10:50 55.55 08-MAR-04:00
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 10.78 26-APR-13:00 45.11 01-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 4.18 03-MAY-09:52 42.01 15-MAY-05:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 8.06 29-JUN-09:50 32.13 13-JUN-05:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 16.93 19-JUL-09:50 25.46 06-JUL-01:00
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 16.44 15-AUG-09:50 27.97 28-AUG-07:10
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 39.19 29-SEP-09:50 31.90 20-SEP-03:40
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 39.30 16-OCT-11:00 38.63 30-OCT-04:00
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 14.52 19-NOV-10:00 45.32 24-NOV-01:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 14.54 05-DEC-09:55 52.06 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 4.18   25.46  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 39.30   66.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 14.07 14-JAN-10:51 66.01 08-JAN-07:00
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 8.56 01-FEB-10:00 51.93 04-FEB-06:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 8.07 11-MAR-10:50 55.55 08-MAR-02:00
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 10.78 26-APR-13:00 45.11 01-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 4.13 03-MAY-09:52 42.01 15-MAY-02:00
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 8.06 29-JUN-09:50 32.12 13-JUN-05:00
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 16.93 19-JUL-09:50 26.53 07-JUL-21:00
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 16.44 15-AUG-09:50 27.99 28-AUG-07:10
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 39.19 29-SEP-09:50 31.90 20-SEP-03:50
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 39.29 16-OCT-11:00 38.63 30-OCT-04:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 14.51 19-NOV-10:00 45.32 24-NOV-01:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 14.53 05-DEC-10:00 52.06 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 4.13   26.53  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 39.29   66.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1160.00 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 15.06 13-JAN-14:00 80.28 08-JAN-07:00
February 2263.36 01-FEB-00:10 1160.00 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 14.95 01-FEB-12:00 66.06 04-FEB-06:00
March 2263.36 01-MAR-00:10 1160.00 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 8.17 11-MAR-11:50 67.89 08-MAR-02:00
April 2263.36 01-APR-00:10 1160.00 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 18.02 26-APR-13:00 54.13 01-APR-06:00
May 2263.36 01-MAY-00:10 1160.00 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 6.77 03-MAY-12:00 53.63 27-MAY-03:00
June 2263.36 01-JUN-00:10 1160.00 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 10.10 29-JUN-11:00 41.89 13-JUN-05:00
July 2263.36 01-JUL-00:10 1160.00 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 20.31 19-JUL-11:00 36.26 06-JUL-01:00
August 2263.36 01-AUG-00:10 1160.00 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 19.97 14-AUG-11:00 32.43 24-AUG-02:00
September 2263.36 01-SEP-00:10 1160.00 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 46.94 29-SEP-11:00 42.73 20-SEP-03:00
October 2263.36 01-OCT-23:10 1160.00 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 49.00 16-OCT-11:00 51.15 30-OCT-03:00
November 2263.36 01-NOV-00:10 1160.00 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 16.74 19-NOV-13:00 59.24 29-NOV-23:00
December 2263.36 01-DEC-00:10 1160.00 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 15.20 16-DEC-13:00 65.76 23-DEC-04:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1160.00   0.00 0.00 0.00 0.00 0.00 6.77   32.43  
Maximum of Months 2263.36   1160.00   0.00 0.00 0.00 0.00 0.00 49.00   80.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 13.68 14-JAN-10:51 66.23 08-JAN-07:00
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 8.38 01-FEB-09:51 52.14 04-FEB-06:00
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 7.89 11-MAR-10:50 55.76 08-MAR-04:00
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 10.62 30-APR-09:52 45.31 01-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 4.52 03-MAY-09:52 42.21 15-MAY-05:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 7.88 29-JUN-09:50 32.32 13-JUN-04:40
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 16.75 19-JUL-09:50 25.65 06-JUL-01:00
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 16.48 15-AUG-09:51 25.21 28-AUG-07:00
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 39.03 29-SEP-09:50 32.10 20-SEP-04:00
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 39.13 16-OCT-11:00 38.83 30-OCT-04:00
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 14.34 19-NOV-10:00 45.52 24-NOV-01:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 14.37 05-DEC-10:00 52.27 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 4.52   25.21  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 39.13   66.23  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 14.19 14-JAN-10:51 66.22 08-JAN-07:00
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 9.93 01-FEB-12:00 52.13 04-FEB-06:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 7.98 11-MAR-10:52 55.75 08-MAR-04:00
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 10.65 30-APR-09:52 45.31 01-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 4.47 03-MAY-09:52 42.20 15-MAY-05:00
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 7.88 29-JUN-09:50 33.08 02-JUN-20:00
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 16.75 19-JUL-09:50 31.63 10-JUL-18:01
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 16.42 15-AUG-09:51 30.77 26-AUG-18:00
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 39.17 29-SEP-09:51 32.09 20-SEP-04:00
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 39.21 16-OCT-09:51 38.82 30-OCT-04:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 14.34 19-NOV-10:00 45.52 24-NOV-01:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 14.37 05-DEC-10:00 52.26 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 4.47   30.77  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 39.21   66.22  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 59.54 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 6.57 14-JAN-10:51 33.88 08-JAN-07:00
February 180.00 01-FEB-00:10 59.54 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 4.29 01-FEB-09:51 26.67 04-FEB-06:00
March 180.00 01-MAR-00:10 59.54 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 4.04 11-MAR-10:50 28.53 08-MAR-04:00
April 180.00 01-APR-00:10 59.54 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 5.43 26-APR-13:00 23.18 01-APR-06:00
May 180.00 01-MAY-00:10 59.54 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 2.29 03-MAY-09:52 21.59 15-MAY-05:00
June 180.00 01-JUN-00:10 59.54 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 4.03 29-JUN-09:50 16.54 13-JUN-05:00
July 180.00 01-JUL-00:10 59.54 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 8.57 19-JUL-09:50 13.12 06-JUL-01:00
August 180.00 01-AUG-00:10 59.54 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 8.41 15-AUG-09:51 13.21 28-AUG-07:00
September 180.00 01-SEP-00:10 59.54 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 19.97 29-SEP-09:50 16.42 20-SEP-03:40
October 180.00 01-OCT-00:10 59.54 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 20.02 16-OCT-11:00 19.86 30-OCT-04:00
November 180.00 01-NOV-00:10 59.54 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 6.69 19-NOV-10:30 23.38 30-NOV-02:50
December 180.00 01-DEC-00:10 59.54 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 7.35 05-DEC-10:00 26.74 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 2.29   13.12  
Maximum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 20.02   33.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2763.12 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 35.07 14-JAN-11:50 170.13 08-JAN-07:00
February 26988.77 01-FEB-00:10 2763.12 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 34.76 01-FEB-12:00 141.32 04-FEB-06:00
March 26988.77 01-MAR-00:10 2763.12 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 20.05 11-MAR-11:50 148.80 08-MAR-02:00
April 26988.77 01-APR-00:10 2763.12 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 37.91 26-APR-13:00 122.23 01-APR-06:00
May 26988.77 01-MAY-00:10 2763.12 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 17.15 03-MAY-12:00 117.72 27-MAY-03:00
June 26988.77 01-JUN-00:10 2763.12 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 26.22 29-JUN-10:50 94.65 13-JUN-05:00
July 26988.77 01-JUL-00:10 2763.12 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 47.93 19-JUL-10:50 79.48 06-JUL-01:00
August 26988.77 01-AUG-00:10 2763.12 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 48.47 14-AUG-10:50 71.04 28-AUG-04:20
September 26988.77 01-SEP-00:10 2763.12 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 103.39 29-SEP-10:50 93.42 20-SEP-03:00
October 26988.77 01-OCT-23:10 2763.12 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 110.38 16-OCT-11:00 109.54 12-OCT-05:00
November 26988.77 01-NOV-00:10 2763.12 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 38.71 19-NOV-13:00 131.36 29-NOV-23:00
December 26988.77 01-DEC-00:10 2763.12 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 33.89 19-DEC-13:00 140.61 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2763.12   6747.90   0.00 0.00 0.00 0.00 17.15   71.04  
Maximum of Months 26988.77   2763.12   6747.90   0.00 0.00 0.00 0.00 110.38   170.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2763.12 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 32.46 14-JAN-11:50 172.50 08-JAN-07:00
February 26988.77 01-FEB-00:10 2763.12 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 33.15 01-FEB-12:00 143.11 04-FEB-06:00
March 26988.77 01-MAR-00:10 2763.12 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 17.44 11-MAR-11:50 151.20 08-MAR-02:00
April 26988.77 01-APR-00:10 2763.12 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 35.72 26-APR-13:00 124.92 01-APR-06:00
May 26988.77 01-MAY-00:10 2763.12 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 15.03 03-MAY-12:00 119.50 27-MAY-03:00
June 26988.77 01-JUN-00:10 2763.12 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 24.06 29-JUN-10:50 96.47 13-JUN-05:00
July 26988.77 01-JUL-00:10 2763.12 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 45.79 19-JUL-10:50 81.07 06-JUL-01:00
August 26988.77 01-AUG-00:10 2763.12 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 46.33 14-AUG-10:50 72.49 28-AUG-03:00
September 26988.77 01-SEP-00:10 2763.12 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 101.41 29-SEP-10:50 95.08 20-SEP-03:00
October 26988.77 01-OCT-23:10 2763.12 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 108.44 16-OCT-11:00 111.27 12-OCT-05:00
November 26988.77 01-NOV-00:10 2763.12 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 36.51 19-NOV-13:00 133.49 29-NOV-23:00
December 26988.77 01-DEC-00:10 2763.12 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 31.77 19-DEC-13:00 142.49 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2763.12   6747.90   0.00 0.00 0.00 0.00 15.03   72.49  
Maximum of Months 26988.77   2763.12   6747.90   0.00 0.00 0.00 0.00 108.44   172.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1090.83 02-JAN-20:10 14604.56 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 12.53 14-JAN-11:30 165.41 08-JAN-07:00
February 2401.70 01-FEB-00:10 1090.83 01-FEB-20:10 14604.56 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 12.46 01-FEB-12:00 134.24 04-FEB-06:00
March 2401.70 01-MAR-00:10 1090.83 01-MAR-20:10 14604.56 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:05 142.31 08-MAR-02:00
April 2401.70 01-APR-00:10 1090.83 03-APR-19:10 14604.56 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 18.92 26-APR-13:00 119.12 01-APR-06:00
May 2401.70 01-MAY-00:10 1090.83 01-MAY-19:10 14604.56 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 0.00 01-MAY-00:10 112.40 15-MAY-02:00
June 2401.70 01-JUN-00:10 1090.83 01-JUN-19:10 14604.56 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 5.94 29-JUN-11:00 90.60 13-JUN-04:00
July 2401.70 01-JUL-00:10 1090.83 03-JUL-19:10 14604.56 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 25.38 19-JUL-12:00 75.75 06-JUL-01:00
August 2401.70 01-AUG-00:10 1090.83 01-AUG-19:10 14604.56 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 25.44 18-AUG-12:00 68.63 31-AUG-04:00
September 2401.70 01-SEP-00:10 1090.83 01-SEP-19:10 14604.56 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 75.20 29-SEP-11:00 89.97 20-SEP-04:00
October 2401.70 01-OCT-23:10 1090.83 02-OCT-19:10 14604.56 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 81.43 16-OCT-11:00 104.92 30-OCT-04:00
November 2401.70 01-NOV-00:10 1090.83 01-NOV-19:10 14604.56 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 18.95 19-NOV-13:00 119.71 24-NOV-01:00
December 2401.70 01-DEC-00:10 1090.83 01-DEC-20:10 14604.56 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 12.57 16-DEC-13:00 134.55 22-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1090.83   14604.56   22492.83   0.00 0.00 0.00 0.00   68.63  
Maximum of Months 2401.70   1090.83   14604.56   22492.83   0.00 0.00 0.00 81.43   165.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1227.68 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 17.11 14-JAN-10:51 143.37 08-JAN-07:00
February 2395.44 01-FEB-00:10 1227.68 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 15.39 01-FEB-12:00 121.56 04-FEB-06:00
March 2395.44 01-MAR-00:10 1227.68 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 2.97 11-MAR-10:52 124.21 08-MAR-02:00
April 2395.44 01-APR-00:10 1227.68 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 18.45 26-APR-13:00 98.93 01-APR-06:00
May 2395.44 01-MAY-00:10 1227.68 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 101.59 27-MAY-03:00
June 2395.44 01-JUN-00:10 1227.68 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 5.75 29-JUN-11:00 81.37 13-JUN-04:00
July 2395.44 01-JUL-00:10 1227.68 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 24.76 19-JUL-12:00 71.91 06-JUL-01:00
August 2395.44 01-AUG-00:10 1227.68 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 24.81 18-AUG-12:00 65.09 28-AUG-03:00
September 2395.44 01-SEP-00:10 1227.68 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 73.53 29-SEP-11:00 81.78 20-SEP-03:00
October 2395.44 01-OCT-23:10 1227.68 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 79.61 16-OCT-11:00 96.02 27-OCT-04:00
November 2395.44 01-NOV-00:10 1227.68 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 18.45 19-NOV-13:00 111.90 29-NOV-23:00
December 2395.44 01-DEC-00:10 1227.68 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 15.65 16-DEC-13:00 120.92 03-DEC-01:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1227.68   0.00 0.00 0.00 0.00 0.00 0.00   65.09  
Maximum of Months 2395.44   1227.68   0.00 0.00 0.00 0.00 0.00 79.61   143.37  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 14521.45 22-JAN-11:35 7667.93 6702.09 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
February 14135.47 01-FEB-11:35 5111.95 5585.17 7097.65 0.00 0.00 0.00 0.00 0.00 0.00
March 13588.08 12-MAR-10:35 7667.93 6702.09 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
April 13666.69 30-APR-10:35 7667.93 6702.09 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
May 13497.55 04-MAY-18:10 62621.41 62552.56 63878.88 0.00 0.00 0.00 0.00 0.00 0.00
June 13529.08 25-JUN-10:35 7667.93 6702.09 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
July 14388.30 23-JUL-10:35 7667.93 6702.09 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
August 14380.85 13-AUG-10:35 7667.93 6702.09 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
September 15083.82 30-SEP-10:35 7667.93 5585.17 7097.65 0.00 0.00 0.00 0.00 0.00 0.00
October 15512.97 15-OCT-10:35 7667.93 6702.09 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
November 15015.09 19-NOV-11:35 7667.93 6702.09 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
December 14370.16 07-DEC-19:10 62621.41 62552.56 63878.88 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 13497.55   5111.95 5585.17 7097.65 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15512.97   62621.41 62552.56 63878.88 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3314.36 14-JAN-12:40 389.84 142.31 252.59 0.00 0.00 0.00 0.00 6.88 0.00
February 2952.85 02-FEB-12:40 259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 24.59
March 2600.76 11-MAR-13:00 389.84 142.31 252.59 0.00 0.00 0.00 0.00 0.00 0.01
April 1910.62 08-APR-12:40 389.84 142.31 252.59 0.00 0.00 0.00 0.00 0.00 8.73
May 1512.72 04-MAY-12:30 259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 2.62
June 1431.73 29-JUN-18:10 6367.45 3187.73 4546.63 0.00 0.00 0.00 0.00 0.00 10.05
July 1569.53 31-JUL-12:40 259.90 142.31 252.59 0.00 0.00 0.00 0.00 20.42 0.00
August 1969.11 27-AUG-12:00 389.84 170.77 288.68 0.00 0.00 0.00 0.00 0.00 5.21
September 3398.98 30-SEP-12:00 389.84 142.31 252.59 0.00 0.00 0.00 0.00 40.21 0.00
October 3976.68 16-OCT-12:10 259.90 142.31 252.59 0.00 0.00 0.00 0.00 58.25 0.00
November 3604.24 19-NOV-12:30 389.84 170.77 288.68 0.00 0.00 0.00 0.00 12.85 0.00
December 3463.38 19-DEC-12:40 259.90 142.31 252.59 0.00 0.00 0.00 0.00 8.60 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1431.73   259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3976.68   6367.45 3187.73 4546.63 0.00 0.00 0.00 0.00 58.25 24.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1469.61 18-JAN-19:10 7373.52 3691.40 5265.02 0.00 0.00 0.00 0.00 0.00 7.89
February 1487.54 03-FEB-21:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 21.74
March 1498.28 23-MAR-18:10 7373.52 3691.40 5265.02 0.00 0.00 0.00 0.00 0.00 12.89
April 1548.14 26-APR-18:10 7373.52 3691.40 5265.02 0.00 0.00 0.00 0.00 0.00 8.54
May 1549.15 04-MAY-18:10 7373.52 3691.40 5265.02 0.00 0.00 0.00 0.00 0.00 8.21
June 1575.66 29-JUN-18:10 7373.52 3691.40 5265.02 0.00 0.00 0.00 0.00 0.00 2.88
July 1614.97 19-JUL-18:10 6320.16 3164.06 4512.87 0.00 0.00 0.00 0.00 0.00 0.78
August 1616.94 17-AUG-18:10 6320.16 3164.06 4512.87 0.00 0.00 0.00 0.00 0.00 4.87
September 1719.39 29-SEP-21:00 1203.84 527.34 752.15 0.00 0.00 0.00 0.00 1.19 0.00
October 1763.49 16-OCT-21:00 1203.84 527.34 752.15 0.00 0.00 0.00 0.00 0.00 12.24
November 1542.36 19-NOV-11:35 902.88 395.51 668.57 0.00 0.00 0.00 0.00 6.80 0.00
December 1505.26 05-DEC-21:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 15.45
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1469.61   902.88 395.51 668.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1763.49   7373.52 3691.40 5265.02 0.00 0.00 0.00 0.00 6.80 21.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 813.92 18-JAN-22:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 0.00 34.14
February 724.79 03-FEB-21:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 0.00 54.17
March 684.56 24-MAR-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 0.00 53.96
April 832.68 26-APR-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 0.00 38.90
May 953.09 04-MAY-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 0.00 33.95
June 1043.58 30-JUN-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 0.00 38.86
July 1146.97 19-JUL-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 0.00 28.97
August 1126.94 18-AUG-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 0.00 24.08
September 1269.33 29-SEP-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 2.81 0.00
October 1352.01 16-OCT-20:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 0.00 14.33
November 778.68 10-NOV-22:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 0.00 44.03
December 844.60 05-DEC-22:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 0.00 34.04
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 684.56   222.77 608.16 795.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1352.01   254.59 684.18 839.45 0.00 0.00 0.00 0.00 2.81 54.17



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 835.85 20-JAN-11:35 97.92 104.84 178.43 0.00 0.00 0.00 0.00 0.35 0.00
February 812.24 04-FEB-11:35 146.88 104.84 178.43 0.00 0.00 0.00 0.00 0.00 1.98
March 827.03 19-MAR-10:35 146.88 125.80 203.92 0.00 0.00 0.00 0.00 0.00 5.05
April 867.29 30-APR-10:35 146.88 125.80 203.92 0.00 0.00 0.00 0.00 11.67 0.00
May 874.51 04-MAY-10:35 97.92 104.84 178.43 0.00 0.00 0.00 0.00 1.15 0.00
June 903.68 25-JUN-10:35 146.88 125.80 203.92 0.00 0.00 0.00 0.00 3.54 0.00
July 941.42 23-JUL-10:35 146.88 125.80 203.92 0.00 0.00 0.00 0.00 10.26 0.00
August 934.24 19-AUG-10:35 146.88 104.84 178.43 0.00 0.00 0.00 0.00 7.58 0.00
September 981.03 30-SEP-10:35 146.88 104.84 178.43 0.00 0.00 0.00 0.00 22.24 0.00
October 971.51 15-OCT-10:35 146.88 125.80 203.92 0.00 0.00 0.00 0.00 25.37 0.00
November 868.13 19-NOV-11:35 146.88 125.80 203.92 0.00 0.00 0.00 0.00 11.93 0.00
December 840.60 19-DEC-11:35 97.92 104.84 178.43 0.00 0.00 0.00 0.00 9.28 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 812.24   97.92 104.84 178.43 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 981.03   146.88 125.80 203.92 0.00 0.00 0.00 0.00 25.37 5.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37929.76 24-JAN-21:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 46.50
February 37838.34 03-FEB-21:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 73.97
March 38062.26 23-MAR-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 66.83
April 38312.42 26-APR-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 46.31
May 38322.27 04-MAY-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 46.36
June 38344.48 30-JUN-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 53.06
July 38565.65 19-JUL-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 32.85
August 38533.52 18-AUG-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 32.87
September 38820.66 29-SEP-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 6.40 0.00
October 38754.72 16-OCT-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 19.55
November 37844.75 28-NOV-21:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 74.10
December 38065.20 05-DEC-21:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 53.30
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 37838.34   705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38820.66   705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 6.40 74.10



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12545.84 14-JAN-11:35 10245.60 192.31 711.25 0.00 0.00 0.00 0.00 25.55 0.00
February 11740.80 04-FEB-11:35 10245.60 192.31 711.25 0.00 0.00 0.00 0.00 0.00 29.73
March 11862.59 11-MAR-11:35 10245.60 192.31 711.25 0.00 0.00 0.00 0.00 11.04 0.00
April 10538.79 08-APR-10:35 10245.60 192.31 711.25 0.00 0.00 0.00 0.00 0.00 1.80
May 9857.86 04-MAY-18:10 83672.40 4536.87 6401.28 0.00 0.00 0.00 0.00 0.00 32.14
June 9828.98 29-JUN-18:10 83672.40 3775.93 6401.28 0.00 0.00 0.00 0.00 0.28 0.00
July 10414.47 30-JUL-10:35 10245.60 230.77 812.86 0.00 0.00 0.00 0.00 36.46 0.00
August 10825.91 27-AUG-10:35 10245.60 230.77 812.86 0.00 0.00 0.00 0.00 16.51 0.00
September 12598.08 30-SEP-10:35 10245.60 192.31 711.25 0.00 0.00 0.00 0.00 83.26 0.00
October 13360.74 15-OCT-10:35 10245.60 230.77 812.86 0.00 0.00 0.00 0.00 88.46 0.00
November 13148.76 19-NOV-10:53 51228.00 692.32 2438.58 0.00 0.00 0.00 0.00 22.78 0.00
December 12430.80 30-DEC-11:35 10245.60 192.31 711.25 0.00 0.00 0.00 0.00 0.00 28.71
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9828.98   10245.60 192.31 711.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13360.74   83672.40 4536.87 6401.28 0.00 0.00 0.00 0.00 88.46 32.14



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 32088.77 22-JAN-11:35 30415.32 4577.51 8445.65 0.00 0.00 0.00 0.00 0.00 209.87
February 31280.51 04-FEB-11:35 30415.32 3814.59 7389.94 0.00 0.00 0.00 0.00 0.00 68.91
March 31414.93 11-MAR-11:35 30415.32 3814.59 7389.94 0.00 0.00 0.00 0.00 49.25 0.00
April 31119.25 26-APR-18:10 248391.78 47325.14 66509.49 0.00 0.00 0.00 0.00 0.00 131.17
May 31410.77 04-MAY-18:10 248391.78 46825.20 66509.49 0.00 0.00 0.00 0.00 0.00 128.40
June 31599.93 29-JUN-18:10 248391.78 45731.06 66509.49 0.00 0.00 0.00 0.00 0.00 37.84
July 32309.83 19-JUL-18:10 212907.24 39402.32 57008.13 0.00 0.00 0.00 0.00 0.00 2.47
August 32307.46 17-AUG-18:10 212907.24 40544.11 57008.13 0.00 0.00 0.00 0.00 0.00 68.88
September 34668.73 30-SEP-10:35 30415.32 3814.59 7389.94 0.00 0.00 0.00 0.00 243.98 0.00
October 35536.82 16-OCT-21:52 364983.84 42581.52 59119.55 0.00 0.00 0.00 0.00 0.00 132.67
November 33624.64 19-NOV-11:35 30415.32 4577.51 8445.65 0.00 0.00 0.00 0.00 94.70 0.00
December 31884.82 30-DEC-11:35 30415.32 3814.59 7389.94 0.00 0.00 0.00 0.00 0.00 53.38
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 31119.25   30415.32 3814.59 7389.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 35536.82   364983.84 47325.14 66509.49 0.00 0.00 0.00 0.00 243.98 209.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3053.25 14-JAN-16:11 378.00 218.80 387.20 0.00 0.00 0.00 0.00 1.32 0.00
February 3065.39 03-FEB-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 8.10
March 2715.12 05-MAR-16:11 378.00 218.80 387.20 0.00 0.00 0.00 0.00 0.00 25.69
April 2866.03 01-APR-18:02 702.00 568.30 726.98 0.00 0.00 0.00 0.00 0.00 12.50
May 2838.61 24-MAY-08:61 252.00 291.73 792.83 0.00 0.00 0.00 0.00 0.00 11.40
June 2774.45 28-JUN-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 12.39
July 2787.62 17-JUL-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 2.73
August 2775.55 17-AUG-18:02 831.60 505.79 726.98 0.00 0.00 0.00 0.00 0.00 5.63
September 2733.30 21-SEP-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 14.12 0.00
October 3101.25 14-OCT-08:61 540.00 530.41 1633.07 0.00 0.00 0.00 0.00 14.67 0.00
November 3025.79 27-NOV-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 9.86
December 3061.56 19-DEC-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 7.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2715.12   252.00 159.12 300.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3101.25   970.20 590.08 1633.07 0.00 0.00 0.00 0.00 14.67 25.69



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2718.28 09-JAN-16:11 680.40 185.62 350.28 0.00 0.00 0.00 0.00 0.00 21.01
February 2877.66 06-FEB-16:11 680.40 185.62 350.28 0.00 0.00 0.00 0.00 0.00 24.41
March 2622.39 19-MAR-18:11 1170.00 947.05 1211.49 0.00 0.00 0.00 0.00 0.00 30.68
April 2893.88 19-APR-18:01 1386.00 842.88 1211.49 0.00 0.00 0.00 0.00 0.00 31.94
May 2824.18 24-MAY-08:51 360.00 416.70 1132.48 0.00 0.00 0.00 0.00 0.00 12.47
June 2692.62 04-JUN-19:31 1053.00 852.35 1469.59 0.00 0.00 0.00 0.00 0.00 26.28
July 2589.43 09-JUL-21:51 1247.40 724.50 805.91 0.00 0.00 0.00 0.00 0.00 20.07
August 2531.90 21-AUG-20:11 1281.60 674.30 1453.79 0.00 0.00 0.00 0.00 0.00 26.04
September 2626.16 30-SEP-08:61 486.00 477.32 1469.59 0.00 0.00 0.00 0.00 4.40 0.00
October 3073.46 14-OCT-08:61 540.00 530.35 1632.88 0.00 0.00 0.00 0.00 13.35 0.00
November 2734.19 28-NOV-19:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 29.82
December 2783.94 19-DEC-19:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 25.25
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2531.90   360.00 185.62 350.28 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3073.46   1386.00 947.05 1632.88 0.00 0.00 0.00 0.00 13.35 31.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 553.77 14-JAN-12:40 0.00 19.64 33.54 0.00 0.00 0.00 0.00 0.00 1.16
February 489.66 02-FEB-12:40 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 6.29
March 410.34 11-MAR-13:10 0.00 19.64 33.54 0.00 0.00 0.00 0.00 0.00 2.28
April 284.73 08-APR-12:50 0.00 19.64 33.54 0.00 0.00 0.00 0.00 0.00 3.85
May 201.52 04-MAY-12:30 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 2.71
June 180.89 30-JUN-06:52 0.00 166.67 1160.96 0.00 0.00 0.00 0.00 0.00 7.48
July 213.21 30-JUL-08:00 0.00 33.33 232.19 0.00 0.00 0.00 0.00 0.00 5.70
August 270.92 30-AUG-13:00 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 2.28
September 507.52 30-SEP-13:05 0.00 39.29 67.08 0.00 0.00 0.00 0.00 4.30 0.00
October 614.45 16-OCT-12:20 0.00 16.67 30.96 0.00 0.00 0.00 0.00 7.00 0.00
November 584.78 19-NOV-12:30 0.00 19.64 33.54 0.00 0.00 0.00 0.00 0.00 0.18
December 566.84 19-DEC-13:00 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 0.60
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 180.89   0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 614.45   0.00 166.67 1160.96 0.00 0.00 0.00 0.00 7.00 7.48



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 933.73 16-JAN-09:02 324.00 200.06 959.99 0.00 0.00 0.00 0.00 0.00 6.15
February 922.76 03-FEB-19:01 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.00 7.29
March 851.14 13-MAR-18:01 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.00 8.29
April 925.04 02-APR-08:51 486.00 300.09 1439.98 0.00 0.00 0.00 0.00 0.00 2.45
May 932.07 24-MAY-08:51 360.00 261.98 1109.66 0.00 0.00 0.00 0.00 0.00 3.48
June 904.91 24-JUN-08:51 540.00 333.44 1599.98 0.00 0.00 0.00 0.00 0.00 1.55
July 930.26 18-JUL-18:01 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.29 0.00
August 878.15 14-AUG-15:12 583.20 100.03 294.19 0.00 0.00 0.00 0.00 2.29 0.00
September 862.08 03-SEP-08:51 540.00 333.44 1599.98 0.00 0.00 0.00 0.00 0.00 1.82
October 1039.01 14-OCT-08:61 540.00 333.44 1599.98 0.00 0.00 0.00 0.00 3.59 0.00
November 949.94 19-NOV-09:41 432.00 266.75 1279.98 0.00 0.00 0.00 0.00 3.04 0.00
December 933.55 19-DEC-19:01 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.00 7.30
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 851.14   324.00 100.03 294.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1039.01   970.20 370.95 1599.98 0.00 0.00 0.00 0.00 3.59 8.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2735.41 14-JAN-16:11 378.00 218.80 387.20 0.00 0.00 0.00 0.00 1.23 0.00
February 2730.37 03-FEB-09:01 252.00 291.73 792.83 0.00 0.00 0.00 0.00 0.00 12.86
March 2452.33 24-MAR-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 14.31
April 2726.99 02-APR-08:61 378.00 371.29 1143.15 0.00 0.00 0.00 0.00 0.00 16.52
May 2733.82 24-MAY-08:61 252.00 291.73 792.83 0.00 0.00 0.00 0.00 0.00 14.46
June 2496.54 20-JUN-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 3.07
July 2529.44 02-JUL-08:61 378.00 371.29 1143.15 0.00 0.00 0.00 0.00 0.00 10.21
August 2533.40 13-AUG-08:61 378.00 371.29 1143.15 0.00 0.00 0.00 0.00 0.00 1.58
September 2504.42 09-SEP-15:11 378.00 218.80 387.20 0.00 0.00 0.00 0.00 0.00 3.12
October 2819.36 14-OCT-08:61 540.00 530.41 1633.07 0.00 0.00 0.00 0.00 14.10 0.00
November 2755.11 27-NOV-09:01 252.00 291.73 792.83 0.00 0.00 0.00 0.00 0.00 4.65
December 2772.75 05-DEC-09:01 252.00 291.73 792.83 0.00 0.00 0.00 0.00 4.80 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2452.33   252.00 185.64 350.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2819.36   680.40 530.41 1633.07 0.00 0.00 0.00 0.00 14.10 16.52



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2568.35 14-JAN-09:52 324.00 318.21 979.73 0.00 0.00 0.00 0.00 0.00 0.80
February 2655.25 03-FEB-09:51 252.00 291.69 792.74 0.00 0.00 0.00 0.00 0.00 5.26
March 2616.58 23-MAR-08:51 324.00 375.03 1019.23 0.00 0.00 0.00 0.00 0.00 15.66
April 2862.21 02-APR-08:51 486.00 477.32 1469.59 0.00 0.00 0.00 0.00 0.00 14.99
May 2949.46 24-MAY-08:51 360.00 416.70 1132.48 0.00 0.00 0.00 0.00 0.00 19.73
June 2769.92 23-JUN-08:51 360.00 416.70 1132.48 0.00 0.00 0.00 0.00 0.00 12.10
July 2737.65 04-JUL-08:51 540.00 530.35 1632.88 0.00 0.00 0.00 0.00 0.00 10.59
August 2643.78 22-AUG-08:51 360.00 416.70 1132.48 0.00 0.00 0.00 0.00 0.00 16.51
September 2684.66 12-SEP-08:51 360.00 416.70 1132.48 0.00 0.00 0.00 0.00 0.00 11.63
October 3144.43 17-OCT-08:21 360.00 416.70 1132.48 0.00 0.00 0.00 0.00 6.45 0.00
November 2584.35 28-NOV-09:52 216.00 250.02 679.49 0.00 0.00 0.00 0.00 0.00 4.21
December 2815.31 05-DEC-09:41 324.00 375.03 1019.23 0.00 0.00 0.00 0.00 6.42 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2568.35   216.00 250.02 679.49 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3144.43   540.00 530.35 1632.88 0.00 0.00 0.00 0.00 6.45 19.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1844.41 22-JAN-11:35 1508.90 773.33 0.00 0.00 0.00 0.00 0.00 0.00 20.58
February 1814.81 04-FEB-11:35 1508.90 644.45 0.00 0.00 0.00 0.00 0.00 0.00 5.30
March 1822.03 12-MAR-10:35 1508.90 773.33 0.00 0.00 0.00 0.00 0.00 0.00 1.63
April 1912.81 30-APR-10:35 1508.90 773.33 0.00 0.00 0.00 0.00 0.00 13.23 0.00
May 1915.57 04-MAY-10:35 1005.94 644.45 0.00 0.00 0.00 0.00 0.00 0.00 0.63
June 1973.16 25-JUN-10:35 1508.90 773.33 0.00 0.00 0.00 0.00 0.00 2.62 0.00
July 2060.22 23-JUL-10:35 1508.90 773.33 0.00 0.00 0.00 0.00 0.00 11.44 0.00
August 2079.22 19-AUG-10:35 1508.90 644.45 0.00 0.00 0.00 0.00 0.00 7.29 0.00
September 2156.67 30-SEP-10:35 1508.90 644.45 0.00 0.00 0.00 0.00 0.00 27.20 0.00
October 2148.07 16-OCT-10:35 1005.94 644.45 0.00 0.00 0.00 0.00 0.00 46.72 0.00
November 1920.68 19-NOV-11:35 1508.90 773.33 0.00 0.00 0.00 0.00 0.00 13.44 0.00
December 1839.05 05-DEC-11:35 1005.94 644.45 0.00 0.00 0.00 0.00 0.00 4.24 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1814.81   1005.94 644.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2156.67   1508.90 773.33 0.00 0.00 0.00 0.00 0.00 46.72 20.58



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3171.30 14-JAN-16:11 378.00 218.80 387.20 0.00 0.00 0.00 0.00 1.11 0.00
February 3180.09 03-FEB-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 8.27
March 2823.55 15-MAR-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 18.50
April 3006.54 01-APR-18:02 702.00 568.30 726.98 0.00 0.00 0.00 0.00 0.00 13.18
May 2920.87 24-MAY-08:61 252.00 291.73 792.83 0.00 0.00 0.00 0.00 0.00 11.24
June 2866.12 28-JUN-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 12.60
July 2894.59 17-JUL-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 2.92
August 2885.94 03-AUG-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 12.08
September 2811.15 24-SEP-15:11 378.00 218.80 387.20 0.00 0.00 0.00 0.00 0.00 12.16
October 3215.93 26-OCT-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 1.35
November 3135.85 30-NOV-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 15.25
December 3179.84 19-DEC-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 7.21
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2811.15   252.00 185.64 350.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3215.93   970.20 590.08 848.14 0.00 0.00 0.00 0.00 1.11 18.50



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2775.92 09-JAN-16:11 680.40 185.62 350.28 0.00 0.00 0.00 0.00 0.00 20.61
February 2971.99 06-FEB-16:11 680.40 185.62 350.28 0.00 0.00 0.00 0.00 0.00 24.50
March 2828.97 19-MAR-18:11 1170.00 947.05 1211.49 0.00 0.00 0.00 0.00 0.00 32.37
April 3123.67 23-APR-18:11 1170.00 947.05 1211.49 0.00 0.00 0.00 0.00 0.00 31.46
May 2975.55 18-MAY-19:11 1386.00 947.05 1632.88 0.00 0.00 0.00 0.00 0.00 33.09
June 2887.22 04-JUN-19:31 1053.00 852.35 1469.59 0.00 0.00 0.00 0.00 0.00 27.82
July 2748.93 08-JUL-21:11 1247.40 724.50 805.91 0.00 0.00 0.00 0.00 0.00 28.53
August 2655.97 21-AUG-20:11 1281.60 674.30 1453.79 0.00 0.00 0.00 0.00 0.00 27.17
September 2752.89 21-SEP-15:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 13.91 0.00
October 3101.98 14-OCT-08:61 540.00 530.35 1632.88 0.00 0.00 0.00 0.00 14.30 0.00
November 2755.47 28-NOV-19:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 28.87
December 2819.93 19-DEC-19:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 24.50
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2655.97   540.00 159.11 300.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3123.67   1386.00 947.05 1632.88 0.00 0.00 0.00 0.00 14.30 33.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1719.83 14-JAN-16:11 378.00 137.54 379.35 0.00 0.00 0.00 0.00 0.22 0.00
February 1709.78 03-FEB-16:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 4.46
March 1507.09 24-MAR-18:01 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.00 15.52
April 1620.68 01-APR-18:02 702.00 357.25 712.25 0.00 0.00 0.00 0.00 0.00 7.07
May 1543.24 24-MAY-08:61 252.00 183.39 776.76 0.00 0.00 0.00 0.00 0.00 5.65
June 1510.04 21-JUN-15:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 1.21
July 1547.70 18-JUL-18:01 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.87 0.00
August 1551.03 02-AUG-15:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 0.23
September 1537.34 21-SEP-15:12 583.20 100.03 294.19 0.00 0.00 0.00 0.00 7.00 0.00
October 1727.93 14-OCT-08:61 540.00 333.44 1599.98 0.00 0.00 0.00 0.00 7.22 0.00
November 1703.46 27-NOV-09:01 252.00 183.39 776.76 0.00 0.00 0.00 0.00 0.00 2.53
December 1716.75 19-DEC-16:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 3.98
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1507.09   252.00 100.03 294.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1727.93   970.20 370.95 1599.98 0.00 0.00 0.00 0.00 7.22 15.52



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 18383.65 18-JAN-19:10 146938.85 17192.76 47235.32 0.00 0.00 0.00 0.00 0.00 27.43
February 17993.18 01-FEB-22:00 23990.02 2456.11 6747.90 0.00 0.00 0.00 0.00 0.00 78.45
March 18482.31 23-MAR-18:10 146938.85 17192.76 47235.32 0.00 0.00 0.00 0.00 0.00 44.84
April 19224.45 26-APR-18:10 146938.85 13366.65 47235.32 0.00 0.00 0.00 0.00 0.00 29.21
May 19400.11 04-MAY-18:10 146938.85 12288.92 47235.32 0.00 0.00 0.00 0.00 0.00 28.53
June 19835.23 29-JUN-18:10 146938.85 10315.66 47235.32 0.00 0.00 0.00 0.00 0.00 9.33
July 20050.39 19-JUL-18:10 125947.58 9495.89 40487.42 0.00 0.00 0.00 0.00 0.00 0.61
August 19688.14 17-AUG-18:10 125947.58 10770.66 40487.42 0.00 0.00 0.00 0.00 0.00 14.27
September 19610.55 29-SEP-21:20 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 3.48 0.00
October 19638.80 04-OCT-21:20 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 22.80
November 18153.02 01-NOV-18:10 104956.32 12280.55 33739.51 0.00 0.00 0.00 0.00 0.00 50.25
December 18351.25 05-DEC-22:00 23990.02 2456.11 6747.90 0.00 0.00 0.00 0.00 0.00 48.28
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 17993.18   23990.02 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20050.39   146938.85 17192.76 47235.32 0.00 0.00 0.00 0.00 3.48 78.45



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19672.31 18-JAN-22:10 53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 0.00 54.89
February 18728.55 01-FEB-23:00 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 84.56
March 19216.42 24-MAR-21:10 53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 0.00 84.32
April 20645.79 26-APR-21:10 53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 0.00 61.12
May 20868.95 04-MAY-21:10 53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 0.00 53.44
June 20943.80 27-JUN-21:10 53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 0.00 53.37
July 21062.11 19-JUL-21:10 53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 0.00 45.71
August 20998.83 18-AUG-21:10 53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 0.00 38.10
September 21234.67 29-SEP-21:10 53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 3.56 0.00
October 20974.03 16-OCT-21:10 53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 0.00 43.09
November 19083.18 10-NOV-22:10 53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 0.00 68.91
December 19614.42 05-DEC-22:10 53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 0.00 52.13
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 18728.55   26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21234.67   53977.54 3684.16 13495.81 0.00 0.00 0.00 0.00 3.56 84.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 27239.42 14-JAN-11:50 800.57 303.01 14604.56 18744.03 0.00 0.00 0.00 12.52 0.00
February 27066.22 01-FEB-11:50 533.71 303.01 14604.56 18744.03 0.00 0.00 0.00 9.22 0.00
March 27917.66 19-MAR-10:35 1601.14 727.22 29209.11 37488.05 0.00 0.00 0.00 0.00 31.88
April 28327.74 30-APR-10:40 1601.14 727.22 29209.11 37488.05 0.00 0.00 0.00 10.32 0.00
May 27982.27 04-MAY-10:50 533.71 303.01 14604.56 18744.03 0.00 0.00 0.00 0.00 13.87
June 28347.66 25-JUN-10:40 1601.14 727.22 29209.11 37488.05 0.00 0.00 0.00 0.00 7.22
July 28761.66 23-JUL-10:40 1601.14 727.22 29209.11 37488.05 0.00 0.00 0.00 10.33 0.00
August 28613.75 19-AUG-10:40 1601.14 606.02 29209.11 37488.05 0.00 0.00 0.00 3.77 0.00
September 29094.77 30-SEP-10:50 800.57 303.01 14604.56 18744.03 0.00 0.00 0.00 42.73 0.00
October 29001.78 15-OCT-10:40 1601.14 727.22 29209.11 37488.05 0.00 0.00 0.00 48.55 0.00
November 27825.70 19-NOV-11:50 800.57 363.61 14604.56 18744.03 0.00 0.00 0.00 12.49 0.00
December 27090.70 05-DEC-11:50 533.71 303.01 14604.56 18744.03 0.00 0.00 0.00 0.00 6.13
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 27066.22   533.71 303.01 14604.56 18744.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 29094.77   1601.14 727.22 29209.11 37488.05 0.00 0.00 0.00 48.55 31.88



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2359.67 20-JAN-11:35 1064.64 682.05 0.00 0.00 0.00 0.00 0.00 0.00 15.45
February 2257.46 04-FEB-11:50 798.48 341.02 0.00 0.00 0.00 0.00 0.00 0.00 18.37
March 2334.01 11-MAR-11:35 1596.96 682.05 0.00 0.00 0.00 0.00 0.00 1.73 0.00
April 2765.77 27-APR-14:10 798.48 341.02 0.00 0.00 0.00 0.00 0.00 0.00 26.56
May 3207.99 04-MAY-12:00 532.32 341.02 0.00 0.00 0.00 0.00 0.00 0.00 0.68
June 3225.71 30-JUN-15:35 2661.60 682.05 0.00 0.00 0.00 0.00 0.00 0.00 8.43
July 3676.43 30-JUL-13:30 532.32 272.82 0.00 0.00 0.00 0.00 0.00 0.00 0.68
August 3919.37 19-AUG-13:10 1596.96 682.05 0.00 0.00 0.00 0.00 0.00 18.46 0.00
September 5439.34 30-SEP-13:30 798.48 341.02 0.00 0.00 0.00 0.00 0.00 49.26 0.00
October 5335.87 16-OCT-12:30 532.32 341.02 0.00 0.00 0.00 0.00 0.00 67.93 0.00
November 3042.65 19-NOV-13:00 798.48 409.23 0.00 0.00 0.00 0.00 0.00 18.45 0.00
December 2771.40 19-DEC-13:00 532.32 341.02 0.00 0.00 0.00 0.00 0.00 12.15 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2257.46   532.32 272.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5439.34   2661.60 682.05 0.00 0.00 0.00 0.00 0.00 67.93 26.56



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.370249E+12 229242.24 14-JAN-18:10 0.410090E+12 337696.64 06-JAN-22:00
February 0.325752E+12 219225.46 13-FEB-19:19 0.355349E+12 334247.49 27-FEB-18:19
March 0.357474E+12 217126.01 23-MAR-18:10 0.404807E+12 335590.07 29-MAR-20:00
April 0.362865E+12 230975.09 26-APR-18:30 0.361740E+12 329317.36 17-APR-17:10
May 0.372531E+12 226655.05 04-MAY-18:00 0.369883E+12 327739.05 12-MAY-17:19
June 0.385239E+12 264641.71 29-JUN-18:10 0.347900E+12 317094.80 02-JUN-17:00
July 0.447397E+12 292990.21 18-JUL-18:10 0.355349E+12 313514.93 10-JUL-17:00
August 0.461646E+12 277997.94 14-AUG-18:40 0.355122E+12 312981.42 30-AUG-17:49
September 0.410130E+12 297934.06 29-SEP-18:00 0.345865E+12 315446.69 29-SEP-17:10
October 0.432269E+12 287292.52 04-OCT-18:10 0.362943E+12 319997.52 31-OCT-17:40
November 0.361352E+12 234906.86 19-NOV-08:00 0.368142E+12 325885.26 24-NOV-18:19
December 0.374253E+12 230413.54 05-DEC-19:10 0.400616E+12 333523.28 12-DEC-21:00
             
Annual Sum or Average 0.466116E+13     0.443781E+13    
Minimum of Months 0.325752E+12 217126.01   0.345865E+12 312981.42  
Maximum of Months 0.461646E+12 297934.06   0.410090E+12 337696.64  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.467757E+11 0.191147E+11 0.140003E+12 0.690928E+11 0.496929E+11 0.542975E+10 0.00 0.283493E+11 0.00 0.00 0.00 0.804707E+10 0.00
February 0.420922E+11 0.163386E+11 0.126445E+12 0.624064E+11 0.443443E+11 0.494084E+10 0.00 0.185276E+11 0.00 0.00 0.00 0.727159E+10 0.00
March 0.465069E+11 0.167457E+11 0.140056E+12 0.690952E+11 0.489078E+11 0.520757E+10 0.00 0.191510E+11 0.00 0.00 0.00 0.804567E+10 0.00
April 0.446956E+11 0.148876E+11 0.135446E+12 0.668635E+11 0.478499E+11 0.562807E+10 0.00 0.360588E+11 0.00 0.00 0.00 0.779701E+10 0.00
May 0.459772E+11 0.142139E+11 0.140035E+12 0.690936E+11 0.493098E+11 0.585302E+10 0.00 0.362378E+11 0.00 0.00 0.00 0.804708E+10 0.00
June 0.444262E+11 0.131775E+11 0.135537E+12 0.668657E+11 0.484714E+11 0.571378E+10 0.00 0.596011E+11 0.00 0.00 0.00 0.778858E+10 0.00
July 0.458995E+11 0.138734E+11 0.139944E+12 0.690912E+11 0.511611E+11 0.615695E+10 0.00 0.109448E+12 0.00 0.00 0.00 0.805551E+10 0.00
August 0.461186E+11 0.148580E+11 0.140067E+12 0.690950E+11 0.515117E+11 0.623439E+10 0.00 0.121929E+12 0.00 0.00 0.00 0.804707E+10 0.00
September 0.449376E+11 0.156427E+11 0.135457E+12 0.668637E+11 0.492530E+11 0.585397E+10 0.00 0.806651E+11 0.00 0.00 0.00 0.779842E+10 0.00
October 0.466486E+11 0.175305E+11 0.139992E+12 0.690927E+11 0.514312E+11 0.608560E+10 0.00 0.896856E+11 0.00 0.00 0.00 0.804567E+10 0.00
November 0.452371E+11 0.181597E+11 0.135531E+12 0.668647E+11 0.482350E+11 0.556033E+10 0.00 0.303632E+11 0.00 0.00 0.00 0.778013E+10 0.00
December 0.467326E+11 0.194405E+11 0.139944E+12 0.690917E+11 0.499031E+11 0.558857E+10 0.00 0.317632E+11 0.00 0.00 0.00 0.805552E+10 0.00
                           
Annual Sum or Average 0.546048E+12 0.193983E+12 0.164846E+13 0.813516E+12 0.590071E+12 0.682528E+11 0.00 0.661780E+12 0.00 0.00 0.00 0.947793E+11 0.00
Minimum of Months 0.420922E+11 0.131775E+11 0.126445E+12 0.624064E+11 0.443443E+11 0.494084E+10 0.00 0.185276E+11 0.00 0.00 0.00 0.727159E+10 0.00
Maximum of Months 0.467757E+11 0.194405E+11 0.140067E+12 0.690952E+11 0.515117E+11 0.623439E+10 0.00 0.121929E+12 0.00 0.00 0.00 0.805552E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.401890E+11 0.00 0.217982E+12 0.00 0.00
February 0.137204E+12 0.00 0.210292E+11 0.00 0.197116E+12 0.00 0.00
March 0.152024E+12 0.00 0.362562E+11 0.00 0.216527E+12 0.00 0.00
April 0.146956E+12 0.00 0.854149E+10 0.00 0.206243E+12 0.00 0.00
May 0.151978E+12 0.00 0.883039E+10 0.00 0.209074E+12 0.00 0.00
June 0.147114E+12 0.00 0.194288E+10 0.00 0.198844E+12 0.00 0.00
July 0.151820E+12 0.00 0.395836E+09 0.00 0.203133E+12 0.00 0.00
August 0.152039E+12 0.00 0.118745E+09 0.00 0.202964E+12 0.00 0.00
September 0.146971E+12 0.00 0.756992E+09 0.00 0.198137E+12 0.00 0.00
October 0.151903E+12 0.00 0.294227E+10 0.00 0.208097E+12 0.00 0.00
November 0.147091E+12 0.00 0.157499E+11 0.00 0.205301E+12 0.00 0.00
December 0.151820E+12 0.00 0.330308E+11 0.00 0.215765E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.169784E+12 0.00 0.247918E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.118745E+09 0.00 0.197116E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.401890E+11 0.00 0.217982E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 45764.37 02-JAN-20:10 12338.45 01-JAN-00:10 88863.15 02-JAN-07:10 49590.64 18-JAN-07:19 27509.29 19-JAN-21:10 2606.48 18-JAN-12:00 0.00 01-JAN-00:10
February 45764.37 01-FEB-20:10 12338.45 01-FEB-00:10 88863.15 01-FEB-07:10 49590.23 10-FEB-07:19 26448.00 03-FEB-19:10 2479.42 01-FEB-13:09 0.00 01-FEB-00:10
March 45764.37 01-MAR-20:10 12338.45 01-MAR-00:10 88863.15 01-MAR-07:10 49590.79 16-MAR-06:19 27415.79 23-MAR-19:19 2695.96 11-MAR-11:50 0.00 01-MAR-00:10
April 45764.37 03-APR-19:10 12338.45 01-APR-00:10 88863.15 03-APR-06:10 49590.16 05-APR-06:19 28008.14 27-APR-19:19 2533.49 13-APR-08:00 0.00 01-APR-00:10
May 45764.37 01-MAY-19:10 12338.45 01-MAY-00:10 88863.15 01-MAY-06:10 49589.56 09-MAY-06:19 28208.16 24-MAY-19:30 2397.62 03-MAY-09:50 0.00 01-MAY-00:10
June 45764.37 01-JUN-19:10 12338.45 01-JUN-00:10 88863.15 01-JUN-06:10 49589.56 16-JUN-06:19 29154.82 22-JUN-20:30 2783.16 29-JUN-18:10 0.00 01-JUN-00:10
July 45764.37 03-JUL-19:10 12338.45 01-JUL-00:10 88863.15 03-JUL-06:10 49589.56 12-JUL-06:19 29069.25 19-JUL-21:00 3077.96 18-JUL-18:10 0.00 01-JUL-00:10
August 45764.37 01-AUG-19:10 12338.45 01-AUG-00:10 88863.15 01-AUG-06:10 49590.07 29-AUG-06:19 29159.27 18-AUG-21:00 3028.22 17-AUG-15:30 0.00 01-AUG-00:10
September 45764.37 01-SEP-19:10 12338.45 01-SEP-00:10 88863.15 01-SEP-06:10 49590.44 18-SEP-06:19 31014.30 29-SEP-21:19 3579.84 29-SEP-15:20 0.00 01-SEP-00:10
October 45764.37 02-OCT-19:10 12338.45 01-OCT-00:10 88863.15 02-OCT-06:10 49590.77 23-OCT-06:19 32130.08 16-OCT-21:00 3533.30 17-OCT-10:50 0.00 01-OCT-00:10
November 45764.37 01-NOV-19:10 12338.45 01-NOV-00:10 88863.15 01-NOV-06:10 49590.83 03-NOV-06:19 27298.43 19-NOV-20:19 2872.51 19-NOV-10:39 0.00 01-NOV-00:10
December 45764.37 01-DEC-20:10 12338.45 01-DEC-00:10 88863.15 01-DEC-07:10 49590.55 08-DEC-07:19 27013.11 19-DEC-19:10 2539.95 16-DEC-10:50 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 45764.37   12338.45   88863.15   49589.56   26448.00   2397.62   0.00  
Maximum of Months 45764.37   12338.45   88863.15   49590.83   32130.08   3579.84   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 63793.54 14-JAN-11:39 0.00 0.00 0.00 4751.12 02-JAN-19:40 0.00
February 58206.08 01-FEB-11:50 0.00 0.00 0.00 4751.13 21-FEB-07:40 0.00
March 58096.67 23-MAR-15:30 0.00 0.00 0.00 4751.12 13-MAR-06:40 0.00
April 65110.38 26-APR-10:39 0.00 0.00 0.00 4751.13 17-APR-06:40 0.00
May 49521.87 03-MAY-09:50 0.00 0.00 0.00 4751.13 22-MAY-06:40 0.00
June 89062.90 29-JUN-18:10 0.00 0.00 0.00 4751.13 05-JUN-06:40 0.00
July 118148.77 19-JUL-15:30 0.00 0.00 0.00 4751.13 31-JUL-06:40 0.00
August 123656.06 17-AUG-15:30 0.00 0.00 0.00 4751.13 21-AUG-06:40 0.00
September 129746.80 29-SEP-15:30 0.00 0.00 0.00 4751.13 25-SEP-06:40 0.00
October 133252.95 16-OCT-12:09 0.00 0.00 0.00 4751.13 02-OCT-06:40 0.00
November 76545.09 19-NOV-10:39 0.00 0.00 0.00 4751.12 13-NOV-07:19 0.00
December 70366.89 05-DEC-09:50 0.00 0.00 0.00 4751.13 26-DEC-07:40 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 49521.87   0.00 0.00 0.00 4751.12   0.00
Maximum of Months 133252.95   0.00 0.00 0.00 4751.13   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 229242.24 14-JAN-18:10 32579.38 72346.32 12338.45 49238.19 19495.27 2201.27 0.00 35404.70 0.00
February 219225.46 13-FEB-19:19 40691.94 77265.07 12338.45 28151.71 25143.74 2261.43 0.00 26932.65 0.00
March 217126.01 23-MAR-18:10 40691.94 77265.07 12338.45 28144.63 23495.93 2219.80 0.00 26526.86 0.00
April 230975.09 26-APR-18:30 40691.94 77265.07 12338.45 28151.17 23739.84 2297.53 0.00 40047.11 0.00
May 226655.05 04-MAY-18:00 40691.94 77265.07 12338.45 28151.71 23849.42 2265.22 0.00 35651.37 0.00
June 264641.71 29-JUN-18:10 37303.93 77265.07 0.00 28142.63 23641.65 2783.16 0.00 89062.90 0.00
July 292990.21 18-JUL-18:10 37629.55 77265.07 0.00 28142.65 27684.85 3077.96 0.00 113111.21 0.00
August 277997.94 14-AUG-18:40 40691.94 77265.07 12338.45 28151.67 24053.81 2750.97 0.00 86306.28 0.00
September 297934.06 29-SEP-18:00 40691.94 77265.07 12338.45 28151.71 27841.57 3545.68 0.00 102034.31 0.00
October 287292.52 04-OCT-18:10 40691.94 77265.07 12338.45 28144.63 23574.21 2861.18 0.00 95973.93 0.00
November 234906.86 19-NOV-08:00 19752.38 85940.95 0.00 49518.29 20615.82 2254.98 0.00 51581.64 0.00
December 230413.54 05-DEC-19:10 40691.94 77265.07 12338.45 28144.63 24377.92 2250.35 0.00 39288.33 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 217126.01   19752.38 72346.32 0.00 28142.63 19495.27 2201.27 0.00 26526.86 0.00
Maximum of Months 297934.06   40691.94 85940.95 12338.45 49518.29 27841.57 3545.68 0.00 113111.21 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 145374.46 08-JAN-06:49 0.00 226533.94 27-JAN-21:19 0.00
February 104248.32 01-FEB-18:10 0.00 94144.57 05-FEB-05:00 0.00 226545.67 03-FEB-21:30 0.00
March 104248.32 01-MAR-18:10 0.00 122659.88 30-MAR-02:00 0.00 225278.96 01-MAR-21:40 0.00
April 104248.32 01-APR-17:10 0.00 63949.66 01-APR-05:00 0.00 223208.90 04-APR-20:49 0.00
May 104248.32 01-MAY-17:10 0.00 51772.77 14-MAY-04:49 0.00 218616.98 01-MAY-20:30 0.00
June 104248.32 01-JUN-17:10 0.00 10297.40 13-JUN-03:00 0.00 214902.14 01-JUN-20:00 0.00
July 104248.32 01-JUL-17:10 0.00 6464.91 06-JUL-00:00 0.00 211848.44 03-JUL-20:19 0.00
August 104248.32 01-AUG-17:10 0.00 3161.19 02-AUG-08:00 0.00 211773.85 31-AUG-20:00 0.00
September 104248.32 01-SEP-17:10 0.00 9405.60 18-SEP-08:00 0.00 214550.93 29-SEP-20:19 0.00
October 104248.32 02-OCT-17:10 0.00 30837.33 30-OCT-03:00 0.00 216861.10 31-OCT-20:19 0.00
November 104248.32 01-NOV-17:10 0.00 65333.00 24-NOV-03:00 0.00 221969.06 29-NOV-21:19 0.00
December 104248.32 01-DEC-18:10 0.00 96677.74 24-DEC-03:00 0.00 225157.38 29-DEC-21:49 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 3161.19   0.00 211773.85   0.00
Maximum of Months 104248.32   0.00 145374.46   0.00 226545.67   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.50 21.69 0.50 21.69
September 0.00 0.00 0.00 0.00 0.83 21.96 0.83 21.96
October 0.00 0.00 0.00 0.00 2.67 21.93 2.67 21.93
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.00 21.91 4.00 21.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.67 21.96 2.67 21.96



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 21.81 0.50 21.81
May 0.00 0.00 0.00 0.00 0.50 21.97 0.50 21.97
June 0.00 0.00 0.00 0.00 1.17 21.74 1.17 21.74
July 0.00 0.00 0.00 0.00 2.33 21.72 2.33 21.72
August 0.00 0.00 0.00 0.00 2.17 21.70 2.17 21.70
September 0.00 0.00 0.00 0.00 0.50 21.91 0.50 21.91
October 0.00 0.00 0.00 0.00 0.83 21.88 0.83 21.88
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   8.00 21.77 8.00 21.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.33 21.97 2.33 21.97



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
May 0.00 0.00 0.00 0.00 0.83 21.76 0.83 21.76
June 0.00 0.00 0.00 0.00 3.50 21.83 3.50 21.83
July 0.00 0.00 0.00 0.00 6.50 21.83 6.50 21.83
August 0.00 0.00 0.00 0.00 5.67 21.78 5.67 21.78
September 0.00 0.00 0.00 0.00 1.67 21.77 1.67 21.77
October 0.00 0.00 0.00 0.00 2.17 21.81 2.17 21.81
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   20.50 21.81 20.50 21.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.50 21.83 6.50 21.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.67 21.81 0.67 21.81
October 0.00 0.00 0.00 0.00 1.17 21.75 1.17 21.75
November 0.00 0.00 0.00 0.00 0.17 21.79 0.17 21.79
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.17 21.76 2.17 21.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.17 21.81 1.17 21.81



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 21.85 0.50 21.85
April 0.00 0.00 0.00 0.00 1.50 22.04 1.50 22.04
May 0.00 0.00 0.00 0.00 2.50 21.95 2.50 21.95
June 0.00 0.00 0.00 0.00 4.00 22.13 4.00 22.13
July 0.00 0.00 0.00 0.00 7.33 22.28 7.33 22.28
August 0.00 0.00 0.00 0.00 7.67 22.28 7.67 22.28
September 0.00 0.00 0.00 0.00 3.33 22.04 3.33 22.04
October 0.00 0.00 0.00 0.00 1.83 21.98 1.83 21.98
November 0.00 0.00 0.00 0.00 0.17 22.02 0.17 22.02
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   28.83 22.16 28.83 22.16
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.67 22.28 7.67 22.28



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 21.70 0.50 21.70
April 0.00 0.00 0.00 0.00 0.33 21.74 0.33 21.74
May 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.17 21.70 1.17 21.70
August 0.00 0.00 0.00 0.00 2.33 21.73 2.33 21.73
September 0.00 0.00 0.00 0.00 1.50 21.93 1.50 21.93
October 0.00 0.00 0.00 0.00 3.67 22.00 3.67 22.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   9.67 21.85 9.67 21.85
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.67 22.00 3.67 22.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
April 0.00 0.00 0.00 0.00 1.00 21.86 1.00 21.86
May 0.00 0.00 0.00 0.00 1.67 21.90 1.67 21.90
June 0.00 0.00 0.00 0.00 2.83 21.83 2.83 21.83
July 0.00 0.00 0.00 0.00 5.67 21.80 5.67 21.80
August 0.00 0.00 0.00 0.00 4.83 21.76 4.83 21.76
September 0.00 0.00 0.00 0.00 0.83 21.97 0.83 21.97
October 0.00 0.00 0.00 0.00 1.33 21.92 1.33 21.92
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   18.33 21.82 18.33 21.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.67 21.97 5.67 21.97



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.00 21.71 1.00 21.71
February 0.00 0.00 0.00 0.00 0.17 21.77 0.17 21.77
March 0.00 0.00 0.00 0.00 0.50 21.70 0.50 21.70
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.67 21.94 0.67 21.94
October 0.00 0.00 0.00 0.00 4.83 22.01 4.83 22.01
November 0.00 0.00 0.00 0.00 1.17 21.76 1.17 21.76
December 0.00 0.00 0.00 0.00 1.17 21.78 1.17 21.78
                 
Annual Sum or Average 0.00   0.00   9.50 21.90 9.50 21.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.83 22.01 4.83 22.01



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 734.83 23.14 0.00 23.14 0.00 23.14
February 672.00 22.55 0.00 22.55 0.00 22.55
March 744.00 22.33 0.00 22.33 0.00 22.33
April 720.00 22.23 0.00 22.23 0.00 22.23
May 744.00 22.22 0.00 22.22 0.00 22.22
June 720.00 22.12 0.00 22.12 0.00 22.12
July 744.00 22.47 0.00 22.47 0.00 22.47
August 744.00 22.58 0.00 22.58 0.00 22.58
September 717.17 22.91 0.00 22.91 0.00 22.91
October 677.17 23.17 0.00 23.17 0.00 23.17
November 657.33 23.28 0.50 23.28 0.00 23.28
December 729.67 23.17 0.00 23.17 0.00 23.17
             
Annual Sum or Average 8604.17 22.67 0.50 22.67 0.00 22.67
Minimum of Months 657.33 22.12 0.00 22.12 0.00 22.12
Maximum of Months 744.00 23.28 0.50 23.28 0.00 23.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 543.17 22.27 110.67 22.56 0.00 22.56
February 534.50 22.05 78.17 22.29 0.00 22.29
March 624.67 21.85 76.83 22.08 0.00 22.08
April 546.33 22.31 95.67 22.54 0.00 22.54
May 694.33 22.16 19.83 22.21 0.00 22.21
June 611.33 22.48 18.83 22.52 0.00 22.52
July 371.83 22.79 176.00 23.09 0.83 23.09
August 221.50 22.87 379.50 23.47 0.50 23.47
September 305.83 22.74 288.17 23.30 2.00 23.30
October 334.00 22.76 265.00 23.27 7.33 23.27
November 505.00 22.54 123.00 22.82 0.00 22.82
December 530.67 22.40 108.67 22.67 0.00 22.67
             
Annual Sum or Average 5823.17 22.36 1740.33 22.71 10.67 22.71
Minimum of Months 221.50 21.85 18.83 22.08 0.00 22.08
Maximum of Months 694.33 22.87 379.50 23.47 7.33 23.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 736.83 22.40 0.00 22.40 0.00 22.40
February 669.50 22.31 0.00 22.31 0.00 22.31
March 736.67 22.15 0.00 22.15 0.00 22.15
April 678.33 22.41 3.50 22.41 0.00 22.41
May 719.67 22.36 4.67 22.37 0.00 22.37
June 637.17 22.49 21.50 22.53 0.00 22.53
July 513.00 22.62 79.00 22.76 3.33 22.76
August 435.50 22.64 130.33 22.88 3.67 22.88
September 533.33 22.69 55.17 22.79 0.00 22.79
October 591.33 22.77 52.17 22.85 0.00 22.85
November 698.83 22.59 0.00 22.59 0.00 22.59
December 738.17 22.52 0.00 22.52 0.00 22.52
             
Annual Sum or Average 7688.33 22.48 346.33 22.53 7.00 22.53
Minimum of Months 435.50 22.15 0.00 22.15 0.00 22.15
Maximum of Months 738.17 22.77 130.33 22.88 3.67 22.88



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 565.83 23.70 0.00 23.70 0.00 23.70
February 504.50 23.76 37.33 23.76 37.17 23.75
March 498.50 23.58 0.00 23.58 0.00 23.58
April 214.83 23.78 2.33 23.78 0.00 23.78
May 212.83 23.93 0.00 23.93 0.00 23.93
June 1.17 24.00 64.67 24.00 0.00 24.00
July 0.00 0.00 299.67 24.00 0.00 24.00
August 0.00 0.00 380.83 24.00 0.00 24.00
September 11.00 24.00 144.50 24.00 0.00 24.00
October 305.33 24.00 125.50 24.00 0.00 24.00
November 389.00 23.95 0.00 23.95 0.00 23.95
December 627.33 23.87 0.00 23.87 0.00 23.87
             
Annual Sum or Average 3330.33 23.80 1054.83 23.85 37.17 23.85
Minimum of Months 0.00 0.00 0.00 23.58 0.00 23.58
Maximum of Months 627.33 24.00 380.83 24.00 37.17 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.24 0.00 21.24 0.00 21.24
February 672.00 21.19 0.00 21.19 0.00 21.19
March 744.00 21.13 0.00 21.13 0.00 21.13
April 720.00 21.33 0.00 21.33 0.00 21.33
May 744.00 21.43 0.00 21.43 0.00 21.43
June 720.00 21.71 0.00 21.71 0.00 21.71
July 744.00 21.92 0.00 21.92 0.00 21.92
August 744.00 21.92 0.00 21.92 0.00 21.92
September 720.00 21.79 0.00 21.79 0.00 21.79
October 744.00 21.88 0.00 21.88 0.00 21.88
November 720.00 21.41 0.00 21.41 0.00 21.41
December 744.00 21.30 0.00 21.30 0.00 21.30
             
Annual Sum or Average 8760.00 21.52 0.00 21.52 0.00 21.52
Minimum of Months 672.00 21.13 0.00 21.13 0.00 21.13
Maximum of Months 744.00 21.92 0.00 21.92 0.00 21.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 253.50 24.00 744.00 24.00 253.50 24.00
February 244.00 24.00 672.00 24.00 244.00 24.00
March 310.17 24.00 744.00 24.00 310.17 24.00
April 344.67 24.00 720.00 24.00 344.67 24.00
May 344.17 24.00 744.00 24.00 344.17 24.00
June 453.33 24.00 720.00 24.00 453.33 24.00
July 591.33 24.00 744.00 24.00 591.33 24.00
August 605.33 24.00 744.00 24.00 605.33 24.00
September 483.00 24.00 720.00 24.00 483.00 24.00
October 376.67 24.00 744.00 24.00 376.67 24.00
November 267.17 24.00 720.00 24.00 267.17 24.00
December 223.17 24.00 744.00 24.00 223.17 24.00
             
Annual Sum or Average 4496.50 24.00 8760.00 24.00 4496.50 24.00
Minimum of Months 223.17 24.00 672.00 24.00 223.17 24.00
Maximum of Months 605.33 24.00 744.00 24.00 605.33 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 606.00 22.05 79.00 22.19 5.33 22.19
February 592.67 21.88 29.50 21.94 1.17 21.94
March 694.17 21.72 16.83 21.74 0.00 21.74
April 713.17 21.80 11.83 21.81 10.17 21.82
May 741.00 21.60 8.17 21.61 8.17 21.62
June 720.00 21.70 48.00 21.76 48.00 21.82
July 743.33 21.84 140.17 21.98 140.17 22.08
August 721.17 22.05 214.83 22.22 214.67 22.33
September 582.83 22.11 165.00 22.27 118.33 22.35
October 529.50 22.20 172.33 22.46 55.17 22.50
November 577.67 22.12 71.33 22.25 2.67 22.25
December 587.33 22.14 83.83 22.32 0.00 22.32
             
Annual Sum or Average 7808.83 21.92 1040.83 22.04 603.83 22.09
Minimum of Months 529.50 21.60 8.17 21.61 0.00 21.62
Maximum of Months 743.33 22.20 214.83 22.46 214.67 22.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 683.33 22.70 16.83 22.72 7.33 22.73
February 631.83 22.57 5.00 22.58 3.17 22.58
March 709.17 22.41 3.67 22.42 0.00 22.42
April 628.33 22.46 22.83 22.50 10.17 22.52
May 678.50 22.43 23.17 22.47 12.83 22.49
June 596.17 22.49 100.00 22.64 78.83 22.72
July 612.50 22.67 234.50 22.91 197.00 23.01
August 642.83 22.83 305.00 23.06 260.67 23.16
September 550.00 22.77 201.17 22.99 145.00 23.08
October 526.33 22.88 130.17 23.05 61.83 23.11
November 620.67 22.79 29.33 22.82 11.50 22.83
December 695.17 22.83 6.00 22.84 0.00 22.84
             
Annual Sum or Average 7574.83 22.65 1077.67 22.76 788.33 22.83
Minimum of Months 526.33 22.41 3.67 22.42 0.00 22.42
Maximum of Months 709.17 22.88 305.00 23.06 260.67 23.16



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 732.50 21.61 8.67 21.61 8.67 21.60
February 656.00 21.53 6.00 21.52 6.00 21.52
March 726.00 21.50 8.33 21.49 8.33 21.48
April 680.00 21.60 0.00 21.60 0.00 21.60
May 723.67 21.63 0.00 21.63 0.00 21.63
June 671.33 21.60 0.00 21.60 0.00 21.60
July 654.67 21.55 0.00 21.55 0.00 21.55
August 645.00 21.53 0.50 21.53 0.50 21.53
September 649.00 21.57 1.00 21.58 0.33 21.58
October 692.33 21.62 0.50 21.62 0.00 21.62
November 692.17 21.62 7.50 21.61 7.50 21.61
December 736.00 21.64 7.50 21.64 7.50 21.63
             
Annual Sum or Average 8258.67 21.58 40.00 21.58 38.83 21.58
Minimum of Months 645.00 21.50 0.00 21.49 0.00 21.48
Maximum of Months 736.00 21.64 8.67 21.64 8.67 21.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.45 43.00 21.43 43.00 21.41
February 671.17 21.45 14.33 21.44 14.33 21.44
March 727.67 21.45 18.67 21.47 10.00 21.46
April 625.50 21.67 48.83 21.89 0.00 21.89
May 642.67 21.76 58.50 22.01 0.00 22.01
June 549.67 21.99 121.50 22.57 10.33 22.61
July 508.33 22.13 201.00 22.93 49.83 23.03
August 516.83 22.07 195.50 22.80 56.33 22.87
September 587.67 21.98 79.83 22.25 16.50 22.27
October 690.17 22.05 42.50 22.14 29.17 22.19
November 720.00 21.61 20.33 21.60 20.33 21.59
December 744.00 21.49 42.17 21.47 42.17 21.45
             
Annual Sum or Average 7727.67 21.73 886.17 21.99 292.00 22.01
Minimum of Months 508.33 21.45 14.33 21.43 0.00 21.41
Maximum of Months 744.00 22.13 201.00 22.93 56.33 23.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.39 11.00 21.38 11.00 21.38
February 672.00 21.39 9.50 21.38 9.50 21.38
March 744.00 21.42 0.00 21.42 0.00 21.42
April 720.00 21.63 0.00 21.63 0.00 21.63
May 744.00 21.75 0.00 21.75 0.00 21.75
June 712.83 22.09 1.67 22.10 0.00 22.10
July 729.17 22.30 25.00 22.34 23.00 22.38
August 735.50 22.24 27.00 22.28 26.83 22.31
September 720.00 21.95 6.67 21.96 6.67 21.97
October 743.50 21.92 18.67 21.96 18.67 21.99
November 720.00 21.43 16.33 21.42 16.33 21.41
December 744.00 21.37 21.83 21.37 21.83 21.36
             
Annual Sum or Average 8729.00 21.74 137.67 21.75 133.83 21.76
Minimum of Months 672.00 21.37 0.00 21.37 0.00 21.36
Maximum of Months 744.00 22.30 27.00 22.34 26.83 22.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.69 13.17 21.68 13.17 21.67
February 672.00 21.58 7.83 21.58 7.83 21.57
March 744.00 21.59 8.67 21.58 8.67 21.57
April 719.33 21.74 0.00 21.74 0.00 21.74
May 743.83 21.71 0.00 21.71 0.00 21.71
June 716.33 21.73 0.00 21.73 0.00 21.73
July 729.33 21.76 0.00 21.76 0.00 21.76
August 705.17 21.71 0.00 21.71 0.00 21.71
September 702.17 21.71 0.33 21.71 0.33 21.71
October 718.33 21.70 0.00 21.70 0.00 21.70
November 720.00 21.71 9.00 21.70 9.00 21.70
December 744.00 21.70 11.33 21.69 11.33 21.68
             
Annual Sum or Average 8658.50 21.69 50.33 21.69 50.33 21.69
Minimum of Months 672.00 21.58 0.00 21.58 0.00 21.57
Maximum of Months 744.00 21.76 13.17 21.76 13.17 21.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 743.50 21.47 34.17 21.46 34.17 21.44
February 672.00 21.44 14.83 21.43 14.83 21.42
March 741.83 21.52 11.17 21.51 10.50 21.50
April 704.67 21.88 9.00 21.92 0.00 21.92
May 720.17 21.94 10.50 21.98 0.00 21.98
June 634.17 22.12 49.00 22.30 3.50 22.31
July 574.50 22.30 129.33 22.71 52.33 22.83
August 588.17 22.35 125.67 22.71 65.67 22.86
September 690.33 22.12 32.00 22.20 16.50 22.23
October 732.50 22.12 32.83 22.17 29.17 22.21
November 718.83 21.57 25.00 21.55 25.00 21.54
December 743.83 21.50 43.67 21.48 43.67 21.46
             
Annual Sum or Average 8264.50 21.84 517.17 21.94 295.33 21.97
Minimum of Months 574.50 21.44 9.00 21.43 0.00 21.42
Maximum of Months 743.83 22.35 129.33 22.71 65.67 22.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.68 0.00 21.68 0.00 21.68
February 672.00 21.64 0.00 21.64 0.00 21.64
March 744.00 21.47 0.00 21.47 0.00 21.47
April 720.00 21.82 0.00 21.82 0.00 21.82
May 744.00 21.88 0.00 21.88 0.00 21.88
June 720.00 22.16 14.83 22.17 14.83 22.17
July 744.00 22.51 75.17 22.52 75.17 22.53
August 744.00 22.61 100.00 22.62 100.00 22.63
September 720.00 22.40 25.67 22.40 25.67 22.40
October 744.00 22.54 28.33 22.55 28.33 22.55
November 720.00 21.96 0.00 21.96 0.00 21.96
December 744.00 21.85 0.00 21.85 0.00 21.85
             
Annual Sum or Average 8760.00 22.05 244.00 22.06 244.00 22.08
Minimum of Months 672.00 21.47 0.00 21.47 0.00 21.47
Maximum of Months 744.00 22.61 100.00 22.62 100.00 22.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 723.50 21.55 46.83 21.52 46.83 21.50
February 649.83 21.46 30.17 21.45 30.17 21.44
March 713.33 21.43 26.33 21.40 26.33 21.37
April 661.83 21.55 3.33 21.55 3.33 21.54
May 698.00 21.56 1.00 21.56 1.00 21.56
June 645.83 21.53 0.33 21.53 0.33 21.53
July 631.67 21.49 2.17 21.49 2.17 21.50
August 625.33 21.47 7.67 21.48 7.67 21.50
September 628.83 21.51 8.50 21.52 5.50 21.53
October 679.00 21.57 5.17 21.58 1.67 21.58
November 682.50 21.56 34.83 21.54 34.83 21.52
December 729.33 21.58 50.50 21.55 50.50 21.52
             
Annual Sum or Average 8069.00 21.52 216.83 21.51 210.33 21.51
Minimum of Months 625.33 21.43 0.33 21.40 0.33 21.37
Maximum of Months 729.33 21.58 50.50 21.58 50.50 21.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.37 106.50 21.32 106.50 21.28
February 669.67 21.38 47.33 21.36 47.33 21.34
March 721.67 21.40 46.33 21.42 35.17 21.39
April 599.67 21.62 76.33 21.98 7.33 22.00
May 612.17 21.69 79.00 22.07 1.33 22.08
June 537.00 22.13 140.67 22.86 36.33 23.05
July 518.50 22.42 219.83 23.30 96.67 23.54
August 518.83 22.23 220.00 23.05 97.17 23.21
September 547.00 21.85 112.83 22.26 34.83 22.29
October 676.50 21.96 57.33 22.10 36.67 22.15
November 719.00 21.54 67.50 21.51 67.50 21.48
December 744.00 21.40 115.00 21.34 115.00 21.30
             
Annual Sum or Average 7608.00 21.71 1288.67 22.02 681.83 22.06
Minimum of Months 518.50 21.37 46.33 21.32 1.33 21.28
Maximum of Months 744.00 22.42 220.00 23.30 115.00 23.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 656.83 21.54 1.00 21.54 1.00 21.54
February 626.00 21.54 1.67 21.54 1.67 21.54
March 699.67 21.51 8.17 21.50 8.17 21.50
April 697.00 21.65 0.00 21.65 0.00 21.65
May 744.00 21.64 0.00 21.64 0.00 21.64
June 720.00 21.67 0.00 21.67 0.00 21.67
July 740.50 21.73 0.50 21.73 0.50 21.73
August 689.67 21.63 2.83 21.64 2.83 21.64
September 631.00 21.51 3.50 21.52 0.17 21.52
October 645.33 21.52 7.17 21.54 0.50 21.54
November 644.17 21.58 4.17 21.59 0.67 21.59
December 656.33 21.56 0.67 21.56 0.50 21.56
             
Annual Sum or Average 8150.50 21.59 29.67 21.60 16.00 21.60
Minimum of Months 626.00 21.51 0.00 21.50 0.00 21.50
Maximum of Months 744.00 21.73 8.17 21.73 8.17 21.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 674.17 22.10 23.33 22.15 6.33 22.16
February 602.67 22.14 19.50 22.19 2.83 22.19
March 641.33 22.10 25.33 22.16 0.00 22.16
April 509.33 22.11 80.00 22.31 10.67 22.33
May 519.17 22.18 105.17 22.41 11.83 22.43
June 416.83 22.28 236.17 22.72 74.50 22.80
July 484.83 22.57 343.17 22.91 191.50 23.02
August 571.83 22.62 348.17 22.92 255.83 23.03
September 511.67 22.37 239.67 22.70 137.33 22.81
October 558.00 22.31 144.83 22.55 57.33 22.63
November 633.50 22.18 36.83 22.25 9.67 22.26
December 698.67 22.17 7.83 22.19 0.00 22.19
             
Annual Sum or Average 6822.00 22.25 1610.00 22.48 757.83 22.56
Minimum of Months 416.83 22.10 7.83 22.15 0.00 22.16
Maximum of Months 698.67 22.62 348.17 22.92 255.83 23.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 580.17 22.27 71.00 22.42 6.50 22.43
February 489.67 22.28 74.00 22.45 3.33 22.45
March 500.00 22.21 102.33 22.45 0.00 22.45
April 377.83 22.21 210.33 22.68 10.50 22.70
May 365.17 22.25 218.83 22.75 10.33 22.76
June 269.50 22.56 366.17 23.10 76.33 23.17
July 318.67 23.00 435.83 23.26 193.17 23.34
August 404.50 23.02 418.83 23.25 256.17 23.34
September 385.67 22.62 334.17 23.02 138.67 23.11
October 438.00 22.46 209.33 22.81 57.50 22.88
November 503.83 22.29 82.50 22.47 10.00 22.48
December 608.67 22.34 37.83 22.42 0.00 22.42
             
Annual Sum or Average 5241.67 22.43 2561.17 22.79 762.50 22.86
Minimum of Months 269.50 22.21 37.83 22.42 0.00 22.42
Maximum of Months 608.67 23.02 435.83 23.26 256.17 23.34



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 525.67 23.99 744.00 23.99 525.67 23.99
February 477.17 23.99 672.00 23.99 477.17 23.99
March 534.17 23.99 744.00 23.99 534.17 23.99
April 530.00 23.99 720.00 23.99 530.00 23.99
May 551.17 23.99 744.00 23.99 551.17 23.99
June 547.17 23.99 720.00 23.99 547.17 23.99
July 574.67 23.99 744.00 23.99 574.67 23.99
August 576.33 23.99 744.00 23.99 576.33 23.99
September 547.83 23.99 720.00 23.99 547.83 23.99
October 544.67 23.99 744.00 23.99 544.67 23.99
November 513.17 23.99 720.00 23.99 513.17 23.99
December 520.50 23.99 744.00 23.99 520.50 23.99
             
Annual Sum or Average 6442.50 23.99 8760.00 23.99 6442.50 23.99
Minimum of Months 477.17 23.99 672.00 23.99 477.17 23.99
Maximum of Months 576.33 23.99 744.00 23.99 576.33 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 719.00 22.60 0.00 22.60 0.00 22.60
February 671.67 22.65 0.00 22.65 0.00 22.65
March 720.17 22.49 6.17 22.51 0.00 22.51
April 561.33 23.00 28.50 23.04 2.83 23.05
May 615.00 23.11 26.50 23.14 0.00 23.14
June 285.50 23.35 229.50 23.62 20.67 23.63
July 107.33 23.78 611.33 23.93 95.17 23.91
August 130.17 23.83 668.67 23.93 127.33 23.92
September 181.50 23.41 303.33 23.73 38.17 23.72
October 401.33 23.49 177.83 23.63 33.67 23.65
November 697.17 22.99 0.00 22.99 0.00 22.99
December 739.67 22.81 0.00 22.81 0.00 22.81
             
Annual Sum or Average 5829.83 22.93 2051.83 23.19 317.83 23.22
Minimum of Months 107.33 22.49 0.00 22.51 0.00 22.51
Maximum of Months 739.67 23.83 668.67 23.93 127.33 23.92



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.14563 40.70115 0.12591 5.54667
February 672.00000 22.54907 44.55967 -0.0053 5.18301
March 744.00000 22.33215 49.03286 -0.0332 5.14275
April 720.00000 22.22840 53.31732 -0.0332 5.18720
May 744.00000 22.22454 52.72863 -1.1278 31.95323
June 720.00000 22.12331 59.37791 -1.1220 31.66931
July 744.00000 22.46704 61.55639 -0.9806 25.49330
August 744.00000 22.57913 61.97193 -0.9368 23.71540
September 720.00000 22.91153 57.82650 -0.8409 20.15741
October 744.00000 23.21378 46.96496 0.18738 5.95837
November 720.00000 23.31752 41.63178 0.17708 5.89413
December 744.00000 23.17910 35.66509 0.10126 5.47327
           
Annual Sum or Average 8760.00000 22.69090 50.46446 -0.3762 14.34010
Minimum of Months 672.00000 22.12331 35.66509 -1.1278 5.14275
Maximum of Months 744.00000 23.31752 61.97193 0.18738 31.95323



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.72021 41.72173 0.09263 6.83432
February 672.00000 22.43063 45.15767 0.02708 6.59767
March 744.00000 22.16883 49.50499 -0.0231 6.66486
April 720.00000 22.64299 52.27286 0.12590 6.45858
May 744.00000 22.25627 52.77169 -1.0415 28.96296
June 720.00000 22.61306 58.04627 -0.8719 21.78752
July 744.00000 23.14607 59.75929 -0.6575 14.65468
August 744.00000 23.44314 59.60029 -0.5395 11.78602
September 720.00000 23.32460 56.77268 -0.5912 13.66093
October 744.00000 23.34500 46.80546 0.30836 7.99246
November 720.00000 22.94418 42.55023 0.16132 6.80194
December 744.00000 22.84609 36.51896 0.09863 6.67790
           
Annual Sum or Average 8760.00000 22.82602 50.13926 -0.2442 11.60760
Minimum of Months 672.00000 22.16883 36.51896 -1.0415 6.45858
Maximum of Months 744.00000 23.44314 59.75929 0.30836 28.96296



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.40708 42.56687 0.00060 5.39351
February 672.00000 22.31186 45.48402 -0.0076 5.35380
March 744.00000 22.16737 49.73920 -0.0187 5.43040
April 720.00000 22.46853 52.91228 0.08447 5.59348
May 744.00000 22.39497 52.54875 -0.9873 26.18373
June 720.00000 22.60290 58.20057 -0.8716 21.64469
July 744.00000 22.87112 60.62512 -0.7525 17.44516
August 744.00000 22.98078 61.05777 -0.7084 16.05374
September 720.00000 22.90018 58.25927 -0.7579 17.59076
October 744.00000 22.93154 48.01684 0.17981 6.09133
November 720.00000 22.61263 43.48167 0.06178 5.41189
December 744.00000 22.52866 37.26205 -0.0014 5.27121
           
Annual Sum or Average 8760.00000 22.59996 50.86433 -0.3168 11.49335
Minimum of Months 672.00000 22.16737 37.26205 -0.9873 5.27121
Maximum of Months 744.00000 22.98078 61.05777 0.17981 26.18373



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.99970 35.07780 0.92970 24.08461
February 672.00000 23.99970 37.38874 0.94156 24.51308
March 744.00000 23.99973 41.01691 0.96771 25.49345
April 720.00000 23.99973 44.66164 1.01017 27.23427
May 744.00000 23.99971 44.08924 0.36624 9.44610
June 720.00000 23.99974 49.80241 0.42468 10.38139
July 744.00000 23.99975 52.76980 0.46201 10.94809
August 744.00000 23.99976 53.47728 0.47239 11.18956
September 720.00000 23.99976 50.66606 0.43283 10.47494
October 744.00000 23.99973 41.16261 1.00278 26.99823
November 720.00000 23.99971 36.24606 0.94561 24.71090
December 744.00000 23.99969 30.33471 0.89824 22.86653
           
Annual Sum or Average 8760.00000 23.99973 43.07931 0.73653 18.99242
Minimum of Months 672.00000 23.99969 30.33471 0.36624 9.44610
Maximum of Months 744.00000 23.99976 53.47728 1.01017 27.23427



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.25624 45.33991 0.08651 6.08983
February 672.00000 22.01193 48.55500 0.02560 5.74737
March 744.00000 21.77471 53.06635 -0.0199 5.67518
April 720.00000 21.80076 57.13761 0.02873 5.44437
May 744.00000 21.60473 57.06752 -1.1345 32.55625
June 720.00000 21.70019 63.39679 -1.0450 28.55652
July 744.00000 21.84334 66.32054 -0.9498 24.57757
August 744.00000 22.05950 66.40489 -0.8532 20.88237
September 720.00000 22.21456 62.74361 -0.8177 19.95883
October 744.00000 22.47858 51.64349 0.20798 6.79328
November 720.00000 22.32738 46.54093 0.11896 6.10728
December 744.00000 22.39473 40.00415 0.09383 6.13436
           
Annual Sum or Average 8760.00000 22.03942 54.87496 -0.3572 14.10112
Minimum of Months 672.00000 21.60473 40.00415 -1.1345 5.44437
Maximum of Months 744.00000 22.47858 66.40489 0.20798 32.55625



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.76895 44.61633 0.12459 5.71178
February 672.00000 22.62990 47.51847 0.10331 5.60638
March 744.00000 22.46540 51.75131 0.08513 5.61196
April 720.00000 22.59029 55.36163 0.14700 5.90400
May 744.00000 22.51988 54.97257 -0.9068 23.14881
June 720.00000 22.65079 60.83011 -0.8144 19.81419
July 744.00000 22.80158 63.59059 -0.7329 17.08783
August 744.00000 22.91256 64.02353 -0.6865 15.61663
September 720.00000 22.94361 60.88162 -0.6972 15.84790
October 744.00000 23.08073 50.46117 0.25679 6.78776
November 720.00000 22.89361 45.67932 0.16724 5.93518
December 744.00000 22.87710 39.45964 0.12050 5.57764
           
Annual Sum or Average 8760.00000 22.76219 53.28281 -0.2382 11.08995
Minimum of Months 672.00000 22.46540 39.45964 -0.9068 5.57764
Maximum of Months 744.00000 23.08073 64.02353 0.25679 23.14881



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.63870 47.43530 -0.2141 6.93569
February 672.00000 21.56883 50.51625 -0.2149 6.79399
March 744.00000 21.54139 53.83035 -0.2073 6.77733
April 720.00000 21.69934 54.55774 -0.1166 6.23656
May 744.00000 21.67192 54.91421 -1.2511 38.89288
June 720.00000 21.71806 56.96042 -1.1839 35.71712
July 744.00000 21.76605 56.62860 -1.1287 33.28256
August 744.00000 21.76904 56.75255 -1.1223 33.04950
September 720.00000 21.74684 56.39553 -1.1563 34.63275
October 744.00000 21.73779 50.12557 -0.1027 6.20730
November 720.00000 21.68404 47.75425 -0.1784 6.66940
December 744.00000 21.66186 42.43063 -0.2281 7.10637
           
Annual Sum or Average 8760.00000 21.68429 52.35651 -0.5944 18.59646
Minimum of Months 672.00000 21.54139 42.43063 -1.2511 6.20730
Maximum of Months 744.00000 21.76904 56.96042 -0.1027 38.89288



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.45042 49.31370 -0.2975 7.54674
February 672.00000 21.45322 51.95866 -0.2687 7.14059
March 744.00000 21.50545 55.09875 -0.2344 7.03222
April 720.00000 22.00619 54.97044 -0.0674 6.74368
May 744.00000 22.10283 54.08104 -1.1328 34.59238
June 720.00000 22.60341 55.67251 -0.9268 27.52348
July 744.00000 22.88407 55.93537 -0.8006 23.30302
August 744.00000 22.79214 57.26590 -0.8310 23.83463
September 720.00000 22.34967 57.65656 -1.0023 28.77917
October 744.00000 22.17349 51.31844 -0.0367 6.30845
November 720.00000 21.61484 49.86199 -0.2290 6.90089
December 744.00000 21.49212 43.76467 -0.3144 7.70114
           
Annual Sum or Average 8760.00000 22.03926 53.06795 -0.5133 15.66638
Minimum of Months 672.00000 21.45042 43.76467 -1.1328 6.30845
Maximum of Months 744.00000 22.88407 57.65656 -0.0367 34.59238



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.38720 45.30394 -0.3302 7.58178
February 672.00000 21.38660 48.18927 -0.3064 7.16479
March 744.00000 21.41622 51.57490 -0.2769 6.83586
April 720.00000 21.62727 53.70415 -0.1978 6.20351
May 744.00000 21.74787 52.57930 -1.3014 40.81299
June 720.00000 22.11260 56.06867 -1.1397 33.38357
July 744.00000 22.33724 58.57140 -1.0387 29.12819
August 744.00000 22.26246 59.99046 -1.0643 30.10424
September 720.00000 21.95462 58.19208 -1.1924 35.59532
October 744.00000 21.92587 49.52629 -0.1397 6.12334
November 720.00000 21.42863 46.59687 -0.3023 7.18718
December 744.00000 21.37445 40.02063 -0.3637 7.97187
           
Annual Sum or Average 8760.00000 21.74934 51.70062 -0.6397 18.23838
Minimum of Months 672.00000 21.37445 40.02063 -1.3014 6.12334
Maximum of Months 744.00000 22.33724 59.99046 -0.1397 40.81299



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.68877 47.18529 -0.2004 6.78939
February 672.00000 21.58347 50.58477 -0.2150 6.76441
March 744.00000 21.58680 53.42724 -0.1998 6.72072
April 720.00000 21.73709 54.34171 -0.1143 6.21434
May 744.00000 21.70793 54.67857 -1.2540 39.00453
June 720.00000 21.73455 57.38342 -1.1947 36.18978
July 744.00000 21.79264 56.69944 -1.1326 33.46239
August 744.00000 21.79485 56.56821 -1.1215 33.01661
September 720.00000 21.74557 57.18988 -1.1724 35.30971
October 744.00000 21.75210 50.33723 -0.1022 6.16534
November 720.00000 21.70936 47.96828 -0.1761 6.58908
December 744.00000 21.69646 42.36656 -0.2207 6.98046
           
Annual Sum or Average 8760.00000 21.71162 52.38907 -0.5943 18.67072
Minimum of Months 672.00000 21.58347 42.36656 -1.2540 6.16534
Maximum of Months 744.00000 21.79485 57.38342 -0.1022 39.00453



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.47349 48.86420 -0.2901 7.32777
February 672.00000 21.43819 51.95852 -0.2768 7.04526
March 744.00000 21.52625 54.71699 -0.2329 6.85843
April 720.00000 21.93951 55.11881 -0.0871 6.23561
May 744.00000 22.02217 54.59427 -1.1673 35.29393
June 720.00000 22.37054 57.09708 -1.0067 28.83527
July 744.00000 22.69142 57.11319 -0.8646 23.98628
August 744.00000 22.66103 58.09780 -0.8722 24.16025
September 720.00000 22.20748 59.31019 -1.0579 30.43208
October 744.00000 22.15574 51.69854 -0.0435 6.08659
November 720.00000 21.57078 49.93659 -0.2439 6.79418
December 744.00000 21.50413 43.77873 -0.3117 7.49093
           
Annual Sum or Average 8760.00000 21.96707 53.51642 -0.5394 15.92743
Minimum of Months 672.00000 21.43819 43.77873 -1.1673 6.08659
Maximum of Months 744.00000 22.69142 59.31019 -0.0435 35.29393



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.59723 48.74414 -0.2389 7.34320
February 672.00000 21.51963 51.98386 -0.2394 7.17509
March 744.00000 21.50380 55.38093 -0.2242 7.12625
April 720.00000 21.69124 55.96139 -0.1160 6.41420
May 744.00000 21.66868 56.21226 -1.2534 39.25702
June 720.00000 21.71681 58.15366 -1.1771 35.62246
July 744.00000 21.76482 57.50481 -1.1187 33.04665
August 744.00000 21.76448 57.84911 -1.1153 32.94829
September 720.00000 21.73598 58.09890 -1.1567 34.86230
October 744.00000 21.71925 51.47311 -0.1107 6.40367
November 720.00000 21.64870 49.16329 -0.1996 6.99520
December 744.00000 21.61612 43.55754 -0.2567 7.55547
           
Annual Sum or Average 8760.00000 21.66301 53.66916 -0.6028 18.79952
Minimum of Months 672.00000 21.50380 43.55754 -1.2534 6.40367
Maximum of Months 744.00000 21.76482 58.15366 -0.1107 39.25702



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.37246 50.81183 -0.3343 8.14392
February 672.00000 21.38688 53.60239 -0.2993 7.64777
March 744.00000 21.48256 56.70371 -0.2493 7.43759
April 720.00000 22.07470 55.96494 -0.0505 7.23589
May 744.00000 22.16991 54.92168 -1.1106 34.55143
June 720.00000 22.73954 55.73028 -0.8744 27.29023
July 744.00000 23.03553 55.33323 -0.7398 23.06622
August 744.00000 22.90400 56.96972 -0.7857 23.67074
September 720.00000 22.38162 58.71386 -0.9872 28.85875
October 744.00000 22.13131 52.58001 -0.0487 6.56700
November 720.00000 21.54625 51.53642 -0.2604 7.36668
December 744.00000 21.39634 45.05136 -0.3586 8.42483
           
Annual Sum or Average 8760.00000 22.05576 53.98014 -0.5096 15.90246
Minimum of Months 672.00000 21.37246 45.05136 -1.1106 6.56700
Maximum of Months 744.00000 23.03553 58.71386 -0.0487 34.55143



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.75353 45.73870 -0.1479 6.78066
February 672.00000 21.66683 49.17223 -0.1773 6.74627
March 744.00000 21.62229 52.28443 -0.1905 6.82630
April 720.00000 21.70502 54.41250 -0.1371 6.40050
May 744.00000 21.63506 56.10918 -1.3157 42.03585
June 720.00000 21.66891 59.75834 -1.2568 39.09473
July 744.00000 21.73833 60.02306 -1.1970 36.37863
August 744.00000 21.75351 58.85237 -1.1707 35.26882
September 720.00000 21.73402 56.50136 -1.1822 35.96494
October 744.00000 21.75680 49.66110 -0.0929 6.38208
November 720.00000 21.76706 46.14112 -0.1349 6.66364
December 744.00000 21.76757 41.19605 -0.1616 6.95640
           
Annual Sum or Average 8760.00000 21.71441 52.49598 -0.5996 19.70438
Minimum of Months 672.00000 21.62229 41.19605 -1.3157 6.38208
Maximum of Months 744.00000 21.76757 60.02306 -0.0929 42.03585



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.21534 45.40423 0.04759 5.76166
February 672.00000 22.26863 47.89914 0.08023 5.73793
March 744.00000 22.26964 51.92650 0.10740 5.81034
April 720.00000 22.44686 55.43119 0.19524 6.33929
May 744.00000 22.52293 54.61944 -0.7782 18.64398
June 720.00000 22.66863 60.41498 -0.6672 15.23534
July 744.00000 22.73259 63.38241 -0.6101 13.60900
August 744.00000 22.70334 64.25688 -0.6187 13.92470
September 720.00000 22.60848 61.53608 -0.6878 15.86848
October 744.00000 22.56540 51.32163 0.21153 6.63349
November 720.00000 22.32273 46.49866 0.09127 5.84279
December 744.00000 22.24721 40.18673 0.02425 5.61380
           
Annual Sum or Average 8760.00000 22.46540 53.59352 -0.2189 9.94286
Minimum of Months 672.00000 22.21534 40.18673 -0.7782 5.61380
Maximum of Months 744.00000 22.73259 64.25688 0.21153 18.64398



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.52848 44.75023 0.14430 6.11942
February 672.00000 22.58460 47.17474 0.17757 6.26143
March 744.00000 22.59771 51.10855 0.20865 6.44737
April 720.00000 22.73764 54.62963 0.28487 7.19030
May 744.00000 22.81057 53.82679 -0.6528 14.75455
June 720.00000 22.92780 59.58851 -0.5534 12.19285
July 744.00000 22.97587 62.56518 -0.5037 11.01499
August 744.00000 22.93897 63.44760 -0.5152 11.34813
September 720.00000 22.85305 60.74342 -0.5808 12.91480
October 744.00000 22.81005 50.68459 0.28719 7.37700
November 720.00000 22.61305 45.86183 0.18051 6.34524
December 744.00000 22.54689 39.64300 0.11657 5.88026
           
Annual Sum or Average 8760.00000 22.74460 52.85589 -0.1191 9.00222
Minimum of Months 672.00000 22.52848 39.64300 -0.6528 5.88026
Maximum of Months 744.00000 22.97587 63.44760 0.28719 14.75455



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.99120 42.43890 1.12307 33.03161
February 672.00000 23.99118 44.61655 1.13643 33.56958
March 744.00000 23.99120 48.12423 1.16463 34.85888
April 720.00000 23.99139 51.63407 1.22213 37.55280
May 744.00000 23.99135 51.07287 0.64759 17.20505
June 720.00000 23.99174 56.58635 0.71551 19.07895
July 744.00000 23.99196 59.45047 0.76415 20.52845
August 744.00000 23.99194 60.11841 0.76845 20.62408
September 720.00000 23.99161 57.37441 0.71751 19.09290
October 744.00000 23.99131 48.19820 1.21106 37.08068
November 720.00000 23.99121 43.50806 1.14005 33.76346
December 744.00000 23.99105 37.81815 1.09216 31.66121
           
Annual Sum or Average 8760.00000 23.99143 50.09920 0.97419 28.13501
Minimum of Months 672.00000 23.99105 37.81815 0.64759 17.20505
Maximum of Months 744.00000 23.99196 60.11841 1.22213 37.55280



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.24111 42.04264 -0.3138 7.29737
February 672.00000 21.19210 45.04870 -0.3089 7.10103
March 744.00000 21.13064 49.43684 -0.3006 6.99844
April 720.00000 21.32843 53.14996 -0.2232 6.19295
May 744.00000 21.43073 52.22280 -1.3504 42.95417
June 720.00000 21.70829 57.95725 -1.2154 36.08142
July 744.00000 21.92368 60.78160 -1.1196 31.47233
August 744.00000 21.91732 61.67097 -1.1168 31.33480
September 720.00000 21.78943 58.75696 -1.1809 34.43132
October 744.00000 21.87516 47.59428 -0.1133 5.55092
November 720.00000 21.40627 43.14833 -0.2624 6.63201
December 744.00000 21.29873 36.42269 -0.3310 7.45476
           
Annual Sum or Average 8760.00000 21.52244 50.70429 -0.6551 18.69563
Minimum of Months 672.00000 21.13064 36.42269 -1.3504 5.55092
Maximum of Months 744.00000 21.92368 61.67097 -0.1133 42.95417



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.67841 45.29850 -0.2270 6.35014
February 672.00000 21.63626 48.29227 -0.2208 6.12464
March 744.00000 21.47258 52.69906 -0.2350 6.34748
April 720.00000 21.82185 55.92203 -0.1265 5.53404
May 744.00000 21.87824 55.20247 -1.2419 37.46190
June 720.00000 22.15891 60.78922 -1.1075 31.00361
July 744.00000 22.51139 63.08862 -0.9661 24.78093
August 744.00000 22.60911 63.60778 -0.9279 23.22851
September 720.00000 22.40270 61.05612 -1.0181 27.00708
October 744.00000 22.53755 50.22024 0.02267 5.29728
November 720.00000 21.96162 46.20356 -0.1500 5.63430
December 744.00000 21.84887 39.67549 -0.2187 6.14767
           
Annual Sum or Average 8760.00000 22.04600 53.52019 -0.5366 15.46546
Minimum of Months 672.00000 21.47258 39.67549 -1.2419 5.29728
Maximum of Months 744.00000 22.60911 63.60778 0.02267 37.46190



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.63988 43.10817 0.00052 5.66419
February 672.00000 22.65326 45.83537 0.02016 5.31495
March 744.00000 22.53383 49.81645 0.01726 5.57057
April 720.00000 23.17787 52.09222 0.19751 6.24624
May 744.00000 23.22909 51.46856 -0.7860 18.53686
June 720.00000 23.64933 56.13264 -0.5998 12.85421
July 744.00000 23.90470 58.30128 -0.4840 9.95826
August 744.00000 23.91546 59.01027 -0.4735 9.73426
September 720.00000 23.73735 56.77772 -0.5602 11.81405
October 744.00000 23.68036 47.24976 0.30127 7.23562
November 720.00000 23.01292 43.81283 0.09908 5.51764
December 744.00000 22.81154 37.89206 0.00867 5.33310
           
Annual Sum or Average 8760.00000 23.24870 50.13725 -0.1897 8.67069
Minimum of Months 672.00000 22.53383 37.89206 -0.7860 5.31495
Maximum of Months 744.00000 23.91546 59.01027 0.30127 18.53686



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.77526 47.73555 0.26017 6.53821
February 672.00000 23.81570 50.17602 0.28254 6.74704
March 744.00000 23.71115 54.54524 0.28449 6.80620
April 720.00000 23.92919 53.61989 0.33982 7.47230
May 744.00000 23.97981 50.88032 -0.6038 12.68006
June 720.00000 23.99993 53.81263 -0.5523 11.40606
July 744.00000 23.99993 56.14474 -0.5178 10.61729
August 744.00000 23.99992 57.13829 -0.5119 10.48667
September 720.00000 23.99993 54.40169 -0.5411 11.18006
October 744.00000 23.99993 44.96606 0.32922 7.38897
November 720.00000 23.97066 44.91125 0.29505 6.94436
December 744.00000 23.88648 41.34597 0.24511 6.36383
           
Annual Sum or Average 8760.00000 23.92262 50.80201 -0.0597 8.72964
Minimum of Months 672.00000 23.71115 41.34597 -0.6038 6.36383
Maximum of Months 744.00000 23.99993 57.13829 0.33982 12.68006



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.283493E+11 75500.98 15-JAN-09:52 665.92 0.125604E+12 0.00 0.153953E+12 4.12 4.72 01-JAN-00:10 0.00 0.00
February 0.185276E+11 74933.53 01-FEB-09:51 617.87 0.838136E+11 0.00 0.102341E+12 4.26 4.72 01-FEB-05:50 0.00 0.00
March 0.191510E+11 68737.83 11-MAR-09:51 641.42 0.859969E+11 0.00 0.105148E+12 4.00 4.72 01-MAR-06:50 0.00 0.00
April 0.360588E+11 66284.78 26-APR-10:35 711.07 0.159191E+12 0.00 0.195249E+12 4.51 4.72 02-APR-00:30 0.00 0.00
May 0.362378E+11 49521.87 03-MAY-09:50 741.97 0.161103E+12 0.00 0.197341E+12 4.55 4.72 02-MAY-00:10 0.00 0.00
June 0.596011E+11 93658.02 29-JUN-18:03 720.00 0.261099E+12 0.00 0.320701E+12 4.47 4.72 01-JUN-01:40 0.00 0.00
July 0.109448E+12 124890.27 19-JUL-15:13 744.00 0.471473E+12 0.00 0.580921E+12 4.39 4.71 06-JUL-01:40 0.00 0.00
August 0.121929E+12 130263.47 17-AUG-15:13 744.00 0.525393E+12 0.00 0.647322E+12 4.38 4.67 28-AUG-03:00 0.00 0.00
September 0.806651E+11 135170.31 29-SEP-15:13 720.00 0.346512E+12 0.00 0.427177E+12 4.43 4.72 03-SEP-01:30 0.00 0.00
October 0.896856E+11 139179.17 14-OCT-15:13 744.00 0.376844E+12 0.00 0.466530E+12 4.40 4.72 08-OCT-00:20 0.00 0.00
November 0.303632E+11 92673.28 19-NOV-09:41 698.50 0.135154E+12 0.00 0.165517E+12 4.46 4.72 01-NOV-03:40 0.00 0.00
December 0.317632E+11 85433.32 05-DEC-09:41 691.67 0.139956E+12 0.00 0.171719E+12 4.27 4.72 01-DEC-00:20 0.00 0.00
                         
Annual Sum or Average 0.661780E+12     8440.42 0.287214E+13 0.00 0.353392E+13 4.35     0.00 0.00
Minimum of Months 0.185276E+11 49521.87   617.87 0.838136E+11 0.00 0.102341E+12 4.00 4.67   0.00 0.00
Maximum of Months 0.121929E+12 139179.17   744.00 0.525393E+12 0.00 0.647322E+12 4.55 4.72   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.268428E+11 0.00 549.11 109821.79 08-JAN-06:50 0.00 42.59 55.88 0.11 0.00 0.04 0.43 08-JAN-06:50
February 0.131546E+11 0.00 516.30 65892.00 05-FEB-06:00 0.00 43.19 56.21 0.07 0.00 0.02 0.26 05-FEB-06:00
March 0.237652E+11 0.00 621.59 90282.33 30-MAR-03:00 0.00 42.26 57.16 0.10 0.00 0.03 0.35 30-MAR-03:00
April 0.522742E+10 0.00 446.77 44725.14 01-APR-06:00 0.00 42.18 53.08 0.03 0.00 0.01 0.17 01-APR-06:00
May 0.537076E+10 0.00 501.89 33662.67 14-MAY-04:50 0.00 38.22 52.39 0.03 0.00 0.01 0.13 14-MAY-04:50
June 0.119904E+10 0.00 288.38 17838.87 02-JUN-08:54 0.00 32.55 42.86 0.00 0.00 0.00 0.07 02-JUN-08:54
July 0.258126E+09 0.00 98.57 17667.72 08-JUL-08:56 0.00 28.63 32.73 0.00 0.00 0.00 0.07 08-JUL-08:56
August 73204637.18 0.00 25.43 15643.33 22-AUG-08:54 0.00 35.54 36.39 0.00 0.00 0.00 0.06 22-AUG-08:54
September 0.458025E+09 0.00 83.05 16849.94 08-SEP-08:54 0.00 37.70 40.15 0.00 0.00 0.00 0.07 08-SEP-08:54
October 0.177241E+10 0.00 169.68 18525.63 30-OCT-04:00 0.00 40.88 45.17 0.01 0.00 0.00 0.07 30-OCT-04:00
November 0.981777E+10 0.00 430.25 44668.18 24-NOV-04:00 0.00 43.33 53.57 0.05 0.00 0.01 0.17 24-NOV-04:00
December 0.215121E+11 0.00 496.69 68400.72 23-DEC-06:00 0.00 42.98 54.93 0.09 0.00 0.03 0.27 23-DEC-06:00
                           
Annual Sum or Average 0.109451E+12 0.00 4227.72     0.00 39.14 48.32 0.04 0.00 0.01    
Minimum of Months 73204637.18 0.00 25.43 15643.33   0.00 28.63 32.73 0.00 0.00 0.00 0.06  
Maximum of Months 0.268428E+11 0.00 621.59 109821.79   0.00 43.33 57.16 0.11 0.00 0.04 0.43  



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.325784E+10 0.00 159.67 0.323482E+10 0.00 0.00 0.00 0.00 20570.98 13-JAN-14:00 20570.98 13-JAN-14:00 0.00 0.00 0.00
February 0.176477E+10 0.00 122.33 0.171146E+10 0.00 0.00 0.00 0.00 17583.23 01-FEB-09:54 17583.23 01-FEB-09:54 0.00 0.00 0.00
March 0.195362E+10 0.00 100.67 0.180527E+10 0.00 0.00 0.00 0.00 22012.17 22-MAR-13:00 17611.20 11-MAR-13:15 0.00 0.00 0.00
April 0.490019E+10 0.00 196.33 0.461280E+10 0.00 0.00 0.00 0.00 22090.96 26-APR-13:00 22090.96 26-APR-13:00 0.00 0.00 0.00
May 0.521145E+10 0.00 255.83 0.512070E+10 0.00 0.00 0.00 0.00 18829.64 04-MAY-13:00 17662.38 03-MAY-12:15 0.00 0.00 0.00
June 0.118888E+11 0.00 440.50 0.944939E+10 0.00 0.00 0.00 0.00 30817.80 29-JUN-12:15 17826.82 29-JUN-12:15 0.00 0.00 0.00
July 0.270220E+11 0.00 560.33 0.158139E+11 0.00 0.00 0.00 0.00 40153.36 31-JUL-12:30 23766.73 31-JUL-12:30 0.00 0.00 0.00
August 0.309007E+11 0.00 562.17 0.166894E+11 0.00 0.00 0.00 0.00 38591.89 18-AUG-12:20 22286.10 18-AUG-12:20 0.00 0.00 0.00
September 0.175428E+11 0.00 498.50 0.122681E+11 0.00 0.00 0.00 0.00 39619.58 22-SEP-12:15 35123.90 29-SEP-13:00 0.00 0.00 0.00
October 0.195118E+11 0.00 442.00 0.143145E+11 0.00 0.00 0.00 0.00 38111.08 01-OCT-12:15 34150.37 16-OCT-12:20 0.00 0.00 0.00
November 0.327790E+10 0.00 196.50 0.321606E+10 0.00 0.00 0.00 0.00 21037.50 19-NOV-13:15 21037.50 19-NOV-13:15 0.00 0.00 0.00
December 0.398719E+10 0.00 167.83 0.398507E+10 0.00 0.00 0.00 0.00 20480.92 05-DEC-09:55 20480.92 05-DEC-09:55 0.00 0.00 0.00
                               
Annual Sum or Average 0.131219E+12 0.00 3702.67 0.922214E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.176477E+10 0.00 100.67 0.171146E+10 0.00 0.00 0.00 0.00 17583.23   17583.23   0.00 0.00 0.00
Maximum of Months 0.309007E+11 0.00 562.17 0.166894E+11 0.00 0.00 0.00 0.00 40153.36   35123.90   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.635666E+11 0.00 295.89 0.632618E+11 0.00 0.00 0.00 0.00 199203.88 14-JAN-11:35 199203.88 14-JAN-11:35 0.00 0.00 0.00
February 0.367906E+11 0.00 249.12 0.358442E+11 0.00 0.00 0.00 0.00 190281.20 01-FEB-11:50 190281.20 01-FEB-11:50 0.00 0.00 0.00
March 0.406281E+11 0.00 226.14 0.397415E+11 0.00 0.00 0.00 0.00 192046.58 23-MAR-10:50 179692.08 11-MAR-11:35 0.00 0.00 0.00
April 0.939448E+11 0.00 366.59 0.918197E+11 0.00 0.00 0.00 0.00 239516.10 26-APR-10:35 200123.91 30-APR-10:50 0.00 0.00 0.00
May 0.101202E+12 0.00 444.92 0.998370E+11 0.00 0.00 0.00 0.00 168657.85 18-MAY-10:50 162021.71 04-MAY-12:00 0.00 0.00 0.00
June 0.181922E+12 0.00 616.33 0.158926E+12 0.00 0.00 0.00 0.00 305437.22 29-JUN-18:03 185914.62 29-JUN-10:50 0.00 0.00 0.00
July 0.352875E+12 0.00 735.50 0.236304E+12 0.00 0.00 0.00 0.00 358736.16 31-JUL-18:20 219722.81 19-JUL-10:50 0.00 0.00 0.00
August 0.395622E+12 0.00 736.67 0.245998E+12 0.00 0.00 0.00 0.00 350035.22 14-AUG-10:35 219522.85 14-AUG-10:50 0.00 0.00 0.00
September 0.241649E+12 0.00 676.00 0.185232E+12 0.00 0.00 0.00 0.00 345734.71 22-SEP-10:35 304294.93 29-SEP-10:50 0.00 0.00 0.00
October 0.264660E+12 0.00 620.50 0.213968E+12 0.00 0.00 0.00 0.00 330532.01 04-OCT-18:07 316773.04 16-OCT-10:50 0.00 0.00 0.00
November 0.669939E+11 0.00 358.97 0.659549E+11 0.00 0.00 0.00 0.00 206782.26 19-NOV-11:35 206782.26 19-NOV-11:35 0.00 0.00 0.00
December 0.726079E+11 0.00 310.20 0.726079E+11 0.00 0.00 0.00 0.00 188951.31 19-DEC-11:35 188951.31 19-DEC-11:35 0.00 0.00 0.00
                               
Annual Sum or Average 0.191246E+13 0.00 5636.82 0.150949E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.367906E+11 0.00 226.14 0.358442E+11 0.00 0.00 0.00 0.00 168657.85   162021.71   0.00 0.00 0.00
Maximum of Months 0.395622E+12 0.00 736.67 0.245998E+12 0.00 0.00 0.00 0.00 358736.16   316773.04   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.199060E+10 0.00 422.94 0.100768E+10 0.00 0.00 0.00 0.00 13498.48 21-JAN-09:01 13016.62 14-JAN-16:11 0.00 0.00 0.00
February 0.176972E+10 0.00 351.94 0.959923E+09 0.00 0.00 0.00 0.00 13013.55 06-FEB-16:11 13013.55 06-FEB-16:11 0.00 0.00 0.00
March 0.192472E+10 0.00 362.68 0.894336E+09 0.00 0.00 0.00 0.00 12934.99 18-MAR-08:62 11794.56 05-MAR-16:11 0.00 0.00 0.00
April 0.386185E+10 0.00 559.73 0.186345E+10 0.00 0.00 0.00 0.00 13232.20 08-APR-08:61 12684.89 01-APR-18:02 0.00 0.00 0.00
May 0.359013E+10 0.00 561.87 0.163179E+10 0.00 0.00 0.00 0.00 13480.33 06-MAY-08:62 12402.07 24-MAY-08:61 0.00 0.00 0.00
June 0.509254E+10 0.00 605.44 0.236927E+10 0.00 0.00 0.00 0.00 13304.03 28-JUN-08:62 11839.66 18-JUN-18:01 0.00 0.00 0.00
July 0.717098E+10 0.00 677.99 0.353203E+10 0.00 0.00 0.00 0.00 13808.12 28-JUL-08:61 11759.07 17-JUL-18:01 0.00 0.00 0.00
August 0.742449E+10 0.00 688.06 0.369212E+10 0.00 0.00 0.00 0.00 14115.07 06-AUG-08:61 11853.98 17-AUG-18:02 0.00 0.00 0.00
September 0.582700E+10 0.00 647.52 0.278263E+10 0.00 0.00 0.00 0.00 13910.19 22-SEP-08:61 11806.78 16-SEP-18:01 0.00 0.00 0.00
October 0.527719E+10 0.00 639.68 0.306802E+10 0.00 0.00 0.00 0.00 13917.24 01-OCT-08:62 13017.22 25-OCT-18:01 0.00 0.00 0.00
November 0.266970E+10 0.00 501.80 0.139116E+10 0.00 0.00 0.00 0.00 13775.65 12-NOV-09:02 13014.14 30-NOV-16:11 0.00 0.00 0.00
December 0.223747E+10 0.00 447.02 0.150562E+10 0.00 0.00 0.00 0.00 13018.01 30-DEC-16:11 13018.01 30-DEC-16:11 0.00 0.00 0.00
                               
Annual Sum or Average 0.488364E+11 0.00 6466.68 0.246980E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.176972E+10 0.00 351.94 0.894336E+09 0.00 0.00 0.00 0.00 12934.99   11759.07   0.00 0.00 0.00
Maximum of Months 0.742449E+10 0.00 688.06 0.369212E+10 0.00 0.00 0.00 0.00 14115.07   13018.01   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.401088E+09 0.00 165.94 0.168981E+09 0.00 0.00 0.00 0.00 12891.70 21-JAN-09:01 11916.66 09-JAN-16:11 0.00 0.00 0.00
February 0.573449E+09 0.00 182.30 0.237544E+09 0.00 0.00 0.00 0.00 12497.99 06-FEB-16:11 12497.99 06-FEB-16:11 0.00 0.00 0.00
March 0.832709E+09 0.00 226.95 0.300065E+09 0.00 0.00 0.00 0.00 12750.07 22-MAR-18:51 11118.96 06-MAR-16:11 0.00 0.00 0.00
April 0.220467E+10 0.00 415.42 0.815301E+09 0.00 0.00 0.00 0.00 13535.38 26-APR-21:51 12331.67 28-APR-17:31 0.00 0.00 0.00
May 0.243130E+10 0.00 431.33 0.943386E+09 0.00 0.00 0.00 0.00 13148.39 02-MAY-21:51 11950.56 24-MAY-08:51 0.00 0.00 0.00
June 0.324210E+10 0.00 398.34 0.139007E+10 0.00 0.00 0.00 0.00 14066.83 28-JUN-21:51 11450.22 04-JUN-19:31 0.00 0.00 0.00
July 0.463825E+10 0.00 419.69 0.229558E+10 0.00 0.00 0.00 0.00 14175.74 27-JUL-21:51 10985.95 08-JUL-21:11 0.00 0.00 0.00
August 0.438383E+10 0.00 414.33 0.207807E+10 0.00 0.00 0.00 0.00 14112.64 19-AUG-08:51 10835.95 21-AUG-20:11 0.00 0.00 0.00
September 0.312233E+10 0.00 396.69 0.126745E+10 0.00 0.00 0.00 0.00 13630.85 30-SEP-21:51 11072.58 19-SEP-19:01 0.00 0.00 0.00
October 0.240236E+10 0.00 385.70 0.123658E+10 0.00 0.00 0.00 0.00 13986.96 01-OCT-08:52 12851.33 14-OCT-08:61 0.00 0.00 0.00
November 0.742539E+09 0.00 270.32 0.272445E+09 0.00 0.00 0.00 0.00 13200.56 12-NOV-09:02 11969.61 28-NOV-19:01 0.00 0.00 0.00
December 0.420934E+09 0.00 180.53 0.251463E+09 0.00 0.00 0.00 0.00 12705.82 09-DEC-16:11 12169.16 19-DEC-19:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.253956E+11 0.00 3887.53 0.112569E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.401088E+09 0.00 165.94 0.168981E+09 0.00 0.00 0.00 0.00 12497.99   10835.95   0.00 0.00 0.00
Maximum of Months 0.463825E+10 0.00 431.33 0.229558E+10 0.00 0.00 0.00 0.00 14175.74   12851.33   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.322250E+11 0.00 573.88 0.219814E+11 0.00 0.00 0.00 0.00 44100.64 14-JAN-12:40 39493.50 06-JAN-13:30 0.00 0.00 0.00
February 0.204396E+11 0.00 421.50 0.133429E+11 0.00 0.00 0.00 0.00 39373.30 02-FEB-12:30 37882.05 02-FEB-12:40 0.00 0.00 0.00
March 0.150588E+11 0.00 418.35 0.635206E+10 0.00 0.00 0.00 0.00 32231.35 11-MAR-13:10 27208.57 11-MAR-13:10 0.00 0.00 0.00
April 0.167383E+11 0.00 515.92 0.570976E+10 0.00 0.00 0.00 0.00 24049.56 08-APR-12:40 13600.76 08-APR-12:50 0.00 0.00 0.00
May 0.928162E+10 0.00 458.36 0.213320E+10 0.00 0.00 0.00 0.00 17223.97 04-MAY-12:30 7149.02 04-MAY-12:30 0.00 0.00 0.00
June 0.126085E+11 0.00 530.17 0.292769E+10 0.00 0.00 0.00 0.00 17116.76 30-JUN-06:52 5984.50 30-JUN-06:52 0.00 0.00 0.00
July 0.203889E+11 0.00 663.63 0.578922E+10 0.00 0.00 0.00 0.00 20394.87 30-JUL-08:00 8122.04 30-JUL-08:00 0.00 0.00 0.00
August 0.280750E+11 0.00 731.33 0.984033E+10 0.00 0.00 0.00 0.00 23027.72 30-AUG-12:50 12399.43 30-AUG-13:00 0.00 0.00 0.00
September 0.313742E+11 0.00 701.25 0.138728E+11 0.00 0.00 0.00 0.00 40394.25 30-SEP-13:05 38788.08 30-SEP-11:40 0.00 0.00 0.00
October 0.399785E+11 0.00 691.93 0.253145E+11 0.00 0.00 0.00 0.00 49006.30 16-OCT-12:20 45667.75 16-OCT-12:20 0.00 0.00 0.00
November 0.332423E+11 0.00 599.42 0.221390E+11 0.00 0.00 0.00 0.00 46466.11 19-NOV-12:30 40925.71 29-NOV-12:30 0.00 0.00 0.00
December 0.365154E+11 0.00 601.48 0.282200E+11 0.00 0.00 0.00 0.00 44779.26 19-DEC-13:00 44779.26 19-DEC-13:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.295926E+12 0.00 6907.21 0.157623E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.928162E+10 0.00 418.35 0.213320E+10 0.00 0.00 0.00 0.00 17116.76   5984.50   0.00 0.00 0.00
Maximum of Months 0.399785E+11 0.00 731.33 0.282200E+11 0.00 0.00 0.00 0.00 49006.30   45667.75   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.907000E+10 0.00 296.93 0.439460E+10 0.00 0.00 0.00 0.00 74058.69 20-JAN-19:01 70813.13 16-JAN-09:02 0.00 0.00 0.00
February 0.105933E+11 0.00 362.66 0.479933E+10 0.00 0.00 0.00 0.00 72168.64 13-FEB-21:12 69721.84 05-FEB-09:01 0.00 0.00 0.00
March 0.135104E+11 0.00 376.76 0.584589E+10 0.00 0.00 0.00 0.00 71369.81 22-MAR-18:51 63592.45 04-MAR-09:01 0.00 0.00 0.00
April 0.204628E+11 0.00 396.58 0.991881E+10 0.00 0.00 0.00 0.00 77227.40 26-APR-21:51 68538.23 01-APR-21:53 0.00 0.00 0.00
May 0.243965E+11 0.00 393.52 0.130178E+11 0.00 0.00 0.00 0.00 75657.80 04-MAY-21:51 68332.24 24-MAY-08:51 0.00 0.00 0.00
June 0.278546E+11 0.00 333.20 0.158679E+11 0.00 0.00 0.00 0.00 80304.64 28-JUN-21:51 65751.96 22-JUN-20:11 0.00 0.00 0.00
July 0.335664E+11 0.00 355.56 0.197103E+11 0.00 0.00 0.00 0.00 81639.85 19-JUL-21:51 66313.25 18-JUL-18:01 0.00 0.00 0.00
August 0.309877E+11 0.00 338.31 0.173552E+11 0.00 0.00 0.00 0.00 80939.31 16-AUG-21:51 62780.44 14-AUG-15:12 0.00 0.00 0.00
September 0.239180E+11 0.00 312.47 0.124068E+11 0.00 0.00 0.00 0.00 80382.99 22-SEP-21:52 63219.12 19-SEP-19:01 0.00 0.00 0.00
October 0.212731E+11 0.00 340.01 0.133279E+11 0.00 0.00 0.00 0.00 80373.69 01-OCT-08:52 74703.77 15-OCT-07:41 0.00 0.00 0.00
November 0.120257E+11 0.00 370.15 0.585158E+10 0.00 0.00 0.00 0.00 73522.71 09-NOV-22:53 70086.65 28-NOV-19:01 0.00 0.00 0.00
December 0.830944E+10 0.00 307.87 0.488882E+10 0.00 0.00 0.00 0.00 70285.34 19-DEC-19:01 70285.34 19-DEC-19:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.235968E+12 0.00 4184.03 0.127385E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.830944E+10 0.00 296.93 0.439460E+10 0.00 0.00 0.00 0.00 70285.34   62780.44   0.00 0.00 0.00
Maximum of Months 0.335664E+11 0.00 396.58 0.197103E+11 0.00 0.00 0.00 0.00 81639.85   74703.77   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.210977E+10 0.00 443.72 0.118809E+10 0.00 0.00 0.00 0.00 11538.85 05-JAN-09:01 11538.85 05-JAN-09:01 0.00 0.00 0.00
February 0.165654E+10 0.00 335.36 0.944673E+09 0.00 0.00 0.00 0.00 11689.42 14-FEB-09:01 11537.60 05-FEB-09:01 0.00 0.00 0.00
March 0.188798E+10 0.00 366.35 0.883551E+09 0.00 0.00 0.00 0.00 11530.08 17-MAR-08:61 10432.34 24-MAR-15:11 0.00 0.00 0.00
April 0.348887E+10 0.00 570.53 0.166980E+10 0.00 0.00 0.00 0.00 11535.84 02-APR-08:61 11535.84 02-APR-08:61 0.00 0.00 0.00
May 0.305072E+10 0.00 556.45 0.138714E+10 0.00 0.00 0.00 0.00 12103.56 06-MAY-08:62 11531.36 24-MAY-08:61 0.00 0.00 0.00
June 0.426441E+10 0.00 620.41 0.189385E+10 0.00 0.00 0.00 0.00 11924.45 28-JUN-08:62 10494.73 20-JUN-15:11 0.00 0.00 0.00
July 0.650447E+10 0.00 702.05 0.311145E+10 0.00 0.00 0.00 0.00 11740.67 13-JUL-18:01 10515.57 02-JUL-08:61 0.00 0.00 0.00
August 0.703795E+10 0.00 706.37 0.344404E+10 0.00 0.00 0.00 0.00 12306.04 08-AUG-08:62 10516.51 22-AUG-08:62 0.00 0.00 0.00
September 0.499563E+10 0.00 644.38 0.232098E+10 0.00 0.00 0.00 0.00 12226.27 23-SEP-08:62 10507.29 09-SEP-15:11 0.00 0.00 0.00
October 0.498973E+10 0.00 645.03 0.295964E+10 0.00 0.00 0.00 0.00 12361.65 01-OCT-08:62 11538.55 26-OCT-15:11 0.00 0.00 0.00
November 0.246201E+10 0.00 498.60 0.139147E+10 0.00 0.00 0.00 0.00 12221.28 12-NOV-09:02 11536.30 30-NOV-16:11 0.00 0.00 0.00
December 0.223963E+10 0.00 454.35 0.161738E+10 0.00 0.00 0.00 0.00 11534.96 05-DEC-09:01 11534.96 05-DEC-09:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.446877E+11 0.00 6543.61 0.228121E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.165654E+10 0.00 335.36 0.883551E+09 0.00 0.00 0.00 0.00 11530.08   10432.34   0.00 0.00 0.00
Maximum of Months 0.703795E+10 0.00 706.37 0.344404E+10 0.00 0.00 0.00 0.00 12361.65   11538.85   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.540618E+09 0.00 157.38 0.280453E+09 0.00 0.00 0.00 0.00 11434.26 20-JAN-19:01 10908.24 14-JAN-09:52 0.00 0.00 0.00
February 0.568790E+09 0.00 154.88 0.292663E+09 0.00 0.00 0.00 0.00 11246.91 14-FEB-09:01 11145.55 03-FEB-09:51 0.00 0.00 0.00
March 0.883974E+09 0.00 223.86 0.376626E+09 0.00 0.00 0.00 0.00 11143.37 17-MAR-08:61 10792.86 23-MAR-08:51 0.00 0.00 0.00
April 0.208473E+10 0.00 420.94 0.938474E+09 0.00 0.00 0.00 0.00 11848.85 02-APR-08:51 11848.85 02-APR-08:51 0.00 0.00 0.00
May 0.213261E+10 0.00 433.20 0.913868E+09 0.00 0.00 0.00 0.00 12166.21 24-MAY-08:51 12166.21 24-MAY-08:51 0.00 0.00 0.00
June 0.284941E+10 0.00 410.75 0.124777E+10 0.00 0.00 0.00 0.00 12777.26 30-JUN-08:51 11245.81 23-JUN-08:51 0.00 0.00 0.00
July 0.430869E+10 0.00 431.12 0.207928E+10 0.00 0.00 0.00 0.00 13180.99 22-JUL-08:51 11059.21 04-JUL-08:51 0.00 0.00 0.00
August 0.424047E+10 0.00 432.55 0.200118E+10 0.00 0.00 0.00 0.00 13369.21 19-AUG-08:51 10835.35 22-AUG-08:51 0.00 0.00 0.00
September 0.256089E+10 0.00 407.03 0.109121E+10 0.00 0.00 0.00 0.00 12838.66 10-SEP-08:51 10941.10 03-SEP-08:51 0.00 0.00 0.00
October 0.221956E+10 0.00 401.01 0.124053E+10 0.00 0.00 0.00 0.00 12831.13 15-OCT-07:41 12831.13 15-OCT-07:41 0.00 0.00 0.00
November 0.713650E+09 0.00 213.49 0.342786E+09 0.00 0.00 0.00 0.00 11697.62 12-NOV-09:02 10982.80 28-NOV-09:52 0.00 0.00 0.00
December 0.456909E+09 0.00 161.19 0.297328E+09 0.00 0.00 0.00 0.00 11606.75 05-DEC-09:41 11606.75 05-DEC-09:41 0.00 0.00 0.00
                               
Annual Sum or Average 0.235603E+11 0.00 3847.39 0.111022E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.456909E+09 0.00 154.88 0.280453E+09 0.00 0.00 0.00 0.00 11143.37   10792.86   0.00 0.00 0.00
Maximum of Months 0.430869E+10 0.00 433.20 0.207928E+10 0.00 0.00 0.00 0.00 13369.21   12831.13   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.426113E+09 0.00 334.43 0.226366E+09 0.00 0.00 0.00 0.00 3683.27 21-JAN-09:01 3384.78 14-JAN-16:11 0.00 0.00 0.00
February 0.392098E+09 0.00 254.36 0.222266E+09 0.00 0.00 0.00 0.00 3500.01 14-FEB-09:01 3384.05 06-FEB-16:11 0.00 0.00 0.00
March 0.462692E+09 0.00 282.17 0.233948E+09 0.00 0.00 0.00 0.00 3494.89 24-MAR-08:61 3079.55 24-MAR-18:01 0.00 0.00 0.00
April 0.960424E+09 0.00 512.88 0.499799E+09 0.00 0.00 0.00 0.00 3601.07 08-APR-08:61 3338.56 01-APR-18:02 0.00 0.00 0.00
May 0.878124E+09 0.00 509.93 0.429480E+09 0.00 0.00 0.00 0.00 3705.51 06-MAY-08:62 3206.55 24-MAY-08:61 0.00 0.00 0.00
June 0.128588E+10 0.00 602.12 0.632113E+09 0.00 0.00 0.00 0.00 3577.55 28-JUN-08:62 3072.18 01-JUN-18:01 0.00 0.00 0.00
July 0.184673E+10 0.00 687.72 0.944010E+09 0.00 0.00 0.00 0.00 3713.76 22-JUL-08:61 3079.41 26-JUL-18:01 0.00 0.00 0.00
August 0.188460E+10 0.00 687.19 0.968048E+09 0.00 0.00 0.00 0.00 3857.95 06-AUG-08:61 3080.51 21-AUG-18:01 0.00 0.00 0.00
September 0.140991E+10 0.00 642.63 0.694599E+09 0.00 0.00 0.00 0.00 3766.68 22-SEP-08:61 3054.85 16-SEP-18:01 0.00 0.00 0.00
October 0.122593E+10 0.00 587.04 0.725928E+09 0.00 0.00 0.00 0.00 3793.78 01-OCT-08:62 3384.90 25-OCT-18:01 0.00 0.00 0.00
November 0.568634E+09 0.00 391.54 0.305925E+09 0.00 0.00 0.00 0.00 3535.30 11-NOV-16:12 3384.15 30-NOV-16:11 0.00 0.00 0.00
December 0.472273E+09 0.00 354.06 0.326948E+09 0.00 0.00 0.00 0.00 3458.11 10-DEC-09:01 3385.15 30-DEC-16:11 0.00 0.00 0.00
                               
Annual Sum or Average 0.118134E+11 0.00 5846.05 0.620943E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.392098E+09 0.00 254.36 0.222266E+09 0.00 0.00 0.00 0.00 3458.11   3054.85   0.00 0.00 0.00
Maximum of Months 0.188460E+10 0.00 687.72 0.968048E+09 0.00 0.00 0.00 0.00 3857.95   3385.15   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 65508373.74 0.00 84.94 30669007.87 0.00 0.00 0.00 0.00 3430.40 21-JAN-09:01 3058.19 09-JAN-16:11 0.00 0.00 0.00
February 0.107684E+09 0.00 115.76 46975033.66 0.00 0.00 0.00 0.00 3243.92 15-FEB-16:11 3242.35 06-FEB-16:11 0.00 0.00 0.00
March 0.186790E+09 0.00 162.30 73577936.40 0.00 0.00 0.00 0.00 3374.42 22-MAR-18:51 2998.41 19-MAR-18:11 0.00 0.00 0.00
April 0.539022E+09 0.00 367.08 0.217245E+09 0.00 0.00 0.00 0.00 3607.49 26-APR-21:51 3300.81 23-APR-18:11 0.00 0.00 0.00
May 0.600209E+09 0.00 408.45 0.251636E+09 0.00 0.00 0.00 0.00 3528.91 06-MAY-08:62 3144.74 18-MAY-19:11 0.00 0.00 0.00
June 0.873505E+09 0.00 403.01 0.394834E+09 0.00 0.00 0.00 0.00 3752.00 28-JUN-21:51 3074.16 04-JUN-19:31 0.00 0.00 0.00
July 0.128649E+10 0.00 424.95 0.661302E+09 0.00 0.00 0.00 0.00 3770.06 27-JUL-21:51 2920.16 08-JUL-21:11 0.00 0.00 0.00
August 0.118331E+10 0.00 421.18 0.576542E+09 0.00 0.00 0.00 0.00 3741.27 19-AUG-08:51 2847.69 21-AUG-20:11 0.00 0.00 0.00
September 0.761589E+09 0.00 409.92 0.310751E+09 0.00 0.00 0.00 0.00 3604.08 07-SEP-21:51 2944.78 21-SEP-15:12 0.00 0.00 0.00
October 0.532004E+09 0.00 339.43 0.280161E+09 0.00 0.00 0.00 0.00 3724.17 01-OCT-08:52 3261.70 14-OCT-08:61 0.00 0.00 0.00
November 0.115070E+09 0.00 158.97 43247184.30 0.00 0.00 0.00 0.00 3269.29 10-NOV-22:12 3037.20 28-NOV-19:01 0.00 0.00 0.00
December 60015577.37 0.00 85.99 39231308.71 0.00 0.00 0.00 0.00 3351.91 09-DEC-16:11 3101.87 19-DEC-19:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.631120E+10 0.00 3381.98 0.292617E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 60015577.37 0.00 84.94 30669007.87 0.00 0.00 0.00 0.00 3243.92   2847.69   0.00 0.00 0.00
Maximum of Months 0.128649E+10 0.00 424.95 0.661302E+09 0.00 0.00 0.00 0.00 3770.06   3300.81   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.739189E+10 0.00 579.88 0.531886E+10 0.00 0.00 0.00 0.00 15822.26 14-JAN-16:11 15822.26 14-JAN-16:11 0.00 0.00 0.00
February 0.493089E+10 0.00 462.97 0.332234E+10 0.00 0.00 0.00 0.00 15823.01 06-FEB-16:11 15823.01 06-FEB-16:11 0.00 0.00 0.00
March 0.428038E+10 0.00 444.50 0.233373E+10 0.00 0.00 0.00 0.00 15911.66 18-MAR-08:62 14401.63 24-MAR-18:01 0.00 0.00 0.00
April 0.514242E+10 0.00 564.58 0.241842E+10 0.00 0.00 0.00 0.00 16024.71 08-APR-08:61 15656.24 01-APR-18:02 0.00 0.00 0.00
May 0.324229E+10 0.00 496.36 0.125440E+10 0.00 0.00 0.00 0.00 16397.52 06-MAY-08:62 14772.53 24-MAY-08:61 0.00 0.00 0.00
June 0.431042E+10 0.00 567.67 0.159808E+10 0.00 0.00 0.00 0.00 16426.34 27-JUN-18:01 14085.72 12-JUN-15:11 0.00 0.00 0.00
July 0.682349E+10 0.00 654.09 0.276705E+10 0.00 0.00 0.00 0.00 17168.46 30-JUL-08:62 14417.01 27-JUL-15:12 0.00 0.00 0.00
August 0.861233E+10 0.00 673.73 0.382447E+10 0.00 0.00 0.00 0.00 17509.50 20-AUG-08:62 14406.42 04-AUG-15:12 0.00 0.00 0.00
September 0.842279E+10 0.00 635.60 0.428601E+10 0.00 0.00 0.00 0.00 17201.77 22-SEP-08:61 14366.12 21-SEP-15:12 0.00 0.00 0.00
October 0.970676E+10 0.00 657.98 0.663109E+10 0.00 0.00 0.00 0.00 17441.66 01-OCT-08:62 15822.05 25-OCT-18:01 0.00 0.00 0.00
November 0.755604E+10 0.00 611.26 0.526147E+10 0.00 0.00 0.00 0.00 16471.56 12-NOV-09:02 15821.91 30-NOV-16:11 0.00 0.00 0.00
December 0.793321E+10 0.00 598.87 0.637398E+10 0.00 0.00 0.00 0.00 15890.97 08-DEC-16:11 15822.45 05-DEC-19:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.783529E+11 0.00 6947.49 0.453899E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.324229E+10 0.00 444.50 0.125440E+10 0.00 0.00 0.00 0.00 15822.26   14085.72   0.00 0.00 0.00
Maximum of Months 0.970676E+10 0.00 673.73 0.663109E+10 0.00 0.00 0.00 0.00 17509.50   15823.01   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 683.25 501.61 181.64 1004.42 362.07 0.00 0.00 0.00
February 539.71 333.96 205.76 758.26 324.89 0.00 0.00 0.00
March 430.45 209.68 220.77 600.11 333.41 0.00 0.00 0.00
April 359.95 139.12 220.83 531.37 275.57 0.00 0.00 0.00
May 253.61 30.71 222.90 319.39 241.27 0.00 0.00 0.00
June 222.49 13.05 209.44 281.26 185.48 0.00 0.00 0.00
July 234.64 25.09 209.55 334.19 166.67 0.00 0.00 0.00
August 301.36 93.65 207.72 483.55 179.57 0.00 0.00 0.00
September 413.83 205.59 208.24 663.19 210.71 0.00 0.00 0.00
October 541.89 363.92 177.97 871.18 230.86 0.00 0.00 0.00
November 658.23 466.37 191.86 969.82 328.75 0.00 0.00 0.00
December 731.17 557.17 174.00 1081.12 363.80 0.00 0.00 0.00
                 
Annual Sum or Average 447.16 244.69 202.47 657.84 266.63 0.00 0.00 0.00
Minimum of Months 222.49 13.05 174.00 281.26 166.67 0.00 0.00 0.00
Maximum of Months 731.17 557.17 222.90 1081.12 363.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1924.00 1412.50 511.50 2842.73 1000.98 0.00 0.00 0.00
February 1519.80 940.40 579.39 2153.14 903.35 0.00 0.00 0.00
March 1212.12 590.45 621.67 1710.51 931.73 0.00 0.00 0.00
April 1013.59 391.76 621.83 1543.65 739.16 0.00 0.00 0.00
May 714.16 86.49 627.67 938.66 653.80 0.00 0.00 0.00
June 626.52 36.75 589.77 847.06 482.84 0.00 0.00 0.00
July 660.73 70.66 590.08 1020.78 409.94 0.00 0.00 0.00
August 848.62 263.70 584.92 1442.89 439.37 0.00 0.00 0.00
September 1165.33 578.93 586.40 1924.34 535.02 0.00 0.00 0.00
October 1525.92 1024.77 501.15 2489.84 603.62 0.00 0.00 0.00
November 1853.53 1313.27 540.26 2752.06 893.95 0.00 0.00 0.00
December 2058.93 1568.96 489.97 3054.46 1002.00 0.00 0.00 0.00
                 
Annual Sum or Average 1259.18 689.03 570.15 1892.60 715.36 0.00 0.00 0.00
Minimum of Months 626.52 36.75 489.97 847.06 409.94 0.00 0.00 0.00
Maximum of Months 2058.93 1568.96 627.67 3054.46 1002.00 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2499.38 1834.91 664.47 3750.03 1375.61 0.00 0.00 0.00
February 1974.30 1221.64 752.67 2831.40 1260.58 0.00 0.00 0.00
March 1574.61 767.03 807.58 2241.52 1306.42 0.00 0.00 0.00
April 1316.71 508.91 807.79 2015.23 1050.30 0.00 0.00 0.00
May 927.73 112.35 815.38 1200.97 946.96 0.00 0.00 0.00
June 813.89 47.74 766.15 1073.59 714.55 0.00 0.00 0.00
July 858.33 91.79 766.54 1302.77 612.10 0.00 0.00 0.00
August 1102.41 342.56 759.84 1871.92 642.93 0.00 0.00 0.00
September 1513.82 752.06 761.77 2520.55 766.51 0.00 0.00 0.00
October 1982.26 1331.24 651.02 3276.02 846.75 0.00 0.00 0.00
November 2407.84 1706.01 701.82 3627.14 1237.33 0.00 0.00 0.00
December 2674.67 2038.17 636.50 4033.35 1375.44 0.00 0.00 0.00
                 
Annual Sum or Average 1635.75 895.09 740.66 2477.67 1010.00 0.00 0.00 0.00
Minimum of Months 813.89 47.74 636.50 1073.59 612.10 0.00 0.00 0.00
Maximum of Months 2674.67 2038.17 815.38 4033.35 1375.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 135.09 99.18 35.91 202.94 66.41 0.00 0.00 0.00
February 106.71 66.03 40.68 152.01 60.49 0.00 0.00 0.00
March 85.11 41.46 43.65 119.96 63.99 0.00 0.00 0.00
April 71.17 27.51 43.66 106.70 50.93 0.00 0.00 0.00
May 50.14 6.07 44.07 63.05 45.85 0.00 0.00 0.00
June 43.99 2.58 41.41 56.59 33.09 0.00 0.00 0.00
July 46.39 4.96 41.43 69.10 27.47 0.00 0.00 0.00
August 59.59 18.52 41.07 99.79 28.51 0.00 0.00 0.00
September 81.82 40.65 41.17 134.97 34.54 0.00 0.00 0.00
October 107.14 71.95 35.19 176.87 37.73 0.00 0.00 0.00
November 130.14 92.21 37.93 195.75 58.93 0.00 0.00 0.00
December 144.57 110.16 34.40 218.24 66.04 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 48.38 40.03 132.95 47.76 0.00 0.00 0.00
Minimum of Months 43.99 2.58 34.40 56.59 27.47 0.00 0.00 0.00
Maximum of Months 144.57 110.16 44.07 218.24 66.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 97.90 49.37 48.53 125.32 134.05 0.00 0.00 0.00
February 116.92 54.04 62.88 144.14 118.44 0.00 0.00 0.00
March 133.72 59.09 74.63 169.25 120.77 0.00 0.00 0.00
April 184.30 95.81 88.48 263.79 92.02 0.00 0.00 0.00
May 181.04 83.49 97.54 254.21 81.50 0.00 0.00 0.00
June 191.74 95.74 96.00 285.85 58.19 0.00 0.00 0.00
July 203.03 108.53 94.50 319.59 48.44 0.00 0.00 0.00
August 190.51 103.16 87.35 301.98 51.17 0.00 0.00 0.00
September 163.27 87.33 75.94 249.47 62.66 0.00 0.00 0.00
October 125.41 68.71 56.70 196.53 73.32 0.00 0.00 0.00
November 112.86 59.07 53.78 149.37 117.17 0.00 0.00 0.00
December 99.27 53.08 46.19 129.18 133.71 0.00 0.00 0.00
                 
Annual Sum or Average 150.13 76.55 73.58 216.08 90.82 0.00 0.00 0.00
Minimum of Months 97.90 49.37 46.19 125.32 48.44 0.00 0.00 0.00
Maximum of Months 203.03 108.53 97.54 319.59 134.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.42 0.00 20.42 15.41 71.69 0.00 0.00 0.00
February 25.63 0.00 25.63 17.70 64.22 0.00 0.00 0.00
March 31.41 0.00 31.41 25.19 66.27 0.00 0.00 0.00
April 36.38 0.29 36.09 33.92 50.44 0.00 0.00 0.00
May 43.77 2.28 41.49 43.17 43.46 0.00 0.00 0.00
June 46.39 4.58 41.81 53.71 32.92 0.00 0.00 0.00
July 43.95 3.73 40.22 56.09 29.27 0.00 0.00 0.00
August 36.54 0.81 35.73 45.52 31.03 0.00 0.00 0.00
September 30.84 0.01 30.84 36.14 37.12 0.00 0.00 0.00
October 24.46 0.00 24.46 32.41 41.74 0.00 0.00 0.00
November 22.15 0.00 22.15 17.62 63.74 0.00 0.00 0.00
December 19.01 0.00 19.01 14.03 71.84 0.00 0.00 0.00
                 
Annual Sum or Average 31.77 0.98 30.79 32.67 50.24 0.00 0.00 0.00
Minimum of Months 19.01 0.00 19.01 14.03 29.27 0.00 0.00 0.00
Maximum of Months 46.39 4.58 41.81 56.09 71.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 97.90 49.37 48.53 130.94 130.67 0.00 0.00 0.00
February 116.92 54.04 62.88 148.15 116.18 0.00 0.00 0.00
March 133.72 59.09 74.63 171.88 119.51 0.00 0.00 0.00
April 184.30 95.81 88.48 262.96 93.06 0.00 0.00 0.00
May 181.04 83.49 97.54 250.81 83.70 0.00 0.00 0.00
June 191.74 95.74 96.00 278.78 63.32 0.00 0.00 0.00
July 203.03 108.53 94.50 311.60 55.32 0.00 0.00 0.00
August 190.51 103.16 87.35 296.44 57.79 0.00 0.00 0.00
September 163.27 87.33 75.94 247.94 66.21 0.00 0.00 0.00
October 125.41 68.71 56.70 197.63 75.69 0.00 0.00 0.00
November 112.86 59.07 53.78 154.03 115.00 0.00 0.00 0.00
December 99.27 53.08 46.19 134.89 130.30 0.00 0.00 0.00
                 
Annual Sum or Average 150.13 76.55 73.58 215.83 92.12 0.00 0.00 0.00
Minimum of Months 97.90 49.37 46.19 130.94 55.32 0.00 0.00 0.00
Maximum of Months 203.03 108.53 97.54 311.60 130.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 108.05 79.33 28.73 149.32 78.28 0.00 0.00 0.00
February 85.35 52.81 32.54 108.86 73.85 0.00 0.00 0.00
March 68.07 33.16 34.91 83.71 75.63 0.00 0.00 0.00
April 56.92 22.00 34.92 73.62 62.98 0.00 0.00 0.00
May 40.11 4.86 35.25 38.33 57.52 0.00 0.00 0.00
June 35.19 2.06 33.12 32.79 45.58 0.00 0.00 0.00
July 37.11 3.97 33.14 42.78 39.99 0.00 0.00 0.00
August 47.66 14.81 32.85 67.51 42.03 0.00 0.00 0.00
September 65.44 32.51 32.93 96.02 48.71 0.00 0.00 0.00
October 85.70 57.55 28.14 128.75 52.07 0.00 0.00 0.00
November 104.09 73.75 30.34 143.52 71.57 0.00 0.00 0.00
December 115.63 88.11 27.52 161.26 77.99 0.00 0.00 0.00
                 
Annual Sum or Average 70.72 38.70 32.02 93.83 60.44 0.00 0.00 0.00
Minimum of Months 35.19 2.06 27.52 32.79 39.99 0.00 0.00 0.00
Maximum of Months 115.63 88.11 35.25 161.26 78.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.34 0.00 16.34 12.70 57.73 0.00 0.00 0.00
February 20.51 0.00 20.51 14.73 51.52 0.00 0.00 0.00
March 25.13 0.00 25.13 21.01 53.07 0.00 0.00 0.00
April 29.11 0.23 28.88 30.15 38.65 0.00 0.00 0.00
May 35.02 1.83 33.19 37.83 33.61 0.00 0.00 0.00
June 37.12 3.67 33.45 47.12 24.68 0.00 0.00 0.00
July 35.16 2.98 32.18 49.53 21.16 0.00 0.00 0.00
August 29.24 0.65 28.59 40.58 22.11 0.00 0.00 0.00
September 24.68 0.00 24.67 31.84 27.15 0.00 0.00 0.00
October 19.57 0.00 19.57 27.85 31.60 0.00 0.00 0.00
November 17.72 0.00 17.72 15.02 50.20 0.00 0.00 0.00
December 15.21 0.00 15.21 11.73 57.45 0.00 0.00 0.00
                 
Annual Sum or Average 25.42 0.78 24.64 28.42 39.02 0.00 0.00 0.00
Minimum of Months 15.21 0.00 15.21 11.73 21.16 0.00 0.00 0.00
Maximum of Months 37.12 3.67 33.45 49.53 57.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 102.74 54.89 47.84 127.80 127.25 0.00 0.00 0.00
February 108.41 49.61 58.80 126.34 113.38 0.00 0.00 0.00
March 132.31 59.09 73.21 162.98 115.49 0.00 0.00 0.00
April 168.65 84.62 84.03 236.71 88.30 0.00 0.00 0.00
May 158.85 66.20 92.65 217.89 79.01 0.00 0.00 0.00
June 158.05 68.61 89.44 232.87 57.60 0.00 0.00 0.00
July 178.98 88.92 90.06 282.15 48.37 0.00 0.00 0.00
August 176.89 94.01 82.88 281.02 49.97 0.00 0.00 0.00
September 129.15 59.40 69.75 194.34 61.33 0.00 0.00 0.00
October 113.82 58.42 55.40 174.99 69.87 0.00 0.00 0.00
November 103.52 52.41 51.11 130.08 112.57 0.00 0.00 0.00
December 99.52 55.46 44.05 123.49 127.08 0.00 0.00 0.00
                 
Annual Sum or Average 136.09 66.10 69.99 191.33 87.39 0.00 0.00 0.00
Minimum of Months 99.52 49.61 44.05 123.49 48.37 0.00 0.00 0.00
Maximum of Months 178.98 94.01 92.65 282.15 127.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 135.09 99.18 35.91 202.11 66.21 0.00 0.00 0.00
February 106.71 66.03 40.68 151.58 59.90 0.00 0.00 0.00
March 85.11 41.46 43.65 119.14 63.47 0.00 0.00 0.00
April 71.17 27.51 43.66 105.88 50.05 0.00 0.00 0.00
May 50.14 6.07 44.07 62.49 44.93 0.00 0.00 0.00
June 43.99 2.58 41.41 56.30 32.09 0.00 0.00 0.00
July 46.39 4.96 41.43 68.52 26.54 0.00 0.00 0.00
August 59.59 18.52 41.07 99.11 27.68 0.00 0.00 0.00
September 81.82 40.65 41.17 134.91 33.45 0.00 0.00 0.00
October 107.14 71.95 35.19 176.51 37.16 0.00 0.00 0.00
November 130.14 92.21 37.93 195.33 58.36 0.00 0.00 0.00
December 144.57 110.16 34.40 217.60 65.67 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 48.38 40.03 132.40 47.06 0.00 0.00 0.00
Minimum of Months 43.99 2.58 34.40 56.30 26.54 0.00 0.00 0.00
Maximum of Months 144.57 110.16 44.07 217.60 66.21 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.42 0.00 20.42 14.60 71.26 0.00 0.00 0.00
February 25.63 0.00 25.63 17.13 63.25 0.00 0.00 0.00
March 31.41 0.00 31.41 24.37 65.55 0.00 0.00 0.00
April 36.38 0.29 36.09 33.40 49.00 0.00 0.00 0.00
May 43.77 2.28 41.49 43.20 42.20 0.00 0.00 0.00
June 46.39 4.58 41.81 54.57 31.11 0.00 0.00 0.00
July 43.95 3.73 40.22 56.29 27.35 0.00 0.00 0.00
August 36.54 0.81 35.73 44.99 29.08 0.00 0.00 0.00
September 30.84 0.01 30.84 36.13 34.92 0.00 0.00 0.00
October 24.46 0.00 24.46 31.72 40.55 0.00 0.00 0.00
November 22.15 0.00 22.15 17.04 62.50 0.00 0.00 0.00
December 19.01 0.00 19.01 13.19 71.10 0.00 0.00 0.00
                 
Annual Sum or Average 31.77 0.98 30.79 32.31 48.92 0.00 0.00 0.00
Minimum of Months 19.01 0.00 19.01 13.19 27.35 0.00 0.00 0.00
Maximum of Months 46.39 4.58 41.81 56.29 71.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 102.74 54.89 47.84 132.95 123.02 0.00 0.00 0.00
February 108.41 49.61 58.80 130.32 110.50 0.00 0.00 0.00
March 132.31 59.09 73.21 165.82 113.90 0.00 0.00 0.00
April 168.65 84.62 84.03 237.23 88.71 0.00 0.00 0.00
May 158.85 66.20 92.65 215.94 80.68 0.00 0.00 0.00
June 158.05 68.61 89.44 228.39 61.53 0.00 0.00 0.00
July 178.98 88.92 90.06 276.07 53.84 0.00 0.00 0.00
August 176.89 94.01 82.88 276.22 54.96 0.00 0.00 0.00
September 129.15 59.40 69.75 193.79 63.50 0.00 0.00 0.00
October 113.82 58.42 55.40 176.08 71.55 0.00 0.00 0.00
November 103.52 52.41 51.11 134.50 109.09 0.00 0.00 0.00
December 99.52 55.46 44.05 128.56 122.68 0.00 0.00 0.00
                 
Annual Sum or Average 136.09 66.10 69.99 191.75 87.72 0.00 0.00 0.00
Minimum of Months 99.52 49.61 44.05 128.56 53.84 0.00 0.00 0.00
Maximum of Months 178.98 94.01 92.65 276.22 123.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.86 0.00 25.86 18.73 96.43 0.00 0.00 0.00
February 32.46 0.00 32.46 22.34 85.99 0.00 0.00 0.00
March 39.78 0.00 39.78 33.19 86.77 0.00 0.00 0.00
April 46.08 0.37 45.70 47.72 64.74 0.00 0.00 0.00
May 55.43 2.89 52.54 60.69 56.03 0.00 0.00 0.00
June 58.76 5.80 52.95 76.35 41.14 0.00 0.00 0.00
July 55.66 4.72 50.93 79.33 36.09 0.00 0.00 0.00
August 46.27 1.03 45.25 63.74 38.82 0.00 0.00 0.00
September 39.06 0.01 39.05 49.30 47.79 0.00 0.00 0.00
October 30.98 0.00 30.98 42.02 56.36 0.00 0.00 0.00
November 28.05 0.00 28.05 21.77 86.23 0.00 0.00 0.00
December 24.07 0.00 24.07 16.59 97.63 0.00 0.00 0.00
                 
Annual Sum or Average 40.24 1.24 39.00 44.45 66.07 0.00 0.00 0.00
Minimum of Months 24.07 0.00 24.07 16.59 36.09 0.00 0.00 0.00
Maximum of Months 58.76 5.80 52.95 79.33 97.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.53 0.00 9.53 6.90 35.55 0.00 0.00 0.00
February 11.97 0.00 11.97 8.24 31.70 0.00 0.00 0.00
March 14.67 0.00 14.67 12.24 31.99 0.00 0.00 0.00
April 16.99 0.14 16.85 17.59 23.87 0.00 0.00 0.00
May 20.43 1.07 19.37 22.37 20.65 0.00 0.00 0.00
June 21.66 2.14 19.52 28.15 15.17 0.00 0.00 0.00
July 20.52 1.74 18.78 29.24 13.31 0.00 0.00 0.00
August 17.06 0.38 16.68 23.50 14.31 0.00 0.00 0.00
September 14.40 0.00 14.40 18.17 17.62 0.00 0.00 0.00
October 11.42 0.00 11.42 15.49 20.78 0.00 0.00 0.00
November 10.34 0.00 10.34 8.03 31.79 0.00 0.00 0.00
December 8.87 0.00 8.87 6.12 35.99 0.00 0.00 0.00
                 
Annual Sum or Average 14.83 0.46 14.38 16.38 24.36 0.00 0.00 0.00
Minimum of Months 8.87 0.00 8.87 6.12 13.31 0.00 0.00 0.00
Maximum of Months 21.66 2.14 19.52 29.24 35.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 63.03 46.28 16.76 95.92 32.13 0.00 0.00 0.00
February 49.79 30.81 18.98 72.02 29.43 0.00 0.00 0.00
March 39.71 19.34 20.37 57.21 30.71 0.00 0.00 0.00
April 33.21 12.83 20.37 51.46 24.44 0.00 0.00 0.00
May 23.40 2.83 20.56 30.82 22.28 0.00 0.00 0.00
June 20.53 1.20 19.32 27.72 16.48 0.00 0.00 0.00
July 21.65 2.31 19.33 33.37 14.18 0.00 0.00 0.00
August 27.80 8.64 19.16 47.57 14.89 0.00 0.00 0.00
September 38.18 18.97 19.21 64.08 17.52 0.00 0.00 0.00
October 49.99 33.57 16.42 83.22 19.58 0.00 0.00 0.00
November 60.72 43.02 17.70 92.42 28.94 0.00 0.00 0.00
December 67.45 51.40 16.05 102.91 32.23 0.00 0.00 0.00
                 
Annual Sum or Average 41.25 22.57 18.68 63.20 23.54 0.00 0.00 0.00
Minimum of Months 20.53 1.20 16.05 27.72 14.18 0.00 0.00 0.00
Maximum of Months 67.45 51.40 20.56 102.91 32.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 171.08 125.60 45.48 260.34 87.22 0.00 0.00 0.00
February 135.14 83.62 51.52 195.49 79.88 0.00 0.00 0.00
March 107.78 52.50 55.28 155.28 83.34 0.00 0.00 0.00
April 90.13 34.84 55.29 139.68 66.33 0.00 0.00 0.00
May 63.50 7.69 55.81 83.66 60.46 0.00 0.00 0.00
June 55.71 3.27 52.44 75.24 44.73 0.00 0.00 0.00
July 58.75 6.28 52.47 90.58 38.50 0.00 0.00 0.00
August 75.46 23.45 52.01 129.11 40.42 0.00 0.00 0.00
September 103.62 51.48 52.14 173.94 47.57 0.00 0.00 0.00
October 135.69 91.12 44.56 225.89 53.14 0.00 0.00 0.00
November 164.82 116.78 48.04 250.85 78.56 0.00 0.00 0.00
December 183.08 139.51 43.57 279.33 87.48 0.00 0.00 0.00
                 
Annual Sum or Average 111.97 61.27 50.70 171.55 63.89 0.00 0.00 0.00
Minimum of Months 55.71 3.27 43.57 75.24 38.50 0.00 0.00 0.00
Maximum of Months 183.08 139.51 55.81 279.33 87.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 135.09 99.18 35.91 202.01 65.60 0.00 0.00 0.00
February 106.71 66.03 40.68 150.79 59.73 0.00 0.00 0.00
March 85.11 41.46 43.65 118.79 63.57 0.00 0.00 0.00
April 71.17 27.51 43.66 105.20 50.66 0.00 0.00 0.00
May 50.14 6.07 44.07 61.76 45.66 0.00 0.00 0.00
June 43.99 2.58 41.41 55.41 32.96 0.00 0.00 0.00
July 46.39 4.96 41.43 67.92 27.31 0.00 0.00 0.00
August 59.59 18.52 41.07 98.48 28.27 0.00 0.00 0.00
September 81.82 40.65 41.17 133.58 34.14 0.00 0.00 0.00
October 107.14 71.95 35.19 175.66 37.08 0.00 0.00 0.00
November 130.14 92.21 37.93 194.55 58.13 0.00 0.00 0.00
December 144.57 110.16 34.40 217.22 65.07 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 48.38 40.03 131.73 47.28 0.00 0.00 0.00
Minimum of Months 43.99 2.58 34.40 55.41 27.31 0.00 0.00 0.00
Maximum of Months 144.57 110.16 44.07 217.22 65.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 97.90 49.37 48.53 124.01 131.95 0.00 0.00 0.00
February 116.92 54.04 62.88 142.47 116.61 0.00 0.00 0.00
March 133.72 59.09 74.63 166.84 119.61 0.00 0.00 0.00
April 184.30 95.81 88.48 259.92 91.31 0.00 0.00 0.00
May 181.04 83.49 97.54 250.19 80.90 0.00 0.00 0.00
June 191.74 95.74 96.00 281.49 57.77 0.00 0.00 0.00
July 203.03 108.53 94.50 315.51 47.95 0.00 0.00 0.00
August 190.51 103.16 87.35 298.20 50.59 0.00 0.00 0.00
September 163.27 87.33 75.94 246.30 61.82 0.00 0.00 0.00
October 125.41 68.71 56.70 194.68 71.88 0.00 0.00 0.00
November 112.86 59.07 53.78 147.84 115.20 0.00 0.00 0.00
December 99.27 53.08 46.19 128.15 131.25 0.00 0.00 0.00
                 
Annual Sum or Average 150.13 76.55 73.58 213.32 89.61 0.00 0.00 0.00
Minimum of Months 97.90 49.37 46.19 124.01 47.95 0.00 0.00 0.00
Maximum of Months 203.03 108.53 97.54 315.51 131.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.42 0.00 20.42 15.70 70.32 0.00 0.00 0.00
February 25.63 0.00 25.63 17.84 63.15 0.00 0.00 0.00
March 31.41 0.00 31.41 24.84 65.78 0.00 0.00 0.00
April 36.38 0.29 36.09 32.84 50.69 0.00 0.00 0.00
May 43.77 2.28 41.49 41.74 43.71 0.00 0.00 0.00
June 46.39 4.58 41.81 51.74 33.76 0.00 0.00 0.00
July 43.95 3.73 40.22 54.24 30.28 0.00 0.00 0.00
August 36.54 0.81 35.73 44.25 31.95 0.00 0.00 0.00
September 30.84 0.01 30.84 35.41 37.34 0.00 0.00 0.00
October 24.46 0.00 24.46 32.38 41.11 0.00 0.00 0.00
November 22.15 0.00 22.15 17.89 62.50 0.00 0.00 0.00
December 19.01 0.00 19.01 14.52 70.20 0.00 0.00 0.00
                 
Annual Sum or Average 31.77 0.98 30.79 32.04 50.00 0.00 0.00 0.00
Minimum of Months 19.01 0.00 19.01 14.52 30.28 0.00 0.00 0.00
Maximum of Months 46.39 4.58 41.81 54.24 70.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 97.90 49.37 48.53 130.43 128.06 0.00 0.00 0.00
February 116.92 54.04 62.88 147.03 114.09 0.00 0.00 0.00
March 133.72 59.09 74.63 169.58 118.42 0.00 0.00 0.00
April 184.30 95.81 88.48 258.45 93.12 0.00 0.00 0.00
May 181.04 83.49 97.54 245.95 83.95 0.00 0.00 0.00
June 191.74 95.74 96.00 272.99 64.67 0.00 0.00 0.00
July 203.03 108.53 94.50 306.04 56.99 0.00 0.00 0.00
August 190.51 103.16 87.35 291.59 59.12 0.00 0.00 0.00
September 163.27 87.33 75.94 244.38 66.26 0.00 0.00 0.00
October 125.41 68.71 56.70 196.04 74.42 0.00 0.00 0.00
November 112.86 59.07 53.78 153.24 112.61 0.00 0.00 0.00
December 99.27 53.08 46.19 134.82 127.23 0.00 0.00 0.00
                 
Annual Sum or Average 150.13 76.55 73.58 212.87 91.47 0.00 0.00 0.00
Minimum of Months 97.90 49.37 46.19 130.43 56.99 0.00 0.00 0.00
Maximum of Months 203.03 108.53 97.54 306.04 128.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 198.12 145.45 52.67 291.67 100.30 0.00 0.00 0.00
February 156.50 96.84 59.66 217.82 90.54 0.00 0.00 0.00
March 124.82 60.80 64.02 172.05 94.99 0.00 0.00 0.00
April 104.38 40.34 64.03 154.75 73.22 0.00 0.00 0.00
May 73.54 8.91 64.64 92.75 64.95 0.00 0.00 0.00
June 64.52 3.78 60.73 84.63 45.71 0.00 0.00 0.00
July 68.04 7.28 60.76 103.32 37.15 0.00 0.00 0.00
August 87.39 27.15 60.23 146.81 39.15 0.00 0.00 0.00
September 120.00 59.61 60.39 196.32 48.91 0.00 0.00 0.00
October 157.13 105.53 51.61 256.29 54.91 0.00 0.00 0.00
November 190.87 135.23 55.63 281.71 88.22 0.00 0.00 0.00
December 212.02 161.56 50.45 313.88 99.50 0.00 0.00 0.00
                 
Annual Sum or Average 129.67 70.95 58.71 192.61 69.69 0.00 0.00 0.00
Minimum of Months 64.52 3.78 50.45 84.63 37.15 0.00 0.00 0.00
Maximum of Months 212.02 161.56 64.64 313.88 100.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 142.93 0.00 142.93 97.53 558.62 0.00 0.00 0.00
February 179.42 0.00 179.42 112.39 511.34 0.00 0.00 0.00
March 219.89 0.00 219.88 165.62 521.84 0.00 0.00 0.00
April 254.66 2.05 252.61 243.74 389.16 0.00 0.00 0.00
May 306.36 15.98 290.38 307.85 339.80 0.00 0.00 0.00
June 324.75 32.08 292.67 396.41 253.05 0.00 0.00 0.00
July 307.61 26.10 281.51 424.08 216.32 0.00 0.00 0.00
August 255.76 5.68 250.08 345.50 230.42 0.00 0.00 0.00
September 215.89 0.04 215.85 265.48 281.04 0.00 0.00 0.00
October 171.24 0.00 171.24 233.48 322.97 0.00 0.00 0.00
November 155.04 0.00 155.04 115.64 495.91 0.00 0.00 0.00
December 133.06 0.00 133.06 88.77 558.72 0.00 0.00 0.00
                 
Annual Sum or Average 222.40 6.87 215.54 233.79 389.32 0.00 0.00 0.00
Minimum of Months 133.06 0.00 133.06 88.77 216.32 0.00 0.00 0.00
Maximum of Months 324.75 32.08 292.67 424.08 558.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 142.93 0.00 142.93 89.55 582.73 0.00 0.00 0.00
February 179.42 0.00 179.42 103.36 535.54 0.00 0.00 0.00
March 219.89 0.00 219.88 154.66 545.32 0.00 0.00 0.00
April 254.66 2.05 252.61 231.04 406.52 0.00 0.00 0.00
May 306.36 15.98 290.38 292.40 354.34 0.00 0.00 0.00
June 324.75 32.08 292.67 381.24 264.90 0.00 0.00 0.00
July 307.61 26.10 281.51 409.75 227.03 0.00 0.00 0.00
August 255.76 5.68 250.08 332.78 242.23 0.00 0.00 0.00
September 215.89 0.04 215.85 254.80 295.46 0.00 0.00 0.00
October 171.24 0.00 171.24 223.93 338.79 0.00 0.00 0.00
November 155.04 0.00 155.04 107.39 517.34 0.00 0.00 0.00
December 133.06 0.00 133.06 81.27 581.92 0.00 0.00 0.00
                 
Annual Sum or Average 222.40 6.87 215.54 222.58 407.03 0.00 0.00 0.00
Minimum of Months 133.06 0.00 133.06 81.27 227.03 0.00 0.00 0.00
Maximum of Months 324.75 32.08 292.67 409.75 582.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.42 0.00 20.42 18.44 78.14 0.00 0.00 0.00
February 25.63 0.00 25.63 20.61 73.48 0.00 0.00 0.00
March 31.41 0.00 31.41 29.33 75.61 0.00 0.00 0.00
April 36.38 0.29 36.09 43.27 56.99 0.00 0.00 0.00
May 43.77 2.28 41.49 54.62 51.00 0.00 0.00 0.00
June 46.39 4.58 41.81 69.17 38.21 0.00 0.00 0.00
July 43.95 3.73 40.22 73.90 32.76 0.00 0.00 0.00
August 36.54 0.81 35.73 61.35 34.41 0.00 0.00 0.00
September 30.84 0.01 30.84 47.62 39.63 0.00 0.00 0.00
October 24.46 0.00 24.46 41.83 45.22 0.00 0.00 0.00
November 22.15 0.00 22.15 21.63 69.13 0.00 0.00 0.00
December 19.01 0.00 19.01 17.14 78.01 0.00 0.00 0.00
                 
Annual Sum or Average 31.77 0.98 30.79 41.71 55.96 0.00 0.00 0.00
Minimum of Months 19.01 0.00 19.01 17.14 32.76 0.00 0.00 0.00
Maximum of Months 46.39 4.58 41.81 73.90 78.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 205.46 109.78 95.68 285.27 274.63 0.00 0.00 0.00
February 216.80 99.21 117.60 275.82 261.33 0.00 0.00 0.00
March 264.60 118.18 146.42 353.11 267.48 0.00 0.00 0.00
April 337.28 169.23 168.05 514.53 207.95 0.00 0.00 0.00
May 317.68 132.39 185.29 474.26 192.55 0.00 0.00 0.00
June 316.07 137.22 178.86 510.88 147.28 0.00 0.00 0.00
July 357.93 177.82 180.11 618.21 126.04 0.00 0.00 0.00
August 353.76 188.01 165.75 615.72 129.64 0.00 0.00 0.00
September 258.28 118.80 139.48 434.44 146.78 0.00 0.00 0.00
October 227.63 116.83 110.79 393.93 163.00 0.00 0.00 0.00
November 207.02 104.81 102.21 289.47 245.30 0.00 0.00 0.00
December 199.02 110.92 88.09 275.83 273.87 0.00 0.00 0.00
                 
Annual Sum or Average 272.16 132.20 139.96 421.12 202.68 0.00 0.00 0.00
Minimum of Months 199.02 99.21 88.09 275.82 126.04 0.00 0.00 0.00
Maximum of Months 357.93 188.01 185.29 618.21 274.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 135.09 99.18 35.91 212.44 72.57 0.00 0.00 0.00
February 106.71 66.03 40.68 159.25 69.91 0.00 0.00 0.00
March 85.11 41.46 43.65 127.10 73.64 0.00 0.00 0.00
April 71.17 27.51 43.66 116.66 58.16 0.00 0.00 0.00
May 50.14 6.07 44.07 72.26 54.13 0.00 0.00 0.00
June 43.99 2.58 41.41 68.12 40.60 0.00 0.00 0.00
July 46.39 4.96 41.43 82.73 34.17 0.00 0.00 0.00
August 59.59 18.52 41.07 113.37 35.29 0.00 0.00 0.00
September 81.82 40.65 41.17 147.40 39.67 0.00 0.00 0.00
October 107.14 71.95 35.19 189.11 43.73 0.00 0.00 0.00
November 130.14 92.21 37.93 205.45 64.86 0.00 0.00 0.00
December 144.57 110.16 34.40 227.87 72.06 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 48.38 40.03 143.45 54.82 0.00 0.00 0.00
Minimum of Months 43.99 2.58 34.40 68.12 34.17 0.00 0.00 0.00
Maximum of Months 144.57 110.16 44.07 227.87 73.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.86 0.00 25.86 14.31 105.02 0.00 0.00 0.00
February 32.46 0.00 32.46 17.26 95.27 0.00 0.00 0.00
March 39.78 0.00 39.78 26.98 95.75 0.00 0.00 0.00
April 46.08 0.37 45.70 38.68 73.99 0.00 0.00 0.00
May 55.43 2.89 52.54 50.18 64.14 0.00 0.00 0.00
June 58.76 5.80 52.95 64.20 49.27 0.00 0.00 0.00
July 55.66 4.72 50.93 67.77 43.51 0.00 0.00 0.00
August 46.27 1.03 45.25 53.78 46.90 0.00 0.00 0.00
September 39.06 0.01 39.05 40.86 57.20 0.00 0.00 0.00
October 30.98 0.00 30.98 35.44 65.26 0.00 0.00 0.00
November 28.05 0.00 28.05 16.81 95.39 0.00 0.00 0.00
December 24.07 0.00 24.07 12.38 106.29 0.00 0.00 0.00
                 
Annual Sum or Average 40.24 1.24 39.00 36.67 74.73 0.00 0.00 0.00
Minimum of Months 24.07 0.00 24.07 12.38 43.51 0.00 0.00 0.00
Maximum of Months 58.76 5.80 52.95 67.77 106.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.14 0.00 23.14 12.81 93.95 0.00 0.00 0.00
February 29.04 0.00 29.04 15.44 85.24 0.00 0.00 0.00
March 35.59 0.00 35.59 24.14 85.67 0.00 0.00 0.00
April 41.22 0.33 40.89 34.60 66.20 0.00 0.00 0.00
May 49.59 2.59 47.01 44.89 57.38 0.00 0.00 0.00
June 52.57 5.19 47.38 57.44 44.08 0.00 0.00 0.00
July 49.80 4.23 45.57 60.64 38.92 0.00 0.00 0.00
August 41.40 0.92 40.48 48.12 41.96 0.00 0.00 0.00
September 34.95 0.01 34.94 36.56 51.17 0.00 0.00 0.00
October 27.72 0.00 27.72 31.71 58.39 0.00 0.00 0.00
November 25.10 0.00 25.10 15.04 85.34 0.00 0.00 0.00
December 21.54 0.00 21.54 11.08 95.08 0.00 0.00 0.00
                 
Annual Sum or Average 36.00 1.11 34.89 32.81 66.86 0.00 0.00 0.00
Minimum of Months 21.54 0.00 21.54 11.08 38.92 0.00 0.00 0.00
Maximum of Months 52.57 5.19 47.38 60.64 95.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 504.34 370.26 134.08 745.64 278.51 0.00 0.00 0.00
February 398.38 246.51 151.88 552.40 259.54 0.00 0.00 0.00
March 317.73 154.77 162.96 434.06 271.00 0.00 0.00 0.00
April 265.69 102.69 163.00 382.87 223.82 0.00 0.00 0.00
May 187.20 22.67 164.53 217.39 205.80 0.00 0.00 0.00
June 164.23 9.63 154.60 189.88 159.79 0.00 0.00 0.00
July 173.20 18.52 154.68 235.93 138.75 0.00 0.00 0.00
August 222.45 69.12 153.33 351.11 144.87 0.00 0.00 0.00
September 305.47 151.75 153.71 484.29 167.60 0.00 0.00 0.00
October 399.99 268.62 131.37 640.06 180.94 0.00 0.00 0.00
November 485.86 344.25 141.62 715.05 254.45 0.00 0.00 0.00
December 539.71 411.27 128.44 800.65 278.80 0.00 0.00 0.00
                 
Annual Sum or Average 330.07 180.61 149.46 478.90 213.41 0.00 0.00 0.00
Minimum of Months 164.23 9.63 128.44 189.88 138.75 0.00 0.00 0.00
Maximum of Months 539.71 411.27 164.53 800.65 278.80 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.183003E+10 0.134351E+10 0.486517E+09 0.269024E+10 0.969778E+09
February 0.130567E+10 0.807910E+09 0.497764E+09 0.183438E+10 0.785963E+09
March 0.115292E+10 0.561611E+09 0.591306E+09 0.160734E+10 0.893000E+09
April 0.932983E+09 0.360602E+09 0.572380E+09 0.137732E+10 0.714285E+09
May 0.679280E+09 82262473.23 0.597017E+09 0.855451E+09 0.646211E+09
June 0.576697E+09 33823907.42 0.542873E+09 0.729021E+09 0.480768E+09
July 0.628462E+09 67204411.99 0.561258E+09 0.895089E+09 0.446420E+09
August 0.807172E+09 0.250821E+09 0.556351E+09 0.129514E+10 0.480972E+09
September 0.107265E+10 0.532887E+09 0.539768E+09 0.171899E+10 0.546169E+09
October 0.145139E+10 0.974720E+09 0.476671E+09 0.233338E+10 0.618330E+09
November 0.170613E+10 0.120883E+10 0.497293E+09 0.251378E+10 0.852130E+09
December 0.195837E+10 0.149233E+10 0.466038E+09 0.289567E+10 0.974409E+09
           
Annual Sum or Average 0.141018E+11 0.771652E+10 0.638524E+10 0.207458E+11 0.840843E+10
Minimum of Months 0.576697E+09 33823907.42 0.466038E+09 0.729021E+09 0.446420E+09
Maximum of Months 0.195837E+10 0.149233E+10 0.597017E+09 0.289567E+10 0.974409E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.515323E+10 0.378323E+10 0.137000E+10 0.761398E+10 0.268104E+10
February 0.367669E+10 0.227502E+10 0.140167E+10 0.520888E+10 0.218538E+10
March 0.324654E+10 0.158146E+10 0.166508E+10 0.458142E+10 0.249554E+10
April 0.262722E+10 0.101543E+10 0.161179E+10 0.400114E+10 0.191591E+10
May 0.191281E+10 0.231646E+09 0.168116E+10 0.251412E+10 0.175115E+10
June 0.162394E+10 95245893.14 0.152869E+10 0.219558E+10 0.125153E+10
July 0.176971E+10 0.189243E+09 0.158047E+10 0.273405E+10 0.109799E+10
August 0.227294E+10 0.706295E+09 0.156665E+10 0.386464E+10 0.117681E+10
September 0.302053E+10 0.150058E+10 0.151995E+10 0.498788E+10 0.138678E+10
October 0.408702E+10 0.274475E+10 0.134227E+10 0.666879E+10 0.161672E+10
November 0.480434E+10 0.340400E+10 0.140034E+10 0.713333E+10 0.231711E+10
December 0.551464E+10 0.420231E+10 0.131233E+10 0.818107E+10 0.268376E+10
           
Annual Sum or Average 0.397096E+11 0.217292E+11 0.179804E+11 0.596849E+11 0.225597E+11
Minimum of Months 0.162394E+10 95245893.14 0.131233E+10 0.219558E+10 0.109799E+10
Maximum of Months 0.551464E+10 0.420231E+10 0.168116E+10 0.818107E+10 0.268376E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.669434E+10 0.491463E+10 0.177971E+10 0.100441E+11 0.368445E+10
February 0.477623E+10 0.295538E+10 0.182085E+10 0.684973E+10 0.304958E+10
March 0.421744E+10 0.205440E+10 0.216303E+10 0.600370E+10 0.349911E+10
April 0.341291E+10 0.131910E+10 0.209380E+10 0.522347E+10 0.272239E+10
May 0.248484E+10 0.300921E+09 0.218392E+10 0.321668E+10 0.253634E+10
June 0.210959E+10 0.123730E+09 0.198586E+10 0.278275E+10 0.185211E+10
July 0.229895E+10 0.245838E+09 0.205311E+10 0.348934E+10 0.163944E+10
August 0.295268E+10 0.917517E+09 0.203517E+10 0.501375E+10 0.172203E+10
September 0.392383E+10 0.194933E+10 0.197450E+10 0.653327E+10 0.198681E+10
October 0.530927E+10 0.356558E+10 0.174369E+10 0.877449E+10 0.226794E+10
November 0.624111E+10 0.442199E+10 0.181913E+10 0.940156E+10 0.320716E+10
December 0.716383E+10 0.545903E+10 0.170479E+10 0.108029E+11 0.368398E+10
           
Annual Sum or Average 0.515850E+11 0.282275E+11 0.233576E+11 0.781357E+11 0.318513E+11
Minimum of Months 0.210959E+10 0.123730E+09 0.170479E+10 0.278275E+10 0.163944E+10
Maximum of Months 0.716383E+10 0.545903E+10 0.218392E+10 0.108029E+11 0.368445E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.361828E+09 0.265635E+09 96193539.89 0.543560E+09 0.177860E+09
February 0.258155E+09 0.159738E+09 98417302.63 0.367754E+09 0.146327E+09
March 0.227952E+09 0.111040E+09 0.116912E+09 0.321304E+09 0.171384E+09
April 0.184468E+09 71297257.09 0.113171E+09 0.276558E+09 0.132018E+09
May 0.134307E+09 16264703.80 0.118042E+09 0.168884E+09 0.122808E+09
June 0.114024E+09 6687567.42 0.107337E+09 0.146680E+09 85771416.78
July 0.124259E+09 13287466.48 0.110972E+09 0.185068E+09 73571054.89
August 0.159593E+09 49591587.53 0.110002E+09 0.267274E+09 76351570.76
September 0.212083E+09 0.105361E+09 0.106722E+09 0.349848E+09 89519036.72
October 0.286966E+09 0.192719E+09 94246894.73 0.473736E+09 0.101044E+09
November 0.337331E+09 0.239007E+09 98324128.04 0.507382E+09 0.152752E+09
December 0.387204E+09 0.295059E+09 92144323.65 0.584539E+09 0.176891E+09
           
Annual Sum or Average 0.278817E+10 0.152569E+10 0.126248E+10 0.419259E+10 0.150630E+10
Minimum of Months 0.114024E+09 6687567.42 92144323.65 0.146680E+09 73571054.89
Maximum of Months 0.387204E+09 0.295059E+09 0.118042E+09 0.584539E+09 0.177860E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.262209E+09 0.132231E+09 0.129978E+09 0.335645E+09 0.359031E+09
February 0.282852E+09 0.130735E+09 0.152118E+09 0.348706E+09 0.286533E+09
March 0.358163E+09 0.158278E+09 0.199885E+09 0.453329E+09 0.323466E+09
April 0.477695E+09 0.248345E+09 0.229350E+09 0.683748E+09 0.238522E+09
May 0.484896E+09 0.223633E+09 0.261263E+09 0.680870E+09 0.218287E+09
June 0.496986E+09 0.248157E+09 0.248829E+09 0.740931E+09 0.150841E+09
July 0.543784E+09 0.290681E+09 0.253103E+09 0.855986E+09 0.129747E+09
August 0.510259E+09 0.276292E+09 0.233967E+09 0.808830E+09 0.137044E+09
September 0.423190E+09 0.226362E+09 0.196828E+09 0.646618E+09 0.162422E+09
October 0.335903E+09 0.184044E+09 0.151860E+09 0.526397E+09 0.196388E+09
November 0.292523E+09 0.153116E+09 0.139407E+09 0.387157E+09 0.303694E+09
December 0.265882E+09 0.142163E+09 0.123718E+09 0.345988E+09 0.358126E+09
           
Annual Sum or Average 0.473434E+10 0.241404E+10 0.232031E+10 0.681420E+10 0.286410E+10
Minimum of Months 0.262209E+09 0.130735E+09 0.123718E+09 0.335645E+09 0.129747E+09
Maximum of Months 0.543784E+09 0.290681E+09 0.261263E+09 0.855986E+09 0.359031E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54692945.39 0.00 54692945.39 41271906.44 0.192007E+09
February 62010236.23 0.00 62010236.23 42831046.78 0.155356E+09
March 84138040.91 770.44 84137270.47 67464442.39 0.177500E+09
April 94302093.46 758828.12 93543265.34 87932322.89 0.130744E+09
May 0.117227E+09 6113231.30 0.111114E+09 0.115620E+09 0.116395E+09
June 0.120254E+09 11879915.73 0.108374E+09 0.139228E+09 85336139.04
July 0.117706E+09 9987889.39 0.107718E+09 0.150236E+09 78400332.99
August 97866000.93 2174349.36 95691651.57 0.121932E+09 83105646.43
September 79945599.65 15899.58 79929700.08 93667971.90 96213147.93
October 65522177.41 0.00 65522177.41 86816799.24 0.111794E+09
November 57411863.01 0.00 57411863.01 45666235.96 0.165215E+09
December 50914483.72 0.00 50914483.72 37567996.30 0.192428E+09
           
Annual Sum or Average 0.100199E+10 30930883.91 0.971059E+09 0.103023E+10 0.158449E+10
Minimum of Months 50914483.72 0.00 50914483.72 37567996.30 78400332.99
Maximum of Months 0.120254E+09 11879915.73 0.111114E+09 0.150236E+09 0.192428E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.262209E+09 0.132231E+09 0.129978E+09 0.350714E+09 0.349982E+09
February 0.282852E+09 0.130735E+09 0.152118E+09 0.358411E+09 0.281053E+09
March 0.358163E+09 0.158278E+09 0.199885E+09 0.460374E+09 0.320092E+09
April 0.477695E+09 0.248345E+09 0.229350E+09 0.681588E+09 0.241205E+09
May 0.484896E+09 0.223633E+09 0.261263E+09 0.671780E+09 0.224171E+09
June 0.496986E+09 0.248157E+09 0.248829E+09 0.722586E+09 0.164123E+09
July 0.543784E+09 0.290681E+09 0.253103E+09 0.834602E+09 0.148158E+09
August 0.510259E+09 0.276292E+09 0.233967E+09 0.793991E+09 0.154779E+09
September 0.423190E+09 0.226362E+09 0.196828E+09 0.642663E+09 0.171619E+09
October 0.335903E+09 0.184044E+09 0.151860E+09 0.529326E+09 0.202738E+09
November 0.292523E+09 0.153116E+09 0.139407E+09 0.399244E+09 0.298083E+09
December 0.265882E+09 0.142163E+09 0.123718E+09 0.361291E+09 0.349005E+09
           
Annual Sum or Average 0.473434E+10 0.241404E+10 0.232031E+10 0.680657E+10 0.290501E+10
Minimum of Months 0.262209E+09 0.130735E+09 0.123718E+09 0.350714E+09 0.148158E+09
Maximum of Months 0.543784E+09 0.290681E+09 0.261263E+09 0.834602E+09 0.349982E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.289405E+09 0.212465E+09 76939530.71 0.399936E+09 0.209675E+09
February 0.206483E+09 0.127765E+09 78718187.18 0.263343E+09 0.178656E+09
March 0.182326E+09 88814382.37 93511326.07 0.224206E+09 0.202573E+09
April 0.147545E+09 57026464.64 90518660.62 0.190820E+09 0.163244E+09
May 0.107424E+09 13009175.87 94414790.61 0.102673E+09 0.154058E+09
June 91201314.76 5348990.16 85852324.60 84991350.10 0.118136E+09
July 99387762.81 10627859.59 88759903.22 0.114576E+09 0.107110E+09
August 0.127649E+09 39665381.65 87983884.11 0.180826E+09 0.112583E+09
September 0.169633E+09 84271997.25 85361016.36 0.248891E+09 0.126250E+09
October 0.229527E+09 0.154145E+09 75382524.23 0.344836E+09 0.139471E+09
November 0.269811E+09 0.191168E+09 78643662.32 0.371996E+09 0.185518E+09
December 0.309701E+09 0.236001E+09 73700801.82 0.431911E+09 0.208877E+09
           
Annual Sum or Average 0.223009E+10 0.122031E+10 0.100979E+10 0.295901E+10 0.190615E+10
Minimum of Months 91201314.76 5348990.16 73700801.82 84991350.10 0.107110E+09
Maximum of Months 0.309701E+09 0.236001E+09 94414790.61 0.431911E+09 0.209675E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 43760156.20 0.00 43760156.20 34019471.71 0.154626E+09
February 49614764.83 0.00 49614764.83 35634293.74 0.124636E+09
March 67319355.11 616.43 67318738.68 56270781.27 0.142144E+09
April 75451674.99 607142.96 74844532.02 78142201.77 0.100192E+09
May 93793905.81 4891233.32 88902672.49 0.101321E+09 90028875.26
June 96215879.76 9505192.38 86710687.38 0.122142E+09 63979975.88
July 94177420.20 7991370.67 86186049.53 0.132660E+09 56672599.47
August 78303178.90 1739710.07 76563468.83 0.108703E+09 59208532.35
September 63964957.52 12721.35 63952236.17 82522429.84 70374950.91
October 52424690.20 0.00 52424690.20 74585368.75 84641247.41
November 45935578.62 0.00 45935578.62 38921217.30 0.130119E+09
December 40736986.18 0.00 40736986.18 31413140.04 0.153866E+09
           
Annual Sum or Average 0.801699E+09 24747987.18 0.776951E+09 0.896335E+09 0.123049E+10
Minimum of Months 40736986.18 0.00 40736986.18 31413140.04 56672599.47
Maximum of Months 96215879.76 9505192.38 88902672.49 0.132660E+09 0.154626E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.275166E+09 0.147025E+09 0.128141E+09 0.342296E+09 0.340831E+09
February 0.262263E+09 0.120010E+09 0.142253E+09 0.305643E+09 0.274294E+09
March 0.354372E+09 0.158278E+09 0.196093E+09 0.436529E+09 0.309323E+09
April 0.437142E+09 0.219339E+09 0.217803E+09 0.613563E+09 0.228883E+09
May 0.425471E+09 0.177307E+09 0.248164E+09 0.583590E+09 0.211623E+09
June 0.409660E+09 0.177844E+09 0.231816E+09 0.603608E+09 0.149287E+09
July 0.479370E+09 0.238152E+09 0.241217E+09 0.755704E+09 0.129547E+09
August 0.473790E+09 0.251803E+09 0.221987E+09 0.752677E+09 0.133843E+09
September 0.334756E+09 0.153974E+09 0.180782E+09 0.503721E+09 0.158963E+09
October 0.304860E+09 0.156473E+09 0.148387E+09 0.468695E+09 0.187141E+09
November 0.268319E+09 0.135839E+09 0.132480E+09 0.337155E+09 0.291780E+09
December 0.266542E+09 0.148557E+09 0.117985E+09 0.330745E+09 0.340378E+09
           
Annual Sum or Average 0.429171E+10 0.208460E+10 0.220711E+10 0.603392E+10 0.275589E+10
Minimum of Months 0.262263E+09 0.120010E+09 0.117985E+09 0.305643E+09 0.129547E+09
Maximum of Months 0.479370E+09 0.251803E+09 0.248164E+09 0.755704E+09 0.340831E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.361828E+09 0.265635E+09 96193539.89 0.541335E+09 0.177344E+09
February 0.258155E+09 0.159738E+09 98417302.63 0.366695E+09 0.144907E+09
March 0.227952E+09 0.111040E+09 0.116912E+09 0.319097E+09 0.170008E+09
April 0.184468E+09 71297257.09 0.113171E+09 0.274448E+09 0.129717E+09
May 0.134307E+09 16264703.80 0.118042E+09 0.167378E+09 0.120338E+09
June 0.114024E+09 6687567.42 0.107337E+09 0.145940E+09 83166375.91
July 0.124259E+09 13287466.48 0.110972E+09 0.183528E+09 71085131.01
August 0.159593E+09 49591587.53 0.110002E+09 0.265460E+09 74143374.56
September 0.212083E+09 0.105361E+09 0.106722E+09 0.349696E+09 86714853.83
October 0.286966E+09 0.192719E+09 94246894.73 0.472773E+09 99539033.77
November 0.337331E+09 0.239007E+09 98324128.04 0.506283E+09 0.151277E+09
December 0.387204E+09 0.295059E+09 92144323.65 0.582807E+09 0.175883E+09
           
Annual Sum or Average 0.278817E+10 0.152569E+10 0.126248E+10 0.417544E+10 0.148412E+10
Minimum of Months 0.114024E+09 6687567.42 92144323.65 0.145940E+09 71085131.01
Maximum of Months 0.387204E+09 0.295059E+09 0.118042E+09 0.582807E+09 0.177344E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54692945.39 0.00 54692945.39 39097459.83 0.190875E+09
February 62010236.23 0.00 62010236.23 41431254.90 0.153005E+09
March 84138040.91 770.44 84137270.47 65266438.63 0.175565E+09
April 94302093.46 758828.12 93543265.34 86585169.14 0.127012E+09
May 0.117227E+09 6113231.30 0.111114E+09 0.115696E+09 0.113024E+09
June 0.120254E+09 11879915.73 0.108374E+09 0.141441E+09 80648380.60
July 0.117706E+09 9987889.39 0.107718E+09 0.150759E+09 73267171.78
August 97866000.93 2174349.36 95691651.57 0.120513E+09 77899405.62
September 79945599.65 15899.58 79929700.08 93651378.07 90517615.20
October 65522177.41 0.00 65522177.41 84953980.44 0.108603E+09
November 57411863.01 0.00 57411863.01 44177391.14 0.161991E+09
December 50914483.72 0.00 50914483.72 35340874.04 0.190428E+09
           
Annual Sum or Average 0.100199E+10 30930883.91 0.971059E+09 0.101891E+10 0.154284E+10
Minimum of Months 50914483.72 0.00 50914483.72 35340874.04 73267171.78
Maximum of Months 0.120254E+09 11879915.73 0.111114E+09 0.150759E+09 0.190875E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.275166E+09 0.147025E+09 0.128141E+09 0.356101E+09 0.329489E+09
February 0.262263E+09 0.120010E+09 0.142253E+09 0.315277E+09 0.267332E+09
March 0.354372E+09 0.158278E+09 0.196093E+09 0.444130E+09 0.305061E+09
April 0.437142E+09 0.219339E+09 0.217803E+09 0.614892E+09 0.229930E+09
May 0.425471E+09 0.177307E+09 0.248164E+09 0.578363E+09 0.216083E+09
June 0.409660E+09 0.177844E+09 0.231816E+09 0.591995E+09 0.159475E+09
July 0.479370E+09 0.238152E+09 0.241217E+09 0.739424E+09 0.144218E+09
August 0.473790E+09 0.251803E+09 0.221987E+09 0.739825E+09 0.147211E+09
September 0.334756E+09 0.153974E+09 0.180782E+09 0.502312E+09 0.164585E+09
October 0.304860E+09 0.156473E+09 0.148387E+09 0.471606E+09 0.191647E+09
November 0.268319E+09 0.135839E+09 0.132480E+09 0.348628E+09 0.282763E+09
December 0.266542E+09 0.148557E+09 0.117985E+09 0.344340E+09 0.328595E+09
           
Annual Sum or Average 0.429171E+10 0.208460E+10 0.220711E+10 0.604689E+10 0.276639E+10
Minimum of Months 0.262263E+09 0.120010E+09 0.117985E+09 0.315277E+09 0.144218E+09
Maximum of Months 0.479370E+09 0.251803E+09 0.248164E+09 0.739825E+09 0.329489E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 69265164.40 0.00 69265164.40 50153492.95 0.258274E+09
February 78532051.55 0.00 78532051.55 54052909.39 0.208037E+09
March 0.106556E+09 975.71 0.106555E+09 88898664.86 0.232408E+09
April 0.119428E+09 961007.93 0.118467E+09 0.123686E+09 0.167810E+09
May 0.148460E+09 7742021.72 0.140718E+09 0.162539E+09 0.150061E+09
June 0.152294E+09 15045163.69 0.137249E+09 0.197910E+09 0.106639E+09
July 0.149067E+09 12649031.71 0.136418E+09 0.212472E+09 96670945.36
August 0.123941E+09 2753676.28 0.121187E+09 0.170721E+09 0.103983E+09
September 0.101246E+09 20135.81 0.101226E+09 0.127778E+09 0.123884E+09
October 82979703.47 0.00 82979703.47 0.112536E+09 0.150958E+09
November 72708502.01 0.00 72708502.01 56438990.20 0.223515E+09
December 64479981.11 0.00 64479981.11 44434486.28 0.261490E+09
           
Annual Sum or Average 0.126896E+10 39172012.85 0.122979E+10 0.140162E+10 0.208373E+10
Minimum of Months 64479981.11 0.00 64479981.11 44434486.28 96670945.36
Maximum of Months 0.152294E+09 15045163.69 0.140718E+09 0.212472E+09 0.261490E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25534007.64 0.00 25534007.64 18488654.19 95210540.39
February 28950165.96 0.00 28950165.96 19926140.55 76691239.79
March 39280776.79 359.69 39280417.10 32771728.87 85675050.99
April 44025977.35 354267.32 43671710.04 45595935.81 61861843.93
May 54728650.81 2854029.78 51874621.03 59918552.83 55318863.53
June 56141870.20 5546270.31 50595599.89 72957647.11 39311528.78
July 54952431.07 4662956.84 50289474.23 78325988.67 35636913.29
August 45689827.05 1015119.10 44674707.96 62934922.15 38332468.70
September 37323489.13 7422.89 37316066.23 47104084.98 45668813.98
October 30589754.62 0.00 30589754.62 41485353.21 55649426.61
November 26803364.46 0.00 26803364.46 20805748.74 82396831.66
December 23769990.94 0.00 23769990.94 16380391.53 96396027.52
           
Annual Sum or Average 0.467790E+09 14440425.92 0.453350E+09 0.516695E+09 0.768150E+09
Minimum of Months 23769990.94 0.00 23769990.94 16380391.53 35636913.29
Maximum of Months 56141870.20 5546270.31 51874621.03 78325988.67 96396027.52



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.168828E+09 0.123944E+09 44883518.08 0.256902E+09 86066404.82
February 0.120454E+09 74532974.55 45921116.82 0.174238E+09 71194589.71
March 0.106362E+09 51810842.88 54550856.44 0.153229E+09 82243506.96
April 86072065.12 33267012.85 52805052.27 0.133394E+09 63339709.29
May 62666947.63 7589045.25 55077902.38 82556838.44 59663338.98
June 53203286.04 3120392.01 50082894.03 71853488.84 42715418.41
July 57978940.19 6199878.31 51779061.87 89383188.19 37987274.27
August 74465597.53 23139234.90 51326362.62 0.127404E+09 39889178.38
September 98957276.75 49160992.76 49796283.99 0.166107E+09 45423548.60
October 0.133897E+09 89921883.95 43975221.30 0.222910E+09 52443535.64
November 0.157397E+09 0.111520E+09 45877641.93 0.239558E+09 75024093.86
December 0.180668E+09 0.137674E+09 42994170.10 0.275647E+09 86324495.35
           
Annual Sum or Average 0.130095E+10 0.711880E+09 0.589070E+09 0.199318E+10 0.742315E+09
Minimum of Months 53203286.04 3120392.01 42994170.10 71853488.84 37987274.27
Maximum of Months 0.180668E+09 0.137674E+09 55077902.38 0.275647E+09 86324495.35



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.458233E+09 0.336410E+09 0.121823E+09 0.697284E+09 0.233602E+09
February 0.326937E+09 0.202298E+09 0.124639E+09 0.472918E+09 0.193237E+09
March 0.288687E+09 0.140625E+09 0.148062E+09 0.415895E+09 0.223226E+09
April 0.233617E+09 90293477.49 0.143324E+09 0.362058E+09 0.171918E+09
May 0.170091E+09 20598221.12 0.149493E+09 0.224076E+09 0.161939E+09
June 0.144405E+09 8469382.17 0.135935E+09 0.195025E+09 0.115938E+09
July 0.157367E+09 16827737.90 0.140539E+09 0.242604E+09 0.103105E+09
August 0.202115E+09 62804616.55 0.139310E+09 0.345802E+09 0.108267E+09
September 0.268590E+09 0.133433E+09 0.135157E+09 0.450849E+09 0.123289E+09
October 0.363424E+09 0.244066E+09 0.119358E+09 0.605022E+09 0.142342E+09
November 0.427209E+09 0.302688E+09 0.124521E+09 0.650209E+09 0.203631E+09
December 0.490369E+09 0.373674E+09 0.116695E+09 0.748163E+09 0.234302E+09
           
Annual Sum or Average 0.353104E+10 0.193219E+10 0.159886E+10 0.540991E+10 0.201480E+10
Minimum of Months 0.144405E+09 8469382.17 0.116695E+09 0.195025E+09 0.103105E+09
Maximum of Months 0.490369E+09 0.373674E+09 0.149493E+09 0.748163E+09 0.234302E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.361828E+09 0.265635E+09 96193539.89 0.541057E+09 0.175701E+09
February 0.258155E+09 0.159738E+09 98417302.63 0.364789E+09 0.144508E+09
March 0.227952E+09 0.111040E+09 0.116912E+09 0.318178E+09 0.170274E+09
April 0.184468E+09 71297257.09 0.113171E+09 0.272678E+09 0.131306E+09
May 0.134307E+09 16264703.80 0.118042E+09 0.165425E+09 0.122299E+09
June 0.114024E+09 6687567.42 0.107337E+09 0.143617E+09 85444082.18
July 0.124259E+09 13287466.48 0.110972E+09 0.181924E+09 73136450.76
August 0.159593E+09 49591587.53 0.110002E+09 0.263758E+09 75717980.48
September 0.212083E+09 0.105361E+09 0.106722E+09 0.346231E+09 88495116.30
October 0.286966E+09 0.192719E+09 94246894.73 0.470479E+09 99302232.29
November 0.337331E+09 0.239007E+09 98324128.04 0.504270E+09 0.150681E+09
December 0.387204E+09 0.295059E+09 92144323.65 0.581801E+09 0.174271E+09
           
Annual Sum or Average 0.278817E+10 0.152569E+10 0.126248E+10 0.415421E+10 0.149114E+10
Minimum of Months 0.114024E+09 6687567.42 92144323.65 0.143617E+09 73136450.76
Maximum of Months 0.387204E+09 0.295059E+09 0.118042E+09 0.581801E+09 0.175701E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.262209E+09 0.132231E+09 0.129978E+09 0.332138E+09 0.353415E+09
February 0.282852E+09 0.130735E+09 0.152118E+09 0.344666E+09 0.282103E+09
March 0.358163E+09 0.158278E+09 0.199885E+09 0.446873E+09 0.320362E+09
April 0.477695E+09 0.248345E+09 0.229350E+09 0.673707E+09 0.236671E+09
May 0.484896E+09 0.223633E+09 0.261263E+09 0.670096E+09 0.216691E+09
June 0.496986E+09 0.248157E+09 0.248829E+09 0.729632E+09 0.149738E+09
July 0.543784E+09 0.290681E+09 0.253103E+09 0.845053E+09 0.128440E+09
August 0.510259E+09 0.276292E+09 0.233967E+09 0.798687E+09 0.135491E+09
September 0.423190E+09 0.226362E+09 0.196828E+09 0.638409E+09 0.160235E+09
October 0.335903E+09 0.184044E+09 0.151860E+09 0.521421E+09 0.192535E+09
November 0.292523E+09 0.153116E+09 0.139407E+09 0.383209E+09 0.298590E+09
December 0.265882E+09 0.142163E+09 0.123718E+09 0.343230E+09 0.351547E+09
           
Annual Sum or Average 0.473434E+10 0.241404E+10 0.232031E+10 0.672712E+10 0.282582E+10
Minimum of Months 0.262209E+09 0.130735E+09 0.123718E+09 0.332138E+09 0.128440E+09
Maximum of Months 0.543784E+09 0.290681E+09 0.261263E+09 0.845053E+09 0.353415E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54692945.39 0.00 54692945.39 42050173.12 0.188343E+09
February 62010236.23 0.00 62010236.23 43159363.34 0.152781E+09
March 84138040.91 770.44 84137270.47 66525228.12 0.176196E+09
April 94302093.46 758828.12 93543265.34 85123783.14 0.131398E+09
May 0.117227E+09 6113231.30 0.111114E+09 0.111789E+09 0.117082E+09
June 0.120254E+09 11879915.73 0.108374E+09 0.134110E+09 87493561.67
July 0.117706E+09 9987889.39 0.107718E+09 0.145274E+09 81109577.71
August 97866000.93 2174349.36 95691651.57 0.118516E+09 85564720.38
September 79945599.65 15899.58 79929700.08 91788987.95 96789764.52
October 65522177.41 0.00 65522177.41 86728597.02 0.110109E+09
November 57411863.01 0.00 57411863.01 46381002.23 0.162004E+09
December 50914483.72 0.00 50914483.72 38901004.70 0.188025E+09
           
Annual Sum or Average 0.100199E+10 30930883.91 0.971059E+09 0.101035E+10 0.157690E+10
Minimum of Months 50914483.72 0.00 50914483.72 38901004.70 81109577.71
Maximum of Months 0.120254E+09 11879915.73 0.111114E+09 0.145274E+09 0.188343E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.262209E+09 0.132231E+09 0.129978E+09 0.349340E+09 0.342993E+09
February 0.282852E+09 0.130735E+09 0.152118E+09 0.355692E+09 0.276009E+09
March 0.358163E+09 0.158278E+09 0.199885E+09 0.454206E+09 0.317173E+09
April 0.477695E+09 0.248345E+09 0.229350E+09 0.669914E+09 0.241363E+09
May 0.484896E+09 0.223633E+09 0.261263E+09 0.658765E+09 0.224849E+09
June 0.496986E+09 0.248157E+09 0.248829E+09 0.707600E+09 0.167613E+09
July 0.543784E+09 0.290681E+09 0.253103E+09 0.819688E+09 0.152641E+09
August 0.510259E+09 0.276292E+09 0.233967E+09 0.780992E+09 0.158334E+09
September 0.423190E+09 0.226362E+09 0.196828E+09 0.633433E+09 0.171748E+09
October 0.335903E+09 0.184044E+09 0.151860E+09 0.525062E+09 0.199336E+09
November 0.292523E+09 0.153116E+09 0.139407E+09 0.397187E+09 0.291875E+09
December 0.265882E+09 0.142163E+09 0.123718E+09 0.361113E+09 0.340761E+09
           
Annual Sum or Average 0.473434E+10 0.241404E+10 0.232031E+10 0.671299E+10 0.288469E+10
Minimum of Months 0.262209E+09 0.130735E+09 0.123718E+09 0.349340E+09 0.152641E+09
Maximum of Months 0.543784E+09 0.290681E+09 0.261263E+09 0.819688E+09 0.342993E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.530656E+09 0.389579E+09 0.141077E+09 0.781202E+09 0.268639E+09
February 0.378609E+09 0.234271E+09 0.144338E+09 0.526961E+09 0.219027E+09
March 0.334314E+09 0.162851E+09 0.171463E+09 0.460824E+09 0.254431E+09
April 0.270540E+09 0.104564E+09 0.165976E+09 0.401122E+09 0.189780E+09
May 0.196974E+09 23853749.05 0.173120E+09 0.248408E+09 0.173967E+09
June 0.167228E+09 9807959.43 0.157420E+09 0.219367E+09 0.118490E+09
July 0.182238E+09 19487344.79 0.162751E+09 0.276736E+09 99513685.10
August 0.234059E+09 72730822.43 0.161328E+09 0.393223E+09 0.104857E+09
September 0.311041E+09 0.154522E+09 0.156519E+09 0.508849E+09 0.126782E+09
October 0.420863E+09 0.282641E+09 0.138222E+09 0.686444E+09 0.147065E+09
November 0.494729E+09 0.350527E+09 0.144202E+09 0.730187E+09 0.228663E+09
December 0.567871E+09 0.432733E+09 0.135138E+09 0.840700E+09 0.266506E+09
           
Annual Sum or Average 0.408912E+10 0.223757E+10 0.185155E+10 0.607402E+10 0.219772E+10
Minimum of Months 0.167228E+09 9807959.43 0.135138E+09 0.219367E+09 99513685.10
Maximum of Months 0.567871E+09 0.432733E+09 0.173120E+09 0.840700E+09 0.268639E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.382836E+09 0.00 0.382836E+09 0.261219E+09 0.149622E+10
February 0.434055E+09 0.00 0.434055E+09 0.271888E+09 0.123703E+10
March 0.588944E+09 5392.86 0.588939E+09 0.443605E+09 0.139770E+10
April 0.660090E+09 5311595.66 0.654778E+09 0.631773E+09 0.100870E+10
May 0.820557E+09 42790998.43 0.777766E+09 0.824546E+09 0.910123E+09
June 0.841745E+09 83156260.58 0.758589E+09 0.102750E+10 0.655906E+09
July 0.823912E+09 69912577.80 0.753999E+09 0.113586E+10 0.579394E+09
August 0.685036E+09 15219869.11 0.669816E+09 0.925395E+09 0.617153E+09
September 0.559598E+09 111292.82 0.559487E+09 0.688125E+09 0.728463E+09
October 0.458638E+09 0.00 0.458638E+09 0.625358E+09 0.865045E+09
November 0.401868E+09 0.00 0.401868E+09 0.299751E+09 0.128541E+10
December 0.356388E+09 0.00 0.356388E+09 0.237774E+09 0.149648E+10
           
Annual Sum or Average 0.701367E+10 0.216508E+09 0.679716E+10 0.737280E+10 0.122776E+11
Minimum of Months 0.356388E+09 0.00 0.356388E+09 0.237774E+09 0.579394E+09
Maximum of Months 0.841745E+09 83156260.58 0.777766E+09 0.113586E+10 0.149648E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.382836E+09 0.00 0.382836E+09 0.239851E+09 0.156078E+10
February 0.434055E+09 0.00 0.434055E+09 0.250052E+09 0.129557E+10
March 0.588944E+09 5392.86 0.588939E+09 0.414254E+09 0.146059E+10
April 0.660090E+09 5311595.66 0.654778E+09 0.598860E+09 0.105370E+10
May 0.820557E+09 42790998.43 0.777766E+09 0.783177E+09 0.949077E+09
June 0.841745E+09 83156260.58 0.758589E+09 0.988171E+09 0.686615E+09
July 0.823912E+09 69912577.80 0.753999E+09 0.109746E+10 0.608064E+09
August 0.685036E+09 15219869.11 0.669816E+09 0.891330E+09 0.648778E+09
September 0.559598E+09 111292.82 0.559487E+09 0.660452E+09 0.765822E+09
October 0.458638E+09 0.00 0.458638E+09 0.599775E+09 0.907425E+09
November 0.401868E+09 0.00 0.401868E+09 0.278367E+09 0.134094E+10
December 0.356388E+09 0.00 0.356388E+09 0.217664E+09 0.155860E+10
           
Annual Sum or Average 0.701367E+10 0.216508E+09 0.679716E+10 0.701942E+10 0.128360E+11
Minimum of Months 0.356388E+09 0.00 0.356388E+09 0.217664E+09 0.608064E+09
Maximum of Months 0.841745E+09 83156260.58 0.777766E+09 0.109746E+10 0.156078E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54692945.39 0.00 54692945.39 49398331.68 0.209287E+09
February 62010236.23 0.00 62010236.23 49856422.45 0.177760E+09
March 84138040.91 770.44 84137270.47 78550254.44 0.202524E+09
April 94302093.46 758828.12 93543265.34 0.112166E+09 0.147726E+09
May 0.117227E+09 6113231.30 0.111114E+09 0.146297E+09 0.136591E+09
June 0.120254E+09 11879915.73 0.108374E+09 0.179287E+09 99050985.77
July 0.117706E+09 9987889.39 0.107718E+09 0.197940E+09 87748622.41
August 97866000.93 2174349.36 95691651.57 0.164309E+09 92160208.54
September 79945599.65 15899.58 79929700.08 0.123438E+09 0.102711E+09
October 65522177.41 0.00 65522177.41 0.112039E+09 0.121114E+09
November 57411863.01 0.00 57411863.01 56062033.74 0.179187E+09
December 50914483.72 0.00 50914483.72 45917198.24 0.208939E+09
           
Annual Sum or Average 0.100199E+10 30930883.91 0.971059E+09 0.131526E+10 0.176480E+10
Minimum of Months 50914483.72 0.00 50914483.72 45917198.24 87748622.41
Maximum of Months 0.120254E+09 11879915.73 0.111114E+09 0.197940E+09 0.209287E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.550293E+09 0.294029E+09 0.256264E+09 0.764058E+09 0.735561E+09
February 0.524489E+09 0.240003E+09 0.284486E+09 0.667254E+09 0.632219E+09
March 0.708693E+09 0.316534E+09 0.392159E+09 0.945776E+09 0.716412E+09
April 0.874222E+09 0.438646E+09 0.435576E+09 0.133365E+10 0.539019E+09
May 0.850882E+09 0.354589E+09 0.496293E+09 0.127027E+10 0.515719E+09
June 0.819263E+09 0.355663E+09 0.463600E+09 0.132419E+10 0.381755E+09
July 0.958671E+09 0.476271E+09 0.482400E+09 0.165582E+10 0.337577E+09
August 0.947513E+09 0.503571E+09 0.443942E+09 0.164915E+10 0.347238E+09
September 0.669465E+09 0.307927E+09 0.361538E+09 0.112607E+10 0.380446E+09
October 0.609676E+09 0.312923E+09 0.296753E+09 0.105509E+10 0.436580E+09
November 0.536599E+09 0.271659E+09 0.264940E+09 0.750314E+09 0.635820E+09
December 0.533045E+09 0.297092E+09 0.235953E+09 0.738770E+09 0.733521E+09
           
Annual Sum or Average 0.858281E+10 0.416891E+10 0.441391E+10 0.132804E+11 0.639187E+10
Minimum of Months 0.524489E+09 0.240003E+09 0.235953E+09 0.667254E+09 0.337577E+09
Maximum of Months 0.958671E+09 0.503571E+09 0.496293E+09 0.165582E+10 0.735561E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.361828E+09 0.265635E+09 96193539.89 0.569012E+09 0.194359E+09
February 0.258155E+09 0.159738E+09 98417302.63 0.385256E+09 0.169137E+09
March 0.227952E+09 0.111040E+09 0.116912E+09 0.340421E+09 0.197232E+09
April 0.184468E+09 71297257.09 0.113171E+09 0.302395E+09 0.150747E+09
May 0.134307E+09 16264703.80 0.118042E+09 0.193545E+09 0.144969E+09
June 0.114024E+09 6687567.42 0.107337E+09 0.176565E+09 0.105239E+09
July 0.124259E+09 13287466.48 0.110972E+09 0.221588E+09 91524091.61
August 0.159593E+09 49591587.53 0.110002E+09 0.303643E+09 94521248.30
September 0.212083E+09 0.105361E+09 0.106722E+09 0.382050E+09 0.102813E+09
October 0.286966E+09 0.192719E+09 94246894.73 0.506500E+09 0.117117E+09
November 0.337331E+09 0.239007E+09 98324128.04 0.532530E+09 0.168128E+09
December 0.387204E+09 0.295059E+09 92144323.65 0.610324E+09 0.192996E+09
           
Annual Sum or Average 0.278817E+10 0.152569E+10 0.126248E+10 0.452383E+10 0.172878E+10
Minimum of Months 0.114024E+09 6687567.42 92144323.65 0.176565E+09 91524091.61
Maximum of Months 0.387204E+09 0.295059E+09 0.118042E+09 0.610324E+09 0.197232E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 69265164.40 0.00 69265164.40 38339720.05 0.281283E+09
February 78532051.55 0.00 78532051.55 41758454.54 0.230480E+09
March 0.106556E+09 975.71 0.106555E+09 72259926.91 0.256450E+09
April 0.119428E+09 961007.93 0.118467E+09 0.100252E+09 0.191789E+09
May 0.148460E+09 7742021.72 0.140718E+09 0.134397E+09 0.171787E+09
June 0.152294E+09 15045163.69 0.137249E+09 0.166394E+09 0.127709E+09
July 0.149067E+09 12649031.71 0.136418E+09 0.181524E+09 0.116526E+09
August 0.123941E+09 2753676.28 0.121187E+09 0.144048E+09 0.125616E+09
September 0.101246E+09 20135.81 0.101226E+09 0.105920E+09 0.148254E+09
October 82979703.47 0.00 82979703.47 94928452.54 0.174805E+09
November 72708502.01 0.00 72708502.01 43561293.62 0.247241E+09
December 64479981.11 0.00 64479981.11 33154968.26 0.284677E+09
           
Annual Sum or Average 0.126896E+10 39172012.85 0.122979E+10 0.115654E+10 0.235662E+10
Minimum of Months 64479981.11 0.00 64479981.11 33154968.26 0.116526E+09
Maximum of Months 0.152294E+09 15045163.69 0.140718E+09 0.181524E+09 0.284677E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 61971805.04 0.00 61971805.04 34302692.80 0.251642E+09
February 70262924.08 0.00 70262924.08 37361447.50 0.206211E+09
March 95335627.48 872.97 95334754.51 64651230.40 0.229447E+09
April 0.106852E+09 859817.44 0.105993E+09 89695527.55 0.171594E+09
May 0.132828E+09 6926816.17 0.125901E+09 0.120245E+09 0.153699E+09
June 0.136258E+09 13460964.96 0.122797E+09 0.148873E+09 0.114261E+09
July 0.133371E+09 11317136.59 0.122054E+09 0.162410E+09 0.104256E+09
August 0.110891E+09 2463724.60 0.108427E+09 0.128880E+09 0.112389E+09
September 90585231.42 18015.59 90567215.84 94767129.92 0.132644E+09
October 74242255.10 0.00 74242255.10 84932846.17 0.156398E+09
November 65052572.24 0.00 65052572.24 38974454.46 0.221205E+09
December 57690483.41 0.00 57690483.41 29663875.73 0.254669E+09
           
Annual Sum or Average 0.113534E+10 35047348.32 0.110029E+10 0.103476E+10 0.210842E+10
Minimum of Months 57690483.41 0.00 57690483.41 29663875.73 0.104256E+09
Maximum of Months 0.136258E+09 13460964.96 0.125901E+09 0.162410E+09 0.254669E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.135081E+10 0.991693E+09 0.359119E+09 0.199712E+10 0.745957E+09
February 0.963770E+09 0.596348E+09 0.367421E+09 0.133637E+10 0.627888E+09
March 0.851014E+09 0.414546E+09 0.436469E+09 0.116258E+10 0.725836E+09
April 0.688674E+09 0.266174E+09 0.422500E+09 0.992397E+09 0.580154E+09
May 0.501407E+09 60720985.93 0.440686E+09 0.582264E+09 0.551215E+09
June 0.425687E+09 24966681.96 0.400720E+09 0.492181E+09 0.414184E+09
July 0.463897E+09 49606071.82 0.414291E+09 0.631922E+09 0.371631E+09
August 0.595809E+09 0.185140E+09 0.410669E+09 0.940410E+09 0.388009E+09
September 0.791771E+09 0.393344E+09 0.398427E+09 0.125528E+10 0.434429E+09
October 0.107133E+10 0.719477E+09 0.351852E+09 0.171433E+10 0.484630E+09
November 0.125936E+10 0.892285E+09 0.367073E+09 0.185340E+10 0.659527E+09
December 0.144555E+10 0.110154E+10 0.344002E+09 0.214446E+10 0.746743E+09
           
Annual Sum or Average 0.104091E+11 0.569585E+10 0.471323E+10 0.151027E+11 0.673020E+10
Minimum of Months 0.425687E+09 24966681.96 0.344002E+09 0.492181E+09 0.371631E+09
Maximum of Months 0.144555E+10 0.110154E+10 0.440686E+09 0.214446E+10 0.746743E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1004.42 362.07 683.25 501.61 181.64 0.00 0.00
February 758.26 324.89 539.71 333.96 205.76 0.00 0.00
March 600.11 333.41 430.45 209.68 220.77 0.00 0.00
April 531.37 275.57 359.95 139.12 220.83 0.00 0.00
May 319.39 241.27 253.61 30.71 222.90 0.00 0.00
June 281.26 185.48 222.49 13.05 209.44 0.00 0.00
July 334.19 166.67 234.64 25.09 209.55 0.00 0.00
August 483.55 179.57 301.36 93.65 207.72 0.00 0.00
September 663.19 210.71 413.83 205.59 208.24 0.00 0.00
October 871.18 230.86 541.89 363.92 177.97 0.00 0.00
November 969.82 328.75 658.23 466.37 191.86 0.00 0.00
December 1081.12 363.80 731.17 557.17 174.00 0.00 0.00
               
Annual Sum or Average 657.84 266.63 447.16 244.69 202.47 0.00 0.00
Minimum of Months 281.26 166.67 222.49 13.05 174.00 0.00 0.00
Maximum of Months 1081.12 363.80 731.17 557.17 222.90 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2842.73 1000.98 1924.00 1412.50 511.50 0.00 0.00
February 2153.14 903.35 1519.80 940.40 579.39 0.00 0.00
March 1710.51 931.73 1212.12 590.45 621.67 0.00 0.00
April 1543.65 739.16 1013.59 391.76 621.83 0.00 0.00
May 938.66 653.80 714.16 86.49 627.67 0.00 0.00
June 847.06 482.84 626.52 36.75 589.77 0.00 0.00
July 1020.78 409.94 660.73 70.66 590.08 0.00 0.00
August 1442.89 439.37 848.62 263.70 584.92 0.00 0.00
September 1924.34 535.02 1165.33 578.93 586.40 0.00 0.00
October 2489.84 603.62 1525.92 1024.77 501.15 0.00 0.00
November 2752.06 893.95 1853.53 1313.27 540.26 0.00 0.00
December 3054.46 1002.00 2058.93 1568.96 489.97 0.00 0.00
               
Annual Sum or Average 1892.60 715.36 1259.18 689.03 570.15 0.00 0.00
Minimum of Months 847.06 409.94 626.52 36.75 489.97 0.00 0.00
Maximum of Months 3054.46 1002.00 2058.93 1568.96 627.67 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3750.03 1375.61 2499.38 1834.91 664.47 0.00 0.00
February 2831.40 1260.58 1974.30 1221.64 752.67 0.00 0.00
March 2241.52 1306.42 1574.61 767.03 807.58 0.00 0.00
April 2015.23 1050.30 1316.71 508.91 807.79 0.00 0.00
May 1200.97 946.96 927.73 112.35 815.38 0.00 0.00
June 1073.59 714.55 813.89 47.74 766.15 0.00 0.00
July 1302.77 612.10 858.33 91.79 766.54 0.00 0.00
August 1871.92 642.93 1102.41 342.56 759.84 0.00 0.00
September 2520.55 766.51 1513.82 752.06 761.77 0.00 0.00
October 3276.02 846.75 1982.26 1331.24 651.02 0.00 0.00
November 3627.14 1237.33 2407.84 1706.01 701.82 0.00 0.00
December 4033.35 1375.44 2674.67 2038.17 636.50 0.00 0.00
               
Annual Sum or Average 2477.67 1010.00 1635.75 895.09 740.66 0.00 0.00
Minimum of Months 1073.59 612.10 813.89 47.74 636.50 0.00 0.00
Maximum of Months 4033.35 1375.61 2674.67 2038.17 815.38 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 322.25 194.45 232.99 148.55 84.44 0.00 0.00
February 292.95 175.72 223.63 120.07 103.56 0.00 0.00
March 286.98 182.52 218.83 100.55 118.28 0.00 0.00
April 368.73 141.20 255.46 123.32 132.15 0.00 0.00
May 315.36 125.45 231.18 89.57 141.62 0.00 0.00
June 340.61 89.45 235.73 98.32 137.41 0.00 0.00
July 387.28 74.51 249.42 113.49 135.93 0.00 0.00
August 400.74 78.64 250.09 121.67 128.42 0.00 0.00
September 383.30 96.06 245.09 127.98 117.11 0.00 0.00
October 371.91 109.55 232.55 140.67 91.89 0.00 0.00
November 340.96 171.94 243.00 151.28 91.72 0.00 0.00
December 340.69 193.02 243.83 163.24 80.59 0.00 0.00
               
Annual Sum or Average 346.28 135.84 238.54 124.93 113.61 0.00 0.00
Minimum of Months 286.98 74.51 218.83 89.57 80.59 0.00 0.00
Maximum of Months 400.74 194.45 255.46 163.24 141.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 144.52 200.52 118.32 49.37 68.95 0.00 0.00
February 163.88 178.42 142.55 54.04 88.51 0.00 0.00
March 194.93 183.64 165.14 59.09 106.04 0.00 0.00
April 295.62 142.24 220.68 96.10 124.57 0.00 0.00
May 292.74 125.92 224.81 85.78 139.03 0.00 0.00
June 331.40 95.15 238.13 100.32 137.81 0.00 0.00
July 366.94 83.83 246.97 112.26 134.72 0.00 0.00
August 341.20 88.05 227.05 103.97 123.08 0.00 0.00
September 282.46 101.71 194.11 87.34 106.77 0.00 0.00
October 228.91 116.31 149.88 68.71 81.16 0.00 0.00
November 169.47 176.56 135.01 59.07 75.93 0.00 0.00
December 146.82 200.05 118.28 53.08 65.20 0.00 0.00
               
Annual Sum or Average 247.00 140.86 181.90 77.53 104.37 0.00 0.00
Minimum of Months 144.52 83.83 118.28 49.37 65.20 0.00 0.00
Maximum of Months 366.94 200.52 246.97 112.26 139.03 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 149.32 78.28 108.05 79.33 28.73 0.00 0.00
February 108.86 73.85 85.35 52.81 32.54 0.00 0.00
March 83.71 75.63 68.07 33.16 34.91 0.00 0.00
April 73.62 62.98 56.92 22.00 34.92 0.00 0.00
May 38.33 57.52 40.11 4.86 35.25 0.00 0.00
June 32.79 45.58 35.19 2.06 33.12 0.00 0.00
July 42.78 39.99 37.11 3.97 33.14 0.00 0.00
August 67.51 42.03 47.66 14.81 32.85 0.00 0.00
September 96.02 48.71 65.44 32.51 32.93 0.00 0.00
October 128.75 52.07 85.70 57.55 28.14 0.00 0.00
November 143.52 71.57 104.09 73.75 30.34 0.00 0.00
December 161.26 77.99 115.63 88.11 27.52 0.00 0.00
               
Annual Sum or Average 93.83 60.44 70.72 38.70 32.02 0.00 0.00
Minimum of Months 32.79 39.99 35.19 2.06 27.52 0.00 0.00
Maximum of Months 161.26 78.28 115.63 88.11 35.25 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 12.70 57.73 16.34 0.00 16.34 0.00 0.00
February 14.73 51.52 20.51 0.00 20.51 0.00 0.00
March 21.01 53.07 25.13 0.00 25.13 0.00 0.00
April 30.15 38.65 29.11 0.23 28.88 0.00 0.00
May 37.83 33.61 35.02 1.83 33.19 0.00 0.00
June 47.12 24.68 37.12 3.67 33.45 0.00 0.00
July 49.53 21.16 35.16 2.98 32.18 0.00 0.00
August 40.58 22.11 29.24 0.65 28.59 0.00 0.00
September 31.84 27.15 24.68 0.00 24.67 0.00 0.00
October 27.85 31.60 19.57 0.00 19.57 0.00 0.00
November 15.02 50.20 17.72 0.00 17.72 0.00 0.00
December 11.73 57.45 15.21 0.00 15.21 0.00 0.00
               
Annual Sum or Average 28.42 39.02 25.42 0.78 24.64 0.00 0.00
Minimum of Months 11.73 21.16 15.21 0.00 15.21 0.00 0.00
Maximum of Months 49.53 57.73 37.12 3.67 33.45 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 327.03 190.58 237.83 154.07 83.76 0.00 0.00
February 275.77 171.13 215.12 115.64 99.48 0.00 0.00
March 279.45 176.29 217.41 100.55 116.86 0.00 0.00
April 340.36 136.11 239.82 112.13 127.69 0.00 0.00
May 278.10 121.66 209.00 72.27 136.73 0.00 0.00
June 288.06 88.56 202.04 71.19 130.85 0.00 0.00
July 350.17 74.41 225.37 93.88 131.49 0.00 0.00
August 379.34 76.87 236.48 112.53 123.95 0.00 0.00
September 328.61 94.14 210.97 100.05 110.92 0.00 0.00
October 350.48 106.01 220.96 130.37 90.59 0.00 0.00
November 322.84 168.37 233.66 144.62 89.04 0.00 0.00
December 338.08 189.75 244.08 165.63 78.45 0.00 0.00
               
Annual Sum or Average 321.92 132.63 224.50 114.48 110.02 0.00 0.00
Minimum of Months 275.77 74.41 202.04 71.19 78.45 0.00 0.00
Maximum of Months 379.34 190.58 244.08 165.63 136.73 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 142.60 189.33 123.16 54.89 68.26 0.00 0.00
February 143.87 170.18 134.04 49.61 84.43 0.00 0.00
March 186.00 175.25 163.72 59.09 104.63 0.00 0.00
April 268.70 135.77 205.03 84.91 120.12 0.00 0.00
May 257.97 121.71 202.62 68.48 134.14 0.00 0.00
June 281.32 91.00 204.44 73.20 131.25 0.00 0.00
July 331.04 79.88 222.92 92.64 130.28 0.00 0.00
August 320.60 83.44 213.43 94.82 118.61 0.00 0.00
September 229.14 97.63 159.99 59.41 100.58 0.00 0.00
October 205.65 109.95 138.28 58.42 79.86 0.00 0.00
November 147.70 167.74 125.67 52.41 73.26 0.00 0.00
December 136.68 188.71 118.52 55.46 63.06 0.00 0.00
               
Annual Sum or Average 221.45 134.04 167.86 67.08 100.78 0.00 0.00
Minimum of Months 136.68 79.88 118.52 49.61 63.06 0.00 0.00
Maximum of Months 331.04 189.33 222.92 94.82 134.14 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 373.01 242.46 269.51 171.88 97.64 0.00 0.00
February 293.42 222.33 229.36 114.43 114.93 0.00 0.00
March 256.20 231.09 201.94 71.85 130.10 0.00 0.00
April 256.14 179.05 186.40 48.18 138.22 0.00 0.00
May 195.57 157.45 162.76 14.48 148.28 0.00 0.00
June 204.67 114.72 156.65 12.42 144.24 0.00 0.00
July 230.51 100.07 156.57 15.06 141.51 0.00 0.00
August 263.25 107.79 166.60 33.49 133.10 0.00 0.00
September 305.39 130.40 195.26 70.46 124.81 0.00 0.00
October 364.33 147.58 228.08 124.70 103.38 0.00 0.00
November 366.44 218.89 263.93 159.80 104.13 0.00 0.00
December 394.85 243.23 283.49 190.92 92.57 0.00 0.00
               
Annual Sum or Average 292.07 174.35 208.29 85.54 122.75 0.00 0.00
Minimum of Months 195.57 100.07 156.57 12.42 92.57 0.00 0.00
Maximum of Months 394.85 243.23 283.49 190.92 148.28 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 320.35 191.88 232.99 148.55 84.44 0.00 0.00
February 290.23 173.32 223.63 120.07 103.56 0.00 0.00
March 283.42 180.97 218.83 100.55 118.28 0.00 0.00
April 363.29 140.14 255.46 123.32 132.15 0.00 0.00
May 309.98 124.60 231.18 89.57 141.62 0.00 0.00
June 334.96 88.79 235.73 98.32 137.41 0.00 0.00
July 381.93 73.76 249.42 113.49 135.93 0.00 0.00
August 395.58 77.77 250.09 121.67 128.42 0.00 0.00
September 378.70 94.79 245.09 127.98 117.11 0.00 0.00
October 368.95 107.57 232.55 140.67 91.89 0.00 0.00
November 338.45 169.39 243.00 151.28 91.72 0.00 0.00
December 339.03 189.98 243.83 163.24 80.59 0.00 0.00
               
Annual Sum or Average 342.37 134.21 238.54 124.93 113.61 0.00 0.00
Minimum of Months 283.42 73.76 218.83 89.57 80.59 0.00 0.00
Maximum of Months 395.58 191.88 255.46 163.24 141.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 144.29 196.54 118.32 49.37 68.95 0.00 0.00
February 162.85 175.22 142.55 54.04 88.51 0.00 0.00
March 192.15 181.94 165.14 59.09 106.04 0.00 0.00
April 289.82 142.34 220.68 96.10 124.57 0.00 0.00
May 286.40 126.37 224.81 85.78 139.03 0.00 0.00
June 323.56 97.24 238.13 100.32 137.81 0.00 0.00
July 359.45 86.45 246.97 112.26 134.72 0.00 0.00
August 334.91 90.14 227.05 103.97 123.08 0.00 0.00
September 277.98 101.79 194.11 87.34 106.77 0.00 0.00
October 227.23 114.35 149.88 68.71 81.16 0.00 0.00
November 168.91 172.89 135.01 59.07 75.93 0.00 0.00
December 147.26 195.34 118.28 53.08 65.20 0.00 0.00
               
Annual Sum or Average 243.32 139.89 181.90 77.53 104.37 0.00 0.00
Minimum of Months 144.29 86.45 118.28 49.37 65.20 0.00 0.00
Maximum of Months 359.45 196.54 246.97 112.26 139.03 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 291.67 100.30 198.12 145.45 52.67 0.00 0.00
February 217.82 90.54 156.50 96.84 59.66 0.00 0.00
March 172.05 94.99 124.82 60.80 64.02 0.00 0.00
April 154.75 73.22 104.38 40.34 64.03 0.00 0.00
May 92.75 64.95 73.54 8.91 64.64 0.00 0.00
June 84.63 45.71 64.52 3.78 60.73 0.00 0.00
July 103.32 37.15 68.04 7.28 60.76 0.00 0.00
August 146.81 39.15 87.39 27.15 60.23 0.00 0.00
September 196.32 48.91 120.00 59.61 60.39 0.00 0.00
October 256.29 54.91 157.13 105.53 51.61 0.00 0.00
November 281.71 88.22 190.87 135.23 55.63 0.00 0.00
December 313.88 99.50 212.02 161.56 50.45 0.00 0.00
               
Annual Sum or Average 192.61 69.69 129.67 70.95 58.71 0.00 0.00
Minimum of Months 84.63 37.15 64.52 3.78 50.45 0.00 0.00
Maximum of Months 313.88 100.30 212.02 161.56 64.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 97.53 558.62 142.93 0.00 142.93 0.00 0.00
February 112.39 511.34 179.42 0.00 179.42 0.00 0.00
March 165.62 521.84 219.89 0.00 219.88 0.00 0.00
April 243.74 389.16 254.66 2.05 252.61 0.00 0.00
May 307.85 339.80 306.36 15.98 290.38 0.00 0.00
June 396.41 253.05 324.75 32.08 292.67 0.00 0.00
July 424.08 216.32 307.61 26.10 281.51 0.00 0.00
August 345.50 230.42 255.76 5.68 250.08 0.00 0.00
September 265.48 281.04 215.89 0.04 215.85 0.00 0.00
October 233.48 322.97 171.24 0.00 171.24 0.00 0.00
November 115.64 495.91 155.04 0.00 155.04 0.00 0.00
December 88.77 558.72 133.06 0.00 133.06 0.00 0.00
               
Annual Sum or Average 233.79 389.32 222.40 6.87 215.54 0.00 0.00
Minimum of Months 88.77 216.32 133.06 0.00 133.06 0.00 0.00
Maximum of Months 424.08 558.72 324.75 32.08 292.67 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 89.55 582.73 142.93 0.00 142.93 0.00 0.00
February 103.36 535.54 179.42 0.00 179.42 0.00 0.00
March 154.66 545.32 219.89 0.00 219.88 0.00 0.00
April 231.04 406.52 254.66 2.05 252.61 0.00 0.00
May 292.40 354.34 306.36 15.98 290.38 0.00 0.00
June 381.24 264.90 324.75 32.08 292.67 0.00 0.00
July 409.75 227.03 307.61 26.10 281.51 0.00 0.00
August 332.78 242.23 255.76 5.68 250.08 0.00 0.00
September 254.80 295.46 215.89 0.04 215.85 0.00 0.00
October 223.93 338.79 171.24 0.00 171.24 0.00 0.00
November 107.39 517.34 155.04 0.00 155.04 0.00 0.00
December 81.27 581.92 133.06 0.00 133.06 0.00 0.00
               
Annual Sum or Average 222.58 407.03 222.40 6.87 215.54 0.00 0.00
Minimum of Months 81.27 227.03 133.06 0.00 133.06 0.00 0.00
Maximum of Months 409.75 582.73 324.75 32.08 292.67 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 508.40 417.58 360.97 208.95 152.01 0.00 0.00
February 450.40 399.46 349.15 165.24 183.91 0.00 0.00
March 503.27 410.46 381.12 159.64 221.48 0.00 0.00
April 670.75 319.39 444.83 197.03 247.80 0.00 0.00
May 598.04 294.57 411.59 140.74 270.85 0.00 0.00
June 645.45 223.38 406.46 144.38 262.08 0.00 0.00
July 773.01 191.13 448.27 186.51 261.76 0.00 0.00
August 789.32 198.22 449.88 207.34 242.55 0.00 0.00
September 628.45 225.06 370.95 159.45 211.49 0.00 0.00
October 622.37 249.45 359.23 188.79 170.45 0.00 0.00
November 510.33 373.07 359.31 197.02 162.30 0.00 0.00
December 512.77 415.86 362.59 221.08 141.51 0.00 0.00
               
Annual Sum or Average 602.14 309.33 392.34 181.56 210.79 0.00 0.00
Minimum of Months 450.40 191.13 349.15 140.74 141.51 0.00 0.00
Maximum of Months 789.32 417.58 449.88 221.08 270.85 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 757.63 462.35 553.33 370.26 183.08 0.00 0.00
February 576.51 431.46 459.89 246.51 213.38 0.00 0.00
March 481.99 449.22 393.11 154.77 238.34 0.00 0.00
April 455.68 363.55 352.99 103.39 249.60 0.00 0.00
May 308.83 323.69 292.22 28.15 264.08 0.00 0.00
June 305.66 247.29 275.56 20.63 254.93 0.00 0.00
July 359.82 216.66 278.65 27.47 251.18 0.00 0.00
August 451.84 232.55 310.13 71.07 239.05 0.00 0.00
September 561.43 275.69 379.48 151.77 227.71 0.00 0.00
October 702.92 300.31 458.69 268.62 190.07 0.00 0.00
November 735.04 423.33 539.01 344.25 194.77 0.00 0.00
December 806.95 463.02 585.32 411.27 174.05 0.00 0.00
               
Annual Sum or Average 542.04 348.65 406.31 182.97 223.34 0.00 0.00
Minimum of Months 305.66 216.66 275.56 20.63 174.05 0.00 0.00
Maximum of Months 806.95 463.02 585.32 411.27 264.08 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.269024E+10 0.969778E+09 0.183003E+10 0.134351E+10 0.486517E+09 0.00 0.00
February 0.183438E+10 0.785963E+09 0.130567E+10 0.807910E+09 0.497764E+09 0.00 0.00
March 0.160734E+10 0.893000E+09 0.115292E+10 0.561611E+09 0.591306E+09 0.00 0.00
April 0.137732E+10 0.714285E+09 0.932983E+09 0.360602E+09 0.572380E+09 0.00 0.00
May 0.855451E+09 0.646211E+09 0.679280E+09 82262473.23 0.597017E+09 0.00 0.00
June 0.729021E+09 0.480768E+09 0.576697E+09 33823907.42 0.542873E+09 0.00 0.00
July 0.895089E+09 0.446420E+09 0.628462E+09 67204411.99 0.561258E+09 0.00 0.00
August 0.129514E+10 0.480972E+09 0.807172E+09 0.250821E+09 0.556351E+09 0.00 0.00
September 0.171899E+10 0.546169E+09 0.107265E+10 0.532887E+09 0.539768E+09 0.00 0.00
October 0.233338E+10 0.618330E+09 0.145139E+10 0.974720E+09 0.476671E+09 0.00 0.00
November 0.251378E+10 0.852130E+09 0.170613E+10 0.120883E+10 0.497293E+09 0.00 0.00
December 0.289567E+10 0.974409E+09 0.195837E+10 0.149233E+10 0.466038E+09 0.00 0.00
               
Annual Sum or Average 0.207458E+11 0.840843E+10 0.141018E+11 0.771652E+10 0.638524E+10 0.00 0.00
Minimum of Months 0.729021E+09 0.446420E+09 0.576697E+09 33823907.42 0.466038E+09 0.00 0.00
Maximum of Months 0.289567E+10 0.974409E+09 0.195837E+10 0.149233E+10 0.597017E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.761398E+10 0.268104E+10 0.515323E+10 0.378323E+10 0.137000E+10 0.00 0.00
February 0.520888E+10 0.218538E+10 0.367669E+10 0.227502E+10 0.140167E+10 0.00 0.00
March 0.458142E+10 0.249554E+10 0.324654E+10 0.158146E+10 0.166508E+10 0.00 0.00
April 0.400114E+10 0.191591E+10 0.262722E+10 0.101543E+10 0.161179E+10 0.00 0.00
May 0.251412E+10 0.175115E+10 0.191281E+10 0.231646E+09 0.168116E+10 0.00 0.00
June 0.219558E+10 0.125153E+10 0.162394E+10 95245893.14 0.152869E+10 0.00 0.00
July 0.273405E+10 0.109799E+10 0.176971E+10 0.189243E+09 0.158047E+10 0.00 0.00
August 0.386464E+10 0.117681E+10 0.227294E+10 0.706295E+09 0.156665E+10 0.00 0.00
September 0.498788E+10 0.138678E+10 0.302053E+10 0.150058E+10 0.151995E+10 0.00 0.00
October 0.666879E+10 0.161672E+10 0.408702E+10 0.274475E+10 0.134227E+10 0.00 0.00
November 0.713333E+10 0.231711E+10 0.480434E+10 0.340400E+10 0.140034E+10 0.00 0.00
December 0.818107E+10 0.268376E+10 0.551464E+10 0.420231E+10 0.131233E+10 0.00 0.00
               
Annual Sum or Average 0.596849E+11 0.225597E+11 0.397096E+11 0.217292E+11 0.179804E+11 0.00 0.00
Minimum of Months 0.219558E+10 0.109799E+10 0.162394E+10 95245893.14 0.131233E+10 0.00 0.00
Maximum of Months 0.818107E+10 0.268376E+10 0.551464E+10 0.420231E+10 0.168116E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.100441E+11 0.368445E+10 0.669434E+10 0.491463E+10 0.177971E+10 0.00 0.00
February 0.684973E+10 0.304958E+10 0.477623E+10 0.295538E+10 0.182085E+10 0.00 0.00
March 0.600370E+10 0.349911E+10 0.421744E+10 0.205440E+10 0.216303E+10 0.00 0.00
April 0.522347E+10 0.272239E+10 0.341291E+10 0.131910E+10 0.209380E+10 0.00 0.00
May 0.321668E+10 0.253634E+10 0.248484E+10 0.300921E+09 0.218392E+10 0.00 0.00
June 0.278275E+10 0.185211E+10 0.210959E+10 0.123730E+09 0.198586E+10 0.00 0.00
July 0.348934E+10 0.163944E+10 0.229895E+10 0.245838E+09 0.205311E+10 0.00 0.00
August 0.501375E+10 0.172203E+10 0.295268E+10 0.917517E+09 0.203517E+10 0.00 0.00
September 0.653327E+10 0.198681E+10 0.392383E+10 0.194933E+10 0.197450E+10 0.00 0.00
October 0.877449E+10 0.226794E+10 0.530927E+10 0.356558E+10 0.174369E+10 0.00 0.00
November 0.940156E+10 0.320716E+10 0.624111E+10 0.442199E+10 0.181913E+10 0.00 0.00
December 0.108029E+11 0.368398E+10 0.716383E+10 0.545903E+10 0.170479E+10 0.00 0.00
               
Annual Sum or Average 0.781357E+11 0.318513E+11 0.515850E+11 0.282275E+11 0.233576E+11 0.00 0.00
Minimum of Months 0.278275E+10 0.163944E+10 0.210959E+10 0.123730E+09 0.170479E+10 0.00 0.00
Maximum of Months 0.108029E+11 0.368445E+10 0.716383E+10 0.545903E+10 0.218392E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.863118E+09 0.520804E+09 0.624037E+09 0.397865E+09 0.226172E+09 0.00 0.00
February 0.708700E+09 0.425100E+09 0.541007E+09 0.290473E+09 0.250535E+09 0.00 0.00
March 0.768651E+09 0.488868E+09 0.586116E+09 0.269318E+09 0.316797E+09 0.00 0.00
April 0.955761E+09 0.365995E+09 0.662163E+09 0.319642E+09 0.342521E+09 0.00 0.00
May 0.844660E+09 0.336002E+09 0.619203E+09 0.239898E+09 0.379305E+09 0.00 0.00
June 0.882855E+09 0.231857E+09 0.611010E+09 0.254845E+09 0.356165E+09 0.00 0.00
July 0.103730E+10 0.199564E+09 0.668044E+09 0.303969E+09 0.364075E+09 0.00 0.00
August 0.107334E+10 0.210631E+09 0.669853E+09 0.325884E+09 0.343969E+09 0.00 0.00
September 0.993517E+09 0.248992E+09 0.635273E+09 0.331723E+09 0.303550E+09 0.00 0.00
October 0.996126E+09 0.293426E+09 0.622869E+09 0.376762E+09 0.246107E+09 0.00 0.00
November 0.883766E+09 0.445673E+09 0.629855E+09 0.392124E+09 0.237731E+09 0.00 0.00
December 0.912496E+09 0.516986E+09 0.653085E+09 0.437223E+09 0.215863E+09 0.00 0.00
               
Annual Sum or Average 0.109203E+11 0.428390E+10 0.752252E+10 0.393973E+10 0.358279E+10 0.00 0.00
Minimum of Months 0.708700E+09 0.199564E+09 0.541007E+09 0.239898E+09 0.215863E+09 0.00 0.00
Maximum of Months 0.107334E+10 0.520804E+09 0.669853E+09 0.437223E+09 0.379305E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.387079E+09 0.537082E+09 0.316902E+09 0.132231E+09 0.184671E+09 0.00 0.00
February 0.396469E+09 0.431637E+09 0.344863E+09 0.130735E+09 0.214128E+09 0.00 0.00
March 0.522104E+09 0.491857E+09 0.442301E+09 0.158279E+09 0.284022E+09 0.00 0.00
April 0.766251E+09 0.368680E+09 0.571997E+09 0.249104E+09 0.322893E+09 0.00 0.00
May 0.784088E+09 0.337254E+09 0.602123E+09 0.229746E+09 0.372377E+09 0.00 0.00
June 0.858991E+09 0.246637E+09 0.617240E+09 0.260037E+09 0.357203E+09 0.00 0.00
July 0.982822E+09 0.224543E+09 0.661491E+09 0.300669E+09 0.360821E+09 0.00 0.00
August 0.913874E+09 0.235835E+09 0.608125E+09 0.278467E+09 0.329659E+09 0.00 0.00
September 0.732125E+09 0.263626E+09 0.503135E+09 0.226378E+09 0.276757E+09 0.00 0.00
October 0.613125E+09 0.311514E+09 0.401425E+09 0.184044E+09 0.217382E+09 0.00 0.00
November 0.439259E+09 0.457645E+09 0.349935E+09 0.153116E+09 0.196819E+09 0.00 0.00
December 0.393242E+09 0.535816E+09 0.316796E+09 0.142163E+09 0.174633E+09 0.00 0.00
               
Annual Sum or Average 0.778943E+10 0.444213E+10 0.573633E+10 0.244497E+10 0.329137E+10 0.00 0.00
Minimum of Months 0.387079E+09 0.224543E+09 0.316796E+09 0.130735E+09 0.174633E+09 0.00 0.00
Maximum of Months 0.982822E+09 0.537082E+09 0.661491E+09 0.300669E+09 0.372377E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.399936E+09 0.209675E+09 0.289405E+09 0.212465E+09 76939530.71 0.00 0.00
February 0.263343E+09 0.178656E+09 0.206483E+09 0.127765E+09 78718187.18 0.00 0.00
March 0.224206E+09 0.202573E+09 0.182326E+09 88814382.37 93511326.07 0.00 0.00
April 0.190820E+09 0.163244E+09 0.147545E+09 57026464.64 90518660.62 0.00 0.00
May 0.102673E+09 0.154058E+09 0.107424E+09 13009175.87 94414790.61 0.00 0.00
June 84991350.10 0.118136E+09 91201314.76 5348990.16 85852324.60 0.00 0.00
July 0.114576E+09 0.107110E+09 99387762.81 10627859.59 88759903.22 0.00 0.00
August 0.180826E+09 0.112583E+09 0.127649E+09 39665381.65 87983884.11 0.00 0.00
September 0.248891E+09 0.126250E+09 0.169633E+09 84271997.25 85361016.36 0.00 0.00
October 0.344836E+09 0.139471E+09 0.229527E+09 0.154145E+09 75382524.23 0.00 0.00
November 0.371996E+09 0.185518E+09 0.269811E+09 0.191168E+09 78643662.32 0.00 0.00
December 0.431911E+09 0.208877E+09 0.309701E+09 0.236001E+09 73700801.82 0.00 0.00
               
Annual Sum or Average 0.295901E+10 0.190615E+10 0.223009E+10 0.122031E+10 0.100979E+10 0.00 0.00
Minimum of Months 84991350.10 0.107110E+09 91201314.76 5348990.16 73700801.82 0.00 0.00
Maximum of Months 0.431911E+09 0.209675E+09 0.309701E+09 0.236001E+09 94414790.61 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 34019471.71 0.154626E+09 43760156.20 0.00 43760156.20 0.00 0.00
February 35634293.74 0.124636E+09 49614764.83 0.00 49614764.83 0.00 0.00
March 56270781.27 0.142144E+09 67319355.11 616.43 67318738.68 0.00 0.00
April 78142201.77 0.100192E+09 75451674.99 607142.96 74844532.02 0.00 0.00
May 0.101321E+09 90028875.26 93793905.81 4891233.32 88902672.49 0.00 0.00
June 0.122142E+09 63979975.88 96215879.76 9505192.38 86710687.38 0.00 0.00
July 0.132660E+09 56672599.47 94177420.20 7991370.67 86186049.53 0.00 0.00
August 0.108703E+09 59208532.35 78303178.90 1739710.07 76563468.83 0.00 0.00
September 82522429.84 70374950.91 63964957.52 12721.35 63952236.17 0.00 0.00
October 74585368.75 84641247.41 52424690.20 0.00 52424690.20 0.00 0.00
November 38921217.30 0.130119E+09 45935578.62 0.00 45935578.62 0.00 0.00
December 31413140.04 0.153866E+09 40736986.18 0.00 40736986.18 0.00 0.00
               
Annual Sum or Average 0.896335E+09 0.123049E+10 0.801699E+09 24747987.18 0.776951E+09 0.00 0.00
Minimum of Months 31413140.04 56672599.47 40736986.18 0.00 40736986.18 0.00 0.00
Maximum of Months 0.132660E+09 0.154626E+09 96215879.76 9505192.38 88902672.49 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.875914E+09 0.510458E+09 0.636994E+09 0.412659E+09 0.224335E+09 0.00 0.00
February 0.667132E+09 0.413996E+09 0.520418E+09 0.279748E+09 0.240671E+09 0.00 0.00
March 0.748468E+09 0.472173E+09 0.582324E+09 0.269318E+09 0.313006E+09 0.00 0.00
April 0.882218E+09 0.352807E+09 0.621610E+09 0.290636E+09 0.330974E+09 0.00 0.00
May 0.744857E+09 0.325850E+09 0.559778E+09 0.193572E+09 0.366206E+09 0.00 0.00
June 0.746655E+09 0.229560E+09 0.523685E+09 0.184532E+09 0.339153E+09 0.00 0.00
July 0.937891E+09 0.199291E+09 0.603629E+09 0.251440E+09 0.352189E+09 0.00 0.00
August 0.101603E+10 0.205877E+09 0.633383E+09 0.301395E+09 0.331988E+09 0.00 0.00
September 0.851752E+09 0.244013E+09 0.546840E+09 0.259335E+09 0.287504E+09 0.00 0.00
October 0.938712E+09 0.283925E+09 0.591826E+09 0.349192E+09 0.242634E+09 0.00 0.00
November 0.836802E+09 0.436421E+09 0.605650E+09 0.374846E+09 0.230804E+09 0.00 0.00
December 0.905512E+09 0.508222E+09 0.653745E+09 0.443616E+09 0.210129E+09 0.00 0.00
               
Annual Sum or Average 0.101519E+11 0.418259E+10 0.707988E+10 0.361029E+10 0.346959E+10 0.00 0.00
Minimum of Months 0.667132E+09 0.199291E+09 0.520418E+09 0.184532E+09 0.210129E+09 0.00 0.00
Maximum of Months 0.101603E+10 0.510458E+09 0.653745E+09 0.443616E+09 0.366206E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.381939E+09 0.507105E+09 0.329859E+09 0.147025E+09 0.182834E+09 0.00 0.00
February 0.348060E+09 0.411689E+09 0.324274E+09 0.120010E+09 0.204264E+09 0.00 0.00
March 0.498173E+09 0.469403E+09 0.438510E+09 0.158279E+09 0.280231E+09 0.00 0.00
April 0.696459E+09 0.351925E+09 0.531444E+09 0.220098E+09 0.311347E+09 0.00 0.00
May 0.690944E+09 0.325992E+09 0.542698E+09 0.183420E+09 0.359278E+09 0.00 0.00
June 0.729178E+09 0.235865E+09 0.529914E+09 0.189724E+09 0.340190E+09 0.00 0.00
July 0.886654E+09 0.213956E+09 0.597076E+09 0.248140E+09 0.348936E+09 0.00 0.00
August 0.858704E+09 0.223476E+09 0.571656E+09 0.253978E+09 0.317678E+09 0.00 0.00
September 0.593923E+09 0.253062E+09 0.414702E+09 0.153990E+09 0.260712E+09 0.00 0.00
October 0.550807E+09 0.294498E+09 0.370382E+09 0.156473E+09 0.213909E+09 0.00 0.00
November 0.382836E+09 0.434784E+09 0.325731E+09 0.135839E+09 0.189891E+09 0.00 0.00
December 0.366093E+09 0.505436E+09 0.317456E+09 0.148557E+09 0.168899E+09 0.00 0.00
               
Annual Sum or Average 0.698377E+10 0.422719E+10 0.529370E+10 0.211553E+10 0.317817E+10 0.00 0.00
Minimum of Months 0.348060E+09 0.213956E+09 0.317456E+09 0.120010E+09 0.168899E+09 0.00 0.00
Maximum of Months 0.886654E+09 0.507105E+09 0.597076E+09 0.253978E+09 0.359278E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.999067E+09 0.649392E+09 0.721859E+09 0.460354E+09 0.261506E+09 0.00 0.00
February 0.709839E+09 0.537863E+09 0.554873E+09 0.276831E+09 0.278043E+09 0.00 0.00
March 0.686195E+09 0.618953E+09 0.540885E+09 0.192437E+09 0.348448E+09 0.00 0.00
April 0.663912E+09 0.464107E+09 0.483143E+09 0.124876E+09 0.358267E+09 0.00 0.00
May 0.523826E+09 0.421717E+09 0.435947E+09 38783317.87 0.397164E+09 0.00 0.00
June 0.530498E+09 0.297357E+09 0.406044E+09 32181208.17 0.373863E+09 0.00 0.00
July 0.617406E+09 0.268021E+09 0.419366E+09 40339604.76 0.379026E+09 0.00 0.00
August 0.705100E+09 0.288710E+09 0.446211E+09 89712646.82 0.356499E+09 0.00 0.00
September 0.791571E+09 0.337998E+09 0.506117E+09 0.182622E+09 0.323496E+09 0.00 0.00
October 0.975834E+09 0.395274E+09 0.610891E+09 0.333988E+09 0.276902E+09 0.00 0.00
November 0.949811E+09 0.567366E+09 0.684118E+09 0.414207E+09 0.269911E+09 0.00 0.00
December 0.105757E+10 0.651460E+09 0.759287E+09 0.511348E+09 0.247939E+09 0.00 0.00
               
Annual Sum or Average 0.921063E+10 0.549822E+10 0.656874E+10 0.269768E+10 0.387106E+10 0.00 0.00
Minimum of Months 0.523826E+09 0.268021E+09 0.406044E+09 32181208.17 0.247939E+09 0.00 0.00
Maximum of Months 0.105757E+10 0.651460E+09 0.759287E+09 0.511348E+09 0.397164E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.858017E+09 0.513937E+09 0.624037E+09 0.397865E+09 0.226172E+09 0.00 0.00
February 0.702127E+09 0.419284E+09 0.541007E+09 0.290473E+09 0.250535E+09 0.00 0.00
March 0.759118E+09 0.484704E+09 0.586116E+09 0.269318E+09 0.316797E+09 0.00 0.00
April 0.941646E+09 0.363237E+09 0.662163E+09 0.319642E+09 0.342521E+09 0.00 0.00
May 0.830246E+09 0.333716E+09 0.619203E+09 0.239898E+09 0.379305E+09 0.00 0.00
June 0.868213E+09 0.230146E+09 0.611010E+09 0.254845E+09 0.356165E+09 0.00 0.00
July 0.102297E+10 0.197571E+09 0.668044E+09 0.303969E+09 0.364075E+09 0.00 0.00
August 0.105952E+10 0.208289E+09 0.669853E+09 0.325884E+09 0.343969E+09 0.00 0.00
September 0.981600E+09 0.245690E+09 0.635273E+09 0.331723E+09 0.303550E+09 0.00 0.00
October 0.988186E+09 0.288122E+09 0.622869E+09 0.376762E+09 0.246107E+09 0.00 0.00
November 0.877262E+09 0.439054E+09 0.629855E+09 0.392124E+09 0.237731E+09 0.00 0.00
December 0.908061E+09 0.508849E+09 0.653085E+09 0.437223E+09 0.215863E+09 0.00 0.00
               
Annual Sum or Average 0.107970E+11 0.423260E+10 0.752252E+10 0.393973E+10 0.358279E+10 0.00 0.00
Minimum of Months 0.702127E+09 0.197571E+09 0.541007E+09 0.239898E+09 0.215863E+09 0.00 0.00
Maximum of Months 0.105952E+10 0.513937E+09 0.669853E+09 0.437223E+09 0.379305E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.386456E+09 0.526402E+09 0.316902E+09 0.132231E+09 0.184671E+09 0.00 0.00
February 0.393955E+09 0.423894E+09 0.344863E+09 0.130735E+09 0.214128E+09 0.00 0.00
March 0.514660E+09 0.487298E+09 0.442301E+09 0.158279E+09 0.284022E+09 0.00 0.00
April 0.751215E+09 0.368938E+09 0.571997E+09 0.249104E+09 0.322893E+09 0.00 0.00
May 0.767094E+09 0.338471E+09 0.602123E+09 0.229746E+09 0.372377E+09 0.00 0.00
June 0.838661E+09 0.252058E+09 0.617240E+09 0.260037E+09 0.357203E+09 0.00 0.00
July 0.962750E+09 0.231538E+09 0.661491E+09 0.300669E+09 0.360821E+09 0.00 0.00
August 0.897030E+09 0.241421E+09 0.608125E+09 0.278467E+09 0.329659E+09 0.00 0.00
September 0.720525E+09 0.263841E+09 0.503135E+09 0.226378E+09 0.276757E+09 0.00 0.00
October 0.608619E+09 0.306272E+09 0.401425E+09 0.184044E+09 0.217382E+09 0.00 0.00
November 0.437816E+09 0.448127E+09 0.349935E+09 0.153116E+09 0.196819E+09 0.00 0.00
December 0.394433E+09 0.523206E+09 0.316796E+09 0.142163E+09 0.174633E+09 0.00 0.00
               
Annual Sum or Average 0.767321E+10 0.441147E+10 0.573633E+10 0.244497E+10 0.329137E+10 0.00 0.00
Minimum of Months 0.386456E+09 0.231538E+09 0.316796E+09 0.130735E+09 0.174633E+09 0.00 0.00
Maximum of Months 0.962750E+09 0.526402E+09 0.661491E+09 0.300669E+09 0.372377E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.781202E+09 0.268639E+09 0.530656E+09 0.389579E+09 0.141077E+09 0.00 0.00
February 0.526961E+09 0.219027E+09 0.378609E+09 0.234271E+09 0.144338E+09 0.00 0.00
March 0.460824E+09 0.254431E+09 0.334314E+09 0.162851E+09 0.171463E+09 0.00 0.00
April 0.401122E+09 0.189780E+09 0.270540E+09 0.104564E+09 0.165976E+09 0.00 0.00
May 0.248408E+09 0.173967E+09 0.196974E+09 23853749.05 0.173120E+09 0.00 0.00
June 0.219367E+09 0.118490E+09 0.167228E+09 9807959.43 0.157420E+09 0.00 0.00
July 0.276736E+09 99513685.10 0.182238E+09 19487344.79 0.162751E+09 0.00 0.00
August 0.393223E+09 0.104857E+09 0.234059E+09 72730822.43 0.161328E+09 0.00 0.00
September 0.508849E+09 0.126782E+09 0.311041E+09 0.154522E+09 0.156519E+09 0.00 0.00
October 0.686444E+09 0.147065E+09 0.420863E+09 0.282641E+09 0.138222E+09 0.00 0.00
November 0.730187E+09 0.228663E+09 0.494729E+09 0.350527E+09 0.144202E+09 0.00 0.00
December 0.840700E+09 0.266506E+09 0.567871E+09 0.432733E+09 0.135138E+09 0.00 0.00
               
Annual Sum or Average 0.607402E+10 0.219772E+10 0.408912E+10 0.223757E+10 0.185155E+10 0.00 0.00
Minimum of Months 0.219367E+09 99513685.10 0.167228E+09 9807959.43 0.135138E+09 0.00 0.00
Maximum of Months 0.840700E+09 0.268639E+09 0.567871E+09 0.432733E+09 0.173120E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.261219E+09 0.149622E+10 0.382836E+09 0.00 0.382836E+09 0.00 0.00
February 0.271888E+09 0.123703E+10 0.434055E+09 0.00 0.434055E+09 0.00 0.00
March 0.443605E+09 0.139770E+10 0.588944E+09 5392.86 0.588939E+09 0.00 0.00
April 0.631773E+09 0.100870E+10 0.660090E+09 5311595.66 0.654778E+09 0.00 0.00
May 0.824546E+09 0.910123E+09 0.820557E+09 42790998.43 0.777766E+09 0.00 0.00
June 0.102750E+10 0.655906E+09 0.841745E+09 83156260.58 0.758589E+09 0.00 0.00
July 0.113586E+10 0.579394E+09 0.823912E+09 69912577.80 0.753999E+09 0.00 0.00
August 0.925395E+09 0.617153E+09 0.685036E+09 15219869.11 0.669816E+09 0.00 0.00
September 0.688125E+09 0.728463E+09 0.559598E+09 111292.82 0.559487E+09 0.00 0.00
October 0.625358E+09 0.865045E+09 0.458638E+09 0.00 0.458638E+09 0.00 0.00
November 0.299751E+09 0.128541E+10 0.401868E+09 0.00 0.401868E+09 0.00 0.00
December 0.237774E+09 0.149648E+10 0.356388E+09 0.00 0.356388E+09 0.00 0.00
               
Annual Sum or Average 0.737280E+10 0.122776E+11 0.701367E+10 0.216508E+09 0.679716E+10 0.00 0.00
Minimum of Months 0.237774E+09 0.579394E+09 0.356388E+09 0.00 0.356388E+09 0.00 0.00
Maximum of Months 0.113586E+10 0.149648E+10 0.841745E+09 83156260.58 0.777766E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.239851E+09 0.156078E+10 0.382836E+09 0.00 0.382836E+09 0.00 0.00
February 0.250052E+09 0.129557E+10 0.434055E+09 0.00 0.434055E+09 0.00 0.00
March 0.414254E+09 0.146059E+10 0.588944E+09 5392.86 0.588939E+09 0.00 0.00
April 0.598860E+09 0.105370E+10 0.660090E+09 5311595.66 0.654778E+09 0.00 0.00
May 0.783177E+09 0.949077E+09 0.820557E+09 42790998.43 0.777766E+09 0.00 0.00
June 0.988171E+09 0.686615E+09 0.841745E+09 83156260.58 0.758589E+09 0.00 0.00
July 0.109746E+10 0.608064E+09 0.823912E+09 69912577.80 0.753999E+09 0.00 0.00
August 0.891330E+09 0.648778E+09 0.685036E+09 15219869.11 0.669816E+09 0.00 0.00
September 0.660452E+09 0.765822E+09 0.559598E+09 111292.82 0.559487E+09 0.00 0.00
October 0.599775E+09 0.907425E+09 0.458638E+09 0.00 0.458638E+09 0.00 0.00
November 0.278367E+09 0.134094E+10 0.401868E+09 0.00 0.401868E+09 0.00 0.00
December 0.217664E+09 0.155860E+10 0.356388E+09 0.00 0.356388E+09 0.00 0.00
               
Annual Sum or Average 0.701942E+10 0.128360E+11 0.701367E+10 0.216508E+09 0.679716E+10 0.00 0.00
Minimum of Months 0.217664E+09 0.608064E+09 0.356388E+09 0.00 0.356388E+09 0.00 0.00
Maximum of Months 0.109746E+10 0.156078E+10 0.841745E+09 83156260.58 0.777766E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.136171E+10 0.111845E+10 0.966814E+09 0.559663E+09 0.407151E+09 0.00 0.00
February 0.108962E+10 0.966364E+09 0.844655E+09 0.399741E+09 0.444914E+09 0.00 0.00
March 0.134796E+10 0.109938E+10 0.102078E+10 0.427575E+09 0.593209E+09 0.00 0.00
April 0.173858E+10 0.827860E+09 0.115299E+10 0.510703E+09 0.642290E+09 0.00 0.00
May 0.160180E+10 0.788973E+09 0.110242E+10 0.376967E+09 0.725448E+09 0.00 0.00
June 0.167300E+10 0.579003E+09 0.105354E+10 0.374230E+09 0.679311E+09 0.00 0.00
July 0.207043E+10 0.511934E+09 0.120064E+10 0.499546E+09 0.701091E+09 0.00 0.00
August 0.211410E+10 0.530918E+09 0.120497E+10 0.555337E+09 0.649635E+09 0.00 0.00
September 0.162893E+10 0.583343E+09 0.961494E+09 0.413303E+09 0.548191E+09 0.00 0.00
October 0.166694E+10 0.668124E+09 0.962164E+09 0.505642E+09 0.456522E+09 0.00 0.00
November 0.132277E+10 0.966998E+09 0.931343E+09 0.510666E+09 0.420676E+09 0.00 0.00
December 0.137339E+10 0.111383E+10 0.971164E+09 0.592152E+09 0.379012E+09 0.00 0.00
               
Annual Sum or Average 0.189892E+11 0.975519E+10 0.123730E+11 0.572553E+10 0.664745E+10 0.00 0.00
Minimum of Months 0.108962E+10 0.511934E+09 0.844655E+09 0.374230E+09 0.379012E+09 0.00 0.00
Maximum of Months 0.211410E+10 0.111845E+10 0.120497E+10 0.592152E+09 0.725448E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.202924E+10 0.123836E+10 0.148205E+10 0.991693E+09 0.490356E+09 0.00 0.00
February 0.139470E+10 0.104379E+10 0.111256E+10 0.596348E+09 0.516216E+09 0.00 0.00
March 0.129095E+10 0.120319E+10 0.105291E+10 0.414547E+09 0.638358E+09 0.00 0.00
April 0.118113E+10 0.942324E+09 0.914954E+09 0.267995E+09 0.646960E+09 0.00 0.00
May 0.827166E+09 0.866962E+09 0.782695E+09 75389823.82 0.707305E+09 0.00 0.00
June 0.792268E+09 0.640974E+09 0.714239E+09 53472810.61 0.660766E+09 0.00 0.00
July 0.963738E+09 0.580296E+09 0.746336E+09 73572240.13 0.672764E+09 0.00 0.00
August 0.121020E+10 0.622875E+09 0.830641E+09 0.190358E+09 0.640284E+09 0.00 0.00
September 0.145523E+10 0.714590E+09 0.983602E+09 0.393382E+09 0.590220E+09 0.00 0.00
October 0.188270E+10 0.804339E+09 0.122855E+10 0.719477E+09 0.509074E+09 0.00 0.00
November 0.190523E+10 0.109727E+10 0.139712E+10 0.892285E+09 0.504834E+09 0.00 0.00
December 0.216134E+10 0.124015E+10 0.156772E+10 0.110154E+10 0.466173E+09 0.00 0.00
               
Annual Sum or Average 0.170939E+11 0.109951E+11 0.128134E+11 0.577007E+10 0.704331E+10 0.00 0.00
Minimum of Months 0.792268E+09 0.580296E+09 0.714239E+09 53472810.61 0.466173E+09 0.00 0.00
Maximum of Months 0.216134E+10 0.124015E+10 0.156772E+10 0.110154E+10 0.707305E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.22 9.61 5.99 2.23 0.81 45.19 208.20 0.00
February 13.28 10.20 7.03 3.12 2.96 66.07 175.60 0.04
March 12.64 10.61 8.97 2.93 3.55 84.90 179.28 0.03
April 15.30 12.62 10.61 2.62 4.76 81.20 282.81 0.02
May 15.56 12.65 10.56 2.92 6.17 105.80 234.18 0.01
June 17.67 14.80 13.02 2.53 9.03 98.05 261.27 0.00
July 19.43 16.76 15.28 2.35 9.62 86.54 312.15 0.00
August 19.66 17.23 15.95 2.55 9.62 74.58 307.55 0.00
September 18.47 15.50 13.65 2.19 8.99 70.75 240.05 0.00
October 18.77 13.72 9.60 2.71 7.74 53.88 216.36 0.00
November 14.32 10.43 6.22 2.47 2.41 50.75 207.87 0.01
December 13.59 8.82 3.19 2.50 0.05 39.49 221.83 0.00
                 
Annual Sum or Average 16.01 12.76 10.02 2.59 5.49 71.44 237.65 0.01
Minimum of Months 12.64 8.82 3.19 2.19 0.05 39.49 175.60 0.00
Maximum of Months 19.66 17.23 15.95 3.12 9.62 105.80 312.15 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 26.00 13-JAN-13:00 15.46 8.00 3.10 11.84 120.00 725.00
February 26.00 01-FEB-11:00 14.67 6.00 4.10 10.11 166.00 715.50
March 24.00 11-MAR-10:00 13.82 6.00 2.60 8.15 120.00 907.00
April 27.00 26-APR-12:00 17.13 11.00 4.10 12.22 159.00 884.00
May 24.00 03-MAY-11:00 15.05 9.00 4.10 12.98 187.00 842.50
June 25.00 29-JUN-10:00 19.59 17.00 4.60 11.65 177.50 829.00
July 28.00 19-JUL-10:00 20.49 17.00 3.60 14.65 173.00 813.00
August 28.00 14-AUG-10:00 21.19 18.00 3.60 14.84 148.00 840.00
September 36.00 29-SEP-10:00 17.91 5.00 3.60 19.35 159.50 790.00
October 37.00 16-OCT-10:00 17.87 4.00 5.70 20.05 122.00 871.50
November 27.00 19-NOV-12:00 14.96 6.00 4.10 11.07 128.50 796.00
December 26.00 05-DEC-09:00 13.09 1.00 3.60 8.94 75.50 857.00
                 
Annual Sum or Average                
Minimum of Months 24.00   13.09 1.00 2.60 8.15 75.50 715.50
Maximum of Months 37.00   21.19 18.00 5.70 20.05 187.00 907.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.00 08-JAN-06:00 -0.3 -2.0 3.10 -15.5 11.50 193.50
February 5.00 04-FEB-05:00 0.22 -8.0 4.10 -10.9 0.00 0.00
March 4.00 07-MAR-04:00 3.53 3.00 0.00 -11.4 0.00 0.00
April 7.00 01-APR-05:00 4.33 1.00 4.10 -9.0 23.50 211.00
May 8.00 14-MAY-03:00 7.45 7.00 1.50 -6.6 0.00 0.00
June 11.00 13-JUN-03:00 9.85 9.00 2.10 -3.4 0.00 0.00
July 13.00 06-JUL-00:00 13.00 13.00 0.00 -0.6 0.00 0.00
August 14.00 24-AUG-01:00 14.00 14.00 0.00 0.51 0.00 0.00
September 11.00 20-SEP-02:00 9.85 9.00 1.50 -3.4 0.00 0.00
October 9.00 12-OCT-04:00 6.56 4.00 3.10 -6.4 0.00 0.00
November 7.00 05-NOV-01:00 5.54 4.00 3.10 -8.3 0.00 0.00
December 5.00 03-DEC-00:00 5.00 5.00 2.10 -0.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 1.00   -0.3 -8.0 0.00 -15.5 0.00 0.00
Maximum of Months 14.00   14.00 14.00 4.10 0.51 23.50 211.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 17.04 17-JAN-11:00 24.00 13.00 3.10 12.79 223.50 9.00
February 16.80 11-FEB-13:00 18.00 16.20 1.10 15.02 241.00 12.50
March 17.41 22-MAR-12:00 22.00 15.00 3.10 8.35 145.50 876.00
April 18.33 26-APR-10:00 26.00 14.00 4.10 12.03 141.50 915.50
May 16.69 05-MAY-14:00 18.00 16.00 5.10 8.74 303.50 269.00
June 19.59 29-JUN-10:00 25.00 17.00 4.60 11.65 177.50 829.00
July 21.19 19-JUL-11:00 28.00 18.00 4.60 14.84 182.50 808.00
August 21.20 18-AUG-11:00 28.00 18.00 3.60 17.21 244.00 667.50
September 21.85 22-SEP-11:00 26.00 20.00 2.60 20.05 284.00 21.00
October 21.09 01-OCT-11:00 26.00 19.00 3.60 13.16 102.00 899.50
November 16.52 10-NOV-12:00 21.00 14.00 5.10 7.15 131.00 808.50
December 15.64 07-DEC-12:00 20.00 13.00 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 15.64   18.00 13.00 1.10 5.94 89.00 9.00
Maximum of Months 21.85   28.00 20.00 5.10 20.05 303.50 915.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 17-JAN-12:00 22.00 16.85 2.10 11.65 241.50 67.50
February 16.20 11-FEB-13:00 18.00 16.80 1.10 15.02 241.00 12.50
March 15.00 23-MAR-15:20 21.67 17.34 3.77 8.02 112.00 809.83
April 15.00 26-APR-21:19 16.00 15.39 2.23 6.15 0.00 0.00
May 16.00 05-MAY-14:00 18.00 16.69 5.10 8.74 303.50 269.00
June 17.00 28-JUN-08:00 19.00 17.66 1.50 16.12 285.00 428.50
July 18.00 18-JUL-10:00 26.00 20.47 4.60 12.79 169.00 819.00
August 18.10 14-AUG-09:00 26.90 20.93 3.40 13.73 139.00 817.00
September 20.00 22-SEP-09:00 22.00 20.55 1.50 16.30 296.00 18.00
October 19.00 01-OCT-07:10 19.17 19.06 0.25 16.82 53.33 0.00
November 15.00 10-NOV-17:19 16.67 15.62 2.77 3.34 0.00 0.00
December 13.00 07-DEC-12:00 20.00 15.64 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 13.00   16.00 15.39 0.25 3.34 0.00 0.00
Maximum of Months 20.00   26.90 20.93 5.10 16.82 303.50 868.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 17.43 27.46 0.00
February 18.00 13.00 16.00 17.38 30.87 0.00
March 18.00 13.00 16.00 17.83 38.09 0.00
April 18.00 13.00 16.00 18.69 55.75 0.00
May 18.00 13.00 16.00 19.73 55.13 0.00
June 18.00 13.00 16.00 20.65 58.21 0.00
July 18.00 13.00 16.00 21.22 63.49 0.00
August 18.00 13.00 16.00 21.28 59.02 0.00
September 18.00 13.00 16.00 20.81 46.26 0.00
October 18.00 13.00 16.00 19.94 34.64 0.00
November 18.00 13.00 16.00 18.91 29.25 0.00
December 18.00 13.00 16.00 17.99 26.27 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.33 43.77 0.00
Minimum of Months 18.00 13.00 16.00 17.38 26.27 0.00
Maximum of Months 18.00 13.00 16.00 21.28 63.49 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.111412E+12 -0.109633E+12 0.00 0.00 744.00 0.00 -0.177918E+10 82.17 0.00 0.00
February 0.100718E+12 -0.990946E+11 0.00 0.00 672.00 0.00 -0.162323E+10 82.17 0.00 0.00
March 0.110748E+12 -0.108944E+12 0.00 0.00 744.00 0.00 -0.180368E+10 82.17 0.00 0.00
April 0.105770E+12 -0.104022E+12 0.00 0.00 720.00 0.00 -0.174853E+10 82.17 0.00 0.00
May 0.107548E+12 -0.105741E+12 0.00 0.00 744.00 0.00 -0.180692E+10 82.17 0.00 0.00
June 0.102562E+12 -0.100811E+12 0.00 0.00 720.00 0.00 -0.175160E+10 82.17 0.00 0.00
July 0.105005E+12 -0.103206E+12 0.00 0.00 744.00 0.00 -0.179963E+10 82.17 0.00 0.00
August 0.104902E+12 -0.103106E+12 0.00 0.00 744.00 0.00 -0.179626E+10 82.17 0.00 0.00
September 0.102279E+12 -0.100550E+12 0.00 0.00 720.00 0.00 -0.172863E+10 82.17 0.00 0.00
October 0.107152E+12 -0.105375E+12 0.00 0.00 744.00 0.00 -0.177713E+10 82.17 0.00 0.00
November 0.105386E+12 -0.103669E+12 0.00 0.00 720.00 0.00 -0.171677E+10 82.17 0.00 0.00
December 0.110458E+12 -0.108679E+12 0.00 0.00 744.00 0.00 -0.177816E+10 82.17 0.00 0.00
                     
Annual Sum or Average 0.127394E+13 -0.125283E+13 0.00 0.00 8760.00 0.00 -0.211097E+11 82.17 0.00 0.00
Minimum of Months 0.100718E+12 -0.109633E+12 0.00 0.00 672.00 0.00 -0.180692E+10 82.17 0.00 0.00
Maximum of Months 0.111412E+12 -0.990946E+11 0.00 0.00 744.00 0.00 -0.162323E+10 82.17 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.804707E+10 -0.788296E+10 0.00 0.00 744.00 0.00 -164109048.2 82.17 0.00 0.00
February 0.727159E+10 -0.712336E+10 0.00 0.00 672.00 0.00 -148227530.0 82.17 0.00 0.00
March 0.804566E+10 -0.788156E+10 0.00 0.00 744.00 0.00 -164108988.6 82.17 0.00 0.00
April 0.779702E+10 -0.763820E+10 0.00 0.00 720.00 0.00 -158814748.1 82.17 0.00 0.00
May 0.804707E+10 -0.788296E+10 0.00 0.00 744.00 0.00 -164108595.2 82.17 0.00 0.00
June 0.778858E+10 -0.762976E+10 0.00 0.00 720.00 0.00 -158813767.6 82.17 0.00 0.00
July 0.805551E+10 -0.789140E+10 0.00 0.00 744.00 0.00 -164107025.7 82.17 0.00 0.00
August 0.804707E+10 -0.788296E+10 0.00 0.00 744.00 0.00 -164107070.8 82.17 0.00 0.00
September 0.779842E+10 -0.763961E+10 0.00 0.00 720.00 0.00 -158814066.9 82.17 0.00 0.00
October 0.804566E+10 -0.788156E+10 0.00 0.00 744.00 0.00 -164108636.1 82.17 0.00 0.00
November 0.778014E+10 -0.762132E+10 0.00 0.00 720.00 0.00 -158815085.6 82.17 0.00 0.00
December 0.805551E+10 -0.789140E+10 0.00 0.00 744.00 0.00 -164109382.6 82.17 0.00 0.00
                     
Annual Sum or Average 0.947793E+11 -0.928471E+11 0.00 0.00 8760.00 0.00 -0.193224E+10 82.17 0.00 0.00
Minimum of Months 0.727159E+10 -0.789140E+10 0.00 0.00 672.00 0.00 -164109382.6 82.17 0.00 0.00
Maximum of Months 0.805551E+10 -0.712336E+10 0.00 0.00 744.00 0.00 -148227530.0 82.17 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.637467E+11 -0.622046E+11 0.00 0.00 744.00 0.00 -0.154207E+10 60.05 0.00 0.00
February 0.576728E+11 -0.562575E+11 0.00 0.00 672.00 0.00 -0.141534E+10 60.05 0.00 0.00
March 0.632409E+11 -0.616648E+11 0.00 0.00 744.00 0.00 -0.157604E+10 60.05 0.00 0.00
April 0.599558E+11 -0.584264E+11 0.00 0.00 720.00 0.00 -0.152940E+10 60.05 0.00 0.00
May 0.604536E+11 -0.588730E+11 0.00 0.00 744.00 0.00 -0.158054E+10 60.05 0.00 0.00
June 0.572177E+11 -0.556840E+11 0.00 0.00 720.00 0.00 -0.153365E+10 60.05 0.00 0.00
July 0.582224E+11 -0.566520E+11 0.00 0.00 744.00 0.00 -0.157043E+10 60.05 0.00 0.00
August 0.581897E+11 -0.566239E+11 0.00 0.00 744.00 0.00 -0.156575E+10 60.05 0.00 0.00
September 0.569345E+11 -0.554326E+11 0.00 0.00 720.00 0.00 -0.150182E+10 60.05 0.00 0.00
October 0.600636E+11 -0.585243E+11 0.00 0.00 744.00 0.00 -0.153923E+10 60.05 0.00 0.00
November 0.595840E+11 -0.580986E+11 0.00 0.00 720.00 0.00 -0.148537E+10 60.05 0.00 0.00
December 0.629180E+11 -0.613773E+11 0.00 0.00 744.00 0.00 -0.154066E+10 60.05 0.00 0.00
                     
Annual Sum or Average 0.718199E+12 -0.699819E+12 0.00 0.00 8760.00 0.00 -0.183803E+11 60.05 0.00 0.00
Minimum of Months 0.569345E+11 -0.622046E+11 0.00 0.00 672.00 0.00 -0.158054E+10 60.05 0.00 0.00
Maximum of Months 0.637467E+11 -0.554326E+11 0.00 0.00 744.00 0.00 -0.141534E+10 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.87 0.86 01-JAN-07:19 6996.10 37.50 285.00 281.50 1006.88 27.14 206.83 264.67
February 279.67 0.87 0.86 01-FEB-07:19 4865.04 32.23 218.50 276.33 664.68 23.84 185.17 247.17
March 338.17 0.87 0.86 01-MAR-07:19 1275.07 20.00 18.33 322.33 475.35 21.26 183.50 267.67
April 358.33 0.87 0.86 01-APR-06:00 877.10 19.51 0.00 335.00 370.15 21.26 205.17 273.67
May 393.83 0.87 0.86 01-MAY-06:49 796.73 19.01 0.00 367.50 324.62 20.74 157.83 278.17
June 381.00 0.87 0.86 01-JUN-06:49 689.14 18.82 0.00 359.83 290.21 20.57 122.33 259.00
July 408.67 0.87 0.86 01-JUL-06:49 678.96 18.93 0.00 369.83 296.31 20.70 170.83 277.33
August 390.67 0.87 0.86 01-AUG-07:30 738.39 19.19 0.00 355.83 321.72 20.94 180.83 281.83
September 328.83 0.87 0.86 01-SEP-06:00 991.71 19.50 0.17 310.67 412.99 21.27 179.00 260.83
October 296.17 0.87 0.86 01-OCT-09:39 3356.14 27.29 136.83 307.00 488.91 21.78 124.83 256.00
November 300.00 0.87 0.86 01-NOV-06:49 6810.79 37.33 295.17 281.67 882.74 26.71 223.67 269.33
December 297.00 0.87 0.86 01-DEC-07:19 6846.78 37.91 289.17 281.83 1234.50 28.68 198.83 267.83
                         
Annual Sum or Average 4065.67 0.87     2631.14 24.74 1243.17 3849.33 534.20 22.64 2138.83 3203.50
Minimum of Months 279.67 0.87 0.86   678.96 18.82 0.00 276.33 290.21 20.57 122.33 247.17
Maximum of Months 408.67 0.87 0.86   6996.10 37.91 295.17 369.83 1234.50 28.68 223.67 281.83



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.24 0.22 01-JAN-07:19 7401.02 37.57 285.00 288.17 1413.78 26.84 183.50 275.67
February 279.67 0.24 0.22 01-FEB-07:10 5186.62 32.32 218.83 283.00 985.83 23.88 181.83 265.83
March 338.17 0.26 0.22 01-MAR-06:00 1523.16 20.45 42.67 331.67 722.52 21.55 204.50 303.50
April 358.33 0.25 0.22 01-APR-06:30 1077.33 20.07 38.33 347.83 569.90 21.63 226.50 317.33
May 393.83 0.26 0.22 01-MAY-06:19 938.34 19.82 5.83 381.33 465.76 21.33 248.33 345.83
June 381.00 0.26 0.22 01-JUN-06:19 816.63 19.67 0.17 372.17 417.28 21.20 244.67 335.67
July 408.67 0.27 0.22 01-JUL-05:00 813.68 19.73 0.50 380.17 430.63 21.28 302.83 349.50
August 390.67 0.26 0.22 01-AUG-06:49 905.72 19.85 12.67 368.17 488.64 21.39 250.17 339.17
September 328.83 0.26 0.22 01-SEP-06:40 1230.98 19.94 37.33 324.00 651.71 21.53 191.17 295.33
October 296.17 0.25 0.22 01-OCT-09:39 3684.47 27.32 138.17 318.00 815.07 21.72 122.17 285.83
November 300.00 0.25 0.22 01-NOV-06:40 7191.92 37.39 295.17 286.17 1261.05 26.47 202.83 277.33
December 297.00 0.25 0.22 01-DEC-07:10 7268.27 37.99 289.33 287.50 1655.29 28.33 177.67 277.33
                         
Annual Sum or Average 4065.67 0.26     2878.23 25.20 1364.00 3968.17 780.66 22.87 2536.17 3668.33
Minimum of Months 279.67 0.24 0.22   813.68 19.67 0.17 283.00 417.28 21.20 122.17 265.83
Maximum of Months 408.67 0.27 0.22   7401.02 37.99 295.17 381.33 1655.29 28.33 302.83 349.50



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.65 0.60 01-JAN-08:50 328.84 14.69 0.00 245.83 170.23 18.24 0.00 61.67
February 279.67 0.64 0.60 01-FEB-08:39 411.28 15.54 0.00 258.83 197.32 18.87 0.00 126.50
March 338.17 0.63 0.60 01-MAR-08:30 492.54 16.10 0.00 317.00 226.28 19.30 0.00 227.33
April 358.33 0.62 0.60 01-APR-06:00 518.97 17.03 0.00 346.00 254.04 20.29 30.17 297.00
May 393.83 0.61 0.60 01-MAY-06:30 697.87 17.97 12.50 389.33 314.13 21.17 91.83 354.83
June 381.00 0.61 0.60 01-JUN-06:19 739.07 19.98 58.83 383.50 341.91 22.38 132.67 348.00
July 408.67 0.62 0.60 01-JUL-05:40 671.97 19.24 44.83 391.33 296.18 20.85 113.33 361.83
August 390.67 0.62 0.60 01-AUG-06:00 532.40 17.11 0.00 372.67 255.91 20.39 57.67 329.33
September 328.83 0.63 0.60 01-SEP-06:49 457.21 16.39 0.00 314.50 226.97 19.66 1.67 233.00
October 296.17 0.66 0.60 01-OCT-09:39 340.73 15.04 0.00 272.00 173.00 18.47 0.00 94.17
November 300.00 0.66 0.60 01-NOV-07:49 337.29 14.48 0.00 252.00 171.93 17.93 0.00 78.33
December 297.00 0.67 0.60 01-DEC-08:20 296.59 14.16 0.00 238.67 157.92 17.78 0.00 43.00
                         
Annual Sum or Average 4065.67 0.63     502.64 16.68 116.17 3781.67 239.08 19.77 427.33 2555.00
Minimum of Months 279.67 0.61 0.60   296.59 14.16 0.00 238.67 157.92 17.78 0.00 43.00
Maximum of Months 408.67 0.67 0.60   739.07 19.98 58.83 391.33 341.91 22.38 132.67 361.83



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.65 0.60 01-JAN-08:50 328.84 14.69 0.00 245.83 170.23 18.24 0.00 61.67
February 279.67 0.64 0.60 01-FEB-08:39 411.28 15.54 0.00 258.83 197.32 18.87 0.00 126.50
March 338.17 0.63 0.60 01-MAR-08:30 492.54 16.10 0.00 317.00 226.28 19.30 0.00 227.33
April 358.33 0.62 0.60 01-APR-06:00 518.97 17.03 0.00 346.00 254.04 20.29 30.17 297.00
May 393.83 0.61 0.60 01-MAY-06:30 697.87 17.97 12.50 389.33 314.13 21.17 91.83 354.83
June 381.00 0.61 0.60 01-JUN-06:19 739.07 19.98 58.83 383.50 341.91 22.38 132.67 348.00
July 408.67 0.62 0.60 01-JUL-05:40 671.97 19.24 44.83 391.33 296.18 20.85 113.33 361.83
August 390.67 0.62 0.60 01-AUG-06:00 532.40 17.11 0.00 372.67 255.91 20.39 57.67 329.33
September 328.83 0.63 0.60 01-SEP-06:49 457.21 16.39 0.00 314.50 226.97 19.66 1.67 233.00
October 296.17 0.66 0.60 01-OCT-09:39 340.73 15.04 0.00 272.00 173.00 18.47 0.00 94.17
November 300.00 0.66 0.60 01-NOV-07:49 337.29 14.48 0.00 252.00 171.93 17.93 0.00 78.33
December 297.00 0.67 0.60 01-DEC-08:20 296.59 14.16 0.00 238.67 157.92 17.78 0.00 43.00
                         
Annual Sum or Average 4065.67 0.63     502.64 16.68 116.17 3781.67 239.08 19.77 427.33 2555.00
Minimum of Months 279.67 0.61 0.60   296.59 14.16 0.00 238.67 157.92 17.78 0.00 43.00
Maximum of Months 408.67 0.67 0.60   739.07 19.98 58.83 391.33 341.91 22.38 132.67 361.83



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.781976E+10 8943.46 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.630431E+10 8391.78 05-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.841655E+10 8532.16 07-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.400991E+10 8113.59 01-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.358791E+10 7975.38 19-MAY-05:00 0.00 0.00 0.00 0.00 0.00
June 0.637782E+09 5275.70 13-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 37024146.19 2368.96 06-JUL-01:00 0.00 0.00 0.00 0.00 0.00
August 16924735.47 904.57 28-AUG-05:50 0.00 0.00 0.00 0.00 0.00
September 0.317077E+09 5276.32 20-SEP-03:00 0.00 0.00 0.00 0.00 0.00
October 0.142155E+10 7833.53 28-OCT-05:00 0.00 0.00 0.00 0.00 0.00
November 0.557451E+10 8114.43 05-NOV-02:00 0.00 0.00 0.00 0.00 0.00
December 0.786357E+10 8394.05 03-DEC-01:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.460069E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 16924735.47 904.57   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.841655E+10 8943.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.139563E+11 78760.16 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.388396E+10 47592.04 05-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.102864E+11 58877.66 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 0.477195E+09 25674.73 01-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.781960E+09 20971.25 15-MAY-02:00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.146073E+09 10047.77 30-OCT-03:00 0.00 0.00 0.00 0.00 0.00
November 0.290597E+10 29739.79 24-NOV-04:00 0.00 0.00 0.00 0.00 0.00
December 0.101022E+11 48186.13 24-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.425400E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.139563E+11 78760.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 24605980.44 463.95 01-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 44269866.44 515.38 25-FEB-18:00 0.00 0.00 0.00 0.00 0.00
March 93099920.97 776.89 29-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 8574592.83 531.35 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 6267674.90 314.90 14-MAY-04:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 7948501.65 454.59 13-DEC-04:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.184767E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 93099920.97 776.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 503034.58 92.94 01-JAN-18:00 0.00 0.00 0.00 0.00 0.00
February 422395.25 204.22 28-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 4010570.38 310.88 29-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 4936000.21     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 4010570.38 310.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 69983838.17 357.64 01-JAN-18:00 0.00 0.00 0.00 0.00 0.00
February 52771190.42 336.57 28-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 0.120649E+09 449.96 30-MAR-10:35 0.00 0.00 0.00 0.00 0.00
April 12413132.15 295.88 01-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 768560.71 179.63 15-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 255869.54 49.50 05-NOV-16:55 0.00 0.00 0.00 0.00 0.00
December 22835203.44 237.33 13-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.279677E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.120649E+09 449.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.144964E+09 3534.74 25-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 0.464478E+09 4037.52 28-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.714396E+09 5117.02 29-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.223303E+09 3291.79 22-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.629239E+09 4055.63 09-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.507545E+09 3410.90 08-JUN-10:35 0.00 0.00 0.00 0.00 0.00
July 0.198981E+09 2451.44 06-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 24237705.21 1704.73 02-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 68173528.53 3506.86 18-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 54889031.67 2562.41 06-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 58941415.99 2307.49 03-NOV-10:40 0.00 0.00 0.00 0.00 0.00
December 99475791.65 3081.90 08-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.318862E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 24237705.21 1704.73   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.714396E+09 5117.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 1089064.38 1815.11 28-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 20478537.94 4445.81 29-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 21567602.31     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 20478537.94 4445.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.111328E+09 2464.93 01-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 79530760.25 2794.76 28-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.205782E+09 3713.34 29-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 7962357.71 1579.57 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.404603E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.205782E+09 3713.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 364132.73 251.73 30-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 364132.73     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 364132.73 251.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 55835154.53 3180.00 03-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 38659491.10 2835.04 06-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 55135830.67 3033.61 30-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 24436506.32 2703.56 03-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 10918860.37 1583.29 15-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 1772372.80 626.58 13-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 75232.40 125.39 17-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 1122800.87 402.68 31-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 7474687.09 1191.56 20-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 12322952.12 2366.00 30-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 29903215.64 2839.33 27-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 40428430.81 3032.74 15-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.278086E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 75232.40 125.39   0.00 0.00 0.00 0.00 0.00
Maximum of Months 55835154.53 3180.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 7739720.41 1319.37 03-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 1606062.21 626.09 06-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 2058776.76 911.53 30-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 50872.23 84.79 30-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 341932.09 401.54 27-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 3665034.27 981.64 15-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 15462397.96     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 7739720.41 1319.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.381776E+09 3563.69 24-JAN-19:04 0.00 0.00 0.00 0.00 0.00
February 0.262662E+09 3565.23 25-FEB-16:12 0.00 0.00 0.00 0.00 0.00
March 0.437831E+09 3641.01 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 60004608.17 3562.13 14-APR-18:04 0.00 0.00 0.00 0.00 0.00
May 44572736.27 3560.15 15-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 8281145.50 3396.40 08-JUN-15:15 0.00 0.00 0.00 0.00 0.00
July 5029046.12 3189.48 03-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 5272189.54 3233.91 18-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 7631463.73 3029.80 13-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 15140093.07 3557.99 25-OCT-18:04 0.00 0.00 0.00 0.00 0.00
November 0.102056E+09 3562.73 05-NOV-18:04 0.00 0.00 0.00 0.00 0.00
December 0.271584E+09 3562.33 20-DEC-19:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.160184E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5029046.12 3029.80   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.437831E+09 3641.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.775475E+09 3626.28 03-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.420811E+09 3605.41 25-FEB-16:12 0.00 0.00 0.00 0.00 0.00
March 0.577018E+09 3637.63 30-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 68150084.54 3539.52 14-APR-18:04 0.00 0.00 0.00 0.00 0.00
May 36553677.54 3543.58 28-MAY-08:53 0.00 0.00 0.00 0.00 0.00
June 4238274.41 3543.04 02-JUN-08:53 0.00 0.00 0.00 0.00 0.00
July 1446067.23 2573.84 10-JUL-08:54 0.00 0.00 0.00 0.00 0.00
August 1804091.13 2406.49 06-AUG-08:54 0.00 0.00 0.00 0.00 0.00
September 6926374.10 3542.35 15-SEP-08:53 0.00 0.00 0.00 0.00 0.00
October 16207140.67 3541.94 26-OCT-08:53 0.00 0.00 0.00 0.00 0.00
November 0.247438E+09 3542.73 26-NOV-19:03 0.00 0.00 0.00 0.00 0.00
December 0.607618E+09 3622.34 13-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.276369E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1446067.23 2406.49   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.775475E+09 3637.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.182439E+10 20638.66 30-JAN-16:14 0.00 0.00 0.00 0.00 0.00
February 0.353565E+09 20639.31 10-FEB-16:14 0.00 0.00 0.00 0.00 0.00
March 0.968203E+09 20636.54 08-MAR-09:04 0.00 0.00 0.00 0.00 0.00
April 81565685.01 20632.36 03-APR-08:53 0.00 0.00 0.00 0.00 0.00
May 30028080.15 20630.46 24-MAY-08:54 0.00 0.00 0.00 0.00 0.00
June 12727542.95 20639.29 02-JUN-08:54 0.00 0.00 0.00 0.00 0.00
July 5270797.66 12887.05 08-JUL-08:56 0.00 0.00 0.00 0.00 0.00
August 9405912.69 18637.11 22-AUG-08:54 0.00 0.00 0.00 0.00 0.00
September 28010127.78 20638.52 20-SEP-08:54 0.00 0.00 0.00 0.00 0.00
October 33175639.50 20639.88 09-OCT-08:54 0.00 0.00 0.00 0.00 0.00
November 0.261338E+09 20621.00 21-NOV-16:14 0.00 0.00 0.00 0.00 0.00
December 0.113222E+10 20639.52 15-DEC-16:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.473991E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5270797.66 12887.05   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.182439E+10 20639.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.378402E+09 3500.18 21-JAN-19:04 0.00 0.00 0.00 0.00 0.00
February 0.314575E+09 3534.06 25-FEB-16:12 0.00 0.00 0.00 0.00 0.00
March 0.484954E+09 3561.96 29-MAR-18:03 0.00 0.00 0.00 0.00 0.00
April 72190006.82 3500.68 09-APR-18:04 0.00 0.00 0.00 0.00 0.00
May 65563974.22 3496.84 22-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 9480483.33 3497.64 01-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 907995.75 3129.26 09-JUL-18:05 0.00 0.00 0.00 0.00 0.00
August 356846.92 1600.10 21-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 7253248.16 3440.80 05-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 16245698.36 3492.17 25-OCT-18:04 0.00 0.00 0.00 0.00 0.00
November 0.132307E+09 3500.03 09-NOV-16:14 0.00 0.00 0.00 0.00 0.00
December 0.300642E+09 3500.45 13-DEC-16:14 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.178288E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 356846.92 1600.10   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.484954E+09 3561.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.750000E+09 3528.61 02-JAN-19:02 0.00 0.00 0.00 0.00 0.00
February 0.504211E+09 3538.90 25-FEB-16:12 0.00 0.00 0.00 0.00 0.00
March 0.640773E+09 3554.18 29-MAR-18:03 0.00 0.00 0.00 0.00 0.00
April 85699838.74 3479.67 09-APR-18:04 0.00 0.00 0.00 0.00 0.00
May 54737958.72 3354.90 13-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 3899142.45 3089.82 07-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 815670.19 2063.66 11-JUL-21:54 0.00 0.00 0.00 0.00 0.00
August 735364.38 1296.44 01-AUG-21:55 0.00 0.00 0.00 0.00 0.00
September 6036372.64 2580.13 02-SEP-19:14 0.00 0.00 0.00 0.00 0.00
October 20899525.67 2856.15 07-OCT-08:55 0.00 0.00 0.00 0.00 0.00
November 0.313186E+09 3478.96 25-NOV-16:13 0.00 0.00 0.00 0.00 0.00
December 0.641974E+09 3534.60 12-DEC-16:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.302297E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 735364.38 1296.44   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.750000E+09 3554.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.206577E+09 1086.47 23-JAN-16:14 0.00 0.00 0.00 0.00 0.00
February 0.159819E+09 1117.32 25-FEB-16:12 0.00 0.00 0.00 0.00 0.00
March 0.216081E+09 1124.83 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 40373646.66 964.60 06-APR-18:04 0.00 0.00 0.00 0.00 0.00
May 35547781.89 944.71 27-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 5329605.26 819.08 08-JUN-15:15 0.00 0.00 0.00 0.00 0.00
July 1167574.31 799.38 03-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 1237635.13 770.69 18-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 2455581.95 917.04 21-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 18771501.47 1024.27 26-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 91767164.05 1061.62 09-NOV-16:14 0.00 0.00 0.00 0.00 0.00
December 0.175353E+09 999.30 14-DEC-19:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.954480E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1167574.31 770.69   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.216081E+09 1124.83   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.376277E+09 1120.93 03-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.235101E+09 1114.19 25-FEB-16:12 0.00 0.00 0.00 0.00 0.00
March 0.272680E+09 1122.04 30-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 43382543.43 974.75 14-APR-18:04 0.00 0.00 0.00 0.00 0.00
May 26033274.30 998.86 24-MAY-08:53 0.00 0.00 0.00 0.00 0.00
June 2316115.50 712.92 08-JUN-19:05 0.00 0.00 0.00 0.00 0.00
July 224841.75 513.74 21-JUL-08:54 0.00 0.00 0.00 0.00 0.00
August 416545.35 533.55 01-AUG-08:54 0.00 0.00 0.00 0.00 0.00
September 2204506.67 855.79 02-SEP-08:54 0.00 0.00 0.00 0.00 0.00
October 22902787.07 1022.44 16-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 0.175183E+09 1077.90 23-NOV-19:03 0.00 0.00 0.00 0.00 0.00
December 0.329698E+09 1119.14 13-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.148642E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 224841.75 513.74   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.376277E+09 1122.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.192904E+09 4373.20 16-JAN-16:15 0.00 0.00 0.00 0.00 0.00
February 0.186315E+09 4747.52 11-FEB-16:15 0.00 0.00 0.00 0.00 0.00
March 0.470675E+09 4847.50 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 81498146.98 4800.88 20-APR-18:04 0.00 0.00 0.00 0.00 0.00
May 0.124002E+09 5225.61 12-MAY-15:14 0.00 0.00 0.00 0.00 0.00
June 23497624.72 4680.01 22-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 9107420.54 4061.30 12-JUL-18:05 0.00 0.00 0.00 0.00 0.00
August 6713635.06 3816.15 31-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 10811410.45 4025.02 01-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 14908781.58 4680.85 24-OCT-15:15 0.00 0.00 0.00 0.00 0.00
November 32613232.68 4564.90 11-NOV-16:15 0.00 0.00 0.00 0.00 0.00
December 0.117555E+09 4047.34 01-DEC-19:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.127060E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 6713635.06 3816.15   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.470675E+09 5225.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.325784E+10 0.323482E+10 20570.98 13-JAN-14:00 20570.98 0.15
February 0.00 0.00 0.176477E+10 0.171146E+10 17583.23 01-FEB-09:54 17583.23 0.13
March 0.00 0.00 0.195362E+10 0.180527E+10 22012.17 22-MAR-13:00 14832.69 0.11
April 0.00 0.00 0.490019E+10 0.461280E+10 22090.96 26-APR-13:00 22090.96 0.25
May 0.00 0.00 0.521145E+10 0.512070E+10 18829.64 04-MAY-13:00 16265.15 0.33
June 0.00 0.00 0.118888E+11 0.944939E+10 30817.80 29-JUN-12:15 17826.82 0.61
July 0.00 0.00 0.270220E+11 0.158139E+11 40153.36 31-JUL-12:30 23766.73 0.75
August 0.00 0.00 0.309007E+11 0.166894E+11 38591.89 18-AUG-12:20 22286.10 0.76
September 0.00 0.00 0.175428E+11 0.122681E+11 39619.58 22-SEP-12:15 19372.88 0.66
October 0.00 0.00 0.195118E+11 0.143145E+11 38111.08 01-OCT-12:15 20334.16 0.44
November 0.00 0.00 0.327790E+10 0.321606E+10 21037.50 19-NOV-13:15 21037.50 0.18
December 0.00 0.00 0.398719E+10 0.398507E+10 20480.92 05-DEC-09:55 20480.92 0.05
                 
Annual Sum or Average 0.00 0.00 0.131219E+12 0.922214E+11       0.37
Minimum of Months 0.00 0.00 0.176477E+10 0.171146E+10 17583.23   14832.69 0.05
Maximum of Months 0.00 0.00 0.309007E+11 0.166894E+11 40153.36   23766.73 0.76



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.635666E+11 0.632618E+11 199203.88 14-JAN-11:35 199203.88 0.27
February 0.00 0.00 0.367906E+11 0.358442E+11 190281.20 01-FEB-11:50 190281.20 0.26
March 0.00 0.00 0.406281E+11 0.397415E+11 192046.58 23-MAR-10:50 154826.26 0.26
April 0.00 0.00 0.939448E+11 0.918197E+11 239516.10 26-APR-10:35 191914.84 0.48
May 0.00 0.00 0.101202E+12 0.998370E+11 168657.85 18-MAY-10:50 150679.41 0.58
June 0.00 0.00 0.181922E+12 0.158926E+12 305437.22 29-JUN-18:03 165642.09 0.85
July 0.00 0.00 0.352875E+12 0.236304E+12 358736.16 31-JUL-18:20 179752.68 0.99
August 0.00 0.00 0.395622E+12 0.245998E+12 350035.22 14-AUG-10:35 219072.76 0.99
September 0.00 0.00 0.241649E+12 0.185232E+12 345734.71 22-SEP-10:35 149185.99 0.93
October 0.00 0.00 0.264660E+12 0.213968E+12 330532.01 04-OCT-18:07 153364.15 0.62
November 0.00 0.00 0.669939E+11 0.659549E+11 206782.26 19-NOV-11:35 206782.26 0.34
December 0.00 0.00 0.726079E+11 0.726079E+11 188951.31 19-DEC-11:35 188951.31 0.13
                 
Annual Sum or Average 0.00 0.00 0.191246E+13 0.150949E+13       0.56
Minimum of Months 0.00 0.00 0.367906E+11 0.358442E+11 168657.85   149185.99 0.13
Maximum of Months 0.00 0.00 0.395622E+12 0.245998E+12 358736.16   219072.76 0.99



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.199060E+10 0.100768E+10 13498.48 21-JAN-09:01 10436.85 0.47
February 0.00 0.00 0.176972E+10 0.959923E+09 13013.55 06-FEB-16:11 13013.55 0.44
March 0.00 0.00 0.192472E+10 0.894336E+09 12934.99 18-MAR-08:62 9850.45 0.49
April 0.00 0.00 0.386185E+10 0.186345E+10 13232.20 08-APR-08:61 10317.65 0.77
May 0.00 0.00 0.359013E+10 0.163179E+10 13480.33 06-MAY-08:62 9721.89 0.75
June 0.00 0.00 0.509254E+10 0.236927E+10 13304.03 28-JUN-08:62 9796.06 0.84
July 0.00 0.00 0.717098E+10 0.353203E+10 13808.12 28-JUL-08:61 10183.69 0.91
August 0.00 0.00 0.742449E+10 0.369212E+10 14115.07 06-AUG-08:61 9938.75 0.92
September 0.00 0.00 0.582700E+10 0.278263E+10 13910.19 22-SEP-08:61 9816.54 0.90
October 0.00 0.00 0.527719E+10 0.306802E+10 13917.24 01-OCT-08:62 10093.88 0.74
November 0.00 0.00 0.266970E+10 0.139116E+10 13775.65 12-NOV-09:02 8865.67 0.57
December 0.00 0.00 0.223747E+10 0.150562E+10 13018.01 30-DEC-16:11 13018.01 0.36
                 
Annual Sum or Average 0.00 0.00 0.488364E+11 0.246980E+11       0.68
Minimum of Months 0.00 0.00 0.176972E+10 0.894336E+09 12934.99   8865.67 0.36
Maximum of Months 0.00 0.00 0.742449E+10 0.369212E+10 14115.07   13018.01 0.92



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.401088E+09 0.168981E+09 12891.70 21-JAN-09:01 9039.64 0.20
February 0.00 0.00 0.573449E+09 0.237544E+09 12497.99 06-FEB-16:11 12497.99 0.24
March 0.00 0.00 0.832709E+09 0.300065E+09 12750.07 22-MAR-18:51 10012.38 0.31
April 0.00 0.00 0.220467E+10 0.815301E+09 13535.38 26-APR-21:51 10109.01 0.57
May 0.00 0.00 0.243130E+10 0.943386E+09 13148.39 02-MAY-21:51 10029.88 0.58
June 0.00 0.00 0.324210E+10 0.139007E+10 14066.83 28-JUN-21:51 10194.59 0.55
July 0.00 0.00 0.463825E+10 0.229558E+10 14175.74 27-JUL-21:51 10158.54 0.56
August 0.00 0.00 0.438383E+10 0.207807E+10 14112.64 19-AUG-08:51 9492.82 0.56
September 0.00 0.00 0.312233E+10 0.126745E+10 13630.85 30-SEP-21:51 10000.74 0.55
October 0.00 0.00 0.240236E+10 0.123658E+10 13986.96 01-OCT-08:52 9136.32 0.44
November 0.00 0.00 0.742539E+09 0.272445E+09 13200.56 12-NOV-09:02 8424.68 0.32
December 0.00 0.00 0.420934E+09 0.251463E+09 12705.82 09-DEC-16:11 10054.23 0.15
                 
Annual Sum or Average 0.00 0.00 0.253956E+11 0.112569E+11       0.42
Minimum of Months 0.00 0.00 0.401088E+09 0.168981E+09 12497.99   8424.68 0.15
Maximum of Months 0.00 0.00 0.463825E+10 0.229558E+10 14175.74   12497.99 0.58



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.322250E+11 0.219814E+11 44100.64 14-JAN-12:40 35863.82 0.62
February 0.00 0.00 0.204396E+11 0.133429E+11 39373.30 02-FEB-12:30 37874.78 0.50
March 0.00 0.00 0.150588E+11 0.635206E+10 32231.35 11-MAR-13:10 27208.57 0.56
April 0.00 0.00 0.167383E+11 0.570976E+10 24049.56 08-APR-12:40 13569.70 0.70
May 0.00 0.00 0.928162E+10 0.213320E+10 17223.97 04-MAY-12:30 7149.02 0.62
June 0.00 0.00 0.126085E+11 0.292769E+10 17116.76 30-JUN-06:52 5984.50 0.74
July 0.00 0.00 0.203889E+11 0.578922E+10 20394.87 30-JUL-08:00 8122.04 0.89
August 0.00 0.00 0.280750E+11 0.984033E+10 23027.72 30-AUG-12:50 12375.44 0.98
September 0.00 0.00 0.313742E+11 0.138728E+11 40394.25 30-SEP-13:05 29719.63 0.97
October 0.00 0.00 0.399785E+11 0.253145E+11 49006.30 16-OCT-12:20 45667.75 0.81
November 0.00 0.00 0.332423E+11 0.221390E+11 46466.11 19-NOV-12:30 37950.72 0.66
December 0.00 0.00 0.365154E+11 0.282200E+11 44779.26 19-DEC-13:00 44779.26 0.51
                 
Annual Sum or Average 0.00 0.00 0.295926E+12 0.157623E+12       0.72
Minimum of Months 0.00 0.00 0.928162E+10 0.213320E+10 17116.76   5984.50 0.50
Maximum of Months 0.00 0.00 0.399785E+11 0.282200E+11 49006.30   45667.75 0.98



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.907000E+10 0.439460E+10 74058.69 20-JAN-19:01 57223.99 0.33
February 0.00 0.00 0.105933E+11 0.479933E+10 72168.64 13-FEB-21:12 55780.49 0.47
March 0.00 0.00 0.135104E+11 0.584589E+10 71369.81 22-MAR-18:51 57042.46 0.50
April 0.00 0.00 0.204628E+11 0.991881E+10 77227.40 26-APR-21:51 57640.60 0.53
May 0.00 0.00 0.243965E+11 0.130178E+11 75657.80 04-MAY-21:51 59607.20 0.53
June 0.00 0.00 0.278546E+11 0.158679E+11 80304.64 28-JUN-21:51 58231.89 0.46
July 0.00 0.00 0.335664E+11 0.197103E+11 81639.85 19-JUL-21:51 57206.21 0.48
August 0.00 0.00 0.309877E+11 0.173552E+11 80939.31 16-AUG-21:51 57465.91 0.45
September 0.00 0.00 0.239180E+11 0.124068E+11 80382.99 22-SEP-21:52 55753.74 0.43
October 0.00 0.00 0.212731E+11 0.133279E+11 80373.69 01-OCT-08:52 53888.12 0.36
November 0.00 0.00 0.120257E+11 0.585158E+10 73522.71 09-NOV-22:53 54479.34 0.43
December 0.00 0.00 0.830944E+10 0.488882E+10 70285.34 19-DEC-19:01 70285.34 0.27
                 
Annual Sum or Average 0.00 0.00 0.235968E+12 0.127385E+12       0.44
Minimum of Months 0.00 0.00 0.830944E+10 0.439460E+10 70285.34   53888.12 0.27
Maximum of Months 0.00 0.00 0.335664E+11 0.197103E+11 81639.85   70285.34 0.53



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.210977E+10 0.118809E+10 11538.85 05-JAN-09:01 11538.85 0.49
February 0.00 0.00 0.165654E+10 0.944673E+09 11689.42 14-FEB-09:01 9474.61 0.41
March 0.00 0.00 0.188798E+10 0.883551E+09 11530.08 17-MAR-08:61 9594.78 0.49
April 0.00 0.00 0.348887E+10 0.166980E+10 11535.84 02-APR-08:61 11535.84 0.78
May 0.00 0.00 0.305072E+10 0.138714E+10 12103.56 06-MAY-08:62 8897.26 0.74
June 0.00 0.00 0.426441E+10 0.189385E+10 11924.45 28-JUN-08:62 8682.85 0.86
July 0.00 0.00 0.650447E+10 0.311145E+10 11740.67 13-JUL-18:01 9437.31 0.94
August 0.00 0.00 0.703795E+10 0.344404E+10 12306.04 08-AUG-08:62 8788.89 0.95
September 0.00 0.00 0.499563E+10 0.232098E+10 12226.27 23-SEP-08:62 8393.02 0.89
October 0.00 0.00 0.498973E+10 0.295964E+10 12361.65 01-OCT-08:62 8940.00 0.74
November 0.00 0.00 0.246201E+10 0.139147E+10 12221.28 12-NOV-09:02 7833.15 0.56
December 0.00 0.00 0.223963E+10 0.161738E+10 11534.96 05-DEC-09:01 11534.96 0.35
                 
Annual Sum or Average 0.00 0.00 0.446877E+11 0.228121E+11       0.69
Minimum of Months 0.00 0.00 0.165654E+10 0.883551E+09 11530.08   7833.15 0.35
Maximum of Months 0.00 0.00 0.703795E+10 0.344404E+10 12361.65   11538.85 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.540618E+09 0.280453E+09 11434.26 20-JAN-19:01 8337.41 0.18
February 0.00 0.00 0.568790E+09 0.292663E+09 11246.91 14-FEB-09:01 8902.93 0.20
March 0.00 0.00 0.883974E+09 0.376626E+09 11143.37 17-MAR-08:61 9173.15 0.30
April 0.00 0.00 0.208473E+10 0.938474E+09 11848.85 02-APR-08:51 11848.85 0.58
May 0.00 0.00 0.213261E+10 0.913868E+09 12166.21 24-MAY-08:51 12166.21 0.58
June 0.00 0.00 0.284941E+10 0.124777E+10 12777.26 30-JUN-08:51 10385.04 0.57
July 0.00 0.00 0.430869E+10 0.207928E+10 13180.99 22-JUL-08:51 10196.44 0.58
August 0.00 0.00 0.424047E+10 0.200118E+10 13369.21 19-AUG-08:51 10076.39 0.58
September 0.00 0.00 0.256089E+10 0.109121E+10 12838.66 10-SEP-08:51 10316.89 0.57
October 0.00 0.00 0.221956E+10 0.124053E+10 12831.13 15-OCT-07:41 12831.13 0.45
November 0.00 0.00 0.713650E+09 0.342786E+09 11697.62 12-NOV-09:02 7425.82 0.26
December 0.00 0.00 0.456909E+09 0.297328E+09 11606.75 05-DEC-09:41 11606.75 0.13
                 
Annual Sum or Average 0.00 0.00 0.235603E+11 0.111022E+11       0.42
Minimum of Months 0.00 0.00 0.456909E+09 0.280453E+09 11143.37   7425.82 0.13
Maximum of Months 0.00 0.00 0.430869E+10 0.207928E+10 13369.21   12831.13 0.58



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.426113E+09 0.226366E+09 3683.27 21-JAN-09:01 2444.58 0.37
February 0.00 0.00 0.392098E+09 0.222266E+09 3500.01 14-FEB-09:01 2271.89 0.32
March 0.00 0.00 0.462692E+09 0.233948E+09 3494.89 24-MAR-08:61 2415.03 0.38
April 0.00 0.00 0.960424E+09 0.499799E+09 3601.07 08-APR-08:61 2449.08 0.70
May 0.00 0.00 0.878124E+09 0.429480E+09 3705.51 06-MAY-08:62 2233.18 0.68
June 0.00 0.00 0.128588E+10 0.632113E+09 3577.55 28-JUN-08:62 2391.45 0.84
July 0.00 0.00 0.184673E+10 0.944010E+09 3713.76 22-JUL-08:61 2548.02 0.92
August 0.00 0.00 0.188460E+10 0.968048E+09 3857.95 06-AUG-08:61 2402.99 0.92
September 0.00 0.00 0.140991E+10 0.694599E+09 3766.68 22-SEP-08:61 2374.82 0.89
October 0.00 0.00 0.122593E+10 0.725928E+09 3793.78 01-OCT-08:62 2481.24 0.68
November 0.00 0.00 0.568634E+09 0.305925E+09 3535.30 11-NOV-16:12 2401.50 0.45
December 0.00 0.00 0.472273E+09 0.326948E+09 3458.11 10-DEC-09:01 2458.47 0.28
                 
Annual Sum or Average 0.00 0.00 0.118134E+11 0.620943E+10       0.62
Minimum of Months 0.00 0.00 0.392098E+09 0.222266E+09 3458.11   2233.18 0.28
Maximum of Months 0.00 0.00 0.188460E+10 0.968048E+09 3857.95   2548.02 0.92



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 65508373.74 30669007.87 3430.40 21-JAN-09:01 2127.38 0.10
February 0.00 0.00 0.107684E+09 46975033.66 3243.92 15-FEB-16:11 2693.45 0.16
March 0.00 0.00 0.186790E+09 73577936.40 3374.42 22-MAR-18:51 2687.81 0.22
April 0.00 0.00 0.539022E+09 0.217245E+09 3607.49 26-APR-21:51 2651.80 0.51
May 0.00 0.00 0.600209E+09 0.251636E+09 3528.91 06-MAY-08:62 2208.63 0.55
June 0.00 0.00 0.873505E+09 0.394834E+09 3752.00 28-JUN-21:51 2687.07 0.56
July 0.00 0.00 0.128649E+10 0.661302E+09 3770.06 27-JUL-21:51 2668.62 0.57
August 0.00 0.00 0.118331E+10 0.576542E+09 3741.27 19-AUG-08:51 2416.27 0.57
September 0.00 0.00 0.761589E+09 0.310751E+09 3604.08 07-SEP-21:51 2439.47 0.57
October 0.00 0.00 0.532004E+09 0.280161E+09 3724.17 01-OCT-08:52 2248.38 0.39
November 0.00 0.00 0.115070E+09 43247184.30 3269.29 10-NOV-22:12 2314.36 0.19
December 0.00 0.00 60015577.37 39231308.71 3351.91 09-DEC-16:11 2510.99 0.06
                 
Annual Sum or Average 0.00 0.00 0.631120E+10 0.292617E+10       0.37
Minimum of Months 0.00 0.00 60015577.37 30669007.87 3243.92   2127.38 0.06
Maximum of Months 0.00 0.00 0.128649E+10 0.661302E+09 3770.06   2693.45 0.57



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.739189E+10 0.531886E+10 15822.26 14-JAN-16:11 15822.26 0.64
February 0.00 0.00 0.493089E+10 0.332234E+10 15823.01 06-FEB-16:11 15823.01 0.58
March 0.00 0.00 0.428038E+10 0.233373E+10 15911.66 18-MAR-08:62 12757.08 0.60
April 0.00 0.00 0.514242E+10 0.241842E+10 16024.71 08-APR-08:61 13044.53 0.77
May 0.00 0.00 0.324229E+10 0.125440E+10 16397.52 06-MAY-08:62 11919.99 0.66
June 0.00 0.00 0.431042E+10 0.159808E+10 16426.34 27-JUN-18:01 12763.59 0.79
July 0.00 0.00 0.682349E+10 0.276705E+10 17168.46 30-JUL-08:62 12186.50 0.88
August 0.00 0.00 0.861233E+10 0.382447E+10 17509.50 20-AUG-08:62 11922.49 0.91
September 0.00 0.00 0.842279E+10 0.428601E+10 17201.77 22-SEP-08:61 11807.12 0.88
October 0.00 0.00 0.970676E+10 0.663109E+10 17441.66 01-OCT-08:62 11972.57 0.75
November 0.00 0.00 0.755604E+10 0.526147E+10 16471.56 12-NOV-09:02 11744.24 0.69
December 0.00 0.00 0.793321E+10 0.637398E+10 15890.97 08-DEC-16:11 13184.81 0.51
                 
Annual Sum or Average 0.00 0.00 0.783529E+11 0.453899E+11       0.72
Minimum of Months 0.00 0.00 0.324229E+10 0.125440E+10 15822.26   11744.24 0.51
Maximum of Months 0.00 0.00 0.970676E+10 0.663109E+10 17509.50   15823.01 0.91



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 10021.95 109821.79 08-JAN-06:50
February 0.00 0.00 01-FEB-00:05 5437.59 65892.00 05-FEB-06:00
March 0.00 0.00 01-MAR-00:05 8872.90 90282.33 30-MAR-03:00
April 0.00 0.00 01-APR-00:10 2016.75 44725.14 01-APR-06:00
May 0.00 0.00 01-MAY-00:10 2005.21 33662.67 14-MAY-04:50
June 0.00 0.00 01-JUN-00:10 462.61 17838.87 02-JUN-08:54
July 0.00 0.00 01-JUL-00:10 96.39 17667.72 08-JUL-08:56
August 0.00 0.00 01-AUG-00:10 27.35 15643.33 22-AUG-08:54
September 0.00 0.00 01-SEP-00:10 176.72 16849.94 08-SEP-08:54
October 0.00 0.00 01-OCT-00:10 661.75 18525.63 30-OCT-04:00
November 0.00 0.00 01-NOV-00:10 3787.72 44668.18 24-NOV-04:00
December 0.00 0.00 01-DEC-00:05 8031.70 68400.72 23-DEC-06:00
             
Annual Sum or Average 0.00     3470.69    
Minimum of Months 0.00 0.00   27.35 15643.33  
Maximum of Months 0.00 0.00   10021.95 109821.79  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 46894.98 304197.46 15-JAN-09:52 0.00 0.00 01-JAN-00:05
February 34645.17 307404.59 01-FEB-09:51 0.00 0.00 01-FEB-00:05
March 32107.58 289111.40 11-MAR-09:51 0.00 0.00 01-MAR-00:05
April 61416.14 278719.34 26-APR-08:52 0.00 0.00 01-APR-00:10
May 60149.04 215121.91 04-MAY-08:52 0.00 0.00 01-MAY-00:10
June 100732.81 388027.64 29-JUN-18:03 0.00 0.00 01-JUN-00:10
July 176027.94 476531.38 18-JUL-18:03 0.00 0.00 01-JUL-00:10
August 196159.20 476865.41 18-AUG-15:13 0.00 0.00 01-AUG-00:10
September 133685.07 457987.76 21-SEP-21:52 0.00 0.00 01-SEP-00:10
October 140697.52 444359.39 14-OCT-15:13 0.00 0.00 01-OCT-00:10
November 52142.85 359604.32 19-NOV-09:41 0.00 0.00 01-NOV-00:10
December 52253.64 335244.60 05-DEC-09:41 0.00 0.00 01-DEC-00:05
             
Annual Sum or Average 91074.95     0.00    
Minimum of Months 32107.58 215121.91   0.00 0.00  
Maximum of Months 196159.20 476865.41   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 23120.51 48443.79 31-JAN-07:55
February 0.00 0.00 01-FEB-00:05 23150.48 48445.78 02-FEB-07:55
March 0.00 0.00 01-MAR-00:05 22919.28 48206.13 01-MAR-08:00
April 0.00 0.00 01-APR-00:10 22438.01 47336.37 03-APR-06:53
May 0.00 0.00 01-MAY-00:10 21878.40 46291.71 01-MAY-07:00
June 0.00 0.00 01-JUN-00:10 21381.45 45108.81 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 21050.28 44195.16 03-JUL-06:50
August 0.00 0.00 01-AUG-00:10 21039.85 44109.22 31-AUG-06:56
September 0.00 0.00 01-SEP-00:10 21284.59 44854.86 29-SEP-06:54
October 0.00 0.00 01-OCT-00:10 21748.39 46034.07 31-OCT-07:00
November 0.00 0.00 01-NOV-00:10 22311.73 47180.68 30-NOV-07:55
December 0.00 0.00 01-DEC-00:05 22812.07 48035.37 29-DEC-07:30
             
Annual Sum or Average 0.00     22088.55    
Minimum of Months 0.00 0.00   21039.85 44109.22  
Maximum of Months 0.00 0.00   23150.48 48445.78  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.261333E+10 0.68 1299.30 01-JAN-00:50 0.89
February 0.236042E+10 0.68 1299.30 01-FEB-01:10 0.89
March 0.261333E+10 0.68 1299.30 01-MAR-00:40 0.89
April 0.252903E+10 0.68 1299.30 01-APR-01:30 0.89
May 0.261333E+10 0.68 1299.30 01-MAY-01:50 0.89
June 0.252903E+10 0.68 1299.30 01-JUN-04:40 0.89
July 0.261333E+10 0.68 1299.30 01-JUL-08:57 0.89
August 0.261333E+10 0.68 1299.30 01-AUG-08:56 0.89
September 0.252903E+10 0.68 1299.30 30-SEP-15:50 0.89
October 0.261333E+10 0.68 1299.30 15-OCT-15:50 0.89
November 0.252903E+10 0.68 1299.30 01-NOV-01:20 0.89
December 0.261333E+10 0.68 1299.30 01-DEC-01:20 0.89
           
Annual Sum or Average 0.307698E+11 0.68      
Minimum of Months 0.236042E+10 0.68 1299.30   0.89
Maximum of Months 0.261333E+10 0.68 1299.30   0.89



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.429772E+11 0.98 22144.87 18-JAN-21:00 1.19
February 0.387061E+11 0.98 22102.70 01-FEB-20:30 1.19
March 0.427745E+11 0.98 22088.84 23-MAR-19:50 1.18
April 0.416701E+11 0.98 22172.98 26-APR-21:10 1.18
May 0.431710E+11 0.98 22636.11 04-MAY-21:10 1.20
June 0.421281E+11 0.98 22902.35 28-JUN-21:10 1.21
July 0.438245E+11 0.99 22888.89 28-JUL-21:10 1.21
August 0.440037E+11 0.99 23141.98 18-AUG-21:20 1.22
September 0.422814E+11 0.98 26390.43 29-SEP-21:20 1.33
October 0.439095E+11 0.99 25929.10 16-OCT-21:20 1.32
November 0.417729E+11 0.98 22111.30 01-NOV-19:40 1.19
December 0.430687E+11 0.98 22424.26 05-DEC-22:10 1.21
           
Annual Sum or Average 0.510288E+12 0.98      
Minimum of Months 0.387061E+11 0.98 22088.84   1.18
Maximum of Months 0.440037E+11 0.99 26390.43   1.33



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:05 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:05 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:05 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.27
May 0.205205E+09 0.27 76.61 01-MAY-00:10 0.27
June 0.198586E+09 0.27 76.61 01-JUN-00:10 0.27
July 0.205205E+09 0.27 76.61 01-JUL-00:10 0.27
August 0.205205E+09 0.27 76.61 01-AUG-00:10 0.27
September 0.198586E+09 0.27 76.61 01-SEP-00:10 0.27
October 0.205205E+09 0.27 76.61 01-OCT-00:10 0.27
November 0.198586E+09 0.27 76.61 01-NOV-00:10 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:05 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.27 76.61   0.27
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:10 -0.0
May 0.00 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 -0.0
September 0.00 -0.0 0.00 01-SEP-00:10 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 -0.0
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 -0.0 0.00 01-JUN-00:10 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 -0.0 0.00 01-SEP-00:10 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 -0.0 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 -0.0 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:10 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:10 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:05 0.27
July 0.116283E+10 0.19 612.92 01-JUL-06:05 0.27
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.27
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.27
October 0.116283E+10 0.19 612.92 01-OCT-06:10 0.27
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:05 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.27
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.144012E+09 0.49 637.45 01-JAN-09:01 0.58
February 0.122069E+09 0.46 637.45 01-FEB-09:01 0.59
March 0.143813E+09 0.45 637.45 01-MAR-09:01 0.58
April 0.182366E+09 0.49 637.45 01-APR-15:11 0.58
May 0.169206E+09 0.47 637.45 01-MAY-08:62 0.58
June 0.216357E+09 0.49 637.45 01-JUN-08:62 0.58
July 0.293845E+09 0.53 637.45 01-JUL-08:61 0.58
August 0.300749E+09 0.54 637.45 01-AUG-08:62 0.58
September 0.245204E+09 0.53 637.45 01-SEP-08:62 0.58
October 0.240093E+09 0.51 637.45 01-OCT-08:62 0.58
November 0.140678E+09 0.49 637.45 01-NOV-08:61 0.58
December 0.147544E+09 0.49 637.45 01-DEC-09:01 0.58
           
Annual Sum or Average 0.234594E+10 0.50      
Minimum of Months 0.122069E+09 0.45 637.45   0.58
Maximum of Months 0.300749E+09 0.54 637.45   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.108785E+09 0.38 612.02 02-JAN-16:12 0.58
February 85978122.77 0.39 612.02 01-FEB-19:01 0.58
March 0.107564E+09 0.40 612.02 01-MAR-19:01 0.58
April 0.103913E+09 0.38 612.02 02-APR-19:02 0.58
May 0.110582E+09 0.36 612.02 01-MAY-08:51 0.58
June 0.127580E+09 0.32 612.02 01-JUN-08:51 0.58
July 0.177738E+09 0.33 612.02 01-JUL-08:51 0.58
August 0.166623E+09 0.32 612.02 01-AUG-08:51 0.58
September 0.125112E+09 0.32 612.02 01-SEP-08:51 0.58
October 0.112017E+09 0.32 612.02 01-OCT-08:52 0.58
November 74219247.08 0.38 612.02 01-NOV-08:61 0.58
December 98172289.30 0.38 612.02 02-DEC-16:11 0.58
           
Annual Sum or Average 0.139828E+10 0.36      
Minimum of Months 74219247.08 0.32 612.02   0.58
Maximum of Months 0.177738E+09 0.40 612.02   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.113783E+10 0.45 2014.05 14-JAN-12:40 0.59
February 0.722424E+09 0.37 1224.60 03-FEB-13:50 0.59
March 0.553672E+09 0.33 1045.34 11-MAR-13:10 0.58
April 0.617641E+09 0.42 752.14 08-APR-12:50 0.58
May 0.379336E+09 0.36 557.71 04-MAY-12:30 0.58
June 0.481961E+09 0.43 519.43 30-JUN-06:52 0.58
July 0.727378E+09 0.52 598.59 30-JUL-08:00 0.58
August 0.967692E+09 0.57 720.50 30-AUG-13:00 0.58
September 0.108027E+10 0.57 1822.15 30-SEP-13:05 0.58
October 0.141885E+10 0.54 2307.90 16-OCT-12:20 0.59
November 0.116462E+10 0.49 2033.97 19-NOV-09:53 0.58
December 0.130403E+10 0.47 1938.01 25-DEC-13:30 0.58
           
Annual Sum or Average 0.105557E+11 0.46      
Minimum of Months 0.379336E+09 0.33 519.43   0.58
Maximum of Months 0.141885E+10 0.57 2307.90   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.653041E+09 0.36 3512.32 01-JAN-09:01 0.58
February 0.589192E+09 0.37 3512.32 01-FEB-09:51 0.59
March 0.783967E+09 0.37 3512.32 01-MAR-09:01 0.59
April 0.852112E+09 0.33 3512.32 01-APR-08:61 0.59
May 0.101774E+10 0.31 3512.32 01-MAY-08:51 0.58
June 0.109614E+10 0.27 3512.32 01-JUN-08:51 0.58
July 0.132932E+10 0.28 3512.32 01-JUL-08:51 0.58
August 0.118569E+10 0.27 3512.32 01-AUG-08:51 0.58
September 0.921478E+09 0.25 3512.32 01-SEP-08:51 0.58
October 0.913641E+09 0.27 3512.32 01-OCT-08:52 0.58
November 0.610947E+09 0.34 3512.32 01-NOV-08:61 0.58
December 0.589703E+09 0.35 3512.32 01-DEC-09:01 0.58
           
Annual Sum or Average 0.105430E+11 0.31      
Minimum of Months 0.589192E+09 0.25 3512.32   0.58
Maximum of Months 0.132932E+10 0.37 3512.32   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.144262E+09 0.50 564.61 01-JAN-09:01 0.58
February 0.119629E+09 0.47 564.61 01-FEB-09:01 0.59
March 0.139795E+09 0.46 564.61 01-MAR-09:01 0.58
April 0.164047E+09 0.52 564.61 01-APR-08:61 0.58
May 0.144734E+09 0.49 564.61 01-MAY-08:62 0.58
June 0.179476E+09 0.51 564.61 01-JUN-08:62 0.58
July 0.261370E+09 0.55 564.61 01-JUL-08:61 0.58
August 0.280726E+09 0.55 564.61 01-AUG-08:62 0.58
September 0.208278E+09 0.52 564.61 01-SEP-08:62 0.58
October 0.225251E+09 0.52 564.61 01-OCT-08:62 0.58
November 0.136211E+09 0.50 564.61 01-NOV-08:61 0.58
December 0.148107E+09 0.50 564.61 01-DEC-09:01 0.58
           
Annual Sum or Average 0.215188E+10 0.51      
Minimum of Months 0.119629E+09 0.46 564.61   0.58
Maximum of Months 0.280726E+09 0.55 564.61   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.102492E+09 0.36 542.34 01-JAN-09:01 0.58
February 86855741.05 0.37 542.34 01-FEB-09:51 0.59
March 0.108132E+09 0.40 542.34 01-MAR-09:01 0.58
April 0.103800E+09 0.41 542.34 01-APR-08:61 0.58
May 0.102937E+09 0.38 542.34 01-MAY-08:51 0.58
June 0.119270E+09 0.33 542.34 01-JUN-08:51 0.58
July 0.174211E+09 0.34 542.34 01-JUL-08:51 0.58
August 0.171390E+09 0.34 542.34 01-AUG-08:51 0.58
September 0.109345E+09 0.33 542.34 01-SEP-08:51 0.58
October 0.105885E+09 0.34 542.34 01-OCT-08:52 0.58
November 74270537.40 0.35 542.34 01-NOV-08:61 0.58
December 93805604.05 0.35 542.34 01-DEC-09:01 0.58
           
Annual Sum or Average 0.135239E+10 0.36      
Minimum of Months 74270537.40 0.33 542.34   0.58
Maximum of Months 0.174211E+09 0.41 542.34   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 41237045.09 0.48 165.80 02-JAN-16:12 0.58
February 36341626.53 0.46 165.80 01-FEB-09:01 0.59
March 43215255.96 0.46 165.80 01-MAR-16:11 0.58
April 48370050.85 0.50 165.80 01-APR-15:11 0.58
May 44571004.68 0.49 165.80 01-MAY-08:62 0.58
June 55790292.57 0.51 165.80 01-JUN-15:11 0.58
July 76679422.24 0.54 165.80 01-JUL-08:61 0.58
August 77310265.89 0.54 165.80 01-AUG-08:62 0.58
September 60378098.79 0.53 165.80 01-SEP-08:62 0.58
October 58832070.56 0.51 165.80 01-OCT-08:62 0.58
November 37256775.61 0.49 165.80 01-NOV-08:61 0.58
December 41819716.04 0.49 165.80 01-DEC-09:01 0.58
           
Annual Sum or Average 0.621802E+09 0.50      
Minimum of Months 36341626.53 0.46 165.80   0.58
Maximum of Months 77310265.89 0.54 165.80   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 37704775.58 0.38 158.80 01-JAN-09:01 0.58
February 29492497.75 0.39 158.80 01-FEB-19:01 0.58
March 34831886.82 0.40 158.80 01-MAR-09:01 0.58
April 27824230.81 0.39 158.80 02-APR-19:02 0.58
May 28959778.56 0.38 158.80 01-MAY-08:51 0.58
June 34673436.76 0.33 158.80 01-JUN-08:51 0.58
July 49982536.40 0.33 158.80 01-JUL-08:51 0.58
August 45536651.29 0.33 158.80 01-AUG-08:51 0.58
September 30852650.27 0.34 158.80 01-SEP-08:51 0.58
October 27568023.19 0.32 158.80 01-OCT-08:52 0.58
November 25058561.52 0.38 158.80 01-NOV-19:12 0.58
December 34731876.14 0.37 158.80 02-DEC-16:11 0.58
           
Annual Sum or Average 0.407217E+09 0.36      
Minimum of Months 25058561.52 0.32 158.80   0.58
Maximum of Months 49982536.40 0.40 158.80   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.365056E+09 0.53 770.52 01-JAN-09:01 0.58
February 0.250137E+09 0.50 770.52 01-FEB-09:01 0.59
March 0.236922E+09 0.48 770.52 01-MAR-09:01 0.58
April 0.226815E+09 0.50 770.52 01-APR-08:61 0.58
May 0.159306E+09 0.46 770.52 01-MAY-08:62 0.58
June 0.179110E+09 0.47 770.52 01-JUN-08:62 0.58
July 0.264690E+09 0.51 770.52 01-JUL-08:61 0.58
August 0.330850E+09 0.53 770.52 01-AUG-08:62 0.58
September 0.337785E+09 0.52 770.52 01-SEP-08:62 0.58
October 0.438165E+09 0.53 770.52 01-OCT-08:62 0.58
November 0.345969E+09 0.53 770.52 01-NOV-08:61 0.58
December 0.395147E+09 0.53 770.52 01-DEC-09:01 0.58
           
Annual Sum or Average 0.352995E+10 0.51      
Minimum of Months 0.159306E+09 0.46 770.52   0.58
Maximum of Months 0.438165E+09 0.53 770.52   0.59



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.223755E+09 0.203393E+09 514.20 08-JAN-06:50 467.40 467.40 37.75 1.18
February 0.145937E+09 0.132657E+09 408.55 05-FEB-06:00 371.37 371.37 35.95 0.66
March 0.218134E+09 0.198284E+09 476.65 30-MAR-03:00 433.27 433.27 36.50 0.92
April 66912176.74 60823168.65 320.25 01-APR-06:00 291.10 291.10 35.84 0.44
May 62171963.86 56514315.15 248.44 14-MAY-04:50 225.83 225.83 34.41 0.31
June 12164829.26 11057829.80 156.37 02-JUN-08:54 142.14 142.14 36.39 0.18
July 1984389.61 1803810.16 134.31 08-JUL-08:56 122.08 122.08 32.29 0.15
August 698906.13 635305.68 150.47 22-AUG-08:54 136.78 136.78 38.36 0.17
September 5336182.70 4850590.07 160.72 19-SEP-08:54 146.10 146.10 39.66 0.19
October 22115812.39 20103273.46 170.57 30-OCT-08:53 155.05 155.05 43.42 0.20
November 0.107883E+09 98065628.70 319.00 24-NOV-04:00 289.97 289.97 35.74 0.44
December 0.195717E+09 0.177907E+09 417.41 23-DEC-06:00 379.43 379.43 36.02 0.68
                 
Annual Sum or Average 0.106281E+10 0.966094E+09            
Minimum of Months 698906.13 635305.68 134.31   122.08 122.08 32.29 0.15
Maximum of Months 0.223755E+09 0.203393E+09 514.20   467.40 467.40 43.42 1.18



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 86278381.29 78427048.60 592.83 24-JAN-09:51 538.89 538.89 6.72 9.56
February 47702607.63 43361670.33 349.43 01-FEB-13:10 317.63 317.63 6.72 7.60
March 53360228.92 48504448.09 565.96 11-MAR-11:50 514.46 514.46 6.72 9.38
April 0.107144E+09 97393996.34 508.98 13-APR-08:51 462.67 462.67 6.72 8.96
May 0.101061E+09 91864541.99 267.63 03-MAY-09:50 243.27 243.27 6.72 6.75
June 0.180654E+09 0.164214E+09 688.53 29-JUN-18:03 625.88 625.88 6.72 10.19
July 0.449974E+09 0.409026E+09 1045.73 18-JUL-18:03 950.57 950.57 6.72 12.14
August 0.528700E+09 0.480588E+09 934.68 17-AUG-15:23 849.63 849.63 6.72 11.58
September 0.327676E+09 0.297857E+09 1546.67 29-SEP-15:13 1405.92 1405.92 6.72 14.24
October 0.358496E+09 0.325873E+09 1403.30 17-OCT-10:50 1275.60 1275.60 6.72 13.69
November 92643425.24 84212873.55 742.51 19-NOV-10:40 674.94 674.94 6.72 10.52
December 80126490.98 72834980.30 440.76 16-DEC-09:52 400.65 400.65 6.72 8.42
                 
Annual Sum or Average 0.241382E+10 0.219416E+10            
Minimum of Months 47702607.63 43361670.33 267.63   243.27 243.27 6.72 6.75
Maximum of Months 0.528700E+09 0.480588E+09 1546.67   1405.92 1405.92 6.72 14.24



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.499140E+10 0.453718E+10 2082.09 01-JAN-00:05 1892.62 1892.62 6.72 18.60
February 0.463130E+10 0.420985E+10 2082.09 01-FEB-00:05 1892.62 1892.62 6.83 18.60
March 0.480776E+10 0.437025E+10 2082.09 01-MAR-00:05 1892.62 1892.62 6.76 18.60
April 0.532984E+10 0.484483E+10 2082.09 01-APR-00:10 1892.62 1892.62 6.75 18.60
May 0.556148E+10 0.505538E+10 2082.09 01-MAY-00:10 1892.62 1892.62 7.28 18.60
June 0.539678E+10 0.490568E+10 2082.09 01-JUN-00:10 1892.62 1892.62 6.97 18.60
July 0.557668E+10 0.506920E+10 2082.09 01-JUL-00:10 1892.62 1892.62 8.03 18.60
August 0.557668E+10 0.506920E+10 2082.09 01-AUG-00:10 1892.62 1892.62 8.95 18.60
September 0.539678E+10 0.490568E+10 2082.09 01-SEP-00:10 1892.62 1892.62 7.55 18.60
October 0.557668E+10 0.506920E+10 2082.09 01-OCT-00:10 1892.62 1892.62 9.27 18.60
November 0.523563E+10 0.475919E+10 2082.09 01-NOV-00:10 1892.62 1892.62 7.15 18.60
December 0.518441E+10 0.471263E+10 2082.09 01-DEC-00:05 1892.62 1892.62 6.87 18.60
                 
Annual Sum or Average 0.632654E+11 0.575083E+11            
Minimum of Months 0.463130E+10 0.420985E+10 2082.09   1892.62 1892.62 6.72 18.60
Maximum of Months 0.557668E+10 0.506920E+10 2082.09   1892.62 1892.62 9.27 18.60



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 50.16 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:05 14.37 14.37 51.10 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:05 14.37 14.37 51.14 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 53.59 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 53.73 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:10 14.37 14.37 53.90 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 54.02 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:10 14.37 14.37 54.07 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:10 14.37 14.37 54.03 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 53.19 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 53.77 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:05 14.37 14.37 51.33 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 50.16 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 54.07 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 40.79 60.00 10021.95 109821.79 08-JAN-06:50
February 0.00 0.00 01-FEB-00:05 44.42 60.00 5437.59 65892.00 05-FEB-06:00
March 0.00 0.00 01-MAR-00:05 35.02 60.00 8872.90 90282.33 30-MAR-03:00
April 0.00 0.00 01-APR-00:10 42.36 60.00 2016.75 44725.14 01-APR-06:00
May 0.00 0.00 01-MAY-00:10 39.73 39.73 2005.21 33662.67 14-MAY-04:50
June 0.00 0.00 01-JUN-00:10 39.20 60.00 462.61 17838.87 02-JUN-08:54
July 0.00 0.00 01-JUL-00:10 29.69 29.69 96.39 17667.72 08-JUL-08:56
August 0.00 0.00 01-AUG-00:10 30.08 30.08 27.35 15643.33 22-AUG-08:54
September 0.00 0.00 01-SEP-00:10 40.14 40.14 176.72 16849.94 08-SEP-08:54
October 0.00 0.00 01-OCT-00:10 39.03 39.03 661.75 18525.63 30-OCT-04:00
November 0.00 0.00 01-NOV-00:10 41.68 41.68 3787.72 44668.18 24-NOV-04:00
December 0.00 0.00 01-DEC-00:05 44.83 60.00 8031.70 68400.72 23-DEC-06:00
                 
Annual Sum or Average 0.00         3470.69    
Minimum of Months 0.00 0.00   29.69 29.69 27.35 15643.33  
Maximum of Months 0.00 0.00   44.83 60.00 10021.95 109821.79  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 46894.98 304197.46 15-JAN-09:52 10.60 6.70 0.00 0.00 01-JAN-00:05
February 34645.17 307404.59 01-FEB-09:51 10.64 6.70 0.00 0.00 01-FEB-00:05
March 32107.58 289111.40 11-MAR-09:51 10.41 6.70 0.00 0.00 01-MAR-00:05
April 61416.14 278719.34 26-APR-08:52 10.28 6.70 0.00 0.00 01-APR-00:10
May 60149.04 215121.91 04-MAY-08:52 9.46 6.70 0.00 0.00 01-MAY-00:10
June 100732.81 388027.64 29-JUN-18:03 11.68 6.70 0.00 0.00 01-JUN-00:10
July 176027.94 476531.38 18-JUL-18:03 12.82 6.70 0.00 0.00 01-JUL-00:10
August 196159.20 476865.41 18-AUG-15:13 12.82 6.70 0.00 0.00 01-AUG-00:10
September 133685.07 457987.76 21-SEP-21:52 12.58 6.70 0.00 0.00 01-SEP-00:10
October 140697.52 444359.39 14-OCT-15:13 12.40 6.70 0.00 0.00 01-OCT-00:10
November 52142.85 359604.32 19-NOV-09:41 11.31 6.70 0.00 0.00 01-NOV-00:10
December 52253.64 335244.60 05-DEC-09:41 11.00 6.70 0.00 0.00 01-DEC-00:05
                 
Annual Sum or Average 91074.95         0.00    
Minimum of Months 32107.58 215121.91   9.46 6.70 0.00 0.00  
Maximum of Months 196159.20 476865.41   12.82 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 50.16 60.05 23120.51 48443.79 31-JAN-07:55
February 0.00 0.00 01-FEB-00:05 51.10 60.05 23150.48 48445.78 02-FEB-07:55
March 0.00 0.00 01-MAR-00:05 51.14 60.05 22919.28 48206.13 01-MAR-08:00
April 0.00 0.00 01-APR-00:10 53.59 60.05 22438.01 47336.37 03-APR-06:53
May 0.00 0.00 01-MAY-00:10 53.73 60.05 21878.40 46291.71 01-MAY-07:00
June 0.00 0.00 01-JUN-00:10 53.90 60.05 21381.45 45108.81 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 54.02 60.05 21050.28 44195.16 03-JUL-06:50
August 0.00 0.00 01-AUG-00:10 54.07 60.05 21039.85 44109.22 31-AUG-06:56
September 0.00 0.00 01-SEP-00:10 54.03 60.05 21284.59 44854.86 29-SEP-06:54
October 0.00 0.00 01-OCT-00:10 53.19 60.05 21748.39 46034.07 31-OCT-07:00
November 0.00 0.00 01-NOV-00:10 53.77 60.05 22311.73 47180.68 30-NOV-07:55
December 0.00 0.00 01-DEC-00:05 51.33 60.05 22812.07 48035.37 29-DEC-07:30
                 
Annual Sum or Average 0.00         22088.55    
Minimum of Months 0.00 0.00   50.16 60.05 21039.85 44109.22  
Maximum of Months 0.00 0.00   54.07 60.05 23150.48 48445.78  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.781976E+10 0.00 0.325784E+10 0.261333E+10 0.00 0.00
February 0.630431E+10 0.00 0.176477E+10 0.236042E+10 0.00 0.00
March 0.841655E+10 0.00 0.195362E+10 0.261333E+10 0.00 0.00
April 0.400991E+10 0.00 0.490019E+10 0.252903E+10 0.00 0.00
May 0.358791E+10 0.00 0.521145E+10 0.261333E+10 0.00 0.00
June 0.637782E+09 0.00 0.118888E+11 0.252903E+10 0.00 0.00
July 37024146.19 0.00 0.270220E+11 0.261333E+10 0.00 0.00
August 16924735.47 0.00 0.309007E+11 0.261333E+10 0.00 0.00
September 0.317077E+09 0.00 0.175428E+11 0.252903E+10 0.00 0.00
October 0.142155E+10 0.00 0.195118E+11 0.261333E+10 0.00 0.00
November 0.557451E+10 0.00 0.327790E+10 0.252903E+10 0.00 0.00
December 0.786357E+10 0.00 0.398719E+10 0.261333E+10 0.00 0.00
             
Annual Sum or Average 0.460069E+11 0.00 0.131219E+12 0.307698E+11 0.00 0.00
Minimum of Months 16924735.47 0.00 0.176477E+10 0.236042E+10 0.00 0.00
Maximum of Months 0.841655E+10 0.00 0.309007E+11 0.261333E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.143713E+11 0.00 0.635666E+11 0.429772E+11 0.00 0.00
February 0.456679E+10 0.00 0.367906E+11 0.387061E+11 0.00 0.00
March 0.115024E+11 0.00 0.406281E+11 0.427745E+11 0.00 0.00
April 0.753885E+09 0.00 0.939448E+11 0.416701E+11 0.00 0.00
May 0.142915E+10 0.00 0.101202E+12 0.431710E+11 0.00 0.00
June 0.509318E+09 0.00 0.181922E+12 0.421281E+11 0.00 0.00
July 0.199056E+09 0.00 0.352875E+12 0.438245E+11 0.00 0.00
August 25360506.08 0.00 0.395622E+12 0.440037E+11 0.00 0.00
September 75648215.63 0.00 0.241649E+12 0.422814E+11 0.00 0.00
October 0.213336E+09 0.00 0.264660E+12 0.439095E+11 0.00 0.00
November 0.299541E+10 0.00 0.669939E+11 0.417729E+11 0.00 0.00
December 0.102765E+11 0.00 0.726079E+11 0.430687E+11 0.00 0.00
             
Annual Sum or Average 0.469181E+11 0.00 0.191246E+13 0.510288E+12 0.00 0.00
Minimum of Months 25360506.08 0.00 0.367906E+11 0.387061E+11 0.00 0.00
Maximum of Months 0.143713E+11 0.00 0.395622E+12 0.440037E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.261333E+10 0.325784E+10 0.781976E+10 0.00 0.00 0.00 0.00 0.00
February 0.236042E+10 0.176477E+10 0.630431E+10 0.00 0.00 0.00 0.00 0.00
March 0.261333E+10 0.195362E+10 0.841655E+10 0.00 0.00 0.00 0.00 0.00
April 0.252903E+10 0.490019E+10 0.400991E+10 0.00 0.00 0.00 0.00 0.00
May 0.261333E+10 0.521145E+10 0.358791E+10 0.00 0.00 0.00 0.00 0.00
June 0.252903E+10 0.118888E+11 0.637782E+09 0.00 0.00 0.00 0.00 0.00
July 0.261333E+10 0.270220E+11 37024146.19 0.00 0.00 0.00 0.00 0.00
August 0.261333E+10 0.309007E+11 16924735.47 0.00 0.00 0.00 0.00 0.00
September 0.252903E+10 0.175428E+11 0.317077E+09 0.00 0.00 0.00 0.00 0.00
October 0.261333E+10 0.195118E+11 0.142155E+10 0.00 0.00 0.00 0.00 0.00
November 0.252903E+10 0.327790E+10 0.557451E+10 0.00 0.00 0.00 0.00 0.00
December 0.261333E+10 0.398719E+10 0.786357E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.307698E+11 0.131219E+12 0.460069E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.236042E+10 0.176477E+10 16924735.47 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.261333E+10 0.309007E+11 0.841655E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.429772E+11 0.635666E+11 0.143713E+11 0.00 0.00 0.00 0.00 0.00
February 0.387061E+11 0.367906E+11 0.456679E+10 0.00 0.00 0.00 0.00 0.00
March 0.427745E+11 0.406281E+11 0.115024E+11 0.00 0.00 0.00 0.00 0.00
April 0.416701E+11 0.939448E+11 0.753885E+09 0.00 0.00 0.00 0.00 0.00
May 0.431710E+11 0.101202E+12 0.142915E+10 0.00 0.00 0.00 0.00 0.00
June 0.421281E+11 0.181922E+12 0.509318E+09 0.00 0.00 0.00 0.00 0.00
July 0.438245E+11 0.352875E+12 0.199056E+09 0.00 0.00 0.00 0.00 0.00
August 0.440037E+11 0.395622E+12 25360506.08 0.00 0.00 0.00 0.00 0.00
September 0.422814E+11 0.241649E+12 75648215.63 0.00 0.00 0.00 0.00 0.00
October 0.439095E+11 0.264660E+12 0.213336E+09 0.00 0.00 0.00 0.00 0.00
November 0.417729E+11 0.669939E+11 0.299541E+10 0.00 0.00 0.00 0.00 0.00
December 0.430687E+11 0.726079E+11 0.102765E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.510288E+12 0.191246E+13 0.469181E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.387061E+11 0.367906E+11 25360506.08 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.440037E+11 0.395622E+12 0.143713E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.261333E+10 0.781976E+10 0.325784E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.236042E+10 0.630431E+10 0.176477E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.261333E+10 0.841655E+10 0.195362E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.252903E+10 0.400991E+10 0.490019E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.261333E+10 0.358791E+10 0.521145E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.252903E+10 0.637782E+09 0.118888E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.261333E+10 37024146.19 0.270220E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.261333E+10 16924735.47 0.309007E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.252903E+10 0.317077E+09 0.175428E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.261333E+10 0.142155E+10 0.195118E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.252903E+10 0.557451E+10 0.327790E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.261333E+10 0.786357E+10 0.398719E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.307698E+11 0.460069E+11 0.131219E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.236042E+10 16924735.47 0.176477E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.261333E+10 0.841655E+10 0.309007E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.429772E+11 0.143713E+11 0.635666E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.387061E+11 0.456679E+10 0.367906E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.427745E+11 0.115024E+11 0.406281E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.416701E+11 0.753885E+09 0.939448E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.431710E+11 0.142915E+10 0.101202E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.421281E+11 0.509318E+09 0.181922E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.438245E+11 0.199056E+09 0.352875E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.440037E+11 25360506.08 0.395622E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.422814E+11 75648215.63 0.241649E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.439095E+11 0.213336E+09 0.264660E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.417729E+11 0.299541E+10 0.669939E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.430687E+11 0.102765E+11 0.726079E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.510288E+12 0.469181E+11 0.191246E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.387061E+11 25360506.08 0.367906E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.440037E+11 0.143713E+11 0.395622E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.356278E+11 0.00 0.00 2088638.12 30016282.15 0.00 0.602556E+10 0.00 0.80
February 0.379577E+11 0.00 0.00 22037.90 8290170.77 0.00 0.154413E+09 0.00 0.83
March 0.424777E+11 0.00 0.00 0.00 500109.38 0.00 0.00 0.00 0.80
April 0.359697E+11 0.00 0.00 0.00 37047719.90 0.00 0.00 0.00 0.86
May 0.367120E+11 0.00 0.00 0.00 7220904.32 0.00 0.00 0.00 0.89
June 0.288663E+11 0.00 0.00 0.00 0.448134E+09 0.00 0.00 0.00 0.92
July 0.186270E+11 0.00 0.00 0.00 0.345256E+10 0.00 0.00 0.00 0.90
August 0.157864E+11 0.00 0.00 0.00 0.421197E+10 0.00 0.00 0.00 0.89
September 0.242391E+11 32786747.01 0.00 144402.89 0.131117E+10 0.00 0.979700E+09 0.00 0.94
October 0.203908E+11 82908031.91 0.00 3024181.14 0.208882E+10 0.00 0.549152E+10 0.00 0.89
November 0.289116E+11 0.00 0.00 5458334.26 13316717.58 0.00 0.104218E+11 0.00 0.85
December 0.340826E+11 0.00 0.00 2416454.29 8841242.19 0.00 0.662037E+10 0.00 0.80
                   
Annual Sum or Average 0.359649E+12 0.115695E+09 0.00 13154048.61 0.116179E+11 0.00 0.296934E+11 0.00 0.86
Minimum of Months 0.157864E+11 0.00 0.00 0.00 500109.38 0.00 0.00 0.00 0.80
Maximum of Months 0.424777E+11 82908031.91 0.00 5458334.26 0.421197E+10 0.00 0.104218E+11 0.00 0.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.305499E+10 5817009.60 0.00 2960795.25 103737.79 0.00 0.112133E+10 0.00 1.57
February 0.289381E+10 1543203.45 0.00 2028068.03 0.00 0.00 0.807369E+09 0.00 1.54
March 0.354859E+10 58378.80 0.00 1230460.25 0.00 0.00 0.432436E+09 0.00 1.39
April 0.285772E+10 3505589.38 0.00 1023132.89 198894.23 0.00 0.491808E+09 0.00 1.48
May 0.330425E+10 198035.52 0.00 179720.24 490694.45 0.00 99558692.42 0.00 1.51
June 0.254161E+10 20175521.51 0.00 79723.02 21374427.33 0.00 0.134728E+09 0.00 1.56
July 0.144771E+10 0.241242E+09 0.00 411522.05 83004461.97 0.00 0.279010E+09 0.00 1.52
August 0.925390E+09 0.371825E+09 0.00 1186620.08 61204974.35 0.00 0.539646E+09 0.00 1.54
September 0.148766E+10 0.143450E+09 0.00 2498877.42 34739487.46 0.00 0.899397E+09 0.00 1.73
October 0.142083E+10 0.306829E+09 0.00 3300477.07 24967577.69 0.00 0.108367E+10 0.00 1.76
November 0.261841E+10 2795022.45 0.00 3327801.59 0.00 0.00 0.130436E+10 0.00 1.67
December 0.281966E+10 1855350.37 0.00 3957535.12 0.00 0.00 0.126088E+10 0.00 1.64
                   
Annual Sum or Average 0.289206E+11 0.109929E+10 0.00 22184733.01 0.226084E+09 0.00 0.845419E+10 0.00 1.58
Minimum of Months 0.925390E+09 58378.80 0.00 79723.02 0.00 0.00 99558692.42 0.00 1.39
Maximum of Months 0.354859E+10 0.371825E+09 0.00 3957535.12 83004461.97 0.00 0.130436E+10 0.00 1.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.422530E+10 0.00 0.00 48221.81 3223688.25 0.00 0.248359E+09 0.00 1.35
February 0.383836E+10 0.00 0.00 62649.95 890347.64 0.00 0.254740E+09 0.00 1.39
March 0.439535E+10 0.00 0.00 40106.67 53710.74 0.00 0.166622E+09 0.00 1.34
April 0.341453E+10 0.00 0.00 147480.32 3978850.50 0.00 0.448393E+09 0.00 1.46
May 0.365494E+10 0.00 0.00 94149.21 775510.58 0.00 0.287761E+09 0.00 1.51
June 0.262304E+10 0.00 0.00 230514.81 48128675.18 0.00 0.476908E+09 0.00 1.56
July 0.137579E+10 9095890.11 0.00 637692.50 0.361703E+09 0.00 0.624125E+09 0.00 1.52
August 0.855579E+09 4835180.33 0.00 1017723.26 0.447522E+09 0.00 0.839234E+09 0.00 1.49
September 0.190024E+10 9543064.11 0.00 659403.90 0.134796E+09 0.00 0.808153E+09 0.00 1.58
October 0.183373E+10 19825647.62 0.00 798174.54 0.213414E+09 0.00 0.950517E+09 0.00 1.50
November 0.371064E+10 0.00 0.00 148491.93 1430188.65 0.00 0.514120E+09 0.00 1.43
December 0.400311E+10 0.00 0.00 116294.41 949531.61 0.00 0.368448E+09 0.00 1.35
                   
Annual Sum or Average 0.358306E+11 43299782.17 0.00 4000903.31 0.121686E+10 0.00 0.598738E+10 0.00 1.46
Minimum of Months 0.855579E+09 0.00 0.00 40106.67 53710.74 0.00 0.166622E+09 0.00 1.34
Maximum of Months 0.439535E+10 19825647.62 0.00 1017723.26 0.447522E+09 0.00 0.950517E+09 0.00 1.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 31570318.99 126962.91 0.00 622707.13 18789.22 0.00 0.328677E+09 0.00 0.05
February 32422100.85 34624.06 0.00 417558.29 0.00 0.00 0.250730E+09 0.00 0.04
March 40131657.81 0.00 0.00 368830.28 692.29 0.00 0.223567E+09 0.00 0.03
April 15352113.69 219900.21 0.00 1003963.22 14590.73 0.00 0.471484E+09 0.00 0.08
May 6713250.45 69746.87 0.00 1413436.80 0.00 0.00 0.623628E+09 0.00 0.10
June 0.00 8719003.01 0.00 2306558.97 0.00 0.00 0.809833E+09 0.00 0.18
July 0.00 94575029.22 0.00 2515591.04 0.00 0.00 0.672925E+09 0.00 0.23
August 0.00 0.105305E+09 0.00 2214947.01 0.00 0.00 0.574596E+09 0.00 0.23
September 0.00 33341024.11 0.00 2161872.04 0.00 0.00 0.734490E+09 0.00 0.20
October 0.00 75430247.19 0.00 2081306.47 0.00 0.00 0.778737E+09 0.00 0.21
November 14421325.54 190146.76 0.00 933733.26 18.50 0.00 0.519911E+09 0.00 0.08
December 27340804.52 102996.10 0.00 685922.48 1880.58 0.00 0.372991E+09 0.00 0.06
                   
Annual Sum or Average 0.167952E+09 0.318115E+09 0.00 16726426.98 35971.31 0.00 0.636157E+10 0.00 0.13
Minimum of Months 0.00 0.00 0.00 368830.28 0.00 0.00 0.223567E+09 0.00 0.03
Maximum of Months 40131657.81 0.105305E+09 0.00 2515591.04 18789.22 0.00 0.809833E+09 0.00 0.23



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.281765E+10 0.00 0.00 0.00 2030358.34 0.00 0.00 0.00 0.69
February 0.257798E+10 0.00 0.00 0.00 560762.90 0.00 0.00 0.00 0.72
March 0.287327E+10 0.00 0.00 0.00 33828.35 0.00 0.00 0.00 0.69
April 0.243306E+10 0.00 0.00 0.00 2505978.14 0.00 0.00 0.00 0.75
May 0.248327E+10 0.00 0.00 0.00 488435.68 0.00 0.00 0.00 0.77
June 0.195257E+10 0.00 0.00 0.00 30312626.21 0.00 0.00 0.00 0.80
July 0.125996E+10 0.00 0.00 0.00 0.233538E+09 0.00 0.00 0.00 0.78
August 0.106782E+10 0.00 0.00 0.00 0.284906E+09 0.00 0.00 0.00 0.77
September 0.170586E+10 0.00 0.00 0.00 90908005.63 0.00 0.00 0.00 0.81
October 0.175093E+10 0.00 0.00 0.00 0.146900E+09 0.00 0.00 0.00 0.77
November 0.266095E+10 0.00 0.00 0.00 900768.07 0.00 0.00 0.00 0.73
December 0.275339E+10 0.00 0.00 0.00 598038.42 0.00 0.00 0.00 0.69
                   
Annual Sum or Average 0.263367E+11 0.00 0.00 0.00 0.793683E+09 0.00 0.00 0.00 0.75
Minimum of Months 0.106782E+10 0.00 0.00 0.00 33828.35 0.00 0.00 0.00 0.69
Maximum of Months 0.287327E+10 0.00 0.00 0.00 0.284906E+09 0.00 0.00 0.00 0.81



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 33224568.96 0.00 0.112160E+09 0.00 0.00 0.578796E+11 0.00 17.18
February 0.00 8784810.67 0.00 98902125.00 0.00 0.00 0.530476E+11 0.00 17.78
March 0.00 506323.24 0.00 0.108537E+09 0.00 0.00 0.588437E+11 0.00 17.08
April 0.00 38803660.67 0.00 0.118409E+09 0.00 0.00 0.508416E+11 0.00 18.74
May 0.00 7542352.41 0.00 0.126872E+09 0.00 0.00 0.518067E+11 0.00 19.38
June 0.00 0.501187E+09 0.00 0.124330E+09 0.00 0.00 0.406865E+11 0.00 20.14
July 0.00 0.419904E+10 0.00 0.101996E+09 0.00 0.00 0.252763E+11 0.00 19.66
August 0.00 0.498674E+10 0.00 88647402.84 0.00 0.00 0.216202E+11 0.00 19.50
September 0.00 0.157059E+10 0.00 0.108436E+09 0.00 0.00 0.351514E+11 0.00 20.27
October 0.00 0.265951E+10 0.00 99898380.33 0.00 0.00 0.366245E+11 0.00 19.48
November 0.00 14472903.22 0.00 0.110369E+09 0.00 0.00 0.554539E+11 0.00 18.50
December 0.00 9926795.23 0.00 0.113323E+09 0.00 0.00 0.569666E+11 0.00 17.29
                   
Annual Sum or Average 0.00 0.140303E+11 0.00 0.131188E+10 0.00 0.00 0.544199E+12 0.00 18.75
Minimum of Months 0.00 506323.24 0.00 88647402.84 0.00 0.00 0.216202E+11 0.00 17.08
Maximum of Months 0.00 0.498674E+10 0.00 0.126872E+09 0.00 0.00 0.588437E+11 0.00 20.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.138813E+11 21399037.22 0.00 8101606.13 2651295.48 0.00 0.190662E+11 0.00 4.08
February 0.155729E+11 6542561.24 0.00 5028331.02 16187.40 0.00 0.145744E+11 0.00 4.22
March 0.218394E+11 0.00 0.00 2792281.44 395660.33 0.00 0.117639E+11 0.00 4.06
April 0.160681E+11 2830300.26 0.00 2891445.02 26479914.16 0.00 0.123863E+11 0.00 4.40
May 0.176400E+11 0.00 0.00 2254947.15 5712801.07 0.00 0.114024E+11 0.00 4.55
June 0.116962E+11 0.00 0.00 3277660.87 0.354540E+09 0.00 0.111380E+11 0.00 4.72
July 0.589386E+10 56667398.41 0.00 4379714.24 0.267482E+10 0.00 0.883845E+10 0.00 4.59
August 0.322584E+10 0.177370E+09 0.00 6038098.61 0.315492E+10 0.00 0.925748E+10 0.00 4.51
September 0.700740E+10 0.519127E+09 0.00 6433132.59 0.544144E+09 0.00 0.129381E+11 0.00 4.78
October 0.676972E+10 0.103714E+10 0.00 10149962.44 0.681288E+09 0.00 0.136993E+11 0.00 4.53
November 0.121376E+11 10737579.37 0.00 9241918.66 33306.56 0.00 0.189762E+11 0.00 4.33
December 0.136917E+11 6124757.54 0.00 11574069.63 869969.94 0.00 0.185014E+11 0.00 4.09
                   
Annual Sum or Average 0.145424E+12 0.183793E+10 0.00 72163167.78 0.744587E+10 0.00 0.162542E+12 0.00 4.40
Minimum of Months 0.322584E+10 0.00 0.00 2254947.15 16187.40 0.00 0.883845E+10 0.00 4.06
Maximum of Months 0.218394E+11 0.103714E+10 0.00 11574069.63 0.315492E+10 0.00 0.190662E+11 0.00 4.78



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.514980E+11 6202510.43 0.00 14438318.30 60387585.39 0.00 0.408990E+11 0.00 1.65
February 0.523792E+11 0.00 0.00 10939882.64 18391460.44 0.00 0.321602E+11 0.00 1.71
March 0.670605E+11 0.00 0.00 7456720.77 1109475.57 0.00 0.271673E+11 0.00 1.65
April 0.437550E+11 0.00 0.00 12234203.85 82189100.10 0.00 0.360303E+11 0.00 1.79
May 0.453135E+11 0.00 0.00 11470204.28 16019329.37 0.00 0.361194E+11 0.00 1.85
June 0.276528E+11 0.00 0.00 18400587.36 0.994170E+09 0.00 0.363676E+11 0.00 1.92
July 0.128776E+11 0.189554E+09 0.00 27851830.18 0.746984E+10 0.00 0.284198E+11 0.00 1.87
August 0.718294E+10 91270825.37 0.00 36204187.72 0.925284E+10 0.00 0.278119E+11 0.00 1.83
September 0.192193E+11 0.424941E+09 0.00 31050342.63 0.255659E+10 0.00 0.367322E+11 0.00 1.94
October 0.185544E+11 0.984295E+09 0.00 38284375.08 0.383477E+10 0.00 0.390312E+11 0.00 1.84
November 0.412257E+11 7121483.88 0.00 19973561.03 22421198.83 0.00 0.460283E+11 0.00 1.76
December 0.486038E+11 0.00 0.00 18486379.13 19613993.56 0.00 0.416955E+11 0.00 1.66
                   
Annual Sum or Average 0.435323E+12 0.170339E+10 0.00 0.246791E+09 0.243283E+11 0.00 0.428463E+12 0.00 1.79
Minimum of Months 0.718294E+10 0.00 0.00 7456720.77 1109475.57 0.00 0.271673E+11 0.00 1.65
Maximum of Months 0.670605E+11 0.984295E+09 0.00 38284375.08 0.925284E+10 0.00 0.460283E+11 0.00 1.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 9807465.35 2147698.73 0.00 6520094.60 688481.91 0.481165E+09 0.131030E+10 1734.20 0.34
February 28257498.67 1413432.33 0.00 5929977.96 0.00 0.289097E+09 0.123786E+10 0.00 0.34
March 41596808.95 2084753.89 0.00 6081585.68 0.00 0.535847E+09 0.121999E+10 0.00 0.34
April 15014832.48 4841079.93 0.00 10882511.41 0.00 52902740.64 0.116070E+10 0.00 0.34
May 25683764.47 1803082.13 0.00 11216133.85 135136.26 42599292.85 0.117606E+10 0.00 0.34
June 9832080.05 32304770.81 0.00 12223353.97 202723.50 1806356.29 0.705308E+09 0.00 0.34
July 0.00 0.220613E+09 0.00 10942749.87 0.00 707135.17 0.319654E+09 0.00 0.34
August 0.00 0.289791E+09 4005.27 8516525.03 0.00 608949.98 0.238978E+09 1919.11 0.34
September 1651345.54 84526546.63 11780.19 10574914.26 3943928.34 1684469.80 0.541380E+09 706.78 0.34
October 4649501.20 0.172306E+09 73017.74 8844220.35 144698.41 2006980.69 0.841619E+09 7720.79 0.34
November 10482856.60 1939550.48 0.00 7920481.88 279771.20 92319147.92 0.141993E+10 0.00 0.34
December 11196668.38 3919910.75 6244.66 7178726.59 0.00 0.324980E+09 0.143084E+10 1164.27 0.34
                   
Annual Sum or Average 0.158173E+09 0.817691E+09 95047.86 0.106831E+09 5394739.63 0.182572E+10 0.116026E+11 13245.15 0.34
Minimum of Months 0.00 1413432.33 0.00 5929977.96 0.00 608949.98 0.238978E+09 0.00 0.34
Maximum of Months 41596808.95 0.289791E+09 73017.74 12223353.97 3943928.34 0.535847E+09 0.143084E+10 7720.79 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.121750E+09 759338.71 14474.56 2119531.99 2061094.06 0.943364E+09 0.740351E+09 2675.01 0.34
February 0.108277E+09 329683.97 0.00 2632054.46 1082999.72 0.535156E+09 0.914900E+09 583.04 0.34
March 0.103592E+09 198294.08 0.00 3136110.70 1886215.55 0.720044E+09 0.976531E+09 0.00 0.34
April 0.156962E+09 2910415.57 0.00 6287463.69 1930097.16 60806410.39 0.101530E+10 0.00 0.34
May 0.223392E+09 1653877.11 0.00 7695170.47 284114.20 38382899.83 0.985945E+09 0.00 0.34
June 0.293388E+09 26315650.74 30763.97 7331535.22 6152619.86 1104276.83 0.427260E+09 4651.02 0.34
July 0.210106E+09 0.185420E+09 29854.40 6237004.69 35133843.55 266331.29 0.114656E+09 4032.41 0.34
August 0.167081E+09 0.242732E+09 137038.15 4220341.18 46882737.29 256614.15 76516985.71 10901.86 0.35
September 0.228220E+09 72299605.10 156667.02 5212488.50 16010722.97 1389504.73 0.320404E+09 5599.78 0.35
October 0.233348E+09 0.140951E+09 195889.82 3580226.03 31345102.49 1953486.82 0.618138E+09 18642.29 0.34
November 0.159999E+09 1714466.09 5569.88 2669700.90 495956.42 0.340156E+09 0.102765E+10 3069.25 0.34
December 0.136571E+09 2709403.10 36607.16 2011936.89 1173171.00 0.840515E+09 0.794885E+09 7678.28 0.34
                   
Annual Sum or Average 0.214269E+10 0.677994E+09 606864.96 53133564.72 0.144439E+09 0.348339E+10 0.801254E+10 57832.94 0.34
Minimum of Months 0.103592E+09 198294.08 0.00 2011936.89 284114.20 256614.15 76516985.71 0.00 0.34
Maximum of Months 0.293388E+09 0.242732E+09 195889.82 7695170.47 46882737.29 0.943364E+09 0.102765E+10 18642.29 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 97880836.73 1623314.05 0.00 4149971.46 0.00 0.00 0.989079E+09 0.00 0.02
February 0.397627E+09 0.00 0.00 2479149.62 0.00 0.00 0.733668E+09 0.00 0.02
March 0.582855E+09 7947255.03 0.00 1764484.51 0.00 0.00 0.608626E+09 0.00 0.02
April 0.172518E+09 375458.21 0.00 1840360.68 0.00 0.00 0.620795E+09 0.00 0.02
May 0.746774E+09 0.00 0.00 352004.53 0.00 0.00 0.214571E+09 0.00 0.02
June 0.438285E+09 11597194.99 0.00 162787.66 9256645.81 0.00 0.118555E+09 0.00 0.02
July 81129455.61 0.342095E+09 0.00 118768.67 14669973.21 0.00 56171649.06 0.00 0.02
August 0.00 0.540227E+09 0.00 221794.76 0.00 0.00 22328995.37 0.00 0.02
September 0.00 0.192775E+09 0.00 1444474.76 0.00 0.00 0.148211E+09 0.00 0.02
October 44841444.89 0.205095E+09 0.00 2499198.50 2008878.01 0.00 0.313501E+09 0.00 0.02
November 34190782.87 0.00 0.00 3828946.96 0.00 0.00 0.949111E+09 0.00 0.02
December 89725476.48 0.00 0.00 4423024.61 0.00 0.00 0.104920E+10 0.00 0.02
                   
Annual Sum or Average 0.268583E+10 0.130173E+10 0.00 23284966.72 25935497.02 0.00 0.582382E+10 0.00 0.02
Minimum of Months 0.00 0.00 0.00 118768.67 0.00 0.00 22328995.37 0.00 0.02
Maximum of Months 0.746774E+09 0.540227E+09 0.00 4423024.61 14669973.21 0.00 0.104920E+10 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.165365E+10 8166988.28 273547.27 45237004.55 30041849.18 0.178721E+09 0.226412E+11 7717.44 0.39
February 0.145865E+10 4471965.22 6739.18 49419002.37 14690241.53 0.133159E+09 0.195323E+11 1169.35 0.39
March 0.141836E+10 2689740.20 0.00 57496201.52 25585382.37 0.118918E+09 0.228660E+11 0.00 0.39
April 0.215524E+10 23990248.47 116572.87 76952385.19 41540011.28 22147877.92 0.145568E+11 11818.66 0.39
May 0.310824E+10 4026941.20 0.00 96261394.54 22260748.23 11854517.58 0.138126E+11 0.00 0.39
June 0.406089E+10 0.237572E+09 98828.00 94864748.84 0.203217E+09 4390420.23 0.572945E+10 5763.65 0.39
July 0.286814E+10 0.205390E+10 43804.39 77112705.42 0.938197E+09 187477.08 0.154797E+10 91.08 0.39
August 0.226635E+10 0.267098E+10 285778.79 52178911.65 0.125918E+10 728427.05 0.104573E+10 2882.88 0.39
September 0.313753E+10 0.765427E+09 1193110.99 60500746.38 0.433443E+09 7146030.40 0.432612E+10 14220.94 0.39
October 0.318120E+10 0.159849E+10 1301760.94 49811245.34 0.740186E+09 10379959.23 0.838356E+10 32618.86 0.39
November 0.218312E+10 14239270.67 0.00 51124217.91 15860969.39 86852051.81 0.184389E+11 0.00 0.39
December 0.184605E+10 35241467.49 425129.67 43799090.39 17534437.03 0.144986E+09 0.220282E+11 64459.74 0.39
                   
Annual Sum or Average 0.293374E+11 0.741919E+10 3745272.09 0.754758E+09 0.374174E+10 0.719471E+09 0.154909E+12 140742.60 0.39
Minimum of Months 0.141836E+10 2689740.20 0.00 43799090.39 14690241.53 187477.08 0.104573E+10 0.00 0.39
Maximum of Months 0.406089E+10 0.267098E+10 1301760.94 96261394.54 0.125918E+10 0.178721E+09 0.228660E+11 64459.74 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 11936583.26 2147698.73 0.00 7591294.01 688481.91 0.488581E+09 0.129969E+10 1734.20 0.34
February 31228969.68 1413432.33 0.00 5897293.32 0.00 0.354942E+09 0.116908E+10 0.00 0.34
March 42173557.78 2084753.89 0.00 6260072.62 0.00 0.572196E+09 0.118289E+10 0.00 0.34
April 10463462.59 4841079.93 0.00 10176069.26 0.00 51751209.99 0.116711E+10 0.00 0.34
May 21755595.06 1938218.39 0.00 10381301.24 0.00 72895334.23 0.115053E+10 0.00 0.34
June 8960360.08 32507494.31 0.00 10903910.26 0.00 1734382.03 0.707571E+09 0.00 0.34
July 0.00 0.220613E+09 0.00 10302443.10 0.00 186404.28 0.320815E+09 0.00 0.34
August 0.00 0.289797E+09 0.00 8424727.78 0.00 74664.93 0.239604E+09 0.00 0.34
September 1651345.54 84037567.09 14264.02 9531620.83 4430882.85 1468628.88 0.542639E+09 247.99 0.34
October 5024769.91 0.170855E+09 18472.45 9100641.33 1658086.47 1607873.11 0.841386E+09 52.52 0.34
November 11262510.58 1839686.36 0.00 8148462.56 379635.31 0.147695E+09 0.136355E+10 0.00 0.34
December 14245026.58 3919910.75 4073.90 7892170.91 0.00 0.387875E+09 0.136418E+10 3335.03 0.34
                   
Annual Sum or Average 0.158702E+09 0.815994E+09 36810.37 0.104610E+09 7157086.54 0.208101E+10 0.113490E+11 5369.74 0.34
Minimum of Months 0.00 1413432.33 0.00 5897293.32 0.00 74664.93 0.239604E+09 0.00 0.34
Maximum of Months 42173557.78 0.289797E+09 18472.45 10903910.26 4430882.85 0.572196E+09 0.136418E+10 3335.03 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.122926E+09 612113.00 16857.03 2802886.74 2208319.76 0.860826E+09 0.821030E+09 292.55 0.34
February 0.108181E+09 412911.50 0.00 2756517.65 1000355.22 0.657358E+09 0.792669E+09 0.00 0.34
March 0.103576E+09 527804.24 0.00 3484473.76 1556705.38 0.744435E+09 0.951808E+09 0.00 0.34
April 0.152987E+09 4535468.47 0.00 6504839.31 305044.26 76832646.39 0.100303E+10 0.00 0.34
May 0.219222E+09 1937356.23 0.00 7714469.82 635.08 67084393.95 0.961395E+09 0.00 0.34
June 0.292645E+09 26501927.22 0.00 6352633.98 6001758.36 1194777.84 0.428891E+09 0.00 0.34
July 0.208631E+09 0.187465E+09 0.00 5331047.02 33122805.65 254107.80 0.117049E+09 0.00 0.34
August 0.166836E+09 0.246296E+09 0.00 3654643.66 43467068.05 302058.15 77282138.57 0.00 0.35
September 0.228659E+09 71619325.81 136688.86 4633183.78 16714424.40 1341501.55 0.320591E+09 2155.80 0.35
October 0.232902E+09 0.141395E+09 140529.72 4082696.41 30971928.84 2974398.34 0.617060E+09 3394.69 0.34
November 0.162357E+09 1523048.16 0.00 3244771.38 696013.49 0.449932E+09 0.914943E+09 0.00 0.34
December 0.136712E+09 2693223.15 8212.77 2489426.60 1222529.86 0.849424E+09 0.785357E+09 2893.76 0.34
                   
Annual Sum or Average 0.213563E+10 0.685518E+09 302288.38 53051590.11 0.137268E+09 0.371196E+10 0.779111E+10 8736.80 0.34
Minimum of Months 0.103576E+09 412911.50 0.00 2489426.60 635.08 254107.80 77282138.57 0.00 0.34
Maximum of Months 0.292645E+09 0.246296E+09 140529.72 7714469.82 43467068.05 0.860826E+09 0.100303E+10 3394.69 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.231497E+11 0.00 0.00 0.00 16681344.73 0.00 0.00 0.00 0.45
February 0.211805E+11 0.00 0.00 0.00 4607206.04 0.00 0.00 0.00 0.47
March 0.236067E+11 0.00 0.00 0.00 277932.39 0.00 0.00 0.00 0.45
April 0.199899E+11 0.00 0.00 0.00 20589018.45 0.00 0.00 0.00 0.49
May 0.204025E+11 0.00 0.00 0.00 4012968.48 0.00 0.00 0.00 0.50
June 0.160422E+11 0.00 0.00 0.00 0.249047E+09 0.00 0.00 0.00 0.52
July 0.103518E+11 0.00 0.00 0.00 0.191874E+10 0.00 0.00 0.00 0.51
August 0.877317E+10 0.00 0.00 0.00 0.234077E+10 0.00 0.00 0.00 0.50
September 0.140153E+11 0.00 0.00 0.00 0.746897E+09 0.00 0.00 0.00 0.53
October 0.143856E+11 0.00 0.00 0.00 0.120692E+10 0.00 0.00 0.00 0.50
November 0.218623E+11 0.00 0.00 0.00 7400675.26 0.00 0.00 0.00 0.48
December 0.226217E+11 0.00 0.00 0.00 4913460.24 0.00 0.00 0.00 0.45
                   
Annual Sum or Average 0.216381E+12 0.00 0.00 0.00 0.652086E+10 0.00 0.00 0.00 0.49
Minimum of Months 0.877317E+10 0.00 0.00 0.00 277932.39 0.00 0.00 0.00 0.45
Maximum of Months 0.236067E+11 0.00 0.00 0.00 0.234077E+10 0.00 0.00 0.00 0.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2799206.43 536924.68 0.00 1330007.33 172120.48 0.228574E+09 0.219246E+09 433.55 0.34
February 7766317.09 353358.08 0.00 1245275.37 0.00 0.172242E+09 0.209034E+09 0.00 0.34
March 9793388.80 521188.47 0.00 1379024.43 0.00 0.216532E+09 0.223174E+09 0.00 0.34
April 2980997.86 1210269.98 0.00 2645716.86 0.00 46366710.38 0.257882E+09 0.00 0.34
May 5074821.47 484554.60 0.00 2736508.45 0.00 37043724.79 0.269036E+09 0.00 0.34
June 2112510.58 8125631.34 0.00 3025892.87 1242.23 2140773.53 0.175013E+09 0.00 0.34
July 0.00 55153322.98 0.00 2725951.41 0.00 164887.68 79935105.43 0.00 0.34
August 0.00 72447660.67 1176.03 2057211.06 0.00 155868.73 59812887.59 305.07 0.34
September 412836.39 21434578.25 2654.77 2479305.01 682902.57 395889.79 0.135535E+09 604.90 0.34
October 1358097.74 43112615.59 17656.14 1930331.54 0.00 21579316.79 0.189412E+09 2528.49 0.34
November 3075476.78 484887.62 0.00 1624593.61 69942.80 0.122444E+09 0.255520E+09 0.00 0.34
December 3777648.62 979977.69 1575.32 1446498.21 0.00 0.214762E+09 0.223562E+09 276.92 0.34
                   
Annual Sum or Average 39151301.74 0.204845E+09 23062.26 24626316.14 926208.08 0.106240E+10 0.229716E+10 4148.92 0.34
Minimum of Months 0.00 353358.08 0.00 1245275.37 0.00 155868.73 59812887.59 0.00 0.34
Maximum of Months 9793388.80 72447660.67 17656.14 3025892.87 682902.57 0.228574E+09 0.269036E+09 2528.49 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 30430130.41 189834.68 3807.69 345735.74 515273.51 0.336210E+09 84910387.63 479.70 0.34
February 26883801.05 82420.99 29.56 489381.07 270749.93 0.250901E+09 0.111967E+09 116.20 0.34
March 25960326.75 49573.52 0.00 657286.71 471553.89 0.264905E+09 0.159304E+09 0.00 0.34
April 38500595.61 1008996.40 2356.74 1532397.49 198765.45 46422639.54 0.223383E+09 9.60 0.34
May 53844364.74 484339.06 0.00 1968972.31 158.77 28227866.21 0.229813E+09 0.00 0.34
June 72958284.68 6611392.98 7030.62 1953526.14 1507018.23 249149.24 0.107110E+09 479.57 0.34
July 52526385.90 46343361.92 18817.76 1692281.74 8783460.89 14779.11 28582793.50 1220.39 0.35
August 41770214.87 60706940.35 35271.45 1096980.90 11696944.80 73459.25 19078045.11 1496.68 0.35
September 56716411.54 18720528.96 39393.22 1231346.61 3357053.06 368077.06 80490489.58 1173.48 0.35
October 58330267.26 35443061.58 28271.86 691886.75 7652488.20 30475272.33 0.124757E+09 3924.94 0.34
November 40086871.75 428616.52 1796.44 399915.01 123989.11 0.203471E+09 0.138661E+09 363.34 0.34
December 34048144.97 689307.60 4306.74 294953.52 287224.47 0.316109E+09 93043947.30 876.08 0.34
                   
Annual Sum or Average 0.532056E+09 0.170758E+09 141082.08 12354663.97 34864680.30 0.147743E+10 0.140110E+10 10139.99 0.34
Minimum of Months 25960326.75 49573.52 0.00 294953.52 158.77 14779.11 19078045.11 0.00 0.34
Maximum of Months 72958284.68 60706940.35 39393.22 1968972.31 11696944.80 0.336210E+09 0.229813E+09 3924.94 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 8333205.17 4523256.67 0.00 18518277.16 31996.41 0.177019E+09 0.269967E+10 2785.34 0.39
February 33143794.18 2270145.23 0.00 13233105.44 0.00 0.155908E+09 0.230511E+10 0.00 0.39
March 48038980.09 3348369.78 0.00 11815427.10 0.00 0.536036E+09 0.230078E+10 0.00 0.39
April 11994895.70 7775366.60 0.00 14293285.20 0.00 72205522.26 0.189230E+10 0.00 0.39
May 30166599.66 3113015.85 0.00 11616992.72 0.00 0.111846E+09 0.186296E+10 0.00 0.39
June 14969099.43 52002970.88 0.00 12022774.59 208041.81 4072255.43 0.114007E+10 0.00 0.39
July 0.00 0.354317E+09 14532.76 11414424.65 0.00 1892733.26 0.518807E+09 299.71 0.39
August 0.00 0.465403E+09 43878.36 10253754.04 0.00 1384781.36 0.386847E+09 1460.98 0.39
September 2652262.96 0.136563E+09 11679.36 14352817.70 5539142.16 2796611.32 0.872063E+09 221.12 0.39
October 3104065.26 0.276854E+09 19467.52 15253488.67 232403.36 4953112.57 0.135333E+10 137.20 0.39
November 2122259.29 3564502.11 0.00 18403741.55 0.00 2893458.43 0.243500E+10 0.00 0.39
December 9308142.23 6307755.86 0.00 19578044.52 0.00 81351907.45 0.273933E+10 0.00 0.39
                   
Annual Sum or Average 0.163833E+09 0.131604E+10 89558.00 0.170756E+09 6011583.74 0.115236E+10 0.205063E+11 4904.36 0.39
Minimum of Months 0.00 2270145.23 0.00 10253754.04 0.00 1384781.36 0.386847E+09 0.00 0.39
Maximum of Months 48038980.09 0.465403E+09 43878.36 19578044.52 5539142.16 0.536036E+09 0.273933E+10 2785.34 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.163216E+11 10913744.50 0.00 21860346.00 30836859.81 0.00 0.415963E+11 0.00 5.31
February 0.150094E+11 0.00 0.00 20813590.89 11531062.96 0.00 0.379811E+11 0.00 5.49
March 0.158810E+11 0.00 0.00 23363916.29 695618.09 0.00 0.431792E+11 0.00 5.30
April 0.102796E+11 6618758.02 0.00 26516667.39 44912097.35 0.00 0.397274E+11 0.00 5.75
May 0.969388E+10 2551157.70 0.00 29893893.37 7492628.45 0.00 0.413549E+11 0.00 5.94
June 0.511083E+10 0.293297E+09 0.00 35552135.39 0.330026E+09 0.00 0.350683E+11 0.00 6.17
July 0.164211E+10 0.289003E+10 0.00 37943398.97 0.191226E+10 0.00 0.243005E+11 0.00 6.01
August 0.122370E+10 0.302685E+10 0.00 36255524.20 0.283171E+10 0.00 0.207583E+11 0.00 5.90
September 0.460174E+10 0.933555E+09 0.00 31956070.39 0.937412E+09 0.00 0.304609E+11 0.00 6.23
October 0.458437E+10 0.163187E+10 0.00 30992234.35 0.138965E+10 0.00 0.314124E+11 0.00 5.90
November 0.140516E+11 3409490.54 0.00 23480809.40 15113156.72 0.00 0.406426E+11 0.00 5.63
December 0.151028E+11 0.00 0.00 22366904.71 12297565.79 0.00 0.414932E+11 0.00 5.32
                   
Annual Sum or Average 0.113503E+12 0.879909E+10 0.00 0.340995E+09 0.752394E+10 0.00 0.427975E+12 0.00 5.75
Minimum of Months 0.122370E+10 0.00 0.00 20813590.89 695618.09 0.00 0.207583E+11 0.00 5.30
Maximum of Months 0.163216E+11 0.302685E+10 0.00 37943398.97 0.283171E+10 0.00 0.431792E+11 0.00 6.23



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.121495E+11 19135938.85 0.00 29448792.23 22617293.96 0.00 0.458036E+11 0.00 5.32
February 0.111623E+11 0.00 0.00 27932031.26 11531788.92 0.00 0.418539E+11 0.00 5.50
March 0.120926E+11 0.00 0.00 31592312.97 695661.89 0.00 0.470053E+11 0.00 5.31
April 0.591599E+10 35493005.90 0.00 34923059.25 16041093.70 0.00 0.442250E+11 0.00 5.76
May 0.512178E+10 3406389.86 0.00 39508040.73 6638028.61 0.00 0.461228E+11 0.00 5.97
June 0.264577E+10 0.456060E+09 0.00 45847297.20 0.167303E+09 0.00 0.377870E+11 0.00 6.20
July 0.112945E+10 0.362686E+10 0.00 46982525.31 0.117572E+10 0.00 0.249758E+11 0.00 6.04
August 0.739987E+09 0.415668E+10 0.00 43548034.57 0.170226E+10 0.00 0.214186E+11 0.00 5.93
September 0.259314E+10 0.141035E+10 0.00 39616457.40 0.465579E+09 0.00 0.326372E+11 0.00 6.26
October 0.263708E+10 0.227040E+10 0.00 38130292.41 0.752368E+09 0.00 0.335233E+11 0.00 5.93
November 0.102020E+11 12718627.55 0.00 30640910.59 5805185.84 0.00 0.445308E+11 0.00 5.64
December 0.112435E+11 2806495.32 0.00 29697808.12 9491844.69 0.00 0.453854E+11 0.00 5.33
                   
Annual Sum or Average 0.776332E+11 0.119939E+11 0.00 0.437868E+09 0.433605E+10 0.00 0.465269E+12 0.00 5.77
Minimum of Months 0.739987E+09 0.00 0.00 27932031.26 695661.89 0.00 0.214186E+11 0.00 5.31
Maximum of Months 0.121495E+11 0.415668E+10 0.00 46982525.31 0.170226E+10 0.00 0.470053E+11 0.00 6.26



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 50119946.84 0.00 0.116508E+09 0.00 0.00 0.545256E+11 0.00 17.53
February 0.00 13879588.66 0.00 0.103181E+09 0.00 0.00 0.509191E+11 0.00 18.18
March 0.00 837964.77 0.00 0.113289E+09 0.00 0.00 0.563094E+11 0.00 17.60
April 0.00 62034186.37 0.00 0.124644E+09 0.00 0.00 0.475653E+11 0.00 19.22
May 0.00 12064063.16 0.00 0.131884E+09 0.00 0.00 0.485472E+11 0.00 19.91
June 0.00 0.749868E+09 0.00 0.126528E+09 0.00 0.00 0.373216E+11 0.00 20.38
July 0.00 0.577876E+10 0.00 0.100074E+09 0.00 0.00 0.227981E+11 0.00 19.69
August 0.00 0.705020E+10 0.00 80441428.92 0.00 0.00 0.189146E+11 0.00 19.29
September 0.00 0.221724E+10 0.00 0.109934E+09 0.00 0.00 0.322656E+11 0.00 20.55
October 0.00 0.357772E+10 0.00 99308848.84 0.00 0.00 0.328849E+11 0.00 19.40
November 0.00 22080266.54 0.00 0.115246E+09 0.00 0.00 0.521823E+11 0.00 18.75
December 0.00 14672236.85 0.00 0.118525E+09 0.00 0.00 0.534265E+11 0.00 17.65
                   
Annual Sum or Average 0.00 0.195495E+11 0.00 0.133956E+10 0.00 0.00 0.507660E+12 0.00 19.01
Minimum of Months 0.00 837964.77 0.00 80441428.92 0.00 0.00 0.189146E+11 0.00 17.53
Maximum of Months 0.00 0.705020E+10 0.00 0.131884E+09 0.00 0.00 0.563094E+11 0.00 20.55



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.602267E+10 1769404.45 0.00 179213.38 2644116.25 0.00 94230620.12 0.00 0.45
February 0.556080E+10 0.00 0.00 31326.81 1217030.38 0.00 34182883.40 0.00 0.47
March 0.619051E+10 0.00 0.00 144150.83 73418.07 0.00 45241596.84 0.00 0.45
April 0.484213E+10 3670297.73 0.00 1028170.80 2036938.32 0.00 0.448105E+09 0.00 0.49
May 0.502274E+10 422705.22 0.00 1061445.52 776938.01 0.00 0.378365E+09 0.00 0.51
June 0.287393E+10 85136024.83 0.00 3990862.15 559144.50 0.00 0.141017E+10 0.00 0.55
July 0.795993E+09 0.688381E+09 0.00 7021153.67 5688202.35 0.00 0.202838E+10 0.00 0.57
August 0.613107E+09 0.861056E+09 0.00 5434364.65 10045678.31 0.00 0.177345E+10 0.00 0.57
September 0.224816E+10 0.236051E+09 0.00 4279364.73 44132701.41 0.00 0.152141E+10 0.00 0.57
October 0.265832E+10 0.475170E+09 0.00 3440992.60 5192048.08 0.00 0.122280E+10 0.00 0.55
November 0.567215E+10 2276035.94 0.00 186559.69 6180.31 0.00 0.102820E+09 0.00 0.48
December 0.591982E+10 873680.50 0.00 158983.93 544662.77 0.00 56676580.84 0.00 0.45
                   
Annual Sum or Average 0.484203E+11 0.235481E+10 0.00 26956588.76 72917058.77 0.00 0.911583E+10 0.00 0.51
Minimum of Months 0.613107E+09 0.00 0.00 31326.81 6180.31 0.00 34182883.40 0.00 0.45
Maximum of Months 0.619051E+10 0.861056E+09 0.00 7021153.67 44132701.41 0.00 0.202838E+10 0.00 0.57



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:21:30

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.158873E+12 0.450130E+10 0.119958E+12 0.431383E+12 0.179911E+12
February 0.207668E+12 0.395454E+10 0.110631E+12 0.395142E+12 0.121333E+12
March 0.296729E+12 0.452224E+10 0.127075E+12 0.439375E+12 0.129859E+12
April 0.386073E+12 0.360489E+10 0.952997E+11 0.370868E+12 0.211674E+12
May 0.414468E+12 0.383296E+10 0.959986E+11 0.380030E+12 0.214536E+12
June 0.409153E+12 0.282270E+10 0.675920E+11 0.288779E+12 0.335792E+12
July 0.433555E+12 0.109233E+10 0.263810E+11 0.146843E+12 0.596743E+12
August 0.393659E+12 0.664365E+09 0.155702E+11 0.108631E+12 0.662976E+12
September 0.309352E+12 0.218697E+10 0.528297E+11 0.238297E+12 0.441037E+12
October 0.210225E+12 0.236996E+10 0.513833E+11 0.243121E+12 0.481230E+12
November 0.175146E+12 0.404821E+10 0.105617E+12 0.408275E+12 0.183747E+12
December 0.138983E+12 0.450252E+10 0.116733E+12 0.422965E+12 0.195860E+12
           
Annual Sum or Average 0.353389E+13 0.381030E+11 0.985069E+12 0.387371E+13 0.375470E+13
Minimum of Months 0.138983E+12 0.664365E+09 0.155702E+11 0.108631E+12 0.121333E+12
Maximum of Months 0.433555E+12 0.452224E+10 0.127075E+12 0.439375E+12 0.662976E+12