Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2024-07-03 12:21:54
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11029.04 | 972.12 | 972.12 |
Net Site Energy | 11029.04 | 972.12 | 972.12 |
Total Source Energy | 21650.16 | 1908.30 | 1908.30 |
Net Source Energy | 21650.16 | 1908.30 | 1908.30 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1684.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 549.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 544.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 567.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 79.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 117.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.78 | 2901.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4654.20 | 6374.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1684.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 549.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 544.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 567.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 79.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 117.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.78 | 2901.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1684.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 549.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 544.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 567.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 79.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 117.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.78 | 2901.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 113.90 | 404.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 231.25 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 410.23 | 561.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 113.90 | 404.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 231.25 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 410.23 | 561.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4654.196 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4654.196 | 100.00 |
Total On-Site and Utility Electric Sources | 4654.196 | 100.00 |
Total Electricity End Uses | 4654.196 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 140.33 | 6.07 |
Air to Air Heat Recovery for Heating | 2171.63 | 93.93 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2311.96 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 227.67 |
Time Setpoint Not Met During Occupied Cooling | 51.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8047.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.7179 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.2862 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8577 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8577 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.7179 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.2862 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8577 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8577 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.7137 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUL-18:10 | 02-FEB-19:19 | - | - | - | - | - | - | - | - | - | - | 05-JAN-21:49 |
Heating | 0.00 | 615142.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 168612.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 36782.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 77265.07 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 28142.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27203.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4108.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4751.04 | 256970.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1691.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 356821.93 | 959733.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 615142.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 168612.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 36782.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 47590.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1023.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 26968.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 27203.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4108.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4751.04 | 256970.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 792.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 670.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1825.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1741.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1725.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 613.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.66 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2576.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1798.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 251.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 372.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.17 | 3145.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 139.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 14739.84 | 6910.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 160.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 153.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 152.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 158.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 32.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 277.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1299.20 | 609.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 160.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 153.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 152.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 158.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 32.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 277.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1299.20 | 609.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.26 | 0.666266 | 0.566000 | 1.28 | 1.00 | 0.500000 | 0.000572 | 0.000070 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.379708 | 0.134599 | 0.313000 | 0.118849 | 0.372855 | 0.500000 | 0.002831 | 0.000038 | 0.160474 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.225167 | 0.262843 | 0.611000 | 0.137577 | 0.700915 | 0.500000 | 0.001450 | 0.000016 | 0.137577 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.181298 | 0.690317 | 0.010000 | 0.001813 | 1.00 | 0.500000 | 0.000552 | 0.000022 | 0.091196 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.100399 | 0.719197 | 0.863000 | 0.086644 | 1.00 | 0.500000 | 0.000530 | 0.000017 | 0.086644 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.41 | 0.017446 | 0.010000 | 0.034086 | 0.300000 | 0.500000 | 0.021839 | 0.000029 | 0.120817 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.61 | 0.089330 | 0.630000 | 1.01 | 0.630000 | 0.500000 | 0.004265 | 0.000125 | 1.01 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.92 | 0.202745 | 0.578000 | 2.84 | 0.578000 | 0.500000 | 0.001879 | 0.000306 | 2.84 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.28 | 0.928974 | 0.557000 | 0.711652 | 1.00 | 0.500000 | 0.000410 | 0.000140 | 0.711652 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.20 | 0.114841 | 0.810000 | 1.78 | 0.810000 | 0.500000 | 0.003318 | 0.000150 | 1.78 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.31 | 0.109329 | 0.771000 | 1.78 | 0.771000 | 0.500000 | 0.003485 | 0.000151 | 1.78 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.29 | 0.061883 | 0.241000 | 0.551389 | 0.300000 | 0.500000 | 0.011074 | 0.000059 | 0.551389 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.708433 | 0.443287 | 0.266000 | 0.188443 | 1.00 | 0.500000 | 0.000859 | 0.000092 | 0.384412 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8035.33 | 0.000070 | 169.73 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4378.79 | 0.000038 | 119.51 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1844.39 | 0.000016 | 42.12 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2488.31 | 0.000022 | 67.91 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1916.45 | 0.000017 | 48.72 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 3296.51 | 0.000029 | 89.97 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 14252.81 | 0.000125 | 327.92 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 35006.78 | 0.000306 | 789.63 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 7886.07 | 0.000069 | 225.33 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 7905.02 | 0.000069 | 225.87 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 44806.21 | 0.000392 | 1280.24 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 45164.49 | 0.000395 | 1290.47 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 7847.69 | 0.000069 | 224.23 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 7866.64 | 0.000069 | 224.77 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15955.73 | 0.000140 | 407.22 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2430.26 | 0.000021 | 69.44 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2437.30 | 0.000021 | 69.64 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 11599.97 | 0.000101 | 331.43 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 17124.58 | 0.000150 | 374.83 |
DINING_FLR_6 VAV BOX REHEAT COIL | 17294.41 | 0.000151 | 378.95 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6703.99 | 0.000059 | 150.95 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10489.72 | 0.000092 | 286.29 |
FLR_3_DOAS HEATING COIL | 30469.72 | 0.000267 | 443.51 |
VAV WITH REHEAT HEATING COIL | 323075.27 | 0.002826 | 4702.56 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.13 | 0.000069 | 0.000350 |
ROOM_2_FLR_3 FAN COIL | 1.10 | 0.000069 | 0.000339 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.52 | 0.000392 | 0.001977 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.51 | 0.000395 | 0.001796 |
ROOM_5_FLR_3 FAN COIL | 1.03 | 0.000069 | 0.000319 |
ROOM_6_FLR_3 FAN COIL | 0.996818 | 0.000069 | 0.000310 |
ROOM_1_FLR_6 FAN COIL | 0.295343 | 0.000021 | 0.000091 |
ROOM_2_FLR_6 FAN COIL | 0.285267 | 0.000021 | 0.000088 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.36 | 0.000101 | 0.000426 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 1.13 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 1.10 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 6.52 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 5.51 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 1.03 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 0.996818 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.295343 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.285267 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.36 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008626 | 12.80 | 0.008500 | 0.000350 | 1.13 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008630 | 12.80 | 0.008500 | 0.000339 | 1.10 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008553 | 12.80 | 0.008500 | 0.001977 | 6.52 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008829 | 12.80 | 0.008500 | 0.001796 | 5.51 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008639 | 12.80 | 0.008500 | 0.000319 | 1.03 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008644 | 12.80 | 0.008500 | 0.000310 | 0.996818 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008621 | 12.80 | 0.008500 | 0.000091 | 0.295343 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008625 | 12.80 | 0.008500 | 0.000088 | 0.285267 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008684 | 12.80 | 0.008500 | 0.000426 | 1.36 | |
FLR_3_DOAS COOLING COIL | 31.20 | 6.70 | 0.015365 | 11.90 | 0.008500 | 0.002511 | 2.05 | 87803.64 |
VAV WITH REHEAT COOLING COIL | 27.08 | 6.70 | 0.012146 | 10.90 | 0.008500 | 0.018446 | 21.75 | 644967.33 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 13.12 | 10.53 | 21.87 | 10.53 | 21.75 | 21.75 | 0.300000 | 0.484265 | 21.75 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 21.75 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 9.33 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002511 | 0.000190 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000267 | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.018446 | 0.000026 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.002826 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 21.75 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.026653 | 4308.61 | |
HEATSYS1 PUMP | 0.005514 | 1644.11 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.005514 | 0.661672 |
COOLSYS1 | 0.026653 | 3.20 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 630276.44 | 630276.44 | 0.005514 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.026653 | 2983.00 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.026653 | 931943.23 | 932547.11 | 106.31 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.718 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.098 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.286 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.976 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13293.583 | 6.718 | 124.824 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13293.583 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 406.155 | 4.286 | 199.096 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 406.155 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.6524 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.8441 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.8569 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.7799 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.7924 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.365 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.017 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9996 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.095 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.20756307E-14 | -0.33770914E-15 | -0.16263325E-09 | 0.36952592E-16 |
29 | 8 | 0.23685375E-07 | 0.88714462E-13 | 0.39655920E-03 | -0.26931086E-09 |
30 | 7 | -0.12800682E-01 | 0.45320291E-08 | -0.23890593E-01 | 0.14554843E-03 |
31 | 6 | 0.42054172 | 0.15673111E-05 | 0.48500809 | -0.49268323E-02 |
32 | 5 | -5.3387987 | 0.58223180E-04 | -4.5403777 | 0.65021910E-01 |
33 | 4 | 33.658449 | 0.47408857E-03 | 21.827556 | -0.43082749 |
34 | 3 | -112.62083 | 0.10289916E-02 | -56.389455 | 1.5353436 |
35 | 2 | 198.51314 | 0.57668395E-03 | 78.577213 | -2.9226634 |
36 | 1 | -171.67490 | 0.61354169E-04 | -55.459608 | 2.7545325 |
37 | 0 | 57.057407 | 0.34787598E-06 | 15.525360 | |
38 | 9 | -0.24257523E-14 | 0.33690592E-16 | -0.15372093E-09 | 0.39666009E-16 |
39 | 8 | 0.22436951E-07 | 0.11417013E-12 | 0.38367618E-03 | -0.25511586E-09 |
40 | 7 | -0.12417040E-01 | 0.58916776E-08 | -0.23338459E-01 | 0.14118628E-03 |
41 | 6 | 0.41011853 | 0.20479623E-05 | 0.47615013 | -0.48039676E-02 |
42 | 5 | -5.2370942 | 0.76414309E-04 | -4.4724296 | 0.63760808E-01 |
43 | 4 | 33.208666 | 0.62469949E-03 | 21.562156 | -0.42485549 |
44 | 3 | -111.66410 | 0.13607335E-02 | -55.864850 | 1.5215209 |
45 | 2 | 197.56520 | 0.76503996E-03 | 78.095736 | -2.9076095 |
46 | 1 | -171.32486 | 0.81633884E-04 | -55.318971 | 2.7483976 |
47 | 0 | 57.057407 | 0.46449959E-06 | 15.548073 | |
48 | 9 | -0.24053431E-14 | 0.30582108E-16 | -0.15312349E-09 | 0.40258954E-16 |
49 | 8 | 0.22353057E-07 | 0.11582316E-12 | 0.38280191E-03 | -0.25416195E-09 |
50 | 7 | -0.12390977E-01 | 0.59826426E-08 | -0.23300939E-01 | 0.14088992E-03 |
51 | 6 | 0.40941037 | 0.20803184E-05 | 0.47554760 | -0.47956200E-02 |
52 | 5 | -5.2301838 | 0.77645268E-04 | -4.4678046 | 0.63675121E-01 |
53 | 4 | 33.178102 | 0.63493787E-03 | 21.544084 | -0.42444968 |
54 | 3 | -111.59908 | 0.13833754E-02 | -55.829123 | 1.5205815 |
55 | 2 | 197.50076 | 0.77794062E-03 | 78.062960 | -2.9065863 |
56 | 1 | -171.30107 | 0.83027327E-04 | -55.309421 | 2.7479805 |
57 | 0 | 57.057407 | 0.47253235E-06 | 15.549635 | |
58 | 9 | -0.46044427E-14 | 0.27900089E-16 | -0.15673021E-09 | 0.84433218E-16 |
59 | 8 | 0.22857479E-07 | 0.10577188E-12 | 0.38804207E-03 | -0.25989740E-09 |
60 | 7 | -0.12547140E-01 | 0.54349272E-08 | -0.23525725E-01 | 0.14266556E-03 |
61 | 6 | 0.41365335 | 0.18858798E-05 | 0.47915629 | -0.48456347E-02 |
62 | 5 | -5.2715868 | 0.70260405E-04 | -4.4954992 | 0.64188504E-01 |
63 | 4 | 33.361217 | 0.57360532E-03 | 21.652286 | -0.42688098 |
64 | 3 | -111.98862 | 0.12479141E-02 | -56.043016 | 1.5262094 |
65 | 2 | 197.88677 | 0.70084509E-03 | 78.259217 | -2.9127162 |
66 | 1 | -171.44362 | 0.74708721E-04 | -55.366651 | 2.7504789 |
67 | 0 | 57.057407 | 0.42455547E-06 | 15.540314 | |
68 | 9 | -0.14490010E-14 | 0.30537737E-16 | -0.15613140E-09 | 0.37153042E-16 |
69 | 8 | 0.22775399E-07 | 0.10742354E-12 | 0.38719206E-03 | -0.25896410E-09 |
70 | 7 | -0.12521818E-01 | 0.55241817E-08 | -0.23489278E-01 | 0.14237764E-03 |
71 | 6 | 0.41296535 | 0.19175017E-05 | 0.47857136 | -0.48375248E-02 |
72 | 5 | -5.2648734 | 0.71459421E-04 | -4.4910111 | 0.64105260E-01 |
73 | 4 | 33.331527 | 0.58354868E-03 | 21.634754 | -0.42648676 |
74 | 3 | -111.92546 | 0.12698472E-02 | -56.008360 | 1.5252969 |
75 | 2 | 197.82418 | 0.71331385E-03 | 78.227414 | -2.9117223 |
76 | 1 | -171.42051 | 0.76052751E-04 | -55.357370 | 2.7500739 |
77 | 0 | 57.057407 | 0.43228786E-06 | 15.541820 | |
78 | 7 | -0.16359629E-14 | -0.14530353E-16 | -0.22331004E-13 | 0.54056000E-15 |
79 | 6 | 0.18262352E-10 | 0.22801053E-11 | 0.52333849E-09 | -0.18642118E-10 |
80 | 5 | -0.59540244E-07 | 0.11129510E-07 | -0.21928235E-05 | 0.17164558E-06 |
81 | 4 | 0.60861605E-04 | 0.41961443E-05 | 0.17683552E-02 | -0.28248824E-03 |
82 | 3 | -0.87523238E-02 | 0.14809838E-03 | -0.21562890 | 0.43346081E-01 |
83 | 2 | 0.12409989 | 0.64146884E-03 | 2.9009744 | -0.61915653 |
84 | 1 | -0.31397648 | 0.40472017E-03 | -7.1381115 | 1.5697592 |
85 | 0 | 0.19977219 | 0.56546383E-05 | 4.4522022 | |
86 | 7 | -0.22331004E-13 | -0.14530353E-16 | -0.16359629E-14 | 0.54056000E-15 |
87 | 6 | 0.52333849E-09 | 0.22801053E-11 | 0.18262352E-10 | -0.18642118E-10 |
88 | 5 | -0.21928235E-05 | 0.11129510E-07 | -0.59540244E-07 | 0.17164558E-06 |
89 | 4 | 0.17683552E-02 | 0.41961443E-05 | 0.60861605E-04 | -0.28248824E-03 |
90 | 3 | -0.21562890 | 0.14809838E-03 | -0.87523238E-02 | 0.43346081E-01 |
91 | 2 | 2.9009744 | 0.64146884E-03 | 0.12409989 | -0.61915653 |
92 | 1 | -7.1381115 | 0.40472017E-03 | -0.31397648 | 1.5697592 |
93 | 0 | 4.4522022 | 0.56546383E-05 | 0.19977219 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
103 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
104 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
105 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
106 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
107 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
108 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
109 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
110 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
111 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
112 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
113 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
114 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
115 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
116 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
117 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
118 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
119 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
120 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
121 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
122 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
123 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
124 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
125 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
126 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
127 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
128 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
129 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
130 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
131 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
132 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
133 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.346_SHGC_0.377 | 37 | 1 | VerySmooth | 1.966 | 1.966 | 1.000 | 0.378 | ||
2 | RESWINDOW_U_0.346_SHGC_0.377 | 38 | 1 | VerySmooth | 1.966 | 1.966 | 1.000 | 0.378 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.78725E-002 | 0.29064 | 0.50510 | 0.50510 | 0.41470 | 0.13613 | 0.17591 | 0.00000 | 0.84000 | 0.84000 | 0.11281 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.78725E-002 | 0.29064 | 0.50510 | 0.50510 | 0.41470 | 0.13613 | 0.17591 | 0.00000 | 0.84000 | 0.84000 | 0.11281 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1554 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.1493E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1759 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.2846E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1081 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.2737E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.3624E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.4492E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1765 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 9.7896E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2004 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1112 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1196 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.3377E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.8983E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.9816E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.7828E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.1834E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.9082E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.6482E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.7908E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1159E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.2941E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.5226E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.7828E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.1834E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.9082E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.6482E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.7908E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1159E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.2941E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.5226E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 29709.76916 | 29709.76916 | 2.26316 | 2.26316 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.48300 | 1.53564E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1584.54332 | 1584.54332 | 7.12067E-002 | 0.85446 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4984.01992 | 4984.01992 | 0.37971 | 0.37971 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3571.14720 | 3571.14720 | 0.16047 | 0.16047 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2955.52225 | 2955.52225 | 0.22517 | 0.22517 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 30.77600 | 1.53643E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1151.95493 | 1151.95493 | 5.17660E-002 | 9.17347E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2380.22696 | 2380.22696 | 0.18130 | 0.18130 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 30.67000 | 1.53641E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2029.39577 | 2029.39577 | 9.11957E-002 | 9.11957E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1318.10427 | 1318.10427 | 0.10040 | 0.10040 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1480.37863 | 1480.37863 | 6.65244E-002 | 6.65244E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44745.32207 | 44745.32207 | 3.40855 | 3.40855 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53651E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2688.64003 | 2688.64003 | 0.12082 | 0.12082 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 21128.77506 | 21128.77506 | 1.61103 | 1.61103 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 9144.22145 | 9144.22145 | 0.41091 | 0.67639 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 64518.13340 | 64518.13340 | 4.91671 | 4.91671 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 20702.81891 | 20702.81891 | 0.93033 | 1.89399 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11028.74930 | 11028.74930 | 1.13210 | 1.13210 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 7886.07148 | 7886.07148 | 0.35645 | 0.35645 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10679.49791 | 10679.49791 | 1.09625 | 1.09625 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 7905.01816 | 7905.01816 | 0.35731 | 0.35731 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 63520.70966 | 63520.70966 | 6.51996 | 6.51996 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 44806.20909 | 44806.20909 | 2.02530 | 2.02530 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 53651.32388 | 53651.32388 | 5.50739 | 5.50739 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.06600 | 1.53574E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 45164.49013 | 45164.49013 | 2.04149 | 2.04149 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10008.02887 | 10008.02887 | 1.02732 | 1.02732 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.87167 | 1.53571E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 7847.68533 | 7847.68533 | 0.35471 | 0.35471 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9710.83795 | 9710.83795 | 0.99682 | 0.99682 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.67033 | 1.53549E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 7866.63948 | 7866.63948 | 0.35557 | 0.35557 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 16772.73939 | 16772.73939 | 1.27765 | 1.27765 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 31.20000 | 1.53651E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 12373.17317 | 12373.17317 | 0.55602 | 0.55602 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2877.18898 | 2877.18898 | 0.29534 | 0.29534 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.71600 | 1.53623E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2430.26355 | 2430.26355 | 0.10985 | 0.10985 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2779.03105 | 2779.03105 | 0.28527 | 0.28527 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2437.29527 | 2437.29527 | 0.11017 | 0.11017 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 13201.29413 | 13201.29413 | 1.35514 | 1.35514 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 11599.96600 | 11599.96600 | 0.52432 | 0.52432 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28852.92891 | 28852.92891 | 2.20064 | 2.20064 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 8150.79110 | 8150.79110 | 0.36628 | 1.18780 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30308.07338 | 30308.07338 | 2.31159 | 2.31159 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 8322.00892 | 8322.00892 | 0.37397 | 1.18780 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29956.62245 | 29956.62245 | 2.28792 | 2.28792 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.87167 | 1.53571E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3931.29889 | 3931.29889 | 0.17665 | 0.36735 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -26.20000 | 3.61342E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9300.22044 | 9300.22044 | 0.70843 | 0.70843 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20000 | 1.53651E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 8554.32877 | 8554.32877 | 0.38441 | 0.38441 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 43560.46 | 16.82051 | 2.05125 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 101562.16 | 6.23516 | 2.05125 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 358430.49 | 21.75044 | 21.75044 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 378223.83 | 7.63897 | 7.63897 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26316 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66627 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28095 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.71844E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.02965E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28095 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8035.32647 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.02965E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 169.72562 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.37971 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13460 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31300 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11885 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37286 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.83063E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.83075E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16047 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4378.78747 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.83075E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 119.50507 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22517 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26284 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.61100 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13758 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70092 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44953E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.61356E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13758 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1844.39469 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.61356E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 42.12368 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18130 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69032 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.81298E-003 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.51921E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.17688E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.11957E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2488.30877 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17688E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 67.90922 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10040 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.71920 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.86300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.66443E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.29758E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.67659E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.66443E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1916.44981 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.67659E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 48.71711 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.40855 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.74461E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.40855E-002 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18386E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.88393E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12082 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3296.51457 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.88393E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 89.96609 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.61103 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.93296E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.63000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01495 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.26511E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.24690E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01495 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14252.81330 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24690E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 327.92269 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.91671 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20274 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57800 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84186 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57800 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87921E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.06255E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.84186 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35006.78144 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.06255E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 789.63469 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.13210 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.13210 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.89908E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.50083E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71041 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62582E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.50083E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.13210 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7886.07148 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.89908E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 225.32771 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.09625 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.09625 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.91565E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.39346E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71040 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62965E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.39346E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.09625 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7905.01816 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.91565E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 225.86899 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.51996 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 6.51996 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.91984E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.97688E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71103 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55336E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.97688E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.51996 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 44806.20909 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.91984E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1280.23755 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.50739 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 5.50739 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.95119E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.79644E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71005 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82906E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.79644E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.50739 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 45164.49013 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.95119E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1290.47331 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.02732 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.02732 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.86550E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.18852E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71038 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63947E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.18852E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.02732 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7847.68533 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.86550E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 224.23106 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.99682 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.99682 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.88208E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.09743E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71037 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64379E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.09743E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.99682 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7866.63948 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.88208E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 224.77256 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27765 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.92897 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71165 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.10130E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.39588E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71165 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15955.73359 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39588E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 407.22432 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.29534 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.29534 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.12610E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.12025E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71042 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62066E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.12025E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.29534 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2430.26355 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.12610E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 69.43774 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28527 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.28527 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.13225E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.81865E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71041 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62467E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.81865E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.28527 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2437.29527 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.13225E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 69.63863 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.35514 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.35514 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.01482E-004 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.25568E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71019 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68351E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.25568E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.35514 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 11599.96600 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01482E-004 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 331.43479 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.20064 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11484 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.81000 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78252 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81000 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.31764E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49813E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78252 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17124.58073 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49813E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 374.83392 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31159 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10933 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.77100 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78224 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77100 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.48490E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51299E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78224 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17294.41286 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51299E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 378.95247 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28792 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.18834E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24100 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55139 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10737E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.86494E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55139 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6703.98603 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.86494E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 150.94572 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70843 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.44329 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26600 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18844 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.59489E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.17687E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38441 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10489.72365 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.17687E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 286.28795 |
318 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
319 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
320 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
321 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
322 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
323 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
324 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.12134 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.53297 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.87227 |
329 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.53297 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.75044 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.75044 |
332 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.48426 |
334 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.75044 |
336 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
339 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 31.20000 |
340 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.89847 |
342 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.53651E-002 |
343 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 87803.63747 |
345 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.51117E-003 |
346 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
347 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 30469.71807 |
348 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.66562E-004 |
349 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 443.50586 |
350 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
351 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.51117E-003 |
352 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.89629E-004 |
353 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.66562E-004 |
354 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.75044 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 9.32920 |
356 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.08251 |
357 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90123 |
359 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.21462E-002 |
360 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 644967.33201 |
362 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.84460E-002 |
363 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 21.75044 |
364 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 323075.27036 |
365 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.82640E-003 |
366 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4702.56322 |
367 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 21.75044 |
368 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.84460E-002 |
369 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.58154E-005 |
370 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.82640E-003 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.66535E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4308.60924 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.51393E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.66167 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.51393E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1644.11342 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 630276.44029 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 630276.44000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.51393E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.66535E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.19841 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.66535E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2982.99550 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.66535E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 931943.23313 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 932547.11000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 106.31037 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8076.52 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4395.76 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1853.09 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2497.95 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1924.52 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 3309.29 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 14319.54 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 35173.69 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 8493.99 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 8514.40 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 48260.41 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 48646.28 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 8452.65 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 8473.07 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 16022.69 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2617.57 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2625.14 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 12494.00 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 17209.81 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 17380.42 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6736.01 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10530.38 |
23 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 18524.03 |
24 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 196413.25 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 18675.20 | 15746.43 | 2928.77 | 0.84 | 4489.35 | 45.53 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 18096.55 | 15251.91 | 2844.64 | 0.84 | 4342.94 | 44.05 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 106099.46 | 90215.87 | 15883.59 | 0.85 | 26350.35 | 267.26 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 94223.17 | 77723.90 | 16499.27 | 0.82 | 21015.28 | 213.15 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 16989.37 | 14302.87 | 2686.50 | 0.84 | 4059.80 | 41.18 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 16499.74 | 13883.53 | 2616.21 | 0.84 | 3939.39 | 39.96 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4867.36 | 4106.44 | 760.92 | 0.84 | 1172.75 | 11.89 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4704.79 | 3967.47 | 737.31 | 0.84 | 1131.57 | 11.48 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 22592.78 | 18926.82 | 3665.96 | 0.84 | 5305.00 | 53.81 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 64803.99 | 40877.16 | 23926.83 | 0.63 | 9107.44 | 92.37 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 628406.15 | 408419.46 | 219986.70 | 0.65 | 98682.77 | 1000.90 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.844 | 0.749 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.844 | 0.749 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.844 | 0.749 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.844 | 0.749 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.346_SHGC_0.377 | N/A | 1.966 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6464099001E-002 | 2.1967651402E-002 | Pass | Pass | 4.5010355543E-003 | 1.1725458526E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.1768681043E-003 | 8.5630009874E-004 | Pass | Pass | 0.2014845550 | 0.6929891688 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.8042077862E-003 | 1.6158011614E-002 | Pass | Pass | 2.3416328484E-002 | 6.0700850503E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5899964742E-002 | 1.7447358934E-002 | Pass | Pass | 4.1132742489E-002 | 0.1280703348 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.7864429669E-004 | 5.2724837372E-004 | Pass | Pass | 0.1740223497 | 0.6447621065 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.0826262400E-005 | 8.0317378140E-005 | Pass | Pass | 2.1397054879E-002 | 6.2140296759E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7663772426E-003 | 3.1942529229E-003 | Pass | Pass | 4.8462690393E-002 | 0.1217875737 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.3352082399E-002 | 3.9107693900E-002 | Pass | Pass | 1.5712588057E-002 | 4.3215286997E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2602652541E-002 | 0.3057532686 | Pass | Pass | 8.7783350702E-002 | 0.2292495020 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2619528211E-002 | 0.3105556110 | Pass | Pass | 8.8131802278E-002 | 0.2316851859 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.0627790678E-002 | 2.3091806197E-002 | Pass | Pass | 8.4612050936E-002 | 0.2218743325 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.3693089049E-002 | 0.1088793391 | Pass | Pass | 0.1615815560 | 0.4604755933 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2607671217E-002 | 0.3020088881 | Pass | Pass | 8.8354382359E-002 | 0.2230722882 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2602974128E-002 | 0.3056554957 | Pass | Pass | 8.5934945833E-002 | 0.2208547574 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.8732426092E-004 | 2.9907359645E-004 | Pass | Pass | 0.4252258624 | 2.5411790596 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2946923356E-002 | 0.3287669603 | Pass | Pass | 0.2414804870 | 1.3576920729 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2939505257E-002 | 0.3333802235 | Pass | Pass | 0.2382298673 | 1.0847779192 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.6570470691E-002 | 0.2769700084 | Pass | Pass | 7.5992000885E-002 | 0.1818161089 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.9329968640E-002 | 9.2782986656E-002 | Pass | Pass | 1.0914696087E-002 | 2.8062958041E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.7997069443E-002 | 9.3314063351E-002 | Pass | Pass | 1.0055557383E-002 | 2.0830394592E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.7251075066E-004 | 1.7860999100E-003 | Pass | Pass | 2.4423258934E-002 | 4.6960074271E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.3101210315E-004 | 3.3505007879E-004 | Pass | Pass | 0.5273063771 | 4.3068858521 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4402.08 | 78.60 | 2141.35 | 6263.49 | 3492.16 | 16377.69 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.966 | 0.378 | 0.416 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.966 | 0.378 | 0.416 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.966 | 0.378 | 0.416 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.966 | 0.378 | 0.416 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.966 | 0.378 | 0.416 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.966 | 0.378 | 0.416 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.966 | 0.378 | 0.416 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.966 | 0.378 | 0.416 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.966 | 0.378 | 0.416 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.966 | 0.378 | 0.416 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.966 | 0.378 | 0.416 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.966 | 0.378 | 0.416 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.966 | 0.378 | 0.416 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.966 | 0.378 | 0.416 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.966 | 0.378 | 0.416 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.966 | 0.378 | 0.416 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.966 | 0.378 | 0.416 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.966 | 0.378 | 0.416 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.966 | 0.378 | 0.416 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.966 | 0.378 | 0.416 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.966 | 0.378 | 0.416 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.346_SHGC_0.377 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.966 | 0.378 | 0.416 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.966 | 0.378 | 0.416 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.966 | 0.378 | 0.416 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.966 | 0.378 | 0.416 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.966 | 0.378 | 0.416 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.966 | 0.378 | 0.416 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.966 | 0.378 | 0.416 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.966 | 0.378 | 0.416 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.346_SHGC_0.377 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.966 | 0.378 | 0.416 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.966 | 0.378 | 0.416 | |||||||||||||||||
North Total or Average | 432.95 | 1.966 | 0.378 | 0.416 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.966 | 0.378 | 0.416 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.7179 | 1978.83 | 13293.58 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 122.93 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.2862 | 94.76 | 406.16 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 2.31 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 38.82 | 0.0000 | Y | 12.74 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.43 | 0.0000 | Y | 91.98 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.78 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.79 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 6.96 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.78 | 0.0000 | Y | 28.11 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.78 | 0.0000 | Y | 28.11 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8577 | 11345.29 | 66457.67 | 365.20 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.63 | 83.63 | 193.69 | |
Exterior Lighting Total | 12338.45 | 193.69 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 630276.44 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 932547.11 | 2.96 | 932547.11 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12240.93 | 18675.20 | 15746.43 | 2928.77 | 0.84 | - | 4489.35 | 45.53 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11865.53 | 18096.55 | 15251.91 | 2844.64 | 0.84 | - | 4342.94 | 44.05 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 69123.36 | 106099.46 | 90215.87 | 15883.59 | 0.85 | - | 26350.35 | 267.26 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 62813.98 | 94223.17 | 77723.90 | 16499.27 | 0.82 | - | 21015.28 | 213.15 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11148.94 | 16989.37 | 14302.87 | 2686.50 | 0.84 | - | 4059.80 | 41.18 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10830.42 | 16499.74 | 13883.53 | 2616.21 | 0.84 | - | 3939.39 | 39.96 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3188.97 | 4867.36 | 4106.44 | 760.92 | 0.84 | - | 1172.75 | 11.89 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3083.51 | 4704.79 | 3967.47 | 737.31 | 0.84 | - | 1131.57 | 11.48 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 14880.35 | 22592.78 | 18926.82 | 3665.96 | 0.84 | - | 5305.00 | 53.81 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 87803.64 | 64803.99 | 40877.16 | 23926.83 | 0.63 | - | 9107.44 | 92.37 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 644967.33 | 628406.15 | 408419.46 | 219986.70 | 0.65 | - | 98682.77 | 1000.90 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8035.33 | 8076.52 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4378.79 | 4395.76 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1844.39 | 1853.09 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2488.31 | 2497.95 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1916.45 | 1924.52 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3296.51 | 3309.29 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14252.81 | 14319.54 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 35006.78 | 35173.69 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7886.07 | 8493.99 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7905.02 | 8514.40 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 44806.21 | 48260.41 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 45164.49 | 48646.28 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7847.69 | 8452.65 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7866.64 | 8473.07 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 15955.73 | 16022.69 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2430.26 | 2617.57 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2437.30 | 2625.14 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 11599.97 | 12494.00 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 17124.58 | 17209.81 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 17294.41 | 17380.42 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6703.99 | 6736.01 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10489.72 | 10530.38 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 30469.72 | 18524.03 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 323075.27 | 196413.25 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.13 | 796.59 | 703.64 | 1.00 | 1.17 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.10 | 771.36 | 703.64 | 1.00 | 1.17 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 6.52 | 4587.68 | 703.64 | 1.00 | 0.95 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 5.51 | 3875.20 | 703.64 | 1.00 | 0.96 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.03 | 722.86 | 703.64 | 1.00 | 1.19 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.00 | 701.40 | 703.64 | 1.00 | 1.20 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.30 | 207.81 | 703.64 | 1.00 | 1.72 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 200.72 | 703.64 | 1.00 | 1.75 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.36 | 953.52 | 703.64 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.75 | 48734.88 | 2240.64 | 1.00 | 1.11 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.026653 | 4308.61 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.005514 | 1644.11 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.026653 | 2983.00 | 111917.77 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 29709.77 | 29709.77 | 15.01 | 2.263 | 2.263 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 24.00 | 24.00 | 0.00931 | 26.48 | 0.01536 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4984.02 | 4984.02 | 74.31 | 0.380 | 0.380 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00906 | 30.85 | 0.01536 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2955.52 | 2955.52 | 38.05 | 0.225 | 0.225 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00950 | 30.78 | 0.01536 | 0.092 | 0.00 |
MECH_FLR_1 | 2380.23 | 2380.23 | 14.49 | 0.181 | 0.181 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00889 | 30.67 | 0.01536 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1318.10 | 1318.10 | 13.91 | 0.100 | 0.100 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00899 | 31.20 | 0.01537 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44745.32 | 44745.32 | 573.37 | 3.409 | 3.409 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00855 | 31.20 | 0.01537 | 0.000 | 0.00 |
CAFE_FLR_1 | 21128.78 | 21128.78 | 111.87 | 1.611 | 1.611 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01005 | 30.85 | 0.01536 | 0.676 | 0.00 |
LOBBY_FLR_1 | 64518.13 | 64518.13 | 49.32 | 4.917 | 4.917 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01001 | 30.93 | 0.01536 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11028.75 | 11028.75 | 282.63 | 1.132 | 1.132 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00863 | 29.54 | 0.01536 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10679.50 | 10679.50 | 273.71 | 1.096 | 1.096 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00863 | 29.54 | 0.01536 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 63520.71 | 63520.71 | 2590.16 | 6.520 | 6.520 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00855 | 31.02 | 0.01536 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 53651.32 | 53651.32 | 2187.12 | 5.507 | 5.507 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 21.11 | 21.11 | 0.00883 | 27.07 | 0.01536 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10008.03 | 10008.03 | 256.47 | 1.027 | 1.027 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 21.11 | 21.11 | 0.00864 | 26.87 | 0.01536 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9710.84 | 9710.84 | 248.88 | 0.997 | 0.997 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00864 | 25.67 | 0.01535 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 16772.74 | 16772.74 | 43.07 | 1.278 | 1.278 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00970 | 31.20 | 0.01537 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2877.19 | 2877.19 | 73.73 | 0.295 | 0.295 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00862 | 29.72 | 0.01536 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2779.03 | 2779.03 | 71.23 | 0.285 | 0.285 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00862 | 29.54 | 0.01536 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13201.29 | 13201.29 | 538.16 | 1.355 | 1.355 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00868 | 31.02 | 0.01536 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28852.93 | 28852.93 | 87.00 | 2.201 | 2.201 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01047 | 31.20 | 0.01537 | 1.188 | 0.00 |
DINING_FLR_6 | 30308.07 | 30308.07 | 91.38 | 2.312 | 2.312 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01038 | 31.20 | 0.01537 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29956.62 | 29956.62 | 289.98 | 2.288 | 2.288 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 23.97 | 0.01005 | 26.87 | 0.01536 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9300.22 | 9300.22 | 22.57 | 0.708 | 0.708 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00909 | 31.20 | 0.01537 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1584.54 | 1584.54 | 0.80 | 0.071 | 0.854 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00798 | -26.20 | 0.00036 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3571.15 | 3571.15 | 53.24 | 0.160 | 0.160 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00776 | -26.20 | 0.00036 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1151.95 | 1151.95 | 14.83 | 0.052 | 0.092 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00771 | -26.20 | 0.00036 | 0.092 | 0.00 |
MECH_FLR_1 | 2029.40 | 2029.40 | 12.36 | 0.091 | 0.091 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00762 | -26.20 | 0.00036 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1480.38 | 1480.38 | 15.62 | 0.067 | 0.067 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00770 | -26.20 | 0.00036 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2688.64 | 2688.64 | 34.45 | 0.121 | 0.121 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00761 | -26.20 | 0.00036 | 0.000 | 0.00 |
CAFE_FLR_1 | 9144.22 | 9144.22 | 48.42 | 0.411 | 0.676 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00779 | -26.20 | 0.00036 | 0.676 | 0.00 |
LOBBY_FLR_1 | 20702.82 | 20702.82 | 15.83 | 0.930 | 1.894 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00774 | -26.20 | 0.00036 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 7886.07 | 7886.07 | 202.09 | 0.356 | 0.356 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00775 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7905.02 | 7905.02 | 202.60 | 0.357 | 0.357 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00775 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 44806.21 | 44806.21 | 1827.05 | 2.025 | 2.025 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00776 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 45164.49 | 45164.49 | 1841.15 | 2.041 | 2.041 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00777 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7847.69 | 7847.69 | 201.11 | 0.355 | 0.355 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00775 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 7866.64 | 7866.64 | 201.62 | 0.356 | 0.356 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00775 | -26.20 | 0.00036 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 12373.17 | 12373.17 | 31.77 | 0.556 | 0.556 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00780 | -26.20 | 0.00036 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2430.26 | 2430.26 | 62.28 | 0.110 | 0.110 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00779 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2437.30 | 2437.30 | 62.47 | 0.110 | 0.110 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00779 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11599.97 | 11599.97 | 472.88 | 0.524 | 0.524 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00780 | -26.20 | 0.00036 | 0.099 | 0.00 |
BANQUET_FLR_6 | 8150.79 | 8150.79 | 24.58 | 0.366 | 1.188 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00785 | -26.20 | 0.00036 | 1.188 | 0.00 |
DINING_FLR_6 | 8322.01 | 8322.01 | 25.09 | 0.374 | 1.188 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00785 | -26.20 | 0.00036 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 3931.30 | 3931.30 | 38.06 | 0.177 | 0.367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00744 | -26.20 | 0.00036 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 8554.33 | 8554.33 | 20.76 | 0.384 | 0.384 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -26.20 | 0.00036 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 16.82 | 2.05 | 6.24 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 21.75 | 21.75 | 7.64 | 7.64 | 21.7504 | 10.5330 | 21.7504 | 0.4843 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8035.326 | 8035.326 | 1.280951 | 0.00007030 | 169.726 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8035.33 | 8035.33 | 1.280951 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00797774 | 49.1934 | 1584.54 | 0.00 | 8080.28 | 8080.28 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4378.787 | 4378.787 | 0.160474 | 0.00003831 | 119.505 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4378.79 | 4378.79 | 0.160474 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00775876 | 47.8625 | 3571.15 | 0.00 | 4400.50 | 4400.50 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1844.395 | 1844.395 | 0.137577 | 0.00001614 | 42.124 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1844.39 | 1844.39 | 0.137577 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00771311 | 47.5827 | 1151.95 | 0.00 | 1854.31 | 1854.31 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2488.309 | 2488.309 | 0.091196 | 0.00002177 | 67.909 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2488.31 | 2488.31 | 0.091196 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00762000 | 47.0153 | 2029.40 | 0.00 | 2500.65 | 2500.65 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1916.450 | 1916.450 | 0.086644 | 0.00001677 | 48.717 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1916.45 | 1916.45 | 0.086644 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00769629 | 47.4803 | 1480.38 | 0.00 | 1926.28 | 1926.28 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 3296.515 | 3296.515 | 0.120817 | 0.00002884 | 89.966 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3296.51 | 3296.51 | 0.120817 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00760894 | 46.9496 | 2688.64 | 0.00 | 3312.86 | 3312.86 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 14252.813 | 14252.813 | 1.014950 | 0.00012469 | 327.923 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14252.81 | 14252.81 | 1.014950 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00779083 | 48.0574 | 9144.22 | 0.00 | 14329.25 | 14329.25 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 35006.781 | 35006.781 | 2.841859 | 0.00030625 | 789.635 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 35006.78 | 35006.78 | 2.841859 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00773792 | 47.7338 | 20702.82 | 0.00 | 35195.84 | 35195.84 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12240.930 | -999.000 | 1.132099 | 0.00035008 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 12240.93 | 11896.62 | 1.132099 | 21.71 | 15.20 | 0.00862582 | 12.80 | 11.68 | 0.00850000 | 29.54 | 0.01536201 | 22.68 | 0.0000 | 21.11 | 0.00862582 | 52.7762 | 11028.75 | 0.00 | 12832.71 | 12832.71 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 7886.071 | 7886.071 | 0.356450 | 0.00006899 | 225.328 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7886.07 | 7886.07 | 0.356450 | 21.11 | 14.20 | 0.00774820 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00774820 | 47.4736 | 7886.07 | 0.00 | 8501.32 | 8501.32 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11865.526 | -999.000 | 1.096249 | 0.00033935 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 11865.53 | 11521.92 | 1.096249 | 21.71 | 15.21 | 0.00862965 | 12.80 | 11.68 | 0.00850000 | 29.54 | 0.01536201 | 22.68 | 0.0000 | 21.11 | 0.00862965 | 52.7993 | 10679.50 | 0.00 | 12438.75 | 12438.75 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 7905.018 | 7905.018 | 0.357306 | 0.00006916 | 225.869 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7905.02 | 7905.02 | 0.357306 | 21.11 | 14.20 | 0.00774880 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00774880 | 47.4773 | 7905.02 | 0.00 | 8521.75 | 8521.75 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 69123.355 | -999.000 | 6.519960 | 0.00197688 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 69123.36 | 68285.34 | 6.519960 | 21.71 | 15.14 | 0.00855336 | 12.80 | 11.68 | 0.00850000 | 31.02 | 0.01536476 | 23.08 | 0.0000 | 21.11 | 0.00855336 | 52.3371 | 63520.71 | 0.00 | 72501.88 | 72501.88 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 44806.209 | 44806.209 | 2.025295 | 0.00039198 | 1280.238 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 44806.21 | 44806.21 | 2.025295 | 21.11 | 14.22 | 0.00776455 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00776455 | 47.5709 | 44806.21 | 0.00 | 48302.31 | 48302.31 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 62813.980 | -999.000 | 5.507388 | 0.00179644 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | unknown | 7/21 19:00:00 | 62813.98 | 58393.91 | 5.507388 | 21.71 | 15.38 | 0.00882906 | 12.80 | 11.68 | 0.00850000 | 27.07 | 0.01535744 | 22.00 | 0.0000 | 21.11 | 0.00882906 | 54.0027 | 53651.32 | 0.00 | 65777.16 | 62759.45 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 45164.490 | 45164.490 | 2.041490 | 0.00039512 | 1290.473 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 45164.49 | 45164.49 | 2.041490 | 21.11 | 14.22 | 0.00776630 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00776630 | 47.5815 | 45164.49 | 0.00 | 48688.55 | 48688.55 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11148.940 | -999.000 | 1.027323 | 0.00031885 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | 7/21 09:50:00 | 11148.94 | 10802.38 | 1.027323 | 21.71 | 15.21 | 0.00863947 | 12.80 | 11.68 | 0.00850000 | 26.87 | 0.01535708 | 21.94 | 0.0000 | 21.11 | 0.00863947 | 52.8586 | 10008.03 | 0.00 | 11686.57 | 11686.57 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 7847.685 | 7847.685 | 0.354715 | 0.00006865 | 224.231 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7847.69 | 7847.69 | 0.354715 | 21.11 | 14.20 | 0.00774701 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00774701 | 47.4664 | 7847.69 | 0.00 | 8459.94 | 8459.94 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10830.415 | -999.000 | 0.996818 | 0.00030974 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 10830.42 | 10483.67 | 0.996818 | 21.71 | 15.22 | 0.00864379 | 12.80 | 11.68 | 0.00850000 | 25.67 | 0.01535487 | 21.60 | 0.0000 | 21.11 | 0.00864379 | 52.8846 | 9710.84 | 0.00 | 11353.73 | 11353.73 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 7866.639 | 7866.639 | 0.355571 | 0.00006882 | 224.773 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7866.64 | 7866.64 | 0.355571 | 21.11 | 14.20 | 0.00774762 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00774762 | 47.4701 | 7866.64 | 0.00 | 8480.37 | 8480.37 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 15955.734 | 15955.734 | 0.711652 | 0.00013959 | 407.224 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15955.73 | 15955.73 | 0.711652 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00780335 | 48.1319 | 12373.17 | 0.00 | 16037.52 | 16037.52 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3188.971 | -999.000 | 0.295343 | 0.00009120 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3188.97 | 3102.86 | 0.295343 | 21.71 | 15.20 | 0.00862066 | 12.80 | 11.68 | 0.00850000 | 29.72 | 0.01536233 | 22.73 | 0.0000 | 21.11 | 0.00862066 | 52.7450 | 2877.19 | 0.00 | 3343.29 | 3343.29 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2430.264 | 2430.264 | 0.109848 | 0.00002126 | 69.438 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2430.26 | 2430.26 | 0.109848 | 21.11 | 14.24 | 0.00779440 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00779440 | 47.7531 | 2430.26 | 0.00 | 2619.87 | 2619.87 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3083.515 | -999.000 | 0.285267 | 0.00008819 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 3083.51 | 2997.56 | 0.285267 | 21.71 | 15.20 | 0.00862467 | 12.80 | 11.68 | 0.00850000 | 29.54 | 0.01536201 | 22.68 | 0.0000 | 21.11 | 0.00862467 | 52.7692 | 2779.03 | 0.00 | 3232.62 | 3232.62 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2437.295 | 2437.295 | 0.110166 | 0.00002132 | 69.639 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2437.30 | 2437.30 | 0.110166 | 21.11 | 14.25 | 0.00779500 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00779500 | 47.7567 | 2437.30 | 0.00 | 2627.45 | 2627.45 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14880.350 | -999.000 | 1.355136 | 0.00042557 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 14880.35 | 14277.67 | 1.355136 | 21.71 | 15.25 | 0.00868351 | 12.80 | 11.68 | 0.00850000 | 31.02 | 0.01536476 | 23.08 | 0.0000 | 21.11 | 0.00868351 | 53.1247 | 13201.29 | 0.00 | 15594.13 | 15594.13 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 11599.966 | 11599.966 | 0.524324 | 0.00010148 | 331.435 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11599.97 | 11599.97 | 0.524324 | 21.11 | 14.25 | 0.00780147 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00780147 | 47.7953 | 11599.97 | 0.00 | 12505.01 | 12505.01 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 17124.581 | 17124.581 | 1.782521 | 0.00014981 | 374.834 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 17124.58 | 17124.58 | 1.782521 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00784835 | 48.4066 | 8150.79 | 0.00 | 17219.37 | 17219.37 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 17294.413 | 17294.413 | 1.782235 | 0.00015130 | 378.952 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 17294.41 | 17294.41 | 1.782235 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00785141 | 48.4252 | 8322.01 | 0.00 | 17390.11 | 17390.11 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6703.986 | 6703.986 | 0.551389 | 0.00005865 | 150.946 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 6703.99 | 6703.99 | 0.551389 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00743695 | 45.9040 | 3931.30 | 0.00 | 6740.22 | 6740.22 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 10489.724 | 10489.724 | 0.384412 | 0.00009177 | 286.288 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10489.72 | 10489.72 | 0.384412 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00787298 | 48.5562 | 8554.33 | 0.00 | 10541.74 | 10541.74 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 87803.637 | -999.000 | 2.051317 | 0.00251117 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 87803.64 | 47531.07 | 2.051317 | 31.20 | 23.13 | 0.01536508 | 11.90 | 11.31 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 99.9965 | 21.11 | 0.00868285 | 53.1196 | 163865.83 | 0.00 | 89691.54 | 48118.14 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 30469.718 | 30469.718 | 0.615395 | 0.00026656 | 443.506 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 30469.72 | 30469.72 | 0.615395 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.75 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 333.3216 | 21.11 | 0.00776567 | 47.5778 | 137943.64 | 0.00 | 22379.93 | 22379.93 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 644967.332 | -999.000 | 21.750443 | 0.01844598 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 644967.33 | 412720.22 | 21.750443 | 27.08 | 19.77 | 0.01214617 | 10.90 | 10.89 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 42.8920 | 23.99 | 0.00972335 | 49.8517 | 285252.50 | 0.00 | 663144.00 | 411525.99 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 323075.270 | 323075.270 | 6.525133 | 0.00282640 | 4702.563 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 323075.27 | 323075.27 | 6.525133 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.75 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 142.9733 | 21.00 | 0.00778034 | 47.9922 | 82732.76 | 0.00 | 237297.98 | 237297.98 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8035.326 | 8035.326 | 1.280951 | 0.00007030 | 169.726 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 1.2497 | 1.274889 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8035.33 | 8035.33 | 1.0000 | 1.47124337 | 1.280951 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.07028937 | 60.00 | 32.22 | 27.78 | 0.000 | 8035.33 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00797774 | 21.00 | 0.00797774 | 49.1934 | 1584.54 | 0.00 | 8080.28 | 8080.28 | 1.47124337 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.99 | 15.22 | 0.00800000 | 42426.9 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4378.787 | 4378.787 | 0.160474 | 0.00003831 | 119.505 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 0.6810 | 0.694741 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 4378.79 | 4378.79 | 1.0000 | 0.18431294 | 0.160474 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.03830364 | 60.00 | 32.22 | 27.78 | 0.000 | 4378.79 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00775876 | 21.00 | 0.00775876 | 47.8625 | 3571.15 | 0.00 | 4400.50 | 4400.50 | 0.18431294 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60809.9 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1844.395 | 1844.395 | 0.137577 | 0.00001614 | 42.124 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 0.2869 | 0.292633 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1844.39 | 1844.39 | 1.0000 | 0.15801515 | 0.137577 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.01613392 | 60.00 | 32.22 | 27.78 | 0.000 | 1844.39 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00771311 | 21.00 | 0.00771311 | 47.5827 | 1151.95 | 0.00 | 1854.31 | 1854.31 | 0.15801515 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.11 | 17.40 | 0.00800000 | 48669.8 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2488.309 | 2488.309 | 0.091196 | 0.00002177 | 67.909 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 0.3870 | 0.394796 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2488.31 | 2488.31 | 1.0000 | 0.10474336 | 0.091196 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.02176659 | 60.00 | 32.22 | 27.78 | 0.000 | 2488.31 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00762000 | 21.00 | 0.00762000 | 47.0153 | 2029.40 | 0.00 | 2500.65 | 2500.65 | 0.10474336 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60808.8 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1916.450 | 1916.450 | 0.086644 | 0.00001677 | 48.717 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 0.2981 | 0.304065 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1916.45 | 1916.45 | 1.0000 | 0.09951580 | 0.086644 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.01676423 | 60.00 | 32.22 | 27.78 | 0.000 | 1916.45 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00769629 | 21.00 | 0.00769629 | 47.4803 | 1480.38 | 0.00 | 1926.28 | 1926.28 | 0.09951580 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.58 | 19.84 | 0.00800000 | 56291.3 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3296.515 | 3296.515 | 0.120817 | 0.00002884 | 89.966 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 0.5127 | 0.523027 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3296.51 | 3296.51 | 1.0000 | 0.13876465 | 0.120817 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.02883641 | 60.00 | 32.22 | 27.78 | 0.000 | 3296.51 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00760894 | 21.00 | 0.00760894 | 46.9496 | 2688.64 | 0.00 | 3312.86 | 3312.86 | 0.13876465 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60808.7 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14252.813 | 14252.813 | 1.014950 | 0.00012469 | 327.923 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 2.2167 | 2.261359 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14252.81 | 14252.81 | 1.0000 | 1.16572684 | 1.014950 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.12467711 | 60.00 | 32.22 | 27.78 | 0.000 | 14252.81 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00779083 | 21.00 | 0.00779083 | 48.0574 | 9144.22 | 0.00 | 14329.25 | 14329.25 | 1.16572684 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.65 | 17.58 | 0.00800000 | 49226.8 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35006.781 | 35006.781 | 2.841859 | 0.00030625 | 789.635 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 5.4446 | 5.554195 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 35006.78 | 35006.78 | 1.0000 | 3.26403354 | 2.841859 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.30622335 | 60.00 | 32.22 | 27.78 | 0.000 | 35006.78 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00773792 | 21.00 | 0.00773792 | 47.7338 | 20702.82 | 0.00 | 35195.84 | 35195.84 | 3.26403354 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.17 | 17.08 | 0.00800000 | 47717.7 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12240.930 | -999.000 | 1.132099 | 0.00035008 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8750 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.132099 | 1.30027841 | 4197.9300 | 999.8980 | 26.65073957 | 15.03 | 6.70 | 8.33 | 931943.23 | 1.3135 | 1.313460 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 12240.93 | 11896.62 | 1.0000 | 1.30027841 | 1.132099 | 21.71 | 15.20 | 0.00862582 | 43736.3 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.35004681 | 6.70 | 15.03 | 8.33 | 0.000 | 12240.93 | 29.54 | 0.01536201 | 22.68 | 0.00000000 | 0.0000 | 21.11 | 0.00862582 | 21.11 | 0.00862582 | 52.7762 | 11028.75 | 0.00 | 12832.71 | 12832.71 | 1.30027841 | 21.71 | 15.68 | 0.00862582 | 43736.3 | 12.04 | 11.91 | 0.00862582 | 33867.1 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7886.071 | 7886.071 | 0.356450 | 0.00006899 | 225.328 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.132099 | 1.30027841 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 1.2265 | 1.251208 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7886.07 | 7886.07 | 1.0000 | 0.40940223 | 0.356450 | 21.11 | 14.20 | 0.00774820 | 40894.0 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.06898376 | 60.00 | 32.22 | 27.78 | 0.000 | 7886.07 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00774820 | 21.11 | 0.00774820 | 47.4736 | 7886.07 | 0.00 | 8501.32 | 8501.32 | 0.40940223 | 16.60 | 12.91 | 0.00774820 | 36297.2 | 36.97 | 20.08 | 0.00774820 | 57062.4 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11865.526 | -999.000 | 1.096249 | 0.00033935 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8821 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.096249 | 1.25910335 | 4197.9300 | 999.8980 | 26.65073957 | 15.03 | 6.70 | 8.33 | 931943.23 | 1.2732 | 1.273179 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 11865.53 | 11521.92 | 1.0000 | 1.25910335 | 1.096249 | 21.71 | 15.21 | 0.00862965 | 43746.0 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.33931158 | 6.70 | 15.03 | 8.33 | 0.000 | 11865.53 | 29.54 | 0.01536201 | 22.68 | 0.00000000 | 0.0000 | 21.11 | 0.00862965 | 21.11 | 0.00862965 | 52.7993 | 10679.50 | 0.00 | 12438.75 | 12438.75 | 1.25910335 | 21.71 | 15.68 | 0.00862965 | 43746.0 | 12.03 | 11.91 | 0.00862965 | 33866.9 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7905.018 | 7905.018 | 0.357306 | 0.00006916 | 225.869 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.096249 | 1.25910335 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 1.2295 | 1.254214 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7905.02 | 7905.02 | 1.0000 | 0.41038584 | 0.357306 | 21.11 | 14.20 | 0.00774880 | 40895.5 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.06914949 | 60.00 | 32.22 | 27.78 | 0.000 | 7905.02 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00774880 | 21.11 | 0.00774880 | 47.4773 | 7905.02 | 0.00 | 8521.75 | 8521.75 | 0.41038584 | 16.60 | 12.91 | 0.00774880 | 36298.7 | 36.97 | 20.08 | 0.00774880 | 57064.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 69123.355 | -999.000 | 6.519960 | 0.00197688 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7403 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.519960 | 7.48853822 | 4197.9300 | 999.8980 | 26.65073957 | 15.03 | 6.70 | 8.33 | 931943.23 | 7.4171 | 7.416982 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 69123.36 | 68285.34 | 1.0000 | 7.48853822 | 6.519960 | 21.71 | 15.14 | 0.00855336 | 43552.7 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 1.97668063 | 6.70 | 15.03 | 8.33 | 0.000 | 69123.36 | 31.02 | 0.01536476 | 23.08 | 0.00000000 | 0.0000 | 21.11 | 0.00855336 | 21.11 | 0.00855336 | 52.3371 | 63520.71 | 0.00 | 72501.88 | 72501.88 | 7.48853822 | 21.71 | 15.61 | 0.00855336 | 43552.7 | 12.23 | 11.92 | 0.00855336 | 33871.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44806.209 | 44806.209 | 2.025295 | 0.00039198 | 1280.238 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.519960 | 7.48853822 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 6.9687 | 7.108977 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 44806.21 | 44806.21 | 1.0000 | 2.32616440 | 2.025295 | 21.11 | 14.22 | 0.00776455 | 40936.1 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.39194428 | 60.00 | 32.22 | 27.78 | 0.000 | 44806.21 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00776455 | 21.11 | 0.00776455 | 47.5709 | 44806.21 | 0.00 | 48302.31 | 48302.31 | 2.32616440 | 16.60 | 12.92 | 0.00776455 | 36338.6 | 36.97 | 20.09 | 0.00776455 | 57103.4 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62813.980 | -999.000 | 5.507388 | 0.00179644 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2528 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.507388 | 6.32554257 | 4197.9300 | 999.8980 | 26.65073957 | 15.03 | 6.70 | 8.33 | 931943.23 | 6.7401 | 6.739982 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | unknown | unknown | unknown | 7/21 19:00:00 | Sensible | 62813.98 | 58393.91 | 1.0000 | 6.32554257 | 5.507388 | 21.71 | 15.38 | 0.00882906 | 44252.4 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 1.79625507 | 6.70 | 15.03 | 8.33 | 0.000 | 62813.98 | 27.07 | 0.01535744 | 22.00 | 0.00000000 | 0.0000 | 21.11 | 0.00882906 | 21.11 | 0.00882906 | 54.0027 | 53651.32 | 0.00 | 65777.16 | 62759.45 | 6.32554257 | 21.71 | 15.85 | 0.00882906 | 44252.4 | 11.99 | 11.91 | 0.00863999 | 33853.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 45164.490 | 45164.490 | 2.041490 | 0.00039512 | 1290.473 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.507388 | 6.32554257 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 7.0245 | 7.165822 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 45164.49 | 45164.49 | 1.0000 | 2.34476500 | 2.041490 | 21.11 | 14.22 | 0.00776630 | 40940.5 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.39507836 | 60.00 | 32.22 | 27.78 | 0.000 | 45164.49 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00776630 | 21.11 | 0.00776630 | 47.5815 | 45164.49 | 0.00 | 48688.55 | 48688.55 | 2.34476500 | 16.60 | 12.92 | 0.00776630 | 36343.0 | 36.97 | 20.09 | 0.00776630 | 57107.8 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11148.940 | -999.000 | 1.027323 | 0.00031885 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9004 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.027323 | 1.17993830 | 4197.9300 | 999.8980 | 26.65073957 | 15.03 | 6.70 | 8.33 | 931943.23 | 1.1963 | 1.196289 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | unknown | unknown | 7/21 09:50:00 | Sensible | 11148.94 | 10802.38 | 1.0000 | 1.17993830 | 1.027323 | 21.71 | 15.21 | 0.00863947 | 43770.9 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.31881980 | 6.70 | 15.03 | 8.33 | 0.000 | 11148.94 | 26.87 | 0.01535708 | 21.94 | 0.00000000 | 0.0000 | 21.11 | 0.00863947 | 21.11 | 0.00863947 | 52.8586 | 10008.03 | 0.00 | 11686.57 | 11686.57 | 1.17993830 | 21.71 | 15.69 | 0.00863947 | 43770.9 | 12.01 | 11.91 | 0.00863947 | 33866.6 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7847.685 | 7847.685 | 0.354715 | 0.00006865 | 224.231 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.027323 | 1.17993830 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 1.2206 | 1.245118 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7847.69 | 7847.69 | 1.0000 | 0.40740942 | 0.354715 | 21.11 | 14.20 | 0.00774701 | 40890.9 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.06864797 | 60.00 | 32.22 | 27.78 | 0.000 | 7847.69 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00774701 | 21.11 | 0.00774701 | 47.4664 | 7847.69 | 0.00 | 8459.94 | 8459.94 | 0.40740942 | 16.60 | 12.90 | 0.00774701 | 36294.2 | 36.97 | 20.08 | 0.00774701 | 57059.4 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10830.415 | -999.000 | 0.996818 | 0.00030974 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9084 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.996818 | 1.14490061 | 4197.9300 | 999.8980 | 26.65073957 | 15.03 | 6.70 | 8.33 | 931943.23 | 1.1621 | 1.162111 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | Sensible | 10830.42 | 10483.67 | 1.0000 | 1.14490061 | 0.996818 | 21.71 | 15.22 | 0.00864379 | 43781.9 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.30971113 | 6.70 | 15.03 | 8.33 | 0.000 | 10830.42 | 25.67 | 0.01535487 | 21.60 | 0.00000000 | 0.0000 | 21.11 | 0.00864379 | 21.11 | 0.00864379 | 52.8846 | 9710.84 | 0.00 | 11353.73 | 11353.73 | 1.14490061 | 21.71 | 15.69 | 0.00864379 | 43781.9 | 12.00 | 11.91 | 0.00864379 | 33865.1 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7866.639 | 7866.639 | 0.355571 | 0.00006882 | 224.773 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.996818 | 1.14490061 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 1.2235 | 1.248125 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7866.64 | 7866.64 | 1.0000 | 0.40839342 | 0.355571 | 21.11 | 14.20 | 0.00774762 | 40892.5 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.06881377 | 60.00 | 32.22 | 27.78 | 0.000 | 7866.64 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00774762 | 21.11 | 0.00774762 | 47.4701 | 7866.64 | 0.00 | 8480.37 | 8480.37 | 0.40839342 | 16.60 | 12.90 | 0.00774762 | 36295.7 | 36.97 | 20.08 | 0.00774762 | 57061.0 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15955.734 | 15955.734 | 0.711652 | 0.00013959 | 407.224 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 2.4816 | 2.531545 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 15955.73 | 15955.73 | 1.0000 | 0.81737228 | 0.711652 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.13957348 | 60.00 | 32.22 | 27.78 | 0.000 | 15955.73 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00780335 | 21.00 | 0.00780335 | 48.1319 | 12373.17 | 0.00 | 16037.52 | 16037.52 | 0.81737228 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.84 | 19.92 | 0.00800000 | 56555.6 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3188.971 | -999.000 | 0.295343 | 0.00009120 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8654 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.295343 | 0.33921753 | 4197.9300 | 999.8980 | 26.65073957 | 15.03 | 6.70 | 8.33 | 931943.23 | 0.3422 | 0.342179 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3188.97 | 3102.86 | 1.0000 | 0.33921753 | 0.295343 | 21.71 | 15.20 | 0.00862066 | 43723.2 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.09119317 | 6.70 | 15.03 | 8.33 | 0.000 | 3188.97 | 29.72 | 0.01536233 | 22.73 | 0.00000000 | 0.0000 | 21.11 | 0.00862066 | 21.11 | 0.00862066 | 52.7450 | 2877.19 | 0.00 | 3343.29 | 3343.29 | 0.33921753 | 21.71 | 15.67 | 0.00862066 | 43723.2 | 12.06 | 11.91 | 0.00862066 | 33867.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2430.264 | 2430.264 | 0.109848 | 0.00002126 | 69.438 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.295343 | 0.33921753 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 0.3780 | 0.385587 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2430.26 | 2430.26 | 1.0000 | 0.12616638 | 0.109848 | 21.11 | 14.24 | 0.00779440 | 41011.4 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.02125884 | 60.00 | 32.22 | 27.78 | 0.000 | 2430.26 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00779440 | 21.11 | 0.00779440 | 47.7531 | 2430.26 | 0.00 | 2619.87 | 2619.87 | 0.12616638 | 16.60 | 12.95 | 0.00779440 | 36414.2 | 36.97 | 20.12 | 0.00779440 | 57179.4 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3083.515 | -999.000 | 0.285267 | 0.00008819 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8728 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.285267 | 0.32764509 | 4197.9300 | 999.8980 | 26.65073957 | 15.03 | 6.70 | 8.33 | 931943.23 | 0.3309 | 0.330863 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 3083.51 | 2997.56 | 1.0000 | 0.32764509 | 0.285267 | 21.71 | 15.20 | 0.00862467 | 43733.3 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.08817749 | 6.70 | 15.03 | 8.33 | 0.000 | 3083.51 | 29.54 | 0.01536201 | 22.68 | 0.00000000 | 0.0000 | 21.11 | 0.00862467 | 21.11 | 0.00862467 | 52.7692 | 2779.03 | 0.00 | 3232.62 | 3232.62 | 0.32764509 | 21.71 | 15.67 | 0.00862467 | 43733.3 | 12.05 | 11.91 | 0.00862467 | 33867.1 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2437.295 | 2437.295 | 0.110166 | 0.00002132 | 69.639 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.285267 | 0.32764509 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 0.3791 | 0.386703 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2437.30 | 2437.30 | 1.0000 | 0.12653143 | 0.110166 | 21.11 | 14.25 | 0.00779500 | 41012.9 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.02132035 | 60.00 | 32.22 | 27.78 | 0.000 | 2437.30 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00779500 | 21.11 | 0.00779500 | 47.7567 | 2437.30 | 0.00 | 2627.45 | 2627.45 | 0.12653143 | 16.60 | 12.95 | 0.00779500 | 36415.7 | 36.97 | 20.12 | 0.00779500 | 57180.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14880.350 | -999.000 | 1.355136 | 0.00042557 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9822 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.355136 | 1.55644945 | 4197.9300 | 999.8980 | 26.65073957 | 15.03 | 6.70 | 8.33 | 931943.23 | 1.5967 | 1.596672 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 14880.35 | 14277.67 | 1.0000 | 1.55644945 | 1.355136 | 21.71 | 15.25 | 0.00868351 | 43882.6 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.42552477 | 6.70 | 15.03 | 8.33 | 0.000 | 14880.35 | 31.02 | 0.01536476 | 23.08 | 0.00000000 | 0.0000 | 21.11 | 0.00868351 | 21.11 | 0.00868351 | 53.1247 | 13201.29 | 0.00 | 15594.13 | 15594.13 | 1.55644945 | 21.71 | 15.73 | 0.00868351 | 43882.6 | 11.90 | 11.90 | 0.00868351 | 33863.6 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11599.966 | 11599.966 | 0.524324 | 0.00010148 | 331.435 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.355136 | 1.55644945 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 1.8041 | 1.840457 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11599.97 | 11599.97 | 1.0000 | 0.60221494 | 0.524324 | 21.11 | 14.25 | 0.00780147 | 41029.5 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.10147121 | 60.00 | 32.22 | 27.78 | 0.000 | 11599.97 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00780147 | 21.11 | 0.00780147 | 47.7953 | 11599.97 | 0.00 | 12505.01 | 12505.01 | 0.60221494 | 16.60 | 12.96 | 0.00780147 | 36432.1 | 36.97 | 20.12 | 0.00780147 | 57197.1 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17124.581 | 17124.581 | 1.782521 | 0.00014981 | 374.834 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 2.6634 | 2.716995 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 17124.58 | 17124.58 | 1.0000 | 2.04732451 | 1.782521 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.14979802 | 60.00 | 32.22 | 27.78 | 0.000 | 17124.58 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00784835 | 21.00 | 0.00784835 | 48.4066 | 8150.79 | 0.00 | 17219.37 | 17219.37 | 2.04732451 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.85 | 16.26 | 0.00800000 | 45345.4 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17294.413 | 17294.413 | 1.782235 | 0.00015130 | 378.952 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 2.6898 | 2.743941 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 17294.41 | 17294.41 | 1.0000 | 2.04699649 | 1.782235 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.15128363 | 60.00 | 32.22 | 27.78 | 0.000 | 17294.41 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00785141 | 21.00 | 0.00785141 | 48.4252 | 8322.01 | 0.00 | 17390.11 | 17390.11 | 2.04699649 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.93 | 16.29 | 0.00800000 | 45430.2 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6703.986 | 6703.986 | 0.551389 | 0.00005865 | 150.946 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 1.0427 | 1.063658 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 6703.99 | 6703.99 | 1.0000 | 0.63330066 | 0.551389 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.05864341 | 60.00 | 32.22 | 27.78 | 0.000 | 6703.99 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.74 | 0.00743695 | 21.00 | 0.00743695 | 45.9040 | 3931.30 | 0.00 | 6740.22 | 6740.22 | 0.63330066 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.04 | 17.03 | 0.00800000 | 47577.7 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10489.724 | 10489.724 | 0.384412 | 0.00009177 | 286.288 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 1.6315 | 1.664305 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 10489.72 | 10489.72 | 1.0000 | 0.44151893 | 0.384412 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.09175932 | 60.00 | 32.22 | 27.78 | 0.000 | 10489.72 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00787298 | 21.00 | 0.00787298 | 48.5562 | 8554.33 | 0.00 | 10541.74 | 10541.74 | 0.44151893 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60810.8 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 87803.637 | -999.000 | 2.051317 | 0.00251117 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1033.4029 | 1004.8586 | 1.1486 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.35596953 | 4197.9300 | 999.8980 | 26.65073957 | 15.03 | 6.70 | 8.33 | 931943.23 | 9.4216 | 9.421565 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 87803.64 | 47531.07 | 1.0000 | 2.35605237 | 2.051317 | 31.20 | 23.13 | 0.01536508 | 70669.3 | 11.90 | 11.31 | 0.00850000 | 33402.1 | 2.51091675 | 6.70 | 15.03 | 8.33 | 2195.006 | 85608.63 | 31.20 | 0.01536508 | 23.13 | 2.05124512 | 99.9965 | 21.11 | 0.00868082 | 21.11 | 0.00868285 | 53.1196 | 163865.83 | 0.00 | 89691.54 | 48118.14 | 2.35605237 | 31.20 | 23.70 | 0.01536508 | 70669.3 | 11.44 | 11.40 | 0.00836907 | 32600.8 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 30469.718 | 30469.718 | 0.615395 | 0.00026656 | 443.506 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.35596953 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 4.7390 | 4.834342 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 30469.72 | 30469.72 | 1.0000 | 0.70681571 | 0.615395 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 0.26653519 | 60.00 | 32.22 | 27.78 | 0.000 | 30469.72 | -26.20 | 0.00036134 | -26.20 | 2.05124512 | 333.3216 | 21.11 | 0.00776549 | 21.11 | 0.00776567 | 47.5778 | 137943.64 | 0.00 | 22379.93 | 22379.93 | 0.70681571 | 2.80 | -3.86 | 0.00036134 | 3719.1 | 34.29 | 12.71 | 0.00036134 | 35382.2 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 644967.332 | -999.000 | 21.750443 | 0.01844598 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.4191 | 1004.8586 | 1.1486 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.750443 | 24.98159828 | 4197.9300 | 999.8980 | 26.65073957 | 15.03 | 6.70 | 8.33 | 931943.23 | 69.2067 | 69.206719 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 644967.33 | 412720.22 | 1.0000 | 24.98159828 | 21.750443 | 27.08 | 19.77 | 0.01214617 | 58201.9 | 10.90 | 10.89 | 0.00850000 | 32384.2 | 18.44410237 | 6.70 | 15.03 | 8.33 | 48734.883 | 596232.45 | 31.20 | 0.01536508 | 23.13 | 9.32920000 | 42.8920 | 23.99 | 0.00972733 | 23.99 | 0.00972335 | 49.8517 | 285252.50 | 0.00 | 663144.00 | 411525.99 | 24.98159828 | 27.08 | 20.31 | 0.01214617 | 58201.9 | 11.05 | 11.01 | 0.00815164 | 31656.6 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 323075.270 | 323075.270 | 6.525133 | 0.00282640 | 4702.563 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.750443 | 24.98159828 | 4197.9300 | 999.8980 | 5.51337077 | 54.44 | 82.22 | 27.78 | 642961.00 | 50.2480 | 51.259297 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 323075.27 | 323075.27 | 1.0000 | 7.49447948 | 6.525133 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 2.82611508 | 60.00 | 32.22 | 27.78 | 0.000 | 323075.27 | -26.20 | 0.00036134 | -26.20 | 9.32920000 | 142.9733 | 20.96 | 0.00778928 | 21.00 | 0.00778034 | 47.9922 | 82732.76 | 0.00 | 237297.98 | 237297.98 | 7.49447948 | 2.80 | -3.86 | 0.00036134 | 3719.1 | 34.29 | 12.71 | 0.00036134 | 35382.2 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 21.75 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 482.17 | 7936.17 | 355.67 |
RETAIL_1_FLR_1 | 4479.17 | 6342.00 | 2641.00 |
RETAIL_2_FLR_1 | 1448.50 | 7696.17 | 952.67 |
MECH_FLR_1 | 2402.00 | 5701.00 | 754.00 |
STORAGE_FLR_1 | 2074.50 | 8760.00 | 2074.50 |
LAUNDRY_FLR_1 | 8698.67 | 3723.17 | 3723.17 |
CAFE_FLR_1 | 2434.33 | 7344.67 | 1571.17 |
LOBBY_FLR_1 | 1719.67 | 7275.67 | 1048.33 |
ROOM_1_FLR_3 | 2961.83 | 8237.17 | 2879.00 |
ROOM_2_FLR_3 | 3851.50 | 8024.00 | 3563.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2555.83 | 8714.00 | 2543.33 |
ROOM_5_FLR_3 | 2866.00 | 8176.67 | 2841.00 |
ROOM_6_FLR_3 | 3673.33 | 7973.67 | 3450.33 |
CORRIDOR_FLR_3 | 1933.83 | 8413.17 | 1902.50 |
ROOM_1_FLR_6 | 3543.83 | 8146.17 | 3367.17 |
ROOM_2_FLR_6 | 4429.67 | 7971.50 | 4104.33 |
ROOM_3_MULT9_FLR_6 | 2381.00 | 8167.67 | 2329.17 |
BANQUET_FLR_6 | 2034.17 | 6908.00 | 1031.67 |
DINING_FLR_6 | 2673.67 | 6032.67 | 899.67 |
KITCHEN_FLR_6 | 8616.17 | 6056.00 | 5997.17 |
CORRIDOR_FLR_6 | 3993.17 | 6352.83 | 2191.50 |
Facility | 8760.00 | 8760.00 | 8047.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 44.50 | 0.00 | 44.50 | 0.00 |
RETAIL_1_FLR_1 | 96.83 | 0.00 | 96.83 | 0.00 |
RETAIL_2_FLR_1 | 86.50 | 0.00 | 86.50 | 0.00 |
MECH_FLR_1 | 92.33 | 0.00 | 92.33 | 0.00 |
STORAGE_FLR_1 | 193.00 | 0.00 | 193.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 56.17 | 0.00 | 56.17 | 0.00 |
LOBBY_FLR_1 | 49.00 | 0.00 | 49.00 | 0.00 |
ROOM_1_FLR_3 | 40.33 | 7.83 | 40.33 | 7.83 |
ROOM_2_FLR_3 | 78.00 | 8.33 | 78.00 | 8.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 151.17 | 23.17 | 151.17 | 23.17 |
ROOM_5_FLR_3 | 56.00 | 0.00 | 56.00 | 0.00 |
ROOM_6_FLR_3 | 91.83 | 19.67 | 91.83 | 19.67 |
CORRIDOR_FLR_3 | 69.67 | 0.00 | 69.67 | 0.00 |
ROOM_1_FLR_6 | 72.00 | 12.00 | 72.00 | 12.00 |
ROOM_2_FLR_6 | 116.67 | 14.83 | 116.67 | 14.83 |
ROOM_3_MULT9_FLR_6 | 22.50 | 7.33 | 22.50 | 7.33 |
BANQUET_FLR_6 | 56.50 | 0.00 | 56.50 | 0.00 |
DINING_FLR_6 | 43.33 | 0.00 | 43.33 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 117.00 | 0.00 | 117.00 | 0.00 |
Facility | 227.67 | 51.67 | 227.67 | 51.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.74 | 106.50 | 4826.41 | 0.715 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.339 | 0.063 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.196 | 0.021 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.117 | 0.024 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.614 | 0.024 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 15.531 | 0.068 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 3.623 | 0.050 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.88 | 422.44 | 5183.56 | 1.473 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.342 | 0.082 | 0.000 | 0.056 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.082 | 0.000 | 0.047 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.388 | 0.036 | 0.000 | 0.085 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.342 | 0.082 | 0.000 | 0.056 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.082 | 0.000 | 0.053 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.400 | 0.010 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.342 | 0.082 | 0.000 | 0.067 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.342 | 0.082 | 0.000 | 0.053 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.389 | 0.067 | 0.000 | 0.107 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.725 | 0.024 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.748 | 0.024 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 15.534 | 0.068 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.473 | 0.017 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.74 | 106.50 | 4826.41 | 0.510 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.929 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.905 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.006 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.443 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 2.356 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 2.660 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.88 | 422.44 | 5183.56 | 1.144 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.289 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 3.611 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 3.672 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 4.129 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.312 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.74 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.49 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.88 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.86 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.86 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.89 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.55 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 29650695.65 | 0.00 | 29650695.65 | 0.00 | 29650695.65 | 26946214.98 | 5357.42 | 138.66 | 3263.92 | 0.00 |
RETAIL_1_FLR_1 | 3059983.03 | 0.00 | 3059983.03 | 145101.77 | 3205084.79 | 2498216.28 | 4592.65 | 78.04 | 4089.31 | 0.00 |
RETAIL_2_FLR_1 | 3168537.56 | 0.00 | 3168537.56 | 56009.47 | 3224547.03 | 2892943.94 | 5532.37 | 119.10 | 3108.54 | 0.00 |
MECH_FLR_1 | 649497.85 | 0.00 | 649497.85 | 132373.10 | 781870.95 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1990872.12 | 0.00 | 1990872.12 | 76371.99 | 2067244.11 | 1821682.01 | 5538.08 | 116.05 | 3105.87 | 0.00 |
LAUNDRY_FLR_1 | 41142131.92 | 0.00 | 41142131.92 | 180748.71 | 41322880.63 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23347260.66 | 0.00 | 23347260.66 | 320755.67 | 23668016.33 | 21330615.53 | 5506.24 | 120.43 | 3133.33 | 0.00 |
LOBBY_FLR_1 | 65605035.61 | 0.00 | 65605035.61 | 916472.22 | 66521507.83 | 59728886.00 | 5518.08 | 124.35 | 3117.58 | 0.00 |
ROOM_1_FLR_3 | 1406076.84 | 56896.43 | 1462973.27 | 84221.76 | 1547195.03 | 1946875.62 | 2433.17 | 5799.67 | 527.17 | 0.00 |
ROOM_2_FLR_3 | 1405912.09 | 47882.15 | 1453794.25 | 84215.33 | 1538009.58 | 1946647.51 | 2433.17 | 5886.71 | 440.13 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 583.60 | 1100495.56 | 23498.82 | 1123994.38 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 369.17 |
ROOM_4_MULT19_FLR_3 | 19070354.14 | 54429.92 | 19124784.06 | 23505.24 | 19148289.30 | 26405105.73 | 2433.33 | 5809.13 | 517.54 | 0.00 |
ROOM_5_FLR_3 | 1406076.84 | 56993.86 | 1463070.69 | 84221.76 | 1547292.45 | 1946875.62 | 2433.17 | 5799.67 | 527.17 | 0.00 |
ROOM_6_FLR_3 | 1405912.09 | 53878.72 | 1459790.81 | 84215.33 | 1544006.15 | 1946647.51 | 2433.17 | 5801.52 | 525.31 | 0.00 |
CORRIDOR_FLR_3 | 16352121.40 | 0.00 | 16352121.40 | 101841.05 | 16453962.45 | 14972100.18 | 5544.29 | 113.50 | 3102.20 | 0.00 |
ROOM_1_FLR_6 | 351519.21 | 68661.62 | 420180.83 | 84239.76 | 504420.59 | 486718.90 | 2251.75 | 5800.25 | 707.99 | 0.00 |
ROOM_2_FLR_6 | 351478.02 | 53370.99 | 404849.01 | 84233.33 | 489082.35 | 486661.88 | 2284.04 | 5920.36 | 555.60 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2258331.41 | 68597.92 | 2326929.33 | 43100.01 | 2370029.34 | 3126920.42 | 2433.33 | 5798.83 | 527.83 | 0.00 |
BANQUET_FLR_6 | 41080653.69 | 0.00 | 41080653.69 | 205692.33 | 41286346.01 | 37458366.31 | 5525.06 | 121.15 | 3113.79 | 0.00 |
DINING_FLR_6 | 41237037.10 | 0.00 | 41237037.10 | 205692.33 | 41442729.43 | 37458366.31 | 5500.49 | 122.68 | 3136.83 | 0.00 |
KITCHEN_FLR_6 | 41814450.28 | 0.00 | 41814450.28 | 184142.32 | 41998592.60 | 11584760.86 | 1.56 | 31.01 | 8727.43 | 0.00 |
CORRIDOR_FLR_6 | 5105483.56 | 0.00 | 5105483.56 | 180228.23 | 5285711.79 | 3961413.96 | 4552.22 | 54.68 | 4153.10 | 0.00 |
Total Facility | 0.19E+10 | 5783045.90 | 0.19E+10 | 8487130.57 | 0.20E+10 | 0.43E+10 | 8760.00 | 6324.28 | 8760.00 | 369.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9402 | 0.0000 | 0.9402 | 0.0000 | 0.9402 | 0.8545 | 5357.42 | 138.66 | 3263.92 |
RETAIL_1_FLR_1 | 0.0970 | 0.0000 | 0.0970 | 0.0046 | 0.1016 | 0.0792 | 4592.65 | 78.04 | 4089.31 |
RETAIL_2_FLR_1 | 0.1005 | 0.0000 | 0.1005 | 0.0018 | 0.1022 | 0.0917 | 5532.37 | 119.10 | 3108.54 |
MECH_FLR_1 | 0.0206 | 0.0000 | 0.0206 | 0.0042 | 0.0248 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0631 | 0.0000 | 0.0631 | 0.0024 | 0.0656 | 0.0578 | 5538.08 | 116.05 | 3105.87 |
LAUNDRY_FLR_1 | 1.3046 | 0.0000 | 1.3046 | 0.0057 | 1.3103 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7403 | 0.0000 | 0.7403 | 0.0102 | 0.7505 | 0.6764 | 5506.24 | 120.43 | 3133.33 |
LOBBY_FLR_1 | 2.0803 | 0.0000 | 2.0803 | 0.0291 | 2.1094 | 1.8940 | 5518.08 | 124.35 | 3117.58 |
ROOM_1_FLR_3 | 0.0446 | 0.0018 | 0.0464 | 0.0027 | 0.0491 | 0.0617 | 2433.17 | 5799.67 | 527.17 |
ROOM_2_FLR_3 | 0.0446 | 0.0015 | 0.0461 | 0.0027 | 0.0488 | 0.0617 | 2433.17 | 5886.71 | 440.13 |
ROOM_4_MULT19_FLR_3 | 0.6047 | 0.0017 | 0.6064 | 0.0007 | 0.6072 | 0.8373 | 2433.33 | 5809.13 | 517.54 |
ROOM_5_FLR_3 | 0.0446 | 0.0018 | 0.0464 | 0.0027 | 0.0491 | 0.0617 | 2433.17 | 5799.67 | 527.17 |
ROOM_6_FLR_3 | 0.0446 | 0.0017 | 0.0463 | 0.0027 | 0.0490 | 0.0617 | 2433.17 | 5801.52 | 525.31 |
CORRIDOR_FLR_3 | 0.5185 | 0.0000 | 0.5185 | 0.0032 | 0.5218 | 0.4748 | 5544.29 | 113.50 | 3102.20 |
ROOM_1_FLR_6 | 0.0111 | 0.0022 | 0.0133 | 0.0027 | 0.0160 | 0.0154 | 2251.75 | 5800.25 | 707.99 |
ROOM_2_FLR_6 | 0.0111 | 0.0017 | 0.0128 | 0.0027 | 0.0155 | 0.0154 | 2284.04 | 5920.36 | 555.60 |
ROOM_3_MULT9_FLR_6 | 0.0716 | 0.0022 | 0.0738 | 0.0014 | 0.0752 | 0.0992 | 2433.33 | 5798.83 | 527.83 |
BANQUET_FLR_6 | 1.3027 | 0.0000 | 1.3027 | 0.0065 | 1.3092 | 1.1878 | 5525.06 | 121.15 | 3113.79 |
DINING_FLR_6 | 1.3076 | 0.0000 | 1.3076 | 0.0065 | 1.3141 | 1.1878 | 5500.49 | 122.68 | 3136.83 |
KITCHEN_FLR_6 | 1.3259 | 0.0000 | 1.3259 | 0.0058 | 1.3318 | 0.3674 | 1.56 | 31.01 | 8727.43 |
CORRIDOR_FLR_6 | 0.1619 | 0.0000 | 0.1619 | 0.0057 | 0.1676 | 0.1256 | 4552.22 | 54.68 | 4153.10 |
Total Facility | 58.8575 | 0.1820 | 59.0395 | 0.2125 | 59.2520 | 73.9670 | 8760.00 | 6324.28 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 37933790.35 | 461295.22 | 38395085.57 | 64690340.46 | 8755.83 | 1.17 | 3.00 | 0.00 |
VAV WITH REHEAT | 0.41E+09 | 0.00 | 0.41E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.2029 | 0.0146 | 1.2175 | 2.0513 | 8755.83 | 1.17 | 3.00 |
VAV WITH REHEAT | 13.1434 | 0.0000 | 13.1434 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6691.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 33.65 | 4750.83 | 0.00 | 0.00 | 0.00 | 3975.53 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.5748 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 12.4480 | 15.0051 | 0.0000 | 0.0000 | 0.0000 | 10.9312 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1340 |
Defaulted Fields | 1182 |
Fields with Defaults | 4001 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4654.20 | 61180.57 | 20-MAY-05:00 | 356821.93 | 26-JUL-18:10 |
Electricity:Building | 2200.29 | 28674.42 | 03-JUN-05:00 | 132137.22 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 266.04 | 3144.96 | 02-JAN-02:10 | 19685.67 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2193.20 | 28533.27 | 03-JUN-05:00 | 131895.89 | 02-JAN-20:10 |
InteriorLights:Electricity | 544.74 | 4639.60 | 03-JUN-05:00 | 45764.37 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 122.93 | 1117.06 | 02-JAN-02:10 | 10053.14 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 544.74 | 4639.60 | 03-JUN-05:00 | 45764.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 544.74 | 4639.60 | 03-JUN-05:00 | 45764.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 122.93 | 1117.06 | 02-JAN-02:10 | 10053.14 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 544.74 | 4639.60 | 03-JUN-05:00 | 45764.37 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.91 | 71.95 | 02-JAN-02:10 | 430.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.31 | 20.97 | 02-JAN-02:10 | 188.71 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.31 | 20.97 | 02-JAN-02:10 | 188.71 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.08 | 270.72 | 17-JUN-05:00 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.74 | 67.51 | 17-JUN-05:00 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.74 | 67.51 | 17-JUN-05:00 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 240.98 | 2916.07 | 03-JUN-05:00 | 18013.24 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 91.98 | 804.66 | 03-JUN-05:00 | 7984.04 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 91.98 | 804.66 | 03-JUN-05:00 | 7984.04 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 253.77 | 3619.58 | 02-JAN-10:10 | 20179.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 253.84 | 3620.57 | 02-JAN-10:10 | 20185.51 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 3.85 | 55.20 | 01-JAN-02:10 | 290.10 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 3.85 | 55.19 | 01-JAN-02:10 | 290.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.06 | 428.75 | 02-JAN-10:10 | 2390.39 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 203.97 | 2433.51 | 03-JUN-05:00 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.11 | 184.21 | 03-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.11 | 184.21 | 03-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 203.97 | 2433.51 | 03-JUN-05:00 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.11 | 184.21 | 03-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.11 | 184.21 | 03-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.99 | 732.80 | 05-JAN-23:30 | 2790.29 | 16-JUL-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 761.20 | 2481.80 | 25-MAR-00:10 | 190536.64 | 04-AUG-15:40 |
LowTempRefrigeration:Refrigeration:Electricity | 15.82 | 0.00 | 01-JAN-11:10 | 1307.26 | 02-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 21.07 | 598.26 | 03-FEB-04:40 | 716.19 | 25-AUG-13:40 |
Fans:Electricity | 567.87 | 12233.95 | 19-JAN-11:00 | 33856.37 | 26-JUN-21:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 707.01 | 13280.72 | 09-NOV-05:00 | 42943.18 | 26-JUN-21:20 |
ExteriorEquipment:Electricity | 813.52 | 9997.87 | 02-JAN-02:20 | 49590.83 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.51 | 379.01 | 17-JUN-05:00 | 1274.03 | 03-JAN-08:00 |
ElectricityPurchased:Facility | 4654.20 | 61180.57 | 20-MAY-05:00 | 356821.93 | 26-JUL-18:10 |
ElectricityPurchased:Plant | 4654.20 | 61180.57 | 20-MAY-05:00 | 356821.93 | 26-JUL-18:10 |
Cogeneration:ElectricityPurchased | 4654.20 | 61180.57 | 20-MAY-05:00 | 356821.93 | 26-JUL-18:10 |
General:Cogeneration:ElectricityPurchased | 4654.20 | 61180.57 | 20-MAY-05:00 | 356821.93 | 26-JUL-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4654.20 | 61180.57 | 20-MAY-05:00 | 356821.93 | 26-JUL-18:10 |
ElectricityNet:Plant | 4654.20 | 61180.57 | 20-MAY-05:00 | 356821.93 | 26-JUL-18:10 |
Cogeneration:ElectricityNet | 4654.20 | 61180.57 | 20-MAY-05:00 | 356821.93 | 26-JUL-18:10 |
General:Cogeneration:ElectricityNet | 4654.20 | 61180.57 | 20-MAY-05:00 | 356821.93 | 26-JUL-18:10 |
General:Fans:Electricity | 567.87 | 12233.95 | 19-JAN-11:00 | 33856.37 | 26-JUN-21:20 |
ExteriorLights:Electricity | 193.69 | 0.00 | 01-JAN-08:00 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.69 | 0.00 | 01-JAN-08:00 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 117.63 | 0.00 | 12-JAN-11:20 | 8265.52 | 01-JAN-00:10 |
General:HeatRecovery:Electricity | 117.63 | 0.00 | 12-JAN-11:20 | 8265.52 | 01-JAN-00:10 |
WaterSystems:Electricity | 94.78 | 1222.48 | 06-JUL-02:20 | 4752.06 | 02-FEB-07:10 |
Water Heater:WaterSystems:Electricity | 94.78 | 1222.48 | 06-JUL-02:20 | 4752.06 | 02-FEB-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 549.99 | 0.00 | 01-JAN-00:30 | 183070.16 | 04-AUG-15:40 |
General:Cooling:Electricity | 549.99 | 0.00 | 01-JAN-00:30 | 183070.16 | 04-AUG-15:40 |
Pumps:Electricity | 79.54 | 47.91 | 11-APR-07:10 | 4462.44 | 30-JAN-16:40 |
General:Pumps:Electricity | 79.54 | 47.91 | 11-APR-07:10 | 4462.44 | 30-JAN-16:40 |
WIRED_LTG_ELECTRICITY | 19.17 | 0.00 | 01-JAN-00:10 | 1610.91 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 6374.84 | 25767.82 | 23-AUG-02:30 | 959733.38 | 02-FEB-19:20 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4586.00 | 12405.92 | 23-AUG-02:30 | 883750.47 | 02-FEB-21:20 |
WaterSystems:NaturalGas | 2901.93 | 12405.92 | 23-AUG-02:30 | 269511.10 | 21-FEB-21:40 |
Water Heater:WaterSystems:NaturalGas | 2901.93 | 12405.92 | 23-AUG-02:30 | 269511.10 | 21-FEB-21:40 |
Heating:NaturalGas | 1684.07 | 0.00 | 19-MAR-19:20 | 651679.50 | 02-FEB-06:00 |
Boiler:Heating:NaturalGas | 1684.07 | 0.00 | 19-MAR-19:20 | 651679.50 | 02-FEB-06:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2242.55 | 0.00 | 01-JAN-00:30 | 590864.59 | 26-JUL-18:20 |
PlantLoopCoolingDemand:HVAC | 2242.55 | 0.00 | 01-JAN-00:30 | 590864.59 | 26-JUL-18:20 |
CoolingCoils:PlantLoopCoolingDemand | 2242.55 | 0.00 | 01-JAN-00:30 | 590864.59 | 26-JUL-18:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:50 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:50 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:50 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:50 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:50 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:50 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 17848.57 | 126642.02 | 29-SEP-14:00 | 2475108.86 | 26-JUL-18:20 |
EnergyTransfer:Building | 4769.38 | 73682.19 | 06-FEB-11:10 | 334873.96 | 26-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 678.87 | 7629.06 | 10-DEC-04:00 | 35303.24 | 02-JUL-10:40 |
Refrigeration:EnergyTransfer | 183.29 | 3939.08 | 03-FEB-02:30 | 10368.99 | 12-SEP-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.64 | 1969.54 | 03-FEB-02:30 | 5184.49 | 12-SEP-06:30 |
General:Refrigeration:EnergyTransfer | 91.64 | 1969.54 | 03-FEB-02:30 | 5184.49 | 12-SEP-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.64 | 1969.54 | 03-FEB-02:30 | 5184.49 | 12-SEP-06:30 |
EnergyTransfer:Plant | 7314.35 | 19210.25 | 21-SEP-15:10 | 1390894.02 | 26-JUL-18:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.60 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 70.04 | 1732.84 | 03-FEB-04:40 | 2556.02 | 25-AUG-13:40 |
EnergyTransfer:Zone:BASEMENT | 358.06 | 2077.15 | 04-FEB-11:10 | 20819.71 | 26-NOV-07:00 |
Heating:EnergyTransfer | 339.94 | 0.00 | 13-JAN-11:20 | 113951.65 | 12-DEC-16:30 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 339.94 | 0.00 | 13-JAN-11:20 | 113951.65 | 12-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4337.79 | 53222.10 | 11-DEC-15:00 | 331264.63 | 26-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 358.06 | 2077.15 | 04-FEB-11:10 | 20819.71 | 26-NOV-07:00 |
General:Cooling:EnergyTransfer | 4337.79 | 53222.10 | 11-DEC-15:00 | 331264.63 | 26-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 358.06 | 2077.15 | 04-FEB-11:10 | 20819.71 | 26-NOV-07:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 32.28 | 0.02 | 22-APR-02:30 | 4473.07 | 07-SEP-12:50 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 4.10 | 0.00 | 01-JAN-10:20 | 2069.35 | 20-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 4.10 | 0.00 | 01-JAN-10:20 | 2069.35 | 20-JAN-07:50 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 28.18 | 0.00 | 01-JAN-00:10 | 4473.07 | 07-SEP-12:50 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 28.18 | 0.00 | 01-JAN-00:10 | 4473.07 | 07-SEP-12:50 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.80 | 1.34 | 12-DEC-12:00 | 1855.93 | 30-JUN-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 467.20 | 04-FEB-11:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 467.20 | 04-FEB-11:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.80 | 0.00 | 06-JAN-10:40 | 1855.93 | 30-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.80 | 0.00 | 06-JAN-10:40 | 1855.93 | 30-JUN-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 8.68 | 0.07 | 17-FEB-17:30 | 1512.21 | 26-JUN-21:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 1.52 | 0.00 | 01-JAN-00:10 | 1223.87 | 04-FEB-11:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 1.52 | 0.00 | 01-JAN-00:10 | 1223.87 | 04-FEB-11:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 7.16 | 0.00 | 01-JAN-14:40 | 1512.21 | 26-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 7.16 | 0.00 | 01-JAN-14:40 | 1512.21 | 26-JUN-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 15.09 | 0.00 | 13-NOV-10:10 | 971.66 | 02-JUL-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 2.48 | 0.00 | 01-JAN-21:00 | 957.43 | 04-FEB-11:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 2.48 | 0.00 | 01-JAN-21:00 | 957.43 | 04-FEB-11:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 12.62 | 0.00 | 01-JAN-00:10 | 971.66 | 02-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 12.62 | 0.00 | 01-JAN-00:10 | 971.66 | 02-JUL-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 578.51 | 6745.20 | 04-FEB-06:00 | 39154.79 | 26-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 578.51 | 6745.20 | 04-FEB-06:00 | 39154.79 | 26-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 578.51 | 6745.20 | 04-FEB-06:00 | 39154.79 | 26-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 225.62 | 0.47 | 26-JAN-08:30 | 13901.61 | 07-SEP-13:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.24 | 0.00 | 01-JAN-00:10 | 2350.78 | 12-DEC-14:50 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.24 | 0.00 | 01-JAN-00:10 | 2350.78 | 12-DEC-14:50 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 225.39 | 0.00 | 15-JAN-15:30 | 13901.61 | 07-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 225.39 | 0.00 | 15-JAN-15:30 | 13901.61 | 07-SEP-13:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 741.12 | 2131.39 | 12-DEC-14:50 | 37937.22 | 07-SEP-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 114.16 | 04-FEB-11:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 114.16 | 04-FEB-11:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 741.12 | 2131.39 | 12-DEC-14:50 | 37937.22 | 07-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 741.12 | 2131.39 | 12-DEC-14:50 | 37937.22 | 07-SEP-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 67.52 | 0.00 | 01-JAN-08:00 | 11352.15 | 06-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 29.09 | 0.00 | 01-JAN-08:00 | 7478.36 | 09-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 29.09 | 0.00 | 01-JAN-08:00 | 7478.36 | 09-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 38.42 | 0.00 | 01-JAN-00:10 | 11352.15 | 06-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 38.42 | 0.00 | 01-JAN-00:10 | 11352.15 | 06-SEP-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 62.81 | 0.00 | 01-JAN-08:00 | 11672.91 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 34.91 | 0.00 | 01-JAN-08:00 | 7459.71 | 09-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 34.91 | 0.00 | 01-JAN-08:00 | 7459.71 | 09-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 27.90 | 0.00 | 01-JAN-00:10 | 11672.91 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 27.90 | 0.00 | 01-JAN-00:10 | 11672.91 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 221.74 | 0.00 | 01-JAN-08:10 | 50812.43 | 07-SEP-13:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 19.51 | 0.00 | 01-JAN-08:10 | 26431.86 | 19-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 19.51 | 0.00 | 01-JAN-08:10 | 26431.86 | 19-JAN-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 202.23 | 0.00 | 01-JAN-00:10 | 50812.43 | 07-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 202.23 | 0.00 | 01-JAN-00:10 | 50812.43 | 07-SEP-13:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 356.79 | 0.00 | 01-JAN-08:00 | 68163.52 | 26-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 107.84 | 0.00 | 01-JAN-08:00 | 45178.84 | 03-FEB-11:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 107.84 | 0.00 | 01-JAN-08:00 | 45178.84 | 03-FEB-11:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 248.95 | 0.00 | 01-JAN-00:10 | 68163.52 | 26-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 248.95 | 0.00 | 01-JAN-00:10 | 68163.52 | 26-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 66.68 | 0.00 | 01-JAN-08:00 | 10648.93 | 02-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 29.11 | 0.00 | 01-JAN-08:00 | 7284.28 | 09-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 29.11 | 0.00 | 01-JAN-08:00 | 7284.28 | 09-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 37.57 | 0.00 | 01-JAN-00:10 | 10648.93 | 02-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 37.57 | 0.00 | 01-JAN-00:10 | 10648.93 | 02-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 62.53 | 0.00 | 01-JAN-08:00 | 11614.46 | 09-JUN-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 34.98 | 0.00 | 01-JAN-08:00 | 7312.66 | 04-FEB-16:40 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 34.98 | 0.00 | 01-JAN-08:00 | 7312.66 | 04-FEB-16:40 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 27.55 | 0.00 | 01-JAN-00:10 | 11614.46 | 09-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 27.55 | 0.00 | 01-JAN-00:10 | 11614.46 | 09-JUN-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 138.35 | 0.13 | 04-DEC-11:00 | 9012.81 | 02-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 9.90 | 0.00 | 01-JAN-00:10 | 6594.55 | 04-FEB-11:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 9.90 | 0.00 | 01-JAN-00:10 | 6594.55 | 04-FEB-11:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 128.45 | 0.00 | 01-JAN-05:20 | 9012.81 | 02-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 128.45 | 0.00 | 01-JAN-05:20 | 9012.81 | 02-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 20.26 | 0.00 | 01-JAN-08:00 | 3110.48 | 04-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.70 | 0.00 | 01-JAN-08:00 | 2241.79 | 09-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.70 | 0.00 | 01-JAN-08:00 | 2241.79 | 09-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.56 | 0.00 | 01-JAN-00:10 | 3110.48 | 04-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.56 | 0.00 | 01-JAN-00:10 | 3110.48 | 04-AUG-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 19.60 | 0.00 | 01-JAN-08:00 | 3104.39 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.52 | 0.00 | 01-JAN-08:00 | 2404.97 | 02-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.52 | 0.00 | 01-JAN-08:00 | 2404.97 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.08 | 0.00 | 01-JAN-00:10 | 3104.39 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.08 | 0.00 | 01-JAN-00:10 | 3104.39 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 89.28 | 0.00 | 01-JAN-08:00 | 15510.23 | 06-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 30.97 | 0.00 | 01-JAN-08:00 | 10441.05 | 09-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 30.97 | 0.00 | 01-JAN-08:00 | 10441.05 | 09-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 58.31 | 0.00 | 01-JAN-00:10 | 15510.23 | 06-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 58.31 | 0.00 | 01-JAN-00:10 | 15510.23 | 06-SEP-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 453.61 | 2950.96 | 31-JAN-11:30 | 21389.11 | 26-JUN-22:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 483.92 | 04-FEB-11:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 483.92 | 04-FEB-11:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 453.61 | 2491.14 | 31-JAN-11:30 | 21389.11 | 26-JUN-22:00 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 453.61 | 2491.14 | 31-JAN-11:30 | 21389.11 | 26-JUN-22:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 479.55 | 4148.28 | 31-JAN-11:30 | 22830.50 | 26-JUN-21:30 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 219.16 | 31-JAN-11:30 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 219.16 | 31-JAN-11:30 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 479.55 | 3929.12 | 31-JAN-11:30 | 22830.50 | 26-JUN-21:30 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 479.55 | 3929.12 | 31-JAN-11:30 | 22830.50 | 26-JUN-21:30 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 587.23 | 5340.17 | 10-DEC-04:00 | 30221.27 | 02-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 587.23 | 5340.17 | 10-DEC-04:00 | 30221.27 | 02-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 59.59 | 0.00 | 13-JAN-04:50 | 6580.05 | 07-SEP-13:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 12.06 | 0.00 | 01-JAN-10:30 | 4910.12 | 04-FEB-11:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 12.06 | 0.00 | 01-JAN-10:30 | 4910.12 | 04-FEB-11:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 47.53 | 0.00 | 01-JAN-00:10 | 6580.05 | 07-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 47.53 | 0.00 | 01-JAN-00:10 | 6580.05 | 07-SEP-13:20 |
PlantLoopHeatingDemand:Facility | 2075.30 | 10271.17 | 21-AUG-00:20 | 585383.53 | 02-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 864.96 | 10271.17 | 21-AUG-00:20 | 64708.90 | 21-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 864.96 | 10271.17 | 21-AUG-00:20 | 64708.90 | 21-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 864.96 | 10271.17 | 21-AUG-00:20 | 64708.90 | 21-FEB-07:10 |
EnergyTransfer:HVAC | 5764.84 | 0.00 | 11-APR-07:10 | 784348.21 | 26-JUL-18:20 |
HeatingCoils:EnergyTransfer | 1210.34 | 0.00 | 19-MAR-19:20 | 527598.12 | 02-FEB-06:00 |
PlantLoopHeatingDemand:HVAC | 1210.34 | 0.00 | 19-MAR-19:20 | 527598.12 | 02-FEB-06:00 |
HeatingCoils:PlantLoopHeatingDemand | 1210.34 | 0.00 | 19-MAR-19:20 | 527598.12 | 02-FEB-06:00 |
CoolingCoils:EnergyTransfer | 2242.55 | 0.00 | 01-JAN-00:30 | 590864.59 | 26-JUL-18:20 |
HeatRecoveryForHeating:EnergyTransfer | 2171.63 | 0.00 | 05-JAN-08:00 | 415687.29 | 05-JAN-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 140.33 | 0.00 | 01-JAN-00:10 | 194514.50 | 04-AUG-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 864.96 | 10271.17 | 21-AUG-00:20 | 64708.90 | 21-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 864.96 | 10271.17 | 21-AUG-00:20 | 64708.90 | 21-FEB-07:10 |
Boilers:EnergyTransfer | 1200.70 | 0.00 | 19-MAR-19:20 | 525437.76 | 02-FEB-06:00 |
Chillers:EnergyTransfer | 2303.53 | 0.00 | 01-JAN-00:30 | 593194.78 | 26-JUL-18:20 |
HeatRejection:EnergyTransfer | 2853.52 | 0.00 | 01-JAN-00:30 | 761100.25 | 26-JUL-18:20 |
General:HeatRejection:EnergyTransfer | 2853.52 | 0.00 | 01-JAN-00:30 | 761100.25 | 26-JUL-18:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -358.066 | 0.000 | 0.000 | 143.920 | 122.932 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -51.892 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 4.104 | -28.176 | 0.000 | 0.000 | 15.183 | 6.265 | 10.186 | 23.606 | 0.000 | 0.034 | 0.000 | 0.000 | -13.965 | 0.000 | -2.815 | -14.421 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.003 | -32.799 | 0.000 | 0.000 | 17.500 | 7.255 | 11.795 | 0.000 | 0.000 | 0.018 | 0.000 | 0.000 | 0.000 | 0.000 | -1.083 | -2.689 |
MECH_FLR_1 | 0.000 | 0.000 | 1.516 | -7.159 | 0.000 | 0.000 | 3.550 | 8.366 | 12.471 | 0.000 | 0.000 | 0.031 | 0.000 | 0.000 | 0.000 | 0.000 | -2.669 | -16.106 |
STORAGE_FLR_1 | 0.000 | 0.000 | 2.476 | -12.616 | 0.000 | 0.000 | 2.982 | 2.308 | 3.598 | 0.000 | 0.000 | 0.032 | 2.640 | 0.000 | 0.000 | 0.000 | -1.419 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -578.518 | 0.000 | 0.000 | 10.551 | 4.900 | 658.131 | 0.000 | 0.000 | 0.042 | 0.000 | 0.000 | 0.000 | 0.000 | -3.880 | -91.226 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.235 | -225.389 | 0.000 | 0.000 | 201.649 | 12.739 | 14.341 | 67.016 | 0.000 | 0.113 | 0.000 | 0.000 | -39.084 | 0.000 | -6.127 | -25.491 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -741.127 | 0.000 | 0.000 | 575.867 | 91.981 | 148.998 | 88.007 | 0.000 | 0.299 | 0.000 | 0.000 | -53.621 | 0.000 | -18.083 | -92.321 |
ROOM_1_FLR_3 | 34.348 | -32.858 | 0.000 | -10.818 | 0.000 | 0.000 | 9.748 | 4.922 | 10.478 | 44.801 | 0.000 | 0.217 | 0.000 | 0.000 | -31.709 | 0.000 | -6.923 | -22.206 |
ROOM_2_FLR_3 | 40.425 | -22.142 | 0.000 | -11.273 | 0.000 | 0.000 | 9.628 | 4.922 | 10.477 | 31.552 | 0.000 | 0.138 | 0.000 | 0.000 | -33.650 | 0.000 | -7.229 | -22.848 |
ROOM_3_MULT19_FLR_3 | 19.505 | -190.234 | 0.010 | -11.997 | 0.000 | 0.000 | 0.000 | 58.777 | 194.997 | 271.487 | 0.000 | 0.129 | 0.000 | 0.000 | -186.889 | 0.000 | -37.204 | -118.580 |
ROOM_4_MULT19_FLR_3 | 165.487 | -156.967 | 0.000 | -149.608 | 0.000 | 0.000 | 183.991 | 58.793 | 195.050 | 79.635 | 0.000 | 1.014 | 0.000 | 0.000 | -190.706 | 0.000 | -49.641 | -137.047 |
ROOM_5_FLR_3 | 34.331 | -31.978 | 0.000 | -10.816 | 0.000 | 0.000 | 9.745 | 4.922 | 10.478 | 43.616 | 0.000 | 0.217 | 0.000 | 0.000 | -31.167 | 0.000 | -6.941 | -22.408 |
ROOM_6_FLR_3 | 40.501 | -21.865 | 0.000 | -11.208 | 0.000 | 0.000 | 9.659 | 4.922 | 10.477 | 30.192 | 0.000 | 0.139 | 0.000 | 0.000 | -32.864 | 0.000 | -7.295 | -22.658 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 9.901 | -128.454 | 0.000 | 0.000 | 119.691 | 56.739 | 0.000 | 39.756 | 0.000 | 0.121 | 0.000 | 0.000 | -40.702 | 0.000 | -7.741 | -49.313 |
ROOM_1_FLR_6 | 12.117 | -8.274 | 0.000 | -2.698 | 0.000 | 0.000 | 2.441 | 1.231 | 2.620 | 11.143 | 0.000 | 0.057 | 0.000 | 0.000 | -7.901 | 0.000 | -1.763 | -8.974 |
ROOM_2_FLR_6 | 13.973 | -5.714 | 0.000 | -2.820 | 0.000 | 0.000 | 2.408 | 1.230 | 2.619 | 7.842 | 0.000 | 0.035 | 0.000 | 0.000 | -8.403 | 0.000 | -1.828 | -9.341 |
ROOM_3_MULT9_FLR_6 | 38.339 | -48.185 | 0.000 | -17.495 | 0.000 | 0.000 | 21.852 | 6.962 | 23.098 | 61.510 | 0.000 | 0.367 | 0.000 | 0.000 | -36.726 | 0.000 | -9.101 | -40.620 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.001 | -453.614 | 0.000 | 0.000 | 342.767 | 28.112 | 175.857 | 8.863 | 0.000 | 0.076 | 0.000 | 0.000 | -23.433 | 0.000 | -4.050 | -74.579 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -479.556 | 0.000 | 0.000 | 336.980 | 28.112 | 175.857 | 8.614 | 0.000 | 0.070 | 0.000 | 0.000 | -24.099 | 0.000 | -4.113 | -41.865 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -587.217 | 0.000 | 0.000 | 27.991 | 13.339 | 540.650 | 20.790 | 0.000 | 0.041 | 4.807 | 0.000 | -16.433 | 0.000 | -3.968 | -0.003 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 12.063 | -47.530 | 0.000 | 0.000 | 30.773 | 15.012 | 0.000 | 19.317 | 0.000 | 0.040 | 0.000 | 0.000 | -18.537 | 0.000 | -3.532 | -7.608 |
Total Facility | 399.026 | -518.217 | 30.311 | -3908.952 | 0.000 | 0.000 | 2078.875 | 544.739 | 2355.282 | 857.744 | 0.000 | 3.231 | 7.448 | 0.000 | -789.890 | 0.000 | -187.405 | -872.195 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | -20819.69 | 0.00 | 0.00 | 5649.24 | 3351.05 | 4055.80 | 0.00 | 0.00 | 0.00 | 7763.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 07-SEP-12:50 | 0.00 | 0.00 | 0.00 | -4472.31 | 0.00 | 0.00 | 150.60 | 142.31 | 252.59 | 5562.95 | 0.00 | 37.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1673.23 |
RETAIL_2_FLR_1 | 30-JUN-21:00 | 0.00 | 0.00 | 0.00 | -1855.99 | 0.00 | 0.00 | 697.61 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3.54 | -117.57 |
MECH_FLR_1 | 26-JUN-21:00 | 0.00 | 0.00 | 0.00 | -1512.27 | 0.00 | 0.00 | 147.52 | 608.16 | 795.27 | 0.00 | 0.00 | 7.38 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -46.05 |
STORAGE_FLR_1 | 02-JUL-10:35 | 0.00 | 0.00 | 0.00 | -974.35 | 0.00 | 0.00 | 46.98 | 62.90 | 101.96 | 0.00 | 0.00 | 14.16 | 748.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 26-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39156.07 | 0.00 | 0.00 | 408.86 | 400.68 | 44299.38 | 0.00 | 0.00 | 16.95 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5969.80 |
CAFE_FLR_1 | 07-SEP-13:00 | 0.00 | 0.00 | 0.00 | -13898.80 | 0.00 | 0.00 | 1979.14 | 96.16 | 355.63 | 15406.18 | 0.00 | 83.96 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4022.27 |
LOBBY_FLR_1 | 07-SEP-21:10 | 0.00 | 0.00 | 0.00 | -37936.61 | 0.00 | 0.00 | 26440.26 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -664.07 | 0.00 | -50.34 | -501.89 |
ROOM_1_FLR_3 | 21-MAY-18:01 | 0.00 | -14692.50 | 0.00 | -551.35 | 0.00 | 0.00 | 283.22 | 378.87 | 484.65 | 6248.92 | 0.00 | 0.00 | 8456.43 | 0.00 | -0.00 | 0.00 | -608.24 | 0.00 |
ROOM_2_FLR_3 | 20-MAY-18:41 | 0.00 | -16224.40 | 0.00 | -652.43 | 0.00 | 0.00 | 243.47 | 378.82 | 484.60 | 2639.35 | 0.00 | 0.00 | 13263.26 | 0.00 | -0.00 | 0.00 | -132.66 | 0.00 |
ROOM_3_MULT19_FLR_3 | 07-SEP-13:00 | 0.00 | -50813.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.71 | 2352.88 | 65533.73 | 0.00 | 302.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18642.84 |
ROOM_4_MULT19_FLR_3 | 06-MAY-19:31 | 0.00 | -74945.71 | 0.00 | -7143.45 | 0.00 | 0.00 | 5436.60 | 4525.19 | 12159.85 | 0.00 | 0.00 | 0.00 | 66187.21 | 0.00 | -5597.38 | 0.00 | -622.33 | 0.00 |
ROOM_5_FLR_3 | 06-MAY-18:01 | 0.00 | -13123.26 | 0.00 | -534.77 | 0.00 | 0.00 | 283.21 | 378.87 | 484.65 | 0.00 | 0.00 | 0.00 | 13492.56 | 0.00 | -111.03 | 0.00 | -870.24 | 0.00 |
ROOM_6_FLR_3 | 09-JUN-08:32 | 0.00 | -13747.83 | 0.00 | -994.35 | 0.00 | 0.00 | 60.62 | 166.68 | 452.99 | 9481.26 | 0.00 | 0.00 | 4624.84 | 0.00 | -0.00 | 0.00 | -44.21 | 0.00 |
CORRIDOR_FLR_3 | 02-JUL-10:35 | 0.00 | 0.00 | 0.00 | -9025.06 | 0.00 | 0.00 | 1797.10 | 1546.67 | 0.00 | 5588.20 | 0.00 | 58.12 | 34.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 21-MAY-18:01 | 0.00 | -3837.14 | 0.00 | -138.09 | 0.00 | 0.00 | 70.80 | 94.72 | 121.16 | 1549.81 | 0.00 | 0.00 | 2305.67 | 0.00 | -0.00 | 0.00 | -166.94 | 0.00 |
ROOM_2_FLR_6 | 20-MAY-18:41 | 0.00 | -4256.97 | 0.00 | -165.67 | 0.00 | 0.00 | 60.22 | 94.71 | 121.15 | 640.80 | 0.00 | 0.00 | 3539.55 | 0.00 | -0.00 | 0.00 | -33.79 | 0.00 |
ROOM_3_MULT9_FLR_6 | 30-JAN-16:11 | 0.00 | -17020.52 | 0.00 | -2790.82 | 0.00 | 0.00 | 537.45 | 150.05 | 441.28 | 2080.52 | 0.00 | 0.00 | 17361.94 | 0.00 | -0.00 | 0.00 | -759.91 | 0.00 |
BANQUET_FLR_6 | 26-JUN-22:00 | 0.00 | 0.00 | 0.00 | -21388.91 | 0.00 | 0.00 | 15644.50 | 1842.08 | 6747.90 | 0.00 | 0.00 | 2.17 | 0.00 | 0.00 | -72.80 | 0.00 | 0.00 | -2774.94 |
DINING_FLR_6 | 26-JUN-21:30 | 0.00 | 0.00 | 0.00 | -22834.98 | 0.00 | 0.00 | 15638.25 | 1842.08 | 6747.90 | 0.00 | 0.00 | 6.46 | 0.00 | 0.00 | -40.20 | 0.00 | 0.00 | -1359.51 |
KITCHEN_FLR_6 | 02-JUL-10:40 | 0.00 | 0.00 | 0.00 | -30221.98 | 0.00 | 0.00 | 464.21 | 363.61 | 23951.61 | 3677.27 | 0.00 | 22.99 | 1742.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 07-SEP-13:20 | 0.00 | 0.00 | 0.00 | -6579.69 | 0.00 | 0.00 | 308.46 | 341.02 | 0.00 | 4511.66 | 0.00 | 47.54 | 1371.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-SEP-18:02 | 0.00 | -157611.62 | 0.00 | -194936.97 | 0.00 | 0.00 | 77728.78 | 38728.51 | 120174.13 | 12094.16 | 0.00 | 1488.33 | 102334.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 20-JAN-07:45 | 0.00 | 0.00 | 2090.92 | 0.00 | 0.00 | 0.00 | 369.09 | 284.62 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1529.91 | 0.00 | -264.03 | -1383.70 |
RETAIL_2_FLR_1 | 04-FEB-11:02 | 0.00 | 0.00 | 508.47 | 0.00 | 0.00 | 0.00 | 328.12 | 164.79 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -102.33 | -1191.56 |
MECH_FLR_1 | 04-FEB-11:02 | 0.00 | 0.00 | 1228.44 | 0.00 | 0.00 | 0.00 | 70.95 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -238.61 | -1560.10 |
STORAGE_FLR_1 | 04-FEB-11:02 | 0.00 | 0.00 | 967.75 | 0.00 | 0.00 | 0.00 | 56.66 | 52.42 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -134.67 | -1031.38 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 20-JAN-07:33 | 0.00 | 0.00 | 2865.48 | 0.00 | 0.00 | 0.00 | 4884.69 | 874.14 | 609.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4722.92 | 0.00 | -590.01 | -3921.03 |
LOBBY_FLR_1 | 04-FEB-11:02 | 0.00 | 0.00 | 456.63 | 0.00 | 0.00 | 0.00 | 10499.42 | 1907.30 | 3694.97 | 20419.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1716.00 | -35262.03 |
ROOM_1_FLR_3 | 02-FEB-07:55 | 7707.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.52 | 212.17 | 948.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4216.51 | 0.00 | -830.21 | -4048.73 |
ROOM_2_FLR_3 | 03-FEB-10:53 | 8322.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.46 | 106.07 | 126.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2594.27 | 0.00 | -700.95 | -5365.86 |
ROOM_3_MULT19_FLR_3 | 19-JAN-05:00 | 26431.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.64 | 3333.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21564.24 | 0.00 | -3192.39 | -5505.66 |
ROOM_4_MULT19_FLR_3 | 03-FEB-11:02 | 45713.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2077.63 | 1267.05 | 2353.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13234.09 | 0.00 | -3665.79 | -34511.68 |
ROOM_5_FLR_3 | 09-DEC-16:23 | 7462.42 | 324.81 | 0.00 | -324.81 | 0.00 | 0.00 | 152.58 | 125.03 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3676.52 | 0.00 | -540.13 | -3744.63 |
ROOM_6_FLR_3 | 02-FEB-17:52 | 7908.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.47 | 106.07 | 505.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4363.65 | 0.00 | -719.88 | -3725.58 |
CORRIDOR_FLR_3 | 04-FEB-11:02 | 0.00 | 0.00 | 6647.60 | 0.00 | 0.00 | 0.00 | 2163.97 | 1288.89 | 0.00 | 5936.50 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -749.20 | -15287.76 |
ROOM_1_FLR_6 | 04-FEB-07:53 | 2451.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.60 | 38.83 | 163.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -940.60 | 0.00 | -180.53 | -1602.78 |
ROOM_2_FLR_6 | 04-FEB-10:53 | 2442.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.64 | 38.83 | 34.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -625.57 | 0.00 | -151.82 | -1777.86 |
ROOM_3_MULT9_FLR_6 | 09-DEC-16:23 | 10661.36 | 516.55 | 0.00 | -516.55 | 0.00 | 0.00 | 343.76 | 176.84 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4291.02 | 0.00 | -622.13 | -6756.55 |
BANQUET_FLR_6 | 04-FEB-11:02 | 0.00 | 0.00 | 1597.87 | 0.00 | 0.00 | 0.00 | 6554.45 | 460.52 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1512.05 | 0.00 | -379.01 | -13469.69 |
DINING_FLR_6 | 04-FEB-11:02 | 0.00 | 0.00 | 737.90 | 0.00 | 0.00 | 0.00 | 6417.36 | 460.52 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1555.96 | 0.00 | -383.08 | -12424.65 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 04-FEB-11:02 | 0.00 | 0.00 | 4964.07 | 0.00 | 0.00 | 0.00 | 589.65 | 341.02 | 0.00 | 3485.58 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -326.89 | -9053.43 |
Total Facility | 12-DEC-16:23 | 29130.75 | 80805.25 | 12716.78 | -80805.25 | 0.00 | 0.00 | 61550.76 | 12737.46 | 73604.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -73102.23 | 0.00 | -12090.24 | -104547.55 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 21.8723 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 21.7504 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 13.1213 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5330 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2632 | 2.2632 | 1.2810 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3797 | 0.3797 | 0.1188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2252 | 0.2252 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1813 | 0.1813 | 0.0018 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1004 | 0.1004 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4086 | 3.4086 | 0.0341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6110 | 1.6110 | 1.0150 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9167 | 4.9167 | 2.8419 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2777 | 1.2777 | 0.7117 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2006 | 2.2006 | 1.7825 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3116 | 2.3116 | 1.7822 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2879 | 2.2879 | 0.5514 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7084 | 0.7084 | 0.1884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 21.8723 | 21.7504 | 21.8723 | 10.5330 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2810 | 1.2810 | 1.2810 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1899 | 0.1899 | 0.1188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1376 | 0.1376 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0906 | 0.0906 | 0.0018 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0866 | 0.0866 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7043 | 1.7043 | 0.0341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0150 | 1.0150 | 1.0150 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8419 | 2.8419 | 2.8419 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7117 | 0.7117 | 0.7117 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7825 | 1.7825 | 1.7825 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7822 | 1.7822 | 1.7822 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1440 | 1.1440 | 0.5514 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3542 | 0.3542 | 0.1884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 13.1213 | 10.5330 | 10.5330 | 10.5330 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 227.67 |
Number of hours cooling loads not met | 51.67 |
Number of hours not met | 279.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1684.07 | 651679.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 549.99 | 183070.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 544.74 | 45764.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.69 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.51 | 1274.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 567.87 | 33856.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 79.54 | 4462.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 117.63 | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.78 | 4752.06 | 2901.93 | 269511.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.82 | 1307.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.07 | 716.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1692.44 | 4654.20 |
Natural Gas | 1788.84 | 6374.84 |
Additional | 0.00 | 0.00 |
Total | 3481.28 | 11029.04 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 48.01 |
Space Heating | 0.00 |
Space Cooling | 48.48 |
Fans (All) | 50.05 |
Service Water Heating | 8.35 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 410.23 |
Subtotal | 410.23 |
Natural Gas [MJ/m2] | |
Space Heating | 148.44 |
Service Water Heating | 255.78 |
Miscellaneous (All) | 561.89 |
Subtotal | 561.89 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.94 |
Space Heating | 15.27 |
Space Cooling | 4.99 |
Fans (All) | 5.15 |
Service Water Heating | 27.17 |
Receptacle Equipment | 31.17 |
Miscellaneous | 11.32 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8694.17 | 65.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8484.67 | 275.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8724.50 | 35.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8657.67 | 102.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8484.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 275.33 | 0.00 | 0.00 | 0.00 |
Average | 8738.23 | 21.77 | 0.00 | 0.00 | 0.00 |
Sum | 192241.00 | 479.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4133.83 | 20.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4115.17 | 38.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 38.83 | 0.00 | 0.00 | 0.00 |
Average | 288884.36 | 2.68 | 0.00 | 0.00 | 0.00 |
Sum | 6355456.00 | 59.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8618.00 | 142.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8310.17 | 449.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8546.67 | 213.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8182.33 | 577.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8711.17 | 48.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8597.83 | 162.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8480.67 | 279.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8353.17 | 406.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8306.67 | 453.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8717.17 | 42.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8647.17 | 112.83 | 0.00 | 0.00 | 0.00 |
Min | 8182.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 577.67 | 0.00 | 0.00 | 0.00 |
Average | 8627.55 | 132.45 | 0.00 | 0.00 | 0.00 |
Sum | 189806.00 | 2914.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50043.83 | 135.17 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 692241.00 | 18176.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1950291.17 | 165137.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4065.17 | 88.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4141.83 | 12.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4127.83 | 26.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4022.67 | 131.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1156451.00 | 89264.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1147951.67 | 97763.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107924.83 | 344.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 103924.17 | 2021.83 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1950291.17 | 165137.83 | 0.00 | 0.00 | 0.00 |
Average | 271927.92 | 16959.13 | 0.00 | 0.00 | 0.00 |
Sum | 5982414.17 | 373100.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303193E+11 | 20061.75 | 30-JAN-07:52 | -29.4 | -29.6 | 0.725142E+10 | 4609.70 | 04-JAN-22:10 | -29.4 | -29.6 |
February | 0.250394E+11 | 19718.57 | 01-FEB-21:40 | -30.0 | -30.2 | 0.616013E+10 | 4394.85 | 17-FEB-22:10 | -13.4 | -14.1 |
March | 0.256420E+11 | 11783.61 | 01-MAR-21:00 | -4.4 | -5.1 | 0.678740E+10 | 4336.34 | 01-MAR-22:10 | -4.4 | -5.1 |
April | 0.237802E+11 | 12024.52 | 16-APR-10:35 | 23.33 | 18.86 | 0.629395E+10 | 4050.75 | 21-APR-22:10 | -0.6 | -0.8 |
May | 0.263193E+11 | 12605.95 | 29-MAY-10:35 | 24.63 | 18.66 | 0.667717E+10 | 4162.79 | 19-MAY-22:10 | 24.63 | 18.66 |
June | 0.281832E+11 | 13823.39 | 25-JUN-10:35 | 28.87 | 21.94 | 0.683836E+10 | 4409.46 | 15-JUN-22:10 | 28.87 | 21.94 |
July | 0.313515E+11 | 14601.67 | 30-JUL-10:35 | 24.63 | 19.89 | 0.739756E+10 | 4619.79 | 21-JUL-22:10 | 24.63 | 19.89 |
August | 0.335035E+11 | 15289.48 | 27-AUG-10:35 | 25.53 | 19.86 | 0.786198E+10 | 4837.09 | 11-AUG-22:10 | 25.53 | 19.86 |
September | 0.338877E+11 | 17496.57 | 21-SEP-21:00 | 12.20 | 11.56 | 0.781096E+10 | 4837.31 | 12-SEP-22:10 | 12.20 | 11.56 |
October | 0.350262E+11 | 18183.82 | 25-OCT-21:00 | 4.40 | 1.66 | 0.813128E+10 | 4837.06 | 18-OCT-23:19 | 4.40 | 1.66 |
November | 0.331150E+11 | 20819.71 | 26-NOV-07:00 | -28.9 | -29.0 | 0.780722E+10 | 4837.04 | 14-NOV-22:19 | -28.9 | -29.0 |
December | 0.318973E+11 | 15853.91 | 01-DEC-22:00 | -3.9 | -4.7 | 0.792381E+10 | 4837.02 | 01-DEC-22:19 | -3.7 | -4.5 |
Annual Sum or Average | 0.358065E+12 | 0.869412E+11 | ||||||||
Minimum of Months | 0.237802E+11 | 11783.61 | -30.0 | -30.2 | 0.616013E+10 | 4050.75 | -29.4 | -29.6 | ||
Maximum of Months | 0.350262E+11 | 20819.71 | 28.87 | 21.94 | 0.813128E+10 | 4837.31 | 28.87 | 21.94 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.476537E+09 | 2095.55 | 12-JAN-12:30 | 1.95 | 0.38 | 0.619389E+09 | 383.05 | 13-JAN-22:19 | 1.83 | 0.65 |
February | 0.826484E+09 | 2863.16 | 08-FEB-13:30 | 2.50 | 1.29 | 0.558948E+09 | 411.53 | 24-FEB-22:19 | 1.67 | 1.15 |
March | 0.147252E+10 | 2565.55 | 24-MAR-13:00 | 12.20 | 6.46 | 0.650761E+09 | 445.19 | 23-MAR-21:19 | 12.20 | 6.46 |
April | 0.221543E+10 | 3684.77 | 15-APR-13:15 | 28.67 | 20.40 | 0.666346E+09 | 491.84 | 18-APR-22:10 | 14.03 | 11.86 |
May | 0.305446E+10 | 2830.69 | 06-MAY-13:00 | 22.20 | 11.68 | 0.739891E+09 | 491.84 | 12-MAY-22:10 | 16.70 | 15.64 |
June | 0.361612E+10 | 3128.81 | 30-JUN-13:00 | 29.40 | 21.96 | 0.761037E+09 | 491.84 | 20-JUN-22:10 | 29.40 | 21.96 |
July | 0.409823E+10 | 3318.58 | 30-JUL-12:00 | 26.70 | 21.51 | 0.811532E+09 | 491.84 | 12-JUL-22:10 | 26.70 | 21.51 |
August | 0.415700E+10 | 3592.89 | 29-AUG-13:30 | 23.60 | 16.39 | 0.813284E+09 | 491.84 | 07-AUG-22:10 | 23.60 | 16.39 |
September | 0.371229E+10 | 4473.07 | 07-SEP-12:50 | 31.52 | 18.17 | 0.735662E+09 | 491.86 | 12-SEP-22:10 | 15.68 | 14.97 |
October | 0.268363E+10 | 4032.65 | 20-OCT-12:50 | 21.68 | 12.55 | 0.687102E+09 | 491.82 | 20-OCT-21:19 | 13.90 | 9.47 |
November | 0.125381E+10 | 3805.07 | 04-NOV-12:50 | 13.72 | 6.77 | 0.620115E+09 | 445.10 | 03-NOV-21:19 | 13.72 | 6.77 |
December | 0.609167E+09 | 2904.58 | 03-DEC-13:00 | 5.60 | 2.41 | 0.627758E+09 | 364.76 | 01-DEC-22:19 | 5.60 | 2.41 |
Annual Sum or Average | 0.281757E+11 | 0.829182E+10 | ||||||||
Minimum of Months | 0.476537E+09 | 2095.55 | 1.95 | 0.38 | 0.558948E+09 | 364.76 | 1.67 | 0.65 | ||
Maximum of Months | 0.415700E+10 | 4473.07 | 31.52 | 21.96 | 0.813284E+09 | 491.86 | 29.40 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167184E+10 | 1588.75 | 05-JAN-21:55 | -23.9 | -24.2 | 0.725383E+09 | 488.67 | 13-JAN-23:10 | 0.82 | 0.04 |
February | 0.185449E+10 | 1259.01 | 24-FEB-21:00 | 2.20 | 1.50 | 0.662458E+09 | 503.79 | 24-FEB-23:10 | 0.60 | 0.07 |
March | 0.245371E+10 | 1350.48 | 24-MAR-20:00 | 3.90 | 2.01 | 0.773758E+09 | 526.37 | 24-MAR-21:40 | 1.33 | 0.09 |
April | 0.273960E+10 | 1549.55 | 16-APR-10:35 | 23.33 | 18.86 | 0.787879E+09 | 569.54 | 18-APR-22:10 | 14.03 | 11.86 |
May | 0.318181E+10 | 1635.81 | 31-MAY-20:55 | 22.20 | 17.24 | 0.860261E+09 | 569.55 | 30-MAY-22:10 | 22.20 | 17.24 |
June | 0.334509E+10 | 1855.93 | 30-JUN-21:00 | 22.20 | 17.11 | 0.870505E+09 | 569.55 | 20-JUN-22:10 | 22.20 | 17.11 |
July | 0.359655E+10 | 1820.70 | 03-JUL-21:00 | 24.40 | 22.86 | 0.917402E+09 | 569.55 | 12-JUL-22:10 | 18.62 | 16.05 |
August | 0.357202E+10 | 1771.97 | 04-AUG-21:00 | 18.30 | 17.97 | 0.921887E+09 | 569.55 | 07-AUG-22:10 | 14.82 | 11.79 |
September | 0.323475E+10 | 1831.40 | 07-SEP-21:00 | 22.80 | 16.44 | 0.857422E+09 | 569.57 | 12-SEP-22:10 | 15.68 | 14.97 |
October | 0.290973E+10 | 1459.96 | 20-OCT-20:00 | 15.00 | 9.90 | 0.824546E+09 | 558.07 | 20-OCT-22:10 | 13.90 | 9.56 |
November | 0.231439E+10 | 1434.43 | 25-NOV-21:23 | -23.9 | -24.3 | 0.746153E+09 | 535.52 | 03-NOV-22:10 | -23.9 | -24.3 |
December | 0.192441E+10 | 1166.67 | 05-DEC-21:00 | -6.7 | -9.2 | 0.735837E+09 | 480.74 | 05-DEC-23:10 | -6.8 | -9.3 |
Annual Sum or Average | 0.327984E+11 | 0.968349E+10 | ||||||||
Minimum of Months | 0.167184E+10 | 1166.67 | -23.9 | -24.3 | 0.662458E+09 | 480.74 | -23.9 | -24.3 | ||
Maximum of Months | 0.359655E+10 | 1855.93 | 24.40 | 22.86 | 0.921887E+09 | 569.57 | 22.20 | 17.24 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11584563.40 | 21.33 | 05-JAN-22:20 | -24.1 | -24.4 | 0.154294E+09 | 106.75 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 21750265.04 | 18.08 | 24-FEB-21:00 | 2.20 | 1.50 | 0.143378E+09 | 111.70 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 39372246.36 | 194.49 | 29-MAR-21:00 | 7.80 | 7.24 | 0.174968E+09 | 120.45 | 28-MAR-21:19 | 7.80 | 7.24 |
April | 0.241741E+09 | 1070.51 | 18-APR-20:00 | 18.30 | 15.20 | 0.184545E+09 | 120.45 | 18-APR-04:00 | 18.30 | 15.20 |
May | 0.663150E+09 | 1274.19 | 31-MAY-20:55 | 22.20 | 17.24 | 0.204445E+09 | 120.45 | 31-MAY-21:19 | 21.40 | 16.40 |
June | 0.137585E+10 | 1512.21 | 26-JUN-21:00 | 25.60 | 21.31 | 0.199005E+09 | 120.46 | 19-JUN-21:10 | 25.60 | 21.31 |
July | 0.175227E+10 | 1457.60 | 03-JUL-21:00 | 24.40 | 22.86 | 0.205008E+09 | 120.45 | 27-JUL-21:30 | 20.55 | 17.79 |
August | 0.170744E+10 | 1491.53 | 04-AUG-20:00 | 18.90 | 18.12 | 0.205875E+09 | 120.45 | 11-AUG-21:30 | 18.05 | 15.93 |
September | 0.107531E+10 | 1392.73 | 08-SEP-20:00 | 20.00 | 15.73 | 0.197813E+09 | 120.46 | 12-SEP-22:10 | 15.68 | 14.97 |
October | 0.168735E+09 | 649.31 | 11-OCT-21:00 | 11.10 | 5.80 | 0.198921E+09 | 120.45 | 12-OCT-23:19 | 2.33 | 0.78 |
November | 81725068.48 | 532.81 | 03-NOV-20:00 | 7.80 | 4.59 | 0.173234E+09 | 120.45 | 07-NOV-00:20 | 10.40 | 9.62 |
December | 20050846.80 | 16.78 | 05-DEC-21:00 | -6.7 | -9.2 | 0.157796E+09 | 106.51 | 05-DEC-22:10 | -7.1 | -9.5 |
Annual Sum or Average | 0.715898E+10 | 0.219928E+10 | ||||||||
Minimum of Months | 11584563.40 | 16.78 | -24.1 | -24.4 | 0.143378E+09 | 106.51 | -7.1 | -9.5 | ||
Maximum of Months | 0.175227E+10 | 1512.21 | 25.60 | 22.86 | 0.205875E+09 | 120.46 | 25.60 | 21.31 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11364286.11 | 298.26 | 13-JAN-22:00 | 2.20 | 0.77 | 0.115074E+09 | 68.58 | 18-JAN-03:30 | 0.85 | 0.49 |
February | 81429897.52 | 428.63 | 24-FEB-22:00 | 2.20 | 1.69 | 0.101393E+09 | 68.57 | 24-FEB-05:19 | 2.20 | 1.69 |
March | 0.450925E+09 | 662.12 | 28-MAR-20:00 | 11.70 | 8.27 | 0.117306E+09 | 70.29 | 28-MAR-22:10 | 8.80 | 7.21 |
April | 0.977168E+09 | 888.86 | 16-APR-10:35 | 23.33 | 18.86 | 0.115368E+09 | 78.74 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.168175E+10 | 920.67 | 31-MAY-10:35 | 27.93 | 19.39 | 0.123648E+09 | 81.14 | 31-MAY-22:10 | 19.42 | 14.32 |
June | 0.184015E+10 | 971.03 | 30-JUN-10:35 | 27.93 | 22.99 | 0.127091E+09 | 84.59 | 30-JUN-22:10 | 21.02 | 16.54 |
July | 0.198594E+10 | 974.28 | 02-JUL-10:35 | 27.77 | 21.90 | 0.134156E+09 | 84.04 | 03-JUL-22:10 | 23.12 | 22.36 |
August | 0.195983E+10 | 955.12 | 04-AUG-10:35 | 29.27 | 25.47 | 0.134241E+09 | 83.92 | 04-AUG-22:10 | 18.22 | 17.52 |
September | 0.171487E+10 | 954.27 | 08-SEP-10:35 | 28.33 | 18.78 | 0.123820E+09 | 82.66 | 11-SEP-22:10 | 19.60 | 18.05 |
October | 0.132055E+10 | 727.20 | 21-OCT-10:35 | 17.17 | 11.84 | 0.118133E+09 | 74.09 | 20-OCT-22:10 | 17.17 | 11.84 |
November | 0.566035E+09 | 693.02 | 03-NOV-20:00 | 7.80 | 4.59 | 0.113286E+09 | 72.34 | 08-NOV-23:10 | 14.40 | 12.79 |
December | 26258195.76 | 250.89 | 03-DEC-21:00 | -1.1 | -2.3 | 0.116675E+09 | 68.57 | 19-DEC-05:40 | -3.1 | -4.2 |
Annual Sum or Average | 0.126163E+11 | 0.144019E+10 | ||||||||
Minimum of Months | 11364286.11 | 250.89 | -1.1 | -2.3 | 0.101393E+09 | 68.57 | -3.1 | -4.2 | ||
Maximum of Months | 0.198594E+10 | 974.28 | 29.27 | 25.47 | 0.134241E+09 | 84.59 | 23.12 | 22.36 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.454123E+11 | 36928.80 | 13-JAN-21:00 | -0.6 | -1.3 | 0.649334E+09 | 381.57 | 12-JAN-23:10 | -0.6 | -1.3 |
February | 0.417953E+11 | 37279.04 | 24-FEB-21:00 | 2.20 | 1.50 | 0.587071E+09 | 381.58 | 08-FEB-23:10 | 2.20 | 1.50 |
March | 0.479441E+11 | 37706.67 | 28-MAR-20:00 | 11.70 | 8.27 | 0.652388E+09 | 381.57 | 15-MAR-21:10 | 11.70 | 8.27 |
April | 0.475166E+11 | 38649.26 | 18-APR-20:00 | 18.30 | 15.20 | 0.629497E+09 | 381.58 | 25-APR-21:40 | -0.5 | -2.7 |
May | 0.507768E+11 | 38948.81 | 31-MAY-20:00 | 24.40 | 17.91 | 0.650705E+09 | 381.60 | 12-MAY-21:19 | 24.40 | 17.91 |
June | 0.501142E+11 | 39154.79 | 26-JUN-20:00 | 26.70 | 21.52 | 0.630874E+09 | 381.68 | 13-JUN-21:10 | 26.70 | 21.52 |
July | 0.520190E+11 | 38984.03 | 03-JUL-20:00 | 26.70 | 23.80 | 0.649347E+09 | 381.69 | 19-JUL-21:10 | 22.62 | 20.36 |
August | 0.520836E+11 | 39027.58 | 04-AUG-20:00 | 18.90 | 18.12 | 0.652095E+09 | 381.67 | 23-AUG-21:10 | 18.22 | 17.17 |
September | 0.493446E+11 | 39057.03 | 07-SEP-20:00 | 23.90 | 17.04 | 0.629201E+09 | 381.68 | 01-SEP-21:10 | 23.90 | 17.04 |
October | 0.493035E+11 | 38156.53 | 20-OCT-20:00 | 15.00 | 9.90 | 0.649645E+09 | 381.57 | 31-OCT-21:19 | -0.8 | -2.6 |
November | 0.461598E+11 | 37807.15 | 03-NOV-20:00 | 7.80 | 4.59 | 0.628134E+09 | 381.58 | 30-NOV-22:30 | -0.6 | -1.1 |
December | 0.460450E+11 | 36705.71 | 01-DEC-21:00 | -5.0 | -5.8 | 0.649343E+09 | 381.56 | 01-DEC-00:20 | -5.0 | -5.8 |
Annual Sum or Average | 0.578515E+12 | 0.765763E+10 | ||||||||
Minimum of Months | 0.417953E+11 | 36705.71 | -5.0 | -5.8 | 0.587071E+09 | 381.56 | -5.0 | -5.8 | ||
Maximum of Months | 0.520836E+11 | 39154.79 | 26.70 | 23.80 | 0.652388E+09 | 381.69 | 26.70 | 21.52 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117334E+11 | 9798.61 | 30-JAN-13:10 | -24.9 | -25.2 | 0.820739E+10 | 5512.02 | 13-JAN-22:40 | -24.9 | -25.2 |
February | 0.132998E+11 | 10753.94 | 08-FEB-11:40 | 2.40 | 1.36 | 0.749992E+10 | 5709.94 | 24-FEB-22:40 | 1.13 | 0.61 |
March | 0.170135E+11 | 9998.93 | 19-MAR-10:35 | 13.87 | 10.01 | 0.868426E+10 | 5897.09 | 23-MAR-21:40 | 9.07 | 5.85 |
April | 0.186466E+11 | 12602.54 | 15-APR-13:30 | 28.85 | 20.45 | 0.875070E+10 | 6322.77 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.218000E+11 | 11099.18 | 31-MAY-18:10 | 27.02 | 19.01 | 0.932429E+10 | 6370.87 | 31-MAY-21:40 | 20.60 | 15.57 |
June | 0.226860E+11 | 11635.94 | 26-JUN-18:10 | 29.72 | 22.36 | 0.938364E+10 | 6460.40 | 26-JUN-22:10 | 24.32 | 20.87 |
July | 0.243984E+11 | 11972.40 | 30-JUL-10:35 | 24.63 | 19.89 | 0.983920E+10 | 6460.35 | 25-JUL-22:10 | 24.63 | 19.89 |
August | 0.245393E+11 | 11840.29 | 27-AUG-10:35 | 25.53 | 19.86 | 0.995979E+10 | 6462.65 | 22-AUG-22:10 | 25.53 | 19.86 |
September | 0.227019E+11 | 13901.61 | 07-SEP-13:00 | 31.70 | 18.06 | 0.936728E+10 | 6462.68 | 07-SEP-22:10 | 20.32 | 16.01 |
October | 0.205202E+11 | 13588.64 | 20-OCT-12:50 | 21.68 | 12.55 | 0.915703E+10 | 6336.02 | 20-OCT-21:40 | 13.90 | 9.51 |
November | 0.153614E+11 | 13854.66 | 04-NOV-12:50 | 13.72 | 6.77 | 0.833220E+10 | 5926.57 | 03-NOV-21:40 | 13.72 | 6.77 |
December | 0.126864E+11 | 11440.64 | 03-DEC-13:00 | 5.60 | 2.41 | 0.831419E+10 | 5389.69 | 01-DEC-22:40 | 5.60 | 2.41 |
Annual Sum or Average | 0.225387E+12 | 0.106820E+12 | ||||||||
Minimum of Months | 0.117334E+11 | 9798.61 | -24.9 | -25.2 | 0.749992E+10 | 5389.69 | -24.9 | -25.2 | ||
Maximum of Months | 0.245393E+11 | 13901.61 | 31.70 | 22.36 | 0.995979E+10 | 6462.68 | 25.53 | 20.87 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472421E+11 | 34303.12 | 05-JAN-21:55 | -23.9 | -24.2 | 0.255842E+11 | 17735.34 | 13-JAN-23:10 | 0.82 | 0.04 |
February | 0.470453E+11 | 32590.11 | 01-FEB-00:05 | -24.1 | -24.4 | 0.236971E+11 | 18110.82 | 24-FEB-22:49 | 0.87 | 0.34 |
March | 0.574768E+11 | 28746.09 | 24-MAR-20:00 | 3.90 | 2.01 | 0.277461E+11 | 18645.94 | 24-MAR-21:49 | 0.97 | -0.3 |
April | 0.608484E+11 | 33189.19 | 18-APR-21:10 | 16.32 | 13.39 | 0.278883E+11 | 19185.86 | 18-APR-22:10 | 14.03 | 11.86 |
May | 0.684108E+11 | 34141.89 | 31-MAY-21:10 | 21.80 | 16.82 | 0.300265E+11 | 19186.09 | 12-MAY-22:10 | 21.80 | 16.82 |
June | 0.707434E+11 | 36842.80 | 26-JUN-21:10 | 25.40 | 21.26 | 0.299396E+11 | 19186.23 | 19-JUN-22:10 | 25.40 | 21.26 |
July | 0.752471E+11 | 36141.27 | 27-JUL-21:10 | 20.92 | 17.78 | 0.312603E+11 | 19186.21 | 13-JUL-22:10 | 20.92 | 17.78 |
August | 0.753088E+11 | 36418.30 | 04-AUG-21:10 | 18.30 | 17.90 | 0.315294E+11 | 19186.22 | 07-AUG-22:10 | 14.82 | 11.79 |
September | 0.696472E+11 | 37937.22 | 07-SEP-21:10 | 22.43 | 16.38 | 0.297939E+11 | 19186.34 | 12-SEP-21:30 | 14.75 | 13.54 |
October | 0.647158E+11 | 31445.23 | 20-OCT-21:10 | 13.90 | 9.45 | 0.293921E+11 | 19184.52 | 20-OCT-21:19 | 13.90 | 9.47 |
November | 0.549322E+11 | 31138.99 | 25-NOV-21:23 | -23.9 | -24.3 | 0.267230E+11 | 19028.98 | 03-NOV-21:49 | -23.9 | -24.3 |
December | 0.495042E+11 | 26739.80 | 03-DEC-11:35 | 4.80 | 2.32 | 0.262787E+11 | 17516.00 | 05-DEC-22:49 | -6.8 | -9.2 |
Annual Sum or Average | 0.741122E+12 | 0.339859E+12 | ||||||||
Minimum of Months | 0.470453E+11 | 26739.80 | -24.1 | -24.4 | 0.236971E+11 | 17516.00 | -23.9 | -24.3 | ||
Maximum of Months | 0.753088E+11 | 37937.22 | 25.40 | 21.26 | 0.315294E+11 | 19186.34 | 25.40 | 21.26 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5210661.10 | 2395.95 | 12-JAN-16:12 | 2.43 | 0.93 | 92317328.85 | 56.69 | 07-JAN-00:20 | 2.43 | 0.93 |
February | 39325689.77 | 3586.80 | 17-FEB-16:11 | -6.9 | -8.9 | 83762961.67 | 56.69 | 05-FEB-00:20 | -6.9 | -8.9 |
March | 0.132434E+09 | 3757.89 | 22-MAR-15:11 | 6.70 | 3.37 | 95354899.50 | 56.69 | 25-MAR-23:19 | 11.30 | 9.18 |
April | 0.629842E+09 | 3790.03 | 26-APR-15:11 | 10.20 | 3.44 | 93767637.36 | 56.69 | 18-APR-21:19 | 10.20 | 3.44 |
May | 0.109769E+10 | 3811.02 | 21-MAY-18:01 | 16.93 | 9.12 | 98886891.13 | 56.69 | 31-MAY-22:40 | 18.27 | 13.07 |
June | 0.179080E+10 | 3320.15 | 17-JUN-18:02 | 23.72 | 19.22 | 96013937.41 | 56.70 | 20-JUN-21:00 | 18.30 | 15.22 |
July | 0.221198E+10 | 3346.77 | 21-JUL-18:01 | 20.00 | 15.79 | 99400446.38 | 56.70 | 01-JUL-23:40 | 20.00 | 15.79 |
August | 0.198229E+10 | 3316.80 | 12-AUG-15:11 | 21.33 | 17.64 | 99429019.40 | 56.70 | 01-AUG-23:10 | 21.33 | 17.64 |
September | 0.131450E+10 | 3303.61 | 17-SEP-08:61 | 19.37 | 14.77 | 95401361.87 | 56.70 | 06-SEP-22:49 | 19.37 | 14.77 |
October | 0.324151E+09 | 3261.09 | 10-OCT-15:11 | 16.70 | 12.85 | 97004245.86 | 56.69 | 10-OCT-21:19 | 10.73 | 9.85 |
November | 70020273.69 | 3695.48 | 12-NOV-16:11 | 0.00 | -2.8 | 91199112.64 | 56.69 | 27-NOV-04:40 | -9.8 | -10.3 |
December | 7421231.06 | 3474.30 | 01-DEC-16:12 | -2.4 | -4.5 | 92803605.94 | 56.69 | 13-DEC-00:20 | -13.1 | -13.5 |
Annual Sum or Average | 0.960567E+10 | 0.113534E+10 | ||||||||
Minimum of Months | 5210661.10 | 2395.95 | -6.9 | -8.9 | 83762961.67 | 56.69 | -13.1 | -13.5 | ||
Maximum of Months | 0.221198E+10 | 3811.02 | 23.72 | 19.22 | 99429019.40 | 56.70 | 21.33 | 17.64 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 465723.85 | 291.85 | 12-JAN-16:13 | 2.43 | 0.93 | 91622134.49 | 56.69 | 21-JAN-00:20 | -11.3 | -11.7 |
February | 11420536.63 | 2586.47 | 25-FEB-16:11 | 5.40 | 2.62 | 82369855.64 | 56.69 | 17-FEB-00:20 | 5.40 | 2.62 |
March | 52488977.19 | 3443.97 | 21-MAR-18:01 | -2.7 | -5.5 | 94323668.34 | 56.69 | 01-MAR-00:20 | -2.7 | -5.5 |
April | 0.407307E+09 | 3665.75 | 29-APR-18:41 | 12.77 | 8.28 | 94690639.85 | 79.22 | 17-APR-18:10 | 12.77 | 8.28 |
May | 0.790327E+09 | 4219.20 | 20-MAY-18:41 | 13.68 | 7.74 | 0.103363E+09 | 75.77 | 30-MAY-21:40 | 19.27 | 16.63 |
June | 0.146524E+10 | 3684.32 | 16-JUN-16:32 | 24.23 | 16.73 | 0.103556E+09 | 91.28 | 08-JUN-18:10 | 24.23 | 16.73 |
July | 0.174732E+10 | 3586.70 | 23-JUL-21:51 | 13.90 | 11.92 | 0.109192E+09 | 90.47 | 24-JUL-18:10 | 21.98 | 17.37 |
August | 0.146790E+10 | 3740.87 | 11-AUG-18:11 | 23.70 | 17.82 | 0.108282E+09 | 87.68 | 16-AUG-18:10 | 21.83 | 15.21 |
September | 0.881854E+09 | 3427.80 | 12-SEP-21:11 | 14.47 | 13.10 | 99140242.49 | 80.83 | 12-SEP-18:10 | 14.47 | 13.10 |
October | 0.125296E+09 | 3028.43 | 10-OCT-18:01 | 12.68 | 11.10 | 96232880.90 | 57.61 | 20-OCT-20:10 | 14.82 | 9.83 |
November | 24235657.32 | 2912.53 | 03-NOV-16:11 | 14.07 | 8.84 | 90383383.54 | 56.69 | 29-NOV-04:10 | -5.0 | -6.0 |
December | 1055975.21 | 419.85 | 01-DEC-16:13 | -2.4 | -4.5 | 92003717.73 | 56.69 | 13-DEC-00:20 | -13.1 | -13.5 |
Annual Sum or Average | 0.697491E+10 | 0.116516E+10 | ||||||||
Minimum of Months | 465723.85 | 291.85 | -2.7 | -5.5 | 82369855.64 | 56.69 | -13.1 | -13.5 | ||
Maximum of Months | 0.174732E+10 | 4219.20 | 24.23 | 17.82 | 0.109192E+09 | 91.28 | 24.23 | 17.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3263336.72 | 206.75 | 30-JAN-15:05 | -24.0 | -24.3 | 0.00 | 0.00 | 01-JAN-00:10 | -24.0 | -24.3 |
February | 8098113.11 | 243.89 | 02-FEB-15:05 | -28.9 | -29.2 | 0.00 | 0.00 | 01-FEB-00:10 | -28.9 | -29.2 |
March | 39367653.23 | 382.41 | 24-MAR-13:10 | 12.38 | 6.48 | 0.00 | 0.00 | 01-MAR-00:10 | 12.38 | 6.48 |
April | 0.149395E+09 | 567.75 | 15-APR-13:30 | 28.85 | 20.45 | 0.00 | 0.00 | 01-APR-00:10 | 28.85 | 20.45 |
May | 0.285060E+09 | 420.68 | 06-MAY-13:00 | 22.20 | 11.68 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 11.68 |
June | 0.408235E+09 | 434.50 | 26-JUN-12:50 | 31.02 | 21.46 | 0.00 | 0.00 | 01-JUN-00:10 | 31.02 | 21.46 |
July | 0.508971E+09 | 472.72 | 30-JUL-13:30 | 26.95 | 19.99 | 0.00 | 0.00 | 01-JUL-00:10 | 26.95 | 19.99 |
August | 0.526411E+09 | 539.60 | 29-AUG-13:30 | 23.60 | 16.39 | 0.00 | 0.00 | 01-AUG-00:10 | 23.60 | 16.39 |
September | 0.442316E+09 | 668.58 | 07-SEP-13:00 | 31.70 | 18.06 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 18.06 |
October | 0.220153E+09 | 651.54 | 20-OCT-12:50 | 21.68 | 12.55 | 0.00 | 0.00 | 01-OCT-00:10 | 21.68 | 12.55 |
November | 65734439.08 | 622.50 | 04-NOV-12:30 | 13.35 | 6.69 | 0.00 | 0.00 | 01-NOV-00:10 | 13.35 | 6.69 |
December | 3935281.46 | 126.48 | 07-DEC-15:05 | -3.6 | -7.4 | 0.00 | 0.00 | 01-DEC-00:10 | -3.6 | -7.4 |
Annual Sum or Average | 0.266094E+10 | 0.00 | ||||||||
Minimum of Months | 3263336.72 | 126.48 | -28.9 | -29.2 | 0.00 | 0.00 | -28.9 | -29.2 | ||
Maximum of Months | 0.526411E+09 | 668.58 | 31.70 | 21.46 | 0.00 | 0.00 | 31.70 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3124437.21 | 219.24 | 13-JAN-19:03 | 0.40 | -0.6 | 91723157.40 | 56.69 | 08-JAN-00:20 | 0.40 | -0.6 |
February | 8978574.50 | 718.87 | 25-FEB-09:02 | 0.78 | -0.3 | 82109338.24 | 56.69 | 09-FEB-22:19 | 0.78 | -0.3 |
March | 72762743.53 | 960.45 | 23-MAR-18:01 | 13.53 | 8.78 | 95288264.71 | 56.69 | 29-MAR-21:19 | 7.60 | 7.05 |
April | 0.208926E+09 | 1046.58 | 30-APR-18:01 | 15.22 | 9.05 | 94069857.84 | 71.17 | 18-APR-21:49 | 15.22 | 9.05 |
May | 0.444454E+09 | 1080.12 | 06-MAY-19:31 | 13.13 | 8.89 | 0.100572E+09 | 72.51 | 12-MAY-21:00 | 16.70 | 15.64 |
June | 0.620942E+09 | 1019.71 | 23-JUN-21:51 | 18.90 | 13.98 | 99961607.19 | 76.12 | 08-JUN-21:40 | 18.90 | 13.98 |
July | 0.659795E+09 | 1006.57 | 25-JUL-15:12 | 29.07 | 22.98 | 0.104761E+09 | 75.34 | 07-JUL-21:49 | 29.07 | 22.98 |
August | 0.589606E+09 | 1040.59 | 11-AUG-18:11 | 23.70 | 17.82 | 0.104284E+09 | 74.11 | 16-AUG-21:30 | 15.30 | 12.85 |
September | 0.418768E+09 | 1049.93 | 19-SEP-18:01 | 12.65 | 8.22 | 97189222.10 | 74.89 | 12-SEP-21:10 | 12.65 | 8.22 |
October | 0.172500E+09 | 984.00 | 12-OCT-15:11 | 11.13 | 5.98 | 96457714.12 | 56.69 | 10-OCT-21:10 | 11.13 | 5.98 |
November | 71038315.75 | 966.35 | 04-NOV-18:01 | 5.50 | 2.14 | 91649822.12 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 4714817.36 | 233.90 | 03-DEC-09:02 | -1.5 | -1.7 | 93231799.64 | 56.69 | 04-DEC-22:19 | 1.87 | 0.13 |
Annual Sum or Average | 0.327561E+10 | 0.115130E+10 | ||||||||
Minimum of Months | 3124437.21 | 219.24 | -1.5 | -1.7 | 82109338.24 | 56.69 | 0.40 | -0.6 | ||
Maximum of Months | 0.659795E+09 | 1080.12 | 29.07 | 22.98 | 0.104761E+09 | 76.12 | 29.07 | 22.98 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4803043.29 | 753.57 | 12-JAN-09:03 | -4.1 | -4.6 | 92119203.13 | 56.69 | 29-JAN-00:20 | -4.4 | -5.0 |
February | 29155372.23 | 2834.46 | 21-FEB-09:02 | -4.8 | -6.3 | 83387134.94 | 56.69 | 19-FEB-00:20 | -4.8 | -6.3 |
March | 0.128744E+09 | 3225.98 | 21-MAR-15:11 | -0.2 | -3.9 | 95552190.29 | 56.69 | 28-MAR-21:19 | 9.63 | 7.55 |
April | 0.535695E+09 | 3414.54 | 26-APR-15:11 | 10.20 | 3.44 | 93858058.50 | 56.69 | 18-APR-21:40 | 10.20 | 3.44 |
May | 0.115970E+10 | 3414.52 | 06-MAY-18:01 | 16.83 | 10.29 | 99230402.30 | 56.69 | 30-MAY-21:40 | 19.27 | 16.63 |
June | 0.181622E+10 | 3094.89 | 29-JUN-08:61 | 24.18 | 20.15 | 96146990.47 | 56.69 | 13-JUN-22:10 | 24.18 | 20.15 |
July | 0.214971E+10 | 3143.94 | 30-JUL-08:61 | 21.38 | 18.90 | 99510556.13 | 56.69 | 19-JUL-22:40 | 21.38 | 18.90 |
August | 0.190036E+10 | 3133.61 | 03-AUG-08:61 | 25.87 | 23.32 | 99596445.82 | 56.69 | 04-AUG-00:20 | 24.07 | 23.18 |
September | 0.131541E+10 | 3114.54 | 09-SEP-08:61 | 19.05 | 16.39 | 95665617.23 | 56.69 | 06-SEP-22:40 | 19.05 | 16.39 |
October | 0.278948E+09 | 2957.59 | 21-OCT-15:11 | 20.23 | 14.13 | 97211814.62 | 56.69 | 02-OCT-21:19 | 20.23 | 14.13 |
November | 62427829.08 | 2897.49 | 03-NOV-15:11 | 15.73 | 9.52 | 91143622.55 | 56.69 | 29-NOV-00:20 | -7.0 | -8.0 |
December | 12230459.81 | 2137.51 | 03-DEC-09:02 | -1.5 | -1.7 | 92650672.50 | 56.69 | 13-DEC-00:20 | -13.1 | -13.5 |
Annual Sum or Average | 0.939340E+10 | 0.113607E+10 | ||||||||
Minimum of Months | 4803043.29 | 753.57 | -4.8 | -6.3 | 83387134.94 | 56.69 | -13.1 | -13.5 | ||
Maximum of Months | 0.214971E+10 | 3414.54 | 25.87 | 23.32 | 99596445.82 | 56.69 | 24.18 | 23.18 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 566981.97 | 436.18 | 12-JAN-09:05 | -4.1 | -4.6 | 91373352.77 | 56.69 | 21-JAN-00:20 | -11.3 | -11.7 |
February | 7719772.22 | 2203.46 | 24-FEB-09:02 | 3.07 | 0.61 | 81858301.33 | 56.69 | 05-FEB-04:40 | 3.07 | 0.61 |
March | 52175365.13 | 2445.02 | 28-MAR-08:62 | 5.37 | 3.26 | 94383970.15 | 56.69 | 28-MAR-21:19 | 9.63 | 7.55 |
April | 0.338766E+09 | 3373.97 | 18-APR-08:51 | 22.80 | 18.62 | 94172661.34 | 72.55 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.885202E+09 | 3473.48 | 31-MAY-08:32 | 25.17 | 19.42 | 0.102276E+09 | 74.44 | 31-MAY-21:30 | 21.00 | 15.98 |
June | 0.149936E+10 | 3685.72 | 09-JUN-08:32 | 22.77 | 17.31 | 0.102182E+09 | 76.67 | 20-JUN-21:30 | 18.85 | 15.10 |
July | 0.168537E+10 | 3593.31 | 01-JUL-08:32 | 23.87 | 18.52 | 0.107871E+09 | 77.04 | 05-JUL-21:10 | 22.43 | 20.32 |
August | 0.141685E+10 | 3582.63 | 11-AUG-08:51 | 23.30 | 17.93 | 0.106614E+09 | 76.08 | 04-AUG-21:40 | 23.30 | 17.93 |
September | 0.889069E+09 | 3583.13 | 17-SEP-08:51 | 21.70 | 16.10 | 98580757.81 | 74.44 | 07-SEP-21:19 | 21.70 | 16.10 |
October | 97820944.33 | 2739.79 | 01-OCT-08:61 | 10.72 | 8.45 | 95941654.76 | 56.69 | 20-OCT-21:10 | 13.90 | 9.45 |
November | 14389659.23 | 2408.06 | 04-NOV-08:62 | 2.77 | 0.71 | 90268344.21 | 56.69 | 25-NOV-00:20 | -13.5 | -13.8 |
December | 875133.04 | 597.74 | 02-DEC-09:03 | -0.2 | -1.8 | 91969770.37 | 56.69 | 14-DEC-00:20 | -2.8 | -2.9 |
Annual Sum or Average | 0.688817E+10 | 0.115749E+10 | ||||||||
Minimum of Months | 566981.97 | 436.18 | -4.1 | -4.6 | 81858301.33 | 56.69 | -13.5 | -13.8 | ||
Maximum of Months | 0.168537E+10 | 3685.72 | 25.17 | 19.42 | 0.107871E+09 | 77.04 | 23.30 | 20.32 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231258E+09 | 1123.31 | 13-JAN-22:20 | 1.83 | 0.65 | 0.119667E+10 | 704.63 | 13-JAN-22:19 | 1.83 | 0.65 |
February | 0.770915E+09 | 1331.41 | 24-FEB-21:00 | 2.20 | 1.50 | 0.107136E+10 | 717.18 | 24-FEB-22:49 | 0.87 | 0.34 |
March | 0.186083E+10 | 1527.74 | 20-MAR-10:35 | 9.43 | 6.43 | 0.121463E+10 | 749.38 | 24-MAR-21:40 | 1.33 | 0.09 |
April | 0.286566E+10 | 1995.99 | 18-APR-10:35 | 26.33 | 20.75 | 0.122571E+10 | 875.82 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.389214E+10 | 2061.78 | 31-MAY-10:35 | 27.93 | 19.39 | 0.136191E+10 | 890.86 | 31-MAY-21:49 | 20.20 | 15.15 |
June | 0.425985E+10 | 2219.27 | 30-JUN-10:35 | 27.93 | 22.99 | 0.142376E+10 | 951.85 | 30-JUN-22:10 | 21.02 | 16.54 |
July | 0.465097E+10 | 2256.08 | 02-JUL-10:35 | 27.77 | 21.90 | 0.152091E+10 | 947.46 | 03-JUL-21:40 | 23.67 | 22.67 |
August | 0.454879E+10 | 2168.70 | 02-AUG-10:35 | 26.33 | 21.24 | 0.151037E+10 | 935.53 | 04-AUG-21:49 | 18.30 | 17.60 |
September | 0.400771E+10 | 2190.78 | 09-SEP-10:35 | 25.53 | 16.73 | 0.137703E+10 | 928.38 | 08-SEP-21:49 | 25.53 | 16.73 |
October | 0.307916E+10 | 1616.55 | 20-OCT-10:35 | 17.13 | 11.05 | 0.123530E+10 | 783.07 | 20-OCT-21:49 | 13.90 | 9.53 |
November | 0.147359E+10 | 1588.42 | 04-NOV-10:35 | 10.20 | 5.24 | 0.117000E+10 | 750.46 | 03-NOV-21:49 | 10.20 | 5.24 |
December | 0.472359E+09 | 1368.71 | 03-DEC-11:35 | 4.80 | 2.32 | 0.119879E+10 | 704.43 | 09-DEC-05:30 | -22.8 | -23.0 |
Annual Sum or Average | 0.321133E+11 | 0.155064E+11 | ||||||||
Minimum of Months | 0.231258E+09 | 1123.31 | 1.83 | 0.65 | 0.107136E+10 | 704.43 | -22.8 | -23.0 | ||
Maximum of Months | 0.465097E+10 | 2256.08 | 27.93 | 22.99 | 0.152091E+10 | 951.85 | 25.53 | 22.67 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2892571.50 | 2472.06 | 12-JAN-16:12 | 2.43 | 0.93 | 91766521.16 | 56.69 | 21-JAN-00:20 | -11.3 | -11.7 |
February | 35755231.19 | 3384.10 | 17-FEB-16:11 | -6.9 | -8.9 | 82824434.13 | 56.69 | 17-FEB-00:20 | -6.9 | -8.9 |
March | 0.112964E+09 | 3894.60 | 22-MAR-15:11 | 6.70 | 3.37 | 94774910.87 | 56.69 | 02-MAR-00:20 | 6.70 | 3.37 |
April | 0.637094E+09 | 3953.25 | 26-APR-15:11 | 10.20 | 3.44 | 93410632.28 | 56.69 | 12-APR-22:40 | 10.20 | 3.44 |
May | 0.108547E+10 | 3975.29 | 21-MAY-18:01 | 16.93 | 9.12 | 98747959.32 | 56.69 | 30-MAY-21:00 | 18.90 | 16.37 |
June | 0.183286E+10 | 3469.78 | 17-JUN-18:02 | 23.72 | 19.22 | 95909017.69 | 56.70 | 07-JUN-01:00 | 23.72 | 19.22 |
July | 0.225327E+10 | 3478.44 | 21-JUL-18:01 | 20.00 | 15.79 | 99333481.52 | 56.70 | 03-JUL-23:40 | 20.00 | 15.79 |
August | 0.197470E+10 | 3450.52 | 30-AUG-18:01 | 20.13 | 17.18 | 99327812.62 | 56.70 | 02-AUG-23:19 | 20.13 | 17.18 |
September | 0.126479E+10 | 3903.10 | 20-SEP-18:01 | 17.23 | 10.71 | 95134828.14 | 56.70 | 12-SEP-21:10 | 17.23 | 10.71 |
October | 0.295456E+09 | 3339.46 | 10-OCT-15:11 | 16.70 | 12.85 | 96540007.65 | 56.69 | 10-OCT-21:19 | 10.73 | 9.85 |
November | 57945150.53 | 3843.25 | 12-NOV-16:11 | 0.00 | -2.8 | 90668473.20 | 56.69 | 29-NOV-05:19 | -5.0 | -6.0 |
December | 5269956.87 | 3391.35 | 01-DEC-16:12 | -2.4 | -4.5 | 92395831.13 | 56.69 | 14-DEC-00:20 | -2.8 | -2.9 |
Annual Sum or Average | 0.955848E+10 | 0.113083E+10 | ||||||||
Minimum of Months | 2892571.50 | 2472.06 | -6.9 | -8.9 | 82824434.13 | 56.69 | -11.3 | -11.7 | ||
Maximum of Months | 0.225327E+10 | 3975.29 | 23.72 | 19.22 | 99333481.52 | 56.70 | 23.72 | 19.22 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 151576.06 | 744.81 | 13-JAN-16:14 | 3.33 | 1.56 | 91047279.85 | 56.69 | 09-JAN-04:30 | 3.33 | 1.56 |
February | 8055235.76 | 2645.35 | 25-FEB-16:11 | 5.40 | 2.62 | 81454835.31 | 56.69 | 07-FEB-00:20 | 5.40 | 2.62 |
March | 39078724.70 | 3565.91 | 21-MAR-18:01 | -2.7 | -5.5 | 93800427.87 | 56.69 | 01-MAR-04:30 | -2.7 | -5.5 |
April | 0.408667E+09 | 3879.99 | 29-APR-18:41 | 12.77 | 8.28 | 94498324.71 | 86.05 | 17-APR-18:10 | 12.77 | 8.28 |
May | 0.783020E+09 | 4422.63 | 20-MAY-18:41 | 13.68 | 7.74 | 0.103909E+09 | 79.18 | 03-MAY-18:10 | 13.68 | 7.74 |
June | 0.154048E+10 | 3843.32 | 16-JUN-16:32 | 24.23 | 16.73 | 0.104454E+09 | 100.20 | 08-JUN-18:10 | 24.23 | 16.73 |
July | 0.183851E+10 | 3881.91 | 23-JUL-21:51 | 13.90 | 11.92 | 0.109956E+09 | 96.74 | 24-JUL-18:10 | 21.98 | 17.37 |
August | 0.150029E+10 | 3879.14 | 11-AUG-18:11 | 23.70 | 17.82 | 0.109054E+09 | 94.88 | 16-AUG-18:10 | 21.83 | 15.21 |
September | 0.846757E+09 | 3566.67 | 12-SEP-21:11 | 14.47 | 13.10 | 99114253.31 | 86.95 | 12-SEP-18:10 | 14.47 | 13.10 |
October | 99765141.65 | 3157.37 | 10-OCT-16:52 | 14.30 | 11.87 | 95675893.23 | 57.60 | 11-OCT-18:10 | 15.35 | 9.78 |
November | 18210252.63 | 3067.27 | 03-NOV-16:11 | 14.07 | 8.84 | 89904302.53 | 56.69 | 23-NOV-00:20 | -1.7 | -2.6 |
December | 239825.58 | 289.35 | 02-DEC-16:13 | 4.30 | 2.45 | 91816199.51 | 56.69 | 29-DEC-00:20 | -8.5 | -9.0 |
Annual Sum or Average | 0.708323E+10 | 0.116468E+10 | ||||||||
Minimum of Months | 151576.06 | 289.35 | -2.7 | -5.5 | 81454835.31 | 56.69 | -8.5 | -9.0 | ||
Maximum of Months | 0.183851E+10 | 4422.63 | 24.23 | 17.82 | 0.109956E+09 | 100.20 | 24.23 | 17.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56496119.31 | 2201.32 | 30-JAN-16:11 | -24.6 | -24.9 | 94071139.26 | 56.69 | 18-JAN-00:20 | -24.6 | -24.9 |
February | 0.112137E+09 | 2037.21 | 17-FEB-16:11 | -6.9 | -8.9 | 85741309.58 | 56.69 | 08-FEB-22:19 | -6.9 | -8.9 |
March | 0.202698E+09 | 2065.39 | 21-MAR-15:11 | -0.2 | -3.9 | 96540481.93 | 56.69 | 20-MAR-00:20 | -0.2 | -3.9 |
April | 0.440311E+09 | 1891.25 | 29-APR-18:01 | 15.03 | 9.32 | 93946749.80 | 56.69 | 18-APR-21:00 | 15.03 | 9.32 |
May | 0.674214E+09 | 2012.45 | 21-MAY-18:01 | 16.93 | 9.12 | 98872244.80 | 56.69 | 04-MAY-21:30 | 16.93 | 9.12 |
June | 0.965349E+09 | 1794.31 | 08-JUN-18:02 | 22.88 | 16.38 | 95972623.11 | 56.69 | 29-JUN-23:49 | 23.30 | 19.15 |
July | 0.116514E+10 | 1858.60 | 07-JUL-18:01 | 22.62 | 17.11 | 99268644.81 | 56.69 | 24-JUL-21:40 | 19.40 | 15.97 |
August | 0.115388E+10 | 1828.57 | 23-AUG-15:12 | 22.97 | 20.08 | 99315052.58 | 56.69 | 14-AUG-21:30 | 22.97 | 20.08 |
September | 0.942311E+09 | 2041.50 | 20-SEP-18:01 | 17.23 | 10.71 | 95573491.89 | 56.69 | 09-SEP-00:10 | 17.23 | 10.71 |
October | 0.497242E+09 | 1799.75 | 02-OCT-18:01 | 13.22 | 11.30 | 97982249.06 | 56.69 | 20-OCT-22:10 | 13.90 | 9.56 |
November | 0.169636E+09 | 2016.34 | 21-NOV-16:11 | -7.2 | -8.8 | 92595671.93 | 56.69 | 02-NOV-21:19 | -7.2 | -8.8 |
December | 99755194.86 | 2034.03 | 05-DEC-16:11 | -5.2 | -8.3 | 94383185.08 | 56.69 | 25-DEC-00:20 | -7.2 | -7.8 |
Annual Sum or Average | 0.647917E+10 | 0.114426E+10 | ||||||||
Minimum of Months | 56496119.31 | 1794.31 | -24.6 | -24.9 | 85741309.58 | 56.69 | -24.6 | -24.9 | ||
Maximum of Months | 0.116514E+10 | 2201.32 | 22.97 | 20.08 | 99315052.58 | 56.69 | 23.30 | 20.08 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305400E+11 | 21191.85 | 31-JAN-23:53 | -23.9 | -24.2 | 0.153441E+11 | 10616.00 | 13-JAN-23:10 | -23.9 | -24.2 |
February | 0.294188E+11 | 16371.35 | 24-FEB-22:00 | 2.20 | 1.69 | 0.139412E+11 | 10718.66 | 24-FEB-23:10 | 0.60 | 0.07 |
March | 0.355823E+11 | 17324.45 | 28-MAR-21:00 | 10.00 | 7.70 | 0.164306E+11 | 11111.03 | 28-MAR-22:10 | 8.80 | 7.21 |
April | 0.374964E+11 | 20224.82 | 18-APR-21:10 | 16.32 | 13.39 | 0.164116E+11 | 11348.80 | 14-APR-21:30 | 16.32 | 13.39 |
May | 0.424106E+11 | 20661.93 | 31-MAY-21:52 | 19.80 | 14.74 | 0.176817E+11 | 11348.93 | 30-MAY-22:10 | 19.80 | 14.74 |
June | 0.433809E+11 | 21389.11 | 26-JUN-22:00 | 24.40 | 20.95 | 0.175193E+11 | 11349.17 | 21-JUN-21:19 | 24.40 | 20.95 |
July | 0.454773E+11 | 21161.48 | 03-JUL-22:00 | 23.30 | 22.56 | 0.181173E+11 | 11349.16 | 18-JUL-22:10 | 18.22 | 14.26 |
August | 0.447766E+11 | 20948.52 | 03-AUG-22:00 | 23.90 | 22.63 | 0.181234E+11 | 11349.17 | 07-AUG-22:10 | 14.82 | 11.79 |
September | 0.409223E+11 | 20491.63 | 11-SEP-21:10 | 19.40 | 17.91 | 0.170513E+11 | 11349.27 | 12-SEP-21:30 | 14.75 | 13.54 |
October | 0.381681E+11 | 17789.28 | 20-OCT-21:00 | 13.90 | 9.43 | 0.168590E+11 | 11286.48 | 11-OCT-22:10 | 13.90 | 9.43 |
November | 0.337474E+11 | 18845.62 | 25-NOV-21:23 | -23.9 | -24.3 | 0.157433E+11 | 11269.27 | 08-NOV-23:10 | -23.9 | -24.3 |
December | 0.316908E+11 | 16076.28 | 04-DEC-23:10 | 2.30 | 0.33 | 0.157176E+11 | 10572.80 | 04-DEC-23:10 | 2.30 | 0.33 |
Annual Sum or Average | 0.453611E+12 | 0.198940E+12 | ||||||||
Minimum of Months | 0.294188E+11 | 16076.28 | -23.9 | -24.3 | 0.139412E+11 | 10572.80 | -23.9 | -24.3 | ||
Maximum of Months | 0.454773E+11 | 21389.11 | 24.40 | 22.63 | 0.181234E+11 | 11349.27 | 24.40 | 20.95 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.332557E+11 | 21877.59 | 31-JAN-23:53 | -23.9 | -24.2 | 0.157910E+11 | 11017.96 | 13-JAN-23:10 | -23.9 | -24.2 |
February | 0.317962E+11 | 19319.18 | 01-FEB-00:05 | -24.1 | -24.4 | 0.144327E+11 | 11129.16 | 24-FEB-23:10 | 0.60 | 0.07 |
March | 0.381150E+11 | 18548.90 | 28-MAR-21:10 | 9.82 | 7.62 | 0.170473E+11 | 11344.25 | 28-MAR-22:30 | 8.60 | 7.19 |
April | 0.396571E+11 | 20827.05 | 18-APR-21:53 | 14.40 | 12.17 | 0.169759E+11 | 11348.77 | 14-APR-21:30 | 14.40 | 12.17 |
May | 0.442606E+11 | 22066.34 | 31-MAY-21:52 | 19.80 | 14.74 | 0.181272E+11 | 11348.94 | 30-MAY-22:10 | 19.80 | 14.74 |
June | 0.451432E+11 | 22830.50 | 26-JUN-21:30 | 25.00 | 21.14 | 0.178928E+11 | 11350.52 | 26-JUN-21:30 | 25.00 | 21.14 |
July | 0.472281E+11 | 22569.85 | 03-JUL-21:10 | 24.22 | 22.81 | 0.184848E+11 | 11349.16 | 18-JUL-22:10 | 18.22 | 14.26 |
August | 0.464794E+11 | 22342.12 | 03-AUG-22:00 | 23.90 | 22.63 | 0.184987E+11 | 11349.17 | 07-AUG-22:10 | 14.82 | 11.79 |
September | 0.426382E+11 | 21599.03 | 07-SEP-21:52 | 20.60 | 15.99 | 0.174793E+11 | 11349.25 | 12-SEP-21:30 | 14.75 | 13.54 |
October | 0.403834E+11 | 19832.87 | 11-OCT-21:10 | 10.80 | 5.64 | 0.174723E+11 | 11344.29 | 11-OCT-22:30 | 8.35 | 4.27 |
November | 0.362021E+11 | 19832.65 | 08-NOV-22:10 | 14.40 | 12.79 | 0.162933E+11 | 11344.19 | 02-NOV-22:19 | 14.40 | 12.79 |
December | 0.343943E+11 | 16877.46 | 04-DEC-23:10 | 2.30 | 0.33 | 0.162326E+11 | 10968.72 | 04-DEC-23:10 | 2.30 | 0.33 |
Annual Sum or Average | 0.479553E+12 | 0.204728E+12 | ||||||||
Minimum of Months | 0.317962E+11 | 16877.46 | -24.1 | -24.4 | 0.144327E+11 | 10968.72 | -23.9 | -24.2 | ||
Maximum of Months | 0.472281E+11 | 22830.50 | 25.00 | 22.81 | 0.184987E+11 | 11350.52 | 25.00 | 21.14 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.426919E+11 | 25168.43 | 13-JAN-11:50 | 3.62 | 1.34 | 0.188495E+11 | 11319.71 | 07-JAN-18:10 | 3.62 | 1.34 |
February | 0.401999E+11 | 26162.56 | 24-FEB-11:35 | 5.93 | 2.90 | 0.170213E+11 | 11319.71 | 04-FEB-18:10 | 5.93 | 2.90 |
March | 0.474575E+11 | 27532.77 | 19-MAR-10:50 | 14.13 | 10.21 | 0.188760E+11 | 11319.60 | 04-MAR-18:10 | 14.13 | 10.21 |
April | 0.485450E+11 | 29349.87 | 15-APR-10:40 | 24.67 | 19.18 | 0.182622E+11 | 11319.68 | 15-APR-17:10 | 29.72 | 18.80 |
May | 0.534420E+11 | 29854.55 | 31-MAY-10:40 | 27.93 | 19.39 | 0.188716E+11 | 11319.68 | 06-MAY-17:10 | 27.93 | 19.39 |
June | 0.536638E+11 | 30199.20 | 11-JUN-10:40 | 29.67 | 22.05 | 0.182660E+11 | 11319.68 | 24-JUN-17:10 | 26.60 | 20.24 |
July | 0.560892E+11 | 30241.02 | 02-JUL-10:40 | 27.77 | 21.90 | 0.188681E+11 | 11319.68 | 08-JUL-17:10 | 22.80 | 18.35 |
August | 0.553848E+11 | 29807.77 | 01-AUG-10:40 | 26.83 | 21.26 | 0.188753E+11 | 11319.68 | 05-AUG-17:10 | 25.32 | 17.94 |
September | 0.515751E+11 | 29943.08 | 08-SEP-10:40 | 28.33 | 18.78 | 0.182615E+11 | 11319.69 | 09-SEP-17:10 | 26.73 | 16.46 |
October | 0.496047E+11 | 27720.86 | 01-OCT-10:40 | 16.07 | 11.42 | 0.188688E+11 | 11319.37 | 21-OCT-17:19 | 15.03 | 11.77 |
November | 0.448749E+11 | 27269.49 | 04-NOV-10:40 | 10.20 | 5.24 | 0.182563E+11 | 11319.68 | 25-NOV-18:10 | -20.8 | -21.1 |
December | 0.436988E+11 | 25578.66 | 03-DEC-11:50 | 4.90 | 2.33 | 0.188679E+11 | 11319.71 | 09-DEC-18:10 | -19.5 | -19.9 |
Annual Sum or Average | 0.587228E+12 | 0.222144E+12 | ||||||||
Minimum of Months | 0.401999E+11 | 25168.43 | 3.62 | 1.34 | 0.170213E+11 | 11319.37 | -20.8 | -21.1 | ||
Maximum of Months | 0.560892E+11 | 30241.02 | 29.67 | 22.05 | 0.188760E+11 | 11319.71 | 29.72 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162705E+09 | 1452.24 | 13-JAN-11:50 | 3.62 | 1.34 | 0.125992E+10 | 748.13 | 13-JAN-22:49 | 1.28 | 0.44 |
February | 0.684715E+09 | 1623.10 | 24-FEB-11:35 | 5.93 | 2.90 | 0.111972E+10 | 782.86 | 24-FEB-22:40 | 1.13 | 0.61 |
March | 0.204975E+10 | 1843.47 | 20-MAR-10:50 | 9.72 | 6.68 | 0.131828E+10 | 861.99 | 28-MAR-21:49 | 9.08 | 7.30 |
April | 0.374771E+10 | 4370.14 | 18-APR-15:10 | 27.75 | 20.46 | 0.138937E+10 | 1007.39 | 18-APR-22:10 | 14.03 | 11.86 |
May | 0.540192E+10 | 5141.11 | 31-MAY-15:10 | 29.72 | 19.55 | 0.163400E+10 | 1007.40 | 30-MAY-22:10 | 29.72 | 19.55 |
June | 0.745124E+10 | 5988.42 | 30-JUN-14:10 | 29.40 | 21.90 | 0.163534E+10 | 1007.42 | 01-JUN-01:10 | 29.40 | 21.90 |
July | 0.841474E+10 | 5950.96 | 29-JUL-13:30 | 27.80 | 20.45 | 0.170967E+10 | 1007.40 | 13-JUL-22:10 | 27.80 | 20.45 |
August | 0.772065E+10 | 6209.55 | 04-AUG-15:10 | 33.90 | 25.49 | 0.171483E+10 | 1007.40 | 07-AUG-22:10 | 14.82 | 11.79 |
September | 0.600556E+10 | 6580.05 | 07-SEP-13:20 | 31.87 | 18.17 | 0.157189E+10 | 1007.43 | 12-SEP-22:10 | 15.68 | 14.97 |
October | 0.385924E+10 | 1976.56 | 20-OCT-10:50 | 17.62 | 11.24 | 0.140848E+10 | 928.92 | 20-OCT-22:10 | 13.90 | 9.56 |
November | 0.173680E+10 | 1950.11 | 04-NOV-10:50 | 10.40 | 5.25 | 0.127673E+10 | 883.08 | 03-NOV-21:40 | 10.40 | 5.25 |
December | 0.294432E+09 | 1552.27 | 03-DEC-11:50 | 4.90 | 2.33 | 0.126926E+10 | 745.59 | 28-DEC-05:19 | -17.2 | -17.5 |
Annual Sum or Average | 0.475295E+11 | 0.173075E+11 | ||||||||
Minimum of Months | 0.162705E+09 | 1452.24 | 3.62 | 1.34 | 0.111972E+10 | 745.59 | -17.2 | -17.5 | ||
Maximum of Months | 0.841474E+10 | 6580.05 | 33.90 | 25.49 | 0.171483E+10 | 1007.43 | 29.72 | 21.90 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150582E+10 | 2090.85 | 20-JAN-07:45 | -23.5 |
February | 0.639240E+09 | 1518.52 | 05-FEB-06:00 | -17.8 |
March | 0.249794E+09 | 842.31 | 06-MAR-07:10 | -12.7 |
April | 56032096.59 | 670.39 | 03-APR-06:05 | -7.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 140772.69 | 75.10 | 30-SEP-06:30 | 0.60 |
October | 705229.90 | 87.86 | 27-OCT-06:10 | 0.25 |
November | 0.422030E+09 | 1570.68 | 28-NOV-05:00 | -21.7 |
December | 0.123072E+10 | 1962.59 | 10-DEC-06:10 | -22.6 |
Annual Sum or Average | 0.410449E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.5 | |
Maximum of Months | 0.150582E+10 | 2090.85 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 743110.33 | 422.34 | 31-JAN-11:23 | -23.6 |
February | 1813269.66 | 508.46 | 04-FEB-11:02 | -23.6 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 276375.13 | 42.65 | 12-DEC-14:50 | -15.7 |
Annual Sum or Average | 2832755.12 | |||
Minimum of Months | 0.00 | 0.00 | -23.6 | |
Maximum of Months | 1813269.66 | 508.46 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.698714E+09 | 1122.22 | 31-JAN-11:23 | -23.6 |
February | 0.402050E+09 | 1228.44 | 04-FEB-11:02 | -23.6 |
March | 23317663.36 | 272.54 | 06-MAR-05:00 | -15.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.107873E+09 | 681.70 | 26-NOV-15:50 | -13.8 |
December | 0.284465E+09 | 774.21 | 11-DEC-15:00 | -19.4 |
Annual Sum or Average | 0.151642E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.6 | |
Maximum of Months | 0.698714E+09 | 1228.44 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.977105E+09 | 864.74 | 31-JAN-11:23 | -23.6 |
February | 0.465118E+09 | 967.75 | 04-FEB-11:02 | -23.6 |
March | 0.162596E+09 | 425.90 | 06-MAR-05:00 | -15.6 |
April | 13044562.27 | 181.33 | 03-APR-11:40 | -3.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.224838E+09 | 746.25 | 26-NOV-09:00 | -23.3 |
December | 0.633322E+09 | 722.99 | 10-DEC-06:10 | -22.6 |
Annual Sum or Average | 0.247602E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.6 | |
Maximum of Months | 0.977105E+09 | 967.75 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84376309.69 | 2865.30 | 20-JAN-07:33 | -23.7 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 7887236.89 | 1110.88 | 26-NOV-16:00 | -13.9 |
December | 0.142960E+09 | 2350.78 | 12-DEC-14:50 | -15.7 |
Annual Sum or Average | 0.235223E+09 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.142960E+09 | 2865.30 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 68493.79 | 456.63 | 04-FEB-11:02 | -23.6 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -0.7 |
Annual Sum or Average | 68493.79 | |||
Minimum of Months | 0.00 | 0.00 | -23.6 | |
Maximum of Months | 68493.79 | 456.63 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205325E+10 | 1897.91 | 19-JAN-19:13 | -23.3 |
February | 0.127676E+10 | 1926.78 | 02-FEB-07:55 | -36.7 |
March | 0.722508E+09 | 1838.40 | 01-MAR-16:12 | -3.9 |
April | 0.269843E+09 | 1821.27 | 03-APR-08:62 | -5.9 |
May | 11833424.17 | 1349.12 | 02-MAY-08:61 | 4.08 |
June | 3163411.91 | 1097.43 | 03-JUN-08:03 | 8.68 |
July | 1448552.72 | 988.43 | 13-JUL-08:04 | 21.38 |
August | 1624877.11 | 959.07 | 23-AUG-08:04 | 18.98 |
September | 42316972.32 | 1717.00 | 29-SEP-08:62 | 5.05 |
October | 0.197297E+09 | 1763.26 | 26-OCT-08:62 | 1.28 |
November | 0.935447E+09 | 1889.20 | 26-NOV-16:23 | -13.9 |
December | 0.175819E+10 | 1921.56 | 09-DEC-16:23 | -19.1 |
Annual Sum or Average | 0.727368E+10 | |||
Minimum of Months | 1448552.72 | 959.07 | -36.7 | |
Maximum of Months | 0.205325E+10 | 1926.78 | 21.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242040E+10 | 1900.21 | 19-JAN-16:12 | -23.0 |
February | 0.157749E+10 | 2080.50 | 03-FEB-10:53 | -29.4 |
March | 0.874706E+09 | 1831.64 | 01-MAR-16:12 | -3.9 |
April | 0.313496E+09 | 1812.77 | 03-APR-08:62 | -5.9 |
May | 14200758.27 | 1728.48 | 02-MAY-08:61 | 4.08 |
June | 3053085.59 | 1101.94 | 03-JUN-08:03 | 8.68 |
July | 493635.74 | 909.43 | 12-JUL-08:53 | 20.00 |
August | 880397.20 | 979.92 | 16-AUG-08:53 | 18.90 |
September | 53785773.70 | 1753.81 | 30-SEP-08:61 | 3.35 |
October | 0.305642E+09 | 1770.90 | 27-OCT-08:62 | 3.15 |
November | 0.112292E+10 | 1886.72 | 26-NOV-16:23 | -13.9 |
December | 0.204003E+10 | 1912.46 | 09-DEC-16:23 | -19.1 |
Annual Sum or Average | 0.872709E+10 | |||
Minimum of Months | 493635.74 | 909.43 | -29.4 | |
Maximum of Months | 0.242040E+10 | 2080.50 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129895E+09 | 347.79 | 19-JAN-05:00 | -27.2 |
February | 26124124.77 | 268.95 | 04-FEB-06:00 | -30.6 |
March | 3179809.08 | 115.94 | 05-MAR-06:00 | -8.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 8407915.72 | 221.64 | 28-NOV-05:00 | -21.7 |
December | 89142251.02 | 270.98 | 12-DEC-05:00 | -20.0 |
Annual Sum or Average | 0.256749E+09 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 0.129895E+09 | 347.79 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.475459E+09 | 542.51 | 31-JAN-16:11 | -20.2 |
February | 0.297400E+09 | 601.48 | 03-FEB-11:02 | -29.2 |
March | 0.103606E+09 | 519.14 | 05-MAR-16:11 | -9.8 |
April | 17240479.28 | 493.73 | 03-APR-15:12 | -3.1 |
May | 150339.96 | 250.17 | 02-MAY-08:04 | 4.08 |
June | 51996.34 | 205.83 | 06-JUN-08:06 | 12.30 |
July | 7738.64 | 42.77 | 09-JUL-08:57 | 17.20 |
August | 60689.94 | 201.38 | 18-AUG-08:54 | 21.10 |
September | 467018.73 | 361.67 | 30-SEP-15:13 | 10.73 |
October | 4240231.23 | 313.96 | 31-OCT-18:03 | -0.1 |
November | 0.154425E+09 | 530.89 | 25-NOV-16:12 | -18.3 |
December | 0.365874E+09 | 530.17 | 25-DEC-16:11 | -8.9 |
Annual Sum or Average | 0.141898E+10 | |||
Minimum of Months | 7738.64 | 42.77 | -29.2 | |
Maximum of Months | 0.475459E+09 | 601.48 | 21.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202868E+10 | 1846.69 | 19-JAN-16:12 | -23.0 |
February | 0.128901E+10 | 1843.17 | 04-FEB-19:02 | -20.0 |
March | 0.706707E+09 | 1791.99 | 01-MAR-16:12 | -3.9 |
April | 0.301972E+09 | 1770.99 | 03-APR-08:62 | -5.9 |
May | 9933368.98 | 1145.54 | 26-MAY-18:04 | 19.32 |
June | 2343790.96 | 1033.91 | 04-JUN-18:04 | 13.22 |
July | 489427.52 | 683.15 | 11-JUL-18:04 | 18.80 |
August | 857634.05 | 968.77 | 06-AUG-08:04 | 12.80 |
September | 35979935.24 | 1204.50 | 22-SEP-15:14 | 15.00 |
October | 0.198997E+09 | 1707.97 | 26-OCT-08:62 | 1.28 |
November | 0.940920E+09 | 1831.83 | 26-NOV-16:23 | -13.9 |
December | 0.176164E+10 | 1865.64 | 09-DEC-16:23 | -19.1 |
Annual Sum or Average | 0.727753E+10 | |||
Minimum of Months | 489427.52 | 683.15 | -23.0 | |
Maximum of Months | 0.202868E+10 | 1865.64 | 19.32 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239715E+10 | 1860.34 | 31-JAN-16:11 | -20.2 |
February | 0.159795E+10 | 1977.19 | 02-FEB-17:52 | -30.6 |
March | 0.855558E+09 | 1795.86 | 05-MAR-16:11 | -9.8 |
April | 0.353632E+09 | 1762.93 | 03-APR-08:62 | -5.9 |
May | 11595778.83 | 1127.08 | 17-MAY-15:14 | 13.90 |
June | 2443611.45 | 1007.54 | 04-JUN-18:04 | 13.22 |
July | 382069.85 | 659.82 | 22-JUL-21:34 | 14.27 |
August | 787961.15 | 1023.19 | 06-AUG-08:04 | 12.80 |
September | 44247129.28 | 863.41 | 18-SEP-18:04 | 9.90 |
October | 0.303661E+09 | 1711.09 | 26-OCT-08:62 | 1.28 |
November | 0.112705E+10 | 1829.62 | 26-NOV-16:23 | -13.9 |
December | 0.205032E+10 | 1857.82 | 09-DEC-16:23 | -19.1 |
Annual Sum or Average | 0.874478E+10 | |||
Minimum of Months | 382069.85 | 659.82 | -30.6 | |
Maximum of Months | 0.239715E+10 | 1977.19 | 14.27 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.973983E+09 | 1537.00 | 20-JAN-07:45 | -23.5 |
February | 0.428929E+09 | 1661.90 | 04-FEB-11:02 | -23.6 |
March | 79073755.79 | 712.39 | 01-MAR-15:00 | -3.9 |
April | 10803646.46 | 443.04 | 03-APR-08:03 | -5.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.237983E+09 | 1405.72 | 26-NOV-16:00 | -13.9 |
December | 0.744572E+09 | 1521.48 | 09-DEC-17:00 | -19.4 |
Annual Sum or Average | 0.247535E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.6 | |
Maximum of Months | 0.973983E+09 | 1661.90 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286729E+10 | 2269.70 | 19-JAN-19:13 | -23.3 |
February | 0.184830E+10 | 2451.06 | 04-FEB-07:53 | -30.6 |
March | 0.111069E+10 | 2180.55 | 01-MAR-16:12 | -3.9 |
April | 0.463480E+09 | 2153.35 | 03-APR-08:62 | -5.9 |
May | 35315462.37 | 2061.30 | 02-MAY-08:61 | 4.08 |
June | 16102593.94 | 1153.26 | 04-JUN-08:03 | 11.38 |
July | 1585241.11 | 1007.93 | 31-JUL-08:04 | 18.42 |
August | 1751197.88 | 938.77 | 07-AUG-08:03 | 15.47 |
September | 99761708.83 | 2080.60 | 30-SEP-08:61 | 3.35 |
October | 0.394970E+09 | 2112.74 | 26-OCT-08:62 | 1.28 |
November | 0.139491E+10 | 2255.05 | 26-NOV-16:23 | -13.9 |
December | 0.247023E+10 | 2287.41 | 09-DEC-16:23 | -19.1 |
Annual Sum or Average | 0.107044E+11 | |||
Minimum of Months | 1585241.11 | 938.77 | -30.6 | |
Maximum of Months | 0.286729E+10 | 2451.06 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329067E+10 | 2415.21 | 31-JAN-07:53 | -30.0 |
February | 0.221147E+10 | 2442.47 | 04-FEB-10:53 | -23.9 |
March | 0.131643E+10 | 2170.63 | 06-MAR-09:02 | -9.5 |
April | 0.523890E+09 | 2142.34 | 03-APR-08:62 | -5.9 |
May | 37388599.35 | 2059.50 | 02-MAY-08:61 | 4.08 |
June | 16490729.22 | 1096.44 | 04-JUN-08:03 | 11.38 |
July | 508220.13 | 822.60 | 12-JUL-08:53 | 20.00 |
August | 981774.99 | 1071.96 | 18-AUG-08:53 | 21.10 |
September | 0.121191E+09 | 2101.74 | 30-SEP-08:61 | 3.35 |
October | 0.553656E+09 | 2110.53 | 23-OCT-08:62 | 0.70 |
November | 0.163428E+10 | 2247.08 | 26-NOV-16:23 | -13.9 |
December | 0.281406E+10 | 2274.01 | 09-DEC-16:23 | -19.1 |
Annual Sum or Average | 0.125210E+11 | |||
Minimum of Months | 508220.13 | 822.60 | -30.0 | |
Maximum of Months | 0.329067E+10 | 2442.47 | 21.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.999095E+09 | 1167.98 | 26-JAN-16:23 | -11.4 |
February | 0.567718E+09 | 1135.18 | 28-FEB-19:02 | -15.7 |
March | 0.337094E+09 | 1136.33 | 01-MAR-16:12 | -3.9 |
April | 0.153134E+09 | 1121.82 | 03-APR-08:62 | -5.9 |
May | 5046068.82 | 650.91 | 17-MAY-15:14 | 13.90 |
June | 1597368.77 | 636.24 | 01-JUN-15:14 | 11.97 |
July | 403884.83 | 500.19 | 31-JUL-08:04 | 18.42 |
August | 727748.05 | 487.53 | 23-AUG-08:04 | 18.98 |
September | 15908931.03 | 597.13 | 13-SEP-15:14 | 19.03 |
October | 58618204.52 | 1069.65 | 26-OCT-08:62 | 1.28 |
November | 0.427798E+09 | 1161.21 | 26-NOV-16:23 | -13.9 |
December | 0.873956E+09 | 1184.61 | 09-DEC-16:23 | -19.1 |
Annual Sum or Average | 0.344110E+10 | |||
Minimum of Months | 403884.83 | 487.53 | -19.1 | |
Maximum of Months | 0.999095E+09 | 1184.61 | 19.03 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 510216.13 | 1379.48 | 31-JAN-11:23 | -23.6 |
February | 290352.03 | 1597.80 | 04-FEB-11:02 | -23.6 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -0.7 |
Annual Sum or Average | 800568.16 | |||
Minimum of Months | 0.00 | 0.00 | -23.6 | |
Maximum of Months | 510216.13 | 1597.80 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 231884.34 | 657.48 | 31-JAN-11:23 | -23.6 |
February | 110680.04 | 737.87 | 04-FEB-11:02 | -23.6 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -0.7 |
Annual Sum or Average | 342564.38 | |||
Minimum of Months | 0.00 | 0.00 | -23.6 | |
Maximum of Months | 231884.34 | 737.87 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.465587E+10 | 4600.54 | 20-JAN-07:45 | -23.5 |
February | 0.235330E+10 | 4964.03 | 04-FEB-11:02 | -23.6 |
March | 0.592419E+09 | 2461.80 | 06-MAR-07:10 | -12.7 |
April | 55959710.21 | 1194.31 | 03-APR-06:10 | -7.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.118801E+10 | 4402.36 | 26-NOV-09:00 | -23.3 |
December | 0.321780E+10 | 4401.11 | 10-DEC-06:10 | -22.6 |
Annual Sum or Average | 0.120634E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.6 | |
Maximum of Months | 0.465587E+10 | 4964.03 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104372E+11 | 10053.14 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.942384E+10 | 10053.14 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.104694E+11 | 10053.14 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.100833E+11 | 10053.14 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.104553E+11 | 10053.14 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.101296E+11 | 10053.14 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.104091E+11 | 10053.14 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.104734E+11 | 10053.14 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.100874E+11 | 10053.14 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.104332E+11 | 10053.14 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.101215E+11 | 10053.14 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.104091E+11 | 10053.14 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.122932E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.942384E+10 | 10053.14 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.104734E+11 | 10053.14 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.195918E+09 | 188.71 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.176896E+09 | 188.71 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.196522E+09 | 188.71 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.189275E+09 | 188.71 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.196257E+09 | 188.71 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.190143E+09 | 188.71 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.195389E+09 | 188.71 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.196597E+09 | 188.71 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.189351E+09 | 188.71 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.195842E+09 | 188.71 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.189992E+09 | 188.71 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.195389E+09 | 188.71 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.230757E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.176896E+09 | 188.71 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.196597E+09 | 188.71 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.126047E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.108947E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.111446E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.985573E+09 | 1573.46 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.906064E+09 | 1573.46 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.846692E+09 | 1573.46 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.881186E+09 | 1573.46 | 03-JUL-19:00 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.956367E+09 | 1573.46 | 01-AUG-19:40 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.104098E+10 | 1573.46 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.117647E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.120052E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.128065E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.127389E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.846692E+09 | 1573.46 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.128065E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.796141E+10 | 7984.04 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.714340E+10 | 7984.04 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.785778E+10 | 7984.04 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.749802E+10 | 7984.04 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.767651E+10 | 7984.04 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.740658E+10 | 7984.04 | 01-JUN-19:40 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.761739E+10 | 7984.04 | 03-JUL-19:00 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.772708E+10 | 7984.04 | 01-AUG-19:40 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.754121E+10 | 7984.04 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.788358E+10 | 7984.04 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.770117E+10 | 7984.04 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.796638E+10 | 7984.04 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.919805E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.714340E+10 | 7984.04 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.796638E+10 | 7984.04 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65789991.58 | 59.53 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 59414784.75 | 59.53 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 65267117.48 | 59.53 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 63743496.62 | 59.53 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 65528554.53 | 59.53 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 63237765.93 | 59.53 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 66042856.93 | 59.53 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 65267117.48 | 59.53 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 63760640.03 | 59.53 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 65781419.88 | 59.53 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 63490631.27 | 59.53 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 66051428.64 | 59.53 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.773376E+09 | 0.256575E+10 | ||||
Minimum of Months | 59414784.75 | 59.53 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 66051428.64 | 59.53 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.256863E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.227466E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.242516E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.224496E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.220572E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.210014E+10 | 2763.12 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.217444E+10 | 2763.12 | 03-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.226016E+10 | 2763.12 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.230088E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.248570E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.247029E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.260123E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.281120E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.210014E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.260123E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.256863E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.227466E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.242516E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.224496E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.220572E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.210014E+10 | 2763.12 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.217444E+10 | 2763.12 | 03-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.226016E+10 | 2763.12 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.230088E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.248570E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.247029E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.260123E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.281120E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.210014E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.260123E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.104372E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.942384E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.104694E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.100833E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.104553E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.101296E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.104091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.104734E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.100874E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.104332E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.101215E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.104091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.122932E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.942384E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.104734E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523328E+09 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399396E+09 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312841E+09 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1508262.29 | 0.213188E+09 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1444761.28 | 0.122827E+09 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9991999.68 | 66854703.80 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7609945.35 | 46493981.71 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7688658.98 | 58619496.65 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5533347.55 | 0.110735E+09 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211602E+09 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309180E+09 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439606E+09 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33776975.13 | 0.281467E+10 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46493981.71 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9991999.68 | 0.523328E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201719E+09 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153960E+09 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120640E+09 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 818533.72 | 82295216.81 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 911189.46 | 46551927.86 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5091429.89 | 25298222.76 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4424739.59 | 17008978.05 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4337510.79 | 21698371.94 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2824740.20 | 42607157.52 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3430.74 | 81967088.89 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120105E+09 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169229E+09 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18411574.39 | 0.108308E+10 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17008978.05 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5091429.89 | 0.201719E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477639E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366761E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294155E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1375803.09 | 0.208289E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1316714.42 | 0.126871E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9111113.94 | 69123157.54 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6938798.70 | 46175196.79 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7006636.79 | 57459587.03 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5047637.31 | 0.112292E+09 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212799E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296008E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401833E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30796704.24 | 0.266940E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46175196.79 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9111113.94 | 0.477639E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.195918E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273471E+09 |
February | 0.339028E+09 | 0.176896E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206427E+09 |
March | 0.376747E+09 | 0.196522E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160483E+09 |
April | 0.363528E+09 | 0.189275E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1432289.44 | 0.106425E+09 |
May | 0.375778E+09 | 0.196257E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1664559.94 | 56042469.89 |
June | 0.364321E+09 | 0.190143E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8424037.81 | 29324146.50 |
July | 0.374985E+09 | 0.195389E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7843466.40 | 18120889.99 |
August | 0.376571E+09 | 0.196597E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7600823.16 | 24085357.91 |
September | 0.363352E+09 | 0.189351E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4816051.18 | 51554806.83 |
October | 0.375161E+09 | 0.195842E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37112.21 | 0.103746E+09 |
November | 0.362735E+09 | 0.189992E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159866E+09 |
December | 0.374985E+09 | 0.195389E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229346E+09 |
Annual Sum or Average | 0.442217E+10 | 0.230757E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31818340.14 | 0.141889E+10 |
Minimum of Months | 0.339028E+09 | 0.176896E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18120889.99 |
Maximum of Months | 0.376747E+09 | 0.196597E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8424037.81 | 0.273471E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707437E+09 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546642E+09 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434291E+09 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 1878652.17 | 0.299456E+09 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 1795436.76 | 0.174341E+09 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 12440090.25 | 94616814.51 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 9474733.49 | 63049999.85 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 9567517.44 | 78458531.50 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 6892424.61 | 0.154261E+09 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297341E+09 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431032E+09 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599441E+09 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 42048854.72 | 0.388037E+10 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63049999.85 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 12440090.25 | 0.707437E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.126047E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115615E+10 |
February | 0.236489E+11 | 0.108947E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883862E+09 |
March | 0.262800E+11 | 0.111446E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690248E+09 |
April | 0.253579E+11 | 0.985573E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4209639.74 | 0.466560E+09 |
May | 0.262123E+11 | 0.906064E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5375486.51 | 0.252040E+09 |
June | 0.254132E+11 | 0.846692E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32689564.01 | 0.132040E+09 |
July | 0.261570E+11 | 0.881186E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29494440.66 | 83193860.37 |
August | 0.262677E+11 | 0.956367E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26375702.82 | 0.110131E+09 |
September | 0.253456E+11 | 0.104098E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14799043.67 | 0.232532E+09 |
October | 0.261693E+11 | 0.117647E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465156E+09 |
November | 0.253025E+11 | 0.120052E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684806E+09 |
December | 0.261570E+11 | 0.128065E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970729E+09 |
Annual Sum or Average | 0.308468E+12 | 0.127389E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112944E+09 | 0.612745E+10 |
Minimum of Months | 0.236489E+11 | 0.846692E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83193860.37 |
Maximum of Months | 0.262800E+11 | 0.128065E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32689564.01 | 0.115615E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.796141E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333211E+10 |
February | 0.702046E+11 | 0.714340E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255953E+10 |
March | 0.780153E+11 | 0.785778E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202047E+10 |
April | 0.752779E+11 | 0.749802E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12715574.80 | 0.138262E+10 |
May | 0.778146E+11 | 0.767651E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14411430.69 | 0.786770E+09 |
June | 0.754422E+11 | 0.740658E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84053610.94 | 0.427434E+09 |
July | 0.776503E+11 | 0.761739E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73663079.40 | 0.284991E+09 |
August | 0.779788E+11 | 0.772708E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70027488.94 | 0.363368E+09 |
September | 0.752414E+11 | 0.754121E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43984758.98 | 0.718753E+09 |
October | 0.776868E+11 | 0.788358E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138738E+10 |
November | 0.751137E+11 | 0.770117E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200890E+10 |
December | 0.776503E+11 | 0.796638E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281054E+10 |
Annual Sum or Average | 0.915726E+12 | 0.919805E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298856E+09 | 0.180829E+11 |
Minimum of Months | 0.702046E+11 | 0.714340E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284991E+09 |
Maximum of Months | 0.780153E+11 | 0.796638E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84053610.94 | 0.333211E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298941E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228630E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177581E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1369554.98 | 0.118751E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1484815.14 | 63415053.22 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9470118.94 | 30527346.67 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8794935.28 | 16465659.61 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8164188.89 | 22837731.63 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023901.52 | 55522050.47 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6083.95 | 0.117135E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175361E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250043E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34313598.72 | 0.155521E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16465659.61 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9470118.94 | 0.298941E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297769E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226614E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175635E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1293842.73 | 0.118677E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1346432.61 | 66306628.07 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8790085.80 | 34713233.24 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7891058.71 | 22141800.25 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7457421.07 | 27856391.49 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4710303.17 | 57469509.47 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 111.33 | 0.115365E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173868E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248457E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31489255.40 | 0.156487E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22141800.25 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8790085.80 | 0.297769E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 65789991.58 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73666101.57 |
February | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60920972.12 |
March | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51151483.29 |
April | 0.00 | 63743496.62 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77226.03 | 41517857.83 |
May | 0.00 | 65528554.53 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59429.88 | 28409593.85 |
June | 0.00 | 63237765.93 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 650835.16 | 17062774.37 |
July | 0.00 | 66042856.93 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 244771.35 | 13203506.49 |
August | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 346168.40 | 15313903.64 |
September | 0.00 | 63760640.03 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 317291.37 | 25063388.75 |
October | 0.00 | 65781419.88 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43945478.81 |
November | 0.00 | 63490631.27 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52943945.75 |
December | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62302151.07 |
Annual Sum or Average | 0.00 | 0.773376E+09 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1695722.19 | 0.485501E+09 |
Minimum of Months | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13203506.49 |
Maximum of Months | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 650835.16 | 73666101.57 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83308242.05 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63375764.52 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49498452.55 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 373529.60 | 33123995.82 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 392136.40 | 17892148.74 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2496333.98 | 9094421.75 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2261851.45 | 5409458.53 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2158324.05 | 7092047.80 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1370310.24 | 15708683.11 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6861.55 | 32382754.85 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49072369.89 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69837935.81 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9059347.26 | 0.435796E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5409458.53 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2496333.98 | 83308242.05 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298769E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228450E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178249E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1373156.56 | 0.119065E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1486835.55 | 63929372.67 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9471275.78 | 30727110.03 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8808686.22 | 16614428.32 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8169574.73 | 23024830.82 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5035997.12 | 55926080.58 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6520.75 | 0.117638E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175261E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249776E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34352046.72 | 0.155743E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16614428.32 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9471275.78 | 0.298769E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297652E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226318E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176226E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1293309.13 | 0.118726E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335548.03 | 66101838.55 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8725875.95 | 34517628.84 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7841739.18 | 22099266.39 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7428770.34 | 27440512.10 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4687342.62 | 57654020.57 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.10 | 0.115533E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173738E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248384E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31312941.36 | 0.156439E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22099266.39 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8725875.95 | 0.297652E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366441E+09 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278557E+09 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215070E+09 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1566335.64 | 0.144807E+09 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1648853.44 | 81126925.62 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8505499.05 | 44852559.64 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6810233.42 | 30600715.23 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7036037.46 | 38306477.21 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4730100.08 | 74797106.43 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23024.21 | 0.140299E+09 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214038E+09 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306301E+09 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30320083.30 | 0.193520E+10 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30600715.23 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8505499.05 | 0.366441E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298758E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228026E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177125E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1344024.85 | 0.118655E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1452256.06 | 63710173.44 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9314923.59 | 30707972.15 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8594985.61 | 16674893.78 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7997177.77 | 23043192.16 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4931789.07 | 55545811.23 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5395.49 | 0.116919E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175018E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249866E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33640552.44 | 0.155405E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16674893.78 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9314923.59 | 0.298758E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297809E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226172E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175342E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1272509.85 | 0.118657E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1318357.54 | 67048426.56 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8650981.03 | 35395316.58 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7722923.77 | 22755744.49 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7319604.82 | 28483582.57 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4635344.45 | 57579946.16 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 618.00 | 0.114955E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173672E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248712E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30920339.46 | 0.156658E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22755744.49 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8650981.03 | 0.297809E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155048E+09 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118882E+09 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92193944.16 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 689186.27 | 61235319.82 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 745513.28 | 32715280.39 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4779961.79 | 15771155.82 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4417823.51 | 8501242.09 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4098681.49 | 11784522.75 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2523502.82 | 28758762.26 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1548.32 | 60934016.28 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91175902.86 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129631E+09 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17256217.49 | 0.806631E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8501242.09 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4779961.79 | 0.155048E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.256863E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751156E+09 |
February | 0.415303E+11 | 0.227466E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573230E+09 |
March | 0.461508E+11 | 0.242516E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454243E+09 |
April | 0.445315E+11 | 0.224496E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3322674.00 | 0.310453E+09 |
May | 0.460320E+11 | 0.220572E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3518091.29 | 0.176920E+09 |
June | 0.446286E+11 | 0.210014E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20045386.20 | 95947300.15 |
July | 0.459349E+11 | 0.217444E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18466783.79 | 62590179.18 |
August | 0.461292E+11 | 0.226016E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18350537.39 | 78788297.57 |
September | 0.445099E+11 | 0.230088E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12325648.17 | 0.157207E+09 |
October | 0.459565E+11 | 0.248570E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63247.84 | 0.305023E+09 |
November | 0.444343E+11 | 0.247029E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450684E+09 |
December | 0.459349E+11 | 0.260123E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633658E+09 |
Annual Sum or Average | 0.541708E+12 | 0.281120E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 76092368.67 | 0.404990E+10 |
Minimum of Months | 0.415303E+11 | 0.210014E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62590179.18 |
Maximum of Months | 0.461508E+11 | 0.260123E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20045386.20 | 0.751156E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.256863E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756216E+09 |
February | 0.415303E+11 | 0.227466E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579101E+09 |
March | 0.461508E+11 | 0.242516E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461500E+09 |
April | 0.445315E+11 | 0.224496E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3089933.44 | 0.317238E+09 |
May | 0.460320E+11 | 0.220572E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3143010.78 | 0.182153E+09 |
June | 0.446286E+11 | 0.210014E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18614138.56 | 99241179.43 |
July | 0.459349E+11 | 0.217444E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16647323.41 | 65398135.95 |
August | 0.461292E+11 | 0.226016E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16729520.81 | 81848900.14 |
September | 0.445099E+11 | 0.230088E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11469946.91 | 0.161668E+09 |
October | 0.459565E+11 | 0.248570E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36419.69 | 0.312652E+09 |
November | 0.444343E+11 | 0.247029E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457120E+09 |
December | 0.459349E+11 | 0.260123E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639280E+09 |
Annual Sum or Average | 0.541708E+12 | 0.281120E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 69730293.60 | 0.411342E+10 |
Minimum of Months | 0.415303E+11 | 0.210014E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65398135.95 |
Maximum of Months | 0.461508E+11 | 0.260123E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18614138.56 | 0.756216E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720919E+09 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556430E+09 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444171E+09 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 1859578.06 | 0.306663E+09 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1764518.36 | 0.179205E+09 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 12341358.98 | 97644168.96 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 9268192.70 | 65479348.96 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 9405570.21 | 81220099.19 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 6830892.83 | 0.158564E+09 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304614E+09 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440547E+09 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612494E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 41470111.14 | 0.396795E+10 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65479348.96 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 12341358.98 | 0.720919E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648831E+09 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492080E+09 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386080E+09 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1816134.54 | 0.267828E+09 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1723660.23 | 0.166372E+09 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12042572.51 | 92319049.46 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9028705.24 | 63687731.05 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9167159.63 | 78865858.64 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6663091.89 | 0.145288E+09 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262535E+09 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384765E+09 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543337E+09 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40441324.04 | 0.353199E+10 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63687731.05 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12042572.51 | 0.648831E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 10053.14 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 10053.14 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 10053.14 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 10053.14 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 10053.14 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 10053.14 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 10053.14 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 10053.14 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 10053.14 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 10053.14 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 10053.14 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 10053.14 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 313.21 | 31-JAN-04:00 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 347.28 | 02-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 224.78 | 06-MAR-01:00 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.31 | 15-APR-15:10 | 160.25 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 31-MAY-13:00 | 113.03 | 03-MAY-03:00 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.12 | 11-JUN-15:00 | 94.33 | 01-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 | 26-JUL-15:10 | 67.89 | 24-JUL-03:00 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.89 | 04-AUG-15:00 | 75.11 | 07-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.37 | 07-SEP-14:00 | 122.56 | 30-SEP-01:00 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 136.82 | 23-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 298.49 | 26-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 263.51 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.89 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 47.89 | 347.28 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 123.35 | 31-JAN-04:00 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 138.06 | 02-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 87.12 | 06-MAR-01:00 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.96 | 15-APR-16:00 | 62.01 | 03-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.97 | 31-MAY-13:00 | 46.18 | 03-MAY-03:00 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.56 | 11-JUN-15:00 | 37.81 | 01-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.34 | 26-JUL-15:00 | 27.14 | 24-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 04-AUG-15:00 | 30.68 | 07-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 06-SEP-14:00 | 49.51 | 30-SEP-01:00 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 | 20-OCT-15:00 | 54.93 | 23-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 117.47 | 26-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 102.02 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.14 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 138.06 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 291.19 | 31-JAN-04:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 328.26 | 02-FEB-06:30 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 205.07 | 06-MAR-01:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.74 | 15-APR-15:00 | 150.79 | 03-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.91 | 31-MAY-13:00 | 114.46 | 03-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.16 | 11-JUN-15:00 | 92.63 | 01-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.11 | 26-JUL-15:00 | 67.99 | 23-JUL-04:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.69 | 04-AUG-15:00 | 76.61 | 07-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 07-SEP-14:00 | 124.35 | 30-SEP-01:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 138.16 | 23-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 278.94 | 26-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 242.44 | 08-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.99 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 43.69 | 328.26 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 188.71 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 164.24 | 31-JAN-04:00 |
February | 220.32 | 01-FEB-00:10 | 188.71 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 184.42 | 02-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 188.71 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 118.31 | 06-MAR-01:00 |
April | 220.32 | 01-APR-00:10 | 188.71 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 15-APR-17:00 | 84.34 | 03-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 188.71 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 | 31-MAY-13:00 | 59.48 | 03-MAY-03:00 |
June | 220.32 | 01-JUN-00:10 | 188.71 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 | 11-JUN-15:00 | 48.06 | 01-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 188.71 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 | 26-JUL-16:00 | 33.36 | 24-JUL-03:00 |
August | 220.32 | 01-AUG-00:10 | 188.71 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 04-AUG-16:00 | 38.61 | 07-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 188.71 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.94 | 06-SEP-14:00 | 64.50 | 30-SEP-01:00 |
October | 220.32 | 01-OCT-23:10 | 188.71 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 | 20-OCT-15:00 | 72.01 | 23-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 188.71 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 157.68 | 26-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 188.71 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 138.82 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.36 | |||||
Maximum of Months | 220.32 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 184.42 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 427.45 | 31-JAN-04:00 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 485.99 | 02-FEB-08:00 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 302.00 | 06-MAR-01:00 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 36.52 | 15-APR-15:10 | 220.83 | 03-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 36.74 | 31-MAY-13:00 | 161.48 | 03-MAY-03:00 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 56.20 | 11-JUN-15:00 | 127.13 | 03-JUN-04:00 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 37.02 | 26-JUL-15:10 | 92.83 | 23-JUL-04:00 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 59.66 | 04-AUG-15:10 | 104.60 | 07-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 50.30 | 07-SEP-14:00 | 173.37 | 30-SEP-01:00 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 191.44 | 23-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 403.78 | 26-NOV-07:00 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 351.77 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 92.83 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 59.66 | 485.99 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 707.73 | 31-JAN-04:00 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 782.61 | 02-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 496.98 | 06-MAR-01:00 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.36 | 15-APR-17:00 | 354.30 | 03-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1573.46 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.80 | 31-MAY-13:00 | 262.80 | 03-MAY-03:00 |
June | 15368.40 | 01-JUN-00:10 | 1573.46 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.26 | 11-JUN-16:00 | 210.73 | 01-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1573.46 | 03-JUL-19:00 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.11 | 26-JUL-18:00 | 150.55 | 24-JUL-03:00 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 01-AUG-19:40 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.00 | 04-AUG-16:00 | 169.57 | 07-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.26 | 07-SEP-14:00 | 280.88 | 30-SEP-01:00 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 303.01 | 23-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 666.52 | 26-NOV-07:00 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 584.35 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.55 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 112.00 | 782.61 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 7984.04 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2047.80 | 31-JAN-04:00 |
February | 45622.98 | 01-FEB-00:10 | 7984.04 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2288.44 | 02-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 7984.04 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1455.75 | 06-MAR-01:00 |
April | 45622.98 | 01-APR-00:10 | 7984.04 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.23 | 15-APR-16:00 | 1049.10 | 03-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 7984.04 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.22 | 31-MAY-13:00 | 781.48 | 03-MAY-03:00 |
June | 45622.98 | 01-JUN-00:10 | 7984.04 | 01-JUN-19:40 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.53 | 11-JUN-15:00 | 633.16 | 01-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 7984.04 | 03-JUL-19:00 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.90 | 26-JUL-15:00 | 458.93 | 24-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 7984.04 | 01-AUG-19:40 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.35 | 04-AUG-15:00 | 515.71 | 07-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 7984.04 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.67 | 06-SEP-14:00 | 840.47 | 30-SEP-01:00 |
October | 45622.98 | 01-OCT-23:10 | 7984.04 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 920.65 | 23-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 7984.04 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1931.31 | 26-NOV-07:00 |
December | 45622.98 | 01-DEC-00:10 | 7984.04 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1688.87 | 08-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.93 | |||||
Maximum of Months | 45622.98 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 323.35 | 2288.44 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.12 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 210.14 | 02-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 131.00 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 | 15-APR-16:40 | 93.51 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 | 31-MAY-15:20 | 66.09 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.72 | 11-JUN-15:20 | 50.37 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 | 26-JUL-15:20 | 34.46 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 | 04-AUG-16:00 | 39.90 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.10 | 07-SEP-16:00 | 71.62 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 | 20-OCT-15:20 | 79.91 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 178.02 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 153.95 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 | 210.14 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 184.94 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 207.85 | 02-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 130.99 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 | 15-APR-15:20 | 93.51 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 | 31-MAY-15:20 | 66.09 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.72 | 11-JUN-15:20 | 50.36 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 | 26-JUL-15:20 | 34.46 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 | 04-AUG-15:20 | 39.90 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.54 | 06-SEP-15:20 | 71.61 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 | 20-OCT-12:40 | 79.90 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 177.17 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 153.93 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 | 207.85 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 59.53 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 47.10 | 31-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 59.53 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 54.44 | 02-FEB-06:10 |
March | 0.00 | 01-MAR-00:10 | 59.53 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 32.12 | 06-MAR-01:00 |
April | 0.00 | 01-APR-00:10 | 59.53 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 | 15-APR-15:10 | 28.02 | 01-APR-05:00 |
May | 0.00 | 01-MAY-00:10 | 59.53 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 | 31-MAY-13:00 | 22.43 | 03-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 59.53 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 | 11-JUN-15:00 | 18.78 | 01-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 59.53 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | 26-JUL-15:00 | 14.39 | 24-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 59.53 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 | 04-AUG-15:00 | 15.95 | 07-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 59.53 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 | 07-SEP-14:00 | 23.30 | 30-SEP-01:00 |
October | 0.00 | 01-OCT-00:10 | 59.53 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 26.00 | 23-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 59.53 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 45.02 | 26-NOV-07:00 |
December | 0.00 | 01-DEC-00:10 | 59.53 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 41.02 | 08-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.39 | |||||
Maximum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 | 54.44 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 50.38 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 57.92 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 36.56 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 15-APR-15:20 | 26.10 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 | 31-MAY-15:20 | 18.45 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 | 11-JUN-15:20 | 14.06 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 | 26-JUL-15:20 | 9.62 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 04-AUG-15:20 | 11.14 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 06-SEP-15:20 | 19.99 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 20-OCT-15:00 | 22.30 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 48.72 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 42.96 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 57.92 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 185.91 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 209.30 | 02-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 131.00 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.09 | 15-APR-15:20 | 93.51 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 | 31-MAY-15:20 | 66.09 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.73 | 11-JUN-15:18 | 50.36 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 | 26-JUL-15:20 | 34.46 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 04-AUG-15:20 | 39.90 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.54 | 06-SEP-15:20 | 71.62 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 | 20-OCT-15:20 | 79.91 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 177.62 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 153.94 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 209.30 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 183.52 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 207.54 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 130.99 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 | 15-APR-15:18 | 93.51 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 | 31-MAY-15:20 | 66.09 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.72 | 11-JUN-15:20 | 50.36 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 | 26-JUL-15:18 | 34.46 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 04-AUG-15:20 | 39.90 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.54 | 06-SEP-15:20 | 71.62 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 20-OCT-15:00 | 79.90 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 176.35 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 153.93 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 207.54 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 226.04 | 31-JAN-04:00 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 254.97 | 02-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 157.95 | 06-MAR-01:00 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.19 | 15-APR-17:00 | 112.64 | 03-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 | 31-MAY-13:00 | 80.92 | 03-MAY-03:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.44 | 11-JUN-15:00 | 67.20 | 01-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 | 26-JUL-16:00 | 48.78 | 24-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 | 04-AUG-16:00 | 55.41 | 07-AUG-04:00 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.45 | 06-SEP-14:00 | 86.40 | 30-SEP-01:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 20-OCT-15:00 | 96.19 | 23-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 213.88 | 26-NOV-07:00 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 185.68 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.78 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.44 | 254.97 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 185.13 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 207.83 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 131.23 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 | 15-APR-16:30 | 93.73 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 | 31-MAY-15:20 | 66.30 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.38 | 11-JUN-15:20 | 50.56 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.26 | 26-JUL-15:20 | 34.65 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.60 | 04-AUG-16:00 | 40.10 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.49 | 07-SEP-16:00 | 71.83 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 | 20-OCT-15:20 | 80.12 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 177.13 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 154.19 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.65 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 35.60 | 207.83 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 182.47 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 207.17 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 131.22 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 | 15-APR-16:30 | 93.72 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.45 | 31-MAY-15:20 | 66.29 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.23 | 11-JUN-15:20 | 50.56 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.26 | 26-JUL-15:20 | 34.65 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.60 | 04-AUG-16:00 | 40.09 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.32 | 06-SEP-15:20 | 71.82 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 20-OCT-12:40 | 80.11 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 175.66 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 154.18 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.65 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.60 | 207.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 96.63 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 108.68 | 02-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 67.14 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.75 | 15-APR-15:20 | 47.96 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 31-MAY-15:20 | 33.92 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 11-JUN-15:20 | 25.87 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 26-JUL-15:20 | 17.73 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 | 04-AUG-15:20 | 20.52 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.34 | 06-SEP-15:20 | 36.75 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 | 20-OCT-15:20 | 40.99 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 91.21 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 78.89 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.73 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 | 108.68 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 453.82 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 501.94 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 328.05 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.19 | 15-APR-16:00 | 238.05 | 03-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.87 | 31-MAY-13:00 | 175.85 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.47 | 11-JUN-15:00 | 141.24 | 01-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.87 | 26-JUL-15:00 | 102.12 | 24-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.96 | 04-AUG-15:00 | 114.71 | 07-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.65 | 06-SEP-14:00 | 188.57 | 30-SEP-01:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.75 | 20-OCT-15:00 | 207.45 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 432.91 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 385.62 | 08-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.12 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 75.96 | 501.94 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 456.37 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 504.96 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 330.86 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.87 | 15-APR-16:00 | 240.78 | 03-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.84 | 31-MAY-13:00 | 178.22 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.41 | 11-JUN-15:00 | 142.76 | 01-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.89 | 26-JUL-15:00 | 103.65 | 24-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.07 | 04-AUG-15:00 | 116.56 | 07-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.82 | 06-SEP-14:00 | 191.34 | 30-SEP-01:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.29 | 20-OCT-15:00 | 210.23 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 434.42 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 388.59 | 08-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.65 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 74.07 | 504.96 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 430.74 | 31-JAN-06:20 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 492.13 | 02-FEB-08:20 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 308.41 | 06-MAR-01:00 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 36.65 | 15-APR-16:50 | 225.66 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 36.86 | 31-MAY-13:00 | 165.20 | 03-MAY-03:00 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 56.69 | 11-JUN-15:00 | 130.19 | 03-JUN-04:00 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 37.17 | 26-JUL-15:50 | 95.24 | 23-JUL-04:00 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 60.22 | 04-AUG-15:10 | 107.20 | 07-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 50.66 | 07-SEP-14:00 | 177.31 | 30-SEP-01:00 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 195.71 | 23-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 412.03 | 26-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 359.13 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 95.24 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 60.22 | 492.13 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 393.02 | 31-JAN-04:00 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 439.74 | 02-FEB-06:00 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 279.97 | 06-MAR-01:00 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.79 | 15-APR-15:00 | 199.77 | 03-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.01 | 31-MAY-13:00 | 147.38 | 03-MAY-03:00 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.42 | 11-JUN-15:00 | 124.94 | 01-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.28 | 26-JUL-15:10 | 91.39 | 24-JUL-03:00 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.87 | 04-AUG-15:00 | 101.48 | 07-AUG-04:00 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.52 | 07-SEP-14:00 | 155.74 | 30-SEP-01:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 172.42 | 23-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 374.24 | 26-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 328.66 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.39 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.87 | 439.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 20061.75 | 30-JAN-07:52 | 30671.71 | 33510.20 | 36502.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19718.57 | 01-FEB-21:40 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11783.61 | 01-MAR-21:00 | 8945.92 | 10053.14 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12024.52 | 16-APR-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12605.95 | 29-MAY-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13823.39 | 25-JUN-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14601.67 | 30-JUL-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15289.48 | 27-AUG-10:35 | 7667.93 | 6702.09 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17496.57 | 21-SEP-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18183.82 | 25-OCT-21:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20819.71 | 26-NOV-07:00 | 8945.92 | 3351.05 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15853.91 | 01-DEC-22:00 | 10223.90 | 8936.08 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11783.61 | 7667.93 | 3351.05 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20819.71 | 30671.71 | 33510.20 | 36502.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2095.55 | 12-JAN-12:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.20 |
February | 2863.16 | 08-FEB-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.64 |
March | 2565.55 | 24-MAR-13:00 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.26 |
April | 3684.77 | 15-APR-13:15 | 779.69 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 | 0.00 |
May | 2830.69 | 06-MAY-13:00 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.05 |
June | 3128.81 | 30-JUN-13:00 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 26.81 | 0.00 |
July | 3318.58 | 30-JUL-12:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 13.48 | 0.00 |
August | 3592.89 | 29-AUG-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 |
September | 4473.07 | 07-SEP-12:50 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 | 0.00 |
October | 4032.65 | 20-OCT-12:50 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 |
November | 3805.07 | 04-NOV-12:50 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.43 |
December | 2904.58 | 03-DEC-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2095.55 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4473.07 | 779.69 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 | 119.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1588.75 | 05-JAN-21:55 | 2407.68 | 1054.69 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.96 |
February | 1259.01 | 24-FEB-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.36 |
March | 1350.48 | 24-MAR-20:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.43 |
April | 1549.55 | 16-APR-10:35 | 902.88 | 395.51 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 0.00 |
May | 1635.81 | 31-MAY-20:55 | 2407.68 | 1054.69 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.51 |
June | 1855.93 | 30-JUN-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 |
July | 1820.70 | 03-JUL-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 0.00 |
August | 1771.97 | 04-AUG-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.22 |
September | 1831.40 | 07-SEP-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 |
October | 1459.96 | 20-OCT-20:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 |
November | 1434.43 | 25-NOV-21:23 | 3160.08 | 1384.28 | 2005.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.64 |
December | 1166.67 | 05-DEC-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1166.67 | 902.88 | 395.51 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1855.93 | 3160.08 | 1384.28 | 2005.72 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 105.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21.33 | 05-JAN-22:20 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.59 |
February | 18.08 | 24-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.48 |
March | 194.49 | 29-MAR-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.88 |
April | 1070.51 | 18-APR-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.59 |
May | 1274.19 | 31-MAY-20:55 | 509.18 | 1216.31 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 |
June | 1512.21 | 26-JUN-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 | 0.00 |
July | 1457.60 | 03-JUL-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 | 0.00 |
August | 1491.53 | 04-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 |
September | 1392.73 | 08-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 |
October | 649.31 | 11-OCT-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.32 |
November | 532.81 | 03-NOV-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.38 |
December | 16.78 | 05-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16.78 | 222.77 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1512.21 | 509.18 | 1216.31 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 | 251.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 298.26 | 13-JAN-22:00 | 195.84 | 167.74 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.12 |
February | 428.63 | 24-FEB-22:00 | 195.84 | 167.74 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 |
March | 662.12 | 28-MAR-20:00 | 171.36 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 |
April | 888.86 | 16-APR-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3.92 | 0.00 |
May | 920.67 | 31-MAY-10:35 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 0.00 |
June | 971.03 | 30-JUN-10:35 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 0.00 |
July | 974.28 | 02-JUL-10:35 | 146.88 | 125.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 14.16 | 0.00 |
August | 955.12 | 04-AUG-10:35 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 0.00 |
September | 954.27 | 08-SEP-10:35 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 16.04 | 0.00 |
October | 727.20 | 21-OCT-10:35 | 146.88 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.23 |
November | 693.02 | 03-NOV-20:00 | 171.36 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.27 |
December | 250.89 | 03-DEC-21:00 | 146.88 | 167.74 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 250.89 | 97.92 | 104.84 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 974.28 | 195.84 | 188.71 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 64.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36928.80 | 13-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 166.15 |
February | 37279.04 | 24-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 147.14 |
March | 37706.67 | 28-MAR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 79.87 |
April | 38649.26 | 18-APR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 36.30 |
May | 38948.81 | 31-MAY-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 2.47 | 0.00 |
June | 39154.79 | 26-JUN-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 16.95 | 0.00 |
July | 38984.03 | 03-JUL-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 16.74 | 0.00 |
August | 39027.58 | 04-AUG-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 |
September | 39057.03 | 07-SEP-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 38156.53 | 20-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 57.78 |
November | 37807.15 | 03-NOV-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 108.39 |
December | 36705.71 | 01-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 201.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36705.71 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39154.79 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 16.95 | 201.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9798.61 | 30-JAN-13:10 | 6830.40 | 192.31 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.58 |
February | 10753.94 | 08-FEB-11:40 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.73 |
March | 9998.93 | 19-MAR-10:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.52 |
April | 12602.54 | 15-APR-13:30 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 | 0.00 |
May | 11099.18 | 31-MAY-18:10 | 71719.20 | 1846.19 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 48.04 | 0.00 |
June | 11635.94 | 26-JUN-18:10 | 71719.20 | 1846.19 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 75.02 | 0.00 |
July | 11972.40 | 30-JUL-10:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 20.08 | 0.00 |
August | 11840.29 | 27-AUG-10:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 29.41 | 0.00 |
September | 13901.61 | 07-SEP-13:00 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 83.96 | 0.00 |
October | 13588.64 | 20-OCT-12:50 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.92 |
November | 13854.66 | 04-NOV-12:50 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.32 |
December | 11440.64 | 03-DEC-13:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9798.61 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13901.61 | 71719.20 | 1846.19 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 83.96 | 618.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34303.12 | 05-JAN-21:55 | 81107.52 | 14193.84 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1750.77 |
February | 32590.11 | 01-FEB-00:05 | 91245.96 | 3548.46 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1716.07 |
March | 28746.09 | 24-MAR-20:00 | 35484.54 | 7984.04 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.56 |
April | 33189.19 | 18-APR-21:10 | 91245.96 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.95 |
May | 34141.89 | 31-MAY-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.15 |
June | 36842.80 | 26-JUN-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 44.76 | 0.00 |
July | 36141.27 | 27-JUL-21:10 | 91245.96 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.87 |
August | 36418.30 | 04-AUG-21:10 | 91245.96 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.60 |
September | 37937.22 | 07-SEP-21:10 | 45622.98 | 5322.69 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.34 |
October | 31445.23 | 20-OCT-21:10 | 91245.96 | 10645.38 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.02 |
November | 31138.99 | 25-NOV-21:23 | 106453.62 | 18629.42 | 25336.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1729.27 |
December | 26739.80 | 03-DEC-11:35 | 30415.32 | 4577.51 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26739.80 | 30415.32 | 3548.46 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37937.22 | 106453.62 | 18629.42 | 25336.95 | 0.00 | 0.00 | 0.00 | 0.00 | 44.76 | 1750.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2395.95 | 12-JAN-16:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.43 |
February | 3586.80 | 17-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.37 |
March | 3757.89 | 22-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.99 |
April | 3790.03 | 26-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 |
May | 3811.02 | 21-MAY-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 |
June | 3320.15 | 17-JUN-18:02 | 702.00 | 568.30 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 | 0.00 |
July | 3346.77 | 21-JUL-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 |
August | 3316.80 | 12-AUG-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 |
September | 3303.61 | 17-SEP-08:61 | 378.00 | 371.29 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.80 |
October | 3261.09 | 10-OCT-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 |
November | 3695.48 | 12-NOV-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.58 |
December | 3474.30 | 01-DEC-16:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2395.95 | 378.00 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3811.02 | 970.20 | 663.02 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 | 93.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 291.85 | 12-JAN-16:13 | 583.20 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.51 |
February | 2586.47 | 25-FEB-16:11 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.21 |
March | 3443.97 | 21-MAR-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.47 |
April | 3665.75 | 29-APR-18:41 | 936.00 | 757.64 | 969.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.39 |
May | 4219.20 | 20-MAY-18:41 | 1170.00 | 947.05 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 |
June | 3684.32 | 16-JUN-16:32 | 583.20 | 159.11 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 |
July | 3586.70 | 23-JUL-21:51 | 1386.00 | 805.00 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.98 |
August | 3740.87 | 11-AUG-18:11 | 1386.00 | 842.88 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 |
September | 3427.80 | 12-SEP-21:11 | 1800.00 | 634.53 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.81 |
October | 3028.43 | 10-OCT-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.35 |
November | 2912.53 | 03-NOV-16:11 | 680.40 | 185.62 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.96 |
December | 419.85 | 01-DEC-16:13 | 583.20 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 291.85 | 378.00 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 | |
Maximum of Months | 4219.20 | 1800.00 | 947.05 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 206.75 | 30-JAN-15:05 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.40 |
February | 243.89 | 02-FEB-15:05 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.63 |
March | 382.41 | 24-MAR-13:10 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.03 |
April | 567.75 | 15-APR-13:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 | 0.00 |
May | 420.68 | 06-MAY-13:00 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 |
June | 434.50 | 26-JUN-12:50 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 0.00 |
July | 472.72 | 30-JUL-13:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
August | 539.60 | 29-AUG-13:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
September | 668.58 | 07-SEP-13:00 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 0.00 |
October | 651.54 | 20-OCT-12:50 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 |
November | 622.50 | 04-NOV-12:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 |
December | 126.48 | 07-DEC-15:05 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 126.48 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 668.58 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 47.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 219.24 | 13-JAN-19:03 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.18 |
February | 718.87 | 25-FEB-09:02 | 270.00 | 166.72 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.05 |
March | 960.45 | 23-MAR-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.51 |
April | 1046.58 | 30-APR-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 |
May | 1080.12 | 06-MAY-19:31 | 1170.00 | 595.42 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 |
June | 1019.71 | 23-JUN-21:51 | 1620.00 | 359.04 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 |
July | 1006.57 | 25-JUL-15:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 0.00 |
August | 1040.59 | 11-AUG-18:11 | 1386.00 | 529.92 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 | 0.00 |
September | 1049.93 | 19-SEP-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.38 |
October | 984.00 | 12-OCT-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 |
November | 966.35 | 04-NOV-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.01 |
December | 233.90 | 03-DEC-09:02 | 324.00 | 200.06 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 219.24 | 270.00 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1080.12 | 1620.00 | 595.42 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 20.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 753.57 | 12-JAN-09:03 | 216.00 | 250.05 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.20 |
February | 2834.46 | 21-FEB-09:02 | 216.00 | 250.05 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.80 |
March | 3225.98 | 21-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.54 |
April | 3414.54 | 26-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 |
May | 3414.52 | 06-MAY-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.30 |
June | 3094.89 | 29-JUN-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 | 0.00 |
July | 3143.94 | 30-JUL-08:61 | 378.00 | 371.29 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.23 |
August | 3133.61 | 03-AUG-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 | 0.00 |
September | 3114.54 | 09-SEP-08:61 | 378.00 | 371.29 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.22 |
October | 2957.59 | 21-OCT-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.85 |
November | 2897.49 | 03-NOV-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 |
December | 2137.51 | 03-DEC-09:02 | 324.00 | 318.25 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 753.57 | 216.00 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3414.54 | 819.00 | 663.02 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 | 84.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 436.18 | 12-JAN-09:05 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.19 |
February | 2203.46 | 24-FEB-09:02 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.62 |
March | 2445.02 | 28-MAR-08:62 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.99 |
April | 3373.97 | 18-APR-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 |
May | 3473.48 | 31-MAY-08:32 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 |
June | 3685.72 | 09-JUN-08:32 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.05 |
July | 3593.31 | 01-JUL-08:32 | 324.00 | 318.21 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 |
August | 3582.63 | 11-AUG-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 |
September | 3583.13 | 17-SEP-08:51 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 |
October | 2739.79 | 01-OCT-08:61 | 378.00 | 371.25 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.68 |
November | 2408.06 | 04-NOV-08:62 | 324.00 | 318.21 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.45 |
December | 597.74 | 02-DEC-09:03 | 324.00 | 318.21 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 436.18 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | |
Maximum of Months | 3685.72 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1123.31 | 13-JAN-22:20 | 2263.36 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.48 |
February | 1331.41 | 24-FEB-21:00 | 1760.39 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.75 |
March | 1527.74 | 20-MAR-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.71 |
April | 1995.99 | 18-APR-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.71 | 0.00 |
May | 2061.78 | 31-MAY-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 | 0.00 |
June | 2219.27 | 30-JUN-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 0.00 |
July | 2256.08 | 02-JUL-10:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 | 0.00 |
August | 2168.70 | 02-AUG-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.61 | 0.00 |
September | 2190.78 | 09-SEP-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.44 | 0.00 |
October | 1616.55 | 20-OCT-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 |
November | 1588.42 | 04-NOV-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.42 |
December | 1368.71 | 03-DEC-11:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1123.31 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2256.08 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 | 72.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2472.06 | 12-JAN-16:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.85 |
February | 3384.10 | 17-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.93 |
March | 3894.60 | 22-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.01 |
April | 3953.25 | 26-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.23 |
May | 3975.29 | 21-MAY-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.89 |
June | 3469.78 | 17-JUN-18:02 | 702.00 | 568.30 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 | 0.00 |
July | 3478.44 | 21-JUL-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.34 |
August | 3450.52 | 30-AUG-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 |
September | 3903.10 | 20-SEP-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 |
October | 3339.46 | 10-OCT-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 |
November | 3843.25 | 12-NOV-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.72 |
December | 3391.35 | 01-DEC-16:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2472.06 | 378.00 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3975.29 | 970.20 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 | 91.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 744.81 | 13-JAN-16:14 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.54 |
February | 2645.35 | 25-FEB-16:11 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.84 |
March | 3565.91 | 21-MAR-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.53 |
April | 3879.99 | 29-APR-18:41 | 936.00 | 757.64 | 969.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 |
May | 4422.63 | 20-MAY-18:41 | 1170.00 | 947.05 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.79 |
June | 3843.32 | 16-JUN-16:32 | 583.20 | 159.11 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 |
July | 3881.91 | 23-JUL-21:51 | 1386.00 | 805.00 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.32 |
August | 3879.14 | 11-AUG-18:11 | 1386.00 | 842.88 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 |
September | 3566.67 | 12-SEP-21:11 | 1800.00 | 634.53 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 |
October | 3157.37 | 10-OCT-16:52 | 583.20 | 159.11 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.98 |
November | 3067.27 | 03-NOV-16:11 | 680.40 | 185.62 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.34 |
December | 289.35 | 02-DEC-16:13 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 289.35 | 378.00 | 159.11 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | |
Maximum of Months | 4422.63 | 1800.00 | 947.05 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2201.32 | 30-JAN-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.43 |
February | 2037.21 | 17-FEB-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.96 |
March | 2065.39 | 21-MAR-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 |
April | 1891.25 | 29-APR-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.89 |
May | 2012.45 | 21-MAY-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 |
June | 1794.31 | 08-JUN-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
July | 1858.60 | 07-JUL-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
August | 1828.57 | 23-AUG-15:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
September | 2041.50 | 20-SEP-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 |
October | 1799.75 | 02-OCT-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 |
November | 2016.34 | 21-NOV-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.06 |
December | 2034.03 | 05-DEC-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1794.31 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2201.32 | 970.20 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 84.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21191.85 | 31-JAN-23:53 | 107955.07 | 3684.16 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.59 |
February | 16371.35 | 24-FEB-22:00 | 23990.02 | 2456.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.18 |
March | 17324.45 | 28-MAR-21:00 | 23990.02 | 2456.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.80 |
April | 20224.82 | 18-APR-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.75 |
May | 20661.93 | 31-MAY-21:52 | 215910.14 | 14736.65 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.97 |
June | 21389.11 | 26-JUN-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 0.00 |
July | 21161.48 | 03-JUL-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 |
August | 20948.52 | 03-AUG-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
September | 20491.63 | 11-SEP-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.98 |
October | 17789.28 | 20-OCT-21:00 | 23990.02 | 2456.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.57 |
November | 18845.62 | 25-NOV-21:23 | 62973.79 | 6447.29 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.20 |
December | 16076.28 | 04-DEC-23:10 | 26988.77 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16076.28 | 23990.02 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21389.11 | 215910.14 | 14736.65 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 388.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21877.59 | 31-JAN-23:53 | 107955.07 | 3684.16 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.41 |
February | 19319.18 | 01-FEB-00:05 | 53977.54 | 1228.05 | 4498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.34 |
March | 18548.90 | 28-MAR-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.11 |
April | 20827.05 | 18-APR-21:53 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.36 |
May | 22066.34 | 31-MAY-21:52 | 215910.14 | 14736.65 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.97 |
June | 22830.50 | 26-JUN-21:30 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 0.00 |
July | 22569.85 | 03-JUL-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 0.00 |
August | 22342.12 | 03-AUG-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
September | 21599.03 | 07-SEP-21:52 | 215910.14 | 14736.65 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.39 |
October | 19832.87 | 11-OCT-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.27 |
November | 19832.65 | 08-NOV-22:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.61 |
December | 16877.46 | 04-DEC-23:10 | 26988.77 | 921.04 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16877.46 | 26988.77 | 921.04 | 4498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22830.50 | 215910.14 | 14736.65 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 391.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25168.43 | 13-JAN-11:50 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 139.18 |
February | 26162.56 | 24-FEB-11:35 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 123.06 |
March | 27532.77 | 19-MAR-10:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 64.59 |
April | 29349.87 | 15-APR-10:40 | 1601.14 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 3.62 | 0.00 |
May | 29854.55 | 31-MAY-10:40 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 24.16 | 0.00 |
June | 30199.20 | 11-JUN-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 34.70 | 0.00 |
July | 30241.02 | 02-JUL-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 22.99 | 0.00 |
August | 29807.77 | 01-AUG-10:40 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 17.49 | 0.00 |
September | 29943.08 | 08-SEP-10:40 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 26.86 | 0.00 |
October | 27720.86 | 01-OCT-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 |
November | 27269.49 | 04-NOV-10:40 | 1601.14 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 94.55 |
December | 25578.66 | 03-DEC-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 131.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25168.43 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30241.02 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 34.70 | 139.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1452.24 | 13-JAN-11:50 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.40 |
February | 1623.10 | 24-FEB-11:35 | 1064.64 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.42 |
March | 1843.47 | 20-MAR-10:50 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.64 |
April | 4370.14 | 18-APR-15:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.31 | 0.00 |
May | 5141.11 | 31-MAY-15:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.28 | 0.00 |
June | 5988.42 | 30-JUN-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.64 | 0.00 |
July | 5950.96 | 29-JUL-13:30 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.95 | 0.00 |
August | 6209.55 | 04-AUG-15:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.87 | 0.00 |
September | 6580.05 | 07-SEP-13:20 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.54 | 0.00 |
October | 1976.56 | 20-OCT-10:50 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 |
November | 1950.11 | 04-NOV-10:50 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.24 |
December | 1552.27 | 03-DEC-11:50 | 798.48 | 409.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1452.24 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6580.05 | 1330.80 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.87 | 117.40 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.362581E+12 | 218560.74 | 20-JAN-07:40 | 0.851692E+12 | 908954.99 | 30-JAN-19:19 |
February | 0.321417E+12 | 214760.12 | 03-FEB-07:30 | 0.745115E+12 | 959733.38 | 02-FEB-19:19 |
March | 0.351036E+12 | 211585.97 | 17-MAR-06:19 | 0.581175E+12 | 517051.12 | 13-MAR-18:10 |
April | 0.351554E+12 | 286936.24 | 16-APR-18:49 | 0.501664E+12 | 516141.95 | 04-APR-17:49 |
May | 0.383999E+12 | 298191.59 | 31-MAY-18:10 | 0.427448E+12 | 405765.70 | 01-MAY-20:49 |
June | 0.446430E+12 | 335505.87 | 26-JUN-18:10 | 0.381370E+12 | 351462.76 | 01-JUN-17:40 |
July | 0.500184E+12 | 356821.93 | 26-JUL-18:10 | 0.379365E+12 | 339708.75 | 03-JUL-17:19 |
August | 0.482068E+12 | 341722.00 | 03-AUG-18:10 | 0.375150E+12 | 334223.05 | 01-AUG-17:49 |
September | 0.396088E+12 | 304394.59 | 07-SEP-18:40 | 0.392640E+12 | 395490.93 | 29-SEP-21:00 |
October | 0.352201E+12 | 219265.27 | 20-OCT-17:19 | 0.506477E+12 | 471593.90 | 31-OCT-17:00 |
November | 0.343378E+12 | 213762.04 | 28-NOV-07:19 | 0.581034E+12 | 816710.48 | 25-NOV-21:49 |
December | 0.363261E+12 | 215303.45 | 19-DEC-07:40 | 0.651709E+12 | 592789.85 | 11-DEC-17:19 |
Annual Sum or Average | 0.465420E+13 | 0.637484E+13 | ||||
Minimum of Months | 0.321417E+12 | 211585.97 | 0.375150E+12 | 334223.05 | ||
Maximum of Months | 0.500184E+12 | 356821.93 | 0.851692E+12 | 959733.38 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.469686E+11 | 0.204621E+11 | 0.140003E+12 | 0.690929E+11 | 0.492354E+11 | 0.431931E+10 | 0.00 | 0.528106E+09 | 0.00 | 0.00 | 0.202241E+11 | 0.804728E+10 | 0.00 |
February | 0.422279E+11 | 0.170493E+11 | 0.126445E+12 | 0.624065E+11 | 0.426525E+11 | 0.442683E+10 | 0.00 | 0.797684E+09 | 0.00 | 0.00 | 0.147972E+11 | 0.727187E+10 | 0.00 |
March | 0.463949E+11 | 0.168938E+11 | 0.140056E+12 | 0.690951E+11 | 0.455400E+11 | 0.579090E+10 | 0.00 | 0.321007E+10 | 0.00 | 0.00 | 0.122913E+11 | 0.804567E+10 | 0.00 |
April | 0.445123E+11 | 0.143175E+11 | 0.135446E+12 | 0.668634E+11 | 0.445888E+11 | 0.639603E+10 | 0.00 | 0.206062E+11 | 0.00 | 0.00 | 0.742318E+10 | 0.779701E+10 | 0.00 |
May | 0.455888E+11 | 0.130220E+11 | 0.140035E+12 | 0.690933E+11 | 0.475253E+11 | 0.818437E+10 | 0.00 | 0.457820E+11 | 0.00 | 0.00 | 0.296445E+10 | 0.804708E+10 | 0.00 |
June | 0.439856E+11 | 0.117117E+11 | 0.135537E+12 | 0.668654E+11 | 0.490223E+11 | 0.813849E+10 | 0.00 | 0.113450E+12 | 0.00 | 0.00 | 0.627567E+10 | 0.778858E+10 | 0.00 |
July | 0.454506E+11 | 0.124816E+11 | 0.139944E+12 | 0.690909E+11 | 0.515529E+11 | 0.867113E+10 | 0.00 | 0.154436E+12 | 0.00 | 0.00 | 0.673512E+10 | 0.805551E+10 | 0.00 |
August | 0.457839E+11 | 0.140140E+11 | 0.140067E+12 | 0.690948E+11 | 0.510282E+11 | 0.858249E+10 | 0.00 | 0.135169E+12 | 0.00 | 0.00 | 0.650190E+10 | 0.804707E+10 | 0.00 |
September | 0.447337E+11 | 0.154428E+11 | 0.135457E+12 | 0.668636E+11 | 0.476360E+11 | 0.768289E+10 | 0.00 | 0.622233E+11 | 0.00 | 0.00 | 0.461647E+10 | 0.779842E+10 | 0.00 |
October | 0.466316E+11 | 0.180561E+11 | 0.139992E+12 | 0.690927E+11 | 0.461706E+11 | 0.649890E+10 | 0.00 | 0.100182E+11 | 0.00 | 0.00 | 0.396946E+10 | 0.804567E+10 | 0.00 |
November | 0.454068E+11 | 0.192850E+11 | 0.135531E+12 | 0.668648E+11 | 0.450909E+11 | 0.535285E+10 | 0.00 | 0.281020E+10 | 0.00 | 0.00 | 0.116619E+11 | 0.778017E+10 | 0.00 |
December | 0.470543E+11 | 0.209581E+11 | 0.139944E+12 | 0.690919E+11 | 0.478222E+11 | 0.549442E+10 | 0.00 | 0.958854E+09 | 0.00 | 0.00 | 0.201712E+11 | 0.805552E+10 | 0.00 |
Annual Sum or Average | 0.544739E+12 | 0.193694E+12 | 0.164846E+13 | 0.813515E+12 | 0.567865E+12 | 0.795386E+11 | 0.00 | 0.549989E+12 | 0.00 | 0.00 | 0.117632E+12 | 0.947798E+11 | 0.00 |
Minimum of Months | 0.422279E+11 | 0.117117E+11 | 0.126445E+12 | 0.624065E+11 | 0.426525E+11 | 0.431931E+10 | 0.00 | 0.528106E+09 | 0.00 | 0.00 | 0.296445E+10 | 0.727187E+10 | 0.00 |
Maximum of Months | 0.470543E+11 | 0.209581E+11 | 0.140067E+12 | 0.690951E+11 | 0.515529E+11 | 0.867113E+10 | 0.00 | 0.154436E+12 | 0.00 | 0.00 | 0.202241E+11 | 0.805552E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.435674E+12 | 0.00 | 0.264099E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.367288E+12 | 0.00 | 0.240623E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.163764E+12 | 0.00 | 0.265388E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.102072E+12 | 0.00 | 0.252636E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.244353E+11 | 0.00 | 0.251034E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.406277E+10 | 0.00 | 0.230193E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 89114930.99 | 0.00 | 0.227456E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.317329E+09 | 0.00 | 0.222794E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.279056E+11 | 0.00 | 0.217763E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.121006E+12 | 0.00 | 0.233568E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.195782E+12 | 0.00 | 0.238160E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.241670E+12 | 0.00 | 0.258218E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.168407E+13 | 0.00 | 0.290193E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 89114930.99 | 0.00 | 0.217763E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.435674E+12 | 0.00 | 0.265388E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 45764.37 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 49590.83 | 02-JAN-07:19 | 30560.70 | 18-JAN-19:19 | 4462.44 | 30-JAN-16:40 | 0.00 | 01-JAN-00:10 |
February | 45764.37 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 49590.83 | 01-FEB-07:19 | 28771.30 | 04-FEB-19:10 | 4114.43 | 04-FEB-16:40 | 0.00 | 01-FEB-00:10 |
March | 45764.37 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 49590.83 | 13-MAR-06:19 | 26006.48 | 01-MAR-19:10 | 3815.88 | 14-MAR-08:09 | 0.00 | 01-MAR-00:10 |
April | 45764.37 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 49590.38 | 14-APR-06:19 | 28729.96 | 18-APR-21:00 | 3764.60 | 04-APR-15:39 | 0.00 | 01-APR-00:10 |
May | 45764.37 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 49589.25 | 10-MAY-06:19 | 30689.99 | 31-MAY-21:00 | 3638.63 | 03-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 45764.37 | 01-JUN-19:40 | 12338.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 49589.49 | 13-JUN-06:19 | 33856.37 | 26-JUN-21:19 | 3919.31 | 26-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 45764.37 | 03-JUL-19:00 | 12338.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 49589.22 | 20-JUL-06:30 | 32217.72 | 03-JUL-21:10 | 4124.88 | 26-JUL-18:19 | 0.00 | 01-JUL-00:10 |
August | 45764.37 | 01-AUG-19:40 | 12338.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 49589.43 | 31-AUG-06:19 | 32226.83 | 04-AUG-21:00 | 3986.22 | 03-AUG-18:19 | 0.00 | 01-AUG-00:10 |
September | 45764.37 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 49590.83 | 21-SEP-06:19 | 33531.22 | 07-SEP-21:00 | 3739.39 | 29-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 45764.37 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 49590.83 | 02-OCT-06:19 | 26619.38 | 20-OCT-20:19 | 3782.33 | 16-OCT-06:19 | 0.00 | 01-OCT-00:10 |
November | 45764.37 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 49590.83 | 01-NOV-06:19 | 28454.18 | 27-NOV-19:19 | 3866.63 | 25-NOV-10:20 | 0.00 | 01-NOV-00:10 |
December | 45764.37 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 49590.83 | 01-DEC-07:19 | 30439.31 | 11-DEC-19:19 | 3933.26 | 13-DEC-02:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45764.37 | 12338.45 | 88863.15 | 49589.22 | 26006.48 | 3638.63 | 0.00 | |||||||
Maximum of Months | 45764.37 | 12338.45 | 88863.15 | 49590.83 | 33856.37 | 4462.44 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3137.57 | 12-JAN-16:19 | 0.00 | 0.00 | 8265.52 | 01-JAN-00:10 | 4751.14 | 06-JAN-07:49 | 0.00 |
February | 6028.80 | 24-FEB-16:19 | 0.00 | 0.00 | 8265.52 | 01-FEB-00:10 | 4752.06 | 02-FEB-07:10 | 0.00 |
March | 26842.21 | 25-MAR-15:20 | 0.00 | 0.00 | 8265.52 | 01-MAR-00:10 | 4751.12 | 13-MAR-06:40 | 0.00 |
April | 109380.96 | 16-APR-15:30 | 0.00 | 0.00 | 8265.52 | 01-APR-00:10 | 4751.13 | 10-APR-06:40 | 0.00 |
May | 109773.02 | 31-MAY-18:10 | 0.00 | 0.00 | 8265.52 | 04-MAY-12:30 | 4751.13 | 01-MAY-06:40 | 0.00 |
June | 154910.67 | 11-JUN-15:20 | 0.00 | 0.00 | 8265.52 | 08-JUN-15:50 | 4751.12 | 12-JUN-06:30 | 0.00 |
July | 168612.37 | 26-JUL-18:10 | 0.00 | 0.00 | 8265.52 | 01-JUL-08:30 | 4751.13 | 10-JUL-06:40 | 0.00 |
August | 183070.16 | 04-AUG-15:39 | 0.00 | 0.00 | 8265.52 | 01-AUG-08:20 | 4751.13 | 07-AUG-06:40 | 0.00 |
September | 129058.16 | 06-SEP-15:30 | 0.00 | 0.00 | 8265.52 | 01-SEP-12:09 | 4751.13 | 25-SEP-06:40 | 0.00 |
October | 58330.08 | 20-OCT-15:20 | 0.00 | 0.00 | 8265.52 | 07-OCT-23:10 | 4751.13 | 10-OCT-06:40 | 0.00 |
November | 21005.67 | 05-NOV-15:20 | 0.00 | 0.00 | 8265.52 | 10-NOV-01:00 | 4751.13 | 16-NOV-19:49 | 0.00 |
December | 2470.47 | 01-DEC-16:19 | 0.00 | 0.00 | 8265.52 | 01-DEC-00:10 | 4751.13 | 26-DEC-07:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2470.47 | 0.00 | 0.00 | 8265.52 | 4751.12 | 0.00 | |||
Maximum of Months | 183070.16 | 0.00 | 0.00 | 8265.52 | 4752.06 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 218560.74 | 20-JAN-07:40 | 25474.78 | 88863.15 | 12338.45 | 49590.83 | 25606.64 | 1497.41 | 0.00 | 0.00 | 0.00 |
February | 214760.12 | 03-FEB-07:30 | 25474.78 | 88863.15 | 12338.45 | 49590.83 | 21656.31 | 1642.22 | 0.00 | 0.00 | 0.00 |
March | 211585.97 | 17-MAR-06:19 | 25474.78 | 88863.15 | 12338.45 | 49590.83 | 19515.28 | 605.56 | 0.00 | 0.00 | 0.00 |
April | 286936.24 | 16-APR-18:49 | 38103.40 | 74342.86 | 12338.45 | 28092.95 | 24974.90 | 3485.23 | 0.00 | 91688.52 | 0.00 |
May | 298191.59 | 31-MAY-18:10 | 36642.55 | 77265.07 | 0.00 | 28142.52 | 28030.02 | 3631.33 | 0.00 | 109773.02 | 0.00 |
June | 335505.87 | 26-JUN-18:10 | 36642.55 | 77265.07 | 0.00 | 28142.52 | 28920.12 | 3919.31 | 0.00 | 145910.67 | 0.00 |
July | 356821.93 | 26-JUL-18:10 | 36782.39 | 77265.07 | 0.00 | 28142.60 | 27203.29 | 4108.48 | 0.00 | 168612.37 | 0.00 |
August | 341722.00 | 03-AUG-18:10 | 36755.72 | 77265.07 | 0.00 | 28142.52 | 27314.39 | 3968.20 | 0.00 | 153568.82 | 0.00 |
September | 304394.59 | 07-SEP-18:40 | 40691.94 | 77265.07 | 12338.45 | 28151.67 | 26693.80 | 3549.43 | 0.00 | 100996.69 | 0.00 |
October | 219265.27 | 20-OCT-17:19 | 30547.21 | 72346.32 | 12338.45 | 49248.20 | 18728.31 | 3074.04 | 0.00 | 27353.09 | 0.00 |
November | 213762.04 | 28-NOV-07:19 | 25474.78 | 88863.15 | 12338.45 | 49590.83 | 21249.93 | 1048.86 | 0.00 | 0.00 | 0.00 |
December | 215303.45 | 19-DEC-07:40 | 25474.78 | 88863.15 | 12338.45 | 49590.83 | 19738.44 | 3508.59 | 0.00 | 590.59 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 211585.97 | 25474.78 | 72346.32 | 0.00 | 28092.95 | 18728.31 | 605.56 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 356821.93 | 40691.94 | 88863.15 | 12338.45 | 49590.83 | 28920.12 | 4108.48 | 0.00 | 168612.37 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 607432.68 | 31-JAN-03:00 | 0.00 | 269334.86 | 31-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 651679.50 | 02-FEB-05:00 | 0.00 | 269511.10 | 21-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 175815.79 | 17-MAR-15:20 | 0.00 | 269469.55 | 01-MAR-21:49 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 177220.34 | 27-APR-15:20 | 0.00 | 268023.24 | 03-APR-20:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 154581.53 | 03-MAY-02:00 | 0.00 | 264793.64 | 01-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 80647.86 | 03-JUN-03:00 | 0.00 | 250581.41 | 01-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 4499.38 | 14-JUL-18:10 | 0.00 | 238825.36 | 03-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 22336.15 | 07-AUG-03:00 | 0.00 | 231774.58 | 01-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 177425.56 | 30-SEP-03:09 | 0.00 | 235543.73 | 29-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 179384.01 | 27-OCT-01:49 | 0.00 | 246786.10 | 30-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 572010.43 | 26-NOV-06:00 | 0.00 | 259670.52 | 29-NOV-21:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 276075.27 | 11-DEC-09:09 | 0.00 | 265567.47 | 29-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 4499.38 | 0.00 | 231774.58 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 651679.50 | 0.00 | 269511.10 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44.50 | 20.07 | 44.50 | 20.07 | 0.00 | 20.07 | 0.00 | 20.07 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.50 | 20.07 | 44.50 | 20.07 | 0.00 | 20.07 | 0.00 | 20.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.50 | 20.07 | 44.50 | 20.07 | 0.00 | 20.07 | 0.00 | 20.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.17 | 19.75 | 41.17 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
February | 52.50 | 18.87 | 52.50 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.17 | 20.15 | 3.17 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.83 | 19.29 | 96.83 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.50 | 20.15 | 52.50 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.17 | 20.17 | 21.17 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
February | 65.33 | 19.39 | 65.33 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.50 | 19.58 | 86.50 | 19.58 | 0.00 | 19.58 | 0.00 | 19.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.33 | 20.17 | 65.33 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.00 | 20.24 | 10.00 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
February | 82.33 | 19.53 | 82.33 | 19.53 | 0.00 | 19.53 | 0.00 | 19.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.33 | 19.60 | 92.33 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.33 | 20.24 | 82.33 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 76.33 | 19.85 | 76.33 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
February | 110.67 | 18.73 | 110.67 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.00 | 20.23 | 6.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 193.00 | 19.22 | 193.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.67 | 20.23 | 110.67 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.50 | 19.48 | 15.50 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 |
February | 40.67 | 18.93 | 40.67 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.17 | 19.08 | 56.17 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.67 | 19.48 | 40.67 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 20.27 | 6.50 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
February | 42.50 | 19.68 | 42.50 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.00 | 19.76 | 49.00 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.50 | 20.27 | 42.50 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.17 | 20.41 | 7.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
February | 29.00 | 20.02 | 29.00 | 20.02 | 0.00 | 20.02 | 0.00 | 20.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.76 | 1.50 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.74 | 1.83 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.77 | 1.83 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.83 | 1.83 | 21.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.48 | 0.67 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
December | 3.50 | 20.38 | 3.50 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Annual Sum or Average | 40.33 | 20.13 | 40.33 | 20.13 | 7.83 | 20.27 | 7.83 | 20.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.00 | 20.48 | 29.00 | 20.48 | 1.83 | 21.83 | 1.83 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.17 | 20.23 | 21.17 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
February | 51.33 | 19.65 | 51.33 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.85 | 0.67 | 21.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.76 | 3.17 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.76 | 3.00 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.77 | 0.83 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.78 | 0.67 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 20.44 | 1.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
December | 4.17 | 20.33 | 4.17 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Annual Sum or Average | 78.00 | 19.86 | 78.00 | 19.86 | 8.33 | 19.96 | 8.33 | 20.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.33 | 20.44 | 51.33 | 20.44 | 3.17 | 21.85 | 3.17 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.00 | 19.94 | 68.00 | 19.94 | 0.00 | 19.94 | 0.00 | 19.94 |
February | 66.50 | 18.61 | 66.50 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
March | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.83 | 0.17 | 21.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.75 | 1.67 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 21.79 | 7.33 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 21.78 | 7.83 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.76 | 5.17 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.71 | 1.00 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8.83 | 20.34 | 8.83 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
December | 7.50 | 20.23 | 7.50 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
Annual Sum or Average | 151.17 | 19.39 | 151.17 | 19.39 | 23.17 | 19.56 | 23.17 | 19.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.00 | 20.52 | 68.00 | 20.52 | 7.83 | 21.83 | 7.83 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.50 | 20.35 | 11.50 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
February | 39.67 | 19.79 | 39.67 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.47 | 0.83 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
December | 4.00 | 20.37 | 4.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Annual Sum or Average | 56.00 | 19.96 | 56.00 | 19.96 | 0.00 | 19.96 | 0.00 | 19.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.67 | 20.47 | 39.67 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.67 | 20.19 | 31.67 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 |
February | 54.00 | 19.33 | 54.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.14 | 0.33 | 22.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.12 | 1.50 | 22.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 22.37 | 5.17 | 22.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 22.38 | 7.17 | 22.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 22.19 | 4.00 | 22.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.29 | 1.50 | 22.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 20.41 | 1.33 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
December | 4.83 | 20.33 | 4.83 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Annual Sum or Average | 91.83 | 19.70 | 91.83 | 19.70 | 19.67 | 19.95 | 19.67 | 20.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.00 | 20.41 | 54.00 | 20.41 | 7.17 | 22.38 | 7.17 | 22.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.67 | 20.34 | 6.67 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
February | 63.00 | 19.91 | 63.00 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.67 | 19.95 | 69.67 | 19.95 | 0.00 | 19.95 | 0.00 | 19.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.00 | 20.34 | 63.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.00 | 20.26 | 21.00 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
February | 45.17 | 19.65 | 45.17 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.84 | 0.83 | 21.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.80 | 2.50 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.79 | 3.50 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.85 | 2.00 | 21.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.87 | 2.50 | 21.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 20.44 | 1.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
December | 4.83 | 20.33 | 4.83 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Annual Sum or Average | 72.00 | 19.89 | 72.00 | 19.89 | 12.00 | 20.04 | 12.00 | 20.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.17 | 20.44 | 45.17 | 20.44 | 3.50 | 21.87 | 3.50 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.50 | 20.10 | 51.50 | 20.10 | 0.00 | 20.10 | 0.00 | 20.10 |
February | 55.50 | 19.05 | 55.50 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.91 | 1.33 | 21.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.83 | 4.83 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.82 | 4.83 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.79 | 2.33 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.84 | 0.83 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.83 | 20.43 | 3.83 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
December | 5.83 | 20.27 | 5.83 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Annual Sum or Average | 116.67 | 19.62 | 116.67 | 19.62 | 14.83 | 19.75 | 14.83 | 19.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.50 | 20.43 | 55.50 | 20.43 | 4.83 | 21.91 | 4.83 | 21.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 20.42 | 4.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
February | 14.50 | 20.27 | 14.50 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.73 | 1.67 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.81 | 2.67 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.78 | 1.00 | 21.78 |
November | 0.50 | 20.48 | 0.50 | 20.48 | 0.50 | 20.92 | 0.50 | 21.15 |
December | 3.17 | 20.33 | 3.17 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Annual Sum or Average | 22.50 | 20.31 | 22.50 | 20.31 | 7.33 | 20.51 | 7.33 | 20.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.50 | 20.48 | 14.50 | 20.48 | 2.67 | 21.81 | 2.67 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.17 | 19.42 | 16.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
February | 40.33 | 18.21 | 40.33 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.50 | 18.55 | 56.50 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.33 | 19.42 | 40.33 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.17 | 19.70 | 10.17 | 19.70 | 0.00 | 19.70 | 0.00 | 19.70 |
February | 33.17 | 18.44 | 33.17 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.33 | 18.73 | 43.33 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.17 | 19.70 | 33.17 | 19.70 | 0.00 | 19.70 | 0.00 | 19.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.50 | 20.05 | 37.50 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 |
February | 76.50 | 18.98 | 76.50 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.00 | 20.29 | 3.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.00 | 19.35 | 117.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 76.50 | 20.29 | 76.50 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.58 | 12.17 | 22.55 | 12.17 | 22.53 |
February | 672.00 | 21.96 | 91.17 | 21.78 | 91.17 | 21.64 |
March | 744.00 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
April | 720.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
May | 744.00 | 21.73 | 6.67 | 21.73 | 6.67 | 21.74 |
June | 720.00 | 22.27 | 44.50 | 22.28 | 44.50 | 22.29 |
July | 744.00 | 22.77 | 87.83 | 22.79 | 87.83 | 22.80 |
August | 487.17 | 23.19 | 141.67 | 23.28 | 96.00 | 23.30 |
September | 387.50 | 23.56 | 94.17 | 23.62 | 17.33 | 23.63 |
October | 615.33 | 23.76 | 0.00 | 23.76 | 0.00 | 23.76 |
November | 614.17 | 23.68 | 4.00 | 23.68 | 0.00 | 23.68 |
December | 744.00 | 23.50 | 0.00 | 23.50 | 0.00 | 23.50 |
Annual Sum or Average | 7936.17 | 22.62 | 482.17 | 22.63 | 355.67 | 22.62 |
Minimum of Months | 387.50 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
Maximum of Months | 744.00 | 23.76 | 141.67 | 23.76 | 96.00 | 23.76 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 729.00 | 21.05 | 593.50 | 20.99 | 593.50 | 20.96 |
February | 643.33 | 21.01 | 410.00 | 20.92 | 403.00 | 20.86 |
March | 692.50 | 21.38 | 276.83 | 21.31 | 264.50 | 21.24 |
April | 581.50 | 21.62 | 171.17 | 21.80 | 91.83 | 21.72 |
May | 533.50 | 22.38 | 149.00 | 22.69 | 19.83 | 22.70 |
June | 319.67 | 22.62 | 444.67 | 23.35 | 88.83 | 23.38 |
July | 223.50 | 23.32 | 593.17 | 23.72 | 138.50 | 23.71 |
August | 219.00 | 23.25 | 571.33 | 23.69 | 113.17 | 23.67 |
September | 369.33 | 22.24 | 291.50 | 22.97 | 24.17 | 22.97 |
October | 627.17 | 21.78 | 69.17 | 21.95 | 10.67 | 21.94 |
November | 687.50 | 21.29 | 334.67 | 21.23 | 321.17 | 21.17 |
December | 716.00 | 21.15 | 574.17 | 21.09 | 571.83 | 21.06 |
Annual Sum or Average | 6342.00 | 21.66 | 4479.17 | 21.96 | 2641.00 | 21.83 |
Minimum of Months | 219.00 | 21.01 | 69.17 | 20.92 | 10.67 | 20.86 |
Maximum of Months | 729.00 | 23.32 | 593.50 | 23.72 | 593.50 | 23.71 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.06 | 253.17 | 21.02 | 253.17 | 21.00 |
February | 672.00 | 21.09 | 144.67 | 20.94 | 144.67 | 20.84 |
March | 744.00 | 21.53 | 4.00 | 21.53 | 4.00 | 21.53 |
April | 688.00 | 21.94 | 15.33 | 21.97 | 3.00 | 21.98 |
May | 702.50 | 22.49 | 31.83 | 22.53 | 21.83 | 22.55 |
June | 514.83 | 22.74 | 185.67 | 22.99 | 88.67 | 23.06 |
July | 452.67 | 23.04 | 297.83 | 23.30 | 148.33 | 23.35 |
August | 437.83 | 23.02 | 259.83 | 23.28 | 116.83 | 23.32 |
September | 532.83 | 22.62 | 104.33 | 22.81 | 20.33 | 22.83 |
October | 743.50 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
November | 720.00 | 21.56 | 45.00 | 21.52 | 45.00 | 21.49 |
December | 744.00 | 21.18 | 106.83 | 21.15 | 106.83 | 21.14 |
Annual Sum or Average | 7696.17 | 21.93 | 1448.50 | 22.03 | 952.67 | 22.02 |
Minimum of Months | 437.83 | 21.06 | 0.00 | 20.94 | 0.00 | 20.84 |
Maximum of Months | 744.00 | 23.04 | 297.83 | 23.30 | 253.17 | 23.35 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.13 | 403.83 | 21.07 | 403.83 | 21.04 |
February | 672.00 | 21.33 | 153.33 | 21.12 | 153.33 | 20.97 |
March | 744.00 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
April | 628.00 | 23.02 | 32.17 | 23.07 | 0.00 | 23.07 |
May | 334.17 | 23.86 | 107.33 | 23.90 | 2.67 | 23.90 |
June | 104.83 | 23.91 | 324.17 | 23.98 | 0.00 | 23.98 |
July | 0.00 | 0.00 | 585.67 | 24.00 | 0.00 | 24.00 |
August | 16.00 | 24.00 | 469.83 | 24.00 | 0.00 | 24.00 |
September | 317.33 | 23.88 | 131.50 | 23.91 | 0.00 | 23.91 |
October | 715.00 | 23.61 | 0.00 | 23.61 | 0.00 | 23.61 |
November | 681.67 | 22.43 | 76.83 | 22.28 | 76.83 | 22.17 |
December | 744.00 | 21.32 | 117.33 | 21.27 | 117.33 | 21.24 |
Annual Sum or Average | 5701.00 | 22.37 | 2402.00 | 22.55 | 754.00 | 22.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.07 | 0.00 | 20.97 |
Maximum of Months | 744.00 | 24.00 | 585.67 | 24.00 | 403.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.87 | 616.17 | 20.86 | 616.17 | 20.85 |
February | 672.00 | 20.62 | 388.17 | 20.51 | 388.17 | 20.47 |
March | 744.00 | 21.00 | 251.67 | 21.00 | 251.67 | 21.00 |
April | 720.00 | 21.16 | 49.50 | 21.15 | 49.50 | 21.14 |
May | 744.00 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
June | 720.00 | 22.03 | 0.00 | 22.03 | 0.00 | 22.03 |
July | 744.00 | 22.28 | 0.00 | 22.28 | 0.00 | 22.28 |
August | 744.00 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
September | 720.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
October | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
November | 720.00 | 21.03 | 216.50 | 21.01 | 216.50 | 21.01 |
December | 744.00 | 21.00 | 552.50 | 21.00 | 552.50 | 21.00 |
Annual Sum or Average | 8760.00 | 21.39 | 2074.50 | 21.28 | 2074.50 | 21.21 |
Minimum of Months | 672.00 | 20.62 | 0.00 | 20.51 | 0.00 | 20.47 |
Maximum of Months | 744.00 | 22.28 | 616.17 | 22.28 | 616.17 | 22.28 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 128.67 | 24.00 | 719.33 | 24.00 | 128.67 | 24.00 |
February | 127.00 | 24.00 | 637.00 | 24.00 | 127.00 | 24.00 |
March | 171.83 | 24.00 | 744.00 | 24.00 | 171.83 | 24.00 |
April | 239.83 | 24.00 | 720.00 | 24.00 | 239.83 | 24.00 |
May | 401.67 | 24.00 | 744.00 | 24.00 | 401.67 | 24.00 |
June | 519.17 | 24.00 | 720.00 | 24.00 | 519.17 | 24.00 |
July | 611.33 | 24.00 | 744.00 | 24.00 | 611.33 | 24.00 |
August | 601.83 | 24.00 | 744.00 | 24.00 | 601.83 | 24.00 |
September | 394.33 | 24.00 | 720.00 | 24.00 | 394.33 | 24.00 |
October | 216.00 | 24.00 | 744.00 | 24.00 | 216.00 | 24.00 |
November | 178.83 | 24.00 | 719.00 | 24.00 | 178.83 | 24.00 |
December | 132.67 | 24.00 | 743.33 | 24.00 | 132.67 | 24.00 |
Annual Sum or Average | 3723.17 | 24.00 | 8698.67 | 24.00 | 3723.17 | 24.00 |
Minimum of Months | 127.00 | 24.00 | 637.00 | 24.00 | 127.00 | 24.00 |
Maximum of Months | 611.33 | 24.00 | 744.00 | 24.00 | 611.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.17 | 21.08 | 369.50 | 21.03 | 369.50 | 21.00 |
February | 653.67 | 21.10 | 170.83 | 20.99 | 162.17 | 20.90 |
March | 715.33 | 21.45 | 50.00 | 21.44 | 42.33 | 21.42 |
April | 625.67 | 21.68 | 69.33 | 21.82 | 16.83 | 21.84 |
May | 659.33 | 21.97 | 87.00 | 22.08 | 44.50 | 22.13 |
June | 502.67 | 22.25 | 250.00 | 22.53 | 134.83 | 22.64 |
July | 478.67 | 22.53 | 387.33 | 22.79 | 223.00 | 22.87 |
August | 424.00 | 22.52 | 389.33 | 22.84 | 176.83 | 22.91 |
September | 473.83 | 22.13 | 237.50 | 22.57 | 54.67 | 22.63 |
October | 649.00 | 21.81 | 57.00 | 21.97 | 0.00 | 21.97 |
November | 693.67 | 21.38 | 111.83 | 21.38 | 95.50 | 21.34 |
December | 728.67 | 21.18 | 254.67 | 21.15 | 251.00 | 21.12 |
Annual Sum or Average | 7344.67 | 21.68 | 2434.33 | 21.84 | 1571.17 | 21.84 |
Minimum of Months | 424.00 | 21.08 | 50.00 | 20.99 | 0.00 | 20.90 |
Maximum of Months | 740.17 | 22.53 | 389.33 | 22.84 | 369.50 | 22.91 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.39 | 133.50 | 21.32 | 133.50 | 21.27 |
February | 672.00 | 21.56 | 99.67 | 21.41 | 99.67 | 21.29 |
March | 744.00 | 22.04 | 0.00 | 22.04 | 0.00 | 22.04 |
April | 648.17 | 22.30 | 42.33 | 22.38 | 15.67 | 22.41 |
May | 594.67 | 22.67 | 86.50 | 22.80 | 58.00 | 22.86 |
June | 464.83 | 22.96 | 284.33 | 23.26 | 156.17 | 23.35 |
July | 451.00 | 23.29 | 399.67 | 23.51 | 262.33 | 23.58 |
August | 366.67 | 23.28 | 403.00 | 23.53 | 200.50 | 23.59 |
September | 418.50 | 22.88 | 209.00 | 23.17 | 61.00 | 23.23 |
October | 714.67 | 22.63 | 0.17 | 22.63 | 0.00 | 22.63 |
November | 713.17 | 22.03 | 21.33 | 22.00 | 21.33 | 21.97 |
December | 744.00 | 21.61 | 40.17 | 21.58 | 40.17 | 21.55 |
Annual Sum or Average | 7275.67 | 22.26 | 1719.67 | 22.45 | 1048.33 | 22.50 |
Minimum of Months | 366.67 | 21.39 | 0.00 | 21.32 | 0.00 | 21.27 |
Maximum of Months | 744.00 | 23.29 | 403.00 | 23.53 | 262.33 | 23.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.52 | 709.50 | 20.50 | 709.50 | 20.50 |
February | 672.00 | 20.67 | 517.33 | 20.58 | 517.33 | 20.55 |
March | 742.17 | 21.03 | 370.83 | 20.92 | 370.83 | 20.86 |
April | 693.17 | 21.25 | 133.00 | 21.15 | 127.50 | 21.06 |
May | 698.50 | 21.58 | 2.33 | 21.59 | 0.00 | 21.59 |
June | 617.67 | 21.47 | 21.67 | 21.53 | 3.33 | 21.54 |
July | 609.33 | 21.45 | 29.67 | 21.53 | 2.83 | 21.54 |
August | 617.33 | 21.46 | 25.83 | 21.53 | 7.67 | 21.54 |
September | 644.83 | 21.45 | 19.50 | 21.48 | 7.83 | 21.47 |
October | 737.50 | 21.37 | 42.50 | 21.33 | 42.50 | 21.30 |
November | 716.67 | 20.86 | 410.00 | 20.76 | 410.00 | 20.71 |
December | 744.00 | 20.63 | 679.67 | 20.60 | 679.67 | 20.58 |
Annual Sum or Average | 8237.17 | 21.13 | 2961.83 | 21.00 | 2879.00 | 20.91 |
Minimum of Months | 609.33 | 20.52 | 2.33 | 20.50 | 0.00 | 20.50 |
Maximum of Months | 744.00 | 21.58 | 709.50 | 21.59 | 709.50 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.39 | 741.67 | 20.39 | 741.67 | 20.39 |
February | 672.00 | 20.42 | 615.00 | 20.39 | 615.00 | 20.38 |
March | 744.00 | 20.81 | 449.50 | 20.70 | 449.50 | 20.66 |
April | 688.83 | 21.21 | 165.83 | 21.14 | 154.50 | 21.05 |
May | 660.33 | 21.77 | 63.00 | 22.05 | 19.67 | 22.11 |
June | 568.83 | 21.95 | 125.83 | 22.48 | 59.33 | 22.69 |
July | 550.50 | 22.18 | 164.67 | 22.78 | 88.17 | 23.01 |
August | 566.67 | 22.05 | 155.33 | 22.56 | 86.67 | 22.73 |
September | 626.50 | 21.64 | 37.83 | 21.78 | 16.00 | 21.79 |
October | 738.33 | 21.15 | 123.00 | 21.08 | 123.00 | 21.02 |
November | 720.00 | 20.69 | 470.67 | 20.61 | 470.67 | 20.57 |
December | 744.00 | 20.45 | 739.17 | 20.45 | 739.17 | 20.45 |
Annual Sum or Average | 8024.00 | 21.17 | 3851.50 | 21.13 | 3563.33 | 21.04 |
Minimum of Months | 550.50 | 20.39 | 37.83 | 20.39 | 16.00 | 20.38 |
Maximum of Months | 744.00 | 22.18 | 741.67 | 22.78 | 741.67 | 23.01 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.48 | 646.67 | 20.44 | 646.67 | 20.42 |
February | 672.00 | 20.50 | 442.83 | 20.37 | 442.83 | 20.32 |
March | 744.00 | 21.01 | 299.17 | 20.94 | 299.17 | 20.89 |
April | 720.00 | 21.32 | 41.83 | 21.28 | 41.83 | 21.25 |
May | 738.83 | 21.77 | 9.33 | 21.79 | 8.33 | 21.80 |
June | 705.83 | 22.03 | 40.83 | 22.11 | 37.33 | 22.18 |
July | 720.50 | 22.18 | 63.67 | 22.28 | 55.67 | 22.36 |
August | 740.83 | 22.14 | 70.33 | 22.23 | 70.33 | 22.30 |
September | 720.00 | 21.76 | 0.83 | 21.76 | 0.83 | 21.76 |
October | 744.00 | 21.25 | 1.83 | 21.24 | 1.83 | 21.24 |
November | 720.00 | 20.93 | 297.33 | 20.83 | 297.33 | 20.77 |
December | 744.00 | 20.65 | 641.17 | 20.62 | 641.17 | 20.60 |
Annual Sum or Average | 8714.00 | 21.34 | 2555.83 | 21.19 | 2543.33 | 21.09 |
Minimum of Months | 672.00 | 20.48 | 0.83 | 20.37 | 0.83 | 20.32 |
Maximum of Months | 744.00 | 22.18 | 646.67 | 22.28 | 646.67 | 22.36 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.50 | 703.67 | 20.48 | 703.67 | 20.48 |
February | 672.00 | 20.65 | 517.33 | 20.57 | 517.33 | 20.53 |
March | 744.00 | 21.12 | 335.00 | 21.00 | 335.00 | 20.94 |
April | 696.67 | 21.30 | 142.67 | 21.18 | 142.00 | 21.09 |
May | 695.83 | 21.64 | 0.83 | 21.64 | 0.00 | 21.64 |
June | 591.33 | 21.42 | 8.50 | 21.44 | 3.00 | 21.44 |
July | 582.33 | 21.38 | 13.50 | 21.42 | 2.33 | 21.43 |
August | 606.00 | 21.45 | 9.33 | 21.47 | 5.17 | 21.48 |
September | 636.50 | 21.48 | 5.83 | 21.48 | 3.17 | 21.48 |
October | 744.00 | 21.44 | 36.50 | 21.42 | 36.50 | 21.40 |
November | 720.00 | 20.86 | 414.83 | 20.75 | 414.83 | 20.70 |
December | 744.00 | 20.60 | 678.00 | 20.57 | 678.00 | 20.56 |
Annual Sum or Average | 8176.67 | 21.14 | 2866.00 | 20.99 | 2841.00 | 20.90 |
Minimum of Months | 582.33 | 20.50 | 0.83 | 20.48 | 0.00 | 20.48 |
Maximum of Months | 744.00 | 21.64 | 703.67 | 21.64 | 703.67 | 21.64 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.38 | 737.83 | 20.38 | 737.83 | 20.38 |
February | 672.00 | 20.39 | 615.83 | 20.36 | 615.83 | 20.35 |
March | 744.00 | 20.88 | 431.50 | 20.79 | 431.50 | 20.74 |
April | 703.00 | 21.28 | 172.67 | 21.17 | 169.00 | 21.08 |
May | 693.50 | 21.91 | 30.67 | 22.01 | 14.17 | 22.05 |
June | 528.67 | 21.84 | 103.83 | 22.32 | 46.50 | 22.51 |
July | 485.67 | 22.01 | 159.83 | 22.66 | 69.50 | 22.88 |
August | 552.17 | 22.01 | 113.50 | 22.38 | 74.17 | 22.53 |
September | 642.67 | 21.74 | 22.00 | 21.83 | 6.17 | 21.84 |
October | 744.00 | 21.19 | 85.00 | 21.16 | 85.00 | 21.13 |
November | 720.00 | 20.68 | 465.83 | 20.59 | 465.83 | 20.55 |
December | 744.00 | 20.44 | 734.83 | 20.44 | 734.83 | 20.43 |
Annual Sum or Average | 7973.67 | 21.17 | 3673.33 | 21.09 | 3450.33 | 21.00 |
Minimum of Months | 485.67 | 20.38 | 22.00 | 20.36 | 6.17 | 20.35 |
Maximum of Months | 744.00 | 22.01 | 737.83 | 22.66 | 737.83 | 22.88 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.98 | 500.67 | 20.98 | 500.67 | 20.98 |
February | 672.00 | 20.89 | 253.83 | 20.84 | 253.83 | 20.81 |
March | 744.00 | 21.07 | 96.00 | 21.06 | 96.00 | 21.05 |
April | 720.00 | 21.46 | 13.83 | 21.46 | 13.83 | 21.45 |
May | 744.00 | 22.15 | 28.00 | 22.17 | 28.00 | 22.18 |
June | 641.00 | 22.80 | 127.17 | 22.88 | 111.17 | 22.93 |
July | 583.50 | 23.20 | 198.17 | 23.25 | 184.67 | 23.28 |
August | 679.17 | 23.14 | 153.00 | 23.15 | 151.17 | 23.15 |
September | 677.50 | 22.54 | 29.83 | 22.57 | 29.83 | 22.60 |
October | 744.00 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
November | 720.00 | 21.07 | 168.17 | 21.06 | 168.17 | 21.05 |
December | 744.00 | 21.00 | 365.17 | 21.00 | 365.17 | 21.00 |
Annual Sum or Average | 8413.17 | 21.75 | 1933.83 | 21.72 | 1902.50 | 21.69 |
Minimum of Months | 583.50 | 20.89 | 0.00 | 20.84 | 0.00 | 20.81 |
Maximum of Months | 744.00 | 23.20 | 500.67 | 23.25 | 500.67 | 23.28 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.44 | 727.00 | 20.43 | 727.00 | 20.42 |
February | 672.00 | 20.54 | 584.83 | 20.47 | 584.83 | 20.45 |
March | 741.83 | 20.92 | 457.00 | 20.80 | 457.00 | 20.75 |
April | 684.67 | 21.15 | 215.67 | 21.04 | 206.00 | 20.95 |
May | 679.33 | 21.51 | 22.50 | 21.53 | 11.83 | 21.53 |
June | 599.83 | 21.40 | 51.00 | 21.53 | 10.83 | 21.55 |
July | 590.17 | 21.38 | 65.00 | 21.57 | 11.00 | 21.59 |
August | 600.67 | 21.39 | 54.00 | 21.53 | 18.67 | 21.55 |
September | 638.00 | 21.38 | 51.00 | 21.44 | 24.17 | 21.42 |
October | 735.33 | 21.27 | 144.17 | 21.19 | 144.17 | 21.14 |
November | 716.33 | 20.75 | 460.50 | 20.66 | 460.50 | 20.62 |
December | 744.00 | 20.54 | 711.17 | 20.52 | 711.17 | 20.52 |
Annual Sum or Average | 8146.17 | 21.03 | 3543.83 | 20.92 | 3367.17 | 20.84 |
Minimum of Months | 590.17 | 20.44 | 22.50 | 20.43 | 10.83 | 20.42 |
Maximum of Months | 744.00 | 21.51 | 727.00 | 21.57 | 727.00 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.33 | 743.50 | 20.33 | 743.50 | 20.33 |
February | 672.00 | 20.30 | 644.17 | 20.29 | 644.17 | 20.28 |
March | 744.00 | 20.71 | 521.50 | 20.62 | 521.50 | 20.58 |
April | 685.00 | 21.13 | 268.00 | 21.06 | 251.50 | 20.97 |
May | 648.00 | 21.78 | 85.83 | 22.13 | 38.50 | 22.24 |
June | 562.83 | 22.04 | 149.00 | 22.64 | 79.50 | 22.92 |
July | 545.00 | 22.26 | 198.00 | 22.92 | 114.33 | 23.20 |
August | 554.50 | 22.08 | 185.83 | 22.66 | 108.17 | 22.86 |
September | 615.33 | 21.56 | 79.67 | 21.72 | 50.33 | 21.72 |
October | 736.83 | 21.03 | 278.83 | 20.93 | 277.50 | 20.87 |
November | 720.00 | 20.60 | 531.50 | 20.54 | 531.50 | 20.51 |
December | 744.00 | 20.41 | 743.83 | 20.41 | 743.83 | 20.41 |
Annual Sum or Average | 7971.50 | 21.12 | 4429.67 | 21.10 | 4104.33 | 21.03 |
Minimum of Months | 545.00 | 20.30 | 79.67 | 20.29 | 38.50 | 20.28 |
Maximum of Months | 744.00 | 22.26 | 743.83 | 22.92 | 743.83 | 23.20 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.33 | 20.91 | 602.00 | 20.80 | 602.00 | 20.76 |
February | 660.50 | 21.03 | 402.67 | 20.90 | 402.67 | 20.84 |
March | 729.33 | 21.24 | 256.17 | 21.12 | 256.17 | 21.05 |
April | 678.67 | 21.26 | 129.50 | 21.17 | 124.17 | 21.10 |
May | 695.50 | 21.58 | 0.33 | 21.58 | 0.33 | 21.58 |
June | 634.17 | 21.51 | 10.00 | 21.53 | 10.00 | 21.54 |
July | 633.17 | 21.49 | 13.67 | 21.52 | 12.33 | 21.54 |
August | 634.17 | 21.49 | 26.83 | 21.53 | 19.50 | 21.55 |
September | 629.83 | 21.45 | 33.00 | 21.53 | 2.00 | 21.53 |
October | 687.00 | 21.41 | 18.17 | 21.41 | 13.83 | 21.41 |
November | 704.83 | 21.11 | 320.33 | 20.98 | 317.83 | 20.91 |
December | 737.17 | 20.92 | 568.33 | 20.80 | 568.33 | 20.75 |
Annual Sum or Average | 8167.67 | 21.27 | 2381.00 | 21.16 | 2329.17 | 21.08 |
Minimum of Months | 629.83 | 20.91 | 0.33 | 20.80 | 0.33 | 20.75 |
Maximum of Months | 743.33 | 21.58 | 602.00 | 21.58 | 602.00 | 21.58 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.44 | 156.83 | 21.32 | 156.83 | 21.23 |
February | 672.00 | 21.41 | 113.17 | 21.15 | 113.17 | 20.95 |
March | 734.17 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
April | 630.17 | 22.15 | 45.83 | 22.24 | 14.00 | 22.27 |
May | 468.50 | 22.42 | 195.83 | 22.74 | 53.17 | 22.81 |
June | 331.00 | 22.82 | 383.83 | 23.18 | 149.00 | 23.27 |
July | 365.67 | 23.14 | 478.33 | 23.31 | 242.17 | 23.40 |
August | 352.67 | 22.90 | 417.50 | 23.22 | 188.33 | 23.31 |
September | 472.67 | 22.41 | 172.00 | 22.72 | 57.00 | 22.79 |
October | 704.17 | 22.18 | 4.00 | 22.19 | 0.00 | 22.19 |
November | 689.00 | 21.86 | 30.83 | 21.86 | 22.00 | 21.83 |
December | 744.00 | 21.64 | 36.00 | 21.61 | 36.00 | 21.58 |
Annual Sum or Average | 6908.00 | 22.06 | 2034.17 | 22.27 | 1031.67 | 22.31 |
Minimum of Months | 331.00 | 21.41 | 0.00 | 21.15 | 0.00 | 20.95 |
Maximum of Months | 744.00 | 23.14 | 478.33 | 23.31 | 242.17 | 23.40 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.67 | 81.83 | 21.57 | 81.83 | 21.49 |
February | 668.33 | 21.70 | 92.67 | 21.45 | 92.67 | 21.25 |
March | 690.83 | 22.22 | 10.00 | 22.24 | 0.00 | 22.24 |
April | 548.50 | 22.41 | 92.67 | 22.57 | 14.17 | 22.60 |
May | 311.33 | 22.64 | 309.17 | 23.09 | 52.17 | 23.14 |
June | 242.00 | 23.22 | 521.50 | 23.41 | 147.33 | 23.48 |
July | 265.33 | 23.69 | 619.83 | 23.52 | 241.67 | 23.59 |
August | 238.50 | 23.46 | 576.00 | 23.46 | 188.00 | 23.53 |
September | 328.50 | 22.62 | 275.67 | 23.05 | 57.83 | 23.12 |
October | 605.00 | 22.40 | 34.83 | 22.47 | 0.00 | 22.47 |
November | 646.33 | 22.10 | 46.50 | 22.16 | 11.00 | 22.15 |
December | 744.00 | 21.90 | 13.00 | 21.89 | 13.00 | 21.87 |
Annual Sum or Average | 6032.67 | 22.28 | 2673.67 | 22.58 | 899.67 | 22.62 |
Minimum of Months | 238.50 | 21.67 | 10.00 | 21.45 | 0.00 | 21.25 |
Maximum of Months | 744.00 | 23.69 | 619.83 | 23.52 | 241.67 | 23.59 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 412.50 | 23.85 | 674.17 | 23.94 | 384.00 | 23.95 |
February | 410.67 | 23.82 | 631.83 | 23.92 | 385.33 | 23.94 |
March | 484.83 | 23.99 | 743.00 | 23.99 | 484.83 | 23.99 |
April | 500.50 | 23.99 | 720.00 | 23.99 | 500.50 | 23.99 |
May | 554.00 | 23.99 | 744.00 | 23.99 | 554.00 | 23.99 |
June | 576.00 | 23.99 | 720.00 | 23.99 | 576.00 | 23.99 |
July | 603.33 | 23.99 | 744.00 | 23.99 | 603.33 | 23.99 |
August | 597.00 | 23.99 | 744.00 | 23.99 | 597.00 | 23.99 |
September | 532.50 | 23.99 | 720.00 | 23.99 | 532.50 | 23.99 |
October | 508.33 | 23.99 | 744.00 | 23.99 | 508.33 | 23.99 |
November | 461.33 | 23.97 | 709.67 | 23.98 | 456.33 | 23.98 |
December | 415.00 | 23.99 | 721.50 | 23.99 | 415.00 | 23.99 |
Annual Sum or Average | 6056.00 | 23.97 | 8616.17 | 23.98 | 5997.17 | 23.98 |
Minimum of Months | 410.67 | 23.82 | 631.83 | 23.92 | 384.00 | 23.94 |
Maximum of Months | 603.33 | 23.99 | 744.00 | 23.99 | 603.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.94 | 584.67 | 20.93 | 584.67 | 20.93 |
February | 672.00 | 20.80 | 319.67 | 20.70 | 319.67 | 20.65 |
March | 744.00 | 21.32 | 152.00 | 21.26 | 152.00 | 21.23 |
April | 637.33 | 21.91 | 60.50 | 22.06 | 12.00 | 22.07 |
May | 455.33 | 23.24 | 159.83 | 23.42 | 29.67 | 23.44 |
June | 227.00 | 23.42 | 462.50 | 23.81 | 79.83 | 23.83 |
July | 144.33 | 23.96 | 676.67 | 23.98 | 137.83 | 23.98 |
August | 149.17 | 23.91 | 621.50 | 23.97 | 130.67 | 23.97 |
September | 371.67 | 22.90 | 234.67 | 23.32 | 24.00 | 23.35 |
October | 744.00 | 22.00 | 0.00 | 22.00 | 0.00 | 22.00 |
November | 720.00 | 21.36 | 216.00 | 21.27 | 216.00 | 21.22 |
December | 744.00 | 21.01 | 505.17 | 21.01 | 505.17 | 21.00 |
Annual Sum or Average | 6352.83 | 21.75 | 3993.17 | 22.08 | 2191.50 | 21.97 |
Minimum of Months | 144.33 | 20.80 | 0.00 | 20.70 | 0.00 | 20.65 |
Maximum of Months | 744.00 | 23.96 | 676.67 | 23.98 | 584.67 | 23.98 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.57809 | 22.09633 | -0.1395 | 5.81643 |
February | 672.00000 | 21.95793 | 24.50663 | -0.2799 | 7.47761 |
March | 744.00000 | 21.87127 | 30.36017 | -0.2726 | 6.69760 |
April | 720.00000 | 21.48811 | 37.44065 | -0.3274 | 7.44440 |
May | 744.00000 | 21.73262 | 50.56416 | -1.3230 | 41.60606 |
June | 720.00000 | 22.26628 | 57.86458 | -1.0819 | 29.92838 |
July | 744.00000 | 22.76959 | 60.43827 | -0.8797 | 21.55798 |
August | 744.00000 | 23.35869 | 57.18801 | -0.6849 | 15.10362 |
September | 720.00000 | 23.68931 | 44.08897 | -0.6497 | 14.11377 |
October | 744.00000 | 23.79435 | 31.41943 | 0.23099 | 6.19574 |
November | 720.00000 | 23.71440 | 28.99205 | 0.19267 | 5.98560 |
December | 744.00000 | 23.50110 | 24.46549 | 0.10275 | 5.34907 |
Annual Sum or Average | 8760.00000 | 22.73244 | 39.20619 | -0.4268 | 13.98811 |
Minimum of Months | 672.00000 | 21.48811 | 22.09633 | -1.3230 | 5.34907 |
Maximum of Months | 744.00000 | 23.79435 | 60.43827 | 0.23099 | 41.60606 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.11008 | 23.20774 | -0.6189 | 14.31429 |
February | 672.00000 | 21.13555 | 25.15574 | -0.5415 | 13.47136 |
March | 744.00000 | 21.56035 | 30.65584 | -0.3618 | 9.60712 |
April | 720.00000 | 22.06357 | 35.97117 | -0.1564 | 8.67171 |
May | 744.00000 | 22.78689 | 47.80769 | -0.8649 | 23.32806 |
June | 720.00000 | 23.32855 | 54.60454 | -0.5889 | 15.19244 |
July | 744.00000 | 23.70261 | 57.55253 | -0.4152 | 9.55104 |
August | 744.00000 | 23.68577 | 56.21785 | -0.4283 | 9.86375 |
September | 720.00000 | 23.04663 | 45.09855 | -0.7472 | 21.41205 |
October | 744.00000 | 22.11868 | 34.22124 | -0.1314 | 7.50116 |
November | 720.00000 | 21.41387 | 32.35393 | -0.4065 | 10.22280 |
December | 744.00000 | 21.25828 | 26.80993 | -0.5490 | 12.69506 |
Annual Sum or Average | 8760.00000 | 22.27473 | 39.22154 | -0.4838 | 12.97217 |
Minimum of Months | 672.00000 | 21.11008 | 23.20774 | -0.8649 | 7.50116 |
Maximum of Months | 744.00000 | 23.70261 | 57.55253 | -0.1314 | 23.32806 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.05927 | 23.80245 | -0.5088 | 10.65157 |
February | 672.00000 | 21.09175 | 25.68275 | -0.4709 | 10.56524 |
March | 744.00000 | 21.53323 | 30.98092 | -0.3163 | 7.58932 |
April | 720.00000 | 22.00689 | 36.48560 | -0.1505 | 6.57342 |
May | 744.00000 | 22.54902 | 48.70659 | -0.9597 | 25.23910 |
June | 720.00000 | 22.97862 | 56.02821 | -0.7474 | 17.89971 |
July | 744.00000 | 23.23733 | 59.34818 | -0.6265 | 13.77442 |
August | 744.00000 | 23.24361 | 57.95746 | -0.6350 | 13.93247 |
September | 720.00000 | 22.87414 | 46.07464 | -0.8520 | 21.91696 |
October | 744.00000 | 22.15891 | 34.44937 | -0.1221 | 5.71544 |
November | 720.00000 | 21.55632 | 32.35655 | -0.3048 | 7.72792 |
December | 744.00000 | 21.17691 | 27.33100 | -0.4495 | 9.39855 |
Annual Sum or Average | 8760.00000 | 22.12809 | 40.02006 | -0.5123 | 12.58820 |
Minimum of Months | 672.00000 | 21.05927 | 23.80245 | -0.9597 | 5.71544 |
Maximum of Months | 744.00000 | 23.24361 | 59.34818 | -0.1221 | 25.23910 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99971 | 16.90196 | 0.70444 | 16.29307 |
February | 672.00000 | 23.99972 | 18.68254 | 0.73734 | 17.36473 |
March | 744.00000 | 23.99975 | 23.48281 | 0.80926 | 19.63200 |
April | 720.00000 | 23.99976 | 29.05980 | 0.87654 | 22.10678 |
May | 744.00000 | 23.99975 | 41.00189 | 0.36115 | 9.52082 |
June | 720.00000 | 23.99982 | 48.85071 | 0.44736 | 10.89425 |
July | 744.00000 | 23.99991 | 52.63502 | 0.48524 | 11.46360 |
August | 744.00000 | 23.99992 | 51.35582 | 0.47458 | 11.34630 |
September | 720.00000 | 23.99988 | 39.48197 | 0.36054 | 9.51845 |
October | 744.00000 | 23.99981 | 27.29713 | 0.86980 | 21.72437 |
November | 720.00000 | 23.99989 | 24.78726 | 0.81255 | 19.81711 |
December | 744.00000 | 23.99982 | 19.90693 | 0.74129 | 17.34226 |
Annual Sum or Average | 8760.00000 | 23.99981 | 32.87269 | 0.63938 | 15.57070 |
Minimum of Months | 672.00000 | 23.99971 | 16.90196 | 0.36054 | 9.51845 |
Maximum of Months | 744.00000 | 23.99992 | 52.63502 | 0.87654 | 22.10678 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.08841 | 25.96980 | -0.5166 | 11.40190 |
February | 672.00000 | 21.16500 | 27.82535 | -0.4278 | 10.58389 |
March | 744.00000 | 21.51496 | 33.28283 | -0.2699 | 7.64038 |
April | 720.00000 | 21.87172 | 38.99466 | -0.1043 | 7.20783 |
May | 744.00000 | 22.07426 | 52.29458 | -0.9639 | 25.89715 |
June | 720.00000 | 22.42299 | 60.01787 | -0.7525 | 18.63336 |
July | 744.00000 | 22.63118 | 63.61842 | -0.6322 | 14.46943 |
August | 744.00000 | 22.72971 | 61.93559 | -0.6065 | 13.97652 |
September | 720.00000 | 22.54109 | 49.21164 | -0.7823 | 21.53607 |
October | 744.00000 | 22.02936 | 37.00096 | -0.0553 | 6.48852 |
November | 720.00000 | 21.45758 | 34.83005 | -0.2957 | 8.30069 |
December | 744.00000 | 21.22620 | 29.51568 | -0.4506 | 10.20378 |
Annual Sum or Average | 8760.00000 | 21.90011 | 42.96682 | -0.4887 | 13.03862 |
Minimum of Months | 672.00000 | 21.08841 | 25.96980 | -0.9639 | 6.48852 |
Maximum of Months | 744.00000 | 22.72971 | 63.61842 | -0.0553 | 25.89715 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.38572 | 26.07173 | -0.4000 | 8.80544 |
February | 672.00000 | 21.56149 | 27.80583 | -0.3300 | 8.39818 |
March | 744.00000 | 22.03619 | 32.98007 | -0.1669 | 6.26022 |
April | 720.00000 | 22.42370 | 38.53471 | -0.0184 | 6.11674 |
May | 744.00000 | 22.83618 | 50.80223 | -0.8173 | 19.98336 |
June | 720.00000 | 23.12716 | 58.34157 | -0.6450 | 14.78973 |
July | 744.00000 | 23.29853 | 61.86113 | -0.5507 | 11.96901 |
August | 744.00000 | 23.34932 | 60.34228 | -0.5429 | 11.70833 |
September | 720.00000 | 23.15103 | 48.24349 | -0.7058 | 16.90810 |
October | 744.00000 | 22.66892 | 36.41960 | 0.03564 | 5.47863 |
November | 720.00000 | 22.04369 | 34.31105 | -0.1581 | 6.61920 |
December | 744.00000 | 21.61263 | 29.46567 | -0.3192 | 7.60986 |
Annual Sum or Average | 8760.00000 | 22.46274 | 42.18551 | -0.3854 | 10.39568 |
Minimum of Months | 672.00000 | 21.38572 | 26.07173 | -0.8173 | 5.47863 |
Maximum of Months | 744.00000 | 23.34932 | 61.86113 | 0.03564 | 19.98336 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.52230 | 31.90505 | -0.7787 | 18.44946 |
February | 672.00000 | 20.67389 | 35.43831 | -0.6732 | 15.78359 |
March | 744.00000 | 21.04059 | 40.99667 | -0.4973 | 11.26858 |
April | 720.00000 | 21.32506 | 45.19879 | -0.3233 | 8.75006 |
May | 744.00000 | 21.68617 | 52.16406 | -1.2462 | 38.92220 |
June | 720.00000 | 21.73232 | 53.41334 | -1.1415 | 34.17470 |
July | 744.00000 | 21.78401 | 53.62129 | -1.0794 | 31.37156 |
August | 744.00000 | 21.77438 | 53.99741 | -1.1031 | 32.41680 |
September | 720.00000 | 21.64330 | 49.71499 | -1.2550 | 39.72462 |
October | 744.00000 | 21.38433 | 45.93363 | -0.3272 | 8.09466 |
November | 720.00000 | 20.87414 | 43.00333 | -0.5537 | 12.58762 |
December | 744.00000 | 20.63059 | 35.78775 | -0.7171 | 16.57978 |
Annual Sum or Average | 8760.00000 | 21.25920 | 45.14731 | -0.8090 | 22.38149 |
Minimum of Months | 672.00000 | 20.52230 | 31.90505 | -1.2550 | 8.09466 |
Maximum of Months | 744.00000 | 21.78401 | 53.99741 | -0.3233 | 39.72462 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.39308 | 32.19531 | -0.8379 | 20.49116 |
February | 672.00000 | 20.42162 | 35.90938 | -0.7622 | 18.41530 |
March | 744.00000 | 20.81119 | 41.56754 | -0.5721 | 12.74670 |
April | 720.00000 | 21.33268 | 45.61358 | -0.3429 | 9.34318 |
May | 744.00000 | 22.06742 | 52.14877 | -1.1510 | 36.05431 |
June | 720.00000 | 22.36511 | 53.27237 | -0.9627 | 29.40566 |
July | 744.00000 | 22.61241 | 53.95385 | -0.8435 | 24.59266 |
August | 744.00000 | 22.49424 | 54.55504 | -0.9071 | 26.19993 |
September | 720.00000 | 21.93872 | 50.23674 | -1.2032 | 38.24731 |
October | 744.00000 | 21.17288 | 46.69748 | -0.4058 | 9.11827 |
November | 720.00000 | 20.69329 | 43.53837 | -0.6170 | 13.99709 |
December | 744.00000 | 20.44891 | 36.19121 | -0.7826 | 18.48666 |
Annual Sum or Average | 8760.00000 | 21.40193 | 45.53940 | -0.7825 | 21.43509 |
Minimum of Months | 672.00000 | 20.39308 | 32.19531 | -1.2032 | 9.11827 |
Maximum of Months | 744.00000 | 22.61241 | 54.55504 | -0.3429 | 38.24731 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.48070 | 28.76221 | -0.7346 | 17.16986 |
February | 672.00000 | 20.49681 | 32.38139 | -0.6936 | 16.63440 |
March | 744.00000 | 21.01007 | 38.38463 | -0.5013 | 10.58763 |
April | 720.00000 | 21.32004 | 43.21951 | -0.3639 | 8.38060 |
May | 744.00000 | 21.78357 | 50.18589 | -1.2988 | 41.06572 |
June | 720.00000 | 22.06802 | 54.08622 | -1.1416 | 33.95876 |
July | 744.00000 | 22.23762 | 56.76136 | -1.0608 | 30.27962 |
August | 744.00000 | 22.15137 | 56.33123 | -1.1055 | 32.08049 |
September | 720.00000 | 21.75651 | 49.14933 | -1.3206 | 42.13114 |
October | 744.00000 | 21.24534 | 43.43257 | -0.3866 | 8.27498 |
November | 720.00000 | 20.93185 | 39.83744 | -0.5191 | 11.28550 |
December | 744.00000 | 20.65100 | 33.04753 | -0.6609 | 14.63401 |
Annual Sum or Average | 8760.00000 | 21.34946 | 43.86170 | -0.8164 | 22.23371 |
Minimum of Months | 672.00000 | 20.48070 | 28.76221 | -1.3206 | 8.27498 |
Maximum of Months | 744.00000 | 22.23762 | 56.76136 | -0.3639 | 42.13114 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.50334 | 31.88263 | -0.7804 | 18.51065 |
February | 672.00000 | 20.65417 | 35.38767 | -0.6798 | 16.04228 |
March | 744.00000 | 21.11908 | 40.76558 | -0.4778 | 10.88476 |
April | 720.00000 | 21.36327 | 45.05096 | -0.3253 | 8.82256 |
May | 744.00000 | 21.74856 | 51.16413 | -1.2196 | 37.69568 |
June | 720.00000 | 21.75765 | 52.76024 | -1.1310 | 33.74999 |
July | 744.00000 | 21.80078 | 53.14337 | -1.0801 | 31.44692 |
August | 744.00000 | 21.79690 | 53.58140 | -1.1037 | 32.45520 |
September | 720.00000 | 21.69236 | 49.21109 | -1.2375 | 38.87912 |
October | 744.00000 | 21.44416 | 45.77627 | -0.3167 | 7.96531 |
November | 720.00000 | 20.86185 | 43.03334 | -0.5572 | 12.66426 |
December | 744.00000 | 20.59941 | 35.82089 | -0.7235 | 16.71352 |
Annual Sum or Average | 8760.00000 | 21.28206 | 44.84571 | -0.8036 | 22.18766 |
Minimum of Months | 672.00000 | 20.50334 | 31.88263 | -1.2375 | 7.96531 |
Maximum of Months | 744.00000 | 21.80078 | 53.58140 | -0.3167 | 38.87912 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.38067 | 32.13984 | -0.8395 | 20.59203 |
February | 672.00000 | 20.38685 | 35.88453 | -0.7724 | 18.81539 |
March | 744.00000 | 20.88025 | 41.32060 | -0.5548 | 12.23061 |
April | 720.00000 | 21.33684 | 45.51690 | -0.3528 | 9.26669 |
May | 744.00000 | 22.04115 | 51.30973 | -1.1504 | 35.07056 |
June | 720.00000 | 22.34806 | 52.86561 | -0.9635 | 28.90766 |
July | 744.00000 | 22.61292 | 53.66468 | -0.8477 | 24.65195 |
August | 744.00000 | 22.44515 | 54.35798 | -0.9285 | 26.29558 |
September | 720.00000 | 21.96355 | 49.61606 | -1.1939 | 37.39433 |
October | 744.00000 | 21.19073 | 46.60038 | -0.4050 | 8.80415 |
November | 720.00000 | 20.67697 | 43.57283 | -0.6222 | 14.11801 |
December | 744.00000 | 20.44015 | 36.19722 | -0.7858 | 18.62662 |
Annual Sum or Average | 8760.00000 | 21.39813 | 45.30195 | -0.7848 | 21.23794 |
Minimum of Months | 672.00000 | 20.38067 | 32.13984 | -1.1939 | 8.80415 |
Maximum of Months | 744.00000 | 22.61292 | 54.35798 | -0.3528 | 37.39433 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.43554 | 32.62092 | -0.8526 | 21.05222 |
February | 672.00000 | 20.53501 | 36.30551 | -0.7500 | 18.36476 |
March | 744.00000 | 20.92265 | 42.11818 | -0.5544 | 12.71357 |
April | 720.00000 | 21.25456 | 46.27064 | -0.3540 | 9.54935 |
May | 744.00000 | 21.66579 | 53.34899 | -1.2558 | 39.61422 |
June | 720.00000 | 21.71618 | 54.52750 | -1.1412 | 34.44277 |
July | 744.00000 | 21.77605 | 54.75295 | -1.0732 | 31.34371 |
August | 744.00000 | 21.76154 | 55.48175 | -1.1022 | 32.59359 |
September | 720.00000 | 21.59786 | 51.03677 | -1.2826 | 41.32993 |
October | 744.00000 | 21.29584 | 47.19227 | -0.3662 | 8.82270 |
November | 720.00000 | 20.76786 | 44.28268 | -0.6123 | 14.19190 |
December | 744.00000 | 20.54360 | 36.63641 | -0.7848 | 18.71649 |
Annual Sum or Average | 8760.00000 | 21.19316 | 46.26514 | -0.8448 | 23.58954 |
Minimum of Months | 672.00000 | 20.43554 | 32.62092 | -1.2826 | 8.82270 |
Maximum of Months | 744.00000 | 21.77605 | 55.48175 | -0.3540 | 41.32993 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.33255 | 32.87065 | -0.9073 | 23.14587 |
February | 672.00000 | 20.30455 | 36.76010 | -0.8366 | 21.19290 |
March | 744.00000 | 20.71143 | 42.69975 | -0.6280 | 14.26368 |
April | 720.00000 | 21.27159 | 46.66041 | -0.3726 | 10.28813 |
May | 744.00000 | 22.10235 | 52.96310 | -1.1415 | 36.57733 |
June | 720.00000 | 22.41171 | 53.79708 | -0.9395 | 29.95505 |
July | 744.00000 | 22.65117 | 54.37707 | -0.8182 | 24.86973 |
August | 744.00000 | 22.53036 | 55.32632 | -0.8878 | 26.44180 |
September | 720.00000 | 21.90236 | 51.38403 | -1.2271 | 39.98173 |
October | 744.00000 | 21.06070 | 48.07289 | -0.4521 | 10.12672 |
November | 720.00000 | 20.60409 | 44.80812 | -0.6738 | 15.67888 |
December | 744.00000 | 20.41154 | 37.01180 | -0.8415 | 20.54137 |
Annual Sum or Average | 8760.00000 | 21.36445 | 46.44313 | -0.8104 | 22.75473 |
Minimum of Months | 672.00000 | 20.30455 | 32.87065 | -1.2271 | 10.12672 |
Maximum of Months | 744.00000 | 22.65117 | 55.32632 | -0.3726 | 39.98173 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.91154 | 32.74298 | -0.6465 | 15.24688 |
February | 672.00000 | 21.07273 | 35.99254 | -0.5401 | 12.77937 |
March | 744.00000 | 21.28482 | 41.12970 | -0.4184 | 10.21384 |
April | 720.00000 | 21.38062 | 45.27283 | -0.3186 | 8.79400 |
May | 744.00000 | 21.69319 | 52.11419 | -1.2730 | 40.30062 |
June | 720.00000 | 21.72719 | 54.53264 | -1.1923 | 36.49636 |
July | 744.00000 | 21.76354 | 55.61201 | -1.1403 | 34.09318 |
August | 744.00000 | 21.75845 | 55.30421 | -1.1454 | 34.40406 |
September | 720.00000 | 21.68139 | 49.77656 | -1.2490 | 39.67138 |
October | 744.00000 | 21.55851 | 45.50859 | -0.2558 | 7.65242 |
November | 720.00000 | 21.15385 | 42.88077 | -0.4592 | 11.04919 |
December | 744.00000 | 20.94551 | 36.44540 | -0.6034 | 14.44358 |
Annual Sum or Average | 8760.00000 | 21.41291 | 45.66094 | -0.7717 | 22.15107 |
Minimum of Months | 672.00000 | 20.91154 | 32.74298 | -1.2730 | 7.65242 |
Maximum of Months | 744.00000 | 21.76354 | 55.61201 | -0.2558 | 40.30062 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.43744 | 25.65796 | -0.3824 | 8.94337 |
February | 672.00000 | 21.40857 | 27.51435 | -0.3513 | 9.83548 |
March | 744.00000 | 21.96754 | 32.77214 | -0.1438 | 6.20282 |
April | 720.00000 | 22.29993 | 38.47698 | 0.01395 | 6.10273 |
May | 744.00000 | 22.73555 | 50.67912 | -0.7249 | 17.25629 |
June | 720.00000 | 22.96099 | 58.44835 | -0.5564 | 12.61903 |
July | 744.00000 | 23.02480 | 62.28076 | -0.4972 | 10.98750 |
August | 744.00000 | 22.96770 | 61.13198 | -0.5375 | 11.92038 |
September | 720.00000 | 22.69968 | 49.05577 | -0.7495 | 18.37836 |
October | 744.00000 | 22.24763 | 36.72483 | -0.0160 | 5.69334 |
November | 720.00000 | 21.92855 | 34.18194 | -0.1527 | 6.65427 |
December | 744.00000 | 21.64114 | 29.11721 | -0.2970 | 7.44346 |
Annual Sum or Average | 8760.00000 | 22.28162 | 42.25911 | -0.3664 | 10.16407 |
Minimum of Months | 672.00000 | 21.40857 | 25.65796 | -0.7495 | 5.69334 |
Maximum of Months | 744.00000 | 23.02480 | 62.28076 | 0.01395 | 18.37836 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.67087 | 25.42701 | -0.2901 | 7.81657 |
February | 672.00000 | 21.71253 | 27.21159 | -0.2443 | 8.60272 |
March | 744.00000 | 22.31934 | 32.29805 | -0.0281 | 5.87663 |
April | 720.00000 | 22.65639 | 37.87685 | 0.12570 | 6.32532 |
May | 744.00000 | 23.01886 | 49.95128 | -0.6007 | 13.62120 |
June | 720.00000 | 23.21174 | 57.65011 | -0.4447 | 10.08568 |
July | 744.00000 | 23.26394 | 61.45841 | -0.3907 | 8.86527 |
August | 744.00000 | 23.20916 | 60.32683 | -0.4305 | 9.61588 |
September | 720.00000 | 22.97781 | 48.39299 | -0.6280 | 14.64513 |
October | 744.00000 | 22.62504 | 36.12599 | 0.10069 | 5.86156 |
November | 720.00000 | 22.25001 | 33.69818 | -0.0439 | 6.34148 |
December | 744.00000 | 21.90359 | 28.82005 | -0.1984 | 6.59314 |
Annual Sum or Average | 8760.00000 | 22.57305 | 41.69070 | -0.2563 | 8.68099 |
Minimum of Months | 672.00000 | 21.67087 | 25.42701 | -0.6280 | 5.86156 |
Maximum of Months | 744.00000 | 23.26394 | 61.45841 | 0.12570 | 14.64513 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.91216 | 26.22542 | 0.82948 | 21.45835 |
February | 672.00000 | 23.88207 | 27.99378 | 0.87509 | 23.54573 |
March | 744.00000 | 23.99069 | 31.12713 | 0.98638 | 27.03237 |
April | 720.00000 | 23.99087 | 36.31532 | 1.07859 | 31.14032 |
May | 744.00000 | 23.99122 | 47.68261 | 0.66509 | 18.17379 |
June | 720.00000 | 23.99163 | 55.26386 | 0.77332 | 21.26216 |
July | 744.00000 | 23.99187 | 58.94940 | 0.81821 | 22.57839 |
August | 744.00000 | 23.99166 | 57.70394 | 0.78742 | 21.57486 |
September | 720.00000 | 23.99134 | 46.24267 | 0.65089 | 17.72962 |
October | 744.00000 | 23.99089 | 34.56478 | 1.05626 | 30.00471 |
November | 720.00000 | 23.97780 | 32.65186 | 0.97058 | 26.47047 |
December | 744.00000 | 23.99065 | 28.32476 | 0.88476 | 22.85960 |
Annual Sum or Average | 8760.00000 | 23.97501 | 40.32865 | 0.86455 | 23.64795 |
Minimum of Months | 672.00000 | 23.88207 | 26.22542 | 0.65089 | 17.72962 |
Maximum of Months | 744.00000 | 23.99187 | 58.94940 | 1.07859 | 31.14032 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.86755 | 20.79142 | -0.6405 | 13.93309 |
February | 672.00000 | 20.61651 | 22.99453 | -0.6590 | 15.46054 |
March | 744.00000 | 21.00392 | 28.69766 | -0.5073 | 10.48195 |
April | 720.00000 | 21.16403 | 35.00911 | -0.3996 | 8.85359 |
May | 744.00000 | 21.48224 | 48.32002 | -1.3593 | 43.58759 |
June | 720.00000 | 22.03057 | 55.86198 | -1.1146 | 31.73552 |
July | 744.00000 | 22.28298 | 59.48640 | -1.0008 | 26.32922 |
August | 744.00000 | 22.25019 | 58.08042 | -1.0223 | 27.21259 |
September | 720.00000 | 21.81703 | 45.55924 | -1.2548 | 38.63554 |
October | 744.00000 | 21.08980 | 33.19010 | -0.4121 | 8.66850 |
November | 720.00000 | 21.02566 | 30.20021 | -0.4885 | 10.27131 |
December | 744.00000 | 20.99866 | 24.35236 | -0.5754 | 11.99101 |
Annual Sum or Average | 8760.00000 | 21.39073 | 38.63899 | -0.7869 | 20.61944 |
Minimum of Months | 672.00000 | 20.61651 | 20.79142 | -1.3593 | 8.66850 |
Maximum of Months | 744.00000 | 22.28298 | 59.48640 | -0.3996 | 43.58759 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.98136 | 25.11638 | -0.5745 | 12.00457 |
February | 672.00000 | 20.89091 | 27.18091 | -0.5672 | 12.07130 |
March | 744.00000 | 21.06770 | 32.86712 | -0.4738 | 9.80186 |
April | 720.00000 | 21.45899 | 38.67317 | -0.3294 | 8.06557 |
May | 744.00000 | 22.15164 | 50.81361 | -1.1737 | 34.37710 |
June | 720.00000 | 22.89747 | 57.57004 | -0.8649 | 21.70167 |
July | 744.00000 | 23.29238 | 60.56341 | -0.7036 | 15.61144 |
August | 744.00000 | 23.17394 | 59.52323 | -0.7539 | 17.11657 |
September | 720.00000 | 22.59845 | 47.93766 | -1.0303 | 28.98993 |
October | 744.00000 | 21.24568 | 37.16858 | -0.3872 | 8.27609 |
November | 720.00000 | 21.06904 | 34.41511 | -0.4724 | 9.87934 |
December | 744.00000 | 21.00012 | 28.71795 | -0.5443 | 11.24095 |
Annual Sum or Average | 8760.00000 | 21.82455 | 41.79952 | -0.6568 | 15.77638 |
Minimum of Months | 672.00000 | 20.89091 | 25.11638 | -1.1737 | 8.06557 |
Maximum of Months | 744.00000 | 23.29238 | 60.56341 | -0.3294 | 34.37710 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.94235 | 24.53538 | -0.6186 | 13.26833 |
February | 672.00000 | 20.79501 | 26.59687 | -0.6123 | 13.95692 |
March | 744.00000 | 21.31825 | 32.26407 | -0.4211 | 9.19229 |
April | 720.00000 | 22.14008 | 37.04451 | -0.1655 | 7.48512 |
May | 744.00000 | 23.47989 | 47.20239 | -0.7191 | 16.97826 |
June | 720.00000 | 23.80220 | 53.73230 | -0.5305 | 11.55249 |
July | 744.00000 | 23.97148 | 56.92998 | -0.4388 | 9.08845 |
August | 744.00000 | 23.95800 | 55.92457 | -0.4607 | 9.53357 |
September | 720.00000 | 23.41453 | 45.43426 | -0.7406 | 18.66447 |
October | 744.00000 | 21.99663 | 35.72635 | -0.2087 | 6.42217 |
November | 720.00000 | 21.35966 | 33.56664 | -0.4125 | 9.49494 |
December | 744.00000 | 21.00845 | 28.38238 | -0.5670 | 11.80657 |
Annual Sum or Average | 8760.00000 | 22.35803 | 39.85743 | -0.4906 | 11.42927 |
Minimum of Months | 672.00000 | 20.79501 | 24.53538 | -0.7406 | 6.42217 |
Maximum of Months | 744.00000 | 23.97148 | 56.92998 | -0.1655 | 18.66447 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.12521 | 25.95036 | -0.5347 | 11.36774 |
February | 672.00000 | 21.33387 | 31.68761 | -0.4425 | 10.71108 |
March | 744.00000 | 22.22301 | 40.11722 | -0.1716 | 6.84948 |
April | 720.00000 | 23.14390 | 43.58559 | 0.07702 | 5.90817 |
May | 744.00000 | 23.93777 | 47.24189 | -0.6349 | 13.68704 |
June | 720.00000 | 23.98605 | 52.38065 | -0.5432 | 11.27384 |
July | 744.00000 | 23.99991 | 55.32068 | -0.4998 | 10.24364 |
August | 744.00000 | 23.99992 | 53.80689 | -0.5122 | 10.52628 |
September | 720.00000 | 23.94601 | 44.72183 | -0.6221 | 13.39468 |
October | 744.00000 | 23.62198 | 40.93014 | 0.17384 | 5.76417 |
November | 720.00000 | 22.51201 | 38.88279 | -0.1080 | 7.03994 |
December | 744.00000 | 21.31538 | 32.08745 | -0.4423 | 9.40155 |
Annual Sum or Average | 8760.00000 | 22.93673 | 42.28349 | -0.3549 | 9.67520 |
Minimum of Months | 672.00000 | 21.12521 | 25.95036 | -0.6349 | 5.76417 |
Maximum of Months | 744.00000 | 23.99992 | 55.32068 | 0.17384 | 13.68704 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.528106E+09 | 4658.69 | 17-JAN-19:05 | 194.52 | 0.249076E+10 | 0.00 | 0.301887E+10 | 1.23 | 4.72 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.797684E+09 | 9965.59 | 25-FEB-09:02 | 248.61 | 0.376220E+10 | 0.00 | 0.455989E+10 | 1.74 | 4.72 | 02-FEB-16:12 | 0.00 | 0.00 |
March | 0.321007E+10 | 30893.33 | 25-MAR-15:11 | 429.72 | 0.149175E+11 | 0.00 | 0.181276E+11 | 2.72 | 4.72 | 01-MAR-01:50 | 0.00 | 0.00 |
April | 0.206062E+11 | 117862.06 | 18-APR-15:13 | 525.19 | 0.875426E+11 | 0.00 | 0.108149E+12 | 3.37 | 4.72 | 01-APR-00:30 | 0.00 | 0.00 |
May | 0.457820E+11 | 118478.70 | 31-MAY-18:03 | 728.57 | 0.199034E+12 | 0.00 | 0.244816E+12 | 4.47 | 4.72 | 01-MAY-02:50 | 0.00 | 0.00 |
June | 0.113450E+12 | 161415.67 | 11-JUN-15:13 | 707.56 | 0.465721E+12 | 0.00 | 0.579171E+12 | 4.26 | 4.72 | 01-JUN-01:30 | 0.00 | 0.00 |
July | 0.154436E+12 | 184218.00 | 26-JUL-18:03 | 744.00 | 0.644215E+12 | 0.00 | 0.798651E+12 | 4.28 | 4.72 | 19-JUL-03:40 | 0.00 | 0.00 |
August | 0.135169E+12 | 187280.11 | 04-AUG-15:13 | 744.00 | 0.563543E+12 | 0.00 | 0.698712E+12 | 4.32 | 4.72 | 06-AUG-08:09 | 0.00 | 0.00 |
September | 0.622233E+11 | 139132.19 | 06-SEP-15:13 | 672.28 | 0.258643E+12 | 0.00 | 0.320866E+12 | 4.17 | 4.72 | 01-SEP-24:00 | 0.00 | 0.00 |
October | 0.100182E+11 | 60277.16 | 20-OCT-15:12 | 533.44 | 0.459558E+11 | 0.00 | 0.559739E+11 | 3.36 | 4.72 | 01-OCT-08:61 | 0.00 | 0.00 |
November | 0.281020E+10 | 30615.22 | 05-NOV-15:11 | 383.38 | 0.131820E+11 | 0.00 | 0.159922E+11 | 2.51 | 4.72 | 01-NOV-06:05 | 0.00 | 0.00 |
December | 0.958854E+09 | 7520.57 | 03-DEC-09:02 | 346.98 | 0.452235E+10 | 0.00 | 0.548120E+10 | 2.20 | 4.72 | 01-DEC-01:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.549989E+12 | 6258.23 | 0.230353E+13 | 0.00 | 0.285352E+13 | 3.23 | 0.00 | 0.00 | ||||
Minimum of Months | 0.528106E+09 | 4658.69 | 194.52 | 0.249076E+10 | 0.00 | 0.301887E+10 | 1.23 | 4.72 | 0.00 | 0.00 | ||
Maximum of Months | 0.154436E+12 | 187280.11 | 744.00 | 0.644215E+12 | 0.00 | 0.798651E+12 | 4.47 | 4.72 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.334380E+12 | 0.00 | 744.00 | 493651.75 | 31-JAN-04:00 | 0.00 | 39.31 | 60.00 | 1.39 | 0.00 | 0.20 | 0.78 | 31-JAN-04:00 |
February | 0.273861E+12 | 0.00 | 672.00 | 525437.76 | 02-FEB-06:00 | 0.00 | 39.53 | 60.00 | 1.25 | 0.00 | 0.18 | 0.83 | 02-FEB-06:00 |
March | 0.106556E+12 | 0.00 | 740.81 | 179927.29 | 09-MAR-16:12 | 0.00 | 40.63 | 59.93 | 0.48 | 0.00 | 0.06 | 0.29 | 09-MAR-16:12 |
April | 0.643074E+11 | 0.00 | 592.03 | 182852.21 | 27-APR-15:12 | 0.00 | 38.41 | 56.55 | 0.26 | 0.00 | 0.04 | 0.29 | 27-APR-15:12 |
May | 0.155127E+11 | 0.00 | 239.15 | 113464.74 | 02-MAY-08:04 | 0.00 | 36.73 | 45.26 | 0.05 | 0.00 | 0.01 | 0.18 | 02-MAY-08:04 |
June | 0.262213E+10 | 0.00 | 100.06 | 50207.35 | 03-JUN-04:00 | 0.00 | 41.82 | 44.85 | 0.01 | 0.00 | 0.00 | 0.08 | 03-JUN-04:00 |
July | 57112214.68 | 0.00 | 11.18 | 16772.35 | 11-JUL-08:55 | 0.00 | 42.86 | 43.14 | 0.00 | 0.00 | 0.00 | 0.03 | 11-JUL-08:55 |
August | 0.210516E+09 | 0.00 | 14.35 | 40905.61 | 08-AUG-15:17 | 0.00 | 42.31 | 42.72 | 0.00 | 0.00 | 0.00 | 0.06 | 08-AUG-15:17 |
September | 0.175252E+11 | 0.00 | 240.43 | 112590.03 | 30-SEP-08:04 | 0.00 | 37.06 | 44.42 | 0.07 | 0.00 | 0.01 | 0.18 | 30-SEP-08:04 |
October | 0.756351E+11 | 0.00 | 647.86 | 157122.24 | 26-OCT-08:03 | 0.00 | 39.35 | 58.22 | 0.28 | 0.00 | 0.04 | 0.25 | 26-OCT-08:03 |
November | 0.134753E+12 | 0.00 | 702.37 | 465869.29 | 26-NOV-07:00 | 0.00 | 40.90 | 59.67 | 0.59 | 0.00 | 0.08 | 0.74 | 26-NOV-07:00 |
December | 0.175275E+12 | 0.00 | 744.00 | 227223.49 | 11-DEC-09:05 | 0.00 | 41.94 | 60.00 | 0.83 | 0.00 | 0.10 | 0.36 | 11-DEC-09:05 |
Annual Sum or Average | 0.120070E+13 | 0.00 | 5448.23 | 0.00 | 40.08 | 52.86 | 0.43 | 0.00 | 0.06 | ||||
Minimum of Months | 57112214.68 | 0.00 | 11.18 | 16772.35 | 0.00 | 36.73 | 42.72 | 0.00 | 0.00 | 0.00 | 0.03 | ||
Maximum of Months | 0.334380E+12 | 0.00 | 744.00 | 525437.76 | 0.00 | 42.86 | 60.00 | 1.39 | 0.00 | 0.20 | 0.83 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 0.189758E+09 | 0.00 | 16.00 | 0.189758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8515.76 | 19-MAR-16:00 | 8515.76 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.306682E+10 | 0.00 | 77.17 | 0.244039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26462.51 | 18-APR-08:50 | 18716.77 | 15-APR-15:12 | 0.00 | 0.00 | 0.00 |
May | 0.699804E+10 | 0.00 | 235.33 | 0.526532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29139.22 | 29-MAY-15:13 | 18572.91 | 31-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.229820E+11 | 0.00 | 394.67 | 0.149848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40089.38 | 26-JUN-06:45 | 20064.61 | 11-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.347628E+11 | 0.00 | 518.17 | 0.197789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40259.69 | 17-JUL-18:50 | 18979.39 | 26-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.283337E+11 | 0.00 | 475.17 | 0.165087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42516.66 | 31-AUG-18:03 | 20409.14 | 04-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.103411E+11 | 0.00 | 268.33 | 0.886675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29549.17 | 11-SEP-08:15 | 19410.19 | 06-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.596914E+09 | 0.00 | 38.00 | 0.596914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15124.14 | 20-OCT-15:12 | 15124.14 | 20-OCT-15:12 | 0.00 | 0.00 | 0.00 |
November | 22232899.69 | 0.00 | 6.67 | 22232899.69 | 0.00 | 0.00 | 0.00 | 0.00 | 1791.45 | 03-NOV-15:11 | 1791.45 | 03-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107293E+12 | 0.00 | 2029.50 | 0.686538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.347628E+11 | 0.00 | 518.17 | 0.197789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42516.66 | 20409.14 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.154201E+09 | 0.00 | 145.82 | 0.154201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4029.28 | 13-JAN-06:10 | 4029.28 | 13-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.177605E+09 | 0.00 | 170.46 | 0.177605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4045.35 | 14-FEB-06:10 | 4045.35 | 14-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.353060E+10 | 0.00 | 227.47 | 0.353060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77611.90 | 19-MAR-16:20 | 77611.90 | 19-MAR-16:20 | 0.00 | 0.00 | 0.00 |
April | 0.468361E+11 | 0.00 | 234.80 | 0.398223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 287759.19 | 18-APR-10:35 | 208585.39 | 15-APR-17:15 | 0.00 | 0.00 | 0.00 |
May | 0.112493E+12 | 0.00 | 366.83 | 0.917267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 278104.23 | 29-MAY-18:03 | 215953.29 | 31-MAY-18:10 | 0.00 | 0.00 | 0.00 |
June | 0.319398E+12 | 0.00 | 543.22 | 0.225699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 391713.68 | 26-JUN-06:52 | 235498.44 | 26-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.463873E+12 | 0.00 | 691.67 | 0.289093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 456048.86 | 17-JUL-19:10 | 232380.22 | 03-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.399658E+12 | 0.00 | 645.67 | 0.255094E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 460232.97 | 28-AUG-19:40 | 228604.47 | 03-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 0.154441E+12 | 0.00 | 388.50 | 0.141124E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 291809.70 | 11-SEP-10:35 | 228687.02 | 07-SEP-18:10 | 0.00 | 0.00 | 0.00 |
October | 0.114415E+11 | 0.00 | 105.56 | 0.114415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145960.90 | 20-OCT-15:10 | 145960.90 | 20-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.771668E+09 | 0.00 | 193.46 | 0.771668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25205.05 | 03-NOV-15:13 | 25205.05 | 03-NOV-15:13 | 0.00 | 0.00 | 0.00 |
December | 0.285675E+09 | 0.00 | 278.90 | 0.285675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4010.45 | 01-DEC-06:10 | 4010.45 | 01-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151306E+13 | 0.00 | 3992.36 | 0.105892E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.154201E+09 | 0.00 | 105.56 | 0.154201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4010.45 | 4010.45 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.463873E+12 | 0.00 | 691.67 | 0.289093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 460232.97 | 235498.44 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 5651838.22 | 0.00 | 0.99 | 3701130.86 | 0.00 | 0.00 | 0.00 | 0.00 | 11107.31 | 12-JAN-16:12 | 11107.31 | 12-JAN-16:12 | 0.00 | 0.00 | 0.00 |
February | 0.123628E+09 | 0.00 | 19.82 | 67379003.31 | 0.00 | 0.00 | 0.00 | 0.00 | 16188.78 | 17-FEB-16:11 | 16188.78 | 17-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.400733E+09 | 0.00 | 78.55 | 0.256061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16660.58 | 10-MAR-16:11 | 16660.58 | 10-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.241126E+10 | 0.00 | 273.44 | 0.150366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16873.16 | 16-APR-08:61 | 16659.80 | 20-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.434981E+10 | 0.00 | 553.56 | 0.214619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17151.77 | 29-MAY-08:61 | 16659.65 | 06-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.769481E+10 | 0.00 | 606.22 | 0.419539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18042.89 | 25-JUN-08:61 | 14642.21 | 22-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.979390E+10 | 0.00 | 695.56 | 0.534146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18590.93 | 20-JUL-08:61 | 14768.25 | 21-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.874678E+10 | 0.00 | 689.89 | 0.448780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19621.98 | 31-AUG-08:61 | 14576.28 | 12-AUG-15:11 | 0.00 | 0.00 | 0.00 |
September | 0.531121E+10 | 0.00 | 504.64 | 0.295924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17388.39 | 11-SEP-08:61 | 14756.91 | 17-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.107788E+10 | 0.00 | 188.01 | 0.570425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15893.60 | 02-OCT-15:11 | 14553.49 | 02-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.200327E+09 | 0.00 | 35.91 | 0.114043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16657.81 | 12-NOV-16:11 | 16657.81 | 12-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 7679658.60 | 0.00 | 1.65 | 6542656.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16018.26 | 01-DEC-16:12 | 16018.26 | 01-DEC-16:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401237E+11 | 0.00 | 3648.24 | 0.216519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5651838.22 | 0.00 | 0.99 | 3701130.86 | 0.00 | 0.00 | 0.00 | 0.00 | 11107.31 | 11107.31 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.979390E+10 | 0.00 | 695.56 | 0.534146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19621.98 | 16660.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 190769.80 | 0.00 | 0.10 | 38768.10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.44 | 12-JAN-16:13 | 171.32 | 12-JAN-16:13 | 0.00 | 0.00 | 0.00 |
February | 28811654.08 | 0.00 | 6.38 | 13786989.98 | 0.00 | 0.00 | 0.00 | 0.00 | 11723.52 | 25-FEB-16:11 | 11723.52 | 25-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.120511E+09 | 0.00 | 32.74 | 74775473.67 | 0.00 | 0.00 | 0.00 | 0.00 | 15528.18 | 21-MAR-18:01 | 15528.18 | 21-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.144669E+10 | 0.00 | 187.61 | 0.853318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16585.47 | 16-APR-21:51 | 16241.13 | 29-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.284660E+10 | 0.00 | 427.79 | 0.121999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18157.31 | 20-MAY-18:41 | 18157.31 | 20-MAY-18:41 | 0.00 | 0.00 | 0.00 |
June | 0.603584E+10 | 0.00 | 466.91 | 0.333174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20544.97 | 26-JUN-08:11 | 16142.67 | 16-JUN-16:32 | 0.00 | 0.00 | 0.00 |
July | 0.738243E+10 | 0.00 | 503.86 | 0.410645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18841.86 | 02-JUL-08:51 | 15481.36 | 23-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.610450E+10 | 0.00 | 502.91 | 0.301518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20788.41 | 03-AUG-07:51 | 15892.82 | 11-AUG-18:11 | 0.00 | 0.00 | 0.00 |
September | 0.333151E+10 | 0.00 | 370.84 | 0.164754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17084.37 | 11-SEP-08:51 | 14863.86 | 12-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 0.305880E+09 | 0.00 | 79.92 | 0.124854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15527.43 | 02-OCT-18:01 | 13653.93 | 10-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 54243628.11 | 0.00 | 9.28 | 28776966.72 | 0.00 | 0.00 | 0.00 | 0.00 | 13061.20 | 03-NOV-16:11 | 13061.20 | 03-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 404648.16 | 0.00 | 0.12 | 265398.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.03 | 01-DEC-16:13 | 1343.03 | 01-DEC-16:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276576E+11 | 0.00 | 2588.45 | 0.144167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 190769.80 | 0.00 | 0.10 | 38768.10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.44 | 171.32 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.738243E+10 | 0.00 | 503.86 | 0.410645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20788.41 | 18157.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 0.233743E+10 | 0.00 | 78.35 | 0.220946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30028.33 | 24-MAR-13:10 | 30028.33 | 24-MAR-13:10 | 0.00 | 0.00 | 0.00 |
April | 0.109689E+11 | 0.00 | 235.95 | 0.626600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46560.98 | 15-APR-13:15 | 42043.23 | 15-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.219428E+11 | 0.00 | 567.23 | 0.905503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33883.83 | 05-MAY-13:15 | 23537.58 | 06-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.326985E+11 | 0.00 | 629.67 | 0.129913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36333.13 | 26-JUN-12:40 | 25165.47 | 26-JUN-12:50 | 0.00 | 0.00 | 0.00 |
July | 0.414807E+11 | 0.00 | 729.83 | 0.168347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38908.31 | 30-JUL-13:30 | 29542.92 | 30-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.425729E+11 | 0.00 | 734.17 | 0.186563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43812.10 | 29-AUG-13:30 | 38064.37 | 29-AUG-13:30 | 0.00 | 0.00 | 0.00 |
September | 0.344368E+11 | 0.00 | 558.77 | 0.194604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53110.25 | 07-SEP-13:00 | 47364.26 | 16-SEP-13:50 | 0.00 | 0.00 | 0.00 |
October | 0.161596E+11 | 0.00 | 349.43 | 0.136837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51433.23 | 20-OCT-12:50 | 51433.23 | 20-OCT-12:50 | 0.00 | 0.00 | 0.00 |
November | 0.442506E+10 | 0.00 | 110.74 | 0.338659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49679.10 | 04-NOV-12:30 | 42897.95 | 04-NOV-11:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207023E+12 | 0.00 | 3994.13 | 0.102543E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.425729E+11 | 0.00 | 734.17 | 0.194604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53110.25 | 51433.23 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 10402245.70 | 0.00 | 0.55 | 8167640.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11769.59 | 13-JAN-19:03 | 10507.87 | 17-JAN-19:05 | 0.00 | 0.00 | 0.00 |
February | 43304575.67 | 0.00 | 3.27 | 28819990.56 | 0.00 | 0.00 | 0.00 | 0.00 | 56238.88 | 25-FEB-09:02 | 56238.88 | 25-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.201391E+10 | 0.00 | 104.34 | 0.847928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75223.16 | 25-MAR-18:23 | 75223.16 | 25-MAR-18:23 | 0.00 | 0.00 | 0.00 |
April | 0.974528E+10 | 0.00 | 241.50 | 0.547501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83141.06 | 16-APR-21:51 | 79978.25 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.276119E+11 | 0.00 | 426.03 | 0.153953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88024.28 | 11-MAY-21:42 | 81133.27 | 06-MAY-19:31 | 0.00 | 0.00 | 0.00 |
June | 0.432228E+11 | 0.00 | 455.68 | 0.266241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102958.74 | 26-JUN-08:11 | 75052.99 | 21-JUN-21:01 | 0.00 | 0.00 | 0.00 |
July | 0.470378E+11 | 0.00 | 448.13 | 0.283185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92712.90 | 02-JUL-08:51 | 73539.52 | 22-JUL-21:31 | 0.00 | 0.00 | 0.00 |
August | 0.413914E+11 | 0.00 | 432.29 | 0.237082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106916.84 | 03-AUG-07:51 | 74531.00 | 11-AUG-18:11 | 0.00 | 0.00 | 0.00 |
September | 0.248861E+11 | 0.00 | 407.17 | 0.138703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85140.94 | 11-SEP-21:51 | 80149.10 | 19-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.577595E+10 | 0.00 | 259.84 | 0.242535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75899.61 | 12-OCT-15:11 | 75899.61 | 12-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.246410E+10 | 0.00 | 110.41 | 0.878880E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74640.28 | 04-NOV-18:01 | 74640.28 | 04-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 12688638.89 | 0.00 | 0.82 | 9065564.14 | 0.00 | 0.00 | 0.00 | 0.00 | 13124.62 | 03-DEC-09:02 | 11153.32 | 19-DEC-19:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204216E+12 | 0.00 | 2890.02 | 0.117590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10402245.70 | 0.00 | 0.55 | 8167640.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11769.59 | 10507.87 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.470378E+11 | 0.00 | 455.68 | 0.283185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106916.84 | 81133.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3593278.11 | 0.00 | 1.94 | 855457.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2730.22 | 12-JAN-09:03 | 1483.36 | 12-JAN-09:03 | 0.00 | 0.00 | 0.00 |
February | 78159005.88 | 0.00 | 15.48 | 44192570.58 | 0.00 | 0.00 | 0.00 | 0.00 | 12679.86 | 21-FEB-09:02 | 12679.86 | 21-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.376307E+09 | 0.00 | 93.39 | 0.209764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14437.06 | 22-MAR-15:13 | 14437.06 | 22-MAR-15:13 | 0.00 | 0.00 | 0.00 |
April | 0.203669E+10 | 0.00 | 274.87 | 0.114882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15125.39 | 06-APR-15:11 | 15125.39 | 06-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.464502E+10 | 0.00 | 600.72 | 0.224174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15289.69 | 11-MAY-15:11 | 15126.97 | 06-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.782848E+10 | 0.00 | 635.14 | 0.429308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16502.31 | 14-JUN-08:62 | 13412.21 | 15-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.956803E+10 | 0.00 | 713.46 | 0.513979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16919.47 | 20-JUL-08:61 | 13342.25 | 21-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.842546E+10 | 0.00 | 707.76 | 0.423038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17841.08 | 31-AUG-08:61 | 13463.23 | 15-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.533203E+10 | 0.00 | 528.73 | 0.294008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15073.14 | 10-SEP-08:61 | 13390.00 | 18-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.885678E+09 | 0.00 | 202.61 | 0.400478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14765.36 | 02-OCT-15:11 | 13077.38 | 21-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.161473E+09 | 0.00 | 39.41 | 77085926.04 | 0.00 | 0.00 | 0.00 | 0.00 | 12919.41 | 03-NOV-15:11 | 12919.41 | 03-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 20816027.01 | 0.00 | 6.17 | 9914303.37 | 0.00 | 0.00 | 0.00 | 0.00 | 9688.83 | 03-DEC-09:02 | 9223.55 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393617E+11 | 0.00 | 3819.68 | 0.207362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3593278.11 | 0.00 | 1.94 | 855457.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2730.22 | 1483.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.956803E+10 | 0.00 | 713.46 | 0.513979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17841.08 | 15126.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 339668.32 | 0.00 | 0.11 | 88920.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1412.96 | 12-JAN-09:05 | 465.80 | 12-JAN-09:05 | 0.00 | 0.00 | 0.00 |
February | 13862981.88 | 0.00 | 5.88 | 4946781.74 | 0.00 | 0.00 | 0.00 | 0.00 | 10014.82 | 24-FEB-09:02 | 10014.82 | 24-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.109424E+09 | 0.00 | 30.55 | 58361526.54 | 0.00 | 0.00 | 0.00 | 0.00 | 11017.98 | 28-MAR-08:62 | 11017.98 | 28-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.118255E+10 | 0.00 | 172.89 | 0.632257E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16069.98 | 18-APR-08:51 | 14605.63 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.330238E+10 | 0.00 | 481.60 | 0.155062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17947.39 | 31-MAY-08:32 | 14970.04 | 31-MAY-08:32 | 0.00 | 0.00 | 0.00 |
June | 0.619888E+10 | 0.00 | 496.81 | 0.345024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19681.30 | 26-JUN-07:52 | 15921.90 | 09-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.714688E+10 | 0.00 | 516.68 | 0.385549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18817.34 | 05-JUL-08:32 | 15471.02 | 01-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.591962E+10 | 0.00 | 516.18 | 0.289840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18829.91 | 03-AUG-07:51 | 14990.42 | 11-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.339735E+10 | 0.00 | 397.42 | 0.169118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16772.11 | 11-SEP-08:51 | 15006.26 | 17-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.201721E+09 | 0.00 | 62.30 | 77519350.51 | 0.00 | 0.00 | 0.00 | 0.00 | 13697.91 | 02-OCT-18:01 | 12189.62 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 18343187.29 | 0.00 | 5.01 | 7434234.05 | 0.00 | 0.00 | 0.00 | 0.00 | 10922.70 | 04-NOV-08:62 | 10922.70 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 661368.93 | 0.00 | 0.11 | 368652.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2079.79 | 02-DEC-09:03 | 1779.50 | 25-DEC-09:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274920E+11 | 0.00 | 2685.54 | 0.142269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 339668.32 | 0.00 | 0.11 | 88920.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1412.96 | 465.80 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.714688E+10 | 0.00 | 516.68 | 0.385549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19681.30 | 15921.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1019022.53 | 0.00 | 0.68 | 613025.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2882.01 | 12-JAN-16:12 | 2882.01 | 12-JAN-16:12 | 0.00 | 0.00 | 0.00 |
February | 30511254.13 | 0.00 | 16.67 | 16544337.01 | 0.00 | 0.00 | 0.00 | 0.00 | 3819.64 | 17-FEB-16:11 | 3819.64 | 17-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 90040271.37 | 0.00 | 62.95 | 57748109.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4345.24 | 22-MAR-15:11 | 4345.24 | 22-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.624697E+09 | 0.00 | 244.73 | 0.407017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4476.06 | 16-APR-08:61 | 4345.43 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.109532E+10 | 0.00 | 495.94 | 0.580450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4629.84 | 29-MAY-08:61 | 4344.62 | 06-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.198001E+10 | 0.00 | 584.87 | 0.112201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4860.42 | 25-JUN-08:61 | 3808.48 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.249193E+10 | 0.00 | 691.83 | 0.140679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5042.48 | 20-JUL-08:61 | 3855.39 | 21-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.217675E+10 | 0.00 | 684.29 | 0.115199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5276.36 | 31-AUG-08:61 | 3794.42 | 31-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.128762E+10 | 0.00 | 456.33 | 0.751821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4673.00 | 11-SEP-08:61 | 4345.01 | 20-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.260593E+09 | 0.00 | 144.76 | 0.147954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4134.61 | 02-OCT-15:11 | 3786.75 | 02-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 48977421.02 | 0.00 | 25.55 | 30083189.97 | 0.00 | 0.00 | 0.00 | 0.00 | 4344.84 | 12-NOV-16:11 | 4344.84 | 12-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 1463347.49 | 0.00 | 0.73 | 1241176.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3898.79 | 01-DEC-16:12 | 3898.79 | 01-DEC-16:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100889E+11 | 0.00 | 3409.32 | 0.567426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1019022.53 | 0.00 | 0.68 | 613025.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2882.01 | 2882.01 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.249193E+10 | 0.00 | 691.83 | 0.140679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5276.36 | 4345.43 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 90894.84 | 0.00 | 0.05 | 38466.10 | 0.00 | 0.00 | 0.00 | 0.00 | 670.70 | 13-JAN-16:14 | 334.42 | 13-JAN-16:14 | 0.00 | 0.00 | 0.00 |
February | 5211770.83 | 0.00 | 5.07 | 2291531.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3022.30 | 25-FEB-16:11 | 3022.30 | 25-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 22491131.73 | 0.00 | 23.89 | 13535301.46 | 0.00 | 0.00 | 0.00 | 0.00 | 4033.66 | 21-MAR-18:01 | 4033.66 | 21-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.374453E+09 | 0.00 | 168.19 | 0.229581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4409.68 | 16-APR-21:51 | 4310.12 | 29-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.722993E+09 | 0.00 | 384.67 | 0.338097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4756.34 | 20-MAY-18:41 | 4756.34 | 20-MAY-18:41 | 0.00 | 0.00 | 0.00 |
June | 0.160253E+10 | 0.00 | 452.65 | 0.919861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5466.73 | 26-JUN-08:11 | 4230.02 | 16-JUN-16:32 | 0.00 | 0.00 | 0.00 |
July | 0.194636E+10 | 0.00 | 504.71 | 0.111033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4965.01 | 02-JUL-08:51 | 4191.69 | 23-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.156293E+10 | 0.00 | 503.79 | 0.792749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5612.49 | 03-AUG-07:51 | 4128.47 | 11-AUG-18:11 | 0.00 | 0.00 | 0.00 |
September | 0.809081E+09 | 0.00 | 328.27 | 0.423154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4494.39 | 11-SEP-08:51 | 3878.06 | 12-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 65092929.64 | 0.00 | 56.63 | 25966725.11 | 0.00 | 0.00 | 0.00 | 0.00 | 4048.20 | 02-OCT-18:01 | 3569.35 | 10-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 13228059.55 | 0.00 | 6.66 | 6831198.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3452.03 | 03-NOV-16:11 | 3452.03 | 03-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 17277.50 | 0.00 | 0.05 | 3171.13 | 0.00 | 0.00 | 0.00 | 0.00 | 196.24 | 02-DEC-16:13 | 36.89 | 02-DEC-16:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.712448E+10 | 0.00 | 2434.63 | 0.386244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 17277.50 | 0.00 | 0.05 | 3171.13 | 0.00 | 0.00 | 0.00 | 0.00 | 196.24 | 36.89 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.194636E+10 | 0.00 | 504.71 | 0.111033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5612.49 | 4756.34 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.405710E+09 | 0.00 | 50.05 | 0.325660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19999.94 | 02-JAN-16:11 | 19999.94 | 02-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.840916E+09 | 0.00 | 87.08 | 0.554586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19998.39 | 17-FEB-16:11 | 19998.39 | 17-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.151669E+10 | 0.00 | 192.62 | 0.955967E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19998.44 | 21-MAR-15:11 | 19998.44 | 21-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.371841E+10 | 0.00 | 312.29 | 0.229554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20330.53 | 16-APR-08:61 | 18813.79 | 29-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.590814E+10 | 0.00 | 564.41 | 0.279180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20807.04 | 31-MAY-08:61 | 19807.60 | 20-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.920601E+10 | 0.00 | 608.91 | 0.470505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22582.25 | 25-JUN-08:61 | 17448.33 | 03-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.115456E+11 | 0.00 | 684.47 | 0.592930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23641.32 | 20-JUL-08:61 | 17797.29 | 07-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.114403E+11 | 0.00 | 680.31 | 0.595004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24588.44 | 31-AUG-08:61 | 17511.50 | 23-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.847543E+10 | 0.00 | 542.07 | 0.516769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21510.19 | 11-SEP-08:61 | 19997.26 | 20-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.397160E+10 | 0.00 | 361.99 | 0.249487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18328.76 | 02-OCT-15:11 | 17760.89 | 02-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.126958E+10 | 0.00 | 144.55 | 0.840562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19941.55 | 21-NOV-16:11 | 19941.55 | 21-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.807391E+09 | 0.00 | 80.41 | 0.662997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20000.54 | 25-DEC-16:11 | 20000.54 | 25-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.591058E+11 | 0.00 | 4309.16 | 0.326741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.405710E+09 | 0.00 | 50.05 | 0.325660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18328.76 | 17448.33 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.115456E+11 | 0.00 | 684.47 | 0.595004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24588.44 | 20000.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 801.79 | 549.34 | 252.45 | 702.01 | 919.29 | 0.00 | 0.00 | 0.00 |
February | 864.33 | 586.41 | 277.93 | 791.26 | 737.47 | 0.00 | 0.00 | 0.00 |
March | 740.39 | 387.58 | 352.81 | 710.01 | 529.77 | 0.00 | 0.00 | 0.00 |
April | 660.07 | 302.50 | 357.56 | 713.24 | 388.67 | 0.00 | 0.00 | 0.00 |
May | 562.94 | 157.48 | 405.47 | 658.89 | 224.01 | 0.00 | 0.00 | 0.00 |
June | 537.40 | 107.32 | 430.08 | 697.70 | 146.29 | 0.00 | 0.00 | 0.00 |
July | 570.29 | 142.63 | 427.66 | 772.60 | 125.35 | 0.00 | 0.00 | 0.00 |
August | 631.96 | 218.85 | 413.11 | 864.39 | 153.11 | 0.00 | 0.00 | 0.00 |
September | 763.02 | 393.73 | 369.29 | 973.46 | 259.62 | 0.00 | 0.00 | 0.00 |
October | 822.27 | 518.40 | 303.86 | 912.37 | 399.56 | 0.00 | 0.00 | 0.00 |
November | 615.43 | 385.32 | 230.12 | 574.89 | 591.77 | 0.00 | 0.00 | 0.00 |
December | 655.31 | 496.29 | 159.02 | 614.64 | 855.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 684.42 | 352.53 | 331.89 | 748.54 | 442.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 537.40 | 107.32 | 159.02 | 574.89 | 125.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 864.33 | 586.41 | 430.08 | 973.46 | 919.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2257.79 | 1546.92 | 710.88 | 1969.70 | 2598.23 | 0.00 | 0.00 | 0.00 |
February | 2433.90 | 1651.28 | 782.62 | 2220.86 | 2092.63 | 0.00 | 0.00 | 0.00 |
March | 2084.88 | 1091.39 | 993.50 | 1997.04 | 1502.39 | 0.00 | 0.00 | 0.00 |
April | 1858.70 | 851.83 | 1006.87 | 2016.31 | 1095.04 | 0.00 | 0.00 | 0.00 |
May | 1585.22 | 443.45 | 1141.77 | 1893.51 | 607.31 | 0.00 | 0.00 | 0.00 |
June | 1513.27 | 302.21 | 1211.06 | 2018.31 | 382.10 | 0.00 | 0.00 | 0.00 |
July | 1605.91 | 401.63 | 1204.28 | 2236.98 | 313.53 | 0.00 | 0.00 | 0.00 |
August | 1779.57 | 616.27 | 1163.30 | 2483.62 | 392.28 | 0.00 | 0.00 | 0.00 |
September | 2148.61 | 1108.71 | 1039.90 | 2760.00 | 707.51 | 0.00 | 0.00 | 0.00 |
October | 2315.45 | 1459.79 | 855.65 | 2570.32 | 1129.34 | 0.00 | 0.00 | 0.00 |
November | 1733.02 | 1085.03 | 647.99 | 1612.95 | 1681.06 | 0.00 | 0.00 | 0.00 |
December | 1845.31 | 1397.51 | 447.80 | 1727.32 | 2418.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1927.27 | 992.70 | 934.58 | 2125.05 | 1239.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1513.27 | 302.21 | 447.80 | 1612.95 | 313.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2433.90 | 1651.28 | 1211.06 | 2760.00 | 2598.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2933.00 | 2009.53 | 923.47 | 2588.31 | 3507.64 | 0.00 | 0.00 | 0.00 |
February | 3161.78 | 2145.11 | 1016.67 | 2924.23 | 2834.24 | 0.00 | 0.00 | 0.00 |
March | 2708.38 | 1417.77 | 1290.61 | 2629.80 | 2059.77 | 0.00 | 0.00 | 0.00 |
April | 2414.56 | 1106.58 | 1307.98 | 2658.21 | 1516.02 | 0.00 | 0.00 | 0.00 |
May | 2059.29 | 576.06 | 1483.22 | 2474.59 | 858.93 | 0.00 | 0.00 | 0.00 |
June | 1965.83 | 392.58 | 1573.24 | 2638.82 | 547.88 | 0.00 | 0.00 | 0.00 |
July | 2086.17 | 521.74 | 1564.42 | 2928.54 | 449.56 | 0.00 | 0.00 | 0.00 |
August | 2311.76 | 800.57 | 1511.19 | 3259.55 | 554.78 | 0.00 | 0.00 | 0.00 |
September | 2791.16 | 1440.28 | 1350.89 | 3630.34 | 986.70 | 0.00 | 0.00 | 0.00 |
October | 3007.90 | 1896.35 | 1111.54 | 3378.84 | 1560.22 | 0.00 | 0.00 | 0.00 |
November | 2251.29 | 1409.51 | 841.78 | 2114.07 | 2307.49 | 0.00 | 0.00 | 0.00 |
December | 2397.16 | 1815.44 | 581.72 | 2271.76 | 3283.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2503.64 | 1289.57 | 1214.07 | 2790.67 | 1700.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1965.83 | 392.58 | 581.72 | 2114.07 | 449.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3161.78 | 2145.11 | 1573.24 | 3630.34 | 3507.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.53 | 108.61 | 49.91 | 139.42 | 187.56 | 0.00 | 0.00 | 0.00 |
February | 170.89 | 115.94 | 54.95 | 156.72 | 150.30 | 0.00 | 0.00 | 0.00 |
March | 146.39 | 76.63 | 69.76 | 140.82 | 107.05 | 0.00 | 0.00 | 0.00 |
April | 130.51 | 59.81 | 70.70 | 141.93 | 76.61 | 0.00 | 0.00 | 0.00 |
May | 111.30 | 31.14 | 80.17 | 132.02 | 40.99 | 0.00 | 0.00 | 0.00 |
June | 106.25 | 21.22 | 85.03 | 142.34 | 23.76 | 0.00 | 0.00 | 0.00 |
July | 112.76 | 28.20 | 84.56 | 158.03 | 18.47 | 0.00 | 0.00 | 0.00 |
August | 124.95 | 43.27 | 81.68 | 175.56 | 23.37 | 0.00 | 0.00 | 0.00 |
September | 150.86 | 77.85 | 73.02 | 195.95 | 45.89 | 0.00 | 0.00 | 0.00 |
October | 162.58 | 102.50 | 60.08 | 182.23 | 77.23 | 0.00 | 0.00 | 0.00 |
November | 121.68 | 76.18 | 45.50 | 114.65 | 118.91 | 0.00 | 0.00 | 0.00 |
December | 129.57 | 98.12 | 31.44 | 122.74 | 173.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.32 | 69.70 | 65.62 | 150.16 | 86.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.25 | 21.22 | 31.44 | 114.65 | 18.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.89 | 115.94 | 85.03 | 195.95 | 187.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.30 | 41.19 | 60.11 | 42.83 | 397.74 | 0.00 | 0.00 | 0.00 |
February | 147.85 | 72.79 | 75.06 | 91.39 | 316.87 | 0.00 | 0.00 | 0.00 |
March | 176.44 | 65.63 | 110.82 | 129.26 | 206.76 | 0.00 | 0.00 | 0.00 |
April | 258.03 | 127.69 | 130.34 | 265.07 | 139.38 | 0.00 | 0.00 | 0.00 |
May | 258.55 | 103.52 | 155.03 | 298.57 | 74.24 | 0.00 | 0.00 | 0.00 |
June | 302.46 | 130.78 | 171.68 | 393.52 | 43.72 | 0.00 | 0.00 | 0.00 |
July | 324.87 | 154.13 | 170.74 | 436.05 | 34.21 | 0.00 | 0.00 | 0.00 |
August | 283.65 | 129.80 | 153.85 | 379.84 | 43.31 | 0.00 | 0.00 | 0.00 |
September | 230.16 | 109.06 | 121.10 | 279.60 | 85.25 | 0.00 | 0.00 | 0.00 |
October | 161.34 | 72.08 | 89.26 | 149.45 | 150.55 | 0.00 | 0.00 | 0.00 |
November | 96.26 | 35.74 | 60.52 | 57.37 | 243.09 | 0.00 | 0.00 | 0.00 |
December | 74.10 | 35.06 | 39.03 | 38.00 | 358.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 201.47 | 89.81 | 111.66 | 214.03 | 173.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.10 | 35.06 | 39.03 | 38.00 | 34.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.87 | 154.13 | 171.68 | 436.05 | 397.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.41 | 0.00 | 25.41 | 0.07 | 227.85 | 0.00 | 0.00 | 0.00 |
February | 32.22 | 0.00 | 32.22 | 1.38 | 182.88 | 0.00 | 0.00 | 0.00 |
March | 48.29 | 0.00 | 48.29 | 14.61 | 116.52 | 0.00 | 0.00 | 0.00 |
April | 55.96 | 0.45 | 55.51 | 31.33 | 76.52 | 0.00 | 0.00 | 0.00 |
May | 72.77 | 2.76 | 70.01 | 66.62 | 38.66 | 0.00 | 0.00 | 0.00 |
June | 85.15 | 7.89 | 77.26 | 102.34 | 23.67 | 0.00 | 0.00 | 0.00 |
July | 79.87 | 5.51 | 74.36 | 100.25 | 19.73 | 0.00 | 0.00 | 0.00 |
August | 66.92 | 1.36 | 65.57 | 83.23 | 24.46 | 0.00 | 0.00 | 0.00 |
September | 51.21 | 0.05 | 51.16 | 50.82 | 47.63 | 0.00 | 0.00 | 0.00 |
October | 38.03 | 0.00 | 38.03 | 18.30 | 82.50 | 0.00 | 0.00 | 0.00 |
November | 26.60 | 0.00 | 26.60 | 4.44 | 135.72 | 0.00 | 0.00 | 0.00 |
December | 17.25 | 0.00 | 17.25 | 0.01 | 200.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.07 | 1.51 | 48.56 | 39.68 | 97.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.25 | 0.00 | 17.25 | 0.01 | 19.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.15 | 7.89 | 77.26 | 102.34 | 227.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.30 | 41.19 | 60.11 | 44.68 | 394.89 | 0.00 | 0.00 | 0.00 |
February | 147.85 | 72.79 | 75.06 | 94.58 | 312.92 | 0.00 | 0.00 | 0.00 |
March | 176.44 | 65.63 | 110.82 | 133.18 | 204.43 | 0.00 | 0.00 | 0.00 |
April | 258.03 | 127.69 | 130.34 | 267.30 | 138.94 | 0.00 | 0.00 | 0.00 |
May | 258.55 | 103.52 | 155.03 | 297.07 | 75.70 | 0.00 | 0.00 | 0.00 |
June | 302.46 | 130.78 | 171.68 | 389.77 | 46.41 | 0.00 | 0.00 | 0.00 |
July | 324.87 | 154.13 | 170.74 | 431.88 | 38.30 | 0.00 | 0.00 | 0.00 |
August | 283.65 | 129.80 | 153.85 | 377.38 | 47.27 | 0.00 | 0.00 | 0.00 |
September | 230.16 | 109.06 | 121.10 | 280.81 | 86.69 | 0.00 | 0.00 | 0.00 |
October | 161.34 | 72.08 | 89.26 | 153.93 | 148.40 | 0.00 | 0.00 | 0.00 |
November | 96.26 | 35.74 | 60.52 | 59.99 | 240.70 | 0.00 | 0.00 | 0.00 |
December | 74.10 | 35.06 | 39.03 | 40.19 | 355.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 201.47 | 89.81 | 111.66 | 214.83 | 173.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.10 | 35.06 | 39.03 | 40.19 | 38.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.87 | 154.13 | 171.68 | 431.88 | 394.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 126.80 | 86.87 | 39.92 | 114.62 | 133.10 | 0.00 | 0.00 | 0.00 |
February | 136.69 | 92.74 | 43.95 | 125.97 | 117.42 | 0.00 | 0.00 | 0.00 |
March | 117.09 | 61.29 | 55.80 | 109.25 | 89.99 | 0.00 | 0.00 | 0.00 |
April | 104.38 | 47.84 | 56.55 | 106.31 | 79.72 | 0.00 | 0.00 | 0.00 |
May | 89.03 | 24.90 | 64.12 | 93.73 | 50.21 | 0.00 | 0.00 | 0.00 |
June | 84.99 | 16.97 | 68.01 | 101.26 | 33.92 | 0.00 | 0.00 | 0.00 |
July | 90.19 | 22.56 | 67.63 | 113.91 | 28.43 | 0.00 | 0.00 | 0.00 |
August | 99.94 | 34.61 | 65.33 | 128.57 | 34.17 | 0.00 | 0.00 | 0.00 |
September | 120.67 | 62.27 | 58.40 | 146.03 | 55.76 | 0.00 | 0.00 | 0.00 |
October | 130.04 | 81.98 | 48.05 | 134.49 | 84.04 | 0.00 | 0.00 | 0.00 |
November | 97.33 | 60.93 | 36.39 | 86.42 | 106.11 | 0.00 | 0.00 | 0.00 |
December | 103.63 | 78.48 | 25.15 | 99.53 | 125.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.24 | 55.75 | 52.49 | 113.27 | 77.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.99 | 16.97 | 25.15 | 86.42 | 28.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.69 | 92.74 | 68.01 | 146.03 | 133.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.33 | 0.00 | 20.33 | 0.03 | 187.72 | 0.00 | 0.00 | 0.00 |
February | 25.78 | 0.00 | 25.78 | 0.88 | 150.01 | 0.00 | 0.00 | 0.00 |
March | 38.64 | 0.00 | 38.63 | 11.31 | 95.91 | 0.00 | 0.00 | 0.00 |
April | 44.78 | 0.36 | 44.42 | 26.35 | 61.86 | 0.00 | 0.00 | 0.00 |
May | 58.22 | 2.21 | 56.01 | 56.21 | 30.30 | 0.00 | 0.00 | 0.00 |
June | 68.13 | 6.31 | 61.82 | 85.79 | 17.86 | 0.00 | 0.00 | 0.00 |
July | 63.90 | 4.41 | 59.50 | 84.71 | 14.02 | 0.00 | 0.00 | 0.00 |
August | 53.54 | 1.08 | 52.46 | 70.59 | 17.90 | 0.00 | 0.00 | 0.00 |
September | 40.97 | 0.04 | 40.94 | 42.80 | 37.13 | 0.00 | 0.00 | 0.00 |
October | 30.43 | 0.00 | 30.43 | 14.48 | 67.32 | 0.00 | 0.00 | 0.00 |
November | 21.28 | 0.00 | 21.28 | 3.24 | 112.82 | 0.00 | 0.00 | 0.00 |
December | 13.81 | 0.00 | 13.81 | 0.00 | 165.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.06 | 1.21 | 38.85 | 33.23 | 79.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.81 | 0.00 | 13.81 | 0.00 | 14.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.13 | 6.31 | 61.82 | 85.79 | 187.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.38 | 41.55 | 59.84 | 39.53 | 390.93 | 0.00 | 0.00 | 0.00 |
February | 135.00 | 59.42 | 75.58 | 71.69 | 310.19 | 0.00 | 0.00 | 0.00 |
March | 183.35 | 72.74 | 110.60 | 134.63 | 201.46 | 0.00 | 0.00 | 0.00 |
April | 223.78 | 97.53 | 126.25 | 215.32 | 136.12 | 0.00 | 0.00 | 0.00 |
May | 282.75 | 123.67 | 159.08 | 326.29 | 70.16 | 0.00 | 0.00 | 0.00 |
June | 310.73 | 135.37 | 175.37 | 403.13 | 41.38 | 0.00 | 0.00 | 0.00 |
July | 314.15 | 145.01 | 169.13 | 418.06 | 32.02 | 0.00 | 0.00 | 0.00 |
August | 264.85 | 114.14 | 150.71 | 351.28 | 40.50 | 0.00 | 0.00 | 0.00 |
September | 237.28 | 112.54 | 124.74 | 287.52 | 83.04 | 0.00 | 0.00 | 0.00 |
October | 150.26 | 62.54 | 87.72 | 130.44 | 145.68 | 0.00 | 0.00 | 0.00 |
November | 88.88 | 28.85 | 60.03 | 44.17 | 238.17 | 0.00 | 0.00 | 0.00 |
December | 68.59 | 29.37 | 39.22 | 27.34 | 352.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.06 | 85.35 | 111.71 | 204.84 | 169.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.59 | 28.85 | 39.22 | 27.34 | 32.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.15 | 145.01 | 175.37 | 418.06 | 390.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.53 | 108.61 | 49.91 | 139.19 | 187.36 | 0.00 | 0.00 | 0.00 |
February | 170.89 | 115.94 | 54.95 | 156.41 | 149.71 | 0.00 | 0.00 | 0.00 |
March | 146.39 | 76.63 | 69.76 | 139.73 | 106.76 | 0.00 | 0.00 | 0.00 |
April | 130.51 | 59.81 | 70.70 | 141.41 | 75.74 | 0.00 | 0.00 | 0.00 |
May | 111.30 | 31.14 | 80.17 | 130.88 | 40.81 | 0.00 | 0.00 | 0.00 |
June | 106.25 | 21.22 | 85.03 | 141.54 | 23.40 | 0.00 | 0.00 | 0.00 |
July | 112.76 | 28.20 | 84.56 | 157.49 | 17.92 | 0.00 | 0.00 | 0.00 |
August | 124.95 | 43.27 | 81.68 | 175.23 | 22.92 | 0.00 | 0.00 | 0.00 |
September | 150.86 | 77.85 | 73.02 | 195.09 | 45.54 | 0.00 | 0.00 | 0.00 |
October | 162.58 | 102.50 | 60.08 | 181.57 | 76.85 | 0.00 | 0.00 | 0.00 |
November | 121.68 | 76.18 | 45.50 | 114.52 | 118.64 | 0.00 | 0.00 | 0.00 |
December | 129.57 | 98.12 | 31.44 | 122.70 | 172.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.32 | 69.70 | 65.62 | 149.61 | 86.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.25 | 21.22 | 31.44 | 114.52 | 17.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.89 | 115.94 | 85.03 | 195.09 | 187.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.41 | 0.00 | 25.41 | 0.06 | 227.80 | 0.00 | 0.00 | 0.00 |
February | 32.22 | 0.00 | 32.22 | 1.19 | 182.41 | 0.00 | 0.00 | 0.00 |
March | 48.29 | 0.00 | 48.29 | 14.03 | 116.68 | 0.00 | 0.00 | 0.00 |
April | 55.96 | 0.45 | 55.51 | 30.98 | 75.55 | 0.00 | 0.00 | 0.00 |
May | 72.77 | 2.76 | 70.01 | 65.72 | 38.22 | 0.00 | 0.00 | 0.00 |
June | 85.15 | 7.89 | 77.26 | 101.51 | 23.04 | 0.00 | 0.00 | 0.00 |
July | 79.87 | 5.51 | 74.36 | 99.38 | 18.74 | 0.00 | 0.00 | 0.00 |
August | 66.92 | 1.36 | 65.57 | 82.80 | 23.45 | 0.00 | 0.00 | 0.00 |
September | 51.21 | 0.05 | 51.16 | 49.77 | 46.98 | 0.00 | 0.00 | 0.00 |
October | 38.03 | 0.00 | 38.03 | 17.72 | 81.92 | 0.00 | 0.00 | 0.00 |
November | 26.60 | 0.00 | 26.60 | 4.32 | 135.46 | 0.00 | 0.00 | 0.00 |
December | 17.25 | 0.00 | 17.25 | 0.01 | 200.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.07 | 1.51 | 48.56 | 39.18 | 97.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.25 | 0.00 | 17.25 | 0.01 | 18.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.15 | 7.89 | 77.26 | 101.51 | 227.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.38 | 41.55 | 59.84 | 40.53 | 387.12 | 0.00 | 0.00 | 0.00 |
February | 135.00 | 59.42 | 75.58 | 73.69 | 304.95 | 0.00 | 0.00 | 0.00 |
March | 183.35 | 72.74 | 110.60 | 137.99 | 198.45 | 0.00 | 0.00 | 0.00 |
April | 223.78 | 97.53 | 126.25 | 217.65 | 135.16 | 0.00 | 0.00 | 0.00 |
May | 282.75 | 123.67 | 159.08 | 325.73 | 71.30 | 0.00 | 0.00 | 0.00 |
June | 310.73 | 135.37 | 175.37 | 399.49 | 43.64 | 0.00 | 0.00 | 0.00 |
July | 314.15 | 145.01 | 169.13 | 413.25 | 35.33 | 0.00 | 0.00 | 0.00 |
August | 264.85 | 114.14 | 150.71 | 348.96 | 43.64 | 0.00 | 0.00 | 0.00 |
September | 237.28 | 112.54 | 124.74 | 288.49 | 83.89 | 0.00 | 0.00 | 0.00 |
October | 150.26 | 62.54 | 87.72 | 134.84 | 142.81 | 0.00 | 0.00 | 0.00 |
November | 88.88 | 28.85 | 60.03 | 45.91 | 234.79 | 0.00 | 0.00 | 0.00 |
December | 68.59 | 29.37 | 39.22 | 28.07 | 348.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.06 | 85.35 | 111.71 | 205.26 | 168.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.59 | 28.85 | 39.22 | 28.07 | 35.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.15 | 145.01 | 175.37 | 413.25 | 387.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.18 | 0.00 | 32.18 | 0.02 | 306.65 | 0.00 | 0.00 | 0.00 |
February | 40.80 | 0.00 | 40.80 | 1.11 | 245.80 | 0.00 | 0.00 | 0.00 |
March | 61.15 | 0.00 | 61.15 | 17.27 | 155.16 | 0.00 | 0.00 | 0.00 |
April | 70.88 | 0.57 | 70.30 | 41.07 | 100.97 | 0.00 | 0.00 | 0.00 |
May | 92.15 | 3.49 | 88.66 | 88.32 | 51.38 | 0.00 | 0.00 | 0.00 |
June | 107.84 | 9.99 | 97.84 | 132.70 | 32.68 | 0.00 | 0.00 | 0.00 |
July | 101.15 | 6.98 | 94.17 | 129.61 | 27.39 | 0.00 | 0.00 | 0.00 |
August | 84.75 | 1.72 | 83.03 | 107.45 | 34.04 | 0.00 | 0.00 | 0.00 |
September | 64.86 | 0.06 | 64.80 | 64.70 | 65.33 | 0.00 | 0.00 | 0.00 |
October | 48.16 | 0.00 | 48.16 | 22.46 | 109.03 | 0.00 | 0.00 | 0.00 |
November | 33.69 | 0.00 | 33.69 | 4.98 | 183.21 | 0.00 | 0.00 | 0.00 |
December | 21.85 | 0.00 | 21.85 | 0.00 | 270.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.41 | 1.91 | 61.50 | 51.11 | 131.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.85 | 0.00 | 21.85 | 0.00 | 27.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.84 | 9.99 | 97.84 | 132.70 | 306.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.86 | 0.00 | 11.86 | 0.01 | 113.04 | 0.00 | 0.00 | 0.00 |
February | 15.04 | 0.00 | 15.04 | 0.41 | 90.61 | 0.00 | 0.00 | 0.00 |
March | 22.54 | 0.00 | 22.54 | 6.37 | 57.20 | 0.00 | 0.00 | 0.00 |
April | 26.13 | 0.21 | 25.92 | 15.14 | 37.22 | 0.00 | 0.00 | 0.00 |
May | 33.97 | 1.29 | 32.68 | 32.56 | 18.94 | 0.00 | 0.00 | 0.00 |
June | 39.75 | 3.68 | 36.07 | 48.92 | 12.05 | 0.00 | 0.00 | 0.00 |
July | 37.29 | 2.57 | 34.72 | 47.78 | 10.10 | 0.00 | 0.00 | 0.00 |
August | 31.24 | 0.63 | 30.61 | 39.61 | 12.55 | 0.00 | 0.00 | 0.00 |
September | 23.91 | 0.02 | 23.89 | 23.85 | 24.08 | 0.00 | 0.00 | 0.00 |
October | 17.75 | 0.00 | 17.75 | 8.28 | 40.19 | 0.00 | 0.00 | 0.00 |
November | 12.42 | 0.00 | 12.42 | 1.83 | 67.54 | 0.00 | 0.00 | 0.00 |
December | 8.06 | 0.00 | 8.06 | 0.00 | 99.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.37 | 0.70 | 22.67 | 18.84 | 48.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.06 | 0.00 | 8.06 | 0.00 | 10.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.75 | 3.68 | 36.07 | 48.92 | 113.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.97 | 50.68 | 23.29 | 64.05 | 91.52 | 0.00 | 0.00 | 0.00 |
February | 79.74 | 54.10 | 25.64 | 72.67 | 72.93 | 0.00 | 0.00 | 0.00 |
March | 68.30 | 35.76 | 32.55 | 65.85 | 51.73 | 0.00 | 0.00 | 0.00 |
April | 60.89 | 27.91 | 32.99 | 67.23 | 37.08 | 0.00 | 0.00 | 0.00 |
May | 51.93 | 14.53 | 37.41 | 62.73 | 20.47 | 0.00 | 0.00 | 0.00 |
June | 49.58 | 9.90 | 39.68 | 66.70 | 12.94 | 0.00 | 0.00 | 0.00 |
July | 52.61 | 13.16 | 39.45 | 73.76 | 10.69 | 0.00 | 0.00 | 0.00 |
August | 58.30 | 20.19 | 38.11 | 82.16 | 13.19 | 0.00 | 0.00 | 0.00 |
September | 70.39 | 36.32 | 34.07 | 91.84 | 23.65 | 0.00 | 0.00 | 0.00 |
October | 75.86 | 47.82 | 28.03 | 85.98 | 37.03 | 0.00 | 0.00 | 0.00 |
November | 56.78 | 35.55 | 21.23 | 53.24 | 58.11 | 0.00 | 0.00 | 0.00 |
December | 60.46 | 45.78 | 14.67 | 56.84 | 84.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.14 | 32.52 | 30.62 | 70.24 | 42.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.58 | 9.90 | 14.67 | 53.24 | 10.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.74 | 54.10 | 39.68 | 91.84 | 91.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 200.77 | 137.55 | 63.21 | 173.84 | 248.40 | 0.00 | 0.00 | 0.00 |
February | 216.43 | 146.83 | 69.59 | 197.25 | 197.95 | 0.00 | 0.00 | 0.00 |
March | 185.39 | 97.05 | 88.34 | 178.74 | 140.40 | 0.00 | 0.00 | 0.00 |
April | 165.28 | 75.75 | 89.53 | 182.47 | 100.65 | 0.00 | 0.00 | 0.00 |
May | 140.96 | 39.43 | 101.53 | 170.27 | 55.55 | 0.00 | 0.00 | 0.00 |
June | 134.56 | 26.87 | 107.69 | 181.05 | 35.13 | 0.00 | 0.00 | 0.00 |
July | 142.80 | 35.71 | 107.09 | 200.19 | 29.02 | 0.00 | 0.00 | 0.00 |
August | 158.24 | 54.80 | 103.44 | 222.99 | 35.79 | 0.00 | 0.00 | 0.00 |
September | 191.06 | 98.59 | 92.47 | 249.27 | 64.18 | 0.00 | 0.00 | 0.00 |
October | 205.89 | 129.81 | 76.09 | 233.35 | 100.50 | 0.00 | 0.00 | 0.00 |
November | 154.10 | 96.48 | 57.62 | 144.50 | 157.72 | 0.00 | 0.00 | 0.00 |
December | 164.09 | 124.27 | 39.82 | 154.27 | 230.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.38 | 88.27 | 83.10 | 190.64 | 115.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 134.56 | 26.87 | 39.82 | 144.50 | 29.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 216.43 | 146.83 | 107.69 | 249.27 | 248.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.53 | 108.61 | 49.91 | 138.88 | 187.55 | 0.00 | 0.00 | 0.00 |
February | 170.89 | 115.94 | 54.95 | 156.17 | 149.88 | 0.00 | 0.00 | 0.00 |
March | 146.39 | 76.63 | 69.76 | 140.35 | 106.84 | 0.00 | 0.00 | 0.00 |
April | 130.51 | 59.81 | 70.70 | 141.08 | 76.29 | 0.00 | 0.00 | 0.00 |
May | 111.30 | 31.14 | 80.17 | 130.88 | 40.80 | 0.00 | 0.00 | 0.00 |
June | 106.25 | 21.22 | 85.03 | 141.38 | 23.39 | 0.00 | 0.00 | 0.00 |
July | 112.76 | 28.20 | 84.56 | 157.01 | 18.07 | 0.00 | 0.00 | 0.00 |
August | 124.95 | 43.27 | 81.68 | 174.47 | 23.01 | 0.00 | 0.00 | 0.00 |
September | 150.86 | 77.85 | 73.02 | 195.17 | 45.24 | 0.00 | 0.00 | 0.00 |
October | 162.58 | 102.50 | 60.08 | 181.60 | 76.81 | 0.00 | 0.00 | 0.00 |
November | 121.68 | 76.18 | 45.50 | 114.41 | 118.56 | 0.00 | 0.00 | 0.00 |
December | 129.57 | 98.12 | 31.44 | 122.53 | 172.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.32 | 69.70 | 65.62 | 149.46 | 86.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.25 | 21.22 | 31.44 | 114.41 | 18.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.89 | 115.94 | 85.03 | 195.17 | 187.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.30 | 41.19 | 60.11 | 42.61 | 398.24 | 0.00 | 0.00 | 0.00 |
February | 147.85 | 72.79 | 75.06 | 90.83 | 316.62 | 0.00 | 0.00 | 0.00 |
March | 176.44 | 65.63 | 110.82 | 128.71 | 206.34 | 0.00 | 0.00 | 0.00 |
April | 258.03 | 127.69 | 130.34 | 263.31 | 138.70 | 0.00 | 0.00 | 0.00 |
May | 258.55 | 103.52 | 155.03 | 296.35 | 73.79 | 0.00 | 0.00 | 0.00 |
June | 302.46 | 130.78 | 171.68 | 391.31 | 43.01 | 0.00 | 0.00 | 0.00 |
July | 324.87 | 154.13 | 170.74 | 433.69 | 33.44 | 0.00 | 0.00 | 0.00 |
August | 283.65 | 129.80 | 153.85 | 377.71 | 42.61 | 0.00 | 0.00 | 0.00 |
September | 230.16 | 109.06 | 121.10 | 278.52 | 84.02 | 0.00 | 0.00 | 0.00 |
October | 161.34 | 72.08 | 89.26 | 148.77 | 149.61 | 0.00 | 0.00 | 0.00 |
November | 96.26 | 35.74 | 60.52 | 57.48 | 242.23 | 0.00 | 0.00 | 0.00 |
December | 74.10 | 35.06 | 39.03 | 38.03 | 357.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 201.47 | 89.81 | 111.66 | 212.89 | 173.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.10 | 35.06 | 39.03 | 38.03 | 33.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.87 | 154.13 | 171.68 | 433.69 | 398.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.41 | 0.00 | 25.41 | 0.08 | 228.13 | 0.00 | 0.00 | 0.00 |
February | 32.22 | 0.00 | 32.22 | 1.42 | 182.54 | 0.00 | 0.00 | 0.00 |
March | 48.29 | 0.00 | 48.29 | 14.78 | 116.25 | 0.00 | 0.00 | 0.00 |
April | 55.96 | 0.45 | 55.51 | 31.11 | 76.36 | 0.00 | 0.00 | 0.00 |
May | 72.77 | 2.76 | 70.01 | 65.60 | 38.83 | 0.00 | 0.00 | 0.00 |
June | 85.15 | 7.89 | 77.26 | 101.27 | 23.78 | 0.00 | 0.00 | 0.00 |
July | 79.87 | 5.51 | 74.36 | 99.33 | 19.89 | 0.00 | 0.00 | 0.00 |
August | 66.92 | 1.36 | 65.57 | 82.56 | 24.70 | 0.00 | 0.00 | 0.00 |
September | 51.21 | 0.05 | 51.16 | 50.81 | 47.21 | 0.00 | 0.00 | 0.00 |
October | 38.03 | 0.00 | 38.03 | 18.63 | 81.85 | 0.00 | 0.00 | 0.00 |
November | 26.60 | 0.00 | 26.60 | 4.61 | 135.08 | 0.00 | 0.00 | 0.00 |
December | 17.25 | 0.00 | 17.25 | 0.02 | 200.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.07 | 1.51 | 48.56 | 39.41 | 97.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.25 | 0.00 | 17.25 | 0.02 | 19.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.15 | 7.89 | 77.26 | 101.27 | 228.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.30 | 41.19 | 60.11 | 44.32 | 395.34 | 0.00 | 0.00 | 0.00 |
February | 147.85 | 72.79 | 75.06 | 94.07 | 312.63 | 0.00 | 0.00 | 0.00 |
March | 176.44 | 65.63 | 110.82 | 132.82 | 204.05 | 0.00 | 0.00 | 0.00 |
April | 258.03 | 127.69 | 130.34 | 265.67 | 138.38 | 0.00 | 0.00 | 0.00 |
May | 258.55 | 103.52 | 155.03 | 294.31 | 75.82 | 0.00 | 0.00 | 0.00 |
June | 302.46 | 130.78 | 171.68 | 386.95 | 46.52 | 0.00 | 0.00 | 0.00 |
July | 324.87 | 154.13 | 170.74 | 429.07 | 38.51 | 0.00 | 0.00 | 0.00 |
August | 283.65 | 129.80 | 153.85 | 374.90 | 47.57 | 0.00 | 0.00 | 0.00 |
September | 230.16 | 109.06 | 121.10 | 279.82 | 85.84 | 0.00 | 0.00 | 0.00 |
October | 161.34 | 72.08 | 89.26 | 153.78 | 147.28 | 0.00 | 0.00 | 0.00 |
November | 96.26 | 35.74 | 60.52 | 60.20 | 239.88 | 0.00 | 0.00 | 0.00 |
December | 74.10 | 35.06 | 39.03 | 40.15 | 355.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 201.47 | 89.81 | 111.66 | 213.60 | 173.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.10 | 35.06 | 39.03 | 40.15 | 38.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.87 | 154.13 | 171.68 | 429.07 | 395.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 232.50 | 159.29 | 73.20 | 196.50 | 282.60 | 0.00 | 0.00 | 0.00 |
February | 250.63 | 170.04 | 80.59 | 221.92 | 227.32 | 0.00 | 0.00 | 0.00 |
March | 214.69 | 112.39 | 102.31 | 200.41 | 161.03 | 0.00 | 0.00 | 0.00 |
April | 191.40 | 87.72 | 103.68 | 205.57 | 113.08 | 0.00 | 0.00 | 0.00 |
May | 163.24 | 45.66 | 117.58 | 192.47 | 59.43 | 0.00 | 0.00 | 0.00 |
June | 155.83 | 31.12 | 124.71 | 209.70 | 33.36 | 0.00 | 0.00 | 0.00 |
July | 165.37 | 41.36 | 124.01 | 233.29 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 183.25 | 63.46 | 119.79 | 257.72 | 32.61 | 0.00 | 0.00 | 0.00 |
September | 221.25 | 114.17 | 107.08 | 285.11 | 66.77 | 0.00 | 0.00 | 0.00 |
October | 238.43 | 150.32 | 88.11 | 261.62 | 116.21 | 0.00 | 0.00 | 0.00 |
November | 178.46 | 111.73 | 66.73 | 162.71 | 179.92 | 0.00 | 0.00 | 0.00 |
December | 190.02 | 143.91 | 46.11 | 173.98 | 260.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 198.46 | 102.22 | 96.24 | 216.72 | 129.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.83 | 31.12 | 46.11 | 162.71 | 24.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 250.63 | 170.04 | 124.71 | 285.11 | 282.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 177.87 | 0.00 | 177.87 | 0.09 | 1704.61 | 0.00 | 0.00 | 0.00 |
February | 225.50 | 0.00 | 225.50 | 5.35 | 1370.07 | 0.00 | 0.00 | 0.00 |
March | 338.00 | 0.00 | 338.00 | 88.57 | 890.95 | 0.00 | 0.00 | 0.00 |
April | 391.74 | 3.17 | 388.57 | 218.25 | 590.02 | 0.00 | 0.00 | 0.00 |
May | 509.34 | 19.30 | 490.04 | 472.63 | 303.55 | 0.00 | 0.00 | 0.00 |
June | 596.04 | 55.24 | 540.80 | 733.05 | 189.12 | 0.00 | 0.00 | 0.00 |
July | 559.06 | 38.56 | 520.50 | 726.86 | 151.05 | 0.00 | 0.00 | 0.00 |
August | 468.43 | 9.49 | 458.94 | 604.21 | 189.41 | 0.00 | 0.00 | 0.00 |
September | 358.46 | 0.33 | 358.13 | 363.76 | 367.75 | 0.00 | 0.00 | 0.00 |
October | 266.18 | 0.00 | 266.18 | 115.50 | 637.42 | 0.00 | 0.00 | 0.00 |
November | 186.19 | 0.00 | 186.19 | 24.48 | 1043.81 | 0.00 | 0.00 | 0.00 |
December | 120.78 | 0.00 | 120.78 | 0.00 | 1514.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 350.45 | 10.55 | 339.91 | 281.04 | 743.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.78 | 0.00 | 120.78 | 0.00 | 151.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 596.04 | 55.24 | 540.80 | 733.05 | 1704.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 177.87 | 0.00 | 177.87 | 0.04 | 1734.10 | 0.00 | 0.00 | 0.00 |
February | 225.50 | 0.00 | 225.50 | 4.40 | 1402.52 | 0.00 | 0.00 | 0.00 |
March | 338.00 | 0.00 | 338.00 | 82.08 | 919.85 | 0.00 | 0.00 | 0.00 |
April | 391.74 | 3.17 | 388.57 | 208.73 | 613.75 | 0.00 | 0.00 | 0.00 |
May | 509.34 | 19.30 | 490.04 | 458.53 | 315.19 | 0.00 | 0.00 | 0.00 |
June | 596.04 | 55.24 | 540.80 | 718.71 | 197.97 | 0.00 | 0.00 | 0.00 |
July | 559.06 | 38.56 | 520.50 | 712.89 | 158.98 | 0.00 | 0.00 | 0.00 |
August | 468.43 | 9.49 | 458.94 | 591.36 | 198.66 | 0.00 | 0.00 | 0.00 |
September | 358.46 | 0.33 | 358.13 | 353.43 | 382.57 | 0.00 | 0.00 | 0.00 |
October | 266.18 | 0.00 | 266.18 | 106.68 | 662.99 | 0.00 | 0.00 | 0.00 |
November | 186.19 | 0.00 | 186.19 | 21.75 | 1074.33 | 0.00 | 0.00 | 0.00 |
December | 120.78 | 0.00 | 120.78 | 0.00 | 1545.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 350.45 | 10.55 | 339.91 | 273.15 | 764.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.78 | 0.00 | 120.78 | 0.00 | 158.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 596.04 | 55.24 | 540.80 | 718.71 | 1734.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.41 | 0.00 | 25.41 | 0.12 | 231.75 | 0.00 | 0.00 | 0.00 |
February | 32.22 | 0.00 | 32.22 | 1.79 | 186.69 | 0.00 | 0.00 | 0.00 |
March | 48.29 | 0.00 | 48.29 | 18.23 | 120.47 | 0.00 | 0.00 | 0.00 |
April | 55.96 | 0.45 | 55.51 | 42.08 | 78.90 | 0.00 | 0.00 | 0.00 |
May | 72.77 | 2.76 | 70.01 | 88.35 | 42.25 | 0.00 | 0.00 | 0.00 |
June | 85.15 | 7.89 | 77.26 | 129.30 | 26.84 | 0.00 | 0.00 | 0.00 |
July | 79.87 | 5.51 | 74.36 | 129.63 | 21.33 | 0.00 | 0.00 | 0.00 |
August | 66.92 | 1.36 | 65.57 | 110.19 | 25.98 | 0.00 | 0.00 | 0.00 |
September | 51.21 | 0.05 | 51.16 | 69.30 | 48.32 | 0.00 | 0.00 | 0.00 |
October | 38.03 | 0.00 | 38.03 | 25.40 | 83.62 | 0.00 | 0.00 | 0.00 |
November | 26.60 | 0.00 | 26.60 | 6.97 | 138.26 | 0.00 | 0.00 | 0.00 |
December | 17.25 | 0.00 | 17.25 | 0.04 | 203.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.07 | 1.51 | 48.56 | 52.08 | 100.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.25 | 0.00 | 17.25 | 0.04 | 21.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.15 | 7.89 | 77.26 | 129.63 | 231.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 202.75 | 83.09 | 119.66 | 85.34 | 791.05 | 0.00 | 0.00 | 0.00 |
February | 269.98 | 118.83 | 151.15 | 154.93 | 626.42 | 0.00 | 0.00 | 0.00 |
March | 366.67 | 145.48 | 221.19 | 299.10 | 415.13 | 0.00 | 0.00 | 0.00 |
April | 447.53 | 195.05 | 252.48 | 481.29 | 286.29 | 0.00 | 0.00 | 0.00 |
May | 565.46 | 247.32 | 318.15 | 735.43 | 156.73 | 0.00 | 0.00 | 0.00 |
June | 621.42 | 270.71 | 350.71 | 901.63 | 100.54 | 0.00 | 0.00 | 0.00 |
July | 628.25 | 290.01 | 338.24 | 939.35 | 79.81 | 0.00 | 0.00 | 0.00 |
August | 529.66 | 228.26 | 301.40 | 800.43 | 97.03 | 0.00 | 0.00 | 0.00 |
September | 474.53 | 225.06 | 249.47 | 655.09 | 175.78 | 0.00 | 0.00 | 0.00 |
October | 300.50 | 125.08 | 175.42 | 306.49 | 296.00 | 0.00 | 0.00 | 0.00 |
November | 177.75 | 57.69 | 120.06 | 105.35 | 484.08 | 0.00 | 0.00 | 0.00 |
December | 137.17 | 58.73 | 78.44 | 59.98 | 711.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 394.08 | 170.68 | 223.40 | 462.05 | 350.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.17 | 57.69 | 78.44 | 59.98 | 79.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 628.25 | 290.01 | 350.71 | 939.35 | 791.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.53 | 108.61 | 49.91 | 142.48 | 190.64 | 0.00 | 0.00 | 0.00 |
February | 170.89 | 115.94 | 54.95 | 161.93 | 153.20 | 0.00 | 0.00 | 0.00 |
March | 146.39 | 76.63 | 69.76 | 148.97 | 110.71 | 0.00 | 0.00 | 0.00 |
April | 130.51 | 59.81 | 70.70 | 154.98 | 78.81 | 0.00 | 0.00 | 0.00 |
May | 111.30 | 31.14 | 80.17 | 152.71 | 44.52 | 0.00 | 0.00 | 0.00 |
June | 106.25 | 21.22 | 85.03 | 166.90 | 28.19 | 0.00 | 0.00 | 0.00 |
July | 112.76 | 28.20 | 84.56 | 184.94 | 22.03 | 0.00 | 0.00 | 0.00 |
August | 124.95 | 43.27 | 81.68 | 200.85 | 26.77 | 0.00 | 0.00 | 0.00 |
September | 150.86 | 77.85 | 73.02 | 216.26 | 47.82 | 0.00 | 0.00 | 0.00 |
October | 162.58 | 102.50 | 60.08 | 195.54 | 79.34 | 0.00 | 0.00 | 0.00 |
November | 121.68 | 76.18 | 45.50 | 120.93 | 121.95 | 0.00 | 0.00 | 0.00 |
December | 129.57 | 98.12 | 31.44 | 126.52 | 175.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.32 | 69.70 | 65.62 | 164.43 | 89.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.25 | 21.22 | 31.44 | 120.93 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.89 | 115.94 | 85.03 | 216.26 | 190.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.18 | 0.00 | 32.18 | 0.01 | 309.53 | 0.00 | 0.00 | 0.00 |
February | 40.80 | 0.00 | 40.80 | 0.85 | 247.85 | 0.00 | 0.00 | 0.00 |
March | 61.15 | 0.00 | 61.15 | 15.41 | 159.16 | 0.00 | 0.00 | 0.00 |
April | 70.88 | 0.57 | 70.30 | 36.74 | 106.75 | 0.00 | 0.00 | 0.00 |
May | 92.15 | 3.49 | 88.66 | 78.90 | 58.34 | 0.00 | 0.00 | 0.00 |
June | 107.84 | 9.99 | 97.84 | 124.58 | 37.23 | 0.00 | 0.00 | 0.00 |
July | 101.15 | 6.98 | 94.17 | 122.69 | 30.70 | 0.00 | 0.00 | 0.00 |
August | 84.75 | 1.72 | 83.03 | 100.66 | 38.39 | 0.00 | 0.00 | 0.00 |
September | 64.86 | 0.06 | 64.80 | 59.52 | 71.06 | 0.00 | 0.00 | 0.00 |
October | 48.16 | 0.00 | 48.16 | 18.92 | 115.91 | 0.00 | 0.00 | 0.00 |
November | 33.69 | 0.00 | 33.69 | 3.95 | 187.97 | 0.00 | 0.00 | 0.00 |
December | 21.85 | 0.00 | 21.85 | 0.00 | 273.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.41 | 1.91 | 61.50 | 47.13 | 135.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.85 | 0.00 | 21.85 | 0.00 | 30.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.84 | 9.99 | 97.84 | 124.58 | 309.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.79 | 0.00 | 28.79 | 0.00 | 276.92 | 0.00 | 0.00 | 0.00 |
February | 36.50 | 0.00 | 36.50 | 0.76 | 221.75 | 0.00 | 0.00 | 0.00 |
March | 54.71 | 0.00 | 54.71 | 13.79 | 142.41 | 0.00 | 0.00 | 0.00 |
April | 63.41 | 0.51 | 62.90 | 32.87 | 95.51 | 0.00 | 0.00 | 0.00 |
May | 82.45 | 3.12 | 79.33 | 70.59 | 52.20 | 0.00 | 0.00 | 0.00 |
June | 96.48 | 8.94 | 87.54 | 111.47 | 33.31 | 0.00 | 0.00 | 0.00 |
July | 90.50 | 6.24 | 84.26 | 109.77 | 27.47 | 0.00 | 0.00 | 0.00 |
August | 75.83 | 1.54 | 74.29 | 90.06 | 34.35 | 0.00 | 0.00 | 0.00 |
September | 58.03 | 0.05 | 57.97 | 53.25 | 63.58 | 0.00 | 0.00 | 0.00 |
October | 43.09 | 0.00 | 43.09 | 16.93 | 103.71 | 0.00 | 0.00 | 0.00 |
November | 30.14 | 0.00 | 30.14 | 3.53 | 168.17 | 0.00 | 0.00 | 0.00 |
December | 19.55 | 0.00 | 19.55 | 0.00 | 244.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.73 | 1.71 | 55.02 | 42.16 | 121.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.55 | 0.00 | 19.55 | 0.00 | 27.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.48 | 8.94 | 87.54 | 111.47 | 276.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 591.83 | 405.49 | 186.34 | 506.57 | 736.99 | 0.00 | 0.00 | 0.00 |
February | 638.00 | 432.85 | 205.15 | 574.98 | 586.43 | 0.00 | 0.00 | 0.00 |
March | 546.51 | 286.08 | 260.43 | 516.32 | 423.64 | 0.00 | 0.00 | 0.00 |
April | 487.22 | 223.29 | 263.93 | 522.33 | 313.36 | 0.00 | 0.00 | 0.00 |
May | 415.53 | 116.24 | 299.29 | 474.61 | 186.47 | 0.00 | 0.00 | 0.00 |
June | 396.68 | 79.22 | 317.46 | 510.41 | 118.62 | 0.00 | 0.00 | 0.00 |
July | 420.96 | 105.28 | 315.68 | 569.62 | 96.48 | 0.00 | 0.00 | 0.00 |
August | 466.48 | 161.54 | 304.94 | 636.12 | 119.45 | 0.00 | 0.00 | 0.00 |
September | 563.21 | 290.63 | 272.59 | 716.25 | 205.61 | 0.00 | 0.00 | 0.00 |
October | 606.95 | 382.65 | 224.29 | 671.12 | 313.80 | 0.00 | 0.00 | 0.00 |
November | 454.27 | 284.42 | 169.86 | 417.26 | 476.64 | 0.00 | 0.00 | 0.00 |
December | 483.71 | 366.33 | 117.38 | 449.94 | 684.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.20 | 260.21 | 244.98 | 546.96 | 354.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 396.68 | 79.22 | 117.38 | 417.26 | 96.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 638.00 | 432.85 | 317.46 | 716.25 | 736.99 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214752E+10 | 0.147136E+10 | 0.676156E+09 | 0.188028E+10 | 0.246222E+10 |
February | 0.209099E+10 | 0.141863E+10 | 0.672359E+09 | 0.191422E+10 | 0.178409E+10 |
March | 0.198306E+10 | 0.103808E+10 | 0.944974E+09 | 0.190170E+10 | 0.141895E+10 |
April | 0.171089E+10 | 0.784093E+09 | 0.926799E+09 | 0.184871E+10 | 0.100742E+10 |
May | 0.150779E+10 | 0.421788E+09 | 0.108600E+10 | 0.176477E+10 | 0.599988E+09 |
June | 0.139293E+10 | 0.278174E+09 | 0.111476E+10 | 0.180845E+10 | 0.379174E+09 |
July | 0.152747E+10 | 0.382015E+09 | 0.114546E+10 | 0.206934E+10 | 0.335735E+09 |
August | 0.169265E+10 | 0.586171E+09 | 0.110648E+10 | 0.231518E+10 | 0.410093E+09 |
September | 0.197774E+10 | 0.102054E+10 | 0.957200E+09 | 0.252321E+10 | 0.672931E+09 |
October | 0.220236E+10 | 0.138850E+10 | 0.813863E+09 | 0.244369E+10 | 0.107018E+10 |
November | 0.159520E+10 | 0.998741E+09 | 0.596460E+09 | 0.149012E+10 | 0.153386E+10 |
December | 0.175518E+10 | 0.132925E+10 | 0.425930E+09 | 0.164625E+10 | 0.229049E+10 |
Annual Sum or Average | 0.215838E+11 | 0.111173E+11 | 0.104664E+11 | 0.236059E+11 | 0.139651E+11 |
Minimum of Months | 0.139293E+10 | 0.278174E+09 | 0.425930E+09 | 0.149012E+10 | 0.335735E+09 |
Maximum of Months | 0.220236E+10 | 0.147136E+10 | 0.114546E+10 | 0.252321E+10 | 0.246222E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.604728E+10 | 0.414326E+10 | 0.190401E+10 | 0.527564E+10 | 0.695911E+10 |
February | 0.588809E+10 | 0.399478E+10 | 0.189332E+10 | 0.537270E+10 | 0.506250E+10 |
March | 0.558415E+10 | 0.292317E+10 | 0.266098E+10 | 0.534888E+10 | 0.402401E+10 |
April | 0.481776E+10 | 0.220795E+10 | 0.260981E+10 | 0.522628E+10 | 0.283834E+10 |
May | 0.424584E+10 | 0.118773E+10 | 0.305812E+10 | 0.507157E+10 | 0.162661E+10 |
June | 0.392240E+10 | 0.783319E+09 | 0.313908E+10 | 0.523147E+10 | 0.990402E+09 |
July | 0.430126E+10 | 0.107573E+10 | 0.322553E+10 | 0.599152E+10 | 0.839772E+09 |
August | 0.476640E+10 | 0.165062E+10 | 0.311578E+10 | 0.665213E+10 | 0.105069E+10 |
September | 0.556919E+10 | 0.287378E+10 | 0.269541E+10 | 0.715391E+10 | 0.183387E+10 |
October | 0.620170E+10 | 0.390991E+10 | 0.229179E+10 | 0.688434E+10 | 0.302484E+10 |
November | 0.449198E+10 | 0.281239E+10 | 0.167959E+10 | 0.418076E+10 | 0.435731E+10 |
December | 0.494247E+10 | 0.374308E+10 | 0.119939E+10 | 0.462644E+10 | 0.647676E+10 |
Annual Sum or Average | 0.607785E+11 | 0.313057E+11 | 0.294728E+11 | 0.670156E+11 | 0.390842E+11 |
Minimum of Months | 0.392240E+10 | 0.783319E+09 | 0.119939E+10 | 0.418076E+10 | 0.839772E+09 |
Maximum of Months | 0.620170E+10 | 0.414326E+10 | 0.322553E+10 | 0.715391E+10 | 0.695911E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.785576E+10 | 0.538234E+10 | 0.247342E+10 | 0.693253E+10 | 0.939487E+10 |
February | 0.764897E+10 | 0.518944E+10 | 0.245953E+10 | 0.707430E+10 | 0.685659E+10 |
March | 0.725413E+10 | 0.379736E+10 | 0.345677E+10 | 0.704365E+10 | 0.551689E+10 |
April | 0.625854E+10 | 0.286826E+10 | 0.339029E+10 | 0.689008E+10 | 0.392953E+10 |
May | 0.551559E+10 | 0.154292E+10 | 0.397267E+10 | 0.662793E+10 | 0.230055E+10 |
June | 0.509542E+10 | 0.101758E+10 | 0.407784E+10 | 0.683982E+10 | 0.142011E+10 |
July | 0.558759E+10 | 0.139743E+10 | 0.419015E+10 | 0.784380E+10 | 0.120411E+10 |
August | 0.619182E+10 | 0.214425E+10 | 0.404758E+10 | 0.873039E+10 | 0.148593E+10 |
September | 0.723470E+10 | 0.373320E+10 | 0.350149E+10 | 0.940984E+10 | 0.255753E+10 |
October | 0.805636E+10 | 0.507920E+10 | 0.297716E+10 | 0.904989E+10 | 0.417888E+10 |
November | 0.583534E+10 | 0.365345E+10 | 0.218188E+10 | 0.547966E+10 | 0.598101E+10 |
December | 0.642055E+10 | 0.486248E+10 | 0.155808E+10 | 0.608469E+10 | 0.879513E+10 |
Annual Sum or Average | 0.789548E+11 | 0.406679E+11 | 0.382869E+11 | 0.880066E+11 | 0.536211E+11 |
Minimum of Months | 0.509542E+10 | 0.101758E+10 | 0.155808E+10 | 0.547966E+10 | 0.120411E+10 |
Maximum of Months | 0.805636E+10 | 0.538234E+10 | 0.419015E+10 | 0.940984E+10 | 0.939487E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.424602E+09 | 0.290914E+09 | 0.133688E+09 | 0.373425E+09 | 0.502369E+09 |
February | 0.413426E+09 | 0.280488E+09 | 0.132938E+09 | 0.379138E+09 | 0.363610E+09 |
March | 0.392085E+09 | 0.205247E+09 | 0.186839E+09 | 0.377174E+09 | 0.286731E+09 |
April | 0.338274E+09 | 0.155029E+09 | 0.183246E+09 | 0.367872E+09 | 0.198580E+09 |
May | 0.298118E+09 | 83394652.06 | 0.214724E+09 | 0.353592E+09 | 0.109792E+09 |
June | 0.275408E+09 | 54999709.10 | 0.220409E+09 | 0.368955E+09 | 61580966.44 |
July | 0.302010E+09 | 75530941.52 | 0.226479E+09 | 0.423260E+09 | 49472384.85 |
August | 0.334669E+09 | 0.115896E+09 | 0.218773E+09 | 0.470220E+09 | 62588206.71 |
September | 0.391035E+09 | 0.201779E+09 | 0.189256E+09 | 0.507905E+09 | 0.118935E+09 |
October | 0.435445E+09 | 0.274529E+09 | 0.160916E+09 | 0.488090E+09 | 0.206855E+09 |
November | 0.315399E+09 | 0.197468E+09 | 0.117931E+09 | 0.297162E+09 | 0.308209E+09 |
December | 0.347030E+09 | 0.262816E+09 | 84214117.22 | 0.328738E+09 | 0.463620E+09 |
Annual Sum or Average | 0.426750E+10 | 0.219809E+10 | 0.206941E+10 | 0.473553E+10 | 0.273234E+10 |
Minimum of Months | 0.275408E+09 | 54999709.10 | 84214117.22 | 0.297162E+09 | 49472384.85 |
Maximum of Months | 0.435445E+09 | 0.290914E+09 | 0.226479E+09 | 0.507905E+09 | 0.502369E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271326E+09 | 0.110333E+09 | 0.160993E+09 | 0.114718E+09 | 0.106530E+10 |
February | 0.357678E+09 | 0.176094E+09 | 0.181584E+09 | 0.221097E+09 | 0.766568E+09 |
March | 0.472590E+09 | 0.175770E+09 | 0.296820E+09 | 0.346200E+09 | 0.553773E+09 |
April | 0.668813E+09 | 0.330967E+09 | 0.337846E+09 | 0.687054E+09 | 0.361266E+09 |
May | 0.692500E+09 | 0.277264E+09 | 0.415236E+09 | 0.799685E+09 | 0.198843E+09 |
June | 0.783985E+09 | 0.338994E+09 | 0.444992E+09 | 0.102002E+10 | 0.113312E+09 |
July | 0.870129E+09 | 0.412810E+09 | 0.457318E+09 | 0.116793E+10 | 91617091.80 |
August | 0.759725E+09 | 0.347643E+09 | 0.412081E+09 | 0.101738E+10 | 0.116004E+09 |
September | 0.596579E+09 | 0.282690E+09 | 0.313889E+09 | 0.724724E+09 | 0.220957E+09 |
October | 0.432136E+09 | 0.193056E+09 | 0.239080E+09 | 0.400297E+09 | 0.403220E+09 |
November | 0.249513E+09 | 92645012.94 | 0.156868E+09 | 0.148713E+09 | 0.630101E+09 |
December | 0.198462E+09 | 93913323.71 | 0.104548E+09 | 0.101769E+09 | 0.958929E+09 |
Annual Sum or Average | 0.635344E+10 | 0.283218E+10 | 0.352126E+10 | 0.674958E+10 | 0.547989E+10 |
Minimum of Months | 0.198462E+09 | 92645012.94 | 0.104548E+09 | 0.101769E+09 | 91617091.80 |
Maximum of Months | 0.870129E+09 | 0.412810E+09 | 0.457318E+09 | 0.116793E+10 | 0.106530E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68058948.78 | 0.00 | 68058948.78 | 191539.63 | 0.610285E+09 |
February | 77935286.52 | 0.00 | 77935286.52 | 3334447.54 | 0.442418E+09 |
March | 0.129333E+09 | 1148.49 | 0.129332E+09 | 39123504.68 | 0.312090E+09 |
April | 0.145061E+09 | 1173225.39 | 0.143888E+09 | 81216907.58 | 0.198350E+09 |
May | 0.194895E+09 | 7383292.77 | 0.187512E+09 | 0.178447E+09 | 0.103555E+09 |
June | 0.220713E+09 | 20456194.03 | 0.200256E+09 | 0.265256E+09 | 61341357.57 |
July | 0.213921E+09 | 14756037.25 | 0.199165E+09 | 0.268510E+09 | 52845370.24 |
August | 0.179240E+09 | 3629607.62 | 0.175611E+09 | 0.222922E+09 | 65504396.66 |
September | 0.132739E+09 | 121560.20 | 0.132617E+09 | 0.131714E+09 | 0.123456E+09 |
October | 0.101851E+09 | 0.00 | 0.101851E+09 | 49016881.78 | 0.220968E+09 |
November | 68947352.64 | 0.00 | 68947352.64 | 11509160.51 | 0.351777E+09 |
December | 46214217.21 | 0.00 | 46214217.21 | 35018.33 | 0.536134E+09 |
Annual Sum or Average | 0.157891E+10 | 47521065.74 | 0.153139E+10 | 0.125128E+10 | 0.307872E+10 |
Minimum of Months | 46214217.21 | 0.00 | 46214217.21 | 35018.33 | 52845370.24 |
Maximum of Months | 0.220713E+09 | 20456194.03 | 0.200256E+09 | 0.268510E+09 | 0.610285E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271326E+09 | 0.110333E+09 | 0.160993E+09 | 0.119683E+09 | 0.105767E+10 |
February | 0.357678E+09 | 0.176094E+09 | 0.181584E+09 | 0.228819E+09 | 0.757026E+09 |
March | 0.472590E+09 | 0.175770E+09 | 0.296820E+09 | 0.356705E+09 | 0.547538E+09 |
April | 0.668813E+09 | 0.330967E+09 | 0.337846E+09 | 0.692843E+09 | 0.360127E+09 |
May | 0.692500E+09 | 0.277264E+09 | 0.415236E+09 | 0.795663E+09 | 0.202763E+09 |
June | 0.783985E+09 | 0.338994E+09 | 0.444992E+09 | 0.101029E+10 | 0.120291E+09 |
July | 0.870129E+09 | 0.412810E+09 | 0.457318E+09 | 0.115675E+10 | 0.102594E+09 |
August | 0.759725E+09 | 0.347643E+09 | 0.412081E+09 | 0.101078E+10 | 0.126619E+09 |
September | 0.596579E+09 | 0.282690E+09 | 0.313889E+09 | 0.727869E+09 | 0.224710E+09 |
October | 0.432136E+09 | 0.193056E+09 | 0.239080E+09 | 0.412291E+09 | 0.397462E+09 |
November | 0.249513E+09 | 92645012.94 | 0.156868E+09 | 0.155501E+09 | 0.623904E+09 |
December | 0.198462E+09 | 93913323.71 | 0.104548E+09 | 0.107653E+09 | 0.951413E+09 |
Annual Sum or Average | 0.635344E+10 | 0.283218E+10 | 0.352126E+10 | 0.677485E+10 | 0.547212E+10 |
Minimum of Months | 0.198462E+09 | 92645012.94 | 0.104548E+09 | 0.107653E+09 | 0.102594E+09 |
Maximum of Months | 0.870129E+09 | 0.412810E+09 | 0.457318E+09 | 0.115675E+10 | 0.105767E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.339614E+09 | 0.232685E+09 | 0.106929E+09 | 0.307004E+09 | 0.356490E+09 |
February | 0.330675E+09 | 0.224346E+09 | 0.106329E+09 | 0.304747E+09 | 0.284051E+09 |
March | 0.313606E+09 | 0.164165E+09 | 0.149441E+09 | 0.292621E+09 | 0.241040E+09 |
April | 0.270566E+09 | 0.123998E+09 | 0.146568E+09 | 0.275555E+09 | 0.206639E+09 |
May | 0.238447E+09 | 66702456.33 | 0.171745E+09 | 0.251051E+09 | 0.134481E+09 |
June | 0.220283E+09 | 43991018.65 | 0.176292E+09 | 0.262460E+09 | 87932872.77 |
July | 0.241560E+09 | 60412738.75 | 0.181147E+09 | 0.305084E+09 | 76149927.23 |
August | 0.267682E+09 | 92698360.87 | 0.174983E+09 | 0.344373E+09 | 91509321.99 |
September | 0.312766E+09 | 0.161391E+09 | 0.151375E+09 | 0.378518E+09 | 0.144540E+09 |
October | 0.348287E+09 | 0.219580E+09 | 0.128707E+09 | 0.360208E+09 | 0.225096E+09 |
November | 0.252269E+09 | 0.157943E+09 | 94326015.77 | 0.224007E+09 | 0.275047E+09 |
December | 0.277569E+09 | 0.210211E+09 | 67357898.11 | 0.266570E+09 | 0.336083E+09 |
Annual Sum or Average | 0.341332E+10 | 0.175812E+10 | 0.165520E+10 | 0.357220E+10 | 0.245906E+10 |
Minimum of Months | 0.220283E+09 | 43991018.65 | 67357898.11 | 0.224007E+09 | 76149927.23 |
Maximum of Months | 0.348287E+09 | 0.232685E+09 | 0.181147E+09 | 0.378518E+09 | 0.356490E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54454376.31 | 0.00 | 54454376.31 | 82228.05 | 0.502783E+09 |
February | 62356493.82 | 0.00 | 62356493.82 | 2139097.70 | 0.362905E+09 |
March | 0.103480E+09 | 918.91 | 0.103479E+09 | 30280663.88 | 0.256880E+09 |
April | 0.116064E+09 | 938704.73 | 0.115125E+09 | 68308240.65 | 0.160337E+09 |
May | 0.155937E+09 | 5907417.17 | 0.150030E+09 | 0.150540E+09 | 81160566.09 |
June | 0.176594E+09 | 16367124.49 | 0.160226E+09 | 0.222358E+09 | 46282748.67 |
July | 0.171159E+09 | 11806394.60 | 0.159353E+09 | 0.226901E+09 | 37540288.44 |
August | 0.143411E+09 | 2904070.99 | 0.140507E+09 | 0.189061E+09 | 47949709.85 |
September | 0.106205E+09 | 97261.05 | 0.106108E+09 | 0.110948E+09 | 96237938.35 |
October | 81491445.51 | 0.00 | 81491445.51 | 38793910.66 | 0.180317E+09 |
November | 55165193.61 | 0.00 | 55165193.61 | 8406295.31 | 0.292431E+09 |
December | 36976274.53 | 0.00 | 36976274.53 | 4936.49 | 0.444465E+09 |
Annual Sum or Average | 0.126329E+10 | 38021891.94 | 0.122527E+10 | 0.104782E+10 | 0.250929E+10 |
Minimum of Months | 36976274.53 | 0.00 | 36976274.53 | 4936.49 | 37540288.44 |
Maximum of Months | 0.176594E+09 | 16367124.49 | 0.160226E+09 | 0.226901E+09 | 0.502783E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271544E+09 | 0.111280E+09 | 0.160264E+09 | 0.105886E+09 | 0.104707E+10 |
February | 0.326586E+09 | 0.143741E+09 | 0.182845E+09 | 0.173422E+09 | 0.750400E+09 |
March | 0.491084E+09 | 0.194840E+09 | 0.296244E+09 | 0.360600E+09 | 0.539579E+09 |
April | 0.580037E+09 | 0.252801E+09 | 0.327237E+09 | 0.558106E+09 | 0.352833E+09 |
May | 0.757321E+09 | 0.331230E+09 | 0.426091E+09 | 0.873928E+09 | 0.187914E+09 |
June | 0.805421E+09 | 0.350867E+09 | 0.454555E+09 | 0.104492E+10 | 0.107266E+09 |
July | 0.841411E+09 | 0.388405E+09 | 0.453006E+09 | 0.111974E+10 | 85760271.27 |
August | 0.709372E+09 | 0.305712E+09 | 0.403660E+09 | 0.940867E+09 | 0.108466E+09 |
September | 0.615030E+09 | 0.291696E+09 | 0.323334E+09 | 0.745265E+09 | 0.215245E+09 |
October | 0.402457E+09 | 0.167516E+09 | 0.234941E+09 | 0.349367E+09 | 0.390181E+09 |
November | 0.230378E+09 | 74769286.73 | 0.155608E+09 | 0.114495E+09 | 0.617328E+09 |
December | 0.183715E+09 | 78658898.99 | 0.105056E+09 | 73232740.16 | 0.943564E+09 |
Annual Sum or Average | 0.621436E+10 | 0.269152E+10 | 0.352284E+10 | 0.645983E+10 | 0.534561E+10 |
Minimum of Months | 0.183715E+09 | 74769286.73 | 0.105056E+09 | 73232740.16 | 85760271.27 |
Maximum of Months | 0.841411E+09 | 0.388405E+09 | 0.454555E+09 | 0.111974E+10 | 0.104707E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.424602E+09 | 0.290914E+09 | 0.133688E+09 | 0.372813E+09 | 0.501813E+09 |
February | 0.413426E+09 | 0.280488E+09 | 0.132938E+09 | 0.378396E+09 | 0.362172E+09 |
March | 0.392085E+09 | 0.205247E+09 | 0.186839E+09 | 0.374251E+09 | 0.285943E+09 |
April | 0.338274E+09 | 0.155029E+09 | 0.183246E+09 | 0.366528E+09 | 0.196318E+09 |
May | 0.298118E+09 | 83394652.06 | 0.214724E+09 | 0.350542E+09 | 0.109307E+09 |
June | 0.275408E+09 | 54999709.10 | 0.220409E+09 | 0.366862E+09 | 60659595.78 |
July | 0.302010E+09 | 75530941.52 | 0.226479E+09 | 0.421828E+09 | 48001130.58 |
August | 0.334669E+09 | 0.115896E+09 | 0.218773E+09 | 0.469325E+09 | 61391997.81 |
September | 0.391035E+09 | 0.201779E+09 | 0.189256E+09 | 0.505663E+09 | 0.118031E+09 |
October | 0.435445E+09 | 0.274529E+09 | 0.160916E+09 | 0.486311E+09 | 0.205846E+09 |
November | 0.315399E+09 | 0.197468E+09 | 0.117931E+09 | 0.296838E+09 | 0.307510E+09 |
December | 0.347030E+09 | 0.262816E+09 | 84214117.22 | 0.328653E+09 | 0.463010E+09 |
Annual Sum or Average | 0.426750E+10 | 0.219809E+10 | 0.206941E+10 | 0.471801E+10 | 0.272000E+10 |
Minimum of Months | 0.275408E+09 | 54999709.10 | 84214117.22 | 0.296838E+09 | 48001130.58 |
Maximum of Months | 0.435445E+09 | 0.290914E+09 | 0.226479E+09 | 0.505663E+09 | 0.501813E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68058948.78 | 0.00 | 68058948.78 | 149043.02 | 0.610133E+09 |
February | 77935286.52 | 0.00 | 77935286.52 | 2882052.77 | 0.441285E+09 |
March | 0.129333E+09 | 1148.49 | 0.129332E+09 | 37566403.26 | 0.312513E+09 |
April | 0.145061E+09 | 1173225.39 | 0.143888E+09 | 80291381.92 | 0.195835E+09 |
May | 0.194895E+09 | 7383292.77 | 0.187512E+09 | 0.176023E+09 | 0.102363E+09 |
June | 0.220713E+09 | 20456194.03 | 0.200256E+09 | 0.263107E+09 | 59706991.18 |
July | 0.213921E+09 | 14756037.25 | 0.199165E+09 | 0.266183E+09 | 50192884.15 |
August | 0.179240E+09 | 3629607.62 | 0.175611E+09 | 0.221781E+09 | 62809518.11 |
September | 0.132739E+09 | 121560.20 | 0.132617E+09 | 0.128996E+09 | 0.121767E+09 |
October | 0.101851E+09 | 0.00 | 0.101851E+09 | 47454887.59 | 0.219409E+09 |
November | 68947352.64 | 0.00 | 68947352.64 | 11208914.04 | 0.351108E+09 |
December | 46214217.21 | 0.00 | 46214217.21 | 20723.68 | 0.536151E+09 |
Annual Sum or Average | 0.157891E+10 | 47521065.74 | 0.153139E+10 | 0.123566E+10 | 0.306327E+10 |
Minimum of Months | 46214217.21 | 0.00 | 46214217.21 | 20723.68 | 50192884.15 |
Maximum of Months | 0.220713E+09 | 20456194.03 | 0.200256E+09 | 0.266183E+09 | 0.610133E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271544E+09 | 0.111280E+09 | 0.160264E+09 | 0.108548E+09 | 0.103687E+10 |
February | 0.326586E+09 | 0.143741E+09 | 0.182845E+09 | 0.178261E+09 | 0.737741E+09 |
March | 0.491084E+09 | 0.194840E+09 | 0.296244E+09 | 0.369595E+09 | 0.531521E+09 |
April | 0.580037E+09 | 0.252801E+09 | 0.327237E+09 | 0.564138E+09 | 0.350341E+09 |
May | 0.757321E+09 | 0.331230E+09 | 0.426091E+09 | 0.872429E+09 | 0.190961E+09 |
June | 0.805421E+09 | 0.350867E+09 | 0.454555E+09 | 0.103548E+10 | 0.113112E+09 |
July | 0.841411E+09 | 0.388405E+09 | 0.453006E+09 | 0.110685E+10 | 94626708.25 |
August | 0.709372E+09 | 0.305712E+09 | 0.403660E+09 | 0.934647E+09 | 0.116881E+09 |
September | 0.615030E+09 | 0.291696E+09 | 0.323334E+09 | 0.747766E+09 | 0.217448E+09 |
October | 0.402457E+09 | 0.167516E+09 | 0.234941E+09 | 0.361165E+09 | 0.382515E+09 |
November | 0.230378E+09 | 74769286.73 | 0.155608E+09 | 0.119004E+09 | 0.608583E+09 |
December | 0.183715E+09 | 78658898.99 | 0.105056E+09 | 75184566.21 | 0.932838E+09 |
Annual Sum or Average | 0.621436E+10 | 0.269152E+10 | 0.352284E+10 | 0.647307E+10 | 0.531344E+10 |
Minimum of Months | 0.183715E+09 | 74769286.73 | 0.105056E+09 | 75184566.21 | 94626708.25 |
Maximum of Months | 0.841411E+09 | 0.388405E+09 | 0.454555E+09 | 0.110685E+10 | 0.103687E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86192364.35 | 0.00 | 86192364.35 | 51747.62 | 0.821334E+09 |
February | 98700122.93 | 0.00 | 98700122.93 | 2690779.86 | 0.594640E+09 |
March | 0.163792E+09 | 1454.49 | 0.163791E+09 | 46265005.20 | 0.415576E+09 |
April | 0.183710E+09 | 1485815.93 | 0.182225E+09 | 0.106456E+09 | 0.261706E+09 |
May | 0.246823E+09 | 9350474.43 | 0.237472E+09 | 0.236552E+09 | 0.137603E+09 |
June | 0.279519E+09 | 25906479.02 | 0.253612E+09 | 0.343967E+09 | 84714412.15 |
July | 0.270917E+09 | 18687590.12 | 0.252230E+09 | 0.347149E+09 | 73362183.60 |
August | 0.226997E+09 | 4596669.03 | 0.222400E+09 | 0.287806E+09 | 91173523.66 |
September | 0.168105E+09 | 153948.32 | 0.167951E+09 | 0.167702E+09 | 0.169340E+09 |
October | 0.128988E+09 | 0.00 | 0.128988E+09 | 60155785.65 | 0.292029E+09 |
November | 87317471.79 | 0.00 | 87317471.79 | 12901984.53 | 0.474892E+09 |
December | 58527390.14 | 0.00 | 58527390.14 | 0.00 | 0.724163E+09 |
Annual Sum or Average | 0.199959E+10 | 60182431.35 | 0.193940E+10 | 0.161170E+10 | 0.414053E+10 |
Minimum of Months | 58527390.14 | 0.00 | 58527390.14 | 0.00 | 73362183.60 |
Maximum of Months | 0.279519E+09 | 25906479.02 | 0.253612E+09 | 0.347149E+09 | 0.821334E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31774074.45 | 0.00 | 31774074.45 | 19076.32 | 0.302778E+09 |
February | 36384952.16 | 0.00 | 36384952.16 | 991932.87 | 0.219209E+09 |
March | 60380549.76 | 536.18 | 60380013.57 | 17055196.60 | 0.153199E+09 |
April | 67723279.93 | 547733.27 | 67175546.66 | 39244118.24 | 96475524.21 |
May | 90989038.84 | 3446972.05 | 87542066.79 | 87202918.71 | 50726172.32 |
June | 0.103042E+09 | 9550200.87 | 93491957.41 | 0.126801E+09 | 31229240.07 |
July | 99871267.75 | 6889019.51 | 92982248.23 | 0.127974E+09 | 27044338.56 |
August | 83680313.74 | 1694522.54 | 81985791.20 | 0.106097E+09 | 33610336.02 |
September | 61970444.93 | 56751.72 | 61913693.20 | 61822054.56 | 62425822.71 |
October | 47550177.45 | 0.00 | 47550177.45 | 22175913.44 | 0.107654E+09 |
November | 32188835.63 | 0.00 | 32188835.63 | 4756205.73 | 0.175065E+09 |
December | 21575619.43 | 0.00 | 21575619.43 | 0.00 | 0.266956E+09 |
Annual Sum or Average | 0.737131E+09 | 22185736.15 | 0.714945E+09 | 0.594139E+09 | 0.152637E+10 |
Minimum of Months | 21575619.43 | 0.00 | 21575619.43 | 0.00 | 27044338.56 |
Maximum of Months | 0.103042E+09 | 9550200.87 | 93491957.41 | 0.127974E+09 | 0.302778E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198118E+09 | 0.135739E+09 | 62378450.77 | 0.171548E+09 | 0.245120E+09 |
February | 0.192903E+09 | 0.130875E+09 | 62028208.67 | 0.175809E+09 | 0.176439E+09 |
March | 0.182945E+09 | 95767190.91 | 87178264.22 | 0.176378E+09 | 0.138551E+09 |
April | 0.157837E+09 | 72335701.59 | 85501758.44 | 0.174255E+09 | 96116435.79 |
May | 0.139101E+09 | 38911608.60 | 0.100189E+09 | 0.168025E+09 | 54814817.73 |
June | 0.128504E+09 | 25662642.63 | 0.102842E+09 | 0.172897E+09 | 33550169.63 |
July | 0.140917E+09 | 35242432.95 | 0.105674E+09 | 0.197554E+09 | 28637923.81 |
August | 0.156155E+09 | 54076604.29 | 0.102078E+09 | 0.220048E+09 | 35315505.27 |
September | 0.182455E+09 | 94149172.69 | 88306292.08 | 0.238042E+09 | 61288560.93 |
October | 0.203177E+09 | 0.128094E+09 | 75082687.79 | 0.230276E+09 | 99171372.56 |
November | 0.147164E+09 | 92137895.15 | 55026114.60 | 0.137989E+09 | 0.150614E+09 |
December | 0.161923E+09 | 0.122629E+09 | 39293967.74 | 0.152238E+09 | 0.227226E+09 |
Annual Sum or Average | 0.199120E+10 | 0.102562E+10 | 0.965579E+09 | 0.221506E+10 | 0.134685E+10 |
Minimum of Months | 0.128504E+09 | 25662642.63 | 39293967.74 | 0.137989E+09 | 28637923.81 |
Maximum of Months | 0.203177E+09 | 0.135739E+09 | 0.105674E+09 | 0.238042E+09 | 0.245120E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.537732E+09 | 0.368424E+09 | 0.169308E+09 | 0.465615E+09 | 0.665305E+09 |
February | 0.523578E+09 | 0.355220E+09 | 0.168357E+09 | 0.477181E+09 | 0.478891E+09 |
March | 0.496551E+09 | 0.259932E+09 | 0.236620E+09 | 0.478726E+09 | 0.376056E+09 |
April | 0.428403E+09 | 0.196334E+09 | 0.232069E+09 | 0.472962E+09 | 0.260880E+09 |
May | 0.377548E+09 | 0.105614E+09 | 0.271934E+09 | 0.456055E+09 | 0.148779E+09 |
June | 0.348787E+09 | 69653661.29 | 0.279134E+09 | 0.469277E+09 | 91062022.92 |
July | 0.382477E+09 | 95655171.69 | 0.286821E+09 | 0.536201E+09 | 77729182.98 |
August | 0.423837E+09 | 0.146775E+09 | 0.277062E+09 | 0.597255E+09 | 95853504.93 |
September | 0.495221E+09 | 0.255540E+09 | 0.239681E+09 | 0.646096E+09 | 0.166350E+09 |
October | 0.551464E+09 | 0.347674E+09 | 0.203790E+09 | 0.625015E+09 | 0.269171E+09 |
November | 0.399433E+09 | 0.250081E+09 | 0.149352E+09 | 0.374532E+09 | 0.408797E+09 |
December | 0.439491E+09 | 0.332840E+09 | 0.106652E+09 | 0.413204E+09 | 0.616739E+09 |
Annual Sum or Average | 0.540452E+10 | 0.278374E+10 | 0.262078E+10 | 0.601212E+10 | 0.365561E+10 |
Minimum of Months | 0.348787E+09 | 69653661.29 | 0.106652E+09 | 0.374532E+09 | 77729182.98 |
Maximum of Months | 0.551464E+09 | 0.368424E+09 | 0.286821E+09 | 0.646096E+09 | 0.665305E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.424602E+09 | 0.290914E+09 | 0.133688E+09 | 0.371977E+09 | 0.502332E+09 |
February | 0.413426E+09 | 0.280488E+09 | 0.132938E+09 | 0.377798E+09 | 0.362589E+09 |
March | 0.392085E+09 | 0.205247E+09 | 0.186839E+09 | 0.375920E+09 | 0.286168E+09 |
April | 0.338274E+09 | 0.155029E+09 | 0.183246E+09 | 0.365672E+09 | 0.197746E+09 |
May | 0.298118E+09 | 83394652.06 | 0.214724E+09 | 0.350553E+09 | 0.109276E+09 |
June | 0.275408E+09 | 54999709.10 | 0.220409E+09 | 0.366465E+09 | 60633135.24 |
July | 0.302010E+09 | 75530941.52 | 0.226479E+09 | 0.420543E+09 | 48408106.04 |
August | 0.334669E+09 | 0.115896E+09 | 0.218773E+09 | 0.467303E+09 | 61637881.82 |
September | 0.391035E+09 | 0.201779E+09 | 0.189256E+09 | 0.505891E+09 | 0.117257E+09 |
October | 0.435445E+09 | 0.274529E+09 | 0.160916E+09 | 0.486387E+09 | 0.205741E+09 |
November | 0.315399E+09 | 0.197468E+09 | 0.117931E+09 | 0.296540E+09 | 0.307304E+09 |
December | 0.347030E+09 | 0.262816E+09 | 84214117.22 | 0.328172E+09 | 0.463192E+09 |
Annual Sum or Average | 0.426750E+10 | 0.219809E+10 | 0.206941E+10 | 0.471322E+10 | 0.272228E+10 |
Minimum of Months | 0.275408E+09 | 54999709.10 | 84214117.22 | 0.296540E+09 | 48408106.04 |
Maximum of Months | 0.435445E+09 | 0.290914E+09 | 0.226479E+09 | 0.505891E+09 | 0.502332E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271326E+09 | 0.110333E+09 | 0.160993E+09 | 0.114131E+09 | 0.106665E+10 |
February | 0.357678E+09 | 0.176094E+09 | 0.181584E+09 | 0.219738E+09 | 0.765956E+09 |
March | 0.472590E+09 | 0.175770E+09 | 0.296820E+09 | 0.344744E+09 | 0.552651E+09 |
April | 0.668813E+09 | 0.330967E+09 | 0.337846E+09 | 0.682511E+09 | 0.359501E+09 |
May | 0.692500E+09 | 0.277264E+09 | 0.415236E+09 | 0.793741E+09 | 0.197627E+09 |
June | 0.783985E+09 | 0.338994E+09 | 0.444992E+09 | 0.101427E+10 | 0.111487E+09 |
July | 0.870129E+09 | 0.412810E+09 | 0.457318E+09 | 0.116159E+10 | 89566967.20 |
August | 0.759725E+09 | 0.347643E+09 | 0.412081E+09 | 0.101166E+10 | 0.114127E+09 |
September | 0.596579E+09 | 0.282690E+09 | 0.313889E+09 | 0.721922E+09 | 0.217781E+09 |
October | 0.432136E+09 | 0.193056E+09 | 0.239080E+09 | 0.398453E+09 | 0.400715E+09 |
November | 0.249513E+09 | 92645012.94 | 0.156868E+09 | 0.148997E+09 | 0.627850E+09 |
December | 0.198462E+09 | 93913323.71 | 0.104548E+09 | 0.101864E+09 | 0.958744E+09 |
Annual Sum or Average | 0.635344E+10 | 0.283218E+10 | 0.352126E+10 | 0.671361E+10 | 0.546266E+10 |
Minimum of Months | 0.198462E+09 | 92645012.94 | 0.104548E+09 | 0.101864E+09 | 89566967.20 |
Maximum of Months | 0.870129E+09 | 0.412810E+09 | 0.457318E+09 | 0.116159E+10 | 0.106665E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68058948.78 | 0.00 | 68058948.78 | 215220.11 | 0.611018E+09 |
February | 77935286.52 | 0.00 | 77935286.52 | 3435500.28 | 0.441602E+09 |
March | 0.129333E+09 | 1148.49 | 0.129332E+09 | 39579419.48 | 0.311361E+09 |
April | 0.145061E+09 | 1173225.39 | 0.143888E+09 | 80645932.33 | 0.197933E+09 |
May | 0.194895E+09 | 7383292.77 | 0.187512E+09 | 0.175699E+09 | 0.104011E+09 |
June | 0.220713E+09 | 20456194.03 | 0.200256E+09 | 0.262488E+09 | 61639578.39 |
July | 0.213921E+09 | 14756037.25 | 0.199165E+09 | 0.266043E+09 | 53286305.49 |
August | 0.179240E+09 | 3629607.62 | 0.175611E+09 | 0.221118E+09 | 66153717.30 |
September | 0.132739E+09 | 121560.20 | 0.132617E+09 | 0.131687E+09 | 0.122373E+09 |
October | 0.101851E+09 | 0.00 | 0.101851E+09 | 49888793.96 | 0.219225E+09 |
November | 68947352.64 | 0.00 | 68947352.64 | 11949316.14 | 0.350134E+09 |
December | 46214217.21 | 0.00 | 46214217.21 | 46421.92 | 0.536174E+09 |
Annual Sum or Average | 0.157891E+10 | 47521065.74 | 0.153139E+10 | 0.124280E+10 | 0.307491E+10 |
Minimum of Months | 46214217.21 | 0.00 | 46214217.21 | 46421.92 | 53286305.49 |
Maximum of Months | 0.220713E+09 | 20456194.03 | 0.200256E+09 | 0.266043E+09 | 0.611018E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271326E+09 | 0.110333E+09 | 0.160993E+09 | 0.118702E+09 | 0.105889E+10 |
February | 0.357678E+09 | 0.176094E+09 | 0.181584E+09 | 0.227583E+09 | 0.756318E+09 |
March | 0.472590E+09 | 0.175770E+09 | 0.296820E+09 | 0.355737E+09 | 0.546521E+09 |
April | 0.668813E+09 | 0.330967E+09 | 0.337846E+09 | 0.688619E+09 | 0.358681E+09 |
May | 0.692500E+09 | 0.277264E+09 | 0.415236E+09 | 0.788288E+09 | 0.203073E+09 |
June | 0.783985E+09 | 0.338994E+09 | 0.444992E+09 | 0.100296E+10 | 0.120579E+09 |
July | 0.870129E+09 | 0.412810E+09 | 0.457318E+09 | 0.114922E+10 | 0.103153E+09 |
August | 0.759725E+09 | 0.347643E+09 | 0.412081E+09 | 0.100415E+10 | 0.127400E+09 |
September | 0.596579E+09 | 0.282690E+09 | 0.313889E+09 | 0.725294E+09 | 0.222494E+09 |
October | 0.432136E+09 | 0.193056E+09 | 0.239080E+09 | 0.411884E+09 | 0.394480E+09 |
November | 0.249513E+09 | 92645012.94 | 0.156868E+09 | 0.156036E+09 | 0.621767E+09 |
December | 0.198462E+09 | 93913323.71 | 0.104548E+09 | 0.107530E+09 | 0.951949E+09 |
Annual Sum or Average | 0.635344E+10 | 0.283218E+10 | 0.352126E+10 | 0.673600E+10 | 0.546530E+10 |
Minimum of Months | 0.198462E+09 | 92645012.94 | 0.104548E+09 | 0.107530E+09 | 0.103153E+09 |
Maximum of Months | 0.870129E+09 | 0.412810E+09 | 0.457318E+09 | 0.114922E+10 | 0.105889E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.622720E+09 | 0.426653E+09 | 0.196067E+09 | 0.526295E+09 | 0.756909E+09 |
February | 0.606329E+09 | 0.411363E+09 | 0.194966E+09 | 0.536862E+09 | 0.549937E+09 |
March | 0.575031E+09 | 0.301014E+09 | 0.274017E+09 | 0.536784E+09 | 0.431293E+09 |
April | 0.496112E+09 | 0.227364E+09 | 0.268748E+09 | 0.532828E+09 | 0.293110E+09 |
May | 0.437219E+09 | 0.122306E+09 | 0.314913E+09 | 0.515511E+09 | 0.159174E+09 |
June | 0.403913E+09 | 80662351.74 | 0.323251E+09 | 0.543531E+09 | 86477507.99 |
July | 0.442927E+09 | 0.110773E+09 | 0.332153E+09 | 0.624842E+09 | 66781319.71 |
August | 0.490824E+09 | 0.169973E+09 | 0.320851E+09 | 0.690286E+09 | 87337200.72 |
September | 0.573491E+09 | 0.295928E+09 | 0.277563E+09 | 0.738997E+09 | 0.173065E+09 |
October | 0.638622E+09 | 0.402624E+09 | 0.235999E+09 | 0.700725E+09 | 0.311261E+09 |
November | 0.462563E+09 | 0.289606E+09 | 0.172957E+09 | 0.421732E+09 | 0.466347E+09 |
December | 0.508953E+09 | 0.385444E+09 | 0.123508E+09 | 0.466000E+09 | 0.699021E+09 |
Annual Sum or Average | 0.625870E+10 | 0.322371E+10 | 0.303499E+10 | 0.683439E+10 | 0.408071E+10 |
Minimum of Months | 0.403913E+09 | 80662351.74 | 0.123508E+09 | 0.421732E+09 | 66781319.71 |
Maximum of Months | 0.638622E+09 | 0.426653E+09 | 0.332153E+09 | 0.738997E+09 | 0.756909E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.476395E+09 | 0.00 | 0.476395E+09 | 227799.12 | 0.456562E+10 |
February | 0.545526E+09 | 0.00 | 0.545526E+09 | 12941601.32 | 0.331447E+10 |
March | 0.905297E+09 | 8039.10 | 0.905289E+09 | 0.237224E+09 | 0.238633E+10 |
April | 0.101539E+10 | 8212266.70 | 0.100718E+10 | 0.565706E+09 | 0.152933E+10 |
May | 0.136422E+10 | 51681092.00 | 0.131253E+10 | 0.126590E+10 | 0.813040E+09 |
June | 0.154493E+10 | 0.143188E+09 | 0.140174E+10 | 0.190006E+10 | 0.490201E+09 |
July | 0.149739E+10 | 0.103288E+09 | 0.139410E+10 | 0.194682E+10 | 0.404579E+09 |
August | 0.125463E+10 | 25406291.07 | 0.122923E+10 | 0.161832E+10 | 0.507311E+09 |
September | 0.929134E+09 | 850889.14 | 0.928283E+09 | 0.942872E+09 | 0.953211E+09 |
October | 0.712929E+09 | 0.00 | 0.712929E+09 | 0.309356E+09 | 0.170726E+10 |
November | 0.482613E+09 | 0.00 | 0.482613E+09 | 63452245.62 | 0.270557E+10 |
December | 0.323487E+09 | 0.00 | 0.323487E+09 | 0.00 | 0.405614E+10 |
Annual Sum or Average | 0.110519E+11 | 0.332635E+09 | 0.107193E+11 | 0.886287E+10 | 0.234331E+11 |
Minimum of Months | 0.323487E+09 | 0.00 | 0.323487E+09 | 0.00 | 0.404579E+09 |
Maximum of Months | 0.154493E+10 | 0.143188E+09 | 0.140174E+10 | 0.194682E+10 | 0.456562E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.476395E+09 | 0.00 | 0.476395E+09 | 102009.57 | 0.464461E+10 |
February | 0.545526E+09 | 0.00 | 0.545526E+09 | 10654505.13 | 0.339298E+10 |
March | 0.905297E+09 | 8039.10 | 0.905289E+09 | 0.219844E+09 | 0.246374E+10 |
April | 0.101539E+10 | 8212266.70 | 0.100718E+10 | 0.541027E+09 | 0.159084E+10 |
May | 0.136422E+10 | 51681092.00 | 0.131253E+10 | 0.122813E+10 | 0.844217E+09 |
June | 0.154493E+10 | 0.143188E+09 | 0.140174E+10 | 0.186289E+10 | 0.513136E+09 |
July | 0.149739E+10 | 0.103288E+09 | 0.139410E+10 | 0.190942E+10 | 0.425817E+09 |
August | 0.125463E+10 | 25406291.07 | 0.122923E+10 | 0.158391E+10 | 0.532096E+09 |
September | 0.929134E+09 | 850889.14 | 0.928283E+09 | 0.916085E+09 | 0.991610E+09 |
October | 0.712929E+09 | 0.00 | 0.712929E+09 | 0.285732E+09 | 0.177574E+10 |
November | 0.482613E+09 | 0.00 | 0.482613E+09 | 56364047.51 | 0.278466E+10 |
December | 0.323487E+09 | 0.00 | 0.323487E+09 | 0.00 | 0.413939E+10 |
Annual Sum or Average | 0.110519E+11 | 0.332635E+09 | 0.107193E+11 | 0.861416E+10 | 0.240988E+11 |
Minimum of Months | 0.323487E+09 | 0.00 | 0.323487E+09 | 0.00 | 0.425817E+09 |
Maximum of Months | 0.154493E+10 | 0.143188E+09 | 0.140174E+10 | 0.190942E+10 | 0.464461E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68058948.78 | 0.00 | 68058948.78 | 332597.01 | 0.620709E+09 |
February | 77935286.52 | 0.00 | 77935286.52 | 4334647.96 | 0.451641E+09 |
March | 0.129333E+09 | 1148.49 | 0.129332E+09 | 48832282.33 | 0.322673E+09 |
April | 0.145061E+09 | 1173225.39 | 0.143888E+09 | 0.109062E+09 | 0.204505E+09 |
May | 0.194895E+09 | 7383292.77 | 0.187512E+09 | 0.236645E+09 | 0.113162E+09 |
June | 0.220713E+09 | 20456194.03 | 0.200256E+09 | 0.335141E+09 | 69574661.35 |
July | 0.213921E+09 | 14756037.25 | 0.199165E+09 | 0.347188E+09 | 57120152.13 |
August | 0.179240E+09 | 3629607.62 | 0.175611E+09 | 0.295123E+09 | 69583853.11 |
September | 0.132739E+09 | 121560.20 | 0.132617E+09 | 0.179623E+09 | 0.125248E+09 |
October | 0.101851E+09 | 0.00 | 0.101851E+09 | 68020065.75 | 0.223979E+09 |
November | 68947352.64 | 0.00 | 68947352.64 | 18061012.96 | 0.358382E+09 |
December | 46214217.21 | 0.00 | 46214217.21 | 104662.71 | 0.546306E+09 |
Annual Sum or Average | 0.157891E+10 | 47521065.74 | 0.153139E+10 | 0.164247E+10 | 0.316288E+10 |
Minimum of Months | 46214217.21 | 0.00 | 46214217.21 | 104662.71 | 57120152.13 |
Maximum of Months | 0.220713E+09 | 20456194.03 | 0.200256E+09 | 0.347188E+09 | 0.620709E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.543050E+09 | 0.222544E+09 | 0.320506E+09 | 0.228567E+09 | 0.211874E+10 |
February | 0.653125E+09 | 0.287462E+09 | 0.365663E+09 | 0.374798E+09 | 0.151543E+10 |
March | 0.982098E+09 | 0.389652E+09 | 0.592446E+09 | 0.801117E+09 | 0.111189E+10 |
April | 0.115999E+10 | 0.505565E+09 | 0.654427E+09 | 0.124751E+10 | 0.742054E+09 |
May | 0.151453E+10 | 0.662413E+09 | 0.852121E+09 | 0.196977E+10 | 0.419797E+09 |
June | 0.161073E+10 | 0.701683E+09 | 0.909045E+09 | 0.233703E+10 | 0.260607E+09 |
July | 0.168270E+10 | 0.776756E+09 | 0.905948E+09 | 0.251595E+10 | 0.213751E+09 |
August | 0.141864E+10 | 0.611380E+09 | 0.807262E+09 | 0.214387E+10 | 0.259896E+09 |
September | 0.122997E+10 | 0.583351E+09 | 0.646622E+09 | 0.169798E+10 | 0.455627E+09 |
October | 0.804857E+09 | 0.335009E+09 | 0.469849E+09 | 0.820913E+09 | 0.792811E+09 |
November | 0.460723E+09 | 0.149528E+09 | 0.311195E+09 | 0.273062E+09 | 0.125472E+10 |
December | 0.367404E+09 | 0.157307E+09 | 0.210097E+09 | 0.160650E+09 | 0.190580E+10 |
Annual Sum or Average | 0.124278E+11 | 0.538265E+10 | 0.704518E+10 | 0.145712E+11 | 0.110511E+11 |
Minimum of Months | 0.367404E+09 | 0.149528E+09 | 0.210097E+09 | 0.160650E+09 | 0.213751E+09 |
Maximum of Months | 0.168270E+10 | 0.776756E+09 | 0.909045E+09 | 0.251595E+10 | 0.211874E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.424602E+09 | 0.290914E+09 | 0.133688E+09 | 0.381612E+09 | 0.510607E+09 |
February | 0.413426E+09 | 0.280488E+09 | 0.132938E+09 | 0.391747E+09 | 0.370629E+09 |
March | 0.392085E+09 | 0.205247E+09 | 0.186839E+09 | 0.398997E+09 | 0.296521E+09 |
April | 0.338274E+09 | 0.155029E+09 | 0.183246E+09 | 0.401699E+09 | 0.204266E+09 |
May | 0.298118E+09 | 83394652.06 | 0.214724E+09 | 0.409024E+09 | 0.119252E+09 |
June | 0.275408E+09 | 54999709.10 | 0.220409E+09 | 0.432592E+09 | 73063653.75 |
July | 0.302010E+09 | 75530941.52 | 0.226479E+09 | 0.495343E+09 | 59000270.80 |
August | 0.334669E+09 | 0.115896E+09 | 0.218773E+09 | 0.537960E+09 | 71699350.34 |
September | 0.391035E+09 | 0.201779E+09 | 0.189256E+09 | 0.560555E+09 | 0.123946E+09 |
October | 0.435445E+09 | 0.274529E+09 | 0.160916E+09 | 0.523729E+09 | 0.212502E+09 |
November | 0.315399E+09 | 0.197468E+09 | 0.117931E+09 | 0.313450E+09 | 0.316107E+09 |
December | 0.347030E+09 | 0.262816E+09 | 84214117.22 | 0.338868E+09 | 0.471096E+09 |
Annual Sum or Average | 0.426750E+10 | 0.219809E+10 | 0.206941E+10 | 0.518558E+10 | 0.282869E+10 |
Minimum of Months | 0.275408E+09 | 54999709.10 | 84214117.22 | 0.313450E+09 | 59000270.80 |
Maximum of Months | 0.435445E+09 | 0.290914E+09 | 0.226479E+09 | 0.560555E+09 | 0.510607E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86192364.35 | 0.00 | 86192364.35 | 13641.18 | 0.829046E+09 |
February | 98700122.93 | 0.00 | 98700122.93 | 2046324.40 | 0.599595E+09 |
March | 0.163792E+09 | 1454.49 | 0.163791E+09 | 41281258.86 | 0.426307E+09 |
April | 0.183710E+09 | 1485815.93 | 0.182225E+09 | 95217957.47 | 0.276692E+09 |
May | 0.246823E+09 | 9350474.43 | 0.237472E+09 | 0.211319E+09 | 0.156255E+09 |
June | 0.279519E+09 | 25906479.02 | 0.253612E+09 | 0.322922E+09 | 96487444.23 |
July | 0.270917E+09 | 18687590.12 | 0.252230E+09 | 0.328600E+09 | 82225157.87 |
August | 0.226997E+09 | 4596669.03 | 0.222400E+09 | 0.269605E+09 | 0.102830E+09 |
September | 0.168105E+09 | 153948.32 | 0.167951E+09 | 0.154273E+09 | 0.184193E+09 |
October | 0.128988E+09 | 0.00 | 0.128988E+09 | 50670460.45 | 0.310464E+09 |
November | 87317471.79 | 0.00 | 87317471.79 | 10225847.00 | 0.487211E+09 |
December | 58527390.14 | 0.00 | 58527390.14 | 0.00 | 0.732458E+09 |
Annual Sum or Average | 0.199959E+10 | 60182431.35 | 0.193940E+10 | 0.148618E+10 | 0.428376E+10 |
Minimum of Months | 58527390.14 | 0.00 | 58527390.14 | 0.00 | 82225157.87 |
Maximum of Months | 0.279519E+09 | 25906479.02 | 0.253612E+09 | 0.328600E+09 | 0.829046E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77116634.97 | 0.00 | 77116634.97 | 12204.82 | 0.741715E+09 |
February | 88307373.96 | 0.00 | 88307373.96 | 1830854.20 | 0.536459E+09 |
March | 0.146545E+09 | 1301.33 | 0.146544E+09 | 36934498.71 | 0.381418E+09 |
April | 0.164366E+09 | 1329365.14 | 0.163037E+09 | 85191867.33 | 0.247557E+09 |
May | 0.220833E+09 | 8365904.91 | 0.212467E+09 | 0.189068E+09 | 0.139802E+09 |
June | 0.250086E+09 | 23178624.94 | 0.226908E+09 | 0.288920E+09 | 86327681.94 |
July | 0.242391E+09 | 16719857.69 | 0.225671E+09 | 0.294000E+09 | 73567160.29 |
August | 0.203095E+09 | 4112657.20 | 0.198982E+09 | 0.241216E+09 | 92002687.54 |
September | 0.150404E+09 | 137738.14 | 0.150266E+09 | 0.138029E+09 | 0.164798E+09 |
October | 0.115406E+09 | 0.00 | 0.115406E+09 | 45335052.96 | 0.277774E+09 |
November | 78123272.85 | 0.00 | 78123272.85 | 9149104.05 | 0.435899E+09 |
December | 52364677.72 | 0.00 | 52364677.72 | 0.00 | 0.655296E+09 |
Annual Sum or Average | 0.178904E+10 | 53845449.36 | 0.173519E+10 | 0.132969E+10 | 0.383262E+10 |
Minimum of Months | 52364677.72 | 0.00 | 52364677.72 | 0.00 | 73567160.29 |
Maximum of Months | 0.250086E+09 | 23178624.94 | 0.226908E+09 | 0.294000E+09 | 0.741715E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158517E+10 | 0.108607E+10 | 0.499098E+09 | 0.135680E+10 | 0.197397E+10 |
February | 0.154344E+10 | 0.104715E+10 | 0.496296E+09 | 0.139099E+10 | 0.141869E+10 |
March | 0.146377E+10 | 0.766246E+09 | 0.697525E+09 | 0.138292E+10 | 0.113468E+10 |
April | 0.126288E+10 | 0.578768E+09 | 0.684111E+09 | 0.135387E+10 | 0.812224E+09 |
May | 0.111296E+10 | 0.311337E+09 | 0.801628E+09 | 0.127119E+10 | 0.499431E+09 |
June | 0.102818E+10 | 0.205330E+09 | 0.822852E+09 | 0.132298E+10 | 0.307458E+09 |
July | 0.112749E+10 | 0.281980E+09 | 0.845514E+09 | 0.152567E+10 | 0.258403E+09 |
August | 0.124942E+10 | 0.432674E+09 | 0.816743E+09 | 0.170379E+10 | 0.319948E+09 |
September | 0.145985E+10 | 0.753300E+09 | 0.706551E+09 | 0.185651E+10 | 0.532943E+09 |
October | 0.162565E+10 | 0.102490E+10 | 0.600747E+09 | 0.179752E+10 | 0.840471E+09 |
November | 0.117748E+10 | 0.737208E+09 | 0.440271E+09 | 0.108154E+10 | 0.123545E+10 |
December | 0.129557E+10 | 0.981169E+09 | 0.314396E+09 | 0.120511E+10 | 0.183408E+10 |
Annual Sum or Average | 0.159319E+11 | 0.820613E+10 | 0.772573E+10 | 0.172489E+11 | 0.111677E+11 |
Minimum of Months | 0.102818E+10 | 0.205330E+09 | 0.314396E+09 | 0.108154E+10 | 0.258403E+09 |
Maximum of Months | 0.162565E+10 | 0.108607E+10 | 0.845514E+09 | 0.185651E+10 | 0.197397E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 702.01 | 919.29 | 801.79 | 549.34 | 252.45 | 0.00 | 0.00 |
February | 791.26 | 737.47 | 864.33 | 586.41 | 277.93 | 0.00 | 0.00 |
March | 710.01 | 529.77 | 740.39 | 387.58 | 352.81 | 0.00 | 0.00 |
April | 713.24 | 388.67 | 660.07 | 302.50 | 357.56 | 0.00 | 0.00 |
May | 658.89 | 224.01 | 562.94 | 157.48 | 405.47 | 0.00 | 0.00 |
June | 697.70 | 146.29 | 537.40 | 107.32 | 430.08 | 0.00 | 0.00 |
July | 772.60 | 125.35 | 570.29 | 142.63 | 427.66 | 0.00 | 0.00 |
August | 864.39 | 153.11 | 631.96 | 218.85 | 413.11 | 0.00 | 0.00 |
September | 973.46 | 259.62 | 763.02 | 393.73 | 369.29 | 0.00 | 0.00 |
October | 912.37 | 399.56 | 822.27 | 518.40 | 303.86 | 0.00 | 0.00 |
November | 574.89 | 591.77 | 615.43 | 385.32 | 230.12 | 0.00 | 0.00 |
December | 614.64 | 855.17 | 655.31 | 496.29 | 159.02 | 0.00 | 0.00 |
Annual Sum or Average | 748.54 | 442.83 | 684.42 | 352.53 | 331.89 | 0.00 | 0.00 |
Minimum of Months | 574.89 | 125.35 | 537.40 | 107.32 | 159.02 | 0.00 | 0.00 |
Maximum of Months | 973.46 | 919.29 | 864.33 | 586.41 | 430.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1969.70 | 2598.23 | 2257.79 | 1546.92 | 710.88 | 0.00 | 0.00 |
February | 2220.86 | 2092.63 | 2433.90 | 1651.28 | 782.62 | 0.00 | 0.00 |
March | 1997.04 | 1502.39 | 2084.88 | 1091.39 | 993.50 | 0.00 | 0.00 |
April | 2016.31 | 1095.04 | 1858.70 | 851.83 | 1006.87 | 0.00 | 0.00 |
May | 1893.51 | 607.31 | 1585.22 | 443.45 | 1141.77 | 0.00 | 0.00 |
June | 2018.31 | 382.10 | 1513.27 | 302.21 | 1211.06 | 0.00 | 0.00 |
July | 2236.98 | 313.53 | 1605.91 | 401.63 | 1204.28 | 0.00 | 0.00 |
August | 2483.62 | 392.28 | 1779.57 | 616.27 | 1163.30 | 0.00 | 0.00 |
September | 2760.00 | 707.51 | 2148.61 | 1108.71 | 1039.90 | 0.00 | 0.00 |
October | 2570.32 | 1129.34 | 2315.45 | 1459.79 | 855.65 | 0.00 | 0.00 |
November | 1612.95 | 1681.06 | 1733.02 | 1085.03 | 647.99 | 0.00 | 0.00 |
December | 1727.32 | 2418.14 | 1845.31 | 1397.51 | 447.80 | 0.00 | 0.00 |
Annual Sum or Average | 2125.05 | 1239.35 | 1927.27 | 992.70 | 934.58 | 0.00 | 0.00 |
Minimum of Months | 1612.95 | 313.53 | 1513.27 | 302.21 | 447.80 | 0.00 | 0.00 |
Maximum of Months | 2760.00 | 2598.23 | 2433.90 | 1651.28 | 1211.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2588.31 | 3507.64 | 2933.00 | 2009.53 | 923.47 | 0.00 | 0.00 |
February | 2924.23 | 2834.24 | 3161.78 | 2145.11 | 1016.67 | 0.00 | 0.00 |
March | 2629.80 | 2059.77 | 2708.38 | 1417.77 | 1290.61 | 0.00 | 0.00 |
April | 2658.21 | 1516.02 | 2414.56 | 1106.58 | 1307.98 | 0.00 | 0.00 |
May | 2474.59 | 858.93 | 2059.29 | 576.06 | 1483.22 | 0.00 | 0.00 |
June | 2638.82 | 547.88 | 1965.83 | 392.58 | 1573.24 | 0.00 | 0.00 |
July | 2928.54 | 449.56 | 2086.17 | 521.74 | 1564.42 | 0.00 | 0.00 |
August | 3259.55 | 554.78 | 2311.76 | 800.57 | 1511.19 | 0.00 | 0.00 |
September | 3630.34 | 986.70 | 2791.16 | 1440.28 | 1350.89 | 0.00 | 0.00 |
October | 3378.84 | 1560.22 | 3007.90 | 1896.35 | 1111.54 | 0.00 | 0.00 |
November | 2114.07 | 2307.49 | 2251.29 | 1409.51 | 841.78 | 0.00 | 0.00 |
December | 2271.76 | 3283.73 | 2397.16 | 1815.44 | 581.72 | 0.00 | 0.00 |
Annual Sum or Average | 2790.67 | 1700.31 | 2503.64 | 1289.57 | 1214.07 | 0.00 | 0.00 |
Minimum of Months | 2114.07 | 449.56 | 1965.83 | 392.58 | 581.72 | 0.00 | 0.00 |
Maximum of Months | 3630.34 | 3507.64 | 3161.78 | 2145.11 | 1573.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 149.49 | 552.54 | 259.83 | 149.81 | 110.02 | 0.00 | 0.00 |
February | 222.86 | 441.92 | 318.74 | 188.73 | 130.01 | 0.00 | 0.00 |
March | 262.27 | 306.00 | 322.83 | 142.26 | 180.58 | 0.00 | 0.00 |
April | 403.94 | 212.93 | 388.54 | 187.50 | 201.04 | 0.00 | 0.00 |
May | 429.64 | 114.29 | 369.85 | 134.65 | 235.20 | 0.00 | 0.00 |
June | 535.60 | 67.20 | 408.72 | 152.00 | 256.71 | 0.00 | 0.00 |
July | 593.96 | 52.56 | 437.63 | 182.33 | 255.30 | 0.00 | 0.00 |
August | 555.19 | 66.47 | 408.60 | 173.07 | 235.53 | 0.00 | 0.00 |
September | 474.33 | 129.91 | 381.02 | 186.91 | 194.11 | 0.00 | 0.00 |
October | 327.51 | 223.60 | 323.92 | 174.58 | 149.34 | 0.00 | 0.00 |
November | 160.01 | 349.99 | 217.94 | 111.93 | 106.02 | 0.00 | 0.00 |
December | 139.21 | 509.60 | 203.66 | 133.19 | 70.48 | 0.00 | 0.00 |
Annual Sum or Average | 355.16 | 251.37 | 336.79 | 159.51 | 177.28 | 0.00 | 0.00 |
Minimum of Months | 139.21 | 52.56 | 203.66 | 111.93 | 70.48 | 0.00 | 0.00 |
Maximum of Months | 593.96 | 552.54 | 437.63 | 188.73 | 256.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 33.32 | 611.30 | 126.71 | 41.19 | 85.52 | 0.00 | 0.00 |
February | 83.02 | 482.86 | 180.07 | 72.79 | 107.27 | 0.00 | 0.00 |
March | 141.99 | 315.15 | 224.73 | 65.63 | 159.11 | 0.00 | 0.00 |
April | 296.17 | 213.00 | 313.99 | 128.14 | 185.85 | 0.00 | 0.00 |
May | 362.50 | 113.17 | 331.32 | 106.28 | 225.04 | 0.00 | 0.00 |
June | 490.83 | 68.79 | 387.61 | 138.68 | 248.94 | 0.00 | 0.00 |
July | 531.41 | 57.31 | 404.74 | 159.64 | 245.10 | 0.00 | 0.00 |
August | 460.10 | 71.22 | 350.57 | 131.15 | 219.42 | 0.00 | 0.00 |
September | 330.51 | 133.20 | 281.37 | 109.11 | 172.26 | 0.00 | 0.00 |
October | 169.57 | 228.24 | 199.37 | 72.08 | 127.29 | 0.00 | 0.00 |
November | 59.44 | 371.43 | 122.86 | 35.74 | 87.12 | 0.00 | 0.00 |
December | 32.15 | 547.33 | 91.35 | 35.06 | 56.29 | 0.00 | 0.00 |
Annual Sum or Average | 250.12 | 266.76 | 251.53 | 91.31 | 160.22 | 0.00 | 0.00 |
Minimum of Months | 32.15 | 57.31 | 91.35 | 35.06 | 56.29 | 0.00 | 0.00 |
Maximum of Months | 531.41 | 611.30 | 404.74 | 159.64 | 248.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 114.62 | 133.10 | 126.80 | 86.87 | 39.92 | 0.00 | 0.00 |
February | 125.97 | 117.42 | 136.69 | 92.74 | 43.95 | 0.00 | 0.00 |
March | 109.25 | 89.99 | 117.09 | 61.29 | 55.80 | 0.00 | 0.00 |
April | 106.31 | 79.72 | 104.38 | 47.84 | 56.55 | 0.00 | 0.00 |
May | 93.73 | 50.21 | 89.03 | 24.90 | 64.12 | 0.00 | 0.00 |
June | 101.26 | 33.92 | 84.99 | 16.97 | 68.01 | 0.00 | 0.00 |
July | 113.91 | 28.43 | 90.19 | 22.56 | 67.63 | 0.00 | 0.00 |
August | 128.57 | 34.17 | 99.94 | 34.61 | 65.33 | 0.00 | 0.00 |
September | 146.03 | 55.76 | 120.67 | 62.27 | 58.40 | 0.00 | 0.00 |
October | 134.49 | 84.04 | 130.04 | 81.98 | 48.05 | 0.00 | 0.00 |
November | 86.42 | 106.11 | 97.33 | 60.93 | 36.39 | 0.00 | 0.00 |
December | 99.53 | 125.48 | 103.63 | 78.48 | 25.15 | 0.00 | 0.00 |
Annual Sum or Average | 113.27 | 77.98 | 108.24 | 55.75 | 52.49 | 0.00 | 0.00 |
Minimum of Months | 86.42 | 28.43 | 84.99 | 16.97 | 25.15 | 0.00 | 0.00 |
Maximum of Months | 146.03 | 133.10 | 136.69 | 92.74 | 68.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.03 | 187.72 | 20.33 | 0.00 | 20.33 | 0.00 | 0.00 |
February | 0.88 | 150.01 | 25.78 | 0.00 | 25.78 | 0.00 | 0.00 |
March | 11.31 | 95.91 | 38.64 | 0.00 | 38.63 | 0.00 | 0.00 |
April | 26.35 | 61.86 | 44.78 | 0.36 | 44.42 | 0.00 | 0.00 |
May | 56.21 | 30.30 | 58.22 | 2.21 | 56.01 | 0.00 | 0.00 |
June | 85.79 | 17.86 | 68.13 | 6.31 | 61.82 | 0.00 | 0.00 |
July | 84.71 | 14.02 | 63.90 | 4.41 | 59.50 | 0.00 | 0.00 |
August | 70.59 | 17.90 | 53.54 | 1.08 | 52.46 | 0.00 | 0.00 |
September | 42.80 | 37.13 | 40.97 | 0.04 | 40.94 | 0.00 | 0.00 |
October | 14.48 | 67.32 | 30.43 | 0.00 | 30.43 | 0.00 | 0.00 |
November | 3.24 | 112.82 | 21.28 | 0.00 | 21.28 | 0.00 | 0.00 |
December | 0.00 | 165.94 | 13.81 | 0.00 | 13.81 | 0.00 | 0.00 |
Annual Sum or Average | 33.23 | 79.57 | 40.06 | 1.21 | 38.85 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 14.02 | 13.81 | 0.00 | 13.81 | 0.00 | 0.00 |
Maximum of Months | 85.79 | 187.72 | 68.13 | 6.31 | 61.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.06 | 549.62 | 259.91 | 150.16 | 109.75 | 0.00 | 0.00 |
February | 203.45 | 435.24 | 305.89 | 175.36 | 130.53 | 0.00 | 0.00 |
March | 267.77 | 301.62 | 329.74 | 149.38 | 180.36 | 0.00 | 0.00 |
April | 353.47 | 208.61 | 354.29 | 157.34 | 196.95 | 0.00 | 0.00 |
May | 454.47 | 108.27 | 394.06 | 154.80 | 239.25 | 0.00 | 0.00 |
June | 543.47 | 63.59 | 416.99 | 156.58 | 260.40 | 0.00 | 0.00 |
July | 574.79 | 49.17 | 426.90 | 173.21 | 253.69 | 0.00 | 0.00 |
August | 525.37 | 62.28 | 389.80 | 157.41 | 232.39 | 0.00 | 0.00 |
September | 481.14 | 127.11 | 388.14 | 190.38 | 197.76 | 0.00 | 0.00 |
October | 309.02 | 219.54 | 312.84 | 165.04 | 147.80 | 0.00 | 0.00 |
November | 147.82 | 345.94 | 210.56 | 105.03 | 105.53 | 0.00 | 0.00 |
December | 129.20 | 504.31 | 198.16 | 127.49 | 70.67 | 0.00 | 0.00 |
Annual Sum or Average | 345.77 | 247.08 | 332.38 | 155.05 | 177.33 | 0.00 | 0.00 |
Minimum of Months | 129.20 | 49.17 | 198.16 | 105.03 | 70.67 | 0.00 | 0.00 |
Maximum of Months | 574.79 | 549.62 | 426.90 | 190.38 | 260.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.46 | 600.80 | 126.79 | 41.55 | 85.25 | 0.00 | 0.00 |
February | 61.09 | 473.57 | 167.21 | 59.42 | 107.80 | 0.00 | 0.00 |
March | 144.60 | 307.71 | 231.64 | 72.75 | 158.89 | 0.00 | 0.00 |
April | 245.63 | 207.72 | 279.74 | 97.98 | 181.76 | 0.00 | 0.00 |
May | 390.26 | 108.32 | 355.52 | 126.42 | 229.09 | 0.00 | 0.00 |
June | 500.46 | 66.13 | 395.88 | 143.26 | 252.63 | 0.00 | 0.00 |
July | 512.33 | 53.77 | 394.02 | 150.52 | 243.49 | 0.00 | 0.00 |
August | 431.30 | 66.63 | 331.77 | 115.49 | 216.27 | 0.00 | 0.00 |
September | 336.34 | 128.95 | 288.49 | 112.58 | 175.91 | 0.00 | 0.00 |
October | 148.27 | 220.44 | 188.29 | 62.54 | 125.74 | 0.00 | 0.00 |
November | 43.89 | 363.90 | 115.48 | 28.85 | 86.63 | 0.00 | 0.00 |
December | 19.72 | 540.10 | 85.85 | 29.37 | 56.48 | 0.00 | 0.00 |
Annual Sum or Average | 239.35 | 260.53 | 247.12 | 86.85 | 160.27 | 0.00 | 0.00 |
Minimum of Months | 19.72 | 53.77 | 85.85 | 28.85 | 56.48 | 0.00 | 0.00 |
Maximum of Months | 512.33 | 600.80 | 395.88 | 150.52 | 252.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 180.67 | 702.36 | 318.78 | 188.23 | 130.55 | 0.00 | 0.00 |
February | 225.52 | 561.37 | 352.00 | 200.93 | 151.07 | 0.00 | 0.00 |
March | 257.63 | 393.89 | 337.39 | 132.80 | 204.59 | 0.00 | 0.00 |
April | 304.74 | 274.75 | 323.18 | 104.44 | 218.74 | 0.00 | 0.00 |
May | 351.89 | 144.33 | 319.02 | 58.74 | 260.28 | 0.00 | 0.00 |
June | 427.19 | 90.62 | 331.73 | 50.45 | 281.28 | 0.00 | 0.00 |
July | 450.02 | 75.88 | 333.85 | 58.42 | 275.43 | 0.00 | 0.00 |
August | 451.45 | 94.80 | 332.54 | 77.34 | 255.20 | 0.00 | 0.00 |
September | 428.93 | 176.51 | 350.21 | 134.99 | 215.22 | 0.00 | 0.00 |
October | 343.65 | 280.33 | 347.66 | 177.63 | 170.03 | 0.00 | 0.00 |
November | 182.46 | 444.49 | 256.98 | 132.03 | 124.96 | 0.00 | 0.00 |
December | 171.84 | 645.87 | 254.45 | 170.05 | 84.40 | 0.00 | 0.00 |
Annual Sum or Average | 315.17 | 322.66 | 321.30 | 123.41 | 197.89 | 0.00 | 0.00 |
Minimum of Months | 171.84 | 75.88 | 254.45 | 50.45 | 84.40 | 0.00 | 0.00 |
Maximum of Months | 451.45 | 702.36 | 352.00 | 200.93 | 281.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 148.70 | 553.00 | 259.83 | 149.81 | 110.02 | 0.00 | 0.00 |
February | 221.71 | 441.21 | 318.74 | 188.73 | 130.01 | 0.00 | 0.00 |
March | 261.30 | 305.42 | 322.83 | 142.26 | 180.58 | 0.00 | 0.00 |
April | 401.28 | 211.87 | 388.54 | 187.50 | 201.04 | 0.00 | 0.00 |
May | 426.24 | 113.60 | 369.85 | 134.65 | 235.20 | 0.00 | 0.00 |
June | 532.40 | 66.12 | 408.72 | 152.00 | 256.71 | 0.00 | 0.00 |
July | 590.57 | 51.39 | 437.63 | 182.33 | 255.30 | 0.00 | 0.00 |
August | 551.95 | 65.39 | 408.60 | 173.07 | 235.53 | 0.00 | 0.00 |
September | 472.50 | 128.06 | 381.02 | 186.91 | 194.11 | 0.00 | 0.00 |
October | 326.31 | 222.37 | 323.92 | 174.58 | 149.34 | 0.00 | 0.00 |
November | 159.98 | 348.88 | 217.94 | 111.93 | 106.02 | 0.00 | 0.00 |
December | 139.24 | 509.57 | 203.66 | 133.19 | 70.48 | 0.00 | 0.00 |
Annual Sum or Average | 353.33 | 250.53 | 336.79 | 159.51 | 177.28 | 0.00 | 0.00 |
Minimum of Months | 139.24 | 51.39 | 203.66 | 111.93 | 70.48 | 0.00 | 0.00 |
Maximum of Months | 590.57 | 553.00 | 437.63 | 188.73 | 256.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 33.07 | 612.14 | 126.71 | 41.19 | 85.52 | 0.00 | 0.00 |
February | 82.67 | 482.35 | 180.07 | 72.79 | 107.27 | 0.00 | 0.00 |
March | 141.84 | 314.54 | 224.73 | 65.63 | 159.11 | 0.00 | 0.00 |
April | 294.24 | 212.20 | 313.99 | 128.14 | 185.85 | 0.00 | 0.00 |
May | 358.69 | 113.43 | 331.32 | 106.28 | 225.04 | 0.00 | 0.00 |
June | 486.95 | 69.04 | 387.61 | 138.68 | 248.94 | 0.00 | 0.00 |
July | 527.70 | 57.71 | 404.74 | 159.64 | 245.10 | 0.00 | 0.00 |
August | 456.92 | 71.72 | 350.57 | 131.15 | 219.42 | 0.00 | 0.00 |
September | 329.45 | 131.88 | 281.37 | 109.11 | 172.26 | 0.00 | 0.00 |
October | 169.75 | 226.47 | 199.37 | 72.08 | 127.29 | 0.00 | 0.00 |
November | 59.93 | 370.08 | 122.86 | 35.74 | 87.12 | 0.00 | 0.00 |
December | 32.24 | 547.68 | 91.35 | 35.06 | 56.29 | 0.00 | 0.00 |
Annual Sum or Average | 248.65 | 266.45 | 251.53 | 91.31 | 160.22 | 0.00 | 0.00 |
Minimum of Months | 32.24 | 57.71 | 91.35 | 35.06 | 56.29 | 0.00 | 0.00 |
Maximum of Months | 527.70 | 612.14 | 404.74 | 159.64 | 248.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.50 | 282.60 | 232.50 | 159.29 | 73.20 | 0.00 | 0.00 |
February | 221.92 | 227.32 | 250.63 | 170.04 | 80.59 | 0.00 | 0.00 |
March | 200.41 | 161.03 | 214.69 | 112.39 | 102.31 | 0.00 | 0.00 |
April | 205.57 | 113.08 | 191.40 | 87.72 | 103.68 | 0.00 | 0.00 |
May | 192.47 | 59.43 | 163.24 | 45.66 | 117.58 | 0.00 | 0.00 |
June | 209.70 | 33.36 | 155.83 | 31.12 | 124.71 | 0.00 | 0.00 |
July | 233.29 | 24.93 | 165.37 | 41.36 | 124.01 | 0.00 | 0.00 |
August | 257.72 | 32.61 | 183.25 | 63.46 | 119.79 | 0.00 | 0.00 |
September | 285.11 | 66.77 | 221.25 | 114.17 | 107.08 | 0.00 | 0.00 |
October | 261.62 | 116.21 | 238.43 | 150.32 | 88.11 | 0.00 | 0.00 |
November | 162.71 | 179.92 | 178.46 | 111.73 | 66.73 | 0.00 | 0.00 |
December | 173.98 | 260.98 | 190.02 | 143.91 | 46.11 | 0.00 | 0.00 |
Annual Sum or Average | 216.72 | 129.40 | 198.46 | 102.22 | 96.24 | 0.00 | 0.00 |
Minimum of Months | 162.71 | 24.93 | 155.83 | 31.12 | 46.11 | 0.00 | 0.00 |
Maximum of Months | 285.11 | 282.60 | 250.63 | 170.04 | 124.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.09 | 1704.61 | 177.87 | 0.00 | 177.87 | 0.00 | 0.00 |
February | 5.35 | 1370.07 | 225.50 | 0.00 | 225.50 | 0.00 | 0.00 |
March | 88.57 | 890.95 | 338.00 | 0.00 | 338.00 | 0.00 | 0.00 |
April | 218.25 | 590.02 | 391.74 | 3.17 | 388.57 | 0.00 | 0.00 |
May | 472.63 | 303.55 | 509.34 | 19.30 | 490.04 | 0.00 | 0.00 |
June | 733.05 | 189.12 | 596.04 | 55.24 | 540.80 | 0.00 | 0.00 |
July | 726.86 | 151.05 | 559.06 | 38.56 | 520.50 | 0.00 | 0.00 |
August | 604.21 | 189.41 | 468.43 | 9.49 | 458.94 | 0.00 | 0.00 |
September | 363.76 | 367.75 | 358.46 | 0.33 | 358.13 | 0.00 | 0.00 |
October | 115.50 | 637.42 | 266.18 | 0.00 | 266.18 | 0.00 | 0.00 |
November | 24.48 | 1043.81 | 186.19 | 0.00 | 186.19 | 0.00 | 0.00 |
December | 0.00 | 1514.39 | 120.78 | 0.00 | 120.78 | 0.00 | 0.00 |
Annual Sum or Average | 281.04 | 743.06 | 350.45 | 10.55 | 339.91 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 151.05 | 120.78 | 0.00 | 120.78 | 0.00 | 0.00 |
Maximum of Months | 733.05 | 1704.61 | 596.04 | 55.24 | 540.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.04 | 1734.10 | 177.87 | 0.00 | 177.87 | 0.00 | 0.00 |
February | 4.40 | 1402.52 | 225.50 | 0.00 | 225.50 | 0.00 | 0.00 |
March | 82.08 | 919.85 | 338.00 | 0.00 | 338.00 | 0.00 | 0.00 |
April | 208.73 | 613.75 | 391.74 | 3.17 | 388.57 | 0.00 | 0.00 |
May | 458.53 | 315.19 | 509.34 | 19.30 | 490.04 | 0.00 | 0.00 |
June | 718.71 | 197.97 | 596.04 | 55.24 | 540.80 | 0.00 | 0.00 |
July | 712.89 | 158.98 | 559.06 | 38.56 | 520.50 | 0.00 | 0.00 |
August | 591.36 | 198.66 | 468.43 | 9.49 | 458.94 | 0.00 | 0.00 |
September | 353.43 | 382.57 | 358.46 | 0.33 | 358.13 | 0.00 | 0.00 |
October | 106.68 | 662.99 | 266.18 | 0.00 | 266.18 | 0.00 | 0.00 |
November | 21.75 | 1074.33 | 186.19 | 0.00 | 186.19 | 0.00 | 0.00 |
December | 0.00 | 1545.47 | 120.78 | 0.00 | 120.78 | 0.00 | 0.00 |
Annual Sum or Average | 273.15 | 764.17 | 350.45 | 10.55 | 339.91 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 158.98 | 120.78 | 0.00 | 120.78 | 0.00 | 0.00 |
Maximum of Months | 718.71 | 1734.10 | 596.04 | 55.24 | 540.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.84 | 1144.34 | 386.69 | 191.70 | 194.99 | 0.00 | 0.00 |
February | 260.75 | 908.42 | 473.08 | 234.77 | 238.32 | 0.00 | 0.00 |
March | 451.50 | 631.51 | 561.35 | 222.11 | 339.24 | 0.00 | 0.00 |
April | 673.40 | 439.05 | 634.00 | 255.31 | 378.69 | 0.00 | 0.00 |
May | 973.52 | 240.54 | 749.53 | 281.21 | 468.32 | 0.00 | 0.00 |
June | 1196.40 | 154.15 | 812.83 | 299.82 | 513.01 | 0.00 | 0.00 |
July | 1253.16 | 122.41 | 820.88 | 323.72 | 497.16 | 0.00 | 0.00 |
August | 1110.50 | 148.81 | 721.53 | 272.89 | 448.64 | 0.00 | 0.00 |
September | 938.48 | 269.75 | 676.60 | 302.95 | 373.65 | 0.00 | 0.00 |
October | 521.85 | 453.39 | 501.10 | 227.58 | 273.53 | 0.00 | 0.00 |
November | 208.03 | 719.08 | 326.03 | 133.87 | 192.16 | 0.00 | 0.00 |
December | 138.14 | 1043.00 | 283.99 | 156.86 | 127.14 | 0.00 | 0.00 |
Annual Sum or Average | 659.24 | 521.10 | 579.47 | 241.89 | 337.58 | 0.00 | 0.00 |
Minimum of Months | 138.14 | 122.41 | 283.99 | 133.87 | 127.14 | 0.00 | 0.00 |
Maximum of Months | 1253.16 | 1144.34 | 820.88 | 323.72 | 513.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 422.19 | 1239.06 | 652.81 | 405.49 | 247.31 | 0.00 | 0.00 |
February | 508.58 | 988.03 | 715.30 | 432.85 | 282.45 | 0.00 | 0.00 |
March | 528.97 | 708.65 | 662.38 | 286.08 | 376.29 | 0.00 | 0.00 |
April | 589.90 | 513.59 | 621.51 | 224.38 | 397.13 | 0.00 | 0.00 |
May | 620.63 | 293.53 | 590.14 | 122.85 | 467.28 | 0.00 | 0.00 |
June | 741.54 | 184.23 | 601.00 | 98.15 | 502.84 | 0.00 | 0.00 |
July | 799.04 | 151.61 | 612.60 | 118.50 | 494.11 | 0.00 | 0.00 |
August | 825.49 | 190.84 | 627.06 | 164.79 | 462.26 | 0.00 | 0.00 |
September | 827.70 | 338.93 | 686.10 | 290.74 | 395.36 | 0.00 | 0.00 |
October | 696.19 | 522.65 | 698.19 | 382.65 | 315.54 | 0.00 | 0.00 |
November | 391.33 | 799.37 | 518.10 | 284.42 | 233.69 | 0.00 | 0.00 |
December | 392.13 | 1145.09 | 525.11 | 366.33 | 158.78 | 0.00 | 0.00 |
Annual Sum or Average | 612.54 | 587.79 | 625.33 | 263.83 | 361.50 | 0.00 | 0.00 |
Minimum of Months | 391.33 | 151.61 | 518.10 | 98.15 | 158.78 | 0.00 | 0.00 |
Maximum of Months | 827.70 | 1239.06 | 715.30 | 432.85 | 502.84 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.188028E+10 | 0.246222E+10 | 0.214752E+10 | 0.147136E+10 | 0.676156E+09 | 0.00 | 0.00 |
February | 0.191422E+10 | 0.178409E+10 | 0.209099E+10 | 0.141863E+10 | 0.672359E+09 | 0.00 | 0.00 |
March | 0.190170E+10 | 0.141895E+10 | 0.198306E+10 | 0.103808E+10 | 0.944974E+09 | 0.00 | 0.00 |
April | 0.184871E+10 | 0.100742E+10 | 0.171089E+10 | 0.784093E+09 | 0.926799E+09 | 0.00 | 0.00 |
May | 0.176477E+10 | 0.599988E+09 | 0.150779E+10 | 0.421788E+09 | 0.108600E+10 | 0.00 | 0.00 |
June | 0.180845E+10 | 0.379174E+09 | 0.139293E+10 | 0.278174E+09 | 0.111476E+10 | 0.00 | 0.00 |
July | 0.206934E+10 | 0.335735E+09 | 0.152747E+10 | 0.382015E+09 | 0.114546E+10 | 0.00 | 0.00 |
August | 0.231518E+10 | 0.410093E+09 | 0.169265E+10 | 0.586171E+09 | 0.110648E+10 | 0.00 | 0.00 |
September | 0.252321E+10 | 0.672931E+09 | 0.197774E+10 | 0.102054E+10 | 0.957200E+09 | 0.00 | 0.00 |
October | 0.244369E+10 | 0.107018E+10 | 0.220236E+10 | 0.138850E+10 | 0.813863E+09 | 0.00 | 0.00 |
November | 0.149012E+10 | 0.153386E+10 | 0.159520E+10 | 0.998741E+09 | 0.596460E+09 | 0.00 | 0.00 |
December | 0.164625E+10 | 0.229049E+10 | 0.175518E+10 | 0.132925E+10 | 0.425930E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.236059E+11 | 0.139651E+11 | 0.215838E+11 | 0.111173E+11 | 0.104664E+11 | 0.00 | 0.00 |
Minimum of Months | 0.149012E+10 | 0.335735E+09 | 0.139293E+10 | 0.278174E+09 | 0.425930E+09 | 0.00 | 0.00 |
Maximum of Months | 0.252321E+10 | 0.246222E+10 | 0.220236E+10 | 0.147136E+10 | 0.114546E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.527564E+10 | 0.695911E+10 | 0.604728E+10 | 0.414326E+10 | 0.190401E+10 | 0.00 | 0.00 |
February | 0.537270E+10 | 0.506250E+10 | 0.588809E+10 | 0.399478E+10 | 0.189332E+10 | 0.00 | 0.00 |
March | 0.534888E+10 | 0.402401E+10 | 0.558415E+10 | 0.292317E+10 | 0.266098E+10 | 0.00 | 0.00 |
April | 0.522628E+10 | 0.283834E+10 | 0.481776E+10 | 0.220795E+10 | 0.260981E+10 | 0.00 | 0.00 |
May | 0.507157E+10 | 0.162661E+10 | 0.424584E+10 | 0.118773E+10 | 0.305812E+10 | 0.00 | 0.00 |
June | 0.523147E+10 | 0.990402E+09 | 0.392240E+10 | 0.783319E+09 | 0.313908E+10 | 0.00 | 0.00 |
July | 0.599152E+10 | 0.839772E+09 | 0.430126E+10 | 0.107573E+10 | 0.322553E+10 | 0.00 | 0.00 |
August | 0.665213E+10 | 0.105069E+10 | 0.476640E+10 | 0.165062E+10 | 0.311578E+10 | 0.00 | 0.00 |
September | 0.715391E+10 | 0.183387E+10 | 0.556919E+10 | 0.287378E+10 | 0.269541E+10 | 0.00 | 0.00 |
October | 0.688434E+10 | 0.302484E+10 | 0.620170E+10 | 0.390991E+10 | 0.229179E+10 | 0.00 | 0.00 |
November | 0.418076E+10 | 0.435731E+10 | 0.449198E+10 | 0.281239E+10 | 0.167959E+10 | 0.00 | 0.00 |
December | 0.462644E+10 | 0.647676E+10 | 0.494247E+10 | 0.374308E+10 | 0.119939E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.670156E+11 | 0.390842E+11 | 0.607785E+11 | 0.313057E+11 | 0.294728E+11 | 0.00 | 0.00 |
Minimum of Months | 0.418076E+10 | 0.839772E+09 | 0.392240E+10 | 0.783319E+09 | 0.119939E+10 | 0.00 | 0.00 |
Maximum of Months | 0.715391E+10 | 0.695911E+10 | 0.620170E+10 | 0.414326E+10 | 0.322553E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.693253E+10 | 0.939487E+10 | 0.785576E+10 | 0.538234E+10 | 0.247342E+10 | 0.00 | 0.00 |
February | 0.707430E+10 | 0.685659E+10 | 0.764897E+10 | 0.518944E+10 | 0.245953E+10 | 0.00 | 0.00 |
March | 0.704365E+10 | 0.551689E+10 | 0.725413E+10 | 0.379736E+10 | 0.345677E+10 | 0.00 | 0.00 |
April | 0.689008E+10 | 0.392953E+10 | 0.625854E+10 | 0.286826E+10 | 0.339029E+10 | 0.00 | 0.00 |
May | 0.662793E+10 | 0.230055E+10 | 0.551559E+10 | 0.154292E+10 | 0.397267E+10 | 0.00 | 0.00 |
June | 0.683982E+10 | 0.142011E+10 | 0.509542E+10 | 0.101758E+10 | 0.407784E+10 | 0.00 | 0.00 |
July | 0.784380E+10 | 0.120411E+10 | 0.558759E+10 | 0.139743E+10 | 0.419015E+10 | 0.00 | 0.00 |
August | 0.873039E+10 | 0.148593E+10 | 0.619182E+10 | 0.214425E+10 | 0.404758E+10 | 0.00 | 0.00 |
September | 0.940984E+10 | 0.255753E+10 | 0.723470E+10 | 0.373320E+10 | 0.350149E+10 | 0.00 | 0.00 |
October | 0.904989E+10 | 0.417888E+10 | 0.805636E+10 | 0.507920E+10 | 0.297716E+10 | 0.00 | 0.00 |
November | 0.547966E+10 | 0.598101E+10 | 0.583534E+10 | 0.365345E+10 | 0.218188E+10 | 0.00 | 0.00 |
December | 0.608469E+10 | 0.879513E+10 | 0.642055E+10 | 0.486248E+10 | 0.155808E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.880066E+11 | 0.536211E+11 | 0.789548E+11 | 0.406679E+11 | 0.382869E+11 | 0.00 | 0.00 |
Minimum of Months | 0.547966E+10 | 0.120411E+10 | 0.509542E+10 | 0.101758E+10 | 0.155808E+10 | 0.00 | 0.00 |
Maximum of Months | 0.940984E+10 | 0.939487E+10 | 0.805636E+10 | 0.538234E+10 | 0.419015E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.400399E+09 | 0.147993E+10 | 0.695928E+09 | 0.401247E+09 | 0.294681E+09 | 0.00 | 0.00 |
February | 0.539141E+09 | 0.106908E+10 | 0.771104E+09 | 0.456582E+09 | 0.314522E+09 | 0.00 | 0.00 |
March | 0.702461E+09 | 0.819592E+09 | 0.864675E+09 | 0.381017E+09 | 0.483659E+09 | 0.00 | 0.00 |
April | 0.104700E+10 | 0.551921E+09 | 0.100709E+10 | 0.485996E+09 | 0.521092E+09 | 0.00 | 0.00 |
May | 0.115075E+10 | 0.306103E+09 | 0.990618E+09 | 0.360659E+09 | 0.629960E+09 | 0.00 | 0.00 |
June | 0.138827E+10 | 0.174192E+09 | 0.105939E+10 | 0.393993E+09 | 0.665401E+09 | 0.00 | 0.00 |
July | 0.159087E+10 | 0.140774E+09 | 0.117214E+10 | 0.488341E+09 | 0.683797E+09 | 0.00 | 0.00 |
August | 0.148702E+10 | 0.178021E+09 | 0.109439E+10 | 0.463539E+09 | 0.630854E+09 | 0.00 | 0.00 |
September | 0.122947E+10 | 0.336728E+09 | 0.987615E+09 | 0.484469E+09 | 0.503146E+09 | 0.00 | 0.00 |
October | 0.877207E+09 | 0.598895E+09 | 0.867581E+09 | 0.467585E+09 | 0.399996E+09 | 0.00 | 0.00 |
November | 0.414749E+09 | 0.907183E+09 | 0.564912E+09 | 0.290113E+09 | 0.274799E+09 | 0.00 | 0.00 |
December | 0.372859E+09 | 0.136490E+10 | 0.545492E+09 | 0.356729E+09 | 0.188763E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112002E+11 | 0.792732E+10 | 0.106209E+11 | 0.503027E+10 | 0.559067E+10 | 0.00 | 0.00 |
Minimum of Months | 0.372859E+09 | 0.140774E+09 | 0.545492E+09 | 0.290113E+09 | 0.188763E+09 | 0.00 | 0.00 |
Maximum of Months | 0.159087E+10 | 0.147993E+10 | 0.117214E+10 | 0.488341E+09 | 0.683797E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 89238137.28 | 0.163732E+10 | 0.339385E+09 | 0.110333E+09 | 0.229052E+09 | 0.00 | 0.00 |
February | 0.200844E+09 | 0.116813E+10 | 0.435613E+09 | 0.176094E+09 | 0.259519E+09 | 0.00 | 0.00 |
March | 0.380293E+09 | 0.844093E+09 | 0.601923E+09 | 0.175772E+09 | 0.426152E+09 | 0.00 | 0.00 |
April | 0.767668E+09 | 0.552084E+09 | 0.813874E+09 | 0.332140E+09 | 0.481734E+09 | 0.00 | 0.00 |
May | 0.970915E+09 | 0.303122E+09 | 0.887395E+09 | 0.284647E+09 | 0.602748E+09 | 0.00 | 0.00 |
June | 0.127222E+10 | 0.178313E+09 | 0.100470E+10 | 0.359450E+09 | 0.645248E+09 | 0.00 | 0.00 |
July | 0.142332E+10 | 0.153500E+09 | 0.108405E+10 | 0.427566E+09 | 0.656483E+09 | 0.00 | 0.00 |
August | 0.123233E+10 | 0.190749E+09 | 0.938965E+09 | 0.351273E+09 | 0.587692E+09 | 0.00 | 0.00 |
September | 0.856675E+09 | 0.345258E+09 | 0.729318E+09 | 0.282812E+09 | 0.446506E+09 | 0.00 | 0.00 |
October | 0.454186E+09 | 0.611309E+09 | 0.533987E+09 | 0.193056E+09 | 0.340931E+09 | 0.00 | 0.00 |
November | 0.154077E+09 | 0.962748E+09 | 0.318460E+09 | 92645012.94 | 0.225815E+09 | 0.00 | 0.00 |
December | 86113421.75 | 0.146597E+10 | 0.244676E+09 | 93913323.71 | 0.150763E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.788788E+10 | 0.841260E+10 | 0.793234E+10 | 0.287970E+10 | 0.505264E+10 | 0.00 | 0.00 |
Minimum of Months | 86113421.75 | 0.153500E+09 | 0.244676E+09 | 92645012.94 | 0.150763E+09 | 0.00 | 0.00 |
Maximum of Months | 0.142332E+10 | 0.163732E+10 | 0.108405E+10 | 0.427566E+09 | 0.656483E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.307004E+09 | 0.356490E+09 | 0.339614E+09 | 0.232685E+09 | 0.106929E+09 | 0.00 | 0.00 |
February | 0.304747E+09 | 0.284051E+09 | 0.330675E+09 | 0.224346E+09 | 0.106329E+09 | 0.00 | 0.00 |
March | 0.292621E+09 | 0.241040E+09 | 0.313606E+09 | 0.164165E+09 | 0.149441E+09 | 0.00 | 0.00 |
April | 0.275555E+09 | 0.206639E+09 | 0.270566E+09 | 0.123998E+09 | 0.146568E+09 | 0.00 | 0.00 |
May | 0.251051E+09 | 0.134481E+09 | 0.238447E+09 | 66702456.33 | 0.171745E+09 | 0.00 | 0.00 |
June | 0.262460E+09 | 87932872.77 | 0.220283E+09 | 43991018.65 | 0.176292E+09 | 0.00 | 0.00 |
July | 0.305084E+09 | 76149927.23 | 0.241560E+09 | 60412738.75 | 0.181147E+09 | 0.00 | 0.00 |
August | 0.344373E+09 | 91509321.99 | 0.267682E+09 | 92698360.87 | 0.174983E+09 | 0.00 | 0.00 |
September | 0.378518E+09 | 0.144540E+09 | 0.312766E+09 | 0.161391E+09 | 0.151375E+09 | 0.00 | 0.00 |
October | 0.360208E+09 | 0.225096E+09 | 0.348287E+09 | 0.219580E+09 | 0.128707E+09 | 0.00 | 0.00 |
November | 0.224007E+09 | 0.275047E+09 | 0.252269E+09 | 0.157943E+09 | 94326015.77 | 0.00 | 0.00 |
December | 0.266570E+09 | 0.336083E+09 | 0.277569E+09 | 0.210211E+09 | 67357898.11 | 0.00 | 0.00 |
Annual Sum or Average | 0.357220E+10 | 0.245906E+10 | 0.341332E+10 | 0.175812E+10 | 0.165520E+10 | 0.00 | 0.00 |
Minimum of Months | 0.224007E+09 | 76149927.23 | 0.220283E+09 | 43991018.65 | 67357898.11 | 0.00 | 0.00 |
Maximum of Months | 0.378518E+09 | 0.356490E+09 | 0.348287E+09 | 0.232685E+09 | 0.181147E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 82228.05 | 0.502783E+09 | 54454376.31 | 0.00 | 54454376.31 | 0.00 | 0.00 |
February | 2139097.70 | 0.362905E+09 | 62356493.82 | 0.00 | 62356493.82 | 0.00 | 0.00 |
March | 30280663.88 | 0.256880E+09 | 0.103480E+09 | 918.91 | 0.103479E+09 | 0.00 | 0.00 |
April | 68308240.65 | 0.160337E+09 | 0.116064E+09 | 938704.73 | 0.115125E+09 | 0.00 | 0.00 |
May | 0.150540E+09 | 81160566.09 | 0.155937E+09 | 5907417.17 | 0.150030E+09 | 0.00 | 0.00 |
June | 0.222358E+09 | 46282748.67 | 0.176594E+09 | 16367124.49 | 0.160226E+09 | 0.00 | 0.00 |
July | 0.226901E+09 | 37540288.44 | 0.171159E+09 | 11806394.60 | 0.159353E+09 | 0.00 | 0.00 |
August | 0.189061E+09 | 47949709.85 | 0.143411E+09 | 2904070.99 | 0.140507E+09 | 0.00 | 0.00 |
September | 0.110948E+09 | 96237938.35 | 0.106205E+09 | 97261.05 | 0.106108E+09 | 0.00 | 0.00 |
October | 38793910.66 | 0.180317E+09 | 81491445.51 | 0.00 | 81491445.51 | 0.00 | 0.00 |
November | 8406295.31 | 0.292431E+09 | 55165193.61 | 0.00 | 55165193.61 | 0.00 | 0.00 |
December | 4936.49 | 0.444465E+09 | 36976274.53 | 0.00 | 36976274.53 | 0.00 | 0.00 |
Annual Sum or Average | 0.104782E+10 | 0.250929E+10 | 0.126329E+10 | 38021891.94 | 0.122527E+10 | 0.00 | 0.00 |
Minimum of Months | 4936.49 | 37540288.44 | 36976274.53 | 0.00 | 36976274.53 | 0.00 | 0.00 |
Maximum of Months | 0.226901E+09 | 0.502783E+09 | 0.176594E+09 | 16367124.49 | 0.160226E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.401918E+09 | 0.147210E+10 | 0.696146E+09 | 0.402194E+09 | 0.293953E+09 | 0.00 | 0.00 |
February | 0.492185E+09 | 0.105294E+10 | 0.740012E+09 | 0.424229E+09 | 0.315782E+09 | 0.00 | 0.00 |
March | 0.717189E+09 | 0.807860E+09 | 0.883169E+09 | 0.400086E+09 | 0.483083E+09 | 0.00 | 0.00 |
April | 0.916193E+09 | 0.540710E+09 | 0.918312E+09 | 0.407829E+09 | 0.510482E+09 | 0.00 | 0.00 |
May | 0.121725E+10 | 0.289997E+09 | 0.105544E+10 | 0.414625E+09 | 0.640814E+09 | 0.00 | 0.00 |
June | 0.140869E+10 | 0.164831E+09 | 0.108083E+10 | 0.405866E+09 | 0.674963E+09 | 0.00 | 0.00 |
July | 0.153952E+10 | 0.131706E+09 | 0.114342E+10 | 0.463936E+09 | 0.679485E+09 | 0.00 | 0.00 |
August | 0.140714E+10 | 0.166805E+09 | 0.104404E+10 | 0.421608E+09 | 0.622432E+09 | 0.00 | 0.00 |
September | 0.124712E+10 | 0.329468E+09 | 0.100607E+10 | 0.493475E+09 | 0.512590E+09 | 0.00 | 0.00 |
October | 0.827672E+09 | 0.588022E+09 | 0.837902E+09 | 0.442046E+09 | 0.395857E+09 | 0.00 | 0.00 |
November | 0.383161E+09 | 0.896666E+09 | 0.545777E+09 | 0.272238E+09 | 0.273539E+09 | 0.00 | 0.00 |
December | 0.346046E+09 | 0.135073E+10 | 0.530745E+09 | 0.341475E+09 | 0.189270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109041E+11 | 0.779184E+10 | 0.104819E+11 | 0.488961E+10 | 0.559225E+10 | 0.00 | 0.00 |
Minimum of Months | 0.346046E+09 | 0.131706E+09 | 0.530745E+09 | 0.272238E+09 | 0.189270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.153952E+10 | 0.147210E+10 | 0.114342E+10 | 0.493475E+09 | 0.679485E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 70874824.82 | 0.160918E+10 | 0.339603E+09 | 0.111280E+09 | 0.228323E+09 | 0.00 | 0.00 |
February | 0.147782E+09 | 0.114566E+10 | 0.404521E+09 | 0.143741E+09 | 0.260780E+09 | 0.00 | 0.00 |
March | 0.387309E+09 | 0.824181E+09 | 0.620417E+09 | 0.194841E+09 | 0.425576E+09 | 0.00 | 0.00 |
April | 0.636669E+09 | 0.538416E+09 | 0.725098E+09 | 0.253974E+09 | 0.471124E+09 | 0.00 | 0.00 |
May | 0.104526E+10 | 0.290133E+09 | 0.952216E+09 | 0.338613E+09 | 0.613603E+09 | 0.00 | 0.00 |
June | 0.129718E+10 | 0.171418E+09 | 0.102613E+10 | 0.371323E+09 | 0.654811E+09 | 0.00 | 0.00 |
July | 0.137224E+10 | 0.144021E+09 | 0.105533E+10 | 0.403161E+09 | 0.652171E+09 | 0.00 | 0.00 |
August | 0.115520E+10 | 0.178458E+09 | 0.888612E+09 | 0.309341E+09 | 0.579271E+09 | 0.00 | 0.00 |
September | 0.871796E+09 | 0.334251E+09 | 0.747768E+09 | 0.291818E+09 | 0.455951E+09 | 0.00 | 0.00 |
October | 0.397122E+09 | 0.590427E+09 | 0.504308E+09 | 0.167516E+09 | 0.336792E+09 | 0.00 | 0.00 |
November | 0.113761E+09 | 0.943239E+09 | 0.299325E+09 | 74769286.73 | 0.224556E+09 | 0.00 | 0.00 |
December | 52823347.29 | 0.144661E+10 | 0.229929E+09 | 78658898.99 | 0.151270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.754801E+10 | 0.821600E+10 | 0.779326E+10 | 0.273904E+10 | 0.505423E+10 | 0.00 | 0.00 |
Minimum of Months | 52823347.29 | 0.144021E+09 | 0.229929E+09 | 74769286.73 | 0.151270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137224E+10 | 0.160918E+10 | 0.105533E+10 | 0.403161E+09 | 0.654811E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.483906E+09 | 0.188121E+10 | 0.853816E+09 | 0.504164E+09 | 0.349653E+09 | 0.00 | 0.00 |
February | 0.545570E+09 | 0.135808E+10 | 0.851566E+09 | 0.486095E+09 | 0.365471E+09 | 0.00 | 0.00 |
March | 0.690046E+09 | 0.105500E+10 | 0.903669E+09 | 0.355701E+09 | 0.547969E+09 | 0.00 | 0.00 |
April | 0.789888E+09 | 0.712148E+09 | 0.837674E+09 | 0.270703E+09 | 0.566971E+09 | 0.00 | 0.00 |
May | 0.942499E+09 | 0.386586E+09 | 0.854461E+09 | 0.157323E+09 | 0.697137E+09 | 0.00 | 0.00 |
June | 0.110728E+10 | 0.234898E+09 | 0.859853E+09 | 0.130773E+09 | 0.729080E+09 | 0.00 | 0.00 |
July | 0.120533E+10 | 0.203229E+09 | 0.894182E+09 | 0.156474E+09 | 0.737707E+09 | 0.00 | 0.00 |
August | 0.120917E+10 | 0.253920E+09 | 0.890668E+09 | 0.207143E+09 | 0.683526E+09 | 0.00 | 0.00 |
September | 0.111178E+10 | 0.457521E+09 | 0.907752E+09 | 0.349900E+09 | 0.557852E+09 | 0.00 | 0.00 |
October | 0.920440E+09 | 0.750842E+09 | 0.931179E+09 | 0.475768E+09 | 0.455410E+09 | 0.00 | 0.00 |
November | 0.472935E+09 | 0.115212E+10 | 0.666104E+09 | 0.342219E+09 | 0.323885E+09 | 0.00 | 0.00 |
December | 0.460257E+09 | 0.172990E+10 | 0.681517E+09 | 0.455468E+09 | 0.226049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.993911E+10 | 0.101755E+11 | 0.101324E+11 | 0.389173E+10 | 0.624071E+10 | 0.00 | 0.00 |
Minimum of Months | 0.460257E+09 | 0.203229E+09 | 0.666104E+09 | 0.130773E+09 | 0.226049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120917E+10 | 0.188121E+10 | 0.931179E+09 | 0.504164E+09 | 0.737707E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.398290E+09 | 0.148116E+10 | 0.695928E+09 | 0.401247E+09 | 0.294681E+09 | 0.00 | 0.00 |
February | 0.536373E+09 | 0.106738E+10 | 0.771104E+09 | 0.456582E+09 | 0.314522E+09 | 0.00 | 0.00 |
March | 0.699879E+09 | 0.818034E+09 | 0.864675E+09 | 0.381017E+09 | 0.483659E+09 | 0.00 | 0.00 |
April | 0.104011E+10 | 0.549177E+09 | 0.100709E+10 | 0.485996E+09 | 0.521092E+09 | 0.00 | 0.00 |
May | 0.114165E+10 | 0.304257E+09 | 0.990618E+09 | 0.360659E+09 | 0.629960E+09 | 0.00 | 0.00 |
June | 0.137998E+10 | 0.171372E+09 | 0.105939E+10 | 0.393993E+09 | 0.665401E+09 | 0.00 | 0.00 |
July | 0.158179E+10 | 0.137632E+09 | 0.117214E+10 | 0.488341E+09 | 0.683797E+09 | 0.00 | 0.00 |
August | 0.147834E+10 | 0.175143E+09 | 0.109439E+10 | 0.463539E+09 | 0.630854E+09 | 0.00 | 0.00 |
September | 0.122471E+10 | 0.331933E+09 | 0.987615E+09 | 0.484469E+09 | 0.503146E+09 | 0.00 | 0.00 |
October | 0.873980E+09 | 0.595595E+09 | 0.867581E+09 | 0.467585E+09 | 0.399996E+09 | 0.00 | 0.00 |
November | 0.414672E+09 | 0.904288E+09 | 0.564912E+09 | 0.290113E+09 | 0.274799E+09 | 0.00 | 0.00 |
December | 0.372939E+09 | 0.136484E+10 | 0.545492E+09 | 0.356729E+09 | 0.188763E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111427E+11 | 0.790082E+10 | 0.106209E+11 | 0.503027E+10 | 0.559067E+10 | 0.00 | 0.00 |
Minimum of Months | 0.372939E+09 | 0.137632E+09 | 0.545492E+09 | 0.290113E+09 | 0.188763E+09 | 0.00 | 0.00 |
Maximum of Months | 0.158179E+10 | 0.148116E+10 | 0.117214E+10 | 0.488341E+09 | 0.683797E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 88573918.75 | 0.163956E+10 | 0.339385E+09 | 0.110333E+09 | 0.229052E+09 | 0.00 | 0.00 |
February | 0.200001E+09 | 0.116690E+10 | 0.435613E+09 | 0.176094E+09 | 0.259519E+09 | 0.00 | 0.00 |
March | 0.379894E+09 | 0.842458E+09 | 0.601923E+09 | 0.175772E+09 | 0.426152E+09 | 0.00 | 0.00 |
April | 0.762665E+09 | 0.550014E+09 | 0.813874E+09 | 0.332140E+09 | 0.481734E+09 | 0.00 | 0.00 |
May | 0.960719E+09 | 0.303816E+09 | 0.887395E+09 | 0.284647E+09 | 0.602748E+09 | 0.00 | 0.00 |
June | 0.126218E+10 | 0.178951E+09 | 0.100470E+10 | 0.359450E+09 | 0.645248E+09 | 0.00 | 0.00 |
July | 0.141339E+10 | 0.154566E+09 | 0.108405E+10 | 0.427566E+09 | 0.656483E+09 | 0.00 | 0.00 |
August | 0.122381E+10 | 0.192100E+09 | 0.938965E+09 | 0.351273E+09 | 0.587692E+09 | 0.00 | 0.00 |
September | 0.853941E+09 | 0.341827E+09 | 0.729318E+09 | 0.282812E+09 | 0.446506E+09 | 0.00 | 0.00 |
October | 0.454646E+09 | 0.606578E+09 | 0.533987E+09 | 0.193056E+09 | 0.340931E+09 | 0.00 | 0.00 |
November | 0.155331E+09 | 0.959246E+09 | 0.318460E+09 | 92645012.94 | 0.225815E+09 | 0.00 | 0.00 |
December | 86353242.26 | 0.146690E+10 | 0.244676E+09 | 93913323.71 | 0.150763E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.784151E+10 | 0.840292E+10 | 0.793234E+10 | 0.287970E+10 | 0.505264E+10 | 0.00 | 0.00 |
Minimum of Months | 86353242.26 | 0.154566E+09 | 0.244676E+09 | 92645012.94 | 0.150763E+09 | 0.00 | 0.00 |
Maximum of Months | 0.141339E+10 | 0.163956E+10 | 0.108405E+10 | 0.427566E+09 | 0.656483E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.526295E+09 | 0.756909E+09 | 0.622720E+09 | 0.426653E+09 | 0.196067E+09 | 0.00 | 0.00 |
February | 0.536862E+09 | 0.549937E+09 | 0.606329E+09 | 0.411363E+09 | 0.194966E+09 | 0.00 | 0.00 |
March | 0.536784E+09 | 0.431293E+09 | 0.575031E+09 | 0.301014E+09 | 0.274017E+09 | 0.00 | 0.00 |
April | 0.532828E+09 | 0.293110E+09 | 0.496112E+09 | 0.227364E+09 | 0.268748E+09 | 0.00 | 0.00 |
May | 0.515511E+09 | 0.159174E+09 | 0.437219E+09 | 0.122306E+09 | 0.314913E+09 | 0.00 | 0.00 |
June | 0.543531E+09 | 86477507.99 | 0.403913E+09 | 80662351.74 | 0.323251E+09 | 0.00 | 0.00 |
July | 0.624842E+09 | 66781319.71 | 0.442927E+09 | 0.110773E+09 | 0.332153E+09 | 0.00 | 0.00 |
August | 0.690286E+09 | 87337200.72 | 0.490824E+09 | 0.169973E+09 | 0.320851E+09 | 0.00 | 0.00 |
September | 0.738997E+09 | 0.173065E+09 | 0.573491E+09 | 0.295928E+09 | 0.277563E+09 | 0.00 | 0.00 |
October | 0.700725E+09 | 0.311261E+09 | 0.638622E+09 | 0.402624E+09 | 0.235999E+09 | 0.00 | 0.00 |
November | 0.421732E+09 | 0.466347E+09 | 0.462563E+09 | 0.289606E+09 | 0.172957E+09 | 0.00 | 0.00 |
December | 0.466000E+09 | 0.699021E+09 | 0.508953E+09 | 0.385444E+09 | 0.123508E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.683439E+10 | 0.408071E+10 | 0.625870E+10 | 0.322371E+10 | 0.303499E+10 | 0.00 | 0.00 |
Minimum of Months | 0.421732E+09 | 66781319.71 | 0.403913E+09 | 80662351.74 | 0.123508E+09 | 0.00 | 0.00 |
Maximum of Months | 0.738997E+09 | 0.756909E+09 | 0.638622E+09 | 0.426653E+09 | 0.332153E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 227799.12 | 0.456562E+10 | 0.476395E+09 | 0.00 | 0.476395E+09 | 0.00 | 0.00 |
February | 12941601.32 | 0.331447E+10 | 0.545526E+09 | 0.00 | 0.545526E+09 | 0.00 | 0.00 |
March | 0.237224E+09 | 0.238633E+10 | 0.905297E+09 | 8039.10 | 0.905289E+09 | 0.00 | 0.00 |
April | 0.565706E+09 | 0.152933E+10 | 0.101539E+10 | 8212266.70 | 0.100718E+10 | 0.00 | 0.00 |
May | 0.126590E+10 | 0.813040E+09 | 0.136422E+10 | 51681092.00 | 0.131253E+10 | 0.00 | 0.00 |
June | 0.190006E+10 | 0.490201E+09 | 0.154493E+10 | 0.143188E+09 | 0.140174E+10 | 0.00 | 0.00 |
July | 0.194682E+10 | 0.404579E+09 | 0.149739E+10 | 0.103288E+09 | 0.139410E+10 | 0.00 | 0.00 |
August | 0.161832E+10 | 0.507311E+09 | 0.125463E+10 | 25406291.07 | 0.122923E+10 | 0.00 | 0.00 |
September | 0.942872E+09 | 0.953211E+09 | 0.929134E+09 | 850889.14 | 0.928283E+09 | 0.00 | 0.00 |
October | 0.309356E+09 | 0.170726E+10 | 0.712929E+09 | 0.00 | 0.712929E+09 | 0.00 | 0.00 |
November | 63452245.62 | 0.270557E+10 | 0.482613E+09 | 0.00 | 0.482613E+09 | 0.00 | 0.00 |
December | 0.00 | 0.405614E+10 | 0.323487E+09 | 0.00 | 0.323487E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.886287E+10 | 0.234331E+11 | 0.110519E+11 | 0.332635E+09 | 0.107193E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.404579E+09 | 0.323487E+09 | 0.00 | 0.323487E+09 | 0.00 | 0.00 |
Maximum of Months | 0.194682E+10 | 0.456562E+10 | 0.154493E+10 | 0.143188E+09 | 0.140174E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 102009.57 | 0.464461E+10 | 0.476395E+09 | 0.00 | 0.476395E+09 | 0.00 | 0.00 |
February | 10654505.13 | 0.339298E+10 | 0.545526E+09 | 0.00 | 0.545526E+09 | 0.00 | 0.00 |
March | 0.219844E+09 | 0.246374E+10 | 0.905297E+09 | 8039.10 | 0.905289E+09 | 0.00 | 0.00 |
April | 0.541027E+09 | 0.159084E+10 | 0.101539E+10 | 8212266.70 | 0.100718E+10 | 0.00 | 0.00 |
May | 0.122813E+10 | 0.844217E+09 | 0.136422E+10 | 51681092.00 | 0.131253E+10 | 0.00 | 0.00 |
June | 0.186289E+10 | 0.513136E+09 | 0.154493E+10 | 0.143188E+09 | 0.140174E+10 | 0.00 | 0.00 |
July | 0.190942E+10 | 0.425817E+09 | 0.149739E+10 | 0.103288E+09 | 0.139410E+10 | 0.00 | 0.00 |
August | 0.158391E+10 | 0.532096E+09 | 0.125463E+10 | 25406291.07 | 0.122923E+10 | 0.00 | 0.00 |
September | 0.916085E+09 | 0.991610E+09 | 0.929134E+09 | 850889.14 | 0.928283E+09 | 0.00 | 0.00 |
October | 0.285732E+09 | 0.177574E+10 | 0.712929E+09 | 0.00 | 0.712929E+09 | 0.00 | 0.00 |
November | 56364047.51 | 0.278466E+10 | 0.482613E+09 | 0.00 | 0.482613E+09 | 0.00 | 0.00 |
December | 0.00 | 0.413939E+10 | 0.323487E+09 | 0.00 | 0.323487E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.861416E+10 | 0.240988E+11 | 0.110519E+11 | 0.332635E+09 | 0.107193E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.425817E+09 | 0.323487E+09 | 0.00 | 0.323487E+09 | 0.00 | 0.00 |
Maximum of Months | 0.190942E+10 | 0.464461E+10 | 0.154493E+10 | 0.143188E+09 | 0.140174E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.425441E+09 | 0.306499E+10 | 0.103571E+10 | 0.513458E+09 | 0.522253E+09 | 0.00 | 0.00 |
February | 0.630814E+09 | 0.219764E+10 | 0.114449E+10 | 0.567950E+09 | 0.576536E+09 | 0.00 | 0.00 |
March | 0.120931E+10 | 0.169145E+10 | 0.150352E+10 | 0.594900E+09 | 0.908617E+09 | 0.00 | 0.00 |
April | 0.174546E+10 | 0.113801E+10 | 0.164333E+10 | 0.661767E+09 | 0.981560E+09 | 0.00 | 0.00 |
May | 0.260749E+10 | 0.644261E+09 | 0.200755E+10 | 0.753191E+09 | 0.125436E+10 | 0.00 | 0.00 |
June | 0.310108E+10 | 0.399555E+09 | 0.210685E+10 | 0.777139E+09 | 0.132971E+10 | 0.00 | 0.00 |
July | 0.335646E+10 | 0.327850E+09 | 0.219863E+10 | 0.867043E+09 | 0.133159E+10 | 0.00 | 0.00 |
August | 0.297435E+10 | 0.398575E+09 | 0.193255E+10 | 0.730906E+09 | 0.120165E+10 | 0.00 | 0.00 |
September | 0.243253E+10 | 0.699190E+09 | 0.175375E+10 | 0.785251E+09 | 0.968495E+09 | 0.00 | 0.00 |
October | 0.139772E+10 | 0.121435E+10 | 0.134215E+10 | 0.609538E+09 | 0.732615E+09 | 0.00 | 0.00 |
November | 0.539220E+09 | 0.186386E+10 | 0.845069E+09 | 0.346996E+09 | 0.498073E+09 | 0.00 | 0.00 |
December | 0.369993E+09 | 0.279358E+10 | 0.760648E+09 | 0.420122E+09 | 0.340525E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.207899E+11 | 0.164333E+11 | 0.182742E+11 | 0.762826E+10 | 0.106460E+11 | 0.00 | 0.00 |
Minimum of Months | 0.369993E+09 | 0.327850E+09 | 0.760648E+09 | 0.346996E+09 | 0.340525E+09 | 0.00 | 0.00 |
Maximum of Months | 0.335646E+10 | 0.306499E+10 | 0.219863E+10 | 0.867043E+09 | 0.133159E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113080E+10 | 0.331871E+10 | 0.174848E+10 | 0.108607E+10 | 0.662407E+09 | 0.00 | 0.00 |
February | 0.123036E+10 | 0.239024E+10 | 0.173045E+10 | 0.104715E+10 | 0.683304E+09 | 0.00 | 0.00 |
March | 0.141679E+10 | 0.189805E+10 | 0.177411E+10 | 0.766249E+09 | 0.100786E+10 | 0.00 | 0.00 |
April | 0.152903E+10 | 0.133122E+10 | 0.161096E+10 | 0.581583E+09 | 0.102937E+10 | 0.00 | 0.00 |
May | 0.166229E+10 | 0.786198E+09 | 0.158062E+10 | 0.329053E+09 | 0.125157E+10 | 0.00 | 0.00 |
June | 0.192207E+10 | 0.477519E+09 | 0.155779E+10 | 0.254415E+09 | 0.130337E+10 | 0.00 | 0.00 |
July | 0.214015E+10 | 0.406079E+09 | 0.164080E+10 | 0.317387E+09 | 0.132341E+10 | 0.00 | 0.00 |
August | 0.221098E+10 | 0.511146E+09 | 0.167951E+10 | 0.441384E+09 | 0.123812E+10 | 0.00 | 0.00 |
September | 0.214539E+10 | 0.878515E+09 | 0.177836E+10 | 0.753592E+09 | 0.102477E+10 | 0.00 | 0.00 |
October | 0.186467E+10 | 0.139986E+10 | 0.187004E+10 | 0.102490E+10 | 0.845140E+09 | 0.00 | 0.00 |
November | 0.101432E+10 | 0.207197E+10 | 0.134292E+10 | 0.737208E+09 | 0.605712E+09 | 0.00 | 0.00 |
December | 0.105028E+10 | 0.306701E+10 | 0.140646E+10 | 0.981169E+09 | 0.425288E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193171E+11 | 0.185365E+11 | 0.197205E+11 | 0.832015E+10 | 0.114003E+11 | 0.00 | 0.00 |
Minimum of Months | 0.101432E+10 | 0.406079E+09 | 0.134292E+10 | 0.254415E+09 | 0.425288E+09 | 0.00 | 0.00 |
Maximum of Months | 0.221098E+10 | 0.331871E+10 | 0.187004E+10 | 0.108607E+10 | 0.132341E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.129252E+12 | -0.127478E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177365E+10 | 81.42 | 0.00 | 0.00 |
February | 0.116897E+12 | -0.115286E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.161092E+10 | 81.13 | 0.00 | 0.00 |
March | 0.129344E+12 | -0.127554E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179057E+10 | 81.27 | 0.00 | 0.00 |
April | 0.124881E+12 | -0.123121E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.176038E+10 | 81.84 | 0.00 | 0.00 |
May | 0.125630E+12 | -0.123809E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.182177E+10 | 82.17 | 0.00 | 0.00 |
June | 0.116075E+12 | -0.114328E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174745E+10 | 82.17 | 0.00 | 0.00 |
July | 0.115496E+12 | -0.113705E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179054E+10 | 82.17 | 0.00 | 0.00 |
August | 0.113455E+12 | -0.111682E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177275E+10 | 82.17 | 0.00 | 0.00 |
September | 0.110745E+12 | -0.109040E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170592E+10 | 82.17 | 0.00 | 0.00 |
October | 0.118139E+12 | -0.116380E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175960E+10 | 82.17 | 0.00 | 0.00 |
November | 0.119557E+12 | -0.117852E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170517E+10 | 82.17 | 0.00 | 0.00 |
December | 0.128400E+12 | -0.126636E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176435E+10 | 82.03 | 0.00 | 0.00 |
Annual Sum or Average | 0.144787E+13 | -0.142687E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210031E+11 | 81.91 | 0.00 | 0.00 |
Minimum of Months | 0.110745E+12 | -0.127554E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.182177E+10 | 81.13 | 0.00 | 0.00 |
Maximum of Months | 0.129344E+12 | -0.109040E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.161092E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804729E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164328773.3 | 82.17 | 0.00 | 0.00 |
February | 0.727187E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148505367.9 | 82.17 | 0.00 | 0.00 |
March | 0.804567E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164110503.1 | 82.17 | 0.00 | 0.00 |
April | 0.779702E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158816154.6 | 82.17 | 0.00 | 0.00 |
May | 0.804707E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164109056.3 | 82.17 | 0.00 | 0.00 |
June | 0.778858E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158814124.7 | 82.17 | 0.00 | 0.00 |
July | 0.805551E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164107244.1 | 82.17 | 0.00 | 0.00 |
August | 0.804707E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164107811.5 | 82.17 | 0.00 | 0.00 |
September | 0.779842E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158814861.5 | 82.17 | 0.00 | 0.00 |
October | 0.804567E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164109845.0 | 82.17 | 0.00 | 0.00 |
November | 0.778017E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158851038.3 | 82.17 | 0.00 | 0.00 |
December | 0.805551E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164110769.4 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947798E+11 | -0.928471E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193279E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727187E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164328773.3 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805551E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148505367.9 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.829720E+11 | -0.814063E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156574E+10 | 60.05 | 0.00 | 0.00 |
February | 0.764460E+11 | -0.750083E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.143764E+10 | 60.05 | 0.00 | 0.00 |
March | 0.838774E+11 | -0.822821E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.159528E+10 | 60.05 | 0.00 | 0.00 |
April | 0.781165E+11 | -0.765572E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.155932E+10 | 60.05 | 0.00 | 0.00 |
May | 0.760813E+11 | -0.744802E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.160111E+10 | 60.05 | 0.00 | 0.00 |
June | 0.688927E+11 | -0.673648E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152791E+10 | 60.05 | 0.00 | 0.00 |
July | 0.672739E+11 | -0.657161E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155782E+10 | 60.05 | 0.00 | 0.00 |
August | 0.655688E+11 | -0.640356E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153317E+10 | 60.05 | 0.00 | 0.00 |
September | 0.642358E+11 | -0.627655E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147033E+10 | 60.05 | 0.00 | 0.00 |
October | 0.695402E+11 | -0.680252E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151494E+10 | 60.05 | 0.00 | 0.00 |
November | 0.718119E+11 | -0.703427E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146929E+10 | 60.05 | 0.00 | 0.00 |
December | 0.790918E+11 | -0.775646E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152718E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.883908E+12 | -0.865549E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.183597E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.642358E+11 | -0.822821E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.160111E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.838774E+11 | -0.627655E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.143764E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.86 | 0.86 | 01-JAN-09:39 | 6183.29 | 37.91 | 207.17 | 250.00 | 4152.31 | 37.39 | 209.00 | 217.50 |
February | 226.83 | 0.87 | 0.86 | 01-FEB-07:49 | 7492.05 | 37.72 | 221.50 | 257.00 | 1586.30 | 28.95 | 208.17 | 232.50 |
March | 334.33 | 0.87 | 0.86 | 01-MAR-07:00 | 4178.51 | 26.05 | 200.33 | 330.33 | 719.50 | 22.21 | 234.00 | 282.33 |
April | 285.17 | 0.87 | 0.86 | 01-APR-07:19 | 1544.34 | 20.77 | 114.83 | 350.50 | 629.64 | 22.48 | 222.33 | 278.67 |
May | 428.67 | 0.87 | 0.86 | 01-MAY-06:49 | 1270.45 | 19.86 | 72.83 | 399.33 | 497.29 | 21.57 | 278.67 | 329.50 |
June | 400.67 | 0.87 | 0.86 | 01-JUN-05:49 | 1294.03 | 20.25 | 121.17 | 400.33 | 518.37 | 21.97 | 281.50 | 333.33 |
July | 414.00 | 0.87 | 0.86 | 01-JUL-05:00 | 1330.71 | 20.59 | 134.17 | 411.17 | 536.91 | 22.31 | 308.83 | 342.33 |
August | 410.83 | 0.87 | 0.86 | 01-AUG-06:19 | 1492.14 | 20.32 | 130.83 | 382.00 | 585.24 | 22.03 | 303.33 | 328.33 |
September | 326.50 | 0.87 | 0.86 | 01-SEP-06:30 | 2528.82 | 23.00 | 178.17 | 336.00 | 695.20 | 22.62 | 247.33 | 289.67 |
October | 325.17 | 0.87 | 0.86 | 01-OCT-06:00 | 6497.91 | 33.67 | 296.00 | 309.33 | 882.00 | 23.62 | 239.67 | 278.00 |
November | 254.83 | 0.87 | 0.86 | 01-NOV-07:40 | 4419.90 | 33.19 | 238.83 | 251.50 | 2123.85 | 30.64 | 224.00 | 220.00 |
December | 186.17 | 0.87 | 0.86 | 01-DEC-07:00 | 5361.29 | 38.02 | 180.33 | 225.67 | 4761.79 | 39.00 | 180.83 | 173.50 |
Annual Sum or Average | 3807.33 | 0.87 | 3191.50 | 25.95 | 2096.17 | 3903.17 | 1180.43 | 24.92 | 2937.67 | 3305.67 | ||
Minimum of Months | 186.17 | 0.86 | 0.86 | 1270.45 | 19.86 | 72.83 | 225.67 | 497.29 | 21.57 | 180.83 | 173.50 | |
Maximum of Months | 428.67 | 0.87 | 0.86 | 7492.05 | 38.02 | 296.00 | 411.17 | 4761.79 | 39.00 | 308.83 | 342.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.24 | 0.22 | 01-JAN-09:39 | 6681.57 | 38.00 | 207.17 | 258.50 | 4649.88 | 37.37 | 203.67 | 236.17 |
February | 226.83 | 0.24 | 0.22 | 01-FEB-07:49 | 7982.59 | 37.79 | 221.83 | 265.00 | 2072.85 | 28.70 | 201.00 | 247.83 |
March | 334.33 | 0.24 | 0.22 | 01-MAR-07:40 | 4535.67 | 26.29 | 203.00 | 341.17 | 1073.49 | 22.36 | 235.50 | 311.67 |
April | 285.17 | 0.25 | 0.22 | 01-APR-06:00 | 1888.85 | 21.00 | 116.83 | 360.67 | 973.15 | 22.58 | 230.50 | 329.50 |
May | 428.67 | 0.25 | 0.22 | 01-MAY-06:10 | 1498.02 | 20.45 | 131.17 | 414.33 | 724.09 | 21.97 | 300.83 | 374.33 |
June | 400.67 | 0.25 | 0.22 | 01-JUN-05:19 | 1520.55 | 20.81 | 175.83 | 414.67 | 744.12 | 22.35 | 307.17 | 378.67 |
July | 414.00 | 0.24 | 0.22 | 01-JUL-05:40 | 1573.01 | 21.10 | 191.83 | 424.00 | 778.40 | 22.63 | 330.67 | 388.50 |
August | 410.83 | 0.25 | 0.22 | 01-AUG-05:00 | 1759.51 | 20.78 | 174.67 | 394.17 | 851.67 | 22.32 | 320.33 | 363.00 |
September | 326.50 | 0.24 | 0.22 | 01-SEP-06:10 | 2890.13 | 23.19 | 175.33 | 345.50 | 1055.22 | 22.72 | 263.00 | 317.50 |
October | 325.17 | 0.24 | 0.22 | 01-OCT-06:49 | 6887.69 | 33.83 | 297.67 | 316.17 | 1271.99 | 23.67 | 234.33 | 296.50 |
November | 254.83 | 0.24 | 0.22 | 01-NOV-07:40 | 4756.60 | 33.31 | 240.17 | 260.67 | 2460.84 | 30.69 | 227.17 | 239.50 |
December | 186.17 | 0.24 | 0.22 | 01-DEC-07:00 | 5825.71 | 38.11 | 180.50 | 236.33 | 5222.50 | 39.07 | 180.83 | 206.83 |
Annual Sum or Average | 3807.33 | 0.24 | 3520.10 | 26.27 | 2316.00 | 4031.17 | 1507.78 | 25.10 | 3035.00 | 3690.00 | ||
Minimum of Months | 186.17 | 0.24 | 0.22 | 1498.02 | 20.45 | 116.83 | 236.33 | 724.09 | 21.97 | 180.83 | 206.83 | |
Maximum of Months | 428.67 | 0.25 | 0.22 | 7982.59 | 38.11 | 297.67 | 424.00 | 5222.50 | 39.07 | 330.67 | 388.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.64 | 0.60 | 01-JAN-09:00 | 444.26 | 15.46 | 0.00 | 229.67 | 216.71 | 18.94 | 0.50 | 124.00 |
February | 226.83 | 0.64 | 0.60 | 01-FEB-09:09 | 456.03 | 15.69 | 0.00 | 241.83 | 224.44 | 19.13 | 0.00 | 149.00 |
March | 334.33 | 0.62 | 0.60 | 01-MAR-08:09 | 640.77 | 16.97 | 0.00 | 330.00 | 287.22 | 20.17 | 13.33 | 262.50 |
April | 285.17 | 0.61 | 0.60 | 01-APR-07:10 | 728.21 | 18.13 | 0.00 | 360.17 | 346.68 | 21.33 | 125.83 | 294.67 |
May | 428.67 | 0.61 | 0.60 | 01-MAY-05:00 | 860.03 | 18.21 | 4.17 | 421.17 | 375.85 | 22.21 | 203.67 | 383.33 |
June | 400.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1043.77 | 21.20 | 67.00 | 423.00 | 483.96 | 24.28 | 291.33 | 395.33 |
July | 414.00 | 0.61 | 0.60 | 01-JUL-05:40 | 975.51 | 20.76 | 54.00 | 431.17 | 451.92 | 23.43 | 287.33 | 402.67 |
August | 410.83 | 0.62 | 0.60 | 01-AUG-05:49 | 802.26 | 18.29 | 4.50 | 396.83 | 364.52 | 21.66 | 202.00 | 367.33 |
September | 326.50 | 0.62 | 0.60 | 01-SEP-06:10 | 643.73 | 17.66 | 0.00 | 339.17 | 309.42 | 20.85 | 62.00 | 286.33 |
October | 325.17 | 0.63 | 0.60 | 01-OCT-07:19 | 521.85 | 16.17 | 0.00 | 297.00 | 240.98 | 19.47 | 0.00 | 214.00 |
November | 254.83 | 0.64 | 0.60 | 01-NOV-08:20 | 457.22 | 15.24 | 0.00 | 237.50 | 202.47 | 18.54 | 0.00 | 130.17 |
December | 186.17 | 0.67 | 0.60 | 02-DEC-09:09 | 315.05 | 14.03 | 0.00 | 197.83 | 159.82 | 17.65 | 0.00 | 40.33 |
Annual Sum or Average | 3807.33 | 0.62 | 708.07 | 17.77 | 129.67 | 3905.33 | 326.95 | 21.07 | 1186.00 | 3049.67 | ||
Minimum of Months | 186.17 | 0.61 | 0.60 | 315.05 | 14.03 | 0.00 | 197.83 | 159.82 | 17.65 | 0.00 | 40.33 | |
Maximum of Months | 428.67 | 0.67 | 0.60 | 1043.77 | 21.20 | 67.00 | 431.17 | 483.96 | 24.28 | 291.33 | 402.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.64 | 0.60 | 01-JAN-09:00 | 444.26 | 15.46 | 0.00 | 229.67 | 216.71 | 18.94 | 0.50 | 124.00 |
February | 226.83 | 0.64 | 0.60 | 01-FEB-09:09 | 456.03 | 15.69 | 0.00 | 241.83 | 224.44 | 19.13 | 0.00 | 149.00 |
March | 334.33 | 0.62 | 0.60 | 01-MAR-08:09 | 640.77 | 16.97 | 0.00 | 330.00 | 287.22 | 20.17 | 13.33 | 262.50 |
April | 285.17 | 0.61 | 0.60 | 01-APR-07:10 | 728.21 | 18.13 | 0.00 | 360.17 | 346.68 | 21.33 | 125.83 | 294.67 |
May | 428.67 | 0.61 | 0.60 | 01-MAY-05:00 | 860.03 | 18.21 | 4.17 | 421.17 | 375.85 | 22.21 | 203.67 | 383.33 |
June | 400.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1043.77 | 21.20 | 67.00 | 423.00 | 483.96 | 24.28 | 291.33 | 395.33 |
July | 414.00 | 0.61 | 0.60 | 01-JUL-05:40 | 975.51 | 20.76 | 54.00 | 431.17 | 451.92 | 23.43 | 287.33 | 402.67 |
August | 410.83 | 0.62 | 0.60 | 01-AUG-05:49 | 802.26 | 18.29 | 4.50 | 396.83 | 364.52 | 21.66 | 202.00 | 367.33 |
September | 326.50 | 0.62 | 0.60 | 01-SEP-06:10 | 643.73 | 17.66 | 0.00 | 339.17 | 309.42 | 20.85 | 62.00 | 286.33 |
October | 325.17 | 0.63 | 0.60 | 01-OCT-07:19 | 521.85 | 16.17 | 0.00 | 297.00 | 240.98 | 19.47 | 0.00 | 214.00 |
November | 254.83 | 0.64 | 0.60 | 01-NOV-08:20 | 457.22 | 15.24 | 0.00 | 237.50 | 202.47 | 18.54 | 0.00 | 130.17 |
December | 186.17 | 0.67 | 0.60 | 02-DEC-09:09 | 315.05 | 14.03 | 0.00 | 197.83 | 159.82 | 17.65 | 0.00 | 40.33 |
Annual Sum or Average | 3807.33 | 0.62 | 708.07 | 17.77 | 129.67 | 3905.33 | 326.95 | 21.07 | 1186.00 | 3049.67 | ||
Minimum of Months | 186.17 | 0.61 | 0.60 | 315.05 | 14.03 | 0.00 | 197.83 | 159.82 | 17.65 | 0.00 | 40.33 | |
Maximum of Months | 428.67 | 0.67 | 0.60 | 1043.77 | 21.20 | 67.00 | 431.17 | 483.96 | 24.28 | 291.33 | 402.67 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.158867E+11 | 31980.12 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107824E+11 | 33531.07 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230196E+10 | 7049.25 | 05-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.429663E+09 | 3996.24 | 03-APR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9067.63 | 0.27 | 12-MAY-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13732.99 | 0.27 | 18-JUN-22:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12689.97 | 0.27 | 09-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14816.65 | 0.27 | 15-AUG-18:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 298774.85 | 190.31 | 30-SEP-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21218989.19 | 1122.59 | 23-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.377405E+10 | 31354.11 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.675702E+10 | 11618.92 | 09-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.399534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9067.63 | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158867E+11 | 33531.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150792E+12 | 274560.18 | 30-JAN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145149E+12 | 287740.78 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.570076E+11 | 105745.28 | 21-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.460311E+11 | 96897.21 | 21-APR-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146509E+11 | 88934.19 | 03-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.219546E+10 | 46293.87 | 03-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 343.89 | 1.72 | 05-JUL-10:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158836E+09 | 14911.95 | 07-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152756E+11 | 94499.32 | 30-SEP-01:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.639674E+11 | 96781.07 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.674136E+11 | 265925.64 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.452571E+11 | 98145.20 | 01-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.607899E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 343.89 | 1.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.150792E+12 | 287740.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159809E+09 | 5075.34 | 31-JAN-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176050E+10 | 6514.15 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70709227.42 | 2462.02 | 17-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1021242.03 | 1390.67 | 01-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176050E+10 | 6514.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.348120E+10 | 3661.58 | 31-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229404E+10 | 3907.79 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112476E+10 | 1586.84 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.541524E+09 | 1416.34 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8490873.92 | 398.10 | 02-MAY-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1539273.76 | 225.84 | 05-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49003748.20 | 821.03 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180040E+09 | 834.25 | 27-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145237E+10 | 3570.95 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280848E+10 | 3122.41 | 10-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.348120E+10 | 3907.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.950067E+09 | 1407.96 | 31-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.689650E+09 | 1500.24 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155328E+09 | 643.59 | 01-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39546309.30 | 574.26 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17209.42 | 51.38 | 02-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 55322.66 | 92.20 | 26-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238468E+09 | 1373.91 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.487319E+09 | 902.78 | 12-DEC-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.950067E+09 | 1500.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111256E+10 | 1905.15 | 31-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.873501E+09 | 2032.30 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30132931.02 | 349.46 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143901E+09 | 1858.30 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366938E+09 | 1016.39 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111256E+10 | 2032.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.256337E+10 | 1468.47 | 31-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.186766E+10 | 1565.81 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120974E+10 | 970.44 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.562899E+09 | 761.23 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29109417.00 | 408.24 | 02-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2445914.05 | 165.80 | 06-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32916808.42 | 343.69 | 30-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220680E+09 | 401.60 | 27-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112575E+10 | 1432.59 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207597E+10 | 1254.93 | 10-DEC-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.969055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.256337E+10 | 1565.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.778702E+10 | 10883.10 | 31-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.567794E+10 | 11596.94 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218702E+10 | 5999.60 | 01-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146896E+10 | 5580.34 | 03-APR-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164813E+09 | 2920.43 | 25-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154284E+09 | 3760.20 | 05-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22850624.63 | 2434.98 | 10-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3729118.13 | 1667.33 | 31-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.251332E+09 | 3782.06 | 27-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.622520E+09 | 3828.91 | 26-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.323403E+10 | 10619.74 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.541488E+10 | 8699.50 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3729118.13 | 1667.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.778702E+10 | 11596.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.985144E+10 | 26711.11 | 31-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.928039E+10 | 28459.38 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.940336E+09 | 9592.09 | 01-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.251333E+09 | 7641.34 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.204791E+10 | 24374.89 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.422636E+10 | 15642.22 | 12-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.985144E+10 | 28459.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163407E+11 | 12227.75 | 31-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113696E+11 | 13038.58 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.532893E+10 | 7310.44 | 01-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177429E+10 | 6231.57 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37708558.52 | 2501.87 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.704711E+09 | 3467.98 | 27-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.720628E+10 | 11928.84 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131562E+11 | 10446.43 | 09-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163407E+11 | 13038.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.853645E+10 | 7710.24 | 31-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.574391E+10 | 8223.27 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198763E+10 | 3637.99 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.429714E+09 | 2374.91 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 488309.73 | 255.14 | 30-SEP-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31928132.95 | 988.86 | 27-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290078E+10 | 7521.12 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.619990E+10 | 6584.70 | 10-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.853645E+10 | 8223.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.556174E+10 | 13053.07 | 31-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.514703E+10 | 13904.59 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.674448E+09 | 4423.80 | 13-MAR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146537E+09 | 3527.66 | 05-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6455742.91 | 2560.84 | 02-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 249458.63 | 415.76 | 05-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8683893.00 | 2625.34 | 29-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 62044715.31 | 3224.90 | 27-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136870E+10 | 12738.79 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.217046E+10 | 5879.63 | 11-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.556174E+10 | 13904.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.414169E+10 | 13183.04 | 31-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.429341E+10 | 14043.14 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108731E+09 | 2686.78 | 06-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8432017.09 | 1921.75 | 05-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5144337.02 | 1384.01 | 27-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.679006E+09 | 12597.52 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.925582E+09 | 4521.52 | 11-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.429341E+10 | 14043.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 13374242.62 | 2269.92 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131303E+09 | 4406.22 | 02-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131303E+09 | 4406.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.863134E+10 | 7558.98 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.567639E+10 | 7559.01 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.328821E+10 | 7558.47 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136073E+10 | 7558.72 | 02-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104098E+09 | 5654.65 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46333199.87 | 4501.46 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7084153.44 | 4275.55 | 13-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7846364.56 | 4091.38 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274344E+09 | 7298.61 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115904E+10 | 7431.96 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.414944E+10 | 7558.85 | 17-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.729815E+10 | 7559.24 | 31-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7084153.44 | 4091.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.863134E+10 | 7559.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100080E+11 | 7516.95 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.681923E+10 | 7520.20 | 02-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.391868E+10 | 7516.43 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155841E+10 | 7516.69 | 02-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114796E+09 | 7227.81 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47018082.24 | 4524.88 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2917629.37 | 3940.93 | 12-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4685629.15 | 4174.59 | 16-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.336865E+09 | 7334.38 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164913E+10 | 7446.12 | 27-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.489584E+10 | 7516.82 | 17-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.838614E+10 | 7517.21 | 31-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2917629.37 | 3940.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100080E+11 | 7520.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.921223E+10 | 25138.26 | 19-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185365E+10 | 19349.94 | 04-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219890E+09 | 8179.83 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.586613E+09 | 15884.83 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.629999E+10 | 19499.31 | 12-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.921223E+10 | 25138.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.469302E+11 | 41713.83 | 31-JAN-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.331695E+11 | 42899.74 | 03-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137794E+11 | 41219.14 | 01-MAR-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.406208E+10 | 40344.95 | 03-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82670693.55 | 23291.12 | 02-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18014795.39 | 20012.14 | 06-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5759220.75 | 8946.15 | 09-JUL-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12522766.19 | 22290.58 | 18-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.309341E+09 | 30363.71 | 30-SEP-15:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275655E+10 | 27116.23 | 31-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178937E+11 | 41593.81 | 27-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.355651E+11 | 41599.61 | 23-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154585E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5759220.75 | 8946.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.469302E+11 | 42899.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.856109E+10 | 7360.54 | 16-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.573980E+10 | 7360.47 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.323434E+10 | 7359.90 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150597E+10 | 7360.15 | 02-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86466059.99 | 4678.79 | 26-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36044228.38 | 4277.26 | 04-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2805827.96 | 3039.73 | 11-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4385781.73 | 4029.09 | 06-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.248699E+09 | 4771.61 | 22-SEP-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117574E+10 | 7197.88 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.417811E+10 | 7360.30 | 17-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.732829E+10 | 7360.70 | 31-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2805827.96 | 3039.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.856109E+10 | 7360.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.995026E+10 | 7319.26 | 16-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.691459E+10 | 7392.13 | 03-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384946E+10 | 7318.60 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173895E+10 | 7318.87 | 02-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 96497452.98 | 4468.67 | 17-MAY-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37104972.03 | 4183.57 | 04-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2121720.63 | 2856.35 | 22-JUL-21:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4036401.59 | 4242.21 | 06-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.299723E+09 | 3647.83 | 18-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166107E+10 | 7195.73 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.493655E+10 | 7320.09 | 20-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.844041E+10 | 7319.42 | 31-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2121720.63 | 2856.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.995026E+10 | 7392.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.293226E+10 | 2237.41 | 13-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196604E+10 | 2252.62 | 02-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120375E+10 | 2237.48 | 14-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.536779E+09 | 2237.43 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65949299.35 | 2170.75 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31675073.40 | 1182.82 | 04-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1898991.08 | 1069.89 | 31-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2452856.54 | 970.10 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138345E+09 | 2196.97 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.496355E+09 | 2237.41 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148532E+10 | 2238.01 | 15-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250477E+10 | 2237.50 | 31-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1898991.08 | 970.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.293226E+10 | 2252.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.332735E+10 | 2221.96 | 13-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230775E+10 | 2275.28 | 02-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140895E+10 | 2222.12 | 12-MAR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.600371E+09 | 2221.98 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65745878.50 | 2164.18 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32226521.44 | 1129.37 | 04-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 717517.50 | 904.17 | 12-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1238854.93 | 1157.22 | 18-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162073E+09 | 2203.35 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.663540E+09 | 2222.18 | 16-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171837E+10 | 2222.63 | 15-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282813E+10 | 2222.06 | 31-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 717517.50 | 904.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.332735E+10 | 2275.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.997356E+10 | 10569.40 | 16-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.617280E+10 | 10568.59 | 22-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.365823E+10 | 10567.94 | 02-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181675E+10 | 10568.53 | 02-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130977E+09 | 6143.23 | 17-MAY-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 55880140.28 | 6037.03 | 01-JUN-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5206546.28 | 5007.06 | 31-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11188582.35 | 4944.51 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.268400E+09 | 5885.33 | 13-SEP-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.916804E+09 | 10253.05 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.449154E+10 | 10568.51 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.846563E+10 | 10569.09 | 30-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.359670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5206546.28 | 4944.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.997356E+10 | 10569.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.189758E+09 | 0.189758E+09 | 8515.76 | 19-MAR-16:00 | 8515.76 | 0.01 |
April | 0.00 | 0.00 | 0.306682E+10 | 0.244039E+10 | 26462.51 | 18-APR-08:50 | 14831.26 | 0.09 |
May | 0.00 | 0.00 | 0.699804E+10 | 0.526532E+10 | 29139.22 | 29-MAY-15:13 | 14564.20 | 0.28 |
June | 0.00 | 0.00 | 0.229820E+11 | 0.149848E+11 | 40089.38 | 26-JUN-06:45 | 16195.62 | 0.55 |
July | 0.00 | 0.00 | 0.347628E+11 | 0.197789E+11 | 40259.69 | 17-JUL-18:50 | 16006.69 | 0.70 |
August | 0.00 | 0.00 | 0.283337E+11 | 0.165087E+11 | 42516.66 | 31-AUG-18:03 | 16363.09 | 0.63 |
September | 0.00 | 0.00 | 0.103411E+11 | 0.886675E+10 | 29549.17 | 11-SEP-08:15 | 15611.99 | 0.33 |
October | 0.00 | 0.00 | 0.596914E+09 | 0.596914E+09 | 15124.14 | 20-OCT-15:12 | 15124.14 | 0.02 |
November | 0.00 | 0.00 | 22232899.69 | 22232899.69 | 1791.45 | 03-NOV-15:11 | 1791.45 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.107293E+12 | 0.686538E+11 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.347628E+11 | 0.197789E+11 | 42516.66 | 16363.09 | 0.70 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.154201E+09 | 0.154201E+09 | 4029.28 | 13-JAN-06:10 | 4029.28 | 0.00 |
February | 0.00 | 0.00 | 0.177605E+09 | 0.177605E+09 | 4045.35 | 14-FEB-06:10 | 4045.35 | 0.00 |
March | 0.00 | 0.00 | 0.353060E+10 | 0.353060E+10 | 77611.90 | 19-MAR-16:20 | 77611.90 | 0.02 |
April | 0.00 | 0.00 | 0.468361E+11 | 0.398223E+11 | 287759.19 | 18-APR-10:35 | 185729.06 | 0.14 |
May | 0.00 | 0.00 | 0.112493E+12 | 0.917267E+11 | 278104.23 | 29-MAY-18:03 | 153472.75 | 0.41 |
June | 0.00 | 0.00 | 0.319398E+12 | 0.225699E+12 | 391713.68 | 26-JUN-06:52 | 159744.04 | 0.75 |
July | 0.00 | 0.00 | 0.463873E+12 | 0.289093E+12 | 456048.86 | 17-JUL-19:10 | 180296.43 | 0.93 |
August | 0.00 | 0.00 | 0.399658E+12 | 0.255094E+12 | 460232.97 | 28-AUG-19:40 | 180806.66 | 0.86 |
September | 0.00 | 0.00 | 0.154441E+12 | 0.141124E+12 | 291809.70 | 11-SEP-10:35 | 193123.87 | 0.46 |
October | 0.00 | 0.00 | 0.114415E+11 | 0.114415E+11 | 145960.90 | 20-OCT-15:10 | 145960.90 | 0.05 |
November | 0.00 | 0.00 | 0.771668E+09 | 0.771668E+09 | 25205.05 | 03-NOV-15:13 | 25205.05 | 0.01 |
December | 0.00 | 0.00 | 0.285675E+09 | 0.285675E+09 | 4010.45 | 01-DEC-06:10 | 4010.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151306E+13 | 0.105892E+13 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.154201E+09 | 0.154201E+09 | 4010.45 | 4010.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.463873E+12 | 0.289093E+12 | 460232.97 | 193123.87 | 0.93 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 5651838.22 | 3701130.86 | 11107.31 | 12-JAN-16:12 | 11107.31 | 0.00 |
February | 0.00 | 0.00 | 0.123628E+09 | 67379003.31 | 16188.78 | 17-FEB-16:11 | 16188.78 | 0.03 |
March | 0.00 | 0.00 | 0.400733E+09 | 0.256061E+09 | 16660.58 | 10-MAR-16:11 | 16660.58 | 0.08 |
April | 0.00 | 0.00 | 0.241126E+10 | 0.150366E+10 | 16873.16 | 16-APR-08:61 | 13019.12 | 0.32 |
May | 0.00 | 0.00 | 0.434981E+10 | 0.214619E+10 | 17151.77 | 29-MAY-08:61 | 12831.05 | 0.73 |
June | 0.00 | 0.00 | 0.769481E+10 | 0.419539E+10 | 18042.89 | 25-JUN-08:61 | 12119.23 | 0.84 |
July | 0.00 | 0.00 | 0.979390E+10 | 0.534146E+10 | 18590.93 | 20-JUL-08:61 | 11660.07 | 0.93 |
August | 0.00 | 0.00 | 0.874678E+10 | 0.448780E+10 | 19621.98 | 31-AUG-08:61 | 10756.75 | 0.93 |
September | 0.00 | 0.00 | 0.531121E+10 | 0.295924E+10 | 17388.39 | 11-SEP-08:61 | 12635.78 | 0.69 |
October | 0.00 | 0.00 | 0.107788E+10 | 0.570425E+09 | 15893.60 | 02-OCT-15:11 | 13789.92 | 0.25 |
November | 0.00 | 0.00 | 0.200327E+09 | 0.114043E+09 | 16657.81 | 12-NOV-16:11 | 16657.81 | 0.05 |
December | 0.00 | 0.00 | 7679658.60 | 6542656.00 | 16018.26 | 01-DEC-16:12 | 16018.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.401237E+11 | 0.216519E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 5651838.22 | 3701130.86 | 11107.31 | 10756.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.979390E+10 | 0.534146E+10 | 19621.98 | 16660.58 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 190769.80 | 38768.10 | 815.44 | 12-JAN-16:13 | 171.32 | 0.00 |
February | 0.00 | 0.00 | 28811654.08 | 13786989.98 | 11723.52 | 25-FEB-16:11 | 11723.52 | 0.01 |
March | 0.00 | 0.00 | 0.120511E+09 | 74775473.67 | 15528.18 | 21-MAR-18:01 | 15528.18 | 0.03 |
April | 0.00 | 0.00 | 0.144669E+10 | 0.853318E+09 | 16585.47 | 16-APR-21:51 | 13086.27 | 0.22 |
May | 0.00 | 0.00 | 0.284660E+10 | 0.121999E+10 | 18157.31 | 20-MAY-18:41 | 18157.31 | 0.57 |
June | 0.00 | 0.00 | 0.603584E+10 | 0.333174E+10 | 20544.97 | 26-JUN-08:11 | 11629.59 | 0.65 |
July | 0.00 | 0.00 | 0.738243E+10 | 0.410645E+10 | 18841.86 | 02-JUL-08:51 | 12390.03 | 0.68 |
August | 0.00 | 0.00 | 0.610450E+10 | 0.301518E+10 | 20788.41 | 03-AUG-07:51 | 11261.66 | 0.68 |
September | 0.00 | 0.00 | 0.333151E+10 | 0.164754E+10 | 17084.37 | 11-SEP-08:51 | 12443.52 | 0.51 |
October | 0.00 | 0.00 | 0.305880E+09 | 0.124854E+09 | 15527.43 | 02-OCT-18:01 | 12970.24 | 0.11 |
November | 0.00 | 0.00 | 54243628.11 | 28776966.72 | 13061.20 | 03-NOV-16:11 | 13061.20 | 0.01 |
December | 0.00 | 0.00 | 404648.16 | 265398.14 | 1343.03 | 01-DEC-16:13 | 1343.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.276576E+11 | 0.144167E+11 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 190769.80 | 38768.10 | 815.44 | 171.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.738243E+10 | 0.410645E+10 | 20788.41 | 18157.31 | 0.68 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.233743E+10 | 0.220946E+10 | 30028.33 | 24-MAR-13:10 | 30028.33 | 0.02 |
April | 0.00 | 0.00 | 0.109689E+11 | 0.626600E+10 | 46560.98 | 15-APR-13:15 | 41935.73 | 0.24 |
May | 0.00 | 0.00 | 0.219428E+11 | 0.905503E+10 | 33883.83 | 05-MAY-13:15 | 22284.44 | 0.67 |
June | 0.00 | 0.00 | 0.326985E+11 | 0.129913E+11 | 36333.13 | 26-JUN-12:40 | 25104.56 | 0.87 |
July | 0.00 | 0.00 | 0.414807E+11 | 0.168347E+11 | 38908.31 | 30-JUL-13:30 | 29542.92 | 0.98 |
August | 0.00 | 0.00 | 0.425729E+11 | 0.186563E+11 | 43812.10 | 29-AUG-13:30 | 38064.37 | 0.99 |
September | 0.00 | 0.00 | 0.344368E+11 | 0.194604E+11 | 53110.25 | 07-SEP-13:00 | 40304.68 | 0.72 |
October | 0.00 | 0.00 | 0.161596E+11 | 0.136837E+11 | 51433.23 | 20-OCT-12:50 | 51433.23 | 0.17 |
November | 0.00 | 0.00 | 0.442506E+10 | 0.338659E+10 | 49679.10 | 04-NOV-12:30 | 38863.85 | 0.09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207023E+12 | 0.102543E+12 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.425729E+11 | 0.194604E+11 | 53110.25 | 51433.23 | 0.99 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 10402245.70 | 8167640.35 | 11769.59 | 13-JAN-19:03 | 5709.63 | 0.00 |
February | 0.00 | 0.00 | 43304575.67 | 28819990.56 | 56238.88 | 25-FEB-09:02 | 56238.88 | 0.00 |
March | 0.00 | 0.00 | 0.201391E+10 | 0.847928E+09 | 75223.16 | 25-MAR-18:23 | 75223.16 | 0.13 |
April | 0.00 | 0.00 | 0.974528E+10 | 0.547501E+10 | 83141.06 | 16-APR-21:51 | 64361.92 | 0.28 |
May | 0.00 | 0.00 | 0.276119E+11 | 0.153953E+11 | 88024.28 | 11-MAY-21:42 | 60744.34 | 0.55 |
June | 0.00 | 0.00 | 0.432228E+11 | 0.266241E+11 | 102958.74 | 26-JUN-08:11 | 56190.68 | 0.63 |
July | 0.00 | 0.00 | 0.470378E+11 | 0.283185E+11 | 92712.90 | 02-JUL-08:51 | 62004.22 | 0.60 |
August | 0.00 | 0.00 | 0.413914E+11 | 0.237082E+11 | 106916.84 | 03-AUG-07:51 | 52489.35 | 0.58 |
September | 0.00 | 0.00 | 0.248861E+11 | 0.138703E+11 | 85140.94 | 11-SEP-21:51 | 64736.01 | 0.54 |
October | 0.00 | 0.00 | 0.577595E+10 | 0.242535E+10 | 75899.61 | 12-OCT-15:11 | 75899.61 | 0.32 |
November | 0.00 | 0.00 | 0.246410E+10 | 0.878880E+09 | 74640.28 | 04-NOV-18:01 | 74640.28 | 0.14 |
December | 0.00 | 0.00 | 12688638.89 | 9065564.14 | 13124.62 | 03-DEC-09:02 | 6790.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.204216E+12 | 0.117590E+12 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 10402245.70 | 8167640.35 | 11769.59 | 5709.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.470378E+11 | 0.283185E+11 | 106916.84 | 75899.61 | 0.63 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3593278.11 | 855457.43 | 2730.22 | 12-JAN-09:03 | 1483.36 | 0.00 |
February | 0.00 | 0.00 | 78159005.88 | 44192570.58 | 12679.86 | 21-FEB-09:02 | 12679.86 | 0.02 |
March | 0.00 | 0.00 | 0.376307E+09 | 0.209764E+09 | 14437.06 | 22-MAR-15:13 | 14437.06 | 0.10 |
April | 0.00 | 0.00 | 0.203669E+10 | 0.114882E+10 | 15125.39 | 06-APR-15:11 | 15125.39 | 0.33 |
May | 0.00 | 0.00 | 0.464502E+10 | 0.224174E+10 | 15289.69 | 11-MAY-15:11 | 11666.00 | 0.79 |
June | 0.00 | 0.00 | 0.782848E+10 | 0.429308E+10 | 16502.31 | 14-JUN-08:62 | 10520.18 | 0.88 |
July | 0.00 | 0.00 | 0.956803E+10 | 0.513979E+10 | 16919.47 | 20-JUL-08:61 | 10591.37 | 0.96 |
August | 0.00 | 0.00 | 0.842546E+10 | 0.423038E+10 | 17841.08 | 31-AUG-08:61 | 9569.21 | 0.95 |
September | 0.00 | 0.00 | 0.533203E+10 | 0.294008E+10 | 15073.14 | 10-SEP-08:61 | 12068.75 | 0.73 |
October | 0.00 | 0.00 | 0.885678E+09 | 0.400478E+09 | 14765.36 | 02-OCT-15:11 | 12103.16 | 0.27 |
November | 0.00 | 0.00 | 0.161473E+09 | 77085926.04 | 12919.41 | 03-NOV-15:11 | 12919.41 | 0.05 |
December | 0.00 | 0.00 | 20816027.01 | 9914303.37 | 9688.83 | 03-DEC-09:02 | 9223.55 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.393617E+11 | 0.207362E+11 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 3593278.11 | 855457.43 | 2730.22 | 1483.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.956803E+10 | 0.513979E+10 | 17841.08 | 15125.39 | 0.96 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 339668.32 | 88920.82 | 1412.96 | 12-JAN-09:05 | 465.80 | 0.00 |
February | 0.00 | 0.00 | 13862981.88 | 4946781.74 | 10014.82 | 24-FEB-09:02 | 10014.82 | 0.01 |
March | 0.00 | 0.00 | 0.109424E+09 | 58361526.54 | 11017.98 | 28-MAR-08:62 | 11017.98 | 0.03 |
April | 0.00 | 0.00 | 0.118255E+10 | 0.632257E+09 | 16069.98 | 18-APR-08:51 | 14064.39 | 0.22 |
May | 0.00 | 0.00 | 0.330238E+10 | 0.155062E+10 | 17947.39 | 31-MAY-08:32 | 14970.04 | 0.64 |
June | 0.00 | 0.00 | 0.619888E+10 | 0.345024E+10 | 19681.30 | 26-JUN-07:52 | 13806.96 | 0.69 |
July | 0.00 | 0.00 | 0.714688E+10 | 0.385549E+10 | 18817.34 | 05-JUL-08:32 | 14507.15 | 0.69 |
August | 0.00 | 0.00 | 0.591962E+10 | 0.289840E+10 | 18829.91 | 03-AUG-07:51 | 11797.24 | 0.69 |
September | 0.00 | 0.00 | 0.339735E+10 | 0.169118E+10 | 16772.11 | 11-SEP-08:51 | 13506.19 | 0.55 |
October | 0.00 | 0.00 | 0.201721E+09 | 77519350.51 | 13697.91 | 02-OCT-18:01 | 11036.18 | 0.08 |
November | 0.00 | 0.00 | 18343187.29 | 7434234.05 | 10922.70 | 04-NOV-08:62 | 10922.70 | 0.01 |
December | 0.00 | 0.00 | 661368.93 | 368652.35 | 2079.79 | 02-DEC-09:03 | 944.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.274920E+11 | 0.142269E+11 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 339668.32 | 88920.82 | 1412.96 | 465.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.714688E+10 | 0.385549E+10 | 19681.30 | 14970.04 | 0.69 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1019022.53 | 613025.06 | 2882.01 | 12-JAN-16:12 | 2882.01 | 0.00 |
February | 0.00 | 0.00 | 30511254.13 | 16544337.01 | 3819.64 | 17-FEB-16:11 | 3819.64 | 0.02 |
March | 0.00 | 0.00 | 90040271.37 | 57748109.57 | 4345.24 | 22-MAR-15:11 | 4345.24 | 0.06 |
April | 0.00 | 0.00 | 0.624697E+09 | 0.407017E+09 | 4476.06 | 16-APR-08:61 | 3332.73 | 0.29 |
May | 0.00 | 0.00 | 0.109532E+10 | 0.580450E+09 | 4629.84 | 29-MAY-08:61 | 3218.41 | 0.65 |
June | 0.00 | 0.00 | 0.198001E+10 | 0.112201E+10 | 4860.42 | 25-JUN-08:61 | 3030.73 | 0.81 |
July | 0.00 | 0.00 | 0.249193E+10 | 0.140679E+10 | 5042.48 | 20-JUL-08:61 | 2794.43 | 0.93 |
August | 0.00 | 0.00 | 0.217675E+10 | 0.115199E+10 | 5276.36 | 31-AUG-08:61 | 2553.13 | 0.92 |
September | 0.00 | 0.00 | 0.128762E+10 | 0.751821E+09 | 4673.00 | 11-SEP-08:61 | 3181.40 | 0.62 |
October | 0.00 | 0.00 | 0.260593E+09 | 0.147954E+09 | 4134.61 | 02-OCT-15:11 | 3602.18 | 0.19 |
November | 0.00 | 0.00 | 48977421.02 | 30083189.97 | 4344.84 | 12-NOV-16:11 | 4344.84 | 0.03 |
December | 0.00 | 0.00 | 1463347.49 | 1241176.33 | 3898.79 | 01-DEC-16:12 | 3898.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.100889E+11 | 0.567426E+10 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 1019022.53 | 613025.06 | 2882.01 | 2553.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.249193E+10 | 0.140679E+10 | 5276.36 | 4345.24 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 90894.84 | 38466.10 | 670.70 | 13-JAN-16:14 | 334.42 | 0.00 |
February | 0.00 | 0.00 | 5211770.83 | 2291531.08 | 3022.30 | 25-FEB-16:11 | 3022.30 | 0.01 |
March | 0.00 | 0.00 | 22491131.73 | 13535301.46 | 4033.66 | 21-MAR-18:01 | 4033.66 | 0.02 |
April | 0.00 | 0.00 | 0.374453E+09 | 0.229581E+09 | 4409.68 | 16-APR-21:51 | 3366.15 | 0.20 |
May | 0.00 | 0.00 | 0.722993E+09 | 0.338097E+09 | 4756.34 | 20-MAY-18:41 | 4756.34 | 0.51 |
June | 0.00 | 0.00 | 0.160253E+10 | 0.919861E+09 | 5466.73 | 26-JUN-08:11 | 2925.74 | 0.63 |
July | 0.00 | 0.00 | 0.194636E+10 | 0.111033E+10 | 4965.01 | 02-JUL-08:51 | 3185.23 | 0.68 |
August | 0.00 | 0.00 | 0.156293E+10 | 0.792749E+09 | 5612.49 | 03-AUG-07:51 | 2712.31 | 0.68 |
September | 0.00 | 0.00 | 0.809081E+09 | 0.423154E+09 | 4494.39 | 11-SEP-08:51 | 3149.78 | 0.45 |
October | 0.00 | 0.00 | 65092929.64 | 25966725.11 | 4048.20 | 02-OCT-18:01 | 3419.85 | 0.08 |
November | 0.00 | 0.00 | 13228059.55 | 6831198.92 | 3452.03 | 03-NOV-16:11 | 3452.03 | 0.01 |
December | 0.00 | 0.00 | 17277.50 | 3171.13 | 196.24 | 02-DEC-16:13 | 36.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.712448E+10 | 0.386244E+10 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 17277.50 | 3171.13 | 196.24 | 36.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.194636E+10 | 0.111033E+10 | 5612.49 | 4756.34 | 0.68 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.405710E+09 | 0.325660E+09 | 19999.94 | 02-JAN-16:11 | 19999.94 | 0.03 |
February | 0.00 | 0.00 | 0.840916E+09 | 0.554586E+09 | 19998.39 | 17-FEB-16:11 | 19998.39 | 0.10 |
March | 0.00 | 0.00 | 0.151669E+10 | 0.955967E+09 | 19998.44 | 21-MAR-15:11 | 19998.44 | 0.20 |
April | 0.00 | 0.00 | 0.371841E+10 | 0.229554E+10 | 20330.53 | 16-APR-08:61 | 15648.90 | 0.37 |
May | 0.00 | 0.00 | 0.590814E+10 | 0.279180E+10 | 20807.04 | 31-MAY-08:61 | 15370.37 | 0.74 |
June | 0.00 | 0.00 | 0.920601E+10 | 0.470505E+10 | 22582.25 | 25-JUN-08:61 | 13985.23 | 0.85 |
July | 0.00 | 0.00 | 0.115456E+11 | 0.592930E+10 | 23641.32 | 20-JUL-08:61 | 12498.64 | 0.92 |
August | 0.00 | 0.00 | 0.114403E+11 | 0.595004E+10 | 24588.44 | 31-AUG-08:61 | 11516.11 | 0.91 |
September | 0.00 | 0.00 | 0.847543E+10 | 0.516769E+10 | 21510.19 | 11-SEP-08:61 | 14830.88 | 0.74 |
October | 0.00 | 0.00 | 0.397160E+10 | 0.249487E+10 | 18328.76 | 02-OCT-15:11 | 17236.02 | 0.48 |
November | 0.00 | 0.00 | 0.126958E+10 | 0.840562E+09 | 19941.55 | 21-NOV-16:11 | 19941.55 | 0.17 |
December | 0.00 | 0.00 | 0.807391E+09 | 0.662997E+09 | 20000.54 | 25-DEC-16:11 | 20000.54 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.591058E+11 | 0.326741E+11 | 0.47 | |||
Minimum of Months | 0.00 | 0.00 | 0.405710E+09 | 0.325660E+09 | 18328.76 | 11516.11 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.115456E+11 | 0.595004E+10 | 24588.44 | 20000.54 | 0.92 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 124843.21 | 493651.75 | 31-JAN-04:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 113203.22 | 525437.76 | 02-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 39783.37 | 179927.29 | 09-MAR-16:12 |
April | 0.00 | 0.00 | 01-APR-00:10 | 24809.96 | 182852.21 | 27-APR-15:12 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5791.78 | 113464.74 | 02-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1011.62 | 50207.35 | 03-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.32 | 16772.35 | 11-JUL-08:55 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 78.60 | 40905.61 | 08-AUG-15:17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 6761.26 | 112590.03 | 30-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28238.92 | 157122.24 | 26-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 51988.10 | 465869.29 | 26-NOV-07:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 65440.07 | 227223.49 | 11-DEC-09:05 |
Annual Sum or Average | 0.00 | 38073.79 | ||||
Minimum of Months | 0.00 | 0.00 | 21.32 | 16772.35 | ||
Maximum of Months | 0.00 | 0.00 | 124843.21 | 525437.76 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 929.94 | 21972.27 | 17-JAN-19:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 1555.14 | 47001.80 | 25-FEB-09:02 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 5569.55 | 136702.55 | 25-MAR-15:11 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 33774.16 | 451942.29 | 18-APR-15:13 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74310.84 | 455570.24 | 31-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 179676.17 | 540370.45 | 26-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 240522.31 | 638536.72 | 26-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 210402.90 | 599928.38 | 28-AUG-21:52 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 99784.95 | 477960.97 | 06-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 17157.91 | 250119.54 | 20-OCT-15:12 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5085.66 | 140860.63 | 05-NOV-15:11 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1688.45 | 35470.11 | 03-DEC-09:02 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 73044.42 | 0.00 | ||||
Minimum of Months | 929.94 | 21972.27 | 0.00 | 0.00 | ||
Maximum of Months | 240522.31 | 638536.72 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 30280.18 | 64226.10 | 31-JAN-07:52 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 30891.29 | 64647.26 | 21-FEB-07:50 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 30606.82 | 64549.59 | 01-MAR-07:58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29423.48 | 62712.86 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 27697.25 | 59738.33 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25881.35 | 55777.68 | 01-JUN-06:58 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24429.59 | 52098.94 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23803.14 | 50021.52 | 01-AUG-06:58 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24109.57 | 51198.31 | 29-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25290.43 | 54506.42 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27028.68 | 58340.51 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 28847.49 | 61751.36 | 29-DEC-07:54 |
Annual Sum or Average | 0.00 | 27336.58 | ||||
Minimum of Months | 0.00 | 0.00 | 23803.14 | 50021.52 | ||
Maximum of Months | 0.00 | 0.00 | 30891.29 | 64647.26 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261333E+10 | 0.70 | 1299.30 | 02-JAN-16:11 | 0.92 |
February | 0.236042E+10 | 0.70 | 1299.30 | 01-FEB-10:00 | 0.93 |
March | 0.261333E+10 | 0.70 | 1299.30 | 06-MAR-16:12 | 0.92 |
April | 0.252903E+10 | 0.70 | 1299.30 | 15-APR-08:51 | 0.91 |
May | 0.261333E+10 | 0.70 | 1299.30 | 02-MAY-08:61 | 0.92 |
June | 0.252903E+10 | 0.70 | 1299.30 | 08-JUN-21:52 | 0.91 |
July | 0.261333E+10 | 0.70 | 1299.30 | 01-JUL-18:17 | 0.91 |
August | 0.261333E+10 | 0.70 | 1299.30 | 01-AUG-21:53 | 0.91 |
September | 0.252903E+10 | 0.70 | 1299.30 | 02-SEP-21:51 | 0.91 |
October | 0.261333E+10 | 0.70 | 1299.30 | 08-OCT-08:62 | 0.92 |
November | 0.252903E+10 | 0.70 | 1299.30 | 01-NOV-08:62 | 0.92 |
December | 0.261333E+10 | 0.70 | 1299.30 | 06-DEC-16:11 | 0.92 |
Annual Sum or Average | 0.307698E+11 | 0.70 | |||
Minimum of Months | 0.236042E+10 | 0.70 | 1299.30 | 0.91 | |
Maximum of Months | 0.261333E+10 | 0.70 | 1299.30 | 0.93 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.369937E+11 | 0.89 | 20332.52 | 09-JAN-19:50 | 1.12 |
February | 0.336843E+11 | 0.90 | 20346.77 | 20-FEB-20:10 | 1.12 |
March | 0.388864E+11 | 0.92 | 20338.31 | 06-MAR-20:00 | 1.12 |
April | 0.383237E+11 | 0.92 | 24314.52 | 18-APR-21:10 | 1.23 |
May | 0.404900E+11 | 0.93 | 25467.19 | 31-MAY-21:10 | 1.27 |
June | 0.405165E+11 | 0.95 | 28278.89 | 26-JUN-21:20 | 1.35 |
July | 0.422479E+11 | 0.95 | 26836.87 | 03-JUL-21:20 | 1.31 |
August | 0.421918E+11 | 0.95 | 26702.06 | 02-AUG-21:20 | 1.30 |
September | 0.400890E+11 | 0.94 | 28574.16 | 07-SEP-21:10 | 1.36 |
October | 0.400312E+11 | 0.93 | 22907.52 | 20-OCT-21:10 | 1.20 |
November | 0.376855E+11 | 0.92 | 21757.98 | 17-NOV-19:20 | 1.16 |
December | 0.379515E+11 | 0.90 | 20559.47 | 01-DEC-19:40 | 1.13 |
Annual Sum or Average | 0.469092E+12 | 0.92 | |||
Minimum of Months | 0.336843E+11 | 0.89 | 20332.52 | 1.12 | |
Maximum of Months | 0.422479E+11 | 0.95 | 28574.16 | 1.36 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:05 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:05 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:05 | 0.28 |
April | 0.198586E+09 | 0.28 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.28 | 76.61 | 01-MAY-00:10 | 0.28 |
June | 0.198586E+09 | 0.28 | 76.61 | 01-JUN-00:10 | 0.28 |
July | 0.205205E+09 | 0.28 | 76.61 | 01-JUL-00:10 | 0.28 |
August | 0.205205E+09 | 0.28 | 76.61 | 01-AUG-00:10 | 0.28 |
September | 0.198586E+09 | 0.28 | 76.61 | 01-SEP-00:10 | 0.28 |
October | 0.205205E+09 | 0.28 | 76.61 | 01-OCT-00:10 | 0.28 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:10 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:05 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.28 | |||
Minimum of Months | 0.185347E+09 | 0.28 | 76.61 | 0.28 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.20 | 612.92 | 01-JAN-07:10 | 0.28 |
February | 0.105030E+10 | 0.20 | 612.92 | 01-FEB-07:05 | 0.28 |
March | 0.116283E+10 | 0.20 | 612.92 | 01-MAR-07:05 | 0.28 |
April | 0.112532E+10 | 0.20 | 612.92 | 01-APR-06:10 | 0.28 |
May | 0.116283E+10 | 0.20 | 612.92 | 01-MAY-06:05 | 0.28 |
June | 0.112532E+10 | 0.20 | 612.92 | 01-JUN-06:05 | 0.28 |
July | 0.116283E+10 | 0.20 | 612.92 | 01-JUL-06:05 | 0.28 |
August | 0.116283E+10 | 0.20 | 612.92 | 01-AUG-06:05 | 0.28 |
September | 0.112532E+10 | 0.20 | 612.92 | 01-SEP-06:05 | 0.28 |
October | 0.116283E+10 | 0.20 | 612.92 | 01-OCT-06:10 | 0.28 |
November | 0.112532E+10 | 0.20 | 612.92 | 01-NOV-06:05 | 0.28 |
December | 0.116283E+10 | 0.20 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.20 | |||
Minimum of Months | 0.105030E+10 | 0.20 | 612.92 | 0.28 | |
Maximum of Months | 0.116283E+10 | 0.20 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.684912E+09 | 0.52 | 796.59 | 01-JAN-09:02 | 0.60 |
February | 0.459786E+09 | 0.48 | 796.59 | 01-FEB-03:30 | 0.61 |
March | 0.257471E+09 | 0.44 | 796.59 | 01-MAR-09:02 | 0.60 |
April | 0.224583E+09 | 0.48 | 796.59 | 01-APR-08:62 | 0.60 |
May | 0.208309E+09 | 0.50 | 796.59 | 01-MAY-15:11 | 0.60 |
June | 0.331221E+09 | 0.54 | 796.59 | 01-JUN-08:61 | 0.60 |
July | 0.404872E+09 | 0.56 | 796.59 | 01-JUL-08:61 | 0.60 |
August | 0.361650E+09 | 0.56 | 796.59 | 01-AUG-08:61 | 0.60 |
September | 0.265714E+09 | 0.52 | 796.59 | 01-SEP-08:62 | 0.60 |
October | 0.164032E+09 | 0.45 | 796.59 | 01-OCT-15:11 | 0.60 |
November | 0.320067E+09 | 0.46 | 796.59 | 03-NOV-15:11 | 0.60 |
December | 0.510955E+09 | 0.50 | 796.59 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.419357E+10 | 0.50 | |||
Minimum of Months | 0.164032E+09 | 0.44 | 796.59 | 0.60 | |
Maximum of Months | 0.684912E+09 | 0.56 | 796.59 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.787253E+09 | 0.57 | 771.36 | 01-JAN-09:02 | 0.60 |
February | 0.523964E+09 | 0.52 | 771.36 | 01-FEB-00:05 | 0.61 |
March | 0.275185E+09 | 0.44 | 771.36 | 01-MAR-09:02 | 0.60 |
April | 0.189726E+09 | 0.43 | 771.36 | 01-APR-08:62 | 0.60 |
May | 0.140040E+09 | 0.40 | 771.36 | 01-MAY-15:11 | 0.60 |
June | 0.259651E+09 | 0.42 | 771.36 | 01-JUN-08:61 | 0.60 |
July | 0.304011E+09 | 0.41 | 771.36 | 01-JUL-08:51 | 0.60 |
August | 0.249005E+09 | 0.41 | 771.36 | 01-AUG-08:51 | 0.60 |
September | 0.178377E+09 | 0.41 | 771.36 | 01-SEP-08:51 | 0.60 |
October | 0.158636E+09 | 0.40 | 771.36 | 01-OCT-18:42 | 0.60 |
November | 0.363755E+09 | 0.47 | 771.36 | 01-NOV-08:62 | 0.60 |
December | 0.566949E+09 | 0.55 | 771.36 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.399655E+10 | 0.45 | |||
Minimum of Months | 0.140040E+09 | 0.40 | 771.36 | 0.60 | |
Maximum of Months | 0.787253E+09 | 0.57 | 771.36 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.656732E+09 | 0.23 | 1293.62 | 19-JAN-05:00 | 0.61 |
February | 0.131729E+09 | 0.05 | 1090.16 | 04-FEB-06:00 | 0.61 |
March | 0.114563E+09 | 0.08 | 965.46 | 24-MAR-13:10 | 0.60 |
April | 0.393394E+09 | 0.20 | 1427.90 | 15-APR-13:30 | 0.60 |
May | 0.804062E+09 | 0.46 | 1078.20 | 06-MAY-13:00 | 0.60 |
June | 0.110745E+10 | 0.52 | 1116.04 | 26-JUN-12:50 | 0.60 |
July | 0.137406E+10 | 0.59 | 1204.53 | 30-JUL-13:30 | 0.60 |
August | 0.141727E+10 | 0.59 | 1360.10 | 29-AUG-13:30 | 0.60 |
September | 0.120526E+10 | 0.47 | 2298.38 | 07-SEP-12:50 | 0.60 |
October | 0.587046E+09 | 0.28 | 2438.05 | 20-OCT-14:00 | 0.60 |
November | 0.225387E+09 | 0.12 | 2369.94 | 04-NOV-13:00 | 0.60 |
December | 0.471169E+09 | 0.18 | 1095.53 | 12-DEC-05:00 | 0.61 |
Annual Sum or Average | 0.848813E+10 | 0.32 | |||
Minimum of Months | 0.114563E+09 | 0.05 | 965.46 | 0.60 | |
Maximum of Months | 0.141727E+10 | 0.59 | 2438.05 | 0.61 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.356579E+10 | 0.48 | 3875.20 | 01-JAN-16:12 | 0.60 |
February | 0.253947E+10 | 0.45 | 3875.20 | 01-FEB-00:05 | 0.61 |
March | 0.105215E+10 | 0.40 | 3875.20 | 01-MAR-09:02 | 0.60 |
April | 0.796513E+09 | 0.39 | 3875.20 | 01-APR-08:62 | 0.60 |
May | 0.117242E+10 | 0.35 | 3875.20 | 01-MAY-08:61 | 0.60 |
June | 0.182551E+10 | 0.38 | 3875.20 | 01-JUN-08:61 | 0.60 |
July | 0.192684E+10 | 0.36 | 3875.20 | 01-JUL-08:51 | 0.60 |
August | 0.164385E+10 | 0.35 | 3875.20 | 01-AUG-08:51 | 0.60 |
September | 0.109681E+10 | 0.37 | 3875.20 | 01-SEP-08:51 | 0.60 |
October | 0.581356E+09 | 0.40 | 3875.20 | 01-OCT-08:61 | 0.60 |
November | 0.141353E+10 | 0.42 | 3875.20 | 01-NOV-15:11 | 0.60 |
December | 0.237046E+10 | 0.44 | 3875.20 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.199847E+11 | 0.40 | |||
Minimum of Months | 0.581356E+09 | 0.35 | 3875.20 | 0.60 | |
Maximum of Months | 0.356579E+10 | 0.48 | 3875.20 | 0.61 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.653018E+09 | 0.53 | 722.86 | 01-JAN-09:02 | 0.60 |
February | 0.434773E+09 | 0.48 | 722.86 | 01-FEB-01:40 | 0.61 |
March | 0.237656E+09 | 0.45 | 722.86 | 01-MAR-09:02 | 0.60 |
April | 0.205805E+09 | 0.49 | 722.86 | 01-APR-08:62 | 0.60 |
May | 0.213329E+09 | 0.53 | 722.86 | 01-MAY-08:61 | 0.60 |
June | 0.328708E+09 | 0.56 | 722.86 | 01-JUN-08:61 | 0.60 |
July | 0.384995E+09 | 0.58 | 722.86 | 01-JUL-08:61 | 0.60 |
August | 0.337646E+09 | 0.57 | 722.86 | 01-AUG-08:61 | 0.60 |
September | 0.255706E+09 | 0.53 | 722.86 | 01-SEP-08:62 | 0.60 |
October | 0.148869E+09 | 0.46 | 722.86 | 01-OCT-08:61 | 0.60 |
November | 0.305115E+09 | 0.46 | 722.86 | 03-NOV-15:11 | 0.60 |
December | 0.486008E+09 | 0.51 | 722.86 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.399163E+10 | 0.51 | |||
Minimum of Months | 0.148869E+09 | 0.45 | 722.86 | 0.60 | |
Maximum of Months | 0.653018E+09 | 0.58 | 722.86 | 0.61 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.747740E+09 | 0.57 | 701.40 | 01-JAN-09:02 | 0.60 |
February | 0.505818E+09 | 0.51 | 701.40 | 01-FEB-00:05 | 0.61 |
March | 0.256989E+09 | 0.43 | 701.40 | 01-MAR-09:02 | 0.60 |
April | 0.180245E+09 | 0.43 | 701.40 | 01-APR-08:62 | 0.60 |
May | 0.156900E+09 | 0.44 | 701.40 | 01-MAY-08:61 | 0.60 |
June | 0.264938E+09 | 0.44 | 701.40 | 01-JUN-08:61 | 0.60 |
July | 0.290643E+09 | 0.42 | 701.40 | 01-JUL-08:32 | 0.60 |
August | 0.238745E+09 | 0.42 | 701.40 | 01-AUG-08:32 | 0.60 |
September | 0.174865E+09 | 0.43 | 701.40 | 01-SEP-08:51 | 0.60 |
October | 0.145224E+09 | 0.40 | 701.40 | 01-OCT-08:61 | 0.60 |
November | 0.342888E+09 | 0.48 | 701.40 | 04-NOV-08:62 | 0.60 |
December | 0.552626E+09 | 0.56 | 701.40 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.385762E+10 | 0.46 | |||
Minimum of Months | 0.145224E+09 | 0.40 | 701.40 | 0.60 | |
Maximum of Months | 0.747740E+09 | 0.57 | 701.40 | 0.61 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.212501E+09 | 0.55 | 207.81 | 01-JAN-09:02 | 0.60 |
February | 0.140519E+09 | 0.52 | 207.81 | 01-FEB-01:20 | 0.61 |
March | 80231401.66 | 0.46 | 207.81 | 01-MAR-09:02 | 0.60 |
April | 66967293.34 | 0.48 | 207.81 | 01-APR-08:62 | 0.60 |
May | 56393894.85 | 0.50 | 207.81 | 01-MAY-15:11 | 0.60 |
June | 88764343.85 | 0.54 | 207.81 | 01-JUN-08:61 | 0.60 |
July | 0.105632E+09 | 0.56 | 207.81 | 01-JUL-08:61 | 0.60 |
August | 91840400.18 | 0.55 | 207.81 | 01-AUG-08:61 | 0.59 |
September | 70517888.02 | 0.51 | 207.81 | 01-SEP-15:11 | 0.60 |
October | 51676088.22 | 0.44 | 207.81 | 01-OCT-15:11 | 0.60 |
November | 0.102727E+09 | 0.48 | 207.81 | 01-NOV-08:62 | 0.60 |
December | 0.161678E+09 | 0.53 | 207.81 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.122945E+10 | 0.51 | |||
Minimum of Months | 51676088.22 | 0.44 | 207.81 | 0.59 | |
Maximum of Months | 0.212501E+09 | 0.56 | 207.81 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.240977E+09 | 0.59 | 200.72 | 01-JAN-09:02 | 0.60 |
February | 0.160911E+09 | 0.55 | 200.72 | 01-FEB-00:05 | 0.61 |
March | 87501583.34 | 0.47 | 200.72 | 01-MAR-09:02 | 0.60 |
April | 57636984.34 | 0.43 | 200.72 | 01-APR-08:62 | 0.60 |
May | 38572204.08 | 0.41 | 200.72 | 01-MAY-15:11 | 0.60 |
June | 72194783.91 | 0.42 | 200.72 | 01-JUN-08:61 | 0.60 |
July | 82711577.82 | 0.41 | 200.72 | 01-JUL-08:51 | 0.60 |
August | 64657132.17 | 0.41 | 200.72 | 01-AUG-08:51 | 0.59 |
September | 48910787.58 | 0.41 | 200.72 | 01-SEP-08:51 | 0.60 |
October | 50929517.60 | 0.40 | 200.72 | 01-OCT-08:61 | 0.60 |
November | 0.113465E+09 | 0.50 | 200.72 | 01-NOV-08:62 | 0.60 |
December | 0.185983E+09 | 0.58 | 200.72 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.120445E+10 | 0.46 | |||
Minimum of Months | 38572204.08 | 0.40 | 200.72 | 0.59 | |
Maximum of Months | 0.240977E+09 | 0.59 | 200.72 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.711369E+09 | 0.49 | 953.52 | 01-JAN-09:02 | 0.60 |
February | 0.475124E+09 | 0.47 | 953.52 | 01-FEB-05:40 | 0.61 |
March | 0.310494E+09 | 0.48 | 953.52 | 01-MAR-09:02 | 0.60 |
April | 0.297310E+09 | 0.49 | 953.52 | 01-APR-15:12 | 0.60 |
May | 0.263898E+09 | 0.51 | 953.52 | 01-MAY-08:61 | 0.60 |
June | 0.374375E+09 | 0.54 | 953.52 | 01-JUN-08:61 | 0.60 |
July | 0.449881E+09 | 0.55 | 953.52 | 01-JUL-08:61 | 0.60 |
August | 0.450300E+09 | 0.55 | 953.52 | 01-AUG-08:61 | 0.59 |
September | 0.397898E+09 | 0.53 | 953.52 | 01-SEP-08:62 | 0.60 |
October | 0.270353E+09 | 0.49 | 953.52 | 01-OCT-08:61 | 0.60 |
November | 0.365560E+09 | 0.47 | 953.52 | 01-NOV-15:11 | 0.60 |
December | 0.583537E+09 | 0.51 | 953.52 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.495010E+10 | 0.51 | |||
Minimum of Months | 0.263898E+09 | 0.47 | 953.52 | 0.59 | |
Maximum of Months | 0.711369E+09 | 0.55 | 953.52 | 0.61 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.210199E+10 | 0.191071E+10 | 1606.66 | 31-JAN-05:00 | 1460.45 | 1460.45 | 37.44 | 5.22 |
February | 0.164088E+10 | 0.149156E+10 | 1635.66 | 03-FEB-04:00 | 1486.81 | 1486.81 | 36.83 | 5.31 |
March | 0.104420E+10 | 0.949175E+09 | 940.26 | 15-MAR-15:11 | 854.69 | 854.69 | 50.13 | 1.43 |
April | 0.572711E+09 | 0.520594E+09 | 948.32 | 27-APR-15:12 | 862.02 | 862.02 | 30.11 | 1.46 |
May | 0.113672E+09 | 0.103328E+09 | 707.92 | 03-MAY-03:00 | 643.50 | 643.50 | 35.52 | 0.94 |
June | 24512846.48 | 22282177.45 | 396.09 | 03-JUN-04:00 | 360.04 | 360.04 | 33.92 | 0.46 |
July | 734970.09 | 668087.81 | 180.44 | 09-JUL-08:57 | 164.02 | 164.02 | 43.63 | 0.19 |
August | 2002988.00 | 1820716.09 | 311.39 | 18-AUG-08:54 | 283.05 | 283.05 | 41.34 | 0.35 |
September | 0.145101E+09 | 0.131897E+09 | 813.56 | 30-SEP-05:00 | 739.52 | 739.52 | 41.69 | 1.14 |
October | 0.624199E+09 | 0.567397E+09 | 877.72 | 26-OCT-08:03 | 797.85 | 797.85 | 30.82 | 1.29 |
November | 0.110807E+10 | 0.100723E+10 | 1512.72 | 26-NOV-07:00 | 1375.07 | 1375.07 | 37.25 | 4.90 |
December | 0.163979E+10 | 0.149057E+10 | 1155.14 | 12-DEC-10:30 | 1050.02 | 1050.02 | 36.90 | 2.19 |
Annual Sum or Average | 0.901786E+10 | 0.819724E+10 | ||||||
Minimum of Months | 734970.09 | 668087.81 | 180.44 | 164.02 | 164.02 | 30.11 | 0.19 | |
Maximum of Months | 0.210199E+10 | 0.191071E+10 | 1635.66 | 1486.81 | 1486.81 | 50.13 | 5.31 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 115203.77 | 104720.23 | 5.10 | 12-JAN-16:17 | 4.64 | 4.64 | 6.72 | 0.90 |
February | 325251.80 | 295653.89 | 27.32 | 25-FEB-09:02 | 24.83 | 24.83 | 6.72 | 2.58 |
March | 3719452.63 | 3380982.44 | 79.57 | 24-MAR-15:11 | 72.33 | 72.33 | 6.72 | 4.57 |
April | 59288147.36 | 53892925.95 | 600.21 | 16-APR-18:03 | 545.59 | 545.59 | 6.72 | 11.80 |
May | 0.118431E+09 | 0.107654E+09 | 653.07 | 31-MAY-18:03 | 593.64 | 593.64 | 6.72 | 12.24 |
June | 0.391517E+09 | 0.355889E+09 | 931.65 | 26-JUN-18:03 | 846.87 | 846.87 | 6.72 | 14.25 |
July | 0.552421E+09 | 0.502151E+09 | 1206.34 | 26-JUL-18:03 | 1096.56 | 1096.56 | 6.72 | 15.89 |
August | 0.462517E+09 | 0.420428E+09 | 1054.62 | 03-AUG-18:03 | 958.65 | 958.65 | 6.72 | 15.02 |
September | 0.194163E+09 | 0.176494E+09 | 695.05 | 06-SEP-18:03 | 631.80 | 631.80 | 6.72 | 12.57 |
October | 17905860.31 | 16276427.02 | 156.34 | 01-OCT-15:13 | 142.11 | 142.11 | 6.72 | 6.38 |
November | 3535015.98 | 3213329.53 | 135.18 | 05-NOV-15:11 | 122.87 | 122.87 | 6.72 | 5.95 |
December | 227371.54 | 206680.73 | 12.98 | 03-DEC-09:02 | 11.80 | 11.80 | 6.72 | 1.66 |
Annual Sum or Average | 0.180417E+10 | 0.163999E+10 | ||||||
Minimum of Months | 115203.77 | 104720.23 | 5.10 | 4.64 | 4.64 | 6.72 | 0.90 | |
Maximum of Months | 0.552421E+09 | 0.502151E+09 | 1206.34 | 1096.56 | 1096.56 | 6.72 | 15.89 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.208889E+10 | 0.189880E+10 | 2983.00 | 01-JAN-00:05 | 2711.54 | 2711.54 | 6.73 | 26.65 |
February | 0.266972E+10 | 0.242678E+10 | 2983.00 | 01-FEB-16:12 | 2711.54 | 2711.54 | 6.78 | 26.65 |
March | 0.461467E+10 | 0.419474E+10 | 2983.00 | 01-MAR-00:05 | 2711.54 | 2711.54 | 6.73 | 26.65 |
April | 0.563986E+10 | 0.512663E+10 | 2983.00 | 01-APR-00:30 | 2711.54 | 2711.54 | 6.72 | 26.65 |
May | 0.782395E+10 | 0.711197E+10 | 2983.00 | 01-MAY-00:10 | 2711.54 | 2711.54 | 6.77 | 26.65 |
June | 0.759829E+10 | 0.690684E+10 | 2983.00 | 01-JUN-00:10 | 2711.54 | 2711.54 | 7.15 | 26.65 |
July | 0.798966E+10 | 0.726260E+10 | 2983.00 | 01-JUL-00:10 | 2711.54 | 2711.54 | 7.98 | 26.65 |
August | 0.798966E+10 | 0.726260E+10 | 2983.00 | 01-AUG-00:10 | 2711.54 | 2711.54 | 8.61 | 26.65 |
September | 0.721945E+10 | 0.656248E+10 | 2983.00 | 01-SEP-00:10 | 2711.54 | 2711.54 | 7.58 | 26.65 |
October | 0.572848E+10 | 0.520719E+10 | 2983.00 | 01-OCT-06:30 | 2711.54 | 2711.54 | 6.73 | 26.65 |
November | 0.411707E+10 | 0.374242E+10 | 2983.00 | 01-NOV-05:20 | 2711.54 | 2711.54 | 6.74 | 26.65 |
December | 0.372610E+10 | 0.338702E+10 | 2983.00 | 01-DEC-00:05 | 2711.54 | 2711.54 | 6.73 | 26.65 |
Annual Sum or Average | 0.672058E+11 | 0.610901E+11 | ||||||
Minimum of Months | 0.208889E+10 | 0.189880E+10 | 2983.00 | 2711.54 | 2711.54 | 6.72 | 26.65 | |
Maximum of Months | 0.798966E+10 | 0.726260E+10 | 2983.00 | 2711.54 | 2711.54 | 8.61 | 26.65 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 47.29 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 48.18 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 48.13 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.48 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 51.90 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 52.44 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.92 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 53.23 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 53.27 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.20 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.60 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 49.25 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 47.29 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.27 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 46.32 | 60.00 | 124843.21 | 493651.75 | 31-JAN-04:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 37.49 | 60.00 | 113203.22 | 525437.76 | 02-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 40.30 | 60.00 | 39783.37 | 179927.29 | 09-MAR-16:12 |
April | 0.00 | 0.00 | 01-APR-00:10 | 49.58 | 60.00 | 24809.96 | 182852.21 | 27-APR-15:12 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.92 | 60.00 | 5791.78 | 113464.74 | 02-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 48.75 | 48.75 | 1011.62 | 50207.35 | 03-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 41.02 | 41.02 | 21.32 | 16772.35 | 11-JUL-08:55 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 45.70 | 45.70 | 78.60 | 40905.61 | 08-AUG-15:17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 46.90 | 46.90 | 6761.26 | 112590.03 | 30-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 35.76 | 60.00 | 28238.92 | 157122.24 | 26-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 36.09 | 60.00 | 51988.10 | 465869.29 | 26-NOV-07:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 40.21 | 60.00 | 65440.07 | 227223.49 | 11-DEC-09:05 |
Annual Sum or Average | 0.00 | 38073.79 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.92 | 41.02 | 21.32 | 16772.35 | ||
Maximum of Months | 0.00 | 0.00 | 49.58 | 60.00 | 124843.21 | 525437.76 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 929.94 | 21972.27 | 17-JAN-19:05 | 6.90 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 1555.14 | 47001.80 | 25-FEB-09:02 | 7.12 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 5569.55 | 136702.55 | 25-MAR-15:11 | 7.92 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 33774.16 | 451942.29 | 18-APR-15:13 | 10.75 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74310.84 | 455570.24 | 31-MAY-18:03 | 10.78 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 179676.17 | 540370.45 | 26-JUN-18:03 | 11.54 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 240522.31 | 638536.72 | 26-JUL-18:03 | 12.42 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 210402.90 | 599928.38 | 28-AUG-21:52 | 12.07 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 99784.95 | 477960.97 | 06-SEP-18:03 | 10.98 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 17157.91 | 250119.54 | 20-OCT-15:12 | 8.94 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5085.66 | 140860.63 | 05-NOV-15:11 | 7.96 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1688.45 | 35470.11 | 03-DEC-09:02 | 7.02 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 73044.42 | 0.00 | ||||||
Minimum of Months | 929.94 | 21972.27 | 6.90 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 240522.31 | 638536.72 | 12.42 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 47.29 | 60.05 | 30280.18 | 64226.10 | 31-JAN-07:52 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 48.18 | 60.05 | 30891.29 | 64647.26 | 21-FEB-07:50 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 48.13 | 60.05 | 30606.82 | 64549.59 | 01-MAR-07:58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.48 | 60.05 | 29423.48 | 62712.86 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 51.90 | 60.05 | 27697.25 | 59738.33 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 52.44 | 60.05 | 25881.35 | 55777.68 | 01-JUN-06:58 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.92 | 60.05 | 24429.59 | 52098.94 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 53.23 | 60.05 | 23803.14 | 50021.52 | 01-AUG-06:58 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 53.27 | 60.05 | 24109.57 | 51198.31 | 29-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.20 | 60.05 | 25290.43 | 54506.42 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.60 | 60.05 | 27028.68 | 58340.51 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 49.25 | 60.05 | 28847.49 | 61751.36 | 29-DEC-07:54 |
Annual Sum or Average | 0.00 | 27336.58 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.29 | 60.05 | 23803.14 | 50021.52 | ||
Maximum of Months | 0.00 | 0.00 | 53.27 | 60.05 | 30891.29 | 64647.26 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.158867E+11 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
February | 0.107824E+11 | 0.00 | 0.00 | 0.236042E+10 | 0.00 | 0.00 |
March | 0.230196E+10 | 0.00 | 0.189758E+09 | 0.261333E+10 | 0.00 | 0.00 |
April | 0.429663E+09 | 0.00 | 0.306682E+10 | 0.252903E+10 | 0.00 | 0.00 |
May | 9067.63 | 0.00 | 0.699804E+10 | 0.261333E+10 | 0.00 | 0.00 |
June | 13732.99 | 0.00 | 0.229820E+11 | 0.252903E+10 | 0.00 | 0.00 |
July | 12689.97 | 0.00 | 0.347628E+11 | 0.261333E+10 | 0.00 | 0.00 |
August | 14816.65 | 0.00 | 0.283337E+11 | 0.261333E+10 | 0.00 | 0.00 |
September | 298774.85 | 0.00 | 0.103411E+11 | 0.252903E+10 | 0.00 | 0.00 |
October | 21218989.19 | 0.00 | 0.596914E+09 | 0.261333E+10 | 0.00 | 0.00 |
November | 0.377405E+10 | 0.00 | 22232899.69 | 0.252903E+10 | 0.00 | 0.00 |
December | 0.675702E+10 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.399534E+11 | 0.00 | 0.107293E+12 | 0.307698E+11 | 0.00 | 0.00 |
Minimum of Months | 9067.63 | 0.00 | 0.00 | 0.236042E+10 | 0.00 | 0.00 |
Maximum of Months | 0.158867E+11 | 0.00 | 0.347628E+11 | 0.261333E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.211292E+12 | 0.00 | 0.154201E+09 | 0.369937E+11 | 0.00 | 0.00 |
February | 0.194278E+12 | 0.00 | 0.177605E+09 | 0.336843E+11 | 0.00 | 0.00 |
March | 0.707546E+11 | 0.00 | 0.353060E+10 | 0.388864E+11 | 0.00 | 0.00 |
April | 0.513250E+11 | 0.00 | 0.468361E+11 | 0.383237E+11 | 0.00 | 0.00 |
May | 0.148608E+11 | 0.00 | 0.112493E+12 | 0.404900E+11 | 0.00 | 0.00 |
June | 0.235397E+10 | 0.00 | 0.319398E+12 | 0.405165E+11 | 0.00 | 0.00 |
July | 22850968.52 | 0.00 | 0.463873E+12 | 0.422479E+11 | 0.00 | 0.00 |
August | 0.162565E+09 | 0.00 | 0.399658E+12 | 0.421918E+11 | 0.00 | 0.00 |
September | 0.156557E+11 | 0.00 | 0.154441E+12 | 0.400890E+11 | 0.00 | 0.00 |
October | 0.657946E+11 | 0.00 | 0.114415E+11 | 0.400312E+11 | 0.00 | 0.00 |
November | 0.878108E+11 | 0.00 | 0.771668E+09 | 0.376855E+11 | 0.00 | 0.00 |
December | 0.830892E+11 | 0.00 | 0.285675E+09 | 0.379515E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.797400E+12 | 0.00 | 0.151306E+13 | 0.469092E+12 | 0.00 | 0.00 |
Minimum of Months | 22850968.52 | 0.00 | 0.154201E+09 | 0.336843E+11 | 0.00 | 0.00 |
Maximum of Months | 0.211292E+12 | 0.00 | 0.463873E+12 | 0.422479E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261333E+10 | 0.00 | 0.158867E+11 | 0.677208E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.00 | 0.107824E+11 | 0.508495E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.189758E+09 | 0.230196E+10 | 0.522867E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.306682E+10 | 0.429663E+09 | 0.324376E+11 | 0.652833E+09 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.699804E+10 | 9067.63 | 0.104024E+11 | 0.572709E+09 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.229820E+11 | 13732.99 | 0.339198E+10 | 0.616506E+10 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 0.347628E+11 | 12689.97 | 0.460868E+09 | 0.740450E+10 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 0.283337E+11 | 14816.65 | 0.115043E+10 | 0.648637E+10 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.103411E+11 | 298774.85 | 0.110297E+11 | 0.145165E+10 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.596914E+09 | 21218989.19 | 0.316557E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 22232899.69 | 0.377405E+10 | 0.475903E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.00 | 0.675702E+10 | 0.715976E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.107293E+12 | 0.399534E+11 | 0.380574E+12 | 0.227331E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 0.00 | 9067.63 | 0.460868E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.347628E+11 | 0.158867E+11 | 0.715976E+11 | 0.740450E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.369937E+11 | 0.154201E+09 | 0.211292E+12 | 0.472617E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336843E+11 | 0.177605E+09 | 0.194278E+12 | 0.268678E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388864E+11 | 0.353060E+10 | 0.707546E+11 | 0.233367E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.383237E+11 | 0.468361E+11 | 0.513250E+11 | 0.867596E+11 | 0.372971E+10 | 0.00 | 0.00 | 0.00 |
May | 0.404900E+11 | 0.112493E+12 | 0.148608E+11 | 0.437442E+09 | 0.309814E+10 | 0.00 | 0.00 | 0.00 |
June | 0.405165E+11 | 0.319398E+12 | 0.235397E+10 | 0.983025E+09 | 0.327378E+11 | 0.00 | 0.00 | 0.00 |
July | 0.422479E+11 | 0.463873E+12 | 22850968.52 | 0.495344E+09 | 0.388315E+11 | 0.00 | 0.00 | 0.00 |
August | 0.421918E+11 | 0.399658E+12 | 0.162565E+09 | 0.958329E+09 | 0.337218E+11 | 0.00 | 0.00 | 0.00 |
September | 0.400890E+11 | 0.154441E+12 | 0.156557E+11 | 0.363009E+10 | 0.547583E+10 | 0.00 | 0.00 | 0.00 |
October | 0.400312E+11 | 0.114415E+11 | 0.657946E+11 | 0.201424E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.376855E+11 | 0.771668E+09 | 0.878108E+11 | 0.219608E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379515E+11 | 0.285675E+09 | 0.830892E+11 | 0.483383E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.469092E+12 | 0.151306E+13 | 0.797400E+12 | 0.179106E+13 | 0.117595E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.336843E+11 | 0.154201E+09 | 22850968.52 | 0.437442E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.422479E+11 | 0.463873E+12 | 0.211292E+12 | 0.483383E+12 | 0.388315E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261333E+10 | 0.158867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.107824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.230196E+10 | 0.189758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.429663E+09 | 0.306682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 9067.63 | 0.699804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 13732.99 | 0.229820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 12689.97 | 0.347628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 14816.65 | 0.283337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 298774.85 | 0.103411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 21218989.19 | 0.596914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.377405E+10 | 22232899.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.675702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.399534E+11 | 0.107293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 9067.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.158867E+11 | 0.347628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.369937E+11 | 0.211292E+12 | 0.154201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336843E+11 | 0.194278E+12 | 0.177605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388864E+11 | 0.707546E+11 | 0.353060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.383237E+11 | 0.513250E+11 | 0.468361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.404900E+11 | 0.148608E+11 | 0.112493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.405165E+11 | 0.235397E+10 | 0.319398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.422479E+11 | 22850968.52 | 0.463873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.421918E+11 | 0.162565E+09 | 0.399658E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.400890E+11 | 0.156557E+11 | 0.154441E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.400312E+11 | 0.657946E+11 | 0.114415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.376855E+11 | 0.878108E+11 | 0.771668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379515E+11 | 0.830892E+11 | 0.285675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.469092E+12 | 0.797400E+12 | 0.151306E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.336843E+11 | 22850968.52 | 0.154201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.422479E+11 | 0.211292E+12 | 0.463873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.573345E+11 | 0.00 | 0.00 | 668.92 | 0.00 | 0.00 | 46649094.22 | 0.00 | 0.60 |
February | 0.452059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901118E+10 | 0.00 | 0.00 | 0.60 |
March | 0.467390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
April | 0.423373E+11 | 0.00 | 0.00 | 0.00 | 0.354981E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
May | 0.371648E+11 | 0.00 | 0.00 | 0.00 | 0.521252E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
June | 0.213832E+11 | 0.00 | 0.00 | 0.00 | 0.404372E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
July | 0.135795E+11 | 0.00 | 0.00 | 0.00 | 0.689421E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
August | 0.927843E+10 | 0.107156E+10 | 0.00 | 8135237.41 | 0.487368E+10 | 0.00 | 0.916952E+10 | 0.00 | 0.84 |
September | 0.689654E+10 | 58689977.09 | 0.00 | 29510064.88 | 0.335367E+09 | 0.00 | 0.276266E+11 | 0.00 | 0.81 |
October | 0.819911E+10 | 0.00 | 0.00 | 38004797.11 | 0.00 | 0.00 | 0.433043E+11 | 0.00 | 0.70 |
November | 0.151603E+11 | 0.00 | 0.00 | 29291387.21 | 0.00 | 0.00 | 0.339402E+11 | 0.00 | 0.66 |
December | 0.255515E+11 | 0.00 | 0.00 | 11869694.77 | 0.00 | 0.00 | 0.197985E+11 | 0.00 | 0.60 |
Annual Sum or Average | 0.328830E+12 | 0.113025E+10 | 0.00 | 0.116812E+09 | 0.170232E+11 | 0.901118E+10 | 0.133886E+12 | 0.00 | 0.71 |
Minimum of Months | 0.689654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.573345E+11 | 0.107156E+10 | 0.00 | 38004797.11 | 0.689421E+10 | 0.901118E+10 | 0.433043E+11 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122298E+10 | 0.00 | 0.00 | 156383.95 | 0.00 | 0.448855E+10 | 0.158524E+09 | 0.00 | 1.06 |
February | 0.214325E+10 | 0.00 | 0.00 | 410192.47 | 0.00 | 0.329479E+10 | 0.317248E+09 | 0.00 | 1.08 |
March | 0.298220E+10 | 0.00 | 0.00 | 666694.04 | 0.00 | 0.103141E+10 | 0.412942E+09 | 0.00 | 1.08 |
April | 0.301588E+10 | 66170062.46 | 0.00 | 1391038.88 | 39776.59 | 0.350498E+09 | 0.694818E+09 | 0.00 | 1.24 |
May | 0.283697E+10 | 64960103.20 | 0.00 | 1546692.54 | 1702832.44 | 0.00 | 0.672994E+09 | 0.00 | 1.48 |
June | 0.137713E+10 | 0.538920E+09 | 0.00 | 2375812.55 | 13730108.19 | 0.00 | 0.655980E+09 | 0.00 | 1.57 |
July | 0.642554E+09 | 0.873397E+09 | 0.00 | 2445485.00 | 20277714.90 | 0.00 | 0.656661E+09 | 0.00 | 1.70 |
August | 0.745671E+09 | 0.750376E+09 | 0.00 | 3759662.60 | 36075550.22 | 0.00 | 0.107037E+10 | 0.00 | 1.73 |
September | 0.206262E+10 | 79842263.57 | 0.00 | 4651870.18 | 0.00 | 5334575.42 | 0.126019E+10 | 0.00 | 1.66 |
October | 0.384507E+10 | 0.00 | 0.00 | 2002544.15 | 0.00 | 25108098.51 | 0.106805E+10 | 0.00 | 1.28 |
November | 0.270336E+10 | 0.00 | 0.00 | 609556.69 | 0.00 | 0.154278E+10 | 0.389548E+09 | 0.00 | 1.12 |
December | 0.120033E+10 | 0.00 | 0.00 | 388223.89 | 0.00 | 0.281244E+10 | 0.303394E+09 | 0.00 | 1.03 |
Annual Sum or Average | 0.247780E+11 | 0.237367E+10 | 0.00 | 20404156.92 | 71825982.34 | 0.135509E+11 | 0.766073E+10 | 0.00 | 1.34 |
Minimum of Months | 0.642554E+09 | 0.00 | 0.00 | 156383.95 | 0.00 | 0.00 | 0.158524E+09 | 0.00 | 1.03 |
Maximum of Months | 0.384507E+10 | 0.873397E+09 | 0.00 | 4651870.18 | 36075550.22 | 0.448855E+10 | 0.126019E+10 | 0.00 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.555048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612391E+09 | 0.00 | 0.00 | 1.01 |
February | 0.431819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150486E+10 | 0.00 | 0.00 | 1.01 |
March | 0.501988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
April | 0.431723E+10 | 1962707.65 | 0.00 | 157520.67 | 36163098.75 | 0.00 | 0.230328E+09 | 0.00 | 1.13 |
May | 0.355861E+10 | 2416096.55 | 0.00 | 247839.81 | 53567629.44 | 0.00 | 0.433514E+09 | 0.00 | 1.39 |
June | 0.151072E+10 | 0.121202E+09 | 0.00 | 914690.31 | 0.315122E+09 | 0.00 | 0.789357E+09 | 0.00 | 1.37 |
July | 0.603786E+09 | 0.308691E+09 | 0.00 | 1105833.51 | 0.440357E+09 | 0.00 | 0.858389E+09 | 0.00 | 1.43 |
August | 0.599067E+09 | 0.224017E+09 | 0.00 | 1490907.54 | 0.420604E+09 | 0.00 | 0.139303E+10 | 0.00 | 1.43 |
September | 0.258229E+10 | 8843646.54 | 0.00 | 1068338.10 | 33409393.32 | 0.00 | 0.103984E+10 | 0.00 | 1.33 |
October | 0.515814E+10 | 0.00 | 0.00 | 33638.02 | 0.00 | 0.00 | 0.147856E+09 | 0.00 | 1.12 |
November | 0.511002E+10 | 0.00 | 0.00 | 1420.47 | 0.00 | 0.00 | 14271967.39 | 0.00 | 1.07 |
December | 0.482260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26434267.83 | 0.00 | 0.00 | 1.00 |
Annual Sum or Average | 0.431510E+11 | 0.667133E+09 | 0.00 | 5020188.43 | 0.129922E+10 | 0.214369E+10 | 0.490659E+10 | 0.00 | 1.20 |
Minimum of Months | 0.599067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
Maximum of Months | 0.555048E+10 | 0.308691E+09 | 0.00 | 1490907.54 | 0.440357E+09 | 0.150486E+10 | 0.139303E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 23026651.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116342E+10 | 0.00 | 0.00 | 0.06 |
February | 42205369.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135026E+10 | 0.00 | 0.00 | 0.07 |
March | 60332906.44 | 0.00 | 0.00 | 7545.56 | 0.00 | 12472015.08 | 6135354.33 | 0.00 | 0.01 |
April | 49699975.36 | 9403057.78 | 0.00 | 397567.20 | 0.00 | 0.00 | 0.178975E+09 | 0.00 | 0.04 |
May | 12634871.39 | 14964596.19 | 0.00 | 1401755.88 | 0.00 | 0.00 | 0.622940E+09 | 0.00 | 0.12 |
June | 4652401.12 | 0.201091E+09 | 0.00 | 2000388.44 | 0.00 | 0.00 | 0.621929E+09 | 0.00 | 0.24 |
July | 0.00 | 0.375576E+09 | 0.00 | 2196639.05 | 0.00 | 0.00 | 0.600397E+09 | 0.00 | 0.31 |
August | 0.00 | 0.304388E+09 | 0.00 | 2670010.90 | 0.00 | 0.00 | 0.863097E+09 | 0.00 | 0.30 |
September | 10214572.07 | 17991697.19 | 0.00 | 2381755.46 | 0.00 | 0.00 | 0.854373E+09 | 0.00 | 0.19 |
October | 53373333.69 | 0.00 | 0.00 | 268774.58 | 0.00 | 0.00 | 0.187022E+09 | 0.00 | 0.03 |
November | 50617127.85 | 0.00 | 0.00 | 98522.99 | 0.00 | 88039632.18 | 72184190.64 | 0.00 | 0.02 |
December | 37503130.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189166E+09 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.344260E+09 | 0.923414E+09 | 0.00 | 11422960.06 | 0.00 | 0.280336E+10 | 0.400705E+10 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Maximum of Months | 60332906.44 | 0.375576E+09 | 0.00 | 2670010.90 | 0.00 | 0.135026E+10 | 0.863097E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.182943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369835E+10 | 0.00 | 0.00 | 0.52 |
February | 0.960152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270713E+10 | 0.00 | 0.00 | 0.52 |
March | 0.196538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119607E+10 | 0.00 | 0.00 | 0.54 |
April | 0.267882E+10 | 0.00 | 0.00 | 0.00 | 24011115.42 | 0.184905E+09 | 0.00 | 0.00 | 0.58 |
May | 0.251385E+10 | 0.00 | 0.00 | 0.00 | 35257782.18 | 0.00 | 0.00 | 0.00 | 0.71 |
June | 0.144637E+10 | 0.00 | 0.00 | 0.00 | 0.273520E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
July | 0.918525E+09 | 0.00 | 0.00 | 0.00 | 0.466328E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
August | 0.124692E+10 | 0.00 | 0.00 | 0.00 | 0.402132E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 0.227543E+10 | 0.00 | 0.00 | 0.00 | 26604221.83 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 0.334166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 0.215250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107471E+10 | 0.00 | 0.00 | 0.55 |
December | 0.386955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266690E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.200695E+11 | 0.00 | 0.00 | 0.00 | 0.122785E+10 | 0.115281E+11 | 0.00 | 0.00 | 0.61 |
Minimum of Months | 0.182943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.334166E+10 | 0.00 | 0.00 | 0.00 | 0.466328E+09 | 0.369835E+10 | 0.00 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.106364E+09 | 0.00 | 0.00 | 0.692836E+11 | 0.00 | 12.03 |
February | 0.00 | 0.00 | 0.00 | 95421254.39 | 0.00 | 0.00 | 0.632580E+11 | 0.00 | 11.97 |
March | 0.00 | 0.00 | 0.00 | 0.104964E+09 | 0.00 | 0.00 | 0.658221E+11 | 0.00 | 13.52 |
April | 0.00 | 0.432348E+09 | 0.00 | 0.102088E+09 | 0.00 | 0.00 | 0.594730E+11 | 0.00 | 14.82 |
May | 0.00 | 0.671317E+09 | 0.00 | 0.114946E+09 | 0.00 | 0.00 | 0.527948E+11 | 0.00 | 18.54 |
June | 0.00 | 0.564534E+10 | 0.00 | 86579126.84 | 0.00 | 0.00 | 0.294782E+11 | 0.00 | 18.21 |
July | 0.00 | 0.107008E+11 | 0.00 | 71241880.40 | 0.00 | 0.00 | 0.179560E+11 | 0.00 | 18.98 |
August | 0.00 | 0.876765E+10 | 0.00 | 85858921.71 | 0.00 | 0.00 | 0.256122E+11 | 0.00 | 19.16 |
September | 0.00 | 0.508644E+09 | 0.00 | 0.113127E+09 | 0.00 | 0.00 | 0.481873E+11 | 0.00 | 17.76 |
October | 0.00 | 0.00 | 0.00 | 0.104920E+09 | 0.00 | 0.00 | 0.705775E+11 | 0.00 | 14.82 |
November | 0.00 | 0.00 | 0.00 | 0.101204E+09 | 0.00 | 0.00 | 0.656226E+11 | 0.00 | 13.70 |
December | 0.00 | 0.00 | 0.00 | 0.105518E+09 | 0.00 | 0.00 | 0.618401E+11 | 0.00 | 12.59 |
Annual Sum or Average | 0.00 | 0.267261E+11 | 0.00 | 0.119223E+10 | 0.00 | 0.00 | 0.629906E+12 | 0.00 | 15.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 71241880.40 | 0.00 | 0.00 | 0.179560E+11 | 0.00 | 11.97 |
Maximum of Months | 0.00 | 0.107008E+11 | 0.00 | 0.114946E+09 | 0.00 | 0.00 | 0.705775E+11 | 0.00 | 19.16 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.404017E+11 | 0.00 | 0.00 | 302483.61 | 0.00 | 0.382197E+10 | 0.124145E+10 | 0.00 | 3.06 |
February | 0.336176E+11 | 0.00 | 0.00 | 1080946.45 | 0.00 | 0.655438E+10 | 0.279304E+10 | 0.00 | 3.06 |
March | 0.309786E+11 | 0.00 | 0.00 | 1933384.42 | 0.00 | 0.00 | 0.605270E+10 | 0.00 | 3.18 |
April | 0.222852E+11 | 0.246047E+09 | 0.00 | 4645791.63 | 39852393.71 | 0.00 | 0.112569E+11 | 0.00 | 3.43 |
May | 0.141770E+11 | 0.224071E+09 | 0.00 | 5821988.46 | 0.188938E+09 | 0.00 | 0.152644E+11 | 0.00 | 4.20 |
June | 0.690421E+10 | 0.207972E+10 | 0.00 | 6983582.97 | 0.112462E+10 | 0.00 | 0.100316E+11 | 0.00 | 4.14 |
July | 0.261692E+10 | 0.355798E+10 | 0.00 | 7521899.95 | 0.190470E+10 | 0.00 | 0.813515E+10 | 0.00 | 4.31 |
August | 0.264074E+10 | 0.290950E+10 | 0.00 | 11626756.34 | 0.180264E+10 | 0.00 | 0.119545E+11 | 0.00 | 4.29 |
September | 0.110929E+11 | 0.291652E+09 | 0.00 | 13429630.83 | 34999908.88 | 0.00 | 0.155638E+11 | 0.00 | 4.04 |
October | 0.226071E+11 | 0.00 | 0.00 | 8260259.15 | 0.00 | 0.00 | 0.165761E+11 | 0.00 | 3.43 |
November | 0.309902E+11 | 0.00 | 0.00 | 2814031.25 | 0.00 | 0.255691E+09 | 0.661524E+10 | 0.00 | 3.24 |
December | 0.319968E+11 | 0.00 | 0.00 | 887465.85 | 0.00 | 0.209178E+10 | 0.169162E+10 | 0.00 | 3.04 |
Annual Sum or Average | 0.250309E+12 | 0.930898E+10 | 0.00 | 65308220.92 | 0.509575E+10 | 0.127238E+11 | 0.107177E+12 | 0.00 | 3.62 |
Minimum of Months | 0.261692E+10 | 0.00 | 0.00 | 302483.61 | 0.00 | 0.00 | 0.124145E+10 | 0.00 | 3.04 |
Maximum of Months | 0.404017E+11 | 0.355798E+10 | 0.00 | 13429630.83 | 0.190470E+10 | 0.655438E+10 | 0.165761E+11 | 0.00 | 4.31 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122706E+12 | 0.00 | 0.00 | 34790.83 | 0.00 | 0.426696E+10 | 0.330089E+09 | 0.00 | 1.24 |
February | 0.997805E+11 | 0.00 | 0.00 | 192607.24 | 0.00 | 0.192071E+11 | 0.129581E+10 | 0.00 | 1.24 |
March | 0.942427E+11 | 0.00 | 0.00 | 2202359.78 | 0.00 | 0.00 | 0.944813E+10 | 0.00 | 1.29 |
April | 0.715139E+11 | 0.242559E+09 | 0.00 | 12639483.99 | 0.545040E+09 | 0.00 | 0.224681E+11 | 0.00 | 1.39 |
May | 0.385818E+11 | 0.100271E+09 | 0.00 | 25402101.37 | 0.105615E+10 | 0.00 | 0.439173E+11 | 0.00 | 1.71 |
June | 0.177629E+11 | 0.321626E+10 | 0.00 | 37910289.52 | 0.582052E+10 | 0.00 | 0.298817E+11 | 0.00 | 1.69 |
July | 0.557635E+10 | 0.784928E+10 | 0.00 | 40318332.47 | 0.768200E+10 | 0.00 | 0.247481E+11 | 0.00 | 1.77 |
August | 0.673588E+10 | 0.634304E+10 | 0.00 | 52551815.66 | 0.709011E+10 | 0.00 | 0.346976E+11 | 0.00 | 1.76 |
September | 0.302912E+11 | 0.511252E+09 | 0.00 | 44698303.74 | 0.361585E+09 | 0.00 | 0.448593E+11 | 0.00 | 1.65 |
October | 0.718939E+11 | 0.00 | 0.00 | 13412769.89 | 0.00 | 0.00 | 0.377156E+11 | 0.00 | 1.38 |
November | 0.904074E+11 | 0.00 | 0.00 | 4611890.40 | 0.00 | 0.00 | 0.154378E+11 | 0.00 | 1.31 |
December | 0.100006E+12 | 0.00 | 0.00 | 3982.67 | 0.00 | 0.00 | 0.157930E+09 | 0.00 | 1.23 |
Annual Sum or Average | 0.749499E+12 | 0.182627E+11 | 0.00 | 0.233979E+09 | 0.225554E+11 | 0.234741E+11 | 0.264957E+12 | 0.00 | 1.47 |
Minimum of Months | 0.557635E+10 | 0.00 | 0.00 | 3982.67 | 0.00 | 0.00 | 0.157930E+09 | 0.00 | 1.23 |
Maximum of Months | 0.122706E+12 | 0.784928E+10 | 0.00 | 52551815.66 | 0.768200E+10 | 0.192071E+11 | 0.448593E+11 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 46057619.14 | 0.00 | 0.00 | 62555.61 | 0.00 | 0.244074E+10 | 3637373.80 | 0.00 | 0.34 |
February | 43245643.81 | 0.00 | 0.00 | 514830.61 | 0.00 | 0.202072E+10 | 53168379.20 | 0.00 | 0.34 |
March | 71602980.11 | 0.00 | 0.00 | 1713599.20 | 0.00 | 0.118838E+10 | 0.251201E+09 | 0.00 | 0.34 |
April | 49868562.81 | 21408913.61 | 0.00 | 5290030.72 | 0.00 | 0.666904E+09 | 0.543019E+09 | 0.00 | 0.34 |
May | 24759764.30 | 26611839.05 | 45444.90 | 9912692.04 | 0.00 | 76571962.91 | 0.885419E+09 | 3868.99 | 0.34 |
June | 13686117.12 | 0.297433E+09 | 82810.81 | 7575450.38 | 0.00 | 35177352.27 | 0.425558E+09 | 6903.26 | 0.34 |
July | 1812329.52 | 0.493651E+09 | 167598.12 | 5845141.96 | 0.00 | 528903.33 | 0.199607E+09 | 23716.44 | 0.34 |
August | 0.00 | 0.345100E+09 | 294209.29 | 7785225.05 | 0.00 | 512225.19 | 0.333904E+09 | 20636.67 | 0.34 |
September | 21832875.90 | 55677823.41 | 23555.95 | 7968018.80 | 0.00 | 0.185891E+09 | 0.659568E+09 | 5940.73 | 0.34 |
October | 64605795.15 | 0.00 | 0.00 | 3750779.30 | 0.00 | 0.758479E+09 | 0.576935E+09 | 0.00 | 0.34 |
November | 58237444.51 | 0.00 | 0.00 | 796328.55 | 0.00 | 0.134354E+10 | 0.186970E+09 | 0.00 | 0.34 |
December | 43961193.46 | 0.00 | 0.00 | 98626.33 | 0.00 | 0.166217E+10 | 6751000.64 | 0.00 | 0.34 |
Annual Sum or Average | 0.439670E+09 | 0.123988E+10 | 613619.07 | 51313278.55 | 0.00 | 0.103796E+11 | 0.412574E+10 | 61066.09 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 62555.61 | 0.00 | 512225.19 | 3637373.80 | 0.00 | 0.34 |
Maximum of Months | 71602980.11 | 0.493651E+09 | 294209.29 | 9912692.04 | 0.00 | 0.244074E+10 | 0.885419E+09 | 23716.44 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3983445.83 | 0.00 | 0.00 | 3676.56 | 0.00 | 0.248588E+10 | 332718.62 | 0.00 | 0.34 |
February | 22621087.71 | 0.00 | 0.00 | 199653.40 | 0.00 | 0.207279E+10 | 21791308.23 | 0.00 | 0.34 |
March | 73714918.87 | 0.00 | 0.00 | 756354.23 | 0.00 | 0.129257E+10 | 0.145679E+09 | 0.00 | 0.34 |
April | 0.103072E+09 | 19670615.71 | 9527.35 | 3267556.65 | 1719022.28 | 0.743703E+09 | 0.414892E+09 | 7239.91 | 0.34 |
May | 0.157295E+09 | 19337518.32 | 26808.52 | 6783115.89 | 7289879.18 | 86944907.27 | 0.745523E+09 | 3823.18 | 0.34 |
June | 90513809.28 | 0.263014E+09 | 225591.63 | 4988125.10 | 34234904.90 | 38186213.80 | 0.348253E+09 | 13719.96 | 0.34 |
July | 79046478.57 | 0.407413E+09 | 252735.57 | 3908582.42 | 86100372.56 | 222593.99 | 0.124591E+09 | 18326.17 | 0.34 |
August | 0.109126E+09 | 0.288138E+09 | 327598.02 | 4837195.06 | 56887601.89 | 480663.77 | 0.227718E+09 | 21177.58 | 0.34 |
September | 0.134090E+09 | 50010061.43 | 38415.97 | 4584938.12 | 5647270.57 | 0.225773E+09 | 0.510709E+09 | 5045.21 | 0.34 |
October | 0.106016E+09 | 0.00 | 0.00 | 1519485.12 | 0.00 | 0.949222E+09 | 0.346849E+09 | 0.00 | 0.34 |
November | 51260050.95 | 0.00 | 0.00 | 350883.44 | 0.00 | 0.145120E+10 | 86541800.04 | 0.00 | 0.34 |
December | 11688654.28 | 0.00 | 0.00 | 6822.00 | 0.00 | 0.170037E+10 | 716475.32 | 0.00 | 0.34 |
Annual Sum or Average | 0.942427E+09 | 0.104758E+10 | 880677.05 | 31206387.99 | 0.191879E+09 | 0.110474E+11 | 0.297360E+10 | 69332.02 | 0.34 |
Minimum of Months | 3983445.83 | 0.00 | 0.00 | 3676.56 | 0.00 | 222593.99 | 332718.62 | 0.00 | 0.34 |
Maximum of Months | 0.157295E+09 | 0.407413E+09 | 327598.02 | 6783115.89 | 86100372.56 | 0.248588E+10 | 0.745523E+09 | 21177.58 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.896181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241125E+09 | 0.00 | 0.00 | 0.02 |
February | 0.127685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
March | 0.722904E+09 | 0.00 | 0.00 | 654482.03 | 0.00 | 0.00 | 0.322183E+09 | 0.00 | 0.02 |
April | 0.608490E+09 | 54692903.99 | 0.00 | 999535.30 | 0.00 | 0.00 | 0.486449E+09 | 0.00 | 0.02 |
May | 0.190848E+09 | 0.117119E+09 | 0.00 | 1557847.26 | 0.00 | 0.00 | 0.652663E+09 | 0.00 | 0.02 |
June | 0.155725E+09 | 0.414585E+09 | 0.00 | 996891.97 | 0.00 | 0.00 | 0.226897E+09 | 0.00 | 0.02 |
July | 0.00 | 0.680353E+09 | 0.00 | 489227.01 | 0.00 | 0.00 | 76453984.93 | 0.00 | 0.02 |
August | 0.00 | 0.575280E+09 | 0.00 | 834470.59 | 0.00 | 0.00 | 79491793.97 | 0.00 | 0.02 |
September | 0.225786E+09 | 85607994.77 | 0.00 | 2106070.40 | 0.00 | 0.00 | 0.554104E+09 | 0.00 | 0.02 |
October | 0.460144E+09 | 0.00 | 0.00 | 3045743.71 | 0.00 | 0.00 | 0.922922E+09 | 0.00 | 0.02 |
November | 0.911588E+09 | 0.00 | 0.00 | 780868.33 | 0.00 | 35278301.84 | 0.236225E+09 | 0.00 | 0.02 |
December | 0.719428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199423E+09 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.616794E+10 | 0.192764E+10 | 0.00 | 11465136.60 | 0.00 | 0.475827E+09 | 0.355739E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.127685E+10 | 0.680353E+09 | 0.00 | 3045743.71 | 0.00 | 0.241125E+09 | 0.922922E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.606748E+09 | 0.00 | 0.00 | 267688.07 | 0.00 | 0.330161E+11 | 0.154997E+09 | 0.00 | 0.39 |
February | 0.767158E+09 | 0.00 | 0.00 | 1162773.47 | 0.00 | 0.265673E+11 | 0.138565E+10 | 0.00 | 0.39 |
March | 0.126355E+10 | 0.00 | 0.00 | 12854032.29 | 0.00 | 0.116943E+11 | 0.754840E+10 | 0.00 | 0.39 |
April | 0.151786E+10 | 0.231703E+09 | 199542.77 | 35530323.43 | 58436075.51 | 0.380557E+10 | 0.117991E+11 | 25971.29 | 0.39 |
May | 0.226822E+10 | 0.210827E+09 | 19559.85 | 92215847.40 | 0.150745E+09 | 19568280.62 | 0.111376E+11 | 7740.48 | 0.39 |
June | 0.128458E+10 | 0.352830E+10 | 481006.67 | 67749927.10 | 0.506455E+09 | 6945539.34 | 0.517796E+10 | 7748.03 | 0.39 |
July | 0.109965E+10 | 0.537631E+10 | 997639.06 | 48112224.36 | 0.132058E+10 | 185986.48 | 0.167031E+10 | 2405.25 | 0.39 |
August | 0.154327E+10 | 0.363790E+10 | 734138.88 | 58941369.76 | 0.104612E+10 | 760586.63 | 0.303824E+10 | 42843.55 | 0.39 |
September | 0.190129E+10 | 0.638186E+09 | 331931.68 | 63089093.11 | 0.116995E+09 | 0.103917E+09 | 0.980269E+10 | 34707.21 | 0.39 |
October | 0.143804E+10 | 0.00 | 0.00 | 31137423.39 | 0.00 | 0.191885E+10 | 0.156510E+11 | 0.00 | 0.39 |
November | 0.102373E+10 | 0.00 | 0.00 | 11959233.60 | 0.00 | 0.138897E+11 | 0.663331E+10 | 0.00 | 0.39 |
December | 0.922424E+09 | 0.00 | 0.00 | 354123.65 | 0.00 | 0.221510E+11 | 0.159097E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.156365E+11 | 0.136232E+11 | 2763818.91 | 0.423374E+09 | 0.319934E+10 | 0.113174E+12 | 0.741584E+11 | 121415.81 | 0.39 |
Minimum of Months | 0.606748E+09 | 0.00 | 0.00 | 267688.07 | 0.00 | 185986.48 | 0.154997E+09 | 0.00 | 0.39 |
Maximum of Months | 0.226822E+10 | 0.537631E+10 | 997639.06 | 92215847.40 | 0.132058E+10 | 0.330161E+11 | 0.156510E+11 | 42843.55 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 38909522.26 | 0.00 | 0.00 | 25267.84 | 0.00 | 0.244048E+10 | 11076013.55 | 0.00 | 0.34 |
February | 39868625.50 | 0.00 | 0.00 | 375401.62 | 0.00 | 0.202616E+10 | 51245630.00 | 0.00 | 0.34 |
March | 65986451.84 | 0.00 | 0.00 | 1430839.60 | 0.00 | 0.115947E+10 | 0.286012E+09 | 0.00 | 0.34 |
April | 36744702.61 | 21408913.61 | 0.00 | 4391405.04 | 0.00 | 0.709622E+09 | 0.514324E+09 | 0.00 | 0.34 |
May | 13754598.51 | 26660070.10 | 418.99 | 10296067.04 | 0.00 | 63071432.43 | 0.909541E+09 | 663.85 | 0.34 |
June | 8368708.07 | 0.297445E+09 | 77329.05 | 7944150.93 | 0.00 | 22717193.44 | 0.442967E+09 | 474.50 | 0.34 |
July | 1812329.52 | 0.493626E+09 | 212561.47 | 6150478.54 | 0.00 | 272763.30 | 0.199558E+09 | 3979.55 | 0.34 |
August | 0.00 | 0.345160E+09 | 248496.87 | 7482012.76 | 0.00 | 337565.35 | 0.334382E+09 | 6563.71 | 0.34 |
September | 17199880.96 | 55707320.10 | 0.00 | 8133855.38 | 0.00 | 0.181466E+09 | 0.668460E+09 | 0.00 | 0.34 |
October | 49490963.23 | 0.00 | 0.00 | 3263052.78 | 0.00 | 0.770702E+09 | 0.580314E+09 | 0.00 | 0.34 |
November | 57046735.89 | 0.00 | 0.00 | 714240.27 | 0.00 | 0.133438E+10 | 0.197403E+09 | 0.00 | 0.34 |
December | 39674115.62 | 0.00 | 0.00 | 102700.76 | 0.00 | 0.164452E+10 | 28689113.07 | 0.00 | 0.34 |
Annual Sum or Average | 0.368857E+09 | 0.124001E+10 | 538806.38 | 50309472.58 | 0.00 | 0.103532E+11 | 0.422397E+10 | 11681.62 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 25267.84 | 0.00 | 272763.30 | 11076013.55 | 0.00 | 0.34 |
Maximum of Months | 65986451.84 | 0.493626E+09 | 248496.87 | 10296067.04 | 0.00 | 0.244048E+10 | 0.909541E+09 | 6563.71 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4338963.85 | 0.00 | 0.00 | 5278.52 | 0.00 | 0.248509E+10 | 767137.58 | 0.00 | 0.34 |
February | 19759057.16 | 0.00 | 0.00 | 87410.20 | 0.00 | 0.207805E+10 | 19504533.67 | 0.00 | 0.34 |
March | 75502136.14 | 0.00 | 0.00 | 519152.15 | 0.00 | 0.128195E+10 | 0.154743E+09 | 0.00 | 0.34 |
April | 99369604.97 | 19933358.93 | 9052.98 | 2493057.09 | 1459789.10 | 0.778910E+09 | 0.384161E+09 | 4204.23 | 0.34 |
May | 0.137198E+09 | 19899454.41 | 0.00 | 7375720.84 | 6758574.79 | 74405351.31 | 0.777567E+09 | 0.00 | 0.34 |
June | 84302811.11 | 0.264520E+09 | 192262.70 | 5213892.92 | 32766380.41 | 25482701.26 | 0.366941E+09 | 9281.91 | 0.34 |
July | 77479147.63 | 0.411098E+09 | 134317.60 | 3943361.83 | 82545703.08 | 286157.48 | 0.126060E+09 | 5969.50 | 0.34 |
August | 0.108155E+09 | 0.290106E+09 | 353663.00 | 4445786.43 | 54903098.07 | 585182.45 | 0.228976E+09 | 11240.28 | 0.34 |
September | 0.126992E+09 | 50433737.67 | 3831.45 | 4763044.41 | 5263032.72 | 0.213696E+09 | 0.529706E+09 | 191.33 | 0.34 |
October | 0.106016E+09 | 0.00 | 0.00 | 979167.18 | 0.00 | 0.955356E+09 | 0.341256E+09 | 0.00 | 0.34 |
November | 46166032.92 | 0.00 | 0.00 | 141090.28 | 0.00 | 0.145941E+10 | 83636886.38 | 0.00 | 0.34 |
December | 4835804.90 | 0.00 | 0.00 | 10694.31 | 0.00 | 0.170442E+10 | 3520564.45 | 0.00 | 0.34 |
Annual Sum or Average | 0.890115E+09 | 0.105599E+10 | 693127.73 | 29977656.15 | 0.183697E+09 | 0.110576E+11 | 0.301684E+10 | 30887.26 | 0.34 |
Minimum of Months | 4338963.85 | 0.00 | 0.00 | 5278.52 | 0.00 | 286157.48 | 767137.58 | 0.00 | 0.34 |
Maximum of Months | 0.137198E+09 | 0.411098E+09 | 353663.00 | 7375720.84 | 82545703.08 | 0.248509E+10 | 0.777567E+09 | 11240.28 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.695234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249266E+11 | 0.00 | 0.00 | 0.34 |
February | 0.148927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152284E+11 | 0.00 | 0.00 | 0.34 |
March | 0.234181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254849E+10 | 0.00 | 0.00 | 0.35 |
April | 0.230353E+11 | 0.00 | 0.00 | 0.00 | 0.197215E+09 | 0.485864E+09 | 0.00 | 0.00 | 0.38 |
May | 0.206475E+11 | 0.00 | 0.00 | 0.00 | 0.289590E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.117527E+11 | 0.179347E+09 | 0.00 | 303951.01 | 0.206720E+10 | 0.00 | 0.127360E+09 | 0.00 | 0.46 |
July | 0.745213E+10 | 0.388747E+09 | 0.00 | 57416.18 | 0.344144E+10 | 0.00 | 92115789.24 | 0.00 | 0.48 |
August | 0.102289E+11 | 80517152.33 | 0.00 | 13166.90 | 0.322239E+10 | 0.00 | 12643526.70 | 0.00 | 0.47 |
September | 0.186750E+11 | 0.00 | 0.00 | 713.09 | 0.218514E+09 | 0.00 | 14278400.71 | 0.00 | 0.44 |
October | 0.274467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
November | 0.202599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624683E+10 | 0.00 | 0.00 | 0.36 |
December | 0.126886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123942E+11 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.197450E+12 | 0.648611E+09 | 0.00 | 375247.19 | 0.943635E+10 | 0.618305E+11 | 0.246398E+09 | 0.00 | 0.40 |
Minimum of Months | 0.695234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.274467E+11 | 0.388747E+09 | 0.00 | 303951.01 | 0.344144E+10 | 0.249266E+11 | 0.127360E+09 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4610834.77 | 0.00 | 0.00 | 11181.80 | 0.00 | 0.617269E+09 | 732694.75 | 0.00 | 0.34 |
February | 7559566.94 | 0.00 | 0.00 | 118951.85 | 0.00 | 0.514191E+09 | 7543891.16 | 0.00 | 0.34 |
March | 17827463.63 | 0.00 | 0.00 | 383080.50 | 0.00 | 0.320153E+09 | 39860718.71 | 0.00 | 0.34 |
April | 11535832.29 | 5352228.40 | 0.00 | 1319194.93 | 0.00 | 0.194460E+09 | 0.108955E+09 | 0.00 | 0.34 |
May | 5585643.57 | 6664388.86 | 65.07 | 2386304.40 | 0.00 | 49153139.01 | 0.192041E+09 | 834.31 | 0.34 |
June | 3196864.29 | 74356793.21 | 21914.61 | 1828183.89 | 0.00 | 25817816.31 | 89656446.36 | 2008.16 | 0.34 |
July | 453082.38 | 0.123411E+09 | 43148.18 | 1375076.86 | 0.00 | 121024.26 | 49999108.72 | 6494.36 | 0.34 |
August | 0.00 | 86274088.46 | 73912.95 | 1820966.20 | 0.00 | 144667.55 | 83584736.79 | 5715.07 | 0.34 |
September | 6152904.59 | 13919455.85 | 5390.49 | 1818636.94 | 0.00 | 79657442.02 | 0.131186E+09 | 1983.68 | 0.34 |
October | 17362341.66 | 0.00 | 0.00 | 874621.73 | 0.00 | 0.237625E+09 | 95080886.79 | 0.00 | 0.34 |
November | 12446379.09 | 0.00 | 0.00 | 179157.20 | 0.00 | 0.363984E+09 | 20776451.47 | 0.00 | 0.34 |
December | 8815456.60 | 0.00 | 0.00 | 17977.01 | 0.00 | 0.418626E+09 | 786375.54 | 0.00 | 0.34 |
Annual Sum or Average | 95546369.82 | 0.309978E+09 | 144431.29 | 12133333.31 | 0.00 | 0.282120E+10 | 0.820203E+09 | 17035.59 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 11181.80 | 0.00 | 121024.26 | 732694.75 | 0.00 | 0.34 |
Maximum of Months | 17827463.63 | 0.123411E+09 | 73912.95 | 2386304.40 | 0.00 | 0.617269E+09 | 0.192041E+09 | 6494.36 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 276582.97 | 0.00 | 0.00 | 1148.35 | 0.00 | 0.622244E+09 | 29020.91 | 0.00 | 0.34 |
February | 3023622.61 | 0.00 | 0.00 | 33927.83 | 0.00 | 0.521780E+09 | 4513754.50 | 0.00 | 0.34 |
March | 14035793.37 | 0.00 | 0.00 | 149299.03 | 0.00 | 0.343483E+09 | 20511276.58 | 0.00 | 0.34 |
April | 24900892.27 | 4917653.93 | 2715.21 | 804570.66 | 429755.57 | 0.205438E+09 | 85090157.81 | 1476.60 | 0.34 |
May | 37504017.07 | 4895948.39 | 6112.38 | 1669152.71 | 1762123.38 | 46170573.28 | 0.163793E+09 | 323.14 | 0.34 |
June | 22019293.13 | 65755358.77 | 55654.72 | 1269111.79 | 8558100.10 | 26443860.61 | 70752927.07 | 2887.61 | 0.34 |
July | 19299153.48 | 0.101867E+09 | 50035.88 | 996356.26 | 21525093.14 | 50031.70 | 31596664.28 | 4073.00 | 0.34 |
August | 27237425.65 | 72030108.67 | 84639.58 | 1197644.78 | 14221900.47 | 119897.12 | 56985379.51 | 6950.15 | 0.34 |
September | 33449454.75 | 12501069.51 | 9194.98 | 1019335.08 | 1411817.64 | 86324590.87 | 97995932.46 | 3116.15 | 0.34 |
October | 26403091.32 | 0.00 | 0.00 | 307382.01 | 0.00 | 0.270495E+09 | 53696261.54 | 0.00 | 0.34 |
November | 10679156.49 | 0.00 | 0.00 | 77152.69 | 0.00 | 0.380401E+09 | 6181637.33 | 0.00 | 0.34 |
December | 737254.54 | 0.00 | 0.00 | 476.79 | 0.00 | 0.427378E+09 | 80249.87 | 0.00 | 0.34 |
Annual Sum or Average | 0.219566E+09 | 0.261967E+09 | 208352.76 | 7525557.97 | 47908790.30 | 0.293033E+10 | 0.591226E+09 | 18826.66 | 0.34 |
Minimum of Months | 276582.97 | 0.00 | 0.00 | 476.79 | 0.00 | 50031.70 | 29020.91 | 0.00 | 0.34 |
Maximum of Months | 37504017.07 | 0.101867E+09 | 84639.58 | 1669152.71 | 21525093.14 | 0.622244E+09 | 0.163793E+09 | 6950.15 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100665E+09 | 0.00 | 0.00 | 1065015.98 | 0.00 | 0.370919E+10 | 0.189120E+09 | 0.00 | 0.39 |
February | 0.128247E+09 | 0.00 | 0.00 | 2200427.68 | 0.00 | 0.294847E+10 | 0.322294E+09 | 0.00 | 0.39 |
March | 60497869.95 | 0.00 | 0.00 | 4305244.15 | 0.00 | 0.164970E+10 | 0.715396E+09 | 0.00 | 0.39 |
April | 43122218.89 | 34385334.33 | 0.00 | 7503568.84 | 0.00 | 0.945869E+09 | 0.103538E+10 | 0.00 | 0.39 |
May | 25629119.23 | 42819334.05 | 1410.99 | 13072561.75 | 0.00 | 99068791.86 | 0.146299E+10 | 328.19 | 0.39 |
June | 11686929.38 | 0.476296E+09 | 31770.68 | 9028974.71 | 1529639.13 | 25035770.95 | 0.728395E+09 | 767.93 | 0.39 |
July | 2910822.93 | 0.793084E+09 | 84748.50 | 6548728.89 | 0.00 | 664653.72 | 0.323617E+09 | 2337.96 | 0.39 |
August | 0.00 | 0.554192E+09 | 48370.84 | 9576973.33 | 536429.34 | 3417577.81 | 0.536623E+09 | 1644.56 | 0.39 |
September | 23146313.78 | 89448426.57 | 23153.43 | 12320320.49 | 0.00 | 0.197022E+09 | 0.117329E+10 | 1191.06 | 0.39 |
October | 46667508.04 | 0.00 | 0.00 | 10066489.30 | 0.00 | 0.682843E+09 | 0.151505E+10 | 0.00 | 0.39 |
November | 59505480.88 | 0.00 | 0.00 | 3466341.09 | 0.00 | 0.178039E+10 | 0.709638E+09 | 0.00 | 0.39 |
December | 34864361.82 | 0.00 | 0.00 | 1707624.44 | 0.00 | 0.249260E+10 | 0.222094E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.536942E+09 | 0.199023E+10 | 189454.44 | 80862270.64 | 2066068.48 | 0.145343E+11 | 0.893389E+10 | 6269.71 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1065015.98 | 0.00 | 664653.72 | 0.189120E+09 | 0.00 | 0.39 |
Maximum of Months | 0.128247E+09 | 0.793084E+09 | 84748.50 | 13072561.75 | 1529639.13 | 0.370919E+10 | 0.151505E+10 | 2337.96 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.521297E+11 | 0.00 | 0.00 | 6246752.51 | 0.00 | 0.408906E+10 | 0.236243E+11 | 0.00 | 3.98 |
February | 0.397786E+11 | 0.00 | 0.00 | 8683455.77 | 0.00 | 0.106080E+11 | 0.250511E+11 | 0.00 | 3.98 |
March | 0.271238E+11 | 0.00 | 0.00 | 15937421.86 | 0.00 | 0.00 | 0.379004E+11 | 0.00 | 4.14 |
April | 0.190045E+11 | 0.350516E+09 | 0.00 | 22901474.68 | 0.143461E+09 | 0.00 | 0.399235E+11 | 0.00 | 4.47 |
May | 0.863517E+10 | 0.570201E+09 | 0.00 | 35573558.41 | 0.155152E+09 | 0.00 | 0.431958E+11 | 0.00 | 5.50 |
June | 0.378422E+10 | 0.474148E+10 | 0.00 | 34809323.60 | 0.908924E+09 | 0.00 | 0.261492E+11 | 0.00 | 5.44 |
July | 0.127606E+10 | 0.834971E+10 | 0.00 | 31976330.77 | 0.133885E+10 | 0.00 | 0.177275E+11 | 0.00 | 5.66 |
August | 0.155454E+10 | 0.691472E+10 | 0.00 | 36046460.36 | 0.142592E+10 | 0.00 | 0.243008E+11 | 0.00 | 5.63 |
September | 0.884526E+10 | 0.420481E+09 | 0.00 | 34144470.30 | 0.126844E+09 | 0.00 | 0.380485E+11 | 0.00 | 5.25 |
October | 0.219085E+11 | 0.00 | 0.00 | 22093429.31 | 0.00 | 0.00 | 0.468170E+11 | 0.00 | 4.44 |
November | 0.320019E+11 | 0.00 | 0.00 | 14752975.94 | 0.00 | 0.00 | 0.343764E+11 | 0.00 | 4.22 |
December | 0.357289E+11 | 0.00 | 0.00 | 8694019.45 | 0.00 | 0.00 | 0.270889E+11 | 0.00 | 3.96 |
Annual Sum or Average | 0.251771E+12 | 0.213471E+11 | 0.00 | 0.271860E+09 | 0.409915E+10 | 0.146971E+11 | 0.384203E+12 | 0.00 | 4.73 |
Minimum of Months | 0.127606E+10 | 0.00 | 0.00 | 6246752.51 | 0.00 | 0.00 | 0.177275E+11 | 0.00 | 3.96 |
Maximum of Months | 0.521297E+11 | 0.834971E+10 | 0.00 | 36046460.36 | 0.142592E+10 | 0.106080E+11 | 0.468170E+11 | 0.00 | 5.66 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.485491E+11 | 0.00 | 0.00 | 10329255.02 | 0.00 | 0.254597E+10 | 0.287311E+11 | 0.00 | 3.99 |
February | 0.367599E+11 | 0.00 | 0.00 | 13391340.28 | 0.00 | 0.873411E+10 | 0.299270E+11 | 0.00 | 3.98 |
March | 0.210406E+11 | 0.00 | 0.00 | 23618220.38 | 0.00 | 0.00 | 0.439798E+11 | 0.00 | 4.14 |
April | 0.136918E+11 | 0.406680E+09 | 0.00 | 31669205.37 | 87337381.02 | 0.00 | 0.453531E+11 | 0.00 | 4.49 |
May | 0.439147E+10 | 0.616668E+09 | 0.00 | 45761730.45 | 0.108576E+09 | 0.00 | 0.477522E+11 | 0.00 | 5.53 |
June | 0.188680E+10 | 0.510523E+10 | 0.00 | 42835864.87 | 0.580462E+09 | 0.00 | 0.282741E+11 | 0.00 | 5.49 |
July | 0.657854E+09 | 0.894236E+10 | 0.00 | 38689220.39 | 0.842035E+09 | 0.00 | 0.184957E+11 | 0.00 | 5.71 |
August | 0.991748E+09 | 0.743606E+10 | 0.00 | 43410875.20 | 0.968070E+09 | 0.00 | 0.250870E+11 | 0.00 | 5.67 |
September | 0.549446E+10 | 0.458713E+09 | 0.00 | 43360109.20 | 88529714.55 | 0.00 | 0.416152E+11 | 0.00 | 5.28 |
October | 0.155572E+11 | 0.00 | 0.00 | 31046625.14 | 0.00 | 0.00 | 0.532342E+11 | 0.00 | 4.45 |
November | 0.261191E+11 | 0.00 | 0.00 | 21531239.56 | 0.00 | 0.00 | 0.402907E+11 | 0.00 | 4.22 |
December | 0.310607E+11 | 0.00 | 0.00 | 13746977.89 | 0.00 | 0.00 | 0.317420E+11 | 0.00 | 3.96 |
Annual Sum or Average | 0.206201E+12 | 0.229657E+11 | 0.00 | 0.359391E+09 | 0.267501E+10 | 0.112801E+11 | 0.434482E+12 | 0.00 | 4.75 |
Minimum of Months | 0.657854E+09 | 0.00 | 0.00 | 10329255.02 | 0.00 | 0.00 | 0.184957E+11 | 0.00 | 3.96 |
Maximum of Months | 0.485491E+11 | 0.894236E+10 | 0.00 | 45761730.45 | 0.968070E+09 | 0.873411E+10 | 0.532342E+11 | 0.00 | 5.71 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 56264115.37 | 0.00 | 0.00 | 0.102335E+09 | 0.00 | 0.00 | 0.648175E+11 | 0.00 | 11.23 |
February | 0.411345E+09 | 0.00 | 0.00 | 93296976.08 | 0.00 | 0.00 | 0.603679E+11 | 0.00 | 11.48 |
March | 0.00 | 0.00 | 0.00 | 0.106412E+09 | 0.00 | 0.00 | 0.635539E+11 | 0.00 | 13.32 |
April | 0.00 | 0.633178E+09 | 0.00 | 0.105318E+09 | 0.00 | 0.00 | 0.583925E+11 | 0.00 | 14.98 |
May | 0.00 | 0.929251E+09 | 0.00 | 0.120089E+09 | 0.00 | 0.00 | 0.514116E+11 | 0.00 | 19.30 |
June | 0.00 | 0.697304E+10 | 0.00 | 89757995.24 | 0.00 | 0.00 | 0.287846E+11 | 0.00 | 18.79 |
July | 0.00 | 0.116566E+11 | 0.00 | 73496092.01 | 0.00 | 0.00 | 0.169748E+11 | 0.00 | 19.47 |
August | 0.00 | 0.101380E+11 | 0.00 | 86146284.76 | 0.00 | 0.00 | 0.235356E+11 | 0.00 | 19.42 |
September | 0.00 | 0.695213E+09 | 0.00 | 0.117143E+09 | 0.00 | 0.00 | 0.459385E+11 | 0.00 | 18.07 |
October | 0.00 | 0.00 | 0.00 | 0.108273E+09 | 0.00 | 0.00 | 0.682203E+11 | 0.00 | 14.95 |
November | 0.00 | 0.00 | 0.00 | 0.100810E+09 | 0.00 | 0.00 | 0.628521E+11 | 0.00 | 13.28 |
December | 0.00 | 0.00 | 0.00 | 0.103591E+09 | 0.00 | 0.00 | 0.580886E+11 | 0.00 | 11.82 |
Annual Sum or Average | 0.467609E+09 | 0.310253E+11 | 0.00 | 0.120667E+10 | 0.00 | 0.00 | 0.602938E+12 | 0.00 | 15.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 73496092.01 | 0.00 | 0.00 | 0.169748E+11 | 0.00 | 11.23 |
Maximum of Months | 0.411345E+09 | 0.116566E+11 | 0.00 | 0.120089E+09 | 0.00 | 0.00 | 0.682203E+11 | 0.00 | 19.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.710119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943492E+10 | 0.00 | 0.00 | 0.37 |
February | 0.272624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753255E+10 | 0.00 | 0.00 | 0.39 |
March | 0.508048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179539E+10 | 0.00 | 0.00 | 0.35 |
April | 0.547195E+10 | 86739514.96 | 0.00 | 1051113.40 | 1017615.47 | 0.332751E+09 | 0.499278E+09 | 0.00 | 0.40 |
May | 0.407794E+10 | 0.133743E+09 | 0.00 | 3064909.37 | 0.00 | 0.00 | 0.149849E+10 | 0.00 | 0.51 |
June | 0.144772E+10 | 0.115587E+10 | 0.00 | 7956751.02 | 799684.48 | 0.00 | 0.209393E+10 | 0.00 | 0.65 |
July | 0.281255E+09 | 0.186950E+10 | 0.00 | 8214270.60 | 0.00 | 0.00 | 0.205593E+10 | 0.00 | 0.72 |
August | 0.451368E+09 | 0.151206E+10 | 0.00 | 9098631.69 | 3802020.45 | 0.00 | 0.269368E+10 | 0.00 | 0.66 |
September | 0.323942E+10 | 0.121867E+09 | 0.00 | 7146672.30 | 0.00 | 0.00 | 0.200718E+10 | 0.00 | 0.55 |
October | 0.726780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
November | 0.438110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286420E+10 | 0.00 | 0.00 | 0.36 |
December | 0.120056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564447E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.363360E+11 | 0.487978E+10 | 0.00 | 36532348.38 | 5619320.40 | 0.276043E+11 | 0.108485E+11 | 0.00 | 0.47 |
Minimum of Months | 0.281255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.726780E+10 | 0.186950E+10 | 0.00 | 9098631.69 | 3802020.45 | 0.943492E+10 | 0.269368E+10 | 0.00 | 0.72 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.217591E+12 | 0.145117E+11 | 0.398328E+12 | 0.103696E+13 | 0.116905E+12 |
February | 0.244948E+12 | 0.112114E+11 | 0.310648E+12 | 0.808312E+12 | 0.109092E+12 |
March | 0.408575E+12 | 0.948233E+10 | 0.262202E+12 | 0.722796E+12 | 0.871778E+11 |
April | 0.480337E+12 | 0.660210E+10 | 0.179125E+12 | 0.526456E+12 | 0.157822E+12 |
May | 0.549099E+12 | 0.398960E+10 | 0.101435E+12 | 0.381995E+12 | 0.267218E+12 |
June | 0.572758E+12 | 0.964725E+09 | 0.226522E+11 | 0.140150E+12 | 0.595091E+12 |
July | 0.555982E+12 | -490712635.9 | -0.173831E+11 | 0.143929E+11 | 0.814611E+12 |
August | 0.501927E+12 | 0.219893E+09 | -519974367.2 | 0.846265E+11 | 0.713962E+12 |
September | 0.345538E+12 | 0.356739E+10 | 0.923049E+11 | 0.346048E+12 | 0.344534E+12 |
October | 0.255788E+12 | 0.661307E+10 | 0.181162E+12 | 0.547870E+12 | 0.112982E+12 |
November | 0.157469E+12 | 0.918818E+10 | 0.258486E+12 | 0.714241E+12 | 0.885408E+11 |
December | 0.112070E+12 | 0.127409E+11 | 0.352910E+12 | 0.939541E+12 | 0.842196E+11 |